Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280

Simulation Timestamp: 2018-10-19 10:15:38


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3024.41 753.54 811.90
Net Site Energy 3024.41 753.54 811.90
Total Source Energy 7097.32 1768.33 1905.27
Net Source Energy 7097.32 1768.33 1905.27


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 285.41 115.37 0.00 0.00 0.00 0.00
Cooling 198.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting 414.32 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.72 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 278.25 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 654.20 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1833.35 1191.07 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 285.41 115.37 0.00 0.00 0.00 0.00
Cooling General 198.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 414.32 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.72 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 278.25 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 654.20 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.87 0.00 0.00 0.00 0.00 0.00
HVAC 204.64 206.59 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 492.16 319.74 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.60 0.00 0.00 0.00 0.00 0.00
HVAC 189.93 191.74 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 456.79 296.76 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1833.35 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1833.35 100.00
     
Total On-Site and Utility Electric Sources 1833.35 100.00
Total Electricity End Uses 1833.35 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 876.25
Time Setpoint Not Met During Occupied Cooling 2876.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 6095.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Weather File Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Latitude [deg] 42.93
Longitude [deg] -78.7
Elevation [m] 215.00
Time Zone -5.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -16.30 0.00 -16.30 Wetbulb [C] 5.10 270.00
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 30.30 9.30 21.80 Wetbulb [C] 5.70 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           96.82 2.653 0.426 0.308              
Non-North Total or Average           87.38 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   6478.81 4698.19 1780.62 0.73 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   17844.66 12213.65 5631.01 0.68 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8723.76 5897.99 2825.77 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   13769.51 10180.16 3589.35 0.74 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6235.6 3.28 11.21 11.88 11.21
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 17267.1 3.36 11.47 12.16 11.61
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8450.7 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13227.9 3.26 11.12 11.78 11.07
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   313.33 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   29222.05 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1069.38 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1069.38 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1345.46 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1341.39 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1069.30 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   313.25 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   313.33 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   3032.81 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1214.73 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4277.51 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3390.07 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4277.51 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1393.66 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1358.03 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4277.21 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1069.30 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4277.21 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1206.97 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   485.25 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   313.33 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3202.87 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1265.81 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4277.51 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3390.07 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   4277.51 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1500.42 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1453.15 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4277.21 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1069.30 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4277.21 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1292.21 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   485.25 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   485.36 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   4613.26 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1574.27 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   4960.08 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   4064.36 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   4982.55 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1859.81 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1804.55 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   4964.47 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1373.32 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   4909.30 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1634.58 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   557.04 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4403.22 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   18456.02 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   9883.06 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   7533.00 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.70 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.31 350.76 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.74 822.75 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 393.50 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.70 781.37 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7321.96 8786.35 0.619 0.743 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.30 0.01335
RESTROOMFLR1 409.76 491.71 0.035 0.042 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 29.56 0.01335
MEETINGROOMFLR1 3459.27 4151.12 0.293 0.351 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.30 0.01335
GUESTROOM101 527.10 632.52 0.062 0.074 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.88 0.01335
GUESTROOM102 428.11 513.73 0.050 0.060 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.88 0.01335
GUESTROOM103 992.25 1190.70 0.117 0.140 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 27.02 0.01335
GUESTROOM104 1148.93 1378.71 0.135 0.162 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM105 1518.44 1822.13 0.178 0.214 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
EMPLOYEELOUNGEFLR1 5325.43 6390.52 0.450 0.541 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
EXERCISECENTERFLR1 1138.40 1366.08 0.096 0.115 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 29.00 0.01335
FRONTOFFICEFLR1 3088.04 3705.64 0.261 0.313 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM201 778.55 934.26 0.091 0.110 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:15:00 29.95 0.01335
GUESTROOM202_205 4022.16 4826.59 0.473 0.567 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.88 0.01335
GUESTROOM206_208 3258.04 3909.65 0.383 0.459 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.88 0.01335
GUESTROOM209_212 3835.81 4602.97 0.451 0.541 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.88 0.01335
GUESTROOM213 1075.01 1290.01 0.126 0.152 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 26.67 0.01335
GUESTROOM214 1291.90 1550.28 0.152 0.182 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM215_218 9495.66 11394.79 1.116 1.339 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM219 5385.59 6462.71 0.633 0.759 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM220_223 4549.15 5458.98 0.535 0.641 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM224 1290.76 1548.91 0.152 0.182 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM301 603.37 724.05 0.071 0.085 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30 0.01335
GUESTROOM302_305 1477.35 1772.82 0.174 0.208 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.74 0.01335
GUESTROOM306_308 1292.32 1550.79 0.152 0.182 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.74 0.01335
GUESTROOM309_312 3810.64 4572.77 0.448 0.537 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.74 0.01335
GUESTROOM313 579.26 695.11 0.068 0.082 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 27.02 0.01335
GUESTROOM314 1212.37 1454.85 0.142 0.171 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.30 0.01335
GUESTROOM315_318 4961.22 5953.46 0.583 0.700 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM319 1098.94 1318.72 0.129 0.155 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM320_323 4352.28 5222.74 0.511 0.614 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM324 720.94 865.12 0.085 0.102 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM401 1440.04 1728.05 0.169 0.203 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 30.18 0.01335
GUESTROOM402_405 2253.90 2704.68 0.265 0.318 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM406_408 1926.83 2312.20 0.226 0.272 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.30 0.01335
GUESTROOM409_412 4899.03 5878.84 0.576 0.691 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM413 830.92 997.10 0.098 0.117 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 30.16 0.01335
GUESTROOM414 1006.66 1207.99 0.118 0.142 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
GUESTROOM415_418 5663.12 6795.74 0.665 0.799 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30 0.01335
GUESTROOM419 1550.62 1860.74 0.182 0.219 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.30 0.01335
GUESTROOM420_423 5627.54 6753.04 0.661 0.794 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.30 0.01335
GUESTROOM424 1565.48 1878.58 0.184 0.221 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.30 0.01335
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
CORRIDORFLR1 13930.28 16716.34 1.177 1.413 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.07 0.01335
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
CORRIDORFLR2 2608.94 3130.73 0.220 0.264 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 29.00 0.01335
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
CORRIDORFLR3 1228.76 1474.51 0.104 0.125 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 28.77 0.01335
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335
CORRIDORFLR4 2115.04 2538.05 0.179 0.214 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 30.16 0.01335
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB   30.30 0.01335


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1845.71 2214.85 0.053 0.236 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -16.30 0.00092
RESTROOMFLR1 127.79 153.35 0.004 0.004 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -16.30 0.00092
MEETINGROOMFLR1 656.41 787.69 0.019 0.126 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -16.30 0.00092
GUESTROOM101 277.29 332.75 0.008 0.013 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -16.30 0.00092
GUESTROOM102 327.21 392.65 0.009 0.013 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -16.30 0.00092
GUESTROOM103 618.37 742.05 0.018 0.021 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -16.30 0.00092
GUESTROOM104 615.01 738.02 0.018 0.021 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30 0.00092
GUESTROOM105 329.63 395.56 0.010 0.013 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -16.30 0.00092
EMPLOYEELOUNGEFLR1 303.99 364.79 0.009 0.051 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -16.30 0.00092
EXERCISECENTERFLR1 208.42 250.11 0.006 0.043 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -16.30 0.00092
FRONTOFFICEFLR1 1218.00 1461.60 0.035 0.056 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -16.30 0.00092
GUESTROOM201 509.43 611.31 0.015 0.018 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -16.30 0.00092
GUESTROOM202_205 1084.91 1301.89 0.031 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -16.30 0.00092
GUESTROOM206_208 859.06 1030.87 0.025 0.043 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -16.30 0.00092
GUESTROOM209_212 1007.46 1208.95 0.029 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -16.30 0.00092
GUESTROOM213 658.54 790.24 0.019 0.023 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -16.30 0.00092
GUESTROOM214 628.88 754.66 0.018 0.022 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -16.30 0.00092
GUESTROOM215_218 1012.13 1214.56 0.029 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -16.30 0.00092
GUESTROOM219 261.01 313.21 0.008 0.013 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -16.30 0.00092
GUESTROOM220_223 969.30 1163.15 0.028 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -16.30 0.00092
GUESTROOM224 502.99 603.59 0.015 0.017 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -16.30 0.00092
GUESTROOM301 552.00 662.40 0.016 0.019 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -16.30 0.00092
GUESTROOM302_305 1214.46 1457.36 0.035 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -16.30 0.00092
GUESTROOM306_308 1038.98 1246.77 0.030 0.043 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -16.30 0.00092
GUESTROOM309_312 1220.59 1464.71 0.035 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -16.30 0.00092
GUESTROOM313 747.50 897.00 0.022 0.026 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -16.30 0.00092
GUESTROOM314 708.14 849.77 0.020 0.025 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 14:30:00 -16.30 0.00092
GUESTROOM315_318 1207.95 1449.54 0.035 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -16.30 0.00092
GUESTROOM319 348.90 418.69 0.010 0.013 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -16.30 0.00092
GUESTROOM320_323 1163.03 1395.63 0.034 0.054 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -16.30 0.00092
GUESTROOM324 574.03 688.84 0.017 0.020 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -16.30 0.00092
GUESTROOM401 809.05 970.86 0.023 0.028 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 21:45:00 -16.30 0.00092
GUESTROOM402_405 2122.01 2546.42 0.061 0.074 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 21:00:00 -16.30 0.00092
GUESTROOM406_408 1792.87 2151.45 0.052 0.062 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -16.30 0.00092
GUESTROOM409_412 2140.74 2568.88 0.062 0.074 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -16.30 0.00092
GUESTROOM413 1046.99 1256.39 0.030 0.036 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -16.30 0.00092
GUESTROOM414 1000.98 1201.18 0.029 0.035 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -16.30 0.00092
GUESTROOM415_418 2125.81 2550.98 0.061 0.074 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -16.30 0.00092
GUESTROOM419 641.62 769.94 0.019 0.022 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 18:00:00 -16.30 0.00092
GUESTROOM420_423 2079.84 2495.81 0.060 0.072 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -16.30 0.00092
GUESTROOM424 859.34 1031.21 0.025 0.030 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 22:00:00 -16.30 0.00092
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB   -16.30 0.00092
CORRIDORFLR1 22626.39 27151.67 0.653 0.784 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -16.30 0.00092
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB   -16.30 0.00092
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB   -16.30 0.00092
CORRIDORFLR2 971.31 1165.57 0.028 0.038 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -16.30 0.00092
FRONTSTAIRSFLR2 17.23 20.67 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB   -16.30 0.00092
CORRIDORFLR3 1243.01 1491.61 0.036 0.043 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092
FRONTSTAIRSFLR3 151.43 181.72 0.003 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092
REARSTAIRSFLR4 26.25 31.50 0.001 0.006 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092
CORRIDORFLR4 2418.35 2902.02 0.070 0.084 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092
FRONTSTAIRSFLR4 320.91 385.10 0.006 0.008 BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -16.30 0.00092


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.31 0.31 0.06 0.06
SAC_FRONTLOUNGE 0.74 0.74 0.24 0.24
SAC_MEETINGROOM 0.35 0.35 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.70 0.70 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 0.74 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 2719.00 7617.25 2267.25
RESTROOMFLR1 1109.75 7935.00 972.75
MEETINGROOMFLR1 928.25 3601.00 477.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 2569.25 8759.75 2569.25
GUESTROOM104 1721.75 8731.75 1721.75
GUESTROOM105 138.50 8476.50 138.50
EMPLOYEELOUNGEFLR1 2815.75 2374.50 369.25
EXERCISECENTERFLR1 1092.00 3316.25 73.75
FRONTOFFICEFLR1 1530.75 6742.25 950.25
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 1577.50 8531.00 1576.00
GUESTROOM206_208 1412.50 8533.00 1411.00
GUESTROOM209_212 1267.75 8662.25 1267.75
GUESTROOM213 2684.25 8716.50 2684.25
GUESTROOM214 1444.50 8554.25 1444.50
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 3300.25 4491.25 231.50
GUESTROOM220_223 423.50 8407.75 410.75
GUESTROOM224 1461.00 8517.00 1461.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 1758.25 8672.25 1758.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 2227.75 8559.50 2227.75
GUESTROOM315_318 427.75 8284.00 389.00
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 948.25 8511.50 940.25
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 3895.25 8202.00 3734.50
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 2749.25 8083.25 2526.00
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2175.25 7845.00 1752.25
GUESTROOM419 2107.00 7980.00 1904.25
GUESTROOM420_423 2274.25 7869.50 1874.00
GUESTROOM424 2973.75 8092.50 2798.75
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7258.75 8760.00 6095.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 633.50 406.25 633.50 406.25
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 1.50 0.00 0.00 0.00
GUESTROOM103 23.75 29.00 23.75 29.00
GUESTROOM104 13.50 33.50 13.50 33.50
GUESTROOM105 0.00 43.25 0.00 43.25
EMPLOYEELOUNGEFLR1 623.25 1098.25 452.75 644.25
EXERCISECENTERFLR1 0.25 0.00 0.00 0.00
FRONTOFFICEFLR1 0.25 0.00 0.25 0.00
GUESTROOM201 0.25 0.00 0.00 0.00
GUESTROOM202_205 18.25 16.75 18.25 16.75
GUESTROOM206_208 16.50 23.25 16.50 23.25
GUESTROOM209_212 16.50 16.25 16.50 16.25
GUESTROOM213 26.50 16.50 26.50 16.50
GUESTROOM214 12.50 21.25 12.50 21.25
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2123.25 0.00 2123.25
GUESTROOM220_223 4.25 19.50 4.25 19.50
GUESTROOM224 13.25 21.25 13.25 21.25
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.25 0.00 0.00 0.00
GUESTROOM306_308 0.50 0.00 0.00 0.00
GUESTROOM309_312 21.50 16.50 21.50 16.50
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 20.00 20.25 20.00 20.25
GUESTROOM315_318 4.75 21.25 4.75 21.25
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 10.75 19.00 10.75 19.00
GUESTROOM324 0.75 0.00 0.00 0.00
GUESTROOM401 34.50 23.50 34.50 23.50
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 26.25 22.25 26.25 22.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 18.25 26.25 18.25 26.25
GUESTROOM419 17.75 31.00 17.75 31.00
GUESTROOM420_423 18.25 26.00 18.25 26.00
GUESTROOM424 23.25 28.75 23.25 28.75
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 1.75 2580.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 21.25 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.25 85.25 0.00 0.00
FRONTSTAIRSFLR4 3.75 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 927.25 3959.00 876.25 2876.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.007515


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.007515
SAC_FRONTOFFICE SUPPLY FAN 0.313149
SAC_FRONTLOUNGE SUPPLY FAN 0.743116
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.697585


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 313.33
CORRIDORFLR1 PTAC HEATING COIL 29222.05
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1069.38
102 PTAC HEATING COIL 1069.38
103 PTAC HEATING COIL 1345.46
104 PTAC HEATING COIL 1341.39
105 PTAC HEATING COIL 1069.30
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 313.25
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 313.33
CORRIDORFLR2 PTAC HEATING COIL 3032.81
201 PTAC HEATING COIL 1214.73
202_205 PTAC HEATING COIL 4277.51
206_208 PTAC HEATING COIL 3390.07
209_212 PTAC HEATING COIL 4277.51
213 PTAC HEATING COIL 1393.66
214 PTAC HEATING COIL 1358.03
215_218 PTAC HEATING COIL 4277.21
219 PTAC HEATING COIL 1069.30
220_223 PTAC HEATING COIL 4277.21
224 PTAC HEATING COIL 1206.97
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 485.25
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 313.33
CORRIDORFLR3 PTAC HEATING COIL 3202.87
301 PTAC HEATING COIL 1265.81
302_305 PTAC HEATING COIL 4277.51
306_308 PTAC HEATING COIL 3390.07
309_312 PTAC HEATING COIL 4277.51
313 PTAC HEATING COIL 1500.42
314 PTAC HEATING COIL 1453.15
315_318 PTAC HEATING COIL 4277.21
319 PTAC HEATING COIL 1069.30
320_323 PTAC HEATING COIL 4277.21
324 PTAC HEATING COIL 1292.21
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 485.25
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 485.36
CORRIDORFLR4 PTAC HEATING COIL 4613.26
401 PTAC HEATING COIL 1574.27
402_405 PTAC HEATING COIL 4960.08
406_408 PTAC HEATING COIL 4064.36
409_412 PTAC HEATING COIL 4982.55
413 PTAC HEATING COIL 1859.81
414 PTAC HEATING COIL 1804.55
415_418 PTAC HEATING COIL 4964.47
419 PTAC HEATING COIL 1373.32
420_423 PTAC HEATING COIL 4909.30
424 PTAC HEATING COIL 1634.58
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 557.04


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.725163 0.313149 6478.81
SAC_FRONTLOUNGE COOLING COIL 0.684443 0.743116 17844.66
SAC_MEETINGROOM COOLING COIL 0.676083 0.351306 8723.76
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.739326 0.697585 13769.51


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.743116
RESTROOMFLR1 DIRECT AIR 0.041546
MEETINGROOMFLR1 DIRECT AIR 0.351306
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.540554
EXERCISECENTERFLR1 DIRECT AIR 0.115485
FRONTOFFICEFLR1 DIRECT AIR 0.313149


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.313149
SAC_FRONTLOUNGE MAIN BRANCH 0.743116
SAC_MEETINGROOM MAIN BRANCH 0.351306
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.697585


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.313149
SAC_FRONTLOUNGE 0.743116
SAC_MEETINGROOM 0.351306
SAC_EXC_EMPLGE_RESTRM 0.697585


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.313149 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.743116 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.351306 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.697585 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.313149 0.313149 0.313149 0.313149 4403.22 6478.81 1.00
SAC_FRONTLOUNGE 0.743116 0.743116 0.743116 0.743116 18456.02 17844.66 1.00
SAC_MEETINGROOM 0.351306 0.351306 0.351306 0.351306 9883.06 8723.76 1.00
SAC_EXC_EMPLGE_RESTRM 0.697585 0.697585 0.697585 0.697585 7533.00 13769.51 0.165550


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4403.22
SAC_FRONTLOUNGE HEATING COIL 18456.02
SAC_MEETINGROOM HEATING COIL 9883.06
SAC_EXC_EMPLGE_RESTRM HEATING COIL 7533.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.351306


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.19 -3.4
February 14.60 -4.2
March 17.58 2.67
April 19.12 7.47
May 21.26 13.73
June 22.81 18.63
July 23.86 22.03
August 23.55 20.69
September 22.34 16.55
October 19.97 9.72
November 18.31 6.03
December 15.21 -2.2
     
Annual Sum or Average 19.51 9.05
Minimum of Months 14.60 -4.2
Maximum of Months 23.86 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -3.4
February 21.66 -4.2
March 22.68 2.67
April 23.33 7.47
May 24.13 13.73
June 25.09 18.63
July 25.85 22.03
August 25.53 20.69
September 24.72 16.55
October 23.65 9.72
November 23.15 6.03
December 21.90 -2.2
     
Annual Sum or Average 23.63 9.05
Minimum of Months 21.66 -4.2
Maximum of Months 25.85 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.91 -3.4
February 14.34 -4.2
March 17.08 2.67
April 18.59 7.47
May 20.78 13.73
June 22.38 18.63
July 23.37 22.03
August 23.02 20.69
September 21.74 16.55
October 19.39 9.72
November 17.82 6.03
December 14.95 -2.2
     
Annual Sum or Average 19.06 9.05
Minimum of Months 14.34 -4.2
Maximum of Months 23.37 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -3.4
February 21.11 -4.2
March 21.31 2.67
April 21.39 7.47
May 22.26 13.73
June 23.17 18.63
July 23.61 22.03
August 23.43 20.69
September 22.82 16.55
October 21.63 9.72
November 21.31 6.03
December 21.12 -2.2
     
Annual Sum or Average 22.03 9.05
Minimum of Months 21.11 -4.2
Maximum of Months 23.61 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.19 -3.4
February 21.10 -4.2
March 21.79 2.67
April 22.22 7.47
May 22.88 13.73
June 23.39 18.63
July 23.62 22.03
August 23.53 20.69
September 23.17 16.55
October 22.48 9.72
November 22.10 6.03
December 21.30 -2.2
     
Annual Sum or Average 22.40 9.05
Minimum of Months 21.10 -4.2
Maximum of Months 23.62 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 -3.4
February 21.16 -4.2
March 21.59 2.67
April 22.07 7.47
May 23.18 13.73
June 23.64 18.63
July 23.80 22.03
August 23.76 20.69
September 23.52 16.55
October 22.41 9.72
November 21.73 6.03
December 21.20 -2.2
     
Annual Sum or Average 22.44 9.05
Minimum of Months 21.16 -4.2
Maximum of Months 23.80 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.34 -3.4
February 23.24 -4.2
March 24.00 2.67
April 24.64 7.47
May 25.52 13.73
June 26.15 18.63
July 26.48 22.03
August 26.40 20.69
September 25.96 16.55
October 25.05 9.72
November 24.41 6.03
December 23.46 -2.2
     
Annual Sum or Average 24.90 9.05
Minimum of Months 23.24 -4.2
Maximum of Months 26.48 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.96 -3.4
February 18.94 -4.2
March 19.71 2.67
April 20.51 7.47
May 22.01 13.73
June 22.90 18.63
July 23.23 22.03
August 23.13 20.69
September 22.60 16.55
October 21.07 9.72
November 20.08 6.03
December 19.02 -2.2
     
Annual Sum or Average 21.03 9.05
Minimum of Months 18.94 -4.2
Maximum of Months 23.23 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.92 -3.4
February 18.90 -4.2
March 19.53 2.67
April 20.18 7.47
May 21.69 13.73
June 22.70 18.63
July 23.14 22.03
August 22.99 20.69
September 22.33 16.55
October 20.72 9.72
November 19.75 6.03
December 18.94 -2.2
     
Annual Sum or Average 20.83 9.05
Minimum of Months 18.90 -4.2
Maximum of Months 23.14 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -3.4
February 20.50 -4.2
March 20.77 2.67
April 21.07 7.47
May 21.53 13.73
June 21.70 18.63
July 21.75 22.03
August 21.74 20.69
September 21.66 16.55
October 21.21 9.72
November 20.91 6.03
December 20.54 -2.2
     
Annual Sum or Average 21.16 9.05
Minimum of Months 20.50 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 -3.4
February 20.60 -4.2
March 21.00 2.67
April 21.30 7.47
May 21.64 13.73
June 21.72 18.63
July 21.75 22.03
August 21.74 20.69
September 21.71 16.55
October 21.44 9.72
November 21.18 6.03
December 20.66 -2.2
     
Annual Sum or Average 21.28 9.05
Minimum of Months 20.60 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 -3.4
February 21.01 -4.2
March 21.40 2.67
April 21.59 7.47
May 21.73 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.75 16.55
October 21.67 9.72
November 21.53 6.03
December 21.09 -2.2
     
Annual Sum or Average 21.51 9.05
Minimum of Months 21.01 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.84 -3.4
February 21.80 -4.2
March 22.21 2.67
April 22.32 7.47
May 22.52 13.73
June 22.53 18.63
July 22.42 22.03
August 22.45 20.69
September 22.50 16.55
October 22.44 9.72
November 22.41 6.03
December 21.93 -2.2
     
Annual Sum or Average 22.28 9.05
Minimum of Months 21.80 -4.2
Maximum of Months 22.53 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 50.09 -3.4
February 49.90 -4.2
March 50.94 2.67
April 51.38 7.47
May 51.99 13.73
June 52.49 18.63
July 52.89 22.03
August 52.85 20.69
September 52.52 16.55
October 51.76 9.72
November 51.13 6.03
December 50.10 -2.2
     
Annual Sum or Average 51.51 9.05
Minimum of Months 49.90 -4.2
Maximum of Months 52.89 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 66.90 -3.4
February 66.61 -4.2
March 67.92 2.67
April 68.47 7.47
May 69.33 13.73
June 69.95 18.63
July 70.52 22.03
August 70.42 20.69
September 69.96 16.55
October 68.96 9.72
November 68.14 6.03
December 66.88 -2.2
     
Annual Sum or Average 68.68 9.05
Minimum of Months 66.61 -4.2
Maximum of Months 70.52 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.30 -3.4
February 22.24 -4.2
March 22.87 2.67
April 23.14 7.47
May 23.55 13.73
June 23.79 18.63
July 23.87 22.03
August 23.86 20.69
September 23.74 16.55
October 23.36 9.72
November 23.09 6.03
December 22.38 -2.2
     
Annual Sum or Average 23.19 9.05
Minimum of Months 22.24 -4.2
Maximum of Months 23.87 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.38 -3.4
February 21.36 -4.2
March 22.12 2.67
April 22.64 7.47
May 23.48 13.73
June 23.78 18.63
July 23.88 22.03
August 23.87 20.69
September 23.74 16.55
October 23.05 9.72
November 22.39 6.03
December 21.43 -2.2
     
Annual Sum or Average 22.77 9.05
Minimum of Months 21.36 -4.2
Maximum of Months 23.88 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.36 -3.4
February 13.67 -4.2
March 17.00 2.67
April 18.77 7.47
May 21.23 13.73
June 23.02 18.63
July 24.31 22.03
August 23.94 20.69
September 22.56 16.55
October 19.81 9.72
November 17.89 6.03
December 14.36 -2.2
     
Annual Sum or Average 19.28 9.05
Minimum of Months 13.67 -4.2
Maximum of Months 24.31 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.30 -3.4
February 17.92 -4.2
March 19.89 2.67
April 20.98 7.47
May 22.47 13.73
June 23.49 18.63
July 24.19 22.03
August 24.04 20.69
September 23.29 16.55
October 21.68 9.72
November 20.47 6.03
December 18.33 -2.2
     
Annual Sum or Average 21.27 9.05
Minimum of Months 17.92 -4.2
Maximum of Months 24.19 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.14 -3.4
February 13.40 -4.2
March 17.07 2.67
April 18.98 7.47
May 21.63 13.73
June 23.40 18.63
July 24.60 22.03
August 24.24 20.69
September 22.82 16.55
October 19.95 9.72
November 17.91 6.03
December 14.10 -2.2
     
Annual Sum or Average 19.39 9.05
Minimum of Months 13.40 -4.2
Maximum of Months 24.60 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 -3.4
February 21.15 -4.2
March 21.91 2.67
April 22.73 7.47
May 23.74 13.73
June 23.87 18.63
July 23.90 22.03
August 23.89 20.69
September 23.85 16.55
October 23.11 9.72
November 22.22 6.03
December 21.22 -2.2
     
Annual Sum or Average 22.74 9.05
Minimum of Months 21.15 -4.2
Maximum of Months 23.90 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.17 -3.4
February 12.47 -4.2
March 15.92 2.67
April 17.86 7.47
May 20.74 13.73
June 22.71 18.63
July 23.92 22.03
August 23.48 20.69
September 21.88 16.55
October 18.79 9.72
November 16.78 6.03
December 13.18 -2.2
     
Annual Sum or Average 18.44 9.05
Minimum of Months 12.47 -4.2
Maximum of Months 23.92 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.38 2.67
April 19.83 7.47
May 21.85 13.73
June 22.98 18.63
July 23.28 22.03
August 23.20 20.69
September 22.55 16.55
October 20.27 9.72
November 19.27 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.79 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.28 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.57 -3.4
February 20.55 -4.2
March 20.89 2.67
April 21.24 7.47
May 21.68 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.73 16.55
October 21.36 9.72
November 21.05 6.03
December 20.61 -2.2
     
Annual Sum or Average 21.25 9.05
Minimum of Months 20.55 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 -3.4
February 20.57 -4.2
March 20.93 2.67
April 21.29 7.47
May 21.69 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.40 9.72
November 21.10 6.03
December 20.64 -2.2
     
Annual Sum or Average 21.27 9.05
Minimum of Months 20.57 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 -3.4
February 20.57 -4.2
March 20.94 2.67
April 21.32 7.47
May 21.70 13.73
June 21.74 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.43 9.72
November 21.13 6.03
December 20.65 -2.2
     
Annual Sum or Average 21.28 9.05
Minimum of Months 20.57 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -3.4
February 20.48 -4.2
March 20.76 2.67
April 21.06 7.47
May 21.59 13.73
June 21.73 18.63
July 21.75 22.03
August 21.75 20.69
September 21.70 16.55
October 21.20 9.72
November 20.86 6.03
December 20.51 -2.2
     
Annual Sum or Average 21.16 9.05
Minimum of Months 20.48 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 -3.4
February 20.60 -4.2
March 21.06 2.67
April 21.39 7.47
May 21.71 13.73
June 21.74 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.53 9.72
November 21.24 6.03
December 20.67 -2.2
     
Annual Sum or Average 21.32 9.05
Minimum of Months 20.60 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.27 -3.4
February 22.09 -4.2
March 22.89 2.67
April 23.22 7.47
May 23.33 13.73
June 23.33 18.63
July 23.33 22.03
August 23.33 20.69
September 23.33 16.55
October 23.28 9.72
November 23.17 6.03
December 22.34 -2.2
     
Annual Sum or Average 23.00 9.05
Minimum of Months 22.09 -4.2
Maximum of Months 23.33 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 29.52 -3.4
February 29.27 -4.2
March 30.60 2.67
April 31.32 7.47
May 32.38 13.73
June 32.96 18.63
July 33.38 22.03
August 33.29 20.69
September 32.88 16.55
October 31.76 9.72
November 30.84 6.03
December 29.49 -2.2
     
Annual Sum or Average 31.49 9.05
Minimum of Months 29.27 -4.2
Maximum of Months 33.38 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 -3.4
February 21.74 -4.2
March 21.89 2.67
April 22.02 7.47
May 22.29 13.73
June 22.62 18.63
July 22.94 22.03
August 22.81 20.69
September 22.55 16.55
October 22.13 9.72
November 21.87 6.03
December 21.75 -2.2
     
Annual Sum or Average 22.20 9.05
Minimum of Months 21.74 -4.2
Maximum of Months 22.94 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 -3.4
February 20.78 -4.2
March 21.23 2.67
April 21.50 7.47
May 21.73 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.75 16.55
October 21.61 9.72
November 21.37 6.03
December 20.82 -2.2
     
Annual Sum or Average 21.41 9.05
Minimum of Months 20.78 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 -3.4
February 20.61 -4.2
March 21.05 2.67
April 21.37 7.47
May 21.71 13.73
June 21.75 18.63
July 21.76 22.03
August 21.75 20.69
September 21.74 16.55
October 21.52 9.72
November 21.22 6.03
December 20.66 -2.2
     
Annual Sum or Average 21.32 9.05
Minimum of Months 20.61 -4.2
Maximum of Months 21.76 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.82 -3.4
February 16.34 -4.2
March 18.91 2.67
April 20.40 7.47
May 22.41 13.73
June 23.71 18.63
July 24.60 22.03
August 24.37 20.69
September 23.38 16.55
October 21.19 9.72
November 19.58 6.03
December 16.80 -2.2
     
Annual Sum or Average 20.73 9.05
Minimum of Months 16.34 -4.2
Maximum of Months 24.60 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.53 -3.4
February 11.73 -4.2
March 15.90 2.67
April 18.27 7.47
May 21.49 13.73
June 23.68 18.63
July 25.24 22.03
August 24.76 20.69
September 23.02 16.55
October 19.46 9.72
November 16.99 6.03
December 12.48 -2.2
     
Annual Sum or Average 18.83 9.05
Minimum of Months 11.73 -4.2
Maximum of Months 25.24 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.15 -3.4
February 12.43 -4.2
March 16.29 2.67
April 18.38 7.47
May 21.40 13.73
June 23.43 18.63
July 24.77 22.03
August 24.35 20.69
September 22.72 16.55
October 19.39 9.72
November 17.14 6.03
December 13.12 -2.2
     
Annual Sum or Average 18.92 9.05
Minimum of Months 12.43 -4.2
Maximum of Months 24.77 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -3.4
February 21.11 -4.2
March 21.40 2.67
April 21.72 7.47
May 23.12 13.73
June 23.74 18.63
July 23.88 22.03
August 23.86 20.69
September 23.54 16.55
October 22.00 9.72
November 21.33 6.03
December 21.11 -2.2
     
Annual Sum or Average 22.33 9.05
Minimum of Months 21.11 -4.2
Maximum of Months 23.88 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.82 -3.4
February 11.11 -4.2
March 14.83 2.67
April 16.94 7.47
May 20.35 13.73
June 22.76 18.63
July 24.18 22.03
August 23.66 20.69
September 21.70 16.55
October 17.92 9.72
November 15.68 6.03
December 11.84 -2.2
     
Annual Sum or Average 17.77 9.05
Minimum of Months 11.11 -4.2
Maximum of Months 24.18 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.24 2.67
April 19.43 7.47
May 21.41 13.73
June 22.84 18.63
July 23.26 22.03
August 23.13 20.69
September 22.24 16.55
October 19.75 9.72
November 19.07 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.60 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.26 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.30 2.67
April 19.57 7.47
May 21.61 13.73
June 22.92 18.63
July 23.28 22.03
August 23.18 20.69
September 22.35 16.55
October 19.95 9.72
November 19.14 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.67 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.28 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.33 2.67
April 19.68 7.47
May 21.70 13.73
June 22.92 18.63
July 23.27 22.03
August 23.17 20.69
September 22.38 16.55
October 20.06 9.72
November 19.19 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.71 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.27 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.55 -3.4
February 20.54 -4.2
March 20.87 2.67
April 21.24 7.47
May 21.67 13.73
June 21.74 18.63
July 21.75 22.03
August 21.75 20.69
September 21.72 16.55
October 21.34 9.72
November 21.03 6.03
December 20.59 -2.2
     
Annual Sum or Average 21.24 9.05
Minimum of Months 20.54 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.27 2.67
April 19.53 7.47
May 21.51 13.73
June 22.84 18.63
July 23.27 22.03
August 23.16 20.69
September 22.29 16.55
October 19.89 9.72
November 19.12 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.64 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.27 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 -3.4
February 20.52 -4.2
March 20.88 2.67
April 21.22 7.47
May 21.66 13.73
June 21.73 18.63
July 21.75 22.03
August 21.75 20.69
September 21.72 16.55
October 21.38 9.72
November 21.03 6.03
December 20.56 -2.2
     
Annual Sum or Average 21.23 9.05
Minimum of Months 20.52 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.82 -3.4
February 20.80 -4.2
March 21.27 2.67
April 21.53 7.47
May 21.74 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.75 16.55
October 21.63 9.72
November 21.41 6.03
December 20.85 -2.2
     
Annual Sum or Average 21.42 9.05
Minimum of Months 20.80 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.04 -3.4
February 20.79 -4.2
March 22.46 2.67
April 23.40 7.47
May 24.89 13.73
June 25.68 18.63
July 26.12 22.03
August 26.00 20.69
September 25.45 16.55
October 23.89 9.72
November 22.74 6.03
December 21.02 -2.2
     
Annual Sum or Average 23.64 9.05
Minimum of Months 20.79 -4.2
Maximum of Months 26.12 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.53 -3.4
February 19.46 -4.2
March 21.00 2.67
April 22.07 7.47
May 23.13 13.73
June 23.30 18.63
July 23.33 22.03
August 23.33 20.69
September 23.27 16.55
October 22.49 9.72
November 21.50 6.03
December 19.67 -2.2
     
Annual Sum or Average 21.85 9.05
Minimum of Months 19.46 -4.2
Maximum of Months 23.33 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.69 -3.4
February 20.67 -4.2
March 21.11 2.67
April 21.41 7.47
May 21.71 13.73
June 21.74 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.52 9.72
November 21.25 6.03
December 20.71 -2.2
     
Annual Sum or Average 21.34 9.05
Minimum of Months 20.67 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -3.4
February 18.90 -4.2
March 19.57 2.67
April 20.38 7.47
May 22.17 13.73
June 23.01 18.63
July 23.28 22.03
August 23.23 20.69
September 22.79 16.55
October 20.97 9.72
November 19.68 6.03
December 18.91 -2.2
     
Annual Sum or Average 20.99 9.05
Minimum of Months 18.90 -4.2
Maximum of Months 23.28 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.50 -3.4
February 15.06 -4.2
March 17.86 2.67
April 19.61 7.47
May 22.13 13.73
June 23.78 18.63
July 24.84 22.03
August 24.54 20.69
September 23.27 16.55
October 20.46 9.72
November 18.53 6.03
December 15.48 -2.2
     
Annual Sum or Average 20.12 9.05
Minimum of Months 15.06 -4.2
Maximum of Months 24.84 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.25 -3.4
February 10.59 -4.2
March 14.95 2.67
April 17.59 7.47
May 21.27 13.73
June 23.76 18.63
July 25.49 22.03
August 24.93 20.69
September 22.93 16.55
October 18.82 9.72
November 16.07 6.03
December 11.24 -2.2
     
Annual Sum or Average 18.28 9.05
Minimum of Months 10.59 -4.2
Maximum of Months 25.49 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.72 -3.4
February 11.19 -4.2
March 15.19 2.67
April 17.57 7.47
May 21.04 13.73
June 23.49 18.63
July 25.04 22.03
August 24.47 20.69
September 22.45 16.55
October 18.51 9.72
November 15.97 6.03
December 11.76 -2.2
     
Annual Sum or Average 18.24 9.05
Minimum of Months 11.19 -4.2
Maximum of Months 25.04 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -3.4
February 21.11 -4.2
March 21.32 2.67
April 21.60 7.47
May 22.64 13.73
June 23.44 18.63
July 23.79 22.03
August 23.65 20.69
September 23.04 16.55
October 21.68 9.72
November 21.24 6.03
December 21.11 -2.2
     
Annual Sum or Average 22.15 9.05
Minimum of Months 21.11 -4.2
Maximum of Months 23.79 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.74 -3.4
February 10.10 -4.2
March 14.06 2.67
April 16.40 7.47
May 20.08 13.73
June 22.81 18.63
July 24.40 22.03
August 23.74 20.69
September 21.45 16.55
October 17.26 9.72
November 14.86 6.03
December 10.82 -2.2
     
Annual Sum or Average 17.27 9.05
Minimum of Months 10.10 -4.2
Maximum of Months 24.40 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -3.4
February 20.47 -4.2
March 20.66 2.67
April 21.01 7.47
May 21.60 13.73
June 21.73 18.63
July 21.76 22.03
August 21.75 20.69
September 21.67 16.55
October 21.01 9.72
November 20.66 6.03
December 20.48 -2.2
     
Annual Sum or Average 21.11 9.05
Minimum of Months 20.47 -4.2
Maximum of Months 21.76 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.22 2.67
April 19.52 7.47
May 21.24 13.73
June 22.65 18.63
July 23.15 22.03
August 22.95 20.69
September 21.92 16.55
October 19.68 9.72
November 19.07 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.52 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.15 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.23 2.67
April 19.57 7.47
May 21.29 13.73
June 22.64 18.63
July 23.14 22.03
August 22.94 20.69
September 21.92 16.55
October 19.73 9.72
November 19.09 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.53 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.14 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.51 -3.4
February 20.50 -4.2
March 20.83 2.67
April 21.27 7.47
May 21.69 13.73
June 21.74 18.63
July 21.75 22.03
August 21.75 20.69
September 21.72 16.55
October 21.31 9.72
November 20.92 6.03
December 20.53 -2.2
     
Annual Sum or Average 21.21 9.05
Minimum of Months 20.50 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -3.4
February 18.89 -4.2
March 19.21 2.67
April 19.49 7.47
May 21.22 13.73
June 22.63 18.63
July 23.15 22.03
August 22.96 20.69
September 21.96 16.55
October 19.67 9.72
November 19.06 6.03
December 18.89 -2.2
     
Annual Sum or Average 20.51 9.05
Minimum of Months 18.89 -4.2
Maximum of Months 23.15 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -3.4
February 18.90 -4.2
March 19.40 2.67
April 20.00 7.47
May 21.65 13.73
June 22.73 18.63
July 23.17 22.03
August 23.03 20.69
September 22.30 16.55
October 20.33 9.72
November 19.35 6.03
December 18.90 -2.2
     
Annual Sum or Average 20.73 9.05
Minimum of Months 18.90 -4.2
Maximum of Months 23.17 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.61 -3.4
February 20.64 -4.2
March 21.14 2.67
April 21.45 7.47
May 21.71 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.53 9.72
November 21.22 6.03
December 20.65 -2.2
     
Annual Sum or Average 21.33 9.05
Minimum of Months 20.61 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.68 -3.4
February 18.52 -4.2
March 20.27 2.67
April 21.36 7.47
May 22.99 13.73
June 24.07 18.63
July 24.66 22.03
August 24.41 20.69
September 23.54 16.55
October 21.68 9.72
November 20.45 6.03
December 18.71 -2.2
     
Annual Sum or Average 21.63 9.05
Minimum of Months 18.52 -4.2
Maximum of Months 24.66 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 -3.4
February 20.61 -4.2
March 21.08 2.67
April 21.43 7.47
May 21.71 13.73
June 21.75 18.63
July 21.76 22.03
August 21.75 20.69
September 21.74 16.55
October 21.51 9.72
November 21.19 6.03
December 20.63 -2.2
     
Annual Sum or Average 21.32 9.05
Minimum of Months 20.59 -4.2
Maximum of Months 21.76 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.59 -3.4
February 20.62 -4.2
March 21.10 2.67
April 21.43 7.47
May 21.71 13.73
June 21.75 18.63
July 21.75 22.03
August 21.75 20.69
September 21.74 16.55
October 21.50 9.72
November 21.18 6.03
December 20.63 -2.2
     
Annual Sum or Average 21.32 9.05
Minimum of Months 20.59 -4.2
Maximum of Months 21.75 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -3.4
February 20.50 -4.2
March 20.85 2.67
April 21.25 7.47
May 21.67 13.73
June 21.74 18.63
July 21.76 22.03
August 21.75 20.69
September 21.72 16.55
October 21.36 9.72
November 20.96 6.03
December 20.53 -2.2
     
Annual Sum or Average 21.22 9.05
Minimum of Months 20.50 -4.2
Maximum of Months 21.76 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.75 -3.4
February 14.46 -4.2
March 17.39 2.67
April 19.33 7.47
May 21.96 13.73
June 23.78 18.63
July 24.91 22.03
August 24.48 20.69
September 22.99 16.55
October 20.01 9.72
November 17.98 6.03
December 14.83 -2.2
     
Annual Sum or Average 19.77 9.05
Minimum of Months 14.46 -4.2
Maximum of Months 24.91 22.03



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.24 -3.4
February 9.88 -4.2
March 14.22 2.67
April 17.12 7.47
May 21.03 13.73
June 23.77 18.63
July 25.63 22.03
August 24.93 20.69
September 22.64 16.55
October 18.21 9.72
November 15.29 6.03
December 10.40 -2.2
     
Annual Sum or Average 17.82 9.05
Minimum of Months 9.88 -4.2
Maximum of Months 25.63 22.03



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:38

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.190174E+12 141503.822 24-JAN-07:15 15177.258 39465.561 8679.036 73873.396 112.458 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.176374E+12 156836.413 07-FEB-07:15 15177.258 39465.561 8691.876 89234.306 71.299 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.155744E+12 131573.714 07-MAR-07:15 15177.258 39465.561 8669.087 68097.645 156.050 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.129283E+12 101070.808 17-APR-06:15 15065.632 39465.561 8655.430 37636.012 240.059 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.132986E+12 83590.266 28-MAY-07:00 17641.054 43276.576 9048.930 0.000 13615.593 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.142289E+12 91539.612 17-JUN-07:00 17492.219 43276.576 9048.930 0.000 21713.774 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.159870E+12 101173.152 21-JUL-07:00 17492.219 43276.576 9048.930 0.000 31347.314 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.153775E+12 90047.310 26-AUG-07:00 17566.637 43276.576 9048.930 0.000 20147.055 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.137654E+12 92242.716 16-SEP-07:00 17566.637 43276.576 9048.930 0.000 22342.461 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.133635E+12 99516.209 17-OCT-06:15 15177.258 39465.561 8655.430 31553.329 468.518 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.136209E+12 100712.795 24-NOV-07:15 13316.689 34010.661 8655.430 40327.474 206.428 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.185352E+12 146806.550 11-DEC-07:15 15177.258 39465.561 8674.729 79176.294 116.594 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.183335E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.129283E+12 83590.266   13316.689 34010.661 8655.430 0.000 71.299 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.190174E+12 156836.413   17641.054 43276.576 9048.930 89234.306 31347.314 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:38

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.124629E+12 115725.828 31-JAN-11:15 16138.151 40096.028 0.000 59491.649 59491.649 59491.649 16138.151
February 0.115343E+12 120958.971 06-FEB-10:45 21146.398 40096.028 0.000 59716.545 59716.545 59716.545 21146.398
March 0.113062E+12 113279.579 04-MAR-10:00 13599.874 40096.028 0.000 59583.678 59583.678 59583.678 13599.874
April 0.979686E+11 103748.054 14-APR-10:00 5945.535 40096.028 0.000 57706.491 57706.491 57706.491 5945.535
May 0.925900E+11 98308.358 05-MAY-08:15 0.000 40096.028 0.000 58212.330 58212.330 58212.330 0.000
June 0.854577E+11 95482.349 03-JUN-08:15 0.000 40096.028 0.000 55386.321 55386.321 55386.321 0.000
July 0.855992E+11 92389.007 01-JUL-08:15 0.000 40096.028 0.000 52292.979 52292.979 52292.979 0.000
August 0.847147E+11 91538.364 12-AUG-08:15 0.000 40096.028 0.000 51442.336 51442.336 51442.336 0.000
September 0.831044E+11 92318.272 30-SEP-08:15 0.000 40096.028 0.000 52222.244 52222.244 52222.244 0.000
October 0.918889E+11 98383.700 24-OCT-09:15 4873.226 40096.028 0.000 53414.446 53414.446 53414.446 4873.226
November 0.969387E+11 100855.205 12-NOV-10:15 5433.111 40096.028 0.000 55326.066 55326.066 55326.066 5433.111
December 0.119769E+12 114576.317 28-DEC-10:00 16154.895 40096.028 0.000 58325.394 58325.394 58325.394 16154.895
                     
Annual Sum or Average 0.119107E+13         0.000        
Minimum of Months 0.831044E+11 91538.364   0.000 40096.028 0.000 51442.336 51442.336 51442.336 0.000
Maximum of Months 0.124629E+12 120958.971   21146.398 40096.028 0.000 59716.545 59716.545 59716.545 21146.398