Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32

Tabular Output Report in Format: HTML

Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+oilfurnace+heatedbsmt+IECC_2009

Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780

Simulation Timestamp: 2019-02-14 08:32:24


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 885930.14 22.71 30.13
Net Site Energy 885930.14 22.71 30.13
Total Source Energy 2191289.94 56.18 74.52
Net Source Energy 2191289.94 56.18 74.52


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 80514.59 0.00 0.00 0.00 0.00
Cooling 188197.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 41096.25 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 214469.00 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 590946.55 294983.59 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 80514.59 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 188197.49 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 41096.25 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 214469.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.05 0.00 0.00 0.00 0.00 0.00
HVAC 7.80 10.03 0.00 0.00 0.00 14.27
Other 10.25 0.00 0.00 0.00 0.00 0.00
Total 20.10 10.03 0.00 0.00 0.00 14.27


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 5.88 7.56 0.00 0.00 0.00 10.76
Other 7.73 0.00 0.00 0.00 0.00 0.00
Total 15.15 7.56 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 590946.550 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 590946.550 100.00
     
Total On-Site and Utility Electric Sources 590946.550 100.00
Total Electricity End Uses 590946.550 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 713.75
Time Setpoint Not Met During Occupied Cooling 148.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 207.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:32
RunPeriod ANNUAL
Weather File Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Latitude [deg] 33.45
Longitude [deg] -112.0
Elevation [ft] 1105.70
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.4163 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.5522 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 16-JUL-18:15 20-JAN-06:00 - - - 01-JAN-08:15
Heating 0.00 130.87 0.00 0.00 0.00 0.00
Cooling 77.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.91 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 13.22 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 112.90 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 160.46 243.77 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 130.87 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 77.19 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.64 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.82 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 13.22 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 112.90 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 87277.81 0.00 0.00 0.00
Cooling 596021.46 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 130151.82 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 232484.40 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1871527.72 319762.21 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 2.97 0.00 0.00 0.00
Cooling 20.27 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.43 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.91 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 63.65 10.87 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 2.97 0.00 0.00 0.00
Cooling 20.27 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.43 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 7.91 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 63.65 10.87 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 38.66 0.00 38.66 Wetbulb [F] 334.66 100.00
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 110.12 21.60 69.98 Wetbulb [F] 807.13 260.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.367 0.534 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.367 0.534 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.065 0.070 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.651 0.260 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.651 0.260 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.651 0.260 0.882              
North Total or Average           531.68 0.651 0.260 0.882              
Non-North Total or Average           1595.05 0.651 0.260 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.419 0.650 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 565746.40 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   28319.32 22370.59 5948.73 0.79 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11187.09 8514.83 2672.26 0.76 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15024.96 11403.56 3621.39 0.76 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   17296.63 13470.51 3826.12 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10687.81 8229.63 2458.18 0.77 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14501.05 10983.70 3517.35 0.76 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16809.88 13077.93 3731.95 0.78 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10373.28 7921.70 2451.59 0.76 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14257.18 10790.56 3466.62 0.76 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16497.61 12847.64 3649.97 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10070.32 7756.18 2314.14 0.77 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13771.28 10401.19 3370.10 0.76 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20060.69 15713.80 4346.88 0.78 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13500.70 10487.76 3012.94 0.78 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17157.83 13170.55 3987.27 0.77 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20031.70 15690.28 4341.42 0.78 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13499.73 10486.96 3012.76 0.78 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17106.98 13129.67 3977.31 0.77 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   14811.53 11303.67 3507.86 0.76 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.3 3.28 11.18 11.83 11.36
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.33 11.36 12.04 11.65
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.2 3.33 11.37 12.05 11.68
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.4 3.30 11.25 11.91 11.47
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.31 11.30 11.97 11.56
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.2 3.34 11.38 12.06 11.69
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.30 11.25 11.92 11.48
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.32 11.34 12.02 11.63
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.1 3.34 11.39 12.07 11.70
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.3 3.30 11.25 11.91 11.47
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.31 11.30 11.97 11.56
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.1 3.34 11.40 12.08 11.72
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.6 3.29 11.22 11.88 11.43
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.1 3.30 11.26 11.93 11.49
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.4 3.32 11.32 11.99 11.59
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.6 3.29 11.22 11.88 11.43
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.30 11.26 11.93 11.49
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.4 3.32 11.32 11.99 11.59
DX COOLING COIL_UNITHEATEDBSMT   1.2 3.33 11.35 12.02 11.63
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 55502.60 60051.38 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 21160.43 22387.04 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 27713.07 29580.82 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 33486.60 35918.08 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 20788.88 21978.69 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 26683.13 28450.11 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 32515.66 34850.48 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 19873.63 20971.58 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 26215.29 27934.52 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 32007.78 34292.61 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 19688.21 20767.83 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 25260.28 26886.05 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 39069.85 42043.35 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 26339.09 28072.55 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 32212.24 34517.82 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 39011.30 41979.05 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 26337.09 28070.34 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 32111.57 34407.34 -
MAIN WATER HEATING COIL_UNITHEATEDBSMT Coil:Heating:Water 27668.64 29520.50 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1037.10 391.19 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 376.81 142.13 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 502.77 189.64 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 613.76 231.51 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 369.66 139.43 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 482.97 182.17 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 595.11 224.47 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 352.08 132.80 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 473.99 178.79 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 585.35 220.79 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 348.51 131.46 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 455.63 171.86 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 721.09 271.99 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 476.36 179.68 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 589.26 222.27 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 719.97 271.57 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 476.32 179.67 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 587.33 221.54 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 501.96 189.34 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 56.890156 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23409.22 23409.22 19.50 1037.105 1037.105 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00801 106.56 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8505.17 8505.17 7.08 376.807 376.807 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00804 106.02 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11348.57 11348.57 9.45 502.772 502.772 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00796 110.12 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13853.66 13853.66 11.54 613.763 613.763 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00803 106.02 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8343.88 8343.88 6.95 369.664 369.664 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00811 103.32 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10901.65 10901.65 9.08 482.972 482.972 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00796 110.12 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13432.63 13432.63 11.19 595.113 595.113 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00806 106.02 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7946.90 7946.90 6.62 352.077 352.077 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00815 104.13 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10698.76 10698.76 8.91 473.990 473.990 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00800 110.12 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13212.22 13212.22 11.01 585.349 585.349 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00807 105.48 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7866.41 7866.41 6.55 348.513 348.513 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00818 101.70 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10284.36 10284.36 8.57 455.630 455.630 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 74.98 74.98 0.00800 110.12 0.00720 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 13257.10 13257.10 11.04 587.327 587.327 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00797 109.15 0.00720 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 13300.78 13300.78 11.08 589.263 589.263 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00797 109.15 0.00720 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 16276.30 16276.30 13.56 721.094 721.094 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00802 106.02 0.00720 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 10751.35 10751.35 8.96 476.323 476.323 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00808 104.13 0.00720 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 10752.22 10752.22 8.96 476.362 476.362 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00808 104.13 0.00720 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 16250.89 16250.89 13.54 719.969 719.969 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00802 106.02 0.00720 44.995 0.00
HEATEDBSMT 11330.20 11330.20 1.45 501.965 501.965 PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 16:00:00 74.98 74.98 0.00800 108.82 0.00720 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4611.71 4611.71 3.84 87.366 87.366 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00685 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6579.08 6579.08 5.48 124.635 124.635 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00701 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6595.22 6595.22 5.49 124.941 124.941 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00701 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4746.31 4746.31 3.95 89.916 89.916 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00687 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6580.95 6580.95 5.48 124.670 124.670 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00701 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5579.65 5579.65 4.65 105.705 105.705 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00716 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4005.86 4005.86 3.34 75.891 75.891 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00706 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5910.12 5910.12 4.92 111.965 111.965 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00719 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5919.27 5919.27 4.93 112.139 112.139 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00719 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4033.76 4033.76 3.36 76.419 76.419 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00707 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5907.81 5907.81 4.92 111.921 111.921 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00719 38.66 0.00513 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7897.91 7897.91 6.58 149.619 149.619 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00711 38.66 0.00513 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7900.53 7900.53 6.58 149.668 149.668 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00711 38.66 0.00513 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7861.08 7861.08 6.55 148.921 148.921 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00711 38.66 0.00513 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6029.83 6029.83 5.02 114.231 114.231 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00700 38.66 0.00513 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6024.62 6024.62 5.02 114.132 114.132 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00700 38.66 0.00513 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7906.10 7906.10 6.59 149.774 149.774 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00711 38.66 0.00513 44.995 0.00
HEATEDBSMT 6278.39 6278.39 0.81 118.951 118.951 PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB 12/21 06:15:00 72.00 72.00 0.00800 38.66 0.00513 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10 1037.10 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 376.81 376.81 87.37 87.37
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 502.77 502.77 124.64 124.64
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 613.76 613.76 124.94 124.94
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 369.66 369.66 89.92 89.92
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 482.97 482.97 124.67 124.67
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 595.11 595.11 105.70 105.70
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 352.08 352.08 75.89 75.89
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 473.99 473.99 111.97 111.97
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 585.35 585.35 112.14 112.14
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 348.51 348.51 76.42 76.42
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 455.63 455.63 111.92 111.92
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 721.09 721.09 148.92 148.92
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 476.36 476.36 114.13 114.13
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 589.26 589.26 149.67 149.67
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 719.97 719.97 149.77 149.77
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 476.32 476.32 114.23 114.23
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 587.33 587.33 149.62 149.62
CENTRAL SYSTEM_UNITHEATEDBSMT 501.96 501.96 118.95 118.95


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2983.00 3373.75 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2461.75 3335.00 52.25
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3195.50 3237.50 56.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2971.50 4023.25 138.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2157.50 4225.25 60.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2921.00 3904.75 59.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3464.25 3178.25 44.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2689.75 3045.50 27.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3407.00 3029.75 35.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3141.50 3816.25 100.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2361.00 3917.25 33.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3078.00 3677.00 37.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3390.50 3670.00 72.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 3628.00 3231.50 63.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 3582.75 3428.75 85.25
LIVING_UNIT2_BACKROW_TOPFLOOR 2812.25 3860.25 53.25
LIVING_UNIT2_FRONTROW_TOPFLOOR 3025.50 3305.50 50.50
LIVING_UNIT1_BACKROW_TOPFLOOR 3395.00 3829.50 136.25
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4150.25 4513.25 207.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 99.75 0.00 99.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 42.00 0.00 42.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 114.25 3.00 114.25 3.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 223.50 80.25 223.50 80.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16.75 62.00 16.75 62.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 54.00 9.25 54.00 9.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14.25 63.75 14.25 63.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 34.75 0.00 34.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 145.75 0.25 145.75 0.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 215.75 68.75 215.75 68.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8.50 43.75 8.50 43.75
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 115.00 2.50 115.00 2.50
LIVING_UNIT3_BACKROW_TOPFLOOR 25.25 30.00 25.25 30.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 54.75 31.75 54.75 31.75
LIVING_UNIT1_FRONTROW_TOPFLOOR 62.00 100.25 62.00 100.25
LIVING_UNIT2_BACKROW_TOPFLOOR 4.25 84.25 4.25 84.25
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 84.50 0.00 84.50
LIVING_UNIT1_BACKROW_TOPFLOOR 222.75 100.50 222.75 100.50
HEATEDBSMT 428.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1136.00 148.00 713.75 148.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.206 0.000 0.265
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.179 0.000 0.265
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.203 0.000 0.265
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.202 0.000 0.264
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.178 0.000 0.265
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.202 0.000 0.265
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.065 0.000 0.265
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.088 0.000 0.265
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.265
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.265
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.202 0.000 0.265
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.203 0.000 0.265
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.203 0.000 0.265
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.178 0.000 0.265
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.179 0.000 0.265
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.202 0.000 0.265
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1890
Defaulted Fields 455
Fields with Defaults 4813
Autosized Fields 342
Autosizable Fields 454
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Fans:Electricity 12036.09 113.03 05-APR-01:45 3872.28 16-JUL-17:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
ElectricityPurchased:Plant 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
Cogeneration:ElectricityPurchased 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
ElectricityNet:Plant 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
Cogeneration:ElectricityNet 173073.91 7483.27 11-APR-03:30 46993.69 16-JUL-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 67154.58 543.92 05-APR-02:00 26542.15 16-JUL-18:00
General:Fans:Electricity 12036.09 113.03 05-APR-01:45 3872.28 16-JUL-17:00
Cooling:Electricity 55118.48 38.23 31-JAN-07:30 22669.87 16-JUL-18:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 2949.84 0.00 01-JAN-15:00 243596.40 20-JAN-07:00
Gas:Plant 2949.84 0.00 01-JAN-15:00 243596.40 20-JAN-07:00
WaterSystems:Gas 2144.69 0.00 01-JAN-00:15 114042.38 21-JAN-09:00
Water Heater:WaterSystems:Gas 2144.69 0.00 01-JAN-00:15 114042.38 21-JAN-09:00
Heating:Gas 805.15 0.00 01-JAN-14:30 132353.12 31-JAN-07:15
Boiler:Heating:Gas 805.15 0.00 01-JAN-14:30 132353.12 31-JAN-07:15


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 07-APR-03:00 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 156593.62 431.70 21-JUL-03:00 135827.41 31-JAN-07:15
PlantLoopHeatingDemand:Plant 93473.99 431.70 21-JUL-03:00 31801.02 21-JAN-08:45
WaterSystems:PlantLoopHeatingDemand 93473.99 431.70 21-JUL-03:00 31801.02 21-JAN-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1628531.28 15869.22 02-NOV-02:30 486768.37 09-JUL-17:00
EnergyTransfer:Building 700232.82 6897.37 05-APR-02:00 232523.45 02-JUL-18:15
EnergyTransfer:Zone:HEATEDBSMT 38768.37 0.00 09-JAN-02:00 13426.63 02-JAN-19:45
Heating:EnergyTransfer 67414.61 0.00 12-JAN-15:00 108607.53 31-JAN-07:15
Heating:EnergyTransfer:Zone:HEATEDBSMT 8062.36 0.00 09-JAN-02:00 13426.63 02-JAN-19:45
Cooling:EnergyTransfer 632818.21 683.68 31-JAN-07:30 232523.45 02-JUL-18:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 30706.01 0.00 01-JAN-00:15 11518.53 16-JUL-18:45
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 104138.27 683.68 31-JAN-07:30 23413.25 29-SEP-16:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 104138.27 683.68 31-JAN-07:30 23413.25 29-SEP-16:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 26922.10 0.00 01-JAN-00:15 9061.92 29-SEP-15:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2026.46 0.00 01-JAN-00:15 4474.28 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24895.64 0.00 01-JAN-00:15 9061.92 29-SEP-15:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 35757.49 0.00 01-JAN-09:30 11803.26 16-JUL-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3461.51 0.00 01-JAN-09:30 6604.69 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 32295.98 0.00 01-JAN-00:15 11803.26 16-JUL-19:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 33120.25 0.00 01-JAN-14:15 14082.94 18-JUN-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4593.83 0.00 01-JAN-14:15 6691.99 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 28526.42 0.00 01-JAN-00:15 14082.94 18-JUN-18:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23659.15 0.00 01-JAN-15:15 8763.99 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3064.87 0.00 01-JAN-15:15 4806.13 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 20594.27 0.00 01-JAN-00:15 8763.99 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 32373.39 0.00 01-JAN-13:00 11500.94 16-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4359.83 0.00 01-JAN-13:00 6636.33 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 28013.56 0.00 01-JAN-00:15 11500.94 16-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 35364.84 0.00 01-JAN-00:15 13897.61 29-SEP-16:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2576.19 0.00 01-JAN-00:15 5335.98 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 32788.65 0.00 01-JAN-00:15 13897.61 29-SEP-16:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 26101.01 0.00 01-JAN-00:15 8475.78 16-JUL-20:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1321.26 0.00 01-JAN-00:15 3631.00 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24779.75 0.00 01-JAN-00:15 8475.78 16-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 34797.52 0.00 01-JAN-00:15 11205.10 16-JUL-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2535.62 0.00 01-JAN-00:15 5719.01 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 32261.89 0.00 01-JAN-00:15 11205.10 16-JUL-19:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 31914.06 0.00 01-JAN-14:30 13483.21 18-JUN-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3582.92 0.00 01-JAN-14:30 5862.27 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 28331.14 0.00 01-JAN-00:15 13483.21 18-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 22504.14 0.00 01-JAN-00:15 8314.52 16-JUL-21:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2122.49 0.00 01-JAN-00:15 3934.75 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 20381.65 0.00 01-JAN-00:15 8314.52 16-JUL-21:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31257.30 0.00 01-JAN-12:45 10962.92 16-JUL-19:45
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3333.95 0.00 01-JAN-12:45 5753.97 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 27923.35 0.00 01-JAN-00:15 10962.92 16-JUL-19:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 38930.96 0.00 01-JAN-13:30 13716.30 16-JUL-20:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5186.79 0.00 01-JAN-13:30 7925.48 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 33744.17 0.00 01-JAN-00:15 13716.30 16-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 40831.51 0.00 01-JAN-10:30 13750.57 16-JUL-20:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4308.96 0.00 01-JAN-10:30 7903.78 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 36522.55 0.00 01-JAN-00:15 13750.57 16-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 41776.36 0.00 01-JAN-11:45 16418.81 27-AUG-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4669.02 0.00 01-JAN-11:45 7808.83 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37107.34 0.00 01-JAN-00:15 16418.81 27-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 30153.76 0.00 01-JAN-14:30 11118.30 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3814.83 0.00 01-JAN-14:30 6076.55 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 26338.93 0.00 01-JAN-00:15 11118.30 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 32046.76 0.00 01-JAN-00:15 11050.48 02-JUL-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2871.46 0.00 01-JAN-00:15 5834.76 31-JAN-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 29175.30 0.00 01-JAN-00:15 11050.48 02-JUL-19:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 39815.60 0.00 01-JAN-14:15 16377.32 27-AUG-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5522.27 0.00 01-JAN-14:15 8012.22 31-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 34293.33 0.00 01-JAN-00:15 16377.32 27-AUG-17:15
EnergyTransfer:Plant 157885.66 431.70 21-JUL-03:00 135872.61 31-JAN-07:15
WaterSystems:EnergyTransfer 93473.99 431.70 21-JUL-03:00 31801.02 21-JAN-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 93473.99 431.70 21-JUL-03:00 31801.02 21-JAN-08:45
EnergyTransfer:HVAC 770412.80 6778.58 21-APR-07:00 264753.42 10-AUG-18:30
HeatingCoils:EnergyTransfer 63119.63 0.00 01-JAN-14:30 105837.30 31-JAN-07:15
PlantLoopHeatingDemand:HVAC 63119.63 0.00 01-JAN-14:30 105837.30 31-JAN-07:15
HeatingCoils:PlantLoopHeatingDemand 63119.63 0.00 01-JAN-14:30 105837.30 31-JAN-07:15
CoolingCoils:EnergyTransfer 707293.17 720.28 31-JAN-07:30 264753.42 10-AUG-18:30
Boilers:EnergyTransfer 64411.67 0.00 01-JAN-14:30 105882.50 31-JAN-07:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -8672.39 0.000 0.000 2872.467 2771.241 10464.601 15207.807 0.000 5509.325 77572.525 0.000 -4410.17 0.000 -5849.52 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 2026.439 -2073.25 0.000 0.000 2941.798 2771.241 10464.601 6573.151 0.000 5202.921 1612.652 0.000 -1689.55 0.000 -5007.59 -0.06
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 3461.486 -2689.53 0.000 0.000 2956.881 2771.241 10464.601 15136.209 0.000 5519.422 1152.503 0.000 -3941.92 0.000 -5224.47 -0.05
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 4593.799 -2375.61 0.000 0.000 2967.798 2771.241 10464.601 11743.508 0.000 5513.017 0.147 0.000 -4319.93 0.000 -5022.27 -185.34
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 3064.853 -1715.05 0.000 0.000 2959.736 2771.241 10464.601 2768.475 0.000 5202.290 0.020 0.000 -1809.96 0.000 -4817.06 -9.85
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 4359.803 -2332.90 0.000 0.000 2969.451 2771.241 10464.601 11387.378 0.000 5518.996 0.476 0.000 -3933.97 0.000 -5077.23 -446.71
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 2576.167 -2730.56 0.000 0.000 2943.530 2771.241 10464.601 15261.788 0.000 4033.745 2995.053 0.000 -4295.96 0.000 -3961.51 -0.05
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 1321.246 -2063.60 0.000 0.000 2928.418 2771.241 10464.601 6560.835 0.000 3723.766 2497.361 0.000 -1736.41 0.000 -3751.28 -0.07
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 2535.607 -2686.70 0.000 0.000 2946.858 2771.241 10464.601 15086.700 0.000 4037.963 2443.448 0.000 -4050.28 0.000 -3974.24 -0.45
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 3582.893 -2359.35 0.000 0.000 2957.780 2771.241 10464.601 11746.919 0.000 4035.479 1033.124 0.000 -4431.92 0.000 -3828.94 -0.10
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 2122.471 -1697.34 0.000 0.000 2947.391 2771.241 10464.601 2790.813 0.000 3724.610 1029.860 0.000 -1856.19 0.000 -3613.08 -0.18
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 3333.936 -2325.39 0.000 0.000 2961.224 2771.241 10464.601 11370.009 0.000 4037.793 872.727 0.000 -4028.23 0.000 -3859.92 -0.45
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 5186.757 -2810.14 0.000 0.000 2965.863 2771.241 10464.601 11235.910 0.000 5493.435 4771.902 0.000 -4032.92 0.000 -5112.60 -0.12
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 4308.929 -3041.51 0.000 0.000 2956.039 2771.241 10464.601 14991.389 0.000 5493.526 4776.238 0.000 -4015.41 0.000 -5223.99 -0.44
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 4668.981 -3090.21 0.000 0.000 2955.038 2771.241 10464.601 15177.557 0.000 5486.222 4998.316 0.000 -4225.66 0.000 -5188.94 -0.02
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 3814.800 -2193.45 0.000 0.000 2955.893 2771.241 10464.601 2734.463 0.000 5178.672 5129.768 0.000 -1845.84 0.000 -4864.61 -0.16
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 2871.437 -2429.65 0.000 0.000 2943.367 2771.241 10464.601 6520.278 0.000 5177.171 5129.710 0.000 -1711.45 0.000 -4991.01 -0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 5522.235 -2855.87 0.000 0.000 2963.927 2771.241 10464.601 11585.462 0.000 5488.153 4975.284 0.000 -4402.86 0.000 -5074.69 -0.02
HEATEDBSMT 0.000 0.000 8062.359 -2557.13 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 22643.655 0.000 0.000 0.000 0.000 -0.29
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7665.724 52178.723 0.000 0.000 0.000 -59844.45 -0.09
Total Facility 0.000 0.000 67414.196 -52699.66 0.000 0.000 53093.457 49882.340 188362.826 187878.651 0.000 96042.229 195813.491 0.000 -60738.65 0.000 -144287.40 -644.45


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-SEP-16:49 0.00 0.00 0.00 -2.0 0.00 0.00 139.89 434.11 1350.56 7406.00 0.00 2111.29 11982.33 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16-JUL-20:23 0.00 0.00 0.00 -0.8 0.00 0.00 423.67 902.05 1651.67 708.24 0.00 2423.01 2963.79 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16-JUL-19:11 0.00 0.00 0.00 -1.0 0.00 0.00 422.84 902.05 1689.30 2413.29 0.00 3360.43 3054.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12-JUL-18:03 0.00 0.00 0.00 -1.2 0.00 0.00 427.01 813.96 1724.99 6202.38 0.00 2532.33 2393.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 02-JUL-19:24 0.00 0.00 0.00 -0.7 0.00 0.00 422.09 902.05 1689.30 729.00 0.00 2545.55 2522.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16-JUL-19:38 0.00 0.00 0.00 -1.0 0.00 0.00 422.78 902.05 1689.30 1962.48 0.00 3005.39 3578.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-SEP-16:49 0.00 0.00 0.00 -1.2 0.00 0.00 140.17 434.11 1350.56 7398.64 0.00 1592.32 3002.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16-JUL-20:35 0.00 0.00 0.00 -0.7 0.00 0.00 424.15 902.05 1651.67 687.85 0.00 1625.44 3193.72 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-JUL-19:08 0.00 0.00 0.00 -0.9 0.00 0.00 425.04 902.05 1689.30 2463.90 0.00 2296.13 3485.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 18-JUN-19:18 0.00 0.00 0.00 -1.1 0.00 0.00 426.03 902.05 1689.30 2960.72 0.00 1729.65 5808.90 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16-JUL-21:38 0.00 0.00 0.00 -0.7 0.00 0.00 475.94 682.17 1577.18 636.91 0.00 1520.64 3452.13 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 16-JUL-19:41 0.00 0.00 0.00 -0.9 0.00 0.00 423.58 902.05 1689.30 1995.19 0.00 2097.36 3911.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 16-JUL-20:00 0.00 0.00 0.00 -1.1 0.00 0.00 418.61 902.05 1689.30 1806.48 0.00 2821.35 6105.88 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 16-JUL-20:00 0.00 0.00 0.00 -1.1 0.00 0.00 420.71 902.05 1689.30 1845.59 0.00 2835.54 6084.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -1.4 0.00 0.00 259.55 604.65 1685.13 7906.58 0.00 2613.37 3366.27 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 02-JUL-19:30 0.00 0.00 0.00 -0.9 0.00 0.00 421.21 902.05 1689.30 726.02 0.00 2544.08 4858.05 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUL-19:24 0.00 0.00 0.00 -0.9 0.00 0.00 422.67 902.05 1689.30 685.86 0.00 2542.31 4876.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -1.4 0.00 0.00 260.14 604.65 1685.13 7928.65 0.00 2619.53 3292.37 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 16-JUL-18:45 0.00 0.00 0.00 -1.0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11519.53 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 16-JUL-19:30 0.00 0.00 0.00 -19.4 0.00 0.00 7390.63 16236.84 30407.43 31591.15 0.00 48840.77 100966.57 0.00 0.00 0.00 -2789.7 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 31-JAN-07:15 0.00 0.00 4474.34 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1110.7 0.00 -3374.0 -2052.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13-DEC-22:10 0.00 0.00 8542.77 0.00 0.00 0.00 549.63 379.85 1340.18 0.00 0.00 0.00 0.00 0.00 -2191.3 0.00 -2487.3 -6133.8
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 09-MAR-09:48 0.00 0.00 27886.93 0.00 0.00 0.00 133.98 116.28 1096.02 205.52 0.00 0.00 0.00 0.00 0.00 0.00 -1029.3 -28409.4
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 30-JAN-17:21 0.00 0.00 14444.82 0.00 0.00 0.00 308.13 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -662.4 0.00 -2196.3 -14162.9
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 30-JAN-17:30 0.00 0.00 8924.42 0.00 0.00 0.00 291.10 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -1694.3 0.00 -2362.6 -7427.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 5336.13 0.00 0.00 0.00 464.79 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2752.3 0.00 -2563.8 -2083.2
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 31-JAN-07:15 0.00 0.00 3631.11 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1128.0 0.00 -2344.3 -2222.0
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17-DEC-00:05 0.00 0.00 9363.17 0.00 0.00 0.00 554.76 62.02 967.17 0.00 0.00 0.00 0.00 0.00 -2196.1 0.00 -1864.6 -6886.5
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-DEC-13:26 0.00 0.00 26347.03 0.00 0.00 0.00 140.35 116.28 1084.63 528.73 0.00 0.00 0.00 0.00 0.00 0.00 -1176.9 -27040.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 30-JAN-17:39 0.00 0.00 11126.93 0.00 0.00 0.00 303.90 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -723.7 0.00 -1544.1 -11431.8
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 30-JAN-17:48 0.00 0.00 7179.69 0.00 0.00 0.00 296.23 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -1931.2 0.00 -1774.4 -6039.0
LIVING_UNIT3_BACKROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 7925.60 0.00 0.00 0.00 464.79 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2714.5 0.00 -3601.1 -3673.2
LIVING_UNIT3_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 7903.90 0.00 0.00 0.00 464.77 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2727.8 0.00 -3601.3 -3638.0
LIVING_UNIT1_FRONTROW_TOPFLOOR 04-APR-10:35 0.00 0.00 9284.82 0.00 0.00 0.00 130.77 116.28 1089.80 2262.86 0.00 0.00 0.00 0.00 0.00 0.00 -561.2 -12323.3
LIVING_UNIT2_BACKROW_TOPFLOOR 31-JAN-08:15 0.00 0.00 6076.62 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -976.1 0.00 -3280.4 -3361.6
LIVING_UNIT2_FRONTROW_TOPFLOOR 31-JAN-07:15 0.00 0.00 5834.85 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1117.6 0.00 -3381.3 -3399.1
LIVING_UNIT1_BACKROW_TOPFLOOR 09-NOV-10:25 0.00 0.00 17205.87 0.00 0.00 0.00 132.95 116.28 1089.80 407.58 0.00 0.00 0.00 0.00 0.00 0.00 -491.0 -18461.5
HEATEDBSMT 11-JAN-00:38 0.00 0.00 26611.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -26611.1
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-07:15 -956.1 0.08 108609.43 -0.1 0.00 0.00 8321.77 6976.77 21793.53 0.00 0.00 3024.87 0.00 0.00 -39479.0 0.00 -57599.4 -50691.8



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1037.105 2.00 2.00 1.00 44.9950 1037.105 0.043 1.000 44.9950 0.04
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 376.807 2.00 2.00 1.00 44.9950 376.807 0.119 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 502.772 2.00 2.00 1.00 44.9950 502.772 0.089 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 613.763 2.00 2.00 1.00 44.9950 613.763 0.073 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 369.664 2.00 2.00 1.00 44.9950 369.664 0.122 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 482.972 2.00 2.00 1.00 44.9950 482.972 0.093 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 595.113 2.00 2.00 1.00 44.9950 595.113 0.076 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 352.077 2.00 2.00 1.00 44.9950 352.077 0.128 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 473.990 2.00 2.00 1.00 44.9950 473.990 0.095 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 585.349 2.00 2.00 1.00 44.9950 585.349 0.077 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 348.513 2.00 2.00 1.00 44.9950 348.513 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 455.630 2.00 2.00 1.00 44.9950 455.630 0.099 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 721.094 2.00 2.00 1.00 44.9950 721.094 0.062 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 476.362 2.00 2.00 1.00 44.9950 476.362 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 589.263 2.00 2.00 1.00 44.9950 589.263 0.076 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 719.969 2.00 2.00 1.00 44.9950 719.969 0.062 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 476.323 2.00 2.00 1.00 44.9950 476.323 0.094 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 587.327 2.00 2.00 1.00 44.9950 587.327 0.077 1.000 44.9950 0.08
CENTRAL SYSTEM_UNITHEATEDBSMT 501.965 0.00 0.00 1.00 44.9950 501.965 0.090 1.000 44.9950 0.09


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 87.366 2.00 2.00 1.00 44.9950 87.366 1.000 1.000 44.9950 0.52
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 124.635 2.00 2.00 1.00 44.9950 124.635 1.000 1.000 44.9950 0.36
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 124.941 2.00 2.00 1.00 44.9950 124.941 1.000 1.000 44.9950 0.36
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 89.916 2.00 2.00 1.00 44.9950 89.916 1.000 1.000 44.9950 0.50
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 124.670 2.00 2.00 1.00 44.9950 124.670 1.000 1.000 44.9950 0.36
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 105.705 2.00 2.00 1.00 44.9950 105.705 1.000 1.000 44.9950 0.43
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 75.891 2.00 2.00 1.00 44.9950 75.891 1.000 1.000 44.9950 0.59
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 111.965 2.00 2.00 1.00 44.9950 111.965 1.000 1.000 44.9950 0.40
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 112.139 2.00 2.00 1.00 44.9950 112.139 1.000 1.000 44.9950 0.40
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 76.419 2.00 2.00 1.00 44.9950 76.419 1.000 1.000 44.9950 0.59
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 111.921 2.00 2.00 1.00 44.9950 111.921 1.000 1.000 44.9950 0.40
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 148.921 2.00 2.00 1.00 44.9950 148.921 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 114.132 2.00 2.00 1.00 44.9950 114.132 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 149.668 2.00 2.00 1.00 44.9950 149.668 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 149.774 2.00 2.00 1.00 44.9950 149.774 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 114.231 2.00 2.00 1.00 44.9950 114.231 1.000 1.000 44.9950 0.39
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 149.619 2.00 2.00 1.00 44.9950 149.619 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNITHEATEDBSMT 118.951 0.00 0.00 1.00 44.9950 118.951 1.000 1.000 44.9950 0.38


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   1037.105 1037.1050 207.4210 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   376.807 376.8071 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   502.772 502.7717 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   613.763 613.7630 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   369.664 369.6641 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   482.972 482.9720 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   595.113 595.1133 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   352.077 352.0773 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   473.990 473.9900 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   585.349 585.3490 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   348.513 348.5126 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   455.630 455.6304 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   587.327 587.3273 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   589.263 589.2625 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   721.094 721.0941 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   476.323 476.3232 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   476.362 476.3617 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   719.969 719.9685 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   501.965 501.9649 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10 1037.105 1037.10 207.4210 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 376.81 376.807 376.81 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 502.77 502.772 502.77 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 613.76 613.763 613.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 369.66 369.664 369.66 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 482.97 482.972 482.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 595.11 595.113 595.11 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 352.08 352.077 352.08 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 473.99 473.990 473.99 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 585.35 585.349 585.35 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 348.51 348.513 348.51 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 455.63 455.630 455.63 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 721.09 721.094 721.09 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 476.36 476.362 476.36 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 589.26 589.263 589.26 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 719.97 719.969 719.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 476.32 476.323 476.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 587.33 587.327 587.33 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 501.96 501.965 501.96 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   87.366 87.366 87.366 44.9950 0.515 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   124.635 124.635 124.635 44.9950 0.361 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   124.941 124.941 124.941 44.9950 0.360 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   89.916 89.916 89.916 44.9950 0.500 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   124.670 124.670 124.670 44.9950 0.361 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   105.705 105.705 105.705 44.9950 0.426 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   75.891 75.891 75.891 44.9950 0.593 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   111.965 111.965 111.965 44.9950 0.402 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   112.139 112.139 112.139 44.9950 0.401 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   76.419 76.419 76.419 44.9950 0.589 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   111.921 111.921 111.921 44.9950 0.402 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   149.619 149.619 149.619 44.9950 0.301 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   149.668 149.668 149.668 44.9950 0.301 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   148.921 148.921 148.921 44.9950 0.302 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   114.231 114.231 114.231 44.9950 0.394 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   114.132 114.132 114.132 44.9950 0.394 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   149.774 149.774 149.774 44.9950 0.300 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   118.951 118.951 118.951 44.9950 0.378 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 87.37 87.366 87.37 87.37 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 124.64 124.635 124.64 124.64 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 124.94 124.941 124.94 124.94 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 89.92 89.916 89.92 89.92 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 124.67 124.670 124.67 124.67 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 105.70 105.705 105.70 105.70 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 75.89 75.891 75.89 75.89 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 111.97 111.965 111.97 111.97 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 112.14 112.139 112.14 112.14 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 76.42 76.419 76.42 76.42 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 111.92 111.921 111.92 111.92 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 148.92 148.921 148.92 148.92 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 114.13 114.132 114.13 114.13 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 149.67 149.668 149.67 149.67 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 149.77 149.774 149.77 149.77 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 114.23 114.231 114.23 114.23 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 149.62 149.619 149.62 149.62 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 118.95 118.951 118.95 118.95 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Sec1.1A-General Information

Data
Weather File ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 713.75
Number of hours cooling loads not met 148.00
Number of hours not met 861.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 805.15 130773.96 0.00 0.00
Space Cooling 55118.48 22606.66 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 12036.09 3872.28 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2144.69 112822.44 0.00 0.00
Receptacle Equipment 88303.07 15497.32 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 173073.91   2949.84   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 590946.55
Natural Gas 0.00 294983.59
Additional 0.00 0.00
Total 301503.54 885930.14


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 1.41
Fans-Interior 0.31
Service Water Heating 0.00
Receptacle Equipment 2.26
Miscellaneous 0.08
Subtotal 4.44


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.60
Service Water Heating 1.61
Miscellaneous -0.0
Subtotal 2.21


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.63
Space Heating 9.09
Space Cooling 21.24
Fans-Interior 4.64
Service Water Heating 24.21
Receptacle Equipment 34.03
Miscellaneous 1.16



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 501.96
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 376.81
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 502.77
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 613.76
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 369.66
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 482.97
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 595.11
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 352.08
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 473.99
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 585.35
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 348.51
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 455.63
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 587.33
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 589.26
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 721.09
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 476.32
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 476.36
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 719.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 376.81
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 502.77
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 613.76
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 369.66
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 482.97
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 595.11
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 352.08
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 473.99
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 585.35
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 348.51
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 455.63
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 721.09
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 476.36
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 589.26
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 719.97
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 476.32
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 587.33
CENTRAL SYSTEM_UNITHEATEDBSMT 501.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10 2.36 0.789941
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 376.81 0.932257 0.761130
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 502.77 1.25 0.758975
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 613.76 1.44 0.778794
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 369.66 0.890651 0.770002
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 482.97 1.21 0.757441
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 595.11 1.40 0.777991
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 352.08 0.864440 0.763663
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 473.99 1.19 0.756851
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 585.35 1.37 0.778758
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 348.51 0.839194 0.770202
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 455.63 1.15 0.755281
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 721.09 1.67 0.783313
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 476.36 1.13 0.776831
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 589.26 1.43 0.767612
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 719.97 1.67 0.783272
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 476.32 1.12 0.776828
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 587.33 1.43 0.767504
DX COOLING COIL_UNITHEATEDBSMT 501.96 1.23 0.763167
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10 1037.10 1037.10 2.36 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 376.81 376.81 376.81 0.932257 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 502.77 502.77 502.77 1.25 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 613.76 613.76 613.76 1.44 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 369.66 369.66 369.66 0.890651 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 482.97 482.97 482.97 1.21 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 595.11 595.11 595.11 1.40 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 352.08 352.08 352.08 0.864440 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 473.99 473.99 473.99 1.19 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 585.35 585.35 585.35 1.37 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 348.51 348.51 348.51 0.839194 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 455.63 455.63 455.63 1.15 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 721.09 721.09 721.09 1.67 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 476.36 476.36 476.36 1.13 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 589.26 589.26 589.26 1.43 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 719.97 719.97 719.97 1.67 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 476.32 476.32 476.32 1.12 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 587.33 587.33 587.33 1.43 1.00
ACANDF_UNITHEATEDBSMT 501.96 501.96 501.96 1.23 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 55502.60 5.60 794.85
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 21160.43 2.14 298.43
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 27713.07 2.80 393.26
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 33486.60 3.38 476.82
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 20788.88 2.10 293.04
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 26683.13 2.69 378.35
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 32515.66 3.28 462.72
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 19873.63 2.01 279.75
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 26215.29 2.65 371.53
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 32007.78 3.23 455.36
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 19688.21 1.99 277.06
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 25260.28 2.55 357.71
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 39069.85 3.94 557.58
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 26339.09 2.66 373.37
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 32212.24 3.25 458.34
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 39011.30 3.94 556.73
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 26337.09 2.66 373.34
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 32111.57 3.24 456.89
MAIN WATER HEATING COIL_UNITHEATEDBSMT 27668.64 2.79 392.36
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 1037.10
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 376.81
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 502.77
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 613.76
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 369.66
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 482.97
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 595.11
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 352.08
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 473.99
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 585.35
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 348.51
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 455.63
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 721.09
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 476.36
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 589.26
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 719.97
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 476.32
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 587.33
SUPPLY FAN_UNITHEATEDBSMT 501.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 7.60 142.60
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 7.60
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 565746.40 56.89
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:32:24

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 744.000 87.876 0.000 0.000 87.876
February 672.000 92.629 0.000 0.000 92.629
March 744.000 111.117 0.000 0.000 111.117
April 720.000 139.388 0.000 0.000 139.388
May 744.000 165.588 0.000 0.000 165.588
June 720.000 197.299 0.000 0.000 197.299
July 744.000 220.617 0.000 0.000 220.617
August 744.000 209.651 0.000 0.000 209.651
September 720.000 180.784 0.000 0.000 180.784
October 744.000 155.834 0.000 0.000 155.834
November 720.000 113.895 0.000 0.000 113.895
December 744.000 81.947 0.000 0.000 81.947
           
Annual Sum or Average 8760.000 1756.625 0.000 0.000 1756.625
Minimum of Months 672.000 81.947 0.000 0.000 81.947
Maximum of Months 744.000 220.617 0.000 0.000 220.617



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 223.700 6.592 311.767 2.347 8.939
February 269.883 11.208 216.542 1.617 12.825
March 340.501 13.042 161.885 1.070 14.111
April 534.175 27.250 56.125 0.340 27.591
May 700.824 38.493 0.000 0.000 38.493
June 720.000 61.146 0.000 0.000 61.146
July 744.000 75.624 0.000 0.000 75.624
August 744.000 68.827 0.000 0.000 68.827
September 720.000 53.719 0.000 0.000 53.719
October 676.097 38.145 13.875 0.029 38.174
November 416.168 16.766 92.875 0.390 17.156
December 197.148 5.794 352.315 2.994 8.787
           
Annual Sum or Average 6286.496 416.606 1205.384 8.787 425.393
Minimum of Months 197.148 5.794 0.000 0.000 8.787
Maximum of Months 744.000 75.624 352.315 2.994 75.624



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 185.170 6.294 296.642 7.540 24.806
February 258.098 13.095 201.208 4.927 26.502
March 352.197 16.737 140.150 3.283 29.172
April 543.265 37.096 47.125 0.954 40.442
May 693.683 52.426 0.000 0.000 52.959
June 720.000 82.250 0.000 0.000 82.250
July 744.000 99.191 0.000 0.000 99.191
August 744.000 89.678 0.000 0.000 89.678
September 720.000 68.343 0.000 0.000 68.343
October 653.934 46.153 10.750 0.160 49.165
November 396.752 18.422 83.250 1.480 30.785
December 168.550 5.393 338.425 9.316 25.258
           
Annual Sum or Average 6179.648 535.078 1117.550 27.660 618.551
Minimum of Months 168.550 5.393 0.000 0.000 24.806
Maximum of Months 744.000 99.191 338.425 9.316 99.191



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 69.212 1.765 397.680 9.463 29.471
February 171.423 7.621 281.374 6.043 25.684
March 262.236 12.851 224.247 3.829 26.228
April 485.016 35.052 70.568 1.156 39.364
May 676.990 54.678 7.000 0.020 54.775
June 720.000 87.595 0.000 0.000 87.595
July 744.000 104.824 0.000 0.000 104.824
August 744.000 92.709 0.000 0.000 92.709
September 720.000 65.648 0.000 0.000 65.648
October 616.736 37.584 35.500 0.342 39.907
November 269.754 8.882 189.700 2.373 20.694
December 53.150 1.021 445.587 11.701 33.732
           
Annual Sum or Average 5532.518 510.230 1651.657 34.926 620.631
Minimum of Months 53.150 1.021 0.000 0.000 20.694
Maximum of Months 744.000 104.824 445.587 11.701 104.824



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 35.602 0.343 461.471 4.563 8.945
February 156.788 4.154 298.721 2.854 8.517
March 255.599 6.536 198.730 1.620 9.449
April 513.841 23.389 63.808 0.499 23.953
May 699.923 38.355 0.000 0.000 38.355
June 720.000 62.579 0.000 0.000 62.579
July 744.000 76.283 0.000 0.000 76.283
August 744.000 67.168 0.000 0.000 67.168
September 720.000 47.452 0.000 0.000 47.452
October 655.183 27.948 25.042 0.076 28.079
November 276.287 4.811 158.657 0.810 5.844
December 14.317 0.099 528.163 5.820 10.117
           
Annual Sum or Average 5535.540 359.117 1734.593 16.242 386.741
Minimum of Months 14.317 0.099 0.000 0.000 5.844
Maximum of Months 744.000 76.283 528.163 5.820 76.283



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 35.970 0.411 472.709 10.034 19.580
February 178.019 5.828 280.712 5.993 18.638
March 306.047 9.807 164.224 3.555 21.587
April 532.802 32.517 49.125 0.981 35.658
May 693.850 51.010 0.000 0.000 51.542
June 720.000 81.637 0.000 0.000 81.637
July 744.000 97.681 0.000 0.000 97.681
August 744.000 86.211 0.000 0.000 86.211
September 720.000 61.060 0.000 0.000 61.060
October 644.494 35.524 16.250 0.209 37.919
November 295.697 6.036 111.083 1.785 17.072
December 13.500 0.098 547.940 12.515 21.160
           
Annual Sum or Average 5628.379 467.820 1642.043 35.072 549.745
Minimum of Months 13.500 0.098 0.000 0.000 17.072
Maximum of Months 744.000 97.681 547.940 12.515 97.681



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 229.324 9.998 325.393 5.537 15.635
February 269.413 16.218 225.225 3.692 21.123
March 347.365 20.981 145.557 2.357 28.039
April 525.956 40.146 49.538 0.686 42.969
May 690.983 55.304 0.083 0.000 55.304
June 720.000 85.099 0.000 0.000 85.099
July 744.000 101.229 0.000 0.000 101.229
August 744.000 92.713 0.000 0.000 92.713
September 720.000 72.172 0.000 0.000 72.172
October 655.823 48.555 22.375 0.157 49.746
November 398.349 21.858 117.958 1.160 24.472
December 205.746 8.677 369.667 6.996 15.673
           
Annual Sum or Average 6250.960 572.950 1255.796 20.584 604.175
Minimum of Months 205.746 8.677 0.000 0.000 15.635
Maximum of Months 744.000 101.229 369.667 6.996 101.229



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 259.941 7.502 252.558 1.838 9.369
February 304.578 12.378 176.833 1.307 13.684
March 384.730 14.483 119.858 0.878 15.468
April 579.792 28.132 46.125 0.267 28.441
May 713.115 38.287 0.000 0.000 38.287
June 720.000 58.828 0.000 0.000 58.828
July 744.000 71.534 0.000 0.000 71.534
August 744.000 66.048 0.000 0.000 66.048
September 720.000 53.005 0.000 0.000 53.005
October 683.862 38.461 4.875 0.009 38.470
November 454.418 18.173 58.625 0.226 18.399
December 233.333 6.675 304.396 2.490 9.165
           
Annual Sum or Average 6541.770 413.508 963.271 7.015 420.700
Minimum of Months 233.333 6.675 0.000 0.000 9.165
Maximum of Months 744.000 71.534 304.396 2.490 71.534



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 210.486 6.813 238.042 5.380 26.007
February 282.653 13.964 163.063 3.568 26.209
March 386.422 17.965 106.042 2.363 28.079
April 570.280 37.674 39.000 0.668 40.053
May 705.506 51.827 0.000 0.000 51.845
June 720.000 79.564 0.000 0.000 79.564
July 744.000 94.517 0.000 0.000 94.517
August 744.000 86.379 0.000 0.000 86.379
September 720.000 67.260 0.000 0.000 67.260
October 667.407 46.016 3.500 0.050 48.954
November 429.741 19.390 51.250 0.821 29.324
December 190.515 5.914 290.625 7.039 24.403
           
Annual Sum or Average 6371.012 527.283 891.521 19.889 602.593
Minimum of Months 190.515 5.914 0.000 0.000 24.403
Maximum of Months 744.000 94.517 290.625 7.039 94.517



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 78.365 1.782 358.002 7.385 27.283
February 189.442 8.201 246.126 4.675 25.028
March 290.043 13.869 174.605 2.843 24.526
April 512.627 35.668 56.921 0.845 39.057
May 689.275 54.348 1.000 0.001 54.435
June 720.000 85.314 0.000 0.000 85.314
July 744.000 100.693 0.000 0.000 100.693
August 744.000 89.970 0.000 0.000 89.970
September 720.000 65.105 0.000 0.000 65.105
October 632.045 37.779 30.513 0.229 40.214
November 304.970 9.496 150.126 1.605 20.661
December 61.246 1.025 408.586 9.394 32.189
           
Annual Sum or Average 5686.014 503.249 1425.879 26.976 604.474
Minimum of Months 61.246 1.025 0.000 0.000 20.661
Maximum of Months 744.000 100.693 408.586 9.394 100.693



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 53.744 0.533 405.703 3.158 6.542
February 191.212 4.955 255.675 1.950 8.148
March 300.020 7.849 154.256 1.052 9.580
April 562.983 24.337 53.423 0.317 24.702
May 713.149 38.020 0.000 0.000 38.020
June 720.000 59.975 0.000 0.000 59.975
July 744.000 71.964 0.000 0.000 71.964
August 744.000 64.213 0.000 0.000 64.213
September 720.000 46.683 0.000 0.000 46.683
October 661.804 28.257 15.380 0.032 28.320
November 318.925 5.927 103.667 0.435 6.531
December 27.367 0.198 482.883 4.215 7.252
           
Annual Sum or Average 5757.204 352.911 1470.987 11.158 371.931
Minimum of Months 27.367 0.198 0.000 0.000 6.531
Maximum of Months 744.000 71.964 482.883 4.215 71.964



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 45.529 0.517 404.033 7.613 20.563
February 196.580 6.556 237.855 4.492 18.515
March 337.257 11.053 124.300 2.553 20.574
April 561.137 33.296 40.750 0.692 35.547
May 705.756 50.490 0.000 0.000 50.508
June 720.000 78.985 0.000 0.000 78.985
July 744.000 93.096 0.000 0.000 93.096
August 744.000 83.052 0.000 0.000 83.052
September 720.000 60.209 0.000 0.000 60.209
October 657.458 35.594 6.125 0.075 38.481
November 330.894 6.909 68.458 1.024 17.301
December 19.217 0.155 489.438 9.850 21.187
           
Annual Sum or Average 5781.827 459.913 1370.960 26.299 538.018
Minimum of Months 19.217 0.155 0.000 0.000 17.301
Maximum of Months 744.000 93.096 489.438 9.850 93.096



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 184.790 8.849 388.833 11.699 22.221
February 239.942 16.591 257.363 7.629 29.891
March 313.652 22.570 168.028 4.751 43.882
April 496.782 46.030 57.028 1.465 53.355
May 668.784 64.969 2.219 0.011 66.694
June 720.000 102.610 0.000 0.000 102.610
July 744.000 122.796 0.000 0.000 122.796
August 744.000 110.260 0.000 0.000 110.260
September 720.000 83.154 0.000 0.000 83.154
October 619.337 53.023 24.750 0.445 57.400
November 349.718 21.576 132.542 2.886 36.113
December 160.190 7.331 429.288 14.175 22.171
           
Annual Sum or Average 5961.194 659.760 1460.051 43.061 750.547
Minimum of Months 160.190 7.331 0.000 0.000 22.171
Maximum of Months 744.000 122.796 429.288 14.175 122.796



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 197.235 6.621 346.155 4.330 11.439
February 259.165 13.031 242.361 2.923 15.955
March 335.035 16.442 180.941 1.951 18.542
April 528.207 34.467 61.427 0.632 35.121
May 690.823 48.551 1.821 0.002 48.553
June 720.000 77.297 0.000 0.000 77.297
July 744.000 93.939 0.000 0.000 93.939
August 744.000 84.546 0.000 0.000 84.546
September 720.000 64.951 0.000 0.000 64.951
October 656.334 43.613 30.000 0.138 43.750
November 396.635 18.180 132.625 0.892 19.072
December 177.140 5.520 381.500 5.405 10.935
           
Annual Sum or Average 6168.574 507.158 1376.831 16.272 524.101
Minimum of Months 177.140 5.520 0.000 0.000 10.935
Maximum of Months 744.000 93.939 381.500 5.405 93.939



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 167.587 6.115 333.078 9.102 25.417
February 248.153 14.501 225.600 5.897 27.691
March 344.820 19.519 153.524 3.851 32.375
April 541.776 43.563 51.500 1.138 46.990
May 689.948 61.689 1.375 0.007 62.897
June 720.000 97.573 0.000 0.000 97.573
July 744.000 116.524 0.000 0.000 116.524
August 744.000 104.481 0.000 0.000 104.481
September 719.750 78.792 0.000 0.000 78.792
October 640.432 50.882 24.250 0.338 53.087
November 383.516 19.248 115.125 2.066 30.255
December 148.324 4.953 369.583 11.099 26.511
           
Annual Sum or Average 6092.306 617.840 1274.035 33.498 702.594
Minimum of Months 148.324 4.953 0.000 0.000 25.417
Maximum of Months 744.000 116.524 369.583 11.099 116.524



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 92.979 2.644 404.183 11.516 31.981
February 189.040 10.753 277.290 7.260 30.919
March 285.065 18.394 216.855 4.501 35.593
April 492.061 44.047 68.350 1.381 49.781
May 670.504 64.967 9.089 0.047 65.415
June 720.000 103.235 0.000 0.000 103.235
July 744.000 122.950 0.000 0.000 122.950
August 744.000 109.291 0.000 0.000 109.291
September 719.750 79.349 0.000 0.000 79.349
October 601.132 45.187 39.946 0.531 48.361
November 284.425 11.973 193.984 3.062 27.684
December 66.504 1.611 444.821 14.014 38.007
           
Annual Sum or Average 5609.461 614.401 1654.519 42.313 742.567
Minimum of Months 66.504 1.611 0.000 0.000 27.684
Maximum of Months 744.000 122.950 444.821 14.014 122.950



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 62.402 1.018 452.964 5.998 9.460
February 188.001 7.253 298.527 3.689 11.643
March 294.299 12.210 202.076 2.141 14.890
April 523.086 32.528 64.448 0.666 33.202
May 690.836 48.602 1.738 0.002 48.604
June 720.000 77.974 0.000 0.000 77.974
July 744.000 94.141 0.000 0.000 94.141
August 744.000 83.640 0.000 0.000 83.640
September 720.000 61.165 0.000 0.000 61.165
October 637.860 35.603 38.462 0.199 35.873
November 306.149 8.022 181.796 1.303 9.575
December 39.373 0.472 517.318 7.523 10.650
           
Annual Sum or Average 5670.006 462.627 1757.329 21.522 490.816
Minimum of Months 39.373 0.472 0.000 0.000 9.460
Maximum of Months 744.000 94.141 517.318 7.523 94.141



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 56.298 1.043 458.467 11.532 22.156
February 197.052 8.891 283.015 6.893 21.859
March 319.321 15.375 167.496 4.039 28.658
April 537.250 41.691 53.325 1.160 45.120
May 690.046 61.656 1.292 0.006 62.879
June 720.000 98.066 0.000 0.000 98.066
July 744.000 116.550 0.000 0.000 116.550
August 744.000 103.531 0.000 0.000 103.531
September 719.750 75.237 0.000 0.000 75.237
October 628.959 43.262 28.250 0.378 45.387
November 308.086 9.168 143.417 2.421 20.557
December 35.896 0.461 528.400 14.252 23.071
           
Annual Sum or Average 5700.657 574.930 1663.662 40.682 663.070
Minimum of Months 35.896 0.461 0.000 0.000 20.557
Maximum of Months 744.000 116.550 528.400 14.252 116.550



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 563.984 16.786 49.645
February 0.000 0.000 477.978 10.255 40.144
March 0.000 0.000 304.428 4.047 38.110
April 18.307 0.100 34.792 0.194 0.294
May 742.625 46.784 0.000 0.000 46.784
June 720.000 97.506 0.000 0.000 97.506
July 744.000 113.103 0.000 0.000 113.103
August 744.000 103.620 0.000 0.000 103.620
September 720.000 81.684 0.000 0.000 81.684
October 744.000 45.239 0.000 0.000 45.239
November 0.500 0.011 183.625 1.167 4.839
December 0.000 0.000 608.346 17.307 41.858
           
Annual Sum or Average 4433.432 488.047 2173.152 49.755 662.824
Minimum of Months 0.000 0.000 0.000 0.000 0.294
Maximum of Months 744.000 113.103 608.346 17.307 113.103



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.66
February 0.00 0.00 0.77
March 0.00 0.00 0.82
April 0.00 0.00 1.03
May 0.00 0.00 1.18
June 0.00 0.00 1.42
July 0.00 0.00 1.56
August 0.00 0.00 1.49
September 0.00 0.00 1.34
October 0.00 0.00 1.14
November 0.00 0.00 0.88
December 0.00 0.00 0.62
       
Annual Sum or Average 0.00 0.00 1.08
Minimum of Months 0.00 0.00 0.62
Maximum of Months 0.00 0.00 1.56



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.10
March 0.00 0.00 0.10
April 0.00 0.00 0.21
May 0.00 0.00 0.29
June 0.00 0.00 0.47
July 0.00 0.00 0.58
August 0.00 0.00 0.53
September 0.00 0.00 0.42
October 0.00 0.00 0.30
November 0.00 0.00 0.13
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.11
March 0.00 0.00 0.13
April 0.00 0.00 0.29
May 0.00 0.00 0.39
June 0.00 0.00 0.64
July 0.00 0.00 0.76
August 0.00 0.00 0.69
September 0.00 0.00 0.54
October 0.00 0.00 0.36
November 0.00 0.00 0.15
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.25
May 0.00 0.00 0.38
June 0.00 0.00 0.63
July 0.00 0.00 0.75
August 0.00 0.00 0.66
September 0.00 0.00 0.48
October 0.00 0.00 0.27
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.75



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.17
May 0.00 0.00 0.28
June 0.00 0.00 0.47
July 0.00 0.00 0.57
August 0.00 0.00 0.51
September 0.00 0.00 0.36
October 0.00 0.00 0.21
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.25
May 0.00 0.00 0.38
June 0.00 0.00 0.64
July 0.00 0.00 0.76
August 0.00 0.00 0.67
September 0.00 0.00 0.48
October 0.00 0.00 0.27
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.76



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.13
March 0.00 0.00 0.15
April 0.00 0.00 0.29
May 0.00 0.00 0.39
June 0.00 0.00 0.61
July 0.00 0.00 0.72
August 0.00 0.00 0.67
September 0.00 0.00 0.54
October 0.00 0.00 0.35
November 0.00 0.00 0.17
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.35
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.72



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.11
March 0.00 0.00 0.11
April 0.00 0.00 0.22
May 0.00 0.00 0.28
June 0.00 0.00 0.45
July 0.00 0.00 0.55
August 0.00 0.00 0.51
September 0.00 0.00 0.42
October 0.00 0.00 0.30
November 0.00 0.00 0.15
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.55



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.12
March 0.00 0.00 0.14
April 0.00 0.00 0.29
May 0.00 0.00 0.39
June 0.00 0.00 0.62
July 0.00 0.00 0.73
August 0.00 0.00 0.67
September 0.00 0.00 0.54
October 0.00 0.00 0.36
November 0.00 0.00 0.16
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.34
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.73



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.10
April 0.00 0.00 0.26
May 0.00 0.00 0.38
June 0.00 0.00 0.62
July 0.00 0.00 0.72
August 0.00 0.00 0.64
September 0.00 0.00 0.48
October 0.00 0.00 0.27
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.72



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.04
March 0.00 0.00 0.06
April 0.00 0.00 0.18
May 0.00 0.00 0.28
June 0.00 0.00 0.45
July 0.00 0.00 0.54
August 0.00 0.00 0.48
September 0.00 0.00 0.36
October 0.00 0.00 0.21
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.54



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.06
March 0.00 0.00 0.08
April 0.00 0.00 0.26
May 0.00 0.00 0.38
June 0.00 0.00 0.62
July 0.00 0.00 0.72
August 0.00 0.00 0.65
September 0.00 0.00 0.48
October 0.00 0.00 0.27
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.30
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.72



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.13
March 0.00 0.00 0.16
April 0.00 0.00 0.33
May 0.00 0.00 0.45
June 0.00 0.00 0.73
July 0.00 0.00 0.86
August 0.00 0.00 0.78
September 0.00 0.00 0.61
October 0.00 0.00 0.38
November 0.00 0.00 0.16
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.86



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.11
March 0.00 0.00 0.12
April 0.00 0.00 0.25
May 0.00 0.00 0.35
June 0.00 0.00 0.57
July 0.00 0.00 0.69
August 0.00 0.00 0.62
September 0.00 0.00 0.49
October 0.00 0.00 0.32
November 0.00 0.00 0.14
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.12
March 0.00 0.00 0.14
April 0.00 0.00 0.33
May 0.00 0.00 0.45
June 0.00 0.00 0.74
July 0.00 0.00 0.87
August 0.00 0.00 0.78
September 0.00 0.00 0.61
October 0.00 0.00 0.38
November 0.00 0.00 0.15
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.39
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.87



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.08
March 0.00 0.00 0.13
April 0.00 0.00 0.32
May 0.00 0.00 0.45
June 0.00 0.00 0.74
July 0.00 0.00 0.87
August 0.00 0.00 0.77
September 0.00 0.00 0.57
October 0.00 0.00 0.32
November 0.00 0.00 0.09
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.37
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.87



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.24
May 0.00 0.00 0.35
June 0.00 0.00 0.57
July 0.00 0.00 0.69
August 0.00 0.00 0.61
September 0.00 0.00 0.46
October 0.00 0.00 0.26
November 0.00 0.00 0.06
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.28
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.07
March 0.00 0.00 0.11
April 0.00 0.00 0.31
May 0.00 0.00 0.45
June 0.00 0.00 0.74
July 0.00 0.00 0.87
August 0.00 0.00 0.78
September 0.00 0.00 0.58
October 0.00 0.00 0.32
November 0.00 0.00 0.07
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.36
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.87



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.34
June 0.00 0.00 0.75
July 0.00 0.00 0.84
August 0.00 0.00 0.77
September 0.00 0.00 0.63
October 0.00 0.00 0.33
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.31
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:32:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1419.34 1056.74
February 0.00 0.00 1390.69 935.21
March 0.00 0.00 1284.53 956.37
April 0.00 0.00 1123.43 809.45
May 0.00 0.00 950.96 708.02
June 0.00 0.00 815.92 587.88
July 0.00 0.00 756.96 563.57
August 0.00 0.00 782.20 582.37
September 0.00 0.00 896.03 645.60
October 0.00 0.00 1058.31 787.94
November 0.00 0.00 1228.51 885.15
December 0.00 0.00 1361.48 1013.66
         
Annual Sum or Average 0.00 0.00 1087.35 9531.96
Minimum of Months 0.00 0.00 756.96 563.57
Maximum of Months 0.00 0.00 1419.34 1056.74