Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2018-10-19 10:15:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2745.94 | 684.16 | 737.15 |
Net Site Energy | 2745.94 | 684.16 | 737.15 |
Total Source Energy | 6656.66 | 1658.53 | 1786.98 |
Net Source Energy | 6656.66 | 1658.53 | 1786.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 29.18 | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 374.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 415.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 290.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 544.34 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1766.71 | 979.23 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 29.18 | 13.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 374.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 415.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 290.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 544.34 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 186.32 | 149.73 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 474.27 | 262.87 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 172.93 | 138.96 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 440.18 | 243.98 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1766.71 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1766.71 | 100.00 |
Total On-Site and Utility Electric Sources | 1766.71 | 100.00 |
Total Electricity End Uses | 1766.71 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 133.75 |
Time Setpoint Not Met During Occupied Cooling | 4511.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5242.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 96.82 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 87.38 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6780.66 | 5151.80 | 1628.86 | 0.76 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18805.51 | 13596.03 | 5209.48 | 0.72 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9693.82 | 6740.69 | 2953.13 | 0.70 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14822.31 | 11283.78 | 3538.53 | 0.76 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6496.3 | 3.22 | 10.99 | 11.64 | 10.88 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18104.8 | 3.29 | 11.22 | 11.89 | 11.23 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9366.6 | 3.34 | 11.40 | 12.08 | 11.50 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14197.9 | 3.22 | 10.98 | 11.63 | 10.87 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 17053.67 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 792.05 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 792.05 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 844.65 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 830.58 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2246.31 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 810.72 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2510.92 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 841.46 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 800.57 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2246.31 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 850.34 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2510.92 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3168.22 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 908.83 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 859.76 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 792.00 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3167.99 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 814.71 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.74 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2653.07 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1075.31 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3353.10 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2753.64 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3358.51 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1169.81 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1119.12 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3329.79 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 905.57 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3289.90 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1078.48 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 278.67 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3261.33 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 13669.78 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 7320.07 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5547.82 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.37 | 410.30 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.90 | 998.89 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.42 | 471.65 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.80 | 890.56 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7908.97 | 9490.76 | 0.752 | 0.902 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
RESTROOMFLR1 | 483.09 | 579.71 | 0.046 | 0.055 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 36.80 | 0.00682 |
MEETINGROOMFLR1 | 3688.57 | 4426.28 | 0.351 | 0.421 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM101 | 629.60 | 755.52 | 0.083 | 0.100 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 37.06 | 0.00682 |
GUESTROOM102 | 523.58 | 628.30 | 0.069 | 0.083 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32 | 0.00682 |
GUESTROOM103 | 1149.40 | 1379.28 | 0.152 | 0.182 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
GUESTROOM104 | 1229.63 | 1475.56 | 0.162 | 0.195 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
GUESTROOM105 | 1538.69 | 1846.43 | 0.203 | 0.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
EMPLOYEELOUNGEFLR1 | 5373.75 | 6448.50 | 0.511 | 0.613 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
EXERCISECENTERFLR1 | 1194.30 | 1433.16 | 0.113 | 0.136 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
FRONTOFFICEFLR1 | 3213.81 | 3856.57 | 0.305 | 0.366 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM201 | 871.20 | 1045.44 | 0.115 | 0.138 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
GUESTROOM202_205 | 4248.05 | 5097.66 | 0.561 | 0.673 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32 | 0.00682 |
GUESTROOM206_208 | 3444.79 | 4133.75 | 0.455 | 0.546 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 37.52 | 0.00682 |
GUESTROOM209_212 | 4058.01 | 4869.61 | 0.536 | 0.643 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32 | 0.00682 |
GUESTROOM213 | 1184.70 | 1421.63 | 0.156 | 0.188 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
GUESTROOM214 | 1320.88 | 1585.05 | 0.174 | 0.209 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71 | 0.00682 |
GUESTROOM215_218 | 9453.55 | 11344.26 | 1.248 | 1.498 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM219 | 5399.24 | 6479.08 | 0.713 | 0.856 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
GUESTROOM220_223 | 4466.16 | 5359.39 | 0.590 | 0.708 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
GUESTROOM224 | 1299.38 | 1559.25 | 0.172 | 0.206 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM301 | 696.61 | 835.93 | 0.092 | 0.110 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM302_305 | 1670.86 | 2005.04 | 0.221 | 0.265 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM306_308 | 1461.70 | 1754.04 | 0.193 | 0.232 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM309_312 | 4011.04 | 4813.25 | 0.530 | 0.636 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 35.95 | 0.00682 |
GUESTROOM313 | 683.36 | 820.04 | 0.090 | 0.108 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
GUESTROOM314 | 1240.84 | 1489.00 | 0.164 | 0.197 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 37.32 | 0.00682 |
GUESTROOM315_318 | 4855.28 | 5826.34 | 0.641 | 0.769 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM319 | 1078.33 | 1293.99 | 0.142 | 0.171 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM320_323 | 4249.07 | 5098.88 | 0.561 | 0.673 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM324 | 731.88 | 878.26 | 0.097 | 0.116 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 37.91 | 0.00682 |
GUESTROOM401 | 1511.70 | 1814.04 | 0.200 | 0.240 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 38.10 | 0.00682 |
GUESTROOM402_405 | 2342.81 | 2811.38 | 0.309 | 0.371 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
GUESTROOM406_408 | 2012.59 | 2415.11 | 0.266 | 0.319 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
GUESTROOM409_412 | 4984.84 | 5981.81 | 0.658 | 0.790 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
GUESTROOM413 | 917.39 | 1100.86 | 0.121 | 0.145 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71 | 0.00682 |
GUESTROOM414 | 993.47 | 1192.16 | 0.131 | 0.157 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 38.10 | 0.00682 |
GUESTROOM415_418 | 5348.41 | 6418.10 | 0.706 | 0.848 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
GUESTROOM419 | 1481.48 | 1777.77 | 0.196 | 0.235 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10 | 0.00682 |
GUESTROOM420_423 | 5317.59 | 6381.11 | 0.702 | 0.843 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 38.10 | 0.00682 |
GUESTROOM424 | 1531.82 | 1838.19 | 0.202 | 0.243 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 38.10 | 0.00682 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR1 | 17041.40 | 20449.69 | 1.618 | 1.942 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 34.98 | 0.00682 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR2 | 2729.86 | 3275.83 | 0.259 | 0.311 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 36.54 | 0.00682 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR3 | 1317.97 | 1581.56 | 0.125 | 0.150 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 36.28 | 0.00682 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 | |
CORRIDORFLR4 | 2092.19 | 2510.63 | 0.199 | 0.238 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 37.71 | 0.00682 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 0.00682 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1356.16 | 1627.40 | 0.044 | 0.236 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | -5.20 | 0.00281 |
RESTROOMFLR1 | 67.91 | 81.49 | 0.002 | 0.003 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
MEETINGROOMFLR1 | 451.63 | 541.95 | 0.015 | 0.126 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -5.20 | 0.00281 |
GUESTROOM101 | 189.20 | 227.04 | 0.006 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
GUESTROOM102 | 231.83 | 278.20 | 0.008 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
GUESTROOM103 | 389.26 | 467.12 | 0.013 | 0.015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -5.20 | 0.00281 |
GUESTROOM104 | 377.56 | 453.08 | 0.012 | 0.015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -5.20 | 0.00281 |
GUESTROOM105 | 229.75 | 275.70 | 0.007 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.20 | 0.00281 |
EMPLOYEELOUNGEFLR1 | 201.47 | 241.76 | 0.007 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20 | 0.00281 |
EXERCISECENTERFLR1 | 122.63 | 147.16 | 0.004 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -5.20 | 0.00281 |
FRONTOFFICEFLR1 | 822.51 | 987.01 | 0.027 | 0.056 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -5.20 | 0.00281 |
GUESTROOM201 | 360.99 | 433.19 | 0.012 | 0.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -5.20 | 0.00281 |
GUESTROOM202_205 | 773.96 | 928.76 | 0.025 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -5.20 | 0.00281 |
GUESTROOM206_208 | 595.76 | 714.92 | 0.019 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -5.20 | 0.00281 |
GUESTROOM209_212 | 691.69 | 830.03 | 0.022 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM213 | 386.61 | 463.93 | 0.013 | 0.015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -5.20 | 0.00281 |
GUESTROOM214 | 352.56 | 423.07 | 0.011 | 0.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 10:15:00 | -5.20 | 0.00281 |
GUESTROOM215_218 | 661.56 | 793.87 | 0.022 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM219 | 139.97 | 167.96 | 0.005 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -5.20 | 0.00281 |
GUESTROOM220_223 | 647.18 | 776.62 | 0.021 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -5.20 | 0.00281 |
GUESTROOM224 | 305.13 | 366.16 | 0.010 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | -5.20 | 0.00281 |
GUESTROOM301 | 394.01 | 472.81 | 0.013 | 0.015 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -5.20 | 0.00281 |
GUESTROOM302_305 | 875.62 | 1050.74 | 0.028 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -5.20 | 0.00281 |
GUESTROOM306_308 | 745.76 | 894.91 | 0.024 | 0.043 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:45:00 | -5.20 | 0.00281 |
GUESTROOM309_312 | 867.31 | 1040.77 | 0.028 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -5.20 | 0.00281 |
GUESTROOM313 | 442.75 | 531.30 | 0.014 | 0.017 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | -5.20 | 0.00281 |
GUESTROOM314 | 401.88 | 482.25 | 0.013 | 0.016 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:45:00 | -5.20 | 0.00281 |
GUESTROOM315_318 | 841.14 | 1009.37 | 0.027 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20 | 0.00281 |
GUESTROOM319 | 222.65 | 267.18 | 0.007 | 0.013 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -5.20 | 0.00281 |
GUESTROOM320_323 | 810.78 | 972.93 | 0.026 | 0.054 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -5.20 | 0.00281 |
GUESTROOM324 | 364.34 | 437.21 | 0.012 | 0.014 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 20:15:00 | -5.20 | 0.00281 |
GUESTROOM401 | 581.48 | 697.78 | 0.019 | 0.023 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | -5.20 | 0.00281 |
GUESTROOM402_405 | 1535.81 | 1842.98 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -5.20 | 0.00281 |
GUESTROOM406_408 | 1297.34 | 1556.81 | 0.042 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -5.20 | 0.00281 |
GUESTROOM409_412 | 1540.32 | 1848.39 | 0.050 | 0.060 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -5.20 | 0.00281 |
GUESTROOM413 | 660.24 | 792.28 | 0.021 | 0.026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20 | 0.00281 |
GUESTROOM414 | 618.01 | 741.61 | 0.020 | 0.024 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | -5.20 | 0.00281 |
GUESTROOM415_418 | 1516.48 | 1819.77 | 0.049 | 0.059 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -5.20 | 0.00281 |
GUESTROOM419 | 440.05 | 528.06 | 0.014 | 0.017 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -5.20 | 0.00281 |
GUESTROOM420_423 | 1483.23 | 1779.88 | 0.048 | 0.058 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -5.20 | 0.00281 |
GUESTROOM424 | 584.14 | 700.97 | 0.019 | 0.023 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20 | 0.00281 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR1 | 13136.12 | 15763.34 | 0.427 | 0.512 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR2 | 282.53 | 339.03 | 0.009 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR3 | 471.89 | 566.26 | 0.015 | 0.038 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 | |
CORRIDORFLR4 | 1318.66 | 1582.40 | 0.043 | 0.051 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:45:00 | -5.20 | 0.00281 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00281 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.37 | 0.37 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.90 | 0.90 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.42 | 0.42 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.80 | 0.80 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.90 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 2087.25 | 6053.75 | 768.25 |
RESTROOMFLR1 | 488.75 | 6529.25 | 58.25 |
MEETINGROOMFLR1 | 1292.00 | 2682.00 | 126.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 177.50 | 8758.25 | 177.50 |
GUESTROOM104 | 24.00 | 8673.75 | 24.00 |
GUESTROOM105 | 9.25 | 8274.75 | 8.00 |
EMPLOYEELOUNGEFLR1 | 2857.25 | 2181.50 | 196.00 |
EXERCISECENTERFLR1 | 1954.75 | 1880.50 | 26.00 |
FRONTOFFICEFLR1 | 1333.00 | 5089.00 | 115.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 21.50 | 8357.25 | 18.75 |
GUESTROOM206_208 | 10.75 | 8359.75 | 8.00 |
GUESTROOM209_212 | 13.00 | 8497.50 | 12.25 |
GUESTROOM213 | 157.25 | 8694.75 | 157.25 |
GUESTROOM214 | 10.25 | 8395.75 | 9.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5171.00 | 3739.00 | 971.00 |
GUESTROOM220_223 | 15.50 | 8235.25 | 12.75 |
GUESTROOM224 | 7.75 | 8337.00 | 7.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 51.50 | 8651.00 | 51.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 14.50 | 8403.25 | 14.00 |
GUESTROOM315_318 | 19.75 | 8049.50 | 9.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 26.25 | 8410.25 | 25.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1535.50 | 7788.75 | 1274.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 611.25 | 7788.00 | 315.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 607.00 | 7290.00 | 69.00 |
GUESTROOM419 | 320.50 | 7630.75 | 46.75 |
GUESTROOM420_423 | 591.00 | 7371.00 | 87.75 |
GUESTROOM424 | 477.50 | 7717.00 | 196.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7129.25 | 8760.00 | 5242.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 1154.00 | 0.00 | 1154.00 |
MEETINGROOMFLR1 | 0.00 | 0.25 | 0.00 | 0.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.25 | 39.75 | 0.25 | 39.75 |
GUESTROOM104 | 0.00 | 45.50 | 0.00 | 45.50 |
GUESTROOM105 | 0.00 | 54.25 | 0.00 | 54.25 |
EMPLOYEELOUNGEFLR1 | 178.50 | 1150.75 | 131.25 | 566.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 25.50 | 0.00 | 25.50 |
GUESTROOM206_208 | 0.00 | 34.00 | 0.00 | 34.00 |
GUESTROOM209_212 | 0.00 | 22.50 | 0.00 | 22.50 |
GUESTROOM213 | 0.25 | 27.25 | 0.25 | 27.25 |
GUESTROOM214 | 0.00 | 34.75 | 0.00 | 34.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 3698.75 | 0.00 | 3698.75 |
GUESTROOM220_223 | 0.00 | 28.75 | 0.00 | 28.75 |
GUESTROOM224 | 0.00 | 34.75 | 0.00 | 34.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 18.75 | 0.00 | 18.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 33.75 | 0.00 | 33.75 |
GUESTROOM315_318 | 0.00 | 32.00 | 0.00 | 32.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 26.75 | 0.00 | 26.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.75 | 39.50 | 0.75 | 39.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.25 | 33.75 | 0.25 | 33.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 39.00 | 0.00 | 39.00 |
GUESTROOM419 | 1.00 | 44.50 | 1.00 | 44.50 |
GUESTROOM420_423 | 0.25 | 38.50 | 0.25 | 38.50 |
GUESTROOM424 | 0.00 | 42.50 | 0.00 | 42.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 5004.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 329.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 417.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 181.00 | 6312.75 | 133.75 | 4511.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.366306 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.902211 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.804365 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR1 PTAC HEATING COIL | 17053.67 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 792.05 |
102 PTAC HEATING COIL | 792.05 |
103 PTAC HEATING COIL | 844.65 |
104 PTAC HEATING COIL | 830.58 |
105 PTAC HEATING COIL | 792.00 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR2 PTAC HEATING COIL | 2246.31 |
201 PTAC HEATING COIL | 810.72 |
202_205 PTAC HEATING COIL | 3168.22 |
206_208 PTAC HEATING COIL | 2510.92 |
209_212 PTAC HEATING COIL | 3168.22 |
213 PTAC HEATING COIL | 841.46 |
214 PTAC HEATING COIL | 800.57 |
215_218 PTAC HEATING COIL | 3167.99 |
219 PTAC HEATING COIL | 792.00 |
220_223 PTAC HEATING COIL | 3167.99 |
224 PTAC HEATING COIL | 792.00 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR3 PTAC HEATING COIL | 2246.31 |
301 PTAC HEATING COIL | 850.34 |
302_305 PTAC HEATING COIL | 3168.22 |
306_308 PTAC HEATING COIL | 2510.92 |
309_312 PTAC HEATING COIL | 3168.22 |
313 PTAC HEATING COIL | 908.83 |
314 PTAC HEATING COIL | 859.76 |
315_318 PTAC HEATING COIL | 3167.99 |
319 PTAC HEATING COIL | 792.00 |
320_323 PTAC HEATING COIL | 3167.99 |
324 PTAC HEATING COIL | 814.71 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 278.67 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 278.74 |
CORRIDORFLR4 PTAC HEATING COIL | 2653.07 |
401 PTAC HEATING COIL | 1075.31 |
402_405 PTAC HEATING COIL | 3353.10 |
406_408 PTAC HEATING COIL | 2753.64 |
409_412 PTAC HEATING COIL | 3358.51 |
413 PTAC HEATING COIL | 1169.81 |
414 PTAC HEATING COIL | 1119.12 |
415_418 PTAC HEATING COIL | 3329.79 |
419 PTAC HEATING COIL | 905.57 |
420_423 PTAC HEATING COIL | 3289.90 |
424 PTAC HEATING COIL | 1078.48 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 278.67 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.759779 | 0.366306 | 6780.66 |
SAC_FRONTLOUNGE COOLING COIL | 0.722981 | 0.902211 | 18805.51 |
SAC_MEETINGROOM COOLING COIL | 0.695359 | 0.421073 | 9693.82 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.761270 | 0.804365 | 14822.31 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.902211 |
RESTROOMFLR1 DIRECT AIR | 0.055053 |
MEETINGROOMFLR1 DIRECT AIR | 0.421073 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.613131 |
EXERCISECENTERFLR1 DIRECT AIR | 0.136181 |
FRONTOFFICEFLR1 DIRECT AIR | 0.366306 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.366306 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.902211 |
SAC_MEETINGROOM MAIN BRANCH | 0.421073 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.804365 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.366306 |
SAC_FRONTLOUNGE | 0.902211 |
SAC_MEETINGROOM | 0.421073 |
SAC_EXC_EMPLGE_RESTRM | 0.804365 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.366306 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.902211 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.421073 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.804365 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.366306 | 0.366306 | 0.366306 | 0.366306 | 3261.33 | 6780.66 | 1.00 |
SAC_FRONTLOUNGE | 0.902211 | 0.902211 | 0.902211 | 0.902211 | 13669.78 | 18805.51 | 1.00 |
SAC_MEETINGROOM | 0.421073 | 0.421073 | 0.421073 | 0.421073 | 7320.07 | 9693.82 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.804365 | 0.804365 | 0.804365 | 0.804365 | 5547.82 | 14822.31 | 0.169302 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3261.33 |
SAC_FRONTLOUNGE HEATING COIL | 13669.78 |
SAC_MEETINGROOM HEATING COIL | 7320.07 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5547.82 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.421073 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.32 | 8.14 |
February | 20.78 | 10.27 |
March | 21.34 | 12.55 |
April | 23.13 | 19.23 |
May | 24.41 | 23.84 |
June | 25.52 | 27.86 |
July | 25.44 | 27.54 |
August | 25.17 | 26.28 |
September | 24.71 | 23.38 |
October | 23.30 | 18.30 |
November | 21.40 | 11.18 |
December | 20.30 | 6.79 |
Annual Sum or Average | 23.00 | 17.98 |
Minimum of Months | 20.30 | 6.79 |
Maximum of Months | 25.52 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.57 | 8.14 |
February | 23.84 | 10.27 |
March | 24.15 | 12.55 |
April | 25.15 | 19.23 |
May | 25.96 | 23.84 |
June | 26.76 | 27.86 |
July | 26.95 | 27.54 |
August | 26.62 | 26.28 |
September | 26.20 | 23.38 |
October | 25.19 | 18.30 |
November | 24.04 | 11.18 |
December | 23.47 | 6.79 |
Annual Sum or Average | 25.17 | 17.98 |
Minimum of Months | 23.47 | 6.79 |
Maximum of Months | 26.95 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 8.14 |
February | 19.89 | 10.27 |
March | 20.64 | 12.55 |
April | 22.55 | 19.23 |
May | 23.94 | 23.84 |
June | 25.04 | 27.86 |
July | 24.93 | 27.54 |
August | 24.56 | 26.28 |
September | 23.93 | 23.38 |
October | 22.47 | 18.30 |
November | 20.45 | 11.18 |
December | 19.30 | 6.79 |
Annual Sum or Average | 22.27 | 17.98 |
Minimum of Months | 19.30 | 6.79 |
Maximum of Months | 25.04 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | 8.14 |
February | 21.88 | 10.27 |
March | 22.28 | 12.55 |
April | 23.24 | 19.23 |
May | 23.69 | 23.84 |
June | 23.87 | 27.86 |
July | 23.88 | 27.54 |
August | 23.85 | 26.28 |
September | 23.69 | 23.38 |
October | 23.14 | 18.30 |
November | 22.05 | 11.18 |
December | 21.38 | 6.79 |
Annual Sum or Average | 22.87 | 17.98 |
Minimum of Months | 21.38 | 6.79 |
Maximum of Months | 23.88 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 8.14 |
February | 22.40 | 10.27 |
March | 22.69 | 12.55 |
April | 23.25 | 19.23 |
May | 23.60 | 23.84 |
June | 23.81 | 27.86 |
July | 23.81 | 27.54 |
August | 23.71 | 26.28 |
September | 23.53 | 23.38 |
October | 23.21 | 18.30 |
November | 22.54 | 11.18 |
December | 22.10 | 6.79 |
Annual Sum or Average | 23.07 | 17.98 |
Minimum of Months | 22.10 | 6.79 |
Maximum of Months | 23.81 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 8.14 |
February | 22.72 | 10.27 |
March | 23.07 | 12.55 |
April | 23.60 | 19.23 |
May | 23.82 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.88 | 23.38 |
October | 23.69 | 18.30 |
November | 22.95 | 11.18 |
December | 22.22 | 6.79 |
Annual Sum or Average | 23.33 | 17.98 |
Minimum of Months | 22.22 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.84 | 8.14 |
February | 25.11 | 10.27 |
March | 25.44 | 12.55 |
April | 26.17 | 19.23 |
May | 27.64 | 23.84 |
June | 30.35 | 27.86 |
July | 31.67 | 27.54 |
August | 31.51 | 26.28 |
September | 30.12 | 23.38 |
October | 27.48 | 18.30 |
November | 25.45 | 11.18 |
December | 24.79 | 6.79 |
Annual Sum or Average | 27.56 | 17.98 |
Minimum of Months | 24.79 | 6.79 |
Maximum of Months | 31.67 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 8.14 |
February | 21.31 | 10.27 |
March | 21.85 | 12.55 |
April | 22.86 | 19.23 |
May | 23.26 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.32 | 23.38 |
October | 22.97 | 18.30 |
November | 21.63 | 11.18 |
December | 20.62 | 6.79 |
Annual Sum or Average | 22.39 | 17.98 |
Minimum of Months | 20.62 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | 8.14 |
February | 20.97 | 10.27 |
March | 21.52 | 12.55 |
April | 22.66 | 19.23 |
May | 23.17 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.20 | 23.38 |
October | 22.68 | 18.30 |
November | 21.28 | 11.18 |
December | 20.27 | 6.79 |
Annual Sum or Average | 22.19 | 17.98 |
Minimum of Months | 20.27 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 8.14 |
February | 21.34 | 10.27 |
March | 21.47 | 12.55 |
April | 21.69 | 19.23 |
May | 21.75 | 23.84 |
June | 21.75 | 27.86 |
July | 21.76 | 27.54 |
August | 21.75 | 26.28 |
September | 21.75 | 23.38 |
October | 21.71 | 18.30 |
November | 21.44 | 11.18 |
December | 21.15 | 6.79 |
Annual Sum or Average | 21.56 | 17.98 |
Minimum of Months | 21.15 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 8.14 |
February | 21.64 | 10.27 |
March | 21.65 | 12.55 |
April | 21.73 | 19.23 |
May | 21.75 | 23.84 |
June | 21.75 | 27.86 |
July | 21.76 | 27.54 |
August | 21.75 | 26.28 |
September | 21.75 | 23.38 |
October | 21.74 | 18.30 |
November | 21.66 | 11.18 |
December | 21.59 | 6.79 |
Annual Sum or Average | 21.70 | 17.98 |
Minimum of Months | 21.59 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 8.14 |
February | 21.73 | 10.27 |
March | 21.73 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.73 | 11.18 |
December | 21.71 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.71 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 8.14 |
February | 22.42 | 10.27 |
March | 22.55 | 12.55 |
April | 22.62 | 19.23 |
May | 22.52 | 23.84 |
June | 22.28 | 27.86 |
July | 22.25 | 27.54 |
August | 22.29 | 26.28 |
September | 22.32 | 23.38 |
October | 22.52 | 18.30 |
November | 22.40 | 11.18 |
December | 22.28 | 6.79 |
Annual Sum or Average | 22.40 | 17.98 |
Minimum of Months | 22.25 | 6.79 |
Maximum of Months | 22.62 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.84 | 8.14 |
February | 51.96 | 10.27 |
March | 52.04 | 12.55 |
April | 52.48 | 19.23 |
May | 52.79 | 23.84 |
June | 53.25 | 27.86 |
July | 53.33 | 27.54 |
August | 53.30 | 26.28 |
September | 53.29 | 23.38 |
October | 52.88 | 18.30 |
November | 52.25 | 11.18 |
December | 51.84 | 6.79 |
Annual Sum or Average | 52.61 | 17.98 |
Minimum of Months | 51.84 | 6.79 |
Maximum of Months | 53.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.10 | 8.14 |
February | 69.25 | 10.27 |
March | 69.37 | 12.55 |
April | 69.99 | 19.23 |
May | 70.43 | 23.84 |
June | 71.07 | 27.86 |
July | 71.21 | 27.54 |
August | 71.13 | 26.28 |
September | 71.08 | 23.38 |
October | 70.40 | 18.30 |
November | 69.57 | 11.18 |
December | 69.15 | 6.79 |
Annual Sum or Average | 70.15 | 17.98 |
Minimum of Months | 69.10 | 6.79 |
Maximum of Months | 71.21 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 8.14 |
February | 23.41 | 10.27 |
March | 23.55 | 12.55 |
April | 23.81 | 19.23 |
May | 23.89 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.88 | 23.38 |
October | 23.85 | 18.30 |
November | 23.50 | 11.18 |
December | 23.22 | 6.79 |
Annual Sum or Average | 23.67 | 17.98 |
Minimum of Months | 23.22 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.10 | 8.14 |
February | 23.27 | 10.27 |
March | 23.45 | 12.55 |
April | 23.80 | 19.23 |
May | 23.89 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.89 | 23.38 |
October | 23.86 | 18.30 |
November | 23.43 | 11.18 |
December | 22.96 | 6.79 |
Annual Sum or Average | 23.61 | 17.98 |
Minimum of Months | 22.96 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.13 | 8.14 |
February | 20.76 | 10.27 |
March | 21.36 | 12.55 |
April | 23.47 | 19.23 |
May | 24.94 | 23.84 |
June | 26.27 | 27.86 |
July | 26.15 | 27.54 |
August | 25.89 | 26.28 |
September | 25.33 | 23.38 |
October | 23.59 | 18.30 |
November | 21.41 | 11.18 |
December | 20.11 | 6.79 |
Annual Sum or Average | 23.30 | 17.98 |
Minimum of Months | 20.11 | 6.79 |
Maximum of Months | 26.27 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.87 | 8.14 |
February | 22.22 | 10.27 |
March | 22.56 | 12.55 |
April | 23.69 | 19.23 |
May | 24.48 | 23.84 |
June | 25.22 | 27.86 |
July | 25.18 | 27.54 |
August | 25.07 | 26.28 |
September | 24.80 | 23.38 |
October | 23.91 | 18.30 |
November | 22.67 | 11.18 |
December | 21.82 | 6.79 |
Annual Sum or Average | 23.63 | 17.98 |
Minimum of Months | 21.82 | 6.79 |
Maximum of Months | 25.22 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | 8.14 |
February | 21.03 | 10.27 |
March | 21.67 | 12.55 |
April | 23.69 | 19.23 |
May | 25.11 | 23.84 |
June | 26.32 | 27.86 |
July | 26.20 | 27.54 |
August | 25.89 | 26.28 |
September | 25.37 | 23.38 |
October | 23.80 | 18.30 |
November | 21.68 | 11.18 |
December | 20.50 | 6.79 |
Annual Sum or Average | 23.49 | 17.98 |
Minimum of Months | 20.50 | 6.79 |
Maximum of Months | 26.32 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 8.14 |
February | 23.45 | 10.27 |
March | 23.66 | 12.55 |
April | 23.87 | 19.23 |
May | 23.89 | 23.84 |
June | 23.97 | 27.86 |
July | 23.97 | 27.54 |
August | 23.93 | 26.28 |
September | 23.90 | 23.38 |
October | 23.89 | 18.30 |
November | 23.58 | 11.18 |
December | 23.07 | 6.79 |
Annual Sum or Average | 23.70 | 17.98 |
Minimum of Months | 23.07 | 6.79 |
Maximum of Months | 23.97 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.92 | 8.14 |
February | 19.59 | 10.27 |
March | 20.52 | 12.55 |
April | 22.83 | 19.23 |
May | 24.47 | 23.84 |
June | 25.73 | 27.86 |
July | 25.58 | 27.54 |
August | 25.16 | 26.28 |
September | 24.43 | 23.38 |
October | 22.70 | 18.30 |
November | 20.23 | 11.18 |
December | 18.82 | 6.79 |
Annual Sum or Average | 22.43 | 17.98 |
Minimum of Months | 18.82 | 6.79 |
Maximum of Months | 25.73 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.93 | 8.14 |
February | 20.75 | 10.27 |
March | 21.55 | 12.55 |
April | 22.92 | 19.23 |
May | 23.29 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.29 | 23.38 |
October | 22.87 | 18.30 |
November | 21.04 | 11.18 |
December | 19.74 | 6.79 |
Annual Sum or Average | 22.12 | 17.98 |
Minimum of Months | 19.74 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 8.14 |
February | 21.51 | 10.27 |
March | 21.64 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.58 | 11.18 |
December | 21.29 | 6.79 |
Annual Sum or Average | 21.64 | 17.98 |
Minimum of Months | 21.29 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | 8.14 |
February | 21.55 | 10.27 |
March | 21.65 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.61 | 11.18 |
December | 21.35 | 6.79 |
Annual Sum or Average | 21.65 | 17.98 |
Minimum of Months | 21.35 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.46 | 8.14 |
February | 21.58 | 10.27 |
March | 21.67 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.64 | 11.18 |
December | 21.41 | 6.79 |
Annual Sum or Average | 21.67 | 17.98 |
Minimum of Months | 21.41 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 8.14 |
February | 21.37 | 10.27 |
March | 21.53 | 12.55 |
April | 21.72 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.74 | 18.30 |
November | 21.47 | 11.18 |
December | 21.14 | 6.79 |
Annual Sum or Average | 21.58 | 17.98 |
Minimum of Months | 21.14 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 8.14 |
February | 21.70 | 10.27 |
March | 21.71 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.65 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.65 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 8.14 |
February | 23.31 | 10.27 |
March | 23.32 | 12.55 |
April | 23.33 | 19.23 |
May | 23.33 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.33 | 23.38 |
October | 23.33 | 18.30 |
November | 23.33 | 11.18 |
December | 23.28 | 6.79 |
Annual Sum or Average | 23.32 | 17.98 |
Minimum of Months | 23.28 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.97 | 8.14 |
February | 32.18 | 10.27 |
March | 32.37 | 12.55 |
April | 32.97 | 19.23 |
May | 33.35 | 23.84 |
June | 33.80 | 27.86 |
July | 33.87 | 27.54 |
August | 33.79 | 26.28 |
September | 33.71 | 23.38 |
October | 33.23 | 18.30 |
November | 32.45 | 11.18 |
December | 31.93 | 6.79 |
Annual Sum or Average | 32.97 | 17.98 |
Minimum of Months | 31.93 | 6.79 |
Maximum of Months | 33.87 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.14 | 8.14 |
February | 22.19 | 10.27 |
March | 22.26 | 12.55 |
April | 22.57 | 19.23 |
May | 22.88 | 23.84 |
June | 23.28 | 27.86 |
July | 23.47 | 27.54 |
August | 23.32 | 26.28 |
September | 23.17 | 23.38 |
October | 22.78 | 18.30 |
November | 22.29 | 11.18 |
December | 22.08 | 6.79 |
Annual Sum or Average | 22.71 | 17.98 |
Minimum of Months | 22.08 | 6.79 |
Maximum of Months | 23.47 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 8.14 |
February | 21.73 | 10.27 |
March | 21.73 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.72 | 11.18 |
December | 21.69 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.69 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 8.14 |
February | 21.70 | 10.27 |
March | 21.71 | 12.55 |
April | 21.75 | 19.23 |
May | 21.76 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.70 | 11.18 |
December | 21.65 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.65 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 8.14 |
February | 22.01 | 10.27 |
March | 22.45 | 12.55 |
April | 23.89 | 19.23 |
May | 24.87 | 23.84 |
June | 25.73 | 27.86 |
July | 25.64 | 27.54 |
August | 25.49 | 26.28 |
September | 25.15 | 23.38 |
October | 24.03 | 18.30 |
November | 22.49 | 11.18 |
December | 21.47 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 21.47 | 6.79 |
Maximum of Months | 25.73 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.98 | 8.14 |
February | 20.77 | 10.27 |
March | 21.57 | 12.55 |
April | 24.11 | 19.23 |
May | 25.90 | 23.84 |
June | 27.46 | 27.86 |
July | 27.27 | 27.54 |
August | 26.94 | 26.28 |
September | 26.25 | 23.38 |
October | 24.11 | 18.30 |
November | 21.49 | 11.18 |
December | 19.94 | 6.79 |
Annual Sum or Average | 23.83 | 17.98 |
Minimum of Months | 19.94 | 6.79 |
Maximum of Months | 27.46 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.95 | 8.14 |
February | 20.58 | 10.27 |
March | 21.34 | 12.55 |
April | 23.66 | 19.23 |
May | 25.25 | 23.84 |
June | 26.57 | 27.86 |
July | 26.44 | 27.54 |
August | 26.10 | 26.28 |
September | 25.51 | 23.38 |
October | 23.74 | 18.30 |
November | 21.28 | 11.18 |
December | 19.90 | 6.79 |
Annual Sum or Average | 23.37 | 17.98 |
Minimum of Months | 19.90 | 6.79 |
Maximum of Months | 26.57 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 8.14 |
February | 22.44 | 10.27 |
March | 22.93 | 12.55 |
April | 23.70 | 19.23 |
May | 23.88 | 23.84 |
June | 23.89 | 27.86 |
July | 23.89 | 27.54 |
August | 23.89 | 26.28 |
September | 23.88 | 23.38 |
October | 23.73 | 18.30 |
November | 22.70 | 11.18 |
December | 21.79 | 6.79 |
Annual Sum or Average | 23.22 | 17.98 |
Minimum of Months | 21.79 | 6.79 |
Maximum of Months | 23.89 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.96 | 8.14 |
February | 18.82 | 10.27 |
March | 19.96 | 12.55 |
April | 22.81 | 19.23 |
May | 24.72 | 23.84 |
June | 26.13 | 27.86 |
July | 25.96 | 27.54 |
August | 25.50 | 26.28 |
September | 24.67 | 23.38 |
October | 22.62 | 18.30 |
November | 19.52 | 11.18 |
December | 17.80 | 6.79 |
Annual Sum or Average | 22.22 | 17.98 |
Minimum of Months | 17.80 | 6.79 |
Maximum of Months | 26.13 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.32 | 8.14 |
February | 20.15 | 10.27 |
March | 21.02 | 12.55 |
April | 22.74 | 19.23 |
May | 23.26 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.26 | 23.38 |
October | 22.63 | 18.30 |
November | 20.43 | 11.18 |
December | 19.23 | 6.79 |
Annual Sum or Average | 21.84 | 17.98 |
Minimum of Months | 19.23 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | 8.14 |
February | 20.30 | 10.27 |
March | 21.13 | 12.55 |
April | 22.80 | 19.23 |
May | 23.28 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.27 | 23.38 |
October | 22.72 | 18.30 |
November | 20.57 | 11.18 |
December | 19.34 | 6.79 |
Annual Sum or Average | 21.91 | 17.98 |
Minimum of Months | 19.34 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.62 | 8.14 |
February | 20.40 | 10.27 |
March | 21.21 | 12.55 |
April | 22.79 | 19.23 |
May | 23.27 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.26 | 23.38 |
October | 22.71 | 18.30 |
November | 20.67 | 11.18 |
December | 19.45 | 6.79 |
Annual Sum or Average | 21.95 | 17.98 |
Minimum of Months | 19.45 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | 8.14 |
February | 21.51 | 10.27 |
March | 21.62 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.75 | 26.28 |
September | 21.75 | 23.38 |
October | 21.74 | 18.30 |
November | 21.57 | 11.18 |
December | 21.30 | 6.79 |
Annual Sum or Average | 21.63 | 17.98 |
Minimum of Months | 21.30 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | 8.14 |
February | 20.30 | 10.27 |
March | 21.10 | 12.55 |
April | 22.76 | 19.23 |
May | 23.27 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.28 | 23.38 |
October | 22.71 | 18.30 |
November | 20.64 | 11.18 |
December | 19.40 | 6.79 |
Annual Sum or Average | 21.92 | 17.98 |
Minimum of Months | 19.40 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 8.14 |
February | 21.61 | 10.27 |
March | 21.65 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.65 | 11.18 |
December | 21.53 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 21.53 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 8.14 |
February | 21.74 | 10.27 |
March | 21.74 | 12.55 |
April | 21.75 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.73 | 11.18 |
December | 21.70 | 6.79 |
Annual Sum or Average | 21.74 | 17.98 |
Minimum of Months | 21.70 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.07 | 8.14 |
February | 24.42 | 10.27 |
March | 24.76 | 12.55 |
April | 25.63 | 19.23 |
May | 26.10 | 23.84 |
June | 26.48 | 27.86 |
July | 26.48 | 27.54 |
August | 26.41 | 26.28 |
September | 26.28 | 23.38 |
October | 25.78 | 18.30 |
November | 24.74 | 11.18 |
December | 23.98 | 6.79 |
Annual Sum or Average | 25.43 | 17.98 |
Minimum of Months | 23.98 | 6.79 |
Maximum of Months | 26.48 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 8.14 |
February | 22.89 | 10.27 |
March | 23.05 | 12.55 |
April | 23.29 | 19.23 |
May | 23.33 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.33 | 23.38 |
October | 23.32 | 18.30 |
November | 22.98 | 11.18 |
December | 22.54 | 6.79 |
Annual Sum or Average | 23.12 | 17.98 |
Minimum of Months | 22.54 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 8.14 |
February | 21.70 | 10.27 |
March | 21.71 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.75 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.69 | 11.18 |
December | 21.65 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.65 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 8.14 |
February | 21.71 | 10.27 |
March | 22.11 | 12.55 |
April | 22.99 | 19.23 |
May | 23.29 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.33 | 26.28 |
September | 23.31 | 23.38 |
October | 23.05 | 18.30 |
November | 22.02 | 11.18 |
December | 21.04 | 6.79 |
Annual Sum or Average | 22.57 | 17.98 |
Minimum of Months | 21.04 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | 8.14 |
February | 21.45 | 10.27 |
March | 22.05 | 12.55 |
April | 23.89 | 19.23 |
May | 25.09 | 23.84 |
June | 26.07 | 27.86 |
July | 25.96 | 27.54 |
August | 25.77 | 26.28 |
September | 25.35 | 23.38 |
October | 23.99 | 18.30 |
November | 22.01 | 11.18 |
December | 20.69 | 6.79 |
Annual Sum or Average | 23.60 | 17.98 |
Minimum of Months | 20.69 | 6.79 |
Maximum of Months | 26.07 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.34 | 8.14 |
February | 20.26 | 10.27 |
March | 21.21 | 12.55 |
April | 24.13 | 19.23 |
May | 26.13 | 23.84 |
June | 27.86 | 27.86 |
July | 27.64 | 27.54 |
August | 27.26 | 26.28 |
September | 26.48 | 23.38 |
October | 24.07 | 18.30 |
November | 21.03 | 11.18 |
December | 19.25 | 6.79 |
Annual Sum or Average | 23.74 | 17.98 |
Minimum of Months | 19.25 | 6.79 |
Maximum of Months | 27.86 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | 8.14 |
February | 19.74 | 10.27 |
March | 20.72 | 12.55 |
April | 23.59 | 19.23 |
May | 25.47 | 23.84 |
June | 27.05 | 27.86 |
July | 26.91 | 27.54 |
August | 26.48 | 26.28 |
September | 25.72 | 23.38 |
October | 23.56 | 18.30 |
November | 20.47 | 11.18 |
December | 18.75 | 6.79 |
Annual Sum or Average | 23.13 | 17.98 |
Minimum of Months | 18.75 | 6.79 |
Maximum of Months | 27.05 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 8.14 |
February | 21.95 | 10.27 |
March | 22.36 | 12.55 |
April | 23.31 | 19.23 |
May | 23.75 | 23.84 |
June | 23.99 | 27.86 |
July | 23.99 | 27.54 |
August | 23.93 | 26.28 |
September | 23.78 | 23.38 |
October | 23.26 | 18.30 |
November | 22.11 | 11.18 |
December | 21.48 | 6.79 |
Annual Sum or Average | 22.96 | 17.98 |
Minimum of Months | 21.48 | 6.79 |
Maximum of Months | 23.99 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.15 | 8.14 |
February | 18.15 | 10.27 |
March | 19.44 | 12.55 |
April | 22.73 | 19.23 |
May | 24.87 | 23.84 |
June | 26.51 | 27.86 |
July | 26.34 | 27.54 |
August | 25.79 | 26.28 |
September | 24.80 | 23.38 |
October | 22.41 | 18.30 |
November | 18.83 | 11.18 |
December | 16.91 | 6.79 |
Annual Sum or Average | 22.01 | 17.98 |
Minimum of Months | 16.91 | 6.79 |
Maximum of Months | 26.51 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | 8.14 |
February | 21.30 | 10.27 |
March | 21.49 | 12.55 |
April | 21.72 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.71 | 18.30 |
November | 21.39 | 11.18 |
December | 20.97 | 6.79 |
Annual Sum or Average | 21.53 | 17.98 |
Minimum of Months | 20.97 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.26 | 8.14 |
February | 19.94 | 10.27 |
March | 20.70 | 12.55 |
April | 22.41 | 19.23 |
May | 23.13 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.31 | 26.28 |
September | 23.11 | 23.38 |
October | 22.25 | 18.30 |
November | 20.15 | 11.18 |
December | 19.17 | 6.79 |
Annual Sum or Average | 21.68 | 17.98 |
Minimum of Months | 19.17 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.30 | 8.14 |
February | 19.98 | 10.27 |
March | 20.73 | 12.55 |
April | 22.39 | 19.23 |
May | 23.12 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.31 | 26.28 |
September | 23.09 | 23.38 |
October | 22.24 | 18.30 |
November | 20.18 | 11.18 |
December | 19.20 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 19.20 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.33 | 8.14 |
February | 21.51 | 10.27 |
March | 21.61 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.74 | 18.30 |
November | 21.56 | 11.18 |
December | 21.27 | 6.79 |
Annual Sum or Average | 21.63 | 17.98 |
Minimum of Months | 21.27 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.30 | 8.14 |
February | 19.98 | 10.27 |
March | 20.73 | 12.55 |
April | 22.44 | 19.23 |
May | 23.15 | 23.84 |
June | 23.32 | 27.86 |
July | 23.33 | 27.54 |
August | 23.31 | 26.28 |
September | 23.14 | 23.38 |
October | 22.33 | 18.30 |
November | 20.24 | 11.18 |
December | 19.20 | 6.79 |
Annual Sum or Average | 21.71 | 17.98 |
Minimum of Months | 19.20 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.40 | 8.14 |
February | 20.93 | 10.27 |
March | 21.39 | 12.55 |
April | 22.61 | 19.23 |
May | 23.16 | 23.84 |
June | 23.33 | 27.86 |
July | 23.33 | 27.54 |
August | 23.32 | 26.28 |
September | 23.19 | 23.38 |
October | 22.64 | 18.30 |
November | 21.18 | 11.18 |
December | 20.27 | 6.79 |
Annual Sum or Average | 22.15 | 17.98 |
Minimum of Months | 20.27 | 6.79 |
Maximum of Months | 23.33 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 8.14 |
February | 21.70 | 10.27 |
March | 21.71 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.69 | 11.18 |
December | 21.65 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.65 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 8.14 |
February | 22.18 | 10.27 |
March | 22.63 | 12.55 |
April | 23.88 | 19.23 |
May | 24.59 | 23.84 |
June | 25.19 | 27.86 |
July | 25.15 | 27.54 |
August | 25.00 | 26.28 |
September | 24.70 | 23.38 |
October | 23.87 | 18.30 |
November | 22.47 | 11.18 |
December | 21.58 | 6.79 |
Annual Sum or Average | 23.58 | 17.98 |
Minimum of Months | 21.58 | 6.79 |
Maximum of Months | 25.19 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 8.14 |
February | 21.69 | 10.27 |
March | 21.70 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.75 | 18.30 |
November | 21.68 | 11.18 |
December | 21.63 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.63 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 8.14 |
February | 21.69 | 10.27 |
March | 21.70 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.75 | 23.38 |
October | 21.75 | 18.30 |
November | 21.68 | 11.18 |
December | 21.64 | 6.79 |
Annual Sum or Average | 21.72 | 17.98 |
Minimum of Months | 21.64 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 8.14 |
February | 21.63 | 10.27 |
March | 21.65 | 12.55 |
April | 21.74 | 19.23 |
May | 21.75 | 23.84 |
June | 21.76 | 27.86 |
July | 21.76 | 27.54 |
August | 21.76 | 26.28 |
September | 21.76 | 23.38 |
October | 21.74 | 18.30 |
November | 21.63 | 11.18 |
December | 21.53 | 6.79 |
Annual Sum or Average | 21.69 | 17.98 |
Minimum of Months | 21.53 | 6.79 |
Maximum of Months | 21.76 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.21 | 8.14 |
February | 20.92 | 10.27 |
March | 21.62 | 12.55 |
April | 23.72 | 19.23 |
May | 25.07 | 23.84 |
June | 26.24 | 27.86 |
July | 26.12 | 27.54 |
August | 25.85 | 26.28 |
September | 25.28 | 23.38 |
October | 23.67 | 18.30 |
November | 21.42 | 11.18 |
December | 20.01 | 6.79 |
Annual Sum or Average | 23.35 | 17.98 |
Minimum of Months | 20.01 | 6.79 |
Maximum of Months | 26.24 | 27.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.57 | 8.14 |
February | 19.61 | 10.27 |
March | 20.70 | 12.55 |
April | 24.00 | 19.23 |
May | 26.19 | 23.84 |
June | 28.14 | 27.86 |
July | 27.93 | 27.54 |
August | 27.45 | 26.28 |
September | 26.51 | 23.38 |
October | 23.78 | 18.30 |
November | 20.35 | 11.18 |
December | 18.39 | 6.79 |
Annual Sum or Average | 23.49 | 17.98 |
Minimum of Months | 18.39 | 6.79 |
Maximum of Months | 28.14 | 27.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.134401E+12 | 89607.627 | 27-JAN-07:15 | 13316.689 | 34010.661 | 9000.173 | 32958.114 | 313.877 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.121862E+12 | 92627.098 | 02-FEB-07:15 | 15177.258 | 39465.561 | 9000.173 | 28296.851 | 679.142 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.134295E+12 | 87922.554 | 02-MAR-07:15 | 15177.258 | 39465.561 | 9000.173 | 23299.531 | 971.917 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.139183E+12 | 87556.283 | 29-APR-07:00 | 17566.637 | 43276.576 | 9471.821 | 0.000 | 17233.138 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.155623E+12 | 91387.664 | 28-MAY-07:00 | 17641.054 | 43276.576 | 9471.821 | 0.000 | 20990.101 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.163783E+12 | 94755.236 | 17-JUN-07:00 | 17641.054 | 43276.576 | 9471.821 | 0.000 | 24357.673 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.176158E+12 | 97860.751 | 22-JUL-07:00 | 17641.054 | 43276.576 | 9471.821 | 0.000 | 27463.188 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.169308E+12 | 96137.885 | 05-AUG-07:00 | 17566.637 | 43276.576 | 9471.821 | 0.000 | 25814.739 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.156977E+12 | 95019.660 | 22-SEP-07:00 | 17789.888 | 43276.576 | 9471.821 | 0.000 | 24473.263 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.147188E+12 | 86595.562 | 04-OCT-19:15 | 19529.751 | 28246.035 | 9034.026 | 0.000 | 25589.637 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.131265E+12 | 85825.937 | 10-NOV-08:00 | 17938.723 | 43276.576 | 9471.821 | 0.000 | 15130.705 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.136666E+12 | 94851.506 | 27-DEC-07:15 | 15177.258 | 39465.561 | 9000.173 | 30765.526 | 434.875 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.176671E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.121862E+12 | 85825.937 | 13316.689 | 28246.035 | 9000.173 | 0.000 | 313.877 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.176158E+12 | 97860.751 | 19529.751 | 43276.576 | 9471.821 | 32958.114 | 27463.188 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.912677E+11 | 95535.331 | 27-JAN-10:45 | 3790.113 | 40096.028 | 0.000 | 51649.189 | 51649.189 | 51649.189 | 3790.113 |
February | 0.816912E+11 | 94249.956 | 17-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 54153.928 | 54153.928 | 54153.928 | 0.000 |
March | 0.874884E+11 | 93294.139 | 03-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 53198.111 | 53198.111 | 53198.111 | 0.000 |
April | 0.803715E+11 | 90872.741 | 01-APR-08:30 | 0.000 | 40096.028 | 0.000 | 50776.713 | 50776.713 | 50776.713 | 0.000 |
May | 0.799208E+11 | 86063.354 | 02-MAY-08:00 | 0.000 | 40096.028 | 0.000 | 45967.326 | 45967.326 | 45967.326 | 0.000 |
June | 0.756589E+11 | 73584.170 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 33488.142 | 33488.142 | 33488.142 | 0.000 |
July | 0.771992E+11 | 72847.910 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 32751.882 | 32751.882 | 32751.882 | 0.000 |
August | 0.772084E+11 | 72835.146 | 28-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 32739.118 | 32739.118 | 32739.118 | 0.000 |
September | 0.756788E+11 | 73639.723 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 33543.695 | 33543.695 | 33543.695 | 0.000 |
October | 0.799677E+11 | 74718.503 | 30-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 34622.475 | 34622.475 | 34622.475 | 0.000 |
November | 0.820467E+11 | 90855.097 | 24-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 50759.069 | 50759.069 | 50759.069 | 0.000 |
December | 0.907342E+11 | 94462.623 | 30-DEC-10:00 | 2265.742 | 40096.028 | 0.000 | 52100.853 | 52100.853 | 52100.853 | 2265.742 |
Annual Sum or Average | 0.979233E+12 | 0.000 | ||||||||
Minimum of Months | 0.756589E+11 | 72835.146 | 0.000 | 40096.028 | 0.000 | 32739.118 | 32739.118 | 32739.118 | 0.000 | |
Maximum of Months | 0.912677E+11 | 95535.331 | 3790.113 | 40096.028 | 0.000 | 54153.928 | 54153.928 | 54153.928 | 3790.113 |