Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2018-10-19 10:15:38


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3427.52 853.98 920.12
Net Site Energy 3427.52 853.98 920.12
Total Source Energy 7998.01 1992.74 2147.06
Net Source Energy 7998.01 1992.74 2147.06


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 540.54 218.10 0.00 0.00 0.00 0.00
Cooling 164.52 0.00 0.00 0.00 0.00 0.00
Interior Lighting 414.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.75 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 279.64 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 731.97 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 2055.96 1371.56 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 540.54 218.10 0.00 0.00 0.00 0.00
Cooling General 164.52 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 414.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.75 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 279.64 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 731.97 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.86 0.00 0.00 0.00 0.00 0.00
HVAC 264.41 255.05 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 551.92 368.19 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.59 0.00 0.00 0.00 0.00 0.00
HVAC 245.40 236.71 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 512.25 341.73 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 2055.96 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 2055.96 100.00
     
Total On-Site and Utility Electric Sources 2055.96 100.00
Total Electricity End Uses 2055.96 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1853.50
Time Setpoint Not Met During Occupied Cooling 2360.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 6513.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod International Falls Intl Ap MN USA TMY3 WMO#=727470
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [m] 359.00
Time Zone -6.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -32.70 0.00 -32.70 Wetbulb [C] 2.40 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 30.10 12.40 21.10 Wetbulb [C] 4.70 200.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.238 0.247 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.238 0.247 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.238 0.247 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.238 0.247 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.238 0.247 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 4.44 0.00 0.00 4.44 4.44 2.670 0.479 0.381     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.69 0.00 0.00 2.69 2.69 2.670 0.479 0.381     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.46_SHGC_0.45 2.97 0.00 0.00 2.97 2.97 2.670 0.479 0.381     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.31 0.00 0.00 1.31 1.31 2.670 0.479 0.381     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 3.41 0.00 0.00 3.41 3.41 2.670 0.479 0.381     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.46_SHGC_0.45 1.65 0.00 0.00 1.65 1.65 2.670 0.479 0.381     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.670 0.479 0.381              
North Total or Average           96.82 2.670 0.479 0.381              
Non-North Total or Average           87.38 2.670 0.479 0.381              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   6576.12 4864.17 1711.95 0.74 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   17305.66 12008.96 5296.70 0.69 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8780.71 5936.49 2844.22 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   13695.99 10270.16 3425.83 0.75 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 6317.1 3.26 11.12 11.78 11.07
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 16724.7 3.34 11.41 12.10 11.51
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8505.9 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13138.9 3.24 11.05 11.71 10.97
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   307.99 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   43440.33 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1311.17 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1357.78 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1731.35 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1743.65 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1370.81 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   307.91 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   307.99 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   3718.56 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1514.24 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   5244.69 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   4156.60 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   5244.69 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1689.50 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1661.31 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   5244.32 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1311.08 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   5244.32 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1524.03 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   594.96 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   307.99 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3961.29 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1570.40 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   5244.69 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   4213.89 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   5244.69 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1807.19 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1762.38 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   5244.32 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1344.66 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   5244.32 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1619.54 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   594.96 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   595.11 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   5948.04 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   2015.29 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   6713.62 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   5513.58 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6737.60 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2329.84 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   2272.53 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   6744.66 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1842.69 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   6685.52 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   2112.84 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   717.75 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   5398.83 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   22629.09 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   12117.71 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   9282.00 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.79 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.33 373.59 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.75 827.77 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.35 396.07 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.72 794.47 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7241.28 8689.53 0.623 0.748 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.10 0.01270
RESTROOMFLR1 393.80 472.56 0.034 0.041 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 29.11 0.01270
MEETINGROOMFLR1 3422.50 4107.00 0.295 0.354 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.10 0.01270
GUESTROOM101 505.27 606.32 0.060 0.072 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.54 0.01270
GUESTROOM102 408.06 489.68 0.049 0.059 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.54 0.01270
GUESTROOM103 963.45 1156.14 0.115 0.138 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 24.92 0.01270
GUESTROOM104 1175.79 1410.94 0.141 0.169 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.10 0.01270
GUESTROOM105 1565.61 1878.74 0.187 0.225 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.10 0.01270
EMPLOYEELOUNGEFLR1 5403.05 6483.66 0.465 0.558 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
EXERCISECENTERFLR1 1153.37 1384.04 0.099 0.119 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 28.36 0.01270
FRONTOFFICEFLR1 3233.06 3879.67 0.278 0.334 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM201 690.56 828.67 0.083 0.099 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.10 0.01270
GUESTROOM202_205 3940.49 4728.59 0.471 0.565 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.54 0.01270
GUESTROOM206_208 3202.56 3843.07 0.383 0.459 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.54 0.01270
GUESTROOM209_212 3757.35 4508.82 0.449 0.539 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 29.54 0.01270
GUESTROOM213 1031.52 1237.82 0.123 0.148 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 24.92 0.01270
GUESTROOM214 1303.09 1563.71 0.156 0.187 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM215_218 9678.62 11614.35 1.157 1.388 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM219 5451.55 6541.87 0.652 0.782 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM220_223 4670.06 5604.08 0.558 0.670 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.10 0.01270
GUESTROOM224 1308.59 1570.31 0.156 0.188 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM301 514.66 617.59 0.062 0.074 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 30.10 0.01270
GUESTROOM302_305 1388.74 1666.48 0.166 0.199 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.36 0.01270
GUESTROOM306_308 1229.68 1475.61 0.147 0.176 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.36 0.01270
GUESTROOM309_312 3726.49 4471.79 0.445 0.535 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 29.36 0.01270
GUESTROOM313 531.97 638.37 0.064 0.076 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 24.92 0.01270
GUESTROOM314 1217.49 1460.99 0.146 0.175 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.10 0.01270
GUESTROOM315_318 5087.09 6104.51 0.608 0.730 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM319 1130.44 1356.53 0.135 0.162 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM320_323 4465.84 5359.01 0.534 0.641 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM324 732.28 878.74 0.088 0.105 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM401 1334.77 1601.72 0.160 0.191 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.10 0.01270
GUESTROOM402_405 2148.24 2577.89 0.257 0.308 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.10 0.01270
GUESTROOM406_408 1852.08 2222.50 0.221 0.266 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.10 0.01270
GUESTROOM409_412 4800.13 5760.15 0.574 0.689 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 30.10 0.01270
GUESTROOM413 782.38 938.86 0.094 0.112 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 29.91 0.01270
GUESTROOM414 1015.58 1218.69 0.121 0.146 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
GUESTROOM415_418 5811.00 6973.21 0.695 0.834 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.10 0.01270
GUESTROOM419 1583.47 1900.17 0.189 0.227 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 30.10 0.01270
GUESTROOM420_423 5769.74 6923.69 0.690 0.828 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 30.10 0.01270
GUESTROOM424 1579.34 1895.20 0.189 0.227 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 30.10 0.01270
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
CORRIDORFLR1 13579.73 16295.68 1.168 1.401 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 27.12 0.01270
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
CORRIDORFLR2 2603.22 3123.86 0.224 0.268 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 28.36 0.01270
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
CORRIDORFLR3 1207.94 1449.53 0.104 0.125 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 28.05 0.01270
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270
CORRIDORFLR4 2077.54 2493.05 0.179 0.214 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 29.73 0.01270
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB   30.10 0.01270


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2462.61 2955.13 0.072 0.236 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -32.70 0.00018
RESTROOMFLR1 195.36 234.43 0.006 0.007 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -32.70 0.00018
MEETINGROOMFLR1 883.59 1060.31 0.026 0.126 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -32.70 0.00018
GUESTROOM101 374.16 448.99 0.011 0.013 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -32.70 0.00018
GUESTROOM102 420.52 504.63 0.012 0.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70 0.00018
GUESTROOM103 731.83 878.20 0.022 0.026 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -32.70 0.00018
GUESTROOM104 742.14 890.56 0.022 0.026 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -32.70 0.00018
GUESTROOM105 431.43 517.72 0.013 0.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:45:00 -32.70 0.00018
EMPLOYEELOUNGEFLR1 418.15 501.78 0.012 0.051 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -32.70 0.00018
EXERCISECENTERFLR1 308.83 370.60 0.009 0.043 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -32.70 0.00018
FRONTOFFICEFLR1 1584.30 1901.16 0.047 0.056 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -32.70 0.00018
GUESTROOM201 550.91 661.09 0.016 0.019 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -32.70 0.00018
GUESTROOM202_205 1283.44 1540.13 0.038 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -32.70 0.00018
GUESTROOM206_208 1038.47 1246.17 0.031 0.043 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -32.70 0.00018
GUESTROOM209_212 1194.48 1433.38 0.035 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -32.70 0.00018
GUESTROOM213 696.96 836.35 0.021 0.025 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -32.70 0.00018
GUESTROOM214 673.52 808.22 0.020 0.024 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -32.70 0.00018
GUESTROOM215_218 1244.65 1493.59 0.037 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -32.70 0.00018
GUESTROOM219 323.26 387.91 0.010 0.013 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -32.70 0.00018
GUESTROOM220_223 1176.26 1411.51 0.035 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -32.70 0.00018
GUESTROOM224 559.12 670.94 0.016 0.020 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -32.70 0.00018
GUESTROOM301 597.71 717.25 0.018 0.021 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -32.70 0.00018
GUESTROOM302_305 1443.92 1732.70 0.042 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 16:30:00 -32.70 0.00018
GUESTROOM306_308 1257.74 1509.29 0.037 0.044 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -32.70 0.00018
GUESTROOM309_312 1449.09 1738.91 0.043 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -32.70 0.00018
GUESTROOM313 795.03 954.04 0.023 0.028 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -32.70 0.00018
GUESTROOM314 757.74 909.29 0.022 0.027 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 14:15:00 -32.70 0.00018
GUESTROOM315_318 1461.21 1753.45 0.043 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -32.70 0.00018
GUESTROOM319 409.64 491.57 0.012 0.014 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -32.70 0.00018
GUESTROOM320_323 1411.12 1693.34 0.042 0.054 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -32.70 0.00018
GUESTROOM324 638.71 766.45 0.019 0.023 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -32.70 0.00018
GUESTROOM401 968.45 1162.14 0.028 0.034 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -32.70 0.00018
GUESTROOM402_405 2750.85 3301.02 0.081 0.097 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 22:15:00 -32.70 0.00018
GUESTROOM406_408 2340.81 2808.97 0.069 0.083 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -32.70 0.00018
GUESTROOM409_412 2770.83 3324.99 0.082 0.098 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -32.70 0.00018
GUESTROOM413 1230.57 1476.69 0.036 0.043 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -32.70 0.00018
GUESTROOM414 1182.86 1419.44 0.035 0.042 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -32.70 0.00018
GUESTROOM415_418 2776.91 3332.30 0.082 0.098 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -32.70 0.00018
GUESTROOM419 824.67 989.60 0.024 0.029 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 17:15:00 -32.70 0.00018
GUESTROOM420_423 2727.63 3273.16 0.080 0.096 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -32.70 0.00018
GUESTROOM424 1049.79 1259.75 0.031 0.037 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -32.70 0.00018
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70 0.00018
CORRIDORFLR1 33752.52 40503.02 0.991 1.190 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -32.70 0.00018
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70 0.00018
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70 0.00018
CORRIDORFLR2 995.17 1194.20 0.029 0.038 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -32.70 0.00018
FRONTSTAIRSFLR2 1.20 1.44 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 12:15:00 -32.70 0.00018
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB   -32.70 0.00018
CORRIDORFLR3 1284.79 1541.74 0.038 0.045 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -32.70 0.00018
FRONTSTAIRSFLR3 113.52 136.22 0.002 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -32.70 0.00018
REARSTAIRSFLR4 32.66 39.20 0.001 0.006 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -32.70 0.00018
CORRIDORFLR4 2940.43 3528.52 0.086 0.104 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -32.70 0.00018
FRONTSTAIRSFLR4 358.96 430.75 0.007 0.009 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -32.70 0.00018


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.33 0.33 0.06 0.06
SAC_FRONTLOUNGE 0.75 0.75 0.24 0.24
SAC_MEETINGROOM 0.35 0.35 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.72 0.72 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 0.75 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 3823.00 7887.25 3506.00
RESTROOMFLR1 2206.25 8175.00 2112.50
MEETINGROOMFLR1 1465.50 3829.50 1107.75
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 3702.00 8759.00 3702.00
GUESTROOM104 2716.75 8716.25 2716.75
GUESTROOM105 857.00 8509.50 847.75
EMPLOYEELOUNGEFLR1 2679.00 2808.75 613.00
EXERCISECENTERFLR1 1159.00 3706.50 230.25
FRONTOFFICEFLR1 2395.50 6975.50 1900.75
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 2696.75 8607.00 2691.25
GUESTROOM206_208 2525.00 8597.75 2520.00
GUESTROOM209_212 2369.50 8699.75 2369.50
GUESTROOM213 3666.75 8739.25 3666.75
GUESTROOM214 2344.50 8580.00 2338.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 2889.00 4874.25 217.00
GUESTROOM220_223 1136.50 8456.25 1111.25
GUESTROOM224 2394.75 8551.25 2387.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 2868.50 8705.25 2867.50
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 3105.50 8593.75 3098.50
GUESTROOM315_318 1260.00 8313.50 1205.50
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 1956.00 8534.25 1935.75
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 4628.50 8325.75 4516.75
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 3855.00 8225.00 3677.25
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 3262.25 7969.75 2906.25
GUESTROOM419 3185.50 8099.75 2993.00
GUESTROOM420_423 3344.25 7995.50 3006.75
GUESTROOM424 3942.25 8197.50 3771.50
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7482.25 8760.00 6513.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 1.50 0.00 1.50 0.00
RESTROOMFLR1 1623.00 201.25 1623.00 201.25
MEETINGROOMFLR1 0.25 0.00 0.25 0.00
GUESTROOM101 0.25 0.00 0.00 0.00
GUESTROOM102 0.50 0.00 0.00 0.00
GUESTROOM103 31.75 24.25 31.75 24.25
GUESTROOM104 22.00 28.25 22.00 28.25
GUESTROOM105 3.50 36.50 3.50 36.50
EMPLOYEELOUNGEFLR1 1152.50 795.50 810.50 481.25
EXERCISECENTERFLR1 0.50 0.00 0.00 0.00
FRONTOFFICEFLR1 0.75 0.00 0.75 0.00
GUESTROOM201 2.25 0.00 0.00 0.00
GUESTROOM202_205 27.50 13.75 27.50 13.75
GUESTROOM206_208 27.00 20.25 27.00 20.25
GUESTROOM209_212 27.25 13.00 27.25 13.00
GUESTROOM213 31.75 13.00 31.75 13.00
GUESTROOM214 20.00 18.25 20.00 18.25
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 1847.50 0.00 1847.50
GUESTROOM220_223 8.00 15.50 8.00 15.50
GUESTROOM224 20.50 18.25 20.50 18.25
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.50 0.00 0.00 0.00
GUESTROOM306_308 1.75 0.00 0.00 0.00
GUESTROOM309_312 29.75 12.75 29.75 12.75
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 22.75 17.25 22.75 17.25
GUESTROOM315_318 10.75 18.25 10.75 18.25
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 17.75 14.75 17.75 14.75
GUESTROOM324 0.75 0.00 0.00 0.00
GUESTROOM401 25.25 20.75 25.25 20.75
GUESTROOM402_405 0.50 0.00 0.00 0.00
GUESTROOM406_408 0.50 0.00 0.00 0.00
GUESTROOM409_412 29.75 18.25 29.75 18.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.25 0.00 0.00 0.00
GUESTROOM415_418 22.50 23.25 22.50 23.25
GUESTROOM419 19.00 26.75 19.00 26.75
GUESTROOM420_423 22.50 22.50 22.50 22.50
GUESTROOM424 13.75 24.25 13.75 24.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 9.50 2166.25 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 35.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 4.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 4.00 0.00 0.00 0.00
REARSTAIRSFLR4 4.25 0.00 0.00 0.00
CORRIDORFLR4 0.00 95.50 0.00 0.00
FRONTSTAIRSFLR4 11.75 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 1929.00 3236.50 1853.50 2360.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:38

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.008552


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.008552
SAC_FRONTOFFICE SUPPLY FAN 0.333530
SAC_FRONTLOUNGE SUPPLY FAN 0.747653
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.717579


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 307.99
CORRIDORFLR1 PTAC HEATING COIL 43440.33
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1311.17
102 PTAC HEATING COIL 1357.78
103 PTAC HEATING COIL 1731.35
104 PTAC HEATING COIL 1743.65
105 PTAC HEATING COIL 1370.81
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 307.91
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 307.99
CORRIDORFLR2 PTAC HEATING COIL 3718.56
201 PTAC HEATING COIL 1514.24
202_205 PTAC HEATING COIL 5244.69
206_208 PTAC HEATING COIL 4156.60
209_212 PTAC HEATING COIL 5244.69
213 PTAC HEATING COIL 1689.50
214 PTAC HEATING COIL 1661.31
215_218 PTAC HEATING COIL 5244.32
219 PTAC HEATING COIL 1311.08
220_223 PTAC HEATING COIL 5244.32
224 PTAC HEATING COIL 1524.03
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 594.96
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 307.99
CORRIDORFLR3 PTAC HEATING COIL 3961.29
301 PTAC HEATING COIL 1570.40
302_305 PTAC HEATING COIL 5244.69
306_308 PTAC HEATING COIL 4213.89
309_312 PTAC HEATING COIL 5244.69
313 PTAC HEATING COIL 1807.19
314 PTAC HEATING COIL 1762.38
315_318 PTAC HEATING COIL 5244.32
319 PTAC HEATING COIL 1344.66
320_323 PTAC HEATING COIL 5244.32
324 PTAC HEATING COIL 1619.54
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 594.96
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 595.11
CORRIDORFLR4 PTAC HEATING COIL 5948.04
401 PTAC HEATING COIL 2015.29
402_405 PTAC HEATING COIL 6713.62
406_408 PTAC HEATING COIL 5513.58
409_412 PTAC HEATING COIL 6737.60
413 PTAC HEATING COIL 2329.84
414 PTAC HEATING COIL 2272.53
415_418 PTAC HEATING COIL 6744.66
419 PTAC HEATING COIL 1842.69
420_423 PTAC HEATING COIL 6685.52
424 PTAC HEATING COIL 2112.84
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 717.75


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.739672 0.333530 6576.12
SAC_FRONTLOUNGE COOLING COIL 0.693932 0.747653 17305.66
SAC_MEETINGROOM COOLING COIL 0.676083 0.353599 8780.71
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.749866 0.717579 13695.99


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.747653
RESTROOMFLR1 DIRECT AIR 0.040619
MEETINGROOMFLR1 DIRECT AIR 0.353599
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.557931
EXERCISECENTERFLR1 DIRECT AIR 0.119029
FRONTOFFICEFLR1 DIRECT AIR 0.333530


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.333530
SAC_FRONTLOUNGE MAIN BRANCH 0.747653
SAC_MEETINGROOM MAIN BRANCH 0.353599
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.717579


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.333530
SAC_FRONTLOUNGE 0.747653
SAC_MEETINGROOM 0.353599
SAC_EXC_EMPLGE_RESTRM 0.717579


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.333530 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.747653 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.353599 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.717579 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.333530 0.333530 0.333530 0.333530 5398.83 6576.12 1.00
SAC_FRONTLOUNGE 0.747653 0.747653 0.747653 0.747653 22629.09 17305.66 1.00
SAC_MEETINGROOM 0.353599 0.353599 0.353599 0.353599 12117.71 8780.71 1.00
SAC_EXC_EMPLGE_RESTRM 0.717579 0.717579 0.717579 0.717579 9282.00 13695.99 0.165875


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 5398.83
SAC_FRONTLOUNGE HEATING COIL 22629.09
SAC_MEETINGROOM HEATING COIL 12117.71
SAC_EXC_EMPLGE_RESTRM HEATING COIL 9282.00


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.353599


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.69 -16.9
February 14.63 -11.6
March 16.57 -6.2
April 18.63 3.97
May 21.66 13.43
June 22.78 18.03
July 23.47 19.67
August 22.84 17.94
September 21.31 12.29
October 19.41 5.42
November 16.75 -2.0
December 13.86 -14.6
     
Annual Sum or Average 18.82 3.36
Minimum of Months 13.69 -16.9
Maximum of Months 23.47 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.24 -16.9
February 21.53 -11.6
March 21.93 -6.2
April 23.03 3.97
May 24.30 13.43
June 25.13 18.03
July 25.56 19.67
August 25.14 17.94
September 24.14 12.29
October 23.29 5.42
November 22.25 -2.0
December 21.28 -14.6
     
Annual Sum or Average 23.24 3.36
Minimum of Months 21.24 -16.9
Maximum of Months 25.56 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.49 -16.9
February 14.27 -11.6
March 16.07 -6.2
April 18.03 3.97
May 21.11 13.43
June 22.29 18.03
July 22.93 19.67
August 22.28 17.94
September 20.72 12.29
October 18.81 5.42
November 16.34 -2.0
December 13.70 -14.6
     
Annual Sum or Average 18.36 3.36
Minimum of Months 13.49 -16.9
Maximum of Months 22.93 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -16.9
February 21.11 -11.6
March 21.11 -6.2
April 21.33 3.97
May 22.31 13.43
June 23.00 18.03
July 23.24 19.67
August 23.04 17.94
September 22.10 12.29
October 21.32 5.42
November 21.16 -2.0
December 21.11 -14.6
     
Annual Sum or Average 21.83 3.36
Minimum of Months 21.11 -16.9
Maximum of Months 23.24 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -16.9
February 20.82 -11.6
March 21.24 -6.2
April 21.99 3.97
May 22.89 13.43
June 23.33 18.03
July 23.50 19.67
August 23.36 17.94
September 22.84 12.29
October 22.20 5.42
November 21.55 -2.0
December 20.63 -14.6
     
Annual Sum or Average 22.08 3.36
Minimum of Months 20.50 -16.9
Maximum of Months 23.50 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 -16.9
February 21.15 -11.6
March 21.22 -6.2
April 21.80 3.97
May 23.08 13.43
June 23.59 18.03
July 23.72 19.67
August 23.63 17.94
September 23.05 12.29
October 21.91 5.42
November 21.34 -2.0
December 21.13 -14.6
     
Annual Sum or Average 22.23 3.36
Minimum of Months 21.12 -16.9
Maximum of Months 23.72 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.81 -16.9
February 23.04 -11.6
March 23.42 -6.2
April 24.28 3.97
May 25.47 13.43
June 25.98 18.03
July 26.22 19.67
August 26.05 17.94
September 25.51 12.29
October 24.63 5.42
November 23.77 -2.0
December 22.95 -14.6
     
Annual Sum or Average 24.52 3.36
Minimum of Months 22.81 -16.9
Maximum of Months 26.22 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.92 -11.6
March 19.01 -6.2
April 19.98 3.97
May 21.95 13.43
June 22.75 18.03
July 23.02 19.67
August 22.83 17.94
September 21.84 12.29
October 20.30 5.42
November 19.22 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.64 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.02 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.90 -11.6
March 18.95 -6.2
April 19.73 3.97
May 21.68 13.43
June 22.54 18.03
July 22.86 19.67
August 22.61 17.94
September 21.51 12.29
October 19.97 5.42
November 19.09 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.48 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 22.86 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.49 -11.6
March 20.53 -6.2
April 20.91 3.97
May 21.50 13.43
June 21.70 18.03
July 21.73 19.67
August 21.70 17.94
September 21.47 12.29
October 21.00 5.42
November 20.63 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.05 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.73 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -16.9
February 20.62 -11.6
March 20.74 -6.2
April 21.20 3.97
May 21.61 13.43
June 21.72 18.03
July 21.74 19.67
August 21.72 17.94
September 21.61 12.29
October 21.25 5.42
November 20.87 -2.0
December 20.49 -14.6
     
Annual Sum or Average 21.17 3.36
Minimum of Months 20.49 -16.9
Maximum of Months 21.74 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.68 -16.9
February 20.95 -11.6
March 21.12 -6.2
April 21.51 3.97
May 21.72 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.72 12.29
October 21.55 5.42
November 21.26 -2.0
December 20.70 -14.6
     
Annual Sum or Average 21.37 3.36
Minimum of Months 20.68 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.88 -16.9
February 21.27 -11.6
March 21.65 -6.2
April 22.11 3.97
May 22.34 13.43
June 22.45 18.03
July 22.41 19.67
August 22.51 17.94
September 22.38 12.29
October 22.22 5.42
November 21.92 -2.0
December 20.96 -14.6
     
Annual Sum or Average 21.93 3.36
Minimum of Months 20.88 -16.9
Maximum of Months 22.51 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 49.51 -16.9
February 49.98 -11.6
March 50.56 -6.2
April 51.28 3.97
May 52.19 13.43
June 52.54 18.03
July 52.84 19.67
August 52.69 17.94
September 52.23 12.29
October 51.57 5.42
November 50.65 -2.0
December 49.57 -14.6
     
Annual Sum or Average 51.31 3.36
Minimum of Months 49.51 -16.9
Maximum of Months 52.84 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 66.68 -16.9
February 66.96 -11.6
March 67.66 -6.2
April 68.37 3.97
May 69.63 13.43
June 70.12 18.03
July 70.51 19.67
August 70.25 17.94
September 69.61 12.29
October 68.85 5.42
November 67.71 -2.0
December 66.73 -14.6
     
Annual Sum or Average 68.60 3.36
Minimum of Months 66.68 -16.9
Maximum of Months 70.51 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.54 -16.9
February 21.94 -11.6
March 22.32 -6.2
April 22.94 3.97
May 23.48 13.43
June 23.72 18.03
July 23.81 19.67
August 23.81 17.94
September 23.51 12.29
October 23.09 5.42
November 22.55 -2.0
December 21.60 -14.6
     
Annual Sum or Average 22.86 3.36
Minimum of Months 21.54 -16.9
Maximum of Months 23.81 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 -16.9
February 21.42 -11.6
March 21.60 -6.2
April 22.36 3.97
May 23.39 13.43
June 23.73 18.03
July 23.83 19.67
August 23.82 17.94
September 23.44 12.29
October 22.55 5.42
November 21.74 -2.0
December 21.17 -14.6
     
Annual Sum or Average 22.53 3.36
Minimum of Months 21.17 -16.9
Maximum of Months 23.83 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.55 -16.9
February 13.59 -11.6
March 15.80 -6.2
April 18.20 3.97
May 21.60 13.43
June 23.01 18.03
July 23.84 19.67
August 23.09 17.94
September 21.34 12.29
October 19.12 5.42
November 16.08 -2.0
December 12.76 -14.6
     
Annual Sum or Average 18.44 3.36
Minimum of Months 12.55 -16.9
Maximum of Months 23.84 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.31 -16.9
February 17.95 -11.6
March 19.13 -6.2
April 20.63 3.97
May 22.65 13.43
June 23.43 18.03
July 23.93 19.67
August 23.56 17.94
September 22.61 12.29
October 21.20 5.42
November 19.36 -2.0
December 17.43 -14.6
     
Annual Sum or Average 20.78 3.36
Minimum of Months 17.31 -16.9
Maximum of Months 23.93 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.90 -16.9
February 13.90 -11.6
March 16.26 -6.2
April 18.61 3.97
May 22.21 13.43
June 23.42 18.03
July 24.21 19.67
August 23.48 17.94
September 21.75 12.29
October 19.55 5.42
November 16.32 -2.0
December 13.00 -14.6
     
Annual Sum or Average 18.83 3.36
Minimum of Months 12.90 -16.9
Maximum of Months 24.21 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -16.9
February 21.18 -11.6
March 21.36 -6.2
April 22.37 3.97
May 23.66 13.43
June 23.89 18.03
July 23.90 19.67
August 23.88 17.94
September 23.65 12.29
October 22.58 5.42
November 21.47 -2.0
December 21.11 -14.6
     
Annual Sum or Average 22.52 3.36
Minimum of Months 21.11 -16.9
Maximum of Months 23.90 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.81 -16.9
February 12.74 -11.6
March 14.98 -6.2
April 17.35 3.97
May 21.23 13.43
June 22.63 18.03
July 23.42 19.67
August 22.61 17.94
September 20.68 12.29
October 18.26 5.42
November 15.17 -2.0
December 12.00 -14.6
     
Annual Sum or Average 17.77 3.36
Minimum of Months 11.81 -16.9
Maximum of Months 23.42 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.91 -6.2
April 19.58 3.97
May 21.87 13.43
June 22.86 18.03
July 23.14 19.67
August 22.95 17.94
September 21.53 12.29
October 19.54 5.42
November 18.96 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.51 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.14 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.52 -11.6
March 20.60 -6.2
April 21.09 3.97
May 21.64 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.62 12.29
October 21.13 5.42
November 20.72 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.13 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -16.9
February 20.54 -11.6
March 20.62 -6.2
April 21.13 3.97
May 21.66 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.64 12.29
October 21.18 5.42
November 20.75 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.15 3.36
Minimum of Months 20.48 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -16.9
February 20.54 -11.6
March 20.63 -6.2
April 21.16 3.97
May 21.66 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.65 12.29
October 21.21 5.42
November 20.77 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.16 3.36
Minimum of Months 20.48 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.48 -11.6
March 20.52 -6.2
April 20.93 3.97
May 21.56 13.43
June 21.73 18.03
July 21.75 19.67
August 21.73 17.94
September 21.53 12.29
October 20.99 5.42
November 20.60 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.07 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -16.9
February 20.65 -11.6
March 20.80 -6.2
April 21.30 3.97
May 21.69 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.68 12.29
October 21.34 5.42
November 20.91 -2.0
December 20.49 -14.6
     
Annual Sum or Average 21.22 3.36
Minimum of Months 20.49 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 -16.9
February 21.53 -11.6
March 22.27 -6.2
April 23.06 3.97
May 23.32 13.43
June 23.33 18.03
July 23.33 19.67
August 23.33 17.94
September 23.33 12.29
October 23.20 5.42
November 22.59 -2.0
December 20.97 -14.6
     
Annual Sum or Average 22.59 3.36
Minimum of Months 20.81 -16.9
Maximum of Months 23.33 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 29.34 -16.9
February 29.64 -11.6
March 30.30 -6.2
April 31.19 3.97
May 32.62 13.43
June 33.08 18.03
July 33.37 19.67
August 33.15 17.94
September 32.53 12.29
October 31.53 5.42
November 30.30 -2.0
December 29.35 -14.6
     
Annual Sum or Average 31.38 3.36
Minimum of Months 29.34 -16.9
Maximum of Months 33.37 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.68 -16.9
February 21.72 -11.6
March 21.78 -6.2
April 21.95 3.97
May 22.39 13.43
June 22.70 18.03
July 22.87 19.67
August 22.74 17.94
September 22.38 12.29
October 22.00 5.42
November 21.78 -2.0
December 21.70 -14.6
     
Annual Sum or Average 22.14 3.36
Minimum of Months 21.68 -16.9
Maximum of Months 22.87 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.55 -16.9
February 20.79 -11.6
March 20.94 -6.2
April 21.41 3.97
May 21.72 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.71 12.29
October 21.42 5.42
November 21.05 -2.0
December 20.54 -14.6
     
Annual Sum or Average 21.28 3.36
Minimum of Months 20.54 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.49 -16.9
February 20.65 -11.6
March 20.78 -6.2
April 21.28 3.97
May 21.69 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.68 12.29
October 21.31 5.42
November 20.89 -2.0
December 20.49 -14.6
     
Annual Sum or Average 21.21 3.36
Minimum of Months 20.49 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.85 -16.9
February 16.57 -11.6
March 18.15 -6.2
April 20.08 3.97
May 22.75 13.43
June 23.69 18.03
July 24.33 19.67
August 23.79 17.94
September 22.54 12.29
October 20.71 5.42
November 18.28 -2.0
December 15.93 -14.6
     
Annual Sum or Average 20.24 3.36
Minimum of Months 15.85 -16.9
Maximum of Months 24.33 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.89 -16.9
February 11.95 -11.6
March 14.76 -6.2
April 17.74 3.97
May 22.09 13.43
June 23.72 18.03
July 24.76 19.67
August 23.77 17.94
September 21.63 12.29
October 18.86 5.42
November 14.95 -2.0
December 11.02 -14.6
     
Annual Sum or Average 18.05 3.36
Minimum of Months 10.89 -16.9
Maximum of Months 24.76 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.88 -16.9
February 12.88 -11.6
March 15.40 -6.2
April 17.97 3.97
May 22.05 13.43
June 23.45 18.03
July 24.33 19.67
August 23.49 17.94
September 21.46 12.29
October 18.89 5.42
November 15.42 -2.0
December 11.96 -14.6
     
Annual Sum or Average 18.30 3.36
Minimum of Months 11.88 -16.9
Maximum of Months 24.33 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -16.9
February 21.11 -11.6
March 21.12 -6.2
April 21.59 3.97
May 23.10 13.43
June 23.67 18.03
July 23.82 19.67
August 23.74 17.94
September 22.89 12.29
October 21.54 5.42
November 21.13 -2.0
December 21.11 -14.6
     
Annual Sum or Average 22.17 3.36
Minimum of Months 21.11 -16.9
Maximum of Months 23.82 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.25 -16.9
February 11.29 -11.6
March 13.72 -6.2
April 16.37 3.97
May 20.93 13.43
June 22.65 18.03
July 23.59 19.67
August 22.62 17.94
September 20.16 12.29
October 17.23 5.42
November 13.90 -2.0
December 10.46 -14.6
     
Annual Sum or Average 16.96 3.36
Minimum of Months 10.25 -16.9
Maximum of Months 23.59 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.89 -6.2
April 19.31 3.97
May 21.50 13.43
June 22.68 18.03
July 23.05 19.67
August 22.78 17.94
September 20.96 12.29
October 19.19 5.42
November 18.91 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.34 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.05 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.89 -6.2
April 19.38 3.97
May 21.62 13.43
June 22.74 18.03
July 23.08 19.67
August 22.86 17.94
September 21.12 12.29
October 19.26 5.42
November 18.93 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.39 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.08 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.89 -6.2
April 19.44 3.97
May 21.71 13.43
June 22.76 18.03
July 23.08 19.67
August 22.85 17.94
September 21.23 12.29
October 19.32 5.42
November 18.93 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.42 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.08 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.51 -11.6
March 20.58 -6.2
April 21.08 3.97
May 21.63 13.43
June 21.74 18.03
July 21.75 19.67
August 21.74 17.94
September 21.60 12.29
October 21.11 5.42
November 20.69 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.12 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.89 -6.2
April 19.35 3.97
May 21.60 13.43
June 22.68 18.03
July 23.08 19.67
August 22.80 17.94
September 21.13 12.29
October 19.31 5.42
November 18.92 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.38 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.08 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.56 -11.6
March 20.66 -6.2
April 21.13 3.97
May 21.64 13.43
June 21.74 18.03
July 21.75 19.67
August 21.74 17.94
September 21.61 12.29
October 21.17 5.42
November 20.74 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.14 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.54 -16.9
February 20.79 -11.6
March 20.96 -6.2
April 21.45 3.97
May 21.73 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.72 12.29
October 21.45 5.42
November 21.08 -2.0
December 20.54 -14.6
     
Annual Sum or Average 21.30 3.36
Minimum of Months 20.54 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 -16.9
February 21.08 -11.6
March 21.94 -6.2
April 23.19 3.97
May 25.09 13.43
June 25.70 18.03
July 26.01 19.67
August 25.75 17.94
September 24.87 12.29
October 23.45 5.42
November 21.93 -2.0
December 20.65 -14.6
     
Annual Sum or Average 23.37 3.36
Minimum of Months 20.63 -16.9
Maximum of Months 26.01 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.00 -16.9
February 19.45 -11.6
March 20.01 -6.2
April 21.63 3.97
May 23.05 13.43
June 23.30 18.03
July 23.33 19.67
August 23.32 17.94
September 23.03 12.29
October 21.81 5.42
November 20.24 -2.0
December 19.00 -14.6
     
Annual Sum or Average 21.44 3.36
Minimum of Months 19.00 -16.9
Maximum of Months 23.33 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 -16.9
February 20.70 -11.6
March 20.82 -6.2
April 21.32 3.97
May 21.69 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.67 12.29
October 21.31 5.42
November 20.93 -2.0
December 20.50 -14.6
     
Annual Sum or Average 21.23 3.36
Minimum of Months 20.50 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.94 -11.6
March 19.05 -6.2
April 20.10 3.97
May 22.21 13.43
June 22.89 18.03
July 23.16 19.67
August 23.02 17.94
September 22.04 12.29
October 20.17 5.42
November 19.07 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.71 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 23.16 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.49 -16.9
February 15.22 -11.6
March 16.95 -6.2
April 19.21 3.97
May 22.55 13.43
June 23.73 18.03
July 24.50 19.67
August 23.83 17.94
September 22.17 12.29
October 19.82 5.42
November 17.03 -2.0
December 14.56 -14.6
     
Annual Sum or Average 19.53 3.36
Minimum of Months 14.49 -16.9
Maximum of Months 24.50 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 9.72 -16.9
February 10.66 -11.6
March 13.63 -6.2
April 16.98 3.97
May 21.95 13.43
June 23.80 18.03
July 24.97 19.67
August 23.83 17.94
September 21.32 12.29
October 18.10 5.42
November 13.80 -2.0
December 9.79 -14.6
     
Annual Sum or Average 17.42 3.36
Minimum of Months 9.72 -16.9
Maximum of Months 24.97 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.16 -16.9
February 11.20 -11.6
March 13.89 -6.2
April 16.94 3.97
May 21.72 13.43
June 23.47 18.03
July 24.44 19.67
August 23.44 17.94
September 20.84 12.29
October 17.65 5.42
November 13.90 -2.0
December 10.27 -14.6
     
Annual Sum or Average 17.36 3.36
Minimum of Months 10.16 -16.9
Maximum of Months 24.44 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -16.9
February 21.11 -11.6
March 21.13 -6.2
April 21.52 3.97
May 22.70 13.43
June 23.33 18.03
July 23.56 19.67
August 23.34 17.94
September 22.33 12.29
October 21.35 5.42
November 21.13 -2.0
December 21.11 -14.6
     
Annual Sum or Average 21.98 3.36
Minimum of Months 21.11 -16.9
Maximum of Months 23.56 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.64 -16.9
February 9.92 -11.6
March 12.59 -6.2
April 15.64 3.97
May 20.68 13.43
June 22.66 18.03
July 23.65 19.67
August 22.55 17.94
September 19.64 12.29
October 16.30 5.42
November 12.76 -2.0
December 8.91 -14.6
     
Annual Sum or Average 16.20 3.36
Minimum of Months 8.64 -16.9
Maximum of Months 23.65 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.46 -16.9
February 20.47 -11.6
March 20.48 -6.2
April 20.87 3.97
May 21.54 13.43
June 21.73 18.03
July 21.74 19.67
August 21.71 17.94
September 21.43 12.29
October 20.75 5.42
November 20.51 -2.0
December 20.46 -14.6
     
Annual Sum or Average 21.02 3.36
Minimum of Months 20.46 -16.9
Maximum of Months 21.74 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.90 -6.2
April 19.38 3.97
May 21.32 13.43
June 22.39 18.03
July 22.77 19.67
August 22.45 17.94
September 20.69 12.29
October 19.14 5.42
November 18.92 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.23 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 22.77 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.90 -6.2
April 19.41 3.97
May 21.36 13.43
June 22.40 18.03
July 22.76 19.67
August 22.44 17.94
September 20.73 12.29
October 19.16 5.42
November 18.92 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.24 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 22.76 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.49 -11.6
March 20.55 -6.2
April 21.08 3.97
May 21.66 13.43
June 21.75 18.03
July 21.75 19.67
August 21.74 17.94
September 21.60 12.29
October 21.02 5.42
November 20.61 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.10 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.89 -11.6
March 18.89 -6.2
April 19.35 3.97
May 21.34 13.43
June 22.41 18.03
July 22.83 19.67
August 22.48 17.94
September 20.74 12.29
October 19.17 5.42
November 18.91 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.24 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 22.83 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -16.9
February 18.94 -11.6
March 19.04 -6.2
April 19.82 3.97
May 21.72 13.43
June 22.56 18.03
July 22.89 19.67
August 22.65 17.94
September 21.32 12.29
October 19.63 5.42
November 18.99 -2.0
December 18.89 -14.6
     
Annual Sum or Average 20.45 3.36
Minimum of Months 18.89 -16.9
Maximum of Months 22.89 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -16.9
February 20.69 -11.6
March 20.82 -6.2
April 21.33 3.97
May 21.71 13.43
June 21.75 18.03
July 21.75 19.67
August 21.74 17.94
September 21.67 12.29
October 21.26 5.42
November 20.88 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.22 3.36
Minimum of Months 20.48 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.84 -16.9
February 18.48 -11.6
March 19.48 -6.2
April 21.00 3.97
May 23.19 13.43
June 24.00 18.03
July 24.36 19.67
August 23.96 17.94
September 22.74 12.29
October 21.05 5.42
November 19.45 -2.0
December 17.92 -14.6
     
Annual Sum or Average 21.14 3.36
Minimum of Months 17.84 -16.9
Maximum of Months 24.36 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -16.9
February 20.65 -11.6
March 20.78 -6.2
April 21.30 3.97
May 21.70 13.43
June 21.75 18.03
July 21.75 19.67
August 21.75 17.94
September 21.67 12.29
October 21.24 5.42
November 20.84 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.20 3.36
Minimum of Months 20.48 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.48 -16.9
February 20.68 -11.6
March 20.80 -6.2
April 21.31 3.97
May 21.70 13.43
June 21.75 18.03
July 21.75 19.67
August 21.74 17.94
September 21.66 12.29
October 21.22 5.42
November 20.84 -2.0
December 20.48 -14.6
     
Annual Sum or Average 21.20 3.36
Minimum of Months 20.48 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -16.9
February 20.55 -11.6
March 20.64 -6.2
April 21.13 3.97
May 21.66 13.43
June 21.74 18.03
July 21.75 19.67
August 21.74 17.94
September 21.60 12.29
October 21.06 5.42
November 20.66 -2.0
December 20.47 -14.6
     
Annual Sum or Average 21.13 3.36
Minimum of Months 20.47 -16.9
Maximum of Months 21.75 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.35 -16.9
February 14.27 -11.6
March 16.15 -6.2
April 18.76 3.97
May 22.37 13.43
June 23.69 18.03
July 24.44 19.67
August 23.66 17.94
September 21.76 12.29
October 19.16 5.42
November 16.21 -2.0
December 13.48 -14.6
     
Annual Sum or Average 18.97 3.36
Minimum of Months 13.35 -16.9
Maximum of Months 24.44 19.67



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:38

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 8.71 -16.9
February 9.66 -11.6
March 12.52 -6.2
April 16.29 3.97
May 21.72 13.43
June 23.81 18.03
July 24.98 19.67
August 23.71 17.94
September 20.83 12.29
October 17.21 5.42
November 12.65 -2.0
December 8.80 -14.6
     
Annual Sum or Average 16.78 3.36
Minimum of Months 8.71 -16.9
Maximum of Months 24.98 19.67



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:38

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.261766E+12 197202.237 05-JAN-07:15 15177.258 39465.561 8751.007 129607.002 5.295 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.203650E+12 188693.280 14-FEB-07:15 15177.258 39465.561 8735.259 121081.648 37.441 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.186267E+12 171618.357 05-MAR-07:15 15140.050 39465.561 8720.606 108213.373 70.655 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.138657E+12 123022.687 05-APR-06:15 15177.258 39465.561 8696.868 59491.528 183.358 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.136180E+12 89475.409 26-MAY-07:00 17492.219 43276.576 9092.551 0.000 19605.950 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.142008E+12 98128.391 30-JUN-07:00 17492.219 43276.576 9092.551 0.000 28258.932 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.153404E+12 95350.472 29-JUL-07:00 17566.637 43276.576 9092.551 0.000 25406.596 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.147014E+12 87242.806 26-AUG-07:00 17492.219 43276.576 9092.551 0.000 17373.348 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.130301E+12 87509.974 01-SEP-07:00 17789.888 43276.576 9092.551 0.000 17342.846 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.138284E+12 118870.147 30-OCT-06:15 15177.258 39465.561 8696.481 51131.886 202.847 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.167739E+12 151347.052 25-NOV-07:15 13316.689 34010.661 8712.992 91034.296 76.302 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.250694E+12 193539.315 24-DEC-07:00 15177.258 39465.561 8743.927 125941.777 14.679 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.205596E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.130301E+12 87242.806   13316.689 34010.661 8696.481 0.000 5.295 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.261766E+12 197202.237   17789.888 43276.576 9092.551 129607.002 28258.932 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:38

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.157469E+12 137012.788 06-JAN-09:15 32547.538 40096.028 0.000 64369.222 64369.222 64369.222 32547.538
February 0.133240E+12 131583.981 17-FEB-09:15 25639.348 40096.028 0.000 65848.605 65848.605 65848.605 25639.348
March 0.135184E+12 124773.042 15-MAR-08:30 20568.078 40096.028 0.000 64108.936 64108.936 64108.936 20568.078
April 0.110879E+12 112779.934 05-APR-09:45 11847.893 40096.028 0.000 60836.013 60836.013 60836.013 11847.893
May 0.101316E+12 103690.237 01-MAY-08:15 796.689 40096.028 0.000 62797.520 62797.520 62797.520 796.689
June 0.928988E+11 100982.007 02-JUN-08:15 0.000 40096.028 0.000 60885.979 60885.979 60885.979 0.000
July 0.926102E+11 98881.168 01-JUL-08:15 0.000 40096.028 0.000 58785.140 58785.140 58785.140 0.000
August 0.910320E+11 96762.981 26-AUG-08:15 0.000 40096.028 0.000 56666.953 56666.953 56666.953 0.000
September 0.898507E+11 97395.726 30-SEP-08:15 0.000 40096.028 0.000 57299.698 57299.698 57299.698 0.000
October 0.101767E+12 103445.928 12-OCT-09:15 6875.620 40096.028 0.000 56474.281 56474.281 56474.281 6875.620
November 0.115527E+12 120746.966 25-NOV-10:00 20628.307 40096.028 0.000 60022.630 60022.630 60022.630 20628.307
December 0.149787E+12 131872.152 24-DEC-09:30 29574.795 40096.028 0.000 62201.329 62201.329 62201.329 29574.795
                     
Annual Sum or Average 0.137156E+13         0.000        
Minimum of Months 0.898507E+11 96762.981   0.000 40096.028 0.000 56474.281 56474.281 56474.281 0.000
Maximum of Months 0.157469E+12 137012.788   32547.538 40096.028 0.000 65848.605 65848.605 65848.605 32547.538