Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31
Tabular Output Report in Format: HTML
Building: MF+CZ3A+USA_TN_Memphis.Intl.AP.723340+oilfurnace+unheatedbsmt+IECC_2012
Environment: ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340
Simulation Timestamp: 2019-02-14 08:31:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 866411.94 | 22.21 | 40.09 |
Net Site Energy | 866411.94 | 22.21 | 40.09 |
Total Source Energy | 1910812.44 | 48.99 | 88.42 |
Net Source Energy | 1910812.44 | 48.99 | 88.42 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 148912.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 93964.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19645.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 251046.17 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 466453.14 | 399958.80 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 148912.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 93964.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 19645.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 251046.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 5.26 | 18.51 | 0.00 | 0.00 | 0.00 | 17.48 |
Other | 13.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 21.59 | 18.51 | 0.00 | 0.00 | 0.00 | 17.48 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.91 | 10.25 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.96 | 10.25 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 466453.142 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 466453.142 | 100.00 |
Total On-Site and Utility Electric Sources | 466453.142 | 100.00 |
Total Electricity End Uses | 466453.142 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 815.50 |
Time Setpoint Not Met During Occupied Cooling | 8.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1333.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31 |
RunPeriod | ANNUAL |
Weather File | Memphis International Ap TN USA TMY3 WMO#=723340 |
Latitude [deg] | 35.07 |
Longitude [deg] | -90.0 |
Elevation [ft] | 265.76 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58419.71 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6659 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 141767.99 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 01-JUL-18:15 | 07-JAN-06:15 | - | - | - | 01-JAN-08:00 |
Heating | 0.00 | 189.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.51 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 119.40 | 303.40 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 189.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.51 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 161421.29 | 0.00 | 0.00 | 0.00 |
Cooling | 297584.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 62217.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 272134.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1477257.10 | 433555.34 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 7.47 | 0.00 | 0.00 | 0.00 |
Cooling | 13.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 68.36 | 20.06 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 7.47 | 0.00 | 0.00 | 0.00 |
Cooling | 13.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 12.59 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 68.36 | 20.06 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 17.06 | 0.00 | 17.06 | Wetbulb [F] | 807.13 | 0.00 |
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 96.08 | 16.56 | 77.36 | Wetbulb [F] | 748.07 | 240.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.218 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.218 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.218 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 351743.28 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23058.23 | 17284.95 | 5773.28 | 0.75 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8017.01 | 5420.16 | 2596.84 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9498.05 | 6505.34 | 2992.71 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12537.06 | 8749.64 | 3787.42 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7885.42 | 5331.20 | 2554.22 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9514.09 | 6518.46 | 2995.63 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12733.59 | 8988.18 | 3745.41 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8517.74 | 5758.70 | 2759.04 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10130.44 | 6849.02 | 3281.42 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12539.19 | 8832.04 | 3707.14 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8389.41 | 5671.94 | 2717.47 | 0.68 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9583.22 | 6606.58 | 2976.64 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14624.72 | 10428.77 | 4195.96 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10483.18 | 7232.38 | 3250.80 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11690.44 | 8119.12 | 3571.32 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14627.53 | 10430.97 | 4196.56 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10539.45 | 7276.31 | 3263.15 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11670.65 | 8122.29 | 3548.36 | 0.70 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.8 | 3.35 | 11.44 | 12.12 | 11.78 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.50 | 11.94 | 12.67 | 12.61 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.48 | 11.88 | 12.61 | 12.51 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.0 | 3.45 | 11.79 | 12.51 | 12.35 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.50 | 11.94 | 12.67 | 12.61 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.48 | 11.87 | 12.60 | 12.50 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.44 | 11.73 | 12.44 | 12.26 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.7 | 3.50 | 11.94 | 12.67 | 12.61 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.50 | 11.94 | 12.67 | 12.61 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.44 | 11.74 | 12.46 | 12.28 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.7 | 3.50 | 11.94 | 12.67 | 12.61 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.47 | 11.84 | 12.57 | 12.45 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.2 | 3.42 | 11.68 | 12.39 | 12.18 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.47 | 11.84 | 12.57 | 12.45 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.46 | 11.81 | 12.53 | 12.39 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.2 | 3.42 | 11.68 | 12.39 | 12.18 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.47 | 11.84 | 12.56 | 12.44 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.46 | 11.80 | 12.52 | 12.38 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 42845.54 | 45583.90 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 13402.29 | 13201.61 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 15847.75 | 15909.60 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 20961.57 | 21554.34 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13225.81 | 13005.48 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 15881.72 | 15947.17 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 21802.63 | 22480.16 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 14073.44 | 13945.58 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 16236.40 | 16338.48 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 21406.74 | 22043.58 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 13901.33 | 13754.65 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 16200.36 | 16298.63 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 25226.46 | 26250.35 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 17502.68 | 17739.13 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19508.00 | 19950.33 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 25231.92 | 26256.29 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 17610.33 | 17858.01 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 19572.03 | 20020.94 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 749.58 | 282.74 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 200.47 | 75.61 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 246.06 | 92.81 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 341.40 | 128.77 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 197.18 | 74.37 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 246.69 | 93.05 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 357.10 | 134.69 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 212.99 | 80.34 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 253.31 | 95.55 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 349.71 | 131.91 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 209.78 | 79.13 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 252.64 | 95.29 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 420.92 | 158.77 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 276.92 | 104.45 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 314.30 | 118.55 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 421.02 | 158.80 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 278.92 | 105.21 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 315.49 | 119.00 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 35.370495 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17440.90 | 17440.90 | 14.53 | 749.581 | 749.581 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00871 | 92.93 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4664.45 | 4664.45 | 3.89 | 200.467 | 200.467 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01024 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5725.36 | 5725.36 | 4.77 | 246.058 | 246.058 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00980 | 89.08 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7943.63 | 7943.63 | 6.62 | 341.401 | 341.401 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00941 | 92.93 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4587.88 | 4587.88 | 3.82 | 197.177 | 197.177 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01028 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5740.09 | 5740.09 | 4.78 | 246.691 | 246.691 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00980 | 89.08 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8308.95 | 8308.95 | 6.92 | 357.096 | 357.096 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00922 | 92.52 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4955.84 | 4955.84 | 4.13 | 212.988 | 212.988 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00993 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5892.91 | 5892.91 | 4.91 | 253.314 | 253.314 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 74.98 | 74.98 | 0.00949 | 96.08 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8137.20 | 8137.20 | 6.78 | 349.715 | 349.715 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00924 | 92.52 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4881.17 | 4881.17 | 4.07 | 209.779 | 209.779 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00996 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5878.59 | 5878.59 | 4.90 | 252.642 | 252.642 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 74.98 | 74.98 | 0.00956 | 89.79 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7340.81 | 7340.81 | 6.11 | 315.493 | 315.493 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00957 | 90.86 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7313.05 | 7313.05 | 6.09 | 314.300 | 314.300 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00956 | 91.48 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9793.74 | 9793.74 | 8.16 | 420.915 | 420.915 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00920 | 92.52 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6489.91 | 6489.91 | 5.41 | 278.923 | 278.923 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00973 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6443.21 | 6443.21 | 5.37 | 276.916 | 276.916 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00973 | 89.62 | 0.01615 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9796.10 | 9796.10 | 8.16 | 421.017 | 421.017 | MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00920 | 92.52 | 0.01615 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 17.06 | 0.00188 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6628.50 | 6628.50 | 5.52 | 121.785 | 121.785 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00590 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8711.24 | 8711.24 | 7.26 | 160.048 | 160.048 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00618 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8717.80 | 8717.80 | 7.26 | 160.169 | 160.169 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00618 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6738.19 | 6738.19 | 5.61 | 123.800 | 123.800 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00592 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8715.21 | 8715.21 | 7.26 | 160.121 | 160.121 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00618 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7476.60 | 7476.60 | 6.23 | 137.371 | 137.371 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00632 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5728.57 | 5728.57 | 4.77 | 105.255 | 105.255 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00608 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7748.89 | 7748.89 | 6.45 | 142.374 | 142.374 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00636 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7752.79 | 7752.79 | 6.46 | 142.445 | 142.445 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00636 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5753.75 | 5753.75 | 4.79 | 105.718 | 105.718 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00609 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7750.37 | 7750.37 | 6.46 | 142.401 | 142.401 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00636 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 10025.23 | 10025.23 | 8.35 | 184.189 | 184.189 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00635 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10021.25 | 10021.25 | 8.35 | 184.116 | 184.116 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00635 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9983.79 | 9983.79 | 8.32 | 183.428 | 183.428 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00634 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8024.53 | 8024.53 | 6.68 | 147.433 | 147.433 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00614 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8014.81 | 8014.81 | 6.68 | 147.255 | 147.255 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00614 | 17.06 | 0.00188 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10026.98 | 10026.98 | 8.35 | 184.221 | 184.221 | MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00635 | 17.06 | 0.00188 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 | 749.58 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 | 200.47 | 121.78 | 121.78 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 | 246.06 | 160.05 | 160.05 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 | 341.40 | 160.17 | 160.17 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 | 197.18 | 123.80 | 123.80 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 | 246.69 | 160.12 | 160.12 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 | 357.10 | 137.37 | 137.37 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 | 212.99 | 105.26 | 105.26 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 | 253.31 | 142.37 | 142.37 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 | 349.71 | 142.45 | 142.45 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 | 209.78 | 105.72 | 105.72 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 | 252.64 | 142.40 | 142.40 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.92 | 420.92 | 183.43 | 183.43 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 276.92 | 276.92 | 147.25 | 147.25 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 314.30 | 314.30 | 184.12 | 184.12 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 421.02 | 421.02 | 184.22 | 184.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 278.92 | 278.92 | 147.43 | 147.43 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 315.49 | 315.49 | 184.19 | 184.19 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1613.00 | 4492.00 | 11.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3435.75 | 4813.00 | 988.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3548.50 | 4703.50 | 788.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3613.75 | 5246.75 | 1048.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3268.75 | 5257.50 | 973.75 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 3464.50 | 5040.25 | 820.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 3714.50 | 4183.75 | 482.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3409.00 | 3975.00 | 328.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3559.25 | 4091.25 | 356.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3667.75 | 4575.00 | 556.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3312.75 | 4391.50 | 356.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3526.00 | 4440.25 | 405.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3817.25 | 4573.25 | 625.25 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3832.00 | 4338.50 | 572.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3908.00 | 4504.50 | 709.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 3589.50 | 4650.00 | 573.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3618.50 | 4355.25 | 530.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3903.25 | 4750.25 | 788.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4221.75 | 5865.00 | 1333.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 74.50 | 1.25 | 74.50 | 1.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 137.50 | 8.00 | 137.50 | 8.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 255.50 | 0.00 | 255.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23.00 | 0.00 | 23.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 64.00 | 0.00 | 64.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10.50 | 0.00 | 10.50 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6.00 | 0.00 | 6.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 157.25 | 1.25 | 157.25 | 1.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 256.00 | 0.00 | 256.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 17.50 | 0.00 | 17.50 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 82.75 | 0.00 | 82.75 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 45.75 | 0.00 | 45.75 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 75.50 | 0.00 | 75.50 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 59.00 | 0.00 | 59.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 10.25 | 0.00 | 10.25 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 3.75 | 0.00 | 3.75 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 166.50 | 0.00 | 166.50 | 0.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 815.50 | 8.00 | 815.50 | 8.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.107 | 0.000 | 0.271 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.092 | 0.000 | 0.271 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.105 | 0.000 | 0.271 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.104 | 0.000 | 0.271 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.092 | 0.000 | 0.271 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.105 | 0.000 | 0.271 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.271 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.033 | 0.000 | 0.271 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.271 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.271 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.033 | 0.000 | 0.271 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.271 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.105 | 0.000 | 0.271 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.105 | 0.000 | 0.271 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.105 | 0.000 | 0.271 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.092 | 0.000 | 0.271 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.092 | 0.000 | 0.271 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.105 | 0.000 | 0.271 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1867 |
Defaulted Fields | 446 |
Fields with Defaults | 4744 |
Autosized Fields | 328 |
Autosizable Fields | 438 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Fans:Electricity | 5753.74 | 97.77 | 06-APR-01:00 | 2009.74 | 19-AUG-17:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
ElectricityPurchased:Plant | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
Cogeneration:ElectricityPurchased | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
ElectricityNet:Plant | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
Cogeneration:ElectricityNet | 136612.81 | 7330.96 | 28-APR-03:15 | 34969.04 | 01-JUL-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 33273.55 | 511.63 | 06-APR-01:00 | 15851.58 | 29-AUG-15:30 |
General:Fans:Electricity | 5753.74 | 97.77 | 06-APR-01:00 | 2009.74 | 19-AUG-17:15 |
Cooling:Electricity | 27519.82 | 0.00 | 06-JAN-14:45 | 13870.07 | 29-AUG-15:30 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 3999.59 | 0.00 | 13-JAN-17:15 | 303188.82 | 07-JAN-06:15 |
Gas:Plant | 3999.59 | 0.00 | 13-JAN-17:15 | 303188.82 | 07-JAN-06:15 |
WaterSystems:Gas | 2510.46 | 0.00 | 01-JAN-00:15 | 114711.39 | 12-FEB-08:30 |
Water Heater:WaterSystems:Gas | 2510.46 | 0.00 | 01-JAN-00:15 | 114711.39 | 12-FEB-08:30 |
Heating:Gas | 1489.13 | 0.00 | 13-JAN-17:15 | 191760.40 | 07-JAN-05:00 |
Boiler:Heating:Gas | 1489.13 | 0.00 | 13-JAN-17:15 | 191760.40 | 07-JAN-05:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
Water:Plant | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
WaterSystems:Water | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
MainsWater:Plant | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 02-JAN-02:15 | 0.18 | 01-JAN-09:00 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 241669.72 | 887.74 | 02-AUG-02:15 | 184121.56 | 07-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 122678.80 | 887.74 | 02-AUG-02:15 | 35288.13 | 29-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 122678.80 | 887.74 | 02-AUG-02:15 | 35288.13 | 29-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1181357.42 | 16218.11 | 04-APR-02:30 | 488794.87 | 07-JAN-07:15 |
EnergyTransfer:Building | 413149.37 | 6894.13 | 03-DEC-16:00 | 156915.97 | 07-JAN-05:00 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 123045.45 | 0.00 | 14-JAN-15:15 | 156915.97 | 07-JAN-05:00 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 290103.92 | 0.00 | 06-JAN-14:45 | 134803.32 | 28-AUG-17:15 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 79249.18 | 0.00 | 06-JAN-14:45 | 17702.61 | 28-AUG-17:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.51 | 0.00 | 01-JAN-00:15 | 572.65 | 07-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 79247.67 | 0.00 | 06-JAN-14:45 | 17702.61 | 28-AUG-17:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14421.21 | 0.00 | 09-JAN-13:30 | 12620.74 | 07-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4791.65 | 0.00 | 09-JAN-13:30 | 12620.74 | 07-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9629.56 | 0.00 | 01-JAN-00:15 | 5214.50 | 29-AUG-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 19716.63 | 0.00 | 10-JAN-13:45 | 10296.76 | 07-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7442.70 | 0.00 | 10-JAN-13:45 | 10296.76 | 07-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12273.92 | 0.00 | 01-JAN-00:15 | 6535.32 | 27-AUG-14:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 19937.60 | 0.00 | 13-JAN-14:30 | 9764.46 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8754.83 | 0.00 | 13-JAN-14:30 | 9764.46 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11182.77 | 0.00 | 01-JAN-00:15 | 8451.64 | 01-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14986.27 | 0.00 | 13-JAN-17:15 | 7612.71 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6665.92 | 0.00 | 13-JAN-17:15 | 7612.71 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8320.34 | 0.00 | 01-JAN-00:15 | 4901.51 | 11-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 19682.22 | 0.00 | 14-JAN-14:00 | 9733.42 | 31-JAN-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8740.10 | 0.00 | 14-JAN-14:00 | 9733.42 | 31-JAN-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10942.12 | 0.00 | 01-JAN-00:15 | 6335.49 | 02-JUL-09:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 19750.03 | 0.00 | 01-JAN-15:15 | 8814.07 | 28-AUG-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5472.65 | 0.00 | 01-JAN-15:15 | 8333.26 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 14277.38 | 0.00 | 01-JAN-00:15 | 8814.07 | 28-AUG-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15225.70 | 0.00 | 04-JAN-14:00 | 7177.24 | 07-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3926.21 | 0.00 | 04-JAN-14:00 | 7177.24 | 07-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11299.48 | 0.00 | 01-JAN-00:15 | 5423.24 | 29-AUG-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 19864.83 | 0.00 | 09-JAN-13:45 | 8334.13 | 07-JAN-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5928.60 | 0.00 | 09-JAN-13:45 | 8334.13 | 07-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13936.22 | 0.00 | 01-JAN-00:15 | 6886.14 | 29-AUG-16:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 19846.17 | 0.00 | 13-JAN-14:30 | 8572.90 | 01-JUL-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7144.37 | 0.00 | 13-JAN-14:30 | 8428.21 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12701.81 | 0.00 | 01-JAN-00:15 | 8572.90 | 01-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14986.27 | 0.00 | 13-JAN-17:15 | 6245.79 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5106.09 | 0.00 | 13-JAN-17:15 | 6245.79 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9880.18 | 0.00 | 01-JAN-00:15 | 5095.51 | 01-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 19659.75 | 0.00 | 13-JAN-15:00 | 8247.16 | 07-JAN-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7139.80 | 0.00 | 13-JAN-15:00 | 8247.16 | 07-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12519.95 | 0.00 | 01-JAN-00:15 | 6510.92 | 02-JUL-09:30 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 24254.56 | 0.00 | 13-JAN-16:15 | 10868.56 | 07-JAN-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 9926.85 | 0.00 | 13-JAN-16:15 | 10868.56 | 07-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 14327.71 | 0.00 | 01-JAN-00:15 | 7815.25 | 27-AUG-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 23931.07 | 0.00 | 13-JAN-11:30 | 10870.36 | 07-JAN-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 8777.97 | 0.00 | 13-JAN-11:30 | 10870.36 | 07-JAN-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 15153.09 | 0.00 | 01-JAN-00:15 | 7996.79 | 29-AUG-16:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24300.61 | 0.00 | 09-JAN-15:00 | 10882.98 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 8821.02 | 0.00 | 09-JAN-15:00 | 10882.98 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 15479.59 | 0.00 | 01-JAN-00:15 | 10300.14 | 28-AUG-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19532.97 | 0.00 | 13-JAN-16:30 | 8811.16 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7775.69 | 0.00 | 13-JAN-16:30 | 8811.16 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 11757.28 | 0.00 | 01-JAN-00:15 | 6813.12 | 28-AUG-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 19159.23 | 0.00 | 13-JAN-11:45 | 8829.68 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6573.24 | 0.00 | 13-JAN-11:45 | 8829.68 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 12585.99 | 0.00 | 01-JAN-00:15 | 6875.65 | 28-AUG-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 24645.09 | 0.00 | 13-JAN-14:45 | 11006.53 | 07-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 10056.24 | 0.00 | 13-JAN-14:45 | 11006.53 | 07-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 14588.84 | 0.00 | 01-JAN-00:15 | 10201.50 | 28-AUG-16:45 |
EnergyTransfer:Plant | 241808.90 | 887.74 | 02-AUG-02:15 | 184629.30 | 07-JAN-07:15 |
WaterSystems:EnergyTransfer | 122678.80 | 887.74 | 02-AUG-02:15 | 35288.13 | 29-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 122678.80 | 887.74 | 02-AUG-02:15 | 35288.13 | 29-JAN-09:00 |
EnergyTransfer:HVAC | 526399.15 | 7316.70 | 06-APR-01:15 | 181975.88 | 19-AUG-17:30 |
HeatingCoils:EnergyTransfer | 118990.92 | 0.00 | 13-JAN-17:15 | 153359.25 | 07-JAN-05:00 |
PlantLoopHeatingDemand:HVAC | 118990.92 | 0.00 | 13-JAN-17:15 | 153359.25 | 07-JAN-05:00 |
HeatingCoils:PlantLoopHeatingDemand | 118990.92 | 0.00 | 13-JAN-17:15 | 153359.25 | 07-JAN-05:00 |
CoolingCoils:EnergyTransfer | 407408.23 | 0.00 | 06-JAN-14:45 | 181975.88 | 19-AUG-17:30 |
Boilers:EnergyTransfer | 119130.10 | 0.00 | 13-JAN-17:15 | 153408.32 | 07-JAN-05:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1.506 | -6599.56 | 0.000 | 0.000 | 2875.051 | 2456.001 | 10405.511 | 7198.637 | 0.000 | 1275.520 | 69176.887 | 0.000 | -4567.11 | 0.000 | -9574.35 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 4791.591 | -801.93 | 0.000 | 0.000 | 2991.480 | 2456.001 | 10405.511 | 3119.813 | 0.000 | 1234.181 | 0.000 | 0.000 | -1734.03 | 0.000 | -8424.93 | -5210.06 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 7442.609 | -1022.14 | 0.000 | 0.000 | 2997.217 | 2456.001 | 10405.511 | 7108.622 | 0.000 | 1274.867 | 0.000 | 0.000 | -4182.17 | 0.000 | -8772.78 | -6455.95 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 8754.735 | -931.27 | 0.000 | 0.000 | 3006.396 | 2456.001 | 10405.511 | 5485.156 | 0.000 | 1275.739 | 0.000 | 0.000 | -4507.52 | 0.000 | -8656.44 | -7036.88 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 6665.854 | -692.90 | 0.000 | 0.000 | 2999.297 | 2456.001 | 10405.511 | 1195.571 | 0.000 | 1234.650 | 0.000 | 0.000 | -1903.34 | 0.000 | -8372.74 | -6360.43 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 8740.002 | -911.24 | 0.000 | 0.000 | 3006.655 | 2456.001 | 10405.511 | 5239.947 | 0.000 | 1275.379 | 0.000 | 0.000 | -4326.63 | 0.000 | -8691.43 | -7163.28 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5472.577 | -1188.98 | 0.000 | 0.000 | 2980.429 | 2456.001 | 10405.511 | 7216.448 | 0.000 | 1077.877 | 0.000 | 0.000 | -4439.01 | 0.000 | -7286.05 | -3606.47 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 3926.158 | -941.00 | 0.000 | 0.000 | 2971.543 | 2456.001 | 10405.511 | 3094.009 | 0.000 | 1036.974 | 0.000 | 0.000 | -1778.12 | 0.000 | -6981.23 | -3831.34 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5928.527 | -1160.58 | 0.000 | 0.000 | 2986.054 | 2456.001 | 10405.511 | 7051.594 | 0.000 | 1077.859 | 0.000 | 0.000 | -4278.04 | 0.000 | -7268.87 | -4422.39 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 7144.286 | -1057.77 | 0.000 | 0.000 | 2995.077 | 2456.001 | 10405.511 | 5441.281 | 0.000 | 1078.182 | 0.000 | 0.000 | -4610.52 | 0.000 | -7175.77 | -5032.28 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 5106.031 | -822.80 | 0.000 | 0.000 | 2986.523 | 2456.001 | 10405.511 | 1183.054 | 0.000 | 1037.243 | 0.000 | 0.000 | -1947.09 | 0.000 | -6888.56 | -4458.48 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 7139.721 | -1042.64 | 0.000 | 0.000 | 2995.997 | 2456.001 | 10405.511 | 5193.495 | 0.000 | 1077.894 | 0.000 | 0.000 | -4423.92 | 0.000 | -7201.37 | -5123.33 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 9926.749 | -1193.18 | 0.000 | 0.000 | 3000.801 | 2456.001 | 10405.511 | 5176.589 | 0.000 | 1265.679 | 0.000 | 0.000 | -4415.15 | 0.000 | -8743.47 | -4744.95 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 8777.874 | -1261.92 | 0.000 | 0.000 | 2993.821 | 2456.001 | 10405.511 | 7049.457 | 0.000 | 1265.620 | 0.000 | 0.000 | -4253.79 | 0.000 | -8802.54 | -4738.83 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 8820.922 | -1289.10 | 0.000 | 0.000 | 2992.637 | 2456.001 | 10405.511 | 7224.584 | 0.000 | 1265.641 | 0.000 | 0.000 | -4380.60 | 0.000 | -8792.10 | -4513.09 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 7775.617 | -979.12 | 0.000 | 0.000 | 2993.064 | 2456.001 | 10405.511 | 1174.305 | 0.000 | 1225.433 | 0.000 | 0.000 | -1937.94 | 0.000 | -8431.61 | -3903.06 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 6573.171 | -1048.13 | 0.000 | 0.000 | 2983.970 | 2456.001 | 10405.511 | 3092.162 | 0.000 | 1224.883 | 0.000 | 0.000 | -1762.01 | 0.000 | -8501.83 | -3885.86 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 10056.141 | -1214.92 | 0.000 | 0.000 | 2999.882 | 2456.001 | 10405.511 | 5410.643 | 0.000 | 1266.237 | 0.000 | 0.000 | -4591.71 | 0.000 | -8725.67 | -4688.26 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5401.570 | 45627.892 | 0.000 | 0.000 | 0.000 | -51029.46 | -0.13 |
Total Facility | 0.000 | 0.000 | 123044.072 | -24159.17 | 0.000 | 0.000 | 53755.895 | 44208.020 | 187299.191 | 87655.365 | 0.000 | 26871.428 | 114804.779 | 0.000 | -64038.71 | 0.000 | -198321.21 | -85175.06 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 28-AUG-16:51 | 0.00 | 0.00 | 0.00 | -1.5 | 0.00 | 0.00 | 140.45 | 384.73 | 1343.91 | 4416.90 | 0.00 | 1361.51 | 10109.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 29-AUG-18:26 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 425.57 | 721.37 | 1713.78 | 282.90 | 0.00 | 1134.07 | 952.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-AUG-14:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.19 | 103.05 | 1100.57 | 2686.50 | 0.00 | 1587.73 | 946.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 01-JUL-17:19 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 263.35 | 535.87 | 1676.47 | 4925.76 | 0.00 | 1305.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -253.1 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11-JUL-18:04 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.07 | 721.37 | 1713.78 | 553.52 | 0.00 | 1229.42 | 257.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 02-JUL-09:45 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.84 | 103.05 | 1113.11 | 4029.42 | 0.00 | 1079.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -90.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28-AUG-16:19 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.45 | 384.73 | 1343.91 | 5273.39 | 0.00 | 1158.42 | 513.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 29-AUG-18:04 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.06 | 721.37 | 1713.78 | 360.59 | 0.00 | 996.30 | 1204.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29-AUG-16:23 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 140.34 | 384.73 | 1343.91 | 1677.51 | 0.00 | 1285.73 | 2064.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 01-JUL-17:19 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 263.35 | 535.87 | 1676.47 | 4906.65 | 0.00 | 1074.07 | 118.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 01-JUL-18:39 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.05 | 721.37 | 1735.60 | 575.37 | 0.00 | 905.81 | 730.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 02-JUL-09:30 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.02 | 103.05 | 1113.11 | 4436.53 | 0.00 | 918.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -151.6 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 27-AUG-17:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 263.34 | 535.87 | 1676.47 | 1163.09 | 0.00 | 1355.27 | 2821.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 29-AUG-16:23 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.29 | 384.73 | 1343.91 | 1659.80 | 0.00 | 1588.05 | 2881.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 28-AUG-16:19 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.45 | 384.73 | 1343.91 | 5236.82 | 0.00 | 1374.94 | 1819.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.05 | 721.37 | 1713.78 | 328.07 | 0.00 | 1130.11 | 2493.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 28-AUG-18:04 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.05 | 721.37 | 1713.78 | 293.06 | 0.00 | 1130.11 | 2591.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 28-AUG-16:36 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.45 | 384.73 | 1343.91 | 4813.56 | 0.00 | 1366.16 | 2154.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-AUG-17:05 | 0.00 | 0.00 | 0.00 | -11.2 | 0.00 | 0.00 | 4740.21 | 9645.69 | 29814.52 | 32498.57 | 0.00 | 22351.46 | 51001.56 | 0.00 | 0.00 | 0.00 | -15159.5 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 31-JAN-06:58 | 0.00 | 0.00 | 651.18 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1074.67 | 0.00 | 0.00 | 0.00 | 6069.41 | 0.00 | -2714.9 | 0.00 | -5991.4 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 07-JAN-04:47 | 0.00 | 0.00 | 13058.68 | 0.00 | 0.00 | 0.00 | 712.02 | 164.88 | 833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -927.4 | 0.00 | -4164.4 | -9676.8 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 07-JAN-04:47 | 0.00 | 0.00 | 10298.42 | 0.00 | 0.00 | 0.00 | 526.31 | 164.88 | 833.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2799.1 | 0.00 | -5799.3 | -3224.2 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 14-OCT-09:42 | 0.00 | 0.00 | 15592.23 | 0.00 | 0.00 | 0.00 | 133.10 | 103.05 | 1113.11 | 359.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -626.3 | -16674.9 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 10-MAR-17:49 | 0.00 | 0.00 | 11605.76 | 0.00 | 0.00 | 0.00 | 306.82 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -503.4 | 0.00 | -1816.3 | -11785.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 31-JAN-04:00 | 0.00 | 0.00 | 9732.84 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2719.9 | 0.00 | -6030.7 | -2410.4 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 02-APR-08:09 | 0.00 | 0.00 | 10225.93 | 0.00 | 0.00 | 0.00 | 218.21 | 151.14 | 1168.32 | 228.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1081.6 | -10910.1 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 06-MAR-18:24 | 0.00 | 0.00 | 8625.39 | 0.00 | 0.00 | 0.00 | 488.70 | 721.37 | 1713.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -611.8 | 0.00 | -1919.7 | -9017.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 07-JAN-07:00 | 0.00 | 0.00 | 8333.87 | 0.00 | 0.00 | 0.00 | 526.31 | 384.73 | 1081.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2859.8 | 0.00 | -4432.3 | -3034.8 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 17-DEC-18:57 | 0.00 | 0.00 | 15801.92 | 0.00 | 0.00 | 0.00 | 508.35 | 721.37 | 1735.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1642.3 | 0.00 | -2162.9 | -14962.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10-MAR-18:00 | 0.00 | 0.00 | 12197.21 | 0.00 | 0.00 | 0.00 | 301.41 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -514.5 | 0.00 | -1516.3 | -12660.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 07-JAN-07:00 | 0.00 | 0.00 | 8246.90 | 0.00 | 0.00 | 0.00 | 526.32 | 384.73 | 1081.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2886.7 | 0.00 | -4432.3 | -2920.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 31-JAN-06:50 | 0.00 | 0.00 | 10868.30 | 0.00 | 0.00 | 0.00 | 526.30 | 384.73 | 1074.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2818.0 | 0.00 | -5998.8 | -4037.1 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 07-JAN-07:00 | 0.00 | 0.00 | 10870.08 | 0.00 | 0.00 | 0.00 | 526.30 | 384.73 | 1081.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2847.8 | 0.00 | -5837.5 | -4177.7 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 07-JAN-08:15 | 0.00 | 0.00 | 10882.71 | 0.00 | 0.00 | 0.00 | 215.06 | 151.14 | 1168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2323.7 | 0.00 | -5666.8 | -4426.7 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 09-MAR-17:54 | 0.00 | 0.00 | 9827.45 | 0.00 | 0.00 | 0.00 | 302.10 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -534.0 | 0.00 | -1962.3 | -9825.4 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 07-JAN-08:15 | 0.00 | 0.00 | 8829.46 | 0.00 | 0.00 | 0.00 | 215.05 | 151.14 | 1168.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -780.9 | 0.00 | -5385.8 | -4197.2 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 17-DEC-16:58 | 0.00 | 0.00 | 14911.07 | 0.00 | 0.00 | 0.00 | 162.38 | 384.73 | 1363.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1268.0 | 0.00 | -1805.1 | -13748.9 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 07-JAN-04:47 | 0.00 | 0.00 | 157277.64 | 0.00 | 0.00 | 0.00 | 9659.31 | 2967.90 | 14994.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -40977.6 | 0.00 | -94445.3 | -49476.6 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 749.581 | 2.00 | 2.00 | 1.00 | 44.9950 | 749.581 | 0.060 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.467 | 2.00 | 2.00 | 1.00 | 44.9950 | 200.467 | 0.224 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 246.058 | 2.00 | 2.00 | 1.00 | 44.9950 | 246.058 | 0.183 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 341.401 | 2.00 | 2.00 | 1.00 | 44.9950 | 341.401 | 0.132 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 197.177 | 2.00 | 2.00 | 1.00 | 44.9950 | 197.177 | 0.228 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 246.691 | 2.00 | 2.00 | 1.00 | 44.9950 | 246.691 | 0.182 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 357.096 | 2.00 | 2.00 | 1.00 | 44.9950 | 357.096 | 0.126 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.988 | 2.00 | 2.00 | 1.00 | 44.9950 | 212.988 | 0.211 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 253.314 | 2.00 | 2.00 | 1.00 | 44.9950 | 253.314 | 0.178 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 349.715 | 2.00 | 2.00 | 1.00 | 44.9950 | 349.715 | 0.129 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 209.779 | 2.00 | 2.00 | 1.00 | 44.9950 | 209.779 | 0.214 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 252.642 | 2.00 | 2.00 | 1.00 | 44.9950 | 252.642 | 0.178 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.915 | 2.00 | 2.00 | 1.00 | 44.9950 | 420.915 | 0.107 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 276.916 | 2.00 | 2.00 | 1.00 | 44.9950 | 276.916 | 0.162 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 314.300 | 2.00 | 2.00 | 1.00 | 44.9950 | 314.300 | 0.143 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 421.017 | 2.00 | 2.00 | 1.00 | 44.9950 | 421.017 | 0.107 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 278.923 | 2.00 | 2.00 | 1.00 | 44.9950 | 278.923 | 0.161 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 315.493 | 2.00 | 2.00 | 1.00 | 44.9950 | 315.493 | 0.143 | 1.000 | 44.9950 | 0.14 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 121.785 | 2.00 | 2.00 | 1.00 | 44.9950 | 121.785 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 160.048 | 2.00 | 2.00 | 1.00 | 44.9950 | 160.048 | 1.000 | 1.000 | 44.9950 | 0.28 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 160.169 | 2.00 | 2.00 | 1.00 | 44.9950 | 160.169 | 1.000 | 1.000 | 44.9950 | 0.28 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 123.800 | 2.00 | 2.00 | 1.00 | 44.9950 | 123.800 | 1.000 | 1.000 | 44.9950 | 0.36 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 160.121 | 2.00 | 2.00 | 1.00 | 44.9950 | 160.121 | 1.000 | 1.000 | 44.9950 | 0.28 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.371 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.371 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 105.255 | 2.00 | 2.00 | 1.00 | 44.9950 | 105.255 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 142.374 | 2.00 | 2.00 | 1.00 | 44.9950 | 142.374 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 142.445 | 2.00 | 2.00 | 1.00 | 44.9950 | 142.445 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 105.718 | 2.00 | 2.00 | 1.00 | 44.9950 | 105.718 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 142.401 | 2.00 | 2.00 | 1.00 | 44.9950 | 142.401 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 183.428 | 2.00 | 2.00 | 1.00 | 44.9950 | 183.428 | 1.000 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 147.255 | 2.00 | 2.00 | 1.00 | 44.9950 | 147.255 | 1.000 | 1.000 | 44.9950 | 0.31 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 184.116 | 2.00 | 2.00 | 1.00 | 44.9950 | 184.116 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 184.221 | 2.00 | 2.00 | 1.00 | 44.9950 | 184.221 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 147.433 | 2.00 | 2.00 | 1.00 | 44.9950 | 147.433 | 1.000 | 1.000 | 44.9950 | 0.31 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 184.189 | 2.00 | 2.00 | 1.00 | 44.9950 | 184.189 | 1.000 | 1.000 | 44.9950 | 0.24 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 749.581 | 749.5805 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.467 | 200.4670 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 246.058 | 246.0579 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 341.401 | 341.4008 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 197.177 | 197.1765 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 246.691 | 246.6912 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 357.096 | 357.0962 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.988 | 212.9880 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 253.314 | 253.3137 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 349.715 | 349.7148 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 209.779 | 209.7789 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 252.642 | 252.6418 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 315.493 | 315.4934 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 314.300 | 314.2996 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.915 | 420.9152 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 278.923 | 278.9229 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 276.916 | 276.9157 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 421.017 | 421.0169 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 | 749.581 | 749.58 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 | 200.467 | 200.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 | 246.058 | 246.06 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 | 341.401 | 341.40 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 | 197.177 | 197.18 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 | 246.691 | 246.69 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 | 357.096 | 357.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 | 212.988 | 212.99 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 | 253.314 | 253.31 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 | 349.715 | 349.71 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 | 209.779 | 209.78 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 | 252.642 | 252.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.92 | 420.915 | 420.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 276.92 | 276.916 | 276.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 314.30 | 314.300 | 314.30 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 421.02 | 421.017 | 421.02 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 278.92 | 278.923 | 278.92 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 315.49 | 315.493 | 315.49 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 121.785 | 121.785 | 121.785 | 44.9950 | 0.369 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 160.048 | 160.048 | 160.048 | 44.9950 | 0.281 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 160.169 | 160.169 | 160.169 | 44.9950 | 0.281 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 123.800 | 123.800 | 123.800 | 44.9950 | 0.363 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 160.121 | 160.121 | 160.121 | 44.9950 | 0.281 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.371 | 137.371 | 137.371 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 105.255 | 105.255 | 105.255 | 44.9950 | 0.427 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 142.374 | 142.374 | 142.374 | 44.9950 | 0.316 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 142.445 | 142.445 | 142.445 | 44.9950 | 0.316 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 105.718 | 105.718 | 105.718 | 44.9950 | 0.426 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 142.401 | 142.401 | 142.401 | 44.9950 | 0.316 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 184.189 | 184.189 | 184.189 | 44.9950 | 0.244 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 184.116 | 184.116 | 184.116 | 44.9950 | 0.244 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 183.428 | 183.428 | 183.428 | 44.9950 | 0.245 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 147.433 | 147.433 | 147.433 | 44.9950 | 0.305 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 147.255 | 147.255 | 147.255 | 44.9950 | 0.306 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 184.221 | 184.221 | 184.221 | 44.9950 | 0.244 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 121.78 | 121.785 | 121.78 | 121.78 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 160.05 | 160.048 | 160.05 | 160.05 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 160.17 | 160.169 | 160.17 | 160.17 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 123.80 | 123.800 | 123.80 | 123.80 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 160.12 | 160.121 | 160.12 | 160.12 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 137.37 | 137.371 | 137.37 | 137.37 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 105.26 | 105.255 | 105.26 | 105.26 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 142.37 | 142.374 | 142.37 | 142.37 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 142.45 | 142.445 | 142.45 | 142.45 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 105.72 | 105.718 | 105.72 | 105.72 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 142.40 | 142.401 | 142.40 | 142.40 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 183.43 | 183.428 | 183.43 | 183.43 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 147.25 | 147.255 | 147.25 | 147.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 184.12 | 184.116 | 184.12 | 184.12 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 184.22 | 184.221 | 184.22 | 184.22 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 147.43 | 147.433 | 147.43 | 147.43 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 184.19 | 184.189 | 184.19 | 184.19 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 815.50 |
Number of hours cooling loads not met | 8.00 |
Number of hours not met | 823.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1489.13 | 189759.66 | 0.00 | 0.00 |
Space Cooling | 27519.82 | 13186.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 5753.74 | 1965.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2510.46 | 113429.16 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 15395.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 136612.81 | 3999.59 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 466453.14 |
Natural Gas | 0.00 | 399958.80 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 866411.94 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.71 |
Fans-Interior | 0.15 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 3.50 |
Natural Gas [kWh/ft2] | |
Space Heating | 1.12 |
Service Water Heating | 1.89 |
Miscellaneous | -0.0 |
Subtotal | 3.00 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.10 |
Space Heating | 17.19 |
Space Cooling | 10.85 |
Fans-Interior | 2.27 |
Service Water Heating | 28.98 |
Receptacle Equipment | 34.62 |
Miscellaneous | 1.01 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 315.49 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 314.30 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 420.92 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 278.92 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 276.92 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 421.02 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 420.92 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 276.92 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 314.30 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 421.02 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 278.92 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 315.49 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 | 1.92 | 0.749622 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 | 0.668084 | 0.676083 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 | 0.791504 | 0.684914 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 | 1.04 | 0.697902 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 | 0.657118 | 0.676083 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 | 0.792841 | 0.685138 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 | 1.06 | 0.705864 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 | 0.709812 | 0.676083 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 | 0.844203 | 0.676083 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 | 1.04 | 0.704355 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 | 0.699117 | 0.676083 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 | 0.798602 | 0.689391 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 420.92 | 1.22 | 0.713092 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 276.92 | 0.873598 | 0.689903 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 314.30 | 0.974204 | 0.694509 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 421.02 | 1.22 | 0.713106 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 278.92 | 0.878288 | 0.690387 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 315.49 | 0.972554 | 0.695959 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 | 749.58 | 749.58 | 1.92 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 | 200.47 | 200.47 | 0.668084 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 | 246.06 | 246.06 | 0.791504 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 | 341.40 | 341.40 | 1.04 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 | 197.18 | 197.18 | 0.657118 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 | 246.69 | 246.69 | 0.792841 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 | 357.10 | 357.10 | 1.06 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 | 212.99 | 212.99 | 0.709812 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 | 253.31 | 253.31 | 0.844203 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 | 349.71 | 349.71 | 1.04 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 | 209.78 | 209.78 | 0.699117 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 | 252.64 | 252.64 | 0.798602 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 420.92 | 420.92 | 420.92 | 1.22 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 276.92 | 276.92 | 276.92 | 0.873598 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 314.30 | 314.30 | 314.30 | 0.974204 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 421.02 | 421.02 | 421.02 | 1.22 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 278.92 | 278.92 | 278.92 | 0.878288 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 315.49 | 315.49 | 315.49 | 0.972554 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 42845.54 | 4.32 | 606.43 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 13402.29 | 1.35 | 179.94 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 15847.75 | 1.60 | 215.56 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 20961.57 | 2.12 | 289.91 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13225.81 | 1.33 | 177.36 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 15881.72 | 1.60 | 216.06 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 21802.63 | 2.20 | 302.10 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 14073.44 | 1.42 | 189.72 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 16236.40 | 1.64 | 221.20 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 21406.74 | 2.16 | 296.34 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 13901.33 | 1.40 | 187.21 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 16200.36 | 1.64 | 220.67 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 25226.46 | 2.55 | 351.80 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 17502.68 | 1.77 | 239.66 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19508.00 | 1.97 | 268.77 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 25231.92 | 2.55 | 351.88 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 17610.33 | 1.78 | 241.22 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19572.03 | 1.98 | 269.70 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 749.58 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 200.47 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 246.06 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 341.40 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 197.18 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 246.69 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 357.10 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 212.99 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 253.31 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 349.71 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 209.78 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 252.64 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 420.92 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 276.92 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 314.30 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 421.02 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 278.92 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 315.49 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 4.73 | 88.66 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 4.73 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 351743.28 | 35.37 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:31:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 679.832 | 47.524 | 4.806 | 0.018 | 47.543 |
February | 663.755 | 51.001 | 0.000 | 0.000 | 51.001 |
March | 744.000 | 81.537 | 0.000 | 0.000 | 81.537 |
April | 720.000 | 95.483 | 0.000 | 0.000 | 95.483 |
May | 744.000 | 122.606 | 0.000 | 0.000 | 122.606 |
June | 720.000 | 135.713 | 0.000 | 0.000 | 135.713 |
July | 744.000 | 150.257 | 0.000 | 0.000 | 150.257 |
August | 744.000 | 146.897 | 0.000 | 0.000 | 146.897 |
September | 720.000 | 130.201 | 0.000 | 0.000 | 130.201 |
October | 744.000 | 100.104 | 0.000 | 0.000 | 100.104 |
November | 720.000 | 77.225 | 0.000 | 0.000 | 77.225 |
December | 744.000 | 58.281 | 0.000 | 0.000 | 58.281 |
Annual Sum or Average | 8687.587 | 1196.828 | 4.806 | 0.018 | 1196.847 |
Minimum of Months | 663.755 | 47.524 | 0.000 | 0.000 | 47.543 |
Maximum of Months | 744.000 | 150.257 | 4.806 | 0.018 | 150.257 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 44.300 | 0.443 | 553.554 | 6.431 | 11.363 |
February | 67.225 | 0.698 | 459.171 | 4.904 | 6.225 |
March | 182.485 | 2.780 | 296.067 | 1.776 | 4.556 |
April | 381.801 | 6.546 | 113.000 | 0.520 | 7.066 |
May | 642.476 | 16.279 | 0.000 | 0.000 | 16.279 |
June | 701.081 | 25.741 | 0.000 | 0.000 | 25.741 |
July | 744.000 | 32.557 | 0.000 | 0.000 | 32.557 |
August | 740.562 | 30.800 | 0.000 | 0.000 | 30.800 |
September | 680.099 | 23.689 | 0.000 | 0.000 | 23.689 |
October | 430.057 | 8.168 | 74.812 | 0.260 | 8.427 |
November | 200.523 | 2.869 | 279.563 | 1.648 | 4.518 |
December | 43.667 | 0.334 | 531.837 | 4.661 | 4.995 |
Annual Sum or Average | 4858.276 | 150.904 | 2308.005 | 20.199 | 176.215 |
Minimum of Months | 43.667 | 0.334 | 0.000 | 0.000 | 4.518 |
Maximum of Months | 744.000 | 32.557 | 553.554 | 6.431 | 32.557 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 32.212 | 0.332 | 611.000 | 18.179 | 21.414 |
February | 57.920 | 0.730 | 458.875 | 12.189 | 16.087 |
March | 180.618 | 3.440 | 279.554 | 4.649 | 12.831 |
April | 385.350 | 8.690 | 92.431 | 1.419 | 12.852 |
May | 636.948 | 21.645 | 0.000 | 0.000 | 22.127 |
June | 698.713 | 33.371 | 0.000 | 0.000 | 33.371 |
July | 744.000 | 42.060 | 0.000 | 0.000 | 42.060 |
August | 732.813 | 39.286 | 0.000 | 0.000 | 39.286 |
September | 675.955 | 29.225 | 0.000 | 0.000 | 29.439 |
October | 397.565 | 9.170 | 62.792 | 0.861 | 14.998 |
November | 178.688 | 2.760 | 271.583 | 4.715 | 11.955 |
December | 30.875 | 0.253 | 528.633 | 12.093 | 17.659 |
Annual Sum or Average | 4751.656 | 190.960 | 2304.868 | 54.104 | 274.078 |
Minimum of Months | 30.875 | 0.253 | 0.000 | 0.000 | 11.955 |
Maximum of Months | 744.000 | 42.060 | 611.000 | 18.179 | 42.060 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 7.542 | 0.044 | 650.300 | 22.713 | 26.077 |
February | 17.563 | 0.140 | 503.527 | 15.134 | 22.434 |
March | 134.135 | 2.660 | 330.448 | 6.065 | 15.424 |
April | 321.116 | 8.192 | 124.261 | 1.823 | 14.728 |
May | 601.470 | 21.942 | 5.542 | 0.021 | 22.167 |
June | 692.533 | 35.386 | 0.000 | 0.000 | 35.386 |
July | 744.000 | 44.267 | 0.000 | 0.000 | 44.267 |
August | 731.071 | 40.622 | 0.000 | 0.000 | 40.622 |
September | 660.189 | 27.917 | 2.375 | 0.009 | 28.006 |
October | 306.592 | 6.406 | 139.824 | 1.511 | 13.619 |
November | 88.684 | 0.967 | 338.057 | 6.489 | 17.029 |
December | 18.500 | 0.098 | 589.854 | 16.359 | 24.706 |
Annual Sum or Average | 4323.395 | 188.641 | 2684.188 | 70.123 | 304.466 |
Minimum of Months | 7.542 | 0.044 | 0.000 | 0.000 | 13.619 |
Maximum of Months | 744.000 | 44.267 | 650.300 | 22.713 | 44.267 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 9.750 | 0.074 | 669.450 | 10.354 | 10.900 |
February | 7.812 | 0.031 | 539.205 | 6.788 | 7.707 |
March | 103.237 | 1.094 | 347.146 | 2.692 | 5.073 |
April | 326.250 | 5.003 | 135.560 | 0.788 | 6.467 |
May | 638.669 | 15.640 | 0.000 | 0.000 | 15.640 |
June | 701.414 | 25.523 | 0.000 | 0.000 | 25.523 |
July | 744.000 | 32.095 | 0.000 | 0.000 | 32.095 |
August | 740.562 | 29.134 | 0.000 | 0.000 | 29.134 |
September | 674.106 | 20.526 | 0.000 | 0.000 | 20.526 |
October | 300.654 | 4.260 | 132.031 | 0.582 | 5.601 |
November | 77.625 | 0.741 | 387.758 | 2.836 | 4.280 |
December | 24.125 | 0.117 | 646.846 | 7.396 | 7.728 |
Annual Sum or Average | 4348.205 | 134.239 | 2857.997 | 31.435 | 170.674 |
Minimum of Months | 7.812 | 0.031 | 0.000 | 0.000 | 4.280 |
Maximum of Months | 744.000 | 32.095 | 669.450 | 10.354 | 32.095 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 7.875 | 0.047 | 676.308 | 20.996 | 22.169 |
February | 11.250 | 0.044 | 539.470 | 13.917 | 16.307 |
March | 127.375 | 1.675 | 340.502 | 5.522 | 10.636 |
April | 340.470 | 7.030 | 108.250 | 1.609 | 10.790 |
May | 636.734 | 21.049 | 0.000 | 0.000 | 21.524 |
June | 699.076 | 33.186 | 0.000 | 0.000 | 33.186 |
July | 744.000 | 41.656 | 0.000 | 0.000 | 41.656 |
August | 732.813 | 37.781 | 0.000 | 0.000 | 37.781 |
September | 674.499 | 26.252 | 0.000 | 0.000 | 26.487 |
October | 303.377 | 5.081 | 107.607 | 1.242 | 11.619 |
November | 69.375 | 0.625 | 372.613 | 6.101 | 9.871 |
December | 14.750 | 0.066 | 650.042 | 15.355 | 16.259 |
Annual Sum or Average | 4361.594 | 174.492 | 2794.793 | 64.742 | 258.285 |
Minimum of Months | 7.875 | 0.044 | 0.000 | 0.000 | 9.871 |
Maximum of Months | 744.000 | 41.656 | 676.308 | 20.996 | 41.656 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 50.333 | 0.822 | 583.092 | 15.586 | 16.409 |
February | 78.629 | 1.469 | 453.771 | 10.691 | 12.167 |
March | 222.756 | 5.929 | 259.421 | 3.741 | 10.333 |
April | 413.659 | 12.291 | 85.217 | 1.041 | 15.674 |
May | 662.248 | 26.335 | 0.500 | 0.000 | 26.336 |
June | 703.414 | 39.408 | 0.000 | 0.000 | 39.408 |
July | 744.000 | 48.624 | 0.000 | 0.000 | 48.624 |
August | 741.437 | 46.302 | 0.000 | 0.000 | 46.302 |
September | 681.917 | 34.928 | 0.000 | 0.000 | 34.928 |
October | 450.273 | 13.108 | 70.216 | 0.656 | 14.703 |
November | 221.267 | 4.610 | 283.486 | 3.847 | 8.547 |
December | 66.083 | 0.678 | 519.787 | 10.331 | 11.010 |
Annual Sum or Average | 5036.017 | 234.504 | 2255.489 | 45.893 | 284.441 |
Minimum of Months | 50.333 | 0.678 | 0.000 | 0.000 | 8.547 |
Maximum of Months | 744.000 | 48.624 | 583.092 | 15.586 | 48.624 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 58.833 | 0.705 | 555.575 | 6.766 | 8.261 |
February | 84.512 | 0.964 | 428.362 | 4.496 | 5.716 |
March | 230.711 | 3.736 | 226.246 | 1.518 | 5.837 |
April | 443.790 | 8.506 | 84.325 | 0.391 | 9.032 |
May | 696.553 | 19.387 | 0.000 | 0.000 | 19.387 |
June | 711.055 | 28.460 | 0.000 | 0.000 | 28.460 |
July | 744.000 | 35.112 | 0.000 | 0.000 | 35.112 |
August | 744.000 | 33.485 | 0.000 | 0.000 | 33.485 |
September | 701.947 | 26.491 | 0.000 | 0.000 | 26.491 |
October | 481.352 | 10.162 | 46.353 | 0.160 | 10.322 |
November | 248.853 | 3.820 | 244.667 | 1.417 | 5.352 |
December | 67.500 | 0.638 | 484.696 | 4.145 | 5.066 |
Annual Sum or Average | 5213.106 | 171.464 | 2070.224 | 18.893 | 192.520 |
Minimum of Months | 58.833 | 0.638 | 0.000 | 0.000 | 5.066 |
Maximum of Months | 744.000 | 35.112 | 555.575 | 6.766 | 35.112 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 46.225 | 0.495 | 565.854 | 14.421 | 20.040 |
February | 73.979 | 0.934 | 423.346 | 9.834 | 13.979 |
March | 215.699 | 4.216 | 219.221 | 3.354 | 13.348 |
April | 442.252 | 10.392 | 70.750 | 0.921 | 13.440 |
May | 684.416 | 24.017 | 0.000 | 0.000 | 24.030 |
June | 707.188 | 35.109 | 0.000 | 0.000 | 35.109 |
July | 744.000 | 43.420 | 0.000 | 0.000 | 43.420 |
August | 741.750 | 40.878 | 0.000 | 0.000 | 40.878 |
September | 689.871 | 31.118 | 0.000 | 0.000 | 31.118 |
October | 461.976 | 10.729 | 38.083 | 0.469 | 14.383 |
November | 210.576 | 3.461 | 240.458 | 3.517 | 11.521 |
December | 51.000 | 0.445 | 485.717 | 9.624 | 16.578 |
Annual Sum or Average | 5068.930 | 205.214 | 2043.429 | 42.140 | 277.843 |
Minimum of Months | 46.225 | 0.445 | 0.000 | 0.000 | 11.521 |
Maximum of Months | 744.000 | 43.420 | 565.854 | 14.421 | 43.420 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 15.333 | 0.120 | 630.054 | 18.913 | 23.306 |
February | 21.750 | 0.207 | 471.520 | 12.559 | 20.274 |
March | 166.483 | 3.467 | 283.822 | 4.583 | 14.875 |
April | 379.908 | 10.204 | 96.212 | 1.238 | 15.755 |
May | 657.084 | 25.494 | 0.375 | 0.000 | 25.540 |
June | 703.389 | 38.983 | 0.000 | 0.000 | 38.983 |
July | 744.000 | 47.912 | 0.000 | 0.000 | 47.912 |
August | 741.437 | 44.370 | 0.000 | 0.000 | 44.370 |
September | 676.579 | 31.524 | 0.000 | 0.000 | 31.524 |
October | 365.756 | 8.131 | 88.548 | 0.916 | 14.446 |
November | 114.596 | 1.484 | 304.071 | 5.062 | 15.939 |
December | 38.583 | 0.269 | 561.833 | 13.525 | 24.784 |
Annual Sum or Average | 4624.899 | 212.166 | 2436.435 | 56.796 | 317.708 |
Minimum of Months | 15.333 | 0.120 | 0.000 | 0.000 | 14.446 |
Maximum of Months | 744.000 | 47.912 | 630.054 | 18.913 | 47.912 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 20.500 | 0.184 | 653.971 | 8.240 | 8.894 |
February | 16.863 | 0.093 | 505.879 | 5.444 | 6.158 |
March | 153.304 | 1.844 | 292.107 | 1.965 | 5.110 |
April | 397.211 | 6.900 | 104.569 | 0.485 | 7.622 |
May | 695.223 | 18.812 | 0.000 | 0.000 | 18.812 |
June | 712.010 | 28.271 | 0.000 | 0.000 | 28.271 |
July | 744.000 | 34.680 | 0.000 | 0.000 | 34.680 |
August | 744.000 | 31.904 | 0.000 | 0.000 | 31.904 |
September | 698.001 | 23.463 | 0.000 | 0.000 | 23.463 |
October | 360.300 | 5.923 | 87.327 | 0.337 | 6.465 |
November | 115.775 | 1.281 | 338.033 | 2.106 | 4.139 |
December | 49.167 | 0.365 | 624.496 | 5.990 | 6.498 |
Annual Sum or Average | 4706.354 | 153.720 | 2606.382 | 24.566 | 182.017 |
Minimum of Months | 16.863 | 0.093 | 0.000 | 0.000 | 4.139 |
Maximum of Months | 744.000 | 34.680 | 653.971 | 8.240 | 34.680 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 14.000 | 0.125 | 659.271 | 17.195 | 18.675 |
February | 16.000 | 0.108 | 503.518 | 11.314 | 13.781 |
March | 159.308 | 2.449 | 288.821 | 4.078 | 10.511 |
April | 405.690 | 9.063 | 80.225 | 1.042 | 12.336 |
May | 685.487 | 24.435 | 0.000 | 0.000 | 24.445 |
June | 707.675 | 36.345 | 0.000 | 0.000 | 36.345 |
July | 744.000 | 44.763 | 0.000 | 0.000 | 44.763 |
August | 741.750 | 41.025 | 0.000 | 0.000 | 41.025 |
September | 688.725 | 29.505 | 0.000 | 0.000 | 29.505 |
October | 364.389 | 6.749 | 61.865 | 0.715 | 11.227 |
November | 98.979 | 1.092 | 326.417 | 4.647 | 9.754 |
December | 36.208 | 0.217 | 624.808 | 12.597 | 14.663 |
Annual Sum or Average | 4662.211 | 195.875 | 2544.924 | 51.588 | 267.031 |
Minimum of Months | 14.000 | 0.108 | 0.000 | 0.000 | 9.754 |
Maximum of Months | 744.000 | 44.763 | 659.271 | 17.195 | 44.763 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 35.000 | 0.496 | 639.804 | 26.452 | 27.351 |
February | 60.208 | 1.044 | 497.083 | 18.248 | 20.599 |
March | 183.275 | 5.560 | 302.217 | 7.061 | 17.771 |
April | 367.882 | 12.647 | 96.505 | 2.011 | 21.223 |
May | 623.635 | 29.208 | 0.597 | 0.002 | 29.855 |
June | 697.895 | 45.556 | 0.000 | 0.000 | 45.556 |
July | 744.000 | 56.678 | 0.000 | 0.000 | 56.678 |
August | 736.304 | 53.277 | 0.000 | 0.000 | 53.277 |
September | 670.225 | 38.874 | 0.000 | 0.000 | 39.149 |
October | 390.526 | 12.820 | 91.469 | 1.528 | 20.932 |
November | 176.300 | 3.755 | 324.354 | 7.476 | 13.473 |
December | 34.375 | 0.372 | 599.383 | 18.629 | 19.454 |
Annual Sum or Average | 4719.626 | 260.287 | 2551.412 | 81.406 | 365.317 |
Minimum of Months | 34.375 | 0.372 | 0.000 | 0.000 | 13.473 |
Maximum of Months | 744.000 | 56.678 | 639.804 | 26.452 | 56.678 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 41.875 | 0.407 | 629.233 | 11.393 | 12.436 |
February | 56.017 | 0.690 | 480.458 | 7.733 | 8.437 |
March | 184.539 | 3.642 | 304.763 | 2.940 | 7.586 |
April | 390.353 | 9.148 | 116.750 | 0.881 | 10.289 |
May | 662.846 | 22.527 | 0.000 | 0.000 | 22.527 |
June | 706.030 | 34.922 | 0.000 | 0.000 | 34.922 |
July | 744.000 | 43.492 | 0.000 | 0.000 | 43.492 |
August | 742.500 | 40.842 | 0.000 | 0.000 | 40.842 |
September | 684.689 | 30.863 | 0.000 | 0.000 | 30.863 |
October | 432.570 | 10.235 | 90.069 | 0.518 | 10.759 |
November | 195.757 | 3.176 | 305.417 | 2.883 | 6.059 |
December | 46.000 | 0.393 | 586.333 | 7.696 | 8.438 |
Annual Sum or Average | 4887.175 | 200.335 | 2513.023 | 34.044 | 236.649 |
Minimum of Months | 41.875 | 0.393 | 0.000 | 0.000 | 6.059 |
Maximum of Months | 744.000 | 43.492 | 629.233 | 11.393 | 43.492 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 28.562 | 0.283 | 635.713 | 20.470 | 22.879 |
February | 46.038 | 0.686 | 473.667 | 13.829 | 17.759 |
March | 184.691 | 4.158 | 299.080 | 5.291 | 14.202 |
April | 404.478 | 11.058 | 97.685 | 1.522 | 15.232 |
May | 657.331 | 27.614 | 0.000 | 0.000 | 27.947 |
June | 704.237 | 42.305 | 0.000 | 0.000 | 42.305 |
July | 744.000 | 52.744 | 0.000 | 0.000 | 52.744 |
August | 738.125 | 49.118 | 0.000 | 0.000 | 49.118 |
September | 682.637 | 36.112 | 0.000 | 0.000 | 36.277 |
October | 404.620 | 10.930 | 74.177 | 1.030 | 16.801 |
November | 175.699 | 2.949 | 297.300 | 5.534 | 12.561 |
December | 32.000 | 0.288 | 590.042 | 14.318 | 18.341 |
Annual Sum or Average | 4802.420 | 238.247 | 2467.663 | 61.994 | 326.167 |
Minimum of Months | 28.562 | 0.283 | 0.000 | 0.000 | 12.561 |
Maximum of Months | 744.000 | 52.744 | 635.713 | 20.470 | 52.744 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 8.875 | 0.077 | 658.813 | 25.543 | 28.166 |
February | 21.471 | 0.235 | 507.183 | 17.165 | 24.412 |
March | 155.129 | 4.117 | 332.075 | 6.798 | 16.483 |
April | 353.740 | 11.677 | 115.393 | 1.990 | 19.027 |
May | 623.535 | 29.012 | 3.899 | 0.013 | 29.273 |
June | 698.462 | 45.644 | 0.000 | 0.000 | 45.644 |
July | 744.000 | 56.668 | 0.000 | 0.000 | 56.668 |
August | 736.575 | 52.592 | 0.000 | 0.000 | 52.592 |
September | 667.347 | 36.908 | 1.625 | 0.006 | 37.012 |
October | 335.064 | 9.376 | 126.854 | 1.665 | 19.158 |
November | 105.663 | 1.513 | 344.238 | 7.548 | 18.518 |
December | 22.500 | 0.157 | 627.542 | 19.140 | 23.381 |
Annual Sum or Average | 4472.361 | 247.976 | 2717.621 | 79.868 | 370.333 |
Minimum of Months | 8.875 | 0.077 | 0.000 | 0.000 | 16.483 |
Maximum of Months | 744.000 | 56.668 | 658.813 | 25.543 | 56.668 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 11.000 | 0.116 | 669.125 | 13.112 | 13.733 |
February | 13.750 | 0.107 | 533.975 | 8.744 | 9.525 |
March | 144.225 | 2.382 | 337.724 | 3.358 | 7.007 |
April | 371.157 | 8.309 | 128.326 | 0.974 | 9.623 |
May | 661.947 | 22.411 | 0.000 | 0.000 | 22.411 |
June | 706.367 | 35.086 | 0.000 | 0.000 | 35.086 |
July | 744.000 | 43.576 | 0.000 | 0.000 | 43.576 |
August | 742.625 | 40.281 | 0.000 | 0.000 | 40.281 |
September | 681.219 | 29.039 | 0.000 | 0.000 | 29.039 |
October | 349.308 | 7.100 | 132.752 | 0.791 | 8.166 |
November | 101.525 | 1.255 | 381.687 | 3.750 | 5.818 |
December | 32.579 | 0.200 | 648.396 | 9.687 | 10.081 |
Annual Sum or Average | 4559.701 | 189.862 | 2831.985 | 40.416 | 234.345 |
Minimum of Months | 11.000 | 0.107 | 0.000 | 0.000 | 5.818 |
Maximum of Months | 744.000 | 43.576 | 669.125 | 13.112 | 43.576 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 9.917 | 0.084 | 676.375 | 22.721 | 23.885 |
February | 14.250 | 0.124 | 532.783 | 15.123 | 17.879 |
March | 150.045 | 2.905 | 333.862 | 5.810 | 12.497 |
April | 389.441 | 10.208 | 107.031 | 1.617 | 14.465 |
May | 657.573 | 27.559 | 0.000 | 0.000 | 27.884 |
June | 704.585 | 42.548 | 0.000 | 0.000 | 42.548 |
July | 744.000 | 52.936 | 0.000 | 0.000 | 52.936 |
August | 738.187 | 48.712 | 0.000 | 0.000 | 48.712 |
September | 681.985 | 34.481 | 0.000 | 0.000 | 34.658 |
October | 335.753 | 7.779 | 104.776 | 1.331 | 14.340 |
November | 92.262 | 1.070 | 377.679 | 6.716 | 11.108 |
December | 18.750 | 0.116 | 650.500 | 16.891 | 17.890 |
Annual Sum or Average | 4536.749 | 228.522 | 2783.007 | 70.210 | 318.802 |
Minimum of Months | 9.917 | 0.084 | 0.000 | 0.000 | 11.108 |
Maximum of Months | 744.000 | 52.936 | 676.375 | 22.721 | 52.936 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.42 |
February | 0.00 | 0.00 | 0.49 |
March | 0.00 | 0.00 | 0.71 |
April | 0.00 | 0.00 | 0.86 |
May | 0.00 | 0.00 | 1.06 |
June | 0.00 | 0.00 | 1.21 |
July | 0.00 | 0.00 | 1.28 |
August | 0.00 | 0.00 | 1.25 |
September | 0.00 | 0.00 | 1.17 |
October | 0.00 | 0.00 | 0.87 |
November | 0.00 | 0.00 | 0.70 |
December | 0.00 | 0.00 | 0.51 |
Annual Sum or Average | 0.00 | 0.00 | 0.88 |
Minimum of Months | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.00 | 0.00 | 1.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.24 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.23 |
June | 0.00 | 0.00 | 0.37 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.41 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.45 |
September | 0.00 | 0.00 | 0.36 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.48 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.47 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.21 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.00 | 0.48 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.48 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.00 | 0.34 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.29 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.51 |
September | 0.00 | 0.00 | 0.39 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.03 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.55 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.54 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.54 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.38 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.11 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.45 |
July | 0.00 | 0.00 | 0.55 |
August | 0.00 | 0.00 | 0.50 |
September | 0.00 | 0.00 | 0.37 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.55 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:31:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1513.38 | 1126.75 |
February | 0.00 | 0.00 | 1519.61 | 1021.90 |
March | 0.00 | 0.00 | 1460.02 | 1087.03 |
April | 0.00 | 0.00 | 1353.00 | 974.85 |
May | 0.00 | 0.00 | 1220.09 | 908.39 |
June | 0.00 | 0.00 | 1103.90 | 795.37 |
July | 0.00 | 0.00 | 1035.84 | 771.21 |
August | 0.00 | 0.00 | 1025.86 | 763.78 |
September | 0.00 | 0.00 | 1087.81 | 783.78 |
October | 0.00 | 0.00 | 1199.24 | 892.86 |
November | 0.00 | 0.00 | 1327.58 | 956.54 |
December | 0.00 | 0.00 | 1444.06 | 1075.14 |
Annual Sum or Average | 0.00 | 0.00 | 1272.80 | 11157.61 |
Minimum of Months | 0.00 | 0.00 | 1025.86 | 763.78 |
Maximum of Months | 0.00 | 0.00 | 1519.61 | 1126.75 |