Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Honolulu Intl Arpt HI USA TMY3 WMO#=911820

Simulation Timestamp: 2018-10-19 10:15:42


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2945.71 733.94 790.78
Net Site Energy 2945.71 733.94 790.78
Total Source Energy 7448.58 1855.84 1999.57
Net Source Energy 7448.58 1855.84 1999.57


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.01 0.00 0.00 0.00 0.00 0.00
Cooling 687.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.92 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 280.22 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 481.29 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2042.93 902.78 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.01 0.00 0.00 0.00 0.00 0.00
Cooling General 687.28 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.92 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 280.22 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 481.29 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 129.97 0.00 0.00 0.00 0.00 0.00
HVAC 259.79 129.20 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 548.42 242.35 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 120.63 0.00 0.00 0.00 0.00 0.00
HVAC 241.12 119.91 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 509.01 224.93 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2042.93 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2042.93 100.00
     
Total On-Site and Utility Electric Sources 2042.93 100.00
Total Electricity End Uses 2042.93 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 299.00
Time Setpoint Not Met During Occupied Cooling 6130.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 6394.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Weather File Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Latitude [deg] 21.32
Longitude [deg] -157.9
Elevation [m] 2.00
Time Zone -10.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 16.20 0.00 16.20 Wetbulb [C] 1.90 320.00
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 32.20 7.10 23.30 Wetbulb [C] 6.70 60.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.704 0.787 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.55 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.704 0.787 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.704 0.787 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 5.778 0.306 0.155     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 4.44 0.00 0.00 4.44 4.44 5.778 0.306 0.155     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 5.778 0.306 0.155     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_1.22_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 5.778 0.306 0.155     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 5.778 0.306 0.155     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 5.778 0.306 0.155     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_1.22_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 5.778 0.306 0.155     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 5.778 0.306 0.155              
North Total or Average           96.82 5.778 0.306 0.155              
Non-North Total or Average           87.38 5.778 0.306 0.155              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7183.00 5062.48 2120.51 0.70 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   19644.53 13281.33 6363.19 0.68 3.80    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8994.31 6080.90 2913.41 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   14458.19 10383.08 4075.11 0.72 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6932.0 3.32 11.34 12.02 11.40
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 19029.6 3.29 11.23 11.91 11.42
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8712.8 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13928.4 3.30 11.25 11.92 11.27
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.36 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   4137.19 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.28 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.36 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   1355.37 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   1772.58 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   477.87 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.28 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.36 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   1355.37 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   1772.58 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.28 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.36 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   1585.78 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   1772.58 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   2236.60 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   559.15 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   2236.44 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   559.11 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.28 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   2302.33 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   9650.18 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   5167.60 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   3859.80 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.32 361.95 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.79 875.86 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 405.70 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.68 764.09 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7994.32 9593.18 0.659 0.791 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
RESTROOMFLR1 480.29 576.35 0.040 0.047 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 31.49 0.01435
MEETINGROOMFLR1 3658.05 4389.66 0.302 0.362 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM101 637.67 765.20 0.073 0.088 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM102 534.35 641.22 0.061 0.073 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM103 1169.52 1403.42 0.134 0.161 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
GUESTROOM104 1256.35 1507.62 0.144 0.173 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM105 1551.54 1861.85 0.178 0.213 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
EMPLOYEELOUNGEFLR1 5215.66 6258.80 0.430 0.516 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
EXERCISECENTERFLR1 1197.90 1437.49 0.099 0.118 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 31.21 0.01435
FRONTOFFICEFLR1 3268.11 3921.73 0.269 0.323 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM201 1035.04 1242.04 0.119 0.142 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 12:45:00 31.70 0.01435
GUESTROOM202_205 4326.04 5191.24 0.496 0.595 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM206_208 3485.85 4183.02 0.399 0.479 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM209_212 4118.46 4942.16 0.472 0.566 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM213 1219.54 1463.45 0.140 0.168 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
GUESTROOM214 1363.86 1636.63 0.156 0.188 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
GUESTROOM215_218 9273.16 11127.79 1.062 1.275 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM219 5246.49 6295.79 0.601 0.721 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
GUESTROOM220_223 4615.87 5539.04 0.529 0.635 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM224 1338.07 1605.69 0.153 0.184 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM301 857.91 1029.49 0.098 0.118 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 31.85 0.01435
GUESTROOM302_305 1760.75 2112.90 0.202 0.242 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM306_308 1521.70 1826.04 0.174 0.209 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM309_312 4067.31 4880.77 0.466 0.559 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM313 719.25 863.10 0.082 0.099 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 29.96 0.01435
GUESTROOM314 1288.04 1545.65 0.148 0.177 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM315_318 4968.27 5961.93 0.569 0.683 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM319 1100.75 1320.90 0.126 0.151 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
GUESTROOM320_323 4402.94 5283.53 0.504 0.605 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM324 771.82 926.19 0.088 0.106 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
GUESTROOM401 1645.96 1975.15 0.189 0.226 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 13:00:00 31.85 0.01435
GUESTROOM402_405 2326.03 2791.24 0.266 0.320 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM406_408 1982.10 2378.52 0.227 0.272 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM409_412 4922.10 5906.52 0.564 0.677 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
GUESTROOM413 898.57 1078.28 0.103 0.124 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 16:00:00 31.77 0.01435
GUESTROOM414 1004.81 1205.77 0.115 0.138 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 32.09 0.01435
GUESTROOM415_418 5389.47 6467.37 0.618 0.741 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 32.20 0.01435
GUESTROOM419 1483.92 1780.71 0.170 0.204 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 32.20 0.01435
GUESTROOM420_423 5365.48 6438.58 0.615 0.738 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 32.20 0.01435
GUESTROOM424 1536.08 1843.30 0.176 0.211 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 32.20 0.01435
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
CORRIDORFLR1 17215.46 20658.55 1.419 1.703 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 30.50 0.01435
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
CORRIDORFLR2 2771.87 3326.24 0.228 0.274 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:15:00 31.03 0.01435
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
CORRIDORFLR3 1406.92 1688.31 0.116 0.139 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 30.85 0.01435
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435
CORRIDORFLR4 2021.94 2426.33 0.167 0.200 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 31.88 0.01435
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB   32.20 0.01435


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 341.11 409.33 0.010 0.236 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:30:00 16.20 0.01152
MEETINGROOMFLR1 57.34 68.81 0.002 0.126 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:45:00 16.20 0.01152
GUESTROOM101 19.28 23.14 0.001 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:30:00 16.20 0.01152
GUESTROOM102 50.65 60.77 0.001 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:30:00 16.20 0.01152
GUESTROOM103 90.16 108.19 0.003 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:30:00 16.20 0.01152
GUESTROOM104 73.06 87.67 0.002 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:30:00 16.20 0.01152
GUESTROOM105 46.59 55.91 0.001 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:45:00 16.20 0.01152
EMPLOYEELOUNGEFLR1 18.26 21.91 0.001 0.051 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 08:30:00 16.20 0.01152
EXERCISECENTERFLR1 0.00 0.00 0.000 0.043 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
FRONTOFFICEFLR1 153.08 183.70 0.004 0.056 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 06:30:00 16.20 0.01152
GUESTROOM201 126.73 152.08 0.004 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM202_205 232.18 278.62 0.007 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM206_208 142.11 170.54 0.004 0.043 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM209_212 169.48 203.37 0.005 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 00:15:00 16.20 0.01152
GUESTROOM213 103.97 124.76 0.003 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM214 75.99 91.18 0.002 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 11:00:00 16.20 0.01152
GUESTROOM215_218 125.34 150.41 0.004 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 09:15:00 16.20 0.01152
GUESTROOM219 0.00 0.00 0.000 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
GUESTROOM220_223 140.93 169.12 0.004 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 08:00:00 16.20 0.01152
GUESTROOM224 69.96 83.95 0.002 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 09:15:00 16.20 0.01152
GUESTROOM301 146.49 175.78 0.004 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM302_305 287.79 345.35 0.008 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM306_308 233.98 280.77 0.007 0.043 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM309_312 271.55 325.86 0.008 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM313 128.91 154.69 0.004 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM314 98.57 118.28 0.003 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 16:30:00 16.20 0.01152
GUESTROOM315_318 252.71 303.25 0.007 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 13:15:00 16.20 0.01152
GUESTROOM319 47.96 57.55 0.001 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 13:30:00 16.20 0.01152
GUESTROOM320_323 233.42 280.10 0.007 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 14:45:00 16.20 0.01152
GUESTROOM324 95.08 114.10 0.003 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 21:00:00 16.20 0.01152
GUESTROOM401 204.25 245.10 0.006 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM402_405 494.38 593.26 0.014 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM406_408 413.72 496.46 0.012 0.043 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM409_412 489.05 586.86 0.014 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM413 194.87 233.85 0.005 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM414 164.13 196.96 0.005 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
GUESTROOM415_418 479.18 575.01 0.014 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 17:30:00 16.20 0.01152
GUESTROOM419 124.90 149.88 0.004 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 18:15:00 16.20 0.01152
GUESTROOM420_423 453.88 544.65 0.013 0.054 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 19:45:00 16.20 0.01152
GUESTROOM424 162.02 194.43 0.005 0.013 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 24:00:00 16.20 0.01152
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
CORRIDORFLR1 3216.52 3859.82 0.091 0.109 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 18:30:00 16.20 0.01152
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
CORRIDORFLR2 0.00 0.00 0.000 0.038 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
CORRIDORFLR3 0.00 0.00 0.000 0.038 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152
CORRIDORFLR4 35.97 43.17 0.001 0.038 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB 2/21 22:00:00 16.20 0.01152
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB   16.20 0.01152


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.32 0.32 0.06 0.06
SAC_FRONTLOUNGE 0.79 0.79 0.24 0.24
SAC_MEETINGROOM 0.36 0.36 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.68 0.68 0.09 0.09



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 7422.50 2783.25 2444.75
RESTROOMFLR1 2560.00 2698.50 210.25
MEETINGROOMFLR1 4129.00 777.00 677.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 109.75 8490.75 109.75
GUESTROOM104 43.50 7688.75 42.25
GUESTROOM105 125.75 6877.50 8.75
EMPLOYEELOUNGEFLR1 3263.00 1944.75 300.50
EXERCISECENTERFLR1 5344.25 76.75 53.75
FRONTOFFICEFLR1 5406.75 571.00 213.00
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 137.75 6840.50 26.75
GUESTROOM206_208 120.25 6870.75 18.75
GUESTROOM209_212 82.75 7015.25 32.25
GUESTROOM213 48.50 7632.00 45.25
GUESTROOM214 180.25 6869.75 17.50
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 6161.00 3672.25 1656.00
GUESTROOM220_223 488.25 6618.50 26.25
GUESTROOM224 200.00 6708.50 12.75
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 103.75 7494.00 94.00
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 179.75 6875.00 20.25
GUESTROOM315_318 695.50 6489.75 15.75
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 394.25 6900.50 53.25
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 1749.25 6390.50 22.75
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1527.25 6433.00 22.25
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 2033.00 6330.75 13.00
GUESTROOM419 1498.50 6394.25 5.25
GUESTROOM420_423 1990.25 6340.25 16.50
GUESTROOM424 1528.50 6413.25 8.25
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 8282.00 8753.75 6394.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 0.00 2513.50 0.00 2513.50
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 91.25 0.00 91.25
GUESTROOM104 0.00 91.25 0.00 91.25
GUESTROOM105 0.00 91.25 0.00 91.25
EMPLOYEELOUNGEFLR1 387.00 1377.00 299.00 694.75
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 88.50 0.00 88.50
GUESTROOM206_208 0.00 91.25 0.00 91.25
GUESTROOM209_212 0.00 87.50 0.00 87.50
GUESTROOM213 0.00 89.00 0.00 89.00
GUESTROOM214 0.00 91.25 0.00 91.25
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 4829.75 0.00 4829.75
GUESTROOM220_223 0.00 91.25 0.00 91.25
GUESTROOM224 0.00 91.25 0.00 91.25
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 86.75 0.00 86.75
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 91.25 0.00 91.25
GUESTROOM315_318 0.00 91.25 0.00 91.25
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 90.25 0.00 90.25
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 0.00 91.25 0.00 91.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 89.25 0.00 89.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 91.25 0.00 91.25
GUESTROOM419 0.00 91.25 0.00 91.25
GUESTROOM420_423 0.00 91.25 0.00 91.25
GUESTROOM424 0.00 91.25 0.00 91.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 7867.25 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 1166.25 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 1.50 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 998.25 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 387.00 8401.25 299.00 6130.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:42

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.323137
SAC_FRONTLOUNGE SUPPLY FAN 0.791085
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.682156


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 321.36
CORRIDORFLR1 PTAC HEATING COIL 4137.19
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 559.15
102 PTAC HEATING COIL 559.15
103 PTAC HEATING COIL 559.15
104 PTAC HEATING COIL 559.11
105 PTAC HEATING COIL 559.11
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 321.28
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 321.36
CORRIDORFLR2 PTAC HEATING COIL 1355.37
201 PTAC HEATING COIL 559.15
202_205 PTAC HEATING COIL 2236.60
206_208 PTAC HEATING COIL 1772.58
209_212 PTAC HEATING COIL 2236.60
213 PTAC HEATING COIL 559.15
214 PTAC HEATING COIL 559.11
215_218 PTAC HEATING COIL 2236.44
219 PTAC HEATING COIL 477.87
220_223 PTAC HEATING COIL 2236.44
224 PTAC HEATING COIL 559.11
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 321.28
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 321.36
CORRIDORFLR3 PTAC HEATING COIL 1355.37
301 PTAC HEATING COIL 559.15
302_305 PTAC HEATING COIL 2236.60
306_308 PTAC HEATING COIL 1772.58
309_312 PTAC HEATING COIL 2236.60
313 PTAC HEATING COIL 559.15
314 PTAC HEATING COIL 559.11
315_318 PTAC HEATING COIL 2236.44
319 PTAC HEATING COIL 559.11
320_323 PTAC HEATING COIL 2236.44
324 PTAC HEATING COIL 559.11
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 321.28
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 321.36
CORRIDORFLR4 PTAC HEATING COIL 1585.78
401 PTAC HEATING COIL 559.15
402_405 PTAC HEATING COIL 2236.60
406_408 PTAC HEATING COIL 1772.58
409_412 PTAC HEATING COIL 2236.60
413 PTAC HEATING COIL 559.15
414 PTAC HEATING COIL 559.11
415_418 PTAC HEATING COIL 2236.44
419 PTAC HEATING COIL 559.11
420_423 PTAC HEATING COIL 2236.44
424 PTAC HEATING COIL 559.11
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 321.28


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.704787 0.323137 7183.00
SAC_FRONTLOUNGE COOLING COIL 0.676083 0.791085 19644.53
SAC_MEETINGROOM COOLING COIL 0.676083 0.362201 8994.31
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.718146 0.682156 14458.19


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.791085
RESTROOMFLR1 DIRECT AIR 0.047481
MEETINGROOMFLR1 DIRECT AIR 0.362201
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.516189
EXERCISECENTERFLR1 DIRECT AIR 0.118486
FRONTOFFICEFLR1 DIRECT AIR 0.323137


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.323137
SAC_FRONTLOUNGE MAIN BRANCH 0.791085
SAC_MEETINGROOM MAIN BRANCH 0.362201
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.682156


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.323137
SAC_FRONTLOUNGE 0.791085
SAC_MEETINGROOM 0.362201
SAC_EXC_EMPLGE_RESTRM 0.682156


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.323137 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.791085 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.362201 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.682156 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.323137 0.323137 0.323137 0.323137 2302.33 7183.00 1.00
SAC_FRONTLOUNGE 0.791085 0.791085 0.791085 0.791085 9650.18 19644.53 1.00
SAC_MEETINGROOM 0.362201 0.362201 0.362201 0.362201 5167.60 8994.31 1.00
SAC_EXC_EMPLGE_RESTRM 0.682156 0.682156 0.682156 0.682156 3859.80 14458.19 0.173694


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 2302.33
SAC_FRONTLOUNGE HEATING COIL 9650.18
SAC_MEETINGROOM HEATING COIL 5167.60
SAC_EXC_EMPLGE_RESTRM HEATING COIL 3859.80


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.362201


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.16 22.49
February 24.42 22.80
March 24.51 23.17
April 24.55 23.76
May 24.98 25.23
June 25.24 25.87
July 25.62 26.90
August 25.70 27.06
September 25.92 26.87
October 25.44 26.22
November 25.03 24.76
December 24.59 23.69
     
Annual Sum or Average 25.02 24.91
Minimum of Months 24.16 22.49
Maximum of Months 25.92 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.66 22.49
February 25.91 22.80
March 25.91 23.17
April 25.97 23.76
May 26.46 25.23
June 26.63 25.87
July 26.97 26.90
August 27.01 27.06
September 27.03 26.87
October 26.83 26.22
November 26.37 24.76
December 26.05 23.69
     
Annual Sum or Average 26.40 24.91
Minimum of Months 25.66 22.49
Maximum of Months 27.03 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.34 22.49
February 23.70 22.80
March 23.91 23.17
April 24.09 23.76
May 24.64 25.23
June 24.94 25.87
July 25.29 26.90
August 25.27 27.06
September 25.32 26.87
October 24.70 26.22
November 24.24 24.76
December 23.76 23.69
     
Annual Sum or Average 24.44 24.91
Minimum of Months 23.34 22.49
Maximum of Months 25.32 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.87 22.49
February 23.84 22.80
March 23.86 23.17
April 23.89 23.76
May 23.89 25.23
June 23.89 25.87
July 23.89 26.90
August 23.89 27.06
September 23.89 26.87
October 23.89 26.22
November 23.88 24.76
December 23.88 23.69
     
Annual Sum or Average 23.88 24.91
Minimum of Months 23.84 22.49
Maximum of Months 23.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.41 22.49
February 23.47 22.80
March 23.55 23.17
April 23.64 23.76
May 23.81 25.23
June 23.87 25.87
July 23.91 26.90
August 23.85 27.06
September 23.77 26.87
October 23.67 26.22
November 23.54 24.76
December 23.47 23.69
     
Annual Sum or Average 23.66 24.91
Minimum of Months 23.41 22.49
Maximum of Months 23.91 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.87 22.49
February 23.87 22.80
March 23.88 23.17
April 23.89 23.76
May 23.89 25.23
June 23.89 25.87
July 23.89 26.90
August 23.89 27.06
September 23.89 26.87
October 23.89 26.22
November 23.89 24.76
December 23.89 23.69
     
Annual Sum or Average 23.89 24.91
Minimum of Months 23.87 22.49
Maximum of Months 23.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 30.44 22.49
February 30.78 22.80
March 31.20 23.17
April 31.95 23.76
May 32.80 25.23
June 33.37 25.87
July 33.66 26.90
August 33.45 27.06
September 33.02 26.87
October 32.29 26.22
November 31.51 24.76
December 30.89 23.69
     
Annual Sum or Average 32.12 24.91
Minimum of Months 30.44 22.49
Maximum of Months 33.66 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 22.49
February 23.33 22.80
March 23.33 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.33 23.69
     
Annual Sum or Average 23.33 24.91
Minimum of Months 23.33 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.24 22.49
February 23.23 22.80
March 23.24 23.17
April 23.32 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.31 24.76
December 23.30 23.69
     
Annual Sum or Average 23.30 24.91
Minimum of Months 23.23 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.75 26.22
November 21.75 24.76
December 21.75 23.69
     
Annual Sum or Average 21.75 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.75 23.76
May 21.75 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 22.49
February 22.38 22.80
March 22.44 23.17
April 22.49 23.76
May 22.42 25.23
June 22.37 25.87
July 22.27 26.90
August 22.23 27.06
September 22.12 26.87
October 22.11 26.22
November 22.17 24.76
December 22.26 23.69
     
Annual Sum or Average 22.30 24.91
Minimum of Months 22.11 22.49
Maximum of Months 22.49 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 52.64 22.49
February 52.61 22.80
March 52.52 23.17
April 52.41 23.76
May 52.54 25.23
June 52.54 25.87
July 52.69 26.90
August 52.79 27.06
September 52.97 26.87
October 53.06 26.22
November 52.87 24.76
December 52.81 23.69
     
Annual Sum or Average 52.70 24.91
Minimum of Months 52.41 22.49
Maximum of Months 53.06 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 70.25 22.49
February 70.34 22.80
March 70.26 23.17
April 70.13 23.76
May 70.40 25.23
June 70.30 25.87
July 70.48 26.90
August 70.64 27.06
September 70.72 26.87
October 70.88 26.22
November 70.47 24.76
December 70.43 23.69
     
Annual Sum or Average 70.44 24.91
Minimum of Months 70.13 22.49
Maximum of Months 70.88 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 22.49
February 23.88 22.80
March 23.89 23.17
April 23.89 23.76
May 23.89 25.23
June 23.89 25.87
July 23.89 26.90
August 23.89 27.06
September 23.89 26.87
October 23.89 26.22
November 23.89 24.76
December 23.89 23.69
     
Annual Sum or Average 23.89 24.91
Minimum of Months 23.88 22.49
Maximum of Months 23.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 22.49
February 23.89 22.80
March 23.89 23.17
April 23.89 23.76
May 23.89 25.23
June 23.89 25.87
July 23.89 26.90
August 23.89 27.06
September 23.89 26.87
October 23.89 26.22
November 23.89 24.76
December 23.89 23.69
     
Annual Sum or Average 23.89 24.91
Minimum of Months 23.89 22.49
Maximum of Months 23.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.91 22.49
February 24.92 22.80
March 24.96 23.17
April 25.15 23.76
May 25.74 25.23
June 25.89 25.87
July 26.33 26.90
August 26.51 27.06
September 26.46 26.87
October 26.44 26.22
November 25.77 24.76
December 25.37 23.69
     
Annual Sum or Average 25.71 24.91
Minimum of Months 24.91 22.49
Maximum of Months 26.51 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.64 22.49
February 24.61 22.80
March 24.61 23.17
April 24.65 23.76
May 24.95 25.23
June 25.04 25.87
July 25.30 26.90
August 25.40 27.06
September 25.46 26.87
October 25.45 26.22
November 25.14 24.76
December 24.91 23.69
     
Annual Sum or Average 25.01 24.91
Minimum of Months 24.61 22.49
Maximum of Months 25.46 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.75 22.49
February 25.09 22.80
March 25.21 23.17
April 25.26 23.76
May 25.78 25.23
June 26.02 25.87
July 26.47 26.90
August 26.57 27.06
September 26.79 26.87
October 26.26 26.22
November 25.72 24.76
December 25.23 23.69
     
Annual Sum or Average 25.77 24.91
Minimum of Months 24.75 22.49
Maximum of Months 26.79 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 22.49
February 23.90 22.80
March 23.90 23.17
April 23.89 23.76
May 23.91 25.23
June 23.93 25.87
July 24.01 26.90
August 24.04 27.06
September 24.08 26.87
October 24.02 26.22
November 23.94 24.76
December 23.91 23.69
     
Annual Sum or Average 23.95 24.91
Minimum of Months 23.89 22.49
Maximum of Months 24.08 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.74 22.49
February 24.18 22.80
March 24.43 23.17
April 24.64 23.76
May 25.31 25.23
June 25.62 25.87
July 26.05 26.90
August 26.03 27.06
September 26.09 26.87
October 25.39 26.22
November 24.80 24.76
December 24.24 23.69
     
Annual Sum or Average 25.05 24.91
Minimum of Months 23.74 22.49
Maximum of Months 26.09 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 22.49
February 23.29 22.80
March 23.31 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.33 23.69
     
Annual Sum or Average 23.33 24.91
Minimum of Months 23.29 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.76 22.80
March 21.75 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.75 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 22.49
February 23.33 22.80
March 23.33 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.33 23.69
     
Annual Sum or Average 23.33 24.91
Minimum of Months 23.33 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 33.32 22.49
February 33.37 22.80
March 33.31 23.17
April 33.23 23.76
May 33.40 25.23
June 33.39 25.87
July 33.56 26.90
August 33.66 27.06
September 33.78 26.87
October 33.82 26.22
November 33.57 24.76
December 33.48 23.69
     
Annual Sum or Average 33.49 24.91
Minimum of Months 33.23 22.49
Maximum of Months 33.82 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.81 22.49
February 22.94 22.80
March 22.88 23.17
April 22.80 23.76
May 22.94 25.23
June 22.98 25.87
July 23.16 26.90
August 23.24 27.06
September 23.40 26.87
October 23.35 26.22
November 23.12 24.76
December 22.99 23.69
     
Annual Sum or Average 23.05 24.91
Minimum of Months 22.80 22.49
Maximum of Months 23.40 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.98 22.49
February 24.95 22.80
March 24.96 23.17
April 25.05 23.76
May 25.43 25.23
June 25.51 25.87
July 25.81 26.90
August 25.94 27.06
September 25.96 26.87
October 25.96 26.22
November 25.54 24.76
December 25.28 23.69
     
Annual Sum or Average 25.45 24.91
Minimum of Months 24.95 22.49
Maximum of Months 25.96 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.69 22.49
February 25.74 22.80
March 25.84 23.17
April 26.13 23.76
May 26.91 25.23
June 27.00 25.87
July 27.52 26.90
August 27.75 27.06
September 27.59 26.87
October 27.60 26.22
November 26.67 24.76
December 26.20 23.69
     
Annual Sum or Average 26.73 24.91
Minimum of Months 25.69 22.49
Maximum of Months 27.75 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.82 22.49
February 25.18 22.80
March 25.32 23.17
April 25.39 23.76
May 25.96 25.23
June 26.20 25.87
July 26.67 26.90
August 26.78 27.06
September 26.99 26.87
October 26.43 26.22
November 25.85 24.76
December 25.33 23.69
     
Annual Sum or Average 25.91 24.91
Minimum of Months 24.82 22.49
Maximum of Months 26.99 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.89 22.49
February 23.88 22.80
March 23.89 23.17
April 23.89 23.76
May 23.89 25.23
June 23.89 25.87
July 23.89 26.90
August 23.89 27.06
September 23.89 26.87
October 23.89 26.22
November 23.89 24.76
December 23.89 23.69
     
Annual Sum or Average 23.89 24.91
Minimum of Months 23.88 22.49
Maximum of Months 23.89 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 22.49
February 24.35 22.80
March 24.63 23.17
April 24.87 23.76
May 25.61 25.23
June 25.92 25.87
July 26.38 26.90
August 26.38 27.06
September 26.43 26.87
October 25.70 26.22
November 25.04 24.76
December 24.43 23.69
     
Annual Sum or Average 25.31 24.91
Minimum of Months 23.88 22.49
Maximum of Months 26.43 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.28 22.49
February 23.26 22.80
March 23.28 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.32 24.76
December 23.31 23.69
     
Annual Sum or Average 23.32 24.91
Minimum of Months 23.26 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 22.49
February 23.29 22.80
March 23.30 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.32 23.69
     
Annual Sum or Average 23.32 24.91
Minimum of Months 23.29 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 22.49
February 23.28 22.80
March 23.30 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.32 24.76
December 23.32 23.69
     
Annual Sum or Average 23.32 24.91
Minimum of Months 23.28 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.75 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.30 22.49
February 23.29 22.80
March 23.30 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.32 24.76
December 23.32 23.69
     
Annual Sum or Average 23.32 24.91
Minimum of Months 23.29 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 26.16 22.49
February 26.17 22.80
March 26.14 23.17
April 26.11 23.76
May 26.25 25.23
June 26.29 25.87
July 26.44 26.90
August 26.49 27.06
September 26.59 26.87
October 26.57 26.22
November 26.42 24.76
December 26.31 23.69
     
Annual Sum or Average 26.33 24.91
Minimum of Months 26.11 22.49
Maximum of Months 26.59 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 22.49
February 23.33 22.80
March 23.33 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.33 23.69
     
Annual Sum or Average 23.33 24.91
Minimum of Months 23.33 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.33 22.49
February 23.32 22.80
March 23.32 23.17
April 23.33 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.33 24.76
December 23.33 23.69
     
Annual Sum or Average 23.33 24.91
Minimum of Months 23.32 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.11 22.49
February 25.10 22.80
March 25.13 23.17
April 25.25 23.76
May 25.70 25.23
June 25.77 25.87
July 26.11 26.90
August 26.24 27.06
September 26.24 26.87
October 26.23 26.22
November 25.74 24.76
December 25.44 23.69
     
Annual Sum or Average 25.67 24.91
Minimum of Months 25.10 22.49
Maximum of Months 26.24 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.80 22.49
February 25.88 22.80
March 26.01 23.17
April 26.33 23.76
May 27.19 25.23
June 27.26 25.87
July 27.82 26.90
August 28.06 27.06
September 27.86 26.87
October 27.87 26.22
November 26.85 24.76
December 26.34 23.69
     
Annual Sum or Average 26.95 24.91
Minimum of Months 25.80 22.49
Maximum of Months 28.06 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.87 22.49
February 25.28 22.80
March 25.45 23.17
April 25.56 23.76
May 26.23 25.23
June 26.50 25.87
July 27.01 26.90
August 27.13 27.06
September 27.29 26.87
October 26.70 26.22
November 26.00 24.76
December 25.43 23.69
     
Annual Sum or Average 26.13 24.91
Minimum of Months 24.87 22.49
Maximum of Months 27.29 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.81 22.49
February 23.81 22.80
March 23.81 23.17
April 23.88 23.76
May 23.93 25.23
June 23.94 25.87
July 24.00 26.90
August 24.04 27.06
September 24.03 26.87
October 24.01 26.22
November 23.91 24.76
December 23.87 23.69
     
Annual Sum or Average 23.92 24.91
Minimum of Months 23.81 22.49
Maximum of Months 24.04 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.88 22.49
February 24.39 22.80
March 24.70 23.17
April 24.97 23.76
May 25.80 25.23
June 26.13 25.87
July 26.63 26.90
August 26.64 27.06
September 26.65 26.87
October 25.88 26.22
November 25.13 24.76
December 24.47 23.69
     
Annual Sum or Average 25.44 24.91
Minimum of Months 23.88 22.49
Maximum of Months 26.65 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.75 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.21 22.49
February 23.18 22.80
March 23.20 23.17
April 23.32 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.30 24.76
December 23.29 23.69
     
Annual Sum or Average 23.29 24.91
Minimum of Months 23.18 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 22.49
February 23.16 22.80
March 23.18 23.17
April 23.31 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.29 24.76
December 23.28 23.69
     
Annual Sum or Average 23.28 24.91
Minimum of Months 23.16 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.75 22.49
February 21.75 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.75 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.19 22.49
February 23.19 22.80
March 23.21 23.17
April 23.31 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.29 24.76
December 23.28 23.69
     
Annual Sum or Average 23.29 24.91
Minimum of Months 23.19 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.25 22.49
February 23.24 22.80
March 23.24 23.17
April 23.32 23.76
May 23.33 25.23
June 23.33 25.87
July 23.33 26.90
August 23.33 27.06
September 23.33 26.87
October 23.33 26.22
November 23.31 24.76
December 23.30 23.69
     
Annual Sum or Average 23.31 24.91
Minimum of Months 23.24 22.49
Maximum of Months 23.33 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.75 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.56 22.49
February 24.60 22.80
March 24.61 23.17
April 24.64 23.76
May 24.87 25.23
June 24.96 25.87
July 25.16 26.90
August 25.21 27.06
September 25.27 26.87
October 25.16 26.22
November 24.95 24.76
December 24.76 23.69
     
Annual Sum or Average 24.90 24.91
Minimum of Months 24.56 22.49
Maximum of Months 25.27 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.75 23.17
April 21.75 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.75 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.76 22.49
February 21.76 22.80
March 21.76 23.17
April 21.76 23.76
May 21.76 25.23
June 21.76 25.87
July 21.76 26.90
August 21.76 27.06
September 21.76 26.87
October 21.76 26.22
November 21.76 24.76
December 21.76 23.69
     
Annual Sum or Average 21.76 24.91
Minimum of Months 21.76 22.49
Maximum of Months 21.76 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.91 22.49
February 24.95 22.80
March 25.02 23.17
April 25.19 23.76
May 25.71 25.23
June 25.81 25.87
July 26.18 26.90
August 26.31 27.06
September 26.26 26.87
October 26.19 26.22
November 25.62 24.76
December 25.27 23.69
     
Annual Sum or Average 25.62 24.91
Minimum of Months 24.91 22.49
Maximum of Months 26.31 27.06



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:42

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.66 22.49
February 25.80 22.80
March 25.97 23.17
April 26.32 23.76
May 27.28 25.23
June 27.37 25.87
July 27.97 26.90
August 28.21 27.06
September 27.96 26.87
October 27.92 26.22
November 26.80 24.76
December 26.25 23.69
     
Annual Sum or Average 26.97 24.91
Minimum of Months 25.66 22.49
Maximum of Months 28.21 27.06



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:42

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.162056E+12 97032.568 01-JAN-08:00 17938.723 43276.576 9108.019 0.000 26701.138 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.150306E+12 101135.256 18-FEB-08:00 17938.723 43276.576 9108.019 0.000 30803.825 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.164841E+12 96080.171 04-MAR-08:00 17938.723 43276.576 9108.019 0.000 25748.740 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.159933E+12 94920.466 08-APR-07:00 17938.723 43276.576 9108.019 0.000 24589.036 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.173350E+12 99840.365 13-MAY-07:00 17938.723 43276.576 9108.019 0.000 29508.935 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.170762E+12 100292.105 30-JUN-07:00 17938.723 43276.576 9108.019 0.000 29960.675 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.182309E+12 102273.157 15-JUL-07:00 17938.723 43276.576 9108.019 0.000 31941.727 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.182723E+12 103055.692 19-AUG-07:00 17938.723 43276.576 9108.019 0.000 32724.261 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.178605E+12 104234.093 03-SEP-07:00 17938.723 43276.576 9108.019 0.000 33902.662 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.180857E+12 103197.468 07-OCT-07:00 17938.723 43276.576 9108.019 0.000 32866.038 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.168525E+12 103620.455 22-NOV-08:00 17938.723 43276.576 9108.019 0.000 33289.025 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.168667E+12 102332.228 01-DEC-08:00 17938.723 43276.576 9108.019 0.000 32000.797 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.204293E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.150306E+12 94920.466   17938.723 43276.576 9108.019 0.000 24589.036 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.182723E+12 104234.093   17938.723 43276.576 9108.019 0.000 33902.662 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:42

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.776708E+11 72950.254 16-JAN-09:15 0.000 40096.028 0.000 32854.226 32854.226 32854.226 0.000
February 0.700560E+11 72932.136 01-FEB-09:15 0.000 40096.028 0.000 32836.108 32836.108 32836.108 0.000
March 0.772192E+11 72818.171 02-MAR-09:15 0.000 40096.028 0.000 32722.143 32722.143 32722.143 0.000
April 0.742593E+11 72555.664 05-APR-08:15 0.000 40096.028 0.000 32459.636 32459.636 32459.636 0.000
May 0.762258E+11 72252.152 07-MAY-08:15 0.000 40096.028 0.000 32156.124 32156.124 32156.124 0.000
June 0.733960E+11 72010.498 01-JUN-08:45 0.000 40096.028 0.000 31914.470 31914.470 31914.470 0.000
July 0.756838E+11 71917.231 02-JUL-08:15 0.000 40096.028 0.000 31821.203 31821.203 31821.203 0.000
August 0.757923E+11 72000.718 27-AUG-08:15 0.000 40096.028 0.000 31904.690 31904.690 31904.690 0.000
September 0.736796E+11 72245.647 30-SEP-08:15 0.000 40096.028 0.000 32149.619 32149.619 32149.619 0.000
October 0.766315E+11 72537.577 30-OCT-08:15 0.000 40096.028 0.000 32441.549 32441.549 32441.549 0.000
November 0.746469E+11 72787.163 29-NOV-09:15 0.000 40096.028 0.000 32691.135 32691.135 32691.135 0.000
December 0.775158E+11 72917.102 31-DEC-09:15 0.000 40096.028 0.000 32821.074 32821.074 32821.074 0.000
                     
Annual Sum or Average 0.902777E+12         0.000        
Minimum of Months 0.700560E+11 71917.231   0.000 40096.028 0.000 31821.203 31821.203 31821.203 0.000
Maximum of Months 0.776708E+11 72950.254   0.000 40096.028 0.000 32854.226 32854.226 32854.226 0.000