Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2018-10-19 10:15:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2727.66 | 679.61 | 732.24 |
Net Site Energy | 2727.66 | 679.61 | 732.24 |
Total Source Energy | 6285.56 | 1566.07 | 1687.36 |
Net Source Energy | 6285.56 | 1566.07 | 1687.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 100.72 | 57.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 149.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 276.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 650.17 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1598.07 | 1129.60 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 100.72 | 57.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 149.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 276.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 650.17 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 141.42 | 190.09 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.00 | 303.24 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 131.25 | 176.43 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 398.16 | 281.44 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1598.07 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1598.07 | 100.00 |
Total On-Site and Utility Electric Sources | 1598.07 | 100.00 |
Total Electricity End Uses | 1598.07 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 205.25 |
Time Setpoint Not Met During Occupied Cooling | 2836.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4594.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | William R Fairchild WA USA TMY3 WMO#=727885 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5327.81 | 4246.21 | 1081.60 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12714.15 | 9660.02 | 3054.13 | 0.76 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6653.13 | 4857.03 | 1796.10 | 0.73 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11698.67 | 9283.26 | 2415.41 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5079.2 | 3.15 | 10.77 | 11.40 | 10.55 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12181.0 | 3.22 | 10.99 | 11.64 | 10.88 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6399.3 | 3.28 | 11.18 | 11.84 | 11.16 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11157.9 | 3.16 | 10.79 | 11.42 | 10.58 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.98 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 18536.28 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.91 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.98 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2520.80 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2817.75 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.91 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.98 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2520.80 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 888.84 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2817.75 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 896.86 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 888.78 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.91 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.98 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2640.97 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1095.62 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2828.14 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3555.37 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1163.68 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1115.31 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 930.91 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3555.11 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1084.92 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 317.91 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3659.85 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 15340.21 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 8214.57 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6202.29 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.32 | 358.88 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.69 | 769.36 | 1120.11 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.33 | 366.17 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.70 | 780.57 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 6869.00 | 8242.80 | 0.572 | 0.687 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 26.26 | 0.00838 |
RESTROOMFLR1 | 355.12 | 426.14 | 0.030 | 0.035 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49 | 0.00838 |
MEETINGROOMFLR1 | 3266.98 | 3920.37 | 0.272 | 0.327 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40 | 0.00838 |
GUESTROOM101 | 433.33 | 520.00 | 0.050 | 0.060 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 25.85 | 0.00838 |
GUESTROOM102 | 338.02 | 405.63 | 0.039 | 0.047 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
GUESTROOM103 | 877.40 | 1052.88 | 0.102 | 0.122 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
GUESTROOM104 | 1163.63 | 1396.36 | 0.135 | 0.162 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM105 | 1567.32 | 1880.78 | 0.181 | 0.218 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 26.40 | 0.00838 |
EMPLOYEELOUNGEFLR1 | 5464.95 | 6557.94 | 0.455 | 0.547 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
EXERCISECENTERFLR1 | 1149.02 | 1378.82 | 0.096 | 0.115 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.13 | 0.00838 |
FRONTOFFICEFLR1 | 3206.78 | 3848.14 | 0.267 | 0.320 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM201 | 589.49 | 707.39 | 0.068 | 0.082 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:45:00 | 25.76 | 0.00838 |
GUESTROOM202_205 | 3664.96 | 4397.95 | 0.424 | 0.509 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 25.85 | 0.00838 |
GUESTROOM206_208 | 2964.16 | 3556.99 | 0.343 | 0.412 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 25.99 | 0.00838 |
GUESTROOM209_212 | 3489.54 | 4187.45 | 0.404 | 0.485 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 25.85 | 0.00838 |
GUESTROOM213 | 958.50 | 1150.20 | 0.111 | 0.133 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
GUESTROOM214 | 1314.06 | 1576.88 | 0.152 | 0.183 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM215_218 | 9829.06 | 11794.88 | 1.138 | 1.365 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM219 | 5529.22 | 6635.07 | 0.640 | 0.768 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM220_223 | 4697.93 | 5637.51 | 0.544 | 0.653 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM224 | 1322.47 | 1586.96 | 0.153 | 0.184 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM301 | 393.50 | 472.20 | 0.046 | 0.055 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 25.95 | 0.00838 |
GUESTROOM302_305 | 1099.52 | 1319.42 | 0.127 | 0.153 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49 | 0.00838 |
GUESTROOM306_308 | 970.36 | 1164.44 | 0.112 | 0.135 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 25.67 | 0.00838 |
GUESTROOM309_312 | 3427.79 | 4113.35 | 0.397 | 0.476 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 25.67 | 0.00838 |
GUESTROOM313 | 455.08 | 546.10 | 0.053 | 0.063 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 22.85 | 0.00838 |
GUESTROOM314 | 1221.29 | 1465.55 | 0.141 | 0.170 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 26.40 | 0.00838 |
GUESTROOM315_318 | 5107.10 | 6128.52 | 0.591 | 0.710 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM319 | 1143.01 | 1371.62 | 0.132 | 0.159 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM320_323 | 4467.99 | 5361.59 | 0.517 | 0.621 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM324 | 736.98 | 884.38 | 0.085 | 0.102 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM401 | 1194.61 | 1433.53 | 0.138 | 0.166 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 26.06 | 0.00838 |
GUESTROOM402_405 | 1763.06 | 2115.68 | 0.204 | 0.245 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM406_408 | 1513.42 | 1816.10 | 0.175 | 0.210 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM409_412 | 4402.76 | 5283.31 | 0.510 | 0.612 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM413 | 669.89 | 803.87 | 0.078 | 0.093 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 26.26 | 0.00838 |
GUESTROOM414 | 1000.19 | 1200.22 | 0.116 | 0.139 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40 | 0.00838 |
GUESTROOM415_418 | 5774.53 | 6929.43 | 0.669 | 0.802 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
GUESTROOM419 | 1578.24 | 1893.89 | 0.183 | 0.219 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 26.40 | 0.00838 |
GUESTROOM420_423 | 5726.09 | 6871.30 | 0.663 | 0.795 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40 | 0.00838 |
GUESTROOM424 | 1575.13 | 1890.16 | 0.182 | 0.219 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 26.40 | 0.00838 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
CORRIDORFLR1 | 12050.88 | 14461.06 | 1.003 | 1.204 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 24.44 | 0.00838 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
CORRIDORFLR2 | 2550.78 | 3060.93 | 0.212 | 0.255 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.13 | 0.00838 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
CORRIDORFLR3 | 1129.06 | 1354.87 | 0.094 | 0.113 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 24.90 | 0.00838 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 | |
CORRIDORFLR4 | 1899.93 | 2279.92 | 0.158 | 0.190 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 26.26 | 0.00838 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 0.00838 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1234.14 | 1480.97 | 0.035 | 0.236 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | -4.30 | 0.00266 |
RESTROOMFLR1 | 56.36 | 67.63 | 0.002 | 0.002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -4.30 | 0.00266 |
MEETINGROOMFLR1 | 418.53 | 502.24 | 0.012 | 0.126 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -4.30 | 0.00266 |
GUESTROOM101 | 174.73 | 209.67 | 0.005 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -4.30 | 0.00266 |
GUESTROOM102 | 215.37 | 258.45 | 0.006 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -4.30 | 0.00266 |
GUESTROOM103 | 341.46 | 409.75 | 0.010 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -4.30 | 0.00266 |
GUESTROOM104 | 328.73 | 394.47 | 0.009 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -4.30 | 0.00266 |
GUESTROOM105 | 215.38 | 258.45 | 0.006 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -4.30 | 0.00266 |
EMPLOYEELOUNGEFLR1 | 188.29 | 225.94 | 0.005 | 0.051 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30 | 0.00266 |
EXERCISECENTERFLR1 | 111.41 | 133.69 | 0.003 | 0.043 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -4.30 | 0.00266 |
FRONTOFFICEFLR1 | 764.20 | 917.04 | 0.022 | 0.056 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -4.30 | 0.00266 |
GUESTROOM201 | 341.83 | 410.20 | 0.010 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -4.30 | 0.00266 |
GUESTROOM202_205 | 721.45 | 865.73 | 0.021 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -4.30 | 0.00266 |
GUESTROOM206_208 | 550.37 | 660.44 | 0.016 | 0.043 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -4.30 | 0.00266 |
GUESTROOM209_212 | 641.03 | 769.24 | 0.018 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -4.30 | 0.00266 |
GUESTROOM213 | 344.35 | 413.22 | 0.010 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | -4.30 | 0.00266 |
GUESTROOM214 | 311.85 | 374.22 | 0.009 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -4.30 | 0.00266 |
GUESTROOM215_218 | 619.31 | 743.17 | 0.018 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -4.30 | 0.00266 |
GUESTROOM219 | 125.55 | 150.66 | 0.004 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -4.30 | 0.00266 |
GUESTROOM220_223 | 608.98 | 730.77 | 0.017 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -4.30 | 0.00266 |
GUESTROOM224 | 276.06 | 331.27 | 0.008 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | -4.30 | 0.00266 |
GUESTROOM301 | 375.29 | 450.34 | 0.011 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | -4.30 | 0.00266 |
GUESTROOM302_305 | 824.75 | 989.70 | 0.023 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -4.30 | 0.00266 |
GUESTROOM306_308 | 697.31 | 836.78 | 0.020 | 0.043 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | -4.30 | 0.00266 |
GUESTROOM309_312 | 814.30 | 977.16 | 0.023 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | -4.30 | 0.00266 |
GUESTROOM313 | 400.76 | 480.91 | 0.011 | 0.014 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:00:00 | -4.30 | 0.00266 |
GUESTROOM314 | 362.01 | 434.42 | 0.010 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 15:45:00 | -4.30 | 0.00266 |
GUESTROOM315_318 | 800.24 | 960.29 | 0.023 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30 | 0.00266 |
GUESTROOM319 | 208.16 | 249.79 | 0.006 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -4.30 | 0.00266 |
GUESTROOM320_323 | 771.50 | 925.80 | 0.022 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -4.30 | 0.00266 |
GUESTROOM324 | 333.53 | 400.24 | 0.010 | 0.013 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | -4.30 | 0.00266 |
GUESTROOM401 | 566.39 | 679.67 | 0.016 | 0.019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 22:45:00 | -4.30 | 0.00266 |
GUESTROOM402_405 | 1496.33 | 1795.59 | 0.043 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -4.30 | 0.00266 |
GUESTROOM406_408 | 1257.92 | 1509.51 | 0.036 | 0.043 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -4.30 | 0.00266 |
GUESTROOM409_412 | 1498.60 | 1798.32 | 0.043 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:00:00 | -4.30 | 0.00266 |
GUESTROOM413 | 623.10 | 747.72 | 0.018 | 0.021 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30 | 0.00266 |
GUESTROOM414 | 582.82 | 699.39 | 0.017 | 0.020 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -4.30 | 0.00266 |
GUESTROOM415_418 | 1487.43 | 1784.92 | 0.042 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -4.30 | 0.00266 |
GUESTROOM419 | 429.16 | 514.99 | 0.012 | 0.015 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -4.30 | 0.00266 |
GUESTROOM420_423 | 1455.11 | 1746.14 | 0.041 | 0.054 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -4.30 | 0.00266 |
GUESTROOM424 | 557.50 | 668.99 | 0.016 | 0.019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30 | 0.00266 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
CORRIDORFLR1 | 14261.68 | 17114.02 | 0.406 | 0.487 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -4.30 | 0.00266 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
CORRIDORFLR2 | 185.36 | 222.43 | 0.005 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -4.30 | 0.00266 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
CORRIDORFLR3 | 364.20 | 437.04 | 0.010 | 0.038 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -4.30 | 0.00266 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 | |
CORRIDORFLR4 | 1217.77 | 1461.32 | 0.035 | 0.042 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | -4.30 | 0.00266 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00266 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.32 | 0.32 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.69 | 0.69 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.33 | 0.33 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.70 | 0.70 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 167.50 | 7934.75 | 140.50 |
RESTROOMFLR1 | 1.75 | 8734.50 | 1.75 |
MEETINGROOMFLR1 | 152.25 | 3798.00 | 6.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 377.00 | 8760.00 | 377.00 |
GUESTROOM104 | 24.50 | 8760.00 | 24.50 |
GUESTROOM105 | 0.00 | 8670.00 | 0.00 |
EMPLOYEELOUNGEFLR1 | 2843.50 | 2298.25 | 217.50 |
EXERCISECENTERFLR1 | 530.75 | 3237.75 | 0.00 |
FRONTOFFICEFLR1 | 194.25 | 7408.75 | 8.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 134.00 | 8760.00 | 134.00 |
GUESTROOM206_208 | 92.50 | 8760.00 | 92.50 |
GUESTROOM209_212 | 66.25 | 8760.00 | 66.25 |
GUESTROOM213 | 480.75 | 8760.00 | 480.75 |
GUESTROOM214 | 11.25 | 8742.50 | 11.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3736.25 | 3756.00 | 18.00 |
GUESTROOM220_223 | 0.00 | 8611.25 | 0.00 |
GUESTROOM224 | 18.25 | 8731.75 | 18.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 166.00 | 8760.00 | 166.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 155.00 | 8753.25 | 155.00 |
GUESTROOM315_318 | 0.00 | 8486.75 | 0.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 16.50 | 8670.25 | 16.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2570.75 | 8488.75 | 2570.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 653.00 | 8356.75 | 653.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 422.00 | 7906.25 | 158.25 |
GUESTROOM419 | 191.50 | 8109.75 | 168.00 |
GUESTROOM420_423 | 443.00 | 7946.75 | 207.25 |
GUESTROOM424 | 697.25 | 8265.25 | 688.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6141.75 | 8760.00 | 4594.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 11.50 | 0.00 | 11.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 3.25 | 19.00 | 3.25 | 19.00 |
GUESTROOM104 | 0.25 | 32.50 | 0.25 | 32.50 |
GUESTROOM105 | 0.00 | 53.25 | 0.00 | 53.25 |
EMPLOYEELOUNGEFLR1 | 213.00 | 560.00 | 180.00 | 475.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.75 | 1.25 | 0.75 | 1.25 |
GUESTROOM206_208 | 0.50 | 15.75 | 0.50 | 15.75 |
GUESTROOM209_212 | 0.50 | 0.75 | 0.50 | 0.75 |
GUESTROOM213 | 4.75 | 0.75 | 4.75 | 0.75 |
GUESTROOM214 | 0.00 | 11.75 | 0.00 | 11.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2357.25 | 0.00 | 2357.25 |
GUESTROOM220_223 | 0.00 | 8.50 | 0.00 | 8.50 |
GUESTROOM224 | 0.00 | 12.25 | 0.00 | 12.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1.25 | 1.00 | 1.25 | 1.00 |
GUESTROOM313 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.75 | 9.75 | 0.75 | 9.75 |
GUESTROOM315_318 | 0.00 | 14.00 | 0.00 | 14.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 7.00 | 0.00 | 7.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 23.25 | 13.50 | 23.25 | 13.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 7.75 | 10.00 | 7.75 | 10.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2.50 | 21.75 | 2.50 | 21.75 |
GUESTROOM419 | 2.25 | 27.25 | 2.25 | 27.25 |
GUESTROOM420_423 | 2.75 | 21.00 | 2.75 | 21.00 |
GUESTROOM424 | 5.25 | 23.50 | 5.25 | 23.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.25 | 1855.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 1.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 239.00 | 3606.25 | 205.25 | 2836.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.320395 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.686859 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.696867 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 317.98 |
CORRIDORFLR1 PTAC HEATING COIL | 18536.28 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 888.84 |
102 PTAC HEATING COIL | 888.84 |
103 PTAC HEATING COIL | 888.84 |
104 PTAC HEATING COIL | 888.78 |
105 PTAC HEATING COIL | 888.78 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 317.91 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 317.98 |
CORRIDORFLR2 PTAC HEATING COIL | 2520.80 |
201 PTAC HEATING COIL | 888.84 |
202_205 PTAC HEATING COIL | 3555.37 |
206_208 PTAC HEATING COIL | 2817.75 |
209_212 PTAC HEATING COIL | 3555.37 |
213 PTAC HEATING COIL | 888.84 |
214 PTAC HEATING COIL | 888.78 |
215_218 PTAC HEATING COIL | 3555.11 |
219 PTAC HEATING COIL | 888.78 |
220_223 PTAC HEATING COIL | 3555.11 |
224 PTAC HEATING COIL | 888.78 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 317.91 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 317.98 |
CORRIDORFLR3 PTAC HEATING COIL | 2520.80 |
301 PTAC HEATING COIL | 888.84 |
302_305 PTAC HEATING COIL | 3555.37 |
306_308 PTAC HEATING COIL | 2817.75 |
309_312 PTAC HEATING COIL | 3555.37 |
313 PTAC HEATING COIL | 896.86 |
314 PTAC HEATING COIL | 888.78 |
315_318 PTAC HEATING COIL | 3555.11 |
319 PTAC HEATING COIL | 888.78 |
320_323 PTAC HEATING COIL | 3555.11 |
324 PTAC HEATING COIL | 888.78 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 317.91 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 317.98 |
CORRIDORFLR4 PTAC HEATING COIL | 2640.97 |
401 PTAC HEATING COIL | 1095.62 |
402_405 PTAC HEATING COIL | 3555.37 |
406_408 PTAC HEATING COIL | 2828.14 |
409_412 PTAC HEATING COIL | 3555.37 |
413 PTAC HEATING COIL | 1163.68 |
414 PTAC HEATING COIL | 1115.31 |
415_418 PTAC HEATING COIL | 3555.11 |
419 PTAC HEATING COIL | 930.91 |
420_423 PTAC HEATING COIL | 3555.11 |
424 PTAC HEATING COIL | 1084.92 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 317.91 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.796989 | 0.320395 | 5327.81 |
SAC_FRONTLOUNGE COOLING COIL | 0.759785 | 0.686859 | 12714.15 |
SAC_MEETINGROOM COOLING COIL | 0.730037 | 0.326903 | 6653.13 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.793531 | 0.696867 | 11698.67 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.686859 |
RESTROOMFLR1 DIRECT AIR | 0.035475 |
MEETINGROOMFLR1 DIRECT AIR | 0.326903 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.546548 |
EXERCISECENTERFLR1 DIRECT AIR | 0.114844 |
FRONTOFFICEFLR1 DIRECT AIR | 0.320395 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.320395 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.686859 |
SAC_MEETINGROOM MAIN BRANCH | 0.326903 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.696867 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.320395 |
SAC_FRONTLOUNGE | 0.686859 |
SAC_MEETINGROOM | 0.326903 |
SAC_EXC_EMPLGE_RESTRM | 0.696867 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.320395 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.686859 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.326903 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.696867 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.320395 | 0.320395 | 0.320395 | 0.320395 | 3659.85 | 5327.81 | 1.00 |
SAC_FRONTLOUNGE | 0.686859 | 0.686859 | 0.686859 | 0.686859 | 15340.21 | 12714.15 | 1.00 |
SAC_MEETINGROOM | 0.326903 | 0.326903 | 0.326903 | 0.326903 | 8214.57 | 6653.13 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.696867 | 0.696867 | 0.696867 | 0.696867 | 6202.29 | 11698.67 | 0.164801 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3659.85 |
SAC_FRONTLOUNGE HEATING COIL | 15340.21 |
SAC_MEETINGROOM HEATING COIL | 8214.57 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6202.29 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.326903 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.86 | 4.18 |
February | 19.72 | 4.25 |
March | 20.24 | 5.90 |
April | 21.32 | 8.96 |
May | 20.75 | 9.99 |
June | 21.69 | 13.31 |
July | 22.20 | 15.02 |
August | 22.42 | 15.65 |
September | 21.96 | 13.43 |
October | 20.77 | 9.33 |
November | 19.83 | 6.66 |
December | 18.87 | 4.10 |
Annual Sum or Average | 20.81 | 9.26 |
Minimum of Months | 18.87 | 4.10 |
Maximum of Months | 22.42 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.10 | 4.18 |
February | 23.15 | 4.25 |
March | 23.31 | 5.90 |
April | 23.65 | 8.96 |
May | 23.73 | 9.99 |
June | 24.25 | 13.31 |
July | 24.53 | 15.02 |
August | 24.61 | 15.65 |
September | 24.27 | 13.43 |
October | 23.60 | 9.33 |
November | 23.32 | 6.66 |
December | 23.04 | 4.10 |
Annual Sum or Average | 23.72 | 9.26 |
Minimum of Months | 23.04 | 4.10 |
Maximum of Months | 24.61 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.14 | 4.18 |
February | 19.00 | 4.25 |
March | 19.64 | 5.90 |
April | 20.54 | 8.96 |
May | 20.18 | 9.99 |
June | 21.17 | 13.31 |
July | 21.65 | 15.02 |
August | 21.76 | 15.65 |
September | 21.19 | 13.43 |
October | 20.07 | 9.33 |
November | 19.19 | 6.66 |
December | 18.32 | 4.10 |
Annual Sum or Average | 20.16 | 9.26 |
Minimum of Months | 18.32 | 4.10 |
Maximum of Months | 21.76 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | 4.18 |
February | 21.22 | 4.25 |
March | 21.31 | 5.90 |
April | 21.79 | 8.96 |
May | 21.93 | 9.99 |
June | 22.56 | 13.31 |
July | 22.91 | 15.02 |
August | 23.03 | 15.65 |
September | 22.57 | 13.43 |
October | 21.72 | 9.33 |
November | 21.34 | 6.66 |
December | 21.20 | 4.10 |
Annual Sum or Average | 21.90 | 9.26 |
Minimum of Months | 21.20 | 4.10 |
Maximum of Months | 23.03 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 4.18 |
February | 22.08 | 4.25 |
March | 22.27 | 5.90 |
April | 22.55 | 8.96 |
May | 22.70 | 9.99 |
June | 23.10 | 13.31 |
July | 23.26 | 15.02 |
August | 23.28 | 15.65 |
September | 23.00 | 13.43 |
October | 22.55 | 9.33 |
November | 22.28 | 6.66 |
December | 22.04 | 4.10 |
Annual Sum or Average | 22.60 | 9.26 |
Minimum of Months | 22.04 | 4.10 |
Maximum of Months | 23.28 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.57 | 4.18 |
February | 21.52 | 4.25 |
March | 21.76 | 5.90 |
April | 22.44 | 8.96 |
May | 22.59 | 9.99 |
June | 23.24 | 13.31 |
July | 23.47 | 15.02 |
August | 23.55 | 15.65 |
September | 23.27 | 13.43 |
October | 22.34 | 9.33 |
November | 21.74 | 6.66 |
December | 21.43 | 4.10 |
Annual Sum or Average | 22.41 | 9.26 |
Minimum of Months | 21.43 | 4.10 |
Maximum of Months | 23.55 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.27 | 4.18 |
February | 24.29 | 4.25 |
March | 24.54 | 5.90 |
April | 25.05 | 8.96 |
May | 25.22 | 9.99 |
June | 25.69 | 13.31 |
July | 25.88 | 15.02 |
August | 25.91 | 15.65 |
September | 25.63 | 13.43 |
October | 25.01 | 9.33 |
November | 24.56 | 6.66 |
December | 24.17 | 4.10 |
Annual Sum or Average | 25.02 | 9.26 |
Minimum of Months | 24.17 | 4.10 |
Maximum of Months | 25.91 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.77 | 4.18 |
February | 19.77 | 4.25 |
March | 20.19 | 5.90 |
April | 21.02 | 8.96 |
May | 21.29 | 9.99 |
June | 22.08 | 13.31 |
July | 22.44 | 15.02 |
August | 22.55 | 15.65 |
September | 22.02 | 13.43 |
October | 20.95 | 9.33 |
November | 20.25 | 6.66 |
December | 19.61 | 4.10 |
Annual Sum or Average | 21.00 | 9.26 |
Minimum of Months | 19.61 | 4.10 |
Maximum of Months | 22.55 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | 4.18 |
February | 19.46 | 4.25 |
March | 19.86 | 5.90 |
April | 20.69 | 8.96 |
May | 20.95 | 9.99 |
June | 21.76 | 13.31 |
July | 22.13 | 15.02 |
August | 22.24 | 15.65 |
September | 21.68 | 13.43 |
October | 20.61 | 9.33 |
November | 19.91 | 6.66 |
December | 19.30 | 4.10 |
Annual Sum or Average | 20.68 | 9.26 |
Minimum of Months | 19.30 | 4.10 |
Maximum of Months | 22.24 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 4.18 |
February | 20.90 | 4.25 |
March | 21.03 | 5.90 |
April | 21.29 | 8.96 |
May | 21.34 | 9.99 |
June | 21.55 | 13.31 |
July | 21.64 | 15.02 |
August | 21.68 | 15.65 |
September | 21.57 | 13.43 |
October | 21.25 | 9.33 |
November | 21.02 | 6.66 |
December | 20.83 | 4.10 |
Annual Sum or Average | 21.25 | 9.26 |
Minimum of Months | 20.83 | 4.10 |
Maximum of Months | 21.68 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 4.18 |
February | 21.22 | 4.25 |
March | 21.24 | 5.90 |
April | 21.53 | 8.96 |
May | 21.52 | 9.99 |
June | 21.65 | 13.31 |
July | 21.71 | 15.02 |
August | 21.73 | 15.65 |
September | 21.71 | 13.43 |
October | 21.50 | 9.33 |
November | 21.29 | 6.66 |
December | 21.10 | 4.10 |
Annual Sum or Average | 21.45 | 9.26 |
Minimum of Months | 21.10 | 4.10 |
Maximum of Months | 21.73 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 4.18 |
February | 21.56 | 4.25 |
March | 21.58 | 5.90 |
April | 21.70 | 8.96 |
May | 21.70 | 9.99 |
June | 21.74 | 13.31 |
July | 21.74 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.69 | 9.33 |
November | 21.61 | 6.66 |
December | 21.49 | 4.10 |
Annual Sum or Average | 21.65 | 9.26 |
Minimum of Months | 21.49 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.22 | 4.18 |
February | 22.17 | 4.25 |
March | 22.27 | 5.90 |
April | 22.14 | 8.96 |
May | 22.28 | 9.99 |
June | 22.43 | 13.31 |
July | 22.45 | 15.02 |
August | 22.46 | 15.65 |
September | 22.32 | 13.43 |
October | 22.33 | 9.33 |
November | 22.35 | 6.66 |
December | 22.29 | 4.10 |
Annual Sum or Average | 22.31 | 9.26 |
Minimum of Months | 22.14 | 4.10 |
Maximum of Months | 22.46 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.41 | 4.18 |
February | 51.44 | 4.25 |
March | 51.50 | 5.90 |
April | 52.03 | 8.96 |
May | 51.91 | 9.99 |
June | 52.23 | 13.31 |
July | 52.43 | 15.02 |
August | 52.56 | 15.65 |
September | 52.47 | 13.43 |
October | 51.90 | 9.33 |
November | 51.50 | 6.66 |
December | 51.14 | 4.10 |
Annual Sum or Average | 51.88 | 9.26 |
Minimum of Months | 51.14 | 4.10 |
Maximum of Months | 52.56 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.99 | 4.18 |
February | 68.94 | 4.25 |
March | 69.14 | 5.90 |
April | 69.57 | 8.96 |
May | 69.30 | 9.99 |
June | 69.70 | 13.31 |
July | 69.94 | 15.02 |
August | 70.09 | 15.65 |
September | 69.94 | 13.43 |
October | 69.42 | 9.33 |
November | 68.98 | 6.66 |
December | 68.58 | 4.10 |
Annual Sum or Average | 69.38 | 9.26 |
Minimum of Months | 68.58 | 4.10 |
Maximum of Months | 70.09 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 4.18 |
February | 22.98 | 4.25 |
March | 23.06 | 5.90 |
April | 23.23 | 8.96 |
May | 23.32 | 9.99 |
June | 23.57 | 13.31 |
July | 23.67 | 15.02 |
August | 23.72 | 15.65 |
September | 23.58 | 13.43 |
October | 23.30 | 9.33 |
November | 23.14 | 6.66 |
December | 22.94 | 4.10 |
Annual Sum or Average | 23.29 | 9.26 |
Minimum of Months | 22.94 | 4.10 |
Maximum of Months | 23.72 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.18 |
February | 22.30 | 4.25 |
March | 22.47 | 5.90 |
April | 23.01 | 8.96 |
May | 23.13 | 9.99 |
June | 23.55 | 13.31 |
July | 23.68 | 15.02 |
August | 23.76 | 15.65 |
September | 23.57 | 13.43 |
October | 23.05 | 9.33 |
November | 22.60 | 6.66 |
December | 22.05 | 4.10 |
Annual Sum or Average | 22.96 | 9.26 |
Minimum of Months | 22.05 | 4.10 |
Maximum of Months | 23.76 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.56 | 4.18 |
February | 19.35 | 4.25 |
March | 20.00 | 5.90 |
April | 21.28 | 8.96 |
May | 20.63 | 9.99 |
June | 21.70 | 13.31 |
July | 22.30 | 15.02 |
August | 22.66 | 15.65 |
September | 22.14 | 13.43 |
October | 20.69 | 9.33 |
November | 19.57 | 6.66 |
December | 18.49 | 4.10 |
Annual Sum or Average | 20.70 | 9.26 |
Minimum of Months | 18.49 | 4.10 |
Maximum of Months | 22.66 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 4.18 |
February | 21.09 | 4.25 |
March | 21.40 | 5.90 |
April | 22.33 | 8.96 |
May | 22.12 | 9.99 |
June | 22.77 | 13.31 |
July | 23.13 | 15.02 |
August | 23.34 | 15.65 |
September | 23.03 | 13.43 |
October | 22.04 | 9.33 |
November | 21.28 | 6.66 |
December | 20.55 | 4.10 |
Annual Sum or Average | 22.02 | 9.26 |
Minimum of Months | 20.55 | 4.10 |
Maximum of Months | 23.34 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.97 | 4.18 |
February | 19.78 | 4.25 |
March | 20.46 | 5.90 |
April | 21.75 | 8.96 |
May | 21.03 | 9.99 |
June | 22.15 | 13.31 |
July | 22.72 | 15.02 |
August | 22.96 | 15.65 |
September | 22.43 | 13.43 |
October | 21.02 | 9.33 |
November | 19.86 | 6.66 |
December | 18.66 | 4.10 |
Annual Sum or Average | 21.07 | 9.26 |
Minimum of Months | 18.66 | 4.10 |
Maximum of Months | 22.96 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.26 | 4.18 |
February | 22.29 | 4.25 |
March | 22.60 | 5.90 |
April | 23.39 | 8.96 |
May | 23.47 | 9.99 |
June | 23.82 | 13.31 |
July | 23.86 | 15.02 |
August | 23.88 | 15.65 |
September | 23.82 | 13.43 |
October | 23.26 | 9.33 |
November | 22.58 | 6.66 |
December | 21.97 | 4.10 |
Annual Sum or Average | 23.10 | 9.26 |
Minimum of Months | 21.97 | 4.10 |
Maximum of Months | 23.88 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.47 | 4.18 |
February | 18.29 | 4.25 |
March | 19.14 | 5.90 |
April | 20.36 | 8.96 |
May | 19.92 | 9.99 |
June | 21.22 | 13.31 |
July | 21.81 | 15.02 |
August | 21.95 | 15.65 |
September | 21.20 | 13.43 |
October | 19.66 | 9.33 |
November | 18.49 | 6.66 |
December | 17.39 | 4.10 |
Annual Sum or Average | 19.83 | 9.26 |
Minimum of Months | 17.39 | 4.10 |
Maximum of Months | 21.95 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.07 | 4.18 |
February | 19.00 | 4.25 |
March | 19.29 | 5.90 |
April | 20.51 | 8.96 |
May | 20.85 | 9.99 |
June | 22.06 | 13.31 |
July | 22.53 | 15.02 |
August | 22.69 | 15.65 |
September | 21.89 | 13.43 |
October | 20.09 | 9.33 |
November | 19.27 | 6.66 |
December | 18.92 | 4.10 |
Annual Sum or Average | 20.52 | 9.26 |
Minimum of Months | 18.92 | 4.10 |
Maximum of Months | 22.69 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | 4.18 |
February | 21.00 | 4.25 |
March | 21.12 | 5.90 |
April | 21.43 | 8.96 |
May | 21.51 | 9.99 |
June | 21.71 | 13.31 |
July | 21.74 | 15.02 |
August | 21.75 | 15.65 |
September | 21.71 | 13.43 |
October | 21.37 | 9.33 |
November | 21.12 | 6.66 |
December | 20.93 | 4.10 |
Annual Sum or Average | 21.37 | 9.26 |
Minimum of Months | 20.93 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.02 | 4.18 |
February | 21.06 | 4.25 |
March | 21.18 | 5.90 |
April | 21.47 | 8.96 |
May | 21.54 | 9.99 |
June | 21.72 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.72 | 13.43 |
October | 21.42 | 9.33 |
November | 21.17 | 6.66 |
December | 20.98 | 4.10 |
Annual Sum or Average | 21.40 | 9.26 |
Minimum of Months | 20.98 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 4.18 |
February | 21.09 | 4.25 |
March | 21.22 | 5.90 |
April | 21.50 | 8.96 |
May | 21.56 | 9.99 |
June | 21.72 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.73 | 13.43 |
October | 21.48 | 9.33 |
November | 21.22 | 6.66 |
December | 21.02 | 4.10 |
Annual Sum or Average | 21.42 | 9.26 |
Minimum of Months | 21.02 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.86 | 4.18 |
February | 20.88 | 4.25 |
March | 21.01 | 5.90 |
April | 21.33 | 8.96 |
May | 21.37 | 9.99 |
June | 21.62 | 13.31 |
July | 21.70 | 15.02 |
August | 21.73 | 15.65 |
September | 21.63 | 13.43 |
October | 21.25 | 9.33 |
November | 20.98 | 6.66 |
December | 20.78 | 4.10 |
Annual Sum or Average | 21.26 | 9.26 |
Minimum of Months | 20.78 | 4.10 |
Maximum of Months | 21.73 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 4.18 |
February | 21.33 | 4.25 |
March | 21.36 | 5.90 |
April | 21.64 | 8.96 |
May | 21.63 | 9.99 |
June | 21.72 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.59 | 9.33 |
November | 21.39 | 6.66 |
December | 21.17 | 4.10 |
Annual Sum or Average | 21.53 | 9.26 |
Minimum of Months | 21.17 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 4.18 |
February | 23.20 | 4.25 |
March | 23.25 | 5.90 |
April | 23.32 | 8.96 |
May | 23.33 | 9.99 |
June | 23.33 | 13.31 |
July | 23.33 | 15.02 |
August | 23.33 | 15.65 |
September | 23.33 | 13.43 |
October | 23.33 | 9.33 |
November | 23.26 | 6.66 |
December | 23.13 | 4.10 |
Annual Sum or Average | 23.28 | 9.26 |
Minimum of Months | 23.13 | 4.10 |
Maximum of Months | 23.33 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 31.45 | 4.18 |
February | 31.43 | 4.25 |
March | 31.65 | 5.90 |
April | 32.35 | 8.96 |
May | 32.20 | 9.99 |
June | 32.66 | 13.31 |
July | 32.86 | 15.02 |
August | 32.98 | 15.65 |
September | 32.80 | 13.43 |
October | 32.11 | 9.33 |
November | 31.52 | 6.66 |
December | 31.02 | 4.10 |
Annual Sum or Average | 32.09 | 9.26 |
Minimum of Months | 31.02 | 4.10 |
Maximum of Months | 32.98 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.88 | 4.18 |
February | 21.90 | 4.25 |
March | 21.93 | 5.90 |
April | 22.20 | 8.96 |
May | 22.21 | 9.99 |
June | 22.38 | 13.31 |
July | 22.47 | 15.02 |
August | 22.51 | 15.65 |
September | 22.44 | 13.43 |
October | 22.15 | 9.33 |
November | 21.94 | 6.66 |
December | 21.81 | 4.10 |
Annual Sum or Average | 22.15 | 9.26 |
Minimum of Months | 21.81 | 4.10 |
Maximum of Months | 22.51 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.37 | 4.18 |
February | 21.41 | 4.25 |
March | 21.42 | 5.90 |
April | 21.68 | 8.96 |
May | 21.68 | 9.99 |
June | 21.74 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.75 | 13.43 |
October | 21.65 | 9.33 |
November | 21.48 | 6.66 |
December | 21.28 | 4.10 |
Annual Sum or Average | 21.58 | 9.26 |
Minimum of Months | 21.28 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 4.18 |
February | 21.27 | 4.25 |
March | 21.30 | 5.90 |
April | 21.63 | 8.96 |
May | 21.63 | 9.99 |
June | 21.73 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.75 | 13.43 |
October | 21.58 | 9.33 |
November | 21.35 | 6.66 |
December | 21.12 | 4.10 |
Annual Sum or Average | 21.51 | 9.26 |
Minimum of Months | 21.12 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | 4.18 |
February | 20.55 | 4.25 |
March | 21.01 | 5.90 |
April | 22.29 | 8.96 |
May | 21.96 | 9.99 |
June | 22.80 | 13.31 |
July | 23.24 | 15.02 |
August | 23.50 | 15.65 |
September | 23.09 | 13.43 |
October | 21.77 | 9.33 |
November | 20.74 | 6.66 |
December | 19.77 | 4.10 |
Annual Sum or Average | 21.78 | 9.26 |
Minimum of Months | 19.77 | 4.10 |
Maximum of Months | 23.50 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.21 | 4.18 |
February | 18.93 | 4.25 |
March | 19.86 | 5.90 |
April | 21.58 | 8.96 |
May | 20.76 | 9.99 |
June | 22.12 | 13.31 |
July | 22.83 | 15.02 |
August | 23.23 | 15.65 |
September | 22.54 | 13.43 |
October | 20.66 | 9.33 |
November | 19.18 | 6.66 |
December | 17.76 | 4.10 |
Annual Sum or Average | 20.73 | 9.26 |
Minimum of Months | 17.76 | 4.10 |
Maximum of Months | 23.23 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.25 | 4.18 |
February | 19.07 | 4.25 |
March | 19.82 | 5.90 |
April | 21.40 | 8.96 |
May | 20.65 | 9.99 |
June | 21.99 | 13.31 |
July | 22.64 | 15.02 |
August | 22.89 | 15.65 |
September | 22.22 | 13.43 |
October | 20.49 | 9.33 |
November | 19.14 | 6.66 |
December | 17.86 | 4.10 |
Annual Sum or Average | 20.62 | 9.26 |
Minimum of Months | 17.86 | 4.10 |
Maximum of Months | 22.89 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.20 | 4.18 |
February | 21.16 | 4.25 |
March | 21.29 | 5.90 |
April | 22.31 | 8.96 |
May | 22.46 | 9.99 |
June | 23.26 | 13.31 |
July | 23.54 | 15.02 |
August | 23.65 | 15.65 |
September | 23.22 | 13.43 |
October | 21.93 | 9.33 |
November | 21.29 | 6.66 |
December | 21.11 | 4.10 |
Annual Sum or Average | 22.21 | 9.26 |
Minimum of Months | 21.11 | 4.10 |
Maximum of Months | 23.65 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.34 | 4.18 |
February | 17.17 | 4.25 |
March | 18.10 | 5.90 |
April | 19.67 | 8.96 |
May | 19.27 | 9.99 |
June | 20.92 | 13.31 |
July | 21.65 | 15.02 |
August | 21.81 | 15.65 |
September | 20.78 | 13.43 |
October | 18.74 | 9.33 |
November | 17.38 | 6.66 |
December | 16.21 | 4.10 |
Annual Sum or Average | 19.10 | 9.26 |
Minimum of Months | 16.21 | 4.10 |
Maximum of Months | 21.81 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.18 |
February | 18.89 | 4.25 |
March | 18.94 | 5.90 |
April | 19.90 | 8.96 |
May | 20.23 | 9.99 |
June | 21.63 | 13.31 |
July | 22.21 | 15.02 |
August | 22.39 | 15.65 |
September | 21.36 | 13.43 |
October | 19.35 | 9.33 |
November | 18.91 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.14 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 22.39 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | 4.18 |
February | 18.89 | 4.25 |
March | 18.99 | 5.90 |
April | 19.96 | 8.96 |
May | 20.40 | 9.99 |
June | 21.76 | 13.31 |
July | 22.30 | 15.02 |
August | 22.45 | 15.65 |
September | 21.43 | 13.43 |
October | 19.52 | 9.33 |
November | 18.97 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.21 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 22.45 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | 4.18 |
February | 18.90 | 4.25 |
March | 19.07 | 5.90 |
April | 20.13 | 8.96 |
May | 20.57 | 9.99 |
June | 21.85 | 13.31 |
July | 22.34 | 15.02 |
August | 22.46 | 15.65 |
September | 21.51 | 13.43 |
October | 19.69 | 9.33 |
November | 19.03 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.29 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 22.46 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 4.18 |
February | 20.99 | 4.25 |
March | 21.12 | 5.90 |
April | 21.43 | 8.96 |
May | 21.50 | 9.99 |
June | 21.69 | 13.31 |
July | 21.74 | 15.02 |
August | 21.74 | 15.65 |
September | 21.70 | 13.43 |
October | 21.37 | 9.33 |
November | 21.10 | 6.66 |
December | 20.90 | 4.10 |
Annual Sum or Average | 21.35 | 9.26 |
Minimum of Months | 20.90 | 4.10 |
Maximum of Months | 21.74 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | 4.18 |
February | 18.90 | 4.25 |
March | 19.08 | 5.90 |
April | 20.18 | 8.96 |
May | 20.45 | 9.99 |
June | 21.70 | 13.31 |
July | 22.21 | 15.02 |
August | 22.35 | 15.65 |
September | 21.46 | 13.43 |
October | 19.71 | 9.33 |
November | 19.04 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.25 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 22.35 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 4.18 |
February | 21.12 | 4.25 |
March | 21.15 | 5.90 |
April | 21.52 | 8.96 |
May | 21.51 | 9.99 |
June | 21.68 | 13.31 |
July | 21.73 | 15.02 |
August | 21.74 | 15.65 |
September | 21.72 | 13.43 |
October | 21.44 | 9.33 |
November | 21.18 | 6.66 |
December | 20.95 | 4.10 |
Annual Sum or Average | 21.40 | 9.26 |
Minimum of Months | 20.95 | 4.10 |
Maximum of Months | 21.74 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.41 | 4.18 |
February | 21.47 | 4.25 |
March | 21.47 | 5.90 |
April | 21.70 | 8.96 |
May | 21.70 | 9.99 |
June | 21.74 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.75 | 13.43 |
October | 21.67 | 9.33 |
November | 21.52 | 6.66 |
December | 21.33 | 4.10 |
Annual Sum or Average | 21.61 | 9.26 |
Minimum of Months | 21.33 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 4.18 |
February | 23.29 | 4.25 |
March | 23.53 | 5.90 |
April | 24.58 | 8.96 |
May | 24.50 | 9.99 |
June | 25.17 | 13.31 |
July | 25.45 | 15.02 |
August | 25.57 | 15.65 |
September | 25.24 | 13.43 |
October | 24.16 | 9.33 |
November | 23.40 | 6.66 |
December | 22.79 | 4.10 |
Annual Sum or Average | 24.25 | 9.26 |
Minimum of Months | 22.79 | 4.10 |
Maximum of Months | 25.57 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 4.18 |
February | 21.54 | 4.25 |
March | 21.75 | 5.90 |
April | 22.76 | 8.96 |
May | 22.84 | 9.99 |
June | 23.23 | 13.31 |
July | 23.29 | 15.02 |
August | 23.32 | 15.65 |
September | 23.23 | 13.43 |
October | 22.59 | 9.33 |
November | 21.84 | 6.66 |
December | 21.05 | 4.10 |
Annual Sum or Average | 22.41 | 9.26 |
Minimum of Months | 21.05 | 4.10 |
Maximum of Months | 23.32 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | 4.18 |
February | 21.28 | 4.25 |
March | 21.28 | 5.90 |
April | 21.62 | 8.96 |
May | 21.62 | 9.99 |
June | 21.72 | 13.31 |
July | 21.74 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.56 | 9.33 |
November | 21.35 | 6.66 |
December | 21.13 | 4.10 |
Annual Sum or Average | 21.50 | 9.26 |
Minimum of Months | 21.13 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | 4.18 |
February | 19.64 | 4.25 |
March | 19.90 | 5.90 |
April | 21.41 | 8.96 |
May | 21.45 | 9.99 |
June | 22.30 | 13.31 |
July | 22.67 | 15.02 |
August | 22.86 | 15.65 |
September | 22.47 | 13.43 |
October | 21.04 | 9.33 |
November | 19.98 | 6.66 |
December | 19.16 | 4.10 |
Annual Sum or Average | 21.05 | 9.26 |
Minimum of Months | 19.16 | 4.10 |
Maximum of Months | 22.86 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.62 | 4.18 |
February | 19.56 | 4.25 |
March | 20.14 | 5.90 |
April | 21.84 | 8.96 |
May | 21.50 | 9.99 |
June | 22.61 | 13.31 |
July | 23.17 | 15.02 |
August | 23.45 | 15.65 |
September | 22.85 | 13.43 |
October | 21.09 | 9.33 |
November | 19.79 | 6.66 |
December | 18.64 | 4.10 |
Annual Sum or Average | 21.20 | 9.26 |
Minimum of Months | 18.64 | 4.10 |
Maximum of Months | 23.45 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.38 | 4.18 |
February | 18.10 | 4.25 |
March | 19.16 | 5.90 |
April | 21.23 | 8.96 |
May | 20.38 | 9.99 |
June | 21.98 | 13.31 |
July | 22.79 | 15.02 |
August | 23.21 | 15.65 |
September | 22.34 | 13.43 |
October | 20.08 | 9.33 |
November | 18.37 | 6.66 |
December | 16.80 | 4.10 |
Annual Sum or Average | 20.25 | 9.26 |
Minimum of Months | 16.80 | 4.10 |
Maximum of Months | 23.21 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.81 | 4.18 |
February | 17.74 | 4.25 |
March | 18.59 | 5.90 |
April | 20.73 | 8.96 |
May | 20.07 | 9.99 |
June | 21.72 | 13.31 |
July | 22.52 | 15.02 |
August | 22.70 | 15.65 |
September | 21.74 | 13.43 |
October | 19.45 | 9.33 |
November | 17.86 | 6.66 |
December | 16.45 | 4.10 |
Annual Sum or Average | 19.79 | 9.26 |
Minimum of Months | 16.45 | 4.10 |
Maximum of Months | 22.70 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.14 | 4.18 |
February | 21.14 | 4.25 |
March | 21.18 | 5.90 |
April | 21.99 | 8.96 |
May | 22.08 | 9.99 |
June | 22.74 | 13.31 |
July | 23.02 | 15.02 |
August | 23.06 | 15.65 |
September | 22.55 | 13.43 |
October | 21.50 | 9.33 |
November | 21.15 | 6.66 |
December | 21.11 | 4.10 |
Annual Sum or Average | 21.89 | 9.26 |
Minimum of Months | 21.11 | 4.10 |
Maximum of Months | 23.06 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.31 | 4.18 |
February | 16.23 | 4.25 |
March | 17.21 | 5.90 |
April | 19.19 | 8.96 |
May | 18.86 | 9.99 |
June | 20.72 | 13.31 |
July | 21.56 | 15.02 |
August | 21.63 | 15.65 |
September | 20.35 | 13.43 |
October | 17.93 | 9.33 |
November | 16.46 | 6.66 |
December | 15.22 | 4.10 |
Annual Sum or Average | 18.48 | 9.26 |
Minimum of Months | 15.22 | 4.10 |
Maximum of Months | 21.63 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | 4.18 |
February | 20.58 | 4.25 |
March | 20.72 | 5.90 |
April | 21.33 | 8.96 |
May | 21.40 | 9.99 |
June | 21.65 | 13.31 |
July | 21.73 | 15.02 |
August | 21.73 | 15.65 |
September | 21.64 | 13.43 |
October | 21.02 | 9.33 |
November | 20.65 | 6.66 |
December | 20.50 | 4.10 |
Annual Sum or Average | 21.13 | 9.26 |
Minimum of Months | 20.50 | 4.10 |
Maximum of Months | 21.73 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.18 |
February | 18.89 | 4.25 |
March | 18.94 | 5.90 |
April | 19.87 | 8.96 |
May | 20.13 | 9.99 |
June | 21.38 | 13.31 |
July | 21.90 | 15.02 |
August | 21.96 | 15.65 |
September | 20.89 | 13.43 |
October | 19.25 | 9.33 |
November | 18.90 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.00 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 21.96 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.18 |
February | 18.89 | 4.25 |
March | 18.97 | 5.90 |
April | 19.94 | 8.96 |
May | 20.22 | 9.99 |
June | 21.43 | 13.31 |
July | 21.92 | 15.02 |
August | 21.96 | 15.65 |
September | 20.92 | 13.43 |
October | 19.30 | 9.33 |
November | 18.91 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.03 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 21.96 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.83 | 4.18 |
February | 20.89 | 4.25 |
March | 21.07 | 5.90 |
April | 21.53 | 8.96 |
May | 21.59 | 9.99 |
June | 21.72 | 13.31 |
July | 21.74 | 15.02 |
August | 21.74 | 15.65 |
September | 21.71 | 13.43 |
October | 21.34 | 9.33 |
November | 20.99 | 6.66 |
December | 20.72 | 4.10 |
Annual Sum or Average | 21.33 | 9.26 |
Minimum of Months | 20.72 | 4.10 |
Maximum of Months | 21.74 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.18 |
February | 18.89 | 4.25 |
March | 18.98 | 5.90 |
April | 20.00 | 8.96 |
May | 20.20 | 9.99 |
June | 21.42 | 13.31 |
July | 21.93 | 15.02 |
August | 22.02 | 15.65 |
September | 21.03 | 13.43 |
October | 19.34 | 9.33 |
November | 18.92 | 6.66 |
December | 18.89 | 4.10 |
Annual Sum or Average | 20.05 | 9.26 |
Minimum of Months | 18.89 | 4.10 |
Maximum of Months | 22.02 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.17 | 4.18 |
February | 19.24 | 4.25 |
March | 19.36 | 5.90 |
April | 20.79 | 8.96 |
May | 20.84 | 9.99 |
June | 21.83 | 13.31 |
July | 22.22 | 15.02 |
August | 22.33 | 15.65 |
September | 21.75 | 13.43 |
October | 20.14 | 9.33 |
November | 19.29 | 6.66 |
December | 18.97 | 4.10 |
Annual Sum or Average | 20.50 | 9.26 |
Minimum of Months | 18.97 | 4.10 |
Maximum of Months | 22.33 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 4.18 |
February | 21.30 | 4.25 |
March | 21.31 | 5.90 |
April | 21.66 | 8.96 |
May | 21.67 | 9.99 |
June | 21.73 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.55 | 9.33 |
November | 21.33 | 6.66 |
December | 21.06 | 4.10 |
Annual Sum or Average | 21.51 | 9.26 |
Minimum of Months | 21.06 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | 4.18 |
February | 20.91 | 4.25 |
March | 21.22 | 5.90 |
April | 22.53 | 8.96 |
May | 22.49 | 9.99 |
June | 23.30 | 13.31 |
July | 23.65 | 15.02 |
August | 23.70 | 15.65 |
September | 23.16 | 13.43 |
October | 21.83 | 9.33 |
November | 21.01 | 6.66 |
December | 20.34 | 4.10 |
Annual Sum or Average | 22.08 | 9.26 |
Minimum of Months | 20.34 | 4.10 |
Maximum of Months | 23.70 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | 4.18 |
February | 21.27 | 4.25 |
March | 21.29 | 5.90 |
April | 21.66 | 8.96 |
May | 21.67 | 9.99 |
June | 21.74 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.54 | 9.33 |
November | 21.31 | 6.66 |
December | 21.04 | 4.10 |
Annual Sum or Average | 21.49 | 9.26 |
Minimum of Months | 21.04 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | 4.18 |
February | 21.26 | 4.25 |
March | 21.27 | 5.90 |
April | 21.65 | 8.96 |
May | 21.66 | 9.99 |
June | 21.73 | 13.31 |
July | 21.75 | 15.02 |
August | 21.75 | 15.65 |
September | 21.74 | 13.43 |
October | 21.53 | 9.33 |
November | 21.29 | 6.66 |
December | 21.01 | 4.10 |
Annual Sum or Average | 21.48 | 9.26 |
Minimum of Months | 21.01 | 4.10 |
Maximum of Months | 21.75 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 4.18 |
February | 21.03 | 4.25 |
March | 21.07 | 5.90 |
April | 21.58 | 8.96 |
May | 21.58 | 9.99 |
June | 21.71 | 13.31 |
July | 21.74 | 15.02 |
August | 21.74 | 15.65 |
September | 21.73 | 13.43 |
October | 21.41 | 9.33 |
November | 21.09 | 6.66 |
December | 20.78 | 4.10 |
Annual Sum or Average | 21.37 | 9.26 |
Minimum of Months | 20.78 | 4.10 |
Maximum of Months | 21.74 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.18 |
February | 18.94 | 4.25 |
March | 19.59 | 5.90 |
April | 21.55 | 8.96 |
May | 21.28 | 9.99 |
June | 22.49 | 13.31 |
July | 23.08 | 15.02 |
August | 23.25 | 15.65 |
September | 22.47 | 13.43 |
October | 20.51 | 9.33 |
November | 19.15 | 6.66 |
December | 17.98 | 4.10 |
Annual Sum or Average | 20.77 | 9.26 |
Minimum of Months | 17.98 | 4.10 |
Maximum of Months | 23.25 | 15.65 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.39 | 4.18 |
February | 17.22 | 4.25 |
March | 18.37 | 5.90 |
April | 20.82 | 8.96 |
May | 20.03 | 9.99 |
June | 21.81 | 13.31 |
July | 22.69 | 15.02 |
August | 23.01 | 15.65 |
September | 21.91 | 13.43 |
October | 19.35 | 9.33 |
November | 17.50 | 6.66 |
December | 15.85 | 4.10 |
Annual Sum or Average | 19.67 | 9.26 |
Minimum of Months | 15.85 | 4.10 |
Maximum of Months | 23.01 | 15.65 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.141946E+12 | 106819.842 | 10-JAN-07:15 | 15177.258 | 39465.561 | 8609.220 | 39136.722 | 234.967 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.125634E+12 | 99288.022 | 17-FEB-07:15 | 13316.689 | 34010.661 | 8609.220 | 38932.197 | 223.143 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.132347E+12 | 89937.494 | 16-MAR-06:15 | 15177.258 | 39465.561 | 8609.220 | 21585.868 | 903.474 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.126034E+12 | 82723.475 | 09-APR-06:15 | 15177.258 | 39465.561 | 8609.220 | 17690.563 | 1772.760 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.128927E+12 | 80177.056 | 27-MAY-07:00 | 17492.219 | 43276.576 | 8975.387 | 0.000 | 10424.761 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.129552E+12 | 83084.316 | 23-JUN-07:00 | 17492.219 | 43276.576 | 8975.387 | 0.000 | 13332.022 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.137759E+12 | 89255.074 | 22-JUL-07:00 | 17566.637 | 43276.576 | 8975.387 | 0.000 | 19428.363 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.139157E+12 | 85589.241 | 18-AUG-07:00 | 17641.054 | 43276.576 | 8975.387 | 0.000 | 15688.112 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.131157E+12 | 83682.925 | 16-SEP-07:00 | 17641.054 | 43276.576 | 8975.387 | 0.000 | 13781.796 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.130547E+12 | 85004.631 | 15-OCT-06:30 | 15177.258 | 39465.561 | 8609.220 | 14864.064 | 2692.414 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.130654E+12 | 97050.507 | 29-NOV-07:15 | 15177.258 | 39465.561 | 8609.220 | 29089.918 | 512.437 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.144353E+12 | 98938.186 | 27-DEC-07:15 | 15177.258 | 39465.561 | 8609.220 | 30989.613 | 500.421 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.159807E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.125634E+12 | 80177.056 | 13316.689 | 34010.661 | 8609.220 | 0.000 | 223.143 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.144353E+12 | 106819.842 | 17641.054 | 43276.576 | 8975.387 | 39136.722 | 19428.363 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.104435E+12 | 105771.159 | 12-JAN-10:15 | 8765.177 | 40096.028 | 0.000 | 56909.954 | 56909.954 | 56909.954 | 8765.177 |
February | 0.942773E+11 | 101844.243 | 19-FEB-11:45 | 4688.824 | 40096.028 | 0.000 | 57059.391 | 57059.391 | 57059.391 | 4688.824 |
March | 0.101062E+12 | 99882.964 | 04-MAR-10:15 | 2199.613 | 40096.028 | 0.000 | 57587.323 | 57587.323 | 57587.323 | 2199.613 |
April | 0.933001E+11 | 98304.148 | 08-APR-08:15 | 34.904 | 40096.028 | 0.000 | 58173.216 | 58173.216 | 58173.216 | 34.904 |
May | 0.939112E+11 | 97268.897 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 57172.869 | 57172.869 | 57172.869 | 0.000 |
June | 0.875864E+11 | 96273.177 | 09-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 56177.149 | 56177.149 | 56177.149 | 0.000 |
July | 0.888779E+11 | 94304.543 | 01-JUL-08:45 | 0.000 | 40096.028 | 0.000 | 54208.515 | 54208.515 | 54208.515 | 0.000 |
August | 0.882739E+11 | 93698.828 | 11-AUG-08:30 | 0.000 | 40096.028 | 0.000 | 53602.800 | 53602.800 | 53602.800 | 0.000 |
September | 0.864956E+11 | 94290.807 | 30-SEP-08:45 | 0.000 | 40096.028 | 0.000 | 54194.779 | 54194.779 | 54194.779 | 0.000 |
October | 0.929437E+11 | 95935.966 | 27-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 55839.938 | 55839.938 | 55839.938 | 0.000 |
November | 0.946745E+11 | 98326.283 | 12-NOV-10:00 | 3100.861 | 40096.028 | 0.000 | 55129.394 | 55129.394 | 55129.394 | 3100.861 |
December | 0.103759E+12 | 103606.458 | 29-DEC-10:15 | 6441.363 | 40096.028 | 0.000 | 57069.067 | 57069.067 | 57069.067 | 6441.363 |
Annual Sum or Average | 0.112960E+13 | 0.000 | ||||||||
Minimum of Months | 0.864956E+11 | 93698.828 | 0.000 | 40096.028 | 0.000 | 53602.800 | 53602.800 | 53602.800 | 0.000 | |
Maximum of Months | 0.104435E+12 | 105771.159 | 8765.177 | 40096.028 | 0.000 | 58173.216 | 58173.216 | 58173.216 | 8765.177 |