Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Simulation Timestamp: 2018-10-19 10:15:33
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2997.11 | 746.74 | 804.57 |
Net Site Energy | 2997.11 | 746.74 | 804.57 |
Total Source Energy | 7604.17 | 1894.61 | 2041.34 |
Net Source Energy | 7604.17 | 1894.61 | 2041.34 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 6.55 | 2.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 719.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 289.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 482.11 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2090.88 | 906.23 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 6.55 | 2.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 719.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 289.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 482.11 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 272.69 | 130.13 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 561.30 | 243.28 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 253.09 | 120.77 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 520.95 | 225.79 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2090.88 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2090.88 | 100.00 |
Total On-Site and Utility Electric Sources | 2090.88 | 100.00 |
Total Electricity End Uses | 2090.88 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 128.00 |
Time Setpoint Not Met During Occupied Cooling | 5956.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5787.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Weather File | New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 |
Latitude [deg] | 28.58 |
Longitude [deg] | 77.20 |
Elevation [m] | 216.00 |
Time Zone | 5.50 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00 | 6.30 | Wetbulb [C] | 0.50 | 270.00 |
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 9.70 | 22.20 | Wetbulb [C] | 3.20 | 320.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 96.82 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 87.38 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8428.88 | 5935.98 | 2492.90 | 0.70 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 22975.02 | 15533.03 | 7442.00 | 0.68 | 3.80 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10283.78 | 6952.69 | 3331.09 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16570.74 | 11713.15 | 4857.58 | 0.71 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8134.9 | 3.32 | 11.34 | 12.02 | 11.41 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 22255.9 | 3.29 | 11.23 | 11.91 | 11.42 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9961.9 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15987.3 | 3.32 | 11.32 | 12.00 | 11.38 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.29 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 15304.94 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.21 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.29 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 1998.76 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2234.22 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.21 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.29 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 1998.76 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 719.94 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2234.22 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 704.77 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.21 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.29 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 1998.76 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 865.82 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2234.22 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 2819.08 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 845.04 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 800.49 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 704.72 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 2818.88 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 775.10 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 313.21 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 2901.93 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 12163.38 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6513.40 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 4908.65 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.38 | 423.88 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.93 | 1024.35 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.41 | 463.87 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.75 | 831.58 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 9116.45 | 10939.73 | 0.771 | 0.925 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
RESTROOMFLR1 | 602.88 | 723.45 | 0.051 | 0.061 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:15:00 | 40.40 | 0.00911 |
MEETINGROOMFLR1 | 4077.92 | 4893.51 | 0.345 | 0.414 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00 | 0.00911 |
GUESTROOM101 | 818.98 | 982.78 | 0.096 | 0.115 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM102 | 705.85 | 847.02 | 0.083 | 0.100 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM103 | 1402.70 | 1683.24 | 0.165 | 0.198 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
GUESTROOM104 | 1459.42 | 1751.30 | 0.171 | 0.206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03 | 0.00911 |
GUESTROOM105 | 1683.70 | 2020.43 | 0.198 | 0.237 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:15:00 | 41.85 | 0.00911 |
EMPLOYEELOUNGEFLR1 | 5461.71 | 6554.05 | 0.462 | 0.554 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
EXERCISECENTERFLR1 | 1336.19 | 1603.43 | 0.113 | 0.136 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:00:00 | 40.64 | 0.00911 |
FRONTOFFICEFLR1 | 3731.73 | 4478.08 | 0.315 | 0.378 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:15:00 | 41.85 | 0.00911 |
GUESTROOM201 | 1248.39 | 1498.07 | 0.147 | 0.176 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:30:00 | 41.76 | 0.00911 |
GUESTROOM202_205 | 4995.11 | 5994.13 | 0.587 | 0.704 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM206_208 | 4040.26 | 4848.32 | 0.475 | 0.570 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM209_212 | 4741.41 | 5689.69 | 0.557 | 0.669 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM213 | 1463.50 | 1756.20 | 0.172 | 0.206 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
GUESTROOM214 | 1572.50 | 1887.00 | 0.185 | 0.222 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:30:00 | 41.03 | 0.00911 |
GUESTROOM215_218 | 9905.27 | 11886.32 | 1.164 | 1.397 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
GUESTROOM219 | 5499.51 | 6599.41 | 0.646 | 0.775 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 41.42 | 0.00911 |
GUESTROOM220_223 | 5037.81 | 6045.37 | 0.592 | 0.710 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
GUESTROOM224 | 1515.63 | 1818.75 | 0.178 | 0.214 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
GUESTROOM301 | 1076.36 | 1291.63 | 0.126 | 0.152 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:15:00 | 42.00 | 0.00911 |
GUESTROOM302_305 | 2400.13 | 2880.15 | 0.282 | 0.338 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM306_308 | 2093.11 | 2511.73 | 0.246 | 0.295 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM309_312 | 4728.94 | 5674.73 | 0.556 | 0.667 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM313 | 972.27 | 1166.72 | 0.114 | 0.137 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 17:30:00 | 40.16 | 0.00911 |
GUESTROOM314 | 1510.92 | 1813.11 | 0.178 | 0.213 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
GUESTROOM315_318 | 5435.86 | 6523.03 | 0.639 | 0.767 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
GUESTROOM319 | 1241.25 | 1489.50 | 0.146 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
GUESTROOM320_323 | 4849.66 | 5819.59 | 0.570 | 0.684 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:45:00 | 41.56 | 0.00911 |
GUESTROOM324 | 960.03 | 1152.03 | 0.113 | 0.135 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:00:00 | 41.42 | 0.00911 |
GUESTROOM401 | 1940.73 | 2328.87 | 0.228 | 0.274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 13:45:00 | 41.88 | 0.00911 |
GUESTROOM402_405 | 3138.31 | 3765.97 | 0.369 | 0.442 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00 | 0.00911 |
GUESTROOM406_408 | 2699.12 | 3238.95 | 0.317 | 0.381 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00 | 0.00911 |
GUESTROOM409_412 | 5756.36 | 6907.64 | 0.676 | 0.812 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00 | 0.00911 |
GUESTROOM413 | 1238.44 | 1486.13 | 0.146 | 0.175 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:15:00 | 41.22 | 0.00911 |
GUESTROOM414 | 1285.38 | 1542.45 | 0.151 | 0.181 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
GUESTROOM415_418 | 5998.94 | 7198.73 | 0.705 | 0.846 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
GUESTROOM419 | 1673.05 | 2007.66 | 0.197 | 0.236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:00:00 | 42.00 | 0.00911 |
GUESTROOM420_423 | 5970.66 | 7164.79 | 0.702 | 0.842 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 14:30:00 | 42.00 | 0.00911 |
GUESTROOM424 | 1789.44 | 2147.33 | 0.210 | 0.252 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:15:00 | 41.85 | 0.00911 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
CORRIDORFLR1 | 24494.84 | 29393.81 | 2.070 | 2.484 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 18:00:00 | 39.67 | 0.00911 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
CORRIDORFLR2 | 3205.33 | 3846.39 | 0.271 | 0.325 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
CORRIDORFLR3 | 1812.13 | 2174.55 | 0.153 | 0.184 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 16:45:00 | 40.84 | 0.00911 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 | |
CORRIDORFLR4 | 2698.66 | 3238.39 | 0.228 | 0.274 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 6/21 15:30:00 | 41.71 | 0.00911 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB | 42.00 | 0.00911 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1154.28 | 1385.13 | 0.033 | 0.236 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | 6.30 | 0.00607 |
RESTROOMFLR1 | 36.91 | 44.29 | 0.001 | 0.001 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | 6.30 | 0.00607 |
MEETINGROOMFLR1 | 368.27 | 441.92 | 0.011 | 0.126 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 6.30 | 0.00607 |
GUESTROOM101 | 151.28 | 181.53 | 0.004 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 6.30 | 0.00607 |
GUESTROOM102 | 190.37 | 228.45 | 0.006 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 6.30 | 0.00607 |
GUESTROOM103 | 293.10 | 351.72 | 0.008 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 6.30 | 0.00607 |
GUESTROOM104 | 275.47 | 330.57 | 0.008 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 6.30 | 0.00607 |
GUESTROOM105 | 188.86 | 226.63 | 0.005 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 6.30 | 0.00607 |
EMPLOYEELOUNGEFLR1 | 162.07 | 194.48 | 0.005 | 0.051 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30 | 0.00607 |
EXERCISECENTERFLR1 | 92.70 | 111.24 | 0.003 | 0.043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 6.30 | 0.00607 |
FRONTOFFICEFLR1 | 661.92 | 794.30 | 0.019 | 0.056 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 6.30 | 0.00607 |
GUESTROOM201 | 370.29 | 444.35 | 0.011 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 6.30 | 0.00607 |
GUESTROOM202_205 | 745.07 | 894.08 | 0.022 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | 6.30 | 0.00607 |
GUESTROOM206_208 | 568.53 | 682.23 | 0.016 | 0.043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 6.30 | 0.00607 |
GUESTROOM209_212 | 658.92 | 790.70 | 0.019 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
GUESTROOM213 | 321.36 | 385.63 | 0.009 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 6.30 | 0.00607 |
GUESTROOM214 | 289.03 | 346.83 | 0.008 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | 6.30 | 0.00607 |
GUESTROOM215_218 | 629.09 | 754.91 | 0.018 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
GUESTROOM219 | 126.01 | 151.21 | 0.004 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
GUESTROOM220_223 | 620.80 | 744.96 | 0.018 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 6.30 | 0.00607 |
GUESTROOM224 | 258.45 | 310.14 | 0.007 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 6.30 | 0.00607 |
GUESTROOM301 | 400.90 | 481.07 | 0.012 | 0.014 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | 6.30 | 0.00607 |
GUESTROOM302_305 | 827.15 | 992.59 | 0.024 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 6.30 | 0.00607 |
GUESTROOM306_308 | 698.90 | 838.69 | 0.020 | 0.043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 14:15:00 | 6.30 | 0.00607 |
GUESTROOM309_312 | 810.32 | 972.39 | 0.023 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 6.30 | 0.00607 |
GUESTROOM313 | 364.68 | 437.61 | 0.011 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:45:00 | 6.30 | 0.00607 |
GUESTROOM314 | 328.00 | 393.60 | 0.009 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:30:00 | 6.30 | 0.00607 |
GUESTROOM315_318 | 790.91 | 949.09 | 0.023 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 6.30 | 0.00607 |
GUESTROOM319 | 203.15 | 243.78 | 0.006 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | 6.30 | 0.00607 |
GUESTROOM320_323 | 762.35 | 914.81 | 0.022 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | 6.30 | 0.00607 |
GUESTROOM324 | 303.78 | 364.54 | 0.009 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 6.30 | 0.00607 |
GUESTROOM401 | 522.47 | 626.96 | 0.015 | 0.018 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | 6.30 | 0.00607 |
GUESTROOM402_405 | 1258.24 | 1509.89 | 0.036 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 21:30:00 | 6.30 | 0.00607 |
GUESTROOM406_408 | 1061.88 | 1274.25 | 0.031 | 0.043 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 18:45:00 | 6.30 | 0.00607 |
GUESTROOM409_412 | 1253.06 | 1503.67 | 0.036 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | 6.30 | 0.00607 |
GUESTROOM413 | 505.15 | 606.17 | 0.015 | 0.018 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30 | 0.00607 |
GUESTROOM414 | 468.04 | 561.64 | 0.014 | 0.016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | 6.30 | 0.00607 |
GUESTROOM415_418 | 1237.68 | 1485.22 | 0.036 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | 6.30 | 0.00607 |
GUESTROOM419 | 350.45 | 420.55 | 0.010 | 0.013 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | 6.30 | 0.00607 |
GUESTROOM420_423 | 1206.17 | 1447.41 | 0.035 | 0.054 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | 6.30 | 0.00607 |
GUESTROOM424 | 446.88 | 536.25 | 0.013 | 0.016 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6.30 | 0.00607 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
CORRIDORFLR1 | 12075.36 | 14490.43 | 0.349 | 0.419 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6.30 | 0.00607 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
CORRIDORFLR2 | 118.13 | 141.75 | 0.003 | 0.038 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | 6.30 | 0.00607 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
CORRIDORFLR3 | 264.11 | 316.93 | 0.008 | 0.038 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 15:45:00 | 6.30 | 0.00607 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 | |
CORRIDORFLR4 | 814.24 | 977.09 | 0.024 | 0.038 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 6.30 | 0.00607 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB | 6.30 | 0.00607 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.38 | 0.38 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.93 | 0.93 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.41 | 0.41 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.75 | 0.75 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 4495.75 | 5173.75 | 2538.50 |
RESTROOMFLR1 | 3115.00 | 4901.00 | 754.75 |
MEETINGROOMFLR1 | 2662.75 | 2007.25 | 1050.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 532.25 | 8306.25 | 456.00 |
GUESTROOM104 | 582.25 | 7948.50 | 388.75 |
GUESTROOM105 | 670.50 | 7416.50 | 277.25 |
EMPLOYEELOUNGEFLR1 | 3360.25 | 2020.50 | 402.75 |
EXERCISECENTERFLR1 | 3764.50 | 683.50 | 244.75 |
FRONTOFFICEFLR1 | 4400.25 | 3497.25 | 1380.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 774.00 | 7890.50 | 401.75 |
GUESTROOM206_208 | 776.75 | 7826.25 | 333.00 |
GUESTROOM209_212 | 749.75 | 7917.00 | 375.00 |
GUESTROOM213 | 640.75 | 8034.75 | 380.50 |
GUESTROOM214 | 744.75 | 7539.75 | 284.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 6584.25 | 3824.00 | 2267.25 |
GUESTROOM220_223 | 823.25 | 7423.75 | 424.25 |
GUESTROOM224 | 743.50 | 7453.25 | 264.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 708.25 | 8173.75 | 527.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 758.50 | 7587.25 | 293.50 |
GUESTROOM315_318 | 918.50 | 7252.25 | 374.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 766.25 | 7687.00 | 498.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1378.50 | 7137.25 | 260.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1194.50 | 7365.25 | 301.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1642.00 | 6734.00 | 261.25 |
GUESTROOM419 | 1342.50 | 6785.25 | 161.25 |
GUESTROOM420_423 | 1602.00 | 6773.00 | 276.75 |
GUESTROOM424 | 1358.75 | 6845.25 | 150.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7436.50 | 8742.00 | 5787.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 1770.50 | 0.00 | 1770.50 |
MEETINGROOMFLR1 | 0.00 | 4.00 | 0.00 | 4.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 79.75 | 0.00 | 79.75 |
GUESTROOM104 | 0.00 | 92.75 | 0.00 | 92.75 |
GUESTROOM105 | 0.00 | 102.25 | 0.00 | 102.25 |
EMPLOYEELOUNGEFLR1 | 190.00 | 902.25 | 128.00 | 489.25 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 58.00 | 0.00 | 58.00 |
GUESTROOM206_208 | 0.00 | 66.00 | 0.00 | 66.00 |
GUESTROOM209_212 | 0.00 | 56.75 | 0.00 | 56.75 |
GUESTROOM213 | 0.00 | 58.75 | 0.00 | 58.75 |
GUESTROOM214 | 0.00 | 75.00 | 0.00 | 75.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 5467.75 | 0.00 | 5467.75 |
GUESTROOM220_223 | 0.00 | 64.00 | 0.00 | 64.00 |
GUESTROOM224 | 0.00 | 71.75 | 0.00 | 71.75 |
GUESTROOM301 | 0.00 | 0.25 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 54.75 | 0.00 | 54.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 70.00 | 0.00 | 70.00 |
GUESTROOM315_318 | 0.00 | 66.75 | 0.00 | 66.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 63.50 | 0.00 | 63.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 211.75 | 0.00 | 211.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 62.25 | 0.00 | 62.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 72.25 | 0.00 | 72.25 |
GUESTROOM419 | 0.00 | 122.75 | 0.00 | 122.75 |
GUESTROOM420_423 | 0.00 | 71.25 | 0.00 | 71.25 |
GUESTROOM424 | 0.00 | 157.75 | 0.00 | 157.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 6911.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 3308.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 1037.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 1759.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 190.00 | 7554.75 | 128.00 | 5956.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:33
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.378432 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.925204 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.751095 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.29 |
CORRIDORFLR1 PTAC HEATING COIL | 15304.94 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 704.77 |
102 PTAC HEATING COIL | 704.77 |
103 PTAC HEATING COIL | 704.77 |
104 PTAC HEATING COIL | 704.72 |
105 PTAC HEATING COIL | 704.72 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 313.21 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 313.29 |
CORRIDORFLR2 PTAC HEATING COIL | 1998.76 |
201 PTAC HEATING COIL | 704.77 |
202_205 PTAC HEATING COIL | 2819.08 |
206_208 PTAC HEATING COIL | 2234.22 |
209_212 PTAC HEATING COIL | 2819.08 |
213 PTAC HEATING COIL | 704.77 |
214 PTAC HEATING COIL | 704.72 |
215_218 PTAC HEATING COIL | 2818.88 |
219 PTAC HEATING COIL | 704.72 |
220_223 PTAC HEATING COIL | 2818.88 |
224 PTAC HEATING COIL | 704.72 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 313.21 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 313.29 |
CORRIDORFLR3 PTAC HEATING COIL | 1998.76 |
301 PTAC HEATING COIL | 719.94 |
302_305 PTAC HEATING COIL | 2819.08 |
306_308 PTAC HEATING COIL | 2234.22 |
309_312 PTAC HEATING COIL | 2819.08 |
313 PTAC HEATING COIL | 704.77 |
314 PTAC HEATING COIL | 704.72 |
315_318 PTAC HEATING COIL | 2818.88 |
319 PTAC HEATING COIL | 704.72 |
320_323 PTAC HEATING COIL | 2818.88 |
324 PTAC HEATING COIL | 704.72 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 313.21 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 313.29 |
CORRIDORFLR4 PTAC HEATING COIL | 1998.76 |
401 PTAC HEATING COIL | 865.82 |
402_405 PTAC HEATING COIL | 2819.08 |
406_408 PTAC HEATING COIL | 2234.22 |
409_412 PTAC HEATING COIL | 2819.08 |
413 PTAC HEATING COIL | 845.04 |
414 PTAC HEATING COIL | 800.49 |
415_418 PTAC HEATING COIL | 2818.88 |
419 PTAC HEATING COIL | 704.72 |
420_423 PTAC HEATING COIL | 2818.88 |
424 PTAC HEATING COIL | 775.10 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 313.21 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.704243 | 0.378432 | 8428.88 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 0.925204 | 22975.02 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.414128 | 10283.78 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.706858 | 0.751095 | 16570.74 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.925204 |
RESTROOMFLR1 DIRECT AIR | 0.061127 |
MEETINGROOMFLR1 DIRECT AIR | 0.414128 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.554415 |
EXERCISECENTERFLR1 DIRECT AIR | 0.135553 |
FRONTOFFICEFLR1 DIRECT AIR | 0.378432 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.378432 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.925204 |
SAC_MEETINGROOM MAIN BRANCH | 0.414128 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.751095 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.378432 |
SAC_FRONTLOUNGE | 0.925204 |
SAC_MEETINGROOM | 0.414128 |
SAC_EXC_EMPLGE_RESTRM | 0.751095 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.378432 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.925204 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.414128 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.751095 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.378432 | 0.378432 | 0.378432 | 0.378432 | 2901.93 | 8428.88 | 1.00 |
SAC_FRONTLOUNGE | 0.925204 | 0.925204 | 0.925204 | 0.925204 | 12163.38 | 22975.02 | 1.00 |
SAC_MEETINGROOM | 0.414128 | 0.414128 | 0.414128 | 0.414128 | 6513.40 | 10283.78 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.751095 | 0.751095 | 0.751095 | 0.751095 | 4908.65 | 16570.74 | 0.180474 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 2901.93 |
SAC_FRONTLOUNGE HEATING COIL | 12163.38 |
SAC_MEETINGROOM HEATING COIL | 6513.40 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 4908.65 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.414128 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.99 | 13.39 |
February | 22.88 | 16.97 |
March | 24.44 | 22.37 |
April | 26.27 | 29.13 |
May | 27.15 | 32.98 |
June | 27.13 | 33.60 |
July | 26.72 | 31.67 |
August | 26.25 | 30.03 |
September | 25.91 | 28.75 |
October | 25.33 | 25.09 |
November | 24.04 | 19.63 |
December | 22.44 | 14.52 |
Annual Sum or Average | 25.06 | 24.88 |
Minimum of Months | 21.99 | 13.39 |
Maximum of Months | 27.15 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.90 | 13.39 |
February | 24.54 | 16.97 |
March | 25.65 | 22.37 |
April | 27.22 | 29.13 |
May | 28.41 | 32.98 |
June | 28.77 | 33.60 |
July | 28.62 | 31.67 |
August | 28.29 | 30.03 |
September | 27.77 | 28.75 |
October | 26.52 | 25.09 |
November | 25.21 | 19.63 |
December | 24.13 | 14.52 |
Annual Sum or Average | 26.60 | 24.88 |
Minimum of Months | 23.90 | 13.39 |
Maximum of Months | 28.77 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.00 | 13.39 |
February | 21.98 | 16.97 |
March | 23.64 | 22.37 |
April | 25.54 | 29.13 |
May | 26.59 | 32.98 |
June | 26.61 | 33.60 |
July | 26.22 | 31.67 |
August | 25.71 | 30.03 |
September | 25.24 | 28.75 |
October | 24.38 | 25.09 |
November | 22.94 | 19.63 |
December | 21.40 | 14.52 |
Annual Sum or Average | 24.28 | 24.88 |
Minimum of Months | 21.00 | 13.39 |
Maximum of Months | 26.61 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.70 | 13.39 |
February | 23.19 | 16.97 |
March | 23.78 | 22.37 |
April | 23.89 | 29.13 |
May | 23.89 | 32.98 |
June | 23.89 | 33.60 |
July | 23.89 | 31.67 |
August | 23.89 | 30.03 |
September | 23.89 | 28.75 |
October | 23.88 | 25.09 |
November | 23.48 | 19.63 |
December | 22.78 | 14.52 |
Annual Sum or Average | 23.60 | 24.88 |
Minimum of Months | 22.70 | 13.39 |
Maximum of Months | 23.89 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.52 | 13.39 |
February | 22.89 | 16.97 |
March | 23.32 | 22.37 |
April | 23.65 | 29.13 |
May | 23.91 | 32.98 |
June | 23.98 | 33.60 |
July | 23.94 | 31.67 |
August | 23.86 | 30.03 |
September | 23.71 | 28.75 |
October | 23.44 | 25.09 |
November | 23.09 | 19.63 |
December | 22.64 | 14.52 |
Annual Sum or Average | 23.41 | 24.88 |
Minimum of Months | 22.52 | 13.39 |
Maximum of Months | 23.98 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.01 | 13.39 |
February | 23.40 | 16.97 |
March | 23.79 | 22.37 |
April | 23.89 | 29.13 |
May | 23.89 | 32.98 |
June | 23.89 | 33.60 |
July | 23.89 | 31.67 |
August | 23.89 | 30.03 |
September | 23.89 | 28.75 |
October | 23.89 | 25.09 |
November | 23.72 | 19.63 |
December | 23.21 | 14.52 |
Annual Sum or Average | 23.70 | 24.88 |
Minimum of Months | 23.01 | 13.39 |
Maximum of Months | 23.89 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.47 | 13.39 |
February | 26.09 | 16.97 |
March | 28.58 | 22.37 |
April | 32.07 | 29.13 |
May | 35.26 | 32.98 |
June | 37.48 | 33.60 |
July | 38.29 | 31.67 |
August | 37.49 | 30.03 |
September | 35.44 | 28.75 |
October | 32.34 | 25.09 |
November | 29.00 | 19.63 |
December | 26.22 | 14.52 |
Annual Sum or Average | 32.01 | 24.88 |
Minimum of Months | 25.47 | 13.39 |
Maximum of Months | 38.29 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.39 |
February | 22.50 | 16.97 |
March | 23.24 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.33 | 25.09 |
November | 23.12 | 19.63 |
December | 22.11 | 14.52 |
Annual Sum or Average | 23.00 | 24.88 |
Minimum of Months | 21.73 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | 13.39 |
February | 22.23 | 16.97 |
March | 23.05 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.28 | 25.09 |
November | 22.75 | 19.63 |
December | 21.74 | 14.52 |
Annual Sum or Average | 22.87 | 24.88 |
Minimum of Months | 21.39 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.50 | 13.39 |
February | 21.66 | 16.97 |
March | 21.74 | 22.37 |
April | 21.75 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.73 | 19.63 |
December | 21.60 | 14.52 |
Annual Sum or Average | 21.71 | 24.88 |
Minimum of Months | 21.50 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 13.39 |
February | 21.73 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.73 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.69 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.75 | 14.52 |
Annual Sum or Average | 21.76 | 24.88 |
Minimum of Months | 21.74 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.63 | 13.39 |
February | 22.73 | 16.97 |
March | 22.67 | 22.37 |
April | 22.28 | 29.13 |
May | 22.06 | 32.98 |
June | 22.01 | 33.60 |
July | 22.09 | 31.67 |
August | 22.20 | 30.03 |
September | 22.26 | 28.75 |
October | 22.38 | 25.09 |
November | 22.61 | 19.63 |
December | 22.63 | 14.52 |
Annual Sum or Average | 22.38 | 24.88 |
Minimum of Months | 22.01 | 13.39 |
Maximum of Months | 22.73 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.76 | 13.39 |
February | 52.09 | 16.97 |
March | 52.71 | 22.37 |
April | 53.39 | 29.13 |
May | 53.70 | 32.98 |
June | 53.79 | 33.60 |
July | 53.66 | 31.67 |
August | 53.55 | 30.03 |
September | 53.41 | 28.75 |
October | 53.30 | 25.09 |
November | 52.74 | 19.63 |
December | 51.99 | 14.52 |
Annual Sum or Average | 53.01 | 24.88 |
Minimum of Months | 51.76 | 13.39 |
Maximum of Months | 53.79 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.48 | 13.39 |
February | 69.81 | 16.97 |
March | 70.53 | 22.37 |
April | 71.40 | 29.13 |
May | 71.90 | 32.98 |
June | 72.10 | 33.60 |
July | 71.89 | 31.67 |
August | 71.77 | 30.03 |
September | 71.59 | 28.75 |
October | 71.26 | 25.09 |
November | 70.56 | 19.63 |
December | 69.75 | 14.52 |
Annual Sum or Average | 71.01 | 24.88 |
Minimum of Months | 69.48 | 13.39 |
Maximum of Months | 72.10 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.47 | 13.39 |
February | 23.70 | 16.97 |
March | 23.88 | 22.37 |
April | 23.89 | 29.13 |
May | 23.89 | 32.98 |
June | 23.89 | 33.60 |
July | 23.89 | 31.67 |
August | 23.89 | 30.03 |
September | 23.89 | 28.75 |
October | 23.89 | 25.09 |
November | 23.84 | 19.63 |
December | 23.56 | 14.52 |
Annual Sum or Average | 23.81 | 24.88 |
Minimum of Months | 23.47 | 13.39 |
Maximum of Months | 23.89 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.43 | 13.39 |
February | 23.72 | 16.97 |
March | 23.89 | 22.37 |
April | 23.89 | 29.13 |
May | 23.89 | 32.98 |
June | 23.89 | 33.60 |
July | 23.89 | 31.67 |
August | 23.89 | 30.03 |
September | 23.89 | 28.75 |
October | 23.89 | 25.09 |
November | 23.86 | 19.63 |
December | 23.57 | 14.52 |
Annual Sum or Average | 23.81 | 24.88 |
Minimum of Months | 23.43 | 13.39 |
Maximum of Months | 23.89 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.15 | 13.39 |
February | 23.23 | 16.97 |
March | 25.02 | 22.37 |
April | 27.21 | 29.13 |
May | 28.24 | 32.98 |
June | 28.15 | 33.60 |
July | 27.69 | 31.67 |
August | 27.17 | 30.03 |
September | 26.76 | 28.75 |
October | 26.19 | 25.09 |
November | 24.62 | 19.63 |
December | 22.71 | 14.52 |
Annual Sum or Average | 25.77 | 24.88 |
Minimum of Months | 22.15 | 13.39 |
Maximum of Months | 28.24 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 13.39 |
February | 23.59 | 16.97 |
March | 24.61 | 22.37 |
April | 25.83 | 29.13 |
May | 26.42 | 32.98 |
June | 26.40 | 33.60 |
July | 26.16 | 31.67 |
August | 25.88 | 30.03 |
September | 25.65 | 28.75 |
October | 25.35 | 25.09 |
November | 24.46 | 19.63 |
December | 23.30 | 14.52 |
Annual Sum or Average | 25.05 | 24.88 |
Minimum of Months | 22.92 | 13.39 |
Maximum of Months | 26.42 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 13.39 |
February | 23.38 | 16.97 |
March | 25.20 | 22.37 |
April | 27.32 | 29.13 |
May | 28.33 | 32.98 |
June | 28.29 | 33.60 |
July | 27.81 | 31.67 |
August | 27.26 | 30.03 |
September | 26.86 | 28.75 |
October | 26.19 | 25.09 |
November | 24.72 | 19.63 |
December | 22.87 | 14.52 |
Annual Sum or Average | 25.89 | 24.88 |
Minimum of Months | 22.33 | 13.39 |
Maximum of Months | 28.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.64 | 13.39 |
February | 23.83 | 16.97 |
March | 23.90 | 22.37 |
April | 24.12 | 29.13 |
May | 24.58 | 32.98 |
June | 24.84 | 33.60 |
July | 24.88 | 31.67 |
August | 24.67 | 30.03 |
September | 24.35 | 28.75 |
October | 23.96 | 25.09 |
November | 23.89 | 19.63 |
December | 23.76 | 14.52 |
Annual Sum or Average | 24.20 | 24.88 |
Minimum of Months | 23.64 | 13.39 |
Maximum of Months | 24.88 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | 13.39 |
February | 22.10 | 16.97 |
March | 24.17 | 22.37 |
April | 26.47 | 29.13 |
May | 27.71 | 32.98 |
June | 27.72 | 33.60 |
July | 27.24 | 31.67 |
August | 26.63 | 30.03 |
September | 26.06 | 28.75 |
October | 25.05 | 25.09 |
November | 23.29 | 19.63 |
December | 21.35 | 14.52 |
Annual Sum or Average | 24.90 | 24.88 |
Minimum of Months | 20.82 | 13.39 |
Maximum of Months | 27.72 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 13.39 |
February | 22.37 | 16.97 |
March | 23.20 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.32 | 25.09 |
November | 22.90 | 19.63 |
December | 21.65 | 14.52 |
Annual Sum or Average | 22.88 | 24.88 |
Minimum of Months | 21.16 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 13.39 |
February | 21.73 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.70 | 14.52 |
Annual Sum or Average | 21.74 | 24.88 |
Minimum of Months | 21.63 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | 13.39 |
February | 21.73 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.70 | 14.52 |
Annual Sum or Average | 21.74 | 24.88 |
Minimum of Months | 21.64 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 13.39 |
February | 21.74 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.71 | 14.52 |
Annual Sum or Average | 21.74 | 24.88 |
Minimum of Months | 21.67 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 13.39 |
February | 21.70 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.63 | 14.52 |
Annual Sum or Average | 21.72 | 24.88 |
Minimum of Months | 21.52 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.75 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.73 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 13.39 |
February | 23.33 | 16.97 |
March | 23.33 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.33 | 25.09 |
November | 23.33 | 19.63 |
December | 23.33 | 14.52 |
Annual Sum or Average | 23.33 | 24.88 |
Minimum of Months | 23.33 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.48 | 13.39 |
February | 32.86 | 16.97 |
March | 33.44 | 22.37 |
April | 34.14 | 29.13 |
May | 34.62 | 32.98 |
June | 34.80 | 33.60 |
July | 34.70 | 31.67 |
August | 34.52 | 30.03 |
September | 34.29 | 28.75 |
October | 33.95 | 25.09 |
November | 33.42 | 19.63 |
December | 32.73 | 14.52 |
Annual Sum or Average | 33.83 | 24.88 |
Minimum of Months | 32.48 | 13.39 |
Maximum of Months | 34.80 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.31 | 13.39 |
February | 22.49 | 16.97 |
March | 22.87 | 22.37 |
April | 23.51 | 29.13 |
May | 24.19 | 32.98 |
June | 24.54 | 33.60 |
July | 24.58 | 31.67 |
August | 24.38 | 30.03 |
September | 24.02 | 28.75 |
October | 23.33 | 25.09 |
November | 22.75 | 19.63 |
December | 22.36 | 14.52 |
Annual Sum or Average | 23.45 | 24.88 |
Minimum of Months | 22.31 | 13.39 |
Maximum of Months | 24.58 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.75 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.74 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.75 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.73 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.84 | 13.39 |
February | 23.72 | 16.97 |
March | 25.03 | 22.37 |
April | 26.51 | 29.13 |
May | 27.21 | 32.98 |
June | 27.15 | 33.60 |
July | 26.83 | 31.67 |
August | 26.48 | 30.03 |
September | 26.19 | 28.75 |
October | 25.85 | 25.09 |
November | 24.76 | 19.63 |
December | 23.33 | 14.52 |
Annual Sum or Average | 25.50 | 24.88 |
Minimum of Months | 22.84 | 13.39 |
Maximum of Months | 27.21 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 13.39 |
February | 23.76 | 16.97 |
March | 26.02 | 22.37 |
April | 28.73 | 29.13 |
May | 29.97 | 32.98 |
June | 29.82 | 33.60 |
July | 29.23 | 31.67 |
August | 28.60 | 30.03 |
September | 28.06 | 28.75 |
October | 27.37 | 25.09 |
November | 25.42 | 19.63 |
December | 23.06 | 14.52 |
Annual Sum or Average | 26.88 | 24.88 |
Minimum of Months | 22.34 | 13.39 |
Maximum of Months | 29.97 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.03 | 13.39 |
February | 23.26 | 16.97 |
March | 25.31 | 22.37 |
April | 27.60 | 29.13 |
May | 28.66 | 32.98 |
June | 28.61 | 33.60 |
July | 28.07 | 31.67 |
August | 27.50 | 30.03 |
September | 27.08 | 28.75 |
October | 26.36 | 25.09 |
November | 24.72 | 19.63 |
December | 22.63 | 14.52 |
Annual Sum or Average | 26.00 | 24.88 |
Minimum of Months | 22.03 | 13.39 |
Maximum of Months | 28.66 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.80 | 13.39 |
February | 23.46 | 16.97 |
March | 23.87 | 22.37 |
April | 23.91 | 29.13 |
May | 24.02 | 32.98 |
June | 24.13 | 33.60 |
July | 24.12 | 31.67 |
August | 24.02 | 30.03 |
September | 23.93 | 28.75 |
October | 23.89 | 25.09 |
November | 23.78 | 19.63 |
December | 23.12 | 14.52 |
Annual Sum or Average | 23.75 | 24.88 |
Minimum of Months | 22.80 | 13.39 |
Maximum of Months | 24.13 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.21 | 13.39 |
February | 21.86 | 16.97 |
March | 24.35 | 22.37 |
April | 26.91 | 29.13 |
May | 28.21 | 32.98 |
June | 28.21 | 33.60 |
July | 27.69 | 31.67 |
August | 27.03 | 30.03 |
September | 26.43 | 28.75 |
October | 25.33 | 25.09 |
November | 23.27 | 19.63 |
December | 20.87 | 14.52 |
Annual Sum or Average | 25.05 | 24.88 |
Minimum of Months | 20.21 | 13.39 |
Maximum of Months | 28.21 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | 13.39 |
February | 21.99 | 16.97 |
March | 23.12 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.29 | 25.09 |
November | 22.69 | 19.63 |
December | 21.07 | 14.52 |
Annual Sum or Average | 22.72 | 24.88 |
Minimum of Months | 20.53 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | 13.39 |
February | 22.09 | 16.97 |
March | 23.17 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.31 | 25.09 |
November | 22.77 | 19.63 |
December | 21.17 | 14.52 |
Annual Sum or Average | 22.77 | 24.88 |
Minimum of Months | 20.66 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | 13.39 |
February | 22.08 | 16.97 |
March | 23.15 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.30 | 25.09 |
November | 22.74 | 19.63 |
December | 21.21 | 14.52 |
Annual Sum or Average | 22.77 | 24.88 |
Minimum of Months | 20.73 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 13.39 |
February | 21.72 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.68 | 14.52 |
Annual Sum or Average | 21.73 | 24.88 |
Minimum of Months | 21.61 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 13.39 |
February | 22.11 | 16.97 |
March | 23.17 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.31 | 25.09 |
November | 22.82 | 19.63 |
December | 21.29 | 14.52 |
Annual Sum or Average | 22.79 | 24.88 |
Minimum of Months | 20.78 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 13.39 |
February | 21.74 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.73 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.69 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.75 | 14.52 |
Annual Sum or Average | 21.76 | 24.88 |
Minimum of Months | 21.74 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.87 | 13.39 |
February | 25.47 | 16.97 |
March | 26.17 | 22.37 |
April | 26.80 | 29.13 |
May | 27.14 | 32.98 |
June | 27.19 | 33.60 |
July | 27.09 | 31.67 |
August | 26.92 | 30.03 |
September | 26.77 | 28.75 |
October | 26.57 | 25.09 |
November | 26.06 | 19.63 |
December | 25.20 | 14.52 |
Annual Sum or Average | 26.36 | 24.88 |
Minimum of Months | 24.87 | 13.39 |
Maximum of Months | 27.19 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.02 | 13.39 |
February | 23.24 | 16.97 |
March | 23.33 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.33 | 25.09 |
November | 23.32 | 19.63 |
December | 23.15 | 14.52 |
Annual Sum or Average | 23.28 | 24.88 |
Minimum of Months | 23.02 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.39 |
February | 21.75 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.74 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.73 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.13 | 13.39 |
February | 22.75 | 16.97 |
March | 23.26 | 22.37 |
April | 23.33 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.33 | 25.09 |
November | 23.15 | 19.63 |
December | 22.46 | 14.52 |
Annual Sum or Average | 23.09 | 24.88 |
Minimum of Months | 22.13 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.44 | 13.39 |
February | 23.59 | 16.97 |
March | 25.19 | 22.37 |
April | 26.88 | 29.13 |
May | 27.65 | 32.98 |
June | 27.57 | 33.60 |
July | 27.20 | 31.67 |
August | 26.81 | 30.03 |
September | 26.48 | 28.75 |
October | 26.08 | 25.09 |
November | 24.80 | 19.63 |
December | 23.04 | 14.52 |
Annual Sum or Average | 25.65 | 24.88 |
Minimum of Months | 22.44 | 13.39 |
Maximum of Months | 27.65 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 13.39 |
February | 23.66 | 16.97 |
March | 26.22 | 22.37 |
April | 29.17 | 29.13 |
May | 30.50 | 32.98 |
June | 30.34 | 33.60 |
July | 29.66 | 31.67 |
August | 28.98 | 30.03 |
September | 28.39 | 28.75 |
October | 27.65 | 25.09 |
November | 25.47 | 19.63 |
December | 22.82 | 14.52 |
Annual Sum or Average | 27.09 | 24.88 |
Minimum of Months | 22.01 | 13.39 |
Maximum of Months | 30.50 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 13.39 |
February | 22.91 | 16.97 |
March | 25.39 | 22.37 |
April | 28.04 | 29.13 |
May | 29.27 | 32.98 |
June | 29.26 | 33.60 |
July | 28.61 | 31.67 |
August | 27.97 | 30.03 |
September | 27.45 | 28.75 |
October | 26.54 | 25.09 |
November | 24.50 | 19.63 |
December | 22.03 | 14.52 |
Annual Sum or Average | 26.12 | 24.88 |
Minimum of Months | 21.34 | 13.39 |
Maximum of Months | 29.27 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.23 | 13.39 |
February | 22.86 | 16.97 |
March | 23.65 | 22.37 |
April | 24.12 | 29.13 |
May | 24.41 | 32.98 |
June | 24.50 | 33.60 |
July | 24.37 | 31.67 |
August | 24.26 | 30.03 |
September | 24.12 | 28.75 |
October | 23.89 | 25.09 |
November | 23.24 | 19.63 |
December | 22.40 | 14.52 |
Annual Sum or Average | 23.68 | 24.88 |
Minimum of Months | 22.23 | 13.39 |
Maximum of Months | 24.50 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 13.39 |
February | 21.54 | 16.97 |
March | 24.37 | 22.37 |
April | 27.24 | 29.13 |
May | 28.70 | 32.98 |
June | 28.73 | 33.60 |
July | 28.09 | 31.67 |
August | 27.38 | 30.03 |
September | 26.69 | 28.75 |
October | 25.40 | 25.09 |
November | 23.00 | 19.63 |
December | 20.30 | 14.52 |
Annual Sum or Average | 25.11 | 24.88 |
Minimum of Months | 19.63 | 13.39 |
Maximum of Months | 28.73 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 13.39 |
February | 21.66 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.79 | 32.98 |
June | 21.82 | 33.60 |
July | 21.79 | 31.67 |
August | 21.77 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.74 | 19.63 |
December | 21.60 | 14.52 |
Annual Sum or Average | 21.72 | 24.88 |
Minimum of Months | 21.47 | 13.39 |
Maximum of Months | 21.82 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.33 | 13.39 |
February | 21.55 | 16.97 |
March | 22.89 | 22.37 |
April | 23.32 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.19 | 25.09 |
November | 22.19 | 19.63 |
December | 20.62 | 14.52 |
Annual Sum or Average | 22.57 | 24.88 |
Minimum of Months | 20.33 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.35 | 13.39 |
February | 21.53 | 16.97 |
March | 22.86 | 22.37 |
April | 23.31 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.17 | 25.09 |
November | 22.15 | 19.63 |
December | 20.63 | 14.52 |
Annual Sum or Average | 22.56 | 24.88 |
Minimum of Months | 20.35 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 13.39 |
February | 21.72 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.75 | 25.09 |
November | 21.75 | 19.63 |
December | 21.68 | 14.52 |
Annual Sum or Average | 21.73 | 24.88 |
Minimum of Months | 21.61 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.44 | 13.39 |
February | 21.67 | 16.97 |
March | 22.93 | 22.37 |
April | 23.32 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.21 | 25.09 |
November | 22.33 | 19.63 |
December | 20.79 | 14.52 |
Annual Sum or Average | 22.62 | 24.88 |
Minimum of Months | 20.44 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.33 | 13.39 |
February | 22.14 | 16.97 |
March | 23.04 | 22.37 |
April | 23.32 | 29.13 |
May | 23.33 | 32.98 |
June | 23.33 | 33.60 |
July | 23.33 | 31.67 |
August | 23.33 | 30.03 |
September | 23.33 | 28.75 |
October | 23.26 | 25.09 |
November | 22.66 | 19.63 |
December | 21.64 | 14.52 |
Annual Sum or Average | 22.84 | 24.88 |
Minimum of Months | 21.33 | 13.39 |
Maximum of Months | 23.33 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.39 |
February | 21.74 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.74 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.72 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.71 | 13.39 |
February | 23.50 | 16.97 |
March | 24.54 | 22.37 |
April | 25.48 | 29.13 |
May | 25.98 | 32.98 |
June | 26.01 | 33.60 |
July | 25.80 | 31.67 |
August | 25.56 | 30.03 |
September | 25.33 | 28.75 |
October | 24.99 | 25.09 |
November | 24.15 | 19.63 |
December | 23.05 | 14.52 |
Annual Sum or Average | 24.76 | 24.88 |
Minimum of Months | 22.71 | 13.39 |
Maximum of Months | 26.01 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.39 |
February | 21.74 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.77 | 32.98 |
June | 21.77 | 33.60 |
July | 21.77 | 31.67 |
August | 21.77 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.74 | 14.52 |
Annual Sum or Average | 21.76 | 24.88 |
Minimum of Months | 21.72 | 13.39 |
Maximum of Months | 21.77 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.39 |
February | 21.74 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.76 | 32.98 |
June | 21.76 | 33.60 |
July | 21.76 | 31.67 |
August | 21.76 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.74 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.72 | 13.39 |
Maximum of Months | 21.76 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | 13.39 |
February | 21.73 | 16.97 |
March | 21.75 | 22.37 |
April | 21.76 | 29.13 |
May | 21.78 | 32.98 |
June | 21.79 | 33.60 |
July | 21.77 | 31.67 |
August | 21.77 | 30.03 |
September | 21.76 | 28.75 |
October | 21.76 | 25.09 |
November | 21.75 | 19.63 |
December | 21.73 | 14.52 |
Annual Sum or Average | 21.75 | 24.88 |
Minimum of Months | 21.68 | 13.39 |
Maximum of Months | 21.79 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.92 | 13.39 |
February | 23.20 | 16.97 |
March | 25.03 | 22.37 |
April | 26.99 | 29.13 |
May | 27.92 | 32.98 |
June | 27.87 | 33.60 |
July | 27.39 | 31.67 |
August | 26.93 | 30.03 |
September | 26.50 | 28.75 |
October | 25.93 | 25.09 |
November | 24.38 | 19.63 |
December | 22.50 | 14.52 |
Annual Sum or Average | 25.56 | 24.88 |
Minimum of Months | 21.92 | 13.39 |
Maximum of Months | 27.92 | 33.60 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:33
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 13.39 |
February | 23.29 | 16.97 |
March | 26.15 | 22.37 |
April | 29.41 | 29.13 |
May | 30.92 | 32.98 |
June | 30.79 | 33.60 |
July | 29.98 | 31.67 |
August | 29.24 | 30.03 |
September | 28.54 | 28.75 |
October | 27.60 | 25.09 |
November | 25.13 | 19.63 |
December | 22.27 | 14.52 |
Annual Sum or Average | 27.08 | 24.88 |
Minimum of Months | 21.44 | 13.39 |
Maximum of Months | 30.92 | 33.60 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:33
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.137664E+12 | 89863.041 | 03-JAN-07:15 | 15177.258 | 39465.561 | 8980.235 | 19694.888 | 2348.985 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.129770E+12 | 87819.662 | 25-FEB-08:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 17152.147 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.158566E+12 | 92911.234 | 11-MAR-07:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 22243.720 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.176133E+12 | 101467.009 | 26-APR-19:15 | 19529.751 | 28246.035 | 9060.896 | 0.000 | 40434.214 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.204588E+12 | 109980.450 | 19-MAY-07:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 39312.936 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.207843E+12 | 114706.399 | 10-JUN-17:15 | 18623.018 | 28375.839 | 9214.594 | 0.000 | 58484.834 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.215677E+12 | 120729.440 | 08-JUL-07:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 50061.925 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.209439E+12 | 113849.857 | 25-AUG-07:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 43182.342 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.192010E+12 | 110652.709 | 17-SEP-19:00 | 19529.751 | 28246.035 | 9080.126 | 0.000 | 49600.684 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.172687E+12 | 96852.015 | 06-OCT-07:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 26184.501 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.147421E+12 | 90033.096 | 10-NOV-08:00 | 17938.723 | 43276.576 | 9444.103 | 0.000 | 19365.581 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.139079E+12 | 88516.977 | 31-DEC-07:15 | 15177.258 | 39465.561 | 8980.235 | 17869.230 | 2828.579 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.209088E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.129770E+12 | 87819.662 | 15177.258 | 28246.035 | 8980.235 | 0.000 | 2348.985 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.215677E+12 | 120729.440 | 19529.751 | 43276.576 | 9444.103 | 19694.888 | 58484.834 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:33
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.828311E+11 | 89488.822 | 24-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 49392.794 | 49392.794 | 49392.794 | 0.000 |
February | 0.731905E+11 | 86415.955 | 06-FEB-09:30 | 0.000 | 40096.028 | 0.000 | 46319.927 | 46319.927 | 46319.927 | 0.000 |
March | 0.790986E+11 | 74191.094 | 02-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 34095.066 | 34095.066 | 34095.066 | 0.000 |
April | 0.744490E+11 | 73118.869 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 33022.841 | 33022.841 | 33022.841 | 0.000 |
May | 0.747030E+11 | 71940.050 | 01-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 31844.022 | 31844.022 | 31844.022 | 0.000 |
June | 0.706645E+11 | 70979.197 | 01-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 30883.169 | 30883.169 | 30883.169 | 0.000 |
July | 0.723389E+11 | 70427.742 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 30331.714 | 30331.714 | 30331.714 | 0.000 |
August | 0.728390E+11 | 70786.808 | 28-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 30690.780 | 30690.780 | 30690.780 | 0.000 |
September | 0.719755E+11 | 71701.213 | 30-SEP-08:45 | 0.000 | 40096.028 | 0.000 | 31605.185 | 31605.185 | 31605.185 | 0.000 |
October | 0.765404E+11 | 72947.076 | 31-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 32851.048 | 32851.048 | 32851.048 | 0.000 |
November | 0.762582E+11 | 74010.626 | 30-NOV-09:45 | 0.000 | 40096.028 | 0.000 | 33914.598 | 33914.598 | 33914.598 | 0.000 |
December | 0.813405E+11 | 89081.806 | 28-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 48985.778 | 48985.778 | 48985.778 | 0.000 |
Annual Sum or Average | 0.906229E+12 | 0.000 | ||||||||
Minimum of Months | 0.706645E+11 | 70427.742 | 0.000 | 40096.028 | 0.000 | 30331.714 | 30331.714 | 30331.714 | 0.000 | |
Maximum of Months | 0.828311E+11 | 89488.822 | 0.000 | 40096.028 | 0.000 | 49392.794 | 49392.794 | 49392.794 | 0.000 |