Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27
Tabular Output Report in Format: HTML
Building: MF+CZ2BWH+USA_AZ_Phoenix-Sky.Harbor.Intl.AP.722780+oilfurnace+slab+IECC_2009
Environment: ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780
Simulation Timestamp: 2019-02-14 08:28:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 864572.67 | 27.70 | 40.01 |
Net Site Energy | 864572.67 | 27.70 | 40.01 |
Total Source Energy | 2142485.54 | 68.65 | 99.14 |
Net Source Energy | 2142485.54 | 68.65 | 99.14 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 31210.78 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 71472.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 178352.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 38625.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 214469.31 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 578631.19 | 285941.48 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 71472.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 178352.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 38625.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 214469.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.04 | 13.23 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 26.78 | 13.23 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 6.95 | 9.16 | 0.00 | 0.00 | 0.00 | 13.45 |
Other | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 18.54 | 9.16 | 0.00 | 0.00 | 0.00 | 13.45 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 578631.188 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 578631.188 | 100.00 |
Total On-Site and Utility Electric Sources | 578631.188 | 100.00 |
Total Electricity End Uses | 578631.188 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 715.50 |
Time Setpoint Not Met During Occupied Cooling | 146.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 211.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:27 |
RunPeriod | ANNUAL |
Weather File | Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Latitude [deg] | 33.45 |
Longitude [deg] | -112.0 |
Elevation [ft] | 1105.70 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 31210.78 | 267087.66 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.5202 | 866.97 | 2.0143 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 2.9092 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 16-JUL-18:15 | 31-JAN-07:30 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 121.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 73.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.79 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 155.80 | 235.78 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 121.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 73.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 77475.83 | 0.00 | 0.00 | 0.00 |
Cooling | 564843.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 122327.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 232484.74 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1832524.97 | 309960.56 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 3.59 | 0.00 | 0.00 | 0.00 |
Cooling | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.76 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84.80 | 14.34 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 3.59 | 0.00 | 0.00 | 0.00 |
Cooling | 26.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.76 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 84.80 | 14.34 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 38.66 | 0.00 | 38.66 | Wetbulb [F] | 334.66 | 100.00 |
PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 110.12 | 21.60 | 69.98 | Wetbulb [F] | 807.13 | 260.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.065 | 0.070 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.651 | 0.260 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.651 | 0.260 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.651 | 0.260 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.651 | 0.260 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.651 | 0.260 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.419 | 0.650 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 537055.83 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 28245.27 | 22310.57 | 5934.70 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11121.55 | 8461.70 | 2659.85 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14955.51 | 11347.91 | 3607.60 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 17222.83 | 13410.62 | 3812.21 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10623.11 | 8176.76 | 2446.35 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14432.36 | 10928.65 | 3503.71 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 16803.69 | 13072.91 | 3730.78 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10366.87 | 7916.50 | 2450.37 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14251.48 | 10785.99 | 3465.49 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 16491.35 | 12842.56 | 3648.78 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10063.84 | 7750.89 | 2312.95 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13765.48 | 10396.54 | 3368.94 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 20060.11 | 15713.34 | 4346.77 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13500.06 | 10487.23 | 3012.82 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17157.29 | 13170.13 | 3987.17 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 20031.12 | 15689.81 | 4341.31 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13499.07 | 10486.43 | 3012.64 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17106.44 | 13129.24 | 3977.20 | 0.77 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.2 | 3.28 | 11.18 | 11.83 | 11.36 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9 | 3.33 | 11.36 | 12.04 | 11.66 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 1.2 | 3.33 | 11.38 | 12.05 | 11.68 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.4 | 3.30 | 11.25 | 11.91 | 11.47 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.8 | 3.31 | 11.30 | 11.98 | 11.57 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 1.2 | 3.34 | 11.39 | 12.07 | 11.70 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.30 | 11.25 | 11.92 | 11.48 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.8 | 3.32 | 11.34 | 12.02 | 11.63 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 1.1 | 3.34 | 11.39 | 12.07 | 11.70 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.3 | 3.30 | 11.25 | 11.91 | 11.47 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.8 | 3.31 | 11.30 | 11.97 | 11.56 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 1.1 | 3.34 | 11.40 | 12.08 | 11.72 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.6 | 3.29 | 11.22 | 11.88 | 11.43 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 1.1 | 3.30 | 11.26 | 11.93 | 11.49 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.4 | 3.32 | 11.32 | 11.99 | 11.59 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.6 | 3.29 | 11.22 | 11.88 | 11.43 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 1.1 | 3.30 | 11.26 | 11.93 | 11.49 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.4 | 3.32 | 11.32 | 11.99 | 11.59 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 55353.46 | 59887.82 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 21028.37 | 22241.98 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 27576.54 | 29430.96 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 33337.56 | 35754.53 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 20656.29 | 21833.04 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 26548.09 | 28301.88 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 32503.16 | 34836.76 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 19860.72 | 20957.40 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 26204.08 | 27922.22 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 31995.16 | 34278.76 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 19674.97 | 20753.28 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 25248.88 | 26873.54 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 39068.69 | 42042.08 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 26337.78 | 28071.10 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 32211.18 | 34516.66 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 39010.13 | 41977.76 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 26335.76 | 28068.88 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 32110.50 | 34406.17 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 1034.24 | 390.11 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 374.27 | 141.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 500.15 | 188.65 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 610.90 | 230.43 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 367.12 | 138.47 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 480.38 | 181.19 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 594.87 | 224.38 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 351.83 | 132.71 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 473.77 | 178.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 585.11 | 220.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 348.26 | 131.36 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 455.41 | 171.78 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 721.07 | 271.98 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 476.34 | 179.67 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 589.24 | 222.26 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 719.95 | 271.56 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 476.30 | 179.66 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 587.31 | 221.53 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 54.005098 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23344.50 | 23344.50 | 19.44 | 1034.238 | 1034.238 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 74.98 | 74.98 | 0.00801 | 106.56 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8447.86 | 8447.86 | 7.04 | 374.268 | 374.268 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00804 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11289.33 | 11289.33 | 9.40 | 500.147 | 500.147 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00796 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13788.99 | 13788.99 | 11.49 | 610.898 | 610.898 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00803 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8286.35 | 8286.35 | 6.90 | 367.115 | 367.115 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00811 | 103.32 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10843.05 | 10843.05 | 9.03 | 480.376 | 480.376 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00796 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13427.21 | 13427.21 | 11.18 | 594.873 | 594.873 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00806 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7941.29 | 7941.29 | 6.61 | 351.829 | 351.829 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00815 | 104.13 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10693.90 | 10693.90 | 8.91 | 473.775 | 473.775 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00800 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13206.74 | 13206.74 | 11.00 | 585.106 | 585.106 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00807 | 105.48 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7860.67 | 7860.67 | 6.55 | 348.258 | 348.258 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00818 | 101.70 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10279.41 | 10279.41 | 8.56 | 455.411 | 455.411 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 74.98 | 74.98 | 0.00800 | 110.12 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 13256.64 | 13256.64 | 11.04 | 587.307 | 587.307 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 74.98 | 74.98 | 0.00797 | 109.15 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 13300.33 | 13300.33 | 11.08 | 589.242 | 589.242 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:45:00 | 74.98 | 74.98 | 0.00797 | 109.15 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 16275.80 | 16275.80 | 13.56 | 721.072 | 721.072 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00802 | 106.02 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 10750.77 | 10750.77 | 8.95 | 476.298 | 476.298 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00808 | 104.13 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 10751.65 | 10751.65 | 8.96 | 476.336 | 476.336 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00808 | 104.13 | 0.00720 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 16250.39 | 16250.39 | 13.54 | 719.946 | 719.946 | PHOENIX SKY HARBOR INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00802 | 106.02 | 0.00720 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 38.66 | 0.00513 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4597.87 | 4597.87 | 3.83 | 87.104 | 87.104 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00685 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6561.01 | 6561.01 | 5.46 | 124.293 | 124.293 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6577.10 | 6577.10 | 5.48 | 124.598 | 124.598 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4731.66 | 4731.66 | 3.94 | 89.638 | 89.638 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00687 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6562.85 | 6562.85 | 5.47 | 124.328 | 124.328 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00701 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5578.40 | 5578.40 | 4.65 | 105.681 | 105.681 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00716 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4003.97 | 4003.97 | 3.34 | 75.855 | 75.855 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00706 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5908.03 | 5908.03 | 4.92 | 111.926 | 111.926 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00719 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5917.17 | 5917.17 | 4.93 | 112.099 | 112.099 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00719 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4031.80 | 4031.80 | 3.36 | 76.382 | 76.382 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00706 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5905.71 | 5905.71 | 4.92 | 111.882 | 111.882 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00719 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7897.65 | 7897.65 | 6.58 | 149.614 | 149.614 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7900.27 | 7900.27 | 6.58 | 149.663 | 149.663 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7860.92 | 7860.92 | 6.55 | 148.918 | 148.918 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6029.54 | 6029.54 | 5.02 | 114.225 | 114.225 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00700 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6024.34 | 6024.34 | 5.02 | 114.127 | 114.127 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00700 | 38.66 | 0.00513 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7905.84 | 7905.84 | 6.59 | 149.769 | 149.769 | PHOENIX SKY HARBOR INTL AP ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00711 | 38.66 | 0.00513 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 | 1034.24 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 | 374.27 | 87.10 | 87.10 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 | 500.15 | 124.29 | 124.29 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 | 610.90 | 124.60 | 124.60 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 | 367.12 | 89.64 | 89.64 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 | 480.38 | 124.33 | 124.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 | 594.87 | 105.68 | 105.68 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 | 351.83 | 75.85 | 75.85 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 | 473.77 | 111.93 | 111.93 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 | 585.11 | 112.10 | 112.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 | 348.26 | 76.38 | 76.38 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 | 455.41 | 111.88 | 111.88 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 721.07 | 721.07 | 148.92 | 148.92 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 476.34 | 476.34 | 114.13 | 114.13 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 589.24 | 589.24 | 149.66 | 149.66 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 719.95 | 719.95 | 149.77 | 149.77 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 476.30 | 476.30 | 114.23 | 114.23 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 587.31 | 587.31 | 149.61 | 149.61 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2925.75 | 3451.50 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2409.75 | 3444.75 | 57.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3135.00 | 3321.00 | 60.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2916.00 | 4122.25 | 143.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2101.50 | 4347.75 | 65.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2875.75 | 3994.75 | 63.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3458.50 | 3188.50 | 44.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2683.25 | 3061.50 | 27.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3397.50 | 3038.75 | 35.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3133.75 | 3832.25 | 99.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2353.50 | 3937.50 | 33.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3072.00 | 3690.75 | 37.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3389.75 | 3671.75 | 72.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3626.25 | 3233.25 | 63.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3581.75 | 3430.50 | 85.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2810.00 | 3861.25 | 53.25 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3023.00 | 3307.25 | 50.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3394.00 | 3831.75 | 136.50 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4137.25 | 4609.00 | 211.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 98.00 | 0.00 | 98.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 42.00 | 0.00 | 42.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 108.25 | 2.50 | 108.25 | 2.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 224.50 | 78.00 | 224.50 | 78.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18.50 | 62.00 | 18.50 | 62.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 50.25 | 9.25 | 50.25 | 9.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 14.00 | 63.75 | 14.00 | 63.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 35.00 | 0.00 | 35.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 147.25 | 0.25 | 147.25 | 0.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 216.75 | 68.75 | 216.75 | 68.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8.50 | 43.75 | 8.50 | 43.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 115.50 | 2.50 | 115.50 | 2.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 25.00 | 30.00 | 25.00 | 30.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 53.25 | 31.75 | 53.25 | 31.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 61.25 | 100.25 | 61.25 | 100.25 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 4.25 | 84.25 | 4.25 | 84.25 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 84.50 | 0.00 | 84.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 223.75 | 100.50 | 223.75 | 100.50 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 715.50 | 146.75 | 715.50 | 146.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.206 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.179 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.202 | 0.000 | 0.264 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.178 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.202 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.065 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.088 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.064 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.089 | 0.000 | 0.265 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.202 | 0.000 | 0.265 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.203 | 0.000 | 0.265 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.178 | 0.000 | 0.265 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.179 | 0.000 | 0.265 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.202 | 0.000 | 0.265 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Surfaces by ClassTotal | Outdoors | |
Wall | 74 | 50 |
Floor | 28 | 3 |
Roof | 21 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1855 |
Defaulted Fields | 436 |
Fields with Defaults | 4694 |
Autosized Fields | 328 |
Autosizable Fields | 438 |
Autocalculated Fields | 90 |
Autocalculatable Fields | 269 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 11312.52 | 110.19 | 01-MAR-03:30 | 3676.31 | 08-JUL-17:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
ElectricityPurchased:Plant | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
Cogeneration:ElectricityPurchased | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
ElectricityNet:Plant | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
Cogeneration:ElectricityNet | 169467.04 | 7453.82 | 01-MAR-03:30 | 45628.60 | 16-JUL-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 63547.70 | 529.01 | 30-OCT-01:15 | 25173.62 | 16-JUL-18:00 |
General:Fans:Electricity | 11312.52 | 110.19 | 01-MAR-03:30 | 3676.31 | 08-JUL-17:15 |
Cooling:Electricity | 52235.19 | 37.42 | 31-JAN-07:30 | 21497.31 | 16-JUL-18:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 2859.41 | 0.00 | 01-JAN-15:00 | 235610.39 | 31-JAN-07:30 |
Gas:Plant | 2859.41 | 0.00 | 01-JAN-15:00 | 235610.39 | 31-JAN-07:30 |
WaterSystems:Gas | 2144.69 | 0.00 | 01-JAN-00:15 | 114042.39 | 21-JAN-09:00 |
Water Heater:WaterSystems:Gas | 2144.69 | 0.00 | 01-JAN-00:15 | 114042.39 | 21-JAN-09:00 |
Heating:Gas | 714.72 | 0.00 | 01-JAN-14:30 | 124395.79 | 31-JAN-07:15 |
Boiler:Heating:Gas | 714.72 | 0.00 | 01-JAN-14:30 | 124395.79 | 31-JAN-07:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 22-MAR-02:15 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 149400.13 | 431.70 | 21-JUL-03:00 | 129515.35 | 31-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 93474.00 | 431.70 | 21-JUL-03:00 | 31801.02 | 21-JAN-08:45 |
WaterSystems:PlantLoopHeatingDemand | 93474.00 | 431.70 | 21-JUL-03:00 | 31801.02 | 21-JAN-08:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1534759.85 | 15534.68 | 02-NOV-02:30 | 463615.43 | 17-JUN-19:00 |
EnergyTransfer:Building | 657664.01 | 6807.65 | 30-OCT-01:15 | 220997.76 | 02-JUL-18:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 59634.10 | 0.00 | 01-JAN-15:30 | 102152.95 | 31-JAN-07:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 598029.91 | 669.15 | 31-JAN-07:30 | 220997.76 | 02-JUL-18:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103452.65 | 669.15 | 31-JAN-07:30 | 23353.46 | 29-SEP-16:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 103452.65 | 669.15 | 31-JAN-07:30 | 23353.46 | 29-SEP-16:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 26348.07 | 0.00 | 01-JAN-00:15 | 9014.54 | 29-SEP-15:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2056.87 | 0.00 | 01-JAN-00:15 | 4485.12 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24291.20 | 0.00 | 01-JAN-00:15 | 9014.54 | 29-SEP-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 35193.79 | 0.00 | 01-JAN-09:30 | 11731.55 | 16-JUL-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3504.99 | 0.00 | 01-JAN-09:30 | 6612.49 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 31688.80 | 0.00 | 01-JAN-00:15 | 11731.55 | 16-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 32612.51 | 0.00 | 01-JAN-14:15 | 14019.98 | 18-JUN-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4642.59 | 0.00 | 01-JAN-14:15 | 6698.20 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 27969.93 | 0.00 | 01-JAN-00:15 | 14019.98 | 18-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23148.87 | 0.00 | 01-JAN-15:30 | 8701.19 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3105.02 | 0.00 | 01-JAN-15:30 | 4815.34 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 20043.84 | 0.00 | 01-JAN-00:15 | 8701.19 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 31855.21 | 0.00 | 01-JAN-13:15 | 11446.03 | 16-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4409.26 | 0.00 | 01-JAN-13:15 | 6643.35 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 27445.94 | 0.00 | 01-JAN-00:15 | 11446.03 | 16-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 35301.53 | 0.00 | 01-JAN-00:15 | 13892.53 | 29-SEP-16:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2583.28 | 0.00 | 01-JAN-00:15 | 5338.81 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 32718.25 | 0.00 | 01-JAN-00:15 | 13892.53 | 29-SEP-16:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26026.15 | 0.00 | 01-JAN-00:15 | 8470.49 | 16-JUL-20:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1326.92 | 0.00 | 01-JAN-00:15 | 3634.21 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24699.23 | 0.00 | 01-JAN-00:15 | 8470.49 | 16-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 34730.44 | 0.00 | 01-JAN-00:15 | 11200.54 | 16-JUL-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2542.70 | 0.00 | 01-JAN-00:15 | 5721.18 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 32187.74 | 0.00 | 01-JAN-00:15 | 11200.54 | 16-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 31851.84 | 0.00 | 01-JAN-14:30 | 13477.67 | 18-JUN-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3592.07 | 0.00 | 01-JAN-14:30 | 5863.97 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 28259.76 | 0.00 | 01-JAN-00:15 | 13477.67 | 18-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 22434.20 | 0.00 | 01-JAN-00:15 | 8309.10 | 16-JUL-21:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2130.53 | 0.00 | 01-JAN-00:15 | 3937.05 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20303.68 | 0.00 | 01-JAN-00:15 | 8309.10 | 16-JUL-21:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 31193.30 | 0.00 | 01-JAN-12:45 | 10954.03 | 16-JUL-19:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3342.31 | 0.00 | 01-JAN-12:45 | 5755.39 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 27850.99 | 0.00 | 01-JAN-00:15 | 10954.03 | 16-JUL-19:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 38926.03 | 0.00 | 01-JAN-13:30 | 13715.86 | 16-JUL-20:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5192.08 | 0.00 | 01-JAN-13:30 | 7925.91 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 33733.95 | 0.00 | 01-JAN-00:15 | 13715.86 | 16-JUL-20:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 40825.13 | 0.00 | 01-JAN-10:30 | 13750.13 | 16-JUL-20:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4312.52 | 0.00 | 01-JAN-10:30 | 7904.34 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 36512.61 | 0.00 | 01-JAN-00:15 | 13750.13 | 16-JUL-20:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 41770.35 | 0.00 | 01-JAN-11:45 | 16418.37 | 27-AUG-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4672.37 | 0.00 | 01-JAN-11:45 | 7809.54 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 37097.99 | 0.00 | 01-JAN-00:15 | 16418.37 | 27-AUG-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 30145.23 | 0.00 | 01-JAN-14:30 | 11117.75 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3818.44 | 0.00 | 01-JAN-14:30 | 6077.16 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 26326.79 | 0.00 | 01-JAN-00:15 | 11117.75 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 32038.25 | 0.00 | 01-JAN-00:15 | 11049.84 | 02-JUL-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2874.41 | 0.00 | 01-JAN-00:15 | 5835.61 | 31-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 29163.84 | 0.00 | 01-JAN-00:15 | 11049.84 | 02-JUL-19:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 39810.44 | 0.00 | 01-JAN-14:15 | 16376.86 | 27-AUG-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5527.73 | 0.00 | 01-JAN-14:15 | 8012.66 | 31-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 34282.71 | 0.00 | 01-JAN-00:15 | 16376.86 | 27-AUG-17:15 |
EnergyTransfer:Plant | 150651.73 | 431.70 | 21-JUL-03:00 | 129506.74 | 31-JAN-07:15 |
WaterSystems:EnergyTransfer | 93474.00 | 431.70 | 21-JUL-03:00 | 31801.02 | 21-JAN-08:45 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 93474.00 | 431.70 | 21-JUL-03:00 | 31801.02 | 21-JAN-08:45 |
EnergyTransfer:HVAC | 726444.11 | 6716.78 | 21-APR-07:00 | 253641.00 | 10-AUG-18:30 |
HeatingCoils:EnergyTransfer | 55926.13 | 0.00 | 01-JAN-14:30 | 99525.24 | 31-JAN-07:15 |
PlantLoopHeatingDemand:HVAC | 55926.13 | 0.00 | 01-JAN-14:30 | 99525.24 | 31-JAN-07:15 |
HeatingCoils:PlantLoopHeatingDemand | 55926.13 | 0.00 | 01-JAN-14:30 | 99525.24 | 31-JAN-07:15 |
CoolingCoils:EnergyTransfer | 670517.99 | 704.97 | 31-JAN-07:30 | 253641.00 | 10-AUG-18:30 |
Boilers:EnergyTransfer | 57177.73 | 0.00 | 01-JAN-14:30 | 99516.63 | 31-JAN-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -8615.29 | 0.000 | 0.000 | 2872.489 | 2771.241 | 10464.601 | 15226.306 | 0.000 | 5509.531 | 76853.314 | 0.000 | -4395.32 | 0.000 | -5849.52 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 2056.854 | -2022.92 | 0.000 | 0.000 | 2943.176 | 2771.241 | 10464.601 | 6581.501 | 0.000 | 5202.927 | 951.484 | 0.000 | -1682.18 | 0.000 | -4998.39 | -0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 3504.961 | -2638.97 | 0.000 | 0.000 | 2958.153 | 2771.241 | 10464.601 | 15156.263 | 0.000 | 5519.433 | 456.060 | 0.000 | -3925.35 | 0.000 | -5216.59 | -0.01 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4642.553 | -2329.27 | 0.000 | 0.000 | 2969.278 | 2771.241 | 10464.601 | 11763.658 | 0.000 | 5513.448 | 0.300 | 0.000 | -4301.89 | 0.000 | -5012.46 | -840.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3105.002 | -1669.21 | 0.000 | 0.000 | 2961.333 | 2771.241 | 10464.601 | 2776.999 | 0.000 | 5202.537 | 0.197 | 0.000 | -1802.00 | 0.000 | -4806.47 | -629.35 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4409.237 | -2285.63 | 0.000 | 0.000 | 2970.830 | 2771.241 | 10464.601 | 11407.594 | 0.000 | 5519.012 | 0.074 | 0.000 | -3916.80 | 0.000 | -5068.53 | -1111.23 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2583.262 | -2724.70 | 0.000 | 0.000 | 2943.756 | 2771.241 | 10464.601 | 15264.253 | 0.000 | 4033.758 | 2911.049 | 0.000 | -4293.38 | 0.000 | -3960.29 | -0.01 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1326.905 | -2056.90 | 0.000 | 0.000 | 2928.696 | 2771.241 | 10464.601 | 6562.070 | 0.000 | 3723.767 | 2407.038 | 0.000 | -1735.19 | 0.000 | -3749.87 | -0.31 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2542.684 | -2680.52 | 0.000 | 0.000 | 2947.132 | 2771.241 | 10464.601 | 15089.352 | 0.000 | 4037.963 | 2355.144 | 0.000 | -4047.57 | 0.000 | -3972.80 | -0.11 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 3592.050 | -2353.41 | 0.000 | 0.000 | 2958.090 | 2771.241 | 10464.601 | 11749.820 | 0.000 | 4035.543 | 944.535 | 0.000 | -4428.77 | 0.000 | -3827.32 | -0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2130.511 | -1690.85 | 0.000 | 0.000 | 2947.743 | 2771.241 | 10464.601 | 2792.103 | 0.000 | 3724.657 | 938.867 | 0.000 | -1854.69 | 0.000 | -3611.30 | -0.07 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 3342.294 | -2319.37 | 0.000 | 0.000 | 2961.523 | 2771.241 | 10464.601 | 11372.788 | 0.000 | 4037.795 | 784.471 | 0.000 | -4025.27 | 0.000 | -3858.42 | -0.09 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 5192.049 | -2809.29 | 0.000 | 0.000 | 2965.898 | 2771.241 | 10464.601 | 11236.410 | 0.000 | 5493.436 | 4755.076 | 0.000 | -4032.47 | 0.000 | -5112.27 | -0.02 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4312.488 | -3040.69 | 0.000 | 0.000 | 2956.085 | 2771.241 | 10464.601 | 14991.861 | 0.000 | 5493.526 | 4761.286 | 0.000 | -4014.97 | 0.000 | -5223.50 | -0.01 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4672.330 | -3089.43 | 0.000 | 0.000 | 2955.086 | 2771.241 | 10464.601 | 15178.005 | 0.000 | 5486.232 | 4984.095 | 0.000 | -4225.22 | 0.000 | -5188.38 | -0.08 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 3818.409 | -2192.44 | 0.000 | 0.000 | 2955.964 | 2771.241 | 10464.601 | 2734.707 | 0.000 | 5178.689 | 5112.776 | 0.000 | -1845.55 | 0.000 | -4863.98 | -0.21 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 2874.387 | -2428.70 | 0.000 | 0.000 | 2943.421 | 2771.241 | 10464.601 | 6520.516 | 0.000 | 5177.175 | 5114.269 | 0.000 | -1711.25 | 0.000 | -4990.48 | -0.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 5527.692 | -2854.99 | 0.000 | 0.000 | 2963.961 | 2771.241 | 10464.601 | 11585.981 | 0.000 | 5488.176 | 4957.697 | 0.000 | -4402.38 | 0.000 | -5074.23 | -0.36 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7668.463 | 52176.881 | 0.000 | 0.000 | 0.000 | -59845.34 | -0.09 |
Total Facility | 0.000 | 0.000 | 59633.668 | -49802.57 | 0.000 | 0.000 | 53102.613 | 49882.340 | 188362.826 | 187990.186 | 0.000 | 96046.070 | 170464.613 | 0.000 | -60640.23 | 0.000 | -144230.13 | -2582.70 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29-SEP-16:49 | 0.00 | 0.00 | 0.00 | -1.9 | 0.00 | 0.00 | 139.86 | 434.11 | 1350.56 | 7407.57 | 0.00 | 2111.05 | 11917.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16-JUL-20:23 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 423.92 | 902.05 | 1651.67 | 709.57 | 0.00 | 2424.50 | 2907.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-JUL-19:11 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 423.08 | 902.05 | 1689.30 | 2416.64 | 0.00 | 3362.15 | 2994.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12-JUL-18:03 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 427.01 | 813.96 | 1724.99 | 6204.48 | 0.00 | 2532.55 | 2330.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 02-JUL-19:24 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 422.19 | 902.05 | 1689.30 | 730.10 | 0.00 | 2546.23 | 2466.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16-JUL-19:38 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 423.04 | 902.05 | 1689.30 | 1965.93 | 0.00 | 3007.22 | 3518.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 29-SEP-17:03 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 263.32 | 604.65 | 1664.02 | 6814.72 | 0.00 | 1578.23 | 2992.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16-JUL-20:35 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 424.18 | 902.05 | 1651.67 | 688.00 | 0.00 | 1625.57 | 3188.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-JUL-19:08 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 425.08 | 902.05 | 1689.30 | 2464.28 | 0.00 | 2296.30 | 3480.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 18-JUN-19:18 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 426.15 | 902.05 | 1689.30 | 2961.65 | 0.00 | 1730.22 | 5801.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-JUL-21:38 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 475.99 | 682.17 | 1577.18 | 637.08 | 0.00 | 1520.66 | 3437.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 16-JUL-19:41 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 423.62 | 902.05 | 1689.30 | 1995.59 | 0.00 | 2097.56 | 3905.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 16-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 418.61 | 902.05 | 1689.30 | 1806.52 | 0.00 | 2821.39 | 6105.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 16-JUL-20:00 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 420.71 | 902.05 | 1689.30 | 1845.63 | 0.00 | 2835.58 | 6084.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-AUG-17:03 | 0.00 | 0.00 | 0.00 | -1.4 | 0.00 | 0.00 | 259.55 | 604.65 | 1685.13 | 7906.59 | 0.00 | 2613.36 | 3365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 02-JUL-19:30 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 421.21 | 902.05 | 1689.30 | 726.04 | 0.00 | 2544.09 | 4857.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 02-JUL-19:24 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 422.67 | 902.05 | 1689.30 | 685.87 | 0.00 | 2542.32 | 4875.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 27-AUG-17:03 | 0.00 | 0.00 | 0.00 | -1.4 | 0.00 | 0.00 | 260.14 | 604.65 | 1685.13 | 7928.66 | 0.00 | 2619.53 | 3291.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 16-JUL-19:30 | 0.00 | 0.00 | 0.00 | -18.4 | 0.00 | 0.00 | 7391.98 | 16236.84 | 30407.43 | 31608.86 | 0.00 | 48850.25 | 89486.01 | 0.00 | 0.00 | 0.00 | -2789.7 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 4485.18 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1110.4 | 0.00 | -3374.0 | -2063.8 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12-DEC-20:25 | 0.00 | 0.00 | 7924.59 | 0.00 | 0.00 | 0.00 | 492.20 | 902.05 | 1628.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2054.4 | 0.00 | -2443.4 | -6449.2 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 09-MAR-09:48 | 0.00 | 0.00 | 27930.99 | 0.00 | 0.00 | 0.00 | 134.12 | 116.28 | 1096.02 | 208.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1026.3 | -28459.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 30-JAN-17:21 | 0.00 | 0.00 | 14694.34 | 0.00 | 0.00 | 0.00 | 308.45 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -661.0 | 0.00 | -2195.7 | -14414.8 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30-JAN-17:30 | 0.00 | 0.00 | 9006.64 | 0.00 | 0.00 | 0.00 | 291.10 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1692.2 | 0.00 | -2362.4 | -7511.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5338.96 | 0.00 | 0.00 | 0.00 | 464.79 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2752.1 | 0.00 | -2563.8 | -2086.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 3634.32 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1127.9 | 0.00 | -2344.3 | -2225.3 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13-DEC-23:25 | 0.00 | 0.00 | 9316.74 | 0.00 | 0.00 | 0.00 | 552.49 | 155.04 | 1150.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2410.7 | 0.00 | -2057.8 | -6706.2 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20-JAN-13:11 | 0.00 | 0.00 | 26324.33 | 0.00 | 0.00 | 0.00 | 140.44 | 116.28 | 1084.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -69.8 | 0.00 | -1025.0 | -26570.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 30-JAN-17:39 | 0.00 | 0.00 | 11164.99 | 0.00 | 0.00 | 0.00 | 303.94 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.5 | 0.00 | -1544.1 | -11470.1 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 30-JAN-17:48 | 0.00 | 0.00 | 7191.08 | 0.00 | 0.00 | 0.00 | 296.24 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1930.9 | 0.00 | -1774.4 | -6050.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 7926.03 | 0.00 | 0.00 | 0.00 | 464.79 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2714.4 | 0.00 | -3601.1 | -3673.6 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 7904.45 | 0.00 | 0.00 | 0.00 | 464.77 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2727.8 | 0.00 | -3601.3 | -3638.5 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 04-APR-10:37 | 0.00 | 0.00 | 8448.81 | 0.00 | 0.00 | 0.00 | 130.78 | 116.28 | 1089.80 | 2263.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -561.9 | -11486.8 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 31-JAN-08:15 | 0.00 | 0.00 | 6077.23 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -976.0 | 0.00 | -3280.4 | -3362.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 31-JAN-07:15 | 0.00 | 0.00 | 5835.70 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1117.6 | 0.00 | -3381.3 | -3400.0 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 09-NOV-10:25 | 0.00 | 0.00 | 17212.85 | 0.00 | 0.00 | 0.00 | 132.95 | 116.28 | 1089.80 | 407.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -490.9 | -18468.6 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 31-JAN-07:15 | -941.1 | 0.08 | 102154.86 | -0.1 | 0.00 | 0.00 | 8321.79 | 6976.77 | 21793.53 | 0.00 | 0.00 | 3024.88 | 0.00 | 0.00 | -39476.0 | 0.00 | -57599.4 | -44255.4 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.238 | 2.00 | 2.00 | 1.00 | 44.9950 | 1034.238 | 0.044 | 1.000 | 44.9950 | 0.04 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 374.268 | 2.00 | 2.00 | 1.00 | 44.9950 | 374.268 | 0.120 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 500.147 | 2.00 | 2.00 | 1.00 | 44.9950 | 500.147 | 0.090 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 610.898 | 2.00 | 2.00 | 1.00 | 44.9950 | 610.898 | 0.074 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 367.115 | 2.00 | 2.00 | 1.00 | 44.9950 | 367.115 | 0.123 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 480.376 | 2.00 | 2.00 | 1.00 | 44.9950 | 480.376 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 594.873 | 2.00 | 2.00 | 1.00 | 44.9950 | 594.873 | 0.076 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 351.829 | 2.00 | 2.00 | 1.00 | 44.9950 | 351.829 | 0.128 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 473.775 | 2.00 | 2.00 | 1.00 | 44.9950 | 473.775 | 0.095 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 585.106 | 2.00 | 2.00 | 1.00 | 44.9950 | 585.106 | 0.077 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 348.258 | 2.00 | 2.00 | 1.00 | 44.9950 | 348.258 | 0.129 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 455.411 | 2.00 | 2.00 | 1.00 | 44.9950 | 455.411 | 0.099 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 721.072 | 2.00 | 2.00 | 1.00 | 44.9950 | 721.072 | 0.062 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 476.336 | 2.00 | 2.00 | 1.00 | 44.9950 | 476.336 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 589.242 | 2.00 | 2.00 | 1.00 | 44.9950 | 589.242 | 0.076 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 719.946 | 2.00 | 2.00 | 1.00 | 44.9950 | 719.946 | 0.062 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 476.298 | 2.00 | 2.00 | 1.00 | 44.9950 | 476.298 | 0.094 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 587.307 | 2.00 | 2.00 | 1.00 | 44.9950 | 587.307 | 0.077 | 1.000 | 44.9950 | 0.08 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 87.104 | 2.00 | 2.00 | 1.00 | 44.9950 | 87.104 | 1.000 | 1.000 | 44.9950 | 0.52 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 124.293 | 2.00 | 2.00 | 1.00 | 44.9950 | 124.293 | 1.000 | 1.000 | 44.9950 | 0.36 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 124.598 | 2.00 | 2.00 | 1.00 | 44.9950 | 124.598 | 1.000 | 1.000 | 44.9950 | 0.36 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 89.638 | 2.00 | 2.00 | 1.00 | 44.9950 | 89.638 | 1.000 | 1.000 | 44.9950 | 0.50 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 124.328 | 2.00 | 2.00 | 1.00 | 44.9950 | 124.328 | 1.000 | 1.000 | 44.9950 | 0.36 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 105.681 | 2.00 | 2.00 | 1.00 | 44.9950 | 105.681 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 75.855 | 2.00 | 2.00 | 1.00 | 44.9950 | 75.855 | 1.000 | 1.000 | 44.9950 | 0.59 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 111.926 | 2.00 | 2.00 | 1.00 | 44.9950 | 111.926 | 1.000 | 1.000 | 44.9950 | 0.40 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 112.099 | 2.00 | 2.00 | 1.00 | 44.9950 | 112.099 | 1.000 | 1.000 | 44.9950 | 0.40 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 76.382 | 2.00 | 2.00 | 1.00 | 44.9950 | 76.382 | 1.000 | 1.000 | 44.9950 | 0.59 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 111.882 | 2.00 | 2.00 | 1.00 | 44.9950 | 111.882 | 1.000 | 1.000 | 44.9950 | 0.40 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 148.918 | 2.00 | 2.00 | 1.00 | 44.9950 | 148.918 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 114.127 | 2.00 | 2.00 | 1.00 | 44.9950 | 114.127 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 149.663 | 2.00 | 2.00 | 1.00 | 44.9950 | 149.663 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 149.769 | 2.00 | 2.00 | 1.00 | 44.9950 | 149.769 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 114.225 | 2.00 | 2.00 | 1.00 | 44.9950 | 114.225 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 149.614 | 2.00 | 2.00 | 1.00 | 44.9950 | 149.614 | 1.000 | 1.000 | 44.9950 | 0.30 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.238 | 1034.2375 | 206.8475 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 374.268 | 374.2684 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 500.147 | 500.1470 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 610.898 | 610.8978 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 367.115 | 367.1152 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 480.376 | 480.3761 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 594.873 | 594.8729 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 351.829 | 351.8291 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 473.775 | 473.7745 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 585.106 | 585.1063 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 348.258 | 348.2581 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 455.411 | 455.4112 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 587.307 | 587.3069 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 589.242 | 589.2423 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 721.072 | 721.0718 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 476.298 | 476.2975 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 476.336 | 476.3365 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 719.946 | 719.9460 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 | 1034.238 | 1034.24 | 206.8475 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 | 374.268 | 374.27 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 | 500.147 | 500.15 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 | 610.898 | 610.90 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 | 367.115 | 367.12 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 | 480.376 | 480.38 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 | 594.873 | 594.87 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 | 351.829 | 351.83 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 | 473.775 | 473.77 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 | 585.106 | 585.11 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 | 348.258 | 348.26 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 | 455.411 | 455.41 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 721.07 | 721.072 | 721.07 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 476.34 | 476.336 | 476.34 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 589.24 | 589.242 | 589.24 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 719.95 | 719.946 | 719.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 476.30 | 476.298 | 476.30 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 587.31 | 587.307 | 587.31 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 87.104 | 87.104 | 87.104 | 44.9950 | 0.517 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 124.293 | 124.293 | 124.293 | 44.9950 | 0.362 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 124.598 | 124.598 | 124.598 | 44.9950 | 0.361 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 89.638 | 89.638 | 89.638 | 44.9950 | 0.502 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 124.328 | 124.328 | 124.328 | 44.9950 | 0.362 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 105.681 | 105.681 | 105.681 | 44.9950 | 0.426 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 75.855 | 75.855 | 75.855 | 44.9950 | 0.593 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 111.926 | 111.926 | 111.926 | 44.9950 | 0.402 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 112.099 | 112.099 | 112.099 | 44.9950 | 0.401 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 76.382 | 76.382 | 76.382 | 44.9950 | 0.589 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 111.882 | 111.882 | 111.882 | 44.9950 | 0.402 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 149.614 | 149.614 | 149.614 | 44.9950 | 0.301 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 149.663 | 149.663 | 149.663 | 44.9950 | 0.301 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 148.918 | 148.918 | 148.918 | 44.9950 | 0.302 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 114.225 | 114.225 | 114.225 | 44.9950 | 0.394 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 114.127 | 114.127 | 114.127 | 44.9950 | 0.394 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 149.769 | 149.769 | 149.769 | 44.9950 | 0.300 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 87.10 | 87.104 | 87.10 | 87.10 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 124.29 | 124.293 | 124.29 | 124.29 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 124.60 | 124.598 | 124.60 | 124.60 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 89.64 | 89.638 | 89.64 | 89.64 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 124.33 | 124.328 | 124.33 | 124.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 105.68 | 105.681 | 105.68 | 105.68 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 75.85 | 75.855 | 75.85 | 75.85 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 111.93 | 111.926 | 111.93 | 111.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 112.10 | 112.099 | 112.10 | 112.10 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 76.38 | 76.382 | 76.38 | 76.38 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 111.88 | 111.882 | 111.88 | 111.88 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 148.92 | 148.918 | 148.92 | 148.92 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 114.13 | 114.127 | 114.13 | 114.13 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 149.66 | 149.663 | 149.66 | 149.66 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 149.77 | 149.769 | 149.77 | 149.77 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 114.23 | 114.225 | 114.23 | 114.23 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 149.61 | 149.614 | 149.61 | 149.61 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Phoenix Sky Harbor Intl Ap AZ USA TMY3 WMO#=722780 |
Total gross floor area [ft2] | 31210.78 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 31210.78 | 21609.96 | 9600.82 |
Data | |
Number of hours heating loads not met | 715.50 |
Number of hours cooling loads not met | 146.75 |
Number of hours not met | 862.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 714.72 | 121904.15 | 0.00 | 0.00 |
Space Cooling | 52235.19 | 21437.55 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 11312.52 | 3676.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2144.69 | 113706.24 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15497.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 169467.04 | 2859.41 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 578631.19 |
Natural Gas | 0.00 | 285941.48 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 864572.67 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.47 |
Space Heating | 0.00 |
Space Cooling | 1.67 |
Fans-Interior | 0.36 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.83 |
Miscellaneous | 0.10 |
Subtotal | 5.43 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.67 |
Service Water Heating | 2.01 |
Miscellaneous | -0.0 |
Subtotal | 2.68 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.77 |
Space Heating | 8.27 |
Space Cooling | 20.63 |
Fans-Interior | 4.47 |
Service Water Heating | 24.81 |
Receptacle Equipment | 34.87 |
Miscellaneous | 1.19 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 587.31 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 589.24 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 721.07 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 476.30 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 476.34 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 719.95 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 721.07 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 476.34 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 589.24 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 719.95 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 476.30 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 587.31 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 | 2.35 | 0.789887 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 | 0.926796 | 0.760838 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 | 1.25 | 0.758778 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 | 1.44 | 0.778654 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 | 0.885259 | 0.769714 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 | 1.20 | 0.757232 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 | 1.40 | 0.777979 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 | 0.863906 | 0.763634 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 | 1.19 | 0.756833 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 | 1.37 | 0.778746 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 | 0.838653 | 0.770172 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 | 1.15 | 0.755262 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 721.07 | 1.67 | 0.783313 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 476.34 | 1.13 | 0.776829 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 589.24 | 1.43 | 0.767611 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 719.95 | 1.67 | 0.783272 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 476.30 | 1.12 | 0.776826 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 587.31 | 1.43 | 0.767503 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 | 1034.24 | 1034.24 | 2.35 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 | 374.27 | 374.27 | 0.926796 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 | 500.15 | 500.15 | 1.25 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 | 610.90 | 610.90 | 1.44 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 | 367.12 | 367.12 | 0.885259 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 | 480.38 | 480.38 | 1.20 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 | 594.87 | 594.87 | 1.40 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 | 351.83 | 351.83 | 0.863906 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 | 473.77 | 473.77 | 1.19 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 | 585.11 | 585.11 | 1.37 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 | 348.26 | 348.26 | 0.838653 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 | 455.41 | 455.41 | 1.15 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 721.07 | 721.07 | 721.07 | 1.67 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 476.34 | 476.34 | 476.34 | 1.13 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 589.24 | 589.24 | 589.24 | 1.43 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 719.95 | 719.95 | 719.95 | 1.67 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 476.30 | 476.30 | 476.30 | 1.12 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 587.31 | 587.31 | 587.31 | 1.43 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 55353.46 | 5.59 | 792.69 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 21028.37 | 2.12 | 296.51 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 27576.54 | 2.78 | 391.28 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 33337.56 | 3.36 | 474.66 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 20656.29 | 2.08 | 291.12 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 26548.09 | 2.68 | 376.40 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 32503.16 | 3.28 | 462.54 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 19860.72 | 2.00 | 279.56 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 26204.08 | 2.64 | 371.37 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 31995.16 | 3.23 | 455.18 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 19674.97 | 1.99 | 276.87 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 25248.88 | 2.55 | 357.55 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 39068.69 | 3.94 | 557.56 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 26337.78 | 2.66 | 373.35 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 32211.18 | 3.25 | 458.33 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 39010.13 | 3.94 | 556.71 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 26335.76 | 2.66 | 373.32 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 32110.50 | 3.24 | 456.87 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 1034.24 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 374.27 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 500.15 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 610.90 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 367.12 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 480.38 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 594.87 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 351.83 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 473.77 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 585.11 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 348.26 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 455.41 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 721.07 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 476.34 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 589.24 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 719.95 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 476.30 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 587.31 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 7.22 | 135.37 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 7.22 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 537055.83 | 54.01 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:28:00
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 87.462 | 0.000 | 0.000 | 87.462 |
February | 672.000 | 92.048 | 0.000 | 0.000 | 92.048 |
March | 744.000 | 110.379 | 0.000 | 0.000 | 110.379 |
April | 720.000 | 137.964 | 0.000 | 0.000 | 137.964 |
May | 744.000 | 162.972 | 0.000 | 0.000 | 162.972 |
June | 720.000 | 196.245 | 0.000 | 0.000 | 196.245 |
July | 744.000 | 220.003 | 0.000 | 0.000 | 220.003 |
August | 744.000 | 209.190 | 0.000 | 0.000 | 209.190 |
September | 720.000 | 180.385 | 0.000 | 0.000 | 180.385 |
October | 744.000 | 153.966 | 0.000 | 0.000 | 153.966 |
November | 720.000 | 113.463 | 0.000 | 0.000 | 113.463 |
December | 744.000 | 81.724 | 0.000 | 0.000 | 81.724 |
Annual Sum or Average | 8760.000 | 1745.800 | 0.000 | 0.000 | 1745.800 |
Minimum of Months | 672.000 | 81.724 | 0.000 | 0.000 | 81.724 |
Maximum of Months | 744.000 | 220.003 | 0.000 | 0.000 | 220.003 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 219.582 | 6.394 | 315.533 | 2.380 | 8.773 |
February | 264.380 | 10.855 | 221.125 | 1.651 | 12.506 |
March | 333.757 | 12.538 | 166.048 | 1.092 | 13.630 |
April | 523.961 | 25.989 | 57.375 | 0.349 | 26.338 |
May | 688.825 | 35.939 | 0.000 | 0.000 | 35.939 |
June | 720.000 | 60.140 | 0.000 | 0.000 | 60.140 |
July | 744.000 | 75.059 | 0.000 | 0.000 | 75.059 |
August | 744.000 | 68.406 | 0.000 | 0.000 | 68.406 |
September | 720.000 | 53.357 | 0.000 | 0.000 | 53.357 |
October | 666.146 | 36.310 | 19.500 | 0.043 | 36.353 |
November | 413.643 | 16.384 | 93.861 | 0.390 | 16.774 |
December | 195.817 | 5.682 | 352.649 | 2.997 | 8.679 |
Annual Sum or Average | 6234.109 | 407.053 | 1226.091 | 8.902 | 415.955 |
Minimum of Months | 195.817 | 5.682 | 0.000 | 0.000 | 8.679 |
Maximum of Months | 744.000 | 75.059 | 352.649 | 2.997 | 75.059 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 180.810 | 6.125 | 300.358 | 7.649 | 24.436 |
February | 255.159 | 12.762 | 206.417 | 5.029 | 25.979 |
March | 345.123 | 16.237 | 143.355 | 3.341 | 29.040 |
April | 536.911 | 35.822 | 48.125 | 0.979 | 39.440 |
May | 683.262 | 49.886 | 0.000 | 0.000 | 50.972 |
June | 720.000 | 81.213 | 0.000 | 0.000 | 81.213 |
July | 744.000 | 98.594 | 0.000 | 0.000 | 98.594 |
August | 744.000 | 89.230 | 0.000 | 0.000 | 89.230 |
September | 720.000 | 67.959 | 0.000 | 0.000 | 67.959 |
October | 644.013 | 44.370 | 15.625 | 0.214 | 46.960 |
November | 392.399 | 18.078 | 84.500 | 1.494 | 30.462 |
December | 166.838 | 5.297 | 338.675 | 9.343 | 25.299 |
Annual Sum or Average | 6132.513 | 525.572 | 1137.055 | 28.048 | 609.583 |
Minimum of Months | 166.838 | 5.297 | 0.000 | 0.000 | 24.436 |
Maximum of Months | 744.000 | 98.594 | 338.675 | 9.343 | 98.594 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 67.966 | 1.693 | 400.321 | 9.552 | 29.644 |
February | 168.757 | 7.364 | 286.419 | 6.158 | 25.326 |
March | 257.697 | 12.409 | 230.295 | 3.907 | 26.042 |
April | 478.228 | 33.777 | 73.982 | 1.188 | 38.178 |
May | 662.268 | 52.027 | 8.781 | 0.036 | 52.241 |
June | 720.000 | 86.507 | 0.000 | 0.000 | 86.507 |
July | 744.000 | 104.207 | 0.000 | 0.000 | 104.207 |
August | 744.000 | 92.257 | 0.000 | 0.000 | 92.257 |
September | 720.000 | 65.276 | 0.000 | 0.000 | 65.276 |
October | 603.211 | 35.773 | 38.004 | 0.390 | 38.119 |
November | 267.163 | 8.585 | 191.141 | 2.388 | 20.349 |
December | 52.296 | 0.989 | 446.907 | 11.705 | 33.632 |
Annual Sum or Average | 5485.586 | 500.864 | 1675.851 | 35.325 | 611.778 |
Minimum of Months | 52.296 | 0.989 | 0.000 | 0.000 | 20.349 |
Maximum of Months | 744.000 | 104.207 | 446.907 | 11.705 | 104.207 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 32.144 | 0.304 | 465.897 | 4.618 | 9.110 |
February | 152.081 | 3.924 | 304.396 | 2.910 | 8.372 |
March | 249.447 | 6.121 | 203.261 | 1.657 | 9.087 |
April | 502.261 | 22.131 | 65.004 | 0.511 | 22.715 |
May | 687.721 | 35.748 | 0.083 | 0.000 | 35.748 |
June | 720.000 | 61.559 | 0.000 | 0.000 | 61.559 |
July | 744.000 | 75.710 | 0.000 | 0.000 | 75.710 |
August | 744.000 | 66.750 | 0.000 | 0.000 | 66.750 |
September | 720.000 | 47.110 | 0.000 | 0.000 | 47.110 |
October | 641.802 | 26.121 | 29.989 | 0.100 | 26.281 |
November | 268.950 | 4.517 | 159.732 | 0.810 | 5.548 |
December | 14.225 | 0.089 | 529.433 | 5.823 | 10.215 |
Annual Sum or Average | 5476.631 | 350.084 | 1757.795 | 16.429 | 378.207 |
Minimum of Months | 14.225 | 0.089 | 0.000 | 0.000 | 5.548 |
Maximum of Months | 744.000 | 75.710 | 529.433 | 5.823 | 75.710 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 34.592 | 0.374 | 477.485 | 10.164 | 19.443 |
February | 174.250 | 5.589 | 286.725 | 6.109 | 18.335 |
March | 298.428 | 9.368 | 168.832 | 3.620 | 21.480 |
April | 526.200 | 31.266 | 50.375 | 1.009 | 34.652 |
May | 683.491 | 48.490 | 0.083 | 0.000 | 49.569 |
June | 720.000 | 80.606 | 0.000 | 0.000 | 80.606 |
July | 744.000 | 97.086 | 0.000 | 0.000 | 97.086 |
August | 744.000 | 85.771 | 0.000 | 0.000 | 85.771 |
September | 720.000 | 60.698 | 0.000 | 0.000 | 60.698 |
October | 634.840 | 33.765 | 19.125 | 0.247 | 36.080 |
November | 289.044 | 5.764 | 112.563 | 1.797 | 16.813 |
December | 12.700 | 0.089 | 551.588 | 12.557 | 20.966 |
Annual Sum or Average | 5581.545 | 458.866 | 1666.775 | 35.505 | 541.498 |
Minimum of Months | 12.700 | 0.089 | 0.000 | 0.000 | 16.813 |
Maximum of Months | 744.000 | 97.086 | 551.588 | 12.557 | 97.086 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 229.241 | 9.974 | 326.113 | 5.567 | 15.643 |
February | 268.433 | 16.175 | 226.600 | 3.719 | 21.036 |
March | 346.167 | 20.918 | 146.795 | 2.376 | 27.942 |
April | 523.866 | 39.987 | 50.215 | 0.692 | 42.836 |
May | 689.347 | 54.977 | 0.500 | 0.000 | 54.978 |
June | 720.000 | 84.981 | 0.000 | 0.000 | 84.981 |
July | 744.000 | 101.166 | 0.000 | 0.000 | 101.166 |
August | 744.000 | 92.668 | 0.000 | 0.000 | 92.668 |
September | 720.000 | 72.132 | 0.000 | 0.000 | 72.132 |
October | 655.023 | 48.326 | 23.250 | 0.164 | 49.496 |
November | 398.007 | 21.821 | 117.813 | 1.166 | 24.505 |
December | 205.704 | 8.666 | 369.625 | 7.022 | 15.688 |
Annual Sum or Average | 6243.788 | 571.792 | 1260.911 | 20.707 | 603.071 |
Minimum of Months | 205.704 | 8.666 | 0.000 | 0.000 | 15.643 |
Maximum of Months | 744.000 | 101.166 | 369.625 | 7.022 | 101.166 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 259.011 | 7.472 | 252.958 | 1.846 | 9.349 |
February | 303.410 | 12.323 | 177.458 | 1.315 | 13.638 |
March | 383.687 | 14.401 | 120.721 | 0.883 | 15.394 |
April | 577.126 | 27.947 | 46.250 | 0.269 | 28.259 |
May | 711.625 | 37.940 | 0.000 | 0.000 | 37.940 |
June | 720.000 | 58.713 | 0.000 | 0.000 | 58.713 |
July | 744.000 | 71.472 | 0.000 | 0.000 | 71.472 |
August | 744.000 | 66.003 | 0.000 | 0.000 | 66.003 |
September | 720.000 | 52.965 | 0.000 | 0.000 | 52.965 |
October | 683.006 | 38.222 | 5.500 | 0.010 | 38.232 |
November | 453.748 | 18.128 | 58.656 | 0.227 | 18.355 |
December | 232.606 | 6.663 | 304.729 | 2.493 | 9.155 |
Annual Sum or Average | 6532.219 | 412.248 | 966.273 | 7.043 | 419.475 |
Minimum of Months | 232.606 | 6.663 | 0.000 | 0.000 | 9.155 |
Maximum of Months | 744.000 | 71.472 | 304.729 | 2.493 | 71.472 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 209.300 | 6.791 | 238.405 | 5.393 | 26.007 |
February | 282.057 | 13.919 | 163.769 | 3.594 | 26.230 |
March | 385.177 | 17.894 | 105.833 | 2.366 | 28.000 |
April | 568.846 | 37.507 | 39.125 | 0.673 | 39.907 |
May | 703.977 | 51.515 | 0.000 | 0.000 | 51.570 |
June | 720.000 | 79.456 | 0.000 | 0.000 | 79.456 |
July | 744.000 | 94.457 | 0.000 | 0.000 | 94.457 |
August | 744.000 | 86.335 | 0.000 | 0.000 | 86.335 |
September | 720.000 | 67.221 | 0.000 | 0.000 | 67.221 |
October | 666.517 | 45.795 | 3.625 | 0.054 | 48.755 |
November | 429.335 | 19.353 | 51.292 | 0.822 | 29.377 |
December | 190.487 | 5.906 | 290.833 | 7.047 | 24.346 |
Annual Sum or Average | 6363.696 | 526.149 | 892.882 | 19.948 | 601.661 |
Minimum of Months | 190.487 | 5.906 | 0.000 | 0.000 | 24.346 |
Maximum of Months | 744.000 | 94.457 | 290.833 | 7.047 | 94.457 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 77.690 | 1.769 | 358.327 | 7.399 | 27.300 |
February | 188.927 | 8.160 | 247.131 | 4.697 | 24.873 |
March | 289.352 | 13.803 | 174.970 | 2.847 | 24.757 |
April | 510.987 | 35.492 | 56.921 | 0.850 | 38.924 |
May | 687.737 | 54.006 | 1.750 | 0.002 | 54.152 |
June | 720.000 | 85.196 | 0.000 | 0.000 | 85.196 |
July | 744.000 | 100.631 | 0.000 | 0.000 | 100.631 |
August | 744.000 | 89.925 | 0.000 | 0.000 | 89.925 |
September | 720.000 | 65.067 | 0.000 | 0.000 | 65.067 |
October | 630.260 | 37.529 | 30.650 | 0.232 | 40.096 |
November | 304.268 | 9.463 | 150.164 | 1.610 | 20.684 |
December | 60.952 | 1.021 | 408.500 | 9.400 | 32.231 |
Annual Sum or Average | 5678.174 | 502.060 | 1428.414 | 27.036 | 603.834 |
Minimum of Months | 60.952 | 1.021 | 0.000 | 0.000 | 20.684 |
Maximum of Months | 744.000 | 100.631 | 408.500 | 9.400 | 100.631 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 53.069 | 0.522 | 407.159 | 3.169 | 6.595 |
February | 189.377 | 4.907 | 257.354 | 1.961 | 8.113 |
March | 297.189 | 7.769 | 155.739 | 1.059 | 9.519 |
April | 560.346 | 24.142 | 53.798 | 0.319 | 24.510 |
May | 710.988 | 37.663 | 0.000 | 0.000 | 37.663 |
June | 720.000 | 59.858 | 0.000 | 0.000 | 59.858 |
July | 744.000 | 71.900 | 0.000 | 0.000 | 71.900 |
August | 744.000 | 64.168 | 0.000 | 0.000 | 64.168 |
September | 720.000 | 46.644 | 0.000 | 0.000 | 46.644 |
October | 660.067 | 28.001 | 16.063 | 0.035 | 28.072 |
November | 318.550 | 5.883 | 104.237 | 0.437 | 6.490 |
December | 27.317 | 0.194 | 482.825 | 4.217 | 7.250 |
Annual Sum or Average | 5744.903 | 351.651 | 1477.175 | 11.197 | 370.782 |
Minimum of Months | 27.317 | 0.194 | 0.000 | 0.000 | 6.490 |
Maximum of Months | 744.000 | 71.900 | 482.825 | 4.217 | 71.900 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 44.720 | 0.509 | 405.177 | 7.626 | 20.543 |
February | 195.661 | 6.516 | 238.349 | 4.509 | 18.466 |
March | 335.497 | 10.983 | 125.242 | 2.568 | 20.482 |
April | 559.581 | 33.126 | 41.125 | 0.697 | 35.356 |
May | 704.290 | 50.179 | 0.000 | 0.000 | 50.233 |
June | 720.000 | 78.878 | 0.000 | 0.000 | 78.878 |
July | 744.000 | 93.037 | 0.000 | 0.000 | 93.037 |
August | 744.000 | 83.008 | 0.000 | 0.000 | 83.008 |
September | 720.000 | 60.171 | 0.000 | 0.000 | 60.171 |
October | 655.741 | 35.363 | 6.625 | 0.085 | 38.265 |
November | 329.822 | 6.875 | 68.792 | 1.032 | 17.335 |
December | 19.021 | 0.153 | 489.327 | 9.853 | 21.322 |
Annual Sum or Average | 5772.332 | 458.798 | 1374.636 | 26.371 | 537.096 |
Minimum of Months | 19.021 | 0.153 | 0.000 | 0.000 | 17.335 |
Maximum of Months | 744.000 | 93.037 | 489.327 | 9.853 | 93.037 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 184.790 | 8.846 | 389.208 | 11.706 | 22.325 |
February | 239.864 | 16.585 | 257.274 | 7.631 | 30.114 |
March | 313.402 | 22.560 | 167.889 | 4.757 | 43.953 |
April | 496.688 | 46.007 | 57.000 | 1.466 | 53.378 |
May | 668.670 | 64.924 | 3.031 | 0.017 | 66.503 |
June | 720.000 | 102.596 | 0.000 | 0.000 | 102.596 |
July | 744.000 | 122.789 | 0.000 | 0.000 | 122.789 |
August | 744.000 | 110.255 | 0.000 | 0.000 | 110.255 |
September | 720.000 | 83.150 | 0.000 | 0.000 | 83.150 |
October | 619.305 | 52.993 | 25.625 | 0.454 | 57.168 |
November | 349.577 | 21.571 | 132.875 | 2.889 | 36.058 |
December | 160.190 | 7.329 | 429.302 | 14.182 | 22.187 |
Annual Sum or Average | 5960.486 | 659.604 | 1462.205 | 43.103 | 750.475 |
Minimum of Months | 160.190 | 7.329 | 0.000 | 0.000 | 22.187 |
Maximum of Months | 744.000 | 122.789 | 429.302 | 14.182 | 122.789 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 197.074 | 6.618 | 346.446 | 4.335 | 11.441 |
February | 259.378 | 13.021 | 243.111 | 2.927 | 15.950 |
March | 334.622 | 16.427 | 180.441 | 1.953 | 18.530 |
April | 528.103 | 34.439 | 61.542 | 0.633 | 35.090 |
May | 690.604 | 48.499 | 2.000 | 0.002 | 48.501 |
June | 720.000 | 77.282 | 0.000 | 0.000 | 77.282 |
July | 744.000 | 93.932 | 0.000 | 0.000 | 93.932 |
August | 744.000 | 84.541 | 0.000 | 0.000 | 84.541 |
September | 720.000 | 64.946 | 0.000 | 0.000 | 64.946 |
October | 655.878 | 43.578 | 30.000 | 0.139 | 43.716 |
November | 396.557 | 18.173 | 132.411 | 0.894 | 19.066 |
December | 177.140 | 5.518 | 381.500 | 5.406 | 10.935 |
Annual Sum or Average | 6167.356 | 506.973 | 1377.451 | 16.289 | 523.930 |
Minimum of Months | 177.140 | 5.518 | 0.000 | 0.000 | 10.935 |
Maximum of Months | 744.000 | 93.932 | 381.500 | 5.406 | 93.932 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 167.587 | 6.112 | 333.536 | 9.101 | 25.432 |
February | 248.117 | 14.494 | 226.267 | 5.905 | 27.663 |
March | 344.542 | 19.506 | 153.122 | 3.848 | 32.532 |
April | 541.715 | 43.539 | 51.500 | 1.141 | 46.984 |
May | 689.948 | 61.646 | 1.500 | 0.007 | 62.873 |
June | 720.000 | 97.560 | 0.000 | 0.000 | 97.560 |
July | 744.000 | 116.518 | 0.000 | 0.000 | 116.518 |
August | 744.000 | 104.476 | 0.000 | 0.000 | 104.476 |
September | 719.750 | 78.788 | 0.000 | 0.000 | 78.788 |
October | 640.408 | 50.850 | 24.250 | 0.341 | 53.065 |
November | 383.455 | 19.242 | 114.875 | 2.068 | 30.325 |
December | 148.262 | 4.952 | 369.667 | 11.107 | 26.562 |
Annual Sum or Average | 6091.784 | 617.684 | 1274.716 | 33.519 | 702.779 |
Minimum of Months | 148.262 | 4.952 | 0.000 | 0.000 | 25.432 |
Maximum of Months | 744.000 | 116.518 | 369.667 | 11.107 | 116.518 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 92.604 | 2.640 | 404.881 | 11.526 | 31.965 |
February | 189.040 | 10.744 | 278.713 | 7.268 | 30.935 |
March | 285.065 | 18.382 | 217.509 | 4.512 | 35.557 |
April | 491.812 | 44.018 | 68.412 | 1.382 | 49.767 |
May | 670.445 | 64.918 | 9.214 | 0.048 | 65.353 |
June | 720.000 | 103.221 | 0.000 | 0.000 | 103.221 |
July | 744.000 | 122.943 | 0.000 | 0.000 | 122.943 |
August | 744.000 | 109.286 | 0.000 | 0.000 | 109.286 |
September | 719.750 | 79.344 | 0.000 | 0.000 | 79.344 |
October | 600.910 | 45.148 | 40.027 | 0.534 | 48.334 |
November | 284.383 | 11.969 | 194.168 | 3.065 | 27.701 |
December | 66.504 | 1.610 | 445.529 | 14.023 | 37.992 |
Annual Sum or Average | 5608.515 | 614.224 | 1658.453 | 42.358 | 742.397 |
Minimum of Months | 66.504 | 1.610 | 0.000 | 0.000 | 27.701 |
Maximum of Months | 744.000 | 122.943 | 445.529 | 14.023 | 122.943 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 62.102 | 1.014 | 452.898 | 6.004 | 9.461 |
February | 187.876 | 7.243 | 299.125 | 3.695 | 11.652 |
March | 294.119 | 12.192 | 201.802 | 2.144 | 14.872 |
April | 522.675 | 32.496 | 64.573 | 0.667 | 33.171 |
May | 690.684 | 48.549 | 2.000 | 0.002 | 48.551 |
June | 720.000 | 77.959 | 0.000 | 0.000 | 77.959 |
July | 744.000 | 94.133 | 0.000 | 0.000 | 94.133 |
August | 744.000 | 83.635 | 0.000 | 0.000 | 83.635 |
September | 720.000 | 61.160 | 0.000 | 0.000 | 61.160 |
October | 637.782 | 35.561 | 38.530 | 0.200 | 35.831 |
November | 305.899 | 8.015 | 182.082 | 1.305 | 9.571 |
December | 39.323 | 0.471 | 517.005 | 7.525 | 10.641 |
Annual Sum or Average | 5668.460 | 462.429 | 1758.015 | 21.542 | 490.637 |
Minimum of Months | 39.323 | 0.471 | 0.000 | 0.000 | 9.461 |
Maximum of Months | 744.000 | 94.133 | 517.005 | 7.525 | 94.133 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 56.360 | 1.040 | 458.342 | 11.537 | 22.392 |
February | 196.794 | 8.883 | 283.783 | 6.905 | 21.898 |
March | 319.185 | 15.361 | 167.309 | 4.038 | 28.826 |
April | 537.290 | 41.665 | 53.500 | 1.161 | 45.085 |
May | 689.710 | 61.612 | 1.500 | 0.007 | 62.838 |
June | 720.000 | 98.054 | 0.000 | 0.000 | 98.054 |
July | 744.000 | 116.543 | 0.000 | 0.000 | 116.543 |
August | 744.000 | 103.526 | 0.000 | 0.000 | 103.526 |
September | 719.750 | 75.232 | 0.000 | 0.000 | 75.232 |
October | 628.638 | 43.227 | 28.250 | 0.379 | 45.363 |
November | 307.855 | 9.163 | 143.542 | 2.427 | 20.553 |
December | 35.896 | 0.461 | 528.025 | 14.250 | 23.254 |
Annual Sum or Average | 5699.477 | 574.768 | 1664.251 | 40.706 | 663.564 |
Minimum of Months | 35.896 | 0.461 | 0.000 | 0.000 | 20.553 |
Maximum of Months | 744.000 | 116.543 | 528.025 | 14.250 | 116.543 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.65 |
February | 0.00 | 0.00 | 0.76 |
March | 0.00 | 0.00 | 0.82 |
April | 0.00 | 0.00 | 1.02 |
May | 0.00 | 0.00 | 1.16 |
June | 0.00 | 0.00 | 1.41 |
July | 0.00 | 0.00 | 1.55 |
August | 0.00 | 0.00 | 1.49 |
September | 0.00 | 0.00 | 1.33 |
October | 0.00 | 0.00 | 1.12 |
November | 0.00 | 0.00 | 0.87 |
December | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.00 | 0.00 | 1.07 |
Minimum of Months | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.00 | 0.00 | 1.55 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.09 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.20 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.00 | 0.53 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.13 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.26 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.58 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.28 |
May | 0.00 | 0.00 | 0.37 |
June | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.00 | 0.76 |
August | 0.00 | 0.00 | 0.69 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.34 |
November | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.76 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.25 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.74 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.46 |
July | 0.00 | 0.00 | 0.57 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.57 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.07 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.36 |
June | 0.00 | 0.00 | 0.63 |
July | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.75 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.07 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.15 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.35 |
November | 0.00 | 0.00 | 0.17 |
December | 0.00 | 0.00 | 0.06 |
Annual Sum or Average | 0.00 | 0.00 | 0.35 |
Minimum of Months | 0.00 | 0.00 | 0.06 |
Maximum of Months | 0.00 | 0.00 | 0.72 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.21 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.42 |
October | 0.00 | 0.00 | 0.30 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.27 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.39 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.73 |
August | 0.00 | 0.00 | 0.67 |
September | 0.00 | 0.00 | 0.54 |
October | 0.00 | 0.00 | 0.36 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.34 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.73 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.10 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.72 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.18 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.21 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.22 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.05 |
March | 0.00 | 0.00 | 0.08 |
April | 0.00 | 0.00 | 0.26 |
May | 0.00 | 0.00 | 0.38 |
June | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.00 | 0.72 |
August | 0.00 | 0.00 | 0.65 |
September | 0.00 | 0.00 | 0.48 |
October | 0.00 | 0.00 | 0.27 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.72 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.06 |
February | 0.00 | 0.00 | 0.13 |
March | 0.00 | 0.00 | 0.16 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.73 |
July | 0.00 | 0.00 | 0.86 |
August | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.05 |
Maximum of Months | 0.00 | 0.00 | 0.86 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.11 |
March | 0.00 | 0.00 | 0.12 |
April | 0.00 | 0.00 | 0.25 |
May | 0.00 | 0.00 | 0.34 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.00 | 0.49 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.14 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.31 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.69 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.05 |
February | 0.00 | 0.00 | 0.12 |
March | 0.00 | 0.00 | 0.14 |
April | 0.00 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.00 | 0.87 |
August | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.00 | 0.61 |
October | 0.00 | 0.00 | 0.38 |
November | 0.00 | 0.00 | 0.15 |
December | 0.00 | 0.00 | 0.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.39 |
Minimum of Months | 0.00 | 0.00 | 0.04 |
Maximum of Months | 0.00 | 0.00 | 0.87 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.08 |
March | 0.00 | 0.00 | 0.13 |
April | 0.00 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.00 | 0.87 |
August | 0.00 | 0.00 | 0.77 |
September | 0.00 | 0.00 | 0.57 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.09 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.37 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.87 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.06 |
March | 0.00 | 0.00 | 0.09 |
April | 0.00 | 0.00 | 0.24 |
May | 0.00 | 0.00 | 0.35 |
June | 0.00 | 0.00 | 0.57 |
July | 0.00 | 0.00 | 0.69 |
August | 0.00 | 0.00 | 0.61 |
September | 0.00 | 0.00 | 0.46 |
October | 0.00 | 0.00 | 0.26 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.69 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.07 |
March | 0.00 | 0.00 | 0.11 |
April | 0.00 | 0.00 | 0.31 |
May | 0.00 | 0.00 | 0.45 |
June | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.00 | 0.87 |
August | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.36 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.87 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:28:00
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1419.34 | 1056.74 |
February | 0.00 | 0.00 | 1390.69 | 935.21 |
March | 0.00 | 0.00 | 1284.53 | 956.37 |
April | 0.00 | 0.00 | 1123.43 | 809.45 |
May | 0.00 | 0.00 | 950.96 | 708.02 |
June | 0.00 | 0.00 | 817.00 | 588.66 |
July | 0.00 | 0.00 | 755.91 | 562.80 |
August | 0.00 | 0.00 | 782.20 | 582.37 |
September | 0.00 | 0.00 | 896.03 | 645.60 |
October | 0.00 | 0.00 | 1058.32 | 787.95 |
November | 0.00 | 0.00 | 1228.54 | 885.18 |
December | 0.00 | 0.00 | 1361.45 | 1013.64 |
Annual Sum or Average | 0.00 | 0.00 | 1087.35 | 9531.97 |
Minimum of Months | 0.00 | 0.00 | 755.91 | 562.80 |
Maximum of Months | 0.00 | 0.00 | 1419.34 | 1056.74 |