Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27

Tabular Output Report in Format: HTML

Building: MF+CZ1A+USA_FL_Miami.Intl.AP.722020+oilfurnace+crawlspace+IECC_2015

Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2019-02-14 08:28:00


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 757275.03 19.41 35.04
Net Site Energy 757275.03 19.41 35.04
Total Source Energy 1969402.28 50.49 91.13
Net Source Energy 1969402.28 50.49 91.13


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 8940.23 0.00 0.00 0.00 0.00
Cooling 170686.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27957.77 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 196958.83 0.00 0.00 0.00 374778.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 551375.97 205899.07 0.00 0.00 0.00 374778.00
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 8940.23 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 170686.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 27957.77 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 196958.83 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 374778.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 9.19 9.53 0.00 0.00 0.00 17.34
Other 13.87 0.00 0.00 0.00 0.00 0.00
Total 25.51 9.53 0.00 0.00 0.00 17.34


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 5.09 5.28 0.00 0.00 0.00 9.61
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 14.14 5.28 0.00 0.00 0.00 9.61


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 551375.967 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 551375.967 100.00
     
Total On-Site and Utility Electric Sources 551375.967 100.00
Total Electricity End Uses 551375.967 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 374778.00 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 374778.00 100.00
Total Water End Uses 374778.00 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 265.50
Time Setpoint Not Met During Occupied Cooling 0.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 4061.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
RunPeriod ANNUAL
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [ft] 36.09
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:15 04-FEB-06:15 - - - 01-JAN-08:30
Heating 0.00 100.31 0.00 0.00 0.00 0.00
Cooling 47.26 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.02 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 111.33 0.00 0.00 0.00 1.36
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 121.92 211.64 0.00 0.00 0.00 1.36


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 100.31 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 47.26 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.36 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.02 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 111.33 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.36
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 9691.21 0.00 0.00 0.00
Cooling 540563.77 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 88542.25 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 213503.38 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1746207.69 223194.59 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 0.45 0.00 0.00 0.00
Cooling 25.01 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.10 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.88 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 80.81 10.33 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 0.45 0.00 0.00 0.00
Cooling 25.01 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.10 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.88 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 80.81 10.33 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 47.66 0.00 47.66 Wetbulb [F] 748.07 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 91.76 12.06 77.54 Wetbulb [F] 885.87 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.219 0.882              
North Total or Average           531.68 0.501 0.219 0.882              
Non-North Total or Average           1595.05 0.501 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 339892.38 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   23580.38 17580.88 5999.50 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8003.39 5410.96 2592.43 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10276.01 6947.44 3328.57 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13397.27 9319.38 4077.89 0.70 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8260.26 5584.62 2675.64 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10425.28 7055.51 3369.77 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13130.60 9242.82 3887.77 0.70 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8440.42 5706.43 2733.99 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10195.92 6968.91 3227.00 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13151.36 9267.25 3884.11 0.70 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8673.89 5864.27 2809.62 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10308.54 7057.44 3251.09 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15655.23 11123.28 4531.95 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11191.06 7656.43 3534.63 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12484.76 8614.72 3870.03 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15666.77 11132.55 4534.22 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11229.30 7698.42 3530.88 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12471.33 8617.40 3853.92 0.69 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.9 3.36 11.46 12.15 11.82
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.46 11.80 12.52 12.38
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.7 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.50 11.93 12.67 12.61
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.44 11.74 12.46 12.28
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.48 11.89 12.62 12.52
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.44 11.74 12.45 12.28
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.48 11.88 12.61 12.51
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.43 11.70 12.41 12.21
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.48 11.88 12.61 12.52
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.47 11.84 12.57 12.45
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.43 11.70 12.41 12.21
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.48 11.87 12.60 12.50
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.47 11.83 12.56 12.44
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 42105.23 45549.35 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 12005.07 12526.57 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 15077.82 15902.64 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 20741.77 22120.15 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 12352.37 12908.33 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 15319.11 16167.62 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 20953.33 22351.58 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 12595.89 13175.44 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 15386.64 16241.24 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 21038.74 22445.25 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 12911.56 13522.35 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 15607.26 16483.49 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 25324.63 27148.35 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 16813.41 17808.42 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 19024.05 20234.96 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 25348.36 27174.36 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 16954.09 17962.86 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 19070.76 20286.22 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 756.81 285.46 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 200.13 75.49 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 256.95 96.92 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 361.70 136.43 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 206.55 77.91 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 261.42 98.60 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 365.62 137.91 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 211.05 79.61 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 262.67 99.08 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 367.20 138.50 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 216.89 81.81 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 266.75 100.62 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.46 168.40 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 289.05 109.03 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 329.94 124.45 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.90 168.57 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 291.65 110.01 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 330.80 124.78 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 34.178795 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17755.08 17755.08 14.79 756.813 756.813 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00890 89.47 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4695.33 4695.33 3.91 200.127 200.127 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01075 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6028.56 6028.56 5.02 256.954 256.954 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01021 88.08 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8485.86 8485.86 7.07 361.704 361.704 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00974 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4846.01 4846.01 4.04 206.550 206.550 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01070 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6133.25 6133.25 5.11 261.416 261.416 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01018 88.08 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8577.96 8577.96 7.15 365.619 365.619 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00943 89.17 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4951.81 4951.81 4.12 211.054 211.054 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01024 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6162.71 6162.71 5.13 262.667 262.667 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00979 88.53 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8615.06 8615.06 7.18 367.198 367.198 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00943 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5088.77 5088.77 4.24 216.893 216.893 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01020 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6258.44 6258.44 5.21 266.747 266.747 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00977 88.53 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7760.96 7760.96 6.46 330.800 330.800 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00987 88.41 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7740.65 7740.65 6.45 329.936 329.936 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00987 88.87 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10474.26 10474.26 8.72 446.459 446.459 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6842.67 6842.67 5.70 291.654 291.654 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01006 87.06 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6781.63 6781.63 5.65 289.053 289.053 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.01006 87.51 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10484.55 10484.55 8.73 446.898 446.898 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 MIAMI INTL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3269.21 3269.21 2.72 59.581 59.581 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4596.59 4596.59 3.83 83.772 83.772 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4604.25 4604.25 3.84 83.911 83.911 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3400.15 3400.15 2.83 61.967 61.967 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4598.66 4598.66 3.83 83.809 83.809 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3454.79 3454.79 2.88 62.963 62.963 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2537.06 2537.06 2.11 46.238 46.238 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3769.48 3769.48 3.14 68.698 68.698 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3773.84 3773.84 3.14 68.778 68.778 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2563.11 2563.11 2.13 46.712 46.712 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3766.77 3766.77 3.14 68.649 68.649 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4998.84 4998.84 4.16 91.102 91.102 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 4999.95 4999.95 4.16 91.123 91.123 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 4958.68 4958.68 4.13 90.371 90.371 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3791.16 3791.16 3.16 69.093 69.093 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3784.89 3784.89 3.15 68.979 68.979 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5005.87 5005.87 4.17 91.231 91.231 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 756.81 756.81 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.13 200.13 59.58 59.58
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.95 256.95 83.77 83.77
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.70 361.70 83.91 83.91
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.55 206.55 61.97 61.97
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.42 261.42 83.81 83.81
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.62 365.62 62.96 62.96
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.05 211.05 46.24 46.24
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.67 262.67 68.70 68.70
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.20 367.20 68.78 68.78
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.89 216.89 46.71 46.71
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.75 266.75 68.65 68.65
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.46 446.46 90.37 90.37
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.05 289.05 68.98 68.98
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.94 329.94 91.12 91.12
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.90 446.90 91.23 91.23
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.65 291.65 69.09 69.09
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.80 330.80 91.10 91.10


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3545.00 1710.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7173.00 4344.50 3499.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7234.50 3767.25 2883.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7159.00 4614.50 3516.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7065.25 5003.00 3894.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7118.75 4133.50 3050.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7369.50 2697.00 1955.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7209.00 2255.25 1633.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7280.25 2260.75 1540.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7222.50 3021.00 2085.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7109.75 2658.75 1804.75
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7176.25 2510.75 1622.50
LIVING_UNIT3_BACKROW_TOPFLOOR 7270.25 2992.25 2070.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 7373.75 2803.00 1997.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 7424.25 3290.00 2445.25
LIVING_UNIT2_BACKROW_TOPFLOOR 7230.00 3259.25 2361.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7341.50 2975.00 2224.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7323.25 3495.50 2533.25
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 7549.50 5420.50 4061.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.75 0.00 0.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 51.75 0.00 51.75 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 80.25 0.00 80.25 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5.75 0.00 5.75 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 32.25 0.00 32.25 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3.50 0.00 3.50 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 56.50 0.00 56.50 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 66.25 0.00 66.25 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 51.75 0.00 51.75 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 32.75 0.00 32.75 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 34.00 0.00 34.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 32.75 0.00 32.75 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 63.75 0.00 63.75 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 265.50 0.75 265.50 0.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.141 0.000 0.264
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.264
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.264
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.141 0.000 0.264
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1867
Defaulted Fields 446
Fields with Defaults 4738
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
Electricity:Building 100751.26 6306.84 02-JAN-03:15 19194.31 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:15 15388.75 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:15 880.12 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:15 381.47 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
Fans:Electricity 8188.15 95.39 15-MAR-00:45 2130.40 27-JUL-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
ElectricityPurchased:Plant 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
Cogeneration:ElectricityPurchased 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
ElectricityNet:Plant 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
Cogeneration:ElectricityNet 161484.65 7387.27 23-FEB-03:15 35706.02 29-JUL-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 58178.05 521.25 24-FEB-00:45 16745.14 29-JUL-16:15
General:Fans:Electricity 8188.15 95.39 15-MAR-00:45 2130.40 27-JUL-17:15
Cooling:Electricity 49989.90 92.87 04-FEB-07:15 14620.79 29-JUL-16:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 2058.99 0.00 01-JAN-00:15 211487.23 04-FEB-06:15
Gas:Plant 2058.99 0.00 01-JAN-00:15 211487.23 04-FEB-06:15
WaterSystems:Gas 1969.59 0.00 01-JAN-00:15 112055.69 22-JAN-08:45
Water Heater:WaterSystems:Gas 1969.59 0.00 01-JAN-00:15 112055.69 22-JAN-08:45
Heating:Gas 89.40 0.00 01-JAN-00:15 102437.30 04-FEB-07:00
Boiler:Heating:Gas 89.40 0.00 01-JAN-00:15 102437.30 04-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
Water:Plant 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
WaterSystems:Water 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
MainsWater:Plant 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
WaterSystems:MainsWater 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 50107.88 0.01 25-JAN-02:15 0.18 01-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 86093.21 664.68 19-JUL-02:15 94872.74 04-FEB-07:15
PlantLoopHeatingDemand:Plant 79448.65 664.68 19-JUL-02:15 21028.72 15-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 79448.65 664.68 19-JUL-02:15 21028.72 15-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1326623.17 16437.50 22-MAR-02:30 348498.47 27-JUL-17:15
EnergyTransfer:Building 489236.38 6794.14 15-MAR-00:45 146273.87 29-JUL-16:30
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 7379.71 0.00 01-JAN-00:15 79294.24 04-FEB-07:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 481856.67 1640.48 04-FEB-07:15 146273.87 29-JUL-16:30
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 98357.80 1640.48 04-FEB-07:15 17696.56 29-JUL-16:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 98357.80 1640.48 04-FEB-07:15 17696.56 29-JUL-16:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17685.21 0.00 01-JAN-03:00 5295.69 29-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 308.59 0.00 01-JAN-00:15 3873.39 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17376.62 0.00 01-JAN-03:00 5295.69 29-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22383.29 0.00 01-JAN-01:30 6915.98 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 525.35 0.00 01-JAN-00:15 5604.38 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21857.94 0.00 01-JAN-01:30 6915.98 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20272.74 0.00 01-JAN-01:15 8636.54 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 741.69 0.00 01-JAN-00:15 5635.21 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19531.05 0.00 01-JAN-01:15 8636.54 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15552.52 0.00 01-JAN-02:45 5444.27 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 479.24 0.00 01-JAN-00:15 4102.87 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15073.28 0.00 01-JAN-02:45 5444.27 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20206.92 0.00 01-JAN-01:15 6785.66 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 661.13 0.00 01-JAN-00:15 5652.73 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19545.78 0.00 01-JAN-01:15 6785.66 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25419.08 0.00 01-JAN-04:00 8744.25 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 276.51 0.00 01-JAN-00:15 3906.84 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25142.58 0.00 01-JAN-04:00 8744.25 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20889.03 0.00 05-JAN-03:30 5637.28 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 109.30 0.00 01-JAN-00:15 2617.08 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20779.73 0.00 05-JAN-03:30 5637.28 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25482.88 0.00 01-JAN-04:00 7081.31 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 242.43 0.00 01-JAN-00:15 4283.30 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25240.45 0.00 01-JAN-04:00 7081.31 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23137.66 0.00 01-JAN-03:45 8648.76 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 402.85 0.00 01-JAN-00:15 4322.37 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22734.82 0.00 01-JAN-03:45 8648.76 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18524.68 0.00 05-JAN-03:30 5613.69 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 197.02 0.00 01-JAN-00:15 2795.43 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18327.66 0.00 05-JAN-03:30 5613.69 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23154.89 0.00 01-JAN-03:45 6959.31 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 324.78 0.00 01-JAN-00:15 4350.44 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22830.12 0.00 01-JAN-03:45 6959.31 29-JUL-16:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 27114.09 0.00 01-JAN-02:30 8895.28 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 597.11 0.00 01-JAN-00:15 5947.86 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26516.98 0.00 01-JAN-02:30 8895.28 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28611.00 0.00 01-JAN-02:45 8901.15 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 502.40 0.00 01-JAN-00:15 5887.01 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28108.60 0.00 01-JAN-02:45 8901.15 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28631.07 0.00 01-JAN-02:45 10806.48 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 583.93 0.00 01-JAN-00:15 5787.36 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28047.14 0.00 01-JAN-02:45 10806.48 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22547.89 0.00 01-JAN-05:30 7726.15 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 417.46 0.00 01-JAN-00:15 4385.11 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22130.43 0.00 01-JAN-05:30 7726.15 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 24071.65 0.00 01-JAN-05:45 7719.11 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 312.37 0.00 01-JAN-00:15 4238.61 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 23759.28 0.00 01-JAN-05:45 7719.11 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 27193.96 0.00 01-JAN-02:45 10819.22 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 697.56 0.00 01-JAN-00:15 5923.23 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26496.41 0.00 01-JAN-02:45 10819.22 29-JUL-16:30
EnergyTransfer:Plant 86600.83 664.68 19-JUL-02:15 98561.57 04-FEB-07:00
WaterSystems:EnergyTransfer 79448.65 664.68 19-JUL-02:15 21028.72 15-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 79448.65 664.68 19-JUL-02:15 21028.72 15-JAN-09:00
EnergyTransfer:HVAC 750785.96 7109.94 24-FEB-01:00 198401.50 27-JUL-18:15
HeatingCoils:EnergyTransfer 6644.56 0.00 01-JAN-00:15 76488.88 04-FEB-07:00
PlantLoopHeatingDemand:HVAC 6644.56 0.00 01-JAN-00:15 76488.88 04-FEB-07:00
HeatingCoils:PlantLoopHeatingDemand 6644.56 0.00 01-JAN-00:15 76488.88 04-FEB-07:00
CoolingCoils:EnergyTransfer 744141.40 1717.55 04-FEB-07:15 198401.50 27-JUL-18:15
Boilers:EnergyTransfer 7152.19 0.00 01-JAN-00:15 81949.84 04-FEB-07:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -8191.01 0.000 0.000 2874.227 2456.001 10401.374 8824.913 0.000 2600.907 74636.425 0.000 -1550.54 0.000 -1885.46 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 308.579 -1447.09 0.000 0.000 2895.579 2456.001 10401.374 3681.672 0.000 2477.563 0.000 0.000 -602.20 0.000 -1650.49 -2591.43
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 525.334 -1820.28 0.000 0.000 2902.855 2456.001 10401.374 9055.440 0.000 2600.045 0.001 0.000 -1425.65 0.000 -1700.40 -2957.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 741.672 -1626.50 0.000 0.000 2906.957 2456.001 10401.374 7181.122 0.000 2603.287 0.000 0.000 -1502.36 0.000 -1634.60 -3622.44
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 479.236 -1255.28 0.000 0.000 2901.588 2456.001 10401.374 1937.248 0.000 2480.123 0.000 0.000 -619.05 0.000 -1591.76 -3371.37
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 661.123 -1627.74 0.000 0.000 2907.202 2456.001 10401.374 7344.407 0.000 2600.000 0.000 0.000 -1407.99 0.000 -1654.74 -3761.47
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 276.503 -2093.81 0.000 0.000 2892.388 2456.001 10401.374 8730.739 0.000 2014.379 1365.514 0.000 -1615.73 0.000 -1378.60 -0.01
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 109.302 -1730.50 0.000 0.000 2886.269 2456.001 10401.374 3631.008 0.000 1892.823 1374.975 0.000 -647.58 0.000 -1324.34 -0.08
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 242.428 -2101.98 0.000 0.000 2893.449 2456.001 10401.374 8928.468 0.000 2014.434 1224.726 0.000 -1538.19 0.000 -1382.12 -0.04
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 402.841 -1893.31 0.000 0.000 2896.717 2456.001 10401.374 7070.876 0.000 2015.982 457.682 0.000 -1626.76 0.000 -1339.83 -0.23
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 197.021 -1526.30 0.000 0.000 2890.752 2456.001 10401.374 1899.236 0.000 1893.810 548.847 0.000 -669.39 0.000 -1289.82 -0.07
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 324.772 -1901.25 0.000 0.000 2897.143 2456.001 10401.374 7226.515 0.000 2014.404 386.444 0.000 -1522.84 0.000 -1353.51 -0.11
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 597.103 -2208.29 0.000 0.000 2900.281 2456.001 10401.374 7124.600 0.000 2573.632 3719.994 0.000 -1541.98 0.000 -1713.85 -0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 502.397 -2340.83 0.000 0.000 2897.856 2456.001 10401.374 8843.119 0.000 2573.552 3717.875 0.000 -1542.67 0.000 -1740.76 -0.06
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 583.918 -2335.70 0.000 0.000 2898.030 2456.001 10401.374 8651.167 0.000 2573.976 3816.837 0.000 -1609.57 0.000 -1724.64 -0.05
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 417.455 -1842.98 0.000 0.000 2894.611 2456.001 10401.374 1857.086 0.000 2454.262 3979.935 0.000 -675.39 0.000 -1654.76 -0.08
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 312.366 -1978.63 0.000 0.000 2891.765 2456.001 10401.374 3594.364 0.000 2452.798 3983.350 0.000 -647.78 0.000 -1684.86 -0.26
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 697.546 -2206.56 0.000 0.000 2900.432 2456.001 10401.374 6961.021 0.000 2576.080 3834.000 0.000 -1633.71 0.000 -1696.33 -0.05
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 40291.065 0.000 0.000 0.000 0.000 -2789.49 -37501.57
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5870.218 48063.829 0.000 0.000 0.000 -53934.05 -0.87
Total Facility 0.000 0.000 7379.598 -40128.02 0.000 0.000 52128.102 44208.020 187224.736 112543.000 0.000 88573.340 151110.432 0.000 -22379.39 0.000 -85124.42 -53807.20


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-16:30 0.00 0.00 0.00 -1.5 0.00 0.00 140.45 384.73 1363.24 4632.32 0.00 1546.20 9943.26 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-17:32 0.00 0.00 0.00 -0.4 0.00 0.00 262.67 535.87 1675.86 533.03 0.00 1353.38 946.18 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.24 2214.26 0.00 1590.86 1222.68 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.46 384.73 1363.24 4680.15 0.00 1546.20 524.16 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-18:18 0.00 0.00 0.00 -0.5 0.00 0.00 426.60 721.37 1734.73 438.43 0.00 1266.90 862.12 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.24 2255.07 0.00 1590.84 1051.59 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.24 4612.84 0.00 1197.41 1047.41 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 1734.73 455.27 0.00 962.85 1338.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.24 2209.29 0.00 1230.55 1753.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.24 4659.89 0.00 1197.40 904.79 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.04 721.37 1734.73 480.64 0.00 962.85 1290.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.45 384.73 1363.24 2253.00 0.00 1230.54 1587.61 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 262.70 535.87 1675.86 1531.31 0.00 1435.24 3462.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 262.74 535.87 1675.86 1492.38 0.00 1435.62 3506.40 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.24 4550.95 0.00 1541.21 2828.06 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1734.73 456.98 0.00 1303.54 3085.71 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1734.73 432.21 0.00 1303.54 3103.46 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.24 4594.80 0.00 1541.21 2796.96 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:30 0.00 0.00 0.00 -12.2 0.00 0.00 2526.18 6925.11 24538.23 45584.56 0.00 38061.19 49889.00 0.00 0.00 0.00 -20899.6 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3873.32 0.00 0.00 0.00 526.29 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -828.2 0.00 -2953.1 -2084.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20-DEC-23:10 0.00 0.00 7025.72 0.00 0.00 0.00 546.26 137.40 1146.27 0.00 0.00 0.00 0.00 0.00 -1483.2 0.00 -1755.2 -5617.2
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 24-JAN-13:06 0.00 0.00 9026.13 0.00 0.00 0.00 137.52 103.05 1076.04 172.91 0.00 0.00 0.00 0.00 0.00 0.00 -1108.1 -9407.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 20-DEC-17:38 0.00 0.00 4120.05 0.00 0.00 0.00 296.86 535.87 1655.83 0.00 0.00 0.00 0.00 0.00 -421.9 0.00 -1122.6 -5064.1
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5652.60 0.00 0.00 0.00 526.30 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2040.9 0.00 -3134.6 -2469.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 3906.72 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2096.3 0.00 -2282.6 -1520.6
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 2617.00 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -845.3 0.00 -2100.7 -1663.6
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 04-FEB-00:25 0.00 0.00 7737.06 0.00 0.00 0.00 551.73 54.96 964.75 0.00 0.00 0.00 0.00 0.00 -1624.7 0.00 -1615.8 -6068.0
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 24-JAN-11:56 0.00 0.00 9098.46 0.00 0.00 0.00 133.70 103.05 1082.63 0.00 0.00 0.00 0.00 0.00 -79.5 0.00 -983.9 -9354.5
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-FEB-07:15 0.00 0.00 2795.38 0.00 0.00 0.00 464.78 343.51 1218.74 0.00 0.00 0.00 0.00 0.00 -790.4 0.00 -2056.6 -1975.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15-DEC-02:25 0.00 0.00 7076.58 0.00 0.00 0.00 546.37 54.96 865.75 0.00 0.00 0.00 0.00 0.00 -1661.4 0.00 -1679.6 -5202.6
LIVING_UNIT3_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5947.72 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2075.1 0.00 -3141.6 -2723.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 20-DEC-23:55 0.00 0.00 6743.19 0.00 0.00 0.00 544.70 137.40 1146.27 0.00 0.00 0.00 0.00 0.00 -1513.9 0.00 -1828.0 -5229.6
LIVING_UNIT1_FRONTROW_TOPFLOOR 15-MAR-08:15 0.00 0.00 10140.24 0.00 0.00 0.00 224.00 151.14 1145.20 0.00 0.00 0.00 0.00 0.00 -566.4 0.00 -1990.8 -9103.3
LIVING_UNIT2_BACKROW_TOPFLOOR 04-FEB-07:15 0.00 0.00 4385.10 0.00 0.00 0.00 464.79 343.51 1218.74 0.00 0.00 0.00 0.00 0.00 -783.6 0.00 -2911.5 -2717.1
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 4238.53 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -836.0 0.00 -2959.6 -2435.6
LIVING_UNIT1_BACKROW_TOPFLOOR 27-JAN-10:22 0.00 0.00 10570.35 0.00 0.00 0.00 130.55 103.05 1078.58 539.97 0.00 0.00 0.00 0.00 0.00 0.00 -245.4 -12177.1
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-FEB-07:00 -1774.6 0.15 79292.30 -0.1 0.00 0.00 9423.29 6925.11 19469.92 0.00 0.00 1178.03 0.00 0.00 -29995.7 0.00 -65337.0 -19181.3



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 756.813 2.00 2.00 1.00 44.9950 756.813 0.059 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.127 2.00 2.00 1.00 44.9950 200.127 0.225 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.954 2.00 2.00 1.00 44.9950 256.954 0.175 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.704 2.00 2.00 1.00 44.9950 361.704 0.124 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.550 2.00 2.00 1.00 44.9950 206.550 0.218 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.416 2.00 2.00 1.00 44.9950 261.416 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.619 2.00 2.00 1.00 44.9950 365.619 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.054 2.00 2.00 1.00 44.9950 211.054 0.213 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.667 2.00 2.00 1.00 44.9950 262.667 0.171 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.198 2.00 2.00 1.00 44.9950 367.198 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.893 2.00 2.00 1.00 44.9950 216.893 0.207 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.747 2.00 2.00 1.00 44.9950 266.747 0.169 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.459 2.00 2.00 1.00 44.9950 446.459 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.053 2.00 2.00 1.00 44.9950 289.053 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.936 2.00 2.00 1.00 44.9950 329.936 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.898 2.00 2.00 1.00 44.9950 446.898 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.654 2.00 2.00 1.00 44.9950 291.654 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.800 2.00 2.00 1.00 44.9950 330.800 0.136 1.000 44.9950 0.14


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 59.581 2.00 2.00 1.00 44.9950 59.581 1.000 1.000 44.9950 0.76
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 83.772 2.00 2.00 1.00 44.9950 83.772 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 83.911 2.00 2.00 1.00 44.9950 83.911 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 61.967 2.00 2.00 1.00 44.9950 61.967 1.000 1.000 44.9950 0.73
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 83.809 2.00 2.00 1.00 44.9950 83.809 1.000 1.000 44.9950 0.54
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 62.963 2.00 2.00 1.00 44.9950 62.963 1.000 1.000 44.9950 0.71
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.238 2.00 2.00 1.00 44.9950 46.238 1.000 1.000 44.9950 0.97
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.698 2.00 2.00 1.00 44.9950 68.698 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.778 2.00 2.00 1.00 44.9950 68.778 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.712 2.00 2.00 1.00 44.9950 46.712 1.000 1.000 44.9950 0.96
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.649 2.00 2.00 1.00 44.9950 68.649 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 90.371 2.00 2.00 1.00 44.9950 90.371 1.000 1.000 44.9950 0.50
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 68.979 2.00 2.00 1.00 44.9950 68.979 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.123 2.00 2.00 1.00 44.9950 91.123 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.231 2.00 2.00 1.00 44.9950 91.231 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.093 2.00 2.00 1.00 44.9950 69.093 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.102 2.00 2.00 1.00 44.9950 91.102 1.000 1.000 44.9950 0.49


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   756.813 756.8131 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   200.127 200.1265 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   256.954 256.9538 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   361.704 361.7035 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   206.550 206.5495 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   261.416 261.4163 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   365.619 365.6189 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   211.054 211.0545 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   262.667 262.6670 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   367.198 367.1984 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   216.893 216.8926 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   266.747 266.7471 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   330.800 330.7996 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   329.936 329.9358 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   446.459 446.4593 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   291.654 291.6543 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   289.053 289.0526 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   446.898 446.8981 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 756.81 756.813 756.81 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.13 200.127 200.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.95 256.954 256.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.70 361.704 361.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.55 206.550 206.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.42 261.416 261.42 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.62 365.619 365.62 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.05 211.054 211.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.67 262.667 262.67 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.20 367.198 367.20 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.89 216.893 216.89 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.75 266.747 266.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.46 446.459 446.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.05 289.053 289.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.94 329.936 329.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.90 446.898 446.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.65 291.654 291.65 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.80 330.800 330.80 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   59.581 59.581 59.581 44.9950 0.755 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   83.772 83.772 83.772 44.9950 0.537 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   83.911 83.911 83.911 44.9950 0.536 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   61.967 61.967 61.967 44.9950 0.726 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   83.809 83.809 83.809 44.9950 0.537 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   62.963 62.963 62.963 44.9950 0.715 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   46.238 46.238 46.238 44.9950 0.973 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   68.698 68.698 68.698 44.9950 0.655 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   68.778 68.778 68.778 44.9950 0.654 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   46.712 46.712 46.712 44.9950 0.963 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   68.649 68.649 68.649 44.9950 0.655 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   91.102 91.102 91.102 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   91.123 91.123 91.123 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   90.371 90.371 90.371 44.9950 0.498 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   69.093 69.093 69.093 44.9950 0.651 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   68.979 68.979 68.979 44.9950 0.652 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   91.231 91.231 91.231 44.9950 0.493 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 59.58 59.581 59.58 59.58 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 83.77 83.772 83.77 83.77 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 83.91 83.911 83.91 83.91 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 61.97 61.967 61.97 61.97 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 83.81 83.809 83.81 83.81 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 62.96 62.963 62.96 62.96 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.24 46.238 46.24 46.24 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.70 68.698 68.70 68.70 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.78 68.778 68.78 68.78 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.71 46.712 46.71 46.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.65 68.649 68.65 68.65 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 90.37 90.371 90.37 90.37 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 68.98 68.979 68.98 68.98 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.12 91.123 91.12 91.12 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.23 91.231 91.23 91.23 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.09 69.093 69.09 69.09 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.10 91.102 91.10 91.10 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Sec1.1A-General Information

Data
Weather File ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 265.50
Number of hours cooling loads not met 0.75
Number of hours not met 266.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 89.40 100234.43 0.00 0.00
Space Cooling 49989.90 13839.95 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8188.15 2057.02 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 1969.59 111252.80 0.00 0.00
Receptacle Equipment 87803.80 15388.75 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 161484.65   2058.99   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 551375.97
Natural Gas 0.00 205899.07
Additional 0.00 0.00
Total 299798.81 757275.03


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 1.28
Fans-Interior 0.21
Service Water Heating 0.00
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 4.14


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.07
Service Water Heating 1.48
Miscellaneous -0.0
Subtotal 1.55


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.84
Space Heating 1.18
Space Cooling 22.54
Fans-Interior 3.69
Service Water Heating 26.01
Receptacle Equipment 39.59
Miscellaneous 1.15



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 756.81
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 200.13
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 256.95
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 361.70
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 206.55
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 261.42
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 365.62
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 211.05
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 262.67
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 367.20
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 216.89
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 266.75
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 330.80
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 329.94
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 446.46
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 291.65
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 289.05
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 446.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 756.81
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 200.13
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 256.95
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 361.70
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 206.55
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 261.42
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 365.62
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 211.05
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.67
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 367.20
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.89
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.75
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.46
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 289.05
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.94
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.90
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.65
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 756.81 1.97 0.745573
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 200.13 0.666949 0.676083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 256.95 0.856334 0.676083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 361.70 1.12 0.695618
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 206.55 0.688355 0.676083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 261.42 0.868773 0.676770
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 365.62 1.09 0.703915
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 211.05 0.703368 0.676083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 262.67 0.849660 0.683500
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 367.20 1.10 0.704661
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 216.89 0.722824 0.676083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 266.75 0.859045 0.684621
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 446.46 1.30 0.710515
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 289.05 0.932588 0.684156
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 329.94 1.04 0.690019
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 446.90 1.31 0.710584
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 291.65 0.935775 0.685565
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 330.80 1.04 0.690977
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 756.81 756.81 756.81 1.97 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 200.13 200.13 200.13 0.666949 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 256.95 256.95 256.95 0.856334 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 361.70 361.70 361.70 1.12 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 206.55 206.55 206.55 0.688355 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 261.42 261.42 261.42 0.868773 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 365.62 365.62 365.62 1.09 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 211.05 211.05 211.05 0.703368 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 262.67 262.67 262.67 0.849660 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 367.20 367.20 367.20 1.10 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 216.89 216.89 216.89 0.722824 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 266.75 266.75 266.75 0.859045 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 446.46 446.46 446.46 1.30 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 289.05 289.05 289.05 0.932588 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 329.94 329.94 329.94 1.04 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 446.90 446.90 446.90 1.31 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 291.65 291.65 291.65 0.935775 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 330.80 330.80 330.80 1.04 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 42105.23 4.25 602.95
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 12005.07 1.21 167.61
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 15077.82 1.52 212.11
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 20741.77 2.09 294.07
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 12352.37 1.25 172.64
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 15319.11 1.55 215.60
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 20953.33 2.11 297.11
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 12595.89 1.27 176.16
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 15386.64 1.55 216.57
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 21038.74 2.12 298.35
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 12911.56 1.30 180.73
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 15607.26 1.58 219.76
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 25324.63 2.56 360.36
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 16813.41 1.70 237.23
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 19024.05 1.92 269.22
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 25348.36 2.56 360.70
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 16954.09 1.71 239.26
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 19070.76 1.92 269.89
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 756.81
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 200.13
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 256.95
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 361.70
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 206.55
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 261.42
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 365.62
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 211.05
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 262.67
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 367.20
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 216.89
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 266.75
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 446.46
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 289.05
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 329.94
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 446.90
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 291.65
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 330.80
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 4.57 85.67
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 4.57
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 339892.38 34.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:00

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 744.000 106.570 0.000 0.000 106.570
February 672.000 102.388 0.000 0.000 102.388
March 744.000 117.503 0.000 0.000 117.503
April 720.000 125.676 0.000 0.000 125.676
May 744.000 143.876 0.000 0.000 143.876
June 720.000 145.622 0.000 0.000 145.622
July 744.000 152.381 0.000 0.000 152.381
August 744.000 152.669 0.000 0.000 152.669
September 720.000 145.608 0.000 0.000 145.608
October 744.000 144.141 0.000 0.000 144.141
November 720.000 125.027 0.000 0.000 125.027
December 744.000 112.383 0.000 0.000 112.383
           
Annual Sum or Average 8760.000 1573.844 0.000 0.000 1573.844
Minimum of Months 672.000 102.388 0.000 0.000 102.388
Maximum of Months 744.000 152.669 0.000 0.000 152.669



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 453.805 11.262 84.111 0.448 11.709
February 465.787 12.725 51.583 0.498 13.224
March 588.404 15.023 60.375 0.457 15.480
April 690.121 19.633 0.250 0.000 19.633
May 744.000 28.420 0.000 0.000 28.420
June 720.000 32.029 0.000 0.000 32.029
July 744.000 34.186 0.000 0.000 34.186
August 744.000 34.242 0.000 0.000 34.242
September 720.000 32.725 0.000 0.000 32.725
October 744.000 30.529 0.000 0.000 30.529
November 629.148 21.861 23.750 0.159 22.020
December 502.926 13.812 63.125 0.550 14.362
           
Annual Sum or Average 7746.191 286.446 283.194 2.112 288.558
Minimum of Months 453.805 11.262 0.000 0.000 11.709
Maximum of Months 744.000 34.242 84.111 0.550 34.242



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 427.401 12.685 75.625 1.641 17.612
February 451.625 15.003 46.708 1.427 18.458
March 577.461 18.529 44.458 1.087 21.335
April 677.486 25.196 0.125 0.006 25.726
May 742.250 35.836 0.000 0.000 35.836
June 720.000 40.330 0.000 0.000 40.330
July 744.000 43.040 0.000 0.000 43.040
August 744.000 42.220 0.000 0.000 42.220
September 720.000 40.148 0.000 0.000 40.148
October 744.000 36.507 0.000 0.000 36.507
November 612.137 25.183 22.125 0.534 26.436
December 462.032 14.954 59.792 1.743 18.848
           
Annual Sum or Average 7622.393 349.631 248.833 6.438 366.496
Minimum of Months 427.401 12.685 0.000 0.000 17.612
Maximum of Months 744.000 43.040 75.625 1.743 43.040



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 331.498 8.205 130.001 2.682 16.088
February 398.046 12.254 73.549 2.050 17.532
March 543.883 17.979 66.714 1.695 23.367
April 668.083 25.875 5.375 0.043 26.036
May 742.250 38.907 0.000 0.000 38.907
June 720.000 43.517 0.000 0.000 43.517
July 744.000 46.778 0.000 0.000 46.778
August 744.000 45.764 0.000 0.000 45.764
September 720.000 41.279 0.000 0.000 41.279
October 744.000 35.409 0.000 0.000 35.409
November 582.096 22.265 30.583 0.753 23.963
December 395.865 11.877 88.417 2.537 18.239
           
Annual Sum or Average 7333.722 350.110 394.639 9.760 376.879
Minimum of Months 331.498 8.205 0.000 0.000 16.088
Maximum of Months 744.000 46.778 130.001 2.682 46.778



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 331.684 5.998 131.914 1.049 7.567
February 422.980 8.598 71.516 0.854 9.747
March 550.979 12.467 79.557 0.788 13.528
April 688.911 18.289 1.750 0.001 18.291
May 744.000 28.544 0.000 0.000 28.544
June 720.000 32.614 0.000 0.000 32.614
July 744.000 34.594 0.000 0.000 34.594
August 744.000 33.823 0.000 0.000 33.823
September 720.000 30.926 0.000 0.000 30.926
October 744.000 26.622 0.000 0.000 26.622
November 606.824 16.928 30.917 0.275 17.216
December 409.666 8.607 101.729 1.112 10.015
           
Annual Sum or Average 7427.044 258.011 417.382 4.080 263.486
Minimum of Months 331.684 5.998 0.000 0.000 7.567
Maximum of Months 744.000 34.594 131.914 1.112 34.594



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 335.363 7.502 111.875 2.206 12.942
February 427.837 10.983 64.729 1.776 14.933
March 552.835 16.035 58.375 1.262 18.859
April 676.986 23.984 1.750 0.022 24.408
May 742.250 35.937 0.000 0.000 35.937
June 720.000 40.837 0.000 0.000 40.837
July 744.000 43.392 0.000 0.000 43.392
August 744.000 41.850 0.000 0.000 41.850
September 720.000 38.530 0.000 0.000 38.530
October 744.000 32.930 0.000 0.000 32.930
November 600.271 20.514 26.875 0.605 21.745
December 381.843 10.027 96.229 2.413 14.173
           
Annual Sum or Average 7389.386 322.520 359.833 8.285 340.536
Minimum of Months 335.363 7.502 0.000 0.000 12.942
Maximum of Months 744.000 43.392 111.875 2.413 43.392



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 490.598 17.545 74.050 0.879 18.497
February 496.382 20.140 44.000 0.848 21.202
March 616.400 25.239 43.425 0.702 26.977
April 696.808 32.175 0.000 0.000 32.175
May 744.000 43.067 0.000 0.000 43.067
June 720.000 46.901 0.000 0.000 46.901
July 744.000 50.812 0.000 0.000 50.812
August 744.000 50.232 0.000 0.000 50.232
September 720.000 47.273 0.000 0.000 47.273
October 744.000 44.121 0.000 0.000 44.121
November 647.679 31.771 19.500 0.272 32.075
December 541.241 21.502 59.250 1.042 22.544
           
Annual Sum or Average 7905.108 430.778 240.225 3.742 435.877
Minimum of Months 490.598 17.545 0.000 0.000 18.497
Maximum of Months 744.000 50.812 74.050 1.042 50.812



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 546.885 14.753 32.979 0.145 14.898
February 532.371 15.891 29.205 0.235 16.126
March 631.237 18.789 26.692 0.189 18.978
April 704.183 23.609 0.000 0.000 23.609
May 744.000 31.442 0.000 0.000 31.442
June 720.000 34.675 0.000 0.000 34.675
July 744.000 37.149 0.000 0.000 37.149
August 744.000 36.856 0.000 0.000 36.856
September 720.000 35.475 0.000 0.000 35.475
October 744.000 33.833 0.000 0.000 33.833
November 672.625 25.418 12.042 0.052 25.470
December 587.552 17.570 41.308 0.271 17.841
           
Annual Sum or Average 8090.853 325.462 142.226 0.892 326.354
Minimum of Months 532.371 14.753 0.000 0.000 14.898
Maximum of Months 744.000 37.149 41.308 0.271 37.149



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 507.161 16.110 28.292 0.508 20.633
February 507.147 18.307 25.800 0.656 20.524
March 629.394 22.653 16.375 0.355 24.908
April 703.160 29.666 0.000 0.000 29.674
May 744.000 39.613 0.000 0.000 39.613
June 720.000 43.818 0.000 0.000 43.818
July 744.000 46.945 0.000 0.000 46.945
August 744.000 45.761 0.000 0.000 45.761
September 720.000 43.756 0.000 0.000 43.756
October 744.000 40.617 0.000 0.000 40.617
November 649.992 29.137 10.708 0.195 30.159
December 543.257 18.658 38.558 0.852 21.312
           
Annual Sum or Average 7956.110 395.042 119.733 2.566 407.720
Minimum of Months 507.147 16.110 0.000 0.000 20.524
Maximum of Months 744.000 46.945 38.558 0.852 46.945



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 406.209 11.168 84.575 1.315 16.328
February 455.640 15.557 45.374 1.075 18.878
March 594.117 22.406 42.925 0.762 26.711
April 695.881 30.902 0.000 0.000 30.902
May 744.000 43.212 0.000 0.000 43.212
June 720.000 47.500 0.000 0.000 47.500
July 744.000 51.231 0.000 0.000 51.231
August 744.000 49.837 0.000 0.000 49.837
September 720.000 45.491 0.000 0.000 45.491
October 744.000 40.179 0.000 0.000 40.179
November 627.458 26.571 20.250 0.352 27.612
December 477.483 15.484 64.121 1.454 20.060
           
Annual Sum or Average 7672.787 399.539 257.245 4.959 417.942
Minimum of Months 406.209 11.168 0.000 0.000 16.328
Maximum of Months 744.000 51.231 84.575 1.454 51.231



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 444.666 8.937 71.382 0.376 9.402
February 492.102 11.697 45.650 0.380 12.222
March 597.042 16.211 42.276 0.294 16.548
April 703.842 22.398 0.000 0.000 22.398
May 744.000 31.565 0.000 0.000 31.565
June 720.000 35.220 0.000 0.000 35.220
July 744.000 37.534 0.000 0.000 37.534
August 744.000 36.474 0.000 0.000 36.474
September 720.000 33.796 0.000 0.000 33.796
October 744.000 30.125 0.000 0.000 30.125
November 655.688 20.579 16.083 0.084 20.663
December 508.621 11.982 69.542 0.527 12.729
           
Annual Sum or Average 7817.959 296.517 244.933 1.660 298.676
Minimum of Months 444.666 8.937 0.000 0.000 9.402
Maximum of Months 744.000 37.534 71.382 0.527 37.534



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 425.701 10.411 48.583 0.806 15.153
February 486.538 14.282 39.725 0.868 16.790
March 602.429 20.129 20.083 0.429 22.500
April 703.132 28.596 0.000 0.000 28.603
May 744.000 39.781 0.000 0.000 39.781
June 720.000 44.373 0.000 0.000 44.373
July 744.000 47.365 0.000 0.000 47.365
August 744.000 45.493 0.000 0.000 45.493
September 720.000 42.285 0.000 0.000 42.285
October 744.000 37.218 0.000 0.000 37.218
November 639.688 24.568 12.833 0.233 25.616
December 471.182 13.318 64.187 1.268 16.727
           
Annual Sum or Average 7744.669 367.819 185.412 3.605 381.903
Minimum of Months 425.701 10.411 0.000 0.000 15.153
Maximum of Months 744.000 47.365 64.187 1.268 47.365



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 439.949 18.137 85.667 2.269 23.996
February 465.546 21.477 47.767 1.772 26.103
March 596.567 27.725 40.524 1.340 34.688
April 690.861 36.691 0.250 0.002 37.107
May 744.000 50.987 0.000 0.000 50.987
June 720.000 56.184 0.000 0.000 56.184
July 744.000 60.864 0.000 0.000 60.864
August 744.000 59.366 0.000 0.000 59.366
September 720.000 55.538 0.000 0.000 55.538
October 744.000 50.380 0.000 0.000 50.380
November 620.480 35.123 21.542 0.653 36.772
December 496.242 22.556 72.917 2.368 25.716
           
Annual Sum or Average 7725.644 495.027 268.665 8.404 517.699
Minimum of Months 439.949 18.137 0.000 0.000 23.996
Maximum of Months 744.000 60.864 85.667 2.368 60.864



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 493.752 15.440 77.950 0.650 16.090
February 491.454 17.365 46.875 0.629 17.994
March 609.237 21.408 53.927 0.575 21.983
April 697.688 28.091 0.000 0.000 28.091
May 744.000 39.096 0.000 0.000 39.096
June 720.000 43.589 0.000 0.000 43.589
July 744.000 46.805 0.000 0.000 46.805
August 744.000 45.656 0.000 0.000 45.656
September 720.000 43.488 0.000 0.000 43.488
October 744.000 40.061 0.000 0.000 40.061
November 648.688 28.829 20.375 0.201 29.030
December 543.810 18.766 61.058 0.760 19.526
           
Annual Sum or Average 7900.629 388.595 260.185 2.814 391.409
Minimum of Months 491.454 15.440 0.000 0.000 16.090
Maximum of Months 744.000 46.805 77.950 0.760 46.805



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 459.647 16.783 68.875 1.482 21.647
February 481.302 19.682 42.125 1.250 22.915
March 610.169 25.079 38.732 0.883 28.067
April 697.474 33.994 0.000 0.000 34.382
May 744.000 47.077 0.000 0.000 47.077
June 720.000 52.508 0.000 0.000 52.508
July 744.000 56.366 0.000 0.000 56.366
August 744.000 54.352 0.000 0.000 54.352
September 720.000 51.570 0.000 0.000 51.570
October 744.000 46.619 0.000 0.000 46.619
November 628.217 32.412 18.750 0.449 33.543
December 500.993 19.849 57.625 1.635 23.489
           
Annual Sum or Average 7793.802 456.292 226.107 5.699 472.537
Minimum of Months 459.647 16.783 0.000 0.000 21.647
Maximum of Months 744.000 56.366 68.875 1.635 56.366



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 389.650 13.345 102.439 2.399 21.372
February 441.637 18.296 61.171 1.857 22.980
March 588.625 26.272 57.412 1.507 31.725
April 690.692 36.269 3.250 0.022 36.334
May 744.000 51.084 0.000 0.000 51.084
June 720.000 56.439 0.000 0.000 56.439
July 744.000 61.072 0.000 0.000 61.072
August 744.000 59.241 0.000 0.000 59.241
September 720.000 54.755 0.000 0.000 54.755
October 744.000 47.803 0.000 0.000 47.803
November 607.330 31.082 25.125 0.655 32.867
December 447.570 17.834 77.458 2.414 23.916
           
Annual Sum or Average 7581.504 473.491 326.855 8.853 499.587
Minimum of Months 389.650 13.345 0.000 0.000 21.372
Maximum of Months 744.000 61.072 102.439 2.414 61.072



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 424.585 10.859 103.921 0.990 11.912
February 465.798 14.380 58.962 0.817 15.260
March 595.604 20.094 60.143 0.667 20.762
April 697.494 27.813 0.000 0.000 27.813
May 744.000 39.371 0.000 0.000 39.371
June 720.000 44.038 0.000 0.000 44.038
July 744.000 47.226 0.000 0.000 47.226
August 744.000 45.753 0.000 0.000 45.753
September 720.000 42.949 0.000 0.000 42.949
October 744.000 37.784 0.000 0.000 37.784
November 634.453 25.061 24.667 0.248 25.309
December 487.137 14.231 84.619 1.098 15.371
           
Annual Sum or Average 7721.071 369.558 332.313 3.819 373.547
Minimum of Months 424.585 10.859 0.000 0.000 11.912
Maximum of Months 744.000 47.226 103.921 1.098 47.226



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 402.116 12.320 88.375 1.839 17.510
February 465.522 16.775 52.232 1.482 20.328
March 596.989 23.783 43.362 0.962 26.857
April 697.599 33.707 0.000 0.000 34.095
May 744.000 47.261 0.000 0.000 47.261
June 720.000 52.833 0.000 0.000 52.833
July 744.000 56.665 0.000 0.000 56.665
August 744.000 54.375 0.000 0.000 54.375
September 720.000 51.015 0.000 0.000 51.015
October 744.000 44.462 0.000 0.000 44.462
November 622.113 28.812 22.250 0.503 30.046
December 451.162 15.504 79.583 2.096 19.653
           
Annual Sum or Average 7651.500 437.511 285.803 6.882 455.099
Minimum of Months 402.116 12.320 0.000 0.000 17.510
Maximum of Months 744.000 56.665 88.375 2.096 56.665



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.94
February 0.00 0.00 1.00
March 0.00 0.00 1.04
April 0.00 0.00 1.14
May 0.00 0.00 1.27
June 0.00 0.00 1.33
July 0.00 0.00 1.34
August 0.00 0.00 1.35
September 0.00 0.00 1.33
October 0.00 0.00 1.27
November 0.00 0.00 1.14
December 0.00 0.00 1.00
       
Annual Sum or Average 0.00 0.00 1.18
Minimum of Months 0.00 0.00 0.94
Maximum of Months 0.00 0.00 1.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.16
March 0.00 0.00 0.17
April 0.00 0.00 0.23
May 0.00 0.00 0.33
June 0.00 0.00 0.39
July 0.00 0.00 0.40
August 0.00 0.00 0.41
September 0.00 0.00 0.40
October 0.00 0.00 0.36
November 0.00 0.00 0.27
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.14
February 0.00 0.00 0.19
March 0.00 0.00 0.21
April 0.00 0.00 0.29
May 0.00 0.00 0.41
June 0.00 0.00 0.49
July 0.00 0.00 0.50
August 0.00 0.00 0.50
September 0.00 0.00 0.49
October 0.00 0.00 0.42
November 0.00 0.00 0.30
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.14
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.14
March 0.00 0.00 0.19
April 0.00 0.00 0.28
May 0.00 0.00 0.41
June 0.00 0.00 0.47
July 0.00 0.00 0.49
August 0.00 0.00 0.48
September 0.00 0.00 0.45
October 0.00 0.00 0.37
November 0.00 0.00 0.24
December 0.00 0.00 0.12
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.11
March 0.00 0.00 0.14
April 0.00 0.00 0.21
May 0.00 0.00 0.33
June 0.00 0.00 0.40
July 0.00 0.00 0.41
August 0.00 0.00 0.40
September 0.00 0.00 0.38
October 0.00 0.00 0.31
November 0.00 0.00 0.20
December 0.00 0.00 0.10
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.14
March 0.00 0.00 0.18
April 0.00 0.00 0.28
May 0.00 0.00 0.41
June 0.00 0.00 0.49
July 0.00 0.00 0.50
August 0.00 0.00 0.49
September 0.00 0.00 0.46
October 0.00 0.00 0.38
November 0.00 0.00 0.24
December 0.00 0.00 0.12
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.43
June 0.00 0.00 0.49
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.45
November 0.00 0.00 0.33
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.20
March 0.00 0.00 0.21
April 0.00 0.00 0.28
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.43
September 0.00 0.00 0.43
October 0.00 0.00 0.39
November 0.00 0.00 0.30
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.51
October 0.00 0.00 0.45
November 0.00 0.00 0.34
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.43
June 0.00 0.00 0.50
July 0.00 0.00 0.52
August 0.00 0.00 0.50
September 0.00 0.00 0.47
October 0.00 0.00 0.40
November 0.00 0.00 0.28
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.15
March 0.00 0.00 0.18
April 0.00 0.00 0.26
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.42
September 0.00 0.00 0.40
October 0.00 0.00 0.35
November 0.00 0.00 0.24
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.28
December 0.00 0.00 0.15
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.50
June 0.00 0.00 0.58
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.50
November 0.00 0.00 0.36
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.21
March 0.00 0.00 0.23
April 0.00 0.00 0.32
May 0.00 0.00 0.43
June 0.00 0.00 0.50
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.50
October 0.00 0.00 0.45
November 0.00 0.00 0.33
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.58
October 0.00 0.00 0.51
November 0.00 0.00 0.36
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.20
March 0.00 0.00 0.26
April 0.00 0.00 0.36
May 0.00 0.00 0.50
June 0.00 0.00 0.58
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.56
October 0.00 0.00 0.47
November 0.00 0.00 0.32
December 0.00 0.00 0.18
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.12
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.31
May 0.00 0.00 0.43
June 0.00 0.00 0.51
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.42
November 0.00 0.00 0.29
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.12
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.19
March 0.00 0.00 0.25
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.48
November 0.00 0.00 0.32
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:00

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1107.97 824.91
February 0.00 0.00 1098.37 738.63
March 0.00 0.00 1059.98 789.19
April 0.00 0.00 1009.96 727.69
May 0.00 0.00 950.88 707.95
June 0.00 0.00 908.25 654.40
July 0.00 0.00 889.84 662.51
August 0.00 0.00 898.32 668.83
September 0.00 0.00 936.80 674.97
October 0.00 0.00 991.13 737.93
November 0.00 0.00 1047.26 754.56
December 0.00 0.00 1090.83 812.16
         
Annual Sum or Average 0.00 0.00 998.58 8753.73
Minimum of Months 0.00 0.00 889.84 654.40
Maximum of Months 0.00 0.00 1107.97 824.91