Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37
Tabular Output Report in Format: HTML
Building: MF+CZ3BWH+USA_TX_El.Paso.Intl.AP.722700+oilfurnace+heatedbsmt+IECC_2012
Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2019-02-14 08:37:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 796590.54 | 20.42 | 27.09 |
Net Site Energy | 796590.54 | 20.42 | 27.09 |
Total Source Energy | 1839063.27 | 47.15 | 62.54 |
Net Source Energy | 1839063.27 | 47.15 | 62.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 84067.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 90789.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 24710.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 244179.76 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 468343.31 | 328247.23 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 84067.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 90789.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 24710.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 244179.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 3.93 | 11.16 | 0.00 | 0.00 | 0.00 | 12.85 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 15.93 | 11.16 | 0.00 | 0.00 | 0.00 | 12.85 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.96 | 8.42 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 12.01 | 8.42 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 468343.313 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 468343.313 | 100.00 |
Total On-Site and Utility Electric Sources | 468343.313 | 100.00 |
Total Electricity End Uses | 468343.313 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1207.25 |
Time Setpoint Not Met During Occupied Cooling | 1.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 580.50 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37 |
RunPeriod | ANNUAL |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [ft] | 3891.27 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4894 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 02-JUL-18:15 | 27-DEC-07:15 | - | - | - | 01-JAN-08:30 |
Heating | 0.00 | 111.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 41.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.83 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 117.40 | 225.37 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 111.53 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 41.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 8.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 91129.14 | 0.00 | 0.00 | 0.00 |
Cooling | 287528.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 78259.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 264690.86 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1483243.27 | 355820.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 3.10 | 0.00 | 0.00 | 0.00 |
Cooling | 9.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 50.44 | 12.10 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 3.10 | 0.00 | 0.00 | 0.00 |
Cooling | 9.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 9.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 50.44 | 12.10 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 22.64 | 0.00 | 22.64 | Wetbulb [F] | 433.09 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 100.58 | 23.40 | 64.58 | Wetbulb [F] | 767.75 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.218 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.218 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.218 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.218 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.218 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 358357.96 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23260.60 | 18577.20 | 4683.40 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6668.06 | 5325.48 | 1342.58 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8218.54 | 6563.78 | 1654.76 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10912.58 | 8715.39 | 2197.19 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6601.77 | 5272.54 | 1329.23 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7947.23 | 6347.10 | 1600.13 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10958.32 | 8751.92 | 2206.40 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6727.18 | 5372.70 | 1354.48 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8173.18 | 6527.55 | 1645.63 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10803.40 | 8628.19 | 2175.21 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6668.73 | 5326.01 | 1342.71 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8008.01 | 6395.64 | 1612.37 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12892.01 | 10296.27 | 2595.74 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8678.88 | 6931.43 | 1747.45 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10056.55 | 8031.72 | 2024.83 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12908.64 | 10309.55 | 2599.09 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8727.24 | 6970.05 | 1757.18 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10088.57 | 8057.29 | 2031.28 | 0.80 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 2349.37 | 1715.76 | 633.61 | 0.73 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.8 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.6 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.6 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.6 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.7 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.8 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.0 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.7 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.8 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.2 | 3.39 | 11.56 | 12.26 | 11.99 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 43049.38 | 46130.41 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 13829.78 | 14028.03 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 16560.94 | 17039.82 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 21306.25 | 22266.57 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13713.03 | 13898.84 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 16083.05 | 16512.94 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 21386.26 | 22353.64 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 13933.62 | 14141.64 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 16480.65 | 16950.18 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 21113.41 | 22052.87 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 13830.67 | 14027.87 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 16189.74 | 16629.47 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 24792.88 | 26099.33 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 17371.67 | 17933.30 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 19798.48 | 20605.35 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 24822.17 | 26131.47 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 17456.84 | 18028.29 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 19854.87 | 20667.42 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 5453.41 | 4653.83 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 872.53 | 329.11 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 250.13 | 94.35 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 308.28 | 116.28 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 409.34 | 154.40 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 247.64 | 93.41 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 298.11 | 112.44 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 411.06 | 155.05 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 252.34 | 95.18 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 306.58 | 115.64 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 405.25 | 152.86 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 250.15 | 94.35 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 300.39 | 113.30 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 483.59 | 182.41 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 325.55 | 122.80 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 377.23 | 142.29 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 484.21 | 182.64 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 327.37 | 123.48 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 378.43 | 142.74 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 71.74 | 27.06 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 36.035652 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17777.13 | 17777.13 | 14.81 | 872.526 | 872.526 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 74.98 | 74.98 | 0.00802 | 96.72 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5096.09 | 5096.09 | 4.24 | 250.125 | 250.125 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00819 | 92.33 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6281.15 | 6281.15 | 5.23 | 308.285 | 308.285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 74.98 | 74.98 | 0.00795 | 100.23 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8340.05 | 8340.05 | 6.95 | 409.341 | 409.341 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:15:00 | 74.98 | 74.98 | 0.00802 | 96.72 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5045.43 | 5045.43 | 4.20 | 247.639 | 247.639 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00819 | 92.33 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6073.80 | 6073.80 | 5.06 | 298.108 | 298.108 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:15:00 | 74.98 | 74.98 | 0.00795 | 100.23 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8374.96 | 8374.96 | 6.98 | 411.057 | 411.057 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00809 | 96.13 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5141.25 | 5141.25 | 4.28 | 252.343 | 252.343 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00825 | 91.45 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6246.45 | 6246.45 | 5.20 | 306.583 | 306.583 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00799 | 99.88 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8256.57 | 8256.57 | 6.88 | 405.246 | 405.246 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00809 | 96.13 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5096.58 | 5096.58 | 4.25 | 250.150 | 250.150 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00825 | 91.45 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6120.15 | 6120.15 | 5.10 | 300.388 | 300.388 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00816 | 94.09 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7710.23 | 7710.23 | 6.42 | 378.432 | 378.432 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00811 | 94.09 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7685.78 | 7685.78 | 6.40 | 377.231 | 377.231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00809 | 94.96 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9852.82 | 9852.82 | 8.21 | 483.591 | 483.591 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00806 | 96.13 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6669.81 | 6669.81 | 5.56 | 327.367 | 327.367 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00817 | 91.45 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6632.85 | 6632.85 | 5.52 | 325.553 | 325.553 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00817 | 91.45 | 0.00682 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9865.53 | 9865.53 | 8.22 | 484.215 | 484.215 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00806 | 96.13 | 0.00682 | 44.995 | 0.00 |
HEATEDBSMT | 1371.39 | 1371.39 | 0.18 | 67.310 | 67.310 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00800 | 93.21 | 0.00682 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 22.64 | 0.00281 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4819.58 | 4819.58 | 4.01 | 101.144 | 101.144 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00618 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6638.56 | 6638.56 | 5.53 | 139.315 | 139.315 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6649.00 | 6649.00 | 5.54 | 139.535 | 139.535 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4962.50 | 4962.50 | 4.13 | 104.143 | 104.143 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00621 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6643.13 | 6643.13 | 5.53 | 139.411 | 139.411 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5857.85 | 5857.85 | 4.88 | 122.935 | 122.935 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00659 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4477.67 | 4477.67 | 3.73 | 93.971 | 93.971 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00639 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6212.41 | 6212.41 | 5.17 | 130.376 | 130.376 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00664 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6215.43 | 6215.43 | 5.18 | 130.440 | 130.440 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00665 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4508.00 | 4508.00 | 3.75 | 94.608 | 94.608 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00640 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6211.97 | 6211.97 | 5.17 | 130.367 | 130.367 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00664 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8115.15 | 8115.15 | 6.76 | 170.302 | 170.302 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00666 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8116.35 | 8116.35 | 6.76 | 170.328 | 170.328 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00666 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8068.34 | 8068.34 | 6.72 | 169.320 | 169.320 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00665 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6407.77 | 6407.77 | 5.34 | 134.473 | 134.473 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00648 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6401.70 | 6401.70 | 5.33 | 134.346 | 134.346 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00647 | 22.64 | 0.00281 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8116.38 | 8116.38 | 6.76 | 170.328 | 170.328 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00666 | 22.64 | 0.00281 | 44.995 | 0.00 |
HEATEDBSMT | 3418.10 | 3418.10 | 0.44 | 71.744 | 71.744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 07:30:00 | 72.00 | 72.00 | 0.00800 | 22.64 | 0.00281 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 | 872.53 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 | 250.13 | 101.14 | 101.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 | 308.28 | 139.32 | 139.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 | 409.34 | 139.53 | 139.53 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 | 247.64 | 104.14 | 104.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 | 298.11 | 139.41 | 139.41 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 | 411.06 | 122.94 | 122.94 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 | 252.34 | 93.97 | 93.97 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 | 306.58 | 130.38 | 130.38 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 | 405.25 | 130.44 | 130.44 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 | 250.15 | 94.61 | 94.61 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 | 300.39 | 130.37 | 130.37 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 483.59 | 483.59 | 169.32 | 169.32 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 325.55 | 325.55 | 134.35 | 134.35 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 377.23 | 377.23 | 170.33 | 170.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 484.21 | 484.21 | 170.33 | 170.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 327.37 | 327.37 | 134.47 | 134.47 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 378.43 | 378.43 | 170.30 | 170.30 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 67.31 | 67.31 | 71.74 | 71.74 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1573.00 | 4306.50 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2417.25 | 4721.50 | 317.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2733.75 | 4494.75 | 281.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2791.00 | 5076.00 | 478.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2266.25 | 5189.50 | 333.25 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2602.50 | 4947.50 | 290.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2891.50 | 4310.25 | 261.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2545.75 | 4417.25 | 224.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2851.00 | 4286.00 | 217.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2850.50 | 4868.50 | 365.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2392.50 | 4900.25 | 243.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2707.25 | 4720.00 | 234.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 2906.25 | 4781.00 | 267.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2977.50 | 4478.50 | 250.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 2986.00 | 4582.25 | 313.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2628.75 | 4981.00 | 279.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2694.50 | 4659.75 | 271.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 2942.00 | 4909.75 | 359.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3466.25 | 5545.50 | 580.50 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 190.25 | 0.00 | 190.25 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 492.75 | 1.00 | 492.75 | 1.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 42.25 | 0.00 | 42.25 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 82.00 | 0.00 | 82.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 43.00 | 0.00 | 43.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 196.50 | 0.00 | 196.50 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 502.00 | 0.00 | 502.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 19.75 | 0.00 | 19.75 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 115.75 | 0.00 | 115.75 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 52.75 | 0.00 | 52.75 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 115.00 | 0.00 | 115.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 114.75 | 0.00 | 114.75 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 13.50 | 0.00 | 13.50 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.25 | 0.00 | 1.25 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 386.50 | 0.00 | 386.50 | 0.00 |
HEATEDBSMT | 656.25 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1782.25 | 1.00 | 1207.25 | 1.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.108 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.093 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.047 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.034 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.046 | 0.000 | 0.270 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.093 | 0.000 | 0.270 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.270 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.270 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Fans:Electricity | 7237.24 | 114.09 | 30-SEP-05:00 | 2495.23 | 26-JUL-17:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
ElectricityPurchased:Plant | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
Cogeneration:ElectricityPurchased | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
ElectricityNet:Plant | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
Cogeneration:ElectricityNet | 137166.40 | 7353.81 | 27-OCT-03:15 | 34384.65 | 02-JUL-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 33827.14 | 489.65 | 16-MAR-06:00 | 14872.89 | 14-JUN-17:30 |
General:Fans:Electricity | 7237.24 | 114.09 | 30-SEP-05:00 | 2495.23 | 26-JUL-17:30 |
Cooling:Electricity | 26589.90 | 102.91 | 27-DEC-07:15 | 12410.72 | 14-JUN-17:30 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 3282.47 | 0.00 | 01-JAN-17:15 | 225209.19 | 27-DEC-07:15 |
Gas:Plant | 3282.47 | 0.00 | 01-JAN-17:15 | 225209.19 | 27-DEC-07:15 |
WaterSystems:Gas | 2441.80 | 0.00 | 01-JAN-00:15 | 114306.16 | 29-JAN-08:15 |
Water Heater:WaterSystems:Gas | 2441.80 | 0.00 | 01-JAN-00:15 | 114306.16 | 29-JAN-08:15 |
Heating:Gas | 840.67 | 0.00 | 01-JAN-17:15 | 111455.10 | 27-DEC-07:15 |
Boiler:Heating:Gas | 840.67 | 0.00 | 01-JAN-17:15 | 111455.10 | 27-DEC-07:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
Water:Plant | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
WaterSystems:Water | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
MainsWater:Plant | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 12-JUN-02:30 | 0.18 | 01-JAN-08:30 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 183793.37 | 872.90 | 31-JUL-03:00 | 119602.96 | 27-DEC-07:15 |
PlantLoopHeatingDemand:Plant | 117199.64 | 872.90 | 31-JUL-03:00 | 33215.85 | 29-JAN-09:00 |
WaterSystems:PlantLoopHeatingDemand | 117199.64 | 872.90 | 31-JUL-03:00 | 33215.85 | 29-JAN-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1039129.87 | 16177.24 | 22-APR-04:00 | 313313.25 | 26-JUL-18:15 |
EnergyTransfer:Building | 402340.95 | 6704.28 | 16-MAR-06:00 | 143802.83 | 15-JUN-18:15 |
EnergyTransfer:Zone:HEATEDBSMT | 7943.27 | 0.00 | 01-APR-16:45 | 4196.52 | 14-FEB-23:45 |
Heating:EnergyTransfer | 70666.36 | 0.00 | 01-APR-16:45 | 91666.15 | 27-DEC-07:15 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 5993.53 | 0.00 | 01-APR-16:45 | 4196.52 | 14-FEB-23:45 |
Cooling:EnergyTransfer | 331674.60 | 1985.18 | 27-DEC-07:15 | 143802.83 | 15-JUN-18:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 1949.75 | 0.00 | 01-JAN-00:15 | 1343.22 | 15-JUN-19:00 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87260.69 | 1985.18 | 27-DEC-07:15 | 18529.53 | 15-JUN-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87260.69 | 1985.18 | 27-DEC-07:15 | 18529.53 | 15-JUN-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14036.70 | 0.00 | 01-JAN-00:15 | 5482.22 | 14-JUN-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1989.01 | 0.00 | 01-JAN-00:15 | 3836.57 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12047.69 | 0.00 | 01-JAN-00:15 | 5482.22 | 14-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 18729.29 | 0.00 | 01-JAN-09:45 | 6567.67 | 15-JUN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 3288.90 | 0.00 | 01-JAN-09:45 | 5510.86 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15440.39 | 0.00 | 01-JAN-00:15 | 6567.67 | 15-JUN-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 18320.88 | 0.00 | 01-JAN-14:30 | 9128.58 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4776.83 | 0.00 | 01-JAN-14:30 | 5604.53 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13544.05 | 0.00 | 01-JAN-00:15 | 9128.58 | 15-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13505.12 | 0.00 | 01-JAN-17:15 | 5502.90 | 05-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3559.46 | 0.00 | 01-JAN-17:15 | 4056.43 | 27-DEC-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9945.66 | 0.00 | 01-JAN-00:15 | 5502.90 | 05-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 18128.89 | 0.00 | 01-JAN-18:15 | 6624.77 | 15-JUN-10:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4756.81 | 0.00 | 01-JAN-18:15 | 5628.86 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13372.08 | 0.00 | 01-JAN-00:15 | 6624.77 | 15-JUN-10:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 19117.28 | 0.00 | 01-JAN-00:15 | 9156.31 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2589.22 | 0.00 | 01-JAN-00:15 | 4722.89 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16528.06 | 0.00 | 01-JAN-00:15 | 9156.31 | 15-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 14198.90 | 0.00 | 01-JAN-00:15 | 5357.86 | 05-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1488.93 | 0.00 | 01-JAN-00:15 | 3467.22 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12709.97 | 0.00 | 01-JAN-00:15 | 5357.86 | 05-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 18718.03 | 0.00 | 01-JAN-00:15 | 6473.94 | 02-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2603.03 | 0.00 | 01-JAN-00:15 | 5066.91 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16115.00 | 0.00 | 01-JAN-00:15 | 6473.94 | 02-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 18107.38 | 0.00 | 01-JAN-14:30 | 9048.27 | 15-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4000.84 | 0.00 | 01-JAN-14:30 | 5093.23 | 27-DEC-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 14106.54 | 0.00 | 01-JAN-00:15 | 9048.27 | 15-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13362.00 | 0.00 | 01-JAN-16:45 | 5432.45 | 14-JUN-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2798.84 | 0.00 | 01-JAN-16:45 | 3640.73 | 27-DEC-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10563.16 | 0.00 | 01-JAN-00:15 | 5432.45 | 14-JUN-18:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17992.96 | 0.00 | 01-JAN-17:15 | 6517.23 | 14-JUN-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 3965.68 | 0.00 | 01-JAN-17:15 | 5112.63 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14027.28 | 0.00 | 01-JAN-00:15 | 6517.23 | 14-JUN-18:15 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 21950.34 | 0.00 | 01-JAN-17:15 | 8236.04 | 02-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5878.92 | 0.00 | 01-JAN-17:15 | 6832.73 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 16071.42 | 0.00 | 01-JAN-00:15 | 8236.04 | 02-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 21705.74 | 0.00 | 01-JAN-10:45 | 8193.93 | 02-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4417.14 | 0.00 | 01-JAN-10:45 | 6727.68 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 17288.60 | 0.00 | 01-JAN-00:15 | 8193.93 | 02-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 22411.18 | 0.00 | 01-JAN-11:30 | 10705.94 | 15-JUN-17:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4740.08 | 0.00 | 01-JAN-11:30 | 6673.91 | 27-DEC-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 17671.10 | 0.00 | 01-JAN-00:15 | 10705.94 | 15-JUN-17:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 17352.98 | 0.00 | 01-JAN-16:15 | 7181.11 | 05-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4607.42 | 0.00 | 01-JAN-16:15 | 5266.83 | 27-DEC-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 12745.56 | 0.00 | 01-JAN-00:15 | 7181.11 | 05-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 17100.75 | 0.00 | 01-JAN-00:15 | 7083.05 | 05-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 3117.43 | 0.00 | 01-JAN-00:15 | 5136.26 | 27-DEC-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 13983.32 | 0.00 | 01-JAN-00:15 | 7083.05 | 05-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 22398.57 | 0.00 | 01-JAN-14:45 | 10782.99 | 15-JUN-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 6094.29 | 0.00 | 01-JAN-14:45 | 6797.60 | 03-FEB-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 16304.27 | 0.00 | 01-JAN-00:15 | 10782.99 | 15-JUN-18:15 |
EnergyTransfer:Plant | 184453.62 | 872.90 | 31-JUL-03:00 | 119588.98 | 27-DEC-07:15 |
WaterSystems:EnergyTransfer | 117199.64 | 872.90 | 31-JUL-03:00 | 33215.85 | 29-JAN-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 117199.64 | 872.90 | 31-JUL-03:00 | 33215.85 | 29-JAN-09:00 |
EnergyTransfer:HVAC | 452335.29 | 6723.34 | 22-APR-06:45 | 162576.22 | 26-JUL-18:15 |
HeatingCoils:EnergyTransfer | 66593.73 | 0.00 | 01-JAN-17:15 | 89178.06 | 27-DEC-07:15 |
PlantLoopHeatingDemand:HVAC | 66593.73 | 0.00 | 01-JAN-17:15 | 89178.06 | 27-DEC-07:15 |
HeatingCoils:PlantLoopHeatingDemand | 66593.73 | 0.00 | 01-JAN-17:15 | 89178.06 | 27-DEC-07:15 |
CoolingCoils:EnergyTransfer | 385741.57 | 2089.88 | 27-DEC-07:15 | 162576.22 | 26-JUL-18:15 |
Boilers:EnergyTransfer | 67253.98 | 0.00 | 01-JAN-17:15 | 89164.08 | 27-DEC-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -7266.86 | 0.000 | 0.000 | 2873.553 | 2456.001 | 10405.511 | 9228.485 | 0.000 | 1338.566 | 72594.258 | 0.000 | -4274.61 | 0.000 | -7361.17 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1988.986 | -1003.30 | 0.000 | 0.000 | 2957.319 | 2456.001 | 10405.511 | 3975.456 | 0.000 | 1291.851 | 0.170 | 0.000 | -1657.58 | 0.000 | -6637.37 | -2732.52 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 3288.864 | -1285.84 | 0.000 | 0.000 | 2975.670 | 2456.001 | 10405.511 | 9299.824 | 0.000 | 1338.509 | 0.029 | 0.000 | -3935.59 | 0.000 | -6823.34 | -3565.11 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4776.791 | -1127.91 | 0.000 | 0.000 | 2996.425 | 2456.001 | 10405.511 | 6733.144 | 0.000 | 1338.634 | 0.014 | 0.000 | -4218.99 | 0.000 | -6603.69 | -4339.84 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 3559.426 | -828.25 | 0.000 | 0.000 | 2986.711 | 2456.001 | 10405.511 | 1233.072 | 0.000 | 1291.987 | 0.000 | 0.000 | -1761.91 | 0.000 | -6436.10 | -3789.03 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 4756.767 | -1113.59 | 0.000 | 0.000 | 2995.555 | 2456.001 | 10405.511 | 6584.767 | 0.000 | 1338.508 | 0.000 | 0.000 | -3950.00 | 0.000 | -6669.01 | -4546.05 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2589.187 | -1376.41 | 0.000 | 0.000 | 2960.186 | 2456.001 | 10405.511 | 9287.276 | 0.000 | 1115.116 | 0.144 | 0.000 | -4178.72 | 0.000 | -5720.73 | -2385.84 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 1488.910 | -1058.46 | 0.000 | 0.000 | 2946.307 | 2456.001 | 10405.511 | 3968.526 | 0.000 | 1068.626 | 0.191 | 0.000 | -1678.68 | 0.000 | -5523.75 | -2421.49 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 2603.005 | -1342.02 | 0.000 | 0.000 | 2966.197 | 2456.001 | 10405.511 | 9278.094 | 0.000 | 1115.114 | 0.170 | 0.000 | -3990.99 | 0.000 | -5718.89 | -2999.08 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 4000.801 | -1174.76 | 0.000 | 0.000 | 2987.812 | 2456.001 | 10405.511 | 6727.043 | 0.000 | 1115.340 | 0.059 | 0.000 | -4275.59 | 0.000 | -5542.23 | -3768.19 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 2798.818 | -879.68 | 0.000 | 0.000 | 2977.067 | 2456.001 | 10405.511 | 1236.138 | 0.000 | 1068.775 | 0.009 | 0.000 | -1783.36 | 0.000 | -5363.24 | -3232.54 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 3965.647 | -1168.16 | 0.000 | 0.000 | 2988.318 | 2456.001 | 10405.511 | 6570.965 | 0.000 | 1115.114 | 0.000 | 0.000 | -3996.59 | 0.000 | -5588.39 | -3889.30 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 5878.868 | -1338.39 | 0.000 | 0.000 | 2993.175 | 2456.001 | 10405.511 | 6559.818 | 0.000 | 1329.361 | 0.000 | 0.000 | -3999.34 | 0.000 | -6692.54 | -2859.45 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4417.097 | -1439.75 | 0.000 | 0.000 | 2978.312 | 2456.001 | 10405.511 | 9289.199 | 0.000 | 1329.339 | 0.059 | 0.000 | -3964.28 | 0.000 | -6802.13 | -2820.49 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 4740.031 | -1471.60 | 0.000 | 0.000 | 2975.990 | 2456.001 | 10405.511 | 9309.602 | 0.000 | 1329.495 | 0.057 | 0.000 | -4127.34 | 0.000 | -6784.73 | -2633.55 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 4607.375 | -1061.42 | 0.000 | 0.000 | 2984.932 | 2456.001 | 10405.511 | 1228.844 | 0.000 | 1283.341 | 0.355 | 0.000 | -1777.14 | 0.000 | -6463.34 | -1979.96 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 3117.399 | -1164.50 | 0.000 | 0.000 | 2964.524 | 2456.001 | 10405.511 | 3972.562 | 0.000 | 1283.093 | 0.050 | 0.000 | -1660.98 | 0.000 | -6595.89 | -1958.92 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 6094.242 | -1357.78 | 0.000 | 0.000 | 2993.028 | 2456.001 | 10405.511 | 6697.976 | 0.000 | 1329.885 | 0.012 | 0.000 | -4263.77 | 0.000 | -6650.16 | -2758.52 |
HEATEDBSMT | 0.000 | 0.000 | 5993.527 | -162.37 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -4043.78 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5451.399 | 54082.028 | 0.000 | 0.000 | 0.000 | -59533.43 | -0.29 |
Total Facility | 0.000 | 0.000 | 70665.742 | -27621.03 | 0.000 | 0.000 | 53501.078 | 44208.020 | 187299.191 | 111180.790 | 0.000 | 27872.054 | 126677.607 | 0.000 | -59495.45 | 0.000 | -173510.13 | -56723.96 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15-JUN-16:41 | 0.00 | 0.00 | 0.00 | -1.6 | 0.00 | 0.00 | 140.43 | 384.73 | 1343.91 | 6008.84 | 0.00 | 1628.97 | 9139.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 476.52 | 0.00 | 1425.81 | 719.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 15-JUN-09:48 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.16 | 103.05 | 1084.61 | 3915.26 | 0.00 | 1257.77 | 92.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 15-JUN-18:30 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 421.84 | 721.37 | 1713.78 | 3828.91 | 0.00 | 1225.75 | 1224.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 05-JUN-18:48 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.02 | 721.37 | 1713.78 | 492.57 | 0.00 | 1371.54 | 776.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 15-JUN-09:48 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.16 | 103.05 | 1084.61 | 3871.14 | 0.00 | 1257.79 | 193.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 426.75 | 721.37 | 1713.78 | 3926.13 | 0.00 | 1047.07 | 1324.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 05-JUN-18:51 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 378.37 | 0.00 | 1057.82 | 1059.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 02-JUL-18:02 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.02 | 721.37 | 1735.60 | 1166.01 | 0.00 | 1086.06 | 1338.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 15-JUN-18:36 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.78 | 721.37 | 1713.78 | 3126.48 | 0.00 | 976.67 | 2095.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14-JUN-18:36 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 547.85 | 0.00 | 1059.48 | 963.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14-JUN-18:02 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 1382.70 | 0.00 | 1180.64 | 1093.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 02-JUL-18:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 425.92 | 721.37 | 1735.60 | 1283.78 | 0.00 | 1294.13 | 2783.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 02-JUL-18:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 427.02 | 721.37 | 1735.60 | 1134.28 | 0.00 | 1350.48 | 2828.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 15-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 3896.34 | 0.00 | 1287.71 | 2720.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 05-JUN-18:54 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 486.89 | 0.00 | 1367.74 | 2464.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 05-JUN-18:51 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.01 | 721.37 | 1713.78 | 366.20 | 0.00 | 1367.74 | 2486.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 15-JUN-18:18 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 426.30 | 721.37 | 1713.78 | 3809.85 | 0.00 | 1230.26 | 2893.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 15-JUN-18:53 | 0.00 | 0.00 | 0.00 | -0.1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-JUN-18:03 | 0.00 | 0.00 | 0.00 | -12.0 | 0.00 | 0.00 | 7676.61 | 12984.58 | 30848.11 | 34972.75 | 0.00 | 21433.41 | 44075.03 | 0.00 | 0.00 | 0.00 | -8116.6 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 27-DEC-07:15 | 0.00 | 0.00 | 3836.57 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.5 | 0.00 | -3140.6 | -1846.6 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-JAN-23:08 | 0.00 | 0.00 | 11032.10 | 0.00 | 0.00 | 0.00 | 553.82 | 137.40 | 1146.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1831.2 | 0.00 | -2496.5 | -8542.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21-NOV-10:30 | 0.00 | 0.00 | 16689.88 | 0.00 | 0.00 | 0.00 | 137.48 | 103.05 | 1079.31 | 58.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -890.8 | -17177.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 27-JAN-17:09 | 0.00 | 0.00 | 10763.19 | 0.00 | 0.00 | 0.00 | 302.59 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -433.6 | 0.00 | -1282.3 | -11542.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25-OCT-02:55 | 0.00 | 0.00 | 5846.31 | 0.00 | 0.00 | 0.00 | 544.35 | 54.96 | 865.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1313.8 | 0.00 | -1619.2 | -4378.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 27-DEC-07:15 | 0.00 | 0.00 | 4722.88 | 0.00 | 0.00 | 0.00 | 464.79 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2145.8 | 0.00 | -2677.0 | -1913.2 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 27-DEC-07:15 | 0.00 | 0.00 | 3467.22 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -868.5 | 0.00 | -2551.3 | -2060.5 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 03-FEB-00:08 | 0.00 | 0.00 | 10949.62 | 0.00 | 0.00 | 0.00 | 555.53 | 54.96 | 960.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1863.5 | 0.00 | -2147.1 | -8510.3 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21-NOV-10:56 | 0.00 | 0.00 | 16421.02 | 0.00 | 0.00 | 0.00 | 135.97 | 103.05 | 1079.31 | 165.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -693.2 | -17211.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 02-FEB-17:39 | 0.00 | 0.00 | 7487.82 | 0.00 | 0.00 | 0.00 | 298.45 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -476.0 | 0.00 | -1133.3 | -8369.2 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11-APR-01:50 | 0.00 | 0.00 | 6052.97 | 0.00 | 0.00 | 0.00 | 547.21 | 54.96 | 890.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1485.2 | 0.00 | -1847.1 | -4213.1 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 03-FEB-07:00 | 0.00 | 0.00 | 6832.80 | 0.00 | 0.00 | 0.00 | 526.30 | 384.73 | 1074.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2222.4 | 0.00 | -3419.2 | -3176.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-JAN-22:40 | 0.00 | 0.00 | 7255.61 | 0.00 | 0.00 | 0.00 | 547.19 | 336.64 | 1334.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1781.9 | 0.00 | -2370.5 | -5321.1 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 17-MAR-08:15 | 0.00 | 0.00 | 16858.05 | 0.00 | 0.00 | 0.00 | 226.91 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -317.5 | 0.00 | -2015.5 | -16049.0 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 01-MAR-17:33 | 0.00 | 0.00 | 8219.32 | 0.00 | 0.00 | 0.00 | 301.48 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -510.0 | 0.00 | -1920.0 | -8283.0 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 27-DEC-07:15 | 0.00 | 0.00 | 5136.26 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -861.2 | 0.00 | -3145.4 | -3142.8 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 28-MAR-08:02 | 0.00 | 0.00 | 13425.52 | 0.00 | 0.00 | 0.00 | 222.06 | 151.14 | 1145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -222.0 | 0.00 | -1219.1 | -13503.5 |
HEATEDBSMT | 14-FEB-23:38 | 0.00 | 0.00 | 4206.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4206.3 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-DEC-07:15 | -1985.2 | 0.17 | 91666.07 | -0.2 | 0.00 | 0.00 | 8321.71 | 6183.13 | 21687.53 | 0.00 | 0.00 | 1610.97 | 0.00 | 0.00 | -30794.2 | 0.00 | -54767.3 | -41922.7 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 872.526 | 2.00 | 2.00 | 1.00 | 44.9950 | 872.526 | 0.052 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 250.125 | 2.00 | 2.00 | 1.00 | 44.9950 | 250.125 | 0.180 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.285 | 2.00 | 2.00 | 1.00 | 44.9950 | 308.285 | 0.146 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 409.341 | 2.00 | 2.00 | 1.00 | 44.9950 | 409.341 | 0.110 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 247.639 | 2.00 | 2.00 | 1.00 | 44.9950 | 247.639 | 0.182 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 298.108 | 2.00 | 2.00 | 1.00 | 44.9950 | 298.108 | 0.151 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 411.057 | 2.00 | 2.00 | 1.00 | 44.9950 | 411.057 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 252.343 | 2.00 | 2.00 | 1.00 | 44.9950 | 252.343 | 0.178 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 306.583 | 2.00 | 2.00 | 1.00 | 44.9950 | 306.583 | 0.147 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 405.246 | 2.00 | 2.00 | 1.00 | 44.9950 | 405.246 | 0.111 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 250.150 | 2.00 | 2.00 | 1.00 | 44.9950 | 250.150 | 0.180 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 300.388 | 2.00 | 2.00 | 1.00 | 44.9950 | 300.388 | 0.150 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 483.591 | 2.00 | 2.00 | 1.00 | 44.9950 | 483.591 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 325.553 | 2.00 | 2.00 | 1.00 | 44.9950 | 325.553 | 0.138 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 377.231 | 2.00 | 2.00 | 1.00 | 44.9950 | 377.231 | 0.119 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 484.215 | 2.00 | 2.00 | 1.00 | 44.9950 | 484.215 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 327.367 | 2.00 | 2.00 | 1.00 | 44.9950 | 327.367 | 0.137 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 378.432 | 2.00 | 2.00 | 1.00 | 44.9950 | 378.432 | 0.119 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 67.310 | 0.00 | 0.00 | 1.00 | 44.9950 | 67.310 | 0.668 | 1.000 | 44.9950 | 0.67 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 101.144 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.144 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 139.315 | 2.00 | 2.00 | 1.00 | 44.9950 | 139.315 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 139.535 | 2.00 | 2.00 | 1.00 | 44.9950 | 139.535 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 104.143 | 2.00 | 2.00 | 1.00 | 44.9950 | 104.143 | 1.000 | 1.000 | 44.9950 | 0.43 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 139.411 | 2.00 | 2.00 | 1.00 | 44.9950 | 139.411 | 1.000 | 1.000 | 44.9950 | 0.32 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 122.935 | 2.00 | 2.00 | 1.00 | 44.9950 | 122.935 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 93.971 | 2.00 | 2.00 | 1.00 | 44.9950 | 93.971 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 130.376 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.376 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 130.440 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.440 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 94.608 | 2.00 | 2.00 | 1.00 | 44.9950 | 94.608 | 1.000 | 1.000 | 44.9950 | 0.48 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 130.367 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.367 | 1.000 | 1.000 | 44.9950 | 0.35 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 169.320 | 2.00 | 2.00 | 1.00 | 44.9950 | 169.320 | 1.000 | 1.000 | 44.9950 | 0.27 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 134.346 | 2.00 | 2.00 | 1.00 | 44.9950 | 134.346 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 170.328 | 2.00 | 2.00 | 1.00 | 44.9950 | 170.328 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 170.328 | 2.00 | 2.00 | 1.00 | 44.9950 | 170.328 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 134.473 | 2.00 | 2.00 | 1.00 | 44.9950 | 134.473 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 170.302 | 2.00 | 2.00 | 1.00 | 44.9950 | 170.302 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.744 | 0.00 | 0.00 | 1.00 | 44.9950 | 71.744 | 1.000 | 1.000 | 44.9950 | 0.63 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 872.526 | 872.5265 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 250.125 | 250.1250 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.285 | 308.2850 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 409.341 | 409.3411 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 247.639 | 247.6386 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 298.108 | 298.1080 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 411.057 | 411.0565 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 252.343 | 252.3427 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 306.583 | 306.5834 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 405.246 | 405.2456 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 250.150 | 250.1502 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 300.388 | 300.3880 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 378.432 | 378.4315 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 377.231 | 377.2306 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 483.591 | 483.5911 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 327.367 | 327.3667 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 325.553 | 325.5529 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 484.215 | 484.2149 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 67.310 | 67.3096 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 | 872.526 | 872.53 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 | 250.125 | 250.13 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 | 308.285 | 308.28 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 | 409.341 | 409.34 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 | 247.639 | 247.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 | 298.108 | 298.11 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 | 411.057 | 411.06 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 | 252.343 | 252.34 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 | 306.583 | 306.58 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 | 405.246 | 405.25 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 | 250.150 | 250.15 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 | 300.388 | 300.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 483.59 | 483.591 | 483.59 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 325.55 | 325.553 | 325.55 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 377.23 | 377.231 | 377.23 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 484.21 | 484.215 | 484.21 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 327.37 | 327.367 | 327.37 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 378.43 | 378.432 | 378.43 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 67.31 | 67.310 | 67.31 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 101.144 | 101.144 | 101.144 | 44.9950 | 0.445 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 139.315 | 139.315 | 139.315 | 44.9950 | 0.323 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 139.535 | 139.535 | 139.535 | 44.9950 | 0.322 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 104.143 | 104.143 | 104.143 | 44.9950 | 0.432 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 139.411 | 139.411 | 139.411 | 44.9950 | 0.323 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 122.935 | 122.935 | 122.935 | 44.9950 | 0.366 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 93.971 | 93.971 | 93.971 | 44.9950 | 0.479 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 130.376 | 130.376 | 130.376 | 44.9950 | 0.345 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 130.440 | 130.440 | 130.440 | 44.9950 | 0.345 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 94.608 | 94.608 | 94.608 | 44.9950 | 0.476 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 130.367 | 130.367 | 130.367 | 44.9950 | 0.345 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 170.302 | 170.302 | 170.302 | 44.9950 | 0.264 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 170.328 | 170.328 | 170.328 | 44.9950 | 0.264 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 169.320 | 169.320 | 169.320 | 44.9950 | 0.266 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 134.473 | 134.473 | 134.473 | 44.9950 | 0.335 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 134.346 | 134.346 | 134.346 | 44.9950 | 0.335 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 170.328 | 170.328 | 170.328 | 44.9950 | 0.264 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 71.744 | 71.744 | 71.744 | 44.9950 | 0.627 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 101.14 | 101.144 | 101.14 | 101.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 139.32 | 139.315 | 139.32 | 139.32 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 139.53 | 139.535 | 139.53 | 139.53 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 104.14 | 104.143 | 104.14 | 104.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 139.41 | 139.411 | 139.41 | 139.41 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 122.94 | 122.935 | 122.94 | 122.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 93.97 | 93.971 | 93.97 | 93.97 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 130.38 | 130.376 | 130.38 | 130.38 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 130.44 | 130.440 | 130.44 | 130.44 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 94.61 | 94.608 | 94.61 | 94.61 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 130.37 | 130.367 | 130.37 | 130.37 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 169.32 | 169.320 | 169.32 | 169.32 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 134.35 | 134.346 | 134.35 | 134.35 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 170.33 | 170.328 | 170.33 | 170.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 170.33 | 170.328 | 170.33 | 170.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 134.47 | 134.473 | 134.47 | 134.47 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 170.30 | 170.302 | 170.30 | 170.30 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.74 | 71.744 | 71.74 | 71.74 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 1207.25 |
Number of hours cooling loads not met | 1.00 |
Number of hours not met | 1208.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 840.67 | 111455.10 | 0.00 | 0.00 |
Space Cooling | 26589.90 | 12120.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 7237.24 | 2447.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2441.80 | 113754.10 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 15395.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 137166.40 | 3282.47 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 468343.31 |
Natural Gas | 0.00 | 328247.23 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 796590.54 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.68 |
Fans-Interior | 0.19 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 3.52 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.63 |
Service Water Heating | 1.83 |
Miscellaneous | -0.0 |
Subtotal | 2.46 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.55 |
Space Heating | 10.55 |
Space Cooling | 11.40 |
Fans-Interior | 3.10 |
Service Water Heating | 30.65 |
Receptacle Equipment | 37.65 |
Miscellaneous | 1.10 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 71.74 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 378.43 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 377.23 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 483.59 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 327.37 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 325.55 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 484.21 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 483.59 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 325.55 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 377.23 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 484.21 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 327.37 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 378.43 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 71.74 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 | 1.94 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 | 0.555671 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 | 0.684878 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 | 0.909382 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 | 0.550148 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 | 0.662269 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 | 0.913193 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 | 0.560598 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 | 0.681098 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 | 0.900283 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 | 0.555727 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 | 0.667334 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 483.59 | 1.07 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 325.55 | 0.723240 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 377.23 | 0.838046 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 484.21 | 1.08 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 327.37 | 0.727270 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 378.43 | 0.840714 | 0.798655 |
DX COOLING COIL_UNITHEATEDBSMT | 71.74 | 0.195781 | 0.730308 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 | 872.53 | 872.53 | 1.94 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 | 250.13 | 250.13 | 0.555671 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 | 308.28 | 308.28 | 0.684878 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 | 409.34 | 409.34 | 0.909382 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 | 247.64 | 247.64 | 0.550148 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 | 298.11 | 298.11 | 0.662269 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 | 411.06 | 411.06 | 0.913193 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 | 252.34 | 252.34 | 0.560598 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 | 306.58 | 306.58 | 0.681098 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 | 405.25 | 405.25 | 0.900283 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 | 250.15 | 250.15 | 0.555727 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 | 300.39 | 300.39 | 0.667334 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 483.59 | 483.59 | 483.59 | 1.07 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 325.55 | 325.55 | 325.55 | 0.723240 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 377.23 | 377.23 | 377.23 | 0.838046 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 484.21 | 484.21 | 484.21 | 1.08 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 327.37 | 327.37 | 327.37 | 0.727270 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 378.43 | 378.43 | 378.43 | 0.840714 | 1.00 |
ACANDF_UNITHEATEDBSMT | 71.74 | 71.74 | 71.74 | 0.195781 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 43049.38 | 4.35 | 612.21 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 13829.78 | 1.40 | 189.40 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 16560.94 | 1.67 | 229.04 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 21306.25 | 2.15 | 297.91 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13713.03 | 1.38 | 187.70 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 16083.05 | 1.62 | 222.11 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 21386.26 | 2.16 | 299.05 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 13933.62 | 1.41 | 190.89 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 16480.65 | 1.66 | 227.85 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 21113.41 | 2.13 | 295.08 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 13830.67 | 1.40 | 189.39 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 16189.74 | 1.63 | 223.63 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 24792.88 | 2.50 | 348.40 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 17371.67 | 1.75 | 240.81 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 19798.48 | 2.00 | 276.01 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 24822.17 | 2.51 | 348.82 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 17456.84 | 1.76 | 242.07 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 19854.87 | 2.00 | 276.83 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 5453.41 | 0.550427 | 66.30 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 872.53 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 250.13 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 308.28 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 409.34 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 247.64 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 298.11 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 411.06 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 252.34 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 306.58 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 405.25 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 250.15 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 300.39 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 483.59 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 325.55 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 377.23 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 484.21 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 327.37 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 378.43 |
SUPPLY FAN_UNITHEATEDBSMT | 71.74 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 4.82 | 90.33 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 4.82 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 358357.96 | 36.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 84.236 | 0.292 | 0.037 | 84.236 |
February | 672.000 | 83.114 | 0.375 | 0.048 | 83.114 |
March | 744.000 | 99.672 | 0.000 | 0.000 | 99.672 |
April | 720.000 | 121.033 | 0.000 | 0.000 | 121.033 |
May | 744.000 | 144.817 | 0.000 | 0.000 | 144.817 |
June | 720.000 | 157.069 | 0.000 | 0.000 | 157.069 |
July | 744.000 | 167.553 | 0.000 | 0.000 | 167.553 |
August | 744.000 | 159.788 | 0.000 | 0.000 | 159.788 |
September | 720.000 | 146.296 | 0.000 | 0.000 | 146.296 |
October | 744.000 | 129.421 | 0.000 | 0.000 | 129.421 |
November | 720.000 | 94.623 | 0.000 | 0.000 | 94.623 |
December | 744.000 | 79.421 | 0.000 | 0.000 | 79.421 |
Annual Sum or Average | 8760.000 | 1467.042 | 0.667 | 0.086 | 1467.042 |
Minimum of Months | 672.000 | 79.421 | 0.000 | 0.000 | 79.421 |
Maximum of Months | 744.000 | 167.553 | 0.375 | 0.048 | 167.553 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 144.642 | 2.124 | 352.304 | 2.220 | 4.344 |
February | 168.217 | 3.873 | 240.292 | 1.524 | 5.398 |
March | 237.163 | 4.964 | 215.121 | 1.027 | 5.991 |
April | 479.085 | 14.670 | 43.575 | 0.145 | 14.815 |
May | 694.722 | 26.418 | 0.000 | 0.000 | 26.418 |
June | 720.000 | 36.764 | 0.000 | 0.000 | 36.764 |
July | 744.000 | 41.896 | 0.000 | 0.000 | 41.896 |
August | 744.000 | 37.234 | 0.000 | 0.000 | 37.234 |
September | 686.807 | 31.203 | 0.000 | 0.000 | 31.203 |
October | 513.778 | 19.302 | 13.417 | 0.017 | 19.319 |
November | 265.421 | 6.733 | 242.260 | 1.246 | 7.979 |
December | 130.696 | 1.580 | 368.458 | 2.873 | 4.453 |
Annual Sum or Average | 5528.530 | 226.761 | 1475.428 | 9.053 | 235.815 |
Minimum of Months | 130.696 | 1.580 | 0.000 | 0.000 | 4.344 |
Maximum of Months | 744.000 | 41.896 | 368.458 | 2.873 | 41.896 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 106.751 | 1.575 | 338.495 | 6.781 | 16.032 |
February | 163.074 | 4.267 | 213.958 | 4.350 | 16.160 |
March | 259.898 | 6.604 | 168.940 | 2.980 | 16.907 |
April | 504.521 | 20.215 | 24.488 | 0.380 | 22.987 |
May | 679.921 | 35.487 | 0.000 | 0.000 | 35.608 |
June | 719.250 | 48.474 | 0.000 | 0.000 | 48.474 |
July | 744.000 | 53.529 | 0.000 | 0.000 | 53.529 |
August | 739.625 | 47.113 | 0.000 | 0.000 | 47.113 |
September | 660.190 | 38.720 | 0.000 | 0.000 | 39.022 |
October | 489.768 | 22.080 | 12.313 | 0.125 | 25.391 |
November | 241.443 | 7.032 | 223.467 | 3.993 | 17.320 |
December | 89.325 | 1.045 | 356.296 | 8.373 | 17.939 |
Annual Sum or Average | 5397.765 | 286.141 | 1337.957 | 26.981 | 356.484 |
Minimum of Months | 89.325 | 1.045 | 0.000 | 0.000 | 16.032 |
Maximum of Months | 744.000 | 53.529 | 356.296 | 8.373 | 53.529 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 3.558 | 0.014 | 433.871 | 10.228 | 34.875 |
February | 70.218 | 1.247 | 313.717 | 6.725 | 26.764 |
March | 169.521 | 4.116 | 268.395 | 4.325 | 21.089 |
April | 427.606 | 18.040 | 56.035 | 0.619 | 22.629 |
May | 651.982 | 35.169 | 1.175 | 0.004 | 35.316 |
June | 719.500 | 49.150 | 0.000 | 0.000 | 49.150 |
July | 744.000 | 54.013 | 0.000 | 0.000 | 54.013 |
August | 739.375 | 45.906 | 0.000 | 0.000 | 45.906 |
September | 641.686 | 34.296 | 2.875 | 0.011 | 34.436 |
October | 406.491 | 15.932 | 54.255 | 0.323 | 17.559 |
November | 98.896 | 1.673 | 325.668 | 5.879 | 20.395 |
December | 0.000 | 0.000 | 461.150 | 12.494 | 40.372 |
Annual Sum or Average | 4672.833 | 259.555 | 1917.142 | 40.607 | 402.504 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.559 |
Maximum of Months | 744.000 | 54.013 | 461.150 | 12.494 | 54.013 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 587.723 | 5.169 | 9.652 |
February | 43.567 | 0.454 | 393.222 | 3.352 | 5.519 |
March | 121.776 | 1.391 | 296.445 | 1.985 | 4.712 |
April | 440.903 | 11.962 | 54.263 | 0.245 | 12.254 |
May | 694.380 | 25.865 | 0.000 | 0.000 | 25.865 |
June | 720.000 | 36.978 | 0.000 | 0.000 | 36.978 |
July | 744.000 | 41.738 | 0.000 | 0.000 | 41.738 |
August | 744.000 | 35.506 | 0.000 | 0.000 | 35.506 |
September | 679.470 | 26.032 | 0.000 | 0.000 | 26.032 |
October | 426.331 | 10.900 | 25.832 | 0.057 | 10.970 |
November | 50.250 | 0.537 | 374.164 | 2.743 | 5.135 |
December | 0.000 | 0.000 | 636.480 | 6.384 | 9.735 |
Annual Sum or Average | 4664.677 | 191.364 | 2368.129 | 19.934 | 224.096 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.712 |
Maximum of Months | 744.000 | 41.738 | 636.480 | 6.384 | 41.738 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 637.741 | 10.513 | 14.818 |
February | 58.275 | 0.678 | 374.170 | 6.311 | 12.639 |
March | 169.638 | 2.548 | 232.292 | 3.726 | 12.304 |
April | 480.274 | 17.471 | 29.000 | 0.422 | 20.000 |
May | 680.959 | 34.802 | 0.000 | 0.000 | 34.915 |
June | 719.250 | 48.395 | 0.000 | 0.000 | 48.395 |
July | 744.000 | 53.079 | 0.000 | 0.000 | 53.079 |
August | 739.375 | 45.270 | 0.000 | 0.000 | 45.270 |
September | 657.410 | 33.772 | 0.000 | 0.000 | 34.116 |
October | 447.179 | 14.040 | 21.458 | 0.193 | 17.656 |
November | 62.904 | 0.903 | 357.853 | 5.466 | 12.764 |
December | 0.000 | 0.000 | 671.717 | 12.776 | 15.846 |
Annual Sum or Average | 4759.263 | 250.958 | 2324.232 | 39.407 | 321.801 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.304 |
Maximum of Months | 744.000 | 53.079 | 671.717 | 12.776 | 53.079 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 155.875 | 3.544 | 378.354 | 6.015 | 9.559 |
February | 185.175 | 5.769 | 254.946 | 4.002 | 11.191 |
March | 264.292 | 9.019 | 178.591 | 2.408 | 18.703 |
April | 485.671 | 22.648 | 30.509 | 0.301 | 25.724 |
May | 682.579 | 37.065 | 0.000 | 0.000 | 37.065 |
June | 720.000 | 50.161 | 0.000 | 0.000 | 50.161 |
July | 744.000 | 55.290 | 0.000 | 0.000 | 55.290 |
August | 742.500 | 48.973 | 0.000 | 0.000 | 48.973 |
September | 674.196 | 40.656 | 0.125 | 0.000 | 40.657 |
October | 490.947 | 24.816 | 23.083 | 0.121 | 25.293 |
November | 259.936 | 9.294 | 254.600 | 3.478 | 13.402 |
December | 134.883 | 2.560 | 402.357 | 7.587 | 10.168 |
Annual Sum or Average | 5540.055 | 309.797 | 1522.567 | 23.911 | 346.186 |
Minimum of Months | 134.883 | 2.560 | 0.000 | 0.000 | 9.559 |
Maximum of Months | 744.000 | 55.290 | 402.357 | 7.587 | 55.290 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 160.950 | 2.364 | 318.749 | 2.132 | 4.602 |
February | 193.398 | 4.268 | 205.114 | 1.387 | 5.655 |
March | 263.901 | 5.616 | 168.106 | 0.871 | 6.523 |
April | 535.776 | 16.542 | 31.319 | 0.103 | 16.645 |
May | 721.186 | 27.815 | 0.000 | 0.000 | 27.815 |
June | 720.000 | 37.816 | 0.000 | 0.000 | 37.816 |
July | 744.000 | 42.910 | 0.000 | 0.000 | 42.910 |
August | 744.000 | 38.488 | 0.000 | 0.000 | 38.488 |
September | 693.945 | 32.524 | 0.000 | 0.000 | 32.524 |
October | 551.201 | 20.288 | 7.951 | 0.011 | 20.299 |
November | 293.712 | 7.455 | 203.358 | 1.177 | 8.997 |
December | 144.225 | 1.751 | 335.232 | 2.824 | 4.689 |
Annual Sum or Average | 5766.294 | 237.837 | 1269.830 | 8.505 | 246.964 |
Minimum of Months | 144.225 | 1.751 | 0.000 | 0.000 | 4.602 |
Maximum of Months | 744.000 | 42.910 | 335.232 | 2.824 | 42.910 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 118.100 | 1.685 | 307.944 | 5.408 | 15.262 |
February | 176.406 | 4.603 | 180.028 | 3.251 | 15.347 |
March | 277.997 | 7.269 | 123.438 | 2.008 | 16.567 |
April | 542.471 | 22.216 | 15.399 | 0.201 | 24.217 |
May | 703.494 | 36.896 | 0.000 | 0.000 | 36.896 |
June | 720.000 | 49.659 | 0.000 | 0.000 | 49.659 |
July | 744.000 | 54.588 | 0.000 | 0.000 | 54.588 |
August | 742.750 | 48.432 | 0.000 | 0.000 | 48.432 |
September | 683.012 | 40.018 | 0.000 | 0.000 | 40.090 |
October | 509.682 | 22.875 | 7.146 | 0.064 | 25.342 |
November | 265.979 | 7.582 | 190.980 | 3.056 | 17.712 |
December | 101.558 | 1.121 | 326.078 | 6.880 | 17.203 |
Annual Sum or Average | 5585.450 | 296.945 | 1151.012 | 20.868 | 361.315 |
Minimum of Months | 101.558 | 1.121 | 0.000 | 0.000 | 15.262 |
Maximum of Months | 744.000 | 54.588 | 326.078 | 6.880 | 54.588 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 4.232 | 0.011 | 404.915 | 8.573 | 34.418 |
February | 77.108 | 1.315 | 277.518 | 5.370 | 25.827 |
March | 187.846 | 4.487 | 215.387 | 3.147 | 21.189 |
April | 464.933 | 19.682 | 40.347 | 0.362 | 23.649 |
May | 680.585 | 36.462 | 0.000 | 0.000 | 36.462 |
June | 720.000 | 50.313 | 0.000 | 0.000 | 50.313 |
July | 744.000 | 55.113 | 0.000 | 0.000 | 55.113 |
August | 742.500 | 47.326 | 0.000 | 0.000 | 47.326 |
September | 666.279 | 35.725 | 1.000 | 0.002 | 35.751 |
October | 424.619 | 16.583 | 40.207 | 0.204 | 17.861 |
November | 114.932 | 1.839 | 295.559 | 4.796 | 19.618 |
December | 0.000 | 0.000 | 440.539 | 10.747 | 40.590 |
Annual Sum or Average | 4827.034 | 268.856 | 1715.471 | 33.201 | 408.117 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.861 |
Maximum of Months | 744.000 | 55.113 | 440.539 | 10.747 | 55.113 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 563.535 | 4.222 | 7.552 |
February | 54.721 | 0.622 | 356.632 | 2.591 | 4.788 |
March | 162.860 | 1.985 | 244.697 | 1.362 | 4.138 |
April | 503.600 | 13.899 | 36.539 | 0.128 | 14.045 |
May | 722.464 | 27.337 | 0.000 | 0.000 | 27.337 |
June | 720.000 | 38.033 | 0.000 | 0.000 | 38.033 |
July | 744.000 | 42.781 | 0.000 | 0.000 | 42.781 |
August | 744.000 | 36.860 | 0.000 | 0.000 | 36.860 |
September | 688.600 | 27.547 | 0.000 | 0.000 | 27.547 |
October | 464.565 | 11.898 | 16.468 | 0.029 | 11.933 |
November | 76.771 | 0.874 | 338.616 | 2.139 | 4.469 |
December | 0.000 | 0.000 | 618.444 | 5.379 | 8.017 |
Annual Sum or Average | 4881.581 | 201.837 | 2174.930 | 15.849 | 227.500 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.138 |
Maximum of Months | 744.000 | 42.781 | 618.444 | 5.379 | 42.781 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 600.935 | 8.938 | 15.026 |
February | 63.692 | 0.851 | 336.784 | 5.041 | 11.719 |
March | 191.981 | 3.147 | 176.754 | 2.662 | 12.263 |
April | 530.134 | 19.564 | 17.104 | 0.221 | 21.602 |
May | 703.919 | 36.313 | 0.000 | 0.000 | 36.313 |
June | 720.000 | 49.664 | 0.000 | 0.000 | 49.664 |
July | 744.000 | 54.257 | 0.000 | 0.000 | 54.257 |
August | 742.750 | 46.755 | 0.000 | 0.000 | 46.755 |
September | 679.568 | 35.285 | 0.000 | 0.000 | 35.387 |
October | 466.626 | 14.894 | 12.446 | 0.103 | 17.683 |
November | 79.279 | 1.186 | 316.710 | 4.435 | 12.873 |
December | 0.000 | 0.000 | 643.909 | 11.129 | 15.804 |
Annual Sum or Average | 4921.950 | 261.918 | 2104.642 | 32.530 | 329.347 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 11.719 |
Maximum of Months | 744.000 | 54.257 | 643.909 | 11.129 | 54.257 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 99.812 | 2.006 | 466.437 | 12.084 | 14.117 |
February | 138.324 | 4.602 | 313.714 | 8.109 | 16.918 |
March | 217.900 | 7.910 | 216.605 | 5.017 | 28.984 |
April | 446.805 | 23.919 | 43.373 | 0.733 | 30.685 |
May | 643.641 | 40.742 | 1.992 | 0.007 | 41.287 |
June | 719.750 | 57.442 | 0.000 | 0.000 | 57.442 |
July | 744.000 | 63.026 | 0.000 | 0.000 | 63.026 |
August | 736.700 | 54.871 | 0.000 | 0.000 | 54.871 |
September | 642.390 | 43.972 | 1.864 | 0.012 | 44.627 |
October | 447.583 | 24.710 | 41.437 | 0.455 | 29.160 |
November | 210.579 | 7.708 | 311.656 | 7.238 | 18.179 |
December | 75.825 | 1.105 | 490.454 | 14.721 | 15.826 |
Annual Sum or Average | 5123.309 | 332.013 | 1887.534 | 48.376 | 415.123 |
Minimum of Months | 75.825 | 1.105 | 0.000 | 0.000 | 14.117 |
Maximum of Months | 744.000 | 63.026 | 490.454 | 14.721 | 63.026 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 90.568 | 1.177 | 416.958 | 4.640 | 6.053 |
February | 143.450 | 3.453 | 290.865 | 3.119 | 6.603 |
March | 216.858 | 5.062 | 255.870 | 2.222 | 7.601 |
April | 468.515 | 17.989 | 59.111 | 0.345 | 18.372 |
May | 684.129 | 31.563 | 0.000 | 0.000 | 31.563 |
June | 720.000 | 45.357 | 0.000 | 0.000 | 45.357 |
July | 744.000 | 50.962 | 0.000 | 0.000 | 50.962 |
August | 744.000 | 44.681 | 0.000 | 0.000 | 44.681 |
September | 676.940 | 36.054 | 0.000 | 0.000 | 36.054 |
October | 477.180 | 20.277 | 33.333 | 0.116 | 20.394 |
November | 230.510 | 6.010 | 286.158 | 2.742 | 8.802 |
December | 68.375 | 0.558 | 443.583 | 5.823 | 7.033 |
Annual Sum or Average | 5264.526 | 263.144 | 1785.879 | 19.008 | 283.476 |
Minimum of Months | 68.375 | 0.558 | 0.000 | 0.000 | 6.053 |
Maximum of Months | 744.000 | 50.962 | 443.583 | 5.823 | 50.962 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 64.792 | 0.794 | 406.429 | 8.985 | 17.392 |
February | 138.026 | 3.721 | 269.385 | 5.711 | 16.482 |
March | 230.694 | 6.317 | 211.003 | 3.808 | 17.433 |
April | 500.313 | 23.217 | 35.083 | 0.496 | 25.643 |
May | 680.462 | 40.536 | 0.000 | 0.000 | 40.786 |
June | 719.250 | 57.067 | 0.000 | 0.000 | 57.067 |
July | 744.000 | 62.512 | 0.000 | 0.000 | 62.512 |
August | 737.275 | 54.548 | 0.000 | 0.000 | 54.548 |
September | 658.347 | 43.519 | 0.000 | 0.000 | 44.038 |
October | 471.688 | 22.874 | 29.500 | 0.306 | 27.459 |
November | 210.963 | 6.154 | 268.488 | 5.296 | 17.305 |
December | 36.212 | 0.255 | 442.250 | 11.129 | 18.790 |
Annual Sum or Average | 5192.022 | 321.514 | 1662.139 | 35.730 | 399.454 |
Minimum of Months | 36.212 | 0.255 | 0.000 | 0.000 | 16.482 |
Maximum of Months | 744.000 | 62.512 | 442.250 | 11.129 | 62.512 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 5.179 | 0.044 | 473.200 | 13.079 | 35.478 |
February | 75.335 | 1.727 | 338.925 | 8.608 | 27.241 |
March | 182.238 | 5.418 | 271.068 | 5.323 | 25.242 |
April | 438.532 | 22.659 | 51.681 | 0.762 | 29.046 |
May | 644.497 | 40.697 | 2.125 | 0.010 | 41.146 |
June | 719.750 | 57.748 | 0.000 | 0.000 | 57.748 |
July | 744.000 | 63.255 | 0.000 | 0.000 | 63.255 |
August | 736.450 | 54.388 | 0.000 | 0.000 | 54.388 |
September | 636.941 | 41.430 | 4.811 | 0.024 | 41.815 |
October | 398.906 | 19.043 | 71.722 | 0.548 | 23.224 |
November | 115.392 | 2.352 | 335.298 | 7.448 | 24.841 |
December | 0.000 | 0.000 | 504.864 | 16.067 | 40.964 |
Annual Sum or Average | 4697.220 | 308.760 | 2053.692 | 51.868 | 464.387 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 23.224 |
Maximum of Months | 744.000 | 63.255 | 504.864 | 16.067 | 63.255 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.458 | 0.005 | 593.401 | 7.215 | 10.563 |
February | 58.194 | 0.924 | 405.153 | 4.578 | 7.272 |
March | 159.342 | 2.780 | 303.529 | 2.768 | 6.492 |
April | 453.577 | 16.817 | 63.333 | 0.373 | 17.211 |
May | 684.165 | 31.562 | 0.000 | 0.000 | 31.562 |
June | 720.000 | 45.702 | 0.000 | 0.000 | 45.702 |
July | 744.000 | 51.224 | 0.000 | 0.000 | 51.224 |
August | 744.000 | 44.207 | 0.000 | 0.000 | 44.207 |
September | 672.110 | 33.477 | 0.375 | 0.000 | 33.477 |
October | 414.398 | 14.355 | 48.820 | 0.165 | 14.536 |
November | 81.421 | 1.087 | 389.515 | 3.995 | 6.394 |
December | 0.000 | 0.000 | 644.446 | 8.892 | 11.865 |
Annual Sum or Average | 4733.666 | 242.141 | 2448.574 | 27.986 | 280.506 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.394 |
Maximum of Months | 744.000 | 51.224 | 644.446 | 8.892 | 51.224 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.125 | 0.000 | 628.647 | 12.784 | 18.005 |
February | 62.836 | 1.138 | 392.097 | 7.673 | 14.169 |
March | 180.285 | 3.834 | 250.906 | 4.396 | 15.234 |
April | 489.353 | 22.043 | 36.708 | 0.517 | 24.544 |
May | 680.845 | 40.507 | 0.000 | 0.000 | 40.749 |
June | 719.500 | 57.347 | 0.000 | 0.000 | 57.347 |
July | 744.000 | 62.701 | 0.000 | 0.000 | 62.701 |
August | 737.150 | 54.074 | 0.000 | 0.000 | 54.074 |
September | 655.789 | 41.084 | 0.250 | 0.003 | 41.560 |
October | 432.017 | 16.966 | 38.667 | 0.381 | 21.569 |
November | 81.021 | 1.317 | 380.365 | 6.938 | 14.757 |
December | 0.000 | 0.000 | 673.054 | 15.559 | 18.668 |
Annual Sum or Average | 4782.922 | 301.012 | 2400.694 | 48.251 | 383.377 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 14.169 |
Maximum of Months | 744.000 | 62.701 | 673.054 | 15.559 | 62.701 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 680.050 | 8.263 | 9.988 |
February | 0.000 | 0.000 | 502.892 | 5.839 | 10.415 |
March | 0.000 | 0.000 | 490.202 | 4.581 | 11.448 |
April | 0.000 | 0.000 | 391.488 | 1.233 | 6.022 |
May | 218.943 | 0.690 | 0.000 | 0.000 | 0.690 |
June | 720.000 | 7.227 | 0.000 | 0.000 | 7.227 |
July | 744.000 | 7.750 | 0.000 | 0.000 | 7.750 |
August | 740.238 | 7.076 | 0.000 | 0.000 | 7.076 |
September | 646.625 | 5.038 | 0.000 | 0.000 | 5.038 |
October | 168.547 | 0.618 | 0.000 | 0.000 | 0.618 |
November | 0.000 | 0.000 | 469.871 | 2.779 | 8.322 |
December | 0.000 | 0.000 | 705.200 | 8.105 | 9.152 |
Annual Sum or Average | 3238.352 | 28.398 | 3239.702 | 30.798 | 83.745 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.618 |
Maximum of Months | 744.000 | 7.750 | 705.200 | 8.263 | 11.448 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.63 |
February | 0.00 | 0.00 | 0.68 |
March | 0.00 | 0.00 | 0.73 |
April | 0.00 | 0.00 | 0.90 |
May | 0.00 | 0.00 | 1.04 |
June | 0.00 | 0.00 | 1.15 |
July | 0.00 | 0.00 | 1.21 |
August | 0.00 | 0.00 | 1.15 |
September | 0.00 | 0.00 | 1.11 |
October | 0.00 | 0.00 | 0.96 |
November | 0.00 | 0.00 | 0.73 |
December | 0.00 | 0.00 | 0.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.91 |
Minimum of Months | 0.00 | 0.00 | 0.60 |
Maximum of Months | 0.00 | 0.00 | 1.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.24 |
October | 0.00 | 0.00 | 0.14 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.14 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.18 |
November | 0.00 | 0.00 | 0.07 |
December | 0.00 | 0.00 | 0.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.02 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.02 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.19 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.05 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.04 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.26 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.14 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.19 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.14 |
May | 0.00 | 0.00 | 0.25 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.05 |
April | 0.00 | 0.00 | 0.17 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.17 |
November | 0.00 | 0.00 | 0.06 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.20 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.13 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.27 |
October | 0.00 | 0.00 | 0.15 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.00 | 0.16 |
November | 0.00 | 0.00 | 0.04 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.19 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.30 |
October | 0.00 | 0.00 | 0.13 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.22 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.10 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.16 |
May | 0.00 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.41 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.31 |
October | 0.00 | 0.00 | 0.12 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |
Minimum of Months | 0.00 | 0.00 | 1018.91 | 758.60 |
Maximum of Months | 0.00 | 0.00 | 1458.69 | 1082.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1454.59 | 1082.99 |
February | 0.00 | 0.00 | 1458.69 | 980.94 |
March | 0.00 | 0.00 | 1400.12 | 1042.43 |
April | 0.00 | 0.00 | 1304.21 | 939.69 |
May | 0.00 | 0.00 | 1183.89 | 881.44 |
June | 0.00 | 0.00 | 1082.43 | 779.90 |
July | 0.00 | 0.00 | 1022.31 | 761.14 |
August | 0.00 | 0.00 | 1018.91 | 758.60 |
September | 0.00 | 0.00 | 1075.42 | 774.85 |
October | 0.00 | 0.00 | 1178.57 | 877.48 |
November | 0.00 | 0.00 | 1293.39 | 931.90 |
December | 0.00 | 0.00 | 1398.30 | 1041.08 |
Annual Sum or Average | 0.00 | 0.00 | 1237.98 | 10852.43 |