Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31

Tabular Output Report in Format: HTML

Building: MF+CZ3A+USA_TN_Memphis.Intl.AP.723340+gasfurnace+unheatedbsmt+IECC_2009

Environment: ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340

Simulation Timestamp: 2019-02-14 08:31:25


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1121356.59 28.75 51.89
Net Site Energy 1121356.59 28.75 51.89
Total Source Energy 2180339.79 55.90 100.90
Net Source Energy 2180339.79 55.90 100.90


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 225922.50 0.00 0.00 0.00 0.00
Cooling 113717.40 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 263405.37 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25900.91 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 268287.96 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 463172.95 658183.65 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 225922.50 0.00 0.00 0.00 0.00
Cooling General 113717.40 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 25900.91 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 268287.96 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 6.46 22.87 0.00 0.00 0.00 19.42
Other 12.19 7.59 0.00 0.00 0.00 0.00
Total 21.43 30.46 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 3.58 12.67 0.00 0.00 0.00 10.76
Other 6.75 4.20 0.00 0.00 0.00 0.00
Total 11.87 16.87 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 463172.945 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 463172.945 100.00
     
Total On-Site and Utility Electric Sources 463172.945 100.00
Total Electricity End Uses 463172.945 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 8.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1640.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31
RunPeriod ANNUAL
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
Latitude [deg] 35.07
Longitude [deg] -90.0
Elevation [ft] 265.76
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 18953.34 7014.93 2461.74 7014.93 2461.74
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 11.22 7.58 21.60 7.58 21.60
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
UNHEATEDBSMT 7794.39 No Yes 58419.71 1.00 185.02 2590.34 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
Total 39005.17     325507.37   16363.00 2590.34 2126.74 2126.74 0.4163 1083.48 2.4729
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 4.4634
Unconditioned Total 17395.21     141767.99   1066.39 2590.34 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 11-JUL-18:15 07-JAN-07:15 - - - 01-JAN-08:15
Heating 0.00 273.34 0.00 0.00 0.00 0.00
Cooling 59.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41.30 17.85 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.14 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 149.92 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 126.95 441.10 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 273.34 0.00 0.00 0.00 0.00
Cooling General 59.38 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.52 7.91 0.00 0.00 0.00 0.00
  gas_range 0.00 7.84 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 22.66 2.10 0.00 0.00 0.00 0.00
  IECC_adj 9.39 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 9.14 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 149.92 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 244899.99 0.00 0.00 0.00
Cooling 360143.02 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 834204.80 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 82028.17 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 290824.15 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1466868.72 713471.08 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 11.33 0.00 0.00 0.00
Cooling 16.67 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.80 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.46 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 67.88 33.02 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 11.33 0.00 0.00 0.00
Cooling 16.67 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 3.80 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.46 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 67.88 33.02 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 17.06 0.00 17.06 Wetbulb [F] 807.13 0.00
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 96.08 16.56 77.36 Wetbulb [F] 748.07 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.501 0.258 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.501 0.258 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.501 0.258 0.882              
North Total or Average           531.68 0.501 0.258 0.882              
Non-North Total or Average           1595.05 0.501 0.258 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.351 0.500 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   26792.46 20123.14 6669.31 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10895.14 7402.96 3492.18 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13191.88 9019.13 4172.75 0.68 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   16259.82 11560.97 4698.86 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10724.04 7304.24 3419.80 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12284.60 8541.07 3743.52 0.70 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15941.85 11506.65 4435.20 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10583.35 7318.62 3264.73 0.69 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12754.41 8829.74 3924.66 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15713.90 11322.05 4391.86 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10508.44 7275.56 3232.89 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11830.71 8319.32 3511.40 0.70 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18930.89 13711.65 5219.24 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13522.24 9484.96 4037.28 0.70 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15110.31 10673.11 4437.19 0.71 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18866.88 13676.95 5189.92 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13556.30 9511.88 4044.41 0.70 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15101.36 10666.00 4435.37 0.71 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.1 3.35 11.43 12.11 11.76
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.49 11.91 12.65 12.57
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.1 3.48 11.88 12.61 12.52
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.3 3.43 11.70 12.41 12.20
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.49 11.90 12.63 12.55
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.0 3.46 11.80 12.53 12.38
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.41 11.62 12.33 12.08
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.9 3.47 11.83 12.55 12.43
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.0 3.47 11.82 12.55 12.42
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.3 3.41 11.63 12.33 12.09
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.47 11.82 12.55 12.42
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.0 3.44 11.75 12.47 12.29
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.5 3.40 11.60 12.31 12.05
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.1 3.45 11.76 12.48 12.31
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.2 3.44 11.73 12.44 12.26
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.5 3.40 11.60 12.30 12.05
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.45 11.76 12.48 12.31
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.2 3.44 11.73 12.44 12.26
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   5075.80 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   12025.96 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   14892.79 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   14898.50 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   12032.16 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   14895.44 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   12749.29 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   9852.22 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   12753.24 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   12761.90 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   9860.93 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   12759.03 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   16516.70 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   13620.69 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   16518.74 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   16532.50 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   13634.54 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   16530.44 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 874.95 330.02 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 276.20 104.18 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 340.10 128.28 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 464.53 175.22 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 273.66 103.22 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 331.22 124.93 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 472.97 178.40 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 281.31 106.11 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 340.02 128.25 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 464.16 175.08 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 280.21 105.69 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 328.56 123.93 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 566.50 213.68 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 373.10 140.73 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 424.49 160.12 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 565.78 213.41 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 374.35 141.20 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 424.16 159.99 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20357.09 20357.09 16.96 874.946 874.946 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00877 92.93 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6426.53 6426.53 5.35 276.204 276.204 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.01002 91.48 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7910.77 7910.77 6.59 340.102 340.102 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.97 0.00970 96.08 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10808.16 10808.16 9.00 464.529 464.529 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00935 92.93 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6367.21 6367.21 5.30 273.656 273.656 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.01006 90.24 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7706.73 7706.73 6.42 331.223 331.223 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 74.98 74.98 0.00972 90.41 0.01615 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11004.94 11004.94 9.17 472.970 472.970 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00906 92.52 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6545.50 6545.50 5.45 281.310 281.310 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00962 90.24 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7909.55 7909.55 6.59 340.016 340.016 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.98 0.00933 96.08 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10799.93 10799.93 9.00 464.159 464.159 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00908 92.52 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6519.89 6519.89 5.43 280.210 280.210 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00964 89.62 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7644.89 7644.89 6.37 328.557 328.557 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:15:00 74.98 74.98 0.00938 90.41 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9868.92 9868.92 8.22 424.160 424.160 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00947 92.11 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9876.66 9876.66 8.23 424.492 424.492 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00947 92.11 0.01615 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 13180.70 13180.70 10.98 566.501 566.501 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00914 92.93 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8710.07 8710.07 7.26 374.351 374.351 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00959 90.86 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8681.01 8681.01 7.23 373.102 373.102 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00960 90.86 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 13163.85 13163.85 10.96 565.776 565.776 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00915 92.52 0.01615 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2461.26 2461.26 2.05 45.224 45.224 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.99 0.00388 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 9514.58 9514.58 7.93 174.794 174.794 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00583 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12423.86 12423.86 10.35 228.234 228.234 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00607 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12429.65 12429.65 10.35 228.340 228.340 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00608 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9520.87 9520.87 7.93 174.909 174.909 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00583 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12426.54 12426.54 10.35 228.283 228.283 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00608 17.06 0.00188 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10248.42 10248.42 8.54 188.289 188.289 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00637 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7308.46 7308.46 6.09 134.279 134.279 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00612 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10252.43 10252.43 8.54 188.363 188.363 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00637 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10261.22 10261.22 8.55 188.524 188.524 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00637 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7317.29 7317.29 6.09 134.441 134.441 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00612 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10258.31 10258.31 8.54 188.471 188.471 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00637 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 14085.73 14085.73 11.73 258.763 258.763 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00623 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 14073.85 14073.85 11.72 258.544 258.544 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00623 17.06 0.00188 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14071.78 14071.78 11.72 258.506 258.506 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00623 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11146.95 11146.95 9.28 204.782 204.782 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00604 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11132.89 11132.89 9.27 204.523 204.523 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00603 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14087.81 14087.81 11.73 258.801 258.801 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00623 17.06 0.00188 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 874.95 874.95 45.22 45.22
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 276.20 276.20 174.79 174.79
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.10 340.10 228.23 228.23
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 464.53 464.53 228.34 228.34
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 273.66 273.66 174.91 174.91
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 331.22 331.22 228.28 228.28
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.97 472.97 188.29 188.29
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 281.31 281.31 134.28 134.28
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 340.02 340.02 188.36 188.36
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 464.16 464.16 188.52 188.52
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 280.21 280.21 134.44 134.44
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 328.56 328.56 188.47 188.47
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 566.50 566.50 258.51 258.51
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 373.10 373.10 204.52 204.52
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 424.49 424.49 258.54 258.54
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 565.78 565.78 258.80 258.80
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 374.35 374.35 204.78 204.78
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 424.16 424.16 258.76 258.76


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2375.00 4297.50 109.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3602.00 4776.75 921.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3889.25 4760.25 983.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3935.50 5363.75 1304.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3511.25 5221.50 969.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3845.75 5138.00 1089.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4045.50 4309.00 668.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3643.25 3946.75 340.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3910.00 4156.50 556.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3957.25 4663.50 768.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3541.75 4380.00 364.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3863.50 4520.25 629.75
LIVING_UNIT3_BACKROW_TOPFLOOR 4278.00 4806.25 1100.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 4289.25 4581.25 1028.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 4356.00 4816.25 1213.75
LIVING_UNIT2_BACKROW_TOPFLOOR 3910.50 4835.25 862.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 3935.75 4568.50 806.50
LIVING_UNIT1_BACKROW_TOPFLOOR 4343.00 5020.25 1314.25
UNHEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4713.50 5792.25 1640.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 6.00 0.00 6.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 8.00 0.00 8.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 6.00 0.00 6.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 6.25 0.00 6.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 3.25 0.00 3.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 6.50 0.00 6.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
UNHEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 8.25 0.00 8.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.248 0.000 0.271
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.215 0.000 0.271
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.244 0.000 0.271
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.244 0.000 0.271
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.215 0.000 0.271
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.244 0.000 0.271
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.107 0.000 0.271
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.078 0.000 0.271
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.107 0.000 0.271
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.107 0.000 0.271
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.078 0.000 0.271
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.107 0.000 0.271
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.244 0.000 0.271
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.244 0.000 0.271
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.244 0.000 0.271
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.215 0.000 0.271
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.215 0.000 0.271
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.244 0.000 0.271
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1878
Defaulted Fields 500
Fields with Defaults 4920
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
Electricity:Building 91754.37 7056.43 02-JAN-03:15 17558.18 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 77145.04 6525.11 02-JAN-04:15 12799.44 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
Fans:Electricity 7585.75 94.02 23-FEB-23:30 2735.07 29-AUG-16:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
ElectricityPurchased:Plant 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
Cogeneration:ElectricityPurchased 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
ElectricityNet:Plant 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
Cogeneration:ElectricityNet 135652.12 8167.60 18-OCT-03:15 37180.49 11-JUL-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 40890.82 469.90 02-APR-23:15 21076.07 29-AUG-15:30
General:Fans:Electricity 7585.75 94.02 23-FEB-23:30 2735.07 29-AUG-16:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 33305.07 0.00 02-JAN-22:15 18361.49 29-AUG-15:30
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 6581.84 2644.47 18-JAN-03:15 440790.30 07-JAN-07:15
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 2682.88 0.00 01-JAN-00:15 150194.16 12-FEB-08:15
WaterSystems:Gas 2682.88 0.00 01-JAN-00:15 150194.16 12-FEB-08:15
Water Heater:WaterSystems:Gas 2682.88 0.00 01-JAN-00:15 150194.16 12-FEB-08:15
Gas:HVAC 2259.22 0.00 13-JAN-15:15 281213.71 31-JAN-04:00
Heating:Gas 2259.22 0.00 13-JAN-15:15 281213.71 31-JAN-04:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 03-JAN-02:45 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
PlantLoopHeatingDemand:Plant 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
WaterSystems:PlantLoopHeatingDemand 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1341199.44 16167.71 09-APR-02:15 485752.86 31-JAN-07:00
EnergyTransfer:Building 536410.91 6573.07 23-FEB-23:30 234057.06 31-JAN-04:00
EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 187346.02 0.00 13-JAN-15:15 234057.06 31-JAN-04:00
Heating:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 349064.88 0.00 02-JAN-22:15 179978.11 27-AUG-16:30
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 78690.45 0.00 02-JAN-22:15 20721.97 01-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 263.20 0.00 01-JAN-00:15 6034.23 31-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 78427.25 0.00 02-JAN-22:15 20721.97 01-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21014.05 0.00 09-JAN-13:45 12110.93 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8158.50 0.00 09-JAN-13:45 12110.93 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12855.56 0.00 01-JAN-00:15 7205.21 29-AUG-18:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 27941.35 0.00 10-JAN-13:15 15356.31 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11882.83 0.00 10-JAN-13:15 15356.31 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16058.52 0.00 01-JAN-00:15 9289.10 27-AUG-14:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 28341.65 0.00 13-JAN-14:15 15496.51 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13671.57 0.00 13-JAN-14:15 15496.51 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14670.08 0.00 01-JAN-00:15 11543.67 01-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21047.91 0.00 13-JAN-15:15 12154.01 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 9996.66 0.00 13-JAN-15:15 12154.01 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11051.25 0.00 01-JAN-00:15 6910.18 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 27673.58 0.00 13-JAN-14:15 15352.62 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13420.98 0.00 13-JAN-14:15 15352.62 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14252.60 0.00 01-JAN-00:15 8352.91 02-JUL-10:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 26461.00 0.00 04-JAN-14:00 11712.83 28-AUG-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8332.69 0.00 04-JAN-14:00 11703.54 07-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18128.31 0.00 01-JAN-00:15 11712.83 28-AUG-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 19893.79 0.00 04-JAN-13:45 8255.55 07-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5354.16 0.00 04-JAN-13:45 8255.55 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14539.62 0.00 01-JAN-00:15 7284.08 29-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 26361.40 0.00 09-JAN-13:45 11650.51 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8727.77 0.00 09-JAN-13:45 11650.51 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17633.62 0.00 01-JAN-00:15 9154.07 27-AUG-14:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 26407.22 0.00 13-JAN-14:15 11732.72 07-JAN-07:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10310.44 0.00 13-JAN-14:15 11732.72 07-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 16096.79 0.00 01-JAN-00:15 11378.14 01-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 19347.25 0.00 13-JAN-14:45 8364.83 07-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6740.94 0.00 13-JAN-14:45 8364.83 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12606.31 0.00 01-JAN-00:15 6827.29 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 25842.28 0.00 13-JAN-13:45 11692.87 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10098.53 0.00 13-JAN-13:45 11692.87 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15743.75 0.00 01-JAN-00:15 8321.76 02-JUL-10:15
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 33342.77 0.00 13-JAN-14:15 17021.81 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 15165.03 0.00 13-JAN-14:15 17021.81 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18177.74 0.00 01-JAN-00:15 10947.45 27-AUG-15:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 33083.60 0.00 13-JAN-11:15 16975.22 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 13864.54 0.00 13-JAN-11:15 16975.22 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19219.06 0.00 01-JAN-00:15 11131.14 27-AUG-15:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 33777.96 0.00 09-JAN-15:15 16882.20 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 14059.51 0.00 09-JAN-15:15 16882.20 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 19718.45 0.00 01-JAN-00:15 13909.33 28-AUG-16:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 26694.39 0.00 13-JAN-14:45 13570.83 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 11602.14 0.00 13-JAN-14:45 13570.83 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 15092.24 0.00 01-JAN-00:15 9175.50 27-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 26388.13 0.00 10-JAN-14:15 13520.32 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10229.08 0.00 10-JAN-14:15 13520.32 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 16159.05 0.00 01-JAN-00:15 9301.08 27-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 34102.13 0.00 13-JAN-14:15 16934.53 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 15467.46 0.00 13-JAN-14:15 16934.53 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18634.67 0.00 01-JAN-00:15 13841.66 28-AUG-16:45
EnergyTransfer:Plant 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
WaterSystems:EnergyTransfer 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 136309.84 986.40 02-AUG-03:00 39209.01 29-JAN-08:30
EnergyTransfer:HVAC 668478.70 7219.47 23-FEB-23:30 238817.77 11-JUL-17:30
HeatingCoils:EnergyTransfer 180738.00 0.00 13-JAN-15:15 224970.96 31-JAN-04:00
CoolingCoils:EnergyTransfer 487740.70 0.00 02-JAN-22:15 238817.77 11-JUL-17:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 263.189 -6531.24 0.000 0.000 2883.419 2771.241 14528.036 8327.656 0.000 1734.326 67739.542 0.000 -6234.32 0.000 -13585.81 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 8158.387 -1070.58 0.000 0.000 2992.844 2771.241 14528.036 3623.792 0.000 1637.757 0.000 0.000 -2389.20 0.000 -11724.75 -6742.57
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 11882.674 -1337.32 0.000 0.000 3005.197 2771.241 14528.036 8205.858 0.000 1733.038 0.000 0.000 -5710.14 0.000 -12431.40 -7925.99
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 13671.410 -1221.68 0.000 0.000 3011.789 2771.241 14528.036 6381.121 0.000 1734.230 0.000 0.000 -6188.25 0.000 -12316.38 -8923.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 9996.544 -920.33 0.000 0.000 3004.066 2771.241 14528.036 1399.309 0.000 1638.315 0.000 0.000 -2636.39 0.000 -11586.85 -8062.99
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 13420.824 -1186.93 0.000 0.000 3012.754 2771.241 14528.036 6075.907 0.000 1733.535 0.000 0.000 -5946.13 0.000 -12328.80 -9014.74
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 8332.570 -1509.67 0.000 0.000 2989.154 2771.241 14528.036 8345.319 0.000 1277.946 0.000 0.000 -6083.04 0.000 -8889.79 -5143.26
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 5354.086 -1210.83 0.000 0.000 2976.105 2771.241 14528.036 3590.491 0.000 1182.458 0.000 0.000 -2456.54 0.000 -8167.78 -5238.47
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 8727.654 -1468.49 0.000 0.000 2991.529 2771.241 14528.036 8125.101 0.000 1277.614 0.000 0.000 -5875.98 0.000 -8886.44 -6025.12
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 10310.316 -1340.50 0.000 0.000 2998.505 2771.241 14528.036 6323.033 0.000 1278.107 0.000 0.000 -6365.20 0.000 -8800.02 -6947.31
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 6740.862 -1049.83 0.000 0.000 2987.908 2771.241 14528.036 1383.397 0.000 1182.557 0.000 0.000 -2713.05 0.000 -8070.00 -6204.59
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 10098.407 -1311.11 0.000 0.000 2999.835 2771.241 14528.036 6012.579 0.000 1277.887 0.000 0.000 -6116.10 0.000 -8810.46 -7017.61
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 15164.864 -1513.80 0.000 0.000 3008.993 2771.241 14528.036 5967.971 0.000 1720.515 0.000 0.000 -6089.61 0.000 -12393.16 -6501.10
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 13864.380 -1600.52 0.000 0.000 3004.011 2771.241 14528.036 8107.452 0.000 1719.960 0.000 0.000 -5822.63 0.000 -12459.38 -6494.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 14059.348 -1642.09 0.000 0.000 3004.102 2771.241 14528.036 8331.404 0.000 1720.831 0.000 0.000 -5983.84 0.000 -12440.65 -6272.20
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 11602.023 -1256.85 0.000 0.000 3000.220 2771.241 14528.036 1361.468 0.000 1625.781 0.000 0.000 -2691.67 0.000 -11656.45 -5448.41
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 10228.956 -1345.69 0.000 0.000 2993.855 2771.241 14528.036 3581.632 0.000 1625.582 0.000 0.000 -2423.27 0.000 -11733.19 -5413.82
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 15467.290 -1551.84 0.000 0.000 3008.383 2771.241 14528.036 6253.767 0.000 1721.021 0.000 0.000 -6312.99 0.000 -12380.94 -6421.29
UNHEATEDBSMT 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5316.022 46019.247 0.000 0.000 0.000 -51335.27 -0.01
Total Facility 0.000 0.000 187343.787 -29069.27 0.000 0.000 53872.669 49882.340 261504.651 101397.255 0.000 33137.483 113758.789 0.000 -88038.33 0.000 -249997.51 -113796.73


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 01-JUL-17:06 0.00 0.00 0.00 -1.7 0.00 0.00 263.36 604.65 2787.26 5969.36 0.00 1913.22 9238.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-AUG-18:41 0.00 0.00 0.00 -0.6 0.00 0.00 423.89 813.96 2666.18 330.57 0.00 1414.30 1594.44 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 27-AUG-14:00 0.00 0.00 0.00 -0.8 0.00 0.00 115.20 116.28 1581.84 3296.56 0.00 2239.70 1944.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 01-JUL-17:19 0.00 0.00 0.00 -1.0 0.00 0.00 263.36 604.65 2787.26 5933.90 0.00 1850.64 106.63 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11-JUL-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.08 813.96 2666.18 685.90 0.00 1746.41 571.41 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 02-JUL-09:45 0.00 0.00 0.00 -0.7 0.00 0.00 114.08 116.28 1603.33 4846.73 0.00 1405.58 280.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 28-AUG-16:21 0.00 0.00 0.00 -1.0 0.00 0.00 140.45 434.11 2094.81 6356.73 0.00 1385.44 1302.88 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-AUG-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.07 813.96 2666.18 467.63 0.00 1176.55 1733.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27-AUG-14:00 0.00 0.00 0.00 -0.8 0.00 0.00 115.19 116.28 1581.84 3306.61 0.00 1596.34 2441.57 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 01-JUL-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 263.35 604.65 2787.26 5905.05 0.00 1312.35 507.85 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11-JUL-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.07 813.96 2666.18 686.66 0.00 1166.97 1067.40 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 02-JUL-10:12 0.00 0.00 0.00 -0.7 0.00 0.00 114.78 116.28 1582.09 3791.95 0.00 1124.28 1602.83 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 27-AUG-15:10 0.00 0.00 0.00 -0.9 0.00 0.00 115.18 201.55 1705.67 2410.61 0.00 2208.32 4306.23 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 27-AUG-15:38 0.00 0.00 0.00 -0.9 0.00 0.00 115.00 201.55 1705.67 2314.53 0.00 2161.59 4653.07 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 28-AUG-16:33 0.00 0.00 0.00 -1.2 0.00 0.00 140.14 434.11 2094.81 5791.42 0.00 1879.71 3574.35 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -0.8 0.00 0.00 263.34 604.65 2787.26 608.48 0.00 1757.55 3154.76 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -0.8 0.00 0.00 263.34 604.65 2787.26 585.34 0.00 1757.55 3303.46 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 28-AUG-16:36 0.00 0.00 0.00 -1.2 0.00 0.00 140.30 434.11 2094.81 5786.02 0.00 1883.30 3504.30 0.00 0.00 0.00 0.00 0.00
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-AUG-16:30 0.00 0.00 0.00 -15.0 0.00 0.00 2528.05 7813.98 38253.58 48073.88 0.00 32820.81 65734.28 0.00 0.00 0.00 -15002.3 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 31-JAN-05:00 0.00 0.00 6033.95 0.00 0.00 0.00 526.31 186.05 1036.84 0.00 0.00 0.00 5657.66 0.00 -3697.8 0.00 -9743.0 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 12110.27 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -1479.0 0.00 -9146.9 -3111.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 15355.49 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3713.2 0.00 -9958.0 -3311.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 15495.69 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3684.5 0.00 -9970.3 -3468.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 12153.35 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -1538.9 0.00 -9146.9 -3094.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 15351.79 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3771.5 0.00 -9955.1 -3252.4
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 07-JAN-07:00 0.00 0.00 11703.28 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -3982.2 0.00 -5888.4 -4235.3
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 07-JAN-05:00 0.00 0.00 8255.01 0.00 0.00 0.00 526.31 186.05 1039.59 0.00 0.00 0.00 0.00 0.00 -1581.6 0.00 -5153.3 -3272.0
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 31-JAN-04:00 0.00 0.00 11649.85 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3779.9 0.00 -6099.1 -3398.0
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 07-JAN-07:00 0.00 0.00 11732.46 0.00 0.00 0.00 526.31 434.11 1442.24 0.00 0.00 0.00 0.00 0.00 -4032.6 0.00 -5888.4 -4214.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 07-JAN-08:15 0.00 0.00 8364.59 0.00 0.00 0.00 215.05 170.54 1655.54 0.00 0.00 0.00 0.00 0.00 -1481.2 0.00 -5059.4 -3865.2
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 31-JAN-04:00 0.00 0.00 11692.21 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3844.9 0.00 -6099.1 -3375.4
LIVING_UNIT3_BACKROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 17020.90 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3833.7 0.00 -9983.2 -4831.3
LIVING_UNIT3_FRONTROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 16974.32 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3766.8 0.00 -9983.2 -4851.7
LIVING_UNIT1_FRONTROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 16881.31 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3666.6 0.00 -9983.2 -4858.8
LIVING_UNIT2_BACKROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 13570.10 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -1562.8 0.00 -9158.6 -4475.9
LIVING_UNIT2_FRONTROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 13519.59 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -1493.8 0.00 -9158.6 -4494.4
LIVING_UNIT1_BACKROW_TOPFLOOR 31-JAN-04:00 0.00 0.00 16933.64 0.00 0.00 0.00 526.31 62.02 1038.94 0.00 0.00 0.00 0.00 0.00 -3733.5 0.00 -9983.2 -4844.3
UNHEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 31-JAN-04:00 0.00 0.00 234044.37 0.00 0.00 0.00 9473.52 1116.28 18700.98 0.00 0.00 0.00 0.00 0.00 -53998.8 0.00 -154774.6 -54561.8



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 874.946 2.00 2.00 1.00 44.9950 874.946 0.051 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 276.204 2.00 2.00 1.00 44.9950 276.204 0.163 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.102 2.00 2.00 1.00 44.9950 340.102 0.132 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 464.529 2.00 2.00 1.00 44.9950 464.529 0.097 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 273.656 2.00 2.00 1.00 44.9950 273.656 0.164 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 331.223 2.00 2.00 1.00 44.9950 331.223 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.970 2.00 2.00 1.00 44.9950 472.970 0.095 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 281.310 2.00 2.00 1.00 44.9950 281.310 0.160 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 340.016 2.00 2.00 1.00 44.9950 340.016 0.132 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 464.159 2.00 2.00 1.00 44.9950 464.159 0.097 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 280.210 2.00 2.00 1.00 44.9950 280.210 0.161 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 328.557 2.00 2.00 1.00 44.9950 328.557 0.137 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 566.501 2.00 2.00 1.00 44.9950 566.501 0.079 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 373.102 2.00 2.00 1.00 44.9950 373.102 0.121 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 424.492 2.00 2.00 1.00 44.9950 424.492 0.106 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 565.776 2.00 2.00 1.00 44.9950 565.776 0.080 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 374.351 2.00 2.00 1.00 44.9950 374.351 0.120 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 424.160 2.00 2.00 1.00 44.9950 424.160 0.106 1.000 44.9950 0.11


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 45.224 2.00 2.00 1.00 44.9950 45.224 1.000 1.000 44.9950 0.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 174.794 2.00 2.00 1.00 44.9950 174.794 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 228.234 2.00 2.00 1.00 44.9950 228.234 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 228.340 2.00 2.00 1.00 44.9950 228.340 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 174.909 2.00 2.00 1.00 44.9950 174.909 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 228.283 2.00 2.00 1.00 44.9950 228.283 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 188.289 2.00 2.00 1.00 44.9950 188.289 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 134.279 2.00 2.00 1.00 44.9950 134.279 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 188.363 2.00 2.00 1.00 44.9950 188.363 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 188.524 2.00 2.00 1.00 44.9950 188.524 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 134.441 2.00 2.00 1.00 44.9950 134.441 1.000 1.000 44.9950 0.33
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 188.471 2.00 2.00 1.00 44.9950 188.471 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 258.506 2.00 2.00 1.00 44.9950 258.506 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 204.523 2.00 2.00 1.00 44.9950 204.523 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 258.544 2.00 2.00 1.00 44.9950 258.544 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 258.801 2.00 2.00 1.00 44.9950 258.801 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 204.782 2.00 2.00 1.00 44.9950 204.782 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 258.763 2.00 2.00 1.00 44.9950 258.763 1.000 1.000 44.9950 0.17


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   874.946 874.9460 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   276.204 276.2043 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   340.102 340.1017 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   464.529 464.5291 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   273.656 273.6555 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   331.223 331.2232 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   472.970 472.9700 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   281.310 281.3101 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   340.016 340.0161 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   464.159 464.1592 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   280.210 280.2098 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   328.557 328.5568 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   424.160 424.1598 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   424.492 424.4924 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   566.501 566.5009 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   374.351 374.3508 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   373.102 373.1019 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   565.776 565.7758 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 874.95 874.946 874.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 276.20 276.204 276.20 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.10 340.102 340.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 464.53 464.529 464.53 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 273.66 273.656 273.66 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 331.22 331.223 331.22 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.97 472.970 472.97 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 281.31 281.310 281.31 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 340.02 340.016 340.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 464.16 464.159 464.16 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 280.21 280.210 280.21 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 328.56 328.557 328.56 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 566.50 566.501 566.50 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 373.10 373.102 373.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 424.49 424.492 424.49 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 565.78 565.776 565.78 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 374.35 374.351 374.35 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 424.16 424.160 424.16 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   45.224 45.224 45.224 44.9950 0.995 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   174.794 174.794 174.794 44.9950 0.257 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   228.234 228.234 228.234 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   228.340 228.340 228.340 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   174.909 174.909 174.909 44.9950 0.257 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   228.283 228.283 228.283 44.9950 0.197 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   188.289 188.289 188.289 44.9950 0.239 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   134.279 134.279 134.279 44.9950 0.335 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   188.363 188.363 188.363 44.9950 0.239 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   188.524 188.524 188.524 44.9950 0.239 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   134.441 134.441 134.441 44.9950 0.335 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   188.471 188.471 188.471 44.9950 0.239 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   258.763 258.763 258.763 44.9950 0.174 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   258.544 258.544 258.544 44.9950 0.174 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   258.506 258.506 258.506 44.9950 0.174 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   204.782 204.782 204.782 44.9950 0.220 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   204.523 204.523 204.523 44.9950 0.220 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   258.801 258.801 258.801 44.9950 0.174 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 45.22 45.224 45.22 45.22 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 174.79 174.794 174.79 174.79 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 228.23 228.234 228.23 228.23 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 228.34 228.340 228.34 228.34 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 174.91 174.909 174.91 174.91 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 228.28 228.283 228.28 228.28 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 188.29 188.289 188.29 188.29 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 134.28 134.279 134.28 134.28 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 188.36 188.363 188.36 188.36 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 188.52 188.524 188.52 188.52 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 134.44 134.441 134.44 134.44 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 188.47 188.471 188.47 188.47 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 258.51 258.506 258.51 258.51 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 204.52 204.523 204.52 204.52 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 258.54 258.544 258.54 258.54 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 258.80 258.801 258.80 258.80 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 204.78 204.782 204.78 204.78 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 258.76 258.763 258.76 258.76 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Sec1.1A-General Information

Data
Weather File ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
UNHEATEDBSMT 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 8.25
Number of hours not met 8.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 2259.22 273142.72 0.00 0.00
Space Cooling 33305.07 17390.79 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 7585.75 2676.96 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2682.88 149813.57 0.00 0.00
Receptacle Equipment 77145.04 12095.32 1639.73 17834.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 135652.12   6581.84   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 263405.37 463172.95
Natural Gas 163973.19 658183.65
Additional 0.00 0.00
Total 427378.56 1121356.59


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 0.85
Fans-Interior 0.19
Service Water Heating 0.00
Receptacle Equipment 1.98
Miscellaneous 0.08
Subtotal 3.48


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 1.70
Service Water Heating 2.01
Miscellaneous 1.23
Subtotal 4.94


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.45
Space Heating 20.15
Space Cooling 10.14
Fans-Interior 2.31
Service Water Heating 23.93
Receptacle Equipment 38.11
Miscellaneous 0.92



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 874.95
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 276.20
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 340.10
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 464.53
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 273.66
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 331.22
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 472.97
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 281.31
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 340.02
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 464.16
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 280.21
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 328.56
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 424.16
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 424.49
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 566.50
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 374.35
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 373.10
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 565.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 874.95
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 276.20
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.10
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 464.53
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 273.66
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 331.22
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 472.97
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 281.31
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 340.02
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 464.16
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 280.21
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 328.56
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 566.50
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 373.10
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 424.49
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 565.78
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 374.35
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 424.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 874.95 2.23 0.751075
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 276.20 0.907928 0.679474
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 340.10 1.10 0.683688
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 464.53 1.35 0.711014
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 273.66 0.893670 0.681109
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 331.22 1.02 0.695267
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 472.97 1.33 0.721789
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 281.31 0.881946 0.691522
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 340.02 1.06 0.692290
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 464.16 1.31 0.720512
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 280.21 0.875703 0.692353
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 328.56 0.985892 0.703197
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 566.50 1.58 0.724300
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 373.10 1.13 0.701434
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 424.49 1.26 0.706347
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 565.78 1.57 0.724919
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 374.35 1.13 0.701658
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 424.16 1.26 0.706294
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 874.95 874.95 874.95 5075.80 2.23 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 276.20 276.20 276.20 12025.96 0.907928 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 340.10 340.10 340.10 14892.79 1.10 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 464.53 464.53 464.53 14898.50 1.35 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 273.66 273.66 273.66 12032.16 0.893670 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 331.22 331.22 331.22 14895.44 1.02 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 472.97 472.97 472.97 12749.29 1.33 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 281.31 281.31 281.31 9852.22 0.881946 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 340.02 340.02 340.02 12753.24 1.06 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 464.16 464.16 464.16 12761.90 1.31 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 280.21 280.21 280.21 9860.93 0.875703 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 328.56 328.56 328.56 12759.03 0.985892 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 566.50 566.50 566.50 16516.70 1.58 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 373.10 373.10 373.10 13620.69 1.13 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 424.49 424.49 424.49 16518.74 1.26 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 565.78 565.78 565.78 16532.50 1.57 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 374.35 374.35 374.35 13634.54 1.13 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 424.16 424.16 424.16 16530.44 1.26 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 874.95
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 276.20
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 340.10
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 464.53
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 273.66
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 331.22
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 472.97
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 281.31
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 340.02
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 464.16
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 280.21
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 328.56
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 566.50
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 373.10
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 424.49
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 565.78
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 374.35
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 424.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 5075.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 12025.96
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 14892.79
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 14898.50
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 12032.16
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 14895.44
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 12749.29
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 9852.22
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 12753.24
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 12761.90
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 9860.93
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 12759.03
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 16516.70
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 13620.69
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 16518.74
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 16532.50
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 13634.54
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 16530.44
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 529.614 35.346 86.125 12.374 47.720
February 556.179 40.232 19.667 1.430 41.662
March 736.012 77.145 0.000 0.000 77.145
April 720.000 96.655 0.000 0.000 96.655
May 744.000 131.461 0.000 0.000 131.461
June 720.000 149.403 0.000 0.000 149.403
July 744.000 167.444 0.000 0.000 167.444
August 744.000 162.891 0.000 0.000 162.891
September 720.000 142.031 0.000 0.000 142.031
October 744.000 102.138 0.000 0.000 102.138
November 708.771 72.785 0.000 0.000 72.785
December 646.462 46.575 6.500 0.190 46.766
           
Annual Sum or Average 8313.038 1224.106 112.292 13.995 1238.101
Minimum of Months 529.614 35.346 0.000 0.000 41.662
Maximum of Months 744.000 167.444 86.125 12.374 167.444



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 42.125 0.671 623.542 22.961 23.632
February 72.320 1.206 490.208 15.375 16.581
March 180.752 4.023 339.408 6.196 10.218
April 360.671 8.790 146.950 2.154 10.944
May 604.808 21.337 8.125 0.024 21.362
June 695.458 33.890 0.000 0.000 33.890
July 744.000 43.002 0.000 0.000 43.002
August 733.463 40.508 0.000 0.000 40.508
September 670.488 30.944 3.250 0.011 30.954
October 401.846 11.196 132.531 1.389 12.585
November 202.153 4.278 317.903 5.869 10.147
December 42.688 0.543 550.867 14.622 15.164
           
Annual Sum or Average 4750.772 200.387 2612.783 68.600 268.987
Minimum of Months 42.125 0.543 0.000 0.000 10.147
Maximum of Months 744.000 43.002 623.542 22.961 43.002



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 33.062 0.499 661.563 31.805 32.304
February 63.920 1.199 523.317 21.494 22.693
March 176.490 4.717 384.854 9.162 13.879
April 352.620 11.117 163.125 3.290 14.406
May 597.770 27.379 20.625 0.145 27.524
June 687.901 42.880 4.250 0.017 42.897
July 744.000 54.425 0.000 0.000 54.425
August 726.617 50.625 0.000 0.000 50.625
September 663.355 37.217 8.000 0.053 37.270
October 378.997 12.267 178.225 2.710 14.977
November 175.773 4.059 370.771 9.210 13.268
December 32.375 0.422 601.158 21.478 21.900
           
Annual Sum or Average 4632.880 246.804 2915.888 99.364 346.168
Minimum of Months 32.375 0.422 0.000 0.000 13.268
Maximum of Months 744.000 54.425 661.563 31.805 54.425



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 13.583 0.084 688.575 47.903 47.987
February 25.104 0.387 571.238 32.291 32.678
March 135.595 4.009 435.011 14.238 18.248
April 288.295 11.064 200.250 5.253 16.318
May 558.330 28.971 30.467 0.271 29.242
June 681.410 47.231 5.500 0.027 47.258
July 744.000 59.494 0.000 0.000 59.494
August 723.068 54.364 0.000 0.000 54.364
September 645.981 37.085 12.083 0.094 37.179
October 299.037 9.288 239.396 4.827 14.115
November 103.208 1.723 448.558 14.969 16.692
December 22.625 0.218 660.042 34.602 34.821
           
Annual Sum or Average 4240.238 253.920 3291.120 154.475 408.395
Minimum of Months 13.583 0.084 0.000 0.000 14.115
Maximum of Months 744.000 59.494 688.575 47.903 59.494



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 12.250 0.104 680.563 26.955 27.059
February 16.458 0.111 556.833 17.714 17.824
March 116.062 1.727 396.562 7.507 9.234
April 314.674 6.726 173.504 2.476 9.202
May 601.961 20.605 8.625 0.028 20.633
June 695.576 33.790 0.000 0.000 33.790
July 744.000 42.647 0.000 0.000 42.647
August 733.575 38.595 0.000 0.000 38.595
September 664.626 27.090 3.750 0.014 27.104
October 296.770 6.102 193.708 1.968 8.070
November 94.033 1.160 411.250 7.589 8.749
December 24.625 0.220 653.875 19.010 19.230
           
Annual Sum or Average 4314.612 178.876 3078.671 83.261 262.137
Minimum of Months 12.250 0.104 0.000 0.000 8.070
Maximum of Months 744.000 42.647 680.563 26.955 42.647



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 6.875 0.048 693.792 34.623 34.670
February 16.563 0.125 574.825 22.926 23.051
March 130.030 2.448 425.163 9.907 12.355
April 321.997 9.235 169.750 3.365 12.600
May 594.916 27.432 20.125 0.139 27.571
June 689.263 43.919 4.000 0.016 43.935
July 744.000 55.503 0.000 0.000 55.503
August 726.792 50.149 0.000 0.000 50.149
September 662.288 34.560 8.750 0.053 34.613
October 304.175 7.274 217.679 3.038 10.312
November 76.667 1.007 443.696 10.451 11.458
December 19.125 0.152 667.367 24.842 24.994
           
Annual Sum or Average 4292.690 231.852 3225.146 109.359 341.211
Minimum of Months 6.875 0.048 0.000 0.000 10.312
Maximum of Months 744.000 55.503 693.792 34.623 55.503



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 49.833 1.208 596.921 36.395 37.603
February 79.683 2.340 478.400 24.909 27.249
March 215.964 8.290 311.125 9.712 18.001
April 389.621 16.118 142.217 3.415 19.534
May 624.230 33.629 12.250 0.065 33.694
June 695.893 50.780 0.000 0.000 50.780
July 744.000 62.973 0.000 0.000 62.973
August 734.700 59.803 0.000 0.000 59.803
September 670.038 44.833 3.625 0.024 44.857
October 420.004 17.662 143.946 2.600 20.262
November 221.202 6.745 320.340 9.868 16.614
December 68.500 1.134 536.304 24.219 25.354
           
Annual Sum or Average 4913.670 305.516 2545.128 111.207 416.724
Minimum of Months 49.833 1.134 0.000 0.000 16.614
Maximum of Months 744.000 62.973 596.921 36.395 62.973



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 58.250 1.080 568.242 18.965 20.045
February 90.762 1.722 448.000 12.993 14.716
March 235.294 5.479 265.125 4.731 10.210
April 433.375 11.476 106.375 1.461 12.938
May 680.104 25.134 0.000 0.000 25.134
June 706.261 36.938 0.000 0.000 36.938
July 744.000 45.613 0.000 0.000 45.613
August 743.500 43.469 0.000 0.000 43.469
September 693.037 34.298 0.000 0.000 34.298
October 477.327 14.030 77.375 0.831 14.861
November 260.973 5.827 270.138 4.520 10.347
December 85.987 1.075 484.121 12.079 13.154
           
Annual Sum or Average 5208.871 226.139 2219.375 55.581 281.720
Minimum of Months 58.250 1.075 0.000 0.000 10.210
Maximum of Months 744.000 45.613 568.242 18.965 45.613



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 45.104 0.785 629.583 27.701 28.486
February 79.738 1.616 484.250 18.934 20.550
March 214.597 5.953 318.863 7.416 13.369
April 422.479 13.537 125.452 2.443 15.979
May 650.863 30.761 8.750 0.041 30.802
June 701.832 45.588 0.000 0.000 45.588
July 744.000 56.690 0.000 0.000 56.690
August 736.062 53.232 0.000 0.000 53.232
September 679.506 40.199 2.875 0.017 40.216
October 433.553 14.575 135.042 1.879 16.454
November 211.718 5.186 322.333 7.657 12.843
December 48.625 0.691 564.583 18.710 19.402
           
Annual Sum or Average 4968.076 268.813 2591.732 84.798 353.611
Minimum of Months 45.104 0.691 0.000 0.000 12.843
Maximum of Months 744.000 56.690 629.583 27.701 56.690



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 24.875 0.247 670.000 42.702 42.948
February 36.687 0.571 538.950 28.864 29.434
March 164.542 5.144 368.835 11.785 16.929
April 356.676 13.405 163.149 3.997 17.402
May 619.286 32.503 14.125 0.085 32.588
June 696.005 50.247 0.000 0.000 50.247
July 744.000 62.090 0.000 0.000 62.090
August 734.650 57.305 0.000 0.000 57.305
September 664.547 40.475 4.194 0.033 40.509
October 350.003 11.407 192.444 3.584 14.991
November 141.212 2.539 392.583 12.800 15.339
December 35.292 0.452 646.000 31.176 31.628
           
Annual Sum or Average 4567.776 276.384 2990.281 135.026 411.410
Minimum of Months 24.875 0.247 0.000 0.000 14.991
Maximum of Months 744.000 62.090 670.000 42.702 62.090



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 22.750 0.278 655.458 23.217 23.495
February 27.937 0.289 514.667 15.259 15.548
March 169.738 2.895 328.417 5.798 8.694
April 392.551 9.320 122.250 1.658 10.978
May 679.533 24.445 0.000 0.000 24.445
June 706.758 36.808 0.000 0.000 36.808
July 744.000 45.202 0.000 0.000 45.202
August 743.500 41.526 0.000 0.000 41.526
September 689.378 30.497 0.000 0.000 30.497
October 374.783 8.429 120.383 1.225 9.653
November 138.654 2.066 353.958 6.037 8.103
December 55.417 0.606 625.850 16.459 17.065
           
Annual Sum or Average 4745.000 202.360 2720.983 69.653 272.014
Minimum of Months 22.750 0.278 0.000 0.000 8.103
Maximum of Months 744.000 45.202 655.458 23.217 45.202



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 16.750 0.168 678.063 30.721 30.889
February 27.354 0.278 538.083 20.320 20.599
March 166.209 3.522 360.817 8.076 11.598
April 394.495 11.614 134.312 2.498 14.112
May 651.475 30.872 8.500 0.039 30.911
June 702.024 46.560 0.000 0.000 46.560
July 744.000 57.646 0.000 0.000 57.646
August 736.062 52.706 0.000 0.000 52.706
September 678.564 37.616 2.875 0.017 37.633
October 356.753 9.255 159.000 2.135 11.390
November 120.742 1.703 386.083 8.819 10.522
December 34.083 0.368 650.625 22.249 22.618
           
Annual Sum or Average 4628.510 252.308 2918.358 94.874 347.182
Minimum of Months 16.750 0.168 0.000 0.000 10.522
Maximum of Months 744.000 57.646 678.063 30.721 57.646



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 32.375 0.741 655.271 53.858 54.599
February 58.950 1.765 536.625 37.125 38.890
March 176.592 7.731 399.073 16.317 24.048
April 323.624 16.411 188.625 6.263 22.674
May 574.372 37.147 33.500 0.362 37.509
June 682.418 58.856 5.536 0.032 58.887
July 744.000 73.868 0.000 0.000 73.868
August 723.447 69.072 0.000 0.000 69.072
September 653.723 49.791 12.750 0.119 49.909
October 363.476 17.294 209.271 5.577 22.871
November 171.513 5.591 392.031 16.712 22.302
December 33.292 0.591 612.188 37.714 38.306
           
Annual Sum or Average 4537.781 338.858 3044.869 174.078 512.936
Minimum of Months 32.375 0.591 0.000 0.000 22.302
Maximum of Months 744.000 73.868 655.271 53.858 73.868



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 40.375 0.637 640.771 33.015 33.652
February 65.190 1.249 506.000 22.375 23.624
March 181.901 5.211 353.765 9.333 14.544
April 365.805 11.983 160.949 3.280 15.263
May 611.244 28.970 15.669 0.062 29.032
June 695.433 45.538 0.000 0.000 45.538
July 744.000 57.087 0.000 0.000 57.087
August 734.604 53.347 0.000 0.000 53.347
September 668.356 39.922 4.437 0.023 39.945
October 395.131 13.907 161.647 2.487 16.395
November 191.221 4.759 342.500 9.209 13.967
December 37.083 0.558 594.917 22.234 22.792
           
Annual Sum or Average 4730.343 263.168 2780.655 102.017 365.185
Minimum of Months 37.083 0.558 0.000 0.000 13.967
Maximum of Months 744.000 57.087 640.771 33.015 57.087



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 29.925 0.447 671.063 41.014 41.461
February 56.950 1.209 530.304 27.849 29.057
March 174.722 5.782 398.708 11.976 17.757
April 356.132 14.127 166.775 4.212 18.338
May 608.359 35.046 20.375 0.175 35.221
June 692.121 54.863 4.250 0.017 54.880
July 744.000 69.043 0.000 0.000 69.043
August 727.996 63.933 0.000 0.000 63.933
September 666.490 46.370 8.500 0.066 46.437
October 374.451 14.777 187.574 3.747 18.525
November 170.717 4.446 386.146 12.344 16.790
December 29.542 0.460 631.625 28.593 29.053
           
Annual Sum or Average 4631.405 310.502 3005.320 129.994 440.496
Minimum of Months 29.542 0.447 0.000 0.000 16.790
Maximum of Months 744.000 69.043 671.063 41.014 69.043



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 16.042 0.129 686.188 58.574 58.703
February 34.458 0.644 564.367 39.751 40.395
March 153.292 6.029 426.554 17.434 23.464
April 311.512 15.290 196.833 6.488 21.779
May 574.081 36.984 33.318 0.357 37.341
June 683.173 59.068 5.292 0.029 59.097
July 744.000 74.001 0.000 0.000 74.001
August 723.542 68.412 0.000 0.000 68.412
September 651.203 47.562 12.906 0.123 47.685
October 321.645 13.145 236.692 6.336 19.481
November 125.875 2.676 446.458 18.955 21.631
December 24.958 0.302 659.813 43.053 43.355
           
Annual Sum or Average 4363.781 324.243 3268.421 191.101 515.343
Minimum of Months 16.042 0.129 0.000 0.000 19.481
Maximum of Months 744.000 74.001 686.188 58.574 74.001



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 13.833 0.148 680.417 36.970 37.118
February 24.417 0.293 550.500 24.538 24.831
March 152.834 3.645 383.625 10.222 13.868
April 349.169 10.967 169.997 3.450 14.417
May 610.413 28.826 14.931 0.057 28.883
June 696.405 45.714 0.000 0.000 45.714
July 744.000 57.164 0.000 0.000 57.164
August 734.954 52.679 0.000 0.000 52.679
September 665.985 37.745 4.625 0.024 37.769
October 333.399 9.899 197.438 3.056 12.955
November 121.762 1.998 407.292 10.952 12.949
December 28.083 0.318 654.375 26.703 27.021
           
Annual Sum or Average 4475.254 249.396 3063.199 115.971 365.367
Minimum of Months 13.833 0.148 0.000 0.000 12.949
Maximum of Months 744.000 57.164 680.417 36.970 57.164



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 8.250 0.082 693.438 44.462 44.545
February 23.250 0.307 566.542 29.702 30.009
March 151.036 4.238 417.083 12.695 16.932
April 344.415 13.101 172.975 4.317 17.418
May 608.845 34.853 20.125 0.172 35.025
June 692.605 54.934 4.000 0.016 54.951
July 744.000 69.000 0.000 0.000 69.000
August 728.496 63.251 0.000 0.000 63.251
September 665.392 44.268 8.500 0.068 44.336
October 323.071 10.752 212.314 4.150 14.902
November 108.687 1.762 447.896 13.913 15.675
December 22.708 0.227 664.396 32.488 32.715
           
Annual Sum or Average 4420.755 296.775 3207.269 141.982 438.757
Minimum of Months 8.250 0.082 0.000 0.000 14.902
Maximum of Months 744.000 69.000 693.438 44.462 69.000



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 255.80 0.00
February 0.00 32.74 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 3.93 0.00
       
Annual Sum or Average 0.00 24.57 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 255.80 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3562.38 0.00
February 0.00 2641.03 0.00
March 0.00 961.27 0.00
April 0.00 345.34 0.00
May 0.00 3.75 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 1.69 0.00
October 0.00 215.51 0.00
November 0.00 940.92 0.00
December 0.00 2268.59 0.00
       
Annual Sum or Average 0.00 903.96 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3562.38 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4962.83 0.00
February 0.00 3713.25 0.00
March 0.00 1429.64 0.00
April 0.00 530.45 0.00
May 0.00 22.55 0.00
June 0.00 2.81 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 8.50 0.00
October 0.00 422.88 0.00
November 0.00 1485.00 0.00
December 0.00 3351.37 0.00
       
Annual Sum or Average 0.00 1316.82 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4962.83 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5474.62 0.00
February 0.00 4085.75 0.00
March 0.00 1627.26 0.00
April 0.00 620.37 0.00
May 0.00 30.96 0.00
June 0.00 3.17 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 11.12 0.00
October 0.00 551.65 0.00
November 0.00 1767.75 0.00
December 0.00 3954.57 0.00
       
Annual Sum or Average 0.00 1499.41 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5474.62 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4223.14 0.00
February 0.00 3072.69 0.00
March 0.00 1176.12 0.00
April 0.00 400.90 0.00
May 0.00 4.46 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 2.23 0.00
October 0.00 308.41 0.00
November 0.00 1228.71 0.00
December 0.00 2978.36 0.00
       
Annual Sum or Average 0.00 1107.93 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4223.14 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5548.24 0.00
February 0.00 4067.46 0.00
March 0.00 1587.62 0.00
April 0.00 557.20 0.00
May 0.00 22.26 0.00
June 0.00 2.60 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 8.83 0.00
October 0.00 486.85 0.00
November 0.00 1730.52 0.00
December 0.00 3980.86 0.00
       
Annual Sum or Average 0.00 1488.40 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5548.24 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3495.87 0.00
February 0.00 2648.98 0.00
March 0.00 932.84 0.00
April 0.00 339.00 0.00
May 0.00 6.20 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 2.43 0.00
October 0.00 249.70 0.00
November 0.00 979.47 0.00
December 0.00 2326.38 0.00
       
Annual Sum or Average 0.00 907.23 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3495.87 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2366.81 0.00
February 0.00 1795.31 0.00
March 0.00 590.41 0.00
April 0.00 188.47 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 103.73 0.00
November 0.00 582.92 0.00
December 0.00 1507.43 0.00
       
Annual Sum or Average 0.00 589.12 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2366.81 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3702.37 0.00
February 0.00 2801.76 0.00
March 0.00 991.15 0.00
April 0.00 337.34 0.00
May 0.00 5.54 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 2.34 0.00
October 0.00 251.16 0.00
November 0.00 1057.51 0.00
December 0.00 2500.72 0.00
       
Annual Sum or Average 0.00 962.59 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3702.37 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4183.66 0.00
February 0.00 3130.87 0.00
March 0.00 1154.66 0.00
April 0.00 404.68 0.00
May 0.00 8.32 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 3.37 0.00
October 0.00 351.13 0.00
November 0.00 1295.89 0.00
December 0.00 3054.43 0.00
       
Annual Sum or Average 0.00 1123.56 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4183.66 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2911.42 0.00
February 0.00 2118.51 0.00
March 0.00 727.13 0.00
April 0.00 214.79 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 153.59 0.00
November 0.00 782.32 0.00
December 0.00 2063.97 0.00
       
Annual Sum or Average 0.00 741.84 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2911.42 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4251.11 0.00
February 0.00 3113.14 0.00
March 0.00 1117.49 0.00
April 0.00 357.26 0.00
May 0.00 5.38 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 2.44 0.00
October 0.00 295.49 0.00
November 0.00 1261.00 0.00
December 0.00 3078.81 0.00
       
Annual Sum or Average 0.00 1115.03 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4251.11 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5595.44 0.00
February 0.00 4270.31 0.00
March 0.00 1695.20 0.00
April 0.00 672.34 0.00
May 0.00 37.64 0.00
June 0.00 3.38 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 12.74 0.00
October 0.00 579.39 0.00
November 0.00 1794.13 0.00
December 0.00 3918.25 0.00
       
Annual Sum or Average 0.00 1536.03 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5595.44 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4294.84 0.00
February 0.00 3222.55 0.00
March 0.00 1214.09 0.00
April 0.00 440.86 0.00
May 0.00 8.08 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 3.10 0.00
October 0.00 323.54 0.00
November 0.00 1237.86 0.00
December 0.00 2892.35 0.00
       
Annual Sum or Average 0.00 1127.14 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4294.84 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5687.29 0.00
February 0.00 4275.44 0.00
March 0.00 1660.62 0.00
April 0.00 603.49 0.00
May 0.00 24.23 0.00
June 0.00 2.51 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 9.52 0.00
October 0.00 519.60 0.00
November 0.00 1768.81 0.00
December 0.00 3964.95 0.00
       
Annual Sum or Average 0.00 1530.96 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5687.29 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6099.10 0.00
February 0.00 4582.55 0.00
March 0.00 1815.37 0.00
April 0.00 698.10 0.00
May 0.00 37.17 0.00
June 0.00 3.11 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 13.24 0.00
October 0.00 659.72 0.00
November 0.00 2039.51 0.00
December 0.00 4482.90 0.00
       
Annual Sum or Average 0.00 1690.01 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6099.10 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4798.11 0.00
February 0.00 3525.89 0.00
March 0.00 1326.72 0.00
April 0.00 462.65 0.00
May 0.00 7.42 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 3.22 0.00
October 0.00 396.61 0.00
November 0.00 1468.73 0.00
December 0.00 3465.65 0.00
       
Annual Sum or Average 0.00 1278.34 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4798.11 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6174.62 0.00
February 0.00 4566.75 0.00
March 0.00 1762.95 0.00
April 0.00 619.52 0.00
May 0.00 23.86 0.00
June 0.00 2.32 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 9.69 0.00
October 0.00 576.28 0.00
November 0.00 1996.56 0.00
December 0.00 4511.69 0.00
       
Annual Sum or Average 0.00 1674.64 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6174.62 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.30
February 0.00 0.00 0.38
March 0.00 0.00 0.66
April 0.00 0.00 0.85
May 0.00 0.00 1.13
June 0.00 0.00 1.32
July 0.00 0.00 1.42
August 0.00 0.00 1.38
September 0.00 0.00 1.26
October 0.00 0.00 0.88
November 0.00 0.00 0.65
December 0.00 0.00 0.40
       
Annual Sum or Average 0.00 0.00 0.89
Minimum of Months 0.00 0.00 0.30
Maximum of Months 0.00 0.00 1.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.04
April 0.00 0.00 0.10
May 0.00 0.00 0.24
June 0.00 0.00 0.39
July 0.00 0.00 0.48
August 0.00 0.00 0.45
September 0.00 0.00 0.36
October 0.00 0.00 0.12
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.12
May 0.00 0.00 0.30
June 0.00 0.00 0.48
July 0.00 0.00 0.59
August 0.00 0.00 0.55
September 0.00 0.00 0.42
October 0.00 0.00 0.13
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.59



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.04
April 0.00 0.00 0.11
May 0.00 0.00 0.28
June 0.00 0.00 0.47
July 0.00 0.00 0.57
August 0.00 0.00 0.52
September 0.00 0.00 0.37
October 0.00 0.00 0.09
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.07
May 0.00 0.00 0.23
June 0.00 0.00 0.39
July 0.00 0.00 0.47
August 0.00 0.00 0.42
September 0.00 0.00 0.31
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.47



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.10
May 0.00 0.00 0.29
June 0.00 0.00 0.48
July 0.00 0.00 0.58
August 0.00 0.00 0.52
September 0.00 0.00 0.38
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.08
April 0.00 0.00 0.15
May 0.00 0.00 0.31
June 0.00 0.00 0.48
July 0.00 0.00 0.58
August 0.00 0.00 0.55
September 0.00 0.00 0.43
October 0.00 0.00 0.16
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.12
May 0.00 0.00 0.26
June 0.00 0.00 0.40
July 0.00 0.00 0.48
August 0.00 0.00 0.45
September 0.00 0.00 0.38
October 0.00 0.00 0.14
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.14
May 0.00 0.00 0.32
June 0.00 0.00 0.49
July 0.00 0.00 0.59
August 0.00 0.00 0.55
September 0.00 0.00 0.44
October 0.00 0.00 0.15
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.59



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.13
May 0.00 0.00 0.30
June 0.00 0.00 0.48
July 0.00 0.00 0.57
August 0.00 0.00 0.53
September 0.00 0.00 0.39
October 0.00 0.00 0.10
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.26
June 0.00 0.00 0.40
July 0.00 0.00 0.47
August 0.00 0.00 0.43
September 0.00 0.00 0.33
October 0.00 0.00 0.09
November 0.00 0.00 0.02
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.47



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.03
April 0.00 0.00 0.12
May 0.00 0.00 0.31
June 0.00 0.00 0.49
July 0.00 0.00 0.58
August 0.00 0.00 0.53
September 0.00 0.00 0.39
October 0.00 0.00 0.09
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.34
June 0.00 0.00 0.56
July 0.00 0.00 0.68
August 0.00 0.00 0.63
September 0.00 0.00 0.48
October 0.00 0.00 0.16
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.12
May 0.00 0.00 0.29
June 0.00 0.00 0.48
July 0.00 0.00 0.58
August 0.00 0.00 0.54
September 0.00 0.00 0.42
October 0.00 0.00 0.14
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.35
June 0.00 0.00 0.56
July 0.00 0.00 0.69
August 0.00 0.00 0.63
September 0.00 0.00 0.48
October 0.00 0.00 0.14
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.34
June 0.00 0.00 0.56
July 0.00 0.00 0.68
August 0.00 0.00 0.62
September 0.00 0.00 0.45
October 0.00 0.00 0.12
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.68



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.04
April 0.00 0.00 0.11
May 0.00 0.00 0.29
June 0.00 0.00 0.48
July 0.00 0.00 0.58
August 0.00 0.00 0.53
September 0.00 0.00 0.40
October 0.00 0.00 0.10
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.04
April 0.00 0.00 0.13
May 0.00 0.00 0.35
June 0.00 0.00 0.57
July 0.00 0.00 0.69
August 0.00 0.00 0.63
September 0.00 0.00 0.46
October 0.00 0.00 0.10
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.69



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1634.25 1216.74
February 0.00 0.00 1634.98 1099.49
March 0.00 0.00 1564.94 1165.14
April 0.00 0.00 1448.26 1043.48
May 0.00 0.00 1301.06 968.67
June 0.00 0.00 1171.51 844.09
July 0.00 0.00 1094.22 814.68
August 0.00 0.00 1085.29 808.03
September 0.00 0.00 1155.24 832.36
October 0.00 0.00 1276.35 950.28
November 0.00 0.00 1420.86 1023.75
December 0.00 0.00 1554.27 1157.20
         
Annual Sum or Average 0.00 0.00 1360.21 11923.91
Minimum of Months 0.00 0.00 1085.29 808.03
Maximum of Months 0.00 0.00 1634.98 1216.74