Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2018-10-19 10:15:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2707.56 | 674.60 | 726.84 |
Net Site Energy | 2707.56 | 674.60 | 726.84 |
Total Source Energy | 6308.47 | 1571.78 | 1693.51 |
Net Source Energy | 6308.47 | 1571.78 | 1693.51 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 85.17 | 43.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 278.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 623.16 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1619.52 | 1088.04 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 85.17 | 43.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 184.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 278.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 623.16 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 147.10 | 178.94 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 434.76 | 292.08 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 136.53 | 166.07 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 403.51 | 271.09 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1619.52 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1619.52 | 100.00 |
Total On-Site and Utility Electric Sources | 1619.52 | 100.00 |
Total Electricity End Uses | 1619.52 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 141.25 |
Time Setpoint Not Met During Occupied Cooling | 3055.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4527.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6018.33 | 4659.52 | 1358.81 | 0.77 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14443.19 | 10581.14 | 3862.05 | 0.73 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7492.22 | 5287.35 | 2204.87 | 0.71 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12610.71 | 9746.82 | 2863.89 | 0.77 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5754.9 | 3.20 | 10.90 | 11.55 | 10.75 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13887.4 | 3.27 | 11.16 | 11.83 | 11.13 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7229.5 | 3.32 | 11.33 | 12.01 | 11.40 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12060.8 | 3.20 | 10.91 | 11.55 | 10.76 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.81 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 18705.19 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 883.94 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 883.94 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 883.94 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.74 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.81 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2506.91 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 883.94 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2802.22 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 913.18 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.74 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.81 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2506.91 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 883.94 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2802.22 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 989.13 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 942.37 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 883.88 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.74 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.81 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2910.37 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1080.00 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2802.22 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3535.77 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 1240.83 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 1193.14 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 930.02 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3535.52 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1131.15 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 316.74 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3639.68 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 15255.65 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 8169.28 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 6161.11 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.34 | 380.17 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 792.46 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.34 | 378.81 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.71 | 784.36 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7131.84 | 8558.21 | 0.596 | 0.716 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 29.24 | 0.00879 |
RESTROOMFLR1 | 386.71 | 464.05 | 0.032 | 0.039 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:15:00 | 28.57 | 0.00879 |
MEETINGROOMFLR1 | 3367.42 | 4040.90 | 0.282 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
GUESTROOM101 | 483.10 | 579.73 | 0.056 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
GUESTROOM102 | 385.63 | 462.76 | 0.045 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
GUESTROOM103 | 930.08 | 1116.10 | 0.108 | 0.130 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 27.68 | 0.00879 |
GUESTROOM104 | 1230.96 | 1477.15 | 0.143 | 0.172 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM105 | 1619.03 | 1942.84 | 0.188 | 0.226 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
EMPLOYEELOUNGEFLR1 | 5483.80 | 6580.56 | 0.459 | 0.550 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
EXERCISECENTERFLR1 | 1188.37 | 1426.04 | 0.099 | 0.119 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94 | 0.00879 |
FRONTOFFICEFLR1 | 3384.56 | 4061.47 | 0.283 | 0.339 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
GUESTROOM201 | 674.51 | 809.41 | 0.078 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 29.01 | 0.00879 |
GUESTROOM202_205 | 3836.50 | 4603.81 | 0.446 | 0.535 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
GUESTROOM206_208 | 3102.81 | 3723.37 | 0.361 | 0.433 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
GUESTROOM209_212 | 3654.16 | 4384.99 | 0.425 | 0.510 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 28.93 | 0.00879 |
GUESTROOM213 | 1005.52 | 1206.62 | 0.117 | 0.140 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 27.68 | 0.00879 |
GUESTROOM214 | 1371.14 | 1645.37 | 0.159 | 0.191 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM215_218 | 9941.15 | 11929.38 | 1.155 | 1.386 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM219 | 5539.32 | 6647.18 | 0.644 | 0.772 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM220_223 | 4877.64 | 5853.17 | 0.567 | 0.680 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
GUESTROOM224 | 1377.55 | 1653.06 | 0.160 | 0.192 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM301 | 489.65 | 587.58 | 0.057 | 0.068 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
GUESTROOM302_305 | 1274.57 | 1529.48 | 0.148 | 0.178 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.78 | 0.00879 |
GUESTROOM306_308 | 1117.61 | 1341.13 | 0.130 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.78 | 0.00879 |
GUESTROOM309_312 | 3603.37 | 4324.05 | 0.419 | 0.502 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.78 | 0.00879 |
GUESTROOM313 | 503.25 | 603.90 | 0.058 | 0.070 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 26.12 | 0.00879 |
GUESTROOM314 | 1283.41 | 1540.09 | 0.149 | 0.179 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 29.40 | 0.00879 |
GUESTROOM315_318 | 5291.81 | 6350.18 | 0.615 | 0.738 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM319 | 1190.09 | 1428.11 | 0.138 | 0.166 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM320_323 | 4661.01 | 5593.21 | 0.542 | 0.650 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM324 | 794.63 | 953.56 | 0.092 | 0.111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM401 | 1293.66 | 1552.39 | 0.150 | 0.180 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 29.27 | 0.00879 |
GUESTROOM402_405 | 1954.56 | 2345.47 | 0.227 | 0.273 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM406_408 | 1673.60 | 2008.32 | 0.194 | 0.233 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM409_412 | 4594.23 | 5513.07 | 0.534 | 0.641 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM413 | 732.27 | 878.72 | 0.085 | 0.102 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 29.24 | 0.00879 |
GUESTROOM414 | 1067.45 | 1280.93 | 0.124 | 0.149 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
GUESTROOM415_418 | 5981.91 | 7178.29 | 0.695 | 0.834 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40 | 0.00879 |
GUESTROOM419 | 1631.39 | 1957.67 | 0.190 | 0.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
GUESTROOM420_423 | 5934.65 | 7121.58 | 0.690 | 0.828 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40 | 0.00879 |
GUESTROOM424 | 1634.84 | 1961.80 | 0.190 | 0.228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 29.40 | 0.00879 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
CORRIDORFLR1 | 13476.98 | 16172.37 | 1.126 | 1.351 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
CORRIDORFLR2 | 2625.42 | 3150.50 | 0.219 | 0.263 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94 | 0.00879 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
CORRIDORFLR3 | 1214.86 | 1457.84 | 0.101 | 0.122 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94 | 0.00879 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 | |
CORRIDORFLR4 | 2012.11 | 2414.53 | 0.168 | 0.202 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 29.24 | 0.00879 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 0.00879 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1217.01 | 1460.41 | 0.035 | 0.236 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | -4.20 | 0.00269 |
RESTROOMFLR1 | 50.13 | 60.16 | 0.001 | 0.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -4.20 | 0.00269 |
MEETINGROOMFLR1 | 408.42 | 490.10 | 0.012 | 0.126 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | -4.20 | 0.00269 |
GUESTROOM101 | 169.02 | 202.83 | 0.005 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -4.20 | 0.00269 |
GUESTROOM102 | 214.62 | 257.55 | 0.006 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -4.20 | 0.00269 |
GUESTROOM103 | 390.70 | 468.84 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -4.20 | 0.00269 |
GUESTROOM104 | 377.86 | 453.44 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | -4.20 | 0.00269 |
GUESTROOM105 | 212.36 | 254.83 | 0.006 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -4.20 | 0.00269 |
EMPLOYEELOUNGEFLR1 | 180.78 | 216.94 | 0.005 | 0.051 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20 | 0.00269 |
EXERCISECENTERFLR1 | 106.78 | 128.14 | 0.003 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | -4.20 | 0.00269 |
FRONTOFFICEFLR1 | 771.39 | 925.67 | 0.022 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | -4.20 | 0.00269 |
GUESTROOM201 | 342.34 | 410.81 | 0.010 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -4.20 | 0.00269 |
GUESTROOM202_205 | 730.50 | 876.60 | 0.021 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | -4.20 | 0.00269 |
GUESTROOM206_208 | 562.34 | 674.80 | 0.016 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | -4.20 | 0.00269 |
GUESTROOM209_212 | 656.77 | 788.12 | 0.019 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -4.20 | 0.00269 |
GUESTROOM213 | 416.99 | 500.39 | 0.012 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | -4.20 | 0.00269 |
GUESTROOM214 | 383.84 | 460.60 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 10:15:00 | -4.20 | 0.00269 |
GUESTROOM215_218 | 625.44 | 750.53 | 0.018 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -4.20 | 0.00269 |
GUESTROOM219 | 135.21 | 162.25 | 0.004 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -4.20 | 0.00269 |
GUESTROOM220_223 | 615.92 | 739.10 | 0.018 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -4.20 | 0.00269 |
GUESTROOM224 | 321.60 | 385.91 | 0.009 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | -4.20 | 0.00269 |
GUESTROOM301 | 375.54 | 450.65 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | -4.20 | 0.00269 |
GUESTROOM302_305 | 833.17 | 999.80 | 0.024 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -4.20 | 0.00269 |
GUESTROOM306_308 | 708.53 | 850.23 | 0.020 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -4.20 | 0.00269 |
GUESTROOM309_312 | 831.06 | 997.27 | 0.024 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | -4.20 | 0.00269 |
GUESTROOM313 | 480.28 | 576.34 | 0.014 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -4.20 | 0.00269 |
GUESTROOM314 | 441.34 | 529.60 | 0.013 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 15:30:00 | -4.20 | 0.00269 |
GUESTROOM315_318 | 806.03 | 967.24 | 0.023 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20 | 0.00269 |
GUESTROOM319 | 220.85 | 265.03 | 0.006 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -4.20 | 0.00269 |
GUESTROOM320_323 | 776.17 | 931.40 | 0.022 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | -4.20 | 0.00269 |
GUESTROOM324 | 386.36 | 463.63 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | -4.20 | 0.00269 |
GUESTROOM401 | 556.01 | 667.21 | 0.016 | 0.019 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 22:15:00 | -4.20 | 0.00269 |
GUESTROOM402_405 | 1470.26 | 1764.31 | 0.042 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 21:45:00 | -4.20 | 0.00269 |
GUESTROOM406_408 | 1240.47 | 1488.57 | 0.035 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -4.20 | 0.00269 |
GUESTROOM409_412 | 1480.52 | 1776.63 | 0.042 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:45:00 | -4.20 | 0.00269 |
GUESTROOM413 | 690.03 | 828.04 | 0.020 | 0.024 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20 | 0.00269 |
GUESTROOM414 | 650.31 | 780.37 | 0.019 | 0.022 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 20:30:00 | -4.20 | 0.00269 |
GUESTROOM415_418 | 1458.21 | 1749.85 | 0.042 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | -4.20 | 0.00269 |
GUESTROOM419 | 431.05 | 517.26 | 0.012 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | -4.20 | 0.00269 |
GUESTROOM420_423 | 1424.61 | 1709.53 | 0.041 | 0.054 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -4.20 | 0.00269 |
GUESTROOM424 | 598.65 | 718.38 | 0.017 | 0.021 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20 | 0.00269 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
CORRIDORFLR1 | 14411.46 | 17293.75 | 0.412 | 0.494 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | -4.20 | 0.00269 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
CORRIDORFLR2 | 408.51 | 490.21 | 0.012 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | -4.20 | 0.00269 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
CORRIDORFLR3 | 619.46 | 743.35 | 0.018 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -4.20 | 0.00269 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
CORRIDORFLR4 | 1449.75 | 1739.69 | 0.041 | 0.050 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | -4.20 | 0.00269 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.34 | 0.34 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.72 | 0.72 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.34 | 0.34 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.71 | 0.71 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 294.75 | 7460.50 | 159.50 |
RESTROOMFLR1 | 1.75 | 8557.75 | 1.75 |
MEETINGROOMFLR1 | 245.75 | 3505.25 | 10.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 467.25 | 8760.00 | 467.25 |
GUESTROOM104 | 34.00 | 8760.00 | 34.00 |
GUESTROOM105 | 0.00 | 8618.50 | 0.00 |
EMPLOYEELOUNGEFLR1 | 2916.00 | 2234.75 | 224.25 |
EXERCISECENTERFLR1 | 652.75 | 2892.50 | 0.00 |
FRONTOFFICEFLR1 | 218.75 | 7056.50 | 3.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 153.75 | 8758.25 | 153.75 |
GUESTROOM206_208 | 112.00 | 8758.25 | 112.00 |
GUESTROOM209_212 | 66.00 | 8760.00 | 66.00 |
GUESTROOM213 | 628.00 | 8760.00 | 628.00 |
GUESTROOM214 | 19.50 | 8692.75 | 19.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3918.75 | 3722.00 | 96.75 |
GUESTROOM220_223 | 1.75 | 8561.25 | 1.75 |
GUESTROOM224 | 36.25 | 8674.75 | 36.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 195.50 | 8760.00 | 195.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 240.50 | 8704.75 | 240.50 |
GUESTROOM315_318 | 1.25 | 8438.50 | 1.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 17.25 | 8623.50 | 17.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 2297.50 | 8381.00 | 2297.50 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 754.50 | 8256.50 | 749.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 483.00 | 7883.75 | 173.50 |
GUESTROOM419 | 272.50 | 8071.75 | 189.25 |
GUESTROOM420_423 | 525.00 | 7924.75 | 241.50 |
GUESTROOM424 | 903.75 | 8230.00 | 843.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6163.50 | 8760.00 | 4527.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 2.00 | 146.50 | 2.00 | 146.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 4.25 | 26.50 | 4.25 | 26.50 |
GUESTROOM104 | 0.00 | 35.50 | 0.00 | 35.50 |
GUESTROOM105 | 0.00 | 58.25 | 0.00 | 58.25 |
EMPLOYEELOUNGEFLR1 | 135.25 | 844.50 | 116.25 | 510.50 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 6.00 | 0.00 | 6.00 |
GUESTROOM206_208 | 0.00 | 18.00 | 0.00 | 18.00 |
GUESTROOM209_212 | 0.00 | 4.25 | 0.00 | 4.25 |
GUESTROOM213 | 6.25 | 5.00 | 6.25 | 5.00 |
GUESTROOM214 | 0.00 | 14.50 | 0.00 | 14.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2493.00 | 0.00 | 2493.00 |
GUESTROOM220_223 | 0.00 | 11.25 | 0.00 | 11.25 |
GUESTROOM224 | 0.00 | 14.75 | 0.00 | 14.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1.00 | 4.00 | 1.00 | 4.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 2.00 | 13.25 | 2.00 | 13.25 |
GUESTROOM315_318 | 0.00 | 15.50 | 0.00 | 15.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 10.50 | 0.00 | 10.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 24.00 | 18.00 | 24.00 | 18.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 9.75 | 14.75 | 9.75 | 14.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2.25 | 23.75 | 2.25 | 23.75 |
GUESTROOM419 | 2.00 | 29.25 | 2.00 | 29.25 |
GUESTROOM420_423 | 3.75 | 22.00 | 3.75 | 22.00 |
GUESTROOM424 | 8.00 | 25.50 | 8.00 | 25.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 2450.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 23.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 160.75 | 4082.50 | 141.25 | 3055.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:36
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.339405 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.715761 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.708446 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.81 |
CORRIDORFLR1 PTAC HEATING COIL | 18705.19 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 883.94 |
102 PTAC HEATING COIL | 883.94 |
103 PTAC HEATING COIL | 883.94 |
104 PTAC HEATING COIL | 883.88 |
105 PTAC HEATING COIL | 883.88 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 316.74 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.81 |
CORRIDORFLR2 PTAC HEATING COIL | 2506.91 |
201 PTAC HEATING COIL | 883.94 |
202_205 PTAC HEATING COIL | 3535.77 |
206_208 PTAC HEATING COIL | 2802.22 |
209_212 PTAC HEATING COIL | 3535.77 |
213 PTAC HEATING COIL | 913.18 |
214 PTAC HEATING COIL | 883.88 |
215_218 PTAC HEATING COIL | 3535.52 |
219 PTAC HEATING COIL | 883.88 |
220_223 PTAC HEATING COIL | 3535.52 |
224 PTAC HEATING COIL | 883.88 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 316.74 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.81 |
CORRIDORFLR3 PTAC HEATING COIL | 2506.91 |
301 PTAC HEATING COIL | 883.94 |
302_305 PTAC HEATING COIL | 3535.77 |
306_308 PTAC HEATING COIL | 2802.22 |
309_312 PTAC HEATING COIL | 3535.77 |
313 PTAC HEATING COIL | 989.13 |
314 PTAC HEATING COIL | 942.37 |
315_318 PTAC HEATING COIL | 3535.52 |
319 PTAC HEATING COIL | 883.88 |
320_323 PTAC HEATING COIL | 3535.52 |
324 PTAC HEATING COIL | 883.88 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 316.74 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 316.81 |
CORRIDORFLR4 PTAC HEATING COIL | 2910.37 |
401 PTAC HEATING COIL | 1080.00 |
402_405 PTAC HEATING COIL | 3535.77 |
406_408 PTAC HEATING COIL | 2802.22 |
409_412 PTAC HEATING COIL | 3535.77 |
413 PTAC HEATING COIL | 1240.83 |
414 PTAC HEATING COIL | 1193.14 |
415_418 PTAC HEATING COIL | 3535.52 |
419 PTAC HEATING COIL | 930.02 |
420_423 PTAC HEATING COIL | 3535.52 |
424 PTAC HEATING COIL | 1131.15 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 316.74 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.774222 | 0.339405 | 6018.33 |
SAC_FRONTLOUNGE COOLING COIL | 0.732604 | 0.715761 | 14443.19 |
SAC_MEETINGROOM COOLING COIL | 0.705712 | 0.338187 | 7492.22 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.772900 | 0.708446 | 12610.71 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.715761 |
RESTROOMFLR1 DIRECT AIR | 0.038774 |
MEETINGROOMFLR1 DIRECT AIR | 0.338187 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.550458 |
EXERCISECENTERFLR1 DIRECT AIR | 0.119214 |
FRONTOFFICEFLR1 DIRECT AIR | 0.339405 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.339405 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.715761 |
SAC_MEETINGROOM MAIN BRANCH | 0.338187 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.708446 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.339405 |
SAC_FRONTLOUNGE | 0.715761 |
SAC_MEETINGROOM | 0.338187 |
SAC_EXC_EMPLGE_RESTRM | 0.708446 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.339405 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.715761 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.338187 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.708446 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.339405 | 0.339405 | 0.339405 | 0.339405 | 3639.68 | 6018.33 | 1.00 |
SAC_FRONTLOUNGE | 0.715761 | 0.715761 | 0.715761 | 0.715761 | 15255.65 | 14443.19 | 1.00 |
SAC_MEETINGROOM | 0.338187 | 0.338187 | 0.338187 | 0.338187 | 8169.28 | 7492.22 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.708446 | 0.708446 | 0.708446 | 0.708446 | 6161.11 | 12610.71 | 0.168276 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3639.68 |
SAC_FRONTLOUNGE HEATING COIL | 15255.65 |
SAC_MEETINGROOM HEATING COIL | 8169.28 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 6161.11 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.338187 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.34 | 4.50 |
February | 18.85 | 5.82 |
March | 19.72 | 8.33 |
April | 20.47 | 10.85 |
May | 21.34 | 12.97 |
June | 21.99 | 15.59 |
July | 22.78 | 17.66 |
August | 22.99 | 18.80 |
September | 22.40 | 15.09 |
October | 20.61 | 11.43 |
November | 19.46 | 8.07 |
December | 18.80 | 5.42 |
Annual Sum or Average | 20.66 | 11.24 |
Minimum of Months | 18.34 | 4.50 |
Maximum of Months | 22.99 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.00 | 4.50 |
February | 23.15 | 5.82 |
March | 23.44 | 8.33 |
April | 23.78 | 10.85 |
May | 24.14 | 12.97 |
June | 24.51 | 15.59 |
July | 24.94 | 17.66 |
August | 25.14 | 18.80 |
September | 24.51 | 15.09 |
October | 23.79 | 11.43 |
November | 23.43 | 8.07 |
December | 23.16 | 5.42 |
Annual Sum or Average | 23.92 | 11.24 |
Minimum of Months | 23.00 | 4.50 |
Maximum of Months | 25.14 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.85 | 4.50 |
February | 18.25 | 5.82 |
March | 19.10 | 8.33 |
April | 19.88 | 10.85 |
May | 20.82 | 12.97 |
June | 21.51 | 15.59 |
July | 22.25 | 17.66 |
August | 22.41 | 18.80 |
September | 21.72 | 15.09 |
October | 19.98 | 11.43 |
November | 18.93 | 8.07 |
December | 18.26 | 5.42 |
Annual Sum or Average | 20.09 | 11.24 |
Minimum of Months | 17.85 | 4.50 |
Maximum of Months | 22.41 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 4.50 |
February | 21.38 | 5.82 |
March | 21.54 | 8.33 |
April | 22.05 | 10.85 |
May | 22.54 | 12.97 |
June | 23.04 | 15.59 |
July | 23.34 | 17.66 |
August | 23.47 | 18.80 |
September | 22.93 | 15.09 |
October | 22.09 | 11.43 |
November | 21.56 | 8.07 |
December | 21.27 | 5.42 |
Annual Sum or Average | 22.21 | 11.24 |
Minimum of Months | 21.24 | 4.50 |
Maximum of Months | 23.47 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 4.50 |
February | 22.12 | 5.82 |
March | 22.37 | 8.33 |
April | 22.66 | 10.85 |
May | 22.98 | 12.97 |
June | 23.28 | 15.59 |
July | 23.46 | 17.66 |
August | 23.50 | 18.80 |
September | 23.21 | 15.09 |
October | 22.73 | 11.43 |
November | 22.39 | 8.07 |
December | 22.10 | 5.42 |
Annual Sum or Average | 22.74 | 11.24 |
Minimum of Months | 22.02 | 4.50 |
Maximum of Months | 23.50 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.46 | 4.50 |
February | 21.70 | 5.82 |
March | 22.06 | 8.33 |
April | 22.61 | 10.85 |
May | 23.11 | 12.97 |
June | 23.48 | 15.59 |
July | 23.65 | 17.66 |
August | 23.67 | 18.80 |
September | 23.41 | 15.09 |
October | 22.67 | 11.43 |
November | 21.96 | 8.07 |
December | 21.53 | 5.42 |
Annual Sum or Average | 22.62 | 11.24 |
Minimum of Months | 21.46 | 4.50 |
Maximum of Months | 23.67 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.17 | 4.50 |
February | 24.37 | 5.82 |
March | 24.76 | 8.33 |
April | 25.18 | 10.85 |
May | 25.59 | 12.97 |
June | 25.93 | 15.59 |
July | 26.16 | 17.66 |
August | 26.22 | 18.80 |
September | 25.88 | 15.09 |
October | 25.27 | 11.43 |
November | 24.72 | 8.07 |
December | 24.31 | 5.42 |
Annual Sum or Average | 25.22 | 11.24 |
Minimum of Months | 24.17 | 4.50 |
Maximum of Months | 26.22 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | 4.50 |
February | 20.02 | 5.82 |
March | 20.65 | 8.33 |
April | 21.32 | 10.85 |
May | 21.94 | 12.97 |
June | 22.51 | 15.59 |
July | 22.84 | 17.66 |
August | 22.93 | 18.80 |
September | 22.39 | 15.09 |
October | 21.41 | 11.43 |
November | 20.55 | 8.07 |
December | 19.87 | 5.42 |
Annual Sum or Average | 21.35 | 11.24 |
Minimum of Months | 19.68 | 4.50 |
Maximum of Months | 22.93 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.71 | 5.82 |
March | 20.31 | 8.33 |
April | 20.99 | 10.85 |
May | 21.62 | 12.97 |
June | 22.22 | 15.59 |
July | 22.60 | 17.66 |
August | 22.71 | 18.80 |
September | 22.07 | 15.09 |
October | 21.06 | 11.43 |
November | 20.19 | 8.07 |
December | 19.54 | 5.42 |
Annual Sum or Average | 21.04 | 11.24 |
Minimum of Months | 19.39 | 4.50 |
Maximum of Months | 22.71 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 4.50 |
February | 20.92 | 5.82 |
March | 21.10 | 8.33 |
April | 21.31 | 10.85 |
May | 21.50 | 12.97 |
June | 21.64 | 15.59 |
July | 21.70 | 17.66 |
August | 21.71 | 18.80 |
September | 21.60 | 15.09 |
October | 21.33 | 11.43 |
November | 21.06 | 8.07 |
December | 20.88 | 5.42 |
Annual Sum or Average | 21.30 | 11.24 |
Minimum of Months | 20.80 | 4.50 |
Maximum of Months | 21.71 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 4.50 |
February | 21.22 | 5.82 |
March | 21.36 | 8.33 |
April | 21.51 | 10.85 |
May | 21.61 | 12.97 |
June | 21.69 | 15.59 |
July | 21.72 | 17.66 |
August | 21.73 | 18.80 |
September | 21.68 | 15.09 |
October | 21.54 | 11.43 |
November | 21.29 | 8.07 |
December | 21.16 | 5.42 |
Annual Sum or Average | 21.47 | 11.24 |
Minimum of Months | 21.06 | 4.50 |
Maximum of Months | 21.73 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.46 | 4.50 |
February | 21.56 | 5.82 |
March | 21.64 | 8.33 |
April | 21.69 | 10.85 |
May | 21.72 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.74 | 15.09 |
October | 21.71 | 11.43 |
November | 21.61 | 8.07 |
December | 21.52 | 5.42 |
Annual Sum or Average | 21.66 | 11.24 |
Minimum of Months | 21.46 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 4.50 |
February | 22.37 | 5.82 |
March | 22.39 | 8.33 |
April | 22.42 | 10.85 |
May | 22.49 | 12.97 |
June | 22.63 | 15.59 |
July | 22.60 | 17.66 |
August | 22.57 | 18.80 |
September | 22.59 | 15.09 |
October | 22.55 | 11.43 |
November | 22.53 | 8.07 |
December | 22.39 | 5.42 |
Annual Sum or Average | 22.49 | 11.24 |
Minimum of Months | 22.37 | 4.50 |
Maximum of Months | 22.63 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.06 | 4.50 |
February | 51.31 | 5.82 |
March | 51.64 | 8.33 |
April | 51.88 | 10.85 |
May | 52.14 | 12.97 |
June | 52.36 | 15.59 |
July | 52.62 | 17.66 |
August | 52.75 | 18.80 |
September | 52.59 | 15.09 |
October | 51.97 | 11.43 |
November | 51.46 | 8.07 |
December | 51.20 | 5.42 |
Annual Sum or Average | 51.92 | 11.24 |
Minimum of Months | 51.06 | 4.50 |
Maximum of Months | 52.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 68.29 | 4.50 |
February | 68.51 | 5.82 |
March | 68.90 | 8.33 |
April | 69.15 | 10.85 |
May | 69.52 | 12.97 |
June | 69.80 | 15.59 |
July | 70.13 | 17.66 |
August | 70.26 | 18.80 |
September | 70.16 | 15.09 |
October | 69.27 | 11.43 |
November | 68.76 | 8.07 |
December | 68.50 | 5.42 |
Annual Sum or Average | 69.28 | 11.24 |
Minimum of Months | 68.29 | 4.50 |
Maximum of Months | 70.26 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.97 | 4.50 |
February | 23.07 | 5.82 |
March | 23.21 | 8.33 |
April | 23.37 | 10.85 |
May | 23.52 | 12.97 |
June | 23.71 | 15.59 |
July | 23.81 | 17.66 |
August | 23.83 | 18.80 |
September | 23.74 | 15.09 |
October | 23.48 | 11.43 |
November | 23.24 | 8.07 |
December | 23.03 | 5.42 |
Annual Sum or Average | 23.42 | 11.24 |
Minimum of Months | 22.97 | 4.50 |
Maximum of Months | 23.83 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.16 | 4.50 |
February | 22.46 | 5.82 |
March | 22.87 | 8.33 |
April | 23.19 | 10.85 |
May | 23.47 | 12.97 |
June | 23.74 | 15.59 |
July | 23.85 | 17.66 |
August | 23.86 | 18.80 |
September | 23.77 | 15.09 |
October | 23.37 | 11.43 |
November | 22.79 | 8.07 |
December | 22.28 | 5.42 |
Annual Sum or Average | 23.15 | 11.24 |
Minimum of Months | 22.16 | 4.50 |
Maximum of Months | 23.86 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.88 | 4.50 |
February | 18.45 | 5.82 |
March | 19.47 | 8.33 |
April | 20.35 | 10.85 |
May | 21.29 | 12.97 |
June | 22.17 | 15.59 |
July | 22.95 | 17.66 |
August | 23.31 | 18.80 |
September | 22.58 | 15.09 |
October | 20.54 | 11.43 |
November | 19.20 | 8.07 |
December | 18.40 | 5.42 |
Annual Sum or Average | 20.56 | 11.24 |
Minimum of Months | 17.88 | 4.50 |
Maximum of Months | 23.31 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.31 | 4.50 |
February | 20.72 | 5.82 |
March | 21.42 | 8.33 |
April | 21.97 | 10.85 |
May | 22.55 | 12.97 |
June | 23.06 | 15.59 |
July | 23.51 | 17.66 |
August | 23.72 | 18.80 |
September | 23.28 | 15.09 |
October | 22.14 | 11.43 |
November | 21.19 | 8.07 |
December | 20.61 | 5.42 |
Annual Sum or Average | 22.05 | 11.24 |
Minimum of Months | 20.31 | 4.50 |
Maximum of Months | 23.72 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.97 | 4.50 |
February | 18.60 | 5.82 |
March | 19.72 | 8.33 |
April | 20.62 | 10.85 |
May | 21.68 | 12.97 |
June | 22.47 | 15.59 |
July | 23.36 | 17.66 |
August | 23.59 | 18.80 |
September | 22.95 | 15.09 |
October | 20.77 | 11.43 |
November | 19.34 | 8.07 |
December | 18.53 | 5.42 |
Annual Sum or Average | 20.81 | 11.24 |
Minimum of Months | 17.97 | 4.50 |
Maximum of Months | 23.59 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | 4.50 |
February | 22.31 | 5.82 |
March | 22.93 | 8.33 |
April | 23.38 | 10.85 |
May | 23.71 | 12.97 |
June | 23.86 | 15.59 |
July | 23.89 | 17.66 |
August | 23.89 | 18.80 |
September | 23.86 | 15.09 |
October | 23.45 | 11.43 |
November | 22.68 | 8.07 |
December | 22.14 | 5.42 |
Annual Sum or Average | 23.17 | 11.24 |
Minimum of Months | 21.93 | 4.50 |
Maximum of Months | 23.89 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.79 | 4.50 |
February | 17.33 | 5.82 |
March | 18.46 | 8.33 |
April | 19.49 | 10.85 |
May | 20.73 | 12.97 |
June | 21.64 | 15.59 |
July | 22.55 | 17.66 |
August | 22.74 | 18.80 |
September | 21.86 | 15.09 |
October | 19.58 | 11.43 |
November | 18.16 | 8.07 |
December | 17.29 | 5.42 |
Annual Sum or Average | 19.73 | 11.24 |
Minimum of Months | 16.79 | 4.50 |
Maximum of Months | 22.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.96 | 4.50 |
February | 19.31 | 5.82 |
March | 19.75 | 8.33 |
April | 20.77 | 10.85 |
May | 21.73 | 12.97 |
June | 22.59 | 15.59 |
July | 22.97 | 17.66 |
August | 23.03 | 18.80 |
September | 22.33 | 15.09 |
October | 20.71 | 11.43 |
November | 19.58 | 8.07 |
December | 18.98 | 5.42 |
Annual Sum or Average | 20.90 | 11.24 |
Minimum of Months | 18.96 | 4.50 |
Maximum of Months | 23.03 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 4.50 |
February | 21.05 | 5.82 |
March | 21.25 | 8.33 |
April | 21.49 | 10.85 |
May | 21.66 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.71 | 15.09 |
October | 21.48 | 11.43 |
November | 21.18 | 8.07 |
December | 20.99 | 5.42 |
Annual Sum or Average | 21.42 | 11.24 |
Minimum of Months | 20.91 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | 4.50 |
February | 21.10 | 5.82 |
March | 21.30 | 8.33 |
April | 21.52 | 10.85 |
May | 21.68 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.72 | 15.09 |
October | 21.51 | 11.43 |
November | 21.23 | 8.07 |
December | 21.04 | 5.42 |
Annual Sum or Average | 21.44 | 11.24 |
Minimum of Months | 20.96 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | 4.50 |
February | 21.13 | 5.82 |
March | 21.34 | 8.33 |
April | 21.54 | 10.85 |
May | 21.68 | 12.97 |
June | 21.73 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.72 | 15.09 |
October | 21.54 | 11.43 |
November | 21.27 | 8.07 |
December | 21.08 | 5.42 |
Annual Sum or Average | 21.46 | 11.24 |
Minimum of Months | 20.99 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | 4.50 |
February | 20.87 | 5.82 |
March | 21.09 | 8.33 |
April | 21.33 | 10.85 |
May | 21.55 | 12.97 |
June | 21.69 | 15.59 |
July | 21.74 | 17.66 |
August | 21.74 | 18.80 |
September | 21.66 | 15.09 |
October | 21.33 | 11.43 |
November | 21.02 | 8.07 |
December | 20.82 | 5.42 |
Annual Sum or Average | 21.30 | 11.24 |
Minimum of Months | 20.74 | 4.50 |
Maximum of Months | 21.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 4.50 |
February | 21.30 | 5.82 |
March | 21.47 | 8.33 |
April | 21.61 | 10.85 |
May | 21.69 | 12.97 |
June | 21.73 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.73 | 15.09 |
October | 21.62 | 11.43 |
November | 21.37 | 8.07 |
December | 21.23 | 5.42 |
Annual Sum or Average | 21.53 | 11.24 |
Minimum of Months | 21.12 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.12 | 4.50 |
February | 23.18 | 5.82 |
March | 23.29 | 8.33 |
April | 23.32 | 10.85 |
May | 23.33 | 12.97 |
June | 23.33 | 15.59 |
July | 23.33 | 17.66 |
August | 23.33 | 18.80 |
September | 23.33 | 15.09 |
October | 23.33 | 11.43 |
November | 23.28 | 8.07 |
December | 23.19 | 5.42 |
Annual Sum or Average | 23.28 | 11.24 |
Minimum of Months | 23.12 | 4.50 |
Maximum of Months | 23.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.80 | 4.50 |
February | 31.13 | 5.82 |
March | 31.65 | 8.33 |
April | 32.04 | 10.85 |
May | 32.46 | 12.97 |
June | 32.76 | 15.59 |
July | 33.03 | 17.66 |
August | 33.13 | 18.80 |
September | 32.96 | 15.09 |
October | 32.12 | 11.43 |
November | 31.40 | 8.07 |
December | 31.01 | 5.42 |
Annual Sum or Average | 32.05 | 11.24 |
Minimum of Months | 30.80 | 4.50 |
Maximum of Months | 33.13 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 4.50 |
February | 21.93 | 5.82 |
March | 22.05 | 8.33 |
April | 22.21 | 10.85 |
May | 22.33 | 12.97 |
June | 22.43 | 15.59 |
July | 22.58 | 17.66 |
August | 22.68 | 18.80 |
September | 22.51 | 15.09 |
October | 22.22 | 11.43 |
November | 21.97 | 8.07 |
December | 21.84 | 5.42 |
Annual Sum or Average | 22.22 | 11.24 |
Minimum of Months | 21.81 | 4.50 |
Maximum of Months | 22.68 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 4.50 |
February | 21.42 | 5.82 |
March | 21.56 | 8.33 |
April | 21.67 | 10.85 |
May | 21.72 | 12.97 |
June | 21.75 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.74 | 15.09 |
October | 21.68 | 11.43 |
November | 21.48 | 8.07 |
December | 21.34 | 5.42 |
Annual Sum or Average | 21.59 | 11.24 |
Minimum of Months | 21.25 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 4.50 |
February | 21.27 | 5.82 |
March | 21.46 | 8.33 |
April | 21.61 | 10.85 |
May | 21.70 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.74 | 15.09 |
October | 21.62 | 11.43 |
November | 21.35 | 8.07 |
December | 21.18 | 5.42 |
Annual Sum or Average | 21.52 | 11.24 |
Minimum of Months | 21.08 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.96 | 5.82 |
March | 20.93 | 8.33 |
April | 21.67 | 10.85 |
May | 22.45 | 12.97 |
June | 23.13 | 15.59 |
July | 23.68 | 17.66 |
August | 23.94 | 18.80 |
September | 23.37 | 15.09 |
October | 21.81 | 11.43 |
November | 20.54 | 8.07 |
December | 19.78 | 5.42 |
Annual Sum or Average | 21.73 | 11.24 |
Minimum of Months | 19.39 | 4.50 |
Maximum of Months | 23.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.95 | 4.50 |
February | 17.69 | 5.82 |
March | 19.12 | 8.33 |
April | 20.26 | 10.85 |
May | 21.51 | 12.97 |
June | 22.65 | 15.59 |
July | 23.56 | 17.66 |
August | 23.98 | 18.80 |
September | 23.07 | 15.09 |
October | 20.44 | 11.43 |
November | 18.65 | 8.07 |
December | 17.59 | 5.42 |
Annual Sum or Average | 20.47 | 11.24 |
Minimum of Months | 16.95 | 4.50 |
Maximum of Months | 23.98 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.15 | 4.50 |
February | 17.86 | 5.82 |
March | 19.10 | 8.33 |
April | 20.19 | 10.85 |
May | 21.43 | 12.97 |
June | 22.37 | 15.59 |
July | 23.37 | 17.66 |
August | 23.61 | 18.80 |
September | 22.82 | 15.09 |
October | 20.29 | 11.43 |
November | 18.64 | 8.07 |
December | 17.73 | 5.42 |
Annual Sum or Average | 20.39 | 11.24 |
Minimum of Months | 17.15 | 4.50 |
Maximum of Months | 23.61 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 4.50 |
February | 21.35 | 5.82 |
March | 21.64 | 8.33 |
April | 22.35 | 10.85 |
May | 23.00 | 12.97 |
June | 23.54 | 15.59 |
July | 23.77 | 17.66 |
August | 23.78 | 18.80 |
September | 23.43 | 15.09 |
October | 22.32 | 11.43 |
November | 21.47 | 8.07 |
December | 21.14 | 5.42 |
Annual Sum or Average | 22.41 | 11.24 |
Minimum of Months | 21.12 | 4.50 |
Maximum of Months | 23.78 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.62 | 4.50 |
February | 16.23 | 5.82 |
March | 17.48 | 8.33 |
April | 18.78 | 10.85 |
May | 20.30 | 12.97 |
June | 21.49 | 15.59 |
July | 22.57 | 17.66 |
August | 22.78 | 18.80 |
September | 21.61 | 15.09 |
October | 18.80 | 11.43 |
November | 17.11 | 8.07 |
December | 16.12 | 5.42 |
Annual Sum or Average | 19.09 | 11.24 |
Minimum of Months | 15.62 | 4.50 |
Maximum of Months | 22.78 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.50 |
February | 19.06 | 5.82 |
March | 19.20 | 8.33 |
April | 20.16 | 10.85 |
May | 21.22 | 12.97 |
June | 22.29 | 15.59 |
July | 22.78 | 17.66 |
August | 22.85 | 18.80 |
September | 21.88 | 15.09 |
October | 19.94 | 11.43 |
November | 19.18 | 8.07 |
December | 18.89 | 5.42 |
Annual Sum or Average | 20.54 | 11.24 |
Minimum of Months | 18.89 | 4.50 |
Maximum of Months | 22.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.50 |
February | 19.14 | 5.82 |
March | 19.36 | 8.33 |
April | 20.37 | 10.85 |
May | 21.41 | 12.97 |
June | 22.41 | 15.59 |
July | 22.89 | 17.66 |
August | 22.95 | 18.80 |
September | 22.01 | 15.09 |
October | 20.21 | 11.43 |
November | 19.31 | 8.07 |
December | 18.90 | 5.42 |
Annual Sum or Average | 20.66 | 11.24 |
Minimum of Months | 18.90 | 4.50 |
Maximum of Months | 22.95 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.91 | 4.50 |
February | 19.19 | 5.82 |
March | 19.50 | 8.33 |
April | 20.51 | 10.85 |
May | 21.52 | 12.97 |
June | 22.44 | 15.59 |
July | 22.88 | 17.66 |
August | 22.94 | 18.80 |
September | 22.04 | 15.09 |
October | 20.36 | 11.43 |
November | 19.39 | 8.07 |
December | 18.92 | 5.42 |
Annual Sum or Average | 20.72 | 11.24 |
Minimum of Months | 18.91 | 4.50 |
Maximum of Months | 22.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 4.50 |
February | 21.03 | 5.82 |
March | 21.24 | 8.33 |
April | 21.47 | 10.85 |
May | 21.64 | 12.97 |
June | 21.72 | 15.59 |
July | 21.75 | 17.66 |
August | 21.74 | 18.80 |
September | 21.69 | 15.09 |
October | 21.45 | 11.43 |
November | 21.16 | 8.07 |
December | 20.96 | 5.42 |
Annual Sum or Average | 21.40 | 11.24 |
Minimum of Months | 20.88 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.50 |
February | 19.14 | 5.82 |
March | 19.38 | 8.33 |
April | 20.33 | 10.85 |
May | 21.35 | 12.97 |
June | 22.27 | 15.59 |
July | 22.80 | 17.66 |
August | 22.87 | 18.80 |
September | 22.02 | 15.09 |
October | 20.25 | 11.43 |
November | 19.31 | 8.07 |
December | 18.90 | 5.42 |
Annual Sum or Average | 20.63 | 11.24 |
Minimum of Months | 18.90 | 4.50 |
Maximum of Months | 22.87 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 4.50 |
February | 21.10 | 5.82 |
March | 21.29 | 8.33 |
April | 21.48 | 10.85 |
May | 21.62 | 12.97 |
June | 21.71 | 15.59 |
July | 21.74 | 17.66 |
August | 21.75 | 18.80 |
September | 21.70 | 15.09 |
October | 21.50 | 11.43 |
November | 21.17 | 8.07 |
December | 21.01 | 5.42 |
Annual Sum or Average | 21.42 | 11.24 |
Minimum of Months | 20.90 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 4.50 |
February | 21.47 | 5.82 |
March | 21.60 | 8.33 |
April | 21.69 | 10.85 |
May | 21.73 | 12.97 |
June | 21.75 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.75 | 15.09 |
October | 21.70 | 11.43 |
November | 21.52 | 8.07 |
December | 21.39 | 5.42 |
Annual Sum or Average | 21.62 | 11.24 |
Minimum of Months | 21.30 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.60 | 4.50 |
February | 23.04 | 5.82 |
March | 23.68 | 8.33 |
April | 24.30 | 10.85 |
May | 24.90 | 12.97 |
June | 25.37 | 15.59 |
July | 25.71 | 17.66 |
August | 25.79 | 18.80 |
September | 25.44 | 15.09 |
October | 24.31 | 11.43 |
November | 23.35 | 8.07 |
December | 22.83 | 5.42 |
Annual Sum or Average | 24.28 | 11.24 |
Minimum of Months | 22.60 | 4.50 |
Maximum of Months | 25.79 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 4.50 |
February | 21.64 | 5.82 |
March | 22.32 | 8.33 |
April | 22.78 | 10.85 |
May | 23.10 | 12.97 |
June | 23.29 | 15.59 |
July | 23.33 | 17.66 |
August | 23.33 | 18.80 |
September | 23.28 | 15.09 |
October | 22.86 | 11.43 |
November | 21.96 | 8.07 |
December | 21.32 | 5.42 |
Annual Sum or Average | 22.53 | 11.24 |
Minimum of Months | 21.08 | 4.50 |
Maximum of Months | 23.33 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.10 | 4.50 |
February | 21.31 | 5.82 |
March | 21.46 | 8.33 |
April | 21.61 | 10.85 |
May | 21.69 | 12.97 |
June | 21.73 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.72 | 15.09 |
October | 21.61 | 11.43 |
November | 21.35 | 8.07 |
December | 21.20 | 5.42 |
Annual Sum or Average | 21.53 | 11.24 |
Minimum of Months | 21.10 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.16 | 4.50 |
February | 19.82 | 5.82 |
March | 20.58 | 8.33 |
April | 21.39 | 10.85 |
May | 22.05 | 12.97 |
June | 22.67 | 15.59 |
July | 23.00 | 17.66 |
August | 23.06 | 18.80 |
September | 22.63 | 15.09 |
October | 21.48 | 11.43 |
November | 20.11 | 8.07 |
December | 19.39 | 5.42 |
Annual Sum or Average | 21.29 | 11.24 |
Minimum of Months | 19.16 | 4.50 |
Maximum of Months | 23.06 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.24 | 4.50 |
February | 18.95 | 5.82 |
March | 20.13 | 8.33 |
April | 21.12 | 10.85 |
May | 22.14 | 12.97 |
June | 23.05 | 15.59 |
July | 23.73 | 17.66 |
August | 24.00 | 18.80 |
September | 23.21 | 15.09 |
October | 21.21 | 11.43 |
November | 19.60 | 8.07 |
December | 18.67 | 5.42 |
Annual Sum or Average | 21.18 | 11.24 |
Minimum of Months | 18.24 | 4.50 |
Maximum of Months | 24.00 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.96 | 4.50 |
February | 16.80 | 5.82 |
March | 18.43 | 8.33 |
April | 19.79 | 10.85 |
May | 21.26 | 12.97 |
June | 22.59 | 15.59 |
July | 23.62 | 17.66 |
August | 24.06 | 18.80 |
September | 22.95 | 15.09 |
October | 19.91 | 11.43 |
November | 17.85 | 8.07 |
December | 16.64 | 5.42 |
Annual Sum or Average | 20.01 | 11.24 |
Minimum of Months | 15.96 | 4.50 |
Maximum of Months | 24.06 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.84 | 4.50 |
February | 16.70 | 5.82 |
March | 18.12 | 8.33 |
April | 19.56 | 10.85 |
May | 21.06 | 12.97 |
June | 22.24 | 15.59 |
July | 23.41 | 17.66 |
August | 23.62 | 18.80 |
September | 22.48 | 15.09 |
October | 19.46 | 11.43 |
November | 17.50 | 8.07 |
December | 16.42 | 5.42 |
Annual Sum or Average | 19.72 | 11.24 |
Minimum of Months | 15.84 | 4.50 |
Maximum of Months | 23.62 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | 4.50 |
February | 21.22 | 5.82 |
March | 21.43 | 8.33 |
April | 21.98 | 10.85 |
May | 22.51 | 12.97 |
June | 23.05 | 15.59 |
July | 23.34 | 17.66 |
August | 23.42 | 18.80 |
September | 22.82 | 15.09 |
October | 21.75 | 11.43 |
November | 21.25 | 8.07 |
December | 21.12 | 5.42 |
Annual Sum or Average | 22.09 | 11.24 |
Minimum of Months | 21.11 | 4.50 |
Maximum of Months | 23.42 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.71 | 4.50 |
February | 15.41 | 5.82 |
March | 16.78 | 8.33 |
April | 18.34 | 10.85 |
May | 20.03 | 12.97 |
June | 21.39 | 15.59 |
July | 22.60 | 17.66 |
August | 22.77 | 18.80 |
September | 21.29 | 15.09 |
October | 18.12 | 11.43 |
November | 16.29 | 8.07 |
December | 15.21 | 5.42 |
Annual Sum or Average | 18.60 | 11.24 |
Minimum of Months | 14.71 | 4.50 |
Maximum of Months | 22.77 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | 4.50 |
February | 20.66 | 5.82 |
March | 20.88 | 8.33 |
April | 21.28 | 10.85 |
May | 21.54 | 12.97 |
June | 21.69 | 15.59 |
July | 21.73 | 17.66 |
August | 21.73 | 18.80 |
September | 21.59 | 15.09 |
October | 21.14 | 11.43 |
November | 20.73 | 8.07 |
December | 20.54 | 5.42 |
Annual Sum or Average | 21.17 | 11.24 |
Minimum of Months | 20.50 | 4.50 |
Maximum of Months | 21.73 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.50 |
February | 19.02 | 5.82 |
March | 19.21 | 8.33 |
April | 20.07 | 10.85 |
May | 21.01 | 12.97 |
June | 22.01 | 15.59 |
July | 22.50 | 17.66 |
August | 22.60 | 18.80 |
September | 21.48 | 15.09 |
October | 19.70 | 11.43 |
November | 19.08 | 8.07 |
December | 18.89 | 5.42 |
Annual Sum or Average | 20.38 | 11.24 |
Minimum of Months | 18.89 | 4.50 |
Maximum of Months | 22.60 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.50 |
February | 19.04 | 5.82 |
March | 19.26 | 8.33 |
April | 20.14 | 10.85 |
May | 21.07 | 12.97 |
June | 22.02 | 15.59 |
July | 22.50 | 17.66 |
August | 22.58 | 18.80 |
September | 21.50 | 15.09 |
October | 19.76 | 11.43 |
November | 19.11 | 8.07 |
December | 18.89 | 5.42 |
Annual Sum or Average | 20.40 | 11.24 |
Minimum of Months | 18.89 | 4.50 |
Maximum of Months | 22.58 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | 4.50 |
February | 20.94 | 5.82 |
March | 21.23 | 8.33 |
April | 21.52 | 10.85 |
May | 21.67 | 12.97 |
June | 21.73 | 15.59 |
July | 21.74 | 17.66 |
August | 21.74 | 18.80 |
September | 21.69 | 15.09 |
October | 21.43 | 11.43 |
November | 21.05 | 8.07 |
December | 20.81 | 5.42 |
Annual Sum or Average | 21.36 | 11.24 |
Minimum of Months | 20.72 | 4.50 |
Maximum of Months | 21.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | 4.50 |
February | 19.03 | 5.82 |
March | 19.23 | 8.33 |
April | 20.09 | 10.85 |
May | 21.04 | 12.97 |
June | 21.99 | 15.59 |
July | 22.51 | 17.66 |
August | 22.60 | 18.80 |
September | 21.61 | 15.09 |
October | 19.77 | 11.43 |
November | 19.11 | 8.07 |
December | 18.89 | 5.42 |
Annual Sum or Average | 20.41 | 11.24 |
Minimum of Months | 18.89 | 4.50 |
Maximum of Months | 22.60 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.96 | 4.50 |
February | 19.41 | 5.82 |
March | 19.90 | 8.33 |
April | 20.76 | 10.85 |
May | 21.51 | 12.97 |
June | 22.23 | 15.59 |
July | 22.64 | 17.66 |
August | 22.74 | 18.80 |
September | 22.08 | 15.09 |
October | 20.63 | 11.43 |
November | 19.49 | 8.07 |
December | 19.07 | 5.42 |
Annual Sum or Average | 20.79 | 11.24 |
Minimum of Months | 18.96 | 4.50 |
Maximum of Months | 22.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.03 | 4.50 |
February | 21.31 | 5.82 |
March | 21.48 | 8.33 |
April | 21.64 | 10.85 |
May | 21.70 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.72 | 15.09 |
October | 21.60 | 11.43 |
November | 21.33 | 8.07 |
December | 21.15 | 5.42 |
Annual Sum or Average | 21.52 | 11.24 |
Minimum of Months | 21.03 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.22 | 4.50 |
February | 20.74 | 5.82 |
March | 21.46 | 8.33 |
April | 22.26 | 10.85 |
May | 22.98 | 12.97 |
June | 23.58 | 15.59 |
July | 24.03 | 17.66 |
August | 24.08 | 18.80 |
September | 23.43 | 15.09 |
October | 22.06 | 11.43 |
November | 21.02 | 8.07 |
December | 20.44 | 5.42 |
Annual Sum or Average | 22.20 | 11.24 |
Minimum of Months | 20.22 | 4.50 |
Maximum of Months | 24.08 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | 4.50 |
February | 21.28 | 5.82 |
March | 21.46 | 8.33 |
April | 21.63 | 10.85 |
May | 21.70 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.73 | 15.09 |
October | 21.60 | 11.43 |
November | 21.31 | 8.07 |
December | 21.13 | 5.42 |
Annual Sum or Average | 21.51 | 11.24 |
Minimum of Months | 21.01 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 4.50 |
February | 21.27 | 5.82 |
March | 21.45 | 8.33 |
April | 21.63 | 10.85 |
May | 21.70 | 12.97 |
June | 21.74 | 15.59 |
July | 21.75 | 17.66 |
August | 21.75 | 18.80 |
September | 21.72 | 15.09 |
October | 21.58 | 11.43 |
November | 21.29 | 8.07 |
December | 21.10 | 5.42 |
Annual Sum or Average | 21.50 | 11.24 |
Minimum of Months | 20.98 | 4.50 |
Maximum of Months | 21.75 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | 4.50 |
February | 21.04 | 5.82 |
March | 21.28 | 8.33 |
April | 21.53 | 10.85 |
May | 21.65 | 12.97 |
June | 21.72 | 15.59 |
July | 21.74 | 17.66 |
August | 21.74 | 18.80 |
September | 21.69 | 15.09 |
October | 21.48 | 11.43 |
November | 21.09 | 8.07 |
December | 20.87 | 5.42 |
Annual Sum or Average | 21.38 | 11.24 |
Minimum of Months | 20.73 | 4.50 |
Maximum of Months | 21.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.64 | 4.50 |
February | 18.43 | 5.82 |
March | 19.68 | 8.33 |
April | 20.87 | 10.85 |
May | 21.97 | 12.97 |
June | 22.95 | 15.59 |
July | 23.69 | 17.66 |
August | 23.89 | 18.80 |
September | 22.88 | 15.09 |
October | 20.72 | 11.43 |
November | 19.05 | 8.07 |
December | 18.07 | 5.42 |
Annual Sum or Average | 20.83 | 11.24 |
Minimum of Months | 17.64 | 4.50 |
Maximum of Months | 23.89 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:36
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.09 | 4.50 |
February | 16.05 | 5.82 |
March | 17.79 | 8.33 |
April | 19.41 | 10.85 |
May | 21.02 | 12.97 |
June | 22.48 | 15.59 |
July | 23.62 | 17.66 |
August | 23.98 | 18.80 |
September | 22.62 | 15.09 |
October | 19.30 | 11.43 |
November | 17.10 | 8.07 |
December | 15.78 | 5.42 |
Annual Sum or Average | 19.54 | 11.24 |
Minimum of Months | 15.09 | 4.50 |
Maximum of Months | 23.98 | 18.80 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.143840E+12 | 102719.256 | 08-JAN-07:15 | 15177.258 | 39465.561 | 8657.416 | 34840.997 | 381.911 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.126686E+12 | 103996.033 | 19-FEB-07:15 | 13316.689 | 34010.661 | 8657.864 | 47816.121 | 186.586 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.130774E+12 | 85110.445 | 01-MAR-07:15 | 15177.258 | 39465.561 | 8657.416 | 20347.938 | 1454.159 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.126498E+12 | 81908.069 | 19-APR-06:15 | 15028.424 | 39465.561 | 8657.416 | 17109.071 | 1639.485 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.132703E+12 | 84614.362 | 06-MAY-07:00 | 17641.054 | 43276.576 | 9036.221 | 0.000 | 14652.398 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.132701E+12 | 83969.950 | 10-JUN-07:00 | 17566.637 | 43276.576 | 9036.221 | 0.000 | 14082.403 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.143368E+12 | 84711.138 | 22-JUL-07:00 | 17789.888 | 43276.576 | 9036.221 | 0.000 | 14600.340 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.146869E+12 | 87937.871 | 25-AUG-07:00 | 17492.219 | 43276.576 | 9036.221 | 0.000 | 18124.742 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.134192E+12 | 83822.972 | 01-SEP-07:00 | 17641.054 | 43276.576 | 9036.221 | 0.000 | 13861.008 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.131134E+12 | 81316.132 | 16-OCT-06:30 | 15177.258 | 39465.561 | 8657.416 | 10163.934 | 3655.850 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.130194E+12 | 89537.910 | 13-NOV-07:15 | 15177.258 | 39465.561 | 8657.416 | 20981.391 | 1060.171 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.140567E+12 | 98556.266 | 26-DEC-07:15 | 15177.258 | 39465.561 | 8657.416 | 30665.957 | 393.960 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.161952E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.126498E+12 | 81316.132 | 13316.689 | 34010.661 | 8657.416 | 0.000 | 186.586 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.146869E+12 | 103996.033 | 17789.888 | 43276.576 | 9036.221 | 47816.121 | 18124.742 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:36
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.103120E+12 | 104374.967 | 07-JAN-11:00 | 8663.486 | 40096.028 | 0.000 | 55615.453 | 55615.453 | 55615.453 | 8663.486 |
February | 0.917997E+11 | 104110.884 | 18-FEB-10:15 | 7154.229 | 40096.028 | 0.000 | 56860.627 | 56860.627 | 56860.627 | 7154.229 |
March | 0.965284E+11 | 97996.129 | 18-MAR-08:15 | 0.000 | 40096.028 | 0.000 | 57900.101 | 57900.101 | 57900.101 | 0.000 |
April | 0.900407E+11 | 96812.325 | 14-APR-08:15 | 0.000 | 40096.028 | 0.000 | 56716.297 | 56716.297 | 56716.297 | 0.000 |
May | 0.897545E+11 | 95117.358 | 05-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 55021.329 | 55021.329 | 55021.329 | 0.000 |
June | 0.840113E+11 | 93040.899 | 03-JUN-08:30 | 0.000 | 40096.028 | 0.000 | 52944.871 | 52944.871 | 52944.871 | 0.000 |
July | 0.851965E+11 | 91745.960 | 21-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 51649.932 | 51649.932 | 51649.932 | 0.000 |
August | 0.847964E+11 | 91203.165 | 25-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 51107.137 | 51107.137 | 51107.137 | 0.000 |
September | 0.828471E+11 | 91679.880 | 30-SEP-08:00 | 0.000 | 40096.028 | 0.000 | 51583.852 | 51583.852 | 51583.852 | 0.000 |
October | 0.886749E+11 | 93848.215 | 20-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 53752.187 | 53752.187 | 53752.187 | 0.000 |
November | 0.913793E+11 | 99231.946 | 11-NOV-10:30 | 5753.229 | 40096.028 | 0.000 | 53382.689 | 53382.689 | 53382.689 | 5753.229 |
December | 0.998916E+11 | 100845.029 | 25-DEC-10:30 | 7691.933 | 40096.028 | 0.000 | 53057.068 | 53057.068 | 53057.068 | 7691.933 |
Annual Sum or Average | 0.108804E+13 | 0.000 | ||||||||
Minimum of Months | 0.828471E+11 | 91203.165 | 0.000 | 40096.028 | 0.000 | 51107.137 | 51107.137 | 51107.137 | 0.000 | |
Maximum of Months | 0.103120E+12 | 104374.967 | 8663.486 | 40096.028 | 0.000 | 57900.101 | 57900.101 | 57900.101 | 8663.486 |