Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2768.66 | 689.82 | 743.25 |
Net Site Energy | 2768.66 | 689.82 | 743.25 |
Total Source Energy | 6595.85 | 1643.38 | 1770.65 |
Net Source Energy | 6595.85 | 1643.38 | 1770.65 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 71.82 | 29.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 290.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 291.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 592.00 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1725.69 | 1042.97 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 71.82 | 29.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 290.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 291.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 592.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 175.63 | 166.84 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 463.26 | 279.99 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 163.00 | 154.84 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.96 | 259.86 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1725.69 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1725.69 | 100.00 |
Total On-Site and Utility Electric Sources | 1725.69 | 100.00 |
Total Electricity End Uses | 1725.69 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 177.75 |
Time Setpoint Not Met During Occupied Cooling | 4035.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5642.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Weather File | Albuquerque Intl Sunport NM USA TMY3 WMO#=723650 |
Latitude [deg] | 35.04 |
Longitude [deg] | -106.6 |
Elevation [m] | 1619.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00 | -7.90 | Wetbulb [C] | 3.20 | 0.00 |
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 13.50 | 15.70 | Wetbulb [C] | 4.40 | 220.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6115.61 | 4884.26 | 1231.35 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16452.20 | 12614.28 | 3837.92 | 0.77 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8655.63 | 6348.43 | 2307.20 | 0.73 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13858.45 | 11068.12 | 2790.33 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5828.9 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15747.7 | 3.21 | 10.95 | 11.59 | 10.82 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8321.6 | 3.27 | 11.15 | 11.82 | 11.13 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13208.8 | 3.15 | 10.76 | 11.39 | 10.54 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.34 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 18122.04 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 787.90 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 787.90 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 880.55 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 866.09 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 787.84 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.28 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.34 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2234.52 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 861.46 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3151.59 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2497.75 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3151.59 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 915.88 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 874.81 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3151.37 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 787.84 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3151.37 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 805.81 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.28 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.34 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2234.52 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 906.73 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3151.59 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2497.75 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3151.59 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 998.10 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 949.01 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3151.37 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 787.84 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3151.37 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 890.22 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.28 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.34 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3006.94 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1154.93 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3581.68 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2939.25 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3590.71 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1287.38 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1236.89 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3560.71 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 976.03 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3519.41 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1182.53 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 264.28 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3244.22 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 13598.06 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 7281.66 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5515.84 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.37 | 413.82 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.91 | 1004.81 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 481.81 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.84 | 926.90 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7544.94 | 9053.92 | 0.756 | 0.908 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.90 | 0.00565 |
RESTROOMFLR1 | 445.21 | 534.25 | 0.045 | 0.053 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 33.75 | 0.00565 |
MEETINGROOMFLR1 | 3573.32 | 4287.98 | 0.358 | 0.430 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM101 | 574.14 | 688.96 | 0.080 | 0.096 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 34.49 | 0.00565 |
GUESTROOM102 | 471.24 | 565.49 | 0.066 | 0.079 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 34.49 | 0.00565 |
GUESTROOM103 | 1063.58 | 1276.29 | 0.148 | 0.178 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
GUESTROOM104 | 1156.40 | 1387.68 | 0.161 | 0.193 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.90 | 0.00565 |
GUESTROOM105 | 1507.57 | 1809.08 | 0.210 | 0.252 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
EMPLOYEELOUNGEFLR1 | 5357.68 | 6429.21 | 0.537 | 0.645 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
EXERCISECENTERFLR1 | 1156.95 | 1388.34 | 0.116 | 0.139 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21 | 0.00565 |
FRONTOFFICEFLR1 | 3074.01 | 3688.81 | 0.308 | 0.369 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
GUESTROOM201 | 816.81 | 980.17 | 0.114 | 0.136 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 34.93 | 0.00565 |
GUESTROOM202_205 | 4131.91 | 4958.29 | 0.575 | 0.690 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 34.49 | 0.00565 |
GUESTROOM206_208 | 3353.28 | 4023.94 | 0.467 | 0.560 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86 | 0.00565 |
GUESTROOM209_212 | 3945.66 | 4734.80 | 0.549 | 0.659 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 34.29 | 0.00565 |
GUESTROOM213 | 1134.56 | 1361.48 | 0.158 | 0.190 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 31.35 | 0.00565 |
GUESTROOM214 | 1286.88 | 1544.25 | 0.179 | 0.215 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM215_218 | 9457.48 | 11348.97 | 1.317 | 1.580 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
GUESTROOM219 | 5405.82 | 6486.98 | 0.753 | 0.903 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM220_223 | 4440.83 | 5328.99 | 0.618 | 0.742 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
GUESTROOM224 | 1277.43 | 1532.92 | 0.178 | 0.213 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
GUESTROOM301 | 645.14 | 774.17 | 0.090 | 0.108 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM302_305 | 1592.83 | 1911.40 | 0.222 | 0.266 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86 | 0.00565 |
GUESTROOM306_308 | 1396.27 | 1675.52 | 0.194 | 0.233 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86 | 0.00565 |
GUESTROOM309_312 | 3934.59 | 4721.50 | 0.548 | 0.658 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86 | 0.00565 |
GUESTROOM313 | 641.65 | 769.98 | 0.089 | 0.107 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 30.85 | 0.00565 |
GUESTROOM314 | 1210.97 | 1453.16 | 0.169 | 0.202 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.70 | 0.00565 |
GUESTROOM315_318 | 4861.22 | 5833.46 | 0.677 | 0.812 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM319 | 1079.06 | 1294.87 | 0.150 | 0.180 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM320_323 | 4248.68 | 5098.42 | 0.592 | 0.710 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM324 | 712.95 | 855.54 | 0.099 | 0.119 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 35.10 | 0.00565 |
GUESTROOM401 | 1533.73 | 1840.48 | 0.214 | 0.256 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 35.10 | 0.00565 |
GUESTROOM402_405 | 2525.20 | 3030.24 | 0.352 | 0.422 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
GUESTROOM406_408 | 2158.99 | 2590.79 | 0.301 | 0.361 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
GUESTROOM409_412 | 5182.92 | 6219.50 | 0.722 | 0.866 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
GUESTROOM413 | 941.76 | 1130.11 | 0.131 | 0.157 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.90 | 0.00565 |
GUESTROOM414 | 1049.72 | 1259.66 | 0.146 | 0.175 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 35.10 | 0.00565 |
GUESTROOM415_418 | 5674.67 | 6809.61 | 0.790 | 0.948 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 35.10 | 0.00565 |
GUESTROOM419 | 1569.07 | 1882.89 | 0.219 | 0.262 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
GUESTROOM420_423 | 5641.53 | 6769.83 | 0.786 | 0.943 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 35.10 | 0.00565 |
GUESTROOM424 | 1602.17 | 1922.60 | 0.223 | 0.268 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 35.10 | 0.00565 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
CORRIDORFLR1 | 15504.56 | 18605.47 | 1.552 | 1.863 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 31.86 | 0.00565 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
CORRIDORFLR2 | 2716.41 | 3259.69 | 0.272 | 0.326 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.21 | 0.00565 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
CORRIDORFLR3 | 1322.77 | 1587.32 | 0.132 | 0.159 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.87 | 0.00565 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 | |
CORRIDORFLR4 | 2385.53 | 2862.64 | 0.239 | 0.287 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.90 | 0.00565 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB | 35.10 | 0.00565 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1347.01 | 1616.41 | 0.046 | 0.236 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | -7.90 | 0.00234 |
RESTROOMFLR1 | 65.12 | 78.14 | 0.002 | 0.003 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.90 | 0.00234 |
MEETINGROOMFLR1 | 455.19 | 546.22 | 0.016 | 0.126 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -7.90 | 0.00234 |
GUESTROOM101 | 189.42 | 227.30 | 0.006 | 0.013 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.90 | 0.00234 |
GUESTROOM102 | 234.01 | 280.81 | 0.008 | 0.013 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.90 | 0.00234 |
GUESTROOM103 | 404.81 | 485.77 | 0.014 | 0.017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -7.90 | 0.00234 |
GUESTROOM104 | 392.78 | 471.34 | 0.013 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -7.90 | 0.00234 |
GUESTROOM105 | 231.90 | 278.28 | 0.008 | 0.013 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -7.90 | 0.00234 |
EMPLOYEELOUNGEFLR1 | 202.75 | 243.30 | 0.007 | 0.051 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90 | 0.00234 |
EXERCISECENTERFLR1 | 123.11 | 147.74 | 0.004 | 0.043 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -7.90 | 0.00234 |
FRONTOFFICEFLR1 | 837.72 | 1005.26 | 0.029 | 0.056 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -7.90 | 0.00234 |
GUESTROOM201 | 388.90 | 466.68 | 0.013 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -7.90 | 0.00234 |
GUESTROOM202_205 | 822.09 | 986.51 | 0.028 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -7.90 | 0.00234 |
GUESTROOM206_208 | 636.00 | 763.20 | 0.022 | 0.043 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -7.90 | 0.00234 |
GUESTROOM209_212 | 741.09 | 889.31 | 0.025 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.90 | 0.00234 |
GUESTROOM213 | 434.25 | 521.10 | 0.015 | 0.018 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -7.90 | 0.00234 |
GUESTROOM214 | 400.05 | 480.05 | 0.014 | 0.016 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 10:15:00 | -7.90 | 0.00234 |
GUESTROOM215_218 | 711.41 | 853.69 | 0.024 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.90 | 0.00234 |
GUESTROOM219 | 157.03 | 188.44 | 0.005 | 0.013 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.90 | 0.00234 |
GUESTROOM220_223 | 696.97 | 836.37 | 0.024 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -7.90 | 0.00234 |
GUESTROOM224 | 342.55 | 411.06 | 0.012 | 0.014 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -7.90 | 0.00234 |
GUESTROOM301 | 426.63 | 511.95 | 0.015 | 0.018 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -7.90 | 0.00234 |
GUESTROOM302_305 | 938.92 | 1126.71 | 0.032 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -7.90 | 0.00234 |
GUESTROOM306_308 | 798.19 | 957.83 | 0.027 | 0.043 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -7.90 | 0.00234 |
GUESTROOM309_312 | 933.58 | 1120.29 | 0.032 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -7.90 | 0.00234 |
GUESTROOM313 | 502.76 | 603.32 | 0.017 | 0.021 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 20:45:00 | -7.90 | 0.00234 |
GUESTROOM314 | 461.88 | 554.26 | 0.016 | 0.019 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 15:30:00 | -7.90 | 0.00234 |
GUESTROOM315_318 | 906.70 | 1088.04 | 0.031 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -7.90 | 0.00234 |
GUESTROOM319 | 245.69 | 294.83 | 0.008 | 0.013 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -7.90 | 0.00234 |
GUESTROOM320_323 | 875.36 | 1050.44 | 0.030 | 0.054 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -7.90 | 0.00234 |
GUESTROOM324 | 412.89 | 495.46 | 0.014 | 0.017 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | -7.90 | 0.00234 |
GUESTROOM401 | 633.46 | 760.15 | 0.022 | 0.026 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 22:30:00 | -7.90 | 0.00234 |
GUESTROOM402_405 | 1668.80 | 2002.56 | 0.057 | 0.069 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -7.90 | 0.00234 |
GUESTROOM406_408 | 1406.45 | 1687.74 | 0.048 | 0.058 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:45:00 | -7.90 | 0.00234 |
GUESTROOM409_412 | 1676.33 | 2011.60 | 0.057 | 0.069 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -7.90 | 0.00234 |
GUESTROOM413 | 743.83 | 892.60 | 0.025 | 0.031 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 23:45:00 | -7.90 | 0.00234 |
GUESTROOM414 | 701.78 | 842.14 | 0.024 | 0.029 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 21:00:00 | -7.90 | 0.00234 |
GUESTROOM415_418 | 1651.42 | 1981.71 | 0.057 | 0.068 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 17:00:00 | -7.90 | 0.00234 |
GUESTROOM419 | 484.40 | 581.28 | 0.017 | 0.020 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -7.90 | 0.00234 |
GUESTROOM420_423 | 1617.01 | 1940.41 | 0.055 | 0.067 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -7.90 | 0.00234 |
GUESTROOM424 | 656.48 | 787.78 | 0.023 | 0.027 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -7.90 | 0.00234 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
CORRIDORFLR1 | 13976.51 | 16771.81 | 0.479 | 0.574 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -7.90 | 0.00234 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
CORRIDORFLR2 | 406.40 | 487.68 | 0.014 | 0.038 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -7.90 | 0.00234 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
CORRIDORFLR3 | 629.33 | 755.20 | 0.022 | 0.038 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -7.90 | 0.00234 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 | |
CORRIDORFLR4 | 1572.79 | 1887.35 | 0.054 | 0.065 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -7.90 | 0.00234 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB | -7.90 | 0.00234 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.37 | 0.37 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.91 | 0.91 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.43 | 0.43 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.84 | 0.84 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.91 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1623.00 | 6657.50 | 762.75 |
RESTROOMFLR1 | 163.75 | 7251.00 | 11.75 |
MEETINGROOMFLR1 | 875.50 | 3120.25 | 77.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 488.25 | 8760.00 | 488.25 |
GUESTROOM104 | 15.00 | 8753.50 | 15.00 |
GUESTROOM105 | 0.00 | 8386.00 | 0.00 |
EMPLOYEELOUNGEFLR1 | 2797.75 | 2241.25 | 187.75 |
EXERCISECENTERFLR1 | 1496.50 | 2434.00 | 4.25 |
FRONTOFFICEFLR1 | 922.75 | 5919.75 | 48.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 120.50 | 8544.25 | 120.50 |
GUESTROOM206_208 | 62.25 | 8550.25 | 62.25 |
GUESTROOM209_212 | 47.50 | 8721.50 | 47.50 |
GUESTROOM213 | 614.75 | 8757.50 | 614.75 |
GUESTROOM214 | 6.75 | 8499.25 | 6.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 4662.25 | 3831.25 | 711.75 |
GUESTROOM220_223 | 0.00 | 8312.75 | 0.00 |
GUESTROOM224 | 9.00 | 8409.50 | 9.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 153.25 | 8724.00 | 153.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 59.50 | 8508.75 | 59.50 |
GUESTROOM315_318 | 6.25 | 8171.75 | 0.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 4.25 | 8411.00 | 4.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2777.00 | 7869.50 | 2465.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1223.00 | 7813.50 | 854.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 808.75 | 7185.50 | 183.00 |
GUESTROOM419 | 533.50 | 7557.75 | 142.75 |
GUESTROOM420_423 | 824.25 | 7254.75 | 221.50 |
GUESTROOM424 | 976.75 | 7753.00 | 605.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7304.50 | 8760.00 | 5642.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 1.50 | 802.75 | 1.50 | 802.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 1.00 | 27.25 | 1.00 | 27.25 |
GUESTROOM104 | 0.00 | 31.25 | 0.00 | 31.25 |
GUESTROOM105 | 0.00 | 38.50 | 0.00 | 38.50 |
EMPLOYEELOUNGEFLR1 | 210.25 | 1200.00 | 171.00 | 541.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 1.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 9.25 | 0.00 | 9.25 |
GUESTROOM206_208 | 0.00 | 20.25 | 0.00 | 20.25 |
GUESTROOM209_212 | 0.00 | 5.00 | 0.00 | 5.00 |
GUESTROOM213 | 2.25 | 11.00 | 2.25 | 11.00 |
GUESTROOM214 | 0.00 | 22.00 | 0.00 | 22.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 3272.25 | 0.00 | 3272.25 |
GUESTROOM220_223 | 0.00 | 12.75 | 0.00 | 12.75 |
GUESTROOM224 | 0.00 | 23.00 | 0.00 | 23.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 5.50 | 0.00 | 5.50 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.75 | 21.00 | 0.75 | 21.00 |
GUESTROOM315_318 | 0.00 | 19.50 | 0.00 | 19.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 12.00 | 0.00 | 12.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4.00 | 29.00 | 4.00 | 29.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 2.00 | 21.50 | 2.00 | 21.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 29.25 | 0.00 | 29.25 |
GUESTROOM419 | 0.50 | 33.50 | 0.50 | 33.50 |
GUESTROOM420_423 | 0.25 | 29.00 | 0.25 | 29.00 |
GUESTROOM424 | 1.00 | 32.75 | 1.00 | 32.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 3786.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 130.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 512.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 219.00 | 5518.75 | 177.75 | 4035.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.369444 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.907555 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.837189 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 264.34 |
CORRIDORFLR1 PTAC HEATING COIL | 18122.04 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 787.90 |
102 PTAC HEATING COIL | 787.90 |
103 PTAC HEATING COIL | 880.55 |
104 PTAC HEATING COIL | 866.09 |
105 PTAC HEATING COIL | 787.84 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 264.28 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 264.34 |
CORRIDORFLR2 PTAC HEATING COIL | 2234.52 |
201 PTAC HEATING COIL | 861.46 |
202_205 PTAC HEATING COIL | 3151.59 |
206_208 PTAC HEATING COIL | 2497.75 |
209_212 PTAC HEATING COIL | 3151.59 |
213 PTAC HEATING COIL | 915.88 |
214 PTAC HEATING COIL | 874.81 |
215_218 PTAC HEATING COIL | 3151.37 |
219 PTAC HEATING COIL | 787.84 |
220_223 PTAC HEATING COIL | 3151.37 |
224 PTAC HEATING COIL | 805.81 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 264.28 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 264.34 |
CORRIDORFLR3 PTAC HEATING COIL | 2234.52 |
301 PTAC HEATING COIL | 906.73 |
302_305 PTAC HEATING COIL | 3151.59 |
306_308 PTAC HEATING COIL | 2497.75 |
309_312 PTAC HEATING COIL | 3151.59 |
313 PTAC HEATING COIL | 998.10 |
314 PTAC HEATING COIL | 949.01 |
315_318 PTAC HEATING COIL | 3151.37 |
319 PTAC HEATING COIL | 787.84 |
320_323 PTAC HEATING COIL | 3151.37 |
324 PTAC HEATING COIL | 890.22 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 264.28 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 264.34 |
CORRIDORFLR4 PTAC HEATING COIL | 3006.94 |
401 PTAC HEATING COIL | 1154.93 |
402_405 PTAC HEATING COIL | 3581.68 |
406_408 PTAC HEATING COIL | 2939.25 |
409_412 PTAC HEATING COIL | 3590.71 |
413 PTAC HEATING COIL | 1287.38 |
414 PTAC HEATING COIL | 1236.89 |
415_418 PTAC HEATING COIL | 3560.71 |
419 PTAC HEATING COIL | 976.03 |
420_423 PTAC HEATING COIL | 3519.41 |
424 PTAC HEATING COIL | 1182.53 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 264.28 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798655 | 0.369444 | 6115.61 |
SAC_FRONTLOUNGE COOLING COIL | 0.766723 | 0.907555 | 16452.20 |
SAC_MEETINGROOM COOLING COIL | 0.733445 | 0.430144 | 8655.63 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.798655 | 0.837189 | 13858.45 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.907555 |
RESTROOMFLR1 DIRECT AIR | 0.053497 |
MEETINGROOMFLR1 DIRECT AIR | 0.430144 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.644587 |
EXERCISECENTERFLR1 DIRECT AIR | 0.139105 |
FRONTOFFICEFLR1 DIRECT AIR | 0.369444 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.369444 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.907555 |
SAC_MEETINGROOM MAIN BRANCH | 0.430144 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.837189 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.369444 |
SAC_FRONTLOUNGE | 0.907555 |
SAC_MEETINGROOM | 0.430144 |
SAC_EXC_EMPLGE_RESTRM | 0.837189 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.369444 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.907555 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.430144 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.837189 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.369444 | 0.369444 | 0.369444 | 0.369444 | 3244.22 | 6115.61 | 1.00 |
SAC_FRONTLOUNGE | 0.907555 | 0.907555 | 0.907555 | 0.907555 | 13598.06 | 16452.20 | 1.00 |
SAC_MEETINGROOM | 0.430144 | 0.430144 | 0.430144 | 0.430144 | 7281.66 | 8655.63 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.837189 | 0.837189 | 0.837189 | 0.837189 | 5515.84 | 13858.45 | 0.166157 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3244.22 |
SAC_FRONTLOUNGE HEATING COIL | 13598.06 |
SAC_MEETINGROOM HEATING COIL | 7281.66 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5515.84 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.430144 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.28 | 2.60 |
February | 19.47 | 4.29 |
March | 20.30 | 8.77 |
April | 21.76 | 13.91 |
May | 22.63 | 17.82 |
June | 24.08 | 23.21 |
July | 24.78 | 25.63 |
August | 24.50 | 24.08 |
September | 23.72 | 20.49 |
October | 22.18 | 13.71 |
November | 20.48 | 6.96 |
December | 19.40 | 2.07 |
Annual Sum or Average | 21.89 | 13.68 |
Minimum of Months | 19.28 | 2.07 |
Maximum of Months | 24.78 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 2.60 |
February | 23.33 | 4.29 |
March | 23.76 | 8.77 |
April | 24.43 | 13.91 |
May | 25.03 | 17.82 |
June | 26.02 | 23.21 |
July | 26.51 | 25.63 |
August | 26.27 | 24.08 |
September | 25.65 | 20.49 |
October | 24.56 | 13.71 |
November | 23.60 | 6.96 |
December | 23.18 | 2.07 |
Annual Sum or Average | 24.63 | 13.68 |
Minimum of Months | 23.17 | 2.07 |
Maximum of Months | 26.51 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.33 | 2.60 |
February | 18.55 | 4.29 |
March | 19.58 | 8.77 |
April | 21.15 | 13.91 |
May | 22.17 | 17.82 |
June | 23.64 | 23.21 |
July | 24.25 | 25.63 |
August | 23.90 | 24.08 |
September | 23.01 | 20.49 |
October | 21.32 | 13.71 |
November | 19.48 | 6.96 |
December | 18.35 | 2.07 |
Annual Sum or Average | 21.16 | 13.68 |
Minimum of Months | 18.33 | 2.07 |
Maximum of Months | 24.25 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | 2.60 |
February | 21.32 | 4.29 |
March | 21.76 | 8.77 |
April | 22.55 | 13.91 |
May | 23.08 | 17.82 |
June | 23.55 | 23.21 |
July | 23.83 | 25.63 |
August | 23.78 | 24.08 |
September | 23.47 | 20.49 |
October | 22.53 | 13.71 |
November | 21.44 | 6.96 |
December | 21.14 | 2.07 |
Annual Sum or Average | 22.48 | 13.68 |
Minimum of Months | 21.14 | 2.07 |
Maximum of Months | 23.83 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 2.60 |
February | 22.00 | 4.29 |
March | 22.42 | 8.77 |
April | 22.96 | 13.91 |
May | 23.32 | 17.82 |
June | 23.65 | 23.21 |
July | 23.75 | 25.63 |
August | 23.67 | 24.08 |
September | 23.44 | 20.49 |
October | 22.91 | 13.71 |
November | 22.28 | 6.96 |
December | 21.86 | 2.07 |
Annual Sum or Average | 22.85 | 13.68 |
Minimum of Months | 21.86 | 2.07 |
Maximum of Months | 23.75 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.77 | 2.60 |
February | 21.99 | 4.29 |
March | 22.69 | 8.77 |
April | 23.28 | 13.91 |
May | 23.60 | 17.82 |
June | 23.80 | 23.21 |
July | 23.87 | 25.63 |
August | 23.87 | 24.08 |
September | 23.77 | 20.49 |
October | 23.27 | 13.71 |
November | 22.39 | 6.96 |
December | 21.62 | 2.07 |
Annual Sum or Average | 23.00 | 13.68 |
Minimum of Months | 21.62 | 2.07 |
Maximum of Months | 23.87 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.35 | 2.60 |
February | 24.51 | 4.29 |
March | 25.04 | 8.77 |
April | 25.67 | 13.91 |
May | 26.13 | 17.82 |
June | 26.67 | 23.21 |
July | 27.65 | 25.63 |
August | 27.99 | 24.08 |
September | 26.96 | 20.49 |
October | 25.82 | 13.71 |
November | 24.98 | 6.96 |
December | 24.32 | 2.07 |
Annual Sum or Average | 25.85 | 13.68 |
Minimum of Months | 24.32 | 2.07 |
Maximum of Months | 27.99 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.94 | 2.60 |
February | 20.25 | 4.29 |
March | 21.19 | 8.77 |
April | 22.23 | 13.91 |
May | 22.82 | 17.82 |
June | 23.21 | 23.21 |
July | 23.33 | 25.63 |
August | 23.32 | 24.08 |
September | 23.18 | 20.49 |
October | 22.23 | 13.71 |
November | 20.89 | 6.96 |
December | 19.84 | 2.07 |
Annual Sum or Average | 21.88 | 13.68 |
Minimum of Months | 19.84 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 2.60 |
February | 19.93 | 4.29 |
March | 20.84 | 8.77 |
April | 21.94 | 13.91 |
May | 22.60 | 17.82 |
June | 23.10 | 23.21 |
July | 23.30 | 25.63 |
August | 23.26 | 24.08 |
September | 23.01 | 20.49 |
October | 21.93 | 13.71 |
November | 20.53 | 6.96 |
December | 19.52 | 2.07 |
Annual Sum or Average | 21.64 | 13.68 |
Minimum of Months | 19.52 | 2.07 |
Maximum of Months | 23.30 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | 2.60 |
February | 21.05 | 4.29 |
March | 21.31 | 8.77 |
April | 21.55 | 13.91 |
May | 21.69 | 17.82 |
June | 21.75 | 23.21 |
July | 21.75 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.54 | 13.71 |
November | 21.22 | 6.96 |
December | 20.89 | 2.07 |
Annual Sum or Average | 21.44 | 13.68 |
Minimum of Months | 20.89 | 2.07 |
Maximum of Months | 21.75 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 2.60 |
February | 21.48 | 4.29 |
March | 21.58 | 8.77 |
April | 21.67 | 13.91 |
May | 21.72 | 17.82 |
June | 21.75 | 23.21 |
July | 21.75 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.69 | 13.71 |
November | 21.63 | 6.96 |
December | 21.46 | 2.07 |
Annual Sum or Average | 21.64 | 13.68 |
Minimum of Months | 21.44 | 2.07 |
Maximum of Months | 21.75 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 2.60 |
February | 21.68 | 4.29 |
March | 21.72 | 8.77 |
April | 21.74 | 13.91 |
May | 21.75 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.74 | 13.71 |
November | 21.73 | 6.96 |
December | 21.67 | 2.07 |
Annual Sum or Average | 21.72 | 13.68 |
Minimum of Months | 21.65 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.13 | 2.60 |
February | 22.17 | 4.29 |
March | 22.38 | 8.77 |
April | 22.60 | 13.91 |
May | 22.66 | 17.82 |
June | 22.45 | 23.21 |
July | 22.27 | 25.63 |
August | 22.28 | 24.08 |
September | 22.38 | 20.49 |
October | 22.42 | 13.71 |
November | 22.29 | 6.96 |
December | 22.14 | 2.07 |
Annual Sum or Average | 22.35 | 13.68 |
Minimum of Months | 22.13 | 2.07 |
Maximum of Months | 22.66 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.72 | 2.60 |
February | 51.80 | 4.29 |
March | 51.95 | 8.77 |
April | 52.30 | 13.91 |
May | 52.50 | 17.82 |
June | 52.95 | 23.21 |
July | 53.27 | 25.63 |
August | 53.28 | 24.08 |
September | 53.15 | 20.49 |
October | 52.74 | 13.71 |
November | 52.19 | 6.96 |
December | 51.82 | 2.07 |
Annual Sum or Average | 52.48 | 13.68 |
Minimum of Months | 51.72 | 2.07 |
Maximum of Months | 53.28 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.90 | 2.60 |
February | 68.95 | 4.29 |
March | 69.20 | 8.77 |
April | 69.70 | 13.91 |
May | 70.04 | 17.82 |
June | 70.69 | 23.21 |
July | 71.08 | 25.63 |
August | 71.01 | 24.08 |
September | 70.76 | 20.49 |
October | 70.12 | 13.71 |
November | 69.39 | 6.96 |
December | 69.00 | 2.07 |
Annual Sum or Average | 69.91 | 13.68 |
Minimum of Months | 68.90 | 2.07 |
Maximum of Months | 71.08 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.05 | 2.60 |
February | 23.13 | 4.29 |
March | 23.36 | 8.77 |
April | 23.69 | 13.91 |
May | 23.82 | 17.82 |
June | 23.88 | 23.21 |
July | 23.89 | 25.63 |
August | 23.89 | 24.08 |
September | 23.89 | 20.49 |
October | 23.70 | 13.71 |
November | 23.37 | 6.96 |
December | 23.09 | 2.07 |
Annual Sum or Average | 23.57 | 13.68 |
Minimum of Months | 23.05 | 2.07 |
Maximum of Months | 23.89 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 2.60 |
February | 22.74 | 4.29 |
March | 23.16 | 8.77 |
April | 23.63 | 13.91 |
May | 23.81 | 17.82 |
June | 23.88 | 23.21 |
July | 23.89 | 25.63 |
August | 23.89 | 24.08 |
September | 23.89 | 20.49 |
October | 23.65 | 13.71 |
November | 23.18 | 6.96 |
December | 22.62 | 2.07 |
Annual Sum or Average | 23.41 | 13.68 |
Minimum of Months | 22.55 | 2.07 |
Maximum of Months | 23.89 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.87 | 2.60 |
February | 19.08 | 4.29 |
March | 20.17 | 8.77 |
April | 21.94 | 13.91 |
May | 22.96 | 17.82 |
June | 24.65 | 23.21 |
July | 25.53 | 25.63 |
August | 25.16 | 24.08 |
September | 24.22 | 20.49 |
October | 22.39 | 13.71 |
November | 20.31 | 6.96 |
December | 18.99 | 2.07 |
Annual Sum or Average | 22.04 | 13.68 |
Minimum of Months | 18.87 | 2.07 |
Maximum of Months | 25.53 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | 2.60 |
February | 21.25 | 4.29 |
March | 21.91 | 8.77 |
April | 22.89 | 13.91 |
May | 23.44 | 17.82 |
June | 24.35 | 23.21 |
July | 24.86 | 25.63 |
August | 24.71 | 24.08 |
September | 24.24 | 20.49 |
October | 23.26 | 13.71 |
November | 22.05 | 6.96 |
December | 21.18 | 2.07 |
Annual Sum or Average | 22.94 | 13.68 |
Minimum of Months | 21.09 | 2.07 |
Maximum of Months | 24.86 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.16 | 2.60 |
February | 19.36 | 4.29 |
March | 20.43 | 8.77 |
April | 22.17 | 13.91 |
May | 23.20 | 17.82 |
June | 24.88 | 23.21 |
July | 25.65 | 25.63 |
August | 25.29 | 24.08 |
September | 24.39 | 20.49 |
October | 22.58 | 13.71 |
November | 20.56 | 6.96 |
December | 19.26 | 2.07 |
Annual Sum or Average | 22.26 | 13.68 |
Minimum of Months | 19.16 | 2.07 |
Maximum of Months | 25.65 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.54 | 2.60 |
February | 22.76 | 4.29 |
March | 23.40 | 8.77 |
April | 23.78 | 13.91 |
May | 23.86 | 17.82 |
June | 23.92 | 23.21 |
July | 23.93 | 25.63 |
August | 23.91 | 24.08 |
September | 23.89 | 20.49 |
October | 23.72 | 13.71 |
November | 23.29 | 6.96 |
December | 22.49 | 2.07 |
Annual Sum or Average | 23.46 | 13.68 |
Minimum of Months | 22.49 | 2.07 |
Maximum of Months | 23.93 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.42 | 2.60 |
February | 17.71 | 4.29 |
March | 19.10 | 8.77 |
April | 21.15 | 13.91 |
May | 22.44 | 17.82 |
June | 24.26 | 23.21 |
July | 24.98 | 25.63 |
August | 24.52 | 24.08 |
September | 23.42 | 20.49 |
October | 21.26 | 13.71 |
November | 18.86 | 6.96 |
December | 17.39 | 2.07 |
Annual Sum or Average | 21.06 | 13.68 |
Minimum of Months | 17.39 | 2.07 |
Maximum of Months | 24.98 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.20 | 2.60 |
February | 19.49 | 4.29 |
March | 20.51 | 8.77 |
April | 22.12 | 13.91 |
May | 22.85 | 17.82 |
June | 23.24 | 23.21 |
July | 23.33 | 25.63 |
August | 23.33 | 24.08 |
September | 23.22 | 20.49 |
October | 21.92 | 13.71 |
November | 19.94 | 6.96 |
December | 19.07 | 2.07 |
Annual Sum or Average | 21.53 | 13.68 |
Minimum of Months | 19.07 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 2.60 |
February | 21.20 | 4.29 |
March | 21.50 | 8.77 |
April | 21.68 | 13.91 |
May | 21.74 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.64 | 13.71 |
November | 21.35 | 6.96 |
December | 21.01 | 2.07 |
Annual Sum or Average | 21.52 | 13.68 |
Minimum of Months | 21.01 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | 2.60 |
February | 21.26 | 4.29 |
March | 21.54 | 8.77 |
April | 21.69 | 13.91 |
May | 21.74 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.66 | 13.71 |
November | 21.40 | 6.96 |
December | 21.07 | 2.07 |
Annual Sum or Average | 21.55 | 13.68 |
Minimum of Months | 21.07 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.22 | 2.60 |
February | 21.30 | 4.29 |
March | 21.58 | 8.77 |
April | 21.70 | 13.91 |
May | 21.74 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.67 | 13.71 |
November | 21.46 | 6.96 |
December | 21.11 | 2.07 |
Annual Sum or Average | 21.57 | 13.68 |
Minimum of Months | 21.11 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 2.60 |
February | 21.01 | 4.29 |
March | 21.32 | 8.77 |
April | 21.60 | 13.91 |
May | 21.71 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.56 | 13.71 |
November | 21.19 | 6.96 |
December | 20.83 | 2.07 |
Annual Sum or Average | 21.43 | 13.68 |
Minimum of Months | 20.83 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 2.60 |
February | 21.56 | 4.29 |
March | 21.66 | 8.77 |
April | 21.72 | 13.91 |
May | 21.74 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.72 | 13.71 |
November | 21.69 | 6.96 |
December | 21.55 | 2.07 |
Annual Sum or Average | 21.68 | 13.68 |
Minimum of Months | 21.51 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 2.60 |
February | 23.24 | 4.29 |
March | 23.32 | 8.77 |
April | 23.33 | 13.91 |
May | 23.33 | 17.82 |
June | 23.33 | 23.21 |
July | 23.33 | 25.63 |
August | 23.33 | 24.08 |
September | 23.33 | 20.49 |
October | 23.32 | 13.71 |
November | 23.32 | 6.96 |
December | 23.22 | 2.07 |
Annual Sum or Average | 23.30 | 13.68 |
Minimum of Months | 23.20 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.52 | 2.60 |
February | 31.64 | 4.29 |
March | 32.06 | 8.77 |
April | 32.64 | 13.91 |
May | 32.94 | 17.82 |
June | 33.46 | 23.21 |
July | 33.77 | 25.63 |
August | 33.70 | 24.08 |
September | 33.49 | 20.49 |
October | 32.89 | 13.71 |
November | 32.13 | 6.96 |
December | 31.55 | 2.07 |
Annual Sum or Average | 32.65 | 13.68 |
Minimum of Months | 31.52 | 2.07 |
Maximum of Months | 33.77 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 2.60 |
February | 22.08 | 4.29 |
March | 22.19 | 8.77 |
April | 22.35 | 13.91 |
May | 22.55 | 17.82 |
June | 22.99 | 23.21 |
July | 23.33 | 25.63 |
August | 23.25 | 24.08 |
September | 23.00 | 20.49 |
October | 22.57 | 13.71 |
November | 22.18 | 6.96 |
December | 21.99 | 2.07 |
Annual Sum or Average | 22.54 | 13.68 |
Minimum of Months | 21.99 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 2.60 |
February | 21.65 | 4.29 |
March | 21.71 | 8.77 |
April | 21.74 | 13.91 |
May | 21.75 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.73 | 13.71 |
November | 21.73 | 6.96 |
December | 21.63 | 2.07 |
Annual Sum or Average | 21.71 | 13.68 |
Minimum of Months | 21.60 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 2.60 |
February | 21.56 | 4.29 |
March | 21.66 | 8.77 |
April | 21.73 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.76 | 20.49 |
October | 21.72 | 13.71 |
November | 21.70 | 6.96 |
December | 21.54 | 2.07 |
Annual Sum or Average | 21.68 | 13.68 |
Minimum of Months | 21.51 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | 2.60 |
February | 20.69 | 4.29 |
March | 21.60 | 8.77 |
April | 22.90 | 13.91 |
May | 23.64 | 17.82 |
June | 24.78 | 23.21 |
July | 25.40 | 25.63 |
August | 25.17 | 24.08 |
September | 24.55 | 20.49 |
October | 23.25 | 13.71 |
November | 21.69 | 6.96 |
December | 20.55 | 2.07 |
Annual Sum or Average | 22.90 | 13.68 |
Minimum of Months | 20.50 | 2.07 |
Maximum of Months | 25.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.26 | 2.60 |
February | 18.52 | 4.29 |
March | 20.05 | 8.77 |
April | 22.33 | 13.91 |
May | 23.64 | 17.82 |
June | 25.72 | 23.21 |
July | 26.76 | 25.63 |
August | 26.24 | 24.08 |
September | 25.02 | 20.49 |
October | 22.70 | 13.71 |
November | 20.05 | 6.96 |
December | 18.33 | 2.07 |
Annual Sum or Average | 22.32 | 13.68 |
Minimum of Months | 18.26 | 2.07 |
Maximum of Months | 26.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.42 | 2.60 |
February | 18.69 | 4.29 |
March | 19.95 | 8.77 |
April | 21.99 | 13.91 |
May | 23.21 | 17.82 |
June | 25.09 | 23.21 |
July | 25.93 | 25.63 |
August | 25.53 | 24.08 |
September | 24.49 | 20.49 |
October | 22.36 | 13.71 |
November | 20.00 | 6.96 |
December | 18.50 | 2.07 |
Annual Sum or Average | 22.03 | 13.68 |
Minimum of Months | 18.42 | 2.07 |
Maximum of Months | 25.93 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.43 | 2.60 |
February | 21.65 | 4.29 |
March | 22.34 | 8.77 |
April | 23.31 | 13.91 |
May | 23.67 | 17.82 |
June | 23.86 | 23.21 |
July | 23.89 | 25.63 |
August | 23.89 | 24.08 |
September | 23.87 | 20.49 |
October | 23.22 | 13.71 |
November | 22.06 | 6.96 |
December | 21.35 | 2.07 |
Annual Sum or Average | 22.88 | 13.68 |
Minimum of Months | 21.35 | 2.07 |
Maximum of Months | 23.89 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.24 | 2.60 |
February | 16.63 | 4.29 |
March | 18.29 | 8.77 |
April | 20.83 | 13.91 |
May | 22.44 | 17.82 |
June | 24.56 | 23.21 |
July | 25.40 | 25.63 |
August | 24.88 | 24.08 |
September | 23.59 | 20.49 |
October | 20.87 | 13.71 |
November | 17.87 | 6.96 |
December | 16.18 | 2.07 |
Annual Sum or Average | 20.67 | 13.68 |
Minimum of Months | 16.18 | 2.07 |
Maximum of Months | 25.40 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.97 | 2.60 |
February | 19.18 | 4.29 |
March | 19.92 | 8.77 |
April | 21.75 | 13.91 |
May | 22.67 | 17.82 |
June | 23.19 | 23.21 |
July | 23.33 | 25.63 |
August | 23.32 | 24.08 |
September | 23.14 | 20.49 |
October | 21.52 | 13.71 |
November | 19.38 | 6.96 |
December | 18.91 | 2.07 |
Annual Sum or Average | 21.28 | 13.68 |
Minimum of Months | 18.91 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.02 | 2.60 |
February | 19.27 | 4.29 |
March | 20.13 | 8.77 |
April | 21.85 | 13.91 |
May | 22.76 | 17.82 |
June | 23.23 | 23.21 |
July | 23.33 | 25.63 |
August | 23.33 | 24.08 |
September | 23.20 | 20.49 |
October | 21.63 | 13.71 |
November | 19.54 | 6.96 |
December | 18.94 | 2.07 |
Annual Sum or Average | 21.36 | 13.68 |
Minimum of Months | 18.94 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.07 | 2.60 |
February | 19.34 | 4.29 |
March | 20.28 | 8.77 |
April | 21.91 | 13.91 |
May | 22.76 | 17.82 |
June | 23.22 | 23.21 |
July | 23.33 | 25.63 |
August | 23.32 | 24.08 |
September | 23.18 | 20.49 |
October | 21.67 | 13.71 |
November | 19.66 | 6.96 |
December | 18.97 | 2.07 |
Annual Sum or Average | 21.40 | 13.68 |
Minimum of Months | 18.97 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 2.60 |
February | 21.21 | 4.29 |
March | 21.50 | 8.77 |
April | 21.67 | 13.91 |
May | 21.73 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.62 | 13.71 |
November | 21.35 | 6.96 |
December | 20.99 | 2.07 |
Annual Sum or Average | 21.52 | 13.68 |
Minimum of Months | 20.99 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.00 | 2.60 |
February | 19.25 | 4.29 |
March | 20.07 | 8.77 |
April | 21.76 | 13.91 |
May | 22.67 | 17.82 |
June | 23.21 | 23.21 |
July | 23.33 | 25.63 |
August | 23.32 | 24.08 |
September | 23.17 | 20.49 |
October | 21.61 | 13.71 |
November | 19.58 | 6.96 |
December | 18.94 | 2.07 |
Annual Sum or Average | 21.34 | 13.68 |
Minimum of Months | 18.94 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 2.60 |
February | 21.41 | 4.29 |
March | 21.55 | 8.77 |
April | 21.68 | 13.91 |
May | 21.72 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.68 | 13.71 |
November | 21.60 | 6.96 |
December | 21.37 | 2.07 |
Annual Sum or Average | 21.62 | 13.68 |
Minimum of Months | 21.36 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 2.60 |
February | 21.67 | 4.29 |
March | 21.72 | 8.77 |
April | 21.74 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.73 | 13.71 |
November | 21.73 | 6.96 |
December | 21.65 | 2.07 |
Annual Sum or Average | 21.72 | 13.68 |
Minimum of Months | 21.62 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.45 | 2.60 |
February | 23.66 | 4.29 |
March | 24.27 | 8.77 |
April | 25.16 | 13.91 |
May | 25.59 | 17.82 |
June | 26.16 | 23.21 |
July | 26.45 | 25.63 |
August | 26.37 | 24.08 |
September | 26.11 | 20.49 |
October | 25.30 | 13.71 |
November | 24.24 | 6.96 |
December | 23.48 | 2.07 |
Annual Sum or Average | 25.03 | 13.68 |
Minimum of Months | 23.45 | 2.07 |
Maximum of Months | 26.45 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 2.60 |
February | 22.30 | 4.29 |
March | 22.81 | 8.77 |
April | 23.18 | 13.91 |
May | 23.29 | 17.82 |
June | 23.33 | 23.21 |
July | 23.33 | 25.63 |
August | 23.33 | 24.08 |
September | 23.33 | 20.49 |
October | 23.14 | 13.71 |
November | 22.81 | 6.96 |
December | 22.11 | 2.07 |
Annual Sum or Average | 22.92 | 13.68 |
Minimum of Months | 22.03 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 2.60 |
February | 21.59 | 4.29 |
March | 21.67 | 8.77 |
April | 21.72 | 13.91 |
May | 21.74 | 17.82 |
June | 21.75 | 23.21 |
July | 21.76 | 25.63 |
August | 21.75 | 24.08 |
September | 21.75 | 20.49 |
October | 21.71 | 13.71 |
November | 21.70 | 6.96 |
December | 21.56 | 2.07 |
Annual Sum or Average | 21.69 | 13.68 |
Minimum of Months | 21.53 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.39 | 2.60 |
February | 20.66 | 4.29 |
March | 21.48 | 8.77 |
April | 22.48 | 13.91 |
May | 22.91 | 17.82 |
June | 23.24 | 23.21 |
July | 23.33 | 25.63 |
August | 23.33 | 24.08 |
September | 23.26 | 20.49 |
October | 22.54 | 13.71 |
November | 21.48 | 6.96 |
December | 20.34 | 2.07 |
Annual Sum or Average | 22.13 | 13.68 |
Minimum of Months | 20.34 | 2.07 |
Maximum of Months | 23.33 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | 2.60 |
February | 19.83 | 4.29 |
March | 21.02 | 8.77 |
April | 22.72 | 13.91 |
May | 23.67 | 17.82 |
June | 25.06 | 23.21 |
July | 25.78 | 25.63 |
August | 25.48 | 24.08 |
September | 24.71 | 20.49 |
October | 23.01 | 13.71 |
November | 21.00 | 6.96 |
December | 19.56 | 2.07 |
Annual Sum or Average | 22.63 | 13.68 |
Minimum of Months | 19.55 | 2.07 |
Maximum of Months | 25.78 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.38 | 2.60 |
February | 17.72 | 4.29 |
March | 19.51 | 8.77 |
April | 22.17 | 13.91 |
May | 23.71 | 17.82 |
June | 26.04 | 23.21 |
July | 27.20 | 25.63 |
August | 26.60 | 24.08 |
September | 25.20 | 20.49 |
October | 22.48 | 13.71 |
November | 19.39 | 6.96 |
December | 17.41 | 2.07 |
Annual Sum or Average | 22.09 | 13.68 |
Minimum of Months | 17.38 | 2.07 |
Maximum of Months | 27.20 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.16 | 2.60 |
February | 17.64 | 4.29 |
March | 19.18 | 8.77 |
April | 21.72 | 13.91 |
May | 23.24 | 17.82 |
June | 25.48 | 23.21 |
July | 26.48 | 25.63 |
August | 25.99 | 24.08 |
September | 24.65 | 20.49 |
October | 21.94 | 13.71 |
November | 19.00 | 6.96 |
December | 17.18 | 2.07 |
Annual Sum or Average | 21.66 | 13.68 |
Minimum of Months | 17.16 | 2.07 |
Maximum of Months | 26.48 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.40 | 2.60 |
February | 21.58 | 4.29 |
March | 21.99 | 8.77 |
April | 22.80 | 13.91 |
May | 23.28 | 17.82 |
June | 23.81 | 23.21 |
July | 24.08 | 25.63 |
August | 23.98 | 24.08 |
September | 23.63 | 20.49 |
October | 22.72 | 13.71 |
November | 21.71 | 6.96 |
December | 21.30 | 2.07 |
Annual Sum or Average | 22.70 | 13.68 |
Minimum of Months | 21.30 | 2.07 |
Maximum of Months | 24.08 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.34 | 2.60 |
February | 15.90 | 4.29 |
March | 17.74 | 8.77 |
April | 20.63 | 13.91 |
May | 22.47 | 17.82 |
June | 24.89 | 23.21 |
July | 25.86 | 25.63 |
August | 25.27 | 24.08 |
September | 23.69 | 20.49 |
October | 20.50 | 13.71 |
November | 17.09 | 6.96 |
December | 15.23 | 2.07 |
Annual Sum or Average | 20.41 | 13.68 |
Minimum of Months | 15.23 | 2.07 |
Maximum of Months | 25.86 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 2.60 |
February | 20.97 | 4.29 |
March | 21.34 | 8.77 |
April | 21.64 | 13.91 |
May | 21.73 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.53 | 13.71 |
November | 21.13 | 6.96 |
December | 20.66 | 2.07 |
Annual Sum or Average | 21.40 | 13.68 |
Minimum of Months | 20.66 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.06 | 2.60 |
February | 19.30 | 4.29 |
March | 20.01 | 8.77 |
April | 21.46 | 13.91 |
May | 22.38 | 17.82 |
June | 23.03 | 23.21 |
July | 23.31 | 25.63 |
August | 23.27 | 24.08 |
September | 22.89 | 20.49 |
October | 21.22 | 13.71 |
November | 19.37 | 6.96 |
December | 18.94 | 2.07 |
Annual Sum or Average | 21.20 | 13.68 |
Minimum of Months | 18.94 | 2.07 |
Maximum of Months | 23.31 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.09 | 2.60 |
February | 19.34 | 4.29 |
March | 20.07 | 8.77 |
April | 21.47 | 13.91 |
May | 22.37 | 17.82 |
June | 23.02 | 23.21 |
July | 23.31 | 25.63 |
August | 23.26 | 24.08 |
September | 22.86 | 20.49 |
October | 21.23 | 13.71 |
November | 19.42 | 6.96 |
December | 18.95 | 2.07 |
Annual Sum or Average | 21.21 | 13.68 |
Minimum of Months | 18.95 | 2.07 |
Maximum of Months | 23.31 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 2.60 |
February | 21.27 | 4.29 |
March | 21.56 | 8.77 |
April | 21.70 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.63 | 13.71 |
November | 21.43 | 6.96 |
December | 20.97 | 2.07 |
Annual Sum or Average | 21.54 | 13.68 |
Minimum of Months | 20.97 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.03 | 2.60 |
February | 19.28 | 4.29 |
March | 19.96 | 8.77 |
April | 21.46 | 13.91 |
May | 22.36 | 17.82 |
June | 23.04 | 23.21 |
July | 23.31 | 25.63 |
August | 23.26 | 24.08 |
September | 22.91 | 20.49 |
October | 21.28 | 13.71 |
November | 19.40 | 6.96 |
December | 18.93 | 2.07 |
Annual Sum or Average | 21.20 | 13.68 |
Minimum of Months | 18.93 | 2.07 |
Maximum of Months | 23.31 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.88 | 2.60 |
February | 20.16 | 4.29 |
March | 20.73 | 8.77 |
April | 21.87 | 13.91 |
May | 22.51 | 17.82 |
June | 23.06 | 23.21 |
July | 23.32 | 25.63 |
August | 23.28 | 24.08 |
September | 23.01 | 20.49 |
October | 21.91 | 13.71 |
November | 20.59 | 6.96 |
December | 19.82 | 2.07 |
Annual Sum or Average | 21.69 | 13.68 |
Minimum of Months | 19.82 | 2.07 |
Maximum of Months | 23.32 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 2.60 |
February | 21.62 | 4.29 |
March | 21.68 | 8.77 |
April | 21.73 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.71 | 13.71 |
November | 21.70 | 6.96 |
December | 21.58 | 2.07 |
Annual Sum or Average | 21.70 | 13.68 |
Minimum of Months | 21.55 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 2.60 |
February | 21.40 | 4.29 |
March | 22.13 | 8.77 |
April | 23.29 | 13.91 |
May | 23.93 | 17.82 |
June | 24.78 | 23.21 |
July | 25.21 | 25.63 |
August | 25.05 | 24.08 |
September | 24.49 | 20.49 |
October | 23.28 | 13.71 |
November | 21.92 | 6.96 |
December | 21.04 | 2.07 |
Annual Sum or Average | 23.14 | 13.68 |
Minimum of Months | 21.04 | 2.07 |
Maximum of Months | 25.21 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 2.60 |
February | 21.59 | 4.29 |
March | 21.67 | 8.77 |
April | 21.73 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.71 | 13.71 |
November | 21.69 | 6.96 |
December | 21.55 | 2.07 |
Annual Sum or Average | 21.69 | 13.68 |
Minimum of Months | 21.51 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 2.60 |
February | 21.60 | 4.29 |
March | 21.68 | 8.77 |
April | 21.73 | 13.91 |
May | 21.75 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.70 | 13.71 |
November | 21.70 | 6.96 |
December | 21.56 | 2.07 |
Annual Sum or Average | 21.69 | 13.68 |
Minimum of Months | 21.53 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 2.60 |
February | 21.46 | 4.29 |
March | 21.59 | 8.77 |
April | 21.71 | 13.91 |
May | 21.74 | 17.82 |
June | 21.76 | 23.21 |
July | 21.76 | 25.63 |
August | 21.76 | 24.08 |
September | 21.75 | 20.49 |
October | 21.68 | 13.71 |
November | 21.63 | 6.96 |
December | 21.40 | 2.07 |
Annual Sum or Average | 21.63 | 13.68 |
Minimum of Months | 21.36 | 2.07 |
Maximum of Months | 21.76 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.87 | 2.60 |
February | 19.32 | 4.29 |
March | 20.63 | 8.77 |
April | 22.56 | 13.91 |
May | 23.65 | 17.82 |
June | 25.25 | 23.21 |
July | 26.05 | 25.63 |
August | 25.69 | 24.08 |
September | 24.65 | 20.49 |
October | 22.63 | 13.71 |
November | 20.39 | 6.96 |
December | 18.85 | 2.07 |
Annual Sum or Average | 22.39 | 13.68 |
Minimum of Months | 18.85 | 2.07 |
Maximum of Months | 26.05 | 25.63 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.47 | 2.60 |
February | 17.00 | 4.29 |
March | 19.00 | 8.77 |
April | 21.98 | 13.91 |
May | 23.71 | 17.82 |
June | 26.34 | 23.21 |
July | 27.59 | 25.63 |
August | 26.92 | 24.08 |
September | 25.23 | 20.49 |
October | 22.09 | 13.71 |
November | 18.64 | 6.96 |
December | 16.46 | 2.07 |
Annual Sum or Average | 21.81 | 13.68 |
Minimum of Months | 16.46 | 2.07 |
Maximum of Months | 27.59 | 25.63 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.144004E+12 | 100284.503 | 17-JAN-07:15 | 15177.258 | 39465.561 | 9045.947 | 31982.191 | 417.432 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.127007E+12 | 98869.664 | 05-FEB-07:15 | 15177.258 | 39465.561 | 9045.947 | 34670.679 | 502.106 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.133603E+12 | 87003.667 | 05-MAR-07:15 | 15177.258 | 39465.561 | 9045.947 | 22077.773 | 1229.014 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.131846E+12 | 82392.636 | 28-APR-07:00 | 17641.054 | 43276.576 | 9527.755 | 0.000 | 11939.139 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.142609E+12 | 86353.697 | 19-MAY-07:00 | 17566.637 | 43276.576 | 9527.755 | 0.000 | 15974.617 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.151671E+12 | 92292.101 | 24-JUN-07:00 | 17492.219 | 43276.576 | 9527.755 | 0.000 | 21987.439 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.167332E+12 | 95495.036 | 21-JUL-07:00 | 17789.888 | 43276.576 | 9527.755 | 0.000 | 24892.704 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.163244E+12 | 92441.027 | 12-AUG-07:00 | 17566.637 | 43276.576 | 9527.755 | 0.000 | 22061.947 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.148125E+12 | 89890.971 | 03-SEP-07:00 | 17641.054 | 43276.576 | 9527.755 | 0.000 | 19437.474 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.140849E+12 | 90540.945 | 26-OCT-06:15 | 15177.258 | 39465.561 | 9045.947 | 21559.992 | 1096.074 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.131059E+12 | 90825.300 | 27-NOV-07:15 | 15177.258 | 39465.561 | 9045.947 | 26199.035 | 929.385 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.144344E+12 | 100464.571 | 22-DEC-07:15 | 13316.689 | 34010.661 | 9045.947 | 39674.974 | 220.187 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.172569E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.127007E+12 | 82392.636 | 13316.689 | 34010.661 | 9045.947 | 0.000 | 220.187 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.167332E+12 | 100464.571 | 17789.888 | 43276.576 | 9527.755 | 39674.974 | 24892.704 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.100398E+12 | 102477.739 | 19-JAN-10:15 | 5990.399 | 40096.028 | 0.000 | 56391.312 | 56391.312 | 56391.312 | 5990.399 |
February | 0.897515E+11 | 102965.798 | 05-FEB-10:15 | 6292.549 | 40096.028 | 0.000 | 56577.222 | 56577.222 | 56577.222 | 6292.549 |
March | 0.942180E+11 | 98339.300 | 04-MAR-09:15 | 76.310 | 40096.028 | 0.000 | 58166.962 | 58166.962 | 58166.962 | 76.310 |
April | 0.864855E+11 | 95736.396 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 55640.368 | 55640.368 | 55640.368 | 0.000 |
May | 0.851804E+11 | 92015.663 | 06-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 51919.635 | 51919.635 | 51919.635 | 0.000 |
June | 0.790614E+11 | 90196.731 | 02-JUN-08:45 | 0.000 | 40096.028 | 0.000 | 50100.703 | 50100.703 | 50100.703 | 0.000 |
July | 0.800546E+11 | 74480.398 | 01-JUL-09:15 | 0.000 | 40096.028 | 0.000 | 34384.370 | 34384.370 | 34384.370 | 0.000 |
August | 0.797984E+11 | 74222.025 | 31-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 34125.997 | 34125.997 | 34125.997 | 0.000 |
September | 0.779971E+11 | 87527.330 | 29-SEP-09:30 | 0.000 | 40096.028 | 0.000 | 47431.302 | 47431.302 | 47431.302 | 0.000 |
October | 0.842465E+11 | 91009.986 | 27-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 50913.958 | 50913.958 | 50913.958 | 0.000 |
November | 0.873167E+11 | 94578.684 | 25-NOV-10:15 | 1455.621 | 40096.028 | 0.000 | 53027.035 | 53027.035 | 53027.035 | 1455.621 |
December | 0.984627E+11 | 102201.028 | 22-DEC-10:15 | 6782.798 | 40096.028 | 0.000 | 55322.202 | 55322.202 | 55322.202 | 6782.798 |
Annual Sum or Average | 0.104297E+13 | 0.000 | ||||||||
Minimum of Months | 0.779971E+11 | 74222.025 | 0.000 | 40096.028 | 0.000 | 34125.997 | 34125.997 | 34125.997 | 0.000 | |
Maximum of Months | 0.100398E+12 | 102965.798 | 6782.798 | 40096.028 | 0.000 | 58166.962 | 58166.962 | 58166.962 | 6782.798 |