Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32

Tabular Output Report in Format: HTML

Building: MF+CZ1A+USA_FL_Miami.Intl.AP.722020+elecres+unheatedbsmt+IECC_2015

Environment: ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020

Simulation Timestamp: 2019-02-14 08:32:44


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 633588.91 16.24 29.32
Net Site Energy 633588.91 16.24 29.32
Total Source Energy 2006576.07 51.44 92.85
Net Source Energy 2006576.07 51.44 92.85


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 6907.99 0.00 0.00 0.00 0.00 0.00
Cooling 154777.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299798.81 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 24363.45 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 94808.41 0.00 0.00 0.00 0.00 374778.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 633588.91 0.00 0.00 0.00 0.00 374778.00
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 6907.99 0.00 0.00 0.00 0.00 0.00
Cooling General 154777.24 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9418.03 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4809.31 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 24363.45 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 94808.41 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 374778.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 13.00 0.00 0.00 0.00 0.00 17.34
Other 13.87 0.00 0.00 0.00 0.00 0.00
Total 29.32 0.00 0.00 0.00 0.00 17.34


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 7.20 0.00 0.00 0.00 0.00 9.61
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 16.24 0.00 0.00 0.00 0.00 9.61


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 633588.909 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 633588.909 100.00
     
Total On-Site and Utility Electric Sources 633588.909 100.00
Total Electricity End Uses 633588.909 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 374778.00 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 374778.00 100.00
Total Water End Uses 374778.00 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1.50
Time Not Comfortable Based on Simple ASHRAE 55-2004 4144.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
RunPeriod ANNUAL
Weather File Miami Intl Ap FL USA TMY3 WMO#=722020
Latitude [deg] 25.82
Longitude [deg] -80.3
Elevation [ft] 36.09
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 18953.34 7014.93 2461.74 7014.93 2461.74
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 11.22 7.58 21.60 7.58 21.60
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
UNHEATEDBSMT 7794.39 No Yes 58419.71 1.00 185.02 2590.34 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     325507.37   16363.00 2590.34 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 17395.21     141767.99   1066.39 2590.34 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 04-FEB-07:15 - - - - 01-JAN-08:30
Heating 73.76 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.19 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.23 0.00 0.00 0.00 0.00 0.00
Interior Equipment 34.65 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.80 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 120.92 0.00 0.00 0.00 0.00 1.36
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 241.54 0.00 0.00 0.00 0.00 1.36


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 73.76 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 6.19 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.23 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.83 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  electric_dryer 4.26 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 5.80 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 120.92 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.36
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 21877.62 0.00 0.00 0.00 0.00
Cooling 490179.53 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949462.83 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 77159.03 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 300258.23 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2006576.07 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 1.01 0.00 0.00 0.00 0.00
Cooling 22.68 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.57 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 13.89 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 92.85 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 1.01 0.00 0.00 0.00 0.00
Cooling 22.68 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.94 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.57 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 13.89 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 92.85 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MIAMI INTL AP ANN HTG 99.6% CONDNS DB 47.66 0.00 47.66 Wetbulb [F] 748.07 340.00
MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 91.76 12.06 77.54 Wetbulb [F] 885.87 140.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.392 0.534 839.40 839.40 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.392 0.534 455.77 455.77 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.392 0.534 839.40 839.40 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.392 0.534 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.066 0.070 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.219 0.882              
North Total or Average           531.68 0.501 0.219 0.882              
Non-North Total or Average           1595.05 0.501 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 0.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 1.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15246.21 10790.81 4455.39 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7716.81 5217.21 2499.61 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10135.78 6852.63 3283.15 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13188.64 9153.96 4034.68 0.69 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7971.63 5389.48 2582.14 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10314.08 6973.17 3340.90 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13111.27 9227.32 3883.95 0.70 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8407.73 5684.32 2723.40 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10186.34 6961.31 3225.03 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13131.81 9251.55 3880.25 0.70 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8640.98 5842.02 2798.96 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10299.02 7049.87 3249.14 0.68 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15653.39 11121.80 4531.59 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11188.68 7654.57 3534.10 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12482.95 8613.31 3869.64 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15664.93 11131.07 4533.86 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11226.89 7696.53 3530.36 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12469.48 8615.95 3853.52 0.69 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.2 3.43 11.72 12.43 12.24
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.46 11.81 12.53 12.40
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.44 11.74 12.46 12.29
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.8 3.48 11.89 12.62 12.53
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.44 11.74 12.46 12.28
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.50 11.94 12.67 12.61
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.48 11.88 12.61 12.51
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.43 11.70 12.41 12.21
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.48 11.88 12.61 12.52
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.47 11.84 12.57 12.45
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.43 11.70 12.41 12.21
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.48 11.87 12.60 12.50
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.47 11.83 12.56 12.44
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   3619.25 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   4361.02 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   5541.58 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5542.99 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   4359.78 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5537.47 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4880.39 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   3688.44 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4878.82 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4881.13 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   3686.46 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4874.15 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   6111.53 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   4915.76 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   6108.50 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   6113.81 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   4916.01 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   6106.88 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 430.53 162.39 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 192.96 72.78 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 253.45 95.60 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 354.00 133.53 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 199.33 75.19 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 257.91 97.28 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 364.89 137.63 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 210.24 79.30 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 262.31 98.94 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 366.46 138.22 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 216.07 81.50 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 266.39 100.48 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.39 168.37 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 288.97 109.00 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 329.87 124.42 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 446.83 168.54 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 291.57 109.98 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 330.73 124.75 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10100.36 10100.36 8.41 430.525 430.525 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00948 89.47 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4527.21 4527.21 3.77 192.961 192.961 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01083 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5946.30 5946.30 4.95 253.447 253.447 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01024 88.08 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8305.12 8305.12 6.92 354.000 354.000 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00977 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4676.68 4676.68 3.90 199.332 199.332 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01078 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6050.89 6050.89 5.04 257.906 257.906 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.01021 88.08 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8560.79 8560.79 7.13 364.887 364.887 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00943 89.17 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4932.63 4932.63 4.11 210.237 210.237 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01024 87.06 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6154.39 6154.39 5.13 262.312 262.312 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00979 88.53 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8597.65 8597.65 7.16 366.457 366.457 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00943 88.87 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5069.46 5069.46 4.22 216.070 216.070 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01021 87.06 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6250.14 6250.14 5.21 266.393 266.393 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00977 88.53 0.01715 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7759.39 7759.39 6.46 330.733 330.733 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00987 88.41 0.01715 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7739.12 7739.12 6.45 329.871 329.871 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00987 88.87 0.01715 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10472.62 10472.62 8.72 446.389 446.389 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6840.64 6840.64 5.70 291.568 291.568 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.01006 87.06 0.01715 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6779.63 6779.63 5.65 288.968 288.968 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.01006 87.51 0.01715 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10482.91 10482.91 8.73 446.828 446.828 MIAMI INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00945 89.17 0.01715 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2471.23 2471.23 2.06 45.038 45.038 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00772 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3223.96 3223.96 2.69 58.756 58.756 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4421.99 4421.99 3.68 80.590 80.590 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4423.42 4423.42 3.68 80.616 80.616 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3222.71 3222.71 2.68 58.733 58.733 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00777 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4417.81 4417.81 3.68 80.513 80.513 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3751.00 3751.00 3.12 68.362 68.362 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2541.42 2541.42 2.12 46.317 46.317 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3749.40 3749.40 3.12 68.332 68.332 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3751.75 3751.75 3.13 68.375 68.375 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2539.41 2539.41 2.12 46.281 46.281 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00789 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3744.66 3744.66 3.12 68.246 68.246 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00787 47.66 0.00699 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4995.64 4995.64 4.16 91.044 91.044 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 4997.28 4997.28 4.16 91.074 91.074 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5000.36 5000.36 4.17 91.130 91.130 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3787.16 3787.16 3.15 69.020 69.020 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3786.90 3786.90 3.15 69.015 69.015 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00778 47.66 0.00699 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5002.68 5002.68 4.17 91.172 91.172 MIAMI INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00779 47.66 0.00699 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 430.53 430.53 45.04 45.04
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 192.96 192.96 58.76 58.76
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 253.45 253.45 80.59 80.59
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 354.00 354.00 80.62 80.62
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 199.33 199.33 58.73 58.73
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 257.91 257.91 80.51 80.51
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 364.89 364.89 68.36 68.36
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 210.24 210.24 46.32 46.32
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.31 262.31 68.33 68.33
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 366.46 366.46 68.38 68.38
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.07 216.07 46.28 46.28
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.39 266.39 68.25 68.25
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.39 446.39 91.13 91.13
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 288.97 288.97 69.02 69.02
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.87 329.87 91.07 91.07
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.83 446.83 91.17 91.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.57 291.57 69.02 69.02
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.73 330.73 91.04 91.04


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6234.25 1241.25 275.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7178.75 4397.00 3577.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7238.00 3792.75 2928.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7151.50 4630.50 3545.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 7067.25 5076.00 3989.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7121.50 4162.25 3098.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7368.50 2700.75 1957.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7212.75 2256.50 1639.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7282.25 2258.75 1545.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7224.00 3015.00 2090.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7112.00 2655.50 1812.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7180.25 2512.25 1630.75
LIVING_UNIT3_BACKROW_TOPFLOOR 7272.75 2992.25 2073.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 7376.25 2803.00 2000.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7424.75 3290.50 2446.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7230.75 3256.25 2362.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7342.50 2975.00 2225.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7324.25 3489.75 2534.50
UNHEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 7547.00 5365.25 4144.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 1.50 0.00 1.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
UNHEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 1.50 0.00 1.50
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.264
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.141 0.000 0.264
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.160 0.000 0.264
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.140 0.000 0.264
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.264
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.051 0.000 0.264
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.264
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.160 0.000 0.264
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.140 0.000 0.264
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.141 0.000 0.264
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.159 0.000 0.264
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1824
Defaulted Fields 446
Fields with Defaults 4578
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
Electricity:Building 100751.26 6306.84 02-JAN-03:15 19194.31 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5597.29 350.38 02-JAN-03:15 1066.35 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87803.80 5989.14 02-JAN-04:15 15388.75 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2758.31 25.25 02-JAN-03:15 880.12 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1408.53 13.53 02-JAN-02:15 381.47 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4877.99 332.73 02-JAN-04:15 854.93 01-JAN-18:15
Electricity:Plant 27767.08 0.00 01-JAN-00:15 35504.14 15-JAN-08:15
WaterSystems:Electricity 27767.08 0.00 01-JAN-00:15 35504.14 15-JAN-08:15
Water Heater:WaterSystems:Electricity 27767.08 0.00 01-JAN-00:15 35504.14 15-JAN-08:15
Fans:Electricity 7135.46 0.00 03-FEB-00:15 1991.42 29-JUL-16:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
ElectricityPurchased:Plant 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
Cogeneration:ElectricityPurchased 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
ElectricityNet:Plant 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
Cogeneration:ElectricityNet 185562.82 6804.92 23-FEB-03:30 70741.96 04-FEB-07:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 54489.15 0.00 03-FEB-00:15 23876.20 04-FEB-07:00
General:Fans:Electricity 7135.46 0.00 03-FEB-00:15 1991.42 29-JUL-16:30
Heating:Electricity 2023.18 0.00 01-JAN-00:15 22139.64 04-FEB-07:00
Cooling:Electricity 45330.50 0.00 09-JAN-01:00 13961.30 29-JUL-16:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
Water:Plant 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
WaterSystems:Water 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
MainsWater:Plant 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
WaterSystems:MainsWater 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 50107.88 0.01 20-DEC-03:00 0.18 01-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
PlantLoopHeatingDemand:Plant 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
WaterSystems:PlantLoopHeatingDemand 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1183398.18 996.96 01-MAR-03:00 330625.83 27-JUL-17:15
EnergyTransfer:Building 425220.36 0.00 03-FEB-00:15 137877.71 29-JUL-16:30
EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 7438.83 0.00 01-JAN-00:15 81465.58 04-FEB-07:00
Heating:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 417781.53 0.00 09-JAN-01:00 137877.71 29-JUL-16:30
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 35862.14 0.00 09-JAN-01:00 10321.56 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 80.29 0.00 01-JAN-00:15 3408.20 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 35781.85 0.00 09-JAN-01:00 10321.56 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17387.44 0.00 01-JAN-03:15 5155.38 02-JAN-14:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 281.03 0.00 01-JAN-00:15 3720.20 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17106.41 0.00 01-JAN-03:15 5155.38 02-JAN-14:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22092.55 0.00 01-JAN-01:30 6803.47 14-OCT-13:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 496.59 0.00 01-JAN-00:15 5317.02 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21595.96 0.00 01-JAN-01:30 6803.47 14-OCT-13:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19981.48 0.00 01-JAN-01:30 8445.23 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 733.40 0.00 01-JAN-00:15 5356.20 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19248.07 0.00 01-JAN-01:30 8445.23 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15210.93 0.00 01-JAN-03:00 5228.25 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 422.60 0.00 01-JAN-00:15 3831.39 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14788.33 0.00 01-JAN-03:00 5228.25 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19873.76 0.00 01-JAN-01:30 6604.86 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 609.66 0.00 01-JAN-00:15 5374.49 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19264.10 0.00 01-JAN-01:30 6604.86 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25399.96 0.00 01-JAN-04:00 8729.29 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 300.43 0.00 01-JAN-00:15 4151.32 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 25099.53 0.00 01-JAN-04:00 8729.29 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20863.04 0.00 05-JAN-03:45 5618.90 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 106.06 0.00 01-JAN-00:15 2595.73 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20756.98 0.00 05-JAN-03:45 5618.90 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25489.63 0.00 01-JAN-04:00 7067.62 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 263.02 0.00 01-JAN-00:15 4229.98 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25226.61 0.00 01-JAN-04:00 7067.62 29-JUL-16:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23154.32 0.00 01-JAN-04:00 8633.88 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 431.02 0.00 01-JAN-00:15 4286.45 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22723.30 0.00 01-JAN-04:00 8633.88 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18493.12 0.00 05-JAN-03:30 5594.80 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 187.27 0.00 01-JAN-00:15 2758.53 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18305.85 0.00 05-JAN-03:30 5594.80 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23148.99 0.00 01-JAN-03:45 6945.58 29-JUL-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 338.15 0.00 01-JAN-00:15 4315.67 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22810.84 0.00 01-JAN-03:45 6945.58 29-JUL-16:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 27123.09 0.00 01-JAN-02:30 8893.80 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 604.51 0.00 01-JAN-00:15 5940.14 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26518.58 0.00 01-JAN-02:30 8893.80 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28625.46 0.00 01-JAN-02:45 8899.71 29-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 514.48 0.00 01-JAN-00:15 5865.68 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28110.98 0.00 01-JAN-02:45 8899.71 29-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28656.15 0.00 01-JAN-02:45 10805.42 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 611.28 0.00 01-JAN-00:15 5811.41 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28044.87 0.00 01-JAN-02:45 10805.42 29-JUL-16:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22546.12 0.00 01-JAN-05:30 7724.56 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 414.18 0.00 01-JAN-00:15 4376.60 04-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 22131.95 0.00 01-JAN-05:30 7724.56 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 24069.98 0.00 01-JAN-05:45 7717.54 29-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 311.39 0.00 01-JAN-00:15 4231.32 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 23758.59 0.00 01-JAN-05:45 7717.54 29-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 27242.19 0.00 01-JAN-02:45 10818.15 29-JUL-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 733.46 0.00 01-JAN-00:15 5914.75 04-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 26508.73 0.00 01-JAN-02:45 10818.15 29-JUL-16:30
EnergyTransfer:Plant 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
WaterSystems:EnergyTransfer 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 79447.67 664.68 20-JUL-02:30 21029.20 15-JAN-08:45
EnergyTransfer:HVAC 678730.15 0.00 03-FEB-00:15 188609.97 27-JUL-17:30
HeatingCoils:EnergyTransfer 6907.99 0.00 01-JAN-00:15 75540.45 04-FEB-07:00
CoolingCoils:EnergyTransfer 671822.15 0.00 09-JAN-01:00 188609.97 27-JUL-17:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 80.292 -2979.84 0.000 0.000 2882.582 2456.001 10401.374 8842.565 0.000 2600.396 11874.591 0.000 -1533.24 0.000 -1822.63 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 281.028 -1424.58 0.000 0.000 2894.513 2456.001 10401.374 3684.637 0.000 2477.445 0.000 0.000 -604.17 0.000 -1657.41 -2826.97
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 496.574 -1798.47 0.000 0.000 2901.253 2456.001 10401.374 9060.691 0.000 2600.030 0.002 0.000 -1431.85 0.000 -1711.17 -3176.89
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 733.389 -1602.93 0.000 0.000 2905.214 2456.001 10401.374 7182.246 0.000 2602.681 0.000 0.000 -1510.64 0.000 -1654.87 -3867.37
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 422.593 -1231.55 0.000 0.000 2900.216 2456.001 10401.374 1939.944 0.000 2479.611 0.000 0.000 -622.39 0.000 -1601.07 -3587.84
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 609.642 -1604.28 0.000 0.000 2905.687 2456.001 10401.374 7349.641 0.000 2599.972 0.000 0.000 -1414.74 0.000 -1665.46 -3977.90
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 300.429 -2090.23 0.000 0.000 2892.383 2456.001 10401.374 8733.636 0.000 2014.390 1294.062 0.000 -1614.83 0.000 -1377.93 -0.19
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 106.059 -1728.60 0.000 0.000 2886.141 2456.001 10401.374 3631.071 0.000 1892.819 1356.334 0.000 -647.77 0.000 -1324.95 -0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 263.016 -2100.82 0.000 0.000 2892.543 2456.001 10401.374 8927.604 0.000 2014.434 1198.764 0.000 -1540.42 0.000 -1386.60 -0.08
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 431.009 -1892.35 0.000 0.000 2895.959 2456.001 10401.374 7067.193 0.000 2015.827 434.025 0.000 -1629.88 0.000 -1348.14 -0.22
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 187.267 -1524.48 0.000 0.000 2890.429 2456.001 10401.374 1899.061 0.000 1893.729 539.898 0.000 -670.16 0.000 -1291.58 -0.05
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 338.149 -1899.65 0.000 0.000 2896.223 2456.001 10401.374 7225.636 0.000 2014.401 362.951 0.000 -1525.51 0.000 -1358.20 -0.32
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 604.501 -2208.42 0.000 0.000 2899.852 2456.001 10401.374 7124.046 0.000 2573.624 3719.196 0.000 -1543.25 0.000 -1716.59 -0.47
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 514.475 -2341.03 0.000 0.000 2897.402 2456.001 10401.374 8842.540 0.000 2573.552 3713.210 0.000 -1543.84 0.000 -1743.60 -0.04
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 611.270 -2335.51 0.000 0.000 2897.794 2456.001 10401.374 8649.633 0.000 2573.966 3793.357 0.000 -1609.61 0.000 -1728.97 -0.41
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 414.172 -1843.11 0.000 0.000 2894.548 2456.001 10401.374 1856.935 0.000 2454.229 3985.732 0.000 -675.64 0.000 -1655.26 -0.42
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 311.387 -1978.57 0.000 0.000 2891.773 2456.001 10401.374 3594.277 0.000 2452.794 3983.712 0.000 -647.79 0.000 -1684.84 -0.13
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 733.453 -2207.58 0.000 0.000 2899.965 2456.001 10401.374 6957.512 0.000 2575.946 3824.268 0.000 -1635.25 0.000 -1704.55 -0.05
UNHEATEDBSMT 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5874.586 48059.364 0.000 0.000 0.000 -53933.95 -0.87
Total Facility 0.000 0.000 7438.706 -34791.99 0.000 0.000 52124.476 44208.020 187224.736 112568.868 0.000 48284.430 88139.465 0.000 -22400.97 0.000 -82367.75 -17440.24


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.24 4637.69 0.00 1546.19 2255.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-JAN-14:23 0.00 0.00 0.00 -0.4 0.00 0.00 115.18 103.05 1084.62 2742.32 0.00 614.75 496.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 14-OCT-13:30 0.00 0.00 0.00 -0.6 0.00 0.00 115.21 103.05 1099.93 3502.37 0.00 1118.21 863.63 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.46 384.73 1363.24 4685.53 0.00 1546.20 327.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-18:18 0.00 0.00 0.00 -0.4 0.00 0.00 426.35 721.37 1734.73 441.10 0.00 1266.00 644.08 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.24 2260.71 0.00 1590.84 865.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.24 4613.26 0.00 1197.41 1032.05 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 1734.73 455.53 0.00 962.85 1320.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.46 384.73 1363.24 2209.70 0.00 1230.55 1739.19 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 384.73 1363.24 4660.30 0.00 1197.40 889.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.5 0.00 0.00 427.04 721.37 1734.73 480.90 0.00 962.85 1270.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-16:05 0.00 0.00 0.00 -0.6 0.00 0.00 140.45 384.73 1363.24 2253.41 0.00 1230.54 1573.48 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 262.70 535.87 1675.86 1531.32 0.00 1435.19 3460.58 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 262.74 535.87 1675.86 1492.39 0.00 1435.58 3504.98 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.24 4550.98 0.00 1541.21 2826.96 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1734.73 457.00 0.00 1303.54 3084.10 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUL-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1734.73 432.23 0.00 1303.54 3101.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-JUL-16:23 0.00 0.00 0.00 -0.9 0.00 0.00 140.46 384.73 1363.24 4594.83 0.00 1541.21 2795.85 0.00 0.00 0.00 0.00 0.00
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-16:23 0.00 0.00 0.00 -11.5 0.00 0.00 2526.08 6925.11 24538.23 45613.78 0.00 25235.65 55090.45 0.00 0.00 0.00 -22010.3 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3408.10 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2048.1 0.00 -3134.6 -218.2
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3720.11 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -831.7 0.00 -2953.0 -1928.1
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5316.89 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2045.3 0.00 -3134.6 -2129.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5356.05 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2054.0 0.00 -3134.6 -2160.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 3831.29 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -840.2 0.00 -2953.0 -2030.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-FEB-07:00 0.00 0.00 5374.35 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2053.2 0.00 -3134.6 -2179.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4151.18 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2084.0 0.00 -2282.6 -1777.3
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 2595.64 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -845.9 0.00 -2100.7 -1641.7
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4229.84 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2080.5 0.00 -2282.6 -1859.5
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4286.30 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2091.6 0.00 -2282.6 -1904.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 04-FEB-07:15 0.00 0.00 2758.47 0.00 0.00 0.00 464.78 343.51 1218.74 0.00 0.00 0.00 0.00 0.00 -791.2 0.00 -2056.6 -1937.6
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 04-FEB-07:00 0.00 0.00 4315.53 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2090.2 0.00 -2282.6 -1935.5
LIVING_UNIT3_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5939.98 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2075.5 0.00 -3141.7 -2715.5
LIVING_UNIT3_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5865.52 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2063.8 0.00 -3141.7 -2652.7
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5811.23 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2066.1 0.00 -3141.7 -2596.1
LIVING_UNIT2_BACKROW_TOPFLOOR 04-FEB-07:15 0.00 0.00 4376.55 0.00 0.00 0.00 464.78 343.51 1218.74 0.00 0.00 0.00 0.00 0.00 -783.8 0.00 -2911.5 -2708.3
LIVING_UNIT2_FRONTROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 4231.21 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -836.2 0.00 -2959.7 -2428.1
LIVING_UNIT1_BACKROW_TOPFLOOR 04-FEB-07:00 0.00 0.00 5914.57 0.00 0.00 0.00 526.31 384.73 1081.66 0.00 0.00 0.00 0.00 0.00 -2076.6 0.00 -3141.7 -2689.0
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 04-FEB-07:00 0.00 0.00 81463.21 0.00 0.00 0.00 9473.52 6925.11 19469.92 0.00 0.00 1178.19 0.00 0.00 -29888.5 0.00 -50262.1 -38359.4



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 430.525 2.00 2.00 1.00 44.9950 430.525 0.105 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 192.961 2.00 2.00 1.00 44.9950 192.961 0.233 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 253.447 2.00 2.00 1.00 44.9950 253.447 0.178 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 354.000 2.00 2.00 1.00 44.9950 354.000 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 199.332 2.00 2.00 1.00 44.9950 199.332 0.226 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 257.906 2.00 2.00 1.00 44.9950 257.906 0.174 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 364.887 2.00 2.00 1.00 44.9950 364.887 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 210.237 2.00 2.00 1.00 44.9950 210.237 0.214 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.312 2.00 2.00 1.00 44.9950 262.312 0.172 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 366.457 2.00 2.00 1.00 44.9950 366.457 0.123 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.070 2.00 2.00 1.00 44.9950 216.070 0.208 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.393 2.00 2.00 1.00 44.9950 266.393 0.169 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.389 2.00 2.00 1.00 44.9950 446.389 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 288.968 2.00 2.00 1.00 44.9950 288.968 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.871 2.00 2.00 1.00 44.9950 329.871 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.828 2.00 2.00 1.00 44.9950 446.828 0.101 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.568 2.00 2.00 1.00 44.9950 291.568 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.733 2.00 2.00 1.00 44.9950 330.733 0.136 1.000 44.9950 0.14


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 45.038 2.00 2.00 1.00 44.9950 45.038 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 58.756 2.00 2.00 1.00 44.9950 58.756 1.000 1.000 44.9950 0.77
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 80.590 2.00 2.00 1.00 44.9950 80.590 1.000 1.000 44.9950 0.56
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 80.616 2.00 2.00 1.00 44.9950 80.616 1.000 1.000 44.9950 0.56
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 58.733 2.00 2.00 1.00 44.9950 58.733 1.000 1.000 44.9950 0.77
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 80.513 2.00 2.00 1.00 44.9950 80.513 1.000 1.000 44.9950 0.56
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 68.362 2.00 2.00 1.00 44.9950 68.362 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.317 2.00 2.00 1.00 44.9950 46.317 1.000 1.000 44.9950 0.97
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.332 2.00 2.00 1.00 44.9950 68.332 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.375 2.00 2.00 1.00 44.9950 68.375 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.281 2.00 2.00 1.00 44.9950 46.281 1.000 1.000 44.9950 0.97
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.246 2.00 2.00 1.00 44.9950 68.246 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 91.130 2.00 2.00 1.00 44.9950 91.130 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 69.015 2.00 2.00 1.00 44.9950 69.015 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.074 2.00 2.00 1.00 44.9950 91.074 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.172 2.00 2.00 1.00 44.9950 91.172 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.020 2.00 2.00 1.00 44.9950 69.020 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.044 2.00 2.00 1.00 44.9950 91.044 1.000 1.000 44.9950 0.49


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   430.525 430.5252 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   192.961 192.9606 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   253.447 253.4475 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   354.000 353.9998 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   199.332 199.3323 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   257.906 257.9057 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   364.887 364.8868 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   210.237 210.2370 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   262.312 262.3123 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   366.457 366.4565 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   216.070 216.0697 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   266.393 266.3934 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   330.733 330.7329 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   329.871 329.8706 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   446.389 446.3895 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   291.568 291.5680 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   288.968 288.9676 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   446.828 446.8281 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 430.53 430.525 430.53 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 192.96 192.961 192.96 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 253.45 253.447 253.45 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 354.00 354.000 354.00 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 199.33 199.332 199.33 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 257.91 257.906 257.91 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 364.89 364.887 364.89 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 210.24 210.237 210.24 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.31 262.312 262.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 366.46 366.457 366.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.07 216.070 216.07 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.39 266.393 266.39 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.39 446.389 446.39 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 288.97 288.968 288.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.87 329.871 329.87 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.83 446.828 446.83 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.57 291.568 291.57 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.73 330.733 330.73 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   45.038 45.038 45.038 44.9950 0.999 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   58.756 58.756 58.756 44.9950 0.766 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   80.590 80.590 80.590 44.9950 0.558 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   80.616 80.616 80.616 44.9950 0.558 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   58.733 58.733 58.733 44.9950 0.766 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   80.513 80.513 80.513 44.9950 0.559 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   68.362 68.362 68.362 44.9950 0.658 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   46.317 46.317 46.317 44.9950 0.971 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   68.332 68.332 68.332 44.9950 0.658 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   68.375 68.375 68.375 44.9950 0.658 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   46.281 46.281 46.281 44.9950 0.972 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   68.246 68.246 68.246 44.9950 0.659 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   91.044 91.044 91.044 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   91.074 91.074 91.074 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   91.130 91.130 91.130 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   69.020 69.020 69.020 44.9950 0.652 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   69.015 69.015 69.015 44.9950 0.652 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   91.172 91.172 91.172 44.9950 0.494 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 45.04 45.038 45.04 45.04 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 58.76 58.756 58.76 58.76 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 80.59 80.590 80.59 80.59 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 80.62 80.616 80.62 80.62 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 58.73 58.733 58.73 58.73 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 80.51 80.513 80.51 80.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 68.36 68.362 68.36 68.36 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 46.32 46.317 46.32 46.32 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 68.33 68.332 68.33 68.33 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 68.38 68.375 68.38 68.38 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 46.28 46.281 46.28 46.28 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 68.25 68.246 68.25 68.25 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 91.13 91.130 91.13 91.13 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 69.02 69.015 69.02 69.02 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 91.07 91.074 91.07 91.07 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 91.17 91.172 91.17 91.17 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 69.02 69.020 69.02 69.02 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 91.04 91.044 91.04 91.04 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Sec1.1A-General Information

Data
Weather File ANNUAL ** Miami Intl Ap FL USA TMY3 WMO#=722020
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
UNHEATEDBSMT 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1.50
Number of hours not met 1.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 1812.17 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 66.85 0.00 0.00 0.00 0.00
Space Heating 2023.18 21601.58 0.00 0.00 0.00 0.00
Space Cooling 45330.50 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 7135.46 1699.31 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 27767.08 35414.80 0.00 0.00 0.00 0.00
Receptacle Equipment 87803.80 10147.25 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 185562.82   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299798.81 633588.91
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299798.81 633588.91


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.05
Space Cooling 1.16
Fans-Interior 0.18
Service Water Heating 0.71
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 4.76


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 6.98
Space Heating 1.09
Space Cooling 24.43
Fans-Interior 3.85
Service Water Heating 14.96
Receptacle Equipment 47.32
Miscellaneous 1.38



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 430.53
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 192.96
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 253.45
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 354.00
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 199.33
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 257.91
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 364.89
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 210.24
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 262.31
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 366.46
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 216.07
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 266.39
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 330.73
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 329.87
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 446.39
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 291.57
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 288.97
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 446.83
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 430.53
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 192.96
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 253.45
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 354.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 199.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 257.91
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 364.89
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 210.24
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 262.31
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 366.46
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 216.07
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 266.39
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 446.39
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 288.97
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 329.87
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 446.83
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 291.57
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 330.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 430.53 1.27 0.707770
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 192.96 0.643068 0.676083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 253.45 0.844649 0.676083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 354.00 1.10 0.694079
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 199.33 0.664302 0.676083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 257.91 0.859506 0.676083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 364.89 1.09 0.703770
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 210.24 0.700644 0.676083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 262.31 0.848861 0.683397
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 366.46 1.09 0.704515
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 216.07 0.720082 0.676083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 266.39 0.858251 0.684519
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 446.39 1.30 0.710504
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 288.97 0.932389 0.684136
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 329.87 1.04 0.690006
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 446.83 1.31 0.710573
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 291.57 0.935574 0.685544
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 330.73 1.04 0.690963
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 430.53 430.53 430.53 3619.25 1.27 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 192.96 192.96 192.96 4361.02 0.643068 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 253.45 253.45 253.45 5541.58 0.844649 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 354.00 354.00 354.00 5542.99 1.10 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 199.33 199.33 199.33 4359.78 0.664302 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 257.91 257.91 257.91 5537.47 0.859506 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 364.89 364.89 364.89 4880.39 1.09 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 210.24 210.24 210.24 3688.44 0.700644 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 262.31 262.31 262.31 4878.82 0.848861 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 366.46 366.46 366.46 4881.13 1.09 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 216.07 216.07 216.07 3686.46 0.720082 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 266.39 266.39 266.39 4874.15 0.858251 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 446.39 446.39 446.39 6111.53 1.30 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 288.97 288.97 288.97 4915.76 0.932389 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 329.87 329.87 329.87 6108.50 1.04 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 446.83 446.83 446.83 6113.81 1.31 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 291.57 291.57 291.57 4916.01 0.935574 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 330.73 330.73 330.73 6106.88 1.04 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 430.53
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 192.96
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 253.45
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 354.00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 199.33
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 257.91
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 364.89
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 210.24
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 262.31
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 366.46
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 216.07
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 266.39
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 446.39
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 288.97
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 329.87
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 446.83
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 291.57
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 330.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 3619.25
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 4361.02
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 5541.58
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 5542.99
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 4359.78
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 5537.47
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 4880.39
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 3688.44
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 4878.82
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 4881.13
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 3686.46
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 4874.15
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 6111.53
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 4915.76
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 6108.50
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 6113.81
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 4916.01
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 6106.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:44

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 623.480 29.282 11.000 0.316 29.599
February 596.961 31.569 20.600 1.071 32.640
March 660.689 38.303 21.000 0.718 39.022
April 715.917 46.420 0.000 0.000 46.420
May 744.000 59.035 0.000 0.000 59.035
June 720.000 62.445 0.000 0.000 62.445
July 744.000 66.529 0.000 0.000 66.529
August 744.000 66.451 0.000 0.000 66.451
September 720.000 62.756 0.000 0.000 62.756
October 744.000 59.769 0.000 0.000 59.769
November 685.996 45.897 6.500 0.095 45.992
December 658.079 34.204 26.500 0.921 35.125
           
Annual Sum or Average 8357.122 602.660 85.600 3.122 605.782
Minimum of Months 596.961 29.282 0.000 0.000 29.599
Maximum of Months 744.000 66.529 26.500 1.071 66.529



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 462.830 11.399 76.937 0.926 12.325
February 470.594 12.665 49.625 1.048 13.713
March 593.067 14.926 57.619 0.952 15.878
April 691.226 19.424 0.000 0.000 19.424
May 744.000 27.773 0.000 0.000 27.773
June 720.000 31.310 0.000 0.000 31.310
July 744.000 33.512 0.000 0.000 33.512
August 744.000 33.492 0.000 0.000 33.492
September 720.000 32.086 0.000 0.000 32.086
October 744.000 30.039 0.000 0.000 30.039
November 632.950 21.648 22.875 0.329 21.977
December 510.193 13.900 61.500 1.179 15.079
           
Annual Sum or Average 7776.860 282.173 268.557 4.434 286.608
Minimum of Months 462.830 11.399 0.000 0.000 12.325
Maximum of Months 744.000 33.512 76.937 1.179 33.512



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 435.139 12.860 109.083 2.024 14.883
February 454.864 14.986 66.208 1.818 16.804
March 584.072 18.486 59.687 1.371 19.857
April 680.514 25.021 5.750 0.043 25.064
May 742.500 35.258 0.000 0.000 35.258
June 720.000 39.699 0.000 0.000 39.699
July 744.000 42.462 0.000 0.000 42.462
August 744.000 41.566 0.000 0.000 41.566
September 720.000 39.596 0.000 0.000 39.596
October 744.000 36.094 0.000 0.000 36.094
November 616.267 25.018 28.821 0.641 25.660
December 471.257 15.066 80.250 2.187 17.253
           
Annual Sum or Average 7656.612 346.111 349.801 8.085 354.196
Minimum of Months 435.139 12.860 0.000 0.000 14.883
Maximum of Months 744.000 42.462 109.083 2.187 42.462



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 338.464 8.259 165.000 4.359 12.618
February 401.812 12.129 96.783 3.381 15.510
March 550.679 17.845 91.375 3.119 20.964
April 671.660 25.556 6.250 0.058 25.614
May 742.500 38.079 0.000 0.000 38.079
June 720.000 42.597 0.000 0.000 42.597
July 744.000 45.900 0.000 0.000 45.900
August 744.000 44.804 0.000 0.000 44.804
September 720.000 40.456 0.000 0.000 40.456
October 744.000 34.775 0.000 0.000 34.775
November 587.079 21.962 37.125 1.171 23.132
December 402.964 11.880 116.454 4.226 16.106
           
Annual Sum or Average 7367.158 344.240 512.987 16.314 360.554
Minimum of Months 338.464 8.259 0.000 0.000 12.618
Maximum of Months 744.000 45.900 165.000 4.359 45.900



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 345.096 6.072 129.592 1.697 7.769
February 428.153 8.535 71.475 1.506 10.041
March 555.750 12.357 76.175 1.318 13.675
April 690.018 18.086 0.000 0.000 18.086
May 744.000 27.896 0.000 0.000 27.896
June 720.000 31.896 0.000 0.000 31.896
July 744.000 33.921 0.000 0.000 33.921
August 744.000 33.074 0.000 0.000 33.074
September 720.000 30.291 0.000 0.000 30.291
October 744.000 26.145 0.000 0.000 26.145
November 611.296 16.727 29.500 0.442 17.169
December 419.129 8.659 98.450 1.916 10.575
           
Annual Sum or Average 7465.442 253.660 405.192 6.878 260.538
Minimum of Months 345.096 6.072 0.000 0.000 7.769
Maximum of Months 744.000 33.921 129.592 1.916 33.921



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 342.961 7.567 141.938 2.618 10.185
February 432.067 10.927 84.250 2.240 13.167
March 557.855 15.922 68.833 1.540 17.463
April 680.410 23.756 5.750 0.045 23.800
May 742.750 35.279 0.000 0.000 35.279
June 720.000 40.115 0.000 0.000 40.115
July 744.000 42.719 0.000 0.000 42.719
August 744.000 41.101 0.000 0.000 41.101
September 720.000 37.888 0.000 0.000 37.888
October 744.000 32.437 0.000 0.000 32.437
November 604.167 20.299 32.125 0.721 21.020
December 391.096 10.044 111.458 2.933 12.977
           
Annual Sum or Average 7423.306 318.053 444.354 10.097 328.150
Minimum of Months 342.961 7.567 0.000 0.000 10.185
Maximum of Months 744.000 42.719 141.938 2.933 42.719



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 489.916 17.501 78.550 1.721 19.222
February 495.495 20.094 47.750 1.772 21.866
March 616.171 25.204 54.083 1.567 26.772
April 696.858 32.148 0.000 0.000 32.148
May 744.000 42.976 0.000 0.000 42.976
June 720.000 46.798 0.000 0.000 46.798
July 744.000 50.715 0.000 0.000 50.715
August 744.000 50.126 0.000 0.000 50.126
September 720.000 47.183 0.000 0.000 47.183
October 744.000 44.052 0.000 0.000 44.052
November 647.188 31.719 21.000 0.537 32.256
December 540.987 21.450 60.861 2.125 23.575
           
Annual Sum or Average 7902.615 429.968 262.244 7.723 437.691
Minimum of Months 489.916 17.501 0.000 0.000 19.222
Maximum of Months 744.000 50.715 78.550 2.125 50.715



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 548.054 14.806 32.125 0.328 15.134
February 534.078 15.913 29.063 0.577 16.490
March 631.900 18.798 26.750 0.455 19.253
April 704.342 23.592 0.000 0.000 23.592
May 744.000 31.364 0.000 0.000 31.364
June 720.000 34.587 0.000 0.000 34.587
July 744.000 37.069 0.000 0.000 37.069
August 744.000 36.766 0.000 0.000 36.766
September 720.000 35.400 0.000 0.000 35.400
October 744.000 33.776 0.000 0.000 33.776
November 672.813 25.404 11.750 0.117 25.521
December 589.407 17.611 41.500 0.646 18.256
           
Annual Sum or Average 8096.593 325.086 141.188 2.123 327.209
Minimum of Months 534.078 14.806 0.000 0.000 15.134
Maximum of Months 744.000 37.069 41.500 0.646 37.069



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 509.375 16.185 72.375 1.165 17.350
February 507.684 18.338 42.250 1.195 19.533
March 630.637 22.679 37.375 0.752 23.431
April 703.222 29.646 0.250 0.000 29.646
May 744.000 39.533 0.000 0.000 39.533
June 720.000 43.730 0.000 0.000 43.730
July 744.000 46.864 0.000 0.000 46.864
August 744.000 45.671 0.000 0.000 45.671
September 720.000 43.679 0.000 0.000 43.679
October 744.000 40.557 0.000 0.000 40.557
November 650.908 29.125 19.750 0.369 29.494
December 545.663 18.711 58.625 1.504 20.215
           
Annual Sum or Average 7963.490 394.717 230.625 4.985 399.702
Minimum of Months 507.684 16.185 0.000 0.000 17.350
Maximum of Months 744.000 46.864 72.375 1.504 46.864



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 412.997 11.248 115.607 2.860 14.108
February 459.413 15.595 62.937 2.358 17.954
March 596.875 22.471 68.625 2.046 24.517
April 695.931 30.878 0.000 0.000 30.878
May 744.000 43.119 0.000 0.000 43.119
June 720.000 47.395 0.000 0.000 47.395
July 744.000 51.133 0.000 0.000 51.133
August 744.000 49.728 0.000 0.000 49.728
September 720.000 45.399 0.000 0.000 45.399
October 744.000 40.108 0.000 0.000 40.108
November 628.523 26.566 26.175 0.719 27.285
December 479.033 15.542 87.583 3.139 18.681
           
Annual Sum or Average 7688.772 399.183 360.928 11.122 410.305
Minimum of Months 412.997 11.248 0.000 0.000 14.108
Maximum of Months 744.000 51.133 115.607 3.139 51.133



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 447.247 9.000 72.125 0.828 9.828
February 493.529 11.729 46.896 0.918 12.647
March 599.137 16.226 41.237 0.679 16.905
April 703.950 22.382 0.000 0.000 22.382
May 744.000 31.486 0.000 0.000 31.486
June 720.000 35.133 0.000 0.000 35.133
July 744.000 37.453 0.000 0.000 37.453
August 744.000 36.384 0.000 0.000 36.384
September 720.000 33.720 0.000 0.000 33.720
October 744.000 30.066 0.000 0.000 30.066
November 657.267 20.575 15.500 0.187 20.762
December 512.120 12.037 71.371 1.234 13.272
           
Annual Sum or Average 7829.250 296.190 247.129 3.847 300.037
Minimum of Months 447.247 9.000 0.000 0.000 9.828
Maximum of Months 744.000 37.453 72.125 1.234 37.453



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 429.760 10.471 91.225 1.577 12.048
February 488.026 14.314 58.000 1.520 15.834
March 603.947 20.147 40.750 0.860 21.007
April 703.222 28.576 0.250 0.000 28.576
May 744.000 39.701 0.000 0.000 39.701
June 720.000 44.285 0.000 0.000 44.285
July 744.000 47.284 0.000 0.000 47.284
August 744.000 45.402 0.000 0.000 45.402
September 720.000 42.207 0.000 0.000 42.207
October 744.000 37.156 0.000 0.000 37.156
November 640.563 24.557 21.750 0.427 24.984
December 474.577 13.360 86.833 2.124 15.484
           
Annual Sum or Average 7756.094 367.458 298.808 6.508 373.967
Minimum of Months 429.760 10.471 0.000 0.000 12.048
Maximum of Months 744.000 47.284 91.225 2.124 47.284



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 440.124 18.134 114.500 3.917 22.051
February 465.590 21.478 70.250 3.264 24.742
March 597.900 27.765 74.750 3.110 30.876
April 690.771 36.689 3.875 0.039 36.728
May 744.000 50.976 0.000 0.000 50.976
June 720.000 56.171 0.000 0.000 56.171
July 744.000 60.851 0.000 0.000 60.851
August 744.000 59.354 0.000 0.000 59.354
September 720.000 55.529 0.000 0.000 55.529
October 744.000 50.372 0.000 0.000 50.372
November 620.396 35.115 29.300 1.128 36.243
December 496.200 22.539 81.417 3.924 26.463
           
Annual Sum or Average 7726.983 494.973 374.092 15.383 510.355
Minimum of Months 440.124 18.134 0.000 0.000 22.051
Maximum of Months 744.000 60.851 114.500 3.924 60.851



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 494.135 15.456 79.100 1.430 16.886
February 491.553 17.372 47.500 1.477 18.849
March 609.258 21.419 54.333 1.313 22.732
April 697.771 28.088 0.000 0.000 28.088
May 744.000 39.083 0.000 0.000 39.083
June 720.000 43.575 0.000 0.000 43.575
July 744.000 46.791 0.000 0.000 46.791
August 744.000 45.641 0.000 0.000 45.641
September 720.000 43.476 0.000 0.000 43.476
October 744.000 40.052 0.000 0.000 40.052
November 648.675 28.827 20.750 0.445 29.272
December 544.476 18.774 61.642 1.749 20.523
           
Annual Sum or Average 7901.869 388.553 263.325 6.414 394.967
Minimum of Months 491.553 15.456 0.000 0.000 16.886
Maximum of Months 744.000 46.791 79.100 1.749 46.791



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 460.210 16.813 98.875 2.510 19.323
February 481.423 19.696 60.250 2.177 21.873
March 610.582 25.093 57.042 1.586 26.679
April 697.474 33.993 3.500 0.030 34.023
May 744.000 47.066 0.000 0.000 47.066
June 720.000 52.496 0.000 0.000 52.496
July 744.000 56.354 0.000 0.000 56.354
August 744.000 54.340 0.000 0.000 54.340
September 720.000 51.560 0.000 0.000 51.560
October 744.000 46.611 0.000 0.000 46.611
November 628.529 32.412 25.125 0.742 33.155
December 501.297 19.865 75.975 2.746 22.612
           
Annual Sum or Average 7795.515 456.299 320.767 9.791 466.090
Minimum of Months 460.210 16.813 0.000 0.000 19.323
Maximum of Months 744.000 56.354 98.875 2.746 56.354



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 391.123 13.413 142.653 5.007 18.421
February 442.396 18.331 81.500 3.815 22.145
March 589.625 26.341 80.750 3.381 29.722
April 690.692 36.268 4.062 0.040 36.308
May 744.000 51.072 0.000 0.000 51.072
June 720.000 56.426 0.000 0.000 56.426
July 744.000 61.059 0.000 0.000 61.059
August 744.000 59.228 0.000 0.000 59.228
September 720.000 54.745 0.000 0.000 54.745
October 744.000 47.795 0.000 0.000 47.795
November 607.616 31.095 33.375 1.304 32.399
December 450.591 17.869 103.083 4.922 22.791
           
Annual Sum or Average 7588.042 473.643 445.424 18.468 492.111
Minimum of Months 391.123 13.413 0.000 0.000 18.421
Maximum of Months 744.000 61.059 142.653 5.007 61.059



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 424.601 10.881 105.746 2.155 13.036
February 466.423 14.395 60.150 1.900 16.294
March 596.017 20.109 60.821 1.513 21.622
April 697.702 27.810 0.000 0.000 27.810
May 744.000 39.358 0.000 0.000 39.358
June 720.000 44.023 0.000 0.000 44.023
July 744.000 47.211 0.000 0.000 47.211
August 744.000 45.738 0.000 0.000 45.738
September 720.000 42.937 0.000 0.000 42.937
October 744.000 37.774 0.000 0.000 37.774
November 634.578 25.063 25.167 0.546 25.609
December 487.946 14.252 84.861 2.489 16.741
           
Annual Sum or Average 7723.267 369.551 336.746 8.602 378.153
Minimum of Months 424.601 10.881 0.000 0.000 13.036
Maximum of Months 744.000 47.211 105.746 2.489 47.211



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 403.099 12.344 118.361 3.028 15.373
February 465.614 16.790 73.869 2.525 19.316
March 597.595 23.797 61.000 1.694 25.491
April 697.599 33.705 3.500 0.030 33.735
May 744.000 47.250 0.000 0.000 47.250
June 720.000 52.821 0.000 0.000 52.821
July 744.000 56.653 0.000 0.000 56.653
August 744.000 54.362 0.000 0.000 54.362
September 720.000 51.004 0.000 0.000 51.004
October 744.000 44.453 0.000 0.000 44.453
November 622.163 28.813 28.875 0.820 29.632
December 452.037 15.519 100.215 3.439 18.959
           
Annual Sum or Average 7654.106 437.512 385.820 11.536 449.048
Minimum of Months 403.099 12.344 0.000 0.000 15.373
Maximum of Months 744.000 56.653 118.361 3.439 56.653



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 9.48 0.00
February 0.00 35.52 0.00
March 0.00 21.51 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 2.95 0.00
December 0.00 27.59 0.00
       
Annual Sum or Average 0.00 7.94 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 35.52 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 74.61 0.00
February 0.00 93.42 0.00
March 0.00 76.65 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 27.42 0.00
December 0.00 94.95 0.00
       
Annual Sum or Average 0.00 30.33 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 94.95 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 157.68 0.00
February 0.00 156.85 0.00
March 0.00 106.81 0.00
April 0.00 3.48 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 51.63 0.00
December 0.00 170.41 0.00
       
Annual Sum or Average 0.00 53.50 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 170.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 243.21 0.00
February 0.00 208.87 0.00
March 0.00 174.01 0.00
April 0.00 3.34 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 67.49 0.00
December 0.00 235.81 0.00
       
Annual Sum or Average 0.00 77.31 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 243.21 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 132.28 0.00
February 0.00 129.92 0.00
March 0.00 102.70 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 35.58 0.00
December 0.00 149.30 0.00
       
Annual Sum or Average 0.00 45.53 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 149.30 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 200.34 0.00
February 0.00 189.72 0.00
March 0.00 117.86 0.00
April 0.00 3.52 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 57.02 0.00
December 0.00 224.40 0.00
       
Annual Sum or Average 0.00 65.61 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 224.40 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 82.02 0.00
February 0.00 93.53 0.00
March 0.00 74.71 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 26.46 0.00
December 0.00 101.28 0.00
       
Annual Sum or Average 0.00 31.26 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 101.28 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 20.53 0.00
February 0.00 39.92 0.00
March 0.00 28.47 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 7.55 0.00
December 0.00 40.36 0.00
       
Annual Sum or Average 0.00 11.27 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 40.36 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 77.20 0.00
February 0.00 87.69 0.00
March 0.00 49.82 0.00
April 0.00 0.03 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 25.27 0.00
December 0.00 99.70 0.00
       
Annual Sum or Average 0.00 28.06 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 99.70 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 135.75 0.00
February 0.00 123.91 0.00
March 0.00 97.11 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 35.25 0.00
December 0.00 149.00 0.00
       
Annual Sum or Average 0.00 44.84 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 149.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 50.37 0.00
February 0.00 61.79 0.00
March 0.00 41.27 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 11.77 0.00
December 0.00 75.04 0.00
       
Annual Sum or Average 0.00 19.86 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 75.04 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 102.82 0.00
February 0.00 109.72 0.00
March 0.00 56.07 0.00
April 0.00 0.03 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 28.77 0.00
December 0.00 138.45 0.00
       
Annual Sum or Average 0.00 36.04 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 138.45 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 191.12 0.00
February 0.00 176.28 0.00
March 0.00 151.74 0.00
April 0.00 1.96 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 56.88 0.00
December 0.00 191.44 0.00
       
Annual Sum or Average 0.00 63.74 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 191.44 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 86.70 0.00
February 0.00 99.13 0.00
March 0.00 79.58 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 27.85 0.00
December 0.00 106.05 0.00
       
Annual Sum or Average 0.00 33.02 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 106.05 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 165.64 0.00
February 0.00 159.05 0.00
March 0.00 104.66 0.00
April 0.00 2.03 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 50.60 0.00
December 0.00 181.21 0.00
       
Annual Sum or Average 0.00 54.87 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 181.21 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 244.14 0.00
February 0.00 205.91 0.00
March 0.00 164.83 0.00
April 0.00 2.03 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 65.68 0.00
December 0.00 239.96 0.00
       
Annual Sum or Average 0.00 76.48 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 244.14 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 129.47 0.00
February 0.00 126.36 0.00
March 0.00 90.92 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 33.90 0.00
December 0.00 149.52 0.00
       
Annual Sum or Average 0.00 43.90 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 149.52 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 199.26 0.00
February 0.00 183.96 0.00
March 0.00 111.43 0.00
April 0.00 2.02 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 55.74 0.00
December 0.00 226.29 0.00
       
Annual Sum or Average 0.00 64.46 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 226.29 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.29
February 0.00 0.00 0.34
March 0.00 0.00 0.38
April 0.00 0.00 0.47
May 0.00 0.00 0.59
June 0.00 0.00 0.65
July 0.00 0.00 0.66
August 0.00 0.00 0.67
September 0.00 0.00 0.65
October 0.00 0.00 0.60
November 0.00 0.00 0.47
December 0.00 0.00 0.34
       
Annual Sum or Average 0.00 0.00 0.51
Minimum of Months 0.00 0.00 0.29
Maximum of Months 0.00 0.00 0.67



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.16
March 0.00 0.00 0.17
April 0.00 0.00 0.23
May 0.00 0.00 0.33
June 0.00 0.00 0.39
July 0.00 0.00 0.40
August 0.00 0.00 0.40
September 0.00 0.00 0.40
October 0.00 0.00 0.36
November 0.00 0.00 0.26
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.15
February 0.00 0.00 0.19
March 0.00 0.00 0.21
April 0.00 0.00 0.29
May 0.00 0.00 0.41
June 0.00 0.00 0.48
July 0.00 0.00 0.50
August 0.00 0.00 0.49
September 0.00 0.00 0.48
October 0.00 0.00 0.42
November 0.00 0.00 0.30
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.15
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.14
March 0.00 0.00 0.19
April 0.00 0.00 0.27
May 0.00 0.00 0.40
June 0.00 0.00 0.47
July 0.00 0.00 0.49
August 0.00 0.00 0.48
September 0.00 0.00 0.44
October 0.00 0.00 0.37
November 0.00 0.00 0.24
December 0.00 0.00 0.13
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.09
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.11
March 0.00 0.00 0.14
April 0.00 0.00 0.21
May 0.00 0.00 0.33
June 0.00 0.00 0.39
July 0.00 0.00 0.40
August 0.00 0.00 0.39
September 0.00 0.00 0.37
October 0.00 0.00 0.31
November 0.00 0.00 0.20
December 0.00 0.00 0.10
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.13
March 0.00 0.00 0.18
April 0.00 0.00 0.28
May 0.00 0.00 0.41
June 0.00 0.00 0.48
July 0.00 0.00 0.50
August 0.00 0.00 0.48
September 0.00 0.00 0.46
October 0.00 0.00 0.37
November 0.00 0.00 0.24
December 0.00 0.00 0.12
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.09
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.43
June 0.00 0.00 0.49
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.45
November 0.00 0.00 0.33
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.20
March 0.00 0.00 0.21
April 0.00 0.00 0.28
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.43
September 0.00 0.00 0.43
October 0.00 0.00 0.39
November 0.00 0.00 0.30
December 0.00 0.00 0.20
       
Annual Sum or Average 0.00 0.00 0.32
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.22
March 0.00 0.00 0.25
April 0.00 0.00 0.33
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.51
October 0.00 0.00 0.45
November 0.00 0.00 0.34
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.43
June 0.00 0.00 0.49
July 0.00 0.00 0.52
August 0.00 0.00 0.50
September 0.00 0.00 0.47
October 0.00 0.00 0.40
November 0.00 0.00 0.28
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.10
February 0.00 0.00 0.15
March 0.00 0.00 0.18
April 0.00 0.00 0.26
May 0.00 0.00 0.36
June 0.00 0.00 0.42
July 0.00 0.00 0.43
August 0.00 0.00 0.42
September 0.00 0.00 0.40
October 0.00 0.00 0.35
November 0.00 0.00 0.24
December 0.00 0.00 0.14
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.10
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.11
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.32
May 0.00 0.00 0.44
June 0.00 0.00 0.51
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.41
November 0.00 0.00 0.28
December 0.00 0.00 0.15
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.11
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.50
June 0.00 0.00 0.58
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.50
November 0.00 0.00 0.36
December 0.00 0.00 0.22
       
Annual Sum or Average 0.00 0.00 0.41
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.17
February 0.00 0.00 0.21
March 0.00 0.00 0.23
April 0.00 0.00 0.32
May 0.00 0.00 0.43
June 0.00 0.00 0.50
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.50
October 0.00 0.00 0.45
November 0.00 0.00 0.33
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.17
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.23
March 0.00 0.00 0.27
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.58
October 0.00 0.00 0.51
November 0.00 0.00 0.36
December 0.00 0.00 0.21
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.20
March 0.00 0.00 0.26
April 0.00 0.00 0.36
May 0.00 0.00 0.50
June 0.00 0.00 0.58
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.56
October 0.00 0.00 0.47
November 0.00 0.00 0.32
December 0.00 0.00 0.18
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.12
February 0.00 0.00 0.17
March 0.00 0.00 0.22
April 0.00 0.00 0.31
May 0.00 0.00 0.43
June 0.00 0.00 0.51
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.49
October 0.00 0.00 0.42
November 0.00 0.00 0.29
December 0.00 0.00 0.16
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.12
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.13
February 0.00 0.00 0.19
March 0.00 0.00 0.25
April 0.00 0.00 0.37
May 0.00 0.00 0.51
June 0.00 0.00 0.59
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.57
October 0.00 0.00 0.48
November 0.00 0.00 0.32
December 0.00 0.00 0.17
       
Annual Sum or Average 0.00 0.00 0.40
Minimum of Months 0.00 0.00 0.13
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:44

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 709.97 528.59
February 0.00 0.00 700.24 470.89
March 0.00 0.00 663.12 493.71
April 0.00 0.00 612.48 441.30
May 0.00 0.00 552.78 411.56
June 0.00 0.00 508.89 366.66
July 0.00 0.00 491.69 366.07
August 0.00 0.00 500.59 372.71
September 0.00 0.00 539.15 388.47
October 0.00 0.00 593.90 442.17
November 0.00 0.00 648.27 467.09
December 0.00 0.00 695.63 517.92
         
Annual Sum or Average 0.00 0.00 600.84 5267.13
Minimum of Months 0.00 0.00 491.69 366.07
Maximum of Months 0.00 0.00 709.97 528.59