Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27

Tabular Output Report in Format: HTML

Building: MF+CZ2A+USA_TX_Houston-Bush.Intercontinental.AP.722430+oilfurnace+slab+IECC_2012

Environment: ANNUAL ** Houston Bush Intercontinental TX USA TMY3 WMO#=722430

Simulation Timestamp: 2019-02-14 08:28:03


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 821377.34 26.32 38.01
Net Site Energy 821377.34 26.32 38.01
Total Source Energy 1936860.74 62.06 89.63
Net Source Energy 1936860.74 62.06 89.63


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.78
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 91638.60 0.00 0.00 0.00 0.00
Cooling 125700.54 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 23850.59 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 227344.27 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 502394.48 318982.87 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 91638.60 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 125700.54 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 23850.59 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 227344.27 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.45 0.00 0.00 0.00 0.00 0.00
HVAC 6.92 14.76 0.00 0.00 0.00 17.48
Other 13.88 0.00 0.00 0.00 0.00 0.00
Total 23.25 14.76 0.00 0.00 0.00 17.48


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.70 0.00 0.00 0.00 0.00 0.00
HVAC 4.79 10.22 0.00 0.00 0.00 12.10
Other 9.61 0.00 0.00 0.00 0.00 0.00
Total 16.10 10.22 0.00 0.00 0.00 12.10


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 502394.478 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 502394.478 100.00
     
Total On-Site and Utility Electric Sources 502394.478 100.00
Total Electricity End Uses 502394.478 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 602.75
Time Setpoint Not Met During Occupied Cooling 11.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 2775.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
RunPeriod ANNUAL
Weather File Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Latitude [deg] 30.00
Longitude [deg] -95.4
Elevation [ft] 95.15
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 31210.78     267087.66   16177.97 0.00 2126.74 2126.74 0.4611 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6659 600.28 2.9092
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 02-AUG-18:15 11-FEB-06:00 - - - 01-JAN-08:30
Heating 0.00 192.12 0.00 0.00 0.00 0.00
Cooling 55.57 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51.01 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8.18 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 112.71 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 129.85 304.82 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 192.12 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 55.57 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.22 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.61 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 8.18 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 112.71 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 99336.24 0.00 0.00 0.00
Cooling 398093.62 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 75534.82 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 246441.19 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1591083.31 345777.43 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 4.60 0.00 0.00 0.00
Cooling 18.42 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.50 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.40 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 73.63 16.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 4.60 0.00 0.00 0.00
Cooling 18.42 0.00 0.00 0.00 0.00
Interior Lighting 6.48 0.00 0.00 0.00 0.00
Exterior Lighting 1.28 0.00 0.00 0.00 0.00
Interior Equipment 43.95 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.50 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.40 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 73.63 16.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 29.12 0.00 29.12 Wetbulb [F] 551.21 0.00
HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 96.80 18.18 76.64 Wetbulb [F] 689.01 170.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.400 0.219 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.400 0.219 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.400 0.219 0.882              
North Total or Average           531.68 0.400 0.219 0.882              
Non-North Total or Average           1595.05 0.400 0.219 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.298 0.400 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 381482.42 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   24480.56 18437.05 6043.51 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9189.19 6234.31 2954.88 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11376.54 7764.11 3612.44 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14097.51 10024.58 4072.92 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9132.89 6224.15 2908.74 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10813.45 7496.01 3317.44 0.69 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13781.30 9880.18 3901.12 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8921.41 6127.85 2793.56 0.69 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11032.52 7585.48 3447.04 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13652.96 9791.21 3861.76 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8990.91 6180.00 2810.91 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10391.23 7242.31 3148.92 0.70 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15869.18 11464.34 4404.84 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11092.91 7760.82 3332.10 0.70 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12639.36 8879.39 3759.97 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15883.64 11476.05 4407.59 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11158.56 7812.50 3346.07 0.70 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12583.46 8859.17 3724.29 0.70 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.0 3.34 11.41 12.09 11.74
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.7 3.49 11.92 12.66 12.59
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.49 11.89 12.62 12.54
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.43 11.69 12.41 12.20
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.7 3.49 11.90 12.63 12.55
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.9 3.46 11.82 12.54 12.41
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.42 11.65 12.36 12.14
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.48 11.86 12.59 12.48
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.47 11.86 12.58 12.48
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.42 11.65 12.36 12.13
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.48 11.86 12.59 12.48
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.46 11.79 12.51 12.36
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.40 11.62 12.32 12.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.45 11.77 12.49 12.33
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.44 11.75 12.47 12.30
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.40 11.62 12.32 12.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.45 11.77 12.49 12.33
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.44 11.74 12.46 12.28
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 45492.87 48793.27 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 14600.23 14873.88 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 17832.66 18436.24 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 23821.71 25024.79 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 14677.90 14959.44 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 17692.77 18282.19 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 23776.16 24973.30 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 14649.11 14926.60 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 17664.98 18250.19 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 23590.83 24769.06 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 14771.29 15061.37 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 17297.33 17844.16 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 27544.70 29114.46 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 18487.45 19157.45 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 20976.65 21894.93 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 27574.86 29147.53 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 18616.21 19299.19 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 20997.99 21918.41 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 804.58 303.48 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 231.99 87.50 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 291.88 110.10 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 402.86 151.96 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 233.43 88.05 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 289.29 109.12 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 402.03 151.64 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 232.90 87.85 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 288.79 108.93 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 398.60 150.35 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 235.16 88.70 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 281.97 106.36 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 471.85 177.98 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 304.02 114.67 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 350.14 132.07 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 472.41 178.19 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 306.40 115.57 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 350.54 132.22 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 38.360994 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18836.49 18836.49 15.69 804.581 804.581 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00867 93.35 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5431.32 5431.32 4.52 231.987 231.987 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00994 91.07 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6831.87 6831.87 5.69 291.882 291.882 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00952 96.80 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9431.70 9431.70 7.86 402.861 402.861 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00925 92.89 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5465.05 5465.05 4.55 233.426 233.426 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00996 89.71 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6772.98 6772.98 5.64 289.290 289.290 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00955 91.94 0.01519 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9412.50 9412.50 7.84 402.033 402.033 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00906 92.89 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5452.83 5452.83 4.54 232.900 232.900 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00969 89.71 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6759.80 6759.80 5.63 288.785 288.785 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00927 96.80 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9332.07 9332.07 7.77 398.599 398.599 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00908 92.44 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5505.83 5505.83 4.59 235.165 235.165 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00968 89.71 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6601.75 6601.75 5.50 281.972 281.972 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 10:45:00 74.98 74.98 0.00934 91.94 0.01519 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8206.70 8206.70 6.84 350.536 350.536 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00942 91.76 0.01519 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8197.42 8197.42 6.83 350.140 350.140 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00942 92.44 0.01519 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11046.78 11046.78 9.20 471.849 471.849 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00910 92.44 0.01519 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7173.61 7173.61 5.98 306.404 306.404 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00958 89.71 0.01519 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7117.75 7117.75 5.93 304.018 304.018 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00959 89.71 0.01519 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11059.86 11059.86 9.21 472.407 472.407 HOUSTON BUSH INTERCONTINENTAL ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00910 92.44 0.01519 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5827.05 5827.05 4.85 106.407 106.407 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00620 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7804.20 7804.20 6.50 142.509 142.509 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00643 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7810.84 7810.84 6.51 142.630 142.630 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00643 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5967.93 5967.93 4.97 108.979 108.979 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00622 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7808.14 7808.14 6.50 142.581 142.581 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00643 29.12 0.00331 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6597.93 6597.93 5.50 120.487 120.487 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00660 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5040.52 5040.52 4.20 92.048 92.048 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6947.42 6947.42 5.79 126.869 126.869 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00664 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6949.11 6949.11 5.79 126.900 126.900 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00664 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5068.44 5068.44 4.22 92.558 92.558 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00644 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6946.53 6946.53 5.79 126.853 126.853 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00664 29.12 0.00331 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9047.46 9047.46 7.54 165.211 165.211 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00657 29.12 0.00331 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9047.80 9047.80 7.54 165.217 165.217 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00657 29.12 0.00331 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9003.48 9003.48 7.50 164.408 164.408 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00656 29.12 0.00331 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7172.59 7172.59 5.97 130.977 130.977 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00641 29.12 0.00331 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7166.42 7166.42 5.97 130.864 130.864 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00641 29.12 0.00331 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9049.33 9049.33 7.54 165.245 165.245 HOUSTON BUSH INTERCONTINENTAL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00657 29.12 0.00331 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 804.58 804.58 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 231.99 231.99 106.41 106.41
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 291.88 291.88 142.51 142.51
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 402.86 402.86 142.63 142.63
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 233.43 233.43 108.98 108.98
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 289.29 289.29 142.58 142.58
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.03 402.03 120.49 120.49
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 232.90 232.90 92.05 92.05
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 288.79 288.79 126.87 126.87
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 398.60 398.60 126.90 126.90
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.16 235.16 92.56 92.56
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 281.97 281.97 126.85 126.85
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 471.85 471.85 164.41 164.41
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 304.02 304.02 130.86 130.86
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 350.14 350.14 165.22 165.22
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 472.41 472.41 165.24 165.24
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 306.40 306.40 130.98 130.98
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.54 350.54 165.21 165.21


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2654.00 3390.00 4.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5237.75 5091.75 2397.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5270.75 4826.25 2050.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5259.00 5528.75 2500.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5099.50 5582.75 2502.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5224.00 5222.75 2161.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5405.25 4417.75 1801.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5249.00 4039.00 1525.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5294.50 4072.25 1428.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5301.00 4782.25 1892.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5150.25 4470.00 1596.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5263.75 4439.25 1519.50
LIVING_UNIT3_BACKROW_TOPFLOOR 5338.75 4671.50 1740.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 5400.75 4447.00 1696.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 5432.50 4786.50 2019.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5259.75 4886.75 1948.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 5316.50 4608.00 1893.25
LIVING_UNIT1_BACKROW_TOPFLOOR 5356.75 4998.75 2073.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 5680.75 5987.50 2775.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 4.50 0.00 4.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24.00 5.50 24.00 5.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 116.25 2.50 116.25 2.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 160.75 2.75 160.75 2.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 18.00 0.25 18.00 0.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 51.00 1.50 51.00 1.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12.00 1.00 12.00 1.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3.00 0.00 3.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 135.00 1.75 135.00 1.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.50 0.50 171.50 0.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4.25 0.00 4.25 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 89.00 1.00 89.00 1.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.50 9.50 44.50 9.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 69.00 10.25 69.00 10.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 47.75 4.25 47.75 4.25
LIVING_UNIT2_BACKROW_TOPFLOOR 2.00 3.00 2.00 3.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 4.75 0.00 4.75
LIVING_UNIT1_BACKROW_TOPFLOOR 123.50 4.00 123.50 4.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 602.75 11.25 602.75 11.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.159 0.000 0.268
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.138 0.000 0.268
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.156 0.000 0.268
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.156 0.000 0.268
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.138 0.000 0.268
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.156 0.000 0.268
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.069 0.000 0.268
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.268
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.069 0.000 0.268
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.068 0.000 0.268
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.050 0.000 0.268
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.068 0.000 0.268
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.156 0.000 0.268
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.156 0.000 0.268
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.156 0.000 0.268
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.138 0.000 0.268
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.138 0.000 0.268
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.156 0.000 0.268
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1855
Defaulted Fields 436
Fields with Defaults 4694
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 90
Autocalculatable Fields 269



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Fans:Electricity 6985.26 96.99 13-MAR-00:30 2394.73 02-AUG-17:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
ElectricityPurchased:Plant 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
Cogeneration:ElectricityPurchased 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
ElectricityNet:Plant 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
Cogeneration:ElectricityNet 147139.16 7356.10 30-JAN-04:00 38029.33 02-AUG-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 43799.90 510.82 13-MAR-00:30 18909.50 02-AUG-16:15
General:Fans:Electricity 6985.26 96.99 13-MAR-00:30 2394.73 02-AUG-17:15
Cooling:Electricity 36814.64 0.00 23-JAN-04:00 16518.23 02-AUG-16:15
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 3189.83 0.00 06-JAN-13:45 304605.24 11-FEB-07:00
Gas:Plant 3189.83 0.00 06-JAN-13:45 304605.24 11-FEB-07:00
WaterSystems:Gas 2273.44 0.00 01-JAN-00:15 113672.02 11-FEB-08:15
Water Heater:WaterSystems:Gas 2273.44 0.00 01-JAN-00:15 113672.02 11-FEB-08:15
Heating:Gas 916.39 0.00 06-JAN-13:45 191979.59 11-FEB-07:00
Boiler:Heating:Gas 916.39 0.00 06-JAN-13:45 191979.59 11-FEB-07:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
Water:Plant 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
WaterSystems:Water 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
MainsWater:Plant 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
WaterSystems:MainsWater 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 18-JAN-03:00 0.18 01-JAN-08:30


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 176830.47 765.40 27-JUL-02:15 176462.18 11-FEB-07:15
PlantLoopHeatingDemand:Plant 103736.18 765.40 27-JUL-02:15 29534.63 28-JAN-08:30
WaterSystems:PlantLoopHeatingDemand 103736.18 765.40 27-JUL-02:15 29534.63 28-JAN-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1234886.95 15285.75 16-OCT-02:45 485105.23 11-FEB-07:00
EnergyTransfer:Building 441179.49 6790.34 16-OCT-02:45 163198.90 01-AUG-17:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 75987.53 0.00 06-JAN-14:00 155843.32 11-FEB-07:00
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 365191.96 0.00 23-JAN-04:00 163198.90 01-AUG-17:30
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87030.71 0.00 23-JAN-04:00 19364.03 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.64 0.00 01-JAN-00:15 689.28 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87030.07 0.00 23-JAN-04:00 19364.03 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16585.30 0.00 01-JAN-11:15 13659.18 12-FEB-10:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3086.29 0.00 01-JAN-11:15 13659.18 12-FEB-10:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13499.01 0.00 01-JAN-00:15 6368.79 01-AUG-18:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21530.63 0.00 01-JAN-10:15 10404.50 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4749.35 0.00 01-JAN-10:15 10404.50 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16781.28 0.00 01-JAN-00:15 7841.56 01-AUG-16:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20928.57 0.00 01-JAN-15:15 10446.13 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5581.68 0.00 01-JAN-15:15 10123.77 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15346.90 0.00 01-JAN-00:15 10446.13 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 15973.23 0.00 06-JAN-13:15 7728.98 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4117.01 0.00 06-JAN-13:15 7728.98 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11856.23 0.00 01-JAN-00:15 6322.02 01-AUG-18:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20652.43 0.00 06-JAN-13:00 10132.75 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5532.56 0.00 06-JAN-13:00 10132.75 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15119.87 0.00 01-JAN-00:15 7533.60 01-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21669.19 0.00 01-JAN-11:45 10376.32 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3365.90 0.00 01-JAN-11:45 8049.87 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18303.29 0.00 01-JAN-00:15 10376.32 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16946.62 0.00 01-JAN-11:15 6286.65 01-AUG-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2229.61 0.00 01-JAN-11:15 6247.23 11-FEB-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14717.01 0.00 01-JAN-00:15 6286.65 01-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21551.39 0.00 01-JAN-10:30 8211.44 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3578.49 0.00 01-JAN-10:30 8211.44 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17972.90 0.00 01-JAN-00:15 7739.08 02-AUG-18:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20801.69 0.00 01-JAN-15:30 10251.19 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4351.64 0.00 01-JAN-15:30 8251.97 11-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 16450.05 0.00 01-JAN-00:15 10251.19 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 15968.16 0.00 06-JAN-13:15 6210.79 02-AUG-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2946.95 0.00 06-JAN-13:15 5943.24 11-FEB-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13021.21 0.00 01-JAN-00:15 6210.79 02-AUG-19:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20584.45 0.00 06-JAN-13:15 8210.04 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4302.47 0.00 06-JAN-13:15 8210.04 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16281.97 0.00 01-JAN-00:15 7474.67 01-AUG-18:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 24777.51 0.00 06-JAN-13:45 11107.29 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 6158.57 0.00 06-JAN-13:45 11107.29 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18618.93 0.00 01-JAN-00:15 9252.82 01-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 25081.05 0.00 01-JAN-12:00 11074.48 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5467.09 0.00 01-JAN-12:00 11074.48 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19613.96 0.00 01-JAN-00:15 9285.53 01-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 25479.42 0.00 01-JAN-12:45 11985.08 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5573.85 0.00 01-JAN-12:45 11029.23 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 19905.58 0.00 01-JAN-00:15 11985.08 01-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 20103.86 0.00 01-JAN-17:15 8636.74 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4692.98 0.00 01-JAN-17:15 8636.74 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 15410.87 0.00 01-JAN-00:15 8028.15 01-AUG-18:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20378.43 0.00 01-JAN-12:15 8620.33 11-FEB-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 3966.38 0.00 01-JAN-12:15 8620.33 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 16412.05 0.00 01-JAN-00:15 7978.90 01-AUG-18:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 25136.84 0.00 01-JAN-15:00 11994.33 01-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 6286.06 0.00 01-JAN-15:00 11092.08 11-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18850.78 0.00 01-JAN-00:15 11994.33 01-AUG-17:30
EnergyTransfer:Plant 177047.06 765.40 27-JUL-02:15 177817.79 11-FEB-07:15
WaterSystems:EnergyTransfer 103736.18 765.40 27-JUL-02:15 29534.63 28-JAN-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 103736.18 765.40 27-JUL-02:15 29534.63 28-JAN-08:30
EnergyTransfer:HVAC 616660.40 6924.93 10-FEB-20:15 218060.01 04-AUG-18:15
HeatingCoils:EnergyTransfer 73094.29 0.00 06-JAN-13:45 152045.82 11-FEB-07:00
PlantLoopHeatingDemand:HVAC 73094.29 0.00 06-JAN-13:45 152045.82 11-FEB-07:00
HeatingCoils:PlantLoopHeatingDemand 73094.29 0.00 06-JAN-13:45 152045.82 11-FEB-07:00
CoolingCoils:EnergyTransfer 543566.11 0.00 23-JAN-04:00 218060.01 04-AUG-18:15
Boilers:EnergyTransfer 73310.88 0.00 06-JAN-13:45 153583.67 11-FEB-07:00



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.640 -7247.65 0.000 0.000 2874.324 2456.001 10405.511 7543.046 0.000 1968.771 72217.605 0.000 -3432.85 0.000 -7003.06 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 3086.235 -1124.16 0.000 0.000 2958.813 2456.001 10405.511 3175.188 0.000 1878.709 0.000 0.000 -1309.88 0.000 -6020.36 -3131.27
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 4749.260 -1397.50 0.000 0.000 2970.328 2456.001 10405.511 7496.976 0.000 1968.645 0.000 0.000 -3121.29 0.000 -6283.01 -3861.21
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 5581.587 -1278.04 0.000 0.000 2976.154 2456.001 10405.511 6035.171 0.000 1973.104 0.000 0.000 -3319.70 0.000 -6183.79 -4577.28
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 4116.946 -987.36 0.000 0.000 2968.271 2456.001 10405.511 1501.486 0.000 1882.733 0.000 0.000 -1389.53 0.000 -5934.32 -4150.88
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 5532.478 -1259.15 0.000 0.000 2976.928 2456.001 10405.511 5844.367 0.000 1968.824 0.000 0.000 -3154.30 0.000 -6208.65 -4701.32
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 3365.839 -1524.24 0.000 0.000 2953.338 2456.001 10405.511 7566.469 0.000 1539.549 0.010 0.000 -3351.75 0.000 -4932.87 -1698.95
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 2229.571 -1225.60 0.000 0.000 2943.282 2456.001 10405.511 3156.353 0.000 1450.060 0.013 0.000 -1348.99 0.000 -4663.70 -1911.11
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 3578.430 -1496.74 0.000 0.000 2958.347 2456.001 10405.511 7451.329 0.000 1539.441 0.000 0.000 -3214.87 0.000 -4917.81 -2283.52
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 4351.576 -1369.91 0.000 0.000 2964.440 2456.001 10405.511 6003.174 0.000 1543.790 0.000 0.000 -3417.16 0.000 -4842.70 -3014.66
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 2946.910 -1084.38 0.000 0.000 2955.422 2456.001 10405.511 1492.610 0.000 1453.677 0.000 0.000 -1429.74 0.000 -4584.85 -2674.31
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 4302.411 -1355.93 0.000 0.000 2966.147 2456.001 10405.511 5807.527 0.000 1539.646 0.000 0.000 -3244.25 0.000 -4857.03 -3093.97
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 6158.485 -1550.54 0.000 0.000 2971.166 2456.001 10405.511 5774.325 0.000 1953.037 0.076 0.000 -3255.28 0.000 -6262.51 -1581.81
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 5467.006 -1633.40 0.000 0.000 2965.796 2456.001 10405.511 7435.331 0.000 1952.317 0.205 0.000 -3209.84 0.000 -6317.88 -1540.32
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 5573.757 -1657.68 0.000 0.000 2964.045 2456.001 10405.511 7561.170 0.000 1954.282 0.137 0.000 -3321.88 0.000 -6313.70 -1373.77
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 4692.922 -1283.38 0.000 0.000 2962.285 2456.001 10405.511 1477.629 0.000 1868.974 0.082 0.000 -1430.15 0.000 -5996.23 -1026.07
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 3966.316 -1366.75 0.000 0.000 2954.652 2456.001 10405.511 3148.939 0.000 1864.579 0.076 0.000 -1341.73 0.000 -6061.56 -980.69
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 6285.974 -1569.84 0.000 0.000 2969.933 2456.001 10405.511 5957.321 0.000 1958.950 0.149 0.000 -3417.04 0.000 -6253.67 -1512.33
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4859.141 45524.656 0.000 0.000 0.000 -50383.80 -0.71
Total Facility 0.000 0.000 75986.341 -30412.25 0.000 0.000 53253.671 44208.020 187299.191 94428.413 0.000 37118.228 117743.009 0.000 -47710.23 0.000 -154021.50 -43114.17


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 01-AUG-17:24 0.00 0.00 0.00 -1.6 0.00 0.00 262.76 535.87 1656.36 4975.82 0.00 1910.99 10044.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 01-AUG-18:18 0.00 0.00 0.00 -0.5 0.00 0.00 425.93 721.37 1713.78 454.86 0.00 1665.59 1398.98 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 01-AUG-15:49 0.00 0.00 0.00 -0.7 0.00 0.00 115.17 178.62 1141.08 2100.31 0.00 2324.57 1983.24 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 01-AUG-17:18 0.00 0.00 0.00 -0.9 0.00 0.00 263.27 535.87 1656.36 5052.37 0.00 1935.31 1015.20 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 01-AUG-18:18 0.00 0.00 0.00 -0.5 0.00 0.00 426.28 721.37 1713.78 601.62 0.00 1666.57 1200.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 01-AUG-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 1713.78 1364.34 0.00 1865.52 1442.63 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 01-AUG-17:18 0.00 0.00 0.00 -0.9 0.00 0.00 263.11 535.87 1656.36 4974.75 0.00 1490.52 1463.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-AUG-18:04 0.00 0.00 0.00 -0.5 0.00 0.00 427.04 721.37 1713.78 513.02 0.00 1316.00 1596.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 02-AUG-18:18 0.00 0.00 0.00 -0.6 0.00 0.00 425.56 721.37 1713.78 1141.76 0.00 1395.83 2348.70 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 01-AUG-17:18 0.00 0.00 0.00 -0.9 0.00 0.00 263.34 535.87 1656.36 5046.01 0.00 1491.74 1266.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 02-AUG-19:17 0.00 0.00 0.00 -0.5 0.00 0.00 425.97 799.44 1651.33 293.05 0.00 1105.26 1953.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 01-AUG-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.04 721.37 1713.78 1376.16 0.00 1411.85 1825.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 01-AUG-17:04 0.00 0.00 0.00 -0.8 0.00 0.00 263.35 535.87 1656.36 1665.38 0.00 1917.34 3225.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 01-AUG-17:04 0.00 0.00 0.00 -0.8 0.00 0.00 263.35 535.87 1656.36 1617.77 0.00 1917.75 3306.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 01-AUG-17:21 0.00 0.00 0.00 -1.0 0.00 0.00 262.15 535.87 1656.36 4937.18 0.00 1920.32 2685.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 01-AUG-18:47 0.00 0.00 0.00 -0.7 0.00 0.00 426.43 721.37 1713.78 471.16 0.00 1466.14 3247.94 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 01-AUG-18:47 0.00 0.00 0.00 -0.7 0.00 0.00 426.23 721.37 1713.78 351.43 0.00 1465.15 3318.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 01-AUG-17:21 0.00 0.00 0.00 -1.0 0.00 0.00 262.24 535.87 1656.36 5002.45 0.00 1921.04 2628.61 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 01-AUG-17:33 0.00 0.00 0.00 -13.6 0.00 0.00 4730.81 9645.69 29814.52 40094.52 0.00 31700.53 64410.69 0.00 0.00 0.00 -16984.9 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11-FEB-07:00 0.00 0.00 689.27 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 6286.18 0.00 -2733.9 0.00 -6234.5 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11-FEB-05:08 0.00 0.00 14363.39 0.00 0.00 0.00 677.33 343.51 917.86 0.00 0.00 0.00 0.00 0.00 -927.3 0.00 -4561.6 -10813.2
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11-JAN-18:42 0.00 0.00 10419.18 0.00 0.00 0.00 486.75 721.37 1713.78 0.00 0.00 0.00 0.00 0.00 -1729.5 0.00 -2823.8 -8787.8
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13-OCT-09:45 0.00 0.00 18284.17 0.00 0.00 0.00 133.80 103.05 1084.61 487.74 0.00 0.00 0.00 0.00 0.00 0.00 -398.8 -19694.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 05-JAN-17:36 0.00 0.00 9297.36 0.00 0.00 0.00 301.65 535.87 1656.36 0.00 0.00 0.00 0.00 0.00 -441.3 0.00 -1544.5 -9805.4
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11-FEB-07:00 0.00 0.00 10132.60 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2754.9 0.00 -6234.6 -3136.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11-FEB-07:00 0.00 0.00 8049.72 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2770.2 0.00 -4292.9 -2979.6
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 11-FEB-17:53 0.00 0.00 13088.67 0.00 0.00 0.00 302.77 535.87 1676.47 0.00 0.00 0.00 0.00 0.00 -751.4 0.00 -2563.6 -12288.8
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 01-FEB-22:41 0.00 0.00 12490.74 0.00 0.00 0.00 554.42 336.64 1334.04 0.00 0.00 0.00 0.00 0.00 -1687.7 0.00 -2106.1 -10922.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 05-JAN-14:12 0.00 0.00 17792.40 0.00 0.00 0.00 138.12 103.05 1085.09 1370.98 0.00 0.00 0.00 0.00 0.00 0.00 -943.6 -19546.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 25-DEC-18:15 0.00 0.00 6863.90 0.00 0.00 0.00 472.06 721.37 1713.78 0.00 0.00 0.00 0.00 0.00 -630.2 0.00 -1813.9 -7327.1
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10-FEB-22:05 0.00 0.00 8350.67 0.00 0.00 0.00 549.25 336.64 1334.04 0.00 0.00 0.00 0.00 0.00 -2178.4 0.00 -3191.6 -5200.6
LIVING_UNIT3_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 11107.12 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2782.6 0.00 -6243.5 -4073.9
LIVING_UNIT3_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 11074.31 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2757.3 0.00 -6243.5 -4066.5
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 11029.06 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2757.7 0.00 -6243.4 -4021.0
LIVING_UNIT2_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 8636.61 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -1133.1 0.00 -5829.6 -3666.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 8620.20 0.00 0.00 0.00 526.31 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -1106.4 0.00 -5829.7 -3677.1
LIVING_UNIT1_BACKROW_TOPFLOOR 11-FEB-07:00 0.00 0.00 11091.91 0.00 0.00 0.00 526.32 384.73 1081.93 0.00 0.00 0.00 0.00 0.00 -2782.1 0.00 -6243.3 -4059.5
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-FEB-06:33 0.00 0.00 156795.39 0.00 0.00 0.00 9548.67 6925.11 19474.66 0.00 0.00 424.13 0.00 0.00 -39504.4 0.00 -96838.5 -56825.1



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 804.581 2.00 2.00 1.00 44.9950 804.581 0.056 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 231.987 2.00 2.00 1.00 44.9950 231.987 0.194 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 291.882 2.00 2.00 1.00 44.9950 291.882 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 402.861 2.00 2.00 1.00 44.9950 402.861 0.112 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 233.426 2.00 2.00 1.00 44.9950 233.426 0.193 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 289.290 2.00 2.00 1.00 44.9950 289.290 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.033 2.00 2.00 1.00 44.9950 402.033 0.112 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 232.900 2.00 2.00 1.00 44.9950 232.900 0.193 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 288.785 2.00 2.00 1.00 44.9950 288.785 0.156 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 398.599 2.00 2.00 1.00 44.9950 398.599 0.113 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.165 2.00 2.00 1.00 44.9950 235.165 0.191 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 281.972 2.00 2.00 1.00 44.9950 281.972 0.160 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 471.849 2.00 2.00 1.00 44.9950 471.849 0.095 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 304.018 2.00 2.00 1.00 44.9950 304.018 0.148 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 350.140 2.00 2.00 1.00 44.9950 350.140 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 472.407 2.00 2.00 1.00 44.9950 472.407 0.095 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 306.404 2.00 2.00 1.00 44.9950 306.404 0.147 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.536 2.00 2.00 1.00 44.9950 350.536 0.128 1.000 44.9950 0.13


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 106.407 2.00 2.00 1.00 44.9950 106.407 1.000 1.000 44.9950 0.42
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 142.509 2.00 2.00 1.00 44.9950 142.509 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 142.630 2.00 2.00 1.00 44.9950 142.630 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 108.979 2.00 2.00 1.00 44.9950 108.979 1.000 1.000 44.9950 0.41
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 142.581 2.00 2.00 1.00 44.9950 142.581 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 120.487 2.00 2.00 1.00 44.9950 120.487 1.000 1.000 44.9950 0.37
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 92.048 2.00 2.00 1.00 44.9950 92.048 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 126.869 2.00 2.00 1.00 44.9950 126.869 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 126.900 2.00 2.00 1.00 44.9950 126.900 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 92.558 2.00 2.00 1.00 44.9950 92.558 1.000 1.000 44.9950 0.49
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 126.853 2.00 2.00 1.00 44.9950 126.853 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 164.408 2.00 2.00 1.00 44.9950 164.408 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 130.864 2.00 2.00 1.00 44.9950 130.864 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 165.217 2.00 2.00 1.00 44.9950 165.217 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 165.245 2.00 2.00 1.00 44.9950 165.245 1.000 1.000 44.9950 0.27
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 130.977 2.00 2.00 1.00 44.9950 130.977 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 165.211 2.00 2.00 1.00 44.9950 165.211 1.000 1.000 44.9950 0.27


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   804.581 804.5809 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   231.987 231.9866 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   291.882 291.8818 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   402.861 402.8614 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   233.426 233.4258 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   289.290 289.2896 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   402.033 402.0331 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   232.900 232.9005 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   288.785 288.7851 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   398.599 398.5985 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   235.165 235.1646 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   281.972 281.9722 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   350.536 350.5357 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   350.140 350.1401 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   471.849 471.8486 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   306.404 306.4044 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   304.018 304.0184 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   472.407 472.4075 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 804.58 804.581 804.58 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 231.99 231.987 231.99 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 291.88 291.882 291.88 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 402.86 402.861 402.86 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 233.43 233.426 233.43 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 289.29 289.290 289.29 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.03 402.033 402.03 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 232.90 232.900 232.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 288.79 288.785 288.79 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 398.60 398.599 398.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.16 235.165 235.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 281.97 281.972 281.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 471.85 471.849 471.85 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 304.02 304.018 304.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 350.14 350.140 350.14 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 472.41 472.407 472.41 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 306.40 306.404 306.40 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.54 350.536 350.54 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   106.407 106.407 106.407 44.9950 0.423 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   142.509 142.509 142.509 44.9950 0.316 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   142.630 142.630 142.630 44.9950 0.315 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   108.979 108.979 108.979 44.9950 0.413 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   142.581 142.581 142.581 44.9950 0.316 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   120.487 120.487 120.487 44.9950 0.373 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   92.048 92.048 92.048 44.9950 0.489 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   126.869 126.869 126.869 44.9950 0.355 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   126.900 126.900 126.900 44.9950 0.355 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   92.558 92.558 92.558 44.9950 0.486 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   126.853 126.853 126.853 44.9950 0.355 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   165.211 165.211 165.211 44.9950 0.272 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   165.217 165.217 165.217 44.9950 0.272 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   164.408 164.408 164.408 44.9950 0.274 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   130.977 130.977 130.977 44.9950 0.344 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   130.864 130.864 130.864 44.9950 0.344 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   165.245 165.245 165.245 44.9950 0.272 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 106.41 106.407 106.41 106.41 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 142.51 142.509 142.51 142.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 142.63 142.630 142.63 142.63 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 108.98 108.979 108.98 108.98 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 142.58 142.581 142.58 142.58 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 120.49 120.487 120.49 120.49 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 92.05 92.048 92.05 92.05 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 126.87 126.869 126.87 126.87 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 126.90 126.900 126.90 126.90 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 92.56 92.558 92.56 92.56 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 126.85 126.853 126.85 126.85 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 164.41 164.408 164.41 164.41 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 130.86 130.864 130.86 130.86 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 165.22 165.217 165.22 165.22 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 165.24 165.245 165.24 165.24 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 130.98 130.977 130.98 130.98 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 165.21 165.211 165.21 165.21 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Sec1.1A-General Information

Data
Weather File ANNUAL ** Houston Bush Intercontinental TX USA TMY3 WMO#=722430
Total gross floor area [ft2] 31210.78
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 31210.78 21609.96 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 602.75
Number of hours cooling loads not met 11.25
Number of hours not met 614.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 916.39 191979.59 0.00 0.00
Space Cooling 36814.64 16274.69 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6985.26 2394.73 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2273.44 112625.65 0.00 0.00
Receptacle Equipment 87836.46 14939.60 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 147139.16   3189.83   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 502394.48
Natural Gas 0.00 318982.87
Additional 0.00 0.00
Total 299910.33 821377.34


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.41
Space Heating 0.00
Space Cooling 1.18
Fans-Interior 0.22
Service Water Heating 0.00
Receptacle Equipment 2.81
Miscellaneous 0.08
Subtotal 4.71


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.86
Service Water Heating 2.13
Miscellaneous -0.0
Subtotal 2.99


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.38
Space Heating 11.16
Space Cooling 15.30
Fans-Interior 2.90
Service Water Heating 27.68
Receptacle Equipment 36.51
Miscellaneous 1.06



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 804.58
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 231.99
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 291.88
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 402.86
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 233.43
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 289.29
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 402.03
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 232.90
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 288.79
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 398.60
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 235.16
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 281.97
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 350.54
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 350.14
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 471.85
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 306.40
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 304.02
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 472.41
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 804.58
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 231.99
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 291.88
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 402.86
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 233.43
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 289.29
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 402.03
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 232.90
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 288.79
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 398.60
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 235.16
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 281.97
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 471.85
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 304.02
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 350.14
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 472.41
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 306.40
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 804.58 2.04 0.753130
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 231.99 0.765765 0.678439
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 291.88 0.948045 0.682466
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 402.86 1.17 0.711089
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 233.43 0.761074 0.681509
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 289.29 0.901121 0.693211
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 402.03 1.15 0.716927
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 232.90 0.743451 0.686870
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 288.79 0.919377 0.687556
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 398.60 1.14 0.717149
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 235.16 0.749243 0.687361
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 281.97 0.865936 0.696964
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 471.85 1.32 0.722428
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 304.02 0.924409 0.699619
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 350.14 1.05 0.702519
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 472.41 1.32 0.722507
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 306.40 0.929880 0.700135
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 350.54 1.05 0.704033
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 804.58 804.58 804.58 2.04 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 231.99 231.99 231.99 0.765765 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 291.88 291.88 291.88 0.948045 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 402.86 402.86 402.86 1.17 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 233.43 233.43 233.43 0.761074 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 289.29 289.29 289.29 0.901121 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 402.03 402.03 402.03 1.15 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 232.90 232.90 232.90 0.743451 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 288.79 288.79 288.79 0.919377 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 398.60 398.60 398.60 1.14 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 235.16 235.16 235.16 0.749243 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 281.97 281.97 281.97 0.865936 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 471.85 471.85 471.85 1.32 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 304.02 304.02 304.02 0.924409 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 350.14 350.14 350.14 1.05 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 472.41 472.41 472.41 1.32 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 306.40 306.40 306.40 0.929880 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 350.54 350.54 350.54 1.05 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 45492.87 4.59 647.57
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 14600.23 1.47 200.62
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 17832.66 1.80 247.55
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 23821.71 2.40 334.40
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 14677.90 1.48 201.74
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 17692.77 1.79 245.52
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 23776.16 2.40 333.70
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 14649.11 1.48 201.30
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 17664.98 1.78 245.08
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 23590.83 2.38 331.01
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 14771.29 1.49 203.07
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 17297.33 1.75 239.72
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 27544.70 2.78 388.31
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 18487.45 1.87 257.06
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 20976.65 2.12 293.13
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 27574.86 2.78 388.74
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 18616.21 1.88 258.92
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 20997.99 2.12 293.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 804.58
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 231.99
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 291.88
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 402.86
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 233.43
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 289.29
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 402.03
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 232.90
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 288.79
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 398.60
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 235.16
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 281.97
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 471.85
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 304.02
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 350.14
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 472.41
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 306.40
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 350.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.13 96.16
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.13
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 381482.42 38.36
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:28:03

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 740.758 65.940 0.000 0.000 65.940
February 652.401 69.962 1.870 0.008 69.970
March 744.000 94.244 0.000 0.000 94.244
April 720.000 112.798 0.000 0.000 112.798
May 744.000 135.553 0.000 0.000 135.553
June 720.000 148.774 0.000 0.000 148.774
July 744.000 160.833 0.000 0.000 160.833
August 744.000 160.214 0.000 0.000 160.214
September 720.000 146.415 0.000 0.000 146.415
October 744.000 118.128 0.000 0.000 118.128
November 720.000 98.369 0.000 0.000 98.369
December 744.000 76.704 0.000 0.000 76.704
           
Annual Sum or Average 8737.159 1387.934 1.870 0.008 1387.942
Minimum of Months 652.401 65.940 0.000 0.000 65.940
Maximum of Months 744.000 160.833 1.870 0.008 160.833



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 86.212 1.435 473.017 4.023 5.742
February 162.790 3.306 279.120 2.801 7.658
March 318.754 6.495 229.135 1.458 7.953
April 484.764 12.782 53.625 0.206 12.988
May 678.536 22.604 0.000 0.000 22.604
June 714.929 33.024 0.000 0.000 33.024
July 744.000 38.678 0.000 0.000 38.678
August 744.000 38.692 0.000 0.000 38.692
September 693.219 32.638 0.000 0.000 32.638
October 510.103 16.720 59.583 0.302 17.022
November 386.235 10.142 160.500 0.988 11.130
December 189.017 3.803 353.312 3.002 6.805
           
Annual Sum or Average 5712.560 220.320 1608.293 12.780 234.934
Minimum of Months 86.212 1.435 0.000 0.000 5.742
Maximum of Months 744.000 38.692 473.017 4.023 38.692



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 77.733 1.480 469.596 10.842 18.342
February 148.902 3.726 291.583 7.921 15.834
March 302.827 7.634 213.115 3.964 15.371
April 475.357 15.634 43.333 0.614 18.793
May 674.822 28.454 0.000 0.000 29.148
June 714.438 41.609 0.000 0.000 41.609
July 744.000 48.446 0.000 0.000 48.446
August 744.000 47.892 0.000 0.000 47.892
September 680.068 39.723 0.000 0.000 39.723
October 488.455 19.741 51.792 0.957 24.317
November 362.084 11.080 152.562 2.933 17.634
December 162.638 3.871 348.521 8.259 17.234
           
Annual Sum or Average 5575.323 269.289 1570.502 35.490 334.342
Minimum of Months 77.733 1.480 0.000 0.000 15.371
Maximum of Months 744.000 48.446 469.596 10.842 48.446



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 35.850 0.703 543.446 13.784 21.711
February 118.077 2.993 345.292 9.691 17.076
March 261.221 7.254 262.189 4.917 16.891
April 447.623 16.881 68.840 0.848 20.492
May 660.611 31.402 6.708 0.026 31.624
June 713.112 46.144 0.000 0.000 46.144
July 744.000 53.722 0.000 0.000 53.722
August 744.000 52.000 0.000 0.000 52.000
September 673.249 41.431 0.000 0.000 41.431
October 435.244 17.124 92.598 1.355 20.972
November 293.746 8.249 199.740 3.867 17.996
December 103.067 2.456 414.992 10.451 21.269
           
Annual Sum or Average 5229.798 280.360 1933.803 44.939 361.328
Minimum of Months 35.850 0.703 0.000 0.000 16.891
Maximum of Months 744.000 53.722 543.446 13.784 53.722



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 27.050 0.291 573.662 6.287 7.845
February 123.021 1.783 344.864 4.423 7.244
March 269.558 4.489 271.750 2.165 7.498
April 467.179 11.630 67.062 0.319 11.978
May 678.389 22.559 0.000 0.000 22.559
June 715.339 33.738 0.000 0.000 33.738
July 744.000 39.139 0.000 0.000 39.139
August 744.000 38.168 0.000 0.000 38.168
September 692.157 30.307 0.000 0.000 30.307
October 463.804 11.782 75.024 0.466 12.292
November 295.042 5.933 213.972 1.629 8.382
December 109.917 1.762 450.037 4.664 8.271
           
Annual Sum or Average 5329.454 201.581 1996.372 19.952 227.422
Minimum of Months 27.050 0.291 0.000 0.000 7.244
Maximum of Months 744.000 39.139 573.662 6.287 39.139



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 26.229 0.354 579.812 12.877 15.785
February 118.960 2.226 345.738 8.985 14.233
March 264.998 5.631 254.890 4.390 12.794
April 464.894 14.853 52.688 0.668 17.676
May 675.180 29.071 0.000 0.000 29.740
June 714.521 43.199 0.000 0.000 43.199
July 744.000 49.944 0.000 0.000 49.944
August 744.000 48.459 0.000 0.000 48.459
September 679.602 38.413 0.000 0.000 38.413
October 465.530 15.282 60.750 1.057 19.494
November 295.028 7.050 204.468 3.481 13.492
December 100.792 1.989 466.900 9.843 15.420
           
Annual Sum or Average 5293.733 256.471 1965.246 41.299 318.648
Minimum of Months 26.229 0.354 0.000 0.000 12.794
Maximum of Months 744.000 49.944 579.812 12.877 49.944



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 105.704 2.748 458.083 8.474 11.244
February 191.116 5.988 283.563 6.254 12.571
March 350.500 11.830 200.911 2.948 16.420
April 512.106 21.175 43.375 0.424 22.924
May 682.600 34.971 0.250 0.000 34.971
June 714.933 47.180 0.000 0.000 47.180
July 744.000 54.445 0.000 0.000 54.445
August 744.000 53.936 0.000 0.000 53.936
September 686.851 44.909 0.000 0.000 44.909
October 515.048 24.486 57.583 0.738 26.380
November 393.985 14.787 155.735 2.285 17.411
December 207.008 6.090 349.517 6.581 12.671
           
Annual Sum or Average 5847.851 322.543 1549.016 27.705 355.061
Minimum of Months 105.704 2.748 0.000 0.000 11.244
Maximum of Months 744.000 54.445 458.083 8.474 54.445



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 111.050 1.902 403.604 3.400 5.361
February 206.215 4.364 265.263 2.633 7.220
March 369.683 8.524 177.792 1.126 10.031
April 549.763 15.630 29.892 0.135 15.768
May 703.993 25.742 0.000 0.000 25.742
June 718.500 34.504 0.000 0.000 34.504
July 744.000 39.594 0.000 0.000 39.594
August 744.000 39.739 0.000 0.000 39.739
September 712.448 33.465 0.000 0.000 33.465
October 571.401 18.783 40.750 0.215 18.998
November 442.593 11.980 126.875 0.781 12.820
December 225.038 4.683 311.433 2.548 7.283
           
Annual Sum or Average 6098.685 238.910 1355.608 10.838 250.523
Minimum of Months 111.050 1.902 0.000 0.000 5.361
Maximum of Months 744.000 39.739 403.604 3.400 39.739



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 93.743 1.829 399.896 8.209 18.093
February 178.503 4.584 263.471 6.067 14.198
March 354.476 9.449 168.237 2.710 16.914
April 521.998 18.146 22.125 0.321 21.027
May 694.916 31.336 0.000 0.000 31.377
June 716.000 42.823 0.000 0.000 42.823
July 744.000 49.094 0.000 0.000 49.094
August 744.000 48.665 0.000 0.000 48.665
September 692.233 40.230 0.000 0.000 40.230
October 532.394 21.423 34.042 0.573 24.784
November 395.674 12.556 121.125 2.023 18.587
December 192.531 4.515 307.767 6.337 16.217
           
Annual Sum or Average 5860.468 284.651 1316.662 26.239 342.008
Minimum of Months 93.743 1.829 0.000 0.000 14.198
Maximum of Months 744.000 49.094 399.896 8.209 49.094



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 48.125 0.911 494.413 10.897 21.145
February 148.729 3.797 306.537 7.651 16.252
March 311.550 9.134 220.417 3.552 17.549
April 496.189 19.642 46.432 0.508 22.423
May 681.363 34.639 0.250 0.000 34.671
June 715.036 47.548 0.000 0.000 47.548
July 744.000 54.497 0.000 0.000 54.497
August 744.000 52.942 0.000 0.000 52.942
September 685.628 42.101 0.000 0.000 42.101
October 478.761 18.876 68.147 0.895 22.225
November 324.929 9.649 169.197 2.880 17.949
December 125.650 3.021 375.190 8.363 20.105
           
Annual Sum or Average 5503.959 296.758 1680.584 34.746 369.408
Minimum of Months 48.125 0.911 0.000 0.000 16.252
Maximum of Months 744.000 54.497 494.413 10.897 54.497



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 46.042 0.527 528.187 4.679 6.608
February 155.542 2.652 314.386 3.283 6.845
March 323.707 6.411 216.500 1.413 8.446
April 534.941 14.436 36.131 0.162 14.608
May 704.916 25.572 0.000 0.000 25.572
June 719.000 34.961 0.000 0.000 34.961
July 744.000 39.766 0.000 0.000 39.766
August 744.000 38.941 0.000 0.000 38.941
September 712.041 30.963 0.000 0.000 30.963
October 529.460 13.712 51.839 0.275 14.013
November 347.767 7.483 177.706 1.095 9.197
December 129.917 2.401 413.482 3.487 7.356
           
Annual Sum or Average 5691.332 217.823 1738.232 14.394 237.276
Minimum of Months 46.042 0.527 0.000 0.000 6.608
Maximum of Months 744.000 39.766 528.187 4.679 39.766



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 42.458 0.544 540.400 10.064 14.146
February 150.634 2.997 316.094 6.985 12.841
March 319.947 7.431 198.792 3.001 14.789
April 510.650 17.391 24.500 0.343 20.155
May 695.158 31.884 0.000 0.000 31.918
June 716.000 44.169 0.000 0.000 44.169
July 744.000 50.299 0.000 0.000 50.299
August 744.000 48.977 0.000 0.000 48.977
September 691.775 38.779 0.000 0.000 38.779
October 510.301 16.917 38.966 0.628 20.347
November 322.958 8.362 169.159 2.467 14.444
December 117.708 2.519 426.603 7.720 14.292
           
Annual Sum or Average 5565.590 270.269 1714.514 31.210 325.156
Minimum of Months 42.458 0.544 0.000 0.000 12.841
Maximum of Months 744.000 50.299 540.400 10.064 50.299



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 77.375 2.143 528.983 15.785 18.764
February 161.902 5.645 318.181 11.211 18.667
March 314.283 11.794 229.577 5.714 22.577
April 476.454 23.069 50.169 0.902 28.190
May 672.752 39.826 1.625 0.005 40.517
June 713.583 54.829 0.000 0.000 54.829
July 744.000 63.502 0.000 0.000 63.502
August 744.000 62.345 0.000 0.000 62.345
September 675.997 50.884 0.000 0.000 50.884
October 480.512 25.862 67.141 1.503 31.767
November 357.008 14.633 179.739 4.516 21.785
December 172.063 5.305 397.312 12.139 18.636
           
Annual Sum or Average 5589.929 359.838 1772.728 51.776 432.463
Minimum of Months 77.375 2.143 0.000 0.000 18.636
Maximum of Months 744.000 63.502 528.983 15.785 63.502



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 77.112 1.518 506.754 6.408 8.446
February 171.433 4.306 307.817 4.673 9.192
March 330.313 8.865 241.083 2.317 11.253
April 506.004 17.838 57.222 0.350 18.207
May 685.961 30.988 0.000 0.000 30.988
June 715.683 42.567 0.000 0.000 42.567
July 744.000 49.084 0.000 0.000 49.084
August 744.000 48.658 0.000 0.000 48.658
September 690.915 39.897 0.000 0.000 39.897
October 515.992 20.574 66.125 0.512 21.086
November 384.996 12.203 167.567 1.657 13.884
December 178.067 4.178 372.104 4.791 8.973
           
Annual Sum or Average 5744.476 280.676 1718.672 20.710 302.235
Minimum of Months 77.112 1.518 0.000 0.000 8.446
Maximum of Months 744.000 49.084 506.754 6.408 49.084



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 69.342 1.519 509.225 12.136 18.598
February 160.185 4.616 305.604 8.648 17.046
March 318.930 9.791 228.292 4.269 17.340
April 492.960 20.539 46.125 0.647 23.460
May 685.632 36.838 0.000 0.000 37.322
June 715.150 51.324 0.000 0.000 51.324
July 744.000 59.097 0.000 0.000 59.097
August 744.000 58.047 0.000 0.000 58.047
September 685.065 47.109 0.000 0.000 47.109
October 501.163 23.422 56.125 1.038 27.761
November 364.574 12.954 158.958 3.248 19.811
December 157.512 4.162 366.479 9.208 18.455
           
Annual Sum or Average 5638.514 329.418 1670.808 39.194 395.370
Minimum of Months 69.342 1.519 0.000 0.000 17.046
Maximum of Months 744.000 59.097 509.225 12.136 59.097



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 44.308 0.991 554.950 15.587 22.027
February 138.833 4.234 337.971 10.723 18.233
March 295.954 10.351 255.252 5.388 20.271
April 472.193 22.517 63.750 0.921 26.042
May 672.881 39.839 3.913 0.015 40.162
June 713.667 55.147 0.000 0.000 55.147
July 744.000 63.681 0.000 0.000 63.681
August 744.000 62.152 0.000 0.000 62.152
September 675.517 49.594 0.000 0.000 49.594
October 458.243 22.207 86.744 1.465 27.335
November 313.523 10.865 194.070 4.372 21.709
December 115.212 3.174 415.933 11.874 23.656
           
Annual Sum or Average 5388.331 344.753 1912.583 50.344 430.008
Minimum of Months 44.308 0.991 0.000 0.000 18.233
Maximum of Months 744.000 63.681 554.950 15.587 63.681



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 42.125 0.581 569.237 7.746 9.486
February 146.640 3.078 340.654 5.337 9.323
March 304.992 7.625 259.048 2.557 10.601
April 499.402 17.381 60.347 0.373 17.778
May 686.240 31.079 0.000 0.000 31.079
June 715.857 42.961 0.000 0.000 42.961
July 744.000 49.352 0.000 0.000 49.352
August 744.000 48.573 0.000 0.000 48.573
September 690.669 38.744 0.000 0.000 38.744
October 489.584 17.072 75.112 0.590 17.674
November 320.485 8.654 208.790 2.059 11.250
December 116.958 2.542 445.783 5.873 9.638
           
Annual Sum or Average 5500.951 267.642 1958.972 24.538 296.459
Minimum of Months 42.125 0.581 0.000 0.000 9.323
Maximum of Months 744.000 49.352 569.237 7.746 49.352



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 37.958 0.613 576.004 13.872 17.489
February 141.224 3.410 340.746 9.525 15.703
March 299.438 8.562 243.850 4.533 16.356
April 487.833 20.148 48.350 0.667 22.992
May 685.976 36.996 0.000 0.000 37.466
June 715.263 51.776 0.000 0.000 51.776
July 744.000 59.450 0.000 0.000 59.450
August 744.000 58.089 0.000 0.000 58.089
September 684.815 46.155 0.000 0.000 46.155
October 484.073 20.076 60.788 1.095 24.509
November 311.779 9.500 203.213 3.777 16.547
December 111.196 2.661 452.121 10.694 18.142
           
Annual Sum or Average 5447.555 317.437 1925.071 44.163 384.676
Minimum of Months 37.958 0.613 0.000 0.000 15.703
Maximum of Months 744.000 59.450 576.004 13.872 59.450



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.57
February 0.00 0.00 0.67
March 0.00 0.00 0.81
April 0.00 0.00 1.00
May 0.00 0.00 1.16
June 0.00 0.00 1.32
July 0.00 0.00 1.37
August 0.00 0.00 1.37
September 0.00 0.00 1.29
October 0.00 0.00 1.01
November 0.00 0.00 0.88
December 0.00 0.00 0.66
       
Annual Sum or Average 0.00 0.00 1.01
Minimum of Months 0.00 0.00 0.57
Maximum of Months 0.00 0.00 1.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.26
June 0.00 0.00 0.39
July 0.00 0.00 0.44
August 0.00 0.00 0.45
September 0.00 0.00 0.38
October 0.00 0.00 0.19
November 0.00 0.00 0.12
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.08
April 0.00 0.00 0.18
May 0.00 0.00 0.31
June 0.00 0.00 0.48
July 0.00 0.00 0.54
August 0.00 0.00 0.54
September 0.00 0.00 0.46
October 0.00 0.00 0.21
November 0.00 0.00 0.13
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.07
April 0.00 0.00 0.17
May 0.00 0.00 0.31
June 0.00 0.00 0.47
July 0.00 0.00 0.53
August 0.00 0.00 0.51
September 0.00 0.00 0.42
October 0.00 0.00 0.16
November 0.00 0.00 0.08
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.05
April 0.00 0.00 0.13
May 0.00 0.00 0.25
June 0.00 0.00 0.40
July 0.00 0.00 0.45
August 0.00 0.00 0.43
September 0.00 0.00 0.35
October 0.00 0.00 0.13
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.16
May 0.00 0.00 0.31
June 0.00 0.00 0.48
July 0.00 0.00 0.54
August 0.00 0.00 0.52
September 0.00 0.00 0.42
October 0.00 0.00 0.16
November 0.00 0.00 0.08
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.06
March 0.00 0.00 0.11
April 0.00 0.00 0.21
May 0.00 0.00 0.33
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.52
September 0.00 0.00 0.44
October 0.00 0.00 0.23
November 0.00 0.00 0.15
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.05
March 0.00 0.00 0.09
April 0.00 0.00 0.18
May 0.00 0.00 0.28
June 0.00 0.00 0.39
July 0.00 0.00 0.44
August 0.00 0.00 0.44
September 0.00 0.00 0.38
October 0.00 0.00 0.20
November 0.00 0.00 0.13
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.05
March 0.00 0.00 0.10
April 0.00 0.00 0.20
May 0.00 0.00 0.34
June 0.00 0.00 0.48
July 0.00 0.00 0.53
August 0.00 0.00 0.53
September 0.00 0.00 0.45
October 0.00 0.00 0.23
November 0.00 0.00 0.14
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.09
April 0.00 0.00 0.19
May 0.00 0.00 0.33
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.41
October 0.00 0.00 0.18
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.07
April 0.00 0.00 0.16
May 0.00 0.00 0.28
June 0.00 0.00 0.40
July 0.00 0.00 0.44
August 0.00 0.00 0.43
September 0.00 0.00 0.35
October 0.00 0.00 0.15
November 0.00 0.00 0.08
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.08
April 0.00 0.00 0.19
May 0.00 0.00 0.33
June 0.00 0.00 0.48
July 0.00 0.00 0.53
August 0.00 0.00 0.52
September 0.00 0.00 0.42
October 0.00 0.00 0.17
November 0.00 0.00 0.09
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.06
March 0.00 0.00 0.11
April 0.00 0.00 0.22
May 0.00 0.00 0.37
June 0.00 0.00 0.54
July 0.00 0.00 0.60
August 0.00 0.00 0.59
September 0.00 0.00 0.49
October 0.00 0.00 0.24
November 0.00 0.00 0.14
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.09
April 0.00 0.00 0.19
May 0.00 0.00 0.32
June 0.00 0.00 0.46
July 0.00 0.00 0.51
August 0.00 0.00 0.51
September 0.00 0.00 0.43
October 0.00 0.00 0.21
November 0.00 0.00 0.13
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.51



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.10
April 0.00 0.00 0.22
May 0.00 0.00 0.38
June 0.00 0.00 0.55
July 0.00 0.00 0.61
August 0.00 0.00 0.60
September 0.00 0.00 0.50
October 0.00 0.00 0.23
November 0.00 0.00 0.14
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.29
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.10
April 0.00 0.00 0.22
May 0.00 0.00 0.37
June 0.00 0.00 0.54
July 0.00 0.00 0.60
August 0.00 0.00 0.58
September 0.00 0.00 0.48
October 0.00 0.00 0.20
November 0.00 0.00 0.11
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.60



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.08
April 0.00 0.00 0.18
May 0.00 0.00 0.32
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.51
September 0.00 0.00 0.41
October 0.00 0.00 0.17
November 0.00 0.00 0.09
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.08
April 0.00 0.00 0.21
May 0.00 0.00 0.38
June 0.00 0.00 0.55
July 0.00 0.00 0.61
August 0.00 0.00 0.60
September 0.00 0.00 0.48
October 0.00 0.00 0.20
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:28:03

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1352.70 1007.12
February 0.00 0.00 1346.14 905.25
March 0.00 0.00 1289.73 960.24
April 0.00 0.00 1198.29 863.38
May 0.00 0.00 1089.14 810.89
June 0.00 0.00 1001.26 721.42
July 0.00 0.00 954.23 710.45
August 0.00 0.00 957.65 713.00
September 0.00 0.00 1018.93 734.15
October 0.00 0.00 1111.51 827.55
November 0.00 0.00 1217.76 877.41
December 0.00 0.00 1307.30 973.32
         
Annual Sum or Average 0.00 0.00 1152.63 10104.19
Minimum of Months 0.00 0.00 954.23 710.45
Maximum of Months 0.00 0.00 1352.70 1007.12