Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09
Tabular Output Report in Format: HTML
Building: OutPatient HealthCare
Environment: Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2018-10-19 19:10:45
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 5301.93 | 1393.78 | 1393.78 |
Net Site Energy | 5301.93 | 1393.78 | 1393.78 |
Total Source Energy | 14938.33 | 3927.00 | 3927.00 |
Net Source Energy | 14938.33 | 3927.00 | 3927.00 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 461.81 | 453.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 558.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 475.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 427.26 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 247.54 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 4412.40 | 889.53 | 0.00 | 0.00 | 0.00 | 637.78 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 453.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 461.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 558.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 541.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 112.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 434.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 2.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 427.26 | 0.00 | 0.00 | 0.00 | 0.00 | 158.94 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 247.54 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 506.04 | 184.32 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1159.93 | 233.84 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 506.04 | 184.32 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1159.93 | 233.84 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 4412.40 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 4412.40 | 100.00 |
Total On-Site and Utility Electric Sources | 4412.40 | 100.00 |
Total Electricity End Uses | 4412.40 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 637.78 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 637.78 | 100.00 |
Total Water End Uses | 637.78 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 8.33 |
Time Setpoint Not Met During Occupied Cooling | 2605.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6629.50 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09 |
RunPeriod | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 6.9965 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 17.8681 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 17.8681 | 5734.7436 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 9.6875 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 24.3264 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 9.6875 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 8.5250 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 6.7813 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 13.2396 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 9.6875 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 11.9479 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 10.5486 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 6.7813 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 6.7813 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 11.9479 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 8.5250 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 8.5250 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 8.5250 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 8.5250 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.363 | 0.384 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.30 | 0.269 | 0.283 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_0.48_SHGC_0.40 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 2.653 | 0.426 | 0.308 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_0.48_SHGC_0.40 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.653 | 0.426 | 0.308 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_0.48_SHGC_0.40 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 2.653 | 0.426 | 0.308 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_0.48_SHGC_0.40 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 2.653 | 0.426 | 0.308 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_0.48_SHGC_0.40 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.653 | 0.426 | 0.308 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_0.48_SHGC_0.40 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.653 | 0.426 | 0.308 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_0.48_SHGC_0.40 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.653 | 0.426 | 0.308 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_0.48_SHGC_0.40 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.653 | 0.426 | 0.308 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_0.48_SHGC_0.40 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.653 | 0.426 | 0.308 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_0.48_SHGC_0.40 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.653 | 0.426 | 0.308 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_0.48_SHGC_0.40 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.653 | 0.426 | 0.308 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_0.48_SHGC_0.40 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.653 | 0.426 | 0.308 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_0.48_SHGC_0.40 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_0.48_SHGC_0.40 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.653 | 0.426 | 0.308 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_0.48_SHGC_0.40 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.653 | 0.426 | 0.308 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 2.653 | 0.426 | 0.308 | ||||||||||||
North Total or Average | 97.22 | 2.653 | 0.426 | 0.308 | ||||||||||||
Non-North Total or Average | 211.08 | 2.653 | 0.426 | 0.308 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BA05F7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E02487 |
F67E1F | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FE5A3C |
7EB6E7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E85BB5 |
D18914 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | C114C1 |
D4B39B | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | E326E4 |
D2D3BC | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
C528DA | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
EFD3F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 28B002 |
62B5AF | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 997723 |
71E924 | SWINGING DOOR_CON | 2.839 | 2.839 | 2.97 | 8E5BB9 |
3C44F9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
49526E | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
865AE8 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 859BC1 |
5E66D1 | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 529072 |
E14DAE | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | D95F04 |
84A1D5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 3330D8 |
9CB8E5 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
E4A528 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 88E360 |
24BAF7 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FB3814 |
19E57D | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | FCD12D |
EDE769 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 5507DC |
1C9872 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 2E2D0C |
F402E9 | SWINGING DOOR_CON | 2.839 | 2.839 | 1.95 | 270BCE |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 86607.51 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 134610.03 | 107507.01 | 27103.02 | 0.80 | 3.40 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 215170.34 | 171846.92 | 43323.42 | 0.80 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 128549.7 | 2.82 | 9.63 | N/A | 11.13 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 205483.0 | 2.82 | 9.63 | N/A | 11.13 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 1653.18 | 1638.40 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 132.56 | 131.37 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 4444.23 | 3030.60 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1221.21 | 1210.30 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1523.80 | 1510.18 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 381.05 | 259.85 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 358.54 | 355.34 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 660.20 | 450.20 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 4099.30 | 2795.38 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 180.95 | 123.39 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 258.39 | 176.20 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 304.21 | 207.44 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 4123.00 | 2811.55 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 550.80 | 375.60 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1033.24 | 1024.00 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3347.49 | 2282.71 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 810.55 | 552.73 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1677.85 | 1144.16 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 634.31 | 628.64 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 2047.13 | 1395.98 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 346.01 | 235.95 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 5051.39 | 3444.63 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1033.24 | 1024.00 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 823.07 | 561.27 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 968.06 | 660.14 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 123.26 | 84.05 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 1106.06 | 754.24 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1033.24 | 1024.00 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 1204.99 | 821.70 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13647.75 | 13525.72 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14259.85 | 14132.34 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 18554.94 | 18389.02 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1239.89 | 1228.80 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 967.81 | 659.97 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2169.80 | 2150.40 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3880.38 | 3845.69 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1033.24 | 1024.00 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 8179.80 | 8106.66 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 2532.15 | 1726.72 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 252.01 | 171.85 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 7172.26 | 7108.13 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 420.25 | 286.58 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 182.17 | 154.25 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2410.89 | 2389.33 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1071.51 | 1061.92 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 3444.13 | 3413.33 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 3555.61 | 3523.82 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1065.45 | 726.55 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 576.60 | 393.20 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 4454.27 | 4414.44 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 837.55 | 815.37 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1343.65 | 1331.64 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 88.78 | 75.84 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 1307.92 | 1296.23 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 355.94 | 352.76 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2156.50 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1204.13 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 124.07 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3993.71 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6459.82 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8867.31 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 1016.70 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4408.41 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2607.13 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8940.65 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3196.48 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4470.33 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 461.67 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 285.32 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 300.37 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 272.91 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 288.36 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 287.03 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 539.07 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 223.60 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 496.89 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 596.27 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2309.67 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 709.77 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 4278.26 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 852.90 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 2370.63 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 570.21 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 601.89 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 139.13 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 298.14 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 357.77 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 685.89 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 2974.15 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1173.25 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1015.98 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 5590.19 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 144.42 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1341.24 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 302.64 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 576.30 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 388.55 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2323.07 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 3612.39 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1970.82 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1361.64 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 8371.48 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 3030.15 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1015.98 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 16375.42 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6327.51 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1580.42 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 748.98 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 389.91 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 5268.28 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7537.31 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4889.70 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 770.70 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 2871.46 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 3832.07 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2386.27 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 3880.70 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1858.98 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 48125.18 | 43715.07 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 48125.18 | 43715.07 | - |
AHU-2_HEATC | Coil:Heating:Water | 78323.46 | 71043.51 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.13 | 18570.80 | 2283.73 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 13.00 | 29402.19 | 2261.98 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.0019 | 474.53 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.00 | 0.00 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 128549.68 | 2.82 | 9.63 | 11.13 | 7.6336 | 3.16 | 10.80 | 5.6159 | 3.42 | 11.65 | 3.4918 | 3.53 | 12.03 | 1.5944 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 205483.03 | 2.82 | 9.63 | 11.13 | 12.2021 | 3.16 | 10.80 | 8.9769 | 3.42 | 11.65 | 5.5816 | 3.53 | 12.03 | 2.5486 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 716.97 | 716.97 | 0.065 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 1 CAFE | 4029.05 | 4029.05 | 0.365 | 0.365 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 1 CLEAN | 554.21 | 554.21 | 0.050 | 0.050 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.60 | 0.00543 |
FLOOR 1 CLEAN WORK | 691.52 | 691.52 | 0.063 | 0.063 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 27.86 | 0.00543 |
FLOOR 1 DICTATION | 345.93 | 345.93 | 0.031 | 0.031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29 | 0.00543 |
FLOOR 1 DRESSING ROOM | 207.39 | 207.39 | 0.019 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 1 HUMID | 169.23 | 169.23 | 0.015 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 IT ROOM | 276.17 | 276.17 | 0.025 | 0.025 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.46 | 0.00543 |
FLOOR 1 LOBBY | 3742.77 | 3742.77 | 0.339 | 0.339 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 31.33 | 0.00543 |
FLOOR 1 LOCKER ROOM | 3038.45 | 3038.45 | 0.275 | 0.275 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 1 LOUNGE | 1522.97 | 1522.97 | 0.138 | 0.138 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 1 MRI CONTROL ROOM | 1858.10 | 1858.10 | 0.168 | 0.168 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 32.22 | 0.00543 |
FLOOR 1 MRI ROOM | 4535.41 | 4535.41 | 0.411 | 0.415 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 30.59 | 0.00543 |
FLOOR 1 NOURISHMENT | 747.05 | 747.05 | 0.068 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29 | 0.00543 |
FLOOR 1 NURSE STATION | 1003.89 | 1003.89 | 0.091 | 0.091 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 25.29 | 0.00543 |
FLOOR 1 OFFICE | 1093.91 | 1093.91 | 0.099 | 0.099 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76 | 0.00543 |
FLOOR 1 OPERATING ROOM 1 | 6696.63 | 6696.63 | 0.935 | 0.935 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 29.39 | 0.00543 |
FLOOR 1 OPERATING ROOM 2 | 6996.95 | 6996.95 | 0.977 | 0.977 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.60 | 0.00543 |
FLOOR 1 OPERATING ROOM 3 | 5778.48 | 5778.48 | 0.763 | 0.763 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:20:00 | 21.27 | 0.00543 |
FLOOR 1 PACU | 519.23 | 519.23 | 0.047 | 0.051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:10:00 | 26.18 | 0.00543 |
FLOOR 1 PRE-OP ROOM 1 | 602.17 | 602.17 | 0.055 | 0.089 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 31.33 | 0.00543 |
FLOOR 1 PRE-OP ROOM 2 | 1066.31 | 1066.31 | 0.097 | 0.160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.35 | 0.00543 |
FLOOR 1 PROCEDURE ROOM | 1750.26 | 1750.26 | 0.159 | 0.336 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 1 RECEPTION | 2297.89 | 2297.89 | 0.208 | 0.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.78 | 0.00543 |
FLOOR 1 RECOVERY ROOM | 3741.31 | 3741.31 | 0.339 | 0.339 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 1 SCHEDULING | 381.52 | 381.52 | 0.035 | 0.035 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90 | 0.00543 |
FLOOR 1 SOIL | 549.87 | 549.87 | 0.050 | 0.099 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 27.02 | 0.00543 |
FLOOR 1 SOIL HOLD | 231.72 | 231.72 | 0.021 | 0.044 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.46 | 0.00543 |
FLOOR 1 SOIL WORK | 737.99 | 737.99 | 0.067 | 0.142 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.44 | 0.00543 |
FLOOR 1 STEP DOWN | 2338.63 | 2338.63 | 0.212 | 0.212 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 33.31 | 0.00543 |
FLOOR 2 CONFERENCE | 2903.74 | 2903.74 | 0.311 | 0.311 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 2 DICTATION | 249.66 | 249.66 | 0.026 | 0.026 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM 1 | 3060.74 | 3060.74 | 0.327 | 0.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.83 | 0.00543 |
FLOOR 2 EXAM 2 | 2524.73 | 2524.73 | 0.270 | 0.270 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.78 | 0.00543 |
FLOOR 2 EXAM 3 | 3465.65 | 3465.65 | 0.371 | 0.371 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 33.78 | 0.00543 |
FLOOR 2 EXAM 4 | 620.93 | 620.93 | 0.066 | 0.066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 2 EXAM 5 | 2497.15 | 2497.15 | 0.267 | 0.267 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.44 | 0.00543 |
FLOOR 2 EXAM 6 | 1084.03 | 1084.03 | 0.116 | 0.116 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 2 EXAM 7 | 3223.03 | 3223.03 | 0.345 | 0.374 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.90 | 0.00543 |
FLOOR 2 EXAM 8 | 1343.37 | 1343.37 | 0.144 | 0.144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 2 EXAM 9 | 1730.68 | 1730.68 | 0.185 | 0.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75 | 0.00543 |
FLOOR 2 LOUNGE | 401.33 | 401.33 | 0.043 | 0.043 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.89 | 0.00543 |
FLOOR 2 NURSE STATION 1 | 645.06 | 645.06 | 0.069 | 0.069 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.89 | 0.00543 |
FLOOR 2 NURSE STATION 2 | 786.38 | 786.38 | 0.084 | 0.084 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.89 | 0.00543 |
FLOOR 2 OFFICE | 3196.20 | 3196.20 | 0.342 | 0.342 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.44 | 0.00543 |
FLOOR 2 RECEPTION | 5786.70 | 5786.70 | 0.619 | 0.619 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 32.62 | 0.00543 |
FLOOR 2 SCHEDULING 1 | 938.25 | 938.25 | 0.100 | 0.100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:30:00 | 24.35 | 0.00543 |
FLOOR 2 SCHEDULING 2 | 1027.10 | 1027.10 | 0.110 | 0.110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.89 | 0.00543 |
FLOOR 2 WORK | 4630.54 | 4630.54 | 0.495 | 0.495 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.46 | 0.00543 |
FLOOR 2 X-RAY | 9430.82 | 9430.82 | 1.009 | 1.009 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 3 DRESSING ROOM | 195.10 | 195.10 | 0.021 | 0.021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90 | 0.00543 |
FLOOR 3 HUMID | 488.88 | 488.88 | 0.052 | 0.052 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90 | 0.00543 |
FLOOR 3 LOCKER | 759.39 | 759.39 | 0.081 | 0.081 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90 | 0.00543 |
FLOOR 3 LOUNGE | 4540.01 | 4540.01 | 0.486 | 0.486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90 | 0.00543 |
FLOOR 3 OFFICE | 11311.95 | 11311.95 | 1.210 | 1.210 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90 | 0.00543 |
FLOOR 3 PHYSICAL THERAPY 1 | 9275.53 | 9275.53 | 0.992 | 0.992 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
FLOOR 3 PHYSICAL THERAPY 2 | 2979.62 | 2979.62 | 0.319 | 0.319 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90 | 0.00543 |
FLOOR 3 TREATMENT | 2542.11 | 2542.11 | 0.272 | 0.272 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90 | 0.00543 |
FLOOR 3 WORK | 3734.28 | 3734.28 | 0.399 | 0.399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 27.86 | 0.00543 |
FLOOR 1 BIO HAZ | 81.04 | 81.04 | 0.007 | 0.007 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 ELECTRICAL ROOM | 599.40 | 599.40 | 0.054 | 0.054 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:10:00 | 30.74 | 0.00543 |
FLOOR 1 ELEVATOR PUMP ROOM | 3721.80 | 3721.80 | 0.337 | 0.337 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 31.58 | 0.00543 |
FLOOR 1 IT HALL | 239.47 | 239.47 | 0.021 | 0.021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 LOBBY HALL | 517.38 | 517.38 | 0.045 | 0.045 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 LOBBY TOILET | 434.21 | 434.21 | 0.039 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 1 LOCKER ROOM HALL | 755.89 | 755.89 | 0.067 | 0.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 MED GAS | 212.52 | 212.52 | 0.019 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65 | 0.00543 |
FLOOR 1 MRI HALL | 323.28 | 323.28 | 0.028 | 0.028 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 MRI TOILET | 142.20 | 142.20 | 0.013 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.16 | 0.00543 |
FLOOR 1 NURSE HALL | 904.91 | 904.91 | 0.080 | 0.080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 NURSE JANITOR | 114.33 | 114.33 | 0.010 | 0.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 NURSE TOILET | 140.22 | 140.22 | 0.012 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 PRE-OP HALL | 904.42 | 904.42 | 0.080 | 0.080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 PRE-OP TOILET | 191.90 | 191.90 | 0.017 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 1 RECEPTION HALL | 234.77 | 234.77 | 0.021 | 0.021 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 SCRUB | 165.39 | 165.39 | 0.015 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:40:00 | 22.11 | 0.00543 |
FLOOR 1 STERILE HALL | 967.32 | 967.32 | 0.088 | 0.088 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 33.16 | 0.00543 |
FLOOR 1 STERILE STORAGE | 537.64 | 537.64 | 0.047 | 0.047 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 STORAGE | 1975.80 | 1975.80 | 0.179 | 0.179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 33.16 | 0.00543 |
FLOOR 1 SUB-STERILE | 760.42 | 760.42 | 0.069 | 0.069 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:40:00 | 27.44 | 0.00543 |
FLOOR 1 UTILITY HALL | 716.20 | 716.20 | 0.065 | 0.065 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.60 | 0.00543 |
FLOOR 1 UTILITY JANITOR | 81.98 | 81.98 | 0.007 | 0.007 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 1 UTILITY ROOM | 871.87 | 871.87 | 0.079 | 0.079 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 28.28 | 0.00543 |
FLOOR 1 VESTIBULE | 280.69 | 280.69 | 0.025 | 0.025 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 31.58 | 0.00543 |
FLOOR 2 CONFERENCE TOILET | 198.13 | 198.13 | 0.021 | 0.050 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM HALL 1 | 597.73 | 597.73 | 0.064 | 0.064 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 2 EXAM HALL 2 | 556.31 | 556.31 | 0.058 | 0.058 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM HALL 3 | 534.37 | 534.37 | 0.055 | 0.055 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM HALL 4 | 550.80 | 550.80 | 0.057 | 0.057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM HALL 5 | 581.49 | 581.49 | 0.060 | 0.060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 EXAM HALL 6 | 578.95 | 578.95 | 0.060 | 0.060 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 JANITOR | 386.31 | 386.31 | 0.041 | 0.041 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 2 OFFICE HALL | 1223.15 | 1223.15 | 0.131 | 0.131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:40:00 | 22.11 | 0.00543 |
FLOOR 2 RECEPTION HALL | 1723.60 | 1723.60 | 0.178 | 0.178 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 RECEPTION TOILET | 366.88 | 366.88 | 0.038 | 0.099 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 STORAGE 1 | 166.98 | 166.98 | 0.017 | 0.017 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 STORAGE 2 | 293.97 | 293.97 | 0.030 | 0.030 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 STORAGE 3 | 381.63 | 381.63 | 0.039 | 0.039 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 UTILITY | 677.36 | 677.36 | 0.072 | 0.072 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 27.02 | 0.00543 |
FLOOR 2 WORK HALL | 2371.96 | 2371.96 | 0.245 | 0.245 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:20:00 | 19.74 | 0.00543 |
FLOOR 2 WORK TOILET | 205.41 | 205.41 | 0.022 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 30.35 | 0.00543 |
FLOOR 3 ELEVATOR HALL | 957.52 | 957.52 | 0.102 | 0.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90 | 0.00543 |
FLOOR 3 JANITOR | 227.81 | 227.81 | 0.024 | 0.024 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 31.33 | 0.00543 |
FLOOR 3 LOUNGE TOILET | 792.52 | 792.52 | 0.085 | 0.151 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90 | 0.00543 |
FLOOR 3 MECHANICAL | 3852.49 | 3852.49 | 0.412 | 0.412 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:50:00 | 27.86 | 0.00543 |
FLOOR 3 MECHANICAL HALL | 1053.97 | 1053.97 | 0.113 | 0.113 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 33.53 | 0.00543 |
FLOOR 3 OFFICE HALL | 2518.57 | 2518.57 | 0.269 | 0.269 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90 | 0.00543 |
FLOOR 3 OFFICE TOILET | 194.54 | 194.54 | 0.021 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 31.09 | 0.00543 |
FLOOR 3 PHYSICAL THERAPY TOILET | 277.60 | 277.60 | 0.030 | 0.066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90 | 0.00543 |
FLOOR 3 STORAGE 1 | 292.82 | 292.82 | 0.031 | 0.031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90 | 0.00543 |
FLOOR 3 STORAGE 2 | 264.53 | 264.53 | 0.028 | 0.028 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.90 | 0.00543 |
FLOOR 3 UNDEVELOPED 1 | 9665.30 | 9665.30 | 1.034 | 1.034 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 33.46 | 0.00543 |
FLOOR 3 UNDEVELOPED 2 | 4989.76 | 4989.76 | 0.534 | 0.534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 33.60 | 0.00543 |
FLOOR 3 UTILITY | 481.37 | 481.37 | 0.051 | 0.051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.90 | 0.00543 |
NE STAIR | 1635.48 | 1635.48 | 0.175 | 0.175 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.90 | 0.00543 |
NW ELEVATOR | 1276.33 | 1276.33 | 0.136 | 0.136 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 30.84 | 0.00543 |
NW STAIR | 1748.18 | 1748.18 | 0.187 | 0.187 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 32.81 | 0.00543 |
SW STAIR | 1030.72 | 1030.72 | 0.110 | 0.110 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:30:00 | 32.42 | 0.00543 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 274.47 | 274.47 | 0.014 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 CAFE | 443.35 | 443.35 | 0.023 | 0.184 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 DRESSING ROOM | 281.72 | 281.72 | 0.015 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 IT ROOM | 8.44 | 8.44 | 0.000 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -17.90 | 0.00096 |
FLOOR 1 LOBBY | 1138.47 | 1138.47 | 0.059 | 0.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.000 | 0.042 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 0.00 | 0.000 | 0.239 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.000 | 0.052 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PROCEDURE ROOM | 193.64 | 193.64 | 0.010 | 0.108 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 RECEPTION | 33.08 | 33.08 | 0.002 | 0.050 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -17.90 | 0.00096 |
FLOOR 1 RECOVERY ROOM | 1120.78 | 1120.78 | 0.058 | 0.161 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 SCHEDULING | 83.44 | 83.44 | 0.004 | 0.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 SOIL HOLD | 1.72 | 1.72 | 0.000 | 0.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -17.90 | 0.00096 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 STEP DOWN | 952.78 | 952.78 | 0.050 | 0.090 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 CONFERENCE | 1443.06 | 1443.06 | 0.075 | 0.075 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 EXAM 1 | 1482.28 | 1482.28 | 0.077 | 0.077 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 2 | 533.29 | 533.29 | 0.028 | 0.076 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 3 | 727.37 | 727.37 | 0.038 | 0.102 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 4 | 362.80 | 362.80 | 0.019 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 5 | 1080.33 | 1080.33 | 0.056 | 0.056 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 6 | 611.50 | 611.50 | 0.032 | 0.032 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 7 | 334.58 | 334.58 | 0.017 | 0.112 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 8 | 653.64 | 653.64 | 0.034 | 0.038 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM 9 | 271.81 | 271.81 | 0.014 | 0.056 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 OFFICE | 1853.53 | 1853.53 | 0.097 | 0.097 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 RECEPTION | 2250.80 | 2250.80 | 0.117 | 0.117 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 WORK | 918.52 | 918.52 | 0.048 | 0.068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 3 DRESSING ROOM | 116.06 | 116.06 | 0.006 | 0.006 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 HUMID | 243.83 | 243.83 | 0.013 | 0.013 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 LOCKER | 266.21 | 266.21 | 0.014 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 LOUNGE | 1203.72 | 1203.72 | 0.062 | 0.062 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 OFFICE | 6764.53 | 6764.53 | 0.350 | 0.350 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 PHYSICAL THERAPY 1 | 4724.38 | 4724.38 | 0.246 | 0.246 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 PHYSICAL THERAPY 2 | 1219.32 | 1219.32 | 0.063 | 0.084 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 TREATMENT | 883.54 | 883.54 | 0.046 | 0.067 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 WORK | 2305.45 | 2305.45 | 0.120 | 0.120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 BIO HAZ | 104.04 | 104.04 | 0.005 | 0.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 ELECTRICAL ROOM | 10.51 | 10.51 | 0.001 | 0.001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -17.90 | 0.00096 |
FLOOR 1 ELEVATOR PUMP ROOM | 383.99 | 383.99 | 0.020 | 0.020 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 IT HALL | 20.22 | 20.22 | 0.001 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 LOBBY HALL | 0.78 | 0.78 | 0.000 | 0.007 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | -17.90 | 0.00096 |
FLOOR 1 LOBBY TOILET | 222.98 | 222.98 | 0.012 | 0.012 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 MED GAS | 498.66 | 498.66 | 0.026 | 0.026 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 MRI HALL | 13.69 | 13.69 | 0.001 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:10:00 | -17.90 | 0.00096 |
FLOOR 1 MRI TOILET | 147.62 | 147.62 | 0.008 | 0.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 NURSE HALL | 107.85 | 107.85 | 0.006 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.000 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 PRE-OP TOILET | 203.15 | 203.15 | 0.011 | 0.011 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 SCRUB | 90.42 | 90.42 | 0.005 | 0.005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 STERILE HALL | 323.41 | 323.41 | 0.017 | 0.017 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 1 STORAGE | 3516.97 | 3516.97 | 0.183 | 0.183 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 SUB-STERILE | 622.52 | 622.52 | 0.032 | 0.032 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 UTILITY HALL | 1059.20 | 1059.20 | 0.055 | 0.055 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 UTILITY JANITOR | 44.97 | 44.97 | 0.002 | 0.002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 UTILITY ROOM | 1033.57 | 1033.57 | 0.054 | 0.054 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 1 VESTIBULE | 280.46 | 280.46 | 0.015 | 0.015 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 CONFERENCE TOILET | 84.48 | 84.48 | 0.004 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 1 | 369.45 | 369.45 | 0.019 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 2 | 227.30 | 227.30 | 0.012 | 0.012 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 3 | 239.42 | 239.42 | 0.013 | 0.013 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 4 | 155.68 | 155.68 | 0.008 | 0.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 5 | 157.64 | 157.64 | 0.008 | 0.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 EXAM HALL 6 | 197.27 | 197.27 | 0.010 | 0.010 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 JANITOR | 430.85 | 430.85 | 0.023 | 0.023 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 OFFICE HALL | 566.27 | 566.27 | 0.030 | 0.030 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00096 | |
FLOOR 2 RECEPTION TOILET | 63.17 | 63.17 | 0.003 | 0.003 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 STORAGE 1 | 77.22 | 77.22 | 0.004 | 0.004 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 STORAGE 2 | 92.88 | 92.88 | 0.005 | 0.007 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 STORAGE 3 | 99.31 | 99.31 | 0.005 | 0.008 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 UTILITY | 549.29 | 549.29 | 0.029 | 0.029 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 2 WORK HALL | 17.32 | 17.32 | 0.001 | 0.024 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -17.90 | 0.00096 |
FLOOR 2 WORK TOILET | 262.30 | 262.30 | 0.014 | 0.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 ELEVATOR HALL | 1079.47 | 1079.47 | 0.056 | 0.056 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 JANITOR | 460.98 | 460.98 | 0.024 | 0.024 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 LOUNGE TOILET | 847.16 | 847.16 | 0.044 | 0.044 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 MECHANICAL | 428.33 | 428.33 | 0.022 | 0.022 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 MECHANICAL HALL | 1093.09 | 1093.09 | 0.057 | 0.057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 OFFICE HALL | 2438.07 | 2438.07 | 0.127 | 0.127 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 OFFICE TOILET | 309.55 | 309.55 | 0.016 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 PHYSICAL THERAPY TOILET | 230.98 | 230.98 | 0.012 | 0.012 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 STORAGE 1 | 357.96 | 357.96 | 0.019 | 0.019 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 STORAGE 2 | 312.82 | 312.82 | 0.016 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 UNDEVELOPED 1 | 6077.02 | 6077.02 | 0.315 | 0.315 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 UNDEVELOPED 2 | 3931.32 | 3931.32 | 0.204 | 0.204 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
FLOOR 3 UTILITY | 619.75 | 619.75 | 0.032 | 0.032 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
NE STAIR | 3068.64 | 3068.64 | 0.160 | 0.160 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
NW ELEVATOR | 1913.53 | 1913.53 | 0.100 | 0.100 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
NW STAIR | 3109.18 | 3109.18 | 0.162 | 0.162 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
SW STAIR | 1489.66 | 1489.66 | 0.078 | 0.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90 | 0.00096 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 8.13 | 8.13 | 2.44 | 2.44 |
AHU-2 | 13.00 | 13.00 | 3.75 | 3.75 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AHU-2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 13.00 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
FLOOR 2 CONFERENCE | AHU-2_DCV | 0.000000 | 0.001575 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 DICTATION | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 3 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 4 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 5 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 6 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 7 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 8 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 9 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 1 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 2 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION | AHU-2_DCV | 0.000000 | 0.001067 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 1 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 2 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 X-RAY | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 DRESSING ROOM | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 HUMID | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOCKER | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 TREATMENT | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 CONFERENCE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 1 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 2 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 3 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 4 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 5 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 6 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 3 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 ELEVATOR HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
NE STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW ELEVATOR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
SW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 3441.50 | 7604.50 | 3406.67 |
FLOOR 1 CAFE | 808.33 | 7193.83 | 507.00 |
FLOOR 1 CLEAN | 885.33 | 7828.17 | 885.33 |
FLOOR 1 CLEAN WORK | 1927.50 | 7830.00 | 1927.50 |
FLOOR 1 DICTATION | 99.33 | 7830.00 | 99.33 |
FLOOR 1 DRESSING ROOM | 2827.83 | 7823.33 | 2827.83 |
FLOOR 1 HUMID | 4.33 | 7830.00 | 4.33 |
FLOOR 1 IT ROOM | 540.50 | 7830.00 | 540.50 |
FLOOR 1 LOBBY | 753.50 | 7776.00 | 733.83 |
FLOOR 1 LOCKER ROOM | 112.50 | 7799.17 | 109.67 |
FLOOR 1 LOUNGE | 38.00 | 7818.00 | 38.00 |
FLOOR 1 MRI CONTROL ROOM | 205.50 | 7638.00 | 112.83 |
FLOOR 1 MRI ROOM | 95.00 | 7490.33 | 0.00 |
FLOOR 1 NOURISHMENT | 8.33 | 7830.00 | 8.33 |
FLOOR 1 NURSE STATION | 76.17 | 7830.00 | 76.17 |
FLOOR 1 OFFICE | 72.17 | 7830.00 | 72.17 |
FLOOR 1 OPERATING ROOM 1 | 2936.17 | 7828.50 | 2936.17 |
FLOOR 1 OPERATING ROOM 2 | 3098.50 | 7830.00 | 3098.50 |
FLOOR 1 OPERATING ROOM 3 | 5815.67 | 7830.00 | 5815.67 |
FLOOR 1 PACU | 2318.50 | 7830.00 | 2318.50 |
FLOOR 1 PRE-OP ROOM 1 | 3393.00 | 7830.00 | 3393.00 |
FLOOR 1 PRE-OP ROOM 2 | 2642.17 | 7830.00 | 2642.17 |
FLOOR 1 PROCEDURE ROOM | 4200.67 | 7830.00 | 4200.67 |
FLOOR 1 RECEPTION | 148.17 | 7799.83 | 147.50 |
FLOOR 1 RECOVERY ROOM | 3192.50 | 7589.17 | 3143.00 |
FLOOR 1 SCHEDULING | 467.83 | 7830.00 | 467.83 |
FLOOR 1 SOIL | 3888.67 | 7830.00 | 3888.67 |
FLOOR 1 SOIL HOLD | 4154.17 | 7830.00 | 4154.17 |
FLOOR 1 SOIL WORK | 4057.83 | 7830.00 | 4057.83 |
FLOOR 1 STEP DOWN | 3019.33 | 7663.83 | 2972.83 |
FLOOR 2 CONFERENCE | 1854.50 | 7704.17 | 1850.00 |
FLOOR 2 DICTATION | 691.67 | 7830.00 | 691.67 |
FLOOR 2 EXAM 1 | 3430.83 | 7811.00 | 3430.83 |
FLOOR 2 EXAM 2 | 3211.33 | 7830.00 | 3211.33 |
FLOOR 2 EXAM 3 | 3514.67 | 7830.00 | 3514.67 |
FLOOR 2 EXAM 4 | 3060.83 | 7730.83 | 3058.00 |
FLOOR 2 EXAM 5 | 3204.67 | 7830.00 | 3204.67 |
FLOOR 2 EXAM 6 | 4007.50 | 7830.00 | 4007.50 |
FLOOR 2 EXAM 7 | 3614.00 | 7830.00 | 3614.00 |
FLOOR 2 EXAM 8 | 3741.67 | 7830.00 | 3741.67 |
FLOOR 2 EXAM 9 | 3200.83 | 7830.00 | 3200.83 |
FLOOR 2 LOUNGE | 327.50 | 7830.00 | 327.50 |
FLOOR 2 NURSE STATION 1 | 414.33 | 7830.00 | 414.33 |
FLOOR 2 NURSE STATION 2 | 397.17 | 7830.00 | 397.17 |
FLOOR 2 OFFICE | 1855.67 | 7830.00 | 1855.67 |
FLOOR 2 RECEPTION | 1224.50 | 7830.00 | 1224.50 |
FLOOR 2 SCHEDULING 1 | 252.83 | 7830.00 | 252.83 |
FLOOR 2 SCHEDULING 2 | 266.67 | 7830.00 | 266.67 |
FLOOR 2 WORK | 645.00 | 7830.00 | 645.00 |
FLOOR 2 X-RAY | 9.17 | 7455.83 | 0.17 |
FLOOR 3 DRESSING ROOM | 2029.83 | 7830.00 | 2029.83 |
FLOOR 3 HUMID | 1576.33 | 7830.00 | 1576.33 |
FLOOR 3 LOCKER | 1254.17 | 7830.00 | 1254.17 |
FLOOR 3 LOUNGE | 1136.67 | 7830.00 | 1136.67 |
FLOOR 3 OFFICE | 1942.67 | 7830.00 | 1942.67 |
FLOOR 3 PHYSICAL THERAPY 1 | 3976.67 | 7563.83 | 3964.83 |
FLOOR 3 PHYSICAL THERAPY 2 | 3944.00 | 7830.00 | 3944.00 |
FLOOR 3 TREATMENT | 3492.33 | 7830.00 | 3492.33 |
FLOOR 3 WORK | 2457.33 | 7813.33 | 2457.33 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 6888.00 | 7830.00 | 6629.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 2.50 | 512.00 | 2.50 | 512.00 |
FLOOR 1 CAFE | 1.83 | 807.17 | 1.83 | 807.17 |
FLOOR 1 CLEAN | 0.00 | 106.00 | 0.00 | 106.00 |
FLOOR 1 CLEAN WORK | 0.17 | 83.83 | 0.17 | 83.83 |
FLOOR 1 DICTATION | 0.00 | 34.83 | 0.00 | 34.83 |
FLOOR 1 DRESSING ROOM | 7.67 | 89.67 | 7.67 | 89.67 |
FLOOR 1 HUMID | 0.00 | 49.33 | 0.00 | 49.33 |
FLOOR 1 IT ROOM | 0.00 | 44.67 | 0.00 | 44.67 |
FLOOR 1 LOBBY | 2.00 | 74.67 | 2.00 | 74.67 |
FLOOR 1 LOCKER ROOM | 0.00 | 153.50 | 0.00 | 153.50 |
FLOOR 1 LOUNGE | 0.00 | 155.50 | 0.00 | 155.50 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 651.50 | 0.00 | 651.50 |
FLOOR 1 MRI ROOM | 0.00 | 1675.00 | 0.00 | 1675.00 |
FLOOR 1 NOURISHMENT | 0.00 | 103.67 | 0.00 | 103.67 |
FLOOR 1 NURSE STATION | 0.00 | 98.67 | 0.00 | 98.67 |
FLOOR 1 OFFICE | 0.00 | 66.00 | 0.00 | 66.00 |
FLOOR 1 OPERATING ROOM 1 | 1.00 | 1826.50 | 1.00 | 1824.67 |
FLOOR 1 OPERATING ROOM 2 | 0.17 | 1733.00 | 0.17 | 1730.50 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 2256.17 | 0.00 | 2256.17 |
FLOOR 1 PACU | 0.17 | 90.67 | 0.17 | 90.67 |
FLOOR 1 PRE-OP ROOM 1 | 2.33 | 13.50 | 2.33 | 13.50 |
FLOOR 1 PRE-OP ROOM 2 | 0.83 | 0.83 | 0.83 | 0.83 |
FLOOR 1 PROCEDURE ROOM | 2.67 | 0.17 | 2.67 | 0.17 |
FLOOR 1 RECEPTION | 0.00 | 286.33 | 0.00 | 286.33 |
FLOOR 1 RECOVERY ROOM | 2.33 | 441.50 | 2.33 | 441.50 |
FLOOR 1 SCHEDULING | 0.17 | 62.00 | 0.17 | 62.00 |
FLOOR 1 SOIL | 1.50 | 0.00 | 1.50 | 0.00 |
FLOOR 1 SOIL HOLD | 2.33 | 0.00 | 2.33 | 0.00 |
FLOOR 1 SOIL WORK | 2.17 | 0.00 | 2.17 | 0.00 |
FLOOR 1 STEP DOWN | 2.83 | 230.50 | 2.83 | 230.50 |
FLOOR 2 CONFERENCE | 0.00 | 282.00 | 0.00 | 282.00 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 2 | 0.00 | 52.00 | 0.00 | 52.00 |
FLOOR 2 EXAM 3 | 0.00 | 67.67 | 0.00 | 67.67 |
FLOOR 2 EXAM 4 | 0.00 | 343.00 | 0.00 | 343.00 |
FLOOR 2 EXAM 5 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 6 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 8 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 LOUNGE | 0.00 | 0.50 | 0.00 | 0.50 |
FLOOR 2 NURSE STATION 1 | 0.00 | 5.50 | 0.00 | 5.50 |
FLOOR 2 NURSE STATION 2 | 0.00 | 5.67 | 0.00 | 5.67 |
FLOOR 2 OFFICE | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 2 RECEPTION | 0.00 | 44.67 | 0.00 | 44.67 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 2 X-RAY | 0.00 | 1519.33 | 0.00 | 1519.33 |
FLOOR 3 DRESSING ROOM | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 3 HUMID | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 3 LOCKER | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 3 LOUNGE | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 3 OFFICE | 0.33 | 0.00 | 0.33 | 0.00 |
FLOOR 3 PHYSICAL THERAPY 1 | 0.00 | 205.83 | 0.00 | 205.83 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 TREATMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 WORK | 0.17 | 0.00 | 0.17 | 0.00 |
FLOOR 1 BIO HAZ | 46.83 | 4.17 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 152.50 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 3.17 | 226.83 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.33 | 13.17 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 104.17 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 10.83 | 43.33 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 14.67 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 155.33 | 32.50 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 41.83 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 14.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 17.33 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 6.67 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 15.33 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 13.00 | 1.50 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 7.33 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.33 | 42.33 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.33 | 58.83 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 155.83 | 64.83 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 1.33 | 35.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 32.67 | 36.33 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.67 | 38.83 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 6.33 | 10.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 2423.17 | 760.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 1.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 5.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 6.67 | 2.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 6.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 5.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 7.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 3.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 2.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 1.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 1.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.67 | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 86.67 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 5227.33 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 1.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 2.83 | 0.00 | 0.00 | 0.00 |
NE STAIR | 51.17 | 0.83 | 0.00 | 0.00 |
NW ELEVATOR | 13.17 | 0.00 | 0.00 | 0.00 |
NW STAIR | 58.17 | 3.83 | 0.00 | 0.00 |
SW STAIR | 6.33 | 5.83 | 0.00 | 0.00 |
Facility | 2457.33 | 7365.00 | 8.33 | 2605.83 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:45
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000036 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.007217 | 0.000003 | 0.005449 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.365372 | 0.000038 | 0.073074 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.050200 | 0.000026 | 0.050200 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.062638 | 0.000033 | 0.062638 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.031327 | 0.000003 | 0.006265 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.018780 | 0.000008 | 0.014738 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.054277 | 0.000006 | 0.010855 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.337014 | 0.000035 | 0.067403 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.014877 | 0.000002 | 0.002975 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.021243 | 0.000002 | 0.004249 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.025010 | 0.000003 | 0.005002 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.338963 | 0.000036 | 0.067793 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.045283 | 0.000005 | 0.009057 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000022 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.275206 | 0.000029 | 0.055041 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.066638 | 0.000007 | 0.013328 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.137940 | 0.000014 | 0.027588 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.026074 | 0.000014 | 0.026074 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.168300 | 0.000018 | 0.033660 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.028447 | 0.000003 | 0.005689 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.415288 | 0.000044 | 0.083058 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000022 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.067667 | 0.000007 | 0.013533 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.079586 | 0.000008 | 0.015917 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.010133 | 0.000001 | 0.002027 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.090932 | 0.000010 | 0.018186 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000022 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.099065 | 0.000010 | 0.019813 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.935015 | 0.000294 | 0.561009 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.976950 | 0.000307 | 0.586170 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.762725 | 0.000399 | 0.762725 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000027 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.079567 | 0.000008 | 0.015913 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000047 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000084 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000022 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000176 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.208175 | 0.000022 | 0.041635 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.020719 | 0.000002 | 0.004144 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.338880 | 0.000154 | 0.294825 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.034550 | 0.000004 | 0.006910 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.014976 | 0.000002 | 0.004755 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000052 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000023 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000074 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.211823 | 0.000077 | 0.146158 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.087594 | 0.000009 | 0.017519 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.047404 | 0.000005 | 0.009481 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.183099 | 0.000096 | 0.183099 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.068857 | 0.000017 | 0.032438 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.064853 | 0.000029 | 0.055233 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.007299 | 0.000001 | 0.002369 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.078950 | 0.000028 | 0.053764 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.025417 | 0.000008 | 0.014631 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.310696 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.025933 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.327362 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.270049 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.370693 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.066410 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.267089 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.115947 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.143685 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.186879 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.063915 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.057578 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.055345 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.057045 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.060273 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.059995 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.041306 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.042921 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.068992 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.084108 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.341788 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.130791 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.619047 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.178274 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.100334 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.109834 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.017340 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.030447 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.039491 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.072429 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.495184 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.245235 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 1.01 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.020863 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.102388 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.052278 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.024360 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.081215 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.485573 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.411945 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.112698 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 1.21 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.269310 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 0.992123 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.318696 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.031311 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.028285 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.271898 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 1.03 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.533553 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.051472 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.399333 | ||
NE STAIR VAV BOX COMPONENT | 0.174879 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.136475 | ||
NW STAIR VAV BOX COMPONENT | 0.186929 | ||
SW STAIR VAV BOX COMPONENT | 0.110213 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 1653.18 | 0.000036 | 35.64 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 132.56 | 0.000003 | 2.86 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 1777.69 | 0.000038 | 95.82 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1221.21 | 0.000026 | 26.33 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1523.80 | 0.000033 | 32.86 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 152.42 | 0.000003 | 8.22 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 358.54 | 0.000008 | 7.73 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 264.08 | 0.000006 | 14.23 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 1639.72 | 0.000035 | 88.39 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 72.38 | 0.000002 | 3.90 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 103.35 | 0.000002 | 5.57 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 121.68 | 0.000003 | 6.56 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 1649.20 | 0.000036 | 88.90 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 220.32 | 0.000005 | 11.88 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1033.24 | 0.000022 | 22.28 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 1338.99 | 0.000029 | 72.18 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 324.22 | 0.000007 | 17.48 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 671.14 | 0.000014 | 36.18 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 634.31 | 0.000014 | 13.68 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 818.85 | 0.000018 | 44.14 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 138.40 | 0.000003 | 7.46 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2020.55 | 0.000044 | 108.91 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1033.24 | 0.000022 | 22.28 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 329.23 | 0.000007 | 17.75 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 387.22 | 0.000008 | 20.87 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 49.30 | 0.000001 | 2.66 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 442.42 | 0.000010 | 23.85 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1033.24 | 0.000022 | 22.28 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 482.00 | 0.000010 | 25.98 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 13647.75 | 0.000294 | 294.26 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 14259.85 | 0.000307 | 307.46 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 18554.94 | 0.000399 | 400.07 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1239.89 | 0.000027 | 26.73 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 387.13 | 0.000008 | 20.87 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2169.80 | 0.000047 | 46.78 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 3880.38 | 0.000084 | 83.67 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1033.24 | 0.000022 | 22.28 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 8179.80 | 0.000176 | 176.37 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1012.86 | 0.000022 | 54.60 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 100.81 | 0.000002 | 5.43 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 7172.26 | 0.000154 | 154.64 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 168.10 | 0.000004 | 9.06 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 115.67 | 0.000002 | 3.93 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2410.89 | 0.000052 | 51.98 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1071.51 | 0.000023 | 23.10 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 3444.13 | 0.000074 | 74.26 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 3555.61 | 0.000077 | 76.66 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 426.18 | 0.000009 | 22.97 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 230.64 | 0.000005 | 12.43 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 4454.27 | 0.000096 | 96.04 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 789.12 | 0.000017 | 18.06 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 1343.65 | 0.000029 | 28.97 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 57.62 | 0.000001 | 1.91 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 1307.92 | 0.000028 | 28.20 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 355.94 | 0.000008 | 7.67 |
AHU-1_HEATC | 48125.18 | 0.001036 | 775.10 |
AHU-1_EXTRAWATERHEATC | 48125.18 | 0.001036 | 775.10 |
AHU-2_HEATC | 78323.46 | 0.001686 | 1261.03 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2156.50 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 1204.13 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 124.07 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 3993.71 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 6459.82 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 8867.31 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 1016.70 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 4408.41 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 2607.13 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 8940.65 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 3196.48 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 4470.33 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 461.67 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 285.32 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 300.37 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 272.91 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 288.36 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 287.03 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 539.07 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 223.60 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 496.89 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 596.27 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 2309.67 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 709.77 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 4278.26 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 852.90 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 2370.63 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 570.21 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 601.89 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 139.13 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 298.14 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 357.77 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 685.89 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 2974.15 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1173.25 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1015.98 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 5590.19 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 144.42 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 1341.24 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 302.64 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 576.30 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 388.55 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 2323.07 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 3612.39 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 1970.82 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 1361.64 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 8371.48 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 3030.15 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1015.98 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 16375.42 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 6327.51 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 1580.42 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 748.98 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 389.91 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 5268.28 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 7537.31 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 4889.70 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 770.70 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 2871.46 |
NE STAIR VAV BOX REHEAT COIL | 3832.07 |
NW ELEVATOR VAV BOX REHEAT COIL | 2386.27 |
NW STAIR VAV BOX REHEAT COIL | 3880.70 |
SW STAIR VAV BOX REHEAT COIL | 1858.98 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 8.13 |
AHU-2 AIR LOOP MAIN BRANCH | 13.00 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 8.13 |
AHU-2 | 13.00 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 8.13 | 2.07 |
AHU-2_OA_CONTROLLER | 13.00 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 8.13 | 134610.03 | 0.798655 | 2.71 | 44865.52 |
AHU-2_COOLC DXCOIL | 13.00 | 215170.34 | 0.798655 | 4.33 | 71716.27 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 8.13 |
AHU-2_FAN | 13.00 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.001036 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.001036 |
AHU-2_HEATC_CONTROLLER | 0.001686 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.001857 | 1.39 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.001857 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
HEATSYS1 PUMP | 0.001857 | 474.53 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.93 | 0.85 |
February | 19.92 | -0.2 |
March | 19.95 | 4.82 |
April | 19.68 | 6.08 |
May | 19.70 | 13.74 |
June | 19.98 | 22.16 |
July | 19.78 | 22.71 |
August | 19.99 | 21.74 |
September | 20.08 | 18.54 |
October | 20.02 | 7.12 |
November | 19.98 | 3.03 |
December | 19.81 | -1.0 |
Annual Sum or Average | 19.90 | 10.02 |
Minimum of Months | 19.68 | -1.0 |
Maximum of Months | 20.08 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.17 | 0.85 |
February | 20.20 | -0.2 |
March | 20.48 | 4.82 |
April | 20.53 | 6.08 |
May | 20.97 | 13.74 |
June | 21.69 | 22.16 |
July | 21.69 | 22.71 |
August | 21.67 | 21.74 |
September | 21.46 | 18.54 |
October | 20.57 | 7.12 |
November | 20.32 | 3.03 |
December | 20.15 | -1.0 |
Annual Sum or Average | 20.83 | 10.02 |
Minimum of Months | 20.15 | -1.0 |
Maximum of Months | 21.69 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 0.85 |
February | 21.26 | -0.2 |
March | 21.44 | 4.82 |
April | 21.15 | 6.08 |
May | 21.44 | 13.74 |
June | 21.89 | 22.16 |
July | 21.82 | 22.71 |
August | 21.90 | 21.74 |
September | 21.88 | 18.54 |
October | 21.51 | 7.12 |
November | 21.45 | 3.03 |
December | 21.19 | -1.0 |
Annual Sum or Average | 21.52 | 10.02 |
Minimum of Months | 21.15 | -1.0 |
Maximum of Months | 21.90 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.44 | 0.85 |
February | 20.50 | -0.2 |
March | 20.66 | 4.82 |
April | 20.49 | 6.08 |
May | 20.39 | 13.74 |
June | 20.54 | 22.16 |
July | 20.36 | 22.71 |
August | 20.45 | 21.74 |
September | 20.62 | 18.54 |
October | 20.58 | 7.12 |
November | 20.56 | 3.03 |
December | 20.49 | -1.0 |
Annual Sum or Average | 20.51 | 10.02 |
Minimum of Months | 20.36 | -1.0 |
Maximum of Months | 20.66 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.12 | 0.85 |
February | 20.18 | -0.2 |
March | 20.34 | 4.82 |
April | 20.18 | 6.08 |
May | 20.15 | 13.74 |
June | 20.29 | 22.16 |
July | 20.11 | 22.71 |
August | 20.21 | 21.74 |
September | 20.35 | 18.54 |
October | 20.27 | 7.12 |
November | 20.23 | 3.03 |
December | 20.15 | -1.0 |
Annual Sum or Average | 20.22 | 10.02 |
Minimum of Months | 20.11 | -1.0 |
Maximum of Months | 20.35 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 0.85 |
February | 21.68 | -0.2 |
March | 21.79 | 4.82 |
April | 21.71 | 6.08 |
May | 21.69 | 13.74 |
June | 21.87 | 22.16 |
July | 21.83 | 22.71 |
August | 21.88 | 21.74 |
September | 21.89 | 18.54 |
October | 21.77 | 7.12 |
November | 21.73 | 3.03 |
December | 21.67 | -1.0 |
Annual Sum or Average | 21.76 | 10.02 |
Minimum of Months | 21.63 | -1.0 |
Maximum of Months | 21.89 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 0.85 |
February | 19.69 | -0.2 |
March | 20.13 | 4.82 |
April | 20.18 | 6.08 |
May | 20.90 | 13.74 |
June | 21.69 | 22.16 |
July | 21.67 | 22.71 |
August | 21.58 | 21.74 |
September | 21.31 | 18.54 |
October | 20.25 | 7.12 |
November | 19.84 | 3.03 |
December | 19.62 | -1.0 |
Annual Sum or Average | 20.55 | 10.02 |
Minimum of Months | 19.62 | -1.0 |
Maximum of Months | 21.69 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 0.85 |
February | 21.63 | -0.2 |
March | 21.83 | 4.82 |
April | 21.79 | 6.08 |
May | 21.99 | 13.74 |
June | 22.23 | 22.16 |
July | 22.20 | 22.71 |
August | 22.20 | 21.74 |
September | 22.15 | 18.54 |
October | 21.91 | 7.12 |
November | 21.75 | 3.03 |
December | 21.54 | -1.0 |
Annual Sum or Average | 21.91 | 10.02 |
Minimum of Months | 21.54 | -1.0 |
Maximum of Months | 22.23 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.01 | 0.85 |
February | 21.04 | -0.2 |
March | 21.24 | 4.82 |
April | 21.13 | 6.08 |
May | 21.25 | 13.74 |
June | 21.57 | 22.16 |
July | 21.41 | 22.71 |
August | 21.43 | 21.74 |
September | 21.40 | 18.54 |
October | 21.19 | 7.12 |
November | 21.10 | 3.03 |
December | 20.96 | -1.0 |
Annual Sum or Average | 21.23 | 10.02 |
Minimum of Months | 20.96 | -1.0 |
Maximum of Months | 21.57 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.85 | 0.85 |
February | 21.90 | -0.2 |
March | 21.99 | 4.82 |
April | 21.94 | 6.08 |
May | 21.91 | 13.74 |
June | 22.07 | 22.16 |
July | 22.06 | 22.71 |
August | 22.08 | 21.74 |
September | 22.07 | 18.54 |
October | 21.98 | 7.12 |
November | 21.95 | 3.03 |
December | 21.90 | -1.0 |
Annual Sum or Average | 21.97 | 10.02 |
Minimum of Months | 21.85 | -1.0 |
Maximum of Months | 22.08 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.88 | 0.85 |
February | 20.92 | -0.2 |
March | 21.16 | 4.82 |
April | 21.13 | 6.08 |
May | 21.30 | 13.74 |
June | 21.69 | 22.16 |
July | 21.66 | 22.71 |
August | 21.71 | 21.74 |
September | 21.62 | 18.54 |
October | 21.20 | 7.12 |
November | 21.04 | 3.03 |
December | 20.88 | -1.0 |
Annual Sum or Average | 21.27 | 10.02 |
Minimum of Months | 20.88 | -1.0 |
Maximum of Months | 21.71 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 0.85 |
February | 21.13 | -0.2 |
March | 21.38 | 4.82 |
April | 21.34 | 6.08 |
May | 21.58 | 13.74 |
June | 21.96 | 22.16 |
July | 21.93 | 22.71 |
August | 21.94 | 21.74 |
September | 21.86 | 18.54 |
October | 21.40 | 7.12 |
November | 21.24 | 3.03 |
December | 21.08 | -1.0 |
Annual Sum or Average | 21.49 | 10.02 |
Minimum of Months | 21.08 | -1.0 |
Maximum of Months | 21.96 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.89 | 0.85 |
February | 20.91 | -0.2 |
March | 21.24 | 4.82 |
April | 21.13 | 6.08 |
May | 21.58 | 13.74 |
June | 22.01 | 22.16 |
July | 21.96 | 22.71 |
August | 21.96 | 21.74 |
September | 21.89 | 18.54 |
October | 21.34 | 7.12 |
November | 21.11 | 3.03 |
December | 20.76 | -1.0 |
Annual Sum or Average | 21.40 | 10.02 |
Minimum of Months | 20.76 | -1.0 |
Maximum of Months | 22.01 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.76 | 0.85 |
February | 21.78 | -0.2 |
March | 21.90 | 4.82 |
April | 21.82 | 6.08 |
May | 21.96 | 13.74 |
June | 22.19 | 22.16 |
July | 22.17 | 22.71 |
August | 22.19 | 21.74 |
September | 22.16 | 18.54 |
October | 21.98 | 7.12 |
November | 21.91 | 3.03 |
December | 21.75 | -1.0 |
Annual Sum or Average | 21.97 | 10.02 |
Minimum of Months | 21.75 | -1.0 |
Maximum of Months | 22.19 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.63 | 0.85 |
February | 19.64 | -0.2 |
March | 19.81 | 4.82 |
April | 19.72 | 6.08 |
May | 19.81 | 13.74 |
June | 20.08 | 22.16 |
July | 19.86 | 22.71 |
August | 19.96 | 21.74 |
September | 19.91 | 18.54 |
October | 19.74 | 7.12 |
November | 19.65 | 3.03 |
December | 19.58 | -1.0 |
Annual Sum or Average | 19.78 | 10.02 |
Minimum of Months | 19.58 | -1.0 |
Maximum of Months | 20.08 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 0.85 |
February | 21.65 | -0.2 |
March | 21.85 | 4.82 |
April | 21.81 | 6.08 |
May | 21.96 | 13.74 |
June | 22.21 | 22.16 |
July | 22.17 | 22.71 |
August | 22.18 | 21.74 |
September | 22.12 | 18.54 |
October | 21.89 | 7.12 |
November | 21.78 | 3.03 |
December | 21.59 | -1.0 |
Annual Sum or Average | 21.90 | 10.02 |
Minimum of Months | 21.59 | -1.0 |
Maximum of Months | 22.21 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 0.85 |
February | 21.54 | -0.2 |
March | 21.71 | 4.82 |
April | 21.65 | 6.08 |
May | 21.73 | 13.74 |
June | 22.00 | 22.16 |
July | 21.99 | 22.71 |
August | 22.03 | 21.74 |
September | 22.00 | 18.54 |
October | 21.76 | 7.12 |
November | 21.66 | 3.03 |
December | 21.52 | -1.0 |
Annual Sum or Average | 21.76 | 10.02 |
Minimum of Months | 21.49 | -1.0 |
Maximum of Months | 22.03 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 0.85 |
February | 21.85 | -0.2 |
March | 21.97 | 4.82 |
April | 21.93 | 6.08 |
May | 21.98 | 13.74 |
June | 22.19 | 22.16 |
July | 22.16 | 22.71 |
August | 22.17 | 21.74 |
September | 22.12 | 18.54 |
October | 21.98 | 7.12 |
November | 21.91 | 3.03 |
December | 21.83 | -1.0 |
Annual Sum or Average | 21.99 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 22.19 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 0.85 |
February | 19.41 | -0.2 |
March | 19.62 | 4.82 |
April | 19.66 | 6.08 |
May | 20.28 | 13.74 |
June | 21.40 | 22.16 |
July | 21.41 | 22.71 |
August | 21.28 | 21.74 |
September | 20.88 | 18.54 |
October | 19.59 | 7.12 |
November | 19.43 | 3.03 |
December | 19.30 | -1.0 |
Annual Sum or Average | 20.14 | 10.02 |
Minimum of Months | 19.30 | -1.0 |
Maximum of Months | 21.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.01 | 0.85 |
February | 22.04 | -0.2 |
March | 22.14 | 4.82 |
April | 22.12 | 6.08 |
May | 22.20 | 13.74 |
June | 22.37 | 22.16 |
July | 22.28 | 22.71 |
August | 22.31 | 21.74 |
September | 22.26 | 18.54 |
October | 22.16 | 7.12 |
November | 22.10 | 3.03 |
December | 22.01 | -1.0 |
Annual Sum or Average | 22.17 | 10.02 |
Minimum of Months | 22.01 | -1.0 |
Maximum of Months | 22.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 0.85 |
February | 21.38 | -0.2 |
March | 21.60 | 4.82 |
April | 21.56 | 6.08 |
May | 21.76 | 13.74 |
June | 22.05 | 22.16 |
July | 22.04 | 22.71 |
August | 22.05 | 21.74 |
September | 22.00 | 18.54 |
October | 21.67 | 7.12 |
November | 21.52 | 3.03 |
December | 21.33 | -1.0 |
Annual Sum or Average | 21.69 | 10.02 |
Minimum of Months | 21.33 | -1.0 |
Maximum of Months | 22.05 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.25 | 0.85 |
February | 22.27 | -0.2 |
March | 22.29 | 4.82 |
April | 22.27 | 6.08 |
May | 22.26 | 13.74 |
June | 22.37 | 22.16 |
July | 22.28 | 22.71 |
August | 22.32 | 21.74 |
September | 22.30 | 18.54 |
October | 22.29 | 7.12 |
November | 22.28 | 3.03 |
December | 22.26 | -1.0 |
Annual Sum or Average | 22.29 | 10.02 |
Minimum of Months | 22.25 | -1.0 |
Maximum of Months | 22.37 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 0.85 |
February | 19.41 | -0.2 |
March | 19.50 | 4.82 |
April | 19.44 | 6.08 |
May | 19.48 | 13.74 |
June | 19.57 | 22.16 |
July | 19.44 | 22.71 |
August | 19.55 | 21.74 |
September | 19.49 | 18.54 |
October | 19.42 | 7.12 |
November | 19.40 | 3.03 |
December | 19.38 | -1.0 |
Annual Sum or Average | 19.46 | 10.02 |
Minimum of Months | 19.38 | -1.0 |
Maximum of Months | 19.57 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 0.85 |
February | 21.87 | -0.2 |
March | 21.96 | 4.82 |
April | 21.90 | 6.08 |
May | 21.87 | 13.74 |
June | 22.03 | 22.16 |
July | 22.00 | 22.71 |
August | 22.03 | 21.74 |
September | 22.02 | 18.54 |
October | 21.94 | 7.12 |
November | 21.92 | 3.03 |
December | 21.87 | -1.0 |
Annual Sum or Average | 21.94 | 10.02 |
Minimum of Months | 21.82 | -1.0 |
Maximum of Months | 22.03 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.34 | 0.85 |
February | 21.28 | -0.2 |
March | 21.39 | 4.82 |
April | 21.24 | 6.08 |
May | 21.34 | 13.74 |
June | 21.69 | 22.16 |
July | 21.65 | 22.71 |
August | 21.74 | 21.74 |
September | 21.76 | 18.54 |
October | 21.47 | 7.12 |
November | 21.43 | 3.03 |
December | 21.32 | -1.0 |
Annual Sum or Average | 21.47 | 10.02 |
Minimum of Months | 21.24 | -1.0 |
Maximum of Months | 21.76 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 0.85 |
February | 21.71 | -0.2 |
March | 21.84 | 4.82 |
April | 21.78 | 6.08 |
May | 21.79 | 13.74 |
June | 22.03 | 22.16 |
July | 22.04 | 22.71 |
August | 22.06 | 21.74 |
September | 22.05 | 18.54 |
October | 21.88 | 7.12 |
November | 21.81 | 3.03 |
December | 21.71 | -1.0 |
Annual Sum or Average | 21.86 | 10.02 |
Minimum of Months | 21.65 | -1.0 |
Maximum of Months | 22.06 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 0.85 |
February | 21.77 | -0.2 |
March | 21.86 | 4.82 |
April | 21.77 | 6.08 |
May | 21.76 | 13.74 |
June | 21.97 | 22.16 |
July | 21.92 | 22.71 |
August | 21.97 | 21.74 |
September | 21.97 | 18.54 |
October | 21.86 | 7.12 |
November | 21.83 | 3.03 |
December | 21.77 | -1.0 |
Annual Sum or Average | 21.85 | 10.02 |
Minimum of Months | 21.74 | -1.0 |
Maximum of Months | 21.97 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.43 | 0.85 |
February | 19.45 | -0.2 |
March | 19.53 | 4.82 |
April | 19.45 | 6.08 |
May | 19.47 | 13.74 |
June | 19.52 | 22.16 |
July | 19.40 | 22.71 |
August | 19.52 | 21.74 |
September | 19.47 | 18.54 |
October | 19.44 | 7.12 |
November | 19.44 | 3.03 |
December | 19.41 | -1.0 |
Annual Sum or Average | 19.46 | 10.02 |
Minimum of Months | 19.40 | -1.0 |
Maximum of Months | 19.53 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.71 | 0.85 |
February | 21.76 | -0.2 |
March | 21.90 | 4.82 |
April | 21.85 | 6.08 |
May | 21.91 | 13.74 |
June | 22.12 | 22.16 |
July | 22.11 | 22.71 |
August | 22.13 | 21.74 |
September | 22.10 | 18.54 |
October | 21.94 | 7.12 |
November | 21.86 | 3.03 |
December | 21.74 | -1.0 |
Annual Sum or Average | 21.93 | 10.02 |
Minimum of Months | 21.71 | -1.0 |
Maximum of Months | 22.13 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.25 | 0.85 |
February | 19.28 | -0.2 |
March | 19.50 | 4.82 |
April | 19.38 | 6.08 |
May | 19.50 | 13.74 |
June | 19.87 | 22.16 |
July | 19.72 | 22.71 |
August | 19.74 | 21.74 |
September | 19.85 | 18.54 |
October | 19.52 | 7.12 |
November | 19.36 | 3.03 |
December | 19.12 | -1.0 |
Annual Sum or Average | 19.51 | 10.02 |
Minimum of Months | 19.12 | -1.0 |
Maximum of Months | 19.87 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.25 | 0.85 |
February | 19.30 | -0.2 |
March | 19.54 | 4.82 |
April | 19.48 | 6.08 |
May | 19.55 | 13.74 |
June | 19.85 | 22.16 |
July | 19.70 | 22.71 |
August | 19.68 | 21.74 |
September | 19.78 | 18.54 |
October | 19.50 | 7.12 |
November | 19.36 | 3.03 |
December | 19.19 | -1.0 |
Annual Sum or Average | 19.52 | 10.02 |
Minimum of Months | 19.19 | -1.0 |
Maximum of Months | 19.85 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.69 | 0.85 |
February | 18.70 | -0.2 |
March | 18.75 | 4.82 |
April | 18.69 | 6.08 |
May | 18.63 | 13.74 |
June | 18.66 | 22.16 |
July | 18.51 | 22.71 |
August | 18.58 | 21.74 |
September | 18.63 | 18.54 |
October | 18.71 | 7.12 |
November | 18.71 | 3.03 |
December | 18.67 | -1.0 |
Annual Sum or Average | 18.66 | 10.02 |
Minimum of Months | 18.51 | -1.0 |
Maximum of Months | 18.75 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 0.85 |
February | 20.13 | -0.2 |
March | 20.27 | 4.82 |
April | 20.08 | 6.08 |
May | 20.05 | 13.74 |
June | 20.17 | 22.16 |
July | 19.97 | 22.71 |
August | 20.10 | 21.74 |
September | 20.23 | 18.54 |
October | 20.19 | 7.12 |
November | 20.17 | 3.03 |
December | 20.11 | -1.0 |
Annual Sum or Average | 20.13 | 10.02 |
Minimum of Months | 19.97 | -1.0 |
Maximum of Months | 20.27 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.15 | 0.85 |
February | 21.17 | -0.2 |
March | 21.41 | 4.82 |
April | 21.36 | 6.08 |
May | 21.52 | 13.74 |
June | 21.89 | 22.16 |
July | 21.87 | 22.71 |
August | 21.92 | 21.74 |
September | 21.90 | 18.54 |
October | 21.51 | 7.12 |
November | 21.32 | 3.03 |
December | 21.13 | -1.0 |
Annual Sum or Average | 21.52 | 10.02 |
Minimum of Months | 21.13 | -1.0 |
Maximum of Months | 21.92 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.59 | 0.85 |
February | 19.61 | -0.2 |
March | 19.77 | 4.82 |
April | 19.67 | 6.08 |
May | 19.74 | 13.74 |
June | 19.94 | 22.16 |
July | 19.79 | 22.71 |
August | 19.86 | 21.74 |
September | 19.91 | 18.54 |
October | 19.73 | 7.12 |
November | 19.64 | 3.03 |
December | 19.57 | -1.0 |
Annual Sum or Average | 19.74 | 10.02 |
Minimum of Months | 19.57 | -1.0 |
Maximum of Months | 19.94 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.75 | 0.85 |
February | 19.79 | -0.2 |
March | 19.90 | 4.82 |
April | 19.78 | 6.08 |
May | 19.78 | 13.74 |
June | 19.86 | 22.16 |
July | 19.72 | 22.71 |
August | 19.79 | 21.74 |
September | 19.88 | 18.54 |
October | 19.83 | 7.12 |
November | 19.80 | 3.03 |
December | 19.77 | -1.0 |
Annual Sum or Average | 19.80 | 10.02 |
Minimum of Months | 19.72 | -1.0 |
Maximum of Months | 19.90 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 0.85 |
February | 19.41 | -0.2 |
March | 19.51 | 4.82 |
April | 19.44 | 6.08 |
May | 19.49 | 13.74 |
June | 19.68 | 22.16 |
July | 19.51 | 22.71 |
August | 19.64 | 21.74 |
September | 19.56 | 18.54 |
October | 19.44 | 7.12 |
November | 19.40 | 3.03 |
December | 19.37 | -1.0 |
Annual Sum or Average | 19.49 | 10.02 |
Minimum of Months | 19.37 | -1.0 |
Maximum of Months | 19.68 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 0.85 |
February | 19.42 | -0.2 |
March | 19.50 | 4.82 |
April | 19.43 | 6.08 |
May | 19.46 | 13.74 |
June | 19.54 | 22.16 |
July | 19.41 | 22.71 |
August | 19.52 | 21.74 |
September | 19.45 | 18.54 |
October | 19.41 | 7.12 |
November | 19.40 | 3.03 |
December | 19.38 | -1.0 |
Annual Sum or Average | 19.44 | 10.02 |
Minimum of Months | 19.38 | -1.0 |
Maximum of Months | 19.54 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 0.85 |
February | 21.59 | -0.2 |
March | 21.74 | 4.82 |
April | 21.61 | 6.08 |
May | 21.80 | 13.74 |
June | 22.11 | 22.16 |
July | 22.09 | 22.71 |
August | 22.13 | 21.74 |
September | 22.09 | 18.54 |
October | 21.83 | 7.12 |
November | 21.76 | 3.03 |
December | 21.56 | -1.0 |
Annual Sum or Average | 21.83 | 10.02 |
Minimum of Months | 21.56 | -1.0 |
Maximum of Months | 22.13 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.41 | 0.85 |
February | 21.44 | -0.2 |
March | 21.62 | 4.82 |
April | 21.54 | 6.08 |
May | 21.66 | 13.74 |
June | 21.97 | 22.16 |
July | 21.97 | 22.71 |
August | 22.00 | 21.74 |
September | 21.99 | 18.54 |
October | 21.70 | 7.12 |
November | 21.58 | 3.03 |
December | 21.42 | -1.0 |
Annual Sum or Average | 21.69 | 10.02 |
Minimum of Months | 21.41 | -1.0 |
Maximum of Months | 22.00 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.94 | 0.85 |
February | 19.93 | -0.2 |
March | 19.99 | 4.82 |
April | 19.74 | 6.08 |
May | 19.78 | 13.74 |
June | 20.06 | 22.16 |
July | 19.87 | 22.71 |
August | 20.08 | 21.74 |
September | 20.17 | 18.54 |
October | 20.06 | 7.12 |
November | 20.01 | 3.03 |
December | 19.82 | -1.0 |
Annual Sum or Average | 19.95 | 10.02 |
Minimum of Months | 19.74 | -1.0 |
Maximum of Months | 20.17 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.22 | 0.85 |
February | 21.18 | -0.2 |
March | 21.38 | 4.82 |
April | 21.26 | 6.08 |
May | 21.53 | 13.74 |
June | 21.91 | 22.16 |
July | 21.90 | 22.71 |
August | 21.92 | 21.74 |
September | 21.90 | 18.54 |
October | 21.51 | 7.12 |
November | 21.38 | 3.03 |
December | 21.12 | -1.0 |
Annual Sum or Average | 21.52 | 10.02 |
Minimum of Months | 21.12 | -1.0 |
Maximum of Months | 21.92 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.03 | 0.85 |
February | 21.12 | -0.2 |
March | 21.40 | 4.82 |
April | 21.32 | 6.08 |
May | 21.63 | 13.74 |
June | 22.03 | 22.16 |
July | 22.05 | 22.71 |
August | 22.04 | 21.74 |
September | 22.01 | 18.54 |
October | 21.51 | 7.12 |
November | 21.22 | 3.03 |
December | 20.95 | -1.0 |
Annual Sum or Average | 21.53 | 10.02 |
Minimum of Months | 20.95 | -1.0 |
Maximum of Months | 22.05 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 0.85 |
February | 19.53 | -0.2 |
March | 19.62 | 4.82 |
April | 19.53 | 6.08 |
May | 19.54 | 13.74 |
June | 19.61 | 22.16 |
July | 19.46 | 22.71 |
August | 19.59 | 21.74 |
September | 19.57 | 18.54 |
October | 19.53 | 7.12 |
November | 19.52 | 3.03 |
December | 19.50 | -1.0 |
Annual Sum or Average | 19.54 | 10.02 |
Minimum of Months | 19.46 | -1.0 |
Maximum of Months | 19.62 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 0.85 |
February | 19.47 | -0.2 |
March | 19.58 | 4.82 |
April | 19.51 | 6.08 |
May | 19.57 | 13.74 |
June | 19.69 | 22.16 |
July | 19.54 | 22.71 |
August | 19.64 | 21.74 |
September | 19.62 | 18.54 |
October | 19.50 | 7.12 |
November | 19.47 | 3.03 |
December | 19.44 | -1.0 |
Annual Sum or Average | 19.54 | 10.02 |
Minimum of Months | 19.44 | -1.0 |
Maximum of Months | 19.69 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 0.85 |
February | 19.48 | -0.2 |
March | 19.56 | 4.82 |
April | 19.48 | 6.08 |
May | 19.50 | 13.74 |
June | 19.56 | 22.16 |
July | 19.42 | 22.71 |
August | 19.55 | 21.74 |
September | 19.51 | 18.54 |
October | 19.47 | 7.12 |
November | 19.47 | 3.03 |
December | 19.44 | -1.0 |
Annual Sum or Average | 19.49 | 10.02 |
Minimum of Months | 19.42 | -1.0 |
Maximum of Months | 19.56 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 0.85 |
February | 19.92 | -0.2 |
March | 20.07 | 4.82 |
April | 19.87 | 6.08 |
May | 20.01 | 13.74 |
June | 20.44 | 22.16 |
July | 20.24 | 22.71 |
August | 20.38 | 21.74 |
September | 20.42 | 18.54 |
October | 20.12 | 7.12 |
November | 20.00 | 3.03 |
December | 19.80 | -1.0 |
Annual Sum or Average | 20.10 | 10.02 |
Minimum of Months | 19.80 | -1.0 |
Maximum of Months | 20.44 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.22 | 0.85 |
February | 21.24 | -0.2 |
March | 21.42 | 4.82 |
April | 21.30 | 6.08 |
May | 21.55 | 13.74 |
June | 21.95 | 22.16 |
July | 21.95 | 22.71 |
August | 21.98 | 21.74 |
September | 21.95 | 18.54 |
October | 21.53 | 7.12 |
November | 21.38 | 3.03 |
December | 21.15 | -1.0 |
Annual Sum or Average | 21.55 | 10.02 |
Minimum of Months | 21.15 | -1.0 |
Maximum of Months | 21.98 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 0.85 |
February | 21.56 | -0.2 |
March | 21.71 | 4.82 |
April | 21.64 | 6.08 |
May | 21.68 | 13.74 |
June | 21.98 | 22.16 |
July | 21.98 | 22.71 |
August | 22.02 | 21.74 |
September | 22.01 | 18.54 |
October | 21.77 | 7.12 |
November | 21.67 | 3.03 |
December | 21.56 | -1.0 |
Annual Sum or Average | 21.76 | 10.02 |
Minimum of Months | 21.51 | -1.0 |
Maximum of Months | 22.02 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.43 | 0.85 |
February | 19.45 | -0.2 |
March | 19.69 | 4.82 |
April | 19.79 | 6.08 |
May | 20.54 | 13.74 |
June | 21.64 | 22.16 |
July | 21.66 | 22.71 |
August | 21.53 | 21.74 |
September | 21.13 | 18.54 |
October | 19.73 | 7.12 |
November | 19.48 | 3.03 |
December | 19.36 | -1.0 |
Annual Sum or Average | 20.29 | 10.02 |
Minimum of Months | 19.36 | -1.0 |
Maximum of Months | 21.66 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.17 | 0.85 |
February | 20.29 | -0.2 |
March | 20.74 | 4.82 |
April | 20.68 | 6.08 |
May | 21.30 | 13.74 |
June | 21.91 | 22.16 |
July | 21.93 | 22.71 |
August | 21.87 | 21.74 |
September | 21.77 | 18.54 |
October | 20.90 | 7.12 |
November | 20.42 | 3.03 |
December | 20.03 | -1.0 |
Annual Sum or Average | 21.00 | 10.02 |
Minimum of Months | 20.03 | -1.0 |
Maximum of Months | 21.93 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | 0.85 |
February | 19.60 | -0.2 |
March | 19.94 | 4.82 |
April | 20.04 | 6.08 |
May | 20.82 | 13.74 |
June | 21.79 | 22.16 |
July | 21.80 | 22.71 |
August | 21.72 | 21.74 |
September | 21.39 | 18.54 |
October | 20.05 | 7.12 |
November | 19.68 | 3.03 |
December | 19.53 | -1.0 |
Annual Sum or Average | 20.50 | 10.02 |
Minimum of Months | 19.53 | -1.0 |
Maximum of Months | 21.80 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 0.85 |
February | 21.04 | -0.2 |
March | 21.34 | 4.82 |
April | 21.29 | 6.08 |
May | 21.60 | 13.74 |
June | 22.03 | 22.16 |
July | 22.05 | 22.71 |
August | 22.04 | 21.74 |
September | 21.99 | 18.54 |
October | 21.46 | 7.12 |
November | 21.17 | 3.03 |
December | 20.91 | -1.0 |
Annual Sum or Average | 21.49 | 10.02 |
Minimum of Months | 20.91 | -1.0 |
Maximum of Months | 22.05 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.94 | 0.85 |
February | 20.00 | -0.2 |
March | 20.46 | 4.82 |
April | 20.48 | 6.08 |
May | 21.15 | 13.74 |
June | 21.91 | 22.16 |
July | 21.93 | 22.71 |
August | 21.88 | 21.74 |
September | 21.70 | 18.54 |
October | 20.64 | 7.12 |
November | 20.15 | 3.03 |
December | 19.86 | -1.0 |
Annual Sum or Average | 20.84 | 10.02 |
Minimum of Months | 19.86 | -1.0 |
Maximum of Months | 21.93 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 14.26 | 0.85 |
February | 13.82 | -0.2 |
March | 15.62 | 4.82 |
April | 16.59 | 6.08 |
May | 18.87 | 13.74 |
June | 22.82 | 22.16 |
July | 22.50 | 22.71 |
August | 22.46 | 21.74 |
September | 21.17 | 18.54 |
October | 16.39 | 7.12 |
November | 14.69 | 3.03 |
December | 13.54 | -1.0 |
Annual Sum or Average | 17.75 | 10.02 |
Minimum of Months | 13.54 | -1.0 |
Maximum of Months | 22.82 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.80 | 0.85 |
February | 20.80 | -0.2 |
March | 20.97 | 4.82 |
April | 20.68 | 6.08 |
May | 21.09 | 13.74 |
June | 21.41 | 22.16 |
July | 21.35 | 22.71 |
August | 21.45 | 21.74 |
September | 21.38 | 18.54 |
October | 21.04 | 7.12 |
November | 20.91 | 3.03 |
December | 20.56 | -1.0 |
Annual Sum or Average | 21.04 | 10.02 |
Minimum of Months | 20.56 | -1.0 |
Maximum of Months | 21.45 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.73 | 0.85 |
February | 19.73 | -0.2 |
March | 19.82 | 4.82 |
April | 19.72 | 6.08 |
May | 19.69 | 13.74 |
June | 19.60 | 22.16 |
July | 19.48 | 22.71 |
August | 19.60 | 21.74 |
September | 19.62 | 18.54 |
October | 19.73 | 7.12 |
November | 19.74 | 3.03 |
December | 19.67 | -1.0 |
Annual Sum or Average | 19.68 | 10.02 |
Minimum of Months | 19.48 | -1.0 |
Maximum of Months | 19.82 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.67 | 0.85 |
February | 21.69 | -0.2 |
March | 21.81 | 4.82 |
April | 21.71 | 6.08 |
May | 21.74 | 13.74 |
June | 21.82 | 22.16 |
July | 21.72 | 22.71 |
August | 21.85 | 21.74 |
September | 21.80 | 18.54 |
October | 21.77 | 7.12 |
November | 21.76 | 3.03 |
December | 21.65 | -1.0 |
Annual Sum or Average | 21.75 | 10.02 |
Minimum of Months | 21.65 | -1.0 |
Maximum of Months | 21.85 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.91 | 0.85 |
February | 19.94 | -0.2 |
March | 20.16 | 4.82 |
April | 20.03 | 6.08 |
May | 20.21 | 13.74 |
June | 20.52 | 22.16 |
July | 20.31 | 22.71 |
August | 20.48 | 21.74 |
September | 20.40 | 18.54 |
October | 20.17 | 7.12 |
November | 19.99 | 3.03 |
December | 19.75 | -1.0 |
Annual Sum or Average | 20.16 | 10.02 |
Minimum of Months | 19.75 | -1.0 |
Maximum of Months | 20.52 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.16 | 0.85 |
February | 20.19 | -0.2 |
March | 20.22 | 4.82 |
April | 19.99 | 6.08 |
May | 19.95 | 13.74 |
June | 19.88 | 22.16 |
July | 19.73 | 22.71 |
August | 19.92 | 21.74 |
September | 19.96 | 18.54 |
October | 20.15 | 7.12 |
November | 20.20 | 3.03 |
December | 20.02 | -1.0 |
Annual Sum or Average | 20.03 | 10.02 |
Minimum of Months | 19.73 | -1.0 |
Maximum of Months | 20.22 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 0.85 |
February | 20.13 | -0.2 |
March | 20.12 | 4.82 |
April | 19.90 | 6.08 |
May | 19.84 | 13.74 |
June | 19.77 | 22.16 |
July | 19.62 | 22.71 |
August | 19.79 | 21.74 |
September | 19.82 | 18.54 |
October | 20.03 | 7.12 |
November | 20.12 | 3.03 |
December | 19.96 | -1.0 |
Annual Sum or Average | 19.93 | 10.02 |
Minimum of Months | 19.62 | -1.0 |
Maximum of Months | 20.13 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | 0.85 |
February | 20.50 | -0.2 |
March | 20.46 | 4.82 |
April | 20.18 | 6.08 |
May | 20.23 | 13.74 |
June | 20.36 | 22.16 |
July | 20.23 | 22.71 |
August | 20.48 | 21.74 |
September | 20.52 | 18.54 |
October | 20.52 | 7.12 |
November | 20.56 | 3.03 |
December | 20.27 | -1.0 |
Annual Sum or Average | 20.40 | 10.02 |
Minimum of Months | 20.18 | -1.0 |
Maximum of Months | 20.56 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.70 | 0.85 |
February | 19.79 | -0.2 |
March | 20.10 | 4.82 |
April | 20.07 | 6.08 |
May | 20.31 | 13.74 |
June | 20.54 | 22.16 |
July | 20.37 | 22.71 |
August | 20.44 | 21.74 |
September | 20.23 | 18.54 |
October | 20.00 | 7.12 |
November | 19.78 | 3.03 |
December | 19.60 | -1.0 |
Annual Sum or Average | 20.08 | 10.02 |
Minimum of Months | 19.60 | -1.0 |
Maximum of Months | 20.54 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.64 | 0.85 |
February | 19.65 | -0.2 |
March | 19.86 | 4.82 |
April | 19.85 | 6.08 |
May | 20.00 | 13.74 |
June | 20.13 | 22.16 |
July | 19.98 | 22.71 |
August | 20.03 | 21.74 |
September | 19.90 | 18.54 |
October | 19.78 | 7.12 |
November | 19.68 | 3.03 |
December | 19.58 | -1.0 |
Annual Sum or Average | 19.84 | 10.02 |
Minimum of Months | 19.58 | -1.0 |
Maximum of Months | 20.13 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.81 | 0.85 |
February | 19.84 | -0.2 |
March | 20.02 | 4.82 |
April | 19.95 | 6.08 |
May | 19.96 | 13.74 |
June | 19.87 | 22.16 |
July | 19.72 | 22.71 |
August | 19.84 | 21.74 |
September | 19.82 | 18.54 |
October | 19.89 | 7.12 |
November | 19.86 | 3.03 |
December | 19.76 | -1.0 |
Annual Sum or Average | 19.86 | 10.02 |
Minimum of Months | 19.72 | -1.0 |
Maximum of Months | 20.02 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.70 | 0.85 |
February | 19.71 | -0.2 |
March | 19.94 | 4.82 |
April | 19.92 | 6.08 |
May | 20.07 | 13.74 |
June | 20.15 | 22.16 |
July | 19.99 | 22.71 |
August | 20.05 | 21.74 |
September | 19.93 | 18.54 |
October | 19.85 | 7.12 |
November | 19.75 | 3.03 |
December | 19.63 | -1.0 |
Annual Sum or Average | 19.89 | 10.02 |
Minimum of Months | 19.63 | -1.0 |
Maximum of Months | 20.15 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 0.85 |
February | 19.95 | -0.2 |
March | 20.17 | 4.82 |
April | 20.11 | 6.08 |
May | 20.15 | 13.74 |
June | 20.07 | 22.16 |
July | 19.92 | 22.71 |
August | 20.03 | 21.74 |
September | 20.00 | 18.54 |
October | 20.05 | 7.12 |
November | 19.98 | 3.03 |
December | 19.86 | -1.0 |
Annual Sum or Average | 20.02 | 10.02 |
Minimum of Months | 19.86 | -1.0 |
Maximum of Months | 20.17 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.13 | 0.85 |
February | 21.14 | -0.2 |
March | 21.31 | 4.82 |
April | 21.14 | 6.08 |
May | 21.41 | 13.74 |
June | 21.70 | 22.16 |
July | 21.58 | 22.71 |
August | 21.72 | 21.74 |
September | 21.67 | 18.54 |
October | 21.37 | 7.12 |
November | 21.25 | 3.03 |
December | 20.97 | -1.0 |
Annual Sum or Average | 21.37 | 10.02 |
Minimum of Months | 20.97 | -1.0 |
Maximum of Months | 21.72 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.32 | 0.85 |
February | 21.30 | -0.2 |
March | 21.41 | 4.82 |
April | 21.23 | 6.08 |
May | 21.39 | 13.74 |
June | 21.57 | 22.16 |
July | 21.45 | 22.71 |
August | 21.62 | 21.74 |
September | 21.59 | 18.54 |
October | 21.44 | 7.12 |
November | 21.41 | 3.03 |
December | 21.20 | -1.0 |
Annual Sum or Average | 21.41 | 10.02 |
Minimum of Months | 21.20 | -1.0 |
Maximum of Months | 21.62 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.33 | 0.85 |
February | 21.30 | -0.2 |
March | 21.39 | 4.82 |
April | 21.20 | 6.08 |
May | 21.32 | 13.74 |
June | 21.50 | 22.16 |
July | 21.38 | 22.71 |
August | 21.56 | 21.74 |
September | 21.55 | 18.54 |
October | 21.41 | 7.12 |
November | 21.42 | 3.03 |
December | 21.22 | -1.0 |
Annual Sum or Average | 21.38 | 10.02 |
Minimum of Months | 21.20 | -1.0 |
Maximum of Months | 21.56 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.99 | 0.85 |
February | 21.07 | -0.2 |
March | 21.38 | 4.82 |
April | 21.36 | 6.08 |
May | 21.58 | 13.74 |
June | 21.76 | 22.16 |
July | 21.65 | 22.71 |
August | 21.72 | 21.74 |
September | 21.59 | 18.54 |
October | 21.33 | 7.12 |
November | 21.18 | 3.03 |
December | 20.94 | -1.0 |
Annual Sum or Average | 21.38 | 10.02 |
Minimum of Months | 20.94 | -1.0 |
Maximum of Months | 21.76 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 0.85 |
February | 21.13 | -0.2 |
March | 21.46 | 4.82 |
April | 21.45 | 6.08 |
May | 21.68 | 13.74 |
June | 21.86 | 22.16 |
July | 21.77 | 22.71 |
August | 21.83 | 21.74 |
September | 21.70 | 18.54 |
October | 21.42 | 7.12 |
November | 21.24 | 3.03 |
December | 20.99 | -1.0 |
Annual Sum or Average | 21.47 | 10.02 |
Minimum of Months | 20.99 | -1.0 |
Maximum of Months | 21.86 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.94 | 0.85 |
February | 21.04 | -0.2 |
March | 21.39 | 4.82 |
April | 21.38 | 6.08 |
May | 21.63 | 13.74 |
June | 21.83 | 22.16 |
July | 21.73 | 22.71 |
August | 21.79 | 21.74 |
September | 21.65 | 18.54 |
October | 21.35 | 7.12 |
November | 21.15 | 3.03 |
December | 20.89 | -1.0 |
Annual Sum or Average | 21.40 | 10.02 |
Minimum of Months | 20.89 | -1.0 |
Maximum of Months | 21.83 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.41 | 0.85 |
February | 20.42 | -0.2 |
March | 20.82 | 4.82 |
April | 20.78 | 6.08 |
May | 21.33 | 13.74 |
June | 21.79 | 22.16 |
July | 21.73 | 22.71 |
August | 21.74 | 21.74 |
September | 21.53 | 18.54 |
October | 20.86 | 7.12 |
November | 20.57 | 3.03 |
December | 20.22 | -1.0 |
Annual Sum or Average | 21.02 | 10.02 |
Minimum of Months | 20.22 | -1.0 |
Maximum of Months | 21.79 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.82 | 0.85 |
February | 21.86 | -0.2 |
March | 21.95 | 4.82 |
April | 21.89 | 6.08 |
May | 21.94 | 13.74 |
June | 21.98 | 22.16 |
July | 21.92 | 22.71 |
August | 22.00 | 21.74 |
September | 21.95 | 18.54 |
October | 21.93 | 7.12 |
November | 21.90 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 21.91 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 22.00 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 0.85 |
February | 21.68 | -0.2 |
March | 21.85 | 4.82 |
April | 21.81 | 6.08 |
May | 21.89 | 13.74 |
June | 21.94 | 22.16 |
July | 21.87 | 22.71 |
August | 21.94 | 21.74 |
September | 21.88 | 18.54 |
October | 21.81 | 7.12 |
November | 21.74 | 3.03 |
December | 21.59 | -1.0 |
Annual Sum or Average | 21.80 | 10.02 |
Minimum of Months | 21.59 | -1.0 |
Maximum of Months | 21.94 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.59 | 0.85 |
February | 21.69 | -0.2 |
March | 21.87 | 4.82 |
April | 21.84 | 6.08 |
May | 21.93 | 13.74 |
June | 21.99 | 22.16 |
July | 21.92 | 22.71 |
August | 21.98 | 21.74 |
September | 21.91 | 18.54 |
October | 21.83 | 7.12 |
November | 21.75 | 3.03 |
December | 21.60 | -1.0 |
Annual Sum or Average | 21.82 | 10.02 |
Minimum of Months | 21.59 | -1.0 |
Maximum of Months | 21.99 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.56 | 0.85 |
February | 20.65 | -0.2 |
March | 21.07 | 4.82 |
April | 21.01 | 6.08 |
May | 21.65 | 13.74 |
June | 22.00 | 22.16 |
July | 21.97 | 22.71 |
August | 21.96 | 21.74 |
September | 21.82 | 18.54 |
October | 21.16 | 7.12 |
November | 20.74 | 3.03 |
December | 20.35 | -1.0 |
Annual Sum or Average | 21.25 | 10.02 |
Minimum of Months | 20.35 | -1.0 |
Maximum of Months | 22.00 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.16 | 0.85 |
February | 21.25 | -0.2 |
March | 21.54 | 4.82 |
April | 21.49 | 6.08 |
May | 21.80 | 13.74 |
June | 22.01 | 22.16 |
July | 21.99 | 22.71 |
August | 22.00 | 21.74 |
September | 21.91 | 18.54 |
October | 21.57 | 7.12 |
November | 21.32 | 3.03 |
December | 21.06 | -1.0 |
Annual Sum or Average | 21.59 | 10.02 |
Minimum of Months | 21.06 | -1.0 |
Maximum of Months | 22.01 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 0.85 |
February | 21.01 | -0.2 |
March | 21.25 | 4.82 |
April | 21.04 | 6.08 |
May | 21.50 | 13.74 |
June | 21.78 | 22.16 |
July | 21.69 | 22.71 |
August | 21.78 | 21.74 |
September | 21.70 | 18.54 |
October | 21.33 | 7.12 |
November | 21.21 | 3.03 |
December | 20.85 | -1.0 |
Annual Sum or Average | 21.35 | 10.02 |
Minimum of Months | 20.85 | -1.0 |
Maximum of Months | 21.78 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 0.85 |
February | 21.68 | -0.2 |
March | 21.81 | 4.82 |
April | 21.72 | 6.08 |
May | 21.83 | 13.74 |
June | 21.94 | 22.16 |
July | 21.86 | 22.71 |
August | 21.95 | 21.74 |
September | 21.91 | 18.54 |
October | 21.80 | 7.12 |
November | 21.76 | 3.03 |
December | 21.61 | -1.0 |
Annual Sum or Average | 21.79 | 10.02 |
Minimum of Months | 21.61 | -1.0 |
Maximum of Months | 21.95 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.70 | 0.85 |
February | 19.71 | -0.2 |
March | 19.80 | 4.82 |
April | 19.71 | 6.08 |
May | 19.67 | 13.74 |
June | 19.56 | 22.16 |
July | 19.45 | 22.71 |
August | 19.56 | 21.74 |
September | 19.59 | 18.54 |
October | 19.71 | 7.12 |
November | 19.72 | 3.03 |
December | 19.65 | -1.0 |
Annual Sum or Average | 19.65 | 10.02 |
Minimum of Months | 19.45 | -1.0 |
Maximum of Months | 19.80 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 0.85 |
February | 21.88 | -0.2 |
March | 21.98 | 4.82 |
April | 21.94 | 6.08 |
May | 22.00 | 13.74 |
June | 22.06 | 22.16 |
July | 22.02 | 22.71 |
August | 22.07 | 21.74 |
September | 22.02 | 18.54 |
October | 21.97 | 7.12 |
November | 21.93 | 3.03 |
December | 21.82 | -1.0 |
Annual Sum or Average | 21.96 | 10.02 |
Minimum of Months | 21.81 | -1.0 |
Maximum of Months | 22.07 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.81 | 0.85 |
February | 21.86 | -0.2 |
March | 21.96 | 4.82 |
April | 21.90 | 6.08 |
May | 21.99 | 13.74 |
June | 22.05 | 22.16 |
July | 22.01 | 22.71 |
August | 22.06 | 21.74 |
September | 22.02 | 18.54 |
October | 21.96 | 7.12 |
November | 21.92 | 3.03 |
December | 21.80 | -1.0 |
Annual Sum or Average | 21.95 | 10.02 |
Minimum of Months | 21.80 | -1.0 |
Maximum of Months | 22.06 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 0.85 |
February | 20.97 | -0.2 |
March | 21.04 | 4.82 |
April | 20.85 | 6.08 |
May | 20.89 | 13.74 |
June | 21.02 | 22.16 |
July | 20.91 | 22.71 |
August | 21.10 | 21.74 |
September | 21.10 | 18.54 |
October | 21.06 | 7.12 |
November | 21.08 | 3.03 |
December | 20.95 | -1.0 |
Annual Sum or Average | 21.00 | 10.02 |
Minimum of Months | 20.85 | -1.0 |
Maximum of Months | 21.10 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.70 | 0.85 |
February | 20.79 | -0.2 |
March | 21.06 | 4.82 |
April | 21.05 | 6.08 |
May | 21.23 | 13.74 |
June | 21.41 | 22.16 |
July | 21.29 | 22.71 |
August | 21.36 | 21.74 |
September | 21.24 | 18.54 |
October | 21.02 | 7.12 |
November | 20.87 | 3.03 |
December | 20.66 | -1.0 |
Annual Sum or Average | 21.06 | 10.02 |
Minimum of Months | 20.66 | -1.0 |
Maximum of Months | 21.41 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.74 | 0.85 |
February | 20.83 | -0.2 |
March | 21.15 | 4.82 |
April | 21.17 | 6.08 |
May | 21.37 | 13.74 |
June | 21.57 | 22.16 |
July | 21.45 | 22.71 |
August | 21.51 | 21.74 |
September | 21.36 | 18.54 |
October | 21.12 | 7.12 |
November | 20.94 | 3.03 |
December | 20.70 | -1.0 |
Annual Sum or Average | 21.16 | 10.02 |
Minimum of Months | 20.70 | -1.0 |
Maximum of Months | 21.57 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.10 | 0.85 |
February | 20.25 | -0.2 |
March | 20.73 | 4.82 |
April | 20.71 | 6.08 |
May | 21.39 | 13.74 |
June | 21.85 | 22.16 |
July | 21.81 | 22.71 |
August | 21.78 | 21.74 |
September | 21.56 | 18.54 |
October | 20.81 | 7.12 |
November | 20.30 | 3.03 |
December | 19.94 | -1.0 |
Annual Sum or Average | 20.94 | 10.02 |
Minimum of Months | 19.94 | -1.0 |
Maximum of Months | 21.85 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.36 | 0.85 |
February | 21.45 | -0.2 |
March | 21.72 | 4.82 |
April | 21.69 | 6.08 |
May | 21.96 | 13.74 |
June | 22.11 | 22.16 |
July | 22.08 | 22.71 |
August | 22.09 | 21.74 |
September | 22.01 | 18.54 |
October | 21.74 | 7.12 |
November | 21.58 | 3.03 |
December | 21.30 | -1.0 |
Annual Sum or Average | 21.76 | 10.02 |
Minimum of Months | 21.30 | -1.0 |
Maximum of Months | 22.11 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 0.85 |
February | 21.69 | -0.2 |
March | 21.87 | 4.82 |
April | 21.81 | 6.08 |
May | 21.97 | 13.74 |
June | 22.08 | 22.16 |
July | 22.05 | 22.71 |
August | 22.09 | 21.74 |
September | 22.03 | 18.54 |
October | 21.87 | 7.12 |
November | 21.79 | 3.03 |
December | 21.60 | -1.0 |
Annual Sum or Average | 21.87 | 10.02 |
Minimum of Months | 21.60 | -1.0 |
Maximum of Months | 22.09 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 0.85 |
February | 19.51 | -0.2 |
March | 19.67 | 4.82 |
April | 19.61 | 6.08 |
May | 19.66 | 13.74 |
June | 19.68 | 22.16 |
July | 19.53 | 22.71 |
August | 19.65 | 21.74 |
September | 19.60 | 18.54 |
October | 19.59 | 7.12 |
November | 19.53 | 3.03 |
December | 19.45 | -1.0 |
Annual Sum or Average | 19.58 | 10.02 |
Minimum of Months | 19.45 | -1.0 |
Maximum of Months | 19.68 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.41 | 0.85 |
February | 22.46 | -0.2 |
March | 22.42 | 4.82 |
April | 22.36 | 6.08 |
May | 22.28 | 13.74 |
June | 22.19 | 22.16 |
July | 22.18 | 22.71 |
August | 22.19 | 21.74 |
September | 22.21 | 18.54 |
October | 22.37 | 7.12 |
November | 22.42 | 3.03 |
December | 22.41 | -1.0 |
Annual Sum or Average | 22.32 | 10.02 |
Minimum of Months | 22.18 | -1.0 |
Maximum of Months | 22.46 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.92 | 0.85 |
February | 20.94 | -0.2 |
March | 21.21 | 4.82 |
April | 21.13 | 6.08 |
May | 21.39 | 13.74 |
June | 21.52 | 22.16 |
July | 21.41 | 22.71 |
August | 21.50 | 21.74 |
September | 21.38 | 18.54 |
October | 21.17 | 7.12 |
November | 21.06 | 3.03 |
December | 20.78 | -1.0 |
Annual Sum or Average | 21.20 | 10.02 |
Minimum of Months | 20.78 | -1.0 |
Maximum of Months | 21.52 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.30 | 0.85 |
February | 20.42 | -0.2 |
March | 20.89 | 4.82 |
April | 20.91 | 6.08 |
May | 21.55 | 13.74 |
June | 21.97 | 22.16 |
July | 21.94 | 22.71 |
August | 21.93 | 21.74 |
September | 21.72 | 18.54 |
October | 20.96 | 7.12 |
November | 20.55 | 3.03 |
December | 20.19 | -1.0 |
Annual Sum or Average | 21.12 | 10.02 |
Minimum of Months | 20.19 | -1.0 |
Maximum of Months | 21.97 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.04 | 0.85 |
February | 21.06 | -0.2 |
March | 21.33 | 4.82 |
April | 21.24 | 6.08 |
May | 21.52 | 13.74 |
June | 21.65 | 22.16 |
July | 21.55 | 22.71 |
August | 21.63 | 21.74 |
September | 21.52 | 18.54 |
October | 21.30 | 7.12 |
November | 21.19 | 3.03 |
December | 20.90 | -1.0 |
Annual Sum or Average | 21.33 | 10.02 |
Minimum of Months | 20.90 | -1.0 |
Maximum of Months | 21.65 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.58 | 0.85 |
February | 19.59 | -0.2 |
March | 19.95 | 4.82 |
April | 19.95 | 6.08 |
May | 20.53 | 13.74 |
June | 21.29 | 22.16 |
July | 21.20 | 22.71 |
August | 21.17 | 21.74 |
September | 20.81 | 18.54 |
October | 19.97 | 7.12 |
November | 19.65 | 3.03 |
December | 19.49 | -1.0 |
Annual Sum or Average | 20.27 | 10.02 |
Minimum of Months | 19.49 | -1.0 |
Maximum of Months | 21.29 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.07 | 0.85 |
February | 21.12 | -0.2 |
March | 21.44 | 4.82 |
April | 21.41 | 6.08 |
May | 21.78 | 13.74 |
June | 21.94 | 22.16 |
July | 21.88 | 22.71 |
August | 21.90 | 21.74 |
September | 21.78 | 18.54 |
October | 21.45 | 7.12 |
November | 21.27 | 3.03 |
December | 20.96 | -1.0 |
Annual Sum or Average | 21.50 | 10.02 |
Minimum of Months | 20.96 | -1.0 |
Maximum of Months | 21.94 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.09 | 0.85 |
February | 21.16 | -0.2 |
March | 21.51 | 4.82 |
April | 21.50 | 6.08 |
May | 21.91 | 13.74 |
June | 22.06 | 22.16 |
July | 22.03 | 22.71 |
August | 22.03 | 21.74 |
September | 21.93 | 18.54 |
October | 21.55 | 7.12 |
November | 21.32 | 3.03 |
December | 20.99 | -1.0 |
Annual Sum or Average | 21.59 | 10.02 |
Minimum of Months | 20.99 | -1.0 |
Maximum of Months | 22.06 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 0.85 |
February | 19.41 | -0.2 |
March | 19.51 | 4.82 |
April | 19.45 | 6.08 |
May | 19.48 | 13.74 |
June | 19.52 | 22.16 |
July | 19.42 | 22.71 |
August | 19.51 | 21.74 |
September | 19.43 | 18.54 |
October | 19.41 | 7.12 |
November | 19.41 | 3.03 |
December | 19.38 | -1.0 |
Annual Sum or Average | 19.44 | 10.02 |
Minimum of Months | 19.38 | -1.0 |
Maximum of Months | 19.52 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 24.94 | 0.85 |
February | 24.94 | -0.2 |
March | 24.89 | 4.82 |
April | 25.19 | 6.08 |
May | 25.25 | 13.74 |
June | 25.00 | 22.16 |
July | 25.28 | 22.71 |
August | 24.98 | 21.74 |
September | 25.21 | 18.54 |
October | 25.32 | 7.12 |
November | 25.11 | 3.03 |
December | 24.93 | -1.0 |
Annual Sum or Average | 25.09 | 10.02 |
Minimum of Months | 24.89 | -1.0 |
Maximum of Months | 25.32 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.93 | 0.85 |
February | 20.97 | -0.2 |
March | 21.35 | 4.82 |
April | 21.36 | 6.08 |
May | 21.90 | 13.74 |
June | 22.10 | 22.16 |
July | 22.09 | 22.71 |
August | 22.08 | 21.74 |
September | 21.98 | 18.54 |
October | 21.47 | 7.12 |
November | 21.15 | 3.03 |
December | 20.71 | -1.0 |
Annual Sum or Average | 21.51 | 10.02 |
Minimum of Months | 20.71 | -1.0 |
Maximum of Months | 22.10 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.56 | 0.85 |
February | 20.64 | -0.2 |
March | 21.12 | 4.82 |
April | 21.12 | 6.08 |
May | 21.71 | 13.74 |
June | 22.00 | 22.16 |
July | 21.97 | 22.71 |
August | 21.96 | 21.74 |
September | 21.79 | 18.54 |
October | 21.16 | 7.12 |
November | 20.81 | 3.03 |
December | 20.43 | -1.0 |
Annual Sum or Average | 21.28 | 10.02 |
Minimum of Months | 20.43 | -1.0 |
Maximum of Months | 22.00 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.66 | 0.85 |
February | 20.76 | -0.2 |
March | 21.14 | 4.82 |
April | 21.11 | 6.08 |
May | 21.66 | 13.74 |
June | 21.97 | 22.16 |
July | 21.93 | 22.71 |
August | 21.94 | 21.74 |
September | 21.78 | 18.54 |
October | 21.20 | 7.12 |
November | 20.92 | 3.03 |
December | 20.53 | -1.0 |
Annual Sum or Average | 21.30 | 10.02 |
Minimum of Months | 20.53 | -1.0 |
Maximum of Months | 21.97 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 0.85 |
February | 19.44 | -0.2 |
March | 19.56 | 4.82 |
April | 19.50 | 6.08 |
May | 19.53 | 13.74 |
June | 19.59 | 22.16 |
July | 19.46 | 22.71 |
August | 19.57 | 21.74 |
September | 19.49 | 18.54 |
October | 19.47 | 7.12 |
November | 19.44 | 3.03 |
December | 19.40 | -1.0 |
Annual Sum or Average | 19.49 | 10.02 |
Minimum of Months | 19.40 | -1.0 |
Maximum of Months | 19.59 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.97 | 0.85 |
February | 19.99 | -0.2 |
March | 20.04 | 4.82 |
April | 19.86 | 6.08 |
May | 19.90 | 13.74 |
June | 20.04 | 22.16 |
July | 19.90 | 22.71 |
August | 20.07 | 21.74 |
September | 20.00 | 18.54 |
October | 20.01 | 7.12 |
November | 20.02 | 3.03 |
December | 19.81 | -1.0 |
Annual Sum or Average | 19.97 | 10.02 |
Minimum of Months | 19.81 | -1.0 |
Maximum of Months | 20.07 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.88 | 0.85 |
February | 19.92 | -0.2 |
March | 20.07 | 4.82 |
April | 19.99 | 6.08 |
May | 20.00 | 13.74 |
June | 19.97 | 22.16 |
July | 19.78 | 22.71 |
August | 19.94 | 21.74 |
September | 19.86 | 18.54 |
October | 19.94 | 7.12 |
November | 19.91 | 3.03 |
December | 19.75 | -1.0 |
Annual Sum or Average | 19.92 | 10.02 |
Minimum of Months | 19.75 | -1.0 |
Maximum of Months | 20.07 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.54 | 0.85 |
February | 19.56 | -0.2 |
March | 19.68 | 4.82 |
April | 19.62 | 6.08 |
May | 19.61 | 13.74 |
June | 19.55 | 22.16 |
July | 19.44 | 22.71 |
August | 19.54 | 21.74 |
September | 19.51 | 18.54 |
October | 19.58 | 7.12 |
November | 19.56 | 3.03 |
December | 19.50 | -1.0 |
Annual Sum or Average | 19.56 | 10.02 |
Minimum of Months | 19.44 | -1.0 |
Maximum of Months | 19.68 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.79 | 0.85 |
February | 19.82 | -0.2 |
March | 20.02 | 4.82 |
April | 19.96 | 6.08 |
May | 20.10 | 13.74 |
June | 20.15 | 22.16 |
July | 20.03 | 22.71 |
August | 20.12 | 21.74 |
September | 20.02 | 18.54 |
October | 19.95 | 7.12 |
November | 19.86 | 3.03 |
December | 19.71 | -1.0 |
Annual Sum or Average | 19.96 | 10.02 |
Minimum of Months | 19.71 | -1.0 |
Maximum of Months | 20.15 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.37 | 0.85 |
February | 20.45 | -0.2 |
March | 20.85 | 4.82 |
April | 20.85 | 6.08 |
May | 21.37 | 13.74 |
June | 21.69 | 22.16 |
July | 21.62 | 22.71 |
August | 21.63 | 21.74 |
September | 21.43 | 18.54 |
October | 20.89 | 7.12 |
November | 20.59 | 3.03 |
December | 20.23 | -1.0 |
Annual Sum or Average | 21.00 | 10.02 |
Minimum of Months | 20.23 | -1.0 |
Maximum of Months | 21.69 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.01 | 0.85 |
February | 20.06 | -0.2 |
March | 20.23 | 4.82 |
April | 20.12 | 6.08 |
May | 20.15 | 13.74 |
June | 20.11 | 22.16 |
July | 19.91 | 22.71 |
August | 20.09 | 21.74 |
September | 20.01 | 18.54 |
October | 20.08 | 7.12 |
November | 20.06 | 3.03 |
December | 19.87 | -1.0 |
Annual Sum or Average | 20.06 | 10.02 |
Minimum of Months | 19.87 | -1.0 |
Maximum of Months | 20.23 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.57 | 0.85 |
February | 20.59 | -0.2 |
March | 20.89 | 4.82 |
April | 20.76 | 6.08 |
May | 21.38 | 13.74 |
June | 21.76 | 22.16 |
July | 21.70 | 22.71 |
August | 21.73 | 21.74 |
September | 21.59 | 18.54 |
October | 20.97 | 7.12 |
November | 20.75 | 3.03 |
December | 20.39 | -1.0 |
Annual Sum or Average | 21.09 | 10.02 |
Minimum of Months | 20.39 | -1.0 |
Maximum of Months | 21.76 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.47 | 0.85 |
February | 20.50 | -0.2 |
March | 20.80 | 4.82 |
April | 20.68 | 6.08 |
May | 21.39 | 13.74 |
June | 21.84 | 22.16 |
July | 21.80 | 22.71 |
August | 21.82 | 21.74 |
September | 21.65 | 18.54 |
October | 20.93 | 7.12 |
November | 20.67 | 3.03 |
December | 20.28 | -1.0 |
Annual Sum or Average | 21.07 | 10.02 |
Minimum of Months | 20.28 | -1.0 |
Maximum of Months | 21.84 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.08 | 0.85 |
February | 20.13 | -0.2 |
March | 20.44 | 4.82 |
April | 20.42 | 6.08 |
May | 20.80 | 13.74 |
June | 21.12 | 22.16 |
July | 21.01 | 22.71 |
August | 21.06 | 21.74 |
September | 20.83 | 18.54 |
October | 20.46 | 7.12 |
November | 20.25 | 3.03 |
December | 19.96 | -1.0 |
Annual Sum or Average | 20.55 | 10.02 |
Minimum of Months | 19.96 | -1.0 |
Maximum of Months | 21.12 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.24 | 0.85 |
February | 20.34 | -0.2 |
March | 20.76 | 4.82 |
April | 20.74 | 6.08 |
May | 21.45 | 13.74 |
June | 21.80 | 22.16 |
July | 21.78 | 22.71 |
August | 21.75 | 21.74 |
September | 21.56 | 18.54 |
October | 20.84 | 7.12 |
November | 20.42 | 3.03 |
December | 20.07 | -1.0 |
Annual Sum or Average | 20.98 | 10.02 |
Minimum of Months | 20.07 | -1.0 |
Maximum of Months | 21.80 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | 0.85 |
February | 19.54 | -0.2 |
March | 19.90 | 4.82 |
April | 19.91 | 6.08 |
May | 20.74 | 13.74 |
June | 21.55 | 22.16 |
July | 21.56 | 22.71 |
August | 21.44 | 21.74 |
September | 21.07 | 18.54 |
October | 20.00 | 7.12 |
November | 19.60 | 3.03 |
December | 19.42 | -1.0 |
Annual Sum or Average | 20.36 | 10.02 |
Minimum of Months | 19.42 | -1.0 |
Maximum of Months | 21.56 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.84 | 0.85 |
February | 19.86 | -0.2 |
March | 20.21 | 4.82 |
April | 20.15 | 6.08 |
May | 20.79 | 13.74 |
June | 21.48 | 22.16 |
July | 21.44 | 22.71 |
August | 21.42 | 21.74 |
September | 21.17 | 18.54 |
October | 20.33 | 7.12 |
November | 19.97 | 3.03 |
December | 19.69 | -1.0 |
Annual Sum or Average | 20.53 | 10.02 |
Minimum of Months | 19.69 | -1.0 |
Maximum of Months | 21.48 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.46 | 0.85 |
February | 19.50 | -0.2 |
March | 19.86 | 4.82 |
April | 19.93 | 6.08 |
May | 20.75 | 13.74 |
June | 21.57 | 22.16 |
July | 21.57 | 22.71 |
August | 21.46 | 21.74 |
September | 21.06 | 18.54 |
October | 19.91 | 7.12 |
November | 19.55 | 3.03 |
December | 19.41 | -1.0 |
Annual Sum or Average | 20.34 | 10.02 |
Minimum of Months | 19.41 | -1.0 |
Maximum of Months | 21.57 | 22.71 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2018-10-19 19:10:45
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.17 | 0.85 |
February | 20.14 | -0.2 |
March | 20.38 | 4.82 |
April | 20.25 | 6.08 |
May | 20.90 | 13.74 |
June | 21.54 | 22.16 |
July | 21.53 | 22.71 |
August | 21.54 | 21.74 |
September | 21.33 | 18.54 |
October | 20.54 | 7.12 |
November | 20.29 | 3.03 |
December | 19.96 | -1.0 |
Annual Sum or Average | 20.72 | 10.02 |
Minimum of Months | 19.96 | -1.0 |
Maximum of Months | 21.54 | 22.71 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2018-10-19 19:10:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.121896E+12 | 0.515485E+11 |
February | 0.119301E+12 | 0.436100E+11 |
March | 0.122126E+12 | 0.733158E+11 |
April | 0.101557E+12 | 0.741824E+11 |
May | 0.843416E+11 | 0.125479E+12 |
June | 0.707835E+11 | 0.187707E+12 |
July | 0.648736E+11 | 0.195960E+12 |
August | 0.647753E+11 | 0.193480E+12 |
September | 0.840861E+11 | 0.154738E+12 |
October | 0.107949E+12 | 0.837128E+11 |
November | 0.107621E+12 | 0.590702E+11 |
December | 0.144225E+12 | 0.453448E+11 |
Annual Sum or Average | 0.119354E+13 | 0.128815E+13 |
Minimum of Months | 0.647753E+11 | 0.436100E+11 |
Maximum of Months | 0.144225E+12 | 0.195960E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2018-10-19 19:10:45
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.443352E+11 | 0.559412E+10 |
February | 0.422349E+11 | 0.231063E+10 |
March | 0.387419E+11 | 0.167007E+11 |
April | 0.351799E+11 | 0.208430E+11 |
May | 0.284930E+11 | 0.710967E+11 |
June | 0.306994E+11 | 0.190343E+12 |
July | 0.309088E+11 | 0.202980E+12 |
August | 0.316030E+11 | 0.195198E+12 |
September | 0.289695E+11 | 0.131166E+12 |
October | 0.365214E+11 | 0.282306E+11 |
November | 0.376383E+11 | 0.101703E+11 |
December | 0.554106E+11 | 0.600836E+10 |
Annual Sum or Average | 0.440736E+12 | 0.880642E+12 |
Minimum of Months | 0.284930E+11 | 0.231063E+10 |
Maximum of Months | 0.554106E+11 | 0.202980E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2018-10-19 19:10:45
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.143020E+12 | 0.586414E+11 |
February | 0.136732E+12 | 0.571973E+11 |
March | 0.159542E+12 | 0.401993E+11 |
April | 0.139447E+12 | 0.356295E+11 |
May | 0.150114E+12 | 0.238054E+11 |
June | 0.190188E+12 | 0.218473E+11 |
July | 0.188393E+12 | 0.233079E+11 |
August | 0.185119E+12 | 0.246869E+11 |
September | 0.178173E+12 | 0.181158E+11 |
October | 0.152698E+12 | 0.344368E+11 |
November | 0.136327E+12 | 0.431818E+11 |
December | 0.162968E+12 | 0.725750E+11 |
Annual Sum or Average | 0.192272E+13 | 0.453624E+12 |
Minimum of Months | 0.136327E+12 | 0.181158E+11 |
Maximum of Months | 0.190188E+12 | 0.725750E+11 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:45
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.354520E+12 | 269940.342 | 20-JAN-14:20 | 35585.685 | 111201.830 | 31047.031 | 16505.507 | 46896.881 | 0.000 | 43.562 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.327694E+12 | 245331.866 | 17-FEB-14:09 | 35585.685 | 111201.830 | 32520.599 | 15302.257 | 26923.905 | 0.000 | 47.077 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.378406E+12 | 277938.708 | 15-MAR-14:30 | 35585.685 | 111201.830 | 34559.830 | 15405.782 | 48751.507 | 0.000 | 40.137 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.340916E+12 | 264251.404 | 12-APR-13:30 | 35585.685 | 111201.830 | 29855.549 | 16041.830 | 46571.937 | 0.000 | 36.976 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.361830E+12 | 270929.127 | 17-MAY-13:00 | 35585.685 | 111201.830 | 31146.861 | 15703.807 | 62650.506 | 0.000 | 33.305 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.398183E+12 | 338079.840 | 14-JUN-15:09 | 35585.685 | 111201.830 | 41406.304 | 27167.582 | 91765.158 | 0.000 | 8.884 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.391725E+12 | 327699.103 | 18-JUL-12:00 | 35585.685 | 111201.830 | 39512.150 | 27425.653 | 87363.610 | 0.000 | 11.994 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.402137E+12 | 345665.220 | 16-AUG-12:00 | 35585.685 | 111201.830 | 42197.380 | 27199.970 | 92550.638 | 0.000 | 9.689 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.380248E+12 | 311219.754 | 28-SEP-13:00 | 35585.685 | 111201.830 | 39650.854 | 23063.374 | 75766.641 | 0.000 | 21.765 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.362629E+12 | 280675.607 | 11-OCT-13:00 | 35585.685 | 111201.830 | 34038.533 | 15791.370 | 60638.425 | 0.000 | 32.786 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.342505E+12 | 271859.738 | 07-NOV-14:30 | 35585.685 | 111201.830 | 30962.408 | 16678.804 | 48891.667 | 0.000 | 36.208 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.371607E+12 | 265011.117 | 01-DEC-14:30 | 35585.685 | 111201.830 | 28727.245 | 17251.611 | 46346.242 | 0.000 | 38.569 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.441240E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.327694E+12 | 245331.866 | 35585.685 | 111201.830 | 28727.245 | 15302.257 | 26923.905 | 0.000 | 8.884 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.402137E+12 | 345665.220 | 35585.685 | 111201.830 | 42197.380 | 27425.653 | 92550.638 | 0.000 | 47.077 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:45
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.199310E+12 | 147082.42 | 02-JAN-16:30 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.180769E+12 | 147082.42 | 01-FEB-17:10 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.208877E+12 | 147082.42 | 01-MAR-17:19 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.193033E+12 | 147033.27 | 28-APR-16:00 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.204026E+12 | 146934.97 | 09-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.201050E+12 | 146934.97 | 23-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.195979E+12 | 146934.97 | 12-JUL-08:09 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.208840E+12 | 146934.97 | 07-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.193043E+12 | 147033.27 | 21-SEP-16:40 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.199281E+12 | 147082.42 | 02-OCT-16:49 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.194769E+12 | 147082.42 | 01-NOV-16:40 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.196073E+12 | 147082.42 | 01-DEC-16:19 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.237505E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.180769E+12 | 146934.97 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.208877E+12 | 147082.42 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:45
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.451566E+11 | 0.00 | 0.118847E+11 | 0.154153E+12 | 0.00 | 0.374594E+11 | 0.304989E+09 | 0.484480E+11 | 0.144088E+11 | 0.00 | 0.427043E+11 | 0.00 | 0.00 | 0.00 |
February | 0.410428E+11 | 0.00 | 0.989704E+10 | 0.139726E+12 | 0.00 | 0.345088E+11 | 0.296085E+09 | 0.461423E+11 | 0.116222E+11 | 0.00 | 0.444585E+11 | 0.00 | 0.00 | 0.00 |
March | 0.484873E+11 | 0.00 | 0.977530E+10 | 0.160390E+12 | 0.00 | 0.403297E+11 | 0.211164E+09 | 0.453583E+11 | 0.226174E+11 | 0.00 | 0.512365E+11 | 0.00 | 0.00 | 0.00 |
April | 0.437203E+11 | 0.00 | 0.826220E+10 | 0.149313E+12 | 0.00 | 0.374631E+11 | 0.174046E+09 | 0.412346E+11 | 0.237862E+11 | 0.00 | 0.369635E+11 | 0.00 | 0.00 | 0.00 |
May | 0.467543E+11 | 0.00 | 0.757166E+10 | 0.157272E+12 | 0.00 | 0.400984E+11 | 0.118745E+09 | 0.311165E+11 | 0.494181E+11 | 0.00 | 0.294810E+11 | 0.00 | 0.00 | 0.00 |
June | 0.465083E+11 | 0.00 | 0.685064E+10 | 0.154542E+12 | 0.00 | 0.443627E+11 | 93654716.23 | 0.262835E+11 | 0.993102E+11 | 0.00 | 0.202320E+11 | 0.00 | 0.00 | 0.00 |
July | 0.439357E+11 | 0.00 | 0.725623E+10 | 0.152043E+12 | 0.00 | 0.424792E+11 | 97929187.46 | 0.252617E+11 | 0.104174E+12 | 0.00 | 0.164775E+11 | 0.00 | 0.00 | 0.00 |
August | 0.484498E+11 | 0.00 | 0.807761E+10 | 0.160390E+12 | 0.00 | 0.452543E+11 | 0.100688E+09 | 0.224217E+11 | 0.101039E+12 | 0.00 | 0.164040E+11 | 0.00 | 0.00 | 0.00 |
September | 0.437305E+11 | 0.00 | 0.893823E+10 | 0.149313E+12 | 0.00 | 0.410440E+11 | 93607070.15 | 0.315882E+11 | 0.732410E+11 | 0.00 | 0.322997E+11 | 0.00 | 0.00 | 0.00 |
October | 0.451278E+11 | 0.00 | 0.104717E+11 | 0.154153E+12 | 0.00 | 0.395198E+11 | 0.178737E+09 | 0.423490E+11 | 0.281089E+11 | 0.00 | 0.427201E+11 | 0.00 | 0.00 | 0.00 |
November | 0.443535E+11 | 0.00 | 0.111900E+11 | 0.150416E+12 | 0.00 | 0.370706E+11 | 0.218617E+09 | 0.437672E+11 | 0.174281E+11 | 0.00 | 0.380610E+11 | 0.00 | 0.00 | 0.00 |
December | 0.440297E+11 | 0.00 | 0.121795E+11 | 0.152043E+12 | 0.00 | 0.359997E+11 | 0.386691E+09 | 0.578392E+11 | 0.129047E+11 | 0.00 | 0.562247E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541296E+12 | 0.00 | 0.112355E+12 | 0.183375E+13 | 0.00 | 0.475590E+12 | 0.227495E+10 | 0.461810E+12 | 0.558059E+12 | 0.00 | 0.427263E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.410428E+11 | 0.00 | 0.685064E+10 | 0.139726E+12 | 0.00 | 0.345088E+11 | 93607070.15 | 0.224217E+11 | 0.116222E+11 | 0.00 | 0.164040E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.484873E+11 | 0.00 | 0.121795E+11 | 0.160390E+12 | 0.00 | 0.452543E+11 | 0.386691E+09 | 0.578392E+11 | 0.104174E+12 | 0.00 | 0.562247E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:45
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.586414E+11 | 0.00 | 0.218220E+11 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.571973E+11 | 0.00 | 0.197943E+11 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.401993E+11 | 0.00 | 0.219703E+11 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.356295E+11 | 0.00 | 0.207357E+11 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.238054E+11 | 0.00 | 0.210368E+11 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.218473E+11 | 0.00 | 0.198936E+11 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.233079E+11 | 0.00 | 0.202066E+11 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.246869E+11 | 0.00 | 0.201271E+11 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.181158E+11 | 0.00 | 0.195666E+11 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.344368E+11 | 0.00 | 0.205528E+11 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.431818E+11 | 0.00 | 0.203874E+11 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.725750E+11 | 0.00 | 0.214421E+11 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.453624E+12 | 0.00 | 0.247535E+12 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.181158E+11 | 0.00 | 0.195666E+11 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.725750E+11 | 0.00 | 0.219703E+11 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:45
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35880.59 | 02-JAN-07:10 | 0.00 | 8471.50 | 01-JAN-06:10 | 111201.83 | 02-JAN-09:09 | 0.00 | 34277.80 | 27-JAN-14:50 | 498.59 | 05-JAN-06:10 | 74479.44 | 14-JAN-07:10 |
February | 35880.59 | 01-FEB-07:10 | 0.00 | 8471.50 | 01-FEB-06:10 | 111201.83 | 01-FEB-09:09 | 0.00 | 35679.90 | 23-FEB-15:30 | 388.64 | 11-FEB-17:00 | 76821.07 | 06-FEB-07:10 |
March | 35880.59 | 01-MAR-17:19 | 0.00 | 8471.50 | 01-MAR-06:10 | 111201.83 | 01-MAR-09:09 | 0.00 | 37690.51 | 30-MAR-14:00 | 383.26 | 19-MAR-07:49 | 65833.71 | 20-MAR-06:10 |
April | 35880.59 | 03-APR-06:10 | 0.00 | 8471.50 | 01-APR-05:10 | 111201.83 | 03-APR-08:09 | 0.00 | 35822.15 | 21-APR-13:30 | 326.55 | 17-APR-05:10 | 70216.31 | 03-APR-06:10 |
May | 35831.44 | 19-MAY-06:10 | 0.00 | 8471.50 | 01-MAY-18:49 | 111201.83 | 01-MAY-08:09 | 0.00 | 33227.72 | 25-MAY-16:00 | 154.13 | 01-MAY-06:10 | 48512.74 | 01-MAY-06:10 |
June | 35831.44 | 16-JUN-06:10 | 0.00 | 8471.50 | 01-JUN-19:19 | 111201.83 | 01-JUN-08:09 | 0.00 | 41484.41 | 30-JUN-15:39 | 150.83 | 17-JUN-06:10 | 40029.82 | 26-JUN-18:30 |
July | 35831.44 | 03-JUL-06:10 | 0.00 | 8471.50 | 01-JUL-19:30 | 111201.83 | 03-JUL-08:09 | 0.00 | 40152.71 | 07-JUL-14:30 | 149.67 | 29-JUL-06:10 | 38471.15 | 08-JUL-06:10 |
August | 35831.44 | 18-AUG-06:10 | 0.00 | 8471.50 | 01-AUG-19:10 | 111201.83 | 01-AUG-08:09 | 0.00 | 44135.66 | 16-AUG-15:09 | 135.09 | 05-AUG-06:10 | 38431.05 | 16-AUG-17:19 |
September | 35880.59 | 05-SEP-06:10 | 0.00 | 8471.50 | 01-SEP-05:10 | 111201.83 | 01-SEP-08:09 | 0.00 | 39757.86 | 28-SEP-14:30 | 161.47 | 22-SEP-05:10 | 46593.00 | 23-SEP-06:10 |
October | 35880.59 | 02-OCT-06:10 | 0.00 | 8471.50 | 01-OCT-05:10 | 111201.83 | 02-OCT-08:09 | 0.00 | 38065.52 | 12-OCT-14:00 | 357.71 | 30-OCT-05:10 | 70187.95 | 30-OCT-06:10 |
November | 35880.59 | 01-NOV-06:10 | 0.00 | 8471.50 | 01-NOV-05:10 | 111201.83 | 01-NOV-08:09 | 0.00 | 33850.08 | 16-NOV-15:30 | 384.56 | 29-NOV-23:30 | 63298.04 | 27-NOV-07:10 |
December | 35880.59 | 01-DEC-07:10 | 0.00 | 8471.50 | 01-DEC-06:10 | 111201.83 | 01-DEC-09:09 | 0.00 | 34463.38 | 15-DEC-14:39 | 498.59 | 19-DEC-06:10 | 108308.91 | 23-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 35831.44 | 0.00 | 8471.50 | 111201.83 | 0.00 | 33227.72 | 135.09 | 38431.05 | ||||||
Maximum of Months | 35880.59 | 0.00 | 8471.50 | 111201.83 | 0.00 | 44135.66 | 498.59 | 108308.91 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:45
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.354520E+12 | 269940.342 | 20-JAN-14:20 | 35585.685 | 111201.830 | 31047.031 | 16505.507 | 46896.881 | 0.000 | 43.562 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.327694E+12 | 245331.866 | 17-FEB-14:09 | 35585.685 | 111201.830 | 32520.599 | 15302.257 | 26923.905 | 0.000 | 47.077 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.378406E+12 | 277938.708 | 15-MAR-14:30 | 35585.685 | 111201.830 | 34559.830 | 15405.782 | 48751.507 | 0.000 | 40.137 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.340916E+12 | 264251.404 | 12-APR-13:30 | 35585.685 | 111201.830 | 29855.549 | 16041.830 | 46571.937 | 0.000 | 36.976 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.361830E+12 | 270929.127 | 17-MAY-13:00 | 35585.685 | 111201.830 | 31146.861 | 15703.807 | 62650.506 | 0.000 | 33.305 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.398183E+12 | 338079.840 | 14-JUN-15:09 | 35585.685 | 111201.830 | 41406.304 | 27167.582 | 91765.158 | 0.000 | 8.884 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.391725E+12 | 327699.103 | 18-JUL-12:00 | 35585.685 | 111201.830 | 39512.150 | 27425.653 | 87363.610 | 0.000 | 11.994 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.402137E+12 | 345665.220 | 16-AUG-12:00 | 35585.685 | 111201.830 | 42197.380 | 27199.970 | 92550.638 | 0.000 | 9.689 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.380248E+12 | 311219.754 | 28-SEP-13:00 | 35585.685 | 111201.830 | 39650.854 | 23063.374 | 75766.641 | 0.000 | 21.765 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.362629E+12 | 280675.607 | 11-OCT-13:00 | 35585.685 | 111201.830 | 34038.533 | 15791.370 | 60638.425 | 0.000 | 32.786 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.342505E+12 | 271859.738 | 07-NOV-14:30 | 35585.685 | 111201.830 | 30962.408 | 16678.804 | 48891.667 | 0.000 | 36.208 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.371607E+12 | 265011.117 | 01-DEC-14:30 | 35585.685 | 111201.830 | 28727.245 | 17251.611 | 46346.242 | 0.000 | 38.569 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.441240E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.327694E+12 | 245331.866 | 35585.685 | 111201.830 | 28727.245 | 15302.257 | 26923.905 | 0.000 | 8.884 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.402137E+12 | 345665.220 | 35585.685 | 111201.830 | 42197.380 | 27425.653 | 92550.638 | 0.000 | 47.077 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:45
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.963253E+11 | 129178.855 | 05-JAN-06:40 | 0.000 | 9905.768 | 0.000 | 119273.087 | 7514.610 | 7514.610 | 111758.477 |
February | 0.913628E+11 | 103242.816 | 11-FEB-17:00 | 0.000 | 4952.884 | 0.000 | 98289.932 | 7514.610 | 7514.610 | 90775.322 |
March | 0.785592E+11 | 103078.761 | 04-MAR-06:00 | 0.000 | 2971.730 | 0.000 | 100107.031 | 7514.610 | 7514.610 | 92592.421 |
April | 0.717350E+11 | 86598.375 | 17-APR-05:10 | 0.000 | 9905.768 | 0.000 | 76692.607 | 7514.610 | 7514.610 | 69177.997 |
May | 0.609680E+11 | 57266.776 | 22-MAY-06:10 | 0.000 | 9905.768 | 0.000 | 47361.008 | 7514.610 | 7514.610 | 39846.398 |
June | 0.575457E+11 | 56117.336 | 17-JUN-06:10 | 0.000 | 4952.884 | 0.000 | 51164.452 | 7514.610 | 7514.610 | 43649.842 |
July | 0.592052E+11 | 55691.167 | 29-JUL-06:10 | 0.000 | 4952.884 | 0.000 | 50738.283 | 7514.610 | 7514.610 | 43223.673 |
August | 0.612037E+11 | 50955.124 | 05-AUG-06:10 | 0.000 | 4952.884 | 0.000 | 46002.240 | 7514.610 | 7514.610 | 38487.630 |
September | 0.530522E+11 | 59238.789 | 22-SEP-05:10 | 0.000 | 9905.768 | 0.000 | 49333.021 | 7514.610 | 7514.610 | 41818.411 |
October | 0.708516E+11 | 93031.392 | 30-OCT-05:49 | 0.000 | 9905.768 | 0.000 | 83125.623 | 7514.610 | 7514.610 | 75611.013 |
November | 0.790174E+11 | 96479.291 | 30-NOV-06:49 | 0.000 | 9905.768 | 0.000 | 86573.523 | 7514.610 | 7514.610 | 79058.913 |
December | 0.109708E+12 | 142227.098 | 21-DEC-17:10 | 0.000 | 9905.768 | 0.000 | 132321.330 | 22660.143 | 22660.143 | 109661.186 |
Annual Sum or Average | 0.889534E+12 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.530522E+11 | 50955.124 | 0.000 | 2971.730 | 0.000 | 46002.240 | 7514.610 | 7514.610 | 38487.630 | |
Maximum of Months | 0.109708E+12 | 142227.098 | 0.000 | 9905.768 | 0.000 | 132321.330 | 22660.143 | 22660.143 | 111758.477 |