Table of Contents

Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14

Tabular Output Report in Format: HTML

Building: Small Hotel

Environment: Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2018-10-19 10:15:34


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 2887.76 719.50 775.22
Net Site Energy 2887.76 719.50 775.22
Total Source Energy 7203.53 1794.79 1933.79
Net Source Energy 7203.53 1794.79 1933.79


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 4013.58
Net Conditioned Building Area 3725.09
Unconditioned Building Area 288.49


End Uses

Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 11.45 6.69 0.00 0.00 0.00 0.00
Cooling 587.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65.79 0.00 0.00 0.00 0.00 0.00
Interior Equipment 591.01 421.49 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 281.66 0.00 0.00 0.00 0.00 0.00
Pumps 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 504.13 0.00 0.00 0.00 2578.25
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 1955.45 932.31 0.00 0.00 0.00 2578.25
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Additional Fuel [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 11.45 6.69 0.00 0.00 0.00 0.00
Cooling General 587.04 0.00 0.00 0.00 0.00 0.00
Interior Lighting General Lights 418.24 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 65.79 0.00 0.00 0.00 0.00 0.00
Interior Equipment General 562.54 0.00 0.00 0.00 0.00 0.00
  ELECTRIC EQUIPMENT#Laundry#05 28.48 0.00 0.00 0.00 0.00 0.00
  GAS EQUIPMENT#Laundry#05 0.00 421.49 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 281.66 0.00 0.00 0.00 0.00 0.00
Pumps General 0.26 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 504.13 0.00 0.00 0.00 0.00
  General 0.00 0.00 0.00 0.00 0.00 2578.25
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 129.94 0.00 0.00 0.00 0.00 0.00
HVAC 236.34 137.13 0.00 0.00 0.00 0.69
Other 158.66 113.15 0.00 0.00 0.00 0.00
Total 524.94 250.28 0.00 0.00 0.00 0.69


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Additional Fuel Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 120.60 0.00 0.00 0.00 0.00 0.00
HVAC 219.36 127.27 0.00 0.00 0.00 0.64
Other 147.25 105.02 0.00 0.00 0.00 0.00
Total 487.21 232.29 0.00 0.00 0.00 0.64


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.00 0.00
High Temperature Geothermal* 0.00 0.00
Photovoltaic Power 0.00 0.00
Wind Power 0.00 0.00
Net Decrease in On-Site Storage 0.00 0.00
Total On-Site Electric Sources 0.00 0.00
     
Electricity Coming From Utility 1955.45 100.00
Surplus Electricity Going To Utility 0.00 0.00
Net Electricity From Utility 1955.45 100.00
     
Total On-Site and Utility Electric Sources 1955.45 100.00
Total Electricity End Uses 1955.45 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 2578.25 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 2578.25 100.00
Total Water End Uses 2578.25 100.00


Comfort and Setpoint Not Met Summary

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.20
Tolerance for Zone Cooling Setpoint Not Met Time 0.20


Facility [Hours]
Time Setpoint Not Met During Occupied Heating 191.25
Time Setpoint Not Met During Occupied Cooling 5428.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 6734.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.


Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Component Sizing Summary
Climatic Data Summary
Envelope Summary
Equipment Summary
HVAC Sizing Summary
System Summary

MONTHLY INDOOR TEMP

| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |

PEAK ELECTRICAL DEMAND

| Meter |

PEAK GAS DEMAND

| Meter |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

General

Value
Program Version and Build EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 10:14
RunPeriod Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 180.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1694.58 635.46 211.83 635.46 211.83
Window Opening Area [m2] 184.20 96.82 8.38 72.38 6.62
Window-Wall Ratio [%] 10.87 15.24 3.95 11.39 3.13


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 1492.32 607.21 211.83 556.77 116.50
Window Opening Area [m2] 179.26 96.82 8.38 67.45 6.62
Window-Wall Ratio [%] 12.01 15.95 3.95 12.11 5.68


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 1003.40
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Gross Wall Area [m2] Window Glass Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
REARSTAIRSFLR1 20.07 Yes Yes 67.30 1.00 35.77 0.00 7.4271   0.0000
CORRIDORFLR1 150.51 Yes Yes 504.62 1.00 32.70 9.82 8.5250   0.0000
REARSTORAGEFLR1 20.07 No Yes 67.30 1.00 35.77 0.00 6.7813   0.0000
FRONTLOUNGEFLR1 163.06 Yes Yes 546.70 1.00 94.02 14.83 11.4097 3.08 26.0600
RESTROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.5486 32.61 0.0000
MEETINGROOMFLR1 80.27 Yes Yes 269.14 1.00 32.70 4.94 13.2396 1.87 6.1800
MECHANICALROOMFLR1 32.61 Yes Yes 109.34 1.00 13.29 0.00 10.2257   0.0000
GUESTROOM101 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM102 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM103 32.61 Yes Yes 109.34 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM104 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
GUESTROOM105 32.61 Yes Yes 109.33 1.00 13.29 1.65 8.0729 21.74 11.8935
EMPLOYEELOUNGEFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 7.8577 1.81 21.5100
LAUNDRYROOMFLR1 97.83 No Yes 327.99 1.00 39.86 4.94 6.4583 8.89 437.5596
ELEVATORCOREFLR1 15.05 No Yes 50.46 1.00 6.13 0.00 0.0000   2147.5789
EXERCISECENTERFLR1 32.61 Yes Yes 109.33 1.00 13.29 1.65 9.3000 4.66 18.5900
FRONTOFFICEFLR1 130.44 Yes Yes 437.33 1.00 53.14 6.58 11.9479 13.04 13.7800
FRONTSTAIRSFLR1 20.07 Yes Yes 67.28 1.00 35.77 0.00 7.4271   0.0000
FRONTSTORAGEFLR1 12.54 No Yes 42.05 1.00 5.11 0.00 6.7813   0.0000
REARSTAIRSFLR2 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR2 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR2 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM201 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM202_205 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM206_208 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM209_212 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM213 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM214 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM215_218 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR2 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM219 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM220_223 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM224 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR2 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR2 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR3 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR3 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR3 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM301 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM302_305 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM306_308 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM309_312 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM313 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM314 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM315_318 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR3 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM319 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM320_323 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM324 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR3 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR3 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
REARSTAIRSFLR4 20.07 Yes Yes 55.06 1.00 29.27 0.00 7.4271   0.0000
CORRIDORFLR4 125.42 Yes Yes 344.05 1.00 18.39 2.62 8.5250   0.0000
REARSTORAGEFLR4 20.07 No Yes 55.07 1.00 29.27 0.00 6.7813   0.0000
GUESTROOM401 32.61 Yes Yes 89.46 1.00 33.45 1.65 8.0729 21.74 11.8935
GUESTROOM402_405 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM406_408 105.36 Yes Yes 289.02 1.00 35.12 6.70 8.0729 23.41 11.8935
GUESTROOM409_412 130.45 Yes Yes 357.84 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM413 32.61 Yes Yes 89.46 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM414 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM415_418 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
ELEVATORCOREFLR4 15.05 No Yes 41.29 1.00 5.02 0.00 0.0000   0.0000
GUESTROOM419 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
GUESTROOM420_423 130.44 Yes Yes 357.81 1.00 43.48 6.58 8.0729 21.74 11.8935
GUESTROOM424 32.61 Yes Yes 89.45 1.00 10.87 1.65 8.0729 21.74 11.8935
FRONTSTORAGEFLR4 12.54 No Yes 34.40 1.00 4.18 0.00 6.7813   0.0000
FRONTSTAIRSFLR4 20.07 Yes Yes 55.05 1.00 29.26 0.00 7.4271   0.0000
Total 4013.58     11621.73   1694.58 184.20 8.3147 15.53 28.1818
Conditioned Total 3725.09     10741.65   1492.32 179.26 8.5515 15.05 10.1966
Unconditioned Total 288.49     880.07   202.26 4.94 5.2567 26.23 260.4149
Not Part of Total 0.00     0.00   0.00 0.00      



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
W_REARSTAIRSFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
S_REARSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_CORRIDORFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 270.00 90.00 W
W_CORRIDORFLR1_10_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 180.00 90.00 S
W_CORRIDORFLR1_16_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 90.00 90.00 E
W_CORRIDORFLR1_20_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 10.22 0.00 90.00 N
S_CORRIDORFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 150.51 180.00 180.00  
W_REARSTORAGEFLR1_2_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 270.00 90.00 W
W_REARSTORAGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 0.00 90.00 N
S_REARSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTLOUNGEFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
W_FRONTLOUNGEFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 66.43 0.00 90.00 N
S_FRONTLOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 163.06 180.00 180.00  
W_RESTROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_RESTROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_MEETINGROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 32.70 0.00 90.00 N
S_MEETINGROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 80.27 180.00 180.00  
W_MECHANICALROOMFLR1_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_MECHANICALROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM101_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM101_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM102_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM102_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM103_5_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 0.00 90.00 N
S_GUESTROOM103_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM104_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM104_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_GUESTROOM105_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_GUESTROOM105_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_EMPLOYEELOUNGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EMPLOYEELOUNGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_LAUNDRYROOMFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 39.86 180.00 90.00 S
S_LAUNDRYROOMFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 97.83 180.00 180.00  
W_ELEVATORCOREFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 6.13 180.00 90.00 S
S_ELEVATORCOREFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 15.05 180.00 180.00  
W_EXERCISECENTERFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 13.29 180.00 90.00 S
S_EXERCISECENTERFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 32.61 180.00 180.00  
W_FRONTOFFICEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 53.14 180.00 90.00 S
S_FRONTOFFICEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 130.44 180.00 180.00  
W_FRONTSTAIRSFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 8.18 180.00 90.00 S
W_FRONTSTAIRSFLR1_4_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 27.59 90.00 90.00 E
S_FRONTSTAIRSFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 20.07 180.00 180.00  
W_FRONTSTORAGEFLR1_3_0_0 NONRES_EXT_WALL 0.30 0.704 0.787 5.11 180.00 90.00 S
S_FRONTSTORAGEFLR1_0_0_0 EXT_SLAB_8IN_WITH_CARPET 0.30 1.827 3.285 12.54 180.00 180.00  
W_REARSTAIRSFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR2_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR2_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR2_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR2_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM201_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM201_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM202_205_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM206_208_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM209_212_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM213_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM214_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM215_218_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM219_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM220_223_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM224_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR2_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR2_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_CORRIDORFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR3_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR3_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
W_REARSTORAGEFLR3_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR3_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
W_GUESTROOM301_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM301_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM302_305_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM306_308_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
W_GUESTROOM309_312_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
W_GUESTROOM313_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
W_GUESTROOM314_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM315_318_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_ELEVATORCOREFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
W_GUESTROOM319_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_GUESTROOM320_323_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
W_GUESTROOM324_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
W_FRONTSTORAGEFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
W_FRONTSTAIRSFLR3_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR3_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_REARSTAIRSFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
R_REARSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_CORRIDORFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 270.00 90.00 W
W_CORRIDORFLR4_9_0_0 RES_EXT_WALL 0.30 0.363 0.384 8.36 180.00 90.00 S
W_CORRIDORFLR4_15_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 90.00 90.00 E
R_CORRIDORFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 125.42 0.00 0.00  
W_REARSTORAGEFLR4_2_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 270.00 90.00 W
W_REARSTORAGEFLR4_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 0.00 90.00 N
R_REARSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  
W_GUESTROOM401_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
W_GUESTROOM401_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM401_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM402_405_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM402_405_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM406_408_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 35.12 0.00 90.00 N
R_GUESTROOM406_408_1_0_0 RES_ROOF 0.55 0.269 0.283 105.36 0.00 0.00  
W_GUESTROOM409_412_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 0.00 90.00 N
R_GUESTROOM409_412_1_0_0 RES_ROOF 0.55 0.269 0.283 130.45 0.00 0.00  
W_GUESTROOM413_5_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 0.00 90.00 N
R_GUESTROOM413_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM414_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM414_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM415_418_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM415_418_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_ELEVATORCOREFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 5.02 180.00 90.00 S
R_ELEVATORCOREFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 15.05 0.00 0.00  
W_GUESTROOM419_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM419_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_GUESTROOM420_423_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 43.48 180.00 90.00 S
R_GUESTROOM420_423_1_0_0 RES_ROOF 0.55 0.269 0.283 130.44 0.00 0.00  
W_GUESTROOM424_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 10.87 180.00 90.00 S
R_GUESTROOM424_1_0_0 RES_ROOF 0.55 0.269 0.283 32.61 0.00 0.00  
W_FRONTSTORAGEFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 4.18 180.00 90.00 S
R_FRONTSTORAGEFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 12.54 0.00 0.00  
W_FRONTSTAIRSFLR4_3_0_0 RES_EXT_WALL 0.30 0.363 0.384 6.69 180.00 90.00 S
W_FRONTSTAIRSFLR4_4_0_0 RES_EXT_WALL 0.30 0.363 0.384 22.58 90.00 90.00 E
R_FRONTSTAIRSFLR4_1_0_0 RES_ROOF 0.55 0.269 0.283 20.07 0.00 0.00  


Exterior Fenestration

Construction Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
W_CORRIDORFLR1_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 4.600 0.293 0.130     No W_CORRIDORFLR1_2_0_0 270.00 90.00 W
D_CORRIDORFLR1_16_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 4.44 0.00 0.00 4.44 4.44 4.600 0.293 0.130     No W_CORRIDORFLR1_16_0_0 90.00 90.00 E
W_CORRIDORFLR1_20_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.69 0.00 0.00 2.69 2.69 4.600 0.293 0.130     No W_CORRIDORFLR1_20_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_FRONTLOUNGEFLR1_5_0_0_0_4 WINDOW_U_0.72_SHGC_0.25 2.97 0.00 0.00 2.97 2.97 4.600 0.293 0.130     No W_FRONTLOUNGEFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_MEETINGROOMFLR1_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_MEETINGROOMFLR1_5_0_0 0.00 90.00 N
W_GUESTROOM101_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM101_5_0_0 0.00 90.00 N
W_GUESTROOM102_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM102_5_0_0 0.00 90.00 N
W_GUESTROOM103_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM103_5_0_0 0.00 90.00 N
W_GUESTROOM104_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM104_3_0_0 180.00 90.00 S
W_GUESTROOM105_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM105_3_0_0 180.00 90.00 S
W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_EMPLOYEELOUNGEFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_LAUNDRYROOMFLR1_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_LAUNDRYROOMFLR1_3_0_0 180.00 90.00 S
W_EXERCISECENTERFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_EXERCISECENTERFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_FRONTOFFICEFLR1_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_FRONTOFFICEFLR1_3_0_0 180.00 90.00 S
W_CORRIDORFLR2_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR2_2_0_0 270.00 90.00 W
W_CORRIDORFLR2_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR2_15_0_0 90.00 90.00 E
W_GUESTROOM201_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM201_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM202_205_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM202_205_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM206_208_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM206_208_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM209_212_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM209_212_5_0_0 0.00 90.00 N
W_GUESTROOM213_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM213_5_0_0 0.00 90.00 N
W_GUESTROOM214_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM214_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM215_218_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM215_218_3_0_0 180.00 90.00 S
W_GUESTROOM219_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM219_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM220_223_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM220_223_3_0_0 180.00 90.00 S
W_GUESTROOM224_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM224_3_0_0 180.00 90.00 S
W_CORRIDORFLR3_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR3_2_0_0 270.00 90.00 W
W_CORRIDORFLR3_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR3_15_0_0 90.00 90.00 E
W_GUESTROOM301_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM301_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM302_305_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM302_305_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM306_308_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM306_308_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM309_312_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM309_312_5_0_0 0.00 90.00 N
W_GUESTROOM313_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM313_5_0_0 0.00 90.00 N
W_GUESTROOM314_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM314_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM315_318_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM315_318_3_0_0 180.00 90.00 S
W_GUESTROOM319_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM319_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM320_323_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM320_323_3_0_0 180.00 90.00 S
W_GUESTROOM324_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM324_3_0_0 180.00 90.00 S
W_CORRIDORFLR4_2_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR4_2_0_0 270.00 90.00 W
W_CORRIDORFLR4_15_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.31 0.00 0.00 1.31 1.31 4.600 0.293 0.130     No W_CORRIDORFLR4_15_0_0 90.00 90.00 E
W_GUESTROOM401_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM401_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM402_405_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM402_405_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM406_408_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 3.41 0.00 0.00 3.41 3.41 4.600 0.293 0.130     No W_GUESTROOM406_408_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM409_412_5_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM409_412_5_0_0 0.00 90.00 N
W_GUESTROOM413_5_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM413_5_0_0 0.00 90.00 N
W_GUESTROOM414_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM414_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM415_418_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM415_418_3_0_0 180.00 90.00 S
W_GUESTROOM419_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM419_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_1 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_2 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM420_423_3_0_0_0_3 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM420_423_3_0_0 180.00 90.00 S
W_GUESTROOM424_3_0_0_0_0 WINDOW_U_0.72_SHGC_0.25 1.65 0.00 0.00 1.65 1.65 4.600 0.293 0.130     No W_GUESTROOM424_3_0_0 180.00 90.00 S
Total or Average           184.20 4.600 0.293 0.130              
North Total or Average           96.82 4.600 0.293 0.130              
Non-North Total or Average           87.38 4.600 0.293 0.130              


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
W_REARSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_REARSTAIRSFLR1_3_0_0
W_CORRIDORFLR1_10_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_CORRIDORFLR1_10_0_0
W_FRONTSTAIRSFLR1_3_0_0_DOOR SWINGING DOOR_CON 3.975 3.975 1.95 W_FRONTSTAIRSFLR1_3_0_0



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

Central Plant

Type Nominal Capacity [W] Nominal Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   7913.25 5780.50 2132.75 0.73 3.73    
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   10551.00 7707.33 2843.67 0.73 3.73    
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed   2637.75 1926.83 710.92 0.73 3.73    
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed   7935.19 5504.79 2430.40 0.69 3.91    
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed   19790.13 13379.78 6410.36 0.68 3.80    
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed   9034.48 6108.06 2926.42 0.68 3.91    
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed   15609.46 10985.24 4624.22 0.70 3.91    


DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
CORRIDORFLR1 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
101 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
102 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
103 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
104 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
105 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR2 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
201 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
202_205 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
206_208 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
209_212 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
213 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
214 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
215_218 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
219 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
220_223 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
224 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR3 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
301 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
302_305 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
306_308 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
309_312 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
313 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
314 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
315_318 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
319 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
320_323 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
324 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
CORRIDORFLR4 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
401 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
402_405 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
406_408 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 7610.9 3.14 10.72 11.36 10.75
409_412 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
413 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
414 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
415_418 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
419 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
420_423 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 10147.8 3.14 10.72 11.36 10.75
424 PTAC COOLING COIL Coil:Cooling:DX:SingleSpeed 2537.0 3.14 10.72 11.36 10.75
SAC_FRONTOFFICE COOLING COIL Coil:Cooling:DX:SingleSpeed 7669.0 3.34 11.41 12.10 11.52
SAC_FRONTLOUNGE COOLING COIL Coil:Cooling:DX:SingleSpeed 19170.7 3.29 11.23 11.91 11.42
SAC_MEETINGROOM COOLING COIL Coil:Cooling:DX:SingleSpeed 8751.7 3.38 11.52 12.22 11.70
SAC_EXC_EMPLGE_RESTRM COOLING COIL Coil:Cooling:DX:SingleSpeed 15066.0 3.32 11.34 12.03 11.42
ANSI/AHRI ratings include supply fan

DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.13 1.00
CORRIDORFLR1 PTAC HEATING COIL Coil:Heating:Electric   17771.40 1.00
MECHRMUNITHEATERHEATINGCOIL Coil:Heating:Electric   0.00 1.00
101 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
102 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
103 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
104 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
105 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.05 1.00
REARSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.13 1.00
CORRIDORFLR2 PTAC HEATING COIL Coil:Heating:Electric   2128.50 1.00
201 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
202_205 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
206_208 PTAC HEATING COIL Coil:Heating:Electric   2379.23 1.00
209_212 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
213 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
214 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
215_218 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
219 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
220_223 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
224 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.05 1.00
REARSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.13 1.00
CORRIDORFLR3 PTAC HEATING COIL Coil:Heating:Electric   2128.50 1.00
301 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
302_305 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
306_308 PTAC HEATING COIL Coil:Heating:Electric   2379.23 1.00
309_312 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
313 PTAC HEATING COIL Coil:Heating:Electric   750.51 1.00
314 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
315_318 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
319 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
320_323 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
324 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.05 1.00
REARSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.13 1.00
CORRIDORFLR4 PTAC HEATING COIL Coil:Heating:Electric   2128.50 1.00
401 PTAC HEATING COIL Coil:Heating:Electric   754.29 1.00
402_405 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
406_408 PTAC HEATING COIL Coil:Heating:Electric   2379.23 1.00
409_412 PTAC HEATING COIL Coil:Heating:Electric   3002.06 1.00
413 PTAC HEATING COIL Coil:Heating:Electric   819.06 1.00
414 PTAC HEATING COIL Coil:Heating:Electric   770.25 1.00
415_418 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
419 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
420_423 PTAC HEATING COIL Coil:Heating:Electric   3001.84 1.00
424 PTAC HEATING COIL Coil:Heating:Electric   750.46 1.00
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL Coil:Heating:Electric   321.05 1.00
SAC_FRONTOFFICE HEATING COIL Coil:Heating:Gas   3090.28 0.80
SAC_FRONTLOUNGE HEATING COIL Coil:Heating:Gas   12952.86 0.80
SAC_MEETINGROOM HEATING COIL Coil:Heating:Gas   6936.16 0.80
SAC_EXC_EMPLGE_RESTRM HEATING COIL Coil:Heating:Gas   5221.12 0.80


Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction End Use
REARSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR1 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
MECHRMUNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.00 0.00   1.00 General
101 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
102 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
103 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
104 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
105 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR1UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR2 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
201 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
202_205 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
206_208 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
209_212 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
213 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
214 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
215_218 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
219 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
220_223 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
224 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR2UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR3 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
301 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
302_305 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
306_308 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
309_312 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
313 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
314 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
315_318 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
319 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
320_323 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
324 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR3UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
REARSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
CORRIDORFLR4 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
401 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
402_405 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
406_408 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.39 248.38 636.87 1.00 General
409_412 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
413 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
414 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
415_418 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
419 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
420_423 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.52 331.17 636.87 1.00 General
424 PTAC SUPPLY FAN Fan:OnOff 0.52 331.17 0.13 82.79 636.87 1.00 General
FRONTSTAIRSFLR4UNITHEATERFAN Fan:ConstantVolume 0.54 49.80 0.01 0.57 92.91 1.00 General
SAC_FRONTOFFICE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.34 383.69 1120.11 1.00 General
SAC_FRONTLOUNGE SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.80 882.35 1107.16 1.00 General
SAC_MEETINGROOM SUPPLY FAN Fan:OnOff 0.56 622.50 0.36 407.52 1120.11 1.00 General
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN Fan:ConstantVolume 0.56 622.50 0.70 783.59 1120.11 1.00 General


Pumps

Type Control Head [pa] Water Flow [m3/s] Electric Power [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W]
SHWSYSSHOWER PUMP Pump:ConstantSpeed Intermittent 29891.00 0.0002 8.11 45084.46 0.85
SHWSYSLAUNDRY PUMP Pump:ConstantSpeed Intermittent 0.00 0.0001 0.00 0.00 0.30


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SHWSYSSHOWER WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.00 0.00
SHWSYSLAUNDRY WATER HEATER WaterHeater:Mixed 0.76 58614.21 0.81 0.80 0.51



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

Zone Cooling

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 8048.18 9657.82 0.664 0.797 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90 0.01651
RESTROOMFLR1 472.43 566.92 0.039 0.047 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:45:00 32.95 0.01651
MEETINGROOMFLR1 3671.82 4406.18 0.303 0.364 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90 0.01651
GUESTROOM101 628.16 753.79 0.072 0.086 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 33.54 0.01651
GUESTROOM102 523.38 628.06 0.060 0.072 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 33.54 0.01651
GUESTROOM103 1143.91 1372.70 0.131 0.157 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 31.71 0.01651
GUESTROOM104 1297.64 1557.16 0.149 0.179 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 33.78 0.01651
GUESTROOM105 1605.66 1926.79 0.184 0.221 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
EMPLOYEELOUNGEFLR1 5368.26 6441.91 0.443 0.532 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90 0.01651
EXERCISECENTERFLR1 1224.33 1469.20 0.101 0.121 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79 0.01651
FRONTOFFICEFLR1 3462.09 4154.51 0.285 0.343 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM201 824.24 989.09 0.095 0.113 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:15:00 33.60 0.01651
GUESTROOM202_205 4165.43 4998.52 0.478 0.573 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66 0.01651
GUESTROOM206_208 3375.65 4050.78 0.387 0.464 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:15:00 33.78 0.01651
GUESTROOM209_212 3965.98 4759.17 0.455 0.546 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66 0.01651
GUESTROOM213 1134.03 1360.83 0.130 0.156 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:30:00 33.11 0.01651
GUESTROOM214 1335.23 1602.28 0.153 0.184 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM215_218 9441.47 11329.76 1.082 1.299 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM219 5353.57 6424.29 0.614 0.736 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM220_223 4589.45 5507.34 0.526 0.631 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 33.90 0.01651
GUESTROOM224 1323.41 1588.10 0.152 0.182 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM301 632.83 759.40 0.073 0.087 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 33.70 0.01651
GUESTROOM302_305 1562.56 1875.07 0.179 0.215 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 33.54 0.01651
GUESTROOM306_308 1379.13 1654.96 0.158 0.190 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66 0.01651
GUESTROOM309_312 3888.71 4666.45 0.446 0.535 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:45:00 33.54 0.01651
GUESTROOM313 623.84 748.60 0.072 0.086 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79 0.01651
GUESTROOM314 1244.21 1493.05 0.143 0.171 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM315_318 4940.01 5928.01 0.566 0.680 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM319 1094.26 1313.11 0.125 0.151 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM320_323 4345.90 5215.08 0.498 0.598 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM324 747.58 897.10 0.086 0.103 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM401 1424.43 1709.31 0.163 0.196 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:30:00 33.70 0.01651
GUESTROOM402_405 2166.33 2599.60 0.248 0.298 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM406_408 1872.56 2247.07 0.215 0.258 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM409_412 4796.53 5755.83 0.550 0.660 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM413 840.91 1009.09 0.096 0.116 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66 0.01651
GUESTROOM414 975.75 1170.90 0.112 0.134 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
GUESTROOM415_418 5392.74 6471.28 0.618 0.742 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 33.90 0.01651
GUESTROOM419 1483.30 1779.96 0.170 0.204 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:30:00 33.90 0.01651
GUESTROOM420_423 5363.00 6435.60 0.615 0.738 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:15:00 33.90 0.01651
GUESTROOM424 1526.26 1831.52 0.175 0.210 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:45:00 33.90 0.01651
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
CORRIDORFLR1 18553.30 22263.96 1.531 1.837 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 32.00 0.01651
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
CORRIDORFLR2 2698.42 3238.10 0.222 0.267 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79 0.01651
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
CORRIDORFLR3 1291.61 1549.93 0.106 0.128 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79 0.01651
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651
CORRIDORFLR4 1968.93 2362.72 0.162 0.195 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 33.66 0.01651
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB   33.90 0.01651


Zone Heating

Calculated Design Load [W] User Design Load [W] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak Temperature at Peak [C] Humidity Ratio at Peak [kgWater/kgAir]
FRONTLOUNGEFLR1 1213.42 1456.11 0.034 0.236 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:15:00 4.60 0.00526
RESTROOMFLR1 34.11 40.94 0.001 0.001 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:45:00 4.60 0.00526
MEETINGROOMFLR1 386.73 464.08 0.011 0.126 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:00:00 4.60 0.00526
GUESTROOM101 157.06 188.47 0.004 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 4.60 0.00526
GUESTROOM102 196.52 235.82 0.006 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 4.60 0.00526
GUESTROOM103 318.37 382.05 0.009 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 4.60 0.00526
GUESTROOM104 300.06 360.07 0.008 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 07:30:00 4.60 0.00526
GUESTROOM105 192.95 231.54 0.005 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 4.60 0.00526
EMPLOYEELOUNGEFLR1 165.18 198.21 0.005 0.051 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60 0.00526
EXERCISECENTERFLR1 99.69 119.63 0.003 0.043 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 4.60 0.00526
FRONTOFFICEFLR1 689.24 827.09 0.019 0.056 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 4.60 0.00526
GUESTROOM201 255.77 306.92 0.007 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 11:00:00 4.60 0.00526
GUESTROOM202_205 597.06 716.47 0.017 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 10:45:00 4.60 0.00526
GUESTROOM206_208 466.04 559.25 0.013 0.043 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:00:00 4.60 0.00526
GUESTROOM209_212 526.20 631.44 0.015 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 4.60 0.00526
GUESTROOM213 279.77 335.72 0.008 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 11:15:00 4.60 0.00526
GUESTROOM214 244.98 293.98 0.007 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 10:30:00 4.60 0.00526
GUESTROOM215_218 489.97 587.96 0.014 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 4.60 0.00526
GUESTROOM219 91.30 109.56 0.003 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:15:00 4.60 0.00526
GUESTROOM220_223 482.19 578.63 0.014 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:15:00 4.60 0.00526
GUESTROOM224 215.59 258.71 0.006 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:30:00 4.60 0.00526
GUESTROOM301 277.05 332.46 0.008 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 17:45:00 4.60 0.00526
GUESTROOM302_305 662.42 794.90 0.019 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 17:30:00 4.60 0.00526
GUESTROOM306_308 576.15 691.38 0.016 0.043 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 14:30:00 4.60 0.00526
GUESTROOM309_312 653.00 783.59 0.018 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:15:00 4.60 0.00526
GUESTROOM313 313.05 375.66 0.009 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 20:30:00 4.60 0.00526
GUESTROOM314 273.34 328.01 0.008 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 15:45:00 4.60 0.00526
GUESTROOM315_318 625.53 750.64 0.018 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:15:00 4.60 0.00526
GUESTROOM319 156.83 188.20 0.004 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 4.60 0.00526
GUESTROOM320_323 600.00 720.00 0.017 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:45:00 4.60 0.00526
GUESTROOM324 252.57 303.09 0.007 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:30:00 4.60 0.00526
GUESTROOM401 401.12 481.34 0.011 0.014 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:45:00 4.60 0.00526
GUESTROOM402_405 1098.48 1318.17 0.031 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 22:15:00 4.60 0.00526
GUESTROOM406_408 943.61 1132.33 0.027 0.043 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:15:00 4.60 0.00526
GUESTROOM409_412 1100.94 1321.13 0.031 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 20:15:00 4.60 0.00526
GUESTROOM413 455.09 546.11 0.013 0.015 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60 0.00526
GUESTROOM414 414.44 497.32 0.012 0.014 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 21:00:00 4.60 0.00526
GUESTROOM415_418 1077.01 1292.41 0.030 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 17:15:00 4.60 0.00526
GUESTROOM419 304.64 365.56 0.009 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 18:00:00 4.60 0.00526
GUESTROOM420_423 1048.04 1257.65 0.030 0.054 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 19:15:00 4.60 0.00526
GUESTROOM424 396.48 475.78 0.011 0.013 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 24:00:00 4.60 0.00526
REARSTAIRSFLR1 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
CORRIDORFLR1 14033.10 16839.72 0.396 0.475 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60 0.00526
FRONTSTAIRSFLR1 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
REARSTAIRSFLR2 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
CORRIDORFLR2 79.63 95.56 0.002 0.038 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 09:30:00 4.60 0.00526
FRONTSTAIRSFLR2 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
REARSTAIRSFLR3 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
CORRIDORFLR3 201.97 242.36 0.006 0.038 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:30:00 4.60 0.00526
FRONTSTAIRSFLR3 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
REARSTAIRSFLR4 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526
CORRIDORFLR4 746.42 895.70 0.021 0.038 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 23:45:00 4.60 0.00526
FRONTSTAIRSFLR4 0.00 0.00 0.000 0.006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB   4.60 0.00526


System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s]
SAC_FRONTOFFICE 0.34 0.34 0.06 0.06
SAC_FRONTLOUNGE 0.80 0.80 0.24 0.24
SAC_MEETINGROOM 0.36 0.36 0.13 0.13
SAC_EXC_EMPLGE_RESTRM 0.70 0.70 0.10 0.10



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
SAC_FRONTLOUNGE OA CONTROLLER DifferentialEnthalpy 0.24 0.80 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule
None            


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
FRONTLOUNGEFLR1 5805.75 6695.75 4180.25
RESTROOMFLR1 2680.75 4850.50 898.00
MEETINGROOMFLR1 3030.25 2801.50 1734.50
GUESTROOM101 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00
GUESTROOM103 768.00 8469.00 768.00
GUESTROOM104 440.25 8108.50 424.25
GUESTROOM105 273.00 7409.00 86.00
EMPLOYEELOUNGEFLR1 3287.50 2098.25 468.25
EXERCISECENTERFLR1 3932.50 869.25 236.50
FRONTOFFICEFLR1 4823.50 3565.25 1497.50
GUESTROOM201 0.00 0.00 0.00
GUESTROOM202_205 565.25 7716.50 336.75
GUESTROOM206_208 478.50 7605.00 203.75
GUESTROOM209_212 521.00 7878.75 405.50
GUESTROOM213 566.50 8186.00 560.50
GUESTROOM214 281.00 7604.00 173.50
GUESTROOM215_218 0.00 0.00 0.00
GUESTROOM219 5913.00 3440.00 1418.25
GUESTROOM220_223 564.00 7538.25 343.25
GUESTROOM224 224.50 7470.25 113.50
GUESTROOM301 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00
GUESTROOM309_312 758.00 8315.00 747.50
GUESTROOM313 0.00 0.00 0.00
GUESTROOM314 309.75 7659.00 213.00
GUESTROOM315_318 679.50 7275.50 206.75
GUESTROOM319 0.00 0.00 0.00
GUESTROOM320_323 635.00 7939.75 562.00
GUESTROOM324 0.00 0.00 0.00
GUESTROOM401 1515.25 7350.50 522.75
GUESTROOM402_405 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00
GUESTROOM409_412 1318.75 7331.25 302.00
GUESTROOM413 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00
GUESTROOM415_418 1483.25 6867.75 146.75
GUESTROOM419 1148.50 6948.25 53.00
GUESTROOM420_423 1460.75 6931.00 179.75
GUESTROOM424 1158.00 7070.25 105.75
REARSTAIRSFLR1 0.00 0.00 0.00
CORRIDORFLR1 0.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00
CORRIDORFLR2 0.00 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00
CORRIDORFLR3 0.00 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00
CORRIDORFLR4 0.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00
LAUNDRYROOMFLR1 2920.00 2920.00 2920.00
ELEVATORCOREFLR1 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00
Facility 7760.25 8756.50 6734.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
FRONTLOUNGEFLR1 0.00 0.00 0.00 0.00
RESTROOMFLR1 1.50 1657.25 1.50 1657.25
MEETINGROOMFLR1 0.00 0.00 0.00 0.00
GUESTROOM101 0.00 0.00 0.00 0.00
GUESTROOM102 0.00 0.00 0.00 0.00
GUESTROOM103 0.00 74.50 0.00 74.50
GUESTROOM104 0.00 80.25 0.00 80.25
GUESTROOM105 0.00 88.50 0.00 88.50
EMPLOYEELOUNGEFLR1 250.25 1160.00 190.25 606.75
EXERCISECENTERFLR1 0.00 0.00 0.00 0.00
FRONTOFFICEFLR1 0.00 0.00 0.00 0.00
GUESTROOM201 0.00 0.00 0.00 0.00
GUESTROOM202_205 0.00 64.75 0.00 64.75
GUESTROOM206_208 0.00 69.50 0.00 69.50
GUESTROOM209_212 0.00 64.00 0.00 64.00
GUESTROOM213 0.00 64.00 0.00 64.00
GUESTROOM214 0.00 69.50 0.00 69.50
GUESTROOM215_218 0.00 0.00 0.00 0.00
GUESTROOM219 0.00 4730.25 0.00 4730.25
GUESTROOM220_223 0.00 68.75 0.00 68.75
GUESTROOM224 0.00 69.50 0.00 69.50
GUESTROOM301 0.00 0.00 0.00 0.00
GUESTROOM302_305 0.00 0.00 0.00 0.00
GUESTROOM306_308 0.00 0.00 0.00 0.00
GUESTROOM309_312 0.00 63.75 0.00 63.75
GUESTROOM313 0.00 0.00 0.00 0.00
GUESTROOM314 0.00 69.00 0.00 69.00
GUESTROOM315_318 0.00 69.00 0.00 69.00
GUESTROOM319 0.00 0.00 0.00 0.00
GUESTROOM320_323 0.00 67.00 0.00 67.00
GUESTROOM324 0.00 0.00 0.00 0.00
GUESTROOM401 0.75 67.75 0.75 67.75
GUESTROOM402_405 0.00 0.00 0.00 0.00
GUESTROOM406_408 0.00 0.00 0.00 0.00
GUESTROOM409_412 0.00 66.25 0.00 66.25
GUESTROOM413 0.00 0.00 0.00 0.00
GUESTROOM414 0.00 0.00 0.00 0.00
GUESTROOM415_418 0.00 72.50 0.00 72.50
GUESTROOM419 0.00 75.50 0.00 75.50
GUESTROOM420_423 0.00 70.75 0.00 70.75
GUESTROOM424 0.00 73.50 0.00 73.50
REARSTAIRSFLR1 0.00 0.00 0.00 0.00
CORRIDORFLR1 9.25 6429.00 0.00 0.00
FRONTSTAIRSFLR1 0.00 0.00 0.00 0.00
REARSTAIRSFLR2 0.00 0.00 0.00 0.00
CORRIDORFLR2 0.00 1429.50 0.00 0.00
FRONTSTAIRSFLR2 0.00 0.00 0.00 0.00
REARSTAIRSFLR3 0.00 0.00 0.00 0.00
CORRIDORFLR3 0.00 7.25 0.00 0.00
FRONTSTAIRSFLR3 0.00 0.00 0.00 0.00
REARSTAIRSFLR4 0.00 0.00 0.00 0.00
CORRIDORFLR4 0.00 833.00 0.00 0.00
FRONTSTAIRSFLR4 0.00 0.00 0.00 0.00
REARSTORAGEFLR1 0.00 0.00 0.00 0.00
MECHANICALROOMFLR1 0.00 0.00 0.00 0.00
LAUNDRYROOMFLR1 0.00 0.00 0.00 0.00
ELEVATORCOREFLR1 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR1 0.00 0.00 0.00 0.00
REARSTORAGEFLR2 0.00 0.00 0.00 0.00
ELEVATORCOREFLR2 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR2 0.00 0.00 0.00 0.00
REARSTORAGEFLR3 0.00 0.00 0.00 0.00
ELEVATORCOREFLR3 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR3 0.00 0.00 0.00 0.00
REARSTORAGEFLR4 0.00 0.00 0.00 0.00
ELEVATORCOREFLR4 0.00 0.00 0.00 0.00
FRONTSTORAGEFLR4 0.00 0.00 0.00 0.00
Facility 254.00 7314.75 191.25 5428.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2018-10-19 10:15:34

ZoneHVAC:UnitHeater

Maximum Supply Air Flow Rate [m3/s]
REARSTAIRSFLR1 UNITHEATER 0.006116
MECHRM UNITHEATER 0.000000
FRONTSTAIRSFLR1 UNITHEATER 0.006114
REARSTAIRSFLR2 UNITHEATER 0.006116
FRONTSTAIRSFLR2 UNITHEATER 0.006114
REARSTAIRSFLR3 UNITHEATER 0.006116
FRONTSTAIRSFLR3 UNITHEATER 0.006114
REARSTAIRSFLR4 UNITHEATER 0.006116
FRONTSTAIRSFLR4 UNITHEATER 0.006114


Fan:ConstantVolume

Maximum Flow Rate [m3/s]
REARSTAIRSFLR1UNITHEATERFAN 0.006116
MECHRMUNITHEATERFAN 0.000000
FRONTSTAIRSFLR1UNITHEATERFAN 0.006114
REARSTAIRSFLR2UNITHEATERFAN 0.006116
FRONTSTAIRSFLR2UNITHEATERFAN 0.006114
REARSTAIRSFLR3UNITHEATERFAN 0.006116
FRONTSTAIRSFLR3UNITHEATERFAN 0.006114
REARSTAIRSFLR4UNITHEATERFAN 0.006116
FRONTSTAIRSFLR4UNITHEATERFAN 0.006114
SAC_FRONTOFFICE SUPPLY FAN 0.342544
SAC_FRONTLOUNGE SUPPLY FAN 0.796949
SAC_EXC_EMPLGE_RESTRM SUPPLY FAN 0.699566


Coil:Heating:Electric

Nominal Capacity [W]
REARSTAIRSFLR1UNITHEATERHEATINGCOIL 321.13
CORRIDORFLR1 PTAC HEATING COIL 17771.40
MECHRMUNITHEATERHEATINGCOIL 0.000000
101 PTAC HEATING COIL 750.51
102 PTAC HEATING COIL 750.51
103 PTAC HEATING COIL 750.51
104 PTAC HEATING COIL 750.46
105 PTAC HEATING COIL 750.46
FRONTSTAIRSFLR1UNITHEATERHEATINGCOIL 321.05
REARSTAIRSFLR2UNITHEATERHEATINGCOIL 321.13
CORRIDORFLR2 PTAC HEATING COIL 2128.50
201 PTAC HEATING COIL 750.51
202_205 PTAC HEATING COIL 3002.06
206_208 PTAC HEATING COIL 2379.23
209_212 PTAC HEATING COIL 3002.06
213 PTAC HEATING COIL 750.51
214 PTAC HEATING COIL 750.46
215_218 PTAC HEATING COIL 3001.84
219 PTAC HEATING COIL 750.46
220_223 PTAC HEATING COIL 3001.84
224 PTAC HEATING COIL 750.46
FRONTSTAIRSFLR2UNITHEATERHEATINGCOIL 321.05
REARSTAIRSFLR3UNITHEATERHEATINGCOIL 321.13
CORRIDORFLR3 PTAC HEATING COIL 2128.50
301 PTAC HEATING COIL 750.51
302_305 PTAC HEATING COIL 3002.06
306_308 PTAC HEATING COIL 2379.23
309_312 PTAC HEATING COIL 3002.06
313 PTAC HEATING COIL 750.51
314 PTAC HEATING COIL 750.46
315_318 PTAC HEATING COIL 3001.84
319 PTAC HEATING COIL 750.46
320_323 PTAC HEATING COIL 3001.84
324 PTAC HEATING COIL 750.46
FRONTSTAIRSFLR3UNITHEATERHEATINGCOIL 321.05
REARSTAIRSFLR4UNITHEATERHEATINGCOIL 321.13
CORRIDORFLR4 PTAC HEATING COIL 2128.50
401 PTAC HEATING COIL 754.29
402_405 PTAC HEATING COIL 3002.06
406_408 PTAC HEATING COIL 2379.23
409_412 PTAC HEATING COIL 3002.06
413 PTAC HEATING COIL 819.06
414 PTAC HEATING COIL 770.25
415_418 PTAC HEATING COIL 3001.84
419 PTAC HEATING COIL 750.46
420_423 PTAC HEATING COIL 3001.84
424 PTAC HEATING COIL 750.46
FRONTSTAIRSFLR4UNITHEATERHEATINGCOIL 321.05


Coil:Cooling:DX:SingleSpeed

Rated Sensible Heat Ratio Rated Air Flow Rate [m3/s] Rated Total Cooling Capacity (gross) [W]
CORRIDORFLR1 PTAC COOLING COIL 0.730484    
101 PTAC COOLING COIL 0.730484    
102 PTAC COOLING COIL 0.730484    
103 PTAC COOLING COIL 0.730484    
104 PTAC COOLING COIL 0.730484    
105 PTAC COOLING COIL 0.730484    
CORRIDORFLR2 PTAC COOLING COIL 0.730484    
201 PTAC COOLING COIL 0.730484    
202_205 PTAC COOLING COIL 0.730484    
206_208 PTAC COOLING COIL 0.730484    
209_212 PTAC COOLING COIL 0.730484    
213 PTAC COOLING COIL 0.730484    
214 PTAC COOLING COIL 0.730484    
215_218 PTAC COOLING COIL 0.730484    
219 PTAC COOLING COIL 0.730484    
220_223 PTAC COOLING COIL 0.730484    
224 PTAC COOLING COIL 0.730484    
CORRIDORFLR3 PTAC COOLING COIL 0.730484    
301 PTAC COOLING COIL 0.730484    
302_305 PTAC COOLING COIL 0.730484    
306_308 PTAC COOLING COIL 0.730484    
309_312 PTAC COOLING COIL 0.730484    
313 PTAC COOLING COIL 0.730484    
314 PTAC COOLING COIL 0.730484    
315_318 PTAC COOLING COIL 0.730484    
319 PTAC COOLING COIL 0.730484    
320_323 PTAC COOLING COIL 0.730484    
324 PTAC COOLING COIL 0.730484    
CORRIDORFLR4 PTAC COOLING COIL 0.730484    
401 PTAC COOLING COIL 0.730484    
402_405 PTAC COOLING COIL 0.730484    
406_408 PTAC COOLING COIL 0.730484    
409_412 PTAC COOLING COIL 0.730484    
413 PTAC COOLING COIL 0.730484    
414 PTAC COOLING COIL 0.730484    
415_418 PTAC COOLING COIL 0.730484    
419 PTAC COOLING COIL 0.730484    
420_423 PTAC COOLING COIL 0.730484    
424 PTAC COOLING COIL 0.730484    
SAC_FRONTOFFICE COOLING COIL 0.693719 0.342544 7935.19
SAC_FRONTLOUNGE COOLING COIL 0.676083 0.796949 19790.13
SAC_MEETINGROOM COOLING COIL 0.676083 0.363819 9034.48
SAC_EXC_EMPLGE_RESTRM COOLING COIL 0.703755 0.699566 15609.46


AirTerminal:SingleDuct:Uncontrolled

Maximum Air Flow Rate [m3/s]
FRONTLOUNGEFLR1 DIRECT AIR 0.796949
RESTROOMFLR1 DIRECT AIR 0.046735
MEETINGROOMFLR1 DIRECT AIR 0.363819
EMPLOYEELOUNGEFLR1 DIRECT AIR 0.531650
EXERCISECENTERFLR1 DIRECT AIR 0.121181
FRONTOFFICEFLR1 DIRECT AIR 0.342544


Branch

Maximum Flow Rate [m3/s]
SAC_FRONTOFFICE MAIN BRANCH 0.342544
SAC_FRONTLOUNGE MAIN BRANCH 0.796949
SAC_MEETINGROOM MAIN BRANCH 0.363819
SAC_EXC_EMPLGE_RESTRM MAIN BRANCH 0.699566


AirLoopHVAC

Design Supply Air Flow Rate [m3/s]
SAC_FRONTOFFICE 0.342544
SAC_FRONTLOUNGE 0.796949
SAC_MEETINGROOM 0.363819
SAC_EXC_EMPLGE_RESTRM 0.699566


Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
SAC_FRONTOFFICE OA CONTROLLER 0.342544 0.056300
SAC_FRONTLOUNGE OA CONTROLLER 0.796949 0.235982
SAC_MEETINGROOM OA CONTROLLER 0.363819 0.126367
SAC_EXC_EMPLGE_RESTRM OA CONTROLLER 0.699566 0.094386


AirLoopHVAC:Unitary:Furnace:HeatCool

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
SAC_FRONTOFFICE 0.342544 0.342544 0.342544 0.342544 3090.28 7935.19 1.00
SAC_FRONTLOUNGE 0.796949 0.796949 0.796949 0.796949 12952.86 19790.13 1.00
SAC_MEETINGROOM 0.363819 0.363819 0.363819 0.363819 6936.16 9034.48 1.00
SAC_EXC_EMPLGE_RESTRM 0.699566 0.699566 0.699566 0.699566 5221.12 15609.46 0.173224


Coil:Heating:Gas

Nominal Capacity [W]
SAC_FRONTOFFICE HEATING COIL 3090.28
SAC_FRONTLOUNGE HEATING COIL 12952.86
SAC_MEETINGROOM HEATING COIL 6936.16
SAC_EXC_EMPLGE_RESTRM HEATING COIL 5221.12


Fan:OnOff

Maximum Flow Rate [m3/s]
SAC_MEETINGROOM SUPPLY FAN 0.363819


PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
SHWSYSSHOWER 0.000180 0.202443
SHWSYSLAUNDRY 0.000129 0.145496


WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SHWSYSSHOWER WATER HEATER 0.000180
SHWSYSLAUNDRY WATER HEATER 0.000129


Pump:ConstantSpeed

Rated Flow Rate [m3/s] Rated Power Consumption [W]
SHWSYSSHOWER PUMP 0.000180 8.11
SHWSYSLAUNDRY PUMP 0.000129 0.000001



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.59 13.57
February 22.19 15.49
March 22.40 17.07
April 23.89 21.23
May 25.32 26.90
June 25.56 27.61
July 25.62 27.94
August 25.61 27.43
September 25.28 26.23
October 24.86 24.23
November 23.32 18.91
December 22.19 15.68
     
Annual Sum or Average 23.99 21.89
Minimum of Months 21.59 13.57
Maximum of Months 25.62 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.96 13.57
February 24.29 15.49
March 24.55 17.07
April 25.47 21.23
May 27.00 26.90
June 27.30 27.61
July 27.49 27.94
August 27.31 27.43
September 26.95 26.23
October 26.36 24.23
November 24.98 18.91
December 24.36 15.68
     
Annual Sum or Average 25.84 21.89
Minimum of Months 23.96 13.57
Maximum of Months 27.49 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.64 13.57
February 21.32 15.49
March 21.76 17.07
April 23.33 21.23
May 24.86 26.90
June 25.11 27.61
July 25.16 27.94
August 25.08 27.43
September 24.68 26.23
October 24.12 24.23
November 22.41 18.91
December 21.28 15.68
     
Annual Sum or Average 23.32 21.89
Minimum of Months 20.64 13.57
Maximum of Months 25.16 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTLOUNGEFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.18 13.57
February 22.51 15.49
March 22.76 17.07
April 23.47 21.23
May 23.89 26.90
June 23.89 27.61
July 23.89 27.94
August 23.89 27.43
September 23.89 26.23
October 23.71 24.23
November 23.06 18.91
December 22.53 15.68
     
Annual Sum or Average 23.31 21.89
Minimum of Months 22.18 13.57
Maximum of Months 23.89 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: RESTROOMFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.56 13.57
February 22.80 15.49
March 23.02 17.07
April 23.47 21.23
May 23.85 26.90
June 23.93 27.61
July 23.95 27.94
August 23.88 27.43
September 23.77 26.23
October 23.58 24.23
November 23.12 18.91
December 22.78 15.68
     
Annual Sum or Average 23.40 21.89
Minimum of Months 22.56 13.57
Maximum of Months 23.95 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MEETINGROOMFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.79 13.57
February 23.06 15.49
March 23.26 17.07
April 23.77 21.23
May 23.89 26.90
June 23.89 27.61
July 23.89 27.94
August 23.89 27.43
September 23.89 26.23
October 23.84 24.23
November 23.56 18.91
December 23.07 15.68
     
Annual Sum or Average 23.57 21.89
Minimum of Months 22.79 13.57
Maximum of Months 23.89 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: MECHANICALROOMFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 25.43 13.57
February 25.69 15.49
March 26.28 17.07
April 28.80 21.23
May 31.24 26.90
June 32.89 27.61
July 33.70 27.94
August 33.36 27.43
September 32.16 26.23
October 30.18 24.23
November 27.74 18.91
December 25.92 15.68
     
Annual Sum or Average 29.47 21.89
Minimum of Months 25.43 13.57
Maximum of Months 33.70 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM101

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.65 13.57
February 22.09 15.49
March 22.42 17.07
April 23.20 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.28 24.23
November 22.87 18.91
December 22.11 15.68
     
Annual Sum or Average 22.86 21.89
Minimum of Months 21.65 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM102

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.36 13.57
February 21.82 15.49
March 22.15 17.07
April 22.99 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.18 24.23
November 22.58 18.91
December 21.83 15.68
     
Annual Sum or Average 22.72 21.89
Minimum of Months 21.36 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM103

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.45 13.57
February 21.53 15.49
March 21.58 17.07
April 21.73 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.74 24.23
November 21.69 18.91
December 21.53 15.68
     
Annual Sum or Average 21.67 21.89
Minimum of Months 21.45 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM104

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 13.57
February 21.69 15.49
March 21.67 17.07
April 21.74 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.75 18.91
December 21.69 15.68
     
Annual Sum or Average 21.73 21.89
Minimum of Months 21.67 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM105

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 13.57
February 21.74 15.49
March 21.73 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.74 15.68
     
Annual Sum or Average 21.75 21.89
Minimum of Months 21.73 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EMPLOYEELOUNGEFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.38 13.57
February 22.52 15.49
March 22.62 17.07
April 22.62 21.23
May 22.32 26.90
June 22.24 27.61
July 22.19 27.94
August 22.19 27.43
September 22.23 26.23
October 22.24 24.23
November 22.44 18.91
December 22.41 15.68
     
Annual Sum or Average 22.36 21.89
Minimum of Months 22.19 13.57
Maximum of Months 22.62 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: LAUNDRYROOMFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 51.74 13.57
February 51.90 15.49
March 51.84 17.07
April 52.32 21.23
May 52.84 26.90
June 53.01 27.61
July 53.07 27.94
August 53.06 27.43
September 52.97 26.23
October 52.91 24.23
November 52.42 18.91
December 51.99 15.68
     
Annual Sum or Average 52.51 21.89
Minimum of Months 51.74 13.57
Maximum of Months 53.07 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 69.20 13.57
February 69.47 15.49
March 69.44 17.07
April 70.14 21.23
May 70.83 26.90
June 71.08 27.61
July 71.18 27.94
August 71.04 27.43
September 70.88 26.23
October 70.59 24.23
November 70.04 18.91
December 69.51 15.68
     
Annual Sum or Average 70.29 21.89
Minimum of Months 69.20 13.57
Maximum of Months 71.18 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: EXERCISECENTERFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.46 13.57
February 23.61 15.49
March 23.67 17.07
April 23.86 21.23
May 23.89 26.90
June 23.89 27.61
July 23.89 27.94
August 23.89 27.43
September 23.89 26.23
October 23.87 24.23
November 23.78 18.91
December 23.58 15.68
     
Annual Sum or Average 23.77 21.89
Minimum of Months 23.46 13.57
Maximum of Months 23.89 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTOFFICEFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.32 13.57
February 23.53 15.49
March 23.60 17.07
April 23.86 21.23
May 23.89 26.90
June 23.89 27.61
July 23.89 27.94
August 23.89 27.43
September 23.89 26.23
October 23.88 24.23
November 23.78 18.91
December 23.51 15.68
     
Annual Sum or Average 23.74 21.89
Minimum of Months 23.32 13.57
Maximum of Months 23.89 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.62 13.57
February 22.29 15.49
March 22.60 17.07
April 24.25 21.23
May 26.00 26.90
June 26.29 27.61
July 26.44 27.94
August 26.29 27.43
September 25.91 26.23
October 25.37 24.23
November 23.67 18.91
December 22.28 15.68
     
Annual Sum or Average 24.43 21.89
Minimum of Months 21.62 13.57
Maximum of Months 26.44 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR1

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.74 13.57
February 23.09 15.49
March 23.22 17.07
April 24.13 21.23
May 25.08 26.90
June 25.26 27.61
July 25.36 27.94
August 25.30 27.43
September 25.12 26.23
October 24.89 24.23
November 23.94 18.91
December 23.15 15.68
     
Annual Sum or Average 24.28 21.89
Minimum of Months 22.74 13.57
Maximum of Months 25.36 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.98 13.57
February 22.66 15.49
March 22.87 17.07
April 24.45 21.23
May 25.88 26.90
June 26.09 27.61
July 26.17 27.94
August 26.11 27.43
September 25.79 26.23
October 25.31 24.23
November 23.80 18.91
December 22.61 15.68
     
Annual Sum or Average 24.49 21.89
Minimum of Months 21.98 13.57
Maximum of Months 26.17 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.54 13.57
February 23.65 15.49
March 23.73 17.07
April 23.90 21.23
May 23.97 26.90
June 24.06 27.61
July 24.16 27.94
August 24.10 27.43
September 24.02 26.23
October 23.99 24.23
November 23.87 18.91
December 23.66 15.68
     
Annual Sum or Average 23.89 21.89
Minimum of Months 23.54 13.57
Maximum of Months 24.16 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 13.57
February 21.44 15.49
March 21.90 17.07
April 23.65 21.23
May 25.26 26.90
June 25.48 27.61
July 25.56 27.94
August 25.45 27.43
September 25.05 26.23
October 24.45 24.23
November 22.65 18.91
December 21.36 15.68
     
Annual Sum or Average 23.58 21.89
Minimum of Months 20.63 13.57
Maximum of Months 25.56 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM201

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.28 13.57
February 21.95 15.49
March 22.29 17.07
April 23.18 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.24 24.23
November 22.76 18.91
December 21.81 15.68
     
Annual Sum or Average 22.77 21.89
Minimum of Months 21.28 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM202_205

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.58 13.57
February 21.63 15.49
March 21.67 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.74 18.91
December 21.63 15.68
     
Annual Sum or Average 21.71 21.89
Minimum of Months 21.58 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM206_208

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.60 13.57
February 21.64 15.49
March 21.68 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.74 18.91
December 21.64 15.68
     
Annual Sum or Average 21.72 21.89
Minimum of Months 21.60 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM209_212

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.63 13.57
February 21.66 15.49
March 21.69 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.74 18.91
December 21.66 15.68
     
Annual Sum or Average 21.72 21.89
Minimum of Months 21.63 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM213

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.49 13.57
February 21.57 15.49
March 21.62 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.72 18.91
December 21.57 15.68
     
Annual Sum or Average 21.69 21.89
Minimum of Months 21.49 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM214

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 13.57
February 21.72 15.49
March 21.71 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.72 15.68
     
Annual Sum or Average 21.75 21.89
Minimum of Months 21.71 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM215_218

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 23.31 13.57
February 23.31 15.49
March 23.32 17.07
April 23.33 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.33 24.23
November 23.33 18.91
December 23.32 15.68
     
Annual Sum or Average 23.33 21.89
Minimum of Months 23.31 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 32.41 13.57
February 32.64 15.49
March 32.66 17.07
April 33.20 21.23
May 33.69 26.90
June 33.84 27.61
July 33.94 27.94
August 33.86 27.43
September 33.75 26.23
October 33.58 24.23
November 33.11 18.91
December 32.65 15.68
     
Annual Sum or Average 33.28 21.89
Minimum of Months 32.41 13.57
Maximum of Months 33.94 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM219

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.34 13.57
February 22.44 15.49
March 22.46 17.07
April 22.74 21.23
May 23.28 26.90
June 23.43 27.61
July 23.60 27.94
August 23.52 27.43
September 23.39 26.23
October 23.23 24.23
November 22.66 18.91
December 22.46 15.68
     
Annual Sum or Average 22.97 21.89
Minimum of Months 22.34 13.57
Maximum of Months 23.60 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM220_223

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 13.57
February 21.74 15.49
March 21.73 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.74 15.68
     
Annual Sum or Average 21.75 21.89
Minimum of Months 21.73 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM224

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 13.57
February 21.73 15.49
March 21.71 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.73 15.68
     
Annual Sum or Average 21.75 21.89
Minimum of Months 21.71 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.69 13.57
February 23.12 15.49
March 23.30 17.07
April 24.40 21.23
May 25.42 26.90
June 25.60 27.61
July 25.70 27.94
August 25.59 27.43
September 25.39 26.23
October 25.09 24.23
November 24.05 18.91
December 23.14 15.68
     
Annual Sum or Average 24.47 21.89
Minimum of Months 22.69 13.57
Maximum of Months 25.70 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR2

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.89 13.57
February 22.70 15.49
March 23.07 17.07
April 25.02 21.23
May 26.89 26.90
June 27.22 27.61
July 27.38 27.94
August 27.12 27.43
September 26.70 26.23
October 26.03 24.23
November 24.19 18.91
December 22.62 15.68
     
Annual Sum or Average 25.08 21.89
Minimum of Months 21.89 13.57
Maximum of Months 27.38 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 13.57
February 22.48 15.49
March 22.74 17.07
April 24.51 21.23
May 26.05 26.90
June 26.26 27.61
July 26.34 27.94
August 26.26 27.43
September 25.92 26.23
October 25.38 24.23
November 23.74 18.91
December 22.39 15.68
     
Annual Sum or Average 24.49 21.89
Minimum of Months 21.70 13.57
Maximum of Months 26.34 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.78 13.57
February 23.17 15.49
March 23.31 17.07
April 23.84 21.23
May 23.89 26.90
June 23.89 27.61
July 23.89 27.94
August 23.89 27.43
September 23.89 26.23
October 23.86 24.23
November 23.66 18.91
December 23.09 15.68
     
Annual Sum or Average 23.60 21.89
Minimum of Months 22.78 13.57
Maximum of Months 23.89 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.12 13.57
February 21.12 15.49
March 21.69 17.07
April 23.77 21.23
May 25.56 26.90
June 25.80 27.61
July 25.87 27.94
August 25.75 27.43
September 25.31 26.23
October 24.62 24.23
November 22.56 18.91
December 21.00 15.68
     
Annual Sum or Average 23.61 21.89
Minimum of Months 20.12 13.57
Maximum of Months 25.87 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM301

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.81 13.57
February 21.60 15.49
March 21.99 17.07
April 23.10 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.18 24.23
November 22.51 18.91
December 21.41 15.68
     
Annual Sum or Average 22.61 21.89
Minimum of Months 20.81 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM302_305

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.92 13.57
February 21.69 15.49
March 22.06 17.07
April 23.13 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.21 24.23
November 22.56 18.91
December 21.52 15.68
     
Annual Sum or Average 22.65 21.89
Minimum of Months 20.92 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM306_308

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.98 13.57
February 21.71 15.49
March 22.08 17.07
April 23.11 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.20 24.23
November 22.55 18.91
December 21.56 15.68
     
Annual Sum or Average 22.66 21.89
Minimum of Months 20.98 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM309_312

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.58 13.57
February 21.63 15.49
March 21.66 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.73 18.91
December 21.62 15.68
     
Annual Sum or Average 21.71 21.89
Minimum of Months 21.58 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM313

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.98 13.57
February 21.70 15.49
March 22.06 17.07
April 23.11 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.20 24.23
November 22.57 18.91
December 21.57 15.68
     
Annual Sum or Average 22.66 21.89
Minimum of Months 20.98 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM314

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 13.57
February 21.69 15.49
March 21.67 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.69 15.68
     
Annual Sum or Average 21.73 21.89
Minimum of Months 21.67 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM315_318

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.74 13.57
February 21.74 15.49
March 21.73 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.74 15.68
     
Annual Sum or Average 21.75 21.89
Minimum of Months 21.73 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 24.84 13.57
February 25.15 15.49
March 25.24 17.07
April 25.91 21.23
May 26.36 26.90
June 26.44 27.61
July 26.49 27.94
August 26.46 27.43
September 26.38 26.23
October 26.24 24.23
November 25.73 18.91
December 25.15 15.68
     
Annual Sum or Average 25.87 21.89
Minimum of Months 24.84 13.57
Maximum of Months 26.49 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM319

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.99 13.57
February 23.09 15.49
March 23.13 17.07
April 23.33 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.33 24.23
November 23.30 18.91
December 23.09 15.68
     
Annual Sum or Average 23.25 21.89
Minimum of Months 22.99 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM320_323

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 13.57
February 21.73 15.49
March 21.71 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.75 18.91
December 21.72 15.68
     
Annual Sum or Average 21.74 21.89
Minimum of Months 21.71 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM324

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.17 13.57
February 22.48 15.49
March 22.57 17.07
April 23.21 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.27 24.23
November 23.04 18.91
December 22.44 15.68
     
Annual Sum or Average 22.99 21.89
Minimum of Months 22.17 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.33 13.57
February 22.90 15.49
March 23.15 17.07
April 24.52 21.23
May 25.68 26.90
June 25.88 27.61
July 25.97 27.94
August 25.83 27.43
September 25.60 26.23
October 25.23 24.23
November 24.00 18.91
December 22.89 15.68
     
Annual Sum or Average 24.51 21.89
Minimum of Months 22.33 13.57
Maximum of Months 25.97 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR3

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.58 13.57
February 22.52 15.49
March 22.96 17.07
April 25.15 21.23
May 27.16 26.90
June 27.52 27.61
July 27.68 27.94
August 27.38 27.43
September 26.91 26.23
October 26.15 24.23
November 24.14 18.91
December 22.40 15.68
     
Annual Sum or Average 25.14 21.89
Minimum of Months 21.58 13.57
Maximum of Months 27.68 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTAIRSFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.10 13.57
February 22.07 15.49
March 22.44 17.07
April 24.60 21.23
May 26.46 26.90
June 26.73 27.61
July 26.79 27.94
August 26.69 27.43
September 26.24 26.23
October 25.57 24.23
November 23.56 18.91
December 21.94 15.68
     
Annual Sum or Average 24.53 21.89
Minimum of Months 21.10 13.57
Maximum of Months 26.79 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: CORRIDORFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.36 13.57
February 22.75 15.49
March 22.94 17.07
April 23.64 21.23
May 23.97 26.90
June 24.02 27.61
July 24.06 27.94
August 24.02 27.43
September 23.98 26.23
October 23.81 24.23
November 23.26 18.91
December 22.66 15.68
     
Annual Sum or Average 23.46 21.89
Minimum of Months 22.36 13.57
Maximum of Months 24.06 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: REARSTORAGEFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 19.63 13.57
February 20.77 15.49
March 21.43 17.07
April 23.81 21.23
May 25.87 26.90
June 26.16 27.61
July 26.22 27.94
August 26.07 27.43
September 25.54 26.23
October 24.75 24.23
November 22.35 18.91
December 20.61 15.68
     
Annual Sum or Average 23.61 21.89
Minimum of Months 19.63 13.57
Maximum of Months 26.22 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM401

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.43 13.57
February 21.53 15.49
March 21.57 17.07
April 21.74 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.74 24.23
November 21.71 18.91
December 21.49 15.68
     
Annual Sum or Average 21.67 21.89
Minimum of Months 21.43 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM402_405

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.63 13.57
February 21.33 15.49
March 21.74 17.07
April 22.91 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.11 24.23
November 22.19 18.91
December 21.18 15.68
     
Annual Sum or Average 22.48 21.89
Minimum of Months 20.63 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM406_408

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.65 13.57
February 21.32 15.49
March 21.73 17.07
April 22.88 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.10 24.23
November 22.17 18.91
December 21.18 15.68
     
Annual Sum or Average 22.48 21.89
Minimum of Months 20.65 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM409_412

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.58 13.57
February 21.62 15.49
March 21.65 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.73 18.91
December 21.61 15.68
     
Annual Sum or Average 21.71 21.89
Minimum of Months 21.58 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM413

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 20.69 13.57
February 21.40 15.49
March 21.78 17.07
April 22.94 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.12 24.23
November 22.27 18.91
December 21.25 15.68
     
Annual Sum or Average 22.51 21.89
Minimum of Months 20.69 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM414

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.54 13.57
February 21.99 15.49
March 22.13 17.07
April 23.03 21.23
May 23.33 26.90
June 23.33 27.61
July 23.33 27.94
August 23.33 27.43
September 23.33 26.23
October 23.19 24.23
November 22.68 18.91
December 21.90 15.68
     
Annual Sum or Average 22.76 21.89
Minimum of Months 21.54 13.57
Maximum of Months 23.33 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM415_418

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.73 13.57
February 21.72 15.49
March 21.70 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.75 18.91
December 21.72 15.68
     
Annual Sum or Average 21.74 21.89
Minimum of Months 21.70 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: ELEVATORCOREFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 22.76 13.57
February 23.17 15.49
March 23.36 17.07
April 24.27 21.23
May 24.98 26.90
June 25.10 27.61
July 25.14 27.94
August 25.09 27.43
September 24.93 26.23
October 24.70 24.23
November 23.86 18.91
December 23.13 15.68
     
Annual Sum or Average 24.21 21.89
Minimum of Months 22.76 13.57
Maximum of Months 25.14 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM419

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 13.57
February 21.72 15.49
March 21.70 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.76 24.23
November 21.75 18.91
December 21.72 15.68
     
Annual Sum or Average 21.74 21.89
Minimum of Months 21.70 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM420_423

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.72 13.57
February 21.72 15.49
March 21.69 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.75 18.91
December 21.71 15.68
     
Annual Sum or Average 21.74 21.89
Minimum of Months 21.69 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: GUESTROOM424

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.70 13.57
February 21.69 15.49
March 21.66 17.07
April 21.75 21.23
May 21.76 26.90
June 21.76 27.61
July 21.76 27.94
August 21.76 27.43
September 21.76 26.23
October 21.75 24.23
November 21.75 18.91
December 21.69 15.68
     
Annual Sum or Average 21.73 21.89
Minimum of Months 21.66 13.57
Maximum of Months 21.76 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTORAGEFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.91 13.57
February 22.54 15.49
March 22.87 17.07
April 24.40 21.23
May 25.78 26.90
June 26.03 27.61
July 26.10 27.94
August 25.94 27.43
September 25.61 26.23
October 25.15 24.23
November 23.68 18.91
December 22.49 15.68
     
Annual Sum or Average 24.38 21.89
Minimum of Months 21.91 13.57
Maximum of Months 26.10 27.94



Table of Contents

Report: MONTHLY INDOOR TEMP

For: FRONTSTAIRSFLR4

Timestamp: 2018-10-19 10:15:34

ZONE MEAN AIR TEMPERATURE [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 21.08 13.57
February 22.14 15.49
March 22.67 17.07
April 25.11 21.23
May 27.39 26.90
June 27.80 27.61
July 27.92 27.94
August 27.61 27.43
September 27.03 26.23
October 26.16 24.23
November 23.86 18.91
December 21.98 15.68
     
Annual Sum or Average 25.08 21.89
Minimum of Months 21.08 13.57
Maximum of Months 27.92 27.94



Table of Contents

Report: PEAK ELECTRICAL DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:34

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum}[W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY [Invalid/Undefined] EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] HEATRECOVERY:ELECTRICITY [Invalid/Undefined] WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] REFRIGERATION:ELECTRICITY [Invalid/Undefined] GENERATORS:ELECTRICITY [Invalid/Undefined] ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined]
January 0.140668E+12 96542.494 05-JAN-07:15 15177.258 39465.561 8750.046 28074.317 879.198 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
February 0.130544E+12 105138.524 05-FEB-07:15 15177.258 39465.561 8764.120 37281.861 253.611 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
March 0.145129E+12 92739.037 18-MAR-07:00 17938.723 43276.576 9157.563 0.000 22358.063 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
April 0.151983E+12 99391.682 29-APR-07:00 17938.723 43276.576 9157.563 0.000 29010.708 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
May 0.182510E+12 105676.064 27-MAY-07:00 17938.723 43276.576 9157.563 0.000 35295.090 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
June 0.180888E+12 107758.048 17-JUN-07:00 17938.723 43276.576 9157.563 0.000 37377.074 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
July 0.191859E+12 108100.184 08-JUL-07:00 17938.723 43276.576 9157.563 0.000 37719.210 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
August 0.188639E+12 104665.279 04-AUG-07:00 17938.723 43276.576 9157.563 0.000 34284.305 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
September 0.177816E+12 104756.140 10-SEP-06:15 15177.258 39465.561 8807.394 0.000 37109.814 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
October 0.173727E+12 110516.398 07-OCT-07:00 17938.723 43276.576 9157.563 0.000 40135.424 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
November 0.146645E+12 96997.512 03-NOV-07:00 17938.723 43276.576 9157.563 0.000 26616.538 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
December 0.145041E+12 97704.558 21-DEC-07:15 15177.258 39465.561 8750.046 29410.270 705.310 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
                                     
Annual Sum or Average 0.195545E+13                   0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Minimum of Months 0.130544E+12 92739.037   15177.258 39465.561 8750.046 0.000 253.611 0.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.191859E+12 110516.398   17938.723 43276.576 9157.563 37281.861 40135.424 4188.000 8.113 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000



Table of Contents

Report: PEAK GAS DEMAND

For: Meter

Timestamp: 2018-10-19 10:15:34

GAS:FACILITY [J] GAS:FACILITY {Maximum}[W] GAS:FACILITY {TIMESTAMP} GAS:HVAC {AT MAX/MIN} [W] INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] GAS:PLANT {AT MAX/MIN} [W] WATERSYSTEMS:GAS {AT MAX/MIN} [W] WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] HEATING:GAS {AT MAX/MIN} [W]
January 0.843953E+11 90026.376 21-JAN-10:30 3091.266 40096.028 0.000 46839.082 46839.082 46839.082 3091.266
February 0.752777E+11 92919.234 05-FEB-09:15 3214.946 40096.028 0.000 49608.261 49608.261 49608.261 3214.946
March 0.811993E+11 86030.072 02-MAR-09:15 0.000 40096.028 0.000 45934.044 45934.044 45934.044 0.000
April 0.764107E+11 74054.795 01-APR-08:15 0.000 40096.028 0.000 33958.767 33958.767 33958.767 0.000
May 0.774533E+11 73228.577 01-MAY-08:15 0.000 40096.028 0.000 33132.549 33132.549 33132.549 0.000
June 0.737981E+11 72451.169 02-JUN-08:15 0.000 40096.028 0.000 32355.141 32355.141 32355.141 0.000
July 0.756755E+11 71976.634 01-JUL-08:15 0.000 40096.028 0.000 31880.606 31880.606 31880.606 0.000
August 0.758687E+11 72172.903 31-AUG-08:15 0.000 40096.028 0.000 32076.875 32076.875 32076.875 0.000
September 0.742862E+11 72772.038 30-SEP-08:15 0.000 40096.028 0.000 32676.010 32676.010 32676.010 0.000
October 0.781566E+11 73614.998 31-OCT-08:15 0.000 40096.028 0.000 33518.970 33518.970 33518.970 0.000
November 0.773341E+11 74341.104 30-NOV-09:00 0.000 40096.028 0.000 34245.076 34245.076 34245.076 0.000
December 0.824591E+11 89195.363 31-DEC-09:45 0.000 40096.028 0.000 49099.335 49099.335 49099.335 0.000
                     
Annual Sum or Average 0.932315E+12         0.000        
Minimum of Months 0.737981E+11 71976.634   0.000 40096.028 0.000 31880.606 31880.606 31880.606 0.000