Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
Tabular Output Report in Format: HTML
Building: Small Hotel
Environment: International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2018-10-19 10:15:38
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 3427.52 | 853.98 | 920.12 |
Net Site Energy | 3427.52 | 853.98 | 920.12 |
Total Source Energy | 7998.01 | 1992.74 | 2147.06 |
Net Source Energy | 7998.01 | 1992.74 | 2147.06 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4013.58 |
Net Conditioned Building Area | 3725.09 |
Unconditioned Building Area | 288.49 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 540.54 | 218.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 164.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 414.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 65.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 591.01 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 279.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 731.97 | 0.00 | 0.00 | 0.00 | 2578.25 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2055.96 | 1371.56 | 0.00 | 0.00 | 0.00 | 2578.25 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 540.54 | 218.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 164.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General Lights | 414.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 65.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 562.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ELECTRIC EQUIPMENT#Laundry#05 | 28.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
GAS EQUIPMENT#Laundry#05 | 0.00 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 279.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 731.97 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.25 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 128.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 264.41 | 255.05 | 0.00 | 0.00 | 0.00 | 0.69 |
Other | 158.66 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 551.92 | 368.19 | 0.00 | 0.00 | 0.00 | 0.69 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 119.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 245.40 | 236.71 | 0.00 | 0.00 | 0.00 | 0.64 |
Other | 147.25 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 512.25 | 341.73 | 0.00 | 0.00 | 0.00 | 0.64 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 2055.96 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 2055.96 | 100.00 |
Total On-Site and Utility Electric Sources | 2055.96 | 100.00 |
Total Electricity End Uses | 2055.96 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 2578.25 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 2578.25 | 100.00 |
Total Water End Uses | 2578.25 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1853.50 |
Time Setpoint Not Met During Occupied Cooling | 2360.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6513.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14 |
RunPeriod | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 180.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
Window Opening Area [m2] | 184.20 | 96.82 | 8.38 | 72.38 | 6.62 |
Window-Wall Ratio [%] | 10.87 | 15.24 | 3.95 | 11.39 | 3.13 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
Window Opening Area [m2] | 179.26 | 96.82 | 8.38 | 67.45 | 6.62 |
Window-Wall Ratio [%] | 12.01 | 15.95 | 3.95 | 12.11 | 5.68 |
Total | |
Gross Roof Area [m2] | 1003.40 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 9.82 | 8.5250 | 0.0000 | |
REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 6.7813 | 0.0000 | |
FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 14.83 | 11.4097 | 3.08 | 26.0600 |
RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.5486 | 32.61 | 0.0000 |
MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 4.94 | 13.2396 | 1.87 | 6.1800 |
MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 10.2257 | 0.0000 | |
GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 8.0729 | 21.74 | 11.8935 |
EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 7.8577 | 1.81 | 21.5100 |
LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 4.94 | 6.4583 | 8.89 | 437.5596 |
ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.0000 | 2147.5789 | |
EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 1.65 | 9.3000 | 4.66 | 18.5900 |
FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 6.58 | 11.9479 | 13.04 | 13.7800 |
FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 7.4271 | 0.0000 | |
FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 6.7813 | 0.0000 | |
REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 7.4271 | 0.0000 | |
CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 2.62 | 8.5250 | 0.0000 | |
REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 6.7813 | 0.0000 | |
GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 6.70 | 8.0729 | 23.41 | 11.8935 |
GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.0000 | 0.0000 | |
GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 6.58 | 8.0729 | 21.74 | 11.8935 |
GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 1.65 | 8.0729 | 21.74 | 11.8935 |
FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 6.7813 | 0.0000 | |
FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 7.4271 | 0.0000 | |
Total | 4013.58 | 11621.73 | 1694.58 | 184.20 | 8.3147 | 15.53 | 28.1818 | |||
Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 179.26 | 8.5515 | 15.05 | 10.1966 | |||
Unconditioned Total | 288.49 | 880.07 | 202.26 | 4.94 | 5.2567 | 26.23 | 260.4149 | |||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
S_REARSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 270.00 | 90.00 | W |
W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 180.00 | 90.00 | S |
W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 90.00 | 90.00 | E |
W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 10.22 | 0.00 | 90.00 | N |
S_CORRIDORFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 150.51 | 180.00 | 180.00 | |
W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 0.00 | 90.00 | N |
S_REARSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.43 | 0.00 | 90.00 | N |
S_FRONTLOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 163.06 | 180.00 | 180.00 | |
W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_RESTROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 32.70 | 0.00 | 90.00 | N |
S_MEETINGROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 80.27 | 180.00 | 180.00 | |
W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_MECHANICALROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM101_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM101_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM102_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM102_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM103_5_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 0.00 | 90.00 | N |
S_GUESTROOM103_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM104_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM104_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_GUESTROOM105_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_GUESTROOM105_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EMPLOYEELOUNGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.86 | 180.00 | 90.00 | S |
S_LAUNDRYROOMFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 97.83 | 180.00 | 180.00 | |
W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.13 | 180.00 | 90.00 | S |
S_ELEVATORCOREFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.05 | 180.00 | 180.00 | |
W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.29 | 180.00 | 90.00 | S |
S_EXERCISECENTERFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 32.61 | 180.00 | 180.00 | |
W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 53.14 | 180.00 | 90.00 | S |
S_FRONTOFFICEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 130.44 | 180.00 | 180.00 | |
W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.59 | 90.00 | 90.00 | E |
S_FRONTSTAIRSFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 20.07 | 180.00 | 180.00 | |
W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.11 | 180.00 | 90.00 | S |
S_FRONTSTORAGEFLR1_0_0_0 | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 12.54 | 180.00 | 180.00 | |
W_REARSTAIRSFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR2_9_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR2_15_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR2_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR2_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM201_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM201_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM213_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM214_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM219_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM224_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR2_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR3_9_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR3_15_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 90.00 | 90.00 | E |
W_REARSTORAGEFLR3_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR3_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 0.00 | 90.00 | N |
W_GUESTROOM301_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM301_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 35.12 | 0.00 | 90.00 | N |
W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
W_GUESTROOM313_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
W_GUESTROOM314_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
W_ELEVATORCOREFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 180.00 | 90.00 | S |
W_GUESTROOM319_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
W_GUESTROOM324_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
W_FRONTSTORAGEFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 4.18 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR3_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
W_REARSTAIRSFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
R_REARSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_CORRIDORFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 270.00 | 90.00 | W |
W_CORRIDORFLR4_9_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 8.36 | 180.00 | 90.00 | S |
W_CORRIDORFLR4_15_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 90.00 | 90.00 | E |
R_CORRIDORFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 125.42 | 0.00 | 0.00 | |
W_REARSTORAGEFLR4_2_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 270.00 | 90.00 | W |
W_REARSTORAGEFLR4_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 0.00 | 90.00 | N |
R_REARSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
W_GUESTROOM401_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
W_GUESTROOM401_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM401_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 35.12 | 0.00 | 90.00 | N |
R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 105.36 | 0.00 | 0.00 | |
W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 0.00 | 90.00 | N |
R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.45 | 0.00 | 0.00 | |
W_GUESTROOM413_5_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 0.00 | 90.00 | N |
R_GUESTROOM413_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM414_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM414_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_ELEVATORCOREFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 5.02 | 180.00 | 90.00 | S |
R_ELEVATORCOREFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 15.05 | 0.00 | 0.00 | |
W_GUESTROOM419_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM419_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 43.48 | 180.00 | 90.00 | S |
R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 130.44 | 0.00 | 0.00 | |
W_GUESTROOM424_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 10.87 | 180.00 | 90.00 | S |
R_GUESTROOM424_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 32.61 | 0.00 | 0.00 | |
W_FRONTSTORAGEFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 4.18 | 180.00 | 90.00 | S |
R_FRONTSTORAGEFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 12.54 | 0.00 | 0.00 | |
W_FRONTSTAIRSFLR4_3_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 6.69 | 180.00 | 90.00 | S |
W_FRONTSTAIRSFLR4_4_0_0 | RES_EXT_WALL | 0.30 | 0.238 | 0.247 | 22.58 | 90.00 | 90.00 | E |
R_FRONTSTAIRSFLR4_1_0_0 | RES_ROOF | 0.23 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
W_CORRIDORFLR1_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | ||
D_CORRIDORFLR1_16_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | ||
W_CORRIDORFLR1_20_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_FRONTLOUNGEFLR1_5_0_0_0_4 | WINDOW_U_0.46_SHGC_0.45 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.670 | 0.479 | 0.381 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_MEETINGROOMFLR1_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM101_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM102_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM103_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM104_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM105_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | ||
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_LAUNDRYROOMFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_EXERCISECENTERFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_FRONTOFFICEFLR1_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR2_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR2_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM201_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM202_205_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM206_208_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM209_212_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM213_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM214_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM215_218_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM219_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM220_223_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM224_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR3_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR3_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM301_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM302_305_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM306_308_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM309_312_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM313_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM314_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM315_318_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM319_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM320_323_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM324_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | ||
W_CORRIDORFLR4_2_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | ||
W_CORRIDORFLR4_15_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 2.670 | 0.479 | 0.381 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | ||
W_GUESTROOM401_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM402_405_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM406_408_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM409_412_5_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM413_5_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | ||
W_GUESTROOM414_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM415_418_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM419_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_1 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_2 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM420_423_3_0_0_0_3 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | ||
W_GUESTROOM424_3_0_0_0_0 | WINDOW_U_0.46_SHGC_0.45 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.670 | 0.479 | 0.381 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | ||
Total or Average | 184.20 | 2.670 | 0.479 | 0.381 | ||||||||||||
North Total or Average | 96.82 | 2.670 | 0.479 | 0.381 | ||||||||||||
Non-North Total or Average | 87.38 | 2.670 | 0.479 | 0.381 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_CORRIDORFLR1_10_0_0 |
W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7913.25 | 5780.50 | 2132.75 | 0.73 | 3.73 | |||
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10551.00 | 7707.33 | 2843.67 | 0.73 | 3.73 | |||
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2637.75 | 1926.83 | 710.92 | 0.73 | 3.73 | |||
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6576.12 | 4864.17 | 1711.95 | 0.74 | 3.91 | |||
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17305.66 | 12008.96 | 5296.70 | 0.69 | 3.91 | |||
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8780.71 | 5936.49 | 2844.22 | 0.68 | 3.91 | |||
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13695.99 | 10270.16 | 3425.83 | 0.75 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
CORRIDORFLR1 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
101 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
102 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
103 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
104 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
105 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR2 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
201 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
202_205 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
206_208 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
209_212 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
213 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
214 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
215_218 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
219 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
220_223 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
224 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR3 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
301 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
302_305 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
306_308 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
309_312 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
313 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
314 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
315_318 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
319 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
320_323 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
324 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
CORRIDORFLR4 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
401 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
402_405 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
406_408 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7610.9 | 3.14 | 10.72 | 11.36 | 10.75 |
409_412 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
413 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
414 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
415_418 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
419 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
420_423 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10147.8 | 3.14 | 10.72 | 11.36 | 10.75 |
424 PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2537.0 | 3.14 | 10.72 | 11.36 | 10.75 |
SAC_FRONTOFFICE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6317.1 | 3.26 | 11.12 | 11.78 | 11.07 |
SAC_FRONTLOUNGE COOLING COIL | Coil:Cooling:DX:SingleSpeed | 16724.7 | 3.34 | 11.41 | 12.10 | 11.51 |
SAC_MEETINGROOM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8505.9 | 3.38 | 11.52 | 12.22 | 11.70 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | Coil:Cooling:DX:SingleSpeed | 13138.9 | 3.24 | 11.05 | 11.71 | 10.97 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 307.99 | 1.00 | |
CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Electric | 43440.33 | 1.00 | |
MECHRMUNITHEATERHEATINGCOIL | Coil:Heating:Electric | 0.00 | 1.00 | |
101 PTAC HEATING COIL | Coil:Heating:Electric | 1311.17 | 1.00 | |
102 PTAC HEATING COIL | Coil:Heating:Electric | 1357.78 | 1.00 | |
103 PTAC HEATING COIL | Coil:Heating:Electric | 1731.35 | 1.00 | |
104 PTAC HEATING COIL | Coil:Heating:Electric | 1743.65 | 1.00 | |
105 PTAC HEATING COIL | Coil:Heating:Electric | 1370.81 | 1.00 | |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 307.91 | 1.00 | |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 307.99 | 1.00 | |
CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Electric | 3718.56 | 1.00 | |
201 PTAC HEATING COIL | Coil:Heating:Electric | 1514.24 | 1.00 | |
202_205 PTAC HEATING COIL | Coil:Heating:Electric | 5244.69 | 1.00 | |
206_208 PTAC HEATING COIL | Coil:Heating:Electric | 4156.60 | 1.00 | |
209_212 PTAC HEATING COIL | Coil:Heating:Electric | 5244.69 | 1.00 | |
213 PTAC HEATING COIL | Coil:Heating:Electric | 1689.50 | 1.00 | |
214 PTAC HEATING COIL | Coil:Heating:Electric | 1661.31 | 1.00 | |
215_218 PTAC HEATING COIL | Coil:Heating:Electric | 5244.32 | 1.00 | |
219 PTAC HEATING COIL | Coil:Heating:Electric | 1311.08 | 1.00 | |
220_223 PTAC HEATING COIL | Coil:Heating:Electric | 5244.32 | 1.00 | |
224 PTAC HEATING COIL | Coil:Heating:Electric | 1524.03 | 1.00 | |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 594.96 | 1.00 | |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 307.99 | 1.00 | |
CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Electric | 3961.29 | 1.00 | |
301 PTAC HEATING COIL | Coil:Heating:Electric | 1570.40 | 1.00 | |
302_305 PTAC HEATING COIL | Coil:Heating:Electric | 5244.69 | 1.00 | |
306_308 PTAC HEATING COIL | Coil:Heating:Electric | 4213.89 | 1.00 | |
309_312 PTAC HEATING COIL | Coil:Heating:Electric | 5244.69 | 1.00 | |
313 PTAC HEATING COIL | Coil:Heating:Electric | 1807.19 | 1.00 | |
314 PTAC HEATING COIL | Coil:Heating:Electric | 1762.38 | 1.00 | |
315_318 PTAC HEATING COIL | Coil:Heating:Electric | 5244.32 | 1.00 | |
319 PTAC HEATING COIL | Coil:Heating:Electric | 1344.66 | 1.00 | |
320_323 PTAC HEATING COIL | Coil:Heating:Electric | 5244.32 | 1.00 | |
324 PTAC HEATING COIL | Coil:Heating:Electric | 1619.54 | 1.00 | |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 594.96 | 1.00 | |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 595.11 | 1.00 | |
CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Electric | 5948.04 | 1.00 | |
401 PTAC HEATING COIL | Coil:Heating:Electric | 2015.29 | 1.00 | |
402_405 PTAC HEATING COIL | Coil:Heating:Electric | 6713.62 | 1.00 | |
406_408 PTAC HEATING COIL | Coil:Heating:Electric | 5513.58 | 1.00 | |
409_412 PTAC HEATING COIL | Coil:Heating:Electric | 6737.60 | 1.00 | |
413 PTAC HEATING COIL | Coil:Heating:Electric | 2329.84 | 1.00 | |
414 PTAC HEATING COIL | Coil:Heating:Electric | 2272.53 | 1.00 | |
415_418 PTAC HEATING COIL | Coil:Heating:Electric | 6744.66 | 1.00 | |
419 PTAC HEATING COIL | Coil:Heating:Electric | 1842.69 | 1.00 | |
420_423 PTAC HEATING COIL | Coil:Heating:Electric | 6685.52 | 1.00 | |
424 PTAC HEATING COIL | Coil:Heating:Electric | 2112.84 | 1.00 | |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | Coil:Heating:Electric | 717.75 | 1.00 | |
SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Gas | 5398.83 | 0.80 | |
SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Gas | 22629.09 | 0.80 | |
SAC_MEETINGROOM HEATING COIL | Coil:Heating:Gas | 12117.71 | 0.80 | |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | Coil:Heating:Gas | 9282.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
REARSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR1 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
MECHRMUNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.00 | 0.00 | 1.00 | General | |
101 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
102 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
103 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
104 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
105 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR1UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR2 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
201 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
202_205 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
206_208 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
209_212 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
213 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
214 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
215_218 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
219 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
220_223 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
224 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR2UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR3 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
301 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
302_305 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
306_308 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
309_312 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
313 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
314 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
315_318 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
319 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
320_323 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
324 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR3UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
REARSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.57 | 92.91 | 1.00 | General |
CORRIDORFLR4 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
401 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
402_405 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
406_408 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 248.38 | 636.87 | 1.00 | General |
409_412 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
413 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
414 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
415_418 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
419 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
420_423 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.52 | 331.17 | 636.87 | 1.00 | General |
424 PTAC SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 82.79 | 636.87 | 1.00 | General |
FRONTSTAIRSFLR4UNITHEATERFAN | Fan:ConstantVolume | 0.54 | 49.80 | 0.01 | 0.79 | 92.91 | 1.00 | General |
SAC_FRONTOFFICE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.33 | 373.59 | 1120.11 | 1.00 | General |
SAC_FRONTLOUNGE SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.75 | 827.77 | 1107.16 | 1.00 | General |
SAC_MEETINGROOM SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.35 | 396.07 | 1120.11 | 1.00 | General |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | Fan:ConstantVolume | 0.56 | 622.50 | 0.72 | 794.47 | 1107.16 | 1.00 | General |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SHWSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0002 | 8.11 | 45084.46 | 0.85 |
SHWSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.0001 | 0.00 | 0.00 | 0.30 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYSSHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
SHWSYSLAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 0.80 | 0.51 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 7241.28 | 8689.53 | 0.623 | 0.748 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10 | 0.01270 |
RESTROOMFLR1 | 393.80 | 472.56 | 0.034 | 0.041 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:15:00 | 29.11 | 0.01270 |
MEETINGROOMFLR1 | 3422.50 | 4107.00 | 0.295 | 0.354 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10 | 0.01270 |
GUESTROOM101 | 505.27 | 606.32 | 0.060 | 0.072 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.54 | 0.01270 |
GUESTROOM102 | 408.06 | 489.68 | 0.049 | 0.059 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.54 | 0.01270 |
GUESTROOM103 | 963.45 | 1156.14 | 0.115 | 0.138 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 24.92 | 0.01270 |
GUESTROOM104 | 1175.79 | 1410.94 | 0.141 | 0.169 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.10 | 0.01270 |
GUESTROOM105 | 1565.61 | 1878.74 | 0.187 | 0.225 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.10 | 0.01270 |
EMPLOYEELOUNGEFLR1 | 5403.05 | 6483.66 | 0.465 | 0.558 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
EXERCISECENTERFLR1 | 1153.37 | 1384.04 | 0.099 | 0.119 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36 | 0.01270 |
FRONTOFFICEFLR1 | 3233.06 | 3879.67 | 0.278 | 0.334 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM201 | 690.56 | 828.67 | 0.083 | 0.099 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.10 | 0.01270 |
GUESTROOM202_205 | 3940.49 | 4728.59 | 0.471 | 0.565 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.54 | 0.01270 |
GUESTROOM206_208 | 3202.56 | 3843.07 | 0.383 | 0.459 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.54 | 0.01270 |
GUESTROOM209_212 | 3757.35 | 4508.82 | 0.449 | 0.539 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 29.54 | 0.01270 |
GUESTROOM213 | 1031.52 | 1237.82 | 0.123 | 0.148 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 24.92 | 0.01270 |
GUESTROOM214 | 1303.09 | 1563.71 | 0.156 | 0.187 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM215_218 | 9678.62 | 11614.35 | 1.157 | 1.388 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM219 | 5451.55 | 6541.87 | 0.652 | 0.782 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM220_223 | 4670.06 | 5604.08 | 0.558 | 0.670 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.10 | 0.01270 |
GUESTROOM224 | 1308.59 | 1570.31 | 0.156 | 0.188 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM301 | 514.66 | 617.59 | 0.062 | 0.074 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.10 | 0.01270 |
GUESTROOM302_305 | 1388.74 | 1666.48 | 0.166 | 0.199 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.36 | 0.01270 |
GUESTROOM306_308 | 1229.68 | 1475.61 | 0.147 | 0.176 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.36 | 0.01270 |
GUESTROOM309_312 | 3726.49 | 4471.79 | 0.445 | 0.535 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.36 | 0.01270 |
GUESTROOM313 | 531.97 | 638.37 | 0.064 | 0.076 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:15:00 | 24.92 | 0.01270 |
GUESTROOM314 | 1217.49 | 1460.99 | 0.146 | 0.175 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.10 | 0.01270 |
GUESTROOM315_318 | 5087.09 | 6104.51 | 0.608 | 0.730 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM319 | 1130.44 | 1356.53 | 0.135 | 0.162 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM320_323 | 4465.84 | 5359.01 | 0.534 | 0.641 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM324 | 732.28 | 878.74 | 0.088 | 0.105 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM401 | 1334.77 | 1601.72 | 0.160 | 0.191 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.10 | 0.01270 |
GUESTROOM402_405 | 2148.24 | 2577.89 | 0.257 | 0.308 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.10 | 0.01270 |
GUESTROOM406_408 | 1852.08 | 2222.50 | 0.221 | 0.266 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.10 | 0.01270 |
GUESTROOM409_412 | 4800.13 | 5760.15 | 0.574 | 0.689 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 30.10 | 0.01270 |
GUESTROOM413 | 782.38 | 938.86 | 0.094 | 0.112 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 29.91 | 0.01270 |
GUESTROOM414 | 1015.58 | 1218.69 | 0.121 | 0.146 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
GUESTROOM415_418 | 5811.00 | 6973.21 | 0.695 | 0.834 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10 | 0.01270 |
GUESTROOM419 | 1583.47 | 1900.17 | 0.189 | 0.227 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:15:00 | 30.10 | 0.01270 |
GUESTROOM420_423 | 5769.74 | 6923.69 | 0.690 | 0.828 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10 | 0.01270 |
GUESTROOM424 | 1579.34 | 1895.20 | 0.189 | 0.227 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10 | 0.01270 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
CORRIDORFLR1 | 13579.73 | 16295.68 | 1.168 | 1.401 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 27.12 | 0.01270 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
CORRIDORFLR2 | 2603.22 | 3123.86 | 0.224 | 0.268 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.36 | 0.01270 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
CORRIDORFLR3 | 1207.94 | 1449.53 | 0.104 | 0.125 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 28.05 | 0.01270 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 | |
CORRIDORFLR4 | 2077.54 | 2493.05 | 0.179 | 0.214 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 29.73 | 0.01270 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 0.01270 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FRONTLOUNGEFLR1 | 2462.61 | 2955.13 | 0.072 | 0.236 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:45:00 | -32.70 | 0.00018 |
RESTROOMFLR1 | 195.36 | 234.43 | 0.006 | 0.007 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -32.70 | 0.00018 |
MEETINGROOMFLR1 | 883.59 | 1060.31 | 0.026 | 0.126 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -32.70 | 0.00018 |
GUESTROOM101 | 374.16 | 448.99 | 0.011 | 0.013 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -32.70 | 0.00018 |
GUESTROOM102 | 420.52 | 504.63 | 0.012 | 0.015 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70 | 0.00018 |
GUESTROOM103 | 731.83 | 878.20 | 0.022 | 0.026 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -32.70 | 0.00018 |
GUESTROOM104 | 742.14 | 890.56 | 0.022 | 0.026 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:30:00 | -32.70 | 0.00018 |
GUESTROOM105 | 431.43 | 517.72 | 0.013 | 0.015 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:45:00 | -32.70 | 0.00018 |
EMPLOYEELOUNGEFLR1 | 418.15 | 501.78 | 0.012 | 0.051 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -32.70 | 0.00018 |
EXERCISECENTERFLR1 | 308.83 | 370.60 | 0.009 | 0.043 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -32.70 | 0.00018 |
FRONTOFFICEFLR1 | 1584.30 | 1901.16 | 0.047 | 0.056 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 06:30:00 | -32.70 | 0.00018 |
GUESTROOM201 | 550.91 | 661.09 | 0.016 | 0.019 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -32.70 | 0.00018 |
GUESTROOM202_205 | 1283.44 | 1540.13 | 0.038 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:30:00 | -32.70 | 0.00018 |
GUESTROOM206_208 | 1038.47 | 1246.17 | 0.031 | 0.043 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70 | 0.00018 |
GUESTROOM209_212 | 1194.48 | 1433.38 | 0.035 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:00:00 | -32.70 | 0.00018 |
GUESTROOM213 | 696.96 | 836.35 | 0.021 | 0.025 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:45:00 | -32.70 | 0.00018 |
GUESTROOM214 | 673.52 | 808.22 | 0.020 | 0.024 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 10:15:00 | -32.70 | 0.00018 |
GUESTROOM215_218 | 1244.65 | 1493.59 | 0.037 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -32.70 | 0.00018 |
GUESTROOM219 | 323.26 | 387.91 | 0.010 | 0.013 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -32.70 | 0.00018 |
GUESTROOM220_223 | 1176.26 | 1411.51 | 0.035 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -32.70 | 0.00018 |
GUESTROOM224 | 559.12 | 670.94 | 0.016 | 0.020 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:15:00 | -32.70 | 0.00018 |
GUESTROOM301 | 597.71 | 717.25 | 0.018 | 0.021 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -32.70 | 0.00018 |
GUESTROOM302_305 | 1443.92 | 1732.70 | 0.042 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | -32.70 | 0.00018 |
GUESTROOM306_308 | 1257.74 | 1509.29 | 0.037 | 0.044 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -32.70 | 0.00018 |
GUESTROOM309_312 | 1449.09 | 1738.91 | 0.043 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:15:00 | -32.70 | 0.00018 |
GUESTROOM313 | 795.03 | 954.04 | 0.023 | 0.028 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:30:00 | -32.70 | 0.00018 |
GUESTROOM314 | 757.74 | 909.29 | 0.022 | 0.027 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 14:15:00 | -32.70 | 0.00018 |
GUESTROOM315_318 | 1461.21 | 1753.45 | 0.043 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:45:00 | -32.70 | 0.00018 |
GUESTROOM319 | 409.64 | 491.57 | 0.012 | 0.014 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70 | 0.00018 |
GUESTROOM320_323 | 1411.12 | 1693.34 | 0.042 | 0.054 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70 | 0.00018 |
GUESTROOM324 | 638.71 | 766.45 | 0.019 | 0.023 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -32.70 | 0.00018 |
GUESTROOM401 | 968.45 | 1162.14 | 0.028 | 0.034 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -32.70 | 0.00018 |
GUESTROOM402_405 | 2750.85 | 3301.02 | 0.081 | 0.097 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:15:00 | -32.70 | 0.00018 |
GUESTROOM406_408 | 2340.81 | 2808.97 | 0.069 | 0.083 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -32.70 | 0.00018 |
GUESTROOM409_412 | 2770.83 | 3324.99 | 0.082 | 0.098 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -32.70 | 0.00018 |
GUESTROOM413 | 1230.57 | 1476.69 | 0.036 | 0.043 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -32.70 | 0.00018 |
GUESTROOM414 | 1182.86 | 1419.44 | 0.035 | 0.042 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:30:00 | -32.70 | 0.00018 |
GUESTROOM415_418 | 2776.91 | 3332.30 | 0.082 | 0.098 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 16:45:00 | -32.70 | 0.00018 |
GUESTROOM419 | 824.67 | 989.60 | 0.024 | 0.029 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | -32.70 | 0.00018 |
GUESTROOM420_423 | 2727.63 | 3273.16 | 0.080 | 0.096 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 19:15:00 | -32.70 | 0.00018 |
GUESTROOM424 | 1049.79 | 1259.75 | 0.031 | 0.037 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 22:30:00 | -32.70 | 0.00018 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00018 | |
CORRIDORFLR1 | 33752.52 | 40503.02 | 0.991 | 1.190 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 08:15:00 | -32.70 | 0.00018 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00018 | |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00018 | |
CORRIDORFLR2 | 995.17 | 1194.20 | 0.029 | 0.038 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 09:45:00 | -32.70 | 0.00018 |
FRONTSTAIRSFLR2 | 1.20 | 1.44 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 12:15:00 | -32.70 | 0.00018 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.000 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00018 | |
CORRIDORFLR3 | 1284.79 | 1541.74 | 0.038 | 0.045 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -32.70 | 0.00018 |
FRONTSTAIRSFLR3 | 113.52 | 136.22 | 0.002 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -32.70 | 0.00018 |
REARSTAIRSFLR4 | 32.66 | 39.20 | 0.001 | 0.006 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -32.70 | 0.00018 |
CORRIDORFLR4 | 2940.43 | 3528.52 | 0.086 | 0.104 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -32.70 | 0.00018 |
FRONTSTAIRSFLR4 | 358.96 | 430.75 | 0.007 | 0.009 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:30:00 | -32.70 | 0.00018 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
SAC_FRONTOFFICE | 0.33 | 0.33 | 0.06 | 0.06 |
SAC_FRONTLOUNGE | 0.75 | 0.75 | 0.24 | 0.24 |
SAC_MEETINGROOM | 0.35 | 0.35 | 0.13 | 0.13 |
SAC_EXC_EMPLGE_RESTRM | 0.72 | 0.72 | 0.10 | 0.10 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
SAC_FRONTLOUNGE OA CONTROLLER | DifferentialDryBulb | 0.24 | 0.75 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FRONTLOUNGEFLR1 | 3823.00 | 7887.25 | 3506.00 |
RESTROOMFLR1 | 2206.25 | 8175.00 | 2112.50 |
MEETINGROOMFLR1 | 1465.50 | 3829.50 | 1107.75 |
GUESTROOM101 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 3702.00 | 8759.00 | 3702.00 |
GUESTROOM104 | 2716.75 | 8716.25 | 2716.75 |
GUESTROOM105 | 857.00 | 8509.50 | 847.75 |
EMPLOYEELOUNGEFLR1 | 2679.00 | 2808.75 | 613.00 |
EXERCISECENTERFLR1 | 1159.00 | 3706.50 | 230.25 |
FRONTOFFICEFLR1 | 2395.50 | 6975.50 | 1900.75 |
GUESTROOM201 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 2696.75 | 8607.00 | 2691.25 |
GUESTROOM206_208 | 2525.00 | 8597.75 | 2520.00 |
GUESTROOM209_212 | 2369.50 | 8699.75 | 2369.50 |
GUESTROOM213 | 3666.75 | 8739.25 | 3666.75 |
GUESTROOM214 | 2344.50 | 8580.00 | 2338.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 2889.00 | 4874.25 | 217.00 |
GUESTROOM220_223 | 1136.50 | 8456.25 | 1111.25 |
GUESTROOM224 | 2394.75 | 8551.25 | 2387.00 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 2868.50 | 8705.25 | 2867.50 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 3105.50 | 8593.75 | 3098.50 |
GUESTROOM315_318 | 1260.00 | 8313.50 | 1205.50 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 1956.00 | 8534.25 | 1935.75 |
GUESTROOM324 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 4628.50 | 8325.75 | 4516.75 |
GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 3855.00 | 8225.00 | 3677.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 3262.25 | 7969.75 | 2906.25 |
GUESTROOM419 | 3185.50 | 8099.75 | 2993.00 |
GUESTROOM420_423 | 3344.25 | 7995.50 | 3006.75 |
GUESTROOM424 | 3942.25 | 8197.50 | 3771.50 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
Facility | 7482.25 | 8760.00 | 6513.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FRONTLOUNGEFLR1 | 1.50 | 0.00 | 1.50 | 0.00 |
RESTROOMFLR1 | 1623.00 | 201.25 | 1623.00 | 201.25 |
MEETINGROOMFLR1 | 0.25 | 0.00 | 0.25 | 0.00 |
GUESTROOM101 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM102 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM103 | 31.75 | 24.25 | 31.75 | 24.25 |
GUESTROOM104 | 22.00 | 28.25 | 22.00 | 28.25 |
GUESTROOM105 | 3.50 | 36.50 | 3.50 | 36.50 |
EMPLOYEELOUNGEFLR1 | 1152.50 | 795.50 | 810.50 | 481.25 |
EXERCISECENTERFLR1 | 0.50 | 0.00 | 0.00 | 0.00 |
FRONTOFFICEFLR1 | 0.75 | 0.00 | 0.75 | 0.00 |
GUESTROOM201 | 2.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM202_205 | 27.50 | 13.75 | 27.50 | 13.75 |
GUESTROOM206_208 | 27.00 | 20.25 | 27.00 | 20.25 |
GUESTROOM209_212 | 27.25 | 13.00 | 27.25 | 13.00 |
GUESTROOM213 | 31.75 | 13.00 | 31.75 | 13.00 |
GUESTROOM214 | 20.00 | 18.25 | 20.00 | 18.25 |
GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM219 | 0.00 | 1847.50 | 0.00 | 1847.50 |
GUESTROOM220_223 | 8.00 | 15.50 | 8.00 | 15.50 |
GUESTROOM224 | 20.50 | 18.25 | 20.50 | 18.25 |
GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM302_305 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM306_308 | 1.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM309_312 | 29.75 | 12.75 | 29.75 | 12.75 |
GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM314 | 22.75 | 17.25 | 22.75 | 17.25 |
GUESTROOM315_318 | 10.75 | 18.25 | 10.75 | 18.25 |
GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM320_323 | 17.75 | 14.75 | 17.75 | 14.75 |
GUESTROOM324 | 0.75 | 0.00 | 0.00 | 0.00 |
GUESTROOM401 | 25.25 | 20.75 | 25.25 | 20.75 |
GUESTROOM402_405 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM406_408 | 0.50 | 0.00 | 0.00 | 0.00 |
GUESTROOM409_412 | 29.75 | 18.25 | 29.75 | 18.25 |
GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
GUESTROOM414 | 0.25 | 0.00 | 0.00 | 0.00 |
GUESTROOM415_418 | 22.50 | 23.25 | 22.50 | 23.25 |
GUESTROOM419 | 19.00 | 26.75 | 19.00 | 26.75 |
GUESTROOM420_423 | 22.50 | 22.50 | 22.50 | 22.50 |
GUESTROOM424 | 13.75 | 24.25 | 13.75 | 24.25 |
REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR1 | 9.50 | 2166.25 | 0.00 | 0.00 |
FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR2 | 0.00 | 35.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR3 | 4.00 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTAIRSFLR3 | 4.00 | 0.00 | 0.00 | 0.00 |
REARSTAIRSFLR4 | 4.25 | 0.00 | 0.00 | 0.00 |
CORRIDORFLR4 | 0.00 | 95.50 | 0.00 | 0.00 |
FRONTSTAIRSFLR4 | 11.75 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1929.00 | 3236.50 | 1853.50 | 2360.50 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 10:15:38
ZoneHVAC:UnitHeaterMaximum Supply Air Flow Rate [m3/s] | |
REARSTAIRSFLR1 UNITHEATER | 0.006116 |
MECHRM UNITHEATER | 0.000000 |
FRONTSTAIRSFLR1 UNITHEATER | 0.006114 |
REARSTAIRSFLR2 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR2 UNITHEATER | 0.006114 |
REARSTAIRSFLR3 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR3 UNITHEATER | 0.006114 |
REARSTAIRSFLR4 UNITHEATER | 0.006116 |
FRONTSTAIRSFLR4 UNITHEATER | 0.008552 |
Maximum Flow Rate [m3/s] | |
REARSTAIRSFLR1UNITHEATERFAN | 0.006116 |
MECHRMUNITHEATERFAN | 0.000000 |
FRONTSTAIRSFLR1UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR2UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR2UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR3UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR3UNITHEATERFAN | 0.006114 |
REARSTAIRSFLR4UNITHEATERFAN | 0.006116 |
FRONTSTAIRSFLR4UNITHEATERFAN | 0.008552 |
SAC_FRONTOFFICE SUPPLY FAN | 0.333530 |
SAC_FRONTLOUNGE SUPPLY FAN | 0.747653 |
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN | 0.717579 |
Nominal Capacity [W] | |
REARSTAIRSFLR1UNITHEATERHEATINGCOIL | 307.99 |
CORRIDORFLR1 PTAC HEATING COIL | 43440.33 |
MECHRMUNITHEATERHEATINGCOIL | 0.000000 |
101 PTAC HEATING COIL | 1311.17 |
102 PTAC HEATING COIL | 1357.78 |
103 PTAC HEATING COIL | 1731.35 |
104 PTAC HEATING COIL | 1743.65 |
105 PTAC HEATING COIL | 1370.81 |
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL | 307.91 |
REARSTAIRSFLR2UNITHEATERHEATINGCOIL | 307.99 |
CORRIDORFLR2 PTAC HEATING COIL | 3718.56 |
201 PTAC HEATING COIL | 1514.24 |
202_205 PTAC HEATING COIL | 5244.69 |
206_208 PTAC HEATING COIL | 4156.60 |
209_212 PTAC HEATING COIL | 5244.69 |
213 PTAC HEATING COIL | 1689.50 |
214 PTAC HEATING COIL | 1661.31 |
215_218 PTAC HEATING COIL | 5244.32 |
219 PTAC HEATING COIL | 1311.08 |
220_223 PTAC HEATING COIL | 5244.32 |
224 PTAC HEATING COIL | 1524.03 |
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL | 594.96 |
REARSTAIRSFLR3UNITHEATERHEATINGCOIL | 307.99 |
CORRIDORFLR3 PTAC HEATING COIL | 3961.29 |
301 PTAC HEATING COIL | 1570.40 |
302_305 PTAC HEATING COIL | 5244.69 |
306_308 PTAC HEATING COIL | 4213.89 |
309_312 PTAC HEATING COIL | 5244.69 |
313 PTAC HEATING COIL | 1807.19 |
314 PTAC HEATING COIL | 1762.38 |
315_318 PTAC HEATING COIL | 5244.32 |
319 PTAC HEATING COIL | 1344.66 |
320_323 PTAC HEATING COIL | 5244.32 |
324 PTAC HEATING COIL | 1619.54 |
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL | 594.96 |
REARSTAIRSFLR4UNITHEATERHEATINGCOIL | 595.11 |
CORRIDORFLR4 PTAC HEATING COIL | 5948.04 |
401 PTAC HEATING COIL | 2015.29 |
402_405 PTAC HEATING COIL | 6713.62 |
406_408 PTAC HEATING COIL | 5513.58 |
409_412 PTAC HEATING COIL | 6737.60 |
413 PTAC HEATING COIL | 2329.84 |
414 PTAC HEATING COIL | 2272.53 |
415_418 PTAC HEATING COIL | 6744.66 |
419 PTAC HEATING COIL | 1842.69 |
420_423 PTAC HEATING COIL | 6685.52 |
424 PTAC HEATING COIL | 2112.84 |
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL | 717.75 |
Rated Sensible Heat Ratio | Rated Air Flow Rate [m3/s] | Rated Total Cooling Capacity (gross) [W] | |
CORRIDORFLR1 PTAC COOLING COIL | 0.730484 | ||
101 PTAC COOLING COIL | 0.730484 | ||
102 PTAC COOLING COIL | 0.730484 | ||
103 PTAC COOLING COIL | 0.730484 | ||
104 PTAC COOLING COIL | 0.730484 | ||
105 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR2 PTAC COOLING COIL | 0.730484 | ||
201 PTAC COOLING COIL | 0.730484 | ||
202_205 PTAC COOLING COIL | 0.730484 | ||
206_208 PTAC COOLING COIL | 0.730484 | ||
209_212 PTAC COOLING COIL | 0.730484 | ||
213 PTAC COOLING COIL | 0.730484 | ||
214 PTAC COOLING COIL | 0.730484 | ||
215_218 PTAC COOLING COIL | 0.730484 | ||
219 PTAC COOLING COIL | 0.730484 | ||
220_223 PTAC COOLING COIL | 0.730484 | ||
224 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR3 PTAC COOLING COIL | 0.730484 | ||
301 PTAC COOLING COIL | 0.730484 | ||
302_305 PTAC COOLING COIL | 0.730484 | ||
306_308 PTAC COOLING COIL | 0.730484 | ||
309_312 PTAC COOLING COIL | 0.730484 | ||
313 PTAC COOLING COIL | 0.730484 | ||
314 PTAC COOLING COIL | 0.730484 | ||
315_318 PTAC COOLING COIL | 0.730484 | ||
319 PTAC COOLING COIL | 0.730484 | ||
320_323 PTAC COOLING COIL | 0.730484 | ||
324 PTAC COOLING COIL | 0.730484 | ||
CORRIDORFLR4 PTAC COOLING COIL | 0.730484 | ||
401 PTAC COOLING COIL | 0.730484 | ||
402_405 PTAC COOLING COIL | 0.730484 | ||
406_408 PTAC COOLING COIL | 0.730484 | ||
409_412 PTAC COOLING COIL | 0.730484 | ||
413 PTAC COOLING COIL | 0.730484 | ||
414 PTAC COOLING COIL | 0.730484 | ||
415_418 PTAC COOLING COIL | 0.730484 | ||
419 PTAC COOLING COIL | 0.730484 | ||
420_423 PTAC COOLING COIL | 0.730484 | ||
424 PTAC COOLING COIL | 0.730484 | ||
SAC_FRONTOFFICE COOLING COIL | 0.739672 | 0.333530 | 6576.12 |
SAC_FRONTLOUNGE COOLING COIL | 0.693932 | 0.747653 | 17305.66 |
SAC_MEETINGROOM COOLING COIL | 0.676083 | 0.353599 | 8780.71 |
SAC_EXC_EMPLGE_RESTRM COOLING COIL | 0.749866 | 0.717579 | 13695.99 |
Maximum Air Flow Rate [m3/s] | |
FRONTLOUNGEFLR1 DIRECT AIR | 0.747653 |
RESTROOMFLR1 DIRECT AIR | 0.040619 |
MEETINGROOMFLR1 DIRECT AIR | 0.353599 |
EMPLOYEELOUNGEFLR1 DIRECT AIR | 0.557931 |
EXERCISECENTERFLR1 DIRECT AIR | 0.119029 |
FRONTOFFICEFLR1 DIRECT AIR | 0.333530 |
Maximum Flow Rate [m3/s] | |
SAC_FRONTOFFICE MAIN BRANCH | 0.333530 |
SAC_FRONTLOUNGE MAIN BRANCH | 0.747653 |
SAC_MEETINGROOM MAIN BRANCH | 0.353599 |
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH | 0.717579 |
Design Supply Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE | 0.333530 |
SAC_FRONTLOUNGE | 0.747653 |
SAC_MEETINGROOM | 0.353599 |
SAC_EXC_EMPLGE_RESTRM | 0.717579 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
SAC_FRONTOFFICE OA CONTROLLER | 0.333530 | 0.056300 |
SAC_FRONTLOUNGE OA CONTROLLER | 0.747653 | 0.235982 |
SAC_MEETINGROOM OA CONTROLLER | 0.353599 | 0.126367 |
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER | 0.717579 | 0.094386 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
SAC_FRONTOFFICE | 0.333530 | 0.333530 | 0.333530 | 0.333530 | 5398.83 | 6576.12 | 1.00 |
SAC_FRONTLOUNGE | 0.747653 | 0.747653 | 0.747653 | 0.747653 | 22629.09 | 17305.66 | 1.00 |
SAC_MEETINGROOM | 0.353599 | 0.353599 | 0.353599 | 0.353599 | 12117.71 | 8780.71 | 1.00 |
SAC_EXC_EMPLGE_RESTRM | 0.717579 | 0.717579 | 0.717579 | 0.717579 | 9282.00 | 13695.99 | 0.165875 |
Nominal Capacity [W] | |
SAC_FRONTOFFICE HEATING COIL | 5398.83 |
SAC_FRONTLOUNGE HEATING COIL | 22629.09 |
SAC_MEETINGROOM HEATING COIL | 12117.71 |
SAC_EXC_EMPLGE_RESTRM HEATING COIL | 9282.00 |
Maximum Flow Rate [m3/s] | |
SAC_MEETINGROOM SUPPLY FAN | 0.353599 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYSSHOWER | 0.000180 | 0.202443 |
SHWSYSLAUNDRY | 0.000129 | 0.145496 |
Use Side Design Flow Rate [m3/s] | |
SHWSYSSHOWER WATER HEATER | 0.000180 |
SHWSYSLAUNDRY WATER HEATER | 0.000129 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SHWSYSSHOWER PUMP | 0.000180 | 8.11 |
SHWSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.69 | -16.9 |
February | 14.63 | -11.6 |
March | 16.57 | -6.2 |
April | 18.63 | 3.97 |
May | 21.66 | 13.43 |
June | 22.78 | 18.03 |
July | 23.47 | 19.67 |
August | 22.84 | 17.94 |
September | 21.31 | 12.29 |
October | 19.41 | 5.42 |
November | 16.75 | -2.0 |
December | 13.86 | -14.6 |
Annual Sum or Average | 18.82 | 3.36 |
Minimum of Months | 13.69 | -16.9 |
Maximum of Months | 23.47 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | -16.9 |
February | 21.53 | -11.6 |
March | 21.93 | -6.2 |
April | 23.03 | 3.97 |
May | 24.30 | 13.43 |
June | 25.13 | 18.03 |
July | 25.56 | 19.67 |
August | 25.14 | 17.94 |
September | 24.14 | 12.29 |
October | 23.29 | 5.42 |
November | 22.25 | -2.0 |
December | 21.28 | -14.6 |
Annual Sum or Average | 23.24 | 3.36 |
Minimum of Months | 21.24 | -16.9 |
Maximum of Months | 25.56 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.49 | -16.9 |
February | 14.27 | -11.6 |
March | 16.07 | -6.2 |
April | 18.03 | 3.97 |
May | 21.11 | 13.43 |
June | 22.29 | 18.03 |
July | 22.93 | 19.67 |
August | 22.28 | 17.94 |
September | 20.72 | 12.29 |
October | 18.81 | 5.42 |
November | 16.34 | -2.0 |
December | 13.70 | -14.6 |
Annual Sum or Average | 18.36 | 3.36 |
Minimum of Months | 13.49 | -16.9 |
Maximum of Months | 22.93 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTLOUNGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -16.9 |
February | 21.11 | -11.6 |
March | 21.11 | -6.2 |
April | 21.33 | 3.97 |
May | 22.31 | 13.43 |
June | 23.00 | 18.03 |
July | 23.24 | 19.67 |
August | 23.04 | 17.94 |
September | 22.10 | 12.29 |
October | 21.32 | 5.42 |
November | 21.16 | -2.0 |
December | 21.11 | -14.6 |
Annual Sum or Average | 21.83 | 3.36 |
Minimum of Months | 21.11 | -16.9 |
Maximum of Months | 23.24 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: RESTROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -16.9 |
February | 20.82 | -11.6 |
March | 21.24 | -6.2 |
April | 21.99 | 3.97 |
May | 22.89 | 13.43 |
June | 23.33 | 18.03 |
July | 23.50 | 19.67 |
August | 23.36 | 17.94 |
September | 22.84 | 12.29 |
October | 22.20 | 5.42 |
November | 21.55 | -2.0 |
December | 20.63 | -14.6 |
Annual Sum or Average | 22.08 | 3.36 |
Minimum of Months | 20.50 | -16.9 |
Maximum of Months | 23.50 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: MEETINGROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | -16.9 |
February | 21.15 | -11.6 |
March | 21.22 | -6.2 |
April | 21.80 | 3.97 |
May | 23.08 | 13.43 |
June | 23.59 | 18.03 |
July | 23.72 | 19.67 |
August | 23.63 | 17.94 |
September | 23.05 | 12.29 |
October | 21.91 | 5.42 |
November | 21.34 | -2.0 |
December | 21.13 | -14.6 |
Annual Sum or Average | 22.23 | 3.36 |
Minimum of Months | 21.12 | -16.9 |
Maximum of Months | 23.72 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: MECHANICALROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.81 | -16.9 |
February | 23.04 | -11.6 |
March | 23.42 | -6.2 |
April | 24.28 | 3.97 |
May | 25.47 | 13.43 |
June | 25.98 | 18.03 |
July | 26.22 | 19.67 |
August | 26.05 | 17.94 |
September | 25.51 | 12.29 |
October | 24.63 | 5.42 |
November | 23.77 | -2.0 |
December | 22.95 | -14.6 |
Annual Sum or Average | 24.52 | 3.36 |
Minimum of Months | 22.81 | -16.9 |
Maximum of Months | 26.22 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM101
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.92 | -11.6 |
March | 19.01 | -6.2 |
April | 19.98 | 3.97 |
May | 21.95 | 13.43 |
June | 22.75 | 18.03 |
July | 23.02 | 19.67 |
August | 22.83 | 17.94 |
September | 21.84 | 12.29 |
October | 20.30 | 5.42 |
November | 19.22 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.64 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.02 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM102
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.90 | -11.6 |
March | 18.95 | -6.2 |
April | 19.73 | 3.97 |
May | 21.68 | 13.43 |
June | 22.54 | 18.03 |
July | 22.86 | 19.67 |
August | 22.61 | 17.94 |
September | 21.51 | 12.29 |
October | 19.97 | 5.42 |
November | 19.09 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.48 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 22.86 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM103
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.49 | -11.6 |
March | 20.53 | -6.2 |
April | 20.91 | 3.97 |
May | 21.50 | 13.43 |
June | 21.70 | 18.03 |
July | 21.73 | 19.67 |
August | 21.70 | 17.94 |
September | 21.47 | 12.29 |
October | 21.00 | 5.42 |
November | 20.63 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.05 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.73 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM104
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -16.9 |
February | 20.62 | -11.6 |
March | 20.74 | -6.2 |
April | 21.20 | 3.97 |
May | 21.61 | 13.43 |
June | 21.72 | 18.03 |
July | 21.74 | 19.67 |
August | 21.72 | 17.94 |
September | 21.61 | 12.29 |
October | 21.25 | 5.42 |
November | 20.87 | -2.0 |
December | 20.49 | -14.6 |
Annual Sum or Average | 21.17 | 3.36 |
Minimum of Months | 20.49 | -16.9 |
Maximum of Months | 21.74 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM105
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.68 | -16.9 |
February | 20.95 | -11.6 |
March | 21.12 | -6.2 |
April | 21.51 | 3.97 |
May | 21.72 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.72 | 12.29 |
October | 21.55 | 5.42 |
November | 21.26 | -2.0 |
December | 20.70 | -14.6 |
Annual Sum or Average | 21.37 | 3.36 |
Minimum of Months | 20.68 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: EMPLOYEELOUNGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | -16.9 |
February | 21.27 | -11.6 |
March | 21.65 | -6.2 |
April | 22.11 | 3.97 |
May | 22.34 | 13.43 |
June | 22.45 | 18.03 |
July | 22.41 | 19.67 |
August | 22.51 | 17.94 |
September | 22.38 | 12.29 |
October | 22.22 | 5.42 |
November | 21.92 | -2.0 |
December | 20.96 | -14.6 |
Annual Sum or Average | 21.93 | 3.36 |
Minimum of Months | 20.88 | -16.9 |
Maximum of Months | 22.51 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: LAUNDRYROOMFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 49.51 | -16.9 |
February | 49.98 | -11.6 |
March | 50.56 | -6.2 |
April | 51.28 | 3.97 |
May | 52.19 | 13.43 |
June | 52.54 | 18.03 |
July | 52.84 | 19.67 |
August | 52.69 | 17.94 |
September | 52.23 | 12.29 |
October | 51.57 | 5.42 |
November | 50.65 | -2.0 |
December | 49.57 | -14.6 |
Annual Sum or Average | 51.31 | 3.36 |
Minimum of Months | 49.51 | -16.9 |
Maximum of Months | 52.84 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 66.68 | -16.9 |
February | 66.96 | -11.6 |
March | 67.66 | -6.2 |
April | 68.37 | 3.97 |
May | 69.63 | 13.43 |
June | 70.12 | 18.03 |
July | 70.51 | 19.67 |
August | 70.25 | 17.94 |
September | 69.61 | 12.29 |
October | 68.85 | 5.42 |
November | 67.71 | -2.0 |
December | 66.73 | -14.6 |
Annual Sum or Average | 68.60 | 3.36 |
Minimum of Months | 66.68 | -16.9 |
Maximum of Months | 70.51 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: EXERCISECENTERFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | -16.9 |
February | 21.94 | -11.6 |
March | 22.32 | -6.2 |
April | 22.94 | 3.97 |
May | 23.48 | 13.43 |
June | 23.72 | 18.03 |
July | 23.81 | 19.67 |
August | 23.81 | 17.94 |
September | 23.51 | 12.29 |
October | 23.09 | 5.42 |
November | 22.55 | -2.0 |
December | 21.60 | -14.6 |
Annual Sum or Average | 22.86 | 3.36 |
Minimum of Months | 21.54 | -16.9 |
Maximum of Months | 23.81 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTOFFICEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | -16.9 |
February | 21.42 | -11.6 |
March | 21.60 | -6.2 |
April | 22.36 | 3.97 |
May | 23.39 | 13.43 |
June | 23.73 | 18.03 |
July | 23.83 | 19.67 |
August | 23.82 | 17.94 |
September | 23.44 | 12.29 |
October | 22.55 | 5.42 |
November | 21.74 | -2.0 |
December | 21.17 | -14.6 |
Annual Sum or Average | 22.53 | 3.36 |
Minimum of Months | 21.17 | -16.9 |
Maximum of Months | 23.83 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.55 | -16.9 |
February | 13.59 | -11.6 |
March | 15.80 | -6.2 |
April | 18.20 | 3.97 |
May | 21.60 | 13.43 |
June | 23.01 | 18.03 |
July | 23.84 | 19.67 |
August | 23.09 | 17.94 |
September | 21.34 | 12.29 |
October | 19.12 | 5.42 |
November | 16.08 | -2.0 |
December | 12.76 | -14.6 |
Annual Sum or Average | 18.44 | 3.36 |
Minimum of Months | 12.55 | -16.9 |
Maximum of Months | 23.84 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR1
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.31 | -16.9 |
February | 17.95 | -11.6 |
March | 19.13 | -6.2 |
April | 20.63 | 3.97 |
May | 22.65 | 13.43 |
June | 23.43 | 18.03 |
July | 23.93 | 19.67 |
August | 23.56 | 17.94 |
September | 22.61 | 12.29 |
October | 21.20 | 5.42 |
November | 19.36 | -2.0 |
December | 17.43 | -14.6 |
Annual Sum or Average | 20.78 | 3.36 |
Minimum of Months | 17.31 | -16.9 |
Maximum of Months | 23.93 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 12.90 | -16.9 |
February | 13.90 | -11.6 |
March | 16.26 | -6.2 |
April | 18.61 | 3.97 |
May | 22.21 | 13.43 |
June | 23.42 | 18.03 |
July | 24.21 | 19.67 |
August | 23.48 | 17.94 |
September | 21.75 | 12.29 |
October | 19.55 | 5.42 |
November | 16.32 | -2.0 |
December | 13.00 | -14.6 |
Annual Sum or Average | 18.83 | 3.36 |
Minimum of Months | 12.90 | -16.9 |
Maximum of Months | 24.21 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -16.9 |
February | 21.18 | -11.6 |
March | 21.36 | -6.2 |
April | 22.37 | 3.97 |
May | 23.66 | 13.43 |
June | 23.89 | 18.03 |
July | 23.90 | 19.67 |
August | 23.88 | 17.94 |
September | 23.65 | 12.29 |
October | 22.58 | 5.42 |
November | 21.47 | -2.0 |
December | 21.11 | -14.6 |
Annual Sum or Average | 22.52 | 3.36 |
Minimum of Months | 21.11 | -16.9 |
Maximum of Months | 23.90 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.81 | -16.9 |
February | 12.74 | -11.6 |
March | 14.98 | -6.2 |
April | 17.35 | 3.97 |
May | 21.23 | 13.43 |
June | 22.63 | 18.03 |
July | 23.42 | 19.67 |
August | 22.61 | 17.94 |
September | 20.68 | 12.29 |
October | 18.26 | 5.42 |
November | 15.17 | -2.0 |
December | 12.00 | -14.6 |
Annual Sum or Average | 17.77 | 3.36 |
Minimum of Months | 11.81 | -16.9 |
Maximum of Months | 23.42 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM201
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.91 | -6.2 |
April | 19.58 | 3.97 |
May | 21.87 | 13.43 |
June | 22.86 | 18.03 |
July | 23.14 | 19.67 |
August | 22.95 | 17.94 |
September | 21.53 | 12.29 |
October | 19.54 | 5.42 |
November | 18.96 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.51 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.14 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM202_205
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.52 | -11.6 |
March | 20.60 | -6.2 |
April | 21.09 | 3.97 |
May | 21.64 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.62 | 12.29 |
October | 21.13 | 5.42 |
November | 20.72 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.13 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM206_208
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -16.9 |
February | 20.54 | -11.6 |
March | 20.62 | -6.2 |
April | 21.13 | 3.97 |
May | 21.66 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.64 | 12.29 |
October | 21.18 | 5.42 |
November | 20.75 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.15 | 3.36 |
Minimum of Months | 20.48 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM209_212
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -16.9 |
February | 20.54 | -11.6 |
March | 20.63 | -6.2 |
April | 21.16 | 3.97 |
May | 21.66 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.65 | 12.29 |
October | 21.21 | 5.42 |
November | 20.77 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.16 | 3.36 |
Minimum of Months | 20.48 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM213
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.48 | -11.6 |
March | 20.52 | -6.2 |
April | 20.93 | 3.97 |
May | 21.56 | 13.43 |
June | 21.73 | 18.03 |
July | 21.75 | 19.67 |
August | 21.73 | 17.94 |
September | 21.53 | 12.29 |
October | 20.99 | 5.42 |
November | 20.60 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.07 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM214
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -16.9 |
February | 20.65 | -11.6 |
March | 20.80 | -6.2 |
April | 21.30 | 3.97 |
May | 21.69 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.68 | 12.29 |
October | 21.34 | 5.42 |
November | 20.91 | -2.0 |
December | 20.49 | -14.6 |
Annual Sum or Average | 21.22 | 3.36 |
Minimum of Months | 20.49 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM215_218
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -16.9 |
February | 21.53 | -11.6 |
March | 22.27 | -6.2 |
April | 23.06 | 3.97 |
May | 23.32 | 13.43 |
June | 23.33 | 18.03 |
July | 23.33 | 19.67 |
August | 23.33 | 17.94 |
September | 23.33 | 12.29 |
October | 23.20 | 5.42 |
November | 22.59 | -2.0 |
December | 20.97 | -14.6 |
Annual Sum or Average | 22.59 | 3.36 |
Minimum of Months | 20.81 | -16.9 |
Maximum of Months | 23.33 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 29.34 | -16.9 |
February | 29.64 | -11.6 |
March | 30.30 | -6.2 |
April | 31.19 | 3.97 |
May | 32.62 | 13.43 |
June | 33.08 | 18.03 |
July | 33.37 | 19.67 |
August | 33.15 | 17.94 |
September | 32.53 | 12.29 |
October | 31.53 | 5.42 |
November | 30.30 | -2.0 |
December | 29.35 | -14.6 |
Annual Sum or Average | 31.38 | 3.36 |
Minimum of Months | 29.34 | -16.9 |
Maximum of Months | 33.37 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM219
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.68 | -16.9 |
February | 21.72 | -11.6 |
March | 21.78 | -6.2 |
April | 21.95 | 3.97 |
May | 22.39 | 13.43 |
June | 22.70 | 18.03 |
July | 22.87 | 19.67 |
August | 22.74 | 17.94 |
September | 22.38 | 12.29 |
October | 22.00 | 5.42 |
November | 21.78 | -2.0 |
December | 21.70 | -14.6 |
Annual Sum or Average | 22.14 | 3.36 |
Minimum of Months | 21.68 | -16.9 |
Maximum of Months | 22.87 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM220_223
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | -16.9 |
February | 20.79 | -11.6 |
March | 20.94 | -6.2 |
April | 21.41 | 3.97 |
May | 21.72 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.71 | 12.29 |
October | 21.42 | 5.42 |
November | 21.05 | -2.0 |
December | 20.54 | -14.6 |
Annual Sum or Average | 21.28 | 3.36 |
Minimum of Months | 20.54 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM224
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | -16.9 |
February | 20.65 | -11.6 |
March | 20.78 | -6.2 |
April | 21.28 | 3.97 |
May | 21.69 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.68 | 12.29 |
October | 21.31 | 5.42 |
November | 20.89 | -2.0 |
December | 20.49 | -14.6 |
Annual Sum or Average | 21.21 | 3.36 |
Minimum of Months | 20.49 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 15.85 | -16.9 |
February | 16.57 | -11.6 |
March | 18.15 | -6.2 |
April | 20.08 | 3.97 |
May | 22.75 | 13.43 |
June | 23.69 | 18.03 |
July | 24.33 | 19.67 |
August | 23.79 | 17.94 |
September | 22.54 | 12.29 |
October | 20.71 | 5.42 |
November | 18.28 | -2.0 |
December | 15.93 | -14.6 |
Annual Sum or Average | 20.24 | 3.36 |
Minimum of Months | 15.85 | -16.9 |
Maximum of Months | 24.33 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR2
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.89 | -16.9 |
February | 11.95 | -11.6 |
March | 14.76 | -6.2 |
April | 17.74 | 3.97 |
May | 22.09 | 13.43 |
June | 23.72 | 18.03 |
July | 24.76 | 19.67 |
August | 23.77 | 17.94 |
September | 21.63 | 12.29 |
October | 18.86 | 5.42 |
November | 14.95 | -2.0 |
December | 11.02 | -14.6 |
Annual Sum or Average | 18.05 | 3.36 |
Minimum of Months | 10.89 | -16.9 |
Maximum of Months | 24.76 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.88 | -16.9 |
February | 12.88 | -11.6 |
March | 15.40 | -6.2 |
April | 17.97 | 3.97 |
May | 22.05 | 13.43 |
June | 23.45 | 18.03 |
July | 24.33 | 19.67 |
August | 23.49 | 17.94 |
September | 21.46 | 12.29 |
October | 18.89 | 5.42 |
November | 15.42 | -2.0 |
December | 11.96 | -14.6 |
Annual Sum or Average | 18.30 | 3.36 |
Minimum of Months | 11.88 | -16.9 |
Maximum of Months | 24.33 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -16.9 |
February | 21.11 | -11.6 |
March | 21.12 | -6.2 |
April | 21.59 | 3.97 |
May | 23.10 | 13.43 |
June | 23.67 | 18.03 |
July | 23.82 | 19.67 |
August | 23.74 | 17.94 |
September | 22.89 | 12.29 |
October | 21.54 | 5.42 |
November | 21.13 | -2.0 |
December | 21.11 | -14.6 |
Annual Sum or Average | 22.17 | 3.36 |
Minimum of Months | 21.11 | -16.9 |
Maximum of Months | 23.82 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.25 | -16.9 |
February | 11.29 | -11.6 |
March | 13.72 | -6.2 |
April | 16.37 | 3.97 |
May | 20.93 | 13.43 |
June | 22.65 | 18.03 |
July | 23.59 | 19.67 |
August | 22.62 | 17.94 |
September | 20.16 | 12.29 |
October | 17.23 | 5.42 |
November | 13.90 | -2.0 |
December | 10.46 | -14.6 |
Annual Sum or Average | 16.96 | 3.36 |
Minimum of Months | 10.25 | -16.9 |
Maximum of Months | 23.59 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM301
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.89 | -6.2 |
April | 19.31 | 3.97 |
May | 21.50 | 13.43 |
June | 22.68 | 18.03 |
July | 23.05 | 19.67 |
August | 22.78 | 17.94 |
September | 20.96 | 12.29 |
October | 19.19 | 5.42 |
November | 18.91 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.34 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.05 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM302_305
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.89 | -6.2 |
April | 19.38 | 3.97 |
May | 21.62 | 13.43 |
June | 22.74 | 18.03 |
July | 23.08 | 19.67 |
August | 22.86 | 17.94 |
September | 21.12 | 12.29 |
October | 19.26 | 5.42 |
November | 18.93 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.39 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.08 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM306_308
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.89 | -6.2 |
April | 19.44 | 3.97 |
May | 21.71 | 13.43 |
June | 22.76 | 18.03 |
July | 23.08 | 19.67 |
August | 22.85 | 17.94 |
September | 21.23 | 12.29 |
October | 19.32 | 5.42 |
November | 18.93 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.42 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.08 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM309_312
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.51 | -11.6 |
March | 20.58 | -6.2 |
April | 21.08 | 3.97 |
May | 21.63 | 13.43 |
June | 21.74 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.60 | 12.29 |
October | 21.11 | 5.42 |
November | 20.69 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.12 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM313
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.89 | -6.2 |
April | 19.35 | 3.97 |
May | 21.60 | 13.43 |
June | 22.68 | 18.03 |
July | 23.08 | 19.67 |
August | 22.80 | 17.94 |
September | 21.13 | 12.29 |
October | 19.31 | 5.42 |
November | 18.92 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.38 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.08 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM314
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.56 | -11.6 |
March | 20.66 | -6.2 |
April | 21.13 | 3.97 |
May | 21.64 | 13.43 |
June | 21.74 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.61 | 12.29 |
October | 21.17 | 5.42 |
November | 20.74 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.14 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM315_318
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.54 | -16.9 |
February | 20.79 | -11.6 |
March | 20.96 | -6.2 |
April | 21.45 | 3.97 |
May | 21.73 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.72 | 12.29 |
October | 21.45 | 5.42 |
November | 21.08 | -2.0 |
December | 20.54 | -14.6 |
Annual Sum or Average | 21.30 | 3.36 |
Minimum of Months | 20.54 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -16.9 |
February | 21.08 | -11.6 |
March | 21.94 | -6.2 |
April | 23.19 | 3.97 |
May | 25.09 | 13.43 |
June | 25.70 | 18.03 |
July | 26.01 | 19.67 |
August | 25.75 | 17.94 |
September | 24.87 | 12.29 |
October | 23.45 | 5.42 |
November | 21.93 | -2.0 |
December | 20.65 | -14.6 |
Annual Sum or Average | 23.37 | 3.36 |
Minimum of Months | 20.63 | -16.9 |
Maximum of Months | 26.01 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM319
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.00 | -16.9 |
February | 19.45 | -11.6 |
March | 20.01 | -6.2 |
April | 21.63 | 3.97 |
May | 23.05 | 13.43 |
June | 23.30 | 18.03 |
July | 23.33 | 19.67 |
August | 23.32 | 17.94 |
September | 23.03 | 12.29 |
October | 21.81 | 5.42 |
November | 20.24 | -2.0 |
December | 19.00 | -14.6 |
Annual Sum or Average | 21.44 | 3.36 |
Minimum of Months | 19.00 | -16.9 |
Maximum of Months | 23.33 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM320_323
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -16.9 |
February | 20.70 | -11.6 |
March | 20.82 | -6.2 |
April | 21.32 | 3.97 |
May | 21.69 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.67 | 12.29 |
October | 21.31 | 5.42 |
November | 20.93 | -2.0 |
December | 20.50 | -14.6 |
Annual Sum or Average | 21.23 | 3.36 |
Minimum of Months | 20.50 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM324
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.94 | -11.6 |
March | 19.05 | -6.2 |
April | 20.10 | 3.97 |
May | 22.21 | 13.43 |
June | 22.89 | 18.03 |
July | 23.16 | 19.67 |
August | 23.02 | 17.94 |
September | 22.04 | 12.29 |
October | 20.17 | 5.42 |
November | 19.07 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.71 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 23.16 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.49 | -16.9 |
February | 15.22 | -11.6 |
March | 16.95 | -6.2 |
April | 19.21 | 3.97 |
May | 22.55 | 13.43 |
June | 23.73 | 18.03 |
July | 24.50 | 19.67 |
August | 23.83 | 17.94 |
September | 22.17 | 12.29 |
October | 19.82 | 5.42 |
November | 17.03 | -2.0 |
December | 14.56 | -14.6 |
Annual Sum or Average | 19.53 | 3.36 |
Minimum of Months | 14.49 | -16.9 |
Maximum of Months | 24.50 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR3
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 9.72 | -16.9 |
February | 10.66 | -11.6 |
March | 13.63 | -6.2 |
April | 16.98 | 3.97 |
May | 21.95 | 13.43 |
June | 23.80 | 18.03 |
July | 24.97 | 19.67 |
August | 23.83 | 17.94 |
September | 21.32 | 12.29 |
October | 18.10 | 5.42 |
November | 13.80 | -2.0 |
December | 9.79 | -14.6 |
Annual Sum or Average | 17.42 | 3.36 |
Minimum of Months | 9.72 | -16.9 |
Maximum of Months | 24.97 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTAIRSFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 10.16 | -16.9 |
February | 11.20 | -11.6 |
March | 13.89 | -6.2 |
April | 16.94 | 3.97 |
May | 21.72 | 13.43 |
June | 23.47 | 18.03 |
July | 24.44 | 19.67 |
August | 23.44 | 17.94 |
September | 20.84 | 12.29 |
October | 17.65 | 5.42 |
November | 13.90 | -2.0 |
December | 10.27 | -14.6 |
Annual Sum or Average | 17.36 | 3.36 |
Minimum of Months | 10.16 | -16.9 |
Maximum of Months | 24.44 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: CORRIDORFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.11 | -16.9 |
February | 21.11 | -11.6 |
March | 21.13 | -6.2 |
April | 21.52 | 3.97 |
May | 22.70 | 13.43 |
June | 23.33 | 18.03 |
July | 23.56 | 19.67 |
August | 23.34 | 17.94 |
September | 22.33 | 12.29 |
October | 21.35 | 5.42 |
November | 21.13 | -2.0 |
December | 21.11 | -14.6 |
Annual Sum or Average | 21.98 | 3.36 |
Minimum of Months | 21.11 | -16.9 |
Maximum of Months | 23.56 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: REARSTORAGEFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.64 | -16.9 |
February | 9.92 | -11.6 |
March | 12.59 | -6.2 |
April | 15.64 | 3.97 |
May | 20.68 | 13.43 |
June | 22.66 | 18.03 |
July | 23.65 | 19.67 |
August | 22.55 | 17.94 |
September | 19.64 | 12.29 |
October | 16.30 | 5.42 |
November | 12.76 | -2.0 |
December | 8.91 | -14.6 |
Annual Sum or Average | 16.20 | 3.36 |
Minimum of Months | 8.64 | -16.9 |
Maximum of Months | 23.65 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM401
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | -16.9 |
February | 20.47 | -11.6 |
March | 20.48 | -6.2 |
April | 20.87 | 3.97 |
May | 21.54 | 13.43 |
June | 21.73 | 18.03 |
July | 21.74 | 19.67 |
August | 21.71 | 17.94 |
September | 21.43 | 12.29 |
October | 20.75 | 5.42 |
November | 20.51 | -2.0 |
December | 20.46 | -14.6 |
Annual Sum or Average | 21.02 | 3.36 |
Minimum of Months | 20.46 | -16.9 |
Maximum of Months | 21.74 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM402_405
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.90 | -6.2 |
April | 19.38 | 3.97 |
May | 21.32 | 13.43 |
June | 22.39 | 18.03 |
July | 22.77 | 19.67 |
August | 22.45 | 17.94 |
September | 20.69 | 12.29 |
October | 19.14 | 5.42 |
November | 18.92 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.23 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 22.77 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM406_408
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.90 | -6.2 |
April | 19.41 | 3.97 |
May | 21.36 | 13.43 |
June | 22.40 | 18.03 |
July | 22.76 | 19.67 |
August | 22.44 | 17.94 |
September | 20.73 | 12.29 |
October | 19.16 | 5.42 |
November | 18.92 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.24 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 22.76 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM409_412
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.49 | -11.6 |
March | 20.55 | -6.2 |
April | 21.08 | 3.97 |
May | 21.66 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.60 | 12.29 |
October | 21.02 | 5.42 |
November | 20.61 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.10 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM413
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.89 | -11.6 |
March | 18.89 | -6.2 |
April | 19.35 | 3.97 |
May | 21.34 | 13.43 |
June | 22.41 | 18.03 |
July | 22.83 | 19.67 |
August | 22.48 | 17.94 |
September | 20.74 | 12.29 |
October | 19.17 | 5.42 |
November | 18.91 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.24 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 22.83 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM414
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -16.9 |
February | 18.94 | -11.6 |
March | 19.04 | -6.2 |
April | 19.82 | 3.97 |
May | 21.72 | 13.43 |
June | 22.56 | 18.03 |
July | 22.89 | 19.67 |
August | 22.65 | 17.94 |
September | 21.32 | 12.29 |
October | 19.63 | 5.42 |
November | 18.99 | -2.0 |
December | 18.89 | -14.6 |
Annual Sum or Average | 20.45 | 3.36 |
Minimum of Months | 18.89 | -16.9 |
Maximum of Months | 22.89 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM415_418
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -16.9 |
February | 20.69 | -11.6 |
March | 20.82 | -6.2 |
April | 21.33 | 3.97 |
May | 21.71 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.67 | 12.29 |
October | 21.26 | 5.42 |
November | 20.88 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.22 | 3.36 |
Minimum of Months | 20.48 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: ELEVATORCOREFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.84 | -16.9 |
February | 18.48 | -11.6 |
March | 19.48 | -6.2 |
April | 21.00 | 3.97 |
May | 23.19 | 13.43 |
June | 24.00 | 18.03 |
July | 24.36 | 19.67 |
August | 23.96 | 17.94 |
September | 22.74 | 12.29 |
October | 21.05 | 5.42 |
November | 19.45 | -2.0 |
December | 17.92 | -14.6 |
Annual Sum or Average | 21.14 | 3.36 |
Minimum of Months | 17.84 | -16.9 |
Maximum of Months | 24.36 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM419
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -16.9 |
February | 20.65 | -11.6 |
March | 20.78 | -6.2 |
April | 21.30 | 3.97 |
May | 21.70 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.75 | 17.94 |
September | 21.67 | 12.29 |
October | 21.24 | 5.42 |
November | 20.84 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.20 | 3.36 |
Minimum of Months | 20.48 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM420_423
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.48 | -16.9 |
February | 20.68 | -11.6 |
March | 20.80 | -6.2 |
April | 21.31 | 3.97 |
May | 21.70 | 13.43 |
June | 21.75 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.66 | 12.29 |
October | 21.22 | 5.42 |
November | 20.84 | -2.0 |
December | 20.48 | -14.6 |
Annual Sum or Average | 21.20 | 3.36 |
Minimum of Months | 20.48 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: GUESTROOM424
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | -16.9 |
February | 20.55 | -11.6 |
March | 20.64 | -6.2 |
April | 21.13 | 3.97 |
May | 21.66 | 13.43 |
June | 21.74 | 18.03 |
July | 21.75 | 19.67 |
August | 21.74 | 17.94 |
September | 21.60 | 12.29 |
October | 21.06 | 5.42 |
November | 20.66 | -2.0 |
December | 20.47 | -14.6 |
Annual Sum or Average | 21.13 | 3.36 |
Minimum of Months | 20.47 | -16.9 |
Maximum of Months | 21.75 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTORAGEFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.35 | -16.9 |
February | 14.27 | -11.6 |
March | 16.15 | -6.2 |
April | 18.76 | 3.97 |
May | 22.37 | 13.43 |
June | 23.69 | 18.03 |
July | 24.44 | 19.67 |
August | 23.66 | 17.94 |
September | 21.76 | 12.29 |
October | 19.16 | 5.42 |
November | 16.21 | -2.0 |
December | 13.48 | -14.6 |
Annual Sum or Average | 18.97 | 3.36 |
Minimum of Months | 13.35 | -16.9 |
Maximum of Months | 24.44 | 19.67 |
Report: MONTHLY INDOOR TEMP
For: FRONTSTAIRSFLR4
Timestamp: 2018-10-19 10:15:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.71 | -16.9 |
February | 9.66 | -11.6 |
March | 12.52 | -6.2 |
April | 16.29 | 3.97 |
May | 21.72 | 13.43 |
June | 23.81 | 18.03 |
July | 24.98 | 19.67 |
August | 23.71 | 17.94 |
September | 20.83 | 12.29 |
October | 17.21 | 5.42 |
November | 12.65 | -2.0 |
December | 8.80 | -14.6 |
Annual Sum or Average | 16.78 | 3.36 |
Minimum of Months | 8.71 | -16.9 |
Maximum of Months | 24.98 | 19.67 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:38
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.261766E+12 | 197202.237 | 05-JAN-07:15 | 15177.258 | 39465.561 | 8751.007 | 129607.002 | 5.295 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.203650E+12 | 188693.280 | 14-FEB-07:15 | 15177.258 | 39465.561 | 8735.259 | 121081.648 | 37.441 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.186267E+12 | 171618.357 | 05-MAR-07:15 | 15140.050 | 39465.561 | 8720.606 | 108213.373 | 70.655 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.138657E+12 | 123022.687 | 05-APR-06:15 | 15177.258 | 39465.561 | 8696.868 | 59491.528 | 183.358 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.136180E+12 | 89475.409 | 26-MAY-07:00 | 17492.219 | 43276.576 | 9092.551 | 0.000 | 19605.950 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.142008E+12 | 98128.391 | 30-JUN-07:00 | 17492.219 | 43276.576 | 9092.551 | 0.000 | 28258.932 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.153404E+12 | 95350.472 | 29-JUL-07:00 | 17566.637 | 43276.576 | 9092.551 | 0.000 | 25406.596 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.147014E+12 | 87242.806 | 26-AUG-07:00 | 17492.219 | 43276.576 | 9092.551 | 0.000 | 17373.348 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.130301E+12 | 87509.974 | 01-SEP-07:00 | 17789.888 | 43276.576 | 9092.551 | 0.000 | 17342.846 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.138284E+12 | 118870.147 | 30-OCT-06:15 | 15177.258 | 39465.561 | 8696.481 | 51131.886 | 202.847 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.167739E+12 | 151347.052 | 25-NOV-07:15 | 13316.689 | 34010.661 | 8712.992 | 91034.296 | 76.302 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.250694E+12 | 193539.315 | 24-DEC-07:00 | 15177.258 | 39465.561 | 8743.927 | 125941.777 | 14.679 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.205596E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.130301E+12 | 87242.806 | 13316.689 | 34010.661 | 8696.481 | 0.000 | 5.295 | 0.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.261766E+12 | 197202.237 | 17789.888 | 43276.576 | 9092.551 | 129607.002 | 28258.932 | 4188.000 | 8.113 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 10:15:38
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC {AT MAX/MIN} [W] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.157469E+12 | 137012.788 | 06-JAN-09:15 | 32547.538 | 40096.028 | 0.000 | 64369.222 | 64369.222 | 64369.222 | 32547.538 |
February | 0.133240E+12 | 131583.981 | 17-FEB-09:15 | 25639.348 | 40096.028 | 0.000 | 65848.605 | 65848.605 | 65848.605 | 25639.348 |
March | 0.135184E+12 | 124773.042 | 15-MAR-08:30 | 20568.078 | 40096.028 | 0.000 | 64108.936 | 64108.936 | 64108.936 | 20568.078 |
April | 0.110879E+12 | 112779.934 | 05-APR-09:45 | 11847.893 | 40096.028 | 0.000 | 60836.013 | 60836.013 | 60836.013 | 11847.893 |
May | 0.101316E+12 | 103690.237 | 01-MAY-08:15 | 796.689 | 40096.028 | 0.000 | 62797.520 | 62797.520 | 62797.520 | 796.689 |
June | 0.928988E+11 | 100982.007 | 02-JUN-08:15 | 0.000 | 40096.028 | 0.000 | 60885.979 | 60885.979 | 60885.979 | 0.000 |
July | 0.926102E+11 | 98881.168 | 01-JUL-08:15 | 0.000 | 40096.028 | 0.000 | 58785.140 | 58785.140 | 58785.140 | 0.000 |
August | 0.910320E+11 | 96762.981 | 26-AUG-08:15 | 0.000 | 40096.028 | 0.000 | 56666.953 | 56666.953 | 56666.953 | 0.000 |
September | 0.898507E+11 | 97395.726 | 30-SEP-08:15 | 0.000 | 40096.028 | 0.000 | 57299.698 | 57299.698 | 57299.698 | 0.000 |
October | 0.101767E+12 | 103445.928 | 12-OCT-09:15 | 6875.620 | 40096.028 | 0.000 | 56474.281 | 56474.281 | 56474.281 | 6875.620 |
November | 0.115527E+12 | 120746.966 | 25-NOV-10:00 | 20628.307 | 40096.028 | 0.000 | 60022.630 | 60022.630 | 60022.630 | 20628.307 |
December | 0.149787E+12 | 131872.152 | 24-DEC-09:30 | 29574.795 | 40096.028 | 0.000 | 62201.329 | 62201.329 | 62201.329 | 29574.795 |
Annual Sum or Average | 0.137156E+13 | 0.000 | ||||||||
Minimum of Months | 0.898507E+11 | 96762.981 | 0.000 | 40096.028 | 0.000 | 56474.281 | 56474.281 | 56474.281 | 0.000 | |
Maximum of Months | 0.157469E+12 | 137012.788 | 32547.538 | 40096.028 | 0.000 | 65848.605 | 65848.605 | 65848.605 | 32547.538 |