Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2018-10-19 10:15:41
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2652.10 | 660.78 | 711.96 |
Net Site Energy | 2652.10 | 660.78 | 711.96 |
Total Source Energy | 6345.19 | 1580.93 | 1703.36 |
Net Source Energy | 6345.19 | 1580.93 | 1703.36 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 5.97 | 6.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 306.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 277.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 558.18 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1666.02 | 986.08 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 5.97 | 6.42 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 306.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 277.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 558.18 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 158.63 | 151.57 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 447.24 | 264.71 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.23 | 140.67 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 415.09 | 245.69 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1666.02 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1666.02 | 100.00 |
Total On-Site and Utility Electric Sources | 1666.02 | 100.00 |
Total Electricity End Uses | 1666.02 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 113.75 |
Time Setpoint Not Met During Occupied Cooling | 3890.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3765.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.848 | 0.287 | 0.200 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.62_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.848 | 0.287 | 0.200 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 96.82 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 87.38 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5667.61 | 4327.80 | 1339.81 | 0.76 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15391.37 | 11194.43 | 4196.94 | 0.73 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7839.27 | 5496.41 | 2342.86 | 0.70 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12602.50 | 9635.09 | 2967.42 | 0.76 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5427.2 | 3.21 | 10.97 | 11.62 | 10.85 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14809.4 | 3.28 | 11.19 | 11.86 | 11.19 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7568.9 | 3.33 | 11.36 | 12.04 | 11.44 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12066.4 | 3.21 | 10.96 | 11.61 | 10.84 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.42 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 12025.56 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.35 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.42 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2127.50 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2378.12 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.35 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.42 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2127.50 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2378.12 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.35 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.42 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2127.50 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 750.16 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2378.12 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3000.65 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 828.26 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 783.04 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 750.11 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3000.44 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 754.81 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 315.35 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3088.84 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 12946.79 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6932.91 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5194.69 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.31 | 346.94 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.75 | 829.69 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 389.75 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.69 | 773.62 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7434.20 | 8921.04 | 0.624 | 0.749 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30 | 0.00820 |
RESTROOMFLR1 | 413.57 | 496.29 | 0.035 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 30.59 | 0.00820 |
MEETINGROOMFLR1 | 3449.57 | 4139.48 | 0.290 | 0.348 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30 | 0.00820 |
GUESTROOM101 | 523.12 | 627.74 | 0.061 | 0.073 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
GUESTROOM102 | 423.41 | 508.09 | 0.049 | 0.059 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
GUESTROOM103 | 1002.04 | 1202.45 | 0.117 | 0.140 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
GUESTROOM104 | 1152.25 | 1382.70 | 0.134 | 0.161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 31.30 | 0.00820 |
GUESTROOM105 | 1502.74 | 1803.29 | 0.175 | 0.210 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
EMPLOYEELOUNGEFLR1 | 5311.38 | 6373.66 | 0.446 | 0.536 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
EXERCISECENTERFLR1 | 1126.56 | 1351.87 | 0.095 | 0.114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05 | 0.00820 |
FRONTOFFICEFLR1 | 3075.15 | 3690.18 | 0.258 | 0.310 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM201 | 737.24 | 884.69 | 0.086 | 0.103 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:45:00 | 30.68 | 0.00820 |
GUESTROOM202_205 | 3932.35 | 4718.81 | 0.459 | 0.551 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
GUESTROOM206_208 | 3169.30 | 3803.16 | 0.370 | 0.444 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
GUESTROOM209_212 | 3739.73 | 4487.68 | 0.436 | 0.524 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
GUESTROOM213 | 1052.03 | 1262.44 | 0.123 | 0.147 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
GUESTROOM214 | 1256.47 | 1507.76 | 0.147 | 0.176 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
GUESTROOM215_218 | 9332.36 | 11198.83 | 1.089 | 1.307 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM219 | 5344.74 | 6413.69 | 0.624 | 0.749 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
GUESTROOM220_223 | 4387.26 | 5264.71 | 0.512 | 0.614 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM224 | 1251.60 | 1501.92 | 0.146 | 0.175 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM301 | 548.37 | 658.05 | 0.064 | 0.077 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
GUESTROOM302_305 | 1342.92 | 1611.50 | 0.157 | 0.188 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 30.90 | 0.00820 |
GUESTROOM306_308 | 1172.21 | 1406.66 | 0.137 | 0.164 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 30.90 | 0.00820 |
GUESTROOM309_312 | 3668.72 | 4402.46 | 0.428 | 0.514 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 30.90 | 0.00820 |
GUESTROOM313 | 545.21 | 654.25 | 0.064 | 0.076 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
GUESTROOM314 | 1165.80 | 1398.96 | 0.136 | 0.163 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 31.30 | 0.00820 |
GUESTROOM315_318 | 4755.74 | 5706.89 | 0.555 | 0.666 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM319 | 1045.46 | 1254.55 | 0.122 | 0.146 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM320_323 | 4150.27 | 4980.33 | 0.484 | 0.581 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM324 | 674.97 | 809.97 | 0.079 | 0.095 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
GUESTROOM401 | 1306.33 | 1567.59 | 0.152 | 0.183 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 30.97 | 0.00820 |
GUESTROOM402_405 | 1837.87 | 2205.45 | 0.214 | 0.257 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM406_408 | 1576.18 | 1891.41 | 0.184 | 0.221 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM409_412 | 4462.09 | 5354.50 | 0.521 | 0.625 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM413 | 719.95 | 863.94 | 0.084 | 0.101 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 31.17 | 0.00820 |
GUESTROOM414 | 867.81 | 1041.37 | 0.101 | 0.122 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
GUESTROOM415_418 | 5116.64 | 6139.97 | 0.597 | 0.717 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 31.19 | 0.00820 |
GUESTROOM419 | 1403.90 | 1684.67 | 0.164 | 0.197 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30 | 0.00820 |
GUESTROOM420_423 | 5083.86 | 6100.63 | 0.593 | 0.712 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 31.19 | 0.00820 |
GUESTROOM424 | 1423.98 | 1708.77 | 0.166 | 0.199 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 31.30 | 0.00820 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
CORRIDORFLR1 | 14385.09 | 17262.11 | 1.207 | 1.449 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
CORRIDORFLR2 | 2538.90 | 3046.68 | 0.213 | 0.256 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 30.41 | 0.00820 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
CORRIDORFLR3 | 1128.83 | 1354.59 | 0.095 | 0.114 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 30.23 | 0.00820 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 | |
CORRIDORFLR4 | 1691.85 | 2030.22 | 0.142 | 0.170 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30 | 0.00820 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 0.00820 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 880.43 | 1056.51 | 0.025 | 0.236 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | 3.80 | 0.00506 |
RESTROOMFLR1 | 13.82 | 16.58 | 0.000 | 0.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 3.80 | 0.00506 |
MEETINGROOMFLR1 | 271.36 | 325.64 | 0.008 | 0.126 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 3.80 | 0.00506 |
GUESTROOM101 | 110.85 | 133.02 | 0.003 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 3.80 | 0.00506 |
GUESTROOM102 | 151.51 | 181.81 | 0.004 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 3.80 | 0.00506 |
GUESTROOM103 | 265.13 | 318.16 | 0.008 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 3.80 | 0.00506 |
GUESTROOM104 | 250.49 | 300.59 | 0.007 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 3.80 | 0.00506 |
GUESTROOM105 | 149.46 | 179.35 | 0.004 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | 3.80 | 0.00506 |
EMPLOYEELOUNGEFLR1 | 117.10 | 140.52 | 0.003 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80 | 0.00506 |
EXERCISECENTERFLR1 | 59.33 | 71.20 | 0.002 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 3.80 | 0.00506 |
FRONTOFFICEFLR1 | 529.75 | 635.70 | 0.015 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 3.80 | 0.00506 |
GUESTROOM201 | 236.85 | 284.22 | 0.007 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 3.80 | 0.00506 |
GUESTROOM202_205 | 506.39 | 607.66 | 0.015 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | 3.80 | 0.00506 |
GUESTROOM206_208 | 373.50 | 448.20 | 0.011 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80 | 0.00506 |
GUESTROOM209_212 | 435.37 | 522.45 | 0.013 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
GUESTROOM213 | 265.34 | 318.41 | 0.008 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 3.80 | 0.00506 |
GUESTROOM214 | 233.39 | 280.07 | 0.007 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | 3.80 | 0.00506 |
GUESTROOM215_218 | 400.09 | 480.11 | 0.011 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
GUESTROOM219 | 66.34 | 79.61 | 0.002 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 3.80 | 0.00506 |
GUESTROOM220_223 | 404.57 | 485.49 | 0.012 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | 3.80 | 0.00506 |
GUESTROOM224 | 201.00 | 241.20 | 0.006 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 3.80 | 0.00506 |
GUESTROOM301 | 261.95 | 314.34 | 0.008 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:45:00 | 3.80 | 0.00506 |
GUESTROOM302_305 | 584.41 | 701.29 | 0.017 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | 3.80 | 0.00506 |
GUESTROOM306_308 | 493.15 | 591.79 | 0.014 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 14:30:00 | 3.80 | 0.00506 |
GUESTROOM309_312 | 576.06 | 691.27 | 0.017 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | 3.80 | 0.00506 |
GUESTROOM313 | 307.62 | 369.14 | 0.009 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:30:00 | 3.80 | 0.00506 |
GUESTROOM314 | 270.82 | 324.98 | 0.008 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 15:45:00 | 3.80 | 0.00506 |
GUESTROOM315_318 | 558.93 | 670.72 | 0.016 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | 3.80 | 0.00506 |
GUESTROOM319 | 140.97 | 169.16 | 0.004 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | 3.80 | 0.00506 |
GUESTROOM320_323 | 535.44 | 642.52 | 0.015 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:45:00 | 3.80 | 0.00506 |
GUESTROOM324 | 244.85 | 293.82 | 0.007 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | 3.80 | 0.00506 |
GUESTROOM401 | 390.39 | 468.47 | 0.011 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:45:00 | 3.80 | 0.00506 |
GUESTROOM402_405 | 1037.23 | 1244.68 | 0.030 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 22:15:00 | 3.80 | 0.00506 |
GUESTROOM406_408 | 874.20 | 1049.03 | 0.025 | 0.043 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | 3.80 | 0.00506 |
GUESTROOM409_412 | 1040.93 | 1249.11 | 0.030 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 3.80 | 0.00506 |
GUESTROOM413 | 455.98 | 547.17 | 0.013 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80 | 0.00506 |
GUESTROOM414 | 418.31 | 501.97 | 0.012 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 21:00:00 | 3.80 | 0.00506 |
GUESTROOM415_418 | 1029.28 | 1235.14 | 0.030 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | 3.80 | 0.00506 |
GUESTROOM419 | 295.01 | 354.01 | 0.008 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | 3.80 | 0.00506 |
GUESTROOM420_423 | 1000.17 | 1200.20 | 0.029 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 3.80 | 0.00506 |
GUESTROOM424 | 394.79 | 473.75 | 0.011 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 3.80 | 0.00506 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
CORRIDORFLR1 | 9223.16 | 11067.79 | 0.265 | 0.318 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80 | 0.00506 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
CORRIDORFLR2 | 63.33 | 75.99 | 0.002 | 0.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 3.80 | 0.00506 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
CORRIDORFLR3 | 205.28 | 246.34 | 0.006 | 0.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | 3.80 | 0.00506 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
CORRIDORFLR4 | 774.65 | 929.58 | 0.022 | 0.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 23:45:00 | 3.80 | 0.00506 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.31 | 0.31 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.75 | 0.75 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.35 | 0.35 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.69 | 0.69 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1649.50 | 5804.75 | 487.50 |
RESTROOMFLR1 | 105.50 | 7813.50 | 4.75 |
MEETINGROOMFLR1 | 1255.50 | 2128.25 | 190.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 17.50 | 8760.00 | 17.50 |
GUESTROOM104 | 6.25 | 8756.75 | 6.25 |
GUESTROOM105 | 0.00 | 8325.75 | 0.00 |
EMPLOYEELOUNGEFLR1 | 2920.75 | 2152.25 | 203.25 |
EXERCISECENTERFLR1 | 1844.50 | 902.00 | 2.00 |
FRONTOFFICEFLR1 | 819.50 | 4562.00 | 14.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 2.75 | 8625.50 | 2.75 |
GUESTROOM206_208 | 0.75 | 8650.50 | 0.75 |
GUESTROOM209_212 | 3.00 | 8752.25 | 3.00 |
GUESTROOM213 | 7.00 | 8760.00 | 7.00 |
GUESTROOM214 | 0.00 | 8584.50 | 0.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5195.75 | 2950.50 | 50.25 |
GUESTROOM220_223 | 0.00 | 8274.50 | 0.00 |
GUESTROOM224 | 0.00 | 8530.50 | 0.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 7.75 | 8754.25 | 7.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 4.25 | 8627.75 | 4.25 |
GUESTROOM315_318 | 0.00 | 7979.75 | 0.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 3.00 | 8476.00 | 3.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 190.50 | 7923.00 | 145.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 82.50 | 7819.50 | 14.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 414.00 | 6983.75 | 0.00 |
GUESTROOM419 | 61.50 | 7345.75 | 0.00 |
GUESTROOM420_423 | 368.50 | 7049.25 | 0.00 |
GUESTROOM424 | 46.75 | 7620.25 | 3.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6221.00 | 8760.00 | 3765.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 422.50 | 0.00 | 422.50 |
MEETINGROOMFLR1 | 0.00 | 9.25 | 0.00 | 9.25 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 57.00 | 0.00 | 57.00 |
GUESTROOM104 | 0.00 | 76.75 | 0.00 | 76.75 |
GUESTROOM105 | 0.00 | 89.50 | 0.00 | 89.50 |
EMPLOYEELOUNGEFLR1 | 146.75 | 1265.75 | 113.75 | 493.50 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 21.25 | 0.00 | 21.25 |
GUESTROOM206_208 | 0.00 | 42.75 | 0.00 | 42.75 |
GUESTROOM209_212 | 0.00 | 18.25 | 0.00 | 18.25 |
GUESTROOM213 | 0.00 | 19.50 | 0.00 | 19.50 |
GUESTROOM214 | 0.00 | 36.50 | 0.00 | 36.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 3206.50 | 0.00 | 3206.50 |
GUESTROOM220_223 | 0.00 | 27.75 | 0.00 | 27.75 |
GUESTROOM224 | 0.00 | 35.75 | 0.00 | 35.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 18.00 | 0.00 | 18.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 31.50 | 0.00 | 31.50 |
GUESTROOM315_318 | 0.00 | 35.50 | 0.00 | 35.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 25.50 | 0.00 | 25.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 36.50 | 0.00 | 36.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 30.50 | 0.00 | 30.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 40.75 | 0.00 | 40.75 |
GUESTROOM419 | 0.00 | 51.25 | 0.00 | 51.25 |
GUESTROOM420_423 | 0.00 | 39.75 | 0.00 | 39.75 |
GUESTROOM424 | 0.00 | 45.75 | 0.00 | 45.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 4966.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 10.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 146.75 | 6224.50 | 113.75 | 3890.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:41
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.309737 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.749384 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.690669 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 315.42 |
CORRIDORFLR1 PTAC HEATING COIL | 12025.56 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 750.16 |
102 PTAC HEATING COIL | 750.16 |
103 PTAC HEATING COIL | 750.16 |
104 PTAC HEATING COIL | 750.11 |
105 PTAC HEATING COIL | 750.11 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 315.35 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 315.42 |
CORRIDORFLR2 PTAC HEATING COIL | 2127.50 |
201 PTAC HEATING COIL | 750.16 |
202_205 PTAC HEATING COIL | 3000.65 |
206_208 PTAC HEATING COIL | 2378.12 |
209_212 PTAC HEATING COIL | 3000.65 |
213 PTAC HEATING COIL | 750.16 |
214 PTAC HEATING COIL | 750.11 |
215_218 PTAC HEATING COIL | 3000.44 |
219 PTAC HEATING COIL | 750.11 |
220_223 PTAC HEATING COIL | 3000.44 |
224 PTAC HEATING COIL | 750.11 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 315.35 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 315.42 |
CORRIDORFLR3 PTAC HEATING COIL | 2127.50 |
301 PTAC HEATING COIL | 750.16 |
302_305 PTAC HEATING COIL | 3000.65 |
306_308 PTAC HEATING COIL | 2378.12 |
309_312 PTAC HEATING COIL | 3000.65 |
313 PTAC HEATING COIL | 750.16 |
314 PTAC HEATING COIL | 750.11 |
315_318 PTAC HEATING COIL | 3000.44 |
319 PTAC HEATING COIL | 750.11 |
320_323 PTAC HEATING COIL | 3000.44 |
324 PTAC HEATING COIL | 750.11 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 315.35 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 315.42 |
CORRIDORFLR4 PTAC HEATING COIL | 2127.50 |
401 PTAC HEATING COIL | 750.16 |
402_405 PTAC HEATING COIL | 3000.65 |
406_408 PTAC HEATING COIL | 2378.12 |
409_412 PTAC HEATING COIL | 3000.65 |
413 PTAC HEATING COIL | 828.26 |
414 PTAC HEATING COIL | 783.04 |
415_418 PTAC HEATING COIL | 3000.44 |
419 PTAC HEATING COIL | 750.11 |
420_423 PTAC HEATING COIL | 3000.44 |
424 PTAC HEATING COIL | 754.81 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 315.35 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.763602 | 0.309737 | 5667.61 |
SAC_FRONTLOUNGE COOLING COIL | 0.727319 | 0.749384 | 15391.37 |
SAC_MEETINGROOM COOLING COIL | 0.701138 | 0.347960 | 7839.27 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.764538 | 0.690669 | 12602.50 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.749384 |
RESTROOMFLR1 DIRECT AIR | 0.041649 |
MEETINGROOMFLR1 DIRECT AIR | 0.347960 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.535505 |
EXERCISECENTERFLR1 DIRECT AIR | 0.113514 |
FRONTOFFICEFLR1 DIRECT AIR | 0.309737 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.309737 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.749384 |
SAC_MEETINGROOM MAIN BRANCH | 0.347960 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.690669 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.309737 |
SAC_FRONTLOUNGE | 0.749384 |
SAC_MEETINGROOM | 0.347960 |
SAC_EXC_EMPLGE_RESTRM | 0.690669 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.309737 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.749384 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.347960 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.690669 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.309737 | 0.309737 | 0.309737 | 0.309737 | 3088.84 | 5667.61 | 1.00 |
SAC_FRONTLOUNGE | 0.749384 | 0.749384 | 0.749384 | 0.749384 | 12946.79 | 15391.37 | 1.00 |
SAC_MEETINGROOM | 0.347960 | 0.347960 | 0.347960 | 0.347960 | 6932.91 | 7839.27 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.690669 | 0.690669 | 0.690669 | 0.690669 | 5194.69 | 12602.50 | 0.164354 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3088.84 |
SAC_FRONTLOUNGE HEATING COIL | 12946.79 |
SAC_MEETINGROOM HEATING COIL | 6932.91 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5194.69 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.347960 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 13.22 |
February | 21.60 | 13.28 |
March | 21.48 | 12.64 |
April | 22.50 | 15.30 |
May | 22.37 | 15.56 |
June | 23.06 | 17.67 |
July | 23.68 | 19.43 |
August | 23.69 | 19.66 |
September | 23.40 | 18.47 |
October | 23.26 | 18.77 |
November | 22.19 | 14.32 |
December | 21.98 | 13.59 |
Annual Sum or Average | 22.60 | 16.01 |
Minimum of Months | 21.48 | 12.64 |
Maximum of Months | 23.69 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.15 | 13.22 |
February | 24.10 | 13.28 |
March | 24.07 | 12.64 |
April | 24.53 | 15.30 |
May | 24.54 | 15.56 |
June | 24.94 | 17.67 |
July | 25.36 | 19.43 |
August | 25.42 | 19.66 |
September | 25.10 | 18.47 |
October | 25.09 | 18.77 |
November | 24.33 | 14.32 |
December | 24.19 | 13.59 |
Annual Sum or Average | 24.66 | 16.01 |
Minimum of Months | 24.07 | 12.64 |
Maximum of Months | 25.42 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 13.22 |
February | 20.84 | 13.28 |
March | 20.83 | 12.64 |
April | 21.88 | 15.30 |
May | 21.97 | 15.56 |
June | 22.67 | 17.67 |
July | 23.22 | 19.43 |
August | 23.11 | 19.66 |
September | 22.70 | 18.47 |
October | 22.48 | 18.77 |
November | 21.30 | 14.32 |
December | 21.00 | 13.59 |
Annual Sum or Average | 21.91 | 16.01 |
Minimum of Months | 20.83 | 12.64 |
Maximum of Months | 23.22 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 13.22 |
February | 22.56 | 13.28 |
March | 22.48 | 12.64 |
April | 22.90 | 15.30 |
May | 23.01 | 15.56 |
June | 23.39 | 17.67 |
July | 23.65 | 19.43 |
August | 23.68 | 19.66 |
September | 23.50 | 18.47 |
October | 23.42 | 18.77 |
November | 22.76 | 14.32 |
December | 22.58 | 13.59 |
Annual Sum or Average | 23.04 | 16.01 |
Minimum of Months | 22.48 | 12.64 |
Maximum of Months | 23.68 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 13.22 |
February | 22.80 | 13.28 |
March | 22.78 | 12.64 |
April | 23.09 | 15.30 |
May | 23.21 | 15.56 |
June | 23.44 | 17.67 |
July | 23.57 | 19.43 |
August | 23.52 | 19.66 |
September | 23.38 | 18.47 |
October | 23.28 | 18.77 |
November | 22.87 | 14.32 |
December | 22.72 | 13.59 |
Annual Sum or Average | 23.11 | 16.01 |
Minimum of Months | 22.70 | 12.64 |
Maximum of Months | 23.57 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.13 | 13.22 |
February | 23.15 | 13.28 |
March | 23.09 | 12.64 |
April | 23.48 | 15.30 |
May | 23.55 | 15.56 |
June | 23.68 | 17.67 |
July | 23.75 | 19.43 |
August | 23.75 | 19.66 |
September | 23.69 | 18.47 |
October | 23.65 | 18.77 |
November | 23.34 | 14.32 |
December | 23.15 | 13.59 |
Annual Sum or Average | 23.45 | 16.01 |
Minimum of Months | 23.09 | 12.64 |
Maximum of Months | 23.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.49 | 13.22 |
February | 25.53 | 13.28 |
March | 25.51 | 12.64 |
April | 25.87 | 15.30 |
May | 26.02 | 15.56 |
June | 26.28 | 17.67 |
July | 26.48 | 19.43 |
August | 26.45 | 19.66 |
September | 26.27 | 18.47 |
October | 26.19 | 18.77 |
November | 25.72 | 14.32 |
December | 25.54 | 13.59 |
Annual Sum or Average | 25.95 | 16.01 |
Minimum of Months | 25.49 | 12.64 |
Maximum of Months | 26.48 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 13.22 |
February | 21.88 | 13.28 |
March | 21.79 | 12.64 |
April | 22.42 | 15.30 |
May | 22.58 | 15.56 |
June | 22.95 | 17.67 |
July | 23.16 | 19.43 |
August | 23.16 | 19.66 |
September | 22.98 | 18.47 |
October | 22.91 | 18.77 |
November | 22.14 | 14.32 |
December | 21.90 | 13.59 |
Annual Sum or Average | 22.48 | 16.01 |
Minimum of Months | 21.79 | 12.64 |
Maximum of Months | 23.16 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.22 |
February | 21.53 | 13.28 |
March | 21.45 | 12.64 |
April | 22.10 | 15.30 |
May | 22.27 | 15.56 |
June | 22.71 | 17.67 |
July | 22.97 | 19.43 |
August | 22.96 | 19.66 |
September | 22.73 | 18.47 |
October | 22.68 | 18.77 |
November | 21.81 | 14.32 |
December | 21.57 | 13.59 |
Annual Sum or Average | 22.19 | 16.01 |
Minimum of Months | 21.45 | 12.64 |
Maximum of Months | 22.97 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 13.22 |
February | 21.54 | 13.28 |
March | 21.52 | 12.64 |
April | 21.68 | 15.30 |
May | 21.70 | 15.56 |
June | 21.74 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.73 | 18.47 |
October | 21.73 | 18.77 |
November | 21.63 | 14.32 |
December | 21.59 | 13.59 |
Annual Sum or Average | 21.66 | 16.01 |
Minimum of Months | 21.52 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.22 |
February | 21.69 | 13.28 |
March | 21.66 | 12.64 |
April | 21.73 | 15.30 |
May | 21.73 | 15.56 |
June | 21.74 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.74 | 14.32 |
December | 21.73 | 13.59 |
Annual Sum or Average | 21.73 | 16.01 |
Minimum of Months | 21.66 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.74 | 13.28 |
March | 21.73 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.73 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 13.22 |
February | 22.41 | 13.28 |
March | 22.37 | 12.64 |
April | 22.48 | 15.30 |
May | 22.56 | 15.56 |
June | 22.64 | 17.67 |
July | 22.57 | 19.43 |
August | 22.51 | 19.66 |
September | 22.50 | 18.47 |
October | 22.38 | 18.77 |
November | 22.32 | 14.32 |
December | 22.21 | 13.59 |
Annual Sum or Average | 22.43 | 16.01 |
Minimum of Months | 22.21 | 12.64 |
Maximum of Months | 22.64 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 52.32 | 13.22 |
February | 52.13 | 13.28 |
March | 52.02 | 12.64 |
April | 52.27 | 15.30 |
May | 52.15 | 15.56 |
June | 52.36 | 17.67 |
July | 52.58 | 19.43 |
August | 52.69 | 19.66 |
September | 52.67 | 18.47 |
October | 52.72 | 18.77 |
November | 52.40 | 14.32 |
December | 52.37 | 13.59 |
Annual Sum or Average | 52.39 | 16.01 |
Minimum of Months | 52.02 | 12.64 |
Maximum of Months | 52.72 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.80 | 13.22 |
February | 69.56 | 13.28 |
March | 69.52 | 12.64 |
April | 69.87 | 15.30 |
May | 69.78 | 15.56 |
June | 70.08 | 17.67 |
July | 70.37 | 19.43 |
August | 70.43 | 19.66 |
September | 70.36 | 18.47 |
October | 70.32 | 18.77 |
November | 69.88 | 14.32 |
December | 69.82 | 13.59 |
Annual Sum or Average | 69.98 | 16.01 |
Minimum of Months | 69.52 | 12.64 |
Maximum of Months | 70.43 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.51 | 13.22 |
February | 23.57 | 13.28 |
March | 23.49 | 12.64 |
April | 23.68 | 15.30 |
May | 23.69 | 15.56 |
June | 23.83 | 17.67 |
July | 23.88 | 19.43 |
August | 23.88 | 19.66 |
September | 23.86 | 18.47 |
October | 23.82 | 18.77 |
November | 23.62 | 14.32 |
December | 23.53 | 13.59 |
Annual Sum or Average | 23.70 | 16.01 |
Minimum of Months | 23.49 | 12.64 |
Maximum of Months | 23.88 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.46 | 13.22 |
February | 23.54 | 13.28 |
March | 23.41 | 12.64 |
April | 23.70 | 15.30 |
May | 23.71 | 15.56 |
June | 23.86 | 17.67 |
July | 23.89 | 19.43 |
August | 23.89 | 19.66 |
September | 23.88 | 18.47 |
October | 23.83 | 18.77 |
November | 23.63 | 14.32 |
December | 23.50 | 13.59 |
Annual Sum or Average | 23.69 | 16.01 |
Minimum of Months | 23.41 | 12.64 |
Maximum of Months | 23.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 13.22 |
February | 21.65 | 13.28 |
March | 21.51 | 12.64 |
April | 22.63 | 15.30 |
May | 22.47 | 15.56 |
June | 23.23 | 17.67 |
July | 23.96 | 19.43 |
August | 24.06 | 19.66 |
September | 23.66 | 18.47 |
October | 23.63 | 18.77 |
November | 22.34 | 14.32 |
December | 22.14 | 13.59 |
Annual Sum or Average | 22.79 | 16.01 |
Minimum of Months | 21.51 | 12.64 |
Maximum of Months | 24.06 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.96 | 13.22 |
February | 22.75 | 13.28 |
March | 22.61 | 12.64 |
April | 23.22 | 15.30 |
May | 23.14 | 15.56 |
June | 23.54 | 17.67 |
July | 23.94 | 19.43 |
August | 24.04 | 19.66 |
September | 23.84 | 18.47 |
October | 23.87 | 18.77 |
November | 23.17 | 14.32 |
December | 23.03 | 13.59 |
Annual Sum or Average | 23.35 | 16.01 |
Minimum of Months | 22.61 | 12.64 |
Maximum of Months | 24.04 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 13.22 |
February | 22.01 | 13.28 |
March | 21.89 | 12.64 |
April | 23.04 | 15.30 |
May | 22.93 | 15.56 |
June | 23.70 | 17.67 |
July | 24.36 | 19.43 |
August | 24.33 | 19.66 |
September | 24.01 | 18.47 |
October | 23.84 | 18.77 |
November | 22.66 | 14.32 |
December | 22.42 | 13.59 |
Annual Sum or Average | 23.13 | 16.01 |
Minimum of Months | 21.89 | 12.64 |
Maximum of Months | 24.36 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.73 | 13.22 |
February | 23.78 | 13.28 |
March | 23.70 | 12.64 |
April | 23.87 | 15.30 |
May | 23.88 | 15.56 |
June | 23.89 | 17.67 |
July | 23.89 | 19.43 |
August | 23.89 | 19.66 |
September | 23.89 | 18.47 |
October | 23.89 | 18.77 |
November | 23.84 | 14.32 |
December | 23.76 | 13.59 |
Annual Sum or Average | 23.83 | 16.01 |
Minimum of Months | 23.70 | 12.64 |
Maximum of Months | 23.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 13.22 |
February | 20.80 | 13.28 |
March | 20.76 | 12.64 |
April | 22.04 | 15.30 |
May | 22.16 | 15.56 |
June | 22.99 | 17.67 |
July | 23.64 | 19.43 |
August | 23.49 | 19.66 |
September | 23.03 | 18.47 |
October | 22.78 | 18.77 |
November | 21.36 | 14.32 |
December | 21.00 | 13.59 |
Annual Sum or Average | 22.09 | 16.01 |
Minimum of Months | 20.76 | 12.64 |
Maximum of Months | 23.64 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 13.22 |
February | 21.62 | 13.28 |
March | 21.53 | 12.64 |
April | 22.50 | 15.30 |
May | 22.68 | 15.56 |
June | 23.11 | 17.67 |
July | 23.29 | 19.43 |
August | 23.28 | 19.66 |
September | 23.12 | 18.47 |
October | 22.99 | 18.77 |
November | 22.00 | 14.32 |
December | 21.62 | 13.59 |
Annual Sum or Average | 22.44 | 16.01 |
Minimum of Months | 21.53 | 12.64 |
Maximum of Months | 23.29 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 13.22 |
February | 21.70 | 13.28 |
March | 21.67 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.74 | 14.32 |
December | 21.70 | 13.59 |
Annual Sum or Average | 21.73 | 16.01 |
Minimum of Months | 21.67 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.22 |
February | 21.71 | 13.28 |
March | 21.68 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.74 | 14.32 |
December | 21.71 | 13.59 |
Annual Sum or Average | 21.73 | 16.01 |
Minimum of Months | 21.68 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.22 |
February | 21.72 | 13.28 |
March | 21.70 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.74 | 14.32 |
December | 21.72 | 13.59 |
Annual Sum or Average | 21.74 | 16.01 |
Minimum of Months | 21.70 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 13.22 |
February | 21.60 | 13.28 |
March | 21.57 | 12.64 |
April | 21.73 | 15.30 |
May | 21.74 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.69 | 14.32 |
December | 21.63 | 13.59 |
Annual Sum or Average | 21.69 | 16.01 |
Minimum of Months | 21.57 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.73 | 13.28 |
March | 21.71 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.71 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 13.22 |
February | 23.33 | 13.28 |
March | 23.33 | 12.64 |
April | 23.33 | 15.30 |
May | 23.33 | 15.56 |
June | 23.33 | 17.67 |
July | 23.33 | 19.43 |
August | 23.33 | 19.66 |
September | 23.33 | 18.47 |
October | 23.33 | 18.77 |
November | 23.33 | 14.32 |
December | 23.33 | 13.59 |
Annual Sum or Average | 23.33 | 16.01 |
Minimum of Months | 23.33 | 12.64 |
Maximum of Months | 23.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.70 | 13.22 |
February | 32.55 | 13.28 |
March | 32.47 | 12.64 |
April | 32.83 | 15.30 |
May | 32.77 | 15.56 |
June | 33.00 | 17.67 |
July | 33.21 | 19.43 |
August | 33.26 | 19.66 |
September | 33.20 | 18.47 |
October | 33.18 | 18.77 |
November | 32.80 | 14.32 |
December | 32.72 | 13.59 |
Annual Sum or Average | 32.89 | 16.01 |
Minimum of Months | 32.47 | 12.64 |
Maximum of Months | 33.26 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 13.22 |
February | 22.31 | 13.28 |
March | 22.29 | 12.64 |
April | 22.42 | 15.30 |
May | 22.38 | 15.56 |
June | 22.49 | 17.67 |
July | 22.63 | 19.43 |
August | 22.68 | 19.66 |
September | 22.62 | 18.47 |
October | 22.61 | 18.77 |
November | 22.37 | 14.32 |
December | 22.32 | 13.59 |
Annual Sum or Average | 22.46 | 16.01 |
Minimum of Months | 22.29 | 12.64 |
Maximum of Months | 22.68 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.75 | 13.28 |
March | 21.73 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.73 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.74 | 13.28 |
March | 21.71 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.71 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.97 | 13.22 |
February | 22.71 | 13.28 |
March | 22.56 | 12.64 |
April | 23.36 | 15.30 |
May | 23.27 | 15.56 |
June | 23.78 | 17.67 |
July | 24.29 | 19.43 |
August | 24.36 | 19.66 |
September | 24.08 | 18.47 |
October | 24.08 | 18.77 |
November | 23.21 | 14.32 |
December | 23.05 | 13.59 |
Annual Sum or Average | 23.48 | 16.01 |
Minimum of Months | 22.56 | 12.64 |
Maximum of Months | 24.36 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 13.22 |
February | 21.93 | 13.28 |
March | 21.82 | 12.64 |
April | 23.21 | 15.30 |
May | 23.08 | 15.56 |
June | 24.00 | 17.67 |
July | 24.87 | 19.43 |
August | 24.89 | 19.66 |
September | 24.36 | 18.47 |
October | 24.27 | 18.77 |
November | 22.73 | 14.32 |
December | 22.46 | 13.59 |
Annual Sum or Average | 23.34 | 16.01 |
Minimum of Months | 21.82 | 12.64 |
Maximum of Months | 24.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.04 | 13.22 |
February | 21.72 | 13.28 |
March | 21.58 | 12.64 |
April | 22.92 | 15.30 |
May | 22.84 | 15.56 |
June | 23.71 | 17.67 |
July | 24.46 | 19.43 |
August | 24.40 | 19.66 |
September | 24.02 | 18.47 |
October | 23.82 | 18.77 |
November | 22.43 | 14.32 |
December | 22.14 | 13.59 |
Annual Sum or Average | 23.01 | 16.01 |
Minimum of Months | 21.58 | 12.64 |
Maximum of Months | 24.46 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.98 | 13.22 |
February | 22.98 | 13.28 |
March | 22.86 | 12.64 |
April | 23.51 | 15.30 |
May | 23.58 | 15.56 |
June | 23.82 | 17.67 |
July | 23.89 | 19.43 |
August | 23.88 | 19.66 |
September | 23.85 | 18.47 |
October | 23.77 | 18.77 |
November | 23.28 | 14.32 |
December | 23.05 | 13.59 |
Annual Sum or Average | 23.46 | 16.01 |
Minimum of Months | 22.86 | 12.64 |
Maximum of Months | 23.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.33 | 13.22 |
February | 20.26 | 13.28 |
March | 20.21 | 12.64 |
April | 21.82 | 15.30 |
May | 22.00 | 15.56 |
June | 23.02 | 17.67 |
July | 23.81 | 19.43 |
August | 23.63 | 19.66 |
September | 23.05 | 18.47 |
October | 22.75 | 18.77 |
November | 20.92 | 14.32 |
December | 20.45 | 13.59 |
Annual Sum or Average | 21.86 | 16.01 |
Minimum of Months | 20.21 | 12.64 |
Maximum of Months | 23.81 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 13.22 |
February | 20.96 | 13.28 |
March | 20.90 | 12.64 |
April | 22.11 | 15.30 |
May | 22.35 | 15.56 |
June | 22.93 | 17.67 |
July | 23.20 | 19.43 |
August | 23.18 | 19.66 |
September | 22.92 | 18.47 |
October | 22.78 | 18.77 |
November | 21.42 | 14.32 |
December | 20.99 | 13.59 |
Annual Sum or Average | 22.06 | 16.01 |
Minimum of Months | 20.90 | 12.64 |
Maximum of Months | 23.20 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | 13.22 |
February | 21.09 | 13.28 |
March | 20.99 | 12.64 |
April | 22.13 | 15.30 |
May | 22.41 | 15.56 |
June | 23.00 | 17.67 |
July | 23.25 | 19.43 |
August | 23.23 | 19.66 |
September | 22.99 | 18.47 |
October | 22.83 | 18.77 |
November | 21.50 | 14.32 |
December | 21.09 | 13.59 |
Annual Sum or Average | 22.13 | 16.01 |
Minimum of Months | 20.99 | 12.64 |
Maximum of Months | 23.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | 13.22 |
February | 21.17 | 13.28 |
March | 21.08 | 12.64 |
April | 22.15 | 15.30 |
May | 22.41 | 15.56 |
June | 22.97 | 17.67 |
July | 23.22 | 19.43 |
August | 23.20 | 19.66 |
September | 22.95 | 18.47 |
October | 22.81 | 18.77 |
November | 21.55 | 14.32 |
December | 21.16 | 13.59 |
Annual Sum or Average | 22.15 | 16.01 |
Minimum of Months | 21.07 | 12.64 |
Maximum of Months | 23.22 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 13.22 |
February | 21.69 | 13.28 |
March | 21.66 | 12.64 |
April | 21.74 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.73 | 14.32 |
December | 21.70 | 13.59 |
Annual Sum or Average | 21.72 | 16.01 |
Minimum of Months | 21.66 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 13.22 |
February | 21.15 | 13.28 |
March | 21.05 | 12.64 |
April | 22.14 | 15.30 |
May | 22.36 | 15.56 |
June | 22.95 | 17.67 |
July | 23.23 | 19.43 |
August | 23.21 | 19.66 |
September | 22.95 | 18.47 |
October | 22.79 | 18.77 |
November | 21.55 | 14.32 |
December | 21.19 | 13.59 |
Annual Sum or Average | 22.14 | 16.01 |
Minimum of Months | 21.05 | 12.64 |
Maximum of Months | 23.23 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.22 |
February | 21.70 | 13.28 |
March | 21.66 | 12.64 |
April | 21.74 | 15.30 |
May | 21.74 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.74 | 13.59 |
Annual Sum or Average | 21.74 | 16.01 |
Minimum of Months | 21.66 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.75 | 13.28 |
March | 21.73 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.73 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.06 | 13.22 |
February | 24.94 | 13.28 |
March | 24.83 | 12.64 |
April | 25.39 | 15.30 |
May | 25.36 | 15.56 |
June | 25.67 | 17.67 |
July | 25.90 | 19.43 |
August | 25.93 | 19.66 |
September | 25.83 | 18.47 |
October | 25.79 | 18.77 |
November | 25.26 | 14.32 |
December | 25.11 | 13.59 |
Annual Sum or Average | 25.42 | 16.01 |
Minimum of Months | 24.83 | 12.64 |
Maximum of Months | 25.93 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.17 | 13.22 |
February | 23.20 | 13.28 |
March | 23.09 | 12.64 |
April | 23.30 | 15.30 |
May | 23.30 | 15.56 |
June | 23.33 | 17.67 |
July | 23.33 | 19.43 |
August | 23.33 | 19.66 |
September | 23.33 | 18.47 |
October | 23.32 | 18.77 |
November | 23.27 | 14.32 |
December | 23.19 | 13.59 |
Annual Sum or Average | 23.27 | 16.01 |
Minimum of Months | 23.09 | 12.64 |
Maximum of Months | 23.33 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.73 | 13.28 |
March | 21.71 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.71 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.37 | 13.22 |
February | 22.24 | 13.28 |
March | 22.00 | 12.64 |
April | 22.67 | 15.30 |
May | 22.66 | 15.56 |
June | 23.05 | 17.67 |
July | 23.26 | 19.43 |
August | 23.28 | 19.66 |
September | 23.17 | 18.47 |
October | 23.11 | 18.77 |
November | 22.62 | 14.32 |
December | 22.44 | 13.59 |
Annual Sum or Average | 22.74 | 16.01 |
Minimum of Months | 22.00 | 12.64 |
Maximum of Months | 23.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 13.22 |
February | 22.35 | 13.28 |
March | 22.18 | 12.64 |
April | 23.23 | 15.30 |
May | 23.16 | 15.56 |
June | 23.83 | 17.67 |
July | 24.44 | 19.43 |
August | 24.50 | 19.66 |
September | 24.12 | 18.47 |
October | 24.08 | 18.77 |
November | 22.95 | 14.32 |
December | 22.72 | 13.59 |
Annual Sum or Average | 23.36 | 16.01 |
Minimum of Months | 22.18 | 12.64 |
Maximum of Months | 24.50 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.07 | 13.22 |
February | 21.62 | 13.28 |
March | 21.50 | 12.64 |
April | 23.13 | 15.30 |
May | 23.03 | 15.56 |
June | 24.08 | 17.67 |
July | 25.06 | 19.43 |
August | 25.05 | 19.66 |
September | 24.42 | 18.47 |
October | 24.28 | 18.77 |
November | 22.49 | 14.32 |
December | 22.16 | 13.59 |
Annual Sum or Average | 23.25 | 16.01 |
Minimum of Months | 21.50 | 12.64 |
Maximum of Months | 25.06 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.37 | 13.22 |
February | 21.06 | 13.28 |
March | 20.95 | 12.64 |
April | 22.61 | 15.30 |
May | 22.54 | 15.56 |
June | 23.64 | 17.67 |
July | 24.53 | 19.43 |
August | 24.45 | 19.66 |
September | 23.91 | 18.47 |
October | 23.63 | 18.77 |
November | 21.86 | 14.32 |
December | 21.47 | 13.59 |
Annual Sum or Average | 22.68 | 16.01 |
Minimum of Months | 20.95 | 12.64 |
Maximum of Months | 24.53 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.35 | 13.22 |
February | 22.28 | 13.28 |
March | 22.25 | 12.64 |
April | 22.90 | 15.30 |
May | 23.00 | 15.56 |
June | 23.42 | 17.67 |
July | 23.64 | 19.43 |
August | 23.64 | 19.66 |
September | 23.45 | 18.47 |
October | 23.34 | 18.77 |
November | 22.56 | 14.32 |
December | 22.35 | 13.59 |
Annual Sum or Average | 22.93 | 16.01 |
Minimum of Months | 22.25 | 12.64 |
Maximum of Months | 23.64 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.73 | 13.22 |
February | 19.67 | 13.28 |
March | 19.68 | 12.64 |
April | 21.54 | 15.30 |
May | 21.72 | 15.56 |
June | 22.91 | 17.67 |
July | 23.81 | 19.43 |
August | 23.62 | 19.66 |
September | 22.89 | 18.47 |
October | 22.52 | 18.77 |
November | 20.37 | 14.32 |
December | 19.83 | 13.59 |
Annual Sum or Average | 21.53 | 16.01 |
Minimum of Months | 19.67 | 12.64 |
Maximum of Months | 23.81 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 13.22 |
February | 21.57 | 13.28 |
March | 21.55 | 12.64 |
April | 21.72 | 15.30 |
May | 21.73 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.74 | 18.47 |
October | 21.74 | 18.77 |
November | 21.70 | 14.32 |
December | 21.62 | 13.59 |
Annual Sum or Average | 21.69 | 16.01 |
Minimum of Months | 21.55 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | 13.22 |
February | 20.46 | 13.28 |
March | 20.48 | 12.64 |
April | 21.62 | 15.30 |
May | 21.90 | 15.56 |
June | 22.59 | 17.67 |
July | 22.94 | 19.43 |
August | 22.92 | 19.66 |
September | 22.56 | 18.47 |
October | 22.39 | 18.77 |
November | 20.87 | 14.32 |
December | 20.50 | 13.59 |
Annual Sum or Average | 21.65 | 16.01 |
Minimum of Months | 20.46 | 12.64 |
Maximum of Months | 22.94 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | 13.22 |
February | 20.51 | 13.28 |
March | 20.53 | 12.64 |
April | 21.63 | 15.30 |
May | 21.90 | 15.56 |
June | 22.57 | 17.67 |
July | 22.90 | 19.43 |
August | 22.89 | 19.66 |
September | 22.53 | 18.47 |
October | 22.37 | 18.77 |
November | 20.89 | 14.32 |
December | 20.52 | 13.59 |
Annual Sum or Average | 21.65 | 16.01 |
Minimum of Months | 20.51 | 12.64 |
Maximum of Months | 22.90 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.22 |
February | 21.69 | 13.28 |
March | 21.67 | 12.64 |
April | 21.74 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.74 | 14.32 |
December | 21.71 | 13.59 |
Annual Sum or Average | 21.73 | 16.01 |
Minimum of Months | 21.67 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.61 | 13.22 |
February | 20.62 | 13.28 |
March | 20.63 | 12.64 |
April | 21.78 | 15.30 |
May | 22.00 | 15.56 |
June | 22.65 | 17.67 |
July | 22.99 | 19.43 |
August | 22.97 | 19.66 |
September | 22.63 | 18.47 |
October | 22.46 | 18.77 |
November | 21.04 | 14.32 |
December | 20.65 | 13.59 |
Annual Sum or Average | 21.76 | 16.01 |
Minimum of Months | 20.61 | 12.64 |
Maximum of Months | 22.99 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.22 |
February | 21.50 | 13.28 |
March | 21.31 | 12.64 |
April | 22.16 | 15.30 |
May | 22.21 | 15.56 |
June | 22.74 | 17.67 |
July | 23.05 | 19.43 |
August | 23.06 | 19.66 |
September | 22.84 | 18.47 |
October | 22.74 | 18.77 |
November | 21.90 | 14.32 |
December | 21.63 | 13.59 |
Annual Sum or Average | 22.23 | 16.01 |
Minimum of Months | 21.31 | 12.64 |
Maximum of Months | 23.06 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.73 | 13.28 |
March | 21.71 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.71 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.86 | 13.22 |
February | 22.74 | 13.28 |
March | 22.69 | 12.64 |
April | 23.44 | 15.30 |
May | 23.44 | 15.56 |
June | 23.89 | 17.67 |
July | 24.23 | 19.43 |
August | 24.25 | 19.66 |
September | 24.00 | 18.47 |
October | 23.90 | 18.77 |
November | 23.09 | 14.32 |
December | 22.89 | 13.59 |
Annual Sum or Average | 23.46 | 16.01 |
Minimum of Months | 22.69 | 12.64 |
Maximum of Months | 24.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.73 | 13.28 |
March | 21.71 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.71 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.73 | 13.28 |
March | 21.70 | 12.64 |
April | 21.75 | 15.30 |
May | 21.75 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.75 | 13.59 |
Annual Sum or Average | 21.74 | 16.01 |
Minimum of Months | 21.70 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.22 |
February | 21.70 | 13.28 |
March | 21.67 | 12.64 |
April | 21.74 | 15.30 |
May | 21.74 | 15.56 |
June | 21.75 | 17.67 |
July | 21.75 | 19.43 |
August | 21.75 | 19.66 |
September | 21.75 | 18.47 |
October | 21.75 | 18.77 |
November | 21.75 | 14.32 |
December | 21.74 | 13.59 |
Annual Sum or Average | 21.74 | 16.01 |
Minimum of Months | 21.67 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.11 | 13.22 |
February | 21.87 | 13.28 |
March | 21.79 | 12.64 |
April | 22.97 | 15.30 |
May | 22.91 | 15.56 |
June | 23.66 | 17.67 |
July | 24.33 | 19.43 |
August | 24.36 | 19.66 |
September | 23.86 | 18.47 |
October | 23.74 | 18.77 |
November | 22.44 | 14.32 |
December | 22.17 | 13.59 |
Annual Sum or Average | 23.03 | 16.01 |
Minimum of Months | 21.79 | 12.64 |
Maximum of Months | 24.36 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:41
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.22 |
February | 21.06 | 13.28 |
March | 21.02 | 12.64 |
April | 22.85 | 15.30 |
May | 22.74 | 15.56 |
June | 23.93 | 17.67 |
July | 24.99 | 19.43 |
August | 24.97 | 19.66 |
September | 24.20 | 18.47 |
October | 23.97 | 18.77 |
November | 21.94 | 14.32 |
December | 21.55 | 13.59 |
Annual Sum or Average | 22.90 | 16.01 |
Minimum of Months | 21.02 | 12.64 |
Maximum of Months | 24.99 | 19.66 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:41
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.136140E+12 | 85774.087 | 20-JAN-08:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 15510.253 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.121157E+12 | 83506.509 | 17-FEB-08:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 13242.674 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.133979E+12 | 83375.425 | 18-MAR-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 13111.590 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.134287E+12 | 83572.343 | 28-APR-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 13308.508 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.138290E+12 | 86157.447 | 05-MAY-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 15893.613 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.139800E+12 | 89541.734 | 30-JUN-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 19277.900 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.151312E+12 | 90275.821 | 29-JUL-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 20011.987 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.152729E+12 | 92011.187 | 19-AUG-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 21747.352 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.143289E+12 | 91689.051 | 29-SEP-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 21425.217 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.146963E+12 | 88171.268 | 14-OCT-07:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 17907.434 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.132423E+12 | 85972.690 | 10-NOV-08:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 15708.856 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.135649E+12 | 83281.235 | 16-DEC-08:00 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 13017.400 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.166602E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.121157E+12 | 83281.235 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 13017.400 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.152729E+12 | 92011.187 | 17938.723 | 43276.576 | 9040.423 | 0.000 | 21747.352 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:41
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.869125E+11 | 91936.779 | 20-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 51840.751 | 51840.751 | 51840.751 | 0.000 |
February | 0.780242E+11 | 92022.498 | 10-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 51926.470 | 51926.470 | 51926.470 | 0.000 |
March | 0.863333E+11 | 91677.551 | 03-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 51581.523 | 51581.523 | 51581.523 | 0.000 |
April | 0.814763E+11 | 91047.697 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 50951.669 | 50951.669 | 50951.669 | 0.000 |
May | 0.830046E+11 | 90256.698 | 04-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 50160.670 | 50160.670 | 50160.670 | 0.000 |
June | 0.790747E+11 | 89838.255 | 02-JUN-08:45 | 0.000 | 40096.028 | 0.000 | 49742.227 | 49742.227 | 49742.227 | 0.000 |
July | 0.810540E+11 | 89181.202 | 06-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 49085.174 | 49085.174 | 49085.174 | 0.000 |
August | 0.810237E+11 | 89248.949 | 15-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 49152.921 | 49152.921 | 49152.921 | 0.000 |
September | 0.788580E+11 | 89585.455 | 24-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 49489.427 | 49489.427 | 49489.427 | 0.000 |
October | 0.825549E+11 | 90177.661 | 27-OCT-08:30 | 0.000 | 40096.028 | 0.000 | 50081.633 | 50081.633 | 50081.633 | 0.000 |
November | 0.816903E+11 | 90892.524 | 24-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 50796.496 | 50796.496 | 50796.496 | 0.000 |
December | 0.860780E+11 | 91869.201 | 30-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 51773.173 | 51773.173 | 51773.173 | 0.000 |
Annual Sum or Average | 0.986085E+12 | 0.000 | ||||||||
Minimum of Months | 0.780242E+11 | 89181.202 | 0.000 | 40096.028 | 0.000 | 49085.174 | 49085.174 | 49085.174 | 0.000 | |
Maximum of Months | 0.869125E+11 | 92022.498 | 0.000 | 40096.028 | 0.000 | 51926.470 | 51926.470 | 51926.470 | 0.000 |