Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32

Tabular Output Report in Format: HTML

Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+gasfurnace+heatedbsmt+IECC_2009

Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780

Simulation Timestamp: 2019-02-14 08:32:39


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1015481.38 26.03 34.54
Net Site Energy 1015481.38 26.03 34.54
Total Source Energy 2290057.75 58.71 77.88
Net Source Energy 2290057.75 58.71 77.88


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 66095.03 0.00 0.00 0.00 0.00
Cooling 202074.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 263405.37 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 45314.98 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 214469.36 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 570943.80 444537.59 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 66095.03 0.00 0.00 0.00 0.00
Cooling General 202074.18 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 45314.98 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 214469.36 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.05 0.00 0.00 0.00 0.00 0.00
HVAC 8.41 9.54 0.00 0.00 0.00 14.27
Other 8.96 5.58 0.00 0.00 0.00 0.00
Total 19.42 15.12 0.00 0.00 0.00 14.27


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 6.34 7.19 0.00 0.00 0.00 10.76
Other 6.75 4.20 0.00 0.00 0.00 0.00
Total 14.64 11.40 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 570943.799 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 570943.799 100.00
     
Total On-Site and Utility Electric Sources 570943.799 100.00
Total Electricity End Uses 570943.799 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 164.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 107.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
RunPeriod ANNUAL
Weather File Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Latitude [deg] 33.45
Longitude [deg] -112.0
Elevation [ft] 1105.70
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.4163 1083.48 2.4729
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.5522 816.79 3.2803
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 16-JUL-19:15 10-FEB-07:15 - - - 01-JAN-08:15
Heating 0.00 112.73 0.00 0.00 0.00 0.00
Cooling 78.76 0.00 0.00 0.00 0.00 0.00
Interior Lighting 16.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.53 0.00 0.00 0.00 0.00 0.00
Interior Equipment 43.33 16.40 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 13.88 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 147.81 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 154.75 276.94 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 112.73 0.00 0.00 0.00 0.00
Cooling General 78.76 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 16.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.63 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.37 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.82 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.62 6.47 0.00 0.00 0.00 0.00
  gas_range 0.00 7.84 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 23.39 2.10 0.00 0.00 0.00 0.00
  IECC_adj 9.69 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 13.88 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 147.81 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 71647.01 0.00 0.00 0.00
Cooling 639968.94 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 834204.80 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 143512.54 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 232484.79 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1808179.01 481878.74 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 2.44 0.00 0.00 0.00
Cooling 21.76 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 28.37 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.88 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.91 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 61.49 16.39 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 2.44 0.00 0.00 0.00
Cooling 21.76 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 28.37 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.88 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.91 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 61.49 16.39 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 38.66 0.00 38.66 Wetbulb [F] 334.66 100.00
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 110.12 21.60 69.98 Wetbulb [F] 807.13 260.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.651 0.260 0.882              
North Total or Average           531.68 0.651 0.260 0.882              
Non-North Total or Average           1595.05 0.651 0.260 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   28946.61 22925.55 6021.06 0.79 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11811.47 9108.48 2702.99 0.77 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15519.63 11800.06 3719.57 0.76 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   17991.00 14066.23 3924.76 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11578.51 8956.14 2622.37 0.77 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14993.93 11378.72 3615.22 0.76 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   17524.80 13689.73 3835.08 0.78 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11158.13 8600.48 2557.65 0.77 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14775.33 11205.80 3569.52 0.76 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   17226.36 13479.29 3747.07 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10935.97 8478.86 2457.11 0.78 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13647.73 10566.66 3081.07 0.77 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20764.88 16321.04 4443.84 0.79 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14399.28 11219.09 3180.19 0.78 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17228.09 13413.59 3814.51 0.78 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20743.86 16303.95 4439.91 0.79 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14303.24 11183.69 3119.55 0.78 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17110.25 13350.38 3759.87 0.78 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   14915.21 11387.09 3528.12 0.76 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.3 3.27 11.16 11.82 11.34
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.31 11.30 11.97 11.55
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.2 3.33 11.37 12.04 11.66
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.4 3.29 11.23 11.89 11.44
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.31 11.28 11.95 11.53
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.2 3.33 11.38 12.05 11.68
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.4 3.29 11.23 11.89 11.45
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.9 3.31 11.30 11.97 11.55
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.2 3.33 11.38 12.06 11.68
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.4 3.29 11.22 11.89 11.43
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.9 3.30 11.27 11.94 11.51
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.1 3.30 11.28 11.94 11.52
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.7 3.28 11.20 11.86 11.40
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.1 3.30 11.24 11.91 11.47
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.4 3.30 11.25 11.91 11.47
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.7 3.28 11.20 11.86 11.40
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.29 11.23 11.89 11.44
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.4 3.29 11.24 11.90 11.46
DX COOLING COIL_UNITHEATEDBSMT   1.2 3.33 11.35 12.02 11.63
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   3900.50 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   5709.43 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   7634.02 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   7650.24 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   5836.03 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   7636.15 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   6655.50 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   5104.57 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   6973.62 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   6982.83 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   5132.27 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   6971.51 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   8891.41 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   7078.18 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   8930.50 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   8936.10 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   7083.67 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   8927.99 0.80
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel   7689.98 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1066.14 402.14 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 409.92 154.62 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 521.47 196.70 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 644.01 242.92 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 404.62 152.62 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 501.60 189.20 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 626.10 236.16 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 386.82 145.91 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 493.57 186.17 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 617.75 233.01 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 384.18 144.91 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 477.95 180.28 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 752.08 283.68 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 511.46 192.92 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 610.97 230.45 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 751.26 283.37 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 512.08 193.15 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 609.70 229.97 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 505.92 190.83 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 24064.66 24064.66 20.04 1066.142 1066.142 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00801 106.02 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9252.54 9252.54 7.71 409.919 409.919 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00806 104.13 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11770.68 11770.68 9.80 521.472 521.472 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00796 110.12 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14536.37 14536.37 12.11 644.009 644.009 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00802 105.48 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9132.93 9132.93 7.61 404.621 404.621 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00808 103.32 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11322.13 11322.13 9.43 501.601 501.601 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00796 110.12 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14131.95 14131.95 11.77 626.095 626.095 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00805 105.48 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8731.08 8731.08 7.27 386.819 386.819 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00813 103.32 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11140.75 11140.75 9.28 493.572 493.572 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00800 110.12 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13943.54 13943.54 11.61 617.749 617.749 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00806 104.94 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8671.49 8671.49 7.22 384.180 384.180 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00814 101.70 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10787.99 10787.99 8.99 477.946 477.946 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00807 104.94 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 13762.00 13762.00 11.46 609.702 609.702 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00802 105.48 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 13790.62 13790.62 11.49 610.969 610.969 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00801 106.02 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 16975.77 16975.77 14.14 752.082 752.082 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00802 105.48 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11558.34 11558.34 9.63 512.075 512.075 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00807 103.32 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11544.56 11544.56 9.62 511.464 511.464 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00805 104.13 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 16957.28 16957.28 14.12 751.263 751.263 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00802 105.48 0.00720 44.995 0.00
HEATEDBSMT 11419.39 11419.39 1.47 505.916 505.916 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 74.98 74.98 0.00800 108.82 0.00720 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4210.77 4210.77 3.51 79.771 79.771 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00682 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6163.83 6163.83 5.13 116.769 116.769 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00698 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6180.29 6180.29 5.15 117.081 117.081 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00698 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4339.24 4339.24 3.61 82.205 82.205 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00683 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6166.00 6166.00 5.14 116.810 116.810 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00698 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5170.78 5170.78 4.31 97.959 97.959 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00715 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3596.90 3596.90 3.00 68.143 68.143 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00705 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5493.60 5493.60 4.58 104.075 104.075 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00718 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5502.96 5502.96 4.58 104.252 104.252 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00718 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3625.00 3625.00 3.02 68.676 68.676 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00705 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5491.47 5491.47 4.57 104.035 104.035 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00718 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7476.94 7476.94 6.23 141.644 141.644 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7479.48 7479.48 6.23 141.692 141.692 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7439.82 7439.82 6.20 140.941 140.941 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5605.33 5605.33 4.67 106.189 106.189 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00698 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.77 5599.77 4.66 106.084 106.084 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00698 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7485.17 7485.17 6.23 141.800 141.800 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.99 0.00709 38.66 0.00513 44.995 0.00
HEATEDBSMT 6220.39 6220.39 0.80 117.852 117.852 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 06:30:00 72.00 72.00 0.00800 38.66 0.00513 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14 1066.14 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 409.92 409.92 79.77 79.77
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 521.47 521.47 116.77 116.77
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 644.01 644.01 117.08 117.08
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 404.62 404.62 82.20 82.20
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 501.60 501.60 116.81 116.81
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 626.10 626.10 97.96 97.96
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 386.82 386.82 68.14 68.14
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 493.57 493.57 104.07 104.07
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 617.75 617.75 104.25 104.25
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 384.18 384.18 68.68 68.68
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 477.95 477.95 104.03 104.03
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 752.08 752.08 140.94 140.94
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 511.46 511.46 106.08 106.08
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 610.97 610.97 141.69 141.69
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 751.26 751.26 141.80 141.80
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 512.08 512.08 106.19 106.19
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 609.70 609.70 141.64 141.64
CENTRAL SYSTEM_UNITHEATEDBSMT 505.92 505.92 117.85 117.85


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3216.75 3133.75 2.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2721.25 2976.00 37.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3413.50 2990.50 41.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3079.50 3756.50 55.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2348.75 3878.25 40.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3054.00 3644.25 42.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3688.50 2926.00 26.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2993.75 2671.00 12.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3660.00 2773.50 16.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3287.25 3534.75 28.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2605.50 3550.25 17.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3297.00 3413.75 24.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3614.25 3443.50 52.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 3863.50 3006.50 47.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 3778.50 3226.00 82.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3036.50 3563.50 35.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3281.00 3026.00 33.25
LIVING_UNIT1_BACKROW_TOPFLOOR 3540.75 3597.25 91.50
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4283.25 4225.75 107.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 110.25 0.00 110.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 52.75 0.00 52.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 10.25 0.00 10.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 87.25 0.00 87.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 57.25 0.00 57.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 17.00 0.00 17.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 71.25 0.00 71.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 38.25 0.00 38.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 4.25 0.00 4.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 78.25 0.00 78.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 47.50 0.00 47.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 41.75 0.00 41.75
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 89.00 0.00 89.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 77.25 0.00 77.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 106.50 0.00 106.50
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 86.50 0.00 86.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 77.75 0.00 77.75
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 109.50 0.00 109.50
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 164.00 0.00 164.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.206 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.179 0.000 0.265
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.203 0.000 0.265
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.202 0.000 0.265
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.178 0.000 0.265
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.203 0.000 0.265
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.065 0.000 0.265
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.065 0.000 0.265
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.203 0.000 0.265
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.203 0.000 0.265
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.203 0.000 0.265
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.178 0.000 0.265
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.179 0.000 0.265
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.202 0.000 0.265
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1900
Defaulted Fields 509
Fields with Defaults 4982
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
Electricity:Building 91754.37 7056.43 02-JAN-03:15 17558.18 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 77145.04 6525.11 02-JAN-04:15 12799.44 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
Fans:Electricity 13271.66 108.14 27-NOV-00:45 4069.00 16-JUL-17:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
ElectricityPurchased:Plant 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
Cogeneration:ElectricityPurchased 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
ElectricityNet:Plant 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
Cogeneration:ElectricityNet 167215.59 8174.84 11-APR-04:00 45321.12 16-JUL-19:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 72454.29 509.24 27-NOV-01:00 27560.55 16-JUL-18:00
General:Fans:Electricity 13271.66 108.14 27-NOV-00:45 4069.00 16-JUL-17:00
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 59182.63 54.16 31-JAN-06:45 23491.54 16-JUL-18:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 4445.38 2644.47 06-APR-03:15 276745.45 10-FEB-07:15
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 2144.69 0.00 01-JAN-00:15 148256.57 22-JAN-08:45
WaterSystems:Gas 2144.69 0.00 01-JAN-00:15 148256.57 22-JAN-08:45
Water Heater:WaterSystems:Gas 2144.69 0.00 01-JAN-00:15 148256.57 22-JAN-08:45
Gas:HVAC 660.95 0.00 23-FEB-15:15 117475.43 31-JAN-07:15
Heating:Gas 660.95 0.00 23-FEB-15:15 117475.43 31-JAN-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 21-FEB-02:30 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
PlantLoopHeatingDemand:Plant 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
WaterSystems:PlantLoopHeatingDemand 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1654026.86 15217.67 05-APR-02:30 509455.93 17-JUN-19:00
EnergyTransfer:Building 743715.89 6808.99 27-NOV-01:00 243318.79 02-JUL-18:45
EnergyTransfer:Zone:HEATEDBSMT 39285.69 0.00 23-FEB-15:15 11600.02 16-JUL-19:00
Heating:EnergyTransfer 57928.23 0.00 23-FEB-15:15 103019.84 31-JAN-07:15
Heating:EnergyTransfer:Zone:HEATEDBSMT 8179.71 0.00 23-FEB-15:15 6444.41 31-JAN-07:15
Cooling:EnergyTransfer 685787.66 970.92 31-JAN-06:45 243318.79 02-JUL-18:45
Cooling:EnergyTransfer:Zone:HEATEDBSMT 31105.98 0.00 01-JAN-00:15 11600.02 16-JUL-19:00
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 107758.75 970.92 31-JAN-06:45 23982.85 29-SEP-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 107758.75 970.92 31-JAN-06:45 23982.85 29-SEP-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29495.25 0.00 01-JAN-00:15 9624.73 02-JUL-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1608.88 0.00 01-JAN-00:15 4149.09 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 27886.38 0.00 01-JAN-00:15 9624.73 02-JUL-19:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 38140.95 0.00 01-JAN-09:30 12290.68 16-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2985.30 0.00 01-JAN-09:30 6280.25 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 35155.65 0.00 01-JAN-00:15 12290.68 16-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 35193.35 0.00 01-JAN-14:00 14775.16 04-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4047.71 0.00 01-JAN-14:00 6343.74 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31145.65 0.00 01-JAN-00:15 14775.16 04-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 25581.32 0.00 01-JAN-00:15 9529.35 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2369.49 0.00 01-JAN-00:15 4464.76 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23211.84 0.00 01-JAN-00:15 9529.35 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 34222.47 0.00 01-JAN-11:30 12024.20 16-JUL-20:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3629.48 0.00 01-JAN-11:30 6317.64 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 30592.99 0.00 01-JAN-00:15 12024.20 16-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 37979.41 0.00 01-JAN-00:15 14537.43 29-SEP-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2138.98 0.00 01-JAN-00:15 5006.85 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 35840.43 0.00 01-JAN-00:15 14537.43 29-SEP-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29019.61 0.00 01-JAN-00:15 9111.99 16-JUL-20:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 970.23 0.00 01-JAN-00:15 3289.81 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 28049.37 0.00 01-JAN-00:15 9111.99 16-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 37483.59 0.00 01-JAN-00:15 11740.01 16-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2133.87 0.00 01-JAN-00:15 5390.62 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 35349.72 0.00 01-JAN-00:15 11740.01 16-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 34215.29 0.00 01-JAN-00:15 14120.45 10-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3057.99 0.00 01-JAN-00:15 5515.35 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31157.30 0.00 01-JAN-00:15 14120.45 10-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 24755.95 0.00 01-JAN-00:15 9020.01 16-JUL-21:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1515.76 0.00 01-JAN-00:15 3591.15 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23240.19 0.00 01-JAN-00:15 9020.01 16-JUL-21:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 33382.03 0.00 01-JAN-00:15 11124.55 16-JUL-20:45
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2693.17 0.00 01-JAN-00:15 5433.18 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 30688.85 0.00 01-JAN-00:15 11124.55 16-JUL-20:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 40905.18 0.00 01-JAN-12:30 13968.72 17-JUN-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4423.81 0.00 01-JAN-12:30 7610.34 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 36481.37 0.00 01-JAN-00:15 13968.72 17-JUN-19:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 43202.20 0.00 01-JAN-10:15 14002.71 02-JUL-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3742.16 0.00 01-JAN-10:15 7582.09 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 39460.04 0.00 01-JAN-00:15 14002.71 02-JUL-19:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 44163.63 0.00 01-JAN-00:15 17060.99 27-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4105.02 0.00 01-JAN-00:15 7481.10 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 40058.61 0.00 01-JAN-00:15 17060.99 27-AUG-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 32264.05 0.00 01-JAN-00:15 11776.88 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3066.79 0.00 01-JAN-00:15 5722.67 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 29197.27 0.00 01-JAN-00:15 11776.88 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 34644.71 0.00 01-JAN-00:15 11849.51 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2352.24 0.00 01-JAN-00:15 5496.55 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 32292.47 0.00 01-JAN-00:15 11849.51 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 42022.46 0.00 01-JAN-14:00 17022.79 27-AUG-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4907.66 0.00 01-JAN-14:00 7662.90 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 37114.80 0.00 01-JAN-00:15 17022.79 27-AUG-17:30
EnergyTransfer:Plant 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
WaterSystems:EnergyTransfer 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
Domestic Hot Water:WaterSystems:EnergyTransfer 93474.58 431.68 21-JUL-03:00 31800.96 21-JAN-08:15
EnergyTransfer:HVAC 816836.39 7155.87 27-NOV-01:00 279111.35 10-AUG-18:30
HeatingCoils:EnergyTransfer 52876.02 0.00 23-FEB-15:15 93980.35 31-JAN-07:15
CoolingCoils:EnergyTransfer 763960.37 1023.06 31-JAN-06:45 279111.35 10-AUG-18:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -8973.90 0.000 0.000 2872.262 2771.241 14528.036 15179.564 0.000 5507.759 77190.870 0.000 -4441.45 0.000 -5849.52 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 1608.859 -2322.31 0.000 0.000 2933.317 2771.241 14528.036 6553.352 0.000 5201.710 1072.261 0.000 -1713.52 0.000 -5068.85 -0.16
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 2985.271 -2927.68 0.000 0.000 2948.144 2771.241 14528.036 15097.793 0.000 5518.825 594.895 0.000 -4000.85 0.000 -5287.72 -0.02
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 4047.673 -2593.74 0.000 0.000 2956.832 2771.241 14528.036 11687.018 0.000 5510.363 0.306 0.000 -4401.01 0.000 -5131.71 -822.78
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 2369.464 -1933.03 0.000 0.000 2947.656 2771.241 14528.036 2747.706 0.000 5201.606 0.117 0.000 -1848.06 0.000 -4904.60 -601.15
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 3629.451 -2547.71 0.000 0.000 2959.894 2771.241 14528.036 11344.120 0.000 5518.134 0.103 0.000 -4006.57 0.000 -5148.46 -1002.84
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 2138.957 -2984.71 0.000 0.000 2936.390 2771.241 14528.036 15216.967 0.000 4033.016 2567.380 0.000 -4349.82 0.000 -4001.72 -0.12
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 970.221 -2335.89 0.000 0.000 2919.988 2771.241 14528.036 6538.180 0.000 3723.501 2156.664 0.000 -1762.58 0.000 -3795.82 -0.02
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 2133.853 -2943.84 0.000 0.000 2937.252 2771.241 14528.036 15041.844 0.000 4037.645 2039.836 0.000 -4115.40 0.000 -4024.58 -0.19
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 3057.965 -2594.71 0.000 0.000 2946.104 2771.241 14528.036 11684.972 0.000 4033.249 565.271 0.000 -4519.29 0.000 -3910.21 -0.22
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 1515.745 -1935.40 0.000 0.000 2933.920 2771.241 14528.036 2767.705 0.000 3723.242 581.742 0.000 -1898.73 0.000 -3682.63 -0.27
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 2693.155 -2555.70 0.000 0.000 2949.476 2771.241 14528.036 11318.817 0.000 4035.153 426.110 0.000 -4111.40 0.000 -3921.70 -0.54
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 4423.775 -3038.09 0.000 0.000 2956.807 2771.241 14528.036 11188.702 0.000 5487.015 4405.406 0.000 -4104.08 0.000 -5175.49 -0.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 3742.128 -3286.14 0.000 0.000 2947.967 2771.241 14528.036 14945.348 0.000 5488.361 4391.563 0.000 -4073.32 0.000 -5281.26 -0.07
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 4104.982 -3335.99 0.000 0.000 2948.336 2771.241 14528.036 15130.512 0.000 5484.540 4610.966 0.000 -4277.19 0.000 -5242.80 -0.19
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 3066.758 -2431.49 0.000 0.000 2945.599 2771.241 14528.036 2713.922 0.000 5176.920 4813.472 0.000 -1881.72 0.000 -4936.89 -0.02
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 2352.215 -2689.25 0.000 0.000 2935.886 2771.241 14528.036 6498.811 0.000 5177.555 4812.700 0.000 -1736.06 0.000 -5047.86 -0.24
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 4907.621 -3090.84 0.000 0.000 2954.695 2771.241 14528.036 11525.213 0.000 5485.088 4579.094 0.000 -4473.48 0.000 -5162.68 -0.11
HEATEDBSMT 0.000 0.000 8179.706 -2590.43 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22926.277 0.000 0.000 0.000 0.000 -0.51
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7634.470 52267.085 0.000 0.000 0.000 -59901.55 -0.47
Total Facility 0.000 0.000 57927.797 -57110.84 0.000 0.000 52930.524 49882.340 261504.651 187180.546 0.000 95978.153 190002.119 0.000 -61714.51 0.000 -145476.06 -2430.10


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-SEP-17:06 0.00 0.00 0.00 -2.0 0.00 0.00 263.32 604.65 2756.77 6835.44 0.00 2095.13 11450.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-JUL-19:15 0.00 0.00 0.00 -0.8 0.00 0.00 421.40 902.05 2354.09 786.04 0.00 2802.82 2365.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16-JUL-19:30 0.00 0.00 0.00 -1.0 0.00 0.00 419.80 902.05 2354.09 2142.87 0.00 3173.61 3321.31 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-JUN-17:18 0.00 0.00 0.00 -1.2 0.00 0.00 263.32 604.65 2787.26 7909.93 0.00 2748.76 486.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 02-JUL-19:30 0.00 0.00 0.00 -0.8 0.00 0.00 421.19 902.05 2354.09 722.36 0.00 2552.66 2596.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16-JUL-20:00 0.00 0.00 0.00 -1.0 0.00 0.00 420.03 902.05 2354.09 1837.20 0.00 2837.42 3697.72 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-SEP-17:03 0.00 0.00 0.00 -1.2 0.00 0.00 263.32 604.65 2756.77 6824.28 0.00 1577.86 2532.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16-JUL-20:55 0.00 0.00 0.00 -0.8 0.00 0.00 424.17 902.05 2199.79 642.62 0.00 1576.00 3400.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-JUL-19:38 0.00 0.00 0.00 -1.0 0.00 0.00 424.27 902.05 2354.09 2016.37 0.00 2096.46 4010.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10-JUN-18:03 0.00 0.00 0.00 -1.2 0.00 0.00 427.01 813.96 2698.15 7376.85 0.00 1622.33 1183.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16-JUL-21:38 0.00 0.00 0.00 -0.8 0.00 0.00 475.84 682.17 2064.68 631.33 0.00 1520.33 3679.89 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16-JUL-20:55 0.00 0.00 0.00 -0.9 0.00 0.00 423.00 902.05 2199.79 1532.88 0.00 1709.04 4394.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 17-JUN-19:33 0.00 0.00 0.00 -1.2 0.00 0.00 426.64 902.05 2354.09 1662.21 0.00 2691.45 5966.09 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 02-JUL-19:12 0.00 0.00 0.00 -1.2 0.00 0.00 420.79 902.05 2354.09 1871.13 0.00 3004.46 5469.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 27-AUG-17:33 0.00 0.00 0.00 -1.4 0.00 0.00 256.67 604.65 2787.26 6882.69 0.00 2533.89 4021.88 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 02-JUL-19:36 0.00 0.00 0.00 -1.0 0.00 0.00 423.71 902.05 2354.09 631.56 0.00 2300.89 5279.96 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUL-19:30 0.00 0.00 0.00 -1.0 0.00 0.00 421.24 902.05 2354.09 678.51 0.00 2544.32 4972.69 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 27-AUG-17:33 0.00 0.00 0.00 -1.4 0.00 0.00 257.32 604.65 2787.26 6918.02 0.00 2540.71 3941.08 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 16-JUL-18:56 0.00 0.00 0.00 -1.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11633.80 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 02-JUL-18:45 0.00 0.00 0.00 -20.3 0.00 0.00 7531.33 14651.21 48566.62 44471.91 0.00 50757.87 83285.80 0.00 0.00 0.00 -5798.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 4149.16 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -1112.3 0.00 -3374.0 -2197.3
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 6280.36 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2702.5 0.00 -3593.3 -2518.9
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31-JAN-08:15 0.00 0.00 6343.76 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2350.8 0.00 -3483.9 -2518.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 31-JAN-08:15 0.00 0.00 4464.81 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -968.5 0.00 -3273.2 -2232.1
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 6317.75 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2698.2 0.00 -3593.3 -2560.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 5006.99 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2754.4 0.00 -2563.9 -2223.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 3289.90 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -1130.0 0.00 -2344.3 -2350.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 5390.77 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2747.9 0.00 -2563.9 -2613.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31-JAN-08:15 0.00 0.00 5515.36 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2386.3 0.00 -2495.1 -2643.0
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 31-JAN-08:15 0.00 0.00 3591.18 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -987.6 0.00 -2284.2 -2328.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 5433.32 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2736.8 0.00 -2563.9 -2667.1
LIVING_UNIT3_BACKROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 7610.49 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2714.9 0.00 -3601.1 -3828.8
LIVING_UNIT3_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 7582.24 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2728.6 0.00 -3601.1 -3786.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 7481.26 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -2714.5 0.00 -3601.1 -3700.0
LIVING_UNIT2_BACKROW_TOPFLOOR 31-JAN-08:15 0.00 0.00 5722.70 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -977.5 0.00 -3280.4 -3473.8
LIVING_UNIT2_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 5496.66 0.00 0.00 0.00 464.78 387.60 1682.03 0.00 0.00 0.00 0.00 0.00 -1118.7 0.00 -3381.3 -3531.0
LIVING_UNIT1_BACKROW_TOPFLOOR 31-JAN-08:15 0.00 0.00 7662.90 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2362.2 0.00 -3491.6 -3818.0
HEATEDBSMT 31-JAN-07:15 0.00 0.00 6444.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -6444.4
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-07:15 -1340.9 0.11 103021.91 -0.1 0.00 0.00 8321.72 6976.77 30276.56 0.00 0.00 3017.97 0.00 0.00 -39500.1 0.00 -57599.9 -53174.1



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1066.142 2.00 2.00 1.00 44.9950 1066.142 0.042 1.000 44.9950 0.04
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 409.919 2.00 2.00 1.00 44.9950 409.919 0.110 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 521.472 2.00 2.00 1.00 44.9950 521.472 0.086 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 644.009 2.00 2.00 1.00 44.9950 644.009 0.070 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 404.621 2.00 2.00 1.00 44.9950 404.621 0.111 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 501.601 2.00 2.00 1.00 44.9950 501.601 0.090 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 626.095 2.00 2.00 1.00 44.9950 626.095 0.072 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 386.819 2.00 2.00 1.00 44.9950 386.819 0.116 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 493.572 2.00 2.00 1.00 44.9950 493.572 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 617.749 2.00 2.00 1.00 44.9950 617.749 0.073 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 384.180 2.00 2.00 1.00 44.9950 384.180 0.117 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 477.946 2.00 2.00 1.00 44.9950 477.946 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 752.082 2.00 2.00 1.00 44.9950 752.082 0.060 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 511.464 2.00 2.00 1.00 44.9950 511.464 0.088 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 610.969 2.00 2.00 1.00 44.9950 610.969 0.074 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 751.263 2.00 2.00 1.00 44.9950 751.263 0.060 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 512.075 2.00 2.00 1.00 44.9950 512.075 0.088 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 609.702 2.00 2.00 1.00 44.9950 609.702 0.074 1.000 44.9950 0.07
CENTRAL SYSTEM_UNITHEATEDBSMT 505.916 0.00 0.00 1.00 44.9950 505.916 0.089 1.000 44.9950 0.09


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 79.771 2.00 2.00 1.00 44.9950 79.771 1.000 1.000 44.9950 0.56
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 116.769 2.00 2.00 1.00 44.9950 116.769 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 117.081 2.00 2.00 1.00 44.9950 117.081 1.000 1.000 44.9950 0.38
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 82.205 2.00 2.00 1.00 44.9950 82.205 1.000 1.000 44.9950 0.55
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 116.810 2.00 2.00 1.00 44.9950 116.810 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 97.959 2.00 2.00 1.00 44.9950 97.959 1.000 1.000 44.9950 0.46
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 68.143 2.00 2.00 1.00 44.9950 68.143 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 104.075 2.00 2.00 1.00 44.9950 104.075 1.000 1.000 44.9950 0.43
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 104.252 2.00 2.00 1.00 44.9950 104.252 1.000 1.000 44.9950 0.43
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 68.676 2.00 2.00 1.00 44.9950 68.676 1.000 1.000 44.9950 0.66
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 104.035 2.00 2.00 1.00 44.9950 104.035 1.000 1.000 44.9950 0.43
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 140.941 2.00 2.00 1.00 44.9950 140.941 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 106.084 2.00 2.00 1.00 44.9950 106.084 1.000 1.000 44.9950 0.42
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 141.692 2.00 2.00 1.00 44.9950 141.692 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 141.800 2.00 2.00 1.00 44.9950 141.800 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 106.189 2.00 2.00 1.00 44.9950 106.189 1.000 1.000 44.9950 0.42
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 141.644 2.00 2.00 1.00 44.9950 141.644 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNITHEATEDBSMT 117.852 0.00 0.00 1.00 44.9950 117.852 1.000 1.000 44.9950 0.38


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   1066.142 1066.1421 213.2284 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   409.919 409.9194 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   521.472 521.4722 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   644.009 644.0087 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   404.621 404.6206 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   501.601 501.6006 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   626.095 626.0951 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   386.819 386.8191 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   493.572 493.5717 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   617.749 617.7486 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   384.180 384.1799 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   477.946 477.9461 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   609.702 609.7015 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   610.969 610.9687 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   752.082 752.0823 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   512.075 512.0751 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   511.464 511.4638 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   751.263 751.2633 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   505.916 505.9164 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14 1066.142 1066.14 213.2284 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 409.92 409.919 409.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 521.47 521.472 521.47 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 644.01 644.009 644.01 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 404.62 404.621 404.62 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 501.60 501.601 501.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 626.10 626.095 626.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 386.82 386.819 386.82 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 493.57 493.572 493.57 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 617.75 617.749 617.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 384.18 384.180 384.18 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 477.95 477.946 477.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 752.08 752.082 752.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 511.46 511.464 511.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 610.97 610.969 610.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 751.26 751.263 751.26 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 512.08 512.075 512.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 609.70 609.702 609.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 505.92 505.916 505.92 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   79.771 79.771 79.771 44.9950 0.564 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   116.769 116.769 116.769 44.9950 0.385 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   117.081 117.081 117.081 44.9950 0.384 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   82.205 82.205 82.205 44.9950 0.547 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   116.810 116.810 116.810 44.9950 0.385 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   97.959 97.959 97.959 44.9950 0.459 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   68.143 68.143 68.143 44.9950 0.660 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   104.075 104.075 104.075 44.9950 0.432 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   104.252 104.252 104.252 44.9950 0.432 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   68.676 68.676 68.676 44.9950 0.655 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   104.035 104.035 104.035 44.9950 0.433 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   141.644 141.644 141.644 44.9950 0.318 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   141.692 141.692 141.692 44.9950 0.318 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   140.941 140.941 140.941 44.9950 0.319 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   106.189 106.189 106.189 44.9950 0.424 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   106.084 106.084 106.084 44.9950 0.424 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   141.800 141.800 141.800 44.9950 0.317 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   117.852 117.852 117.852 44.9950 0.382 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 79.77 79.771 79.77 79.77 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 116.77 116.769 116.77 116.77 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 117.08 117.081 117.08 117.08 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 82.20 82.205 82.20 82.20 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 116.81 116.810 116.81 116.81 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 97.96 97.959 97.96 97.96 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 68.14 68.143 68.14 68.14 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 104.07 104.075 104.07 104.07 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 104.25 104.252 104.25 104.25 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 68.68 68.676 68.68 68.68 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 104.03 104.035 104.03 104.03 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 140.94 140.941 140.94 140.94 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 106.08 106.084 106.08 106.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 141.69 141.692 141.69 141.69 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 141.80 141.800 141.80 141.80 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 106.19 106.189 106.19 106.19 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 141.64 141.644 141.64 141.64 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 117.85 117.852 117.85 117.85 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Sec1.1A-General Information

Data
Weather File ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 164.00
Number of hours not met 164.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4758.75 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 741.27 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 660.95 112651.34 0.00 0.00
Space Cooling 59182.63 23066.38 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 13271.66 4065.22 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2144.69 147703.47 0.00 0.00
Receptacle Equipment 77145.04 12689.50 1639.73 16390.65 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 167215.59   4445.38   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 263405.37 570943.80
Natural Gas 163973.19 444537.59
Additional 0.00 0.00
Total 427378.56 1015481.38


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 1.52
Fans-Interior 0.34
Service Water Heating 0.00
Receptacle Equipment 1.98
Miscellaneous 0.08
Subtotal 4.29


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.50
Service Water Heating 1.61
Miscellaneous 1.23
Subtotal 3.34


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.91
Space Heating 6.51
Space Cooling 19.90
Fans-Interior 4.46
Service Water Heating 21.12
Receptacle Equipment 42.09
Miscellaneous 1.01



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 505.92
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 409.92
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 521.47
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 644.01
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 404.62
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 501.60
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 626.10
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 386.82
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 493.57
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 617.75
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 384.18
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 477.95
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 609.70
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 610.97
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 752.08
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 512.08
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 511.46
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 751.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 409.92
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 521.47
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 644.01
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 404.62
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 501.60
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 626.10
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 386.82
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 493.57
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 617.75
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 384.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 477.95
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 752.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 511.46
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 610.97
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 751.26
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 512.08
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 609.70
CENTRAL SYSTEM_UNITHEATEDBSMT 505.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14 2.41 0.791994
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 409.92 0.984289 0.771155
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 521.47 1.29 0.760331
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 644.01 1.50 0.781848
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 404.62 0.964876 0.773514
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 501.60 1.25 0.758888
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 626.10 1.46 0.781163
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 386.82 0.929844 0.770781
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 493.57 1.23 0.758413
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 617.75 1.44 0.782481
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 384.18 0.911330 0.775319
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 477.95 1.14 0.774243
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 752.08 1.73 0.785992
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 511.46 1.20 0.779143
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 610.97 1.44 0.778588
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 751.26 1.73 0.785965
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 512.08 1.19 0.781899
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 609.70 1.43 0.780256
DX COOLING COIL_UNITHEATEDBSMT 505.92 1.24 0.763455
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14 1066.14 1066.14 3900.50 2.41 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 409.92 409.92 409.92 5709.43 0.984289 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 521.47 521.47 521.47 7634.02 1.29 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 644.01 644.01 644.01 7650.24 1.50 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 404.62 404.62 404.62 5836.03 0.964876 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 501.60 501.60 501.60 7636.15 1.25 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 626.10 626.10 626.10 6655.50 1.46 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 386.82 386.82 386.82 5104.57 0.929844 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 493.57 493.57 493.57 6973.62 1.23 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 617.75 617.75 617.75 6982.83 1.44 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 384.18 384.18 384.18 5132.27 0.911330 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 477.95 477.95 477.95 6971.51 1.14 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 752.08 752.08 752.08 8891.41 1.73 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 511.46 511.46 511.46 7078.18 1.20 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 610.97 610.97 610.97 8930.50 1.44 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 751.26 751.26 751.26 8936.10 1.73 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 512.08 512.08 512.08 7083.67 1.19 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 609.70 609.70 609.70 8927.99 1.43 1.00
ACANDF_UNITHEATEDBSMT 505.92 505.92 505.92 7689.98 1.24 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 1066.14
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 409.92
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 521.47
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 644.01
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 404.62
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 501.60
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 626.10
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 386.82
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 493.57
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 617.75
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 384.18
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 477.95
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 752.08
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 511.46
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 610.97
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 751.26
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 512.08
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 609.70
SUPPLY FAN_UNITHEATEDBSMT 505.92
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 3900.50
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 5709.43
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 7634.02
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 7650.24
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 5836.03
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 7636.15
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 6655.50
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 5104.57
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 6973.62
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 6982.83
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 5132.27
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 6971.51
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 8891.41
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 7078.18
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 8930.50
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 8936.10
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 7083.67
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 8927.99
MAIN FUEL HEATING COIL_UNITHEATEDBSMT 7689.98
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:39

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 744.000 93.255 0.000 0.000 93.255
February 672.000 97.525 0.000 0.000 97.525
March 744.000 116.563 0.000 0.000 116.563
April 720.000 144.936 0.000 0.000 144.936
May 744.000 171.418 0.000 0.000 171.418
June 720.000 203.291 0.000 0.000 203.291
July 744.000 226.926 0.000 0.000 226.926
August 744.000 215.825 0.000 0.000 215.825
September 720.000 186.545 0.000 0.000 186.545
October 744.000 161.489 0.000 0.000 161.489
November 720.000 119.164 0.000 0.000 119.164
December 744.000 87.223 0.000 0.000 87.223
           
Annual Sum or Average 8760.000 1824.159 0.000 0.000 1824.159
Minimum of Months 672.000 87.223 0.000 0.000 87.223
Maximum of Months 744.000 226.926 0.000 0.000 226.926



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 272.498 9.307 272.542 10.784 20.091
February 300.230 14.150 189.631 7.318 21.467
March 378.539 16.654 132.517 4.742 21.395
April 561.690 32.183 44.542 1.401 33.585
May 714.395 44.413 0.000 0.000 44.413
June 720.000 67.654 0.000 0.000 67.654
July 744.000 82.683 0.000 0.000 82.683
August 744.000 75.661 0.000 0.000 75.661
September 720.000 59.918 0.000 0.000 59.918
October 685.698 43.889 7.250 0.066 43.955
November 446.880 20.976 70.125 1.524 22.500
December 242.416 8.127 316.375 14.020 22.147
           
Annual Sum or Average 6530.345 475.613 1032.982 39.856 515.468
Minimum of Months 242.416 8.127 0.000 0.000 20.091
Maximum of Months 744.000 82.683 316.375 14.020 82.683



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 231.574 8.288 334.067 19.089 27.377
February 285.174 15.514 230.000 12.438 27.952
March 384.000 19.884 170.042 8.440 28.324
April 558.601 41.166 57.000 2.370 43.537
May 702.338 57.120 1.500 0.005 57.125
June 720.000 87.049 0.000 0.000 87.049
July 744.000 104.275 0.000 0.000 104.275
August 744.000 94.702 0.000 0.000 94.702
September 720.000 73.065 0.000 0.000 73.065
October 667.638 50.726 23.875 0.569 51.295
November 429.502 21.921 128.937 4.177 26.098
December 203.344 7.101 365.406 23.562 30.663
           
Annual Sum or Average 6390.171 580.810 1310.827 70.651 651.461
Minimum of Months 203.344 7.101 0.000 0.000 26.098
Maximum of Months 744.000 104.275 365.406 23.562 104.275



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 116.588 3.043 440.292 31.442 34.485
February 198.301 9.755 304.146 20.034 29.789
March 293.596 15.891 229.317 12.402 28.293
April 506.387 39.426 75.750 3.812 43.238
May 689.593 59.979 2.083 0.008 59.988
June 720.000 93.241 0.000 0.000 93.241
July 744.000 110.856 0.000 0.000 110.856
August 744.000 98.606 0.000 0.000 98.606
September 720.000 71.098 0.000 0.000 71.098
October 638.020 42.584 39.375 1.130 43.713
November 316.458 12.113 202.783 7.779 19.893
December 83.725 1.951 498.458 39.271 41.222
           
Annual Sum or Average 5770.669 558.542 1792.204 115.878 674.420
Minimum of Months 83.725 1.951 0.000 0.000 19.893
Maximum of Months 744.000 110.856 498.458 39.271 110.856



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 77.771 1.134 411.913 16.019 17.153
February 200.492 6.124 266.286 10.062 16.186
March 308.210 9.432 164.464 5.552 14.983
April 546.929 27.756 54.000 1.651 29.408
May 713.658 43.657 0.000 0.000 43.657
June 720.000 68.200 0.000 0.000 68.200
July 744.000 82.427 0.000 0.000 82.427
August 744.000 73.094 0.000 0.000 73.094
September 720.000 52.829 0.000 0.000 52.829
October 669.258 33.009 15.500 0.155 33.164
November 345.492 8.134 113.855 2.428 10.562
December 48.598 0.530 488.012 20.981 21.511
           
Annual Sum or Average 5838.408 406.324 1514.030 56.848 463.173
Minimum of Months 48.598 0.530 0.000 0.000 10.562
Maximum of Months 744.000 82.427 488.012 20.981 82.427



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 69.089 1.047 455.792 23.281 24.328
February 214.271 7.708 286.100 14.152 21.860
March 348.268 12.698 184.185 8.626 21.325
April 552.907 36.543 57.750 2.364 38.908
May 702.547 55.687 1.500 0.005 55.692
June 720.000 86.427 0.000 0.000 86.427
July 744.000 102.767 0.000 0.000 102.767
August 744.000 91.230 0.000 0.000 91.230
September 720.000 65.775 0.000 0.000 65.775
October 662.077 40.096 25.375 0.588 40.684
November 367.109 9.179 141.321 4.474 13.653
December 40.875 0.432 524.804 29.369 29.801
           
Annual Sum or Average 5885.143 509.591 1676.827 82.858 592.449
Minimum of Months 40.875 0.432 0.000 0.000 13.653
Maximum of Months 744.000 102.767 524.804 29.369 102.767



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 267.599 12.709 298.250 18.142 30.851
February 294.770 19.080 206.878 12.031 31.111
March 376.853 24.635 148.893 8.022 32.658
April 549.888 44.880 46.667 2.338 47.218
May 703.208 60.871 0.000 0.000 60.871
June 720.000 90.959 0.000 0.000 90.959
July 744.000 107.460 0.000 0.000 107.460
August 744.000 98.821 0.000 0.000 98.821
September 720.000 77.851 0.000 0.000 77.851
October 671.008 53.910 22.775 0.455 54.366
November 426.191 25.847 105.292 3.448 29.296
December 237.419 11.032 340.857 23.214 34.247
           
Annual Sum or Average 6454.934 628.056 1169.611 67.652 695.708
Minimum of Months 237.419 11.032 0.000 0.000 29.296
Maximum of Months 744.000 107.460 340.857 23.214 107.460



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 310.323 10.648 210.187 6.661 17.309
February 348.706 15.673 146.625 4.676 20.349
March 432.346 18.480 97.625 3.167 21.647
April 606.956 33.236 26.000 0.887 34.123
May 725.423 44.171 0.000 0.000 44.171
June 720.000 65.077 0.000 0.000 65.077
July 744.000 78.282 0.000 0.000 78.282
August 744.000 72.618 0.000 0.000 72.618
September 720.000 59.019 0.000 0.000 59.019
October 694.516 44.177 1.875 0.012 44.189
November 491.120 22.698 41.250 0.602 23.300
December 286.065 9.442 263.958 9.246 18.687
           
Annual Sum or Average 6823.454 473.522 787.521 25.250 498.772
Minimum of Months 286.065 9.442 0.000 0.000 17.309
Maximum of Months 744.000 78.282 263.958 9.246 78.282



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 263.871 9.164 293.308 14.108 23.272
February 311.134 16.664 195.375 9.235 25.899
March 417.376 21.466 134.667 6.248 27.715
April 587.730 42.006 43.500 1.617 43.623
May 714.265 56.756 0.000 0.000 56.756
June 720.000 84.569 0.000 0.000 84.569
July 744.000 99.842 0.000 0.000 99.842
August 744.000 91.612 0.000 0.000 91.612
September 720.000 72.161 0.000 0.000 72.161
October 680.954 50.816 17.750 0.311 51.127
November 456.880 23.210 91.375 2.499 25.709
December 233.232 7.936 326.500 18.155 26.091
           
Annual Sum or Average 6593.443 576.202 1102.475 52.173 628.376
Minimum of Months 233.232 7.936 0.000 0.000 23.272
Maximum of Months 744.000 99.842 326.500 18.155 99.842



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 143.083 3.387 400.633 25.083 28.471
February 221.259 10.616 272.225 15.808 26.423
March 326.698 17.298 182.284 9.374 26.672
April 537.671 40.437 61.042 2.783 43.220
May 702.818 60.023 0.000 0.000 60.023
June 720.000 91.319 0.000 0.000 91.319
July 744.000 107.085 0.000 0.000 107.085
August 744.000 96.209 0.000 0.000 96.209
September 720.000 70.861 0.000 0.000 70.861
October 651.965 43.107 34.250 0.772 43.879
November 342.935 13.138 164.268 5.398 18.536
December 101.629 2.174 462.688 32.328 34.502
           
Annual Sum or Average 5956.059 555.654 1577.389 91.545 647.199
Minimum of Months 101.629 2.174 0.000 0.000 18.536
Maximum of Months 744.000 107.085 462.688 32.328 107.085



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 112.017 1.636 340.246 10.986 12.622
February 243.724 7.352 216.812 6.855 14.207
March 369.354 11.351 116.746 3.668 15.019
April 595.380 29.233 31.792 1.019 30.252
May 726.100 43.768 0.000 0.000 43.768
June 720.000 66.035 0.000 0.000 66.035
July 744.000 78.509 0.000 0.000 78.509
August 744.000 70.547 0.000 0.000 70.547
September 720.000 52.437 0.000 0.000 52.437
October 677.454 33.670 5.308 0.036 33.706
November 390.273 9.743 73.634 1.226 10.969
December 70.877 0.881 426.092 15.219 16.100
           
Annual Sum or Average 6113.178 405.162 1210.630 39.009 444.170
Minimum of Months 70.877 0.881 0.000 0.000 10.969
Maximum of Months 744.000 78.509 426.092 15.219 78.509



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 81.042 1.387 408.295 18.141 19.528
February 235.556 9.071 247.813 10.859 19.930
March 387.344 15.043 147.851 6.456 21.498
April 582.166 39.405 46.750 1.649 41.053
May 714.848 57.963 0.000 0.000 57.963
June 720.000 87.611 0.000 0.000 87.611
July 744.000 102.204 0.000 0.000 102.204
August 744.000 91.763 0.000 0.000 91.763
September 720.000 67.811 0.000 0.000 67.811
October 673.764 42.081 19.125 0.338 42.418
November 395.200 10.912 105.125 2.812 13.724
December 55.804 0.660 479.021 23.697 24.357
           
Annual Sum or Average 6053.724 525.909 1453.979 63.951 589.860
Minimum of Months 55.804 0.660 0.000 0.000 13.724
Maximum of Months 744.000 102.204 479.021 23.697 102.204



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 216.591 11.196 368.863 31.188 42.384
February 259.569 19.299 264.458 20.618 39.917
March 337.815 26.099 217.190 14.057 40.156
April 514.817 50.732 74.646 4.419 55.151
May 683.360 70.544 9.219 0.095 70.638
June 720.000 108.560 0.000 0.000 108.560
July 744.000 129.121 0.000 0.000 129.121
August 744.000 116.456 0.000 0.000 116.456
September 720.000 88.915 0.000 0.000 88.915
October 639.052 58.344 38.250 1.477 59.821
November 379.547 25.352 173.625 8.204 33.557
December 188.923 9.313 406.208 37.968 47.281
           
Annual Sum or Average 6147.673 713.929 1552.460 118.027 831.956
Minimum of Months 188.923 9.313 0.000 0.000 33.557
Maximum of Months 744.000 129.121 406.208 37.968 129.121



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 243.463 9.156 310.921 15.795 24.951
February 290.772 15.909 214.738 10.563 26.471
March 367.416 20.040 155.266 6.899 26.939
April 552.225 39.166 55.500 2.128 41.294
May 703.330 54.085 0.000 0.000 54.085
June 720.000 83.132 0.000 0.000 83.132
July 744.000 100.266 0.000 0.000 100.266
August 744.000 90.701 0.000 0.000 90.701
September 720.000 70.598 0.000 0.000 70.598
October 672.714 48.977 21.946 0.368 49.345
November 424.458 22.232 105.538 2.840 25.072
December 210.665 7.699 351.010 20.022 27.721
           
Annual Sum or Average 6393.044 561.962 1214.920 58.614 620.576
Minimum of Months 210.665 7.699 0.000 0.000 24.951
Maximum of Months 744.000 100.266 351.010 20.022 100.266



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 210.792 8.302 352.540 24.018 32.320
February 276.411 17.429 242.583 15.485 32.915
March 374.206 23.441 180.385 10.277 33.718
April 556.930 49.188 59.500 2.954 52.142
May 699.759 68.418 6.750 0.053 68.472
June 720.000 105.131 0.000 0.000 105.131
July 744.000 124.390 0.000 0.000 124.390
August 744.000 112.126 0.000 0.000 112.126
September 720.000 85.772 0.000 0.000 85.772
October 654.589 57.041 29.375 0.913 57.954
November 414.350 23.483 142.875 5.590 29.073
December 180.858 6.821 390.750 29.398 36.218
           
Annual Sum or Average 6295.895 681.542 1404.758 88.688 770.230
Minimum of Months 180.858 6.821 0.000 0.000 29.073
Maximum of Months 744.000 124.390 390.750 29.398 124.390



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 133.858 4.326 442.255 37.866 42.192
February 211.949 13.178 305.750 23.893 37.071
March 312.240 21.808 234.723 14.919 36.727
April 510.544 48.738 77.232 4.606 53.344
May 684.736 70.556 9.219 0.096 70.652
June 720.000 109.199 0.000 0.000 109.199
July 744.000 129.292 0.000 0.000 129.292
August 744.000 115.496 0.000 0.000 115.496
September 720.000 85.109 0.000 0.000 85.109
October 622.888 50.435 45.250 1.818 52.253
November 320.670 15.514 217.670 10.425 25.940
December 98.829 2.857 493.396 46.706 49.563
           
Annual Sum or Average 5823.714 666.508 1825.494 140.330 806.838
Minimum of Months 98.829 2.857 0.000 0.000 25.940
Maximum of Months 744.000 129.292 493.396 46.706 129.292



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 108.830 2.228 412.333 21.369 23.597
February 220.629 9.659 265.500 13.204 22.863
March 332.706 15.762 172.598 7.497 23.259
April 546.403 37.482 58.600 2.266 39.748
May 703.962 54.525 0.000 0.000 54.525
June 720.000 84.354 0.000 0.000 84.354
July 744.000 101.035 0.000 0.000 101.035
August 744.000 90.306 0.000 0.000 90.306
September 720.000 67.227 0.000 0.000 67.227
October 657.589 41.156 30.530 0.554 41.711
November 350.217 11.807 149.905 4.136 15.943
December 68.827 1.235 478.037 27.424 28.659
           
Annual Sum or Average 5917.163 516.778 1567.503 76.450 593.228
Minimum of Months 68.827 1.235 0.000 0.000 15.943
Maximum of Months 744.000 101.035 478.037 27.424 101.035



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 86.824 2.020 454.667 29.361 31.381
February 220.513 11.379 287.033 17.698 29.077
March 353.091 19.167 190.030 10.644 29.811
April 553.172 47.493 60.000 3.007 50.500
May 700.079 68.701 6.750 0.053 68.754
June 720.000 106.081 0.000 0.000 106.081
July 744.000 124.903 0.000 0.000 124.903
August 744.000 111.611 0.000 0.000 111.611
September 720.000 82.496 0.000 0.000 82.496
October 646.307 49.456 32.500 0.985 50.441
November 355.794 12.968 166.143 6.294 19.262
December 58.250 1.087 520.446 36.630 37.717
           
Annual Sum or Average 5902.031 637.362 1717.569 104.671 742.034
Minimum of Months 58.250 1.087 0.000 0.000 19.262
Maximum of Months 744.000 124.903 520.446 36.630 124.903



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 63.649 63.649
February 0.000 0.000 636.442 39.939 39.939
March 0.000 0.000 474.412 16.460 16.460
April 26.536 0.154 30.625 0.560 0.714
May 742.625 47.886 0.000 0.000 47.886
June 720.000 98.537 0.000 0.000 98.537
July 744.000 114.192 0.000 0.000 114.192
August 744.000 104.689 0.000 0.000 104.689
September 720.000 82.702 0.000 0.000 82.702
October 744.000 46.405 0.000 0.000 46.405
November 0.500 0.012 204.724 3.711 3.723
December 0.000 0.000 744.000 62.684 62.684
           
Annual Sum or Average 4441.661 494.577 2834.204 187.003 681.581
Minimum of Months 0.000 0.000 0.000 0.000 0.714
Maximum of Months 744.000 114.192 744.000 63.649 114.192



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 535.24 0.00
February 0.00 402.11 0.00
March 0.00 235.34 0.00
April 0.00 71.87 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 3.29 0.00
November 0.00 78.18 0.00
December 0.00 695.84 0.00
       
Annual Sum or Average 0.00 168.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 695.84 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 995.78 0.00
February 0.00 718.38 0.00
March 0.00 440.26 0.00
April 0.00 127.78 0.00
May 0.00 0.26 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 29.70 0.00
November 0.00 225.17 0.00
December 0.00 1229.13 0.00
       
Annual Sum or Average 0.00 313.02 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1229.13 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1330.94 0.00
February 0.00 938.91 0.00
March 0.00 524.97 0.00
April 0.00 166.74 0.00
May 0.00 0.36 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 47.81 0.00
November 0.00 340.27 0.00
December 0.00 1662.34 0.00
       
Annual Sum or Average 0.00 416.60 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1662.34 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 823.33 0.00
February 0.00 572.58 0.00
March 0.00 285.33 0.00
April 0.00 87.70 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 7.95 0.00
November 0.00 128.96 0.00
December 0.00 1078.34 0.00
       
Annual Sum or Average 0.00 248.15 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1078.34 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1262.93 0.00
February 0.00 849.94 0.00
March 0.00 467.95 0.00
April 0.00 132.53 0.00
May 0.00 0.25 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 31.88 0.00
November 0.00 250.78 0.00
December 0.00 1593.19 0.00
       
Annual Sum or Average 0.00 381.75 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1593.19 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 687.21 0.00
February 0.00 504.55 0.00
March 0.00 303.89 0.00
April 0.00 91.53 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 17.25 0.00
November 0.00 134.98 0.00
December 0.00 879.35 0.00
       
Annual Sum or Average 0.00 217.65 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 879.35 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 313.20 0.00
February 0.00 243.44 0.00
March 0.00 148.92 0.00
April 0.00 43.10 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.55 0.00
November 0.00 29.25 0.00
December 0.00 434.76 0.00
       
Annual Sum or Average 0.00 100.84 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 434.76 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 710.27 0.00
February 0.00 514.75 0.00
March 0.00 314.59 0.00
April 0.00 84.14 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 15.66 0.00
November 0.00 130.02 0.00
December 0.00 914.06 0.00
       
Annual Sum or Average 0.00 223.09 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 914.06 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1010.34 0.00
February 0.00 704.94 0.00
March 0.00 377.57 0.00
April 0.00 115.84 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 31.08 0.00
November 0.00 224.66 0.00
December 0.00 1302.16 0.00
       
Annual Sum or Average 0.00 313.18 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1302.16 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 522.97 0.00
February 0.00 361.28 0.00
March 0.00 174.59 0.00
April 0.00 50.11 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 1.72 0.00
November 0.00 60.30 0.00
December 0.00 724.50 0.00
       
Annual Sum or Average 0.00 157.71 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 724.50 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 942.93 0.00
February 0.00 624.89 0.00
March 0.00 335.55 0.00
April 0.00 88.54 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 17.54 0.00
November 0.00 151.01 0.00
December 0.00 1231.71 0.00
       
Annual Sum or Average 0.00 282.31 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1231.71 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1313.88 0.00
February 0.00 961.66 0.00
March 0.00 592.19 0.00
April 0.00 192.37 0.00
May 0.00 3.98 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 62.24 0.00
November 0.00 357.15 0.00
December 0.00 1599.52 0.00
       
Annual Sum or Average 0.00 422.30 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1599.52 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 778.91 0.00
February 0.00 576.69 0.00
March 0.00 340.22 0.00
April 0.00 108.43 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 18.14 0.00
November 0.00 144.72 0.00
December 0.00 987.38 0.00
       
Annual Sum or Average 0.00 245.50 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 987.38 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1250.98 0.00
February 0.00 892.98 0.00
March 0.00 535.28 0.00
April 0.00 159.00 0.00
May 0.00 2.78 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 47.57 0.00
November 0.00 300.86 0.00
December 0.00 1531.21 0.00
       
Annual Sum or Average 0.00 392.33 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1531.21 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1604.98 0.00
February 0.00 1121.25 0.00
March 0.00 632.36 0.00
April 0.00 201.75 0.00
May 0.00 4.05 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 77.05 0.00
November 0.00 456.61 0.00
December 0.00 1979.67 0.00
       
Annual Sum or Average 0.00 505.17 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1979.67 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1053.35 0.00
February 0.00 720.60 0.00
March 0.00 369.56 0.00
April 0.00 115.42 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 27.33 0.00
November 0.00 210.65 0.00
December 0.00 1351.82 0.00
       
Annual Sum or Average 0.00 320.06 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1351.82 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1532.03 0.00
February 0.00 1022.41 0.00
March 0.00 555.38 0.00
April 0.00 162.14 0.00
May 0.00 2.75 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 51.38 0.00
November 0.00 339.37 0.00
December 0.00 1911.33 0.00
       
Annual Sum or Average 0.00 463.87 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1911.33 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3447.49 0.00
February 0.00 2395.00 0.00
March 0.00 891.55 0.00
April 0.00 31.32 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 207.72 0.00
December 0.00 3395.23 0.00
       
Annual Sum or Average 0.00 860.26 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3447.49 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.69
February 0.00 0.00 0.80
March 0.00 0.00 0.86
April 0.00 0.00 1.07
May 0.00 0.00 1.21
June 0.00 0.00 1.45
July 0.00 0.00 1.59
August 0.00 0.00 1.53
September 0.00 0.00 1.37
October 0.00 0.00 1.17
November 0.00 0.00 0.91
December 0.00 0.00 0.66
       
Annual Sum or Average 0.00 0.00 1.11
Minimum of Months 0.00 0.00 0.66
Maximum of Months 0.00 0.00 1.59



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.12
March 0.00 0.00 0.12
April 0.00 0.00 0.24
May 0.00 0.00 0.32
June 0.00 0.00 0.50
July 0.00 0.00 0.62
August 0.00 0.00 0.57
September 0.00 0.00 0.46
October 0.00 0.00 0.33
November 0.00 0.00 0.16
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.13
March 0.00 0.00 0.15
April 0.00 0.00 0.32
May 0.00 0.00 0.43
June 0.00 0.00 0.67
July 0.00 0.00 0.80
August 0.00 0.00 0.73
September 0.00 0.00 0.58
October 0.00 0.00 0.39
November 0.00 0.00 0.18
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.80



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.11
April 0.00 0.00 0.28
May 0.00 0.00 0.42
June 0.00 0.00 0.67
July 0.00 0.00 0.78
August 0.00 0.00 0.70
September 0.00 0.00 0.52
October 0.00 0.00 0.30
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.78



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.20
May 0.00 0.00 0.31
June 0.00 0.00 0.51
July 0.00 0.00 0.61
August 0.00 0.00 0.54
September 0.00 0.00 0.40
October 0.00 0.00 0.24
November 0.00 0.00 0.06
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.61



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.28
May 0.00 0.00 0.42
June 0.00 0.00 0.67
July 0.00 0.00 0.79
August 0.00 0.00 0.71
September 0.00 0.00 0.52
October 0.00 0.00 0.30
November 0.00 0.00 0.07
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.79



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.09
February 0.00 0.00 0.15
March 0.00 0.00 0.18
April 0.00 0.00 0.33
May 0.00 0.00 0.43
June 0.00 0.00 0.65
July 0.00 0.00 0.76
August 0.00 0.00 0.70
September 0.00 0.00 0.57
October 0.00 0.00 0.39
November 0.00 0.00 0.20
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.08
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.13
March 0.00 0.00 0.14
April 0.00 0.00 0.25
May 0.00 0.00 0.32
June 0.00 0.00 0.49
July 0.00 0.00 0.58
August 0.00 0.00 0.55
September 0.00 0.00 0.46
October 0.00 0.00 0.34
November 0.00 0.00 0.18
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.14
March 0.00 0.00 0.17
April 0.00 0.00 0.33
May 0.00 0.00 0.43
June 0.00 0.00 0.66
July 0.00 0.00 0.77
August 0.00 0.00 0.71
September 0.00 0.00 0.58
October 0.00 0.00 0.40
November 0.00 0.00 0.19
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.38
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.77



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.12
April 0.00 0.00 0.29
May 0.00 0.00 0.42
June 0.00 0.00 0.65
July 0.00 0.00 0.76
August 0.00 0.00 0.68
September 0.00 0.00 0.52
October 0.00 0.00 0.30
November 0.00 0.00 0.10
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.08
April 0.00 0.00 0.22
May 0.00 0.00 0.32
June 0.00 0.00 0.49
July 0.00 0.00 0.58
August 0.00 0.00 0.52
September 0.00 0.00 0.40
October 0.00 0.00 0.25
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.07
March 0.00 0.00 0.11
April 0.00 0.00 0.29
May 0.00 0.00 0.42
June 0.00 0.00 0.66
July 0.00 0.00 0.76
August 0.00 0.00 0.68
September 0.00 0.00 0.51
October 0.00 0.00 0.31
November 0.00 0.00 0.08
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.33
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.15
March 0.00 0.00 0.19
April 0.00 0.00 0.36
May 0.00 0.00 0.49
June 0.00 0.00 0.77
July 0.00 0.00 0.90
August 0.00 0.00 0.82
September 0.00 0.00 0.64
October 0.00 0.00 0.41
November 0.00 0.00 0.19
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.07
Maximum of Months 0.00 0.00 0.90



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.13
March 0.00 0.00 0.15
April 0.00 0.00 0.29
May 0.00 0.00 0.38
June 0.00 0.00 0.61
July 0.00 0.00 0.73
August 0.00 0.00 0.66
September 0.00 0.00 0.53
October 0.00 0.00 0.36
November 0.00 0.00 0.17
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.73



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.14
March 0.00 0.00 0.17
April 0.00 0.00 0.36
May 0.00 0.00 0.49
June 0.00 0.00 0.77
July 0.00 0.00 0.91
August 0.00 0.00 0.82
September 0.00 0.00 0.64
October 0.00 0.00 0.42
November 0.00 0.00 0.18
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.42
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.91



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.10
March 0.00 0.00 0.15
April 0.00 0.00 0.35
May 0.00 0.00 0.49
June 0.00 0.00 0.77
July 0.00 0.00 0.90
August 0.00 0.00 0.81
September 0.00 0.00 0.61
October 0.00 0.00 0.35
November 0.00 0.00 0.11
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.90



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.11
April 0.00 0.00 0.27
May 0.00 0.00 0.38
June 0.00 0.00 0.61
July 0.00 0.00 0.73
August 0.00 0.00 0.65
September 0.00 0.00 0.50
October 0.00 0.00 0.29
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.73



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.09
March 0.00 0.00 0.14
April 0.00 0.00 0.35
May 0.00 0.00 0.49
June 0.00 0.00 0.78
July 0.00 0.00 0.91
August 0.00 0.00 0.81
September 0.00 0.00 0.61
October 0.00 0.00 0.35
November 0.00 0.00 0.10
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.91



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.34
June 0.00 0.00 0.76
July 0.00 0.00 0.85
August 0.00 0.00 0.78
September 0.00 0.00 0.64
October 0.00 0.00 0.34
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.85



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11
Maximum of Months 0.00 0.00 1419.50 1056.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.50 1056.86
February 0.00 0.00 1390.14 934.84
March 0.00 0.00 1283.23 955.40
April 0.00 0.00 1125.44 810.89
May 0.00 0.00 950.12 707.39
June 0.00 0.00 816.89 588.58
July 0.00 0.00 754.99 562.11
August 0.00 0.00 783.27 583.17
September 0.00 0.00 896.17 645.70
October 0.00 0.00 1058.69 788.23
November 0.00 0.00 1227.54 884.46
December 0.00 0.00 1362.41 1014.35
         
Annual Sum or Average 0.00 0.00 1087.35 9531.97
Minimum of Months 0.00 0.00 754.99 562.11