Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745
Simulation Timestamp: 2018-10-19 10:15:32
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2786.88 | 694.36 | 748.14 |
Net Site Energy | 2786.88 | 694.36 | 748.14 |
Total Source Energy | 6876.30 | 1713.26 | 1845.94 |
Net Source Energy | 6876.30 | 1713.26 | 1845.94 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 12.29 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 469.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 293.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 508.31 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1850.85 | 936.04 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 12.29 | 6.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 469.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 418.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 293.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 508.31 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 129.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 208.25 | 138.13 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 496.86 | 251.28 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 120.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 193.28 | 128.20 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 461.15 | 233.22 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 1850.85 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 1850.85 | 100.00 |
Total On-Site and Utility Electric Sources | 1850.85 | 100.00 |
Total Electricity End Uses | 1850.85 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 66.25 |
Time Setpoint Not Met During Occupied Cooling | 4958.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4552.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Weather File | Tucson-Davis Monthan AFB AZ USA TMY3 WMO#=722745 |
Latitude [deg] | 32.17 |
Longitude [deg] | -110.9 |
Elevation [m] | 809.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00 | 0.50 | Wetbulb [C] | 2.10 | 140.00 |
TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 13.30 | 18.50 | Wetbulb [C] | 4.80 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.704 | 0.787 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.72_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 4.600 | 0.293 | 0.130 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 4.600 | 0.293 | 0.130 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.72_SHGC_0.25 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 4.600 | 0.293 | 0.130 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 4.600 | 0.293 | 0.130 | ||||||||||||
North Total or Average | 96.82 | 4.600 | 0.293 | 0.130 | ||||||||||||
Non-North Total or Average | 87.38 | 4.600 | 0.293 | 0.130 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7839.69 | 5875.65 | 1964.05 | 0.75 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 20694.12 | 14769.21 | 5924.90 | 0.71 | 3.80 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10302.28 | 7065.28 | 3237.00 | 0.69 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 15502.00 | 11541.79 | 3960.21 | 0.74 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7521.2 | 3.24 | 11.05 | 11.71 | 10.98 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19947.5 | 3.22 | 10.99 | 11.66 | 11.06 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9967.1 | 3.36 | 11.46 | 12.15 | 11.60 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 14881.9 | 3.25 | 11.08 | 11.74 | 11.02 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.78 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 20635.54 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 743.50 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 743.50 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 776.68 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 761.56 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.71 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.78 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 2108.60 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 743.50 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 2356.99 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 743.50 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.71 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.78 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 2108.60 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 743.50 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 2356.99 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 761.21 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 743.45 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.71 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.78 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 2108.60 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 896.69 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 2356.99 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 2973.99 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 968.96 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 925.59 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 765.17 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 2973.78 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 897.52 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 291.71 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 3061.39 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 12831.77 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 6871.32 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 5209.88 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.41 | 459.52 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.96 | 1064.23 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.43 | 483.12 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.80 | 884.20 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 8821.38 | 10585.66 | 0.801 | 0.961 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 40.60 | 0.00558 |
RESTROOMFLR1 | 561.84 | 674.21 | 0.051 | 0.061 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 39.20 | 0.00558 |
MEETINGROOMFLR1 | 3955.49 | 4746.58 | 0.359 | 0.431 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM101 | 755.55 | 906.66 | 0.095 | 0.114 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 40.00 | 0.00558 |
GUESTROOM102 | 645.21 | 774.26 | 0.081 | 0.098 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 40.00 | 0.00558 |
GUESTROOM103 | 1325.91 | 1591.09 | 0.167 | 0.201 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 37.11 | 0.00558 |
GUESTROOM104 | 1428.72 | 1714.47 | 0.180 | 0.216 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40 | 0.00558 |
GUESTROOM105 | 1690.59 | 2028.71 | 0.213 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
EMPLOYEELOUNGEFLR1 | 5451.82 | 6542.18 | 0.495 | 0.594 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
EXERCISECENTERFLR1 | 1315.19 | 1578.23 | 0.119 | 0.143 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.94 | 0.00558 |
FRONTOFFICEFLR1 | 3767.84 | 4521.41 | 0.342 | 0.410 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM201 | 1028.38 | 1234.05 | 0.130 | 0.156 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 40.80 | 0.00558 |
GUESTROOM202_205 | 4581.75 | 5498.10 | 0.578 | 0.694 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM206_208 | 3723.04 | 4467.65 | 0.470 | 0.564 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 40.40 | 0.00558 |
GUESTROOM209_212 | 4370.93 | 5245.12 | 0.551 | 0.662 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM213 | 1292.21 | 1550.66 | 0.163 | 0.196 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 37.61 | 0.00558 |
GUESTROOM214 | 1448.76 | 1738.51 | 0.183 | 0.219 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM215_218 | 9703.85 | 11644.62 | 1.224 | 1.469 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM219 | 5426.19 | 6511.43 | 0.685 | 0.821 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM220_223 | 4859.58 | 5831.50 | 0.613 | 0.736 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80 | 0.00558 |
GUESTROOM224 | 1421.35 | 1705.62 | 0.179 | 0.215 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM301 | 854.39 | 1025.26 | 0.108 | 0.129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM302_305 | 1985.31 | 2382.37 | 0.250 | 0.301 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM306_308 | 1746.23 | 2095.48 | 0.220 | 0.264 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM309_312 | 4320.10 | 5184.12 | 0.545 | 0.654 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM313 | 789.97 | 947.96 | 0.100 | 0.120 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 37.61 | 0.00558 |
GUESTROOM314 | 1368.51 | 1642.21 | 0.173 | 0.207 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM315_318 | 5234.77 | 6281.72 | 0.660 | 0.793 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM319 | 1175.82 | 1410.99 | 0.148 | 0.178 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM320_323 | 4642.30 | 5570.77 | 0.586 | 0.703 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM324 | 854.29 | 1025.14 | 0.108 | 0.129 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM401 | 1684.80 | 2021.77 | 0.213 | 0.255 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 40.80 | 0.00558 |
GUESTROOM402_405 | 2702.30 | 3242.76 | 0.341 | 0.409 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM406_408 | 2334.25 | 2801.10 | 0.294 | 0.353 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM409_412 | 5344.24 | 6413.09 | 0.674 | 0.809 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM413 | 1044.05 | 1252.87 | 0.132 | 0.158 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
GUESTROOM414 | 1140.67 | 1368.81 | 0.144 | 0.173 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 40.80 | 0.00558 |
GUESTROOM415_418 | 5795.43 | 6954.51 | 0.731 | 0.877 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80 | 0.00558 |
GUESTROOM419 | 1600.17 | 1920.20 | 0.202 | 0.242 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
GUESTROOM420_423 | 5765.82 | 6918.98 | 0.727 | 0.873 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 40.80 | 0.00558 |
GUESTROOM424 | 1671.41 | 2005.69 | 0.211 | 0.253 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 40.80 | 0.00558 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
CORRIDORFLR1 | 22300.49 | 26760.59 | 2.022 | 2.427 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 37.61 | 0.00558 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
CORRIDORFLR2 | 2923.03 | 3507.63 | 0.265 | 0.318 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:45:00 | 39.20 | 0.00558 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
CORRIDORFLR3 | 1522.96 | 1827.55 | 0.138 | 0.166 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 38.94 | 0.00558 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 | |
CORRIDORFLR4 | 2347.62 | 2817.15 | 0.213 | 0.256 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 40.20 | 0.00558 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN CLG .4% CONDNS DB=>MWB | 40.80 | 0.00558 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 1486.74 | 1784.09 | 0.046 | 0.236 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:15:00 | 0.50 | 0.00432 |
RESTROOMFLR1 | 65.57 | 78.69 | 0.002 | 0.002 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 0.50 | 0.00432 |
MEETINGROOMFLR1 | 489.52 | 587.43 | 0.015 | 0.126 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:00:00 | 0.50 | 0.00432 |
GUESTROOM101 | 201.87 | 242.24 | 0.006 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 0.50 | 0.00432 |
GUESTROOM102 | 241.94 | 290.32 | 0.008 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 0.50 | 0.00432 |
GUESTROOM103 | 389.25 | 467.10 | 0.012 | 0.015 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 0.50 | 0.00432 |
GUESTROOM104 | 376.67 | 452.00 | 0.012 | 0.014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 07:45:00 | 0.50 | 0.00432 |
GUESTROOM105 | 244.44 | 293.32 | 0.008 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | 0.50 | 0.00432 |
EMPLOYEELOUNGEFLR1 | 219.95 | 263.94 | 0.007 | 0.051 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50 | 0.00432 |
EXERCISECENTERFLR1 | 141.73 | 170.08 | 0.004 | 0.043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:00:00 | 0.50 | 0.00432 |
FRONTOFFICEFLR1 | 874.56 | 1049.48 | 0.027 | 0.056 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 0.50 | 0.00432 |
GUESTROOM201 | 313.97 | 376.76 | 0.010 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 0.50 | 0.00432 |
GUESTROOM202_205 | 727.92 | 873.51 | 0.023 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:45:00 | 0.50 | 0.00432 |
GUESTROOM206_208 | 574.93 | 689.92 | 0.018 | 0.043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 0.50 | 0.00432 |
GUESTROOM209_212 | 652.68 | 783.21 | 0.020 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 0.50 | 0.00432 |
GUESTROOM213 | 338.58 | 406.30 | 0.011 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 0.50 | 0.00432 |
GUESTROOM214 | 309.25 | 371.10 | 0.010 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | 0.50 | 0.00432 |
GUESTROOM215_218 | 648.64 | 778.37 | 0.020 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 0.50 | 0.00432 |
GUESTROOM219 | 135.05 | 162.06 | 0.004 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:15:00 | 0.50 | 0.00432 |
GUESTROOM220_223 | 628.09 | 753.70 | 0.020 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:15:00 | 0.50 | 0.00432 |
GUESTROOM224 | 271.73 | 326.07 | 0.008 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:30:00 | 0.50 | 0.00432 |
GUESTROOM301 | 338.34 | 406.01 | 0.011 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 17:45:00 | 0.50 | 0.00432 |
GUESTROOM302_305 | 801.97 | 962.36 | 0.025 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 17:30:00 | 0.50 | 0.00432 |
GUESTROOM306_308 | 696.80 | 836.16 | 0.022 | 0.043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 14:15:00 | 0.50 | 0.00432 |
GUESTROOM309_312 | 792.76 | 951.31 | 0.025 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:15:00 | 0.50 | 0.00432 |
GUESTROOM313 | 376.36 | 451.63 | 0.012 | 0.014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | 0.50 | 0.00432 |
GUESTROOM314 | 341.47 | 409.76 | 0.011 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 15:45:00 | 0.50 | 0.00432 |
GUESTROOM315_318 | 790.28 | 948.33 | 0.025 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 0.50 | 0.00432 |
GUESTROOM319 | 203.42 | 244.10 | 0.006 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 13:15:00 | 0.50 | 0.00432 |
GUESTROOM320_323 | 760.46 | 912.56 | 0.024 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | 0.50 | 0.00432 |
GUESTROOM324 | 314.64 | 377.57 | 0.010 | 0.013 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 0.50 | 0.00432 |
GUESTROOM401 | 489.26 | 587.11 | 0.015 | 0.018 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:45:00 | 0.50 | 0.00432 |
GUESTROOM402_405 | 1331.83 | 1598.19 | 0.041 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 22:15:00 | 0.50 | 0.00432 |
GUESTROOM406_408 | 1141.33 | 1369.60 | 0.035 | 0.043 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 0.50 | 0.00432 |
GUESTROOM409_412 | 1334.78 | 1601.73 | 0.041 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 20:00:00 | 0.50 | 0.00432 |
GUESTROOM413 | 549.48 | 659.38 | 0.017 | 0.020 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50 | 0.00432 |
GUESTROOM414 | 513.36 | 616.03 | 0.016 | 0.019 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 21:15:00 | 0.50 | 0.00432 |
GUESTROOM415_418 | 1334.01 | 1600.81 | 0.041 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | 0.50 | 0.00432 |
GUESTROOM419 | 379.68 | 455.61 | 0.012 | 0.014 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | 0.50 | 0.00432 |
GUESTROOM420_423 | 1302.62 | 1563.14 | 0.040 | 0.054 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 19:15:00 | 0.50 | 0.00432 |
GUESTROOM424 | 489.96 | 587.96 | 0.015 | 0.018 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50 | 0.00432 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
CORRIDORFLR1 | 16313.46 | 19576.15 | 0.506 | 0.607 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 0.50 | 0.00432 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
CORRIDORFLR2 | 181.55 | 217.86 | 0.006 | 0.038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 09:45:00 | 0.50 | 0.00432 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
CORRIDORFLR3 | 320.40 | 384.48 | 0.010 | 0.038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 13:30:00 | 0.50 | 0.00432 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 | |
CORRIDORFLR4 | 992.81 | 1191.37 | 0.031 | 0.038 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 0.50 | 0.00432 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | TUCSON-DAVIS-MONTHAN.AFB_AZ_USA ANN HTG 99.6% CONDNS DB | 0.50 | 0.00432 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.41 | 0.41 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.96 | 0.96 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.43 | 0.43 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.80 | 0.80 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.96 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 1673.25 | 5778.00 | 346.25 |
RESTROOMFLR1 | 595.25 | 6376.00 | 31.00 |
MEETINGROOMFLR1 | 1114.75 | 2434.25 | 79.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 56.50 | 8742.75 | 56.50 |
GUESTROOM104 | 20.50 | 8560.75 | 20.50 |
GUESTROOM105 | 2.50 | 8290.50 | 2.50 |
EMPLOYEELOUNGEFLR1 | 2807.00 | 2079.50 | 119.00 |
EXERCISECENTERFLR1 | 1612.25 | 1441.25 | 9.25 |
FRONTOFFICEFLR1 | 1248.75 | 4854.00 | 56.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 16.50 | 8383.00 | 16.50 |
GUESTROOM206_208 | 11.00 | 8377.50 | 11.00 |
GUESTROOM209_212 | 16.75 | 8444.00 | 16.75 |
GUESTROOM213 | 31.75 | 8639.00 | 31.75 |
GUESTROOM214 | 13.50 | 8385.50 | 13.50 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 5491.25 | 3758.75 | 1235.50 |
GUESTROOM220_223 | 12.50 | 8320.25 | 12.50 |
GUESTROOM224 | 10.25 | 8335.50 | 10.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 26.25 | 8642.75 | 26.25 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 15.75 | 8398.50 | 15.75 |
GUESTROOM315_318 | 10.50 | 8191.00 | 6.75 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 19.75 | 8468.25 | 19.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 733.75 | 7774.25 | 450.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 361.00 | 7787.75 | 92.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 462.50 | 7107.00 | 32.75 |
GUESTROOM419 | 277.50 | 7445.50 | 20.75 |
GUESTROOM420_423 | 445.75 | 7171.00 | 36.00 |
GUESTROOM424 | 342.25 | 7618.00 | 58.00 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 6729.75 | 8759.75 | 4552.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
RESTROOMFLR1 | 0.00 | 1356.00 | 0.00 | 1356.00 |
MEETINGROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 0.00 | 50.25 | 0.00 | 50.25 |
GUESTROOM104 | 0.00 | 68.25 | 0.00 | 68.25 |
GUESTROOM105 | 0.00 | 83.25 | 0.00 | 83.25 |
EMPLOYEELOUNGEFLR1 | 108.00 | 1044.75 | 66.25 | 550.75 |
EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 0.00 | 34.25 | 0.00 | 34.25 |
GUESTROOM206_208 | 0.00 | 43.75 | 0.00 | 43.75 |
GUESTROOM209_212 | 0.00 | 33.00 | 0.00 | 33.00 |
GUESTROOM213 | 0.00 | 35.25 | 0.00 | 35.25 |
GUESTROOM214 | 0.00 | 45.00 | 0.00 | 45.00 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 4096.50 | 0.00 | 4096.50 |
GUESTROOM220_223 | 0.00 | 40.25 | 0.00 | 40.25 |
GUESTROOM224 | 0.00 | 45.25 | 0.00 | 45.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 0.00 | 30.00 | 0.00 | 30.00 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 0.00 | 44.50 | 0.00 | 44.50 |
GUESTROOM315_318 | 0.00 | 43.50 | 0.00 | 43.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 0.00 | 37.00 | 0.00 | 37.00 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 0.00 | 48.25 | 0.00 | 48.25 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 0.00 | 43.75 | 0.00 | 43.75 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 0.00 | 51.00 | 0.00 | 51.00 |
GUESTROOM419 | 0.00 | 57.25 | 0.00 | 57.25 |
GUESTROOM420_423 | 0.00 | 50.00 | 0.00 | 50.00 |
GUESTROOM424 | 0.00 | 54.25 | 0.00 | 54.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 5682.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 1184.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 49.75 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.25 | 912.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 108.25 | 6784.00 | 66.25 | 4958.75 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:32
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.006114 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.006114 |
SAC_FRONTOFFICE SUPPLY FAN | 0.410243 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.961231 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.798624 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 291.78 |
CORRIDORFLR1 PTAC HEATING COIL | 20635.54 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 743.50 |
102 PTAC HEATING COIL | 743.50 |
103 PTAC HEATING COIL | 776.68 |
104 PTAC HEATING COIL | 761.56 |
105 PTAC HEATING COIL | 743.45 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 291.71 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 291.78 |
CORRIDORFLR2 PTAC HEATING COIL | 2108.60 |
201 PTAC HEATING COIL | 743.50 |
202_205 PTAC HEATING COIL | 2973.99 |
206_208 PTAC HEATING COIL | 2356.99 |
209_212 PTAC HEATING COIL | 2973.99 |
213 PTAC HEATING COIL | 743.50 |
214 PTAC HEATING COIL | 743.45 |
215_218 PTAC HEATING COIL | 2973.78 |
219 PTAC HEATING COIL | 743.45 |
220_223 PTAC HEATING COIL | 2973.78 |
224 PTAC HEATING COIL | 743.45 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 291.71 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 291.78 |
CORRIDORFLR3 PTAC HEATING COIL | 2108.60 |
301 PTAC HEATING COIL | 743.50 |
302_305 PTAC HEATING COIL | 2973.99 |
306_308 PTAC HEATING COIL | 2356.99 |
309_312 PTAC HEATING COIL | 2973.99 |
313 PTAC HEATING COIL | 761.21 |
314 PTAC HEATING COIL | 743.45 |
315_318 PTAC HEATING COIL | 2973.78 |
319 PTAC HEATING COIL | 743.45 |
320_323 PTAC HEATING COIL | 2973.78 |
324 PTAC HEATING COIL | 743.45 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 291.71 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 291.78 |
CORRIDORFLR4 PTAC HEATING COIL | 2108.60 |
401 PTAC HEATING COIL | 896.69 |
402_405 PTAC HEATING COIL | 2973.99 |
406_408 PTAC HEATING COIL | 2356.99 |
409_412 PTAC HEATING COIL | 2973.99 |
413 PTAC HEATING COIL | 968.96 |
414 PTAC HEATING COIL | 925.59 |
415_418 PTAC HEATING COIL | 2973.78 |
419 PTAC HEATING COIL | 765.17 |
420_423 PTAC HEATING COIL | 2973.78 |
424 PTAC HEATING COIL | 897.52 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 291.71 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.749474 | 0.410243 | 7839.69 |
SAC_FRONTLOUNGE COOLING COIL | 0.713691 | 0.961231 | 20694.12 |
SAC_MEETINGROOM COOLING COIL | 0.685798 | 0.431318 | 10302.28 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.744536 | 0.798624 | 15502.00 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.961231 |
RESTROOMFLR1 DIRECT AIR | 0.061163 |
MEETINGROOMFLR1 DIRECT AIR | 0.431318 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.594207 |
EXERCISECENTERFLR1 DIRECT AIR | 0.143254 |
FRONTOFFICEFLR1 DIRECT AIR | 0.410243 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.410243 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.961231 |
SAC_MEETINGROOM MAIN BRANCH | 0.431318 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.798624 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.410243 |
SAC_FRONTLOUNGE | 0.961231 |
SAC_MEETINGROOM | 0.431318 |
SAC_EXC_EMPLGE_RESTRM | 0.798624 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.410243 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.961231 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.431318 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.798624 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.410243 | 0.410243 | 0.410243 | 0.410243 | 3061.39 | 7839.69 | 1.00 |
SAC_FRONTLOUNGE | 0.961231 | 0.961231 | 0.961231 | 0.961231 | 12831.77 | 20694.12 | 1.00 |
SAC_MEETINGROOM | 0.431318 | 0.431318 | 0.431318 | 0.431318 | 6871.32 | 10302.28 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.798624 | 0.798624 | 0.798624 | 0.798624 | 5209.88 | 15502.00 | 0.179376 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 3061.39 |
SAC_FRONTLOUNGE HEATING COIL | 12831.77 |
SAC_MEETINGROOM HEATING COIL | 6871.32 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 5209.88 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.431318 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.21 | 14.83 |
February | 21.44 | 12.72 |
March | 22.00 | 15.42 |
April | 24.62 | 23.31 |
May | 25.38 | 26.31 |
June | 26.79 | 31.20 |
July | 26.46 | 30.42 |
August | 26.23 | 29.82 |
September | 25.76 | 27.75 |
October | 23.91 | 20.87 |
November | 22.40 | 15.43 |
December | 21.44 | 11.86 |
Annual Sum or Average | 24.06 | 21.71 |
Minimum of Months | 21.44 | 11.86 |
Maximum of Months | 26.79 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.26 | 14.83 |
February | 23.80 | 12.72 |
March | 24.30 | 15.42 |
April | 25.90 | 23.31 |
May | 26.58 | 26.31 |
June | 27.72 | 31.20 |
July | 27.62 | 30.42 |
August | 27.44 | 29.82 |
September | 26.98 | 27.75 |
October | 25.44 | 20.87 |
November | 24.38 | 15.43 |
December | 23.80 | 11.86 |
Annual Sum or Average | 25.69 | 21.71 |
Minimum of Months | 23.80 | 11.86 |
Maximum of Months | 27.72 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 14.83 |
February | 20.59 | 12.72 |
March | 21.31 | 15.42 |
April | 23.92 | 23.31 |
May | 24.88 | 26.31 |
June | 26.32 | 31.20 |
July | 25.94 | 30.42 |
August | 25.60 | 29.82 |
September | 25.04 | 27.75 |
October | 23.03 | 20.87 |
November | 21.41 | 15.43 |
December | 20.29 | 11.86 |
Annual Sum or Average | 23.30 | 21.71 |
Minimum of Months | 20.29 | 11.86 |
Maximum of Months | 26.32 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.53 | 14.83 |
February | 22.08 | 12.72 |
March | 22.63 | 15.42 |
April | 23.53 | 23.31 |
May | 23.77 | 26.31 |
June | 23.89 | 31.20 |
July | 23.89 | 30.42 |
August | 23.89 | 29.82 |
September | 23.87 | 27.75 |
October | 23.27 | 20.87 |
November | 22.59 | 15.43 |
December | 22.10 | 11.86 |
Annual Sum or Average | 23.18 | 21.71 |
Minimum of Months | 22.08 | 11.86 |
Maximum of Months | 23.89 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 14.83 |
February | 22.58 | 12.72 |
March | 22.81 | 15.42 |
April | 23.41 | 23.31 |
May | 23.67 | 26.31 |
June | 23.93 | 31.20 |
July | 23.88 | 30.42 |
August | 23.79 | 29.82 |
September | 23.65 | 27.75 |
October | 23.19 | 20.87 |
November | 22.74 | 15.43 |
December | 22.31 | 11.86 |
Annual Sum or Average | 23.21 | 21.71 |
Minimum of Months | 22.31 | 11.86 |
Maximum of Months | 23.93 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.14 | 14.83 |
February | 22.97 | 12.72 |
March | 23.22 | 15.42 |
April | 23.77 | 23.31 |
May | 23.88 | 26.31 |
June | 23.89 | 31.20 |
July | 23.89 | 30.42 |
August | 23.89 | 29.82 |
September | 23.89 | 27.75 |
October | 23.71 | 20.87 |
November | 23.29 | 15.43 |
December | 22.79 | 11.86 |
Annual Sum or Average | 23.53 | 21.71 |
Minimum of Months | 22.79 | 11.86 |
Maximum of Months | 23.89 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.53 | 14.83 |
February | 25.37 | 12.72 |
March | 25.77 | 15.42 |
April | 28.45 | 23.31 |
May | 31.45 | 26.31 |
June | 33.95 | 31.20 |
July | 34.94 | 30.42 |
August | 34.49 | 29.82 |
September | 32.89 | 27.75 |
October | 29.86 | 20.87 |
November | 26.81 | 15.43 |
December | 25.25 | 11.86 |
Annual Sum or Average | 29.59 | 21.71 |
Minimum of Months | 25.25 | 11.86 |
Maximum of Months | 34.94 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.02 | 14.83 |
February | 21.67 | 12.72 |
March | 22.20 | 15.42 |
April | 23.21 | 23.31 |
May | 23.33 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 23.09 | 20.87 |
November | 22.36 | 15.43 |
December | 21.42 | 11.86 |
Annual Sum or Average | 22.72 | 21.71 |
Minimum of Months | 21.42 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 14.83 |
February | 21.33 | 12.72 |
March | 21.91 | 15.42 |
April | 23.03 | 23.31 |
May | 23.26 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.78 | 20.87 |
November | 21.98 | 15.43 |
December | 21.09 | 11.86 |
Annual Sum or Average | 22.54 | 21.71 |
Minimum of Months | 21.09 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 14.83 |
February | 21.46 | 12.72 |
March | 21.59 | 15.42 |
April | 21.75 | 23.31 |
May | 21.75 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.75 | 27.75 |
October | 21.71 | 20.87 |
November | 21.63 | 15.43 |
December | 21.45 | 11.86 |
Annual Sum or Average | 21.66 | 21.71 |
Minimum of Months | 21.45 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.83 |
February | 21.69 | 12.72 |
March | 21.70 | 15.42 |
April | 21.75 | 23.31 |
May | 21.75 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.74 | 15.43 |
December | 21.72 | 11.86 |
Annual Sum or Average | 21.74 | 21.71 |
Minimum of Months | 21.69 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.74 | 12.72 |
March | 21.74 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.75 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.74 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 14.83 |
February | 22.76 | 12.72 |
March | 22.73 | 15.42 |
April | 22.61 | 23.31 |
May | 22.53 | 26.31 |
June | 22.20 | 31.20 |
July | 22.23 | 30.42 |
August | 22.23 | 29.82 |
September | 22.29 | 27.75 |
October | 22.53 | 20.87 |
November | 22.59 | 15.43 |
December | 22.40 | 11.86 |
Annual Sum or Average | 22.46 | 21.71 |
Minimum of Months | 22.20 | 11.86 |
Maximum of Months | 22.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 52.10 | 14.83 |
February | 51.63 | 12.72 |
March | 51.76 | 15.42 |
April | 52.64 | 23.31 |
May | 52.81 | 26.31 |
June | 53.33 | 31.20 |
July | 53.33 | 30.42 |
August | 53.34 | 29.82 |
September | 53.25 | 27.75 |
October | 52.67 | 20.87 |
November | 52.13 | 15.43 |
December | 51.79 | 11.86 |
Annual Sum or Average | 52.57 | 21.71 |
Minimum of Months | 51.63 | 11.86 |
Maximum of Months | 53.34 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 69.58 | 14.83 |
February | 69.20 | 12.72 |
March | 69.36 | 15.42 |
April | 70.38 | 23.31 |
May | 70.68 | 26.31 |
June | 71.34 | 31.20 |
July | 71.31 | 30.42 |
August | 71.30 | 29.82 |
September | 71.07 | 27.75 |
October | 70.28 | 20.87 |
November | 69.64 | 15.43 |
December | 69.34 | 11.86 |
Annual Sum or Average | 70.30 | 21.71 |
Minimum of Months | 69.20 | 11.86 |
Maximum of Months | 71.34 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.56 | 14.83 |
February | 23.55 | 12.72 |
March | 23.59 | 15.42 |
April | 23.87 | 23.31 |
May | 23.89 | 26.31 |
June | 23.89 | 31.20 |
July | 23.89 | 30.42 |
August | 23.89 | 29.82 |
September | 23.89 | 27.75 |
October | 23.82 | 20.87 |
November | 23.64 | 15.43 |
December | 23.36 | 11.86 |
Annual Sum or Average | 23.74 | 21.71 |
Minimum of Months | 23.36 | 11.86 |
Maximum of Months | 23.89 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.54 | 14.83 |
February | 23.51 | 12.72 |
March | 23.56 | 15.42 |
April | 23.88 | 23.31 |
May | 23.89 | 26.31 |
June | 23.89 | 31.20 |
July | 23.89 | 30.42 |
August | 23.89 | 29.82 |
September | 23.89 | 27.75 |
October | 23.82 | 20.87 |
November | 23.64 | 15.43 |
December | 23.26 | 11.86 |
Annual Sum or Average | 23.72 | 21.71 |
Minimum of Months | 23.26 | 11.86 |
Maximum of Months | 23.89 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.38 | 14.83 |
February | 21.59 | 12.72 |
March | 22.19 | 15.42 |
April | 25.21 | 23.31 |
May | 26.12 | 26.31 |
June | 27.77 | 31.20 |
July | 27.50 | 30.42 |
August | 27.24 | 29.82 |
September | 26.61 | 27.75 |
October | 24.49 | 20.87 |
November | 22.61 | 15.43 |
December | 21.56 | 11.86 |
Annual Sum or Average | 24.62 | 21.71 |
Minimum of Months | 21.56 | 11.86 |
Maximum of Months | 27.77 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.21 | 14.83 |
February | 22.68 | 12.72 |
March | 23.00 | 15.42 |
April | 24.65 | 23.31 |
May | 25.12 | 26.31 |
June | 26.03 | 31.20 |
July | 25.92 | 30.42 |
August | 25.82 | 29.82 |
September | 25.52 | 27.75 |
October | 24.40 | 20.87 |
November | 23.36 | 15.43 |
December | 22.70 | 11.86 |
Annual Sum or Average | 24.38 | 21.71 |
Minimum of Months | 22.68 | 11.86 |
Maximum of Months | 26.03 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.64 | 14.83 |
February | 22.00 | 12.72 |
March | 22.49 | 15.42 |
April | 25.13 | 23.31 |
May | 25.96 | 26.31 |
June | 27.35 | 31.20 |
July | 27.02 | 30.42 |
August | 26.73 | 29.82 |
September | 26.25 | 27.75 |
October | 24.38 | 20.87 |
November | 22.85 | 15.43 |
December | 21.95 | 11.86 |
Annual Sum or Average | 24.57 | 21.71 |
Minimum of Months | 21.95 | 11.86 |
Maximum of Months | 27.35 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.77 | 14.83 |
February | 23.73 | 12.72 |
March | 23.77 | 15.42 |
April | 23.90 | 23.31 |
May | 23.95 | 26.31 |
June | 24.23 | 31.20 |
July | 24.14 | 30.42 |
August | 24.10 | 29.82 |
September | 23.99 | 27.75 |
October | 23.89 | 20.87 |
November | 23.80 | 15.43 |
December | 23.57 | 11.86 |
Annual Sum or Average | 23.90 | 21.71 |
Minimum of Months | 23.57 | 11.86 |
Maximum of Months | 24.23 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | 14.83 |
February | 20.71 | 12.72 |
March | 21.43 | 15.42 |
April | 24.27 | 23.31 |
May | 25.30 | 26.31 |
June | 26.78 | 31.20 |
July | 26.41 | 30.42 |
August | 26.01 | 29.82 |
September | 25.44 | 27.75 |
October | 23.32 | 20.87 |
November | 21.54 | 15.43 |
December | 20.35 | 11.86 |
Annual Sum or Average | 23.58 | 21.71 |
Minimum of Months | 20.35 | 11.86 |
Maximum of Months | 26.78 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 14.83 |
February | 21.40 | 12.72 |
March | 22.13 | 15.42 |
April | 23.21 | 23.31 |
May | 23.32 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.92 | 20.87 |
November | 22.13 | 15.43 |
December | 21.02 | 11.86 |
Annual Sum or Average | 22.62 | 21.71 |
Minimum of Months | 21.02 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 14.83 |
February | 21.66 | 12.72 |
March | 21.72 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.72 | 15.43 |
December | 21.62 | 11.86 |
Annual Sum or Average | 21.73 | 21.71 |
Minimum of Months | 21.62 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 14.83 |
February | 21.67 | 12.72 |
March | 21.72 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.73 | 15.43 |
December | 21.64 | 11.86 |
Annual Sum or Average | 21.73 | 21.71 |
Minimum of Months | 21.64 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 14.83 |
February | 21.70 | 12.72 |
March | 21.73 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.73 | 15.43 |
December | 21.67 | 11.86 |
Annual Sum or Average | 21.74 | 21.71 |
Minimum of Months | 21.67 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 14.83 |
February | 21.55 | 12.72 |
March | 21.66 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.73 | 20.87 |
November | 21.68 | 15.43 |
December | 21.52 | 11.86 |
Annual Sum or Average | 21.69 | 21.71 |
Minimum of Months | 21.52 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.74 | 12.72 |
March | 21.74 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.74 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.33 | 14.83 |
February | 23.33 | 12.72 |
March | 23.32 | 15.42 |
April | 23.33 | 23.31 |
May | 23.33 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 23.33 | 20.87 |
November | 23.33 | 15.43 |
December | 23.32 | 11.86 |
Annual Sum or Average | 23.33 | 21.71 |
Minimum of Months | 23.32 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 32.74 | 14.83 |
February | 32.46 | 12.72 |
March | 32.60 | 15.42 |
April | 33.39 | 23.31 |
May | 33.59 | 26.31 |
June | 34.11 | 31.20 |
July | 34.08 | 30.42 |
August | 34.05 | 29.82 |
September | 33.88 | 27.75 |
October | 33.29 | 20.87 |
November | 32.80 | 15.43 |
December | 32.46 | 11.86 |
Annual Sum or Average | 33.29 | 21.71 |
Minimum of Months | 32.46 | 11.86 |
Maximum of Months | 34.11 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | 14.83 |
February | 22.32 | 12.72 |
March | 22.39 | 15.42 |
April | 22.85 | 23.31 |
May | 23.00 | 26.31 |
June | 23.52 | 31.20 |
July | 23.62 | 30.42 |
August | 23.60 | 29.82 |
September | 23.43 | 27.75 |
October | 22.81 | 20.87 |
November | 22.45 | 15.43 |
December | 22.22 | 11.86 |
Annual Sum or Average | 22.89 | 21.71 |
Minimum of Months | 22.22 | 11.86 |
Maximum of Months | 23.62 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.75 | 12.72 |
March | 21.75 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.75 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.75 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.74 | 12.72 |
March | 21.74 | 15.42 |
April | 21.76 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.74 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.20 | 14.83 |
February | 22.71 | 12.72 |
March | 23.07 | 15.42 |
April | 24.95 | 23.31 |
May | 25.51 | 26.31 |
June | 26.48 | 31.20 |
July | 26.34 | 30.42 |
August | 26.17 | 29.82 |
September | 25.81 | 27.75 |
October | 24.55 | 20.87 |
November | 23.39 | 15.43 |
December | 22.67 | 11.86 |
Annual Sum or Average | 24.58 | 21.71 |
Minimum of Months | 22.67 | 11.86 |
Maximum of Months | 26.48 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.69 | 14.83 |
February | 22.03 | 12.72 |
March | 22.65 | 15.42 |
April | 25.98 | 23.31 |
May | 27.07 | 26.31 |
June | 28.84 | 31.20 |
July | 28.52 | 30.42 |
August | 28.15 | 29.82 |
September | 27.41 | 27.75 |
October | 25.07 | 20.87 |
November | 22.99 | 15.43 |
December | 21.88 | 11.86 |
Annual Sum or Average | 25.29 | 21.71 |
Minimum of Months | 21.88 | 11.86 |
Maximum of Months | 28.84 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.39 | 14.83 |
February | 21.73 | 12.72 |
March | 22.30 | 15.42 |
April | 25.21 | 23.31 |
May | 26.11 | 26.31 |
June | 27.57 | 31.20 |
July | 27.23 | 30.42 |
August | 26.91 | 29.82 |
September | 26.39 | 27.75 |
October | 24.35 | 20.87 |
November | 22.65 | 15.43 |
December | 21.61 | 11.86 |
Annual Sum or Average | 24.55 | 21.71 |
Minimum of Months | 21.61 | 11.86 |
Maximum of Months | 27.57 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.23 | 14.83 |
February | 22.90 | 12.72 |
March | 23.29 | 15.42 |
April | 23.86 | 23.31 |
May | 23.89 | 26.31 |
June | 23.91 | 31.20 |
July | 23.89 | 30.42 |
August | 23.89 | 29.82 |
September | 23.89 | 27.75 |
October | 23.73 | 20.87 |
November | 23.36 | 15.43 |
December | 22.69 | 11.86 |
Annual Sum or Average | 23.55 | 21.71 |
Minimum of Months | 22.69 | 11.86 |
Maximum of Months | 23.91 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.75 | 14.83 |
February | 20.18 | 12.72 |
March | 21.11 | 15.42 |
April | 24.43 | 23.31 |
May | 25.58 | 26.31 |
June | 27.16 | 31.20 |
July | 26.78 | 30.42 |
August | 26.35 | 29.82 |
September | 25.73 | 27.75 |
October | 23.31 | 20.87 |
November | 21.19 | 15.43 |
December | 19.71 | 11.86 |
Annual Sum or Average | 23.54 | 21.71 |
Minimum of Months | 19.71 | 11.86 |
Maximum of Months | 27.16 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.42 | 14.83 |
February | 20.77 | 12.72 |
March | 21.73 | 15.42 |
April | 23.15 | 23.31 |
May | 23.31 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.74 | 20.87 |
November | 21.70 | 15.43 |
December | 20.44 | 11.86 |
Annual Sum or Average | 22.39 | 21.71 |
Minimum of Months | 20.44 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 14.83 |
February | 20.87 | 12.72 |
March | 21.81 | 15.42 |
April | 23.18 | 23.31 |
May | 23.32 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.78 | 20.87 |
November | 21.78 | 15.43 |
December | 20.53 | 11.86 |
Annual Sum or Average | 22.43 | 21.71 |
Minimum of Months | 20.53 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 14.83 |
February | 20.95 | 12.72 |
March | 21.82 | 15.42 |
April | 23.15 | 23.31 |
May | 23.31 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.76 | 20.87 |
November | 21.79 | 15.43 |
December | 20.60 | 11.86 |
Annual Sum or Average | 22.44 | 21.71 |
Minimum of Months | 20.60 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 14.83 |
February | 21.65 | 12.72 |
March | 21.71 | 15.42 |
April | 21.75 | 23.31 |
May | 21.75 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.74 | 20.87 |
November | 21.72 | 15.43 |
December | 21.62 | 11.86 |
Annual Sum or Average | 21.72 | 21.71 |
Minimum of Months | 21.62 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 14.83 |
February | 20.98 | 12.72 |
March | 21.80 | 15.42 |
April | 23.19 | 23.31 |
May | 23.32 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.78 | 20.87 |
November | 21.81 | 15.43 |
December | 20.62 | 11.86 |
Annual Sum or Average | 22.45 | 21.71 |
Minimum of Months | 20.62 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.83 |
February | 21.71 | 12.72 |
March | 21.72 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.74 | 15.43 |
December | 21.73 | 11.86 |
Annual Sum or Average | 21.74 | 21.71 |
Minimum of Months | 21.71 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.75 | 12.72 |
March | 21.75 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.75 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.75 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.22 | 14.83 |
February | 24.88 | 12.72 |
March | 25.14 | 15.42 |
April | 26.11 | 23.31 |
May | 26.32 | 26.31 |
June | 26.75 | 31.20 |
July | 26.70 | 30.42 |
August | 26.64 | 29.82 |
September | 26.52 | 27.75 |
October | 25.91 | 20.87 |
November | 25.33 | 15.43 |
December | 24.81 | 11.86 |
Annual Sum or Average | 25.87 | 21.71 |
Minimum of Months | 24.81 | 11.86 |
Maximum of Months | 26.75 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.19 | 14.83 |
February | 23.14 | 12.72 |
March | 23.15 | 15.42 |
April | 23.33 | 23.31 |
May | 23.33 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 23.30 | 20.87 |
November | 23.23 | 15.43 |
December | 22.97 | 11.86 |
Annual Sum or Average | 23.25 | 21.71 |
Minimum of Months | 22.97 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.74 | 12.72 |
March | 21.74 | 15.42 |
April | 21.75 | 23.31 |
May | 21.75 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.74 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.57 | 14.83 |
February | 22.19 | 12.72 |
March | 22.49 | 15.42 |
April | 23.24 | 23.31 |
May | 23.32 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 23.09 | 20.87 |
November | 22.70 | 15.43 |
December | 22.08 | 11.86 |
Annual Sum or Average | 22.92 | 21.71 |
Minimum of Months | 22.08 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.92 | 14.83 |
February | 22.36 | 12.72 |
March | 22.85 | 15.42 |
April | 25.11 | 23.31 |
May | 25.76 | 26.31 |
June | 26.82 | 31.20 |
July | 26.65 | 30.42 |
August | 26.45 | 29.82 |
September | 26.04 | 27.75 |
October | 24.55 | 20.87 |
November | 23.16 | 15.43 |
December | 22.24 | 11.86 |
Annual Sum or Average | 24.59 | 21.71 |
Minimum of Months | 22.24 | 11.86 |
Maximum of Months | 26.82 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.43 | 14.83 |
February | 21.75 | 12.72 |
March | 22.48 | 15.42 |
April | 26.15 | 23.31 |
May | 27.34 | 26.31 |
June | 29.24 | 31.20 |
July | 28.88 | 30.42 |
August | 28.47 | 29.82 |
September | 27.65 | 27.75 |
October | 25.08 | 20.87 |
November | 22.79 | 15.43 |
December | 21.51 | 11.86 |
Annual Sum or Average | 25.33 | 21.71 |
Minimum of Months | 21.51 | 11.86 |
Maximum of Months | 29.24 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.89 | 14.83 |
February | 21.05 | 12.72 |
March | 21.90 | 15.42 |
April | 25.38 | 23.31 |
May | 26.44 | 26.31 |
June | 28.17 | 31.20 |
July | 27.77 | 30.42 |
August | 27.41 | 29.82 |
September | 26.77 | 27.75 |
October | 24.25 | 20.87 |
November | 22.19 | 15.43 |
December | 20.83 | 11.86 |
Annual Sum or Average | 24.52 | 21.71 |
Minimum of Months | 20.83 | 11.86 |
Maximum of Months | 28.17 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.55 | 14.83 |
February | 22.23 | 12.72 |
March | 22.72 | 15.42 |
April | 23.66 | 23.31 |
May | 23.90 | 26.31 |
June | 24.21 | 31.20 |
July | 24.10 | 30.42 |
August | 24.09 | 29.82 |
September | 23.97 | 27.75 |
October | 23.37 | 20.87 |
November | 22.73 | 15.43 |
December | 22.12 | 11.86 |
Annual Sum or Average | 23.31 | 21.71 |
Minimum of Months | 22.12 | 11.86 |
Maximum of Months | 24.21 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.30 | 14.83 |
February | 19.58 | 12.72 |
March | 20.77 | 15.42 |
April | 24.55 | 23.31 |
May | 25.83 | 26.31 |
June | 27.65 | 31.20 |
July | 27.21 | 30.42 |
August | 26.75 | 29.82 |
September | 26.02 | 27.75 |
October | 23.16 | 20.87 |
November | 20.75 | 15.43 |
December | 19.05 | 11.86 |
Annual Sum or Average | 23.49 | 21.71 |
Minimum of Months | 19.05 | 11.86 |
Maximum of Months | 27.65 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 14.83 |
February | 21.50 | 12.72 |
March | 21.64 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.71 | 20.87 |
November | 21.65 | 15.43 |
December | 21.46 | 11.86 |
Annual Sum or Average | 21.68 | 21.71 |
Minimum of Months | 21.46 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.94 | 14.83 |
February | 20.34 | 12.72 |
March | 21.34 | 15.42 |
April | 22.91 | 23.31 |
May | 23.22 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.32 | 27.75 |
October | 22.40 | 20.87 |
November | 21.24 | 15.43 |
December | 20.14 | 11.86 |
Annual Sum or Average | 22.16 | 21.71 |
Minimum of Months | 20.14 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | 14.83 |
February | 20.36 | 12.72 |
March | 21.33 | 15.42 |
April | 22.88 | 23.31 |
May | 23.21 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.32 | 27.75 |
October | 22.37 | 20.87 |
November | 21.23 | 15.43 |
December | 20.16 | 11.86 |
Annual Sum or Average | 22.16 | 21.71 |
Minimum of Months | 20.16 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 14.83 |
February | 21.64 | 12.72 |
March | 21.70 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.73 | 20.87 |
November | 21.71 | 15.43 |
December | 21.62 | 11.86 |
Annual Sum or Average | 21.72 | 21.71 |
Minimum of Months | 21.62 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 14.83 |
February | 20.49 | 12.72 |
March | 21.42 | 15.42 |
April | 22.97 | 23.31 |
May | 23.25 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.32 | 27.75 |
October | 22.47 | 20.87 |
November | 21.36 | 15.43 |
December | 20.24 | 11.86 |
Annual Sum or Average | 22.22 | 21.71 |
Minimum of Months | 20.24 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 14.83 |
February | 21.42 | 12.72 |
March | 21.89 | 15.42 |
April | 23.03 | 23.31 |
May | 23.26 | 26.31 |
June | 23.33 | 31.20 |
July | 23.33 | 30.42 |
August | 23.33 | 29.82 |
September | 23.33 | 27.75 |
October | 22.74 | 20.87 |
November | 22.06 | 15.43 |
December | 21.26 | 11.86 |
Annual Sum or Average | 22.57 | 21.71 |
Minimum of Months | 21.26 | 11.86 |
Maximum of Months | 23.33 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.73 | 12.72 |
March | 21.73 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.73 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 23.11 | 14.83 |
February | 22.70 | 12.72 |
March | 23.14 | 15.42 |
April | 24.55 | 23.31 |
May | 24.92 | 26.31 |
June | 25.59 | 31.20 |
July | 25.47 | 30.42 |
August | 25.36 | 29.82 |
September | 25.12 | 27.75 |
October | 24.11 | 20.87 |
November | 23.26 | 15.43 |
December | 22.56 | 11.86 |
Annual Sum or Average | 24.16 | 21.71 |
Minimum of Months | 22.56 | 11.86 |
Maximum of Months | 25.59 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.73 | 12.72 |
March | 21.73 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.73 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 14.83 |
February | 21.73 | 12.72 |
March | 21.73 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.75 | 15.43 |
December | 21.74 | 11.86 |
Annual Sum or Average | 21.75 | 21.71 |
Minimum of Months | 21.73 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 14.83 |
February | 21.70 | 12.72 |
March | 21.71 | 15.42 |
April | 21.75 | 23.31 |
May | 21.76 | 26.31 |
June | 21.76 | 31.20 |
July | 21.76 | 30.42 |
August | 21.76 | 29.82 |
September | 21.76 | 27.75 |
October | 21.75 | 20.87 |
November | 21.74 | 15.43 |
December | 21.72 | 11.86 |
Annual Sum or Average | 21.74 | 21.71 |
Minimum of Months | 21.70 | 11.86 |
Maximum of Months | 21.76 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.48 | 14.83 |
February | 21.88 | 12.72 |
March | 22.52 | 15.42 |
April | 25.06 | 23.31 |
May | 25.81 | 26.31 |
June | 27.09 | 31.20 |
July | 26.86 | 30.42 |
August | 26.62 | 29.82 |
September | 26.09 | 27.75 |
October | 24.27 | 20.87 |
November | 22.71 | 15.43 |
December | 21.68 | 11.86 |
Annual Sum or Average | 24.43 | 21.71 |
Minimum of Months | 21.68 | 11.86 |
Maximum of Months | 27.09 | 31.20 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:32
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.97 | 14.83 |
February | 21.20 | 12.72 |
March | 22.12 | 15.42 |
April | 26.19 | 23.31 |
May | 27.50 | 26.31 |
June | 29.64 | 31.20 |
July | 29.21 | 30.42 |
August | 28.77 | 29.82 |
September | 27.83 | 27.75 |
October | 24.85 | 20.87 |
November | 22.32 | 15.43 |
December | 20.87 | 11.86 |
Annual Sum or Average | 25.22 | 21.71 |
Minimum of Months | 20.87 | 11.86 |
Maximum of Months | 29.64 | 31.20 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:32
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.139459E+12 | 90277.465 | 01-JAN-07:15 | 13316.689 | 34010.661 | 9108.376 | 28966.712 | 678.914 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.122471E+12 | 86788.626 | 01-FEB-07:15 | 15177.258 | 39465.561 | 9108.376 | 14896.335 | 3944.982 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.138938E+12 | 95136.514 | 26-MAR-06:15 | 15177.258 | 39465.561 | 9108.376 | 25754.342 | 1434.863 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.149439E+12 | 89853.911 | 15-APR-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 19039.001 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.161780E+12 | 90140.743 | 19-MAY-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 19325.833 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.174336E+12 | 102961.921 | 30-JUN-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 32147.011 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.184735E+12 | 105755.037 | 22-JUL-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 34940.126 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.182802E+12 | 103032.207 | 12-AUG-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 32217.296 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.170628E+12 | 100926.712 | 02-SEP-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 30111.802 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.152441E+12 | 93333.914 | 07-OCT-07:00 | 17938.723 | 43276.576 | 9591.499 | 0.000 | 22519.003 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.136532E+12 | 89865.722 | 23-NOV-07:15 | 15177.258 | 39465.561 | 9108.376 | 24087.389 | 2019.024 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.137287E+12 | 97047.177 | 07-DEC-07:15 | 15177.258 | 39465.561 | 9108.376 | 28104.137 | 995.731 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.185085E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.122471E+12 | 86788.626 | 13316.689 | 34010.661 | 9108.376 | 0.000 | 678.914 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.184735E+12 | 105755.037 | 17938.723 | 43276.576 | 9591.499 | 28966.712 | 34940.126 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:32
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.850492E+11 | 91261.736 | 28-JAN-09:15 | 0.000 | 40096.028 | 0.000 | 51165.707 | 51165.707 | 51165.707 | 0.000 |
February | 0.763889E+11 | 91046.048 | 03-FEB-09:15 | 0.000 | 40096.028 | 0.000 | 50950.020 | 50950.020 | 50950.020 | 0.000 |
March | 0.822781E+11 | 89980.403 | 03-MAR-09:00 | 0.000 | 40096.028 | 0.000 | 49884.375 | 49884.375 | 49884.375 | 0.000 |
April | 0.766686E+11 | 74278.114 | 01-APR-08:00 | 0.000 | 40096.028 | 0.000 | 34182.086 | 34182.086 | 34182.086 | 0.000 |
May | 0.772267E+11 | 73241.442 | 01-MAY-08:15 | 0.000 | 40096.028 | 0.000 | 33145.414 | 33145.414 | 33145.414 | 0.000 |
June | 0.731728E+11 | 72201.440 | 01-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 32105.412 | 32105.412 | 32105.412 | 0.000 |
July | 0.748192E+11 | 71555.985 | 01-JUL-08:30 | 0.000 | 40096.028 | 0.000 | 31459.957 | 31459.957 | 31459.957 | 0.000 |
August | 0.750556E+11 | 71812.835 | 29-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 31716.807 | 31716.807 | 31716.807 | 0.000 |
September | 0.738013E+11 | 72563.520 | 30-SEP-08:45 | 0.000 | 40096.028 | 0.000 | 32467.492 | 32467.492 | 32467.492 | 0.000 |
October | 0.782311E+11 | 73673.748 | 31-OCT-08:45 | 0.000 | 40096.028 | 0.000 | 33577.720 | 33577.720 | 33577.720 | 0.000 |
November | 0.782988E+11 | 89381.655 | 30-NOV-09:15 | 0.000 | 40096.028 | 0.000 | 49285.627 | 49285.627 | 49285.627 | 0.000 |
December | 0.850458E+11 | 90374.841 | 30-DEC-09:00 | 0.000 | 40096.028 | 0.000 | 50278.813 | 50278.813 | 50278.813 | 0.000 |
Annual Sum or Average | 0.936036E+12 | 0.000 | ||||||||
Minimum of Months | 0.731728E+11 | 71555.985 | 0.000 | 40096.028 | 0.000 | 31459.957 | 31459.957 | 31459.957 | 0.000 | |
Maximum of Months | 0.850492E+11 | 91261.736 | 0.000 | 40096.028 | 0.000 | 51165.707 | 51165.707 | 51165.707 | 0.000 |