Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Rochester International Arpt MN USA TMY3 WMO#=726440

Simulation Timestamp: 2018-10-19 10:15:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3289.67 819.63 883.11
Net Site Energy 3289.67 819.63 883.11
Total Source Energy 7751.86 1931.41 2080.98
Net Source Energy 7751.86 1931.41 2080.98


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 460.56 168.93 0.00 0.00 0.00 0.00
Cooling 197.44 0.00 0.00 0.00 0.00 0.00
Interior Lighting 414.43 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.77 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 280.06 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 689.72 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2009.53 1280.13 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 460.56 168.93 0.00 0.00 0.00 0.00
Cooling General 197.44 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 414.43 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.77 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 280.06 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 689.72 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.91 0.00 0.00 0.00 0.00 0.00
HVAC 251.89 230.50 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 539.46 343.65 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.65 0.00 0.00 0.00 0.00 0.00
HVAC 233.78 213.93 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 500.68 318.95 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2009.53 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2009.53 100.00
     
Total On-Site and Utility Electric Sources 2009.53 100.00
Total Electricity End Uses 2009.53 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1478.00
Time Setpoint Not Met During Occupied Cooling 2737.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 6646.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Rochester International Arpt MN USA TMY3 WMO#=726440
Weather File Rochester International Arpt MN USA TMY3 WMO#=726440
Latitude [deg] 43.90
Longitude [deg] -92.5
Elevation [m] 398.00
Time Zone -6.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB -26.20 0.00 -26.20 Wetbulb [C] 5.70 310.00
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 31.20 10.60 23.10 Wetbulb [C] 6.70 200.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           96.82 2.653 0.426 0.308              
Non-North Total or Average           87.38 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7070.36 5026.50 2043.87 0.71 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   19029.83 12865.75 6164.08 0.68 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8963.19 6059.87 2903.33 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   14605.47 10641.89 3963.58 0.73 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6817.7 3.31 11.30 11.98 11.34
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 18434.2 3.38 11.52 12.22 11.70
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8682.6 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 14050.8 3.28 11.18 11.85 11.17
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   306.55 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   37770.87 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1202.50 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1222.89 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1695.93 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1673.99 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1219.11 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   545.65 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   545.78 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   3796.81 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1514.06 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4809.99 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3812.08 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4809.99 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1784.82 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1676.67 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4809.65 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1202.41 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4809.65 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1458.59 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   708.92 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   545.78 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   4178.87 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1577.36 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4809.99 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3927.86 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   4821.40 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1921.76 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1743.79 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4809.65 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1278.28 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4809.65 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1554.18 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   863.64 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   767.39 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   5927.94 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1962.84 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   6167.20 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   5056.41 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6198.71 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2371.68 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   2135.09 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   6136.96 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1713.76 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   6077.78 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1981.13 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   1140.13 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4951.35 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   20753.49 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   11113.34 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   8503.27 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.87 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 1.16 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.98 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.02 1.67 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.33 364.26 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.77 848.45 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 404.30 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.71 790.79 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7386.80 8864.16 0.639 0.766 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 31.04 0.01534
RESTROOMFLR1 417.67 501.21 0.036 0.043 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 30.56 0.01534
MEETINGROOMFLR1 3477.13 4172.55 0.301 0.361 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 31.20 0.01534
GUESTROOM101 536.10 643.32 0.064 0.077 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 30.72 0.01534
GUESTROOM102 437.34 524.81 0.053 0.063 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 30.72 0.01534
GUESTROOM103 1006.01 1207.22 0.121 0.145 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
GUESTROOM104 1165.78 1398.93 0.140 0.168 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
GUESTROOM105 1531.35 1837.62 0.184 0.221 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
EMPLOYEELOUNGEFLR1 5321.79 6386.15 0.460 0.552 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
EXERCISECENTERFLR1 1145.87 1375.05 0.099 0.119 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 29.72 0.01534
FRONTOFFICEFLR1 3137.36 3764.84 0.271 0.325 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM201 816.64 979.96 0.098 0.118 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
GUESTROOM202_205 4075.56 4890.67 0.490 0.587 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 30.72 0.01534
GUESTROOM206_208 3299.64 3959.56 0.396 0.476 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 30.88 0.01534
GUESTROOM209_212 3887.47 4664.97 0.467 0.560 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 30.72 0.01534
GUESTROOM213 1092.84 1311.41 0.131 0.158 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
GUESTROOM214 1312.50 1575.01 0.158 0.189 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
GUESTROOM215_218 9538.72 11446.47 1.146 1.375 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM219 5385.74 6462.89 0.647 0.776 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM220_223 4622.52 5547.02 0.555 0.666 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM224 1310.54 1572.64 0.157 0.189 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM301 648.81 778.57 0.078 0.094 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM302_305 1539.13 1846.96 0.185 0.222 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 30.56 0.01534
GUESTROOM306_308 1341.66 1610.00 0.161 0.193 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 30.56 0.01534
GUESTROOM309_312 3871.29 4645.55 0.465 0.558 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 30.56 0.01534
GUESTROOM313 598.96 718.75 0.072 0.086 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.07 0.01534
GUESTROOM314 1235.94 1483.13 0.148 0.178 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 31.20 0.01534
GUESTROOM315_318 5040.14 6048.17 0.605 0.726 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM319 1118.05 1341.66 0.134 0.161 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM320_323 4434.47 5321.36 0.533 0.639 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
GUESTROOM324 742.91 891.50 0.089 0.107 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
GUESTROOM401 1485.12 1782.15 0.178 0.214 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 31.07 0.01534
GUESTROOM402_405 2321.48 2785.78 0.279 0.335 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM406_408 1980.74 2376.89 0.238 0.285 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 31.20 0.01534
GUESTROOM409_412 4966.41 5959.69 0.597 0.716 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM413 852.48 1022.98 0.102 0.123 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 31.04 0.01534
GUESTROOM414 1033.05 1239.66 0.124 0.149 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
GUESTROOM415_418 5753.78 6904.54 0.691 0.829 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 31.20 0.01534
GUESTROOM419 1573.19 1887.83 0.189 0.227 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 31.20 0.01534
GUESTROOM420_423 5718.67 6862.40 0.687 0.824 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 31.20 0.01534
GUESTROOM424 1589.65 1907.58 0.191 0.229 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 31.20 0.01534
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
CORRIDORFLR1 14178.48 17014.18 1.225 1.470 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 28.66 0.01534
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
CORRIDORFLR2 2634.23 3161.07 0.227 0.273 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 29.72 0.01534
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
CORRIDORFLR3 1263.48 1516.18 0.109 0.131 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 29.45 0.01534
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534
CORRIDORFLR4 2157.09 2588.51 0.186 0.224 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 31.04 0.01534
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB   31.20 0.01534


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2263.64 2716.37 0.067 0.236 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -26.20 0.00036
RESTROOMFLR1 171.22 205.47 0.005 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -26.20 0.00036
MEETINGROOMFLR1 808.89 970.67 0.024 0.126 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -26.20 0.00036
GUESTROOM101 342.26 410.72 0.010 0.013 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20 0.00036
GUESTROOM102 396.90 476.28 0.012 0.014 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -26.20 0.00036
GUESTROOM103 791.11 949.33 0.023 0.028 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -26.20 0.00036
GUESTROOM104 772.87 927.44 0.023 0.027 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -26.20 0.00036
GUESTROOM105 393.80 472.56 0.012 0.014 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -26.20 0.00036
EMPLOYEELOUNGEFLR1 370.72 444.87 0.011 0.051 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -26.20 0.00036
EXERCISECENTERFLR1 267.15 320.58 0.008 0.043 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -26.20 0.00036
FRONTOFFICEFLR1 1461.37 1753.65 0.043 0.056 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -26.20 0.00036
GUESTROOM201 639.55 767.46 0.019 0.023 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -26.20 0.00036
GUESTROOM202_205 1354.68 1625.61 0.040 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -26.20 0.00036
GUESTROOM206_208 1086.33 1303.60 0.032 0.043 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
GUESTROOM209_212 1275.35 1530.42 0.038 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -26.20 0.00036
GUESTROOM213 865.18 1038.22 0.026 0.031 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -26.20 0.00036
GUESTROOM214 775.10 930.12 0.023 0.027 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -26.20 0.00036
GUESTROOM215_218 1268.98 1522.78 0.038 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -26.20 0.00036
GUESTROOM219 349.43 419.32 0.010 0.013 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -26.20 0.00036
GUESTROOM220_223 1204.09 1444.91 0.036 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -26.20 0.00036
GUESTROOM224 593.37 712.04 0.018 0.021 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -26.20 0.00036
GUESTROOM301 692.30 830.76 0.020 0.025 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -26.20 0.00036
GUESTROOM302_305 1515.65 1818.78 0.045 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:30:00 -26.20 0.00036
GUESTROOM306_308 1300.85 1561.02 0.038 0.046 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:30:00 -26.20 0.00036
GUESTROOM309_312 1529.14 1834.97 0.045 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:30:00 -26.20 0.00036
GUESTROOM313 979.29 1175.15 0.029 0.035 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -26.20 0.00036
GUESTROOM314 831.03 997.24 0.025 0.029 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:15:00 -26.20 0.00036
GUESTROOM315_318 1485.52 1782.63 0.044 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -26.20 0.00036
GUESTROOM319 443.10 531.72 0.013 0.016 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -26.20 0.00036
GUESTROOM320_323 1432.91 1719.49 0.042 0.054 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -26.20 0.00036
GUESTROOM324 673.02 807.62 0.020 0.024 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -26.20 0.00036
GUESTROOM401 1013.53 1216.23 0.030 0.036 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -26.20 0.00036
GUESTROOM402_405 2650.64 3180.77 0.078 0.094 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -26.20 0.00036
GUESTROOM406_408 2241.30 2689.56 0.066 0.079 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -26.20 0.00036
GUESTROOM409_412 2676.91 3212.29 0.079 0.095 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -26.20 0.00036
GUESTROOM413 1354.23 1625.07 0.040 0.048 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -26.20 0.00036
GUESTROOM414 1157.12 1388.54 0.034 0.041 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -26.20 0.00036
GUESTROOM415_418 2625.63 3150.75 0.078 0.093 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -26.20 0.00036
GUESTROOM419 806.01 967.21 0.024 0.029 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -26.20 0.00036
GUESTROOM420_423 2576.31 3091.57 0.076 0.091 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -26.20 0.00036
GUESTROOM424 1028.81 1234.58 0.030 0.036 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -26.20 0.00036
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB   -26.20 0.00036
CORRIDORFLR1 29336.25 35203.50 0.866 1.039 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -26.20 0.00036
FRONTSTAIRSFLR1 30.61 36.73 0.001 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -26.20 0.00036
REARSTAIRSFLR2 117.72 141.27 0.002 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
CORRIDORFLR2 1399.59 1679.51 0.041 0.050 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -26.20 0.00036
FRONTSTAIRSFLR2 391.51 469.81 0.008 0.009 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
REARSTAIRSFLR3 241.49 289.79 0.005 0.006 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
CORRIDORFLR3 1717.95 2061.53 0.051 0.061 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
FRONTSTAIRSFLR3 520.46 624.56 0.010 0.012 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
REARSTAIRSFLR4 440.19 528.23 0.009 0.011 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
CORRIDORFLR4 3175.53 3810.63 0.094 0.113 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036
FRONTSTAIRSFLR4 750.90 901.08 0.015 0.018 ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -26.20 0.00036


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.33 0.33 0.06 0.06
SAC_FRONTLOUNGE 0.77 0.77 0.24 0.24
SAC_MEETINGROOM 0.36 0.36 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.71 0.71 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 0.77 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 3642.25 7597.75 3064.00
RESTROOMFLR1 1741.75 7877.00 1589.50
MEETINGROOMFLR1 1479.75 3660.50 911.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 3291.50 8760.00 3291.50
GUESTROOM104 2368.25 8717.50 2367.75
GUESTROOM105 591.25 8398.00 582.25
EMPLOYEELOUNGEFLR1 2780.50 2591.75 502.50
EXERCISECENTERFLR1 1337.75 3369.50 160.25
FRONTOFFICEFLR1 2191.75 6597.00 1505.50
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 2246.25 8515.50 2244.50
GUESTROOM206_208 2070.00 8506.00 2064.50
GUESTROOM209_212 1942.75 8653.25 1942.75
GUESTROOM213 3378.00 8724.50 3378.00
GUESTROOM214 2166.25 8483.00 2159.00
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 3149.25 4811.00 334.75
GUESTROOM220_223 998.00 8337.75 976.50
GUESTROOM224 2133.25 8441.50 2125.50
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 2457.00 8656.50 2457.00
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 2912.75 8505.00 2904.75
GUESTROOM315_318 1089.00 8215.50 1022.25
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 1585.25 8431.50 1571.00
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 4538.50 8149.50 4286.00
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 3523.25 8074.50 3204.75
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2961.25 7857.25 2438.00
GUESTROOM419 2884.25 7991.50 2561.00
GUESTROOM420_423 3039.50 7892.50 2533.00
GUESTROOM424 3682.50 8096.00 3400.75
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7592.75 8760.00 6646.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.50 0.00 0.50 0.00
RESTROOMFLR1 1267.50 346.50 1267.50 346.50
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.25 0.00 0.00 0.00
GUESTROOM102 0.75 0.00 0.00 0.00
GUESTROOM103 30.25 29.50 30.25 29.50
GUESTROOM104 18.00 33.75 18.00 33.75
GUESTROOM105 2.75 42.25 2.75 42.25
EMPLOYEELOUNGEFLR1 902.50 1012.50 645.25 594.00
EXERCISECENTERFLR1 0.25 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 25.50 20.25 25.50 20.25
GUESTROOM206_208 24.75 26.75 24.75 26.75
GUESTROOM209_212 25.00 19.75 25.00 19.75
GUESTROOM213 25.75 20.00 25.75 20.00
GUESTROOM214 16.75 25.75 16.75 25.75
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2077.00 0.00 2077.00
GUESTROOM220_223 8.75 24.50 8.75 24.50
GUESTROOM224 17.75 26.00 17.75 26.00
GUESTROOM301 0.75 0.00 0.00 0.00
GUESTROOM302_305 0.25 0.00 0.00 0.00
GUESTROOM306_308 0.25 0.00 0.00 0.00
GUESTROOM309_312 29.50 19.75 29.50 19.75
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 24.00 25.25 24.00 25.25
GUESTROOM315_318 9.25 26.25 9.25 26.25
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 16.75 23.50 16.75 23.50
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 55.75 27.75 55.75 27.75
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 31.50 26.50 31.50 26.50
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.50 0.00 0.00 0.00
GUESTROOM415_418 23.50 28.75 23.50 28.75
GUESTROOM419 21.50 31.25 21.50 31.25
GUESTROOM420_423 23.25 28.50 23.25 28.50
GUESTROOM424 17.50 29.50 17.50 29.50
REARSTAIRSFLR1 5.50 0.00 0.00 0.00
CORRIDORFLR1 12.25 2475.00 0.00 0.00
FRONTSTAIRSFLR1 5.75 0.00 0.00 0.00
REARSTAIRSFLR2 11.50 0.00 0.00 0.00
CORRIDORFLR2 0.00 62.75 0.00 0.00
FRONTSTAIRSFLR2 21.75 0.00 0.00 0.00
REARSTAIRSFLR3 37.75 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 33.75 0.00 0.00 0.00
REARSTAIRSFLR4 50.50 0.00 0.00 0.00
CORRIDORFLR4 4.25 194.00 0.00 0.00
FRONTSTAIRSFLR4 34.50 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 1539.50 3709.50 1478.00 2737.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.009371
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.012457
REARSTAIRSFLR4 UNITHEATER 0.010536
FRONTSTAIRSFLR4 UNITHEATER 0.017971


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.009371
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.012457
REARSTAIRSFLR4UNITHEATERFAN 0.010536
FRONTSTAIRSFLR4UNITHEATERFAN 0.017971
SAC_FRONTOFFICE SUPPLY FAN 0.325201
SAC_FRONTLOUNGE SUPPLY FAN 0.766331
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.714251


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 306.55
CORRIDORFLR1 PTAC HEATING COIL 37770.87
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1202.50
102 PTAC HEATING COIL 1222.89
103 PTAC HEATING COIL 1695.93
104 PTAC HEATING COIL 1673.99
105 PTAC HEATING COIL 1219.11
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 545.65
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 545.78
CORRIDORFLR2 PTAC HEATING COIL 3796.81
201 PTAC HEATING COIL 1514.06
202_205 PTAC HEATING COIL 4809.99
206_208 PTAC HEATING COIL 3812.08
209_212 PTAC HEATING COIL 4809.99
213 PTAC HEATING COIL 1784.82
214 PTAC HEATING COIL 1676.67
215_218 PTAC HEATING COIL 4809.65
219 PTAC HEATING COIL 1202.41
220_223 PTAC HEATING COIL 4809.65
224 PTAC HEATING COIL 1458.59
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 708.92
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 545.78
CORRIDORFLR3 PTAC HEATING COIL 4178.87
301 PTAC HEATING COIL 1577.36
302_305 PTAC HEATING COIL 4809.99
306_308 PTAC HEATING COIL 3927.86
309_312 PTAC HEATING COIL 4821.40
313 PTAC HEATING COIL 1921.76
314 PTAC HEATING COIL 1743.79
315_318 PTAC HEATING COIL 4809.65
319 PTAC HEATING COIL 1278.28
320_323 PTAC HEATING COIL 4809.65
324 PTAC HEATING COIL 1554.18
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 863.64
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 767.39
CORRIDORFLR4 PTAC HEATING COIL 5927.94
401 PTAC HEATING COIL 1962.84
402_405 PTAC HEATING COIL 6167.20
406_408 PTAC HEATING COIL 5056.41
409_412 PTAC HEATING COIL 6198.71
413 PTAC HEATING COIL 2371.68
414 PTAC HEATING COIL 2135.09
415_418 PTAC HEATING COIL 6136.96
419 PTAC HEATING COIL 1713.76
420_423 PTAC HEATING COIL 6077.78
424 PTAC HEATING COIL 1981.13
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 1140.13


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.710925 0.325201 7070.36
SAC_FRONTLOUNGE COOLING COIL 0.676083 0.766331 19029.83
SAC_MEETINGROOM COOLING COIL 0.676083 0.360948 8963.19
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.728623 0.714251 14605.47


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.766331
RESTROOMFLR1 DIRECT AIR 0.043286
MEETINGROOMFLR1 DIRECT AIR 0.360948
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.552147
EXERCISECENTERFLR1 DIRECT AIR 0.118818
FRONTOFFICEFLR1 DIRECT AIR 0.325201


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.325201
SAC_FRONTLOUNGE MAIN BRANCH 0.766331
SAC_MEETINGROOM MAIN BRANCH 0.360948
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.714251


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.325201
SAC_FRONTLOUNGE 0.766331
SAC_MEETINGROOM 0.360948
SAC_EXC_EMPLGE_RESTRM 0.714251


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.325201 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.766331 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.360948 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.714251 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.325201 0.325201 0.325201 0.325201 4951.35 7070.36 1.00
SAC_FRONTLOUNGE 0.766331 0.766331 0.766331 0.766331 20753.49 19029.83 1.00
SAC_MEETINGROOM 0.360948 0.360948 0.360948 0.360948 11113.34 8963.19 1.00
SAC_EXC_EMPLGE_RESTRM 0.714251 0.714251 0.714251 0.714251 8503.27 14605.47 0.166353


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4951.35
SAC_FRONTLOUNGE HEATING COIL 20753.49
SAC_MEETINGROOM HEATING COIL 11113.34
SAC_EXC_EMPLGE_RESTRM HEATING COIL 8503.27


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.360948


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.88 -12.6
February 14.21 -7.7
March 16.25 0.33
April 18.90 7.02
May 21.33 14.19
June 22.93 19.16
July 23.58 20.92
August 23.23 20.05
September 21.85 15.39
October 19.19 7.43
November 16.35 -0.0
December 14.09 -7.6
     
Annual Sum or Average 18.76 6.46
Minimum of Months 12.88 -12.6
Maximum of Months 23.58 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.33 -12.6
February 21.70 -7.7
March 22.34 0.33
April 23.35 7.02
May 24.37 14.19
June 25.33 19.16
July 25.74 20.92
August 25.56 20.05
September 24.63 15.39
October 23.42 7.43
November 22.40 -0.0
December 21.51 -7.6
     
Annual Sum or Average 23.48 6.46
Minimum of Months 21.33 -12.6
Maximum of Months 25.74 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.63 -12.6
February 13.84 -7.7
March 15.84 0.33
April 18.40 7.02
May 20.85 14.19
June 22.47 19.16
July 23.08 20.92
August 22.71 20.05
September 21.26 15.39
October 18.56 7.43
November 15.95 -0.0
December 13.77 -7.6
     
Annual Sum or Average 18.30 6.46
Minimum of Months 12.63 -12.6
Maximum of Months 23.08 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -12.6
February 21.11 -7.7
March 21.18 0.33
April 21.56 7.02
May 22.38 14.19
June 23.10 19.16
July 23.47 20.92
August 23.30 20.05
September 22.56 15.39
October 21.43 7.43
November 21.23 -0.0
December 21.11 -7.6
     
Annual Sum or Average 21.97 6.46
Minimum of Months 21.11 -12.6
Maximum of Months 23.47 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -12.6
February 20.97 -7.7
March 21.56 0.33
April 22.19 7.02
May 22.93 14.19
June 23.37 19.16
July 23.55 20.92
August 23.46 20.05
September 23.00 15.39
October 22.24 7.43
November 21.62 -0.0
December 20.93 -7.6
     
Annual Sum or Average 22.21 6.46
Minimum of Months 20.60 -12.6
Maximum of Months 23.55 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.13 -12.6
February 21.16 -7.7
March 21.44 0.33
April 22.04 7.02
May 23.22 14.19
June 23.58 19.16
July 23.76 20.92
August 23.72 20.05
September 23.24 15.39
October 22.11 7.43
November 21.55 -0.0
December 21.15 -7.6
     
Annual Sum or Average 22.35 6.46
Minimum of Months 21.13 -12.6
Maximum of Months 23.76 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.88 -12.6
February 23.13 -7.7
March 23.74 0.33
April 24.53 7.02
May 25.54 14.19
June 26.09 19.16
July 26.35 20.92
August 26.28 20.05
September 25.78 15.39
October 24.78 7.43
November 23.94 -0.0
December 23.15 -7.6
     
Annual Sum or Average 24.69 6.46
Minimum of Months 22.88 -12.6
Maximum of Months 26.35 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -12.6
February 18.94 -7.7
March 19.42 0.33
April 20.45 7.02
May 22.09 14.19
June 22.82 19.16
July 23.16 20.92
August 23.05 20.05
September 22.24 15.39
October 20.61 7.43
November 19.62 -0.0
December 18.90 -7.6
     
Annual Sum or Average 20.86 6.46
Minimum of Months 18.90 -12.6
Maximum of Months 23.16 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.90 -7.7
March 19.27 0.33
April 20.20 7.02
May 21.79 14.19
June 22.63 19.16
July 23.03 20.92
August 22.88 20.05
September 21.97 15.39
October 20.25 7.43
November 19.45 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.69 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.03 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -12.6
February 20.50 -7.7
March 20.66 0.33
April 21.00 7.02
May 21.54 14.19
June 21.67 19.16
July 21.74 20.92
August 21.74 20.05
September 21.56 15.39
October 21.09 7.43
November 20.74 -0.0
December 20.48 -7.6
     
Annual Sum or Average 21.10 6.46
Minimum of Months 20.47 -12.6
Maximum of Months 21.74 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -12.6
February 20.66 -7.7
March 20.87 0.33
April 21.21 7.02
May 21.63 14.19
June 21.70 19.16
July 21.75 20.92
August 21.74 20.05
September 21.65 15.39
October 21.39 7.43
November 20.93 -0.0
December 20.59 -7.6
     
Annual Sum or Average 21.22 6.46
Minimum of Months 20.52 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.77 -12.6
February 21.01 -7.7
March 21.29 0.33
April 21.51 7.02
May 21.73 14.19
June 21.74 19.16
July 21.75 20.92
August 21.75 20.05
September 21.73 15.39
October 21.65 7.43
November 21.30 -0.0
December 20.97 -7.6
     
Annual Sum or Average 21.44 6.46
Minimum of Months 20.77 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.16 -12.6
February 21.63 -7.7
March 22.12 0.33
April 22.32 7.02
May 22.52 14.19
June 22.50 19.16
July 22.48 20.92
August 22.48 20.05
September 22.38 15.39
October 22.30 7.43
November 22.06 -0.0
December 21.57 -7.6
     
Annual Sum or Average 22.13 6.46
Minimum of Months 21.16 -12.6
Maximum of Months 22.52 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 49.50 -12.6
February 49.98 -7.7
March 50.57 0.33
April 51.32 7.02
May 52.06 14.19
June 52.55 19.16
July 52.84 20.92
August 52.77 20.05
September 52.40 15.39
October 51.62 7.43
November 50.63 -0.0
December 49.87 -7.6
     
Annual Sum or Average 51.35 6.46
Minimum of Months 49.50 -12.6
Maximum of Months 52.84 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 66.27 -12.6
February 66.68 -7.7
March 67.31 0.33
April 68.31 7.02
May 69.39 14.19
June 70.08 19.16
July 70.46 20.92
August 70.28 20.05
September 69.74 15.39
October 68.66 7.43
November 67.47 -0.0
December 66.62 -7.6
     
Annual Sum or Average 68.45 6.46
Minimum of Months 66.27 -12.6
Maximum of Months 70.46 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -12.6
February 22.16 -7.7
March 22.68 0.33
April 23.12 7.02
May 23.57 14.19
June 23.77 19.16
July 23.86 20.92
August 23.84 20.05
September 23.61 15.39
October 23.20 7.43
November 22.67 -0.0
December 22.07 -7.6
     
Annual Sum or Average 23.03 6.46
Minimum of Months 21.72 -12.6
Maximum of Months 23.86 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.23 -12.6
February 21.45 -7.7
March 21.90 0.33
April 22.57 7.02
May 23.50 14.19
June 23.76 19.16
July 23.87 20.92
August 23.86 20.05
September 23.52 15.39
October 22.80 7.43
November 22.00 -0.0
December 21.34 -7.6
     
Annual Sum or Average 22.66 6.46
Minimum of Months 21.23 -12.6
Maximum of Months 23.87 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.81 -12.6
February 13.22 -7.7
March 15.51 0.33
April 18.46 7.02
May 21.30 14.19
June 23.18 19.16
July 23.93 20.92
August 23.54 20.05
September 22.00 15.39
October 18.85 7.43
November 15.66 -0.0
December 13.13 -7.6
     
Annual Sum or Average 18.41 6.46
Minimum of Months 11.81 -12.6
Maximum of Months 23.93 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.02 -12.6
February 17.81 -7.7
March 19.09 0.33
April 20.80 7.02
May 22.51 14.19
June 23.56 19.16
July 24.00 20.92
August 23.83 20.05
September 22.99 15.39
October 21.17 7.43
November 19.26 -0.0
December 17.69 -7.6
     
Annual Sum or Average 20.83 6.46
Minimum of Months 17.02 -12.6
Maximum of Months 24.00 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.37 -12.6
February 12.90 -7.7
March 15.35 0.33
April 18.63 7.02
May 21.67 14.19
June 23.56 19.16
July 24.31 20.92
August 23.86 20.05
September 22.21 15.39
October 18.91 7.43
November 15.44 -0.0
December 12.75 -7.6
     
Annual Sum or Average 18.44 6.46
Minimum of Months 11.37 -12.6
Maximum of Months 24.31 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -12.6
February 21.20 -7.7
March 21.63 0.33
April 22.51 7.02
May 23.70 14.19
June 23.85 19.16
July 23.90 20.92
August 23.90 20.05
September 23.63 15.39
October 22.73 7.43
November 21.79 -0.0
December 21.13 -7.6
     
Annual Sum or Average 22.60 6.46
Minimum of Months 21.12 -12.6
Maximum of Months 23.90 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.17 -12.6
February 11.73 -7.7
March 14.30 0.33
April 17.57 7.02
May 20.80 14.19
June 22.84 19.16
July 23.59 20.92
August 23.10 20.05
September 21.24 15.39
October 17.65 7.43
November 14.37 -0.0
December 11.57 -7.6
     
Annual Sum or Average 17.44 6.46
Minimum of Months 10.17 -12.6
Maximum of Months 23.59 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 19.10 0.33
April 19.97 7.02
May 21.93 14.19
June 22.79 19.16
July 23.23 20.92
August 23.13 20.05
September 21.96 15.39
October 19.67 7.43
November 19.22 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.65 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.23 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -12.6
February 20.56 -7.7
March 20.78 0.33
April 21.13 7.02
May 21.67 14.19
June 21.72 19.16
July 21.75 20.92
August 21.75 20.05
September 21.64 15.39
October 21.23 7.43
November 20.83 -0.0
December 20.50 -7.6
     
Annual Sum or Average 21.17 6.46
Minimum of Months 20.49 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -12.6
February 20.58 -7.7
March 20.81 0.33
April 21.17 7.02
May 21.68 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.66 15.39
October 21.28 7.43
November 20.87 -0.0
December 20.51 -7.6
     
Annual Sum or Average 21.19 6.46
Minimum of Months 20.49 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -12.6
February 20.58 -7.7
March 20.82 0.33
April 21.19 7.02
May 21.69 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.67 15.39
October 21.32 7.43
November 20.89 -0.0
December 20.51 -7.6
     
Annual Sum or Average 21.20 6.46
Minimum of Months 20.49 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -12.6
February 20.49 -7.7
March 20.64 0.33
April 20.98 7.02
May 21.58 14.19
June 21.69 19.16
July 21.75 20.92
August 21.75 20.05
September 21.57 15.39
October 21.04 7.43
November 20.71 -0.0
December 20.47 -7.6
     
Annual Sum or Average 21.10 6.46
Minimum of Months 20.47 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -12.6
February 20.67 -7.7
March 20.90 0.33
April 21.27 7.02
May 21.70 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.69 15.39
October 21.46 7.43
November 20.95 -0.0
December 20.58 -7.6
     
Annual Sum or Average 21.25 6.46
Minimum of Months 20.52 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 -12.6
February 21.85 -7.7
March 22.65 0.33
April 23.09 7.02
May 23.33 14.19
June 23.33 19.16
July 23.33 20.92
August 23.33 20.05
September 23.32 15.39
October 23.24 7.43
November 22.53 -0.0
December 21.73 -7.6
     
Annual Sum or Average 22.74 6.46
Minimum of Months 21.07 -12.6
Maximum of Months 23.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 28.79 -12.6
February 29.27 -7.7
March 30.00 0.33
April 31.14 7.02
May 32.42 14.19
June 33.03 19.16
July 33.33 20.92
August 33.20 20.05
September 32.63 15.39
October 31.37 7.43
November 30.09 -0.0
December 29.13 -7.6
     
Annual Sum or Average 31.21 6.46
Minimum of Months 28.79 -12.6
Maximum of Months 33.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.69 -12.6
February 21.72 -7.7
March 21.84 0.33
April 22.08 7.02
May 22.42 14.19
June 22.78 19.16
July 22.93 20.92
August 22.88 20.05
September 22.52 15.39
October 22.05 7.43
November 21.85 -0.0
December 21.72 -7.6
     
Annual Sum or Average 22.21 6.46
Minimum of Months 21.69 -12.6
Maximum of Months 22.93 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -12.6
February 20.82 -7.7
March 21.10 0.33
April 21.39 7.02
May 21.73 14.19
June 21.74 19.16
July 21.75 20.92
August 21.75 20.05
September 21.72 15.39
October 21.57 7.43
November 21.12 -0.0
December 20.75 -7.6
     
Annual Sum or Average 21.34 6.46
Minimum of Months 20.60 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -12.6
February 20.67 -7.7
March 20.91 0.33
April 21.26 7.02
May 21.70 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.69 15.39
October 21.45 7.43
November 20.96 -0.0
December 20.60 -7.6
     
Annual Sum or Average 21.25 6.46
Minimum of Months 20.52 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.17 -12.6
February 16.17 -7.7
March 17.76 0.33
April 20.08 7.02
May 22.43 14.19
June 23.81 19.16
July 24.37 20.92
August 24.09 20.05
September 22.95 15.39
October 20.42 7.43
November 17.92 -0.0
December 15.90 -7.6
     
Annual Sum or Average 20.11 6.46
Minimum of Months 15.17 -12.6
Maximum of Months 24.37 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 9.70 -12.6
February 11.30 -7.7
March 13.95 0.33
April 17.76 7.02
May 21.53 14.19
June 23.89 19.16
July 24.80 20.92
August 24.24 20.05
September 22.28 15.39
October 18.13 7.43
November 14.11 -0.0
December 10.99 -7.6
     
Annual Sum or Average 17.76 6.46
Minimum of Months 9.70 -12.6
Maximum of Months 24.80 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.37 -12.6
February 11.94 -7.7
March 14.47 0.33
April 18.02 7.02
May 21.46 14.19
June 23.59 19.16
July 24.44 20.92
August 23.91 20.05
September 21.99 15.39
October 18.21 7.43
November 14.53 -0.0
December 11.71 -7.6
     
Annual Sum or Average 17.92 6.46
Minimum of Months 10.37 -12.6
Maximum of Months 24.44 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -12.6
February 21.11 -7.7
March 21.22 0.33
April 21.80 7.02
May 23.14 14.19
June 23.60 19.16
July 23.87 20.92
August 23.83 20.05
September 23.11 15.39
October 21.60 7.43
November 21.32 -0.0
December 21.11 -7.6
     
Annual Sum or Average 22.24 6.46
Minimum of Months 21.11 -12.6
Maximum of Months 23.87 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.53 -12.6
February 10.24 -7.7
March 13.07 0.33
April 16.68 7.02
May 20.45 14.19
June 22.88 19.16
July 23.80 20.92
August 23.21 20.05
September 20.91 15.39
October 16.61 7.43
November 13.08 -0.0
December 10.06 -7.6
     
Annual Sum or Average 16.66 6.46
Minimum of Months 8.53 -12.6
Maximum of Months 23.80 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 18.97 0.33
April 19.72 7.02
May 21.54 14.19
June 22.61 19.16
July 23.17 20.92
August 23.03 20.05
September 21.61 15.39
October 19.27 7.43
November 19.03 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.48 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.17 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 19.03 0.33
April 19.84 7.02
May 21.73 14.19
June 22.71 19.16
July 23.22 20.92
August 23.11 20.05
September 21.76 15.39
October 19.42 7.43
November 19.11 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.56 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.22 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 19.07 0.33
April 19.90 7.02
May 21.81 14.19
June 22.74 19.16
July 23.21 20.92
August 23.10 20.05
September 21.80 15.39
October 19.51 7.43
November 19.15 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.59 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.21 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -12.6
February 20.54 -7.7
March 20.76 0.33
April 21.12 7.02
May 21.66 14.19
June 21.72 19.16
July 21.75 20.92
August 21.75 20.05
September 21.63 15.39
October 21.21 7.43
November 20.81 -0.0
December 20.49 -7.6
     
Annual Sum or Average 21.16 6.46
Minimum of Months 20.48 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 18.98 0.33
April 19.78 7.02
May 21.60 14.19
June 22.68 19.16
July 23.19 20.92
August 23.07 20.05
September 21.71 15.39
October 19.36 7.43
November 19.12 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.52 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.19 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -12.6
February 20.57 -7.7
March 20.75 0.33
April 21.12 7.02
May 21.64 14.19
June 21.70 19.16
July 21.75 20.92
August 21.75 20.05
September 21.63 15.39
October 21.28 7.43
November 20.82 -0.0
December 20.51 -7.6
     
Annual Sum or Average 21.17 6.46
Minimum of Months 20.49 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -12.6
February 20.84 -7.7
March 21.12 0.33
April 21.42 7.02
May 21.73 14.19
June 21.75 19.16
July 21.75 20.92
August 21.75 20.05
September 21.73 15.39
October 21.60 7.43
November 21.13 -0.0
December 20.75 -7.6
     
Annual Sum or Average 21.35 6.46
Minimum of Months 20.60 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.08 -12.6
February 20.74 -7.7
March 21.71 0.33
April 23.20 7.02
May 24.92 14.19
June 25.68 19.16
July 26.02 20.92
August 25.88 20.05
September 25.08 15.39
October 23.37 7.43
November 21.75 -0.0
December 20.51 -7.6
     
Annual Sum or Average 23.26 6.46
Minimum of Months 20.08 -12.6
Maximum of Months 26.02 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.09 -12.6
February 19.64 -7.7
March 20.49 0.33
April 21.76 7.02
May 23.12 14.19
June 23.27 19.16
July 23.33 20.92
August 23.33 20.05
September 23.03 15.39
October 22.17 7.43
November 20.55 -0.0
December 19.27 -7.6
     
Annual Sum or Average 21.60 6.46
Minimum of Months 19.09 -12.6
Maximum of Months 23.33 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.54 -12.6
February 20.73 -7.7
March 20.98 0.33
April 21.29 7.02
May 21.70 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.69 15.39
October 21.47 7.43
November 21.00 -0.0
December 20.65 -7.6
     
Annual Sum or Average 21.28 6.46
Minimum of Months 20.54 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -12.6
February 18.94 -7.7
March 19.30 0.33
April 20.35 7.02
May 22.20 14.19
June 22.87 19.16
July 23.24 20.92
August 23.18 20.05
September 22.29 15.39
October 20.42 7.43
November 19.50 -0.0
December 18.90 -7.6
     
Annual Sum or Average 20.85 6.46
Minimum of Months 18.90 -12.6
Maximum of Months 23.24 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.83 -12.6
February 14.87 -7.7
March 16.58 0.33
April 19.27 7.02
May 22.17 14.19
June 23.87 19.16
July 24.57 20.92
August 24.20 20.05
September 22.70 15.39
October 19.51 7.43
November 16.74 -0.0
December 14.50 -7.6
     
Annual Sum or Average 19.42 6.46
Minimum of Months 13.83 -12.6
Maximum of Months 24.57 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.78 -12.6
February 10.31 -7.7
March 12.86 0.33
April 17.05 7.02
May 21.32 14.19
June 23.98 19.16
July 25.02 20.92
August 24.35 20.05
September 22.07 15.39
October 17.32 7.43
November 13.08 -0.0
December 9.78 -7.6
     
Annual Sum or Average 17.20 6.46
Minimum of Months 8.78 -12.6
Maximum of Months 25.02 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 9.14 -12.6
February 10.81 -7.7
March 13.35 0.33
April 17.25 7.02
May 21.18 14.19
June 23.66 19.16
July 24.66 20.92
August 24.01 20.05
September 21.60 15.39
October 17.22 7.43
November 13.30 -0.0
December 10.35 -7.6
     
Annual Sum or Average 17.25 6.46
Minimum of Months 9.14 -12.6
Maximum of Months 24.66 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -12.6
February 21.11 -7.7
March 21.21 0.33
April 21.72 7.02
May 22.72 14.19
June 23.37 19.16
July 23.71 20.92
August 23.56 20.05
September 22.70 15.39
October 21.43 7.43
November 21.20 -0.0
December 21.11 -7.6
     
Annual Sum or Average 22.08 6.46
Minimum of Months 21.11 -12.6
Maximum of Months 23.71 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 7.15 -12.6
February 9.09 -7.7
March 12.27 0.33
April 16.17 7.02
May 20.25 14.19
June 22.94 19.16
July 23.96 20.92
August 23.26 20.05
September 20.58 15.39
October 15.90 7.43
November 12.09 -0.0
December 8.86 -7.6
     
Annual Sum or Average 16.08 6.46
Minimum of Months 7.15 -12.6
Maximum of Months 23.96 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.46 -12.6
February 20.45 -7.7
March 20.58 0.33
April 20.92 7.02
May 21.59 14.19
June 21.68 19.16
July 21.75 20.92
August 21.75 20.05
September 21.51 15.39
October 20.83 7.43
November 20.61 -0.0
December 20.46 -7.6
     
Annual Sum or Average 21.05 6.46
Minimum of Months 20.45 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 19.02 0.33
April 19.76 7.02
May 21.41 14.19
June 22.44 19.16
July 23.02 20.92
August 22.80 20.05
September 21.36 15.39
October 19.28 7.43
November 19.00 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.41 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.02 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 19.04 0.33
April 19.79 7.02
May 21.45 14.19
June 22.45 19.16
July 23.00 20.92
August 22.78 20.05
September 21.37 15.39
October 19.32 7.43
November 19.02 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.42 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.00 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -12.6
February 20.51 -7.7
March 20.73 0.33
April 21.13 7.02
May 21.69 14.19
June 21.72 19.16
July 21.75 20.92
August 21.75 20.05
September 21.63 15.39
October 21.17 7.43
November 20.76 -0.0
December 20.48 -7.6
     
Annual Sum or Average 21.15 6.46
Minimum of Months 20.47 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.89 -7.7
March 18.99 0.33
April 19.74 7.02
May 21.37 14.19
June 22.44 19.16
July 23.02 20.92
August 22.81 20.05
September 21.38 15.39
October 19.25 7.43
November 19.01 -0.0
December 18.89 -7.6
     
Annual Sum or Average 20.40 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.02 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -12.6
February 18.94 -7.7
March 19.21 0.33
April 20.12 7.02
May 21.74 14.19
June 22.58 19.16
July 23.06 20.92
August 22.90 20.05
September 21.75 15.39
October 19.90 7.43
November 19.27 -0.0
December 18.90 -7.6
     
Annual Sum or Average 20.62 6.46
Minimum of Months 18.89 -12.6
Maximum of Months 23.06 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 -12.6
February 20.71 -7.7
March 20.99 0.33
April 21.30 7.02
May 21.72 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.70 15.39
October 21.49 7.43
November 20.97 -0.0
December 20.61 -7.6
     
Annual Sum or Average 21.27 6.46
Minimum of Months 20.53 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.55 -12.6
February 18.33 -7.7
March 19.54 0.33
April 21.19 7.02
May 23.06 14.19
June 24.08 19.16
July 24.49 20.92
August 24.25 20.05
September 23.14 15.39
October 21.15 7.43
November 19.41 -0.0
December 18.07 -7.6
     
Annual Sum or Average 21.20 6.46
Minimum of Months 17.55 -12.6
Maximum of Months 24.49 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.51 -12.6
February 20.68 -7.7
March 20.93 0.33
April 21.28 7.02
May 21.72 14.19
June 21.73 19.16
July 21.76 20.92
August 21.75 20.05
September 21.69 15.39
October 21.46 7.43
November 20.94 -0.0
December 20.57 -7.6
     
Annual Sum or Average 21.25 6.46
Minimum of Months 20.51 -12.6
Maximum of Months 21.76 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.52 -12.6
February 20.70 -7.7
March 20.96 0.33
April 21.28 7.02
May 21.72 14.19
June 21.73 19.16
July 21.75 20.92
August 21.75 20.05
September 21.69 15.39
October 21.46 7.43
November 20.95 -0.0
December 20.59 -7.6
     
Annual Sum or Average 21.26 6.46
Minimum of Months 20.52 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -12.6
February 20.57 -7.7
March 20.74 0.33
April 21.12 7.02
May 21.67 14.19
June 21.72 19.16
July 21.75 20.92
August 21.75 20.05
September 21.63 15.39
October 21.26 7.43
November 20.79 -0.0
December 20.50 -7.6
     
Annual Sum or Average 21.17 6.46
Minimum of Months 20.48 -12.6
Maximum of Months 21.75 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.97 -12.6
February 14.15 -7.7
March 16.11 0.33
April 18.98 7.02
May 22.05 14.19
June 23.87 19.16
July 24.59 20.92
August 24.14 20.05
September 22.40 15.39
October 19.04 7.43
November 16.08 -0.0
December 13.68 -7.6
     
Annual Sum or Average 19.03 6.46
Minimum of Months 12.97 -12.6
Maximum of Months 24.59 20.92



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.23 -12.6
February 9.62 -7.7
March 12.17 0.33
April 16.58 7.02
May 21.16 14.19
June 24.03 19.16
July 25.12 20.92
August 24.35 20.05
September 21.73 15.39
October 16.66 7.43
November 12.32 -0.0
December 8.86 -7.6
     
Annual Sum or Average 16.77 6.46
Minimum of Months 8.23 -12.6
Maximum of Months 25.12 20.92



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:37

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.250668E+12 194025.735 19-JAN-07:15 15177.258 39465.561 8767.924 126418.879 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.194339E+12 205907.427 02-FEB-07:15 15177.258 39465.561 8800.952 138267.543 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.166135E+12 143944.669 06-MAR-07:15 15177.258 39465.561 8733.209 80451.013 109.514 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.139335E+12 116835.707 03-APR-06:15 15177.258 39465.561 8712.865 53299.411 172.499 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.137046E+12 86045.611 28-MAY-07:00 17566.637 43276.576 9110.625 0.000 16083.661 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.146454E+12 96492.702 30-JUN-07:00 17492.219 43276.576 9110.625 0.000 26605.170 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.157297E+12 94292.518 04-JUL-07:00 17492.219 43276.576 9110.625 0.000 24404.986 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.154523E+12 101784.971 04-AUG-07:00 17492.219 43276.576 9110.625 0.000 31897.439 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.137992E+12 89592.120 08-SEP-07:00 17641.054 43276.576 9110.625 0.000 19555.753 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.136209E+12 97982.650 23-OCT-06:15 15177.258 39465.561 8706.324 29956.109 481.284 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.170522E+12 179977.893 26-NOV-07:15 15177.258 39465.561 8741.851 112353.780 43.330 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.219013E+12 189992.453 09-DEC-07:15 13316.689 34010.661 8766.696 129702.294 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.200953E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.136209E+12 86045.611   13316.689 34010.661 8706.324 0.000 0.000 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.250668E+12 205907.427   17641.054 43276.576 9110.625 138267.543 31897.439 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:37

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.146548E+12 131397.788 19-JAN-09:15 29063.792 40096.028 0.000 62237.968 62237.968 62237.968 29063.792
February 0.124104E+12 137259.763 02-FEB-09:15 34285.658 40096.028 0.000 62878.077 62878.077 62878.077 34285.658
March 0.120477E+12 114826.980 04-MAR-10:00 12340.676 40096.028 0.000 62390.276 62390.276 62390.276 12340.676
April 0.104196E+12 111921.201 01-APR-09:45 10794.971 40096.028 0.000 61030.202 61030.202 61030.202 10794.971
May 0.962758E+11 101544.411 02-MAY-10:15 2545.983 40096.028 0.000 58902.400 58902.400 58902.400 2545.983
June 0.884838E+11 97620.166 02-JUN-08:30 0.000 40096.028 0.000 57524.138 57524.138 57524.138 0.000
July 0.881160E+11 95150.875 01-JUL-08:15 0.000 40096.028 0.000 55054.847 55054.847 55054.847 0.000
August 0.868154E+11 93015.069 04-AUG-08:15 0.000 40096.028 0.000 52919.041 52919.041 52919.041 0.000
September 0.859702E+11 95486.495 30-SEP-09:15 2084.309 40096.028 0.000 53306.158 53306.158 53306.158 2084.309
October 0.958872E+11 100380.597 28-OCT-09:15 4605.642 40096.028 0.000 55678.927 55678.927 55678.927 4605.642
November 0.110347E+12 117838.094 25-NOV-09:15 17787.408 40096.028 0.000 59954.658 59954.658 59954.658 17787.408
December 0.132912E+12 128313.022 09-DEC-11:30 30517.545 40096.028 0.000 57699.448 57699.448 57699.448 30517.545
                     
Annual Sum or Average 0.128013E+13         0.000        
Minimum of Months 0.859702E+11 93015.069   0.000 40096.028 0.000 52919.041 52919.041 52919.041 0.000
Maximum of Months 0.146548E+12 137259.763   34285.658 40096.028 0.000 62878.077 62878.077 62878.077 34285.658