Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Simulation Timestamp: 2018-10-19 10:15:40
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3767.62 | 938.72 | 1011.42 |
Net Site Energy | 3767.62 | 938.72 | 1011.42 |
Total Source Energy | 8744.74 | 2178.79 | 2347.52 |
Net Source Energy | 8744.74 | 2178.79 | 2347.52 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 775.50 | 319.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 111.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 415.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 789.23 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2237.46 | 1530.16 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 775.50 | 319.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 111.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 415.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 278.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 789.23 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 313.00 | 297.62 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 600.65 | 410.77 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 290.50 | 276.23 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 557.47 | 381.24 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2237.46 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2237.46 | 100.00 |
Total On-Site and Utility Electric Sources | 2237.46 | 100.00 |
Total Electricity End Uses | 2237.46 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2740.00 |
Time Setpoint Not Met During Occupied Cooling | 1823.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6532.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Weather File | Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 |
Latitude [deg] | 64.82 |
Longitude [deg] | -147.8 |
Elevation [m] | 133.00 |
Time Zone | -9.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00 | -41.90 | Wetbulb [C] | 0.30 | 20.00 |
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 10.20 | 16.10 | Wetbulb [C] | 3.10 | 180.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.210 | 0.217 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.670 | 0.479 | 0.381 | ||||||||||||
North Total or Average | 96.82 | 2.670 | 0.479 | 0.381 | ||||||||||||
Non-North Total or Average | 87.38 | 2.670 | 0.479 | 0.381 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5877.42 | 4694.03 | 1183.39 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12389.35 | 9601.28 | 2788.07 | 0.77 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6518.35 | 4844.04 | 1674.31 | 0.74 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11931.59 | 9529.23 | 2402.36 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5601.9 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11845.9 | 3.19 | 10.90 | 11.54 | 10.75 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6258.8 | 3.25 | 11.09 | 11.75 | 11.04 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11372.3 | 3.15 | 10.76 | 11.39 | 10.54 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 53556.02 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1564.20 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1607.79 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1899.86 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1901.88 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1610.70 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 4245.08 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1741.37 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 5987.31 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 4745.15 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 5987.31 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1761.57 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1721.39 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 5986.89 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1496.72 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 5986.89 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1654.73 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 4245.08 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1800.60 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 6029.93 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 4939.65 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 6019.48 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1865.91 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1809.91 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 5988.89 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1532.37 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 5986.89 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1765.86 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.32 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.40 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 6480.73 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 2334.30 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 7907.36 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 6494.59 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 7916.63 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2490.28 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 2429.60 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 7875.76 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 2124.47 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 7823.34 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 2386.67 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 679.21 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 6313.05 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 25833.24 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 13833.51 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 10624.76 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.36 | 397.70 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.70 | 784.31 | 1120.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 374.47 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 798.03 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 6967.88 | 8361.46 | 0.584 | 0.700 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 27.25 | 0.00698 |
RESTROOMFLR1 | 365.26 | 438.31 | 0.031 | 0.037 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 26.18 | 0.00698 |
MEETINGROOMFLR1 | 3324.51 | 3989.41 | 0.279 | 0.334 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM101 | 468.34 | 562.00 | 0.054 | 0.065 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM102 | 374.37 | 449.25 | 0.044 | 0.052 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM103 | 934.51 | 1121.41 | 0.109 | 0.130 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM104 | 1260.35 | 1512.42 | 0.147 | 0.176 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM105 | 1666.64 | 1999.97 | 0.194 | 0.233 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
EMPLOYEELOUNGEFLR1 | 5561.98 | 6674.37 | 0.466 | 0.559 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
EXERCISECENTERFLR1 | 1245.34 | 1494.41 | 0.104 | 0.125 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 25.97 | 0.00698 |
FRONTOFFICEFLR1 | 3536.06 | 4243.28 | 0.296 | 0.355 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
GUESTROOM201 | 605.07 | 726.08 | 0.070 | 0.084 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 27.27 | 0.00698 |
GUESTROOM202_205 | 3861.84 | 4634.21 | 0.449 | 0.539 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM206_208 | 3166.59 | 3799.91 | 0.368 | 0.442 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM209_212 | 3686.19 | 4423.42 | 0.429 | 0.515 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM213 | 1013.25 | 1215.90 | 0.118 | 0.141 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM214 | 1392.85 | 1671.42 | 0.162 | 0.194 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM215_218 | 10144.65 | 12173.58 | 1.180 | 1.416 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM219 | 5611.15 | 6733.38 | 0.653 | 0.783 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM220_223 | 5014.93 | 6017.91 | 0.583 | 0.700 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
GUESTROOM224 | 1402.52 | 1683.03 | 0.163 | 0.196 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
GUESTROOM301 | 417.36 | 500.83 | 0.049 | 0.058 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
GUESTROOM302_305 | 1290.40 | 1548.48 | 0.150 | 0.180 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM306_308 | 1168.39 | 1402.07 | 0.136 | 0.163 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM309_312 | 3631.17 | 4357.40 | 0.422 | 0.507 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM313 | 506.52 | 607.83 | 0.059 | 0.071 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 21:15:00 | 21.15 | 0.00698 |
GUESTROOM314 | 1303.06 | 1563.67 | 0.152 | 0.182 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM315_318 | 5439.58 | 6527.49 | 0.633 | 0.759 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM319 | 1226.69 | 1472.03 | 0.143 | 0.171 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM320_323 | 4797.40 | 5756.88 | 0.558 | 0.670 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM324 | 816.90 | 980.28 | 0.095 | 0.114 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM401 | 1169.15 | 1402.99 | 0.136 | 0.163 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 27.40 | 0.00698 |
GUESTROOM402_405 | 1787.43 | 2144.92 | 0.208 | 0.250 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM406_408 | 1550.50 | 1860.60 | 0.180 | 0.216 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM409_412 | 4424.75 | 5309.70 | 0.515 | 0.618 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 27.40 | 0.00698 |
GUESTROOM413 | 672.26 | 806.71 | 0.078 | 0.094 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 26.94 | 0.00698 |
GUESTROOM414 | 1055.52 | 1266.62 | 0.123 | 0.147 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
GUESTROOM415_418 | 6033.50 | 7240.20 | 0.702 | 0.842 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
GUESTROOM419 | 1634.98 | 1961.97 | 0.190 | 0.228 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
GUESTROOM420_423 | 5980.76 | 7176.91 | 0.696 | 0.835 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 27.40 | 0.00698 |
GUESTROOM424 | 1627.42 | 1952.90 | 0.189 | 0.227 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 27.40 | 0.00698 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR1 | 12582.58 | 15099.10 | 1.052 | 1.263 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 24.95 | 0.00698 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR2 | 2615.58 | 3138.70 | 0.219 | 0.263 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 25.46 | 0.00698 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR3 | 1197.00 | 1436.40 | 0.100 | 0.120 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 25.21 | 0.00698 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 | |
CORRIDORFLR4 | 1855.14 | 2226.16 | 0.155 | 0.186 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 26.79 | 0.00698 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 27.40 | 0.00698 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2904.87 | 3485.84 | 0.083 | 0.236 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
RESTROOMFLR1 | 247.11 | 296.53 | 0.007 | 0.008 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -41.90 | 0.00006 |
MEETINGROOMFLR1 | 1053.90 | 1264.68 | 0.030 | 0.126 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -41.90 | 0.00006 |
GUESTROOM101 | 448.25 | 537.90 | 0.013 | 0.015 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
GUESTROOM102 | 484.58 | 581.49 | 0.014 | 0.017 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
GUESTROOM103 | 727.97 | 873.56 | 0.021 | 0.025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -41.90 | 0.00006 |
GUESTROOM104 | 729.71 | 875.66 | 0.021 | 0.025 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
GUESTROOM105 | 487.06 | 584.48 | 0.014 | 0.017 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -41.90 | 0.00006 |
EMPLOYEELOUNGEFLR1 | 487.84 | 585.41 | 0.014 | 0.051 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -41.90 | 0.00006 |
EXERCISECENTERFLR1 | 370.32 | 444.38 | 0.011 | 0.043 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -41.90 | 0.00006 |
FRONTOFFICEFLR1 | 1765.06 | 2118.07 | 0.051 | 0.061 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -41.90 | 0.00006 |
GUESTROOM201 | 595.90 | 715.08 | 0.017 | 0.020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -41.90 | 0.00006 |
GUESTROOM202_205 | 1428.30 | 1713.96 | 0.041 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -41.90 | 0.00006 |
GUESTROOM206_208 | 1163.77 | 1396.52 | 0.033 | 0.043 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
GUESTROOM209_212 | 1321.57 | 1585.88 | 0.038 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -41.90 | 0.00006 |
GUESTROOM213 | 612.73 | 735.27 | 0.018 | 0.021 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:30:00 | -41.90 | 0.00006 |
GUESTROOM214 | 579.30 | 695.16 | 0.017 | 0.020 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -41.90 | 0.00006 |
GUESTROOM215_218 | 1347.91 | 1617.49 | 0.039 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -41.90 | 0.00006 |
GUESTROOM219 | 340.98 | 409.18 | 0.010 | 0.013 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -41.90 | 0.00006 |
GUESTROOM220_223 | 1266.49 | 1519.79 | 0.036 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
GUESTROOM224 | 523.76 | 628.51 | 0.015 | 0.018 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -41.90 | 0.00006 |
GUESTROOM301 | 645.25 | 774.30 | 0.018 | 0.022 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -41.90 | 0.00006 |
GUESTROOM302_305 | 1603.95 | 1924.74 | 0.046 | 0.055 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -41.90 | 0.00006 |
GUESTROOM306_308 | 1405.12 | 1686.15 | 0.040 | 0.048 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -41.90 | 0.00006 |
GUESTROOM309_312 | 1595.25 | 1914.29 | 0.046 | 0.055 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:15:00 | -41.90 | 0.00006 |
GUESTROOM313 | 699.68 | 839.62 | 0.020 | 0.024 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM314 | 653.07 | 783.69 | 0.019 | 0.022 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:15:00 | -41.90 | 0.00006 |
GUESTROOM315_318 | 1570.00 | 1884.00 | 0.045 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -41.90 | 0.00006 |
GUESTROOM319 | 421.79 | 506.15 | 0.012 | 0.014 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -41.90 | 0.00006 |
GUESTROOM320_323 | 1522.78 | 1827.34 | 0.044 | 0.054 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -41.90 | 0.00006 |
GUESTROOM324 | 616.36 | 739.64 | 0.018 | 0.021 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -41.90 | 0.00006 |
GUESTROOM401 | 1090.00 | 1308.01 | 0.031 | 0.037 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -41.90 | 0.00006 |
GUESTROOM402_405 | 3168.48 | 3802.18 | 0.091 | 0.109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 21:30:00 | -41.90 | 0.00006 |
GUESTROOM406_408 | 2700.91 | 3241.09 | 0.077 | 0.093 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | -41.90 | 0.00006 |
GUESTROOM409_412 | 3176.20 | 3811.44 | 0.091 | 0.109 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -41.90 | 0.00006 |
GUESTROOM413 | 1219.99 | 1463.99 | 0.035 | 0.042 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM414 | 1169.48 | 1403.37 | 0.033 | 0.040 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
GUESTROOM415_418 | 3142.38 | 3770.86 | 0.090 | 0.108 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -41.90 | 0.00006 |
GUESTROOM419 | 915.21 | 1098.25 | 0.026 | 0.031 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -41.90 | 0.00006 |
GUESTROOM420_423 | 3098.70 | 3718.44 | 0.089 | 0.106 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -41.90 | 0.00006 |
GUESTROOM424 | 1133.71 | 1360.45 | 0.032 | 0.039 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -41.90 | 0.00006 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR1 | 41677.38 | 50012.86 | 1.192 | 1.430 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR2 | 728.64 | 874.36 | 0.021 | 0.038 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR3 | 1004.56 | 1205.48 | 0.029 | 0.038 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:15:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | -41.90 | 0.00006 | |
CORRIDORFLR4 | 2975.09 | 3570.11 | 0.085 | 0.102 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:15:00 | -41.90 | 0.00006 |
FRONTSTAIRSFLR4 | 55.58 | 66.70 | 0.001 | 0.006 | FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:15:00 | -41.90 | 0.00006 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.36 | 0.36 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.70 | 0.70 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.33 | 0.33 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.72 | 0.72 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 4105.50 | 8041.25 | 4076.25 |
RESTROOMFLR1 | 3454.75 | 8669.50 | 3454.75 |
MEETINGROOMFLR1 | 1617.75 | 4117.25 | 1544.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 4491.25 | 8760.00 | 4491.25 |
GUESTROOM104 | 3826.25 | 8760.00 | 3826.25 |
GUESTROOM105 | 1945.75 | 8683.25 | 1945.75 |
EMPLOYEELOUNGEFLR1 | 2435.50 | 3281.75 | 804.25 |
EXERCISECENTERFLR1 | 1067.75 | 4198.50 | 656.25 |
FRONTOFFICEFLR1 | 3296.25 | 7806.00 | 3172.25 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 3866.50 | 8760.00 | 3866.50 |
GUESTROOM206_208 | 3717.75 | 8760.00 | 3717.75 |
GUESTROOM209_212 | 3445.75 | 8760.00 | 3445.75 |
GUESTROOM213 | 4437.25 | 8760.00 | 4437.25 |
GUESTROOM214 | 3364.25 | 8738.50 | 3364.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 2354.25 | 5286.50 | 58.75 |
GUESTROOM220_223 | 2197.25 | 8649.75 | 2197.25 |
GUESTROOM224 | 3469.00 | 8723.75 | 3469.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 3938.25 | 8760.00 | 3938.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 4029.25 | 8744.00 | 4029.25 |
GUESTROOM315_318 | 2309.75 | 8556.75 | 2309.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 3106.75 | 8677.50 | 3106.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 5211.25 | 8630.25 | 5211.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 4573.75 | 8527.75 | 4573.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 4115.00 | 8185.00 | 3994.00 |
GUESTROOM419 | 4079.50 | 8351.25 | 4060.75 |
GUESTROOM420_423 | 4187.50 | 8217.25 | 4079.50 |
GUESTROOM424 | 4591.50 | 8441.50 | 4577.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7559.00 | 8760.00 | 6532.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 1.00 | 0.00 | 1.00 | 0.00 |
RESTROOMFLR1 | 2536.25 | 97.50 | 2536.25 | 97.50 |
MEETINGROOMFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
GUESTROOM101 | 1.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 42.25 | 11.00 | 42.25 | 11.00 |
GUESTROOM104 | 32.75 | 18.00 | 32.75 | 18.00 |
GUESTROOM105 | 15.75 | 29.25 | 15.75 | 29.25 |
EMPLOYEELOUNGEFLR1 | 1570.25 | 522.25 | 1102.50 | 333.50 |
EXERCISECENTERFLR1 | 1.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
GUESTROOM201 | 1.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 39.75 | 0.50 | 39.75 | 0.50 |
GUESTROOM206_208 | 38.50 | 5.25 | 38.50 | 5.25 |
GUESTROOM209_212 | 38.75 | 0.25 | 38.75 | 0.25 |
GUESTROOM213 | 41.00 | 0.00 | 41.00 | 0.00 |
GUESTROOM214 | 29.75 | 6.75 | 29.75 | 6.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 1466.25 | 0.00 | 1466.25 |
GUESTROOM220_223 | 21.50 | 3.75 | 21.50 | 3.75 |
GUESTROOM224 | 32.25 | 7.00 | 32.25 | 7.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.25 | 0.00 | 0.00 |
GUESTROOM309_312 | 41.00 | 0.25 | 41.00 | 0.25 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 33.25 | 5.25 | 33.25 | 5.25 |
GUESTROOM315_318 | 24.00 | 7.00 | 24.00 | 7.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 30.50 | 3.00 | 30.50 | 3.00 |
GUESTROOM324 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 26.75 | 6.25 | 26.75 | 6.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 30.50 | 2.75 | 30.50 | 2.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 27.25 | 11.50 | 27.25 | 11.50 |
GUESTROOM419 | 22.00 | 15.75 | 22.00 | 15.75 |
GUESTROOM420_423 | 27.50 | 10.50 | 27.50 | 10.50 |
GUESTROOM424 | 18.00 | 13.75 | 18.00 | 13.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 1.00 | 1508.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 2.75 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 1.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 9.50 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 13.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 6.50 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2778.75 | 2414.50 | 2740.00 | 1823.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:40
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.355055 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.700209 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.720788 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR1 PTAC HEATING COIL | 53556.02 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1564.20 |
102 PTAC HEATING COIL | 1607.79 |
103 PTAC HEATING COIL | 1899.86 |
104 PTAC HEATING COIL | 1901.88 |
105 PTAC HEATING COIL | 1610.70 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR2 PTAC HEATING COIL | 4245.08 |
201 PTAC HEATING COIL | 1741.37 |
202_205 PTAC HEATING COIL | 5987.31 |
206_208 PTAC HEATING COIL | 4745.15 |
209_212 PTAC HEATING COIL | 5987.31 |
213 PTAC HEATING COIL | 1761.57 |
214 PTAC HEATING COIL | 1721.39 |
215_218 PTAC HEATING COIL | 5986.89 |
219 PTAC HEATING COIL | 1496.72 |
220_223 PTAC HEATING COIL | 5986.89 |
224 PTAC HEATING COIL | 1654.73 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR3 PTAC HEATING COIL | 4245.08 |
301 PTAC HEATING COIL | 1800.60 |
302_305 PTAC HEATING COIL | 6029.93 |
306_308 PTAC HEATING COIL | 4939.65 |
309_312 PTAC HEATING COIL | 6019.48 |
313 PTAC HEATING COIL | 1865.91 |
314 PTAC HEATING COIL | 1809.91 |
315_318 PTAC HEATING COIL | 5988.89 |
319 PTAC HEATING COIL | 1532.37 |
320_323 PTAC HEATING COIL | 5986.89 |
324 PTAC HEATING COIL | 1765.86 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.32 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 316.40 |
CORRIDORFLR4 PTAC HEATING COIL | 6480.73 |
401 PTAC HEATING COIL | 2334.30 |
402_405 PTAC HEATING COIL | 7907.36 |
406_408 PTAC HEATING COIL | 6494.59 |
409_412 PTAC HEATING COIL | 7916.63 |
413 PTAC HEATING COIL | 2490.28 |
414 PTAC HEATING COIL | 2429.60 |
415_418 PTAC HEATING COIL | 7875.76 |
419 PTAC HEATING COIL | 2124.47 |
420_423 PTAC HEATING COIL | 7823.34 |
424 PTAC HEATING COIL | 2386.67 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 679.21 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798655 | 0.355055 | 5877.42 |
SAC_FRONTLOUNGE COOLING COIL | 0.774963 | 0.700209 | 12389.35 |
SAC_MEETINGROOM COOLING COIL | 0.743139 | 0.334314 | 6518.35 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.798655 | 0.720788 | 11931.59 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.700209 |
RESTROOMFLR1 DIRECT AIR | 0.036670 |
MEETINGROOMFLR1 DIRECT AIR | 0.334314 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.559027 |
EXERCISECENTERFLR1 DIRECT AIR | 0.125090 |
FRONTOFFICEFLR1 DIRECT AIR | 0.355055 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.355055 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.700209 |
SAC_MEETINGROOM MAIN BRANCH | 0.334314 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.720788 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.355055 |
SAC_FRONTLOUNGE | 0.700209 |
SAC_MEETINGROOM | 0.334314 |
SAC_EXC_EMPLGE_RESTRM | 0.720788 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.355055 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.700209 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.334314 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.720788 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.355055 | 0.355055 | 0.355055 | 0.355055 | 6313.05 | 5877.42 | 1.00 |
SAC_FRONTLOUNGE | 0.700209 | 0.700209 | 0.700209 | 0.700209 | 25833.24 | 12389.35 | 1.00 |
SAC_MEETINGROOM | 0.334314 | 0.334314 | 0.334314 | 0.334314 | 13833.51 | 6518.35 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.720788 | 0.720788 | 0.720788 | 0.720788 | 10624.76 | 11931.59 | 0.173547 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 6313.05 |
SAC_FRONTLOUNGE HEATING COIL | 25833.24 |
SAC_MEETINGROOM HEATING COIL | 13833.51 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 10624.76 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.334314 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.03 | -17.6 |
February | 15.73 | -15.4 |
March | 16.18 | -10.3 |
April | 18.19 | 0.73 |
May | 20.74 | 10.60 |
June | 22.40 | 15.96 |
July | 22.77 | 16.86 |
August | 22.07 | 14.24 |
September | 20.33 | 6.72 |
October | 17.40 | -3.1 |
November | 16.33 | -17.6 |
December | 15.04 | -19.3 |
Annual Sum or Average | 18.53 | -1.4 |
Minimum of Months | 15.03 | -19.3 |
Maximum of Months | 22.77 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | -17.6 |
February | 21.32 | -15.4 |
March | 21.53 | -10.3 |
April | 22.64 | 0.73 |
May | 23.80 | 10.60 |
June | 24.60 | 15.96 |
July | 24.86 | 16.86 |
August | 24.40 | 14.24 |
September | 23.42 | 6.72 |
October | 22.19 | -3.1 |
November | 21.18 | -17.6 |
December | 21.17 | -19.3 |
Annual Sum or Average | 22.70 | -1.4 |
Minimum of Months | 21.17 | -19.3 |
Maximum of Months | 24.86 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.01 | -17.6 |
February | 15.44 | -15.4 |
March | 15.69 | -10.3 |
April | 17.42 | 0.73 |
May | 20.09 | 10.60 |
June | 21.86 | 15.96 |
July | 22.20 | 16.86 |
August | 21.40 | 14.24 |
September | 19.62 | 6.72 |
October | 16.95 | -3.1 |
November | 16.20 | -17.6 |
December | 15.11 | -19.3 |
Annual Sum or Average | 18.10 | -1.4 |
Minimum of Months | 15.01 | -19.3 |
Maximum of Months | 22.20 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.20 | 0.73 |
May | 22.28 | 10.60 |
June | 23.20 | 15.96 |
July | 23.21 | 16.86 |
August | 22.85 | 14.24 |
September | 21.53 | 6.72 |
October | 21.16 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.75 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.21 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -17.6 |
February | 20.67 | -15.4 |
March | 20.97 | -10.3 |
April | 21.73 | 0.73 |
May | 22.72 | 10.60 |
June | 23.39 | 15.96 |
July | 23.46 | 16.86 |
August | 23.19 | 14.24 |
September | 22.41 | 6.72 |
October | 21.55 | -3.1 |
November | 20.61 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.81 | -1.4 |
Minimum of Months | 20.48 | -19.3 |
Maximum of Months | 23.46 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -17.6 |
February | 21.13 | -15.4 |
March | 21.16 | -10.3 |
April | 21.53 | 0.73 |
May | 22.80 | 10.60 |
June | 23.58 | 15.96 |
July | 23.61 | 16.86 |
August | 23.27 | 14.24 |
September | 22.10 | 6.72 |
October | 21.33 | -3.1 |
November | 21.12 | -17.6 |
December | 21.12 | -19.3 |
Annual Sum or Average | 21.99 | -1.4 |
Minimum of Months | 21.12 | -19.3 |
Maximum of Months | 23.61 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.74 | -17.6 |
February | 22.87 | -15.4 |
March | 23.12 | -10.3 |
April | 23.91 | 0.73 |
May | 25.12 | 10.60 |
June | 25.85 | 15.96 |
July | 25.95 | 16.86 |
August | 25.64 | 14.24 |
September | 24.75 | 6.72 |
October | 23.74 | -3.1 |
November | 22.97 | -17.6 |
December | 22.72 | -19.3 |
Annual Sum or Average | 24.12 | -1.4 |
Minimum of Months | 22.72 | -19.3 |
Maximum of Months | 25.95 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.92 | -10.3 |
April | 19.54 | 0.73 |
May | 21.39 | 10.60 |
June | 22.64 | 15.96 |
July | 22.73 | 16.86 |
August | 22.22 | 14.24 |
September | 20.54 | 6.72 |
October | 19.23 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.24 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.73 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.90 | -10.3 |
April | 19.36 | 0.73 |
May | 21.07 | 10.60 |
June | 22.39 | 15.96 |
July | 22.50 | 16.86 |
August | 21.93 | 14.24 |
September | 20.21 | 6.72 |
October | 19.12 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.09 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.50 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.49 | -10.3 |
April | 20.75 | 0.73 |
May | 21.37 | 10.60 |
June | 21.65 | 15.96 |
July | 21.69 | 16.86 |
August | 21.54 | 14.24 |
September | 21.07 | 6.72 |
October | 20.62 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.92 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.69 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.51 | -15.4 |
March | 20.60 | -10.3 |
April | 21.09 | 0.73 |
May | 21.58 | 10.60 |
June | 21.70 | 15.96 |
July | 21.71 | 16.86 |
August | 21.65 | 14.24 |
September | 21.35 | 6.72 |
October | 20.81 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.04 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.71 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -17.6 |
February | 20.70 | -15.4 |
March | 20.96 | -10.3 |
April | 21.41 | 0.73 |
May | 21.70 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.73 | 14.24 |
September | 21.60 | 6.72 |
October | 21.16 | -3.1 |
November | 20.54 | -17.6 |
December | 20.51 | -19.3 |
Annual Sum or Average | 21.20 | -1.4 |
Minimum of Months | 20.51 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | -17.6 |
February | 21.01 | -15.4 |
March | 21.39 | -10.3 |
April | 21.92 | 0.73 |
May | 22.30 | 10.60 |
June | 22.61 | 15.96 |
July | 22.58 | 16.86 |
August | 22.56 | 14.24 |
September | 22.29 | 6.72 |
October | 21.79 | -3.1 |
November | 20.63 | -17.6 |
December | 20.73 | -19.3 |
Annual Sum or Average | 21.72 | -1.4 |
Minimum of Months | 20.63 | -19.3 |
Maximum of Months | 22.61 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.17 | -17.6 |
February | 49.69 | -15.4 |
March | 50.29 | -10.3 |
April | 51.26 | 0.73 |
May | 52.02 | 10.60 |
June | 52.56 | 15.96 |
July | 52.71 | 16.86 |
August | 52.53 | 14.24 |
September | 51.85 | 6.72 |
October | 50.74 | -3.1 |
November | 49.55 | -17.6 |
December | 49.03 | -19.3 |
Annual Sum or Average | 50.96 | -1.4 |
Minimum of Months | 49.03 | -19.3 |
Maximum of Months | 52.71 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 66.92 | -17.6 |
February | 67.26 | -15.4 |
March | 67.52 | -10.3 |
April | 68.27 | 0.73 |
May | 69.26 | 10.60 |
June | 69.99 | 15.96 |
July | 70.24 | 16.86 |
August | 69.97 | 14.24 |
September | 69.28 | 6.72 |
October | 68.03 | -3.1 |
November | 67.38 | -17.6 |
December | 66.93 | -19.3 |
Annual Sum or Average | 68.43 | -1.4 |
Minimum of Months | 66.92 | -19.3 |
Maximum of Months | 70.24 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | -17.6 |
February | 21.57 | -15.4 |
March | 21.98 | -10.3 |
April | 22.69 | 0.73 |
May | 23.29 | 10.60 |
June | 23.71 | 15.96 |
July | 23.74 | 16.86 |
August | 23.64 | 14.24 |
September | 23.14 | 6.72 |
October | 22.39 | -3.1 |
November | 21.29 | -17.6 |
December | 21.23 | -19.3 |
Annual Sum or Average | 22.50 | -1.4 |
Minimum of Months | 21.23 | -19.3 |
Maximum of Months | 23.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -17.6 |
February | 21.22 | -15.4 |
March | 21.41 | -10.3 |
April | 22.20 | 0.73 |
May | 23.15 | 10.60 |
June | 23.74 | 15.96 |
July | 23.78 | 16.86 |
August | 23.64 | 14.24 |
September | 22.80 | 6.72 |
October | 21.72 | -3.1 |
November | 21.11 | -17.6 |
December | 21.12 | -19.3 |
Annual Sum or Average | 22.26 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.78 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.12 | -17.6 |
February | 14.94 | -15.4 |
March | 15.53 | -10.3 |
April | 17.61 | 0.73 |
May | 20.72 | 10.60 |
June | 22.63 | 15.96 |
July | 23.15 | 16.86 |
August | 22.35 | 14.24 |
September | 20.27 | 6.72 |
October | 16.93 | -3.1 |
November | 15.60 | -17.6 |
December | 14.08 | -19.3 |
Annual Sum or Average | 18.18 | -1.4 |
Minimum of Months | 14.08 | -19.3 |
Maximum of Months | 23.15 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.78 | -17.6 |
February | 18.33 | -15.4 |
March | 18.84 | -10.3 |
April | 20.30 | 0.73 |
May | 22.17 | 10.60 |
June | 23.29 | 15.96 |
July | 23.56 | 16.86 |
August | 23.15 | 14.24 |
September | 21.83 | 6.72 |
October | 19.74 | -3.1 |
November | 18.56 | -17.6 |
December | 17.72 | -19.3 |
Annual Sum or Average | 20.45 | -1.4 |
Minimum of Months | 17.72 | -19.3 |
Maximum of Months | 23.56 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.22 | -17.6 |
February | 15.90 | -15.4 |
March | 16.14 | -10.3 |
April | 18.20 | 0.73 |
May | 21.18 | 10.60 |
June | 23.06 | 15.96 |
July | 23.48 | 16.86 |
August | 22.70 | 14.24 |
September | 20.79 | 6.72 |
October | 17.38 | -3.1 |
November | 16.85 | -17.6 |
December | 15.29 | -19.3 |
Annual Sum or Average | 18.86 | -1.4 |
Minimum of Months | 15.22 | -19.3 |
Maximum of Months | 23.48 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.12 | -15.4 |
March | 21.20 | -10.3 |
April | 22.12 | 0.73 |
May | 23.55 | 10.60 |
June | 23.88 | 15.96 |
July | 23.88 | 16.86 |
August | 23.80 | 14.24 |
September | 22.98 | 6.72 |
October | 21.56 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 22.29 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.88 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.27 | -17.6 |
February | 14.73 | -15.4 |
March | 14.83 | -10.3 |
April | 16.72 | 0.73 |
May | 20.04 | 10.60 |
June | 22.21 | 15.96 |
July | 22.61 | 16.86 |
August | 21.65 | 14.24 |
September | 19.39 | 6.72 |
October | 16.14 | -3.1 |
November | 15.76 | -17.6 |
December | 14.42 | -19.3 |
Annual Sum or Average | 17.75 | -1.4 |
Minimum of Months | 14.27 | -19.3 |
Maximum of Months | 22.61 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.27 | 0.73 |
May | 21.36 | 10.60 |
June | 22.95 | 15.96 |
July | 22.98 | 16.86 |
August | 22.34 | 14.24 |
September | 19.95 | 6.72 |
October | 18.99 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.20 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.98 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.53 | -10.3 |
April | 20.90 | 0.73 |
May | 21.60 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.68 | 14.24 |
September | 21.20 | 6.72 |
October | 20.68 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.00 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.49 | -15.4 |
March | 20.54 | -10.3 |
April | 20.94 | 0.73 |
May | 21.62 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.68 | 14.24 |
September | 21.25 | 6.72 |
October | 20.71 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.01 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.49 | -15.4 |
March | 20.54 | -10.3 |
April | 20.96 | 0.73 |
May | 21.63 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.68 | 14.24 |
September | 21.29 | 6.72 |
October | 20.73 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.02 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.50 | -10.3 |
April | 20.77 | 0.73 |
May | 21.46 | 10.60 |
June | 21.72 | 15.96 |
July | 21.73 | 16.86 |
August | 21.62 | 14.24 |
September | 21.09 | 6.72 |
October | 20.61 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.95 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.73 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.54 | -15.4 |
March | 20.66 | -10.3 |
April | 21.21 | 0.73 |
May | 21.67 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.72 | 14.24 |
September | 21.48 | 6.72 |
October | 20.87 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.09 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | -17.6 |
February | 20.97 | -15.4 |
March | 21.86 | -10.3 |
April | 22.85 | 0.73 |
May | 23.32 | 10.60 |
June | 23.33 | 15.96 |
July | 23.33 | 16.86 |
August | 23.33 | 14.24 |
September | 23.24 | 6.72 |
October | 22.47 | -3.1 |
November | 20.46 | -17.6 |
December | 19.92 | -19.3 |
Annual Sum or Average | 22.12 | -1.4 |
Minimum of Months | 19.92 | -19.3 |
Maximum of Months | 23.33 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.69 | -17.6 |
February | 29.99 | -15.4 |
March | 30.23 | -10.3 |
April | 31.09 | 0.73 |
May | 32.34 | 10.60 |
June | 33.03 | 15.96 |
July | 33.19 | 16.86 |
August | 32.92 | 14.24 |
September | 32.02 | 6.72 |
October | 30.62 | -3.1 |
November | 30.08 | -17.6 |
December | 29.69 | -19.3 |
Annual Sum or Average | 31.25 | -1.4 |
Minimum of Months | 29.69 | -19.3 |
Maximum of Months | 33.19 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | -17.6 |
February | 21.68 | -15.4 |
March | 21.74 | -10.3 |
April | 21.95 | 0.73 |
May | 22.24 | 10.60 |
June | 22.51 | 15.96 |
July | 22.63 | 16.86 |
August | 22.50 | 14.24 |
September | 22.10 | 6.72 |
October | 21.79 | -3.1 |
November | 21.66 | -17.6 |
December | 21.62 | -19.3 |
Annual Sum or Average | 22.01 | -1.4 |
Minimum of Months | 21.62 | -19.3 |
Maximum of Months | 22.63 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.58 | -15.4 |
March | 20.79 | -10.3 |
April | 21.33 | 0.73 |
May | 21.70 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.73 | 14.24 |
September | 21.53 | 6.72 |
October | 20.96 | -3.1 |
November | 20.47 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.13 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.53 | -15.4 |
March | 20.65 | -10.3 |
April | 21.20 | 0.73 |
May | 21.67 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.72 | 14.24 |
September | 21.46 | 6.72 |
October | 20.84 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.08 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.94 | -17.6 |
February | 17.54 | -15.4 |
March | 18.02 | -10.3 |
April | 19.72 | 0.73 |
May | 22.17 | 10.60 |
June | 23.58 | 15.96 |
July | 23.91 | 16.86 |
August | 23.34 | 14.24 |
September | 21.65 | 6.72 |
October | 18.98 | -3.1 |
November | 17.88 | -17.6 |
December | 16.86 | -19.3 |
Annual Sum or Average | 20.06 | -1.4 |
Minimum of Months | 16.86 | -19.3 |
Maximum of Months | 23.91 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.48 | -17.6 |
February | 14.30 | -15.4 |
March | 14.73 | -10.3 |
April | 17.08 | 0.73 |
May | 21.01 | 10.60 |
June | 23.35 | 15.96 |
July | 23.97 | 16.86 |
August | 22.96 | 14.24 |
September | 20.44 | 6.72 |
October | 16.28 | -3.1 |
November | 15.33 | -17.6 |
December | 13.44 | -19.3 |
Annual Sum or Average | 18.05 | -1.4 |
Minimum of Months | 13.44 | -19.3 |
Maximum of Months | 23.97 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.37 | -17.6 |
February | 15.05 | -15.4 |
March | 15.30 | -10.3 |
April | 17.52 | 0.73 |
May | 20.88 | 10.60 |
June | 23.07 | 15.96 |
July | 23.53 | 16.86 |
August | 22.59 | 14.24 |
September | 20.27 | 6.72 |
October | 16.56 | -3.1 |
November | 16.04 | -17.6 |
December | 14.44 | -19.3 |
Annual Sum or Average | 18.32 | -1.4 |
Minimum of Months | 14.37 | -19.3 |
Maximum of Months | 23.53 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.40 | 0.73 |
May | 22.77 | 10.60 |
June | 23.71 | 15.96 |
July | 23.74 | 16.86 |
August | 23.38 | 14.24 |
September | 21.82 | 6.72 |
October | 21.14 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.97 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.91 | -17.6 |
February | 13.41 | -15.4 |
March | 13.57 | -10.3 |
April | 15.65 | 0.73 |
May | 19.49 | 10.60 |
June | 22.22 | 15.96 |
July | 22.67 | 16.86 |
August | 21.43 | 14.24 |
September | 18.47 | 6.72 |
October | 14.91 | -3.1 |
November | 14.47 | -17.6 |
December | 13.04 | -19.3 |
Annual Sum or Average | 16.87 | -1.4 |
Minimum of Months | 12.91 | -19.3 |
Maximum of Months | 22.67 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.04 | 0.73 |
May | 20.82 | 10.60 |
June | 22.76 | 15.96 |
July | 22.80 | 16.86 |
August | 21.98 | 14.24 |
September | 19.40 | 6.72 |
October | 18.89 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.02 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.80 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.08 | 0.73 |
May | 20.91 | 10.60 |
June | 22.81 | 15.96 |
July | 22.85 | 16.86 |
August | 22.03 | 14.24 |
September | 19.47 | 6.72 |
October | 18.91 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.05 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.85 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.14 | 0.73 |
May | 21.05 | 10.60 |
June | 22.83 | 15.96 |
July | 22.86 | 16.86 |
August | 22.06 | 14.24 |
September | 19.58 | 6.72 |
October | 18.92 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.08 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.86 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.52 | -10.3 |
April | 20.90 | 0.73 |
May | 21.59 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.65 | 14.24 |
September | 21.19 | 6.72 |
October | 20.66 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.99 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.09 | 0.73 |
May | 20.83 | 10.60 |
June | 22.68 | 15.96 |
July | 22.78 | 16.86 |
August | 21.98 | 14.24 |
September | 19.62 | 6.72 |
October | 18.91 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.04 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.78 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.56 | -10.3 |
April | 21.06 | 0.73 |
May | 21.61 | 10.60 |
June | 21.73 | 15.96 |
July | 21.74 | 16.86 |
August | 21.69 | 14.24 |
September | 21.33 | 6.72 |
October | 20.73 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.03 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -17.6 |
February | 20.58 | -15.4 |
March | 20.80 | -10.3 |
April | 21.37 | 0.73 |
May | 21.72 | 10.60 |
June | 21.75 | 15.96 |
July | 21.75 | 16.86 |
August | 21.74 | 14.24 |
September | 21.56 | 6.72 |
October | 20.98 | -3.1 |
November | 20.47 | -17.6 |
December | 20.48 | -19.3 |
Annual Sum or Average | 21.14 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | -17.6 |
February | 21.45 | -15.4 |
March | 21.79 | -10.3 |
April | 23.01 | 0.73 |
May | 24.72 | 10.60 |
June | 25.70 | 15.96 |
July | 25.83 | 16.86 |
August | 25.42 | 14.24 |
September | 24.03 | 6.72 |
October | 22.26 | -3.1 |
November | 21.51 | -17.6 |
December | 21.07 | -19.3 |
Annual Sum or Average | 23.17 | -1.4 |
Minimum of Months | 21.07 | -19.3 |
Maximum of Months | 25.83 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -17.6 |
February | 19.07 | -15.4 |
March | 19.52 | -10.3 |
April | 21.39 | 0.73 |
May | 22.94 | 10.60 |
June | 23.31 | 15.96 |
July | 23.32 | 16.86 |
August | 23.22 | 14.24 |
September | 22.28 | 6.72 |
October | 20.21 | -3.1 |
November | 18.89 | -17.6 |
December | 18.91 | -19.3 |
Annual Sum or Average | 21.01 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 23.32 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.53 | -15.4 |
March | 20.67 | -10.3 |
April | 21.24 | 0.73 |
May | 21.68 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.71 | 14.24 |
September | 21.43 | 6.72 |
October | 20.84 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.09 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.93 | -10.3 |
April | 19.94 | 0.73 |
May | 21.86 | 10.60 |
June | 22.91 | 15.96 |
July | 22.98 | 16.86 |
August | 22.60 | 14.24 |
September | 20.76 | 6.72 |
October | 19.18 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.40 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.98 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.65 | -17.6 |
February | 16.27 | -15.4 |
March | 16.79 | -10.3 |
April | 18.79 | 0.73 |
May | 21.81 | 10.60 |
June | 23.62 | 15.96 |
July | 24.00 | 16.86 |
August | 23.22 | 14.24 |
September | 20.93 | 6.72 |
October | 17.82 | -3.1 |
November | 16.60 | -17.6 |
December | 15.50 | -19.3 |
Annual Sum or Average | 19.27 | -1.4 |
Minimum of Months | 15.50 | -19.3 |
Maximum of Months | 24.00 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.27 | -17.6 |
February | 13.13 | -15.4 |
March | 13.56 | -10.3 |
April | 16.22 | 0.73 |
May | 20.70 | 10.60 |
June | 23.41 | 15.96 |
July | 24.08 | 16.86 |
August | 22.88 | 14.24 |
September | 19.86 | 6.72 |
October | 15.23 | -3.1 |
November | 14.12 | -17.6 |
December | 12.11 | -19.3 |
Annual Sum or Average | 17.32 | -1.4 |
Minimum of Months | 12.11 | -19.3 |
Maximum of Months | 24.08 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.14 | -17.6 |
February | 12.94 | -15.4 |
March | 13.55 | -10.3 |
April | 16.38 | 0.73 |
May | 20.35 | 10.60 |
June | 23.03 | 15.96 |
July | 23.50 | 16.86 |
August | 22.25 | 14.24 |
September | 19.13 | 6.72 |
October | 14.89 | -3.1 |
November | 13.64 | -17.6 |
December | 12.09 | -19.3 |
Annual Sum or Average | 17.01 | -1.4 |
Minimum of Months | 12.09 | -19.3 |
Maximum of Months | 23.50 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -17.6 |
February | 21.11 | -15.4 |
March | 21.11 | -10.3 |
April | 21.39 | 0.73 |
May | 22.37 | 10.60 |
June | 23.31 | 15.96 |
July | 23.35 | 16.86 |
August | 22.88 | 14.24 |
September | 21.49 | 6.72 |
October | 21.12 | -3.1 |
November | 21.11 | -17.6 |
December | 21.11 | -19.3 |
Annual Sum or Average | 21.79 | -1.4 |
Minimum of Months | 21.11 | -19.3 |
Maximum of Months | 23.35 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.98 | -17.6 |
February | 11.65 | -15.4 |
March | 12.20 | -10.3 |
April | 14.83 | 0.73 |
May | 19.09 | 10.60 |
June | 22.19 | 15.96 |
July | 22.62 | 16.86 |
August | 21.11 | 14.24 |
September | 17.59 | 6.72 |
October | 13.65 | -3.1 |
November | 12.44 | -17.6 |
December | 11.05 | -19.3 |
Annual Sum or Average | 15.81 | -1.4 |
Minimum of Months | 10.98 | -19.3 |
Maximum of Months | 22.62 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -17.6 |
February | 20.47 | -15.4 |
March | 20.47 | -10.3 |
April | 20.72 | 0.73 |
May | 21.49 | 10.60 |
June | 21.72 | 15.96 |
July | 21.72 | 16.86 |
August | 21.57 | 14.24 |
September | 20.87 | 6.72 |
October | 20.51 | -3.1 |
November | 20.46 | -17.6 |
December | 20.46 | -19.3 |
Annual Sum or Average | 20.91 | -1.4 |
Minimum of Months | 20.46 | -19.3 |
Maximum of Months | 21.72 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.11 | 0.73 |
May | 20.61 | 10.60 |
June | 22.49 | 15.96 |
July | 22.50 | 16.86 |
August | 21.59 | 14.24 |
September | 19.24 | 6.72 |
October | 18.89 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 19.92 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.50 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.14 | 0.73 |
May | 20.69 | 10.60 |
June | 22.52 | 15.96 |
July | 22.51 | 16.86 |
August | 21.61 | 14.24 |
September | 19.29 | 6.72 |
October | 18.89 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 19.93 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.52 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.49 | -10.3 |
April | 20.90 | 0.73 |
May | 21.63 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.65 | 14.24 |
September | 21.11 | 6.72 |
October | 20.59 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 20.98 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.89 | -10.3 |
April | 19.11 | 0.73 |
May | 20.60 | 10.60 |
June | 22.44 | 15.96 |
July | 22.52 | 16.86 |
August | 21.64 | 14.24 |
September | 19.33 | 6.72 |
October | 18.89 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 19.92 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.52 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -17.6 |
February | 18.89 | -15.4 |
March | 18.93 | -10.3 |
April | 19.74 | 0.73 |
May | 21.25 | 10.60 |
June | 22.54 | 15.96 |
July | 22.62 | 16.86 |
August | 22.08 | 14.24 |
September | 20.06 | 6.72 |
October | 18.99 | -3.1 |
November | 18.89 | -17.6 |
December | 18.89 | -19.3 |
Annual Sum or Average | 20.16 | -1.4 |
Minimum of Months | 18.89 | -19.3 |
Maximum of Months | 22.62 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.64 | -10.3 |
April | 21.24 | 0.73 |
May | 21.69 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.71 | 14.24 |
September | 21.40 | 6.72 |
October | 20.76 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.07 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.03 | -17.6 |
February | 18.48 | -15.4 |
March | 19.14 | -10.3 |
April | 20.75 | 0.73 |
May | 22.71 | 10.60 |
June | 23.94 | 15.96 |
July | 24.07 | 16.86 |
August | 23.44 | 14.24 |
September | 21.63 | 6.72 |
October | 19.63 | -3.1 |
November | 18.37 | -17.6 |
December | 17.95 | -19.3 |
Annual Sum or Average | 20.69 | -1.4 |
Minimum of Months | 17.95 | -19.3 |
Maximum of Months | 24.07 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.62 | -10.3 |
April | 21.20 | 0.73 |
May | 21.68 | 10.60 |
June | 21.74 | 15.96 |
July | 21.75 | 16.86 |
August | 21.71 | 14.24 |
September | 21.39 | 6.72 |
October | 20.75 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.06 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.75 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.48 | -15.4 |
March | 20.63 | -10.3 |
April | 21.22 | 0.73 |
May | 21.68 | 10.60 |
June | 21.74 | 15.96 |
July | 21.74 | 16.86 |
August | 21.71 | 14.24 |
September | 21.37 | 6.72 |
October | 20.74 | -3.1 |
November | 20.47 | -17.6 |
December | 20.47 | -19.3 |
Annual Sum or Average | 21.06 | -1.4 |
Minimum of Months | 20.47 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -17.6 |
February | 20.47 | -15.4 |
March | 20.53 | -10.3 |
April | 21.04 | 0.73 |
May | 21.63 | 10.60 |
June | 21.73 | 15.96 |
July | 21.74 | 16.86 |
August | 21.68 | 14.24 |
September | 21.24 | 6.72 |
October | 20.63 | -3.1 |
November | 20.47 | -17.6 |
December | 20.46 | -19.3 |
Annual Sum or Average | 21.01 | -1.4 |
Minimum of Months | 20.46 | -19.3 |
Maximum of Months | 21.74 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.11 | -17.6 |
February | 14.87 | -15.4 |
March | 15.74 | -10.3 |
April | 18.26 | 0.73 |
May | 21.55 | 10.60 |
June | 23.52 | 15.96 |
July | 23.87 | 16.86 |
August | 22.89 | 14.24 |
September | 20.29 | 6.72 |
October | 16.83 | -3.1 |
November | 14.91 | -17.6 |
December | 13.85 | -19.3 |
Annual Sum or Average | 18.41 | -1.4 |
Minimum of Months | 13.85 | -19.3 |
Maximum of Months | 23.87 | 16.86 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:40
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.43 | -17.6 |
February | 11.43 | -15.4 |
March | 12.13 | -10.3 |
April | 15.44 | 0.73 |
May | 20.34 | 10.60 |
June | 23.34 | 15.96 |
July | 23.98 | 16.86 |
August | 22.53 | 14.24 |
September | 19.02 | 6.72 |
October | 13.91 | -3.1 |
November | 11.90 | -17.6 |
December | 9.95 | -19.3 |
Annual Sum or Average | 16.23 | -1.4 |
Minimum of Months | 9.95 | -19.3 |
Maximum of Months | 23.98 | 16.86 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:40
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.271889E+12 | 211851.437 | 12-JAN-07:15 | 15177.258 | 39465.561 | 8722.653 | 144289.851 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.224791E+12 | 203187.808 | 27-FEB-07:15 | 15177.258 | 39465.561 | 8719.567 | 135615.905 | 13.404 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.209716E+12 | 184572.485 | 01-MAR-07:15 | 15177.258 | 39465.561 | 8708.333 | 116979.939 | 45.281 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.148366E+12 | 154402.078 | 03-APR-06:15 | 15177.258 | 39465.561 | 8695.662 | 90945.943 | 109.540 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.128970E+12 | 79542.964 | 13-MAY-07:00 | 17641.054 | 43276.576 | 9054.925 | 0.000 | 9562.297 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.132507E+12 | 85850.452 | 30-JUN-07:00 | 17492.219 | 43276.576 | 9054.925 | 0.000 | 16018.619 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.140950E+12 | 87378.237 | 22-JUL-07:00 | 17641.054 | 43276.576 | 9054.925 | 0.000 | 17397.570 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.136466E+12 | 86951.570 | 31-AUG-06:15 | 15102.841 | 39465.561 | 8680.457 | 22481.778 | 1212.820 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.129699E+12 | 101094.022 | 30-SEP-06:15 | 13316.689 | 34010.661 | 8680.457 | 40669.098 | 221.004 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.177401E+12 | 155635.581 | 22-OCT-06:15 | 15177.258 | 39465.561 | 8690.829 | 87995.839 | 109.980 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.253887E+12 | 184302.805 | 29-NOV-07:00 | 15177.258 | 39465.561 | 8706.400 | 116719.675 | 37.798 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.282822E+12 | 194216.727 | 15-DEC-07:15 | 13316.689 | 34010.661 | 8710.945 | 133982.320 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.223746E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.128970E+12 | 79542.964 | 13316.689 | 34010.661 | 8680.457 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.282822E+12 | 211851.437 | 17641.054 | 43276.576 | 9054.925 | 144289.851 | 17397.570 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:40
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.164757E+12 | 142837.334 | 12-JAN-09:15 | 37992.745 | 40096.028 | 0.000 | 64748.561 | 64748.561 | 64748.561 | 37992.745 |
February | 0.143242E+12 | 140128.462 | 24-FEB-09:15 | 28138.813 | 40096.028 | 0.000 | 71893.622 | 71893.622 | 71893.622 | 28138.813 |
March | 0.146685E+12 | 131909.074 | 31-MAR-08:15 | 20362.946 | 40096.028 | 0.000 | 71450.100 | 71450.100 | 71450.100 | 20362.946 |
April | 0.119795E+12 | 123136.120 | 03-APR-08:15 | 17899.502 | 40096.028 | 0.000 | 65140.590 | 65140.590 | 65140.590 | 17899.502 |
May | 0.108283E+12 | 111715.866 | 12-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 71619.838 | 71619.838 | 71619.838 | 0.000 |
June | 0.995325E+11 | 105277.022 | 02-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 65180.994 | 65180.994 | 65180.994 | 0.000 |
July | 0.100308E+12 | 104109.952 | 07-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 64013.924 | 64013.924 | 64013.924 | 0.000 |
August | 0.995061E+11 | 103033.633 | 31-AUG-09:00 | 3120.495 | 40096.028 | 0.000 | 59817.111 | 59817.111 | 59817.111 | 3120.495 |
September | 0.101800E+12 | 110307.935 | 29-SEP-10:15 | 9950.225 | 40096.028 | 0.000 | 60261.682 | 60261.682 | 60261.682 | 9950.225 |
October | 0.125332E+12 | 123532.868 | 27-OCT-10:30 | 22380.861 | 40096.028 | 0.000 | 61055.979 | 61055.979 | 61055.979 | 22380.861 |
November | 0.153595E+12 | 134980.947 | 28-NOV-10:45 | 32377.250 | 40096.028 | 0.000 | 62507.669 | 62507.669 | 62507.669 | 32377.250 |
December | 0.167320E+12 | 145042.802 | 15-DEC-09:15 | 34747.943 | 40096.028 | 0.000 | 70198.831 | 70198.831 | 70198.831 | 34747.943 |
Annual Sum or Average | 0.153016E+13 | 0.000 | ||||||||
Minimum of Months | 0.995061E+11 | 103033.633 | 0.000 | 40096.028 | 0.000 | 59817.111 | 59817.111 | 59817.111 | 0.000 | |
Maximum of Months | 0.167320E+12 | 145042.802 | 37992.745 | 40096.028 | 0.000 | 71893.622 | 71893.622 | 71893.622 | 37992.745 |