Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745

Simulation Timestamp: 2018-10-19 10:15:32


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2786.88 694.36 748.14
Net Site Energy 2786.88 694.36 748.14
Total Source Energy 6876.30 1713.26 1845.94
Net Source Energy 6876.30 1713.26 1845.94


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 12.29 6.24 0.00 0.00 0.00 0.00
Cooling 469.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.83 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 293.94 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 508.31 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1850.85 936.04 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 12.29 6.24 0.00 0.00 0.00 0.00
Cooling General 469.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.83 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 293.94 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 508.31 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 129.95 0.00 0.00 0.00 0.00 0.00
HVAC 208.25 138.13 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 496.86 251.28 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 120.61 0.00 0.00 0.00 0.00 0.00
HVAC 193.28 128.20 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 461.15 233.22 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1850.85 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1850.85 100.00
     
Total On-Site and Utility Electric Sources 1850.85 100.00
Total Electricity End Uses 1850.85 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 66.25
Time Setpoint Not Met During Occupied Cooling 4958.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 4552.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Weather File Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Latitude [deg] 32.17
Longitude [deg] -110.9
Elevation [m] 809.00
Time Zone -7.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 0.50 0.00 0.50 Wetbulb [C] 2.10 140.00
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 40.80 13.30 18.50 Wetbulb [C] 4.80 310.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.55 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 4.600 0.293 0.130     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 4.44 0.00 0.00 4.44 4.44 4.600 0.293 0.130     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 4.600 0.293 0.130     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 4.600 0.293 0.130              
North Total or Average           96.82 4.600 0.293 0.130              
Non-North Total or Average           87.38 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7839.69 5875.65 1964.05 0.75 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   20694.12 14769.21 5924.90 0.71 3.80    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   10302.28 7065.28 3237.00 0.69 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   15502.00 11541.79 3960.21 0.74 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7521.2 3.24 11.05 11.71 10.98
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 19947.5 3.22 10.99 11.66 11.06
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 9967.1 3.36 11.46 12.15 11.60
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 14881.9 3.25 11.08 11.74 11.02
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.78 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   20635.54 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   743.50 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   743.50 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   776.68 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   761.56 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.71 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.78 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2108.60 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   743.50 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   2356.99 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   743.50 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.71 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.78 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   2108.60 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   743.50 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   2356.99 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   761.21 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   743.45 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.71 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.78 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   2108.60 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   896.69 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   2356.99 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   2973.99 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   968.96 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   925.59 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   765.17 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   2973.78 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   897.52 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   291.71 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   3061.39 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   12831.77 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   6871.32 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   5209.88 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.41 459.52 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.96 1064.23 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 483.12 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.80 884.20 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 8821.38 10585.66 0.801 0.961 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 40.60 0.00558
RESTROOMFLR1 561.84 674.21 0.051 0.061 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
MEETINGROOMFLR1 3955.49 4746.58 0.359 0.431 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM101 755.55 906.66 0.095 0.114 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 40.00 0.00558
GUESTROOM102 645.21 774.26 0.081 0.098 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 40.00 0.00558
GUESTROOM103 1325.91 1591.09 0.167 0.201 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 37.11 0.00558
GUESTROOM104 1428.72 1714.47 0.180 0.216 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40 0.00558
GUESTROOM105 1690.59 2028.71 0.213 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
EMPLOYEELOUNGEFLR1 5451.82 6542.18 0.495 0.594 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
EXERCISECENTERFLR1 1315.19 1578.23 0.119 0.143 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.94 0.00558
FRONTOFFICEFLR1 3767.84 4521.41 0.342 0.410 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM201 1028.38 1234.05 0.130 0.156 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 40.80 0.00558
GUESTROOM202_205 4581.75 5498.10 0.578 0.694 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM206_208 3723.04 4467.65 0.470 0.564 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 40.40 0.00558
GUESTROOM209_212 4370.93 5245.12 0.551 0.662 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM213 1292.21 1550.66 0.163 0.196 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
GUESTROOM214 1448.76 1738.51 0.183 0.219 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM215_218 9703.85 11644.62 1.224 1.469 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM219 5426.19 6511.43 0.685 0.821 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM220_223 4859.58 5831.50 0.613 0.736 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80 0.00558
GUESTROOM224 1421.35 1705.62 0.179 0.215 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM301 854.39 1025.26 0.108 0.129 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM302_305 1985.31 2382.37 0.250 0.301 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM306_308 1746.23 2095.48 0.220 0.264 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM309_312 4320.10 5184.12 0.545 0.654 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM313 789.97 947.96 0.100 0.120 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
GUESTROOM314 1368.51 1642.21 0.173 0.207 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM315_318 5234.77 6281.72 0.660 0.793 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM319 1175.82 1410.99 0.148 0.178 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM320_323 4642.30 5570.77 0.586 0.703 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM324 854.29 1025.14 0.108 0.129 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM401 1684.80 2021.77 0.213 0.255 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 40.80 0.00558
GUESTROOM402_405 2702.30 3242.76 0.341 0.409 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM406_408 2334.25 2801.10 0.294 0.353 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM409_412 5344.24 6413.09 0.674 0.809 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM413 1044.05 1252.87 0.132 0.158 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
GUESTROOM414 1140.67 1368.81 0.144 0.173 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 40.80 0.00558
GUESTROOM415_418 5795.43 6954.51 0.731 0.877 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80 0.00558
GUESTROOM419 1600.17 1920.20 0.202 0.242 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
GUESTROOM420_423 5765.82 6918.98 0.727 0.873 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 40.80 0.00558
GUESTROOM424 1671.41 2005.69 0.211 0.253 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 40.80 0.00558
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
CORRIDORFLR1 22300.49 26760.59 2.022 2.427 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 37.61 0.00558
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
CORRIDORFLR2 2923.03 3507.63 0.265 0.318 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 39.20 0.00558
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
CORRIDORFLR3 1522.96 1827.55 0.138 0.166 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 38.94 0.00558
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558
CORRIDORFLR4 2347.62 2817.15 0.213 0.256 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 40.20 0.00558
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB   40.80 0.00558


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1486.74 1784.09 0.046 0.236 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:15:00 0.50 0.00432
RESTROOMFLR1 65.57 78.69 0.002 0.002 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 0.50 0.00432
MEETINGROOMFLR1 489.52 587.43 0.015 0.126 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:00:00 0.50 0.00432
GUESTROOM101 201.87 242.24 0.006 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 0.50 0.00432
GUESTROOM102 241.94 290.32 0.008 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 0.50 0.00432
GUESTROOM103 389.25 467.10 0.012 0.015 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 0.50 0.00432
GUESTROOM104 376.67 452.00 0.012 0.014 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 07:45:00 0.50 0.00432
GUESTROOM105 244.44 293.32 0.008 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:15:00 0.50 0.00432
EMPLOYEELOUNGEFLR1 219.95 263.94 0.007 0.051 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50 0.00432
EXERCISECENTERFLR1 141.73 170.08 0.004 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 0.50 0.00432
FRONTOFFICEFLR1 874.56 1049.48 0.027 0.056 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 0.50 0.00432
GUESTROOM201 313.97 376.76 0.010 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 11:00:00 0.50 0.00432
GUESTROOM202_205 727.92 873.51 0.023 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 10:45:00 0.50 0.00432
GUESTROOM206_208 574.93 689.92 0.018 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 0.50 0.00432
GUESTROOM209_212 652.68 783.21 0.020 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
GUESTROOM213 338.58 406.30 0.011 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 11:00:00 0.50 0.00432
GUESTROOM214 309.25 371.10 0.010 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 10:30:00 0.50 0.00432
GUESTROOM215_218 648.64 778.37 0.020 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
GUESTROOM219 135.05 162.06 0.004 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 0.50 0.00432
GUESTROOM220_223 628.09 753.70 0.020 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:15:00 0.50 0.00432
GUESTROOM224 271.73 326.07 0.008 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:30:00 0.50 0.00432
GUESTROOM301 338.34 406.01 0.011 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 17:45:00 0.50 0.00432
GUESTROOM302_305 801.97 962.36 0.025 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 17:30:00 0.50 0.00432
GUESTROOM306_308 696.80 836.16 0.022 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 14:15:00 0.50 0.00432
GUESTROOM309_312 792.76 951.31 0.025 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:15:00 0.50 0.00432
GUESTROOM313 376.36 451.63 0.012 0.014 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:15:00 0.50 0.00432
GUESTROOM314 341.47 409.76 0.011 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 15:45:00 0.50 0.00432
GUESTROOM315_318 790.28 948.33 0.025 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:00:00 0.50 0.00432
GUESTROOM319 203.42 244.10 0.006 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:15:00 0.50 0.00432
GUESTROOM320_323 760.46 912.56 0.024 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:30:00 0.50 0.00432
GUESTROOM324 314.64 377.57 0.010 0.013 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 0.50 0.00432
GUESTROOM401 489.26 587.11 0.015 0.018 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 22:45:00 0.50 0.00432
GUESTROOM402_405 1331.83 1598.19 0.041 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 22:15:00 0.50 0.00432
GUESTROOM406_408 1141.33 1369.60 0.035 0.043 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:00:00 0.50 0.00432
GUESTROOM409_412 1334.78 1601.73 0.041 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 0.50 0.00432
GUESTROOM413 549.48 659.38 0.017 0.020 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50 0.00432
GUESTROOM414 513.36 616.03 0.016 0.019 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 21:15:00 0.50 0.00432
GUESTROOM415_418 1334.01 1600.81 0.041 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 17:15:00 0.50 0.00432
GUESTROOM419 379.68 455.61 0.012 0.014 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 18:00:00 0.50 0.00432
GUESTROOM420_423 1302.62 1563.14 0.040 0.054 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 19:15:00 0.50 0.00432
GUESTROOM424 489.96 587.96 0.015 0.018 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50 0.00432
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
CORRIDORFLR1 16313.46 19576.15 0.506 0.607 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 0.50 0.00432
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
CORRIDORFLR2 181.55 217.86 0.006 0.038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 09:45:00 0.50 0.00432
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
CORRIDORFLR3 320.40 384.48 0.010 0.038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 13:30:00 0.50 0.00432
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432
CORRIDORFLR4 992.81 1191.37 0.031 0.038 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 0.50 0.00432
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB   0.50 0.00432


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.41 0.41 0.06 0.06
SAC_FRONTLOUNGE 0.96 0.96 0.24 0.24
SAC_MEETINGROOM 0.43 0.43 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.80 0.80 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 0.96 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 1673.25 5778.00 346.25
RESTROOMFLR1 595.25 6376.00 31.00
MEETINGROOMFLR1 1114.75 2434.25 79.00
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 56.50 8742.75 56.50
GUESTROOM104 20.50 8560.75 20.50
GUESTROOM105 2.50 8290.50 2.50
EMPLOYEELOUNGEFLR1 2807.00 2079.50 119.00
EXERCISECENTERFLR1 1612.25 1441.25 9.25
FRONTOFFICEFLR1 1248.75 4854.00 56.75
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 16.50 8383.00 16.50
GUESTROOM206_208 11.00 8377.50 11.00
GUESTROOM209_212 16.75 8444.00 16.75
GUESTROOM213 31.75 8639.00 31.75
GUESTROOM214 13.50 8385.50 13.50
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 5491.25 3758.75 1235.50
GUESTROOM220_223 12.50 8320.25 12.50
GUESTROOM224 10.25 8335.50 10.25
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 26.25 8642.75 26.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 15.75 8398.50 15.75
GUESTROOM315_318 10.50 8191.00 6.75
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 19.75 8468.25 19.75
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 733.75 7774.25 450.25
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 361.00 7787.75 92.75
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 462.50 7107.00 32.75
GUESTROOM419 277.50 7445.50 20.75
GUESTROOM420_423 445.75 7171.00 36.00
GUESTROOM424 342.25 7618.00 58.00
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 6729.75 8759.75 4552.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 0.00 1356.00 0.00 1356.00
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 50.25 0.00 50.25
GUESTROOM104 0.00 68.25 0.00 68.25
GUESTROOM105 0.00 83.25 0.00 83.25
EMPLOYEELOUNGEFLR1 108.00 1044.75 66.25 550.75
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 34.25 0.00 34.25
GUESTROOM206_208 0.00 43.75 0.00 43.75
GUESTROOM209_212 0.00 33.00 0.00 33.00
GUESTROOM213 0.00 35.25 0.00 35.25
GUESTROOM214 0.00 45.00 0.00 45.00
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 4096.50 0.00 4096.50
GUESTROOM220_223 0.00 40.25 0.00 40.25
GUESTROOM224 0.00 45.25 0.00 45.25
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 30.00 0.00 30.00
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 44.50 0.00 44.50
GUESTROOM315_318 0.00 43.50 0.00 43.50
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 37.00 0.00 37.00
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 0.00 48.25 0.00 48.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 43.75 0.00 43.75
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 51.00 0.00 51.00
GUESTROOM419 0.00 57.25 0.00 57.25
GUESTROOM420_423 0.00 50.00 0.00 50.00
GUESTROOM424 0.00 54.25 0.00 54.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 5682.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 1184.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 49.75 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.25 912.25 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 108.25 6784.00 66.25 4958.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:32

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.410243
SAC_FRONTLOUNGE SUPPLY FAN 0.961231
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.798624


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 291.78
CORRIDORFLR1 PTAC HEATING COIL 20635.54
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 743.50
102 PTAC HEATING COIL 743.50
103 PTAC HEATING COIL 776.68
104 PTAC HEATING COIL 761.56
105 PTAC HEATING COIL 743.45
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 291.71
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 291.78
CORRIDORFLR2 PTAC HEATING COIL 2108.60
201 PTAC HEATING COIL 743.50
202_205 PTAC HEATING COIL 2973.99
206_208 PTAC HEATING COIL 2356.99
209_212 PTAC HEATING COIL 2973.99
213 PTAC HEATING COIL 743.50
214 PTAC HEATING COIL 743.45
215_218 PTAC HEATING COIL 2973.78
219 PTAC HEATING COIL 743.45
220_223 PTAC HEATING COIL 2973.78
224 PTAC HEATING COIL 743.45
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 291.71
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 291.78
CORRIDORFLR3 PTAC HEATING COIL 2108.60
301 PTAC HEATING COIL 743.50
302_305 PTAC HEATING COIL 2973.99
306_308 PTAC HEATING COIL 2356.99
309_312 PTAC HEATING COIL 2973.99
313 PTAC HEATING COIL 761.21
314 PTAC HEATING COIL 743.45
315_318 PTAC HEATING COIL 2973.78
319 PTAC HEATING COIL 743.45
320_323 PTAC HEATING COIL 2973.78
324 PTAC HEATING COIL 743.45
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 291.71
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 291.78
CORRIDORFLR4 PTAC HEATING COIL 2108.60
401 PTAC HEATING COIL 896.69
402_405 PTAC HEATING COIL 2973.99
406_408 PTAC HEATING COIL 2356.99
409_412 PTAC HEATING COIL 2973.99
413 PTAC HEATING COIL 968.96
414 PTAC HEATING COIL 925.59
415_418 PTAC HEATING COIL 2973.78
419 PTAC HEATING COIL 765.17
420_423 PTAC HEATING COIL 2973.78
424 PTAC HEATING COIL 897.52
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 291.71


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.749474 0.410243 7839.69
SAC_FRONTLOUNGE COOLING COIL 0.713691 0.961231 20694.12
SAC_MEETINGROOM COOLING COIL 0.685798 0.431318 10302.28
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.744536 0.798624 15502.00


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.961231
RESTROOMFLR1 DIRECT AIR 0.061163
MEETINGROOMFLR1 DIRECT AIR 0.431318
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.594207
EXERCISECENTERFLR1 DIRECT AIR 0.143254
FRONTOFFICEFLR1 DIRECT AIR 0.410243


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.410243
SAC_FRONTLOUNGE MAIN BRANCH 0.961231
SAC_MEETINGROOM MAIN BRANCH 0.431318
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.798624


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.410243
SAC_FRONTLOUNGE 0.961231
SAC_MEETINGROOM 0.431318
SAC_EXC_EMPLGE_RESTRM 0.798624


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.410243 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.961231 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.431318 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.798624 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.410243 0.410243 0.410243 0.410243 3061.39 7839.69 1.00
SAC_FRONTLOUNGE 0.961231 0.961231 0.961231 0.961231 12831.77 20694.12 1.00
SAC_MEETINGROOM 0.431318 0.431318 0.431318 0.431318 6871.32 10302.28 1.00
SAC_EXC_EMPLGE_RESTRM 0.798624 0.798624 0.798624 0.798624 5209.88 15502.00 0.179376


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 3061.39
SAC_FRONTLOUNGE HEATING COIL 12831.77
SAC_MEETINGROOM HEATING COIL 6871.32
SAC_EXC_EMPLGE_RESTRM HEATING COIL 5209.88


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.431318


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.21 14.83
February 21.44 12.72
March 22.00 15.42
April 24.62 23.31
May 25.38 26.31
June 26.79 31.20
July 26.46 30.42
August 26.23 29.82
September 25.76 27.75
October 23.91 20.87
November 22.40 15.43
December 21.44 11.86
     
Annual Sum or Average 24.06 21.71
Minimum of Months 21.44 11.86
Maximum of Months 26.79 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.26 14.83
February 23.80 12.72
March 24.30 15.42
April 25.90 23.31
May 26.58 26.31
June 27.72 31.20
July 27.62 30.42
August 27.44 29.82
September 26.98 27.75
October 25.44 20.87
November 24.38 15.43
December 23.80 11.86
     
Annual Sum or Average 25.69 21.71
Minimum of Months 23.80 11.86
Maximum of Months 27.72 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 14.83
February 20.59 12.72
March 21.31 15.42
April 23.92 23.31
May 24.88 26.31
June 26.32 31.20
July 25.94 30.42
August 25.60 29.82
September 25.04 27.75
October 23.03 20.87
November 21.41 15.43
December 20.29 11.86
     
Annual Sum or Average 23.30 21.71
Minimum of Months 20.29 11.86
Maximum of Months 26.32 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.53 14.83
February 22.08 12.72
March 22.63 15.42
April 23.53 23.31
May 23.77 26.31
June 23.89 31.20
July 23.89 30.42
August 23.89 29.82
September 23.87 27.75
October 23.27 20.87
November 22.59 15.43
December 22.10 11.86
     
Annual Sum or Average 23.18 21.71
Minimum of Months 22.08 11.86
Maximum of Months 23.89 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.57 14.83
February 22.58 12.72
March 22.81 15.42
April 23.41 23.31
May 23.67 26.31
June 23.93 31.20
July 23.88 30.42
August 23.79 29.82
September 23.65 27.75
October 23.19 20.87
November 22.74 15.43
December 22.31 11.86
     
Annual Sum or Average 23.21 21.71
Minimum of Months 22.31 11.86
Maximum of Months 23.93 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.14 14.83
February 22.97 12.72
March 23.22 15.42
April 23.77 23.31
May 23.88 26.31
June 23.89 31.20
July 23.89 30.42
August 23.89 29.82
September 23.89 27.75
October 23.71 20.87
November 23.29 15.43
December 22.79 11.86
     
Annual Sum or Average 23.53 21.71
Minimum of Months 22.79 11.86
Maximum of Months 23.89 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.53 14.83
February 25.37 12.72
March 25.77 15.42
April 28.45 23.31
May 31.45 26.31
June 33.95 31.20
July 34.94 30.42
August 34.49 29.82
September 32.89 27.75
October 29.86 20.87
November 26.81 15.43
December 25.25 11.86
     
Annual Sum or Average 29.59 21.71
Minimum of Months 25.25 11.86
Maximum of Months 34.94 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.02 14.83
February 21.67 12.72
March 22.20 15.42
April 23.21 23.31
May 23.33 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 23.09 20.87
November 22.36 15.43
December 21.42 11.86
     
Annual Sum or Average 22.72 21.71
Minimum of Months 21.42 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 14.83
February 21.33 12.72
March 21.91 15.42
April 23.03 23.31
May 23.26 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.78 20.87
November 21.98 15.43
December 21.09 11.86
     
Annual Sum or Average 22.54 21.71
Minimum of Months 21.09 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.59 14.83
February 21.46 12.72
March 21.59 15.42
April 21.75 23.31
May 21.75 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.75 27.75
October 21.71 20.87
November 21.63 15.43
December 21.45 11.86
     
Annual Sum or Average 21.66 21.71
Minimum of Months 21.45 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 14.83
February 21.69 12.72
March 21.70 15.42
April 21.75 23.31
May 21.75 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.74 15.43
December 21.72 11.86
     
Annual Sum or Average 21.74 21.71
Minimum of Months 21.69 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.74 12.72
March 21.74 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.75 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.74 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.48 14.83
February 22.76 12.72
March 22.73 15.42
April 22.61 23.31
May 22.53 26.31
June 22.20 31.20
July 22.23 30.42
August 22.23 29.82
September 22.29 27.75
October 22.53 20.87
November 22.59 15.43
December 22.40 11.86
     
Annual Sum or Average 22.46 21.71
Minimum of Months 22.20 11.86
Maximum of Months 22.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 52.10 14.83
February 51.63 12.72
March 51.76 15.42
April 52.64 23.31
May 52.81 26.31
June 53.33 31.20
July 53.33 30.42
August 53.34 29.82
September 53.25 27.75
October 52.67 20.87
November 52.13 15.43
December 51.79 11.86
     
Annual Sum or Average 52.57 21.71
Minimum of Months 51.63 11.86
Maximum of Months 53.34 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 69.58 14.83
February 69.20 12.72
March 69.36 15.42
April 70.38 23.31
May 70.68 26.31
June 71.34 31.20
July 71.31 30.42
August 71.30 29.82
September 71.07 27.75
October 70.28 20.87
November 69.64 15.43
December 69.34 11.86
     
Annual Sum or Average 70.30 21.71
Minimum of Months 69.20 11.86
Maximum of Months 71.34 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.56 14.83
February 23.55 12.72
March 23.59 15.42
April 23.87 23.31
May 23.89 26.31
June 23.89 31.20
July 23.89 30.42
August 23.89 29.82
September 23.89 27.75
October 23.82 20.87
November 23.64 15.43
December 23.36 11.86
     
Annual Sum or Average 23.74 21.71
Minimum of Months 23.36 11.86
Maximum of Months 23.89 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.54 14.83
February 23.51 12.72
March 23.56 15.42
April 23.88 23.31
May 23.89 26.31
June 23.89 31.20
July 23.89 30.42
August 23.89 29.82
September 23.89 27.75
October 23.82 20.87
November 23.64 15.43
December 23.26 11.86
     
Annual Sum or Average 23.72 21.71
Minimum of Months 23.26 11.86
Maximum of Months 23.89 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 14.83
February 21.59 12.72
March 22.19 15.42
April 25.21 23.31
May 26.12 26.31
June 27.77 31.20
July 27.50 30.42
August 27.24 29.82
September 26.61 27.75
October 24.49 20.87
November 22.61 15.43
December 21.56 11.86
     
Annual Sum or Average 24.62 21.71
Minimum of Months 21.56 11.86
Maximum of Months 27.77 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 14.83
February 22.68 12.72
March 23.00 15.42
April 24.65 23.31
May 25.12 26.31
June 26.03 31.20
July 25.92 30.42
August 25.82 29.82
September 25.52 27.75
October 24.40 20.87
November 23.36 15.43
December 22.70 11.86
     
Annual Sum or Average 24.38 21.71
Minimum of Months 22.68 11.86
Maximum of Months 26.03 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.64 14.83
February 22.00 12.72
March 22.49 15.42
April 25.13 23.31
May 25.96 26.31
June 27.35 31.20
July 27.02 30.42
August 26.73 29.82
September 26.25 27.75
October 24.38 20.87
November 22.85 15.43
December 21.95 11.86
     
Annual Sum or Average 24.57 21.71
Minimum of Months 21.95 11.86
Maximum of Months 27.35 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.77 14.83
February 23.73 12.72
March 23.77 15.42
April 23.90 23.31
May 23.95 26.31
June 24.23 31.20
July 24.14 30.42
August 24.10 29.82
September 23.99 27.75
October 23.89 20.87
November 23.80 15.43
December 23.57 11.86
     
Annual Sum or Average 23.90 21.71
Minimum of Months 23.57 11.86
Maximum of Months 24.23 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 14.83
February 20.71 12.72
March 21.43 15.42
April 24.27 23.31
May 25.30 26.31
June 26.78 31.20
July 26.41 30.42
August 26.01 29.82
September 25.44 27.75
October 23.32 20.87
November 21.54 15.43
December 20.35 11.86
     
Annual Sum or Average 23.58 21.71
Minimum of Months 20.35 11.86
Maximum of Months 26.78 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 14.83
February 21.40 12.72
March 22.13 15.42
April 23.21 23.31
May 23.32 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.92 20.87
November 22.13 15.43
December 21.02 11.86
     
Annual Sum or Average 22.62 21.71
Minimum of Months 21.02 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 14.83
February 21.66 12.72
March 21.72 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.72 15.43
December 21.62 11.86
     
Annual Sum or Average 21.73 21.71
Minimum of Months 21.62 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 14.83
February 21.67 12.72
March 21.72 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.73 15.43
December 21.64 11.86
     
Annual Sum or Average 21.73 21.71
Minimum of Months 21.64 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 14.83
February 21.70 12.72
March 21.73 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.73 15.43
December 21.67 11.86
     
Annual Sum or Average 21.74 21.71
Minimum of Months 21.67 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.66 14.83
February 21.55 12.72
March 21.66 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.73 20.87
November 21.68 15.43
December 21.52 11.86
     
Annual Sum or Average 21.69 21.71
Minimum of Months 21.52 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.74 12.72
March 21.74 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.74 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 14.83
February 23.33 12.72
March 23.32 15.42
April 23.33 23.31
May 23.33 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 23.33 20.87
November 23.33 15.43
December 23.32 11.86
     
Annual Sum or Average 23.33 21.71
Minimum of Months 23.32 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 32.74 14.83
February 32.46 12.72
March 32.60 15.42
April 33.39 23.31
May 33.59 26.31
June 34.11 31.20
July 34.08 30.42
August 34.05 29.82
September 33.88 27.75
October 33.29 20.87
November 32.80 15.43
December 32.46 11.86
     
Annual Sum or Average 33.29 21.71
Minimum of Months 32.46 11.86
Maximum of Months 34.11 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.43 14.83
February 22.32 12.72
March 22.39 15.42
April 22.85 23.31
May 23.00 26.31
June 23.52 31.20
July 23.62 30.42
August 23.60 29.82
September 23.43 27.75
October 22.81 20.87
November 22.45 15.43
December 22.22 11.86
     
Annual Sum or Average 22.89 21.71
Minimum of Months 22.22 11.86
Maximum of Months 23.62 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.75 12.72
March 21.75 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.75 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.75 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.74 12.72
March 21.74 15.42
April 21.76 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.74 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 14.83
February 22.71 12.72
March 23.07 15.42
April 24.95 23.31
May 25.51 26.31
June 26.48 31.20
July 26.34 30.42
August 26.17 29.82
September 25.81 27.75
October 24.55 20.87
November 23.39 15.43
December 22.67 11.86
     
Annual Sum or Average 24.58 21.71
Minimum of Months 22.67 11.86
Maximum of Months 26.48 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 14.83
February 22.03 12.72
March 22.65 15.42
April 25.98 23.31
May 27.07 26.31
June 28.84 31.20
July 28.52 30.42
August 28.15 29.82
September 27.41 27.75
October 25.07 20.87
November 22.99 15.43
December 21.88 11.86
     
Annual Sum or Average 25.29 21.71
Minimum of Months 21.88 11.86
Maximum of Months 28.84 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.39 14.83
February 21.73 12.72
March 22.30 15.42
April 25.21 23.31
May 26.11 26.31
June 27.57 31.20
July 27.23 30.42
August 26.91 29.82
September 26.39 27.75
October 24.35 20.87
November 22.65 15.43
December 21.61 11.86
     
Annual Sum or Average 24.55 21.71
Minimum of Months 21.61 11.86
Maximum of Months 27.57 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.23 14.83
February 22.90 12.72
March 23.29 15.42
April 23.86 23.31
May 23.89 26.31
June 23.91 31.20
July 23.89 30.42
August 23.89 29.82
September 23.89 27.75
October 23.73 20.87
November 23.36 15.43
December 22.69 11.86
     
Annual Sum or Average 23.55 21.71
Minimum of Months 22.69 11.86
Maximum of Months 23.91 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.75 14.83
February 20.18 12.72
March 21.11 15.42
April 24.43 23.31
May 25.58 26.31
June 27.16 31.20
July 26.78 30.42
August 26.35 29.82
September 25.73 27.75
October 23.31 20.87
November 21.19 15.43
December 19.71 11.86
     
Annual Sum or Average 23.54 21.71
Minimum of Months 19.71 11.86
Maximum of Months 27.16 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.42 14.83
February 20.77 12.72
March 21.73 15.42
April 23.15 23.31
May 23.31 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.74 20.87
November 21.70 15.43
December 20.44 11.86
     
Annual Sum or Average 22.39 21.71
Minimum of Months 20.44 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.49 14.83
February 20.87 12.72
March 21.81 15.42
April 23.18 23.31
May 23.32 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.78 20.87
November 21.78 15.43
December 20.53 11.86
     
Annual Sum or Average 22.43 21.71
Minimum of Months 20.53 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.51 14.83
February 20.95 12.72
March 21.82 15.42
April 23.15 23.31
May 23.31 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.76 20.87
November 21.79 15.43
December 20.60 11.86
     
Annual Sum or Average 22.44 21.71
Minimum of Months 20.60 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.71 14.83
February 21.65 12.72
March 21.71 15.42
April 21.75 23.31
May 21.75 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.74 20.87
November 21.72 15.43
December 21.62 11.86
     
Annual Sum or Average 21.72 21.71
Minimum of Months 21.62 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.52 14.83
February 20.98 12.72
March 21.80 15.42
April 23.19 23.31
May 23.32 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.78 20.87
November 21.81 15.43
December 20.62 11.86
     
Annual Sum or Average 22.45 21.71
Minimum of Months 20.62 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 14.83
February 21.71 12.72
March 21.72 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.74 15.43
December 21.73 11.86
     
Annual Sum or Average 21.74 21.71
Minimum of Months 21.71 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.75 12.72
March 21.75 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.75 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.75 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.22 14.83
February 24.88 12.72
March 25.14 15.42
April 26.11 23.31
May 26.32 26.31
June 26.75 31.20
July 26.70 30.42
August 26.64 29.82
September 26.52 27.75
October 25.91 20.87
November 25.33 15.43
December 24.81 11.86
     
Annual Sum or Average 25.87 21.71
Minimum of Months 24.81 11.86
Maximum of Months 26.75 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 14.83
February 23.14 12.72
March 23.15 15.42
April 23.33 23.31
May 23.33 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 23.30 20.87
November 23.23 15.43
December 22.97 11.86
     
Annual Sum or Average 23.25 21.71
Minimum of Months 22.97 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.74 12.72
March 21.74 15.42
April 21.75 23.31
May 21.75 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.74 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.57 14.83
February 22.19 12.72
March 22.49 15.42
April 23.24 23.31
May 23.32 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 23.09 20.87
November 22.70 15.43
December 22.08 11.86
     
Annual Sum or Average 22.92 21.71
Minimum of Months 22.08 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.92 14.83
February 22.36 12.72
March 22.85 15.42
April 25.11 23.31
May 25.76 26.31
June 26.82 31.20
July 26.65 30.42
August 26.45 29.82
September 26.04 27.75
October 24.55 20.87
November 23.16 15.43
December 22.24 11.86
     
Annual Sum or Average 24.59 21.71
Minimum of Months 22.24 11.86
Maximum of Months 26.82 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.43 14.83
February 21.75 12.72
March 22.48 15.42
April 26.15 23.31
May 27.34 26.31
June 29.24 31.20
July 28.88 30.42
August 28.47 29.82
September 27.65 27.75
October 25.08 20.87
November 22.79 15.43
December 21.51 11.86
     
Annual Sum or Average 25.33 21.71
Minimum of Months 21.51 11.86
Maximum of Months 29.24 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 14.83
February 21.05 12.72
March 21.90 15.42
April 25.38 23.31
May 26.44 26.31
June 28.17 31.20
July 27.77 30.42
August 27.41 29.82
September 26.77 27.75
October 24.25 20.87
November 22.19 15.43
December 20.83 11.86
     
Annual Sum or Average 24.52 21.71
Minimum of Months 20.83 11.86
Maximum of Months 28.17 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.55 14.83
February 22.23 12.72
March 22.72 15.42
April 23.66 23.31
May 23.90 26.31
June 24.21 31.20
July 24.10 30.42
August 24.09 29.82
September 23.97 27.75
October 23.37 20.87
November 22.73 15.43
December 22.12 11.86
     
Annual Sum or Average 23.31 21.71
Minimum of Months 22.12 11.86
Maximum of Months 24.21 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.30 14.83
February 19.58 12.72
March 20.77 15.42
April 24.55 23.31
May 25.83 26.31
June 27.65 31.20
July 27.21 30.42
August 26.75 29.82
September 26.02 27.75
October 23.16 20.87
November 20.75 15.43
December 19.05 11.86
     
Annual Sum or Average 23.49 21.71
Minimum of Months 19.05 11.86
Maximum of Months 27.65 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.62 14.83
February 21.50 12.72
March 21.64 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.71 20.87
November 21.65 15.43
December 21.46 11.86
     
Annual Sum or Average 21.68 21.71
Minimum of Months 21.46 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.94 14.83
February 20.34 12.72
March 21.34 15.42
April 22.91 23.31
May 23.22 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.32 27.75
October 22.40 20.87
November 21.24 15.43
December 20.14 11.86
     
Annual Sum or Average 22.16 21.71
Minimum of Months 20.14 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.93 14.83
February 20.36 12.72
March 21.33 15.42
April 22.88 23.31
May 23.21 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.32 27.75
October 22.37 20.87
November 21.23 15.43
December 20.16 11.86
     
Annual Sum or Average 22.16 21.71
Minimum of Months 20.16 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 14.83
February 21.64 12.72
March 21.70 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.73 20.87
November 21.71 15.43
December 21.62 11.86
     
Annual Sum or Average 21.72 21.71
Minimum of Months 21.62 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 14.83
February 20.49 12.72
March 21.42 15.42
April 22.97 23.31
May 23.25 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.32 27.75
October 22.47 20.87
November 21.36 15.43
December 20.24 11.86
     
Annual Sum or Average 22.22 21.71
Minimum of Months 20.24 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.85 14.83
February 21.42 12.72
March 21.89 15.42
April 23.03 23.31
May 23.26 26.31
June 23.33 31.20
July 23.33 30.42
August 23.33 29.82
September 23.33 27.75
October 22.74 20.87
November 22.06 15.43
December 21.26 11.86
     
Annual Sum or Average 22.57 21.71
Minimum of Months 21.26 11.86
Maximum of Months 23.33 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.73 12.72
March 21.73 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.73 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.11 14.83
February 22.70 12.72
March 23.14 15.42
April 24.55 23.31
May 24.92 26.31
June 25.59 31.20
July 25.47 30.42
August 25.36 29.82
September 25.12 27.75
October 24.11 20.87
November 23.26 15.43
December 22.56 11.86
     
Annual Sum or Average 24.16 21.71
Minimum of Months 22.56 11.86
Maximum of Months 25.59 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.73 12.72
March 21.73 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.73 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 14.83
February 21.73 12.72
March 21.73 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.75 15.43
December 21.74 11.86
     
Annual Sum or Average 21.75 21.71
Minimum of Months 21.73 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 14.83
February 21.70 12.72
March 21.71 15.42
April 21.75 23.31
May 21.76 26.31
June 21.76 31.20
July 21.76 30.42
August 21.76 29.82
September 21.76 27.75
October 21.75 20.87
November 21.74 15.43
December 21.72 11.86
     
Annual Sum or Average 21.74 21.71
Minimum of Months 21.70 11.86
Maximum of Months 21.76 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.48 14.83
February 21.88 12.72
March 22.52 15.42
April 25.06 23.31
May 25.81 26.31
June 27.09 31.20
July 26.86 30.42
August 26.62 29.82
September 26.09 27.75
October 24.27 20.87
November 22.71 15.43
December 21.68 11.86
     
Annual Sum or Average 24.43 21.71
Minimum of Months 21.68 11.86
Maximum of Months 27.09 31.20



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:32

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.97 14.83
February 21.20 12.72
March 22.12 15.42
April 26.19 23.31
May 27.50 26.31
June 29.64 31.20
July 29.21 30.42
August 28.77 29.82
September 27.83 27.75
October 24.85 20.87
November 22.32 15.43
December 20.87 11.86
     
Annual Sum or Average 25.22 21.71
Minimum of Months 20.87 11.86
Maximum of Months 29.64 31.20



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:32

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.139459E+12 90277.465 01-JAN-07:15 13316.689 34010.661 9108.376 28966.712 678.914 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.122471E+12 86788.626 01-FEB-07:15 15177.258 39465.561 9108.376 14896.335 3944.982 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.138938E+12 95136.514 26-MAR-06:15 15177.258 39465.561 9108.376 25754.342 1434.863 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.149439E+12 89853.911 15-APR-07:00 17938.723 43276.576 9591.499 0.000 19039.001 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.161780E+12 90140.743 19-MAY-07:00 17938.723 43276.576 9591.499 0.000 19325.833 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.174336E+12 102961.921 30-JUN-07:00 17938.723 43276.576 9591.499 0.000 32147.011 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.184735E+12 105755.037 22-JUL-07:00 17938.723 43276.576 9591.499 0.000 34940.126 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.182802E+12 103032.207 12-AUG-07:00 17938.723 43276.576 9591.499 0.000 32217.296 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.170628E+12 100926.712 02-SEP-07:00 17938.723 43276.576 9591.499 0.000 30111.802 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.152441E+12 93333.914 07-OCT-07:00 17938.723 43276.576 9591.499 0.000 22519.003 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.136532E+12 89865.722 23-NOV-07:15 15177.258 39465.561 9108.376 24087.389 2019.024 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.137287E+12 97047.177 07-DEC-07:15 15177.258 39465.561 9108.376 28104.137 995.731 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.185085E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.122471E+12 86788.626   13316.689 34010.661 9108.376 0.000 678.914 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.184735E+12 105755.037   17938.723 43276.576 9591.499 28966.712 34940.126 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:32

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.850492E+11 91261.736 28-JAN-09:15 0.000 40096.028 0.000 51165.707 51165.707 51165.707 0.000
February 0.763889E+11 91046.048 03-FEB-09:15 0.000 40096.028 0.000 50950.020 50950.020 50950.020 0.000
March 0.822781E+11 89980.403 03-MAR-09:00 0.000 40096.028 0.000 49884.375 49884.375 49884.375 0.000
April 0.766686E+11 74278.114 01-APR-08:00 0.000 40096.028 0.000 34182.086 34182.086 34182.086 0.000
May 0.772267E+11 73241.442 01-MAY-08:15 0.000 40096.028 0.000 33145.414 33145.414 33145.414 0.000
June 0.731728E+11 72201.440 01-JUN-08:15 0.000 40096.028 0.000 32105.412 32105.412 32105.412 0.000
July 0.748192E+11 71555.985 01-JUL-08:30 0.000 40096.028 0.000 31459.957 31459.957 31459.957 0.000
August 0.750556E+11 71812.835 29-AUG-08:15 0.000 40096.028 0.000 31716.807 31716.807 31716.807 0.000
September 0.738013E+11 72563.520 30-SEP-08:45 0.000 40096.028 0.000 32467.492 32467.492 32467.492 0.000
October 0.782311E+11 73673.748 31-OCT-08:45 0.000 40096.028 0.000 33577.720 33577.720 33577.720 0.000
November 0.782988E+11 89381.655 30-NOV-09:15 0.000 40096.028 0.000 49285.627 49285.627 49285.627 0.000
December 0.850458E+11 90374.841 30-DEC-09:00 0.000 40096.028 0.000 50278.813 50278.813 50278.813 0.000
                     
Annual Sum or Average 0.936036E+12         0.000        
Minimum of Months 0.731728E+11 71555.985   0.000 40096.028 0.000 31459.957 31459.957 31459.957 0.000
Maximum of Months 0.850492E+11 91261.736   0.000 40096.028 0.000 51165.707 51165.707 51165.707 0.000