Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09
Tabular Output Report in Format: HTML
Building: OutPatient HealthCare
Environment: Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2018-10-19 19:10:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 5240.75 | 1377.69 | 1377.69 |
Net Site Energy | 5240.75 | 1377.69 | 1377.69 |
Total Source Energy | 13846.86 | 3640.07 | 3640.07 |
Net Source Energy | 13846.86 | 3640.07 | 3640.07 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 351.71 | 882.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 520.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 112.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 404.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 3.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 153.07 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 249.51 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3920.26 | 1320.49 | 0.00 | 0.00 | 0.00 | 535.79 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 882.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 351.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 520.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 112.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 363.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 3.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 153.07 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 249.51 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 376.68 | 297.61 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1030.56 | 347.13 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 376.68 | 297.61 | 0.00 | 0.00 | 0.00 | 0.14 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1030.56 | 347.13 | 0.00 | 0.00 | 0.00 | 0.14 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3920.26 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3920.26 | 100.00 |
Total On-Site and Utility Electric Sources | 3920.26 | 100.00 |
Total Electricity End Uses | 3920.26 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 535.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 535.79 | 100.00 |
Total Water End Uses | 535.79 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 27.33 |
Time Setpoint Not Met During Occupied Cooling | 1679.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7830.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09 |
RunPeriod | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 6.9965 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 17.8681 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 17.8681 | 5734.7436 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 9.6875 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 24.3264 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 9.6875 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 8.5250 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 6.7813 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 13.2396 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 9.6875 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 11.9479 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 10.5486 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 6.7813 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 6.7813 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 11.9479 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 8.5250 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 8.5250 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 8.5250 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 8.5250 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_0.48_SHGC_0.40 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 2.653 | 0.426 | 0.308 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_0.48_SHGC_0.40 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 2.653 | 0.426 | 0.308 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_0.48_SHGC_0.40 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 2.653 | 0.426 | 0.308 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_0.48_SHGC_0.40 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 97.22 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 211.08 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BA05F7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E02487 |
F67E1F | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FE5A3C |
7EB6E7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E85BB5 |
D18914 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | C114C1 |
D4B39B | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E326E4 |
D2D3BC | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
C528DA | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
EFD3F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
62B5AF | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 997723 |
71E924 | SWINGING DOOR_CON | 2.839 | 2.839 | 2.97 | 8E5BB9 |
3C44F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
49526E | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
865AE8 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
5E66D1 | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 529072 |
E14DAE | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | D95F04 |
84A1D5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 3330D8 |
9CB8E5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
E4A528 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
24BAF7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FB3814 |
19E57D | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FCD12D |
EDE769 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 5507DC |
1C9872 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 2E2D0C |
F402E9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 270BCE |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 99275.60 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 176519.48 | 119341.86 | 57177.62 | 0.68 | 3.40 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 239606.20 | 167116.01 | 72490.19 | 0.70 | 3.30 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 171321.5 | 3.01 | 10.25 | N/A | 11.42 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 231899.6 | 2.89 | 9.87 | N/A | 11.01 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 1985.51 | 1966.92 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 139.14 | 137.83 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 4495.52 | 3062.92 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1212.67 | 1201.32 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1516.71 | 1502.51 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 367.93 | 250.68 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 417.13 | 413.23 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 651.79 | 444.08 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 4049.34 | 2758.92 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 180.62 | 123.06 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 259.83 | 177.03 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 297.71 | 202.84 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 3945.71 | 2789.80 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 559.03 | 380.88 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1240.94 | 1229.32 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3301.82 | 2249.62 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 814.37 | 554.85 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1662.29 | 1132.56 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 681.80 | 675.42 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 2316.43 | 1578.24 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 350.37 | 238.72 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 6066.83 | 4133.49 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1240.94 | 1229.32 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 817.07 | 556.69 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 986.67 | 672.25 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 123.02 | 83.82 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 1098.84 | 748.67 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1240.94 | 1229.32 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 1191.70 | 811.93 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13622.28 | 13494.73 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14119.07 | 13986.88 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 21877.37 | 21672.53 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1489.13 | 1475.19 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 975.89 | 664.90 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2605.98 | 2581.58 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4660.43 | 4616.80 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1240.94 | 1229.32 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9824.13 | 9732.15 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 2538.32 | 1729.42 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 252.84 | 172.27 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 7258.81 | 7190.84 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 420.21 | 308.17 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 175.40 | 158.10 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2895.53 | 2868.42 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1286.90 | 1274.85 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 4136.48 | 4097.75 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 3516.75 | 3483.83 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1060.97 | 784.83 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 579.44 | 394.79 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 4572.73 | 4529.92 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 898.61 | 890.19 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1396.45 | 1383.37 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 87.89 | 79.68 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 1441.37 | 1427.87 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 408.78 | 404.95 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2434.98 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1446.19 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 139.10 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3826.15 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7321.32 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9761.76 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1039.67 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4335.72 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2867.52 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10737.93 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3404.41 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5368.97 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 482.35 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 328.42 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 330.65 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 277.88 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 293.04 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 291.77 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 655.18 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 252.47 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 561.05 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 673.26 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2649.88 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 740.18 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 4830.68 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 865.39 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 2847.18 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 643.81 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 679.58 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 157.10 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 336.63 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 403.96 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 762.44 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 3358.11 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1191.42 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1220.22 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 6312.00 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 191.40 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1318.64 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 422.50 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 588.05 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 438.16 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2395.36 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 4338.56 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1928.72 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1604.38 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 8323.65 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 2969.76 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1220.22 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16076.46 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6661.86 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1898.12 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 713.28 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 463.58 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 5227.42 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7500.93 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4864.59 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 955.67 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 2852.59 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 4103.09 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2576.84 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 4202.59 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2005.97 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 57506.44 | 51642.46 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 57506.44 | 51642.46 | - |
AHU-2_HEATC | Coil:Heating:Water | 91533.81 | 81600.24 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 7.11 | 16233.74 | 2283.73 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.49 | 23830.36 | 2271.59 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.0021 | 543.94 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.00 | 0.00 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 171321.46 | 3.01 | 10.25 | 11.42 | 8.0144 | 3.27 | 11.14 | 6.3664 | 3.46 | 11.81 | 4.3138 | 3.59 | 12.25 | 1.8832 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 231899.60 | 2.89 | 9.87 | 11.01 | 11.8276 | 3.14 | 10.72 | 9.2480 | 3.35 | 11.42 | 6.1177 | 3.47 | 11.83 | 2.7063 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 733.27 | 733.27 | 0.055 | 0.068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22 | 0.01335 |
FLOOR 1 CAFE | 4087.08 | 4087.08 | 0.308 | 0.308 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22 | 0.01335 |
FLOOR 1 CLEAN | 551.85 | 551.85 | 0.042 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71 | 0.01335 |
FLOOR 1 CLEAN WORK | 688.52 | 688.52 | 0.052 | 0.052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50 | 0.01335 |
FLOOR 1 DICTATION | 347.02 | 347.02 | 0.025 | 0.025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 DRESSING ROOM | 197.90 | 197.90 | 0.015 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 1 HUMID | 169.86 | 169.86 | 0.012 | 0.012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 IT ROOM | 271.01 | 271.01 | 0.020 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 1 LOBBY | 3591.58 | 3591.58 | 0.270 | 0.270 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 28.53 | 0.01335 |
FLOOR 1 LOCKER ROOM | 3005.18 | 3005.18 | 0.226 | 0.226 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 1 LOUNGE | 1512.99 | 1512.99 | 0.114 | 0.114 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 28.16 | 0.01335 |
FLOOR 1 MRI CONTROL ROOM | 1836.62 | 1836.62 | 0.138 | 0.159 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 29.12 | 0.01335 |
FLOOR 1 MRI ROOM | 4521.97 | 4521.97 | 0.340 | 0.415 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
FLOOR 1 NOURISHMENT | 743.65 | 743.65 | 0.056 | 0.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.89 | 0.01335 |
FLOOR 1 NURSE STATION | 1000.10 | 1000.10 | 0.075 | 0.075 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.89 | 0.01335 |
FLOOR 1 OFFICE | 1084.82 | 1084.82 | 0.082 | 0.082 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18 | 0.01335 |
FLOOR 1 OPERATING ROOM 1 | 6702.00 | 6702.00 | 0.777 | 0.777 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 27.93 | 0.01335 |
FLOOR 1 OPERATING ROOM 2 | 6946.63 | 6946.63 | 0.805 | 0.805 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.98 | 0.01335 |
FLOOR 1 OPERATING ROOM 3 | 5806.03 | 5806.03 | 0.636 | 0.749 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:20:00 | 22.36 | 0.01335 |
FLOOR 1 PACU | 517.60 | 517.60 | 0.039 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 25.45 | 0.01335 |
FLOOR 1 PRE-OP ROOM 1 | 594.96 | 594.96 | 0.045 | 0.089 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 28.38 | 0.01335 |
FLOOR 1 PRE-OP ROOM 2 | 1060.33 | 1060.33 | 0.080 | 0.160 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.30 | 0.01335 |
FLOOR 1 PROCEDURE ROOM | 1723.44 | 1723.44 | 0.130 | 0.336 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.21 | 0.01335 |
FLOOR 1 RECEPTION | 2309.84 | 2309.84 | 0.174 | 0.174 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
FLOOR 1 RECOVERY ROOM | 3796.65 | 3796.65 | 0.286 | 0.286 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22 | 0.01335 |
FLOOR 1 SCHEDULING | 382.51 | 382.51 | 0.029 | 0.029 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 1 SOIL | 547.54 | 547.54 | 0.041 | 0.099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.98 | 0.01335 |
FLOOR 1 SOIL HOLD | 228.83 | 228.83 | 0.017 | 0.044 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:50:00 | 29.71 | 0.01335 |
FLOOR 1 SOIL WORK | 735.11 | 735.11 | 0.055 | 0.142 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 26.24 | 0.01335 |
FLOOR 1 STEP DOWN | 2319.22 | 2319.22 | 0.174 | 0.174 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.93 | 0.01335 |
FLOOR 2 CONFERENCE | 2941.72 | 2941.72 | 0.261 | 0.261 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14 | 0.01335 |
FLOOR 2 DICTATION | 253.62 | 253.62 | 0.022 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM 1 | 2940.04 | 2940.04 | 0.261 | 0.261 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84 | 0.01335 |
FLOOR 2 EXAM 2 | 2552.30 | 2552.30 | 0.227 | 0.255 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
FLOOR 2 EXAM 3 | 3508.95 | 3508.95 | 0.312 | 0.340 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30 | 0.01335 |
FLOOR 2 EXAM 4 | 636.65 | 636.65 | 0.057 | 0.057 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14 | 0.01335 |
FLOOR 2 EXAM 5 | 2462.54 | 2462.54 | 0.219 | 0.219 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50 | 0.01335 |
FLOOR 2 EXAM 6 | 1065.05 | 1065.05 | 0.095 | 0.106 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 2 EXAM 7 | 3198.33 | 3198.33 | 0.284 | 0.374 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30 | 0.01335 |
FLOOR 2 EXAM 8 | 1321.55 | 1321.55 | 0.117 | 0.127 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 2 EXAM 9 | 1716.59 | 1716.59 | 0.152 | 0.187 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30 | 0.01335 |
FLOOR 2 LOUNGE | 401.20 | 401.20 | 0.036 | 0.036 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.01 | 0.01335 |
FLOOR 2 NURSE STATION 1 | 644.82 | 644.82 | 0.057 | 0.057 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.01 | 0.01335 |
FLOOR 2 NURSE STATION 2 | 786.20 | 786.20 | 0.070 | 0.070 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.01 | 0.01335 |
FLOOR 2 OFFICE | 3141.65 | 3141.65 | 0.279 | 0.279 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50 | 0.01335 |
FLOOR 2 RECEPTION | 5703.98 | 5703.98 | 0.507 | 0.507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 29.62 | 0.01335 |
FLOOR 2 SCHEDULING 1 | 937.74 | 937.74 | 0.083 | 0.083 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.30 | 0.01335 |
FLOOR 2 SCHEDULING 2 | 1027.42 | 1027.42 | 0.091 | 0.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.01 | 0.01335 |
FLOOR 2 WORK | 4582.39 | 4582.39 | 0.407 | 0.407 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30 | 0.01335 |
FLOOR 2 X-RAY | 9421.32 | 9421.32 | 0.837 | 0.849 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
FLOOR 3 DRESSING ROOM | 189.22 | 189.22 | 0.017 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30 | 0.01335 |
FLOOR 3 HUMID | 475.36 | 475.36 | 0.042 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 LOCKER | 742.52 | 742.52 | 0.066 | 0.066 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 LOUNGE | 4373.95 | 4373.95 | 0.388 | 0.388 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 OFFICE | 10692.20 | 10692.20 | 0.949 | 0.949 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 PHYSICAL THERAPY 1 | 9131.31 | 9131.31 | 0.811 | 0.811 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14 | 0.01335 |
FLOOR 3 PHYSICAL THERAPY 2 | 2916.97 | 2916.97 | 0.259 | 0.279 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30 | 0.01335 |
FLOOR 3 TREATMENT | 2490.38 | 2490.38 | 0.221 | 0.225 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30 | 0.01335 |
FLOOR 3 WORK | 3621.50 | 3621.50 | 0.322 | 0.322 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.77 | 0.01335 |
FLOOR 1 BIO HAZ | 83.71 | 83.71 | 0.006 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 ELECTRICAL ROOM | 593.35 | 593.35 | 0.045 | 0.045 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:20:00 | 28.47 | 0.01335 |
FLOOR 1 ELEVATOR PUMP ROOM | 3686.08 | 3686.08 | 0.277 | 0.277 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 28.69 | 0.01335 |
FLOOR 1 IT HALL | 242.00 | 242.00 | 0.018 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 LOBBY HALL | 528.48 | 528.48 | 0.038 | 0.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 LOBBY TOILET | 440.65 | 440.65 | 0.032 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 LOCKER ROOM HALL | 763.76 | 763.76 | 0.056 | 0.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 MED GAS | 192.18 | 192.18 | 0.014 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99 | 0.01335 |
FLOOR 1 MRI HALL | 329.27 | 329.27 | 0.024 | 0.024 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 MRI TOILET | 138.88 | 138.88 | 0.010 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02 | 0.01335 |
FLOOR 1 NURSE HALL | 928.32 | 928.32 | 0.068 | 0.068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 NURSE JANITOR | 114.66 | 114.66 | 0.008 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 NURSE TOILET | 141.78 | 141.78 | 0.010 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 PRE-OP HALL | 917.56 | 917.56 | 0.067 | 0.067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 PRE-OP TOILET | 182.02 | 182.02 | 0.014 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.07 | 0.01335 |
FLOOR 1 RECEPTION HALL | 236.86 | 236.86 | 0.017 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 SCRUB | 159.68 | 159.68 | 0.012 | 0.012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.42 | 0.01335 |
FLOOR 1 STERILE HALL | 965.89 | 965.89 | 0.073 | 0.073 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 29.91 | 0.01335 |
FLOOR 1 STERILE STORAGE | 543.51 | 543.51 | 0.040 | 0.040 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 STORAGE | 1712.43 | 1712.43 | 0.129 | 0.129 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 29.74 | 0.01335 |
FLOOR 1 SUB-STERILE | 737.32 | 737.32 | 0.055 | 0.055 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50 | 0.01335 |
FLOOR 1 UTILITY HALL | 663.84 | 663.84 | 0.050 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71 | 0.01335 |
FLOOR 1 UTILITY JANITOR | 81.55 | 81.55 | 0.006 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 1 UTILITY ROOM | 843.85 | 843.85 | 0.063 | 0.063 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 27.00 | 0.01335 |
FLOOR 1 VESTIBULE | 260.73 | 260.73 | 0.020 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 28.53 | 0.01335 |
FLOOR 2 CONFERENCE TOILET | 202.65 | 202.65 | 0.017 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 1 | 583.85 | 583.85 | 0.050 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 2 | 573.20 | 573.20 | 0.049 | 0.049 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 3 | 552.61 | 552.61 | 0.047 | 0.047 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 4 | 564.58 | 564.58 | 0.048 | 0.048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 5 | 594.65 | 594.65 | 0.051 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 EXAM HALL 6 | 592.25 | 592.25 | 0.051 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 JANITOR | 385.18 | 385.18 | 0.033 | 0.033 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 OFFICE HALL | 1228.55 | 1228.55 | 0.105 | 0.105 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 RECEPTION HALL | 1759.49 | 1759.49 | 0.151 | 0.151 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 RECEPTION TOILET | 375.51 | 375.51 | 0.032 | 0.099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 STORAGE 1 | 171.84 | 171.84 | 0.015 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 STORAGE 2 | 300.88 | 300.88 | 0.026 | 0.026 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 STORAGE 3 | 390.26 | 390.26 | 0.033 | 0.033 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 UTILITY | 660.24 | 660.24 | 0.059 | 0.059 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 26.50 | 0.01335 |
FLOOR 2 WORK HALL | 2423.62 | 2423.62 | 0.207 | 0.207 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 2 WORK TOILET | 204.89 | 204.89 | 0.018 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 21.40 | 0.01335 |
FLOOR 3 ELEVATOR HALL | 889.28 | 889.28 | 0.079 | 0.079 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 JANITOR | 200.71 | 200.71 | 0.018 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 28.53 | 0.01335 |
FLOOR 3 LOUNGE TOILET | 734.53 | 734.53 | 0.065 | 0.151 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30 | 0.01335 |
FLOOR 3 MECHANICAL | 3780.50 | 3780.50 | 0.336 | 0.336 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 26.77 | 0.01335 |
FLOOR 3 MECHANICAL HALL | 1015.29 | 1015.29 | 0.090 | 0.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 | 29.59 | 0.01335 |
FLOOR 3 OFFICE HALL | 2355.00 | 2355.00 | 0.209 | 0.209 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30 | 0.01335 |
FLOOR 3 OFFICE TOILET | 174.59 | 174.59 | 0.016 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22 | 0.01335 |
FLOOR 3 PHYSICAL THERAPY TOILET | 267.53 | 267.53 | 0.024 | 0.066 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30 | 0.01335 |
FLOOR 3 STORAGE 1 | 279.59 | 279.59 | 0.025 | 0.025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30 | 0.01335 |
FLOOR 3 STORAGE 2 | 253.36 | 253.36 | 0.022 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30 | 0.01335 |
FLOOR 3 UNDEVELOPED 1 | 9142.02 | 9142.02 | 0.812 | 0.812 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.93 | 0.01335 |
FLOOR 3 UNDEVELOPED 2 | 4729.32 | 4729.32 | 0.420 | 0.420 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02 | 0.01335 |
FLOOR 3 UTILITY | 459.20 | 459.20 | 0.041 | 0.041 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30 | 0.01335 |
NE STAIR | 1495.93 | 1495.93 | 0.133 | 0.133 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30 | 0.01335 |
NW ELEVATOR | 1137.47 | 1137.47 | 0.101 | 0.101 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22 | 0.01335 |
NW STAIR | 1541.05 | 1541.05 | 0.137 | 0.137 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 29.37 | 0.01335 |
SW STAIR | 952.24 | 952.24 | 0.085 | 0.085 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 29.37 | 0.01335 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 326.34 | 326.34 | 0.014 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 CAFE | 616.63 | 616.63 | 0.026 | 0.184 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 DRESSING ROOM | 327.90 | 327.90 | 0.014 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 IT ROOM | 17.46 | 17.46 | 0.001 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -16.30 | 0.00092 |
FLOOR 1 LOBBY | 1348.50 | 1348.50 | 0.058 | 0.058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 LOCKER ROOM | 27.87 | 27.87 | 0.001 | 0.042 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | -16.30 | 0.00092 |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 OPERATING ROOM 1 | 9.14 | 9.14 | 0.000 | 0.239 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | -16.30 | 0.00092 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 PRE-OP ROOM 1 | 0.35 | 0.35 | 0.000 | 0.052 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | -16.30 | 0.00092 |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 PROCEDURE ROOM | 397.67 | 397.67 | 0.017 | 0.108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 RECEPTION | 164.27 | 164.27 | 0.007 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 RECOVERY ROOM | 1387.39 | 1387.39 | 0.060 | 0.161 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 SCHEDULING | 153.09 | 153.09 | 0.007 | 0.007 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 SOIL HOLD | 2.79 | 2.79 | 0.000 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | -16.30 | 0.00092 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 STEP DOWN | 1136.00 | 1136.00 | 0.049 | 0.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 CONFERENCE | 1713.68 | 1713.68 | 0.074 | 0.074 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 EXAM 1 | 1760.65 | 1760.65 | 0.076 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 2 | 793.74 | 793.74 | 0.034 | 0.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 3 | 1083.97 | 1083.97 | 0.046 | 0.102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 4 | 414.52 | 414.52 | 0.018 | 0.018 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 5 | 1246.01 | 1246.01 | 0.054 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 6 | 716.51 | 716.51 | 0.031 | 0.032 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 7 | 671.32 | 671.32 | 0.029 | 0.112 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 8 | 796.75 | 796.75 | 0.034 | 0.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM 9 | 454.97 | 454.97 | 0.020 | 0.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 OFFICE | 2128.15 | 2128.15 | 0.092 | 0.092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 RECEPTION | 2655.47 | 2655.47 | 0.115 | 0.115 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 WORK | 1291.10 | 1291.10 | 0.056 | 0.068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 3 DRESSING ROOM | 153.97 | 153.97 | 0.007 | 0.007 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 HUMID | 340.66 | 340.66 | 0.015 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 LOCKER | 353.03 | 353.03 | 0.015 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 LOUNGE | 1178.45 | 1178.45 | 0.050 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 OFFICE | 6744.58 | 6744.58 | 0.290 | 0.290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 PHYSICAL THERAPY 1 | 4759.64 | 4759.64 | 0.206 | 0.206 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 PHYSICAL THERAPY 2 | 1646.46 | 1646.46 | 0.071 | 0.084 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 TREATMENT | 1234.91 | 1234.91 | 0.053 | 0.067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 WORK | 2294.17 | 2294.17 | 0.099 | 0.099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 BIO HAZ | 109.37 | 109.37 | 0.005 | 0.005 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 ELECTRICAL ROOM | 59.25 | 59.25 | 0.003 | 0.003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 ELEVATOR PUMP ROOM | 469.13 | 469.13 | 0.020 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 IT HALL | 32.53 | 32.53 | 0.001 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 LOBBY HALL | 9.38 | 9.38 | 0.000 | 0.007 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:40:00 | -16.30 | 0.00092 |
FLOOR 1 LOBBY TOILET | 250.54 | 250.54 | 0.011 | 0.011 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 MED GAS | 536.24 | 536.24 | 0.023 | 0.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 MRI HALL | 35.38 | 35.38 | 0.002 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 MRI TOILET | 192.94 | 192.94 | 0.008 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 NURSE HALL | 159.15 | 159.15 | 0.007 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 PRE-OP HALL | 1.40 | 1.40 | 0.000 | 0.015 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:10:00 | -16.30 | 0.00092 |
FLOOR 1 PRE-OP TOILET | 233.69 | 233.69 | 0.010 | 0.010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 SCRUB | 102.90 | 102.90 | 0.004 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 STERILE HALL | 390.51 | 390.51 | 0.017 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 1 STORAGE | 3615.84 | 3615.84 | 0.157 | 0.157 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 SUB-STERILE | 709.70 | 709.70 | 0.031 | 0.031 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 UTILITY HALL | 1102.05 | 1102.05 | 0.048 | 0.048 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 UTILITY JANITOR | 52.31 | 52.31 | 0.002 | 0.002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 UTILITY ROOM | 1140.36 | 1140.36 | 0.049 | 0.049 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 1 VESTIBULE | 322.33 | 322.33 | 0.014 | 0.014 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 CONFERENCE TOILET | 87.84 | 87.84 | 0.004 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 1 | 386.75 | 386.75 | 0.017 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 2 | 262.31 | 262.31 | 0.011 | 0.011 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 3 | 264.13 | 264.13 | 0.012 | 0.012 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 4 | 173.27 | 173.27 | 0.008 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 5 | 183.32 | 183.32 | 0.008 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 EXAM HALL 6 | 225.67 | 225.67 | 0.010 | 0.010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 JANITOR | 523.83 | 523.83 | 0.023 | 0.023 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 OFFICE HALL | 591.53 | 591.53 | 0.026 | 0.026 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00092 | |
FLOOR 2 RECEPTION TOILET | 71.81 | 71.81 | 0.003 | 0.003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 STORAGE 1 | 81.73 | 81.73 | 0.004 | 0.004 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 STORAGE 2 | 95.92 | 95.92 | 0.004 | 0.007 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 STORAGE 3 | 112.14 | 112.14 | 0.005 | 0.008 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 UTILITY | 611.08 | 611.08 | 0.027 | 0.027 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 2 WORK HALL | 52.38 | 52.38 | 0.002 | 0.024 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:10:00 | -16.30 | 0.00092 |
FLOOR 2 WORK TOILET | 298.80 | 298.80 | 0.013 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 ELEVATOR HALL | 1063.93 | 1063.93 | 0.046 | 0.046 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 JANITOR | 470.73 | 470.73 | 0.020 | 0.020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 LOUNGE TOILET | 854.63 | 854.63 | 0.037 | 0.037 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 MECHANICAL | 405.97 | 405.97 | 0.017 | 0.017 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 MECHANICAL HALL | 1288.33 | 1288.33 | 0.056 | 0.056 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 OFFICE HALL | 2395.22 | 2395.22 | 0.103 | 0.103 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 OFFICE TOILET | 306.78 | 306.78 | 0.013 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 PHYSICAL THERAPY TOILET | 297.19 | 297.19 | 0.013 | 0.013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 STORAGE 1 | 435.18 | 435.18 | 0.019 | 0.019 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 STORAGE 2 | 372.03 | 372.03 | 0.016 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 UNDEVELOPED 1 | 6063.26 | 6063.26 | 0.261 | 0.261 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 UNDEVELOPED 2 | 3918.96 | 3918.96 | 0.169 | 0.169 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
FLOOR 3 UTILITY | 768.24 | 768.24 | 0.033 | 0.033 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
NE STAIR | 3287.85 | 3287.85 | 0.143 | 0.143 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
NW ELEVATOR | 2068.15 | 2068.15 | 0.090 | 0.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
NW STAIR | 3369.45 | 3369.45 | 0.146 | 0.146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
SW STAIR | 1608.68 | 1608.68 | 0.070 | 0.070 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -16.30 | 0.00092 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 7.11 | 7.11 | 2.40 | 2.40 |
AHU-2 | 10.49 | 10.49 | 3.41 | 3.41 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AHU-2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.49 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
FLOOR 2 CONFERENCE | AHU-2_DCV | 0.000000 | 0.001575 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 DICTATION | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 3 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 4 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 5 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 6 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 7 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 8 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 9 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 1 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 2 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION | AHU-2_DCV | 0.000000 | 0.001067 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 1 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 2 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 X-RAY | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 DRESSING ROOM | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 HUMID | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOCKER | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 TREATMENT | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 CONFERENCE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 1 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 2 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 3 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 4 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 5 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 6 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 3 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 ELEVATOR HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
NE STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW ELEVATOR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
SW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 4412.17 | 7830.00 | 4412.17 |
FLOOR 1 CAFE | 1083.00 | 7779.83 | 1083.00 |
FLOOR 1 CLEAN | 1886.33 | 7830.00 | 1886.33 |
FLOOR 1 CLEAN WORK | 3227.67 | 7830.00 | 3227.67 |
FLOOR 1 DICTATION | 301.83 | 7830.00 | 301.83 |
FLOOR 1 DRESSING ROOM | 3333.67 | 7830.00 | 3333.67 |
FLOOR 1 HUMID | 101.33 | 7830.00 | 101.33 |
FLOOR 1 IT ROOM | 938.00 | 7830.00 | 938.00 |
FLOOR 1 LOBBY | 1307.50 | 7830.00 | 1307.50 |
FLOOR 1 LOCKER ROOM | 233.00 | 7830.00 | 233.00 |
FLOOR 1 LOUNGE | 116.67 | 7830.00 | 116.67 |
FLOOR 1 MRI CONTROL ROOM | 280.00 | 7830.00 | 280.00 |
FLOOR 1 MRI ROOM | 55.33 | 7830.00 | 55.33 |
FLOOR 1 NOURISHMENT | 117.00 | 7830.00 | 117.00 |
FLOOR 1 NURSE STATION | 241.83 | 7830.00 | 241.83 |
FLOOR 1 OFFICE | 180.83 | 7830.00 | 180.83 |
FLOOR 1 OPERATING ROOM 1 | 4846.67 | 7830.00 | 4846.67 |
FLOOR 1 OPERATING ROOM 2 | 4873.83 | 7830.00 | 4873.83 |
FLOOR 1 OPERATING ROOM 3 | 7830.00 | 7830.00 | 7830.00 |
FLOOR 1 PACU | 3887.67 | 7830.00 | 3887.67 |
FLOOR 1 PRE-OP ROOM 1 | 4415.33 | 7830.00 | 4415.33 |
FLOOR 1 PRE-OP ROOM 2 | 4131.17 | 7830.00 | 4131.17 |
FLOOR 1 PROCEDURE ROOM | 4305.67 | 7830.00 | 4305.67 |
FLOOR 1 RECEPTION | 376.00 | 7830.00 | 376.00 |
FLOOR 1 RECOVERY ROOM | 4075.33 | 7830.00 | 4075.33 |
FLOOR 1 SCHEDULING | 1134.83 | 7830.00 | 1134.83 |
FLOOR 1 SOIL | 4484.50 | 7830.00 | 4484.50 |
FLOOR 1 SOIL HOLD | 4573.83 | 7830.00 | 4573.83 |
FLOOR 1 SOIL WORK | 4524.50 | 7830.00 | 4524.50 |
FLOOR 1 STEP DOWN | 3858.33 | 7830.00 | 3858.33 |
FLOOR 2 CONFERENCE | 2525.00 | 7794.67 | 2525.00 |
FLOOR 2 DICTATION | 964.67 | 7830.00 | 964.67 |
FLOOR 2 EXAM 1 | 3843.50 | 7810.33 | 3843.50 |
FLOOR 2 EXAM 2 | 3844.33 | 7830.00 | 3844.33 |
FLOOR 2 EXAM 3 | 4001.83 | 7830.00 | 4001.83 |
FLOOR 2 EXAM 4 | 3685.00 | 7827.83 | 3685.00 |
FLOOR 2 EXAM 5 | 3343.50 | 7830.00 | 3343.50 |
FLOOR 2 EXAM 6 | 4291.00 | 7830.00 | 4291.00 |
FLOOR 2 EXAM 7 | 4088.33 | 7830.00 | 4088.33 |
FLOOR 2 EXAM 8 | 3927.67 | 7830.00 | 3927.67 |
FLOOR 2 EXAM 9 | 3657.83 | 7830.00 | 3657.83 |
FLOOR 2 LOUNGE | 529.17 | 7830.00 | 529.17 |
FLOOR 2 NURSE STATION 1 | 584.00 | 7830.00 | 584.00 |
FLOOR 2 NURSE STATION 2 | 540.00 | 7830.00 | 540.00 |
FLOOR 2 OFFICE | 2508.17 | 7830.00 | 2508.17 |
FLOOR 2 RECEPTION | 1879.33 | 7830.00 | 1879.33 |
FLOOR 2 SCHEDULING 1 | 403.83 | 7830.00 | 403.83 |
FLOOR 2 SCHEDULING 2 | 460.00 | 7830.00 | 460.00 |
FLOOR 2 WORK | 941.17 | 7830.00 | 941.17 |
FLOOR 2 X-RAY | 11.50 | 7433.00 | 1.50 |
FLOOR 3 DRESSING ROOM | 2094.33 | 7830.00 | 2094.33 |
FLOOR 3 HUMID | 1735.67 | 7830.00 | 1735.67 |
FLOOR 3 LOCKER | 1377.00 | 7830.00 | 1377.00 |
FLOOR 3 LOUNGE | 1263.17 | 7830.00 | 1263.17 |
FLOOR 3 OFFICE | 2107.83 | 7830.00 | 2107.83 |
FLOOR 3 PHYSICAL THERAPY 1 | 4325.33 | 7674.00 | 4325.33 |
FLOOR 3 PHYSICAL THERAPY 2 | 4129.00 | 7830.00 | 4129.00 |
FLOOR 3 TREATMENT | 3613.83 | 7830.00 | 3613.83 |
FLOOR 3 WORK | 2796.17 | 7812.67 | 2796.17 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 7830.00 | 7830.00 | 7830.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 3.00 | 0.00 | 3.00 | 0.00 |
FLOOR 1 CAFE | 0.00 | 35.83 | 0.00 | 35.83 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DRESSING ROOM | 26.50 | 0.00 | 26.50 | 0.00 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 337.67 | 0.00 | 337.67 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 293.33 | 0.00 | 293.33 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 759.00 | 0.00 | 759.00 |
FLOOR 1 PACU | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP ROOM 1 | 1.17 | 0.00 | 1.17 | 0.00 |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PROCEDURE ROOM | 0.67 | 0.00 | 0.67 | 0.00 |
FLOOR 1 RECEPTION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECOVERY ROOM | 0.17 | 0.83 | 0.17 | 0.83 |
FLOOR 1 SCHEDULING | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL HOLD | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STEP DOWN | 1.67 | 0.00 | 1.67 | 0.00 |
FLOOR 2 CONFERENCE | 0.00 | 9.67 | 0.00 | 9.67 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 3 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 4 | 0.00 | 18.83 | 0.00 | 18.83 |
FLOOR 2 EXAM 5 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 6 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 8 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 2 | 0.00 | 1.83 | 0.00 | 1.83 |
FLOOR 2 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK | 0.83 | 0.00 | 0.83 | 0.00 |
FLOOR 2 X-RAY | 0.00 | 1567.67 | 0.00 | 1567.67 |
FLOOR 3 DRESSING ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOCKER | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE | 2.17 | 0.00 | 2.17 | 0.00 |
FLOOR 3 PHYSICAL THERAPY 1 | 0.00 | 9.33 | 0.00 | 9.33 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 TREATMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 BIO HAZ | 55.83 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 3.17 | 0.83 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 2.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 7.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 147.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 9.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 1.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 9.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.83 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 8.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 2.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 2.67 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 172.67 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 1.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 64.67 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 3.50 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 20.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 2822.50 | 447.17 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 3.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 10.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 14.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 11.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 8.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 13.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 4.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 1.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 4.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 1.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 1.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 1.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 4.50 | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 108.17 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 5097.17 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 1.17 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 2.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 3.17 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 1.17 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 11.50 | 0.00 | 0.00 | 0.00 |
NE STAIR | 84.00 | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 36.83 | 0.00 | 0.00 | 0.00 |
NW STAIR | 122.00 | 0.00 | 0.00 | 0.00 |
SW STAIR | 20.00 | 0.00 | 0.00 | 0.00 |
Facility | 2843.00 | 6871.67 | 27.33 | 1679.17 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:48
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000043 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.006175 | 0.000003 | 0.004762 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.307728 | 0.000039 | 0.061546 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.041505 | 0.000026 | 0.041505 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.051911 | 0.000033 | 0.051911 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.025186 | 0.000003 | 0.005037 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.014882 | 0.000009 | 0.014277 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.044616 | 0.000006 | 0.008923 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.277186 | 0.000035 | 0.055437 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.012364 | 0.000002 | 0.002473 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.017786 | 0.000002 | 0.003557 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.020379 | 0.000003 | 0.004076 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.270093 | 0.000036 | 0.057962 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.038267 | 0.000005 | 0.007653 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.226017 | 0.000028 | 0.045203 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.055745 | 0.000007 | 0.011149 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.113787 | 0.000014 | 0.022757 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.023335 | 0.000015 | 0.023335 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.158564 | 0.000020 | 0.031713 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.023984 | 0.000003 | 0.004797 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.415288 | 0.000052 | 0.083058 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.055930 | 0.000007 | 0.011186 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.067540 | 0.000008 | 0.013508 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.008421 | 0.000001 | 0.001684 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.075218 | 0.000009 | 0.015044 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.081574 | 0.000010 | 0.016315 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.777062 | 0.000293 | 0.466237 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.805401 | 0.000304 | 0.483240 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.748776 | 0.000471 | 0.748776 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000032 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.066802 | 0.000008 | 0.013360 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000056 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000100 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000212 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.173753 | 0.000022 | 0.034751 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.017308 | 0.000002 | 0.003462 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.285564 | 0.000156 | 0.248440 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.028764 | 0.000004 | 0.006636 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.012007 | 0.000003 | 0.004496 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000062 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000028 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000089 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.174442 | 0.000076 | 0.120365 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.072626 | 0.000011 | 0.017053 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.039664 | 0.000005 | 0.007933 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.156507 | 0.000098 | 0.156507 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.055442 | 0.000019 | 0.030756 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.049916 | 0.000030 | 0.047795 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.006016 | 0.000001 | 0.002290 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.063452 | 0.000031 | 0.049332 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.019606 | 0.000009 | 0.013991 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.261380 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.021810 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.261134 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.254836 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.339781 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.056544 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.218717 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.106182 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.127418 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.186879 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.049999 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.049099 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.047366 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.048361 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.050999 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.050779 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.033143 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.035627 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.057265 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.069821 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.278984 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.105152 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.506690 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.150609 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.083266 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.091229 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.014763 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.025771 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.033394 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.058626 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.406905 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.207351 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 0.849452 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.016804 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.078958 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.042213 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.020468 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.065947 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.388441 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.335669 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.090157 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 0.949422 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.209098 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 0.810984 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.279375 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.024827 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.022498 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.224633 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 0.811711 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.419913 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.040777 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.321572 | ||
NE STAIR VAV BOX COMPONENT | 0.142818 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.101002 | ||
NW STAIR VAV BOX COMPONENT | 0.146281 | ||
SW STAIR VAV BOX COMPONENT | 0.084555 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 1985.51 | 0.000043 | 42.81 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 139.14 | 0.000003 | 3.00 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 1798.21 | 0.000039 | 96.93 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1212.67 | 0.000026 | 26.15 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1516.71 | 0.000033 | 32.70 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 147.17 | 0.000003 | 7.93 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 417.13 | 0.000009 | 8.99 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 260.71 | 0.000006 | 14.05 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 1619.73 | 0.000035 | 87.31 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 72.25 | 0.000002 | 3.89 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 103.93 | 0.000002 | 5.60 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 119.08 | 0.000003 | 6.42 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 1693.52 | 0.000036 | 85.07 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 223.61 | 0.000005 | 12.05 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1240.94 | 0.000027 | 26.76 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 1320.73 | 0.000028 | 71.19 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 325.75 | 0.000007 | 17.56 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 664.92 | 0.000014 | 35.84 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 681.80 | 0.000015 | 14.70 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 926.57 | 0.000020 | 49.94 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 140.15 | 0.000003 | 7.55 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2426.73 | 0.000052 | 130.81 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1240.94 | 0.000027 | 26.76 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 326.83 | 0.000007 | 17.62 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 394.67 | 0.000008 | 21.27 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 49.21 | 0.000001 | 2.65 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 439.54 | 0.000009 | 23.69 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1240.94 | 0.000027 | 26.76 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 476.68 | 0.000010 | 25.69 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 13622.28 | 0.000293 | 293.71 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 14119.07 | 0.000304 | 304.42 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 21877.37 | 0.000471 | 471.70 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1489.13 | 0.000032 | 32.11 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 390.36 | 0.000008 | 21.04 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2605.98 | 0.000056 | 56.19 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 4660.43 | 0.000100 | 100.48 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1240.94 | 0.000027 | 26.76 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 9824.13 | 0.000212 | 211.82 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1015.33 | 0.000022 | 54.73 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 101.14 | 0.000002 | 5.45 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 7258.81 | 0.000156 | 156.51 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 193.90 | 0.000004 | 9.06 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 131.36 | 0.000003 | 3.78 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2895.53 | 0.000062 | 62.43 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1286.90 | 0.000028 | 27.75 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 4136.48 | 0.000089 | 89.19 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 3516.75 | 0.000076 | 75.83 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 498.25 | 0.000011 | 22.88 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 231.78 | 0.000005 | 12.49 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 4572.73 | 0.000098 | 98.59 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 898.61 | 0.000019 | 19.38 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 1396.45 | 0.000030 | 30.11 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 66.90 | 0.000001 | 1.90 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 1441.37 | 0.000031 | 31.08 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 408.78 | 0.000009 | 8.81 |
AHU-1_HEATC | 57506.44 | 0.001238 | 923.40 |
AHU-1_EXTRAWATERHEATC | 57506.44 | 0.001238 | 923.40 |
AHU-2_HEATC | 91533.81 | 0.001971 | 1466.84 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2434.98 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 1446.19 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 139.10 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 3826.15 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 7321.32 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 9761.76 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 1039.67 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 4335.72 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 2867.52 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 10737.93 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 3404.41 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 5368.97 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 482.35 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 328.42 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 330.65 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 277.88 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 293.04 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 291.77 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 655.18 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 252.47 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 561.05 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 673.26 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 2649.88 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 740.18 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 4830.68 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 865.39 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 2847.18 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 643.81 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 679.58 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 157.10 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 336.63 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 403.96 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 762.44 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 3358.11 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1191.42 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1220.22 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 6312.00 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 191.40 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 1318.64 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 422.50 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 588.05 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 438.16 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 2395.36 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 4338.56 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 1928.72 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 1604.38 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 8323.65 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 2969.76 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1220.22 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 16076.46 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 6661.86 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 1898.12 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 713.28 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 463.58 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 5227.42 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 7500.93 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 4864.59 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 955.67 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 2852.59 |
NE STAIR VAV BOX REHEAT COIL | 4103.09 |
NW ELEVATOR VAV BOX REHEAT COIL | 2576.84 |
NW STAIR VAV BOX REHEAT COIL | 4202.59 |
SW STAIR VAV BOX REHEAT COIL | 2005.97 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 7.11 |
AHU-2 AIR LOOP MAIN BRANCH | 10.49 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 7.11 |
AHU-2 | 10.49 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 7.11 | 2.07 |
AHU-2_OA_CONTROLLER | 10.49 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 7.11 | 176519.48 | 0.676083 | 2.37 | 58833.94 |
AHU-2_COOLC DXCOIL | 10.49 | 239606.20 | 0.697461 | 3.50 | 79860.75 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 7.11 |
AHU-2_FAN | 10.49 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.001238 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.001238 |
AHU-2_HEATC_CONTROLLER | 0.001971 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.002129 | 1.60 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.002129 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
HEATSYS1 PUMP | 0.002129 | 543.94 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | -3.4 |
February | 19.44 | -4.2 |
March | 19.55 | 2.67 |
April | 19.46 | 7.47 |
May | 19.47 | 13.73 |
June | 19.52 | 18.63 |
July | 19.44 | 22.03 |
August | 19.55 | 20.69 |
September | 19.47 | 16.55 |
October | 19.43 | 9.73 |
November | 19.43 | 6.03 |
December | 19.40 | -2.2 |
Annual Sum or Average | 19.47 | 9.05 |
Minimum of Months | 19.40 | -4.2 |
Maximum of Months | 19.55 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.03 | -3.4 |
February | 20.05 | -4.2 |
March | 20.32 | 2.67 |
April | 20.45 | 7.47 |
May | 20.75 | 13.73 |
June | 21.42 | 18.63 |
July | 21.54 | 22.03 |
August | 21.54 | 20.69 |
September | 21.13 | 16.55 |
October | 20.46 | 9.73 |
November | 20.29 | 6.03 |
December | 20.08 | -2.2 |
Annual Sum or Average | 20.67 | 9.05 |
Minimum of Months | 20.03 | -4.2 |
Maximum of Months | 21.54 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | -3.4 |
February | 20.67 | -4.2 |
March | 21.12 | 2.67 |
April | 21.13 | 7.47 |
May | 21.29 | 13.73 |
June | 21.60 | 18.63 |
July | 21.61 | 22.03 |
August | 21.70 | 20.69 |
September | 21.49 | 16.55 |
October | 21.08 | 9.73 |
November | 20.94 | 6.03 |
December | 20.66 | -2.2 |
Annual Sum or Average | 21.16 | 9.05 |
Minimum of Months | 20.66 | -4.2 |
Maximum of Months | 21.70 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.24 | -3.4 |
February | 20.26 | -4.2 |
March | 20.31 | 2.67 |
April | 20.08 | 7.47 |
May | 19.97 | 13.73 |
June | 20.07 | 18.63 |
July | 19.95 | 22.03 |
August | 20.12 | 20.69 |
September | 20.02 | 16.55 |
October | 19.99 | 9.73 |
November | 20.14 | 6.03 |
December | 20.21 | -2.2 |
Annual Sum or Average | 20.11 | 9.05 |
Minimum of Months | 19.95 | -4.2 |
Maximum of Months | 20.31 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.94 | -3.4 |
February | 19.95 | -4.2 |
March | 20.02 | 2.67 |
April | 19.84 | 7.47 |
May | 19.77 | 13.73 |
June | 19.86 | 18.63 |
July | 19.74 | 22.03 |
August | 19.90 | 20.69 |
September | 19.80 | 16.55 |
October | 19.76 | 9.73 |
November | 19.87 | 6.03 |
December | 19.90 | -2.2 |
Annual Sum or Average | 19.86 | 9.05 |
Minimum of Months | 19.74 | -4.2 |
Maximum of Months | 20.02 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.50 | -3.4 |
February | 21.54 | -4.2 |
March | 21.66 | 2.67 |
April | 21.58 | 7.47 |
May | 21.55 | 13.73 |
June | 21.74 | 18.63 |
July | 21.69 | 22.03 |
August | 21.80 | 20.69 |
September | 21.72 | 16.55 |
October | 21.57 | 9.73 |
November | 21.58 | 6.03 |
December | 21.54 | -2.2 |
Annual Sum or Average | 21.62 | 9.05 |
Minimum of Months | 21.50 | -4.2 |
Maximum of Months | 21.80 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | -3.4 |
February | 19.49 | -4.2 |
March | 19.91 | 2.67 |
April | 20.17 | 7.47 |
May | 20.76 | 13.73 |
June | 21.42 | 18.63 |
July | 21.61 | 22.03 |
August | 21.53 | 20.69 |
September | 21.05 | 16.55 |
October | 20.21 | 9.73 |
November | 19.78 | 6.03 |
December | 19.49 | -2.2 |
Annual Sum or Average | 20.41 | 9.05 |
Minimum of Months | 19.47 | -4.2 |
Maximum of Months | 21.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | -3.4 |
February | 21.30 | -4.2 |
March | 21.63 | 2.67 |
April | 21.76 | 7.47 |
May | 21.90 | 13.73 |
June | 22.10 | 18.63 |
July | 22.12 | 22.03 |
August | 22.13 | 20.69 |
September | 22.03 | 16.55 |
October | 21.72 | 9.73 |
November | 21.59 | 6.03 |
December | 21.31 | -2.2 |
Annual Sum or Average | 21.74 | 9.05 |
Minimum of Months | 21.28 | -4.2 |
Maximum of Months | 22.13 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.84 | -3.4 |
February | 20.86 | -4.2 |
March | 21.06 | 2.67 |
April | 21.01 | 7.47 |
May | 21.07 | 13.73 |
June | 21.21 | 18.63 |
July | 21.14 | 22.03 |
August | 21.23 | 20.69 |
September | 21.07 | 16.55 |
October | 20.95 | 9.73 |
November | 20.96 | 6.03 |
December | 20.83 | -2.2 |
Annual Sum or Average | 21.02 | 9.05 |
Minimum of Months | 20.83 | -4.2 |
Maximum of Months | 21.23 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | -3.4 |
February | 21.78 | -4.2 |
March | 21.88 | 2.67 |
April | 21.83 | 7.47 |
May | 21.79 | 13.73 |
June | 21.97 | 18.63 |
July | 21.94 | 22.03 |
August | 22.02 | 20.69 |
September | 21.96 | 16.55 |
October | 21.82 | 9.73 |
November | 21.83 | 6.03 |
December | 21.79 | -2.2 |
Annual Sum or Average | 21.86 | 9.05 |
Minimum of Months | 21.73 | -4.2 |
Maximum of Months | 22.02 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.67 | -3.4 |
February | 20.70 | -4.2 |
March | 20.93 | 2.67 |
April | 20.96 | 7.47 |
May | 21.10 | 13.73 |
June | 21.52 | 18.63 |
July | 21.51 | 22.03 |
August | 21.60 | 20.69 |
September | 21.41 | 16.55 |
October | 21.00 | 9.73 |
November | 20.90 | 6.03 |
December | 20.74 | -2.2 |
Annual Sum or Average | 21.09 | 9.05 |
Minimum of Months | 20.67 | -4.2 |
Maximum of Months | 21.60 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | -3.4 |
February | 20.97 | -4.2 |
March | 21.22 | 2.67 |
April | 21.28 | 7.47 |
May | 21.43 | 13.73 |
June | 21.81 | 18.63 |
July | 21.83 | 22.03 |
August | 21.88 | 20.69 |
September | 21.67 | 16.55 |
October | 21.28 | 9.73 |
November | 21.18 | 6.03 |
December | 21.00 | -2.2 |
Annual Sum or Average | 21.38 | 9.05 |
Minimum of Months | 20.93 | -4.2 |
Maximum of Months | 21.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.35 | -3.4 |
February | 20.43 | -4.2 |
March | 21.00 | 2.67 |
April | 21.21 | 7.47 |
May | 21.49 | 13.73 |
June | 21.86 | 18.63 |
July | 21.90 | 22.03 |
August | 21.91 | 20.69 |
September | 21.66 | 16.55 |
October | 21.11 | 9.73 |
November | 20.89 | 6.03 |
December | 20.43 | -2.2 |
Annual Sum or Average | 21.19 | 9.05 |
Minimum of Months | 20.35 | -4.2 |
Maximum of Months | 21.91 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.39 | -3.4 |
February | 21.44 | -4.2 |
March | 21.76 | 2.67 |
April | 21.81 | 7.47 |
May | 21.89 | 13.73 |
June | 22.11 | 18.63 |
July | 22.12 | 22.03 |
August | 22.14 | 20.69 |
September | 22.07 | 16.55 |
October | 21.79 | 9.73 |
November | 21.69 | 6.03 |
December | 21.49 | -2.2 |
Annual Sum or Average | 21.81 | 9.05 |
Minimum of Months | 21.39 | -4.2 |
Maximum of Months | 22.14 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.45 | -3.4 |
February | 19.47 | -4.2 |
March | 19.58 | 2.67 |
April | 19.51 | 7.47 |
May | 19.53 | 13.73 |
June | 19.60 | 18.63 |
July | 19.50 | 22.03 |
August | 19.61 | 20.69 |
September | 19.50 | 16.55 |
October | 19.45 | 9.73 |
November | 19.46 | 6.03 |
December | 19.43 | -2.2 |
Annual Sum or Average | 19.51 | 9.05 |
Minimum of Months | 19.43 | -4.2 |
Maximum of Months | 19.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.40 | -3.4 |
February | 21.44 | -4.2 |
March | 21.70 | 2.67 |
April | 21.78 | 7.47 |
May | 21.86 | 13.73 |
June | 22.08 | 18.63 |
July | 22.09 | 22.03 |
August | 22.11 | 20.69 |
September | 22.01 | 16.55 |
October | 21.77 | 9.73 |
November | 21.70 | 6.03 |
December | 21.47 | -2.2 |
Annual Sum or Average | 21.78 | 9.05 |
Minimum of Months | 21.40 | -4.2 |
Maximum of Months | 22.11 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.28 | -3.4 |
February | 21.32 | -4.2 |
March | 21.54 | 2.67 |
April | 21.56 | 7.47 |
May | 21.60 | 13.73 |
June | 21.90 | 18.63 |
July | 21.89 | 22.03 |
August | 21.96 | 20.69 |
September | 21.87 | 16.55 |
October | 21.59 | 9.73 |
November | 21.52 | 6.03 |
December | 21.38 | -2.2 |
Annual Sum or Average | 21.62 | 9.05 |
Minimum of Months | 21.28 | -4.2 |
Maximum of Months | 21.96 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.74 | -4.2 |
March | 21.87 | 2.67 |
April | 21.86 | 7.47 |
May | 21.88 | 13.73 |
June | 22.06 | 18.63 |
July | 22.06 | 22.03 |
August | 22.09 | 20.69 |
September | 22.01 | 16.55 |
October | 21.84 | 9.73 |
November | 21.82 | 6.03 |
December | 21.75 | -2.2 |
Annual Sum or Average | 21.89 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 22.09 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.36 | -3.4 |
February | 19.35 | -4.2 |
March | 19.54 | 2.67 |
April | 19.58 | 7.47 |
May | 19.97 | 13.73 |
June | 20.93 | 18.63 |
July | 21.32 | 22.03 |
August | 21.11 | 20.69 |
September | 20.30 | 16.55 |
October | 19.53 | 9.73 |
November | 19.42 | 6.03 |
December | 19.35 | -2.2 |
Annual Sum or Average | 19.99 | 9.05 |
Minimum of Months | 19.35 | -4.2 |
Maximum of Months | 21.32 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | -3.4 |
February | 21.82 | -4.2 |
March | 21.96 | 2.67 |
April | 22.01 | 7.47 |
May | 22.06 | 13.73 |
June | 22.16 | 18.63 |
July | 22.16 | 22.03 |
August | 22.17 | 20.69 |
September | 22.12 | 16.55 |
October | 21.97 | 9.73 |
November | 21.94 | 6.03 |
December | 21.83 | -2.2 |
Annual Sum or Average | 22.00 | 9.05 |
Minimum of Months | 21.79 | -4.2 |
Maximum of Months | 22.17 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | -3.4 |
February | 21.13 | -4.2 |
March | 21.44 | 2.67 |
April | 21.53 | 7.47 |
May | 21.65 | 13.73 |
June | 21.94 | 18.63 |
July | 21.95 | 22.03 |
August | 22.00 | 20.69 |
September | 21.87 | 16.55 |
October | 21.53 | 9.73 |
November | 21.41 | 6.03 |
December | 21.18 | -2.2 |
Annual Sum or Average | 21.56 | 9.05 |
Minimum of Months | 21.08 | -4.2 |
Maximum of Months | 22.00 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.06 | -3.4 |
February | 22.09 | -4.2 |
March | 22.13 | 2.67 |
April | 22.13 | 7.47 |
May | 22.11 | 13.73 |
June | 22.16 | 18.63 |
July | 22.16 | 22.03 |
August | 22.17 | 20.69 |
September | 22.15 | 16.55 |
October | 22.09 | 9.73 |
November | 22.10 | 6.03 |
December | 22.09 | -2.2 |
Annual Sum or Average | 22.12 | 9.05 |
Minimum of Months | 22.06 | -4.2 |
Maximum of Months | 22.17 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | -3.4 |
February | 19.40 | -4.2 |
March | 19.48 | 2.67 |
April | 19.41 | 7.47 |
May | 19.43 | 13.73 |
June | 19.47 | 18.63 |
July | 19.38 | 22.03 |
August | 19.48 | 20.69 |
September | 19.41 | 16.55 |
October | 19.38 | 9.73 |
November | 19.39 | 6.03 |
December | 19.37 | -2.2 |
Annual Sum or Average | 19.41 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 19.48 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.70 | -3.4 |
February | 21.75 | -4.2 |
March | 21.84 | 2.67 |
April | 21.77 | 7.47 |
May | 21.73 | 13.73 |
June | 21.89 | 18.63 |
July | 21.84 | 22.03 |
August | 21.93 | 20.69 |
September | 21.87 | 16.55 |
October | 21.75 | 9.73 |
November | 21.77 | 6.03 |
December | 21.75 | -2.2 |
Annual Sum or Average | 21.80 | 9.05 |
Minimum of Months | 21.70 | -4.2 |
Maximum of Months | 21.93 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | -3.4 |
February | 20.83 | -4.2 |
March | 21.14 | 2.67 |
April | 21.11 | 7.47 |
May | 21.16 | 13.73 |
June | 21.49 | 18.63 |
July | 21.47 | 22.03 |
August | 21.61 | 20.69 |
September | 21.48 | 16.55 |
October | 21.15 | 9.73 |
November | 21.06 | 6.03 |
December | 20.88 | -2.2 |
Annual Sum or Average | 21.19 | 9.05 |
Minimum of Months | 20.82 | -4.2 |
Maximum of Months | 21.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | -3.4 |
February | 21.54 | -4.2 |
March | 21.70 | 2.67 |
April | 21.68 | 7.47 |
May | 21.66 | 13.73 |
June | 21.94 | 18.63 |
July | 21.93 | 22.03 |
August | 22.01 | 20.69 |
September | 21.94 | 16.55 |
October | 21.70 | 9.73 |
November | 21.67 | 6.03 |
December | 21.58 | -2.2 |
Annual Sum or Average | 21.74 | 9.05 |
Minimum of Months | 21.49 | -4.2 |
Maximum of Months | 22.01 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | -3.4 |
February | 21.56 | -4.2 |
March | 21.71 | 2.67 |
April | 21.64 | 7.47 |
May | 21.62 | 13.73 |
June | 21.81 | 18.63 |
July | 21.76 | 22.03 |
August | 21.86 | 20.69 |
September | 21.78 | 16.55 |
October | 21.62 | 9.73 |
November | 21.62 | 6.03 |
December | 21.56 | -2.2 |
Annual Sum or Average | 21.67 | 9.05 |
Minimum of Months | 21.52 | -4.2 |
Maximum of Months | 21.86 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | -3.4 |
February | 19.40 | -4.2 |
March | 19.48 | 2.67 |
April | 19.41 | 7.47 |
May | 19.43 | 13.73 |
June | 19.47 | 18.63 |
July | 19.37 | 22.03 |
August | 19.48 | 20.69 |
September | 19.41 | 16.55 |
October | 19.39 | 9.73 |
November | 19.39 | 6.03 |
December | 19.38 | -2.2 |
Annual Sum or Average | 19.42 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 19.48 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | -3.4 |
February | 21.57 | -4.2 |
March | 21.77 | 2.67 |
April | 21.79 | 7.47 |
May | 21.82 | 13.73 |
June | 22.03 | 18.63 |
July | 22.03 | 22.03 |
August | 22.08 | 20.69 |
September | 22.01 | 16.55 |
October | 21.78 | 9.73 |
November | 21.73 | 6.03 |
December | 21.60 | -2.2 |
Annual Sum or Average | 21.81 | 9.05 |
Minimum of Months | 21.52 | -4.2 |
Maximum of Months | 22.08 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.70 | -3.4 |
February | 18.72 | -4.2 |
March | 18.99 | 2.67 |
April | 19.00 | 7.47 |
May | 19.05 | 13.73 |
June | 19.24 | 18.63 |
July | 19.28 | 22.03 |
August | 19.31 | 20.69 |
September | 19.14 | 16.55 |
October | 18.94 | 9.73 |
November | 18.84 | 6.03 |
December | 18.66 | -2.2 |
Annual Sum or Average | 18.99 | 9.05 |
Minimum of Months | 18.66 | -4.2 |
Maximum of Months | 19.31 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.89 | -3.4 |
February | 18.91 | -4.2 |
March | 19.10 | 2.67 |
April | 19.11 | 7.47 |
May | 19.12 | 13.73 |
June | 19.27 | 18.63 |
July | 19.28 | 22.03 |
August | 19.30 | 20.69 |
September | 19.16 | 16.55 |
October | 19.00 | 9.73 |
November | 18.98 | 6.03 |
December | 18.86 | -2.2 |
Annual Sum or Average | 19.08 | 9.05 |
Minimum of Months | 18.86 | -4.2 |
Maximum of Months | 19.30 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.43 | -3.4 |
February | 18.42 | -4.2 |
March | 18.40 | 2.67 |
April | 18.35 | 7.47 |
May | 18.34 | 13.73 |
June | 18.33 | 18.63 |
July | 18.33 | 22.03 |
August | 18.32 | 20.69 |
September | 18.32 | 16.55 |
October | 18.34 | 9.73 |
November | 18.37 | 6.03 |
December | 18.41 | -2.2 |
Annual Sum or Average | 18.36 | 9.05 |
Minimum of Months | 18.32 | -4.2 |
Maximum of Months | 18.43 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | -3.4 |
February | 19.65 | -4.2 |
March | 19.72 | 2.67 |
April | 19.58 | 7.47 |
May | 19.55 | 13.73 |
June | 19.60 | 18.63 |
July | 19.50 | 22.03 |
August | 19.61 | 20.69 |
September | 19.54 | 16.55 |
October | 19.53 | 9.73 |
November | 19.58 | 6.03 |
December | 19.60 | -2.2 |
Annual Sum or Average | 19.59 | 9.05 |
Minimum of Months | 19.50 | -4.2 |
Maximum of Months | 19.72 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | -3.4 |
February | 20.77 | -4.2 |
March | 21.13 | 2.67 |
April | 21.22 | 7.47 |
May | 21.36 | 13.73 |
June | 21.73 | 18.63 |
July | 21.73 | 22.03 |
August | 21.82 | 20.69 |
September | 21.68 | 16.55 |
October | 21.28 | 9.73 |
November | 21.12 | 6.03 |
December | 20.83 | -2.2 |
Annual Sum or Average | 21.29 | 9.05 |
Minimum of Months | 20.72 | -4.2 |
Maximum of Months | 21.82 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.41 | -3.4 |
February | 19.43 | -4.2 |
March | 19.52 | 2.67 |
April | 19.45 | 7.47 |
May | 19.47 | 13.73 |
June | 19.52 | 18.63 |
July | 19.44 | 22.03 |
August | 19.55 | 20.69 |
September | 19.46 | 16.55 |
October | 19.42 | 9.73 |
November | 19.42 | 6.03 |
December | 19.40 | -2.2 |
Annual Sum or Average | 19.46 | 9.05 |
Minimum of Months | 19.40 | -4.2 |
Maximum of Months | 19.55 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | -3.4 |
February | 19.52 | -4.2 |
March | 19.59 | 2.67 |
April | 19.48 | 7.47 |
May | 19.47 | 13.73 |
June | 19.51 | 18.63 |
July | 19.42 | 22.03 |
August | 19.52 | 20.69 |
September | 19.45 | 16.55 |
October | 19.44 | 9.73 |
November | 19.48 | 6.03 |
December | 19.49 | -2.2 |
Annual Sum or Average | 19.49 | 9.05 |
Minimum of Months | 19.42 | -4.2 |
Maximum of Months | 19.59 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | -3.4 |
February | 19.40 | -4.2 |
March | 19.47 | 2.67 |
April | 19.41 | 7.47 |
May | 19.43 | 13.73 |
June | 19.47 | 18.63 |
July | 19.38 | 22.03 |
August | 19.49 | 20.69 |
September | 19.41 | 16.55 |
October | 19.38 | 9.73 |
November | 19.39 | 6.03 |
December | 19.37 | -2.2 |
Annual Sum or Average | 19.42 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 19.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | -3.4 |
February | 19.41 | -4.2 |
March | 19.49 | 2.67 |
April | 19.43 | 7.47 |
May | 19.45 | 13.73 |
June | 19.49 | 18.63 |
July | 19.39 | 22.03 |
August | 19.49 | 20.69 |
September | 19.43 | 16.55 |
October | 19.40 | 9.73 |
November | 19.40 | 6.03 |
December | 19.39 | -2.2 |
Annual Sum or Average | 19.43 | 9.05 |
Minimum of Months | 19.39 | -4.2 |
Maximum of Months | 19.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.17 | -3.4 |
February | 21.20 | -4.2 |
March | 21.56 | 2.67 |
April | 21.60 | 7.47 |
May | 21.69 | 13.73 |
June | 21.95 | 18.63 |
July | 21.96 | 22.03 |
August | 22.02 | 20.69 |
September | 21.90 | 16.55 |
October | 21.58 | 9.73 |
November | 21.48 | 6.03 |
December | 21.24 | -2.2 |
Annual Sum or Average | 21.62 | 9.05 |
Minimum of Months | 21.17 | -4.2 |
Maximum of Months | 22.02 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.06 | -3.4 |
February | 21.11 | -4.2 |
March | 21.41 | 2.67 |
April | 21.44 | 7.47 |
May | 21.52 | 13.73 |
June | 21.84 | 18.63 |
July | 21.84 | 22.03 |
August | 21.92 | 20.69 |
September | 21.82 | 16.55 |
October | 21.48 | 9.73 |
November | 21.38 | 6.03 |
December | 21.17 | -2.2 |
Annual Sum or Average | 21.50 | 9.05 |
Minimum of Months | 21.06 | -4.2 |
Maximum of Months | 21.92 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | -3.4 |
February | 19.49 | -4.2 |
March | 19.66 | 2.67 |
April | 19.55 | 7.47 |
May | 19.54 | 13.73 |
June | 19.61 | 18.63 |
July | 19.58 | 22.03 |
August | 19.73 | 20.69 |
September | 19.62 | 16.55 |
October | 19.53 | 9.73 |
November | 19.48 | 6.03 |
December | 19.44 | -2.2 |
Annual Sum or Average | 19.56 | 9.05 |
Minimum of Months | 19.44 | -4.2 |
Maximum of Months | 19.73 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -3.4 |
February | 20.66 | -4.2 |
March | 21.14 | 2.67 |
April | 21.22 | 7.47 |
May | 21.39 | 13.73 |
June | 21.73 | 18.63 |
July | 21.76 | 22.03 |
August | 21.83 | 20.69 |
September | 21.66 | 16.55 |
October | 21.26 | 9.73 |
November | 21.11 | 6.03 |
December | 20.73 | -2.2 |
Annual Sum or Average | 21.26 | 9.05 |
Minimum of Months | 20.62 | -4.2 |
Maximum of Months | 21.83 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.50 | -3.4 |
February | 20.58 | -4.2 |
March | 21.06 | 2.67 |
April | 21.25 | 7.47 |
May | 21.48 | 13.73 |
June | 21.88 | 18.63 |
July | 21.91 | 22.03 |
August | 21.95 | 20.69 |
September | 21.77 | 16.55 |
October | 21.20 | 9.73 |
November | 20.91 | 6.03 |
December | 20.55 | -2.2 |
Annual Sum or Average | 21.26 | 9.05 |
Minimum of Months | 20.50 | -4.2 |
Maximum of Months | 21.95 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | -3.4 |
February | 19.43 | -4.2 |
March | 19.50 | 2.67 |
April | 19.42 | 7.47 |
May | 19.44 | 13.73 |
June | 19.47 | 18.63 |
July | 19.38 | 22.03 |
August | 19.48 | 20.69 |
September | 19.41 | 16.55 |
October | 19.39 | 9.73 |
November | 19.40 | 6.03 |
December | 19.40 | -2.2 |
Annual Sum or Average | 19.43 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.50 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | -3.4 |
February | 19.42 | -4.2 |
March | 19.49 | 2.67 |
April | 19.42 | 7.47 |
May | 19.44 | 13.73 |
June | 19.48 | 18.63 |
July | 19.38 | 22.03 |
August | 19.49 | 20.69 |
September | 19.42 | 16.55 |
October | 19.39 | 9.73 |
November | 19.40 | 6.03 |
December | 19.39 | -2.2 |
Annual Sum or Average | 19.43 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | -3.4 |
February | 19.41 | -4.2 |
March | 19.49 | 2.67 |
April | 19.41 | 7.47 |
May | 19.44 | 13.73 |
June | 19.47 | 18.63 |
July | 19.38 | 22.03 |
August | 19.48 | 20.69 |
September | 19.41 | 16.55 |
October | 19.39 | 9.73 |
November | 19.39 | 6.03 |
December | 19.38 | -2.2 |
Annual Sum or Average | 19.42 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | -3.4 |
February | 19.50 | -4.2 |
March | 19.73 | 2.67 |
April | 19.68 | 7.47 |
May | 19.75 | 13.73 |
June | 19.94 | 18.63 |
July | 19.93 | 22.03 |
August | 20.03 | 20.69 |
September | 19.83 | 16.55 |
October | 19.61 | 9.73 |
November | 19.51 | 6.03 |
December | 19.44 | -2.2 |
Annual Sum or Average | 19.70 | 9.05 |
Minimum of Months | 19.44 | -4.2 |
Maximum of Months | 20.03 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.65 | -3.4 |
February | 20.72 | -4.2 |
March | 21.14 | 2.67 |
April | 21.23 | 7.47 |
May | 21.39 | 13.73 |
June | 21.78 | 18.63 |
July | 21.81 | 22.03 |
August | 21.88 | 20.69 |
September | 21.73 | 16.55 |
October | 21.27 | 9.73 |
November | 21.05 | 6.03 |
December | 20.71 | -2.2 |
Annual Sum or Average | 21.28 | 9.05 |
Minimum of Months | 20.65 | -4.2 |
Maximum of Months | 21.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -3.4 |
February | 21.33 | -4.2 |
March | 21.53 | 2.67 |
April | 21.52 | 7.47 |
May | 21.53 | 13.73 |
June | 21.87 | 18.63 |
July | 21.86 | 22.03 |
August | 21.95 | 20.69 |
September | 21.87 | 16.55 |
October | 21.57 | 9.73 |
November | 21.51 | 6.03 |
December | 21.39 | -2.2 |
Annual Sum or Average | 21.60 | 9.05 |
Minimum of Months | 21.29 | -4.2 |
Maximum of Months | 21.95 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.37 | -3.4 |
February | 19.37 | -4.2 |
March | 19.61 | 2.67 |
April | 19.73 | 7.47 |
May | 20.29 | 13.73 |
June | 21.29 | 18.63 |
July | 21.60 | 22.03 |
August | 21.43 | 20.69 |
September | 20.69 | 16.55 |
October | 19.72 | 9.73 |
November | 19.50 | 6.03 |
December | 19.37 | -2.2 |
Annual Sum or Average | 20.17 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 21.60 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | -3.4 |
February | 19.69 | -4.2 |
March | 20.23 | 2.67 |
April | 20.61 | 7.47 |
May | 21.07 | 13.73 |
June | 21.66 | 18.63 |
July | 21.77 | 22.03 |
August | 21.74 | 20.69 |
September | 21.38 | 16.55 |
October | 20.49 | 9.73 |
November | 20.07 | 6.03 |
December | 19.66 | -2.2 |
Annual Sum or Average | 20.67 | 9.05 |
Minimum of Months | 19.64 | -4.2 |
Maximum of Months | 21.77 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.45 | -3.4 |
February | 19.46 | -4.2 |
March | 19.78 | 2.67 |
April | 19.98 | 7.47 |
May | 20.59 | 13.73 |
June | 21.51 | 18.63 |
July | 21.73 | 22.03 |
August | 21.63 | 20.69 |
September | 21.00 | 16.55 |
October | 19.99 | 9.73 |
November | 19.70 | 6.03 |
December | 19.46 | -2.2 |
Annual Sum or Average | 20.36 | 9.05 |
Minimum of Months | 19.45 | -4.2 |
Maximum of Months | 21.73 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -3.4 |
February | 20.60 | -4.2 |
March | 21.01 | 2.67 |
April | 21.19 | 7.47 |
May | 21.43 | 13.73 |
June | 21.88 | 18.63 |
July | 21.91 | 22.03 |
August | 21.95 | 20.69 |
September | 21.76 | 16.55 |
October | 21.17 | 9.73 |
November | 20.92 | 6.03 |
December | 20.59 | -2.2 |
Annual Sum or Average | 21.25 | 9.05 |
Minimum of Months | 20.53 | -4.2 |
Maximum of Months | 21.95 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | -3.4 |
February | 19.66 | -4.2 |
March | 20.10 | 2.67 |
April | 20.44 | 7.47 |
May | 20.94 | 13.73 |
June | 21.67 | 18.63 |
July | 21.83 | 22.03 |
August | 21.76 | 20.69 |
September | 21.35 | 16.55 |
October | 20.37 | 9.73 |
November | 20.04 | 6.03 |
December | 19.67 | -2.2 |
Annual Sum or Average | 20.63 | 9.05 |
Minimum of Months | 19.63 | -4.2 |
Maximum of Months | 21.83 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 11.40 | -3.4 |
February | 11.40 | -4.2 |
March | 13.95 | 2.67 |
April | 15.99 | 7.47 |
May | 18.27 | 13.73 |
June | 20.47 | 18.63 |
July | 21.88 | 22.03 |
August | 21.45 | 20.69 |
September | 19.76 | 16.55 |
October | 16.72 | 9.73 |
November | 14.84 | 6.03 |
December | 12.23 | -2.2 |
Annual Sum or Average | 16.56 | 9.05 |
Minimum of Months | 11.40 | -4.2 |
Maximum of Months | 21.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.95 | -3.4 |
February | 20.02 | -4.2 |
March | 20.59 | 2.67 |
April | 20.72 | 7.47 |
May | 20.96 | 13.73 |
June | 21.15 | 18.63 |
July | 21.06 | 22.03 |
August | 21.22 | 20.69 |
September | 21.03 | 16.55 |
October | 20.67 | 9.73 |
November | 20.37 | 6.03 |
December | 19.95 | -2.2 |
Annual Sum or Average | 20.64 | 9.05 |
Minimum of Months | 19.95 | -4.2 |
Maximum of Months | 21.22 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | -3.4 |
February | 19.50 | -4.2 |
March | 19.64 | 2.67 |
April | 19.60 | 7.47 |
May | 19.57 | 13.73 |
June | 19.52 | 18.63 |
July | 19.39 | 22.03 |
August | 19.50 | 20.69 |
September | 19.48 | 16.55 |
October | 19.54 | 9.73 |
November | 19.53 | 6.03 |
December | 19.45 | -2.2 |
Annual Sum or Average | 19.52 | 9.05 |
Minimum of Months | 19.39 | -4.2 |
Maximum of Months | 19.64 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -3.4 |
February | 21.37 | -4.2 |
March | 21.67 | 2.67 |
April | 21.67 | 7.47 |
May | 21.65 | 13.73 |
June | 21.71 | 18.63 |
July | 21.56 | 22.03 |
August | 21.72 | 20.69 |
September | 21.66 | 16.55 |
October | 21.57 | 9.73 |
November | 21.52 | 6.03 |
December | 21.36 | -2.2 |
Annual Sum or Average | 21.56 | 9.05 |
Minimum of Months | 21.29 | -4.2 |
Maximum of Months | 21.72 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | -3.4 |
February | 19.52 | -4.2 |
March | 19.90 | 2.67 |
April | 20.05 | 7.47 |
May | 20.25 | 13.73 |
June | 20.45 | 18.63 |
July | 20.33 | 22.03 |
August | 20.43 | 20.69 |
September | 20.21 | 16.55 |
October | 19.90 | 9.73 |
November | 19.65 | 6.03 |
December | 19.45 | -2.2 |
Annual Sum or Average | 19.97 | 9.05 |
Minimum of Months | 19.45 | -4.2 |
Maximum of Months | 20.45 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -3.4 |
February | 19.65 | -4.2 |
March | 19.90 | 2.67 |
April | 19.85 | 7.47 |
May | 19.81 | 13.73 |
June | 19.76 | 18.63 |
July | 19.57 | 22.03 |
August | 19.74 | 20.69 |
September | 19.73 | 16.55 |
October | 19.79 | 9.73 |
November | 19.74 | 6.03 |
December | 19.59 | -2.2 |
Annual Sum or Average | 19.73 | 9.05 |
Minimum of Months | 19.57 | -4.2 |
Maximum of Months | 19.90 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.60 | -3.4 |
February | 19.64 | -4.2 |
March | 19.87 | 2.67 |
April | 19.80 | 7.47 |
May | 19.75 | 13.73 |
June | 19.69 | 18.63 |
July | 19.52 | 22.03 |
August | 19.68 | 20.69 |
September | 19.66 | 16.55 |
October | 19.74 | 9.73 |
November | 19.71 | 6.03 |
December | 19.58 | -2.2 |
Annual Sum or Average | 19.69 | 9.05 |
Minimum of Months | 19.52 | -4.2 |
Maximum of Months | 19.87 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.65 | -3.4 |
February | 19.71 | -4.2 |
March | 20.14 | 2.67 |
April | 20.15 | 7.47 |
May | 20.16 | 13.73 |
June | 20.21 | 18.63 |
July | 20.10 | 22.03 |
August | 20.29 | 20.69 |
September | 20.25 | 16.55 |
October | 20.12 | 9.73 |
November | 19.86 | 6.03 |
December | 19.61 | -2.2 |
Annual Sum or Average | 20.02 | 9.05 |
Minimum of Months | 19.61 | -4.2 |
Maximum of Months | 20.29 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | -3.4 |
February | 19.55 | -4.2 |
March | 19.85 | 2.67 |
April | 20.11 | 7.47 |
May | 20.24 | 13.73 |
June | 20.36 | 18.63 |
July | 20.23 | 22.03 |
August | 20.27 | 20.69 |
September | 20.09 | 16.55 |
October | 19.88 | 9.73 |
November | 19.69 | 6.03 |
December | 19.51 | -2.2 |
Annual Sum or Average | 19.94 | 9.05 |
Minimum of Months | 19.51 | -4.2 |
Maximum of Months | 20.36 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.50 | -3.4 |
February | 19.53 | -4.2 |
March | 19.74 | 2.67 |
April | 19.77 | 7.47 |
May | 19.84 | 13.73 |
June | 19.90 | 18.63 |
July | 19.74 | 22.03 |
August | 19.86 | 20.69 |
September | 19.75 | 16.55 |
October | 19.71 | 9.73 |
November | 19.63 | 6.03 |
December | 19.51 | -2.2 |
Annual Sum or Average | 19.71 | 9.05 |
Minimum of Months | 19.50 | -4.2 |
Maximum of Months | 19.90 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.60 | -3.4 |
February | 19.63 | -4.2 |
March | 19.80 | 2.67 |
April | 19.78 | 7.47 |
May | 19.76 | 13.73 |
June | 19.71 | 18.63 |
July | 19.52 | 22.03 |
August | 19.66 | 20.69 |
September | 19.63 | 16.55 |
October | 19.71 | 9.73 |
November | 19.70 | 6.03 |
December | 19.61 | -2.2 |
Annual Sum or Average | 19.68 | 9.05 |
Minimum of Months | 19.52 | -4.2 |
Maximum of Months | 19.80 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | -3.4 |
February | 19.58 | -4.2 |
March | 19.82 | 2.67 |
April | 19.89 | 7.47 |
May | 19.93 | 13.73 |
June | 19.97 | 18.63 |
July | 19.78 | 22.03 |
August | 19.91 | 20.69 |
September | 19.81 | 16.55 |
October | 19.80 | 9.73 |
November | 19.72 | 6.03 |
December | 19.56 | -2.2 |
Annual Sum or Average | 19.78 | 9.05 |
Minimum of Months | 19.54 | -4.2 |
Maximum of Months | 19.97 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.66 | -3.4 |
February | 19.70 | -4.2 |
March | 19.90 | 2.67 |
April | 19.91 | 7.47 |
May | 19.89 | 13.73 |
June | 19.85 | 18.63 |
July | 19.64 | 22.03 |
August | 19.80 | 20.69 |
September | 19.77 | 16.55 |
October | 19.83 | 9.73 |
November | 19.80 | 6.03 |
December | 19.68 | -2.2 |
Annual Sum or Average | 19.79 | 9.05 |
Minimum of Months | 19.64 | -4.2 |
Maximum of Months | 19.91 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.34 | -3.4 |
February | 20.45 | -4.2 |
March | 21.09 | 2.67 |
April | 21.24 | 7.47 |
May | 21.42 | 13.73 |
June | 21.63 | 18.63 |
July | 21.54 | 22.03 |
August | 21.66 | 20.69 |
September | 21.49 | 16.55 |
October | 21.12 | 9.73 |
November | 20.83 | 6.03 |
December | 20.38 | -2.2 |
Annual Sum or Average | 21.10 | 9.05 |
Minimum of Months | 20.34 | -4.2 |
Maximum of Months | 21.66 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.58 | -3.4 |
February | 20.68 | -4.2 |
March | 21.19 | 2.67 |
April | 21.25 | 7.47 |
May | 21.32 | 13.73 |
June | 21.45 | 18.63 |
July | 21.32 | 22.03 |
August | 21.49 | 20.69 |
September | 21.38 | 16.55 |
October | 21.17 | 9.73 |
November | 20.99 | 6.03 |
December | 20.63 | -2.2 |
Annual Sum or Average | 21.12 | 9.05 |
Minimum of Months | 20.58 | -4.2 |
Maximum of Months | 21.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.61 | -3.4 |
February | 20.70 | -4.2 |
March | 21.19 | 2.67 |
April | 21.22 | 7.47 |
May | 21.26 | 13.73 |
June | 21.38 | 18.63 |
July | 21.25 | 22.03 |
August | 21.43 | 20.69 |
September | 21.34 | 16.55 |
October | 21.15 | 9.73 |
November | 20.98 | 6.03 |
December | 20.65 | -2.2 |
Annual Sum or Average | 21.10 | 9.05 |
Minimum of Months | 20.61 | -4.2 |
Maximum of Months | 21.43 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | -3.4 |
February | 20.80 | -4.2 |
March | 21.22 | 2.67 |
April | 21.37 | 7.47 |
May | 21.48 | 13.73 |
June | 21.64 | 18.63 |
July | 21.52 | 22.03 |
August | 21.62 | 20.69 |
September | 21.46 | 16.55 |
October | 21.26 | 9.73 |
November | 21.14 | 6.03 |
December | 20.82 | -2.2 |
Annual Sum or Average | 21.25 | 9.05 |
Minimum of Months | 20.70 | -4.2 |
Maximum of Months | 21.64 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.75 | -3.4 |
February | 20.85 | -4.2 |
March | 21.30 | 2.67 |
April | 21.48 | 7.47 |
May | 21.59 | 13.73 |
June | 21.76 | 18.63 |
July | 21.66 | 22.03 |
August | 21.75 | 20.69 |
September | 21.59 | 16.55 |
October | 21.37 | 9.73 |
November | 21.24 | 6.03 |
December | 20.88 | -2.2 |
Annual Sum or Average | 21.35 | 9.05 |
Minimum of Months | 20.75 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.62 | -3.4 |
February | 20.73 | -4.2 |
March | 21.21 | 2.67 |
April | 21.41 | 7.47 |
May | 21.53 | 13.73 |
June | 21.72 | 18.63 |
July | 21.60 | 22.03 |
August | 21.70 | 20.69 |
September | 21.53 | 16.55 |
October | 21.29 | 9.73 |
November | 21.15 | 6.03 |
December | 20.76 | -2.2 |
Annual Sum or Average | 21.27 | 9.05 |
Minimum of Months | 20.62 | -4.2 |
Maximum of Months | 21.72 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.91 | -3.4 |
February | 19.96 | -4.2 |
March | 20.59 | 2.67 |
April | 20.87 | 7.47 |
May | 21.29 | 13.73 |
June | 21.67 | 18.63 |
July | 21.70 | 22.03 |
August | 21.72 | 20.69 |
September | 21.38 | 16.55 |
October | 20.83 | 9.73 |
November | 20.48 | 6.03 |
December | 19.96 | -2.2 |
Annual Sum or Average | 20.87 | 9.05 |
Minimum of Months | 19.91 | -4.2 |
Maximum of Months | 21.72 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.53 | -3.4 |
February | 21.60 | -4.2 |
March | 21.84 | 2.67 |
April | 21.86 | 7.47 |
May | 21.85 | 13.73 |
June | 21.89 | 18.63 |
July | 21.77 | 22.03 |
August | 21.88 | 20.69 |
September | 21.84 | 16.55 |
October | 21.77 | 9.73 |
November | 21.72 | 6.03 |
December | 21.59 | -2.2 |
Annual Sum or Average | 21.76 | 9.05 |
Minimum of Months | 21.53 | -4.2 |
Maximum of Months | 21.89 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | -3.4 |
February | 21.43 | -4.2 |
March | 21.70 | 2.67 |
April | 21.76 | 7.47 |
May | 21.76 | 13.73 |
June | 21.82 | 18.63 |
July | 21.69 | 22.03 |
August | 21.80 | 20.69 |
September | 21.74 | 16.55 |
October | 21.65 | 9.73 |
November | 21.59 | 6.03 |
December | 21.43 | -2.2 |
Annual Sum or Average | 21.64 | 9.05 |
Minimum of Months | 21.35 | -4.2 |
Maximum of Months | 21.82 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.37 | -3.4 |
February | 21.45 | -4.2 |
March | 21.73 | 2.67 |
April | 21.81 | 7.47 |
May | 21.80 | 13.73 |
June | 21.87 | 18.63 |
July | 21.75 | 22.03 |
August | 21.85 | 20.69 |
September | 21.79 | 16.55 |
October | 21.70 | 9.73 |
November | 21.64 | 6.03 |
December | 21.46 | -2.2 |
Annual Sum or Average | 21.69 | 9.05 |
Minimum of Months | 21.37 | -4.2 |
Maximum of Months | 21.87 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.75 | -3.4 |
February | 19.88 | -4.2 |
March | 20.72 | 2.67 |
April | 21.19 | 7.47 |
May | 21.61 | 13.73 |
June | 21.89 | 18.63 |
July | 21.89 | 22.03 |
August | 21.90 | 20.69 |
September | 21.64 | 16.55 |
October | 21.01 | 9.73 |
November | 20.46 | 6.03 |
December | 19.78 | -2.2 |
Annual Sum or Average | 20.98 | 9.05 |
Minimum of Months | 19.75 | -4.2 |
Maximum of Months | 21.90 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -3.4 |
February | 20.76 | -4.2 |
March | 21.32 | 2.67 |
April | 21.58 | 7.47 |
May | 21.76 | 13.73 |
June | 21.93 | 18.63 |
July | 21.87 | 22.03 |
August | 21.92 | 20.69 |
September | 21.78 | 16.55 |
October | 21.41 | 9.73 |
November | 21.15 | 6.03 |
December | 20.71 | -2.2 |
Annual Sum or Average | 21.40 | 9.05 |
Minimum of Months | 20.63 | -4.2 |
Maximum of Months | 21.93 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.22 | -3.4 |
February | 20.28 | -4.2 |
March | 20.94 | 2.67 |
April | 21.12 | 7.47 |
May | 21.37 | 13.73 |
June | 21.59 | 18.63 |
July | 21.51 | 22.03 |
August | 21.61 | 20.69 |
September | 21.42 | 16.55 |
October | 21.01 | 9.73 |
November | 20.76 | 6.03 |
December | 20.28 | -2.2 |
Annual Sum or Average | 21.01 | 9.05 |
Minimum of Months | 20.22 | -4.2 |
Maximum of Months | 21.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | -3.4 |
February | 21.34 | -4.2 |
March | 21.69 | 2.67 |
April | 21.75 | 7.47 |
May | 21.78 | 13.73 |
June | 21.87 | 18.63 |
July | 21.77 | 22.03 |
August | 21.88 | 20.69 |
September | 21.80 | 16.55 |
October | 21.65 | 9.73 |
November | 21.57 | 6.03 |
December | 21.35 | -2.2 |
Annual Sum or Average | 21.65 | 9.05 |
Minimum of Months | 21.26 | -4.2 |
Maximum of Months | 21.88 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | -3.4 |
February | 19.49 | -4.2 |
March | 19.63 | 2.67 |
April | 19.58 | 7.47 |
May | 19.55 | 13.73 |
June | 19.51 | 18.63 |
July | 19.38 | 22.03 |
August | 19.49 | 20.69 |
September | 19.46 | 16.55 |
October | 19.52 | 9.73 |
November | 19.52 | 6.03 |
December | 19.45 | -2.2 |
Annual Sum or Average | 19.50 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.63 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | -3.4 |
February | 21.65 | -4.2 |
March | 21.88 | 2.67 |
April | 21.92 | 7.47 |
May | 21.91 | 13.73 |
June | 21.98 | 18.63 |
July | 21.89 | 22.03 |
August | 21.98 | 20.69 |
September | 21.93 | 16.55 |
October | 21.83 | 9.73 |
November | 21.79 | 6.03 |
December | 21.66 | -2.2 |
Annual Sum or Average | 21.83 | 9.05 |
Minimum of Months | 21.58 | -4.2 |
Maximum of Months | 21.98 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | -3.4 |
February | 21.57 | -4.2 |
March | 21.84 | 2.67 |
April | 21.89 | 7.47 |
May | 21.90 | 13.73 |
June | 21.97 | 18.63 |
July | 21.89 | 22.03 |
August | 21.97 | 20.69 |
September | 21.92 | 16.55 |
October | 21.80 | 9.73 |
November | 21.73 | 6.03 |
December | 21.57 | -2.2 |
Annual Sum or Average | 21.80 | 9.05 |
Minimum of Months | 21.49 | -4.2 |
Maximum of Months | 21.97 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.32 | -3.4 |
February | 20.36 | -4.2 |
March | 20.75 | 2.67 |
April | 20.77 | 7.47 |
May | 20.74 | 13.73 |
June | 20.82 | 18.63 |
July | 20.70 | 22.03 |
August | 20.86 | 20.69 |
September | 20.80 | 16.55 |
October | 20.69 | 9.73 |
November | 20.57 | 6.03 |
December | 20.33 | -2.2 |
Annual Sum or Average | 20.64 | 9.05 |
Minimum of Months | 20.32 | -4.2 |
Maximum of Months | 20.86 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.38 | -3.4 |
February | 20.47 | -4.2 |
March | 20.82 | 2.67 |
April | 20.96 | 7.47 |
May | 21.01 | 13.73 |
June | 21.15 | 18.63 |
July | 21.01 | 22.03 |
August | 21.11 | 20.69 |
September | 20.98 | 16.55 |
October | 20.83 | 9.73 |
November | 20.72 | 6.03 |
December | 20.47 | -2.2 |
Annual Sum or Average | 20.83 | 9.05 |
Minimum of Months | 20.38 | -4.2 |
Maximum of Months | 21.15 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.44 | -3.4 |
February | 20.54 | -4.2 |
March | 20.93 | 2.67 |
April | 21.10 | 7.47 |
May | 21.17 | 13.73 |
June | 21.32 | 18.63 |
July | 21.17 | 22.03 |
August | 21.28 | 20.69 |
September | 21.13 | 16.55 |
October | 20.97 | 9.73 |
November | 20.85 | 6.03 |
December | 20.56 | -2.2 |
Annual Sum or Average | 20.96 | 9.05 |
Minimum of Months | 20.44 | -4.2 |
Maximum of Months | 21.32 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.60 | -3.4 |
February | 19.67 | -4.2 |
March | 20.27 | 2.67 |
April | 20.78 | 7.47 |
May | 21.26 | 13.73 |
June | 21.64 | 18.63 |
July | 21.66 | 22.03 |
August | 21.62 | 20.69 |
September | 21.27 | 16.55 |
October | 20.53 | 9.73 |
November | 20.05 | 6.03 |
December | 19.62 | -2.2 |
Annual Sum or Average | 20.67 | 9.05 |
Minimum of Months | 19.60 | -4.2 |
Maximum of Months | 21.66 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.97 | -3.4 |
February | 21.04 | -4.2 |
March | 21.53 | 2.67 |
April | 21.74 | 7.47 |
May | 21.87 | 13.73 |
June | 22.03 | 18.63 |
July | 21.98 | 22.03 |
August | 22.03 | 20.69 |
September | 21.90 | 16.55 |
October | 21.63 | 9.73 |
November | 21.48 | 6.03 |
December | 21.09 | -2.2 |
Annual Sum or Average | 21.61 | 9.05 |
Minimum of Months | 20.97 | -4.2 |
Maximum of Months | 22.03 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | -3.4 |
February | 21.38 | -4.2 |
March | 21.75 | 2.67 |
April | 21.87 | 7.47 |
May | 21.92 | 13.73 |
June | 22.04 | 18.63 |
July | 21.99 | 22.03 |
August | 22.04 | 20.69 |
September | 21.96 | 16.55 |
October | 21.77 | 9.73 |
November | 21.66 | 6.03 |
December | 21.41 | -2.2 |
Annual Sum or Average | 21.76 | 9.05 |
Minimum of Months | 21.29 | -4.2 |
Maximum of Months | 22.04 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | -3.4 |
February | 19.42 | -4.2 |
March | 19.54 | 2.67 |
April | 19.51 | 7.47 |
May | 19.54 | 13.73 |
June | 19.54 | 18.63 |
July | 19.41 | 22.03 |
August | 19.53 | 20.69 |
September | 19.46 | 16.55 |
October | 19.46 | 9.73 |
November | 19.43 | 6.03 |
December | 19.39 | -2.2 |
Annual Sum or Average | 19.47 | 9.05 |
Minimum of Months | 19.39 | -4.2 |
Maximum of Months | 19.54 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.34 | -3.4 |
February | 22.37 | -4.2 |
March | 22.41 | 2.67 |
April | 22.39 | 7.47 |
May | 22.24 | 13.73 |
June | 22.17 | 18.63 |
July | 22.11 | 22.03 |
August | 22.14 | 20.69 |
September | 22.18 | 16.55 |
October | 22.31 | 9.73 |
November | 22.39 | 6.03 |
December | 22.36 | -2.2 |
Annual Sum or Average | 22.28 | 9.05 |
Minimum of Months | 22.11 | -4.2 |
Maximum of Months | 22.41 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.53 | -3.4 |
February | 20.57 | -4.2 |
March | 21.07 | 2.67 |
April | 21.23 | 7.47 |
May | 21.37 | 13.73 |
June | 21.47 | 18.63 |
July | 21.36 | 22.03 |
August | 21.47 | 20.69 |
September | 21.32 | 16.55 |
October | 21.14 | 9.73 |
November | 21.01 | 6.03 |
December | 20.59 | -2.2 |
Annual Sum or Average | 21.10 | 9.05 |
Minimum of Months | 20.53 | -4.2 |
Maximum of Months | 21.47 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.86 | -3.4 |
February | 19.94 | -4.2 |
March | 20.63 | 2.67 |
April | 21.07 | 7.47 |
May | 21.49 | 13.73 |
June | 21.85 | 18.63 |
July | 21.89 | 22.03 |
August | 21.87 | 20.69 |
September | 21.54 | 16.55 |
October | 20.92 | 9.73 |
November | 20.51 | 6.03 |
December | 19.96 | -2.2 |
Annual Sum or Average | 20.97 | 9.05 |
Minimum of Months | 19.86 | -4.2 |
Maximum of Months | 21.89 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.63 | -3.4 |
February | 20.67 | -4.2 |
March | 21.19 | 2.67 |
April | 21.36 | 7.47 |
May | 21.50 | 13.73 |
June | 21.61 | 18.63 |
July | 21.51 | 22.03 |
August | 21.61 | 20.69 |
September | 21.46 | 16.55 |
October | 21.27 | 9.73 |
November | 21.14 | 6.03 |
December | 20.70 | -2.2 |
Annual Sum or Average | 21.22 | 9.05 |
Minimum of Months | 20.63 | -4.2 |
Maximum of Months | 21.61 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | -3.4 |
February | 19.42 | -4.2 |
March | 19.71 | 2.67 |
April | 19.88 | 7.47 |
May | 20.26 | 13.73 |
June | 20.77 | 18.63 |
July | 20.94 | 22.03 |
August | 20.85 | 20.69 |
September | 20.31 | 16.55 |
October | 19.80 | 9.73 |
November | 19.55 | 6.03 |
December | 19.40 | -2.2 |
Annual Sum or Average | 20.03 | 9.05 |
Minimum of Months | 19.40 | -4.2 |
Maximum of Months | 20.94 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.75 | -3.4 |
February | 20.80 | -4.2 |
March | 21.32 | 2.67 |
April | 21.55 | 7.47 |
May | 21.74 | 13.73 |
June | 21.89 | 18.63 |
July | 21.85 | 22.03 |
August | 21.88 | 20.69 |
September | 21.72 | 16.55 |
October | 21.46 | 9.73 |
November | 21.29 | 6.03 |
December | 20.83 | -2.2 |
Annual Sum or Average | 21.43 | 9.05 |
Minimum of Months | 20.75 | -4.2 |
Maximum of Months | 21.89 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.81 | -3.4 |
February | 20.87 | -4.2 |
March | 21.38 | 2.67 |
April | 21.66 | 7.47 |
May | 21.85 | 13.73 |
June | 22.01 | 18.63 |
July | 21.98 | 22.03 |
August | 22.00 | 20.69 |
September | 21.85 | 16.55 |
October | 21.57 | 9.73 |
November | 21.38 | 6.03 |
December | 20.92 | -2.2 |
Annual Sum or Average | 21.53 | 9.05 |
Minimum of Months | 20.81 | -4.2 |
Maximum of Months | 22.01 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | -3.4 |
February | 19.40 | -4.2 |
March | 19.49 | 2.67 |
April | 19.43 | 7.47 |
May | 19.45 | 13.73 |
June | 19.48 | 18.63 |
July | 19.38 | 22.03 |
August | 19.48 | 20.69 |
September | 19.41 | 16.55 |
October | 19.40 | 9.73 |
November | 19.39 | 6.03 |
December | 19.38 | -2.2 |
Annual Sum or Average | 19.42 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.80 | -3.4 |
February | 24.78 | -4.2 |
March | 24.81 | 2.67 |
April | 25.37 | 7.47 |
May | 25.30 | 13.73 |
June | 25.08 | 18.63 |
July | 25.24 | 22.03 |
August | 24.96 | 20.69 |
September | 25.31 | 16.55 |
October | 25.35 | 9.73 |
November | 25.15 | 6.03 |
December | 24.97 | -2.2 |
Annual Sum or Average | 25.09 | 9.05 |
Minimum of Months | 24.78 | -4.2 |
Maximum of Months | 25.37 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.22 | -3.4 |
February | 20.33 | -4.2 |
March | 21.12 | 2.67 |
April | 21.59 | 7.47 |
May | 21.89 | 13.73 |
June | 22.06 | 18.63 |
July | 22.08 | 22.03 |
August | 22.07 | 20.69 |
September | 21.92 | 16.55 |
October | 21.50 | 9.73 |
November | 21.09 | 6.03 |
December | 20.32 | -2.2 |
Annual Sum or Average | 21.36 | 9.05 |
Minimum of Months | 20.22 | -4.2 |
Maximum of Months | 22.08 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.14 | -3.4 |
February | 20.23 | -4.2 |
March | 20.93 | 2.67 |
April | 21.33 | 7.47 |
May | 21.65 | 13.73 |
June | 21.91 | 18.63 |
July | 21.92 | 22.03 |
August | 21.92 | 20.69 |
September | 21.66 | 16.55 |
October | 21.20 | 9.73 |
November | 20.91 | 6.03 |
December | 20.26 | -2.2 |
Annual Sum or Average | 21.18 | 9.05 |
Minimum of Months | 20.14 | -4.2 |
Maximum of Months | 21.92 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.12 | -3.4 |
February | 20.24 | -4.2 |
March | 20.96 | 2.67 |
April | 21.34 | 7.47 |
May | 21.64 | 13.73 |
June | 21.91 | 18.63 |
July | 21.92 | 22.03 |
August | 21.92 | 20.69 |
September | 21.67 | 16.55 |
October | 21.20 | 9.73 |
November | 20.84 | 6.03 |
December | 20.22 | -2.2 |
Annual Sum or Average | 21.17 | 9.05 |
Minimum of Months | 20.12 | -4.2 |
Maximum of Months | 21.92 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | -3.4 |
February | 19.40 | -4.2 |
March | 19.49 | 2.67 |
April | 19.45 | 7.47 |
May | 19.47 | 13.73 |
June | 19.50 | 18.63 |
July | 19.40 | 22.03 |
August | 19.50 | 20.69 |
September | 19.43 | 16.55 |
October | 19.40 | 9.73 |
November | 19.40 | 6.03 |
December | 19.38 | -2.2 |
Annual Sum or Average | 19.43 | 9.05 |
Minimum of Months | 19.38 | -4.2 |
Maximum of Months | 19.50 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.49 | -3.4 |
February | 19.54 | -4.2 |
March | 19.83 | 2.67 |
April | 19.86 | 7.47 |
May | 19.89 | 13.73 |
June | 19.95 | 18.63 |
July | 19.86 | 22.03 |
August | 19.96 | 20.69 |
September | 19.87 | 16.55 |
October | 19.78 | 9.73 |
November | 19.60 | 6.03 |
December | 19.46 | -2.2 |
Annual Sum or Average | 19.76 | 9.05 |
Minimum of Months | 19.46 | -4.2 |
Maximum of Months | 19.96 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.55 | -3.4 |
February | 19.60 | -4.2 |
March | 19.86 | 2.67 |
April | 19.91 | 7.47 |
May | 19.89 | 13.73 |
June | 19.82 | 18.63 |
July | 19.65 | 22.03 |
August | 19.79 | 20.69 |
September | 19.71 | 16.55 |
October | 19.79 | 9.73 |
November | 19.71 | 6.03 |
December | 19.55 | -2.2 |
Annual Sum or Average | 19.74 | 9.05 |
Minimum of Months | 19.55 | -4.2 |
Maximum of Months | 19.91 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.43 | -3.4 |
February | 19.45 | -4.2 |
March | 19.57 | 2.67 |
April | 19.53 | 7.47 |
May | 19.52 | 13.73 |
June | 19.50 | 18.63 |
July | 19.39 | 22.03 |
August | 19.49 | 20.69 |
September | 19.44 | 16.55 |
October | 19.47 | 9.73 |
November | 19.47 | 6.03 |
December | 19.42 | -2.2 |
Annual Sum or Average | 19.47 | 9.05 |
Minimum of Months | 19.39 | -4.2 |
Maximum of Months | 19.57 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -3.4 |
February | 19.65 | -4.2 |
March | 19.92 | 2.67 |
April | 20.02 | 7.47 |
May | 20.08 | 13.73 |
June | 20.11 | 18.63 |
July | 19.98 | 22.03 |
August | 20.09 | 20.69 |
September | 19.99 | 16.55 |
October | 19.91 | 9.73 |
November | 19.81 | 6.03 |
December | 19.62 | -2.2 |
Annual Sum or Average | 19.90 | 9.05 |
Minimum of Months | 19.61 | -4.2 |
Maximum of Months | 20.11 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.91 | -3.4 |
February | 19.97 | -4.2 |
March | 20.56 | 2.67 |
April | 20.90 | 7.47 |
May | 21.23 | 13.73 |
June | 21.49 | 18.63 |
July | 21.45 | 22.03 |
August | 21.48 | 20.69 |
September | 21.20 | 16.55 |
October | 20.76 | 9.73 |
November | 20.43 | 6.03 |
December | 19.98 | -2.2 |
Annual Sum or Average | 20.78 | 9.05 |
Minimum of Months | 19.91 | -4.2 |
Maximum of Months | 21.49 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.68 | -3.4 |
February | 19.75 | -4.2 |
March | 20.09 | 2.67 |
April | 20.15 | 7.47 |
May | 20.13 | 13.73 |
June | 20.07 | 18.63 |
July | 19.86 | 22.03 |
August | 20.02 | 20.69 |
September | 19.94 | 16.55 |
October | 20.02 | 9.73 |
November | 19.91 | 6.03 |
December | 19.68 | -2.2 |
Annual Sum or Average | 19.94 | 9.05 |
Minimum of Months | 19.68 | -4.2 |
Maximum of Months | 20.15 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.70 | -3.4 |
February | 19.81 | -4.2 |
March | 20.57 | 2.67 |
April | 20.90 | 7.47 |
May | 21.26 | 13.73 |
June | 21.56 | 18.63 |
July | 21.57 | 22.03 |
August | 21.58 | 20.69 |
September | 21.30 | 16.55 |
October | 20.77 | 9.73 |
November | 20.29 | 6.03 |
December | 19.72 | -2.2 |
Annual Sum or Average | 20.76 | 9.05 |
Minimum of Months | 19.70 | -4.2 |
Maximum of Months | 21.58 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.61 | -3.4 |
February | 19.70 | -4.2 |
March | 20.45 | 2.67 |
April | 20.82 | 7.47 |
May | 21.27 | 13.73 |
June | 21.65 | 18.63 |
July | 21.70 | 22.03 |
August | 21.68 | 20.69 |
September | 21.35 | 16.55 |
October | 20.71 | 9.73 |
November | 20.15 | 6.03 |
December | 19.62 | -2.2 |
Annual Sum or Average | 20.73 | 9.05 |
Minimum of Months | 19.61 | -4.2 |
Maximum of Months | 21.70 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.73 | -3.4 |
February | 19.77 | -4.2 |
March | 20.18 | 2.67 |
April | 20.41 | 7.47 |
May | 20.60 | 13.73 |
June | 20.79 | 18.63 |
July | 20.77 | 22.03 |
August | 20.80 | 20.69 |
September | 20.56 | 16.55 |
October | 20.28 | 9.73 |
November | 20.09 | 6.03 |
December | 19.77 | -2.2 |
Annual Sum or Average | 20.31 | 9.05 |
Minimum of Months | 19.73 | -4.2 |
Maximum of Months | 20.80 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.60 | -3.4 |
February | 19.74 | -4.2 |
March | 20.50 | 2.67 |
April | 20.99 | 7.47 |
May | 21.44 | 13.73 |
June | 21.72 | 18.63 |
July | 21.76 | 22.03 |
August | 21.73 | 20.69 |
September | 21.44 | 16.55 |
October | 20.83 | 9.73 |
November | 20.28 | 6.03 |
December | 19.63 | -2.2 |
Annual Sum or Average | 20.81 | 9.05 |
Minimum of Months | 19.60 | -4.2 |
Maximum of Months | 21.76 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | -3.4 |
February | 19.39 | -4.2 |
March | 19.69 | 2.67 |
April | 19.99 | 7.47 |
May | 20.66 | 13.73 |
June | 21.38 | 18.63 |
July | 21.62 | 22.03 |
August | 21.44 | 20.69 |
September | 20.88 | 16.55 |
October | 19.90 | 9.73 |
November | 19.52 | 6.03 |
December | 19.37 | -2.2 |
Annual Sum or Average | 20.27 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 21.62 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.45 | -3.4 |
February | 19.49 | -4.2 |
March | 19.93 | 2.67 |
April | 20.24 | 7.47 |
May | 20.77 | 13.73 |
June | 21.37 | 18.63 |
July | 21.54 | 22.03 |
August | 21.45 | 20.69 |
September | 20.99 | 16.55 |
October | 20.17 | 9.73 |
November | 19.72 | 6.03 |
December | 19.45 | -2.2 |
Annual Sum or Average | 20.39 | 9.05 |
Minimum of Months | 19.45 | -4.2 |
Maximum of Months | 21.54 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | -3.4 |
February | 19.37 | -4.2 |
March | 19.71 | 2.67 |
April | 19.98 | 7.47 |
May | 20.70 | 13.73 |
June | 21.44 | 18.63 |
July | 21.67 | 22.03 |
August | 21.50 | 20.69 |
September | 20.89 | 16.55 |
October | 19.90 | 9.73 |
November | 19.53 | 6.03 |
December | 19.37 | -2.2 |
Annual Sum or Average | 20.29 | 9.05 |
Minimum of Months | 19.37 | -4.2 |
Maximum of Months | 21.67 | 22.03 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2018-10-19 19:10:48
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | -3.4 |
February | 19.54 | -4.2 |
March | 20.07 | 2.67 |
April | 20.37 | 7.47 |
May | 20.88 | 13.73 |
June | 21.44 | 18.63 |
July | 21.61 | 22.03 |
August | 21.54 | 20.69 |
September | 21.14 | 16.55 |
October | 20.34 | 9.73 |
November | 19.83 | 6.03 |
December | 19.48 | -2.2 |
Annual Sum or Average | 20.48 | 9.05 |
Minimum of Months | 19.48 | -4.2 |
Maximum of Months | 21.61 | 22.03 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2018-10-19 19:10:48
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.143548E+12 | 0.131442E+11 |
February | 0.133966E+12 | 0.121439E+11 |
March | 0.106919E+12 | 0.482063E+11 |
April | 0.679153E+11 | 0.596508E+11 |
May | 0.555526E+11 | 0.112804E+12 |
June | 0.448646E+11 | 0.179358E+12 |
July | 0.444558E+11 | 0.244481E+12 |
August | 0.446564E+11 | 0.214938E+12 |
September | 0.450268E+11 | 0.155781E+12 |
October | 0.602594E+11 | 0.825773E+11 |
November | 0.746775E+11 | 0.500308E+11 |
December | 0.128797E+12 | 0.170702E+11 |
Annual Sum or Average | 0.950638E+12 | 0.119018E+13 |
Minimum of Months | 0.444558E+11 | 0.121439E+11 |
Maximum of Months | 0.143548E+12 | 0.244481E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2018-10-19 19:10:48
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.825489E+11 | 0.000 |
February | 0.757403E+11 | 0.000 |
March | 0.512009E+11 | 0.124654E+11 |
April | 0.321241E+11 | 0.816806E+10 |
May | 0.301087E+11 | 0.585552E+11 |
June | 0.314234E+11 | 0.160819E+12 |
July | 0.345256E+11 | 0.231540E+12 |
August | 0.338764E+11 | 0.205378E+12 |
September | 0.301946E+11 | 0.117265E+12 |
October | 0.320700E+11 | 0.228069E+11 |
November | 0.361365E+11 | 0.762934E+10 |
December | 0.751764E+11 | 0.118022E+09 |
Annual Sum or Average | 0.545126E+12 | 0.824745E+12 |
Minimum of Months | 0.301087E+11 | 0.000 |
Maximum of Months | 0.825489E+11 | 0.231540E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2018-10-19 19:10:48
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.134520E+12 | 0.137115E+12 |
February | 0.122125E+12 | 0.130039E+12 |
March | 0.113662E+12 | 0.899679E+11 |
April | 0.807573E+11 | 0.571101E+11 |
May | 0.994098E+11 | 0.485848E+11 |
June | 0.136721E+12 | 0.436263E+11 |
July | 0.174599E+12 | 0.443729E+11 |
August | 0.160378E+12 | 0.434675E+11 |
September | 0.116774E+12 | 0.453470E+11 |
October | 0.821307E+11 | 0.578876E+11 |
November | 0.862984E+11 | 0.605008E+11 |
December | 0.121808E+12 | 0.124586E+12 |
Annual Sum or Average | 0.142918E+13 | 0.882605E+12 |
Minimum of Months | 0.807573E+11 | 0.434675E+11 |
Maximum of Months | 0.174599E+12 | 0.137115E+12 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:48
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.346670E+12 | 247882.127 | 30-JAN-07:10 | 35880.590 | 86960.562 | 16083.219 | 79857.888 | 0.000 | 8471.500 | 432.539 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.313556E+12 | 256249.062 | 06-FEB-07:10 | 35880.590 | 86960.562 | 16167.465 | 86053.105 | 0.000 | 8471.500 | 515.321 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.332738E+12 | 240087.066 | 14-MAR-13:30 | 35585.685 | 111201.830 | 22695.563 | 6352.254 | 64193.390 | 0.000 | 58.344 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.282162E+12 | 223917.833 | 26-APR-14:09 | 35585.685 | 111201.830 | 28353.674 | 16887.248 | 28430.547 | 0.000 | 58.493 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.310910E+12 | 247354.241 | 10-MAY-14:00 | 35585.685 | 111201.830 | 25060.752 | 5460.677 | 69990.361 | 0.000 | 54.935 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.344461E+12 | 286963.945 | 27-JUN-12:00 | 35585.685 | 111201.830 | 27522.640 | 5334.232 | 107270.379 | 0.000 | 49.179 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.377660E+12 | 290067.254 | 20-JUL-13:50 | 35585.685 | 111201.830 | 29543.116 | 4756.901 | 108932.349 | 0.000 | 47.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.377264E+12 | 279299.639 | 18-AUG-14:39 | 35585.685 | 111201.830 | 31509.005 | 4380.304 | 96576.554 | 0.000 | 46.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.318894E+12 | 262320.819 | 15-SEP-12:09 | 35585.685 | 111201.830 | 25631.012 | 5943.540 | 83906.762 | 0.000 | 51.989 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.292209E+12 | 230929.356 | 11-OCT-15:09 | 35585.685 | 111201.830 | 25313.585 | 5658.329 | 53114.713 | 0.000 | 55.214 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.292753E+12 | 227721.156 | 24-NOV-07:10 | 35880.590 | 86960.562 | 15835.604 | 67626.894 | 1302.280 | 8471.500 | 298.223 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.330981E+12 | 260038.902 | 11-DEC-07:10 | 35880.590 | 86960.562 | 16066.865 | 90185.428 | 0.000 | 8471.500 | 570.335 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.392026E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.282162E+12 | 223917.833 | 35585.685 | 86960.562 | 15835.604 | 4380.304 | 0.000 | 0.000 | 46.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.377660E+12 | 290067.254 | 35880.590 | 111201.830 | 31509.005 | 90185.428 | 108932.349 | 8471.500 | 570.335 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:48
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.199322E+12 | 147082.42 | 02-JAN-16:30 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.180768E+12 | 147082.42 | 01-FEB-16:40 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.208877E+12 | 147082.42 | 01-MAR-17:49 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.193038E+12 | 146934.97 | 03-APR-08:09 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.204035E+12 | 146934.97 | 11-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.201051E+12 | 146934.97 | 14-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.195981E+12 | 146934.97 | 13-JUL-08:09 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.208844E+12 | 146934.97 | 02-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.193050E+12 | 147033.27 | 27-SEP-16:00 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.199284E+12 | 147082.42 | 19-OCT-16:30 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.194786E+12 | 147082.42 | 01-NOV-16:30 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.196093E+12 | 147082.42 | 01-DEC-16:10 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.237513E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.180768E+12 | 146934.97 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.208877E+12 | 147082.42 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:48
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.451680E+11 | 0.00 | 0.121897E+11 | 0.154153E+12 | 0.00 | 0.311369E+11 | 0.638152E+09 | 0.615900E+11 | 0.369990E+10 | 0.00 | 0.380934E+11 | 0.00 | 0.00 | 0.00 |
February | 0.410424E+11 | 0.00 | 0.100495E+11 | 0.139726E+12 | 0.00 | 0.285193E+11 | 0.612817E+09 | 0.565480E+11 | 0.342575E+10 | 0.00 | 0.336317E+11 | 0.00 | 0.00 | 0.00 |
March | 0.484870E+11 | 0.00 | 0.980071E+10 | 0.160390E+12 | 0.00 | 0.342520E+11 | 0.397941E+09 | 0.381899E+11 | 0.160260E+11 | 0.00 | 0.251942E+11 | 0.00 | 0.00 | 0.00 |
April | 0.437251E+11 | 0.00 | 0.814530E+10 | 0.149313E+12 | 0.00 | 0.335314E+11 | 0.221858E+09 | 0.208984E+11 | 0.179833E+11 | 0.00 | 0.834420E+10 | 0.00 | 0.00 | 0.00 |
May | 0.467629E+11 | 0.00 | 0.728207E+10 | 0.157272E+12 | 0.00 | 0.353542E+11 | 0.183099E+09 | 0.155283E+11 | 0.444139E+11 | 0.00 | 0.411346E+10 | 0.00 | 0.00 | 0.00 |
June | 0.465090E+11 | 0.00 | 0.653331E+10 | 0.154542E+12 | 0.00 | 0.364741E+11 | 0.155791E+09 | 0.128906E+11 | 0.869864E+11 | 0.00 | 0.369723E+09 | 0.00 | 0.00 | 0.00 |
July | 0.439386E+11 | 0.00 | 0.692598E+10 | 0.152043E+12 | 0.00 | 0.369437E+11 | 0.153680E+09 | 0.154553E+11 | 0.122200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.484536E+11 | 0.00 | 0.788954E+10 | 0.160390E+12 | 0.00 | 0.383083E+11 | 0.153297E+09 | 0.142113E+11 | 0.107858E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437375E+11 | 0.00 | 0.890773E+10 | 0.149313E+12 | 0.00 | 0.340037E+11 | 0.162336E+09 | 0.130892E+11 | 0.696407E+11 | 0.00 | 39989458.37 | 0.00 | 0.00 | 0.00 |
October | 0.451304E+11 | 0.00 | 0.105784E+11 | 0.154153E+12 | 0.00 | 0.335537E+11 | 0.216207E+09 | 0.174410E+11 | 0.275585E+11 | 0.00 | 0.357753E+10 | 0.00 | 0.00 | 0.00 |
November | 0.443709E+11 | 0.00 | 0.114288E+11 | 0.150416E+12 | 0.00 | 0.312868E+11 | 0.239097E+09 | 0.285719E+11 | 0.154497E+11 | 0.00 | 0.109901E+11 | 0.00 | 0.00 | 0.00 |
December | 0.440506E+11 | 0.00 | 0.125099E+11 | 0.152043E+12 | 0.00 | 0.309877E+11 | 0.569654E+09 | 0.572986E+11 | 0.480491E+10 | 0.00 | 0.287165E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541376E+12 | 0.00 | 0.112241E+12 | 0.183375E+13 | 0.00 | 0.404352E+12 | 0.370393E+10 | 0.351712E+12 | 0.520047E+12 | 0.00 | 0.153071E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.410424E+11 | 0.00 | 0.653331E+10 | 0.139726E+12 | 0.00 | 0.285193E+11 | 0.153297E+09 | 0.128906E+11 | 0.342575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.484870E+11 | 0.00 | 0.125099E+11 | 0.160390E+12 | 0.00 | 0.383083E+11 | 0.638152E+09 | 0.615900E+11 | 0.122200E+12 | 0.00 | 0.380934E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:48
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.137115E+12 | 0.00 | 0.220209E+11 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.130039E+12 | 0.00 | 0.200023E+11 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.899679E+11 | 0.00 | 0.222098E+11 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.571101E+11 | 0.00 | 0.209595E+11 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.485848E+11 | 0.00 | 0.212549E+11 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.436263E+11 | 0.00 | 0.200683E+11 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.443729E+11 | 0.00 | 0.203412E+11 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.434675E+11 | 0.00 | 0.201711E+11 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.453470E+11 | 0.00 | 0.196921E+11 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.578876E+11 | 0.00 | 0.206813E+11 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.605008E+11 | 0.00 | 0.205028E+11 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.124586E+12 | 0.00 | 0.216060E+11 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.882605E+12 | 0.00 | 0.249510E+12 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.434675E+11 | 0.00 | 0.196921E+11 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.137115E+12 | 0.00 | 0.222098E+11 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:48
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35880.59 | 02-JAN-07:10 | 0.00 | 8471.50 | 01-JAN-06:10 | 111201.83 | 02-JAN-09:09 | 0.00 | 21109.46 | 06-JAN-14:00 | 559.65 | 10-JAN-06:10 | 80579.25 | 28-JAN-07:10 |
February | 35880.59 | 01-FEB-07:10 | 0.00 | 8471.50 | 01-FEB-06:10 | 111201.83 | 01-FEB-09:09 | 0.00 | 23523.60 | 28-FEB-15:30 | 570.33 | 06-FEB-06:10 | 86053.11 | 06-FEB-07:10 |
March | 35880.59 | 01-MAR-07:10 | 0.00 | 8471.50 | 01-MAR-06:10 | 111201.83 | 01-MAR-09:09 | 0.00 | 26563.83 | 08-MAR-15:20 | 570.33 | 07-MAR-06:10 | 79232.61 | 04-MAR-07:10 |
April | 35880.59 | 03-APR-06:10 | 0.00 | 8471.50 | 01-APR-05:10 | 111201.83 | 03-APR-08:09 | 0.00 | 29633.17 | 06-APR-14:39 | 331.36 | 17-APR-05:10 | 65715.69 | 17-APR-06:10 |
May | 35880.59 | 12-MAY-06:10 | 0.00 | 8471.50 | 01-MAY-05:10 | 111201.83 | 01-MAY-08:09 | 0.00 | 28754.01 | 04-MAY-15:30 | 199.06 | 20-MAY-06:10 | 41445.46 | 08-MAY-06:10 |
June | 35831.44 | 13-JUN-06:10 | 0.00 | 8471.50 | 01-JUN-19:49 | 111201.83 | 01-JUN-08:09 | 0.00 | 28896.89 | 20-JUN-15:00 | 175.53 | 03-JUN-06:10 | 34946.59 | 17-JUN-06:10 |
July | 35880.59 | 21-JUL-06:10 | 0.00 | 8471.50 | 01-JUL-19:00 | 111201.83 | 03-JUL-08:09 | 0.00 | 31292.79 | 21-JUL-13:39 | 156.62 | 08-JUL-06:10 | 35696.04 | 29-JUL-06:10 |
August | 35880.59 | 21-AUG-06:10 | 0.00 | 8471.50 | 01-AUG-19:40 | 111201.83 | 01-AUG-08:09 | 0.00 | 32544.17 | 09-AUG-15:30 | 167.96 | 12-AUG-06:10 | 34977.29 | 26-AUG-06:10 |
September | 35880.59 | 01-SEP-06:10 | 0.00 | 8471.50 | 01-SEP-05:10 | 111201.83 | 01-SEP-08:09 | 0.00 | 30573.98 | 21-SEP-15:09 | 204.96 | 30-SEP-06:10 | 40492.33 | 30-SEP-06:10 |
October | 35880.59 | 02-OCT-06:10 | 0.00 | 8471.50 | 01-OCT-05:10 | 111201.83 | 02-OCT-08:09 | 0.00 | 30188.18 | 17-OCT-15:30 | 283.15 | 17-OCT-05:10 | 64384.26 | 30-OCT-06:10 |
November | 35880.59 | 01-NOV-06:10 | 0.00 | 8471.50 | 01-NOV-05:10 | 111201.83 | 01-NOV-08:09 | 0.00 | 28474.41 | 03-NOV-14:50 | 323.30 | 24-NOV-06:10 | 75075.86 | 25-NOV-07:10 |
December | 35880.59 | 01-DEC-07:10 | 0.00 | 8471.50 | 01-DEC-06:10 | 111201.83 | 01-DEC-09:09 | 0.00 | 19776.24 | 15-DEC-17:00 | 570.33 | 11-DEC-06:10 | 90185.43 | 11-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 35831.44 | 0.00 | 8471.50 | 111201.83 | 0.00 | 19776.24 | 156.62 | 34946.59 | ||||||
Maximum of Months | 35880.59 | 0.00 | 8471.50 | 111201.83 | 0.00 | 32544.17 | 570.33 | 90185.43 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:48
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.346670E+12 | 247882.127 | 30-JAN-07:10 | 35880.590 | 86960.562 | 16083.219 | 79857.888 | 0.000 | 8471.500 | 432.539 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.313556E+12 | 256249.062 | 06-FEB-07:10 | 35880.590 | 86960.562 | 16167.465 | 86053.105 | 0.000 | 8471.500 | 515.321 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.332738E+12 | 240087.066 | 14-MAR-13:30 | 35585.685 | 111201.830 | 22695.563 | 6352.254 | 64193.390 | 0.000 | 58.344 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.282162E+12 | 223917.833 | 26-APR-14:09 | 35585.685 | 111201.830 | 28353.674 | 16887.248 | 28430.547 | 0.000 | 58.493 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.310910E+12 | 247354.241 | 10-MAY-14:00 | 35585.685 | 111201.830 | 25060.752 | 5460.677 | 69990.361 | 0.000 | 54.935 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.344461E+12 | 286963.945 | 27-JUN-12:00 | 35585.685 | 111201.830 | 27522.640 | 5334.232 | 107270.379 | 0.000 | 49.179 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.377660E+12 | 290067.254 | 20-JUL-13:50 | 35585.685 | 111201.830 | 29543.116 | 4756.901 | 108932.349 | 0.000 | 47.372 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.377264E+12 | 279299.639 | 18-AUG-14:39 | 35585.685 | 111201.830 | 31509.005 | 4380.304 | 96576.554 | 0.000 | 46.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.318894E+12 | 262320.819 | 15-SEP-12:09 | 35585.685 | 111201.830 | 25631.012 | 5943.540 | 83906.762 | 0.000 | 51.989 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.292209E+12 | 230929.356 | 11-OCT-15:09 | 35585.685 | 111201.830 | 25313.585 | 5658.329 | 53114.713 | 0.000 | 55.214 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.292753E+12 | 227721.156 | 24-NOV-07:10 | 35880.590 | 86960.562 | 15835.604 | 67626.894 | 1302.280 | 8471.500 | 298.223 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.330981E+12 | 260038.902 | 11-DEC-07:10 | 35880.590 | 86960.562 | 16066.865 | 90185.428 | 0.000 | 8471.500 | 570.335 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.392026E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.282162E+12 | 223917.833 | 35585.685 | 86960.562 | 15835.604 | 4380.304 | 0.000 | 0.000 | 46.260 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.377660E+12 | 290067.254 | 35880.590 | 111201.830 | 31509.005 | 90185.428 | 108932.349 | 8471.500 | 570.335 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:48
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.174998E+12 | 144228.801 | 04-JAN-06:00 | 0.000 | 9905.768 | 0.000 | 134323.033 | 7514.610 | 7514.610 | 126808.423 |
February | 0.164413E+12 | 167011.199 | 06-FEB-07:19 | 0.000 | 9905.768 | 0.000 | 157105.430 | 7514.610 | 7514.610 | 149590.820 |
March | 0.128567E+12 | 151311.718 | 07-MAR-06:30 | 0.000 | 9905.768 | 0.000 | 141405.950 | 7514.610 | 7514.610 | 133891.340 |
April | 0.934394E+11 | 98716.499 | 01-APR-06:10 | 0.000 | 4952.884 | 0.000 | 93763.615 | 7514.610 | 7514.610 | 86249.005 |
May | 0.859655E+11 | 71838.094 | 01-MAY-05:10 | 0.000 | 9905.768 | 0.000 | 61932.326 | 7514.610 | 7514.610 | 54417.716 |
June | 0.794995E+11 | 63228.985 | 03-JUN-06:10 | 0.000 | 4952.884 | 0.000 | 58276.101 | 7514.610 | 7514.610 | 50761.491 |
July | 0.804048E+11 | 56895.002 | 08-JUL-06:10 | 0.000 | 4952.884 | 0.000 | 51942.118 | 7514.610 | 7514.610 | 44427.508 |
August | 0.800282E+11 | 60666.781 | 12-AUG-06:10 | 0.000 | 4952.884 | 0.000 | 55713.897 | 7514.610 | 7514.610 | 48199.287 |
September | 0.804089E+11 | 72801.804 | 30-SEP-06:10 | 0.000 | 4952.884 | 0.000 | 67848.920 | 7514.610 | 7514.610 | 60334.310 |
October | 0.944309E+11 | 86381.480 | 17-OCT-05:10 | 0.000 | 9905.768 | 0.000 | 76475.712 | 7514.610 | 7514.610 | 68961.102 |
November | 0.964518E+11 | 95403.038 | 24-NOV-06:10 | 0.000 | 9905.768 | 0.000 | 85497.270 | 7514.610 | 7514.610 | 77982.660 |
December | 0.161882E+12 | 164130.749 | 11-DEC-07:19 | 0.000 | 9905.768 | 0.000 | 154224.981 | 7514.610 | 7514.610 | 146710.371 |
Annual Sum or Average | 0.132049E+13 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.794995E+11 | 56895.002 | 0.000 | 4952.884 | 0.000 | 51942.118 | 7514.610 | 7514.610 | 44427.508 | |
Maximum of Months | 0.174998E+12 | 167011.199 | 0.000 | 9905.768 | 0.000 | 157105.430 | 7514.610 | 7514.610 | 149590.820 |