Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:38
Tabular Output Report in Format: HTML
Building: MF+CZ3CWH+USA_CA_San.Francisco.Intl.AP.724940+oilfurnace+heatedbsmt+IECC_2009
Environment: ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940
Simulation Timestamp: 2019-02-14 08:38:54
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 872027.70 | 22.36 | 29.66 |
Net Site Energy | 872027.70 | 22.36 | 29.66 |
Total Source Energy | 1774503.12 | 45.49 | 60.35 |
Net Source Energy | 1774503.12 | 45.49 | 60.35 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 180718.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 23552.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12886.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 293217.28 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 398091.74 | 473935.96 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 180718.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 23552.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 12886.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 293217.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 1.24 | 16.12 | 0.00 | 0.00 | 0.00 | 14.27 |
Other | 10.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 13.54 | 16.12 | 0.00 | 0.00 | 0.00 | 14.27 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 0.93 | 12.15 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 10.21 | 12.15 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 398091.740 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 398091.740 | 100.00 |
Total On-Site and Utility Electric Sources | 398091.740 | 100.00 |
Total Electricity End Uses | 398091.740 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 2573.00 |
Time Setpoint Not Met During Occupied Cooling | 11.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 65.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:38 |
RunPeriod | ANNUAL |
Weather File | San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Latitude [deg] | 37.62 |
Longitude [deg] | -122.4 |
Elevation [ft] | 6.56 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.5522 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 30-JUN-18:15 | 24-JAN-06:15 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 119.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 27.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 51.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.58 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 101.90 | 232.75 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 119.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 27.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 6.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.58 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 195899.05 | 0.00 | 0.00 | 0.00 |
Cooling | 74590.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 40811.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 317847.54 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1260756.54 | 513746.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 6.66 | 0.00 | 0.00 | 0.00 |
Cooling | 2.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.81 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 42.88 | 17.47 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 6.66 | 0.00 | 0.00 | 0.00 |
Cooling | 2.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.81 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 42.88 | 17.47 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 38.84 | 0.00 | 38.84 | Wetbulb [F] | 433.09 | 150.00 |
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 82.94 | 15.30 | 62.96 | Wetbulb [F] | 1161.47 | 310.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.087 | 0.094 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.501 | 0.258 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.501 | 0.258 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.501 | 0.258 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.501 | 0.258 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.501 | 0.258 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.351 | 0.500 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 314400.12 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 20415.31 | 16304.79 | 4110.51 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4823.93 | 3852.65 | 971.27 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6477.26 | 5173.10 | 1304.16 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9052.21 | 7229.59 | 1822.61 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 3979.16 | 3177.97 | 801.18 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 5713.67 | 4563.25 | 1150.42 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9647.67 | 7705.16 | 1942.51 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4694.71 | 3749.46 | 945.26 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6378.04 | 5093.86 | 1284.18 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8889.81 | 7099.90 | 1789.92 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4146.99 | 3312.02 | 834.97 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 5542.44 | 4426.50 | 1115.94 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10933.86 | 8732.39 | 2201.48 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5979.82 | 4775.81 | 1204.00 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 7270.67 | 5806.76 | 1463.91 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10760.74 | 8594.12 | 2166.62 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5821.32 | 4649.23 | 1172.09 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6808.31 | 5437.49 | 1370.82 | 0.80 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 2086.37 | 1566.19 | 520.18 | 0.75 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.6 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.7 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.3 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.8 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.7 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.3 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.4 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 0.9 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.6 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.5 | 3.26 | 11.12 | 11.77 | 11.27 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.2 | 3.35 | 11.43 | 12.11 | 11.76 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 43066.07 | 46377.88 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 11410.11 | 11627.49 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 14767.50 | 15326.18 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 19996.26 | 21075.10 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 9694.72 | 9732.86 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13216.94 | 13618.25 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 21204.89 | 22401.74 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 11147.52 | 11336.93 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 14565.71 | 15103.08 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 19666.03 | 20710.79 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 10035.35 | 10108.79 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 12868.97 | 13234.06 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 23817.27 | 25271.02 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 13757.30 | 14214.19 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 16378.68 | 17097.79 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 23465.72 | 24884.93 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 13435.47 | 13859.79 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 15439.78 | 16065.11 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 5298.22 | 4829.90 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 765.80 | 288.85 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 180.95 | 68.25 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 242.97 | 91.65 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 339.56 | 128.08 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 149.26 | 56.30 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 214.33 | 80.84 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 361.89 | 136.50 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 176.10 | 66.42 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 239.25 | 90.24 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 333.47 | 125.78 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 155.56 | 58.68 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 207.90 | 78.42 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 410.14 | 154.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 224.31 | 84.61 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 272.73 | 102.87 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 403.65 | 152.25 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 218.36 | 82.37 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 255.39 | 96.33 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 68.05 | 25.67 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 31.615353 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17988.20 | 17988.20 | 14.98 | 765.797 | 765.797 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00808 | 80.03 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4250.42 | 4250.42 | 3.54 | 180.950 | 180.950 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 74.98 | 74.98 | 0.00808 | 82.94 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5707.20 | 5707.20 | 4.75 | 242.968 | 242.968 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 74.98 | 74.98 | 0.00807 | 82.75 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7976.04 | 7976.04 | 6.64 | 339.557 | 339.557 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00813 | 80.03 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3506.09 | 3506.09 | 2.92 | 149.262 | 149.262 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00835 | 77.55 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5034.42 | 5034.42 | 4.19 | 214.325 | 214.325 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 74.98 | 74.98 | 0.00810 | 77.13 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8500.69 | 8500.69 | 7.08 | 361.893 | 361.893 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00815 | 80.03 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4136.57 | 4136.57 | 3.45 | 176.103 | 176.103 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00833 | 78.69 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5619.75 | 5619.75 | 4.68 | 239.246 | 239.246 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 74.98 | 74.98 | 0.00810 | 82.75 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7832.92 | 7832.92 | 6.52 | 333.465 | 333.465 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00818 | 79.65 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3653.96 | 3653.96 | 3.04 | 155.557 | 155.557 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00843 | 76.97 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4883.53 | 4883.53 | 4.07 | 207.902 | 207.902 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 10:15:00 | 74.98 | 74.98 | 0.00814 | 77.70 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 5998.92 | 5998.92 | 5.00 | 255.386 | 255.386 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 74.98 | 74.98 | 0.00806 | 82.48 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6406.29 | 6406.29 | 5.34 | 272.730 | 272.730 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 74.98 | 74.98 | 0.00806 | 82.94 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 9633.99 | 9633.99 | 8.02 | 410.139 | 410.139 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00812 | 80.03 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5129.24 | 5129.24 | 4.27 | 218.363 | 218.363 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:15:00 | 74.98 | 74.98 | 0.00824 | 78.69 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5268.90 | 5268.90 | 4.39 | 224.308 | 224.308 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00822 | 79.27 | 0.00771 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 9481.45 | 9481.45 | 7.90 | 403.645 | 403.645 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00812 | 80.03 | 0.00771 | 44.995 | 0.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB | 74.44 | 32.00 | 0.00000 | 82.94 | 0.00771 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 38.84 | 0.00496 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4536.59 | 4536.59 | 3.78 | 82.583 | 82.583 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00671 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6311.66 | 6311.66 | 5.26 | 114.895 | 114.895 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00686 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6320.36 | 6320.36 | 5.26 | 115.053 | 115.053 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00686 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4671.41 | 4671.41 | 3.89 | 85.037 | 85.037 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00673 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6313.79 | 6313.79 | 5.26 | 114.933 | 114.933 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00686 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5226.08 | 5226.08 | 4.35 | 95.136 | 95.136 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00702 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3869.28 | 3869.28 | 3.22 | 70.438 | 70.438 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00692 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5563.83 | 5563.83 | 4.63 | 101.284 | 101.284 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00706 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5566.15 | 5566.15 | 4.64 | 101.327 | 101.327 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00706 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3897.92 | 3897.92 | 3.25 | 70.959 | 70.959 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00693 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5562.18 | 5562.18 | 4.63 | 101.254 | 101.254 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00706 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7575.49 | 7575.49 | 6.31 | 137.900 | 137.900 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00698 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7577.77 | 7577.77 | 6.31 | 137.942 | 137.942 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00698 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 7531.29 | 7531.29 | 6.27 | 137.096 | 137.096 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00697 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5915.33 | 5915.33 | 4.93 | 107.681 | 107.681 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00687 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5910.13 | 5910.13 | 4.92 | 107.586 | 107.586 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00687 | 38.84 | 0.00496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 7577.00 | 7577.00 | 6.31 | 137.928 | 137.928 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00698 | 38.84 | 0.00496 | 44.995 | 0.00 |
HEATEDBSMT | 3737.77 | 3737.77 | 0.48 | 68.048 | 68.048 | SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB | 1/21 07:30:00 | 72.00 | 72.00 | 0.00800 | 38.84 | 0.00496 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 | 765.80 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 | 180.95 | 82.58 | 82.58 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 | 242.97 | 114.89 | 114.89 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 | 339.56 | 115.05 | 115.05 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 | 149.26 | 85.04 | 85.04 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 | 214.33 | 114.93 | 114.93 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 | 361.89 | 95.14 | 95.14 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 | 176.10 | 70.44 | 70.44 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 | 239.25 | 101.28 | 101.28 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 | 333.47 | 101.33 | 101.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 | 155.56 | 70.96 | 70.96 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 | 207.90 | 101.25 | 101.25 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 410.14 | 410.14 | 137.10 | 137.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 224.31 | 224.31 | 107.59 | 107.59 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 272.73 | 272.73 | 137.94 | 137.94 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 403.65 | 403.65 | 137.93 | 137.93 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 218.36 | 218.36 | 107.68 | 107.68 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 255.39 | 255.39 | 137.90 | 137.90 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 68.05 | 68.05 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.00 | 6273.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 432.50 | 6896.25 | 10.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 711.50 | 6730.75 | 4.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 586.75 | 7494.50 | 45.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 113.75 | 7935.25 | 10.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 290.00 | 7463.75 | 6.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 982.00 | 6403.50 | 13.50 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 464.75 | 6408.25 | 17.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 721.50 | 6397.50 | 13.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 602.75 | 7231.75 | 39.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 199.00 | 7551.50 | 18.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 333.25 | 7171.50 | 15.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 593.25 | 7286.50 | 4.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 795.75 | 6856.75 | 4.25 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 969.00 | 6897.50 | 7.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 411.75 | 7569.75 | 9.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 613.50 | 6993.50 | 8.75 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 756.25 | 7306.25 | 10.75 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1414.50 | 8147.50 | 65.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 3.75 | 0.00 | 3.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 532.25 | 4.50 | 532.25 | 4.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 701.50 | 0.00 | 701.50 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 129.25 | 3.50 | 129.25 | 3.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 294.75 | 2.75 | 294.75 | 2.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 89.75 | 0.00 | 89.75 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3.25 | 0.25 | 3.25 | 0.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 640.75 | 2.00 | 640.75 | 2.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 673.50 | 0.00 | 673.50 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 23.50 | 0.00 | 23.50 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 480.25 | 2.00 | 480.25 | 2.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 232.00 | 6.75 | 232.00 | 6.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 331.25 | 6.75 | 331.25 | 6.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 376.75 | 0.00 | 376.75 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21.75 | 2.75 | 21.75 | 2.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7.25 | 0.00 | 7.25 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 597.00 | 0.00 | 597.00 | 0.00 |
HEATEDBSMT | 452.75 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2915.75 | 11.25 | 2573.00 | 11.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.304 | 0.000 | 0.274 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.261 | 0.000 | 0.273 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.296 | 0.000 | 0.273 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.294 | 0.000 | 0.273 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.260 | 0.000 | 0.273 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.295 | 0.000 | 0.273 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.130 | 0.000 | 0.273 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.095 | 0.000 | 0.273 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.130 | 0.000 | 0.273 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.129 | 0.000 | 0.273 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.094 | 0.000 | 0.273 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.130 | 0.000 | 0.273 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.296 | 0.000 | 0.273 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.296 | 0.000 | 0.273 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.296 | 0.000 | 0.273 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.260 | 0.000 | 0.273 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.261 | 0.000 | 0.273 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.295 | 0.000 | 0.273 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.006 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 3774.13 | 108.71 | 21-OCT-02:00 | 1893.01 | 30-JUN-16:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
ElectricityPurchased:Plant | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
Cogeneration:ElectricityPurchased | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
ElectricityNet:Plant | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
Cogeneration:ElectricityNet | 116591.41 | 7526.68 | 19-JUN-03:15 | 29844.46 | 30-JUN-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 10672.08 | 522.65 | 02-MAY-23:30 | 10710.74 | 02-JUN-15:00 |
General:Fans:Electricity | 3774.13 | 108.71 | 21-OCT-02:00 | 1893.01 | 30-JUN-16:15 |
Cooling:Electricity | 6897.95 | 31.32 | 22-DEC-05:00 | 8854.78 | 02-JUN-15:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 4739.36 | 0.00 | 13-FEB-15:30 | 232587.91 | 24-JAN-06:15 |
Gas:Plant | 4739.36 | 0.00 | 13-FEB-15:30 | 232587.91 | 24-JAN-06:15 |
WaterSystems:Gas | 2932.17 | 0.00 | 01-JAN-00:15 | 114922.67 | 12-FEB-08:45 |
Water Heater:WaterSystems:Gas | 2932.17 | 0.00 | 01-JAN-00:15 | 114922.67 | 12-FEB-08:45 |
Heating:Gas | 1807.19 | 0.00 | 13-FEB-15:15 | 121358.31 | 24-JAN-06:00 |
Boiler:Heating:Gas | 1807.19 | 0.00 | 13-FEB-15:15 | 121358.31 | 24-JAN-06:00 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 13-FEB-02:45 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 300517.05 | 1556.86 | 03-AUG-02:15 | 126651.17 | 26-DEC-07:15 |
PlantLoopHeatingDemand:Plant | 156420.46 | 1556.42 | 08-AUG-02:15 | 36459.03 | 05-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 156420.46 | 1556.42 | 08-AUG-02:15 | 36459.03 | 05-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 816028.30 | 15861.67 | 21-OCT-02:15 | 319807.39 | 24-JAN-06:15 |
EnergyTransfer:Building | 253669.97 | 6756.76 | 03-JUN-01:30 | 115541.86 | 30-JUN-16:15 |
EnergyTransfer:Zone:HEATEDBSMT | 9556.43 | 0.00 | 01-MAY-09:30 | 4362.20 | 16-FEB-21:00 |
Heating:EnergyTransfer | 151213.75 | 0.00 | 01-MAY-09:30 | 100390.17 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 9556.43 | 0.00 | 01-MAY-09:30 | 4362.20 | 16-FEB-21:00 |
Cooling:EnergyTransfer | 102456.22 | 516.91 | 22-DEC-05:00 | 115541.86 | 30-JUN-16:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 64724.48 | 516.91 | 22-DEC-05:00 | 17456.22 | 02-APR-16:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 64724.48 | 516.91 | 22-DEC-05:00 | 17456.22 | 02-APR-16:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6744.41 | 0.00 | 01-JAN-11:30 | 4674.51 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4996.93 | 0.00 | 01-JAN-11:30 | 4674.51 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1747.48 | 0.00 | 01-JAN-00:15 | 4399.09 | 20-OCT-14:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11286.56 | 0.00 | 01-JAN-10:45 | 6380.75 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8502.92 | 0.00 | 01-JAN-10:45 | 6380.75 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2783.64 | 0.00 | 01-JAN-00:15 | 5790.16 | 16-SEP-15:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12555.39 | 0.00 | 01-JAN-15:15 | 7766.18 | 30-JUN-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10617.29 | 0.00 | 01-JAN-15:15 | 6442.75 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1938.09 | 0.00 | 01-JAN-00:15 | 7766.18 | 30-JUN-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8106.43 | 0.00 | 13-FEB-15:45 | 4867.38 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7556.11 | 0.00 | 13-FEB-15:45 | 4867.38 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 550.32 | 0.00 | 01-JAN-00:15 | 3457.84 | 30-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12087.69 | 0.00 | 13-FEB-15:15 | 6429.83 | 22-DEC-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10727.98 | 0.00 | 13-FEB-15:15 | 6429.83 | 22-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1359.71 | 0.00 | 01-JAN-00:15 | 4921.68 | 30-JUN-16:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9739.65 | 0.00 | 01-JAN-12:00 | 8148.26 | 02-APR-16:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5381.94 | 0.00 | 01-JAN-12:00 | 4957.64 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4357.71 | 0.00 | 01-JAN-00:15 | 8148.26 | 02-APR-16:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5366.71 | 0.00 | 01-JAN-11:15 | 4267.97 | 20-OCT-15:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 3014.72 | 0.00 | 01-JAN-11:15 | 3511.58 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2351.99 | 0.00 | 01-JAN-00:15 | 4267.97 | 20-OCT-15:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9035.74 | 0.00 | 01-JAN-10:45 | 5657.61 | 16-SEP-15:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5768.97 | 0.00 | 01-JAN-10:45 | 5311.27 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 3266.77 | 0.00 | 01-JAN-00:15 | 5657.61 | 16-SEP-15:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10060.40 | 0.00 | 01-FEB-15:45 | 7618.73 | 02-JUN-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7726.64 | 0.00 | 01-FEB-15:45 | 5324.93 | 12-JAN-17:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2333.76 | 0.00 | 01-JAN-00:15 | 7618.73 | 02-JUN-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5616.38 | 0.00 | 03-JAN-18:15 | 3617.53 | 30-JUN-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4750.07 | 0.00 | 03-JAN-18:15 | 3581.46 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 866.31 | 0.00 | 01-JAN-00:15 | 3617.53 | 30-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9274.70 | 0.00 | 13-FEB-15:00 | 5342.99 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7610.62 | 0.00 | 13-FEB-15:00 | 5342.99 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1664.08 | 0.00 | 01-JAN-00:15 | 4794.92 | 30-JUN-16:30 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 14795.28 | 0.00 | 13-FEB-15:00 | 7441.90 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 12793.86 | 0.00 | 13-FEB-15:00 | 7441.90 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2001.42 | 0.00 | 01-JAN-00:15 | 6056.16 | 16-SEP-15:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 13768.06 | 0.00 | 01-JAN-12:45 | 7420.11 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 10932.06 | 0.00 | 01-JAN-12:45 | 7420.11 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2835.99 | 0.00 | 01-JAN-00:15 | 6534.94 | 16-SEP-15:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 14861.25 | 0.00 | 01-JAN-13:30 | 9320.83 | 30-JUN-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11133.09 | 0.00 | 01-JAN-13:30 | 7354.43 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 3728.16 | 0.00 | 01-JAN-00:15 | 9320.83 | 30-JUN-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 10749.97 | 0.00 | 03-JAN-18:15 | 5688.95 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 9527.07 | 0.00 | 03-JAN-18:15 | 5688.95 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 1222.90 | 0.00 | 01-JAN-00:15 | 5102.51 | 30-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9558.53 | 0.00 | 01-JAN-13:00 | 5651.57 | 24-JAN-06:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 7566.88 | 0.00 | 01-JAN-13:00 | 5651.57 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 1991.64 | 0.00 | 01-JAN-00:15 | 5289.34 | 02-APR-17:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 15781.94 | 0.00 | 01-FEB-15:45 | 9318.89 | 30-JUN-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 13050.18 | 0.00 | 01-FEB-15:45 | 7421.84 | 24-JAN-06:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2731.76 | 0.00 | 01-JAN-00:15 | 9318.89 | 30-JUN-17:15 |
EnergyTransfer:Plant | 300995.41 | 1556.86 | 03-AUG-02:15 | 126653.16 | 26-DEC-07:15 |
WaterSystems:EnergyTransfer | 156420.46 | 1556.42 | 08-AUG-02:15 | 36459.03 | 05-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 156420.46 | 1556.42 | 08-AUG-02:15 | 36459.03 | 05-FEB-09:00 |
EnergyTransfer:HVAC | 261362.91 | 7046.36 | 27-JUN-23:00 | 132791.95 | 30-JUN-16:15 |
HeatingCoils:EnergyTransfer | 144096.59 | 0.00 | 13-FEB-15:15 | 97891.02 | 24-JAN-06:00 |
PlantLoopHeatingDemand:HVAC | 144096.59 | 0.00 | 13-FEB-15:15 | 97891.02 | 24-JAN-06:00 |
HeatingCoils:PlantLoopHeatingDemand | 144096.59 | 0.00 | 13-FEB-15:15 | 97891.02 | 24-JAN-06:00 |
CoolingCoils:EnergyTransfer | 117266.32 | 546.42 | 22-DEC-05:00 | 132791.95 | 30-JUN-16:15 |
Boilers:EnergyTransfer | 144574.94 | 0.00 | 13-FEB-15:15 | 97086.65 | 24-JAN-06:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 0.000 | -5390.10 | 0.000 | 0.000 | 2873.569 | 2771.241 | 10464.601 | 6948.021 | 0.000 | 53.767 | 65440.280 | 0.000 | -7098.44 | 0.000 | -16728.63 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 4996.871 | -145.52 | 0.000 | 0.000 | 3088.713 | 2771.241 | 10464.601 | 3315.349 | 0.000 | 49.922 | 0.000 | 0.000 | -2739.08 | 0.000 | -13841.09 | -6359.08 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 8502.831 | -231.81 | 0.000 | 0.000 | 3116.087 | 2771.241 | 10464.601 | 6683.922 | 0.000 | 53.333 | 0.000 | 0.000 | -6365.66 | 0.000 | -14642.44 | -7800.33 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 10617.198 | -161.40 | 0.000 | 0.000 | 3127.120 | 2771.241 | 10464.601 | 4658.593 | 0.000 | 54.202 | 0.000 | 0.000 | -6574.23 | 0.000 | -14271.20 | -8909.47 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 7556.046 | -45.83 | 0.000 | 0.000 | 3123.350 | 2771.241 | 10464.601 | 561.568 | 0.000 | 50.313 | 0.000 | 0.000 | -2794.48 | 0.000 | -13408.99 | -7773.34 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 10727.882 | -113.23 | 0.000 | 0.000 | 3131.302 | 2771.241 | 10464.601 | 4015.172 | 0.000 | 53.501 | 0.000 | 0.000 | -6370.14 | 0.000 | -14388.44 | -9045.43 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5381.873 | -362.89 | 0.000 | 0.000 | 3074.826 | 2771.241 | 10464.601 | 7106.148 | 0.000 | 36.969 | 0.030 | 0.000 | -6741.36 | 0.000 | -10602.90 | -7133.76 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 3014.678 | -195.87 | 0.000 | 0.000 | 3053.529 | 2771.241 | 10464.601 | 3299.718 | 0.000 | 33.418 | 0.038 | 0.000 | -2813.32 | 0.000 | -9765.94 | -7705.96 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5768.898 | -272.04 | 0.000 | 0.000 | 3093.771 | 2771.241 | 10464.601 | 6646.026 | 0.000 | 36.725 | 0.016 | 0.000 | -6532.32 | 0.000 | -10561.74 | -8420.48 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 7726.564 | -194.35 | 0.000 | 0.000 | 3106.866 | 2771.241 | 10464.601 | 4611.786 | 0.000 | 37.552 | 0.000 | 0.000 | -6731.96 | 0.000 | -10287.00 | -9365.93 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 4750.020 | -72.14 | 0.000 | 0.000 | 3092.245 | 2771.241 | 10464.601 | 553.851 | 0.000 | 33.866 | 0.000 | 0.000 | -2869.24 | 0.000 | -9474.03 | -8456.26 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 7610.539 | -138.58 | 0.000 | 0.000 | 3113.846 | 2771.241 | 10464.601 | 3985.226 | 0.000 | 36.752 | 0.000 | 0.000 | -6518.40 | 0.000 | -10369.32 | -9430.42 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 12793.748 | -166.67 | 0.000 | 0.000 | 3123.265 | 2771.241 | 10464.601 | 3994.391 | 0.000 | 52.127 | 0.000 | 0.000 | -6484.60 | 0.000 | -14503.29 | -10210.11 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 10931.952 | -236.17 | 0.000 | 0.000 | 3112.569 | 2771.241 | 10464.601 | 6693.847 | 0.000 | 52.378 | 0.000 | 0.000 | -6441.24 | 0.000 | -14666.18 | -10083.23 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 11132.985 | -310.47 | 0.000 | 0.000 | 3105.788 | 2771.241 | 10464.601 | 7171.401 | 0.000 | 53.845 | 0.000 | 0.000 | -6562.08 | 0.000 | -14622.25 | -9787.44 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 9526.995 | -101.84 | 0.000 | 0.000 | 3113.182 | 2771.241 | 10464.601 | 546.641 | 0.000 | 50.267 | 0.000 | 0.000 | -2836.58 | 0.000 | -13571.78 | -8841.69 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 7566.814 | -165.86 | 0.000 | 0.000 | 3093.534 | 2771.241 | 10464.601 | 3317.517 | 0.000 | 50.069 | 0.000 | 0.000 | -2749.11 | 0.000 | -13800.91 | -8722.15 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 13050.070 | -227.49 | 0.000 | 0.000 | 3119.066 | 2771.241 | 10464.601 | 4556.360 | 0.000 | 54.174 | 0.000 | 0.000 | -6653.33 | 0.000 | -14418.81 | -10211.66 |
HEATEDBSMT | 0.000 | 0.000 | 9556.428 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -9556.43 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5386.268 | 52713.816 | 0.000 | 0.000 | 0.000 | -58100.08 | -0.05 |
Total Facility | 0.000 | 0.000 | 151212.392 | -8532.25 | 0.000 | 0.000 | 55662.629 | 49882.340 | 188362.826 | 78665.537 | 0.000 | 6229.446 | 118154.180 | 0.000 | -95875.58 | 0.000 | -292025.04 | -157813.21 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 02-APR-16:40 | 0.00 | 0.00 | 0.00 | -1.5 | 0.00 | 0.00 | 140.42 | 434.11 | 1371.36 | 5642.31 | 0.00 | 622.69 | 9303.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20-OCT-14:20 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 115.16 | 116.28 | 1091.85 | 2105.49 | 0.00 | 308.95 | 661.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-SEP-15:34 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.15 | 201.55 | 1168.29 | 1186.74 | 0.00 | 486.75 | 2652.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 30-JUN-17:03 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 263.33 | 604.65 | 1664.02 | 5143.18 | 0.00 | 532.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -441.0 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 30-JUN-19:18 | 0.00 | 0.00 | 0.00 | -0.3 | 0.00 | 0.00 | 424.03 | 902.05 | 1664.78 | 0.00 | 0.00 | 0.00 | 996.32 | 0.00 | -184.9 | 0.00 | -325.8 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 30-JUN-16:21 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 139.44 | 434.11 | 1350.56 | 1072.66 | 0.00 | 826.66 | 1100.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 02-APR-16:40 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.44 | 434.11 | 1371.36 | 5613.50 | 0.00 | 465.32 | 124.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 20-OCT-15:04 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 115.16 | 201.55 | 1147.45 | 1548.25 | 0.00 | 204.27 | 1051.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-SEP-15:25 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.39 | 201.55 | 1168.29 | 1506.54 | 0.00 | 469.62 | 2215.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 02-JUN-17:19 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 263.33 | 604.65 | 1664.02 | 5373.24 | 0.00 | 222.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -509.1 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 30-JUN-19:18 | 0.00 | 0.00 | 0.00 | -0.3 | 0.00 | 0.00 | 423.73 | 902.05 | 1664.78 | 0.00 | 0.00 | 0.00 | 1042.80 | 0.00 | -185.6 | 0.00 | -220.0 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 30-JUN-16:36 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 139.91 | 434.11 | 1350.56 | 911.89 | 0.00 | 440.18 | 1524.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 16-SEP-15:15 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.51 | 201.55 | 1168.29 | 1276.32 | 0.00 | 929.48 | 2371.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 16-SEP-15:34 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.71 | 201.55 | 1168.29 | 1145.87 | 0.00 | 465.52 | 3474.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 30-JUN-16:21 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 140.44 | 434.11 | 1350.56 | 5595.33 | 0.00 | 835.51 | 965.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 30-JUN-19:18 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.00 | 902.05 | 1664.78 | 0.00 | 0.00 | 0.00 | 2662.93 | 0.00 | -206.4 | 0.00 | -313.7 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 02-APR-17:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 263.32 | 604.65 | 1685.13 | 298.53 | 0.00 | 419.80 | 2018.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 30-JUN-17:03 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.33 | 604.65 | 1664.02 | 5023.66 | 0.00 | 524.05 | 1239.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-JUN-16:06 | 0.00 | 0.00 | 0.00 | -9.6 | 0.00 | 0.00 | 2508.24 | 7813.98 | 24310.00 | 44000.45 | 0.00 | 14283.24 | 53423.27 | 0.00 | 0.00 | 0.00 | -30684.8 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 22-DEC-05:00 | 0.00 | 0.00 | 4674.12 | 0.00 | 0.00 | 0.00 | 526.29 | 186.05 | 831.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -691.9 | 0.00 | -4487.3 | -1039.2 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-DEC-21:26 | 0.00 | 0.00 | 11226.58 | 0.00 | 0.00 | 0.00 | 555.52 | 682.17 | 1555.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1646.4 | 0.00 | -2311.1 | -10062.0 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23-DEC-13:38 | 0.00 | 0.00 | 15497.63 | 0.00 | 0.00 | 0.00 | 143.73 | 116.28 | 1109.73 | 970.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1480.6 | -16357.3 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23-NOV-16:39 | 0.00 | 0.00 | 8689.21 | 0.00 | 0.00 | 0.00 | 159.07 | 434.11 | 1350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -425.8 | 0.00 | -1577.0 | -8630.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 26-JUL-01:25 | 0.00 | 0.00 | 6954.27 | 0.00 | 0.00 | 0.00 | 546.88 | 62.02 | 891.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1278.1 | 0.00 | -1720.8 | -5455.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23-MAY-08:20 | 0.00 | 0.00 | 11298.73 | 0.00 | 0.00 | 0.00 | 220.41 | 170.54 | 1155.86 | 284.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -725.3 | -12404.6 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 23-JAN-16:38 | 0.00 | 0.00 | 3908.79 | 0.00 | 0.00 | 0.00 | 157.95 | 434.11 | 1350.56 | 76.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1742.2 | -4185.7 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 29-JAN-23:53 | 0.00 | 0.00 | 11003.33 | 0.00 | 0.00 | 0.00 | 556.39 | 155.04 | 1159.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1756.4 | 0.00 | -1920.1 | -9198.0 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 23-DEC-13:28 | 0.00 | 0.00 | 15153.75 | 0.00 | 0.00 | 0.00 | 142.44 | 116.28 | 1109.73 | 504.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1196.1 | -15831.0 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 24-NOV-09:15 | 0.00 | 0.00 | 7022.86 | 0.00 | 0.00 | 0.00 | 127.31 | 116.28 | 1096.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -225.8 | 0.00 | -1263.2 | -6873.6 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 04-JUN-03:00 | 0.00 | 0.00 | 8064.24 | 0.00 | 0.00 | 0.00 | 548.89 | 62.02 | 868.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1407.5 | 0.00 | -1714.4 | -6421.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 24-JAN-06:00 | 0.00 | 0.00 | 7441.77 | 0.00 | 0.00 | 0.00 | 526.31 | 387.60 | 916.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2208.1 | 0.00 | -3793.8 | -3270.1 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 25-DEC-20:45 | 0.00 | 0.00 | 8423.54 | 0.00 | 0.00 | 0.00 | 492.36 | 902.05 | 1628.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1713.8 | 0.00 | -2400.1 | -7332.3 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 23-MAY-08:33 | 0.00 | 0.00 | 14466.97 | 0.00 | 0.00 | 0.00 | 227.65 | 170.54 | 1155.86 | 490.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -771.3 | -15740.4 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 24-JAN-16:04 | 0.00 | 0.00 | 8528.74 | 0.00 | 0.00 | 0.00 | 156.25 | 434.11 | 1350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -418.1 | 0.00 | -2589.6 | -7461.9 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 24-JAN-06:00 | 0.00 | 0.00 | 5651.48 | 0.00 | 0.00 | 0.00 | 526.31 | 387.60 | 916.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -903.4 | 0.00 | -3565.8 | -3012.5 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 30-MAY-08:05 | 0.00 | 0.00 | 17278.62 | 0.00 | 0.00 | 0.00 | 221.59 | 170.54 | 1155.86 | 251.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1156.4 | -17921.4 |
HEATEDBSMT | 30-MAR-18:26 | 0.00 | 0.00 | 4375.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4375.7 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JAN-06:00 | -1312.0 | 0.11 | 100388.29 | -0.1 | 0.00 | 0.00 | 9423.26 | 6976.77 | 16493.20 | 0.00 | 0.00 | 1421.69 | 0.00 | 0.00 | -32165.1 | 0.00 | -60799.1 | -40427.0 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 765.797 | 2.00 | 2.00 | 1.00 | 44.9950 | 765.797 | 0.059 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.950 | 2.00 | 2.00 | 1.00 | 44.9950 | 180.950 | 0.249 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 242.968 | 2.00 | 2.00 | 1.00 | 44.9950 | 242.968 | 0.185 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 339.557 | 2.00 | 2.00 | 1.00 | 44.9950 | 339.557 | 0.133 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 149.262 | 2.00 | 2.00 | 1.00 | 44.9950 | 149.262 | 0.301 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 214.325 | 2.00 | 2.00 | 1.00 | 44.9950 | 214.325 | 0.210 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 361.893 | 2.00 | 2.00 | 1.00 | 44.9950 | 361.893 | 0.124 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.103 | 2.00 | 2.00 | 1.00 | 44.9950 | 176.103 | 0.256 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 239.246 | 2.00 | 2.00 | 1.00 | 44.9950 | 239.246 | 0.188 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 333.465 | 2.00 | 2.00 | 1.00 | 44.9950 | 333.465 | 0.135 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 155.557 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.557 | 0.289 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 207.902 | 2.00 | 2.00 | 1.00 | 44.9950 | 207.902 | 0.216 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 410.139 | 2.00 | 2.00 | 1.00 | 44.9950 | 410.139 | 0.110 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 224.308 | 2.00 | 2.00 | 1.00 | 44.9950 | 224.308 | 0.201 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 272.730 | 2.00 | 2.00 | 1.00 | 44.9950 | 272.730 | 0.165 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 403.645 | 2.00 | 2.00 | 1.00 | 44.9950 | 403.645 | 0.111 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 218.363 | 2.00 | 2.00 | 1.00 | 44.9950 | 218.363 | 0.206 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 255.386 | 2.00 | 2.00 | 1.00 | 44.9950 | 255.386 | 0.176 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 0.00 | 0.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 82.583 | 2.00 | 2.00 | 1.00 | 44.9950 | 82.583 | 1.000 | 1.000 | 44.9950 | 0.54 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 114.895 | 2.00 | 2.00 | 1.00 | 44.9950 | 114.895 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 115.053 | 2.00 | 2.00 | 1.00 | 44.9950 | 115.053 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 85.037 | 2.00 | 2.00 | 1.00 | 44.9950 | 85.037 | 1.000 | 1.000 | 44.9950 | 0.53 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 114.933 | 2.00 | 2.00 | 1.00 | 44.9950 | 114.933 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 95.136 | 2.00 | 2.00 | 1.00 | 44.9950 | 95.136 | 1.000 | 1.000 | 44.9950 | 0.47 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 70.438 | 2.00 | 2.00 | 1.00 | 44.9950 | 70.438 | 1.000 | 1.000 | 44.9950 | 0.64 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 101.284 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.284 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 101.327 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.327 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 70.959 | 2.00 | 2.00 | 1.00 | 44.9950 | 70.959 | 1.000 | 1.000 | 44.9950 | 0.63 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 101.254 | 2.00 | 2.00 | 1.00 | 44.9950 | 101.254 | 1.000 | 1.000 | 44.9950 | 0.44 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 137.096 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.096 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 107.586 | 2.00 | 2.00 | 1.00 | 44.9950 | 107.586 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 137.942 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.942 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 137.928 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.928 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 107.681 | 2.00 | 2.00 | 1.00 | 44.9950 | 107.681 | 1.000 | 1.000 | 44.9950 | 0.42 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 137.900 | 2.00 | 2.00 | 1.00 | 44.9950 | 137.900 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 68.048 | 0.00 | 0.00 | 1.00 | 44.9950 | 68.048 | 1.000 | 1.000 | 44.9950 | 0.66 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 765.797 | 765.7970 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.950 | 180.9499 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 242.968 | 242.9680 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 339.557 | 339.5567 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 149.262 | 149.2618 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 214.325 | 214.3251 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 361.893 | 361.8931 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.103 | 176.1030 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 239.246 | 239.2462 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 333.465 | 333.4651 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 155.557 | 155.5575 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 207.902 | 207.9020 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 255.386 | 255.3858 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 272.730 | 272.7297 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 410.139 | 410.1393 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 218.363 | 218.3632 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 224.308 | 224.3084 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 403.645 | 403.6453 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 44.9950 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 | 765.797 | 765.80 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 | 180.950 | 180.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 | 242.968 | 242.97 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 | 339.557 | 339.56 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 | 149.262 | 149.26 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 | 214.325 | 214.33 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 | 361.893 | 361.89 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 | 176.103 | 176.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 | 239.246 | 239.25 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 | 333.465 | 333.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 | 155.557 | 155.56 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 | 207.902 | 207.90 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 410.14 | 410.139 | 410.14 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 224.31 | 224.308 | 224.31 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 272.73 | 272.730 | 272.73 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 403.65 | 403.645 | 403.65 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 218.36 | 218.363 | 218.36 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 255.39 | 255.386 | 255.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.995 | 44.99 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 82.583 | 82.583 | 82.583 | 44.9950 | 0.545 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 114.895 | 114.895 | 114.895 | 44.9950 | 0.392 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 115.053 | 115.053 | 115.053 | 44.9950 | 0.391 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 85.037 | 85.037 | 85.037 | 44.9950 | 0.529 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 114.933 | 114.933 | 114.933 | 44.9950 | 0.391 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 95.136 | 95.136 | 95.136 | 44.9950 | 0.473 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 70.438 | 70.438 | 70.438 | 44.9950 | 0.639 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 101.284 | 101.284 | 101.284 | 44.9950 | 0.444 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 101.327 | 101.327 | 101.327 | 44.9950 | 0.444 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 70.959 | 70.959 | 70.959 | 44.9950 | 0.634 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 101.254 | 101.254 | 101.254 | 44.9950 | 0.444 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 137.900 | 137.900 | 137.900 | 44.9950 | 0.326 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 137.942 | 137.942 | 137.942 | 44.9950 | 0.326 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 137.096 | 137.096 | 137.096 | 44.9950 | 0.328 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 107.681 | 107.681 | 107.681 | 44.9950 | 0.418 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 107.586 | 107.586 | 107.586 | 44.9950 | 0.418 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 137.928 | 137.928 | 137.928 | 44.9950 | 0.326 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 68.048 | 68.048 | 68.048 | 44.9950 | 0.661 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 82.58 | 82.583 | 82.58 | 82.58 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 114.89 | 114.895 | 114.89 | 114.89 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 115.05 | 115.053 | 115.05 | 115.05 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 85.04 | 85.037 | 85.04 | 85.04 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 114.93 | 114.933 | 114.93 | 114.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 95.14 | 95.136 | 95.14 | 95.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 70.44 | 70.438 | 70.44 | 70.44 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 101.28 | 101.284 | 101.28 | 101.28 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 101.33 | 101.327 | 101.33 | 101.33 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 70.96 | 70.959 | 70.96 | 70.96 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 101.25 | 101.254 | 101.25 | 101.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 137.10 | 137.096 | 137.10 | 137.10 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 107.59 | 107.586 | 107.59 | 107.59 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 137.94 | 137.942 | 137.94 | 137.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 137.93 | 137.928 | 137.93 | 137.93 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 107.68 | 107.681 | 107.68 | 107.68 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 137.90 | 137.900 | 137.90 | 137.90 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 68.05 | 68.048 | 68.05 | 68.05 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 2573.00 |
Number of hours cooling loads not met | 11.25 |
Number of hours not met | 2584.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 1807.19 | 119089.07 | 0.00 | 0.00 |
Space Cooling | 6897.95 | 7985.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 3774.13 | 1809.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2932.17 | 113498.84 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15031.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 116591.41 | 4739.36 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 398091.74 |
Natural Gas | 0.00 | 473935.96 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 872027.70 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 0.18 |
Fans-Interior | 0.10 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 2.99 |
Natural Gas [kWh/ft2] | |
Space Heating | 1.36 |
Service Water Heating | 2.20 |
Miscellaneous | -0.0 |
Subtotal | 3.56 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 5.72 |
Space Heating | 20.72 |
Space Cooling | 2.70 |
Fans-Interior | 1.48 |
Service Water Heating | 33.62 |
Receptacle Equipment | 34.57 |
Miscellaneous | 1.18 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 68.05 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 255.39 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 272.73 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 410.14 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 218.36 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 224.31 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 403.65 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 410.14 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 224.31 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 272.73 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 403.65 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 218.36 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 255.39 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 68.05 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 | 1.70 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 | 0.401994 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 | 0.539772 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 | 0.754351 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 | 0.331596 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 | 0.476139 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 | 0.803973 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 | 0.391226 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 | 0.531503 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 | 0.740818 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 | 0.345583 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 | 0.461870 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 410.14 | 0.911155 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 224.31 | 0.498318 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 272.73 | 0.605889 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 403.65 | 0.896728 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 218.36 | 0.485110 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 255.39 | 0.567359 | 0.798655 |
DX COOLING COIL_UNITHEATEDBSMT | 68.05 | 0.173864 | 0.750675 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 | 765.80 | 765.80 | 1.70 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 | 180.95 | 180.95 | 0.401994 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 | 242.97 | 242.97 | 0.539772 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 | 339.56 | 339.56 | 0.754351 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 | 149.26 | 149.26 | 0.331596 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 | 214.33 | 214.33 | 0.476139 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 | 361.89 | 361.89 | 0.803973 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 | 176.10 | 176.10 | 0.391226 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 | 239.25 | 239.25 | 0.531503 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 | 333.47 | 333.47 | 0.740818 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 | 155.56 | 155.56 | 0.345583 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 | 207.90 | 207.90 | 0.461870 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 410.14 | 410.14 | 410.14 | 0.911155 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 224.31 | 224.31 | 224.31 | 0.498318 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 272.73 | 272.73 | 272.73 | 0.605889 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 403.65 | 403.65 | 403.65 | 0.896728 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 218.36 | 218.36 | 218.36 | 0.485110 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 255.39 | 255.39 | 255.39 | 0.567359 | 1.00 |
ACANDF_UNITHEATEDBSMT | 68.05 | 68.05 | 68.05 | 0.173864 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 43066.07 | 4.35 | 614.77 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 11410.11 | 1.15 | 156.77 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 14767.50 | 1.49 | 205.50 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 19996.26 | 2.02 | 281.28 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 9694.72 | 0.978513 | 131.82 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 13216.94 | 1.33 | 182.99 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 21204.89 | 2.14 | 298.76 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 11147.52 | 1.13 | 152.94 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 14565.71 | 1.47 | 202.55 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 19666.03 | 1.98 | 276.46 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 10035.35 | 1.01 | 136.76 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 12868.97 | 1.30 | 177.92 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 23817.27 | 2.40 | 336.60 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 13757.30 | 1.39 | 190.85 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 16378.68 | 1.65 | 228.85 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 23465.72 | 2.37 | 331.50 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 13435.47 | 1.36 | 186.18 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 15439.78 | 1.56 | 215.23 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 5298.22 | 0.534763 | 67.38 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 765.80 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 180.95 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 242.97 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 339.56 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 149.26 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 214.33 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 361.89 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 176.10 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 239.25 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 333.47 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 155.56 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 207.90 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 410.14 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 224.31 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 272.73 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 403.65 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 218.36 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 255.39 |
SUPPLY FAN_UNITHEATEDBSMT | 68.05 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 4.23 | 79.25 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 4.23 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 314400.12 | 31.62 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:38:54
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 744.000 | 62.761 | 0.000 | 0.000 | 62.761 |
February | 672.000 | 67.983 | 0.125 | 0.017 | 67.983 |
March | 744.000 | 82.403 | 0.250 | 0.032 | 82.403 |
April | 720.000 | 82.616 | 0.125 | 0.016 | 82.616 |
May | 744.000 | 92.832 | 0.000 | 0.000 | 92.832 |
June | 720.000 | 92.669 | 0.000 | 0.000 | 92.669 |
July | 744.000 | 101.466 | 0.000 | 0.000 | 101.466 |
August | 744.000 | 106.955 | 0.000 | 0.000 | 106.955 |
September | 720.000 | 107.286 | 0.000 | 0.000 | 107.286 |
October | 744.000 | 97.196 | 0.000 | 0.000 | 97.196 |
November | 720.000 | 80.963 | 0.000 | 0.000 | 80.963 |
December | 744.000 | 70.371 | 0.000 | 0.000 | 70.371 |
Annual Sum or Average | 8760.000 | 1045.499 | 0.500 | 0.065 | 1045.499 |
Minimum of Months | 672.000 | 62.761 | 0.000 | 0.000 | 62.761 |
Maximum of Months | 744.000 | 107.286 | 0.250 | 0.032 | 107.286 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 11.700 | 0.077 | 613.192 | 4.481 | 4.558 |
February | 67.141 | 1.369 | 414.275 | 2.586 | 3.955 |
March | 100.812 | 2.030 | 405.437 | 2.346 | 4.376 |
April | 62.410 | 1.475 | 392.708 | 1.795 | 3.270 |
May | 88.252 | 1.848 | 292.024 | 1.203 | 3.051 |
June | 106.218 | 2.689 | 296.136 | 1.132 | 3.821 |
July | 152.208 | 1.997 | 197.633 | 0.427 | 2.424 |
August | 224.249 | 4.810 | 132.614 | 0.237 | 5.046 |
September | 289.547 | 7.283 | 97.966 | 0.166 | 7.449 |
October | 205.393 | 4.880 | 231.529 | 0.715 | 5.595 |
November | 93.987 | 1.797 | 362.958 | 1.671 | 3.468 |
December | 41.995 | 0.637 | 495.646 | 3.297 | 3.934 |
Annual Sum or Average | 1443.913 | 30.893 | 3932.118 | 20.056 | 50.949 |
Minimum of Months | 11.700 | 0.077 | 97.966 | 0.166 | 2.424 |
Maximum of Months | 289.547 | 7.283 | 613.192 | 4.481 | 7.449 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 6.312 | 0.043 | 608.467 | 13.496 | 17.809 |
February | 58.871 | 1.540 | 399.381 | 8.151 | 15.324 |
March | 114.449 | 3.028 | 375.146 | 7.261 | 16.211 |
April | 117.820 | 3.057 | 335.854 | 5.513 | 14.245 |
May | 141.853 | 3.725 | 231.427 | 3.785 | 14.479 |
June | 201.341 | 6.311 | 250.833 | 3.835 | 16.161 |
July | 211.280 | 4.541 | 153.500 | 1.853 | 14.073 |
August | 256.394 | 8.489 | 112.479 | 1.268 | 19.158 |
September | 274.999 | 9.744 | 83.875 | 0.983 | 20.134 |
October | 194.843 | 6.268 | 210.808 | 2.995 | 17.938 |
November | 77.034 | 1.866 | 349.698 | 5.831 | 14.780 |
December | 25.140 | 0.446 | 490.217 | 10.342 | 19.056 |
Annual Sum or Average | 1680.336 | 49.058 | 3601.686 | 65.314 | 199.367 |
Minimum of Months | 6.312 | 0.043 | 83.875 | 0.983 | 14.073 |
Maximum of Months | 274.999 | 9.744 | 608.467 | 13.496 | 20.134 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 661.175 | 17.172 | 27.484 |
February | 15.825 | 0.263 | 484.794 | 10.853 | 24.632 |
March | 37.152 | 0.977 | 469.905 | 9.056 | 21.715 |
April | 62.754 | 1.850 | 404.626 | 6.347 | 18.873 |
May | 114.740 | 3.576 | 291.372 | 4.191 | 18.130 |
June | 149.739 | 6.408 | 300.317 | 4.108 | 17.178 |
July | 186.938 | 6.212 | 230.549 | 2.233 | 16.009 |
August | 197.025 | 7.524 | 217.894 | 1.865 | 16.301 |
September | 173.083 | 5.854 | 202.756 | 1.637 | 12.884 |
October | 83.054 | 2.123 | 350.314 | 4.389 | 16.608 |
November | 5.594 | 0.081 | 464.110 | 8.301 | 27.681 |
December | 0.000 | 0.000 | 600.846 | 14.258 | 30.697 |
Annual Sum or Average | 1025.903 | 34.868 | 4678.659 | 84.410 | 248.193 |
Minimum of Months | 0.000 | 0.000 | 202.756 | 1.637 | 12.884 |
Maximum of Months | 197.025 | 7.524 | 661.175 | 17.172 | 30.697 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.364 | 6.986 | 7.115 |
February | 3.333 | 0.012 | 584.153 | 4.407 | 6.171 |
March | 13.021 | 0.170 | 541.965 | 3.543 | 6.538 |
April | 29.048 | 0.555 | 463.970 | 2.508 | 6.631 |
May | 77.758 | 1.257 | 324.952 | 1.512 | 5.165 |
June | 87.025 | 2.190 | 296.511 | 1.334 | 4.432 |
July | 100.796 | 1.017 | 220.365 | 0.579 | 1.860 |
August | 142.598 | 2.420 | 180.235 | 0.411 | 2.854 |
September | 99.971 | 1.648 | 154.853 | 0.331 | 1.997 |
October | 53.670 | 0.806 | 370.284 | 1.419 | 3.533 |
November | 0.000 | 0.000 | 591.468 | 3.248 | 4.734 |
December | 0.000 | 0.000 | 725.819 | 5.878 | 6.648 |
Annual Sum or Average | 607.219 | 10.076 | 5195.938 | 32.155 | 57.678 |
Minimum of Months | 0.000 | 0.000 | 154.853 | 0.331 | 1.860 |
Maximum of Months | 142.598 | 2.420 | 741.364 | 6.986 | 7.115 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.667 | 17.837 | 17.864 |
February | 2.513 | 0.006 | 599.033 | 11.606 | 12.374 |
March | 24.016 | 0.425 | 517.631 | 9.363 | 12.707 |
April | 63.785 | 1.336 | 429.696 | 6.657 | 10.578 |
May | 111.330 | 2.846 | 271.854 | 4.264 | 11.872 |
June | 185.713 | 5.604 | 267.063 | 4.080 | 14.484 |
July | 191.364 | 3.354 | 165.321 | 2.051 | 11.688 |
August | 223.798 | 5.852 | 141.542 | 1.610 | 14.609 |
September | 167.861 | 3.734 | 122.833 | 1.394 | 12.435 |
October | 80.622 | 1.523 | 322.598 | 4.231 | 12.893 |
November | 1.625 | 0.004 | 599.824 | 8.800 | 12.924 |
December | 0.000 | 0.000 | 739.146 | 15.432 | 15.796 |
Annual Sum or Average | 1052.627 | 24.685 | 4920.208 | 87.325 | 160.224 |
Minimum of Months | 0.000 | 0.000 | 122.833 | 1.394 | 10.578 |
Maximum of Months | 223.798 | 5.852 | 743.667 | 17.837 | 17.864 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 20.313 | 0.251 | 600.312 | 11.100 | 11.352 |
February | 99.812 | 2.913 | 396.625 | 6.680 | 9.815 |
March | 150.136 | 5.093 | 358.863 | 5.539 | 13.688 |
April | 153.961 | 5.057 | 292.178 | 3.617 | 14.528 |
May | 193.970 | 6.116 | 206.609 | 2.402 | 14.963 |
June | 208.782 | 8.516 | 233.344 | 2.458 | 15.418 |
July | 255.875 | 9.539 | 160.490 | 1.025 | 14.480 |
August | 288.863 | 12.214 | 132.890 | 0.777 | 15.522 |
September | 315.862 | 14.125 | 111.562 | 0.638 | 16.524 |
October | 235.822 | 8.597 | 230.536 | 2.231 | 13.318 |
November | 112.621 | 3.066 | 372.742 | 4.664 | 7.924 |
December | 60.967 | 1.269 | 504.208 | 8.602 | 9.871 |
Annual Sum or Average | 2096.983 | 76.757 | 3600.360 | 49.734 | 157.404 |
Minimum of Months | 20.313 | 0.251 | 111.562 | 0.638 | 7.924 |
Maximum of Months | 315.862 | 14.125 | 600.312 | 11.100 | 16.524 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 20.817 | 0.117 | 544.367 | 3.323 | 3.782 |
February | 103.704 | 1.832 | 337.776 | 1.882 | 3.921 |
March | 150.506 | 2.838 | 333.604 | 1.581 | 4.775 |
April | 114.053 | 2.078 | 281.483 | 1.088 | 3.476 |
May | 135.290 | 2.494 | 191.096 | 0.696 | 3.249 |
June | 164.718 | 3.488 | 209.363 | 0.643 | 4.250 |
July | 226.008 | 3.453 | 103.522 | 0.151 | 3.635 |
August | 298.413 | 6.399 | 59.014 | 0.079 | 6.482 |
September | 357.554 | 9.434 | 34.878 | 0.049 | 9.483 |
October | 272.145 | 6.234 | 157.632 | 0.429 | 6.667 |
November | 137.792 | 2.533 | 296.196 | 1.112 | 3.684 |
December | 66.120 | 0.902 | 438.951 | 2.411 | 3.331 |
Annual Sum or Average | 2047.120 | 41.801 | 2987.880 | 13.443 | 56.736 |
Minimum of Months | 20.817 | 0.117 | 34.878 | 0.049 | 3.249 |
Maximum of Months | 357.554 | 9.434 | 544.367 | 3.323 | 9.483 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 9.158 | 0.056 | 542.646 | 10.215 | 17.909 |
February | 71.632 | 1.802 | 325.975 | 5.833 | 15.245 |
March | 145.863 | 3.684 | 308.063 | 4.934 | 15.352 |
April | 145.370 | 3.790 | 240.542 | 3.283 | 14.722 |
May | 189.262 | 4.500 | 139.062 | 2.036 | 15.490 |
June | 234.859 | 7.184 | 172.542 | 2.175 | 16.587 |
July | 276.850 | 5.878 | 72.750 | 0.718 | 15.662 |
August | 307.677 | 9.699 | 48.500 | 0.441 | 19.864 |
September | 332.163 | 11.208 | 28.833 | 0.305 | 20.477 |
October | 232.569 | 7.149 | 140.287 | 1.769 | 18.382 |
November | 104.543 | 2.278 | 283.510 | 3.965 | 14.428 |
December | 32.076 | 0.531 | 434.295 | 7.732 | 16.744 |
Annual Sum or Average | 2082.020 | 57.761 | 2737.005 | 43.406 | 200.863 |
Minimum of Months | 9.158 | 0.056 | 28.833 | 0.305 | 14.428 |
Maximum of Months | 332.163 | 11.208 | 542.646 | 10.215 | 20.477 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 637.648 | 13.532 | 26.544 |
February | 19.500 | 0.321 | 436.318 | 8.134 | 24.010 |
March | 50.364 | 1.179 | 408.902 | 6.395 | 18.464 |
April | 91.796 | 2.474 | 334.355 | 4.090 | 16.725 |
May | 153.881 | 4.450 | 233.577 | 2.569 | 15.880 |
June | 181.721 | 7.318 | 240.849 | 2.504 | 16.349 |
July | 229.313 | 7.712 | 169.402 | 1.138 | 14.991 |
August | 242.892 | 8.799 | 157.126 | 0.951 | 15.035 |
September | 230.667 | 7.201 | 137.401 | 0.838 | 12.444 |
October | 111.616 | 2.517 | 287.781 | 2.939 | 15.299 |
November | 8.950 | 0.078 | 412.123 | 6.091 | 25.265 |
December | 0.000 | 0.000 | 558.309 | 11.023 | 31.755 |
Annual Sum or Average | 1320.699 | 42.049 | 4013.791 | 60.203 | 232.762 |
Minimum of Months | 0.000 | 0.000 | 137.401 | 0.838 | 12.444 |
Maximum of Months | 242.892 | 8.799 | 637.648 | 13.532 | 31.755 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 735.910 | 5.046 | 5.184 |
February | 8.667 | 0.056 | 542.598 | 3.030 | 4.876 |
March | 16.975 | 0.257 | 460.835 | 2.179 | 4.655 |
April | 46.407 | 0.830 | 362.540 | 1.347 | 3.354 |
May | 103.650 | 1.820 | 217.964 | 0.753 | 2.821 |
June | 143.268 | 2.970 | 213.925 | 0.639 | 3.852 |
July | 181.625 | 2.375 | 109.202 | 0.160 | 2.547 |
August | 218.054 | 3.722 | 79.021 | 0.120 | 3.843 |
September | 190.533 | 2.830 | 65.058 | 0.088 | 2.924 |
October | 85.218 | 1.184 | 273.365 | 0.801 | 2.654 |
November | 1.500 | 0.003 | 508.707 | 2.122 | 3.380 |
December | 0.000 | 0.000 | 699.644 | 4.219 | 5.008 |
Annual Sum or Average | 995.898 | 16.047 | 4268.769 | 20.504 | 45.096 |
Minimum of Months | 0.000 | 0.000 | 65.058 | 0.088 | 2.547 |
Maximum of Months | 218.054 | 3.722 | 735.910 | 5.046 | 5.184 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 738.142 | 13.639 | 14.078 |
February | 5.792 | 0.028 | 560.575 | 8.341 | 10.964 |
March | 35.795 | 0.552 | 427.262 | 6.071 | 11.324 |
April | 90.344 | 1.720 | 301.271 | 3.740 | 11.966 |
May | 153.786 | 3.430 | 154.055 | 2.171 | 13.280 |
June | 233.058 | 6.481 | 177.780 | 2.169 | 14.855 |
July | 252.228 | 4.642 | 76.583 | 0.751 | 13.209 |
August | 278.126 | 6.999 | 62.642 | 0.564 | 15.924 |
September | 231.667 | 4.652 | 47.425 | 0.472 | 13.099 |
October | 93.945 | 1.807 | 226.050 | 2.505 | 12.362 |
November | 2.028 | 0.007 | 498.650 | 5.955 | 13.089 |
December | 0.000 | 0.000 | 712.269 | 11.623 | 13.995 |
Annual Sum or Average | 1376.769 | 30.320 | 3982.704 | 58.001 | 158.147 |
Minimum of Months | 0.000 | 0.000 | 47.425 | 0.472 | 10.964 |
Maximum of Months | 278.126 | 6.999 | 738.142 | 13.639 | 15.924 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 4.104 | 0.017 | 676.247 | 22.614 | 22.651 |
February | 62.604 | 2.019 | 482.583 | 14.214 | 17.125 |
March | 107.196 | 3.978 | 420.083 | 12.012 | 23.279 |
April | 108.762 | 4.201 | 356.068 | 8.622 | 25.962 |
May | 142.802 | 5.260 | 250.677 | 5.958 | 28.364 |
June | 167.054 | 8.314 | 276.918 | 6.157 | 27.202 |
July | 210.500 | 8.557 | 206.319 | 3.436 | 27.701 |
August | 234.692 | 11.383 | 190.608 | 2.818 | 27.774 |
September | 253.435 | 12.504 | 158.462 | 2.347 | 26.967 |
October | 172.969 | 6.834 | 301.563 | 5.944 | 22.476 |
November | 69.242 | 2.073 | 463.750 | 10.984 | 14.148 |
December | 23.833 | 0.511 | 612.625 | 18.409 | 18.997 |
Annual Sum or Average | 1557.192 | 65.650 | 4395.904 | 113.515 | 282.646 |
Minimum of Months | 4.104 | 0.017 | 158.462 | 2.347 | 14.148 |
Maximum of Months | 253.435 | 12.504 | 676.247 | 22.614 | 28.364 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 659.815 | 7.412 | 7.618 |
February | 49.992 | 1.207 | 459.458 | 4.480 | 6.241 |
March | 91.792 | 2.182 | 430.854 | 3.961 | 6.427 |
April | 78.696 | 1.996 | 411.369 | 3.093 | 6.263 |
May | 97.032 | 2.370 | 324.946 | 2.139 | 5.119 |
June | 128.875 | 3.908 | 324.728 | 2.076 | 6.985 |
July | 168.083 | 3.216 | 262.951 | 1.085 | 4.531 |
August | 217.650 | 6.058 | 219.911 | 0.753 | 6.889 |
September | 272.121 | 7.873 | 170.047 | 0.576 | 8.464 |
October | 173.320 | 4.659 | 300.388 | 1.674 | 6.412 |
November | 78.958 | 1.539 | 415.837 | 3.203 | 4.789 |
December | 24.725 | 0.307 | 566.212 | 5.769 | 6.089 |
Annual Sum or Average | 1381.244 | 35.315 | 4546.518 | 36.221 | 75.826 |
Minimum of Months | 0.000 | 0.000 | 170.047 | 0.576 | 4.531 |
Maximum of Months | 272.121 | 7.873 | 659.815 | 7.412 | 8.464 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 660.064 | 16.173 | 18.587 |
February | 48.343 | 1.316 | 454.917 | 9.906 | 15.654 |
March | 100.589 | 2.835 | 404.161 | 8.510 | 16.355 |
April | 110.453 | 3.290 | 369.792 | 6.370 | 14.218 |
May | 141.335 | 4.054 | 269.286 | 4.452 | 14.531 |
June | 188.550 | 6.962 | 276.000 | 4.492 | 16.576 |
July | 205.578 | 5.200 | 197.917 | 2.459 | 14.264 |
August | 250.695 | 9.108 | 169.146 | 1.973 | 17.640 |
September | 267.179 | 9.844 | 139.107 | 1.616 | 19.347 |
October | 169.827 | 5.732 | 270.267 | 4.112 | 17.149 |
November | 65.021 | 1.500 | 404.775 | 7.393 | 15.060 |
December | 14.875 | 0.182 | 563.967 | 12.890 | 19.195 |
Annual Sum or Average | 1562.444 | 50.022 | 4179.398 | 80.343 | 198.576 |
Minimum of Months | 0.000 | 0.000 | 139.107 | 1.616 | 14.218 |
Maximum of Months | 267.179 | 9.844 | 660.064 | 16.173 | 19.347 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 684.189 | 21.786 | 30.422 |
February | 19.846 | 0.506 | 507.494 | 13.812 | 24.540 |
March | 57.804 | 1.834 | 453.830 | 11.112 | 24.038 |
April | 87.654 | 3.174 | 395.761 | 7.963 | 21.980 |
May | 134.268 | 4.788 | 311.416 | 5.501 | 21.031 |
June | 163.327 | 8.129 | 303.884 | 5.345 | 22.630 |
July | 204.208 | 8.094 | 251.964 | 3.136 | 21.246 |
August | 218.842 | 10.109 | 231.510 | 2.671 | 22.457 |
September | 208.888 | 8.673 | 219.640 | 2.379 | 18.592 |
October | 97.107 | 3.112 | 364.220 | 5.959 | 20.797 |
November | 12.310 | 0.203 | 481.208 | 10.901 | 28.678 |
December | 0.000 | 0.000 | 633.667 | 18.584 | 32.938 |
Annual Sum or Average | 1204.254 | 48.622 | 4838.784 | 109.148 | 289.348 |
Minimum of Months | 0.000 | 0.000 | 219.640 | 2.379 | 18.592 |
Maximum of Months | 218.842 | 10.109 | 684.189 | 21.786 | 32.938 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 742.211 | 9.328 | 9.444 |
February | 13.817 | 0.150 | 569.622 | 5.926 | 7.882 |
March | 32.833 | 0.588 | 507.400 | 4.694 | 7.647 |
April | 50.521 | 1.384 | 449.595 | 3.401 | 7.637 |
May | 86.773 | 2.138 | 338.734 | 2.205 | 5.163 |
June | 126.628 | 3.880 | 325.842 | 2.056 | 6.813 |
July | 162.533 | 2.963 | 267.607 | 1.089 | 4.255 |
August | 196.038 | 5.061 | 238.986 | 0.828 | 5.927 |
September | 180.788 | 4.158 | 199.365 | 0.689 | 4.855 |
October | 83.994 | 1.738 | 394.597 | 2.317 | 4.775 |
November | 6.000 | 0.029 | 572.829 | 4.590 | 5.545 |
December | 0.000 | 0.000 | 729.154 | 8.069 | 8.823 |
Annual Sum or Average | 939.925 | 22.089 | 5335.944 | 45.193 | 78.767 |
Minimum of Months | 0.000 | 0.000 | 199.365 | 0.689 | 4.255 |
Maximum of Months | 196.038 | 5.061 | 742.211 | 9.328 | 9.444 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.610 | 18.638 | 18.675 |
February | 15.563 | 0.168 | 589.308 | 11.951 | 13.644 |
March | 45.747 | 1.029 | 494.165 | 9.426 | 13.632 |
April | 88.025 | 2.337 | 425.312 | 6.689 | 12.262 |
May | 132.178 | 3.717 | 279.464 | 4.428 | 13.533 |
June | 188.569 | 6.850 | 275.277 | 4.354 | 16.073 |
July | 200.948 | 4.944 | 200.583 | 2.412 | 13.534 |
August | 238.568 | 8.055 | 179.648 | 2.043 | 15.989 |
September | 209.168 | 6.143 | 154.458 | 1.776 | 15.308 |
October | 85.193 | 2.420 | 356.276 | 4.908 | 13.922 |
November | 7.375 | 0.069 | 571.988 | 9.401 | 14.084 |
December | 0.000 | 0.000 | 740.733 | 16.307 | 16.583 |
Annual Sum or Average | 1211.334 | 35.732 | 5010.823 | 92.333 | 177.238 |
Minimum of Months | 0.000 | 0.000 | 154.458 | 1.776 | 12.262 |
Maximum of Months | 238.568 | 8.055 | 743.610 | 18.638 | 18.675 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 10.646 | 10.646 |
February | 0.000 | 0.000 | 622.013 | 7.882 | 9.165 |
March | 0.000 | 0.000 | 575.775 | 6.925 | 11.242 |
April | 0.000 | 0.000 | 550.587 | 5.481 | 9.829 |
May | 0.000 | 0.000 | 85.320 | 0.116 | 0.770 |
June | 0.000 | 0.000 | 3.000 | 0.001 | 0.001 |
July | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
August | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
September | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 11.483 | 0.006 | 0.006 |
November | 0.000 | 0.000 | 629.187 | 5.757 | 8.025 |
December | 0.000 | 0.000 | 744.000 | 9.122 | 9.122 |
Annual Sum or Average | 0.000 | 0.000 | 3965.365 | 45.937 | 58.807 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 0.000 | 0.000 | 744.000 | 10.646 | 11.242 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.48 |
February | 0.00 | 0.00 | 0.58 |
March | 0.00 | 0.00 | 0.64 |
April | 0.00 | 0.00 | 0.66 |
May | 0.00 | 0.00 | 0.71 |
June | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.00 | 0.79 |
August | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.00 | 0.87 |
October | 0.00 | 0.00 | 0.75 |
November | 0.00 | 0.00 | 0.65 |
December | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.69 |
Minimum of Months | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.00 | 0.00 | 0.87 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.01 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.03 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.08 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.05 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.01 |
August | 0.00 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.02 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.04 |
July | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.03 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.04 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.07 |
July | 0.00 | 0.00 | 0.07 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.11 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.03 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.08 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.09 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.07 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.01 |
June | 0.00 | 0.00 | 0.02 |
July | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.03 |
September | 0.00 | 0.00 | 0.02 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.03 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.03 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.04 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.05 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.02 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.09 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.10 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.05 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.07 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.08 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.06 |
August | 0.00 | 0.00 | 0.08 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.08 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.02 |
June | 0.00 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.04 |
September | 0.00 | 0.00 | 0.03 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.04 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.05 |
July | 0.00 | 0.00 | 0.04 |
August | 0.00 | 0.00 | 0.06 |
September | 0.00 | 0.00 | 0.05 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.06 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:38:54
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1554.09 | 1157.06 |
February | 0.00 | 0.00 | 1560.82 | 1049.61 |
March | 0.00 | 0.00 | 1545.05 | 1150.33 |
April | 0.00 | 0.00 | 1518.58 | 1094.16 |
May | 0.00 | 0.00 | 1477.36 | 1099.94 |
June | 0.00 | 0.00 | 1441.96 | 1038.95 |
July | 0.00 | 0.00 | 1419.46 | 1056.83 |
August | 0.00 | 0.00 | 1412.57 | 1051.70 |
September | 0.00 | 0.00 | 1429.12 | 1029.70 |
October | 0.00 | 0.00 | 1457.95 | 1085.48 |
November | 0.00 | 0.00 | 1494.79 | 1077.01 |
December | 0.00 | 0.00 | 1532.68 | 1141.12 |
Annual Sum or Average | 0.00 | 0.00 | 1486.60 | 13031.88 |
Minimum of Months | 0.00 | 0.00 | 1412.57 | 1029.70 |
Maximum of Months | 0.00 | 0.00 | 1560.82 | 1157.06 |