Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Great Falls Intl Arpt MT USA TMY3 WMO#=727750

Simulation Timestamp: 2018-10-19 10:15:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 3048.78 759.61 818.44
Net Site Energy 3048.78 759.61 818.44
Total Source Energy 7126.52 1775.60 1913.11
Net Source Energy 7126.52 1775.60 1913.11


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 304.72 112.03 0.00 0.00 0.00 0.00
Cooling 171.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting 414.73 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.72 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 287.06 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 680.57 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1834.68 1214.09 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 304.72 112.03 0.00 0.00 0.00 0.00
Cooling General 171.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 414.73 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.72 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 287.06 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 680.57 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 128.98 0.00 0.00 0.00 0.00 0.00
HVAC 204.89 212.77 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 492.52 325.92 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 119.71 0.00 0.00 0.00 0.00 0.00
HVAC 190.16 197.48 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 457.12 302.50 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1834.68 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1834.68 100.00
     
Total On-Site and Utility Electric Sources 1834.68 100.00
Total Electricity End Uses 1834.68 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 784.25
Time Setpoint Not Met During Occupied Cooling 2822.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 6110.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Weather File Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Latitude [deg] 47.47
Longitude [deg] -111.4
Elevation [m] 1117.00
Time Zone -7.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB -27.60 0.00 -27.60 Wetbulb [C] 2.70 230.00
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 33.40 16.00 16.30 Wetbulb [C] 4.90 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.363 0.384 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.23 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.23 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.23 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.23 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.23 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 4.44 0.00 0.00 4.44 4.44 2.653 0.426 0.308     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.69 0.00 0.00 2.69 2.69 2.653 0.426 0.308     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.52_SHGC_0.40 2.97 0.00 0.00 2.97 2.97 2.653 0.426 0.308     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.31 0.00 0.00 1.31 1.31 2.653 0.426 0.308     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 3.41 0.00 0.00 3.41 3.41 2.653 0.426 0.308     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.52_SHGC_0.40 1.65 0.00 0.00 1.65 1.65 2.653 0.426 0.308     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 2.653 0.426 0.308              
North Total or Average           96.82 2.653 0.426 0.308              
Non-North Total or Average           87.38 2.653 0.426 0.308              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 2.839 2.839 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   6087.61 4861.52 1226.09 0.80 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   15439.69 11736.69 3703.00 0.76 3.91    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   8068.98 5870.41 2198.57 0.73 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   13293.83 10554.66 2739.17 0.79 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 5802.3 3.15 10.76 11.39 10.54
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 14791.5 3.22 10.99 11.64 10.88
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 7763.7 3.28 11.19 11.86 11.18
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 12678.6 3.16 10.78 11.42 10.58
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   281.09 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   35297.60 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   1122.86 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   1164.88 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   1516.61 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   1524.13 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   1175.50 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   281.02 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   281.09 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   3227.60 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   1478.02 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   4491.43 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   3559.62 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   4491.43 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   1580.36 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   1550.31 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   4491.11 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   1122.78 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   4491.11 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   1399.30 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   509.51 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   281.09 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   3587.87 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   1544.46 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   4635.25 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   3784.34 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   4635.38 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   1707.08 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   1660.58 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   4644.78 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   1219.20 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   4584.05 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   1499.87 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   509.51 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   509.64 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   5397.41 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   1948.46 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   6062.05 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   4966.18 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   6078.46 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   2180.45 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   2117.67 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   6082.27 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   1673.78 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   6022.33 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   1947.54 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   671.65 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   4623.43 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   19379.02 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   10377.32 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   7952.63 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.90 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.37 411.85 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.84 924.55 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.39 440.36 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.79 877.76 1107.16 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 7382.21 8858.65 0.696 0.835 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 33.16 0.00627
RESTROOMFLR1 416.37 499.65 0.039 0.047 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 32.12 0.00627
MEETINGROOMFLR1 3472.97 4167.57 0.328 0.393 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM101 529.21 635.05 0.069 0.083 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.44 0.00627
GUESTROOM102 430.26 516.31 0.056 0.068 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.44 0.00627
GUESTROOM103 993.72 1192.46 0.130 0.156 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
GUESTROOM104 1194.52 1433.43 0.156 0.188 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM105 1568.97 1882.76 0.205 0.247 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
EMPLOYEELOUNGEFLR1 5414.04 6496.85 0.510 0.613 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
EXERCISECENTERFLR1 1178.10 1413.71 0.111 0.133 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:00:00 31.16 0.00627
FRONTOFFICEFLR1 3253.22 3903.86 0.306 0.368 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
GUESTROOM201 792.14 950.57 0.104 0.124 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 33.40 0.00627
GUESTROOM202_205 4040.89 4849.06 0.529 0.635 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.44 0.00627
GUESTROOM206_208 3275.02 3930.02 0.429 0.515 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.44 0.00627
GUESTROOM209_212 3852.23 4622.68 0.505 0.605 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 32.44 0.00627
GUESTROOM213 1078.89 1294.66 0.141 0.170 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
GUESTROOM214 1339.94 1607.93 0.175 0.211 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM215_218 9747.43 11696.91 1.276 1.532 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
GUESTROOM219 5475.40 6570.48 0.717 0.860 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM220_223 4728.41 5674.10 0.619 0.743 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
GUESTROOM224 1340.74 1608.89 0.176 0.211 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
GUESTROOM301 619.68 743.61 0.081 0.097 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM302_305 1495.13 1794.16 0.196 0.235 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 32.12 0.00627
GUESTROOM306_308 1308.71 1570.45 0.171 0.206 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 32.12 0.00627
GUESTROOM309_312 3830.58 4596.70 0.502 0.602 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 16:15:00 32.12 0.00627
GUESTROOM313 583.93 700.71 0.076 0.092 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:15:00 26.72 0.00627
GUESTROOM314 1259.61 1511.53 0.165 0.198 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:15:00 33.16 0.00627
GUESTROOM315_318 5155.70 6186.83 0.675 0.810 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM319 1152.52 1383.02 0.151 0.181 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM320_323 4535.39 5442.47 0.594 0.713 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM324 769.16 922.99 0.101 0.121 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM401 1478.48 1774.17 0.194 0.232 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 33.40 0.00627
GUESTROOM402_405 2345.77 2814.92 0.307 0.369 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM406_408 2005.27 2406.33 0.263 0.315 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM409_412 4996.17 5995.40 0.654 0.785 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM413 864.88 1037.85 0.113 0.136 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 32.68 0.00627
GUESTROOM414 1089.02 1306.83 0.143 0.171 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 33.40 0.00627
GUESTROOM415_418 5961.44 7153.72 0.781 0.937 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.40 0.00627
GUESTROOM419 1632.64 1959.16 0.214 0.257 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.40 0.00627
GUESTROOM420_423 5920.86 7105.03 0.775 0.930 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 33.40 0.00627
GUESTROOM424 1649.60 1979.52 0.216 0.259 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 33.40 0.00627
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
CORRIDORFLR1 14630.84 17557.00 1.377 1.653 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 29.56 0.00627
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
CORRIDORFLR2 2681.28 3217.53 0.252 0.303 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 30.76 0.00627
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
CORRIDORFLR3 1289.58 1547.50 0.121 0.146 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 30.36 0.00627
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627
CORRIDORFLR4 2270.48 2724.57 0.214 0.257 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 32.68 0.00627
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB   33.40 0.00627


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 2233.40 2680.08 0.072 0.236 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -27.60 0.00034
RESTROOMFLR1 170.47 204.56 0.005 0.007 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -27.60 0.00034
MEETINGROOMFLR1 793.83 952.60 0.026 0.126 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:00:00 -27.60 0.00034
GUESTROOM101 336.38 403.65 0.011 0.013 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -27.60 0.00034
GUESTROOM102 383.37 460.04 0.012 0.015 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:30:00 -27.60 0.00034
GUESTROOM103 676.47 811.77 0.022 0.026 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 07:45:00 -27.60 0.00034
GUESTROOM104 682.79 819.34 0.022 0.026 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -27.60 0.00034
GUESTROOM105 392.26 470.71 0.013 0.015 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -27.60 0.00034
EMPLOYEELOUNGEFLR1 374.56 449.47 0.012 0.051 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -27.60 0.00034
EXERCISECENTERFLR1 269.60 323.52 0.009 0.043 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -27.60 0.00034
FRONTOFFICEFLR1 1439.85 1727.82 0.046 0.056 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:30:00 -27.60 0.00034
GUESTROOM201 644.31 773.18 0.021 0.025 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:45:00 -27.60 0.00034
GUESTROOM202_205 1343.84 1612.61 0.043 0.054 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:30:00 -27.60 0.00034
GUESTROOM206_208 1069.46 1283.35 0.034 0.043 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
GUESTROOM209_212 1251.94 1502.33 0.040 0.054 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:00:00 -27.60 0.00034
GUESTROOM213 729.60 875.52 0.024 0.028 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:00:00 -27.60 0.00034
GUESTROOM214 704.60 845.52 0.023 0.027 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 10:15:00 -27.60 0.00034
GUESTROOM215_218 1289.66 1547.59 0.042 0.054 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -27.60 0.00034
GUESTROOM219 334.93 401.92 0.011 0.013 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -27.60 0.00034
GUESTROOM220_223 1228.68 1474.42 0.040 0.054 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -27.60 0.00034
GUESTROOM224 578.76 694.51 0.019 0.022 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:15:00 -27.60 0.00034
GUESTROOM301 699.68 839.62 0.023 0.027 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -27.60 0.00034
GUESTROOM302_305 1513.24 1815.89 0.049 0.059 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:30:00 -27.60 0.00034
GUESTROOM306_308 1291.58 1549.90 0.042 0.050 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -27.60 0.00034
GUESTROOM309_312 1513.35 1816.02 0.049 0.059 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:15:00 -27.60 0.00034
GUESTROOM313 835.20 1002.24 0.027 0.032 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -27.60 0.00034
GUESTROOM314 796.50 955.79 0.026 0.031 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:45:00 -27.60 0.00034
GUESTROOM315_318 1521.35 1825.62 0.049 0.059 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 12:45:00 -27.60 0.00034
GUESTROOM319 428.68 514.41 0.014 0.017 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -27.60 0.00034
GUESTROOM320_323 1470.74 1764.89 0.047 0.057 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:00:00 -27.60 0.00034
GUESTROOM324 662.56 795.08 0.021 0.026 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:00:00 -27.60 0.00034
GUESTROOM401 1036.35 1243.62 0.033 0.040 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:15:00 -27.60 0.00034
GUESTROOM402_405 2702.24 3242.69 0.087 0.105 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:30:00 -27.60 0.00034
GUESTROOM406_408 2276.45 2731.74 0.073 0.088 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -27.60 0.00034
GUESTROOM409_412 2715.92 3259.10 0.088 0.105 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -27.60 0.00034
GUESTROOM413 1229.68 1475.61 0.040 0.048 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -27.60 0.00034
GUESTROOM414 1177.40 1412.88 0.038 0.046 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:15:00 -27.60 0.00034
GUESTROOM415_418 2719.26 3263.11 0.088 0.105 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 16:45:00 -27.60 0.00034
GUESTROOM419 807.49 968.99 0.026 0.031 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 17:30:00 -27.60 0.00034
GUESTROOM420_423 2669.31 3203.18 0.086 0.103 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 19:00:00 -27.60 0.00034
GUESTROOM424 1035.62 1242.75 0.033 0.040 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 22:30:00 -27.60 0.00034
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB   -27.60 0.00034
CORRIDORFLR1 27394.05 32872.86 0.882 1.058 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:15:00 -27.60 0.00034
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB   -27.60 0.00034
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB   -27.60 0.00034
CORRIDORFLR2 1023.90 1228.69 0.033 0.040 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 09:45:00 -27.60 0.00034
FRONTSTAIRSFLR2 15.52 18.62 0.000 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -27.60 0.00034
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB   -27.60 0.00034
CORRIDORFLR3 1324.12 1588.95 0.043 0.051 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -27.60 0.00034
FRONTSTAIRSFLR3 148.40 178.09 0.003 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -27.60 0.00034
REARSTAIRSFLR4 49.65 59.58 0.001 0.006 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 23:30:00 -27.60 0.00034
CORRIDORFLR4 2832.08 3398.50 0.091 0.110 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -27.60 0.00034
FRONTSTAIRSFLR4 369.34 443.20 0.008 0.010 GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 13:30:00 -27.60 0.00034


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.37 0.37 0.06 0.06
SAC_FRONTLOUNGE 0.84 0.84 0.24 0.24
SAC_MEETINGROOM 0.39 0.39 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.79 0.79 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 1805.75 7649.75 1687.00
RESTROOMFLR1 846.00 8460.25 840.00
MEETINGROOMFLR1 459.75 3762.50 333.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 2411.75 8760.00 2411.75
GUESTROOM104 1173.00 8758.25 1173.00
GUESTROOM105 314.25 8673.25 314.25
EMPLOYEELOUNGEFLR1 2704.75 2437.75 344.75
EXERCISECENTERFLR1 747.50 3644.00 92.50
FRONTOFFICEFLR1 1025.50 7382.25 788.00
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 1448.00 8751.50 1448.00
GUESTROOM206_208 1274.50 8751.25 1274.50
GUESTROOM209_212 1135.75 8760.00 1135.75
GUESTROOM213 2687.50 8760.00 2687.50
GUESTROOM214 1064.25 8704.50 1064.25
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 3201.00 4551.75 275.00
GUESTROOM220_223 497.00 8628.50 496.00
GUESTROOM224 1055.75 8689.00 1055.75
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 1593.75 8760.00 1593.75
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 1867.50 8704.75 1867.50
GUESTROOM315_318 533.50 8497.50 532.25
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 793.00 8666.75 792.00
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 4279.25 8370.75 4260.25
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 2742.25 8295.25 2705.00
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1820.75 7939.00 1566.50
GUESTROOM419 1724.25 8151.00 1641.00
GUESTROOM420_423 1924.50 7986.50 1690.25
GUESTROOM424 2909.00 8260.50 2832.00
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7294.50 8760.00 6110.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.50 0.00 0.50 0.00
RESTROOMFLR1 607.50 297.50 607.50 297.50
MEETINGROOMFLR1 0.50 0.00 0.50 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 1.00 0.00 0.00 0.00
GUESTROOM103 15.00 13.00 15.00 13.00
GUESTROOM104 8.00 18.50 8.00 18.50
GUESTROOM105 2.00 30.25 2.00 30.25
EMPLOYEELOUNGEFLR1 514.00 967.00 384.25 580.00
EXERCISECENTERFLR1 1.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 11.75 1.75 11.75 1.75
GUESTROOM206_208 11.50 6.00 11.50 6.00
GUESTROOM209_212 11.00 1.50 11.00 1.50
GUESTROOM213 15.75 2.00 15.75 2.00
GUESTROOM214 8.00 7.50 8.00 7.50
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 2135.50 0.00 2135.50
GUESTROOM220_223 5.00 5.50 5.00 5.50
GUESTROOM224 7.75 7.50 7.75 7.50
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 14.75 1.50 14.75 1.50
GUESTROOM313 0.50 0.00 0.00 0.00
GUESTROOM314 8.75 7.25 8.75 7.25
GUESTROOM315_318 5.00 6.50 5.00 6.50
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 6.75 5.25 6.75 5.25
GUESTROOM324 0.50 0.00 0.00 0.00
GUESTROOM401 10.75 13.25 10.75 13.25
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 16.75 9.25 16.75 9.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 10.25 15.50 10.25 15.50
GUESTROOM419 8.50 21.75 8.50 21.75
GUESTROOM420_423 11.00 14.75 11.00 14.75
GUESTROOM424 6.75 19.25 6.75 19.25
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 7.50 2222.50 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 24.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 145.50 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 820.00 3732.75 784.25 2822.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:37

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.009641


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.009641
SAC_FRONTOFFICE SUPPLY FAN 0.367689
SAC_FRONTLOUNGE SUPPLY FAN 0.835062
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.792807


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 281.09
CORRIDORFLR1 PTAC HEATING COIL 35297.60
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 1122.86
102 PTAC HEATING COIL 1164.88
103 PTAC HEATING COIL 1516.61
104 PTAC HEATING COIL 1524.13
105 PTAC HEATING COIL 1175.50
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 281.02
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 281.09
CORRIDORFLR2 PTAC HEATING COIL 3227.60
201 PTAC HEATING COIL 1478.02
202_205 PTAC HEATING COIL 4491.43
206_208 PTAC HEATING COIL 3559.62
209_212 PTAC HEATING COIL 4491.43
213 PTAC HEATING COIL 1580.36
214 PTAC HEATING COIL 1550.31
215_218 PTAC HEATING COIL 4491.11
219 PTAC HEATING COIL 1122.78
220_223 PTAC HEATING COIL 4491.11
224 PTAC HEATING COIL 1399.30
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 509.51
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 281.09
CORRIDORFLR3 PTAC HEATING COIL 3587.87
301 PTAC HEATING COIL 1544.46
302_305 PTAC HEATING COIL 4635.25
306_308 PTAC HEATING COIL 3784.34
309_312 PTAC HEATING COIL 4635.38
313 PTAC HEATING COIL 1707.08
314 PTAC HEATING COIL 1660.58
315_318 PTAC HEATING COIL 4644.78
319 PTAC HEATING COIL 1219.20
320_323 PTAC HEATING COIL 4584.05
324 PTAC HEATING COIL 1499.87
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 509.51
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 509.64
CORRIDORFLR4 PTAC HEATING COIL 5397.41
401 PTAC HEATING COIL 1948.46
402_405 PTAC HEATING COIL 6062.05
406_408 PTAC HEATING COIL 4966.18
409_412 PTAC HEATING COIL 6078.46
413 PTAC HEATING COIL 2180.45
414 PTAC HEATING COIL 2117.67
415_418 PTAC HEATING COIL 6082.27
419 PTAC HEATING COIL 1673.78
420_423 PTAC HEATING COIL 6022.33
424 PTAC HEATING COIL 1947.54
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 671.65


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.798592 0.367689 6087.61
SAC_FRONTLOUNGE COOLING COIL 0.760164 0.835062 15439.69
SAC_MEETINGROOM COOLING COIL 0.727528 0.393145 8068.98
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.793952 0.792807 13293.83


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.835062
RESTROOMFLR1 DIRECT AIR 0.047052
MEETINGROOMFLR1 DIRECT AIR 0.393145
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.612549
EXERCISECENTERFLR1 DIRECT AIR 0.133206
FRONTOFFICEFLR1 DIRECT AIR 0.367689


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.367689
SAC_FRONTLOUNGE MAIN BRANCH 0.835062
SAC_MEETINGROOM MAIN BRANCH 0.393145
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.792807


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.367689
SAC_FRONTLOUNGE 0.835062
SAC_MEETINGROOM 0.393145
SAC_EXC_EMPLGE_RESTRM 0.792807


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.367689 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.835062 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.393145 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.792807 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.367689 0.367689 0.367689 0.367689 4623.43 6087.61 1.00
SAC_FRONTLOUNGE 0.835062 0.835062 0.835062 0.835062 19379.02 15439.69 1.00
SAC_MEETINGROOM 0.393145 0.393145 0.393145 0.393145 10377.32 8068.98 1.00
SAC_EXC_EMPLGE_RESTRM 0.792807 0.792807 0.792807 0.792807 7952.63 13293.83 0.168018


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 4623.43
SAC_FRONTLOUNGE HEATING COIL 19379.02
SAC_MEETINGROOM HEATING COIL 10377.32
SAC_EXC_EMPLGE_RESTRM HEATING COIL 7952.63


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.393145


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.95 -8.8
February 16.54 -2.2
March 17.53 0.30
April 19.42 6.67
May 20.29 10.10
June 22.33 16.46
July 23.56 20.57
August 23.16 19.17
September 21.61 14.69
October 19.97 8.64
November 18.01 2.84
December 16.22 -4.1
     
Annual Sum or Average 19.48 7.07
Minimum of Months 14.95 -8.8
Maximum of Months 23.56 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.93 -8.8
February 22.41 -2.2
March 22.77 0.30
April 23.45 6.67
May 23.88 10.10
June 24.88 16.46
July 25.58 20.57
August 25.28 19.17
September 24.58 14.69
October 23.68 8.64
November 22.94 2.84
December 22.23 -4.1
     
Annual Sum or Average 23.64 7.07
Minimum of Months 21.93 -8.8
Maximum of Months 25.58 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.62 -8.8
February 16.01 -2.2
March 16.97 0.30
April 18.85 6.67
May 19.79 10.10
June 21.84 16.46
July 22.99 20.57
August 22.53 19.17
September 20.97 14.69
October 19.29 8.64
November 17.38 2.84
December 15.79 -4.1
     
Annual Sum or Average 18.93 7.07
Minimum of Months 14.62 -8.8
Maximum of Months 22.99 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.15 -8.8
February 21.30 -2.2
March 21.24 0.30
April 21.84 6.67
May 22.33 10.10
June 23.18 16.46
July 23.55 20.57
August 23.47 19.17
September 22.91 14.69
October 22.04 8.64
November 21.49 2.84
December 21.19 -4.1
     
Annual Sum or Average 22.14 7.07
Minimum of Months 21.15 -8.8
Maximum of Months 23.55 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -8.8
February 21.49 -2.2
March 21.77 0.30
April 22.32 6.67
May 22.66 10.10
June 23.26 16.46
July 23.52 20.57
August 23.42 19.17
September 23.02 14.69
October 22.50 8.64
November 21.96 2.84
December 21.44 -4.1
     
Annual Sum or Average 22.38 7.07
Minimum of Months 21.11 -8.8
Maximum of Months 23.52 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.21 -8.8
February 21.42 -2.2
March 21.49 0.30
April 22.22 6.67
May 22.70 10.10
June 23.50 16.46
July 23.71 20.57
August 23.64 19.17
September 23.21 14.69
October 22.51 8.64
November 21.76 2.84
December 21.28 -4.1
     
Annual Sum or Average 22.39 7.07
Minimum of Months 21.21 -8.8
Maximum of Months 23.71 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.28 -8.8
February 23.67 -2.2
March 24.00 0.30
April 24.70 6.67
May 25.13 10.10
June 25.94 16.46
July 26.30 20.57
August 26.20 19.17
September 25.71 14.69
October 25.02 8.64
November 24.26 2.84
December 23.61 -4.1
     
Annual Sum or Average 24.82 7.07
Minimum of Months 23.28 -8.8
Maximum of Months 26.30 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.11 -8.8
February 19.41 -2.2
March 19.60 0.30
April 20.64 6.67
May 21.36 10.10
June 22.58 16.46
July 23.02 20.57
August 22.89 19.17
September 22.17 14.69
October 21.07 8.64
November 19.96 2.84
December 19.20 -4.1
     
Annual Sum or Average 20.92 7.07
Minimum of Months 19.11 -8.8
Maximum of Months 23.02 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.00 -8.8
February 19.23 -2.2
March 19.34 0.30
April 20.31 6.67
May 21.06 10.10
June 22.34 16.46
July 22.86 20.57
August 22.69 19.17
September 21.89 14.69
October 20.72 8.64
November 19.70 2.84
December 19.07 -4.1
     
Annual Sum or Average 20.69 7.07
Minimum of Months 19.00 -8.8
Maximum of Months 22.86 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.56 -8.8
February 20.70 -2.2
March 20.76 0.30
April 21.10 6.67
May 21.31 10.10
June 21.65 16.46
July 21.74 20.57
August 21.70 19.17
September 21.52 14.69
October 21.22 8.64
November 20.87 2.84
December 20.60 -4.1
     
Annual Sum or Average 21.15 7.07
Minimum of Months 20.56 -8.8
Maximum of Months 21.74 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -8.8
February 20.99 -2.2
March 21.07 0.30
April 21.35 6.67
May 21.45 10.10
June 21.69 16.46
July 21.74 20.57
August 21.73 19.17
September 21.63 14.69
October 21.49 8.64
November 21.22 2.84
December 20.88 -4.1
     
Annual Sum or Average 21.33 7.07
Minimum of Months 20.74 -8.8
Maximum of Months 21.74 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 -8.8
February 21.34 -2.2
March 21.43 0.30
April 21.60 6.67
May 21.65 10.10
June 21.74 16.46
July 21.75 20.57
August 21.75 19.17
September 21.72 14.69
October 21.67 8.64
November 21.53 2.84
December 21.28 -4.1
     
Annual Sum or Average 21.55 7.07
Minimum of Months 21.07 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 -8.8
February 21.98 -2.2
March 22.14 0.30
April 22.37 6.67
May 22.47 10.10
June 22.53 16.46
July 22.46 20.57
August 22.49 19.17
September 22.47 14.69
October 22.44 8.64
November 22.30 2.84
December 21.99 -4.1
     
Annual Sum or Average 22.28 7.07
Minimum of Months 21.72 -8.8
Maximum of Months 22.53 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 50.10 -8.8
February 50.71 -2.2
March 51.04 0.30
April 51.57 6.67
May 51.78 10.10
June 52.45 16.46
July 52.87 20.57
August 52.85 19.17
September 52.43 14.69
October 51.91 8.64
November 51.23 2.84
December 50.56 -4.1
     
Annual Sum or Average 51.63 7.07
Minimum of Months 50.10 -8.8
Maximum of Months 52.87 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 67.08 -8.8
February 67.57 -2.2
March 68.06 0.30
April 68.75 6.67
May 69.02 10.10
June 69.93 16.46
July 70.47 20.57
August 70.35 19.17
September 69.69 14.69
October 69.04 8.64
November 68.19 2.84
December 67.52 -4.1
     
Annual Sum or Average 68.81 7.07
Minimum of Months 67.08 -8.8
Maximum of Months 70.47 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.24 -8.8
February 22.62 -2.2
March 22.82 0.30
April 23.19 6.67
May 23.37 10.10
June 23.70 16.46
July 23.83 20.57
August 23.83 19.17
September 23.64 14.69
October 23.38 8.64
November 23.02 2.84
December 22.55 -4.1
     
Annual Sum or Average 23.18 7.07
Minimum of Months 22.24 -8.8
Maximum of Months 23.83 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.64 -8.8
February 22.00 -2.2
March 22.18 0.30
April 22.77 6.67
May 23.13 10.10
June 23.67 16.46
July 23.84 20.57
August 23.83 19.17
September 23.56 14.69
October 23.14 8.64
November 22.48 2.84
December 21.82 -4.1
     
Annual Sum or Average 22.84 7.07
Minimum of Months 21.64 -8.8
Maximum of Months 23.84 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.04 -8.8
February 15.79 -2.2
March 16.97 0.30
April 19.12 6.67
May 20.04 10.10
June 22.53 16.46
July 24.00 20.57
August 23.56 19.17
September 21.73 14.69
October 19.79 8.64
November 17.51 2.84
December 15.48 -4.1
     
Annual Sum or Average 19.23 7.07
Minimum of Months 14.04 -8.8
Maximum of Months 24.00 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.24 -8.8
February 19.26 -2.2
March 19.96 0.30
April 21.21 6.67
May 21.75 10.10
June 23.21 16.46
July 24.03 20.57
August 23.84 19.17
September 22.86 14.69
October 21.75 8.64
November 20.36 2.84
December 19.05 -4.1
     
Annual Sum or Average 21.30 7.07
Minimum of Months 18.24 -8.8
Maximum of Months 24.03 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.79 -8.8
February 15.71 -2.2
March 16.98 0.30
April 19.33 6.67
May 20.35 10.10
June 22.86 16.46
July 24.29 20.57
August 23.80 19.17
September 21.90 14.69
October 19.94 8.64
November 17.48 2.84
December 15.29 -4.1
     
Annual Sum or Average 19.33 7.07
Minimum of Months 13.79 -8.8
Maximum of Months 24.29 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.34 -8.8
February 21.67 -2.2
March 21.93 0.30
April 22.86 6.67
May 23.19 10.10
June 23.82 16.46
July 23.89 20.57
August 23.87 19.17
September 23.61 14.69
October 23.16 8.64
November 22.20 2.84
December 21.41 -4.1
     
Annual Sum or Average 22.75 7.07
Minimum of Months 21.34 -8.8
Maximum of Months 23.89 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.67 -8.8
February 14.46 -2.2
March 15.70 0.30
April 18.13 6.67
May 19.35 10.10
June 22.06 16.46
July 23.50 20.57
August 22.90 19.17
September 20.85 14.69
October 18.65 8.64
November 16.15 2.84
December 14.11 -4.1
     
Annual Sum or Average 18.23 7.07
Minimum of Months 12.67 -8.8
Maximum of Months 23.50 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.90 -8.8
February 19.03 -2.2
March 19.04 0.30
April 19.99 6.67
May 20.99 10.10
June 22.61 16.46
July 23.11 20.57
August 22.94 19.17
September 21.85 14.69
October 20.29 8.64
November 19.29 2.84
December 18.92 -4.1
     
Annual Sum or Average 20.59 7.07
Minimum of Months 18.90 -8.8
Maximum of Months 23.11 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 -8.8
February 20.83 -2.2
March 20.90 0.30
April 21.28 6.67
May 21.45 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.62 14.69
October 21.38 8.64
November 20.99 2.84
December 20.69 -4.1
     
Annual Sum or Average 21.25 7.07
Minimum of Months 20.64 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.66 -8.8
February 20.86 -2.2
March 20.95 0.30
April 21.32 6.67
May 21.48 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.63 14.69
October 21.42 8.64
November 21.03 2.84
December 20.72 -4.1
     
Annual Sum or Average 21.28 7.07
Minimum of Months 20.66 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.67 -8.8
February 20.88 -2.2
March 20.97 0.30
April 21.35 6.67
May 21.49 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.64 14.69
October 21.45 8.64
November 21.07 2.84
December 20.73 -4.1
     
Annual Sum or Average 21.29 7.07
Minimum of Months 20.67 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.53 -8.8
February 20.65 -2.2
March 20.71 0.30
April 21.09 6.67
May 21.31 10.10
June 21.69 16.46
July 21.75 20.57
August 21.73 19.17
September 21.53 14.69
October 21.21 8.64
November 20.81 2.84
December 20.56 -4.1
     
Annual Sum or Average 21.13 7.07
Minimum of Months 20.53 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.76 -8.8
February 21.02 -2.2
March 21.13 0.30
April 21.43 6.67
May 21.51 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.67 14.69
October 21.56 8.64
November 21.27 2.84
December 20.89 -4.1
     
Annual Sum or Average 21.37 7.07
Minimum of Months 20.76 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.82 -8.8
February 22.57 -2.2
March 22.86 0.30
April 23.22 6.67
May 23.25 10.10
June 23.33 16.46
July 23.33 20.57
August 23.33 19.17
September 23.32 14.69
October 23.28 8.64
November 23.01 2.84
December 22.43 -4.1
     
Annual Sum or Average 22.98 7.07
Minimum of Months 21.82 -8.8
Maximum of Months 23.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 29.60 -8.8
February 30.20 -2.2
March 30.66 0.30
April 31.53 6.67
May 31.88 10.10
June 32.87 16.46
July 33.33 20.57
August 33.21 19.17
September 32.57 14.69
October 31.83 8.64
November 30.82 2.84
December 30.00 -4.1
     
Annual Sum or Average 31.55 7.07
Minimum of Months 29.60 -8.8
Maximum of Months 33.33 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 -8.8
February 21.83 -2.2
March 21.87 0.30
April 22.07 6.67
May 22.22 10.10
June 22.59 16.46
July 22.88 20.57
August 22.80 19.17
September 22.56 14.69
October 22.17 8.64
November 21.91 2.84
December 21.76 -4.1
     
Annual Sum or Average 22.20 7.07
Minimum of Months 21.73 -8.8
Maximum of Months 22.88 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.91 -8.8
February 21.19 -2.2
March 21.29 0.30
April 21.52 6.67
May 21.59 10.10
June 21.74 16.46
July 21.75 20.57
August 21.75 19.17
September 21.70 14.69
October 21.63 8.64
November 21.42 2.84
December 21.08 -4.1
     
Annual Sum or Average 21.47 7.07
Minimum of Months 20.91 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.76 -8.8
February 21.03 -2.2
March 21.12 0.30
April 21.42 6.67
May 21.51 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.67 14.69
October 21.56 8.64
November 21.27 2.84
December 20.90 -4.1
     
Annual Sum or Average 21.37 7.07
Minimum of Months 20.76 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 16.64 -8.8
February 17.95 -2.2
March 18.94 0.30
April 20.65 6.67
May 21.34 10.10
June 23.37 16.46
July 24.44 20.57
August 24.12 19.17
September 22.74 14.69
October 21.24 8.64
November 19.35 2.84
December 17.61 -4.1
     
Annual Sum or Average 20.71 7.07
Minimum of Months 16.64 -8.8
Maximum of Months 24.44 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.05 -8.8
February 14.21 -2.2
March 15.84 0.30
April 18.67 6.67
May 19.83 10.10
June 23.13 16.46
July 24.94 20.57
August 24.32 19.17
September 21.90 14.69
October 19.41 8.64
November 16.41 2.84
December 13.77 -4.1
     
Annual Sum or Average 18.73 7.07
Minimum of Months 12.05 -8.8
Maximum of Months 24.94 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 12.72 -8.8
February 14.78 -2.2
March 16.13 0.30
April 18.73 6.67
May 19.94 10.10
June 22.81 16.46
July 24.42 20.57
August 23.83 19.17
September 21.65 14.69
October 19.35 8.64
November 16.63 2.84
December 14.28 -4.1
     
Annual Sum or Average 18.79 7.07
Minimum of Months 12.72 -8.8
Maximum of Months 24.42 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -8.8
February 21.21 -2.2
March 21.19 0.30
April 21.84 6.67
May 22.47 10.10
June 23.52 16.46
July 23.81 20.57
August 23.71 19.17
September 23.04 14.69
October 22.07 8.64
November 21.33 2.84
December 21.11 -4.1
     
Annual Sum or Average 22.21 7.07
Minimum of Months 21.11 -8.8
Maximum of Months 23.81 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.17 -8.8
February 13.16 -2.2
March 14.47 0.30
April 17.20 6.67
May 18.71 10.10
June 21.97 16.46
July 23.68 20.57
August 22.95 19.17
September 20.46 14.69
October 17.74 8.64
November 14.94 2.84
December 12.74 -4.1
     
Annual Sum or Average 17.46 7.07
Minimum of Months 11.17 -8.8
Maximum of Months 23.68 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.93 -2.2
March 18.91 0.30
April 19.57 6.67
May 20.60 10.10
June 22.36 16.46
July 23.00 20.57
August 22.77 19.17
September 21.48 14.69
October 19.73 8.64
November 19.00 2.84
December 18.89 -4.1
     
Annual Sum or Average 20.35 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 23.00 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.96 -2.2
March 18.94 0.30
April 19.69 6.67
May 20.74 10.10
June 22.48 16.46
July 23.06 20.57
August 22.85 19.17
September 21.62 14.69
October 19.93 8.64
November 19.12 2.84
December 18.90 -4.1
     
Annual Sum or Average 20.44 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 23.06 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.98 -2.2
March 18.97 0.30
April 19.78 6.67
May 20.83 10.10
June 22.50 16.46
July 23.05 20.57
August 22.84 19.17
September 21.66 14.69
October 20.03 8.64
November 19.17 2.84
December 18.90 -4.1
     
Annual Sum or Average 20.48 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 23.05 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.61 -8.8
February 20.80 -2.2
March 20.88 0.30
April 21.26 6.67
May 21.44 10.10
June 21.72 16.46
July 21.75 20.57
August 21.73 19.17
September 21.60 14.69
October 21.35 8.64
November 20.96 2.84
December 20.66 -4.1
     
Annual Sum or Average 21.23 7.07
Minimum of Months 20.61 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.93 -2.2
March 18.91 0.30
April 19.61 6.67
May 20.64 10.10
June 22.38 16.46
July 23.03 20.57
August 22.78 19.17
September 21.52 14.69
October 19.86 8.64
November 19.07 2.84
December 18.89 -4.1
     
Annual Sum or Average 20.39 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 23.03 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 -8.8
February 20.87 -2.2
March 20.93 0.30
April 21.27 6.67
May 21.40 10.10
June 21.70 16.46
July 21.75 20.57
August 21.73 19.17
September 21.61 14.69
October 21.42 8.64
November 21.08 2.84
December 20.72 -4.1
     
Annual Sum or Average 21.26 7.07
Minimum of Months 20.64 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 -8.8
February 21.21 -2.2
March 21.32 0.30
April 21.54 6.67
May 21.61 10.10
June 21.74 16.46
July 21.75 20.57
August 21.75 19.17
September 21.70 14.69
October 21.64 8.64
November 21.44 2.84
December 21.11 -4.1
     
Annual Sum or Average 21.48 7.07
Minimum of Months 20.92 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.07 -8.8
February 21.89 -2.2
March 22.45 0.30
April 23.58 6.67
May 24.15 10.10
June 25.46 16.46
July 26.02 20.57
August 25.83 19.17
September 24.96 14.69
October 23.93 8.64
November 22.65 2.84
December 21.58 -4.1
     
Annual Sum or Average 23.64 7.07
Minimum of Months 21.07 -8.8
Maximum of Months 26.02 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.90 -8.8
February 20.68 -2.2
March 21.15 0.30
April 22.15 6.67
May 22.52 10.10
June 23.22 16.46
July 23.32 20.57
August 23.30 19.17
September 23.01 14.69
October 22.56 8.64
November 21.46 2.84
December 20.21 -4.1
     
Annual Sum or Average 21.96 7.07
Minimum of Months 19.90 -8.8
Maximum of Months 23.32 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.82 -8.8
February 21.10 -2.2
March 21.18 0.30
April 21.43 6.67
May 21.53 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.67 14.69
October 21.56 8.64
November 21.31 2.84
December 20.96 -4.1
     
Annual Sum or Average 21.40 7.07
Minimum of Months 20.82 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.02 -8.8
February 19.39 -2.2
March 19.47 0.30
April 20.57 6.67
May 21.28 10.10
June 22.69 16.46
July 23.14 20.57
August 23.02 19.17
September 22.24 14.69
October 21.13 8.64
November 19.87 2.84
December 19.05 -4.1
     
Annual Sum or Average 20.91 7.07
Minimum of Months 19.02 -8.8
Maximum of Months 23.14 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 15.28 -8.8
February 16.69 -2.2
March 17.80 0.30
April 19.86 6.67
May 20.80 10.10
June 23.34 16.46
July 24.63 20.57
August 24.20 19.17
September 22.44 14.69
October 20.50 8.64
November 18.22 2.84
December 16.24 -4.1
     
Annual Sum or Average 20.02 7.07
Minimum of Months 15.28 -8.8
Maximum of Months 24.63 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.86 -8.8
February 13.00 -2.2
March 14.79 0.30
April 17.98 6.67
May 19.37 10.10
June 23.13 16.46
July 25.16 20.57
August 24.42 19.17
September 21.64 14.69
October 18.74 8.64
November 15.37 2.84
December 12.45 -4.1
     
Annual Sum or Average 18.10 7.07
Minimum of Months 10.86 -8.8
Maximum of Months 25.16 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 11.17 -8.8
February 13.42 -2.2
March 14.85 0.30
April 17.84 6.67
May 19.45 10.10
June 22.77 16.46
July 24.62 20.57
August 23.88 19.17
September 21.25 14.69
October 18.38 8.64
November 15.32 2.84
December 12.68 -4.1
     
Annual Sum or Average 17.99 7.07
Minimum of Months 11.17 -8.8
Maximum of Months 24.62 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.11 -8.8
February 21.20 -2.2
March 21.22 0.30
April 21.70 6.67
May 22.23 10.10
June 23.10 16.46
July 23.56 20.57
August 23.38 19.17
September 22.67 14.69
October 21.70 8.64
November 21.21 2.84
December 21.11 -4.1
     
Annual Sum or Average 22.02 7.07
Minimum of Months 21.11 -8.8
Maximum of Months 23.56 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 9.86 -8.8
February 12.16 -2.2
March 13.56 0.30
April 16.58 6.67
May 18.41 10.10
June 21.95 16.46
July 23.86 20.57
August 22.98 19.17
September 20.14 14.69
October 16.99 8.64
November 13.98 2.84
December 11.53 -4.1
     
Annual Sum or Average 16.86 7.07
Minimum of Months 9.86 -8.8
Maximum of Months 23.86 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.47 -8.8
February 20.58 -2.2
March 20.60 0.30
April 21.03 6.67
May 21.33 10.10
June 21.68 16.46
July 21.75 20.57
August 21.71 19.17
September 21.47 14.69
October 21.03 8.64
November 20.63 2.84
December 20.48 -4.1
     
Annual Sum or Average 21.07 7.07
Minimum of Months 20.47 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.96 -2.2
March 18.98 0.30
April 19.64 6.67
May 20.58 10.10
June 22.08 16.46
July 22.75 20.57
August 22.47 19.17
September 21.27 14.69
October 19.64 8.64
November 18.99 2.84
December 18.89 -4.1
     
Annual Sum or Average 20.27 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 22.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.97 -2.2
March 19.00 0.30
April 19.68 6.67
May 20.62 10.10
June 22.09 16.46
July 22.74 20.57
August 22.45 19.17
September 21.28 14.69
October 19.68 8.64
November 19.01 2.84
December 18.89 -4.1
     
Annual Sum or Average 20.28 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 22.74 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.54 -8.8
February 20.76 -2.2
March 20.84 0.30
April 21.26 6.67
May 21.47 10.10
June 21.72 16.46
July 21.75 20.57
August 21.73 19.17
September 21.59 14.69
October 21.31 8.64
November 20.88 2.84
December 20.58 -4.1
     
Annual Sum or Average 21.20 7.07
Minimum of Months 20.54 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.89 -8.8
February 18.94 -2.2
March 18.95 0.30
April 19.60 6.67
May 20.55 10.10
June 22.07 16.46
July 22.78 20.57
August 22.49 19.17
September 21.26 14.69
October 19.62 8.64
November 18.98 2.84
December 18.89 -4.1
     
Annual Sum or Average 20.26 7.07
Minimum of Months 18.89 -8.8
Maximum of Months 22.78 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.94 -8.8
February 19.23 -2.2
March 19.33 0.30
April 20.15 6.67
May 20.94 10.10
June 22.24 16.46
July 22.85 20.57
August 22.64 19.17
September 21.70 14.69
October 20.40 8.64
November 19.45 2.84
December 18.96 -4.1
     
Annual Sum or Average 20.58 7.07
Minimum of Months 18.94 -8.8
Maximum of Months 22.85 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.78 -8.8
February 21.10 -2.2
March 21.19 0.30
April 21.42 6.67
May 21.55 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.66 14.69
October 21.54 8.64
November 21.31 2.84
December 20.91 -4.1
     
Annual Sum or Average 21.39 7.07
Minimum of Months 20.78 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 18.49 -8.8
February 19.53 -2.2
March 20.13 0.30
April 21.43 6.67
May 22.23 10.10
June 23.75 16.46
July 24.48 20.57
August 24.16 19.17
September 23.01 14.69
October 21.64 8.64
November 20.25 2.84
December 19.05 -4.1
     
Annual Sum or Average 21.52 7.07
Minimum of Months 18.49 -8.8
Maximum of Months 24.48 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.74 -8.8
February 21.05 -2.2
March 21.14 0.30
April 21.40 6.67
May 21.54 10.10
June 21.73 16.46
July 21.75 20.57
August 21.74 19.17
September 21.66 14.69
October 21.53 8.64
November 21.26 2.84
December 20.85 -4.1
     
Annual Sum or Average 21.37 7.07
Minimum of Months 20.74 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.76 -8.8
February 21.08 -2.2
March 21.16 0.30
April 21.40 6.67
May 21.54 10.10
June 21.72 16.46
July 21.75 20.57
August 21.73 19.17
September 21.65 14.69
October 21.53 8.64
November 21.28 2.84
December 20.87 -4.1
     
Annual Sum or Average 21.37 7.07
Minimum of Months 20.76 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.60 -8.8
February 20.85 -2.2
March 20.92 0.30
April 21.25 6.67
May 21.44 10.10
June 21.71 16.46
July 21.75 20.57
August 21.73 19.17
September 21.60 14.69
October 21.39 8.64
November 21.05 2.84
December 20.64 -4.1
     
Annual Sum or Average 21.25 7.07
Minimum of Months 20.60 -8.8
Maximum of Months 21.75 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 14.40 -8.8
February 16.00 -2.2
March 17.19 0.30
April 19.47 6.67
May 20.65 10.10
June 23.30 16.46
July 24.68 20.57
August 24.12 19.17
September 22.13 14.69
October 19.92 8.64
November 17.51 2.84
December 15.34 -4.1
     
Annual Sum or Average 19.58 7.07
Minimum of Months 14.40 -8.8
Maximum of Months 24.68 20.57



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:37

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 10.10 -8.8
February 12.06 -2.2
March 13.90 0.30
April 17.39 6.67
May 19.11 10.10
June 23.12 16.46
July 25.29 20.57
August 24.40 19.17
September 21.29 14.69
October 18.01 8.64
November 14.42 2.84
December 11.28 -4.1
     
Annual Sum or Average 17.56 7.07
Minimum of Months 10.10 -8.8
Maximum of Months 25.29 20.57



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:37

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.213598E+12 177156.890 29-JAN-07:15 15177.258 39465.561 8969.079 109291.096 57.783 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.157755E+12 158996.856 01-FEB-07:15 15177.258 39465.561 8938.977 91104.096 114.850 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.155133E+12 144461.520 06-MAR-07:15 15177.258 39465.561 8936.527 80759.752 114.308 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.131209E+12 100168.156 29-APR-06:15 13242.271 34010.661 8914.910 43799.667 192.534 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.136261E+12 95039.572 08-MAY-06:15 15102.841 39465.561 8914.910 31182.522 365.625 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.137238E+12 89340.696 23-JUN-07:00 17789.888 43276.576 9355.274 0.000 18910.845 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.151182E+12 90182.066 14-JUL-07:00 17641.054 43276.576 9355.274 0.000 19901.050 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.147233E+12 86948.785 11-AUG-07:00 17641.054 43276.576 9355.274 0.000 16667.768 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.136753E+12 86351.780 02-SEP-07:00 17789.888 43276.576 9355.274 0.000 15921.928 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.135557E+12 104434.810 10-OCT-06:15 15177.258 39465.561 8914.910 36393.193 287.775 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.147919E+12 134882.426 27-NOV-07:15 15177.258 39465.561 8928.699 66970.242 144.552 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.184846E+12 174062.673 31-DEC-07:15 15177.258 39465.561 8960.435 106204.656 58.650 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.183468E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.131209E+12 86351.780   13242.271 34010.661 8914.910 0.000 57.783 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.213598E+12 177156.890   17789.888 43276.576 9355.274 109291.096 19901.050 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:37

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.131433E+12 126311.822 27-JAN-09:15 23305.969 40096.028 0.000 62909.825 62909.825 62909.825 23305.969
February 0.108686E+12 121458.213 04-FEB-11:15 20125.864 40096.028 0.000 61236.321 61236.321 61236.321 20125.864
March 0.113937E+12 120169.543 04-MAR-11:00 19030.804 40096.028 0.000 61042.711 61042.711 61042.711 19030.804
April 0.997295E+11 105264.873 27-APR-09:00 6603.768 40096.028 0.000 58565.077 58565.077 58565.077 6603.768
May 0.977952E+11 101730.934 08-MAY-09:45 7300.970 40096.028 0.000 54333.935 54333.935 54333.935 7300.970
June 0.882355E+11 97795.269 03-JUN-08:15 0.000 40096.028 0.000 57699.241 57699.241 57699.241 0.000
July 0.879382E+11 94397.474 01-JUL-08:45 0.000 40096.028 0.000 54301.446 54301.446 54301.446 0.000
August 0.868586E+11 92601.258 26-AUG-08:15 0.000 40096.028 0.000 52505.230 52505.230 52505.230 0.000
September 0.857685E+11 93662.864 22-SEP-08:15 0.000 40096.028 0.000 53566.836 53566.836 53566.836 0.000
October 0.934857E+11 98663.801 05-OCT-09:15 5263.130 40096.028 0.000 53304.643 53304.643 53304.643 5263.130
November 0.100928E+12 109604.686 26-NOV-10:15 15285.484 40096.028 0.000 54223.173 54223.173 54223.173 15285.484
December 0.119298E+12 121934.012 31-DEC-10:30 22003.899 40096.028 0.000 59834.085 59834.085 59834.085 22003.899
                     
Annual Sum or Average 0.121409E+13         0.000        
Minimum of Months 0.857685E+11 92601.258   0.000 40096.028 0.000 52505.230 52505.230 52505.230 0.000