Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Rochester International Arpt MN USA TMY3 WMO#=726440
Simulation Timestamp: 2018-10-19 10:15:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3289.67 | 819.63 | 883.11 |
Net Site Energy | 3289.67 | 819.63 | 883.11 |
Total Source Energy | 7751.86 | 1931.41 | 2080.98 |
Net Source Energy | 7751.86 | 1931.41 | 2080.98 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 460.56 | 168.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 197.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 689.72 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2009.53 | 1280.13 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 460.56 | 168.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 197.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 280.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 689.72 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 251.89 | 230.50 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 539.46 | 343.65 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 233.78 | 213.93 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 500.68 | 318.95 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2009.53 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2009.53 | 100.00 |
Total On-Site and Utility Electric Sources | 2009.53 | 100.00 |
Total Electricity End Uses | 2009.53 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1478.00 |
Time Setpoint Not Met During Occupied Cooling | 2737.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6646.25 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Weather File | Rochester International Arpt MN USA TMY3 WMO#=726440 |
Latitude [deg] | 43.90 |
Longitude [deg] | -92.5 |
Elevation [m] | 398.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00 | -26.20 | Wetbulb [C] | 5.70 | 310.00 |
ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 10.60 | 23.10 | Wetbulb [C] | 6.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7070.36 | 5026.50 | 2043.87 | 0.71 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19029.83 | 12865.75 | 6164.08 | 0.68 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8963.19 | 6059.87 | 2903.33 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14605.47 | 10641.89 | 3963.58 | 0.73 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6817.7 | 3.31 | 11.30 | 11.98 | 11.34 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 18434.2 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8682.6 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14050.8 | 3.28 | 11.18 | 11.85 | 11.17 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 306.55 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 37770.87 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1202.50 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1222.89 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1695.93 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1673.99 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1219.11 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 545.65 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 545.78 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3796.81 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1514.06 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4809.99 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3812.08 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4809.99 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1784.82 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1676.67 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4809.65 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1202.41 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4809.65 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1458.59 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 708.92 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 545.78 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 4178.87 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1577.36 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4809.99 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3927.86 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4821.40 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1921.76 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1743.79 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4809.65 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1278.28 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4809.65 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1554.18 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 863.64 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 767.39 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 5927.94 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1962.84 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 6167.20 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 5056.41 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 6198.71 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2371.68 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 2135.09 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 6136.96 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1713.76 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 6077.78 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1981.13 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 1140.13 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4951.35 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 20753.49 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 11113.34 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 8503.27 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.87 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 1.16 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.98 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.02 | 1.67 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.33 | 364.26 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.77 | 848.45 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.36 | 404.30 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.71 | 790.79 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7386.80 | 8864.16 | 0.639 | 0.766 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 31.04 | 0.01534 |
RESTROOMFLR1 | 417.67 | 501.21 | 0.036 | 0.043 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 30.56 | 0.01534 |
MEETINGROOMFLR1 | 3477.13 | 4172.55 | 0.301 | 0.361 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20 | 0.01534 |
GUESTROOM101 | 536.10 | 643.32 | 0.064 | 0.077 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.72 | 0.01534 |
GUESTROOM102 | 437.34 | 524.81 | 0.053 | 0.063 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.72 | 0.01534 |
GUESTROOM103 | 1006.01 | 1207.22 | 0.121 | 0.145 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
GUESTROOM104 | 1165.78 | 1398.93 | 0.140 | 0.168 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
GUESTROOM105 | 1531.35 | 1837.62 | 0.184 | 0.221 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
EMPLOYEELOUNGEFLR1 | 5321.79 | 6386.15 | 0.460 | 0.552 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
EXERCISECENTERFLR1 | 1145.87 | 1375.05 | 0.099 | 0.119 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.72 | 0.01534 |
FRONTOFFICEFLR1 | 3137.36 | 3764.84 | 0.271 | 0.325 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM201 | 816.64 | 979.96 | 0.098 | 0.118 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
GUESTROOM202_205 | 4075.56 | 4890.67 | 0.490 | 0.587 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.72 | 0.01534 |
GUESTROOM206_208 | 3299.64 | 3959.56 | 0.396 | 0.476 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.88 | 0.01534 |
GUESTROOM209_212 | 3887.47 | 4664.97 | 0.467 | 0.560 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 30.72 | 0.01534 |
GUESTROOM213 | 1092.84 | 1311.41 | 0.131 | 0.158 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
GUESTROOM214 | 1312.50 | 1575.01 | 0.158 | 0.189 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
GUESTROOM215_218 | 9538.72 | 11446.47 | 1.146 | 1.375 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM219 | 5385.74 | 6462.89 | 0.647 | 0.776 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM220_223 | 4622.52 | 5547.02 | 0.555 | 0.666 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM224 | 1310.54 | 1572.64 | 0.157 | 0.189 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM301 | 648.81 | 778.57 | 0.078 | 0.094 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM302_305 | 1539.13 | 1846.96 | 0.185 | 0.222 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 30.56 | 0.01534 |
GUESTROOM306_308 | 1341.66 | 1610.00 | 0.161 | 0.193 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 30.56 | 0.01534 |
GUESTROOM309_312 | 3871.29 | 4645.55 | 0.465 | 0.558 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 30.56 | 0.01534 |
GUESTROOM313 | 598.96 | 718.75 | 0.072 | 0.086 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.07 | 0.01534 |
GUESTROOM314 | 1235.94 | 1483.13 | 0.148 | 0.178 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 31.20 | 0.01534 |
GUESTROOM315_318 | 5040.14 | 6048.17 | 0.605 | 0.726 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM319 | 1118.05 | 1341.66 | 0.134 | 0.161 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM320_323 | 4434.47 | 5321.36 | 0.533 | 0.639 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
GUESTROOM324 | 742.91 | 891.50 | 0.089 | 0.107 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
GUESTROOM401 | 1485.12 | 1782.15 | 0.178 | 0.214 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:45:00 | 31.07 | 0.01534 |
GUESTROOM402_405 | 2321.48 | 2785.78 | 0.279 | 0.335 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM406_408 | 1980.74 | 2376.89 | 0.238 | 0.285 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 31.20 | 0.01534 |
GUESTROOM409_412 | 4966.41 | 5959.69 | 0.597 | 0.716 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM413 | 852.48 | 1022.98 | 0.102 | 0.123 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 31.04 | 0.01534 |
GUESTROOM414 | 1033.05 | 1239.66 | 0.124 | 0.149 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
GUESTROOM415_418 | 5753.78 | 6904.54 | 0.691 | 0.829 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20 | 0.01534 |
GUESTROOM419 | 1573.19 | 1887.83 | 0.189 | 0.227 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 31.20 | 0.01534 |
GUESTROOM420_423 | 5718.67 | 6862.40 | 0.687 | 0.824 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 31.20 | 0.01534 |
GUESTROOM424 | 1589.65 | 1907.58 | 0.191 | 0.229 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 31.20 | 0.01534 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
CORRIDORFLR1 | 14178.48 | 17014.18 | 1.225 | 1.470 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.66 | 0.01534 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
CORRIDORFLR2 | 2634.23 | 3161.07 | 0.227 | 0.273 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 29.72 | 0.01534 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
CORRIDORFLR3 | 1263.48 | 1516.18 | 0.109 | 0.131 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 29.45 | 0.01534 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 | |
CORRIDORFLR4 | 2157.09 | 2588.51 | 0.186 | 0.224 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 31.04 | 0.01534 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN CLG .4% CONDNS DB=>MWB | 31.20 | 0.01534 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2263.64 | 2716.37 | 0.067 | 0.236 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -26.20 | 0.00036 |
RESTROOMFLR1 | 171.22 | 205.47 | 0.005 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -26.20 | 0.00036 |
MEETINGROOMFLR1 | 808.89 | 970.67 | 0.024 | 0.126 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -26.20 | 0.00036 |
GUESTROOM101 | 342.26 | 410.72 | 0.010 | 0.013 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20 | 0.00036 |
GUESTROOM102 | 396.90 | 476.28 | 0.012 | 0.014 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -26.20 | 0.00036 |
GUESTROOM103 | 791.11 | 949.33 | 0.023 | 0.028 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -26.20 | 0.00036 |
GUESTROOM104 | 772.87 | 927.44 | 0.023 | 0.027 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -26.20 | 0.00036 |
GUESTROOM105 | 393.80 | 472.56 | 0.012 | 0.014 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -26.20 | 0.00036 |
EMPLOYEELOUNGEFLR1 | 370.72 | 444.87 | 0.011 | 0.051 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -26.20 | 0.00036 |
EXERCISECENTERFLR1 | 267.15 | 320.58 | 0.008 | 0.043 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -26.20 | 0.00036 |
FRONTOFFICEFLR1 | 1461.37 | 1753.65 | 0.043 | 0.056 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -26.20 | 0.00036 |
GUESTROOM201 | 639.55 | 767.46 | 0.019 | 0.023 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -26.20 | 0.00036 |
GUESTROOM202_205 | 1354.68 | 1625.61 | 0.040 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -26.20 | 0.00036 |
GUESTROOM206_208 | 1086.33 | 1303.60 | 0.032 | 0.043 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
GUESTROOM209_212 | 1275.35 | 1530.42 | 0.038 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -26.20 | 0.00036 |
GUESTROOM213 | 865.18 | 1038.22 | 0.026 | 0.031 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -26.20 | 0.00036 |
GUESTROOM214 | 775.10 | 930.12 | 0.023 | 0.027 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -26.20 | 0.00036 |
GUESTROOM215_218 | 1268.98 | 1522.78 | 0.038 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -26.20 | 0.00036 |
GUESTROOM219 | 349.43 | 419.32 | 0.010 | 0.013 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -26.20 | 0.00036 |
GUESTROOM220_223 | 1204.09 | 1444.91 | 0.036 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -26.20 | 0.00036 |
GUESTROOM224 | 593.37 | 712.04 | 0.018 | 0.021 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -26.20 | 0.00036 |
GUESTROOM301 | 692.30 | 830.76 | 0.020 | 0.025 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -26.20 | 0.00036 |
GUESTROOM302_305 | 1515.65 | 1818.78 | 0.045 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | -26.20 | 0.00036 |
GUESTROOM306_308 | 1300.85 | 1561.02 | 0.038 | 0.046 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:30:00 | -26.20 | 0.00036 |
GUESTROOM309_312 | 1529.14 | 1834.97 | 0.045 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:30:00 | -26.20 | 0.00036 |
GUESTROOM313 | 979.29 | 1175.15 | 0.029 | 0.035 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -26.20 | 0.00036 |
GUESTROOM314 | 831.03 | 997.24 | 0.025 | 0.029 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:15:00 | -26.20 | 0.00036 |
GUESTROOM315_318 | 1485.52 | 1782.63 | 0.044 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -26.20 | 0.00036 |
GUESTROOM319 | 443.10 | 531.72 | 0.013 | 0.016 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -26.20 | 0.00036 |
GUESTROOM320_323 | 1432.91 | 1719.49 | 0.042 | 0.054 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -26.20 | 0.00036 |
GUESTROOM324 | 673.02 | 807.62 | 0.020 | 0.024 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -26.20 | 0.00036 |
GUESTROOM401 | 1013.53 | 1216.23 | 0.030 | 0.036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -26.20 | 0.00036 |
GUESTROOM402_405 | 2650.64 | 3180.77 | 0.078 | 0.094 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -26.20 | 0.00036 |
GUESTROOM406_408 | 2241.30 | 2689.56 | 0.066 | 0.079 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -26.20 | 0.00036 |
GUESTROOM409_412 | 2676.91 | 3212.29 | 0.079 | 0.095 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -26.20 | 0.00036 |
GUESTROOM413 | 1354.23 | 1625.07 | 0.040 | 0.048 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -26.20 | 0.00036 |
GUESTROOM414 | 1157.12 | 1388.54 | 0.034 | 0.041 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -26.20 | 0.00036 |
GUESTROOM415_418 | 2625.63 | 3150.75 | 0.078 | 0.093 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -26.20 | 0.00036 |
GUESTROOM419 | 806.01 | 967.21 | 0.024 | 0.029 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -26.20 | 0.00036 |
GUESTROOM420_423 | 2576.31 | 3091.57 | 0.076 | 0.091 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -26.20 | 0.00036 |
GUESTROOM424 | 1028.81 | 1234.58 | 0.030 | 0.036 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -26.20 | 0.00036 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | -26.20 | 0.00036 | |
CORRIDORFLR1 | 29336.25 | 35203.50 | 0.866 | 1.039 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -26.20 | 0.00036 |
FRONTSTAIRSFLR1 | 30.61 | 36.73 | 0.001 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -26.20 | 0.00036 |
REARSTAIRSFLR2 | 117.72 | 141.27 | 0.002 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
CORRIDORFLR2 | 1399.59 | 1679.51 | 0.041 | 0.050 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -26.20 | 0.00036 |
FRONTSTAIRSFLR2 | 391.51 | 469.81 | 0.008 | 0.009 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
REARSTAIRSFLR3 | 241.49 | 289.79 | 0.005 | 0.006 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
CORRIDORFLR3 | 1717.95 | 2061.53 | 0.051 | 0.061 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
FRONTSTAIRSFLR3 | 520.46 | 624.56 | 0.010 | 0.012 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
REARSTAIRSFLR4 | 440.19 | 528.23 | 0.009 | 0.011 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
CORRIDORFLR4 | 3175.53 | 3810.63 | 0.094 | 0.113 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
FRONTSTAIRSFLR4 | 750.90 | 901.08 | 0.015 | 0.018 | ROCHESTER INTERNATIONAL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -26.20 | 0.00036 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.33 | 0.33 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.77 | 0.77 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.36 | 0.36 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.71 | 0.71 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.77 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3642.25 | 7597.75 | 3064.00 |
RESTROOMFLR1 | 1741.75 | 7877.00 | 1589.50 |
MEETINGROOMFLR1 | 1479.75 | 3660.50 | 911.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 3291.50 | 8760.00 | 3291.50 |
GUESTROOM104 | 2368.25 | 8717.50 | 2367.75 |
GUESTROOM105 | 591.25 | 8398.00 | 582.25 |
EMPLOYEELOUNGEFLR1 | 2780.50 | 2591.75 | 502.50 |
EXERCISECENTERFLR1 | 1337.75 | 3369.50 | 160.25 |
FRONTOFFICEFLR1 | 2191.75 | 6597.00 | 1505.50 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 2246.25 | 8515.50 | 2244.50 |
GUESTROOM206_208 | 2070.00 | 8506.00 | 2064.50 |
GUESTROOM209_212 | 1942.75 | 8653.25 | 1942.75 |
GUESTROOM213 | 3378.00 | 8724.50 | 3378.00 |
GUESTROOM214 | 2166.25 | 8483.00 | 2159.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3149.25 | 4811.00 | 334.75 |
GUESTROOM220_223 | 998.00 | 8337.75 | 976.50 |
GUESTROOM224 | 2133.25 | 8441.50 | 2125.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 2457.00 | 8656.50 | 2457.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 2912.75 | 8505.00 | 2904.75 |
GUESTROOM315_318 | 1089.00 | 8215.50 | 1022.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1585.25 | 8431.50 | 1571.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4538.50 | 8149.50 | 4286.00 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 3523.25 | 8074.50 | 3204.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 2961.25 | 7857.25 | 2438.00 |
GUESTROOM419 | 2884.25 | 7991.50 | 2561.00 |
GUESTROOM420_423 | 3039.50 | 7892.50 | 2533.00 |
GUESTROOM424 | 3682.50 | 8096.00 | 3400.75 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7592.75 | 8760.00 | 6646.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
RESTROOMFLR1 | 1267.50 | 346.50 | 1267.50 | 346.50 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 30.25 | 29.50 | 30.25 | 29.50 |
GUESTROOM104 | 18.00 | 33.75 | 18.00 | 33.75 |
GUESTROOM105 | 2.75 | 42.25 | 2.75 | 42.25 |
EMPLOYEELOUNGEFLR1 | 902.50 | 1012.50 | 645.25 | 594.00 |
EXERCISECENTERFLR1 | 0.25 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 25.50 | 20.25 | 25.50 | 20.25 |
GUESTROOM206_208 | 24.75 | 26.75 | 24.75 | 26.75 |
GUESTROOM209_212 | 25.00 | 19.75 | 25.00 | 19.75 |
GUESTROOM213 | 25.75 | 20.00 | 25.75 | 20.00 |
GUESTROOM214 | 16.75 | 25.75 | 16.75 | 25.75 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2077.00 | 0.00 | 2077.00 |
GUESTROOM220_223 | 8.75 | 24.50 | 8.75 | 24.50 |
GUESTROOM224 | 17.75 | 26.00 | 17.75 | 26.00 |
GUESTROOM301 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 29.50 | 19.75 | 29.50 | 19.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 24.00 | 25.25 | 24.00 | 25.25 |
GUESTROOM315_318 | 9.25 | 26.25 | 9.25 | 26.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 16.75 | 23.50 | 16.75 | 23.50 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 55.75 | 27.75 | 55.75 | 27.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 31.50 | 26.50 | 31.50 | 26.50 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 23.50 | 28.75 | 23.50 | 28.75 |
GUESTROOM419 | 21.50 | 31.25 | 21.50 | 31.25 |
GUESTROOM420_423 | 23.25 | 28.50 | 23.25 | 28.50 |
GUESTROOM424 | 17.50 | 29.50 | 17.50 | 29.50 |
REARSTAIRSFLR1 | 5.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 12.25 | 2475.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 5.75 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 11.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 62.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 21.75 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 37.75 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 33.75 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 50.50 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 4.25 | 194.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 34.50 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1539.50 | 3709.50 | 1478.00 | 2737.25 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.009371 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.012457 |
REARSTAIRSFLR4 UNITHEATER | 0.010536 |
FRONTSTAIRSFLR4 UNITHEATER | 0.017971 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.009371 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.012457 |
REARSTAIRSFLR4UNITHEATERFAN | 0.010536 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.017971 |
SAC_FRONTOFFICE SUPPLY FAN | 0.325201 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.766331 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.714251 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 306.55 |
CORRIDORFLR1 PTAC HEATING COIL | 37770.87 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1202.50 |
102 PTAC HEATING COIL | 1222.89 |
103 PTAC HEATING COIL | 1695.93 |
104 PTAC HEATING COIL | 1673.99 |
105 PTAC HEATING COIL | 1219.11 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 545.65 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 545.78 |
CORRIDORFLR2 PTAC HEATING COIL | 3796.81 |
201 PTAC HEATING COIL | 1514.06 |
202_205 PTAC HEATING COIL | 4809.99 |
206_208 PTAC HEATING COIL | 3812.08 |
209_212 PTAC HEATING COIL | 4809.99 |
213 PTAC HEATING COIL | 1784.82 |
214 PTAC HEATING COIL | 1676.67 |
215_218 PTAC HEATING COIL | 4809.65 |
219 PTAC HEATING COIL | 1202.41 |
220_223 PTAC HEATING COIL | 4809.65 |
224 PTAC HEATING COIL | 1458.59 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 708.92 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 545.78 |
CORRIDORFLR3 PTAC HEATING COIL | 4178.87 |
301 PTAC HEATING COIL | 1577.36 |
302_305 PTAC HEATING COIL | 4809.99 |
306_308 PTAC HEATING COIL | 3927.86 |
309_312 PTAC HEATING COIL | 4821.40 |
313 PTAC HEATING COIL | 1921.76 |
314 PTAC HEATING COIL | 1743.79 |
315_318 PTAC HEATING COIL | 4809.65 |
319 PTAC HEATING COIL | 1278.28 |
320_323 PTAC HEATING COIL | 4809.65 |
324 PTAC HEATING COIL | 1554.18 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 863.64 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 767.39 |
CORRIDORFLR4 PTAC HEATING COIL | 5927.94 |
401 PTAC HEATING COIL | 1962.84 |
402_405 PTAC HEATING COIL | 6167.20 |
406_408 PTAC HEATING COIL | 5056.41 |
409_412 PTAC HEATING COIL | 6198.71 |
413 PTAC HEATING COIL | 2371.68 |
414 PTAC HEATING COIL | 2135.09 |
415_418 PTAC HEATING COIL | 6136.96 |
419 PTAC HEATING COIL | 1713.76 |
420_423 PTAC HEATING COIL | 6077.78 |
424 PTAC HEATING COIL | 1981.13 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 1140.13 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.710925 | 0.325201 | 7070.36 |
SAC_FRONTLOUNGE COOLING COIL | 0.676083 | 0.766331 | 19029.83 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.360948 | 8963.19 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.728623 | 0.714251 | 14605.47 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.766331 |
RESTROOMFLR1 DIRECT AIR | 0.043286 |
MEETINGROOMFLR1 DIRECT AIR | 0.360948 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.552147 |
EXERCISECENTERFLR1 DIRECT AIR | 0.118818 |
FRONTOFFICEFLR1 DIRECT AIR | 0.325201 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.325201 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.766331 |
SAC_MEETINGROOM MAIN BRANCH | 0.360948 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.714251 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.325201 |
SAC_FRONTLOUNGE | 0.766331 |
SAC_MEETINGROOM | 0.360948 |
SAC_EXC_EMPLGE_RESTRM | 0.714251 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.325201 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.766331 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.360948 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.714251 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.325201 | 0.325201 | 0.325201 | 0.325201 | 4951.35 | 7070.36 | 1.00 |
SAC_FRONTLOUNGE | 0.766331 | 0.766331 | 0.766331 | 0.766331 | 20753.49 | 19029.83 | 1.00 |
SAC_MEETINGROOM | 0.360948 | 0.360948 | 0.360948 | 0.360948 | 11113.34 | 8963.19 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.714251 | 0.714251 | 0.714251 | 0.714251 | 8503.27 | 14605.47 | 0.166353 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4951.35 |
SAC_FRONTLOUNGE HEATING COIL | 20753.49 |
SAC_MEETINGROOM HEATING COIL | 11113.34 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 8503.27 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.360948 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.88 | -12.6 |
February | 14.21 | -7.7 |
March | 16.25 | 0.33 |
April | 18.90 | 7.02 |
May | 21.33 | 14.19 |
June | 22.93 | 19.16 |
July | 23.58 | 20.92 |
August | 23.23 | 20.05 |
September | 21.85 | 15.39 |
October | 19.19 | 7.43 |
November | 16.35 | -0.0 |
December | 14.09 | -7.6 |
Annual Sum or Average | 18.76 | 6.46 |
Minimum of Months | 12.88 | -12.6 |
Maximum of Months | 23.58 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.33 | -12.6 |
February | 21.70 | -7.7 |
March | 22.34 | 0.33 |
April | 23.35 | 7.02 |
May | 24.37 | 14.19 |
June | 25.33 | 19.16 |
July | 25.74 | 20.92 |
August | 25.56 | 20.05 |
September | 24.63 | 15.39 |
October | 23.42 | 7.43 |
November | 22.40 | -0.0 |
December | 21.51 | -7.6 |
Annual Sum or Average | 23.48 | 6.46 |
Minimum of Months | 21.33 | -12.6 |
Maximum of Months | 25.74 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.63 | -12.6 |
February | 13.84 | -7.7 |
March | 15.84 | 0.33 |
April | 18.40 | 7.02 |
May | 20.85 | 14.19 |
June | 22.47 | 19.16 |
July | 23.08 | 20.92 |
August | 22.71 | 20.05 |
September | 21.26 | 15.39 |
October | 18.56 | 7.43 |
November | 15.95 | -0.0 |
December | 13.77 | -7.6 |
Annual Sum or Average | 18.30 | 6.46 |
Minimum of Months | 12.63 | -12.6 |
Maximum of Months | 23.08 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -12.6 |
February | 21.11 | -7.7 |
March | 21.18 | 0.33 |
April | 21.56 | 7.02 |
May | 22.38 | 14.19 |
June | 23.10 | 19.16 |
July | 23.47 | 20.92 |
August | 23.30 | 20.05 |
September | 22.56 | 15.39 |
October | 21.43 | 7.43 |
November | 21.23 | -0.0 |
December | 21.11 | -7.6 |
Annual Sum or Average | 21.97 | 6.46 |
Minimum of Months | 21.11 | -12.6 |
Maximum of Months | 23.47 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -12.6 |
February | 20.97 | -7.7 |
March | 21.56 | 0.33 |
April | 22.19 | 7.02 |
May | 22.93 | 14.19 |
June | 23.37 | 19.16 |
July | 23.55 | 20.92 |
August | 23.46 | 20.05 |
September | 23.00 | 15.39 |
October | 22.24 | 7.43 |
November | 21.62 | -0.0 |
December | 20.93 | -7.6 |
Annual Sum or Average | 22.21 | 6.46 |
Minimum of Months | 20.60 | -12.6 |
Maximum of Months | 23.55 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | -12.6 |
February | 21.16 | -7.7 |
March | 21.44 | 0.33 |
April | 22.04 | 7.02 |
May | 23.22 | 14.19 |
June | 23.58 | 19.16 |
July | 23.76 | 20.92 |
August | 23.72 | 20.05 |
September | 23.24 | 15.39 |
October | 22.11 | 7.43 |
November | 21.55 | -0.0 |
December | 21.15 | -7.6 |
Annual Sum or Average | 22.35 | 6.46 |
Minimum of Months | 21.13 | -12.6 |
Maximum of Months | 23.76 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.88 | -12.6 |
February | 23.13 | -7.7 |
March | 23.74 | 0.33 |
April | 24.53 | 7.02 |
May | 25.54 | 14.19 |
June | 26.09 | 19.16 |
July | 26.35 | 20.92 |
August | 26.28 | 20.05 |
September | 25.78 | 15.39 |
October | 24.78 | 7.43 |
November | 23.94 | -0.0 |
December | 23.15 | -7.6 |
Annual Sum or Average | 24.69 | 6.46 |
Minimum of Months | 22.88 | -12.6 |
Maximum of Months | 26.35 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -12.6 |
February | 18.94 | -7.7 |
March | 19.42 | 0.33 |
April | 20.45 | 7.02 |
May | 22.09 | 14.19 |
June | 22.82 | 19.16 |
July | 23.16 | 20.92 |
August | 23.05 | 20.05 |
September | 22.24 | 15.39 |
October | 20.61 | 7.43 |
November | 19.62 | -0.0 |
December | 18.90 | -7.6 |
Annual Sum or Average | 20.86 | 6.46 |
Minimum of Months | 18.90 | -12.6 |
Maximum of Months | 23.16 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.90 | -7.7 |
March | 19.27 | 0.33 |
April | 20.20 | 7.02 |
May | 21.79 | 14.19 |
June | 22.63 | 19.16 |
July | 23.03 | 20.92 |
August | 22.88 | 20.05 |
September | 21.97 | 15.39 |
October | 20.25 | 7.43 |
November | 19.45 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.69 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.03 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -12.6 |
February | 20.50 | -7.7 |
March | 20.66 | 0.33 |
April | 21.00 | 7.02 |
May | 21.54 | 14.19 |
June | 21.67 | 19.16 |
July | 21.74 | 20.92 |
August | 21.74 | 20.05 |
September | 21.56 | 15.39 |
October | 21.09 | 7.43 |
November | 20.74 | -0.0 |
December | 20.48 | -7.6 |
Annual Sum or Average | 21.10 | 6.46 |
Minimum of Months | 20.47 | -12.6 |
Maximum of Months | 21.74 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -12.6 |
February | 20.66 | -7.7 |
March | 20.87 | 0.33 |
April | 21.21 | 7.02 |
May | 21.63 | 14.19 |
June | 21.70 | 19.16 |
July | 21.75 | 20.92 |
August | 21.74 | 20.05 |
September | 21.65 | 15.39 |
October | 21.39 | 7.43 |
November | 20.93 | -0.0 |
December | 20.59 | -7.6 |
Annual Sum or Average | 21.22 | 6.46 |
Minimum of Months | 20.52 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | -12.6 |
February | 21.01 | -7.7 |
March | 21.29 | 0.33 |
April | 21.51 | 7.02 |
May | 21.73 | 14.19 |
June | 21.74 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.73 | 15.39 |
October | 21.65 | 7.43 |
November | 21.30 | -0.0 |
December | 20.97 | -7.6 |
Annual Sum or Average | 21.44 | 6.46 |
Minimum of Months | 20.77 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | -12.6 |
February | 21.63 | -7.7 |
March | 22.12 | 0.33 |
April | 22.32 | 7.02 |
May | 22.52 | 14.19 |
June | 22.50 | 19.16 |
July | 22.48 | 20.92 |
August | 22.48 | 20.05 |
September | 22.38 | 15.39 |
October | 22.30 | 7.43 |
November | 22.06 | -0.0 |
December | 21.57 | -7.6 |
Annual Sum or Average | 22.13 | 6.46 |
Minimum of Months | 21.16 | -12.6 |
Maximum of Months | 22.52 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.50 | -12.6 |
February | 49.98 | -7.7 |
March | 50.57 | 0.33 |
April | 51.32 | 7.02 |
May | 52.06 | 14.19 |
June | 52.55 | 19.16 |
July | 52.84 | 20.92 |
August | 52.77 | 20.05 |
September | 52.40 | 15.39 |
October | 51.62 | 7.43 |
November | 50.63 | -0.0 |
December | 49.87 | -7.6 |
Annual Sum or Average | 51.35 | 6.46 |
Minimum of Months | 49.50 | -12.6 |
Maximum of Months | 52.84 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 66.27 | -12.6 |
February | 66.68 | -7.7 |
March | 67.31 | 0.33 |
April | 68.31 | 7.02 |
May | 69.39 | 14.19 |
June | 70.08 | 19.16 |
July | 70.46 | 20.92 |
August | 70.28 | 20.05 |
September | 69.74 | 15.39 |
October | 68.66 | 7.43 |
November | 67.47 | -0.0 |
December | 66.62 | -7.6 |
Annual Sum or Average | 68.45 | 6.46 |
Minimum of Months | 66.27 | -12.6 |
Maximum of Months | 70.46 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -12.6 |
February | 22.16 | -7.7 |
March | 22.68 | 0.33 |
April | 23.12 | 7.02 |
May | 23.57 | 14.19 |
June | 23.77 | 19.16 |
July | 23.86 | 20.92 |
August | 23.84 | 20.05 |
September | 23.61 | 15.39 |
October | 23.20 | 7.43 |
November | 22.67 | -0.0 |
December | 22.07 | -7.6 |
Annual Sum or Average | 23.03 | 6.46 |
Minimum of Months | 21.72 | -12.6 |
Maximum of Months | 23.86 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | -12.6 |
February | 21.45 | -7.7 |
March | 21.90 | 0.33 |
April | 22.57 | 7.02 |
May | 23.50 | 14.19 |
June | 23.76 | 19.16 |
July | 23.87 | 20.92 |
August | 23.86 | 20.05 |
September | 23.52 | 15.39 |
October | 22.80 | 7.43 |
November | 22.00 | -0.0 |
December | 21.34 | -7.6 |
Annual Sum or Average | 22.66 | 6.46 |
Minimum of Months | 21.23 | -12.6 |
Maximum of Months | 23.87 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.81 | -12.6 |
February | 13.22 | -7.7 |
March | 15.51 | 0.33 |
April | 18.46 | 7.02 |
May | 21.30 | 14.19 |
June | 23.18 | 19.16 |
July | 23.93 | 20.92 |
August | 23.54 | 20.05 |
September | 22.00 | 15.39 |
October | 18.85 | 7.43 |
November | 15.66 | -0.0 |
December | 13.13 | -7.6 |
Annual Sum or Average | 18.41 | 6.46 |
Minimum of Months | 11.81 | -12.6 |
Maximum of Months | 23.93 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.02 | -12.6 |
February | 17.81 | -7.7 |
March | 19.09 | 0.33 |
April | 20.80 | 7.02 |
May | 22.51 | 14.19 |
June | 23.56 | 19.16 |
July | 24.00 | 20.92 |
August | 23.83 | 20.05 |
September | 22.99 | 15.39 |
October | 21.17 | 7.43 |
November | 19.26 | -0.0 |
December | 17.69 | -7.6 |
Annual Sum or Average | 20.83 | 6.46 |
Minimum of Months | 17.02 | -12.6 |
Maximum of Months | 24.00 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.37 | -12.6 |
February | 12.90 | -7.7 |
March | 15.35 | 0.33 |
April | 18.63 | 7.02 |
May | 21.67 | 14.19 |
June | 23.56 | 19.16 |
July | 24.31 | 20.92 |
August | 23.86 | 20.05 |
September | 22.21 | 15.39 |
October | 18.91 | 7.43 |
November | 15.44 | -0.0 |
December | 12.75 | -7.6 |
Annual Sum or Average | 18.44 | 6.46 |
Minimum of Months | 11.37 | -12.6 |
Maximum of Months | 24.31 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -12.6 |
February | 21.20 | -7.7 |
March | 21.63 | 0.33 |
April | 22.51 | 7.02 |
May | 23.70 | 14.19 |
June | 23.85 | 19.16 |
July | 23.90 | 20.92 |
August | 23.90 | 20.05 |
September | 23.63 | 15.39 |
October | 22.73 | 7.43 |
November | 21.79 | -0.0 |
December | 21.13 | -7.6 |
Annual Sum or Average | 22.60 | 6.46 |
Minimum of Months | 21.12 | -12.6 |
Maximum of Months | 23.90 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.17 | -12.6 |
February | 11.73 | -7.7 |
March | 14.30 | 0.33 |
April | 17.57 | 7.02 |
May | 20.80 | 14.19 |
June | 22.84 | 19.16 |
July | 23.59 | 20.92 |
August | 23.10 | 20.05 |
September | 21.24 | 15.39 |
October | 17.65 | 7.43 |
November | 14.37 | -0.0 |
December | 11.57 | -7.6 |
Annual Sum or Average | 17.44 | 6.46 |
Minimum of Months | 10.17 | -12.6 |
Maximum of Months | 23.59 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 19.10 | 0.33 |
April | 19.97 | 7.02 |
May | 21.93 | 14.19 |
June | 22.79 | 19.16 |
July | 23.23 | 20.92 |
August | 23.13 | 20.05 |
September | 21.96 | 15.39 |
October | 19.67 | 7.43 |
November | 19.22 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.65 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.23 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -12.6 |
February | 20.56 | -7.7 |
March | 20.78 | 0.33 |
April | 21.13 | 7.02 |
May | 21.67 | 14.19 |
June | 21.72 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.64 | 15.39 |
October | 21.23 | 7.43 |
November | 20.83 | -0.0 |
December | 20.50 | -7.6 |
Annual Sum or Average | 21.17 | 6.46 |
Minimum of Months | 20.49 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -12.6 |
February | 20.58 | -7.7 |
March | 20.81 | 0.33 |
April | 21.17 | 7.02 |
May | 21.68 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.66 | 15.39 |
October | 21.28 | 7.43 |
November | 20.87 | -0.0 |
December | 20.51 | -7.6 |
Annual Sum or Average | 21.19 | 6.46 |
Minimum of Months | 20.49 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -12.6 |
February | 20.58 | -7.7 |
March | 20.82 | 0.33 |
April | 21.19 | 7.02 |
May | 21.69 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.67 | 15.39 |
October | 21.32 | 7.43 |
November | 20.89 | -0.0 |
December | 20.51 | -7.6 |
Annual Sum or Average | 21.20 | 6.46 |
Minimum of Months | 20.49 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -12.6 |
February | 20.49 | -7.7 |
March | 20.64 | 0.33 |
April | 20.98 | 7.02 |
May | 21.58 | 14.19 |
June | 21.69 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.57 | 15.39 |
October | 21.04 | 7.43 |
November | 20.71 | -0.0 |
December | 20.47 | -7.6 |
Annual Sum or Average | 21.10 | 6.46 |
Minimum of Months | 20.47 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -12.6 |
February | 20.67 | -7.7 |
March | 20.90 | 0.33 |
April | 21.27 | 7.02 |
May | 21.70 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.69 | 15.39 |
October | 21.46 | 7.43 |
November | 20.95 | -0.0 |
December | 20.58 | -7.6 |
Annual Sum or Average | 21.25 | 6.46 |
Minimum of Months | 20.52 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | -12.6 |
February | 21.85 | -7.7 |
March | 22.65 | 0.33 |
April | 23.09 | 7.02 |
May | 23.33 | 14.19 |
June | 23.33 | 19.16 |
July | 23.33 | 20.92 |
August | 23.33 | 20.05 |
September | 23.32 | 15.39 |
October | 23.24 | 7.43 |
November | 22.53 | -0.0 |
December | 21.73 | -7.6 |
Annual Sum or Average | 22.74 | 6.46 |
Minimum of Months | 21.07 | -12.6 |
Maximum of Months | 23.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 28.79 | -12.6 |
February | 29.27 | -7.7 |
March | 30.00 | 0.33 |
April | 31.14 | 7.02 |
May | 32.42 | 14.19 |
June | 33.03 | 19.16 |
July | 33.33 | 20.92 |
August | 33.20 | 20.05 |
September | 32.63 | 15.39 |
October | 31.37 | 7.43 |
November | 30.09 | -0.0 |
December | 29.13 | -7.6 |
Annual Sum or Average | 31.21 | 6.46 |
Minimum of Months | 28.79 | -12.6 |
Maximum of Months | 33.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | -12.6 |
February | 21.72 | -7.7 |
March | 21.84 | 0.33 |
April | 22.08 | 7.02 |
May | 22.42 | 14.19 |
June | 22.78 | 19.16 |
July | 22.93 | 20.92 |
August | 22.88 | 20.05 |
September | 22.52 | 15.39 |
October | 22.05 | 7.43 |
November | 21.85 | -0.0 |
December | 21.72 | -7.6 |
Annual Sum or Average | 22.21 | 6.46 |
Minimum of Months | 21.69 | -12.6 |
Maximum of Months | 22.93 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -12.6 |
February | 20.82 | -7.7 |
March | 21.10 | 0.33 |
April | 21.39 | 7.02 |
May | 21.73 | 14.19 |
June | 21.74 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.72 | 15.39 |
October | 21.57 | 7.43 |
November | 21.12 | -0.0 |
December | 20.75 | -7.6 |
Annual Sum or Average | 21.34 | 6.46 |
Minimum of Months | 20.60 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -12.6 |
February | 20.67 | -7.7 |
March | 20.91 | 0.33 |
April | 21.26 | 7.02 |
May | 21.70 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.69 | 15.39 |
October | 21.45 | 7.43 |
November | 20.96 | -0.0 |
December | 20.60 | -7.6 |
Annual Sum or Average | 21.25 | 6.46 |
Minimum of Months | 20.52 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.17 | -12.6 |
February | 16.17 | -7.7 |
March | 17.76 | 0.33 |
April | 20.08 | 7.02 |
May | 22.43 | 14.19 |
June | 23.81 | 19.16 |
July | 24.37 | 20.92 |
August | 24.09 | 20.05 |
September | 22.95 | 15.39 |
October | 20.42 | 7.43 |
November | 17.92 | -0.0 |
December | 15.90 | -7.6 |
Annual Sum or Average | 20.11 | 6.46 |
Minimum of Months | 15.17 | -12.6 |
Maximum of Months | 24.37 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.70 | -12.6 |
February | 11.30 | -7.7 |
March | 13.95 | 0.33 |
April | 17.76 | 7.02 |
May | 21.53 | 14.19 |
June | 23.89 | 19.16 |
July | 24.80 | 20.92 |
August | 24.24 | 20.05 |
September | 22.28 | 15.39 |
October | 18.13 | 7.43 |
November | 14.11 | -0.0 |
December | 10.99 | -7.6 |
Annual Sum or Average | 17.76 | 6.46 |
Minimum of Months | 9.70 | -12.6 |
Maximum of Months | 24.80 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.37 | -12.6 |
February | 11.94 | -7.7 |
March | 14.47 | 0.33 |
April | 18.02 | 7.02 |
May | 21.46 | 14.19 |
June | 23.59 | 19.16 |
July | 24.44 | 20.92 |
August | 23.91 | 20.05 |
September | 21.99 | 15.39 |
October | 18.21 | 7.43 |
November | 14.53 | -0.0 |
December | 11.71 | -7.6 |
Annual Sum or Average | 17.92 | 6.46 |
Minimum of Months | 10.37 | -12.6 |
Maximum of Months | 24.44 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -12.6 |
February | 21.11 | -7.7 |
March | 21.22 | 0.33 |
April | 21.80 | 7.02 |
May | 23.14 | 14.19 |
June | 23.60 | 19.16 |
July | 23.87 | 20.92 |
August | 23.83 | 20.05 |
September | 23.11 | 15.39 |
October | 21.60 | 7.43 |
November | 21.32 | -0.0 |
December | 21.11 | -7.6 |
Annual Sum or Average | 22.24 | 6.46 |
Minimum of Months | 21.11 | -12.6 |
Maximum of Months | 23.87 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.53 | -12.6 |
February | 10.24 | -7.7 |
March | 13.07 | 0.33 |
April | 16.68 | 7.02 |
May | 20.45 | 14.19 |
June | 22.88 | 19.16 |
July | 23.80 | 20.92 |
August | 23.21 | 20.05 |
September | 20.91 | 15.39 |
October | 16.61 | 7.43 |
November | 13.08 | -0.0 |
December | 10.06 | -7.6 |
Annual Sum or Average | 16.66 | 6.46 |
Minimum of Months | 8.53 | -12.6 |
Maximum of Months | 23.80 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 18.97 | 0.33 |
April | 19.72 | 7.02 |
May | 21.54 | 14.19 |
June | 22.61 | 19.16 |
July | 23.17 | 20.92 |
August | 23.03 | 20.05 |
September | 21.61 | 15.39 |
October | 19.27 | 7.43 |
November | 19.03 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.48 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.17 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 19.03 | 0.33 |
April | 19.84 | 7.02 |
May | 21.73 | 14.19 |
June | 22.71 | 19.16 |
July | 23.22 | 20.92 |
August | 23.11 | 20.05 |
September | 21.76 | 15.39 |
October | 19.42 | 7.43 |
November | 19.11 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.56 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.22 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 19.07 | 0.33 |
April | 19.90 | 7.02 |
May | 21.81 | 14.19 |
June | 22.74 | 19.16 |
July | 23.21 | 20.92 |
August | 23.10 | 20.05 |
September | 21.80 | 15.39 |
October | 19.51 | 7.43 |
November | 19.15 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.59 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.21 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -12.6 |
February | 20.54 | -7.7 |
March | 20.76 | 0.33 |
April | 21.12 | 7.02 |
May | 21.66 | 14.19 |
June | 21.72 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.63 | 15.39 |
October | 21.21 | 7.43 |
November | 20.81 | -0.0 |
December | 20.49 | -7.6 |
Annual Sum or Average | 21.16 | 6.46 |
Minimum of Months | 20.48 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 18.98 | 0.33 |
April | 19.78 | 7.02 |
May | 21.60 | 14.19 |
June | 22.68 | 19.16 |
July | 23.19 | 20.92 |
August | 23.07 | 20.05 |
September | 21.71 | 15.39 |
October | 19.36 | 7.43 |
November | 19.12 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.52 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.19 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -12.6 |
February | 20.57 | -7.7 |
March | 20.75 | 0.33 |
April | 21.12 | 7.02 |
May | 21.64 | 14.19 |
June | 21.70 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.63 | 15.39 |
October | 21.28 | 7.43 |
November | 20.82 | -0.0 |
December | 20.51 | -7.6 |
Annual Sum or Average | 21.17 | 6.46 |
Minimum of Months | 20.49 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -12.6 |
February | 20.84 | -7.7 |
March | 21.12 | 0.33 |
April | 21.42 | 7.02 |
May | 21.73 | 14.19 |
June | 21.75 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.73 | 15.39 |
October | 21.60 | 7.43 |
November | 21.13 | -0.0 |
December | 20.75 | -7.6 |
Annual Sum or Average | 21.35 | 6.46 |
Minimum of Months | 20.60 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.08 | -12.6 |
February | 20.74 | -7.7 |
March | 21.71 | 0.33 |
April | 23.20 | 7.02 |
May | 24.92 | 14.19 |
June | 25.68 | 19.16 |
July | 26.02 | 20.92 |
August | 25.88 | 20.05 |
September | 25.08 | 15.39 |
October | 23.37 | 7.43 |
November | 21.75 | -0.0 |
December | 20.51 | -7.6 |
Annual Sum or Average | 23.26 | 6.46 |
Minimum of Months | 20.08 | -12.6 |
Maximum of Months | 26.02 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.09 | -12.6 |
February | 19.64 | -7.7 |
March | 20.49 | 0.33 |
April | 21.76 | 7.02 |
May | 23.12 | 14.19 |
June | 23.27 | 19.16 |
July | 23.33 | 20.92 |
August | 23.33 | 20.05 |
September | 23.03 | 15.39 |
October | 22.17 | 7.43 |
November | 20.55 | -0.0 |
December | 19.27 | -7.6 |
Annual Sum or Average | 21.60 | 6.46 |
Minimum of Months | 19.09 | -12.6 |
Maximum of Months | 23.33 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -12.6 |
February | 20.73 | -7.7 |
March | 20.98 | 0.33 |
April | 21.29 | 7.02 |
May | 21.70 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.69 | 15.39 |
October | 21.47 | 7.43 |
November | 21.00 | -0.0 |
December | 20.65 | -7.6 |
Annual Sum or Average | 21.28 | 6.46 |
Minimum of Months | 20.54 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -12.6 |
February | 18.94 | -7.7 |
March | 19.30 | 0.33 |
April | 20.35 | 7.02 |
May | 22.20 | 14.19 |
June | 22.87 | 19.16 |
July | 23.24 | 20.92 |
August | 23.18 | 20.05 |
September | 22.29 | 15.39 |
October | 20.42 | 7.43 |
November | 19.50 | -0.0 |
December | 18.90 | -7.6 |
Annual Sum or Average | 20.85 | 6.46 |
Minimum of Months | 18.90 | -12.6 |
Maximum of Months | 23.24 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.83 | -12.6 |
February | 14.87 | -7.7 |
March | 16.58 | 0.33 |
April | 19.27 | 7.02 |
May | 22.17 | 14.19 |
June | 23.87 | 19.16 |
July | 24.57 | 20.92 |
August | 24.20 | 20.05 |
September | 22.70 | 15.39 |
October | 19.51 | 7.43 |
November | 16.74 | -0.0 |
December | 14.50 | -7.6 |
Annual Sum or Average | 19.42 | 6.46 |
Minimum of Months | 13.83 | -12.6 |
Maximum of Months | 24.57 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.78 | -12.6 |
February | 10.31 | -7.7 |
March | 12.86 | 0.33 |
April | 17.05 | 7.02 |
May | 21.32 | 14.19 |
June | 23.98 | 19.16 |
July | 25.02 | 20.92 |
August | 24.35 | 20.05 |
September | 22.07 | 15.39 |
October | 17.32 | 7.43 |
November | 13.08 | -0.0 |
December | 9.78 | -7.6 |
Annual Sum or Average | 17.20 | 6.46 |
Minimum of Months | 8.78 | -12.6 |
Maximum of Months | 25.02 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.14 | -12.6 |
February | 10.81 | -7.7 |
March | 13.35 | 0.33 |
April | 17.25 | 7.02 |
May | 21.18 | 14.19 |
June | 23.66 | 19.16 |
July | 24.66 | 20.92 |
August | 24.01 | 20.05 |
September | 21.60 | 15.39 |
October | 17.22 | 7.43 |
November | 13.30 | -0.0 |
December | 10.35 | -7.6 |
Annual Sum or Average | 17.25 | 6.46 |
Minimum of Months | 9.14 | -12.6 |
Maximum of Months | 24.66 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -12.6 |
February | 21.11 | -7.7 |
March | 21.21 | 0.33 |
April | 21.72 | 7.02 |
May | 22.72 | 14.19 |
June | 23.37 | 19.16 |
July | 23.71 | 20.92 |
August | 23.56 | 20.05 |
September | 22.70 | 15.39 |
October | 21.43 | 7.43 |
November | 21.20 | -0.0 |
December | 21.11 | -7.6 |
Annual Sum or Average | 22.08 | 6.46 |
Minimum of Months | 21.11 | -12.6 |
Maximum of Months | 23.71 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 7.15 | -12.6 |
February | 9.09 | -7.7 |
March | 12.27 | 0.33 |
April | 16.17 | 7.02 |
May | 20.25 | 14.19 |
June | 22.94 | 19.16 |
July | 23.96 | 20.92 |
August | 23.26 | 20.05 |
September | 20.58 | 15.39 |
October | 15.90 | 7.43 |
November | 12.09 | -0.0 |
December | 8.86 | -7.6 |
Annual Sum or Average | 16.08 | 6.46 |
Minimum of Months | 7.15 | -12.6 |
Maximum of Months | 23.96 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -12.6 |
February | 20.45 | -7.7 |
March | 20.58 | 0.33 |
April | 20.92 | 7.02 |
May | 21.59 | 14.19 |
June | 21.68 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.51 | 15.39 |
October | 20.83 | 7.43 |
November | 20.61 | -0.0 |
December | 20.46 | -7.6 |
Annual Sum or Average | 21.05 | 6.46 |
Minimum of Months | 20.45 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 19.02 | 0.33 |
April | 19.76 | 7.02 |
May | 21.41 | 14.19 |
June | 22.44 | 19.16 |
July | 23.02 | 20.92 |
August | 22.80 | 20.05 |
September | 21.36 | 15.39 |
October | 19.28 | 7.43 |
November | 19.00 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.41 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.02 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 19.04 | 0.33 |
April | 19.79 | 7.02 |
May | 21.45 | 14.19 |
June | 22.45 | 19.16 |
July | 23.00 | 20.92 |
August | 22.78 | 20.05 |
September | 21.37 | 15.39 |
October | 19.32 | 7.43 |
November | 19.02 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.42 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.00 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -12.6 |
February | 20.51 | -7.7 |
March | 20.73 | 0.33 |
April | 21.13 | 7.02 |
May | 21.69 | 14.19 |
June | 21.72 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.63 | 15.39 |
October | 21.17 | 7.43 |
November | 20.76 | -0.0 |
December | 20.48 | -7.6 |
Annual Sum or Average | 21.15 | 6.46 |
Minimum of Months | 20.47 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.89 | -7.7 |
March | 18.99 | 0.33 |
April | 19.74 | 7.02 |
May | 21.37 | 14.19 |
June | 22.44 | 19.16 |
July | 23.02 | 20.92 |
August | 22.81 | 20.05 |
September | 21.38 | 15.39 |
October | 19.25 | 7.43 |
November | 19.01 | -0.0 |
December | 18.89 | -7.6 |
Annual Sum or Average | 20.40 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.02 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -12.6 |
February | 18.94 | -7.7 |
March | 19.21 | 0.33 |
April | 20.12 | 7.02 |
May | 21.74 | 14.19 |
June | 22.58 | 19.16 |
July | 23.06 | 20.92 |
August | 22.90 | 20.05 |
September | 21.75 | 15.39 |
October | 19.90 | 7.43 |
November | 19.27 | -0.0 |
December | 18.90 | -7.6 |
Annual Sum or Average | 20.62 | 6.46 |
Minimum of Months | 18.89 | -12.6 |
Maximum of Months | 23.06 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -12.6 |
February | 20.71 | -7.7 |
March | 20.99 | 0.33 |
April | 21.30 | 7.02 |
May | 21.72 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.70 | 15.39 |
October | 21.49 | 7.43 |
November | 20.97 | -0.0 |
December | 20.61 | -7.6 |
Annual Sum or Average | 21.27 | 6.46 |
Minimum of Months | 20.53 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.55 | -12.6 |
February | 18.33 | -7.7 |
March | 19.54 | 0.33 |
April | 21.19 | 7.02 |
May | 23.06 | 14.19 |
June | 24.08 | 19.16 |
July | 24.49 | 20.92 |
August | 24.25 | 20.05 |
September | 23.14 | 15.39 |
October | 21.15 | 7.43 |
November | 19.41 | -0.0 |
December | 18.07 | -7.6 |
Annual Sum or Average | 21.20 | 6.46 |
Minimum of Months | 17.55 | -12.6 |
Maximum of Months | 24.49 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.51 | -12.6 |
February | 20.68 | -7.7 |
March | 20.93 | 0.33 |
April | 21.28 | 7.02 |
May | 21.72 | 14.19 |
June | 21.73 | 19.16 |
July | 21.76 | 20.92 |
August | 21.75 | 20.05 |
September | 21.69 | 15.39 |
October | 21.46 | 7.43 |
November | 20.94 | -0.0 |
December | 20.57 | -7.6 |
Annual Sum or Average | 21.25 | 6.46 |
Minimum of Months | 20.51 | -12.6 |
Maximum of Months | 21.76 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.52 | -12.6 |
February | 20.70 | -7.7 |
March | 20.96 | 0.33 |
April | 21.28 | 7.02 |
May | 21.72 | 14.19 |
June | 21.73 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.69 | 15.39 |
October | 21.46 | 7.43 |
November | 20.95 | -0.0 |
December | 20.59 | -7.6 |
Annual Sum or Average | 21.26 | 6.46 |
Minimum of Months | 20.52 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -12.6 |
February | 20.57 | -7.7 |
March | 20.74 | 0.33 |
April | 21.12 | 7.02 |
May | 21.67 | 14.19 |
June | 21.72 | 19.16 |
July | 21.75 | 20.92 |
August | 21.75 | 20.05 |
September | 21.63 | 15.39 |
October | 21.26 | 7.43 |
November | 20.79 | -0.0 |
December | 20.50 | -7.6 |
Annual Sum or Average | 21.17 | 6.46 |
Minimum of Months | 20.48 | -12.6 |
Maximum of Months | 21.75 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.97 | -12.6 |
February | 14.15 | -7.7 |
March | 16.11 | 0.33 |
April | 18.98 | 7.02 |
May | 22.05 | 14.19 |
June | 23.87 | 19.16 |
July | 24.59 | 20.92 |
August | 24.14 | 20.05 |
September | 22.40 | 15.39 |
October | 19.04 | 7.43 |
November | 16.08 | -0.0 |
December | 13.68 | -7.6 |
Annual Sum or Average | 19.03 | 6.46 |
Minimum of Months | 12.97 | -12.6 |
Maximum of Months | 24.59 | 20.92 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.23 | -12.6 |
February | 9.62 | -7.7 |
March | 12.17 | 0.33 |
April | 16.58 | 7.02 |
May | 21.16 | 14.19 |
June | 24.03 | 19.16 |
July | 25.12 | 20.92 |
August | 24.35 | 20.05 |
September | 21.73 | 15.39 |
October | 16.66 | 7.43 |
November | 12.32 | -0.0 |
December | 8.86 | -7.6 |
Annual Sum or Average | 16.77 | 6.46 |
Minimum of Months | 8.23 | -12.6 |
Maximum of Months | 25.12 | 20.92 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.250668E+12 | 194025.735 | 19-JAN-07:15 | 15177.258 | 39465.561 | 8767.924 | 126418.879 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.194339E+12 | 205907.427 | 02-FEB-07:15 | 15177.258 | 39465.561 | 8800.952 | 138267.543 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.166135E+12 | 143944.669 | 06-MAR-07:15 | 15177.258 | 39465.561 | 8733.209 | 80451.013 | 109.514 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.139335E+12 | 116835.707 | 03-APR-06:15 | 15177.258 | 39465.561 | 8712.865 | 53299.411 | 172.499 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.137046E+12 | 86045.611 | 28-MAY-07:00 | 17566.637 | 43276.576 | 9110.625 | 0.000 | 16083.661 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.146454E+12 | 96492.702 | 30-JUN-07:00 | 17492.219 | 43276.576 | 9110.625 | 0.000 | 26605.170 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.157297E+12 | 94292.518 | 04-JUL-07:00 | 17492.219 | 43276.576 | 9110.625 | 0.000 | 24404.986 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.154523E+12 | 101784.971 | 04-AUG-07:00 | 17492.219 | 43276.576 | 9110.625 | 0.000 | 31897.439 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.137992E+12 | 89592.120 | 08-SEP-07:00 | 17641.054 | 43276.576 | 9110.625 | 0.000 | 19555.753 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.136209E+12 | 97982.650 | 23-OCT-06:15 | 15177.258 | 39465.561 | 8706.324 | 29956.109 | 481.284 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.170522E+12 | 179977.893 | 26-NOV-07:15 | 15177.258 | 39465.561 | 8741.851 | 112353.780 | 43.330 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.219013E+12 | 189992.453 | 09-DEC-07:15 | 13316.689 | 34010.661 | 8766.696 | 129702.294 | 0.000 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.200953E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.136209E+12 | 86045.611 | 13316.689 | 34010.661 | 8706.324 | 0.000 | 0.000 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.250668E+12 | 205907.427 | 17641.054 | 43276.576 | 9110.625 | 138267.543 | 31897.439 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.146548E+12 | 131397.788 | 19-JAN-09:15 | 29063.792 | 40096.028 | 0.000 | 62237.968 | 62237.968 | 62237.968 | 29063.792 |
February | 0.124104E+12 | 137259.763 | 02-FEB-09:15 | 34285.658 | 40096.028 | 0.000 | 62878.077 | 62878.077 | 62878.077 | 34285.658 |
March | 0.120477E+12 | 114826.980 | 04-MAR-10:00 | 12340.676 | 40096.028 | 0.000 | 62390.276 | 62390.276 | 62390.276 | 12340.676 |
April | 0.104196E+12 | 111921.201 | 01-APR-09:45 | 10794.971 | 40096.028 | 0.000 | 61030.202 | 61030.202 | 61030.202 | 10794.971 |
May | 0.962758E+11 | 101544.411 | 02-MAY-10:15 | 2545.983 | 40096.028 | 0.000 | 58902.400 | 58902.400 | 58902.400 | 2545.983 |
June | 0.884838E+11 | 97620.166 | 02-JUN-08:30 | 0.000 | 40096.028 | 0.000 | 57524.138 | 57524.138 | 57524.138 | 0.000 |
July | 0.881160E+11 | 95150.875 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 55054.847 | 55054.847 | 55054.847 | 0.000 |
August | 0.868154E+11 | 93015.069 | 04-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 52919.041 | 52919.041 | 52919.041 | 0.000 |
September | 0.859702E+11 | 95486.495 | 30-SEP-09:15 | 2084.309 | 40096.028 | 0.000 | 53306.158 | 53306.158 | 53306.158 | 2084.309 |
October | 0.958872E+11 | 100380.597 | 28-OCT-09:15 | 4605.642 | 40096.028 | 0.000 | 55678.927 | 55678.927 | 55678.927 | 4605.642 |
November | 0.110347E+12 | 117838.094 | 25-NOV-09:15 | 17787.408 | 40096.028 | 0.000 | 59954.658 | 59954.658 | 59954.658 | 17787.408 |
December | 0.132912E+12 | 128313.022 | 09-DEC-11:30 | 30517.545 | 40096.028 | 0.000 | 57699.448 | 57699.448 | 57699.448 | 30517.545 |
Annual Sum or Average | 0.128013E+13 | 0.000 | ||||||||
Minimum of Months | 0.859702E+11 | 93015.069 | 0.000 | 40096.028 | 0.000 | 52919.041 | 52919.041 | 52919.041 | 0.000 | |
Maximum of Months | 0.146548E+12 | 137259.763 | 34285.658 | 40096.028 | 0.000 | 62878.077 | 62878.077 | 62878.077 | 34285.658 |