Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31

Tabular Output Report in Format: HTML

Building: MF+CZ3A+USA_TN_Memphis.Intl.AP.723340+gasfurnace+heatedbsmt+IECC_2012

Environment: ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340

Simulation Timestamp: 2019-02-14 08:31:25


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 993872.81 25.48 33.80
Net Site Energy 993872.81 25.48 33.80
Total Source Energy 2007204.43 51.46 68.26
Net Source Energy 2007204.43 51.46 68.26


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 132454.09 0.00 0.00 0.00 0.00
Cooling 108930.56 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 261812.16 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 22721.91 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 251047.89 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 446397.65 547475.17 0.00 0.00 0.00 377715.79
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 132454.09 0.00 0.00 0.00 0.00
Cooling General 108930.56 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 22721.91 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 251047.89 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.80 0.00 0.00 0.00 0.00 0.00
HVAC 4.48 13.04 0.00 0.00 0.00 12.85
Other 8.90 5.58 0.00 0.00 0.00 0.00
Total 15.18 18.62 0.00 0.00 0.00 12.85


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 3.38 9.83 0.00 0.00 0.00 9.68
Other 6.71 4.20 0.00 0.00 0.00 0.00
Total 11.44 14.04 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 446397.647 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 446397.647 100.00
     
Total On-Site and Utility Electric Sources 446397.647 100.00
Total Electricity End Uses 446397.647 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 4.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 686.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:31
RunPeriod ANNUAL
Weather File Memphis International Ap TN USA TMY3 WMO#=723340
Latitude [deg] 35.07
Longitude [deg] -90.0
Elevation [ft] 265.76
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 4.4634
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.3689 1083.48 2.4729
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.4894 816.79 3.2803
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 19-AUG-18:15 07-JAN-08:45 - - - 01-JAN-08:15
Heating 0.00 170.31 0.00 0.00 0.00 0.00
Cooling 49.80 0.00 0.00 0.00 0.00 0.00
Interior Lighting 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.10 0.00 0.00 0.00 0.00 0.00
Interior Equipment 41.39 22.33 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.64 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 149.10 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 113.93 341.74 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 170.31 0.00 0.00 0.00 0.00
Cooling General 49.80 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 12.99 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.62 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.48 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.38 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.74 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.63 12.06 0.00 0.00 0.00 0.00
  gas_range 0.00 8.49 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 22.66 1.77 0.00 0.00 0.00 0.00
  IECC_adj 9.39 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.64 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 149.10 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 143580.23 0.00 0.00 0.00
Cooling 344983.10 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 829159.12 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 71960.29 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 272135.91 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1413741.35 593463.08 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 4.88 0.00 0.00 0.00
Cooling 11.73 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 28.20 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.45 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.25 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 48.08 20.18 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 4.88 0.00 0.00 0.00
Cooling 11.73 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 28.20 6.04 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.45 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 9.25 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 48.08 20.18 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 17.06 0.00 17.06 Wetbulb [F] 807.13 0.00
MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 96.08 16.56 77.36 Wetbulb [F] 748.07 240.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.218 0.882              
North Total or Average           531.68 0.350 0.218 0.882              
Non-North Total or Average           1595.05 0.350 0.218 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 1.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   23993.03 18095.60 5897.43 0.75 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9601.05 6550.50 3050.55 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10740.70 7383.59 3357.12 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13607.31 9628.48 3978.83 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9515.80 6482.56 3033.24 0.68 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10558.56 7256.39 3302.17 0.69 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13514.38 9644.39 3869.99 0.71 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9532.37 6548.46 2983.90 0.69 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10636.14 7377.71 3258.43 0.69 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13351.89 9512.96 3838.93 0.71 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9450.60 6482.64 2967.96 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10482.38 7271.98 3210.40 0.69 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15377.25 11068.19 4309.06 0.72 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11428.66 7991.98 3436.68 0.70 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12521.70 8812.19 3709.51 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15394.43 11082.10 4312.33 0.72 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11485.89 8037.26 3448.63 0.70 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12567.51 8848.55 3718.96 0.70 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   3092.54 2090.81 1001.72 0.68 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.9 3.34 11.41 12.09 11.73
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.8 3.49 11.89 12.63 12.54
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.48 11.86 12.59 12.48
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.43 11.72 12.43 12.24
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.8 3.49 11.90 12.63 12.55
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.9 3.48 11.86 12.59 12.48
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.42 11.68 12.39 12.17
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.8 3.48 11.86 12.59 12.48
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.46 11.81 12.54 12.40
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.42 11.69 12.39 12.19
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.48 11.87 12.60 12.49
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.46 11.81 12.54 12.40
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.2 3.41 11.64 12.34 12.10
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.45 11.78 12.49 12.34
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.44 11.74 12.46 12.29
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.2 3.41 11.63 12.34 12.10
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.45 11.77 12.49 12.33
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.44 11.74 12.46 12.28
DX COOLING COIL_UNITHEATEDBSMT   0.2 3.50 11.94 12.67 12.61
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   5063.51 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   8493.80 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   10560.53 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   10568.91 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   8633.72 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   10566.38 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   9486.14 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   7845.02 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   9835.95 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   9840.35 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   7876.59 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   9837.97 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12049.51 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   10114.85 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12095.21 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   12101.02 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   10125.68 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   12099.30 0.80
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel   6797.39 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 791.18 298.43 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 246.14 92.84 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 281.02 106.00 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 384.00 144.84 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 242.95 91.64 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 276.05 104.12 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 389.71 147.00 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 248.95 93.90 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 285.02 107.51 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 383.45 144.63 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 245.83 92.72 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 280.99 105.99 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 453.06 170.89 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 312.84 118.00 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 348.46 131.44 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 453.73 171.14 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 314.94 118.79 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 350.15 132.08 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 77.33 29.17 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18408.92 18408.92 15.33 791.183 791.183 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00866 92.52 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5727.06 5727.06 4.77 246.136 246.136 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00987 89.62 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6538.70 6538.70 5.45 281.019 281.019 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00967 91.48 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8934.92 8934.92 7.44 384.004 384.004 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00926 92.52 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5653.00 5653.00 4.71 242.953 242.953 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00990 89.62 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6423.09 6423.09 5.35 276.050 276.050 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00971 90.86 0.01615 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9067.90 9067.90 7.55 389.714 389.714 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00911 92.11 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5792.57 5792.57 4.82 248.948 248.948 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00966 89.62 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6631.81 6631.81 5.52 285.017 285.017 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00949 90.86 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8922.14 8922.14 7.43 383.449 383.449 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00913 92.11 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5719.96 5719.96 4.76 245.828 245.828 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00969 89.62 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6538.13 6538.13 5.45 280.991 280.991 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00952 90.24 0.01615 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8147.28 8147.28 6.79 350.153 350.153 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00941 90.86 0.01615 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8107.84 8107.84 6.75 348.458 348.458 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00941 90.86 0.01615 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10541.74 10541.74 8.78 453.063 453.063 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00910 92.11 0.01615 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7328.01 7328.01 6.10 314.942 314.942 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00953 89.62 0.01615 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7279.08 7279.08 6.06 312.839 312.839 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00954 89.62 0.01615 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10557.18 10557.18 8.79 453.726 453.726 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00910 92.11 0.01615 44.995 0.00
HEATEDBSMT 1161.64 1161.64 0.15 49.919 49.919 MEMPHIS INTERNATIONAL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00811 89.62 0.01615 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.000 44.995 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB   32.00 32.00 0.00000 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5929.97 5929.97 4.94 108.951 108.951 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00577 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8027.29 8027.29 6.69 147.483 147.483 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00609 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8035.80 8035.80 6.69 147.639 147.639 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00609 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6071.96 6071.96 5.06 111.560 111.560 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00580 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8033.23 8033.23 6.69 147.592 147.592 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.98 0.00609 17.06 0.00188 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6936.90 6936.90 5.78 127.455 127.455 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00625 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5271.48 5271.48 4.39 96.857 96.857 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00600 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7291.88 7291.88 6.07 133.977 133.977 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7296.35 7296.35 6.08 134.059 134.059 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5303.52 5303.52 4.42 97.446 97.446 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00601 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7293.94 7293.94 6.08 134.015 134.015 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:00:00 72.00 71.99 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9588.81 9588.81 7.99 176.171 176.171 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9584.66 9584.66 7.98 176.095 176.095 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9538.29 9538.29 7.94 175.243 175.243 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00630 17.06 0.00188 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7585.98 7585.98 6.32 139.376 139.376 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00608 17.06 0.00188 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7574.99 7574.99 6.31 139.174 139.174 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00608 17.06 0.00188 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9590.55 9590.55 7.99 176.203 176.203 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 11:15:00 72.00 71.98 0.00630 17.06 0.00188 44.995 0.00
HEATEDBSMT 4207.94 4207.94 0.54 77.330 77.330 MEMPHIS INTERNATIONAL AP ANN HTG 99.6% CONDNS DB 1/21 07:30:00 72.00 72.00 0.00800 17.06 0.00188 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 791.18 791.18 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 246.14 246.14 108.95 108.95
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 281.02 281.02 147.48 147.48
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 384.00 384.00 147.64 147.64
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 242.95 242.95 111.56 111.56
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.05 276.05 147.59 147.59
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 389.71 389.71 127.46 127.46
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 248.95 248.95 96.86 96.86
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 285.02 285.02 133.98 133.98
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 383.45 383.45 134.06 134.06
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.83 245.83 97.45 97.45
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 280.99 280.99 134.02 134.02
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.06 453.06 175.24 175.24
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 312.84 312.84 139.17 139.17
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 348.46 348.46 176.09 176.09
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 453.73 453.73 176.20 176.20
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 314.94 314.94 139.38 139.38
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.15 350.15 176.17 176.17
CENTRAL SYSTEM_UNITHEATEDBSMT 49.92 49.92 77.33 77.33


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2133.75 3886.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3570.00 3712.75 341.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3723.00 3905.75 364.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3753.00 4394.00 519.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3471.50 4167.75 361.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3634.25 4242.50 378.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3880.50 3663.75 253.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3562.75 3361.25 107.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3734.25 3602.75 187.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3764.50 4033.50 281.25
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3470.25 3773.25 109.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3652.25 3941.25 195.75
LIVING_UNIT3_BACKROW_TOPFLOOR 3937.00 4174.00 435.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 3968.50 3947.00 402.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 4036.25 4089.50 508.25
LIVING_UNIT2_BACKROW_TOPFLOOR 3720.25 4105.75 323.25
LIVING_UNIT2_FRONTROW_TOPFLOOR 3773.75 3821.00 299.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3991.50 4314.75 556.75
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4298.75 4911.00 686.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 4.25 0.00 4.25
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 1.00 0.00 1.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 4.25 0.00 4.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.107 0.000 0.271
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.093 0.000 0.271
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.105 0.000 0.271
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.105 0.000 0.271
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.092 0.000 0.271
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.105 0.000 0.271
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.271
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.034 0.000 0.271
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.271
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.271
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.033 0.000 0.271
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.271
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.105 0.000 0.271
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.105 0.000 0.271
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.105 0.000 0.271
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.092 0.000 0.271
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.093 0.000 0.271
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.105 0.000 0.271
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1900
Defaulted Fields 509
Fields with Defaults 4982
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
Electricity:Building 89625.89 7014.87 02-JAN-03:15 16912.36 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4979.22 389.71 02-JAN-03:15 939.58 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 76678.43 6519.25 02-JAN-04:15 12694.94 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4259.91 362.18 02-JAN-04:15 705.27 01-JAN-20:15
Fans:Electricity 6654.70 94.26 19-NOV-22:00 2272.40 19-AUG-17:30
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
ElectricityPurchased:Plant 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
Cogeneration:ElectricityPurchased 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
ElectricityNet:Plant 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
Cogeneration:ElectricityNet 130739.04 8002.11 09-MAR-03:15 33367.19 19-AUG-18:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 38557.82 467.14 19-NOV-22:00 17242.69 29-AUG-16:30
General:Fans:Electricity 6654.70 94.26 19-NOV-22:00 2272.40 19-AUG-17:30
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 31903.12 0.00 06-JAN-23:30 15016.94 29-AUG-16:30
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 5474.75 2644.47 01-MAY-03:15 341492.89 07-JAN-08:45
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 2510.48 0.00 01-JAN-00:15 149101.78 29-JAN-08:15
WaterSystems:Gas 2510.48 0.00 01-JAN-00:15 149101.78 29-JAN-08:15
Water Heater:WaterSystems:Gas 2510.48 0.00 01-JAN-00:15 149101.78 29-JAN-08:15
Gas:HVAC 1324.54 0.00 01-MAY-02:15 177426.16 07-JAN-05:00
Heating:Gas 1324.54 0.00 01-MAY-02:15 177426.16 07-JAN-05:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
Water:Plant 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
WaterSystems:Water 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
MainsWater:Plant 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
WaterSystems:MainsWater 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 09-MAR-02:45 0.18 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
PlantLoopHeatingDemand:Plant 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
WaterSystems:PlantLoopHeatingDemand 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1158003.96 15948.98 04-OCT-02:30 360036.85 19-AUG-17:30
EnergyTransfer:Building 455572.75 6944.80 16-OCT-00:15 150394.77 28-AUG-17:15
EnergyTransfer:Zone:HEATEDBSMT 10023.60 0.00 01-MAY-02:15 4294.72 07-JAN-08:00
Heating:EnergyTransfer 110096.52 0.00 01-MAY-02:15 147662.72 07-JAN-05:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 8704.01 0.00 01-MAY-02:15 4294.72 07-JAN-08:00
Cooling:EnergyTransfer 345476.23 0.00 06-JAN-23:30 150394.77 28-AUG-17:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 1319.58 0.00 01-JAN-00:15 1263.65 28-AUG-17:30
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 84908.42 0.00 06-JAN-23:30 18761.76 01-JUL-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 84908.42 0.00 06-JAN-23:30 18761.76 01-JUL-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17091.34 0.00 01-JAN-11:30 6901.48 07-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3723.46 0.00 01-JAN-11:30 6901.48 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13367.88 0.00 01-JAN-00:15 6256.39 29-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 21780.02 0.00 04-JAN-14:00 9235.59 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5899.22 0.00 04-JAN-14:00 9235.59 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15880.80 0.00 01-JAN-00:15 7348.28 29-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 21667.90 0.00 13-JAN-13:45 9518.56 01-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7117.72 0.00 13-JAN-13:45 9249.31 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 14550.18 0.00 01-JAN-00:15 9518.56 01-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16681.18 0.00 13-JAN-14:00 7045.06 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4985.60 0.00 13-JAN-14:00 7045.06 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11695.59 0.00 01-JAN-00:15 5959.33 11-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21265.95 0.00 13-JAN-13:00 9262.16 31-JAN-04:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6993.23 0.00 13-JAN-13:00 9262.16 31-JAN-04:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14272.72 0.00 01-JAN-00:15 7088.55 02-JUL-09:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21512.12 0.00 01-JAN-14:15 9460.95 01-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4477.97 0.00 01-JAN-14:15 7729.97 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 17034.15 0.00 01-JAN-00:15 9460.95 01-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17149.77 0.00 01-JAN-14:00 6213.92 29-AUG-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2922.45 0.00 01-JAN-14:00 5739.69 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14227.32 0.00 01-JAN-00:15 6213.92 29-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21575.99 0.00 04-JAN-14:00 7942.81 07-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4877.16 0.00 04-JAN-14:00 7942.81 07-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16698.83 0.00 01-JAN-00:15 7375.71 29-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 21305.28 0.00 13-JAN-14:00 9371.93 01-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6004.73 0.00 13-JAN-14:00 8047.20 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15300.56 0.00 01-JAN-00:15 9371.93 01-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16441.29 0.00 01-JAN-18:45 5941.83 01-JUL-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3908.24 0.00 01-JAN-18:45 5868.63 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12533.05 0.00 01-JAN-00:15 5941.83 01-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20967.66 0.00 13-JAN-13:15 7953.97 07-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5893.30 0.00 13-JAN-13:15 7953.97 07-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15074.36 0.00 01-JAN-00:15 6967.47 02-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 25299.74 0.00 13-JAN-14:15 10581.75 07-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8620.11 0.00 13-JAN-14:15 10581.75 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 16679.63 0.00 01-JAN-00:15 8506.26 27-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 25227.59 0.00 10-JAN-14:45 10566.57 07-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 7593.28 0.00 10-JAN-14:45 10566.57 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 17634.31 0.00 01-JAN-00:15 8592.81 27-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 25623.90 0.00 04-JAN-15:15 10962.71 28-AUG-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 7664.74 0.00 04-JAN-15:15 10550.22 07-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 17959.16 0.00 01-JAN-00:15 10962.71 28-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 20673.92 0.00 13-JAN-15:00 8452.50 07-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6484.77 0.00 13-JAN-15:00 8452.50 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14189.15 0.00 01-JAN-00:15 7633.97 28-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20594.13 0.00 04-JAN-18:15 8336.35 07-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5422.44 0.00 04-JAN-18:15 8336.35 07-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15171.68 0.00 01-JAN-00:15 7693.48 28-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 25782.94 0.00 13-JAN-14:15 10955.01 01-JUL-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 8804.09 0.00 13-JAN-14:15 10646.72 07-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 16978.85 0.00 01-JAN-00:15 10955.01 01-JUL-17:30
EnergyTransfer:Plant 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
WaterSystems:EnergyTransfer 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
Domestic Hot Water:WaterSystems:EnergyTransfer 122678.87 887.75 02-AUG-02:15 35288.25 29-JAN-08:30
EnergyTransfer:HVAC 579752.34 7526.02 16-OCT-00:15 200598.20 19-AUG-17:30
HeatingCoils:EnergyTransfer 105963.27 0.00 01-MAY-02:15 141940.92 07-JAN-05:00
CoolingCoils:EnergyTransfer 473789.07 0.00 06-JAN-23:30 200598.20 19-AUG-17:30



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 0.000 -7070.98 0.000 0.000 2874.302 2456.001 14468.945 7176.417 0.000 1275.493 70855.495 0.000 -4617.97 0.000 -9580.25 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 3723.403 -1113.25 0.000 0.000 2965.242 2456.001 14468.945 3098.907 0.000 1234.325 0.000 0.000 -1777.78 0.000 -8608.41 -4192.72
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 5899.137 -1322.52 0.000 0.000 2979.624 2456.001 14468.945 7070.752 0.000 1275.157 0.000 0.000 -4266.33 0.000 -8880.43 -5122.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 7117.630 -1211.70 0.000 0.000 2987.354 2456.001 14468.945 5434.480 0.000 1275.391 0.000 0.000 -4599.88 0.000 -8793.82 -5795.96
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 4985.535 -973.99 0.000 0.000 2977.910 2456.001 14468.945 1177.564 0.000 1234.317 0.000 0.000 -1948.38 0.000 -8502.05 -5154.18
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 6993.146 -1188.60 0.000 0.000 2988.190 2456.001 14468.945 5199.929 0.000 1275.419 0.000 0.000 -4419.79 0.000 -8805.48 -5883.57
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 4477.904 -1418.56 0.000 0.000 2968.285 2456.001 14468.945 7206.666 0.000 1077.880 0.013 0.000 -4483.14 0.000 -7349.46 -3788.98
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 2922.403 -1184.82 0.000 0.000 2956.160 2456.001 14468.945 3086.385 0.000 1036.978 0.000 0.000 -1802.50 0.000 -7057.75 -3839.24
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 4877.094 -1390.64 0.000 0.000 2971.582 2456.001 14468.945 7039.913 0.000 1077.842 0.000 0.000 -4331.24 0.000 -7341.09 -4520.16
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 6004.655 -1274.19 0.000 0.000 2979.457 2456.001 14468.945 5417.801 0.000 1077.906 0.000 0.000 -4669.60 0.000 -7269.37 -5165.24
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 3908.195 -1043.73 0.000 0.000 2969.071 2456.001 14468.945 1175.540 0.000 1036.979 0.000 0.000 -1976.75 0.000 -6973.45 -4531.40
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 5893.231 -1255.36 0.000 0.000 2980.771 2456.001 14468.945 5179.637 0.000 1077.899 0.000 0.000 -4483.40 0.000 -7277.48 -5221.15
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 8620.018 -1389.05 0.000 0.000 2989.090 2456.001 14468.945 5169.298 0.000 1265.652 0.000 0.000 -4458.48 0.000 -8816.00 -5014.81
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 7593.187 -1468.55 0.000 0.000 2982.960 2456.001 14468.945 7043.639 0.000 1265.651 0.000 0.000 -4292.35 0.000 -8869.83 -5013.82
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 7664.648 -1495.59 0.000 0.000 2982.463 2456.001 14468.945 7216.808 0.000 1265.633 0.000 0.000 -4415.43 0.000 -8860.20 -4819.76
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 6484.703 -1181.64 0.000 0.000 2979.898 2456.001 14468.945 1169.592 0.000 1224.933 0.000 0.000 -1959.57 0.000 -8510.99 -4124.30
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 5422.377 -1263.47 0.000 0.000 2972.348 2456.001 14468.945 3087.578 0.000 1224.878 0.000 0.000 -1779.94 0.000 -8574.09 -4106.36
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 8803.992 -1413.96 0.000 0.000 2988.181 2456.001 14468.945 5396.602 0.000 1265.745 0.000 0.000 -4633.43 0.000 -8808.48 -4958.75
HEATEDBSMT 0.000 0.000 8704.013 -109.89 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -7384.43
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5371.593 45714.354 0.000 0.000 0.000 -51085.95 -0.03
Total Facility 0.000 0.000 110095.272 -28770.50 0.000 0.000 53492.889 44208.020 260441.015 87347.508 0.000 26839.671 116569.863 0.000 -64915.97 0.000 -199964.59 -88636.88


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 01-JUL-17:06 0.00 0.00 0.00 -1.6 0.00 0.00 263.34 535.87 2778.60 4964.08 0.00 1339.15 8929.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-AUG-18:04 0.00 0.00 0.00 -0.5 0.00 0.00 427.07 721.37 2654.97 360.23 0.00 1236.88 856.44 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-AUG-18:15 0.00 0.00 0.00 -0.6 0.00 0.00 426.02 721.37 2654.97 864.16 0.00 1285.97 1401.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 01-JUL-17:19 0.00 0.00 0.00 -0.8 0.00 0.00 263.35 535.87 2778.60 4935.86 0.00 1305.51 0.00 0.00 0.00 0.00 0.00 -298.2
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11-JUL-18:04 0.00 0.00 0.00 -0.5 0.00 0.00 427.07 721.37 2654.97 553.19 0.00 1229.42 374.24 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 02-JUL-09:10 0.00 0.00 0.00 -0.6 0.00 0.00 114.96 103.05 1590.30 4744.03 0.00 1045.80 0.00 0.00 0.00 0.00 0.00 -476.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 01-JUL-17:19 0.00 0.00 0.00 -0.8 0.00 0.00 263.34 535.87 2778.60 4765.97 0.00 1074.06 45.19 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-AUG-18:04 0.00 0.00 0.00 -0.5 0.00 0.00 427.06 721.37 2654.97 363.13 0.00 996.29 1051.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-AUG-16:23 0.00 0.00 0.00 -0.6 0.00 0.00 140.40 384.73 2088.16 1687.74 0.00 1285.69 1792.43 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 01-JUL-17:19 0.00 0.00 0.00 -0.8 0.00 0.00 263.34 535.87 2778.60 4922.18 0.00 1074.07 0.00 0.00 0.00 0.00 0.00 -199.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 01-JUL-18:33 0.00 0.00 0.00 -0.5 0.00 0.00 427.05 721.37 2685.69 577.93 0.00 905.81 624.19 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 02-JUL-08:48 0.00 0.00 0.00 -0.6 0.00 0.00 194.55 151.14 1644.19 4926.55 0.00 890.32 0.00 0.00 0.00 0.00 0.00 -838.5
LIVING_UNIT3_BACKROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 263.34 535.87 2778.60 1180.59 0.00 1355.27 2393.24 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 27-AUG-17:03 0.00 0.00 0.00 -0.7 0.00 0.00 263.34 535.87 2778.60 1163.02 0.00 1355.27 2497.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 28-AUG-17:05 0.00 0.00 0.00 -0.9 0.00 0.00 263.35 535.87 2749.11 3841.13 0.00 1327.21 2247.46 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 28-AUG-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 2654.97 331.07 0.00 1130.11 2370.13 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 28-AUG-18:04 0.00 0.00 0.00 -0.6 0.00 0.00 427.05 721.37 2654.97 295.99 0.00 1130.11 2464.79 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 01-JUL-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 263.35 535.87 2778.60 4883.92 0.00 1301.34 1194.26 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 28-AUG-17:18 0.00 0.00 0.00 -0.1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1263.65 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 28-AUG-17:08 0.00 0.00 0.00 -12.5 0.00 0.00 4740.19 9645.69 49484.00 32716.79 0.00 22351.47 45977.70 0.00 0.00 0.00 -14440.4 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 07-JAN-05:00 0.00 0.00 6901.02 0.00 0.00 0.00 526.31 164.88 1038.68 0.00 0.00 0.00 0.00 0.00 -1146.5 0.00 -5497.4 -1986.9
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 9235.06 0.00 0.00 0.00 526.31 54.96 1038.39 0.00 0.00 0.00 0.00 0.00 -2699.3 0.00 -6030.7 -2124.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 07-JAN-05:00 0.00 0.00 9248.73 0.00 0.00 0.00 526.31 164.88 1038.68 0.00 0.00 0.00 0.00 0.00 -2871.0 0.00 -5799.3 -2308.3
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 7044.66 0.00 0.00 0.00 526.31 54.96 1038.39 0.00 0.00 0.00 0.00 0.00 -1109.7 0.00 -5677.8 -1876.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 31-JAN-04:00 0.00 0.00 9261.63 0.00 0.00 0.00 526.31 54.96 1038.39 0.00 0.00 0.00 0.00 0.00 -2728.3 0.00 -6030.7 -2122.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 07-JAN-08:15 0.00 0.00 7729.70 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -2335.8 0.00 -4341.4 -3062.9
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 07-JAN-08:15 0.00 0.00 5739.49 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -787.7 0.00 -4060.5 -2901.6
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 07-JAN-06:00 0.00 0.00 7942.40 0.00 0.00 0.00 526.31 343.51 1162.87 0.00 0.00 0.00 0.00 0.00 -2867.9 0.00 -4391.3 -2715.9
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 07-JAN-08:15 0.00 0.00 8046.92 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -2597.7 0.00 -4341.4 -3118.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 07-JAN-08:15 0.00 0.00 5868.42 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -1057.2 0.00 -4060.5 -2761.1
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 07-JAN-06:00 0.00 0.00 7953.56 0.00 0.00 0.00 526.31 343.51 1162.87 0.00 0.00 0.00 0.00 0.00 -2890.2 0.00 -4391.3 -2704.7
LIVING_UNIT3_BACKROW_TOPFLOOR 07-JAN-05:00 0.00 0.00 10581.08 0.00 0.00 0.00 526.31 164.88 1038.68 0.00 0.00 0.00 0.00 0.00 -2851.8 0.00 -5806.5 -3652.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 07-JAN-05:00 0.00 0.00 10565.89 0.00 0.00 0.00 526.31 164.88 1038.68 0.00 0.00 0.00 0.00 0.00 -2826.4 0.00 -5806.5 -3662.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 07-JAN-07:00 0.00 0.00 10549.99 0.00 0.00 0.00 526.31 384.73 1438.48 0.00 0.00 0.00 0.00 0.00 -2885.1 0.00 -5837.5 -4176.9
LIVING_UNIT2_BACKROW_TOPFLOOR 07-JAN-08:15 0.00 0.00 8452.28 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -1051.9 0.00 -5385.8 -4025.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 07-JAN-05:00 0.00 0.00 8335.81 0.00 0.00 0.00 526.31 164.88 1038.68 0.00 0.00 0.00 0.00 0.00 -1146.6 0.00 -5504.2 -3414.9
LIVING_UNIT1_BACKROW_TOPFLOOR 07-JAN-08:15 0.00 0.00 10646.44 0.00 0.00 0.00 215.05 151.14 1644.19 0.00 0.00 0.00 0.00 0.00 -2588.1 0.00 -5667.0 -4401.7
HEATEDBSMT 07-JAN-08:00 0.00 0.00 4294.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -4294.7
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 07-JAN-05:00 0.00 0.00 147653.49 0.00 0.00 0.00 9447.86 2967.90 18696.27 0.00 0.00 0.00 0.00 0.00 -41352.9 0.00 -95412.4 -42000.3



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 791.183 2.00 2.00 1.00 44.9950 791.183 0.057 1.000 44.9950 0.06
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 246.136 2.00 2.00 1.00 44.9950 246.136 0.183 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 281.019 2.00 2.00 1.00 44.9950 281.019 0.160 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 384.004 2.00 2.00 1.00 44.9950 384.004 0.117 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 242.953 2.00 2.00 1.00 44.9950 242.953 0.185 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.050 2.00 2.00 1.00 44.9950 276.050 0.163 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 389.714 2.00 2.00 1.00 44.9950 389.714 0.115 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 248.948 2.00 2.00 1.00 44.9950 248.948 0.181 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 285.017 2.00 2.00 1.00 44.9950 285.017 0.158 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 383.449 2.00 2.00 1.00 44.9950 383.449 0.117 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.828 2.00 2.00 1.00 44.9950 245.828 0.183 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 280.991 2.00 2.00 1.00 44.9950 280.991 0.160 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.063 2.00 2.00 1.00 44.9950 453.063 0.099 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 312.839 2.00 2.00 1.00 44.9950 312.839 0.144 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 348.458 2.00 2.00 1.00 44.9950 348.458 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 453.726 2.00 2.00 1.00 44.9950 453.726 0.099 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 314.942 2.00 2.00 1.00 44.9950 314.942 0.143 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.153 2.00 2.00 1.00 44.9950 350.153 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNITHEATEDBSMT 49.919 0.00 0.00 1.00 44.9950 49.919 0.901 1.000 44.9950 0.90


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 108.951 2.00 2.00 1.00 44.9950 108.951 1.000 1.000 44.9950 0.41
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 147.483 2.00 2.00 1.00 44.9950 147.483 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 147.639 2.00 2.00 1.00 44.9950 147.639 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 111.560 2.00 2.00 1.00 44.9950 111.560 1.000 1.000 44.9950 0.40
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 147.592 2.00 2.00 1.00 44.9950 147.592 1.000 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 127.455 2.00 2.00 1.00 44.9950 127.455 1.000 1.000 44.9950 0.35
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 96.857 2.00 2.00 1.00 44.9950 96.857 1.000 1.000 44.9950 0.46
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 133.977 2.00 2.00 1.00 44.9950 133.977 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 134.059 2.00 2.00 1.00 44.9950 134.059 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 97.446 2.00 2.00 1.00 44.9950 97.446 1.000 1.000 44.9950 0.46
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 134.015 2.00 2.00 1.00 44.9950 134.015 1.000 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 175.243 2.00 2.00 1.00 44.9950 175.243 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 139.174 2.00 2.00 1.00 44.9950 139.174 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 176.095 2.00 2.00 1.00 44.9950 176.095 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 176.203 2.00 2.00 1.00 44.9950 176.203 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 139.376 2.00 2.00 1.00 44.9950 139.376 1.000 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 176.171 2.00 2.00 1.00 44.9950 176.171 1.000 1.000 44.9950 0.26
CENTRAL SYSTEM_UNITHEATEDBSMT 77.330 0.00 0.00 1.00 44.9950 77.330 1.000 1.000 44.9950 0.58


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   791.183 791.1826 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   246.136 246.1360 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   281.019 281.0186 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   384.004 384.0039 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   242.953 242.9532 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   276.050 276.0503 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   389.714 389.7137 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   248.948 248.9483 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   285.017 285.0170 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   383.449 383.4495 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   245.828 245.8279 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   280.991 280.9912 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   350.153 350.1535 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   348.458 348.4582 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   453.063 453.0627 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   314.942 314.9423 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   312.839 312.8393 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   453.726 453.7264 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   49.919 49.9189 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 791.18 791.183 791.18 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 246.14 246.136 246.14 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 281.02 281.019 281.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 384.00 384.004 384.00 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 242.95 242.953 242.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.05 276.050 276.05 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 389.71 389.714 389.71 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 248.95 248.948 248.95 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 285.02 285.017 285.02 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 383.45 383.449 383.45 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.83 245.828 245.83 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 280.99 280.991 280.99 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.06 453.063 453.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 312.84 312.839 312.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 348.46 348.458 348.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 453.73 453.726 453.73 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 314.94 314.942 314.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.15 350.153 350.15 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 49.92 49.919 49.92 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   108.951 108.951 108.951 44.9950 0.413 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   147.483 147.483 147.483 44.9950 0.305 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   147.639 147.639 147.639 44.9950 0.305 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   111.560 111.560 111.560 44.9950 0.403 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   147.592 147.592 147.592 44.9950 0.305 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   127.455 127.455 127.455 44.9950 0.353 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   96.857 96.857 96.857 44.9950 0.465 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   133.977 133.977 133.977 44.9950 0.336 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   134.059 134.059 134.059 44.9950 0.336 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   97.446 97.446 97.446 44.9950 0.462 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   134.015 134.015 134.015 44.9950 0.336 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   176.171 176.171 176.171 44.9950 0.255 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   176.095 176.095 176.095 44.9950 0.256 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   175.243 175.243 175.243 44.9950 0.257 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   139.376 139.376 139.376 44.9950 0.323 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   139.174 139.174 139.174 44.9950 0.323 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   176.203 176.203 176.203 44.9950 0.255 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   77.330 77.330 77.330 44.9950 0.582 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 108.95 108.951 108.95 108.95 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 147.48 147.483 147.48 147.48 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 147.64 147.639 147.64 147.64 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 111.56 111.560 111.56 111.56 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 147.59 147.592 147.59 147.59 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 127.46 127.455 127.46 127.46 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 96.86 96.857 96.86 96.86 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 133.98 133.977 133.98 133.98 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 134.06 134.059 134.06 134.06 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 97.45 97.446 97.45 97.45 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 134.02 134.015 134.02 134.02 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 175.24 175.243 175.24 175.24 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 139.17 139.174 139.17 139.17 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 176.09 176.095 176.09 176.09 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 176.20 176.203 176.20 176.20 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 139.38 139.376 139.38 139.38 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 176.17 176.171 176.17 176.17 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 77.33 77.330 77.33 77.33 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Sec1.1A-General Information

Data
Weather File ANNUAL ** Memphis International Ap TN USA TMY3 WMO#=723340
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 4.25
Number of hours not met 4.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 3805.56 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 614.75 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 1324.54 170190.15 0.00 0.00
Space Cooling 31903.12 14585.71 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 6654.70 2237.96 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 2510.48 148991.42 0.00 0.00
Receptacle Equipment 76678.43 12123.21 1639.73 22311.32 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 130739.04   5474.75   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 261812.16 446397.65
Natural Gas 163973.19 547475.17
Additional 0.00 0.00
Total 425785.36 993872.81


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.00
Space Cooling 0.82
Fans-Interior 0.17
Service Water Heating 0.00
Receptacle Equipment 1.97
Miscellaneous 0.07
Subtotal 3.35


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.99
Service Water Heating 1.89
Miscellaneous 1.23
Subtotal 4.11


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.45
Space Heating 13.33
Space Cooling 10.96
Fans-Interior 2.29
Service Water Heating 25.26
Receptacle Equipment 42.84
Miscellaneous 0.88



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 77.33
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 791.18
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 246.14
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 281.02
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 384.00
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 242.95
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 276.05
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 389.71
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 248.95
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 285.02
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 383.45
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 245.83
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 280.99
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 350.15
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 348.46
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 453.06
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 314.94
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 312.84
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 453.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 791.18
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 246.14
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 281.02
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 384.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 242.95
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.05
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 389.71
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 248.95
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 285.02
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 383.45
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 245.83
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 280.99
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 453.06
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 312.84
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 348.46
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 453.73
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 314.94
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 350.15
CENTRAL SYSTEM_UNITHEATEDBSMT 77.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 791.18 2.00 0.754203
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 246.14 0.800087 0.682269
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 281.02 0.895058 0.687440
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 384.00 1.13 0.707596
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 242.95 0.792983 0.681242
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 276.05 0.879880 0.687252
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 389.71 1.13 0.713639
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 248.95 0.794364 0.686971
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 285.02 0.886345 0.693645
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 383.45 1.11 0.712481
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 245.83 0.787550 0.685950
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 280.99 0.873531 0.693734
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 453.06 1.28 0.719777
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 312.84 0.952388 0.699293
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 348.46 1.04 0.703754
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 453.73 1.28 0.719877
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 314.94 0.957157 0.699751
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 350.15 1.05 0.704081
DX COOLING COIL_UNITHEATEDBSMT 77.33 0.257711 0.676083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 791.18 791.18 791.18 5063.51 2.00 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 246.14 246.14 246.14 8493.80 0.800087 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 281.02 281.02 281.02 10560.53 0.895058 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 384.00 384.00 384.00 10568.91 1.13 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 242.95 242.95 242.95 8633.72 0.792983 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 276.05 276.05 276.05 10566.38 0.879880 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 389.71 389.71 389.71 9486.14 1.13 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 248.95 248.95 248.95 7845.02 0.794364 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 285.02 285.02 285.02 9835.95 0.886345 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 383.45 383.45 383.45 9840.35 1.11 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 245.83 245.83 245.83 7876.59 0.787550 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 280.99 280.99 280.99 9837.97 0.873531 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 453.06 453.06 453.06 12049.51 1.28 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 312.84 312.84 312.84 10114.85 0.952388 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 348.46 348.46 348.46 12095.21 1.04 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 453.73 453.73 453.73 12101.02 1.28 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 314.94 314.94 314.94 10125.68 0.957157 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 350.15 350.15 350.15 12099.30 1.05 1.00
ACANDF_UNITHEATEDBSMT 77.33 77.33 77.33 6797.39 0.257711 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 791.18
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 246.14
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 281.02
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 384.00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 242.95
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 276.05
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 389.71
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 248.95
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 285.02
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 383.45
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 245.83
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 280.99
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 453.06
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 312.84
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 348.46
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 453.73
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 314.94
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 350.15
SUPPLY FAN_UNITHEATEDBSMT 77.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 5063.51
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 8493.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 10560.53
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 10568.91
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 8633.72
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 10566.38
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 9486.14
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 7845.02
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 9835.95
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 9840.35
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 7876.59
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 9837.97
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 12049.51
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 10114.85
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 12095.21
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 12101.02
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 10125.68
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 12099.30
MAIN FUEL HEATING COIL_UNITHEATEDBSMT 6797.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:31:25

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 705.004 54.259 0.000 0.000 54.259
February 668.750 57.280 0.000 0.000 57.280
March 744.000 88.638 0.000 0.000 88.638
April 720.000 102.352 0.000 0.000 102.352
May 744.000 130.847 0.000 0.000 130.847
June 720.000 144.419 0.000 0.000 144.419
July 744.000 159.551 0.000 0.000 159.551
August 744.000 156.055 0.000 0.000 156.055
September 720.000 138.769 0.000 0.000 138.769
October 744.000 108.225 0.000 0.000 108.225
November 720.000 84.034 0.000 0.000 84.034
December 744.000 65.346 0.000 0.000 65.346
           
Annual Sum or Average 8717.754 1289.776 0.000 0.000 1289.776
Minimum of Months 668.750 54.259 0.000 0.000 54.259
Maximum of Months 744.000 159.551 0.000 0.000 159.551



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 65.771 1.088 521.575 14.524 15.611
February 112.519 1.682 405.375 9.538 11.220
March 274.745 5.320 204.675 2.984 8.304
April 473.004 10.592 78.336 0.762 11.355
May 703.965 23.153 0.000 0.000 23.153
June 712.500 33.004 0.000 0.000 33.004
July 744.000 40.283 0.000 0.000 40.283
August 744.000 38.442 0.000 0.000 38.442
September 705.664 30.943 0.000 0.000 30.943
October 514.648 13.599 32.500 0.273 13.872
November 296.739 5.557 213.750 2.711 8.268
December 101.087 1.168 407.636 8.416 9.584
           
Annual Sum or Average 5448.643 204.832 1863.847 39.208 244.040
Minimum of Months 65.771 1.088 0.000 0.000 8.268
Maximum of Months 744.000 40.283 521.575 14.524 40.283



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 53.542 0.871 601.354 19.968 20.839
February 91.323 1.566 442.079 13.300 14.865
March 244.777 5.764 255.542 4.522 10.286
April 466.418 12.649 93.250 1.365 14.015
May 687.880 28.151 0.375 0.000 28.152
June 707.783 40.145 0.000 0.000 40.145
July 744.000 49.194 0.000 0.000 49.194
August 742.250 46.369 0.000 0.000 46.369
September 692.737 36.011 0.000 0.000 36.011
October 495.277 14.242 65.500 0.736 14.978
November 247.551 5.103 274.333 4.678 9.780
December 70.854 0.837 517.417 12.642 13.479
           
Annual Sum or Average 5244.391 240.902 2249.850 57.210 298.113
Minimum of Months 53.542 0.837 0.000 0.000 9.780
Maximum of Months 744.000 49.194 601.354 19.968 49.194



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 31.896 0.379 648.663 31.327 31.706
February 42.229 0.604 497.417 20.576 21.180
March 195.067 4.941 308.854 7.435 12.376
April 405.079 12.274 121.687 2.234 14.508
May 669.918 29.316 1.250 0.002 29.318
June 705.993 43.477 0.000 0.000 43.477
July 744.000 52.963 0.000 0.000 52.963
August 741.875 49.168 0.000 0.000 49.168
September 683.786 35.894 0.000 0.000 35.894
October 418.393 11.389 108.083 1.478 12.868
November 165.563 2.802 341.000 8.101 10.903
December 55.625 0.614 619.050 21.969 22.583
           
Annual Sum or Average 4859.424 243.820 2646.004 93.122 336.942
Minimum of Months 31.896 0.379 0.000 0.000 10.903
Maximum of Months 744.000 52.963 648.663 31.327 52.963



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 32.208 0.376 633.975 18.135 18.511
February 41.458 0.366 478.804 11.475 11.842
March 205.934 3.053 269.944 3.901 6.955
April 433.348 8.709 95.979 0.928 9.637
May 704.211 22.465 0.000 0.000 22.465
June 712.829 32.688 0.000 0.000 32.688
July 744.000 39.692 0.000 0.000 39.692
August 744.000 36.643 0.000 0.000 36.643
September 703.819 27.714 0.000 0.000 27.714
October 428.229 8.791 56.969 0.450 9.241
November 171.122 2.313 293.361 3.920 6.234
December 62.792 0.705 587.125 12.222 12.927
           
Annual Sum or Average 4983.950 183.515 2416.156 51.033 234.548
Minimum of Months 32.208 0.366 0.000 0.000 6.234
Maximum of Months 744.000 39.692 633.975 18.135 39.692



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 22.375 0.275 656.125 22.893 23.168
February 33.229 0.363 496.958 14.667 15.031
March 202.210 3.624 308.913 5.174 8.799
April 444.529 10.761 97.982 1.428 12.189
May 688.723 27.495 0.375 0.000 27.496
June 708.096 39.823 0.000 0.000 39.823
July 744.000 48.610 0.000 0.000 48.610
August 742.250 44.695 0.000 0.000 44.695
September 691.493 32.989 0.000 0.000 32.989
October 433.744 9.542 77.625 0.871 10.412
November 154.643 2.080 339.063 5.651 7.731
December 55.313 0.527 627.725 15.940 16.467
           
Annual Sum or Average 4920.605 220.784 2604.765 66.624 287.408
Minimum of Months 22.375 0.275 0.000 0.000 7.731
Maximum of Months 744.000 48.610 656.125 22.893 48.610



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 69.125 1.438 528.133 23.335 24.773
February 107.696 2.379 414.442 15.779 18.158
March 285.618 8.499 211.563 4.976 13.475
April 474.408 16.250 87.257 1.371 17.621
May 693.264 31.896 0.000 0.000 31.896
June 710.795 45.153 0.000 0.000 45.153
July 744.000 54.772 0.000 0.000 54.772
August 743.875 52.356 0.000 0.000 52.356
September 698.400 40.598 0.000 0.000 40.598
October 493.215 17.449 56.844 0.761 18.209
November 277.566 7.053 238.313 5.021 12.075
December 108.146 1.560 447.275 14.617 16.177
           
Annual Sum or Average 5406.107 279.403 1983.826 65.859 345.262
Minimum of Months 69.125 1.438 0.000 0.000 12.075
Maximum of Months 744.000 54.772 528.133 23.335 54.772



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 76.792 1.353 489.288 12.583 13.936
February 136.819 2.012 376.333 8.409 10.421
March 326.473 6.445 174.646 2.458 8.902
April 514.294 12.462 58.508 0.492 12.953
May 716.812 24.870 0.000 0.000 24.870
June 716.500 34.133 0.000 0.000 34.133
July 744.000 41.205 0.000 0.000 41.205
August 744.000 39.470 0.000 0.000 39.470
September 712.687 32.111 0.000 0.000 32.111
October 538.040 14.637 23.833 0.174 14.811
November 334.729 6.528 185.048 2.146 8.675
December 116.604 1.535 377.150 7.323 8.858
           
Annual Sum or Average 5677.751 216.761 1684.806 33.584 250.345
Minimum of Months 76.792 1.353 0.000 0.000 8.675
Maximum of Months 744.000 41.205 489.288 12.583 41.205



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 63.000 1.081 578.229 18.184 19.265
February 106.341 1.804 421.458 12.240 14.044
March 281.709 6.704 214.607 3.847 10.551
April 502.183 14.537 76.750 1.028 15.565
May 707.542 30.058 0.000 0.000 30.058
June 711.542 41.603 0.000 0.000 41.603
July 744.000 50.558 0.000 0.000 50.558
August 743.750 47.834 0.000 0.000 47.834
September 703.070 37.430 0.000 0.000 37.430
October 512.054 15.258 49.375 0.535 15.794
November 271.652 5.853 248.917 4.005 9.858
December 82.896 1.114 492.083 11.515 12.629
           
Annual Sum or Average 5429.737 253.834 2081.420 51.354 305.188
Minimum of Months 63.000 1.081 0.000 0.000 9.858
Maximum of Months 744.000 50.558 578.229 18.184 50.558



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 40.187 0.508 636.267 28.639 29.148
February 47.625 0.705 479.000 18.855 19.560
March 224.617 5.759 266.879 6.321 12.080
April 444.180 14.067 103.692 1.691 15.757
May 691.860 31.143 0.000 0.000 31.143
June 710.830 44.782 0.000 0.000 44.782
July 744.000 54.111 0.000 0.000 54.111
August 743.750 50.463 0.000 0.000 50.463
September 695.551 37.244 0.000 0.000 37.244
October 437.046 12.230 88.102 1.152 13.382
November 186.533 3.341 316.271 7.072 10.413
December 64.292 0.870 606.708 20.253 21.124
           
Annual Sum or Average 5030.472 255.223 2496.919 83.984 339.207
Minimum of Months 40.187 0.508 0.000 0.000 10.413
Maximum of Months 744.000 54.111 636.267 28.639 54.111



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 38.542 0.536 612.571 15.971 16.507
February 58.646 0.537 446.375 10.111 10.648
March 266.627 4.116 229.321 3.165 7.281
April 483.619 10.614 70.600 0.580 11.194
May 717.802 24.240 0.000 0.000 24.240
June 717.125 33.845 0.000 0.000 33.845
July 744.000 40.646 0.000 0.000 40.646
August 744.000 37.744 0.000 0.000 37.744
September 711.750 28.972 0.000 0.000 28.972
October 449.737 9.755 41.333 0.313 10.068
November 218.693 3.066 255.992 3.195 6.261
December 73.083 1.016 554.525 10.865 11.881
           
Annual Sum or Average 5223.625 195.086 2210.717 44.200 239.286
Minimum of Months 38.542 0.536 0.000 0.000 6.261
Maximum of Months 744.000 40.646 612.571 15.971 40.646



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 29.750 0.396 641.063 21.353 21.749
February 39.358 0.477 481.225 13.676 14.153
March 234.177 4.494 272.108 4.441 8.935
April 482.833 12.667 82.250 1.085 13.752
May 708.482 29.472 0.000 0.000 29.472
June 711.979 41.348 0.000 0.000 41.348
July 744.000 50.059 0.000 0.000 50.059
August 743.750 46.251 0.000 0.000 46.251
September 701.534 34.504 0.000 0.000 34.504
October 451.474 10.459 59.500 0.666 11.125
November 173.433 2.616 314.058 5.008 7.624
December 62.042 0.768 611.125 14.968 15.736
           
Annual Sum or Average 5082.813 233.512 2461.329 61.196 294.708
Minimum of Months 29.750 0.396 0.000 0.000 7.624
Maximum of Months 744.000 50.059 641.063 21.353 50.059



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 47.250 0.978 612.479 34.513 35.490
February 76.283 1.767 475.308 23.514 25.281
March 227.296 7.766 292.372 8.597 16.363
April 426.574 16.305 119.071 2.720 19.025
May 657.567 34.460 2.083 0.008 34.468
June 703.706 51.086 0.000 0.000 51.086
July 744.000 62.632 0.000 0.000 62.632
August 741.500 59.118 0.000 0.000 59.118
September 679.775 44.275 0.750 0.001 44.276
October 446.956 16.741 108.106 1.927 18.668
November 223.633 5.796 308.681 9.027 14.822
December 66.642 0.892 558.613 23.308 24.200
           
Annual Sum or Average 5041.182 301.815 2477.463 103.614 405.429
Minimum of Months 47.250 0.892 0.000 0.000 14.822
Maximum of Months 744.000 62.632 612.479 34.513 62.632



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 58.542 0.946 592.279 21.332 22.278
February 89.733 1.434 445.313 14.273 15.707
March 250.825 5.880 246.175 4.849 10.729
April 454.334 12.774 99.625 1.339 14.112
May 693.346 27.831 0.000 0.000 27.831
June 710.554 40.493 0.000 0.000 40.493
July 744.000 49.523 0.000 0.000 49.523
August 744.000 46.744 0.000 0.000 46.744
September 698.546 36.311 0.000 0.000 36.311
October 480.351 14.256 67.975 0.715 14.970
November 250.819 5.325 261.989 4.747 10.072
December 73.750 1.005 519.938 13.540 14.545
           
Annual Sum or Average 5248.799 242.522 2233.293 60.794 303.316
Minimum of Months 58.542 0.946 0.000 0.000 10.072
Maximum of Months 744.000 49.523 592.279 21.332 49.523



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 47.792 0.722 633.042 27.084 27.806
February 75.141 1.322 467.019 18.069 19.391
March 230.658 6.241 288.833 6.382 12.623
April 456.247 14.701 99.575 1.827 16.528
May 683.527 32.938 1.250 0.003 32.941
June 707.964 47.949 0.000 0.000 47.949
July 744.000 58.889 0.000 0.000 58.889
August 741.875 55.116 0.000 0.000 55.116
September 689.667 41.585 0.250 0.000 41.585
October 464.322 14.783 87.738 1.230 16.013
November 220.373 4.882 299.083 6.793 11.675
December 58.708 0.757 578.688 18.118 18.875
           
Annual Sum or Average 5120.273 279.884 2455.478 79.508 359.392
Minimum of Months 47.792 0.722 0.000 0.000 11.675
Maximum of Months 744.000 58.889 633.042 27.084 58.889



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 28.000 0.359 656.500 38.904 39.263
February 41.958 0.703 509.875 25.859 26.563
March 201.383 6.201 324.042 9.532 15.733
April 408.821 15.293 126.312 2.881 18.174
May 657.858 34.299 2.000 0.008 34.307
June 704.144 51.198 0.000 0.000 51.198
July 744.000 62.646 0.000 0.000 62.646
August 741.562 58.453 0.000 0.000 58.453
September 677.582 42.329 0.833 0.001 42.330
October 403.588 13.091 139.500 2.396 15.487
November 167.004 3.225 361.333 10.859 14.084
December 53.333 0.601 635.813 28.257 28.858
           
Annual Sum or Average 4829.235 288.398 2756.208 118.698 407.096
Minimum of Months 28.000 0.359 0.000 0.000 14.084
Maximum of Months 744.000 62.646 656.500 38.904 62.646



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 30.167 0.389 646.750 25.031 25.420
February 39.229 0.470 490.250 16.178 16.648
March 217.095 4.437 282.107 5.600 10.036
April 438.352 11.866 107.792 1.455 13.321
May 694.827 27.728 0.000 0.000 27.728
June 711.147 40.665 0.000 0.000 40.665
July 744.000 49.612 0.000 0.000 49.612
August 744.000 46.180 0.000 0.000 46.180
September 697.268 34.480 0.000 0.000 34.480
October 415.346 10.717 92.021 1.004 11.721
November 167.018 2.823 328.917 6.139 8.962
December 60.083 0.736 616.750 17.692 18.428
           
Annual Sum or Average 4958.533 230.102 2564.586 73.099 303.201
Minimum of Months 30.167 0.389 0.000 0.000 8.962
Maximum of Months 744.000 49.612 646.750 25.031 49.612



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 20.750 0.282 661.833 30.413 30.695
February 32.146 0.452 514.333 19.797 20.249
March 205.326 4.825 317.104 7.060 11.885
April 443.263 13.769 101.344 1.898 15.667
May 684.163 32.812 1.250 0.003 32.815
June 708.110 48.075 0.000 0.000 48.075
July 744.000 58.933 0.000 0.000 58.933
August 742.000 54.560 0.000 0.000 54.560
September 689.139 39.839 0.250 0.000 39.840
October 407.156 11.232 108.633 1.448 12.680
November 149.704 2.485 364.229 8.097 10.582
December 51.375 0.529 644.125 21.936 22.465
           
Annual Sum or Average 4877.132 267.791 2713.102 90.654 358.445
Minimum of Months 20.750 0.282 0.000 0.000 10.582
Maximum of Months 744.000 58.933 661.833 30.413 58.933



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 9.340 9.340
February 0.000 0.000 672.000 8.047 8.047
March 0.000 0.000 744.000 5.544 5.544
April 0.000 0.000 720.000 2.827 2.827
May 0.000 0.000 2.000 0.003 0.003
June 545.107 2.556 0.000 0.000 2.556
July 742.004 5.400 0.000 0.000 5.400
August 732.483 5.468 0.000 0.000 5.468
September 573.792 2.776 0.000 0.000 2.776
October 9.871 0.009 0.000 0.000 0.009
November 0.000 0.000 706.479 3.367 3.367
December 0.000 0.000 744.000 7.655 7.655
           
Annual Sum or Average 2603.257 16.210 4332.479 36.785 52.995
Minimum of Months 0.000 0.000 0.000 0.000 0.003
Maximum of Months 742.004 5.468 744.000 9.340 9.340



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1785.95 0.00
February 0.00 1298.57 0.00
March 0.00 366.98 0.00
April 0.00 96.87 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 33.52 0.00
November 0.00 344.45 0.00
December 0.00 1034.85 0.00
       
Annual Sum or Average 0.00 409.48 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1785.95 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2673.88 0.00
February 0.00 1971.77 0.00
March 0.00 605.48 0.00
April 0.00 188.94 0.00
May 0.00 0.07 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 98.57 0.00
November 0.00 647.26 0.00
December 0.00 1692.90 0.00
       
Annual Sum or Average 0.00 650.67 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2673.88 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3072.42 0.00
February 0.00 2234.19 0.00
March 0.00 729.18 0.00
April 0.00 226.38 0.00
May 0.00 0.21 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 144.98 0.00
November 0.00 821.03 0.00
December 0.00 2154.60 0.00
       
Annual Sum or Average 0.00 775.68 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3072.42 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2296.49 0.00
February 0.00 1608.81 0.00
March 0.00 494.04 0.00
April 0.00 121.45 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 57.00 0.00
November 0.00 512.99 0.00
December 0.00 1547.66 0.00
       
Annual Sum or Average 0.00 548.85 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2296.49 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3122.45 0.00
February 0.00 2214.90 0.00
March 0.00 705.76 0.00
April 0.00 201.23 0.00
May 0.00 0.07 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 118.75 0.00
November 0.00 796.53 0.00
December 0.00 2174.15 0.00
       
Annual Sum or Average 0.00 771.80 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3122.45 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2024.00 0.00
February 0.00 1515.26 0.00
March 0.00 431.61 0.00
April 0.00 122.86 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 65.99 0.00
November 0.00 450.06 0.00
December 0.00 1267.81 0.00
       
Annual Sum or Average 0.00 485.17 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2024.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1412.96 0.00
February 0.00 1045.39 0.00
March 0.00 275.98 0.00
April 0.00 57.03 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 19.49 0.00
November 0.00 249.06 0.00
December 0.00 822.36 0.00
       
Annual Sum or Average 0.00 320.30 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1412.96 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2236.15 0.00
February 0.00 1666.43 0.00
March 0.00 473.03 0.00
April 0.00 130.62 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 65.84 0.00
November 0.00 508.91 0.00
December 0.00 1416.09 0.00
       
Annual Sum or Average 0.00 536.36 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2236.15 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2618.96 0.00
February 0.00 1908.96 0.00
March 0.00 578.05 0.00
April 0.00 159.76 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 105.35 0.00
November 0.00 668.27 0.00
December 0.00 1852.10 0.00
       
Annual Sum or Average 0.00 652.27 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2618.96 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1823.51 0.00
February 0.00 1278.10 0.00
March 0.00 361.38 0.00
April 0.00 68.44 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 35.76 0.00
November 0.00 376.94 0.00
December 0.00 1240.51 0.00
       
Annual Sum or Average 0.00 428.61 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1823.51 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2663.97 0.00
February 0.00 1889.01 0.00
March 0.00 554.10 0.00
April 0.00 139.87 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 83.10 0.00
November 0.00 645.56 0.00
December 0.00 1867.36 0.00
       
Annual Sum or Average 0.00 648.44 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2663.97 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3270.80 0.00
February 0.00 2467.15 0.00
March 0.00 814.71 0.00
April 0.00 266.38 0.00
May 0.00 0.80 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.11 0.00
October 0.00 182.62 0.00
November 0.00 883.99 0.00
December 0.00 2208.90 0.00
       
Annual Sum or Average 0.00 833.99 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3270.80 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2457.74 0.00
February 0.00 1820.62 0.00
March 0.00 558.64 0.00
April 0.00 159.37 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 82.36 0.00
November 0.00 565.09 0.00
December 0.00 1560.00 0.00
       
Annual Sum or Average 0.00 594.88 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2457.74 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3350.01 0.00
February 0.00 2474.36 0.00
March 0.00 789.43 0.00
April 0.00 233.54 0.00
May 0.00 0.38 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.02 0.00
October 0.00 152.17 0.00
November 0.00 868.22 0.00
December 0.00 2241.03 0.00
       
Annual Sum or Average 0.00 835.23 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3350.01 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3697.30 0.00
February 0.00 2720.90 0.00
March 0.00 905.93 0.00
April 0.00 282.94 0.00
May 0.00 0.77 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.15 0.00
October 0.00 227.68 0.00
November 0.00 1066.43 0.00
December 0.00 2685.45 0.00
       
Annual Sum or Average 0.00 958.09 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3697.30 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2867.73 0.00
February 0.00 2052.09 0.00
March 0.00 641.55 0.00
April 0.00 172.23 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 115.01 0.00
November 0.00 726.72 0.00
December 0.00 2026.94 0.00
       
Annual Sum or Average 0.00 711.27 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2867.73 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3744.82 0.00
February 0.00 2698.77 0.00
March 0.00 869.36 0.00
April 0.00 241.55 0.00
May 0.00 0.36 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.03 0.00
October 0.00 178.34 0.00
November 0.00 1030.22 0.00
December 0.00 2700.98 0.00
       
Annual Sum or Average 0.00 948.02 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3744.82 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2925.65 0.00
February 0.00 2790.67 0.00
March 0.00 1736.69 0.00
April 0.00 915.14 0.00
May 0.00 0.94 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 1089.79 0.00
December 0.00 2397.81 0.00
       
Annual Sum or Average 0.00 978.58 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2925.65 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.47
February 0.00 0.00 0.55
March 0.00 0.00 0.77
April 0.00 0.00 0.91
May 0.00 0.00 1.12
June 0.00 0.00 1.27
July 0.00 0.00 1.34
August 0.00 0.00 1.31
September 0.00 0.00 1.23
October 0.00 0.00 0.93
November 0.00 0.00 0.75
December 0.00 0.00 0.57
       
Annual Sum or Average 0.00 0.00 0.94
Minimum of Months 0.00 0.00 0.47
Maximum of Months 0.00 0.00 1.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.12
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.44
August 0.00 0.00 0.42
September 0.00 0.00 0.35
October 0.00 0.00 0.15
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.14
May 0.00 0.00 0.30
June 0.00 0.00 0.45
July 0.00 0.00 0.53
August 0.00 0.00 0.50
September 0.00 0.00 0.40
October 0.00 0.00 0.15
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.12
May 0.00 0.00 0.29
June 0.00 0.00 0.44
July 0.00 0.00 0.52
August 0.00 0.00 0.48
September 0.00 0.00 0.36
October 0.00 0.00 0.11
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.44
August 0.00 0.00 0.40
September 0.00 0.00 0.32
October 0.00 0.00 0.09
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.04
April 0.00 0.00 0.12
May 0.00 0.00 0.29
June 0.00 0.00 0.44
July 0.00 0.00 0.52
August 0.00 0.00 0.48
September 0.00 0.00 0.37
October 0.00 0.00 0.10
November 0.00 0.00 0.02
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.08
April 0.00 0.00 0.16
May 0.00 0.00 0.30
June 0.00 0.00 0.44
July 0.00 0.00 0.52
August 0.00 0.00 0.50
September 0.00 0.00 0.40
October 0.00 0.00 0.16
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.07
April 0.00 0.00 0.14
May 0.00 0.00 0.27
June 0.00 0.00 0.38
July 0.00 0.00 0.44
August 0.00 0.00 0.42
September 0.00 0.00 0.36
October 0.00 0.00 0.15
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.31
June 0.00 0.00 0.45
July 0.00 0.00 0.53
August 0.00 0.00 0.50
September 0.00 0.00 0.41
October 0.00 0.00 0.16
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.30
June 0.00 0.00 0.44
July 0.00 0.00 0.52
August 0.00 0.00 0.48
September 0.00 0.00 0.37
October 0.00 0.00 0.12
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.04
April 0.00 0.00 0.12
May 0.00 0.00 0.26
June 0.00 0.00 0.38
July 0.00 0.00 0.44
August 0.00 0.00 0.40
September 0.00 0.00 0.32
October 0.00 0.00 0.10
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.13
May 0.00 0.00 0.31
June 0.00 0.00 0.45
July 0.00 0.00 0.52
August 0.00 0.00 0.48
September 0.00 0.00 0.37
October 0.00 0.00 0.11
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.07
April 0.00 0.00 0.15
May 0.00 0.00 0.32
June 0.00 0.00 0.49
July 0.00 0.00 0.58
August 0.00 0.00 0.55
September 0.00 0.00 0.43
October 0.00 0.00 0.15
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.06
April 0.00 0.00 0.13
May 0.00 0.00 0.28
June 0.00 0.00 0.43
July 0.00 0.00 0.50
August 0.00 0.00 0.47
September 0.00 0.00 0.39
October 0.00 0.00 0.14
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.06
April 0.00 0.00 0.15
May 0.00 0.00 0.33
June 0.00 0.00 0.50
July 0.00 0.00 0.59
August 0.00 0.00 0.55
September 0.00 0.00 0.43
October 0.00 0.00 0.14
November 0.00 0.00 0.05
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.24
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.59



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.06
April 0.00 0.00 0.15
May 0.00 0.00 0.32
June 0.00 0.00 0.49
July 0.00 0.00 0.58
August 0.00 0.00 0.54
September 0.00 0.00 0.41
October 0.00 0.00 0.12
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.04
April 0.00 0.00 0.12
May 0.00 0.00 0.28
June 0.00 0.00 0.43
July 0.00 0.00 0.50
August 0.00 0.00 0.47
September 0.00 0.00 0.37
October 0.00 0.00 0.11
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.33
June 0.00 0.00 0.50
July 0.00 0.00 0.59
August 0.00 0.00 0.54
September 0.00 0.00 0.41
October 0.00 0.00 0.11
November 0.00 0.00 0.03
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.59



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.03
July 0.00 0.00 0.05
August 0.00 0.00 0.05
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.01
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36
Maximum of Months 0.00 0.00 1517.45 1126.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:31:25

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1513.57 1126.89
February 0.00 0.00 1517.45 1020.45
March 0.00 0.00 1460.97 1087.73
April 0.00 0.00 1353.84 975.46
May 0.00 0.00 1220.01 908.33
June 0.00 0.00 1102.45 794.33
July 0.00 0.00 1036.24 771.51
August 0.00 0.00 1025.29 763.36
September 0.00 0.00 1088.30 784.13
October 0.00 0.00 1199.46 893.03
November 0.00 0.00 1325.59 955.10
December 0.00 0.00 1447.04 1077.36
         
Annual Sum or Average 0.00 0.00 1272.81 11157.68
Minimum of Months 0.00 0.00 1025.29 763.36