Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2018-10-19 10:15:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3024.41 | 753.54 | 811.90 |
Net Site Energy | 3024.41 | 753.54 | 811.90 |
Total Source Energy | 7097.32 | 1768.33 | 1905.27 |
Net Source Energy | 7097.32 | 1768.33 | 1905.27 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 285.41 | 115.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 198.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 654.20 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1833.35 | 1191.07 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 285.41 | 115.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 198.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 278.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 654.20 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 204.64 | 206.59 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 492.16 | 319.74 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 189.93 | 191.74 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 456.79 | 296.76 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1833.35 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1833.35 | 100.00 |
Total On-Site and Utility Electric Sources | 1833.35 | 100.00 |
Total Electricity End Uses | 1833.35 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 876.25 |
Time Setpoint Not Met During Occupied Cooling | 2876.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6095.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6478.81 | 4698.19 | 1780.62 | 0.73 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17844.66 | 12213.65 | 5631.01 | 0.68 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8723.76 | 5897.99 | 2825.77 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13769.51 | 10180.16 | 3589.35 | 0.74 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6235.6 | 3.28 | 11.21 | 11.88 | 11.21 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17267.1 | 3.36 | 11.47 | 12.16 | 11.61 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8450.7 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13227.9 | 3.26 | 11.12 | 11.78 | 11.07 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.33 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 29222.05 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1069.38 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1069.38 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1345.46 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1341.39 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1069.30 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.25 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.33 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3032.81 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1214.73 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4277.51 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3390.07 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4277.51 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1393.66 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1358.03 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4277.21 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1069.30 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4277.21 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1206.97 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 485.25 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.33 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 3202.87 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1265.81 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4277.51 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3390.07 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4277.51 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1500.42 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1453.15 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4277.21 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1069.30 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4277.21 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1292.21 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 485.25 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 485.36 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 4613.26 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1574.27 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 4960.08 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 4064.36 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 4982.55 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1859.81 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1804.55 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 4964.47 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1373.32 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 4909.30 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1634.58 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 557.04 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4403.22 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 18456.02 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 9883.06 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 7533.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.70 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.31 | 350.76 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.74 | 822.75 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 393.50 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.70 | 781.37 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7321.96 | 8786.35 | 0.619 | 0.743 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
RESTROOMFLR1 | 409.76 | 491.71 | 0.035 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 29.56 | 0.01335 |
MEETINGROOMFLR1 | 3459.27 | 4151.12 | 0.293 | 0.351 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
GUESTROOM101 | 527.10 | 632.52 | 0.062 | 0.074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.88 | 0.01335 |
GUESTROOM102 | 428.11 | 513.73 | 0.050 | 0.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.88 | 0.01335 |
GUESTROOM103 | 992.25 | 1190.70 | 0.117 | 0.140 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.02 | 0.01335 |
GUESTROOM104 | 1148.93 | 1378.71 | 0.135 | 0.162 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM105 | 1518.44 | 1822.13 | 0.178 | 0.214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
EMPLOYEELOUNGEFLR1 | 5325.43 | 6390.52 | 0.450 | 0.541 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
EXERCISECENTERFLR1 | 1138.40 | 1366.08 | 0.096 | 0.115 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.00 | 0.01335 |
FRONTOFFICEFLR1 | 3088.04 | 3705.64 | 0.261 | 0.313 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM201 | 778.55 | 934.26 | 0.091 | 0.110 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:15:00 | 29.95 | 0.01335 |
GUESTROOM202_205 | 4022.16 | 4826.59 | 0.473 | 0.567 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.88 | 0.01335 |
GUESTROOM206_208 | 3258.04 | 3909.65 | 0.383 | 0.459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.88 | 0.01335 |
GUESTROOM209_212 | 3835.81 | 4602.97 | 0.451 | 0.541 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.88 | 0.01335 |
GUESTROOM213 | 1075.01 | 1290.01 | 0.126 | 0.152 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67 | 0.01335 |
GUESTROOM214 | 1291.90 | 1550.28 | 0.152 | 0.182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM215_218 | 9495.66 | 11394.79 | 1.116 | 1.339 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM219 | 5385.59 | 6462.71 | 0.633 | 0.759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM220_223 | 4549.15 | 5458.98 | 0.535 | 0.641 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM224 | 1290.76 | 1548.91 | 0.152 | 0.182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM301 | 603.37 | 724.05 | 0.071 | 0.085 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
GUESTROOM302_305 | 1477.35 | 1772.82 | 0.174 | 0.208 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.74 | 0.01335 |
GUESTROOM306_308 | 1292.32 | 1550.79 | 0.152 | 0.182 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.74 | 0.01335 |
GUESTROOM309_312 | 3810.64 | 4572.77 | 0.448 | 0.537 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.74 | 0.01335 |
GUESTROOM313 | 579.26 | 695.11 | 0.068 | 0.082 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 27.02 | 0.01335 |
GUESTROOM314 | 1212.37 | 1454.85 | 0.142 | 0.171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
GUESTROOM315_318 | 4961.22 | 5953.46 | 0.583 | 0.700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM319 | 1098.94 | 1318.72 | 0.129 | 0.155 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM320_323 | 4352.28 | 5222.74 | 0.511 | 0.614 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM324 | 720.94 | 865.12 | 0.085 | 0.102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM401 | 1440.04 | 1728.05 | 0.169 | 0.203 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 30.18 | 0.01335 |
GUESTROOM402_405 | 2253.90 | 2704.68 | 0.265 | 0.318 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM406_408 | 1926.83 | 2312.20 | 0.226 | 0.272 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.30 | 0.01335 |
GUESTROOM409_412 | 4899.03 | 5878.84 | 0.576 | 0.691 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM413 | 830.92 | 997.10 | 0.098 | 0.117 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 30.16 | 0.01335 |
GUESTROOM414 | 1006.66 | 1207.99 | 0.118 | 0.142 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
GUESTROOM415_418 | 5663.12 | 6795.74 | 0.665 | 0.799 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
GUESTROOM419 | 1550.62 | 1860.74 | 0.182 | 0.219 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.30 | 0.01335 |
GUESTROOM420_423 | 5627.54 | 6753.04 | 0.661 | 0.794 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
GUESTROOM424 | 1565.48 | 1878.58 | 0.184 | 0.221 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
CORRIDORFLR1 | 13930.28 | 16716.34 | 1.177 | 1.413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
CORRIDORFLR2 | 2608.94 | 3130.73 | 0.220 | 0.264 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.00 | 0.01335 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
CORRIDORFLR3 | 1228.76 | 1474.51 | 0.104 | 0.125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 28.77 | 0.01335 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 | |
CORRIDORFLR4 | 2115.04 | 2538.05 | 0.179 | 0.214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 30.16 | 0.01335 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 0.01335 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1845.71 | 2214.85 | 0.053 | 0.236 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -16.30 | 0.00092 |
RESTROOMFLR1 | 127.79 | 153.35 | 0.004 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -16.30 | 0.00092 |
MEETINGROOMFLR1 | 656.41 | 787.69 | 0.019 | 0.126 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -16.30 | 0.00092 |
GUESTROOM101 | 277.29 | 332.75 | 0.008 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -16.30 | 0.00092 |
GUESTROOM102 | 327.21 | 392.65 | 0.009 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -16.30 | 0.00092 |
GUESTROOM103 | 618.37 | 742.05 | 0.018 | 0.021 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -16.30 | 0.00092 |
GUESTROOM104 | 615.01 | 738.02 | 0.018 | 0.021 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30 | 0.00092 |
GUESTROOM105 | 329.63 | 395.56 | 0.010 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -16.30 | 0.00092 |
EMPLOYEELOUNGEFLR1 | 303.99 | 364.79 | 0.009 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30 | 0.00092 |
EXERCISECENTERFLR1 | 208.42 | 250.11 | 0.006 | 0.043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -16.30 | 0.00092 |
FRONTOFFICEFLR1 | 1218.00 | 1461.60 | 0.035 | 0.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -16.30 | 0.00092 |
GUESTROOM201 | 509.43 | 611.31 | 0.015 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -16.30 | 0.00092 |
GUESTROOM202_205 | 1084.91 | 1301.89 | 0.031 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -16.30 | 0.00092 |
GUESTROOM206_208 | 859.06 | 1030.87 | 0.025 | 0.043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -16.30 | 0.00092 |
GUESTROOM209_212 | 1007.46 | 1208.95 | 0.029 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -16.30 | 0.00092 |
GUESTROOM213 | 658.54 | 790.24 | 0.019 | 0.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -16.30 | 0.00092 |
GUESTROOM214 | 628.88 | 754.66 | 0.018 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -16.30 | 0.00092 |
GUESTROOM215_218 | 1012.13 | 1214.56 | 0.029 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -16.30 | 0.00092 |
GUESTROOM219 | 261.01 | 313.21 | 0.008 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -16.30 | 0.00092 |
GUESTROOM220_223 | 969.30 | 1163.15 | 0.028 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -16.30 | 0.00092 |
GUESTROOM224 | 502.99 | 603.59 | 0.015 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -16.30 | 0.00092 |
GUESTROOM301 | 552.00 | 662.40 | 0.016 | 0.019 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -16.30 | 0.00092 |
GUESTROOM302_305 | 1214.46 | 1457.36 | 0.035 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -16.30 | 0.00092 |
GUESTROOM306_308 | 1038.98 | 1246.77 | 0.030 | 0.043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -16.30 | 0.00092 |
GUESTROOM309_312 | 1220.59 | 1464.71 | 0.035 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -16.30 | 0.00092 |
GUESTROOM313 | 747.50 | 897.00 | 0.022 | 0.026 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -16.30 | 0.00092 |
GUESTROOM314 | 708.14 | 849.77 | 0.020 | 0.025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 14:30:00 | -16.30 | 0.00092 |
GUESTROOM315_318 | 1207.95 | 1449.54 | 0.035 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -16.30 | 0.00092 |
GUESTROOM319 | 348.90 | 418.69 | 0.010 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30 | 0.00092 |
GUESTROOM320_323 | 1163.03 | 1395.63 | 0.034 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -16.30 | 0.00092 |
GUESTROOM324 | 574.03 | 688.84 | 0.017 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -16.30 | 0.00092 |
GUESTROOM401 | 809.05 | 970.86 | 0.023 | 0.028 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 21:45:00 | -16.30 | 0.00092 |
GUESTROOM402_405 | 2122.01 | 2546.42 | 0.061 | 0.074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 21:00:00 | -16.30 | 0.00092 |
GUESTROOM406_408 | 1792.87 | 2151.45 | 0.052 | 0.062 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | -16.30 | 0.00092 |
GUESTROOM409_412 | 2140.74 | 2568.88 | 0.062 | 0.074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -16.30 | 0.00092 |
GUESTROOM413 | 1046.99 | 1256.39 | 0.030 | 0.036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -16.30 | 0.00092 |
GUESTROOM414 | 1000.98 | 1201.18 | 0.029 | 0.035 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -16.30 | 0.00092 |
GUESTROOM415_418 | 2125.81 | 2550.98 | 0.061 | 0.074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -16.30 | 0.00092 |
GUESTROOM419 | 641.62 | 769.94 | 0.019 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | -16.30 | 0.00092 |
GUESTROOM420_423 | 2079.84 | 2495.81 | 0.060 | 0.072 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -16.30 | 0.00092 |
GUESTROOM424 | 859.34 | 1031.21 | 0.025 | 0.030 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | -16.30 | 0.00092 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
CORRIDORFLR1 | 22626.39 | 27151.67 | 0.653 | 0.784 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -16.30 | 0.00092 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
CORRIDORFLR2 | 971.31 | 1165.57 | 0.028 | 0.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -16.30 | 0.00092 |
FRONTSTAIRSFLR2 | 17.23 | 20.67 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
CORRIDORFLR3 | 1243.01 | 1491.61 | 0.036 | 0.043 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
FRONTSTAIRSFLR3 | 151.43 | 181.72 | 0.003 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
REARSTAIRSFLR4 | 26.25 | 31.50 | 0.001 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
CORRIDORFLR4 | 2418.35 | 2902.02 | 0.070 | 0.084 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
FRONTSTAIRSFLR4 | 320.91 | 385.10 | 0.006 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -16.30 | 0.00092 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.31 | 0.31 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.74 | 0.74 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.35 | 0.35 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.70 | 0.70 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.74 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 2719.00 | 7617.25 | 2267.25 |
RESTROOMFLR1 | 1109.75 | 7935.00 | 972.75 |
MEETINGROOMFLR1 | 928.25 | 3601.00 | 477.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 2569.25 | 8759.75 | 2569.25 |
GUESTROOM104 | 1721.75 | 8731.75 | 1721.75 |
GUESTROOM105 | 138.50 | 8476.50 | 138.50 |
EMPLOYEELOUNGEFLR1 | 2815.75 | 2374.50 | 369.25 |
EXERCISECENTERFLR1 | 1092.00 | 3316.25 | 73.75 |
FRONTOFFICEFLR1 | 1530.75 | 6742.25 | 950.25 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1577.50 | 8531.00 | 1576.00 |
GUESTROOM206_208 | 1412.50 | 8533.00 | 1411.00 |
GUESTROOM209_212 | 1267.75 | 8662.25 | 1267.75 |
GUESTROOM213 | 2684.25 | 8716.50 | 2684.25 |
GUESTROOM214 | 1444.50 | 8554.25 | 1444.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3300.25 | 4491.25 | 231.50 |
GUESTROOM220_223 | 423.50 | 8407.75 | 410.75 |
GUESTROOM224 | 1461.00 | 8517.00 | 1461.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1758.25 | 8672.25 | 1758.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 2227.75 | 8559.50 | 2227.75 |
GUESTROOM315_318 | 427.75 | 8284.00 | 389.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 948.25 | 8511.50 | 940.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 3895.25 | 8202.00 | 3734.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 2749.25 | 8083.25 | 2526.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2175.25 | 7845.00 | 1752.25 |
GUESTROOM419 | 2107.00 | 7980.00 | 1904.25 |
GUESTROOM420_423 | 2274.25 | 7869.50 | 1874.00 |
GUESTROOM424 | 2973.75 | 8092.50 | 2798.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7258.75 | 8760.00 | 6095.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 633.50 | 406.25 | 633.50 | 406.25 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 1.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 23.75 | 29.00 | 23.75 | 29.00 |
GUESTROOM104 | 13.50 | 33.50 | 13.50 | 33.50 |
GUESTROOM105 | 0.00 | 43.25 | 0.00 | 43.25 |
EMPLOYEELOUNGEFLR1 | 623.25 | 1098.25 | 452.75 | 644.25 |
EXERCISECENTERFLR1 | 0.25 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
GUESTROOM201 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 18.25 | 16.75 | 18.25 | 16.75 |
GUESTROOM206_208 | 16.50 | 23.25 | 16.50 | 23.25 |
GUESTROOM209_212 | 16.50 | 16.25 | 16.50 | 16.25 |
GUESTROOM213 | 26.50 | 16.50 | 26.50 | 16.50 |
GUESTROOM214 | 12.50 | 21.25 | 12.50 | 21.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2123.25 | 0.00 | 2123.25 |
GUESTROOM220_223 | 4.25 | 19.50 | 4.25 | 19.50 |
GUESTROOM224 | 13.25 | 21.25 | 13.25 | 21.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 21.50 | 16.50 | 21.50 | 16.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 20.00 | 20.25 | 20.00 | 20.25 |
GUESTROOM315_318 | 4.75 | 21.25 | 4.75 | 21.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 10.75 | 19.00 | 10.75 | 19.00 |
GUESTROOM324 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 34.50 | 23.50 | 34.50 | 23.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 26.25 | 22.25 | 26.25 | 22.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 18.25 | 26.25 | 18.25 | 26.25 |
GUESTROOM419 | 17.75 | 31.00 | 17.75 | 31.00 |
GUESTROOM420_423 | 18.25 | 26.00 | 18.25 | 26.00 |
GUESTROOM424 | 23.25 | 28.75 | 23.25 | 28.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 1.75 | 2580.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 21.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.25 | 85.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 3.75 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 927.25 | 3959.00 | 876.25 | 2876.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.007515 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.007515 |
SAC_FRONTOFFICE SUPPLY FAN | 0.313149 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.743116 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.697585 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.33 |
CORRIDORFLR1 PTAC HEATING COIL | 29222.05 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1069.38 |
102 PTAC HEATING COIL | 1069.38 |
103 PTAC HEATING COIL | 1345.46 |
104 PTAC HEATING COIL | 1341.39 |
105 PTAC HEATING COIL | 1069.30 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.25 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 313.33 |
CORRIDORFLR2 PTAC HEATING COIL | 3032.81 |
201 PTAC HEATING COIL | 1214.73 |
202_205 PTAC HEATING COIL | 4277.51 |
206_208 PTAC HEATING COIL | 3390.07 |
209_212 PTAC HEATING COIL | 4277.51 |
213 PTAC HEATING COIL | 1393.66 |
214 PTAC HEATING COIL | 1358.03 |
215_218 PTAC HEATING COIL | 4277.21 |
219 PTAC HEATING COIL | 1069.30 |
220_223 PTAC HEATING COIL | 4277.21 |
224 PTAC HEATING COIL | 1206.97 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 485.25 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 313.33 |
CORRIDORFLR3 PTAC HEATING COIL | 3202.87 |
301 PTAC HEATING COIL | 1265.81 |
302_305 PTAC HEATING COIL | 4277.51 |
306_308 PTAC HEATING COIL | 3390.07 |
309_312 PTAC HEATING COIL | 4277.51 |
313 PTAC HEATING COIL | 1500.42 |
314 PTAC HEATING COIL | 1453.15 |
315_318 PTAC HEATING COIL | 4277.21 |
319 PTAC HEATING COIL | 1069.30 |
320_323 PTAC HEATING COIL | 4277.21 |
324 PTAC HEATING COIL | 1292.21 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 485.25 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 485.36 |
CORRIDORFLR4 PTAC HEATING COIL | 4613.26 |
401 PTAC HEATING COIL | 1574.27 |
402_405 PTAC HEATING COIL | 4960.08 |
406_408 PTAC HEATING COIL | 4064.36 |
409_412 PTAC HEATING COIL | 4982.55 |
413 PTAC HEATING COIL | 1859.81 |
414 PTAC HEATING COIL | 1804.55 |
415_418 PTAC HEATING COIL | 4964.47 |
419 PTAC HEATING COIL | 1373.32 |
420_423 PTAC HEATING COIL | 4909.30 |
424 PTAC HEATING COIL | 1634.58 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 557.04 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.725163 | 0.313149 | 6478.81 |
SAC_FRONTLOUNGE COOLING COIL | 0.684443 | 0.743116 | 17844.66 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.351306 | 8723.76 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.739326 | 0.697585 | 13769.51 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.743116 |
RESTROOMFLR1 DIRECT AIR | 0.041546 |
MEETINGROOMFLR1 DIRECT AIR | 0.351306 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.540554 |
EXERCISECENTERFLR1 DIRECT AIR | 0.115485 |
FRONTOFFICEFLR1 DIRECT AIR | 0.313149 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.313149 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.743116 |
SAC_MEETINGROOM MAIN BRANCH | 0.351306 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.697585 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.313149 |
SAC_FRONTLOUNGE | 0.743116 |
SAC_MEETINGROOM | 0.351306 |
SAC_EXC_EMPLGE_RESTRM | 0.697585 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.313149 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.743116 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.351306 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.697585 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.313149 | 0.313149 | 0.313149 | 0.313149 | 4403.22 | 6478.81 | 1.00 |
SAC_FRONTLOUNGE | 0.743116 | 0.743116 | 0.743116 | 0.743116 | 18456.02 | 17844.66 | 1.00 |
SAC_MEETINGROOM | 0.351306 | 0.351306 | 0.351306 | 0.351306 | 9883.06 | 8723.76 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.697585 | 0.697585 | 0.697585 | 0.697585 | 7533.00 | 13769.51 | 0.165550 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4403.22 |
SAC_FRONTLOUNGE HEATING COIL | 18456.02 |
SAC_MEETINGROOM HEATING COIL | 9883.06 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 7533.00 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.351306 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.19 | -3.4 |
February | 14.60 | -4.2 |
March | 17.58 | 2.67 |
April | 19.12 | 7.47 |
May | 21.26 | 13.73 |
June | 22.81 | 18.63 |
July | 23.86 | 22.03 |
August | 23.55 | 20.69 |
September | 22.34 | 16.55 |
October | 19.97 | 9.72 |
November | 18.31 | 6.03 |
December | 15.21 | -2.2 |
Annual Sum or Average | 19.51 | 9.05 |
Minimum of Months | 14.60 | -4.2 |
Maximum of Months | 23.86 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | -3.4 |
February | 21.66 | -4.2 |
March | 22.68 | 2.67 |
April | 23.33 | 7.47 |
May | 24.13 | 13.73 |
June | 25.09 | 18.63 |
July | 25.85 | 22.03 |
August | 25.53 | 20.69 |
September | 24.72 | 16.55 |
October | 23.65 | 9.72 |
November | 23.15 | 6.03 |
December | 21.90 | -2.2 |
Annual Sum or Average | 23.63 | 9.05 |
Minimum of Months | 21.66 | -4.2 |
Maximum of Months | 25.85 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.91 | -3.4 |
February | 14.34 | -4.2 |
March | 17.08 | 2.67 |
April | 18.59 | 7.47 |
May | 20.78 | 13.73 |
June | 22.38 | 18.63 |
July | 23.37 | 22.03 |
August | 23.02 | 20.69 |
September | 21.74 | 16.55 |
October | 19.39 | 9.72 |
November | 17.82 | 6.03 |
December | 14.95 | -2.2 |
Annual Sum or Average | 19.06 | 9.05 |
Minimum of Months | 14.34 | -4.2 |
Maximum of Months | 23.37 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -3.4 |
February | 21.11 | -4.2 |
March | 21.31 | 2.67 |
April | 21.39 | 7.47 |
May | 22.26 | 13.73 |
June | 23.17 | 18.63 |
July | 23.61 | 22.03 |
August | 23.43 | 20.69 |
September | 22.82 | 16.55 |
October | 21.63 | 9.72 |
November | 21.31 | 6.03 |
December | 21.12 | -2.2 |
Annual Sum or Average | 22.03 | 9.05 |
Minimum of Months | 21.11 | -4.2 |
Maximum of Months | 23.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | -3.4 |
February | 21.10 | -4.2 |
March | 21.79 | 2.67 |
April | 22.22 | 7.47 |
May | 22.88 | 13.73 |
June | 23.39 | 18.63 |
July | 23.62 | 22.03 |
August | 23.53 | 20.69 |
September | 23.17 | 16.55 |
October | 22.48 | 9.72 |
November | 22.10 | 6.03 |
December | 21.30 | -2.2 |
Annual Sum or Average | 22.40 | 9.05 |
Minimum of Months | 21.10 | -4.2 |
Maximum of Months | 23.62 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -3.4 |
February | 21.16 | -4.2 |
March | 21.59 | 2.67 |
April | 22.07 | 7.47 |
May | 23.18 | 13.73 |
June | 23.64 | 18.63 |
July | 23.80 | 22.03 |
August | 23.76 | 20.69 |
September | 23.52 | 16.55 |
October | 22.41 | 9.72 |
November | 21.73 | 6.03 |
December | 21.20 | -2.2 |
Annual Sum or Average | 22.44 | 9.05 |
Minimum of Months | 21.16 | -4.2 |
Maximum of Months | 23.80 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | -3.4 |
February | 23.24 | -4.2 |
March | 24.00 | 2.67 |
April | 24.64 | 7.47 |
May | 25.52 | 13.73 |
June | 26.15 | 18.63 |
July | 26.48 | 22.03 |
August | 26.40 | 20.69 |
September | 25.96 | 16.55 |
October | 25.05 | 9.72 |
November | 24.41 | 6.03 |
December | 23.46 | -2.2 |
Annual Sum or Average | 24.90 | 9.05 |
Minimum of Months | 23.24 | -4.2 |
Maximum of Months | 26.48 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.96 | -3.4 |
February | 18.94 | -4.2 |
March | 19.71 | 2.67 |
April | 20.51 | 7.47 |
May | 22.01 | 13.73 |
June | 22.90 | 18.63 |
July | 23.23 | 22.03 |
August | 23.13 | 20.69 |
September | 22.60 | 16.55 |
October | 21.07 | 9.72 |
November | 20.08 | 6.03 |
December | 19.02 | -2.2 |
Annual Sum or Average | 21.03 | 9.05 |
Minimum of Months | 18.94 | -4.2 |
Maximum of Months | 23.23 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.92 | -3.4 |
February | 18.90 | -4.2 |
March | 19.53 | 2.67 |
April | 20.18 | 7.47 |
May | 21.69 | 13.73 |
June | 22.70 | 18.63 |
July | 23.14 | 22.03 |
August | 22.99 | 20.69 |
September | 22.33 | 16.55 |
October | 20.72 | 9.72 |
November | 19.75 | 6.03 |
December | 18.94 | -2.2 |
Annual Sum or Average | 20.83 | 9.05 |
Minimum of Months | 18.90 | -4.2 |
Maximum of Months | 23.14 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -3.4 |
February | 20.50 | -4.2 |
March | 20.77 | 2.67 |
April | 21.07 | 7.47 |
May | 21.53 | 13.73 |
June | 21.70 | 18.63 |
July | 21.75 | 22.03 |
August | 21.74 | 20.69 |
September | 21.66 | 16.55 |
October | 21.21 | 9.72 |
November | 20.91 | 6.03 |
December | 20.54 | -2.2 |
Annual Sum or Average | 21.16 | 9.05 |
Minimum of Months | 20.50 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -3.4 |
February | 20.60 | -4.2 |
March | 21.00 | 2.67 |
April | 21.30 | 7.47 |
May | 21.64 | 13.73 |
June | 21.72 | 18.63 |
July | 21.75 | 22.03 |
August | 21.74 | 20.69 |
September | 21.71 | 16.55 |
October | 21.44 | 9.72 |
November | 21.18 | 6.03 |
December | 20.66 | -2.2 |
Annual Sum or Average | 21.28 | 9.05 |
Minimum of Months | 20.60 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | -3.4 |
February | 21.01 | -4.2 |
March | 21.40 | 2.67 |
April | 21.59 | 7.47 |
May | 21.73 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.75 | 16.55 |
October | 21.67 | 9.72 |
November | 21.53 | 6.03 |
December | 21.09 | -2.2 |
Annual Sum or Average | 21.51 | 9.05 |
Minimum of Months | 21.01 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.84 | -3.4 |
February | 21.80 | -4.2 |
March | 22.21 | 2.67 |
April | 22.32 | 7.47 |
May | 22.52 | 13.73 |
June | 22.53 | 18.63 |
July | 22.42 | 22.03 |
August | 22.45 | 20.69 |
September | 22.50 | 16.55 |
October | 22.44 | 9.72 |
November | 22.41 | 6.03 |
December | 21.93 | -2.2 |
Annual Sum or Average | 22.28 | 9.05 |
Minimum of Months | 21.80 | -4.2 |
Maximum of Months | 22.53 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.09 | -3.4 |
February | 49.90 | -4.2 |
March | 50.94 | 2.67 |
April | 51.38 | 7.47 |
May | 51.99 | 13.73 |
June | 52.49 | 18.63 |
July | 52.89 | 22.03 |
August | 52.85 | 20.69 |
September | 52.52 | 16.55 |
October | 51.76 | 9.72 |
November | 51.13 | 6.03 |
December | 50.10 | -2.2 |
Annual Sum or Average | 51.51 | 9.05 |
Minimum of Months | 49.90 | -4.2 |
Maximum of Months | 52.89 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 66.90 | -3.4 |
February | 66.61 | -4.2 |
March | 67.92 | 2.67 |
April | 68.47 | 7.47 |
May | 69.33 | 13.73 |
June | 69.95 | 18.63 |
July | 70.52 | 22.03 |
August | 70.42 | 20.69 |
September | 69.96 | 16.55 |
October | 68.96 | 9.72 |
November | 68.14 | 6.03 |
December | 66.88 | -2.2 |
Annual Sum or Average | 68.68 | 9.05 |
Minimum of Months | 66.61 | -4.2 |
Maximum of Months | 70.52 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.30 | -3.4 |
February | 22.24 | -4.2 |
March | 22.87 | 2.67 |
April | 23.14 | 7.47 |
May | 23.55 | 13.73 |
June | 23.79 | 18.63 |
July | 23.87 | 22.03 |
August | 23.86 | 20.69 |
September | 23.74 | 16.55 |
October | 23.36 | 9.72 |
November | 23.09 | 6.03 |
December | 22.38 | -2.2 |
Annual Sum or Average | 23.19 | 9.05 |
Minimum of Months | 22.24 | -4.2 |
Maximum of Months | 23.87 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.38 | -3.4 |
February | 21.36 | -4.2 |
March | 22.12 | 2.67 |
April | 22.64 | 7.47 |
May | 23.48 | 13.73 |
June | 23.78 | 18.63 |
July | 23.88 | 22.03 |
August | 23.87 | 20.69 |
September | 23.74 | 16.55 |
October | 23.05 | 9.72 |
November | 22.39 | 6.03 |
December | 21.43 | -2.2 |
Annual Sum or Average | 22.77 | 9.05 |
Minimum of Months | 21.36 | -4.2 |
Maximum of Months | 23.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.36 | -3.4 |
February | 13.67 | -4.2 |
March | 17.00 | 2.67 |
April | 18.77 | 7.47 |
May | 21.23 | 13.73 |
June | 23.02 | 18.63 |
July | 24.31 | 22.03 |
August | 23.94 | 20.69 |
September | 22.56 | 16.55 |
October | 19.81 | 9.72 |
November | 17.89 | 6.03 |
December | 14.36 | -2.2 |
Annual Sum or Average | 19.28 | 9.05 |
Minimum of Months | 13.67 | -4.2 |
Maximum of Months | 24.31 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.30 | -3.4 |
February | 17.92 | -4.2 |
March | 19.89 | 2.67 |
April | 20.98 | 7.47 |
May | 22.47 | 13.73 |
June | 23.49 | 18.63 |
July | 24.19 | 22.03 |
August | 24.04 | 20.69 |
September | 23.29 | 16.55 |
October | 21.68 | 9.72 |
November | 20.47 | 6.03 |
December | 18.33 | -2.2 |
Annual Sum or Average | 21.27 | 9.05 |
Minimum of Months | 17.92 | -4.2 |
Maximum of Months | 24.19 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.14 | -3.4 |
February | 13.40 | -4.2 |
March | 17.07 | 2.67 |
April | 18.98 | 7.47 |
May | 21.63 | 13.73 |
June | 23.40 | 18.63 |
July | 24.60 | 22.03 |
August | 24.24 | 20.69 |
September | 22.82 | 16.55 |
October | 19.95 | 9.72 |
November | 17.91 | 6.03 |
December | 14.10 | -2.2 |
Annual Sum or Average | 19.39 | 9.05 |
Minimum of Months | 13.40 | -4.2 |
Maximum of Months | 24.60 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | -3.4 |
February | 21.15 | -4.2 |
March | 21.91 | 2.67 |
April | 22.73 | 7.47 |
May | 23.74 | 13.73 |
June | 23.87 | 18.63 |
July | 23.90 | 22.03 |
August | 23.89 | 20.69 |
September | 23.85 | 16.55 |
October | 23.11 | 9.72 |
November | 22.22 | 6.03 |
December | 21.22 | -2.2 |
Annual Sum or Average | 22.74 | 9.05 |
Minimum of Months | 21.15 | -4.2 |
Maximum of Months | 23.90 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.17 | -3.4 |
February | 12.47 | -4.2 |
March | 15.92 | 2.67 |
April | 17.86 | 7.47 |
May | 20.74 | 13.73 |
June | 22.71 | 18.63 |
July | 23.92 | 22.03 |
August | 23.48 | 20.69 |
September | 21.88 | 16.55 |
October | 18.79 | 9.72 |
November | 16.78 | 6.03 |
December | 13.18 | -2.2 |
Annual Sum or Average | 18.44 | 9.05 |
Minimum of Months | 12.47 | -4.2 |
Maximum of Months | 23.92 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.38 | 2.67 |
April | 19.83 | 7.47 |
May | 21.85 | 13.73 |
June | 22.98 | 18.63 |
July | 23.28 | 22.03 |
August | 23.20 | 20.69 |
September | 22.55 | 16.55 |
October | 20.27 | 9.72 |
November | 19.27 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.79 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.28 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.57 | -3.4 |
February | 20.55 | -4.2 |
March | 20.89 | 2.67 |
April | 21.24 | 7.47 |
May | 21.68 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.73 | 16.55 |
October | 21.36 | 9.72 |
November | 21.05 | 6.03 |
December | 20.61 | -2.2 |
Annual Sum or Average | 21.25 | 9.05 |
Minimum of Months | 20.55 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -3.4 |
February | 20.57 | -4.2 |
March | 20.93 | 2.67 |
April | 21.29 | 7.47 |
May | 21.69 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.40 | 9.72 |
November | 21.10 | 6.03 |
December | 20.64 | -2.2 |
Annual Sum or Average | 21.27 | 9.05 |
Minimum of Months | 20.57 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -3.4 |
February | 20.57 | -4.2 |
March | 20.94 | 2.67 |
April | 21.32 | 7.47 |
May | 21.70 | 13.73 |
June | 21.74 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.43 | 9.72 |
November | 21.13 | 6.03 |
December | 20.65 | -2.2 |
Annual Sum or Average | 21.28 | 9.05 |
Minimum of Months | 20.57 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -3.4 |
February | 20.48 | -4.2 |
March | 20.76 | 2.67 |
April | 21.06 | 7.47 |
May | 21.59 | 13.73 |
June | 21.73 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.70 | 16.55 |
October | 21.20 | 9.72 |
November | 20.86 | 6.03 |
December | 20.51 | -2.2 |
Annual Sum or Average | 21.16 | 9.05 |
Minimum of Months | 20.48 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -3.4 |
February | 20.60 | -4.2 |
March | 21.06 | 2.67 |
April | 21.39 | 7.47 |
May | 21.71 | 13.73 |
June | 21.74 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.53 | 9.72 |
November | 21.24 | 6.03 |
December | 20.67 | -2.2 |
Annual Sum or Average | 21.32 | 9.05 |
Minimum of Months | 20.60 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.27 | -3.4 |
February | 22.09 | -4.2 |
March | 22.89 | 2.67 |
April | 23.22 | 7.47 |
May | 23.33 | 13.73 |
June | 23.33 | 18.63 |
July | 23.33 | 22.03 |
August | 23.33 | 20.69 |
September | 23.33 | 16.55 |
October | 23.28 | 9.72 |
November | 23.17 | 6.03 |
December | 22.34 | -2.2 |
Annual Sum or Average | 23.00 | 9.05 |
Minimum of Months | 22.09 | -4.2 |
Maximum of Months | 23.33 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.52 | -3.4 |
February | 29.27 | -4.2 |
March | 30.60 | 2.67 |
April | 31.32 | 7.47 |
May | 32.38 | 13.73 |
June | 32.96 | 18.63 |
July | 33.38 | 22.03 |
August | 33.29 | 20.69 |
September | 32.88 | 16.55 |
October | 31.76 | 9.72 |
November | 30.84 | 6.03 |
December | 29.49 | -2.2 |
Annual Sum or Average | 31.49 | 9.05 |
Minimum of Months | 29.27 | -4.2 |
Maximum of Months | 33.38 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | -3.4 |
February | 21.74 | -4.2 |
March | 21.89 | 2.67 |
April | 22.02 | 7.47 |
May | 22.29 | 13.73 |
June | 22.62 | 18.63 |
July | 22.94 | 22.03 |
August | 22.81 | 20.69 |
September | 22.55 | 16.55 |
October | 22.13 | 9.72 |
November | 21.87 | 6.03 |
December | 21.75 | -2.2 |
Annual Sum or Average | 22.20 | 9.05 |
Minimum of Months | 21.74 | -4.2 |
Maximum of Months | 22.94 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | -3.4 |
February | 20.78 | -4.2 |
March | 21.23 | 2.67 |
April | 21.50 | 7.47 |
May | 21.73 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.75 | 16.55 |
October | 21.61 | 9.72 |
November | 21.37 | 6.03 |
December | 20.82 | -2.2 |
Annual Sum or Average | 21.41 | 9.05 |
Minimum of Months | 20.78 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -3.4 |
February | 20.61 | -4.2 |
March | 21.05 | 2.67 |
April | 21.37 | 7.47 |
May | 21.71 | 13.73 |
June | 21.75 | 18.63 |
July | 21.76 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.52 | 9.72 |
November | 21.22 | 6.03 |
December | 20.66 | -2.2 |
Annual Sum or Average | 21.32 | 9.05 |
Minimum of Months | 20.61 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.82 | -3.4 |
February | 16.34 | -4.2 |
March | 18.91 | 2.67 |
April | 20.40 | 7.47 |
May | 22.41 | 13.73 |
June | 23.71 | 18.63 |
July | 24.60 | 22.03 |
August | 24.37 | 20.69 |
September | 23.38 | 16.55 |
October | 21.19 | 9.72 |
November | 19.58 | 6.03 |
December | 16.80 | -2.2 |
Annual Sum or Average | 20.73 | 9.05 |
Minimum of Months | 16.34 | -4.2 |
Maximum of Months | 24.60 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.53 | -3.4 |
February | 11.73 | -4.2 |
March | 15.90 | 2.67 |
April | 18.27 | 7.47 |
May | 21.49 | 13.73 |
June | 23.68 | 18.63 |
July | 25.24 | 22.03 |
August | 24.76 | 20.69 |
September | 23.02 | 16.55 |
October | 19.46 | 9.72 |
November | 16.99 | 6.03 |
December | 12.48 | -2.2 |
Annual Sum or Average | 18.83 | 9.05 |
Minimum of Months | 11.73 | -4.2 |
Maximum of Months | 25.24 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.15 | -3.4 |
February | 12.43 | -4.2 |
March | 16.29 | 2.67 |
April | 18.38 | 7.47 |
May | 21.40 | 13.73 |
June | 23.43 | 18.63 |
July | 24.77 | 22.03 |
August | 24.35 | 20.69 |
September | 22.72 | 16.55 |
October | 19.39 | 9.72 |
November | 17.14 | 6.03 |
December | 13.12 | -2.2 |
Annual Sum or Average | 18.92 | 9.05 |
Minimum of Months | 12.43 | -4.2 |
Maximum of Months | 24.77 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -3.4 |
February | 21.11 | -4.2 |
March | 21.40 | 2.67 |
April | 21.72 | 7.47 |
May | 23.12 | 13.73 |
June | 23.74 | 18.63 |
July | 23.88 | 22.03 |
August | 23.86 | 20.69 |
September | 23.54 | 16.55 |
October | 22.00 | 9.72 |
November | 21.33 | 6.03 |
December | 21.11 | -2.2 |
Annual Sum or Average | 22.33 | 9.05 |
Minimum of Months | 21.11 | -4.2 |
Maximum of Months | 23.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.82 | -3.4 |
February | 11.11 | -4.2 |
March | 14.83 | 2.67 |
April | 16.94 | 7.47 |
May | 20.35 | 13.73 |
June | 22.76 | 18.63 |
July | 24.18 | 22.03 |
August | 23.66 | 20.69 |
September | 21.70 | 16.55 |
October | 17.92 | 9.72 |
November | 15.68 | 6.03 |
December | 11.84 | -2.2 |
Annual Sum or Average | 17.77 | 9.05 |
Minimum of Months | 11.11 | -4.2 |
Maximum of Months | 24.18 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.24 | 2.67 |
April | 19.43 | 7.47 |
May | 21.41 | 13.73 |
June | 22.84 | 18.63 |
July | 23.26 | 22.03 |
August | 23.13 | 20.69 |
September | 22.24 | 16.55 |
October | 19.75 | 9.72 |
November | 19.07 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.60 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.26 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.30 | 2.67 |
April | 19.57 | 7.47 |
May | 21.61 | 13.73 |
June | 22.92 | 18.63 |
July | 23.28 | 22.03 |
August | 23.18 | 20.69 |
September | 22.35 | 16.55 |
October | 19.95 | 9.72 |
November | 19.14 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.67 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.28 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.33 | 2.67 |
April | 19.68 | 7.47 |
May | 21.70 | 13.73 |
June | 22.92 | 18.63 |
July | 23.27 | 22.03 |
August | 23.17 | 20.69 |
September | 22.38 | 16.55 |
October | 20.06 | 9.72 |
November | 19.19 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.71 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.27 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -3.4 |
February | 20.54 | -4.2 |
March | 20.87 | 2.67 |
April | 21.24 | 7.47 |
May | 21.67 | 13.73 |
June | 21.74 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.72 | 16.55 |
October | 21.34 | 9.72 |
November | 21.03 | 6.03 |
December | 20.59 | -2.2 |
Annual Sum or Average | 21.24 | 9.05 |
Minimum of Months | 20.54 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.27 | 2.67 |
April | 19.53 | 7.47 |
May | 21.51 | 13.73 |
June | 22.84 | 18.63 |
July | 23.27 | 22.03 |
August | 23.16 | 20.69 |
September | 22.29 | 16.55 |
October | 19.89 | 9.72 |
November | 19.12 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.64 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.27 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -3.4 |
February | 20.52 | -4.2 |
March | 20.88 | 2.67 |
April | 21.22 | 7.47 |
May | 21.66 | 13.73 |
June | 21.73 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.72 | 16.55 |
October | 21.38 | 9.72 |
November | 21.03 | 6.03 |
December | 20.56 | -2.2 |
Annual Sum or Average | 21.23 | 9.05 |
Minimum of Months | 20.52 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | -3.4 |
February | 20.80 | -4.2 |
March | 21.27 | 2.67 |
April | 21.53 | 7.47 |
May | 21.74 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.75 | 16.55 |
October | 21.63 | 9.72 |
November | 21.41 | 6.03 |
December | 20.85 | -2.2 |
Annual Sum or Average | 21.42 | 9.05 |
Minimum of Months | 20.80 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | -3.4 |
February | 20.79 | -4.2 |
March | 22.46 | 2.67 |
April | 23.40 | 7.47 |
May | 24.89 | 13.73 |
June | 25.68 | 18.63 |
July | 26.12 | 22.03 |
August | 26.00 | 20.69 |
September | 25.45 | 16.55 |
October | 23.89 | 9.72 |
November | 22.74 | 6.03 |
December | 21.02 | -2.2 |
Annual Sum or Average | 23.64 | 9.05 |
Minimum of Months | 20.79 | -4.2 |
Maximum of Months | 26.12 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.53 | -3.4 |
February | 19.46 | -4.2 |
March | 21.00 | 2.67 |
April | 22.07 | 7.47 |
May | 23.13 | 13.73 |
June | 23.30 | 18.63 |
July | 23.33 | 22.03 |
August | 23.33 | 20.69 |
September | 23.27 | 16.55 |
October | 22.49 | 9.72 |
November | 21.50 | 6.03 |
December | 19.67 | -2.2 |
Annual Sum or Average | 21.85 | 9.05 |
Minimum of Months | 19.46 | -4.2 |
Maximum of Months | 23.33 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | -3.4 |
February | 20.67 | -4.2 |
March | 21.11 | 2.67 |
April | 21.41 | 7.47 |
May | 21.71 | 13.73 |
June | 21.74 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.52 | 9.72 |
November | 21.25 | 6.03 |
December | 20.71 | -2.2 |
Annual Sum or Average | 21.34 | 9.05 |
Minimum of Months | 20.67 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -3.4 |
February | 18.90 | -4.2 |
March | 19.57 | 2.67 |
April | 20.38 | 7.47 |
May | 22.17 | 13.73 |
June | 23.01 | 18.63 |
July | 23.28 | 22.03 |
August | 23.23 | 20.69 |
September | 22.79 | 16.55 |
October | 20.97 | 9.72 |
November | 19.68 | 6.03 |
December | 18.91 | -2.2 |
Annual Sum or Average | 20.99 | 9.05 |
Minimum of Months | 18.90 | -4.2 |
Maximum of Months | 23.28 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.50 | -3.4 |
February | 15.06 | -4.2 |
March | 17.86 | 2.67 |
April | 19.61 | 7.47 |
May | 22.13 | 13.73 |
June | 23.78 | 18.63 |
July | 24.84 | 22.03 |
August | 24.54 | 20.69 |
September | 23.27 | 16.55 |
October | 20.46 | 9.72 |
November | 18.53 | 6.03 |
December | 15.48 | -2.2 |
Annual Sum or Average | 20.12 | 9.05 |
Minimum of Months | 15.06 | -4.2 |
Maximum of Months | 24.84 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.25 | -3.4 |
February | 10.59 | -4.2 |
March | 14.95 | 2.67 |
April | 17.59 | 7.47 |
May | 21.27 | 13.73 |
June | 23.76 | 18.63 |
July | 25.49 | 22.03 |
August | 24.93 | 20.69 |
September | 22.93 | 16.55 |
October | 18.82 | 9.72 |
November | 16.07 | 6.03 |
December | 11.24 | -2.2 |
Annual Sum or Average | 18.28 | 9.05 |
Minimum of Months | 10.59 | -4.2 |
Maximum of Months | 25.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.72 | -3.4 |
February | 11.19 | -4.2 |
March | 15.19 | 2.67 |
April | 17.57 | 7.47 |
May | 21.04 | 13.73 |
June | 23.49 | 18.63 |
July | 25.04 | 22.03 |
August | 24.47 | 20.69 |
September | 22.45 | 16.55 |
October | 18.51 | 9.72 |
November | 15.97 | 6.03 |
December | 11.76 | -2.2 |
Annual Sum or Average | 18.24 | 9.05 |
Minimum of Months | 11.19 | -4.2 |
Maximum of Months | 25.04 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -3.4 |
February | 21.11 | -4.2 |
March | 21.32 | 2.67 |
April | 21.60 | 7.47 |
May | 22.64 | 13.73 |
June | 23.44 | 18.63 |
July | 23.79 | 22.03 |
August | 23.65 | 20.69 |
September | 23.04 | 16.55 |
October | 21.68 | 9.72 |
November | 21.24 | 6.03 |
December | 21.11 | -2.2 |
Annual Sum or Average | 22.15 | 9.05 |
Minimum of Months | 21.11 | -4.2 |
Maximum of Months | 23.79 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.74 | -3.4 |
February | 10.10 | -4.2 |
March | 14.06 | 2.67 |
April | 16.40 | 7.47 |
May | 20.08 | 13.73 |
June | 22.81 | 18.63 |
July | 24.40 | 22.03 |
August | 23.74 | 20.69 |
September | 21.45 | 16.55 |
October | 17.26 | 9.72 |
November | 14.86 | 6.03 |
December | 10.82 | -2.2 |
Annual Sum or Average | 17.27 | 9.05 |
Minimum of Months | 10.10 | -4.2 |
Maximum of Months | 24.40 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -3.4 |
February | 20.47 | -4.2 |
March | 20.66 | 2.67 |
April | 21.01 | 7.47 |
May | 21.60 | 13.73 |
June | 21.73 | 18.63 |
July | 21.76 | 22.03 |
August | 21.75 | 20.69 |
September | 21.67 | 16.55 |
October | 21.01 | 9.72 |
November | 20.66 | 6.03 |
December | 20.48 | -2.2 |
Annual Sum or Average | 21.11 | 9.05 |
Minimum of Months | 20.47 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.22 | 2.67 |
April | 19.52 | 7.47 |
May | 21.24 | 13.73 |
June | 22.65 | 18.63 |
July | 23.15 | 22.03 |
August | 22.95 | 20.69 |
September | 21.92 | 16.55 |
October | 19.68 | 9.72 |
November | 19.07 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.52 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.15 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.23 | 2.67 |
April | 19.57 | 7.47 |
May | 21.29 | 13.73 |
June | 22.64 | 18.63 |
July | 23.14 | 22.03 |
August | 22.94 | 20.69 |
September | 21.92 | 16.55 |
October | 19.73 | 9.72 |
November | 19.09 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.53 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.14 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -3.4 |
February | 20.50 | -4.2 |
March | 20.83 | 2.67 |
April | 21.27 | 7.47 |
May | 21.69 | 13.73 |
June | 21.74 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.72 | 16.55 |
October | 21.31 | 9.72 |
November | 20.92 | 6.03 |
December | 20.53 | -2.2 |
Annual Sum or Average | 21.21 | 9.05 |
Minimum of Months | 20.50 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.89 | -4.2 |
March | 19.21 | 2.67 |
April | 19.49 | 7.47 |
May | 21.22 | 13.73 |
June | 22.63 | 18.63 |
July | 23.15 | 22.03 |
August | 22.96 | 20.69 |
September | 21.96 | 16.55 |
October | 19.67 | 9.72 |
November | 19.06 | 6.03 |
December | 18.89 | -2.2 |
Annual Sum or Average | 20.51 | 9.05 |
Minimum of Months | 18.89 | -4.2 |
Maximum of Months | 23.15 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -3.4 |
February | 18.90 | -4.2 |
March | 19.40 | 2.67 |
April | 20.00 | 7.47 |
May | 21.65 | 13.73 |
June | 22.73 | 18.63 |
July | 23.17 | 22.03 |
August | 23.03 | 20.69 |
September | 22.30 | 16.55 |
October | 20.33 | 9.72 |
November | 19.35 | 6.03 |
December | 18.90 | -2.2 |
Annual Sum or Average | 20.73 | 9.05 |
Minimum of Months | 18.90 | -4.2 |
Maximum of Months | 23.17 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.61 | -3.4 |
February | 20.64 | -4.2 |
March | 21.14 | 2.67 |
April | 21.45 | 7.47 |
May | 21.71 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.53 | 9.72 |
November | 21.22 | 6.03 |
December | 20.65 | -2.2 |
Annual Sum or Average | 21.33 | 9.05 |
Minimum of Months | 20.61 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.68 | -3.4 |
February | 18.52 | -4.2 |
March | 20.27 | 2.67 |
April | 21.36 | 7.47 |
May | 22.99 | 13.73 |
June | 24.07 | 18.63 |
July | 24.66 | 22.03 |
August | 24.41 | 20.69 |
September | 23.54 | 16.55 |
October | 21.68 | 9.72 |
November | 20.45 | 6.03 |
December | 18.71 | -2.2 |
Annual Sum or Average | 21.63 | 9.05 |
Minimum of Months | 18.52 | -4.2 |
Maximum of Months | 24.66 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -3.4 |
February | 20.61 | -4.2 |
March | 21.08 | 2.67 |
April | 21.43 | 7.47 |
May | 21.71 | 13.73 |
June | 21.75 | 18.63 |
July | 21.76 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.51 | 9.72 |
November | 21.19 | 6.03 |
December | 20.63 | -2.2 |
Annual Sum or Average | 21.32 | 9.05 |
Minimum of Months | 20.59 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.59 | -3.4 |
February | 20.62 | -4.2 |
March | 21.10 | 2.67 |
April | 21.43 | 7.47 |
May | 21.71 | 13.73 |
June | 21.75 | 18.63 |
July | 21.75 | 22.03 |
August | 21.75 | 20.69 |
September | 21.74 | 16.55 |
October | 21.50 | 9.72 |
November | 21.18 | 6.03 |
December | 20.63 | -2.2 |
Annual Sum or Average | 21.32 | 9.05 |
Minimum of Months | 20.59 | -4.2 |
Maximum of Months | 21.75 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -3.4 |
February | 20.50 | -4.2 |
March | 20.85 | 2.67 |
April | 21.25 | 7.47 |
May | 21.67 | 13.73 |
June | 21.74 | 18.63 |
July | 21.76 | 22.03 |
August | 21.75 | 20.69 |
September | 21.72 | 16.55 |
October | 21.36 | 9.72 |
November | 20.96 | 6.03 |
December | 20.53 | -2.2 |
Annual Sum or Average | 21.22 | 9.05 |
Minimum of Months | 20.50 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.75 | -3.4 |
February | 14.46 | -4.2 |
March | 17.39 | 2.67 |
April | 19.33 | 7.47 |
May | 21.96 | 13.73 |
June | 23.78 | 18.63 |
July | 24.91 | 22.03 |
August | 24.48 | 20.69 |
September | 22.99 | 16.55 |
October | 20.01 | 9.72 |
November | 17.98 | 6.03 |
December | 14.83 | -2.2 |
Annual Sum or Average | 19.77 | 9.05 |
Minimum of Months | 14.46 | -4.2 |
Maximum of Months | 24.91 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.24 | -3.4 |
February | 9.88 | -4.2 |
March | 14.22 | 2.67 |
April | 17.12 | 7.47 |
May | 21.03 | 13.73 |
June | 23.77 | 18.63 |
July | 25.63 | 22.03 |
August | 24.93 | 20.69 |
September | 22.64 | 16.55 |
October | 18.21 | 9.72 |
November | 15.29 | 6.03 |
December | 10.40 | -2.2 |
Annual Sum or Average | 17.82 | 9.05 |
Minimum of Months | 9.88 | -4.2 |
Maximum of Months | 25.63 | 22.03 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:38
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.190174E+12 | 141503.822 | 24-JAN-07:15 | 15177.258 | 39465.561 | 8679.036 | 73873.396 | 112.458 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.176374E+12 | 156836.413 | 07-FEB-07:15 | 15177.258 | 39465.561 | 8691.876 | 89234.306 | 71.299 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.155744E+12 | 131573.714 | 07-MAR-07:15 | 15177.258 | 39465.561 | 8669.087 | 68097.645 | 156.050 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.129283E+12 | 101070.808 | 17-APR-06:15 | 15065.632 | 39465.561 | 8655.430 | 37636.012 | 240.059 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.132986E+12 | 83590.266 | 28-MAY-07:00 | 17641.054 | 43276.576 | 9048.930 | 0.000 | 13615.593 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.142289E+12 | 91539.612 | 17-JUN-07:00 | 17492.219 | 43276.576 | 9048.930 | 0.000 | 21713.774 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.159870E+12 | 101173.152 | 21-JUL-07:00 | 17492.219 | 43276.576 | 9048.930 | 0.000 | 31347.314 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.153775E+12 | 90047.310 | 26-AUG-07:00 | 17566.637 | 43276.576 | 9048.930 | 0.000 | 20147.055 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.137654E+12 | 92242.716 | 16-SEP-07:00 | 17566.637 | 43276.576 | 9048.930 | 0.000 | 22342.461 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.133635E+12 | 99516.209 | 17-OCT-06:15 | 15177.258 | 39465.561 | 8655.430 | 31553.329 | 468.518 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.136209E+12 | 100712.795 | 24-NOV-07:15 | 13316.689 | 34010.661 | 8655.430 | 40327.474 | 206.428 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.185352E+12 | 146806.550 | 11-DEC-07:15 | 15177.258 | 39465.561 | 8674.729 | 79176.294 | 116.594 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.183335E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.129283E+12 | 83590.266 | 13316.689 | 34010.661 | 8655.430 | 0.000 | 71.299 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.190174E+12 | 156836.413 | 17641.054 | 43276.576 | 9048.930 | 89234.306 | 31347.314 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:38
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.124629E+12 | 115725.828 | 31-JAN-11:15 | 16138.151 | 40096.028 | 0.000 | 59491.649 | 59491.649 | 59491.649 | 16138.151 |
February | 0.115343E+12 | 120958.971 | 06-FEB-10:45 | 21146.398 | 40096.028 | 0.000 | 59716.545 | 59716.545 | 59716.545 | 21146.398 |
March | 0.113062E+12 | 113279.579 | 04-MAR-10:00 | 13599.874 | 40096.028 | 0.000 | 59583.678 | 59583.678 | 59583.678 | 13599.874 |
April | 0.979686E+11 | 103748.054 | 14-APR-10:00 | 5945.535 | 40096.028 | 0.000 | 57706.491 | 57706.491 | 57706.491 | 5945.535 |
May | 0.925900E+11 | 98308.358 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 58212.330 | 58212.330 | 58212.330 | 0.000 |
June | 0.854577E+11 | 95482.349 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 55386.321 | 55386.321 | 55386.321 | 0.000 |
July | 0.855992E+11 | 92389.007 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 52292.979 | 52292.979 | 52292.979 | 0.000 |
August | 0.847147E+11 | 91538.364 | 12-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 51442.336 | 51442.336 | 51442.336 | 0.000 |
September | 0.831044E+11 | 92318.272 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 52222.244 | 52222.244 | 52222.244 | 0.000 |
October | 0.918889E+11 | 98383.700 | 24-OCT-09:15 | 4873.226 | 40096.028 | 0.000 | 53414.446 | 53414.446 | 53414.446 | 4873.226 |
November | 0.969387E+11 | 100855.205 | 12-NOV-10:15 | 5433.111 | 40096.028 | 0.000 | 55326.066 | 55326.066 | 55326.066 | 5433.111 |
December | 0.119769E+12 | 114576.317 | 28-DEC-10:00 | 16154.895 | 40096.028 | 0.000 | 58325.394 | 58325.394 | 58325.394 | 16154.895 |
Annual Sum or Average | 0.119107E+13 | 0.000 | ||||||||
Minimum of Months | 0.831044E+11 | 91538.364 | 0.000 | 40096.028 | 0.000 | 51442.336 | 51442.336 | 51442.336 | 0.000 | |
Maximum of Months | 0.124629E+12 | 120958.971 | 21146.398 | 40096.028 | 0.000 | 59716.545 | 59716.545 | 59716.545 | 21146.398 |