Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
Tabular Output Report in Format: HTML
Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+gasfurnace+heatedbsmt+IECC_2009
Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Simulation Timestamp: 2019-02-14 08:32:39
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1015481.38 | 26.03 | 34.54 |
Net Site Energy | 1015481.38 | 26.03 | 34.54 |
Total Source Energy | 2290057.75 | 58.71 | 77.88 |
Net Source Energy | 2290057.75 | 58.71 | 77.88 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 66095.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 202074.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 263405.37 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 45314.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 214469.36 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 570943.80 | 444537.59 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 66095.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 202074.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 3888.48 | 79268.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 67443.41 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 143183.64 | 17261.25 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 59304.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 45314.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 214469.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 8.41 | 9.54 | 0.00 | 0.00 | 0.00 | 14.27 |
Other | 8.96 | 5.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 19.42 | 15.12 | 0.00 | 0.00 | 0.00 | 14.27 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 6.34 | 7.19 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 6.75 | 4.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 14.64 | 11.40 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 570943.799 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 570943.799 | 100.00 |
Total On-Site and Utility Electric Sources | 570943.799 | 100.00 |
Total Electricity End Uses | 570943.799 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 164.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 107.75 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32 |
RunPeriod | ANNUAL |
Weather File | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Latitude [deg] | 33.45 |
Longitude [deg] | -112.0 |
Elevation [ft] | 1105.70 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 2.4729 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.5522 | 816.79 | 3.2803 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 16-JUL-19:15 | 10-FEB-07:15 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 112.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 78.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.33 | 16.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 147.81 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 154.75 | 276.94 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 112.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 78.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 16.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 3.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 0.62 | 6.47 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 7.84 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 23.39 | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 9.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 13.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 147.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 71647.01 | 0.00 | 0.00 | 0.00 |
Cooling | 639968.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 834204.80 | 177746.94 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 143512.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 232484.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1808179.01 | 481878.74 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 |
Cooling | 21.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 28.37 | 6.04 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.91 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 61.49 | 16.39 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 2.44 | 0.00 | 0.00 | 0.00 |
Cooling | 21.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 28.37 | 6.04 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 7.91 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 61.49 | 16.39 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 38.66 | 0.00 | 38.66 | Wetbulb [F] | 334.66 | 100.00 |
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 110.12 | 21.60 | 69.98 | Wetbulb [F] | 807.13 | 260.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.651 | 0.260 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.651 | 0.260 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.651 | 0.260 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 28946.61 | 22925.55 | 6021.06 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11811.47 | 9108.48 | 2702.99 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15519.63 | 11800.06 | 3719.57 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 17991.00 | 14066.23 | 3924.76 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11578.51 | 8956.14 | 2622.37 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14993.93 | 11378.72 | 3615.22 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 17524.80 | 13689.73 | 3835.08 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11158.13 | 8600.48 | 2557.65 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14775.33 | 11205.80 | 3569.52 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 17226.36 | 13479.29 | 3747.07 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10935.97 | 8478.86 | 2457.11 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13647.73 | 10566.66 | 3081.07 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 20764.88 | 16321.04 | 4443.84 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14399.28 | 11219.09 | 3180.19 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17228.09 | 13413.59 | 3814.51 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 20743.86 | 16303.95 | 4439.91 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14303.24 | 11183.69 | 3119.55 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17110.25 | 13350.38 | 3759.87 | 0.78 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 14915.21 | 11387.09 | 3528.12 | 0.76 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.3 | 3.27 | 11.16 | 11.82 | 11.34 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9 | 3.31 | 11.30 | 11.97 | 11.55 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.2 | 3.33 | 11.37 | 12.04 | 11.66 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.4 | 3.29 | 11.23 | 11.89 | 11.44 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.9 | 3.31 | 11.28 | 11.95 | 11.53 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.2 | 3.33 | 11.38 | 12.05 | 11.68 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.4 | 3.29 | 11.23 | 11.89 | 11.45 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.9 | 3.31 | 11.30 | 11.97 | 11.55 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.2 | 3.33 | 11.38 | 12.06 | 11.68 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.4 | 3.29 | 11.22 | 11.89 | 11.43 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.9 | 3.30 | 11.27 | 11.94 | 11.51 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.1 | 3.30 | 11.28 | 11.94 | 11.52 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.7 | 3.28 | 11.20 | 11.86 | 11.40 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.1 | 3.30 | 11.24 | 11.91 | 11.47 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.4 | 3.30 | 11.25 | 11.91 | 11.47 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.7 | 3.28 | 11.20 | 11.86 | 11.40 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.1 | 3.29 | 11.23 | 11.89 | 11.44 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.4 | 3.29 | 11.24 | 11.90 | 11.46 | |
DX COOLING COIL_UNITHEATEDBSMT | 1.2 | 3.33 | 11.35 | 12.02 | 11.63 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 3900.50 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5709.43 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 7634.02 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 7650.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5836.03 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 7636.15 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6655.50 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 5104.57 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6973.62 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6982.83 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 5132.27 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 6971.51 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 8891.41 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 7078.18 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 8930.50 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 8936.10 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 7083.67 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 8927.99 | 0.80 | |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Fuel | 7689.98 | 0.80 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 1066.14 | 402.14 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 409.92 | 154.62 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 521.47 | 196.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 644.01 | 242.92 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 404.62 | 152.62 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 501.60 | 189.20 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 626.10 | 236.16 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 386.82 | 145.91 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 493.57 | 186.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 617.75 | 233.01 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 384.18 | 144.91 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 477.95 | 180.28 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 752.08 | 283.68 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 511.46 | 192.92 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 610.97 | 230.45 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 751.26 | 283.37 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 512.08 | 193.15 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 609.70 | 229.97 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 505.92 | 190.83 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 24064.66 | 24064.66 | 20.04 | 1066.142 | 1066.142 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00801 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9252.54 | 9252.54 | 7.71 | 409.919 | 409.919 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00806 | 104.13 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11770.68 | 11770.68 | 9.80 | 521.472 | 521.472 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00796 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 14536.37 | 14536.37 | 12.11 | 644.009 | 644.009 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00802 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9132.93 | 9132.93 | 7.61 | 404.621 | 404.621 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00808 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11322.13 | 11322.13 | 9.43 | 501.601 | 501.601 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00796 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 14131.95 | 14131.95 | 11.77 | 626.095 | 626.095 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00805 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8731.08 | 8731.08 | 7.27 | 386.819 | 386.819 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00813 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11140.75 | 11140.75 | 9.28 | 493.572 | 493.572 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00800 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13943.54 | 13943.54 | 11.61 | 617.749 | 617.749 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00806 | 104.94 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8671.49 | 8671.49 | 7.22 | 384.180 | 384.180 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00814 | 101.70 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10787.99 | 10787.99 | 8.99 | 477.946 | 477.946 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00807 | 104.94 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 13762.00 | 13762.00 | 11.46 | 609.702 | 609.702 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00802 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 13790.62 | 13790.62 | 11.49 | 610.969 | 610.969 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00801 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 16975.77 | 16975.77 | 14.14 | 752.082 | 752.082 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00802 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 11558.34 | 11558.34 | 9.63 | 512.075 | 512.075 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00807 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 11544.56 | 11544.56 | 9.62 | 511.464 | 511.464 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00805 | 104.13 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 16957.28 | 16957.28 | 14.12 | 751.263 | 751.263 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00802 | 105.48 | 0.00720 | 44.995 | 0.00 |
HEATEDBSMT | 11419.39 | 11419.39 | 1.47 | 505.916 | 505.916 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:00:00 | 74.98 | 74.98 | 0.00800 | 108.82 | 0.00720 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 38.66 | 0.00513 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4210.77 | 4210.77 | 3.51 | 79.771 | 79.771 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00682 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6163.83 | 6163.83 | 5.13 | 116.769 | 116.769 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00698 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6180.29 | 6180.29 | 5.15 | 117.081 | 117.081 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00698 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4339.24 | 4339.24 | 3.61 | 82.205 | 82.205 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00683 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6166.00 | 6166.00 | 5.14 | 116.810 | 116.810 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00698 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5170.78 | 5170.78 | 4.31 | 97.959 | 97.959 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00715 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3596.90 | 3596.90 | 3.00 | 68.143 | 68.143 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00705 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5493.60 | 5493.60 | 4.58 | 104.075 | 104.075 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00718 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5502.96 | 5502.96 | 4.58 | 104.252 | 104.252 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00718 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3625.00 | 3625.00 | 3.02 | 68.676 | 68.676 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00705 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5491.47 | 5491.47 | 4.57 | 104.035 | 104.035 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.99 | 0.00718 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7476.94 | 7476.94 | 6.23 | 141.644 | 141.644 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00709 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7479.48 | 7479.48 | 6.23 | 141.692 | 141.692 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00709 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7439.82 | 7439.82 | 6.20 | 140.941 | 140.941 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00709 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5605.33 | 5605.33 | 4.67 | 106.189 | 106.189 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00698 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.77 | 5599.77 | 4.66 | 106.084 | 106.084 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00698 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7485.17 | 7485.17 | 6.23 | 141.800 | 141.800 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00709 | 38.66 | 0.00513 | 44.995 | 0.00 |
HEATEDBSMT | 6220.39 | 6220.39 | 0.80 | 117.852 | 117.852 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 06:30:00 | 72.00 | 72.00 | 0.00800 | 38.66 | 0.00513 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 | 1066.14 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 | 409.92 | 79.77 | 79.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 | 521.47 | 116.77 | 116.77 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 | 644.01 | 117.08 | 117.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 | 404.62 | 82.20 | 82.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 | 501.60 | 116.81 | 116.81 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 | 626.10 | 97.96 | 97.96 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 | 386.82 | 68.14 | 68.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 | 493.57 | 104.07 | 104.07 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 | 617.75 | 104.25 | 104.25 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 | 384.18 | 68.68 | 68.68 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 | 477.95 | 104.03 | 104.03 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 752.08 | 752.08 | 140.94 | 140.94 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 511.46 | 511.46 | 106.08 | 106.08 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 610.97 | 610.97 | 141.69 | 141.69 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 751.26 | 751.26 | 141.80 | 141.80 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 512.08 | 512.08 | 106.19 | 106.19 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 609.70 | 609.70 | 141.64 | 141.64 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 505.92 | 505.92 | 117.85 | 117.85 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3216.75 | 3133.75 | 2.75 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2721.25 | 2976.00 | 37.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3413.50 | 2990.50 | 41.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3079.50 | 3756.50 | 55.75 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2348.75 | 3878.25 | 40.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3054.00 | 3644.25 | 42.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3688.50 | 2926.00 | 26.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2993.75 | 2671.00 | 12.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3660.00 | 2773.50 | 16.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3287.25 | 3534.75 | 28.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2605.50 | 3550.25 | 17.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3297.00 | 3413.75 | 24.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3614.25 | 3443.50 | 52.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3863.50 | 3006.50 | 47.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3778.50 | 3226.00 | 82.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 3036.50 | 3563.50 | 35.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3281.00 | 3026.00 | 33.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3540.75 | 3597.25 | 91.50 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4283.25 | 4225.75 | 107.75 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 110.25 | 0.00 | 110.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 52.75 | 0.00 | 52.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 10.25 | 0.00 | 10.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 87.25 | 0.00 | 87.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 57.25 | 0.00 | 57.25 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 17.00 | 0.00 | 17.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 71.25 | 0.00 | 71.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 38.25 | 0.00 | 38.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 4.25 | 0.00 | 4.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 78.25 | 0.00 | 78.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 47.50 | 0.00 | 47.50 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 41.75 | 0.00 | 41.75 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 89.00 | 0.00 | 89.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 77.25 | 0.00 | 77.25 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 106.50 | 0.00 | 106.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 86.50 | 0.00 | 86.50 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 77.75 | 0.00 | 77.75 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 109.50 | 0.00 | 109.50 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 164.00 | 0.00 | 164.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.206 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.179 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.202 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.178 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.065 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.065 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.178 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.179 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.202 | 0.000 | 0.265 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1900 |
Defaulted Fields | 509 |
Fields with Defaults | 4982 |
Autosized Fields | 300 |
Autosizable Fields | 410 |
Autocalculated Fields | 98 |
Autocalculatable Fields | 286 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
Electricity:Building | 91754.37 | 7056.43 | 02-JAN-03:15 | 17558.18 | 01-JAN-20:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 77145.04 | 6525.11 | 02-JAN-04:15 | 12799.44 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
gas_dryer:InteriorEquipment:Electricity | 1138.84 | 5.81 | 02-JAN-03:15 | 291.20 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
gas_mels:InteriorEquipment:Electricity | 41935.01 | 3663.85 | 01-JAN-09:15 | 7086.44 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 17368.96 | 1517.52 | 01-JAN-09:15 | 2935.11 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
Fans:Electricity | 13271.66 | 108.14 | 27-NOV-00:45 | 4069.00 | 16-JUL-17:00 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
ElectricityPurchased:Plant | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
Cogeneration:ElectricityPurchased | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
ElectricityNet:Plant | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
Cogeneration:ElectricityNet | 167215.59 | 8174.84 | 11-APR-04:00 | 45321.12 | 16-JUL-19:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 72454.29 | 509.24 | 27-NOV-01:00 | 27560.55 | 16-JUL-18:00 |
General:Fans:Electricity | 13271.66 | 108.14 | 27-NOV-00:45 | 4069.00 | 16-JUL-17:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 59182.63 | 54.16 | 31-JAN-06:45 | 23491.54 | 16-JUL-18:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4445.38 | 2644.47 | 06-APR-03:15 | 276745.45 | 10-FEB-07:15 |
Gas:Building | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
gas_dryer:InteriorEquipment:Gas | 792.69 | 403.80 | 02-JAN-03:15 | 20254.25 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Gas | 674.43 | 651.88 | 01-JAN-02:15 | 27685.38 | 01-JAN-17:15 |
gas_mels:InteriorEquipment:Gas | 172.61 | 1507.04 | 01-JAN-09:15 | 2914.85 | 01-JAN-20:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Plant | 2144.69 | 0.00 | 01-JAN-00:15 | 148256.57 | 22-JAN-08:45 |
WaterSystems:Gas | 2144.69 | 0.00 | 01-JAN-00:15 | 148256.57 | 22-JAN-08:45 |
Water Heater:WaterSystems:Gas | 2144.69 | 0.00 | 01-JAN-00:15 | 148256.57 | 22-JAN-08:45 |
Gas:HVAC | 660.95 | 0.00 | 23-FEB-15:15 | 117475.43 | 31-JAN-07:15 |
Heating:Gas | 660.95 | 0.00 | 23-FEB-15:15 | 117475.43 | 31-JAN-07:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 21-FEB-02:30 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
PlantLoopHeatingDemand:Plant | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
WaterSystems:PlantLoopHeatingDemand | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1654026.86 | 15217.67 | 05-APR-02:30 | 509455.93 | 17-JUN-19:00 |
EnergyTransfer:Building | 743715.89 | 6808.99 | 27-NOV-01:00 | 243318.79 | 02-JUL-18:45 |
EnergyTransfer:Zone:HEATEDBSMT | 39285.69 | 0.00 | 23-FEB-15:15 | 11600.02 | 16-JUL-19:00 |
Heating:EnergyTransfer | 57928.23 | 0.00 | 23-FEB-15:15 | 103019.84 | 31-JAN-07:15 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 8179.71 | 0.00 | 23-FEB-15:15 | 6444.41 | 31-JAN-07:15 |
Cooling:EnergyTransfer | 685787.66 | 970.92 | 31-JAN-06:45 | 243318.79 | 02-JUL-18:45 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 31105.98 | 0.00 | 01-JAN-00:15 | 11600.02 | 16-JUL-19:00 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 107758.75 | 970.92 | 31-JAN-06:45 | 23982.85 | 29-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 107758.75 | 970.92 | 31-JAN-06:45 | 23982.85 | 29-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 29495.25 | 0.00 | 01-JAN-00:15 | 9624.73 | 02-JUL-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1608.88 | 0.00 | 01-JAN-00:15 | 4149.09 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 27886.38 | 0.00 | 01-JAN-00:15 | 9624.73 | 02-JUL-19:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 38140.95 | 0.00 | 01-JAN-09:30 | 12290.68 | 16-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2985.30 | 0.00 | 01-JAN-09:30 | 6280.25 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 35155.65 | 0.00 | 01-JAN-00:15 | 12290.68 | 16-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 35193.35 | 0.00 | 01-JAN-14:00 | 14775.16 | 04-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4047.71 | 0.00 | 01-JAN-14:00 | 6343.74 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 31145.65 | 0.00 | 01-JAN-00:15 | 14775.16 | 04-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 25581.32 | 0.00 | 01-JAN-00:15 | 9529.35 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2369.49 | 0.00 | 01-JAN-00:15 | 4464.76 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23211.84 | 0.00 | 01-JAN-00:15 | 9529.35 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 34222.47 | 0.00 | 01-JAN-11:30 | 12024.20 | 16-JUL-20:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3629.48 | 0.00 | 01-JAN-11:30 | 6317.64 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30592.99 | 0.00 | 01-JAN-00:15 | 12024.20 | 16-JUL-20:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 37979.41 | 0.00 | 01-JAN-00:15 | 14537.43 | 29-SEP-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2138.98 | 0.00 | 01-JAN-00:15 | 5006.85 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 35840.43 | 0.00 | 01-JAN-00:15 | 14537.43 | 29-SEP-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 29019.61 | 0.00 | 01-JAN-00:15 | 9111.99 | 16-JUL-20:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 970.23 | 0.00 | 01-JAN-00:15 | 3289.81 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 28049.37 | 0.00 | 01-JAN-00:15 | 9111.99 | 16-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 37483.59 | 0.00 | 01-JAN-00:15 | 11740.01 | 16-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2133.87 | 0.00 | 01-JAN-00:15 | 5390.62 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 35349.72 | 0.00 | 01-JAN-00:15 | 11740.01 | 16-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 34215.29 | 0.00 | 01-JAN-00:15 | 14120.45 | 10-JUN-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3057.99 | 0.00 | 01-JAN-00:15 | 5515.35 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 31157.30 | 0.00 | 01-JAN-00:15 | 14120.45 | 10-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 24755.95 | 0.00 | 01-JAN-00:15 | 9020.01 | 16-JUL-21:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1515.76 | 0.00 | 01-JAN-00:15 | 3591.15 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23240.19 | 0.00 | 01-JAN-00:15 | 9020.01 | 16-JUL-21:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 33382.03 | 0.00 | 01-JAN-00:15 | 11124.55 | 16-JUL-20:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2693.17 | 0.00 | 01-JAN-00:15 | 5433.18 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 30688.85 | 0.00 | 01-JAN-00:15 | 11124.55 | 16-JUL-20:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 40905.18 | 0.00 | 01-JAN-12:30 | 13968.72 | 17-JUN-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4423.81 | 0.00 | 01-JAN-12:30 | 7610.34 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 36481.37 | 0.00 | 01-JAN-00:15 | 13968.72 | 17-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 43202.20 | 0.00 | 01-JAN-10:15 | 14002.71 | 02-JUL-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 3742.16 | 0.00 | 01-JAN-10:15 | 7582.09 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 39460.04 | 0.00 | 01-JAN-00:15 | 14002.71 | 02-JUL-19:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 44163.63 | 0.00 | 01-JAN-00:15 | 17060.99 | 27-AUG-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4105.02 | 0.00 | 01-JAN-00:15 | 7481.10 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 40058.61 | 0.00 | 01-JAN-00:15 | 17060.99 | 27-AUG-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 32264.05 | 0.00 | 01-JAN-00:15 | 11776.88 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3066.79 | 0.00 | 01-JAN-00:15 | 5722.67 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 29197.27 | 0.00 | 01-JAN-00:15 | 11776.88 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 34644.71 | 0.00 | 01-JAN-00:15 | 11849.51 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2352.24 | 0.00 | 01-JAN-00:15 | 5496.55 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 32292.47 | 0.00 | 01-JAN-00:15 | 11849.51 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 42022.46 | 0.00 | 01-JAN-14:00 | 17022.79 | 27-AUG-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4907.66 | 0.00 | 01-JAN-14:00 | 7662.90 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 37114.80 | 0.00 | 01-JAN-00:15 | 17022.79 | 27-AUG-17:30 |
EnergyTransfer:Plant | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
WaterSystems:EnergyTransfer | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 93474.58 | 431.68 | 21-JUL-03:00 | 31800.96 | 21-JAN-08:15 |
EnergyTransfer:HVAC | 816836.39 | 7155.87 | 27-NOV-01:00 | 279111.35 | 10-AUG-18:30 |
HeatingCoils:EnergyTransfer | 52876.02 | 0.00 | 23-FEB-15:15 | 93980.35 | 31-JAN-07:15 |
CoolingCoils:EnergyTransfer | 763960.37 | 1023.06 | 31-JAN-06:45 | 279111.35 | 10-AUG-18:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8973.90 | 0.000 | 0.000 | 2872.262 | 2771.241 | 14528.036 | 15179.564 | 0.000 | 5507.759 | 77190.870 | 0.000 | -4441.45 | 0.000 | -5849.52 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1608.859 | -2322.31 | 0.000 | 0.000 | 2933.317 | 2771.241 | 14528.036 | 6553.352 | 0.000 | 5201.710 | 1072.261 | 0.000 | -1713.52 | 0.000 | -5068.85 | -0.16 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 2985.271 | -2927.68 | 0.000 | 0.000 | 2948.144 | 2771.241 | 14528.036 | 15097.793 | 0.000 | 5518.825 | 594.895 | 0.000 | -4000.85 | 0.000 | -5287.72 | -0.02 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4047.673 | -2593.74 | 0.000 | 0.000 | 2956.832 | 2771.241 | 14528.036 | 11687.018 | 0.000 | 5510.363 | 0.306 | 0.000 | -4401.01 | 0.000 | -5131.71 | -822.78 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 2369.464 | -1933.03 | 0.000 | 0.000 | 2947.656 | 2771.241 | 14528.036 | 2747.706 | 0.000 | 5201.606 | 0.117 | 0.000 | -1848.06 | 0.000 | -4904.60 | -601.15 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3629.451 | -2547.71 | 0.000 | 0.000 | 2959.894 | 2771.241 | 14528.036 | 11344.120 | 0.000 | 5518.134 | 0.103 | 0.000 | -4006.57 | 0.000 | -5148.46 | -1002.84 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2138.957 | -2984.71 | 0.000 | 0.000 | 2936.390 | 2771.241 | 14528.036 | 15216.967 | 0.000 | 4033.016 | 2567.380 | 0.000 | -4349.82 | 0.000 | -4001.72 | -0.12 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 970.221 | -2335.89 | 0.000 | 0.000 | 2919.988 | 2771.241 | 14528.036 | 6538.180 | 0.000 | 3723.501 | 2156.664 | 0.000 | -1762.58 | 0.000 | -3795.82 | -0.02 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2133.853 | -2943.84 | 0.000 | 0.000 | 2937.252 | 2771.241 | 14528.036 | 15041.844 | 0.000 | 4037.645 | 2039.836 | 0.000 | -4115.40 | 0.000 | -4024.58 | -0.19 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 3057.965 | -2594.71 | 0.000 | 0.000 | 2946.104 | 2771.241 | 14528.036 | 11684.972 | 0.000 | 4033.249 | 565.271 | 0.000 | -4519.29 | 0.000 | -3910.21 | -0.22 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 1515.745 | -1935.40 | 0.000 | 0.000 | 2933.920 | 2771.241 | 14528.036 | 2767.705 | 0.000 | 3723.242 | 581.742 | 0.000 | -1898.73 | 0.000 | -3682.63 | -0.27 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2693.155 | -2555.70 | 0.000 | 0.000 | 2949.476 | 2771.241 | 14528.036 | 11318.817 | 0.000 | 4035.153 | 426.110 | 0.000 | -4111.40 | 0.000 | -3921.70 | -0.54 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 4423.775 | -3038.09 | 0.000 | 0.000 | 2956.807 | 2771.241 | 14528.036 | 11188.702 | 0.000 | 5487.015 | 4405.406 | 0.000 | -4104.08 | 0.000 | -5175.49 | -0.17 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3742.128 | -3286.14 | 0.000 | 0.000 | 2947.967 | 2771.241 | 14528.036 | 14945.348 | 0.000 | 5488.361 | 4391.563 | 0.000 | -4073.32 | 0.000 | -5281.26 | -0.07 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4104.982 | -3335.99 | 0.000 | 0.000 | 2948.336 | 2771.241 | 14528.036 | 15130.512 | 0.000 | 5484.540 | 4610.966 | 0.000 | -4277.19 | 0.000 | -5242.80 | -0.19 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3066.758 | -2431.49 | 0.000 | 0.000 | 2945.599 | 2771.241 | 14528.036 | 2713.922 | 0.000 | 5176.920 | 4813.472 | 0.000 | -1881.72 | 0.000 | -4936.89 | -0.02 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 2352.215 | -2689.25 | 0.000 | 0.000 | 2935.886 | 2771.241 | 14528.036 | 6498.811 | 0.000 | 5177.555 | 4812.700 | 0.000 | -1736.06 | 0.000 | -5047.86 | -0.24 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 4907.621 | -3090.84 | 0.000 | 0.000 | 2954.695 | 2771.241 | 14528.036 | 11525.213 | 0.000 | 5485.088 | 4579.094 | 0.000 | -4473.48 | 0.000 | -5162.68 | -0.11 |
HEATEDBSMT | 0.000 | 0.000 | 8179.706 | -2590.43 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 22926.277 | 0.000 | 0.000 | 0.000 | 0.000 | -0.51 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7634.470 | 52267.085 | 0.000 | 0.000 | 0.000 | -59901.55 | -0.47 |
Total Facility | 0.000 | 0.000 | 57927.797 | -57110.84 | 0.000 | 0.000 | 52930.524 | 49882.340 | 261504.651 | 187180.546 | 0.000 | 95978.153 | 190002.119 | 0.000 | -61714.51 | 0.000 | -145476.06 | -2430.10 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-SEP-17:06 | 0.00 | 0.00 | 0.00 | -2.0 | 0.00 | 0.00 | 263.32 | 604.65 | 2756.77 | 6835.44 | 0.00 | 2095.13 | 11450.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 02-JUL-19:15 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 421.40 | 902.05 | 2354.09 | 786.04 | 0.00 | 2802.82 | 2365.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-JUL-19:30 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 419.80 | 902.05 | 2354.09 | 2142.87 | 0.00 | 3173.61 | 3321.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 04-JUN-17:18 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 263.32 | 604.65 | 2787.26 | 7909.93 | 0.00 | 2748.76 | 486.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 02-JUL-19:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 421.19 | 902.05 | 2354.09 | 722.36 | 0.00 | 2552.66 | 2596.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 420.03 | 902.05 | 2354.09 | 1837.20 | 0.00 | 2837.42 | 3697.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-SEP-17:03 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 263.32 | 604.65 | 2756.77 | 6824.28 | 0.00 | 1577.86 | 2532.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16-JUL-20:55 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.17 | 902.05 | 2199.79 | 642.62 | 0.00 | 1576.00 | 3400.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-JUL-19:38 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 424.27 | 902.05 | 2354.09 | 2016.37 | 0.00 | 2096.46 | 4010.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10-JUN-18:03 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 427.01 | 813.96 | 2698.15 | 7376.85 | 0.00 | 1622.33 | 1183.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-JUL-21:38 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 475.84 | 682.17 | 2064.68 | 631.33 | 0.00 | 1520.33 | 3679.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16-JUL-20:55 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 423.00 | 902.05 | 2199.79 | 1532.88 | 0.00 | 1709.04 | 4394.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 17-JUN-19:33 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 426.64 | 902.05 | 2354.09 | 1662.21 | 0.00 | 2691.45 | 5966.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 02-JUL-19:12 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 420.79 | 902.05 | 2354.09 | 1871.13 | 0.00 | 3004.46 | 5469.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-AUG-17:33 | 0.00 | 0.00 | 0.00 | -1.4 | 0.00 | 0.00 | 256.67 | 604.65 | 2787.26 | 6882.69 | 0.00 | 2533.89 | 4021.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-JUL-19:36 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 423.71 | 902.05 | 2354.09 | 631.56 | 0.00 | 2300.89 | 5279.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 02-JUL-19:30 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 421.24 | 902.05 | 2354.09 | 678.51 | 0.00 | 2544.32 | 4972.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 27-AUG-17:33 | 0.00 | 0.00 | 0.00 | -1.4 | 0.00 | 0.00 | 257.32 | 604.65 | 2787.26 | 6918.02 | 0.00 | 2540.71 | 3941.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-18:56 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11633.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 02-JUL-18:45 | 0.00 | 0.00 | 0.00 | -20.3 | 0.00 | 0.00 | 7531.33 | 14651.21 | 48566.62 | 44471.91 | 0.00 | 50757.87 | 83285.80 | 0.00 | 0.00 | 0.00 | -5798.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 4149.16 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1112.3 | 0.00 | -3374.0 | -2197.3 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 6280.36 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2702.5 | 0.00 | -3593.3 | -2518.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 6343.76 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2350.8 | 0.00 | -3483.9 | -2518.1 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 4464.81 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -968.5 | 0.00 | -3273.2 | -2232.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 6317.75 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2698.2 | 0.00 | -3593.3 | -2560.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5006.99 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2754.4 | 0.00 | -2563.9 | -2223.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 3289.90 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1130.0 | 0.00 | -2344.3 | -2350.1 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5390.77 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2747.9 | 0.00 | -2563.9 | -2613.4 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 5515.36 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2386.3 | 0.00 | -2495.1 | -2643.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 3591.18 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -987.6 | 0.00 | -2284.2 | -2328.4 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5433.32 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2736.8 | 0.00 | -2563.9 | -2667.1 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 7610.49 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2714.9 | 0.00 | -3601.1 | -3828.8 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 7582.24 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2728.6 | 0.00 | -3601.1 | -3786.9 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 7481.26 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2714.5 | 0.00 | -3601.1 | -3700.0 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 5722.70 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -977.5 | 0.00 | -3280.4 | -3473.8 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5496.66 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1682.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1118.7 | 0.00 | -3381.3 | -3531.0 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 7662.90 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2362.2 | 0.00 | -3491.6 | -3818.0 |
HEATEDBSMT | 31-JAN-07:15 | 0.00 | 0.00 | 6444.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6444.4 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JAN-07:15 | -1340.9 | 0.11 | 103021.91 | -0.1 | 0.00 | 0.00 | 8321.72 | 6976.77 | 30276.56 | 0.00 | 0.00 | 3017.97 | 0.00 | 0.00 | -39500.1 | 0.00 | -57599.9 | -53174.1 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.142 | 2.00 | 2.00 | 1.00 | 44.9950 | 1066.142 | 0.042 | 1.000 | 44.9950 | 0.04 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 409.919 | 2.00 | 2.00 | 1.00 | 44.9950 | 409.919 | 0.110 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 521.472 | 2.00 | 2.00 | 1.00 | 44.9950 | 521.472 | 0.086 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 644.009 | 2.00 | 2.00 | 1.00 | 44.9950 | 644.009 | 0.070 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 404.621 | 2.00 | 2.00 | 1.00 | 44.9950 | 404.621 | 0.111 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 501.601 | 2.00 | 2.00 | 1.00 | 44.9950 | 501.601 | 0.090 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 626.095 | 2.00 | 2.00 | 1.00 | 44.9950 | 626.095 | 0.072 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 386.819 | 2.00 | 2.00 | 1.00 | 44.9950 | 386.819 | 0.116 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 493.572 | 2.00 | 2.00 | 1.00 | 44.9950 | 493.572 | 0.091 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 617.749 | 2.00 | 2.00 | 1.00 | 44.9950 | 617.749 | 0.073 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 384.180 | 2.00 | 2.00 | 1.00 | 44.9950 | 384.180 | 0.117 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 477.946 | 2.00 | 2.00 | 1.00 | 44.9950 | 477.946 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 752.082 | 2.00 | 2.00 | 1.00 | 44.9950 | 752.082 | 0.060 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 511.464 | 2.00 | 2.00 | 1.00 | 44.9950 | 511.464 | 0.088 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 610.969 | 2.00 | 2.00 | 1.00 | 44.9950 | 610.969 | 0.074 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 751.263 | 2.00 | 2.00 | 1.00 | 44.9950 | 751.263 | 0.060 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 512.075 | 2.00 | 2.00 | 1.00 | 44.9950 | 512.075 | 0.088 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 609.702 | 2.00 | 2.00 | 1.00 | 44.9950 | 609.702 | 0.074 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 505.916 | 0.00 | 0.00 | 1.00 | 44.9950 | 505.916 | 0.089 | 1.000 | 44.9950 | 0.09 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 79.771 | 2.00 | 2.00 | 1.00 | 44.9950 | 79.771 | 1.000 | 1.000 | 44.9950 | 0.56 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 116.769 | 2.00 | 2.00 | 1.00 | 44.9950 | 116.769 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 117.081 | 2.00 | 2.00 | 1.00 | 44.9950 | 117.081 | 1.000 | 1.000 | 44.9950 | 0.38 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 82.205 | 2.00 | 2.00 | 1.00 | 44.9950 | 82.205 | 1.000 | 1.000 | 44.9950 | 0.55 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 116.810 | 2.00 | 2.00 | 1.00 | 44.9950 | 116.810 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 97.959 | 2.00 | 2.00 | 1.00 | 44.9950 | 97.959 | 1.000 | 1.000 | 44.9950 | 0.46 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 68.143 | 2.00 | 2.00 | 1.00 | 44.9950 | 68.143 | 1.000 | 1.000 | 44.9950 | 0.66 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 104.075 | 2.00 | 2.00 | 1.00 | 44.9950 | 104.075 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 104.252 | 2.00 | 2.00 | 1.00 | 44.9950 | 104.252 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 68.676 | 2.00 | 2.00 | 1.00 | 44.9950 | 68.676 | 1.000 | 1.000 | 44.9950 | 0.66 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 104.035 | 2.00 | 2.00 | 1.00 | 44.9950 | 104.035 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 140.941 | 2.00 | 2.00 | 1.00 | 44.9950 | 140.941 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 106.084 | 2.00 | 2.00 | 1.00 | 44.9950 | 106.084 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 141.692 | 2.00 | 2.00 | 1.00 | 44.9950 | 141.692 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 141.800 | 2.00 | 2.00 | 1.00 | 44.9950 | 141.800 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 106.189 | 2.00 | 2.00 | 1.00 | 44.9950 | 106.189 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 141.644 | 2.00 | 2.00 | 1.00 | 44.9950 | 141.644 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 117.852 | 0.00 | 0.00 | 1.00 | 44.9950 | 117.852 | 1.000 | 1.000 | 44.9950 | 0.38 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.142 | 1066.1421 | 213.2284 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 409.919 | 409.9194 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 521.472 | 521.4722 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 644.009 | 644.0087 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 404.621 | 404.6206 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 501.601 | 501.6006 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 626.095 | 626.0951 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 386.819 | 386.8191 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 493.572 | 493.5717 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 617.749 | 617.7486 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 384.180 | 384.1799 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 477.946 | 477.9461 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 609.702 | 609.7015 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 610.969 | 610.9687 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 752.082 | 752.0823 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 512.075 | 512.0751 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 511.464 | 511.4638 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 751.263 | 751.2633 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 505.916 | 505.9164 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 | 1066.142 | 1066.14 | 213.2284 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 | 409.919 | 409.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 | 521.472 | 521.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 | 644.009 | 644.01 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 | 404.621 | 404.62 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 | 501.601 | 501.60 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 | 626.095 | 626.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 | 386.819 | 386.82 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 | 493.572 | 493.57 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 | 617.749 | 617.75 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 | 384.180 | 384.18 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 | 477.946 | 477.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 752.08 | 752.082 | 752.08 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 511.46 | 511.464 | 511.46 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 610.97 | 610.969 | 610.97 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 751.26 | 751.263 | 751.26 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 512.08 | 512.075 | 512.08 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 609.70 | 609.702 | 609.70 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 505.92 | 505.916 | 505.92 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 79.771 | 79.771 | 79.771 | 44.9950 | 0.564 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 116.769 | 116.769 | 116.769 | 44.9950 | 0.385 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 117.081 | 117.081 | 117.081 | 44.9950 | 0.384 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 82.205 | 82.205 | 82.205 | 44.9950 | 0.547 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 116.810 | 116.810 | 116.810 | 44.9950 | 0.385 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 97.959 | 97.959 | 97.959 | 44.9950 | 0.459 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 68.143 | 68.143 | 68.143 | 44.9950 | 0.660 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 104.075 | 104.075 | 104.075 | 44.9950 | 0.432 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 104.252 | 104.252 | 104.252 | 44.9950 | 0.432 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 68.676 | 68.676 | 68.676 | 44.9950 | 0.655 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 104.035 | 104.035 | 104.035 | 44.9950 | 0.433 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 141.644 | 141.644 | 141.644 | 44.9950 | 0.318 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 141.692 | 141.692 | 141.692 | 44.9950 | 0.318 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 140.941 | 140.941 | 140.941 | 44.9950 | 0.319 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 106.189 | 106.189 | 106.189 | 44.9950 | 0.424 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 106.084 | 106.084 | 106.084 | 44.9950 | 0.424 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 141.800 | 141.800 | 141.800 | 44.9950 | 0.317 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 117.852 | 117.852 | 117.852 | 44.9950 | 0.382 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 79.77 | 79.771 | 79.77 | 79.77 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 116.77 | 116.769 | 116.77 | 116.77 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 117.08 | 117.081 | 117.08 | 117.08 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 82.20 | 82.205 | 82.20 | 82.20 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 116.81 | 116.810 | 116.81 | 116.81 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 97.96 | 97.959 | 97.96 | 97.96 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 68.14 | 68.143 | 68.14 | 68.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 104.07 | 104.075 | 104.07 | 104.07 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 104.25 | 104.252 | 104.25 | 104.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 68.68 | 68.676 | 68.68 | 68.68 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 104.03 | 104.035 | 104.03 | 104.03 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 140.94 | 140.941 | 140.94 | 140.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 106.08 | 106.084 | 106.08 | 106.08 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 141.69 | 141.692 | 141.69 | 141.69 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 141.80 | 141.800 | 141.80 | 141.80 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 106.19 | 106.189 | 106.19 | 106.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 141.64 | 141.644 | 141.64 | 141.64 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 117.85 | 117.852 | 117.85 | 117.85 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 164.00 |
Number of hours not met | 164.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4758.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 741.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 660.95 | 112651.34 | 0.00 | 0.00 |
Space Cooling | 59182.63 | 23066.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 13271.66 | 4065.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2144.69 | 147703.47 | 0.00 | 0.00 |
Receptacle Equipment | 77145.04 | 12689.50 | 1639.73 | 16390.65 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 167215.59 | 4445.38 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 263405.37 | 570943.80 |
Natural Gas | 163973.19 | 444537.59 |
Additional | 0.00 | 0.00 |
Total | 427378.56 | 1015481.38 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 1.52 |
Fans-Interior | 0.34 |
Service Water Heating | 0.00 |
Receptacle Equipment | 1.98 |
Miscellaneous | 0.08 |
Subtotal | 4.29 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.50 |
Service Water Heating | 1.61 |
Miscellaneous | 1.23 |
Subtotal | 3.34 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.91 |
Space Heating | 6.51 |
Space Cooling | 19.90 |
Fans-Interior | 4.46 |
Service Water Heating | 21.12 |
Receptacle Equipment | 42.09 |
Miscellaneous | 1.01 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 505.92 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 609.70 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 610.97 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 752.08 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 512.08 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 511.46 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 751.26 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 752.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 511.46 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 610.97 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 751.26 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 512.08 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 609.70 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 505.92 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 | 2.41 | 0.791994 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 | 0.984289 | 0.771155 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 | 1.29 | 0.760331 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 | 1.50 | 0.781848 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 | 0.964876 | 0.773514 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 | 1.25 | 0.758888 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 | 1.46 | 0.781163 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 | 0.929844 | 0.770781 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 | 1.23 | 0.758413 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 | 1.44 | 0.782481 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 | 0.911330 | 0.775319 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 | 1.14 | 0.774243 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 752.08 | 1.73 | 0.785992 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 511.46 | 1.20 | 0.779143 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 610.97 | 1.44 | 0.778588 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 751.26 | 1.73 | 0.785965 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 512.08 | 1.19 | 0.781899 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 609.70 | 1.43 | 0.780256 |
DX COOLING COIL_UNITHEATEDBSMT | 505.92 | 1.24 | 0.763455 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 | 1066.14 | 1066.14 | 3900.50 | 2.41 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 | 409.92 | 409.92 | 5709.43 | 0.984289 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 | 521.47 | 521.47 | 7634.02 | 1.29 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 | 644.01 | 644.01 | 7650.24 | 1.50 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 | 404.62 | 404.62 | 5836.03 | 0.964876 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 | 501.60 | 501.60 | 7636.15 | 1.25 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 | 626.10 | 626.10 | 6655.50 | 1.46 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 | 386.82 | 386.82 | 5104.57 | 0.929844 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 | 493.57 | 493.57 | 6973.62 | 1.23 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 | 617.75 | 617.75 | 6982.83 | 1.44 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 | 384.18 | 384.18 | 5132.27 | 0.911330 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 | 477.95 | 477.95 | 6971.51 | 1.14 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 752.08 | 752.08 | 752.08 | 8891.41 | 1.73 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 511.46 | 511.46 | 511.46 | 7078.18 | 1.20 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 610.97 | 610.97 | 610.97 | 8930.50 | 1.44 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 751.26 | 751.26 | 751.26 | 8936.10 | 1.73 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 512.08 | 512.08 | 512.08 | 7083.67 | 1.19 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 609.70 | 609.70 | 609.70 | 8927.99 | 1.43 | 1.00 |
ACANDF_UNITHEATEDBSMT | 505.92 | 505.92 | 505.92 | 7689.98 | 1.24 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 1066.14 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 409.92 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 521.47 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 644.01 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 404.62 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 501.60 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 626.10 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 386.82 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 493.57 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 617.75 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 384.18 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 477.95 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 752.08 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 511.46 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 610.97 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 751.26 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 512.08 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 609.70 |
SUPPLY FAN_UNITHEATEDBSMT | 505.92 |
Design Size Nominal Capacity [Btu/h] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 3900.50 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 5709.43 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 7634.02 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 7650.24 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 5836.03 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 7636.15 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 6655.50 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 5104.57 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 6973.62 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 6982.83 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 5132.27 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 6971.51 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 8891.41 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 7078.18 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 8930.50 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 8936.10 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 7083.67 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 8927.99 |
MAIN FUEL HEATING COIL_UNITHEATEDBSMT | 7689.98 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:32:39
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 93.255 | 0.000 | 0.000 | 93.255 |
February | 672.000 | 97.525 | 0.000 | 0.000 | 97.525 |
March | 744.000 | 116.563 | 0.000 | 0.000 | 116.563 |
April | 720.000 | 144.936 | 0.000 | 0.000 | 144.936 |
May | 744.000 | 171.418 | 0.000 | 0.000 | 171.418 |
June | 720.000 | 203.291 | 0.000 | 0.000 | 203.291 |
July | 744.000 | 226.926 | 0.000 | 0.000 | 226.926 |
August | 744.000 | 215.825 | 0.000 | 0.000 | 215.825 |
September | 720.000 | 186.545 | 0.000 | 0.000 | 186.545 |
October | 744.000 | 161.489 | 0.000 | 0.000 | 161.489 |
November | 720.000 | 119.164 | 0.000 | 0.000 | 119.164 |
December | 744.000 | 87.223 | 0.000 | 0.000 | 87.223 |
Annual Sum or Average | 8760.000 | 1824.159 | 0.000 | 0.000 | 1824.159 |
Minimum of Months | 672.000 | 87.223 | 0.000 | 0.000 | 87.223 |
Maximum of Months | 744.000 | 226.926 | 0.000 | 0.000 | 226.926 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 272.498 | 9.307 | 272.542 | 10.784 | 20.091 |
February | 300.230 | 14.150 | 189.631 | 7.318 | 21.467 |
March | 378.539 | 16.654 | 132.517 | 4.742 | 21.395 |
April | 561.690 | 32.183 | 44.542 | 1.401 | 33.585 |
May | 714.395 | 44.413 | 0.000 | 0.000 | 44.413 |
June | 720.000 | 67.654 | 0.000 | 0.000 | 67.654 |
July | 744.000 | 82.683 | 0.000 | 0.000 | 82.683 |
August | 744.000 | 75.661 | 0.000 | 0.000 | 75.661 |
September | 720.000 | 59.918 | 0.000 | 0.000 | 59.918 |
October | 685.698 | 43.889 | 7.250 | 0.066 | 43.955 |
November | 446.880 | 20.976 | 70.125 | 1.524 | 22.500 |
December | 242.416 | 8.127 | 316.375 | 14.020 | 22.147 |
Annual Sum or Average | 6530.345 | 475.613 | 1032.982 | 39.856 | 515.468 |
Minimum of Months | 242.416 | 8.127 | 0.000 | 0.000 | 20.091 |
Maximum of Months | 744.000 | 82.683 | 316.375 | 14.020 | 82.683 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 231.574 | 8.288 | 334.067 | 19.089 | 27.377 |
February | 285.174 | 15.514 | 230.000 | 12.438 | 27.952 |
March | 384.000 | 19.884 | 170.042 | 8.440 | 28.324 |
April | 558.601 | 41.166 | 57.000 | 2.370 | 43.537 |
May | 702.338 | 57.120 | 1.500 | 0.005 | 57.125 |
June | 720.000 | 87.049 | 0.000 | 0.000 | 87.049 |
July | 744.000 | 104.275 | 0.000 | 0.000 | 104.275 |
August | 744.000 | 94.702 | 0.000 | 0.000 | 94.702 |
September | 720.000 | 73.065 | 0.000 | 0.000 | 73.065 |
October | 667.638 | 50.726 | 23.875 | 0.569 | 51.295 |
November | 429.502 | 21.921 | 128.937 | 4.177 | 26.098 |
December | 203.344 | 7.101 | 365.406 | 23.562 | 30.663 |
Annual Sum or Average | 6390.171 | 580.810 | 1310.827 | 70.651 | 651.461 |
Minimum of Months | 203.344 | 7.101 | 0.000 | 0.000 | 26.098 |
Maximum of Months | 744.000 | 104.275 | 365.406 | 23.562 | 104.275 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 116.588 | 3.043 | 440.292 | 31.442 | 34.485 |
February | 198.301 | 9.755 | 304.146 | 20.034 | 29.789 |
March | 293.596 | 15.891 | 229.317 | 12.402 | 28.293 |
April | 506.387 | 39.426 | 75.750 | 3.812 | 43.238 |
May | 689.593 | 59.979 | 2.083 | 0.008 | 59.988 |
June | 720.000 | 93.241 | 0.000 | 0.000 | 93.241 |
July | 744.000 | 110.856 | 0.000 | 0.000 | 110.856 |
August | 744.000 | 98.606 | 0.000 | 0.000 | 98.606 |
September | 720.000 | 71.098 | 0.000 | 0.000 | 71.098 |
October | 638.020 | 42.584 | 39.375 | 1.130 | 43.713 |
November | 316.458 | 12.113 | 202.783 | 7.779 | 19.893 |
December | 83.725 | 1.951 | 498.458 | 39.271 | 41.222 |
Annual Sum or Average | 5770.669 | 558.542 | 1792.204 | 115.878 | 674.420 |
Minimum of Months | 83.725 | 1.951 | 0.000 | 0.000 | 19.893 |
Maximum of Months | 744.000 | 110.856 | 498.458 | 39.271 | 110.856 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 77.771 | 1.134 | 411.913 | 16.019 | 17.153 |
February | 200.492 | 6.124 | 266.286 | 10.062 | 16.186 |
March | 308.210 | 9.432 | 164.464 | 5.552 | 14.983 |
April | 546.929 | 27.756 | 54.000 | 1.651 | 29.408 |
May | 713.658 | 43.657 | 0.000 | 0.000 | 43.657 |
June | 720.000 | 68.200 | 0.000 | 0.000 | 68.200 |
July | 744.000 | 82.427 | 0.000 | 0.000 | 82.427 |
August | 744.000 | 73.094 | 0.000 | 0.000 | 73.094 |
September | 720.000 | 52.829 | 0.000 | 0.000 | 52.829 |
October | 669.258 | 33.009 | 15.500 | 0.155 | 33.164 |
November | 345.492 | 8.134 | 113.855 | 2.428 | 10.562 |
December | 48.598 | 0.530 | 488.012 | 20.981 | 21.511 |
Annual Sum or Average | 5838.408 | 406.324 | 1514.030 | 56.848 | 463.173 |
Minimum of Months | 48.598 | 0.530 | 0.000 | 0.000 | 10.562 |
Maximum of Months | 744.000 | 82.427 | 488.012 | 20.981 | 82.427 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 69.089 | 1.047 | 455.792 | 23.281 | 24.328 |
February | 214.271 | 7.708 | 286.100 | 14.152 | 21.860 |
March | 348.268 | 12.698 | 184.185 | 8.626 | 21.325 |
April | 552.907 | 36.543 | 57.750 | 2.364 | 38.908 |
May | 702.547 | 55.687 | 1.500 | 0.005 | 55.692 |
June | 720.000 | 86.427 | 0.000 | 0.000 | 86.427 |
July | 744.000 | 102.767 | 0.000 | 0.000 | 102.767 |
August | 744.000 | 91.230 | 0.000 | 0.000 | 91.230 |
September | 720.000 | 65.775 | 0.000 | 0.000 | 65.775 |
October | 662.077 | 40.096 | 25.375 | 0.588 | 40.684 |
November | 367.109 | 9.179 | 141.321 | 4.474 | 13.653 |
December | 40.875 | 0.432 | 524.804 | 29.369 | 29.801 |
Annual Sum or Average | 5885.143 | 509.591 | 1676.827 | 82.858 | 592.449 |
Minimum of Months | 40.875 | 0.432 | 0.000 | 0.000 | 13.653 |
Maximum of Months | 744.000 | 102.767 | 524.804 | 29.369 | 102.767 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 267.599 | 12.709 | 298.250 | 18.142 | 30.851 |
February | 294.770 | 19.080 | 206.878 | 12.031 | 31.111 |
March | 376.853 | 24.635 | 148.893 | 8.022 | 32.658 |
April | 549.888 | 44.880 | 46.667 | 2.338 | 47.218 |
May | 703.208 | 60.871 | 0.000 | 0.000 | 60.871 |
June | 720.000 | 90.959 | 0.000 | 0.000 | 90.959 |
July | 744.000 | 107.460 | 0.000 | 0.000 | 107.460 |
August | 744.000 | 98.821 | 0.000 | 0.000 | 98.821 |
September | 720.000 | 77.851 | 0.000 | 0.000 | 77.851 |
October | 671.008 | 53.910 | 22.775 | 0.455 | 54.366 |
November | 426.191 | 25.847 | 105.292 | 3.448 | 29.296 |
December | 237.419 | 11.032 | 340.857 | 23.214 | 34.247 |
Annual Sum or Average | 6454.934 | 628.056 | 1169.611 | 67.652 | 695.708 |
Minimum of Months | 237.419 | 11.032 | 0.000 | 0.000 | 29.296 |
Maximum of Months | 744.000 | 107.460 | 340.857 | 23.214 | 107.460 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 310.323 | 10.648 | 210.187 | 6.661 | 17.309 |
February | 348.706 | 15.673 | 146.625 | 4.676 | 20.349 |
March | 432.346 | 18.480 | 97.625 | 3.167 | 21.647 |
April | 606.956 | 33.236 | 26.000 | 0.887 | 34.123 |
May | 725.423 | 44.171 | 0.000 | 0.000 | 44.171 |
June | 720.000 | 65.077 | 0.000 | 0.000 | 65.077 |
July | 744.000 | 78.282 | 0.000 | 0.000 | 78.282 |
August | 744.000 | 72.618 | 0.000 | 0.000 | 72.618 |
September | 720.000 | 59.019 | 0.000 | 0.000 | 59.019 |
October | 694.516 | 44.177 | 1.875 | 0.012 | 44.189 |
November | 491.120 | 22.698 | 41.250 | 0.602 | 23.300 |
December | 286.065 | 9.442 | 263.958 | 9.246 | 18.687 |
Annual Sum or Average | 6823.454 | 473.522 | 787.521 | 25.250 | 498.772 |
Minimum of Months | 286.065 | 9.442 | 0.000 | 0.000 | 17.309 |
Maximum of Months | 744.000 | 78.282 | 263.958 | 9.246 | 78.282 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 263.871 | 9.164 | 293.308 | 14.108 | 23.272 |
February | 311.134 | 16.664 | 195.375 | 9.235 | 25.899 |
March | 417.376 | 21.466 | 134.667 | 6.248 | 27.715 |
April | 587.730 | 42.006 | 43.500 | 1.617 | 43.623 |
May | 714.265 | 56.756 | 0.000 | 0.000 | 56.756 |
June | 720.000 | 84.569 | 0.000 | 0.000 | 84.569 |
July | 744.000 | 99.842 | 0.000 | 0.000 | 99.842 |
August | 744.000 | 91.612 | 0.000 | 0.000 | 91.612 |
September | 720.000 | 72.161 | 0.000 | 0.000 | 72.161 |
October | 680.954 | 50.816 | 17.750 | 0.311 | 51.127 |
November | 456.880 | 23.210 | 91.375 | 2.499 | 25.709 |
December | 233.232 | 7.936 | 326.500 | 18.155 | 26.091 |
Annual Sum or Average | 6593.443 | 576.202 | 1102.475 | 52.173 | 628.376 |
Minimum of Months | 233.232 | 7.936 | 0.000 | 0.000 | 23.272 |
Maximum of Months | 744.000 | 99.842 | 326.500 | 18.155 | 99.842 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 143.083 | 3.387 | 400.633 | 25.083 | 28.471 |
February | 221.259 | 10.616 | 272.225 | 15.808 | 26.423 |
March | 326.698 | 17.298 | 182.284 | 9.374 | 26.672 |
April | 537.671 | 40.437 | 61.042 | 2.783 | 43.220 |
May | 702.818 | 60.023 | 0.000 | 0.000 | 60.023 |
June | 720.000 | 91.319 | 0.000 | 0.000 | 91.319 |
July | 744.000 | 107.085 | 0.000 | 0.000 | 107.085 |
August | 744.000 | 96.209 | 0.000 | 0.000 | 96.209 |
September | 720.000 | 70.861 | 0.000 | 0.000 | 70.861 |
October | 651.965 | 43.107 | 34.250 | 0.772 | 43.879 |
November | 342.935 | 13.138 | 164.268 | 5.398 | 18.536 |
December | 101.629 | 2.174 | 462.688 | 32.328 | 34.502 |
Annual Sum or Average | 5956.059 | 555.654 | 1577.389 | 91.545 | 647.199 |
Minimum of Months | 101.629 | 2.174 | 0.000 | 0.000 | 18.536 |
Maximum of Months | 744.000 | 107.085 | 462.688 | 32.328 | 107.085 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 112.017 | 1.636 | 340.246 | 10.986 | 12.622 |
February | 243.724 | 7.352 | 216.812 | 6.855 | 14.207 |
March | 369.354 | 11.351 | 116.746 | 3.668 | 15.019 |
April | 595.380 | 29.233 | 31.792 | 1.019 | 30.252 |
May | 726.100 | 43.768 | 0.000 | 0.000 | 43.768 |
June | 720.000 | 66.035 | 0.000 | 0.000 | 66.035 |
July | 744.000 | 78.509 | 0.000 | 0.000 | 78.509 |
August | 744.000 | 70.547 | 0.000 | 0.000 | 70.547 |
September | 720.000 | 52.437 | 0.000 | 0.000 | 52.437 |
October | 677.454 | 33.670 | 5.308 | 0.036 | 33.706 |
November | 390.273 | 9.743 | 73.634 | 1.226 | 10.969 |
December | 70.877 | 0.881 | 426.092 | 15.219 | 16.100 |
Annual Sum or Average | 6113.178 | 405.162 | 1210.630 | 39.009 | 444.170 |
Minimum of Months | 70.877 | 0.881 | 0.000 | 0.000 | 10.969 |
Maximum of Months | 744.000 | 78.509 | 426.092 | 15.219 | 78.509 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 81.042 | 1.387 | 408.295 | 18.141 | 19.528 |
February | 235.556 | 9.071 | 247.813 | 10.859 | 19.930 |
March | 387.344 | 15.043 | 147.851 | 6.456 | 21.498 |
April | 582.166 | 39.405 | 46.750 | 1.649 | 41.053 |
May | 714.848 | 57.963 | 0.000 | 0.000 | 57.963 |
June | 720.000 | 87.611 | 0.000 | 0.000 | 87.611 |
July | 744.000 | 102.204 | 0.000 | 0.000 | 102.204 |
August | 744.000 | 91.763 | 0.000 | 0.000 | 91.763 |
September | 720.000 | 67.811 | 0.000 | 0.000 | 67.811 |
October | 673.764 | 42.081 | 19.125 | 0.338 | 42.418 |
November | 395.200 | 10.912 | 105.125 | 2.812 | 13.724 |
December | 55.804 | 0.660 | 479.021 | 23.697 | 24.357 |
Annual Sum or Average | 6053.724 | 525.909 | 1453.979 | 63.951 | 589.860 |
Minimum of Months | 55.804 | 0.660 | 0.000 | 0.000 | 13.724 |
Maximum of Months | 744.000 | 102.204 | 479.021 | 23.697 | 102.204 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 216.591 | 11.196 | 368.863 | 31.188 | 42.384 |
February | 259.569 | 19.299 | 264.458 | 20.618 | 39.917 |
March | 337.815 | 26.099 | 217.190 | 14.057 | 40.156 |
April | 514.817 | 50.732 | 74.646 | 4.419 | 55.151 |
May | 683.360 | 70.544 | 9.219 | 0.095 | 70.638 |
June | 720.000 | 108.560 | 0.000 | 0.000 | 108.560 |
July | 744.000 | 129.121 | 0.000 | 0.000 | 129.121 |
August | 744.000 | 116.456 | 0.000 | 0.000 | 116.456 |
September | 720.000 | 88.915 | 0.000 | 0.000 | 88.915 |
October | 639.052 | 58.344 | 38.250 | 1.477 | 59.821 |
November | 379.547 | 25.352 | 173.625 | 8.204 | 33.557 |
December | 188.923 | 9.313 | 406.208 | 37.968 | 47.281 |
Annual Sum or Average | 6147.673 | 713.929 | 1552.460 | 118.027 | 831.956 |
Minimum of Months | 188.923 | 9.313 | 0.000 | 0.000 | 33.557 |
Maximum of Months | 744.000 | 129.121 | 406.208 | 37.968 | 129.121 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 243.463 | 9.156 | 310.921 | 15.795 | 24.951 |
February | 290.772 | 15.909 | 214.738 | 10.563 | 26.471 |
March | 367.416 | 20.040 | 155.266 | 6.899 | 26.939 |
April | 552.225 | 39.166 | 55.500 | 2.128 | 41.294 |
May | 703.330 | 54.085 | 0.000 | 0.000 | 54.085 |
June | 720.000 | 83.132 | 0.000 | 0.000 | 83.132 |
July | 744.000 | 100.266 | 0.000 | 0.000 | 100.266 |
August | 744.000 | 90.701 | 0.000 | 0.000 | 90.701 |
September | 720.000 | 70.598 | 0.000 | 0.000 | 70.598 |
October | 672.714 | 48.977 | 21.946 | 0.368 | 49.345 |
November | 424.458 | 22.232 | 105.538 | 2.840 | 25.072 |
December | 210.665 | 7.699 | 351.010 | 20.022 | 27.721 |
Annual Sum or Average | 6393.044 | 561.962 | 1214.920 | 58.614 | 620.576 |
Minimum of Months | 210.665 | 7.699 | 0.000 | 0.000 | 24.951 |
Maximum of Months | 744.000 | 100.266 | 351.010 | 20.022 | 100.266 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 210.792 | 8.302 | 352.540 | 24.018 | 32.320 |
February | 276.411 | 17.429 | 242.583 | 15.485 | 32.915 |
March | 374.206 | 23.441 | 180.385 | 10.277 | 33.718 |
April | 556.930 | 49.188 | 59.500 | 2.954 | 52.142 |
May | 699.759 | 68.418 | 6.750 | 0.053 | 68.472 |
June | 720.000 | 105.131 | 0.000 | 0.000 | 105.131 |
July | 744.000 | 124.390 | 0.000 | 0.000 | 124.390 |
August | 744.000 | 112.126 | 0.000 | 0.000 | 112.126 |
September | 720.000 | 85.772 | 0.000 | 0.000 | 85.772 |
October | 654.589 | 57.041 | 29.375 | 0.913 | 57.954 |
November | 414.350 | 23.483 | 142.875 | 5.590 | 29.073 |
December | 180.858 | 6.821 | 390.750 | 29.398 | 36.218 |
Annual Sum or Average | 6295.895 | 681.542 | 1404.758 | 88.688 | 770.230 |
Minimum of Months | 180.858 | 6.821 | 0.000 | 0.000 | 29.073 |
Maximum of Months | 744.000 | 124.390 | 390.750 | 29.398 | 124.390 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 133.858 | 4.326 | 442.255 | 37.866 | 42.192 |
February | 211.949 | 13.178 | 305.750 | 23.893 | 37.071 |
March | 312.240 | 21.808 | 234.723 | 14.919 | 36.727 |
April | 510.544 | 48.738 | 77.232 | 4.606 | 53.344 |
May | 684.736 | 70.556 | 9.219 | 0.096 | 70.652 |
June | 720.000 | 109.199 | 0.000 | 0.000 | 109.199 |
July | 744.000 | 129.292 | 0.000 | 0.000 | 129.292 |
August | 744.000 | 115.496 | 0.000 | 0.000 | 115.496 |
September | 720.000 | 85.109 | 0.000 | 0.000 | 85.109 |
October | 622.888 | 50.435 | 45.250 | 1.818 | 52.253 |
November | 320.670 | 15.514 | 217.670 | 10.425 | 25.940 |
December | 98.829 | 2.857 | 493.396 | 46.706 | 49.563 |
Annual Sum or Average | 5823.714 | 666.508 | 1825.494 | 140.330 | 806.838 |
Minimum of Months | 98.829 | 2.857 | 0.000 | 0.000 | 25.940 |
Maximum of Months | 744.000 | 129.292 | 493.396 | 46.706 | 129.292 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 108.830 | 2.228 | 412.333 | 21.369 | 23.597 |
February | 220.629 | 9.659 | 265.500 | 13.204 | 22.863 |
March | 332.706 | 15.762 | 172.598 | 7.497 | 23.259 |
April | 546.403 | 37.482 | 58.600 | 2.266 | 39.748 |
May | 703.962 | 54.525 | 0.000 | 0.000 | 54.525 |
June | 720.000 | 84.354 | 0.000 | 0.000 | 84.354 |
July | 744.000 | 101.035 | 0.000 | 0.000 | 101.035 |
August | 744.000 | 90.306 | 0.000 | 0.000 | 90.306 |
September | 720.000 | 67.227 | 0.000 | 0.000 | 67.227 |
October | 657.589 | 41.156 | 30.530 | 0.554 | 41.711 |
November | 350.217 | 11.807 | 149.905 | 4.136 | 15.943 |
December | 68.827 | 1.235 | 478.037 | 27.424 | 28.659 |
Annual Sum or Average | 5917.163 | 516.778 | 1567.503 | 76.450 | 593.228 |
Minimum of Months | 68.827 | 1.235 | 0.000 | 0.000 | 15.943 |
Maximum of Months | 744.000 | 101.035 | 478.037 | 27.424 | 101.035 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 86.824 | 2.020 | 454.667 | 29.361 | 31.381 |
February | 220.513 | 11.379 | 287.033 | 17.698 | 29.077 |
March | 353.091 | 19.167 | 190.030 | 10.644 | 29.811 |
April | 553.172 | 47.493 | 60.000 | 3.007 | 50.500 |
May | 700.079 | 68.701 | 6.750 | 0.053 | 68.754 |
June | 720.000 | 106.081 | 0.000 | 0.000 | 106.081 |
July | 744.000 | 124.903 | 0.000 | 0.000 | 124.903 |
August | 744.000 | 111.611 | 0.000 | 0.000 | 111.611 |
September | 720.000 | 82.496 | 0.000 | 0.000 | 82.496 |
October | 646.307 | 49.456 | 32.500 | 0.985 | 50.441 |
November | 355.794 | 12.968 | 166.143 | 6.294 | 19.262 |
December | 58.250 | 1.087 | 520.446 | 36.630 | 37.717 |
Annual Sum or Average | 5902.031 | 637.362 | 1717.569 | 104.671 | 742.034 |
Minimum of Months | 58.250 | 1.087 | 0.000 | 0.000 | 19.262 |
Maximum of Months | 744.000 | 124.903 | 520.446 | 36.630 | 124.903 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 63.649 | 63.649 |
February | 0.000 | 0.000 | 636.442 | 39.939 | 39.939 |
March | 0.000 | 0.000 | 474.412 | 16.460 | 16.460 |
April | 26.536 | 0.154 | 30.625 | 0.560 | 0.714 |
May | 742.625 | 47.886 | 0.000 | 0.000 | 47.886 |
June | 720.000 | 98.537 | 0.000 | 0.000 | 98.537 |
July | 744.000 | 114.192 | 0.000 | 0.000 | 114.192 |
August | 744.000 | 104.689 | 0.000 | 0.000 | 104.689 |
September | 720.000 | 82.702 | 0.000 | 0.000 | 82.702 |
October | 744.000 | 46.405 | 0.000 | 0.000 | 46.405 |
November | 0.500 | 0.012 | 204.724 | 3.711 | 3.723 |
December | 0.000 | 0.000 | 744.000 | 62.684 | 62.684 |
Annual Sum or Average | 4441.661 | 494.577 | 2834.204 | 187.003 | 681.581 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.714 |
Maximum of Months | 744.000 | 114.192 | 744.000 | 63.649 | 114.192 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 535.24 | 0.00 |
February | 0.00 | 402.11 | 0.00 |
March | 0.00 | 235.34 | 0.00 |
April | 0.00 | 71.87 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 3.29 | 0.00 |
November | 0.00 | 78.18 | 0.00 |
December | 0.00 | 695.84 | 0.00 |
Annual Sum or Average | 0.00 | 168.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 695.84 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 995.78 | 0.00 |
February | 0.00 | 718.38 | 0.00 |
March | 0.00 | 440.26 | 0.00 |
April | 0.00 | 127.78 | 0.00 |
May | 0.00 | 0.26 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 29.70 | 0.00 |
November | 0.00 | 225.17 | 0.00 |
December | 0.00 | 1229.13 | 0.00 |
Annual Sum or Average | 0.00 | 313.02 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1229.13 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1330.94 | 0.00 |
February | 0.00 | 938.91 | 0.00 |
March | 0.00 | 524.97 | 0.00 |
April | 0.00 | 166.74 | 0.00 |
May | 0.00 | 0.36 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 47.81 | 0.00 |
November | 0.00 | 340.27 | 0.00 |
December | 0.00 | 1662.34 | 0.00 |
Annual Sum or Average | 0.00 | 416.60 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1662.34 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 823.33 | 0.00 |
February | 0.00 | 572.58 | 0.00 |
March | 0.00 | 285.33 | 0.00 |
April | 0.00 | 87.70 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 7.95 | 0.00 |
November | 0.00 | 128.96 | 0.00 |
December | 0.00 | 1078.34 | 0.00 |
Annual Sum or Average | 0.00 | 248.15 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1078.34 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1262.93 | 0.00 |
February | 0.00 | 849.94 | 0.00 |
March | 0.00 | 467.95 | 0.00 |
April | 0.00 | 132.53 | 0.00 |
May | 0.00 | 0.25 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 31.88 | 0.00 |
November | 0.00 | 250.78 | 0.00 |
December | 0.00 | 1593.19 | 0.00 |
Annual Sum or Average | 0.00 | 381.75 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1593.19 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 687.21 | 0.00 |
February | 0.00 | 504.55 | 0.00 |
March | 0.00 | 303.89 | 0.00 |
April | 0.00 | 91.53 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 17.25 | 0.00 |
November | 0.00 | 134.98 | 0.00 |
December | 0.00 | 879.35 | 0.00 |
Annual Sum or Average | 0.00 | 217.65 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 879.35 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 313.20 | 0.00 |
February | 0.00 | 243.44 | 0.00 |
March | 0.00 | 148.92 | 0.00 |
April | 0.00 | 43.10 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.55 | 0.00 |
November | 0.00 | 29.25 | 0.00 |
December | 0.00 | 434.76 | 0.00 |
Annual Sum or Average | 0.00 | 100.84 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 434.76 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 710.27 | 0.00 |
February | 0.00 | 514.75 | 0.00 |
March | 0.00 | 314.59 | 0.00 |
April | 0.00 | 84.14 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 15.66 | 0.00 |
November | 0.00 | 130.02 | 0.00 |
December | 0.00 | 914.06 | 0.00 |
Annual Sum or Average | 0.00 | 223.09 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 914.06 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1010.34 | 0.00 |
February | 0.00 | 704.94 | 0.00 |
March | 0.00 | 377.57 | 0.00 |
April | 0.00 | 115.84 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 31.08 | 0.00 |
November | 0.00 | 224.66 | 0.00 |
December | 0.00 | 1302.16 | 0.00 |
Annual Sum or Average | 0.00 | 313.18 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1302.16 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 522.97 | 0.00 |
February | 0.00 | 361.28 | 0.00 |
March | 0.00 | 174.59 | 0.00 |
April | 0.00 | 50.11 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 1.72 | 0.00 |
November | 0.00 | 60.30 | 0.00 |
December | 0.00 | 724.50 | 0.00 |
Annual Sum or Average | 0.00 | 157.71 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 724.50 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 942.93 | 0.00 |
February | 0.00 | 624.89 | 0.00 |
March | 0.00 | 335.55 | 0.00 |
April | 0.00 | 88.54 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 17.54 | 0.00 |
November | 0.00 | 151.01 | 0.00 |
December | 0.00 | 1231.71 | 0.00 |
Annual Sum or Average | 0.00 | 282.31 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1231.71 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1313.88 | 0.00 |
February | 0.00 | 961.66 | 0.00 |
March | 0.00 | 592.19 | 0.00 |
April | 0.00 | 192.37 | 0.00 |
May | 0.00 | 3.98 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 62.24 | 0.00 |
November | 0.00 | 357.15 | 0.00 |
December | 0.00 | 1599.52 | 0.00 |
Annual Sum or Average | 0.00 | 422.30 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1599.52 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 778.91 | 0.00 |
February | 0.00 | 576.69 | 0.00 |
March | 0.00 | 340.22 | 0.00 |
April | 0.00 | 108.43 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 18.14 | 0.00 |
November | 0.00 | 144.72 | 0.00 |
December | 0.00 | 987.38 | 0.00 |
Annual Sum or Average | 0.00 | 245.50 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 987.38 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1250.98 | 0.00 |
February | 0.00 | 892.98 | 0.00 |
March | 0.00 | 535.28 | 0.00 |
April | 0.00 | 159.00 | 0.00 |
May | 0.00 | 2.78 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 47.57 | 0.00 |
November | 0.00 | 300.86 | 0.00 |
December | 0.00 | 1531.21 | 0.00 |
Annual Sum or Average | 0.00 | 392.33 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1531.21 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1604.98 | 0.00 |
February | 0.00 | 1121.25 | 0.00 |
March | 0.00 | 632.36 | 0.00 |
April | 0.00 | 201.75 | 0.00 |
May | 0.00 | 4.05 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 77.05 | 0.00 |
November | 0.00 | 456.61 | 0.00 |
December | 0.00 | 1979.67 | 0.00 |
Annual Sum or Average | 0.00 | 505.17 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1979.67 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1053.35 | 0.00 |
February | 0.00 | 720.60 | 0.00 |
March | 0.00 | 369.56 | 0.00 |
April | 0.00 | 115.42 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 27.33 | 0.00 |
November | 0.00 | 210.65 | 0.00 |
December | 0.00 | 1351.82 | 0.00 |
Annual Sum or Average | 0.00 | 320.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1351.82 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1532.03 | 0.00 |
February | 0.00 | 1022.41 | 0.00 |
March | 0.00 | 555.38 | 0.00 |
April | 0.00 | 162.14 | 0.00 |
May | 0.00 | 2.75 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 51.38 | 0.00 |
November | 0.00 | 339.37 | 0.00 |
December | 0.00 | 1911.33 | 0.00 |
Annual Sum or Average | 0.00 | 463.87 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1911.33 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3447.49 | 0.00 |
February | 0.00 | 2395.00 | 0.00 |
March | 0.00 | 891.55 | 0.00 |
April | 0.00 | 31.32 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 207.72 | 0.00 |
December | 0.00 | 3395.23 | 0.00 |
Annual Sum or Average | 0.00 | 860.26 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 3447.49 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.69 |
February | 0.00 | 0.00 | 0.80 |
March | 0.00 | 0.00 | 0.86 |
April | 0.00 | 0.00 | 1.07 |
May | 0.00 | 0.00 | 1.21 |
June | 0.00 | 0.00 | 1.45 |
July | 0.00 | 0.00 | 1.59 |
August | 0.00 | 0.00 | 1.53 |
September | 0.00 | 0.00 | 1.37 |
October | 0.00 | 0.00 | 1.17 |
November | 0.00 | 0.00 | 0.91 |
December | 0.00 | 0.00 | 0.66 |
Annual Sum or Average | 0.00 | 0.00 | 1.11 |
Minimum of Months | 0.00 | 0.00 | 0.66 |
Maximum of Months | 0.00 | 0.00 | 1.59 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.50 |
July | 0.00 | 0.00 | 0.62 |
August | 0.00 | 0.00 | 0.57 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.33 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.62 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.00 | 0.80 |
August | 0.00 | 0.00 | 0.73 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.39 |
November | 0.00 | 0.00 | 0.18 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.80 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.00 | 0.78 |
August | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.78 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.20 |
May | 0.00 | 0.00 | 0.31 |
June | 0.00 | 0.00 | 0.51 |
July | 0.00 | 0.00 | 0.61 |
August | 0.00 | 0.00 | 0.54 |
September | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.00 | 0.24 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.61 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.67 |
July | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.79 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.09 |
February | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.00 | 0.18 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.70 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.39 |
November | 0.00 | 0.00 | 0.20 |
December | 0.00 | 0.00 | 0.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.08 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.55 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.18 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.17 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.00 | 0.77 |
August | 0.00 | 0.00 | 0.71 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.40 |
November | 0.00 | 0.00 | 0.19 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.38 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.77 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.65 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.00 | 0.52 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.22 |
May | 0.00 | 0.00 | 0.32 |
June | 0.00 | 0.00 | 0.49 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.52 |
September | 0.00 | 0.00 | 0.40 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.25 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.00 | 0.66 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.68 |
September | 0.00 | 0.00 | 0.51 |
October | 0.00 | 0.00 | 0.31 |
November | 0.00 | 0.00 | 0.08 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.08 |
February | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.00 | 0.19 |
April | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.00 | 0.90 |
August | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.00 | 0.64 |
October | 0.00 | 0.00 | 0.41 |
November | 0.00 | 0.00 | 0.19 |
December | 0.00 | 0.00 | 0.07 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.07 |
Maximum of Months | 0.00 | 0.00 | 0.90 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.00 | 0.53 |
October | 0.00 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.73 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.14 |
March | 0.00 | 0.00 | 0.17 |
April | 0.00 | 0.00 | 0.36 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.00 | 0.91 |
August | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.00 | 0.64 |
October | 0.00 | 0.00 | 0.42 |
November | 0.00 | 0.00 | 0.18 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.42 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.91 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.03 |
February | 0.00 | 0.00 | 0.10 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.77 |
July | 0.00 | 0.00 | 0.90 |
August | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.11 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.90 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.27 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.00 | 0.50 |
October | 0.00 | 0.00 | 0.29 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.73 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.35 |
May | 0.00 | 0.00 | 0.49 |
June | 0.00 | 0.00 | 0.78 |
July | 0.00 | 0.00 | 0.91 |
August | 0.00 | 0.00 | 0.81 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.10 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.91 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.76 |
July | 0.00 | 0.00 | 0.85 |
August | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.00 | 0.64 |
October | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.85 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:32:39
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.50 | 1056.86 |
February | 0.00 | 0.00 | 1390.14 | 934.84 |
March | 0.00 | 0.00 | 1283.23 | 955.40 |
April | 0.00 | 0.00 | 1125.44 | 810.89 |
May | 0.00 | 0.00 | 950.12 | 707.39 |
June | 0.00 | 0.00 | 816.89 | 588.58 |
July | 0.00 | 0.00 | 754.99 | 562.11 |
August | 0.00 | 0.00 | 783.27 | 583.17 |
September | 0.00 | 0.00 | 896.17 | 645.70 |
October | 0.00 | 0.00 | 1058.69 | 788.23 |
November | 0.00 | 0.00 | 1227.54 | 884.46 |
December | 0.00 | 0.00 | 1362.41 | 1014.35 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 754.99 | 562.11 |
Maximum of Months | 0.00 | 0.00 | 1419.50 | 1056.86 |