Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4670.08 | 1227.67 | 1227.67 |
Net Site Energy | 4670.08 | 1227.67 | 1227.67 |
Total Source Energy | 12541.87 | 3297.01 | 3297.01 |
Net Source Energy | 12541.87 | 3297.01 | 3297.01 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 207.83 | 646.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 447.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 112.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 409.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 36.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 244.81 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3590.74 | 1079.34 | 0.00 | 0.00 | 0.00 | 492.46 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 646.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 207.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 447.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 541.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 112.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 368.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 36.59 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 244.81 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 289.99 | 234.22 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 943.94 | 283.74 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 289.99 | 234.22 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 943.94 | 283.74 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3590.74 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3590.74 | 100.00 |
Total On-Site and Utility Electric Sources | 3590.74 | 100.00 |
Total Electricity End Uses | 3590.74 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 492.46 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 492.46 | 100.00 |
Total Water End Uses | 492.46 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 3.00 |
Time Setpoint Not Met During Occupied Cooling | 1717.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7830.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09 |
RunPeriod | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 6.9965 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 17.8681 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 17.8681 | 5734.7436 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 9.6875 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 24.3264 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 9.6875 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 8.5250 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 6.7813 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 13.2396 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 9.6875 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 11.9479 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 10.5486 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 6.7813 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 6.7813 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 11.9479 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 8.5250 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 8.5250 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 8.5250 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 8.5250 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_0.52_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_0.52_SHGC_0.40 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 2.653 | 0.426 | 0.308 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_0.52_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_0.52_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_0.52_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_0.52_SHGC_0.40 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 2.653 | 0.426 | 0.308 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_0.52_SHGC_0.40 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 2.653 | 0.426 | 0.308 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_0.52_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_0.52_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_0.52_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_0.52_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_0.52_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_0.52_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_0.52_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_0.52_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_0.52_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_0.52_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_0.52_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_0.52_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_0.52_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_0.52_SHGC_0.40 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_0.52_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_0.52_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 97.22 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 211.08 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BA05F7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E02487 |
F67E1F | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FE5A3C |
7EB6E7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E85BB5 |
D18914 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | C114C1 |
D4B39B | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E326E4 |
D2D3BC | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
C528DA | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
EFD3F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
62B5AF | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 997723 |
71E924 | SWINGING DOOR_CON | 2.839 | 2.839 | 2.97 | 8E5BB9 |
3C44F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
49526E | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
865AE8 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
5E66D1 | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 529072 |
E14DAE | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | D95F04 |
84A1D5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 3330D8 |
9CB8E5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
E4A528 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
24BAF7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FB3814 |
19E57D | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FCD12D |
EDE769 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 5507DC |
1C9872 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 2E2D0C |
F402E9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 270BCE |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 72852.60 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 167547.69 | 115738.80 | 51808.89 | 0.69 | 3.40 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 199370.08 | 150215.98 | 49154.10 | 0.75 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 162301.0 | 2.98 | 10.18 | N/A | 11.31 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 191539.2 | 2.89 | 9.85 | N/A | 10.97 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 2007.61 | 1988.76 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 83.31 | 82.53 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 4953.41 | 3374.73 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1213.62 | 1202.23 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1533.59 | 1519.19 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 369.01 | 251.40 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 258.44 | 256.02 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 652.73 | 444.70 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 4043.31 | 2754.68 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 180.88 | 123.23 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 247.11 | 168.36 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 288.19 | 196.34 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 4062.02 | 2767.43 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 558.51 | 380.51 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1254.75 | 1242.98 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3221.28 | 2194.64 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 808.16 | 550.60 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1646.38 | 1121.67 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 492.85 | 488.23 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 2342.21 | 1595.73 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 336.52 | 229.27 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 6134.35 | 4179.30 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1254.75 | 1242.98 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 817.44 | 556.92 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 994.49 | 677.54 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 123.07 | 83.85 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 1101.29 | 750.30 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1254.75 | 1242.98 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 1182.39 | 805.55 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13947.13 | 13816.22 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14189.97 | 14056.78 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22120.85 | 21913.23 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1505.71 | 1491.57 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 971.16 | 661.65 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2634.98 | 2610.25 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4712.30 | 4668.07 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1254.75 | 1242.98 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9933.47 | 9840.24 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 2699.58 | 1839.21 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 252.97 | 172.35 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 8281.65 | 8203.92 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 455.37 | 310.24 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 194.75 | 132.69 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2927.76 | 2900.28 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1301.23 | 1289.01 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 4182.51 | 4143.26 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 3873.41 | 3837.06 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1179.03 | 803.27 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 580.07 | 395.20 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 3304.04 | 3273.03 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 821.79 | 730.43 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 982.75 | 973.53 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 83.65 | 56.99 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 1006.19 | 996.74 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 294.98 | 278.47 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2467.35 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1462.28 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 140.94 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3995.69 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7402.80 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9870.40 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1241.59 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4355.67 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2899.43 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10857.44 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3442.30 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5428.72 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 344.34 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 284.20 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 274.49 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 281.41 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 281.41 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 281.41 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 437.30 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 255.83 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 568.51 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 682.21 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 1680.02 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 665.36 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 4894.90 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 864.48 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 652.37 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 688.61 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 159.18 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 341.11 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 409.33 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 516.18 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 3402.79 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1185.36 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1233.80 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 6395.89 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 94.01 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 877.22 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 236.29 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 444.20 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 383.75 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2427.20 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 4386.85 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 998.83 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 6112.77 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1719.24 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1233.80 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 18235.68 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6736.00 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1919.24 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 678.93 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 277.59 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 5285.60 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6447.10 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3325.94 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 641.43 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 1969.84 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2830.31 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1771.50 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2834.80 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1395.48 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 30108.17 | 28324.55 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 30108.17 | 28324.55 | - |
AHU-2_HEATC | Coil:Heating:Water | 59133.15 | 54724.43 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 7.15 | 16332.72 | 2283.73 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.56 | 23995.23 | 2271.59 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.0016 | 399.16 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.00 | 0.00 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 162300.95 | 2.98 | 10.18 | 11.31 | 8.1530 | 3.23 | 11.02 | 6.4070 | 3.43 | 11.72 | 4.2677 | 3.56 | 12.16 | 1.8756 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 191539.21 | 2.89 | 9.85 | 10.97 | 12.0420 | 3.12 | 10.64 | 9.0595 | 3.35 | 11.45 | 5.7294 | 3.49 | 11.89 | 2.5519 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 852.80 | 852.80 | 0.063 | 0.068 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.23 | 0.00879 |
FLOOR 1 CAFE | 4503.68 | 4503.68 | 0.335 | 0.335 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.23 | 0.00879 |
FLOOR 1 CLEAN | 552.29 | 552.29 | 0.041 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.27 | 0.00879 |
FLOOR 1 CLEAN WORK | 689.63 | 689.63 | 0.051 | 0.052 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 25.15 | 0.00879 |
FLOOR 1 DICTATION | 348.08 | 348.08 | 0.025 | 0.025 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 DRESSING ROOM | 172.65 | 172.65 | 0.013 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
FLOOR 1 HUMID | 170.15 | 170.15 | 0.012 | 0.012 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 IT ROOM | 262.35 | 262.35 | 0.020 | 0.020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 28.88 | 0.00879 |
FLOOR 1 LOBBY | 3697.54 | 3697.54 | 0.275 | 0.275 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 27.25 | 0.00879 |
FLOOR 1 LOCKER ROOM | 2931.95 | 2931.95 | 0.218 | 0.218 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
FLOOR 1 LOUNGE | 1498.54 | 1498.54 | 0.111 | 0.111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
FLOOR 1 MRI CONTROL ROOM | 1817.77 | 1817.77 | 0.135 | 0.159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22 | 0.00879 |
FLOOR 1 MRI ROOM | 4520.76 | 4520.76 | 0.336 | 0.415 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.08 | 0.00879 |
FLOOR 1 NOURISHMENT | 743.99 | 743.99 | 0.055 | 0.055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35 | 0.00879 |
FLOOR 1 NURSE STATION | 1002.33 | 1002.33 | 0.075 | 0.075 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 23.35 | 0.00879 |
FLOOR 1 OFFICE | 1076.34 | 1076.34 | 0.080 | 0.080 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97 | 0.00879 |
FLOOR 1 OPERATING ROOM 1 | 6862.27 | 6862.27 | 0.787 | 0.787 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 26.75 | 0.00879 |
FLOOR 1 OPERATING ROOM 2 | 6981.78 | 6981.78 | 0.801 | 0.801 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97 | 0.00879 |
FLOOR 1 OPERATING ROOM 3 | 5797.91 | 5797.91 | 0.628 | 0.749 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 07:20:00 | 20.53 | 0.00879 |
FLOOR 1 PACU | 518.70 | 518.70 | 0.039 | 0.051 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 23.97 | 0.00879 |
FLOOR 1 PRE-OP ROOM 1 | 601.54 | 601.54 | 0.045 | 0.089 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 27.25 | 0.00879 |
FLOOR 1 PRE-OP ROOM 2 | 1060.69 | 1060.69 | 0.079 | 0.160 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:30:00 | 22.69 | 0.00879 |
FLOOR 1 PROCEDURE ROOM | 1655.37 | 1655.37 | 0.123 | 0.336 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.30 | 0.00879 |
FLOOR 1 RECEPTION | 2456.65 | 2456.65 | 0.183 | 0.183 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40 | 0.00879 |
FLOOR 1 RECOVERY ROOM | 4331.93 | 4331.93 | 0.322 | 0.322 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31 | 0.00879 |
FLOOR 1 SCHEDULING | 414.54 | 414.54 | 0.031 | 0.031 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
FLOOR 1 SOIL | 548.04 | 548.04 | 0.041 | 0.099 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.56 | 0.00879 |
FLOOR 1 SOIL HOLD | 223.79 | 223.79 | 0.017 | 0.044 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 28.88 | 0.00879 |
FLOOR 1 SOIL WORK | 737.10 | 737.10 | 0.055 | 0.142 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.86 | 0.00879 |
FLOOR 1 STEP DOWN | 2554.65 | 2554.65 | 0.190 | 0.190 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.30 | 0.00879 |
FLOOR 2 CONFERENCE | 3303.07 | 3303.07 | 0.290 | 0.290 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31 | 0.00879 |
FLOOR 2 DICTATION | 254.50 | 254.50 | 0.022 | 0.022 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM 1 | 3070.64 | 3070.64 | 0.270 | 0.270 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 27.94 | 0.00879 |
FLOOR 2 EXAM 2 | 2769.67 | 2769.67 | 0.243 | 0.255 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40 | 0.00879 |
FLOOR 2 EXAM 3 | 3842.95 | 3842.95 | 0.338 | 0.340 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31 | 0.00879 |
FLOOR 2 EXAM 4 | 760.36 | 760.36 | 0.067 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
FLOOR 2 EXAM 5 | 2474.05 | 2474.05 | 0.217 | 0.217 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.27 | 0.00879 |
FLOOR 2 EXAM 6 | 998.27 | 998.27 | 0.088 | 0.106 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
FLOOR 2 EXAM 7 | 3096.43 | 3096.43 | 0.272 | 0.374 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40 | 0.00879 |
FLOOR 2 EXAM 8 | 1242.73 | 1242.73 | 0.109 | 0.127 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40 | 0.00879 |
FLOOR 2 EXAM 9 | 1662.63 | 1662.63 | 0.146 | 0.187 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40 | 0.00879 |
FLOOR 2 LOUNGE | 401.47 | 401.47 | 0.035 | 0.035 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36 | 0.00879 |
FLOOR 2 NURSE STATION 1 | 639.46 | 639.46 | 0.056 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36 | 0.00879 |
FLOOR 2 NURSE STATION 2 | 775.99 | 775.99 | 0.068 | 0.068 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36 | 0.00879 |
FLOOR 2 OFFICE | 3169.52 | 3169.52 | 0.278 | 0.278 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.27 | 0.00879 |
FLOOR 2 RECEPTION | 6124.24 | 6124.24 | 0.538 | 0.538 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98 | 0.00879 |
FLOOR 2 SCHEDULING 1 | 933.45 | 933.45 | 0.082 | 0.082 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:30:00 | 22.69 | 0.00879 |
FLOOR 2 SCHEDULING 2 | 1024.19 | 1024.19 | 0.090 | 0.090 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36 | 0.00879 |
FLOOR 2 WORK | 4447.81 | 4447.81 | 0.391 | 0.391 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19 | 0.00879 |
FLOOR 2 X-RAY | 9426.02 | 9426.02 | 0.828 | 0.849 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
FLOOR 3 DRESSING ROOM | 184.27 | 184.27 | 0.016 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 HUMID | 463.12 | 463.12 | 0.041 | 0.041 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 LOCKER | 720.23 | 720.23 | 0.063 | 0.063 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
FLOOR 3 LOUNGE | 4261.87 | 4261.87 | 0.374 | 0.374 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 OFFICE | 10289.65 | 10289.65 | 0.904 | 0.904 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 PHYSICAL THERAPY 1 | 10357.84 | 10357.84 | 0.910 | 0.910 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
FLOOR 3 PHYSICAL THERAPY 2 | 2877.69 | 2877.69 | 0.253 | 0.279 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40 | 0.00879 |
FLOOR 3 TREATMENT | 2459.08 | 2459.08 | 0.216 | 0.225 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40 | 0.00879 |
FLOOR 3 WORK | 3637.12 | 3637.12 | 0.319 | 0.319 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.86 | 0.00879 |
FLOOR 1 BIO HAZ | 70.94 | 70.94 | 0.005 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 ELECTRICAL ROOM | 594.23 | 594.23 | 0.044 | 0.044 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 27.01 | 0.00879 |
FLOOR 1 ELEVATOR PUMP ROOM | 3680.94 | 3680.94 | 0.274 | 0.274 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 27.60 | 0.00879 |
FLOOR 1 IT HALL | 230.02 | 230.02 | 0.017 | 0.017 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 LOBBY HALL | 528.13 | 528.13 | 0.038 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 LOBBY TOILET | 431.19 | 431.19 | 0.031 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 LOCKER ROOM HALL | 757.99 | 757.99 | 0.055 | 0.055 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 MED GAS | 162.48 | 162.48 | 0.012 | 0.012 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14 | 0.00879 |
FLOOR 1 MRI HALL | 316.08 | 316.08 | 0.023 | 0.023 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 MRI TOILET | 128.08 | 128.08 | 0.010 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98 | 0.00879 |
FLOOR 1 NURSE HALL | 936.13 | 936.13 | 0.067 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 NURSE JANITOR | 114.73 | 114.73 | 0.008 | 0.008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 NURSE TOILET | 142.91 | 142.91 | 0.010 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 PRE-OP HALL | 913.26 | 913.26 | 0.066 | 0.066 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 PRE-OP TOILET | 184.17 | 184.17 | 0.014 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
FLOOR 1 RECEPTION HALL | 237.04 | 237.04 | 0.017 | 0.017 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 SCRUB | 177.30 | 177.30 | 0.013 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:10:00 | 22.03 | 0.00879 |
FLOOR 1 STERILE HALL | 1073.37 | 1073.37 | 0.080 | 0.080 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28.88 | 0.00879 |
FLOOR 1 STERILE STORAGE | 544.23 | 544.23 | 0.039 | 0.039 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 STORAGE | 1369.14 | 1369.14 | 0.102 | 0.102 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:00:00 | 28.78 | 0.00879 |
FLOOR 1 SUB-STERILE | 748.14 | 748.14 | 0.056 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.27 | 0.00879 |
FLOOR 1 UTILITY HALL | 576.44 | 576.44 | 0.043 | 0.043 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:30:00 | 22.69 | 0.00879 |
FLOOR 1 UTILITY JANITOR | 77.60 | 77.60 | 0.006 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 1 UTILITY ROOM | 822.20 | 822.20 | 0.061 | 0.061 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 25.15 | 0.00879 |
FLOOR 1 VESTIBULE | 268.54 | 268.54 | 0.020 | 0.020 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 27.25 | 0.00879 |
FLOOR 2 CONFERENCE TOILET | 202.08 | 202.08 | 0.017 | 0.050 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM HALL 1 | 674.95 | 674.95 | 0.059 | 0.059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90 | 0.00879 |
FLOOR 2 EXAM HALL 2 | 577.73 | 577.73 | 0.049 | 0.049 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM HALL 3 | 557.75 | 557.75 | 0.047 | 0.047 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM HALL 4 | 541.32 | 541.32 | 0.046 | 0.046 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM HALL 5 | 570.34 | 570.34 | 0.048 | 0.048 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 EXAM HALL 6 | 568.46 | 568.46 | 0.048 | 0.048 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 JANITOR | 365.60 | 365.60 | 0.031 | 0.031 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 OFFICE HALL | 1304.18 | 1304.18 | 0.115 | 0.115 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:10:00 | 22.03 | 0.00879 |
FLOOR 2 RECEPTION HALL | 1758.23 | 1758.23 | 0.149 | 0.149 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 RECEPTION TOILET | 375.32 | 375.32 | 0.032 | 0.099 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 STORAGE 1 | 173.06 | 173.06 | 0.015 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 STORAGE 2 | 287.37 | 287.37 | 0.024 | 0.024 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 STORAGE 3 | 374.87 | 374.87 | 0.032 | 0.032 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 UTILITY | 661.43 | 661.43 | 0.058 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.56 | 0.00879 |
FLOOR 2 WORK HALL | 2383.70 | 2383.70 | 0.202 | 0.202 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 2 WORK TOILET | 196.99 | 196.99 | 0.017 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 19.45 | 0.00879 |
FLOOR 3 ELEVATOR HALL | 858.79 | 858.79 | 0.075 | 0.075 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40 | 0.00879 |
FLOOR 3 JANITOR | 191.22 | 191.22 | 0.017 | 0.017 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 27.25 | 0.00879 |
FLOOR 3 LOUNGE TOILET | 678.02 | 678.02 | 0.060 | 0.151 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 29.40 | 0.00879 |
FLOOR 3 MECHANICAL | 3781.42 | 3781.42 | 0.332 | 0.332 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 24.56 | 0.00879 |
FLOOR 3 MECHANICAL HALL | 967.45 | 967.45 | 0.085 | 0.085 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46 | 0.00879 |
FLOOR 3 OFFICE HALL | 2349.89 | 2349.89 | 0.206 | 0.206 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40 | 0.00879 |
FLOOR 3 OFFICE TOILET | 173.29 | 173.29 | 0.015 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 27.08 | 0.00879 |
FLOOR 3 PHYSICAL THERAPY TOILET | 257.12 | 257.12 | 0.023 | 0.066 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 STORAGE 1 | 266.16 | 266.16 | 0.023 | 0.023 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40 | 0.00879 |
FLOOR 3 STORAGE 2 | 239.64 | 239.64 | 0.021 | 0.021 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40 | 0.00879 |
FLOOR 3 UNDEVELOPED 1 | 9902.84 | 9902.84 | 0.870 | 0.870 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19 | 0.00879 |
FLOOR 3 UNDEVELOPED 2 | 5233.16 | 5233.16 | 0.460 | 0.460 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.30 | 0.00879 |
FLOOR 3 UTILITY | 431.52 | 431.52 | 0.038 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40 | 0.00879 |
NE STAIR | 1322.92 | 1322.92 | 0.116 | 0.116 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31 | 0.00879 |
NW ELEVATOR | 1180.34 | 1180.34 | 0.104 | 0.104 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 27.25 | 0.00879 |
NW STAIR | 1289.68 | 1289.68 | 0.113 | 0.113 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 29.19 | 0.00879 |
SW STAIR | 1067.90 | 1067.90 | 0.094 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 28.64 | 0.00879 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 130.33 | 130.33 | 0.006 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 CAFE | 68.20 | 68.20 | 0.003 | 0.184 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -4.20 | 0.00269 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 DRESSING ROOM | 204.07 | 204.07 | 0.009 | 0.009 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.000 | 0.004 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 LOBBY | 516.05 | 516.05 | 0.022 | 0.032 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.000 | 0.042 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 0.00 | 0.000 | 0.239 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.000 | 0.052 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PROCEDURE ROOM | 11.19 | 11.19 | 0.000 | 0.108 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -4.20 | 0.00269 |
FLOOR 1 RECEPTION | 0.00 | 0.00 | 0.000 | 0.050 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 RECOVERY ROOM | 409.17 | 409.17 | 0.017 | 0.161 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 SCHEDULING | 8.88 | 8.88 | 0.000 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20 | 0.00269 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 SOIL HOLD | 0.00 | 0.00 | 0.000 | 0.008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 STEP DOWN | 592.20 | 592.20 | 0.025 | 0.090 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 CONFERENCE | 1026.93 | 1026.93 | 0.044 | 0.049 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 EXAM 1 | 1045.57 | 1045.57 | 0.045 | 0.051 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 2 | 77.03 | 77.03 | 0.003 | 0.076 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 3 | 99.66 | 99.66 | 0.004 | 0.102 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 4 | 251.52 | 251.52 | 0.011 | 0.012 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 5 | 712.82 | 712.82 | 0.030 | 0.050 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 6 | 352.73 | 352.73 | 0.015 | 0.032 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.000 | 0.112 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 EXAM 8 | 297.96 | 297.96 | 0.013 | 0.038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM 9 | 6.70 | 6.70 | 0.000 | 0.056 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -4.20 | 0.00269 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 OFFICE | 1356.25 | 1356.25 | 0.058 | 0.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 RECEPTION | 1312.49 | 1312.49 | 0.055 | 0.098 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 WORK | 34.46 | 34.46 | 0.001 | 0.068 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -4.20 | 0.00269 |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 3 DRESSING ROOM | 74.12 | 74.12 | 0.003 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 HUMID | 141.58 | 141.58 | 0.006 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 LOCKER | 120.93 | 120.93 | 0.005 | 0.008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 LOUNGE | 118.46 | 118.46 | 0.005 | 0.048 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -4.20 | 0.00269 |
FLOOR 3 OFFICE | 3466.46 | 3466.46 | 0.146 | 0.146 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 PHYSICAL THERAPY 1 | 3096.43 | 3096.43 | 0.132 | 0.184 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 PHYSICAL THERAPY 2 | 905.33 | 905.33 | 0.038 | 0.084 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 TREATMENT | 549.29 | 549.29 | 0.023 | 0.067 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 WORK | 1590.79 | 1590.79 | 0.068 | 0.068 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 BIO HAZ | 65.30 | 65.30 | 0.003 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 ELEVATOR PUMP ROOM | 269.15 | 269.15 | 0.011 | 0.011 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.000 | 0.004 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.000 | 0.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 LOBBY TOILET | 171.50 | 171.50 | 0.007 | 0.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 MED GAS | 388.08 | 388.08 | 0.017 | 0.017 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.000 | 0.004 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 MRI TOILET | 76.43 | 76.43 | 0.003 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.000 | 0.014 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.000 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 PRE-OP TOILET | 149.07 | 149.07 | 0.006 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 SCRUB | 39.61 | 39.61 | 0.002 | 0.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 STERILE HALL | 47.12 | 47.12 | 0.002 | 0.017 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 1 STORAGE | 2623.61 | 2623.61 | 0.112 | 0.112 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 SUB-STERILE | 471.06 | 471.06 | 0.020 | 0.020 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 UTILITY HALL | 778.69 | 778.69 | 0.033 | 0.033 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 UTILITY JANITOR | 20.04 | 20.04 | 0.001 | 0.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 UTILITY ROOM | 801.34 | 801.34 | 0.034 | 0.034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 1 VESTIBULE | 200.27 | 200.27 | 0.009 | 0.009 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 CONFERENCE TOILET | 35.68 | 35.68 | 0.002 | 0.002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM HALL 1 | 171.57 | 171.57 | 0.007 | 0.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM HALL 2 | 34.84 | 34.84 | 0.002 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM HALL 3 | 64.80 | 64.80 | 0.003 | 0.005 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 EXAM HALL 6 | 1.52 | 1.52 | 0.000 | 0.006 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -4.20 | 0.00269 |
FLOOR 2 JANITOR | 350.19 | 350.19 | 0.015 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 OFFICE HALL | 262.63 | 262.63 | 0.011 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 STORAGE 1 | 31.15 | 31.15 | 0.001 | 0.003 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 STORAGE 2 | 2.06 | 2.06 | 0.000 | 0.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | -4.20 | 0.00269 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.000 | 0.008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 UTILITY | 414.67 | 414.67 | 0.018 | 0.018 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.000 | 0.024 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00269 | |
FLOOR 2 WORK TOILET | 205.14 | 205.14 | 0.009 | 0.009 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 ELEVATOR HALL | 711.20 | 711.20 | 0.030 | 0.030 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 JANITOR | 356.07 | 356.07 | 0.015 | 0.015 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 LOUNGE TOILET | 534.01 | 534.01 | 0.023 | 0.023 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 MECHANICAL HALL | 807.40 | 807.40 | 0.034 | 0.034 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 OFFICE HALL | 1383.95 | 1383.95 | 0.059 | 0.059 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 OFFICE TOILET | 236.96 | 236.96 | 0.010 | 0.010 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 PHYSICAL THERAPY TOILET | 155.47 | 155.47 | 0.007 | 0.007 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 STORAGE 1 | 302.95 | 302.95 | 0.013 | 0.013 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 STORAGE 2 | 224.58 | 224.58 | 0.010 | 0.010 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 UNDEVELOPED 1 | 3899.40 | 3899.40 | 0.165 | 0.165 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 UNDEVELOPED 2 | 2692.47 | 2692.47 | 0.114 | 0.114 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
FLOOR 3 UTILITY | 519.72 | 519.72 | 0.022 | 0.022 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
NE STAIR | 2273.50 | 2273.50 | 0.097 | 0.097 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
NW ELEVATOR | 1426.49 | 1426.49 | 0.061 | 0.061 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
NW STAIR | 2279.70 | 2279.70 | 0.098 | 0.098 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
SW STAIR | 1122.10 | 1122.10 | 0.048 | 0.048 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -4.20 | 0.00269 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 7.15 | 7.15 | 2.24 | 2.24 |
AHU-2 | 10.56 | 10.56 | 2.56 | 2.56 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AHU-2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.56 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
FLOOR 2 CONFERENCE | AHU-2_DCV | 0.000000 | 0.001575 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 DICTATION | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 3 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 4 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 5 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 6 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 7 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 8 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 9 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 1 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 2 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION | AHU-2_DCV | 0.000000 | 0.001067 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 1 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 2 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 X-RAY | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 DRESSING ROOM | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 HUMID | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOCKER | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 TREATMENT | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 CONFERENCE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 1 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 2 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 3 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 4 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 5 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 6 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 3 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 ELEVATOR HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
NE STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW ELEVATOR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
SW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 4405.67 | 7830.00 | 4405.67 |
FLOOR 1 CAFE | 892.50 | 7733.33 | 892.50 |
FLOOR 1 CLEAN | 2130.17 | 7830.00 | 2130.17 |
FLOOR 1 CLEAN WORK | 3396.33 | 7830.00 | 3396.33 |
FLOOR 1 DICTATION | 252.17 | 7830.00 | 252.17 |
FLOOR 1 DRESSING ROOM | 2824.33 | 7830.00 | 2824.33 |
FLOOR 1 HUMID | 57.00 | 7830.00 | 57.00 |
FLOOR 1 IT ROOM | 621.50 | 7830.00 | 621.50 |
FLOOR 1 LOBBY | 823.83 | 7830.00 | 823.83 |
FLOOR 1 LOCKER ROOM | 129.17 | 7830.00 | 129.17 |
FLOOR 1 LOUNGE | 76.50 | 7830.00 | 76.50 |
FLOOR 1 MRI CONTROL ROOM | 154.33 | 7830.00 | 154.33 |
FLOOR 1 MRI ROOM | 38.83 | 7830.00 | 38.83 |
FLOOR 1 NOURISHMENT | 91.00 | 7830.00 | 91.00 |
FLOOR 1 NURSE STATION | 208.00 | 7830.00 | 208.00 |
FLOOR 1 OFFICE | 131.00 | 7830.00 | 131.00 |
FLOOR 1 OPERATING ROOM 1 | 5204.83 | 7830.00 | 5204.83 |
FLOOR 1 OPERATING ROOM 2 | 5107.67 | 7830.00 | 5107.67 |
FLOOR 1 OPERATING ROOM 3 | 7830.00 | 7830.00 | 7830.00 |
FLOOR 1 PACU | 3983.50 | 7830.00 | 3983.50 |
FLOOR 1 PRE-OP ROOM 1 | 4445.17 | 7830.00 | 4445.17 |
FLOOR 1 PRE-OP ROOM 2 | 4212.17 | 7830.00 | 4212.17 |
FLOOR 1 PROCEDURE ROOM | 4393.00 | 7830.00 | 4393.00 |
FLOOR 1 RECEPTION | 272.50 | 7830.00 | 272.50 |
FLOOR 1 RECOVERY ROOM | 4214.17 | 7830.00 | 4214.17 |
FLOOR 1 SCHEDULING | 769.50 | 7830.00 | 769.50 |
FLOOR 1 SOIL | 4514.67 | 7830.00 | 4514.67 |
FLOOR 1 SOIL HOLD | 4599.50 | 7830.00 | 4599.50 |
FLOOR 1 SOIL WORK | 4553.67 | 7830.00 | 4553.67 |
FLOOR 1 STEP DOWN | 3992.83 | 7828.83 | 3992.83 |
FLOOR 2 CONFERENCE | 2073.67 | 7747.33 | 2073.67 |
FLOOR 2 DICTATION | 618.50 | 7830.00 | 618.50 |
FLOOR 2 EXAM 1 | 3231.00 | 7793.67 | 3231.00 |
FLOOR 2 EXAM 2 | 3358.33 | 7830.00 | 3358.33 |
FLOOR 2 EXAM 3 | 3608.50 | 7830.00 | 3608.50 |
FLOOR 2 EXAM 4 | 3480.83 | 7830.00 | 3480.83 |
FLOOR 2 EXAM 5 | 2754.33 | 7830.00 | 2754.33 |
FLOOR 2 EXAM 6 | 3698.00 | 7830.00 | 3698.00 |
FLOOR 2 EXAM 7 | 3633.00 | 7830.00 | 3633.00 |
FLOOR 2 EXAM 8 | 3273.17 | 7830.00 | 3273.17 |
FLOOR 2 EXAM 9 | 3084.83 | 7830.00 | 3084.83 |
FLOOR 2 LOUNGE | 296.17 | 7830.00 | 296.17 |
FLOOR 2 NURSE STATION 1 | 325.17 | 7830.00 | 325.17 |
FLOOR 2 NURSE STATION 2 | 293.67 | 7830.00 | 293.67 |
FLOOR 2 OFFICE | 1511.33 | 7830.00 | 1511.33 |
FLOOR 2 RECEPTION | 1206.50 | 7830.00 | 1206.50 |
FLOOR 2 SCHEDULING 1 | 202.67 | 7830.00 | 202.67 |
FLOOR 2 SCHEDULING 2 | 254.50 | 7830.00 | 254.50 |
FLOOR 2 WORK | 398.00 | 7830.00 | 398.00 |
FLOOR 2 X-RAY | 3.17 | 7257.67 | 0.00 |
FLOOR 3 DRESSING ROOM | 1313.83 | 7830.00 | 1313.83 |
FLOOR 3 HUMID | 1005.17 | 7830.00 | 1005.17 |
FLOOR 3 LOCKER | 705.50 | 7830.00 | 705.50 |
FLOOR 3 LOUNGE | 599.50 | 7830.00 | 599.50 |
FLOOR 3 OFFICE | 1184.67 | 7830.00 | 1184.67 |
FLOOR 3 PHYSICAL THERAPY 1 | 4089.00 | 7658.00 | 4085.67 |
FLOOR 3 PHYSICAL THERAPY 2 | 3770.83 | 7830.00 | 3770.83 |
FLOOR 3 TREATMENT | 3224.67 | 7830.00 | 3224.67 |
FLOOR 3 WORK | 1988.33 | 7820.17 | 1988.33 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 7830.00 | 7830.00 | 7830.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 CAFE | 0.00 | 7.17 | 0.00 | 7.17 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DRESSING ROOM | 1.50 | 0.00 | 1.50 | 0.00 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 136.33 | 0.00 | 136.33 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 127.33 | 0.00 | 127.33 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 220.33 | 0.00 | 220.33 |
FLOOR 1 PACU | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PROCEDURE ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECOVERY ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCHEDULING | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL HOLD | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STEP DOWN | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE | 0.00 | 2.50 | 0.00 | 2.50 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 3 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 4 | 0.00 | 2.67 | 0.00 | 2.67 |
FLOOR 2 EXAM 5 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 6 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 8 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 2 | 0.00 | 3.00 | 0.00 | 3.00 |
FLOOR 2 OFFICE | 0.33 | 0.00 | 0.33 | 0.00 |
FLOOR 2 RECEPTION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 X-RAY | 0.00 | 1643.67 | 0.00 | 1643.67 |
FLOOR 3 DRESSING ROOM | 0.33 | 0.00 | 0.33 | 0.00 |
FLOOR 3 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOCKER | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE | 2.83 | 0.00 | 2.83 | 0.00 |
FLOOR 3 PHYSICAL THERAPY 1 | 0.00 | 2.17 | 0.00 | 2.17 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 TREATMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 WORK | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 1 BIO HAZ | 48.83 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 1.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 1.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 83.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.67 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 124.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 21.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 2.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 7.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 2878.50 | 229.17 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 9.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 7.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 11.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 5.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 4.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 6.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 3.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 3951.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 3.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 1.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 5.83 | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 33.67 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 5179.17 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 7.67 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 1.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.83 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 2.83 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 2.00 | 0.00 | 0.00 | 0.00 |
NE STAIR | 20.00 | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 4.33 | 0.00 | 0.00 | 0.00 |
NW STAIR | 37.17 | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.17 | 0.00 | 0.00 | 0.00 |
Facility | 4134.17 | 6749.83 | 3.00 | 1717.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:38
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000043 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.005185 | 0.000002 | 0.002820 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.335339 | 0.000043 | 0.067068 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.041080 | 0.000026 | 0.041080 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.051911 | 0.000033 | 0.051911 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.024981 | 0.000003 | 0.004996 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.012839 | 0.000006 | 0.008748 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.044189 | 0.000006 | 0.008838 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.273727 | 0.000035 | 0.054745 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.012245 | 0.000002 | 0.002449 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.016729 | 0.000002 | 0.003346 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.019510 | 0.000002 | 0.003902 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.274993 | 0.000035 | 0.054999 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.037811 | 0.000005 | 0.007562 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.218077 | 0.000028 | 0.043615 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.054711 | 0.000007 | 0.010942 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.111458 | 0.000014 | 0.022292 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.016683 | 0.000011 | 0.016683 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.158564 | 0.000020 | 0.031713 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.022782 | 0.000003 | 0.004556 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.415288 | 0.000053 | 0.083058 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.055340 | 0.000007 | 0.011068 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.067325 | 0.000009 | 0.013465 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.008332 | 0.000001 | 0.001666 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.074556 | 0.000009 | 0.014911 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.080046 | 0.000010 | 0.016009 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.786835 | 0.000300 | 0.472101 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.800535 | 0.000305 | 0.480321 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.748776 | 0.000476 | 0.748776 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000032 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.065746 | 0.000008 | 0.013149 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000057 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000101 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000214 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.182758 | 0.000023 | 0.036552 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.017126 | 0.000002 | 0.003425 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.322217 | 0.000178 | 0.280329 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.030828 | 0.000004 | 0.006166 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.013185 | 0.000002 | 0.002637 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000063 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000028 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000090 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.190018 | 0.000083 | 0.131112 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.079819 | 0.000010 | 0.015964 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.039270 | 0.000005 | 0.007854 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.111840 | 0.000071 | 0.111840 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.055634 | 0.000013 | 0.020053 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.042866 | 0.000021 | 0.033265 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.005663 | 0.000001 | 0.001133 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.061142 | 0.000022 | 0.034059 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.019969 | 0.000005 | 0.008552 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.290221 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.021635 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.269703 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.254836 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.339781 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.066783 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.217305 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.106182 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.127418 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.186879 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.059268 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.048916 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.047245 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.045766 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.048309 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.048130 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.031092 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.035259 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.056165 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.068155 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.278340 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.114522 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.538001 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.148796 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.081973 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.089940 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.014698 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.024360 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.031693 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.058082 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.390601 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.201702 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 0.849452 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.016182 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.075412 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.040670 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.016791 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.063256 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.374321 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.332052 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.084953 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 0.903620 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.206348 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 0.909781 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.279375 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.023372 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.021043 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.224633 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 0.869584 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.459532 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.037892 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.319402 | ||
NE STAIR VAV BOX COMPONENT | 0.116168 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.103648 | ||
NW STAIR VAV BOX COMPONENT | 0.113249 | ||
SW STAIR VAV BOX COMPONENT | 0.093774 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 2007.61 | 0.000043 | 43.29 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 83.31 | 0.000002 | 1.80 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 1981.36 | 0.000043 | 106.80 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1213.62 | 0.000026 | 26.17 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1533.59 | 0.000033 | 33.07 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 147.60 | 0.000003 | 7.96 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 258.44 | 0.000006 | 5.57 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 261.09 | 0.000006 | 14.07 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 1617.32 | 0.000035 | 87.18 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 72.35 | 0.000002 | 3.90 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 98.85 | 0.000002 | 5.33 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 115.28 | 0.000002 | 6.21 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 1624.81 | 0.000035 | 87.58 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 223.41 | 0.000005 | 12.04 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1254.75 | 0.000027 | 27.05 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 1288.51 | 0.000028 | 69.45 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 323.26 | 0.000007 | 17.42 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 658.55 | 0.000014 | 35.50 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 492.85 | 0.000011 | 10.63 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 936.88 | 0.000020 | 50.50 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 134.61 | 0.000003 | 7.26 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2453.74 | 0.000053 | 132.26 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1254.75 | 0.000027 | 27.05 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 326.98 | 0.000007 | 17.62 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 397.79 | 0.000009 | 21.44 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 49.23 | 0.000001 | 2.65 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 440.52 | 0.000009 | 23.75 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1254.75 | 0.000027 | 27.05 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 472.95 | 0.000010 | 25.49 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 13947.13 | 0.000300 | 300.72 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 14189.97 | 0.000305 | 305.95 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 22120.85 | 0.000476 | 476.95 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1505.71 | 0.000032 | 32.46 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 388.46 | 0.000008 | 20.94 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2634.98 | 0.000057 | 56.81 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 4712.30 | 0.000101 | 101.60 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1254.75 | 0.000027 | 27.05 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 9933.47 | 0.000214 | 214.18 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1079.83 | 0.000023 | 58.21 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 101.19 | 0.000002 | 5.45 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 8281.65 | 0.000178 | 178.56 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 182.15 | 0.000004 | 9.82 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 77.90 | 0.000002 | 4.20 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2927.76 | 0.000063 | 63.13 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1301.23 | 0.000028 | 28.06 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 4182.51 | 0.000090 | 90.18 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 3873.41 | 0.000083 | 83.52 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 471.61 | 0.000010 | 25.42 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 232.03 | 0.000005 | 12.51 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 3304.04 | 0.000071 | 71.24 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 592.41 | 0.000013 | 17.72 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 982.75 | 0.000021 | 21.19 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 33.46 | 0.000001 | 1.80 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 1006.19 | 0.000022 | 21.69 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 252.65 | 0.000005 | 6.36 |
AHU-1_HEATC | 30108.17 | 0.000648 | 489.86 |
AHU-1_EXTRAWATERHEATC | 30108.17 | 0.000648 | 489.86 |
AHU-2_HEATC | 59133.15 | 0.001273 | 957.63 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2467.35 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 1462.28 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 140.94 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 3995.69 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 7402.80 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 9870.40 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 1241.59 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 4355.67 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 2899.43 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 10857.44 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 3442.30 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 5428.72 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 344.34 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 284.20 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 274.49 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 281.41 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 281.41 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 281.41 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 437.30 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 255.83 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 568.51 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 682.21 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 1680.02 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 665.36 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 4894.90 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 864.48 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 0.000000 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 652.37 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 688.61 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 159.18 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 341.11 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 409.33 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 516.18 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 3402.79 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1185.36 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1233.80 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 6395.89 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 94.01 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 877.22 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 236.29 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 444.20 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 383.75 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 2427.20 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 4386.85 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 0.000000 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 998.83 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 6112.77 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 1719.24 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1233.80 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 18235.68 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 6736.00 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 1919.24 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 678.93 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 277.59 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 5285.60 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 6447.10 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 3325.94 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 641.43 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 1969.84 |
NE STAIR VAV BOX REHEAT COIL | 2830.31 |
NW ELEVATOR VAV BOX REHEAT COIL | 1771.50 |
NW STAIR VAV BOX REHEAT COIL | 2834.80 |
SW STAIR VAV BOX REHEAT COIL | 1395.48 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 7.15 |
AHU-2 AIR LOOP MAIN BRANCH | 10.56 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 7.15 |
AHU-2 | 10.56 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 7.15 | 2.07 |
AHU-2_OA_CONTROLLER | 10.56 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 7.15 | 167547.69 | 0.690781 | 2.38 | 55843.64 |
AHU-2_COOLC DXCOIL | 10.56 | 199370.08 | 0.753453 | 3.52 | 66450.05 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 7.15 |
AHU-2_FAN | 10.56 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.000648 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.000648 |
AHU-2_HEATC_CONTROLLER | 0.001273 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.001562 | 1.17 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.001562 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
HEATSYS1 PUMP | 0.001562 | 399.16 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 4.50 |
February | 19.46 | 5.82 |
March | 19.54 | 8.33 |
April | 19.46 | 10.85 |
May | 19.47 | 12.97 |
June | 19.52 | 15.59 |
July | 19.43 | 17.66 |
August | 19.55 | 18.80 |
September | 19.49 | 15.09 |
October | 19.42 | 11.43 |
November | 19.41 | 8.07 |
December | 19.40 | 5.42 |
Annual Sum or Average | 19.46 | 11.24 |
Minimum of Months | 19.40 | 4.50 |
Maximum of Months | 19.55 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.20 | 4.50 |
February | 20.29 | 5.82 |
March | 20.51 | 8.33 |
April | 20.64 | 10.85 |
May | 20.85 | 12.97 |
June | 21.35 | 15.59 |
July | 21.40 | 17.66 |
August | 21.50 | 18.80 |
September | 21.13 | 15.09 |
October | 20.55 | 11.43 |
November | 20.36 | 8.07 |
December | 20.25 | 5.42 |
Annual Sum or Average | 20.76 | 11.24 |
Minimum of Months | 20.20 | 4.50 |
Maximum of Months | 21.50 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.73 | 4.50 |
February | 20.90 | 5.82 |
March | 21.13 | 8.33 |
April | 21.10 | 10.85 |
May | 21.21 | 12.97 |
June | 21.41 | 15.59 |
July | 21.38 | 17.66 |
August | 21.53 | 18.80 |
September | 21.31 | 15.09 |
October | 21.03 | 11.43 |
November | 20.83 | 8.07 |
December | 20.74 | 5.42 |
Annual Sum or Average | 21.11 | 11.24 |
Minimum of Months | 20.73 | 4.50 |
Maximum of Months | 21.53 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.07 | 4.50 |
February | 20.11 | 5.82 |
March | 20.17 | 8.33 |
April | 19.97 | 10.85 |
May | 19.93 | 12.97 |
June | 20.05 | 15.59 |
July | 19.94 | 17.66 |
August | 20.11 | 18.80 |
September | 20.01 | 15.09 |
October | 19.90 | 11.43 |
November | 19.97 | 8.07 |
December | 20.04 | 5.42 |
Annual Sum or Average | 20.02 | 11.24 |
Minimum of Months | 19.90 | 4.50 |
Maximum of Months | 20.17 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.79 | 4.50 |
February | 19.83 | 5.82 |
March | 19.90 | 8.33 |
April | 19.75 | 10.85 |
May | 19.73 | 12.97 |
June | 19.83 | 15.59 |
July | 19.71 | 17.66 |
August | 19.87 | 18.80 |
September | 19.77 | 15.09 |
October | 19.68 | 11.43 |
November | 19.73 | 8.07 |
December | 19.77 | 5.42 |
Annual Sum or Average | 19.78 | 11.24 |
Minimum of Months | 19.68 | 4.50 |
Maximum of Months | 19.90 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 4.50 |
February | 21.55 | 5.82 |
March | 21.66 | 8.33 |
April | 21.57 | 10.85 |
May | 21.56 | 12.97 |
June | 21.74 | 15.59 |
July | 21.67 | 17.66 |
August | 21.79 | 18.80 |
September | 21.71 | 15.09 |
October | 21.55 | 11.43 |
November | 21.53 | 8.07 |
December | 21.53 | 5.42 |
Annual Sum or Average | 21.61 | 11.24 |
Minimum of Months | 21.49 | 4.50 |
Maximum of Months | 21.79 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 4.50 |
February | 19.85 | 5.82 |
March | 20.26 | 8.33 |
April | 20.52 | 10.85 |
May | 20.82 | 12.97 |
June | 21.25 | 15.59 |
July | 21.31 | 17.66 |
August | 21.41 | 18.80 |
September | 21.00 | 15.09 |
October | 20.33 | 11.43 |
November | 19.94 | 8.07 |
December | 19.71 | 5.42 |
Annual Sum or Average | 20.51 | 11.24 |
Minimum of Months | 19.69 | 4.50 |
Maximum of Months | 21.41 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | 4.50 |
February | 21.58 | 5.82 |
March | 21.78 | 8.33 |
April | 21.82 | 10.85 |
May | 21.89 | 12.97 |
June | 22.06 | 15.59 |
July | 22.04 | 17.66 |
August | 22.09 | 18.80 |
September | 21.98 | 15.09 |
October | 21.73 | 11.43 |
November | 21.58 | 8.07 |
December | 21.50 | 5.42 |
Annual Sum or Average | 21.79 | 11.24 |
Minimum of Months | 21.45 | 4.50 |
Maximum of Months | 22.09 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 4.50 |
February | 20.95 | 5.82 |
March | 21.10 | 8.33 |
April | 21.01 | 10.85 |
May | 21.07 | 12.97 |
June | 21.14 | 15.59 |
July | 21.07 | 17.66 |
August | 21.20 | 18.80 |
September | 21.05 | 15.09 |
October | 20.94 | 11.43 |
November | 20.93 | 8.07 |
December | 20.89 | 5.42 |
Annual Sum or Average | 21.02 | 11.24 |
Minimum of Months | 20.89 | 4.50 |
Maximum of Months | 21.20 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.50 |
February | 21.80 | 5.82 |
March | 21.89 | 8.33 |
April | 21.82 | 10.85 |
May | 21.80 | 12.97 |
June | 21.97 | 15.59 |
July | 21.93 | 17.66 |
August | 22.01 | 18.80 |
September | 21.95 | 15.09 |
October | 21.80 | 11.43 |
November | 21.79 | 8.07 |
December | 21.78 | 5.42 |
Annual Sum or Average | 21.86 | 11.24 |
Minimum of Months | 21.74 | 4.50 |
Maximum of Months | 22.01 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.79 | 4.50 |
February | 20.88 | 5.82 |
March | 21.06 | 8.33 |
April | 21.06 | 10.85 |
May | 21.15 | 12.97 |
June | 21.50 | 15.59 |
July | 21.46 | 17.66 |
August | 21.58 | 18.80 |
September | 21.41 | 15.09 |
October | 21.03 | 11.43 |
November | 20.93 | 8.07 |
December | 20.84 | 5.42 |
Annual Sum or Average | 21.14 | 11.24 |
Minimum of Months | 20.79 | 4.50 |
Maximum of Months | 21.58 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | 4.50 |
February | 21.16 | 5.82 |
March | 21.37 | 8.33 |
April | 21.37 | 10.85 |
May | 21.49 | 12.97 |
June | 21.78 | 15.59 |
July | 21.76 | 17.66 |
August | 21.85 | 18.80 |
September | 21.67 | 15.09 |
October | 21.32 | 11.43 |
November | 21.21 | 8.07 |
December | 21.12 | 5.42 |
Annual Sum or Average | 21.43 | 11.24 |
Minimum of Months | 21.07 | 4.50 |
Maximum of Months | 21.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | 4.50 |
February | 20.85 | 5.82 |
March | 21.18 | 8.33 |
April | 21.28 | 10.85 |
May | 21.48 | 12.97 |
June | 21.70 | 15.59 |
July | 21.74 | 17.66 |
August | 21.80 | 18.80 |
September | 21.59 | 15.09 |
October | 21.15 | 11.43 |
November | 20.89 | 8.07 |
December | 20.71 | 5.42 |
Annual Sum or Average | 21.25 | 11.24 |
Minimum of Months | 20.65 | 4.50 |
Maximum of Months | 21.80 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 4.50 |
February | 21.66 | 5.82 |
March | 21.84 | 8.33 |
April | 21.85 | 10.85 |
May | 21.89 | 12.97 |
June | 22.06 | 15.59 |
July | 22.07 | 17.66 |
August | 22.11 | 18.80 |
September | 22.03 | 15.09 |
October | 21.81 | 11.43 |
November | 21.68 | 8.07 |
December | 21.59 | 5.42 |
Annual Sum or Average | 21.84 | 11.24 |
Minimum of Months | 21.51 | 4.50 |
Maximum of Months | 22.11 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.44 | 4.50 |
February | 19.47 | 5.82 |
March | 19.57 | 8.33 |
April | 19.50 | 10.85 |
May | 19.52 | 12.97 |
June | 19.58 | 15.59 |
July | 19.50 | 17.66 |
August | 19.61 | 18.80 |
September | 19.50 | 15.09 |
October | 19.44 | 11.43 |
November | 19.44 | 8.07 |
December | 19.43 | 5.42 |
Annual Sum or Average | 19.50 | 11.24 |
Minimum of Months | 19.43 | 4.50 |
Maximum of Months | 19.61 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 4.50 |
February | 21.68 | 5.82 |
March | 21.85 | 8.33 |
April | 21.84 | 10.85 |
May | 21.89 | 12.97 |
June | 22.05 | 15.59 |
July | 22.04 | 17.66 |
August | 22.08 | 18.80 |
September | 22.00 | 15.09 |
October | 21.80 | 11.43 |
November | 21.72 | 8.07 |
December | 21.65 | 5.42 |
Annual Sum or Average | 21.85 | 11.24 |
Minimum of Months | 21.59 | 4.50 |
Maximum of Months | 22.08 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.37 | 4.50 |
February | 21.47 | 5.82 |
March | 21.64 | 8.33 |
April | 21.60 | 10.85 |
May | 21.62 | 12.97 |
June | 21.88 | 15.59 |
July | 21.86 | 17.66 |
August | 21.94 | 18.80 |
September | 21.86 | 15.09 |
October | 21.59 | 11.43 |
November | 21.51 | 8.07 |
December | 21.45 | 5.42 |
Annual Sum or Average | 21.65 | 11.24 |
Minimum of Months | 21.37 | 4.50 |
Maximum of Months | 21.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 4.50 |
February | 21.80 | 5.82 |
March | 21.92 | 8.33 |
April | 21.88 | 10.85 |
May | 21.90 | 12.97 |
June | 22.05 | 15.59 |
July | 22.03 | 17.66 |
August | 22.08 | 18.80 |
September | 22.00 | 15.09 |
October | 21.84 | 11.43 |
November | 21.81 | 8.07 |
December | 21.78 | 5.42 |
Annual Sum or Average | 21.90 | 11.24 |
Minimum of Months | 21.74 | 4.50 |
Maximum of Months | 22.08 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 4.50 |
February | 19.44 | 5.82 |
March | 19.59 | 8.33 |
April | 19.80 | 10.85 |
May | 20.16 | 12.97 |
June | 20.76 | 15.59 |
July | 21.00 | 17.66 |
August | 21.04 | 18.80 |
September | 20.30 | 15.09 |
October | 19.57 | 11.43 |
November | 19.46 | 8.07 |
December | 19.39 | 5.42 |
Annual Sum or Average | 20.00 | 11.24 |
Minimum of Months | 19.39 | 4.50 |
Maximum of Months | 21.04 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.86 | 4.50 |
February | 21.92 | 5.82 |
March | 22.02 | 8.33 |
April | 22.03 | 10.85 |
May | 22.06 | 12.97 |
June | 22.13 | 15.59 |
July | 22.13 | 17.66 |
August | 22.14 | 18.80 |
September | 22.09 | 15.09 |
October | 21.98 | 11.43 |
November | 21.92 | 8.07 |
December | 21.88 | 5.42 |
Annual Sum or Average | 22.01 | 11.24 |
Minimum of Months | 21.86 | 4.50 |
Maximum of Months | 22.14 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | 4.50 |
February | 21.39 | 5.82 |
March | 21.60 | 8.33 |
April | 21.62 | 10.85 |
May | 21.68 | 12.97 |
June | 21.91 | 15.59 |
July | 21.90 | 17.66 |
August | 21.97 | 18.80 |
September | 21.86 | 15.09 |
October | 21.57 | 11.43 |
November | 21.44 | 8.07 |
December | 21.34 | 5.42 |
Annual Sum or Average | 21.63 | 11.24 |
Minimum of Months | 21.26 | 4.50 |
Maximum of Months | 21.97 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | 4.50 |
February | 22.10 | 5.82 |
March | 22.13 | 8.33 |
April | 22.11 | 10.85 |
May | 22.11 | 12.97 |
June | 22.15 | 15.59 |
July | 22.15 | 17.66 |
August | 22.16 | 18.80 |
September | 22.13 | 15.09 |
October | 22.09 | 11.43 |
November | 22.07 | 8.07 |
December | 22.07 | 5.42 |
Annual Sum or Average | 22.11 | 11.24 |
Minimum of Months | 22.06 | 4.50 |
Maximum of Months | 22.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 4.50 |
February | 19.40 | 5.82 |
March | 19.48 | 8.33 |
April | 19.41 | 10.85 |
May | 19.43 | 12.97 |
June | 19.47 | 15.59 |
July | 19.37 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.38 | 11.43 |
November | 19.39 | 8.07 |
December | 19.37 | 5.42 |
Annual Sum or Average | 19.41 | 11.24 |
Minimum of Months | 19.37 | 4.50 |
Maximum of Months | 19.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | 4.50 |
February | 21.75 | 5.82 |
March | 21.84 | 8.33 |
April | 21.75 | 10.85 |
May | 21.74 | 12.97 |
June | 21.88 | 15.59 |
July | 21.83 | 17.66 |
August | 21.92 | 18.80 |
September | 21.85 | 15.09 |
October | 21.73 | 11.43 |
November | 21.72 | 8.07 |
December | 21.72 | 5.42 |
Annual Sum or Average | 21.79 | 11.24 |
Minimum of Months | 21.70 | 4.50 |
Maximum of Months | 21.92 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 4.50 |
February | 21.03 | 5.82 |
March | 21.21 | 8.33 |
April | 21.15 | 10.85 |
May | 21.18 | 12.97 |
June | 21.45 | 15.59 |
July | 21.41 | 17.66 |
August | 21.57 | 18.80 |
September | 21.45 | 15.09 |
October | 21.16 | 11.43 |
November | 21.03 | 8.07 |
December | 20.98 | 5.42 |
Annual Sum or Average | 21.21 | 11.24 |
Minimum of Months | 20.91 | 4.50 |
Maximum of Months | 21.57 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.54 | 4.50 |
February | 21.62 | 5.82 |
March | 21.75 | 8.33 |
April | 21.69 | 10.85 |
May | 21.68 | 12.97 |
June | 21.93 | 15.59 |
July | 21.91 | 17.66 |
August | 21.99 | 18.80 |
September | 21.93 | 15.09 |
October | 21.69 | 11.43 |
November | 21.64 | 8.07 |
December | 21.61 | 5.42 |
Annual Sum or Average | 21.75 | 11.24 |
Minimum of Months | 21.54 | 4.50 |
Maximum of Months | 21.99 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | 4.50 |
February | 21.60 | 5.82 |
March | 21.72 | 8.33 |
April | 21.63 | 10.85 |
May | 21.63 | 12.97 |
June | 21.79 | 15.59 |
July | 21.74 | 17.66 |
August | 21.85 | 18.80 |
September | 21.77 | 15.09 |
October | 21.61 | 11.43 |
November | 21.57 | 8.07 |
December | 21.56 | 5.42 |
Annual Sum or Average | 21.67 | 11.24 |
Minimum of Months | 21.53 | 4.50 |
Maximum of Months | 21.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.40 | 5.82 |
March | 19.48 | 8.33 |
April | 19.41 | 10.85 |
May | 19.43 | 12.97 |
June | 19.47 | 15.59 |
July | 19.37 | 17.66 |
August | 19.47 | 18.80 |
September | 19.41 | 15.09 |
October | 19.38 | 11.43 |
November | 19.39 | 8.07 |
December | 19.37 | 5.42 |
Annual Sum or Average | 19.41 | 11.24 |
Minimum of Months | 19.37 | 4.50 |
Maximum of Months | 19.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 4.50 |
February | 21.70 | 5.82 |
March | 21.85 | 8.33 |
April | 21.81 | 10.85 |
May | 21.83 | 12.97 |
June | 22.01 | 15.59 |
July | 22.00 | 17.66 |
August | 22.06 | 18.80 |
September | 21.99 | 15.09 |
October | 21.79 | 11.43 |
November | 21.72 | 8.07 |
December | 21.66 | 5.42 |
Annual Sum or Average | 21.83 | 11.24 |
Minimum of Months | 21.60 | 4.50 |
Maximum of Months | 22.06 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.74 | 4.50 |
February | 18.82 | 5.82 |
March | 18.98 | 8.33 |
April | 18.96 | 10.85 |
May | 18.97 | 12.97 |
June | 19.10 | 15.59 |
July | 19.12 | 17.66 |
August | 19.21 | 18.80 |
September | 19.05 | 15.09 |
October | 18.86 | 11.43 |
November | 18.76 | 8.07 |
December | 18.74 | 5.42 |
Annual Sum or Average | 18.94 | 11.24 |
Minimum of Months | 18.74 | 4.50 |
Maximum of Months | 19.21 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.90 | 4.50 |
February | 18.96 | 5.82 |
March | 19.09 | 8.33 |
April | 19.06 | 10.85 |
May | 19.06 | 12.97 |
June | 19.18 | 15.59 |
July | 19.17 | 17.66 |
August | 19.24 | 18.80 |
September | 19.10 | 15.09 |
October | 18.94 | 11.43 |
November | 18.90 | 8.07 |
December | 18.90 | 5.42 |
Annual Sum or Average | 19.04 | 11.24 |
Minimum of Months | 18.90 | 4.50 |
Maximum of Months | 19.24 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.35 | 4.50 |
February | 18.36 | 5.82 |
March | 18.34 | 8.33 |
April | 18.33 | 10.85 |
May | 18.32 | 12.97 |
June | 18.32 | 15.59 |
July | 18.32 | 17.66 |
August | 18.32 | 18.80 |
September | 18.32 | 15.09 |
October | 18.32 | 11.43 |
November | 18.33 | 8.07 |
December | 18.34 | 5.42 |
Annual Sum or Average | 18.33 | 11.24 |
Minimum of Months | 18.32 | 4.50 |
Maximum of Months | 18.36 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | 4.50 |
February | 19.57 | 5.82 |
March | 19.65 | 8.33 |
April | 19.54 | 10.85 |
May | 19.54 | 12.97 |
June | 19.59 | 15.59 |
July | 19.49 | 17.66 |
August | 19.61 | 18.80 |
September | 19.53 | 15.09 |
October | 19.49 | 11.43 |
November | 19.53 | 8.07 |
December | 19.54 | 5.42 |
Annual Sum or Average | 19.55 | 11.24 |
Minimum of Months | 19.49 | 4.50 |
Maximum of Months | 19.65 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 4.50 |
February | 21.08 | 5.82 |
March | 21.30 | 8.33 |
April | 21.30 | 10.85 |
May | 21.37 | 12.97 |
June | 21.68 | 15.59 |
July | 21.67 | 17.66 |
August | 21.78 | 18.80 |
September | 21.66 | 15.09 |
October | 21.30 | 11.43 |
November | 21.13 | 8.07 |
December | 21.04 | 5.42 |
Annual Sum or Average | 21.36 | 11.24 |
Minimum of Months | 20.95 | 4.50 |
Maximum of Months | 21.78 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.41 | 4.50 |
February | 19.43 | 5.82 |
March | 19.52 | 8.33 |
April | 19.44 | 10.85 |
May | 19.46 | 12.97 |
June | 19.51 | 15.59 |
July | 19.43 | 17.66 |
August | 19.54 | 18.80 |
September | 19.46 | 15.09 |
October | 19.41 | 11.43 |
November | 19.41 | 8.07 |
December | 19.40 | 5.42 |
Annual Sum or Average | 19.45 | 11.24 |
Minimum of Months | 19.40 | 4.50 |
Maximum of Months | 19.54 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.45 | 4.50 |
February | 19.47 | 5.82 |
March | 19.55 | 8.33 |
April | 19.45 | 10.85 |
May | 19.46 | 12.97 |
June | 19.51 | 15.59 |
July | 19.41 | 17.66 |
August | 19.52 | 18.80 |
September | 19.45 | 15.09 |
October | 19.42 | 11.43 |
November | 19.44 | 8.07 |
December | 19.44 | 5.42 |
Annual Sum or Average | 19.47 | 11.24 |
Minimum of Months | 19.41 | 4.50 |
Maximum of Months | 19.55 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 4.50 |
February | 19.40 | 5.82 |
March | 19.47 | 8.33 |
April | 19.41 | 10.85 |
May | 19.43 | 12.97 |
June | 19.47 | 15.59 |
July | 19.38 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.38 | 11.43 |
November | 19.39 | 8.07 |
December | 19.37 | 5.42 |
Annual Sum or Average | 19.42 | 11.24 |
Minimum of Months | 19.37 | 4.50 |
Maximum of Months | 19.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 4.50 |
February | 19.42 | 5.82 |
March | 19.49 | 8.33 |
April | 19.43 | 10.85 |
May | 19.45 | 12.97 |
June | 19.48 | 15.59 |
July | 19.39 | 17.66 |
August | 19.49 | 18.80 |
September | 19.43 | 15.09 |
October | 19.40 | 11.43 |
November | 19.40 | 8.07 |
December | 19.39 | 5.42 |
Annual Sum or Average | 19.43 | 11.24 |
Minimum of Months | 19.39 | 4.50 |
Maximum of Months | 19.49 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | 4.50 |
February | 21.44 | 5.82 |
March | 21.62 | 8.33 |
April | 21.61 | 10.85 |
May | 21.66 | 12.97 |
June | 21.86 | 15.59 |
July | 21.85 | 17.66 |
August | 21.94 | 18.80 |
September | 21.82 | 15.09 |
October | 21.57 | 11.43 |
November | 21.44 | 8.07 |
December | 21.34 | 5.42 |
Annual Sum or Average | 21.62 | 11.24 |
Minimum of Months | 21.28 | 4.50 |
Maximum of Months | 21.94 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 4.50 |
February | 21.28 | 5.82 |
March | 21.48 | 8.33 |
April | 21.45 | 10.85 |
May | 21.49 | 12.97 |
June | 21.77 | 15.59 |
July | 21.75 | 17.66 |
August | 21.85 | 18.80 |
September | 21.75 | 15.09 |
October | 21.45 | 11.43 |
November | 21.32 | 8.07 |
December | 21.25 | 5.42 |
Annual Sum or Average | 21.50 | 11.24 |
Minimum of Months | 21.16 | 4.50 |
Maximum of Months | 21.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.43 | 4.50 |
February | 19.49 | 5.82 |
March | 19.58 | 8.33 |
April | 19.49 | 10.85 |
May | 19.49 | 12.97 |
June | 19.54 | 15.59 |
July | 19.47 | 17.66 |
August | 19.62 | 18.80 |
September | 19.56 | 15.09 |
October | 19.46 | 11.43 |
November | 19.43 | 8.07 |
December | 19.42 | 5.42 |
Annual Sum or Average | 19.50 | 11.24 |
Minimum of Months | 19.42 | 4.50 |
Maximum of Months | 19.62 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.84 | 4.50 |
February | 21.00 | 5.82 |
March | 21.24 | 8.33 |
April | 21.23 | 10.85 |
May | 21.31 | 12.97 |
June | 21.56 | 15.59 |
July | 21.56 | 17.66 |
August | 21.68 | 18.80 |
September | 21.54 | 15.09 |
October | 21.22 | 11.43 |
November | 21.04 | 8.07 |
December | 20.91 | 5.42 |
Annual Sum or Average | 21.26 | 11.24 |
Minimum of Months | 20.84 | 4.50 |
Maximum of Months | 21.68 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | 4.50 |
February | 20.83 | 5.82 |
March | 21.16 | 8.33 |
April | 21.28 | 10.85 |
May | 21.38 | 12.97 |
June | 21.77 | 15.59 |
July | 21.74 | 17.66 |
August | 21.86 | 18.80 |
September | 21.63 | 15.09 |
October | 21.13 | 11.43 |
November | 20.83 | 8.07 |
December | 20.70 | 5.42 |
Annual Sum or Average | 21.25 | 11.24 |
Minimum of Months | 20.62 | 4.50 |
Maximum of Months | 21.86 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 4.50 |
February | 19.41 | 5.82 |
March | 19.49 | 8.33 |
April | 19.42 | 10.85 |
May | 19.43 | 12.97 |
June | 19.47 | 15.59 |
July | 19.38 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.39 | 11.43 |
November | 19.40 | 8.07 |
December | 19.39 | 5.42 |
Annual Sum or Average | 19.42 | 11.24 |
Minimum of Months | 19.38 | 4.50 |
Maximum of Months | 19.49 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.41 | 5.82 |
March | 19.49 | 8.33 |
April | 19.42 | 10.85 |
May | 19.43 | 12.97 |
June | 19.48 | 15.59 |
July | 19.38 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.39 | 11.43 |
November | 19.39 | 8.07 |
December | 19.38 | 5.42 |
Annual Sum or Average | 19.42 | 11.24 |
Minimum of Months | 19.38 | 4.50 |
Maximum of Months | 19.49 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.41 | 5.82 |
March | 19.48 | 8.33 |
April | 19.41 | 10.85 |
May | 19.43 | 12.97 |
June | 19.47 | 15.59 |
July | 19.38 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.39 | 11.43 |
November | 19.39 | 8.07 |
December | 19.38 | 5.42 |
Annual Sum or Average | 19.42 | 11.24 |
Minimum of Months | 19.38 | 4.50 |
Maximum of Months | 19.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 4.50 |
February | 19.53 | 5.82 |
March | 19.67 | 8.33 |
April | 19.62 | 10.85 |
May | 19.65 | 12.97 |
June | 19.74 | 15.59 |
July | 19.77 | 17.66 |
August | 19.89 | 18.80 |
September | 19.75 | 15.09 |
October | 19.55 | 11.43 |
November | 19.46 | 8.07 |
December | 19.45 | 5.42 |
Annual Sum or Average | 19.63 | 11.24 |
Minimum of Months | 19.45 | 4.50 |
Maximum of Months | 19.89 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 4.50 |
February | 20.98 | 5.82 |
March | 21.24 | 8.33 |
April | 21.28 | 10.85 |
May | 21.35 | 12.97 |
June | 21.68 | 15.59 |
July | 21.67 | 17.66 |
August | 21.80 | 18.80 |
September | 21.62 | 15.09 |
October | 21.23 | 11.43 |
November | 20.98 | 8.07 |
December | 20.87 | 5.42 |
Annual Sum or Average | 21.29 | 11.24 |
Minimum of Months | 20.78 | 4.50 |
Maximum of Months | 21.80 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 4.50 |
February | 21.45 | 5.82 |
March | 21.60 | 8.33 |
April | 21.55 | 10.85 |
May | 21.55 | 12.97 |
June | 21.85 | 15.59 |
July | 21.83 | 17.66 |
August | 21.93 | 18.80 |
September | 21.85 | 15.09 |
October | 21.56 | 11.43 |
November | 21.48 | 8.07 |
December | 21.44 | 5.42 |
Annual Sum or Average | 21.62 | 11.24 |
Minimum of Months | 21.36 | 4.50 |
Maximum of Months | 21.93 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 4.50 |
February | 19.54 | 5.82 |
March | 19.75 | 8.33 |
April | 20.03 | 10.85 |
May | 20.49 | 12.97 |
June | 21.13 | 15.59 |
July | 21.34 | 17.66 |
August | 21.36 | 18.80 |
September | 20.69 | 15.09 |
October | 19.83 | 11.43 |
November | 19.60 | 8.07 |
December | 19.45 | 5.42 |
Annual Sum or Average | 20.23 | 11.24 |
Minimum of Months | 19.45 | 4.50 |
Maximum of Months | 21.36 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.86 | 4.50 |
February | 20.06 | 5.82 |
March | 20.47 | 8.33 |
April | 20.78 | 10.85 |
May | 20.97 | 12.97 |
June | 21.47 | 15.59 |
July | 21.47 | 17.66 |
August | 21.60 | 18.80 |
September | 21.18 | 15.09 |
October | 20.49 | 11.43 |
November | 20.08 | 8.07 |
December | 19.92 | 5.42 |
Annual Sum or Average | 20.70 | 11.24 |
Minimum of Months | 19.86 | 4.50 |
Maximum of Months | 21.60 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 4.50 |
February | 19.73 | 5.82 |
March | 20.01 | 8.33 |
April | 20.28 | 10.85 |
May | 20.66 | 12.97 |
June | 21.33 | 15.59 |
July | 21.44 | 17.66 |
August | 21.53 | 18.80 |
September | 20.95 | 15.09 |
October | 20.11 | 11.43 |
November | 19.83 | 8.07 |
December | 19.65 | 5.42 |
Annual Sum or Average | 20.43 | 11.24 |
Minimum of Months | 19.63 | 4.50 |
Maximum of Months | 21.53 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | 4.50 |
February | 20.90 | 5.82 |
March | 21.20 | 8.33 |
April | 21.32 | 10.85 |
May | 21.43 | 12.97 |
June | 21.82 | 15.59 |
July | 21.80 | 17.66 |
August | 21.91 | 18.80 |
September | 21.69 | 15.09 |
October | 21.20 | 11.43 |
November | 20.93 | 8.07 |
December | 20.80 | 5.42 |
Annual Sum or Average | 21.31 | 11.24 |
Minimum of Months | 20.72 | 4.50 |
Maximum of Months | 21.91 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.87 | 4.50 |
February | 20.03 | 5.82 |
March | 20.36 | 8.33 |
April | 20.69 | 10.85 |
May | 20.94 | 12.97 |
June | 21.50 | 15.59 |
July | 21.55 | 17.66 |
August | 21.65 | 18.80 |
September | 21.21 | 15.09 |
October | 20.45 | 11.43 |
November | 20.10 | 8.07 |
December | 19.94 | 5.42 |
Annual Sum or Average | 20.69 | 11.24 |
Minimum of Months | 19.87 | 4.50 |
Maximum of Months | 21.65 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.69 | 4.50 |
February | 15.20 | 5.82 |
March | 15.77 | 8.33 |
April | 17.17 | 10.85 |
May | 18.00 | 12.97 |
June | 19.08 | 15.59 |
July | 20.32 | 17.66 |
August | 20.82 | 18.80 |
September | 19.09 | 15.09 |
October | 17.19 | 11.43 |
November | 15.50 | 8.07 |
December | 15.00 | 5.42 |
Annual Sum or Average | 17.33 | 11.24 |
Minimum of Months | 14.69 | 4.50 |
Maximum of Months | 20.82 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.23 | 4.50 |
February | 20.45 | 5.82 |
March | 20.81 | 8.33 |
April | 20.85 | 10.85 |
May | 20.98 | 12.97 |
June | 21.13 | 15.59 |
July | 21.00 | 17.66 |
August | 21.16 | 18.80 |
September | 20.98 | 15.09 |
October | 20.73 | 11.43 |
November | 20.43 | 8.07 |
December | 20.25 | 5.42 |
Annual Sum or Average | 20.75 | 11.24 |
Minimum of Months | 20.23 | 4.50 |
Maximum of Months | 21.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 4.50 |
February | 19.54 | 5.82 |
March | 19.67 | 8.33 |
April | 19.59 | 10.85 |
May | 19.57 | 12.97 |
June | 19.54 | 15.59 |
July | 19.40 | 17.66 |
August | 19.51 | 18.80 |
September | 19.48 | 15.09 |
October | 19.53 | 11.43 |
November | 19.50 | 8.07 |
December | 19.50 | 5.42 |
Annual Sum or Average | 19.53 | 11.24 |
Minimum of Months | 19.40 | 4.50 |
Maximum of Months | 19.67 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.38 | 4.50 |
February | 21.53 | 5.82 |
March | 21.74 | 8.33 |
April | 21.68 | 10.85 |
May | 21.67 | 12.97 |
June | 21.74 | 15.59 |
July | 21.60 | 17.66 |
August | 21.72 | 18.80 |
September | 21.66 | 15.09 |
October | 21.59 | 11.43 |
November | 21.52 | 8.07 |
December | 21.46 | 5.42 |
Annual Sum or Average | 21.61 | 11.24 |
Minimum of Months | 21.38 | 4.50 |
Maximum of Months | 21.74 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.57 | 4.50 |
February | 19.72 | 5.82 |
March | 20.03 | 8.33 |
April | 20.12 | 10.85 |
May | 20.26 | 12.97 |
June | 20.27 | 15.59 |
July | 20.30 | 17.66 |
August | 20.37 | 18.80 |
September | 20.22 | 15.09 |
October | 19.92 | 11.43 |
November | 19.65 | 8.07 |
December | 19.58 | 5.42 |
Annual Sum or Average | 20.00 | 11.24 |
Minimum of Months | 19.57 | 4.50 |
Maximum of Months | 20.37 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 4.50 |
February | 19.79 | 5.82 |
March | 19.98 | 8.33 |
April | 19.85 | 10.85 |
May | 19.84 | 12.97 |
June | 19.81 | 15.59 |
July | 19.65 | 17.66 |
August | 19.76 | 18.80 |
September | 19.77 | 15.09 |
October | 19.80 | 11.43 |
November | 19.72 | 8.07 |
December | 19.70 | 5.42 |
Annual Sum or Average | 19.78 | 11.24 |
Minimum of Months | 19.65 | 4.50 |
Maximum of Months | 19.98 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.67 | 4.50 |
February | 19.76 | 5.82 |
March | 19.93 | 8.33 |
April | 19.80 | 10.85 |
May | 19.77 | 12.97 |
June | 19.74 | 15.59 |
July | 19.57 | 17.66 |
August | 19.69 | 18.80 |
September | 19.70 | 15.09 |
October | 19.75 | 11.43 |
November | 19.69 | 8.07 |
December | 19.68 | 5.42 |
Annual Sum or Average | 19.73 | 11.24 |
Minimum of Months | 19.57 | 4.50 |
Maximum of Months | 19.93 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.67 | 4.50 |
February | 19.86 | 5.82 |
March | 20.11 | 8.33 |
April | 20.07 | 10.85 |
May | 20.02 | 12.97 |
June | 20.00 | 15.59 |
July | 19.89 | 17.66 |
August | 20.08 | 18.80 |
September | 20.07 | 15.09 |
October | 19.99 | 11.43 |
November | 19.75 | 8.07 |
December | 19.70 | 5.42 |
Annual Sum or Average | 19.93 | 11.24 |
Minimum of Months | 19.67 | 4.50 |
Maximum of Months | 20.11 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | 4.50 |
February | 19.74 | 5.82 |
March | 20.05 | 8.33 |
April | 20.19 | 10.85 |
May | 20.27 | 12.97 |
June | 20.41 | 15.59 |
July | 20.20 | 17.66 |
August | 20.28 | 18.80 |
September | 20.09 | 15.09 |
October | 19.90 | 11.43 |
November | 19.72 | 8.07 |
December | 19.64 | 5.42 |
Annual Sum or Average | 20.01 | 11.24 |
Minimum of Months | 19.64 | 4.50 |
Maximum of Months | 20.41 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | 4.50 |
February | 19.66 | 5.82 |
March | 19.85 | 8.33 |
April | 19.81 | 10.85 |
May | 19.88 | 12.97 |
June | 19.93 | 15.59 |
July | 19.76 | 17.66 |
August | 19.85 | 18.80 |
September | 19.76 | 15.09 |
October | 19.72 | 11.43 |
November | 19.66 | 8.07 |
December | 19.60 | 5.42 |
Annual Sum or Average | 19.76 | 11.24 |
Minimum of Months | 19.60 | 4.50 |
Maximum of Months | 19.93 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | 4.50 |
February | 19.72 | 5.82 |
March | 19.86 | 8.33 |
April | 19.77 | 10.85 |
May | 19.78 | 12.97 |
June | 19.76 | 15.59 |
July | 19.58 | 17.66 |
August | 19.67 | 18.80 |
September | 19.66 | 15.09 |
October | 19.71 | 11.43 |
November | 19.70 | 8.07 |
December | 19.68 | 5.42 |
Annual Sum or Average | 19.71 | 11.24 |
Minimum of Months | 19.58 | 4.50 |
Maximum of Months | 19.86 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 4.50 |
February | 19.75 | 5.82 |
March | 19.96 | 8.33 |
April | 19.92 | 10.85 |
May | 19.98 | 12.97 |
June | 20.00 | 15.59 |
July | 19.82 | 17.66 |
August | 19.90 | 18.80 |
September | 19.83 | 15.09 |
October | 19.81 | 11.43 |
November | 19.75 | 8.07 |
December | 19.69 | 5.42 |
Annual Sum or Average | 19.84 | 11.24 |
Minimum of Months | 19.69 | 4.50 |
Maximum of Months | 20.00 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.77 | 4.50 |
February | 19.82 | 5.82 |
March | 20.00 | 8.33 |
April | 19.91 | 10.85 |
May | 19.92 | 12.97 |
June | 19.91 | 15.59 |
July | 19.72 | 17.66 |
August | 19.82 | 18.80 |
September | 19.80 | 15.09 |
October | 19.83 | 11.43 |
November | 19.81 | 8.07 |
December | 19.77 | 5.42 |
Annual Sum or Average | 19.84 | 11.24 |
Minimum of Months | 19.72 | 4.50 |
Maximum of Months | 20.00 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | 4.50 |
February | 20.81 | 5.82 |
March | 21.19 | 8.33 |
April | 21.26 | 10.85 |
May | 21.37 | 12.97 |
June | 21.46 | 15.59 |
July | 21.43 | 17.66 |
August | 21.54 | 18.80 |
September | 21.39 | 15.09 |
October | 21.12 | 11.43 |
November | 20.78 | 8.07 |
December | 20.62 | 5.42 |
Annual Sum or Average | 21.13 | 11.24 |
Minimum of Months | 20.53 | 4.50 |
Maximum of Months | 21.54 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 4.50 |
February | 21.03 | 5.82 |
March | 21.35 | 8.33 |
April | 21.33 | 10.85 |
May | 21.35 | 12.97 |
June | 21.45 | 15.59 |
July | 21.33 | 17.66 |
August | 21.48 | 18.80 |
September | 21.38 | 15.09 |
October | 21.24 | 11.43 |
November | 21.01 | 8.07 |
December | 20.89 | 5.42 |
Annual Sum or Average | 21.22 | 11.24 |
Minimum of Months | 20.80 | 4.50 |
Maximum of Months | 21.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.78 | 4.50 |
February | 21.02 | 5.82 |
March | 21.31 | 8.33 |
April | 21.28 | 10.85 |
May | 21.27 | 12.97 |
June | 21.37 | 15.59 |
July | 21.24 | 17.66 |
August | 21.41 | 18.80 |
September | 21.31 | 15.09 |
October | 21.19 | 11.43 |
November | 20.98 | 8.07 |
December | 20.87 | 5.42 |
Annual Sum or Average | 21.17 | 11.24 |
Minimum of Months | 20.78 | 4.50 |
Maximum of Months | 21.41 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | 4.50 |
February | 21.13 | 5.82 |
March | 21.43 | 8.33 |
April | 21.44 | 10.85 |
May | 21.51 | 12.97 |
June | 21.64 | 15.59 |
July | 21.50 | 17.66 |
August | 21.59 | 18.80 |
September | 21.45 | 15.09 |
October | 21.30 | 11.43 |
November | 21.19 | 8.07 |
December | 21.06 | 5.42 |
Annual Sum or Average | 21.35 | 11.24 |
Minimum of Months | 20.96 | 4.50 |
Maximum of Months | 21.64 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | 4.50 |
February | 21.25 | 5.82 |
March | 21.56 | 8.33 |
April | 21.58 | 10.85 |
May | 21.64 | 12.97 |
June | 21.78 | 15.59 |
July | 21.66 | 17.66 |
August | 21.74 | 18.80 |
September | 21.60 | 15.09 |
October | 21.44 | 11.43 |
November | 21.31 | 8.07 |
December | 21.18 | 5.42 |
Annual Sum or Average | 21.48 | 11.24 |
Minimum of Months | 21.06 | 4.50 |
Maximum of Months | 21.78 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.96 | 4.50 |
February | 21.15 | 5.82 |
March | 21.49 | 8.33 |
April | 21.52 | 10.85 |
May | 21.59 | 12.97 |
June | 21.72 | 15.59 |
July | 21.60 | 17.66 |
August | 21.68 | 18.80 |
September | 21.54 | 15.09 |
October | 21.36 | 11.43 |
November | 21.23 | 8.07 |
December | 21.08 | 5.42 |
Annual Sum or Average | 21.41 | 11.24 |
Minimum of Months | 20.96 | 4.50 |
Maximum of Months | 21.72 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.39 | 4.50 |
February | 20.60 | 5.82 |
March | 21.02 | 8.33 |
April | 21.15 | 10.85 |
May | 21.35 | 12.97 |
June | 21.55 | 15.59 |
July | 21.55 | 17.66 |
August | 21.65 | 18.80 |
September | 21.40 | 15.09 |
October | 21.00 | 11.43 |
November | 20.72 | 8.07 |
December | 20.48 | 5.42 |
Annual Sum or Average | 21.07 | 11.24 |
Minimum of Months | 20.39 | 4.50 |
Maximum of Months | 21.65 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 4.50 |
February | 21.73 | 5.82 |
March | 21.90 | 8.33 |
April | 21.87 | 10.85 |
May | 21.86 | 12.97 |
June | 21.92 | 15.59 |
July | 21.81 | 17.66 |
August | 21.89 | 18.80 |
September | 21.84 | 15.09 |
October | 21.78 | 11.43 |
November | 21.73 | 8.07 |
December | 21.67 | 5.42 |
Annual Sum or Average | 21.80 | 11.24 |
Minimum of Months | 21.60 | 4.50 |
Maximum of Months | 21.92 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.45 | 4.50 |
February | 21.59 | 5.82 |
March | 21.80 | 8.33 |
April | 21.78 | 10.85 |
May | 21.78 | 12.97 |
June | 21.86 | 15.59 |
July | 21.73 | 17.66 |
August | 21.81 | 18.80 |
September | 21.74 | 15.09 |
October | 21.67 | 11.43 |
November | 21.61 | 8.07 |
December | 21.54 | 5.42 |
Annual Sum or Average | 21.70 | 11.24 |
Minimum of Months | 21.45 | 4.50 |
Maximum of Months | 21.86 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 4.50 |
February | 21.63 | 5.82 |
March | 21.86 | 8.33 |
April | 21.83 | 10.85 |
May | 21.84 | 12.97 |
June | 21.91 | 15.59 |
July | 21.79 | 17.66 |
August | 21.86 | 18.80 |
September | 21.79 | 15.09 |
October | 21.72 | 11.43 |
November | 21.66 | 8.07 |
December | 21.59 | 5.42 |
Annual Sum or Average | 21.75 | 11.24 |
Minimum of Months | 21.49 | 4.50 |
Maximum of Months | 21.91 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.22 | 4.50 |
February | 20.56 | 5.82 |
March | 21.12 | 8.33 |
April | 21.38 | 10.85 |
May | 21.56 | 12.97 |
June | 21.82 | 15.59 |
July | 21.73 | 17.66 |
August | 21.81 | 18.80 |
September | 21.52 | 15.09 |
October | 21.08 | 11.43 |
November | 20.61 | 8.07 |
December | 20.31 | 5.42 |
Annual Sum or Average | 21.15 | 11.24 |
Minimum of Months | 20.22 | 4.50 |
Maximum of Months | 21.82 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.89 | 4.50 |
February | 21.14 | 5.82 |
March | 21.53 | 8.33 |
April | 21.63 | 10.85 |
May | 21.72 | 12.97 |
June | 21.89 | 15.59 |
July | 21.79 | 17.66 |
August | 21.88 | 18.80 |
September | 21.69 | 15.09 |
October | 21.42 | 11.43 |
November | 21.17 | 8.07 |
December | 21.01 | 5.42 |
Annual Sum or Average | 21.48 | 11.24 |
Minimum of Months | 20.89 | 4.50 |
Maximum of Months | 21.89 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.56 | 4.50 |
February | 20.78 | 5.82 |
March | 21.17 | 8.33 |
April | 21.26 | 10.85 |
May | 21.41 | 12.97 |
June | 21.52 | 15.59 |
July | 21.47 | 17.66 |
August | 21.54 | 18.80 |
September | 21.38 | 15.09 |
October | 21.12 | 11.43 |
November | 20.82 | 8.07 |
December | 20.63 | 5.42 |
Annual Sum or Average | 21.14 | 11.24 |
Minimum of Months | 20.56 | 4.50 |
Maximum of Months | 21.54 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.40 | 4.50 |
February | 21.57 | 5.82 |
March | 21.80 | 8.33 |
April | 21.78 | 10.85 |
May | 21.79 | 12.97 |
June | 21.87 | 15.59 |
July | 21.78 | 17.66 |
August | 21.87 | 18.80 |
September | 21.79 | 15.09 |
October | 21.68 | 11.43 |
November | 21.57 | 8.07 |
December | 21.49 | 5.42 |
Annual Sum or Average | 21.70 | 11.24 |
Minimum of Months | 21.40 | 4.50 |
Maximum of Months | 21.87 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.17 | 4.50 |
February | 18.27 | 5.82 |
March | 18.45 | 8.33 |
April | 18.33 | 10.85 |
May | 18.20 | 12.97 |
June | 18.02 | 15.59 |
July | 17.77 | 17.66 |
August | 17.75 | 18.80 |
September | 18.01 | 15.09 |
October | 18.25 | 11.43 |
November | 18.23 | 8.07 |
December | 18.24 | 5.42 |
Annual Sum or Average | 18.14 | 11.24 |
Minimum of Months | 17.75 | 4.50 |
Maximum of Months | 18.45 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 4.50 |
February | 21.78 | 5.82 |
March | 21.96 | 8.33 |
April | 21.93 | 10.85 |
May | 21.93 | 12.97 |
June | 22.01 | 15.59 |
July | 21.92 | 17.66 |
August | 21.98 | 18.80 |
September | 21.93 | 15.09 |
October | 21.85 | 11.43 |
November | 21.80 | 8.07 |
December | 21.75 | 5.42 |
Annual Sum or Average | 21.87 | 11.24 |
Minimum of Months | 21.65 | 4.50 |
Maximum of Months | 22.01 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.55 | 4.50 |
February | 21.70 | 5.82 |
March | 21.91 | 8.33 |
April | 21.89 | 10.85 |
May | 21.90 | 12.97 |
June | 21.96 | 15.59 |
July | 21.88 | 17.66 |
August | 21.94 | 18.80 |
September | 21.88 | 15.09 |
October | 21.80 | 11.43 |
November | 21.71 | 8.07 |
December | 21.64 | 5.42 |
Annual Sum or Average | 21.81 | 11.24 |
Minimum of Months | 21.55 | 4.50 |
Maximum of Months | 21.96 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.41 | 4.50 |
February | 20.60 | 5.82 |
March | 20.83 | 8.33 |
April | 20.80 | 10.85 |
May | 20.76 | 12.97 |
June | 20.81 | 15.59 |
July | 20.69 | 17.66 |
August | 20.83 | 18.80 |
September | 20.79 | 15.09 |
October | 20.70 | 11.43 |
November | 20.55 | 8.07 |
December | 20.49 | 5.42 |
Annual Sum or Average | 20.69 | 11.24 |
Minimum of Months | 20.41 | 4.50 |
Maximum of Months | 20.83 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.55 | 4.50 |
February | 20.71 | 5.82 |
March | 20.99 | 8.33 |
April | 21.01 | 10.85 |
May | 21.05 | 12.97 |
June | 21.16 | 15.59 |
July | 21.01 | 17.66 |
August | 21.09 | 18.80 |
September | 20.98 | 15.09 |
October | 20.85 | 11.43 |
November | 20.75 | 8.07 |
December | 20.65 | 5.42 |
Annual Sum or Average | 20.90 | 11.24 |
Minimum of Months | 20.55 | 4.50 |
Maximum of Months | 21.16 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | 4.50 |
February | 20.84 | 5.82 |
March | 21.15 | 8.33 |
April | 21.17 | 10.85 |
May | 21.22 | 12.97 |
June | 21.34 | 15.59 |
July | 21.18 | 17.66 |
August | 21.25 | 18.80 |
September | 21.14 | 15.09 |
October | 21.00 | 11.43 |
November | 20.90 | 8.07 |
December | 20.78 | 5.42 |
Annual Sum or Average | 21.06 | 11.24 |
Minimum of Months | 20.67 | 4.50 |
Maximum of Months | 21.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.87 | 4.50 |
February | 20.10 | 5.82 |
March | 20.60 | 8.33 |
April | 20.99 | 10.85 |
May | 21.19 | 12.97 |
June | 21.53 | 15.59 |
July | 21.43 | 17.66 |
August | 21.51 | 18.80 |
September | 21.10 | 15.09 |
October | 20.58 | 11.43 |
November | 20.13 | 8.07 |
December | 19.93 | 5.42 |
Annual Sum or Average | 20.75 | 11.24 |
Minimum of Months | 19.87 | 4.50 |
Maximum of Months | 21.53 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | 4.50 |
February | 21.46 | 5.82 |
March | 21.78 | 8.33 |
April | 21.83 | 10.85 |
May | 21.89 | 12.97 |
June | 22.01 | 15.59 |
July | 21.95 | 17.66 |
August | 22.00 | 18.80 |
September | 21.89 | 15.09 |
October | 21.70 | 11.43 |
November | 21.54 | 8.07 |
December | 21.39 | 5.42 |
Annual Sum or Average | 21.73 | 11.24 |
Minimum of Months | 21.26 | 4.50 |
Maximum of Months | 22.01 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.47 | 4.50 |
February | 21.66 | 5.82 |
March | 21.90 | 8.33 |
April | 21.92 | 10.85 |
May | 21.94 | 12.97 |
June | 22.04 | 15.59 |
July | 21.98 | 17.66 |
August | 22.03 | 18.80 |
September | 21.94 | 15.09 |
October | 21.81 | 11.43 |
November | 21.69 | 8.07 |
December | 21.60 | 5.42 |
Annual Sum or Average | 21.83 | 11.24 |
Minimum of Months | 21.47 | 4.50 |
Maximum of Months | 22.04 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 4.50 |
February | 19.46 | 5.82 |
March | 19.58 | 8.33 |
April | 19.53 | 10.85 |
May | 19.55 | 12.97 |
June | 19.55 | 15.59 |
July | 19.44 | 17.66 |
August | 19.53 | 18.80 |
September | 19.48 | 15.09 |
October | 19.46 | 11.43 |
November | 19.43 | 8.07 |
December | 19.41 | 5.42 |
Annual Sum or Average | 19.49 | 11.24 |
Minimum of Months | 19.41 | 4.50 |
Maximum of Months | 19.58 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | 4.50 |
February | 22.36 | 5.82 |
March | 22.40 | 8.33 |
April | 22.32 | 10.85 |
May | 22.26 | 12.97 |
June | 22.21 | 15.59 |
July | 22.15 | 17.66 |
August | 22.16 | 18.80 |
September | 22.19 | 15.09 |
October | 22.28 | 11.43 |
November | 22.37 | 8.07 |
December | 22.37 | 5.42 |
Annual Sum or Average | 22.28 | 11.24 |
Minimum of Months | 22.15 | 4.50 |
Maximum of Months | 22.40 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 4.50 |
February | 21.05 | 5.82 |
March | 21.34 | 8.33 |
April | 21.34 | 10.85 |
May | 21.41 | 12.97 |
June | 21.50 | 15.59 |
July | 21.37 | 17.66 |
August | 21.47 | 18.80 |
September | 21.34 | 15.09 |
October | 21.22 | 11.43 |
November | 21.12 | 8.07 |
December | 20.98 | 5.42 |
Annual Sum or Average | 21.25 | 11.24 |
Minimum of Months | 20.91 | 4.50 |
Maximum of Months | 21.50 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | 4.50 |
February | 20.55 | 5.82 |
March | 21.06 | 8.33 |
April | 21.29 | 10.85 |
May | 21.53 | 12.97 |
June | 21.75 | 15.59 |
July | 21.73 | 17.66 |
August | 21.78 | 18.80 |
September | 21.48 | 15.09 |
October | 21.05 | 11.43 |
November | 20.66 | 8.07 |
December | 20.36 | 5.42 |
Annual Sum or Average | 21.13 | 11.24 |
Minimum of Months | 20.28 | 4.50 |
Maximum of Months | 21.78 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.02 | 4.50 |
February | 21.17 | 5.82 |
March | 21.47 | 8.33 |
April | 21.47 | 10.85 |
May | 21.54 | 12.97 |
June | 21.62 | 15.59 |
July | 21.51 | 17.66 |
August | 21.60 | 18.80 |
September | 21.48 | 15.09 |
October | 21.36 | 11.43 |
November | 21.24 | 8.07 |
December | 21.11 | 5.42 |
Annual Sum or Average | 21.38 | 11.24 |
Minimum of Months | 21.02 | 4.50 |
Maximum of Months | 21.62 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.52 | 4.50 |
February | 19.63 | 5.82 |
March | 19.92 | 8.33 |
April | 20.12 | 10.85 |
May | 20.40 | 12.97 |
June | 20.64 | 15.59 |
July | 20.77 | 17.66 |
August | 20.79 | 18.80 |
September | 20.39 | 15.09 |
October | 19.88 | 11.43 |
November | 19.65 | 8.07 |
December | 19.51 | 5.42 |
Annual Sum or Average | 20.10 | 11.24 |
Minimum of Months | 19.51 | 4.50 |
Maximum of Months | 20.79 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.12 | 4.50 |
February | 21.29 | 5.82 |
March | 21.61 | 8.33 |
April | 21.67 | 10.85 |
May | 21.77 | 12.97 |
June | 21.87 | 15.59 |
July | 21.79 | 17.66 |
August | 21.84 | 18.80 |
September | 21.70 | 15.09 |
October | 21.55 | 11.43 |
November | 21.39 | 8.07 |
December | 21.23 | 5.42 |
Annual Sum or Average | 21.57 | 11.24 |
Minimum of Months | 21.12 | 4.50 |
Maximum of Months | 21.87 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | 4.50 |
February | 21.36 | 5.82 |
March | 21.69 | 8.33 |
April | 21.79 | 10.85 |
May | 21.88 | 12.97 |
June | 21.98 | 15.59 |
July | 21.93 | 17.66 |
August | 21.96 | 18.80 |
September | 21.82 | 15.09 |
October | 21.65 | 11.43 |
November | 21.47 | 8.07 |
December | 21.28 | 5.42 |
Annual Sum or Average | 21.67 | 11.24 |
Minimum of Months | 21.17 | 4.50 |
Maximum of Months | 21.98 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.41 | 5.82 |
March | 19.49 | 8.33 |
April | 19.43 | 10.85 |
May | 19.45 | 12.97 |
June | 19.48 | 15.59 |
July | 19.38 | 17.66 |
August | 19.48 | 18.80 |
September | 19.41 | 15.09 |
October | 19.39 | 11.43 |
November | 19.39 | 8.07 |
December | 19.38 | 5.42 |
Annual Sum or Average | 19.42 | 11.24 |
Minimum of Months | 19.38 | 4.50 |
Maximum of Months | 19.49 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.11 | 4.50 |
February | 25.16 | 5.82 |
March | 25.11 | 8.33 |
April | 25.47 | 10.85 |
May | 25.41 | 12.97 |
June | 25.29 | 15.59 |
July | 25.48 | 17.66 |
August | 25.07 | 18.80 |
September | 25.38 | 15.09 |
October | 25.43 | 11.43 |
November | 25.23 | 8.07 |
December | 25.28 | 5.42 |
Annual Sum or Average | 25.28 | 11.24 |
Minimum of Months | 25.07 | 4.50 |
Maximum of Months | 25.48 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.90 | 4.50 |
February | 21.18 | 5.82 |
March | 21.61 | 8.33 |
April | 21.80 | 10.85 |
May | 21.93 | 12.97 |
June | 22.05 | 15.59 |
July | 22.03 | 17.66 |
August | 22.04 | 18.80 |
September | 21.90 | 15.09 |
October | 21.64 | 11.43 |
November | 21.31 | 8.07 |
December | 21.03 | 5.42 |
Annual Sum or Average | 21.62 | 11.24 |
Minimum of Months | 20.90 | 4.50 |
Maximum of Months | 22.05 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | 4.50 |
February | 20.90 | 5.82 |
March | 21.36 | 8.33 |
April | 21.52 | 10.85 |
May | 21.68 | 12.97 |
June | 21.85 | 15.59 |
July | 21.80 | 17.66 |
August | 21.84 | 18.80 |
September | 21.61 | 15.09 |
October | 21.32 | 11.43 |
November | 21.04 | 8.07 |
December | 20.75 | 5.42 |
Annual Sum or Average | 21.36 | 11.24 |
Minimum of Months | 20.66 | 4.50 |
Maximum of Months | 21.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | 4.50 |
February | 20.87 | 5.82 |
March | 21.34 | 8.33 |
April | 21.51 | 10.85 |
May | 21.68 | 12.97 |
June | 21.85 | 15.59 |
July | 21.81 | 17.66 |
August | 21.85 | 18.80 |
September | 21.62 | 15.09 |
October | 21.32 | 11.43 |
November | 20.98 | 8.07 |
December | 20.70 | 5.42 |
Annual Sum or Average | 21.34 | 11.24 |
Minimum of Months | 20.58 | 4.50 |
Maximum of Months | 21.85 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 4.50 |
February | 19.41 | 5.82 |
March | 19.51 | 8.33 |
April | 19.45 | 10.85 |
May | 19.48 | 12.97 |
June | 19.50 | 15.59 |
July | 19.41 | 17.66 |
August | 19.50 | 18.80 |
September | 19.44 | 15.09 |
October | 19.40 | 11.43 |
November | 19.39 | 8.07 |
December | 19.38 | 5.42 |
Annual Sum or Average | 19.44 | 11.24 |
Minimum of Months | 19.38 | 4.50 |
Maximum of Months | 19.51 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | 4.50 |
February | 19.63 | 5.82 |
March | 19.83 | 8.33 |
April | 19.82 | 10.85 |
May | 19.82 | 12.97 |
June | 19.80 | 15.59 |
July | 19.72 | 17.66 |
August | 19.83 | 18.80 |
September | 19.78 | 15.09 |
October | 19.70 | 11.43 |
November | 19.55 | 8.07 |
December | 19.52 | 5.42 |
Annual Sum or Average | 19.71 | 11.24 |
Minimum of Months | 19.50 | 4.50 |
Maximum of Months | 19.83 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | 4.50 |
February | 19.77 | 5.82 |
March | 20.00 | 8.33 |
April | 19.93 | 10.85 |
May | 19.92 | 12.97 |
June | 19.87 | 15.59 |
July | 19.68 | 17.66 |
August | 19.78 | 18.80 |
September | 19.76 | 15.09 |
October | 19.79 | 11.43 |
November | 19.73 | 8.07 |
December | 19.69 | 5.42 |
Annual Sum or Average | 19.80 | 11.24 |
Minimum of Months | 19.68 | 4.50 |
Maximum of Months | 20.00 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | 4.50 |
February | 19.49 | 5.82 |
March | 19.60 | 8.33 |
April | 19.52 | 10.85 |
May | 19.52 | 12.97 |
June | 19.51 | 15.59 |
July | 19.39 | 17.66 |
August | 19.49 | 18.80 |
September | 19.45 | 15.09 |
October | 19.47 | 11.43 |
November | 19.47 | 8.07 |
December | 19.46 | 5.42 |
Annual Sum or Average | 19.49 | 11.24 |
Minimum of Months | 19.39 | 4.50 |
Maximum of Months | 19.60 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 4.50 |
February | 19.88 | 5.82 |
March | 20.11 | 8.33 |
April | 20.11 | 10.85 |
May | 20.15 | 12.97 |
June | 20.19 | 15.59 |
July | 20.07 | 17.66 |
August | 20.14 | 18.80 |
September | 20.04 | 15.09 |
October | 19.98 | 11.43 |
November | 19.89 | 8.07 |
December | 19.82 | 5.42 |
Annual Sum or Average | 20.02 | 11.24 |
Minimum of Months | 19.80 | 4.50 |
Maximum of Months | 20.19 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.28 | 4.50 |
February | 20.50 | 5.82 |
March | 20.94 | 8.33 |
April | 21.09 | 10.85 |
May | 21.27 | 12.97 |
June | 21.43 | 15.59 |
July | 21.35 | 17.66 |
August | 21.40 | 18.80 |
September | 21.16 | 15.09 |
October | 20.86 | 11.43 |
November | 20.58 | 8.07 |
December | 20.37 | 5.42 |
Annual Sum or Average | 20.94 | 11.24 |
Minimum of Months | 20.28 | 4.50 |
Maximum of Months | 21.43 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.88 | 4.50 |
February | 19.98 | 5.82 |
March | 20.25 | 8.33 |
April | 20.17 | 10.85 |
May | 20.18 | 12.97 |
June | 20.14 | 15.59 |
July | 19.93 | 17.66 |
August | 20.03 | 18.80 |
September | 20.00 | 15.09 |
October | 20.03 | 11.43 |
November | 19.95 | 8.07 |
December | 19.89 | 5.42 |
Annual Sum or Average | 20.04 | 11.24 |
Minimum of Months | 19.88 | 4.50 |
Maximum of Months | 20.25 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.06 | 4.50 |
February | 20.39 | 5.82 |
March | 20.86 | 8.33 |
April | 21.09 | 10.85 |
May | 21.30 | 12.97 |
June | 21.46 | 15.59 |
July | 21.44 | 17.66 |
August | 21.49 | 18.80 |
September | 21.22 | 15.09 |
October | 20.88 | 11.43 |
November | 20.39 | 8.07 |
December | 20.13 | 5.42 |
Annual Sum or Average | 20.90 | 11.24 |
Minimum of Months | 20.06 | 4.50 |
Maximum of Months | 21.49 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.91 | 4.50 |
February | 20.25 | 5.82 |
March | 20.76 | 8.33 |
April | 21.05 | 10.85 |
May | 21.30 | 12.97 |
June | 21.50 | 15.59 |
July | 21.52 | 17.66 |
August | 21.55 | 18.80 |
September | 21.25 | 15.09 |
October | 20.81 | 11.43 |
November | 20.24 | 8.07 |
December | 19.98 | 5.42 |
Annual Sum or Average | 20.85 | 11.24 |
Minimum of Months | 19.91 | 4.50 |
Maximum of Months | 21.55 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.99 | 4.50 |
February | 20.13 | 5.82 |
March | 20.44 | 8.33 |
April | 20.55 | 10.85 |
May | 20.66 | 12.97 |
June | 20.77 | 15.59 |
July | 20.71 | 17.66 |
August | 20.74 | 18.80 |
September | 20.57 | 15.09 |
October | 20.36 | 11.43 |
November | 20.19 | 8.07 |
December | 20.06 | 5.42 |
Annual Sum or Average | 20.43 | 11.24 |
Minimum of Months | 19.99 | 4.50 |
Maximum of Months | 20.77 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.04 | 4.50 |
February | 20.37 | 5.82 |
March | 20.90 | 8.33 |
April | 21.22 | 10.85 |
May | 21.42 | 12.97 |
June | 21.65 | 15.59 |
July | 21.60 | 17.66 |
August | 21.64 | 18.80 |
September | 21.33 | 15.09 |
October | 20.92 | 11.43 |
November | 20.45 | 8.07 |
December | 20.09 | 5.42 |
Annual Sum or Average | 20.97 | 11.24 |
Minimum of Months | 20.04 | 4.50 |
Maximum of Months | 21.65 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.44 | 4.50 |
February | 19.56 | 5.82 |
March | 19.88 | 8.33 |
April | 20.35 | 10.85 |
May | 20.75 | 12.97 |
June | 21.19 | 15.59 |
July | 21.31 | 17.66 |
August | 21.34 | 18.80 |
September | 20.81 | 15.09 |
October | 20.00 | 11.43 |
November | 19.60 | 8.07 |
December | 19.44 | 5.42 |
Annual Sum or Average | 20.31 | 11.24 |
Minimum of Months | 19.44 | 4.50 |
Maximum of Months | 21.34 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.62 | 4.50 |
February | 19.81 | 5.82 |
March | 20.20 | 8.33 |
April | 20.49 | 10.85 |
May | 20.80 | 12.97 |
June | 21.10 | 15.59 |
July | 21.23 | 17.66 |
August | 21.27 | 18.80 |
September | 20.92 | 15.09 |
October | 20.26 | 11.43 |
November | 19.83 | 8.07 |
December | 19.63 | 5.42 |
Annual Sum or Average | 20.43 | 11.24 |
Minimum of Months | 19.62 | 4.50 |
Maximum of Months | 21.27 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 4.50 |
February | 19.59 | 5.82 |
March | 19.91 | 8.33 |
April | 20.36 | 10.85 |
May | 20.81 | 12.97 |
June | 21.22 | 15.59 |
July | 21.36 | 17.66 |
August | 21.40 | 18.80 |
September | 20.86 | 15.09 |
October | 20.00 | 11.43 |
November | 19.63 | 8.07 |
December | 19.45 | 5.42 |
Annual Sum or Average | 20.34 | 11.24 |
Minimum of Months | 19.45 | 4.50 |
Maximum of Months | 21.40 | 18.80 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2018-10-19 19:10:38
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.65 | 4.50 |
February | 19.93 | 5.82 |
March | 20.31 | 8.33 |
April | 20.60 | 10.85 |
May | 20.88 | 12.97 |
June | 21.16 | 15.59 |
July | 21.27 | 17.66 |
August | 21.32 | 18.80 |
September | 20.99 | 15.09 |
October | 20.41 | 11.43 |
November | 19.88 | 8.07 |
December | 19.70 | 5.42 |
Annual Sum or Average | 20.51 | 11.24 |
Minimum of Months | 19.65 | 4.50 |
Maximum of Months | 21.32 | 18.80 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2018-10-19 19:10:38
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.809941E+11 | 0.428913E+11 |
February | 0.722871E+11 | 0.507541E+11 |
March | 0.666127E+11 | 0.704333E+11 |
April | 0.546692E+11 | 0.864820E+11 |
May | 0.517513E+11 | 0.112820E+12 |
June | 0.465878E+11 | 0.136266E+12 |
July | 0.471766E+11 | 0.163534E+12 |
August | 0.468595E+11 | 0.184598E+12 |
September | 0.469336E+11 | 0.141543E+12 |
October | 0.535721E+11 | 0.973368E+11 |
November | 0.601296E+11 | 0.683997E+11 |
December | 0.737251E+11 | 0.461474E+11 |
Annual Sum or Average | 0.701299E+12 | 0.120120E+13 |
Minimum of Months | 0.465878E+11 | 0.428913E+11 |
Maximum of Months | 0.809941E+11 | 0.184598E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2018-10-19 19:10:38
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.426367E+11 | 0.891496E+08 |
February | 0.341670E+11 | 0.207850E+10 |
March | 0.312848E+11 | 0.426775E+10 |
April | 0.285906E+11 | 0.228536E+11 |
May | 0.292566E+11 | 0.475970E+11 |
June | 0.290774E+11 | 0.842356E+11 |
July | 0.315547E+11 | 0.133955E+12 |
August | 0.326672E+11 | 0.163768E+12 |
September | 0.296097E+11 | 0.775129E+11 |
October | 0.294004E+11 | 0.162095E+11 |
November | 0.316720E+11 | 0.366764E+10 |
December | 0.388308E+11 | 0.000 |
Annual Sum or Average | 0.388748E+12 | 0.556234E+12 |
Minimum of Months | 0.285906E+11 | 0.000 |
Maximum of Months | 0.426367E+11 | 0.163768E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2018-10-19 19:10:38
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.857724E+11 | 0.712517E+11 |
February | 0.811258E+11 | 0.572757E+11 |
March | 0.805000E+11 | 0.545356E+11 |
April | 0.763131E+11 | 0.520960E+11 |
May | 0.872988E+11 | 0.513432E+11 |
June | 0.101825E+12 | 0.446444E+11 |
July | 0.123865E+12 | 0.453710E+11 |
August | 0.139007E+12 | 0.439717E+11 |
September | 0.101402E+12 | 0.455562E+11 |
October | 0.756077E+11 | 0.539857E+11 |
November | 0.697708E+11 | 0.589952E+11 |
December | 0.781050E+11 | 0.671226E+11 |
Annual Sum or Average | 0.110059E+13 | 0.646149E+12 |
Minimum of Months | 0.697708E+11 | 0.439717E+11 |
Maximum of Months | 0.139007E+12 | 0.712517E+11 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:38
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.298088E+12 | 231043.907 | 17-JAN-07:10 | 35880.590 | 86960.562 | 15829.925 | 69064.204 | 5047.578 | 8471.500 | 208.141 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.272453E+12 | 226013.896 | 13-FEB-07:10 | 35880.590 | 86960.562 | 15761.334 | 57921.893 | 6197.712 | 8471.500 | 174.447 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.299450E+12 | 217827.126 | 24-MAR-14:39 | 35585.685 | 111201.830 | 28251.689 | 15340.169 | 13217.025 | 0.000 | 61.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.277506E+12 | 251412.055 | 27-APR-14:00 | 35585.685 | 111201.830 | 29300.791 | 3969.873 | 71300.984 | 0.000 | 52.892 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.298467E+12 | 239271.273 | 04-MAY-14:30 | 35585.685 | 111201.830 | 28327.965 | 4328.038 | 59773.824 | 0.000 | 53.932 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.309109E+12 | 247798.455 | 28-JUN-16:00 | 35585.685 | 111201.830 | 28847.958 | 4232.012 | 67876.872 | 0.000 | 54.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.326551E+12 | 259631.277 | 24-JUL-14:00 | 35585.685 | 111201.830 | 27360.221 | 5124.242 | 80307.731 | 0.000 | 51.568 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.355618E+12 | 270790.635 | 10-AUG-15:00 | 35585.685 | 111201.830 | 32833.772 | 3636.596 | 87484.391 | 0.000 | 48.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.303466E+12 | 248264.610 | 14-SEP-14:30 | 35585.685 | 111201.830 | 29667.596 | 4075.478 | 67684.162 | 0.000 | 49.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.285865E+12 | 224818.248 | 04-OCT-14:00 | 35585.685 | 111201.830 | 26659.377 | 4620.327 | 46696.788 | 0.000 | 54.241 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.276634E+12 | 216403.724 | 24-NOV-07:10 | 35880.590 | 86960.562 | 15799.717 | 59279.299 | 5220.476 | 8471.500 | 207.023 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.287532E+12 | 228327.094 | 26-DEC-07:10 | 35880.590 | 86960.562 | 15882.757 | 71560.292 | 2416.180 | 8471.500 | 260.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.359074E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.272453E+12 | 216403.724 | 35585.685 | 86960.562 | 15761.334 | 3636.596 | 2416.180 | 0.000 | 48.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.355618E+12 | 270790.635 | 35880.590 | 111201.830 | 32833.772 | 71560.292 | 87484.391 | 8471.500 | 260.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:38
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.199350E+12 | 147082.42 | 02-JAN-15:00 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.180784E+12 | 147082.42 | 01-FEB-17:10 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.208891E+12 | 147082.42 | 01-MAR-17:40 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.193037E+12 | 146934.97 | 03-APR-08:09 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.204029E+12 | 146934.97 | 04-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.201049E+12 | 146885.82 | 01-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.195985E+12 | 147033.27 | 12-JUL-08:09 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.208844E+12 | 146934.97 | 08-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.193056E+12 | 147082.42 | 25-SEP-16:49 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.199298E+12 | 147082.42 | 13-OCT-16:49 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.194805E+12 | 147082.42 | 01-NOV-16:19 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.196121E+12 | 147082.42 | 01-DEC-16:10 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.237525E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.180784E+12 | 146885.82 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.208891E+12 | 147082.42 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:38
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.451967E+11 | 0.00 | 0.126624E+11 | 0.154153E+12 | 0.00 | 0.318597E+11 | 0.302860E+09 | 0.333826E+11 | 0.115237E+11 | 0.00 | 0.900639E+10 | 0.00 | 0.00 | 0.00 |
February | 0.410580E+11 | 0.00 | 0.102986E+11 | 0.139726E+12 | 0.00 | 0.298151E+11 | 0.244310E+09 | 0.274087E+11 | 0.138370E+11 | 0.00 | 0.100649E+11 | 0.00 | 0.00 | 0.00 |
March | 0.485007E+11 | 0.00 | 0.984137E+10 | 0.160390E+12 | 0.00 | 0.353326E+11 | 0.218013E+09 | 0.186480E+11 | 0.194934E+11 | 0.00 | 0.702603E+10 | 0.00 | 0.00 | 0.00 |
April | 0.437246E+11 | 0.00 | 0.795723E+10 | 0.149313E+12 | 0.00 | 0.342509E+11 | 0.198030E+09 | 0.120386E+11 | 0.282566E+11 | 0.00 | 0.176697E+10 | 0.00 | 0.00 | 0.00 |
May | 0.467571E+11 | 0.00 | 0.694807E+10 | 0.157272E+12 | 0.00 | 0.360867E+11 | 0.190806E+09 | 0.103054E+11 | 0.407292E+11 | 0.00 | 0.177448E+09 | 0.00 | 0.00 | 0.00 |
June | 0.465073E+11 | 0.00 | 0.607124E+10 | 0.154542E+12 | 0.00 | 0.360713E+11 | 0.163929E+09 | 0.103505E+11 | 0.553938E+11 | 0.00 | 9435174.58 | 0.00 | 0.00 | 0.00 |
July | 0.439417E+11 | 0.00 | 0.653680E+10 | 0.152043E+12 | 0.00 | 0.363337E+11 | 0.164791E+09 | 0.127571E+11 | 0.747678E+11 | 0.00 | 6124495.41 | 0.00 | 0.00 | 0.00 |
August | 0.484535E+11 | 0.00 | 0.760592E+10 | 0.160390E+12 | 0.00 | 0.379462E+11 | 0.160599E+09 | 0.132009E+11 | 0.878603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437430E+11 | 0.00 | 0.884165E+10 | 0.149313E+12 | 0.00 | 0.346672E+11 | 0.167093E+09 | 0.118515E+11 | 0.548830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451450E+11 | 0.00 | 0.107563E+11 | 0.154153E+12 | 0.00 | 0.335768E+11 | 0.202391E+09 | 0.124708E+11 | 0.292906E+11 | 0.00 | 0.269497E+09 | 0.00 | 0.00 | 0.00 |
November | 0.443891E+11 | 0.00 | 0.118304E+11 | 0.150416E+12 | 0.00 | 0.312706E+11 | 0.227890E+09 | 0.177023E+11 | 0.187343E+11 | 0.00 | 0.206358E+10 | 0.00 | 0.00 | 0.00 |
December | 0.440785E+11 | 0.00 | 0.130334E+11 | 0.152043E+12 | 0.00 | 0.318577E+11 | 0.272453E+09 | 0.277108E+11 | 0.123330E+11 | 0.00 | 0.620351E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541495E+12 | 0.00 | 0.112383E+12 | 0.183375E+13 | 0.00 | 0.409069E+12 | 0.251316E+10 | 0.207827E+12 | 0.447103E+12 | 0.00 | 0.365939E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.410580E+11 | 0.00 | 0.607124E+10 | 0.139726E+12 | 0.00 | 0.298151E+11 | 0.160599E+09 | 0.103054E+11 | 0.115237E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485007E+11 | 0.00 | 0.130334E+11 | 0.160390E+12 | 0.00 | 0.379462E+11 | 0.302860E+09 | 0.333826E+11 | 0.878603E+11 | 0.00 | 0.100649E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:38
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.712517E+11 | 0.00 | 0.212967E+11 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.572757E+11 | 0.00 | 0.192403E+11 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.545356E+11 | 0.00 | 0.213777E+11 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.520960E+11 | 0.00 | 0.203512E+11 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.513432E+11 | 0.00 | 0.208097E+11 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.446444E+11 | 0.00 | 0.198200E+11 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.453710E+11 | 0.00 | 0.203041E+11 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.439717E+11 | 0.00 | 0.201886E+11 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.455562E+11 | 0.00 | 0.196559E+11 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.539857E+11 | 0.00 | 0.205421E+11 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.589952E+11 | 0.00 | 0.201625E+11 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.671226E+11 | 0.00 | 0.210655E+11 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.646149E+12 | 0.00 | 0.244814E+12 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.439717E+11 | 0.00 | 0.192403E+11 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.712517E+11 | 0.00 | 0.213777E+11 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:38
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35880.59 | 02-JAN-07:10 | 0.00 | 8471.50 | 01-JAN-06:10 | 111201.83 | 02-JAN-09:09 | 0.00 | 25226.49 | 20-JAN-13:39 | 309.36 | 15-JAN-08:09 | 69064.20 | 17-JAN-07:10 |
February | 35880.59 | 01-FEB-07:10 | 0.00 | 8471.50 | 01-FEB-06:10 | 111201.83 | 01-FEB-09:09 | 0.00 | 28459.83 | 08-FEB-14:50 | 296.39 | 19-FEB-07:10 | 69872.32 | 18-FEB-07:10 |
March | 35880.59 | 01-MAR-07:10 | 0.00 | 8471.50 | 01-MAR-06:10 | 111201.83 | 01-MAR-09:09 | 0.00 | 29988.78 | 01-MAR-15:30 | 235.08 | 18-MAR-05:10 | 60071.79 | 25-MAR-06:10 |
April | 35880.59 | 03-APR-06:10 | 0.00 | 8471.50 | 01-APR-05:10 | 111201.83 | 03-APR-08:09 | 0.00 | 29803.14 | 19-APR-13:30 | 201.45 | 01-APR-06:10 | 46060.30 | 01-APR-06:30 |
May | 35880.59 | 01-MAY-06:10 | 0.00 | 8471.50 | 01-MAY-19:19 | 111201.83 | 01-MAY-08:09 | 0.00 | 28905.88 | 25-MAY-15:39 | 195.80 | 27-MAY-06:10 | 35909.00 | 06-MAY-06:10 |
June | 35831.44 | 14-JUN-06:10 | 0.00 | 8471.50 | 01-JUN-19:00 | 111201.83 | 01-JUN-08:09 | 0.00 | 29180.15 | 28-JUN-15:39 | 171.83 | 24-JUN-06:10 | 31951.81 | 24-JUN-06:10 |
July | 35880.59 | 26-JUL-06:10 | 0.00 | 8471.50 | 01-JUL-20:10 | 111201.83 | 03-JUL-08:09 | 0.00 | 29753.51 | 20-JUL-16:40 | 166.06 | 29-JUL-06:10 | 32117.24 | 01-JUL-06:10 |
August | 35880.59 | 16-AUG-06:10 | 0.00 | 8471.50 | 01-AUG-19:40 | 111201.83 | 01-AUG-08:09 | 0.00 | 32938.55 | 10-AUG-15:30 | 167.89 | 19-AUG-06:10 | 32255.41 | 19-AUG-06:10 |
September | 35880.59 | 01-SEP-06:10 | 0.00 | 8471.50 | 01-SEP-05:10 | 111201.83 | 01-SEP-08:09 | 0.00 | 29729.14 | 14-SEP-14:50 | 182.38 | 30-SEP-06:10 | 35370.03 | 23-SEP-06:10 |
October | 35880.59 | 02-OCT-06:10 | 0.00 | 8471.50 | 01-OCT-05:10 | 111201.83 | 02-OCT-08:09 | 0.00 | 26766.09 | 04-OCT-14:30 | 201.88 | 28-OCT-06:10 | 42189.08 | 28-OCT-06:10 |
November | 35880.59 | 01-NOV-06:10 | 0.00 | 8471.50 | 01-NOV-05:10 | 111201.83 | 01-NOV-08:09 | 0.00 | 25635.67 | 15-NOV-14:20 | 230.18 | 13-NOV-07:30 | 59279.30 | 24-NOV-07:10 |
December | 35880.59 | 01-DEC-07:10 | 0.00 | 8471.50 | 01-DEC-06:10 | 111201.83 | 01-DEC-09:09 | 0.00 | 23464.19 | 05-DEC-15:09 | 265.40 | 26-DEC-06:00 | 71560.29 | 26-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 35831.44 | 0.00 | 8471.50 | 111201.83 | 0.00 | 23464.19 | 166.06 | 31951.81 | ||||||
Maximum of Months | 35880.59 | 0.00 | 8471.50 | 111201.83 | 0.00 | 32938.55 | 309.36 | 71560.29 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:38
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.298088E+12 | 231043.907 | 17-JAN-07:10 | 35880.590 | 86960.562 | 15829.925 | 69064.204 | 5047.578 | 8471.500 | 208.141 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.272453E+12 | 226013.896 | 13-FEB-07:10 | 35880.590 | 86960.562 | 15761.334 | 57921.893 | 6197.712 | 8471.500 | 174.447 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.299450E+12 | 217827.126 | 24-MAR-14:39 | 35585.685 | 111201.830 | 28251.689 | 15340.169 | 13217.025 | 0.000 | 61.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.277506E+12 | 251412.055 | 27-APR-14:00 | 35585.685 | 111201.830 | 29300.791 | 3969.873 | 71300.984 | 0.000 | 52.892 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.298467E+12 | 239271.273 | 04-MAY-14:30 | 35585.685 | 111201.830 | 28327.965 | 4328.038 | 59773.824 | 0.000 | 53.932 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.309109E+12 | 247798.455 | 28-JUN-16:00 | 35585.685 | 111201.830 | 28847.958 | 4232.012 | 67876.872 | 0.000 | 54.097 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.326551E+12 | 259631.277 | 24-JUL-14:00 | 35585.685 | 111201.830 | 27360.221 | 5124.242 | 80307.731 | 0.000 | 51.568 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.355618E+12 | 270790.635 | 10-AUG-15:00 | 35585.685 | 111201.830 | 32833.772 | 3636.596 | 87484.391 | 0.000 | 48.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.303466E+12 | 248264.610 | 14-SEP-14:30 | 35585.685 | 111201.830 | 29667.596 | 4075.478 | 67684.162 | 0.000 | 49.859 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.285865E+12 | 224818.248 | 04-OCT-14:00 | 35585.685 | 111201.830 | 26659.377 | 4620.327 | 46696.788 | 0.000 | 54.241 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.276634E+12 | 216403.724 | 24-NOV-07:10 | 35880.590 | 86960.562 | 15799.717 | 59279.299 | 5220.476 | 8471.500 | 207.023 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.287532E+12 | 228327.094 | 26-DEC-07:10 | 35880.590 | 86960.562 | 15882.757 | 71560.292 | 2416.180 | 8471.500 | 260.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.359074E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.272453E+12 | 216403.724 | 35585.685 | 86960.562 | 15761.334 | 3636.596 | 2416.180 | 0.000 | 48.361 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.355618E+12 | 270790.635 | 35880.590 | 111201.830 | 32833.772 | 71560.292 | 87484.391 | 8471.500 | 260.704 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:38
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.108410E+12 | 95732.247 | 07-JAN-07:00 | 0.000 | 4952.884 | 0.000 | 90779.363 | 7514.610 | 7514.610 | 83264.753 |
February | 0.908873E+11 | 84295.556 | 18-FEB-06:00 | 0.000 | 2971.730 | 0.000 | 81323.825 | 7514.610 | 7514.610 | 73809.215 |
March | 0.923030E+11 | 87055.815 | 18-MAR-05:10 | 0.000 | 2971.730 | 0.000 | 84084.084 | 7514.610 | 7514.610 | 76569.474 |
April | 0.878170E+11 | 71913.174 | 15-APR-06:10 | 0.000 | 4952.884 | 0.000 | 66960.290 | 7514.610 | 7514.610 | 59445.680 |
May | 0.882788E+11 | 71649.082 | 27-MAY-06:10 | 0.000 | 4952.884 | 0.000 | 66696.197 | 7514.610 | 7514.610 | 59181.587 |
June | 0.802693E+11 | 64412.484 | 24-JUN-06:10 | 0.000 | 4952.884 | 0.000 | 59459.600 | 7514.610 | 7514.610 | 51944.990 |
July | 0.813658E+11 | 62234.218 | 29-JUL-06:10 | 0.000 | 4952.884 | 0.000 | 57281.334 | 7514.610 | 7514.610 | 49766.724 |
August | 0.805500E+11 | 62845.305 | 19-AUG-06:10 | 0.000 | 4952.884 | 0.000 | 57892.421 | 7514.610 | 7514.610 | 50377.811 |
September | 0.805819E+11 | 68201.643 | 30-SEP-06:10 | 0.000 | 4952.884 | 0.000 | 63248.759 | 7514.610 | 7514.610 | 55734.149 |
October | 0.903897E+11 | 74188.512 | 21-OCT-06:10 | 0.000 | 4952.884 | 0.000 | 69235.628 | 7514.610 | 7514.610 | 61721.018 |
November | 0.946059E+11 | 81157.025 | 25-NOV-07:10 | 0.000 | 4952.884 | 0.000 | 76204.141 | 7514.610 | 7514.610 | 68689.531 |
December | 0.103879E+12 | 84578.306 | 23-DEC-07:10 | 0.000 | 4952.884 | 0.000 | 79625.422 | 7514.610 | 7514.610 | 72110.812 |
Annual Sum or Average | 0.107934E+13 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.802693E+11 | 62234.218 | 0.000 | 2971.730 | 0.000 | 57281.334 | 7514.610 | 7514.610 | 49766.724 | |
Maximum of Months | 0.108410E+12 | 95732.247 | 0.000 | 4952.884 | 0.000 | 90779.363 | 7514.610 | 7514.610 | 83264.753 |