Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27

Tabular Output Report in Format: HTML

Building: MF+CZ1A+USA_FL_Miami.Intl.AP.722020+gasfurnace+crawlspace+IECC_2012

Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2019-02-14 08:27:57


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 902807.53 23.15 41.78
Net Site Energy 902807.53 23.15 41.78
Total Source Energy 2092348.86 53.64 96.82
Net Source Energy 2092348.86 53.64 96.82


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 6431.60 0.00 0.00 0.00 0.00
Cooling 188726.20 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 261812.16 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 31192.82 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 197738.55 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 534664.19 368143.35 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 6431.60 0.00 0.00 0.00 0.00
Cooling General 188726.20 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 31192.82 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 197738.55 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 10.18 9.45 0.00 0.00 0.00 17.48
Other 12.12 7.59 0.00 0.00 0.00 0.00
Total 24.74 17.04 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 5.64 5.23 0.00 0.00 0.00 9.68
Other 6.71 4.20 0.00 0.00 0.00 0.00
Total 13.71 9.44 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 534664.186 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 534664.186 100.00
     
Total On-Site and Utility Electric Sources 534664.186 100.00
Total Electricity End Uses 534664.186 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3214.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
RunPeriod ANNUAL
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [ft] 36.09
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.3689 1083.48 2.4729
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 4.4634
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:15 04-FEB-07:30 - - - 01-JAN-08:30
Heating 0.00 78.52 0.00 0.00 0.00 0.00
Cooling 51.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41.39 17.85 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.77 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 145.62 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 115.44 241.99 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 78.52 0.00 0.00 0.00 0.00
Cooling General 51.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.38 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.63 7.91 0.00 0.00 0.00 0.00
  gas_range 0.00 7.84 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 22.66 2.10 0.00 0.00 0.00 0.00
  IECC_adj 9.39 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.77 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 145.62 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 6971.86 0.00 0.00 0.00
Cooling 597695.86 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 829159.12 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 98787.66 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 214348.59 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1693281.48 399067.39 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 0.32 0.00 0.00 0.00
Cooling 27.66 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 38.37 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.57 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.92 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 78.36 18.47 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 0.32 0.00 0.00 0.00
Cooling 27.66 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 38.37 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.57 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.92 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 78.36 18.47 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 47.66 0.00 47.66 Wetbulb [F] 748.07 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 91.76 12.06 77.54 Wetbulb [F] 885.87 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.219 0.882              
North Total or Average           531.68 0.501 0.219 0.882              
Non-North Total or Average           1595.05 0.501 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   24257.61 18167.50 6090.11 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9331.60 6308.94 3022.66 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10770.40 7325.97 3444.43 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14177.38 9961.55 4215.84 0.70 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9595.55 6487.39 3108.16 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10897.00 7424.49 3472.51 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13901.85 9885.85 4016.00 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9610.56 6542.94 3067.62 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10796.45 7425.99 3370.45 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13966.68 9936.83 4029.85 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9785.15 6676.97 3108.18 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10889.71 7508.01 3381.70 0.69 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16419.78 11765.70 4654.08 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12096.35 8389.87 3706.48 0.69 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13305.15 9286.16 4018.99 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16444.36 11785.46 4658.90 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12171.84 8449.01 3722.84 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13305.26 9299.89 4005.37 0.70 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.9 3.35 11.44 12.13 11.78
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.8 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.49 11.91 12.64 12.56
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.44 11.75 12.47 12.30
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.8 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.9 3.49 11.90 12.63 12.55
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.43 11.69 12.41 12.20
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.49 11.90 12.64 12.56
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.47 11.85 12.58 12.47
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.43 11.69 12.40 12.20
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.49 11.89 12.63 12.54
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.9 3.47 11.84 12.57 12.45
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.42 11.66 12.36 12.14
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.0 3.46 11.81 12.54 12.40
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.1 3.45 11.78 12.51 12.35
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.42 11.66 12.36 12.14
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.0 3.46 11.81 12.53 12.40
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.1 3.45 11.78 12.50 12.34
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   3616.94 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   4010.50 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   5307.83 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   5315.85 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   4132.69 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   5310.28 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   4202.81 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   3616.94 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   4501.29 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   4506.08 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   3616.94 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   4499.03 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   5664.75 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   4506.40 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   5705.92 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   5712.15 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   4513.33 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   5705.06 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 786.88 296.81 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 233.34 88.01 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 273.83 103.29 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 392.92 148.21 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 239.94 90.50 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 278.32 104.98 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 397.31 149.86 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 244.95 92.39 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 282.89 106.71 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 399.66 150.75 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 250.94 94.65 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 287.16 108.32 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 478.38 180.44 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 324.07 122.24 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 362.36 136.68 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 479.32 180.80 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 326.79 123.26 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 363.76 137.21 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18460.72 18460.72 15.38 786.884 786.884 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00886 89.17 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5474.53 5474.53 4.56 233.339 233.339 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01042 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6424.60 6424.60 5.35 273.834 273.834 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01009 88.08 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9218.20 9218.20 7.68 392.917 392.917 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00960 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5629.36 5629.36 4.69 239.939 239.939 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01038 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6529.81 6529.81 5.44 278.319 278.319 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01007 88.08 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9321.54 9321.54 7.76 397.310 397.310 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00931 88.87 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5746.98 5746.98 4.79 244.946 244.946 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00996 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6637.23 6637.23 5.53 282.894 282.894 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00974 88.41 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9376.68 9376.68 7.81 399.661 399.661 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00930 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5887.67 5887.67 4.90 250.943 250.943 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00993 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6737.36 6737.36 5.61 287.161 287.161 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00975 87.96 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8534.31 8534.31 7.11 363.761 363.761 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00972 87.96 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8501.51 8501.51 7.08 362.365 362.365 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00972 88.41 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11223.30 11223.30 9.35 478.384 478.384 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00935 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7666.95 7666.95 6.39 326.788 326.788 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00985 87.06 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7603.29 7603.29 6.33 324.075 324.075 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00986 87.06 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11245.24 11245.24 9.37 479.319 479.319 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00935 88.87 0.01715 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2868.25 2868.25 2.39 52.274 52.274 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4184.77 4184.77 3.49 76.267 76.267 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4192.91 4192.91 3.49 76.415 76.415 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2992.25 2992.25 2.49 54.533 54.533 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00781 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4187.26 4187.26 3.49 76.312 76.312 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3063.39 3063.39 2.55 55.830 55.830 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00792 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2148.59 2148.59 1.79 39.158 44.995 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:00:00 72.00 72.00 0.00804 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3366.28 3366.28 2.80 61.350 61.350 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00792 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3371.15 3371.15 2.81 61.439 61.439 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00792 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2174.54 2174.54 1.81 39.631 44.995 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 10:00:00 72.00 72.00 0.00803 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3363.99 3363.99 2.80 61.309 61.309 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 72.00 0.00792 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4587.87 4587.87 3.82 83.613 83.613 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 4588.74 4588.74 3.82 83.629 83.629 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 4546.96 4546.96 3.79 82.867 82.867 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3378.52 3378.52 2.81 61.573 61.573 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00781 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3371.49 3371.49 2.81 61.445 61.445 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00781 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 4595.07 4595.07 3.83 83.744 83.744 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 72.00 0.00780 47.66 0.00699 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 786.88 786.88 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 233.34 233.34 52.27 52.27
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 273.83 273.83 76.27 76.27
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.92 392.92 76.41 76.41
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 239.94 239.94 54.53 54.53
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 278.32 278.32 76.31 76.31
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 397.31 397.31 55.83 55.83
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.95 244.95 44.99 44.99
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 282.89 282.89 61.35 61.35
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 399.66 399.66 61.44 61.44
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 250.94 250.94 44.99 44.99
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 287.16 287.16 61.31 61.31
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 478.38 478.38 82.87 82.87
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 324.07 324.07 61.44 61.44
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.36 362.36 83.63 83.63
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 479.32 479.32 83.74 83.74
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 326.79 326.79 61.57 61.57
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 363.76 363.76 83.61 83.61


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4059.25 1402.25 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7252.00 3470.50 2754.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7299.25 3178.00 2392.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7225.75 3977.00 2990.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7120.75 3873.00 2950.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7176.75 3436.75 2491.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7459.25 2116.00 1475.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7308.25 1474.50 965.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7358.75 1696.75 1083.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7313.00 2364.75 1566.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7161.50 1748.00 1070.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7236.25 1899.25 1140.25
LIVING_UNIT3_BACKROW_TOPFLOOR 7376.50 2472.75 1679.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 7471.75 2324.00 1623.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 7502.50 2768.75 2021.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7333.00 2597.25 1838.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 7460.25 2379.25 1744.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7408.00 2939.25 2093.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 7612.00 4437.25 3214.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.141 0.000 0.264
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.264
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.141 0.000 0.264
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.264
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.141 0.000 0.264
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.141 0.000 0.264
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1878
Defaulted Fields 500
Fields with Defaults 4912
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
Electricity:Building 89625.89 7014.87 02-JAN-03:15 16912.36 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 76678.43 6519.25 02-JAN-04:15 12694.94 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
Fans:Electricity 9135.62 95.50 24-FEB-01:15 2331.04 27-JUL-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
ElectricityPurchased:Plant 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
Cogeneration:ElectricityPurchased 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
ElectricityNet:Plant 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
Cogeneration:ElectricityNet 156590.17 8039.15 25-FEB-03:15 33810.19 29-JUL-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 64408.95 505.22 24-FEB-01:45 17855.50 27-JUL-17:15
General:Fans:Electricity 9135.62 95.50 24-FEB-01:15 2331.04 27-JUL-17:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 55273.33 112.05 04-FEB-06:30 15524.46 27-JUL-17:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 3681.43 2644.47 02-JAN-03:30 241815.82 04-FEB-07:30
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 1977.39 0.00 01-JAN-00:15 145707.63 14-JAN-09:00
WaterSystems:Gas 1977.39 0.00 01-JAN-00:15 145707.63 14-JAN-09:00
Water Heater:WaterSystems:Gas 1977.39 0.00 01-JAN-00:15 145707.63 14-JAN-09:00
Gas:HVAC 64.32 0.00 01-JAN-00:15 84267.70 04-FEB-07:00
Heating:Gas 64.32 0.00 01-JAN-00:15 84267.70 04-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
Water:Plant 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
MainsWater:Plant 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
PlantLoopHeatingDemand:Plant 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
WaterSystems:PlantLoopHeatingDemand 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1457850.33 15793.28 24-FEB-01:15 376188.07 27-JUL-17:30
EnergyTransfer:Building 549901.80 6875.13 03-FEB-00:45 156621.09 29-JUL-16:30
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 5604.84 0.00 01-JAN-00:15 73411.50 04-FEB-07:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 544296.96 1988.47 04-FEB-06:30 156621.09 29-JUL-16:30
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 101890.50 1988.47 04-FEB-06:30 18318.45 29-JUL-16:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 101890.50 1988.47 04-FEB-06:30 18318.45 29-JUL-16:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 20966.88 0.00 01-JAN-06:00 6283.87 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 217.87 0.00 01-JAN-00:15 3517.02 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 20749.01 0.00 01-JAN-06:00 6283.87 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25557.65 0.00 01-JAN-02:15 7410.88 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 425.11 0.00 01-JAN-00:15 5251.95 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25132.55 0.00 01-JAN-02:15 7410.88 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23317.56 0.00 01-JAN-02:00 9202.52 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 616.66 0.00 01-JAN-00:15 5308.92 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 22700.90 0.00 01-JAN-02:00 9202.52 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 18629.17 0.00 01-JAN-06:00 6269.22 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 327.17 0.00 01-JAN-00:15 3767.59 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 18302.01 0.00 01-JAN-06:00 6269.22 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23208.68 0.00 01-JAN-02:00 7361.45 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 499.72 0.00 01-JAN-00:15 5340.26 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 22708.96 0.00 01-JAN-02:00 7361.45 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 28898.84 0.00 05-JAN-02:30 9318.80 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 196.88 0.00 01-JAN-00:15 3573.85 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 28701.96 0.00 05-JAN-02:30 9318.80 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24560.31 0.00 05-JAN-05:00 6429.00 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 61.41 0.00 01-JAN-00:15 2238.74 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24498.90 0.00 05-JAN-05:00 6429.00 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29016.83 0.00 02-JAN-05:00 7632.82 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 188.94 0.00 01-JAN-00:15 3901.49 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 28827.89 0.00 02-JAN-05:00 7632.82 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 26550.53 0.00 02-JAN-05:00 9223.26 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 311.06 0.00 01-JAN-00:15 3977.85 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 26239.47 0.00 02-JAN-05:00 9223.26 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 22046.95 0.00 05-JAN-05:00 6406.73 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 104.23 0.00 01-JAN-00:15 2436.40 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21942.72 0.00 05-JAN-05:00 6406.73 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 26560.95 0.00 02-JAN-05:00 7611.71 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 230.88 0.00 01-JAN-00:15 4027.87 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 26330.07 0.00 02-JAN-05:00 7611.71 29-JUL-18:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 30453.05 0.00 01-JAN-03:30 9616.14 29-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 460.29 0.00 01-JAN-00:15 5631.51 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 29992.76 0.00 01-JAN-03:30 9616.14 29-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 32034.32 0.00 01-JAN-03:30 9612.32 29-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 402.96 0.00 01-JAN-00:15 5522.39 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 31631.36 0.00 01-JAN-03:30 9612.32 29-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 32034.58 0.00 01-JAN-03:30 11382.01 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 482.87 0.00 01-JAN-00:15 5450.57 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 31551.71 0.00 01-JAN-03:30 11382.01 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 26010.08 0.00 05-JAN-03:00 8543.24 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 286.25 0.00 01-JAN-00:15 4021.19 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 25723.82 0.00 05-JAN-03:00 8543.24 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 27624.03 0.00 05-JAN-03:00 8536.08 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 218.71 0.00 01-JAN-00:15 3856.39 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 27405.33 0.00 05-JAN-03:00 8536.08 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 30540.88 0.00 01-JAN-03:30 11394.82 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 573.84 0.00 01-JAN-00:15 5587.50 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 29967.05 0.00 01-JAN-03:30 11394.82 29-JUL-16:30
EnergyTransfer:Plant 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
WaterSystems:EnergyTransfer 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 80071.24 669.90 19-JUL-02:15 21193.66 15-JAN-08:30
EnergyTransfer:HVAC 827877.28 7276.77 24-FEB-01:15 214981.74 27-JUL-18:15
HeatingCoils:EnergyTransfer 5145.28 0.00 01-JAN-00:15 67414.16 04-FEB-07:00
CoolingCoils:EnergyTransfer 822732.00 2082.42 04-FEB-06:30 214981.74 27-JUL-18:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -8485.21 0.000 0.000 2874.210 2456.001 14468.945 8811.145 0.000 2600.846 74138.241 0.000 -1573.30 0.000 -1885.49 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 217.864 -1727.94 0.000 0.000 2891.426 2456.001 14468.945 3671.009 0.000 2477.803 0.000 0.000 -615.80 0.000 -1679.63 -3138.49
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 425.097 -2092.99 0.000 0.000 2897.612 2456.001 14468.945 9035.582 0.000 2600.123 0.001 0.000 -1460.45 0.000 -1734.91 -3555.32
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 616.646 -1890.48 0.000 0.000 2900.619 2456.001 14468.945 7151.145 0.000 2601.196 0.001 0.000 -1542.87 0.000 -1686.86 -4263.90
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 327.161 -1524.16 0.000 0.000 2895.066 2456.001 14468.945 1923.802 0.000 2478.493 0.000 0.000 -638.27 0.000 -1637.87 -3971.13
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 499.712 -1891.16 0.000 0.000 2900.533 2456.001 14468.945 7319.816 0.000 2600.068 0.000 0.000 -1451.12 0.000 -1701.48 -4383.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 196.876 -2390.24 0.000 0.000 2889.183 2456.001 14468.945 8710.928 0.000 2014.357 1009.119 0.000 -1647.12 0.000 -1396.26 -0.16
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 61.410 -2040.23 0.000 0.000 2883.270 2456.001 14468.945 3620.040 0.000 1892.874 1118.701 0.000 -661.29 0.000 -1340.84 -0.02
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 188.938 -2400.74 0.000 0.000 2889.210 2456.001 14468.945 8907.316 0.000 2014.474 880.332 0.000 -1573.31 0.000 -1403.80 -0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 311.054 -2185.17 0.000 0.000 2891.722 2456.001 14468.945 7042.057 0.000 2014.872 95.021 0.000 -1667.94 0.000 -1372.12 -0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 104.231 -1827.36 0.000 0.000 2885.733 2456.001 14468.945 1886.147 0.000 1893.065 255.278 0.000 -688.48 0.000 -1317.94 -0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 230.875 -2192.73 0.000 0.000 2891.404 2456.001 14468.945 7200.931 0.000 2014.436 19.404 0.000 -1566.54 0.000 -1385.12 -0.01
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 460.281 -2497.75 0.000 0.000 2895.481 2456.001 14468.945 7101.820 0.000 2573.568 3366.590 0.000 -1581.07 0.000 -1748.58 -0.37
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 402.956 -2634.21 0.000 0.000 2893.843 2456.001 14468.945 8823.101 0.000 2573.585 3357.708 0.000 -1576.09 0.000 -1768.45 -0.43
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 482.867 -2627.56 0.000 0.000 2894.325 2456.001 14468.945 8629.593 0.000 2573.648 3441.416 0.000 -1641.07 0.000 -1753.97 -0.08
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 286.250 -2142.24 0.000 0.000 2890.394 2456.001 14468.945 1845.542 0.000 2453.133 3702.172 0.000 -692.45 0.000 -1685.93 -0.07
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 218.703 -2282.27 0.000 0.000 2888.604 2456.001 14468.945 3584.004 0.000 2452.628 3705.593 0.000 -661.16 0.000 -1707.79 -0.04
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 573.827 -2495.59 0.000 0.000 2895.861 2456.001 14468.945 6935.130 0.000 2574.564 3468.322 0.000 -1671.28 0.000 -1734.23 -0.23
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 40095.431 0.000 0.000 0.000 0.000 -2825.77 -37269.66
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5841.093 48151.567 0.000 0.000 0.000 -53992.66 -0.80
Total Facility 0.000 0.000 5604.747 -45328.03 0.000 0.000 52048.498 44208.020 260441.015 112199.109 0.000 88340.259 146709.466 0.000 -22909.59 0.000 -85759.71 -56584.07


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-16:30 0.00 0.00 0.00 -1.5 0.00 0.00 140.45 384.73 2117.60 4636.63 0.00 1546.19 9761.56 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 2685.69 452.22 0.00 1308.47 695.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUL-16:19 0.00 0.00 0.00 -0.6 0.00 0.00 140.36 384.73 2117.60 2099.33 0.00 1545.63 1132.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.8 0.00 0.00 140.46 384.73 2117.60 4684.48 0.00 1546.19 331.12 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 2685.69 477.79 0.00 1308.49 652.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 2685.69 1109.72 0.00 1381.57 1039.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.8 0.00 0.00 140.45 384.73 2117.60 4616.76 0.00 1197.40 863.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 2685.69 454.18 0.00 962.85 1180.79 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 2685.69 1080.81 0.00 1035.77 1684.78 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.8 0.00 0.00 140.45 384.73 2117.60 4663.90 0.00 1197.39 720.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.04 721.37 2685.69 479.53 0.00 962.85 1133.17 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 2685.69 1106.62 0.00 1035.77 1637.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-17:32 0.00 0.00 0.00 -0.8 0.00 0.00 262.79 535.87 2778.60 1263.42 0.00 1422.99 3368.58 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-17:32 0.00 0.00 0.00 -0.8 0.00 0.00 262.76 535.87 2778.60 1231.61 0.00 1422.74 3396.78 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 2117.60 4555.65 0.00 1541.20 2644.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.7 0.00 0.00 427.05 721.37 2685.69 456.31 0.00 1303.53 2952.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.7 0.00 0.00 427.05 721.37 2685.69 431.52 0.00 1303.54 2970.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 2117.60 4599.47 0.00 1541.20 2613.22 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:30 0.00 0.00 0.00 -13.1 0.00 0.00 2527.61 6925.11 38116.86 45648.14 0.00 38059.07 46668.14 0.00 0.00 0.00 -20911.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3516.93 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -830.5 0.00 -2953.0 -2082.9
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5251.80 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2036.1 0.00 -3134.6 -2430.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5308.76 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2044.1 0.00 -3134.6 -2479.6
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3767.49 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -836.5 0.00 -2953.0 -2327.5
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5340.11 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2042.7 0.00 -3134.6 -2512.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 3573.72 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2100.7 0.00 -2282.6 -1540.0
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 2238.66 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -849.2 0.00 -2100.7 -1638.2
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 3901.35 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2083.9 0.00 -2282.6 -1884.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 3977.70 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2094.1 0.00 -2282.6 -1950.5
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 2436.31 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -858.8 0.00 -2100.7 -1826.3
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4027.73 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2091.8 0.00 -2282.6 -2002.9
LIVING_UNIT3_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5631.34 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2077.3 0.00 -3141.7 -2761.8
LIVING_UNIT3_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5522.22 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2067.1 0.00 -3141.7 -2663.0
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5450.39 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2070.3 0.00 -3141.7 -2588.0
LIVING_UNIT2_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 4021.06 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -851.1 0.00 -2959.7 -2559.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 3856.28 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -838.7 0.00 -2959.7 -2407.4
LIVING_UNIT1_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5587.31 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2079.3 0.00 -3141.7 -2715.8
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-FEB-07:00 -2348.4 0.20 73409.15 -0.2 0.00 0.00 9423.30 6925.11 25892.67 0.00 0.00 1165.13 0.00 0.00 -30050.8 0.00 -65363.7 -19052.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 786.884 2.00 2.00 1.00 44.9950 786.884 0.057 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 233.339 2.00 2.00 1.00 44.9950 233.339 0.193 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 273.834 2.00 2.00 1.00 44.9950 273.834 0.164 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.917 2.00 2.00 1.00 44.9950 392.917 0.115 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 239.939 2.00 2.00 1.00 44.9950 239.939 0.188 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 278.319 2.00 2.00 1.00 44.9950 278.319 0.162 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 397.310 2.00 2.00 1.00 44.9950 397.310 0.113 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.946 2.00 2.00 1.00 44.9950 244.946 0.184 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 282.894 2.00 2.00 1.00 44.9950 282.894 0.159 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 399.661 2.00 2.00 1.00 44.9950 399.661 0.113 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 250.943 2.00 2.00 1.00 44.9950 250.943 0.179 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 287.161 2.00 2.00 1.00 44.9950 287.161 0.157 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 478.384 2.00 2.00 1.00 44.9950 478.384 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 324.075 2.00 2.00 1.00 44.9950 324.075 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.365 2.00 2.00 1.00 44.9950 362.365 0.124 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 479.319 2.00 2.00 1.00 44.9950 479.319 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 326.788 2.00 2.00 1.00 44.9950 326.788 0.138 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 363.761 2.00 2.00 1.00 44.9950 363.761 0.124 1.000 44.9950 0.12


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 52.274 2.00 2.00 1.00 44.9950 52.274 1.000 1.000 44.9950 0.86
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 76.267 2.00 2.00 1.00 44.9950 76.267 1.000 1.000 44.9950 0.59
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 76.415 2.00 2.00 1.00 44.9950 76.415 1.000 1.000 44.9950 0.59
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 54.533 2.00 2.00 1.00 44.9950 54.533 1.000 1.000 44.9950 0.83
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 76.312 2.00 2.00 1.00 44.9950 76.312 1.000 1.000 44.9950 0.59
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 55.830 2.00 2.00 1.00 44.9950 55.830 1.000 1.000 44.9950 0.81
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 61.350 2.00 2.00 1.00 44.9950 61.350 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 61.439 2.00 2.00 1.00 44.9950 61.439 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 61.309 2.00 2.00 1.00 44.9950 61.309 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 82.867 2.00 2.00 1.00 44.9950 82.867 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 61.445 2.00 2.00 1.00 44.9950 61.445 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 83.629 2.00 2.00 1.00 44.9950 83.629 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 83.744 2.00 2.00 1.00 44.9950 83.744 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 61.573 2.00 2.00 1.00 44.9950 61.573 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 83.613 2.00 2.00 1.00 44.9950 83.613 1.000 1.000 44.9950 0.54


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   786.884 786.8838 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   233.339 233.3386 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   273.834 273.8343 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   392.917 392.9171 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   239.939 239.9388 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   278.319 278.3186 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   397.310 397.3104 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   244.946 244.9465 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   282.894 282.8941 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   399.661 399.6609 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   250.943 250.9434 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   287.161 287.1610 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   363.761 363.7611 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   362.365 362.3650 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   478.384 478.3835 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   326.788 326.7880 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   324.075 324.0746 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   479.319 479.3190 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 786.88 786.884 786.88 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 233.34 233.339 233.34 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 273.83 273.834 273.83 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.92 392.917 392.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 239.94 239.939 239.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 278.32 278.319 278.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 397.31 397.310 397.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.95 244.946 244.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 282.89 282.894 282.89 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 399.66 399.661 399.66 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 250.94 250.943 250.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 287.16 287.161 287.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 478.38 478.384 478.38 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 324.07 324.075 324.07 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.36 362.365 362.36 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 479.32 479.319 479.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 326.79 326.788 326.79 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 363.76 363.761 363.76 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   52.274 52.274 52.274 44.9950 0.861 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   76.267 76.267 76.267 44.9950 0.590 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   76.415 76.415 76.415 44.9950 0.589 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   54.533 54.533 54.533 44.9950 0.825 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   76.312 76.312 76.312 44.9950 0.590 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   55.830 55.830 55.830 44.9950 0.806 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   61.350 61.350 61.350 44.9950 0.733 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   61.439 61.439 61.439 44.9950 0.732 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   61.309 61.309 61.309 44.9950 0.734 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   83.613 83.613 83.613 44.9950 0.538 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   83.629 83.629 83.629 44.9950 0.538 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   82.867 82.867 82.867 44.9950 0.543 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   61.573 61.573 61.573 44.9950 0.731 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   61.445 61.445 61.445 44.9950 0.732 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   83.744 83.744 83.744 44.9950 0.537 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 52.27 52.274 52.27 52.27 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 76.27 76.267 76.27 76.27 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 76.41 76.415 76.41 76.41 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 54.53 54.533 54.53 54.53 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 76.31 76.312 76.31 76.31 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 55.83 55.830 55.83 55.83 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 61.35 61.350 61.35 61.35 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 61.44 61.439 61.44 61.44 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 61.31 61.309 61.31 61.31 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 82.87 82.867 82.87 82.87 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 61.44 61.445 61.44 61.44 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 83.63 83.629 83.63 83.63 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 83.74 83.744 83.74 83.74 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 61.57 61.573 61.57 61.57 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 83.61 83.613 83.61 83.61 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Sec1.1A-General Information

Data
Weather File ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 64.32 78465.73 0.00 0.00
Space Cooling 55273.33 14991.81 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 9135.62 2274.86 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1977.39 145516.09 0.00 0.00
Receptacle Equipment 76678.43 12123.21 1639.73 17834.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 156590.17   3681.43   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 261812.16 534664.19
Natural Gas 163973.19 368143.35
Additional 0.00 0.00
Total 425785.36 902807.53


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 1.42
Fans-Interior 0.23
Service Water Heating 0.00
Receptacle Equipment 1.97
Miscellaneous 0.07
Subtotal 4.01


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.05
Service Water Heating 1.48
Miscellaneous 1.23
Subtotal 2.76


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.90
Space Heating 0.71
Space Cooling 20.90
Fans-Interior 3.46
Service Water Heating 21.90
Receptacle Equipment 47.16
Miscellaneous 0.97



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 786.88
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 233.34
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 273.83
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 392.92
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 239.94
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 278.32
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 397.31
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 244.95
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 282.89
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 399.66
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 250.94
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 287.16
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 363.76
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 362.36
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 478.38
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 326.79
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 324.07
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 479.32
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 786.88
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 233.34
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 273.83
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 392.92
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 239.94
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 278.32
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 397.31
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 244.95
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 282.89
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 399.66
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 250.94
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 287.16
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 478.38
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 324.07
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.36
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 479.32
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 326.79
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 363.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 786.88 2.02 0.748940
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 233.34 0.777633 0.676083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 273.83 0.897533 0.680195
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 392.92 1.18 0.702636
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 239.94 0.799629 0.676083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 278.32 0.908083 0.681333
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 397.31 1.16 0.711118
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 244.95 0.800880 0.680808
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 282.89 0.899704 0.687818
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 399.66 1.16 0.711467
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 250.94 0.815429 0.682357
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 287.16 0.907476 0.689459
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 478.38 1.37 0.716556
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 324.07 1.01 0.693587
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 362.36 1.11 0.697937
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 479.32 1.37 0.716687
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 326.79 1.01 0.694144
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 363.76 1.11 0.698964
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 786.88 786.88 786.88 3616.94 2.02 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 233.34 233.34 233.34 4010.50 0.777633 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 273.83 273.83 273.83 5307.83 0.897533 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 392.92 392.92 392.92 5315.85 1.18 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 239.94 239.94 239.94 4132.69 0.799629 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 278.32 278.32 278.32 5310.28 0.908083 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 397.31 397.31 397.31 4202.81 1.16 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 244.95 244.95 244.95 3616.94 0.800880 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 282.89 282.89 282.89 4501.29 0.899704 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 399.66 399.66 399.66 4506.08 1.16 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 250.94 250.94 250.94 3616.94 0.815429 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 287.16 287.16 287.16 4499.03 0.907476 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 478.38 478.38 478.38 5664.75 1.37 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 324.07 324.07 324.07 4506.40 1.01 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 362.36 362.36 362.36 5705.92 1.11 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 479.32 479.32 479.32 5712.15 1.37 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 326.79 326.79 326.79 4513.33 1.01 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 363.76 363.76 363.76 5705.06 1.11 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 786.88
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 233.34
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 273.83
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 392.92
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 239.94
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 278.32
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 397.31
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 244.95
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 282.89
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 399.66
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 250.94
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 287.16
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 478.38
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 324.07
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 362.36
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 479.32
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 326.79
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 363.76
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 3616.94
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 4010.50
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 5307.83
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 5315.85
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 4132.69
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 5310.28
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 4202.81
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 3616.94
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 4501.29
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 4506.08
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 3616.94
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 4499.03
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 5664.75
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 4506.40
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 5705.92
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 5712.15
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 4513.33
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 5705.06
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:57

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 744.000 111.729 0.000 0.000 111.729
February 672.000 107.128 0.000 0.000 107.128
March 744.000 122.777 0.000 0.000 122.777
April 720.000 130.881 0.000 0.000 130.881
May 744.000 149.533 0.000 0.000 149.533
June 720.000 151.218 0.000 0.000 151.218
July 744.000 158.208 0.000 0.000 158.208
August 744.000 158.478 0.000 0.000 158.478
September 720.000 151.208 0.000 0.000 151.208
October 744.000 149.778 0.000 0.000 149.778
November 720.000 130.277 0.000 0.000 130.277
December 744.000 117.630 0.000 0.000 117.630
           
Annual Sum or Average 8760.000 1638.846 0.000 0.000 1638.846
Minimum of Months 672.000 107.128 0.000 0.000 107.128
Maximum of Months 744.000 158.478 0.000 0.000 158.478



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 516.190 14.642 63.308 0.806 15.449
February 498.894 15.936 43.875 1.119 17.055
March 614.928 18.787 47.375 0.970 19.757
April 696.675 23.665 0.000 0.000 23.665
May 744.000 32.778 0.000 0.000 32.778
June 720.000 36.293 0.000 0.000 36.293
July 744.000 38.576 0.000 0.000 38.576
August 744.000 38.674 0.000 0.000 38.674
September 720.000 36.983 0.000 0.000 36.983
October 744.000 34.868 0.000 0.000 34.868
November 654.813 25.786 19.500 0.316 26.103
December 558.040 17.416 55.750 1.233 18.649
           
Annual Sum or Average 7955.540 334.405 229.808 4.445 338.850
Minimum of Months 498.894 14.642 0.000 0.000 15.449
Maximum of Months 744.000 38.674 63.308 1.233 38.674



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 472.463 15.966 92.208 1.842 17.808
February 483.468 18.225 58.521 1.794 20.019
March 612.001 22.339 53.750 1.334 23.673
April 695.090 29.307 4.000 0.029 29.336
May 744.000 40.321 0.000 0.000 40.321
June 720.000 44.715 0.000 0.000 44.715
July 744.000 47.561 0.000 0.000 47.561
August 744.000 46.786 0.000 0.000 46.786
September 720.000 44.524 0.000 0.000 44.524
October 744.000 40.966 0.000 0.000 40.966
November 635.179 29.137 24.375 0.603 29.740
December 512.633 18.455 71.375 2.150 20.604
           
Annual Sum or Average 7826.833 398.304 304.229 7.752 406.056
Minimum of Months 472.463 15.966 0.000 0.000 17.808
Maximum of Months 744.000 47.561 92.208 2.150 47.561



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 387.743 11.445 137.333 3.969 15.414
February 439.235 15.726 80.948 3.347 19.073
March 581.687 22.251 83.750 3.112 25.363
April 687.350 30.637 4.250 0.039 30.675
May 744.000 44.264 0.000 0.000 44.264
June 720.000 48.837 0.000 0.000 48.837
July 744.000 52.280 0.000 0.000 52.280
August 744.000 51.300 0.000 0.000 51.300
September 720.000 46.579 0.000 0.000 46.579
October 744.000 40.738 0.000 0.000 40.738
November 610.799 26.795 32.500 1.110 27.905
December 455.195 15.519 98.375 4.111 19.630
           
Annual Sum or Average 7578.010 406.372 437.156 15.688 422.059
Minimum of Months 387.743 11.445 0.000 0.000 15.414
Maximum of Months 744.000 52.280 137.333 4.111 52.280



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 426.886 8.936 94.750 1.467 10.403
February 464.527 11.725 61.500 1.557 13.282
March 585.012 16.094 62.871 1.315 17.409
April 695.687 22.349 0.000 0.000 22.349
May 744.000 32.901 0.000 0.000 32.901
June 720.000 36.871 0.000 0.000 36.871
July 744.000 38.974 0.000 0.000 38.974
August 744.000 38.254 0.000 0.000 38.254
September 720.000 35.191 0.000 0.000 35.191
October 744.000 30.993 0.000 0.000 30.993
November 639.542 20.855 24.250 0.416 21.271
December 489.001 11.867 81.958 1.908 13.775
           
Annual Sum or Average 7716.655 305.009 325.330 6.662 311.671
Minimum of Months 426.886 8.936 0.000 0.000 10.403
Maximum of Months 744.000 38.974 94.750 1.908 38.974



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 404.870 10.411 111.292 2.229 12.640
February 466.204 14.202 71.500 2.147 16.349
March 588.522 19.767 57.217 1.438 21.206
April 695.059 28.161 4.000 0.030 28.190
May 744.000 40.492 0.000 0.000 40.492
June 720.000 45.296 0.000 0.000 45.296
July 744.000 47.993 0.000 0.000 47.993
August 744.000 46.498 0.000 0.000 46.498
September 720.000 42.987 0.000 0.000 42.987
October 744.000 37.483 0.000 0.000 37.483
November 624.667 24.536 27.125 0.659 25.195
December 456.611 13.196 96.500 2.745 15.940
           
Annual Sum or Average 7651.933 371.021 367.633 9.248 380.270
Minimum of Months 404.870 10.411 0.000 0.000 12.640
Maximum of Months 744.000 47.993 111.292 2.745 47.993



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 538.638 21.807 58.333 1.197 23.004
February 523.925 24.241 39.500 1.556 25.796
March 631.182 29.986 40.300 1.276 31.262
April 703.958 37.256 0.000 0.000 37.256
May 744.000 48.629 0.000 0.000 48.629
June 720.000 52.422 0.000 0.000 52.422
July 744.000 56.549 0.000 0.000 56.549
August 744.000 55.986 0.000 0.000 55.986
September 720.000 52.803 0.000 0.000 52.803
October 744.000 49.705 0.000 0.000 49.705
November 665.000 36.780 16.000 0.405 37.185
December 580.697 26.069 50.833 1.821 27.890
           
Annual Sum or Average 8059.400 492.233 204.967 6.254 498.487
Minimum of Months 523.925 21.807 0.000 0.000 23.004
Maximum of Months 744.000 56.549 58.333 1.821 56.549



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 589.757 18.923 11.750 0.174 19.097
February 575.417 19.798 19.250 0.439 20.237
March 647.164 23.121 20.500 0.326 23.447
April 709.122 28.147 0.000 0.000 28.147
May 744.000 36.356 0.000 0.000 36.356
June 720.000 39.560 0.000 0.000 39.560
July 744.000 42.213 0.000 0.000 42.213
August 744.000 41.946 0.000 0.000 41.946
September 720.000 40.367 0.000 0.000 40.367
October 744.000 38.780 0.000 0.000 38.780
November 681.563 29.965 6.750 0.052 30.017
December 637.285 21.956 29.232 0.450 22.407
           
Annual Sum or Average 8256.307 381.132 87.482 1.442 382.574
Minimum of Months 575.417 18.923 0.000 0.000 19.097
Maximum of Months 744.000 42.213 29.232 0.450 42.213



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 553.551 19.986 51.750 0.847 20.834
February 535.740 21.953 36.000 1.064 23.017
March 645.789 26.859 27.250 0.624 27.483
April 707.135 34.033 0.000 0.000 34.033
May 744.000 44.294 0.000 0.000 44.294
June 720.000 48.418 0.000 0.000 48.418
July 744.000 51.712 0.000 0.000 51.712
August 744.000 50.551 0.000 0.000 50.551
September 720.000 48.357 0.000 0.000 48.357
October 744.000 45.303 0.000 0.000 45.303
November 667.094 33.443 15.750 0.282 33.725
December 584.411 22.737 49.125 1.323 24.061
           
Annual Sum or Average 8109.721 447.648 179.875 4.141 451.789
Minimum of Months 535.740 19.986 0.000 0.000 20.834
Maximum of Months 744.000 51.712 51.750 1.323 51.712



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 481.870 15.203 88.650 2.173 17.376
February 493.035 19.545 52.208 2.116 21.661
March 614.292 27.105 55.857 1.746 28.851
April 703.369 35.960 0.000 0.000 35.960
May 744.000 48.738 0.000 0.000 48.738
June 720.000 52.985 0.000 0.000 52.985
July 744.000 56.928 0.000 0.000 56.928
August 744.000 55.543 0.000 0.000 55.543
September 720.000 50.964 0.000 0.000 50.964
October 744.000 45.703 0.000 0.000 45.703
November 651.250 31.518 21.000 0.568 32.087
December 535.131 19.868 72.333 2.730 22.599
           
Annual Sum or Average 7894.947 460.060 290.049 9.333 469.394
Minimum of Months 481.870 15.203 0.000 0.000 17.376
Maximum of Months 744.000 56.928 88.650 2.730 56.928



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 517.140 12.826 29.375 0.398 13.224
February 540.365 15.537 29.058 0.688 16.225
March 624.489 20.535 27.292 0.476 21.011
April 708.781 27.074 0.000 0.000 27.074
May 744.000 36.658 0.000 0.000 36.658
June 720.000 40.303 0.000 0.000 40.303
July 744.000 42.805 0.000 0.000 42.805
August 744.000 41.762 0.000 0.000 41.762
September 720.000 38.862 0.000 0.000 38.862
October 744.000 35.227 0.000 0.000 35.227
November 671.708 25.249 9.250 0.096 25.345
December 586.200 16.251 50.807 0.845 17.096
           
Annual Sum or Average 8064.683 353.090 145.782 2.502 355.592
Minimum of Months 517.140 12.826 0.000 0.000 13.224
Maximum of Months 744.000 42.805 50.807 0.845 42.805



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 498.866 14.060 62.517 1.092 15.152
February 517.363 17.938 43.625 1.309 19.247
March 628.439 24.302 28.875 0.683 24.985
April 707.135 33.041 0.000 0.000 33.041
May 744.000 44.552 0.000 0.000 44.552
June 720.000 49.069 0.000 0.000 49.069
July 744.000 52.233 0.000 0.000 52.233
August 744.000 50.382 0.000 0.000 50.382
September 720.000 46.977 0.000 0.000 46.977
October 744.000 41.998 0.000 0.000 41.998
November 659.875 28.945 17.500 0.320 29.265
December 537.100 17.232 67.000 1.728 18.960
           
Annual Sum or Average 7964.779 420.729 219.517 5.133 425.862
Minimum of Months 498.866 14.060 0.000 0.000 15.152
Maximum of Months 744.000 52.233 67.000 1.728 52.233



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 484.228 22.213 97.708 3.348 25.561
February 488.077 25.518 57.625 3.025 28.544
March 615.733 32.516 66.250 2.830 35.346
April 696.085 41.831 2.250 0.013 41.844
May 744.000 56.669 0.000 0.000 56.669
June 720.000 61.809 0.000 0.000 61.809
July 744.000 66.690 0.000 0.000 66.690
August 744.000 65.217 0.000 0.000 65.217
September 720.000 61.154 0.000 0.000 61.154
October 744.000 56.045 0.000 0.000 56.045
November 643.621 40.114 24.625 0.988 41.103
December 536.229 26.985 71.125 3.659 30.644
           
Annual Sum or Average 7879.974 556.761 319.583 13.863 570.625
Minimum of Months 484.228 22.213 0.000 0.000 25.561
Maximum of Months 744.000 66.690 97.708 3.659 66.690



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 538.407 19.779 59.250 1.041 20.820
February 524.253 21.502 40.250 1.338 22.841
March 628.667 26.218 39.907 1.123 27.341
April 704.033 33.285 0.000 0.000 33.285
May 744.000 44.909 0.000 0.000 44.909
June 720.000 49.425 0.000 0.000 49.425
July 744.000 52.858 0.000 0.000 52.858
August 744.000 51.731 0.000 0.000 51.731
September 720.000 49.309 0.000 0.000 49.309
October 744.000 45.881 0.000 0.000 45.881
November 667.250 33.988 17.000 0.348 34.336
December 581.070 23.404 51.625 1.576 24.980
           
Annual Sum or Average 8059.680 452.288 208.032 5.426 457.714
Minimum of Months 524.253 19.779 0.000 0.000 20.820
Maximum of Months 744.000 52.858 59.250 1.576 52.858



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 505.575 20.826 84.958 2.158 22.984
February 501.644 23.646 50.083 2.047 25.694
March 628.944 29.758 47.012 1.431 31.189
April 702.826 39.063 2.375 0.012 39.075
May 744.000 52.745 0.000 0.000 52.745
June 720.000 58.180 0.000 0.000 58.180
July 744.000 62.266 0.000 0.000 62.266
August 744.000 60.254 0.000 0.000 60.254
September 720.000 57.220 0.000 0.000 57.220
October 744.000 52.266 0.000 0.000 52.266
November 650.208 37.347 21.875 0.667 38.014
December 543.026 24.184 66.083 2.602 26.785
           
Annual Sum or Average 7948.224 517.756 272.387 8.917 526.673
Minimum of Months 501.644 20.826 0.000 0.000 22.984
Maximum of Months 744.000 62.266 84.958 2.602 62.266



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 443.731 17.305 117.375 4.214 21.518
February 468.803 22.285 66.500 3.492 25.776
March 607.233 31.053 71.732 3.066 34.119
April 695.960 41.427 2.583 0.014 41.440
May 744.000 56.783 0.000 0.000 56.783
June 720.000 62.083 0.000 0.000 62.083
July 744.000 66.919 0.000 0.000 66.919
August 744.000 65.111 0.000 0.000 65.111
September 720.000 60.387 0.000 0.000 60.387
October 744.000 53.479 0.000 0.000 53.479
November 633.799 36.052 27.875 1.121 37.173
December 501.341 22.118 85.696 4.475 26.593
           
Annual Sum or Average 7766.868 535.003 371.762 16.380 551.383
Minimum of Months 443.731 17.305 0.000 0.000 21.518
Maximum of Months 744.000 66.919 117.375 4.475 66.919



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 491.099 14.922 79.375 1.577 16.500
February 502.319 18.382 48.875 1.697 20.079
March 618.817 24.827 46.537 1.278 26.105
April 703.875 32.951 0.000 0.000 32.951
May 744.000 45.100 0.000 0.000 45.100
June 720.000 49.776 0.000 0.000 49.776
July 744.000 53.175 0.000 0.000 53.175
August 744.000 51.723 0.000 0.000 51.723
September 720.000 48.663 0.000 0.000 48.663
October 744.000 43.488 0.000 0.000 43.488
November 657.979 30.098 19.083 0.426 30.524
December 542.984 18.643 67.125 2.168 20.811
           
Annual Sum or Average 7933.072 431.749 260.996 7.146 438.895
Minimum of Months 491.099 14.922 0.000 0.000 16.500
Maximum of Months 744.000 53.175 79.375 2.168 53.175



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 464.648 16.154 97.250 2.514 18.667
February 490.152 20.698 58.125 2.348 23.046
March 621.411 28.449 50.146 1.494 29.943
April 702.826 38.799 2.250 0.012 38.811
May 744.000 52.960 0.000 0.000 52.960
June 720.000 58.539 0.000 0.000 58.539
July 744.000 62.601 0.000 0.000 62.601
August 744.000 60.310 0.000 0.000 60.310
September 720.000 56.687 0.000 0.000 56.687
October 744.000 50.110 0.000 0.000 50.110
November 643.521 33.713 23.281 0.719 34.431
December 509.188 19.640 81.625 3.137 22.777
           
Annual Sum or Average 7847.746 498.661 312.678 10.223 508.884
Minimum of Months 464.648 16.154 0.000 0.000 18.667
Maximum of Months 744.000 62.601 97.250 3.137 62.601



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 49.39 0.00
February 0.00 75.88 0.00
March 0.00 59.41 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 20.00 0.00
December 0.00 75.54 0.00
       
Annual Sum or Average 0.00 23.12 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 75.88 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 127.24 0.00
February 0.00 137.16 0.00
March 0.00 92.13 0.00
April 0.00 2.07 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 43.06 0.00
December 0.00 148.48 0.00
       
Annual Sum or Average 0.00 45.47 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 148.48 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 191.37 0.00
February 0.00 178.62 0.00
March 0.00 150.02 0.00
April 0.00 1.93 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 55.32 0.00
December 0.00 198.17 0.00
       
Annual Sum or Average 0.00 64.23 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 198.17 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 90.02 0.00
February 0.00 105.80 0.00
March 0.00 80.69 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 26.38 0.00
December 0.00 117.07 0.00
       
Annual Sum or Average 0.00 34.73 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 117.07 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 151.56 0.00
February 0.00 161.63 0.00
March 0.00 97.79 0.00
April 0.00 2.07 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 46.31 0.00
December 0.00 186.61 0.00
       
Annual Sum or Average 0.00 53.40 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 186.61 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 45.10 0.00
February 0.00 64.92 0.00
March 0.00 48.09 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 15.76 0.00
December 0.00 68.66 0.00
       
Annual Sum or Average 0.00 20.02 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 68.66 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9.18 0.00
February 0.00 25.57 0.00
March 0.00 17.16 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 2.83 0.00
December 0.00 23.70 0.00
       
Annual Sum or Average 0.00 6.44 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 25.57 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 48.04 0.00
February 0.00 66.80 0.00
March 0.00 35.36 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 16.54 0.00
December 0.00 75.02 0.00
       
Annual Sum or Average 0.00 19.94 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 75.02 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 87.31 0.00
February 0.00 94.11 0.00
March 0.00 70.15 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 23.58 0.00
December 0.00 109.70 0.00
       
Annual Sum or Average 0.00 31.85 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 109.70 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 20.44 0.00
February 0.00 39.12 0.00
March 0.00 24.43 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 5.08 0.00
December 0.00 43.41 0.00
       
Annual Sum or Average 0.00 10.92 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 43.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 60.98 0.00
February 0.00 80.93 0.00
March 0.00 38.13 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 18.48 0.00
December 0.00 96.47 0.00
       
Annual Sum or Average 0.00 24.34 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 96.47 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 141.25 0.00
February 0.00 141.34 0.00
March 0.00 119.41 0.00
April 0.00 0.56 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 43.09 0.00
December 0.00 154.39 0.00
       
Annual Sum or Average 0.00 49.68 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 154.39 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 51.58 0.00
February 0.00 73.42 0.00
March 0.00 55.66 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 17.81 0.00
December 0.00 78.07 0.00
       
Annual Sum or Average 0.00 22.83 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 78.07 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 121.11 0.00
February 0.00 127.18 0.00
March 0.00 80.28 0.00
April 0.00 0.69 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 38.66 0.00
December 0.00 145.98 0.00
       
Annual Sum or Average 0.00 42.49 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 145.98 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 178.93 0.00
February 0.00 164.16 0.00
March 0.00 130.20 0.00
April 0.00 0.60 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 49.17 0.00
December 0.00 190.03 0.00
       
Annual Sum or Average 0.00 59.08 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 190.03 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 77.63 0.00
February 0.00 92.44 0.00
March 0.00 62.88 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 21.67 0.00
December 0.00 106.72 0.00
       
Annual Sum or Average 0.00 29.87 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 106.72 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 140.47 0.00
February 0.00 145.28 0.00
March 0.00 83.51 0.00
April 0.00 0.67 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 41.51 0.00
December 0.00 175.31 0.00
       
Annual Sum or Average 0.00 48.52 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 175.31 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.98
February 0.00 0.00 1.04
March 0.00 0.00 1.07
April 0.00 0.00 1.18
May 0.00 0.00 1.31
June 0.00 0.00 1.36
July 0.00 0.00 1.38
August 0.00 0.00 1.38
September 0.00 0.00 1.36
October 0.00 0.00 1.31
November 0.00 0.00 1.18
December 0.00 0.00 1.03
       
Annual Sum or Average 0.00 0.00 1.22
Minimum of Months 0.00 0.00 0.98
Maximum of Months 0.00 0.00 1.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.20
March 0.00 0.00 0.21
April 0.00 0.00 0.28
May 0.00 0.00 0.38
June 0.00 0.00 0.44
July 0.00 0.00 0.45
August 0.00 0.00 0.45
September 0.00 0.00 0.45
October 0.00 0.00 0.41
November 0.00 0.00 0.31
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.34
May 0.00 0.00 0.46
June 0.00 0.00 0.53
July 0.00 0.00 0.54
August 0.00 0.00 0.54
September 0.00 0.00 0.53
October 0.00 0.00 0.47
November 0.00 0.00 0.34
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.45
June 0.00 0.00 0.52
July 0.00 0.00 0.53
August 0.00 0.00 0.53
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.28
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.15
March 0.00 0.00 0.18
April 0.00 0.00 0.26
May 0.00 0.00 0.38
June 0.00 0.00 0.45
July 0.00 0.00 0.45
August 0.00 0.00 0.45
September 0.00 0.00 0.42
October 0.00 0.00 0.36
November 0.00 0.00 0.25
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.46
June 0.00 0.00 0.53
July 0.00 0.00 0.55
August 0.00 0.00 0.53
September 0.00 0.00 0.51
October 0.00 0.00 0.42
November 0.00 0.00 0.29
December 0.00 0.00 0.15
       
Annual Sum or Average 0.00 0.00 0.36
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.55



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.26
March 0.00 0.00 0.29
April 0.00 0.00 0.37
May 0.00 0.00 0.48
June 0.00 0.00 0.53
July 0.00 0.00 0.56
August 0.00 0.00 0.55
September 0.00 0.00 0.54
October 0.00 0.00 0.49
November 0.00 0.00 0.37
December 0.00 0.00 0.26
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.24
March 0.00 0.00 0.26
April 0.00 0.00 0.32
May 0.00 0.00 0.41
June 0.00 0.00 0.46
July 0.00 0.00 0.48
August 0.00 0.00 0.48
September 0.00 0.00 0.47
October 0.00 0.00 0.44
November 0.00 0.00 0.35
December 0.00 0.00 0.25
       
Annual Sum or Average 0.00 0.00 0.36
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.26
March 0.00 0.00 0.29
April 0.00 0.00 0.38
May 0.00 0.00 0.48
June 0.00 0.00 0.55
July 0.00 0.00 0.57
August 0.00 0.00 0.56
September 0.00 0.00 0.55
October 0.00 0.00 0.50
November 0.00 0.00 0.38
December 0.00 0.00 0.25
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.15
February 0.00 0.00 0.21
March 0.00 0.00 0.26
April 0.00 0.00 0.36
May 0.00 0.00 0.48
June 0.00 0.00 0.54
July 0.00 0.00 0.56
August 0.00 0.00 0.55
September 0.00 0.00 0.52
October 0.00 0.00 0.45
November 0.00 0.00 0.32
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.15
Maximum of Months 0.00 0.00 0.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.19
March 0.00 0.00 0.23
April 0.00 0.00 0.31
May 0.00 0.00 0.41
June 0.00 0.00 0.47
July 0.00 0.00 0.48
August 0.00 0.00 0.47
September 0.00 0.00 0.45
October 0.00 0.00 0.39
November 0.00 0.00 0.29
December 0.00 0.00 0.18
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.15
February 0.00 0.00 0.21
March 0.00 0.00 0.26
April 0.00 0.00 0.36
May 0.00 0.00 0.48
June 0.00 0.00 0.55
July 0.00 0.00 0.57
August 0.00 0.00 0.55
September 0.00 0.00 0.53
October 0.00 0.00 0.45
November 0.00 0.00 0.32
December 0.00 0.00 0.19
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.15
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.27
March 0.00 0.00 0.31
April 0.00 0.00 0.41
May 0.00 0.00 0.55
June 0.00 0.00 0.62
July 0.00 0.00 0.64
August 0.00 0.00 0.63
September 0.00 0.00 0.61
October 0.00 0.00 0.54
November 0.00 0.00 0.40
December 0.00 0.00 0.26
       
Annual Sum or Average 0.00 0.00 0.46
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.64



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.25
March 0.00 0.00 0.28
April 0.00 0.00 0.36
May 0.00 0.00 0.48
June 0.00 0.00 0.55
July 0.00 0.00 0.57
August 0.00 0.00 0.56
September 0.00 0.00 0.55
October 0.00 0.00 0.49
November 0.00 0.00 0.38
December 0.00 0.00 0.25
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.27
March 0.00 0.00 0.31
April 0.00 0.00 0.42
May 0.00 0.00 0.55
June 0.00 0.00 0.64
July 0.00 0.00 0.66
August 0.00 0.00 0.64
September 0.00 0.00 0.62
October 0.00 0.00 0.55
November 0.00 0.00 0.41
December 0.00 0.00 0.25
       
Annual Sum or Average 0.00 0.00 0.46
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 0.66



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.23
March 0.00 0.00 0.30
April 0.00 0.00 0.41
May 0.00 0.00 0.55
June 0.00 0.00 0.62
July 0.00 0.00 0.65
August 0.00 0.00 0.63
September 0.00 0.00 0.60
October 0.00 0.00 0.51
November 0.00 0.00 0.36
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.44
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.65



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.21
March 0.00 0.00 0.26
April 0.00 0.00 0.35
May 0.00 0.00 0.48
June 0.00 0.00 0.55
July 0.00 0.00 0.57
August 0.00 0.00 0.55
September 0.00 0.00 0.54
October 0.00 0.00 0.46
November 0.00 0.00 0.33
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.16
February 0.00 0.00 0.23
March 0.00 0.00 0.29
April 0.00 0.00 0.41
May 0.00 0.00 0.55
June 0.00 0.00 0.64
July 0.00 0.00 0.66
August 0.00 0.00 0.64
September 0.00 0.00 0.62
October 0.00 0.00 0.52
November 0.00 0.00 0.36
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.44
Minimum of Months 0.00 0.00 0.16
Maximum of Months 0.00 0.00 0.66



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:57

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1112.15 828.03
February 0.00 0.00 1102.58 741.46
March 0.00 0.00 1065.31 793.15
April 0.00 0.00 1014.69 731.10
May 0.00 0.00 954.45 710.62
June 0.00 0.00 909.81 655.53
July 0.00 0.00 892.67 664.62
August 0.00 0.00 901.52 671.21
September 0.00 0.00 941.61 678.44
October 0.00 0.00 994.26 740.25
November 0.00 0.00 1051.56 757.66
December 0.00 0.00 1096.43 816.33
         
Annual Sum or Average 0.00 0.00 1002.53 8788.38
Minimum of Months 0.00 0.00 892.67 655.53
Maximum of Months 0.00 0.00 1112.15 828.03