Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27

Tabular Output Report in Format: HTML

Building: MF+CZ2A+USA_TX_Houston-Bush.Intercontinental.AP.722430+gasfurnace+slab+IECC_2009

Environment: ANNUAL ** Houston Bush Intercontinental TX USA TMY3 WMO#=722430

Simulation Timestamp: 2019-02-14 08:27:59


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1013151.24 32.46 46.88
Net Site Energy 1013151.24 32.46 46.88
Total Source Energy 2141396.81 68.61 99.09
Net Source Energy 2141396.81 68.61 99.09


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.78
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 106621.28 0.00 0.00 0.00 0.00
Cooling 147489.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 263405.37 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 29743.62 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 241769.03 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 500787.74 512363.50 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 106621.28 0.00 0.00 0.00 0.00
Cooling General 147489.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 29743.62 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 241769.03 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 8.20 16.12 0.00 0.00 0.00 19.42
Other 12.19 7.59 0.00 0.00 0.00 0.00
Total 23.17 23.71 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.93 0.00 0.00 0.00 0.00 0.00
HVAC 5.68 11.16 0.00 0.00 0.00 13.45
Other 8.44 5.25 0.00 0.00 0.00 0.00
Total 16.05 16.42 0.00 0.00 0.00 13.45


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 500787.740 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 500787.740 100.00
     
Total On-Site and Utility Electric Sources 500787.740 100.00
Total Electricity End Uses 500787.740 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 5.75
Time Setpoint Not Met During Occupied Cooling 22.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2534.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
RunPeriod ANNUAL
Weather File Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Latitude [deg] 30.00
Longitude [deg] -95.4
Elevation [ft] 95.15
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
Total 31210.78     267087.66   16177.97 0.00 2126.74 2126.74 0.5202 866.97 3.0904
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 4.4634
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 02-AUG-18:15 11-FEB-07:15 - - - 01-JAN-08:15
Heating 0.00 216.21 0.00 0.00 0.00 0.00
Cooling 65.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41.30 17.85 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.98 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 148.51 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 133.76 382.56 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 216.21 0.00 0.00 0.00 0.00
Cooling General 65.34 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.52 7.91 0.00 0.00 0.00 0.00
  gas_range 0.00 7.84 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 22.66 2.10 0.00 0.00 0.00 0.00
  IECC_adj 9.39 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 9.98 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 148.51 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 115577.46 0.00 0.00 0.00
Cooling 467099.20 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 834204.80 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 94198.04 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 262077.63 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1585994.77 555402.03 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 5.35 0.00 0.00 0.00
Cooling 21.61 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 12.13 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 73.39 25.70 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 5.35 0.00 0.00 0.00
Cooling 21.61 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.36 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 12.13 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 73.39 25.70 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 29.12 0.00 29.12 Wetbulb [F] 551.21 0.00
HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 96.80 18.18 76.64 Wetbulb [F] 689.01 170.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.651 0.260 0.882              
North Total or Average           531.68 0.651 0.260 0.882              
Non-North Total or Average           1595.05 0.651 0.260 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   26985.21 20431.53 6553.69 0.76 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10881.40 7493.99 3387.41 0.69 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12756.56 8976.34 3780.23 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   16738.34 12083.55 4654.79 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10847.54 7505.97 3341.57 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12858.30 9057.47 3800.83 0.70 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16188.55 11806.31 4382.23 0.73 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10432.85 7291.97 3140.88 0.70 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12723.88 8885.54 3838.34 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16082.12 11738.02 4344.11 0.73 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10487.51 7354.17 3133.34 0.70 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12188.24 8651.37 3536.87 0.71 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   19127.25 14014.98 5112.27 0.73 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13389.94 9497.11 3892.83 0.71 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15153.81 10829.66 4324.15 0.71 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   19078.67 13997.32 5081.35 0.73 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13400.76 9530.60 3870.15 0.71 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15157.22 10832.47 4324.75 0.71 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.2 3.34 11.39 12.07 11.70
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.47 11.85 12.58 12.46
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.0 3.44 11.75 12.46 12.29
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.3 3.41 11.62 12.32 12.08
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.47 11.83 12.55 12.42
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.0 3.44 11.74 12.46 12.28
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.39 11.57 12.27 12.00
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.45 11.78 12.50 12.34
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.0 3.45 11.78 12.50 12.35
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.3 3.39 11.57 12.27 11.99
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.45 11.76 12.48 12.31
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.0 3.43 11.70 12.42 12.22
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.5 3.38 11.55 12.24 11.96
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.1 3.43 11.71 12.42 12.22
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.2 3.42 11.67 12.38 12.16
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.5 3.38 11.54 12.24 11.95
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.43 11.69 12.40 12.20
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.2 3.42 11.67 12.38 12.16
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   4509.35 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   8591.31 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   11073.51 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   11077.50 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   8654.57 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   11073.58 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   9737.79 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   7401.58 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   9896.71 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   9901.20 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   7419.60 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   9897.43 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12569.70 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   10108.96 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12593.42 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   12600.35 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   10118.61 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   12597.62 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 897.93 338.69 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 286.10 107.91 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 354.88 133.86 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 496.81 187.39 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 288.81 108.94 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 358.68 135.29 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 492.70 185.84 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 285.21 107.58 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 347.05 130.91 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 490.41 184.98 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 289.15 109.07 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 346.71 130.78 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 588.81 222.10 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 380.16 143.39 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 438.55 165.42 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 589.15 222.22 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 383.10 144.50 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 438.69 165.47 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 21021.68 21021.68 17.51 897.933 897.933 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00867 92.89 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6698.02 6698.02 5.58 286.096 286.096 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00974 91.76 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8308.46 8308.46 6.92 354.878 354.878 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00944 91.94 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11630.89 11630.89 9.69 496.805 496.805 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00914 92.89 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6761.55 6761.55 5.63 288.807 288.807 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00976 90.39 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8397.52 8397.52 6.99 358.682 358.682 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00942 91.94 0.01519 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11535.03 11535.03 9.61 492.696 492.696 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00891 92.89 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6677.45 6677.45 5.56 285.208 285.208 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00944 90.39 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8123.50 8123.50 6.77 347.051 347.051 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00916 96.80 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11481.45 11481.45 9.56 490.407 490.407 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00892 92.44 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6769.78 6769.78 5.64 289.152 289.152 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00944 89.71 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8117.49 8117.49 6.76 346.714 346.714 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00918 91.94 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 10270.33 10270.33 8.55 438.688 438.688 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00927 92.44 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10267.13 10267.13 8.55 438.551 438.551 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00927 92.44 0.01519 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 13784.92 13784.92 11.48 588.814 588.814 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00898 92.89 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8969.10 8969.10 7.47 383.100 383.100 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00940 90.39 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8900.20 8900.20 7.41 380.159 380.159 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00940 91.07 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 13792.77 13792.77 11.49 589.149 589.149 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00898 92.44 0.01519 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6606.38 6606.38 5.50 120.635 120.635 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00614 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9125.33 9125.33 7.60 166.628 166.628 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00640 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9129.37 9129.37 7.60 166.702 166.702 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00640 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6670.57 6670.57 5.56 121.807 121.807 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.99 0.00616 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9125.39 9125.39 7.60 166.629 166.629 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00640 29.12 0.00331 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7769.72 7769.72 6.47 141.883 141.883 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00664 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5398.91 5398.91 4.50 98.592 98.592 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00643 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7930.98 7930.98 6.61 144.828 144.828 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00667 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7935.53 7935.53 6.61 144.911 144.911 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00667 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5417.20 5417.20 4.51 98.926 98.926 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00643 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7931.71 7931.71 6.61 144.841 144.841 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00667 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 10671.97 10671.97 8.89 194.869 194.869 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00655 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 10667.71 10667.71 8.89 194.791 194.791 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00655 29.12 0.00331 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10643.64 10643.64 8.87 194.351 194.351 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00654 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8156.26 8156.26 6.79 148.935 148.935 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.99 0.00636 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8146.47 8146.47 6.79 148.757 148.757 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.99 0.00636 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10674.74 10674.74 8.89 194.919 194.919 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00655 29.12 0.00331 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 897.93 897.93 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 286.10 286.10 120.63 120.63
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 354.88 354.88 166.63 166.63
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 496.81 496.81 166.70 166.70
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 288.81 288.81 121.81 121.81
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.68 358.68 166.63 166.63
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 492.70 492.70 141.88 141.88
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 285.21 285.21 98.59 98.59
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 347.05 347.05 144.83 144.83
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 490.41 490.41 144.91 144.91
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 289.15 289.15 98.93 98.93
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 346.71 346.71 144.84 144.84
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 588.81 588.81 194.35 194.35
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 380.16 380.16 148.76 148.76
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 438.55 438.55 194.79 194.79
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 589.15 589.15 194.92 194.92
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 383.10 383.10 148.94 148.94
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 438.69 438.69 194.87 194.87


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3257.00 3172.25 12.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5326.25 4640.75 2063.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5420.75 4591.25 1908.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5321.50 5225.75 2257.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5216.25 5117.25 2143.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5296.00 4921.00 1947.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5521.75 4138.75 1590.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5355.25 3497.25 1165.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5424.25 3795.50 1251.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5367.00 4483.00 1646.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5252.00 3944.00 1212.75
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5333.50 4165.25 1336.25
LIVING_UNIT3_BACKROW_TOPFLOOR 5464.00 4581.50 1759.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 5546.25 4367.50 1727.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 5592.00 4679.25 2017.25
LIVING_UNIT2_BACKROW_TOPFLOOR 5335.25 4672.00 1806.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 5432.75 4370.00 1757.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5505.25 4884.50 2076.25
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 5847.00 5619.00 2534.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 6.00 0.00 6.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.50 7.50 0.50 7.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3.75 17.75 3.75 17.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5.75 4.50 5.75 4.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.25 3.75 1.25 3.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3.75 5.25 3.75 5.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 3.00 0.00 3.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 1.00 0.00 1.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 5.50 0.00 5.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 2.00 0.00 2.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 4.00 0.00 4.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3.25 14.75 3.25 14.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 2.75 16.75 2.75 16.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 2.50 6.50 2.50 6.50
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 6.50 0.00 6.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 8.25 0.00 8.25
LIVING_UNIT1_BACKROW_TOPFLOOR 4.25 6.50 4.25 6.50
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 5.75 22.00 5.75 22.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.222 0.000 0.268
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.193 0.000 0.268
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.219 0.000 0.268
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.219 0.000 0.268
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.193 0.000 0.268
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.219 0.000 0.268
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.096 0.000 0.268
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.268
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.096 0.000 0.268
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.096 0.000 0.268
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.070 0.000 0.268
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.096 0.000 0.268
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.219 0.000 0.268
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.219 0.000 0.268
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.219 0.000 0.268
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.193 0.000 0.268
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.193 0.000 0.268
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.219 0.000 0.268
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1866
Defaulted Fields 490
Fields with Defaults 4870
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 89
Autocalculatable Fields 268



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
Electricity:Building 91754.37 7056.43 02-JAN-03:15 17558.18 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 77145.04 6525.11 02-JAN-04:15 12799.44 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
Fans:Electricity 8711.18 95.46 20-MAR-23:45 2924.33 02-AUG-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
ElectricityPurchased:Plant 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
Cogeneration:ElectricityPurchased 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
ElectricityNet:Plant 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
Cogeneration:ElectricityNet 146668.58 8185.21 09-MAR-03:15 39173.65 02-AUG-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 51907.28 459.03 10-FEB-20:30 22331.43 02-AUG-16:15
General:Fans:Electricity 8711.18 95.46 20-MAR-23:45 2924.33 02-AUG-17:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 43196.09 0.00 05-JAN-04:45 19411.23 02-AUG-16:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 5123.64 2644.47 30-JAN-03:15 382288.98 11-FEB-07:15
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 2417.69 0.00 01-JAN-00:15 148569.66 11-FEB-08:45
WaterSystems:Gas 2417.69 0.00 01-JAN-00:15 148569.66 11-FEB-08:45
Water Heater:WaterSystems:Gas 2417.69 0.00 01-JAN-00:15 148569.66 11-FEB-08:45
Gas:HVAC 1066.21 0.00 06-JAN-13:15 217976.16 11-FEB-07:00
Heating:Gas 1066.21 0.00 06-JAN-13:15 217976.16 11-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 14-FEB-02:30 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
PlantLoopHeatingDemand:Plant 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
WaterSystems:PlantLoopHeatingDemand 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1360182.51 15348.66 16-OCT-02:15 451692.41 04-AUG-18:15
EnergyTransfer:Building 524115.59 6675.58 01-NOV-02:45 197604.41 01-AUG-17:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 89596.49 0.00 06-JAN-13:15 184136.33 11-FEB-07:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 434519.10 0.00 05-JAN-04:45 197604.41 01-AUG-17:30
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 89933.29 0.00 05-JAN-04:45 21489.22 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17.22 0.00 01-JAN-00:15 3262.96 11-FEB-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 89916.07 0.00 05-JAN-04:45 21489.22 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 20532.13 0.00 01-JAN-10:45 8988.70 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3531.00 0.00 01-JAN-10:45 8988.70 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17001.14 0.00 01-JAN-00:15 7743.13 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 26543.61 0.00 01-JAN-10:00 11598.89 11-FEB-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5731.40 0.00 01-JAN-10:00 11598.89 11-FEB-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20812.22 0.00 01-JAN-00:15 9379.06 01-AUG-15:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 25844.50 0.00 01-JAN-14:30 12649.17 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6727.53 0.00 01-JAN-14:30 11804.65 11-FEB-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 19116.96 0.00 01-JAN-00:15 12649.17 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 19412.11 0.00 01-JAN-17:15 9055.27 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4481.25 0.00 01-JAN-17:15 9055.27 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14930.87 0.00 01-JAN-00:15 7657.67 01-AUG-18:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 25320.56 0.00 06-JAN-12:30 11608.87 11-FEB-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6534.29 0.00 06-JAN-12:30 11608.87 11-FEB-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18786.27 0.00 01-JAN-00:15 9258.86 01-AUG-18:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 26519.53 0.00 01-JAN-11:30 12470.57 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4022.43 0.00 01-JAN-11:30 10004.34 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 22497.10 0.00 01-JAN-00:15 12470.57 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20695.83 0.00 01-JAN-10:45 7569.35 01-AUG-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2273.02 0.00 01-JAN-10:45 6594.66 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 18422.80 0.00 01-JAN-00:15 7569.35 01-AUG-18:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 26331.23 0.00 01-JAN-10:00 10100.61 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4224.58 0.00 01-JAN-10:00 10100.61 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22106.65 0.00 01-JAN-00:15 9252.23 01-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 25423.30 0.00 01-JAN-14:30 12363.22 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5121.04 0.00 01-JAN-14:30 10176.29 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20302.26 0.00 01-JAN-00:15 12363.22 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 19224.00 0.00 01-JAN-16:00 7580.24 01-AUG-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2961.01 0.00 01-JAN-16:00 6736.58 11-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16262.99 0.00 01-JAN-00:15 7580.24 01-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24970.66 0.00 01-JAN-14:30 10175.81 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4941.86 0.00 01-JAN-14:30 10175.81 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20028.80 0.00 01-JAN-00:15 9046.77 01-AUG-17:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 30372.15 0.00 01-JAN-14:45 13225.85 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 7516.38 0.00 01-JAN-14:45 13225.85 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 22855.78 0.00 01-JAN-00:15 11357.40 01-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 30933.74 0.00 01-JAN-11:30 13221.31 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 6798.51 0.00 01-JAN-11:30 13221.31 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 24135.24 0.00 01-JAN-00:15 11360.38 01-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 31515.21 0.00 01-JAN-12:30 14737.79 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 6986.16 0.00 01-JAN-12:30 13397.92 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24529.06 0.00 01-JAN-00:15 14737.79 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 24494.69 0.00 01-JAN-15:30 10631.38 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5357.12 0.00 01-JAN-15:30 10631.38 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 19137.57 0.00 01-JAN-00:15 9877.93 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 25075.92 0.00 01-JAN-12:00 10607.30 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4613.69 0.00 01-JAN-12:00 10607.30 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20462.22 0.00 01-JAN-00:15 9865.41 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 30973.12 0.00 01-JAN-14:30 14705.04 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 7758.01 0.00 01-JAN-14:30 13428.87 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 23215.11 0.00 01-JAN-00:15 14705.04 01-AUG-17:30
EnergyTransfer:Plant 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
WaterSystems:EnergyTransfer 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 115262.40 850.45 27-JUL-02:15 32816.90 28-JAN-09:00
EnergyTransfer:HVAC 720804.52 7104.01 20-MAR-23:45 258691.84 04-AUG-18:30
HeatingCoils:EnergyTransfer 85297.02 0.00 06-JAN-13:15 174380.93 11-FEB-07:00
CoolingCoils:EnergyTransfer 635507.50 0.00 05-JAN-04:45 258691.84 04-AUG-18:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 17.222 -7488.00 0.000 0.000 2875.124 2771.241 14528.036 9280.489 0.000 2269.502 71562.995 0.000 -5240.88 0.000 -8147.70 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 3530.924 -1415.81 0.000 0.000 2954.495 2771.241 14528.036 3933.808 0.000 2143.386 0.000 0.000 -2011.27 0.000 -6974.20 -3875.31
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 5731.282 -1733.19 0.000 0.000 2969.487 2771.241 14528.036 9200.143 0.000 2267.894 0.000 0.000 -4760.52 0.000 -7316.67 -4578.72
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 6727.416 -1592.00 0.000 0.000 2974.718 2771.241 14528.036 7446.450 0.000 2271.618 0.000 0.000 -5093.36 0.000 -7225.29 -5284.02
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 4481.174 -1243.41 0.000 0.000 2964.508 2771.241 14528.036 1873.805 0.000 2145.313 0.000 0.000 -2158.85 0.000 -6857.55 -4816.79
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 6534.170 -1564.48 0.000 0.000 2976.065 2771.241 14528.036 7185.849 0.000 2269.391 0.000 0.000 -4847.29 0.000 -7230.42 -5400.77
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 4022.356 -1873.49 0.000 0.000 2954.013 2771.241 14528.036 9266.517 0.000 1670.511 0.102 0.000 -5140.70 0.000 -5391.13 -2183.89
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 2272.981 -1534.21 0.000 0.000 2939.381 2771.241 14528.036 3891.195 0.000 1545.278 0.007 0.000 -2085.81 0.000 -5024.61 -2414.87
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 4224.504 -1840.99 0.000 0.000 2956.527 2771.241 14528.036 9096.934 0.000 1670.374 0.022 0.000 -4944.97 0.000 -5387.98 -2808.04
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 5120.956 -1690.72 0.000 0.000 2962.074 2771.241 14528.036 7377.124 0.000 1672.966 0.000 0.000 -5287.81 0.000 -5320.41 -3521.99
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 2960.962 -1354.35 0.000 0.000 2950.022 2771.241 14528.036 1856.967 0.000 1547.059 0.000 0.000 -2242.24 0.000 -4943.05 -3165.94
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 4941.780 -1667.95 0.000 0.000 2964.108 2771.241 14528.036 7107.157 0.000 1670.505 0.000 0.000 -5030.54 0.000 -5321.32 -3602.13
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 7516.254 -1903.38 0.000 0.000 2972.636 2771.241 14528.036 7028.581 0.000 2250.033 0.227 0.000 -5034.02 0.000 -7276.64 -1900.33
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 6798.385 -2009.92 0.000 0.000 2967.660 2771.241 14528.036 9037.797 0.000 2249.520 0.112 0.000 -4919.58 0.000 -7340.07 -1957.78
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 6986.034 -2042.71 0.000 0.000 2967.091 2771.241 14528.036 9213.571 0.000 2251.524 0.191 0.000 -5075.79 0.000 -7329.55 -1783.29
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 5357.036 -1593.73 0.000 0.000 2961.216 2771.241 14528.036 1824.141 0.000 2129.173 0.115 0.000 -2234.88 0.000 -6910.37 -1288.02
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 4613.610 -1704.04 0.000 0.000 2954.649 2771.241 14528.036 3864.867 0.000 2126.289 0.229 0.000 -2065.30 0.000 -6982.65 -1348.54
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 7757.885 -1933.29 0.000 0.000 2971.322 2771.241 14528.036 7276.168 0.000 2254.634 0.087 0.000 -5265.13 0.000 -7276.70 -1802.50
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4854.546 45687.121 0.000 0.000 0.000 -50541.67 -1.06
Total Facility 0.000 0.000 89594.929 -36185.67 0.000 0.000 53235.096 49882.340 261504.651 115761.563 0.000 41259.517 117251.208 0.000 -73438.93 0.000 -168797.99 -51734.00


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.8 0.00 0.00 257.26 604.65 2756.77 5725.36 0.00 2222.37 9968.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.6 0.00 0.00 263.33 604.65 2756.77 843.41 0.00 2146.76 1146.01 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 01-AUG-14:55 0.00 0.00 0.00 -0.8 0.00 0.00 115.17 116.28 1545.65 3164.20 0.00 2662.03 1782.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.1 0.00 0.00 260.98 604.65 2756.77 5872.84 0.00 2260.17 919.61 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 01-AUG-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 426.23 813.96 2666.18 897.57 0.00 2045.98 835.12 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 01-AUG-18:03 0.00 0.00 0.00 -0.8 0.00 0.00 426.90 813.96 2666.18 1920.89 0.00 2185.79 1279.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.0 0.00 0.00 260.88 604.65 2756.77 5736.35 0.00 1614.44 1522.93 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-AUG-18:03 0.00 0.00 0.00 -0.6 0.00 0.00 427.04 813.96 2666.18 728.32 0.00 1417.86 1541.78 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 01-AUG-18:03 0.00 0.00 0.00 -0.8 0.00 0.00 427.04 813.96 2666.18 1763.76 0.00 1552.46 2029.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.0 0.00 0.00 261.52 604.65 2756.77 5859.85 0.00 1619.00 1287.41 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 01-AUG-18:05 0.00 0.00 0.00 -0.6 0.00 0.00 427.04 813.96 2666.18 904.13 0.00 1418.28 1359.56 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.8 0.00 0.00 263.34 604.65 2756.77 2204.70 0.00 1632.57 1618.44 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.9 0.00 0.00 260.15 604.65 2756.77 2121.99 0.00 2243.57 3395.72 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.9 0.00 0.00 259.85 604.65 2756.77 2008.78 0.00 2240.46 3514.74 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.2 0.00 0.00 258.61 604.65 2756.77 5648.94 0.00 2227.92 3277.31 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.8 0.00 0.00 262.97 604.65 2756.77 943.46 0.00 2136.55 3191.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -0.8 0.00 0.00 262.68 604.65 2756.77 832.97 0.00 2133.55 3296.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 01-AUG-17:33 0.00 0.00 0.00 -1.2 0.00 0.00 258.56 604.65 2756.77 5760.97 0.00 2227.22 3134.11 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 01-AUG-17:33 0.00 0.00 0.00 -16.5 0.00 0.00 4709.42 10883.76 49621.87 52674.82 0.00 36036.66 60083.72 0.00 0.00 0.00 -15759.0 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11-FEB-04:53 0.00 0.00 3274.13 0.00 0.00 0.00 526.31 186.05 1039.59 0.00 0.00 0.00 7041.27 0.00 -4200.0 0.00 -7867.3 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11-FEB-07:00 0.00 0.00 8988.39 0.00 0.00 0.00 529.77 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -1677.8 0.00 -6993.8 -2722.9
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11-FEB-03:53 0.00 0.00 11611.29 0.00 0.00 0.00 529.37 62.02 1040.43 0.00 0.00 0.00 0.00 0.00 -3960.1 0.00 -7787.0 -1496.0
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11-FEB-03:53 0.00 0.00 11817.76 0.00 0.00 0.00 528.80 62.02 1040.43 0.00 0.00 0.00 0.00 0.00 -4121.4 0.00 -7795.6 -1531.9
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11-FEB-07:00 0.00 0.00 9054.96 0.00 0.00 0.00 530.75 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -1733.1 0.00 -6984.6 -2744.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11-FEB-03:53 0.00 0.00 11623.95 0.00 0.00 0.00 530.37 62.02 1040.43 0.00 0.00 0.00 0.00 0.00 -4018.8 0.00 -7774.3 -1463.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 10003.89 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4282.3 0.00 -4899.4 -3224.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 6594.36 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -1711.5 0.00 -4320.4 -2965.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 10100.16 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4280.4 0.00 -4899.4 -3323.0
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 10175.82 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4344.2 0.00 -4899.4 -3334.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11-FEB-08:15 0.00 0.00 6736.65 0.00 0.00 0.00 215.05 170.54 1655.54 0.00 0.00 0.00 0.00 0.00 -1544.4 0.00 -4061.6 -3171.8
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 10175.35 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4346.9 0.00 -4899.4 -3331.7
LIVING_UNIT3_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 13225.36 0.00 0.00 0.00 538.11 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4298.1 0.00 -7486.0 -3855.8
LIVING_UNIT3_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 13220.83 0.00 0.00 0.00 536.74 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4233.6 0.00 -7500.4 -3899.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 13397.41 0.00 0.00 0.00 534.40 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4240.7 0.00 -7528.5 -4039.0
LIVING_UNIT2_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 10631.00 0.00 0.00 0.00 526.34 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -1777.1 0.00 -7043.2 -4213.3
LIVING_UNIT2_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 10606.93 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -1702.3 0.00 -7047.1 -4260.2
LIVING_UNIT1_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 13428.36 0.00 0.00 0.00 535.64 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4305.1 0.00 -7515.6 -4019.6
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-FEB-07:00 0.00 0.00 184129.16 0.00 0.00 0.00 9572.15 7813.98 25960.31 0.00 0.00 708.80 0.00 0.00 -61406.5 0.00 -116221.2 -50556.7



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 897.933 2.00 2.00 1.00 44.9950 897.933 0.050 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 286.096 2.00 2.00 1.00 44.9950 286.096 0.157 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 354.878 2.00 2.00 1.00 44.9950 354.878 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 496.805 2.00 2.00 1.00 44.9950 496.805 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 288.807 2.00 2.00 1.00 44.9950 288.807 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.682 2.00 2.00 1.00 44.9950 358.682 0.125 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 492.696 2.00 2.00 1.00 44.9950 492.696 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 285.208 2.00 2.00 1.00 44.9950 285.208 0.158 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 347.051 2.00 2.00 1.00 44.9950 347.051 0.130 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 490.407 2.00 2.00 1.00 44.9950 490.407 0.092 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 289.152 2.00 2.00 1.00 44.9950 289.152 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 346.714 2.00 2.00 1.00 44.9950 346.714 0.130 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 588.814 2.00 2.00 1.00 44.9950 588.814 0.076 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 380.159 2.00 2.00 1.00 44.9950 380.159 0.118 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 438.551 2.00 2.00 1.00 44.9950 438.551 0.103 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 589.149 2.00 2.00 1.00 44.9950 589.149 0.076 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 383.100 2.00 2.00 1.00 44.9950 383.100 0.117 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 438.688 2.00 2.00 1.00 44.9950 438.688 0.103 1.000 44.9950 0.10


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 120.635 2.00 2.00 1.00 44.9950 120.635 1.000 1.000 44.9950 0.37
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 166.628 2.00 2.00 1.00 44.9950 166.628 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 166.702 2.00 2.00 1.00 44.9950 166.702 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 121.807 2.00 2.00 1.00 44.9950 121.807 1.000 1.000 44.9950 0.37
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 166.629 2.00 2.00 1.00 44.9950 166.629 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 141.883 2.00 2.00 1.00 44.9950 141.883 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 98.592 2.00 2.00 1.00 44.9950 98.592 1.000 1.000 44.9950 0.46
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 144.828 2.00 2.00 1.00 44.9950 144.828 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 144.911 2.00 2.00 1.00 44.9950 144.911 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 98.926 2.00 2.00 1.00 44.9950 98.926 1.000 1.000 44.9950 0.45
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 144.841 2.00 2.00 1.00 44.9950 144.841 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 194.351 2.00 2.00 1.00 44.9950 194.351 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 148.757 2.00 2.00 1.00 44.9950 148.757 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 194.791 2.00 2.00 1.00 44.9950 194.791 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 194.919 2.00 2.00 1.00 44.9950 194.919 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 148.935 2.00 2.00 1.00 44.9950 148.935 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 194.869 2.00 2.00 1.00 44.9950 194.869 1.000 1.000 44.9950 0.23


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   897.933 897.9334 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   286.096 286.0958 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   354.878 354.8778 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   496.805 496.8050 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   288.807 288.8073 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   358.682 358.6820 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   492.696 492.6957 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   285.208 285.2083 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   347.051 347.0508 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   490.407 490.4074 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   289.152 289.1515 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   346.714 346.7138 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   438.688 438.6879 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   438.551 438.5513 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   588.814 588.8139 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   383.100 383.1004 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   380.159 380.1588 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   589.149 589.1486 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 897.93 897.933 897.93 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 286.10 286.096 286.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 354.88 354.878 354.88 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 496.81 496.805 496.81 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 288.81 288.807 288.81 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.68 358.682 358.68 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 492.70 492.696 492.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 285.21 285.208 285.21 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 347.05 347.051 347.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 490.41 490.407 490.41 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 289.15 289.152 289.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 346.71 346.714 346.71 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 588.81 588.814 588.81 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 380.16 380.159 380.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 438.55 438.551 438.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 589.15 589.149 589.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 383.10 383.100 383.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 438.69 438.688 438.69 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   120.635 120.635 120.635 44.9950 0.373 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   166.628 166.628 166.628 44.9950 0.270 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   166.702 166.702 166.702 44.9950 0.270 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   121.807 121.807 121.807 44.9950 0.369 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   166.629 166.629 166.629 44.9950 0.270 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   141.883 141.883 141.883 44.9950 0.317 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   98.592 98.592 98.592 44.9950 0.456 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   144.828 144.828 144.828 44.9950 0.311 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   144.911 144.911 144.911 44.9950 0.311 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   98.926 98.926 98.926 44.9950 0.455 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   144.841 144.841 144.841 44.9950 0.311 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   194.869 194.869 194.869 44.9950 0.231 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   194.791 194.791 194.791 44.9950 0.231 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   194.351 194.351 194.351 44.9950 0.232 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   148.935 148.935 148.935 44.9950 0.302 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   148.757 148.757 148.757 44.9950 0.302 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   194.919 194.919 194.919 44.9950 0.231 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 120.63 120.635 120.63 120.63 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 166.63 166.628 166.63 166.63 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 166.70 166.702 166.70 166.70 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 121.81 121.807 121.81 121.81 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 166.63 166.629 166.63 166.63 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 141.88 141.883 141.88 141.88 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 98.59 98.592 98.59 98.59 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 144.83 144.828 144.83 144.83 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 144.91 144.911 144.91 144.91 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 98.93 98.926 98.93 98.93 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 144.84 144.841 144.84 144.84 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 194.35 194.351 194.35 194.35 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 148.76 148.757 148.76 148.76 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 194.79 194.791 194.79 194.79 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 194.92 194.919 194.92 194.92 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 148.94 148.935 148.94 148.94 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 194.87 194.869 194.87 194.87 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Sec1.1A-General Information

Data
Weather File ANNUAL ** Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Total gross floor area [ft2] 31210.78
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 31210.78 21609.96 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 5.75
Number of hours cooling loads not met 22.00
Number of hours not met 27.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 1066.21 216052.94 0.00 0.00
Space Cooling 43196.09 19136.58 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8711.18 2924.33 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2417.69 148402.03 0.00 0.00
Receptacle Equipment 77145.04 12095.32 1639.73 17834.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 146668.58   5123.64   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 263405.37 500787.74
Natural Gas 163973.19 512363.50
Additional 0.00 0.00
Total 427378.56 1013151.24


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.47
Space Heating 0.00
Space Cooling 1.38
Fans-Interior 0.28
Service Water Heating 0.00
Receptacle Equipment 2.47
Miscellaneous 0.10
Subtotal 4.70


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 1.00
Service Water Heating 2.27
Miscellaneous 1.54
Subtotal 4.81


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.92
Space Heating 10.52
Space Cooling 14.56
Fans-Interior 2.94
Service Water Heating 23.86
Receptacle Equipment 42.18
Miscellaneous 1.01



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 897.93
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 286.10
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 354.88
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 496.81
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 288.81
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 358.68
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 492.70
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 285.21
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 347.05
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 490.41
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 289.15
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 346.71
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 438.69
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 438.55
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 588.81
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 383.10
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 380.16
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 589.15
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 897.93
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 286.10
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 354.88
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 496.81
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 288.81
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 358.68
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 492.70
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 285.21
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 347.05
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 490.41
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 289.15
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 346.71
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 588.81
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 380.16
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 438.55
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 589.15
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 383.10
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 438.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 897.93 2.25 0.757138
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 286.10 0.906783 0.688697
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 354.88 1.06 0.703664
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 496.81 1.39 0.721909
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 288.81 0.903962 0.691952
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 358.68 1.07 0.704407
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 492.70 1.35 0.729300
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 285.21 0.869404 0.698943
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 347.05 1.06 0.698335
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 490.41 1.34 0.729880
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 289.15 0.873959 0.701232
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 346.71 1.02 0.709813
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 588.81 1.59 0.732723
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 380.16 1.12 0.709272
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 438.55 1.26 0.714649
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 589.15 1.59 0.733663
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 383.10 1.12 0.711199
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 438.69 1.26 0.714674
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 897.93 897.93 897.93 4509.35 2.25 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 286.10 286.10 286.10 8591.31 0.906783 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 354.88 354.88 354.88 11073.51 1.06 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 496.81 496.81 496.81 11077.50 1.39 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 288.81 288.81 288.81 8654.57 0.903962 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 358.68 358.68 358.68 11073.58 1.07 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 492.70 492.70 492.70 9737.79 1.35 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 285.21 285.21 285.21 7401.58 0.869404 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 347.05 347.05 347.05 9896.71 1.06 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 490.41 490.41 490.41 9901.20 1.34 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 289.15 289.15 289.15 7419.60 0.873959 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 346.71 346.71 346.71 9897.43 1.02 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 588.81 588.81 588.81 12569.70 1.59 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 380.16 380.16 380.16 10108.96 1.12 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 438.55 438.55 438.55 12593.42 1.26 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 589.15 589.15 589.15 12600.35 1.59 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 383.10 383.10 383.10 10118.61 1.12 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 438.69 438.69 438.69 12597.62 1.26 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 897.93
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 286.10
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 354.88
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 496.81
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 288.81
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 358.68
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 492.70
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 285.21
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 347.05
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 490.41
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 289.15
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 346.71
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 588.81
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 380.16
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 438.55
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 589.15
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 383.10
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 438.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 4509.35
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 8591.31
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 11073.51
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 11077.50
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 8654.57
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 11073.58
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 9737.79
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 7401.58
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 9896.71
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 9901.20
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 7419.60
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 9897.43
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 12569.70
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 10108.96
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 12593.42
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 12600.35
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 10118.61
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 12597.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:27:59

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 714.257 63.791 0.000 0.000 63.791
February 629.533 70.339 12.000 1.029 71.368
March 742.000 96.996 0.000 0.000 96.996
April 720.000 119.283 0.000 0.000 119.283
May 744.000 145.417 0.000 0.000 145.417
June 720.000 160.923 0.000 0.000 160.923
July 744.000 174.539 0.000 0.000 174.539
August 744.000 173.614 0.000 0.000 173.614
September 720.000 158.510 0.000 0.000 158.510
October 744.000 125.163 0.000 0.000 125.163
November 720.000 102.176 0.000 0.000 102.176
December 729.533 76.439 0.000 0.000 76.439
           
Annual Sum or Average 8671.324 1467.190 12.000 1.029 1468.219
Minimum of Months 629.533 63.791 0.000 0.000 63.791
Maximum of Months 744.000 174.539 12.000 1.029 174.539



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 106.567 2.363 447.052 12.836 15.199
February 188.882 4.920 292.646 9.833 14.753
March 340.904 9.265 218.866 4.861 14.127
April 509.363 17.195 54.292 0.748 17.944
May 683.149 28.980 1.000 0.001 28.981
June 715.089 40.912 0.000 0.000 40.912
July 744.000 47.573 0.000 0.000 47.573
August 744.000 47.517 0.000 0.000 47.517
September 693.909 40.601 0.000 0.000 40.601
October 527.460 21.917 63.250 1.105 23.022
November 405.597 13.797 157.825 3.400 17.197
December 222.550 5.710 344.187 9.715 15.424
           
Annual Sum or Average 5881.469 280.751 1579.118 42.499 323.250
Minimum of Months 106.567 2.363 0.000 0.000 14.127
Maximum of Months 744.000 47.573 447.052 12.836 47.573



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 89.438 2.308 522.175 19.746 22.054
February 159.118 5.394 335.292 14.495 19.888
March 316.576 10.720 251.551 7.565 18.285
April 487.757 21.015 74.750 1.415 22.430
May 675.132 37.056 9.250 0.075 37.131
June 714.188 53.025 0.000 0.000 53.025
July 744.000 61.497 0.000 0.000 61.497
August 744.000 60.613 0.000 0.000 60.613
September 677.946 50.744 0.000 0.000 50.744
October 494.685 26.166 92.917 2.176 28.342
November 373.927 15.077 195.500 5.760 20.837
December 186.010 5.670 397.607 15.259 20.930
           
Annual Sum or Average 5662.776 349.286 1879.041 66.491 415.776
Minimum of Months 89.438 2.308 0.000 0.000 18.285
Maximum of Months 744.000 61.497 522.175 19.746 61.497



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 51.950 1.241 582.687 32.161 33.402
February 132.962 4.436 373.396 22.689 27.124
March 278.708 10.086 289.571 12.145 22.231
April 461.157 22.055 96.607 2.444 24.499
May 662.124 39.680 12.750 0.124 39.804
June 712.996 56.994 0.000 0.000 56.994
July 744.000 66.120 0.000 0.000 66.120
August 744.000 63.917 0.000 0.000 63.917
September 671.124 51.451 0.000 0.000 51.451
October 443.539 22.506 116.267 3.614 26.120
November 308.427 11.433 240.938 9.725 21.159
December 127.962 3.715 458.604 24.617 28.332
           
Annual Sum or Average 5338.951 353.636 2170.820 107.519 461.154
Minimum of Months 51.950 1.241 0.000 0.000 21.159
Maximum of Months 744.000 66.120 582.687 32.161 66.120



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 47.354 0.669 570.646 16.929 17.598
February 144.996 2.935 345.017 12.110 15.045
March 294.996 6.711 260.731 5.897 12.609
April 492.754 15.787 65.667 0.879 16.666
May 683.153 28.994 1.125 0.002 28.996
June 715.308 41.825 0.000 0.000 41.825
July 744.000 48.193 0.000 0.000 48.193
August 744.000 46.934 0.000 0.000 46.934
September 692.202 37.800 0.000 0.000 37.800
October 491.185 16.015 76.269 1.330 17.344
November 320.783 8.558 209.467 4.401 12.960
December 127.583 2.785 441.496 12.496 15.281
           
Annual Sum or Average 5498.315 257.205 1970.417 54.045 311.250
Minimum of Months 47.354 0.669 0.000 0.000 12.609
Maximum of Months 744.000 48.193 570.646 16.929 48.193



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 41.812 0.681 597.745 23.369 24.050
February 132.011 3.395 376.367 16.549 19.944
March 282.209 7.937 277.292 8.300 16.237
April 476.765 19.508 81.500 1.477 20.986
May 675.810 36.842 9.250 0.074 36.916
June 714.521 53.525 0.000 0.000 53.525
July 744.000 61.686 0.000 0.000 61.686
August 744.000 59.778 0.000 0.000 59.778
September 677.646 47.814 0.000 0.000 47.814
October 476.709 20.200 96.396 2.319 22.519
November 310.839 9.772 235.575 6.619 16.391
December 113.204 2.931 483.047 17.877 20.807
           
Annual Sum or Average 5389.525 324.068 2157.171 76.585 400.652
Minimum of Months 41.812 0.681 0.000 0.000 16.237
Maximum of Months 744.000 61.686 597.745 23.369 61.686



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 118.604 3.981 453.271 21.498 25.479
February 209.708 8.178 289.950 16.014 24.192
March 359.050 15.543 216.000 7.935 23.478
April 518.442 26.938 60.321 1.386 28.324
May 683.891 43.336 3.625 0.016 43.352
June 714.683 57.649 0.000 0.000 57.649
July 744.000 66.355 0.000 0.000 66.355
August 744.000 65.719 0.000 0.000 65.719
September 684.492 55.204 0.000 0.000 55.204
October 519.716 31.073 77.786 2.231 33.305
November 401.163 19.116 165.813 6.105 25.222
December 227.681 8.442 353.083 16.835 25.277
           
Annual Sum or Average 5925.431 401.534 1619.849 72.022 473.556
Minimum of Months 118.604 3.981 0.000 0.000 23.478
Maximum of Months 744.000 66.355 453.271 21.498 66.355



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 136.125 3.161 374.517 9.781 12.942
February 242.600 6.479 254.000 7.551 14.030
March 399.667 11.857 167.958 3.285 15.142
April 568.408 20.550 29.775 0.401 20.951
May 709.185 32.332 0.000 0.000 32.332
June 718.375 42.251 0.000 0.000 42.251
July 744.000 48.198 0.000 0.000 48.198
August 744.000 48.381 0.000 0.000 48.381
September 712.792 41.264 0.000 0.000 41.264
October 586.285 24.422 41.808 0.686 25.108
November 461.941 16.118 119.000 2.327 18.445
December 263.754 7.090 296.125 7.423 14.513
           
Annual Sum or Average 6287.131 302.102 1283.183 31.454 333.556
Minimum of Months 136.125 3.161 0.000 0.000 12.942
Maximum of Months 744.000 48.381 374.517 9.781 48.381



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 108.022 2.754 469.725 16.218 18.972
February 194.512 6.285 302.579 11.974 18.259
March 367.548 12.520 214.667 5.736 18.255
April 534.834 23.105 54.750 0.918 24.023
May 695.620 38.707 3.250 0.014 38.721
June 715.417 52.159 0.000 0.000 52.159
July 744.000 59.653 0.000 0.000 59.653
August 744.000 59.121 0.000 0.000 59.121
September 689.692 49.246 0.000 0.000 49.246
October 536.989 27.180 70.750 1.532 28.712
November 407.647 16.291 165.625 4.404 20.695
December 217.323 6.388 360.000 12.632 19.020
           
Annual Sum or Average 5955.604 353.408 1641.346 53.428 406.836
Minimum of Months 108.022 2.754 0.000 0.000 18.255
Maximum of Months 744.000 59.653 469.725 16.218 59.653



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 65.183 1.597 544.542 27.540 29.137
February 168.142 5.477 337.633 19.322 24.799
March 326.875 12.373 251.896 9.587 21.960
April 505.274 25.171 70.056 1.666 26.837
May 682.696 43.033 4.667 0.024 43.057
June 714.750 58.188 0.000 0.000 58.188
July 744.000 66.532 0.000 0.000 66.532
August 744.000 64.623 0.000 0.000 64.623
September 683.107 51.856 0.000 0.000 51.856
October 488.344 24.516 94.114 2.712 27.228
November 342.273 13.118 209.538 7.860 20.978
December 147.763 4.460 424.683 21.165 25.625
           
Annual Sum or Average 5612.407 370.944 1937.128 89.876 460.821
Minimum of Months 65.183 1.597 0.000 0.000 20.978
Maximum of Months 744.000 66.532 544.542 27.540 66.532



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 71.875 1.124 492.767 13.400 14.524
February 187.642 4.219 308.875 9.613 13.833
March 352.458 9.176 202.698 4.068 13.245
April 555.700 19.174 35.450 0.464 19.637
May 710.633 32.337 0.000 0.000 32.337
June 718.750 43.060 0.000 0.000 43.060
July 744.000 48.700 0.000 0.000 48.700
August 744.000 47.692 0.000 0.000 47.692
September 712.179 38.420 0.000 0.000 38.420
October 552.811 18.446 51.333 0.842 19.288
November 383.328 10.571 160.088 3.121 13.692
December 152.075 3.683 386.808 9.911 13.593
           
Annual Sum or Average 5885.451 276.603 1638.019 41.418 318.021
Minimum of Months 71.875 1.124 0.000 0.000 13.245
Maximum of Months 744.000 48.700 492.767 13.400 48.700



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 56.596 1.002 564.079 19.557 20.560
February 166.289 4.378 342.560 13.836 18.214
March 335.823 10.081 241.177 6.288 16.370
April 525.987 22.336 55.625 0.947 23.283
May 695.783 39.673 3.000 0.014 39.687
June 715.750 54.184 0.000 0.000 54.184
July 744.000 61.578 0.000 0.000 61.578
August 744.000 59.949 0.000 0.000 59.949
September 689.379 47.828 0.000 0.000 47.828
October 521.167 22.024 76.000 1.637 23.660
November 340.162 11.288 201.450 5.124 16.413
December 134.837 3.620 447.933 15.034 18.654
           
Annual Sum or Average 5669.773 337.943 1931.825 62.437 400.380
Minimum of Months 56.596 1.002 0.000 0.000 16.370
Maximum of Months 744.000 61.578 564.079 19.557 61.578



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 88.742 3.259 528.750 34.020 37.279
February 169.263 7.750 342.492 24.521 32.271
March 316.546 15.560 271.458 13.471 29.030
April 478.029 29.258 87.000 2.814 32.072
May 667.138 49.223 14.500 0.155 49.378
June 711.778 67.126 0.000 0.000 67.126
July 744.000 77.650 0.000 0.000 77.650
August 744.000 76.156 0.000 0.000 76.156
September 668.601 62.727 0.000 0.000 62.727
October 474.194 33.011 112.577 4.277 37.287
November 361.652 19.051 211.375 10.578 29.629
December 184.458 7.511 411.333 26.502 34.014
           
Annual Sum or Average 5608.401 448.280 1979.485 116.338 564.619
Minimum of Months 88.742 3.259 0.000 0.000 29.030
Maximum of Months 744.000 77.650 528.750 34.020 77.650



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 97.779 2.529 490.754 18.825 21.355
February 189.426 6.200 304.192 13.914 20.114
March 345.775 12.186 236.958 7.069 19.254
April 514.185 23.139 63.833 1.190 24.329
May 684.604 38.695 3.250 0.009 38.703
June 714.786 52.231 0.000 0.000 52.231
July 744.000 60.009 0.000 0.000 60.009
August 744.000 59.422 0.000 0.000 59.422
September 685.665 49.301 0.000 0.000 49.301
October 516.906 26.689 77.900 1.813 28.502
November 395.133 16.303 171.864 5.218 21.521
December 208.700 6.309 366.771 14.341 20.650
           
Annual Sum or Average 5840.959 353.013 1715.522 62.379 415.392
Minimum of Months 97.779 2.529 0.000 0.000 19.254
Maximum of Months 744.000 60.009 490.754 18.825 60.009



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 80.967 2.380 546.167 25.479 27.859
February 162.683 6.398 344.096 18.401 24.799
March 324.589 13.062 259.188 9.557 22.619
April 492.403 26.237 74.125 1.797 28.034
May 680.679 45.836 9.083 0.083 45.919
June 713.008 63.306 0.000 0.000 63.306
July 744.000 72.833 0.000 0.000 72.833
August 744.000 71.423 0.000 0.000 71.423
September 676.848 58.450 0.000 0.000 58.450
October 495.681 30.120 98.500 2.860 32.980
November 365.957 16.993 202.125 7.516 24.509
December 175.261 5.973 408.683 19.717 25.690
           
Annual Sum or Average 5656.077 413.011 1941.967 85.410 498.421
Minimum of Months 80.967 2.380 0.000 0.000 22.619
Maximum of Months 744.000 72.833 546.167 25.479 72.833



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 58.021 1.706 578.500 38.420 40.126
February 147.735 5.999 367.813 26.740 32.739
March 301.104 13.794 284.667 14.328 28.122
April 474.213 28.586 94.250 2.915 31.501
May 668.209 49.356 14.031 0.151 49.507
June 711.833 67.693 0.000 0.000 67.693
July 744.000 78.060 0.000 0.000 78.060
August 744.000 76.026 0.000 0.000 76.026
September 667.530 61.125 0.000 0.000 61.125
October 455.369 28.655 121.937 4.617 33.273
November 323.408 14.649 239.792 11.977 26.626
December 136.608 4.658 458.454 29.816 34.474
           
Annual Sum or Average 5432.031 430.307 2159.444 128.964 559.271
Minimum of Months 58.021 1.706 0.000 0.000 26.626
Maximum of Months 744.000 78.060 578.500 38.420 78.060



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 56.646 1.159 562.333 22.609 23.768
February 161.563 4.621 339.379 15.868 20.489
March 322.598 10.547 253.292 7.754 18.301
April 508.288 22.583 66.208 1.249 23.832
May 684.970 38.945 2.850 0.007 38.952
June 715.116 52.930 0.000 0.000 52.930
July 744.000 60.571 0.000 0.000 60.571
August 744.000 59.475 0.000 0.000 59.475
September 685.246 47.910 0.000 0.000 47.910
October 494.380 22.472 86.588 2.030 24.502
November 341.915 11.969 210.517 6.252 18.221
December 136.562 3.839 435.292 17.129 20.968
           
Annual Sum or Average 5595.282 337.021 1956.459 72.898 409.919
Minimum of Months 56.646 1.159 0.000 0.000 18.221
Maximum of Months 744.000 60.571 562.333 22.609 60.571



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 50.021 1.088 593.625 28.741 29.829
February 145.576 4.869 367.729 20.076 24.945
March 303.809 11.362 273.704 10.050 21.412
April 488.657 25.571 76.500 1.829 27.400
May 680.923 45.827 9.000 0.081 45.909
June 713.308 63.601 0.000 0.000 63.601
July 744.000 72.959 0.000 0.000 72.959
August 744.000 71.118 0.000 0.000 71.118
September 676.807 56.883 0.000 0.000 56.883
October 481.105 25.887 102.583 2.979 28.866
November 322.807 12.707 235.917 8.382 21.089
December 124.000 3.792 474.346 22.289 26.081
           
Annual Sum or Average 5475.013 395.666 2133.404 94.426 490.092
Minimum of Months 50.021 1.088 0.000 0.000 21.089
Maximum of Months 744.000 72.959 593.625 28.741 72.959



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 20.38 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 1.56 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 20.38 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1373.53 0.00
February 0.00 1164.87 0.00
March 0.00 520.20 0.00
April 0.00 82.75 0.00
May 0.00 0.13 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 118.23 0.00
November 0.00 375.97 0.00
December 0.00 1039.54 0.00
       
Annual Sum or Average 0.00 386.24 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1373.53 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2195.57 0.00
February 0.00 1784.34 0.00
March 0.00 841.19 0.00
April 0.00 162.54 0.00
May 0.00 8.35 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 241.92 0.00
November 0.00 661.84 0.00
December 0.00 1696.68 0.00
       
Annual Sum or Average 0.00 627.91 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2195.57 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2555.36 0.00
February 0.00 1995.87 0.00
March 0.00 964.99 0.00
April 0.00 200.65 0.00
May 0.00 9.84 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 287.14 0.00
November 0.00 798.46 0.00
December 0.00 1955.93 0.00
       
Annual Sum or Average 0.00 725.56 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2555.36 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1807.75 0.00
February 0.00 1431.73 0.00
March 0.00 629.75 0.00
April 0.00 97.00 0.00
May 0.00 0.20 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 141.98 0.00
November 0.00 485.66 0.00
December 0.00 1334.37 0.00
       
Annual Sum or Average 0.00 490.15 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1807.75 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2570.93 0.00
February 0.00 2015.63 0.00
March 0.00 913.07 0.00
April 0.00 167.96 0.00
May 0.00 8.12 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 255.16 0.00
November 0.00 752.50 0.00
December 0.00 1966.65 0.00
       
Annual Sum or Average 0.00 715.57 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2570.93 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1514.04 0.00
February 0.00 1248.69 0.00
March 0.00 558.86 0.00
April 0.00 100.88 0.00
May 0.00 1.15 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 157.15 0.00
November 0.00 444.32 0.00
December 0.00 1185.68 0.00
       
Annual Sum or Average 0.00 430.80 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1514.04 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 904.53 0.00
February 0.00 773.09 0.00
March 0.00 303.74 0.00
April 0.00 38.34 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 63.43 0.00
November 0.00 222.36 0.00
December 0.00 686.45 0.00
       
Annual Sum or Average 0.00 247.04 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 904.53 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1647.99 0.00
February 0.00 1347.06 0.00
March 0.00 582.84 0.00
April 0.00 96.38 0.00
May 0.00 1.47 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 155.69 0.00
November 0.00 462.48 0.00
December 0.00 1283.61 0.00
       
Annual Sum or Average 0.00 461.11 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1647.99 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1981.31 0.00
February 0.00 1539.03 0.00
March 0.00 689.73 0.00
April 0.00 123.87 0.00
May 0.00 1.74 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 195.14 0.00
November 0.00 584.30 0.00
December 0.00 1522.72 0.00
       
Annual Sum or Average 0.00 549.17 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1981.31 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1225.21 0.00
February 0.00 973.18 0.00
March 0.00 371.98 0.00
April 0.00 43.81 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 76.99 0.00
November 0.00 294.84 0.00
December 0.00 906.18 0.00
       
Annual Sum or Average 0.00 321.64 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1225.21 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1989.41 0.00
February 0.00 1558.21 0.00
March 0.00 639.66 0.00
April 0.00 99.56 0.00
May 0.00 1.39 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 166.49 0.00
November 0.00 538.62 0.00
December 0.00 1529.28 0.00
       
Annual Sum or Average 0.00 539.42 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1989.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2587.88 0.00
February 0.00 2065.15 0.00
March 0.00 1024.70 0.00
April 0.00 221.23 0.00
May 0.00 11.80 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 325.33 0.00
November 0.00 831.50 0.00
December 0.00 2016.01 0.00
       
Annual Sum or Average 0.00 751.63 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2587.88 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1783.80 0.00
February 0.00 1459.64 0.00
March 0.00 669.82 0.00
April 0.00 116.49 0.00
May 0.00 0.85 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 171.79 0.00
November 0.00 510.95 0.00
December 0.00 1358.88 0.00
       
Annual Sum or Average 0.00 502.01 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1783.80 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2607.16 0.00
February 0.00 2084.63 0.00
March 0.00 977.93 0.00
April 0.00 189.96 0.00
May 0.00 8.53 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 292.60 0.00
November 0.00 794.73 0.00
December 0.00 2017.59 0.00
       
Annual Sum or Average 0.00 742.27 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2607.16 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2928.04 0.00
February 0.00 2256.26 0.00
March 0.00 1091.97 0.00
April 0.00 229.59 0.00
May 0.00 11.50 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 351.89 0.00
November 0.00 943.21 0.00
December 0.00 2272.29 0.00
       
Annual Sum or Average 0.00 834.76 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2928.04 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2127.95 0.00
February 0.00 1653.47 0.00
March 0.00 729.80 0.00
April 0.00 121.52 0.00
May 0.00 0.63 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 191.04 0.00
November 0.00 608.00 0.00
December 0.00 1612.15 0.00
       
Annual Sum or Average 0.00 582.72 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2127.95 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2941.03 0.00
February 0.00 2274.40 0.00
March 0.00 1028.40 0.00
April 0.00 193.37 0.00
May 0.00 8.31 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 304.86 0.00
November 0.00 886.26 0.00
December 0.00 2280.80 0.00
       
Annual Sum or Average 0.00 820.65 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2941.03 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.54
February 0.00 0.00 0.66
March 0.00 0.00 0.82
April 0.00 0.00 1.04
May 0.00 0.00 1.23
June 0.00 0.00 1.41
July 0.00 0.00 1.47
August 0.00 0.00 1.46
September 0.00 0.00 1.38
October 0.00 0.00 1.06
November 0.00 0.00 0.90
December 0.00 0.00 0.65
       
Annual Sum or Average 0.00 0.00 1.05
Minimum of Months 0.00 0.00 0.54
Maximum of Months 0.00 0.00 1.47



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.06
March 0.00 0.00 0.10
April 0.00 0.00 0.19
May 0.00 0.00 0.31
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.52
September 0.00 0.00 0.46
October 0.00 0.00 0.23
November 0.00 0.00 0.15
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.06
March 0.00 0.00 0.11
April 0.00 0.00 0.22
May 0.00 0.00 0.38
June 0.00 0.00 0.57
July 0.00 0.00 0.64
August 0.00 0.00 0.63
September 0.00 0.00 0.54
October 0.00 0.00 0.26
November 0.00 0.00 0.16
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.64



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.09
April 0.00 0.00 0.21
May 0.00 0.00 0.37
June 0.00 0.00 0.56
July 0.00 0.00 0.63
August 0.00 0.00 0.60
September 0.00 0.00 0.50
October 0.00 0.00 0.21
November 0.00 0.00 0.11
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.63



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.07
April 0.00 0.00 0.17
May 0.00 0.00 0.31
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.42
October 0.00 0.00 0.17
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.08
April 0.00 0.00 0.20
May 0.00 0.00 0.37
June 0.00 0.00 0.57
July 0.00 0.00 0.64
August 0.00 0.00 0.62
September 0.00 0.00 0.50
October 0.00 0.00 0.20
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.64



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.08
March 0.00 0.00 0.14
April 0.00 0.00 0.25
May 0.00 0.00 0.39
June 0.00 0.00 0.55
July 0.00 0.00 0.61
August 0.00 0.00 0.60
September 0.00 0.00 0.52
October 0.00 0.00 0.28
November 0.00 0.00 0.18
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.07
March 0.00 0.00 0.12
April 0.00 0.00 0.22
May 0.00 0.00 0.33
June 0.00 0.00 0.46
July 0.00 0.00 0.50
August 0.00 0.00 0.51
September 0.00 0.00 0.44
October 0.00 0.00 0.25
November 0.00 0.00 0.17
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.07
March 0.00 0.00 0.13
April 0.00 0.00 0.24
May 0.00 0.00 0.40
June 0.00 0.00 0.56
July 0.00 0.00 0.62
August 0.00 0.00 0.62
September 0.00 0.00 0.53
October 0.00 0.00 0.28
November 0.00 0.00 0.17
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.11
April 0.00 0.00 0.24
May 0.00 0.00 0.39
June 0.00 0.00 0.55
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.48
October 0.00 0.00 0.22
November 0.00 0.00 0.12
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.09
April 0.00 0.00 0.20
May 0.00 0.00 0.33
June 0.00 0.00 0.46
July 0.00 0.00 0.50
August 0.00 0.00 0.49
September 0.00 0.00 0.41
October 0.00 0.00 0.19
November 0.00 0.00 0.11
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.10
April 0.00 0.00 0.23
May 0.00 0.00 0.39
June 0.00 0.00 0.56
July 0.00 0.00 0.62
August 0.00 0.00 0.60
September 0.00 0.00 0.49
October 0.00 0.00 0.21
November 0.00 0.00 0.12
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.07
March 0.00 0.00 0.14
April 0.00 0.00 0.27
May 0.00 0.00 0.44
June 0.00 0.00 0.63
July 0.00 0.00 0.70
August 0.00 0.00 0.69
September 0.00 0.00 0.58
October 0.00 0.00 0.29
November 0.00 0.00 0.18
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.70



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.12
April 0.00 0.00 0.24
May 0.00 0.00 0.39
June 0.00 0.00 0.54
July 0.00 0.00 0.60
August 0.00 0.00 0.60
September 0.00 0.00 0.51
October 0.00 0.00 0.26
November 0.00 0.00 0.17
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.12
April 0.00 0.00 0.26
May 0.00 0.00 0.45
June 0.00 0.00 0.65
July 0.00 0.00 0.72
August 0.00 0.00 0.70
September 0.00 0.00 0.59
October 0.00 0.00 0.29
November 0.00 0.00 0.17
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.72



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.12
April 0.00 0.00 0.26
May 0.00 0.00 0.44
June 0.00 0.00 0.64
July 0.00 0.00 0.71
August 0.00 0.00 0.69
September 0.00 0.00 0.57
October 0.00 0.00 0.25
November 0.00 0.00 0.14
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.71



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.10
April 0.00 0.00 0.23
May 0.00 0.00 0.39
June 0.00 0.00 0.55
July 0.00 0.00 0.61
August 0.00 0.00 0.59
September 0.00 0.00 0.49
October 0.00 0.00 0.22
November 0.00 0.00 0.12
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.11
April 0.00 0.00 0.26
May 0.00 0.00 0.45
June 0.00 0.00 0.65
July 0.00 0.00 0.72
August 0.00 0.00 0.70
September 0.00 0.00 0.57
October 0.00 0.00 0.25
November 0.00 0.00 0.13
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.72



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41
Maximum of Months 0.00 0.00 1447.40 1077.63



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:27:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1447.40 1077.63
February 0.00 0.00 1443.33 970.60
March 0.00 0.00 1376.20 1024.62
April 0.00 0.00 1276.36 919.63
May 0.00 0.00 1154.69 859.70
June 0.00 0.00 1056.16 760.98
July 0.00 0.00 1005.21 748.41
August 0.00 0.00 1009.72 751.77
September 0.00 0.00 1076.71 775.78
October 0.00 0.00 1181.54 879.69
November 0.00 0.00 1299.76 936.49
December 0.00 0.00 1396.86 1040.00
         
Annual Sum or Average 0.00 0.00 1225.76 10745.29
Minimum of Months 0.00 0.00 1005.21 748.41