Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2018-10-19 10:15:35


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2811.55 700.51 754.76
Net Site Energy 2811.55 700.51 754.76
Total Source Energy 6797.12 1693.53 1824.68
Net Source Energy 6797.12 1693.53 1824.68


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 68.52 31.06 0.00 0.00 0.00 0.00
Cooling 378.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting 415.43 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.90 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 280.77 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 559.00 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1800.00 1011.55 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 68.52 31.06 0.00 0.00 0.00 0.00
Cooling General 378.12 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 415.43 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.90 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 280.77 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 559.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 129.21 0.00 0.00 0.00 0.00 0.00
HVAC 195.34 158.40 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 483.21 271.55 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.92 0.00 0.00 0.00 0.00 0.00
HVAC 181.30 147.02 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 448.48 252.03 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1800.00 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1800.00 100.00
     
Total On-Site and Utility Electric Sources 1800.00 100.00
Total Electricity End Uses 1800.00 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 252.00
Time Setpoint Not Met During Occupied Cooling 4233.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 6023.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.477 0.514 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.55 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 2.848 0.287 0.200     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 4.44 0.00 0.00 4.44 4.44 2.848 0.287 0.200     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 2.848 0.287 0.200     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 2.848 0.287 0.200     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 2.848 0.287 0.200     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 2.848 0.287 0.200     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 2.848 0.287 0.200     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.62_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 2.848 0.287 0.200     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 2.848 0.287 0.200     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 2.848 0.287 0.200     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 2.848 0.287 0.200     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 2.848 0.287 0.200     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.62_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 2.848 0.287 0.200     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.848 0.287 0.200              
North Total or Average           96.82 2.848 0.287 0.200              
Non-North Total or Average           87.38 2.848 0.287 0.200              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7228.15 5077.70 2150.45 0.70 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   19549.17 13216.87 6332.31 0.68 3.80    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   9149.35 6185.72 2963.63 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   15180.40 10896.02 4284.38 0.72 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6977.6 3.33 11.35 12.03 11.43
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 18937.3 3.29 11.23 11.91 11.42
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8863.0 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 14624.8 3.30 11.25 11.93 11.28
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.87 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   20284.83 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   898.07 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   898.07 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1018.46 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1006.52 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   898.00 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.80 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.87 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2546.97 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   898.07 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   3592.27 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   2847.00 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   3592.27 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1021.66 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   982.47 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   3592.02 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   898.00 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   3592.02 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   898.00 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.80 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.87 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   2546.97 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   935.40 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   3592.27 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   2847.00 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   3592.27 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1096.87 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1049.70 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   3592.02 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   898.00 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   3592.02 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   969.64 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.80 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.87 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   3255.18 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1160.57 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   3654.60 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   3000.07 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   3670.20 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1357.47 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1309.26 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   3638.90 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1001.67 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   3596.27 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1234.09 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   309.80 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   3697.84 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   15499.43 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   8299.83 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   6302.24 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.32 361.17 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.79 871.61 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.37 412.70 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.72 791.94 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7671.26 9205.52 0.656 0.787 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
RESTROOMFLR1 452.06 542.47 0.039 0.046 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 33.26 0.01445
MEETINGROOMFLR1 3588.00 4305.60 0.307 0.368 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM101 587.24 704.69 0.070 0.084 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83 0.01445
GUESTROOM102 483.36 580.03 0.057 0.069 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83 0.01445
GUESTROOM103 1092.20 1310.63 0.130 0.156 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
GUESTROOM104 1196.95 1436.34 0.142 0.171 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.12 0.01445
GUESTROOM105 1520.78 1824.94 0.181 0.217 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
EMPLOYEELOUNGEFLR1 5343.32 6411.98 0.457 0.548 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
EXERCISECENTERFLR1 1175.01 1410.02 0.100 0.121 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 33.07 0.01445
FRONTOFFICEFLR1 3144.60 3773.52 0.269 0.322 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM201 830.23 996.28 0.099 0.118 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 34.16 0.01445
GUESTROOM202_205 4120.16 4944.20 0.490 0.587 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83 0.01445
GUESTROOM206_208 3337.62 4005.15 0.397 0.476 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83 0.01445
GUESTROOM209_212 3935.59 4722.71 0.468 0.561 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 33.83 0.01445
GUESTROOM213 1135.93 1363.11 0.135 0.162 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 31.41 0.01445
GUESTROOM214 1294.96 1553.95 0.154 0.185 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
GUESTROOM215_218 9388.77 11266.53 1.115 1.338 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM219 5374.00 6448.80 0.638 0.766 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
GUESTROOM220_223 4420.97 5305.16 0.525 0.630 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM224 1279.35 1535.22 0.152 0.182 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM301 648.75 778.50 0.077 0.093 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01445
GUESTROOM302_305 1543.35 1852.03 0.183 0.220 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 33.64 0.01445
GUESTROOM306_308 1349.28 1619.14 0.160 0.192 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 33.64 0.01445
GUESTROOM309_312 3877.15 4652.58 0.461 0.553 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 33.64 0.01445
GUESTROOM313 632.97 759.56 0.075 0.090 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 31.05 0.01445
GUESTROOM314 1211.01 1453.22 0.144 0.173 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.12 0.01445
GUESTROOM315_318 4802.60 5763.12 0.571 0.685 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM319 1063.22 1275.87 0.126 0.152 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
GUESTROOM320_323 4197.29 5036.75 0.499 0.598 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM324 709.59 851.51 0.084 0.101 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
GUESTROOM401 1441.92 1730.31 0.171 0.206 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40 0.01445
GUESTROOM402_405 2145.65 2574.77 0.255 0.306 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM406_408 1840.00 2208.00 0.219 0.262 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM409_412 4779.58 5735.49 0.568 0.681 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
GUESTROOM413 840.33 1008.40 0.100 0.120 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 33.97 0.01445
GUESTROOM414 943.42 1132.11 0.112 0.134 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.26 0.01445
GUESTROOM415_418 5238.67 6286.41 0.622 0.747 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 34.40 0.01445
GUESTROOM419 1447.64 1737.17 0.172 0.206 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 34.40 0.01445
GUESTROOM420_423 5207.59 6249.11 0.619 0.742 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 34.40 0.01445
GUESTROOM424 1489.02 1786.83 0.177 0.212 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40 0.01445
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
CORRIDORFLR1 16067.85 19281.42 1.373 1.648 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 32.12 0.01445
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
CORRIDORFLR2 2646.98 3176.38 0.226 0.271 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.83 0.01445
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
CORRIDORFLR3 1240.54 1488.64 0.106 0.127 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.83 0.01445
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445
CORRIDORFLR4 1925.14 2310.16 0.164 0.197 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 33.97 0.01445
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB   34.40 0.01445


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1492.51 1791.01 0.044 0.236 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:15:00 -6.30 0.00230
RESTROOMFLR1 87.03 104.43 0.003 0.003 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -6.30 0.00230
MEETINGROOMFLR1 511.34 613.61 0.015 0.126 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -6.30 0.00230
GUESTROOM101 215.55 258.66 0.006 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -6.30 0.00230
GUESTROOM102 262.25 314.70 0.008 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -6.30 0.00230
GUESTROOM103 484.35 581.22 0.014 0.017 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -6.30 0.00230
GUESTROOM104 474.42 569.30 0.014 0.017 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -6.30 0.00230
GUESTROOM105 260.20 312.24 0.008 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -6.30 0.00230
EMPLOYEELOUNGEFLR1 230.83 276.99 0.007 0.051 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30 0.00230
EXERCISECENTERFLR1 146.60 175.91 0.004 0.043 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -6.30 0.00230
FRONTOFFICEFLR1 952.37 1142.85 0.028 0.056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -6.30 0.00230
GUESTROOM201 383.60 460.32 0.011 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -6.30 0.00230
GUESTROOM202_205 831.24 997.49 0.024 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -6.30 0.00230
GUESTROOM206_208 647.08 776.49 0.019 0.043 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -6.30 0.00230
GUESTROOM209_212 756.12 907.35 0.022 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -6.30 0.00230
GUESTROOM213 487.01 584.41 0.014 0.017 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -6.30 0.00230
GUESTROOM214 454.38 545.26 0.013 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -6.30 0.00230
GUESTROOM215_218 732.13 878.55 0.021 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -6.30 0.00230
GUESTROOM219 171.76 206.11 0.005 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -6.30 0.00230
GUESTROOM220_223 709.86 851.83 0.021 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -6.30 0.00230
GUESTROOM224 377.43 452.91 0.011 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -6.30 0.00230
GUESTROOM301 415.13 498.15 0.012 0.015 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -6.30 0.00230
GUESTROOM302_305 926.74 1112.09 0.027 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -6.30 0.00230
GUESTROOM306_308 792.73 951.27 0.023 0.043 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -6.30 0.00230
GUESTROOM309_312 927.41 1112.89 0.027 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -6.30 0.00230
GUESTROOM313 549.68 659.62 0.016 0.019 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -6.30 0.00230
GUESTROOM314 510.41 612.49 0.015 0.018 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 15:15:00 -6.30 0.00230
GUESTROOM315_318 900.58 1080.70 0.026 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -6.30 0.00230
GUESTROOM319 252.91 303.49 0.007 0.013 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -6.30 0.00230
GUESTROOM320_323 866.85 1040.22 0.025 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -6.30 0.00230
GUESTROOM324 443.69 532.43 0.013 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -6.30 0.00230
GUESTROOM401 602.77 723.32 0.018 0.021 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:15:00 -6.30 0.00230
GUESTROOM402_405 1588.01 1905.61 0.046 0.056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 21:30:00 -6.30 0.00230
GUESTROOM406_408 1344.95 1613.94 0.039 0.047 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 18:45:00 -6.30 0.00230
GUESTROOM409_412 1601.02 1921.22 0.047 0.056 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -6.30 0.00230
GUESTROOM413 766.86 920.23 0.022 0.027 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -6.30 0.00230
GUESTROOM414 726.70 872.04 0.021 0.025 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 20:15:00 -6.30 0.00230
GUESTROOM415_418 1575.03 1890.04 0.046 0.055 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -6.30 0.00230
GUESTROOM419 470.38 564.45 0.014 0.017 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 18:00:00 -6.30 0.00230
GUESTROOM420_423 1539.51 1847.41 0.045 0.054 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -6.30 0.00230
GUESTROOM424 664.06 796.87 0.019 0.023 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 -6.30 0.00230
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
CORRIDORFLR1 15657.75 18789.30 0.457 0.549 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -6.30 0.00230
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
CORRIDORFLR2 588.10 705.72 0.017 0.038 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -6.30 0.00230
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
CORRIDORFLR3 809.07 970.88 0.024 0.038 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -6.30 0.00230
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230
CORRIDORFLR4 1679.31 2015.18 0.049 0.059 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -6.30 0.00230
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB   -6.30 0.00230


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.32 0.32 0.06 0.06
SAC_FRONTLOUNGE 0.79 0.79 0.24 0.24
SAC_MEETINGROOM 0.37 0.37 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.72 0.72 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialEnthalpy 0.24 0.79 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 3695.25 6717.75 2384.00
RESTROOMFLR1 1111.75 6355.50 418.50
MEETINGROOMFLR1 1915.25 3081.50 933.00
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 1173.75 8692.25 1173.75
GUESTROOM104 465.25 8499.00 465.25
GUESTROOM105 86.50 8071.25 56.25
EMPLOYEELOUNGEFLR1 3074.50 2197.25 365.50
EXERCISECENTERFLR1 2359.00 1961.25 96.00
FRONTOFFICEFLR1 2439.25 5017.75 678.25
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 531.25 8133.25 489.00
GUESTROOM206_208 422.25 8105.75 367.00
GUESTROOM209_212 396.25 8298.00 390.25
GUESTROOM213 1086.75 8458.50 1086.75
GUESTROOM214 225.75 8189.25 209.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 4877.50 3758.75 828.25
GUESTROOM220_223 238.25 8067.00 155.00
GUESTROOM224 196.75 8109.50 179.25
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 735.00 8482.50 735.00
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 514.00 8221.50 499.00
GUESTROOM315_318 319.75 7875.50 102.75
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 323.75 8290.50 299.00
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 2346.25 7854.75 1844.50
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1545.00 7810.00 1016.25
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1118.75 7466.00 403.25
GUESTROOM419 892.00 7609.50 373.75
GUESTROOM420_423 1137.75 7529.75 462.00
GUESTROOM424 1366.00 7744.25 874.25
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7334.50 8759.50 6023.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 67.00 1021.75 67.00 1021.75
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 4.00 51.00 4.00 51.00
GUESTROOM104 1.25 56.75 1.25 56.75
GUESTROOM105 0.00 69.75 0.00 69.75
EMPLOYEELOUNGEFLR1 289.00 1172.75 223.00 589.75
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 1.50 42.00 1.50 42.00
GUESTROOM206_208 1.00 46.75 1.00 46.75
GUESTROOM209_212 1.00 41.00 1.00 41.00
GUESTROOM213 5.00 41.00 5.00 41.00
GUESTROOM214 0.50 46.50 0.50 46.50
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 3498.75 0.00 3498.75
GUESTROOM220_223 0.00 44.50 0.00 44.50
GUESTROOM224 0.50 46.25 0.50 46.25
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 2.75 40.50 2.75 40.50
GUESTROOM313 0.25 0.00 0.00 0.00
GUESTROOM314 1.50 44.50 1.50 44.50
GUESTROOM315_318 0.00 45.75 0.00 45.75
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.25 43.25 0.25 43.25
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 15.00 47.75 15.00 47.75
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 4.50 45.50 4.50 45.50
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 1.25 50.50 1.25 50.50
GUESTROOM419 1.25 53.75 1.25 53.75
GUESTROOM420_423 1.50 48.50 1.50 48.50
GUESTROOM424 2.00 51.00 2.00 51.00
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 2.25 4725.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 523.75 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 3.50 388.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 314.25 5866.00 252.00 4233.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:35

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.322439
SAC_FRONTLOUNGE SUPPLY FAN 0.787245
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.715293


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 309.87
CORRIDORFLR1 PTAC HEATING COIL 20284.83
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 898.07
102 PTAC HEATING COIL 898.07
103 PTAC HEATING COIL 1018.46
104 PTAC HEATING COIL 1006.52
105 PTAC HEATING COIL 898.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 309.80
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 309.87
CORRIDORFLR2 PTAC HEATING COIL 2546.97
201 PTAC HEATING COIL 898.07
202_205 PTAC HEATING COIL 3592.27
206_208 PTAC HEATING COIL 2847.00
209_212 PTAC HEATING COIL 3592.27
213 PTAC HEATING COIL 1021.66
214 PTAC HEATING COIL 982.47
215_218 PTAC HEATING COIL 3592.02
219 PTAC HEATING COIL 898.00
220_223 PTAC HEATING COIL 3592.02
224 PTAC HEATING COIL 898.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 309.80
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 309.87
CORRIDORFLR3 PTAC HEATING COIL 2546.97
301 PTAC HEATING COIL 935.40
302_305 PTAC HEATING COIL 3592.27
306_308 PTAC HEATING COIL 2847.00
309_312 PTAC HEATING COIL 3592.27
313 PTAC HEATING COIL 1096.87
314 PTAC HEATING COIL 1049.70
315_318 PTAC HEATING COIL 3592.02
319 PTAC HEATING COIL 898.00
320_323 PTAC HEATING COIL 3592.02
324 PTAC HEATING COIL 969.64
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 309.80
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 309.87
CORRIDORFLR4 PTAC HEATING COIL 3255.18
401 PTAC HEATING COIL 1160.57
402_405 PTAC HEATING COIL 3654.60
406_408 PTAC HEATING COIL 3000.07
409_412 PTAC HEATING COIL 3670.20
413 PTAC HEATING COIL 1357.47
414 PTAC HEATING COIL 1309.26
415_418 PTAC HEATING COIL 3638.90
419 PTAC HEATING COIL 1001.67
420_423 PTAC HEATING COIL 3596.27
424 PTAC HEATING COIL 1234.09
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 309.80


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.702489 0.322439 7228.15
SAC_FRONTLOUNGE COOLING COIL 0.676083 0.787245 19549.17
SAC_MEETINGROOM COOLING COIL 0.676083 0.368444 9149.35
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.717769 0.715293 15180.40


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.787245
RESTROOMFLR1 DIRECT AIR 0.046345
MEETINGROOMFLR1 DIRECT AIR 0.368444
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.548419
EXERCISECENTERFLR1 DIRECT AIR 0.120529
FRONTOFFICEFLR1 DIRECT AIR 0.322439


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.322439
SAC_FRONTLOUNGE MAIN BRANCH 0.787245
SAC_MEETINGROOM MAIN BRANCH 0.368444
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.715293


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.322439
SAC_FRONTLOUNGE 0.787245
SAC_MEETINGROOM 0.368444
SAC_EXC_EMPLGE_RESTRM 0.715293


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.322439 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.787245 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.368444 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.715293 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.322439 0.322439 0.322439 0.322439 3697.84 7228.15 1.00
SAC_FRONTLOUNGE 0.787245 0.787245 0.787245 0.787245 15499.43 19549.17 1.00
SAC_MEETINGROOM 0.368444 0.368444 0.368444 0.368444 8299.83 9149.35 1.00
SAC_EXC_EMPLGE_RESTRM 0.715293 0.715293 0.715293 0.715293 6302.24 15180.40 0.168503


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 3697.84
SAC_FRONTLOUNGE HEATING COIL 15499.43
SAC_MEETINGROOM HEATING COIL 8299.83
SAC_EXC_EMPLGE_RESTRM HEATING COIL 6302.24


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.368444


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.09 3.96
February 19.06 7.94
March 21.25 13.76
April 22.51 17.21
May 23.57 20.84
June 24.69 24.80
July 25.02 26.06
August 25.25 26.55
September 24.07 22.53
October 22.15 16.03
November 20.82 11.94
December 19.15 7.70
     
Annual Sum or Average 22.15 16.65
Minimum of Months 18.09 3.96
Maximum of Months 25.25 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.88 3.96
February 23.36 7.94
March 24.18 13.76
April 24.84 17.21
May 25.57 20.84
June 26.43 24.80
July 26.82 26.06
August 26.99 26.55
September 25.98 22.53
October 24.70 16.03
November 23.99 11.94
December 23.36 7.70
     
Annual Sum or Average 24.93 16.65
Minimum of Months 22.88 3.96
Maximum of Months 26.99 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.42 3.96
February 18.41 7.94
March 20.61 13.76
April 21.95 17.21
May 23.08 20.84
June 24.21 24.80
July 24.51 26.06
August 24.65 26.55
September 23.44 22.53
October 21.46 16.03
November 20.07 11.94
December 18.44 7.70
     
Annual Sum or Average 21.54 16.65
Minimum of Months 17.42 3.96
Maximum of Months 24.65 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.27 3.96
February 21.66 7.94
March 22.26 13.76
April 22.90 17.21
May 23.44 20.84
June 23.77 24.80
July 23.86 26.06
August 23.89 26.55
September 23.65 22.53
October 22.67 16.03
November 22.05 11.94
December 21.39 7.70
     
Annual Sum or Average 22.74 16.65
Minimum of Months 21.27 3.96
Maximum of Months 23.89 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.79 3.96
February 22.14 7.94
March 22.75 13.76
April 23.14 17.21
May 23.49 20.84
June 23.73 24.80
July 23.81 26.06
August 23.80 26.55
September 23.56 22.53
October 23.02 16.03
November 22.57 11.94
December 22.10 7.70
     
Annual Sum or Average 23.00 16.65
Minimum of Months 21.79 3.96
Maximum of Months 23.81 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.61 3.96
February 22.18 7.94
March 22.98 13.76
April 23.47 17.21
May 23.74 20.84
June 23.87 24.80
July 23.89 26.06
August 23.89 26.55
September 23.86 22.53
October 23.37 16.03
November 22.83 11.94
December 22.01 7.70
     
Annual Sum or Average 23.15 16.65
Minimum of Months 21.61 3.96
Maximum of Months 23.89 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.14 3.96
February 24.59 7.94
March 25.43 13.76
April 25.97 17.21
May 26.62 20.84
June 28.99 24.80
July 30.60 26.06
August 30.68 26.55
September 29.18 22.53
October 26.51 16.03
November 25.34 11.94
December 24.64 7.70
     
Annual Sum or Average 26.90 16.65
Minimum of Months 24.14 3.96
Maximum of Months 30.68 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.77 3.96
February 20.59 7.94
March 21.88 13.76
April 22.59 17.21
May 23.12 20.84
June 23.31 24.80
July 23.33 26.06
August 23.33 26.55
September 23.30 22.53
October 22.45 16.03
November 21.56 11.94
December 20.47 7.70
     
Annual Sum or Average 22.15 16.65
Minimum of Months 19.77 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.54 3.96
February 20.32 7.94
March 21.57 13.76
April 22.35 17.21
May 22.96 20.84
June 23.25 24.80
July 23.32 26.06
August 23.33 26.55
September 23.17 22.53
October 22.13 16.03
November 21.22 11.94
December 20.14 7.70
     
Annual Sum or Average 21.95 16.65
Minimum of Months 19.54 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.79 3.96
February 21.04 7.94
March 21.42 13.76
April 21.64 17.21
May 21.74 20.84
June 21.75 24.80
July 21.75 26.06
August 21.75 26.55
September 21.75 22.53
October 21.57 16.03
November 21.38 11.94
December 21.04 7.70
     
Annual Sum or Average 21.47 16.65
Minimum of Months 20.79 3.96
Maximum of Months 21.75 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.14 3.96
February 21.31 7.94
March 21.58 13.76
April 21.69 17.21
May 21.74 20.84
June 21.75 24.80
July 21.75 26.06
August 21.76 26.55
September 21.75 22.53
October 21.67 16.03
November 21.60 11.94
December 21.38 7.70
     
Annual Sum or Average 21.60 16.65
Minimum of Months 21.14 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.49 3.96
February 21.58 7.94
March 21.70 13.76
April 21.74 17.21
May 21.75 20.84
June 21.75 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.73 16.03
November 21.71 11.94
December 21.64 7.70
     
Annual Sum or Average 21.70 16.65
Minimum of Months 21.49 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.24 3.96
February 22.39 7.94
March 22.55 13.76
April 22.58 17.21
May 22.59 20.84
June 22.37 24.80
July 22.27 26.06
August 22.20 26.55
September 22.43 22.53
October 22.53 16.03
November 22.42 11.94
December 22.33 7.70
     
Annual Sum or Average 22.41 16.65
Minimum of Months 22.20 3.96
Maximum of Months 22.59 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 51.02 3.96
February 51.32 7.94
March 51.99 13.76
April 52.32 17.21
May 52.67 20.84
June 53.04 24.80
July 53.24 26.06
August 53.37 26.55
September 52.99 22.53
October 52.39 16.03
November 51.94 11.94
December 51.41 7.70
     
Annual Sum or Average 52.31 16.65
Minimum of Months 51.02 3.96
Maximum of Months 53.37 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 68.08 3.96
February 68.39 7.94
March 69.26 13.76
April 69.81 17.21
May 70.32 20.84
June 70.78 24.80
July 71.07 26.06
August 71.19 26.55
September 70.71 22.53
October 69.80 16.03
November 69.22 11.94
December 68.52 7.70
     
Annual Sum or Average 69.77 16.65
Minimum of Months 68.08 3.96
Maximum of Months 71.19 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.92 3.96
February 23.17 7.94
March 23.56 13.76
April 23.72 17.21
May 23.86 20.84
June 23.88 24.80
July 23.89 26.06
August 23.89 26.55
September 23.88 22.53
October 23.70 16.03
November 23.44 11.94
December 23.15 7.70
     
Annual Sum or Average 23.59 16.65
Minimum of Months 22.92 3.96
Maximum of Months 23.89 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.31 3.96
February 22.77 7.94
March 23.45 13.76
April 23.69 17.21
May 23.86 20.84
June 23.88 24.80
July 23.89 26.06
August 23.89 26.55
September 23.88 22.53
October 23.67 16.03
November 23.29 11.94
December 22.72 7.70
     
Annual Sum or Average 23.44 16.65
Minimum of Months 22.31 3.96
Maximum of Months 23.89 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.60 3.96
February 18.77 7.94
March 21.22 13.76
April 22.70 17.21
May 23.93 20.84
June 25.31 24.80
July 25.70 26.06
August 25.92 26.55
September 24.60 22.53
October 22.34 16.03
November 20.77 11.94
December 18.86 7.70
     
Annual Sum or Average 22.33 16.65
Minimum of Months 17.60 3.96
Maximum of Months 25.92 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.28 3.96
February 21.01 7.94
March 22.49 13.76
April 23.29 17.21
May 23.96 20.84
June 24.71 24.80
July 24.95 26.06
August 25.10 26.55
September 24.39 22.53
October 23.18 16.03
November 22.27 11.94
December 21.10 7.70
     
Annual Sum or Average 23.07 16.65
Minimum of Months 20.28 3.96
Maximum of Months 25.10 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.77 3.96
February 18.94 7.94
March 21.54 13.76
April 23.01 17.21
May 24.18 20.84
June 25.41 24.80
July 25.75 26.06
August 25.97 26.55
September 24.70 22.53
October 22.52 16.03
November 21.02 11.94
December 19.04 7.70
     
Annual Sum or Average 22.51 16.65
Minimum of Months 17.77 3.96
Maximum of Months 25.97 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.05 3.96
February 22.66 7.94
March 23.60 13.76
April 23.81 17.21
May 23.89 20.84
June 23.94 24.80
July 24.01 26.06
August 24.03 26.55
September 23.90 22.53
October 23.77 16.03
November 23.43 11.94
December 22.65 7.70
     
Annual Sum or Average 23.48 16.65
Minimum of Months 22.05 3.96
Maximum of Months 24.03 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.45 3.96
February 17.73 7.94
March 20.47 13.76
April 22.14 17.21
May 23.46 20.84
June 24.78 24.80
July 25.10 26.06
August 25.26 26.55
September 23.87 22.53
October 21.47 16.03
November 19.77 11.94
December 17.70 7.70
     
Annual Sum or Average 21.54 16.65
Minimum of Months 16.45 3.96
Maximum of Months 25.26 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.27 3.96
February 20.15 7.94
March 21.55 13.76
April 22.59 17.21
May 23.19 20.84
June 23.31 24.80
July 23.33 26.06
August 23.33 26.55
September 23.26 22.53
October 22.18 16.03
November 20.99 11.94
December 19.66 7.70
     
Annual Sum or Average 21.91 16.65
Minimum of Months 19.27 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.93 3.96
February 21.20 7.94
March 21.57 13.76
April 21.72 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.68 16.03
November 21.53 11.94
December 21.19 7.70
     
Annual Sum or Average 21.55 16.65
Minimum of Months 20.93 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.97 3.96
February 21.24 7.94
March 21.59 13.76
April 21.72 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.69 16.03
November 21.55 11.94
December 21.24 7.70
     
Annual Sum or Average 21.57 16.65
Minimum of Months 20.97 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.00 3.96
February 21.26 7.94
March 21.61 13.76
April 21.72 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.69 16.03
November 21.58 11.94
December 21.28 7.70
     
Annual Sum or Average 21.58 16.65
Minimum of Months 21.00 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.76 3.96
February 21.05 7.94
March 21.46 13.76
April 21.68 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.61 16.03
November 21.40 11.94
December 21.01 7.70
     
Annual Sum or Average 21.48 16.65
Minimum of Months 20.76 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.20 3.96
February 21.37 7.94
March 21.66 13.76
April 21.73 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.71 16.03
November 21.66 11.94
December 21.45 7.70
     
Annual Sum or Average 21.63 16.65
Minimum of Months 21.20 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.00 3.96
February 23.11 7.94
March 23.32 13.76
April 23.33 17.21
May 23.33 20.84
June 23.33 24.80
July 23.33 26.06
August 23.33 26.55
September 23.33 22.53
October 23.33 16.03
November 23.30 11.94
December 23.21 7.70
     
Annual Sum or Average 23.27 16.65
Minimum of Months 23.00 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 30.81 3.96
February 31.30 7.94
March 32.30 13.76
April 32.81 17.21
May 33.20 20.84
June 33.58 24.80
July 33.77 26.06
August 33.88 26.55
September 33.46 22.53
October 32.74 16.03
November 32.16 11.94
December 31.34 7.70
     
Annual Sum or Average 32.62 16.65
Minimum of Months 30.81 3.96
Maximum of Months 33.88 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 3.96
February 22.05 7.94
March 22.32 13.76
April 22.54 17.21
May 22.77 20.84
June 23.14 24.80
July 23.38 26.06
August 23.52 26.55
September 22.99 22.53
October 22.56 16.03
November 22.25 11.94
December 22.01 7.70
     
Annual Sum or Average 22.62 16.65
Minimum of Months 21.89 3.96
Maximum of Months 23.52 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.36 3.96
February 21.49 7.94
March 21.69 13.76
April 21.74 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.73 16.03
November 21.70 11.94
December 21.57 7.70
     
Annual Sum or Average 21.67 16.65
Minimum of Months 21.36 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.19 3.96
February 21.37 7.94
March 21.66 13.76
April 21.73 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.76 22.53
October 21.72 16.03
November 21.66 11.94
December 21.45 7.70
     
Annual Sum or Average 21.63 16.65
Minimum of Months 21.19 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.42 3.96
February 20.39 7.94
March 22.34 13.76
April 23.41 17.21
May 24.24 20.84
June 25.13 24.80
July 25.38 26.06
August 25.52 26.55
September 24.68 22.53
October 23.13 16.03
November 22.00 11.94
December 20.47 7.70
     
Annual Sum or Average 23.02 16.65
Minimum of Months 19.42 3.96
Maximum of Months 25.52 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.73 3.96
February 18.24 7.94
March 21.35 13.76
April 23.23 17.21
May 24.69 20.84
June 26.31 24.80
July 26.75 26.06
August 26.95 26.55
September 25.40 22.53
October 22.63 16.03
November 20.73 11.94
December 18.32 7.70
     
Annual Sum or Average 22.63 16.65
Minimum of Months 16.73 3.96
Maximum of Months 26.95 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.01 3.96
February 18.34 7.94
March 21.22 13.76
April 22.91 17.21
May 24.25 20.84
June 25.59 24.80
July 25.95 26.06
August 26.17 26.55
September 24.79 22.53
October 22.31 16.03
November 20.60 11.94
December 18.38 7.70
     
Annual Sum or Average 22.31 16.65
Minimum of Months 17.01 3.96
Maximum of Months 26.17 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.32 3.96
February 21.92 7.94
March 22.87 13.76
April 23.52 17.21
May 23.84 20.84
June 23.88 24.80
July 23.89 26.06
August 23.89 26.55
September 23.87 22.53
October 23.27 16.03
November 22.55 11.94
December 21.58 7.70
     
Annual Sum or Average 23.04 16.65
Minimum of Months 21.32 3.96
Maximum of Months 23.89 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.34 3.96
February 16.84 7.94
March 19.96 13.76
April 22.00 17.21
May 23.60 20.84
June 25.07 24.80
July 25.44 26.06
August 25.60 26.55
September 24.04 22.53
October 21.14 16.03
November 19.08 11.94
December 16.69 7.70
     
Annual Sum or Average 21.26 16.65
Minimum of Months 15.34 3.96
Maximum of Months 25.60 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.08 3.96
February 19.82 7.94
March 21.06 13.76
April 22.33 17.21
May 23.11 20.84
June 23.29 24.80
July 23.33 26.06
August 23.33 26.55
September 23.20 22.53
October 21.77 16.03
November 20.43 11.94
December 19.27 7.70
     
Annual Sum or Average 21.68 16.65
Minimum of Months 19.08 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.14 3.96
February 19.93 7.94
March 21.22 13.76
April 22.42 17.21
May 23.16 20.84
June 23.30 24.80
July 23.33 26.06
August 23.33 26.55
September 23.24 22.53
October 21.90 16.03
November 20.62 11.94
December 19.40 7.70
     
Annual Sum or Average 21.76 16.65
Minimum of Months 19.14 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.18 3.96
February 19.99 7.94
March 21.29 13.76
April 22.43 17.21
May 23.14 20.84
June 23.30 24.80
July 23.33 26.06
August 23.33 26.55
September 23.23 22.53
October 21.93 16.03
November 20.71 11.94
December 19.47 7.70
     
Annual Sum or Average 21.79 16.65
Minimum of Months 19.18 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.90 3.96
February 21.18 7.94
March 21.55 13.76
April 21.70 17.21
May 21.75 20.84
June 21.75 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.66 16.03
November 21.51 11.94
December 21.18 7.70
     
Annual Sum or Average 21.54 16.65
Minimum of Months 20.90 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.13 3.96
February 19.87 7.94
March 21.17 13.76
April 22.38 17.21
May 23.13 20.84
June 23.30 24.80
July 23.33 26.06
August 23.33 26.55
September 23.22 22.53
October 21.87 16.03
November 20.60 11.94
December 19.37 7.70
     
Annual Sum or Average 21.73 16.65
Minimum of Months 19.13 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.01 3.96
February 21.22 7.94
March 21.58 13.76
April 21.71 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.67 16.03
November 21.57 11.94
December 21.28 7.70
     
Annual Sum or Average 21.57 16.65
Minimum of Months 21.01 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.39 3.96
February 21.51 7.94
March 21.70 13.76
April 21.74 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.73 16.03
November 21.70 11.94
December 21.60 7.70
     
Annual Sum or Average 21.68 16.65
Minimum of Months 21.39 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.70 3.96
February 23.38 7.94
March 24.69 13.76
April 25.39 17.21
May 25.87 20.84
June 26.25 24.80
July 26.38 26.06
August 26.46 26.55
September 26.07 22.53
October 25.19 16.03
November 24.43 11.94
December 23.36 7.70
     
Annual Sum or Average 25.02 16.65
Minimum of Months 22.70 3.96
Maximum of Months 26.46 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.31 3.96
February 21.98 7.94
March 23.00 13.76
April 23.23 17.21
May 23.33 20.84
June 23.33 24.80
July 23.33 26.06
August 23.33 26.55
September 23.33 22.53
October 23.18 16.03
November 22.85 11.94
December 22.09 7.70
     
Annual Sum or Average 22.86 16.65
Minimum of Months 21.31 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.24 3.96
February 21.40 7.94
March 21.65 13.76
April 21.73 17.21
May 21.75 20.84
June 21.75 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.71 16.03
November 21.66 11.94
December 21.48 7.70
     
Annual Sum or Average 21.64 16.65
Minimum of Months 21.24 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.69 3.96
February 20.56 7.94
March 22.05 13.76
April 22.74 17.21
May 23.19 20.84
June 23.31 24.80
July 23.33 26.06
August 23.33 26.55
September 23.27 22.53
October 22.52 16.03
November 21.74 11.94
December 20.39 7.70
     
Annual Sum or Average 22.18 16.65
Minimum of Months 19.69 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.37 3.96
February 19.57 7.94
March 21.95 13.76
April 23.31 17.21
May 24.35 20.84
June 25.38 24.80
July 25.65 26.06
August 25.80 26.55
September 24.81 22.53
October 22.88 16.03
November 21.45 11.94
December 19.57 7.70
     
Annual Sum or Average 22.77 16.65
Minimum of Months 18.37 3.96
Maximum of Months 25.80 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.80 3.96
February 17.52 7.94
March 21.01 13.76
April 23.16 17.21
May 24.83 20.84
June 26.59 24.80
July 27.07 26.06
August 27.26 26.55
September 25.55 22.53
October 22.41 16.03
November 20.24 11.94
December 17.54 7.70
     
Annual Sum or Average 22.44 16.65
Minimum of Months 15.80 3.96
Maximum of Months 27.26 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.81 3.96
February 17.41 7.94
March 20.69 13.76
April 22.69 17.21
May 24.36 20.84
June 25.91 24.80
July 26.34 26.06
August 26.56 26.55
September 24.87 22.53
October 21.89 16.03
November 19.82 11.94
December 17.31 7.70
     
Annual Sum or Average 21.99 16.65
Minimum of Months 15.81 3.96
Maximum of Months 26.56 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.24 3.96
February 21.65 7.94
March 22.40 13.76
April 23.07 17.21
May 23.59 20.84
June 23.88 24.80
July 23.99 26.06
August 24.00 26.55
September 23.73 22.53
October 22.72 16.03
November 22.07 11.94
December 21.38 7.70
     
Annual Sum or Average 22.82 16.65
Minimum of Months 21.24 3.96
Maximum of Months 24.00 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.50 3.96
February 16.17 7.94
March 19.53 13.76
April 21.80 17.21
May 23.66 20.84
June 25.31 24.80
July 25.74 26.06
August 25.90 26.55
September 24.06 22.53
October 20.76 16.03
November 18.45 11.94
December 15.92 7.70
     
Annual Sum or Average 21.01 16.65
Minimum of Months 14.50 3.96
Maximum of Months 25.90 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 3.96
February 20.94 7.94
March 21.36 13.76
April 21.65 17.21
May 21.74 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.50 16.03
November 21.27 11.94
December 20.80 7.70
     
Annual Sum or Average 21.41 16.65
Minimum of Months 20.63 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.08 3.96
February 19.70 7.94
March 20.83 13.76
April 22.02 17.21
May 22.91 20.84
June 23.24 24.80
July 23.32 26.06
August 23.33 26.55
September 23.08 22.53
October 21.40 16.03
November 20.25 11.94
December 19.24 7.70
     
Annual Sum or Average 21.54 16.65
Minimum of Months 19.08 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.09 3.96
February 19.73 7.94
March 20.86 13.76
April 22.01 17.21
May 22.89 20.84
June 23.23 24.80
July 23.32 26.06
August 23.33 26.55
September 23.07 22.53
October 21.40 16.03
November 20.28 11.94
December 19.26 7.70
     
Annual Sum or Average 21.55 16.65
Minimum of Months 19.09 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 3.96
February 21.11 7.94
March 21.52 13.76
April 21.70 17.21
May 21.75 20.84
June 21.75 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.63 16.03
November 21.47 11.94
December 21.09 7.70
     
Annual Sum or Average 21.51 16.65
Minimum of Months 20.81 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.07 3.96
February 19.70 7.94
March 20.85 13.76
April 22.06 17.21
May 22.92 20.84
June 23.25 24.80
July 23.32 26.06
August 23.33 26.55
September 23.09 22.53
October 21.45 16.03
November 20.27 11.94
December 19.23 7.70
     
Annual Sum or Average 21.55 16.65
Minimum of Months 19.07 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.41 3.96
February 20.16 7.94
March 21.46 13.76
April 22.31 17.21
May 22.98 20.84
June 23.25 24.80
July 23.32 26.06
August 23.33 26.55
September 23.14 22.53
October 21.95 16.03
November 21.03 11.94
December 19.84 7.70
     
Annual Sum or Average 21.86 16.65
Minimum of Months 19.41 3.96
Maximum of Months 23.33 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.21 3.96
February 21.37 7.94
March 21.63 13.76
April 21.72 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.69 16.03
November 21.64 11.94
December 21.47 7.70
     
Annual Sum or Average 21.63 16.65
Minimum of Months 21.21 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.39 3.96
February 21.17 7.94
March 22.63 13.76
April 23.52 17.21
May 24.23 20.84
June 24.81 24.80
July 24.98 26.06
August 25.05 26.55
September 24.39 22.53
October 23.16 16.03
November 22.22 11.94
December 21.07 7.70
     
Annual Sum or Average 23.15 16.65
Minimum of Months 20.39 3.96
Maximum of Months 25.05 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.16 3.96
February 21.34 7.94
March 21.63 13.76
April 21.72 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.69 16.03
November 21.64 11.94
December 21.43 7.70
     
Annual Sum or Average 21.62 16.65
Minimum of Months 21.16 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 3.96
February 21.35 7.94
March 21.62 13.76
April 21.72 17.21
May 21.75 20.84
June 21.75 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.69 16.03
November 21.63 11.94
December 21.44 7.70
     
Annual Sum or Average 21.62 16.65
Minimum of Months 21.18 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.95 3.96
February 21.17 7.94
March 21.55 13.76
April 21.70 17.21
May 21.75 20.84
June 21.76 24.80
July 21.76 26.06
August 21.76 26.55
September 21.75 22.53
October 21.65 16.03
November 21.55 11.94
December 21.23 7.70
     
Annual Sum or Average 21.55 16.65
Minimum of Months 20.95 3.96
Maximum of Months 21.76 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.80 3.96
February 19.10 7.94
March 21.58 13.76
April 23.07 17.21
May 24.28 20.84
June 25.43 24.80
July 25.74 26.06
August 25.87 26.55
September 24.63 22.53
October 22.50 16.03
November 20.95 11.94
December 19.03 7.70
     
Annual Sum or Average 22.52 16.65
Minimum of Months 17.80 3.96
Maximum of Months 25.87 26.55



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:35

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.98 3.96
February 16.87 7.94
March 20.58 13.76
April 22.93 17.21
May 24.83 20.84
June 26.75 24.80
July 27.28 26.06
August 27.46 26.55
September 25.45 22.53
October 22.00 16.03
November 19.63 11.94
December 16.80 7.70
     
Annual Sum or Average 22.16 16.65
Minimum of Months 14.98 3.96
Maximum of Months 27.46 26.55



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:35

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.150144E+12 112590.335 08-JAN-07:15 15177.258 39465.561 8731.081 44829.304 191.017 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.130288E+12 131494.183 12-FEB-07:15 15177.258 39465.561 8755.012 63760.573 139.665 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.135484E+12 87575.217 19-MAR-06:45 15177.258 39465.561 8725.136 18299.773 1711.376 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.138208E+12 87624.226 06-APR-06:15 15177.258 39465.561 8725.136 18524.395 1535.763 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.153535E+12 89764.364 26-MAY-07:00 17566.637 43276.576 9137.833 0.000 19775.206 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.163805E+12 96551.526 23-JUN-07:00 17641.054 43276.576 9137.833 0.000 26487.951 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.177722E+12 101799.045 07-JUL-07:00 17789.888 43276.576 9137.833 0.000 31586.635 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.181128E+12 102043.661 19-AUG-07:00 17566.637 43276.576 9137.833 0.000 32054.503 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.156862E+12 96136.286 09-SEP-07:00 17789.888 43276.576 9137.833 0.000 25923.876 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.142332E+12 86825.896 26-OCT-06:30 15177.258 39465.561 8725.136 17298.191 1963.637 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.132009E+12 99687.944 21-NOV-07:15 15177.258 39465.561 8725.136 31725.331 398.545 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.138483E+12 108452.814 18-DEC-07:15 15177.258 39465.561 8725.136 40628.795 259.951 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.180000E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.130288E+12 86825.896   15177.258 39465.561 8725.136 0.000 139.665 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.181128E+12 131494.183   17789.888 43276.576 9137.833 63760.573 32054.503 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:35

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.102163E+12 106028.929 07-JAN-10:15 11721.774 40096.028 0.000 54211.128 54211.128 54211.128 11721.774
February 0.884303E+11 104825.298 03-FEB-10:00 10251.611 40096.028 0.000 54477.660 54477.660 54477.660 10251.611
March 0.893672E+11 95979.063 18-MAR-09:30 3880.496 40096.028 0.000 52002.539 52002.539 52002.539 3880.496
April 0.825693E+11 92409.792 01-APR-08:15 0.000 40096.028 0.000 52313.764 52313.764 52313.764 0.000
May 0.811849E+11 89586.583 02-MAY-08:45 0.000 40096.028 0.000 49490.555 49490.555 49490.555 0.000
June 0.764960E+11 74080.371 01-JUN-08:00 0.000 40096.028 0.000 33984.343 33984.343 33984.343 0.000
July 0.779628E+11 73323.058 02-JUL-08:15 0.000 40096.028 0.000 33227.029 33227.029 33227.029 0.000
August 0.778875E+11 73235.665 31-AUG-08:15 0.000 40096.028 0.000 33139.637 33139.637 33139.637 0.000
September 0.762970E+11 73942.030 30-SEP-08:45 0.000 40096.028 0.000 33846.002 33846.002 33846.002 0.000
October 0.812732E+11 89837.682 30-OCT-08:15 0.000 40096.028 0.000 49741.654 49741.654 49741.654 0.000
November 0.840734E+11 95384.540 22-NOV-10:15 4691.075 40096.028 0.000 50597.437 50597.437 50597.437 4691.075
December 0.938474E+11 97946.311 02-DEC-10:30 7016.001 40096.028 0.000 50834.282 50834.282 50834.282 7016.001
                     
Annual Sum or Average 0.101155E+13         0.000        
Minimum of Months 0.762970E+11 73235.665   0.000 40096.028 0.000 33139.637 33139.637 33139.637 0.000
Maximum of Months 0.102163E+12 106028.929   11721.774 40096.028 0.000 54477.660 54477.660 54477.660 11721.774