Program Version:EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09
Tabular Output Report in Format: HTML
Building: OutPatient HealthCare
Environment: San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2018-10-19 19:10:35
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 4840.99 | 1272.60 | 1272.60 |
Net Site Energy | 4840.99 | 1272.60 | 1272.60 |
Total Source Energy | 13355.35 | 3510.86 | 3510.86 |
Net Source Energy | 13355.35 | 3510.86 | 3510.86 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 3804.01 |
Net Conditioned Building Area | 3804.01 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 161.33 | 522.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 793.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 541.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 415.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 237.55 | 0.00 | 0.00 | 0.00 | 478.84 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 3892.33 | 948.66 | 0.00 | 0.00 | 0.00 | 490.87 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 522.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Other | 161.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 793.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 541.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 112.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | General | 1833.75 | 188.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Fan Energy | 374.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Zone Exhaust Fans | 40.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 1.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 32.34 | 0.00 | 0.00 | 0.00 | 0.00 | 12.03 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 237.55 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.84 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 369.26 | 199.86 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1023.22 | 249.38 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 171.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 369.26 | 199.86 | 0.00 | 0.00 | 0.00 | 0.13 |
Other | 482.06 | 49.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 1023.22 | 249.38 | 0.00 | 0.00 | 0.00 | 0.13 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.00 | 0.00 |
High Temperature Geothermal* | 0.00 | 0.00 |
Photovoltaic Power | 0.00 | 0.00 |
Wind Power | 0.00 | 0.00 |
Net Decrease in On-Site Storage | 0.00 | 0.00 |
Total On-Site Electric Sources | 0.00 | 0.00 |
Electricity Coming From Utility | 3892.33 | 100.00 |
Surplus Electricity Going To Utility | 0.00 | 0.00 |
Net Electricity From Utility | 3892.33 | 100.00 |
Total On-Site and Utility Electric Sources | 3892.33 | 100.00 |
Total Electricity End Uses | 3892.33 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 490.87 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 490.87 | 100.00 |
Total Water End Uses | 490.87 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.20 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.20 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 634.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 7830.00 |
Table of Contents
TopMONTHLY INDOOR TEMP
| FLOOR 1 ANESTHESIA | FLOOR 1 BIO HAZ | FLOOR 1 CAFE | FLOOR 1 CLEAN | FLOOR 1 CLEAN WORK | FLOOR 1 DICTATION | FLOOR 1 DRESSING ROOM | FLOOR 1 ELECTRICAL ROOM | FLOOR 1 ELEVATOR PUMP ROOM | FLOOR 1 HUMID | FLOOR 1 IT HALL | FLOOR 1 IT ROOM | FLOOR 1 LOBBY | FLOOR 1 LOBBY HALL | FLOOR 1 LOBBY TOILET | FLOOR 1 LOCKER ROOM | FLOOR 1 LOCKER ROOM HALL | FLOOR 1 LOUNGE | FLOOR 1 MED GAS | FLOOR 1 MRI CONTROL ROOM | FLOOR 1 MRI HALL | FLOOR 1 MRI ROOM | FLOOR 1 MRI TOILET | FLOOR 1 NOURISHMENT | FLOOR 1 NURSE HALL | FLOOR 1 NURSE JANITOR | FLOOR 1 NURSE STATION | FLOOR 1 NURSE TOILET | FLOOR 1 OFFICE | FLOOR 1 OPERATING ROOM 1 | FLOOR 1 OPERATING ROOM 2 | FLOOR 1 OPERATING ROOM 3 | FLOOR 1 PACU | FLOOR 1 PRE-OP HALL | FLOOR 1 PRE-OP ROOM 1 | FLOOR 1 PRE-OP ROOM 2 | FLOOR 1 PRE-OP TOILET | FLOOR 1 PROCEDURE ROOM | FLOOR 1 RECEPTION | FLOOR 1 RECEPTION HALL | FLOOR 1 RECOVERY ROOM | FLOOR 1 SCHEDULING | FLOOR 1 SCRUB | FLOOR 1 SOIL | FLOOR 1 SOIL HOLD | FLOOR 1 SOIL WORK | FLOOR 1 STEP DOWN | FLOOR 1 STERILE HALL | FLOOR 1 STERILE STORAGE | FLOOR 1 STORAGE | FLOOR 1 SUB-STERILE | FLOOR 1 UTILITY HALL | FLOOR 1 UTILITY JANITOR | FLOOR 1 UTILITY ROOM | FLOOR 1 VESTIBULE | FLOOR 2 CONFERENCE | FLOOR 2 CONFERENCE TOILET | FLOOR 2 DICTATION | FLOOR 2 EXAM 1 | FLOOR 2 EXAM 2 | FLOOR 2 EXAM 3 | FLOOR 2 EXAM 4 | FLOOR 2 EXAM 5 | FLOOR 2 EXAM 6 | FLOOR 2 EXAM 7 | FLOOR 2 EXAM 8 | FLOOR 2 EXAM 9 | FLOOR 2 EXAM HALL 1 | FLOOR 2 EXAM HALL 2 | FLOOR 2 EXAM HALL 3 | FLOOR 2 EXAM HALL 4 | FLOOR 2 EXAM HALL 5 | FLOOR 2 EXAM HALL 6 | FLOOR 2 JANITOR | FLOOR 2 LOUNGE | FLOOR 2 NURSE STATION 1 | FLOOR 2 NURSE STATION 2 | FLOOR 2 OFFICE | FLOOR 2 OFFICE HALL | FLOOR 2 RECEPTION | FLOOR 2 RECEPTION HALL | FLOOR 2 RECEPTION TOILET | FLOOR 2 SCHEDULING 1 | FLOOR 2 SCHEDULING 2 | FLOOR 2 STORAGE 1 | FLOOR 2 STORAGE 2 | FLOOR 2 STORAGE 3 | FLOOR 2 UTILITY | FLOOR 2 WORK | FLOOR 2 WORK HALL | FLOOR 2 WORK TOILET | FLOOR 2 X-RAY | FLOOR 3 DRESSING ROOM | FLOOR 3 ELEVATOR HALL | FLOOR 3 HUMID | FLOOR 3 JANITOR | FLOOR 3 LOCKER | FLOOR 3 LOUNGE | FLOOR 3 LOUNGE TOILET | FLOOR 3 MECHANICAL | FLOOR 3 MECHANICAL HALL | FLOOR 3 OFFICE | FLOOR 3 OFFICE HALL | FLOOR 3 OFFICE TOILET | FLOOR 3 PHYSICAL THERAPY 1 | FLOOR 3 PHYSICAL THERAPY 2 | FLOOR 3 PHYSICAL THERAPY TOILET | FLOOR 3 STORAGE 1 | FLOOR 3 STORAGE 2 | FLOOR 3 TREATMENT | FLOOR 3 UNDEVELOPED 1 | FLOOR 3 UNDEVELOPED 2 | FLOOR 3 UTILITY | FLOOR 3 WORK | NE STAIR | NW ELEVATOR | NW STAIR | SW STAIR |OVERALL HVAC AIR SYSTEM LOADS
| AHU-1 | AHU-2 |OVERALL HVAC SYSTEM ENERGY
| Meter |COMPONENTS OF PEAK ELECTRICAL DEMAND
| Meter |ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
| Meter |BUILDING ENERGY PERFORMANCE - ELECTRICITY
| Meter |BUILDING ENERGY PERFORMANCE - NATURAL GAS
| Meter |PEAK ENERGY END-USE - ELECTRICITY
| Meter |PEAK ELECTRICAL DEMAND
| Meter |PEAK GAS DEMAND
| Meter |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
GeneralValue | |
Program Version and Build | EnergyPlus-Linux--- 8.0.0.---, YMD=2018.10.19 19:09 |
RunPeriod | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1553.34 | 473.81 | 302.86 | 473.81 | 302.86 |
Window Opening Area [m2] | 308.29 | 97.22 | 57.97 | 114.08 | 39.02 |
Window-Wall Ratio [%] | 19.85 | 20.52 | 19.14 | 24.08 | 12.88 |
Total | |
Gross Roof Area [m2] | 1373.29 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Gross Wall Area [m2] | Window Glass Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
FLOOR 1 ANESTHESIA | 10.03 | Yes | Yes | 30.58 | 1.00 | 8.36 | 2.23 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 BIO HAZ | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 CAFE | 39.02 | Yes | Yes | 118.93 | 1.00 | 18.58 | 8.92 | 6.9965 | 0.93 | 10.7600 |
FLOOR 1 CLEAN | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 CLEAN WORK | 15.33 | Yes | Yes | 46.72 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 DICTATION | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 DRESSING ROOM | 4.18 | Yes | Yes | 12.74 | 1.00 | 8.36 | 2.32 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 ELECTRICAL ROOM | 9.10 | Yes | Yes | 27.75 | 1.00 | 6.50 | 0.00 | 17.8681 | 53.8200 | |
FLOOR 1 ELEVATOR PUMP ROOM | 8.45 | Yes | Yes | 25.77 | 1.00 | 18.58 | 0.00 | 17.8681 | 5734.7436 | |
FLOOR 1 HUMID | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 IT HALL | 13.01 | Yes | Yes | 39.64 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 IT ROOM | 10.41 | Yes | Yes | 31.71 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 LOBBY | 57.79 | Yes | Yes | 176.13 | 1.00 | 20.44 | 8.92 | 9.6875 | 9.29 | 11.8400 |
FLOOR 1 LOBBY HALL | 22.30 | Yes | Yes | 67.96 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOBBY TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 LOCKER ROOM | 61.32 | Yes | Yes | 186.89 | 1.00 | 20.44 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 LOCKER ROOM HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 LOUNGE | 33.45 | Yes | Yes | 101.94 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 1 MED GAS | 5.20 | Yes | Yes | 15.86 | 1.00 | 13.94 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 MRI CONTROL ROOM | 15.61 | Yes | Yes | 47.57 | 1.00 | 4.65 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI HALL | 13.66 | Yes | Yes | 41.63 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 MRI ROOM | 40.88 | Yes | Yes | 124.59 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 1 MRI TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 NOURISHMENT | 16.91 | Yes | Yes | 51.54 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE HALL | 46.08 | Yes | Yes | 140.45 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 NURSE JANITOR | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 NURSE STATION | 24.25 | Yes | Yes | 73.91 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 1 NURSE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 OFFICE | 44.87 | Yes | Yes | 136.77 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 OPERATING ROOM 1 | 42.74 | Yes | Yes | 130.26 | 1.00 | 39.95 | 8.92 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 2 | 44.59 | Yes | Yes | 135.92 | 1.00 | 22.30 | 6.69 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 OPERATING ROOM 3 | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 20.3438 | 4.64 | 118.3600 |
FLOOR 1 PACU | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 PRE-OP HALL | 49.05 | Yes | Yes | 149.51 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 PRE-OP ROOM 1 | 17.56 | Yes | Yes | 53.52 | 1.00 | 3.72 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP ROOM 2 | 31.40 | Yes | Yes | 95.71 | 1.00 | 0.00 | 0.00 | 6.6736 | 9.29 | 21.5300 |
FLOOR 1 PRE-OP TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 1 PROCEDURE ROOM | 26.48 | Yes | Yes | 80.70 | 1.00 | 17.65 | 5.57 | 24.3264 | 4.64 | 32.2900 |
FLOOR 1 RECEPTION | 47.29 | Yes | Yes | 144.13 | 1.00 | 12.08 | 3.34 | 9.6875 | 3.10 | 11.8400 |
FLOOR 1 RECEPTION HALL | 11.89 | Yes | Yes | 36.25 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 RECOVERY ROOM | 50.17 | Yes | Yes | 152.91 | 1.00 | 41.81 | 8.92 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 SCHEDULING | 11.06 | Yes | Yes | 33.70 | 1.00 | 6.50 | 0.74 | 11.9479 | 18.58 | 11.8400 |
FLOOR 1 SCRUB | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 SOIL | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL HOLD | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 SOIL WORK | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 21.5300 |
FLOOR 1 STEP DOWN | 27.87 | Yes | Yes | 84.95 | 1.00 | 34.37 | 6.69 | 12.3785 | 4.64 | 32.2900 |
FLOOR 1 STERILE HALL | 57.23 | Yes | Yes | 174.43 | 1.00 | 7.43 | 2.23 | 8.5250 | 4.3100 | |
FLOOR 1 STERILE STORAGE | 36.79 | Yes | Yes | 112.13 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 STORAGE | 85.47 | Yes | Yes | 260.51 | 1.00 | 58.53 | 8.36 | 6.7813 | 1.0800 | |
FLOOR 1 SUB-STERILE | 18.21 | Yes | Yes | 55.50 | 1.00 | 13.01 | 2.97 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY HALL | 23.78 | Yes | Yes | 72.49 | 1.00 | 14.86 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 1 UTILITY JANITOR | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 1 UTILITY ROOM | 33.45 | Yes | Yes | 101.94 | 1.00 | 16.72 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 1 VESTIBULE | 6.69 | Yes | Yes | 20.39 | 1.00 | 7.43 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 CONFERENCE | 31.22 | Yes | Yes | 95.14 | 1.00 | 37.16 | 8.92 | 13.2396 | 1.86 | 10.7600 |
FLOOR 2 CONFERENCE TOILET | 5.95 | Yes | Yes | 18.12 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 DICTATION | 6.50 | Yes | Yes | 19.82 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 EXAM 1 | 33.45 | Yes | Yes | 101.94 | 1.00 | 39.02 | 8.92 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 2 | 50.17 | Yes | Yes | 152.91 | 1.00 | 16.72 | 3.72 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 3 | 66.89 | Yes | Yes | 203.88 | 1.00 | 22.30 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 4 | 7.80 | Yes | Yes | 23.79 | 1.00 | 6.50 | 2.23 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 5 | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 6 | 20.90 | Yes | Yes | 63.71 | 1.00 | 13.94 | 4.18 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 7 | 73.58 | Yes | Yes | 224.27 | 1.00 | 22.30 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 8 | 25.08 | Yes | Yes | 76.46 | 1.00 | 16.72 | 5.57 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM 9 | 36.79 | Yes | Yes | 112.13 | 1.00 | 11.15 | 2.79 | 17.8681 | 4.64 | 11.8400 |
FLOOR 2 EXAM HALL 1 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 3 | 16.72 | Yes | Yes | 50.97 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 4 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 5 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 EXAM HALL 6 | 18.39 | Yes | Yes | 56.07 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 LOUNGE | 7.43 | Yes | Yes | 22.65 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 2 NURSE STATION 1 | 13.94 | Yes | Yes | 42.48 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 NURSE STATION 2 | 16.72 | Yes | Yes | 50.97 | 1.00 | 0.00 | 0.00 | 9.3646 | 4.64 | 21.5300 |
FLOOR 2 OFFICE | 52.03 | Yes | Yes | 158.57 | 1.00 | 37.16 | 8.92 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 OFFICE HALL | 41.25 | Yes | Yes | 125.73 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION | 91.42 | Yes | Yes | 278.64 | 1.00 | 45.52 | 16.72 | 9.6875 | 3.10 | 11.8400 |
FLOOR 2 RECEPTION HALL | 52.40 | Yes | Yes | 159.71 | 1.00 | 6.50 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 RECEPTION TOILET | 11.71 | Yes | Yes | 35.68 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 SCHEDULING 1 | 30.10 | Yes | Yes | 91.75 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 SCHEDULING 2 | 31.77 | Yes | Yes | 96.84 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 2 STORAGE 1 | 5.20 | Yes | Yes | 15.86 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 2 | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 STORAGE 3 | 13.38 | Yes | Yes | 40.78 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 2 UTILITY | 11.71 | Yes | Yes | 35.68 | 1.00 | 8.36 | 2.23 | 6.7813 | 1.0800 | |
FLOOR 2 WORK | 157.01 | Yes | Yes | 478.55 | 1.00 | 24.15 | 5.57 | 11.9479 | 18.58 | 9.7803 |
FLOOR 2 WORK HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 2 WORK TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 2 X-RAY | 83.61 | Yes | Yes | 254.85 | 1.00 | 0.00 | 0.00 | 14.2084 | 4.64 | 107.6400 |
FLOOR 3 DRESSING ROOM | 3.90 | Yes | Yes | 11.89 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 ELEVATOR HALL | 34.37 | Yes | Yes | 104.77 | 1.00 | 3.72 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 HUMID | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 JANITOR | 5.85 | Yes | Yes | 17.84 | 1.00 | 14.86 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 LOCKER | 11.15 | Yes | Yes | 33.98 | 1.00 | 0.00 | 0.00 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE | 70.51 | Yes | Yes | 214.92 | 1.00 | 21.37 | 5.57 | 11.5174 | 6.19 | 32.2900 |
FLOOR 3 LOUNGE TOILET | 17.84 | Yes | Yes | 54.37 | 1.00 | 11.15 | 4.18 | 10.5486 | 4.3100 | |
FLOOR 3 MECHANICAL | 32.52 | Yes | Yes | 99.11 | 1.00 | 23.23 | 5.95 | 17.8681 | 53.8200 | |
FLOOR 3 MECHANICAL HALL | 27.87 | Yes | Yes | 84.95 | 1.00 | 0.00 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE | 282.05 | Yes | Yes | 859.70 | 1.00 | 68.75 | 19.51 | 11.9479 | 18.58 | 11.8400 |
FLOOR 3 OFFICE HALL | 77.48 | Yes | Yes | 236.16 | 1.00 | 5.57 | 0.00 | 8.5250 | 4.3100 | |
FLOOR 3 OFFICE TOILET | 5.02 | Yes | Yes | 15.29 | 1.00 | 5.57 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 PHYSICAL THERAPY 1 | 120.77 | Yes | Yes | 368.12 | 1.00 | 78.97 | 28.99 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY 2 | 55.00 | Yes | Yes | 167.64 | 1.00 | 0.00 | 0.00 | 9.7952 | 4.64 | 16.1500 |
FLOOR 3 PHYSICAL THERAPY TOILET | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 10.5486 | 4.3100 | |
FLOOR 3 STORAGE 1 | 10.03 | Yes | Yes | 30.58 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 STORAGE 2 | 7.80 | Yes | Yes | 23.79 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 TREATMENT | 44.22 | Yes | Yes | 134.79 | 1.00 | 0.00 | 0.00 | 17.8681 | 4.64 | 11.8400 |
FLOOR 3 UNDEVELOPED 1 | 210.70 | Yes | Yes | 642.23 | 1.00 | 66.89 | 25.64 | 6.7813 | 11.8400 | |
FLOOR 3 UNDEVELOPED 2 | 107.02 | Yes | Yes | 326.21 | 1.00 | 52.03 | 13.38 | 6.7813 | 11.8400 | |
FLOOR 3 UTILITY | 20.07 | Yes | Yes | 61.16 | 1.00 | 0.00 | 0.00 | 6.7813 | 1.0800 | |
FLOOR 3 WORK | 53.33 | Yes | Yes | 162.54 | 1.00 | 38.09 | 8.92 | 11.9479 | 18.58 | 11.8400 |
NE STAIR | 15.61 | Yes | Yes | 142.72 | 1.00 | 97.55 | 12.02 | 8.5250 | 4.3100 | |
NW ELEVATOR | 13.01 | Yes | Yes | 118.93 | 1.00 | 75.25 | 0.00 | 8.5250 | 4.3100 | |
NW STAIR | 17.84 | Yes | Yes | 163.10 | 1.00 | 111.48 | 11.15 | 8.5250 | 4.3100 | |
SW STAIR | 8.92 | Yes | Yes | 81.55 | 1.00 | 55.74 | 1.11 | 8.5250 | 4.3100 | |
Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Conditioned Total | 3804.01 | 11932.15 | 1553.34 | 308.29 | 11.2925 | 9.08 | 31.9597 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
481E71 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.36 | 180.00 | 90.00 | S |
FLOOR 1 ANESTHESIA SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 0.00 | 180.00 | |
FLOOR 1 BIO HAZ SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
5F762C | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 18.58 | 180.00 | 90.00 | S |
FLOOR 1 CAFE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 39.02 | 90.00 | 180.00 | |
FLOOR 1 CLEAN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 CLEAN WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.33 | 180.00 | 180.00 | |
FLOOR 1 DICTATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 0.00 | 180.00 | |
84FB73 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.36 | 0.00 | 90.00 | N |
FLOOR 1 DRESSING ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 4.18 | 0.00 | 180.00 | |
7F5C82 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 ELECTRICAL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 9.10 | 0.00 | 180.00 | |
C732B0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 12.08 | 0.00 | 90.00 | N |
E02487 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 270.00 | 90.00 | W |
FLOOR 1 ELEVATOR PUMP ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.45 | 180.00 | 180.00 | |
FLOOR 1 HUMID SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
FLOOR 1 IT HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 180.00 | 180.00 | |
FLOOR 1 IT ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.41 | 90.00 | 180.00 | |
FE5A3C | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 20.44 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.79 | 90.00 | 180.00 | |
FLOOR 1 LOBBY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 22.30 | 0.00 | 180.00 | |
9D87EC | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 LOBBY TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 0.00 | 180.00 | |
F629C1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 20.44 | 0.00 | 90.00 | N |
FLOOR 1 LOCKER ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 61.32 | 270.00 | 180.00 | |
FLOOR 1 LOCKER ROOM HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 180.00 | 180.00 | |
FLOOR 1 LOUNGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
E85BB5 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 7.43 | 0.00 | 90.00 | N |
577FC1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 90.00 | 90.00 | E |
FLOOR 1 MED GAS SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 180.00 | 180.00 | |
FLOOR 1 MED GAS ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 5.20 | 180.00 | 0.00 | |
C114C1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 4.65 | 0.00 | 90.00 | N |
FLOOR 1 MRI CONTROL ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 180.00 | 180.00 | |
FLOOR 1 MRI HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.66 | 180.00 | 180.00 | |
FLOOR 1 MRI ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 40.88 | 90.00 | 180.00 | |
ADB8D0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 0.00 | 90.00 | N |
FLOOR 1 MRI TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 90.00 | 180.00 | |
FLOOR 1 NOURISHMENT SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.91 | 270.00 | 180.00 | |
FLOOR 1 NURSE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 46.08 | 270.00 | 180.00 | |
FLOOR 1 NURSE JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 NURSE STATION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 24.25 | 180.00 | 180.00 | |
FLOOR 1 NURSE TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 180.00 | 180.00 | |
FLOOR 1 OFFICE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.87 | 0.00 | 180.00 | |
879583 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 18.58 | 180.00 | 90.00 | S |
E326E4 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 21.37 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 42.74 | 0.00 | 180.00 | |
1D96D7 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 90.00 | 90.00 | E |
FLOOR 1 OPERATING ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.59 | 0.00 | 180.00 | |
FLOOR 1 OPERATING ROOM 3 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 44.22 | 0.00 | 180.00 | |
FLOOR 1 PACU SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 10.03 | 180.00 | 180.00 | |
FLOOR 1 PRE-OP HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 49.05 | 180.00 | 180.00 | |
84418A | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 3.72 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP ROOM 1 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.56 | 90.00 | 180.00 | |
FLOOR 1 PRE-OP ROOM 2 SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 31.40 | 0.00 | 180.00 | |
1535AC | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
FLOOR 1 PRE-OP TOILET SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.02 | 270.00 | 180.00 | |
6D2616 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 17.65 | 0.00 | 90.00 | N |
FLOOR 1 PROCEDURE ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 26.48 | 270.00 | 180.00 | |
A5A6A3 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 12.08 | 180.00 | 90.00 | S |
FLOOR 1 RECEPTION SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 47.29 | 270.00 | 180.00 | |
FLOOR 1 RECEPTION HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.89 | 0.00 | 180.00 | |
28B002 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 41.81 | 180.00 | 90.00 | S |
FLOOR 1 RECOVERY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 50.17 | 90.00 | 180.00 | |
EA6DC8 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 180.00 | 90.00 | S |
FLOOR 1 SCHEDULING SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.06 | 90.00 | 180.00 | |
FLOOR 1 SCRUB SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 7.80 | 90.00 | 180.00 | |
FLOOR 1 SOIL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 11.71 | 90.00 | 180.00 | |
FLOOR 1 SOIL HOLD SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 5.20 | 0.00 | 180.00 | |
FLOOR 1 SOIL WORK SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 16.72 | 0.00 | 180.00 | |
B40F89 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 270.00 | 90.00 | W |
997723 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 23.23 | 180.00 | 90.00 | S |
FLOOR 1 STEP DOWN SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 27.87 | 270.00 | 180.00 | |
CEC7BD | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 7.43 | 180.00 | 90.00 | S |
FLOOR 1 STERILE HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 57.23 | 270.00 | 180.00 | |
FLOOR 1 NURSE STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 36.79 | 0.00 | 180.00 | |
8E5BB9 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 21.37 | 270.00 | 90.00 | W |
859BC1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 37.16 | 0.00 | 90.00 | N |
FLOOR 1 STORAGE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 85.47 | 270.00 | 180.00 | |
FLOOR 1 STORGE ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 85.47 | 270.00 | 0.00 | |
61E610 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.01 | 90.00 | 90.00 | E |
FLOOR 1 SUB-STERILE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 18.21 | 180.00 | 180.00 | |
529072 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 14.86 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY HALL SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 23.78 | 90.00 | 180.00 | |
FLOOR 1 UTILITY HALL ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 11.89 | 180.00 | 0.00 | |
FLOOR 1 UTILITY JANITOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 3.90 | 90.00 | 180.00 | |
D95F04 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 16.72 | 90.00 | 90.00 | E |
FLOOR 1 UTILITY ROOM SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 33.45 | 180.00 | 180.00 | |
3330D8 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 7.43 | 270.00 | 90.00 | W |
FLOOR 1 VESTIBULE SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 6.69 | 90.00 | 180.00 | |
208CCF | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 90.00 | 90.00 | E |
AEF992 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 26.01 | 180.00 | 90.00 | S |
54D065 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 180.00 | 90.00 | S |
1775A6 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.87 | 270.00 | 90.00 | W |
97F00A | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 16.72 | 180.00 | 90.00 | S |
A497E9 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 180.00 | 90.00 | S |
88A75F | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 180.00 | 90.00 | S |
B4E619 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 23.23 | 90.00 | 90.00 | E |
9EC269 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 13.94 | 0.00 | 90.00 | N |
B316F7 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 0.00 | 90.00 | N |
9621FD | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 16.72 | 0.00 | 90.00 | N |
42CEE1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 0.00 | 90.00 | N |
4979C8 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 180.00 | 90.00 | S |
8CA0BF | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 180.00 | 90.00 | S |
6C95E7 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 180.00 | 90.00 | S |
F209CC | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 0.00 | 90.00 | N |
155BD6 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 0.00 | 90.00 | N |
C5EA55 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 0.00 | 90.00 | N |
8177BA | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 270.00 | 90.00 | W |
5E657E | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.36 | 0.00 | 90.00 | N |
4B1439 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 37.16 | 90.00 | 90.00 | E |
4ABC66 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 30.66 | 180.00 | 90.00 | S |
5B04CF | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 14.86 | 270.00 | 90.00 | W |
8D1BC4 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 180.00 | 90.00 | S |
4B55FA | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.36 | 90.00 | 90.00 | E |
9C3A6A | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 20.44 | 0.00 | 90.00 | N |
C52EE0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 3.72 | 0.00 | 90.00 | N |
1C33AD | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
6CC177 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 DRESSING ROOM ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 3.90 | 270.00 | 0.00 | |
F7D24D | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 3.72 | 0.00 | 90.00 | N |
FLOOR 3 ELEVATOR HALL ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 34.37 | 0.00 | 0.00 | |
FLOOR 3 HUMID ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 10.03 | 270.00 | 0.00 | |
FC22D1 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 8.36 | 0.00 | 90.00 | N |
DD2E2D | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 6.50 | 270.00 | 90.00 | W |
FLOOR 3 JANITOR ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 5.85 | 0.00 | 0.00 | |
FLOOR 3 LOCKER ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 11.15 | 0.00 | 0.00 | |
68A2D7 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 21.37 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 70.51 | 270.00 | 0.00 | |
CE3FEF | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 0.00 | 90.00 | N |
FLOOR 3 LOUNGE TOILET ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 17.84 | 0.00 | 0.00 | |
CE618F | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 23.23 | 90.00 | 90.00 | E |
FLOOR 3 MECHANICAL ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 32.52 | 0.00 | 0.00 | |
FLOOR 3 MECHANICAL HALL ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 27.87 | 0.00 | 0.00 | |
5ADC59 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 68.75 | 0.00 | 90.00 | N |
FLOOR 3 OFFICE ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 282.05 | 180.00 | 0.00 | |
D4F411 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE HALL ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 77.48 | 270.00 | 0.00 | |
B35AD6 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 5.57 | 270.00 | 90.00 | W |
FLOOR 3 OFFICE TOILET ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 5.02 | 270.00 | 0.00 | |
D22917 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 18.58 | 90.00 | 90.00 | E |
C1BC97 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.39 | 180.00 | 90.00 | S |
FLOOR 3 PHYICAL THERAPY 1 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 120.77 | 180.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY 2 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 55.00 | 90.00 | 0.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 7.80 | 90.00 | 0.00 | |
FLOOR 3 STORAGE 1 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 10.03 | 180.00 | 0.00 | |
FLOOR 3 STORAGE 2 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 7.80 | 180.00 | 0.00 | |
FLOOR 3 TREATMENT ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 44.22 | 90.00 | 0.00 | |
8DA7DB | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 39.02 | 180.00 | 90.00 | S |
38B339 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 27.87 | 270.00 | 90.00 | W |
FLOOR 3 UNDEVELOPED 1 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 210.70 | 0.00 | 0.00 | |
BE5F2F | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 14.86 | 270.00 | 90.00 | W |
1DEE26 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 37.16 | 180.00 | 90.00 | S |
FLOOR 3 UNDEVELOPED 2 ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 107.02 | 180.00 | 0.00 | |
FLOOR 3 UTILITY ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 20.07 | 0.00 | 0.00 | |
C86329 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 38.09 | 90.00 | 90.00 | E |
FLOOR 3 WORK ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 53.33 | 90.00 | 0.00 | |
DFC6F0 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 19.51 | 90.00 | 90.00 | E |
88E360 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.89 | 0.00 | 90.00 | N |
E7B55F | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 11.15 | 180.00 | 90.00 | S |
NE STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 15.61 | 0.00 | 180.00 | |
NE STAIR ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 15.61 | 0.00 | 0.00 | |
FB3814 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 19.51 | 180.00 | 90.00 | S |
FCD12D | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 55.74 | 270.00 | 90.00 | W |
NW ELEVATOR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 13.01 | 90.00 | 180.00 | |
NW ELEVATOR ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 13.01 | 90.00 | 0.00 | |
5507DC | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 270.00 | 90.00 | W |
2E2D0C | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 66.89 | 0.00 | 90.00 | N |
AF0124 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 90.00 | 90.00 | E |
NW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 17.84 | 270.00 | 180.00 | |
NW STAIR ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 17.84 | 270.00 | 0.00 | |
850EA7 | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 33.45 | 180.00 | 90.00 | S |
270BCE | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 22.30 | 270.00 | 90.00 | W |
SW STAIR SLAB | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.827 | 3.285 | 8.92 | 270.00 | 180.00 | |
SW STAIR ROOF | NONRES_ROOF | 0.55 | 0.269 | 0.283 | 8.92 | 180.00 | 0.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
78F987 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 481E71 | 180.00 | 90.00 | S | ||
D8037E | WINDOW_U_0.62_SHGC_0.25 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.848 | 0.287 | 0.200 | No | 5F762C | 180.00 | 90.00 | S | ||
4A8120 | WINDOW_U_0.62_SHGC_0.25 | 2.32 | 0.00 | 0.00 | 2.32 | 2.32 | 2.848 | 0.287 | 0.200 | No | 84FB73 | 0.00 | 90.00 | N | ||
AAE778 | WINDOW_U_0.62_SHGC_0.25 | 8.92 | 0.00 | 0.00 | 8.92 | 8.92 | 2.848 | 0.287 | 0.200 | No | FE5A3C | 270.00 | 90.00 | W | ||
3AAD8B | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | F629C1 | 0.00 | 90.00 | N | ||
8128A9 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | F629C1 | 0.00 | 90.00 | N | ||
9B1541 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 879583 | 180.00 | 90.00 | S | ||
CF850A | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 879583 | 180.00 | 90.00 | S | ||
A6BA23 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | E326E4 | 90.00 | 90.00 | E | ||
D10D28 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | E326E4 | 90.00 | 90.00 | E | ||
591336 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1D96D7 | 90.00 | 90.00 | E | ||
38B811 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1D96D7 | 90.00 | 90.00 | E | ||
C044D6 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1D96D7 | 90.00 | 90.00 | E | ||
1D94BE | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 6D2616 | 0.00 | 90.00 | N | ||
18748E | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 6D2616 | 0.00 | 90.00 | N | ||
137A56 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | A5A6A3 | 180.00 | 90.00 | S | ||
8D508E | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 28B002 | 180.00 | 90.00 | S | ||
B2D381 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 28B002 | 180.00 | 90.00 | S | ||
1DA13A | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 28B002 | 180.00 | 90.00 | S | ||
44E54A | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 28B002 | 180.00 | 90.00 | S | ||
757D10 | WINDOW_U_0.62_SHGC_0.25 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.848 | 0.287 | 0.200 | No | EA6DC8 | 180.00 | 90.00 | S | ||
E33BAE | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | B40F89 | 270.00 | 90.00 | W | ||
24167A | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 997723 | 180.00 | 90.00 | S | ||
2C0938 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 997723 | 180.00 | 90.00 | S | ||
8600DD | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | CEC7BD | 180.00 | 90.00 | S | ||
A1ED60 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 859BC1 | 0.00 | 90.00 | N | ||
E8D997 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 859BC1 | 0.00 | 90.00 | N | ||
88E1FC | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 859BC1 | 0.00 | 90.00 | N | ||
F83F33 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | 61E610 | 90.00 | 90.00 | E | ||
B1F5EE | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | D95F04 | 90.00 | 90.00 | E | ||
F52F3D | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 208CCF | 90.00 | 90.00 | E | ||
80885D | WINDOW_U_0.62_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.848 | 0.287 | 0.200 | No | AEF992 | 180.00 | 90.00 | S | ||
FEEF06 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 54D065 | 180.00 | 90.00 | S | ||
2BE8DE | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1775A6 | 270.00 | 90.00 | W | ||
513E2A | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1775A6 | 270.00 | 90.00 | W | ||
BA5CD9 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 1775A6 | 270.00 | 90.00 | W | ||
1AD478 | WINDOW_U_0.62_SHGC_0.25 | 3.72 | 0.00 | 0.00 | 3.72 | 3.72 | 2.848 | 0.287 | 0.200 | No | 97F00A | 180.00 | 90.00 | S | ||
27F0AC | WINDOW_U_0.62_SHGC_0.25 | 5.95 | 0.00 | 0.00 | 5.95 | 5.95 | 2.848 | 0.287 | 0.200 | No | A497E9 | 180.00 | 90.00 | S | ||
724114 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 88A75F | 180.00 | 90.00 | S | ||
D538C4 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | B4E619 | 90.00 | 90.00 | E | ||
5635BC | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | B4E619 | 90.00 | 90.00 | E | ||
831C1D | WINDOW_U_0.62_SHGC_0.25 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.848 | 0.287 | 0.200 | No | 9EC269 | 0.00 | 90.00 | N | ||
9BB95F | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | B316F7 | 0.00 | 90.00 | N | ||
C0778D | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | B316F7 | 0.00 | 90.00 | N | ||
7D2D69 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 9621FD | 0.00 | 90.00 | N | ||
2EF63B | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 9621FD | 0.00 | 90.00 | N | ||
C417C0 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 42CEE1 | 0.00 | 90.00 | N | ||
EB042B | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 4B1439 | 90.00 | 90.00 | E | ||
4C1F71 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 4B1439 | 90.00 | 90.00 | E | ||
D23C8B | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 4B1439 | 90.00 | 90.00 | E | ||
B4E4BE | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 4B1439 | 90.00 | 90.00 | E | ||
EEF55D | WINDOW_U_0.62_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.848 | 0.287 | 0.200 | No | 4ABC66 | 180.00 | 90.00 | S | ||
E55A57 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | 4ABC66 | 180.00 | 90.00 | S | ||
93D018 | WINDOW_U_0.62_SHGC_0.25 | 6.69 | 0.00 | 0.00 | 6.69 | 6.69 | 2.848 | 0.287 | 0.200 | No | 5B04CF | 270.00 | 90.00 | W | ||
DD9F5D | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | 4B55FA | 90.00 | 90.00 | E | ||
15B02B | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 9C3A6A | 0.00 | 90.00 | N | ||
820282 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 9C3A6A | 0.00 | 90.00 | N | ||
9BA05A | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 68A2D7 | 0.00 | 90.00 | N | ||
C639E8 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 68A2D7 | 0.00 | 90.00 | N | ||
A2790A | WINDOW_U_0.62_SHGC_0.25 | 4.18 | 0.00 | 0.00 | 4.18 | 4.18 | 2.848 | 0.287 | 0.200 | No | CE3FEF | 0.00 | 90.00 | N | ||
79FCEE | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | CE618F | 90.00 | 90.00 | E | ||
EDE617 | WINDOW_U_0.62_SHGC_0.25 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 2.848 | 0.287 | 0.200 | No | CE618F | 90.00 | 90.00 | E | ||
C61F0D | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
7248C5 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
29FA28 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
F0B23F | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
EEC10E | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
944FCE | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
C41399 | WINDOW_U_0.62_SHGC_0.25 | 2.79 | 0.00 | 0.00 | 2.79 | 2.79 | 2.848 | 0.287 | 0.200 | No | 5ADC59 | 0.00 | 90.00 | N | ||
95BA33 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | D22917 | 90.00 | 90.00 | E | ||
F27282 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | D22917 | 90.00 | 90.00 | E | ||
3DB407 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | C1BC97 | 180.00 | 90.00 | S | ||
3DADE2 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | C1BC97 | 180.00 | 90.00 | S | ||
DF3E2C | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | C1BC97 | 180.00 | 90.00 | S | ||
5031C8 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | C1BC97 | 180.00 | 90.00 | S | ||
C087D0 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | 8DA7DB | 180.00 | 90.00 | S | ||
D2CA75 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | 8DA7DB | 180.00 | 90.00 | S | ||
B0FB49 | WINDOW_U_0.62_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.848 | 0.287 | 0.200 | No | 8DA7DB | 180.00 | 90.00 | S | ||
FE9BC9 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | 38B339 | 270.00 | 90.00 | W | ||
9DF7DE | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | 38B339 | 270.00 | 90.00 | W | ||
D0BE44 | WINDOW_U_0.62_SHGC_0.25 | 3.34 | 0.00 | 0.00 | 3.34 | 3.34 | 2.848 | 0.287 | 0.200 | No | 38B339 | 270.00 | 90.00 | W | ||
6B5226 | WINDOW_U_0.62_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.848 | 0.287 | 0.200 | No | BE5F2F | 270.00 | 90.00 | W | ||
8F59F7 | WINDOW_U_0.62_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.848 | 0.287 | 0.200 | No | 1DEE26 | 180.00 | 90.00 | S | ||
44F571 | WINDOW_U_0.62_SHGC_0.25 | 4.46 | 0.00 | 0.00 | 4.46 | 4.46 | 2.848 | 0.287 | 0.200 | No | 1DEE26 | 180.00 | 90.00 | S | ||
6BD844 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | C86329 | 90.00 | 90.00 | E | ||
86D536 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | C86329 | 90.00 | 90.00 | E | ||
BAF71D | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | C86329 | 90.00 | 90.00 | E | ||
3833A2 | WINDOW_U_0.62_SHGC_0.25 | 2.23 | 0.00 | 0.00 | 2.23 | 2.23 | 2.848 | 0.287 | 0.200 | No | C86329 | 90.00 | 90.00 | E | ||
2111A1 | WINDOW_U_0.62_SHGC_0.25 | 0.74 | 0.00 | 0.00 | 0.74 | 0.74 | 2.848 | 0.287 | 0.200 | No | DFC6F0 | 90.00 | 90.00 | E | ||
9BC521 | WINDOW_U_0.62_SHGC_0.25 | 5.71 | 0.00 | 0.00 | 5.71 | 5.71 | 2.848 | 0.287 | 0.200 | No | 88E360 | 0.00 | 90.00 | N | ||
142781 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | 88E360 | 0.00 | 90.00 | N | ||
E74902 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | 2E2D0C | 0.00 | 90.00 | N | ||
93BBC3 | WINDOW_U_0.62_SHGC_0.25 | 5.57 | 0.00 | 0.00 | 5.57 | 5.57 | 2.848 | 0.287 | 0.200 | No | 2E2D0C | 0.00 | 90.00 | N | ||
C635A6 | WINDOW_U_0.62_SHGC_0.25 | 1.11 | 0.00 | 0.00 | 1.11 | 1.11 | 2.848 | 0.287 | 0.200 | No | 850EA7 | 180.00 | 90.00 | S | ||
Total or Average | 308.29 | 2.848 | 0.287 | 0.200 | ||||||||||||
North Total or Average | 97.22 | 2.848 | 0.287 | 0.200 | ||||||||||||
Non-North Total or Average | 211.08 | 2.848 | 0.287 | 0.200 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
BA05F7 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | E02487 |
F67E1F | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | FE5A3C |
7EB6E7 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | E85BB5 |
D18914 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | C114C1 |
D4B39B | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | E326E4 |
D2D3BC | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 28B002 |
C528DA | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 28B002 |
EFD3F9 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 28B002 |
62B5AF | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 997723 |
71E924 | SWINGING DOOR_CON | 3.975 | 3.975 | 2.97 | 8E5BB9 |
3C44F9 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 859BC1 |
49526E | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 859BC1 |
865AE8 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 859BC1 |
5E66D1 | OVERHEAD DOOR_CON | 2.841 | 2.841 | 7.43 | 529072 |
E14DAE | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | D95F04 |
84A1D5 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 3330D8 |
9CB8E5 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 88E360 |
E4A528 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 88E360 |
24BAF7 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | FB3814 |
19E57D | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | FCD12D |
EDE769 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 5507DC |
1C9872 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 2E2D0C |
F402E9 | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 270BCE |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
HEATSYS1 BOILER | Boiler:HotWater | 64534.55 | 0.80 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 168520.11 | 115598.90 | 52921.21 | 0.69 | 3.40 | |||
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 194033.26 | 145010.67 | 49022.59 | 0.75 | 3.40 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 163346.1 | 2.99 | 10.20 | N/A | 11.35 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 186562.5 | 2.90 | 9.88 | N/A | 11.01 |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | Coil:Heating:Water | 1998.79 | 1980.05 | - |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | Coil:Heating:Water | 91.53 | 66.98 | - |
FLOOR 1 CAFE VAV BOX REHEAT COIL | Coil:Heating:Water | 4358.58 | 2969.53 | - |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | Coil:Heating:Water | 1220.54 | 1209.10 | - |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 1526.85 | 1512.54 | - |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Water | 372.32 | 253.66 | - |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 214.13 | 191.99 | - |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 656.23 | 447.10 | - |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 4091.35 | 2787.47 | - |
FLOOR 1 HUMID VAV BOX REHEAT COIL | Coil:Heating:Water | 183.63 | 125.11 | - |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 263.88 | 179.79 | - |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 298.28 | 203.22 | - |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | Coil:Heating:Water | 3924.74 | 2673.95 | - |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 559.30 | 381.06 | - |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1249.24 | 1237.53 | - |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 3295.85 | 2245.49 | - |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 831.81 | 566.72 | - |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Water | 1665.31 | 1134.59 | - |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | Coil:Heating:Water | 401.91 | 398.14 | - |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 2331.92 | 1588.76 | - |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 354.45 | 241.49 | - |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 6107.42 | 4161.03 | - |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1249.24 | 1237.53 | - |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | Coil:Heating:Water | 822.73 | 560.53 | - |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 995.64 | 678.33 | - |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 125.99 | 85.84 | - |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | Coil:Heating:Water | 1104.56 | 752.54 | - |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1249.24 | 1237.53 | - |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Water | 1200.26 | 817.74 | - |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13525.50 | 13398.67 | - |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 13927.29 | 13796.70 | - |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22023.72 | 21817.21 | - |
FLOOR 1 PACU VAV BOX REHEAT COIL | Coil:Heating:Water | 1499.09 | 1485.04 | - |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 991.14 | 675.27 | - |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | Coil:Heating:Water | 2623.41 | 2598.81 | - |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | Coil:Heating:Water | 4691.61 | 4647.62 | - |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | Coil:Heating:Water | 1249.24 | 1237.53 | - |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 9889.85 | 9797.12 | - |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Water | 2507.81 | 1708.59 | - |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 258.29 | 175.98 | - |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 7164.83 | 7097.65 | - |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | Coil:Heating:Water | 423.26 | 288.37 | - |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | Coil:Heating:Water | 156.61 | 106.70 | - |
FLOOR 1 SOIL VAV BOX REHEAT COIL | Coil:Heating:Water | 2914.90 | 2887.57 | - |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | Coil:Heating:Water | 1295.51 | 1283.37 | - |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | Coil:Heating:Water | 4164.15 | 4125.10 | - |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | Coil:Heating:Water | 3519.63 | 3486.62 | - |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 1042.77 | 710.45 | - |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 595.30 | 405.58 | - |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | Coil:Heating:Water | 2670.16 | 2645.12 | - |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | Coil:Heating:Water | 768.46 | 553.59 | - |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | Coil:Heating:Water | 747.18 | 724.28 | - |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | Coil:Heating:Water | 86.17 | 58.71 | - |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | Coil:Heating:Water | 939.30 | 813.82 | - |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | Coil:Heating:Water | 342.05 | 233.04 | - |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2421.11 | 1.00 | |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | Coil:Heating:Electric | 138.30 | 1.00 | |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3732.04 | 1.00 | |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7370.30 | 1.00 | |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9827.06 | 1.00 | |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 974.18 | 1.00 | |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 4139.42 | 1.00 | |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 2886.70 | 1.00 | |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | Coil:Heating:Electric | 10809.77 | 1.00 | |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3427.19 | 1.00 | |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | Coil:Heating:Electric | 5404.88 | 1.00 | |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 278.13 | 1.00 | |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 276.20 | 1.00 | |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 266.13 | 1.00 | |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 276.14 | 1.00 | |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | Coil:Heating:Electric | 285.59 | 1.00 | |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | Coil:Heating:Electric | 284.86 | 1.00 | |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 318.71 | 1.00 | |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 251.04 | 1.00 | |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 557.86 | 1.00 | |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 669.43 | 1.00 | |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 1516.08 | 1.00 | |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 619.24 | 1.00 | |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | Coil:Heating:Electric | 4803.21 | 1.00 | |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 855.26 | 1.00 | |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 640.15 | 1.00 | |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 675.71 | 1.00 | |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 156.20 | 1.00 | |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 334.72 | 1.00 | |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 401.66 | 1.00 | |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 351.45 | 1.00 | |
FLOOR 2 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 3339.05 | 1.00 | |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1173.97 | 1.00 | |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1228.38 | 1.00 | |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | Coil:Heating:Electric | 6276.07 | 1.00 | |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 92.36 | 1.00 | |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 516.02 | 1.00 | |
FLOOR 3 HUMID VAV BOX REHEAT COIL | Coil:Heating:Electric | 232.23 | 1.00 | |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 372.09 | 1.00 | |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | Coil:Heating:Electric | 376.56 | 1.00 | |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | Coil:Heating:Electric | 2381.74 | 1.00 | |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 4367.58 | 1.00 | |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 479.75 | 1.00 | |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | Coil:Heating:Electric | 5998.27 | 1.00 | |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | Coil:Heating:Electric | 1163.13 | 1.00 | |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 1228.38 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14878.92 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6706.42 | 1.00 | |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | Coil:Heating:Electric | 0.00 | 1.00 | |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 674.18 | 1.00 | |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 234.30 | 1.00 | |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | Coil:Heating:Electric | 5262.39 | 1.00 | |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 6326.28 | 1.00 | |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 3213.30 | 1.00 | |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | Coil:Heating:Electric | 602.49 | 1.00 | |
FLOOR 3 WORK VAV BOX REHEAT COIL | Coil:Heating:Electric | 1722.99 | 1.00 | |
NE STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2136.10 | 1.00 | |
NW ELEVATOR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1388.52 | 1.00 | |
NW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 2148.85 | 1.00 | |
SW STAIR VAV BOX REHEAT COIL | Coil:Heating:Electric | 1076.62 | 1.00 | |
AHU-1_HEATC | Coil:Heating:Water | 13015.82 | 12602.74 | - |
AHU-1_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
AHU-1_EXTRAWATERHEATC | Coil:Heating:Water | 13015.82 | 12602.74 | - |
AHU-2_HEATC | Coil:Heating:Water | 70343.56 | 64033.10 | - |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | End Use | |
FLOOR 1 ANESTHESIA EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 54.61 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 LOBBY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI CONTROL ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.16 | 127.44 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI ROOM EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.42 | 323.16 | 778.12 | 1.00 | Zone Exhaust Fans |
FLOOR 1 MRI TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 NURSE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 PRE-OP TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL HOLD EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 35.39 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 1 SOIL WORK EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.14 | 113.76 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 CONFERENCE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.05 | 40.45 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 RECEPTION TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.10 | 79.63 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 WORK TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 2 X-RAY EXHAUST FAN | Fan:ZoneExhaust | 0.16 | 124.50 | 0.85 | 661.02 | 778.13 | 1.00 | Zone Exhaust Fans |
FLOOR 3 LOUNGE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.15 | 121.35 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 OFFICE TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.04 | 34.13 | 803.55 | 1.00 | Zone Exhaust Fans |
FLOOR 3 PHYSICAL THERAPY TOILET EXHAUST FAN | Fan:ZoneExhaust | 0.31 | 249.10 | 0.07 | 53.09 | 803.55 | 1.00 | Zone Exhaust Fans |
AHU-1_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 7.06 | 16122.96 | 2283.73 | 1.00 | Fan Energy |
AHU-2_FAN | Fan:VariableVolume | 0.61 | 1389.42 | 10.09 | 22910.89 | 2271.59 | 1.00 | Fan Energy |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.0001 | 8.07 | 127739.32 | 0.30 |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.0014 | 353.59 | 255487.18 | 0.90 |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.20 | 0.81 | 0.00 | 0.00 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
AHU-1_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 163346.05 | 2.99 | 10.20 | 11.35 | 8.0130 | 3.24 | 11.06 | 6.3198 | 3.44 | 11.75 | 4.2322 | 3.57 | 12.19 | 1.8575 |
AHU-2_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 186562.48 | 2.90 | 9.88 | 11.01 | 11.4473 | 3.13 | 10.68 | 8.6490 | 3.37 | 11.48 | 5.4914 | 3.49 | 11.92 | 2.4475 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
Zone CoolingCalculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 707.01 | 707.01 | 0.053 | 0.068 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
FLOOR 1 CAFE | 3962.66 | 3962.66 | 0.296 | 0.296 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00 | 0.00820 |
FLOOR 1 CLEAN | 555.44 | 555.44 | 0.041 | 0.041 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 26.91 | 0.00820 |
FLOOR 1 CLEAN WORK | 692.67 | 692.67 | 0.052 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 27.67 | 0.00820 |
FLOOR 1 DICTATION | 351.02 | 351.02 | 0.025 | 0.025 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 DRESSING ROOM | 194.93 | 194.93 | 0.015 | 0.015 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30 | 0.00820 |
FLOOR 1 HUMID | 172.77 | 172.77 | 0.012 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 IT ROOM | 271.53 | 271.53 | 0.020 | 0.020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 31.30 | 0.00820 |
FLOOR 1 LOBBY | 3572.55 | 3572.55 | 0.267 | 0.267 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 30.17 | 0.00820 |
FLOOR 1 LOCKER ROOM | 2999.83 | 2999.83 | 0.224 | 0.224 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
FLOOR 1 LOUNGE | 1515.75 | 1515.75 | 0.113 | 0.113 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:50:00 | 29.03 | 0.00820 |
FLOOR 1 MRI CONTROL ROOM | 1840.37 | 1840.37 | 0.137 | 0.159 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:10:00 | 30.65 | 0.00820 |
FLOOR 1 MRI ROOM | 4514.19 | 4514.19 | 0.337 | 0.415 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 29.61 | 0.00820 |
FLOOR 1 NOURISHMENT | 748.81 | 748.81 | 0.056 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12 | 0.00820 |
FLOOR 1 NURSE STATION | 1005.30 | 1005.30 | 0.075 | 0.075 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12 | 0.00820 |
FLOOR 1 OFFICE | 1092.61 | 1092.61 | 0.082 | 0.082 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.41 | 0.00820 |
FLOOR 1 OPERATING ROOM 1 | 6654.85 | 6654.85 | 0.766 | 0.766 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:10:00 | 28.14 | 0.00820 |
FLOOR 1 OPERATING ROOM 2 | 6852.55 | 6852.55 | 0.789 | 0.789 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.66 | 0.00820 |
FLOOR 1 OPERATING ROOM 3 | 5819.87 | 5819.87 | 0.634 | 0.749 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 07:20:00 | 23.71 | 0.00820 |
FLOOR 1 PACU | 519.88 | 519.88 | 0.039 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:10:00 | 26.66 | 0.00820 |
FLOOR 1 PRE-OP ROOM 1 | 612.95 | 612.95 | 0.046 | 0.089 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 29.61 | 0.00820 |
FLOOR 1 PRE-OP ROOM 2 | 1068.95 | 1068.95 | 0.080 | 0.160 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:30:00 | 25.56 | 0.00820 |
FLOOR 1 PROCEDURE ROOM | 1707.21 | 1707.21 | 0.128 | 0.336 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31.30 | 0.00820 |
FLOOR 1 RECEPTION | 2282.12 | 2282.12 | 0.171 | 0.171 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
FLOOR 1 RECOVERY ROOM | 3747.73 | 3747.73 | 0.280 | 0.280 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
FLOOR 1 SCHEDULING | 385.30 | 385.30 | 0.029 | 0.029 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 1 SOIL | 551.09 | 551.09 | 0.041 | 0.099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
FLOOR 1 SOIL HOLD | 229.23 | 229.23 | 0.017 | 0.044 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30 | 0.00820 |
FLOOR 1 SOIL WORK | 738.93 | 738.93 | 0.055 | 0.142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 27.41 | 0.00820 |
FLOOR 1 STEP DOWN | 2321.32 | 2321.32 | 0.173 | 0.173 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 31.12 | 0.00820 |
FLOOR 2 CONFERENCE | 2789.83 | 2789.83 | 0.246 | 0.246 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00 | 0.00820 |
FLOOR 2 DICTATION | 250.54 | 250.54 | 0.021 | 0.021 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM 1 | 2868.04 | 2868.04 | 0.253 | 0.253 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 30.29 | 0.00820 |
FLOOR 2 EXAM 2 | 2490.98 | 2490.98 | 0.220 | 0.255 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 31.15 | 0.00820 |
FLOOR 2 EXAM 3 | 3410.05 | 3410.05 | 0.301 | 0.340 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 31.08 | 0.00820 |
FLOOR 2 EXAM 4 | 596.59 | 596.59 | 0.053 | 0.053 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00 | 0.00820 |
FLOOR 2 EXAM 5 | 2351.22 | 2351.22 | 0.207 | 0.207 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
FLOOR 2 EXAM 6 | 1038.89 | 1038.89 | 0.092 | 0.106 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
FLOOR 2 EXAM 7 | 3158.48 | 3158.48 | 0.279 | 0.374 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 2 EXAM 8 | 1286.70 | 1286.70 | 0.114 | 0.127 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30 | 0.00820 |
FLOOR 2 EXAM 9 | 1693.82 | 1693.82 | 0.149 | 0.187 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 2 LOUNGE | 397.94 | 397.94 | 0.035 | 0.035 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.28 | 0.00820 |
FLOOR 2 NURSE STATION 1 | 639.45 | 639.45 | 0.056 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.28 | 0.00820 |
FLOOR 2 NURSE STATION 2 | 780.49 | 780.49 | 0.069 | 0.069 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.28 | 0.00820 |
FLOOR 2 OFFICE | 2971.51 | 2971.51 | 0.262 | 0.262 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
FLOOR 2 RECEPTION | 5568.74 | 5568.74 | 0.491 | 0.491 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 30.94 | 0.00820 |
FLOOR 2 SCHEDULING 1 | 932.25 | 932.25 | 0.082 | 0.082 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:30:00 | 25.56 | 0.00820 |
FLOOR 2 SCHEDULING 2 | 1019.94 | 1019.94 | 0.090 | 0.090 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 25.28 | 0.00820 |
FLOOR 2 WORK | 4534.54 | 4534.54 | 0.400 | 0.400 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 31.30 | 0.00820 |
FLOOR 2 X-RAY | 9406.92 | 9406.92 | 0.830 | 0.849 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
FLOOR 3 DRESSING ROOM | 181.04 | 181.04 | 0.016 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30 | 0.00820 |
FLOOR 3 HUMID | 455.17 | 455.17 | 0.040 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30 | 0.00820 |
FLOOR 3 LOCKER | 714.10 | 714.10 | 0.063 | 0.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30 | 0.00820 |
FLOOR 3 LOUNGE | 4237.62 | 4237.62 | 0.374 | 0.374 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30 | 0.00820 |
FLOOR 3 OFFICE | 10195.17 | 10195.17 | 0.899 | 0.899 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 31.30 | 0.00820 |
FLOOR 3 PHYSICAL THERAPY 1 | 8451.13 | 8451.13 | 0.746 | 0.746 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 30.93 | 0.00820 |
FLOOR 3 PHYSICAL THERAPY 2 | 2784.62 | 2784.62 | 0.246 | 0.279 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.23 | 0.00820 |
FLOOR 3 TREATMENT | 2386.16 | 2386.16 | 0.211 | 0.225 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 3 WORK | 3377.03 | 3377.03 | 0.298 | 0.298 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 27.41 | 0.00820 |
FLOOR 1 BIO HAZ | 84.97 | 84.97 | 0.006 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 ELECTRICAL ROOM | 597.42 | 597.42 | 0.045 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 11:00:00 | 29.25 | 0.00820 |
FLOOR 1 ELEVATOR PUMP ROOM | 3724.71 | 3724.71 | 0.278 | 0.278 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 30.17 | 0.00820 |
FLOOR 1 IT HALL | 245.86 | 245.86 | 0.018 | 0.018 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 LOBBY HALL | 528.84 | 528.84 | 0.038 | 0.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 LOBBY TOILET | 444.54 | 444.54 | 0.033 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
FLOOR 1 LOCKER ROOM HALL | 780.50 | 780.50 | 0.057 | 0.057 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 MED GAS | 210.96 | 210.96 | 0.016 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:40:00 | 30.62 | 0.00820 |
FLOOR 1 MRI HALL | 333.30 | 333.30 | 0.024 | 0.024 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 MRI TOILET | 140.22 | 140.22 | 0.010 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 31.03 | 0.00820 |
FLOOR 1 NURSE HALL | 937.22 | 937.22 | 0.068 | 0.068 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 NURSE JANITOR | 117.48 | 117.48 | 0.009 | 0.009 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 NURSE TOILET | 143.50 | 143.50 | 0.010 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 PRE-OP HALL | 932.29 | 932.29 | 0.067 | 0.067 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 PRE-OP TOILET | 199.14 | 199.14 | 0.015 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
FLOOR 1 RECEPTION HALL | 242.08 | 242.08 | 0.018 | 0.018 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 SCRUB | 142.57 | 142.57 | 0.011 | 0.011 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.71 | 0.00820 |
FLOOR 1 STERILE HALL | 949.32 | 949.32 | 0.071 | 0.071 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 30.50 | 0.00820 |
FLOOR 1 STERILE STORAGE | 558.71 | 558.71 | 0.040 | 0.040 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 STORAGE | 1746.56 | 1746.56 | 0.130 | 0.130 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 30.94 | 0.00820 |
FLOOR 1 SUB-STERILE | 699.60 | 699.60 | 0.052 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
FLOOR 1 UTILITY HALL | 680.22 | 680.22 | 0.051 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 26.12 | 0.00820 |
FLOOR 1 UTILITY JANITOR | 80.00 | 80.00 | 0.006 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 1 UTILITY ROOM | 855.13 | 855.13 | 0.064 | 0.064 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 27.41 | 0.00820 |
FLOOR 1 VESTIBULE | 311.40 | 311.40 | 0.023 | 0.023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 30.05 | 0.00820 |
FLOOR 2 CONFERENCE TOILET | 198.47 | 198.47 | 0.017 | 0.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 1 | 565.20 | 565.20 | 0.048 | 0.048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 2 | 561.01 | 561.01 | 0.048 | 0.048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 3 | 540.25 | 540.25 | 0.046 | 0.046 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 4 | 552.34 | 552.34 | 0.047 | 0.047 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 5 | 579.82 | 579.82 | 0.049 | 0.049 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 EXAM HALL 6 | 578.72 | 578.72 | 0.049 | 0.049 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 JANITOR | 405.08 | 405.08 | 0.036 | 0.036 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:50:00 | 29.31 | 0.00820 |
FLOOR 2 OFFICE HALL | 1185.86 | 1185.86 | 0.101 | 0.101 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 RECEPTION HALL | 1738.82 | 1738.82 | 0.148 | 0.148 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 RECEPTION TOILET | 369.82 | 369.82 | 0.031 | 0.099 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 STORAGE 1 | 167.76 | 167.76 | 0.014 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 STORAGE 2 | 293.70 | 293.70 | 0.025 | 0.025 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 STORAGE 3 | 382.40 | 382.40 | 0.032 | 0.032 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 UTILITY | 610.44 | 610.44 | 0.054 | 0.054 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 27.16 | 0.00820 |
FLOOR 2 WORK HALL | 2387.54 | 2387.54 | 0.203 | 0.203 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 2 WORK TOILET | 220.92 | 220.92 | 0.019 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 29.16 | 0.00820 |
FLOOR 3 ELEVATOR HALL | 851.98 | 851.98 | 0.075 | 0.075 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 3 JANITOR | 229.60 | 229.60 | 0.020 | 0.020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 29.61 | 0.00820 |
FLOOR 3 LOUNGE TOILET | 683.73 | 683.73 | 0.060 | 0.151 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 31.30 | 0.00820 |
FLOOR 3 MECHANICAL | 3608.09 | 3608.09 | 0.318 | 0.318 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 27.41 | 0.00820 |
FLOOR 3 MECHANICAL HALL | 940.36 | 940.36 | 0.083 | 0.083 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 12:40:00 | 30.62 | 0.00820 |
FLOOR 3 OFFICE HALL | 2211.23 | 2211.23 | 0.195 | 0.195 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 31.30 | 0.00820 |
FLOOR 3 OFFICE TOILET | 196.67 | 196.67 | 0.017 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:40:00 | 29.46 | 0.00820 |
FLOOR 3 PHYSICAL THERAPY TOILET | 267.72 | 267.72 | 0.023 | 0.066 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 3 STORAGE 1 | 273.47 | 273.47 | 0.023 | 0.023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 3 STORAGE 2 | 244.59 | 244.59 | 0.021 | 0.021 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
FLOOR 3 UNDEVELOPED 1 | 8596.36 | 8596.36 | 0.758 | 0.758 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 31.12 | 0.00820 |
FLOOR 3 UNDEVELOPED 2 | 4480.24 | 4480.24 | 0.395 | 0.395 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 31.21 | 0.00820 |
FLOOR 3 UTILITY | 429.25 | 429.25 | 0.036 | 0.036 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:20:00 | 22.79 | 0.00820 |
NE STAIR | 1491.19 | 1491.19 | 0.132 | 0.132 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 31.23 | 0.00820 |
NW ELEVATOR | 1397.06 | 1397.06 | 0.123 | 0.123 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 29.76 | 0.00820 |
NW STAIR | 1607.69 | 1607.69 | 0.142 | 0.142 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.53 | 0.00820 |
SW STAIR | 1080.55 | 1080.55 | 0.095 | 0.095 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 16:20:00 | 30.53 | 0.00820 |
Calculated Design Load [W] | User Design Load [W] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak | Temperature at Peak [C] | Humidity Ratio at Peak [kgWater/kgAir] | |
FLOOR 1 ANESTHESIA | 6.65 | 6.65 | 0.000 | 0.015 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80 | 0.00506 |
FLOOR 1 CAFE | 0.00 | 0.00 | 0.000 | 0.184 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.000 | 0.018 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.000 | 0.023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.000 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 DRESSING ROOM | 124.89 | 124.89 | 0.005 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.000 | 0.002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.000 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 LOBBY | 47.98 | 47.98 | 0.002 | 0.032 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | 3.80 | 0.00506 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.000 | 0.042 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.000 | 0.023 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.000 | 0.024 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.000 | 0.062 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.000 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.000 | 0.020 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.000 | 0.019 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 0.00 | 0.000 | 0.239 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 0.00 | 0.000 | 0.249 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 0.00 | 0.000 | 0.247 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PACU | 0.00 | 0.00 | 0.000 | 0.032 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.000 | 0.052 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.000 | 0.093 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PROCEDURE ROOM | 0.00 | 0.00 | 0.000 | 0.108 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 RECEPTION | 0.00 | 0.00 | 0.000 | 0.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 RECOVERY ROOM | 8.06 | 8.06 | 0.000 | 0.161 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80 | 0.00506 |
FLOOR 1 SCHEDULING | 0.00 | 0.00 | 0.000 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.000 | 0.018 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 SOIL HOLD | 0.00 | 0.00 | 0.000 | 0.008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.000 | 0.025 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 STEP DOWN | 126.32 | 126.32 | 0.005 | 0.090 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 CONFERENCE | 605.45 | 605.45 | 0.026 | 0.049 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.000 | 0.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM 1 | 537.56 | 537.56 | 0.023 | 0.051 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM 2 | 0.00 | 0.00 | 0.000 | 0.076 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM 3 | 0.00 | 0.00 | 0.000 | 0.102 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM 4 | 112.30 | 112.30 | 0.005 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM 5 | 248.59 | 248.59 | 0.011 | 0.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM 6 | 52.85 | 52.85 | 0.002 | 0.032 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.000 | 0.112 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM 8 | 1.27 | 1.27 | 0.000 | 0.038 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.000 | 0.056 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.000 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.000 | 0.011 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.000 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 OFFICE | 773.10 | 773.10 | 0.033 | 0.033 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 RECEPTION | 166.73 | 166.73 | 0.007 | 0.098 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.000 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.000 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 WORK | 0.00 | 0.00 | 0.000 | 0.068 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 X-RAY | 0.00 | 0.00 | 0.000 | 0.127 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 DRESSING ROOM | 0.00 | 0.00 | 0.000 | 0.002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 HUMID | 0.00 | 0.00 | 0.000 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 LOCKER | 0.00 | 0.00 | 0.000 | 0.008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 LOUNGE | 0.00 | 0.00 | 0.000 | 0.048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 OFFICE | 422.43 | 422.43 | 0.018 | 0.122 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 PHYSICAL THERAPY 1 | 1910.77 | 1910.77 | 0.081 | 0.184 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 PHYSICAL THERAPY 2 | 49.71 | 49.71 | 0.002 | 0.084 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80 | 0.00506 |
FLOOR 3 TREATMENT | 0.00 | 0.00 | 0.000 | 0.067 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 3 WORK | 1066.88 | 1066.88 | 0.045 | 0.045 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 BIO HAZ | 32.84 | 32.84 | 0.001 | 0.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 ELEVATOR PUMP ROOM | 119.20 | 119.20 | 0.005 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.000 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.000 | 0.007 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 LOBBY TOILET | 98.77 | 98.77 | 0.004 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.000 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 MED GAS | 316.73 | 316.73 | 0.014 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.000 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 MRI TOILET | 19.01 | 19.01 | 0.001 | 0.001 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.000 | 0.014 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.000 | 0.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.000 | 0.015 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 PRE-OP TOILET | 68.21 | 68.21 | 0.003 | 0.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 SCRUB | 0.15 | 0.15 | 0.000 | 0.002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 07:10:00 | 3.80 | 0.00506 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.000 | 0.017 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.000 | 0.022 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 STORAGE | 2125.73 | 2125.73 | 0.091 | 0.091 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 SUB-STERILE | 269.61 | 269.61 | 0.012 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 UTILITY HALL | 551.84 | 551.84 | 0.024 | 0.024 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.000 | 0.002 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 1 UTILITY ROOM | 500.69 | 500.69 | 0.022 | 0.022 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 1 VESTIBULE | 101.46 | 101.46 | 0.004 | 0.004 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM HALL 1 | 11.77 | 11.77 | 0.001 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 3.80 | 0.00506 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.000 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.000 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.000 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 JANITOR | 255.72 | 255.72 | 0.011 | 0.011 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.000 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.000 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.000 | 0.003 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.000 | 0.007 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.000 | 0.008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 UTILITY | 270.49 | 270.49 | 0.012 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.000 | 0.024 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00506 | |
FLOOR 2 WORK TOILET | 143.62 | 143.62 | 0.006 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 ELEVATOR HALL | 378.62 | 378.62 | 0.016 | 0.016 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 JANITOR | 298.44 | 298.44 | 0.013 | 0.013 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 LOUNGE TOILET | 255.54 | 255.54 | 0.011 | 0.011 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 MECHANICAL HALL | 284.26 | 284.26 | 0.012 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 OFFICE HALL | 365.24 | 365.24 | 0.016 | 0.024 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 OFFICE TOILET | 195.19 | 195.19 | 0.008 | 0.008 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 STORAGE 1 | 76.52 | 76.52 | 0.003 | 0.006 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 STORAGE 2 | 50.48 | 50.48 | 0.002 | 0.005 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 UNDEVELOPED 1 | 1627.16 | 1627.16 | 0.070 | 0.128 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 UNDEVELOPED 2 | 1734.68 | 1734.68 | 0.074 | 0.074 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
FLOOR 3 UTILITY | 153.97 | 153.97 | 0.007 | 0.012 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
NE STAIR | 1719.56 | 1719.56 | 0.074 | 0.074 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
NW ELEVATOR | 1120.89 | 1120.89 | 0.048 | 0.048 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
NW STAIR | 1732.83 | 1732.83 | 0.074 | 0.074 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
SW STAIR | 867.92 | 867.92 | 0.037 | 0.037 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 3.80 | 0.00506 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | |
AHU-1 | 7.06 | 7.06 | 2.16 | 2.16 |
AHU-2 | 10.09 | 10.09 | 2.20 | 2.20 |
Report: System Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
AHU-2_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 10.09 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule | |
FLOOR 2 CONFERENCE | AHU-2_DCV | 0.000000 | 0.001575 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 DICTATION | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 3 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 4 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 5 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 6 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 7 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 8 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM 9 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 1 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 NURSE STATION 2 | AHU-2_DCV | 0.000000 | 0.000813 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION | AHU-2_DCV | 0.000000 | 0.001067 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 1 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 SCHEDULING 2 | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 X-RAY | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 DRESSING ROOM | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 HUMID | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOCKER | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE | AHU-2_DCV | 0.000000 | 0.000686 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 1 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY 2 | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 TREATMENT | AHU-2_DCV | 0.000000 | 0.001524 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 WORK | AHU-2_DCV | 0.000000 | 0.000432 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 CONFERENCE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 1 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 2 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 3 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 4 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 5 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 EXAM HALL 6 | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 RECEPTION TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 STORAGE 3 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 2 WORK TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 ELEVATOR HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 JANITOR | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 LOUNGE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 MECHANICAL HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE HALL | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 OFFICE TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 PHYSICAL THERAPY TOILET | AHU-2_DCV | 0.000000 | 0.000000 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 STORAGE 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 1 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UNDEVELOPED 2 | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
FLOOR 3 UTILITY | AHU-2_DCV | 0.000000 | 0.000610 | 1.00 | 1.00 | Constant-0.0 |
NE STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW ELEVATOR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
NW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
SW STAIR | AHU-2_DCV | 0.000000 | 0.000305 | 1.00 | 1.00 | Constant-0.0 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
FLOOR 1 ANESTHESIA | 4223.50 | 7830.00 | 4223.50 |
FLOOR 1 CAFE | 234.33 | 7661.17 | 215.67 |
FLOOR 1 CLEAN | 1703.83 | 7830.00 | 1703.83 |
FLOOR 1 CLEAN WORK | 3030.00 | 7830.00 | 3030.00 |
FLOOR 1 DICTATION | 108.67 | 7830.00 | 108.67 |
FLOOR 1 DRESSING ROOM | 1719.33 | 7830.00 | 1719.33 |
FLOOR 1 HUMID | 13.17 | 7830.00 | 13.17 |
FLOOR 1 IT ROOM | 335.67 | 7830.00 | 335.67 |
FLOOR 1 LOBBY | 201.83 | 7830.00 | 201.83 |
FLOOR 1 LOCKER ROOM | 21.67 | 7830.00 | 21.67 |
FLOOR 1 LOUNGE | 10.50 | 7830.00 | 10.50 |
FLOOR 1 MRI CONTROL ROOM | 107.67 | 7830.00 | 107.67 |
FLOOR 1 MRI ROOM | 5.33 | 7830.00 | 5.33 |
FLOOR 1 NOURISHMENT | 20.50 | 7830.00 | 20.50 |
FLOOR 1 NURSE STATION | 102.67 | 7830.00 | 102.67 |
FLOOR 1 OFFICE | 19.17 | 7830.00 | 19.17 |
FLOOR 1 OPERATING ROOM 1 | 3483.83 | 7830.00 | 3483.83 |
FLOOR 1 OPERATING ROOM 2 | 3830.00 | 7830.00 | 3830.00 |
FLOOR 1 OPERATING ROOM 3 | 7830.00 | 7830.00 | 7830.00 |
FLOOR 1 PACU | 3760.83 | 7830.00 | 3760.83 |
FLOOR 1 PRE-OP ROOM 1 | 4193.50 | 7830.00 | 4193.50 |
FLOOR 1 PRE-OP ROOM 2 | 3984.50 | 7830.00 | 3984.50 |
FLOOR 1 PROCEDURE ROOM | 4173.67 | 7830.00 | 4173.67 |
FLOOR 1 RECEPTION | 39.17 | 7830.00 | 39.17 |
FLOOR 1 RECOVERY ROOM | 3670.33 | 7795.17 | 3670.33 |
FLOOR 1 SCHEDULING | 233.50 | 7830.00 | 233.50 |
FLOOR 1 SOIL | 4426.00 | 7830.00 | 4426.00 |
FLOOR 1 SOIL HOLD | 4510.83 | 7830.00 | 4510.83 |
FLOOR 1 SOIL WORK | 4483.00 | 7830.00 | 4483.00 |
FLOOR 1 STEP DOWN | 3269.00 | 7815.00 | 3269.00 |
FLOOR 2 CONFERENCE | 1098.00 | 7790.17 | 1098.00 |
FLOOR 2 DICTATION | 600.50 | 7830.00 | 600.50 |
FLOOR 2 EXAM 1 | 2061.00 | 7824.67 | 2061.00 |
FLOOR 2 EXAM 2 | 2798.67 | 7830.00 | 2798.67 |
FLOOR 2 EXAM 3 | 3122.83 | 7830.00 | 3122.83 |
FLOOR 2 EXAM 4 | 2374.33 | 7825.83 | 2374.33 |
FLOOR 2 EXAM 5 | 1731.83 | 7830.00 | 1731.83 |
FLOOR 2 EXAM 6 | 3057.17 | 7830.00 | 3057.17 |
FLOOR 2 EXAM 7 | 3144.00 | 7830.00 | 3144.00 |
FLOOR 2 EXAM 8 | 2611.50 | 7830.00 | 2611.50 |
FLOOR 2 EXAM 9 | 2439.50 | 7830.00 | 2439.50 |
FLOOR 2 LOUNGE | 200.17 | 7830.00 | 200.17 |
FLOOR 2 NURSE STATION 1 | 184.17 | 7830.00 | 184.17 |
FLOOR 2 NURSE STATION 2 | 170.50 | 7830.00 | 170.50 |
FLOOR 2 OFFICE | 365.67 | 7830.00 | 365.67 |
FLOOR 2 RECEPTION | 391.50 | 7830.00 | 391.50 |
FLOOR 2 SCHEDULING 1 | 89.83 | 7830.00 | 89.83 |
FLOOR 2 SCHEDULING 2 | 104.00 | 7830.00 | 104.00 |
FLOOR 2 WORK | 155.00 | 7830.00 | 155.00 |
FLOOR 2 X-RAY | 2.50 | 7698.67 | 0.00 |
FLOOR 3 DRESSING ROOM | 1180.17 | 7830.00 | 1180.17 |
FLOOR 3 HUMID | 789.67 | 7830.00 | 789.67 |
FLOOR 3 LOCKER | 294.33 | 7830.00 | 294.33 |
FLOOR 3 LOUNGE | 188.50 | 7830.00 | 188.50 |
FLOOR 3 OFFICE | 449.67 | 7830.00 | 449.67 |
FLOOR 3 PHYSICAL THERAPY 1 | 3310.17 | 7680.67 | 3305.83 |
FLOOR 3 PHYSICAL THERAPY 2 | 3421.33 | 7830.00 | 3421.33 |
FLOOR 3 TREATMENT | 2811.00 | 7830.00 | 2811.00 |
FLOOR 3 WORK | 711.50 | 7830.00 | 711.50 |
FLOOR 1 BIO HAZ | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 0.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.00 | 0.00 | 0.00 |
NE STAIR | 0.00 | 0.00 | 0.00 |
NW ELEVATOR | 0.00 | 0.00 | 0.00 |
NW STAIR | 0.00 | 0.00 | 0.00 |
SW STAIR | 0.00 | 0.00 | 0.00 |
Facility | 7830.00 | 7830.00 | 7830.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
FLOOR 1 ANESTHESIA | 0.00 | 1.00 | 0.00 | 1.00 |
FLOOR 1 CAFE | 0.00 | 130.67 | 0.00 | 130.67 |
FLOOR 1 CLEAN | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 CLEAN WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 DRESSING ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 IT ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI CONTROL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NOURISHMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE STATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 OPERATING ROOM 1 | 0.00 | 252.50 | 0.00 | 252.50 |
FLOOR 1 OPERATING ROOM 2 | 0.00 | 261.00 | 0.00 | 260.83 |
FLOOR 1 OPERATING ROOM 3 | 0.00 | 170.17 | 0.00 | 170.17 |
FLOOR 1 PACU | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP ROOM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP ROOM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PROCEDURE ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION | 0.00 | 23.33 | 0.00 | 23.33 |
FLOOR 1 RECOVERY ROOM | 0.00 | 79.67 | 0.00 | 79.67 |
FLOOR 1 SCHEDULING | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL HOLD | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SOIL WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STEP DOWN | 0.00 | 35.00 | 0.00 | 35.00 |
FLOOR 2 CONFERENCE | 0.00 | 13.00 | 0.00 | 13.00 |
FLOOR 2 DICTATION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 3 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 4 | 0.00 | 40.33 | 0.00 | 40.33 |
FLOOR 2 EXAM 5 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 6 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 7 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 8 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM 9 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 NURSE STATION 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 SCHEDULING 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 X-RAY | 0.00 | 336.83 | 0.00 | 336.83 |
FLOOR 3 DRESSING ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 HUMID | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOCKER | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY 1 | 0.00 | 12.33 | 0.00 | 12.33 |
FLOOR 3 PHYSICAL THERAPY 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 TREATMENT | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 WORK | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 BIO HAZ | 11.83 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELECTRICAL ROOM | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 ELEVATOR PUMP ROOM | 0.00 | 0.67 | 0.00 | 0.00 |
FLOOR 1 IT HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOBBY TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 LOCKER ROOM HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MED GAS | 28.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 MRI TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 NURSE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 PRE-OP TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 RECEPTION HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SCRUB | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STERILE STORAGE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 STORAGE | 33.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 SUB-STERILE | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY HALL | 2.33 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY JANITOR | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 UTILITY ROOM | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 1 VESTIBULE | 2051.67 | 456.00 | 0.00 | 0.00 |
FLOOR 2 CONFERENCE TOILET | 4283.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 1 | 3.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 2 | 6.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 3 | 8.50 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 4 | 2.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 5 | 1.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 EXAM HALL 6 | 2.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 JANITOR | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 OFFICE HALL | 0.67 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 RECEPTION TOILET | 4001.83 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 1 | 6.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 2 STORAGE 3 | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 UTILITY | 0.33 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK HALL | 0.17 | 0.00 | 0.00 | 0.00 |
FLOOR 2 WORK TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 ELEVATOR HALL | 6.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 JANITOR | 2.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 LOUNGE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL | 0.00 | 5369.67 | 0.00 | 0.00 |
FLOOR 3 MECHANICAL HALL | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE HALL | 3.50 | 0.00 | 0.00 | 0.00 |
FLOOR 3 OFFICE TOILET | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 PHYSICAL THERAPY TOILET | 4690.33 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 STORAGE 2 | 0.50 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 1 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UNDEVELOPED 2 | 0.00 | 0.00 | 0.00 | 0.00 |
FLOOR 3 UTILITY | 0.67 | 0.00 | 0.00 | 0.00 |
NE STAIR | 1.50 | 2.33 | 0.00 | 0.00 |
NW ELEVATOR | 4.83 | 0.00 | 0.00 | 0.00 |
NW STAIR | 3.33 | 0.00 | 0.00 | 0.00 |
SW STAIR | 1.17 | 5.17 | 0.00 | 0.00 |
Facility | 4828.50 | 6176.50 | 0.00 | 634.83 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2018-10-19 19:10:35
AirTerminal:SingleDuct:VAV:ReheatMaximum Air Flow Rate [m3/s] | Maximum Reheat Water Flow Rate [m3/s] | Reheat Coil Sizing Air Volume Flow Rate [m3/s] | |
FLOOR 1 ANESTHESIA VAV BOX COMPONENT | 0.067956 | 0.000043 | 0.067956 |
FLOOR 1 BIO HAZ VAV BOX COMPONENT | 0.006224 | 0.000001 | 0.001430 |
FLOOR 1 CAFE VAV BOX COMPONENT | 0.296372 | 0.000038 | 0.059274 |
FLOOR 1 CLEAN VAV BOX COMPONENT | 0.041497 | 0.000026 | 0.041497 |
FLOOR 1 CLEAN WORK VAV BOX COMPONENT | 0.051911 | 0.000033 | 0.051911 |
FLOOR 1 DICTATION VAV BOX COMPONENT | 0.025316 | 0.000003 | 0.005063 |
FLOOR 1 DRESSING ROOM VAV BOX COMPONENT | 0.014560 | 0.000003 | 0.005373 |
FLOOR 1 ELECTRICAL ROOM VAV BOX COMPONENT | 0.044622 | 0.000006 | 0.008924 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX COMPONENT | 0.278201 | 0.000035 | 0.055640 |
FLOOR 1 HUMID VAV BOX COMPONENT | 0.012486 | 0.000002 | 0.002497 |
FLOOR 1 IT HALL VAV BOX COMPONENT | 0.017943 | 0.000002 | 0.003589 |
FLOOR 1 IT ROOM VAV BOX COMPONENT | 0.020282 | 0.000003 | 0.004056 |
FLOOR 1 LOBBY VAV BOX COMPONENT | 0.266872 | 0.000034 | 0.053374 |
FLOOR 1 LOBBY HALL VAV BOX COMPONENT | 0.038031 | 0.000005 | 0.007606 |
FLOOR 1 LOBBY TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 LOCKER ROOM VAV BOX COMPONENT | 0.224109 | 0.000028 | 0.044822 |
FLOOR 1 LOCKER ROOM HALL VAV BOX COMPONENT | 0.056561 | 0.000007 | 0.011312 |
FLOOR 1 LOUNGE VAV BOX COMPONENT | 0.113237 | 0.000014 | 0.022647 |
FLOOR 1 MED GAS VAV BOX COMPONENT | 0.015756 | 0.000009 | 0.013664 |
FLOOR 1 MRI CONTROL ROOM VAV BOX COMPONENT | 0.158564 | 0.000020 | 0.031713 |
FLOOR 1 MRI HALL VAV BOX COMPONENT | 0.024101 | 0.000003 | 0.004820 |
FLOOR 1 MRI ROOM VAV BOX COMPONENT | 0.415288 | 0.000053 | 0.083058 |
FLOOR 1 MRI TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 NOURISHMENT VAV BOX COMPONENT | 0.055943 | 0.000007 | 0.011189 |
FLOOR 1 NURSE HALL VAV BOX COMPONENT | 0.067700 | 0.000009 | 0.013540 |
FLOOR 1 NURSE JANITOR VAV BOX COMPONENT | 0.008567 | 0.000001 | 0.001713 |
FLOOR 1 NURSE STATION VAV BOX COMPONENT | 0.075107 | 0.000010 | 0.015021 |
FLOOR 1 NURSE TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 OFFICE VAV BOX COMPONENT | 0.081614 | 0.000010 | 0.016323 |
FLOOR 1 OPERATING ROOM 1 VAV BOX COMPONENT | 0.766414 | 0.000291 | 0.459848 |
FLOOR 1 OPERATING ROOM 2 VAV BOX COMPONENT | 0.789181 | 0.000300 | 0.473509 |
FLOOR 1 OPERATING ROOM 3 VAV BOX COMPONENT | 0.748776 | 0.000474 | 0.748776 |
FLOOR 1 PACU VAV BOX COMPONENT | 0.050967 | 0.000032 | 0.050967 |
FLOOR 1 PRE-OP HALL VAV BOX COMPONENT | 0.067395 | 0.000009 | 0.013479 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX COMPONENT | 0.089192 | 0.000056 | 0.089192 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX COMPONENT | 0.159508 | 0.000101 | 0.159508 |
FLOOR 1 PRE-OP TOILET VAV BOX COMPONENT | 0.042473 | 0.000027 | 0.042473 |
FLOOR 1 PROCEDURE ROOM VAV BOX COMPONENT | 0.336241 | 0.000213 | 0.336241 |
FLOOR 1 RECEPTION VAV BOX COMPONENT | 0.170524 | 0.000022 | 0.034105 |
FLOOR 1 RECEPTION HALL VAV BOX COMPONENT | 0.017563 | 0.000002 | 0.003513 |
FLOOR 1 RECOVERY ROOM VAV BOX COMPONENT | 0.279994 | 0.000154 | 0.243594 |
FLOOR 1 SCHEDULING VAV BOX COMPONENT | 0.028780 | 0.000004 | 0.005756 |
FLOOR 1 SCRUB VAV BOX COMPONENT | 0.010649 | 0.000001 | 0.002130 |
FLOOR 1 SOIL VAV BOX COMPONENT | 0.099103 | 0.000063 | 0.099103 |
FLOOR 1 SOIL HOLD VAV BOX COMPONENT | 0.044046 | 0.000028 | 0.044046 |
FLOOR 1 SOIL WORK VAV BOX COMPONENT | 0.141575 | 0.000090 | 0.141575 |
FLOOR 1 STEP DOWN VAV BOX COMPONENT | 0.173424 | 0.000076 | 0.119662 |
FLOOR 1 STERILE HALL VAV BOX COMPONENT | 0.070906 | 0.000009 | 0.014181 |
FLOOR 1 STERILE STORAGE VAV BOX COMPONENT | 0.040479 | 0.000005 | 0.008096 |
FLOOR 1 STORAGE VAV BOX COMPONENT | 0.130452 | 0.000057 | 0.090782 |
FLOOR 1 SUB-STERILE VAV BOX COMPONENT | 0.052253 | 0.000007 | 0.011633 |
FLOOR 1 UTILITY HALL VAV BOX COMPONENT | 0.050806 | 0.000015 | 0.023639 |
FLOOR 1 UTILITY JANITOR VAV BOX COMPONENT | 0.005859 | 0.000001 | 0.001172 |
FLOOR 1 UTILITY ROOM VAV BOX COMPONENT | 0.063870 | 0.000014 | 0.021522 |
FLOOR 1 VESTIBULE VAV BOX COMPONENT | 0.023259 | 0.000003 | 0.004652 |
FLOOR 2 CONFERENCE VAV BOX COMPONENT | 0.246209 | ||
FLOOR 2 CONFERENCE TOILET VAV BOX COMPONENT | 0.050338 | ||
FLOOR 2 DICTATION VAV BOX COMPONENT | 0.021411 | ||
FLOOR 2 EXAM 1 VAV BOX COMPONENT | 0.253018 | ||
FLOOR 2 EXAM 2 VAV BOX COMPONENT | 0.254836 | ||
FLOOR 2 EXAM 3 VAV BOX COMPONENT | 0.339781 | ||
FLOOR 2 EXAM 4 VAV BOX COMPONENT | 0.052630 | ||
FLOOR 2 EXAM 5 VAV BOX COMPONENT | 0.207427 | ||
FLOOR 2 EXAM 6 VAV BOX COMPONENT | 0.106182 | ||
FLOOR 2 EXAM 7 VAV BOX COMPONENT | 0.373759 | ||
FLOOR 2 EXAM 8 VAV BOX COMPONENT | 0.127418 | ||
FLOOR 2 EXAM 9 VAV BOX COMPONENT | 0.186879 | ||
FLOOR 2 EXAM HALL 1 VAV BOX COMPONENT | 0.048082 | ||
FLOOR 2 EXAM HALL 2 VAV BOX COMPONENT | 0.047750 | ||
FLOOR 2 EXAM HALL 3 VAV BOX COMPONENT | 0.046008 | ||
FLOOR 2 EXAM HALL 4 VAV BOX COMPONENT | 0.046949 | ||
FLOOR 2 EXAM HALL 5 VAV BOX COMPONENT | 0.049372 | ||
FLOOR 2 EXAM HALL 6 VAV BOX COMPONENT | 0.049247 | ||
FLOOR 2 JANITOR VAV BOX COMPONENT | 0.035728 | ||
FLOOR 2 LOUNGE VAV BOX COMPONENT | 0.035103 | ||
FLOOR 2 NURSE STATION 1 VAV BOX COMPONENT | 0.056411 | ||
FLOOR 2 NURSE STATION 2 VAV BOX COMPONENT | 0.068853 | ||
FLOOR 2 OFFICE VAV BOX COMPONENT | 0.262100 | ||
FLOOR 2 OFFICE HALL VAV BOX COMPONENT | 0.100581 | ||
FLOOR 2 RECEPTION VAV BOX COMPONENT | 0.491362 | ||
FLOOR 2 RECEPTION HALL VAV BOX COMPONENT | 0.147858 | ||
FLOOR 2 RECEPTION TOILET VAV BOX COMPONENT | 0.099103 | ||
FLOOR 2 SCHEDULING 1 VAV BOX COMPONENT | 0.082228 | ||
FLOOR 2 SCHEDULING 2 VAV BOX COMPONENT | 0.089963 | ||
FLOOR 2 STORAGE 1 VAV BOX COMPONENT | 0.014317 | ||
FLOOR 2 STORAGE 2 VAV BOX COMPONENT | 0.024991 | ||
FLOOR 2 STORAGE 3 VAV BOX COMPONENT | 0.032473 | ||
FLOOR 2 UTILITY VAV BOX COMPONENT | 0.053840 | ||
FLOOR 2 WORK VAV BOX COMPONENT | 0.399972 | ||
FLOOR 2 WORK HALL VAV BOX COMPONENT | 0.202957 | ||
FLOOR 2 WORK TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 2 X-RAY VAV BOX COMPONENT | 0.849452 | ||
FLOOR 3 DRESSING ROOM VAV BOX COMPONENT | 0.015968 | ||
FLOOR 3 ELEVATOR HALL VAV BOX COMPONENT | 0.075143 | ||
FLOOR 3 HUMID VAV BOX COMPONENT | 0.040148 | ||
FLOOR 3 JANITOR VAV BOX COMPONENT | 0.020251 | ||
FLOOR 3 LOCKER VAV BOX COMPONENT | 0.062994 | ||
FLOOR 3 LOUNGE VAV BOX COMPONENT | 0.373833 | ||
FLOOR 3 LOUNGE TOILET VAV BOX COMPONENT | 0.151014 | ||
FLOOR 3 MECHANICAL VAV BOX COMPONENT | 0.318229 | ||
FLOOR 3 MECHANICAL HALL VAV BOX COMPONENT | 0.082938 | ||
FLOOR 3 OFFICE VAV BOX COMPONENT | 0.899271 | ||
FLOOR 3 OFFICE HALL VAV BOX COMPONENT | 0.195028 | ||
FLOOR 3 OFFICE TOILET VAV BOX COMPONENT | 0.042473 | ||
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX COMPONENT | 0.745586 | ||
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX COMPONENT | 0.279375 | ||
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX COMPONENT | 0.066069 | ||
FLOOR 3 STORAGE 1 VAV BOX COMPONENT | 0.023310 | ||
FLOOR 3 STORAGE 2 VAV BOX COMPONENT | 0.020790 | ||
FLOOR 3 TREATMENT VAV BOX COMPONENT | 0.224633 | ||
FLOOR 3 UNDEVELOPED 1 VAV BOX COMPONENT | 0.758189 | ||
FLOOR 3 UNDEVELOPED 2 VAV BOX COMPONENT | 0.395152 | ||
FLOOR 3 UTILITY VAV BOX COMPONENT | 0.036416 | ||
FLOOR 3 WORK VAV BOX COMPONENT | 0.297870 | ||
NE STAIR VAV BOX COMPONENT | 0.131521 | ||
NW ELEVATOR VAV BOX COMPONENT | 0.123219 | ||
NW STAIR VAV BOX COMPONENT | 0.141796 | ||
SW STAIR VAV BOX COMPONENT | 0.095303 |
Design Coil Load [W] | Maximum Water Flow Rate [m3/s] | U-Factor Times Area Value [W/K] | |
FLOOR 1 ANESTHESIA VAV BOX REHEAT COIL | 1998.79 | 0.000043 | 43.10 |
FLOOR 1 BIO HAZ VAV BOX REHEAT COIL | 42.05 | 0.000001 | 1.97 |
FLOOR 1 CAFE VAV BOX REHEAT COIL | 1743.43 | 0.000038 | 93.98 |
FLOOR 1 CLEAN VAV BOX REHEAT COIL | 1220.54 | 0.000026 | 26.32 |
FLOOR 1 CLEAN WORK VAV BOX REHEAT COIL | 1526.85 | 0.000033 | 32.92 |
FLOOR 1 DICTATION VAV BOX REHEAT COIL | 148.93 | 0.000003 | 8.03 |
FLOOR 1 DRESSING ROOM VAV BOX REHEAT COIL | 158.04 | 0.000003 | 4.62 |
FLOOR 1 ELECTRICAL ROOM VAV BOX REHEAT COIL | 262.49 | 0.000006 | 14.15 |
FLOOR 1 ELEVATOR PUMP ROOM VAV BOX REHEAT COIL | 1636.54 | 0.000035 | 88.21 |
FLOOR 1 HUMID VAV BOX REHEAT COIL | 73.45 | 0.000002 | 3.96 |
FLOOR 1 IT HALL VAV BOX REHEAT COIL | 105.55 | 0.000002 | 5.69 |
FLOOR 1 IT ROOM VAV BOX REHEAT COIL | 119.31 | 0.000003 | 6.43 |
FLOOR 1 LOBBY VAV BOX REHEAT COIL | 1569.90 | 0.000034 | 84.62 |
FLOOR 1 LOBBY HALL VAV BOX REHEAT COIL | 223.72 | 0.000005 | 12.06 |
FLOOR 1 LOBBY TOILET VAV BOX REHEAT COIL | 1249.24 | 0.000027 | 26.94 |
FLOOR 1 LOCKER ROOM VAV BOX REHEAT COIL | 1318.34 | 0.000028 | 71.06 |
FLOOR 1 LOCKER ROOM HALL VAV BOX REHEAT COIL | 332.72 | 0.000007 | 17.93 |
FLOOR 1 LOUNGE VAV BOX REHEAT COIL | 666.13 | 0.000014 | 35.91 |
FLOOR 1 MED GAS VAV BOX REHEAT COIL | 401.91 | 0.000009 | 8.67 |
FLOOR 1 MRI CONTROL ROOM VAV BOX REHEAT COIL | 932.77 | 0.000020 | 50.28 |
FLOOR 1 MRI HALL VAV BOX REHEAT COIL | 141.78 | 0.000003 | 7.64 |
FLOOR 1 MRI ROOM VAV BOX REHEAT COIL | 2442.97 | 0.000053 | 131.68 |
FLOOR 1 MRI TOILET VAV BOX REHEAT COIL | 1249.24 | 0.000027 | 26.94 |
FLOOR 1 NOURISHMENT VAV BOX REHEAT COIL | 329.09 | 0.000007 | 17.74 |
FLOOR 1 NURSE HALL VAV BOX REHEAT COIL | 398.25 | 0.000009 | 21.47 |
FLOOR 1 NURSE JANITOR VAV BOX REHEAT COIL | 50.40 | 0.000001 | 2.72 |
FLOOR 1 NURSE STATION VAV BOX REHEAT COIL | 441.82 | 0.000010 | 23.82 |
FLOOR 1 NURSE TOILET VAV BOX REHEAT COIL | 1249.24 | 0.000027 | 26.94 |
FLOOR 1 OFFICE VAV BOX REHEAT COIL | 480.10 | 0.000010 | 25.88 |
FLOOR 1 OPERATING ROOM 1 VAV BOX REHEAT COIL | 13525.50 | 0.000291 | 291.63 |
FLOOR 1 OPERATING ROOM 2 VAV BOX REHEAT COIL | 13927.29 | 0.000300 | 300.29 |
FLOOR 1 OPERATING ROOM 3 VAV BOX REHEAT COIL | 22023.72 | 0.000474 | 474.86 |
FLOOR 1 PACU VAV BOX REHEAT COIL | 1499.09 | 0.000032 | 32.32 |
FLOOR 1 PRE-OP HALL VAV BOX REHEAT COIL | 396.46 | 0.000009 | 21.37 |
FLOOR 1 PRE-OP ROOM 1 VAV BOX REHEAT COIL | 2623.41 | 0.000056 | 56.56 |
FLOOR 1 PRE-OP ROOM 2 VAV BOX REHEAT COIL | 4691.61 | 0.000101 | 101.16 |
FLOOR 1 PRE-OP TOILET VAV BOX REHEAT COIL | 1249.24 | 0.000027 | 26.94 |
FLOOR 1 PROCEDURE ROOM VAV BOX REHEAT COIL | 9889.85 | 0.000213 | 213.24 |
FLOOR 1 RECEPTION VAV BOX REHEAT COIL | 1003.12 | 0.000022 | 54.07 |
FLOOR 1 RECEPTION HALL VAV BOX REHEAT COIL | 103.32 | 0.000002 | 5.57 |
FLOOR 1 RECOVERY ROOM VAV BOX REHEAT COIL | 7164.83 | 0.000154 | 154.48 |
FLOOR 1 SCHEDULING VAV BOX REHEAT COIL | 169.30 | 0.000004 | 9.13 |
FLOOR 1 SCRUB VAV BOX REHEAT COIL | 62.64 | 0.000001 | 3.38 |
FLOOR 1 SOIL VAV BOX REHEAT COIL | 2914.90 | 0.000063 | 62.85 |
FLOOR 1 SOIL HOLD VAV BOX REHEAT COIL | 1295.51 | 0.000028 | 27.93 |
FLOOR 1 SOIL WORK VAV BOX REHEAT COIL | 4164.15 | 0.000090 | 89.78 |
FLOOR 1 STEP DOWN VAV BOX REHEAT COIL | 3519.63 | 0.000076 | 75.89 |
FLOOR 1 STERILE HALL VAV BOX REHEAT COIL | 417.11 | 0.000009 | 22.48 |
FLOOR 1 STERILE STORAGE VAV BOX REHEAT COIL | 238.12 | 0.000005 | 12.84 |
FLOOR 1 STORAGE VAV BOX REHEAT COIL | 2670.16 | 0.000057 | 57.57 |
FLOOR 1 SUB-STERILE VAV BOX REHEAT COIL | 342.16 | 0.000007 | 16.57 |
FLOOR 1 UTILITY HALL VAV BOX REHEAT COIL | 695.28 | 0.000015 | 16.11 |
FLOOR 1 UTILITY JANITOR VAV BOX REHEAT COIL | 34.47 | 0.000001 | 1.86 |
FLOOR 1 UTILITY ROOM VAV BOX REHEAT COIL | 633.03 | 0.000014 | 20.25 |
FLOOR 1 VESTIBULE VAV BOX REHEAT COIL | 136.82 | 0.000003 | 7.38 |
AHU-1_HEATC | 13015.82 | 0.000280 | 213.61 |
AHU-1_EXTRAWATERHEATC | 13015.82 | 0.000280 | 213.61 |
AHU-2_HEATC | 70343.56 | 0.001514 | 1133.82 |
Nominal Capacity [W] | |
FLOOR 2 CONFERENCE VAV BOX REHEAT COIL | 2421.11 |
FLOOR 2 CONFERENCE TOILET VAV BOX REHEAT COIL | 0.000000 |
FLOOR 2 DICTATION VAV BOX REHEAT COIL | 138.30 |
FLOOR 2 EXAM 1 VAV BOX REHEAT COIL | 3732.04 |
FLOOR 2 EXAM 2 VAV BOX REHEAT COIL | 7370.30 |
FLOOR 2 EXAM 3 VAV BOX REHEAT COIL | 9827.06 |
FLOOR 2 EXAM 4 VAV BOX REHEAT COIL | 974.18 |
FLOOR 2 EXAM 5 VAV BOX REHEAT COIL | 4139.42 |
FLOOR 2 EXAM 6 VAV BOX REHEAT COIL | 2886.70 |
FLOOR 2 EXAM 7 VAV BOX REHEAT COIL | 10809.77 |
FLOOR 2 EXAM 8 VAV BOX REHEAT COIL | 3427.19 |
FLOOR 2 EXAM 9 VAV BOX REHEAT COIL | 5404.88 |
FLOOR 2 EXAM HALL 1 VAV BOX REHEAT COIL | 278.13 |
FLOOR 2 EXAM HALL 2 VAV BOX REHEAT COIL | 276.20 |
FLOOR 2 EXAM HALL 3 VAV BOX REHEAT COIL | 266.13 |
FLOOR 2 EXAM HALL 4 VAV BOX REHEAT COIL | 276.14 |
FLOOR 2 EXAM HALL 5 VAV BOX REHEAT COIL | 285.59 |
FLOOR 2 EXAM HALL 6 VAV BOX REHEAT COIL | 284.86 |
FLOOR 2 JANITOR VAV BOX REHEAT COIL | 318.71 |
FLOOR 2 LOUNGE VAV BOX REHEAT COIL | 251.04 |
FLOOR 2 NURSE STATION 1 VAV BOX REHEAT COIL | 557.86 |
FLOOR 2 NURSE STATION 2 VAV BOX REHEAT COIL | 669.43 |
FLOOR 2 OFFICE VAV BOX REHEAT COIL | 1516.08 |
FLOOR 2 OFFICE HALL VAV BOX REHEAT COIL | 619.24 |
FLOOR 2 RECEPTION VAV BOX REHEAT COIL | 4803.21 |
FLOOR 2 RECEPTION HALL VAV BOX REHEAT COIL | 855.26 |
FLOOR 2 RECEPTION TOILET VAV BOX REHEAT COIL | 0.000000 |
FLOOR 2 SCHEDULING 1 VAV BOX REHEAT COIL | 640.15 |
FLOOR 2 SCHEDULING 2 VAV BOX REHEAT COIL | 675.71 |
FLOOR 2 STORAGE 1 VAV BOX REHEAT COIL | 156.20 |
FLOOR 2 STORAGE 2 VAV BOX REHEAT COIL | 334.72 |
FLOOR 2 STORAGE 3 VAV BOX REHEAT COIL | 401.66 |
FLOOR 2 UTILITY VAV BOX REHEAT COIL | 351.45 |
FLOOR 2 WORK VAV BOX REHEAT COIL | 3339.05 |
FLOOR 2 WORK HALL VAV BOX REHEAT COIL | 1173.97 |
FLOOR 2 WORK TOILET VAV BOX REHEAT COIL | 1228.38 |
FLOOR 2 X-RAY VAV BOX REHEAT COIL | 6276.07 |
FLOOR 3 DRESSING ROOM VAV BOX REHEAT COIL | 92.36 |
FLOOR 3 ELEVATOR HALL VAV BOX REHEAT COIL | 516.02 |
FLOOR 3 HUMID VAV BOX REHEAT COIL | 232.23 |
FLOOR 3 JANITOR VAV BOX REHEAT COIL | 372.09 |
FLOOR 3 LOCKER VAV BOX REHEAT COIL | 376.56 |
FLOOR 3 LOUNGE VAV BOX REHEAT COIL | 2381.74 |
FLOOR 3 LOUNGE TOILET VAV BOX REHEAT COIL | 4367.58 |
FLOOR 3 MECHANICAL VAV BOX REHEAT COIL | 0.000000 |
FLOOR 3 MECHANICAL HALL VAV BOX REHEAT COIL | 479.75 |
FLOOR 3 OFFICE VAV BOX REHEAT COIL | 5998.27 |
FLOOR 3 OFFICE HALL VAV BOX REHEAT COIL | 1163.13 |
FLOOR 3 OFFICE TOILET VAV BOX REHEAT COIL | 1228.38 |
FLOOR 3 PHYSICAL THERAPY 1 VAV BOX REHEAT COIL | 14878.92 |
FLOOR 3 PHYSICAL THERAPY 2 VAV BOX REHEAT COIL | 6706.42 |
FLOOR 3 PHYSICAL THERAPY TOILET VAV BOX REHEAT COIL | 0.000000 |
FLOOR 3 STORAGE 1 VAV BOX REHEAT COIL | 674.18 |
FLOOR 3 STORAGE 2 VAV BOX REHEAT COIL | 234.30 |
FLOOR 3 TREATMENT VAV BOX REHEAT COIL | 5262.39 |
FLOOR 3 UNDEVELOPED 1 VAV BOX REHEAT COIL | 6326.28 |
FLOOR 3 UNDEVELOPED 2 VAV BOX REHEAT COIL | 3213.30 |
FLOOR 3 UTILITY VAV BOX REHEAT COIL | 602.49 |
FLOOR 3 WORK VAV BOX REHEAT COIL | 1722.99 |
NE STAIR VAV BOX REHEAT COIL | 2136.10 |
NW ELEVATOR VAV BOX REHEAT COIL | 1388.52 |
NW STAIR VAV BOX REHEAT COIL | 2148.85 |
SW STAIR VAV BOX REHEAT COIL | 1076.62 |
Maximum Flow Rate [m3/s] | |
AHU-1 AIR LOOP MAIN BRANCH | 7.06 |
AHU-2 AIR LOOP MAIN BRANCH | 10.09 |
Design Supply Air Flow Rate [m3/s] | |
AHU-1 | 7.06 |
AHU-2 | 10.09 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
AHU-1_OA_CONTROLLER | 7.06 | 2.07 |
AHU-2_OA_CONTROLLER | 10.09 |
Rated High Speed Air Flow Rate [m3/s] | Rated High Speed Total Cooling Capacity (gross) [W] | Rated High Speed Sensible Heat Ratio | Rated Low Speed Air Flow Rate [m3/s] | Rated Low Speed Total Cooling Capacity (gross) [W] | |
AHU-1_COOLC DXCOIL | 7.06 | 168520.11 | 0.685965 | 2.35 | 56167.75 |
AHU-2_COOLC DXCOIL | 10.09 | 194033.26 | 0.747350 | 3.36 | 64671.28 |
Maximum Flow Rate [m3/s] | |
AHU-1_FAN | 7.06 |
AHU-2_FAN | 10.09 |
Maximum Actuated Flow [m3/s] | |
AHU-1_HEATC_CONTROLLER | 0.000280 |
AHU-1_EXTRAWATERHEATC_CONTROLLER | 0.000280 |
AHU-2_HEATC_CONTROLLER | 0.001514 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SWHSYS1 | 0.000063 | 0.047375 |
HEATSYS1 | 0.001384 | 1.04 |
Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 0.001384 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000063 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
SWHSYS1 PUMP | 0.000063 | 8.07 |
Rated Flow Rate [m3/s] | Rated Power Consumption [W] | |
HEATSYS1 PUMP | 0.001384 | 353.59 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ANESTHESIA
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.47 | 13.22 |
February | 19.45 | 13.28 |
March | 19.51 | 12.64 |
April | 19.44 | 15.30 |
May | 19.45 | 15.56 |
June | 19.50 | 17.67 |
July | 19.41 | 19.43 |
August | 19.53 | 19.66 |
September | 19.47 | 18.47 |
October | 19.47 | 18.77 |
November | 19.49 | 14.32 |
December | 19.52 | 13.59 |
Annual Sum or Average | 19.48 | 16.01 |
Minimum of Months | 19.41 | 12.64 |
Maximum of Months | 19.53 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 BIO HAZ
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.46 | 13.22 |
February | 20.52 | 13.28 |
March | 20.66 | 12.64 |
April | 20.86 | 15.30 |
May | 20.95 | 15.56 |
June | 21.41 | 17.67 |
July | 21.47 | 19.43 |
August | 21.53 | 19.66 |
September | 21.28 | 18.47 |
October | 20.89 | 18.77 |
November | 20.58 | 14.32 |
December | 20.51 | 13.59 |
Annual Sum or Average | 20.93 | 16.01 |
Minimum of Months | 20.46 | 12.64 |
Maximum of Months | 21.53 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CAFE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | 13.22 |
February | 21.25 | 13.28 |
March | 21.33 | 12.64 |
April | 21.31 | 15.30 |
May | 21.25 | 15.56 |
June | 21.48 | 17.67 |
July | 21.46 | 19.43 |
August | 21.63 | 19.66 |
September | 21.55 | 18.47 |
October | 21.47 | 18.77 |
November | 21.37 | 14.32 |
December | 21.43 | 13.59 |
Annual Sum or Average | 21.40 | 16.01 |
Minimum of Months | 21.25 | 12.64 |
Maximum of Months | 21.63 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 13.22 |
February | 19.91 | 13.28 |
March | 20.00 | 12.64 |
April | 19.85 | 15.30 |
May | 19.88 | 15.56 |
June | 20.05 | 17.67 |
July | 19.94 | 19.43 |
August | 20.11 | 19.66 |
September | 20.00 | 18.47 |
October | 19.88 | 18.77 |
November | 19.96 | 14.32 |
December | 20.03 | 13.59 |
Annual Sum or Average | 19.96 | 16.01 |
Minimum of Months | 19.85 | 12.64 |
Maximum of Months | 20.11 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 CLEAN WORK
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.72 | 13.22 |
February | 19.71 | 13.28 |
March | 19.80 | 12.64 |
April | 19.68 | 15.30 |
May | 19.70 | 15.56 |
June | 19.84 | 17.67 |
July | 19.73 | 19.43 |
August | 19.88 | 19.66 |
September | 19.79 | 18.47 |
October | 19.69 | 18.77 |
November | 19.75 | 14.32 |
December | 19.79 | 13.59 |
Annual Sum or Average | 19.76 | 16.01 |
Minimum of Months | 19.68 | 12.64 |
Maximum of Months | 19.88 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DICTATION
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.51 | 13.22 |
February | 21.54 | 13.28 |
March | 21.64 | 12.64 |
April | 21.55 | 15.30 |
May | 21.55 | 15.56 |
June | 21.74 | 17.67 |
July | 21.69 | 19.43 |
August | 21.80 | 19.66 |
September | 21.72 | 18.47 |
October | 21.56 | 18.77 |
November | 21.57 | 14.32 |
December | 21.58 | 13.59 |
Annual Sum or Average | 21.62 | 16.01 |
Minimum of Months | 21.51 | 12.64 |
Maximum of Months | 21.80 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 DRESSING ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.33 | 13.22 |
February | 20.43 | 13.28 |
March | 20.58 | 12.64 |
April | 20.80 | 15.30 |
May | 20.90 | 15.56 |
June | 21.30 | 17.67 |
July | 21.38 | 19.43 |
August | 21.41 | 19.66 |
September | 21.19 | 18.47 |
October | 20.98 | 18.77 |
November | 20.52 | 14.32 |
December | 20.37 | 13.59 |
Annual Sum or Average | 20.85 | 16.01 |
Minimum of Months | 20.33 | 12.64 |
Maximum of Months | 21.41 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELECTRICAL ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.73 | 13.22 |
February | 21.75 | 13.28 |
March | 21.85 | 12.64 |
April | 21.89 | 15.30 |
May | 21.91 | 15.56 |
June | 22.06 | 17.67 |
July | 22.08 | 19.43 |
August | 22.11 | 19.66 |
September | 22.02 | 18.47 |
October | 21.92 | 18.77 |
November | 21.81 | 14.32 |
December | 21.80 | 13.59 |
Annual Sum or Average | 21.91 | 16.01 |
Minimum of Months | 21.73 | 12.64 |
Maximum of Months | 22.11 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 ELEVATOR PUMP ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 13.22 |
February | 20.93 | 13.28 |
March | 21.03 | 12.64 |
April | 20.99 | 15.30 |
May | 21.03 | 15.56 |
June | 21.15 | 17.67 |
July | 21.09 | 19.43 |
August | 21.19 | 19.66 |
September | 21.07 | 18.47 |
October | 21.00 | 18.77 |
November | 20.97 | 14.32 |
December | 20.96 | 13.59 |
Annual Sum or Average | 21.03 | 16.01 |
Minimum of Months | 20.91 | 12.64 |
Maximum of Months | 21.19 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 HUMID
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.79 | 13.28 |
March | 21.87 | 12.64 |
April | 21.80 | 15.30 |
May | 21.79 | 15.56 |
June | 21.97 | 17.67 |
July | 21.94 | 19.43 |
August | 22.02 | 19.66 |
September | 21.96 | 18.47 |
October | 21.81 | 18.77 |
November | 21.82 | 14.32 |
December | 21.83 | 13.59 |
Annual Sum or Average | 21.86 | 16.01 |
Minimum of Months | 21.75 | 12.64 |
Maximum of Months | 22.02 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 13.22 |
February | 21.00 | 13.28 |
March | 21.13 | 12.64 |
April | 21.15 | 15.30 |
May | 21.19 | 15.56 |
June | 21.52 | 17.67 |
July | 21.49 | 19.43 |
August | 21.60 | 19.66 |
September | 21.45 | 18.47 |
October | 21.18 | 18.77 |
November | 21.06 | 14.32 |
December | 21.02 | 13.59 |
Annual Sum or Average | 21.23 | 16.01 |
Minimum of Months | 20.95 | 12.64 |
Maximum of Months | 21.60 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 IT ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 13.22 |
February | 21.30 | 13.28 |
March | 21.44 | 12.64 |
April | 21.47 | 15.30 |
May | 21.52 | 15.56 |
June | 21.81 | 17.67 |
July | 21.80 | 19.43 |
August | 21.87 | 19.66 |
September | 21.74 | 18.47 |
October | 21.49 | 18.77 |
November | 21.35 | 14.32 |
December | 21.30 | 13.59 |
Annual Sum or Average | 21.53 | 16.01 |
Minimum of Months | 21.24 | 12.64 |
Maximum of Months | 21.87 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.19 | 13.22 |
February | 21.26 | 13.28 |
March | 21.38 | 12.64 |
April | 21.51 | 15.30 |
May | 21.54 | 15.56 |
June | 21.77 | 17.67 |
July | 21.82 | 19.43 |
August | 21.87 | 19.66 |
September | 21.74 | 18.47 |
October | 21.57 | 18.77 |
November | 21.35 | 14.32 |
December | 21.31 | 13.59 |
Annual Sum or Average | 21.53 | 16.01 |
Minimum of Months | 21.19 | 12.64 |
Maximum of Months | 21.87 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.80 | 13.22 |
February | 21.84 | 13.28 |
March | 21.92 | 12.64 |
April | 21.92 | 15.30 |
May | 21.89 | 15.56 |
June | 22.07 | 17.67 |
July | 22.08 | 19.43 |
August | 22.12 | 19.66 |
September | 22.08 | 18.47 |
October | 21.97 | 18.77 |
November | 21.91 | 14.32 |
December | 21.91 | 13.59 |
Annual Sum or Average | 21.96 | 16.01 |
Minimum of Months | 21.80 | 12.64 |
Maximum of Months | 22.12 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOBBY TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.45 | 13.22 |
February | 19.47 | 13.28 |
March | 19.56 | 12.64 |
April | 19.51 | 15.30 |
May | 19.53 | 15.56 |
June | 19.61 | 17.67 |
July | 19.52 | 19.43 |
August | 19.63 | 19.66 |
September | 19.53 | 18.47 |
October | 19.48 | 18.77 |
November | 19.47 | 14.32 |
December | 19.45 | 13.59 |
Annual Sum or Average | 19.52 | 16.01 |
Minimum of Months | 19.45 | 12.64 |
Maximum of Months | 19.63 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.22 |
February | 21.78 | 13.28 |
March | 21.87 | 12.64 |
April | 21.86 | 15.30 |
May | 21.88 | 15.56 |
June | 22.06 | 17.67 |
July | 22.06 | 19.43 |
August | 22.09 | 19.66 |
September | 22.02 | 18.47 |
October | 21.90 | 18.77 |
November | 21.82 | 14.32 |
December | 21.81 | 13.59 |
Annual Sum or Average | 21.91 | 16.01 |
Minimum of Months | 21.74 | 12.64 |
Maximum of Months | 22.09 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOCKER ROOM HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.52 | 13.22 |
February | 21.57 | 13.28 |
March | 21.67 | 12.64 |
April | 21.63 | 15.30 |
May | 21.63 | 15.56 |
June | 21.90 | 17.67 |
July | 21.88 | 19.43 |
August | 21.95 | 19.66 |
September | 21.88 | 18.47 |
October | 21.67 | 18.77 |
November | 21.63 | 14.32 |
December | 21.61 | 13.59 |
Annual Sum or Average | 21.71 | 16.01 |
Minimum of Months | 21.52 | 12.64 |
Maximum of Months | 21.95 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 LOUNGE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 13.22 |
February | 21.83 | 13.28 |
March | 21.92 | 12.64 |
April | 21.89 | 15.30 |
May | 21.90 | 15.56 |
June | 22.06 | 17.67 |
July | 22.05 | 19.43 |
August | 22.09 | 19.66 |
September | 22.02 | 18.47 |
October | 21.89 | 18.77 |
November | 21.86 | 14.32 |
December | 21.86 | 13.59 |
Annual Sum or Average | 21.93 | 16.01 |
Minimum of Months | 21.79 | 12.64 |
Maximum of Months | 22.09 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MED GAS
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.60 | 13.22 |
February | 19.62 | 13.28 |
March | 19.89 | 12.64 |
April | 20.34 | 15.30 |
May | 20.50 | 15.56 |
June | 21.05 | 17.67 |
July | 21.28 | 19.43 |
August | 21.23 | 19.66 |
September | 20.86 | 18.47 |
October | 20.42 | 18.77 |
November | 19.66 | 14.32 |
December | 19.59 | 13.59 |
Annual Sum or Average | 20.34 | 16.01 |
Minimum of Months | 19.59 | 12.64 |
Maximum of Months | 21.28 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI CONTROL ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.95 | 13.22 |
February | 21.97 | 13.28 |
March | 22.02 | 12.64 |
April | 22.03 | 15.30 |
May | 22.05 | 15.56 |
June | 22.13 | 17.67 |
July | 22.14 | 19.43 |
August | 22.15 | 19.66 |
September | 22.11 | 18.47 |
October | 22.06 | 18.77 |
November | 22.00 | 14.32 |
December | 22.00 | 13.59 |
Annual Sum or Average | 22.05 | 16.01 |
Minimum of Months | 21.95 | 12.64 |
Maximum of Months | 22.15 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.22 |
February | 21.56 | 13.28 |
March | 21.66 | 12.64 |
April | 21.66 | 15.30 |
May | 21.68 | 15.56 |
June | 21.91 | 17.67 |
July | 21.91 | 19.43 |
August | 21.97 | 19.66 |
September | 21.89 | 18.47 |
October | 21.72 | 18.77 |
November | 21.61 | 14.32 |
December | 21.58 | 13.59 |
Annual Sum or Average | 21.72 | 16.01 |
Minimum of Months | 21.49 | 12.64 |
Maximum of Months | 21.97 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.08 | 13.22 |
February | 22.09 | 13.28 |
March | 22.12 | 12.64 |
April | 22.11 | 15.30 |
May | 22.11 | 15.56 |
June | 22.15 | 17.67 |
July | 22.15 | 19.43 |
August | 22.16 | 19.66 |
September | 22.14 | 18.47 |
October | 22.11 | 18.77 |
November | 22.10 | 14.32 |
December | 22.12 | 13.59 |
Annual Sum or Average | 22.12 | 16.01 |
Minimum of Months | 22.08 | 12.64 |
Maximum of Months | 22.16 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 MRI TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 13.22 |
February | 19.40 | 13.28 |
March | 19.47 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.47 | 17.67 |
July | 19.37 | 19.43 |
August | 19.48 | 19.66 |
September | 19.41 | 18.47 |
October | 19.38 | 18.77 |
November | 19.39 | 14.32 |
December | 19.37 | 13.59 |
Annual Sum or Average | 19.41 | 16.01 |
Minimum of Months | 19.37 | 12.64 |
Maximum of Months | 19.48 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NOURISHMENT
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.69 | 13.22 |
February | 21.72 | 13.28 |
March | 21.81 | 12.64 |
April | 21.73 | 15.30 |
May | 21.72 | 15.56 |
June | 21.89 | 17.67 |
July | 21.84 | 19.43 |
August | 21.93 | 19.66 |
September | 21.86 | 18.47 |
October | 21.73 | 18.77 |
November | 21.75 | 14.32 |
December | 21.77 | 13.59 |
Annual Sum or Average | 21.79 | 16.01 |
Minimum of Months | 21.69 | 12.64 |
Maximum of Months | 21.93 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | 13.22 |
February | 21.19 | 13.28 |
March | 21.26 | 12.64 |
April | 21.20 | 15.30 |
May | 21.16 | 15.56 |
June | 21.45 | 17.67 |
July | 21.40 | 19.43 |
August | 21.57 | 19.66 |
September | 21.50 | 18.47 |
October | 21.32 | 18.77 |
November | 21.30 | 14.32 |
December | 21.32 | 13.59 |
Annual Sum or Average | 21.32 | 16.01 |
Minimum of Months | 21.16 | 12.64 |
Maximum of Months | 21.57 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE JANITOR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.62 | 13.22 |
February | 21.66 | 13.28 |
March | 21.75 | 12.64 |
April | 21.70 | 15.30 |
May | 21.69 | 15.56 |
June | 21.95 | 17.67 |
July | 21.93 | 19.43 |
August | 22.00 | 19.66 |
September | 21.94 | 18.47 |
October | 21.73 | 18.77 |
November | 21.72 | 14.32 |
December | 21.71 | 13.59 |
Annual Sum or Average | 21.78 | 16.01 |
Minimum of Months | 21.62 | 12.64 |
Maximum of Months | 22.00 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE STATION
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.60 | 13.22 |
February | 21.61 | 13.28 |
March | 21.71 | 12.64 |
April | 21.62 | 15.30 |
May | 21.61 | 15.56 |
June | 21.80 | 17.67 |
July | 21.74 | 19.43 |
August | 21.85 | 19.66 |
September | 21.78 | 18.47 |
October | 21.65 | 18.77 |
November | 21.66 | 14.32 |
December | 21.68 | 13.59 |
Annual Sum or Average | 21.69 | 16.01 |
Minimum of Months | 21.60 | 12.64 |
Maximum of Months | 21.85 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 NURSE TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 13.22 |
February | 19.40 | 13.28 |
March | 19.47 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.47 | 17.67 |
July | 19.37 | 19.43 |
August | 19.47 | 19.66 |
September | 19.41 | 18.47 |
October | 19.38 | 18.77 |
November | 19.39 | 14.32 |
December | 19.37 | 13.59 |
Annual Sum or Average | 19.41 | 16.01 |
Minimum of Months | 19.37 | 12.64 |
Maximum of Months | 19.47 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OFFICE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.22 |
February | 21.79 | 13.28 |
March | 21.87 | 12.64 |
April | 21.84 | 15.30 |
May | 21.83 | 15.56 |
June | 22.02 | 17.67 |
July | 22.01 | 19.43 |
August | 22.07 | 19.66 |
September | 22.01 | 18.47 |
October | 21.87 | 18.77 |
November | 21.83 | 14.32 |
December | 21.83 | 13.59 |
Annual Sum or Average | 21.89 | 16.01 |
Minimum of Months | 21.74 | 12.64 |
Maximum of Months | 22.07 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.98 | 13.22 |
February | 18.94 | 13.28 |
March | 18.95 | 12.64 |
April | 18.94 | 15.30 |
May | 18.95 | 15.56 |
June | 19.11 | 17.67 |
July | 19.14 | 19.43 |
August | 19.22 | 19.66 |
September | 19.13 | 18.47 |
October | 19.10 | 18.77 |
November | 19.04 | 14.32 |
December | 19.11 | 13.59 |
Annual Sum or Average | 19.05 | 16.01 |
Minimum of Months | 18.94 | 12.64 |
Maximum of Months | 19.22 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.02 | 13.22 |
February | 19.00 | 13.28 |
March | 19.04 | 12.64 |
April | 19.02 | 15.30 |
May | 19.05 | 15.56 |
June | 19.20 | 17.67 |
July | 19.21 | 19.43 |
August | 19.27 | 19.66 |
September | 19.17 | 18.47 |
October | 19.10 | 18.77 |
November | 19.07 | 14.32 |
December | 19.13 | 13.59 |
Annual Sum or Average | 19.11 | 16.01 |
Minimum of Months | 19.00 | 12.64 |
Maximum of Months | 19.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 OPERATING ROOM 3
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.34 | 13.22 |
February | 18.33 | 13.28 |
March | 18.32 | 12.64 |
April | 18.33 | 15.30 |
May | 18.33 | 15.56 |
June | 18.32 | 17.67 |
July | 18.33 | 19.43 |
August | 18.32 | 19.66 |
September | 18.33 | 18.47 |
October | 18.34 | 18.77 |
November | 18.34 | 14.32 |
December | 18.35 | 13.59 |
Annual Sum or Average | 18.33 | 16.01 |
Minimum of Months | 18.32 | 12.64 |
Maximum of Months | 18.35 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PACU
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.51 | 13.22 |
February | 19.52 | 13.28 |
March | 19.60 | 12.64 |
April | 19.51 | 15.30 |
May | 19.53 | 15.56 |
June | 19.59 | 17.67 |
July | 19.49 | 19.43 |
August | 19.61 | 19.66 |
September | 19.54 | 18.47 |
October | 19.50 | 18.77 |
November | 19.53 | 14.32 |
December | 19.54 | 13.59 |
Annual Sum or Average | 19.54 | 16.01 |
Minimum of Months | 19.49 | 12.64 |
Maximum of Months | 19.61 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | 13.22 |
February | 21.33 | 13.28 |
March | 21.42 | 12.64 |
April | 21.42 | 15.30 |
May | 21.41 | 15.56 |
June | 21.71 | 17.67 |
July | 21.69 | 19.43 |
August | 21.80 | 19.66 |
September | 21.71 | 18.47 |
October | 21.49 | 18.77 |
November | 21.41 | 14.32 |
December | 21.39 | 13.59 |
Annual Sum or Average | 21.51 | 16.01 |
Minimum of Months | 21.29 | 12.64 |
Maximum of Months | 21.80 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 13.22 |
February | 19.43 | 13.28 |
March | 19.51 | 12.64 |
April | 19.45 | 15.30 |
May | 19.46 | 15.56 |
June | 19.52 | 17.67 |
July | 19.43 | 19.43 |
August | 19.54 | 19.66 |
September | 19.47 | 18.47 |
October | 19.43 | 18.77 |
November | 19.43 | 14.32 |
December | 19.42 | 13.59 |
Annual Sum or Average | 19.46 | 16.01 |
Minimum of Months | 19.42 | 12.64 |
Maximum of Months | 19.54 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP ROOM 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 13.22 |
February | 19.44 | 13.28 |
March | 19.51 | 12.64 |
April | 19.44 | 15.30 |
May | 19.46 | 15.56 |
June | 19.51 | 17.67 |
July | 19.41 | 19.43 |
August | 19.52 | 19.66 |
September | 19.45 | 18.47 |
October | 19.42 | 18.77 |
November | 19.44 | 14.32 |
December | 19.44 | 13.59 |
Annual Sum or Average | 19.46 | 16.01 |
Minimum of Months | 19.41 | 12.64 |
Maximum of Months | 19.52 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PRE-OP TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.38 | 13.22 |
February | 19.40 | 13.28 |
March | 19.47 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.47 | 17.67 |
July | 19.38 | 19.43 |
August | 19.48 | 19.66 |
September | 19.41 | 18.47 |
October | 19.39 | 18.77 |
November | 19.39 | 14.32 |
December | 19.37 | 13.59 |
Annual Sum or Average | 19.42 | 16.01 |
Minimum of Months | 19.37 | 12.64 |
Maximum of Months | 19.48 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 PROCEDURE ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.40 | 13.22 |
February | 19.42 | 13.28 |
March | 19.49 | 12.64 |
April | 19.43 | 15.30 |
May | 19.45 | 15.56 |
June | 19.49 | 17.67 |
July | 19.39 | 19.43 |
August | 19.49 | 19.66 |
September | 19.43 | 18.47 |
October | 19.40 | 18.77 |
November | 19.40 | 14.32 |
December | 19.39 | 13.59 |
Annual Sum or Average | 19.43 | 16.01 |
Minimum of Months | 19.39 | 12.64 |
Maximum of Months | 19.49 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 13.22 |
February | 21.66 | 13.28 |
March | 21.73 | 12.64 |
April | 21.72 | 15.30 |
May | 21.68 | 15.56 |
June | 21.89 | 17.67 |
July | 21.89 | 19.43 |
August | 21.98 | 19.66 |
September | 21.92 | 18.47 |
October | 21.81 | 18.77 |
November | 21.74 | 14.32 |
December | 21.76 | 13.59 |
Annual Sum or Average | 21.79 | 16.01 |
Minimum of Months | 21.63 | 12.64 |
Maximum of Months | 21.98 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECEPTION HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.41 | 13.22 |
February | 21.45 | 13.28 |
March | 21.55 | 12.64 |
April | 21.51 | 15.30 |
May | 21.49 | 15.56 |
June | 21.78 | 17.67 |
July | 21.76 | 19.43 |
August | 21.86 | 19.66 |
September | 21.79 | 18.47 |
October | 21.58 | 18.77 |
November | 21.53 | 14.32 |
December | 21.52 | 13.59 |
Annual Sum or Average | 21.60 | 16.01 |
Minimum of Months | 21.41 | 12.64 |
Maximum of Months | 21.86 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 RECOVERY ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 13.22 |
February | 19.62 | 13.28 |
March | 19.64 | 12.64 |
April | 19.53 | 15.30 |
May | 19.50 | 15.56 |
June | 19.56 | 17.67 |
July | 19.48 | 19.43 |
August | 19.66 | 19.66 |
September | 19.67 | 18.47 |
October | 19.71 | 18.77 |
November | 19.71 | 14.32 |
December | 19.77 | 13.59 |
Annual Sum or Average | 19.63 | 16.01 |
Minimum of Months | 19.48 | 12.64 |
Maximum of Months | 19.77 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCHEDULING
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | 13.22 |
February | 21.31 | 13.28 |
March | 21.38 | 12.64 |
April | 21.38 | 15.30 |
May | 21.35 | 15.56 |
June | 21.61 | 17.67 |
July | 21.61 | 19.43 |
August | 21.73 | 19.66 |
September | 21.66 | 18.47 |
October | 21.52 | 18.77 |
November | 21.42 | 14.32 |
December | 21.41 | 13.59 |
Annual Sum or Average | 21.47 | 16.01 |
Minimum of Months | 21.29 | 12.64 |
Maximum of Months | 21.73 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SCRUB
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.31 | 13.22 |
February | 21.33 | 13.28 |
March | 21.45 | 12.64 |
April | 21.52 | 15.30 |
May | 21.52 | 15.56 |
June | 21.82 | 17.67 |
July | 21.87 | 19.43 |
August | 21.95 | 19.66 |
September | 21.80 | 18.47 |
October | 21.60 | 18.77 |
November | 21.45 | 14.32 |
December | 21.41 | 13.59 |
Annual Sum or Average | 21.59 | 16.01 |
Minimum of Months | 21.31 | 12.64 |
Maximum of Months | 21.95 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 13.22 |
February | 19.40 | 13.28 |
March | 19.48 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.47 | 17.67 |
July | 19.38 | 19.43 |
August | 19.48 | 19.66 |
September | 19.41 | 18.47 |
October | 19.39 | 18.77 |
November | 19.39 | 14.32 |
December | 19.38 | 13.59 |
Annual Sum or Average | 19.42 | 16.01 |
Minimum of Months | 19.38 | 12.64 |
Maximum of Months | 19.48 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL HOLD
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 13.22 |
February | 19.40 | 13.28 |
March | 19.48 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.48 | 17.67 |
July | 19.38 | 19.43 |
August | 19.49 | 19.66 |
September | 19.42 | 18.47 |
October | 19.39 | 18.77 |
November | 19.39 | 14.32 |
December | 19.38 | 13.59 |
Annual Sum or Average | 19.42 | 16.01 |
Minimum of Months | 19.38 | 12.64 |
Maximum of Months | 19.49 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SOIL WORK
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 13.22 |
February | 19.40 | 13.28 |
March | 19.48 | 12.64 |
April | 19.41 | 15.30 |
May | 19.43 | 15.56 |
June | 19.47 | 17.67 |
July | 19.38 | 19.43 |
August | 19.48 | 19.66 |
September | 19.41 | 18.47 |
October | 19.39 | 18.77 |
November | 19.39 | 14.32 |
December | 19.38 | 13.59 |
Annual Sum or Average | 19.42 | 16.01 |
Minimum of Months | 19.38 | 12.64 |
Maximum of Months | 19.48 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STEP DOWN
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.80 | 13.22 |
February | 19.75 | 13.28 |
March | 19.78 | 12.64 |
April | 19.78 | 15.30 |
May | 19.69 | 15.56 |
June | 19.82 | 17.67 |
July | 19.80 | 19.43 |
August | 20.00 | 19.66 |
September | 19.93 | 18.47 |
October | 19.89 | 18.77 |
November | 19.86 | 14.32 |
December | 19.88 | 13.59 |
Annual Sum or Average | 19.83 | 16.01 |
Minimum of Months | 19.69 | 12.64 |
Maximum of Months | 20.00 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.35 | 13.22 |
February | 21.34 | 13.28 |
March | 21.42 | 12.64 |
April | 21.43 | 15.30 |
May | 21.40 | 15.56 |
June | 21.71 | 17.67 |
July | 21.72 | 19.43 |
August | 21.84 | 19.66 |
September | 21.74 | 18.47 |
October | 21.56 | 18.77 |
November | 21.48 | 14.32 |
December | 21.47 | 13.59 |
Annual Sum or Average | 21.54 | 16.01 |
Minimum of Months | 21.34 | 12.64 |
Maximum of Months | 21.84 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STERILE STORAGE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.22 |
February | 21.53 | 13.28 |
March | 21.62 | 12.64 |
April | 21.57 | 15.30 |
May | 21.56 | 15.56 |
June | 21.87 | 17.67 |
July | 21.85 | 19.43 |
August | 21.94 | 19.66 |
September | 21.87 | 18.47 |
October | 21.63 | 18.77 |
November | 21.60 | 14.32 |
December | 21.59 | 13.59 |
Annual Sum or Average | 21.68 | 16.01 |
Minimum of Months | 21.49 | 12.64 |
Maximum of Months | 21.94 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 STORAGE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.76 | 13.22 |
February | 19.81 | 13.28 |
March | 20.01 | 12.64 |
April | 20.53 | 15.30 |
May | 20.72 | 15.56 |
June | 21.31 | 17.67 |
July | 21.50 | 19.43 |
August | 21.46 | 19.66 |
September | 21.11 | 18.47 |
October | 20.55 | 18.77 |
November | 19.88 | 14.32 |
December | 19.76 | 13.59 |
Annual Sum or Average | 20.54 | 16.01 |
Minimum of Months | 19.76 | 12.64 |
Maximum of Months | 21.50 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 SUB-STERILE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.72 | 13.22 |
February | 20.76 | 13.28 |
March | 20.90 | 12.64 |
April | 21.18 | 15.30 |
May | 21.18 | 15.56 |
June | 21.53 | 17.67 |
July | 21.67 | 19.43 |
August | 21.72 | 19.66 |
September | 21.45 | 18.47 |
October | 21.22 | 18.77 |
November | 20.89 | 14.32 |
December | 20.81 | 13.59 |
Annual Sum or Average | 21.17 | 16.01 |
Minimum of Months | 20.72 | 12.64 |
Maximum of Months | 21.72 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.06 | 13.22 |
February | 20.12 | 13.28 |
March | 20.32 | 12.64 |
April | 20.81 | 15.30 |
May | 20.94 | 15.56 |
June | 21.43 | 17.67 |
July | 21.60 | 19.43 |
August | 21.61 | 19.66 |
September | 21.26 | 18.47 |
October | 20.82 | 18.77 |
November | 20.21 | 14.32 |
December | 20.10 | 13.59 |
Annual Sum or Average | 20.78 | 16.01 |
Minimum of Months | 20.06 | 12.64 |
Maximum of Months | 21.61 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY JANITOR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.22 | 13.22 |
February | 21.26 | 13.28 |
March | 21.38 | 12.64 |
April | 21.48 | 15.30 |
May | 21.48 | 15.56 |
June | 21.81 | 17.67 |
July | 21.86 | 19.43 |
August | 21.94 | 19.66 |
September | 21.77 | 18.47 |
October | 21.54 | 18.77 |
November | 21.36 | 14.32 |
December | 21.32 | 13.59 |
Annual Sum or Average | 21.54 | 16.01 |
Minimum of Months | 21.22 | 12.64 |
Maximum of Months | 21.94 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 UTILITY ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.49 | 13.22 |
February | 20.56 | 13.28 |
March | 20.74 | 12.64 |
April | 21.10 | 15.30 |
May | 21.12 | 15.56 |
June | 21.55 | 17.67 |
July | 21.72 | 19.43 |
August | 21.75 | 19.66 |
September | 21.46 | 18.47 |
October | 21.14 | 18.77 |
November | 20.64 | 14.32 |
December | 20.54 | 13.59 |
Annual Sum or Average | 21.07 | 16.01 |
Minimum of Months | 20.49 | 12.64 |
Maximum of Months | 21.75 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 1 VESTIBULE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.45 | 13.22 |
February | 18.31 | 13.28 |
March | 17.93 | 12.64 |
April | 19.44 | 15.30 |
May | 19.44 | 15.56 |
June | 20.28 | 17.67 |
July | 21.07 | 19.43 |
August | 21.21 | 19.66 |
September | 20.60 | 18.47 |
October | 20.68 | 18.77 |
November | 18.82 | 14.32 |
December | 18.82 | 13.59 |
Annual Sum or Average | 19.59 | 16.01 |
Minimum of Months | 17.93 | 12.64 |
Maximum of Months | 21.21 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.89 | 13.22 |
February | 20.86 | 13.28 |
March | 20.95 | 12.64 |
April | 20.92 | 15.30 |
May | 20.82 | 15.56 |
June | 20.92 | 17.67 |
July | 20.83 | 19.43 |
August | 21.06 | 19.66 |
September | 20.96 | 18.47 |
October | 20.99 | 18.77 |
November | 20.99 | 14.32 |
December | 20.98 | 13.59 |
Annual Sum or Average | 20.93 | 16.01 |
Minimum of Months | 20.82 | 12.64 |
Maximum of Months | 21.06 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 CONFERENCE TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.14 | 13.22 |
February | 18.16 | 13.28 |
March | 18.27 | 12.64 |
April | 18.01 | 15.30 |
May | 17.89 | 15.56 |
June | 17.74 | 17.67 |
July | 17.54 | 19.43 |
August | 17.66 | 19.66 |
September | 17.70 | 18.47 |
October | 17.69 | 18.77 |
November | 18.13 | 14.32 |
December | 18.19 | 13.59 |
Annual Sum or Average | 17.93 | 16.01 |
Minimum of Months | 17.54 | 12.64 |
Maximum of Months | 18.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 DICTATION
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.56 | 13.22 |
February | 21.60 | 13.28 |
March | 21.74 | 12.64 |
April | 21.63 | 15.30 |
May | 21.57 | 15.56 |
June | 21.64 | 17.67 |
July | 21.49 | 19.43 |
August | 21.66 | 19.66 |
September | 21.57 | 18.47 |
October | 21.53 | 18.77 |
November | 21.63 | 14.32 |
December | 21.64 | 13.59 |
Annual Sum or Average | 21.60 | 16.01 |
Minimum of Months | 21.49 | 12.64 |
Maximum of Months | 21.74 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.13 | 13.22 |
February | 20.15 | 13.28 |
March | 20.26 | 12.64 |
April | 20.35 | 15.30 |
May | 20.24 | 15.56 |
June | 20.33 | 17.67 |
July | 20.28 | 19.43 |
August | 20.45 | 19.66 |
September | 20.33 | 18.47 |
October | 20.21 | 18.77 |
November | 20.21 | 14.32 |
December | 20.16 | 13.59 |
Annual Sum or Average | 20.26 | 16.01 |
Minimum of Months | 20.13 | 12.64 |
Maximum of Months | 20.45 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.82 | 13.22 |
February | 19.81 | 13.28 |
March | 19.92 | 12.64 |
April | 19.76 | 15.30 |
May | 19.75 | 15.56 |
June | 19.74 | 17.67 |
July | 19.57 | 19.43 |
August | 19.72 | 19.66 |
September | 19.68 | 18.47 |
October | 19.66 | 18.77 |
November | 19.80 | 14.32 |
December | 19.83 | 13.59 |
Annual Sum or Average | 19.75 | 16.01 |
Minimum of Months | 19.57 | 12.64 |
Maximum of Months | 19.92 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 3
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.78 | 13.22 |
February | 19.75 | 13.28 |
March | 19.85 | 12.64 |
April | 19.69 | 15.30 |
May | 19.68 | 15.56 |
June | 19.67 | 17.67 |
July | 19.51 | 19.43 |
August | 19.66 | 19.66 |
September | 19.62 | 18.47 |
October | 19.61 | 18.77 |
November | 19.74 | 14.32 |
December | 19.77 | 13.59 |
Annual Sum or Average | 19.69 | 16.01 |
Minimum of Months | 19.51 | 12.64 |
Maximum of Months | 19.85 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 4
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.45 | 13.22 |
February | 20.36 | 13.28 |
March | 20.37 | 12.64 |
April | 20.23 | 15.30 |
May | 20.03 | 15.56 |
June | 20.04 | 17.67 |
July | 19.92 | 19.43 |
August | 20.23 | 19.66 |
September | 20.26 | 18.47 |
October | 20.31 | 18.77 |
November | 20.49 | 14.32 |
December | 20.52 | 13.59 |
Annual Sum or Average | 20.27 | 16.01 |
Minimum of Months | 19.92 | 12.64 |
Maximum of Months | 20.52 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 5
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.96 | 13.22 |
February | 20.04 | 13.28 |
March | 20.27 | 12.64 |
April | 20.32 | 15.30 |
May | 20.31 | 15.56 |
June | 20.36 | 17.67 |
July | 20.30 | 19.43 |
August | 20.40 | 19.66 |
September | 20.13 | 18.47 |
October | 20.00 | 18.77 |
November | 19.98 | 14.32 |
December | 19.94 | 13.59 |
Annual Sum or Average | 20.17 | 16.01 |
Minimum of Months | 19.94 | 12.64 |
Maximum of Months | 20.40 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 6
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.69 | 13.22 |
February | 19.73 | 13.28 |
March | 19.87 | 12.64 |
April | 19.79 | 15.30 |
May | 19.83 | 15.56 |
June | 19.89 | 17.67 |
July | 19.72 | 19.43 |
August | 19.82 | 19.66 |
September | 19.72 | 18.47 |
October | 19.66 | 18.77 |
November | 19.70 | 14.32 |
December | 19.68 | 13.59 |
Annual Sum or Average | 19.76 | 16.01 |
Minimum of Months | 19.66 | 12.64 |
Maximum of Months | 19.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 7
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.67 | 13.22 |
February | 19.71 | 13.28 |
March | 19.85 | 12.64 |
April | 19.70 | 15.30 |
May | 19.73 | 15.56 |
June | 19.72 | 17.67 |
July | 19.55 | 19.43 |
August | 19.66 | 19.66 |
September | 19.60 | 18.47 |
October | 19.56 | 18.77 |
November | 19.67 | 14.32 |
December | 19.67 | 13.59 |
Annual Sum or Average | 19.67 | 16.01 |
Minimum of Months | 19.55 | 12.64 |
Maximum of Months | 19.85 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 8
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.76 | 13.22 |
February | 19.81 | 13.28 |
March | 19.96 | 12.64 |
April | 19.85 | 15.30 |
May | 19.90 | 15.56 |
June | 19.94 | 17.67 |
July | 19.76 | 19.43 |
August | 19.86 | 19.66 |
September | 19.77 | 18.47 |
October | 19.71 | 18.77 |
November | 19.78 | 14.32 |
December | 19.76 | 13.59 |
Annual Sum or Average | 19.82 | 16.01 |
Minimum of Months | 19.71 | 12.64 |
Maximum of Months | 19.96 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM 9
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.79 | 13.22 |
February | 19.83 | 13.28 |
March | 19.98 | 12.64 |
April | 19.84 | 15.30 |
May | 19.86 | 15.56 |
June | 19.86 | 17.67 |
July | 19.67 | 19.43 |
August | 19.80 | 19.66 |
September | 19.73 | 18.47 |
October | 19.68 | 18.77 |
November | 19.79 | 14.32 |
December | 19.79 | 13.59 |
Annual Sum or Average | 19.80 | 16.01 |
Minimum of Months | 19.67 | 12.64 |
Maximum of Months | 19.98 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | 13.22 |
February | 21.32 | 13.28 |
March | 21.42 | 12.64 |
April | 21.45 | 15.30 |
May | 21.36 | 15.56 |
June | 21.48 | 17.67 |
July | 21.43 | 19.43 |
August | 21.60 | 19.66 |
September | 21.50 | 18.47 |
October | 21.44 | 18.77 |
November | 21.43 | 14.32 |
December | 21.41 | 13.59 |
Annual Sum or Average | 21.43 | 16.01 |
Minimum of Months | 21.29 | 12.64 |
Maximum of Months | 21.60 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 13.22 |
February | 21.30 | 13.28 |
March | 21.40 | 12.64 |
April | 21.32 | 15.30 |
May | 21.23 | 15.56 |
June | 21.33 | 17.67 |
July | 21.22 | 19.43 |
August | 21.41 | 19.66 |
September | 21.35 | 18.47 |
October | 21.33 | 18.77 |
November | 21.40 | 14.32 |
December | 21.41 | 13.59 |
Annual Sum or Average | 21.33 | 16.01 |
Minimum of Months | 21.22 | 12.64 |
Maximum of Months | 21.41 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 3
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.29 | 13.22 |
February | 21.27 | 13.28 |
March | 21.35 | 12.64 |
April | 21.26 | 15.30 |
May | 21.14 | 15.56 |
June | 21.23 | 17.67 |
July | 21.11 | 19.43 |
August | 21.34 | 19.66 |
September | 21.29 | 18.47 |
October | 21.28 | 18.77 |
November | 21.38 | 14.32 |
December | 21.40 | 13.59 |
Annual Sum or Average | 21.28 | 16.01 |
Minimum of Months | 21.11 | 12.64 |
Maximum of Months | 21.40 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 4
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.20 | 13.22 |
February | 21.31 | 13.28 |
March | 21.49 | 12.64 |
April | 21.45 | 15.30 |
May | 21.47 | 15.56 |
June | 21.60 | 17.67 |
July | 21.48 | 19.43 |
August | 21.58 | 19.66 |
September | 21.43 | 18.47 |
October | 21.33 | 18.77 |
November | 21.32 | 14.32 |
December | 21.27 | 13.59 |
Annual Sum or Average | 21.41 | 16.01 |
Minimum of Months | 21.20 | 12.64 |
Maximum of Months | 21.60 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 5
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.30 | 13.22 |
February | 21.43 | 13.28 |
March | 21.62 | 12.64 |
April | 21.57 | 15.30 |
May | 21.59 | 15.56 |
June | 21.73 | 17.67 |
July | 21.62 | 19.43 |
August | 21.71 | 19.66 |
September | 21.57 | 18.47 |
October | 21.46 | 18.77 |
November | 21.44 | 14.32 |
December | 21.39 | 13.59 |
Annual Sum or Average | 21.54 | 16.01 |
Minimum of Months | 21.30 | 12.64 |
Maximum of Months | 21.73 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 EXAM HALL 6
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.23 | 13.22 |
February | 21.36 | 13.28 |
March | 21.55 | 12.64 |
April | 21.51 | 15.30 |
May | 21.53 | 15.56 |
June | 21.67 | 17.67 |
July | 21.56 | 19.43 |
August | 21.65 | 19.66 |
September | 21.51 | 18.47 |
October | 21.40 | 18.77 |
November | 21.37 | 14.32 |
December | 21.32 | 13.59 |
Annual Sum or Average | 21.47 | 16.01 |
Minimum of Months | 21.23 | 12.64 |
Maximum of Months | 21.67 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 JANITOR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.91 | 13.22 |
February | 21.01 | 13.28 |
March | 21.19 | 12.64 |
April | 21.34 | 15.30 |
May | 21.37 | 15.56 |
June | 21.58 | 17.67 |
July | 21.59 | 19.43 |
August | 21.64 | 19.66 |
September | 21.44 | 18.47 |
October | 21.33 | 18.77 |
November | 21.09 | 14.32 |
December | 20.97 | 13.59 |
Annual Sum or Average | 21.29 | 16.01 |
Minimum of Months | 20.91 | 12.64 |
Maximum of Months | 21.64 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 LOUNGE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.72 | 13.22 |
February | 21.77 | 13.28 |
March | 21.89 | 12.64 |
April | 21.81 | 15.30 |
May | 21.77 | 15.56 |
June | 21.82 | 17.67 |
July | 21.71 | 19.43 |
August | 21.82 | 19.66 |
September | 21.74 | 18.47 |
October | 21.69 | 18.77 |
November | 21.79 | 14.32 |
December | 21.79 | 13.59 |
Annual Sum or Average | 21.78 | 16.01 |
Minimum of Months | 21.69 | 12.64 |
Maximum of Months | 21.89 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 13.22 |
February | 21.69 | 13.28 |
March | 21.83 | 12.64 |
April | 21.75 | 15.30 |
May | 21.74 | 15.56 |
June | 21.81 | 17.67 |
July | 21.69 | 19.43 |
August | 21.79 | 19.66 |
September | 21.69 | 18.47 |
October | 21.62 | 18.77 |
November | 21.69 | 14.32 |
December | 21.67 | 13.59 |
Annual Sum or Average | 21.71 | 16.01 |
Minimum of Months | 21.61 | 12.64 |
Maximum of Months | 21.83 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 NURSE STATION 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.63 | 13.22 |
February | 21.73 | 13.28 |
March | 21.87 | 12.64 |
April | 21.80 | 15.30 |
May | 21.79 | 15.56 |
June | 21.87 | 17.67 |
July | 21.75 | 19.43 |
August | 21.84 | 19.66 |
September | 21.74 | 18.47 |
October | 21.67 | 18.77 |
November | 21.73 | 14.32 |
December | 21.70 | 13.59 |
Annual Sum or Average | 21.76 | 16.01 |
Minimum of Months | 21.63 | 12.64 |
Maximum of Months | 21.87 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.25 | 13.22 |
February | 21.28 | 13.28 |
March | 21.49 | 12.64 |
April | 21.64 | 15.30 |
May | 21.65 | 15.56 |
June | 21.77 | 17.67 |
July | 21.81 | 19.43 |
August | 21.87 | 19.66 |
September | 21.64 | 18.47 |
October | 21.58 | 18.77 |
November | 21.40 | 14.32 |
December | 21.31 | 13.59 |
Annual Sum or Average | 21.56 | 16.01 |
Minimum of Months | 21.25 | 12.64 |
Maximum of Months | 21.87 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 OFFICE HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.44 | 13.22 |
February | 21.51 | 13.28 |
March | 21.69 | 12.64 |
April | 21.72 | 15.30 |
May | 21.71 | 15.56 |
June | 21.82 | 17.67 |
July | 21.80 | 19.43 |
August | 21.88 | 19.66 |
September | 21.70 | 18.47 |
October | 21.62 | 18.77 |
November | 21.57 | 14.32 |
December | 21.52 | 13.59 |
Annual Sum or Average | 21.67 | 16.01 |
Minimum of Months | 21.44 | 12.64 |
Maximum of Months | 21.88 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.18 | 13.22 |
February | 21.21 | 13.28 |
March | 21.34 | 12.64 |
April | 21.37 | 15.30 |
May | 21.30 | 15.56 |
June | 21.41 | 17.67 |
July | 21.35 | 19.43 |
August | 21.49 | 19.66 |
September | 21.40 | 18.47 |
October | 21.37 | 18.77 |
November | 21.33 | 14.32 |
December | 21.31 | 13.59 |
Annual Sum or Average | 21.34 | 16.01 |
Minimum of Months | 21.18 | 12.64 |
Maximum of Months | 21.49 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.65 | 13.22 |
February | 21.71 | 13.28 |
March | 21.82 | 12.64 |
April | 21.77 | 15.30 |
May | 21.72 | 15.56 |
June | 21.80 | 17.67 |
July | 21.71 | 19.43 |
August | 21.83 | 19.66 |
September | 21.75 | 18.47 |
October | 21.71 | 18.77 |
November | 21.75 | 14.32 |
December | 21.74 | 13.59 |
Annual Sum or Average | 21.75 | 16.01 |
Minimum of Months | 21.65 | 12.64 |
Maximum of Months | 21.83 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 RECEPTION TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 18.03 | 13.22 |
February | 18.09 | 13.28 |
March | 18.20 | 12.64 |
April | 17.94 | 15.30 |
May | 17.85 | 15.56 |
June | 17.70 | 17.67 |
July | 17.49 | 19.43 |
August | 17.57 | 19.66 |
September | 17.63 | 18.47 |
October | 17.60 | 18.77 |
November | 18.04 | 14.32 |
December | 18.09 | 13.59 |
Annual Sum or Average | 17.85 | 16.01 |
Minimum of Months | 17.49 | 12.64 |
Maximum of Months | 18.20 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.79 | 13.22 |
February | 21.86 | 13.28 |
March | 21.97 | 12.64 |
April | 21.93 | 15.30 |
May | 21.89 | 15.56 |
June | 21.96 | 17.67 |
July | 21.88 | 19.43 |
August | 21.96 | 19.66 |
September | 21.88 | 18.47 |
October | 21.82 | 18.77 |
November | 21.88 | 14.32 |
December | 21.86 | 13.59 |
Annual Sum or Average | 21.89 | 16.01 |
Minimum of Months | 21.79 | 12.64 |
Maximum of Months | 21.97 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 SCHEDULING 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.75 | 13.22 |
February | 21.82 | 13.28 |
March | 21.93 | 12.64 |
April | 21.88 | 15.30 |
May | 21.84 | 15.56 |
June | 21.90 | 17.67 |
July | 21.82 | 19.43 |
August | 21.91 | 19.66 |
September | 21.84 | 18.47 |
October | 21.79 | 18.77 |
November | 21.85 | 14.32 |
December | 21.84 | 13.59 |
Annual Sum or Average | 21.85 | 16.01 |
Minimum of Months | 21.75 | 12.64 |
Maximum of Months | 21.93 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.69 | 13.22 |
February | 20.68 | 13.28 |
March | 20.77 | 12.64 |
April | 20.65 | 15.30 |
May | 20.53 | 15.56 |
June | 20.58 | 17.67 |
July | 20.46 | 19.43 |
August | 20.65 | 19.66 |
September | 20.62 | 18.47 |
October | 20.60 | 18.77 |
November | 20.74 | 14.32 |
December | 20.79 | 13.59 |
Annual Sum or Average | 20.65 | 16.01 |
Minimum of Months | 20.46 | 12.64 |
Maximum of Months | 20.79 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.77 | 13.22 |
February | 20.88 | 13.28 |
March | 21.03 | 12.64 |
April | 20.99 | 15.30 |
May | 20.99 | 15.56 |
June | 21.09 | 17.67 |
July | 20.97 | 19.43 |
August | 21.06 | 19.66 |
September | 20.93 | 18.47 |
October | 20.83 | 18.77 |
November | 20.88 | 14.32 |
December | 20.84 | 13.59 |
Annual Sum or Average | 20.94 | 16.01 |
Minimum of Months | 20.77 | 12.64 |
Maximum of Months | 21.09 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 STORAGE 3
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.87 | 13.22 |
February | 21.01 | 13.28 |
March | 21.19 | 12.64 |
April | 21.13 | 15.30 |
May | 21.14 | 15.56 |
June | 21.27 | 17.67 |
July | 21.12 | 19.43 |
August | 21.21 | 19.66 |
September | 21.08 | 18.47 |
October | 20.97 | 18.77 |
November | 21.00 | 14.32 |
December | 20.96 | 13.59 |
Annual Sum or Average | 21.08 | 16.01 |
Minimum of Months | 20.87 | 12.64 |
Maximum of Months | 21.27 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 UTILITY
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.71 | 13.22 |
February | 20.80 | 13.28 |
March | 21.03 | 12.64 |
April | 21.31 | 15.30 |
May | 21.29 | 15.56 |
June | 21.46 | 17.67 |
July | 21.56 | 19.43 |
August | 21.60 | 19.66 |
September | 21.26 | 18.47 |
October | 21.13 | 18.77 |
November | 20.85 | 14.32 |
December | 20.74 | 13.59 |
Annual Sum or Average | 21.15 | 16.01 |
Minimum of Months | 20.71 | 12.64 |
Maximum of Months | 21.60 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.61 | 13.22 |
February | 21.72 | 13.28 |
March | 21.88 | 12.64 |
April | 21.88 | 15.30 |
May | 21.88 | 15.56 |
June | 21.99 | 17.67 |
July | 21.95 | 19.43 |
August | 21.99 | 19.66 |
September | 21.89 | 18.47 |
October | 21.80 | 18.77 |
November | 21.74 | 14.32 |
December | 21.69 | 13.59 |
Annual Sum or Average | 21.84 | 16.01 |
Minimum of Months | 21.61 | 12.64 |
Maximum of Months | 21.99 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.74 | 13.22 |
February | 21.83 | 13.28 |
March | 21.95 | 12.64 |
April | 21.94 | 15.30 |
May | 21.91 | 15.56 |
June | 22.00 | 17.67 |
July | 21.95 | 19.43 |
August | 22.01 | 19.66 |
September | 21.93 | 18.47 |
October | 21.87 | 18.77 |
November | 21.86 | 14.32 |
December | 21.84 | 13.59 |
Annual Sum or Average | 21.90 | 16.01 |
Minimum of Months | 21.74 | 12.64 |
Maximum of Months | 22.01 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 WORK TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.48 | 13.22 |
February | 19.50 | 13.28 |
March | 19.61 | 12.64 |
April | 19.54 | 15.30 |
May | 19.56 | 15.56 |
June | 19.59 | 17.67 |
July | 19.46 | 19.43 |
August | 19.57 | 19.66 |
September | 19.50 | 18.47 |
October | 19.44 | 18.77 |
November | 19.48 | 14.32 |
December | 19.47 | 13.59 |
Annual Sum or Average | 19.52 | 16.01 |
Minimum of Months | 19.44 | 12.64 |
Maximum of Months | 19.61 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 2 X-RAY
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 22.19 | 13.22 |
February | 22.21 | 13.28 |
March | 22.25 | 12.64 |
April | 22.18 | 15.30 |
May | 22.16 | 15.56 |
June | 22.16 | 17.67 |
July | 22.13 | 19.43 |
August | 22.15 | 19.66 |
September | 22.13 | 18.47 |
October | 22.12 | 18.77 |
November | 22.19 | 14.32 |
December | 22.22 | 13.59 |
Annual Sum or Average | 22.17 | 16.01 |
Minimum of Months | 22.12 | 12.64 |
Maximum of Months | 22.25 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 DRESSING ROOM
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.08 | 13.22 |
February | 21.17 | 13.28 |
March | 21.35 | 12.64 |
April | 21.29 | 15.30 |
May | 21.27 | 15.56 |
June | 21.34 | 17.67 |
July | 21.20 | 19.43 |
August | 21.32 | 19.66 |
September | 21.19 | 18.47 |
October | 21.11 | 18.77 |
November | 21.17 | 14.32 |
December | 21.12 | 13.59 |
Annual Sum or Average | 21.22 | 16.01 |
Minimum of Months | 21.08 | 12.64 |
Maximum of Months | 21.35 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 ELEVATOR HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 13.22 |
February | 21.15 | 13.28 |
March | 21.34 | 12.64 |
April | 21.52 | 15.30 |
May | 21.55 | 15.56 |
June | 21.75 | 17.67 |
July | 21.77 | 19.43 |
August | 21.80 | 19.66 |
September | 21.60 | 18.47 |
October | 21.47 | 18.77 |
November | 21.20 | 14.32 |
December | 21.06 | 13.59 |
Annual Sum or Average | 21.43 | 16.01 |
Minimum of Months | 20.98 | 12.64 |
Maximum of Months | 21.80 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 HUMID
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.24 | 13.22 |
February | 21.33 | 13.28 |
March | 21.50 | 12.64 |
April | 21.45 | 15.30 |
May | 21.43 | 15.56 |
June | 21.50 | 17.67 |
July | 21.38 | 19.43 |
August | 21.49 | 19.66 |
September | 21.37 | 18.47 |
October | 21.29 | 18.77 |
November | 21.33 | 14.32 |
December | 21.29 | 13.59 |
Annual Sum or Average | 21.38 | 16.01 |
Minimum of Months | 21.24 | 12.64 |
Maximum of Months | 21.50 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 JANITOR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.92 | 13.22 |
February | 20.01 | 13.28 |
March | 20.21 | 12.64 |
April | 20.52 | 15.30 |
May | 20.57 | 15.56 |
June | 20.88 | 17.67 |
July | 20.99 | 19.43 |
August | 20.99 | 19.66 |
September | 20.66 | 18.47 |
October | 20.50 | 18.77 |
November | 20.05 | 14.32 |
December | 19.93 | 13.59 |
Annual Sum or Average | 20.44 | 16.01 |
Minimum of Months | 19.92 | 12.64 |
Maximum of Months | 20.99 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOCKER
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.49 | 13.22 |
February | 21.59 | 13.28 |
March | 21.74 | 12.64 |
April | 21.75 | 15.30 |
May | 21.76 | 15.56 |
June | 21.84 | 17.67 |
July | 21.78 | 19.43 |
August | 21.83 | 19.66 |
September | 21.71 | 18.47 |
October | 21.64 | 18.77 |
November | 21.59 | 14.32 |
December | 21.53 | 13.59 |
Annual Sum or Average | 21.69 | 16.01 |
Minimum of Months | 21.49 | 12.64 |
Maximum of Months | 21.84 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.58 | 13.22 |
February | 21.69 | 13.28 |
March | 21.81 | 12.64 |
April | 21.85 | 15.30 |
May | 21.87 | 15.56 |
June | 21.95 | 17.67 |
July | 21.91 | 19.43 |
August | 21.94 | 19.66 |
September | 21.83 | 18.47 |
October | 21.77 | 18.77 |
November | 21.69 | 14.32 |
December | 21.62 | 13.59 |
Annual Sum or Average | 21.79 | 16.01 |
Minimum of Months | 21.58 | 12.64 |
Maximum of Months | 21.95 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 LOUNGE TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.39 | 13.22 |
February | 19.41 | 13.28 |
March | 19.49 | 12.64 |
April | 19.42 | 15.30 |
May | 19.44 | 15.56 |
June | 19.48 | 17.67 |
July | 19.38 | 19.43 |
August | 19.48 | 19.66 |
September | 19.41 | 18.47 |
October | 19.39 | 18.77 |
November | 19.39 | 14.32 |
December | 19.38 | 13.59 |
Annual Sum or Average | 19.42 | 16.01 |
Minimum of Months | 19.38 | 12.64 |
Maximum of Months | 19.49 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 25.57 | 13.22 |
February | 25.60 | 13.28 |
March | 25.44 | 12.64 |
April | 25.72 | 15.30 |
May | 25.64 | 15.56 |
June | 25.48 | 17.67 |
July | 25.78 | 19.43 |
August | 25.41 | 19.66 |
September | 25.56 | 18.47 |
October | 25.52 | 18.77 |
November | 25.60 | 14.32 |
December | 25.69 | 13.59 |
Annual Sum or Average | 25.58 | 16.01 |
Minimum of Months | 25.41 | 12.64 |
Maximum of Months | 25.78 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 MECHANICAL HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.66 | 13.22 |
February | 21.75 | 13.28 |
March | 21.86 | 12.64 |
April | 21.96 | 15.30 |
May | 21.98 | 15.56 |
June | 22.05 | 17.67 |
July | 22.06 | 19.43 |
August | 22.07 | 19.66 |
September | 21.97 | 18.47 |
October | 21.91 | 18.77 |
November | 21.79 | 14.32 |
December | 21.71 | 13.59 |
Annual Sum or Average | 21.90 | 16.01 |
Minimum of Months | 21.66 | 12.64 |
Maximum of Months | 22.07 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.21 | 13.22 |
February | 21.37 | 13.28 |
March | 21.56 | 12.64 |
April | 21.64 | 15.30 |
May | 21.67 | 15.56 |
June | 21.82 | 17.67 |
July | 21.81 | 19.43 |
August | 21.84 | 19.66 |
September | 21.66 | 18.47 |
October | 21.57 | 18.77 |
November | 21.39 | 14.32 |
December | 21.28 | 13.59 |
Annual Sum or Average | 21.57 | 16.01 |
Minimum of Months | 21.21 | 12.64 |
Maximum of Months | 21.84 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE HALL
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.26 | 13.22 |
February | 21.39 | 13.28 |
March | 21.55 | 12.64 |
April | 21.66 | 15.30 |
May | 21.64 | 15.56 |
June | 21.79 | 17.67 |
July | 21.79 | 19.43 |
August | 21.84 | 19.66 |
September | 21.68 | 18.47 |
October | 21.60 | 18.77 |
November | 21.45 | 14.32 |
December | 21.36 | 13.59 |
Annual Sum or Average | 21.59 | 16.01 |
Minimum of Months | 21.26 | 12.64 |
Maximum of Months | 21.84 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 OFFICE TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.42 | 13.22 |
February | 19.44 | 13.28 |
March | 19.54 | 12.64 |
April | 19.48 | 15.30 |
May | 19.49 | 15.56 |
June | 19.54 | 17.67 |
July | 19.43 | 19.43 |
August | 19.53 | 19.66 |
September | 19.46 | 18.47 |
October | 19.41 | 18.77 |
November | 19.42 | 14.32 |
December | 19.40 | 13.59 |
Annual Sum or Average | 19.46 | 16.01 |
Minimum of Months | 19.40 | 12.64 |
Maximum of Months | 19.54 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.01 | 13.22 |
February | 19.98 | 13.28 |
March | 20.02 | 12.64 |
April | 19.95 | 15.30 |
May | 19.82 | 15.56 |
June | 19.83 | 17.67 |
July | 19.76 | 19.43 |
August | 19.99 | 19.66 |
September | 19.94 | 18.47 |
October | 19.93 | 18.77 |
November | 20.03 | 14.32 |
December | 20.02 | 13.59 |
Annual Sum or Average | 19.94 | 16.01 |
Minimum of Months | 19.76 | 12.64 |
Maximum of Months | 20.03 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.75 | 13.22 |
February | 19.79 | 13.28 |
March | 19.94 | 12.64 |
April | 19.78 | 15.30 |
May | 19.76 | 15.56 |
June | 19.75 | 17.67 |
July | 19.60 | 19.43 |
August | 19.73 | 19.66 |
September | 19.66 | 18.47 |
October | 19.62 | 18.77 |
November | 19.74 | 14.32 |
December | 19.74 | 13.59 |
Annual Sum or Average | 19.74 | 16.01 |
Minimum of Months | 19.60 | 12.64 |
Maximum of Months | 19.94 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 PHYSICAL THERAPY TOILET
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 17.86 | 13.22 |
February | 17.96 | 13.28 |
March | 18.12 | 12.64 |
April | 17.89 | 15.30 |
May | 17.83 | 15.56 |
June | 17.68 | 17.67 |
July | 17.47 | 19.43 |
August | 17.53 | 19.66 |
September | 17.52 | 18.47 |
October | 17.46 | 18.77 |
November | 17.86 | 14.32 |
December | 17.87 | 13.59 |
Annual Sum or Average | 17.75 | 16.01 |
Minimum of Months | 17.46 | 12.64 |
Maximum of Months | 18.12 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.94 | 13.22 |
February | 19.99 | 13.28 |
March | 20.15 | 12.64 |
April | 20.08 | 15.30 |
May | 20.07 | 15.56 |
June | 20.10 | 17.67 |
July | 19.97 | 19.43 |
August | 20.08 | 19.66 |
September | 19.97 | 18.47 |
October | 19.90 | 18.77 |
November | 19.97 | 14.32 |
December | 19.95 | 13.59 |
Annual Sum or Average | 20.01 | 16.01 |
Minimum of Months | 19.90 | 12.64 |
Maximum of Months | 20.15 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 STORAGE 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.82 | 13.22 |
February | 20.96 | 13.28 |
March | 21.15 | 12.64 |
April | 21.23 | 15.30 |
May | 21.24 | 15.56 |
June | 21.39 | 17.67 |
July | 21.34 | 19.43 |
August | 21.40 | 19.66 |
September | 21.21 | 18.47 |
October | 21.10 | 18.77 |
November | 20.98 | 14.32 |
December | 20.87 | 13.59 |
Annual Sum or Average | 21.14 | 16.01 |
Minimum of Months | 20.82 | 12.64 |
Maximum of Months | 21.40 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 TREATMENT
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.97 | 13.22 |
February | 20.02 | 13.28 |
March | 20.18 | 12.64 |
April | 20.01 | 15.30 |
May | 19.99 | 15.56 |
June | 19.98 | 17.67 |
July | 19.79 | 19.43 |
August | 19.96 | 19.66 |
September | 19.87 | 18.47 |
October | 19.81 | 18.77 |
November | 19.96 | 14.32 |
December | 19.96 | 13.59 |
Annual Sum or Average | 19.96 | 16.01 |
Minimum of Months | 19.79 | 12.64 |
Maximum of Months | 20.18 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 1
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.98 | 13.22 |
February | 21.04 | 13.28 |
March | 21.14 | 12.64 |
April | 21.29 | 15.30 |
May | 21.23 | 15.56 |
June | 21.36 | 17.67 |
July | 21.37 | 19.43 |
August | 21.46 | 19.66 |
September | 21.33 | 18.47 |
October | 21.27 | 18.77 |
November | 21.15 | 14.32 |
December | 21.10 | 13.59 |
Annual Sum or Average | 21.23 | 16.01 |
Minimum of Months | 20.98 | 12.64 |
Maximum of Months | 21.46 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UNDEVELOPED 2
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.95 | 13.22 |
February | 20.99 | 13.28 |
March | 21.08 | 12.64 |
April | 21.29 | 15.30 |
May | 21.23 | 15.56 |
June | 21.40 | 17.67 |
July | 21.45 | 19.43 |
August | 21.52 | 19.66 |
September | 21.38 | 18.47 |
October | 21.32 | 18.77 |
November | 21.14 | 14.32 |
December | 21.07 | 13.59 |
Annual Sum or Average | 21.24 | 16.01 |
Minimum of Months | 20.95 | 12.64 |
Maximum of Months | 21.52 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 UTILITY
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.26 | 13.22 |
February | 20.36 | 13.28 |
March | 20.52 | 12.64 |
April | 20.54 | 15.30 |
May | 20.52 | 15.56 |
June | 20.60 | 17.67 |
July | 20.53 | 19.43 |
August | 20.60 | 19.66 |
September | 20.46 | 18.47 |
October | 20.37 | 18.77 |
November | 20.35 | 14.32 |
December | 20.31 | 13.59 |
Annual Sum or Average | 20.45 | 16.01 |
Minimum of Months | 20.26 | 12.64 |
Maximum of Months | 20.60 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: FLOOR 3 WORK
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 21.05 | 13.22 |
February | 21.13 | 13.28 |
March | 21.30 | 12.64 |
April | 21.48 | 15.30 |
May | 21.53 | 15.56 |
June | 21.62 | 17.67 |
July | 21.67 | 19.43 |
August | 21.70 | 19.66 |
September | 21.49 | 18.47 |
October | 21.44 | 18.77 |
November | 21.20 | 14.32 |
December | 21.09 | 13.59 |
Annual Sum or Average | 21.39 | 16.01 |
Minimum of Months | 21.05 | 12.64 |
Maximum of Months | 21.70 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: NE STAIR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.09 | 13.22 |
February | 20.13 | 13.28 |
March | 20.33 | 12.64 |
April | 20.71 | 15.30 |
May | 20.86 | 15.56 |
June | 21.22 | 17.67 |
July | 21.37 | 19.43 |
August | 21.31 | 19.66 |
September | 21.03 | 18.47 |
October | 20.85 | 18.77 |
November | 20.21 | 14.32 |
December | 20.06 | 13.59 |
Annual Sum or Average | 20.68 | 16.01 |
Minimum of Months | 20.06 | 12.64 |
Maximum of Months | 21.37 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: NW ELEVATOR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.37 | 13.22 |
February | 20.42 | 13.28 |
March | 20.55 | 12.64 |
April | 20.87 | 15.30 |
May | 20.89 | 15.56 |
June | 21.17 | 17.67 |
July | 21.29 | 19.43 |
August | 21.30 | 19.66 |
September | 21.10 | 18.47 |
October | 20.93 | 18.77 |
November | 20.54 | 14.32 |
December | 20.42 | 13.59 |
Annual Sum or Average | 20.82 | 16.01 |
Minimum of Months | 20.37 | 12.64 |
Maximum of Months | 21.30 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: NW STAIR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.97 | 13.22 |
February | 20.07 | 13.28 |
March | 20.31 | 12.64 |
April | 20.74 | 15.30 |
May | 20.91 | 15.56 |
June | 21.27 | 17.67 |
July | 21.41 | 19.43 |
August | 21.35 | 19.66 |
September | 21.06 | 18.47 |
October | 20.83 | 18.77 |
November | 20.14 | 14.32 |
December | 19.95 | 13.59 |
Annual Sum or Average | 20.67 | 16.01 |
Minimum of Months | 19.95 | 12.64 |
Maximum of Months | 21.41 | 19.66 |
Report: MONTHLY INDOOR TEMP
For: SW STAIR
Timestamp: 2018-10-19 19:10:35
ZONE MEAN AIR TEMPERATURE [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 20.64 | 13.22 |
February | 20.62 | 13.28 |
March | 20.68 | 12.64 |
April | 20.95 | 15.30 |
May | 20.91 | 15.56 |
June | 21.16 | 17.67 |
July | 21.29 | 19.43 |
August | 21.34 | 19.66 |
September | 21.21 | 18.47 |
October | 21.10 | 18.77 |
November | 20.78 | 14.32 |
December | 20.71 | 13.59 |
Annual Sum or Average | 20.95 | 16.01 |
Minimum of Months | 20.62 | 12.64 |
Maximum of Months | 21.34 | 19.66 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-1
Timestamp: 2018-10-19 19:10:35
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.569470E+11 | 0.110054E+12 |
February | 0.503853E+11 | 0.103985E+12 |
March | 0.504816E+11 | 0.116328E+12 |
April | 0.469771E+11 | 0.137846E+12 |
May | 0.485113E+11 | 0.143625E+12 |
June | 0.446498E+11 | 0.175170E+12 |
July | 0.452134E+11 | 0.212395E+12 |
August | 0.447894E+11 | 0.225757E+12 |
September | 0.439530E+11 | 0.185342E+12 |
October | 0.498697E+11 | 0.170560E+12 |
November | 0.556694E+11 | 0.119325E+12 |
December | 0.650105E+11 | 0.107893E+12 |
Annual Sum or Average | 0.602457E+12 | 0.180828E+13 |
Minimum of Months | 0.439530E+11 | 0.103985E+12 |
Maximum of Months | 0.650105E+11 | 0.225757E+12 |
Report: OVERALL HVAC AIR SYSTEM LOADS
For: AHU-2
Timestamp: 2018-10-19 19:10:35
AIR SYSTEM TOTAL HEATING ENERGY [J] | AIR SYSTEM TOTAL COOLING ENERGY [J] | |
January | 0.297708E+11 | 0.539001E+11 |
February | 0.259861E+11 | 0.383227E+11 |
March | 0.284200E+11 | 0.433016E+11 |
April | 0.280534E+11 | 0.838310E+11 |
May | 0.292741E+11 | 0.949415E+11 |
June | 0.295469E+11 | 0.154534E+12 |
July | 0.313575E+11 | 0.219332E+12 |
August | 0.317623E+11 | 0.237757E+12 |
September | 0.301289E+11 | 0.174365E+12 |
October | 0.309566E+11 | 0.152890E+12 |
November | 0.270619E+11 | 0.608033E+11 |
December | 0.285681E+11 | 0.542660E+11 |
Annual Sum or Average | 0.350887E+12 | 0.136824E+13 |
Minimum of Months | 0.259861E+11 | 0.383227E+11 |
Maximum of Months | 0.317623E+11 | 0.237757E+12 |
Report: OVERALL HVAC SYSTEM ENERGY
For: Meter
Timestamp: 2018-10-19 19:10:35
ELECTRICITY:HVAC [J] | HEATING:GAS [J] | |
January | 0.974667E+11 | 0.465898E+11 |
February | 0.843709E+11 | 0.422314E+11 |
March | 0.859802E+11 | 0.496014E+11 |
April | 0.100427E+12 | 0.449752E+11 |
May | 0.106184E+12 | 0.466571E+11 |
June | 0.128612E+12 | 0.417297E+11 |
July | 0.155405E+12 | 0.424976E+11 |
August | 0.164368E+12 | 0.408994E+11 |
September | 0.136724E+12 | 0.412041E+11 |
October | 0.134518E+12 | 0.427964E+11 |
November | 0.101034E+12 | 0.415384E+11 |
December | 0.107573E+12 | 0.420187E+11 |
Annual Sum or Average | 0.140266E+13 | 0.522739E+12 |
Minimum of Months | 0.843709E+11 | 0.408994E+11 |
Maximum of Months | 0.164368E+12 | 0.496014E+11 |
Report: COMPONENTS OF PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:35
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.308307E+12 | 246632.586 | 06-JAN-13:00 | 35585.685 | 111201.830 | 27124.587 | 16910.833 | 40506.945 | 0.000 | 52.572 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.274909E+12 | 259841.707 | 03-FEB-14:00 | 35585.685 | 111201.830 | 26849.927 | 17220.494 | 48575.533 | 0.000 | 47.759 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.304780E+12 | 241068.822 | 23-MAR-14:30 | 35585.685 | 111201.830 | 26713.582 | 3924.978 | 63589.960 | 0.000 | 52.787 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.302148E+12 | 244089.520 | 26-APR-12:00 | 35585.685 | 111201.830 | 26194.714 | 4255.371 | 66799.672 | 0.000 | 52.248 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.318447E+12 | 235383.173 | 04-MAY-13:30 | 35585.685 | 111201.830 | 24662.746 | 4442.596 | 59436.963 | 0.000 | 53.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.337277E+12 | 246837.371 | 29-JUN-12:00 | 35585.685 | 111201.830 | 24547.259 | 4808.789 | 70641.591 | 0.000 | 52.217 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.359366E+12 | 261686.766 | 19-JUL-13:00 | 35585.685 | 111201.830 | 27205.157 | 4195.209 | 83449.566 | 0.000 | 49.319 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.381815E+12 | 266445.957 | 17-AUG-13:00 | 35585.685 | 111201.830 | 27995.870 | 3934.548 | 87679.460 | 0.000 | 48.564 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.338958E+12 | 275373.585 | 29-SEP-12:00 | 35585.685 | 111201.830 | 32314.729 | 2457.073 | 93769.107 | 0.000 | 45.161 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.344228E+12 | 262054.943 | 16-OCT-10:00 | 35585.685 | 111201.830 | 23935.997 | 5911.352 | 85365.562 | 0.000 | 54.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.306703E+12 | 256349.833 | 28-NOV-13:00 | 35585.685 | 111201.830 | 26852.094 | 17501.628 | 52871.373 | 0.000 | 48.179 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.315390E+12 | 256164.123 | 19-DEC-13:09 | 35585.685 | 111201.830 | 26811.946 | 17576.315 | 54046.118 | 0.000 | 47.245 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.389233E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.274909E+12 | 235383.173 | 35585.685 | 111201.830 | 23935.997 | 2457.073 | 40506.945 | 0.000 | 45.161 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.381815E+12 | 275373.585 | 35585.685 | 111201.830 | 32314.729 | 17576.315 | 93769.107 | 0.000 | 54.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: ENERGY CONSUMPTION - ELECTRICITY & NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:35
ELECTRICITY:BUILDING [J] | ELECTRICITY:BUILDING {Maximum}[W] | ELECTRICITY:BUILDING {TIMESTAMP} | GAS:BUILDING [J] | GAS:BUILDING {Maximum}[W] | GAS:BUILDING {TIMESTAMP} | |
January | 0.199311E+12 | 147082.42 | 02-JAN-16:49 | 0.158619E+11 | 9905.77 | 02-JAN-06:10 |
February | 0.180765E+12 | 147082.42 | 01-FEB-17:19 | 0.143713E+11 | 9905.77 | 01-FEB-06:10 |
March | 0.208894E+12 | 147082.42 | 01-MAR-17:30 | 0.163897E+11 | 9905.77 | 01-MAR-06:10 |
April | 0.193059E+12 | 147033.27 | 21-APR-16:10 | 0.153698E+11 | 9905.77 | 03-APR-05:10 |
May | 0.204060E+12 | 146934.97 | 02-MAY-08:09 | 0.161258E+11 | 9905.77 | 01-MAY-05:10 |
June | 0.201094E+12 | 146934.97 | 01-JUN-08:09 | 0.158049E+11 | 9905.77 | 01-JUN-05:10 |
July | 0.196021E+12 | 146934.97 | 03-JUL-09:20 | 0.156907E+11 | 9905.77 | 03-JUL-05:10 |
August | 0.208879E+12 | 146934.97 | 03-AUG-08:09 | 0.163897E+11 | 9905.77 | 01-AUG-05:10 |
September | 0.193070E+12 | 147082.42 | 21-SEP-16:40 | 0.153698E+11 | 9905.77 | 01-SEP-05:10 |
October | 0.199297E+12 | 147082.42 | 03-OCT-16:49 | 0.158619E+11 | 9905.77 | 02-OCT-05:10 |
November | 0.194762E+12 | 147082.42 | 01-NOV-16:40 | 0.154482E+11 | 9905.77 | 01-NOV-05:10 |
December | 0.196076E+12 | 147082.42 | 01-DEC-16:10 | 0.156907E+11 | 9905.77 | 01-DEC-06:10 |
Annual Sum or Average | 0.237529E+13 | 0.188374E+12 | ||||
Minimum of Months | 0.180765E+12 | 146934.97 | 0.143713E+11 | 9905.77 | ||
Maximum of Months | 0.208894E+12 | 147082.42 | 0.163897E+11 | 9905.77 |
Report: BUILDING ENERGY PERFORMANCE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:35
INTERIORLIGHTS:ELECTRICITY [J] | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY [J] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | COGENERATION:ELECTRICITY [Invalid/Undefined] | |
January | 0.451574E+11 | 0.00 | 0.113408E+11 | 0.154153E+12 | 0.00 | 0.343353E+11 | 0.188621E+09 | 0.162547E+11 | 0.416334E+11 | 0.00 | 0.524331E+10 | 0.00 | 0.00 | 0.00 |
February | 0.410393E+11 | 0.00 | 0.960731E+10 | 0.139726E+12 | 0.00 | 0.310501E+11 | 0.164898E+09 | 0.127445E+11 | 0.361557E+11 | 0.00 | 0.442066E+10 | 0.00 | 0.00 | 0.00 |
March | 0.485034E+11 | 0.00 | 0.971430E+10 | 0.160390E+12 | 0.00 | 0.354992E+11 | 0.191562E+09 | 0.100849E+11 | 0.402645E+11 | 0.00 | 0.131643E+09 | 0.00 | 0.00 | 0.00 |
April | 0.437466E+11 | 0.00 | 0.849602E+10 | 0.149313E+12 | 0.00 | 0.338858E+11 | 0.166084E+09 | 0.106572E+11 | 0.554616E+11 | 0.00 | 0.422453E+09 | 0.00 | 0.00 | 0.00 |
May | 0.467885E+11 | 0.00 | 0.803028E+10 | 0.157272E+12 | 0.00 | 0.347038E+11 | 0.172046E+09 | 0.117290E+11 | 0.595916E+11 | 0.00 | 0.159776E+09 | 0.00 | 0.00 | 0.00 |
June | 0.465527E+11 | 0.00 | 0.741774E+10 | 0.154542E+12 | 0.00 | 0.351905E+11 | 0.152419E+09 | 0.117044E+11 | 0.817175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.439780E+11 | 0.00 | 0.778688E+10 | 0.152043E+12 | 0.00 | 0.355340E+11 | 0.154100E+09 | 0.133325E+11 | 0.106538E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.484889E+11 | 0.00 | 0.841816E+10 | 0.160390E+12 | 0.00 | 0.376722E+11 | 0.149563E+09 | 0.125832E+11 | 0.114113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437575E+11 | 0.00 | 0.901447E+10 | 0.149313E+12 | 0.00 | 0.346099E+11 | 0.150403E+09 | 0.125854E+11 | 0.895283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451438E+11 | 0.00 | 0.102531E+11 | 0.154153E+12 | 0.00 | 0.347918E+11 | 0.160433E+09 | 0.153622E+11 | 0.817690E+11 | 0.00 | 0.259468E+10 | 0.00 | 0.00 | 0.00 |
November | 0.443467E+11 | 0.00 | 0.107427E+11 | 0.150416E+12 | 0.00 | 0.336022E+11 | 0.163894E+09 | 0.146264E+11 | 0.455524E+11 | 0.00 | 0.725298E+10 | 0.00 | 0.00 | 0.00 |
December | 0.440333E+11 | 0.00 | 0.115645E+11 | 0.152043E+12 | 0.00 | 0.344867E+11 | 0.176936E+09 | 0.196670E+11 | 0.413087E+11 | 0.00 | 0.121104E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.541536E+12 | 0.00 | 0.112386E+12 | 0.183375E+13 | 0.00 | 0.415361E+12 | 0.199096E+10 | 0.161331E+12 | 0.793634E+12 | 0.00 | 0.323359E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.410393E+11 | 0.00 | 0.741774E+10 | 0.139726E+12 | 0.00 | 0.310501E+11 | 0.149563E+09 | 0.100849E+11 | 0.361557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.485034E+11 | 0.00 | 0.115645E+11 | 0.160390E+12 | 0.00 | 0.376722E+11 | 0.191562E+09 | 0.196670E+11 | 0.114113E+12 | 0.00 | 0.121104E+11 | 0.00 | 0.00 | 0.00 |
Report: BUILDING ENERGY PERFORMANCE - NATURAL GAS
For: Meter
Timestamp: 2018-10-19 19:10:35
INTERIOREQUIPMENT:GAS [J] | EXTERIOREQUIPMENT:GAS [Invalid/Undefined] | HEATING:GAS [J] | COOLING:GAS [Invalid/Undefined] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [Invalid/Undefined] | |
January | 0.158619E+11 | 0.00 | 0.465898E+11 | 0.00 | 0.203132E+11 | 0.00 |
February | 0.143713E+11 | 0.00 | 0.422314E+11 | 0.00 | 0.183478E+11 | 0.00 |
March | 0.163897E+11 | 0.00 | 0.496014E+11 | 0.00 | 0.202596E+11 | 0.00 |
April | 0.153698E+11 | 0.00 | 0.449752E+11 | 0.00 | 0.194779E+11 | 0.00 |
May | 0.161258E+11 | 0.00 | 0.466571E+11 | 0.00 | 0.201271E+11 | 0.00 |
June | 0.158049E+11 | 0.00 | 0.417297E+11 | 0.00 | 0.194779E+11 | 0.00 |
July | 0.156907E+11 | 0.00 | 0.424976E+11 | 0.00 | 0.201271E+11 | 0.00 |
August | 0.163897E+11 | 0.00 | 0.408994E+11 | 0.00 | 0.201271E+11 | 0.00 |
September | 0.153698E+11 | 0.00 | 0.412041E+11 | 0.00 | 0.194779E+11 | 0.00 |
October | 0.158619E+11 | 0.00 | 0.427964E+11 | 0.00 | 0.201271E+11 | 0.00 |
November | 0.154482E+11 | 0.00 | 0.415384E+11 | 0.00 | 0.194779E+11 | 0.00 |
December | 0.156907E+11 | 0.00 | 0.420187E+11 | 0.00 | 0.202066E+11 | 0.00 |
Annual Sum or Average | 0.188374E+12 | 0.00 | 0.522739E+12 | 0.00 | 0.237547E+12 | 0.00 |
Minimum of Months | 0.143713E+11 | 0.00 | 0.408994E+11 | 0.00 | 0.183478E+11 | 0.00 |
Maximum of Months | 0.163897E+11 | 0.00 | 0.496014E+11 | 0.00 | 0.203132E+11 | 0.00 |
Report: PEAK ENERGY END-USE - ELECTRICITY
For: Meter
Timestamp: 2018-10-19 19:10:35
INTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | TASKLIGHTS:INTERIORLIGHTS:ELECTRICITY [Invalid/Undefined] | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | GENERAL:INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 35880.59 | 02-JAN-07:10 | 0.00 | 8471.50 | 01-JAN-06:10 | 111201.83 | 02-JAN-09:09 | 0.00 | 28633.36 | 26-JAN-15:20 | 229.10 | 08-JAN-06:00 | 52053.93 | 07-JAN-07:10 |
February | 35880.59 | 01-FEB-07:10 | 0.00 | 8471.50 | 01-FEB-06:10 | 111201.83 | 01-FEB-09:09 | 0.00 | 27607.41 | 22-FEB-15:30 | 196.04 | 11-FEB-07:10 | 48750.74 | 04-FEB-07:10 |
March | 35880.59 | 01-MAR-17:30 | 0.00 | 8471.50 | 01-MAR-06:10 | 111201.83 | 01-MAR-09:09 | 0.00 | 27720.00 | 24-MAR-14:00 | 180.53 | 11-MAR-07:10 | 33977.60 | 18-MAR-06:10 |
April | 35880.59 | 03-APR-06:10 | 0.00 | 8471.50 | 01-APR-05:10 | 111201.83 | 03-APR-08:09 | 0.00 | 27540.48 | 28-APR-14:00 | 191.92 | 01-APR-06:10 | 40685.49 | 01-APR-06:30 |
May | 35880.59 | 08-MAY-06:10 | 0.00 | 8471.50 | 01-MAY-18:30 | 111201.83 | 01-MAY-08:09 | 0.00 | 26461.32 | 19-MAY-16:30 | 173.72 | 13-MAY-06:10 | 35158.42 | 06-MAY-06:10 |
June | 35880.59 | 09-JUN-06:10 | 0.00 | 8471.50 | 01-JUN-18:49 | 111201.83 | 01-JUN-08:09 | 0.00 | 26918.45 | 30-JUN-16:30 | 160.00 | 17-JUN-06:10 | 35098.05 | 17-JUN-06:10 |
July | 35880.59 | 11-JUL-06:10 | 0.00 | 8471.50 | 01-JUL-18:00 | 111201.83 | 03-JUL-08:09 | 0.00 | 28086.08 | 19-JUL-15:00 | 156.03 | 08-JUL-06:10 | 32813.65 | 22-JUL-06:10 |
August | 35880.59 | 01-AUG-06:10 | 0.00 | 8471.50 | 01-AUG-18:49 | 111201.83 | 01-AUG-08:09 | 0.00 | 28681.91 | 18-AUG-14:00 | 150.94 | 12-AUG-06:10 | 33600.99 | 12-AUG-06:10 |
September | 35880.59 | 01-SEP-06:10 | 0.00 | 8471.50 | 01-SEP-05:10 | 111201.83 | 01-SEP-08:09 | 0.00 | 33881.86 | 29-SEP-14:50 | 163.54 | 16-SEP-06:10 | 36101.01 | 09-SEP-06:10 |
October | 35880.59 | 02-OCT-06:10 | 0.00 | 8471.50 | 01-OCT-05:10 | 111201.83 | 02-OCT-08:09 | 0.00 | 30156.56 | 17-OCT-14:39 | 184.71 | 28-OCT-06:10 | 52701.60 | 14-OCT-06:10 |
November | 35880.59 | 01-NOV-06:10 | 0.00 | 8471.50 | 01-NOV-05:10 | 111201.83 | 01-NOV-08:09 | 0.00 | 28278.90 | 22-NOV-14:20 | 191.68 | 25-NOV-07:10 | 45064.47 | 27-NOV-07:10 |
December | 35880.59 | 01-DEC-07:10 | 0.00 | 8471.50 | 01-DEC-06:10 | 111201.83 | 01-DEC-09:09 | 0.00 | 27668.26 | 19-DEC-14:30 | 185.75 | 16-DEC-07:10 | 48256.07 | 30-DEC-07:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 35880.59 | 0.00 | 8471.50 | 111201.83 | 0.00 | 26461.32 | 150.94 | 32813.65 | ||||||
Maximum of Months | 35880.59 | 0.00 | 8471.50 | 111201.83 | 0.00 | 33881.86 | 229.10 | 52701.60 |
Report: PEAK ELECTRICAL DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:35
ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [Invalid/Undefined] | EXTERIOREQUIPMENT:ELECTRICITY [Invalid/Undefined] | HUMIDIFICATION:ELECTRICITY [Invalid/Undefined] | HEATRECOVERY:ELECTRICITY [Invalid/Undefined] | WATERSYSTEMS:ELECTRICITY [Invalid/Undefined] | REFRIGERATION:ELECTRICITY [Invalid/Undefined] | GENERATORS:ELECTRICITY [Invalid/Undefined] | ELECTRICITYPRODUCED:FACILITY [Invalid/Undefined] | |
January | 0.308307E+12 | 246632.586 | 06-JAN-13:00 | 35585.685 | 111201.830 | 27124.587 | 16910.833 | 40506.945 | 0.000 | 52.572 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
February | 0.274909E+12 | 259841.707 | 03-FEB-14:00 | 35585.685 | 111201.830 | 26849.927 | 17220.494 | 48575.533 | 0.000 | 47.759 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
March | 0.304780E+12 | 241068.822 | 23-MAR-14:30 | 35585.685 | 111201.830 | 26713.582 | 3924.978 | 63589.960 | 0.000 | 52.787 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
April | 0.302148E+12 | 244089.520 | 26-APR-12:00 | 35585.685 | 111201.830 | 26194.714 | 4255.371 | 66799.672 | 0.000 | 52.248 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
May | 0.318447E+12 | 235383.173 | 04-MAY-13:30 | 35585.685 | 111201.830 | 24662.746 | 4442.596 | 59436.963 | 0.000 | 53.353 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
June | 0.337277E+12 | 246837.371 | 29-JUN-12:00 | 35585.685 | 111201.830 | 24547.259 | 4808.789 | 70641.591 | 0.000 | 52.217 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 0.359366E+12 | 261686.766 | 19-JUL-13:00 | 35585.685 | 111201.830 | 27205.157 | 4195.209 | 83449.566 | 0.000 | 49.319 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.381815E+12 | 266445.957 | 17-AUG-13:00 | 35585.685 | 111201.830 | 27995.870 | 3934.548 | 87679.460 | 0.000 | 48.564 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.338958E+12 | 275373.585 | 29-SEP-12:00 | 35585.685 | 111201.830 | 32314.729 | 2457.073 | 93769.107 | 0.000 | 45.161 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.344228E+12 | 262054.943 | 16-OCT-10:00 | 35585.685 | 111201.830 | 23935.997 | 5911.352 | 85365.562 | 0.000 | 54.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
November | 0.306703E+12 | 256349.833 | 28-NOV-13:00 | 35585.685 | 111201.830 | 26852.094 | 17501.628 | 52871.373 | 0.000 | 48.179 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
December | 0.315390E+12 | 256164.123 | 19-DEC-13:09 | 35585.685 | 111201.830 | 26811.946 | 17576.315 | 54046.118 | 0.000 | 47.245 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Annual Sum or Average | 0.389233E+13 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |||||||||
Minimum of Months | 0.274909E+12 | 235383.173 | 35585.685 | 111201.830 | 23935.997 | 2457.073 | 40506.945 | 0.000 | 45.161 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | |
Maximum of Months | 0.381815E+12 | 275373.585 | 35585.685 | 111201.830 | 32314.729 | 17576.315 | 93769.107 | 0.000 | 54.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: PEAK GAS DEMAND
For: Meter
Timestamp: 2018-10-19 19:10:35
GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | GAS:HVAC [Invalid/Undefined] | INTERIOREQUIPMENT:GAS {AT MAX/MIN} [W] | MISCPLUGGAS:INTERIOREQUIPMENT:GAS [Invalid/Undefined] | GAS:PLANT {AT MAX/MIN} [W] | WATERSYSTEMS:GAS {AT MAX/MIN} [W] | WATER HEATER:WATERSYSTEMS:GAS {AT MAX/MIN} [W] | HEATING:GAS {AT MAX/MIN} [W] | |
January | 0.827648E+11 | 79855.765 | 28-JAN-07:10 | 0.000 | 4952.884 | 0.000 | 74902.881 | 7514.610 | 7514.610 | 67388.271 |
February | 0.749504E+11 | 71747.323 | 25-FEB-07:10 | 0.000 | 4952.884 | 0.000 | 66794.439 | 7514.610 | 7514.610 | 59279.829 |
March | 0.862507E+11 | 68219.472 | 04-MAR-07:10 | 0.000 | 4952.884 | 0.000 | 63266.588 | 7514.610 | 7514.610 | 55751.978 |
April | 0.798229E+11 | 68782.251 | 22-APR-06:10 | 0.000 | 4952.884 | 0.000 | 63829.367 | 7514.610 | 7514.610 | 56314.757 |
May | 0.829100E+11 | 65836.324 | 06-MAY-06:10 | 0.000 | 4952.884 | 0.000 | 60883.440 | 7514.610 | 7514.610 | 53368.830 |
June | 0.770124E+11 | 61589.505 | 17-JUN-06:10 | 0.000 | 4952.884 | 0.000 | 56636.621 | 7514.610 | 7514.610 | 49122.011 |
July | 0.783155E+11 | 59962.784 | 08-JUL-06:10 | 0.000 | 4952.884 | 0.000 | 55009.900 | 7514.610 | 7514.610 | 47495.290 |
August | 0.774162E+11 | 57871.422 | 12-AUG-06:10 | 0.000 | 4952.884 | 0.000 | 52918.538 | 7514.610 | 7514.610 | 45403.928 |
September | 0.760517E+11 | 62976.733 | 16-SEP-06:10 | 0.000 | 4952.884 | 0.000 | 58023.848 | 7514.610 | 7514.610 | 50509.238 |
October | 0.787855E+11 | 67141.281 | 28-OCT-06:10 | 0.000 | 4952.884 | 0.000 | 62188.397 | 7514.610 | 7514.610 | 54673.787 |
November | 0.764645E+11 | 70251.272 | 04-NOV-06:10 | 0.000 | 4952.884 | 0.000 | 65298.388 | 7514.610 | 7514.610 | 57783.778 |
December | 0.779160E+11 | 69735.557 | 02-DEC-07:10 | 0.000 | 4952.884 | 0.000 | 64782.673 | 7514.610 | 7514.610 | 57268.063 |
Annual Sum or Average | 0.948661E+12 | 0.000 | 0.000 | |||||||
Minimum of Months | 0.749504E+11 | 57871.422 | 0.000 | 4952.884 | 0.000 | 52918.538 | 7514.610 | 7514.610 | 45403.928 | |
Maximum of Months | 0.862507E+11 | 79855.765 | 0.000 | 4952.884 | 0.000 | 74902.881 | 7514.610 | 7514.610 | 67388.271 |