Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Simulation Timestamp: 2018-10-19 10:15:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2811.55 | 700.51 | 754.76 |
Net Site Energy | 2811.55 | 700.51 | 754.76 |
Total Source Energy | 6797.12 | 1693.53 | 1824.68 |
Net Source Energy | 6797.12 | 1693.53 | 1824.68 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 68.52 | 31.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 378.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 415.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 559.00 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1800.00 | 1011.55 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 68.52 | 31.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 378.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 415.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 280.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 559.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 195.34 | 158.40 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.21 | 271.55 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 181.30 | 147.02 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 448.48 | 252.03 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1800.00 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1800.00 | 100.00 |
Total On-Site and Utility Electric Sources | 1800.00 | 100.00 |
Total Electricity End Uses | 1800.00 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 252.00 |
Time Setpoint Not Met During Occupied Cooling | 4233.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6023.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Weather File | Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 |
Latitude [deg] | 33.63 |
Longitude [deg] | -84.4 |
Elevation [m] | 308.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00 | -6.30 | Wetbulb [C] | 5.30 | 320.00 |
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 9.50 | 23.50 | Wetbulb [C] | 4.00 | 300.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 96.82 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 87.38 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7228.15 | 5077.70 | 2150.45 | 0.70 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19549.17 | 13216.87 | 6332.31 | 0.68 | 3.80 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9149.35 | 6185.72 | 2963.63 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15180.40 | 10896.02 | 4284.38 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6977.6 | 3.33 | 11.35 | 12.03 | 11.43 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18937.3 | 3.29 | 11.23 | 11.91 | 11.42 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8863.0 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14624.8 | 3.30 | 11.25 | 11.93 | 11.28 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.87 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 20284.83 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 898.07 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 898.07 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1018.46 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1006.52 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 898.00 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.80 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.87 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2546.97 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 898.07 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3592.27 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2847.00 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3592.27 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1021.66 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 982.47 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3592.02 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 898.00 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3592.02 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 898.00 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.80 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.87 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2546.97 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 935.40 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3592.27 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2847.00 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3592.27 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1096.87 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1049.70 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3592.02 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 898.00 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3592.02 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 969.64 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.80 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.87 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 3255.18 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1160.57 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3654.60 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 3000.07 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3670.20 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1357.47 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1309.26 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3638.90 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1001.67 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3596.27 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1234.09 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 309.80 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3697.84 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 15499.43 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 8299.83 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6302.24 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.32 | 361.17 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.79 | 871.61 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.37 | 412.70 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 791.94 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7671.26 | 9205.52 | 0.656 | 0.787 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
RESTROOMFLR1 | 452.06 | 542.47 | 0.039 | 0.046 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 33.26 | 0.01445 |
MEETINGROOMFLR1 | 3588.00 | 4305.60 | 0.307 | 0.368 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM101 | 587.24 | 704.69 | 0.070 | 0.084 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.83 | 0.01445 |
GUESTROOM102 | 483.36 | 580.03 | 0.057 | 0.069 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.83 | 0.01445 |
GUESTROOM103 | 1092.20 | 1310.63 | 0.130 | 0.156 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
GUESTROOM104 | 1196.95 | 1436.34 | 0.142 | 0.171 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.12 | 0.01445 |
GUESTROOM105 | 1520.78 | 1824.94 | 0.181 | 0.217 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
EMPLOYEELOUNGEFLR1 | 5343.32 | 6411.98 | 0.457 | 0.548 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
EXERCISECENTERFLR1 | 1175.01 | 1410.02 | 0.100 | 0.121 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 33.07 | 0.01445 |
FRONTOFFICEFLR1 | 3144.60 | 3773.52 | 0.269 | 0.322 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM201 | 830.23 | 996.28 | 0.099 | 0.118 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 34.16 | 0.01445 |
GUESTROOM202_205 | 4120.16 | 4944.20 | 0.490 | 0.587 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.83 | 0.01445 |
GUESTROOM206_208 | 3337.62 | 4005.15 | 0.397 | 0.476 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.83 | 0.01445 |
GUESTROOM209_212 | 3935.59 | 4722.71 | 0.468 | 0.561 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 33.83 | 0.01445 |
GUESTROOM213 | 1135.93 | 1363.11 | 0.135 | 0.162 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 31.41 | 0.01445 |
GUESTROOM214 | 1294.96 | 1553.95 | 0.154 | 0.185 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
GUESTROOM215_218 | 9388.77 | 11266.53 | 1.115 | 1.338 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM219 | 5374.00 | 6448.80 | 0.638 | 0.766 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
GUESTROOM220_223 | 4420.97 | 5305.16 | 0.525 | 0.630 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM224 | 1279.35 | 1535.22 | 0.152 | 0.182 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM301 | 648.75 | 778.50 | 0.077 | 0.093 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01445 |
GUESTROOM302_305 | 1543.35 | 1852.03 | 0.183 | 0.220 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 33.64 | 0.01445 |
GUESTROOM306_308 | 1349.28 | 1619.14 | 0.160 | 0.192 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 33.64 | 0.01445 |
GUESTROOM309_312 | 3877.15 | 4652.58 | 0.461 | 0.553 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 33.64 | 0.01445 |
GUESTROOM313 | 632.97 | 759.56 | 0.075 | 0.090 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 31.05 | 0.01445 |
GUESTROOM314 | 1211.01 | 1453.22 | 0.144 | 0.173 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 34.12 | 0.01445 |
GUESTROOM315_318 | 4802.60 | 5763.12 | 0.571 | 0.685 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM319 | 1063.22 | 1275.87 | 0.126 | 0.152 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
GUESTROOM320_323 | 4197.29 | 5036.75 | 0.499 | 0.598 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM324 | 709.59 | 851.51 | 0.084 | 0.101 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
GUESTROOM401 | 1441.92 | 1730.31 | 0.171 | 0.206 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 34.40 | 0.01445 |
GUESTROOM402_405 | 2145.65 | 2574.77 | 0.255 | 0.306 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM406_408 | 1840.00 | 2208.00 | 0.219 | 0.262 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM409_412 | 4779.58 | 5735.49 | 0.568 | 0.681 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
GUESTROOM413 | 840.33 | 1008.40 | 0.100 | 0.120 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 33.97 | 0.01445 |
GUESTROOM414 | 943.42 | 1132.11 | 0.112 | 0.134 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 34.26 | 0.01445 |
GUESTROOM415_418 | 5238.67 | 6286.41 | 0.622 | 0.747 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 34.40 | 0.01445 |
GUESTROOM419 | 1447.64 | 1737.17 | 0.172 | 0.206 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 34.40 | 0.01445 |
GUESTROOM420_423 | 5207.59 | 6249.11 | 0.619 | 0.742 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 34.40 | 0.01445 |
GUESTROOM424 | 1489.02 | 1786.83 | 0.177 | 0.212 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 34.40 | 0.01445 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
CORRIDORFLR1 | 16067.85 | 19281.42 | 1.373 | 1.648 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 32.12 | 0.01445 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
CORRIDORFLR2 | 2646.98 | 3176.38 | 0.226 | 0.271 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.83 | 0.01445 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
CORRIDORFLR3 | 1240.54 | 1488.64 | 0.106 | 0.127 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 32.83 | 0.01445 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 | |
CORRIDORFLR4 | 1925.14 | 2310.16 | 0.164 | 0.197 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 33.97 | 0.01445 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB | 34.40 | 0.01445 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1492.51 | 1791.01 | 0.044 | 0.236 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | -6.30 | 0.00230 |
RESTROOMFLR1 | 87.03 | 104.43 | 0.003 | 0.003 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -6.30 | 0.00230 |
MEETINGROOMFLR1 | 511.34 | 613.61 | 0.015 | 0.126 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -6.30 | 0.00230 |
GUESTROOM101 | 215.55 | 258.66 | 0.006 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -6.30 | 0.00230 |
GUESTROOM102 | 262.25 | 314.70 | 0.008 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -6.30 | 0.00230 |
GUESTROOM103 | 484.35 | 581.22 | 0.014 | 0.017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -6.30 | 0.00230 |
GUESTROOM104 | 474.42 | 569.30 | 0.014 | 0.017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -6.30 | 0.00230 |
GUESTROOM105 | 260.20 | 312.24 | 0.008 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -6.30 | 0.00230 |
EMPLOYEELOUNGEFLR1 | 230.83 | 276.99 | 0.007 | 0.051 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -6.30 | 0.00230 |
EXERCISECENTERFLR1 | 146.60 | 175.91 | 0.004 | 0.043 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -6.30 | 0.00230 |
FRONTOFFICEFLR1 | 952.37 | 1142.85 | 0.028 | 0.056 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -6.30 | 0.00230 |
GUESTROOM201 | 383.60 | 460.32 | 0.011 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -6.30 | 0.00230 |
GUESTROOM202_205 | 831.24 | 997.49 | 0.024 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -6.30 | 0.00230 |
GUESTROOM206_208 | 647.08 | 776.49 | 0.019 | 0.043 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -6.30 | 0.00230 |
GUESTROOM209_212 | 756.12 | 907.35 | 0.022 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -6.30 | 0.00230 |
GUESTROOM213 | 487.01 | 584.41 | 0.014 | 0.017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -6.30 | 0.00230 |
GUESTROOM214 | 454.38 | 545.26 | 0.013 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -6.30 | 0.00230 |
GUESTROOM215_218 | 732.13 | 878.55 | 0.021 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -6.30 | 0.00230 |
GUESTROOM219 | 171.76 | 206.11 | 0.005 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -6.30 | 0.00230 |
GUESTROOM220_223 | 709.86 | 851.83 | 0.021 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -6.30 | 0.00230 |
GUESTROOM224 | 377.43 | 452.91 | 0.011 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -6.30 | 0.00230 |
GUESTROOM301 | 415.13 | 498.15 | 0.012 | 0.015 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -6.30 | 0.00230 |
GUESTROOM302_305 | 926.74 | 1112.09 | 0.027 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -6.30 | 0.00230 |
GUESTROOM306_308 | 792.73 | 951.27 | 0.023 | 0.043 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -6.30 | 0.00230 |
GUESTROOM309_312 | 927.41 | 1112.89 | 0.027 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -6.30 | 0.00230 |
GUESTROOM313 | 549.68 | 659.62 | 0.016 | 0.019 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -6.30 | 0.00230 |
GUESTROOM314 | 510.41 | 612.49 | 0.015 | 0.018 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | -6.30 | 0.00230 |
GUESTROOM315_318 | 900.58 | 1080.70 | 0.026 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30 | 0.00230 |
GUESTROOM319 | 252.91 | 303.49 | 0.007 | 0.013 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -6.30 | 0.00230 |
GUESTROOM320_323 | 866.85 | 1040.22 | 0.025 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -6.30 | 0.00230 |
GUESTROOM324 | 443.69 | 532.43 | 0.013 | 0.016 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -6.30 | 0.00230 |
GUESTROOM401 | 602.77 | 723.32 | 0.018 | 0.021 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | -6.30 | 0.00230 |
GUESTROOM402_405 | 1588.01 | 1905.61 | 0.046 | 0.056 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 21:30:00 | -6.30 | 0.00230 |
GUESTROOM406_408 | 1344.95 | 1613.94 | 0.039 | 0.047 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -6.30 | 0.00230 |
GUESTROOM409_412 | 1601.02 | 1921.22 | 0.047 | 0.056 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -6.30 | 0.00230 |
GUESTROOM413 | 766.86 | 920.23 | 0.022 | 0.027 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -6.30 | 0.00230 |
GUESTROOM414 | 726.70 | 872.04 | 0.021 | 0.025 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | -6.30 | 0.00230 |
GUESTROOM415_418 | 1575.03 | 1890.04 | 0.046 | 0.055 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -6.30 | 0.00230 |
GUESTROOM419 | 470.38 | 564.45 | 0.014 | 0.017 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -6.30 | 0.00230 |
GUESTROOM420_423 | 1539.51 | 1847.41 | 0.045 | 0.054 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -6.30 | 0.00230 |
GUESTROOM424 | 664.06 | 796.87 | 0.019 | 0.023 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -6.30 | 0.00230 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
CORRIDORFLR1 | 15657.75 | 18789.30 | 0.457 | 0.549 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -6.30 | 0.00230 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
CORRIDORFLR2 | 588.10 | 705.72 | 0.017 | 0.038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -6.30 | 0.00230 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
CORRIDORFLR3 | 809.07 | 970.88 | 0.024 | 0.038 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -6.30 | 0.00230 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 | |
CORRIDORFLR4 | 1679.31 | 2015.18 | 0.049 | 0.059 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -6.30 | 0.00230 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB | -6.30 | 0.00230 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.32 | 0.32 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.79 | 0.79 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.37 | 0.37 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.72 | 0.72 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialEnthalpy | 0.24 | 0.79 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3695.25 | 6717.75 | 2384.00 |
RESTROOMFLR1 | 1111.75 | 6355.50 | 418.50 |
MEETINGROOMFLR1 | 1915.25 | 3081.50 | 933.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 1173.75 | 8692.25 | 1173.75 |
GUESTROOM104 | 465.25 | 8499.00 | 465.25 |
GUESTROOM105 | 86.50 | 8071.25 | 56.25 |
EMPLOYEELOUNGEFLR1 | 3074.50 | 2197.25 | 365.50 |
EXERCISECENTERFLR1 | 2359.00 | 1961.25 | 96.00 |
FRONTOFFICEFLR1 | 2439.25 | 5017.75 | 678.25 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 531.25 | 8133.25 | 489.00 |
GUESTROOM206_208 | 422.25 | 8105.75 | 367.00 |
GUESTROOM209_212 | 396.25 | 8298.00 | 390.25 |
GUESTROOM213 | 1086.75 | 8458.50 | 1086.75 |
GUESTROOM214 | 225.75 | 8189.25 | 209.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 4877.50 | 3758.75 | 828.25 |
GUESTROOM220_223 | 238.25 | 8067.00 | 155.00 |
GUESTROOM224 | 196.75 | 8109.50 | 179.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 735.00 | 8482.50 | 735.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 514.00 | 8221.50 | 499.00 |
GUESTROOM315_318 | 319.75 | 7875.50 | 102.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 323.75 | 8290.50 | 299.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2346.25 | 7854.75 | 1844.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1545.00 | 7810.00 | 1016.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1118.75 | 7466.00 | 403.25 |
GUESTROOM419 | 892.00 | 7609.50 | 373.75 |
GUESTROOM420_423 | 1137.75 | 7529.75 | 462.00 |
GUESTROOM424 | 1366.00 | 7744.25 | 874.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7334.50 | 8759.50 | 6023.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 67.00 | 1021.75 | 67.00 | 1021.75 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 4.00 | 51.00 | 4.00 | 51.00 |
GUESTROOM104 | 1.25 | 56.75 | 1.25 | 56.75 |
GUESTROOM105 | 0.00 | 69.75 | 0.00 | 69.75 |
EMPLOYEELOUNGEFLR1 | 289.00 | 1172.75 | 223.00 | 589.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1.50 | 42.00 | 1.50 | 42.00 |
GUESTROOM206_208 | 1.00 | 46.75 | 1.00 | 46.75 |
GUESTROOM209_212 | 1.00 | 41.00 | 1.00 | 41.00 |
GUESTROOM213 | 5.00 | 41.00 | 5.00 | 41.00 |
GUESTROOM214 | 0.50 | 46.50 | 0.50 | 46.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 3498.75 | 0.00 | 3498.75 |
GUESTROOM220_223 | 0.00 | 44.50 | 0.00 | 44.50 |
GUESTROOM224 | 0.50 | 46.25 | 0.50 | 46.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 2.75 | 40.50 | 2.75 | 40.50 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 1.50 | 44.50 | 1.50 | 44.50 |
GUESTROOM315_318 | 0.00 | 45.75 | 0.00 | 45.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.25 | 43.25 | 0.25 | 43.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 15.00 | 47.75 | 15.00 | 47.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 4.50 | 45.50 | 4.50 | 45.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1.25 | 50.50 | 1.25 | 50.50 |
GUESTROOM419 | 1.25 | 53.75 | 1.25 | 53.75 |
GUESTROOM420_423 | 1.50 | 48.50 | 1.50 | 48.50 |
GUESTROOM424 | 2.00 | 51.00 | 2.00 | 51.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 2.25 | 4725.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 523.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 3.50 | 388.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 314.25 | 5866.00 | 252.00 | 4233.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:35
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.322439 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.787245 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.715293 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 309.87 |
CORRIDORFLR1 PTAC HEATING COIL | 20284.83 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 898.07 |
102 PTAC HEATING COIL | 898.07 |
103 PTAC HEATING COIL | 1018.46 |
104 PTAC HEATING COIL | 1006.52 |
105 PTAC HEATING COIL | 898.00 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 309.80 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 309.87 |
CORRIDORFLR2 PTAC HEATING COIL | 2546.97 |
201 PTAC HEATING COIL | 898.07 |
202_205 PTAC HEATING COIL | 3592.27 |
206_208 PTAC HEATING COIL | 2847.00 |
209_212 PTAC HEATING COIL | 3592.27 |
213 PTAC HEATING COIL | 1021.66 |
214 PTAC HEATING COIL | 982.47 |
215_218 PTAC HEATING COIL | 3592.02 |
219 PTAC HEATING COIL | 898.00 |
220_223 PTAC HEATING COIL | 3592.02 |
224 PTAC HEATING COIL | 898.00 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 309.80 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 309.87 |
CORRIDORFLR3 PTAC HEATING COIL | 2546.97 |
301 PTAC HEATING COIL | 935.40 |
302_305 PTAC HEATING COIL | 3592.27 |
306_308 PTAC HEATING COIL | 2847.00 |
309_312 PTAC HEATING COIL | 3592.27 |
313 PTAC HEATING COIL | 1096.87 |
314 PTAC HEATING COIL | 1049.70 |
315_318 PTAC HEATING COIL | 3592.02 |
319 PTAC HEATING COIL | 898.00 |
320_323 PTAC HEATING COIL | 3592.02 |
324 PTAC HEATING COIL | 969.64 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 309.80 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 309.87 |
CORRIDORFLR4 PTAC HEATING COIL | 3255.18 |
401 PTAC HEATING COIL | 1160.57 |
402_405 PTAC HEATING COIL | 3654.60 |
406_408 PTAC HEATING COIL | 3000.07 |
409_412 PTAC HEATING COIL | 3670.20 |
413 PTAC HEATING COIL | 1357.47 |
414 PTAC HEATING COIL | 1309.26 |
415_418 PTAC HEATING COIL | 3638.90 |
419 PTAC HEATING COIL | 1001.67 |
420_423 PTAC HEATING COIL | 3596.27 |
424 PTAC HEATING COIL | 1234.09 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 309.80 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.702489 | 0.322439 | 7228.15 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 0.787245 | 19549.17 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.368444 | 9149.35 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.717769 | 0.715293 | 15180.40 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.787245 |
RESTROOMFLR1 DIRECT AIR | 0.046345 |
MEETINGROOMFLR1 DIRECT AIR | 0.368444 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.548419 |
EXERCISECENTERFLR1 DIRECT AIR | 0.120529 |
FRONTOFFICEFLR1 DIRECT AIR | 0.322439 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.322439 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.787245 |
SAC_MEETINGROOM MAIN BRANCH | 0.368444 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.715293 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.322439 |
SAC_FRONTLOUNGE | 0.787245 |
SAC_MEETINGROOM | 0.368444 |
SAC_EXC_EMPLGE_RESTRM | 0.715293 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.322439 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.787245 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.368444 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.715293 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.322439 | 0.322439 | 0.322439 | 0.322439 | 3697.84 | 7228.15 | 1.00 |
SAC_FRONTLOUNGE | 0.787245 | 0.787245 | 0.787245 | 0.787245 | 15499.43 | 19549.17 | 1.00 |
SAC_MEETINGROOM | 0.368444 | 0.368444 | 0.368444 | 0.368444 | 8299.83 | 9149.35 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.715293 | 0.715293 | 0.715293 | 0.715293 | 6302.24 | 15180.40 | 0.168503 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3697.84 |
SAC_FRONTLOUNGE HEATING COIL | 15499.43 |
SAC_MEETINGROOM HEATING COIL | 8299.83 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6302.24 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.368444 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.09 | 3.96 |
February | 19.06 | 7.94 |
March | 21.25 | 13.76 |
April | 22.51 | 17.21 |
May | 23.57 | 20.84 |
June | 24.69 | 24.80 |
July | 25.02 | 26.06 |
August | 25.25 | 26.55 |
September | 24.07 | 22.53 |
October | 22.15 | 16.03 |
November | 20.82 | 11.94 |
December | 19.15 | 7.70 |
Annual Sum or Average | 22.15 | 16.65 |
Minimum of Months | 18.09 | 3.96 |
Maximum of Months | 25.25 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | 3.96 |
February | 23.36 | 7.94 |
March | 24.18 | 13.76 |
April | 24.84 | 17.21 |
May | 25.57 | 20.84 |
June | 26.43 | 24.80 |
July | 26.82 | 26.06 |
August | 26.99 | 26.55 |
September | 25.98 | 22.53 |
October | 24.70 | 16.03 |
November | 23.99 | 11.94 |
December | 23.36 | 7.70 |
Annual Sum or Average | 24.93 | 16.65 |
Minimum of Months | 22.88 | 3.96 |
Maximum of Months | 26.99 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.42 | 3.96 |
February | 18.41 | 7.94 |
March | 20.61 | 13.76 |
April | 21.95 | 17.21 |
May | 23.08 | 20.84 |
June | 24.21 | 24.80 |
July | 24.51 | 26.06 |
August | 24.65 | 26.55 |
September | 23.44 | 22.53 |
October | 21.46 | 16.03 |
November | 20.07 | 11.94 |
December | 18.44 | 7.70 |
Annual Sum or Average | 21.54 | 16.65 |
Minimum of Months | 17.42 | 3.96 |
Maximum of Months | 24.65 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.27 | 3.96 |
February | 21.66 | 7.94 |
March | 22.26 | 13.76 |
April | 22.90 | 17.21 |
May | 23.44 | 20.84 |
June | 23.77 | 24.80 |
July | 23.86 | 26.06 |
August | 23.89 | 26.55 |
September | 23.65 | 22.53 |
October | 22.67 | 16.03 |
November | 22.05 | 11.94 |
December | 21.39 | 7.70 |
Annual Sum or Average | 22.74 | 16.65 |
Minimum of Months | 21.27 | 3.96 |
Maximum of Months | 23.89 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 3.96 |
February | 22.14 | 7.94 |
March | 22.75 | 13.76 |
April | 23.14 | 17.21 |
May | 23.49 | 20.84 |
June | 23.73 | 24.80 |
July | 23.81 | 26.06 |
August | 23.80 | 26.55 |
September | 23.56 | 22.53 |
October | 23.02 | 16.03 |
November | 22.57 | 11.94 |
December | 22.10 | 7.70 |
Annual Sum or Average | 23.00 | 16.65 |
Minimum of Months | 21.79 | 3.96 |
Maximum of Months | 23.81 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 3.96 |
February | 22.18 | 7.94 |
March | 22.98 | 13.76 |
April | 23.47 | 17.21 |
May | 23.74 | 20.84 |
June | 23.87 | 24.80 |
July | 23.89 | 26.06 |
August | 23.89 | 26.55 |
September | 23.86 | 22.53 |
October | 23.37 | 16.03 |
November | 22.83 | 11.94 |
December | 22.01 | 7.70 |
Annual Sum or Average | 23.15 | 16.65 |
Minimum of Months | 21.61 | 3.96 |
Maximum of Months | 23.89 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.14 | 3.96 |
February | 24.59 | 7.94 |
March | 25.43 | 13.76 |
April | 25.97 | 17.21 |
May | 26.62 | 20.84 |
June | 28.99 | 24.80 |
July | 30.60 | 26.06 |
August | 30.68 | 26.55 |
September | 29.18 | 22.53 |
October | 26.51 | 16.03 |
November | 25.34 | 11.94 |
December | 24.64 | 7.70 |
Annual Sum or Average | 26.90 | 16.65 |
Minimum of Months | 24.14 | 3.96 |
Maximum of Months | 30.68 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.77 | 3.96 |
February | 20.59 | 7.94 |
March | 21.88 | 13.76 |
April | 22.59 | 17.21 |
May | 23.12 | 20.84 |
June | 23.31 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.30 | 22.53 |
October | 22.45 | 16.03 |
November | 21.56 | 11.94 |
December | 20.47 | 7.70 |
Annual Sum or Average | 22.15 | 16.65 |
Minimum of Months | 19.77 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | 3.96 |
February | 20.32 | 7.94 |
March | 21.57 | 13.76 |
April | 22.35 | 17.21 |
May | 22.96 | 20.84 |
June | 23.25 | 24.80 |
July | 23.32 | 26.06 |
August | 23.33 | 26.55 |
September | 23.17 | 22.53 |
October | 22.13 | 16.03 |
November | 21.22 | 11.94 |
December | 20.14 | 7.70 |
Annual Sum or Average | 21.95 | 16.65 |
Minimum of Months | 19.54 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | 3.96 |
February | 21.04 | 7.94 |
March | 21.42 | 13.76 |
April | 21.64 | 17.21 |
May | 21.74 | 20.84 |
June | 21.75 | 24.80 |
July | 21.75 | 26.06 |
August | 21.75 | 26.55 |
September | 21.75 | 22.53 |
October | 21.57 | 16.03 |
November | 21.38 | 11.94 |
December | 21.04 | 7.70 |
Annual Sum or Average | 21.47 | 16.65 |
Minimum of Months | 20.79 | 3.96 |
Maximum of Months | 21.75 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.14 | 3.96 |
February | 21.31 | 7.94 |
March | 21.58 | 13.76 |
April | 21.69 | 17.21 |
May | 21.74 | 20.84 |
June | 21.75 | 24.80 |
July | 21.75 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.67 | 16.03 |
November | 21.60 | 11.94 |
December | 21.38 | 7.70 |
Annual Sum or Average | 21.60 | 16.65 |
Minimum of Months | 21.14 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 3.96 |
February | 21.58 | 7.94 |
March | 21.70 | 13.76 |
April | 21.74 | 17.21 |
May | 21.75 | 20.84 |
June | 21.75 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.73 | 16.03 |
November | 21.71 | 11.94 |
December | 21.64 | 7.70 |
Annual Sum or Average | 21.70 | 16.65 |
Minimum of Months | 21.49 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.24 | 3.96 |
February | 22.39 | 7.94 |
March | 22.55 | 13.76 |
April | 22.58 | 17.21 |
May | 22.59 | 20.84 |
June | 22.37 | 24.80 |
July | 22.27 | 26.06 |
August | 22.20 | 26.55 |
September | 22.43 | 22.53 |
October | 22.53 | 16.03 |
November | 22.42 | 11.94 |
December | 22.33 | 7.70 |
Annual Sum or Average | 22.41 | 16.65 |
Minimum of Months | 22.20 | 3.96 |
Maximum of Months | 22.59 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.02 | 3.96 |
February | 51.32 | 7.94 |
March | 51.99 | 13.76 |
April | 52.32 | 17.21 |
May | 52.67 | 20.84 |
June | 53.04 | 24.80 |
July | 53.24 | 26.06 |
August | 53.37 | 26.55 |
September | 52.99 | 22.53 |
October | 52.39 | 16.03 |
November | 51.94 | 11.94 |
December | 51.41 | 7.70 |
Annual Sum or Average | 52.31 | 16.65 |
Minimum of Months | 51.02 | 3.96 |
Maximum of Months | 53.37 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.08 | 3.96 |
February | 68.39 | 7.94 |
March | 69.26 | 13.76 |
April | 69.81 | 17.21 |
May | 70.32 | 20.84 |
June | 70.78 | 24.80 |
July | 71.07 | 26.06 |
August | 71.19 | 26.55 |
September | 70.71 | 22.53 |
October | 69.80 | 16.03 |
November | 69.22 | 11.94 |
December | 68.52 | 7.70 |
Annual Sum or Average | 69.77 | 16.65 |
Minimum of Months | 68.08 | 3.96 |
Maximum of Months | 71.19 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 3.96 |
February | 23.17 | 7.94 |
March | 23.56 | 13.76 |
April | 23.72 | 17.21 |
May | 23.86 | 20.84 |
June | 23.88 | 24.80 |
July | 23.89 | 26.06 |
August | 23.89 | 26.55 |
September | 23.88 | 22.53 |
October | 23.70 | 16.03 |
November | 23.44 | 11.94 |
December | 23.15 | 7.70 |
Annual Sum or Average | 23.59 | 16.65 |
Minimum of Months | 22.92 | 3.96 |
Maximum of Months | 23.89 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 3.96 |
February | 22.77 | 7.94 |
March | 23.45 | 13.76 |
April | 23.69 | 17.21 |
May | 23.86 | 20.84 |
June | 23.88 | 24.80 |
July | 23.89 | 26.06 |
August | 23.89 | 26.55 |
September | 23.88 | 22.53 |
October | 23.67 | 16.03 |
November | 23.29 | 11.94 |
December | 22.72 | 7.70 |
Annual Sum or Average | 23.44 | 16.65 |
Minimum of Months | 22.31 | 3.96 |
Maximum of Months | 23.89 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.60 | 3.96 |
February | 18.77 | 7.94 |
March | 21.22 | 13.76 |
April | 22.70 | 17.21 |
May | 23.93 | 20.84 |
June | 25.31 | 24.80 |
July | 25.70 | 26.06 |
August | 25.92 | 26.55 |
September | 24.60 | 22.53 |
October | 22.34 | 16.03 |
November | 20.77 | 11.94 |
December | 18.86 | 7.70 |
Annual Sum or Average | 22.33 | 16.65 |
Minimum of Months | 17.60 | 3.96 |
Maximum of Months | 25.92 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | 3.96 |
February | 21.01 | 7.94 |
March | 22.49 | 13.76 |
April | 23.29 | 17.21 |
May | 23.96 | 20.84 |
June | 24.71 | 24.80 |
July | 24.95 | 26.06 |
August | 25.10 | 26.55 |
September | 24.39 | 22.53 |
October | 23.18 | 16.03 |
November | 22.27 | 11.94 |
December | 21.10 | 7.70 |
Annual Sum or Average | 23.07 | 16.65 |
Minimum of Months | 20.28 | 3.96 |
Maximum of Months | 25.10 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.77 | 3.96 |
February | 18.94 | 7.94 |
March | 21.54 | 13.76 |
April | 23.01 | 17.21 |
May | 24.18 | 20.84 |
June | 25.41 | 24.80 |
July | 25.75 | 26.06 |
August | 25.97 | 26.55 |
September | 24.70 | 22.53 |
October | 22.52 | 16.03 |
November | 21.02 | 11.94 |
December | 19.04 | 7.70 |
Annual Sum or Average | 22.51 | 16.65 |
Minimum of Months | 17.77 | 3.96 |
Maximum of Months | 25.97 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.05 | 3.96 |
February | 22.66 | 7.94 |
March | 23.60 | 13.76 |
April | 23.81 | 17.21 |
May | 23.89 | 20.84 |
June | 23.94 | 24.80 |
July | 24.01 | 26.06 |
August | 24.03 | 26.55 |
September | 23.90 | 22.53 |
October | 23.77 | 16.03 |
November | 23.43 | 11.94 |
December | 22.65 | 7.70 |
Annual Sum or Average | 23.48 | 16.65 |
Minimum of Months | 22.05 | 3.96 |
Maximum of Months | 24.03 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.45 | 3.96 |
February | 17.73 | 7.94 |
March | 20.47 | 13.76 |
April | 22.14 | 17.21 |
May | 23.46 | 20.84 |
June | 24.78 | 24.80 |
July | 25.10 | 26.06 |
August | 25.26 | 26.55 |
September | 23.87 | 22.53 |
October | 21.47 | 16.03 |
November | 19.77 | 11.94 |
December | 17.70 | 7.70 |
Annual Sum or Average | 21.54 | 16.65 |
Minimum of Months | 16.45 | 3.96 |
Maximum of Months | 25.26 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.27 | 3.96 |
February | 20.15 | 7.94 |
March | 21.55 | 13.76 |
April | 22.59 | 17.21 |
May | 23.19 | 20.84 |
June | 23.31 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.26 | 22.53 |
October | 22.18 | 16.03 |
November | 20.99 | 11.94 |
December | 19.66 | 7.70 |
Annual Sum or Average | 21.91 | 16.65 |
Minimum of Months | 19.27 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | 3.96 |
February | 21.20 | 7.94 |
March | 21.57 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.68 | 16.03 |
November | 21.53 | 11.94 |
December | 21.19 | 7.70 |
Annual Sum or Average | 21.55 | 16.65 |
Minimum of Months | 20.93 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | 3.96 |
February | 21.24 | 7.94 |
March | 21.59 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.69 | 16.03 |
November | 21.55 | 11.94 |
December | 21.24 | 7.70 |
Annual Sum or Average | 21.57 | 16.65 |
Minimum of Months | 20.97 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.00 | 3.96 |
February | 21.26 | 7.94 |
March | 21.61 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.69 | 16.03 |
November | 21.58 | 11.94 |
December | 21.28 | 7.70 |
Annual Sum or Average | 21.58 | 16.65 |
Minimum of Months | 21.00 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | 3.96 |
February | 21.05 | 7.94 |
March | 21.46 | 13.76 |
April | 21.68 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.61 | 16.03 |
November | 21.40 | 11.94 |
December | 21.01 | 7.70 |
Annual Sum or Average | 21.48 | 16.65 |
Minimum of Months | 20.76 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.20 | 3.96 |
February | 21.37 | 7.94 |
March | 21.66 | 13.76 |
April | 21.73 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.71 | 16.03 |
November | 21.66 | 11.94 |
December | 21.45 | 7.70 |
Annual Sum or Average | 21.63 | 16.65 |
Minimum of Months | 21.20 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 3.96 |
February | 23.11 | 7.94 |
March | 23.32 | 13.76 |
April | 23.33 | 17.21 |
May | 23.33 | 20.84 |
June | 23.33 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.33 | 22.53 |
October | 23.33 | 16.03 |
November | 23.30 | 11.94 |
December | 23.21 | 7.70 |
Annual Sum or Average | 23.27 | 16.65 |
Minimum of Months | 23.00 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.81 | 3.96 |
February | 31.30 | 7.94 |
March | 32.30 | 13.76 |
April | 32.81 | 17.21 |
May | 33.20 | 20.84 |
June | 33.58 | 24.80 |
July | 33.77 | 26.06 |
August | 33.88 | 26.55 |
September | 33.46 | 22.53 |
October | 32.74 | 16.03 |
November | 32.16 | 11.94 |
December | 31.34 | 7.70 |
Annual Sum or Average | 32.62 | 16.65 |
Minimum of Months | 30.81 | 3.96 |
Maximum of Months | 33.88 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 3.96 |
February | 22.05 | 7.94 |
March | 22.32 | 13.76 |
April | 22.54 | 17.21 |
May | 22.77 | 20.84 |
June | 23.14 | 24.80 |
July | 23.38 | 26.06 |
August | 23.52 | 26.55 |
September | 22.99 | 22.53 |
October | 22.56 | 16.03 |
November | 22.25 | 11.94 |
December | 22.01 | 7.70 |
Annual Sum or Average | 22.62 | 16.65 |
Minimum of Months | 21.89 | 3.96 |
Maximum of Months | 23.52 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 3.96 |
February | 21.49 | 7.94 |
March | 21.69 | 13.76 |
April | 21.74 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.73 | 16.03 |
November | 21.70 | 11.94 |
December | 21.57 | 7.70 |
Annual Sum or Average | 21.67 | 16.65 |
Minimum of Months | 21.36 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 3.96 |
February | 21.37 | 7.94 |
March | 21.66 | 13.76 |
April | 21.73 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.76 | 22.53 |
October | 21.72 | 16.03 |
November | 21.66 | 11.94 |
December | 21.45 | 7.70 |
Annual Sum or Average | 21.63 | 16.65 |
Minimum of Months | 21.19 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 3.96 |
February | 20.39 | 7.94 |
March | 22.34 | 13.76 |
April | 23.41 | 17.21 |
May | 24.24 | 20.84 |
June | 25.13 | 24.80 |
July | 25.38 | 26.06 |
August | 25.52 | 26.55 |
September | 24.68 | 22.53 |
October | 23.13 | 16.03 |
November | 22.00 | 11.94 |
December | 20.47 | 7.70 |
Annual Sum or Average | 23.02 | 16.65 |
Minimum of Months | 19.42 | 3.96 |
Maximum of Months | 25.52 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.73 | 3.96 |
February | 18.24 | 7.94 |
March | 21.35 | 13.76 |
April | 23.23 | 17.21 |
May | 24.69 | 20.84 |
June | 26.31 | 24.80 |
July | 26.75 | 26.06 |
August | 26.95 | 26.55 |
September | 25.40 | 22.53 |
October | 22.63 | 16.03 |
November | 20.73 | 11.94 |
December | 18.32 | 7.70 |
Annual Sum or Average | 22.63 | 16.65 |
Minimum of Months | 16.73 | 3.96 |
Maximum of Months | 26.95 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.01 | 3.96 |
February | 18.34 | 7.94 |
March | 21.22 | 13.76 |
April | 22.91 | 17.21 |
May | 24.25 | 20.84 |
June | 25.59 | 24.80 |
July | 25.95 | 26.06 |
August | 26.17 | 26.55 |
September | 24.79 | 22.53 |
October | 22.31 | 16.03 |
November | 20.60 | 11.94 |
December | 18.38 | 7.70 |
Annual Sum or Average | 22.31 | 16.65 |
Minimum of Months | 17.01 | 3.96 |
Maximum of Months | 26.17 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.32 | 3.96 |
February | 21.92 | 7.94 |
March | 22.87 | 13.76 |
April | 23.52 | 17.21 |
May | 23.84 | 20.84 |
June | 23.88 | 24.80 |
July | 23.89 | 26.06 |
August | 23.89 | 26.55 |
September | 23.87 | 22.53 |
October | 23.27 | 16.03 |
November | 22.55 | 11.94 |
December | 21.58 | 7.70 |
Annual Sum or Average | 23.04 | 16.65 |
Minimum of Months | 21.32 | 3.96 |
Maximum of Months | 23.89 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.34 | 3.96 |
February | 16.84 | 7.94 |
March | 19.96 | 13.76 |
April | 22.00 | 17.21 |
May | 23.60 | 20.84 |
June | 25.07 | 24.80 |
July | 25.44 | 26.06 |
August | 25.60 | 26.55 |
September | 24.04 | 22.53 |
October | 21.14 | 16.03 |
November | 19.08 | 11.94 |
December | 16.69 | 7.70 |
Annual Sum or Average | 21.26 | 16.65 |
Minimum of Months | 15.34 | 3.96 |
Maximum of Months | 25.60 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.08 | 3.96 |
February | 19.82 | 7.94 |
March | 21.06 | 13.76 |
April | 22.33 | 17.21 |
May | 23.11 | 20.84 |
June | 23.29 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.20 | 22.53 |
October | 21.77 | 16.03 |
November | 20.43 | 11.94 |
December | 19.27 | 7.70 |
Annual Sum or Average | 21.68 | 16.65 |
Minimum of Months | 19.08 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.14 | 3.96 |
February | 19.93 | 7.94 |
March | 21.22 | 13.76 |
April | 22.42 | 17.21 |
May | 23.16 | 20.84 |
June | 23.30 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.24 | 22.53 |
October | 21.90 | 16.03 |
November | 20.62 | 11.94 |
December | 19.40 | 7.70 |
Annual Sum or Average | 21.76 | 16.65 |
Minimum of Months | 19.14 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.18 | 3.96 |
February | 19.99 | 7.94 |
March | 21.29 | 13.76 |
April | 22.43 | 17.21 |
May | 23.14 | 20.84 |
June | 23.30 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.23 | 22.53 |
October | 21.93 | 16.03 |
November | 20.71 | 11.94 |
December | 19.47 | 7.70 |
Annual Sum or Average | 21.79 | 16.65 |
Minimum of Months | 19.18 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 3.96 |
February | 21.18 | 7.94 |
March | 21.55 | 13.76 |
April | 21.70 | 17.21 |
May | 21.75 | 20.84 |
June | 21.75 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.66 | 16.03 |
November | 21.51 | 11.94 |
December | 21.18 | 7.70 |
Annual Sum or Average | 21.54 | 16.65 |
Minimum of Months | 20.90 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.13 | 3.96 |
February | 19.87 | 7.94 |
March | 21.17 | 13.76 |
April | 22.38 | 17.21 |
May | 23.13 | 20.84 |
June | 23.30 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.22 | 22.53 |
October | 21.87 | 16.03 |
November | 20.60 | 11.94 |
December | 19.37 | 7.70 |
Annual Sum or Average | 21.73 | 16.65 |
Minimum of Months | 19.13 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | 3.96 |
February | 21.22 | 7.94 |
March | 21.58 | 13.76 |
April | 21.71 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.67 | 16.03 |
November | 21.57 | 11.94 |
December | 21.28 | 7.70 |
Annual Sum or Average | 21.57 | 16.65 |
Minimum of Months | 21.01 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | 3.96 |
February | 21.51 | 7.94 |
March | 21.70 | 13.76 |
April | 21.74 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.73 | 16.03 |
November | 21.70 | 11.94 |
December | 21.60 | 7.70 |
Annual Sum or Average | 21.68 | 16.65 |
Minimum of Months | 21.39 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 3.96 |
February | 23.38 | 7.94 |
March | 24.69 | 13.76 |
April | 25.39 | 17.21 |
May | 25.87 | 20.84 |
June | 26.25 | 24.80 |
July | 26.38 | 26.06 |
August | 26.46 | 26.55 |
September | 26.07 | 22.53 |
October | 25.19 | 16.03 |
November | 24.43 | 11.94 |
December | 23.36 | 7.70 |
Annual Sum or Average | 25.02 | 16.65 |
Minimum of Months | 22.70 | 3.96 |
Maximum of Months | 26.46 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 3.96 |
February | 21.98 | 7.94 |
March | 23.00 | 13.76 |
April | 23.23 | 17.21 |
May | 23.33 | 20.84 |
June | 23.33 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.33 | 22.53 |
October | 23.18 | 16.03 |
November | 22.85 | 11.94 |
December | 22.09 | 7.70 |
Annual Sum or Average | 22.86 | 16.65 |
Minimum of Months | 21.31 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 3.96 |
February | 21.40 | 7.94 |
March | 21.65 | 13.76 |
April | 21.73 | 17.21 |
May | 21.75 | 20.84 |
June | 21.75 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.71 | 16.03 |
November | 21.66 | 11.94 |
December | 21.48 | 7.70 |
Annual Sum or Average | 21.64 | 16.65 |
Minimum of Months | 21.24 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 3.96 |
February | 20.56 | 7.94 |
March | 22.05 | 13.76 |
April | 22.74 | 17.21 |
May | 23.19 | 20.84 |
June | 23.31 | 24.80 |
July | 23.33 | 26.06 |
August | 23.33 | 26.55 |
September | 23.27 | 22.53 |
October | 22.52 | 16.03 |
November | 21.74 | 11.94 |
December | 20.39 | 7.70 |
Annual Sum or Average | 22.18 | 16.65 |
Minimum of Months | 19.69 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.37 | 3.96 |
February | 19.57 | 7.94 |
March | 21.95 | 13.76 |
April | 23.31 | 17.21 |
May | 24.35 | 20.84 |
June | 25.38 | 24.80 |
July | 25.65 | 26.06 |
August | 25.80 | 26.55 |
September | 24.81 | 22.53 |
October | 22.88 | 16.03 |
November | 21.45 | 11.94 |
December | 19.57 | 7.70 |
Annual Sum or Average | 22.77 | 16.65 |
Minimum of Months | 18.37 | 3.96 |
Maximum of Months | 25.80 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.80 | 3.96 |
February | 17.52 | 7.94 |
March | 21.01 | 13.76 |
April | 23.16 | 17.21 |
May | 24.83 | 20.84 |
June | 26.59 | 24.80 |
July | 27.07 | 26.06 |
August | 27.26 | 26.55 |
September | 25.55 | 22.53 |
October | 22.41 | 16.03 |
November | 20.24 | 11.94 |
December | 17.54 | 7.70 |
Annual Sum or Average | 22.44 | 16.65 |
Minimum of Months | 15.80 | 3.96 |
Maximum of Months | 27.26 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.81 | 3.96 |
February | 17.41 | 7.94 |
March | 20.69 | 13.76 |
April | 22.69 | 17.21 |
May | 24.36 | 20.84 |
June | 25.91 | 24.80 |
July | 26.34 | 26.06 |
August | 26.56 | 26.55 |
September | 24.87 | 22.53 |
October | 21.89 | 16.03 |
November | 19.82 | 11.94 |
December | 17.31 | 7.70 |
Annual Sum or Average | 21.99 | 16.65 |
Minimum of Months | 15.81 | 3.96 |
Maximum of Months | 26.56 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 3.96 |
February | 21.65 | 7.94 |
March | 22.40 | 13.76 |
April | 23.07 | 17.21 |
May | 23.59 | 20.84 |
June | 23.88 | 24.80 |
July | 23.99 | 26.06 |
August | 24.00 | 26.55 |
September | 23.73 | 22.53 |
October | 22.72 | 16.03 |
November | 22.07 | 11.94 |
December | 21.38 | 7.70 |
Annual Sum or Average | 22.82 | 16.65 |
Minimum of Months | 21.24 | 3.96 |
Maximum of Months | 24.00 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.50 | 3.96 |
February | 16.17 | 7.94 |
March | 19.53 | 13.76 |
April | 21.80 | 17.21 |
May | 23.66 | 20.84 |
June | 25.31 | 24.80 |
July | 25.74 | 26.06 |
August | 25.90 | 26.55 |
September | 24.06 | 22.53 |
October | 20.76 | 16.03 |
November | 18.45 | 11.94 |
December | 15.92 | 7.70 |
Annual Sum or Average | 21.01 | 16.65 |
Minimum of Months | 14.50 | 3.96 |
Maximum of Months | 25.90 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | 3.96 |
February | 20.94 | 7.94 |
March | 21.36 | 13.76 |
April | 21.65 | 17.21 |
May | 21.74 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.50 | 16.03 |
November | 21.27 | 11.94 |
December | 20.80 | 7.70 |
Annual Sum or Average | 21.41 | 16.65 |
Minimum of Months | 20.63 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.08 | 3.96 |
February | 19.70 | 7.94 |
March | 20.83 | 13.76 |
April | 22.02 | 17.21 |
May | 22.91 | 20.84 |
June | 23.24 | 24.80 |
July | 23.32 | 26.06 |
August | 23.33 | 26.55 |
September | 23.08 | 22.53 |
October | 21.40 | 16.03 |
November | 20.25 | 11.94 |
December | 19.24 | 7.70 |
Annual Sum or Average | 21.54 | 16.65 |
Minimum of Months | 19.08 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.09 | 3.96 |
February | 19.73 | 7.94 |
March | 20.86 | 13.76 |
April | 22.01 | 17.21 |
May | 22.89 | 20.84 |
June | 23.23 | 24.80 |
July | 23.32 | 26.06 |
August | 23.33 | 26.55 |
September | 23.07 | 22.53 |
October | 21.40 | 16.03 |
November | 20.28 | 11.94 |
December | 19.26 | 7.70 |
Annual Sum or Average | 21.55 | 16.65 |
Minimum of Months | 19.09 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | 3.96 |
February | 21.11 | 7.94 |
March | 21.52 | 13.76 |
April | 21.70 | 17.21 |
May | 21.75 | 20.84 |
June | 21.75 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.63 | 16.03 |
November | 21.47 | 11.94 |
December | 21.09 | 7.70 |
Annual Sum or Average | 21.51 | 16.65 |
Minimum of Months | 20.81 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.07 | 3.96 |
February | 19.70 | 7.94 |
March | 20.85 | 13.76 |
April | 22.06 | 17.21 |
May | 22.92 | 20.84 |
June | 23.25 | 24.80 |
July | 23.32 | 26.06 |
August | 23.33 | 26.55 |
September | 23.09 | 22.53 |
October | 21.45 | 16.03 |
November | 20.27 | 11.94 |
December | 19.23 | 7.70 |
Annual Sum or Average | 21.55 | 16.65 |
Minimum of Months | 19.07 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.41 | 3.96 |
February | 20.16 | 7.94 |
March | 21.46 | 13.76 |
April | 22.31 | 17.21 |
May | 22.98 | 20.84 |
June | 23.25 | 24.80 |
July | 23.32 | 26.06 |
August | 23.33 | 26.55 |
September | 23.14 | 22.53 |
October | 21.95 | 16.03 |
November | 21.03 | 11.94 |
December | 19.84 | 7.70 |
Annual Sum or Average | 21.86 | 16.65 |
Minimum of Months | 19.41 | 3.96 |
Maximum of Months | 23.33 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | 3.96 |
February | 21.37 | 7.94 |
March | 21.63 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.69 | 16.03 |
November | 21.64 | 11.94 |
December | 21.47 | 7.70 |
Annual Sum or Average | 21.63 | 16.65 |
Minimum of Months | 21.21 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.39 | 3.96 |
February | 21.17 | 7.94 |
March | 22.63 | 13.76 |
April | 23.52 | 17.21 |
May | 24.23 | 20.84 |
June | 24.81 | 24.80 |
July | 24.98 | 26.06 |
August | 25.05 | 26.55 |
September | 24.39 | 22.53 |
October | 23.16 | 16.03 |
November | 22.22 | 11.94 |
December | 21.07 | 7.70 |
Annual Sum or Average | 23.15 | 16.65 |
Minimum of Months | 20.39 | 3.96 |
Maximum of Months | 25.05 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 3.96 |
February | 21.34 | 7.94 |
March | 21.63 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.69 | 16.03 |
November | 21.64 | 11.94 |
December | 21.43 | 7.70 |
Annual Sum or Average | 21.62 | 16.65 |
Minimum of Months | 21.16 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | 3.96 |
February | 21.35 | 7.94 |
March | 21.62 | 13.76 |
April | 21.72 | 17.21 |
May | 21.75 | 20.84 |
June | 21.75 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.69 | 16.03 |
November | 21.63 | 11.94 |
December | 21.44 | 7.70 |
Annual Sum or Average | 21.62 | 16.65 |
Minimum of Months | 21.18 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 3.96 |
February | 21.17 | 7.94 |
March | 21.55 | 13.76 |
April | 21.70 | 17.21 |
May | 21.75 | 20.84 |
June | 21.76 | 24.80 |
July | 21.76 | 26.06 |
August | 21.76 | 26.55 |
September | 21.75 | 22.53 |
October | 21.65 | 16.03 |
November | 21.55 | 11.94 |
December | 21.23 | 7.70 |
Annual Sum or Average | 21.55 | 16.65 |
Minimum of Months | 20.95 | 3.96 |
Maximum of Months | 21.76 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.80 | 3.96 |
February | 19.10 | 7.94 |
March | 21.58 | 13.76 |
April | 23.07 | 17.21 |
May | 24.28 | 20.84 |
June | 25.43 | 24.80 |
July | 25.74 | 26.06 |
August | 25.87 | 26.55 |
September | 24.63 | 22.53 |
October | 22.50 | 16.03 |
November | 20.95 | 11.94 |
December | 19.03 | 7.70 |
Annual Sum or Average | 22.52 | 16.65 |
Minimum of Months | 17.80 | 3.96 |
Maximum of Months | 25.87 | 26.55 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.98 | 3.96 |
February | 16.87 | 7.94 |
March | 20.58 | 13.76 |
April | 22.93 | 17.21 |
May | 24.83 | 20.84 |
June | 26.75 | 24.80 |
July | 27.28 | 26.06 |
August | 27.46 | 26.55 |
September | 25.45 | 22.53 |
October | 22.00 | 16.03 |
November | 19.63 | 11.94 |
December | 16.80 | 7.70 |
Annual Sum or Average | 22.16 | 16.65 |
Minimum of Months | 14.98 | 3.96 |
Maximum of Months | 27.46 | 26.55 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:35
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.150144E+12 | 112590.335 | 08-JAN-07:15 | 15177.258 | 39465.561 | 8731.081 | 44829.304 | 191.017 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.130288E+12 | 131494.183 | 12-FEB-07:15 | 15177.258 | 39465.561 | 8755.012 | 63760.573 | 139.665 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.135484E+12 | 87575.217 | 19-MAR-06:45 | 15177.258 | 39465.561 | 8725.136 | 18299.773 | 1711.376 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.138208E+12 | 87624.226 | 06-APR-06:15 | 15177.258 | 39465.561 | 8725.136 | 18524.395 | 1535.763 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.153535E+12 | 89764.364 | 26-MAY-07:00 | 17566.637 | 43276.576 | 9137.833 | 0.000 | 19775.206 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.163805E+12 | 96551.526 | 23-JUN-07:00 | 17641.054 | 43276.576 | 9137.833 | 0.000 | 26487.951 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.177722E+12 | 101799.045 | 07-JUL-07:00 | 17789.888 | 43276.576 | 9137.833 | 0.000 | 31586.635 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.181128E+12 | 102043.661 | 19-AUG-07:00 | 17566.637 | 43276.576 | 9137.833 | 0.000 | 32054.503 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.156862E+12 | 96136.286 | 09-SEP-07:00 | 17789.888 | 43276.576 | 9137.833 | 0.000 | 25923.876 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.142332E+12 | 86825.896 | 26-OCT-06:30 | 15177.258 | 39465.561 | 8725.136 | 17298.191 | 1963.637 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.132009E+12 | 99687.944 | 21-NOV-07:15 | 15177.258 | 39465.561 | 8725.136 | 31725.331 | 398.545 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.138483E+12 | 108452.814 | 18-DEC-07:15 | 15177.258 | 39465.561 | 8725.136 | 40628.795 | 259.951 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.180000E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.130288E+12 | 86825.896 | 15177.258 | 39465.561 | 8725.136 | 0.000 | 139.665 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.181128E+12 | 131494.183 | 17789.888 | 43276.576 | 9137.833 | 63760.573 | 32054.503 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:35
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.102163E+12 | 106028.929 | 07-JAN-10:15 | 11721.774 | 40096.028 | 0.000 | 54211.128 | 54211.128 | 54211.128 | 11721.774 |
February | 0.884303E+11 | 104825.298 | 03-FEB-10:00 | 10251.611 | 40096.028 | 0.000 | 54477.660 | 54477.660 | 54477.660 | 10251.611 |
March | 0.893672E+11 | 95979.063 | 18-MAR-09:30 | 3880.496 | 40096.028 | 0.000 | 52002.539 | 52002.539 | 52002.539 | 3880.496 |
April | 0.825693E+11 | 92409.792 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 52313.764 | 52313.764 | 52313.764 | 0.000 |
May | 0.811849E+11 | 89586.583 | 02-MAY-08:45 | 0.000 | 40096.028 | 0.000 | 49490.555 | 49490.555 | 49490.555 | 0.000 |
June | 0.764960E+11 | 74080.371 | 01-JUN-08:00 | 0.000 | 40096.028 | 0.000 | 33984.343 | 33984.343 | 33984.343 | 0.000 |
July | 0.779628E+11 | 73323.058 | 02-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 33227.029 | 33227.029 | 33227.029 | 0.000 |
August | 0.778875E+11 | 73235.665 | 31-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 33139.637 | 33139.637 | 33139.637 | 0.000 |
September | 0.762970E+11 | 73942.030 | 30-SEP-08:45 | 0.000 | 40096.028 | 0.000 | 33846.002 | 33846.002 | 33846.002 | 0.000 |
October | 0.812732E+11 | 89837.682 | 30-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 49741.654 | 49741.654 | 49741.654 | 0.000 |
November | 0.840734E+11 | 95384.540 | 22-NOV-10:15 | 4691.075 | 40096.028 | 0.000 | 50597.437 | 50597.437 | 50597.437 | 4691.075 |
December | 0.938474E+11 | 97946.311 | 02-DEC-10:30 | 7016.001 | 40096.028 | 0.000 | 50834.282 | 50834.282 | 50834.282 | 7016.001 |
Annual Sum or Average | 0.101155E+13 | 0.000 | ||||||||
Minimum of Months | 0.762970E+11 | 73235.665 | 0.000 | 40096.028 | 0.000 | 33139.637 | 33139.637 | 33139.637 | 0.000 | |
Maximum of Months | 0.102163E+12 | 106028.929 | 11721.774 | 40096.028 | 0.000 | 54477.660 | 54477.660 | 54477.660 | 11721.774 |