Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Albuquerque Intl Sunport NM USA TMY3 WMO#=723650

Simulation Timestamp: 2018-10-19 10:15:36


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2768.66 689.82 743.25
Net Site Energy 2768.66 689.82 743.25
Total Source Energy 6595.85 1643.38 1770.65
Net Source Energy 6595.85 1643.38 1770.65


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 71.82 29.48 0.00 0.00 0.00 0.00
Cooling 290.41 0.00 0.00 0.00 0.00 0.00
Interior Lighting 414.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.80 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 291.73 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 592.00 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1725.69 1042.97 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 71.82 29.48 0.00 0.00 0.00 0.00
Cooling General 290.41 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 414.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.80 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 291.73 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 592.00 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.98 0.00 0.00 0.00 0.00 0.00
HVAC 175.63 166.84 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 463.26 279.99 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.71 0.00 0.00 0.00 0.00 0.00
HVAC 163.00 154.84 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 429.96 259.86 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1725.69 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1725.69 100.00
     
Total On-Site and Utility Electric Sources 1725.69 100.00
Total Electricity End Uses 1725.69 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 177.75
Time Setpoint Not Met During Occupied Cooling 4035.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 5642.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Weather File Albuquerque Intl Sunport NM USA TMY3 WMO#=723650
Latitude [deg] 35.04
Longitude [deg] -106.6
Elevation [m] 1619.00
Time Zone -7.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB -7.90 0.00 -7.90 Wetbulb [C] 3.20 0.00
ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 35.10 13.50 15.70 Wetbulb [C] 4.40 220.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           96.82 2.653 0.426 0.308              
Non-North Total or Average           87.38 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   6115.61 4884.26 1231.35 0.80 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   16452.20 12614.28 3837.92 0.77 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8655.63 6348.43 2307.20 0.73 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   13858.45 11068.12 2790.33 0.80 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 5828.9 3.15 10.76 11.39 10.54
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 15747.7 3.21 10.95 11.59 10.82
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8321.6 3.27 11.15 11.82 11.13
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 13208.8 3.15 10.76 11.39 10.54
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.34 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   18122.04 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   787.90 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   787.90 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   880.55 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   866.09 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   787.84 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.28 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.34 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2234.52 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   861.46 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   3151.59 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   2497.75 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   3151.59 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   915.88 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   874.81 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   3151.37 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   787.84 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   3151.37 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   805.81 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.28 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.34 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   2234.52 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   906.73 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   3151.59 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   2497.75 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   3151.59 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   998.10 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   949.01 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   3151.37 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   787.84 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   3151.37 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   890.22 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.28 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.34 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   3006.94 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1154.93 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   3581.68 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   2939.25 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   3590.71 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   1287.38 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   1236.89 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   3560.71 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   976.03 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   3519.41 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1182.53 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   264.28 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   3244.22 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   13598.06 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   7281.66 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   5515.84 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.37 413.82 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.91 1004.81 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.43 481.81 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.84 926.90 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7544.94 9053.92 0.756 0.908 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.90 0.00565
RESTROOMFLR1 445.21 534.25 0.045 0.053 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:30:00 33.75 0.00565
MEETINGROOMFLR1 3573.32 4287.98 0.358 0.430 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM101 574.14 688.96 0.080 0.096 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 34.49 0.00565
GUESTROOM102 471.24 565.49 0.066 0.079 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 34.49 0.00565
GUESTROOM103 1063.58 1276.29 0.148 0.178 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
GUESTROOM104 1156.40 1387.68 0.161 0.193 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.90 0.00565
GUESTROOM105 1507.57 1809.08 0.210 0.252 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
EMPLOYEELOUNGEFLR1 5357.68 6429.21 0.537 0.645 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
EXERCISECENTERFLR1 1156.95 1388.34 0.116 0.139 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 33.21 0.00565
FRONTOFFICEFLR1 3074.01 3688.81 0.308 0.369 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
GUESTROOM201 816.81 980.17 0.114 0.136 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:45:00 34.93 0.00565
GUESTROOM202_205 4131.91 4958.29 0.575 0.690 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 34.49 0.00565
GUESTROOM206_208 3353.28 4023.94 0.467 0.560 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
GUESTROOM209_212 3945.66 4734.80 0.549 0.659 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 34.29 0.00565
GUESTROOM213 1134.56 1361.48 0.158 0.190 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 31.35 0.00565
GUESTROOM214 1286.88 1544.25 0.179 0.215 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM215_218 9457.48 11348.97 1.317 1.580 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
GUESTROOM219 5405.82 6486.98 0.753 0.903 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM220_223 4440.83 5328.99 0.618 0.742 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
GUESTROOM224 1277.43 1532.92 0.178 0.213 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
GUESTROOM301 645.14 774.17 0.090 0.108 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM302_305 1592.83 1911.40 0.222 0.266 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
GUESTROOM306_308 1396.27 1675.52 0.194 0.233 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
GUESTROOM309_312 3934.59 4721.50 0.548 0.658 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
GUESTROOM313 641.65 769.98 0.089 0.107 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 30.85 0.00565
GUESTROOM314 1210.97 1453.16 0.169 0.202 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.70 0.00565
GUESTROOM315_318 4861.22 5833.46 0.677 0.812 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM319 1079.06 1294.87 0.150 0.180 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM320_323 4248.68 5098.42 0.592 0.710 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM324 712.95 855.54 0.099 0.119 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 35.10 0.00565
GUESTROOM401 1533.73 1840.48 0.214 0.256 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 35.10 0.00565
GUESTROOM402_405 2525.20 3030.24 0.352 0.422 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
GUESTROOM406_408 2158.99 2590.79 0.301 0.361 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
GUESTROOM409_412 5182.92 6219.50 0.722 0.866 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
GUESTROOM413 941.76 1130.11 0.131 0.157 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.90 0.00565
GUESTROOM414 1049.72 1259.66 0.146 0.175 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 35.10 0.00565
GUESTROOM415_418 5674.67 6809.61 0.790 0.948 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565
GUESTROOM419 1569.07 1882.89 0.219 0.262 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
GUESTROOM420_423 5641.53 6769.83 0.786 0.943 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 35.10 0.00565
GUESTROOM424 1602.17 1922.60 0.223 0.268 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 35.10 0.00565
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
CORRIDORFLR1 15504.56 18605.47 1.552 1.863 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 31.86 0.00565
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
CORRIDORFLR2 2716.41 3259.69 0.272 0.326 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 33.21 0.00565
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
CORRIDORFLR3 1322.77 1587.32 0.132 0.159 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 32.87 0.00565
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565
CORRIDORFLR4 2385.53 2862.64 0.239 0.287 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 34.90 0.00565
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN CLG .4% CONDNS DB=>MWB   35.10 0.00565


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1347.01 1616.41 0.046 0.236 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:15:00 -7.90 0.00234
RESTROOMFLR1 65.12 78.14 0.002 0.003 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -7.90 0.00234
MEETINGROOMFLR1 455.19 546.22 0.016 0.126 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:00:00 -7.90 0.00234
GUESTROOM101 189.42 227.30 0.006 0.013 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -7.90 0.00234
GUESTROOM102 234.01 280.81 0.008 0.013 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -7.90 0.00234
GUESTROOM103 404.81 485.77 0.014 0.017 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:30:00 -7.90 0.00234
GUESTROOM104 392.78 471.34 0.013 0.016 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 07:45:00 -7.90 0.00234
GUESTROOM105 231.90 278.28 0.008 0.013 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -7.90 0.00234
EMPLOYEELOUNGEFLR1 202.75 243.30 0.007 0.051 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90 0.00234
EXERCISECENTERFLR1 123.11 147.74 0.004 0.043 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:00:00 -7.90 0.00234
FRONTOFFICEFLR1 837.72 1005.26 0.029 0.056 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 06:30:00 -7.90 0.00234
GUESTROOM201 388.90 466.68 0.013 0.016 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -7.90 0.00234
GUESTROOM202_205 822.09 986.51 0.028 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 10:45:00 -7.90 0.00234
GUESTROOM206_208 636.00 763.20 0.022 0.043 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:00:00 -7.90 0.00234
GUESTROOM209_212 741.09 889.31 0.025 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -7.90 0.00234
GUESTROOM213 434.25 521.10 0.015 0.018 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 11:00:00 -7.90 0.00234
GUESTROOM214 400.05 480.05 0.014 0.016 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 10:15:00 -7.90 0.00234
GUESTROOM215_218 711.41 853.69 0.024 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -7.90 0.00234
GUESTROOM219 157.03 188.44 0.005 0.013 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -7.90 0.00234
GUESTROOM220_223 696.97 836.37 0.024 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:15:00 -7.90 0.00234
GUESTROOM224 342.55 411.06 0.012 0.014 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:15:00 -7.90 0.00234
GUESTROOM301 426.63 511.95 0.015 0.018 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 17:30:00 -7.90 0.00234
GUESTROOM302_305 938.92 1126.71 0.032 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 17:15:00 -7.90 0.00234
GUESTROOM306_308 798.19 957.83 0.027 0.043 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -7.90 0.00234
GUESTROOM309_312 933.58 1120.29 0.032 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 -7.90 0.00234
GUESTROOM313 502.76 603.32 0.017 0.021 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 20:45:00 -7.90 0.00234
GUESTROOM314 461.88 554.26 0.016 0.019 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 15:30:00 -7.90 0.00234
GUESTROOM315_318 906.70 1088.04 0.031 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:00:00 -7.90 0.00234
GUESTROOM319 245.69 294.83 0.008 0.013 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -7.90 0.00234
GUESTROOM320_323 875.36 1050.44 0.030 0.054 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:15:00 -7.90 0.00234
GUESTROOM324 412.89 495.46 0.014 0.017 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 20:00:00 -7.90 0.00234
GUESTROOM401 633.46 760.15 0.022 0.026 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 22:30:00 -7.90 0.00234
GUESTROOM402_405 1668.80 2002.56 0.057 0.069 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 21:45:00 -7.90 0.00234
GUESTROOM406_408 1406.45 1687.74 0.048 0.058 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 18:45:00 -7.90 0.00234
GUESTROOM409_412 1676.33 2011.60 0.057 0.069 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 19:45:00 -7.90 0.00234
GUESTROOM413 743.83 892.60 0.025 0.031 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 23:45:00 -7.90 0.00234
GUESTROOM414 701.78 842.14 0.024 0.029 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 21:00:00 -7.90 0.00234
GUESTROOM415_418 1651.42 1981.71 0.057 0.068 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 17:00:00 -7.90 0.00234
GUESTROOM419 484.40 581.28 0.017 0.020 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 18:00:00 -7.90 0.00234
GUESTROOM420_423 1617.01 1940.41 0.055 0.067 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 19:00:00 -7.90 0.00234
GUESTROOM424 656.48 787.78 0.023 0.027 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 24:00:00 -7.90 0.00234
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
CORRIDORFLR1 13976.51 16771.81 0.479 0.574 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 08:00:00 -7.90 0.00234
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
CORRIDORFLR2 406.40 487.68 0.014 0.038 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 09:45:00 -7.90 0.00234
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
CORRIDORFLR3 629.33 755.20 0.022 0.038 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -7.90 0.00234
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234
CORRIDORFLR4 1572.79 1887.35 0.054 0.065 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB 12/21 13:30:00 -7.90 0.00234
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 ALBUQUERQUE.INTL.SUNPORT_NM_USA ANN HTG 99.6% CONDNS DB   -7.90 0.00234


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.37 0.37 0.06 0.06
SAC_FRONTLOUNGE 0.91 0.91 0.24 0.24
SAC_MEETINGROOM 0.43 0.43 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.84 0.84 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialDryBulb 0.24 0.91 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 1623.00 6657.50 762.75
RESTROOMFLR1 163.75 7251.00 11.75
MEETINGROOMFLR1 875.50 3120.25 77.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 488.25 8760.00 488.25
GUESTROOM104 15.00 8753.50 15.00
GUESTROOM105 0.00 8386.00 0.00
EMPLOYEELOUNGEFLR1 2797.75 2241.25 187.75
EXERCISECENTERFLR1 1496.50 2434.00 4.25
FRONTOFFICEFLR1 922.75 5919.75 48.50
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 120.50 8544.25 120.50
GUESTROOM206_208 62.25 8550.25 62.25
GUESTROOM209_212 47.50 8721.50 47.50
GUESTROOM213 614.75 8757.50 614.75
GUESTROOM214 6.75 8499.25 6.75
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 4662.25 3831.25 711.75
GUESTROOM220_223 0.00 8312.75 0.00
GUESTROOM224 9.00 8409.50 9.00
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 153.25 8724.00 153.25
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 59.50 8508.75 59.50
GUESTROOM315_318 6.25 8171.75 0.00
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 4.25 8411.00 4.25
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 2777.00 7869.50 2465.50
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1223.00 7813.50 854.50
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 808.75 7185.50 183.00
GUESTROOM419 533.50 7557.75 142.75
GUESTROOM420_423 824.25 7254.75 221.50
GUESTROOM424 976.75 7753.00 605.50
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7304.50 8760.00 5642.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 1.50 802.75 1.50 802.75
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 1.00 27.25 1.00 27.25
GUESTROOM104 0.00 31.25 0.00 31.25
GUESTROOM105 0.00 38.50 0.00 38.50
EMPLOYEELOUNGEFLR1 210.25 1200.00 171.00 541.75
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 1.25 0.00 0.00 0.00
GUESTROOM202_205 0.00 9.25 0.00 9.25
GUESTROOM206_208 0.00 20.25 0.00 20.25
GUESTROOM209_212 0.00 5.00 0.00 5.00
GUESTROOM213 2.25 11.00 2.25 11.00
GUESTROOM214 0.00 22.00 0.00 22.00
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 3272.25 0.00 3272.25
GUESTROOM220_223 0.00 12.75 0.00 12.75
GUESTROOM224 0.00 23.00 0.00 23.00
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.50 0.00 0.00 0.00
GUESTROOM306_308 0.25 0.00 0.00 0.00
GUESTROOM309_312 0.00 5.50 0.00 5.50
GUESTROOM313 0.25 0.00 0.00 0.00
GUESTROOM314 0.75 21.00 0.75 21.00
GUESTROOM315_318 0.00 19.50 0.00 19.50
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 12.00 0.00 12.00
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 4.00 29.00 4.00 29.00
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 2.00 21.50 2.00 21.50
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 29.25 0.00 29.25
GUESTROOM419 0.50 33.50 0.50 33.50
GUESTROOM420_423 0.25 29.00 0.25 29.00
GUESTROOM424 1.00 32.75 1.00 32.75
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 0.00 3786.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 130.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 512.75 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 219.00 5518.75 177.75 4035.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:36

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.369444
SAC_FRONTLOUNGE SUPPLY FAN 0.907555
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.837189


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 264.34
CORRIDORFLR1 PTAC HEATING COIL 18122.04
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 787.90
102 PTAC HEATING COIL 787.90
103 PTAC HEATING COIL 880.55
104 PTAC HEATING COIL 866.09
105 PTAC HEATING COIL 787.84
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 264.28
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 264.34
CORRIDORFLR2 PTAC HEATING COIL 2234.52
201 PTAC HEATING COIL 861.46
202_205 PTAC HEATING COIL 3151.59
206_208 PTAC HEATING COIL 2497.75
209_212 PTAC HEATING COIL 3151.59
213 PTAC HEATING COIL 915.88
214 PTAC HEATING COIL 874.81
215_218 PTAC HEATING COIL 3151.37
219 PTAC HEATING COIL 787.84
220_223 PTAC HEATING COIL 3151.37
224 PTAC HEATING COIL 805.81
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 264.28
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 264.34
CORRIDORFLR3 PTAC HEATING COIL 2234.52
301 PTAC HEATING COIL 906.73
302_305 PTAC HEATING COIL 3151.59
306_308 PTAC HEATING COIL 2497.75
309_312 PTAC HEATING COIL 3151.59
313 PTAC HEATING COIL 998.10
314 PTAC HEATING COIL 949.01
315_318 PTAC HEATING COIL 3151.37
319 PTAC HEATING COIL 787.84
320_323 PTAC HEATING COIL 3151.37
324 PTAC HEATING COIL 890.22
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 264.28
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 264.34
CORRIDORFLR4 PTAC HEATING COIL 3006.94
401 PTAC HEATING COIL 1154.93
402_405 PTAC HEATING COIL 3581.68
406_408 PTAC HEATING COIL 2939.25
409_412 PTAC HEATING COIL 3590.71
413 PTAC HEATING COIL 1287.38
414 PTAC HEATING COIL 1236.89
415_418 PTAC HEATING COIL 3560.71
419 PTAC HEATING COIL 976.03
420_423 PTAC HEATING COIL 3519.41
424 PTAC HEATING COIL 1182.53
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 264.28


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.798655 0.369444 6115.61
SAC_FRONTLOUNGE COOLING COIL 0.766723 0.907555 16452.20
SAC_MEETINGROOM COOLING COIL 0.733445 0.430144 8655.63
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.798655 0.837189 13858.45


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.907555
RESTROOMFLR1 DIRECT AIR 0.053497
MEETINGROOMFLR1 DIRECT AIR 0.430144
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.644587
EXERCISECENTERFLR1 DIRECT AIR 0.139105
FRONTOFFICEFLR1 DIRECT AIR 0.369444


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.369444
SAC_FRONTLOUNGE MAIN BRANCH 0.907555
SAC_MEETINGROOM MAIN BRANCH 0.430144
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.837189


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.369444
SAC_FRONTLOUNGE 0.907555
SAC_MEETINGROOM 0.430144
SAC_EXC_EMPLGE_RESTRM 0.837189


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.369444 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.907555 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.430144 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.837189 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.369444 0.369444 0.369444 0.369444 3244.22 6115.61 1.00
SAC_FRONTLOUNGE 0.907555 0.907555 0.907555 0.907555 13598.06 16452.20 1.00
SAC_MEETINGROOM 0.430144 0.430144 0.430144 0.430144 7281.66 8655.63 1.00
SAC_EXC_EMPLGE_RESTRM 0.837189 0.837189 0.837189 0.837189 5515.84 13858.45 0.166157


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 3244.22
SAC_FRONTLOUNGE HEATING COIL 13598.06
SAC_MEETINGROOM HEATING COIL 7281.66
SAC_EXC_EMPLGE_RESTRM HEATING COIL 5515.84


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.430144


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.28 2.60
February 19.47 4.29
March 20.30 8.77
April 21.76 13.91
May 22.63 17.82
June 24.08 23.21
July 24.78 25.63
August 24.50 24.08
September 23.72 20.49
October 22.18 13.71
November 20.48 6.96
December 19.40 2.07
     
Annual Sum or Average 21.89 13.68
Minimum of Months 19.28 2.07
Maximum of Months 24.78 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.17 2.60
February 23.33 4.29
March 23.76 8.77
April 24.43 13.91
May 25.03 17.82
June 26.02 23.21
July 26.51 25.63
August 26.27 24.08
September 25.65 20.49
October 24.56 13.71
November 23.60 6.96
December 23.18 2.07
     
Annual Sum or Average 24.63 13.68
Minimum of Months 23.17 2.07
Maximum of Months 26.51 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.33 2.60
February 18.55 4.29
March 19.58 8.77
April 21.15 13.91
May 22.17 17.82
June 23.64 23.21
July 24.25 25.63
August 23.90 24.08
September 23.01 20.49
October 21.32 13.71
November 19.48 6.96
December 18.35 2.07
     
Annual Sum or Average 21.16 13.68
Minimum of Months 18.33 2.07
Maximum of Months 24.25 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.18 2.60
February 21.32 4.29
March 21.76 8.77
April 22.55 13.91
May 23.08 17.82
June 23.55 23.21
July 23.83 25.63
August 23.78 24.08
September 23.47 20.49
October 22.53 13.71
November 21.44 6.96
December 21.14 2.07
     
Annual Sum or Average 22.48 13.68
Minimum of Months 21.14 2.07
Maximum of Months 23.83 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.88 2.60
February 22.00 4.29
March 22.42 8.77
April 22.96 13.91
May 23.32 17.82
June 23.65 23.21
July 23.75 25.63
August 23.67 24.08
September 23.44 20.49
October 22.91 13.71
November 22.28 6.96
December 21.86 2.07
     
Annual Sum or Average 22.85 13.68
Minimum of Months 21.86 2.07
Maximum of Months 23.75 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.77 2.60
February 21.99 4.29
March 22.69 8.77
April 23.28 13.91
May 23.60 17.82
June 23.80 23.21
July 23.87 25.63
August 23.87 24.08
September 23.77 20.49
October 23.27 13.71
November 22.39 6.96
December 21.62 2.07
     
Annual Sum or Average 23.00 13.68
Minimum of Months 21.62 2.07
Maximum of Months 23.87 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.35 2.60
February 24.51 4.29
March 25.04 8.77
April 25.67 13.91
May 26.13 17.82
June 26.67 23.21
July 27.65 25.63
August 27.99 24.08
September 26.96 20.49
October 25.82 13.71
November 24.98 6.96
December 24.32 2.07
     
Annual Sum or Average 25.85 13.68
Minimum of Months 24.32 2.07
Maximum of Months 27.99 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.94 2.60
February 20.25 4.29
March 21.19 8.77
April 22.23 13.91
May 22.82 17.82
June 23.21 23.21
July 23.33 25.63
August 23.32 24.08
September 23.18 20.49
October 22.23 13.71
November 20.89 6.96
December 19.84 2.07
     
Annual Sum or Average 21.88 13.68
Minimum of Months 19.84 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.63 2.60
February 19.93 4.29
March 20.84 8.77
April 21.94 13.91
May 22.60 17.82
June 23.10 23.21
July 23.30 25.63
August 23.26 24.08
September 23.01 20.49
October 21.93 13.71
November 20.53 6.96
December 19.52 2.07
     
Annual Sum or Average 21.64 13.68
Minimum of Months 19.52 2.07
Maximum of Months 23.30 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.97 2.60
February 21.05 4.29
March 21.31 8.77
April 21.55 13.91
May 21.69 17.82
June 21.75 23.21
July 21.75 25.63
August 21.75 24.08
September 21.75 20.49
October 21.54 13.71
November 21.22 6.96
December 20.89 2.07
     
Annual Sum or Average 21.44 13.68
Minimum of Months 20.89 2.07
Maximum of Months 21.75 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.44 2.60
February 21.48 4.29
March 21.58 8.77
April 21.67 13.91
May 21.72 17.82
June 21.75 23.21
July 21.75 25.63
August 21.75 24.08
September 21.75 20.49
October 21.69 13.71
November 21.63 6.96
December 21.46 2.07
     
Annual Sum or Average 21.64 13.68
Minimum of Months 21.44 2.07
Maximum of Months 21.75 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.65 2.60
February 21.68 4.29
March 21.72 8.77
April 21.74 13.91
May 21.75 17.82
June 21.75 23.21
July 21.76 25.63
August 21.75 24.08
September 21.75 20.49
October 21.74 13.71
November 21.73 6.96
December 21.67 2.07
     
Annual Sum or Average 21.72 13.68
Minimum of Months 21.65 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.13 2.60
February 22.17 4.29
March 22.38 8.77
April 22.60 13.91
May 22.66 17.82
June 22.45 23.21
July 22.27 25.63
August 22.28 24.08
September 22.38 20.49
October 22.42 13.71
November 22.29 6.96
December 22.14 2.07
     
Annual Sum or Average 22.35 13.68
Minimum of Months 22.13 2.07
Maximum of Months 22.66 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 51.72 2.60
February 51.80 4.29
March 51.95 8.77
April 52.30 13.91
May 52.50 17.82
June 52.95 23.21
July 53.27 25.63
August 53.28 24.08
September 53.15 20.49
October 52.74 13.71
November 52.19 6.96
December 51.82 2.07
     
Annual Sum or Average 52.48 13.68
Minimum of Months 51.72 2.07
Maximum of Months 53.28 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 68.90 2.60
February 68.95 4.29
March 69.20 8.77
April 69.70 13.91
May 70.04 17.82
June 70.69 23.21
July 71.08 25.63
August 71.01 24.08
September 70.76 20.49
October 70.12 13.71
November 69.39 6.96
December 69.00 2.07
     
Annual Sum or Average 69.91 13.68
Minimum of Months 68.90 2.07
Maximum of Months 71.08 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.05 2.60
February 23.13 4.29
March 23.36 8.77
April 23.69 13.91
May 23.82 17.82
June 23.88 23.21
July 23.89 25.63
August 23.89 24.08
September 23.89 20.49
October 23.70 13.71
November 23.37 6.96
December 23.09 2.07
     
Annual Sum or Average 23.57 13.68
Minimum of Months 23.05 2.07
Maximum of Months 23.89 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.55 2.60
February 22.74 4.29
March 23.16 8.77
April 23.63 13.91
May 23.81 17.82
June 23.88 23.21
July 23.89 25.63
August 23.89 24.08
September 23.89 20.49
October 23.65 13.71
November 23.18 6.96
December 22.62 2.07
     
Annual Sum or Average 23.41 13.68
Minimum of Months 22.55 2.07
Maximum of Months 23.89 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.87 2.60
February 19.08 4.29
March 20.17 8.77
April 21.94 13.91
May 22.96 17.82
June 24.65 23.21
July 25.53 25.63
August 25.16 24.08
September 24.22 20.49
October 22.39 13.71
November 20.31 6.96
December 18.99 2.07
     
Annual Sum or Average 22.04 13.68
Minimum of Months 18.87 2.07
Maximum of Months 25.53 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.09 2.60
February 21.25 4.29
March 21.91 8.77
April 22.89 13.91
May 23.44 17.82
June 24.35 23.21
July 24.86 25.63
August 24.71 24.08
September 24.24 20.49
October 23.26 13.71
November 22.05 6.96
December 21.18 2.07
     
Annual Sum or Average 22.94 13.68
Minimum of Months 21.09 2.07
Maximum of Months 24.86 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.16 2.60
February 19.36 4.29
March 20.43 8.77
April 22.17 13.91
May 23.20 17.82
June 24.88 23.21
July 25.65 25.63
August 25.29 24.08
September 24.39 20.49
October 22.58 13.71
November 20.56 6.96
December 19.26 2.07
     
Annual Sum or Average 22.26 13.68
Minimum of Months 19.16 2.07
Maximum of Months 25.65 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.54 2.60
February 22.76 4.29
March 23.40 8.77
April 23.78 13.91
May 23.86 17.82
June 23.92 23.21
July 23.93 25.63
August 23.91 24.08
September 23.89 20.49
October 23.72 13.71
November 23.29 6.96
December 22.49 2.07
     
Annual Sum or Average 23.46 13.68
Minimum of Months 22.49 2.07
Maximum of Months 23.93 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.42 2.60
February 17.71 4.29
March 19.10 8.77
April 21.15 13.91
May 22.44 17.82
June 24.26 23.21
July 24.98 25.63
August 24.52 24.08
September 23.42 20.49
October 21.26 13.71
November 18.86 6.96
December 17.39 2.07
     
Annual Sum or Average 21.06 13.68
Minimum of Months 17.39 2.07
Maximum of Months 24.98 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.20 2.60
February 19.49 4.29
March 20.51 8.77
April 22.12 13.91
May 22.85 17.82
June 23.24 23.21
July 23.33 25.63
August 23.33 24.08
September 23.22 20.49
October 21.92 13.71
November 19.94 6.96
December 19.07 2.07
     
Annual Sum or Average 21.53 13.68
Minimum of Months 19.07 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 2.60
February 21.20 4.29
March 21.50 8.77
April 21.68 13.91
May 21.74 17.82
June 21.75 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.64 13.71
November 21.35 6.96
December 21.01 2.07
     
Annual Sum or Average 21.52 13.68
Minimum of Months 21.01 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.17 2.60
February 21.26 4.29
March 21.54 8.77
April 21.69 13.91
May 21.74 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.66 13.71
November 21.40 6.96
December 21.07 2.07
     
Annual Sum or Average 21.55 13.68
Minimum of Months 21.07 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.22 2.60
February 21.30 4.29
March 21.58 8.77
April 21.70 13.91
May 21.74 17.82
June 21.75 23.21
July 21.76 25.63
August 21.75 24.08
September 21.75 20.49
October 21.67 13.71
November 21.46 6.96
December 21.11 2.07
     
Annual Sum or Average 21.57 13.68
Minimum of Months 21.11 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 2.60
February 21.01 4.29
March 21.32 8.77
April 21.60 13.91
May 21.71 17.82
June 21.75 23.21
July 21.76 25.63
August 21.75 24.08
September 21.75 20.49
October 21.56 13.71
November 21.19 6.96
December 20.83 2.07
     
Annual Sum or Average 21.43 13.68
Minimum of Months 20.83 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.51 2.60
February 21.56 4.29
March 21.66 8.77
April 21.72 13.91
May 21.74 17.82
June 21.75 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.72 13.71
November 21.69 6.96
December 21.55 2.07
     
Annual Sum or Average 21.68 13.68
Minimum of Months 21.51 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.20 2.60
February 23.24 4.29
March 23.32 8.77
April 23.33 13.91
May 23.33 17.82
June 23.33 23.21
July 23.33 25.63
August 23.33 24.08
September 23.33 20.49
October 23.32 13.71
November 23.32 6.96
December 23.22 2.07
     
Annual Sum or Average 23.30 13.68
Minimum of Months 23.20 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 31.52 2.60
February 31.64 4.29
March 32.06 8.77
April 32.64 13.91
May 32.94 17.82
June 33.46 23.21
July 33.77 25.63
August 33.70 24.08
September 33.49 20.49
October 32.89 13.71
November 32.13 6.96
December 31.55 2.07
     
Annual Sum or Average 32.65 13.68
Minimum of Months 31.52 2.07
Maximum of Months 33.77 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.01 2.60
February 22.08 4.29
March 22.19 8.77
April 22.35 13.91
May 22.55 17.82
June 22.99 23.21
July 23.33 25.63
August 23.25 24.08
September 23.00 20.49
October 22.57 13.71
November 22.18 6.96
December 21.99 2.07
     
Annual Sum or Average 22.54 13.68
Minimum of Months 21.99 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.60 2.60
February 21.65 4.29
March 21.71 8.77
April 21.74 13.91
May 21.75 17.82
June 21.75 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.73 13.71
November 21.73 6.96
December 21.63 2.07
     
Annual Sum or Average 21.71 13.68
Minimum of Months 21.60 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.51 2.60
February 21.56 4.29
March 21.66 8.77
April 21.73 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.76 20.49
October 21.72 13.71
November 21.70 6.96
December 21.54 2.07
     
Annual Sum or Average 21.68 13.68
Minimum of Months 21.51 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.50 2.60
February 20.69 4.29
March 21.60 8.77
April 22.90 13.91
May 23.64 17.82
June 24.78 23.21
July 25.40 25.63
August 25.17 24.08
September 24.55 20.49
October 23.25 13.71
November 21.69 6.96
December 20.55 2.07
     
Annual Sum or Average 22.90 13.68
Minimum of Months 20.50 2.07
Maximum of Months 25.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.26 2.60
February 18.52 4.29
March 20.05 8.77
April 22.33 13.91
May 23.64 17.82
June 25.72 23.21
July 26.76 25.63
August 26.24 24.08
September 25.02 20.49
October 22.70 13.71
November 20.05 6.96
December 18.33 2.07
     
Annual Sum or Average 22.32 13.68
Minimum of Months 18.26 2.07
Maximum of Months 26.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.42 2.60
February 18.69 4.29
March 19.95 8.77
April 21.99 13.91
May 23.21 17.82
June 25.09 23.21
July 25.93 25.63
August 25.53 24.08
September 24.49 20.49
October 22.36 13.71
November 20.00 6.96
December 18.50 2.07
     
Annual Sum or Average 22.03 13.68
Minimum of Months 18.42 2.07
Maximum of Months 25.93 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.43 2.60
February 21.65 4.29
March 22.34 8.77
April 23.31 13.91
May 23.67 17.82
June 23.86 23.21
July 23.89 25.63
August 23.89 24.08
September 23.87 20.49
October 23.22 13.71
November 22.06 6.96
December 21.35 2.07
     
Annual Sum or Average 22.88 13.68
Minimum of Months 21.35 2.07
Maximum of Months 23.89 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.24 2.60
February 16.63 4.29
March 18.29 8.77
April 20.83 13.91
May 22.44 17.82
June 24.56 23.21
July 25.40 25.63
August 24.88 24.08
September 23.59 20.49
October 20.87 13.71
November 17.87 6.96
December 16.18 2.07
     
Annual Sum or Average 20.67 13.68
Minimum of Months 16.18 2.07
Maximum of Months 25.40 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.97 2.60
February 19.18 4.29
March 19.92 8.77
April 21.75 13.91
May 22.67 17.82
June 23.19 23.21
July 23.33 25.63
August 23.32 24.08
September 23.14 20.49
October 21.52 13.71
November 19.38 6.96
December 18.91 2.07
     
Annual Sum or Average 21.28 13.68
Minimum of Months 18.91 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.02 2.60
February 19.27 4.29
March 20.13 8.77
April 21.85 13.91
May 22.76 17.82
June 23.23 23.21
July 23.33 25.63
August 23.33 24.08
September 23.20 20.49
October 21.63 13.71
November 19.54 6.96
December 18.94 2.07
     
Annual Sum or Average 21.36 13.68
Minimum of Months 18.94 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.07 2.60
February 19.34 4.29
March 20.28 8.77
April 21.91 13.91
May 22.76 17.82
June 23.22 23.21
July 23.33 25.63
August 23.32 24.08
September 23.18 20.49
October 21.67 13.71
November 19.66 6.96
December 18.97 2.07
     
Annual Sum or Average 21.40 13.68
Minimum of Months 18.97 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 2.60
February 21.21 4.29
March 21.50 8.77
April 21.67 13.91
May 21.73 17.82
June 21.75 23.21
July 21.76 25.63
August 21.75 24.08
September 21.75 20.49
October 21.62 13.71
November 21.35 6.96
December 20.99 2.07
     
Annual Sum or Average 21.52 13.68
Minimum of Months 20.99 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.00 2.60
February 19.25 4.29
March 20.07 8.77
April 21.76 13.91
May 22.67 17.82
June 23.21 23.21
July 23.33 25.63
August 23.32 24.08
September 23.17 20.49
October 21.61 13.71
November 19.58 6.96
December 18.94 2.07
     
Annual Sum or Average 21.34 13.68
Minimum of Months 18.94 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.36 2.60
February 21.41 4.29
March 21.55 8.77
April 21.68 13.91
May 21.72 17.82
June 21.75 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.68 13.71
November 21.60 6.96
December 21.37 2.07
     
Annual Sum or Average 21.62 13.68
Minimum of Months 21.36 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.62 2.60
February 21.67 4.29
March 21.72 8.77
April 21.74 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.73 13.71
November 21.73 6.96
December 21.65 2.07
     
Annual Sum or Average 21.72 13.68
Minimum of Months 21.62 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.45 2.60
February 23.66 4.29
March 24.27 8.77
April 25.16 13.91
May 25.59 17.82
June 26.16 23.21
July 26.45 25.63
August 26.37 24.08
September 26.11 20.49
October 25.30 13.71
November 24.24 6.96
December 23.48 2.07
     
Annual Sum or Average 25.03 13.68
Minimum of Months 23.45 2.07
Maximum of Months 26.45 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.03 2.60
February 22.30 4.29
March 22.81 8.77
April 23.18 13.91
May 23.29 17.82
June 23.33 23.21
July 23.33 25.63
August 23.33 24.08
September 23.33 20.49
October 23.14 13.71
November 22.81 6.96
December 22.11 2.07
     
Annual Sum or Average 22.92 13.68
Minimum of Months 22.03 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.53 2.60
February 21.59 4.29
March 21.67 8.77
April 21.72 13.91
May 21.74 17.82
June 21.75 23.21
July 21.76 25.63
August 21.75 24.08
September 21.75 20.49
October 21.71 13.71
November 21.70 6.96
December 21.56 2.07
     
Annual Sum or Average 21.69 13.68
Minimum of Months 21.53 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.39 2.60
February 20.66 4.29
March 21.48 8.77
April 22.48 13.91
May 22.91 17.82
June 23.24 23.21
July 23.33 25.63
August 23.33 24.08
September 23.26 20.49
October 22.54 13.71
November 21.48 6.96
December 20.34 2.07
     
Annual Sum or Average 22.13 13.68
Minimum of Months 20.34 2.07
Maximum of Months 23.33 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.55 2.60
February 19.83 4.29
March 21.02 8.77
April 22.72 13.91
May 23.67 17.82
June 25.06 23.21
July 25.78 25.63
August 25.48 24.08
September 24.71 20.49
October 23.01 13.71
November 21.00 6.96
December 19.56 2.07
     
Annual Sum or Average 22.63 13.68
Minimum of Months 19.55 2.07
Maximum of Months 25.78 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.38 2.60
February 17.72 4.29
March 19.51 8.77
April 22.17 13.91
May 23.71 17.82
June 26.04 23.21
July 27.20 25.63
August 26.60 24.08
September 25.20 20.49
October 22.48 13.71
November 19.39 6.96
December 17.41 2.07
     
Annual Sum or Average 22.09 13.68
Minimum of Months 17.38 2.07
Maximum of Months 27.20 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 17.16 2.60
February 17.64 4.29
March 19.18 8.77
April 21.72 13.91
May 23.24 17.82
June 25.48 23.21
July 26.48 25.63
August 25.99 24.08
September 24.65 20.49
October 21.94 13.71
November 19.00 6.96
December 17.18 2.07
     
Annual Sum or Average 21.66 13.68
Minimum of Months 17.16 2.07
Maximum of Months 26.48 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.40 2.60
February 21.58 4.29
March 21.99 8.77
April 22.80 13.91
May 23.28 17.82
June 23.81 23.21
July 24.08 25.63
August 23.98 24.08
September 23.63 20.49
October 22.72 13.71
November 21.71 6.96
December 21.30 2.07
     
Annual Sum or Average 22.70 13.68
Minimum of Months 21.30 2.07
Maximum of Months 24.08 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.34 2.60
February 15.90 4.29
March 17.74 8.77
April 20.63 13.91
May 22.47 17.82
June 24.89 23.21
July 25.86 25.63
August 25.27 24.08
September 23.69 20.49
October 20.50 13.71
November 17.09 6.96
December 15.23 2.07
     
Annual Sum or Average 20.41 13.68
Minimum of Months 15.23 2.07
Maximum of Months 25.86 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.80 2.60
February 20.97 4.29
March 21.34 8.77
April 21.64 13.91
May 21.73 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.53 13.71
November 21.13 6.96
December 20.66 2.07
     
Annual Sum or Average 21.40 13.68
Minimum of Months 20.66 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.06 2.60
February 19.30 4.29
March 20.01 8.77
April 21.46 13.91
May 22.38 17.82
June 23.03 23.21
July 23.31 25.63
August 23.27 24.08
September 22.89 20.49
October 21.22 13.71
November 19.37 6.96
December 18.94 2.07
     
Annual Sum or Average 21.20 13.68
Minimum of Months 18.94 2.07
Maximum of Months 23.31 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.09 2.60
February 19.34 4.29
March 20.07 8.77
April 21.47 13.91
May 22.37 17.82
June 23.02 23.21
July 23.31 25.63
August 23.26 24.08
September 22.86 20.49
October 21.23 13.71
November 19.42 6.96
December 18.95 2.07
     
Annual Sum or Average 21.21 13.68
Minimum of Months 18.95 2.07
Maximum of Months 23.31 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.12 2.60
February 21.27 4.29
March 21.56 8.77
April 21.70 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.63 13.71
November 21.43 6.96
December 20.97 2.07
     
Annual Sum or Average 21.54 13.68
Minimum of Months 20.97 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.03 2.60
February 19.28 4.29
March 19.96 8.77
April 21.46 13.91
May 22.36 17.82
June 23.04 23.21
July 23.31 25.63
August 23.26 24.08
September 22.91 20.49
October 21.28 13.71
November 19.40 6.96
December 18.93 2.07
     
Annual Sum or Average 21.20 13.68
Minimum of Months 18.93 2.07
Maximum of Months 23.31 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.88 2.60
February 20.16 4.29
March 20.73 8.77
April 21.87 13.91
May 22.51 17.82
June 23.06 23.21
July 23.32 25.63
August 23.28 24.08
September 23.01 20.49
October 21.91 13.71
November 20.59 6.96
December 19.82 2.07
     
Annual Sum or Average 21.69 13.68
Minimum of Months 19.82 2.07
Maximum of Months 23.32 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.55 2.60
February 21.62 4.29
March 21.68 8.77
April 21.73 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.71 13.71
November 21.70 6.96
December 21.58 2.07
     
Annual Sum or Average 21.70 13.68
Minimum of Months 21.55 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.06 2.60
February 21.40 4.29
March 22.13 8.77
April 23.29 13.91
May 23.93 17.82
June 24.78 23.21
July 25.21 25.63
August 25.05 24.08
September 24.49 20.49
October 23.28 13.71
November 21.92 6.96
December 21.04 2.07
     
Annual Sum or Average 23.14 13.68
Minimum of Months 21.04 2.07
Maximum of Months 25.21 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.51 2.60
February 21.59 4.29
March 21.67 8.77
April 21.73 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.71 13.71
November 21.69 6.96
December 21.55 2.07
     
Annual Sum or Average 21.69 13.68
Minimum of Months 21.51 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.53 2.60
February 21.60 4.29
March 21.68 8.77
April 21.73 13.91
May 21.75 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.70 13.71
November 21.70 6.96
December 21.56 2.07
     
Annual Sum or Average 21.69 13.68
Minimum of Months 21.53 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.36 2.60
February 21.46 4.29
March 21.59 8.77
April 21.71 13.91
May 21.74 17.82
June 21.76 23.21
July 21.76 25.63
August 21.76 24.08
September 21.75 20.49
October 21.68 13.71
November 21.63 6.96
December 21.40 2.07
     
Annual Sum or Average 21.63 13.68
Minimum of Months 21.36 2.07
Maximum of Months 21.76 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.87 2.60
February 19.32 4.29
March 20.63 8.77
April 22.56 13.91
May 23.65 17.82
June 25.25 23.21
July 26.05 25.63
August 25.69 24.08
September 24.65 20.49
October 22.63 13.71
November 20.39 6.96
December 18.85 2.07
     
Annual Sum or Average 22.39 13.68
Minimum of Months 18.85 2.07
Maximum of Months 26.05 25.63



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:36

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.47 2.60
February 17.00 4.29
March 19.00 8.77
April 21.98 13.91
May 23.71 17.82
June 26.34 23.21
July 27.59 25.63
August 26.92 24.08
September 25.23 20.49
October 22.09 13.71
November 18.64 6.96
December 16.46 2.07
     
Annual Sum or Average 21.81 13.68
Minimum of Months 16.46 2.07
Maximum of Months 27.59 25.63



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:36

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.144004E+12 100284.503 17-JAN-07:15 15177.258 39465.561 9045.947 31982.191 417.432 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.127007E+12 98869.664 05-FEB-07:15 15177.258 39465.561 9045.947 34670.679 502.106 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.133603E+12 87003.667 05-MAR-07:15 15177.258 39465.561 9045.947 22077.773 1229.014 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.131846E+12 82392.636 28-APR-07:00 17641.054 43276.576 9527.755 0.000 11939.139 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.142609E+12 86353.697 19-MAY-07:00 17566.637 43276.576 9527.755 0.000 15974.617 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.151671E+12 92292.101 24-JUN-07:00 17492.219 43276.576 9527.755 0.000 21987.439 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.167332E+12 95495.036 21-JUL-07:00 17789.888 43276.576 9527.755 0.000 24892.704 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.163244E+12 92441.027 12-AUG-07:00 17566.637 43276.576 9527.755 0.000 22061.947 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.148125E+12 89890.971 03-SEP-07:00 17641.054 43276.576 9527.755 0.000 19437.474 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.140849E+12 90540.945 26-OCT-06:15 15177.258 39465.561 9045.947 21559.992 1096.074 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.131059E+12 90825.300 27-NOV-07:15 15177.258 39465.561 9045.947 26199.035 929.385 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.144344E+12 100464.571 22-DEC-07:15 13316.689 34010.661 9045.947 39674.974 220.187 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.172569E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.127007E+12 82392.636   13316.689 34010.661 9045.947 0.000 220.187 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.167332E+12 100464.571   17789.888 43276.576 9527.755 39674.974 24892.704 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:36

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.100398E+12 102477.739 19-JAN-10:15 5990.399 40096.028 0.000 56391.312 56391.312 56391.312 5990.399
February 0.897515E+11 102965.798 05-FEB-10:15 6292.549 40096.028 0.000 56577.222 56577.222 56577.222 6292.549
March 0.942180E+11 98339.300 04-MAR-09:15 76.310 40096.028 0.000 58166.962 58166.962 58166.962 76.310
April 0.864855E+11 95736.396 01-APR-08:15 0.000 40096.028 0.000 55640.368 55640.368 55640.368 0.000
May 0.851804E+11 92015.663 06-MAY-08:15 0.000 40096.028 0.000 51919.635 51919.635 51919.635 0.000
June 0.790614E+11 90196.731 02-JUN-08:45 0.000 40096.028 0.000 50100.703 50100.703 50100.703 0.000
July 0.800546E+11 74480.398 01-JUL-09:15 0.000 40096.028 0.000 34384.370 34384.370 34384.370 0.000
August 0.797984E+11 74222.025 31-AUG-08:15 0.000 40096.028 0.000 34125.997 34125.997 34125.997 0.000
September 0.779971E+11 87527.330 29-SEP-09:30 0.000 40096.028 0.000 47431.302 47431.302 47431.302 0.000
October 0.842465E+11 91009.986 27-OCT-08:15 0.000 40096.028 0.000 50913.958 50913.958 50913.958 0.000
November 0.873167E+11 94578.684 25-NOV-10:15 1455.621 40096.028 0.000 53027.035 53027.035 53027.035 1455.621
December 0.984627E+11 102201.028 22-DEC-10:15 6782.798 40096.028 0.000 55322.202 55322.202 55322.202 6782.798
                     
Annual Sum or Average 0.104297E+13         0.000        
Minimum of Months 0.779971E+11 74222.025   0.000 40096.028 0.000 34125.997 34125.997 34125.997 0.000
Maximum of Months 0.100398E+12 102965.798   6782.798 40096.028 0.000 58166.962 58166.962 58166.962 6782.798