Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37

Tabular Output Report in Format: HTML

Building: MF+CZ3CWH+USA_CA_San.Francisco.Intl.AP.724940+elecres+heatedbsmt+IECC_2012

Environment: ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940

Simulation Timestamp: 2019-02-14 08:37:21


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 596578.49 15.29 20.29
Net Site Energy 596578.49 15.29 20.29
Total Source Energy 1889364.08 48.44 64.25
Net Source Energy 1889364.08 48.44 64.25


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 66867.94 0.00 0.00 0.00 0.00 0.00
Cooling 14186.69 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 8724.99 0.00 0.00 0.00 0.00 0.00
Interior Equipment 299910.33 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6410.71 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 156269.80 0.00 0.00 0.00 0.00 377715.79
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 596578.49 0.00 0.00 0.00 0.00 377715.79
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 66867.94 0.00 0.00 0.00 0.00 0.00
Cooling General 14186.69 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44208.02 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 7094.15 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1630.84 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 9491.86 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 4847.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 6410.71 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 156269.80 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 377715.79
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.80 0.00 0.00 0.00 0.00 0.00
HVAC 8.29 0.00 0.00 0.00 0.00 12.85
Other 10.20 0.00 0.00 0.00 0.00 0.00
Total 20.29 0.00 0.00 0.00 0.00 12.85


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.36 0.00 0.00 0.00 0.00 0.00
HVAC 6.25 0.00 0.00 0.00 0.00 9.68
Other 7.69 0.00 0.00 0.00 0.00 0.00
Total 15.29 0.00 0.00 0.00 0.00 9.68


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 596578.490 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 596578.490 100.00
     
Total On-Site and Utility Electric Sources 596578.490 100.00
Total Electricity End Uses 596578.490 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 377715.79 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 377715.79 100.00
Total Water End Uses 377715.79 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 7.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 18.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37
RunPeriod ANNUAL
Weather File San Francisco Intl Ap CA USA TMY3 WMO#=724940
Latitude [deg] 37.62
Longitude [deg] -122.4
Elevation [ft] 6.56
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6659 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6659 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.3689 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.4894 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 24-JAN-07:15 - - - - 01-JAN-08:45
Heating 60.97 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.19 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.23 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.69 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2.94 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 126.34 0.00 0.00 0.00 0.00 1.37
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 230.36 0.00 0.00 0.00 0.00 1.37


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 60.97 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 6.19 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.23 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.78 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.61 0.00 0.00 0.00 0.00 0.00
  electric_dryer 3.48 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 2.94 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 126.34 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.37
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 211770.77 0.00 0.00 0.00 0.00
Cooling 44929.25 0.00 0.00 0.00 0.00
Interior Lighting 140006.80 0.00 0.00 0.00 0.00
Exterior Lighting 27632.04 0.00 0.00 0.00 0.00
Interior Equipment 949816.03 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 20302.72 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 494906.47 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1889364.08 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 7.20 0.00 0.00 0.00 0.00
Cooling 1.53 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 0.69 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 16.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 64.25 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 7.20 0.00 0.00 0.00 0.00
Cooling 1.53 0.00 0.00 0.00 0.00
Interior Lighting 4.76 0.00 0.00 0.00 0.00
Exterior Lighting 0.94 0.00 0.00 0.00 0.00
Interior Equipment 32.30 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 0.69 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 16.83 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 64.25 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 38.84 0.00 38.84 Wetbulb [F] 433.09 150.00
SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 82.94 15.30 62.96 Wetbulb [F] 1161.47 310.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.218 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.218 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.218 0.882              
North Total or Average           531.68 0.350 0.218 0.882              
Non-North Total or Average           1595.05 0.350 0.218 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.4836 1200.55 580.62 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 522.42
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3329 43219.92 14389.84               12947.46


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 26.35 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 115.43
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 8.64 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 26.54
Exterior Lighting Total 629.94           2555.34



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10084.15 8053.76 2030.39 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   4025.75 3215.19 810.56 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   5051.46 4034.37 1017.08 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7421.14 5926.93 1494.21 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   3562.25 2845.01 717.24 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   4828.55 3856.35 972.20 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7964.60 6360.97 1603.63 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   4179.76 3338.19 841.57 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   5112.60 4083.20 1029.39 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7375.60 5890.56 1485.04 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   3721.00 2971.79 749.20 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   4742.75 3787.82 954.93 0.80 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8824.14 7047.44 1776.69 0.80 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   5075.62 4053.67 1021.95 0.80 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   5528.32 4415.22 1113.10 0.80 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8695.41 6944.64 1750.78 0.80 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   4991.45 3986.45 1005.00 0.80 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   5403.74 4315.72 1088.01 0.80 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   2032.72 1525.91 506.81 0.75 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   0.8 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.6 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.3 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   0.7 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.4 3.26 11.12 11.77 11.27
DX COOLING COIL_UNITHEATEDBSMT   0.2 3.35 11.43 12.11 11.76
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   4050.39 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   4704.77 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   5835.08 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5834.78 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   4703.45 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   5830.90 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5565.17 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   4421.49 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5567.74 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5567.53 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   4421.04 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5564.62 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   6839.60 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   5685.85 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   6841.89 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   6841.49 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   5685.74 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   6839.80 1.00
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT Coil:Heating:Electric   5203.50 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 378.27 142.68 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 151.01 56.96 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 189.48 71.47 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 278.37 105.00 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 133.62 50.40 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 181.12 68.32 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 298.76 112.69 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 156.79 59.14 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 191.78 72.34 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 276.67 104.36 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 139.58 52.65 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 177.90 67.10 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 331.00 124.85 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 190.39 71.81 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 207.37 78.22 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 326.17 123.03 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 187.23 70.62 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 202.70 76.46 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 66.30 25.01 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8885.28 8885.28 7.40 378.266 378.266 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 74.98 74.98 0.00815 80.03 0.00771 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3547.13 3547.13 2.95 151.010 151.010 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00843 76.97 0.00771 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4450.89 4450.89 3.71 189.485 189.485 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 13:45:00 74.98 74.98 0.00812 82.75 0.00771 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6538.85 6538.85 5.45 278.374 278.374 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00821 79.65 0.00771 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3138.74 3138.74 2.61 133.623 133.623 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00846 76.97 0.00771 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4254.52 4254.52 3.54 181.123 181.123 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 09:45:00 74.98 74.98 0.00817 76.48 0.00771 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7017.70 7017.70 5.85 298.760 298.760 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00821 79.65 0.00771 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3682.83 3682.83 3.07 156.787 156.787 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00845 76.97 0.00771 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4504.73 4504.73 3.75 191.778 191.778 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 74.98 74.98 0.00814 82.94 0.00771 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6498.71 6498.71 5.41 276.666 276.666 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 74.98 74.98 0.00824 79.27 0.00771 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3278.61 3278.61 2.73 139.578 139.578 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00849 76.97 0.00771 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4178.91 4178.91 3.48 177.905 177.905 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 10:00:00 74.98 74.98 0.00818 77.13 0.00771 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4761.29 4761.29 3.97 202.699 202.699 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 18:15:00 74.98 74.98 0.00829 78.69 0.00771 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 4871.06 4871.06 4.06 207.372 207.372 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 74.98 74.98 0.00810 82.94 0.00771 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7775.05 7775.05 6.48 331.002 331.002 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00819 79.65 0.00771 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4398.01 4398.01 3.66 187.234 187.234 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00838 76.97 0.00771 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4472.18 4472.18 3.73 190.391 190.391 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 74.98 74.98 0.00837 76.97 0.00771 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7661.63 7661.63 6.38 326.173 326.173 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB 8/21 17:45:00 74.98 74.98 0.00819 79.65 0.00771 44.995 0.00
HEATEDBSMT 0.00 0.00 0.00 0.000 44.995 SAN FRANCISCO INTL AP ANN CLG .4% CONDNS DB=>MWB   74.41 32.00 0.00000 82.94 0.00771 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2328.89 2328.89 1.94 42.396 44.995 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00656 38.84 0.00496 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3135.71 3135.71 2.61 57.084 57.084 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00676 38.84 0.00496 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4282.75 4282.75 3.57 77.964 77.964 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00691 38.84 0.00496 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4282.45 4282.45 3.57 77.958 77.958 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00691 38.84 0.00496 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3134.37 3134.37 2.61 57.059 57.059 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00676 38.84 0.00496 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4278.51 4278.51 3.56 77.887 77.887 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00691 38.84 0.00496 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4008.82 4008.82 3.34 72.978 72.978 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2848.22 2848.22 2.37 51.851 51.851 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00689 38.84 0.00496 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4011.43 4011.43 3.34 73.026 73.026 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4011.22 4011.22 3.34 73.022 73.022 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2847.76 2847.76 2.37 51.842 51.842 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00689 38.84 0.00496 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4008.26 4008.26 3.34 72.968 72.968 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5302.33 5302.33 4.42 96.524 96.524 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 5304.45 5304.45 4.42 96.563 96.563 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5302.13 5302.13 4.42 96.521 96.521 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4131.19 4131.19 3.44 75.205 75.205 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00692 38.84 0.00496 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4131.31 4131.31 3.44 75.207 75.207 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00692 38.84 0.00496 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5304.04 5304.04 4.42 96.555 96.555 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00703 38.84 0.00496 44.995 0.00
HEATEDBSMT 3641.65 3641.65 0.47 66.298 66.298 SAN FRANCISCO INTL AP ANN HTG 99.6% CONDNS DB 1/21 07:45:00 72.00 72.00 0.00800 38.84 0.00496 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 378.27 378.27 44.99 44.99
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 151.01 151.01 57.08 57.08
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 189.48 189.48 77.96 77.96
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 278.37 278.37 77.96 77.96
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.62 133.62 57.06 57.06
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 181.12 181.12 77.89 77.89
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 298.76 298.76 72.98 72.98
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 156.79 156.79 51.85 51.85
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 191.78 191.78 73.03 73.03
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 276.67 276.67 73.02 73.02
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 139.58 139.58 51.84 51.84
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 177.90 177.90 72.97 72.97
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 331.00 331.00 96.52 96.52
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.39 190.39 75.21 75.21
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 207.37 207.37 96.56 96.56
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 326.17 326.17 96.56 96.56
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 187.23 187.23 75.21 75.21
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 202.70 202.70 96.52 96.52
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.99 66.30 66.30


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 758.50 5412.75 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 465.75 5886.50 8.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.75 5888.00 11.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 613.00 6869.25 13.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 217.50 7050.50 10.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 345.25 6724.75 12.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1010.75 5767.25 14.50
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 561.00 5517.00 7.25
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.00 5595.25 15.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 663.75 6629.75 16.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 315.50 6623.25 9.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 392.50 6450.25 15.50
LIVING_UNIT3_BACKROW_TOPFLOOR 586.50 6689.25 14.25
LIVING_UNIT3_FRONTROW_TOPFLOOR 761.00 6178.75 14.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 979.25 6353.75 14.00
LIVING_UNIT2_BACKROW_TOPFLOOR 509.25 6947.00 15.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 655.50 6285.25 15.00
LIVING_UNIT1_BACKROW_TOPFLOOR 788.00 6834.75 14.50
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 1406.50 7524.75 18.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 3.00 0.00 3.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 1.75 0.00 1.75
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 5.50 0.00 5.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 3.00 0.00 3.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 7.75 0.00 7.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.130 0.000 0.274
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.113 0.000 0.273
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.128 0.000 0.273
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.127 0.000 0.273
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.112 0.000 0.273
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.127 0.000 0.273
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.056 0.000 0.273
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.041 0.000 0.273
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.056 0.000 0.273
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.056 0.000 0.273
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.041 0.000 0.273
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.056 0.000 0.273
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.127 0.000 0.273
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.128 0.000 0.273
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.127 0.000 0.273
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.112 0.000 0.273
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.112 0.000 0.273
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.127 0.000 0.273
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1846
Defaulted Fields 455
Fields with Defaults 4639
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
Electricity:Building 100783.92 6307.14 02-JAN-03:15 19201.42 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
General:InteriorLights:Electricity 12947.46 289.95 01-JAN-00:15 4217.42 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5599.11 350.40 02-JAN-03:15 1066.75 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 719.30 16.11 01-JAN-00:15 234.30 01-JAN-19:15
InteriorEquipment:Electricity 87836.46 5989.55 02-JAN-04:15 15395.85 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 2779.94 25.45 02-JAN-03:15 887.02 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1419.57 13.63 02-JAN-02:15 384.46 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4879.80 332.75 02-JAN-04:15 855.33 01-JAN-18:15
Electricity:Plant 45767.64 0.00 01-JAN-00:15 37245.27 05-FEB-08:30
WaterSystems:Electricity 45767.64 0.00 01-JAN-00:15 37245.27 05-FEB-08:30
Water Heater:WaterSystems:Electricity 45767.64 0.00 01-JAN-00:15 37245.27 05-FEB-08:30
Fans:Electricity 1877.54 0.99 04-JUN-02:00 1455.22 30-JUN-18:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
ElectricityPurchased:Plant 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
Cogeneration:ElectricityPurchased 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
ElectricityNet:Plant 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
Cogeneration:ElectricityNet 174723.37 6810.52 26-MAY-04:00 67465.96 24-JAN-07:15
ExteriorLights:Electricity 2555.34 20.06 01-JAN-09:15 629.94 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2077.71 0.00 01-JAN-06:15 474.36 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 477.63 10.70 01-JAN-00:15 155.58 01-JAN-19:15
Electricity:HVAC 25616.48 4.83 04-JUN-02:00 20003.21 24-JAN-06:00
General:Fans:Electricity 1877.54 0.99 04-JUN-02:00 1455.22 30-JUN-18:15
Heating:Electricity 19584.00 0.00 01-MAY-08:15 19077.23 24-JAN-06:00
Cooling:Electricity 4154.94 0.00 01-JAN-00:15 6660.59 02-JUN-15:00
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
Water:Plant 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
WaterSystems:Water 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
MainsWater:Plant 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
WaterSystems:MainsWater 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45
Domestic Hot Water:WaterSystems:MainsWater 50500.66 0.01 20-NOV-03:00 0.18 01-JAN-08:45


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
PlantLoopHeatingDemand:Plant 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 402638.47 1708.62 03-MAY-02:15 214732.04 30-JUN-18:15
EnergyTransfer:Building 126429.25 51.12 04-JUN-02:00 89307.35 30-JUN-18:15
EnergyTransfer:Zone:HEATEDBSMT 9189.23 0.00 01-MAY-08:15 3528.15 24-JAN-08:00
Heating:EnergyTransfer 69825.58 0.00 01-MAY-08:15 68250.94 24-JAN-06:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 9189.23 0.00 01-MAY-08:15 3528.15 24-JAN-08:00
Cooling:EnergyTransfer 56603.66 0.00 01-JAN-00:15 89307.35 30-JUN-18:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12230.70 0.00 01-JAN-00:15 8433.04 02-APR-16:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 177.97 0.00 01-JAN-00:15 2031.43 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12052.73 0.00 01-JAN-00:15 8433.04 02-APR-16:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3896.94 0.00 01-JAN-00:15 3498.36 16-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1552.17 0.00 01-JAN-00:15 2748.48 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2344.77 0.00 01-JAN-00:15 3498.36 16-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6410.98 0.00 01-JAN-10:00 4474.09 16-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3246.23 0.00 01-JAN-10:00 3955.48 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3164.75 0.00 01-JAN-00:15 4474.09 16-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7147.81 0.00 01-JAN-15:00 6419.10 02-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4767.78 0.00 01-JAN-15:00 3966.40 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2380.03 0.00 01-JAN-00:15 6419.10 02-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4004.52 0.00 02-JAN-18:45 3075.92 30-JUN-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2992.74 0.00 02-JAN-18:45 2803.99 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1011.78 0.00 01-JAN-00:15 3075.92 30-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6433.32 0.00 03-JAN-14:00 4066.73 30-JUN-15:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4645.74 0.00 03-JAN-14:00 3995.91 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1787.58 0.00 01-JAN-00:15 4066.73 30-JUN-15:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6694.91 0.00 01-JAN-12:15 6579.05 02-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2154.39 0.00 01-JAN-12:15 3468.66 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4540.52 0.00 01-JAN-00:15 6579.05 02-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 3948.86 0.00 01-JAN-00:15 3539.04 02-APR-17:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1029.64 0.00 01-JAN-00:15 2326.17 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2919.22 0.00 01-JAN-00:15 3539.04 02-APR-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6034.31 0.00 01-JAN-10:00 4512.37 16-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2371.21 0.00 01-JAN-10:00 3552.61 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3663.09 0.00 01-JAN-00:15 4512.37 16-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6469.73 0.00 01-JAN-15:15 6361.44 30-JUN-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3738.66 0.00 01-JAN-15:15 3562.78 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2731.07 0.00 01-JAN-00:15 6361.44 30-JUN-18:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3546.57 0.00 01-JAN-19:15 3225.50 30-JUN-19:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2132.07 0.00 01-JAN-19:15 2384.41 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1414.50 0.00 01-JAN-00:15 3225.50 30-JUN-19:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5781.00 0.00 03-JAN-14:00 4020.18 30-JUN-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3603.56 0.00 03-JAN-14:00 3599.58 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2177.44 0.00 01-JAN-00:15 4020.18 30-JUN-15:30
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8182.29 0.00 03-JAN-18:15 4845.10 24-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5904.59 0.00 03-JAN-18:15 4845.10 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2277.70 0.00 01-JAN-00:15 4758.49 30-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 7595.80 0.00 01-JAN-12:45 4912.63 02-APR-16:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4496.89 0.00 01-JAN-12:45 4807.53 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3098.91 0.00 01-JAN-00:15 4912.63 02-APR-16:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 8651.89 0.00 01-JAN-13:45 7531.89 30-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4714.50 0.00 01-JAN-13:45 4758.03 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3937.39 0.00 01-JAN-00:15 7531.89 30-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5819.12 0.00 02-JAN-18:45 4369.75 30-JUN-19:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4166.64 0.00 02-JAN-18:45 3630.67 26-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1652.49 0.00 01-JAN-00:15 4369.75 30-JUN-19:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5215.08 0.00 01-JAN-13:00 4407.13 30-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2751.30 0.00 01-JAN-13:00 3570.58 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2463.79 0.00 01-JAN-00:15 4407.13 30-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9176.19 0.00 03-JAN-14:45 7563.29 30-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 6190.26 0.00 03-JAN-14:45 4812.29 24-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2985.93 0.00 01-JAN-00:15 7563.29 30-JUN-17:30
EnergyTransfer:Plant 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
WaterSystems:EnergyTransfer 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 140779.81 1400.84 08-AUG-02:15 32814.13 05-FEB-09:00
EnergyTransfer:HVAC 135429.41 65.39 23-MAY-00:15 104141.20 30-JUN-18:15
HeatingCoils:EnergyTransfer 66867.94 0.00 01-MAY-08:15 65091.50 24-JAN-06:00
CoolingCoils:EnergyTransfer 68561.46 0.00 01-JAN-00:15 104141.20 30-JUN-18:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 177.965 -1003.72 0.000 0.000 2916.694 2456.001 10405.511 6286.199 0.000 36.869 6405.930 0.000 -5140.84 0.000 -11491.64 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 1552.155 -195.26 0.000 0.000 3022.338 2456.001 10405.511 2894.572 0.000 35.287 0.058 0.000 -2053.84 0.000 -10390.87 -5576.40
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 3246.184 -263.55 0.000 0.000 3056.529 2456.001 10405.511 5942.037 0.000 36.665 0.061 0.000 -4818.92 0.000 -10679.02 -6480.28
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 4767.732 -198.20 0.000 0.000 3078.448 2456.001 10405.511 4162.004 0.000 36.980 0.000 0.000 -4934.68 0.000 -10423.18 -7168.82
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 2992.707 -84.26 0.000 0.000 3064.541 2456.001 10405.511 527.204 0.000 35.413 0.000 0.000 -2076.57 0.000 -10072.49 -6320.55
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 4645.692 -148.86 0.000 0.000 3082.699 2456.001 10405.511 3619.551 0.000 36.828 0.000 0.000 -4774.95 0.000 -10462.60 -7221.17
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 2154.368 -378.12 0.000 0.000 3025.775 2456.001 10405.511 6355.865 0.000 29.526 0.120 0.000 -5031.54 0.000 -8896.70 -5958.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 1029.623 -243.10 0.000 0.000 2996.073 2456.001 10405.511 2882.020 0.000 28.021 0.254 0.000 -2091.77 0.000 -8604.30 -6181.98
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 2371.181 -305.05 0.000 0.000 3034.206 2456.001 10405.511 5914.106 0.000 29.432 0.105 0.000 -4911.39 0.000 -8904.21 -6731.79
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 3738.624 -227.43 0.000 0.000 3058.043 2456.001 10405.511 4137.122 0.000 29.686 0.000 0.000 -5025.73 0.000 -8689.52 -7378.70
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 2132.053 -117.80 0.000 0.000 3037.383 2456.001 10405.511 521.178 0.000 28.117 0.000 0.000 -2115.61 0.000 -8364.53 -6685.62
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 3603.517 -181.33 0.000 0.000 3062.577 2456.001 10405.511 3598.158 0.000 29.494 0.000 0.000 -4859.32 0.000 -8725.64 -7392.88
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 5904.527 -189.68 0.000 0.000 3080.043 2456.001 10405.511 3633.958 0.000 36.071 0.000 0.000 -4823.72 0.000 -10489.66 -7925.06
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 4496.841 -258.07 0.000 0.000 3062.224 2456.001 10405.511 5969.473 0.000 36.076 0.027 0.000 -4839.68 0.000 -10636.57 -7851.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 4714.457 -327.89 0.000 0.000 3059.630 2456.001 10405.511 6416.566 0.000 36.528 0.019 0.000 -4920.99 0.000 -10588.93 -7641.44
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 4166.598 -137.61 0.000 0.000 3064.046 2456.001 10405.511 533.115 0.000 35.134 0.000 0.000 -2089.79 0.000 -10096.93 -6821.21
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 2751.268 -205.18 0.000 0.000 3038.772 2456.001 10405.511 2906.307 0.000 34.918 0.077 0.000 -2049.98 0.000 -10282.87 -6796.15
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 6190.208 -248.66 0.000 0.000 3076.762 2456.001 10405.511 4145.340 0.000 36.860 0.000 0.000 -4965.64 0.000 -10448.70 -7910.45
HEATEDBSMT 0.000 0.000 9189.232 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -9189.23
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 5499.950 52310.301 0.000 0.000 0.000 -57810.25 -1.02
Total Facility 0.000 0.000 69824.932 -4713.78 0.000 0.000 54816.785 44208.020 187299.191 70444.775 0.000 6107.851 58716.953 0.000 -71524.98 0.000 -236058.59 -127232.08


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 02-APR-16:45 0.00 0.00 0.00 -0.7 0.00 0.00 140.43 384.73 1363.77 4774.70 0.00 464.69 1326.02 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16-SEP-15:34 0.00 0.00 0.00 -0.3 0.00 0.00 115.16 178.62 1161.01 581.99 0.00 301.54 1191.64 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16-SEP-15:34 0.00 0.00 0.00 -0.4 0.00 0.00 114.85 178.62 1161.01 1044.33 0.00 310.57 1692.05 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 02-JUN-17:19 0.00 0.00 0.00 -0.5 0.00 0.00 263.33 535.87 1656.36 4636.73 0.00 223.05 0.00 0.00 0.00 0.00 0.00 -896.3
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 30-JUN-19:18 0.00 0.00 0.00 -0.3 0.00 0.00 424.63 799.44 1651.33 0.00 0.00 0.00 564.85 0.00 -121.5 0.00 -225.1 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 30-JUN-15:20 0.00 0.00 0.00 -0.3 0.00 0.00 114.98 178.62 1141.08 1251.34 0.00 787.68 607.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 02-JUN-17:19 0.00 0.00 0.00 -0.5 0.00 0.00 263.33 535.87 1656.36 4493.10 0.00 177.00 0.00 0.00 0.00 0.00 0.00 -546.6
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 02-APR-17:03 0.00 0.00 0.00 -0.3 0.00 0.00 263.32 535.87 1676.47 277.56 0.00 267.25 518.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-SEP-15:34 0.00 0.00 0.00 -0.4 0.00 0.00 115.03 178.62 1161.01 1044.46 0.00 241.57 1800.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 30-JUN-18:05 0.00 0.00 0.00 -0.5 0.00 0.00 427.03 721.37 1713.78 3160.24 0.00 173.20 166.69 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 30-JUN-19:18 0.00 0.00 0.00 -0.3 0.00 0.00 424.05 799.44 1651.33 0.00 0.00 0.00 661.60 0.00 -121.1 0.00 -183.0 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 30-JUN-15:33 0.00 0.00 0.00 -0.3 0.00 0.00 115.06 178.62 1141.08 1176.55 0.00 550.34 869.19 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 30-JUN-19:18 0.00 0.00 0.00 -0.4 0.00 0.00 423.39 799.44 1651.33 0.00 0.00 0.00 2519.42 0.00 -361.7 0.00 -246.9 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 16-SEP-15:34 0.00 0.00 0.00 -0.4 0.00 0.00 114.68 178.62 1161.01 1029.58 0.00 302.94 2154.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 30-JUN-17:19 0.00 0.00 0.00 -0.6 0.00 0.00 263.33 535.87 1656.36 4043.59 0.00 299.81 733.69 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 30-JUN-19:18 0.00 0.00 0.00 -0.4 0.00 0.00 425.60 799.44 1651.33 0.00 0.00 0.00 1877.94 0.00 -133.6 0.00 -225.4 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 30-JUN-19:04 0.00 0.00 0.00 -0.4 0.00 0.00 426.20 799.44 1651.33 0.00 0.00 0.00 1664.14 0.00 -68.9 0.00 -41.2 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 30-JUN-17:19 0.00 0.00 0.00 -0.6 0.00 0.00 263.33 535.87 1656.36 4164.08 0.00 299.81 644.68 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-JUN-18:15 0.00 0.00 0.00 -7.4 0.00 0.00 7675.38 12984.58 30848.11 22115.80 0.00 3549.09 22409.70 0.00 0.00 0.00 -10262.8 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 2031.38 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 538.21 0.00 -1656.6 0.00 -2697.4 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 2748.42 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -673.9 0.00 -2600.0 -1259.0
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 3955.38 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1654.1 0.00 -2697.4 -1388.2
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 3966.29 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1654.3 0.00 -2697.4 -1399.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 2803.92 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -673.7 0.00 -2600.0 -1314.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 24-JAN-06:00 0.00 0.00 3995.80 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1654.1 0.00 -2697.4 -1428.7
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 3468.55 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1670.8 0.00 -2240.8 -1341.4
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 2326.10 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -680.1 0.00 -2143.2 -1287.2
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 3552.50 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1667.9 0.00 -2240.8 -1428.3
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 3562.67 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1666.4 0.00 -2240.8 -1439.9
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 2384.33 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -677.9 0.00 -2143.2 -1347.7
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24-JAN-06:00 0.00 0.00 3599.47 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1665.1 0.00 -2240.8 -1478.0
LIVING_UNIT3_BACKROW_TOPFLOOR 24-JAN-06:00 0.00 0.00 4844.97 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1651.3 0.00 -2702.9 -2275.2
LIVING_UNIT3_FRONTROW_TOPFLOOR 24-JAN-06:00 0.00 0.00 4807.41 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1654.7 0.00 -2702.9 -2234.3
LIVING_UNIT1_FRONTROW_TOPFLOOR 24-JAN-06:00 0.00 0.00 4757.91 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1656.2 0.00 -2702.9 -2183.3
LIVING_UNIT2_BACKROW_TOPFLOOR 26-DEC-08:08 0.00 0.00 3630.87 0.00 0.00 0.00 215.05 151.14 1145.90 0.00 0.00 0.00 0.00 0.00 -493.6 0.00 -2209.7 -2439.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 24-JAN-06:00 0.00 0.00 3570.49 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -673.1 0.00 -2605.1 -2076.7
LIVING_UNIT1_BACKROW_TOPFLOOR 24-JAN-06:00 0.00 0.00 4812.16 0.00 0.00 0.00 526.31 343.51 914.63 0.00 0.00 0.00 0.00 0.00 -1652.4 0.00 -2702.9 -2241.4
HEATEDBSMT 24-JAN-08:00 0.00 0.00 3528.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -3528.1
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 24-JAN-06:00 0.00 0.00 68249.18 0.00 0.00 0.00 9473.52 6183.13 16463.41 0.00 0.00 1531.72 0.00 0.00 -23952.8 0.00 -45261.2 -32687.0



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 378.266 2.00 2.00 1.00 44.9950 378.266 0.119 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 151.010 2.00 2.00 1.00 44.9950 151.010 0.298 1.000 44.9950 0.30
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 189.485 2.00 2.00 1.00 44.9950 189.485 0.237 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 278.374 2.00 2.00 1.00 44.9950 278.374 0.162 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.623 2.00 2.00 1.00 44.9950 133.623 0.337 1.000 44.9950 0.34
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 181.123 2.00 2.00 1.00 44.9950 181.123 0.248 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 298.760 2.00 2.00 1.00 44.9950 298.760 0.151 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 156.787 2.00 2.00 1.00 44.9950 156.787 0.287 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 191.778 2.00 2.00 1.00 44.9950 191.778 0.235 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 276.666 2.00 2.00 1.00 44.9950 276.666 0.163 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 139.578 2.00 2.00 1.00 44.9950 139.578 0.322 1.000 44.9950 0.32
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 177.905 2.00 2.00 1.00 44.9950 177.905 0.253 1.000 44.9950 0.25
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 331.002 2.00 2.00 1.00 44.9950 331.002 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.391 2.00 2.00 1.00 44.9950 190.391 0.236 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 207.372 2.00 2.00 1.00 44.9950 207.372 0.217 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 326.173 2.00 2.00 1.00 44.9950 326.173 0.138 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 187.234 2.00 2.00 1.00 44.9950 187.234 0.240 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 202.699 2.00 2.00 1.00 44.9950 202.699 0.222 1.000 44.9950 0.22
CENTRAL SYSTEM_UNITHEATEDBSMT 44.995 0.00 0.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.995 2.00 2.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 57.084 2.00 2.00 1.00 44.9950 57.084 1.000 1.000 44.9950 0.79
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 77.964 2.00 2.00 1.00 44.9950 77.964 1.000 1.000 44.9950 0.58
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 77.958 2.00 2.00 1.00 44.9950 77.958 1.000 1.000 44.9950 0.58
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 57.059 2.00 2.00 1.00 44.9950 57.059 1.000 1.000 44.9950 0.79
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 77.887 2.00 2.00 1.00 44.9950 77.887 1.000 1.000 44.9950 0.58
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 72.978 2.00 2.00 1.00 44.9950 72.978 1.000 1.000 44.9950 0.62
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 51.851 2.00 2.00 1.00 44.9950 51.851 1.000 1.000 44.9950 0.87
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 73.026 2.00 2.00 1.00 44.9950 73.026 1.000 1.000 44.9950 0.62
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 73.022 2.00 2.00 1.00 44.9950 73.022 1.000 1.000 44.9950 0.62
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 51.842 2.00 2.00 1.00 44.9950 51.842 1.000 1.000 44.9950 0.87
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 72.968 2.00 2.00 1.00 44.9950 72.968 1.000 1.000 44.9950 0.62
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 96.521 2.00 2.00 1.00 44.9950 96.521 1.000 1.000 44.9950 0.47
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 75.207 2.00 2.00 1.00 44.9950 75.207 1.000 1.000 44.9950 0.60
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 96.563 2.00 2.00 1.00 44.9950 96.563 1.000 1.000 44.9950 0.47
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 96.555 2.00 2.00 1.00 44.9950 96.555 1.000 1.000 44.9950 0.47
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 75.205 2.00 2.00 1.00 44.9950 75.205 1.000 1.000 44.9950 0.60
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 96.524 2.00 2.00 1.00 44.9950 96.524 1.000 1.000 44.9950 0.47
CENTRAL SYSTEM_UNITHEATEDBSMT 66.298 0.00 0.00 1.00 44.9950 66.298 1.000 1.000 44.9950 0.68


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   378.266 378.2658 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   151.010 151.0096 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   189.485 189.4849 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   278.374 278.3737 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   133.623 133.6235 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   181.123 181.1235 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   298.760 298.7595 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   156.787 156.7867 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   191.778 191.7783 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   276.666 276.6655 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   139.578 139.5781 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   177.905 177.9050 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   202.699 202.6992 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   207.372 207.3724 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   331.002 331.0016 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   187.234 187.2338 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   190.391 190.3912 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   326.173 326.1729 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   44.995 44.9950 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 378.27 378.266 378.27 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 151.01 151.010 151.01 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 189.48 189.485 189.48 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 278.37 278.374 278.37 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.62 133.623 133.62 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 181.12 181.123 181.12 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 298.76 298.760 298.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 156.79 156.787 156.79 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 191.78 191.778 191.78 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 276.67 276.666 276.67 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 139.58 139.578 139.58 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 177.90 177.905 177.90 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 331.00 331.002 331.00 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.39 190.391 190.39 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 207.37 207.372 207.37 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 326.17 326.173 326.17 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 187.23 187.234 187.23 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 202.70 202.699 202.70 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.995 44.99 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   44.995 44.995 44.995 44.9950 1.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   57.084 57.084 57.084 44.9950 0.788 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   77.964 77.964 77.964 44.9950 0.577 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   77.958 77.958 77.958 44.9950 0.577 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   57.059 57.059 57.059 44.9950 0.789 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   77.887 77.887 77.887 44.9950 0.578 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   72.978 72.978 72.978 44.9950 0.617 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   51.851 51.851 51.851 44.9950 0.868 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   73.026 73.026 73.026 44.9950 0.616 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   73.022 73.022 73.022 44.9950 0.616 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   51.842 51.842 51.842 44.9950 0.868 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   72.968 72.968 72.968 44.9950 0.617 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   96.524 96.524 96.524 44.9950 0.466 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   96.563 96.563 96.563 44.9950 0.466 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   96.521 96.521 96.521 44.9950 0.466 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   75.205 75.205 75.205 44.9950 0.598 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   75.207 75.207 75.207 44.9950 0.598 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   96.555 96.555 96.555 44.9950 0.466 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   66.298 66.298 66.298 44.9950 0.679 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.995 44.99 44.99 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 57.08 57.084 57.08 57.08 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 77.96 77.964 77.96 77.96 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 77.96 77.958 77.96 77.96 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 57.06 57.059 57.06 57.06 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 77.89 77.887 77.89 77.89 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 72.98 72.978 72.98 72.98 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 51.85 51.851 51.85 51.85 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 73.03 73.026 73.03 73.03 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 73.02 73.022 73.02 73.02 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 51.84 51.842 51.84 51.84 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 72.97 72.968 72.97 72.97 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 96.52 96.521 96.52 96.52 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 75.21 75.207 75.21 75.21 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 96.56 96.563 96.56 96.56 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 96.56 96.555 96.56 96.56 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 75.21 75.205 75.21 75.21 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 96.52 96.524 96.52 96.52 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 66.30 66.298 66.30 66.30 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Sec1.1A-General Information

Data
Weather File ANNUAL ** San Francisco Intl Ap CA USA TMY3 WMO#=724940
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 7.75
Number of hours not met 7.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 12947.46 1812.17 0.00 0.00 0.00 0.00
Exterior Lighting 2555.34 66.85 0.00 0.00 0.00 0.00
Space Heating 19584.00 17856.72 0.00 0.00 0.00 0.00
Space Cooling 4154.94 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 1877.54 861.50 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 45767.64 37001.73 0.00 0.00 0.00 0.00
Receptacle Equipment 87836.46 9867.00 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 174723.37   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 299910.33 596578.49
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 299910.33 596578.49


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.33
Space Heating 0.50
Space Cooling 0.11
Fans-Interior 0.05
Service Water Heating 1.17
Receptacle Equipment 2.25
Miscellaneous 0.07
Subtotal 4.48


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 7.41
Space Heating 11.21
Space Cooling 2.38
Fans-Interior 1.07
Service Water Heating 26.19
Receptacle Equipment 50.27
Miscellaneous 1.46



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 66.30
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 378.27
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 151.01
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 189.48
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 278.37
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 133.62
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 181.12
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 298.76
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 156.79
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 191.78
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 276.67
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 139.58
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 177.90
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 202.70
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 207.37
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 331.00
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 187.23
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 190.39
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 326.17
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 378.27
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 151.01
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 189.48
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 278.37
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 133.62
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 181.12
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 298.76
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 156.79
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 191.78
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 276.67
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 139.58
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 177.90
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 331.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 190.39
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 207.37
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 326.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 187.23
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 202.70
CENTRAL SYSTEM_UNITHEATEDBSMT 66.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 378.27 0.840346 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 151.01 0.335479 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 189.48 0.420955 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 278.37 0.618428 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 133.62 0.296855 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 181.12 0.402379 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 298.76 0.663717 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 156.79 0.348313 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 191.78 0.426050 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 276.67 0.614633 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 139.58 0.310083 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 177.90 0.395229 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 331.00 0.735345 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 190.39 0.422968 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 207.37 0.460693 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 326.17 0.724618 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 187.23 0.415954 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 202.70 0.450311 0.798655
DX COOLING COIL_UNITHEATEDBSMT 66.30 0.169393 0.750675
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 378.27 378.27 378.27 4050.39 0.840346 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 151.01 151.01 151.01 4704.77 0.335479 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 189.48 189.48 189.48 5835.08 0.420955 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 278.37 278.37 278.37 5834.78 0.618428 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 133.62 133.62 133.62 4703.45 0.296855 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 181.12 181.12 181.12 5830.90 0.402379 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 298.76 298.76 298.76 5565.17 0.663717 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 156.79 156.79 156.79 4421.49 0.348313 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 191.78 191.78 191.78 5567.74 0.426050 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 276.67 276.67 276.67 5567.53 0.614633 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 139.58 139.58 139.58 4421.04 0.310083 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 177.90 177.90 177.90 5564.62 0.395229 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 331.00 331.00 331.00 6839.60 0.735345 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 190.39 190.39 190.39 5685.85 0.422968 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 207.37 207.37 207.37 6841.89 0.460693 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 326.17 326.17 326.17 6841.49 0.724618 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 187.23 187.23 187.23 5685.74 0.415954 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 202.70 202.70 202.70 6839.80 0.450311 1.00
ACANDF_UNITHEATEDBSMT 66.30 66.30 66.30 5203.50 0.169393 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 378.27
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 151.01
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 189.48
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 278.37
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 133.62
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 181.12
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 298.76
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 156.79
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 191.78
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 276.67
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 139.58
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 177.90
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 331.00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 190.39
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 207.37
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 326.17
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 187.23
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 202.70
SUPPLY FAN_UNITHEATEDBSMT 66.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 4050.39
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 4704.77
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 5835.08
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 5834.78
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 4703.45
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 5830.90
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 5565.17
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 4421.49
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 5567.74
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 5567.53
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 4421.04
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 5564.62
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 6839.60
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 5685.85
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 6841.89
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 6841.49
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 5685.74
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 6839.80
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT 5203.50
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:37:21

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 202.671 2.773 157.174 3.176 5.949
February 319.374 8.765 43.946 0.455 9.219
March 424.595 13.815 20.700 0.267 14.082
April 491.125 14.910 0.000 0.000 14.910
May 596.531 20.218 0.000 0.000 20.218
June 578.235 21.246 0.000 0.000 21.246
July 730.500 26.161 0.000 0.000 26.161
August 732.375 29.685 0.000 0.000 29.685
September 712.438 31.619 0.000 0.000 31.619
October 642.669 22.647 0.000 0.000 22.647
November 449.045 11.985 9.021 0.253 12.238
December 300.089 6.283 73.608 1.442 7.725
           
Annual Sum or Average 6179.646 210.107 304.449 5.592 215.699
Minimum of Months 202.671 2.773 0.000 0.000 5.949
Maximum of Months 732.375 31.619 157.174 3.176 31.619



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 12.333 0.047 475.733 5.782 5.829
February 99.660 1.406 281.225 2.839 4.245
March 161.729 2.303 260.181 2.148 4.451
April 120.771 1.894 180.691 1.188 3.082
May 189.518 2.864 105.701 0.588 3.452
June 209.394 3.604 83.399 0.426 4.029
July 297.471 4.273 0.000 0.000 4.273
August 370.811 7.049 0.000 0.000 7.049
September 409.777 9.659 0.000 0.000 9.659
October 309.591 6.221 42.392 0.182 6.403
November 156.871 2.160 172.671 1.146 3.306
December 60.500 0.645 363.413 3.735 4.380
           
Annual Sum or Average 2398.426 42.124 1965.406 18.034 60.158
Minimum of Months 12.333 0.047 0.000 0.000 3.082
Maximum of Months 409.777 9.659 475.733 5.782 9.659



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 4.167 0.020 603.853 10.218 10.238
February 74.760 1.429 363.321 5.444 6.873
March 160.280 3.066 319.445 4.378 7.444
April 172.920 3.403 241.308 2.671 6.075
May 237.281 4.567 136.708 1.523 6.090
June 282.455 6.911 174.583 1.547 8.458
July 344.452 6.596 72.125 0.313 6.909
August 379.705 9.858 45.750 0.166 10.024
September 395.729 11.240 35.750 0.139 11.379
October 283.046 6.877 143.500 1.129 8.006
November 114.939 1.879 308.208 3.298 5.177
December 33.821 0.382 471.655 7.313 7.695
           
Annual Sum or Average 2483.554 56.227 2916.207 38.140 94.367
Minimum of Months 4.167 0.020 35.750 0.139 5.177
Maximum of Months 395.729 11.240 603.853 10.218 11.379



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 734.687 20.662 20.662
February 20.638 0.291 518.912 12.079 12.370
March 58.234 1.063 436.313 8.638 9.701
April 107.804 2.354 332.875 5.016 7.369
May 192.834 4.633 194.833 2.645 7.278
June 214.500 7.095 194.134 2.258 9.353
July 270.938 8.047 82.494 0.396 8.443
August 295.318 9.000 58.887 0.288 9.287
September 284.221 7.728 51.000 0.267 7.995
October 142.829 2.753 249.746 2.802 5.555
November 10.574 0.070 493.875 8.691 8.761
December 0.000 0.000 686.896 17.037 17.037
           
Annual Sum or Average 1597.889 43.033 4034.652 80.778 123.812
Minimum of Months 0.000 0.000 51.000 0.267 5.555
Maximum of Months 295.318 9.000 734.687 20.662 20.662



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 699.250 8.862 8.862
February 8.604 0.052 513.167 5.080 5.132
March 16.771 0.224 426.674 3.303 3.527
April 52.106 0.789 291.139 1.714 2.503
May 146.679 2.150 132.585 0.705 2.855
June 181.286 3.062 106.237 0.471 3.533
July 257.242 3.117 1.958 0.001 3.118
August 292.623 4.382 1.375 0.001 4.382
September 284.424 3.713 0.000 0.000 3.713
October 112.464 1.406 134.775 0.573 1.979
November 1.583 0.004 455.112 3.046 3.050
December 0.000 0.000 667.517 7.162 7.162
           
Annual Sum or Average 1353.781 18.898 3429.789 30.917 49.815
Minimum of Months 0.000 0.000 0.000 0.000 1.979
Maximum of Months 292.623 4.382 699.250 8.862 8.862



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 742.833 13.713 13.713
February 7.167 0.032 578.688 7.991 8.024
March 38.491 0.498 436.708 5.462 5.959
April 111.751 1.655 293.950 3.053 4.708
May 202.969 3.613 146.438 1.573 5.185
June 272.017 6.384 177.083 1.496 7.880
July 333.555 5.560 73.208 0.313 5.872
August 336.666 7.497 55.375 0.203 7.700
September 321.247 5.598 45.333 0.181 5.779
October 141.359 1.998 210.796 1.625 3.623
November 1.875 0.005 512.980 5.271 5.276
December 0.000 0.000 731.250 11.422 11.422
           
Annual Sum or Average 1767.096 32.839 4004.642 52.303 85.142
Minimum of Months 0.000 0.000 45.333 0.181 3.623
Maximum of Months 336.666 7.497 742.833 13.713 13.713



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 15.742 0.100 514.079 12.424 12.524
February 124.142 2.549 312.375 6.462 9.012
March 195.406 4.951 275.656 4.570 9.520
April 205.570 5.494 184.169 2.341 7.835
May 278.917 7.099 115.726 1.277 8.376
June 269.349 8.915 109.996 0.954 9.869
July 335.167 10.722 3.583 0.004 10.726
August 367.265 13.010 4.500 0.008 13.018
September 394.909 14.889 6.107 0.012 14.901
October 295.575 8.996 86.306 0.813 9.809
November 155.854 2.976 236.544 3.223 6.199
December 65.437 0.956 416.208 8.687 9.643
           
Annual Sum or Average 2703.333 80.656 2265.249 40.776 121.432
Minimum of Months 15.742 0.100 3.583 0.004 6.199
Maximum of Months 394.909 14.889 514.079 12.424 14.901



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 17.408 0.071 432.167 4.782 4.853
February 122.533 1.827 237.171 2.144 3.971
March 202.286 3.112 191.323 1.402 4.514
April 168.149 2.683 126.097 0.639 3.322
May 243.984 3.839 65.833 0.256 4.095
June 249.558 4.523 44.749 0.224 4.747
July 345.096 5.599 0.000 0.000 5.599
August 412.806 8.464 0.000 0.000 8.464
September 463.625 11.352 0.000 0.000 11.352
October 346.265 7.297 21.542 0.082 7.378
November 189.429 2.860 116.738 0.746 3.606
December 81.458 0.843 309.546 2.887 3.730
           
Annual Sum or Average 2842.599 52.471 1545.166 13.161 65.632
Minimum of Months 17.408 0.071 0.000 0.000 3.322
Maximum of Months 463.625 11.352 432.167 4.782 11.352



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 4.233 0.012 576.675 8.857 8.869
February 90.779 1.649 319.167 4.447 6.095
March 195.145 3.684 277.763 3.257 6.941
April 208.322 4.221 181.258 1.722 5.943
May 288.111 5.495 98.375 0.903 6.398
June 316.787 7.856 125.125 0.896 8.752
July 385.109 7.922 23.500 0.061 7.983
August 422.806 11.174 12.000 0.030 11.204
September 429.469 12.670 12.250 0.034 12.704
October 319.771 7.766 101.125 0.702 8.468
November 144.814 2.313 255.198 2.391 4.704
December 43.542 0.439 437.000 6.179 6.618
           
Annual Sum or Average 2848.886 65.201 2419.436 29.479 94.680
Minimum of Months 4.233 0.012 12.000 0.030 4.704
Maximum of Months 429.469 12.670 576.675 8.857 12.704



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 732.358 18.376 18.376
February 23.325 0.325 472.667 10.250 10.574
March 76.080 1.285 392.433 6.677 7.961
April 137.119 2.981 267.850 3.367 6.348
May 235.797 5.500 146.205 1.631 7.130
June 244.125 7.886 138.529 1.262 9.148
July 306.313 9.140 18.008 0.054 9.194
August 326.929 10.084 16.644 0.055 10.139
September 320.382 8.951 21.583 0.079 9.030
October 177.708 3.227 199.854 2.000 5.227
November 20.829 0.109 452.062 7.076 7.185
December 0.000 0.000 661.396 14.993 14.993
           
Annual Sum or Average 1868.607 49.486 3519.590 65.817 115.304
Minimum of Months 0.000 0.000 16.644 0.054 5.227
Maximum of Months 326.929 10.084 732.358 18.376 18.376



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 666.375 7.773 7.773
February 12.937 0.092 444.708 4.140 4.233
March 33.204 0.356 333.149 2.268 2.624
April 78.067 1.168 185.694 0.950 2.118
May 211.769 3.029 78.770 0.308 3.338
June 231.357 4.026 48.917 0.219 4.244
July 313.271 4.526 0.000 0.000 4.526
August 353.148 5.839 0.000 0.000 5.839
September 363.484 5.405 0.000 0.000 5.405
October 144.108 1.878 84.576 0.335 2.212
November 7.542 0.032 369.687 2.234 2.266
December 0.000 0.000 611.725 6.154 6.154
           
Annual Sum or Average 1748.887 26.351 2823.602 24.381 50.732
Minimum of Months 0.000 0.000 0.000 0.000 2.118
Maximum of Months 363.484 5.839 666.375 7.773 7.773



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 739.021 12.064 12.064
February 11.800 0.066 548.917 6.588 6.654
March 53.696 0.655 364.683 4.046 4.701
April 155.781 2.251 214.546 1.962 4.213
May 251.313 4.477 103.958 0.918 5.395
June 312.140 7.362 125.350 0.841 8.203
July 373.116 6.934 25.208 0.066 6.999
August 376.804 8.731 19.542 0.043 8.774
September 378.150 7.034 17.125 0.048 7.082
October 161.864 2.409 163.933 1.080 3.489
November 6.302 0.023 450.064 4.123 4.145
December 0.000 0.000 714.542 9.931 9.931
           
Annual Sum or Average 2080.967 39.941 3486.889 41.709 81.650
Minimum of Months 0.000 0.000 17.125 0.043 3.489
Maximum of Months 378.150 8.731 739.021 12.064 12.064



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 638.879 20.351 20.351
February 79.592 1.719 408.500 11.288 13.007
March 143.358 3.913 368.449 8.889 12.801
April 155.594 4.652 310.645 5.679 10.331
May 213.254 6.120 210.167 3.431 9.551
June 222.594 8.569 232.683 3.281 11.850
July 279.583 9.832 136.316 0.909 10.742
August 314.408 12.120 92.834 0.601 12.721
September 337.617 13.399 72.683 0.502 13.901
October 240.685 7.237 226.640 3.035 10.272
November 97.917 1.931 373.892 7.573 9.504
December 30.354 0.369 528.917 15.416 15.786
           
Annual Sum or Average 2114.957 69.860 3600.604 80.956 150.816
Minimum of Months 0.000 0.000 72.683 0.502 9.504
Maximum of Months 337.617 13.399 638.879 20.351 20.351



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 1.208 0.002 584.589 9.628 9.630
February 70.333 1.174 351.208 4.930 6.104
March 138.924 2.346 321.613 3.774 6.120
April 126.335 2.457 258.123 2.317 4.774
May 178.655 3.335 152.333 1.234 4.569
June 203.313 4.610 160.748 1.087 5.698
July 273.292 5.143 32.938 0.076 5.219
August 330.127 7.779 15.923 0.029 7.808
September 375.386 9.888 11.530 0.024 9.912
October 261.175 5.577 125.562 0.713 6.290
November 119.200 1.738 287.144 2.684 4.422
December 33.771 0.272 467.302 6.794 7.065
           
Annual Sum or Average 2111.718 44.321 2769.012 33.290 77.611
Minimum of Months 1.208 0.002 11.530 0.024 4.422
Maximum of Months 375.386 9.888 584.589 9.628 9.912



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 658.646 13.078 13.078
February 56.521 1.141 417.992 6.987 8.128
March 143.530 2.729 346.250 5.350 8.080
April 159.548 3.551 270.333 3.235 6.786
May 212.304 4.657 149.156 1.758 6.415
June 267.709 7.267 191.750 1.941 9.208
July 323.749 6.871 94.292 0.488 7.359
August 357.711 10.103 72.875 0.330 10.432
September 378.584 11.148 58.292 0.276 11.424
October 243.737 6.105 195.463 1.732 7.837
November 95.357 1.420 359.596 4.517 5.937
December 14.758 0.120 551.042 9.752 9.873
           
Annual Sum or Average 2253.508 55.112 3365.686 49.445 104.557
Minimum of Months 0.000 0.000 58.292 0.276 5.937
Maximum of Months 378.584 11.148 658.646 13.078 13.078



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 737.158 25.823 25.823
February 23.038 0.442 516.408 15.119 15.560
March 78.474 1.771 433.128 10.729 12.499
April 124.237 3.517 344.371 6.412 9.930
May 199.951 5.593 224.503 3.573 9.166
June 217.635 8.388 237.190 3.298 11.686
July 271.083 9.407 139.608 0.932 10.339
August 293.988 10.872 104.526 0.694 11.566
September 291.535 9.866 91.497 0.617 10.482
October 150.089 3.426 298.065 4.396 7.822
November 18.563 0.188 505.417 11.400 11.588
December 0.000 0.000 696.979 21.815 21.815
           
Annual Sum or Average 1668.593 53.468 4328.850 104.809 158.278
Minimum of Months 0.000 0.000 91.497 0.617 7.822
Maximum of Months 293.988 10.872 737.158 25.823 25.823



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 726.875 13.473 13.473
February 15.238 0.171 511.437 7.698 7.870
March 51.842 0.676 423.292 5.094 5.769
April 87.979 1.694 310.042 2.845 4.539
May 163.758 3.027 164.000 1.324 4.351
June 196.765 4.583 158.267 1.078 5.662
July 264.729 4.891 32.542 0.082 4.973
August 301.186 6.665 23.240 0.048 6.713
September 306.288 6.279 16.385 0.040 6.320
October 117.708 2.139 218.800 1.477 3.616
November 11.083 0.069 478.562 5.209 5.278
December 0.000 0.000 680.596 11.246 11.246
           
Annual Sum or Average 1516.576 30.195 3744.038 49.615 79.810
Minimum of Months 0.000 0.000 16.385 0.040 3.616
Maximum of Months 306.288 6.665 726.875 13.473 13.473



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 742.750 16.342 16.342
February 15.675 0.153 568.946 9.465 9.618
March 58.260 0.963 425.409 6.320 7.283
April 134.267 2.576 301.042 3.557 6.132
May 198.938 4.312 154.521 1.786 6.098
June 266.486 7.223 191.600 1.896 9.119
July 319.009 6.641 94.375 0.480 7.120
August 335.568 9.033 76.958 0.360 9.393
September 331.955 7.577 67.625 0.315 7.892
October 126.137 2.553 258.449 2.348 4.901
November 10.798 0.068 522.642 6.751 6.819
December 0.000 0.000 736.667 13.912 13.912
           
Annual Sum or Average 1797.093 41.097 4140.983 63.533 104.630
Minimum of Months 0.000 0.000 67.625 0.315 4.901
Maximum of Months 335.568 9.033 742.750 16.342 16.342



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 9.630 9.630
February 0.000 0.000 672.000 7.399 7.399
March 0.000 0.000 744.000 6.820 6.820
April 0.000 0.000 720.000 5.451 5.451
May 0.000 0.000 24.221 0.030 0.030
June 0.000 0.000 0.000 0.000 0.000
July 0.000 0.000 0.000 0.000 0.000
August 0.000 0.000 0.000 0.000 0.000
September 0.000 0.000 0.000 0.000 0.000
October 0.000 0.000 0.000 0.000 0.000
November 0.000 0.000 717.000 5.650 5.650
December 0.000 0.000 744.000 8.438 8.438
           
Annual Sum or Average 0.000 0.000 4365.221 43.419 43.419
Minimum of Months 0.000 0.000 0.000 0.000 0.000
Maximum of Months 0.000 0.000 744.000 9.630 9.630



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 121.17 0.00
February 0.00 19.20 0.00
March 0.00 10.20 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 9.97 0.00
December 0.00 55.01 0.00
       
Annual Sum or Average 0.00 18.12 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 121.17 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 641.92 0.00
February 0.00 349.01 0.00
March 0.00 238.47 0.00
April 0.00 136.24 0.00
May 0.00 65.24 0.00
June 0.00 48.82 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 20.21 0.00
November 0.00 131.48 0.00
December 0.00 414.66 0.00
       
Annual Sum or Average 0.00 170.04 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 641.92 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1121.24 0.00
February 0.00 661.35 0.00
March 0.00 480.43 0.00
April 0.00 302.88 0.00
May 0.00 167.11 0.00
June 0.00 175.46 0.00
July 0.00 34.37 0.00
August 0.00 18.24 0.00
September 0.00 15.76 0.00
October 0.00 123.89 0.00
November 0.00 373.99 0.00
December 0.00 802.48 0.00
       
Annual Sum or Average 0.00 355.45 0.00
Minimum of Months 0.00 15.76 0.00
Maximum of Months 0.00 1121.24 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1543.20 0.00
February 0.00 998.82 0.00
March 0.00 645.17 0.00
April 0.00 387.11 0.00
May 0.00 197.57 0.00
June 0.00 174.24 0.00
July 0.00 29.59 0.00
August 0.00 21.47 0.00
September 0.00 20.60 0.00
October 0.00 209.32 0.00
November 0.00 670.76 0.00
December 0.00 1272.52 0.00
       
Annual Sum or Average 0.00 512.42 0.00
Minimum of Months 0.00 20.60 0.00
Maximum of Months 0.00 1543.20 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1111.52 0.00
February 0.00 705.41 0.00
March 0.00 414.30 0.00
April 0.00 222.15 0.00
May 0.00 88.39 0.00
June 0.00 61.08 0.00
July 0.00 0.16 0.00
August 0.00 0.06 0.00
September 0.00 0.00 0.00
October 0.00 71.91 0.00
November 0.00 394.74 0.00
December 0.00 898.27 0.00
       
Annual Sum or Average 0.00 329.35 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 1111.52 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1573.06 0.00
February 0.00 1014.95 0.00
March 0.00 626.54 0.00
April 0.00 361.92 0.00
May 0.00 180.44 0.00
June 0.00 177.33 0.00
July 0.00 35.88 0.00
August 0.00 23.26 0.00
September 0.00 21.46 0.00
October 0.00 186.47 0.00
November 0.00 624.84 0.00
December 0.00 1310.29 0.00
       
Annual Sum or Average 0.00 509.59 0.00
Minimum of Months 0.00 21.46 0.00
Maximum of Months 0.00 1573.06 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 824.70 0.00
February 0.00 474.91 0.00
March 0.00 303.34 0.00
April 0.00 160.57 0.00
May 0.00 84.78 0.00
June 0.00 65.42 0.00
July 0.00 0.25 0.00
August 0.00 0.54 0.00
September 0.00 0.83 0.00
October 0.00 53.97 0.00
November 0.00 221.05 0.00
December 0.00 576.64 0.00
       
Annual Sum or Average 0.00 229.88 0.00
Minimum of Months 0.00 0.25 0.00
Maximum of Months 0.00 824.70 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 480.54 0.00
February 0.00 238.52 0.00
March 0.00 140.89 0.00
April 0.00 66.35 0.00
May 0.00 25.71 0.00
June 0.00 23.21 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 8.22 0.00
November 0.00 77.50 0.00
December 0.00 290.09 0.00
       
Annual Sum or Average 0.00 112.33 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 480.54 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 916.24 0.00
February 0.00 509.31 0.00
March 0.00 336.98 0.00
April 0.00 184.09 0.00
May 0.00 93.40 0.00
June 0.00 95.81 0.00
July 0.00 6.36 0.00
August 0.00 3.09 0.00
September 0.00 3.67 0.00
October 0.00 72.59 0.00
November 0.00 255.59 0.00
December 0.00 639.19 0.00
       
Annual Sum or Average 0.00 259.01 0.00
Minimum of Months 0.00 3.09 0.00
Maximum of Months 0.00 916.24 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1317.69 0.00
February 0.00 813.73 0.00
March 0.00 478.77 0.00
April 0.00 249.50 0.00
May 0.00 116.93 0.00
June 0.00 93.52 0.00
July 0.00 3.87 0.00
August 0.00 3.91 0.00
September 0.00 5.84 0.00
October 0.00 143.38 0.00
November 0.00 524.31 0.00
December 0.00 1075.13 0.00
       
Annual Sum or Average 0.00 400.85 0.00
Minimum of Months 0.00 3.87 0.00
Maximum of Months 0.00 1317.69 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 877.29 0.00
February 0.00 517.39 0.00
March 0.00 256.02 0.00
April 0.00 110.79 0.00
May 0.00 34.79 0.00
June 0.00 25.52 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 37.76 0.00
November 0.00 260.55 0.00
December 0.00 694.59 0.00
       
Annual Sum or Average 0.00 233.72 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 877.29 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1344.60 0.00
February 0.00 812.94 0.00
March 0.00 450.92 0.00
April 0.00 225.94 0.00
May 0.00 102.29 0.00
June 0.00 96.83 0.00
July 0.00 7.30 0.00
August 0.00 4.83 0.00
September 0.00 5.53 0.00
October 0.00 120.39 0.00
November 0.00 474.83 0.00
December 0.00 1106.93 0.00
       
Annual Sum or Average 0.00 394.83 0.00
Minimum of Months 0.00 4.83 0.00
Maximum of Months 0.00 1344.60 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1498.50 0.00
February 0.00 920.20 0.00
March 0.00 654.50 0.00
April 0.00 432.10 0.00
May 0.00 252.61 0.00
June 0.00 249.64 0.00
July 0.00 66.96 0.00
August 0.00 44.24 0.00
September 0.00 38.16 0.00
October 0.00 223.50 0.00
November 0.00 576.23 0.00
December 0.00 1135.12 0.00
       
Annual Sum or Average 0.00 506.27 0.00
Minimum of Months 0.00 38.16 0.00
Maximum of Months 0.00 1498.50 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1024.59 0.00
February 0.00 580.83 0.00
March 0.00 401.61 0.00
April 0.00 254.79 0.00
May 0.00 131.32 0.00
June 0.00 119.54 0.00
July 0.00 8.11 0.00
August 0.00 3.11 0.00
September 0.00 2.67 0.00
October 0.00 75.84 0.00
November 0.00 295.19 0.00
December 0.00 722.96 0.00
       
Annual Sum or Average 0.00 300.88 0.00
Minimum of Months 0.00 2.67 0.00
Maximum of Months 0.00 1024.59 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1537.56 0.00
February 0.00 909.51 0.00
March 0.00 629.03 0.00
April 0.00 393.03 0.00
May 0.00 206.74 0.00
June 0.00 235.81 0.00
July 0.00 57.34 0.00
August 0.00 38.75 0.00
September 0.00 33.48 0.00
October 0.00 203.65 0.00
November 0.00 548.79 0.00
December 0.00 1146.56 0.00
       
Annual Sum or Average 0.00 493.72 0.00
Minimum of Months 0.00 33.48 0.00
Maximum of Months 0.00 1537.56 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1930.07 0.00
February 0.00 1251.07 0.00
March 0.00 801.89 0.00
April 0.00 495.26 0.00
May 0.00 267.09 0.00
June 0.00 254.70 0.00
July 0.00 69.67 0.00
August 0.00 51.90 0.00
September 0.00 47.65 0.00
October 0.00 328.60 0.00
November 0.00 880.45 0.00
December 0.00 1630.53 0.00
       
Annual Sum or Average 0.00 665.32 0.00
Minimum of Months 0.00 47.65 0.00
Maximum of Months 0.00 1930.07 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1457.89 0.00
February 0.00 922.30 0.00
March 0.00 551.19 0.00
April 0.00 318.14 0.00
May 0.00 143.23 0.00
June 0.00 120.59 0.00
July 0.00 8.85 0.00
August 0.00 5.22 0.00
September 0.00 4.52 0.00
October 0.00 159.84 0.00
November 0.00 582.41 0.00
December 0.00 1216.97 0.00
       
Annual Sum or Average 0.00 455.98 0.00
Minimum of Months 0.00 4.52 0.00
Maximum of Months 0.00 1457.89 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 1965.03 0.00
February 0.00 1260.03 0.00
March 0.00 759.95 0.00
April 0.00 441.93 0.00
May 0.00 214.76 0.00
June 0.00 235.58 0.00
July 0.00 57.66 0.00
August 0.00 43.29 0.00
September 0.00 39.17 0.00
October 0.00 282.31 0.00
November 0.00 838.85 0.00
December 0.00 1672.82 0.00
       
Annual Sum or Average 0.00 648.81 0.00
Minimum of Months 0.00 39.17 0.00
Maximum of Months 0.00 1965.03 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2693.15 0.00
February 0.00 2291.04 0.00
March 0.00 1907.46 0.00
April 0.00 1575.43 0.00
May 0.00 8.52 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 1632.90 0.00
December 0.00 2359.95 0.00
       
Annual Sum or Average 0.00 1031.34 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2693.15 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.07
March 0.00 0.00 0.10
April 0.00 0.00 0.12
May 0.00 0.00 0.15
June 0.00 0.00 0.17
July 0.00 0.00 0.20
August 0.00 0.00 0.23
September 0.00 0.00 0.25
October 0.00 0.00 0.17
November 0.00 0.00 0.09
December 0.00 0.00 0.05
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.01
May 0.00 0.00 0.02
June 0.00 0.00 0.03
July 0.00 0.00 0.03
August 0.00 0.00 0.05
September 0.00 0.00 0.08
October 0.00 0.00 0.05
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.05
July 0.00 0.00 0.05
August 0.00 0.00 0.08
September 0.00 0.00 0.09
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.09



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.03
June 0.00 0.00 0.06
July 0.00 0.00 0.06
August 0.00 0.00 0.07
September 0.00 0.00 0.06
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.07



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.02
June 0.00 0.00 0.02
July 0.00 0.00 0.02
August 0.00 0.00 0.03
September 0.00 0.00 0.03
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.01
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.03



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.05
July 0.00 0.00 0.04
August 0.00 0.00 0.06
September 0.00 0.00 0.04
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.06



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.04
May 0.00 0.00 0.05
June 0.00 0.00 0.07
July 0.00 0.00 0.08
August 0.00 0.00 0.10
September 0.00 0.00 0.12
October 0.00 0.00 0.07
November 0.00 0.00 0.02
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.12



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.02
April 0.00 0.00 0.02
May 0.00 0.00 0.03
June 0.00 0.00 0.04
July 0.00 0.00 0.04
August 0.00 0.00 0.07
September 0.00 0.00 0.09
October 0.00 0.00 0.06
November 0.00 0.00 0.02
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.09



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.03
May 0.00 0.00 0.04
June 0.00 0.00 0.06
July 0.00 0.00 0.06
August 0.00 0.00 0.09
September 0.00 0.00 0.10
October 0.00 0.00 0.06
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.06
July 0.00 0.00 0.07
August 0.00 0.00 0.08
September 0.00 0.00 0.07
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.02
June 0.00 0.00 0.03
July 0.00 0.00 0.04
August 0.00 0.00 0.05
September 0.00 0.00 0.04
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.03
June 0.00 0.00 0.06
July 0.00 0.00 0.05
August 0.00 0.00 0.07
September 0.00 0.00 0.06
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.07



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.04
May 0.00 0.00 0.05
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.09
September 0.00 0.00 0.11
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.11



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.02
May 0.00 0.00 0.03
June 0.00 0.00 0.04
July 0.00 0.00 0.04
August 0.00 0.00 0.06
September 0.00 0.00 0.08
October 0.00 0.00 0.04
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.06
July 0.00 0.00 0.05
August 0.00 0.00 0.08
September 0.00 0.00 0.09
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.09



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.04
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.08
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.02
June 0.00 0.00 0.04
July 0.00 0.00 0.04
August 0.00 0.00 0.05
September 0.00 0.00 0.05
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.05



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.03
June 0.00 0.00 0.06
July 0.00 0.00 0.05
August 0.00 0.00 0.07
September 0.00 0.00 0.06
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.07



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74
Maximum of Months 0.00 0.00 1056.84 784.59



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:37:21

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1053.82 784.59
February 0.00 0.00 1056.84 710.70
March 0.00 0.00 1044.07 777.34
April 0.00 0.00 1017.88 733.40
May 0.00 0.00 981.98 731.11
June 0.00 0.00 948.88 683.68
July 0.00 0.00 930.09 692.48
August 0.00 0.00 922.78 687.03
September 0.00 0.00 937.86 675.74
October 0.00 0.00 962.89 716.90
November 0.00 0.00 997.81 718.93
December 0.00 0.00 1033.90 769.76
         
Annual Sum or Average 0.00 0.00 990.35 8681.66
Minimum of Months 0.00 0.00 922.78 675.74