Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27

Tabular Output Report in Format: HTML

Building: MF+CZ1A+USA_FL_Miami.Intl.AP.722020+hp+crawlspace+IECC_2012

Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2019-02-14 08:27:59


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 630416.09 16.16 29.17
Net Site Energy 630416.09 16.16 29.17
Total Source Energy 1996527.77 51.19 92.39
Net Source Energy 1996527.77 51.19 92.39


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 2512.37 0.00 0.00 0.00 0.00 0.00
Cooling 155490.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24141.75 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 95428.27 0.00 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 630416.09 0.00 0.00 0.00 0.00 377715.79
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 2512.37 0.00 0.00 0.00 0.00 0.00
Cooling General 155490.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 24141.75 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 95428.27 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 12.84 0.00 0.00 0.00 0.00 17.48
Other 13.88 0.00 0.00 0.00 0.00 0.00
Total 29.17 0.00 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 7.12 0.00 0.00 0.00 0.00 9.68
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 16.16 0.00 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 630416.094 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 630416.094 100.00
     
Total On-Site and Utility Electric Sources 630416.094 100.00
Total Electricity End Uses 630416.094 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 4142.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
RunPeriod ANNUAL
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [ft] 36.09
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:00 - - - - 01-JAN-08:45
Heating 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 43.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.57 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6.32 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 116.37 0.00 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 233.72 0.00 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 43.37 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.38 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6.32 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 116.37 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 7956.67 0.00 0.00 0.00 0.00
Cooling 492437.99 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 76456.92 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 302221.33 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1996527.77 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.37 0.00 0.00 0.00 0.00
Cooling 22.79 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.54 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 13.99 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 92.39 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.37 0.00 0.00 0.00 0.00
Cooling 22.79 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.54 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 13.99 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 92.39 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 47.66 0.00 47.66 Wetbulb [F] 748.07 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 91.76 12.06 77.54 Wetbulb [F] 885.87 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.219 0.882              
North Total or Average           531.68 0.501 0.219 0.882              
Non-North Total or Average           1595.05 0.501 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15530.03 10989.04 4541.00 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8004.47 5411.68 2592.78 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10277.09 6948.17 3328.92 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13491.04 9360.02 4131.03 0.69 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8261.31 5585.33 2675.98 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10455.54 7068.82 3386.73 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13212.10 9278.21 3933.89 0.70 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8441.51 5707.16 2734.35 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10302.53 7015.13 3287.40 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13240.61 9305.95 3934.66 0.70 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8674.98 5865.01 2809.97 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10414.12 7103.21 3310.90 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15744.93 11162.17 4582.75 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11337.52 7719.82 3617.71 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12590.28 8660.43 3929.85 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15756.46 11171.44 4585.02 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11387.40 7766.83 3620.58 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12588.90 8668.31 3920.60 0.69 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.2 3.43 11.71 12.28 11.76
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.46 11.80 12.39 11.91
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.7 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.44 11.74 12.32 11.82
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.49 11.89 12.48 12.05
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.44 11.74 12.32 11.81
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.50 11.93 12.52 12.10
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.48 11.88 12.48 12.04
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.43 11.70 12.27 11.75
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.49 11.89 12.48 12.05
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.47 11.84 12.43 11.97
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.43 11.70 12.27 11.74
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.48 11.88 12.48 12.04
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.47 11.84 12.43 11.96
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 16094.7 8884.2 8.06 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8263.4 4547.0 7.96 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10609.6 5838.0 8.12 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 13957.9 7694.1 8.03 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8528.6 4692.9 8.00 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10793.8 5939.4 8.13 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 13683.5 7549.2 8.01 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 8714.6 4795.3 8.03 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 10642.2 5858.8 8.11 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 13714.0 7566.4 8.01 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 8955.6 4927.9 8.05 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 10759.0 5923.8 8.11 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 16320.1 9009.8 8.07 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11711.3 6447.3 8.13 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 13016.5 7170.9 8.00 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 16332.1 9016.5 8.07 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11764.5 6477.4 8.12 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 13016.2 7171.2 8.00 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   15530.03 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   3799.31 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   8004.47 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   4537.68 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10277.09 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   5721.67 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   13491.04 3.69
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5723.02 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   8261.31 3.69
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   4536.40 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10455.54 3.69
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5717.51 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   13212.10 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4901.80 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   8441.51 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   3711.44 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   10302.53 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4900.23 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   13240.61 3.69
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4902.53 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   8674.98 3.69
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   3709.45 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   10414.12 3.69
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4895.56 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   15744.93 3.69
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   6114.07 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   11337.52 3.69
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   4919.06 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   12590.28 3.69
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   6111.04 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   15756.46 3.69
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   6116.35 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   11387.40 3.69
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   4919.32 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   12588.90 3.69
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   6109.41 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 438.27 165.31 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 200.15 75.50 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 256.98 96.93 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 361.73 136.44 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 206.58 77.92 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 261.44 98.61 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 365.65 137.92 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 211.08 79.62 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 262.69 99.09 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 367.22 138.51 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 216.92 81.82 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 266.77 100.63 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.48 168.41 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 289.08 109.04 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 329.96 124.46 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.92 168.58 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 291.68 110.02 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 330.82 124.78 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10282.01 10282.01 8.56 438.268 438.268 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00946 89.47 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4695.96 4695.96 3.91 200.153 200.153 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01075 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6029.19 6029.19 5.02 256.981 256.981 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01021 88.08 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8486.37 8486.37 7.07 361.726 361.726 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00974 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4846.62 4846.62 4.04 206.576 206.576 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01070 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6133.88 6133.88 5.11 261.443 261.443 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01018 88.08 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8578.58 8578.58 7.15 365.645 365.645 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00943 89.17 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4952.45 4952.45 4.13 211.082 211.082 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01024 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6163.35 6163.35 5.13 262.694 262.694 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00979 88.53 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8615.61 8615.61 7.18 367.222 367.222 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00943 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5089.41 5089.41 4.24 216.920 216.920 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01020 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6259.08 6259.08 5.21 266.774 266.774 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00977 88.53 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7761.50 7761.50 6.46 330.823 330.823 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00987 88.41 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7741.18 7741.18 6.45 329.958 329.958 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00987 88.87 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10474.82 10474.82 8.72 446.483 446.483 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6843.31 6843.31 5.70 291.682 291.682 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01006 87.06 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6782.24 6782.24 5.65 289.079 289.079 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.01006 87.51 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10485.11 10485.11 8.73 446.922 446.922 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2653.95 2653.95 2.21 48.368 48.368 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00773 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3403.23 3403.23 2.83 62.023 62.023 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4604.73 4604.73 3.84 83.920 83.920 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4606.11 4606.11 3.84 83.945 83.945 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3401.94 3401.94 2.83 62.000 62.000 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4600.52 4600.52 3.83 83.843 83.843 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3772.73 3772.73 3.14 68.758 68.758 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2564.76 2564.76 2.14 46.743 46.743 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3771.14 3771.14 3.14 68.729 68.729 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3773.47 3773.47 3.14 68.771 68.771 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2562.75 2562.75 2.13 46.706 46.706 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3766.40 3766.40 3.14 68.642 68.642 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4998.21 4998.21 4.16 91.091 91.091 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 4999.86 4999.86 4.16 91.121 91.121 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5002.93 5002.93 4.17 91.177 91.177 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3790.52 3790.52 3.16 69.081 69.081 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3790.26 3790.26 3.16 69.077 69.077 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5005.25 5005.25 4.17 91.219 91.219 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 438.27 438.27 48.37 48.37
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.15 200.15 62.02 62.02
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.98 256.98 83.92 83.92
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.73 361.73 83.95 83.95
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.58 206.58 62.00 62.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.44 261.44 83.84 83.84
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.65 365.65 68.76 68.76
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.08 211.08 46.74 46.74
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.69 262.69 68.73 68.73
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.22 367.22 68.77 68.77
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.92 216.92 46.71 46.71
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.77 266.77 68.64 68.64
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.48 446.48 91.18 91.18
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.08 289.08 69.08 69.08
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.96 329.96 91.12 91.12
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.92 446.92 91.22 91.22
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.68 291.68 69.08 69.08
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.82 330.82 91.09 91.09


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6328.00 1335.00 364.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7195.25 4435.00 3589.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7250.00 3834.75 2955.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7163.50 4671.75 3573.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7088.25 5096.25 3990.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7133.00 4204.00 3123.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7404.00 2790.25 2047.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7254.75 2358.75 1740.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7308.75 2320.25 1606.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7254.75 3112.25 2186.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7142.25 2770.75 1921.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7197.50 2586.25 1702.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7292.00 3060.75 2143.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7397.25 2873.00 2072.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 7449.25 3376.00 2534.75
LIVING_UNIT2_BACKROW_TOPFLOOR 7249.50 3322.50 2428.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 7367.50 3046.00 2298.75
LIVING_UNIT1_BACKROW_TOPFLOOR 7343.25 3576.00 2623.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 7564.75 5369.50 4142.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 1.25 0.00 1.25
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 1.25 0.00 1.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.264
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.141 0.000 0.264
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.264
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.264
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.141 0.000 0.264
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1842
Defaulted Fields 518
Fields with Defaults 4732
Autosized Fields 324
Autosizable Fields 450
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Electricity:Plant 27948.63 0.00 01-JAN-00:15 35534.65 22-JAN-08:45
WaterSystems:Electricity 27948.63 0.00 01-JAN-00:15 35534.65 22-JAN-08:45
Water Heater:WaterSystems:Electricity 27948.63 0.00 01-JAN-00:15 35534.65 22-JAN-08:45
Fans:Electricity 7070.53 0.00 24-JAN-03:00 1990.42 29-JUL-16:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
ElectricityPurchased:Plant 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
Cogeneration:ElectricityPurchased 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
ElectricityNet:Plant 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
Cogeneration:ElectricityNet 184633.58 6809.05 27-FEB-04:00 68449.62 29-JUL-19:00
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 53345.70 0.00 24-JAN-03:00 16113.81 29-JUL-16:15
General:Fans:Electricity 7070.53 0.00 24-JAN-03:00 1990.42 29-JUL-16:30
Cooling:Electricity 45539.36 0.00 09-JAN-00:45 14125.03 29-JUL-16:15
Heating:Electricity 735.81 0.00 01-JAN-00:15 10687.50 04-FEB-07:00
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
Water:Plant 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
MainsWater:Plant 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 02-JAN-02:15 0.18 01-JAN-08:45


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
PlantLoopHeatingDemand:Plant 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1187074.36 1015.35 12-DEC-02:15 334414.44 27-JUL-17:15
EnergyTransfer:Building 427358.48 0.00 24-JAN-03:00 139397.23 29-JUL-16:30
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 7777.79 0.00 01-JAN-00:15 83335.03 04-FEB-07:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 419580.69 0.00 09-JAN-00:45 139397.23 29-JUL-16:30
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 36115.30 0.00 09-JAN-00:45 10551.06 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 98.78 0.00 01-JAN-00:15 3667.89 04-FEB-06:45
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 36016.52 0.00 09-JAN-00:45 10551.06 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17695.32 0.00 01-JAN-03:00 5332.95 29-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 322.52 0.00 01-JAN-00:15 3996.87 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17372.80 0.00 01-JAN-03:00 5332.95 29-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22406.22 0.00 01-JAN-01:30 6916.46 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 543.70 0.00 01-JAN-00:15 5597.73 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21862.52 0.00 01-JAN-01:30 6916.46 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20339.59 0.00 01-JAN-01:15 8637.03 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 798.93 0.00 01-JAN-00:15 5633.63 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19540.66 0.00 01-JAN-01:15 8637.03 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15554.80 0.00 01-JAN-02:45 5475.85 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 478.07 0.00 01-JAN-00:15 4101.00 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15076.73 0.00 01-JAN-02:45 5475.85 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20218.82 0.00 01-JAN-01:15 6786.14 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 669.06 0.00 01-JAN-00:15 5651.00 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19549.76 0.00 01-JAN-01:15 6786.14 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25430.70 0.00 01-JAN-04:00 8744.66 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 307.57 0.00 01-JAN-00:15 4189.23 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25123.13 0.00 01-JAN-04:00 8744.66 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20889.28 0.00 05-JAN-03:30 5637.25 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 110.85 0.00 01-JAN-00:15 2636.56 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20778.43 0.00 05-JAN-03:30 5637.25 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25516.41 0.00 01-JAN-04:00 7081.52 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 268.63 0.00 01-JAN-00:15 4264.70 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25247.78 0.00 01-JAN-04:00 7081.52 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23187.79 0.00 01-JAN-03:45 8649.31 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 439.35 0.00 01-JAN-00:15 4318.00 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22748.44 0.00 01-JAN-03:45 8649.31 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18527.30 0.00 05-JAN-03:30 5614.12 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 194.94 0.00 01-JAN-00:15 2792.11 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18332.36 0.00 05-JAN-03:30 5614.12 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23181.31 0.00 01-JAN-03:45 6959.54 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 345.68 0.00 01-JAN-00:15 4346.15 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22835.63 0.00 01-JAN-03:45 6959.54 29-JUL-16:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 27128.95 0.00 01-JAN-02:30 9006.43 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 606.56 0.00 01-JAN-00:15 5944.79 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26522.39 0.00 01-JAN-02:30 9006.43 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28630.62 0.00 01-JAN-02:45 9004.81 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 515.80 0.00 01-JAN-00:15 5872.65 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28114.82 0.00 01-JAN-02:45 9004.81 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28661.26 0.00 01-JAN-02:45 10806.99 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 612.66 0.00 01-JAN-00:15 5818.97 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28048.60 0.00 01-JAN-02:45 10806.99 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22551.98 0.00 01-JAN-05:30 7723.30 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 416.38 0.00 01-JAN-00:15 4382.89 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22135.60 0.00 01-JAN-05:30 7723.30 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 24075.28 0.00 01-JAN-05:45 7716.42 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 312.83 0.00 01-JAN-00:15 4241.65 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 23762.45 0.00 01-JAN-05:45 7716.42 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 27247.55 0.00 01-JAN-02:45 10819.73 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 735.49 0.00 01-JAN-00:15 5920.03 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26512.07 0.00 01-JAN-02:45 10819.73 29-JUL-16:30
EnergyTransfer:Plant 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
WaterSystems:EnergyTransfer 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 80070.61 669.88 19-JUL-02:15 21194.82 15-JAN-09:00
EnergyTransfer:HVAC 679645.28 0.00 24-JAN-03:00 190611.76 27-JUL-17:15
CoolingCoils:EnergyTransfer 672132.69 0.00 09-JAN-00:45 190611.76 27-JUL-17:15
HeatingCoils:EnergyTransfer 7512.59 0.00 01-JAN-00:15 79529.01 04-FEB-07:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 98.775 -2999.38 0.000 0.000 2883.232 2456.001 10405.511 8836.406 0.000 2600.320 12082.396 0.000 -1528.33 0.000 -1817.71 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 322.518 -1446.77 0.000 0.000 2895.622 2456.001 10405.511 3682.178 0.000 2477.487 0.000 0.000 -602.00 0.000 -1649.54 -2614.94
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 543.686 -1820.66 0.000 0.000 2902.217 2456.001 10405.511 9054.970 0.000 2599.959 0.001 0.000 -1427.10 0.000 -1704.13 -2968.55
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 798.913 -1627.30 0.000 0.000 2906.223 2456.001 10405.511 7176.219 0.000 2603.083 0.000 0.000 -1504.37 0.000 -1647.99 -3652.97
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 478.058 -1255.56 0.000 0.000 2901.478 2456.001 10405.511 1937.102 0.000 2480.016 0.000 0.000 -619.32 0.000 -1592.59 -3369.41
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 669.042 -1628.07 0.000 0.000 2906.783 2456.001 10405.511 7344.013 0.000 2599.923 0.000 0.000 -1409.10 0.000 -1657.25 -3765.06
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 307.570 -2092.19 0.000 0.000 2892.497 2456.001 10405.511 8733.747 0.000 2014.355 1304.920 0.000 -1614.36 0.000 -1377.12 -0.01
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 110.851 -1730.39 0.000 0.000 2886.310 2456.001 10405.511 3631.123 0.000 1892.766 1367.384 0.000 -647.52 0.000 -1323.88 -0.21
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 268.622 -2102.59 0.000 0.000 2892.687 2456.001 10405.511 8927.688 0.000 2014.397 1208.606 0.000 -1539.91 0.000 -1385.70 -0.07
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 439.345 -1894.44 0.000 0.000 2896.149 2456.001 10405.511 7067.408 0.000 2015.857 444.145 0.000 -1628.93 0.000 -1346.98 -0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 194.937 -1526.69 0.000 0.000 2890.691 2456.001 10405.511 1899.107 0.000 1893.740 552.188 0.000 -669.60 0.000 -1290.04 -0.01
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 345.671 -1901.71 0.000 0.000 2896.442 2456.001 10405.511 7225.869 0.000 2014.366 373.312 0.000 -1524.56 0.000 -1356.79 -0.06
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 606.550 -2208.74 0.000 0.000 2899.877 2456.001 10405.511 7124.174 0.000 2573.605 3716.229 0.000 -1543.07 0.000 -1716.31 -0.14
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 515.788 -2341.35 0.000 0.000 2897.408 2456.001 10405.511 8842.627 0.000 2573.524 3711.362 0.000 -1543.80 0.000 -1743.46 -0.42
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 612.653 -2335.82 0.000 0.000 2897.794 2456.001 10405.511 8649.706 0.000 2573.914 3791.417 0.000 -1609.59 0.000 -1728.85 -0.05
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 416.373 -1843.41 0.000 0.000 2894.579 2456.001 10405.511 1856.986 0.000 2454.211 3982.555 0.000 -675.53 0.000 -1654.94 -0.04
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 312.828 -1978.89 0.000 0.000 2891.781 2456.001 10405.511 3594.321 0.000 2452.757 3981.793 0.000 -647.77 0.000 -1684.67 -0.01
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 735.474 -2207.86 0.000 0.000 2899.978 2456.001 10405.511 6957.624 0.000 2575.909 3821.030 0.000 -1635.11 0.000 -1704.35 -0.00
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 40291.654 0.000 0.000 0.000 0.000 -2785.54 -37506.12
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5874.608 48059.223 0.000 0.000 0.000 -53933.83 -0.87
Total Facility 0.000 0.000 7777.655 -34941.83 0.000 0.000 52131.747 44208.020 187299.191 112541.268 0.000 88576.449 88396.564 0.000 -22369.96 0.000 -85101.67 -53878.94


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.77 4632.33 0.00 1546.20 2489.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-17:32 0.00 0.00 0.00 -0.4 0.00 0.00 262.97 535.87 1676.47 533.49 0.00 1356.04 976.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.77 2214.26 0.00 1590.86 1222.60 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.46 384.73 1363.77 4680.16 0.00 1546.21 524.22 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 1735.60 478.93 0.00 1308.42 810.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.77 2255.08 0.00 1590.85 1051.51 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.77 4612.86 0.00 1197.41 1047.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 1735.60 455.28 0.00 962.85 1338.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.77 2209.30 0.00 1230.55 1752.94 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.77 4659.90 0.00 1197.41 904.91 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.04 721.37 1735.60 480.64 0.00 962.85 1289.53 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.45 384.73 1363.77 2253.01 0.00 1230.54 1587.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.8 0.00 0.00 263.35 535.87 1676.47 1535.20 0.00 1443.49 3561.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.8 0.00 0.00 263.35 535.87 1676.47 1496.11 0.00 1443.43 3598.83 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.77 4550.96 0.00 1541.21 2828.12 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1735.60 457.02 0.00 1303.54 3081.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1735.60 432.25 0.00 1303.54 3099.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.77 4594.81 0.00 1541.21 2797.02 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:23 0.00 0.00 0.00 -11.6 0.00 0.00 2527.34 6925.11 24547.80 45592.41 0.00 38051.82 43808.96 0.00 0.00 0.00 -22010.3 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 04-FEB-06:45 0.00 0.00 3667.75 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2022.3 0.00 -3122.9 -515.6
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3996.79 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -826.0 0.00 -2953.0 -2210.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5597.61 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2033.0 0.00 -3134.6 -2423.0
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5633.51 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2041.7 0.00 -3134.6 -2450.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 4100.91 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -834.7 0.00 -2953.0 -2306.2
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5650.88 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2041.0 0.00 -3134.6 -2468.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4189.10 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2082.2 0.00 -2282.6 -1817.3
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 2636.48 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -844.9 0.00 -2100.7 -1683.8
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4264.57 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2078.8 0.00 -2282.6 -1896.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4317.87 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2090.1 0.00 -2282.6 -1938.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-FEB-07:15 0.00 0.00 2792.06 0.00 0.00 0.00 464.78 343.51 1219.22 0.00 0.00 0.00 0.00 0.00 -790.5 0.00 -2056.6 -1972.5
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4346.02 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2088.8 0.00 -2282.6 -1967.6
LIVING_UNIT3_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5944.66 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2075.3 0.00 -3141.7 -2720.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5872.52 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2063.5 0.00 -3141.7 -2660.3
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5818.84 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2065.8 0.00 -3141.7 -2604.3
LIVING_UNIT2_BACKROW_TOPFLOOR 04-FEB-07:15 0.00 0.00 4382.87 0.00 0.00 0.00 464.78 343.51 1219.22 0.00 0.00 0.00 0.00 0.00 -783.6 0.00 -2911.5 -2715.2
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 4241.56 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -836.0 0.00 -2959.7 -2438.9
LIVING_UNIT1_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5919.90 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2076.4 0.00 -3141.7 -2694.8
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-FEB-07:00 0.00 0.00 83333.08 0.00 0.00 0.00 9473.51 6925.11 19474.66 0.00 0.00 1178.47 0.00 0.00 -29818.4 0.00 -64967.9 -25598.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 438.268 2.00 2.00 1.00 44.9950 438.268 0.103 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.153 2.00 2.00 1.00 44.9950 200.153 0.225 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.981 2.00 2.00 1.00 44.9950 256.981 0.175 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.726 2.00 2.00 1.00 44.9950 361.726 0.124 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.576 2.00 2.00 1.00 44.9950 206.576 0.218 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.443 2.00 2.00 1.00 44.9950 261.443 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.645 2.00 2.00 1.00 44.9950 365.645 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.082 2.00 2.00 1.00 44.9950 211.082 0.213 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.694 2.00 2.00 1.00 44.9950 262.694 0.171 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.222 2.00 2.00 1.00 44.9950 367.222 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.920 2.00 2.00 1.00 44.9950 216.920 0.207 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.774 2.00 2.00 1.00 44.9950 266.774 0.169 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.483 2.00 2.00 1.00 44.9950 446.483 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.079 2.00 2.00 1.00 44.9950 289.079 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.958 2.00 2.00 1.00 44.9950 329.958 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.922 2.00 2.00 1.00 44.9950 446.922 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.682 2.00 2.00 1.00 44.9950 291.682 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.823 2.00 2.00 1.00 44.9950 330.823 0.136 1.000 44.9950 0.14


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 48.368 2.00 2.00 1.00 44.9950 48.368 1.000 1.000 44.9950 0.93
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 62.023 2.00 2.00 1.00 44.9950 62.023 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 83.920 2.00 2.00 1.00 44.9950 83.920 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 83.945 2.00 2.00 1.00 44.9950 83.945 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 62.000 2.00 2.00 1.00 44.9950 62.000 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 83.843 2.00 2.00 1.00 44.9950 83.843 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 68.758 2.00 2.00 1.00 44.9950 68.758 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.743 2.00 2.00 1.00 44.9950 46.743 1.000 1.000 44.9950 0.96
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.729 2.00 2.00 1.00 44.9950 68.729 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.771 2.00 2.00 1.00 44.9950 68.771 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.706 2.00 2.00 1.00 44.9950 46.706 1.000 1.000 44.9950 0.96
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.642 2.00 2.00 1.00 44.9950 68.642 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 91.177 2.00 2.00 1.00 44.9950 91.177 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 69.077 2.00 2.00 1.00 44.9950 69.077 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.121 2.00 2.00 1.00 44.9950 91.121 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.219 2.00 2.00 1.00 44.9950 91.219 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.081 2.00 2.00 1.00 44.9950 69.081 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.091 2.00 2.00 1.00 44.9950 91.091 1.000 1.000 44.9950 0.49


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   438.268 438.2681 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   200.153 200.1534 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   256.981 256.9807 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   361.726 361.7257 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   206.576 206.5757 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   261.443 261.4431 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   365.645 365.6453 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   211.082 211.0817 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   262.694 262.6941 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   367.222 367.2221 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   216.920 216.9197 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   266.774 266.7742 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   330.823 330.8229 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   329.958 329.9584 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   446.483 446.4834 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   291.682 291.6818 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   289.079 289.0789 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   446.922 446.9217 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 438.27 438.268 438.27 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.15 200.153 200.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.98 256.981 256.98 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.73 361.726 361.73 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.58 206.576 206.58 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.44 261.443 261.44 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.65 365.645 365.65 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.08 211.082 211.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.69 262.694 262.69 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.22 367.222 367.22 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.92 216.920 216.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.77 266.774 266.77 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.48 446.483 446.48 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.08 289.079 289.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.96 329.958 329.96 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.92 446.922 446.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.68 291.682 291.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.82 330.823 330.82 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   48.368 48.368 48.368 44.9950 0.930 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   62.023 62.023 62.023 44.9950 0.725 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   83.920 83.920 83.920 44.9950 0.536 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   83.945 83.945 83.945 44.9950 0.536 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   62.000 62.000 62.000 44.9950 0.726 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   83.843 83.843 83.843 44.9950 0.537 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   68.758 68.758 68.758 44.9950 0.654 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   46.743 46.743 46.743 44.9950 0.963 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   68.729 68.729 68.729 44.9950 0.655 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   68.771 68.771 68.771 44.9950 0.654 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   46.706 46.706 46.706 44.9950 0.963 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   68.642 68.642 68.642 44.9950 0.656 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   91.091 91.091 91.091 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   91.121 91.121 91.121 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   91.177 91.177 91.177 44.9950 0.493 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   69.081 69.081 69.081 44.9950 0.651 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   69.077 69.077 69.077 44.9950 0.651 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   91.219 91.219 91.219 44.9950 0.493 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 48.37 48.368 48.37 48.37 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 62.02 62.023 62.02 62.02 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 83.92 83.920 83.92 83.92 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 83.95 83.945 83.95 83.95 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 62.00 62.000 62.00 62.00 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 83.84 83.843 83.84 83.84 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 68.76 68.758 68.76 68.76 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.74 46.743 46.74 46.74 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.73 68.729 68.73 68.73 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.77 68.771 68.77 68.77 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.71 46.706 46.71 46.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.64 68.642 68.64 68.64 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 91.18 91.177 91.18 91.18 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 69.08 69.077 69.08 69.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.12 91.121 91.12 91.12 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.22 91.219 91.22 91.22 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.08 69.081 69.08 69.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.09 91.091 91.09 91.09 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Sec1.1A-General Information

Data
Weather File ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1.25
Number of hours not met 1.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 735.81 0.00 0.00 0.00 0.00 0.00
Space Cooling 45539.36 12701.66 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 7070.53 1849.72 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 27948.63 34082.08 0.00 0.00 0.00 0.00
Receptacle Equipment 87836.46 15395.85 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 184633.58   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 630416.09
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299910.33 630416.09


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.02
Space Cooling 1.17
Fans-Interior 0.18
Service Water Heating 0.72
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 4.73


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.01
Space Heating 0.40
Space Cooling 24.66
Fans-Interior 3.83
Service Water Heating 15.14
Receptacle Equipment 47.57
Miscellaneous 1.38



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 438.27
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 200.15
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 256.98
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 361.73
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 206.58
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 261.44
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 365.65
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 211.08
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 262.69
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 367.22
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 216.92
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 266.77
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 330.82
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 329.96
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 446.48
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 291.68
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 289.08
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 446.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 438.27
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.15
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.98
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.73
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.58
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.44
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.65
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.08
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.69
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.22
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.92
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.77
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.48
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.08
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.96
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.92
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.68
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 438.27 1.29 0.707599
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 200.15 0.667039 0.676083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 256.98 0.856424 0.676083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 361.73 1.12 0.693795
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 206.58 0.688442 0.676083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 261.44 0.871295 0.676083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 365.65 1.10 0.702251
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 211.08 0.703459 0.676083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 262.69 0.858544 0.680913
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 367.22 1.10 0.702834
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 216.92 0.722915 0.676083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 266.77 0.867843 0.682076
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 446.48 1.31 0.708938
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 289.08 0.944793 0.680909
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 329.96 1.05 0.687866
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 446.92 1.31 0.709007
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 291.68 0.948950 0.682054
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 330.82 1.05 0.688567
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Supplemental Heating Coil Nominal Capacity [Btu/h] Fraction of Supply Air Flow That Goes Through the Controlling Zone
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR 438.27 438.27 438.27 15530.03 1.29 3799.31 1.00
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR 200.15 200.15 200.15 8004.47 0.667039 4537.68 1.00
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR 256.98 256.98 256.98 10277.09 0.856424 5721.67 1.00
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR 361.73 361.73 361.73 13491.04 1.12 5723.02 1.00
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR 206.58 206.58 206.58 8261.31 0.688442 4536.40 1.00
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR 261.44 261.44 261.44 10455.54 0.871295 5717.51 1.00
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR 365.65 365.65 365.65 13212.10 1.10 4901.80 1.00
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR 211.08 211.08 211.08 8441.51 0.703459 3711.44 1.00
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR 262.69 262.69 262.69 10302.53 0.858544 4900.23 1.00
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR 367.22 367.22 367.22 13240.61 1.10 4902.53 1.00
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR 216.92 216.92 216.92 8674.98 0.722915 3709.45 1.00
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR 266.77 266.77 266.77 10414.12 0.867843 4895.56 1.00
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR 446.48 446.48 446.48 15744.93 1.31 6114.07 1.00
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR 289.08 289.08 289.08 11337.52 0.944793 4919.06 1.00
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR 329.96 329.96 329.96 12590.28 1.05 6111.04 1.00
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR 446.92 446.92 446.92 15756.46 1.31 6116.35 1.00
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR 291.68 291.68 291.68 11387.40 0.948950 4919.32 1.00
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR 330.82 330.82 330.82 12588.90 1.05 6109.41 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 438.27
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 200.15
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 256.98
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 361.73
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 206.58
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 261.44
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 365.65
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 211.08
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 262.69
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 367.22
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 216.92
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 266.77
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 446.48
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 289.08
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 329.96
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 446.92
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 291.68
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 330.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Heating Capacity [Btu/h]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 438.27 15530.03
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 200.15 8004.47
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 256.98 10277.09
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 361.73 13491.04
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 206.58 8261.31
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 261.44 10455.54
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 365.65 13212.10
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 211.08 8441.51
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 262.69 10302.53
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 367.22 13240.61
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 216.92 8674.98
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 266.77 10414.12
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 446.48 15744.93
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 289.08 11337.52
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 329.96 12590.28
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 446.92 15756.46
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 291.68 11387.40
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 330.82 12588.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 3799.31
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 4537.68
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 5721.67
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 5723.02
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 4536.40
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 5717.51
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 4901.80
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 3711.44
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 4900.23
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 4902.53
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 3709.45
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 4895.56
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 6114.07
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 4919.06
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 6111.04
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR 6116.35
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR 4919.32
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR 6109.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 618.314 29.211 12.000 0.114 29.325
February 592.894 31.660 23.500 0.383 32.043
March 657.936 38.497 23.000 0.265 38.762
April 714.558 46.606 0.000 0.000 46.606
May 744.000 59.589 0.000 0.000 59.589
June 720.000 62.979 0.000 0.000 62.979
July 744.000 66.912 0.000 0.000 66.912
August 744.000 66.989 0.000 0.000 66.989
September 720.000 63.236 0.000 0.000 63.236
October 744.000 60.190 0.000 0.000 60.190
November 684.958 46.201 8.600 0.042 46.243
December 653.263 34.251 31.375 0.337 34.588
           
Annual Sum or Average 8337.924 606.322 98.475 1.142 607.464
Minimum of Months 592.894 29.211 0.000 0.000 29.325
Maximum of Months 744.000 66.989 31.375 0.383 66.989



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 453.321 11.376 87.250 0.647 12.023
February 465.603 12.839 53.250 0.733 13.572
March 587.604 15.176 61.625 0.665 15.840
April 690.121 19.738 0.500 0.000 19.738
May 744.000 28.657 0.000 0.000 28.657
June 720.000 32.326 0.000 0.000 32.326
July 744.000 34.422 0.000 0.000 34.422
August 744.000 34.552 0.000 0.000 34.552
September 720.000 33.017 0.000 0.000 33.017
October 744.000 30.838 0.000 0.000 30.838
November 629.002 22.151 24.375 0.225 22.375
December 502.355 14.024 64.167 0.814 14.838
           
Annual Sum or Average 7744.006 289.115 291.167 3.083 292.198
Minimum of Months 453.321 11.376 0.000 0.000 12.023
Maximum of Months 744.000 34.552 87.250 0.814 34.552



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 427.984 12.801 114.750 1.265 14.067
February 451.915 15.109 70.292 1.181 16.290
March 578.050 18.683 63.000 0.885 19.568
April 677.486 25.290 6.375 0.028 25.318
May 742.250 36.023 0.000 0.000 36.023
June 720.000 40.536 0.000 0.000 40.536
July 744.000 43.174 0.000 0.000 43.174
August 744.000 42.417 0.000 0.000 42.417
September 720.000 40.352 0.000 0.000 40.352
October 744.000 36.747 0.000 0.000 36.747
November 612.137 25.429 29.875 0.399 25.828
December 462.207 15.144 83.625 1.396 16.540
           
Annual Sum or Average 7624.029 351.707 367.917 5.154 356.861
Minimum of Months 427.984 12.801 0.000 0.000 14.067
Maximum of Months 744.000 43.174 114.750 1.396 43.174



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 332.206 8.181 172.844 2.085 10.266
February 398.629 12.198 101.979 1.685 13.883
March 546.267 17.974 93.500 1.524 19.498
April 668.146 25.669 7.344 0.030 25.699
May 742.250 38.652 0.000 0.000 38.652
June 720.000 43.223 0.000 0.000 43.223
July 744.000 46.377 0.000 0.000 46.377
August 744.000 45.444 0.000 0.000 45.444
September 720.000 40.982 0.000 0.000 40.982
October 744.000 35.184 0.000 0.000 35.184
November 582.138 22.198 38.500 0.560 22.758
December 396.377 11.897 121.604 2.074 13.971
           
Annual Sum or Average 7338.013 347.979 535.771 7.958 355.937
Minimum of Months 332.206 8.181 0.000 0.000 10.266
Maximum of Months 744.000 46.377 172.844 2.085 46.377



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 332.129 6.067 141.042 1.088 7.155
February 423.146 8.663 76.646 0.985 9.648
March 551.042 12.596 84.092 0.864 13.460
April 688.946 18.357 1.750 0.001 18.359
May 744.000 28.759 0.000 0.000 28.759
June 720.000 32.892 0.000 0.000 32.892
July 744.000 34.807 0.000 0.000 34.807
August 744.000 34.103 0.000 0.000 34.103
September 720.000 31.176 0.000 0.000 31.176
October 744.000 26.852 0.000 0.000 26.852
November 606.824 17.138 31.167 0.285 17.423
December 410.249 8.753 107.333 1.237 9.989
           
Annual Sum or Average 7428.338 260.163 442.029 4.460 264.623
Minimum of Months 332.129 6.067 0.000 0.000 7.155
Maximum of Months 744.000 34.807 141.042 1.237 34.807



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 335.455 7.524 150.875 1.608 9.132
February 428.034 10.990 89.875 1.407 12.397
March 553.163 16.109 75.450 0.986 17.095
April 677.111 23.988 6.500 0.029 24.017
May 742.250 36.029 0.000 0.000 36.029
June 720.000 40.941 0.000 0.000 40.941
July 744.000 43.416 0.000 0.000 43.416
August 744.000 41.932 0.000 0.000 41.932
September 720.000 38.610 0.000 0.000 38.610
October 744.000 33.019 0.000 0.000 33.019
November 600.646 20.626 33.500 0.439 21.065
December 381.956 10.117 116.333 1.815 11.933
           
Annual Sum or Average 7390.614 323.301 472.533 6.285 329.586
Minimum of Months 335.455 7.524 0.000 0.000 9.132
Maximum of Months 744.000 43.416 150.875 1.815 43.416



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 489.095 17.461 79.936 0.716 18.176
February 494.801 20.036 47.821 0.772 20.808
March 615.308 25.154 55.250 0.670 25.824
April 696.675 31.960 0.000 0.000 31.960
May 744.000 42.731 0.000 0.000 42.731
June 720.000 46.494 0.000 0.000 46.494
July 744.000 50.321 0.000 0.000 50.321
August 744.000 49.797 0.000 0.000 49.797
September 720.000 46.892 0.000 0.000 46.892
October 744.000 43.842 0.000 0.000 43.842
November 645.846 31.646 21.333 0.223 31.869
December 539.479 21.470 61.208 0.906 22.376
           
Annual Sum or Average 7897.204 427.804 265.549 3.286 431.090
Minimum of Months 489.095 17.461 0.000 0.000 18.176
Maximum of Months 744.000 50.321 79.936 0.906 50.321



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 546.602 14.934 34.354 0.169 15.103
February 531.037 16.036 29.795 0.305 16.341
March 631.300 18.950 27.350 0.236 19.186
April 704.183 23.704 0.000 0.000 23.704
May 744.000 31.577 0.000 0.000 31.577
June 720.000 34.823 0.000 0.000 34.823
July 744.000 37.256 0.000 0.000 37.256
August 744.000 37.008 0.000 0.000 37.008
September 720.000 35.642 0.000 0.000 35.642
October 744.000 34.049 0.000 0.000 34.049
November 672.063 25.674 12.125 0.060 25.733
December 587.210 17.824 42.600 0.330 18.153
           
Annual Sum or Average 8088.395 327.478 146.224 1.098 328.576
Minimum of Months 531.037 14.934 0.000 0.000 15.103
Maximum of Months 744.000 37.256 42.600 0.330 37.256



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 507.843 16.163 73.833 0.605 16.768
February 507.325 18.303 42.500 0.655 18.957
March 629.864 22.643 37.500 0.411 23.054
April 703.222 29.536 0.500 0.000 29.536
May 744.000 39.417 0.000 0.000 39.417
June 720.000 43.574 0.000 0.000 43.574
July 744.000 46.630 0.000 0.000 46.630
August 744.000 45.485 0.000 0.000 45.485
September 720.000 43.531 0.000 0.000 43.531
October 744.000 40.473 0.000 0.000 40.473
November 650.242 29.133 19.750 0.192 29.325
December 543.824 18.732 59.375 0.802 19.534
           
Annual Sum or Average 7958.319 393.618 233.458 2.665 396.283
Minimum of Months 507.325 16.163 0.000 0.000 16.768
Maximum of Months 744.000 46.630 73.833 0.802 46.630



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 409.617 11.157 116.517 1.152 12.309
February 457.660 15.494 64.000 1.000 16.494
March 595.792 22.382 69.875 0.852 23.234
April 695.881 30.655 0.000 0.000 30.655
May 744.000 42.850 0.000 0.000 42.850
June 720.000 47.067 0.000 0.000 47.067
July 744.000 50.712 0.000 0.000 50.712
August 744.000 49.367 0.000 0.000 49.367
September 720.000 45.068 0.000 0.000 45.068
October 744.000 39.839 0.000 0.000 39.839
November 627.633 26.436 26.500 0.292 26.728
December 477.908 15.495 88.542 1.304 16.799
           
Annual Sum or Average 7680.491 396.522 365.433 4.600 401.123
Minimum of Months 409.617 11.157 0.000 0.000 12.309
Maximum of Months 744.000 50.712 116.517 1.304 50.712



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 444.799 9.037 73.913 0.395 9.432
February 492.372 11.779 48.833 0.455 12.234
March 598.058 16.337 43.025 0.335 16.672
April 703.842 22.455 0.000 0.000 22.455
May 744.000 31.678 0.000 0.000 31.678
June 720.000 35.350 0.000 0.000 35.350
July 744.000 37.619 0.000 0.000 37.619
August 744.000 36.596 0.000 0.000 36.596
September 720.000 33.917 0.000 0.000 33.917
October 744.000 30.256 0.000 0.000 30.256
November 655.688 20.745 16.750 0.090 20.835
December 509.038 12.146 72.500 0.592 12.738
           
Annual Sum or Average 7819.797 297.916 255.021 1.866 299.782
Minimum of Months 444.799 9.037 0.000 0.000 9.432
Maximum of Months 744.000 37.619 73.913 0.592 37.619



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 426.005 10.393 92.208 0.808 11.201
February 486.834 14.221 58.350 0.813 15.034
March 602.576 20.084 40.750 0.464 20.548
April 703.194 28.440 0.500 0.000 28.440
May 744.000 39.579 0.000 0.000 39.579
June 720.000 44.127 0.000 0.000 44.127
July 744.000 47.046 0.000 0.000 47.046
August 744.000 45.207 0.000 0.000 45.207
September 720.000 42.037 0.000 0.000 42.037
October 744.000 37.020 0.000 0.000 37.020
November 639.688 24.502 21.875 0.219 24.721
December 471.266 13.335 87.604 1.108 14.443
           
Annual Sum or Average 7745.562 365.989 301.288 3.413 369.403
Minimum of Months 426.005 10.393 0.000 0.000 11.201
Maximum of Months 744.000 47.046 92.208 1.108 47.046



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 439.824 18.103 114.542 1.629 19.733
February 465.590 21.405 70.250 1.427 22.832
March 597.400 27.706 74.821 1.330 29.036
April 690.896 36.443 3.875 0.015 36.458
May 744.000 50.624 0.000 0.000 50.624
June 720.000 55.733 0.000 0.000 55.733
July 744.000 60.302 0.000 0.000 60.302
August 744.000 58.882 0.000 0.000 58.882
September 720.000 55.103 0.000 0.000 55.103
October 744.000 50.058 0.000 0.000 50.058
November 619.980 34.998 29.350 0.471 35.468
December 495.867 22.559 81.500 1.694 24.253
           
Annual Sum or Average 7725.558 491.917 374.338 6.565 498.482
Minimum of Months 439.824 18.103 0.000 0.000 19.733
Maximum of Months 744.000 60.302 114.542 1.694 60.302



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 493.752 15.424 79.400 0.666 16.089
February 491.579 17.299 47.500 0.725 18.023
March 609.175 21.334 54.500 0.630 21.964
April 697.688 27.852 0.000 0.000 27.852
May 744.000 38.790 0.000 0.000 38.790
June 720.000 43.234 0.000 0.000 43.234
July 744.000 46.351 0.000 0.000 46.351
August 744.000 45.271 0.000 0.000 45.271
September 720.000 43.139 0.000 0.000 43.139
October 744.000 39.795 0.000 0.000 39.795
November 648.738 28.738 20.750 0.207 28.944
December 543.976 18.785 61.767 0.840 19.625
           
Annual Sum or Average 7900.909 386.010 263.917 3.067 389.077
Minimum of Months 491.579 15.424 0.000 0.000 16.089
Maximum of Months 744.000 46.351 79.400 0.840 46.351



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 460.054 16.804 99.000 1.286 18.090
February 481.423 19.655 60.250 1.176 20.831
March 610.515 25.062 57.208 0.849 25.911
April 697.474 33.837 3.500 0.014 33.851
May 744.000 46.881 0.000 0.000 46.881
June 720.000 52.255 0.000 0.000 52.255
July 744.000 56.018 0.000 0.000 56.018
August 744.000 54.062 0.000 0.000 54.062
September 720.000 51.323 0.000 0.000 51.323
October 744.000 46.457 0.000 0.000 46.457
November 628.404 32.398 25.125 0.382 32.779
December 500.868 19.910 76.225 1.454 21.364
           
Annual Sum or Average 7794.737 454.661 321.308 5.161 459.822
Minimum of Months 460.054 16.804 0.000 0.000 18.090
Maximum of Months 744.000 56.018 99.000 1.454 56.018



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 390.998 13.349 143.208 2.055 15.404
February 442.187 18.235 81.500 1.646 19.881
March 589.542 26.268 80.750 1.436 27.704
April 690.692 36.016 4.094 0.016 36.032
May 744.000 50.720 0.000 0.000 50.720
June 720.000 55.988 0.000 0.000 55.988
July 744.000 60.509 0.000 0.000 60.509
August 744.000 58.754 0.000 0.000 58.754
September 720.000 54.313 0.000 0.000 54.313
October 744.000 47.459 0.000 0.000 47.459
November 607.616 30.952 33.375 0.538 31.490
December 450.132 17.853 103.854 2.094 19.947
           
Annual Sum or Average 7587.167 470.417 446.781 7.785 478.202
Minimum of Months 390.998 13.349 0.000 0.000 15.404
Maximum of Months 744.000 60.509 143.208 2.094 60.509



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 424.226 10.821 105.982 0.982 11.803
February 466.235 14.296 60.150 0.910 15.206
March 595.842 20.003 60.857 0.717 20.720
April 697.619 27.552 0.000 0.000 27.552
May 744.000 39.038 0.000 0.000 39.038
June 720.000 43.651 0.000 0.000 43.651
July 744.000 46.737 0.000 0.000 46.737
August 744.000 45.334 0.000 0.000 45.334
September 720.000 42.566 0.000 0.000 42.566
October 744.000 37.475 0.000 0.000 37.475
November 634.453 24.936 25.167 0.249 25.185
December 487.562 14.227 85.500 1.168 15.395
           
Annual Sum or Average 7721.938 366.637 337.656 4.027 370.664
Minimum of Months 424.226 10.821 0.000 0.000 11.803
Maximum of Months 744.000 46.737 105.982 1.168 46.737



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 402.616 12.284 118.750 1.547 13.831
February 465.589 16.700 74.092 1.352 18.052
March 597.409 23.731 61.000 0.905 24.637
April 697.599 33.517 3.500 0.014 33.531
May 744.000 47.029 0.000 0.000 47.029
June 720.000 52.541 0.000 0.000 52.541
July 744.000 56.275 0.000 0.000 56.275
August 744.000 54.042 0.000 0.000 54.042
September 720.000 50.722 0.000 0.000 50.722
October 744.000 44.234 0.000 0.000 44.234
November 622.113 28.730 28.875 0.420 29.150
December 451.537 15.513 100.326 1.804 17.317
           
Annual Sum or Average 7652.862 435.318 386.544 6.043 441.360
Minimum of Months 402.616 12.284 0.000 0.000 13.831
Maximum of Months 744.000 56.275 118.750 1.804 56.275



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 13.07 0.00 0.00
February 46.30 0.00 0.00
March 29.54 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 5.08 0.00 0.00
December 38.09 0.00 0.00
       
Annual Sum or Average 10.82 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 46.30 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 90.11 0.00 0.00
February 107.89 0.00 0.00
March 90.30 0.00 0.00
April 0.03 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 32.54 0.00 0.00
December 109.68 0.00 0.00
       
Annual Sum or Average 35.59 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 109.68 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 178.21 0.00 0.00
February 175.25 0.00 0.00
March 120.17 0.00 0.00
April 4.37 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 58.00 0.00 0.00
December 189.61 0.00 0.00
       
Annual Sum or Average 60.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 189.61 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 278.65 0.00 0.00
February 237.80 0.00 0.00
March 197.50 0.00 0.00
April 4.37 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 76.97 0.00 0.00
December 266.91 0.00 0.00
       
Annual Sum or Average 88.04 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 278.65 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 155.53 0.00 0.00
February 148.77 0.00 0.00
March 119.85 0.00 0.00
April 0.20 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 41.95 0.00 0.00
December 171.11 0.00 0.00
       
Annual Sum or Average 52.80 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 171.11 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 227.82 0.00 0.00
February 211.76 0.00 0.00
March 134.50 0.00 0.00
April 4.41 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 64.07 0.00 0.00
December 249.94 0.00 0.00
       
Annual Sum or Average 73.87 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 249.94 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 89.37 0.00 0.00
February 100.70 0.00 0.00
March 80.80 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 28.74 0.00 0.00
December 109.10 0.00 0.00
       
Annual Sum or Average 33.81 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 109.10 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 22.74 0.00 0.00
February 42.92 0.00 0.00
March 30.71 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 8.38 0.00 0.00
December 43.52 0.00 0.00
       
Annual Sum or Average 12.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 43.52 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 81.90 0.00 0.00
February 92.12 0.00 0.00
March 52.66 0.00 0.00
April 0.05 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 26.77 0.00 0.00
December 104.87 0.00 0.00
       
Annual Sum or Average 29.60 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 104.87 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 146.91 0.00 0.00
February 133.09 0.00 0.00
March 104.74 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 38.13 0.00 0.00
December 160.25 0.00 0.00
       
Annual Sum or Average 48.33 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 160.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 55.30 0.00 0.00
February 66.37 0.00 0.00
March 44.83 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 12.90 0.00 0.00
December 80.71 0.00 0.00
       
Annual Sum or Average 21.51 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 80.71 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 109.29 0.00 0.00
February 115.50 0.00 0.00
March 59.42 0.00 0.00
April 0.05 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 30.48 0.00 0.00
December 146.05 0.00 0.00
       
Annual Sum or Average 38.10 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 146.05 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 202.16 0.00 0.00
February 186.02 0.00 0.00
March 160.26 0.00 0.00
April 2.08 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 60.16 0.00 0.00
December 202.10 0.00 0.00
       
Annual Sum or Average 67.33 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 202.16 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 90.77 0.00 0.00
February 103.41 0.00 0.00
March 83.09 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 29.13 0.00 0.00
December 110.65 0.00 0.00
       
Annual Sum or Average 34.49 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 110.65 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 171.76 0.00 0.00
February 164.54 0.00 0.00
March 108.35 0.00 0.00
April 2.12 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 52.47 0.00 0.00
December 187.56 0.00 0.00
       
Annual Sum or Average 56.83 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 187.56 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 258.58 0.00 0.00
February 217.41 0.00 0.00
March 174.17 0.00 0.00
April 2.16 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 69.52 0.00 0.00
December 253.67 0.00 0.00
       
Annual Sum or Average 80.87 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 258.58 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 135.81 0.00 0.00
February 131.90 0.00 0.00
March 95.10 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 35.53 0.00 0.00
December 156.35 0.00 0.00
       
Annual Sum or Average 45.93 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 156.35 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 206.95 0.00 0.00
February 190.40 0.00 0.00
March 115.51 0.00 0.00
April 2.11 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 57.83 0.00 0.00
December 234.54 0.00 0.00
       
Annual Sum or Average 66.84 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 234.54 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.28
February 0.00 0.00 0.34
March 0.00 0.00 0.38
April 0.00 0.00 0.47
May 0.00 0.00 0.59
June 0.00 0.00 0.65
July 0.00 0.00 0.67
August 0.00 0.00 0.67
September 0.00 0.00 0.66
October 0.00 0.00 0.60
November 0.00 0.00 0.47
December 0.00 0.00 0.34
       
Annual Sum or Average 0.00 0.00 0.51
Minimum of Months 0.00 0.00 0.28
Maximum of Months 0.00 0.00 0.67



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.16
March 0.00 0.00 0.17
April 0.00 0.00 0.23
May 0.00 0.00 0.33
June 0.00 0.00 0.39
July 0.00 0.00 0.40
August 0.00 0.00 0.41
September 0.00 0.00 0.40
October 0.00 0.00 0.36
November 0.00 0.00 0.27
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.19
March 0.00 0.00 0.21
April 0.00 0.00 0.29
May 0.00 0.00 0.41
June 0.00 0.00 0.49
July 0.00 0.00 0.50
August 0.00 0.00 0.49
September 0.00 0.00 0.48
October 0.00 0.00 0.42
November 0.00 0.00 0.30
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.14
March 0.00 0.00 0.19
April 0.00 0.00 0.27
May 0.00 0.00 0.41
June 0.00 0.00 0.47
July 0.00 0.00 0.49
August 0.00 0.00 0.48
September 0.00 0.00 0.45
October 0.00 0.00 0.37
November 0.00 0.00 0.24
December 0.00 0.00 0.12
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.11
March 0.00 0.00 0.14
April 0.00 0.00 0.21
May 0.00 0.00 0.33
June 0.00 0.00 0.40
July 0.00 0.00 0.41
August 0.00 0.00 0.40
September 0.00 0.00 0.38
October 0.00 0.00 0.31
November 0.00 0.00 0.20
December 0.00 0.00 0.10
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.13
March 0.00 0.00 0.18
April 0.00 0.00 0.28
May 0.00 0.00 0.41
June 0.00 0.00 0.49
July 0.00 0.00 0.50
August 0.00 0.00 0.49
September 0.00 0.00 0.46
October 0.00 0.00 0.38
November 0.00 0.00 0.24
December 0.00 0.00 0.11
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.43
June 0.00 0.00 0.49
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.44
November 0.00 0.00 0.33
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.20
March 0.00 0.00 0.21
April 0.00 0.00 0.27
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.43
September 0.00 0.00 0.43
October 0.00 0.00 0.39
November 0.00 0.00 0.30
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.51
October 0.00 0.00 0.45
November 0.00 0.00 0.34
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.31
May 0.00 0.00 0.43
June 0.00 0.00 0.49
July 0.00 0.00 0.52
August 0.00 0.00 0.50
September 0.00 0.00 0.47
October 0.00 0.00 0.40
November 0.00 0.00 0.28
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.14
March 0.00 0.00 0.18
April 0.00 0.00 0.26
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.42
September 0.00 0.00 0.40
October 0.00 0.00 0.35
November 0.00 0.00 0.24
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.28
December 0.00 0.00 0.15
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.50
June 0.00 0.00 0.57
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.50
November 0.00 0.00 0.36
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.21
March 0.00 0.00 0.23
April 0.00 0.00 0.31
May 0.00 0.00 0.43
June 0.00 0.00 0.50
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.50
October 0.00 0.00 0.44
November 0.00 0.00 0.33
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.58
October 0.00 0.00 0.51
November 0.00 0.00 0.36
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.19
March 0.00 0.00 0.26
April 0.00 0.00 0.36
May 0.00 0.00 0.50
June 0.00 0.00 0.58
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.56
October 0.00 0.00 0.47
November 0.00 0.00 0.32
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.12
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.31
May 0.00 0.00 0.43
June 0.00 0.00 0.51
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.42
November 0.00 0.00 0.28
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.12
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.19
March 0.00 0.00 0.25
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.48
November 0.00 0.00 0.32
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 714.69 532.10
February 0.00 0.00 705.19 474.23
March 0.00 0.00 667.82 497.21
April 0.00 0.00 617.12 444.64
May 0.00 0.00 555.26 413.41
June 0.00 0.00 513.42 369.92
July 0.00 0.00 493.98 367.78
August 0.00 0.00 505.01 375.99
September 0.00 0.00 541.61 390.23
October 0.00 0.00 598.57 445.65
November 0.00 0.00 653.15 470.60
December 0.00 0.00 698.18 519.81
         
Annual Sum or Average 0.00 0.00 604.77 5301.57
Minimum of Months 0.00 0.00 493.98 367.78
Maximum of Months 0.00 0.00 714.69 532.10