Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2018-10-19 10:15:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2887.76 | 719.50 | 775.22 |
Net Site Energy | 2887.76 | 719.50 | 775.22 |
Total Source Energy | 7203.53 | 1794.79 | 1933.79 |
Net Source Energy | 7203.53 | 1794.79 | 1933.79 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 11.45 | 6.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 587.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 281.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 504.13 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1955.45 | 932.31 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 11.45 | 6.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 587.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 281.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 504.13 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 236.34 | 137.13 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 524.94 | 250.28 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 219.36 | 127.27 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 487.21 | 232.29 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1955.45 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1955.45 | 100.00 |
Total On-Site and Utility Electric Sources | 1955.45 | 100.00 |
Total Electricity End Uses | 1955.45 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 191.25 |
Time Setpoint Not Met During Occupied Cooling | 5428.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6734.75 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 96.82 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 87.38 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7935.19 | 5504.79 | 2430.40 | 0.69 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19790.13 | 13379.78 | 6410.36 | 0.68 | 3.80 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9034.48 | 6108.06 | 2926.42 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15609.46 | 10985.24 | 4624.22 | 0.70 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7669.0 | 3.34 | 11.41 | 12.10 | 11.52 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19170.7 | 3.29 | 11.23 | 11.91 | 11.42 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8751.7 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15066.0 | 3.32 | 11.34 | 12.03 | 11.42 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.13 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 17771.40 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.05 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.13 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2128.50 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2379.23 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.05 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.13 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2128.50 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2379.23 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 750.51 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.05 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.13 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2128.50 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 754.29 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2379.23 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 3002.06 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 819.06 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 770.25 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 3001.84 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 750.46 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 321.05 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3090.28 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 12952.86 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6936.16 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5221.12 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.34 | 383.69 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.80 | 882.35 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 407.52 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.70 | 783.59 | 1120.11 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 8048.18 | 9657.82 | 0.664 | 0.797 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90 | 0.01651 |
RESTROOMFLR1 | 472.43 | 566.92 | 0.039 | 0.047 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:45:00 | 32.95 | 0.01651 |
MEETINGROOMFLR1 | 3671.82 | 4406.18 | 0.303 | 0.364 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90 | 0.01651 |
GUESTROOM101 | 628.16 | 753.79 | 0.072 | 0.086 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 33.54 | 0.01651 |
GUESTROOM102 | 523.38 | 628.06 | 0.060 | 0.072 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 33.54 | 0.01651 |
GUESTROOM103 | 1143.91 | 1372.70 | 0.131 | 0.157 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 31.71 | 0.01651 |
GUESTROOM104 | 1297.64 | 1557.16 | 0.149 | 0.179 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.78 | 0.01651 |
GUESTROOM105 | 1605.66 | 1926.79 | 0.184 | 0.221 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
EMPLOYEELOUNGEFLR1 | 5368.26 | 6441.91 | 0.443 | 0.532 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 33.90 | 0.01651 |
EXERCISECENTERFLR1 | 1224.33 | 1469.20 | 0.101 | 0.121 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
FRONTOFFICEFLR1 | 3462.09 | 4154.51 | 0.285 | 0.343 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM201 | 824.24 | 989.09 | 0.095 | 0.113 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:15:00 | 33.60 | 0.01651 |
GUESTROOM202_205 | 4165.43 | 4998.52 | 0.478 | 0.573 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
GUESTROOM206_208 | 3375.65 | 4050.78 | 0.387 | 0.464 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:15:00 | 33.78 | 0.01651 |
GUESTROOM209_212 | 3965.98 | 4759.17 | 0.455 | 0.546 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
GUESTROOM213 | 1134.03 | 1360.83 | 0.130 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 33.11 | 0.01651 |
GUESTROOM214 | 1335.23 | 1602.28 | 0.153 | 0.184 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM215_218 | 9441.47 | 11329.76 | 1.082 | 1.299 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM219 | 5353.57 | 6424.29 | 0.614 | 0.736 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM220_223 | 4589.45 | 5507.34 | 0.526 | 0.631 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 33.90 | 0.01651 |
GUESTROOM224 | 1323.41 | 1588.10 | 0.152 | 0.182 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM301 | 632.83 | 759.40 | 0.073 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70 | 0.01651 |
GUESTROOM302_305 | 1562.56 | 1875.07 | 0.179 | 0.215 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 33.54 | 0.01651 |
GUESTROOM306_308 | 1379.13 | 1654.96 | 0.158 | 0.190 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
GUESTROOM309_312 | 3888.71 | 4666.45 | 0.446 | 0.535 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:45:00 | 33.54 | 0.01651 |
GUESTROOM313 | 623.84 | 748.60 | 0.072 | 0.086 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
GUESTROOM314 | 1244.21 | 1493.05 | 0.143 | 0.171 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM315_318 | 4940.01 | 5928.01 | 0.566 | 0.680 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM319 | 1094.26 | 1313.11 | 0.125 | 0.151 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM320_323 | 4345.90 | 5215.08 | 0.498 | 0.598 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM324 | 747.58 | 897.10 | 0.086 | 0.103 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM401 | 1424.43 | 1709.31 | 0.163 | 0.196 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70 | 0.01651 |
GUESTROOM402_405 | 2166.33 | 2599.60 | 0.248 | 0.298 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM406_408 | 1872.56 | 2247.07 | 0.215 | 0.258 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM409_412 | 4796.53 | 5755.83 | 0.550 | 0.660 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM413 | 840.91 | 1009.09 | 0.096 | 0.116 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
GUESTROOM414 | 975.75 | 1170.90 | 0.112 | 0.134 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
GUESTROOM415_418 | 5392.74 | 6471.28 | 0.618 | 0.742 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 33.90 | 0.01651 |
GUESTROOM419 | 1483.30 | 1779.96 | 0.170 | 0.204 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90 | 0.01651 |
GUESTROOM420_423 | 5363.00 | 6435.60 | 0.615 | 0.738 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 33.90 | 0.01651 |
GUESTROOM424 | 1526.26 | 1831.52 | 0.175 | 0.210 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 33.90 | 0.01651 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
CORRIDORFLR1 | 18553.30 | 22263.96 | 1.531 | 1.837 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 32.00 | 0.01651 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
CORRIDORFLR2 | 2698.42 | 3238.10 | 0.222 | 0.267 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
CORRIDORFLR3 | 1291.61 | 1549.93 | 0.106 | 0.128 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79 | 0.01651 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 | |
CORRIDORFLR4 | 1968.93 | 2362.72 | 0.162 | 0.195 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 33.66 | 0.01651 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 0.01651 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1213.42 | 1456.11 | 0.034 | 0.236 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:15:00 | 4.60 | 0.00526 |
RESTROOMFLR1 | 34.11 | 40.94 | 0.001 | 0.001 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | 4.60 | 0.00526 |
MEETINGROOMFLR1 | 386.73 | 464.08 | 0.011 | 0.126 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 4.60 | 0.00526 |
GUESTROOM101 | 157.06 | 188.47 | 0.004 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 4.60 | 0.00526 |
GUESTROOM102 | 196.52 | 235.82 | 0.006 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 4.60 | 0.00526 |
GUESTROOM103 | 318.37 | 382.05 | 0.009 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 4.60 | 0.00526 |
GUESTROOM104 | 300.06 | 360.07 | 0.008 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 4.60 | 0.00526 |
GUESTROOM105 | 192.95 | 231.54 | 0.005 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 4.60 | 0.00526 |
EMPLOYEELOUNGEFLR1 | 165.18 | 198.21 | 0.005 | 0.051 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60 | 0.00526 |
EXERCISECENTERFLR1 | 99.69 | 119.63 | 0.003 | 0.043 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 4.60 | 0.00526 |
FRONTOFFICEFLR1 | 689.24 | 827.09 | 0.019 | 0.056 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | 4.60 | 0.00526 |
GUESTROOM201 | 255.77 | 306.92 | 0.007 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | 4.60 | 0.00526 |
GUESTROOM202_205 | 597.06 | 716.47 | 0.017 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | 4.60 | 0.00526 |
GUESTROOM206_208 | 466.04 | 559.25 | 0.013 | 0.043 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | 4.60 | 0.00526 |
GUESTROOM209_212 | 526.20 | 631.44 | 0.015 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
GUESTROOM213 | 279.77 | 335.72 | 0.008 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 11:15:00 | 4.60 | 0.00526 |
GUESTROOM214 | 244.98 | 293.98 | 0.007 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | 4.60 | 0.00526 |
GUESTROOM215_218 | 489.97 | 587.96 | 0.014 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
GUESTROOM219 | 91.30 | 109.56 | 0.003 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | 4.60 | 0.00526 |
GUESTROOM220_223 | 482.19 | 578.63 | 0.014 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | 4.60 | 0.00526 |
GUESTROOM224 | 215.59 | 258.71 | 0.006 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | 4.60 | 0.00526 |
GUESTROOM301 | 277.05 | 332.46 | 0.008 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:45:00 | 4.60 | 0.00526 |
GUESTROOM302_305 | 662.42 | 794.90 | 0.019 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | 4.60 | 0.00526 |
GUESTROOM306_308 | 576.15 | 691.38 | 0.016 | 0.043 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 14:30:00 | 4.60 | 0.00526 |
GUESTROOM309_312 | 653.00 | 783.59 | 0.018 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:15:00 | 4.60 | 0.00526 |
GUESTROOM313 | 313.05 | 375.66 | 0.009 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 20:30:00 | 4.60 | 0.00526 |
GUESTROOM314 | 273.34 | 328.01 | 0.008 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 15:45:00 | 4.60 | 0.00526 |
GUESTROOM315_318 | 625.53 | 750.64 | 0.018 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | 4.60 | 0.00526 |
GUESTROOM319 | 156.83 | 188.20 | 0.004 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 4.60 | 0.00526 |
GUESTROOM320_323 | 600.00 | 720.00 | 0.017 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:45:00 | 4.60 | 0.00526 |
GUESTROOM324 | 252.57 | 303.09 | 0.007 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | 4.60 | 0.00526 |
GUESTROOM401 | 401.12 | 481.34 | 0.011 | 0.014 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:45:00 | 4.60 | 0.00526 |
GUESTROOM402_405 | 1098.48 | 1318.17 | 0.031 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | 4.60 | 0.00526 |
GUESTROOM406_408 | 943.61 | 1132.33 | 0.027 | 0.043 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | 4.60 | 0.00526 |
GUESTROOM409_412 | 1100.94 | 1321.13 | 0.031 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 20:15:00 | 4.60 | 0.00526 |
GUESTROOM413 | 455.09 | 546.11 | 0.013 | 0.015 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60 | 0.00526 |
GUESTROOM414 | 414.44 | 497.32 | 0.012 | 0.014 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 21:00:00 | 4.60 | 0.00526 |
GUESTROOM415_418 | 1077.01 | 1292.41 | 0.030 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | 4.60 | 0.00526 |
GUESTROOM419 | 304.64 | 365.56 | 0.009 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 18:00:00 | 4.60 | 0.00526 |
GUESTROOM420_423 | 1048.04 | 1257.65 | 0.030 | 0.054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | 4.60 | 0.00526 |
GUESTROOM424 | 396.48 | 475.78 | 0.011 | 0.013 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 4.60 | 0.00526 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
CORRIDORFLR1 | 14033.10 | 16839.72 | 0.396 | 0.475 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60 | 0.00526 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
CORRIDORFLR2 | 79.63 | 95.56 | 0.002 | 0.038 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:30:00 | 4.60 | 0.00526 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
CORRIDORFLR3 | 201.97 | 242.36 | 0.006 | 0.038 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | 4.60 | 0.00526 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 | |
CORRIDORFLR4 | 746.42 | 895.70 | 0.021 | 0.038 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 23:45:00 | 4.60 | 0.00526 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00526 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.34 | 0.34 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.80 | 0.80 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.36 | 0.36 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.70 | 0.70 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialEnthalpy | 0.24 | 0.80 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 5805.75 | 6695.75 | 4180.25 |
RESTROOMFLR1 | 2680.75 | 4850.50 | 898.00 |
MEETINGROOMFLR1 | 3030.25 | 2801.50 | 1734.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 768.00 | 8469.00 | 768.00 |
GUESTROOM104 | 440.25 | 8108.50 | 424.25 |
GUESTROOM105 | 273.00 | 7409.00 | 86.00 |
EMPLOYEELOUNGEFLR1 | 3287.50 | 2098.25 | 468.25 |
EXERCISECENTERFLR1 | 3932.50 | 869.25 | 236.50 |
FRONTOFFICEFLR1 | 4823.50 | 3565.25 | 1497.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 565.25 | 7716.50 | 336.75 |
GUESTROOM206_208 | 478.50 | 7605.00 | 203.75 |
GUESTROOM209_212 | 521.00 | 7878.75 | 405.50 |
GUESTROOM213 | 566.50 | 8186.00 | 560.50 |
GUESTROOM214 | 281.00 | 7604.00 | 173.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5913.00 | 3440.00 | 1418.25 |
GUESTROOM220_223 | 564.00 | 7538.25 | 343.25 |
GUESTROOM224 | 224.50 | 7470.25 | 113.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 758.00 | 8315.00 | 747.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 309.75 | 7659.00 | 213.00 |
GUESTROOM315_318 | 679.50 | 7275.50 | 206.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 635.00 | 7939.75 | 562.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 1515.25 | 7350.50 | 522.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 1318.75 | 7331.25 | 302.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1483.25 | 6867.75 | 146.75 |
GUESTROOM419 | 1148.50 | 6948.25 | 53.00 |
GUESTROOM420_423 | 1460.75 | 6931.00 | 179.75 |
GUESTROOM424 | 1158.00 | 7070.25 | 105.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7760.25 | 8756.50 | 6734.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 1.50 | 1657.25 | 1.50 | 1657.25 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 74.50 | 0.00 | 74.50 |
GUESTROOM104 | 0.00 | 80.25 | 0.00 | 80.25 |
GUESTROOM105 | 0.00 | 88.50 | 0.00 | 88.50 |
EMPLOYEELOUNGEFLR1 | 250.25 | 1160.00 | 190.25 | 606.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 64.75 | 0.00 | 64.75 |
GUESTROOM206_208 | 0.00 | 69.50 | 0.00 | 69.50 |
GUESTROOM209_212 | 0.00 | 64.00 | 0.00 | 64.00 |
GUESTROOM213 | 0.00 | 64.00 | 0.00 | 64.00 |
GUESTROOM214 | 0.00 | 69.50 | 0.00 | 69.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 4730.25 | 0.00 | 4730.25 |
GUESTROOM220_223 | 0.00 | 68.75 | 0.00 | 68.75 |
GUESTROOM224 | 0.00 | 69.50 | 0.00 | 69.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 63.75 | 0.00 | 63.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 69.00 | 0.00 | 69.00 |
GUESTROOM315_318 | 0.00 | 69.00 | 0.00 | 69.00 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 67.00 | 0.00 | 67.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.75 | 67.75 | 0.75 | 67.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 66.25 | 0.00 | 66.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 72.50 | 0.00 | 72.50 |
GUESTROOM419 | 0.00 | 75.50 | 0.00 | 75.50 |
GUESTROOM420_423 | 0.00 | 70.75 | 0.00 | 70.75 |
GUESTROOM424 | 0.00 | 73.50 | 0.00 | 73.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 9.25 | 6429.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 1429.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 7.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 833.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 254.00 | 7314.75 | 191.25 | 5428.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:34
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.342544 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.796949 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.699566 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.13 |
CORRIDORFLR1 PTAC HEATING COIL | 17771.40 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 750.51 |
102 PTAC HEATING COIL | 750.51 |
103 PTAC HEATING COIL | 750.51 |
104 PTAC HEATING COIL | 750.46 |
105 PTAC HEATING COIL | 750.46 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 321.05 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.13 |
CORRIDORFLR2 PTAC HEATING COIL | 2128.50 |
201 PTAC HEATING COIL | 750.51 |
202_205 PTAC HEATING COIL | 3002.06 |
206_208 PTAC HEATING COIL | 2379.23 |
209_212 PTAC HEATING COIL | 3002.06 |
213 PTAC HEATING COIL | 750.51 |
214 PTAC HEATING COIL | 750.46 |
215_218 PTAC HEATING COIL | 3001.84 |
219 PTAC HEATING COIL | 750.46 |
220_223 PTAC HEATING COIL | 3001.84 |
224 PTAC HEATING COIL | 750.46 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 321.05 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.13 |
CORRIDORFLR3 PTAC HEATING COIL | 2128.50 |
301 PTAC HEATING COIL | 750.51 |
302_305 PTAC HEATING COIL | 3002.06 |
306_308 PTAC HEATING COIL | 2379.23 |
309_312 PTAC HEATING COIL | 3002.06 |
313 PTAC HEATING COIL | 750.51 |
314 PTAC HEATING COIL | 750.46 |
315_318 PTAC HEATING COIL | 3001.84 |
319 PTAC HEATING COIL | 750.46 |
320_323 PTAC HEATING COIL | 3001.84 |
324 PTAC HEATING COIL | 750.46 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 321.05 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.13 |
CORRIDORFLR4 PTAC HEATING COIL | 2128.50 |
401 PTAC HEATING COIL | 754.29 |
402_405 PTAC HEATING COIL | 3002.06 |
406_408 PTAC HEATING COIL | 2379.23 |
409_412 PTAC HEATING COIL | 3002.06 |
413 PTAC HEATING COIL | 819.06 |
414 PTAC HEATING COIL | 770.25 |
415_418 PTAC HEATING COIL | 3001.84 |
419 PTAC HEATING COIL | 750.46 |
420_423 PTAC HEATING COIL | 3001.84 |
424 PTAC HEATING COIL | 750.46 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 321.05 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.693719 | 0.342544 | 7935.19 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 0.796949 | 19790.13 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.363819 | 9034.48 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.703755 | 0.699566 | 15609.46 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.796949 |
RESTROOMFLR1 DIRECT AIR | 0.046735 |
MEETINGROOMFLR1 DIRECT AIR | 0.363819 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.531650 |
EXERCISECENTERFLR1 DIRECT AIR | 0.121181 |
FRONTOFFICEFLR1 DIRECT AIR | 0.342544 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.342544 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.796949 |
SAC_MEETINGROOM MAIN BRANCH | 0.363819 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.699566 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.342544 |
SAC_FRONTLOUNGE | 0.796949 |
SAC_MEETINGROOM | 0.363819 |
SAC_EXC_EMPLGE_RESTRM | 0.699566 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.342544 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.796949 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.363819 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.699566 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.342544 | 0.342544 | 0.342544 | 0.342544 | 3090.28 | 7935.19 | 1.00 |
SAC_FRONTLOUNGE | 0.796949 | 0.796949 | 0.796949 | 0.796949 | 12952.86 | 19790.13 | 1.00 |
SAC_MEETINGROOM | 0.363819 | 0.363819 | 0.363819 | 0.363819 | 6936.16 | 9034.48 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.699566 | 0.699566 | 0.699566 | 0.699566 | 5221.12 | 15609.46 | 0.173224 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3090.28 |
SAC_FRONTLOUNGE HEATING COIL | 12952.86 |
SAC_MEETINGROOM HEATING COIL | 6936.16 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5221.12 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.363819 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 13.57 |
February | 22.19 | 15.49 |
March | 22.40 | 17.07 |
April | 23.89 | 21.23 |
May | 25.32 | 26.90 |
June | 25.56 | 27.61 |
July | 25.62 | 27.94 |
August | 25.61 | 27.43 |
September | 25.28 | 26.23 |
October | 24.86 | 24.23 |
November | 23.32 | 18.91 |
December | 22.19 | 15.68 |
Annual Sum or Average | 23.99 | 21.89 |
Minimum of Months | 21.59 | 13.57 |
Maximum of Months | 25.62 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.96 | 13.57 |
February | 24.29 | 15.49 |
March | 24.55 | 17.07 |
April | 25.47 | 21.23 |
May | 27.00 | 26.90 |
June | 27.30 | 27.61 |
July | 27.49 | 27.94 |
August | 27.31 | 27.43 |
September | 26.95 | 26.23 |
October | 26.36 | 24.23 |
November | 24.98 | 18.91 |
December | 24.36 | 15.68 |
Annual Sum or Average | 25.84 | 21.89 |
Minimum of Months | 23.96 | 13.57 |
Maximum of Months | 27.49 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | 13.57 |
February | 21.32 | 15.49 |
March | 21.76 | 17.07 |
April | 23.33 | 21.23 |
May | 24.86 | 26.90 |
June | 25.11 | 27.61 |
July | 25.16 | 27.94 |
August | 25.08 | 27.43 |
September | 24.68 | 26.23 |
October | 24.12 | 24.23 |
November | 22.41 | 18.91 |
December | 21.28 | 15.68 |
Annual Sum or Average | 23.32 | 21.89 |
Minimum of Months | 20.64 | 13.57 |
Maximum of Months | 25.16 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.18 | 13.57 |
February | 22.51 | 15.49 |
March | 22.76 | 17.07 |
April | 23.47 | 21.23 |
May | 23.89 | 26.90 |
June | 23.89 | 27.61 |
July | 23.89 | 27.94 |
August | 23.89 | 27.43 |
September | 23.89 | 26.23 |
October | 23.71 | 24.23 |
November | 23.06 | 18.91 |
December | 22.53 | 15.68 |
Annual Sum or Average | 23.31 | 21.89 |
Minimum of Months | 22.18 | 13.57 |
Maximum of Months | 23.89 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.56 | 13.57 |
February | 22.80 | 15.49 |
March | 23.02 | 17.07 |
April | 23.47 | 21.23 |
May | 23.85 | 26.90 |
June | 23.93 | 27.61 |
July | 23.95 | 27.94 |
August | 23.88 | 27.43 |
September | 23.77 | 26.23 |
October | 23.58 | 24.23 |
November | 23.12 | 18.91 |
December | 22.78 | 15.68 |
Annual Sum or Average | 23.40 | 21.89 |
Minimum of Months | 22.56 | 13.57 |
Maximum of Months | 23.95 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.79 | 13.57 |
February | 23.06 | 15.49 |
March | 23.26 | 17.07 |
April | 23.77 | 21.23 |
May | 23.89 | 26.90 |
June | 23.89 | 27.61 |
July | 23.89 | 27.94 |
August | 23.89 | 27.43 |
September | 23.89 | 26.23 |
October | 23.84 | 24.23 |
November | 23.56 | 18.91 |
December | 23.07 | 15.68 |
Annual Sum or Average | 23.57 | 21.89 |
Minimum of Months | 22.79 | 13.57 |
Maximum of Months | 23.89 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.43 | 13.57 |
February | 25.69 | 15.49 |
March | 26.28 | 17.07 |
April | 28.80 | 21.23 |
May | 31.24 | 26.90 |
June | 32.89 | 27.61 |
July | 33.70 | 27.94 |
August | 33.36 | 27.43 |
September | 32.16 | 26.23 |
October | 30.18 | 24.23 |
November | 27.74 | 18.91 |
December | 25.92 | 15.68 |
Annual Sum or Average | 29.47 | 21.89 |
Minimum of Months | 25.43 | 13.57 |
Maximum of Months | 33.70 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 13.57 |
February | 22.09 | 15.49 |
March | 22.42 | 17.07 |
April | 23.20 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.28 | 24.23 |
November | 22.87 | 18.91 |
December | 22.11 | 15.68 |
Annual Sum or Average | 22.86 | 21.89 |
Minimum of Months | 21.65 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 13.57 |
February | 21.82 | 15.49 |
March | 22.15 | 17.07 |
April | 22.99 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.18 | 24.23 |
November | 22.58 | 18.91 |
December | 21.83 | 15.68 |
Annual Sum or Average | 22.72 | 21.89 |
Minimum of Months | 21.36 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | 13.57 |
February | 21.53 | 15.49 |
March | 21.58 | 17.07 |
April | 21.73 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.74 | 24.23 |
November | 21.69 | 18.91 |
December | 21.53 | 15.68 |
Annual Sum or Average | 21.67 | 21.89 |
Minimum of Months | 21.45 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.57 |
February | 21.69 | 15.49 |
March | 21.67 | 17.07 |
April | 21.74 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.75 | 18.91 |
December | 21.69 | 15.68 |
Annual Sum or Average | 21.73 | 21.89 |
Minimum of Months | 21.67 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.57 |
February | 21.74 | 15.49 |
March | 21.73 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.74 | 15.68 |
Annual Sum or Average | 21.75 | 21.89 |
Minimum of Months | 21.73 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 13.57 |
February | 22.52 | 15.49 |
March | 22.62 | 17.07 |
April | 22.62 | 21.23 |
May | 22.32 | 26.90 |
June | 22.24 | 27.61 |
July | 22.19 | 27.94 |
August | 22.19 | 27.43 |
September | 22.23 | 26.23 |
October | 22.24 | 24.23 |
November | 22.44 | 18.91 |
December | 22.41 | 15.68 |
Annual Sum or Average | 22.36 | 21.89 |
Minimum of Months | 22.19 | 13.57 |
Maximum of Months | 22.62 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 51.74 | 13.57 |
February | 51.90 | 15.49 |
March | 51.84 | 17.07 |
April | 52.32 | 21.23 |
May | 52.84 | 26.90 |
June | 53.01 | 27.61 |
July | 53.07 | 27.94 |
August | 53.06 | 27.43 |
September | 52.97 | 26.23 |
October | 52.91 | 24.23 |
November | 52.42 | 18.91 |
December | 51.99 | 15.68 |
Annual Sum or Average | 52.51 | 21.89 |
Minimum of Months | 51.74 | 13.57 |
Maximum of Months | 53.07 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.20 | 13.57 |
February | 69.47 | 15.49 |
March | 69.44 | 17.07 |
April | 70.14 | 21.23 |
May | 70.83 | 26.90 |
June | 71.08 | 27.61 |
July | 71.18 | 27.94 |
August | 71.04 | 27.43 |
September | 70.88 | 26.23 |
October | 70.59 | 24.23 |
November | 70.04 | 18.91 |
December | 69.51 | 15.68 |
Annual Sum or Average | 70.29 | 21.89 |
Minimum of Months | 69.20 | 13.57 |
Maximum of Months | 71.18 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.46 | 13.57 |
February | 23.61 | 15.49 |
March | 23.67 | 17.07 |
April | 23.86 | 21.23 |
May | 23.89 | 26.90 |
June | 23.89 | 27.61 |
July | 23.89 | 27.94 |
August | 23.89 | 27.43 |
September | 23.89 | 26.23 |
October | 23.87 | 24.23 |
November | 23.78 | 18.91 |
December | 23.58 | 15.68 |
Annual Sum or Average | 23.77 | 21.89 |
Minimum of Months | 23.46 | 13.57 |
Maximum of Months | 23.89 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.32 | 13.57 |
February | 23.53 | 15.49 |
March | 23.60 | 17.07 |
April | 23.86 | 21.23 |
May | 23.89 | 26.90 |
June | 23.89 | 27.61 |
July | 23.89 | 27.94 |
August | 23.89 | 27.43 |
September | 23.89 | 26.23 |
October | 23.88 | 24.23 |
November | 23.78 | 18.91 |
December | 23.51 | 15.68 |
Annual Sum or Average | 23.74 | 21.89 |
Minimum of Months | 23.32 | 13.57 |
Maximum of Months | 23.89 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 13.57 |
February | 22.29 | 15.49 |
March | 22.60 | 17.07 |
April | 24.25 | 21.23 |
May | 26.00 | 26.90 |
June | 26.29 | 27.61 |
July | 26.44 | 27.94 |
August | 26.29 | 27.43 |
September | 25.91 | 26.23 |
October | 25.37 | 24.23 |
November | 23.67 | 18.91 |
December | 22.28 | 15.68 |
Annual Sum or Average | 24.43 | 21.89 |
Minimum of Months | 21.62 | 13.57 |
Maximum of Months | 26.44 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.74 | 13.57 |
February | 23.09 | 15.49 |
March | 23.22 | 17.07 |
April | 24.13 | 21.23 |
May | 25.08 | 26.90 |
June | 25.26 | 27.61 |
July | 25.36 | 27.94 |
August | 25.30 | 27.43 |
September | 25.12 | 26.23 |
October | 24.89 | 24.23 |
November | 23.94 | 18.91 |
December | 23.15 | 15.68 |
Annual Sum or Average | 24.28 | 21.89 |
Minimum of Months | 22.74 | 13.57 |
Maximum of Months | 25.36 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.98 | 13.57 |
February | 22.66 | 15.49 |
March | 22.87 | 17.07 |
April | 24.45 | 21.23 |
May | 25.88 | 26.90 |
June | 26.09 | 27.61 |
July | 26.17 | 27.94 |
August | 26.11 | 27.43 |
September | 25.79 | 26.23 |
October | 25.31 | 24.23 |
November | 23.80 | 18.91 |
December | 22.61 | 15.68 |
Annual Sum or Average | 24.49 | 21.89 |
Minimum of Months | 21.98 | 13.57 |
Maximum of Months | 26.17 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.54 | 13.57 |
February | 23.65 | 15.49 |
March | 23.73 | 17.07 |
April | 23.90 | 21.23 |
May | 23.97 | 26.90 |
June | 24.06 | 27.61 |
July | 24.16 | 27.94 |
August | 24.10 | 27.43 |
September | 24.02 | 26.23 |
October | 23.99 | 24.23 |
November | 23.87 | 18.91 |
December | 23.66 | 15.68 |
Annual Sum or Average | 23.89 | 21.89 |
Minimum of Months | 23.54 | 13.57 |
Maximum of Months | 24.16 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | 13.57 |
February | 21.44 | 15.49 |
March | 21.90 | 17.07 |
April | 23.65 | 21.23 |
May | 25.26 | 26.90 |
June | 25.48 | 27.61 |
July | 25.56 | 27.94 |
August | 25.45 | 27.43 |
September | 25.05 | 26.23 |
October | 24.45 | 24.23 |
November | 22.65 | 18.91 |
December | 21.36 | 15.68 |
Annual Sum or Average | 23.58 | 21.89 |
Minimum of Months | 20.63 | 13.57 |
Maximum of Months | 25.56 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | 13.57 |
February | 21.95 | 15.49 |
March | 22.29 | 17.07 |
April | 23.18 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.24 | 24.23 |
November | 22.76 | 18.91 |
December | 21.81 | 15.68 |
Annual Sum or Average | 22.77 | 21.89 |
Minimum of Months | 21.28 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.57 |
February | 21.63 | 15.49 |
March | 21.67 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.74 | 18.91 |
December | 21.63 | 15.68 |
Annual Sum or Average | 21.71 | 21.89 |
Minimum of Months | 21.58 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 13.57 |
February | 21.64 | 15.49 |
March | 21.68 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.74 | 18.91 |
December | 21.64 | 15.68 |
Annual Sum or Average | 21.72 | 21.89 |
Minimum of Months | 21.60 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 13.57 |
February | 21.66 | 15.49 |
March | 21.69 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.74 | 18.91 |
December | 21.66 | 15.68 |
Annual Sum or Average | 21.72 | 21.89 |
Minimum of Months | 21.63 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.57 |
February | 21.57 | 15.49 |
March | 21.62 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.72 | 18.91 |
December | 21.57 | 15.68 |
Annual Sum or Average | 21.69 | 21.89 |
Minimum of Months | 21.49 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.57 |
February | 21.72 | 15.49 |
March | 21.71 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.72 | 15.68 |
Annual Sum or Average | 21.75 | 21.89 |
Minimum of Months | 21.71 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.31 | 13.57 |
February | 23.31 | 15.49 |
March | 23.32 | 17.07 |
April | 23.33 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.33 | 24.23 |
November | 23.33 | 18.91 |
December | 23.32 | 15.68 |
Annual Sum or Average | 23.33 | 21.89 |
Minimum of Months | 23.31 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.41 | 13.57 |
February | 32.64 | 15.49 |
March | 32.66 | 17.07 |
April | 33.20 | 21.23 |
May | 33.69 | 26.90 |
June | 33.84 | 27.61 |
July | 33.94 | 27.94 |
August | 33.86 | 27.43 |
September | 33.75 | 26.23 |
October | 33.58 | 24.23 |
November | 33.11 | 18.91 |
December | 32.65 | 15.68 |
Annual Sum or Average | 33.28 | 21.89 |
Minimum of Months | 32.41 | 13.57 |
Maximum of Months | 33.94 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 13.57 |
February | 22.44 | 15.49 |
March | 22.46 | 17.07 |
April | 22.74 | 21.23 |
May | 23.28 | 26.90 |
June | 23.43 | 27.61 |
July | 23.60 | 27.94 |
August | 23.52 | 27.43 |
September | 23.39 | 26.23 |
October | 23.23 | 24.23 |
November | 22.66 | 18.91 |
December | 22.46 | 15.68 |
Annual Sum or Average | 22.97 | 21.89 |
Minimum of Months | 22.34 | 13.57 |
Maximum of Months | 23.60 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.57 |
February | 21.74 | 15.49 |
March | 21.73 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.74 | 15.68 |
Annual Sum or Average | 21.75 | 21.89 |
Minimum of Months | 21.73 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.57 |
February | 21.73 | 15.49 |
March | 21.71 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.73 | 15.68 |
Annual Sum or Average | 21.75 | 21.89 |
Minimum of Months | 21.71 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 13.57 |
February | 23.12 | 15.49 |
March | 23.30 | 17.07 |
April | 24.40 | 21.23 |
May | 25.42 | 26.90 |
June | 25.60 | 27.61 |
July | 25.70 | 27.94 |
August | 25.59 | 27.43 |
September | 25.39 | 26.23 |
October | 25.09 | 24.23 |
November | 24.05 | 18.91 |
December | 23.14 | 15.68 |
Annual Sum or Average | 24.47 | 21.89 |
Minimum of Months | 22.69 | 13.57 |
Maximum of Months | 25.70 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 13.57 |
February | 22.70 | 15.49 |
March | 23.07 | 17.07 |
April | 25.02 | 21.23 |
May | 26.89 | 26.90 |
June | 27.22 | 27.61 |
July | 27.38 | 27.94 |
August | 27.12 | 27.43 |
September | 26.70 | 26.23 |
October | 26.03 | 24.23 |
November | 24.19 | 18.91 |
December | 22.62 | 15.68 |
Annual Sum or Average | 25.08 | 21.89 |
Minimum of Months | 21.89 | 13.57 |
Maximum of Months | 27.38 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.57 |
February | 22.48 | 15.49 |
March | 22.74 | 17.07 |
April | 24.51 | 21.23 |
May | 26.05 | 26.90 |
June | 26.26 | 27.61 |
July | 26.34 | 27.94 |
August | 26.26 | 27.43 |
September | 25.92 | 26.23 |
October | 25.38 | 24.23 |
November | 23.74 | 18.91 |
December | 22.39 | 15.68 |
Annual Sum or Average | 24.49 | 21.89 |
Minimum of Months | 21.70 | 13.57 |
Maximum of Months | 26.34 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.78 | 13.57 |
February | 23.17 | 15.49 |
March | 23.31 | 17.07 |
April | 23.84 | 21.23 |
May | 23.89 | 26.90 |
June | 23.89 | 27.61 |
July | 23.89 | 27.94 |
August | 23.89 | 27.43 |
September | 23.89 | 26.23 |
October | 23.86 | 24.23 |
November | 23.66 | 18.91 |
December | 23.09 | 15.68 |
Annual Sum or Average | 23.60 | 21.89 |
Minimum of Months | 22.78 | 13.57 |
Maximum of Months | 23.89 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.12 | 13.57 |
February | 21.12 | 15.49 |
March | 21.69 | 17.07 |
April | 23.77 | 21.23 |
May | 25.56 | 26.90 |
June | 25.80 | 27.61 |
July | 25.87 | 27.94 |
August | 25.75 | 27.43 |
September | 25.31 | 26.23 |
October | 24.62 | 24.23 |
November | 22.56 | 18.91 |
December | 21.00 | 15.68 |
Annual Sum or Average | 23.61 | 21.89 |
Minimum of Months | 20.12 | 13.57 |
Maximum of Months | 25.87 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | 13.57 |
February | 21.60 | 15.49 |
March | 21.99 | 17.07 |
April | 23.10 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.18 | 24.23 |
November | 22.51 | 18.91 |
December | 21.41 | 15.68 |
Annual Sum or Average | 22.61 | 21.89 |
Minimum of Months | 20.81 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 13.57 |
February | 21.69 | 15.49 |
March | 22.06 | 17.07 |
April | 23.13 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.21 | 24.23 |
November | 22.56 | 18.91 |
December | 21.52 | 15.68 |
Annual Sum or Average | 22.65 | 21.89 |
Minimum of Months | 20.92 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 13.57 |
February | 21.71 | 15.49 |
March | 22.08 | 17.07 |
April | 23.11 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.20 | 24.23 |
November | 22.55 | 18.91 |
December | 21.56 | 15.68 |
Annual Sum or Average | 22.66 | 21.89 |
Minimum of Months | 20.98 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.57 |
February | 21.63 | 15.49 |
March | 21.66 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.73 | 18.91 |
December | 21.62 | 15.68 |
Annual Sum or Average | 21.71 | 21.89 |
Minimum of Months | 21.58 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 13.57 |
February | 21.70 | 15.49 |
March | 22.06 | 17.07 |
April | 23.11 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.20 | 24.23 |
November | 22.57 | 18.91 |
December | 21.57 | 15.68 |
Annual Sum or Average | 22.66 | 21.89 |
Minimum of Months | 20.98 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.57 |
February | 21.69 | 15.49 |
March | 21.67 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.69 | 15.68 |
Annual Sum or Average | 21.73 | 21.89 |
Minimum of Months | 21.67 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.57 |
February | 21.74 | 15.49 |
March | 21.73 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.74 | 15.68 |
Annual Sum or Average | 21.75 | 21.89 |
Minimum of Months | 21.73 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.84 | 13.57 |
February | 25.15 | 15.49 |
March | 25.24 | 17.07 |
April | 25.91 | 21.23 |
May | 26.36 | 26.90 |
June | 26.44 | 27.61 |
July | 26.49 | 27.94 |
August | 26.46 | 27.43 |
September | 26.38 | 26.23 |
October | 26.24 | 24.23 |
November | 25.73 | 18.91 |
December | 25.15 | 15.68 |
Annual Sum or Average | 25.87 | 21.89 |
Minimum of Months | 24.84 | 13.57 |
Maximum of Months | 26.49 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.99 | 13.57 |
February | 23.09 | 15.49 |
March | 23.13 | 17.07 |
April | 23.33 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.33 | 24.23 |
November | 23.30 | 18.91 |
December | 23.09 | 15.68 |
Annual Sum or Average | 23.25 | 21.89 |
Minimum of Months | 22.99 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.57 |
February | 21.73 | 15.49 |
March | 21.71 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.75 | 18.91 |
December | 21.72 | 15.68 |
Annual Sum or Average | 21.74 | 21.89 |
Minimum of Months | 21.71 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.17 | 13.57 |
February | 22.48 | 15.49 |
March | 22.57 | 17.07 |
April | 23.21 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.27 | 24.23 |
November | 23.04 | 18.91 |
December | 22.44 | 15.68 |
Annual Sum or Average | 22.99 | 21.89 |
Minimum of Months | 22.17 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.33 | 13.57 |
February | 22.90 | 15.49 |
March | 23.15 | 17.07 |
April | 24.52 | 21.23 |
May | 25.68 | 26.90 |
June | 25.88 | 27.61 |
July | 25.97 | 27.94 |
August | 25.83 | 27.43 |
September | 25.60 | 26.23 |
October | 25.23 | 24.23 |
November | 24.00 | 18.91 |
December | 22.89 | 15.68 |
Annual Sum or Average | 24.51 | 21.89 |
Minimum of Months | 22.33 | 13.57 |
Maximum of Months | 25.97 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.57 |
February | 22.52 | 15.49 |
March | 22.96 | 17.07 |
April | 25.15 | 21.23 |
May | 27.16 | 26.90 |
June | 27.52 | 27.61 |
July | 27.68 | 27.94 |
August | 27.38 | 27.43 |
September | 26.91 | 26.23 |
October | 26.15 | 24.23 |
November | 24.14 | 18.91 |
December | 22.40 | 15.68 |
Annual Sum or Average | 25.14 | 21.89 |
Minimum of Months | 21.58 | 13.57 |
Maximum of Months | 27.68 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.10 | 13.57 |
February | 22.07 | 15.49 |
March | 22.44 | 17.07 |
April | 24.60 | 21.23 |
May | 26.46 | 26.90 |
June | 26.73 | 27.61 |
July | 26.79 | 27.94 |
August | 26.69 | 27.43 |
September | 26.24 | 26.23 |
October | 25.57 | 24.23 |
November | 23.56 | 18.91 |
December | 21.94 | 15.68 |
Annual Sum or Average | 24.53 | 21.89 |
Minimum of Months | 21.10 | 13.57 |
Maximum of Months | 26.79 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.36 | 13.57 |
February | 22.75 | 15.49 |
March | 22.94 | 17.07 |
April | 23.64 | 21.23 |
May | 23.97 | 26.90 |
June | 24.02 | 27.61 |
July | 24.06 | 27.94 |
August | 24.02 | 27.43 |
September | 23.98 | 26.23 |
October | 23.81 | 24.23 |
November | 23.26 | 18.91 |
December | 22.66 | 15.68 |
Annual Sum or Average | 23.46 | 21.89 |
Minimum of Months | 22.36 | 13.57 |
Maximum of Months | 24.06 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 13.57 |
February | 20.77 | 15.49 |
March | 21.43 | 17.07 |
April | 23.81 | 21.23 |
May | 25.87 | 26.90 |
June | 26.16 | 27.61 |
July | 26.22 | 27.94 |
August | 26.07 | 27.43 |
September | 25.54 | 26.23 |
October | 24.75 | 24.23 |
November | 22.35 | 18.91 |
December | 20.61 | 15.68 |
Annual Sum or Average | 23.61 | 21.89 |
Minimum of Months | 19.63 | 13.57 |
Maximum of Months | 26.22 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.43 | 13.57 |
February | 21.53 | 15.49 |
March | 21.57 | 17.07 |
April | 21.74 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.74 | 24.23 |
November | 21.71 | 18.91 |
December | 21.49 | 15.68 |
Annual Sum or Average | 21.67 | 21.89 |
Minimum of Months | 21.43 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | 13.57 |
February | 21.33 | 15.49 |
March | 21.74 | 17.07 |
April | 22.91 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.11 | 24.23 |
November | 22.19 | 18.91 |
December | 21.18 | 15.68 |
Annual Sum or Average | 22.48 | 21.89 |
Minimum of Months | 20.63 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | 13.57 |
February | 21.32 | 15.49 |
March | 21.73 | 17.07 |
April | 22.88 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.10 | 24.23 |
November | 22.17 | 18.91 |
December | 21.18 | 15.68 |
Annual Sum or Average | 22.48 | 21.89 |
Minimum of Months | 20.65 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.57 |
February | 21.62 | 15.49 |
March | 21.65 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.73 | 18.91 |
December | 21.61 | 15.68 |
Annual Sum or Average | 21.71 | 21.89 |
Minimum of Months | 21.58 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | 13.57 |
February | 21.40 | 15.49 |
March | 21.78 | 17.07 |
April | 22.94 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.12 | 24.23 |
November | 22.27 | 18.91 |
December | 21.25 | 15.68 |
Annual Sum or Average | 22.51 | 21.89 |
Minimum of Months | 20.69 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 13.57 |
February | 21.99 | 15.49 |
March | 22.13 | 17.07 |
April | 23.03 | 21.23 |
May | 23.33 | 26.90 |
June | 23.33 | 27.61 |
July | 23.33 | 27.94 |
August | 23.33 | 27.43 |
September | 23.33 | 26.23 |
October | 23.19 | 24.23 |
November | 22.68 | 18.91 |
December | 21.90 | 15.68 |
Annual Sum or Average | 22.76 | 21.89 |
Minimum of Months | 21.54 | 13.57 |
Maximum of Months | 23.33 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.57 |
February | 21.72 | 15.49 |
March | 21.70 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.75 | 18.91 |
December | 21.72 | 15.68 |
Annual Sum or Average | 21.74 | 21.89 |
Minimum of Months | 21.70 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.76 | 13.57 |
February | 23.17 | 15.49 |
March | 23.36 | 17.07 |
April | 24.27 | 21.23 |
May | 24.98 | 26.90 |
June | 25.10 | 27.61 |
July | 25.14 | 27.94 |
August | 25.09 | 27.43 |
September | 24.93 | 26.23 |
October | 24.70 | 24.23 |
November | 23.86 | 18.91 |
December | 23.13 | 15.68 |
Annual Sum or Average | 24.21 | 21.89 |
Minimum of Months | 22.76 | 13.57 |
Maximum of Months | 25.14 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.57 |
February | 21.72 | 15.49 |
March | 21.70 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.76 | 24.23 |
November | 21.75 | 18.91 |
December | 21.72 | 15.68 |
Annual Sum or Average | 21.74 | 21.89 |
Minimum of Months | 21.70 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.57 |
February | 21.72 | 15.49 |
March | 21.69 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.75 | 18.91 |
December | 21.71 | 15.68 |
Annual Sum or Average | 21.74 | 21.89 |
Minimum of Months | 21.69 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 13.57 |
February | 21.69 | 15.49 |
March | 21.66 | 17.07 |
April | 21.75 | 21.23 |
May | 21.76 | 26.90 |
June | 21.76 | 27.61 |
July | 21.76 | 27.94 |
August | 21.76 | 27.43 |
September | 21.76 | 26.23 |
October | 21.75 | 24.23 |
November | 21.75 | 18.91 |
December | 21.69 | 15.68 |
Annual Sum or Average | 21.73 | 21.89 |
Minimum of Months | 21.66 | 13.57 |
Maximum of Months | 21.76 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.91 | 13.57 |
February | 22.54 | 15.49 |
March | 22.87 | 17.07 |
April | 24.40 | 21.23 |
May | 25.78 | 26.90 |
June | 26.03 | 27.61 |
July | 26.10 | 27.94 |
August | 25.94 | 27.43 |
September | 25.61 | 26.23 |
October | 25.15 | 24.23 |
November | 23.68 | 18.91 |
December | 22.49 | 15.68 |
Annual Sum or Average | 24.38 | 21.89 |
Minimum of Months | 21.91 | 13.57 |
Maximum of Months | 26.10 | 27.94 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:34
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 13.57 |
February | 22.14 | 15.49 |
March | 22.67 | 17.07 |
April | 25.11 | 21.23 |
May | 27.39 | 26.90 |
June | 27.80 | 27.61 |
July | 27.92 | 27.94 |
August | 27.61 | 27.43 |
September | 27.03 | 26.23 |
October | 26.16 | 24.23 |
November | 23.86 | 18.91 |
December | 21.98 | 15.68 |
Annual Sum or Average | 25.08 | 21.89 |
Minimum of Months | 21.08 | 13.57 |
Maximum of Months | 27.92 | 27.94 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:34
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.140668E+12 | 96542.494 | 05-JAN-07:15 | 15177.258 | 39465.561 | 8750.046 | 28074.317 | 879.198 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.130544E+12 | 105138.524 | 05-FEB-07:15 | 15177.258 | 39465.561 | 8764.120 | 37281.861 | 253.611 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.145129E+12 | 92739.037 | 18-MAR-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 22358.063 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.151983E+12 | 99391.682 | 29-APR-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 29010.708 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.182510E+12 | 105676.064 | 27-MAY-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 35295.090 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.180888E+12 | 107758.048 | 17-JUN-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 37377.074 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.191859E+12 | 108100.184 | 08-JUL-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 37719.210 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.188639E+12 | 104665.279 | 04-AUG-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 34284.305 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.177816E+12 | 104756.140 | 10-SEP-06:15 | 15177.258 | 39465.561 | 8807.394 | 0.000 | 37109.814 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.173727E+12 | 110516.398 | 07-OCT-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 40135.424 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.146645E+12 | 96997.512 | 03-NOV-07:00 | 17938.723 | 43276.576 | 9157.563 | 0.000 | 26616.538 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.145041E+12 | 97704.558 | 21-DEC-07:15 | 15177.258 | 39465.561 | 8750.046 | 29410.270 | 705.310 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.195545E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.130544E+12 | 92739.037 | 15177.258 | 39465.561 | 8750.046 | 0.000 | 253.611 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.191859E+12 | 110516.398 | 17938.723 | 43276.576 | 9157.563 | 37281.861 | 40135.424 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:34
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.843953E+11 | 90026.376 | 21-JAN-10:30 | 3091.266 | 40096.028 | 0.000 | 46839.082 | 46839.082 | 46839.082 | 3091.266 |
February | 0.752777E+11 | 92919.234 | 05-FEB-09:15 | 3214.946 | 40096.028 | 0.000 | 49608.261 | 49608.261 | 49608.261 | 3214.946 |
March | 0.811993E+11 | 86030.072 | 02-MAR-09:15 | 0.000 | 40096.028 | 0.000 | 45934.044 | 45934.044 | 45934.044 | 0.000 |
April | 0.764107E+11 | 74054.795 | 01-APR-08:15 | 0.000 | 40096.028 | 0.000 | 33958.767 | 33958.767 | 33958.767 | 0.000 |
May | 0.774533E+11 | 73228.577 | 01-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 33132.549 | 33132.549 | 33132.549 | 0.000 |
June | 0.737981E+11 | 72451.169 | 02-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 32355.141 | 32355.141 | 32355.141 | 0.000 |
July | 0.756755E+11 | 71976.634 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 31880.606 | 31880.606 | 31880.606 | 0.000 |
August | 0.758687E+11 | 72172.903 | 31-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 32076.875 | 32076.875 | 32076.875 | 0.000 |
September | 0.742862E+11 | 72772.038 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 32676.010 | 32676.010 | 32676.010 | 0.000 |
October | 0.781566E+11 | 73614.998 | 31-OCT-08:15 | 0.000 | 40096.028 | 0.000 | 33518.970 | 33518.970 | 33518.970 | 0.000 |
November | 0.773341E+11 | 74341.104 | 30-NOV-09:00 | 0.000 | 40096.028 | 0.000 | 34245.076 | 34245.076 | 34245.076 | 0.000 |
December | 0.824591E+11 | 89195.363 | 31-DEC-09:45 | 0.000 | 40096.028 | 0.000 | 49099.335 | 49099.335 | 49099.335 | 0.000 |
Annual Sum or Average | 0.932315E+12 | 0.000 | ||||||||
Minimum of Months | 0.737981E+11 | 71976.634 | 0.000 | 40096.028 | 0.000 | 31880.606 | 31880.606 | 31880.606 | 0.000 | |
Maximum of Months | 0.843953E+11 | 92919.234 | 3214.946 | 40096.028 | 0.000 | 49608.261 | 49608.261 | 49608.261 | 3214.946 |