Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2018-10-19 10:15:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3048.78 | 759.61 | 818.44 |
Net Site Energy | 3048.78 | 759.61 | 818.44 |
Total Source Energy | 7126.52 | 1775.60 | 1913.11 |
Net Source Energy | 7126.52 | 1775.60 | 1913.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 304.72 | 112.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 171.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 287.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 680.57 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1834.68 | 1214.09 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 304.72 | 112.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 171.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 287.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 680.57 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 204.89 | 212.77 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 492.52 | 325.92 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 190.16 | 197.48 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 457.12 | 302.50 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1834.68 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1834.68 | 100.00 |
Total On-Site and Utility Electric Sources | 1834.68 | 100.00 |
Total Electricity End Uses | 1834.68 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 784.25 |
Time Setpoint Not Met During Occupied Cooling | 2822.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6110.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
Latitude [deg] | 47.47 |
Longitude [deg] | -111.4 |
Elevation [m] | 1117.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.653 | 0.426 | 0.308 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.52_SHGC_0.40 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.653 | 0.426 | 0.308 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 96.82 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 87.38 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6087.61 | 4861.52 | 1226.09 | 0.80 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15439.69 | 11736.69 | 3703.00 | 0.76 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8068.98 | 5870.41 | 2198.57 | 0.73 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13293.83 | 10554.66 | 2739.17 | 0.79 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5802.3 | 3.15 | 10.76 | 11.39 | 10.54 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14791.5 | 3.22 | 10.99 | 11.64 | 10.88 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7763.7 | 3.28 | 11.19 | 11.86 | 11.18 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 12678.6 | 3.16 | 10.78 | 11.42 | 10.58 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 281.09 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 35297.60 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1122.86 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1164.88 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1516.61 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1524.13 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1175.50 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 281.02 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 281.09 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3227.60 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1478.02 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 4491.43 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 3559.62 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 4491.43 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1580.36 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1550.31 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 4491.11 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1122.78 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 4491.11 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1399.30 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 509.51 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 281.09 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 3587.87 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1544.46 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 4635.25 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 3784.34 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 4635.38 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1707.08 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1660.58 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 4644.78 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1219.20 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 4584.05 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1499.87 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 509.51 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 509.64 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 5397.41 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 1948.46 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 6062.05 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 4966.18 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 6078.46 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2180.45 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 2117.67 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 6082.27 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1673.78 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 6022.33 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 1947.54 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 671.65 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 4623.43 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 19379.02 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 10377.32 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 7952.63 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.90 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.37 | 411.85 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.84 | 924.55 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.39 | 440.36 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.79 | 877.76 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7382.21 | 8858.65 | 0.696 | 0.835 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 33.16 | 0.00627 |
RESTROOMFLR1 | 416.37 | 499.65 | 0.039 | 0.047 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 32.12 | 0.00627 |
MEETINGROOMFLR1 | 3472.97 | 4167.57 | 0.328 | 0.393 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM101 | 529.21 | 635.05 | 0.069 | 0.083 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 32.44 | 0.00627 |
GUESTROOM102 | 430.26 | 516.31 | 0.056 | 0.068 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 32.44 | 0.00627 |
GUESTROOM103 | 993.72 | 1192.46 | 0.130 | 0.156 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
GUESTROOM104 | 1194.52 | 1433.43 | 0.156 | 0.188 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM105 | 1568.97 | 1882.76 | 0.205 | 0.247 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
EMPLOYEELOUNGEFLR1 | 5414.04 | 6496.85 | 0.510 | 0.613 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
EXERCISECENTERFLR1 | 1178.10 | 1413.71 | 0.111 | 0.133 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.16 | 0.00627 |
FRONTOFFICEFLR1 | 3253.22 | 3903.86 | 0.306 | 0.368 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
GUESTROOM201 | 792.14 | 950.57 | 0.104 | 0.124 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 33.40 | 0.00627 |
GUESTROOM202_205 | 4040.89 | 4849.06 | 0.529 | 0.635 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 32.44 | 0.00627 |
GUESTROOM206_208 | 3275.02 | 3930.02 | 0.429 | 0.515 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 32.44 | 0.00627 |
GUESTROOM209_212 | 3852.23 | 4622.68 | 0.505 | 0.605 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 32.44 | 0.00627 |
GUESTROOM213 | 1078.89 | 1294.66 | 0.141 | 0.170 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
GUESTROOM214 | 1339.94 | 1607.93 | 0.175 | 0.211 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM215_218 | 9747.43 | 11696.91 | 1.276 | 1.532 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
GUESTROOM219 | 5475.40 | 6570.48 | 0.717 | 0.860 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM220_223 | 4728.41 | 5674.10 | 0.619 | 0.743 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
GUESTROOM224 | 1340.74 | 1608.89 | 0.176 | 0.211 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
GUESTROOM301 | 619.68 | 743.61 | 0.081 | 0.097 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM302_305 | 1495.13 | 1794.16 | 0.196 | 0.235 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 32.12 | 0.00627 |
GUESTROOM306_308 | 1308.71 | 1570.45 | 0.171 | 0.206 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 32.12 | 0.00627 |
GUESTROOM309_312 | 3830.58 | 4596.70 | 0.502 | 0.602 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 32.12 | 0.00627 |
GUESTROOM313 | 583.93 | 700.71 | 0.076 | 0.092 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 26.72 | 0.00627 |
GUESTROOM314 | 1259.61 | 1511.53 | 0.165 | 0.198 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 33.16 | 0.00627 |
GUESTROOM315_318 | 5155.70 | 6186.83 | 0.675 | 0.810 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM319 | 1152.52 | 1383.02 | 0.151 | 0.181 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM320_323 | 4535.39 | 5442.47 | 0.594 | 0.713 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM324 | 769.16 | 922.99 | 0.101 | 0.121 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM401 | 1478.48 | 1774.17 | 0.194 | 0.232 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 33.40 | 0.00627 |
GUESTROOM402_405 | 2345.77 | 2814.92 | 0.307 | 0.369 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM406_408 | 2005.27 | 2406.33 | 0.263 | 0.315 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM409_412 | 4996.17 | 5995.40 | 0.654 | 0.785 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM413 | 864.88 | 1037.85 | 0.113 | 0.136 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 32.68 | 0.00627 |
GUESTROOM414 | 1089.02 | 1306.83 | 0.143 | 0.171 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40 | 0.00627 |
GUESTROOM415_418 | 5961.44 | 7153.72 | 0.781 | 0.937 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40 | 0.00627 |
GUESTROOM419 | 1632.64 | 1959.16 | 0.214 | 0.257 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40 | 0.00627 |
GUESTROOM420_423 | 5920.86 | 7105.03 | 0.775 | 0.930 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40 | 0.00627 |
GUESTROOM424 | 1649.60 | 1979.52 | 0.216 | 0.259 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 33.40 | 0.00627 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
CORRIDORFLR1 | 14630.84 | 17557.00 | 1.377 | 1.653 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 29.56 | 0.00627 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
CORRIDORFLR2 | 2681.28 | 3217.53 | 0.252 | 0.303 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 30.76 | 0.00627 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
CORRIDORFLR3 | 1289.58 | 1547.50 | 0.121 | 0.146 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 30.36 | 0.00627 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 | |
CORRIDORFLR4 | 2270.48 | 2724.57 | 0.214 | 0.257 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 32.68 | 0.00627 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 0.00627 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2233.40 | 2680.08 | 0.072 | 0.236 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -27.60 | 0.00034 |
RESTROOMFLR1 | 170.47 | 204.56 | 0.005 | 0.007 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -27.60 | 0.00034 |
MEETINGROOMFLR1 | 793.83 | 952.60 | 0.026 | 0.126 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -27.60 | 0.00034 |
GUESTROOM101 | 336.38 | 403.65 | 0.011 | 0.013 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -27.60 | 0.00034 |
GUESTROOM102 | 383.37 | 460.04 | 0.012 | 0.015 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | -27.60 | 0.00034 |
GUESTROOM103 | 676.47 | 811.77 | 0.022 | 0.026 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -27.60 | 0.00034 |
GUESTROOM104 | 682.79 | 819.34 | 0.022 | 0.026 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -27.60 | 0.00034 |
GUESTROOM105 | 392.26 | 470.71 | 0.013 | 0.015 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -27.60 | 0.00034 |
EMPLOYEELOUNGEFLR1 | 374.56 | 449.47 | 0.012 | 0.051 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -27.60 | 0.00034 |
EXERCISECENTERFLR1 | 269.60 | 323.52 | 0.009 | 0.043 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -27.60 | 0.00034 |
FRONTOFFICEFLR1 | 1439.85 | 1727.82 | 0.046 | 0.056 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -27.60 | 0.00034 |
GUESTROOM201 | 644.31 | 773.18 | 0.021 | 0.025 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -27.60 | 0.00034 |
GUESTROOM202_205 | 1343.84 | 1612.61 | 0.043 | 0.054 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -27.60 | 0.00034 |
GUESTROOM206_208 | 1069.46 | 1283.35 | 0.034 | 0.043 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
GUESTROOM209_212 | 1251.94 | 1502.33 | 0.040 | 0.054 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -27.60 | 0.00034 |
GUESTROOM213 | 729.60 | 875.52 | 0.024 | 0.028 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 11:00:00 | -27.60 | 0.00034 |
GUESTROOM214 | 704.60 | 845.52 | 0.023 | 0.027 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -27.60 | 0.00034 |
GUESTROOM215_218 | 1289.66 | 1547.59 | 0.042 | 0.054 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -27.60 | 0.00034 |
GUESTROOM219 | 334.93 | 401.92 | 0.011 | 0.013 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -27.60 | 0.00034 |
GUESTROOM220_223 | 1228.68 | 1474.42 | 0.040 | 0.054 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -27.60 | 0.00034 |
GUESTROOM224 | 578.76 | 694.51 | 0.019 | 0.022 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -27.60 | 0.00034 |
GUESTROOM301 | 699.68 | 839.62 | 0.023 | 0.027 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -27.60 | 0.00034 |
GUESTROOM302_305 | 1513.24 | 1815.89 | 0.049 | 0.059 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | -27.60 | 0.00034 |
GUESTROOM306_308 | 1291.58 | 1549.90 | 0.042 | 0.050 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -27.60 | 0.00034 |
GUESTROOM309_312 | 1513.35 | 1816.02 | 0.049 | 0.059 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -27.60 | 0.00034 |
GUESTROOM313 | 835.20 | 1002.24 | 0.027 | 0.032 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -27.60 | 0.00034 |
GUESTROOM314 | 796.50 | 955.79 | 0.026 | 0.031 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 14:45:00 | -27.60 | 0.00034 |
GUESTROOM315_318 | 1521.35 | 1825.62 | 0.049 | 0.059 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -27.60 | 0.00034 |
GUESTROOM319 | 428.68 | 514.41 | 0.014 | 0.017 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60 | 0.00034 |
GUESTROOM320_323 | 1470.74 | 1764.89 | 0.047 | 0.057 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -27.60 | 0.00034 |
GUESTROOM324 | 662.56 | 795.08 | 0.021 | 0.026 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:00:00 | -27.60 | 0.00034 |
GUESTROOM401 | 1036.35 | 1243.62 | 0.033 | 0.040 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | -27.60 | 0.00034 |
GUESTROOM402_405 | 2702.24 | 3242.69 | 0.087 | 0.105 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -27.60 | 0.00034 |
GUESTROOM406_408 | 2276.45 | 2731.74 | 0.073 | 0.088 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -27.60 | 0.00034 |
GUESTROOM409_412 | 2715.92 | 3259.10 | 0.088 | 0.105 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -27.60 | 0.00034 |
GUESTROOM413 | 1229.68 | 1475.61 | 0.040 | 0.048 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60 | 0.00034 |
GUESTROOM414 | 1177.40 | 1412.88 | 0.038 | 0.046 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -27.60 | 0.00034 |
GUESTROOM415_418 | 2719.26 | 3263.11 | 0.088 | 0.105 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -27.60 | 0.00034 |
GUESTROOM419 | 807.49 | 968.99 | 0.026 | 0.031 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -27.60 | 0.00034 |
GUESTROOM420_423 | 2669.31 | 3203.18 | 0.086 | 0.103 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 19:00:00 | -27.60 | 0.00034 |
GUESTROOM424 | 1035.62 | 1242.75 | 0.033 | 0.040 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -27.60 | 0.00034 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00034 | |
CORRIDORFLR1 | 27394.05 | 32872.86 | 0.882 | 1.058 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -27.60 | 0.00034 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00034 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00034 | |
CORRIDORFLR2 | 1023.90 | 1228.69 | 0.033 | 0.040 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -27.60 | 0.00034 |
FRONTSTAIRSFLR2 | 15.52 | 18.62 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -27.60 | 0.00034 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00034 | |
CORRIDORFLR3 | 1324.12 | 1588.95 | 0.043 | 0.051 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -27.60 | 0.00034 |
FRONTSTAIRSFLR3 | 148.40 | 178.09 | 0.003 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -27.60 | 0.00034 |
REARSTAIRSFLR4 | 49.65 | 59.58 | 0.001 | 0.006 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60 | 0.00034 |
CORRIDORFLR4 | 2832.08 | 3398.50 | 0.091 | 0.110 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -27.60 | 0.00034 |
FRONTSTAIRSFLR4 | 369.34 | 443.20 | 0.008 | 0.010 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -27.60 | 0.00034 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.37 | 0.37 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.84 | 0.84 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.39 | 0.39 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.79 | 0.79 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1805.75 | 7649.75 | 1687.00 |
RESTROOMFLR1 | 846.00 | 8460.25 | 840.00 |
MEETINGROOMFLR1 | 459.75 | 3762.50 | 333.50 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 2411.75 | 8760.00 | 2411.75 |
GUESTROOM104 | 1173.00 | 8758.25 | 1173.00 |
GUESTROOM105 | 314.25 | 8673.25 | 314.25 |
EMPLOYEELOUNGEFLR1 | 2704.75 | 2437.75 | 344.75 |
EXERCISECENTERFLR1 | 747.50 | 3644.00 | 92.50 |
FRONTOFFICEFLR1 | 1025.50 | 7382.25 | 788.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 1448.00 | 8751.50 | 1448.00 |
GUESTROOM206_208 | 1274.50 | 8751.25 | 1274.50 |
GUESTROOM209_212 | 1135.75 | 8760.00 | 1135.75 |
GUESTROOM213 | 2687.50 | 8760.00 | 2687.50 |
GUESTROOM214 | 1064.25 | 8704.50 | 1064.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 3201.00 | 4551.75 | 275.00 |
GUESTROOM220_223 | 497.00 | 8628.50 | 496.00 |
GUESTROOM224 | 1055.75 | 8689.00 | 1055.75 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 1593.75 | 8760.00 | 1593.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 1867.50 | 8704.75 | 1867.50 |
GUESTROOM315_318 | 533.50 | 8497.50 | 532.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 793.00 | 8666.75 | 792.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4279.25 | 8370.75 | 4260.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 2742.25 | 8295.25 | 2705.00 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 1820.75 | 7939.00 | 1566.50 |
GUESTROOM419 | 1724.25 | 8151.00 | 1641.00 |
GUESTROOM420_423 | 1924.50 | 7986.50 | 1690.25 |
GUESTROOM424 | 2909.00 | 8260.50 | 2832.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7294.50 | 8760.00 | 6110.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
RESTROOMFLR1 | 607.50 | 297.50 | 607.50 | 297.50 |
MEETINGROOMFLR1 | 0.50 | 0.00 | 0.50 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 1.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 15.00 | 13.00 | 15.00 | 13.00 |
GUESTROOM104 | 8.00 | 18.50 | 8.00 | 18.50 |
GUESTROOM105 | 2.00 | 30.25 | 2.00 | 30.25 |
EMPLOYEELOUNGEFLR1 | 514.00 | 967.00 | 384.25 | 580.00 |
EXERCISECENTERFLR1 | 1.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 11.75 | 1.75 | 11.75 | 1.75 |
GUESTROOM206_208 | 11.50 | 6.00 | 11.50 | 6.00 |
GUESTROOM209_212 | 11.00 | 1.50 | 11.00 | 1.50 |
GUESTROOM213 | 15.75 | 2.00 | 15.75 | 2.00 |
GUESTROOM214 | 8.00 | 7.50 | 8.00 | 7.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 2135.50 | 0.00 | 2135.50 |
GUESTROOM220_223 | 5.00 | 5.50 | 5.00 | 5.50 |
GUESTROOM224 | 7.75 | 7.50 | 7.75 | 7.50 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 14.75 | 1.50 | 14.75 | 1.50 |
GUESTROOM313 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 8.75 | 7.25 | 8.75 | 7.25 |
GUESTROOM315_318 | 5.00 | 6.50 | 5.00 | 6.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 6.75 | 5.25 | 6.75 | 5.25 |
GUESTROOM324 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 10.75 | 13.25 | 10.75 | 13.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 16.75 | 9.25 | 16.75 | 9.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 10.25 | 15.50 | 10.25 | 15.50 |
GUESTROOM419 | 8.50 | 21.75 | 8.50 | 21.75 |
GUESTROOM420_423 | 11.00 | 14.75 | 11.00 | 14.75 |
GUESTROOM424 | 6.75 | 19.25 | 6.75 | 19.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 7.50 | 2222.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 24.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 145.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 820.00 | 3732.75 | 784.25 | 2822.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:37
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.009641 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.009641 |
SAC_FRONTOFFICE SUPPLY FAN | 0.367689 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.835062 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.792807 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 281.09 |
CORRIDORFLR1 PTAC HEATING COIL | 35297.60 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1122.86 |
102 PTAC HEATING COIL | 1164.88 |
103 PTAC HEATING COIL | 1516.61 |
104 PTAC HEATING COIL | 1524.13 |
105 PTAC HEATING COIL | 1175.50 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 281.02 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 281.09 |
CORRIDORFLR2 PTAC HEATING COIL | 3227.60 |
201 PTAC HEATING COIL | 1478.02 |
202_205 PTAC HEATING COIL | 4491.43 |
206_208 PTAC HEATING COIL | 3559.62 |
209_212 PTAC HEATING COIL | 4491.43 |
213 PTAC HEATING COIL | 1580.36 |
214 PTAC HEATING COIL | 1550.31 |
215_218 PTAC HEATING COIL | 4491.11 |
219 PTAC HEATING COIL | 1122.78 |
220_223 PTAC HEATING COIL | 4491.11 |
224 PTAC HEATING COIL | 1399.30 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 509.51 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 281.09 |
CORRIDORFLR3 PTAC HEATING COIL | 3587.87 |
301 PTAC HEATING COIL | 1544.46 |
302_305 PTAC HEATING COIL | 4635.25 |
306_308 PTAC HEATING COIL | 3784.34 |
309_312 PTAC HEATING COIL | 4635.38 |
313 PTAC HEATING COIL | 1707.08 |
314 PTAC HEATING COIL | 1660.58 |
315_318 PTAC HEATING COIL | 4644.78 |
319 PTAC HEATING COIL | 1219.20 |
320_323 PTAC HEATING COIL | 4584.05 |
324 PTAC HEATING COIL | 1499.87 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 509.51 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 509.64 |
CORRIDORFLR4 PTAC HEATING COIL | 5397.41 |
401 PTAC HEATING COIL | 1948.46 |
402_405 PTAC HEATING COIL | 6062.05 |
406_408 PTAC HEATING COIL | 4966.18 |
409_412 PTAC HEATING COIL | 6078.46 |
413 PTAC HEATING COIL | 2180.45 |
414 PTAC HEATING COIL | 2117.67 |
415_418 PTAC HEATING COIL | 6082.27 |
419 PTAC HEATING COIL | 1673.78 |
420_423 PTAC HEATING COIL | 6022.33 |
424 PTAC HEATING COIL | 1947.54 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 671.65 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.798592 | 0.367689 | 6087.61 |
SAC_FRONTLOUNGE COOLING COIL | 0.760164 | 0.835062 | 15439.69 |
SAC_MEETINGROOM COOLING COIL | 0.727528 | 0.393145 | 8068.98 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.793952 | 0.792807 | 13293.83 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.835062 |
RESTROOMFLR1 DIRECT AIR | 0.047052 |
MEETINGROOMFLR1 DIRECT AIR | 0.393145 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.612549 |
EXERCISECENTERFLR1 DIRECT AIR | 0.133206 |
FRONTOFFICEFLR1 DIRECT AIR | 0.367689 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.367689 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.835062 |
SAC_MEETINGROOM MAIN BRANCH | 0.393145 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.792807 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.367689 |
SAC_FRONTLOUNGE | 0.835062 |
SAC_MEETINGROOM | 0.393145 |
SAC_EXC_EMPLGE_RESTRM | 0.792807 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.367689 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.835062 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.393145 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.792807 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.367689 | 0.367689 | 0.367689 | 0.367689 | 4623.43 | 6087.61 | 1.00 |
SAC_FRONTLOUNGE | 0.835062 | 0.835062 | 0.835062 | 0.835062 | 19379.02 | 15439.69 | 1.00 |
SAC_MEETINGROOM | 0.393145 | 0.393145 | 0.393145 | 0.393145 | 10377.32 | 8068.98 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.792807 | 0.792807 | 0.792807 | 0.792807 | 7952.63 | 13293.83 | 0.168018 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 4623.43 |
SAC_FRONTLOUNGE HEATING COIL | 19379.02 |
SAC_MEETINGROOM HEATING COIL | 10377.32 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 7952.63 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.393145 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.95 | -8.8 |
February | 16.54 | -2.2 |
March | 17.53 | 0.30 |
April | 19.42 | 6.67 |
May | 20.29 | 10.10 |
June | 22.33 | 16.46 |
July | 23.56 | 20.57 |
August | 23.16 | 19.17 |
September | 21.61 | 14.69 |
October | 19.97 | 8.64 |
November | 18.01 | 2.84 |
December | 16.22 | -4.1 |
Annual Sum or Average | 19.48 | 7.07 |
Minimum of Months | 14.95 | -8.8 |
Maximum of Months | 23.56 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.93 | -8.8 |
February | 22.41 | -2.2 |
March | 22.77 | 0.30 |
April | 23.45 | 6.67 |
May | 23.88 | 10.10 |
June | 24.88 | 16.46 |
July | 25.58 | 20.57 |
August | 25.28 | 19.17 |
September | 24.58 | 14.69 |
October | 23.68 | 8.64 |
November | 22.94 | 2.84 |
December | 22.23 | -4.1 |
Annual Sum or Average | 23.64 | 7.07 |
Minimum of Months | 21.93 | -8.8 |
Maximum of Months | 25.58 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.62 | -8.8 |
February | 16.01 | -2.2 |
March | 16.97 | 0.30 |
April | 18.85 | 6.67 |
May | 19.79 | 10.10 |
June | 21.84 | 16.46 |
July | 22.99 | 20.57 |
August | 22.53 | 19.17 |
September | 20.97 | 14.69 |
October | 19.29 | 8.64 |
November | 17.38 | 2.84 |
December | 15.79 | -4.1 |
Annual Sum or Average | 18.93 | 7.07 |
Minimum of Months | 14.62 | -8.8 |
Maximum of Months | 22.99 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | -8.8 |
February | 21.30 | -2.2 |
March | 21.24 | 0.30 |
April | 21.84 | 6.67 |
May | 22.33 | 10.10 |
June | 23.18 | 16.46 |
July | 23.55 | 20.57 |
August | 23.47 | 19.17 |
September | 22.91 | 14.69 |
October | 22.04 | 8.64 |
November | 21.49 | 2.84 |
December | 21.19 | -4.1 |
Annual Sum or Average | 22.14 | 7.07 |
Minimum of Months | 21.15 | -8.8 |
Maximum of Months | 23.55 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -8.8 |
February | 21.49 | -2.2 |
March | 21.77 | 0.30 |
April | 22.32 | 6.67 |
May | 22.66 | 10.10 |
June | 23.26 | 16.46 |
July | 23.52 | 20.57 |
August | 23.42 | 19.17 |
September | 23.02 | 14.69 |
October | 22.50 | 8.64 |
November | 21.96 | 2.84 |
December | 21.44 | -4.1 |
Annual Sum or Average | 22.38 | 7.07 |
Minimum of Months | 21.11 | -8.8 |
Maximum of Months | 23.52 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | -8.8 |
February | 21.42 | -2.2 |
March | 21.49 | 0.30 |
April | 22.22 | 6.67 |
May | 22.70 | 10.10 |
June | 23.50 | 16.46 |
July | 23.71 | 20.57 |
August | 23.64 | 19.17 |
September | 23.21 | 14.69 |
October | 22.51 | 8.64 |
November | 21.76 | 2.84 |
December | 21.28 | -4.1 |
Annual Sum or Average | 22.39 | 7.07 |
Minimum of Months | 21.21 | -8.8 |
Maximum of Months | 23.71 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.28 | -8.8 |
February | 23.67 | -2.2 |
March | 24.00 | 0.30 |
April | 24.70 | 6.67 |
May | 25.13 | 10.10 |
June | 25.94 | 16.46 |
July | 26.30 | 20.57 |
August | 26.20 | 19.17 |
September | 25.71 | 14.69 |
October | 25.02 | 8.64 |
November | 24.26 | 2.84 |
December | 23.61 | -4.1 |
Annual Sum or Average | 24.82 | 7.07 |
Minimum of Months | 23.28 | -8.8 |
Maximum of Months | 26.30 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.11 | -8.8 |
February | 19.41 | -2.2 |
March | 19.60 | 0.30 |
April | 20.64 | 6.67 |
May | 21.36 | 10.10 |
June | 22.58 | 16.46 |
July | 23.02 | 20.57 |
August | 22.89 | 19.17 |
September | 22.17 | 14.69 |
October | 21.07 | 8.64 |
November | 19.96 | 2.84 |
December | 19.20 | -4.1 |
Annual Sum or Average | 20.92 | 7.07 |
Minimum of Months | 19.11 | -8.8 |
Maximum of Months | 23.02 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.00 | -8.8 |
February | 19.23 | -2.2 |
March | 19.34 | 0.30 |
April | 20.31 | 6.67 |
May | 21.06 | 10.10 |
June | 22.34 | 16.46 |
July | 22.86 | 20.57 |
August | 22.69 | 19.17 |
September | 21.89 | 14.69 |
October | 20.72 | 8.64 |
November | 19.70 | 2.84 |
December | 19.07 | -4.1 |
Annual Sum or Average | 20.69 | 7.07 |
Minimum of Months | 19.00 | -8.8 |
Maximum of Months | 22.86 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.56 | -8.8 |
February | 20.70 | -2.2 |
March | 20.76 | 0.30 |
April | 21.10 | 6.67 |
May | 21.31 | 10.10 |
June | 21.65 | 16.46 |
July | 21.74 | 20.57 |
August | 21.70 | 19.17 |
September | 21.52 | 14.69 |
October | 21.22 | 8.64 |
November | 20.87 | 2.84 |
December | 20.60 | -4.1 |
Annual Sum or Average | 21.15 | 7.07 |
Minimum of Months | 20.56 | -8.8 |
Maximum of Months | 21.74 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | -8.8 |
February | 20.99 | -2.2 |
March | 21.07 | 0.30 |
April | 21.35 | 6.67 |
May | 21.45 | 10.10 |
June | 21.69 | 16.46 |
July | 21.74 | 20.57 |
August | 21.73 | 19.17 |
September | 21.63 | 14.69 |
October | 21.49 | 8.64 |
November | 21.22 | 2.84 |
December | 20.88 | -4.1 |
Annual Sum or Average | 21.33 | 7.07 |
Minimum of Months | 20.74 | -8.8 |
Maximum of Months | 21.74 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | -8.8 |
February | 21.34 | -2.2 |
March | 21.43 | 0.30 |
April | 21.60 | 6.67 |
May | 21.65 | 10.10 |
June | 21.74 | 16.46 |
July | 21.75 | 20.57 |
August | 21.75 | 19.17 |
September | 21.72 | 14.69 |
October | 21.67 | 8.64 |
November | 21.53 | 2.84 |
December | 21.28 | -4.1 |
Annual Sum or Average | 21.55 | 7.07 |
Minimum of Months | 21.07 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | -8.8 |
February | 21.98 | -2.2 |
March | 22.14 | 0.30 |
April | 22.37 | 6.67 |
May | 22.47 | 10.10 |
June | 22.53 | 16.46 |
July | 22.46 | 20.57 |
August | 22.49 | 19.17 |
September | 22.47 | 14.69 |
October | 22.44 | 8.64 |
November | 22.30 | 2.84 |
December | 21.99 | -4.1 |
Annual Sum or Average | 22.28 | 7.07 |
Minimum of Months | 21.72 | -8.8 |
Maximum of Months | 22.53 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 50.10 | -8.8 |
February | 50.71 | -2.2 |
March | 51.04 | 0.30 |
April | 51.57 | 6.67 |
May | 51.78 | 10.10 |
June | 52.45 | 16.46 |
July | 52.87 | 20.57 |
August | 52.85 | 19.17 |
September | 52.43 | 14.69 |
October | 51.91 | 8.64 |
November | 51.23 | 2.84 |
December | 50.56 | -4.1 |
Annual Sum or Average | 51.63 | 7.07 |
Minimum of Months | 50.10 | -8.8 |
Maximum of Months | 52.87 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 67.08 | -8.8 |
February | 67.57 | -2.2 |
March | 68.06 | 0.30 |
April | 68.75 | 6.67 |
May | 69.02 | 10.10 |
June | 69.93 | 16.46 |
July | 70.47 | 20.57 |
August | 70.35 | 19.17 |
September | 69.69 | 14.69 |
October | 69.04 | 8.64 |
November | 68.19 | 2.84 |
December | 67.52 | -4.1 |
Annual Sum or Average | 68.81 | 7.07 |
Minimum of Months | 67.08 | -8.8 |
Maximum of Months | 70.47 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.24 | -8.8 |
February | 22.62 | -2.2 |
March | 22.82 | 0.30 |
April | 23.19 | 6.67 |
May | 23.37 | 10.10 |
June | 23.70 | 16.46 |
July | 23.83 | 20.57 |
August | 23.83 | 19.17 |
September | 23.64 | 14.69 |
October | 23.38 | 8.64 |
November | 23.02 | 2.84 |
December | 22.55 | -4.1 |
Annual Sum or Average | 23.18 | 7.07 |
Minimum of Months | 22.24 | -8.8 |
Maximum of Months | 23.83 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.64 | -8.8 |
February | 22.00 | -2.2 |
March | 22.18 | 0.30 |
April | 22.77 | 6.67 |
May | 23.13 | 10.10 |
June | 23.67 | 16.46 |
July | 23.84 | 20.57 |
August | 23.83 | 19.17 |
September | 23.56 | 14.69 |
October | 23.14 | 8.64 |
November | 22.48 | 2.84 |
December | 21.82 | -4.1 |
Annual Sum or Average | 22.84 | 7.07 |
Minimum of Months | 21.64 | -8.8 |
Maximum of Months | 23.84 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.04 | -8.8 |
February | 15.79 | -2.2 |
March | 16.97 | 0.30 |
April | 19.12 | 6.67 |
May | 20.04 | 10.10 |
June | 22.53 | 16.46 |
July | 24.00 | 20.57 |
August | 23.56 | 19.17 |
September | 21.73 | 14.69 |
October | 19.79 | 8.64 |
November | 17.51 | 2.84 |
December | 15.48 | -4.1 |
Annual Sum or Average | 19.23 | 7.07 |
Minimum of Months | 14.04 | -8.8 |
Maximum of Months | 24.00 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.24 | -8.8 |
February | 19.26 | -2.2 |
March | 19.96 | 0.30 |
April | 21.21 | 6.67 |
May | 21.75 | 10.10 |
June | 23.21 | 16.46 |
July | 24.03 | 20.57 |
August | 23.84 | 19.17 |
September | 22.86 | 14.69 |
October | 21.75 | 8.64 |
November | 20.36 | 2.84 |
December | 19.05 | -4.1 |
Annual Sum or Average | 21.30 | 7.07 |
Minimum of Months | 18.24 | -8.8 |
Maximum of Months | 24.03 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.79 | -8.8 |
February | 15.71 | -2.2 |
March | 16.98 | 0.30 |
April | 19.33 | 6.67 |
May | 20.35 | 10.10 |
June | 22.86 | 16.46 |
July | 24.29 | 20.57 |
August | 23.80 | 19.17 |
September | 21.90 | 14.69 |
October | 19.94 | 8.64 |
November | 17.48 | 2.84 |
December | 15.29 | -4.1 |
Annual Sum or Average | 19.33 | 7.07 |
Minimum of Months | 13.79 | -8.8 |
Maximum of Months | 24.29 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | -8.8 |
February | 21.67 | -2.2 |
March | 21.93 | 0.30 |
April | 22.86 | 6.67 |
May | 23.19 | 10.10 |
June | 23.82 | 16.46 |
July | 23.89 | 20.57 |
August | 23.87 | 19.17 |
September | 23.61 | 14.69 |
October | 23.16 | 8.64 |
November | 22.20 | 2.84 |
December | 21.41 | -4.1 |
Annual Sum or Average | 22.75 | 7.07 |
Minimum of Months | 21.34 | -8.8 |
Maximum of Months | 23.89 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.67 | -8.8 |
February | 14.46 | -2.2 |
March | 15.70 | 0.30 |
April | 18.13 | 6.67 |
May | 19.35 | 10.10 |
June | 22.06 | 16.46 |
July | 23.50 | 20.57 |
August | 22.90 | 19.17 |
September | 20.85 | 14.69 |
October | 18.65 | 8.64 |
November | 16.15 | 2.84 |
December | 14.11 | -4.1 |
Annual Sum or Average | 18.23 | 7.07 |
Minimum of Months | 12.67 | -8.8 |
Maximum of Months | 23.50 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | -8.8 |
February | 19.03 | -2.2 |
March | 19.04 | 0.30 |
April | 19.99 | 6.67 |
May | 20.99 | 10.10 |
June | 22.61 | 16.46 |
July | 23.11 | 20.57 |
August | 22.94 | 19.17 |
September | 21.85 | 14.69 |
October | 20.29 | 8.64 |
November | 19.29 | 2.84 |
December | 18.92 | -4.1 |
Annual Sum or Average | 20.59 | 7.07 |
Minimum of Months | 18.90 | -8.8 |
Maximum of Months | 23.11 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -8.8 |
February | 20.83 | -2.2 |
March | 20.90 | 0.30 |
April | 21.28 | 6.67 |
May | 21.45 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.62 | 14.69 |
October | 21.38 | 8.64 |
November | 20.99 | 2.84 |
December | 20.69 | -4.1 |
Annual Sum or Average | 21.25 | 7.07 |
Minimum of Months | 20.64 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | -8.8 |
February | 20.86 | -2.2 |
March | 20.95 | 0.30 |
April | 21.32 | 6.67 |
May | 21.48 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.63 | 14.69 |
October | 21.42 | 8.64 |
November | 21.03 | 2.84 |
December | 20.72 | -4.1 |
Annual Sum or Average | 21.28 | 7.07 |
Minimum of Months | 20.66 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | -8.8 |
February | 20.88 | -2.2 |
March | 20.97 | 0.30 |
April | 21.35 | 6.67 |
May | 21.49 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.64 | 14.69 |
October | 21.45 | 8.64 |
November | 21.07 | 2.84 |
December | 20.73 | -4.1 |
Annual Sum or Average | 21.29 | 7.07 |
Minimum of Months | 20.67 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -8.8 |
February | 20.65 | -2.2 |
March | 20.71 | 0.30 |
April | 21.09 | 6.67 |
May | 21.31 | 10.10 |
June | 21.69 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.53 | 14.69 |
October | 21.21 | 8.64 |
November | 20.81 | 2.84 |
December | 20.56 | -4.1 |
Annual Sum or Average | 21.13 | 7.07 |
Minimum of Months | 20.53 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | -8.8 |
February | 21.02 | -2.2 |
March | 21.13 | 0.30 |
April | 21.43 | 6.67 |
May | 21.51 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.67 | 14.69 |
October | 21.56 | 8.64 |
November | 21.27 | 2.84 |
December | 20.89 | -4.1 |
Annual Sum or Average | 21.37 | 7.07 |
Minimum of Months | 20.76 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | -8.8 |
February | 22.57 | -2.2 |
March | 22.86 | 0.30 |
April | 23.22 | 6.67 |
May | 23.25 | 10.10 |
June | 23.33 | 16.46 |
July | 23.33 | 20.57 |
August | 23.33 | 19.17 |
September | 23.32 | 14.69 |
October | 23.28 | 8.64 |
November | 23.01 | 2.84 |
December | 22.43 | -4.1 |
Annual Sum or Average | 22.98 | 7.07 |
Minimum of Months | 21.82 | -8.8 |
Maximum of Months | 23.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.60 | -8.8 |
February | 30.20 | -2.2 |
March | 30.66 | 0.30 |
April | 31.53 | 6.67 |
May | 31.88 | 10.10 |
June | 32.87 | 16.46 |
July | 33.33 | 20.57 |
August | 33.21 | 19.17 |
September | 32.57 | 14.69 |
October | 31.83 | 8.64 |
November | 30.82 | 2.84 |
December | 30.00 | -4.1 |
Annual Sum or Average | 31.55 | 7.07 |
Minimum of Months | 29.60 | -8.8 |
Maximum of Months | 33.33 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -8.8 |
February | 21.83 | -2.2 |
March | 21.87 | 0.30 |
April | 22.07 | 6.67 |
May | 22.22 | 10.10 |
June | 22.59 | 16.46 |
July | 22.88 | 20.57 |
August | 22.80 | 19.17 |
September | 22.56 | 14.69 |
October | 22.17 | 8.64 |
November | 21.91 | 2.84 |
December | 21.76 | -4.1 |
Annual Sum or Average | 22.20 | 7.07 |
Minimum of Months | 21.73 | -8.8 |
Maximum of Months | 22.88 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | -8.8 |
February | 21.19 | -2.2 |
March | 21.29 | 0.30 |
April | 21.52 | 6.67 |
May | 21.59 | 10.10 |
June | 21.74 | 16.46 |
July | 21.75 | 20.57 |
August | 21.75 | 19.17 |
September | 21.70 | 14.69 |
October | 21.63 | 8.64 |
November | 21.42 | 2.84 |
December | 21.08 | -4.1 |
Annual Sum or Average | 21.47 | 7.07 |
Minimum of Months | 20.91 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | -8.8 |
February | 21.03 | -2.2 |
March | 21.12 | 0.30 |
April | 21.42 | 6.67 |
May | 21.51 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.67 | 14.69 |
October | 21.56 | 8.64 |
November | 21.27 | 2.84 |
December | 20.90 | -4.1 |
Annual Sum or Average | 21.37 | 7.07 |
Minimum of Months | 20.76 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 16.64 | -8.8 |
February | 17.95 | -2.2 |
March | 18.94 | 0.30 |
April | 20.65 | 6.67 |
May | 21.34 | 10.10 |
June | 23.37 | 16.46 |
July | 24.44 | 20.57 |
August | 24.12 | 19.17 |
September | 22.74 | 14.69 |
October | 21.24 | 8.64 |
November | 19.35 | 2.84 |
December | 17.61 | -4.1 |
Annual Sum or Average | 20.71 | 7.07 |
Minimum of Months | 16.64 | -8.8 |
Maximum of Months | 24.44 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.05 | -8.8 |
February | 14.21 | -2.2 |
March | 15.84 | 0.30 |
April | 18.67 | 6.67 |
May | 19.83 | 10.10 |
June | 23.13 | 16.46 |
July | 24.94 | 20.57 |
August | 24.32 | 19.17 |
September | 21.90 | 14.69 |
October | 19.41 | 8.64 |
November | 16.41 | 2.84 |
December | 13.77 | -4.1 |
Annual Sum or Average | 18.73 | 7.07 |
Minimum of Months | 12.05 | -8.8 |
Maximum of Months | 24.94 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.72 | -8.8 |
February | 14.78 | -2.2 |
March | 16.13 | 0.30 |
April | 18.73 | 6.67 |
May | 19.94 | 10.10 |
June | 22.81 | 16.46 |
July | 24.42 | 20.57 |
August | 23.83 | 19.17 |
September | 21.65 | 14.69 |
October | 19.35 | 8.64 |
November | 16.63 | 2.84 |
December | 14.28 | -4.1 |
Annual Sum or Average | 18.79 | 7.07 |
Minimum of Months | 12.72 | -8.8 |
Maximum of Months | 24.42 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -8.8 |
February | 21.21 | -2.2 |
March | 21.19 | 0.30 |
April | 21.84 | 6.67 |
May | 22.47 | 10.10 |
June | 23.52 | 16.46 |
July | 23.81 | 20.57 |
August | 23.71 | 19.17 |
September | 23.04 | 14.69 |
October | 22.07 | 8.64 |
November | 21.33 | 2.84 |
December | 21.11 | -4.1 |
Annual Sum or Average | 22.21 | 7.07 |
Minimum of Months | 21.11 | -8.8 |
Maximum of Months | 23.81 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.17 | -8.8 |
February | 13.16 | -2.2 |
March | 14.47 | 0.30 |
April | 17.20 | 6.67 |
May | 18.71 | 10.10 |
June | 21.97 | 16.46 |
July | 23.68 | 20.57 |
August | 22.95 | 19.17 |
September | 20.46 | 14.69 |
October | 17.74 | 8.64 |
November | 14.94 | 2.84 |
December | 12.74 | -4.1 |
Annual Sum or Average | 17.46 | 7.07 |
Minimum of Months | 11.17 | -8.8 |
Maximum of Months | 23.68 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.93 | -2.2 |
March | 18.91 | 0.30 |
April | 19.57 | 6.67 |
May | 20.60 | 10.10 |
June | 22.36 | 16.46 |
July | 23.00 | 20.57 |
August | 22.77 | 19.17 |
September | 21.48 | 14.69 |
October | 19.73 | 8.64 |
November | 19.00 | 2.84 |
December | 18.89 | -4.1 |
Annual Sum or Average | 20.35 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 23.00 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.96 | -2.2 |
March | 18.94 | 0.30 |
April | 19.69 | 6.67 |
May | 20.74 | 10.10 |
June | 22.48 | 16.46 |
July | 23.06 | 20.57 |
August | 22.85 | 19.17 |
September | 21.62 | 14.69 |
October | 19.93 | 8.64 |
November | 19.12 | 2.84 |
December | 18.90 | -4.1 |
Annual Sum or Average | 20.44 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 23.06 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.98 | -2.2 |
March | 18.97 | 0.30 |
April | 19.78 | 6.67 |
May | 20.83 | 10.10 |
June | 22.50 | 16.46 |
July | 23.05 | 20.57 |
August | 22.84 | 19.17 |
September | 21.66 | 14.69 |
October | 20.03 | 8.64 |
November | 19.17 | 2.84 |
December | 18.90 | -4.1 |
Annual Sum or Average | 20.48 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 23.05 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.61 | -8.8 |
February | 20.80 | -2.2 |
March | 20.88 | 0.30 |
April | 21.26 | 6.67 |
May | 21.44 | 10.10 |
June | 21.72 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.60 | 14.69 |
October | 21.35 | 8.64 |
November | 20.96 | 2.84 |
December | 20.66 | -4.1 |
Annual Sum or Average | 21.23 | 7.07 |
Minimum of Months | 20.61 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.93 | -2.2 |
March | 18.91 | 0.30 |
April | 19.61 | 6.67 |
May | 20.64 | 10.10 |
June | 22.38 | 16.46 |
July | 23.03 | 20.57 |
August | 22.78 | 19.17 |
September | 21.52 | 14.69 |
October | 19.86 | 8.64 |
November | 19.07 | 2.84 |
December | 18.89 | -4.1 |
Annual Sum or Average | 20.39 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 23.03 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | -8.8 |
February | 20.87 | -2.2 |
March | 20.93 | 0.30 |
April | 21.27 | 6.67 |
May | 21.40 | 10.10 |
June | 21.70 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.61 | 14.69 |
October | 21.42 | 8.64 |
November | 21.08 | 2.84 |
December | 20.72 | -4.1 |
Annual Sum or Average | 21.26 | 7.07 |
Minimum of Months | 20.64 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | -8.8 |
February | 21.21 | -2.2 |
March | 21.32 | 0.30 |
April | 21.54 | 6.67 |
May | 21.61 | 10.10 |
June | 21.74 | 16.46 |
July | 21.75 | 20.57 |
August | 21.75 | 19.17 |
September | 21.70 | 14.69 |
October | 21.64 | 8.64 |
November | 21.44 | 2.84 |
December | 21.11 | -4.1 |
Annual Sum or Average | 21.48 | 7.07 |
Minimum of Months | 20.92 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | -8.8 |
February | 21.89 | -2.2 |
March | 22.45 | 0.30 |
April | 23.58 | 6.67 |
May | 24.15 | 10.10 |
June | 25.46 | 16.46 |
July | 26.02 | 20.57 |
August | 25.83 | 19.17 |
September | 24.96 | 14.69 |
October | 23.93 | 8.64 |
November | 22.65 | 2.84 |
December | 21.58 | -4.1 |
Annual Sum or Average | 23.64 | 7.07 |
Minimum of Months | 21.07 | -8.8 |
Maximum of Months | 26.02 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.90 | -8.8 |
February | 20.68 | -2.2 |
March | 21.15 | 0.30 |
April | 22.15 | 6.67 |
May | 22.52 | 10.10 |
June | 23.22 | 16.46 |
July | 23.32 | 20.57 |
August | 23.30 | 19.17 |
September | 23.01 | 14.69 |
October | 22.56 | 8.64 |
November | 21.46 | 2.84 |
December | 20.21 | -4.1 |
Annual Sum or Average | 21.96 | 7.07 |
Minimum of Months | 19.90 | -8.8 |
Maximum of Months | 23.32 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | -8.8 |
February | 21.10 | -2.2 |
March | 21.18 | 0.30 |
April | 21.43 | 6.67 |
May | 21.53 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.67 | 14.69 |
October | 21.56 | 8.64 |
November | 21.31 | 2.84 |
December | 20.96 | -4.1 |
Annual Sum or Average | 21.40 | 7.07 |
Minimum of Months | 20.82 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.02 | -8.8 |
February | 19.39 | -2.2 |
March | 19.47 | 0.30 |
April | 20.57 | 6.67 |
May | 21.28 | 10.10 |
June | 22.69 | 16.46 |
July | 23.14 | 20.57 |
August | 23.02 | 19.17 |
September | 22.24 | 14.69 |
October | 21.13 | 8.64 |
November | 19.87 | 2.84 |
December | 19.05 | -4.1 |
Annual Sum or Average | 20.91 | 7.07 |
Minimum of Months | 19.02 | -8.8 |
Maximum of Months | 23.14 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.28 | -8.8 |
February | 16.69 | -2.2 |
March | 17.80 | 0.30 |
April | 19.86 | 6.67 |
May | 20.80 | 10.10 |
June | 23.34 | 16.46 |
July | 24.63 | 20.57 |
August | 24.20 | 19.17 |
September | 22.44 | 14.69 |
October | 20.50 | 8.64 |
November | 18.22 | 2.84 |
December | 16.24 | -4.1 |
Annual Sum or Average | 20.02 | 7.07 |
Minimum of Months | 15.28 | -8.8 |
Maximum of Months | 24.63 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.86 | -8.8 |
February | 13.00 | -2.2 |
March | 14.79 | 0.30 |
April | 17.98 | 6.67 |
May | 19.37 | 10.10 |
June | 23.13 | 16.46 |
July | 25.16 | 20.57 |
August | 24.42 | 19.17 |
September | 21.64 | 14.69 |
October | 18.74 | 8.64 |
November | 15.37 | 2.84 |
December | 12.45 | -4.1 |
Annual Sum or Average | 18.10 | 7.07 |
Minimum of Months | 10.86 | -8.8 |
Maximum of Months | 25.16 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.17 | -8.8 |
February | 13.42 | -2.2 |
March | 14.85 | 0.30 |
April | 17.84 | 6.67 |
May | 19.45 | 10.10 |
June | 22.77 | 16.46 |
July | 24.62 | 20.57 |
August | 23.88 | 19.17 |
September | 21.25 | 14.69 |
October | 18.38 | 8.64 |
November | 15.32 | 2.84 |
December | 12.68 | -4.1 |
Annual Sum or Average | 17.99 | 7.07 |
Minimum of Months | 11.17 | -8.8 |
Maximum of Months | 24.62 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -8.8 |
February | 21.20 | -2.2 |
March | 21.22 | 0.30 |
April | 21.70 | 6.67 |
May | 22.23 | 10.10 |
June | 23.10 | 16.46 |
July | 23.56 | 20.57 |
August | 23.38 | 19.17 |
September | 22.67 | 14.69 |
October | 21.70 | 8.64 |
November | 21.21 | 2.84 |
December | 21.11 | -4.1 |
Annual Sum or Average | 22.02 | 7.07 |
Minimum of Months | 21.11 | -8.8 |
Maximum of Months | 23.56 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.86 | -8.8 |
February | 12.16 | -2.2 |
March | 13.56 | 0.30 |
April | 16.58 | 6.67 |
May | 18.41 | 10.10 |
June | 21.95 | 16.46 |
July | 23.86 | 20.57 |
August | 22.98 | 19.17 |
September | 20.14 | 14.69 |
October | 16.99 | 8.64 |
November | 13.98 | 2.84 |
December | 11.53 | -4.1 |
Annual Sum or Average | 16.86 | 7.07 |
Minimum of Months | 9.86 | -8.8 |
Maximum of Months | 23.86 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -8.8 |
February | 20.58 | -2.2 |
March | 20.60 | 0.30 |
April | 21.03 | 6.67 |
May | 21.33 | 10.10 |
June | 21.68 | 16.46 |
July | 21.75 | 20.57 |
August | 21.71 | 19.17 |
September | 21.47 | 14.69 |
October | 21.03 | 8.64 |
November | 20.63 | 2.84 |
December | 20.48 | -4.1 |
Annual Sum or Average | 21.07 | 7.07 |
Minimum of Months | 20.47 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.96 | -2.2 |
March | 18.98 | 0.30 |
April | 19.64 | 6.67 |
May | 20.58 | 10.10 |
June | 22.08 | 16.46 |
July | 22.75 | 20.57 |
August | 22.47 | 19.17 |
September | 21.27 | 14.69 |
October | 19.64 | 8.64 |
November | 18.99 | 2.84 |
December | 18.89 | -4.1 |
Annual Sum or Average | 20.27 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 22.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.97 | -2.2 |
March | 19.00 | 0.30 |
April | 19.68 | 6.67 |
May | 20.62 | 10.10 |
June | 22.09 | 16.46 |
July | 22.74 | 20.57 |
August | 22.45 | 19.17 |
September | 21.28 | 14.69 |
October | 19.68 | 8.64 |
November | 19.01 | 2.84 |
December | 18.89 | -4.1 |
Annual Sum or Average | 20.28 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 22.74 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -8.8 |
February | 20.76 | -2.2 |
March | 20.84 | 0.30 |
April | 21.26 | 6.67 |
May | 21.47 | 10.10 |
June | 21.72 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.59 | 14.69 |
October | 21.31 | 8.64 |
November | 20.88 | 2.84 |
December | 20.58 | -4.1 |
Annual Sum or Average | 21.20 | 7.07 |
Minimum of Months | 20.54 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -8.8 |
February | 18.94 | -2.2 |
March | 18.95 | 0.30 |
April | 19.60 | 6.67 |
May | 20.55 | 10.10 |
June | 22.07 | 16.46 |
July | 22.78 | 20.57 |
August | 22.49 | 19.17 |
September | 21.26 | 14.69 |
October | 19.62 | 8.64 |
November | 18.98 | 2.84 |
December | 18.89 | -4.1 |
Annual Sum or Average | 20.26 | 7.07 |
Minimum of Months | 18.89 | -8.8 |
Maximum of Months | 22.78 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.94 | -8.8 |
February | 19.23 | -2.2 |
March | 19.33 | 0.30 |
April | 20.15 | 6.67 |
May | 20.94 | 10.10 |
June | 22.24 | 16.46 |
July | 22.85 | 20.57 |
August | 22.64 | 19.17 |
September | 21.70 | 14.69 |
October | 20.40 | 8.64 |
November | 19.45 | 2.84 |
December | 18.96 | -4.1 |
Annual Sum or Average | 20.58 | 7.07 |
Minimum of Months | 18.94 | -8.8 |
Maximum of Months | 22.85 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | -8.8 |
February | 21.10 | -2.2 |
March | 21.19 | 0.30 |
April | 21.42 | 6.67 |
May | 21.55 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.66 | 14.69 |
October | 21.54 | 8.64 |
November | 21.31 | 2.84 |
December | 20.91 | -4.1 |
Annual Sum or Average | 21.39 | 7.07 |
Minimum of Months | 20.78 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.49 | -8.8 |
February | 19.53 | -2.2 |
March | 20.13 | 0.30 |
April | 21.43 | 6.67 |
May | 22.23 | 10.10 |
June | 23.75 | 16.46 |
July | 24.48 | 20.57 |
August | 24.16 | 19.17 |
September | 23.01 | 14.69 |
October | 21.64 | 8.64 |
November | 20.25 | 2.84 |
December | 19.05 | -4.1 |
Annual Sum or Average | 21.52 | 7.07 |
Minimum of Months | 18.49 | -8.8 |
Maximum of Months | 24.48 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | -8.8 |
February | 21.05 | -2.2 |
March | 21.14 | 0.30 |
April | 21.40 | 6.67 |
May | 21.54 | 10.10 |
June | 21.73 | 16.46 |
July | 21.75 | 20.57 |
August | 21.74 | 19.17 |
September | 21.66 | 14.69 |
October | 21.53 | 8.64 |
November | 21.26 | 2.84 |
December | 20.85 | -4.1 |
Annual Sum or Average | 21.37 | 7.07 |
Minimum of Months | 20.74 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.76 | -8.8 |
February | 21.08 | -2.2 |
March | 21.16 | 0.30 |
April | 21.40 | 6.67 |
May | 21.54 | 10.10 |
June | 21.72 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.65 | 14.69 |
October | 21.53 | 8.64 |
November | 21.28 | 2.84 |
December | 20.87 | -4.1 |
Annual Sum or Average | 21.37 | 7.07 |
Minimum of Months | 20.76 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.60 | -8.8 |
February | 20.85 | -2.2 |
March | 20.92 | 0.30 |
April | 21.25 | 6.67 |
May | 21.44 | 10.10 |
June | 21.71 | 16.46 |
July | 21.75 | 20.57 |
August | 21.73 | 19.17 |
September | 21.60 | 14.69 |
October | 21.39 | 8.64 |
November | 21.05 | 2.84 |
December | 20.64 | -4.1 |
Annual Sum or Average | 21.25 | 7.07 |
Minimum of Months | 20.60 | -8.8 |
Maximum of Months | 21.75 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.40 | -8.8 |
February | 16.00 | -2.2 |
March | 17.19 | 0.30 |
April | 19.47 | 6.67 |
May | 20.65 | 10.10 |
June | 23.30 | 16.46 |
July | 24.68 | 20.57 |
August | 24.12 | 19.17 |
September | 22.13 | 14.69 |
October | 19.92 | 8.64 |
November | 17.51 | 2.84 |
December | 15.34 | -4.1 |
Annual Sum or Average | 19.58 | 7.07 |
Minimum of Months | 14.40 | -8.8 |
Maximum of Months | 24.68 | 20.57 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:37
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.10 | -8.8 |
February | 12.06 | -2.2 |
March | 13.90 | 0.30 |
April | 17.39 | 6.67 |
May | 19.11 | 10.10 |
June | 23.12 | 16.46 |
July | 25.29 | 20.57 |
August | 24.40 | 19.17 |
September | 21.29 | 14.69 |
October | 18.01 | 8.64 |
November | 14.42 | 2.84 |
December | 11.28 | -4.1 |
Annual Sum or Average | 17.56 | 7.07 |
Minimum of Months | 10.10 | -8.8 |
Maximum of Months | 25.29 | 20.57 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.213598E+12 | 177156.890 | 29-JAN-07:15 | 15177.258 | 39465.561 | 8969.079 | 109291.096 | 57.783 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.157755E+12 | 158996.856 | 01-FEB-07:15 | 15177.258 | 39465.561 | 8938.977 | 91104.096 | 114.850 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.155133E+12 | 144461.520 | 06-MAR-07:15 | 15177.258 | 39465.561 | 8936.527 | 80759.752 | 114.308 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.131209E+12 | 100168.156 | 29-APR-06:15 | 13242.271 | 34010.661 | 8914.910 | 43799.667 | 192.534 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.136261E+12 | 95039.572 | 08-MAY-06:15 | 15102.841 | 39465.561 | 8914.910 | 31182.522 | 365.625 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.137238E+12 | 89340.696 | 23-JUN-07:00 | 17789.888 | 43276.576 | 9355.274 | 0.000 | 18910.845 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.151182E+12 | 90182.066 | 14-JUL-07:00 | 17641.054 | 43276.576 | 9355.274 | 0.000 | 19901.050 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.147233E+12 | 86948.785 | 11-AUG-07:00 | 17641.054 | 43276.576 | 9355.274 | 0.000 | 16667.768 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.136753E+12 | 86351.780 | 02-SEP-07:00 | 17789.888 | 43276.576 | 9355.274 | 0.000 | 15921.928 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.135557E+12 | 104434.810 | 10-OCT-06:15 | 15177.258 | 39465.561 | 8914.910 | 36393.193 | 287.775 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.147919E+12 | 134882.426 | 27-NOV-07:15 | 15177.258 | 39465.561 | 8928.699 | 66970.242 | 144.552 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.184846E+12 | 174062.673 | 31-DEC-07:15 | 15177.258 | 39465.561 | 8960.435 | 106204.656 | 58.650 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.183468E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.131209E+12 | 86351.780 | 13242.271 | 34010.661 | 8914.910 | 0.000 | 57.783 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.213598E+12 | 177156.890 | 17789.888 | 43276.576 | 9355.274 | 109291.096 | 19901.050 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:37
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.131433E+12 | 126311.822 | 27-JAN-09:15 | 23305.969 | 40096.028 | 0.000 | 62909.825 | 62909.825 | 62909.825 | 23305.969 |
February | 0.108686E+12 | 121458.213 | 04-FEB-11:15 | 20125.864 | 40096.028 | 0.000 | 61236.321 | 61236.321 | 61236.321 | 20125.864 |
March | 0.113937E+12 | 120169.543 | 04-MAR-11:00 | 19030.804 | 40096.028 | 0.000 | 61042.711 | 61042.711 | 61042.711 | 19030.804 |
April | 0.997295E+11 | 105264.873 | 27-APR-09:00 | 6603.768 | 40096.028 | 0.000 | 58565.077 | 58565.077 | 58565.077 | 6603.768 |
May | 0.977952E+11 | 101730.934 | 08-MAY-09:45 | 7300.970 | 40096.028 | 0.000 | 54333.935 | 54333.935 | 54333.935 | 7300.970 |
June | 0.882355E+11 | 97795.269 | 03-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 57699.241 | 57699.241 | 57699.241 | 0.000 |
July | 0.879382E+11 | 94397.474 | 01-JUL-08:45 | 0.000 | 40096.028 | 0.000 | 54301.446 | 54301.446 | 54301.446 | 0.000 |
August | 0.868586E+11 | 92601.258 | 26-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 52505.230 | 52505.230 | 52505.230 | 0.000 |
September | 0.857685E+11 | 93662.864 | 22-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 53566.836 | 53566.836 | 53566.836 | 0.000 |
October | 0.934857E+11 | 98663.801 | 05-OCT-09:15 | 5263.130 | 40096.028 | 0.000 | 53304.643 | 53304.643 | 53304.643 | 5263.130 |
November | 0.100928E+12 | 109604.686 | 26-NOV-10:15 | 15285.484 | 40096.028 | 0.000 | 54223.173 | 54223.173 | 54223.173 | 15285.484 |
December | 0.119298E+12 | 121934.012 | 31-DEC-10:30 | 22003.899 | 40096.028 | 0.000 | 59834.085 | 59834.085 | 59834.085 | 22003.899 |
Annual Sum or Average | 0.121409E+13 | 0.000 | ||||||||
Minimum of Months | 0.857685E+11 | 92601.258 | 0.000 | 40096.028 | 0.000 | 52505.230 | 52505.230 | 52505.230 | 0.000 | |
Maximum of Months | 0.131433E+12 | 126311.822 | 23305.969 | 40096.028 | 0.000 | 62909.825 | 62909.825 | 62909.825 | 23305.969 |