Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
Tabular Output Report in Format: HTML
Building: MF+CZ1AT+USA_HI_Honolulu.Intl.AP.911820+gasfurnace+crawlspace+IECC_2015
Environment: ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820
Simulation Timestamp: 2019-02-14 08:27:57
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 890472.11 | 22.83 | 41.21 |
Net Site Energy | 890472.11 | 22.83 | 41.21 |
Total Source Energy | 2074404.80 | 53.18 | 95.99 |
Net Source Energy | 2074404.80 | 53.18 | 95.99 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 36.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 184967.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 261700.64 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 32867.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 193993.07 | 0.00 | 0.00 | 0.00 | 374778.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 532469.05 | 358003.06 | 0.00 | 0.00 | 0.00 | 374778.00 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 36.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 184967.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9418.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4809.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 3888.48 | 79268.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 67443.41 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 143183.64 | 17261.25 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 59304.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 32867.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 193993.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374778.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.08 | 8.98 | 0.00 | 0.00 | 0.00 | 17.34 |
Other | 12.11 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 24.64 | 16.57 | 0.00 | 0.00 | 0.00 | 17.34 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 5.58 | 4.97 | 0.00 | 0.00 | 0.00 | 9.61 |
Other | 6.71 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 13.65 | 9.18 | 0.00 | 0.00 | 0.00 | 9.61 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 532469.048 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 532469.048 | 100.00 |
Total On-Site and Utility Electric Sources | 532469.048 | 100.00 |
Total Electricity End Uses | 532469.048 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 374778.00 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 374778.00 | 100.00 |
Total Water End Uses | 374778.00 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 44.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2303.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27 |
RunPeriod | ANNUAL |
Weather File | Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Latitude [deg] | 21.32 |
Longitude [deg] | -157.9 |
Elevation [ft] | 6.56 |
Time Zone | -10.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19407.54 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 4.4634 |
Total | 39005.17 | 286495.20 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 2.4729 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6659 | 600.28 | 4.4634 | |||
Unconditioned Total | 17395.21 | 102755.82 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 04-SEP-18:15 | 14-JAN-17:00 | - | - | - | 01-JAN-08:45 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 40.96 | 43.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 143.74 | 0.00 | 0.00 | 0.00 | 1.36 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 109.06 | 187.50 | 0.00 | 0.00 | 0.00 | 1.36 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 45.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 0.52 | 13.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 27.71 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 22.66 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 9.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 143.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 39.89 | 0.00 | 0.00 | 0.00 |
Cooling | 585793.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 828805.92 | 177746.94 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 104091.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 210288.49 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1686329.48 | 388075.32 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38.35 | 8.23 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9.73 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 78.03 | 17.96 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38.35 | 8.23 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9.73 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 78.03 | 17.96 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 61.16 | 0.00 | 61.16 | Wetbulb [F] | 374.03 | 320.00 |
HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 89.96 | 12.78 | 73.94 | Wetbulb [F] | 1318.96 | 60.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.219 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.219 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.501 | 0.219 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.501 | 0.219 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.501 | 0.219 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23170.72 | 17834.48 | 5336.24 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8358.62 | 5804.53 | 2554.09 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9568.81 | 6749.66 | 2819.15 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13183.14 | 9599.13 | 3584.00 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8276.66 | 5749.79 | 2526.87 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9618.01 | 6788.88 | 2829.13 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12944.60 | 9542.98 | 3401.62 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8298.76 | 5852.65 | 2446.11 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9405.79 | 6706.33 | 2699.46 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12792.94 | 9433.50 | 3359.44 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8261.35 | 5821.35 | 2440.00 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9449.29 | 6741.71 | 2707.59 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15049.52 | 11121.12 | 3928.40 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10375.22 | 7399.71 | 2975.51 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11371.43 | 8152.44 | 3218.99 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15069.24 | 11137.29 | 3931.95 | 0.74 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10369.52 | 7408.17 | 2961.35 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11389.54 | 8167.03 | 3222.51 | 0.72 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.8 | 3.31 | 11.30 | 11.98 | 11.57 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.46 | 11.81 | 12.53 | 12.39 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.44 | 11.73 | 12.45 | 12.27 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.39 | 11.58 | 12.28 | 12.01 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.7 | 3.46 | 11.81 | 12.53 | 12.39 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.44 | 11.73 | 12.44 | 12.26 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.38 | 11.52 | 12.21 | 11.91 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.44 | 11.73 | 12.45 | 12.27 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.42 | 11.68 | 12.39 | 12.18 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.38 | 11.52 | 12.21 | 11.91 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.44 | 11.74 | 12.45 | 12.28 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.42 | 11.68 | 12.39 | 12.17 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.37 | 11.51 | 12.20 | 11.89 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.42 | 11.68 | 12.39 | 12.18 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.42 | 11.65 | 12.36 | 12.14 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.2 | 3.37 | 11.51 | 12.20 | 11.89 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.42 | 11.67 | 12.38 | 12.16 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.42 | 11.65 | 12.36 | 12.13 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 2963.27 | 0.80 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 800.70 | 302.02 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 224.66 | 84.74 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 267.87 | 101.04 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 399.66 | 150.75 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 222.68 | 83.99 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 269.71 | 101.73 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 404.42 | 152.55 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 232.20 | 87.59 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 270.62 | 102.08 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 399.92 | 150.85 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 230.65 | 87.00 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 272.32 | 102.72 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 472.87 | 178.36 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 298.74 | 112.68 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 331.73 | 125.13 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 473.66 | 178.66 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 299.85 | 113.10 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 332.42 | 125.39 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 18805.20 | 18805.20 | 15.66 | 800.701 | 800.701 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00869 | 86.89 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5276.58 | 5276.58 | 4.40 | 224.661 | 224.661 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00996 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6291.58 | 6291.58 | 5.24 | 267.873 | 267.873 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 74.98 | 74.98 | 0.00968 | 86.06 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9386.55 | 9386.55 | 7.82 | 399.662 | 399.662 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00926 | 86.89 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5230.07 | 5230.07 | 4.36 | 222.680 | 222.680 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00999 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6334.75 | 6334.75 | 5.28 | 269.712 | 269.712 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:30:00 | 74.98 | 74.98 | 0.00967 | 86.06 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9498.63 | 9498.63 | 7.91 | 404.422 | 404.422 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00900 | 86.89 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5453.85 | 5453.85 | 4.54 | 232.203 | 232.203 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00959 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6356.22 | 6356.22 | 5.29 | 270.621 | 270.621 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 74.98 | 74.98 | 0.00934 | 86.54 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9392.92 | 9392.92 | 7.82 | 399.921 | 399.921 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00902 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5417.49 | 5417.49 | 4.51 | 230.655 | 230.655 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00960 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6396.06 | 6396.06 | 5.33 | 272.318 | 272.318 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 10:45:00 | 74.98 | 74.98 | 0.00933 | 86.54 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7807.31 | 7807.31 | 6.50 | 332.419 | 332.419 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00947 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7791.06 | 7791.06 | 6.49 | 331.728 | 331.728 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00948 | 86.41 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11106.00 | 11106.00 | 9.25 | 472.874 | 472.874 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00909 | 86.89 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7042.51 | 7042.51 | 5.87 | 299.849 | 299.849 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00958 | 84.98 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7016.30 | 7016.30 | 5.84 | 298.735 | 298.735 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00958 | 85.46 | 0.01435 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11124.38 | 11124.38 | 9.27 | 473.657 | 473.657 | HONOLULU INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00909 | 86.89 | 0.01435 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 61.16 | 0.01152 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 457.74 | 457.74 | 0.38 | 8.334 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01183 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1069.62 | 1069.62 | 0.89 | 19.474 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:15:00 | 72.00 | 72.00 | 0.01144 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1083.89 | 1083.89 | 0.90 | 19.734 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:15:00 | 72.00 | 72.00 | 0.01143 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 563.14 | 563.14 | 0.47 | 10.253 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01172 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1078.91 | 1078.91 | 0.90 | 19.644 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:15:00 | 72.00 | 72.00 | 0.01143 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 511.87 | 511.87 | 0.43 | 9.319 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01182 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 114.50 | 114.50 | 0.10 | 2.085 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01240 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 739.15 | 739.15 | 0.62 | 13.457 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01156 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 745.93 | 745.93 | 0.62 | 13.581 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01156 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 159.89 | 159.89 | 0.13 | 2.911 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01234 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 742.46 | 742.46 | 0.62 | 13.518 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01156 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1267.94 | 1267.94 | 1.06 | 23.085 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:15:00 | 72.00 | 72.00 | 0.01128 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1266.23 | 1266.23 | 1.05 | 23.054 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:30:00 | 72.00 | 72.00 | 0.01126 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1210.02 | 1210.02 | 1.01 | 22.031 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01117 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 682.42 | 682.42 | 0.57 | 12.425 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01160 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 666.79 | 666.79 | 0.56 | 12.140 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 15:00:00 | 72.00 | 72.00 | 0.01162 | 61.16 | 0.01152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1270.99 | 1270.99 | 1.06 | 23.141 | 44.995 | HONOLULU INTL ARPT ANN HTG 99.6% CONDNS DB | 2/21 11:15:00 | 72.00 | 72.00 | 0.01128 | 61.16 | 0.01152 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 | 800.70 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 | 224.66 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 | 267.87 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 | 399.66 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 | 222.68 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 | 269.71 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 | 404.42 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 | 232.20 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 | 270.62 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 | 399.92 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 | 230.65 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 | 272.32 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 472.87 | 472.87 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 298.74 | 298.74 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 331.73 | 331.73 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 473.66 | 473.66 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 299.85 | 299.85 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 332.42 | 332.42 | 44.99 | 44.99 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4090.00 | 1125.75 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7956.75 | 1763.50 | 1669.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8042.25 | 1800.50 | 1627.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7949.00 | 2448.50 | 2235.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7803.00 | 1923.25 | 1815.75 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7950.25 | 1860.50 | 1683.50 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8125.25 | 824.50 | 753.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8047.00 | 243.50 | 227.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8089.75 | 547.25 | 478.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8057.25 | 922.50 | 839.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7909.00 | 299.00 | 278.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8028.00 | 579.50 | 508.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8151.25 | 1024.50 | 904.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8164.00 | 998.50 | 879.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8147.50 | 1395.50 | 1261.25 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8112.25 | 894.25 | 836.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8160.00 | 810.75 | 758.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8112.00 | 1468.25 | 1321.50 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 8283.75 | 2854.25 | 2303.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 2.50 | 0.00 | 2.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 40.50 | 0.00 | 40.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 34.50 | 0.00 | 34.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.50 | 0.00 | 0.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 6.50 | 0.00 | 6.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 44.75 | 0.00 | 44.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.153 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.153 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.076 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.076 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.076 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.076 | 0.000 | 0.264 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.174 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.153 | 0.000 | 0.264 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.153 | 0.000 | 0.264 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.174 | 0.000 | 0.264 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1878 |
Defaulted Fields | 500 |
Fields with Defaults | 4912 |
Autosized Fields | 288 |
Autosizable Fields | 396 |
Autocalculated Fields | 98 |
Autocalculatable Fields | 286 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
Electricity:Building | 89593.23 | 7014.56 | 02-JAN-03:15 | 16905.04 | 01-JAN-20:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4977.40 | 389.70 | 02-JAN-03:15 | 939.17 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 76645.77 | 6518.84 | 02-JAN-04:15 | 12687.62 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
dishwasher:InteriorEquipment:Electricity | 2758.31 | 25.25 | 02-JAN-03:15 | 880.12 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1408.53 | 13.53 | 02-JAN-02:15 | 381.47 | 01-JAN-09:15 |
gas_dryer:InteriorEquipment:Electricity | 1138.84 | 5.81 | 02-JAN-03:15 | 291.20 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
gas_mels:InteriorEquipment:Electricity | 41935.01 | 3663.85 | 01-JAN-09:15 | 7086.44 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 17368.96 | 1517.52 | 01-JAN-09:15 | 2935.11 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4258.10 | 362.16 | 02-JAN-04:15 | 704.87 | 01-JAN-20:15 |
Fans:Electricity | 9626.09 | 116.43 | 08-MAR-04:15 | 2276.36 | 04-SEP-17:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
ElectricityPurchased:Plant | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
Cogeneration:ElectricityPurchased | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
ElectricityNet:Plant | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
Cogeneration:ElectricityNet | 155947.27 | 8112.59 | 12-FEB-03:15 | 31942.29 | 04-SEP-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 63798.71 | 599.40 | 12-FEB-02:30 | 15991.42 | 03-SEP-16:15 |
General:Fans:Electricity | 9626.09 | 116.43 | 08-MAR-04:15 | 2276.36 | 04-SEP-17:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 54172.62 | 420.64 | 12-FEB-07:00 | 13722.67 | 03-SEP-16:15 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 3580.03 | 2644.47 | 02-JAN-03:15 | 187371.19 | 14-JAN-18:00 |
Gas:Building | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
gas_dryer:InteriorEquipment:Gas | 792.69 | 403.80 | 02-JAN-03:15 | 20254.25 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Gas | 674.43 | 651.88 | 01-JAN-02:15 | 27685.38 | 01-JAN-17:15 |
gas_mels:InteriorEquipment:Gas | 172.61 | 1507.04 | 01-JAN-09:15 | 2914.85 | 01-JAN-20:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Plant | 1939.93 | 0.00 | 01-JAN-00:15 | 145133.87 | 21-JAN-08:45 |
WaterSystems:Gas | 1939.93 | 0.00 | 01-JAN-00:15 | 145133.87 | 21-JAN-08:45 |
Water Heater:WaterSystems:Gas | 1939.93 | 0.00 | 01-JAN-00:15 | 145133.87 | 21-JAN-08:45 |
Gas:HVAC | 0.37 | 0.00 | 01-JAN-00:15 | 11300.60 | 12-FEB-07:00 |
Heating:Gas | 0.37 | 0.00 | 01-JAN-00:15 | 11300.60 | 12-FEB-07:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
Water:Plant | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
WaterSystems:Water | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
MainsWater:Plant | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
WaterSystems:MainsWater | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
Domestic Hot Water:WaterSystems:MainsWater | 50107.88 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-08:45 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
PlantLoopHeatingDemand:Plant | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
WaterSystems:PlantLoopHeatingDemand | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1460311.60 | 16852.63 | 08-MAR-03:00 | 351346.97 | 02-SEP-17:30 |
EnergyTransfer:Building | 568448.03 | 7349.14 | 08-FEB-04:30 | 144796.44 | 02-SEP-17:30 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 33.96 | 0.00 | 01-JAN-00:15 | 10401.76 | 12-FEB-07:00 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 568414.07 | 6257.78 | 12-FEB-07:15 | 144796.44 | 02-SEP-17:30 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103318.91 | 6257.78 | 12-FEB-07:15 | 18515.69 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103318.91 | 6257.78 | 12-FEB-07:15 | 18515.69 | 05-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21474.33 | 0.00 | 01-JAN-05:00 | 6134.38 | 13-DEC-15:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.14 | 0.00 | 01-JAN-00:15 | 240.27 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21474.18 | 0.00 | 01-JAN-05:00 | 6134.38 | 13-DEC-15:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27348.65 | 0.00 | 01-JAN-02:45 | 7261.66 | 15-DEC-12:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5.12 | 0.00 | 01-JAN-00:15 | 1124.61 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27343.53 | 0.00 | 01-JAN-02:45 | 7261.66 | 15-DEC-12:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23117.44 | 0.00 | 01-JAN-02:45 | 9266.72 | 04-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6.42 | 0.00 | 01-JAN-00:15 | 1128.16 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23111.03 | 0.00 | 01-JAN-02:45 | 9266.72 | 04-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19126.07 | 0.00 | 01-JAN-04:45 | 5401.49 | 03-SEP-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.44 | 0.00 | 01-JAN-00:15 | 362.46 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19125.63 | 0.00 | 01-JAN-04:45 | 5401.49 | 03-SEP-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25039.80 | 0.00 | 01-JAN-02:45 | 7120.84 | 12-JUL-10:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5.57 | 0.00 | 01-JAN-00:15 | 1148.88 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25034.23 | 0.00 | 01-JAN-02:45 | 7120.84 | 12-JUL-10:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29080.16 | 0.00 | 05-JAN-05:00 | 9404.75 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.09 | 0.00 | 01-JAN-00:15 | 241.06 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29080.07 | 0.00 | 05-JAN-05:00 | 9404.75 | 05-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 25338.59 | 0.00 | 16-JAN-05:00 | 6308.26 | 13-DEC-15:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 25338.59 | 0.00 | 16-JAN-05:00 | 6308.26 | 13-DEC-15:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31165.21 | 0.00 | 05-JAN-05:00 | 7366.70 | 15-DEC-12:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.34 | 0.00 | 01-JAN-00:15 | 427.05 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31164.87 | 0.00 | 05-JAN-05:00 | 7366.70 | 15-DEC-12:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26828.47 | 0.00 | 05-JAN-05:00 | 9131.55 | 04-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.57 | 0.00 | 01-JAN-00:15 | 417.12 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26827.90 | 0.00 | 05-JAN-05:00 | 9131.55 | 04-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 22994.97 | 0.00 | 16-JAN-04:45 | 5576.91 | 03-SEP-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 22994.97 | 0.00 | 16-JAN-04:45 | 5576.91 | 03-SEP-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28879.28 | 0.00 | 05-JAN-05:00 | 7181.07 | 12-JUL-10:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.44 | 0.00 | 01-JAN-00:15 | 467.37 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28878.84 | 0.00 | 05-JAN-05:00 | 7181.07 | 12-JUL-10:15 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32587.99 | 0.00 | 01-JAN-04:15 | 8295.30 | 01-OCT-14:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 3.45 | 0.00 | 01-JAN-00:15 | 1194.57 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 32584.54 | 0.00 | 01-JAN-04:15 | 8295.30 | 01-OCT-14:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34078.15 | 0.00 | 01-JAN-04:30 | 8567.68 | 11-OCT-14:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 3.18 | 0.00 | 01-JAN-00:15 | 1169.77 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 34074.97 | 0.00 | 01-JAN-04:30 | 8567.68 | 11-OCT-14:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32107.19 | 0.00 | 01-JAN-04:30 | 10855.72 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 3.70 | 0.00 | 01-JAN-00:15 | 1115.76 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 32103.49 | 0.00 | 01-JAN-04:30 | 10855.72 | 05-SEP-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 26889.39 | 0.00 | 07-JAN-04:30 | 7353.83 | 03-SEP-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.12 | 0.00 | 01-JAN-00:15 | 180.60 | 12-FEB-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 26889.27 | 0.00 | 07-JAN-04:30 | 7353.83 | 03-SEP-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 28410.47 | 0.00 | 07-JAN-04:30 | 7382.85 | 11-OCT-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.06 | 0.00 | 01-JAN-00:15 | 176.29 | 12-FEB-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 28410.41 | 0.00 | 07-JAN-04:30 | 7382.85 | 11-OCT-15:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30662.94 | 0.00 | 01-JAN-04:30 | 10840.49 | 05-SEP-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4.31 | 0.00 | 01-JAN-00:15 | 1157.74 | 12-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30658.63 | 0.00 | 01-JAN-04:30 | 10840.49 | 05-SEP-17:30 |
EnergyTransfer:Plant | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
WaterSystems:EnergyTransfer | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 77059.75 | 727.41 | 19-JUL-02:15 | 18732.55 | 15-JAN-08:15 |
EnergyTransfer:HVAC | 814803.82 | 8555.20 | 08-MAR-04:30 | 198867.27 | 04-SEP-17:30 |
HeatingCoils:EnergyTransfer | 29.44 | 0.00 | 01-JAN-00:15 | 9040.48 | 12-FEB-07:00 |
CoolingCoils:EnergyTransfer | 814774.38 | 7422.44 | 12-FEB-07:15 | 198867.27 | 04-SEP-17:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8604.16 | 0.000 | 0.000 | 2874.096 | 2456.001 | 14464.809 | 8500.780 | 0.000 | 2536.907 | 74737.400 | 0.000 | -1330.42 | 0.000 | -920.61 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.143 | -1788.32 | 0.000 | 0.000 | 2875.618 | 2456.001 | 14464.809 | 3530.243 | 0.000 | 2398.222 | 0.007 | 0.000 | -535.67 | 0.000 | -876.20 | -2838.92 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 5.117 | -2277.11 | 0.000 | 0.000 | 2878.911 | 2456.001 | 14464.809 | 10385.263 | 0.000 | 2532.619 | 0.003 | 0.000 | -1280.83 | 0.000 | -896.05 | -3202.28 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 6.419 | -1924.63 | 0.000 | 0.000 | 2879.791 | 2456.001 | 14464.809 | 6979.023 | 0.000 | 2536.522 | 0.000 | 0.000 | -1312.49 | 0.000 | -889.92 | -4009.16 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.437 | -1592.75 | 0.000 | 0.000 | 2875.908 | 2456.001 | 14464.809 | 1965.545 | 0.000 | 2398.541 | 0.000 | 0.000 | -531.44 | 0.000 | -874.42 | -3629.63 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 5.570 | -2084.80 | 0.000 | 0.000 | 2879.278 | 2456.001 | 14464.809 | 8853.490 | 0.000 | 2536.203 | 0.000 | 0.000 | -1264.21 | 0.000 | -895.02 | -4001.82 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.095 | -2421.72 | 0.000 | 0.000 | 2874.921 | 2456.001 | 14464.809 | 8405.019 | 0.000 | 1876.756 | 1200.056 | 0.000 | -1445.11 | 0.000 | -752.45 | -0.01 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.000 | -2110.15 | 0.000 | 0.000 | 2873.986 | 2456.001 | 14464.809 | 3488.513 | 0.000 | 1739.732 | 1616.654 | 0.000 | -580.88 | 0.000 | -720.07 | -0.04 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.341 | -2595.35 | 0.000 | 0.000 | 2874.844 | 2456.001 | 14464.809 | 10263.556 | 0.000 | 1874.258 | 1378.132 | 0.000 | -1394.36 | 0.000 | -752.57 | -0.01 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.573 | -2234.17 | 0.000 | 0.000 | 2875.157 | 2456.001 | 14464.809 | 6892.026 | 0.000 | 1876.777 | 447.241 | 0.000 | -1433.43 | 0.000 | -751.17 | -0.07 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.000 | -1914.98 | 0.000 | 0.000 | 2874.023 | 2456.001 | 14464.809 | 1936.812 | 0.000 | 1739.769 | 818.115 | 0.000 | -574.51 | 0.000 | -719.84 | -0.20 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 0.441 | -2404.98 | 0.000 | 0.000 | 2875.078 | 2456.001 | 14464.809 | 8742.401 | 0.000 | 1876.747 | 590.243 | 0.000 | -1374.44 | 0.000 | -752.26 | -0.02 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3.451 | -2713.58 | 0.000 | 0.000 | 2876.800 | 2456.001 | 14464.809 | 8637.261 | 0.000 | 2507.419 | 3962.602 | 0.000 | -1402.48 | 0.000 | -921.15 | -0.51 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3.181 | -2837.70 | 0.000 | 0.000 | 2876.679 | 2456.001 | 14464.809 | 10174.078 | 0.000 | 2506.956 | 3931.883 | 0.000 | -1416.77 | 0.000 | -921.68 | -0.11 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3.704 | -2673.50 | 0.000 | 0.000 | 2876.897 | 2456.001 | 14464.809 | 8322.422 | 0.000 | 2507.607 | 3855.517 | 0.000 | -1463.95 | 0.000 | -919.54 | -0.03 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 0.125 | -2239.29 | 0.000 | 0.000 | 2874.750 | 2456.001 | 14464.809 | 1898.193 | 0.000 | 2371.281 | 4304.729 | 0.000 | -586.39 | 0.000 | -894.08 | -0.03 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 0.056 | -2365.96 | 0.000 | 0.000 | 2874.681 | 2456.001 | 14464.809 | 3452.638 | 0.000 | 2371.287 | 4277.171 | 0.000 | -591.50 | 0.000 | -894.61 | -0.08 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 4.313 | -2553.18 | 0.000 | 0.000 | 2877.114 | 2456.001 | 14464.809 | 6794.027 | 0.000 | 2507.710 | 3928.789 | 0.000 | -1456.17 | 0.000 | -917.95 | -0.03 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 44123.668 | 0.000 | 0.000 | 0.000 | 0.000 | -148.54 | -43975.13 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5545.346 | 54368.000 | 0.000 | 0.000 | 0.000 | -59913.35 | -0.49 |
Total Facility | 0.000 | 0.000 | 33.965 | -47336.34 | 0.000 | 0.000 | 51768.530 | 44208.020 | 260366.561 | 119221.288 | 0.000 | 90364.327 | 159416.540 | 0.000 | -19975.06 | 0.000 | -75331.47 | -61658.56 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 05-SEP-17:19 | 0.00 | 0.00 | 0.00 | -1.5 | 0.00 | 0.00 | 262.58 | 535.87 | 2748.57 | 4760.98 | 0.00 | 1308.07 | 8909.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13-DEC-15:34 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.33 | 178.62 | 1668.09 | 1621.10 | 0.00 | 742.35 | 1815.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15-DEC-12:08 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.68 | 103.05 | 1597.22 | 3813.59 | 0.00 | 865.40 | 767.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 04-SEP-17:25 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.37 | 535.87 | 2748.57 | 4893.32 | 0.00 | 1282.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -457.0 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 03-SEP-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.05 | 721.37 | 2684.82 | 257.08 | 0.00 | 1001.27 | 312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-JUL-10:15 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.81 | 103.05 | 1526.07 | 4164.26 | 0.00 | 975.23 | 250.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 05-SEP-17:23 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.35 | 535.87 | 2748.57 | 4734.39 | 0.00 | 907.30 | 215.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 13-DEC-15:34 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.53 | 178.62 | 1668.09 | 1611.43 | 0.00 | 558.21 | 2180.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15-DEC-12:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.60 | 103.05 | 1597.22 | 3677.25 | 0.00 | 613.43 | 1261.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 04-SEP-17:20 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.36 | 535.87 | 2748.57 | 4864.39 | 0.00 | 885.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -166.1 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 03-SEP-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.05 | 721.37 | 2684.82 | 259.42 | 0.00 | 737.09 | 749.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-JUL-10:23 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.02 | 103.05 | 1526.07 | 3753.53 | 0.00 | 720.19 | 990.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 01-OCT-14:34 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.17 | 103.05 | 1569.96 | 1713.41 | 0.00 | 1511.88 | 3284.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 11-OCT-13:53 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 113.14 | 103.05 | 1536.52 | 2718.58 | 0.00 | 965.29 | 3136.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 05-SEP-17:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.36 | 535.87 | 2748.57 | 4686.62 | 0.00 | 1309.46 | 1312.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 03-SEP-18:18 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.80 | 721.37 | 2684.82 | 198.37 | 0.00 | 940.29 | 2390.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 11-OCT-14:53 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.18 | 103.05 | 1538.41 | 1251.82 | 0.00 | 1145.34 | 3231.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 05-SEP-17:23 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.36 | 535.87 | 2748.57 | 4707.66 | 0.00 | 1309.46 | 1275.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-SEP-17:25 | 0.00 | 0.00 | 0.00 | -12.1 | 0.00 | 0.00 | 4736.94 | 9645.69 | 50003.80 | 35810.97 | 0.00 | 28166.81 | 31742.66 | 0.00 | 0.00 | 0.00 | -15229.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 240.27 | 0.00 | 0.00 | 0.00 | 526.30 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -467.2 | 0.00 | -1213.2 | -909.1 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1124.61 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1113.9 | 0.00 | -1269.1 | -1090.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1128.15 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1114.9 | 0.00 | -1269.1 | -1093.4 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 362.46 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -464.4 | 0.00 | -1213.2 | -1034.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1148.87 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1111.9 | 0.00 | -1269.1 | -1117.1 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 241.06 | 0.00 | 0.00 | 0.00 | 526.12 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.2 | 0.00 | -1008.2 | -409.7 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 427.05 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.8 | 0.00 | -1008.2 | -613.4 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 417.13 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1159.2 | 0.00 | -1008.2 | -599.1 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 467.38 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1153.6 | 0.00 | -1008.2 | -654.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1194.57 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.0 | 0.00 | -1274.5 | -1144.3 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1169.77 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1125.5 | 0.00 | -1274.5 | -1119.0 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1115.76 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1130.7 | 0.00 | -1274.5 | -1059.8 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12-FEB-07:15 | 0.00 | 0.00 | 180.61 | 0.00 | 0.00 | 0.00 | 464.77 | 343.51 | 1695.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -397.6 | 0.00 | -1131.4 | -1155.3 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12-FEB-07:15 | 0.00 | 0.00 | 176.29 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1695.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -336.8 | 0.00 | -1131.4 | -1211.8 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 12-FEB-07:00 | 0.00 | 0.00 | 1157.73 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1129.9 | 0.00 | -1274.5 | -1102.6 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 12-FEB-07:00 | -6283.9 | 0.52 | 10401.75 | -0.5 | 0.00 | 0.00 | 9376.81 | 6925.11 | 25887.94 | 0.00 | 0.00 | 2326.40 | 0.00 | 0.00 | -16620.4 | 0.00 | -25202.0 | -6811.7 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 800.701 | 2.00 | 2.00 | 1.00 | 44.9950 | 800.701 | 0.056 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 224.661 | 2.00 | 2.00 | 1.00 | 44.9950 | 224.661 | 0.200 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 267.873 | 2.00 | 2.00 | 1.00 | 44.9950 | 267.873 | 0.168 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 399.662 | 2.00 | 2.00 | 1.00 | 44.9950 | 399.662 | 0.113 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 222.680 | 2.00 | 2.00 | 1.00 | 44.9950 | 222.680 | 0.202 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.712 | 2.00 | 2.00 | 1.00 | 44.9950 | 269.712 | 0.167 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 404.422 | 2.00 | 2.00 | 1.00 | 44.9950 | 404.422 | 0.111 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 232.203 | 2.00 | 2.00 | 1.00 | 44.9950 | 232.203 | 0.194 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 270.621 | 2.00 | 2.00 | 1.00 | 44.9950 | 270.621 | 0.166 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 399.921 | 2.00 | 2.00 | 1.00 | 44.9950 | 399.921 | 0.113 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 230.655 | 2.00 | 2.00 | 1.00 | 44.9950 | 230.655 | 0.195 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 272.318 | 2.00 | 2.00 | 1.00 | 44.9950 | 272.318 | 0.165 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 472.874 | 2.00 | 2.00 | 1.00 | 44.9950 | 472.874 | 0.095 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 298.735 | 2.00 | 2.00 | 1.00 | 44.9950 | 298.735 | 0.151 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 331.728 | 2.00 | 2.00 | 1.00 | 44.9950 | 331.728 | 0.136 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 473.657 | 2.00 | 2.00 | 1.00 | 44.9950 | 473.657 | 0.095 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 299.849 | 2.00 | 2.00 | 1.00 | 44.9950 | 299.849 | 0.150 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 332.419 | 2.00 | 2.00 | 1.00 | 44.9950 | 332.419 | 0.135 | 1.000 | 44.9950 | 0.14 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 800.701 | 800.7013 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 224.661 | 224.6609 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 267.873 | 267.8735 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 399.662 | 399.6620 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 222.680 | 222.6797 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.712 | 269.7115 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 404.422 | 404.4224 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 232.203 | 232.2028 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 270.621 | 270.6213 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 399.921 | 399.9214 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 230.655 | 230.6546 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 272.318 | 272.3175 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 332.419 | 332.4194 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 331.728 | 331.7276 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 472.874 | 472.8742 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 299.849 | 299.8493 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 298.735 | 298.7353 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 473.657 | 473.6568 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 | 800.701 | 800.70 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 | 224.661 | 224.66 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 | 267.873 | 267.87 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 | 399.662 | 399.66 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 | 222.680 | 222.68 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 | 269.712 | 269.71 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 | 404.422 | 404.42 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 | 232.203 | 232.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 | 270.621 | 270.62 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 | 399.921 | 399.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 | 230.655 | 230.65 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 | 272.318 | 272.32 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 472.87 | 472.874 | 472.87 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 298.74 | 298.735 | 298.74 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 331.73 | 331.728 | 331.73 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 473.66 | 473.657 | 473.66 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 299.85 | 299.849 | 299.85 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 332.42 | 332.419 | 332.42 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Honolulu Intl Arpt HI USA TMY3 WMO#=911820 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 44.75 |
Number of hours not met | 44.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 0.37 | 0.00 | 0.00 | 0.00 |
Space Cooling | 54172.62 | 13285.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 9626.09 | 2239.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 1939.93 | 143635.97 | 0.00 | 0.00 |
Receptacle Equipment | 76645.77 | 11996.98 | 1639.73 | 43735.22 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 155947.27 | 3580.03 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 261700.64 | 532469.05 |
Natural Gas | 163973.19 | 358003.06 |
Additional | 0.00 | 0.00 |
Total | 425673.83 | 890472.11 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 1.39 |
Fans-Interior | 0.25 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1.97 |
Miscellaneous | 0.07 |
Subtotal | 4.00 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 1.46 |
Miscellaneous | 1.23 |
Subtotal | 2.69 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.96 |
Space Heating | 0.00 |
Space Cooling | 20.77 |
Fans-Interior | 3.69 |
Service Water Heating | 21.79 |
Receptacle Equipment | 47.80 |
Miscellaneous | 0.98 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 332.42 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 331.73 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 472.87 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 299.85 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 298.74 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 473.66 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 472.87 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 298.74 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 331.73 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 473.66 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 299.85 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 332.42 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 | 1.93 | 0.769699 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 | 0.696552 | 0.694436 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 | 0.797401 | 0.705381 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 | 1.10 | 0.728137 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 | 0.689721 | 0.694699 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 | 0.801501 | 0.705851 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 | 1.08 | 0.737217 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 | 0.691564 | 0.705244 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 | 0.783816 | 0.713000 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 | 1.07 | 0.737399 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 | 0.688446 | 0.704649 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 | 0.787441 | 0.713462 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 472.87 | 1.25 | 0.738968 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 298.74 | 0.864601 | 0.713210 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 331.73 | 0.947619 | 0.716923 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 473.66 | 1.26 | 0.739074 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 299.85 | 0.864127 | 0.714418 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 332.42 | 0.949128 | 0.717064 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 | 800.70 | 800.70 | 2963.27 | 1.93 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 | 224.66 | 224.66 | 2963.27 | 0.696552 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 | 267.87 | 267.87 | 2963.27 | 0.797401 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 | 399.66 | 399.66 | 2963.27 | 1.10 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 | 222.68 | 222.68 | 2963.27 | 0.689721 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 | 269.71 | 269.71 | 2963.27 | 0.801501 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 | 404.42 | 404.42 | 2963.27 | 1.08 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 | 232.20 | 232.20 | 2963.27 | 0.691564 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 | 270.62 | 270.62 | 2963.27 | 0.783816 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 | 399.92 | 399.92 | 2963.27 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 | 230.65 | 230.65 | 2963.27 | 0.688446 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 | 272.32 | 272.32 | 2963.27 | 0.787441 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 472.87 | 472.87 | 472.87 | 2963.27 | 1.25 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 298.74 | 298.74 | 298.74 | 2963.27 | 0.864601 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 331.73 | 331.73 | 331.73 | 2963.27 | 0.947619 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 473.66 | 473.66 | 473.66 | 2963.27 | 1.26 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 299.85 | 299.85 | 299.85 | 2963.27 | 0.864127 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 332.42 | 332.42 | 332.42 | 2963.27 | 0.949128 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 800.70 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 224.66 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 267.87 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 399.66 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 222.68 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 269.71 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 404.42 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 232.20 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 270.62 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 399.92 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 230.65 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 272.32 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 472.87 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 298.74 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 331.73 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 473.66 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 299.85 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 332.42 |
Design Size Nominal Capacity [Btu/h] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 2963.27 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 2963.27 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:27:57
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 132.534 | 0.000 | 0.000 | 132.534 |
February | 672.000 | 124.992 | 0.000 | 0.000 | 124.992 |
March | 744.000 | 136.761 | 0.000 | 0.000 | 136.761 |
April | 720.000 | 132.503 | 0.000 | 0.000 | 132.503 |
May | 744.000 | 145.312 | 0.000 | 0.000 | 145.312 |
June | 720.000 | 145.475 | 0.000 | 0.000 | 145.475 |
July | 744.000 | 157.391 | 0.000 | 0.000 | 157.391 |
August | 744.000 | 157.957 | 0.000 | 0.000 | 157.957 |
September | 720.000 | 156.069 | 0.000 | 0.000 | 156.069 |
October | 744.000 | 154.186 | 0.000 | 0.000 | 154.186 |
November | 720.000 | 143.425 | 0.000 | 0.000 | 143.425 |
December | 744.000 | 140.896 | 0.000 | 0.000 | 140.896 |
Annual Sum or Average | 8760.000 | 1727.499 | 0.000 | 0.000 | 1727.499 |
Minimum of Months | 672.000 | 124.992 | 0.000 | 0.000 | 124.992 |
Maximum of Months | 744.000 | 157.957 | 0.000 | 0.000 | 157.957 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 689.796 | 22.987 | 0.000 | 0.000 | 22.987 |
February | 619.967 | 22.300 | 1.000 | 0.004 | 22.304 |
March | 674.509 | 22.978 | 0.000 | 0.000 | 22.978 |
April | 714.264 | 22.364 | 0.000 | 0.000 | 22.364 |
May | 744.000 | 28.337 | 0.000 | 0.000 | 28.337 |
June | 720.000 | 29.979 | 0.000 | 0.000 | 29.979 |
July | 744.000 | 35.197 | 0.000 | 0.000 | 35.197 |
August | 744.000 | 35.714 | 0.000 | 0.000 | 35.714 |
September | 720.000 | 36.074 | 0.000 | 0.000 | 36.074 |
October | 744.000 | 35.365 | 0.000 | 0.000 | 35.365 |
November | 701.331 | 30.934 | 0.000 | 0.000 | 30.934 |
December | 724.312 | 28.224 | 0.000 | 0.000 | 28.224 |
Annual Sum or Average | 8540.179 | 350.451 | 1.000 | 0.004 | 350.455 |
Minimum of Months | 619.967 | 22.300 | 0.000 | 0.000 | 22.304 |
Maximum of Months | 744.000 | 36.074 | 1.000 | 0.004 | 36.074 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 630.533 | 27.678 | 0.000 | 0.000 | 27.678 |
February | 582.037 | 26.237 | 7.750 | 0.128 | 26.366 |
March | 640.775 | 28.362 | 2.500 | 0.028 | 28.389 |
April | 690.292 | 29.530 | 0.000 | 0.000 | 29.530 |
May | 738.250 | 38.053 | 0.000 | 0.000 | 38.053 |
June | 720.000 | 39.843 | 0.000 | 0.000 | 39.843 |
July | 744.000 | 46.304 | 0.000 | 0.000 | 46.304 |
August | 744.000 | 47.067 | 0.000 | 0.000 | 47.067 |
September | 720.000 | 44.949 | 0.000 | 0.000 | 44.949 |
October | 741.125 | 44.588 | 0.000 | 0.000 | 44.588 |
November | 688.979 | 37.239 | 0.000 | 0.000 | 37.239 |
December | 704.479 | 33.521 | 0.000 | 0.000 | 33.521 |
Annual Sum or Average | 8344.471 | 443.371 | 10.250 | 0.156 | 443.527 |
Minimum of Months | 582.037 | 26.237 | 0.000 | 0.000 | 26.366 |
Maximum of Months | 744.000 | 47.067 | 7.750 | 0.128 | 47.067 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 596.531 | 20.136 | 0.000 | 0.000 | 20.136 |
February | 563.249 | 23.918 | 10.750 | 0.230 | 24.149 |
March | 622.765 | 27.992 | 3.000 | 0.048 | 28.040 |
April | 685.207 | 28.772 | 0.000 | 0.000 | 28.772 |
May | 738.125 | 38.542 | 0.000 | 0.000 | 38.542 |
June | 720.000 | 42.019 | 0.000 | 0.000 | 42.019 |
July | 744.000 | 49.162 | 0.000 | 0.000 | 49.162 |
August | 744.000 | 48.591 | 0.000 | 0.000 | 48.591 |
September | 720.000 | 48.080 | 0.000 | 0.000 | 48.080 |
October | 740.208 | 41.174 | 0.000 | 0.000 | 41.174 |
November | 680.746 | 32.820 | 0.000 | 0.000 | 32.820 |
December | 690.663 | 26.529 | 0.000 | 0.000 | 26.529 |
Annual Sum or Average | 8245.494 | 427.737 | 13.750 | 0.278 | 428.015 |
Minimum of Months | 563.249 | 20.136 | 0.000 | 0.000 | 20.136 |
Maximum of Months | 744.000 | 49.162 | 10.750 | 0.230 | 49.162 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 677.332 | 16.478 | 0.000 | 0.000 | 16.478 |
February | 611.789 | 17.719 | 2.250 | 0.011 | 17.730 |
March | 670.870 | 20.392 | 0.000 | 0.000 | 20.392 |
April | 714.229 | 21.674 | 0.000 | 0.000 | 21.674 |
May | 744.000 | 29.107 | 0.000 | 0.000 | 29.107 |
June | 720.000 | 31.278 | 0.000 | 0.000 | 31.278 |
July | 744.000 | 36.227 | 0.000 | 0.000 | 36.227 |
August | 744.000 | 35.670 | 0.000 | 0.000 | 35.670 |
September | 720.000 | 34.330 | 0.000 | 0.000 | 34.330 |
October | 744.000 | 31.404 | 0.000 | 0.000 | 31.404 |
November | 697.762 | 25.296 | 0.000 | 0.000 | 25.296 |
December | 717.677 | 21.321 | 0.000 | 0.000 | 21.321 |
Annual Sum or Average | 8505.658 | 320.896 | 2.250 | 0.011 | 320.908 |
Minimum of Months | 611.789 | 16.478 | 0.000 | 0.000 | 16.478 |
Maximum of Months | 744.000 | 36.227 | 2.250 | 0.011 | 36.227 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 627.125 | 21.663 | 0.000 | 0.000 | 21.663 |
February | 577.822 | 21.927 | 8.500 | 0.142 | 22.069 |
March | 638.772 | 25.988 | 2.750 | 0.029 | 26.016 |
April | 690.542 | 28.858 | 0.000 | 0.000 | 28.858 |
May | 738.750 | 38.639 | 0.000 | 0.000 | 38.639 |
June | 720.000 | 40.943 | 0.000 | 0.000 | 40.943 |
July | 744.000 | 47.192 | 0.000 | 0.000 | 47.192 |
August | 744.000 | 46.999 | 0.000 | 0.000 | 46.999 |
September | 720.000 | 43.408 | 0.000 | 0.000 | 43.408 |
October | 740.875 | 41.175 | 0.000 | 0.000 | 41.175 |
November | 688.471 | 32.046 | 0.000 | 0.000 | 32.046 |
December | 702.846 | 27.103 | 0.000 | 0.000 | 27.103 |
Annual Sum or Average | 8333.203 | 415.940 | 11.250 | 0.171 | 416.111 |
Minimum of Months | 577.822 | 21.663 | 0.000 | 0.000 | 21.663 |
Maximum of Months | 744.000 | 47.192 | 8.500 | 0.142 | 47.192 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 714.492 | 33.348 | 0.000 | 0.000 | 33.348 |
February | 632.436 | 34.021 | 0.750 | 0.004 | 34.025 |
March | 692.763 | 36.291 | 0.000 | 0.000 | 36.291 |
April | 717.625 | 35.323 | 0.000 | 0.000 | 35.323 |
May | 744.000 | 43.208 | 0.000 | 0.000 | 43.208 |
June | 720.000 | 45.195 | 0.000 | 0.000 | 45.195 |
July | 744.000 | 52.107 | 0.000 | 0.000 | 52.107 |
August | 744.000 | 52.859 | 0.000 | 0.000 | 52.859 |
September | 720.000 | 53.939 | 0.000 | 0.000 | 53.939 |
October | 744.000 | 50.581 | 0.000 | 0.000 | 50.581 |
November | 709.183 | 43.952 | 0.000 | 0.000 | 43.952 |
December | 729.837 | 40.052 | 0.000 | 0.000 | 40.052 |
Annual Sum or Average | 8612.337 | 520.877 | 0.750 | 0.004 | 520.881 |
Minimum of Months | 632.436 | 33.348 | 0.000 | 0.000 | 33.348 |
Maximum of Months | 744.000 | 53.939 | 0.750 | 0.004 | 53.939 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 743.750 | 29.021 | 0.000 | 0.000 | 29.021 |
February | 655.879 | 27.396 | 0.000 | 0.000 | 27.396 |
March | 737.254 | 28.453 | 0.000 | 0.000 | 28.453 |
April | 720.000 | 27.761 | 0.000 | 0.000 | 27.761 |
May | 744.000 | 33.385 | 0.000 | 0.000 | 33.385 |
June | 720.000 | 34.205 | 0.000 | 0.000 | 34.205 |
July | 744.000 | 38.966 | 0.000 | 0.000 | 38.966 |
August | 744.000 | 39.595 | 0.000 | 0.000 | 39.595 |
September | 720.000 | 39.769 | 0.000 | 0.000 | 39.769 |
October | 744.000 | 39.980 | 0.000 | 0.000 | 39.980 |
November | 720.000 | 35.588 | 0.000 | 0.000 | 35.588 |
December | 744.000 | 33.753 | 0.000 | 0.000 | 33.753 |
Annual Sum or Average | 8736.883 | 407.871 | 0.000 | 0.000 | 407.871 |
Minimum of Months | 655.879 | 27.396 | 0.000 | 0.000 | 27.396 |
Maximum of Months | 744.000 | 39.980 | 0.000 | 0.000 | 39.980 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 715.625 | 33.069 | 0.000 | 0.000 | 33.069 |
February | 633.562 | 30.904 | 1.500 | 0.010 | 30.914 |
March | 698.597 | 33.358 | 0.000 | 0.000 | 33.358 |
April | 718.250 | 34.690 | 0.000 | 0.000 | 34.690 |
May | 744.000 | 42.897 | 0.000 | 0.000 | 42.897 |
June | 720.000 | 43.815 | 0.000 | 0.000 | 43.815 |
July | 744.000 | 49.802 | 0.000 | 0.000 | 49.802 |
August | 744.000 | 50.699 | 0.000 | 0.000 | 50.699 |
September | 720.000 | 48.375 | 0.000 | 0.000 | 48.375 |
October | 744.000 | 48.946 | 0.000 | 0.000 | 48.946 |
November | 709.625 | 41.542 | 0.000 | 0.000 | 41.542 |
December | 730.750 | 38.664 | 0.000 | 0.000 | 38.664 |
Annual Sum or Average | 8622.410 | 496.759 | 1.500 | 0.010 | 496.770 |
Minimum of Months | 633.562 | 30.904 | 0.000 | 0.000 | 30.914 |
Maximum of Months | 744.000 | 50.699 | 1.500 | 0.010 | 50.699 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 706.917 | 26.106 | 0.000 | 0.000 | 26.106 |
February | 624.028 | 29.166 | 2.500 | 0.025 | 29.191 |
March | 688.135 | 33.592 | 0.000 | 0.000 | 33.592 |
April | 717.262 | 34.643 | 0.000 | 0.000 | 34.643 |
May | 744.000 | 44.038 | 0.000 | 0.000 | 44.038 |
June | 720.000 | 46.563 | 0.000 | 0.000 | 46.563 |
July | 744.000 | 53.194 | 0.000 | 0.000 | 53.194 |
August | 744.000 | 52.832 | 0.000 | 0.000 | 52.832 |
September | 720.000 | 52.169 | 0.000 | 0.000 | 52.169 |
October | 744.000 | 46.302 | 0.000 | 0.000 | 46.302 |
November | 706.581 | 37.786 | 0.000 | 0.000 | 37.786 |
December | 725.683 | 32.406 | 0.000 | 0.000 | 32.406 |
Annual Sum or Average | 8584.606 | 488.795 | 2.500 | 0.025 | 488.820 |
Minimum of Months | 624.028 | 26.106 | 0.000 | 0.000 | 26.106 |
Maximum of Months | 744.000 | 53.194 | 2.500 | 0.025 | 53.194 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 743.500 | 22.566 | 0.000 | 0.000 | 22.566 |
February | 652.171 | 22.877 | 0.000 | 0.000 | 22.877 |
March | 736.783 | 25.944 | 0.000 | 0.000 | 25.944 |
April | 720.000 | 27.069 | 0.000 | 0.000 | 27.069 |
May | 744.000 | 34.054 | 0.000 | 0.000 | 34.054 |
June | 720.000 | 35.362 | 0.000 | 0.000 | 35.362 |
July | 744.000 | 39.866 | 0.000 | 0.000 | 39.866 |
August | 744.000 | 39.486 | 0.000 | 0.000 | 39.486 |
September | 720.000 | 38.035 | 0.000 | 0.000 | 38.035 |
October | 744.000 | 36.046 | 0.000 | 0.000 | 36.046 |
November | 719.750 | 29.972 | 0.000 | 0.000 | 29.972 |
December | 744.000 | 26.899 | 0.000 | 0.000 | 26.899 |
Annual Sum or Average | 8732.204 | 378.177 | 0.000 | 0.000 | 378.177 |
Minimum of Months | 652.171 | 22.566 | 0.000 | 0.000 | 22.566 |
Maximum of Months | 744.000 | 39.866 | 0.000 | 0.000 | 39.866 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 714.042 | 27.189 | 0.000 | 0.000 | 27.189 |
February | 632.006 | 26.746 | 1.750 | 0.014 | 26.759 |
March | 698.066 | 31.127 | 0.000 | 0.000 | 31.127 |
April | 718.250 | 34.092 | 0.000 | 0.000 | 34.092 |
May | 744.000 | 43.477 | 0.000 | 0.000 | 43.477 |
June | 720.000 | 44.871 | 0.000 | 0.000 | 44.871 |
July | 744.000 | 50.662 | 0.000 | 0.000 | 50.662 |
August | 744.000 | 50.667 | 0.000 | 0.000 | 50.667 |
September | 720.000 | 46.925 | 0.000 | 0.000 | 46.925 |
October | 744.000 | 45.687 | 0.000 | 0.000 | 45.687 |
November | 709.000 | 36.471 | 0.000 | 0.000 | 36.471 |
December | 730.375 | 32.409 | 0.000 | 0.000 | 32.409 |
Annual Sum or Average | 8617.739 | 470.320 | 1.750 | 0.014 | 470.334 |
Minimum of Months | 632.006 | 26.746 | 0.000 | 0.000 | 26.759 |
Maximum of Months | 744.000 | 50.667 | 1.750 | 0.014 | 50.667 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 658.812 | 34.734 | 0.000 | 0.000 | 34.734 |
February | 601.619 | 36.349 | 6.250 | 0.163 | 36.513 |
March | 664.176 | 39.543 | 2.000 | 0.021 | 39.564 |
April | 711.691 | 38.914 | 0.000 | 0.000 | 38.914 |
May | 743.500 | 49.534 | 0.000 | 0.000 | 49.534 |
June | 720.000 | 52.243 | 0.000 | 0.000 | 52.243 |
July | 744.000 | 60.755 | 0.000 | 0.000 | 60.755 |
August | 744.000 | 61.175 | 0.000 | 0.000 | 61.175 |
September | 720.000 | 61.522 | 0.000 | 0.000 | 61.522 |
October | 744.000 | 56.675 | 0.000 | 0.000 | 56.675 |
November | 696.567 | 48.053 | 0.000 | 0.000 | 48.053 |
December | 713.172 | 42.620 | 0.000 | 0.000 | 42.620 |
Annual Sum or Average | 8461.535 | 582.117 | 8.250 | 0.185 | 582.301 |
Minimum of Months | 601.619 | 34.734 | 0.000 | 0.000 | 34.734 |
Maximum of Months | 744.000 | 61.522 | 6.250 | 0.163 | 61.522 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 724.604 | 30.984 | 0.000 | 0.000 | 30.984 |
February | 637.206 | 30.250 | 0.500 | 0.002 | 30.252 |
March | 700.341 | 32.087 | 0.000 | 0.000 | 32.087 |
April | 718.417 | 31.847 | 0.000 | 0.000 | 31.847 |
May | 744.000 | 40.119 | 0.000 | 0.000 | 40.119 |
June | 720.000 | 41.611 | 0.000 | 0.000 | 41.611 |
July | 744.000 | 47.934 | 0.000 | 0.000 | 47.934 |
August | 744.000 | 48.273 | 0.000 | 0.000 | 48.273 |
September | 720.000 | 47.786 | 0.000 | 0.000 | 47.786 |
October | 744.000 | 46.658 | 0.000 | 0.000 | 46.658 |
November | 710.858 | 40.321 | 0.000 | 0.000 | 40.321 |
December | 735.762 | 37.068 | 0.000 | 0.000 | 37.068 |
Annual Sum or Average | 8643.188 | 474.936 | 0.500 | 0.002 | 474.938 |
Minimum of Months | 637.206 | 30.250 | 0.000 | 0.000 | 30.252 |
Maximum of Months | 744.000 | 48.273 | 0.500 | 0.002 | 48.273 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 669.742 | 34.856 | 0.000 | 0.000 | 34.856 |
February | 609.578 | 33.488 | 5.250 | 0.105 | 33.593 |
March | 676.061 | 36.764 | 1.500 | 0.012 | 36.776 |
April | 713.500 | 38.431 | 0.000 | 0.000 | 38.431 |
May | 743.750 | 49.167 | 0.000 | 0.000 | 49.167 |
June | 720.000 | 50.755 | 0.000 | 0.000 | 50.755 |
July | 744.000 | 58.258 | 0.000 | 0.000 | 58.258 |
August | 744.000 | 58.912 | 0.000 | 0.000 | 58.912 |
September | 720.000 | 55.913 | 0.000 | 0.000 | 55.913 |
October | 744.000 | 55.338 | 0.000 | 0.000 | 55.338 |
November | 699.667 | 45.951 | 0.000 | 0.000 | 45.951 |
December | 718.187 | 41.633 | 0.000 | 0.000 | 41.633 |
Annual Sum or Average | 8502.485 | 559.466 | 6.750 | 0.117 | 559.583 |
Minimum of Months | 609.578 | 33.488 | 0.000 | 0.000 | 33.593 |
Maximum of Months | 744.000 | 58.912 | 5.250 | 0.105 | 58.912 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 647.762 | 29.340 | 0.000 | 0.000 | 29.340 |
February | 595.152 | 33.255 | 7.500 | 0.192 | 33.447 |
March | 663.310 | 38.459 | 2.000 | 0.024 | 38.483 |
April | 711.691 | 38.853 | 0.000 | 0.000 | 38.853 |
May | 743.750 | 50.079 | 0.000 | 0.000 | 50.079 |
June | 720.000 | 53.074 | 0.000 | 0.000 | 53.074 |
July | 744.000 | 61.448 | 0.000 | 0.000 | 61.448 |
August | 744.000 | 61.424 | 0.000 | 0.000 | 61.424 |
September | 720.000 | 60.989 | 0.000 | 0.000 | 60.989 |
October | 744.000 | 54.402 | 0.000 | 0.000 | 54.402 |
November | 694.024 | 43.484 | 0.000 | 0.000 | 43.484 |
December | 706.694 | 36.606 | 0.000 | 0.000 | 36.606 |
Annual Sum or Average | 8434.383 | 561.413 | 9.500 | 0.215 | 561.629 |
Minimum of Months | 595.152 | 29.340 | 0.000 | 0.000 | 29.340 |
Maximum of Months | 744.000 | 61.448 | 7.500 | 0.192 | 61.448 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 721.354 | 26.035 | 0.000 | 0.000 | 26.035 |
February | 632.113 | 27.360 | 1.062 | 0.004 | 27.364 |
March | 699.814 | 31.160 | 0.000 | 0.000 | 31.160 |
April | 718.417 | 31.869 | 0.000 | 0.000 | 31.869 |
May | 744.000 | 40.739 | 0.000 | 0.000 | 40.739 |
June | 720.000 | 42.504 | 0.000 | 0.000 | 42.504 |
July | 744.000 | 48.719 | 0.000 | 0.000 | 48.719 |
August | 744.000 | 48.645 | 0.000 | 0.000 | 48.645 |
September | 720.000 | 47.417 | 0.000 | 0.000 | 47.417 |
October | 744.000 | 44.690 | 0.000 | 0.000 | 44.690 |
November | 709.450 | 36.165 | 0.000 | 0.000 | 36.165 |
December | 733.262 | 31.585 | 0.000 | 0.000 | 31.585 |
Annual Sum or Average | 8630.410 | 456.888 | 1.062 | 0.004 | 456.892 |
Minimum of Months | 632.113 | 26.035 | 0.000 | 0.000 | 26.035 |
Maximum of Months | 744.000 | 48.719 | 1.062 | 0.004 | 48.719 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 667.404 | 30.286 | 0.000 | 0.000 | 30.286 |
February | 607.480 | 30.725 | 6.062 | 0.115 | 30.840 |
March | 675.913 | 35.823 | 1.500 | 0.012 | 35.836 |
April | 713.750 | 38.326 | 0.000 | 0.000 | 38.326 |
May | 743.750 | 49.493 | 0.000 | 0.000 | 49.493 |
June | 720.000 | 51.334 | 0.000 | 0.000 | 51.334 |
July | 744.000 | 58.737 | 0.000 | 0.000 | 58.737 |
August | 744.000 | 59.054 | 0.000 | 0.000 | 59.054 |
September | 720.000 | 55.444 | 0.000 | 0.000 | 55.444 |
October | 744.000 | 53.472 | 0.000 | 0.000 | 53.472 |
November | 698.471 | 42.033 | 0.000 | 0.000 | 42.033 |
December | 717.992 | 36.520 | 0.000 | 0.000 | 36.520 |
Annual Sum or Average | 8496.759 | 541.247 | 7.562 | 0.128 | 541.375 |
Minimum of Months | 607.480 | 30.286 | 0.000 | 0.000 | 30.286 |
Maximum of Months | 744.000 | 59.054 | 6.062 | 0.115 | 59.054 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.19 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.01 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.19 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5.61 | 0.00 |
March | 0.00 | 1.09 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.52 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 5.61 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6.73 | 0.00 |
March | 0.00 | 1.27 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.62 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6.73 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.59 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.05 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.59 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6.16 | 0.00 |
March | 0.00 | 1.13 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.57 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6.16 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.12 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.01 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.12 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.45 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.45 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.73 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.73 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.59 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.04 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.59 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4.04 | 0.00 |
March | 0.00 | 0.48 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.35 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4.04 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.07 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.01 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.07 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 3.71 | 0.00 |
March | 0.00 | 0.38 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.32 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 3.71 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4.74 | 0.00 |
March | 0.00 | 0.53 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.41 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4.74 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.16 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.01 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.16 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4.05 | 0.00 |
March | 0.00 | 0.39 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.34 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4.05 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 1.09 |
February | 0.00 | 0.00 | 1.15 |
March | 0.00 | 0.00 | 1.13 |
April | 0.00 | 0.00 | 1.12 |
May | 0.00 | 0.00 | 1.19 |
June | 0.00 | 0.00 | 1.23 |
July | 0.00 | 0.00 | 1.29 |
August | 0.00 | 0.00 | 1.29 |
September | 0.00 | 0.00 | 1.33 |
October | 0.00 | 0.00 | 1.27 |
November | 0.00 | 0.00 | 1.22 |
December | 0.00 | 0.00 | 1.16 |
Annual Sum or Average | 0.00 | 0.00 | 1.21 |
Minimum of Months | 0.00 | 0.00 | 1.09 |
Maximum of Months | 0.00 | 0.00 | 1.33 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.24 |
February | 0.00 | 0.00 | 0.27 |
March | 0.00 | 0.00 | 0.24 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.30 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.35 |
December | 0.00 | 0.00 | 0.30 |
Annual Sum or Average | 0.00 | 0.00 | 0.32 |
Minimum of Months | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.40 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.18 |
February | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.31 |
December | 0.00 | 0.00 | 0.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.18 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.17 |
February | 0.00 | 0.00 | 0.21 |
March | 0.00 | 0.00 | 0.22 |
April | 0.00 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.23 |
Annual Sum or Average | 0.00 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.17 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.22 |
February | 0.00 | 0.00 | 0.25 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.30 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.44 |
July | 0.00 | 0.00 | 0.49 |
August | 0.00 | 0.00 | 0.49 |
September | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.00 | 0.43 |
November | 0.00 | 0.00 | 0.34 |
December | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.22 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.30 |
February | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.45 |
November | 0.00 | 0.00 | 0.41 |
December | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.30 |
February | 0.00 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.29 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.43 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.43 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.33 |
February | 0.00 | 0.00 | 0.35 |
March | 0.00 | 0.00 | 0.33 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.50 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.00 | 0.49 |
November | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.23 |
February | 0.00 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.47 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.35 |
December | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.23 |
February | 0.00 | 0.00 | 0.26 |
March | 0.00 | 0.00 | 0.26 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.41 |
October | 0.00 | 0.00 | 0.37 |
November | 0.00 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.23 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.27 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.51 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.46 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.00 | 0.00 | 0.51 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.31 |
February | 0.00 | 0.00 | 0.36 |
March | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.51 |
November | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.44 |
Minimum of Months | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.31 |
February | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.00 | 0.32 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.00 | 0.42 |
December | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.40 |
Minimum of Months | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.00 | 0.50 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.34 |
February | 0.00 | 0.00 | 0.37 |
March | 0.00 | 0.00 | 0.36 |
April | 0.00 | 0.00 | 0.38 |
May | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.55 |
November | 0.00 | 0.00 | 0.47 |
December | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.00 | 0.34 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.26 |
February | 0.00 | 0.00 | 0.33 |
March | 0.00 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.44 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.48 |
November | 0.00 | 0.00 | 0.40 |
December | 0.00 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.25 |
February | 0.00 | 0.00 | 0.30 |
March | 0.00 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.40 |
June | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.44 |
November | 0.00 | 0.00 | 0.37 |
December | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.25 |
Maximum of Months | 0.00 | 0.00 | 0.49 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.29 |
February | 0.00 | 0.00 | 0.34 |
March | 0.00 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.38 |
May | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.00 | 0.52 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.53 |
November | 0.00 | 0.00 | 0.43 |
December | 0.00 | 0.00 | 0.36 |
Annual Sum or Average | 0.00 | 0.00 | 0.45 |
Minimum of Months | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:27:57
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1040.88 | 774.96 |
February | 0.00 | 0.00 | 1035.92 | 696.63 |
March | 0.00 | 0.00 | 1016.35 | 756.70 |
April | 0.00 | 0.00 | 989.57 | 712.99 |
May | 0.00 | 0.00 | 956.60 | 712.22 |
June | 0.00 | 0.00 | 934.76 | 673.50 |
July | 0.00 | 0.00 | 925.71 | 689.22 |
August | 0.00 | 0.00 | 930.10 | 692.48 |
September | 0.00 | 0.00 | 950.84 | 685.09 |
October | 0.00 | 0.00 | 980.86 | 730.28 |
November | 0.00 | 0.00 | 1010.19 | 727.85 |
December | 0.00 | 0.00 | 1034.19 | 769.99 |
Annual Sum or Average | 0.00 | 0.00 | 983.54 | 8621.91 |
Minimum of Months | 0.00 | 0.00 | 925.71 | 673.50 |
Maximum of Months | 0.00 | 0.00 | 1040.88 | 774.96 |