Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2018-10-19 10:15:40


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3767.62 938.72 1011.42
Net Site Energy 3767.62 938.72 1011.42
Total Source Energy 8744.74 2178.79 2347.52
Net Source Energy 8744.74 2178.79 2347.52


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 775.50 319.44 0.00 0.00 0.00 0.00
Cooling 111.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting 415.21 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.29 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 278.84 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 789.23 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2237.46 1530.16 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 775.50 319.44 0.00 0.00 0.00 0.00
Cooling General 111.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 415.21 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.29 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 278.84 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 789.23 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.99 0.00 0.00 0.00 0.00 0.00
HVAC 313.00 297.62 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 600.65 410.77 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.72 0.00 0.00 0.00 0.00 0.00
HVAC 290.50 276.23 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 557.47 381.24 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2237.46 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2237.46 100.00
     
Total On-Site and Utility Electric Sources 2237.46 100.00
Total Electricity End Uses 2237.46 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 2740.00
Time Setpoint Not Met During Occupied Cooling 1823.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6532.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.210 0.217 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.210 0.217 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.210 0.217 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.210 0.217 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.210 0.217 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 4.44 0.00 0.00 4.44 4.44 2.670 0.479 0.381     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.670 0.479 0.381              
North Total or Average           96.82 2.670 0.479 0.381              
Non-North Total or Average           87.38 2.670 0.479 0.381              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   5877.42 4694.03 1183.39 0.80 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   12389.35 9601.28 2788.07 0.77 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   6518.35 4844.04 1674.31 0.74 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   11931.59 9529.23 2402.36 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 5601.9 3.15 10.76 11.39 10.54
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 11845.9 3.19 10.90 11.54 10.75
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 6258.8 3.25 11.09 11.75 11.04
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 11372.3 3.15 10.76 11.39 10.54
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.40 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   53556.02 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1564.20 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1607.79 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1899.86 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1901.88 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1610.70 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.32 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.40 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   4245.08 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1741.37 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   5987.31 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   4745.15 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   5987.31 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1761.57 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1721.39 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   5986.89 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1496.72 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   5986.89 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1654.73 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.32 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.40 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   4245.08 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1800.60 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   6029.93 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   4939.65 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   6019.48 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1865.91 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1809.91 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   5988.89 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1532.37 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   5986.89 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1765.86 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.32 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   316.40 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   6480.73 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   2334.30 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   7907.36 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   6494.59 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   7916.63 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2490.28 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   2429.60 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   7875.76 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   2124.47 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   7823.34 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   2386.67 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   679.21 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   6313.05 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   25833.24 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   13833.51 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   10624.76 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.36 397.70 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.70 784.31 1120.11 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.33 374.47 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.72 798.03 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 6967.88 8361.46 0.584 0.700 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 27.25 0.00698
RESTROOMFLR1 365.26 438.31 0.031 0.037 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 26.18 0.00698
MEETINGROOMFLR1 3324.51 3989.41 0.279 0.334 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM101 468.34 562.00 0.054 0.065 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM102 374.37 449.25 0.044 0.052 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM103 934.51 1121.41 0.109 0.130 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM104 1260.35 1512.42 0.147 0.176 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM105 1666.64 1999.97 0.194 0.233 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
EMPLOYEELOUNGEFLR1 5561.98 6674.37 0.466 0.559 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
EXERCISECENTERFLR1 1245.34 1494.41 0.104 0.125 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 25.97 0.00698
FRONTOFFICEFLR1 3536.06 4243.28 0.296 0.355 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
GUESTROOM201 605.07 726.08 0.070 0.084 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 27.27 0.00698
GUESTROOM202_205 3861.84 4634.21 0.449 0.539 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM206_208 3166.59 3799.91 0.368 0.442 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM209_212 3686.19 4423.42 0.429 0.515 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM213 1013.25 1215.90 0.118 0.141 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM214 1392.85 1671.42 0.162 0.194 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM215_218 10144.65 12173.58 1.180 1.416 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM219 5611.15 6733.38 0.653 0.783 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM220_223 5014.93 6017.91 0.583 0.700 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
GUESTROOM224 1402.52 1683.03 0.163 0.196 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
GUESTROOM301 417.36 500.83 0.049 0.058 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
GUESTROOM302_305 1290.40 1548.48 0.150 0.180 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM306_308 1168.39 1402.07 0.136 0.163 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM309_312 3631.17 4357.40 0.422 0.507 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM313 506.52 607.83 0.059 0.071 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:15:00 21.15 0.00698
GUESTROOM314 1303.06 1563.67 0.152 0.182 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM315_318 5439.58 6527.49 0.633 0.759 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM319 1226.69 1472.03 0.143 0.171 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM320_323 4797.40 5756.88 0.558 0.670 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM324 816.90 980.28 0.095 0.114 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM401 1169.15 1402.99 0.136 0.163 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 27.40 0.00698
GUESTROOM402_405 1787.43 2144.92 0.208 0.250 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM406_408 1550.50 1860.60 0.180 0.216 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM409_412 4424.75 5309.70 0.515 0.618 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 27.40 0.00698
GUESTROOM413 672.26 806.71 0.078 0.094 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 26.94 0.00698
GUESTROOM414 1055.52 1266.62 0.123 0.147 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
GUESTROOM415_418 6033.50 7240.20 0.702 0.842 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
GUESTROOM419 1634.98 1961.97 0.190 0.228 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
GUESTROOM420_423 5980.76 7176.91 0.696 0.835 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 27.40 0.00698
GUESTROOM424 1627.42 1952.90 0.189 0.227 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 27.40 0.00698
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
CORRIDORFLR1 12582.58 15099.10 1.052 1.263 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 24.95 0.00698
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
CORRIDORFLR2 2615.58 3138.70 0.219 0.263 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 25.46 0.00698
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
CORRIDORFLR3 1197.00 1436.40 0.100 0.120 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 25.21 0.00698
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698
CORRIDORFLR4 1855.14 2226.16 0.155 0.186 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 26.79 0.00698
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   27.40 0.00698


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2904.87 3485.84 0.083 0.236 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -41.90 0.00006
RESTROOMFLR1 247.11 296.53 0.007 0.008 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -41.90 0.00006
MEETINGROOMFLR1 1053.90 1264.68 0.030 0.126 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -41.90 0.00006
GUESTROOM101 448.25 537.90 0.013 0.015 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -41.90 0.00006
GUESTROOM102 484.58 581.49 0.014 0.017 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -41.90 0.00006
GUESTROOM103 727.97 873.56 0.021 0.025 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -41.90 0.00006
GUESTROOM104 729.71 875.66 0.021 0.025 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:45:00 -41.90 0.00006
GUESTROOM105 487.06 584.48 0.014 0.017 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:45:00 -41.90 0.00006
EMPLOYEELOUNGEFLR1 487.84 585.41 0.014 0.051 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90 0.00006
EXERCISECENTERFLR1 370.32 444.38 0.011 0.043 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -41.90 0.00006
FRONTOFFICEFLR1 1765.06 2118.07 0.051 0.061 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -41.90 0.00006
GUESTROOM201 595.90 715.08 0.017 0.020 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -41.90 0.00006
GUESTROOM202_205 1428.30 1713.96 0.041 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -41.90 0.00006
GUESTROOM206_208 1163.77 1396.52 0.033 0.043 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
GUESTROOM209_212 1321.57 1585.88 0.038 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -41.90 0.00006
GUESTROOM213 612.73 735.27 0.018 0.021 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:30:00 -41.90 0.00006
GUESTROOM214 579.30 695.16 0.017 0.020 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -41.90 0.00006
GUESTROOM215_218 1347.91 1617.49 0.039 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -41.90 0.00006
GUESTROOM219 340.98 409.18 0.010 0.013 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -41.90 0.00006
GUESTROOM220_223 1266.49 1519.79 0.036 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -41.90 0.00006
GUESTROOM224 523.76 628.51 0.015 0.018 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:30:00 -41.90 0.00006
GUESTROOM301 645.25 774.30 0.018 0.022 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -41.90 0.00006
GUESTROOM302_305 1603.95 1924.74 0.046 0.055 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -41.90 0.00006
GUESTROOM306_308 1405.12 1686.15 0.040 0.048 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -41.90 0.00006
GUESTROOM309_312 1595.25 1914.29 0.046 0.055 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:15:00 -41.90 0.00006
GUESTROOM313 699.68 839.62 0.020 0.024 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90 0.00006
GUESTROOM314 653.07 783.69 0.019 0.022 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:15:00 -41.90 0.00006
GUESTROOM315_318 1570.00 1884.00 0.045 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -41.90 0.00006
GUESTROOM319 421.79 506.15 0.012 0.014 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -41.90 0.00006
GUESTROOM320_323 1522.78 1827.34 0.044 0.054 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -41.90 0.00006
GUESTROOM324 616.36 739.64 0.018 0.021 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:00:00 -41.90 0.00006
GUESTROOM401 1090.00 1308.01 0.031 0.037 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:00:00 -41.90 0.00006
GUESTROOM402_405 3168.48 3802.18 0.091 0.109 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 21:30:00 -41.90 0.00006
GUESTROOM406_408 2700.91 3241.09 0.077 0.093 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:45:00 -41.90 0.00006
GUESTROOM409_412 3176.20 3811.44 0.091 0.109 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -41.90 0.00006
GUESTROOM413 1219.99 1463.99 0.035 0.042 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90 0.00006
GUESTROOM414 1169.48 1403.37 0.033 0.040 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90 0.00006
GUESTROOM415_418 3142.38 3770.86 0.090 0.108 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -41.90 0.00006
GUESTROOM419 915.21 1098.25 0.026 0.031 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -41.90 0.00006
GUESTROOM420_423 3098.70 3718.44 0.089 0.106 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -41.90 0.00006
GUESTROOM424 1133.71 1360.45 0.032 0.039 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -41.90 0.00006
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
CORRIDORFLR1 41677.38 50012.86 1.192 1.430 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -41.90 0.00006
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
CORRIDORFLR2 728.64 874.36 0.021 0.038 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -41.90 0.00006
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
CORRIDORFLR3 1004.56 1205.48 0.029 0.038 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:15:00 -41.90 0.00006
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB   -41.90 0.00006
CORRIDORFLR4 2975.09 3570.11 0.085 0.102 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:15:00 -41.90 0.00006
FRONTSTAIRSFLR4 55.58 66.70 0.001 0.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:15:00 -41.90 0.00006


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.36 0.36 0.06 0.06
SAC_FRONTLOUNGE 0.70 0.70 0.24 0.24
SAC_MEETINGROOM 0.33 0.33 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.72 0.72 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 4105.50 8041.25 4076.25
RESTROOMFLR1 3454.75 8669.50 3454.75
MEETINGROOMFLR1 1617.75 4117.25 1544.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 4491.25 8760.00 4491.25
GUESTROOM104 3826.25 8760.00 3826.25
GUESTROOM105 1945.75 8683.25 1945.75
EMPLOYEELOUNGEFLR1 2435.50 3281.75 804.25
EXERCISECENTERFLR1 1067.75 4198.50 656.25
FRONTOFFICEFLR1 3296.25 7806.00 3172.25
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 3866.50 8760.00 3866.50
GUESTROOM206_208 3717.75 8760.00 3717.75
GUESTROOM209_212 3445.75 8760.00 3445.75
GUESTROOM213 4437.25 8760.00 4437.25
GUESTROOM214 3364.25 8738.50 3364.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 2354.25 5286.50 58.75
GUESTROOM220_223 2197.25 8649.75 2197.25
GUESTROOM224 3469.00 8723.75 3469.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 3938.25 8760.00 3938.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 4029.25 8744.00 4029.25
GUESTROOM315_318 2309.75 8556.75 2309.75
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 3106.75 8677.50 3106.75
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 5211.25 8630.25 5211.25
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 4573.75 8527.75 4573.00
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 4115.00 8185.00 3994.00
GUESTROOM419 4079.50 8351.25 4060.75
GUESTROOM420_423 4187.50 8217.25 4079.50
GUESTROOM424 4591.50 8441.50 4577.75
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7559.00 8760.00 6532.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 1.00 0.00 1.00 0.00
RESTROOMFLR1 2536.25 97.50 2536.25 97.50
MEETINGROOMFLR1 0.50 0.00 0.50 0.00
GUESTROOM101 1.75 0.00 0.00 0.00
GUESTROOM102 0.50 0.00 0.00 0.00
GUESTROOM103 42.25 11.00 42.25 11.00
GUESTROOM104 32.75 18.00 32.75 18.00
GUESTROOM105 15.75 29.25 15.75 29.25
EMPLOYEELOUNGEFLR1 1570.25 522.25 1102.50 333.50
EXERCISECENTERFLR1 1.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.25 0.00 0.25 0.00
GUESTROOM201 1.75 0.00 0.00 0.00
GUESTROOM202_205 39.75 0.50 39.75 0.50
GUESTROOM206_208 38.50 5.25 38.50 5.25
GUESTROOM209_212 38.75 0.25 38.75 0.25
GUESTROOM213 41.00 0.00 41.00 0.00
GUESTROOM214 29.75 6.75 29.75 6.75
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 1466.25 0.00 1466.25
GUESTROOM220_223 21.50 3.75 21.50 3.75
GUESTROOM224 32.25 7.00 32.25 7.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.50 0.00 0.00 0.00
GUESTROOM306_308 0.25 0.25 0.00 0.00
GUESTROOM309_312 41.00 0.25 41.00 0.25
GUESTROOM313 0.25 0.00 0.00 0.00
GUESTROOM314 33.25 5.25 33.25 5.25
GUESTROOM315_318 24.00 7.00 24.00 7.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 30.50 3.00 30.50 3.00
GUESTROOM324 0.50 0.00 0.00 0.00
GUESTROOM401 26.75 6.25 26.75 6.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 30.50 2.75 30.50 2.75
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.25 0.00 0.00 0.00
GUESTROOM415_418 27.25 11.50 27.25 11.50
GUESTROOM419 22.00 15.75 22.00 15.75
GUESTROOM420_423 27.50 10.50 27.50 10.50
GUESTROOM424 18.00 13.75 18.00 13.75
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 1.00 1508.25 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR2 2.75 0.00 0.00 0.00
REARSTAIRSFLR3 1.25 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 9.50 0.00 0.00 0.00
REARSTAIRSFLR4 13.50 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR4 6.50 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 2778.75 2414.50 2740.00 1823.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:40

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.355055
SAC_FRONTLOUNGE SUPPLY FAN 0.700209
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.720788


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 316.40
CORRIDORFLR1 PTAC HEATING COIL 53556.02
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1564.20
102 PTAC HEATING COIL 1607.79
103 PTAC HEATING COIL 1899.86
104 PTAC HEATING COIL 1901.88
105 PTAC HEATING COIL 1610.70
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 316.32
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 316.40
CORRIDORFLR2 PTAC HEATING COIL 4245.08
201 PTAC HEATING COIL 1741.37
202_205 PTAC HEATING COIL 5987.31
206_208 PTAC HEATING COIL 4745.15
209_212 PTAC HEATING COIL 5987.31
213 PTAC HEATING COIL 1761.57
214 PTAC HEATING COIL 1721.39
215_218 PTAC HEATING COIL 5986.89
219 PTAC HEATING COIL 1496.72
220_223 PTAC HEATING COIL 5986.89
224 PTAC HEATING COIL 1654.73
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 316.32
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 316.40
CORRIDORFLR3 PTAC HEATING COIL 4245.08
301 PTAC HEATING COIL 1800.60
302_305 PTAC HEATING COIL 6029.93
306_308 PTAC HEATING COIL 4939.65
309_312 PTAC HEATING COIL 6019.48
313 PTAC HEATING COIL 1865.91
314 PTAC HEATING COIL 1809.91
315_318 PTAC HEATING COIL 5988.89
319 PTAC HEATING COIL 1532.37
320_323 PTAC HEATING COIL 5986.89
324 PTAC HEATING COIL 1765.86
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 316.32
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 316.40
CORRIDORFLR4 PTAC HEATING COIL 6480.73
401 PTAC HEATING COIL 2334.30
402_405 PTAC HEATING COIL 7907.36
406_408 PTAC HEATING COIL 6494.59
409_412 PTAC HEATING COIL 7916.63
413 PTAC HEATING COIL 2490.28
414 PTAC HEATING COIL 2429.60
415_418 PTAC HEATING COIL 7875.76
419 PTAC HEATING COIL 2124.47
420_423 PTAC HEATING COIL 7823.34
424 PTAC HEATING COIL 2386.67
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 679.21


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.798655 0.355055 5877.42
SAC_FRONTLOUNGE COOLING COIL 0.774963 0.700209 12389.35
SAC_MEETINGROOM COOLING COIL 0.743139 0.334314 6518.35
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.798655 0.720788 11931.59


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.700209
RESTROOMFLR1 DIRECT AIR 0.036670
MEETINGROOMFLR1 DIRECT AIR 0.334314
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.559027
EXERCISECENTERFLR1 DIRECT AIR 0.125090
FRONTOFFICEFLR1 DIRECT AIR 0.355055


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.355055
SAC_FRONTLOUNGE MAIN BRANCH 0.700209
SAC_MEETINGROOM MAIN BRANCH 0.334314
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.720788


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.355055
SAC_FRONTLOUNGE 0.700209
SAC_MEETINGROOM 0.334314
SAC_EXC_EMPLGE_RESTRM 0.720788


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.355055 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.700209 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.334314 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.720788 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.355055 0.355055 0.355055 0.355055 6313.05 5877.42 1.00
SAC_FRONTLOUNGE 0.700209 0.700209 0.700209 0.700209 25833.24 12389.35 1.00
SAC_MEETINGROOM 0.334314 0.334314 0.334314 0.334314 13833.51 6518.35 1.00
SAC_EXC_EMPLGE_RESTRM 0.720788 0.720788 0.720788 0.720788 10624.76 11931.59 0.173547


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 6313.05
SAC_FRONTLOUNGE HEATING COIL 25833.24
SAC_MEETINGROOM HEATING COIL 13833.51
SAC_EXC_EMPLGE_RESTRM HEATING COIL 10624.76


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.334314


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.03 -17.6
February 15.73 -15.4
March 16.18 -10.3
April 18.19 0.73
May 20.74 10.60
June 22.40 15.96
July 22.77 16.86
August 22.07 14.24
September 20.33 6.72
October 17.40 -3.1
November 16.33 -17.6
December 15.04 -19.3
     
Annual Sum or Average 18.53 -1.4
Minimum of Months 15.03 -19.3
Maximum of Months 22.77 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 -17.6
February 21.32 -15.4
March 21.53 -10.3
April 22.64 0.73
May 23.80 10.60
June 24.60 15.96
July 24.86 16.86
August 24.40 14.24
September 23.42 6.72
October 22.19 -3.1
November 21.18 -17.6
December 21.17 -19.3
     
Annual Sum or Average 22.70 -1.4
Minimum of Months 21.17 -19.3
Maximum of Months 24.86 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.01 -17.6
February 15.44 -15.4
March 15.69 -10.3
April 17.42 0.73
May 20.09 10.60
June 21.86 15.96
July 22.20 16.86
August 21.40 14.24
September 19.62 6.72
October 16.95 -3.1
November 16.20 -17.6
December 15.11 -19.3
     
Annual Sum or Average 18.10 -1.4
Minimum of Months 15.01 -19.3
Maximum of Months 22.20 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -17.6
February 21.11 -15.4
March 21.11 -10.3
April 21.20 0.73
May 22.28 10.60
June 23.20 15.96
July 23.21 16.86
August 22.85 14.24
September 21.53 6.72
October 21.16 -3.1
November 21.11 -17.6
December 21.11 -19.3
     
Annual Sum or Average 21.75 -1.4
Minimum of Months 21.11 -19.3
Maximum of Months 23.21 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -17.6
February 20.67 -15.4
March 20.97 -10.3
April 21.73 0.73
May 22.72 10.60
June 23.39 15.96
July 23.46 16.86
August 23.19 14.24
September 22.41 6.72
October 21.55 -3.1
November 20.61 -17.6
December 20.48 -19.3
     
Annual Sum or Average 21.81 -1.4
Minimum of Months 20.48 -19.3
Maximum of Months 23.46 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -17.6
February 21.13 -15.4
March 21.16 -10.3
April 21.53 0.73
May 22.80 10.60
June 23.58 15.96
July 23.61 16.86
August 23.27 14.24
September 22.10 6.72
October 21.33 -3.1
November 21.12 -17.6
December 21.12 -19.3
     
Annual Sum or Average 21.99 -1.4
Minimum of Months 21.12 -19.3
Maximum of Months 23.61 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.74 -17.6
February 22.87 -15.4
March 23.12 -10.3
April 23.91 0.73
May 25.12 10.60
June 25.85 15.96
July 25.95 16.86
August 25.64 14.24
September 24.75 6.72
October 23.74 -3.1
November 22.97 -17.6
December 22.72 -19.3
     
Annual Sum or Average 24.12 -1.4
Minimum of Months 22.72 -19.3
Maximum of Months 25.95 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.92 -10.3
April 19.54 0.73
May 21.39 10.60
June 22.64 15.96
July 22.73 16.86
August 22.22 14.24
September 20.54 6.72
October 19.23 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.24 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.73 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.90 -10.3
April 19.36 0.73
May 21.07 10.60
June 22.39 15.96
July 22.50 16.86
August 21.93 14.24
September 20.21 6.72
October 19.12 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.09 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.50 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.47 -15.4
March 20.49 -10.3
April 20.75 0.73
May 21.37 10.60
June 21.65 15.96
July 21.69 16.86
August 21.54 14.24
September 21.07 6.72
October 20.62 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 20.92 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.69 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.51 -15.4
March 20.60 -10.3
April 21.09 0.73
May 21.58 10.60
June 21.70 15.96
July 21.71 16.86
August 21.65 14.24
September 21.35 6.72
October 20.81 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.04 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.71 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 -17.6
February 20.70 -15.4
March 20.96 -10.3
April 21.41 0.73
May 21.70 10.60
June 21.74 15.96
July 21.75 16.86
August 21.73 14.24
September 21.60 6.72
October 21.16 -3.1
November 20.54 -17.6
December 20.51 -19.3
     
Annual Sum or Average 21.20 -1.4
Minimum of Months 20.51 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -17.6
February 21.01 -15.4
March 21.39 -10.3
April 21.92 0.73
May 22.30 10.60
June 22.61 15.96
July 22.58 16.86
August 22.56 14.24
September 22.29 6.72
October 21.79 -3.1
November 20.63 -17.6
December 20.73 -19.3
     
Annual Sum or Average 21.72 -1.4
Minimum of Months 20.63 -19.3
Maximum of Months 22.61 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 49.17 -17.6
February 49.69 -15.4
March 50.29 -10.3
April 51.26 0.73
May 52.02 10.60
June 52.56 15.96
July 52.71 16.86
August 52.53 14.24
September 51.85 6.72
October 50.74 -3.1
November 49.55 -17.6
December 49.03 -19.3
     
Annual Sum or Average 50.96 -1.4
Minimum of Months 49.03 -19.3
Maximum of Months 52.71 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 66.92 -17.6
February 67.26 -15.4
March 67.52 -10.3
April 68.27 0.73
May 69.26 10.60
June 69.99 15.96
July 70.24 16.86
August 69.97 14.24
September 69.28 6.72
October 68.03 -3.1
November 67.38 -17.6
December 66.93 -19.3
     
Annual Sum or Average 68.43 -1.4
Minimum of Months 66.92 -19.3
Maximum of Months 70.24 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.26 -17.6
February 21.57 -15.4
March 21.98 -10.3
April 22.69 0.73
May 23.29 10.60
June 23.71 15.96
July 23.74 16.86
August 23.64 14.24
September 23.14 6.72
October 22.39 -3.1
November 21.29 -17.6
December 21.23 -19.3
     
Annual Sum or Average 22.50 -1.4
Minimum of Months 21.23 -19.3
Maximum of Months 23.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -17.6
February 21.22 -15.4
March 21.41 -10.3
April 22.20 0.73
May 23.15 10.60
June 23.74 15.96
July 23.78 16.86
August 23.64 14.24
September 22.80 6.72
October 21.72 -3.1
November 21.11 -17.6
December 21.12 -19.3
     
Annual Sum or Average 22.26 -1.4
Minimum of Months 21.11 -19.3
Maximum of Months 23.78 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.12 -17.6
February 14.94 -15.4
March 15.53 -10.3
April 17.61 0.73
May 20.72 10.60
June 22.63 15.96
July 23.15 16.86
August 22.35 14.24
September 20.27 6.72
October 16.93 -3.1
November 15.60 -17.6
December 14.08 -19.3
     
Annual Sum or Average 18.18 -1.4
Minimum of Months 14.08 -19.3
Maximum of Months 23.15 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.78 -17.6
February 18.33 -15.4
March 18.84 -10.3
April 20.30 0.73
May 22.17 10.60
June 23.29 15.96
July 23.56 16.86
August 23.15 14.24
September 21.83 6.72
October 19.74 -3.1
November 18.56 -17.6
December 17.72 -19.3
     
Annual Sum or Average 20.45 -1.4
Minimum of Months 17.72 -19.3
Maximum of Months 23.56 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.22 -17.6
February 15.90 -15.4
March 16.14 -10.3
April 18.20 0.73
May 21.18 10.60
June 23.06 15.96
July 23.48 16.86
August 22.70 14.24
September 20.79 6.72
October 17.38 -3.1
November 16.85 -17.6
December 15.29 -19.3
     
Annual Sum or Average 18.86 -1.4
Minimum of Months 15.22 -19.3
Maximum of Months 23.48 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -17.6
February 21.12 -15.4
March 21.20 -10.3
April 22.12 0.73
May 23.55 10.60
June 23.88 15.96
July 23.88 16.86
August 23.80 14.24
September 22.98 6.72
October 21.56 -3.1
November 21.11 -17.6
December 21.11 -19.3
     
Annual Sum or Average 22.29 -1.4
Minimum of Months 21.11 -19.3
Maximum of Months 23.88 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.27 -17.6
February 14.73 -15.4
March 14.83 -10.3
April 16.72 0.73
May 20.04 10.60
June 22.21 15.96
July 22.61 16.86
August 21.65 14.24
September 19.39 6.72
October 16.14 -3.1
November 15.76 -17.6
December 14.42 -19.3
     
Annual Sum or Average 17.75 -1.4
Minimum of Months 14.27 -19.3
Maximum of Months 22.61 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.27 0.73
May 21.36 10.60
June 22.95 15.96
July 22.98 16.86
August 22.34 14.24
September 19.95 6.72
October 18.99 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.20 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.98 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.48 -15.4
March 20.53 -10.3
April 20.90 0.73
May 21.60 10.60
June 21.74 15.96
July 21.74 16.86
August 21.68 14.24
September 21.20 6.72
October 20.68 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.00 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.49 -15.4
March 20.54 -10.3
April 20.94 0.73
May 21.62 10.60
June 21.74 15.96
July 21.75 16.86
August 21.68 14.24
September 21.25 6.72
October 20.71 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.01 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.49 -15.4
March 20.54 -10.3
April 20.96 0.73
May 21.63 10.60
June 21.74 15.96
July 21.74 16.86
August 21.68 14.24
September 21.29 6.72
October 20.73 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.02 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.47 -15.4
March 20.50 -10.3
April 20.77 0.73
May 21.46 10.60
June 21.72 15.96
July 21.73 16.86
August 21.62 14.24
September 21.09 6.72
October 20.61 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 20.95 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.73 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.54 -15.4
March 20.66 -10.3
April 21.21 0.73
May 21.67 10.60
June 21.74 15.96
July 21.75 16.86
August 21.72 14.24
September 21.48 6.72
October 20.87 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.09 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.28 -17.6
February 20.97 -15.4
March 21.86 -10.3
April 22.85 0.73
May 23.32 10.60
June 23.33 15.96
July 23.33 16.86
August 23.33 14.24
September 23.24 6.72
October 22.47 -3.1
November 20.46 -17.6
December 19.92 -19.3
     
Annual Sum or Average 22.12 -1.4
Minimum of Months 19.92 -19.3
Maximum of Months 23.33 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 29.69 -17.6
February 29.99 -15.4
March 30.23 -10.3
April 31.09 0.73
May 32.34 10.60
June 33.03 15.96
July 33.19 16.86
August 32.92 14.24
September 32.02 6.72
October 30.62 -3.1
November 30.08 -17.6
December 29.69 -19.3
     
Annual Sum or Average 31.25 -1.4
Minimum of Months 29.69 -19.3
Maximum of Months 33.19 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.63 -17.6
February 21.68 -15.4
March 21.74 -10.3
April 21.95 0.73
May 22.24 10.60
June 22.51 15.96
July 22.63 16.86
August 22.50 14.24
September 22.10 6.72
October 21.79 -3.1
November 21.66 -17.6
December 21.62 -19.3
     
Annual Sum or Average 22.01 -1.4
Minimum of Months 21.62 -19.3
Maximum of Months 22.63 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -17.6
February 20.58 -15.4
March 20.79 -10.3
April 21.33 0.73
May 21.70 10.60
June 21.75 15.96
July 21.75 16.86
August 21.73 14.24
September 21.53 6.72
October 20.96 -3.1
November 20.47 -17.6
December 20.48 -19.3
     
Annual Sum or Average 21.13 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.53 -15.4
March 20.65 -10.3
April 21.20 0.73
May 21.67 10.60
June 21.74 15.96
July 21.75 16.86
August 21.72 14.24
September 21.46 6.72
October 20.84 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.08 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.94 -17.6
February 17.54 -15.4
March 18.02 -10.3
April 19.72 0.73
May 22.17 10.60
June 23.58 15.96
July 23.91 16.86
August 23.34 14.24
September 21.65 6.72
October 18.98 -3.1
November 17.88 -17.6
December 16.86 -19.3
     
Annual Sum or Average 20.06 -1.4
Minimum of Months 16.86 -19.3
Maximum of Months 23.91 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.48 -17.6
February 14.30 -15.4
March 14.73 -10.3
April 17.08 0.73
May 21.01 10.60
June 23.35 15.96
July 23.97 16.86
August 22.96 14.24
September 20.44 6.72
October 16.28 -3.1
November 15.33 -17.6
December 13.44 -19.3
     
Annual Sum or Average 18.05 -1.4
Minimum of Months 13.44 -19.3
Maximum of Months 23.97 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.37 -17.6
February 15.05 -15.4
March 15.30 -10.3
April 17.52 0.73
May 20.88 10.60
June 23.07 15.96
July 23.53 16.86
August 22.59 14.24
September 20.27 6.72
October 16.56 -3.1
November 16.04 -17.6
December 14.44 -19.3
     
Annual Sum or Average 18.32 -1.4
Minimum of Months 14.37 -19.3
Maximum of Months 23.53 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -17.6
February 21.11 -15.4
March 21.11 -10.3
April 21.40 0.73
May 22.77 10.60
June 23.71 15.96
July 23.74 16.86
August 23.38 14.24
September 21.82 6.72
October 21.14 -3.1
November 21.11 -17.6
December 21.11 -19.3
     
Annual Sum or Average 21.97 -1.4
Minimum of Months 21.11 -19.3
Maximum of Months 23.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.91 -17.6
February 13.41 -15.4
March 13.57 -10.3
April 15.65 0.73
May 19.49 10.60
June 22.22 15.96
July 22.67 16.86
August 21.43 14.24
September 18.47 6.72
October 14.91 -3.1
November 14.47 -17.6
December 13.04 -19.3
     
Annual Sum or Average 16.87 -1.4
Minimum of Months 12.91 -19.3
Maximum of Months 22.67 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.04 0.73
May 20.82 10.60
June 22.76 15.96
July 22.80 16.86
August 21.98 14.24
September 19.40 6.72
October 18.89 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.02 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.80 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.08 0.73
May 20.91 10.60
June 22.81 15.96
July 22.85 16.86
August 22.03 14.24
September 19.47 6.72
October 18.91 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.05 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.85 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.14 0.73
May 21.05 10.60
June 22.83 15.96
July 22.86 16.86
August 22.06 14.24
September 19.58 6.72
October 18.92 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.08 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.86 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.47 -15.4
March 20.52 -10.3
April 20.90 0.73
May 21.59 10.60
June 21.74 15.96
July 21.74 16.86
August 21.65 14.24
September 21.19 6.72
October 20.66 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 20.99 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.09 0.73
May 20.83 10.60
June 22.68 15.96
July 22.78 16.86
August 21.98 14.24
September 19.62 6.72
October 18.91 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.04 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.78 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.48 -15.4
March 20.56 -10.3
April 21.06 0.73
May 21.61 10.60
June 21.73 15.96
July 21.74 16.86
August 21.69 14.24
September 21.33 6.72
October 20.73 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.03 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -17.6
February 20.58 -15.4
March 20.80 -10.3
April 21.37 0.73
May 21.72 10.60
June 21.75 15.96
July 21.75 16.86
August 21.74 14.24
September 21.56 6.72
October 20.98 -3.1
November 20.47 -17.6
December 20.48 -19.3
     
Annual Sum or Average 21.14 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 -17.6
February 21.45 -15.4
March 21.79 -10.3
April 23.01 0.73
May 24.72 10.60
June 25.70 15.96
July 25.83 16.86
August 25.42 14.24
September 24.03 6.72
October 22.26 -3.1
November 21.51 -17.6
December 21.07 -19.3
     
Annual Sum or Average 23.17 -1.4
Minimum of Months 21.07 -19.3
Maximum of Months 25.83 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -17.6
February 19.07 -15.4
March 19.52 -10.3
April 21.39 0.73
May 22.94 10.60
June 23.31 15.96
July 23.32 16.86
August 23.22 14.24
September 22.28 6.72
October 20.21 -3.1
November 18.89 -17.6
December 18.91 -19.3
     
Annual Sum or Average 21.01 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 23.32 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.53 -15.4
March 20.67 -10.3
April 21.24 0.73
May 21.68 10.60
June 21.74 15.96
July 21.74 16.86
August 21.71 14.24
September 21.43 6.72
October 20.84 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.09 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.93 -10.3
April 19.94 0.73
May 21.86 10.60
June 22.91 15.96
July 22.98 16.86
August 22.60 14.24
September 20.76 6.72
October 19.18 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.40 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.98 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.65 -17.6
February 16.27 -15.4
March 16.79 -10.3
April 18.79 0.73
May 21.81 10.60
June 23.62 15.96
July 24.00 16.86
August 23.22 14.24
September 20.93 6.72
October 17.82 -3.1
November 16.60 -17.6
December 15.50 -19.3
     
Annual Sum or Average 19.27 -1.4
Minimum of Months 15.50 -19.3
Maximum of Months 24.00 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.27 -17.6
February 13.13 -15.4
March 13.56 -10.3
April 16.22 0.73
May 20.70 10.60
June 23.41 15.96
July 24.08 16.86
August 22.88 14.24
September 19.86 6.72
October 15.23 -3.1
November 14.12 -17.6
December 12.11 -19.3
     
Annual Sum or Average 17.32 -1.4
Minimum of Months 12.11 -19.3
Maximum of Months 24.08 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.14 -17.6
February 12.94 -15.4
March 13.55 -10.3
April 16.38 0.73
May 20.35 10.60
June 23.03 15.96
July 23.50 16.86
August 22.25 14.24
September 19.13 6.72
October 14.89 -3.1
November 13.64 -17.6
December 12.09 -19.3
     
Annual Sum or Average 17.01 -1.4
Minimum of Months 12.09 -19.3
Maximum of Months 23.50 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -17.6
February 21.11 -15.4
March 21.11 -10.3
April 21.39 0.73
May 22.37 10.60
June 23.31 15.96
July 23.35 16.86
August 22.88 14.24
September 21.49 6.72
October 21.12 -3.1
November 21.11 -17.6
December 21.11 -19.3
     
Annual Sum or Average 21.79 -1.4
Minimum of Months 21.11 -19.3
Maximum of Months 23.35 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.98 -17.6
February 11.65 -15.4
March 12.20 -10.3
April 14.83 0.73
May 19.09 10.60
June 22.19 15.96
July 22.62 16.86
August 21.11 14.24
September 17.59 6.72
October 13.65 -3.1
November 12.44 -17.6
December 11.05 -19.3
     
Annual Sum or Average 15.81 -1.4
Minimum of Months 10.98 -19.3
Maximum of Months 22.62 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.46 -17.6
February 20.47 -15.4
March 20.47 -10.3
April 20.72 0.73
May 21.49 10.60
June 21.72 15.96
July 21.72 16.86
August 21.57 14.24
September 20.87 6.72
October 20.51 -3.1
November 20.46 -17.6
December 20.46 -19.3
     
Annual Sum or Average 20.91 -1.4
Minimum of Months 20.46 -19.3
Maximum of Months 21.72 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.11 0.73
May 20.61 10.60
June 22.49 15.96
July 22.50 16.86
August 21.59 14.24
September 19.24 6.72
October 18.89 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 19.92 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.50 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.14 0.73
May 20.69 10.60
June 22.52 15.96
July 22.51 16.86
August 21.61 14.24
September 19.29 6.72
October 18.89 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 19.93 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.52 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.47 -15.4
March 20.49 -10.3
April 20.90 0.73
May 21.63 10.60
June 21.74 15.96
July 21.74 16.86
August 21.65 14.24
September 21.11 6.72
October 20.59 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 20.98 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.89 -10.3
April 19.11 0.73
May 20.60 10.60
June 22.44 15.96
July 22.52 16.86
August 21.64 14.24
September 19.33 6.72
October 18.89 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 19.92 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.52 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -17.6
February 18.89 -15.4
March 18.93 -10.3
April 19.74 0.73
May 21.25 10.60
June 22.54 15.96
July 22.62 16.86
August 22.08 14.24
September 20.06 6.72
October 18.99 -3.1
November 18.89 -17.6
December 18.89 -19.3
     
Annual Sum or Average 20.16 -1.4
Minimum of Months 18.89 -19.3
Maximum of Months 22.62 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.48 -15.4
March 20.64 -10.3
April 21.24 0.73
May 21.69 10.60
June 21.74 15.96
July 21.75 16.86
August 21.71 14.24
September 21.40 6.72
October 20.76 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.07 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.03 -17.6
February 18.48 -15.4
March 19.14 -10.3
April 20.75 0.73
May 22.71 10.60
June 23.94 15.96
July 24.07 16.86
August 23.44 14.24
September 21.63 6.72
October 19.63 -3.1
November 18.37 -17.6
December 17.95 -19.3
     
Annual Sum or Average 20.69 -1.4
Minimum of Months 17.95 -19.3
Maximum of Months 24.07 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.48 -15.4
March 20.62 -10.3
April 21.20 0.73
May 21.68 10.60
June 21.74 15.96
July 21.75 16.86
August 21.71 14.24
September 21.39 6.72
October 20.75 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.06 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.75 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.48 -15.4
March 20.63 -10.3
April 21.22 0.73
May 21.68 10.60
June 21.74 15.96
July 21.74 16.86
August 21.71 14.24
September 21.37 6.72
October 20.74 -3.1
November 20.47 -17.6
December 20.47 -19.3
     
Annual Sum or Average 21.06 -1.4
Minimum of Months 20.47 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -17.6
February 20.47 -15.4
March 20.53 -10.3
April 21.04 0.73
May 21.63 10.60
June 21.73 15.96
July 21.74 16.86
August 21.68 14.24
September 21.24 6.72
October 20.63 -3.1
November 20.47 -17.6
December 20.46 -19.3
     
Annual Sum or Average 21.01 -1.4
Minimum of Months 20.46 -19.3
Maximum of Months 21.74 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.11 -17.6
February 14.87 -15.4
March 15.74 -10.3
April 18.26 0.73
May 21.55 10.60
June 23.52 15.96
July 23.87 16.86
August 22.89 14.24
September 20.29 6.72
October 16.83 -3.1
November 14.91 -17.6
December 13.85 -19.3
     
Annual Sum or Average 18.41 -1.4
Minimum of Months 13.85 -19.3
Maximum of Months 23.87 16.86



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:40

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.43 -17.6
February 11.43 -15.4
March 12.13 -10.3
April 15.44 0.73
May 20.34 10.60
June 23.34 15.96
July 23.98 16.86
August 22.53 14.24
September 19.02 6.72
October 13.91 -3.1
November 11.90 -17.6
December 9.95 -19.3
     
Annual Sum or Average 16.23 -1.4
Minimum of Months 9.95 -19.3
Maximum of Months 23.98 16.86



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:40

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.271889E+12 211851.437 12-JAN-07:15 15177.258 39465.561 8722.653 144289.851 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.224791E+12 203187.808 27-FEB-07:15 15177.258 39465.561 8719.567 135615.905 13.404 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.209716E+12 184572.485 01-MAR-07:15 15177.258 39465.561 8708.333 116979.939 45.281 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.148366E+12 154402.078 03-APR-06:15 15177.258 39465.561 8695.662 90945.943 109.540 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.128970E+12 79542.964 13-MAY-07:00 17641.054 43276.576 9054.925 0.000 9562.297 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.132507E+12 85850.452 30-JUN-07:00 17492.219 43276.576 9054.925 0.000 16018.619 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.140950E+12 87378.237 22-JUL-07:00 17641.054 43276.576 9054.925 0.000 17397.570 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.136466E+12 86951.570 31-AUG-06:15 15102.841 39465.561 8680.457 22481.778 1212.820 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.129699E+12 101094.022 30-SEP-06:15 13316.689 34010.661 8680.457 40669.098 221.004 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.177401E+12 155635.581 22-OCT-06:15 15177.258 39465.561 8690.829 87995.839 109.980 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.253887E+12 184302.805 29-NOV-07:00 15177.258 39465.561 8706.400 116719.675 37.798 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.282822E+12 194216.727 15-DEC-07:15 13316.689 34010.661 8710.945 133982.320 0.000 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.223746E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.128970E+12 79542.964   13316.689 34010.661 8680.457 0.000 0.000 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.282822E+12 211851.437   17641.054 43276.576 9054.925 144289.851 17397.570 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:40

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.164757E+12 142837.334 12-JAN-09:15 37992.745 40096.028 0.000 64748.561 64748.561 64748.561 37992.745
February 0.143242E+12 140128.462 24-FEB-09:15 28138.813 40096.028 0.000 71893.622 71893.622 71893.622 28138.813
March 0.146685E+12 131909.074 31-MAR-08:15 20362.946 40096.028 0.000 71450.100 71450.100 71450.100 20362.946
April 0.119795E+12 123136.120 03-APR-08:15 17899.502 40096.028 0.000 65140.590 65140.590 65140.590 17899.502
May 0.108283E+12 111715.866 12-MAY-08:15 0.000 40096.028 0.000 71619.838 71619.838 71619.838 0.000
June 0.995325E+11 105277.022 02-JUN-08:15 0.000 40096.028 0.000 65180.994 65180.994 65180.994 0.000
July 0.100308E+12 104109.952 07-JUL-08:15 0.000 40096.028 0.000 64013.924 64013.924 64013.924 0.000
August 0.995061E+11 103033.633 31-AUG-09:00 3120.495 40096.028 0.000 59817.111 59817.111 59817.111 3120.495
September 0.101800E+12 110307.935 29-SEP-10:15 9950.225 40096.028 0.000 60261.682 60261.682 60261.682 9950.225
October 0.125332E+12 123532.868 27-OCT-10:30 22380.861 40096.028 0.000 61055.979 61055.979 61055.979 22380.861
November 0.153595E+12 134980.947 28-NOV-10:45 32377.250 40096.028 0.000 62507.669 62507.669 62507.669 32377.250
December 0.167320E+12 145042.802 15-DEC-09:15 34747.943 40096.028 0.000 70198.831 70198.831 70198.831 34747.943
                     
Annual Sum or Average 0.153016E+13         0.000        
Minimum of Months 0.995061E+11 103033.633   0.000 40096.028 0.000 59817.111 59817.111 59817.111 0.000
Maximum of Months 0.167320E+12 145042.802   37992.745 40096.028 0.000 71893.622 71893.622 71893.622 37992.745