Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2018-10-19 10:15:42
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2945.71 | 733.94 | 790.78 |
Net Site Energy | 2945.71 | 733.94 | 790.78 |
Total Source Energy | 7448.58 | 1855.84 | 1999.57 |
Net Source Energy | 7448.58 | 1855.84 | 1999.57 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 687.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 280.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 481.29 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2042.93 | 902.78 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 687.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 280.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 481.29 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 259.79 | 129.20 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 548.42 | 242.35 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 241.12 | 119.91 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 509.01 | 224.93 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2042.93 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2042.93 | 100.00 |
Total On-Site and Utility Electric Sources | 2042.93 | 100.00 |
Total Electricity End Uses | 2042.93 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 299.00 |
Time Setpoint Not Met During Occupied Cooling | 6130.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6394.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [m] | 2.00 |
Time Zone | -10.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.00 | 16.20 | Wetbulb [C] | 1.90 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 7.10 | 23.30 | Wetbulb [C] | 6.70 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.704 | 0.787 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_1.22_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 5.778 | 0.306 | 0.155 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 5.778 | 0.306 | 0.155 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_1.22_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 5.778 | 0.306 | 0.155 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 5.778 | 0.306 | 0.155 | ||||||||||||
North Total or Average | 96.82 | 5.778 | 0.306 | 0.155 | ||||||||||||
Non-North Total or Average | 87.38 | 5.778 | 0.306 | 0.155 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7183.00 | 5062.48 | 2120.51 | 0.70 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19644.53 | 13281.33 | 6363.19 | 0.68 | 3.80 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8994.31 | 6080.90 | 2913.41 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14458.19 | 10383.08 | 4075.11 | 0.72 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6932.0 | 3.32 | 11.34 | 12.02 | 11.40 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19029.6 | 3.29 | 11.23 | 11.91 | 11.42 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8712.8 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13928.4 | 3.30 | 11.25 | 11.92 | 11.27 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 4137.19 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 1355.37 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 1772.58 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 477.87 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 1355.37 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 1772.58 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.36 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 1585.78 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 1772.58 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 2236.60 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 559.15 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 2236.44 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 559.11 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.28 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 2302.33 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 9650.18 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 5167.60 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 3859.80 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.32 | 361.95 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.79 | 875.86 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 405.70 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.68 | 764.09 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7994.32 | 9593.18 | 0.659 | 0.791 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
RESTROOMFLR1 | 480.29 | 576.35 | 0.040 | 0.047 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 31.49 | 0.01435 |
MEETINGROOMFLR1 | 3658.05 | 4389.66 | 0.302 | 0.362 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM101 | 637.67 | 765.20 | 0.073 | 0.088 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM102 | 534.35 | 641.22 | 0.061 | 0.073 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM103 | 1169.52 | 1403.42 | 0.134 | 0.161 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 29.96 | 0.01435 |
GUESTROOM104 | 1256.35 | 1507.62 | 0.144 | 0.173 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM105 | 1551.54 | 1861.85 | 0.178 | 0.213 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
EMPLOYEELOUNGEFLR1 | 5215.66 | 6258.80 | 0.430 | 0.516 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
EXERCISECENTERFLR1 | 1197.90 | 1437.49 | 0.099 | 0.118 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 31.21 | 0.01435 |
FRONTOFFICEFLR1 | 3268.11 | 3921.73 | 0.269 | 0.323 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM201 | 1035.04 | 1242.04 | 0.119 | 0.142 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 12:45:00 | 31.70 | 0.01435 |
GUESTROOM202_205 | 4326.04 | 5191.24 | 0.496 | 0.595 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM206_208 | 3485.85 | 4183.02 | 0.399 | 0.479 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM209_212 | 4118.46 | 4942.16 | 0.472 | 0.566 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM213 | 1219.54 | 1463.45 | 0.140 | 0.168 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 29.96 | 0.01435 |
GUESTROOM214 | 1363.86 | 1636.63 | 0.156 | 0.188 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
GUESTROOM215_218 | 9273.16 | 11127.79 | 1.062 | 1.275 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM219 | 5246.49 | 6295.79 | 0.601 | 0.721 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
GUESTROOM220_223 | 4615.87 | 5539.04 | 0.529 | 0.635 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM224 | 1338.07 | 1605.69 | 0.153 | 0.184 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM301 | 857.91 | 1029.49 | 0.098 | 0.118 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 31.85 | 0.01435 |
GUESTROOM302_305 | 1760.75 | 2112.90 | 0.202 | 0.242 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM306_308 | 1521.70 | 1826.04 | 0.174 | 0.209 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM309_312 | 4067.31 | 4880.77 | 0.466 | 0.559 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM313 | 719.25 | 863.10 | 0.082 | 0.099 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 29.96 | 0.01435 |
GUESTROOM314 | 1288.04 | 1545.65 | 0.148 | 0.177 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM315_318 | 4968.27 | 5961.93 | 0.569 | 0.683 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM319 | 1100.75 | 1320.90 | 0.126 | 0.151 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
GUESTROOM320_323 | 4402.94 | 5283.53 | 0.504 | 0.605 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM324 | 771.82 | 926.19 | 0.088 | 0.106 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
GUESTROOM401 | 1645.96 | 1975.15 | 0.189 | 0.226 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 31.85 | 0.01435 |
GUESTROOM402_405 | 2326.03 | 2791.24 | 0.266 | 0.320 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM406_408 | 1982.10 | 2378.52 | 0.227 | 0.272 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM409_412 | 4922.10 | 5906.52 | 0.564 | 0.677 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
GUESTROOM413 | 898.57 | 1078.28 | 0.103 | 0.124 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 31.77 | 0.01435 |
GUESTROOM414 | 1004.81 | 1205.77 | 0.115 | 0.138 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 32.09 | 0.01435 |
GUESTROOM415_418 | 5389.47 | 6467.37 | 0.618 | 0.741 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 32.20 | 0.01435 |
GUESTROOM419 | 1483.92 | 1780.71 | 0.170 | 0.204 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 32.20 | 0.01435 |
GUESTROOM420_423 | 5365.48 | 6438.58 | 0.615 | 0.738 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 32.20 | 0.01435 |
GUESTROOM424 | 1536.08 | 1843.30 | 0.176 | 0.211 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 32.20 | 0.01435 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
CORRIDORFLR1 | 17215.46 | 20658.55 | 1.419 | 1.703 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 30.50 | 0.01435 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
CORRIDORFLR2 | 2771.87 | 3326.24 | 0.228 | 0.274 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:15:00 | 31.03 | 0.01435 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
CORRIDORFLR3 | 1406.92 | 1688.31 | 0.116 | 0.139 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 30.85 | 0.01435 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 | |
CORRIDORFLR4 | 2021.94 | 2426.33 | 0.167 | 0.200 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 31.88 | 0.01435 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 32.20 | 0.01435 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 341.11 | 409.33 | 0.010 | 0.236 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:30:00 | 16.20 | 0.01152 |
MEETINGROOMFLR1 | 57.34 | 68.81 | 0.002 | 0.126 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:45:00 | 16.20 | 0.01152 |
GUESTROOM101 | 19.28 | 23.14 | 0.001 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:30:00 | 16.20 | 0.01152 |
GUESTROOM102 | 50.65 | 60.77 | 0.001 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:30:00 | 16.20 | 0.01152 |
GUESTROOM103 | 90.16 | 108.19 | 0.003 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:30:00 | 16.20 | 0.01152 |
GUESTROOM104 | 73.06 | 87.67 | 0.002 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:30:00 | 16.20 | 0.01152 |
GUESTROOM105 | 46.59 | 55.91 | 0.001 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:45:00 | 16.20 | 0.01152 |
EMPLOYEELOUNGEFLR1 | 18.26 | 21.91 | 0.001 | 0.051 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:30:00 | 16.20 | 0.01152 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.000 | 0.043 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
FRONTOFFICEFLR1 | 153.08 | 183.70 | 0.004 | 0.056 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 06:30:00 | 16.20 | 0.01152 |
GUESTROOM201 | 126.73 | 152.08 | 0.004 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM202_205 | 232.18 | 278.62 | 0.007 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM206_208 | 142.11 | 170.54 | 0.004 | 0.043 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM209_212 | 169.48 | 203.37 | 0.005 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 00:15:00 | 16.20 | 0.01152 |
GUESTROOM213 | 103.97 | 124.76 | 0.003 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM214 | 75.99 | 91.18 | 0.002 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:00:00 | 16.20 | 0.01152 |
GUESTROOM215_218 | 125.34 | 150.41 | 0.004 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:15:00 | 16.20 | 0.01152 |
GUESTROOM219 | 0.00 | 0.00 | 0.000 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
GUESTROOM220_223 | 140.93 | 169.12 | 0.004 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 08:00:00 | 16.20 | 0.01152 |
GUESTROOM224 | 69.96 | 83.95 | 0.002 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 09:15:00 | 16.20 | 0.01152 |
GUESTROOM301 | 146.49 | 175.78 | 0.004 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM302_305 | 287.79 | 345.35 | 0.008 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM306_308 | 233.98 | 280.77 | 0.007 | 0.043 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM309_312 | 271.55 | 325.86 | 0.008 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM313 | 128.91 | 154.69 | 0.004 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM314 | 98.57 | 118.28 | 0.003 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 16:30:00 | 16.20 | 0.01152 |
GUESTROOM315_318 | 252.71 | 303.25 | 0.007 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:15:00 | 16.20 | 0.01152 |
GUESTROOM319 | 47.96 | 57.55 | 0.001 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 13:30:00 | 16.20 | 0.01152 |
GUESTROOM320_323 | 233.42 | 280.10 | 0.007 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 14:45:00 | 16.20 | 0.01152 |
GUESTROOM324 | 95.08 | 114.10 | 0.003 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 21:00:00 | 16.20 | 0.01152 |
GUESTROOM401 | 204.25 | 245.10 | 0.006 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM402_405 | 494.38 | 593.26 | 0.014 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM406_408 | 413.72 | 496.46 | 0.012 | 0.043 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM409_412 | 489.05 | 586.86 | 0.014 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM413 | 194.87 | 233.85 | 0.005 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM414 | 164.13 | 196.96 | 0.005 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
GUESTROOM415_418 | 479.18 | 575.01 | 0.014 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 17:30:00 | 16.20 | 0.01152 |
GUESTROOM419 | 124.90 | 149.88 | 0.004 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:15:00 | 16.20 | 0.01152 |
GUESTROOM420_423 | 453.88 | 544.65 | 0.013 | 0.054 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 19:45:00 | 16.20 | 0.01152 |
GUESTROOM424 | 162.02 | 194.43 | 0.005 | 0.013 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 24:00:00 | 16.20 | 0.01152 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
CORRIDORFLR1 | 3216.52 | 3859.82 | 0.091 | 0.109 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 18:30:00 | 16.20 | 0.01152 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
CORRIDORFLR2 | 0.00 | 0.00 | 0.000 | 0.038 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
CORRIDORFLR3 | 0.00 | 0.00 | 0.000 | 0.038 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 | |
CORRIDORFLR4 | 35.97 | 43.17 | 0.001 | 0.038 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 22:00:00 | 16.20 | 0.01152 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 16.20 | 0.01152 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.32 | 0.32 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.79 | 0.79 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.36 | 0.36 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.68 | 0.68 | 0.09 | 0.09 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 7422.50 | 2783.25 | 2444.75 |
RESTROOMFLR1 | 2560.00 | 2698.50 | 210.25 |
MEETINGROOMFLR1 | 4129.00 | 777.00 | 677.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 109.75 | 8490.75 | 109.75 |
GUESTROOM104 | 43.50 | 7688.75 | 42.25 |
GUESTROOM105 | 125.75 | 6877.50 | 8.75 |
EMPLOYEELOUNGEFLR1 | 3263.00 | 1944.75 | 300.50 |
EXERCISECENTERFLR1 | 5344.25 | 76.75 | 53.75 |
FRONTOFFICEFLR1 | 5406.75 | 571.00 | 213.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 137.75 | 6840.50 | 26.75 |
GUESTROOM206_208 | 120.25 | 6870.75 | 18.75 |
GUESTROOM209_212 | 82.75 | 7015.25 | 32.25 |
GUESTROOM213 | 48.50 | 7632.00 | 45.25 |
GUESTROOM214 | 180.25 | 6869.75 | 17.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 6161.00 | 3672.25 | 1656.00 |
GUESTROOM220_223 | 488.25 | 6618.50 | 26.25 |
GUESTROOM224 | 200.00 | 6708.50 | 12.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 103.75 | 7494.00 | 94.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 179.75 | 6875.00 | 20.25 |
GUESTROOM315_318 | 695.50 | 6489.75 | 15.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 394.25 | 6900.50 | 53.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1749.25 | 6390.50 | 22.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1527.25 | 6433.00 | 22.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2033.00 | 6330.75 | 13.00 |
GUESTROOM419 | 1498.50 | 6394.25 | 5.25 |
GUESTROOM420_423 | 1990.25 | 6340.25 | 16.50 |
GUESTROOM424 | 1528.50 | 6413.25 | 8.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 8282.00 | 8753.75 | 6394.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 2513.50 | 0.00 | 2513.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM104 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM105 | 0.00 | 91.25 | 0.00 | 91.25 |
EMPLOYEELOUNGEFLR1 | 387.00 | 1377.00 | 299.00 | 694.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 88.50 | 0.00 | 88.50 |
GUESTROOM206_208 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM209_212 | 0.00 | 87.50 | 0.00 | 87.50 |
GUESTROOM213 | 0.00 | 89.00 | 0.00 | 89.00 |
GUESTROOM214 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 4829.75 | 0.00 | 4829.75 |
GUESTROOM220_223 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM224 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 86.75 | 0.00 | 86.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM315_318 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 90.25 | 0.00 | 90.25 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 89.25 | 0.00 | 89.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM419 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM420_423 | 0.00 | 91.25 | 0.00 | 91.25 |
GUESTROOM424 | 0.00 | 91.25 | 0.00 | 91.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 7867.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 1166.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 1.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 998.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 387.00 | 8401.25 | 299.00 | 6130.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:42
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.323137 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.791085 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.682156 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR1 PTAC HEATING COIL | 4137.19 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 559.15 |
102 PTAC HEATING COIL | 559.15 |
103 PTAC HEATING COIL | 559.15 |
104 PTAC HEATING COIL | 559.11 |
105 PTAC HEATING COIL | 559.11 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR2 PTAC HEATING COIL | 1355.37 |
201 PTAC HEATING COIL | 559.15 |
202_205 PTAC HEATING COIL | 2236.60 |
206_208 PTAC HEATING COIL | 1772.58 |
209_212 PTAC HEATING COIL | 2236.60 |
213 PTAC HEATING COIL | 559.15 |
214 PTAC HEATING COIL | 559.11 |
215_218 PTAC HEATING COIL | 2236.44 |
219 PTAC HEATING COIL | 477.87 |
220_223 PTAC HEATING COIL | 2236.44 |
224 PTAC HEATING COIL | 559.11 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR3 PTAC HEATING COIL | 1355.37 |
301 PTAC HEATING COIL | 559.15 |
302_305 PTAC HEATING COIL | 2236.60 |
306_308 PTAC HEATING COIL | 1772.58 |
309_312 PTAC HEATING COIL | 2236.60 |
313 PTAC HEATING COIL | 559.15 |
314 PTAC HEATING COIL | 559.11 |
315_318 PTAC HEATING COIL | 2236.44 |
319 PTAC HEATING COIL | 559.11 |
320_323 PTAC HEATING COIL | 2236.44 |
324 PTAC HEATING COIL | 559.11 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.28 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.36 |
CORRIDORFLR4 PTAC HEATING COIL | 1585.78 |
401 PTAC HEATING COIL | 559.15 |
402_405 PTAC HEATING COIL | 2236.60 |
406_408 PTAC HEATING COIL | 1772.58 |
409_412 PTAC HEATING COIL | 2236.60 |
413 PTAC HEATING COIL | 559.15 |
414 PTAC HEATING COIL | 559.11 |
415_418 PTAC HEATING COIL | 2236.44 |
419 PTAC HEATING COIL | 559.11 |
420_423 PTAC HEATING COIL | 2236.44 |
424 PTAC HEATING COIL | 559.11 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.28 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.704787 | 0.323137 | 7183.00 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 0.791085 | 19644.53 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.362201 | 8994.31 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.718146 | 0.682156 | 14458.19 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.791085 |
RESTROOMFLR1 DIRECT AIR | 0.047481 |
MEETINGROOMFLR1 DIRECT AIR | 0.362201 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.516189 |
EXERCISECENTERFLR1 DIRECT AIR | 0.118486 |
FRONTOFFICEFLR1 DIRECT AIR | 0.323137 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.323137 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.791085 |
SAC_MEETINGROOM MAIN BRANCH | 0.362201 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.682156 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.323137 |
SAC_FRONTLOUNGE | 0.791085 |
SAC_MEETINGROOM | 0.362201 |
SAC_EXC_EMPLGE_RESTRM | 0.682156 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.323137 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.791085 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.362201 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.682156 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.323137 | 0.323137 | 0.323137 | 0.323137 | 2302.33 | 7183.00 | 1.00 |
SAC_FRONTLOUNGE | 0.791085 | 0.791085 | 0.791085 | 0.791085 | 9650.18 | 19644.53 | 1.00 |
SAC_MEETINGROOM | 0.362201 | 0.362201 | 0.362201 | 0.362201 | 5167.60 | 8994.31 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.682156 | 0.682156 | 0.682156 | 0.682156 | 3859.80 | 14458.19 | 0.173694 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 2302.33 |
SAC_FRONTLOUNGE HEATING COIL | 9650.18 |
SAC_MEETINGROOM HEATING COIL | 5167.60 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 3859.80 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.362201 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.16 | 22.49 |
February | 24.42 | 22.80 |
March | 24.51 | 23.17 |
April | 24.55 | 23.76 |
May | 24.98 | 25.23 |
June | 25.24 | 25.87 |
July | 25.62 | 26.90 |
August | 25.70 | 27.06 |
September | 25.92 | 26.87 |
October | 25.44 | 26.22 |
November | 25.03 | 24.76 |
December | 24.59 | 23.69 |
Annual Sum or Average | 25.02 | 24.91 |
Minimum of Months | 24.16 | 22.49 |
Maximum of Months | 25.92 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.66 | 22.49 |
February | 25.91 | 22.80 |
March | 25.91 | 23.17 |
April | 25.97 | 23.76 |
May | 26.46 | 25.23 |
June | 26.63 | 25.87 |
July | 26.97 | 26.90 |
August | 27.01 | 27.06 |
September | 27.03 | 26.87 |
October | 26.83 | 26.22 |
November | 26.37 | 24.76 |
December | 26.05 | 23.69 |
Annual Sum or Average | 26.40 | 24.91 |
Minimum of Months | 25.66 | 22.49 |
Maximum of Months | 27.03 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.34 | 22.49 |
February | 23.70 | 22.80 |
March | 23.91 | 23.17 |
April | 24.09 | 23.76 |
May | 24.64 | 25.23 |
June | 24.94 | 25.87 |
July | 25.29 | 26.90 |
August | 25.27 | 27.06 |
September | 25.32 | 26.87 |
October | 24.70 | 26.22 |
November | 24.24 | 24.76 |
December | 23.76 | 23.69 |
Annual Sum or Average | 24.44 | 24.91 |
Minimum of Months | 23.34 | 22.49 |
Maximum of Months | 25.32 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 22.49 |
February | 23.84 | 22.80 |
March | 23.86 | 23.17 |
April | 23.89 | 23.76 |
May | 23.89 | 25.23 |
June | 23.89 | 25.87 |
July | 23.89 | 26.90 |
August | 23.89 | 27.06 |
September | 23.89 | 26.87 |
October | 23.89 | 26.22 |
November | 23.88 | 24.76 |
December | 23.88 | 23.69 |
Annual Sum or Average | 23.88 | 24.91 |
Minimum of Months | 23.84 | 22.49 |
Maximum of Months | 23.89 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.41 | 22.49 |
February | 23.47 | 22.80 |
March | 23.55 | 23.17 |
April | 23.64 | 23.76 |
May | 23.81 | 25.23 |
June | 23.87 | 25.87 |
July | 23.91 | 26.90 |
August | 23.85 | 27.06 |
September | 23.77 | 26.87 |
October | 23.67 | 26.22 |
November | 23.54 | 24.76 |
December | 23.47 | 23.69 |
Annual Sum or Average | 23.66 | 24.91 |
Minimum of Months | 23.41 | 22.49 |
Maximum of Months | 23.91 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.87 | 22.49 |
February | 23.87 | 22.80 |
March | 23.88 | 23.17 |
April | 23.89 | 23.76 |
May | 23.89 | 25.23 |
June | 23.89 | 25.87 |
July | 23.89 | 26.90 |
August | 23.89 | 27.06 |
September | 23.89 | 26.87 |
October | 23.89 | 26.22 |
November | 23.89 | 24.76 |
December | 23.89 | 23.69 |
Annual Sum or Average | 23.89 | 24.91 |
Minimum of Months | 23.87 | 22.49 |
Maximum of Months | 23.89 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 30.44 | 22.49 |
February | 30.78 | 22.80 |
March | 31.20 | 23.17 |
April | 31.95 | 23.76 |
May | 32.80 | 25.23 |
June | 33.37 | 25.87 |
July | 33.66 | 26.90 |
August | 33.45 | 27.06 |
September | 33.02 | 26.87 |
October | 32.29 | 26.22 |
November | 31.51 | 24.76 |
December | 30.89 | 23.69 |
Annual Sum or Average | 32.12 | 24.91 |
Minimum of Months | 30.44 | 22.49 |
Maximum of Months | 33.66 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 22.49 |
February | 23.33 | 22.80 |
March | 23.33 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.33 | 23.69 |
Annual Sum or Average | 23.33 | 24.91 |
Minimum of Months | 23.33 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.24 | 22.49 |
February | 23.23 | 22.80 |
March | 23.24 | 23.17 |
April | 23.32 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.31 | 24.76 |
December | 23.30 | 23.69 |
Annual Sum or Average | 23.30 | 24.91 |
Minimum of Months | 23.23 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.75 | 26.22 |
November | 21.75 | 24.76 |
December | 21.75 | 23.69 |
Annual Sum or Average | 21.75 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.75 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 22.49 |
February | 22.38 | 22.80 |
March | 22.44 | 23.17 |
April | 22.49 | 23.76 |
May | 22.42 | 25.23 |
June | 22.37 | 25.87 |
July | 22.27 | 26.90 |
August | 22.23 | 27.06 |
September | 22.12 | 26.87 |
October | 22.11 | 26.22 |
November | 22.17 | 24.76 |
December | 22.26 | 23.69 |
Annual Sum or Average | 22.30 | 24.91 |
Minimum of Months | 22.11 | 22.49 |
Maximum of Months | 22.49 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 52.64 | 22.49 |
February | 52.61 | 22.80 |
March | 52.52 | 23.17 |
April | 52.41 | 23.76 |
May | 52.54 | 25.23 |
June | 52.54 | 25.87 |
July | 52.69 | 26.90 |
August | 52.79 | 27.06 |
September | 52.97 | 26.87 |
October | 53.06 | 26.22 |
November | 52.87 | 24.76 |
December | 52.81 | 23.69 |
Annual Sum or Average | 52.70 | 24.91 |
Minimum of Months | 52.41 | 22.49 |
Maximum of Months | 53.06 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 70.25 | 22.49 |
February | 70.34 | 22.80 |
March | 70.26 | 23.17 |
April | 70.13 | 23.76 |
May | 70.40 | 25.23 |
June | 70.30 | 25.87 |
July | 70.48 | 26.90 |
August | 70.64 | 27.06 |
September | 70.72 | 26.87 |
October | 70.88 | 26.22 |
November | 70.47 | 24.76 |
December | 70.43 | 23.69 |
Annual Sum or Average | 70.44 | 24.91 |
Minimum of Months | 70.13 | 22.49 |
Maximum of Months | 70.88 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 22.49 |
February | 23.88 | 22.80 |
March | 23.89 | 23.17 |
April | 23.89 | 23.76 |
May | 23.89 | 25.23 |
June | 23.89 | 25.87 |
July | 23.89 | 26.90 |
August | 23.89 | 27.06 |
September | 23.89 | 26.87 |
October | 23.89 | 26.22 |
November | 23.89 | 24.76 |
December | 23.89 | 23.69 |
Annual Sum or Average | 23.89 | 24.91 |
Minimum of Months | 23.88 | 22.49 |
Maximum of Months | 23.89 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 22.49 |
February | 23.89 | 22.80 |
March | 23.89 | 23.17 |
April | 23.89 | 23.76 |
May | 23.89 | 25.23 |
June | 23.89 | 25.87 |
July | 23.89 | 26.90 |
August | 23.89 | 27.06 |
September | 23.89 | 26.87 |
October | 23.89 | 26.22 |
November | 23.89 | 24.76 |
December | 23.89 | 23.69 |
Annual Sum or Average | 23.89 | 24.91 |
Minimum of Months | 23.89 | 22.49 |
Maximum of Months | 23.89 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.91 | 22.49 |
February | 24.92 | 22.80 |
March | 24.96 | 23.17 |
April | 25.15 | 23.76 |
May | 25.74 | 25.23 |
June | 25.89 | 25.87 |
July | 26.33 | 26.90 |
August | 26.51 | 27.06 |
September | 26.46 | 26.87 |
October | 26.44 | 26.22 |
November | 25.77 | 24.76 |
December | 25.37 | 23.69 |
Annual Sum or Average | 25.71 | 24.91 |
Minimum of Months | 24.91 | 22.49 |
Maximum of Months | 26.51 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.64 | 22.49 |
February | 24.61 | 22.80 |
March | 24.61 | 23.17 |
April | 24.65 | 23.76 |
May | 24.95 | 25.23 |
June | 25.04 | 25.87 |
July | 25.30 | 26.90 |
August | 25.40 | 27.06 |
September | 25.46 | 26.87 |
October | 25.45 | 26.22 |
November | 25.14 | 24.76 |
December | 24.91 | 23.69 |
Annual Sum or Average | 25.01 | 24.91 |
Minimum of Months | 24.61 | 22.49 |
Maximum of Months | 25.46 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.75 | 22.49 |
February | 25.09 | 22.80 |
March | 25.21 | 23.17 |
April | 25.26 | 23.76 |
May | 25.78 | 25.23 |
June | 26.02 | 25.87 |
July | 26.47 | 26.90 |
August | 26.57 | 27.06 |
September | 26.79 | 26.87 |
October | 26.26 | 26.22 |
November | 25.72 | 24.76 |
December | 25.23 | 23.69 |
Annual Sum or Average | 25.77 | 24.91 |
Minimum of Months | 24.75 | 22.49 |
Maximum of Months | 26.79 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 22.49 |
February | 23.90 | 22.80 |
March | 23.90 | 23.17 |
April | 23.89 | 23.76 |
May | 23.91 | 25.23 |
June | 23.93 | 25.87 |
July | 24.01 | 26.90 |
August | 24.04 | 27.06 |
September | 24.08 | 26.87 |
October | 24.02 | 26.22 |
November | 23.94 | 24.76 |
December | 23.91 | 23.69 |
Annual Sum or Average | 23.95 | 24.91 |
Minimum of Months | 23.89 | 22.49 |
Maximum of Months | 24.08 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.74 | 22.49 |
February | 24.18 | 22.80 |
March | 24.43 | 23.17 |
April | 24.64 | 23.76 |
May | 25.31 | 25.23 |
June | 25.62 | 25.87 |
July | 26.05 | 26.90 |
August | 26.03 | 27.06 |
September | 26.09 | 26.87 |
October | 25.39 | 26.22 |
November | 24.80 | 24.76 |
December | 24.24 | 23.69 |
Annual Sum or Average | 25.05 | 24.91 |
Minimum of Months | 23.74 | 22.49 |
Maximum of Months | 26.09 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 22.49 |
February | 23.29 | 22.80 |
March | 23.31 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.33 | 23.69 |
Annual Sum or Average | 23.33 | 24.91 |
Minimum of Months | 23.29 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.75 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 22.49 |
February | 23.33 | 22.80 |
March | 23.33 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.33 | 23.69 |
Annual Sum or Average | 23.33 | 24.91 |
Minimum of Months | 23.33 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 33.32 | 22.49 |
February | 33.37 | 22.80 |
March | 33.31 | 23.17 |
April | 33.23 | 23.76 |
May | 33.40 | 25.23 |
June | 33.39 | 25.87 |
July | 33.56 | 26.90 |
August | 33.66 | 27.06 |
September | 33.78 | 26.87 |
October | 33.82 | 26.22 |
November | 33.57 | 24.76 |
December | 33.48 | 23.69 |
Annual Sum or Average | 33.49 | 24.91 |
Minimum of Months | 33.23 | 22.49 |
Maximum of Months | 33.82 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | 22.49 |
February | 22.94 | 22.80 |
March | 22.88 | 23.17 |
April | 22.80 | 23.76 |
May | 22.94 | 25.23 |
June | 22.98 | 25.87 |
July | 23.16 | 26.90 |
August | 23.24 | 27.06 |
September | 23.40 | 26.87 |
October | 23.35 | 26.22 |
November | 23.12 | 24.76 |
December | 22.99 | 23.69 |
Annual Sum or Average | 23.05 | 24.91 |
Minimum of Months | 22.80 | 22.49 |
Maximum of Months | 23.40 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.98 | 22.49 |
February | 24.95 | 22.80 |
March | 24.96 | 23.17 |
April | 25.05 | 23.76 |
May | 25.43 | 25.23 |
June | 25.51 | 25.87 |
July | 25.81 | 26.90 |
August | 25.94 | 27.06 |
September | 25.96 | 26.87 |
October | 25.96 | 26.22 |
November | 25.54 | 24.76 |
December | 25.28 | 23.69 |
Annual Sum or Average | 25.45 | 24.91 |
Minimum of Months | 24.95 | 22.49 |
Maximum of Months | 25.96 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.69 | 22.49 |
February | 25.74 | 22.80 |
March | 25.84 | 23.17 |
April | 26.13 | 23.76 |
May | 26.91 | 25.23 |
June | 27.00 | 25.87 |
July | 27.52 | 26.90 |
August | 27.75 | 27.06 |
September | 27.59 | 26.87 |
October | 27.60 | 26.22 |
November | 26.67 | 24.76 |
December | 26.20 | 23.69 |
Annual Sum or Average | 26.73 | 24.91 |
Minimum of Months | 25.69 | 22.49 |
Maximum of Months | 27.75 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.82 | 22.49 |
February | 25.18 | 22.80 |
March | 25.32 | 23.17 |
April | 25.39 | 23.76 |
May | 25.96 | 25.23 |
June | 26.20 | 25.87 |
July | 26.67 | 26.90 |
August | 26.78 | 27.06 |
September | 26.99 | 26.87 |
October | 26.43 | 26.22 |
November | 25.85 | 24.76 |
December | 25.33 | 23.69 |
Annual Sum or Average | 25.91 | 24.91 |
Minimum of Months | 24.82 | 22.49 |
Maximum of Months | 26.99 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.89 | 22.49 |
February | 23.88 | 22.80 |
March | 23.89 | 23.17 |
April | 23.89 | 23.76 |
May | 23.89 | 25.23 |
June | 23.89 | 25.87 |
July | 23.89 | 26.90 |
August | 23.89 | 27.06 |
September | 23.89 | 26.87 |
October | 23.89 | 26.22 |
November | 23.89 | 24.76 |
December | 23.89 | 23.69 |
Annual Sum or Average | 23.89 | 24.91 |
Minimum of Months | 23.88 | 22.49 |
Maximum of Months | 23.89 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 22.49 |
February | 24.35 | 22.80 |
March | 24.63 | 23.17 |
April | 24.87 | 23.76 |
May | 25.61 | 25.23 |
June | 25.92 | 25.87 |
July | 26.38 | 26.90 |
August | 26.38 | 27.06 |
September | 26.43 | 26.87 |
October | 25.70 | 26.22 |
November | 25.04 | 24.76 |
December | 24.43 | 23.69 |
Annual Sum or Average | 25.31 | 24.91 |
Minimum of Months | 23.88 | 22.49 |
Maximum of Months | 26.43 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | 22.49 |
February | 23.26 | 22.80 |
March | 23.28 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.32 | 24.76 |
December | 23.31 | 23.69 |
Annual Sum or Average | 23.32 | 24.91 |
Minimum of Months | 23.26 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 22.49 |
February | 23.29 | 22.80 |
March | 23.30 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.32 | 23.69 |
Annual Sum or Average | 23.32 | 24.91 |
Minimum of Months | 23.29 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 22.49 |
February | 23.28 | 22.80 |
March | 23.30 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.32 | 24.76 |
December | 23.32 | 23.69 |
Annual Sum or Average | 23.32 | 24.91 |
Minimum of Months | 23.28 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.75 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.30 | 22.49 |
February | 23.29 | 22.80 |
March | 23.30 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.32 | 24.76 |
December | 23.32 | 23.69 |
Annual Sum or Average | 23.32 | 24.91 |
Minimum of Months | 23.29 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.16 | 22.49 |
February | 26.17 | 22.80 |
March | 26.14 | 23.17 |
April | 26.11 | 23.76 |
May | 26.25 | 25.23 |
June | 26.29 | 25.87 |
July | 26.44 | 26.90 |
August | 26.49 | 27.06 |
September | 26.59 | 26.87 |
October | 26.57 | 26.22 |
November | 26.42 | 24.76 |
December | 26.31 | 23.69 |
Annual Sum or Average | 26.33 | 24.91 |
Minimum of Months | 26.11 | 22.49 |
Maximum of Months | 26.59 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 22.49 |
February | 23.33 | 22.80 |
March | 23.33 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.33 | 23.69 |
Annual Sum or Average | 23.33 | 24.91 |
Minimum of Months | 23.33 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 22.49 |
February | 23.32 | 22.80 |
March | 23.32 | 23.17 |
April | 23.33 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.33 | 24.76 |
December | 23.33 | 23.69 |
Annual Sum or Average | 23.33 | 24.91 |
Minimum of Months | 23.32 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.11 | 22.49 |
February | 25.10 | 22.80 |
March | 25.13 | 23.17 |
April | 25.25 | 23.76 |
May | 25.70 | 25.23 |
June | 25.77 | 25.87 |
July | 26.11 | 26.90 |
August | 26.24 | 27.06 |
September | 26.24 | 26.87 |
October | 26.23 | 26.22 |
November | 25.74 | 24.76 |
December | 25.44 | 23.69 |
Annual Sum or Average | 25.67 | 24.91 |
Minimum of Months | 25.10 | 22.49 |
Maximum of Months | 26.24 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.80 | 22.49 |
February | 25.88 | 22.80 |
March | 26.01 | 23.17 |
April | 26.33 | 23.76 |
May | 27.19 | 25.23 |
June | 27.26 | 25.87 |
July | 27.82 | 26.90 |
August | 28.06 | 27.06 |
September | 27.86 | 26.87 |
October | 27.87 | 26.22 |
November | 26.85 | 24.76 |
December | 26.34 | 23.69 |
Annual Sum or Average | 26.95 | 24.91 |
Minimum of Months | 25.80 | 22.49 |
Maximum of Months | 28.06 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.87 | 22.49 |
February | 25.28 | 22.80 |
March | 25.45 | 23.17 |
April | 25.56 | 23.76 |
May | 26.23 | 25.23 |
June | 26.50 | 25.87 |
July | 27.01 | 26.90 |
August | 27.13 | 27.06 |
September | 27.29 | 26.87 |
October | 26.70 | 26.22 |
November | 26.00 | 24.76 |
December | 25.43 | 23.69 |
Annual Sum or Average | 26.13 | 24.91 |
Minimum of Months | 24.87 | 22.49 |
Maximum of Months | 27.29 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.81 | 22.49 |
February | 23.81 | 22.80 |
March | 23.81 | 23.17 |
April | 23.88 | 23.76 |
May | 23.93 | 25.23 |
June | 23.94 | 25.87 |
July | 24.00 | 26.90 |
August | 24.04 | 27.06 |
September | 24.03 | 26.87 |
October | 24.01 | 26.22 |
November | 23.91 | 24.76 |
December | 23.87 | 23.69 |
Annual Sum or Average | 23.92 | 24.91 |
Minimum of Months | 23.81 | 22.49 |
Maximum of Months | 24.04 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.88 | 22.49 |
February | 24.39 | 22.80 |
March | 24.70 | 23.17 |
April | 24.97 | 23.76 |
May | 25.80 | 25.23 |
June | 26.13 | 25.87 |
July | 26.63 | 26.90 |
August | 26.64 | 27.06 |
September | 26.65 | 26.87 |
October | 25.88 | 26.22 |
November | 25.13 | 24.76 |
December | 24.47 | 23.69 |
Annual Sum or Average | 25.44 | 24.91 |
Minimum of Months | 23.88 | 22.49 |
Maximum of Months | 26.65 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 22.49 |
February | 23.18 | 22.80 |
March | 23.20 | 23.17 |
April | 23.32 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.30 | 24.76 |
December | 23.29 | 23.69 |
Annual Sum or Average | 23.29 | 24.91 |
Minimum of Months | 23.18 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 22.49 |
February | 23.16 | 22.80 |
March | 23.18 | 23.17 |
April | 23.31 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.29 | 24.76 |
December | 23.28 | 23.69 |
Annual Sum or Average | 23.28 | 24.91 |
Minimum of Months | 23.16 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 22.49 |
February | 21.75 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.75 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 22.49 |
February | 23.19 | 22.80 |
March | 23.21 | 23.17 |
April | 23.31 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.29 | 24.76 |
December | 23.28 | 23.69 |
Annual Sum or Average | 23.29 | 24.91 |
Minimum of Months | 23.19 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.25 | 22.49 |
February | 23.24 | 22.80 |
March | 23.24 | 23.17 |
April | 23.32 | 23.76 |
May | 23.33 | 25.23 |
June | 23.33 | 25.87 |
July | 23.33 | 26.90 |
August | 23.33 | 27.06 |
September | 23.33 | 26.87 |
October | 23.33 | 26.22 |
November | 23.31 | 24.76 |
December | 23.30 | 23.69 |
Annual Sum or Average | 23.31 | 24.91 |
Minimum of Months | 23.24 | 22.49 |
Maximum of Months | 23.33 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.56 | 22.49 |
February | 24.60 | 22.80 |
March | 24.61 | 23.17 |
April | 24.64 | 23.76 |
May | 24.87 | 25.23 |
June | 24.96 | 25.87 |
July | 25.16 | 26.90 |
August | 25.21 | 27.06 |
September | 25.27 | 26.87 |
October | 25.16 | 26.22 |
November | 24.95 | 24.76 |
December | 24.76 | 23.69 |
Annual Sum or Average | 24.90 | 24.91 |
Minimum of Months | 24.56 | 22.49 |
Maximum of Months | 25.27 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.75 | 23.17 |
April | 21.75 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.75 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 22.49 |
February | 21.76 | 22.80 |
March | 21.76 | 23.17 |
April | 21.76 | 23.76 |
May | 21.76 | 25.23 |
June | 21.76 | 25.87 |
July | 21.76 | 26.90 |
August | 21.76 | 27.06 |
September | 21.76 | 26.87 |
October | 21.76 | 26.22 |
November | 21.76 | 24.76 |
December | 21.76 | 23.69 |
Annual Sum or Average | 21.76 | 24.91 |
Minimum of Months | 21.76 | 22.49 |
Maximum of Months | 21.76 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.91 | 22.49 |
February | 24.95 | 22.80 |
March | 25.02 | 23.17 |
April | 25.19 | 23.76 |
May | 25.71 | 25.23 |
June | 25.81 | 25.87 |
July | 26.18 | 26.90 |
August | 26.31 | 27.06 |
September | 26.26 | 26.87 |
October | 26.19 | 26.22 |
November | 25.62 | 24.76 |
December | 25.27 | 23.69 |
Annual Sum or Average | 25.62 | 24.91 |
Minimum of Months | 24.91 | 22.49 |
Maximum of Months | 26.31 | 27.06 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:42
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.66 | 22.49 |
February | 25.80 | 22.80 |
March | 25.97 | 23.17 |
April | 26.32 | 23.76 |
May | 27.28 | 25.23 |
June | 27.37 | 25.87 |
July | 27.97 | 26.90 |
August | 28.21 | 27.06 |
September | 27.96 | 26.87 |
October | 27.92 | 26.22 |
November | 26.80 | 24.76 |
December | 26.25 | 23.69 |
Annual Sum or Average | 26.97 | 24.91 |
Minimum of Months | 25.66 | 22.49 |
Maximum of Months | 28.21 | 27.06 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:42
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.162056E+12 | 97032.568 | 01-JAN-08:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 26701.138 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.150306E+12 | 101135.256 | 18-FEB-08:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 30803.825 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.164841E+12 | 96080.171 | 04-MAR-08:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 25748.740 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.159933E+12 | 94920.466 | 08-APR-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 24589.036 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.173350E+12 | 99840.365 | 13-MAY-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 29508.935 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.170762E+12 | 100292.105 | 30-JUN-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 29960.675 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.182309E+12 | 102273.157 | 15-JUL-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 31941.727 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.182723E+12 | 103055.692 | 19-AUG-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 32724.261 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.178605E+12 | 104234.093 | 03-SEP-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 33902.662 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.180857E+12 | 103197.468 | 07-OCT-07:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 32866.038 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.168525E+12 | 103620.455 | 22-NOV-08:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 33289.025 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.168667E+12 | 102332.228 | 01-DEC-08:00 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 32000.797 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.204293E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.150306E+12 | 94920.466 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 24589.036 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.182723E+12 | 104234.093 | 17938.723 | 43276.576 | 9108.019 | 0.000 | 33902.662 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:42
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.776708E+11 | 72950.254 | 16-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 32854.226 | 32854.226 | 32854.226 | 0.000 |
February | 0.700560E+11 | 72932.136 | 01-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 32836.108 | 32836.108 | 32836.108 | 0.000 |
March | 0.772192E+11 | 72818.171 | 02-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 32722.143 | 32722.143 | 32722.143 | 0.000 |
April | 0.742593E+11 | 72555.664 | 05-APR-08:15 | 0.000 | 40096.028 | 0.000 | 32459.636 | 32459.636 | 32459.636 | 0.000 |
May | 0.762258E+11 | 72252.152 | 07-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 32156.124 | 32156.124 | 32156.124 | 0.000 |
June | 0.733960E+11 | 72010.498 | 01-JUN-08:45 | 0.000 | 40096.028 | 0.000 | 31914.470 | 31914.470 | 31914.470 | 0.000 |
July | 0.756838E+11 | 71917.231 | 02-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 31821.203 | 31821.203 | 31821.203 | 0.000 |
August | 0.757923E+11 | 72000.718 | 27-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 31904.690 | 31904.690 | 31904.690 | 0.000 |
September | 0.736796E+11 | 72245.647 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 32149.619 | 32149.619 | 32149.619 | 0.000 |
October | 0.766315E+11 | 72537.577 | 30-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 32441.549 | 32441.549 | 32441.549 | 0.000 |
November | 0.746469E+11 | 72787.163 | 29-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 32691.135 | 32691.135 | 32691.135 | 0.000 |
December | 0.775158E+11 | 72917.102 | 31-DEC-09:15 | 0.000 | 40096.028 | 0.000 | 32821.074 | 32821.074 | 32821.074 | 0.000 |
Annual Sum or Average | 0.902777E+12 | 0.000 | ||||||||
Minimum of Months | 0.700560E+11 | 71917.231 | 0.000 | 40096.028 | 0.000 | 31821.203 | 31821.203 | 31821.203 | 0.000 | |
Maximum of Months | 0.776708E+11 | 72950.254 | 0.000 | 40096.028 | 0.000 | 32854.226 | 32854.226 | 32854.226 | 0.000 |