Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39

Tabular Output Report in Format: HTML

Building: MF+CZ4AWH+USA_MD_Baltimore-Washington.Intl.AP.724060+elecres+heatedbsmt+IECC_2009

Environment: ANNUAL ** Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060

Simulation Timestamp: 2019-02-14 08:39:37


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 923223.14 23.67 31.40
Net Site Energy 923223.14 23.67 31.40
Total Source Energy 2923847.69 74.96 99.44
Net Source Energy 2923847.69 74.96 99.44


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.82


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 305196.38 0.00 0.00 0.00 0.00 0.00
Cooling 60340.08 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 19823.42 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 176210.46 0.00 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 923223.14 0.00 0.00 0.00 0.00 419684.21
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 305196.38 0.00 0.00 0.00 0.00 0.00
Cooling General 60340.08 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 19823.42 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 176210.46 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.05 0.00 0.00 0.00 0.00 0.00
HVAC 19.10 0.00 0.00 0.00 0.00 14.27
Other 10.25 0.00 0.00 0.00 0.00 0.00
Total 31.40 0.00 0.00 0.00 0.00 14.27


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 14.40 0.00 0.00 0.00 0.00 10.76
Other 7.73 0.00 0.00 0.00 0.00 0.00
Total 23.67 0.00 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 923223.142 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 923223.142 100.00
     
Total On-Site and Utility Electric Sources 923223.142 100.00
Total Electricity End Uses 923223.142 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 20.25
Time Not Comfortable Based on Simple ASHRAE 55-2004 1730.25


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39
RunPeriod ANNUAL
Weather File Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Latitude [deg] 39.17
Longitude [deg] -76.7
Elevation [ft] 147.65
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58419.71 1.00 185.02 0.00 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 39005.17     325507.37   16363.00 0.00 2126.74 2126.74 0.4163 1083.48 1.6118
Conditioned Total 29404.35     242159.09   15481.63 0.00 2126.74 2126.74 0.5522 816.79 2.1381
Unconditioned Total 9600.82     83348.27   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 25-DEC-06:45 - - - - 01-JAN-08:15
Heating 225.17 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 7.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.30 0.00 0.00 0.00 0.00 0.00
Interior Equipment 28.51 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7.12 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 127.29 0.00 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 396.21 0.00 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 225.17 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 7.82 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.30 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.58 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.25 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.31 0.00 0.00 0.00 0.00 0.00
  electric_dryer 1.74 0.00 0.00 0.00 0.00 0.00
  electric_range 2.10 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 18.31 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.21 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 7.12 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 127.29 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 966556.93 0.00 0.00 0.00 0.00
Cooling 191097.03 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 62780.78 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 558058.51 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 2923847.69 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 32.87 0.00 0.00 0.00 0.00
Cooling 6.50 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.14 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 18.98 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 99.44 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 32.87 0.00 0.00 0.00 0.00
Cooling 6.50 0.00 0.00 0.00 0.00
Interior Lighting 5.37 0.00 0.00 0.00 0.00
Exterior Lighting 1.11 0.00 0.00 0.00 0.00
Interior Equipment 32.47 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 2.14 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 18.98 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 99.44 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 12.92 0.00 12.92 Wetbulb [F] 767.75 290.00
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 93.92 18.72 75.02 Wetbulb [F] 905.56 280.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.087 0.094 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.330 0.882              
North Total or Average           531.68 0.350 0.330 0.882              
Non-North Total or Average           1595.05 0.350 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   17399.71 12837.12 4562.60 0.74 4.07    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9522.47 6500.95 3021.52 0.68 4.07    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11927.15 8327.00 3600.15 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14930.62 10840.08 4090.54 0.73 4.07    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8792.59 6069.91 2722.68 0.69 4.07    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10753.88 7688.91 3064.98 0.71 4.07    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14505.22 10655.62 3849.60 0.73 4.07    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8656.67 6040.35 2616.32 0.70 4.07    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11230.13 7906.83 3323.30 0.70 4.07    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14083.34 10322.97 3760.37 0.73 4.07    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8356.57 5835.04 2521.53 0.70 4.07    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10156.55 7295.79 2860.76 0.72 4.07    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16490.05 12104.50 4385.56 0.73 4.07    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10634.58 7498.31 3136.27 0.71 4.07    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12875.71 9098.13 3777.58 0.71 4.07    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16392.96 12039.76 4353.19 0.73 4.07    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10544.19 7447.46 3096.73 0.71 4.07    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12673.26 8937.20 3736.06 0.71 4.07    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   3912.04 2644.86 1267.17 0.68 4.07    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.4 3.37 11.51 12.21 11.90
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.8 3.48 11.89 12.62 12.53
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.0 3.45 11.78 12.50 12.35
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.2 3.40 11.59 12.29 12.03
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.7 3.47 11.84 12.56 12.44
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.9 3.42 11.67 12.38 12.16
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.38 11.54 12.23 11.94
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.45 11.79 12.51 12.36
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.44 11.74 12.46 12.28
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.38 11.55 12.24 11.96
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.45 11.78 12.50 12.35
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.41 11.65 12.35 12.12
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.38 11.54 12.23 11.94
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.44 11.74 12.45 12.27
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.44 11.73 12.44 12.25
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.38 11.54 12.23 11.94
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.8 3.44 11.73 12.44 12.26
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.44 11.73 12.45 12.27
DX COOLING COIL_UNITHEATEDBSMT   0.3 3.50 11.94 12.67 12.61
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   13523.75 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   12859.68 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   15441.94 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   15450.92 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   12860.23 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   15440.31 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   13276.47 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   10657.25 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   13265.17 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   13279.30 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   10657.83 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   13263.80 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   17101.30 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   14490.00 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   17086.83 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   17106.83 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   14493.98 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   17089.45 1.00
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT Coil:Heating:Electric   8130.66 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 544.61 205.42 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 244.54 92.24 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 325.10 122.63 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 449.43 169.52 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 232.65 87.76 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 311.59 117.53 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 449.32 169.48 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 235.61 88.87 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 312.88 118.02 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 433.93 163.67 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 227.86 85.95 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 297.75 112.31 0.38 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 509.86 192.32 0.38 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 297.39 112.17 0.38 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 362.06 136.57 0.38 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 507.53 191.43 0.38 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 296.18 111.72 0.38 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 354.55 133.73 0.38 1.00 General
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 97.82 36.90 0.38 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.06 0.96



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12725.51 12725.51 10.60 544.606 544.606 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:15:00 74.98 74.98 0.00899 90.83 0.01446 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5713.59 5713.59 4.76 244.536 244.536 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:45:00 74.98 74.98 0.00976 93.08 0.01446 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7594.80 7594.80 6.33 325.100 325.100 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:15:00 74.98 74.98 0.00947 93.92 0.01446 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10501.61 10501.61 8.75 449.429 449.429 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00919 90.36 0.01446 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5436.50 5436.50 4.53 232.654 232.654 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.01000 87.32 0.01446 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7281.12 7281.12 6.06 311.590 311.590 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 09:45:00 74.98 74.98 0.00953 86.01 0.01446 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10499.33 10499.33 8.75 449.316 449.316 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00894 90.36 0.01446 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5505.79 5505.79 4.59 235.614 235.614 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00959 88.02 0.01446 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7309.96 7309.96 6.09 312.882 312.882 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 74.98 74.98 0.00918 93.92 0.01446 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10139.73 10139.73 8.45 433.927 433.927 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00899 89.90 0.01446 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5324.71 5324.71 4.44 227.863 227.863 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00968 86.62 0.01446 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6957.82 6957.82 5.80 297.748 297.748 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 74.98 74.98 0.00927 86.81 0.01446 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8283.45 8283.45 6.90 354.548 354.548 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 74.98 74.98 0.00937 93.36 0.01446 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8459.07 8459.07 7.05 362.065 362.065 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 74.98 74.98 0.00935 93.36 0.01446 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11913.66 11913.66 9.92 509.860 509.860 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 74.98 74.98 0.00907 90.36 0.01446 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6920.82 6920.82 5.76 296.177 296.177 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00967 87.32 0.01446 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6949.14 6949.14 5.79 297.390 297.390 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00965 88.02 0.01446 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11859.09 11859.09 9.88 507.525 507.525 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00909 89.90 0.01446 44.995 0.00
HEATEDBSMT 788.26 788.26 0.10 33.729 44.995 BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00903 87.32 0.01446 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10819.50 10819.50 9.01 197.911 197.911 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00573 12.92 0.00152 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10145.60 10145.60 8.45 185.585 185.585 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00575 12.92 0.00152 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12766.10 12766.10 10.63 233.513 233.513 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00596 12.92 0.00152 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12775.22 12775.22 10.64 233.680 233.680 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00596 12.92 0.00152 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10146.16 10146.16 8.45 185.596 185.596 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00575 12.92 0.00152 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12764.45 12764.45 10.63 233.483 233.483 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00596 12.92 0.00152 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10568.35 10568.35 8.80 193.334 193.334 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00627 12.92 0.00152 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7910.34 7910.34 6.59 144.714 144.714 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00606 12.92 0.00152 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10556.88 10556.88 8.79 193.125 193.125 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00627 12.92 0.00152 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10571.22 10571.22 8.81 193.387 193.387 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00627 12.92 0.00152 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7910.92 7910.92 6.59 144.725 144.725 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00606 12.92 0.00152 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10555.49 10555.49 8.79 193.099 193.099 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00627 12.92 0.00152 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 14437.97 14437.97 12.03 264.094 264.094 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00612 12.92 0.00152 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 14435.31 14435.31 12.02 264.045 264.045 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00612 12.92 0.00152 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14450.00 14450.00 12.04 264.314 264.314 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00612 12.92 0.00152 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11804.06 11804.06 9.83 215.922 215.922 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00596 12.92 0.00152 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11800.03 11800.03 9.83 215.848 215.848 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00596 12.92 0.00152 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14455.60 14455.60 12.04 264.417 264.417 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.98 0.00612 12.92 0.00152 44.995 0.00
HEATEDBSMT 5345.81 5345.81 0.69 97.821 97.821 BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB 1/21 07:15:00 72.00 72.00 0.00800 12.92 0.00152 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 544.61 544.61 197.91 197.91
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.54 244.54 185.59 185.59
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.10 325.10 233.51 233.51
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 449.43 449.43 233.68 233.68
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 232.65 232.65 185.60 185.60
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 311.59 311.59 233.48 233.48
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 449.32 449.32 193.33 193.33
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 235.61 235.61 144.71 144.71
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.88 312.88 193.12 193.12
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 433.93 433.93 193.39 193.39
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 227.86 227.86 144.72 144.72
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.75 297.75 193.10 193.10
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 509.86 509.86 264.31 264.31
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 297.39 297.39 215.85 215.85
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.06 362.06 264.05 264.05
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 507.53 507.53 264.42 264.42
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 296.18 296.18 215.92 215.92
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 354.55 354.55 264.09 264.09
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.99 97.82 97.82


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2691.25 5050.00 376.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2595.75 5852.75 717.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3008.00 5715.00 879.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3110.50 6199.25 1190.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2575.50 6235.25 826.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3065.00 6033.50 1040.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3064.50 5585.00 810.75
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2576.75 5439.75 464.50
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2964.50 5415.50 669.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3089.00 5871.75 945.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2549.50 5779.25 536.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3055.25 5702.50 824.25
LIVING_UNIT3_BACKROW_TOPFLOOR 3492.50 5870.25 1285.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 3343.50 5700.75 1083.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 3397.25 5918.50 1259.75
LIVING_UNIT2_BACKROW_TOPFLOOR 2960.00 6049.00 979.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 2872.25 5847.50 824.50
LIVING_UNIT1_BACKROW_TOPFLOOR 3551.50 6082.50 1477.75
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3896.75 6542.50 1730.25
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 2.50 0.00 2.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 4.75 0.00 4.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 3.50 0.00 3.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 1.50 0.00 1.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 17.25 0.00 17.25
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 1.25 0.00 1.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 2.00 0.00 2.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 12.50 0.00 12.50
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 4.50 0.00 4.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 2.00 0.00 2.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 2.75 0.00 2.75
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 2.00 0.00 2.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.75 0.00 0.75
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 3.50 0.00 3.50
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 20.25 0.00 20.25
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.271 0.000 0.274
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.238 0.000 0.274
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.270 0.000 0.274
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.269 0.000 0.274
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.237 0.000 0.274
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.269 0.000 0.274
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.274
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.086 0.000 0.274
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.274
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.274
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.086 0.000 0.274
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.274
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.270 0.000 0.274
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.270 0.000 0.274
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.270 0.000 0.274
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.237 0.000 0.274
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.238 0.000 0.274
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.270 0.000 0.274
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1846
Defaulted Fields 455
Fields with Defaults 4639
Autosized Fields 300
Autosizable Fields 410
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Electricity:Plant 51607.77 0.00 01-JAN-00:15 39031.72 11-FEB-08:15
WaterSystems:Electricity 51607.77 0.00 01-JAN-00:15 39031.72 11-FEB-08:15
Water Heater:WaterSystems:Electricity 51607.77 0.00 01-JAN-00:15 39031.72 11-FEB-08:15
Fans:Electricity 5805.80 0.00 03-MAY-22:15 2412.71 09-JUL-16:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
ElectricityPurchased:Plant 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
Cogeneration:ElectricityPurchased 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
ElectricityNet:Plant 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
Cogeneration:ElectricityNet 270389.67 6919.48 01-JUN-03:45 116040.19 25-DEC-06:45
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 112862.56 0.00 03-MAY-22:15 68537.25 25-DEC-07:15
General:Fans:Electricity 5805.80 0.00 03-MAY-22:15 2412.71 09-JUL-16:15
Heating:Electricity 89384.62 0.00 01-MAY-12:15 66437.81 25-DEC-07:15
Cooling:Electricity 17672.15 0.00 01-JAN-00:15 15486.79 09-JUL-16:00
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 09-JAN-02:30 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
PlantLoopHeatingDemand:Plant 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
WaterSystems:PlantLoopHeatingDemand 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1227248.53 1400.51 09-SEP-03:00 500057.87 25-DEC-07:15
EnergyTransfer:Building 498535.91 0.00 03-MAY-22:15 233849.10 25-DEC-07:15
EnergyTransfer:Zone:HEATEDBSMT 14318.96 0.00 01-MAY-11:45 5432.01 19-JAN-08:00
Heating:EnergyTransfer 314618.05 0.00 01-MAY-12:15 233849.10 25-DEC-07:15
Heating:EnergyTransfer:Zone:HEATEDBSMT 14085.80 0.00 01-MAY-11:45 5432.01 19-JAN-08:00
Cooling:EnergyTransfer 183917.86 0.00 01-JAN-00:15 152983.83 17-AUG-17:15
Cooling:EnergyTransfer:Zone:HEATEDBSMT 233.16 0.00 01-JAN-00:15 883.95 09-JUL-19:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29124.20 0.00 01-JAN-12:45 13164.37 17-AUG-16:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10860.74 0.00 01-JAN-12:45 12649.09 25-DEC-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18263.46 0.00 01-JAN-00:15 13164.37 17-AUG-16:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21324.49 0.00 06-JAN-14:00 11570.07 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13461.41 0.00 06-JAN-14:00 11570.07 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7863.08 0.00 01-JAN-00:15 6170.33 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 28235.11 0.00 14-JAN-13:15 14505.78 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 17530.80 0.00 14-JAN-13:15 14505.78 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10704.31 0.00 01-JAN-00:15 8287.98 08-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 30053.01 0.00 01-FEB-13:30 14617.02 25-DEC-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20475.59 0.00 01-FEB-13:30 14617.02 25-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9577.42 0.00 01-JAN-00:15 10724.00 08-JUL-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 22875.76 0.00 01-FEB-13:45 11722.44 25-DEC-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16235.59 0.00 01-FEB-13:45 11722.44 25-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6640.16 0.00 01-JAN-00:15 5665.67 29-JUN-17:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29484.77 0.00 01-FEB-13:45 14507.05 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 20117.68 0.00 01-FEB-13:45 14507.05 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 9367.09 0.00 01-JAN-00:15 7890.12 11-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24894.01 0.00 01-JAN-14:15 11235.00 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13385.76 0.00 01-JAN-14:15 11235.00 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11508.25 0.00 01-JAN-00:15 11033.82 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17537.80 0.00 01-JAN-12:30 8342.47 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9155.74 0.00 01-JAN-12:30 8342.47 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8382.07 0.00 01-JAN-00:15 5937.52 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24394.00 0.00 01-JAN-13:00 11263.35 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13156.41 0.00 01-JAN-13:00 11263.35 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11237.59 0.00 01-JAN-00:15 7891.52 08-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 25889.13 0.00 01-FEB-13:30 11309.24 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15879.14 0.00 01-FEB-13:30 11309.24 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10009.99 0.00 01-JAN-00:15 10445.62 08-JUL-17:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18720.96 0.00 26-JAN-20:15 8440.40 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11613.85 0.00 26-JAN-20:15 8440.40 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7107.11 0.00 01-JAN-00:15 5468.85 09-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 25389.34 0.00 01-FEB-13:30 11328.46 19-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15531.44 0.00 01-FEB-13:30 11328.46 19-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9857.90 0.00 01-JAN-00:15 7563.16 11-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 33884.66 0.00 01-FEB-14:15 15849.83 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 22893.05 0.00 01-FEB-14:15 15849.83 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 10991.62 0.00 01-JAN-00:15 8595.81 29-JUN-16:15
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 32269.75 0.00 01-FEB-13:00 15839.59 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 20608.53 0.00 01-FEB-13:00 15839.59 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 11661.22 0.00 01-JAN-00:15 8878.15 17-AUG-14:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 32991.47 0.00 14-JAN-15:00 15875.15 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 21016.82 0.00 14-JAN-15:00 15875.15 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 11974.65 0.00 01-JAN-00:15 12504.68 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 27200.60 0.00 01-FEB-14:30 13097.76 25-DEC-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 18860.20 0.00 01-FEB-14:30 13097.76 25-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 8340.40 0.00 01-JAN-00:15 7216.27 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 25417.26 0.00 01-FEB-13:15 12882.67 25-DEC-07:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 16453.05 0.00 01-FEB-13:15 12882.67 25-DEC-07:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 8964.21 0.00 01-JAN-00:15 7409.52 17-AUG-17:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 34530.63 0.00 01-FEB-14:00 16030.20 25-DEC-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 23296.47 0.00 01-FEB-14:00 16030.20 25-DEC-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 11234.16 0.00 01-JAN-00:15 12336.75 17-AUG-17:15
EnergyTransfer:Plant 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
WaterSystems:EnergyTransfer 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 160405.43 1274.38 09-AUG-02:15 43862.98 05-FEB-08:45
EnergyTransfer:HVAC 568307.19 0.00 03-MAY-22:15 226685.82 25-DEC-07:15
HeatingCoils:EnergyTransfer 305196.38 0.00 01-MAY-12:15 226685.82 25-DEC-07:15
CoolingCoils:EnergyTransfer 263110.81 0.00 01-JAN-00:15 215746.08 09-JUL-18:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 10860.666 -1520.93 0.000 0.000 3006.615 2771.241 10464.601 8705.289 0.000 854.094 5623.674 0.000 -5534.62 0.000 -18488.18 -0.31
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 13461.325 -654.81 0.000 0.000 3037.708 2771.241 10464.601 4072.567 0.000 806.232 0.000 0.000 -2208.67 0.000 -17005.95 -7536.05
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 17530.689 -891.43 0.000 0.000 3045.706 2771.241 10464.601 8811.182 0.000 853.943 0.000 0.000 -5319.72 0.000 -18142.72 -9310.67
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 20475.466 -797.57 0.000 0.000 3052.377 2771.241 10464.601 6090.648 0.000 854.354 0.000 0.000 -5780.63 0.000 -18013.78 -10336.98
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 16235.506 -552.98 0.000 0.000 3048.854 2771.241 10464.601 1252.234 0.000 806.299 0.000 0.000 -2456.13 0.000 -16865.59 -8616.87
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 20117.566 -780.07 0.000 0.000 3053.116 2771.241 10464.601 6087.664 0.000 852.447 0.000 0.000 -5563.69 0.000 -18028.11 -10387.76
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 13385.676 -958.37 0.000 0.000 3032.620 2771.241 10464.601 8727.729 0.000 625.205 0.000 0.000 -5564.71 0.000 -12767.88 -9166.39
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 9155.679 -698.03 0.000 0.000 3024.216 2771.241 10464.601 4063.320 0.000 577.429 0.000 0.000 -2242.21 0.000 -11638.16 -7794.11
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 13156.332 -935.84 0.000 0.000 3034.669 2771.241 10464.601 8790.179 0.000 625.148 0.000 0.000 -5400.87 0.000 -12775.87 -9427.90
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 15879.042 -833.60 0.000 0.000 3042.417 2771.241 10464.601 6082.579 0.000 625.554 0.000 0.000 -5867.05 0.000 -12673.18 -10315.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 11613.789 -591.86 0.000 0.000 3037.529 2771.241 10464.601 1250.519 0.000 577.697 0.000 0.000 -2490.60 0.000 -11528.63 -8589.05
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 15531.352 -820.94 0.000 0.000 3043.954 2771.241 10464.601 6073.298 0.000 624.418 0.000 0.000 -5640.48 0.000 -12682.24 -10328.25
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 22892.929 -915.35 0.000 0.000 3051.580 2771.241 10464.601 6075.703 0.000 846.038 0.000 0.000 -5614.45 0.000 -18080.99 -11415.07
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 20608.416 -971.12 0.000 0.000 3046.111 2771.241 10464.601 8820.567 0.000 846.165 0.000 0.000 -5356.94 0.000 -18159.60 -11379.38
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 21016.700 -997.21 0.000 0.000 3045.964 2771.241 10464.601 8755.005 0.000 846.564 0.000 0.000 -5505.85 0.000 -18137.17 -11282.57
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 18860.103 -694.56 0.000 0.000 3047.069 2771.241 10464.601 1247.777 0.000 799.453 0.000 0.000 -2474.16 0.000 -16923.73 -9452.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 16452.958 -746.51 0.000 0.000 3039.865 2771.241 10464.601 4074.594 0.000 798.912 0.000 0.000 -2218.06 0.000 -17008.42 -9411.55
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 23296.347 -935.54 0.000 0.000 3050.787 2771.241 10464.601 6071.539 0.000 847.105 0.000 0.000 -5828.23 0.000 -18069.39 -11369.99
HEATEDBSMT 0.000 0.000 14085.795 -19.42 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -13852.64
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4263.331 42161.582 0.000 0.000 0.000 -46424.91 -0.28
Total Facility 0.000 0.000 314616.335 -15316.14 0.000 0.000 54741.158 49882.340 188362.826 105052.391 0.000 17930.389 47785.256 0.000 -81067.09 0.000 -333414.49 -179973.15


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 17-AUG-16:30 0.00 0.00 0.00 -1.1 0.00 0.00 140.46 434.11 1350.56 6987.81 0.00 1622.35 2633.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17-AUG-17:05 0.00 0.00 0.00 -0.5 0.00 0.00 263.34 604.65 1664.02 544.20 0.00 1517.71 1577.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 08-JUL-08:49 0.00 0.00 0.00 -0.7 0.00 0.00 194.55 170.54 1179.68 6679.77 0.00 916.37 0.00 0.00 0.00 0.00 0.00 -851.9
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 08-JUL-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 259.41 604.65 1685.13 7324.40 0.00 1370.80 0.00 0.00 0.00 0.00 0.00 -501.7
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUN-17:06 0.00 0.00 0.00 -0.5 0.00 0.00 263.35 604.65 1664.02 742.16 0.00 1676.61 716.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11-JUL-08:47 0.00 0.00 0.00 -0.7 0.00 0.00 194.55 170.54 1155.86 6456.17 0.00 610.47 0.00 0.00 0.00 0.00 0.00 -695.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 17-AUG-17:05 0.00 0.00 0.00 -0.9 0.00 0.00 263.34 604.65 1664.02 5875.57 0.00 1176.68 1450.62 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17-AUG-17:05 0.00 0.00 0.00 -0.5 0.00 0.00 263.34 604.65 1664.02 549.59 0.00 1085.39 1771.31 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 08-JUL-08:49 0.00 0.00 0.00 -0.7 0.00 0.00 194.55 170.54 1179.68 6676.19 0.00 673.50 0.00 0.00 0.00 0.00 0.00 -1001.6
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 08-JUL-17:34 0.00 0.00 0.00 -0.9 0.00 0.00 260.36 604.65 1685.13 6823.33 0.00 961.50 122.99 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 09-JUL-20:08 0.00 0.00 0.00 -0.5 0.00 0.00 426.03 902.05 1651.67 126.62 0.00 704.52 1680.69 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11-JUL-08:47 0.00 0.00 0.00 -0.6 0.00 0.00 194.54 170.54 1155.86 6450.07 0.00 468.18 0.00 0.00 0.00 0.00 0.00 -874.1
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUN-16:08 0.00 0.00 0.00 -0.7 0.00 0.00 140.45 434.11 1350.56 1914.18 0.00 2061.43 2698.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 17-AUG-14:10 0.00 0.00 0.00 -0.7 0.00 0.00 115.17 116.28 1091.85 2826.08 0.00 1848.61 2882.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 17-AUG-17:05 0.00 0.00 0.00 -1.0 0.00 0.00 263.34 604.65 1664.02 5848.44 0.00 1603.39 2522.26 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 17-AUG-17:05 0.00 0.00 0.00 -0.6 0.00 0.00 263.34 604.65 1664.02 558.56 0.00 1512.27 2614.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 17-AUG-17:05 0.00 0.00 0.00 -0.6 0.00 0.00 263.34 604.65 1664.02 541.52 0.00 1512.27 2824.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 17-AUG-17:05 0.00 0.00 0.00 -1.0 0.00 0.00 263.34 604.65 1664.02 5867.75 0.00 1603.38 2334.89 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 09-JUL-19:04 0.00 0.00 0.00 -0.1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 883.95 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 17-AUG-17:05 0.00 0.00 0.00 -12.8 0.00 0.00 4740.06 10883.76 29952.39 46673.56 0.00 25787.51 51937.08 0.00 0.00 0.00 -16964.0 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 25-DEC-07:00 0.00 0.00 12648.97 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2931.6 0.00 -9854.7 -1901.1
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 25-DEC-07:15 0.00 0.00 11570.01 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1171.8 0.00 -9046.7 -3414.6
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25-DEC-07:15 0.00 0.00 14505.70 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2883.1 0.00 -9812.1 -3873.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 25-DEC-08:15 0.00 0.00 14616.59 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2587.6 0.00 -9633.0 -3937.4
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 25-DEC-08:15 0.00 0.00 11722.08 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1053.9 0.00 -8882.4 -3327.2
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 25-DEC-07:15 0.00 0.00 14506.98 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2905.5 0.00 -9812.1 -3852.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 11234.89 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2955.0 0.00 -5822.4 -4001.7
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 8342.38 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -1200.2 0.00 -5245.8 -3440.6
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 11263.23 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2950.8 0.00 -5822.4 -4034.2
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 11309.12 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2953.1 0.00 -5822.4 -4077.8
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 8440.30 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -1199.0 0.00 -5245.8 -3539.7
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 19-JAN-05:00 0.00 0.00 11328.34 0.00 0.00 0.00 526.31 186.05 831.88 0.00 0.00 0.00 0.00 0.00 -2949.1 0.00 -5822.4 -4101.0
LIVING_UNIT3_BACKROW_TOPFLOOR 25-DEC-07:15 0.00 0.00 15849.74 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2920.0 0.00 -9824.2 -5168.7
LIVING_UNIT3_FRONTROW_TOPFLOOR 25-DEC-07:15 0.00 0.00 15839.50 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2893.0 0.00 -9824.2 -5185.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 25-DEC-07:15 0.00 0.00 15875.02 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -2933.2 0.00 -9824.2 -5180.8
LIVING_UNIT2_BACKROW_TOPFLOOR 25-DEC-08:15 0.00 0.00 13097.36 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1061.0 0.00 -8893.5 -4684.3
LIVING_UNIT2_FRONTROW_TOPFLOOR 25-DEC-07:15 0.00 0.00 12882.60 0.00 0.00 0.00 464.78 387.60 1210.75 0.00 0.00 0.00 0.00 0.00 -1174.8 0.00 -9057.8 -4713.1
LIVING_UNIT1_BACKROW_TOPFLOOR 25-DEC-08:15 0.00 0.00 16029.74 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2607.5 0.00 -9645.1 -5318.6
HEATEDBSMT 19-JAN-08:00 0.00 0.00 5432.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -5432.0
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 25-DEC-07:15 0.00 0.00 233847.06 0.00 0.00 0.00 8366.07 6976.77 21793.53 0.00 0.00 0.00 0.00 0.00 -42231.8 0.00 -150666.8 -78084.8



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 544.606 2.00 2.00 1.00 44.9950 544.606 0.083 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.536 2.00 2.00 1.00 44.9950 244.536 0.184 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.100 2.00 2.00 1.00 44.9950 325.100 0.138 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 449.429 2.00 2.00 1.00 44.9950 449.429 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 232.654 2.00 2.00 1.00 44.9950 232.654 0.193 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 311.590 2.00 2.00 1.00 44.9950 311.590 0.144 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 449.316 2.00 2.00 1.00 44.9950 449.316 0.100 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 235.614 2.00 2.00 1.00 44.9950 235.614 0.191 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.882 2.00 2.00 1.00 44.9950 312.882 0.144 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 433.927 2.00 2.00 1.00 44.9950 433.927 0.104 1.000 44.9950 0.10
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 227.863 2.00 2.00 1.00 44.9950 227.863 0.197 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.748 2.00 2.00 1.00 44.9950 297.748 0.151 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 509.860 2.00 2.00 1.00 44.9950 509.860 0.088 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 297.390 2.00 2.00 1.00 44.9950 297.390 0.151 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.065 2.00 2.00 1.00 44.9950 362.065 0.124 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 507.525 2.00 2.00 1.00 44.9950 507.525 0.089 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 296.177 2.00 2.00 1.00 44.9950 296.177 0.152 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 354.548 2.00 2.00 1.00 44.9950 354.548 0.127 1.000 44.9950 0.13
CENTRAL SYSTEM_UNITHEATEDBSMT 44.995 0.00 0.00 1.00 44.9950 44.995 1.000 1.000 44.9950 1.00


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 197.911 2.00 2.00 1.00 44.9950 197.911 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 185.585 2.00 2.00 1.00 44.9950 185.585 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 233.513 2.00 2.00 1.00 44.9950 233.513 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 233.680 2.00 2.00 1.00 44.9950 233.680 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 185.596 2.00 2.00 1.00 44.9950 185.596 1.000 1.000 44.9950 0.24
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 233.483 2.00 2.00 1.00 44.9950 233.483 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 193.334 2.00 2.00 1.00 44.9950 193.334 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 144.714 2.00 2.00 1.00 44.9950 144.714 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 193.125 2.00 2.00 1.00 44.9950 193.125 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 193.387 2.00 2.00 1.00 44.9950 193.387 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 144.725 2.00 2.00 1.00 44.9950 144.725 1.000 1.000 44.9950 0.31
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 193.099 2.00 2.00 1.00 44.9950 193.099 1.000 1.000 44.9950 0.23
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 264.314 2.00 2.00 1.00 44.9950 264.314 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 215.848 2.00 2.00 1.00 44.9950 215.848 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 264.045 2.00 2.00 1.00 44.9950 264.045 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 264.417 2.00 2.00 1.00 44.9950 264.417 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 215.922 2.00 2.00 1.00 44.9950 215.922 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.094 2.00 2.00 1.00 44.9950 264.094 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNITHEATEDBSMT 97.821 0.00 0.00 1.00 44.9950 97.821 1.000 1.000 44.9950 0.46


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.00 0.000000 7794.39 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.39 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   544.606 544.6061 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   244.536 244.5357 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   325.100 325.0997 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   449.429 449.4288 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   232.654 232.6537 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   311.590 311.5901 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   449.316 449.3157 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   235.614 235.6142 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   312.882 312.8820 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   433.927 433.9275 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   227.863 227.8635 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   297.748 297.7483 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   354.548 354.5477 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   362.065 362.0648 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   509.860 509.8600 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   296.177 296.1766 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   297.390 297.3901 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   507.525 507.5251 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   44.995 44.9950 1168.9135 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 544.61 544.606 544.61 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.54 244.536 244.54 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.10 325.100 325.10 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 449.43 449.429 449.43 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 232.65 232.654 232.65 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 311.59 311.590 311.59 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 449.32 449.316 449.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 235.61 235.614 235.61 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.88 312.882 312.88 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 433.93 433.927 433.93 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 227.86 227.863 227.86 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.75 297.748 297.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 509.86 509.860 509.86 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 297.39 297.390 297.39 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.06 362.065 362.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 507.53 507.525 507.53 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 296.18 296.177 296.18 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 354.55 354.548 354.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 44.99 44.995 44.99 1168.9135 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   197.911 197.911 197.911 44.9950 0.227 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   185.585 185.585 185.585 44.9950 0.242 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   233.513 233.513 233.513 44.9950 0.193 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   233.680 233.680 233.680 44.9950 0.193 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   185.596 185.596 185.596 44.9950 0.242 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   233.483 233.483 233.483 44.9950 0.193 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   193.334 193.334 193.334 44.9950 0.233 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   144.714 144.714 144.714 44.9950 0.311 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   193.125 193.125 193.125 44.9950 0.233 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   193.387 193.387 193.387 44.9950 0.233 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   144.725 144.725 144.725 44.9950 0.311 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   193.099 193.099 193.099 44.9950 0.233 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   264.094 264.094 264.094 44.9950 0.170 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   264.045 264.045 264.045 44.9950 0.170 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   264.314 264.314 264.314 44.9950 0.170 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   215.922 215.922 215.922 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   215.848 215.848 215.848 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   264.417 264.417 264.417 44.9950 0.170 1.000 0.000 0.000 0.000 0.000 1.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   97.821 97.821 97.821 44.9950 0.460 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 197.91 197.911 197.91 197.91 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 185.59 185.585 185.59 185.59 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 233.51 233.513 233.51 233.51 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 233.68 233.680 233.68 233.68 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 185.60 185.596 185.60 185.60 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 233.48 233.483 233.48 233.48 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 193.33 193.334 193.33 193.33 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 144.71 144.714 144.71 144.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 193.12 193.125 193.12 193.12 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 193.39 193.387 193.39 193.39 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 144.72 144.725 144.72 144.72 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 193.10 193.099 193.10 193.10 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 264.31 264.314 264.31 264.31 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 215.85 215.848 215.85 215.85 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 264.05 264.045 264.05 264.05 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 264.42 264.417 264.42 264.42 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 215.92 215.922 215.92 215.92 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.09 264.094 264.09 264.09 44.9950 1.000
CENTRAL SYSTEM_UNITHEATEDBSMT 97.82 97.821 97.82 97.82 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Sec1.1A-General Information

Data
Weather File ANNUAL ** Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Total gross floor area [ft2] 39005.17
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 29404.35 9600.82  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 20.25
Number of hours not met 20.25


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 2290.15 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 88.11 0.00 0.00 0.00 0.00
Space Heating 89384.62 65948.06 0.00 0.00 0.00 0.00
Space Cooling 17672.15 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 5805.80 2084.29 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 51607.77 37280.71 0.00 0.00 0.00 0.00
Receptacle Equipment 88303.07 8348.87 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 270389.67   0.00   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 923223.14
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 923223.14


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 2.29
Space Cooling 0.45
Fans-Interior 0.15
Service Water Heating 1.32
Receptacle Equipment 2.26
Miscellaneous 0.08
Subtotal 6.93


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 5.40
Space Heating 33.06
Space Cooling 6.54
Fans-Interior 2.15
Service Water Heating 19.09
Receptacle Equipment 32.66
Miscellaneous 1.11



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 97.82
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 544.61
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 244.54
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 325.10
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 449.43
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 232.65
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 311.59
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 449.32
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 235.61
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 312.88
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 433.93
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 227.86
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 297.75
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 354.55
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 362.06
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 509.86
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 296.18
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 297.39
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 507.53
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 544.61
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 244.54
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 325.10
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 449.43
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 232.65
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 311.59
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 449.32
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 235.61
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 312.88
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 433.93
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 227.86
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 297.75
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 509.86
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 297.39
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 362.06
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 507.53
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 296.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 354.55
CENTRAL SYSTEM_UNITHEATEDBSMT 97.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 544.61 1.45 0.737777
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 244.54 0.793539 0.682696
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 325.10 0.993929 0.698155
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 449.43 1.24 0.726030
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 232.65 0.732716 0.690344
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 311.59 0.896157 0.714989
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 449.32 1.21 0.734606
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 235.61 0.721389 0.697768
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 312.88 0.935844 0.704073
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 433.93 1.17 0.732991
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 227.86 0.696381 0.698257
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 297.75 0.846379 0.718333
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 509.86 1.37 0.734048
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 297.39 0.886215 0.705088
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 362.06 1.07 0.706612
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 507.53 1.37 0.734447
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 296.18 0.878682 0.706309
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 354.55 1.06 0.705201
DX COOLING COIL_UNITHEATEDBSMT 97.82 0.326003 0.676083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 544.61 544.61 544.61 13523.75 1.45 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 244.54 244.54 244.54 12859.68 0.793539 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 325.10 325.10 325.10 15441.94 0.993929 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 449.43 449.43 449.43 15450.92 1.24 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 232.65 232.65 232.65 12860.23 0.732716 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 311.59 311.59 311.59 15440.31 0.896157 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 449.32 449.32 449.32 13276.47 1.21 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 235.61 235.61 235.61 10657.25 0.721389 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 312.88 312.88 312.88 13265.17 0.935844 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 433.93 433.93 433.93 13279.30 1.17 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 227.86 227.86 227.86 10657.83 0.696381 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 297.75 297.75 297.75 13263.80 0.846379 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 509.86 509.86 509.86 17101.30 1.37 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 297.39 297.39 297.39 14490.00 0.886215 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 362.06 362.06 362.06 17086.83 1.07 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 507.53 507.53 507.53 17106.83 1.37 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 296.18 296.18 296.18 14493.98 0.878682 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 354.55 354.55 354.55 17089.45 1.06 1.00
ACANDF_UNITHEATEDBSMT 97.82 97.82 97.82 8130.66 0.326003 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 544.61
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 244.54
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 325.10
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 449.43
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 232.65
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 311.59
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 449.32
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 235.61
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 312.88
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 433.93
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 227.86
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 297.75
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 509.86
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 297.39
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 362.06
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 507.53
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 296.18
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 354.55
SUPPLY FAN_UNITHEATEDBSMT 97.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 13523.75
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 12859.68
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 15441.94
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 15450.92
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 12860.23
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 15440.31
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 13276.47
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 10657.25
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 13265.17
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 13279.30
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 10657.83
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 13263.80
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 17101.30
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 14490.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 17086.83
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 17106.83
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 14493.98
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 17089.45
MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT 8130.66
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:37

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 3.833 0.045 678.479 47.986 48.031
February 45.875 0.971 552.937 34.050 35.021
March 153.118 6.215 424.187 16.354 22.569
April 322.943 12.844 127.333 2.806 15.649
May 563.140 33.954 47.221 0.717 34.672
June 696.423 54.192 1.417 0.001 54.193
July 744.000 69.412 0.000 0.000 69.412
August 744.000 63.457 0.000 0.000 63.457
September 660.537 44.673 1.000 0.002 44.675
October 353.097 15.773 180.354 4.702 20.474
November 174.542 4.895 358.233 10.996 15.891
December 61.142 1.472 595.992 39.117 40.590
           
Annual Sum or Average 4522.650 307.903 2967.154 156.731 464.635
Minimum of Months 3.833 0.045 0.000 0.000 15.649
Maximum of Months 744.000 69.412 678.479 47.986 69.412



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 734.271 25.362 25.362
February 9.375 0.097 620.992 19.060 19.157
March 62.900 1.182 563.862 11.216 12.398
April 151.229 2.180 341.258 3.560 5.740
May 380.620 11.462 141.820 1.215 12.677
June 622.270 22.466 9.250 0.046 22.512
July 735.513 31.637 0.000 0.000 31.637
August 701.990 28.610 0.000 0.000 28.610
September 529.622 18.211 22.438 0.095 18.306
October 209.812 5.035 326.458 4.194 9.228
November 53.537 0.883 493.145 8.244 9.127
December 24.958 0.314 668.083 21.188 21.501
           
Annual Sum or Average 3481.827 122.075 3921.577 94.180 216.255
Minimum of Months 0.000 0.000 0.000 0.000 5.740
Maximum of Months 735.513 31.637 734.271 25.362 31.637



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 738.833 35.986 35.986
February 10.208 0.104 631.858 26.488 26.592
March 69.946 1.620 551.350 15.570 17.191
April 186.075 4.036 352.104 5.100 9.136
May 400.786 17.047 151.625 1.959 19.006
June 612.974 32.381 14.875 0.106 32.486
July 723.771 42.777 0.000 0.000 42.777
August 687.170 38.238 0.500 0.000 38.238
September 532.720 23.866 50.875 0.324 24.189
October 201.391 6.279 362.562 6.619 12.898
November 48.646 1.022 535.742 12.670 13.692
December 20.458 0.286 689.292 30.623 30.909
           
Annual Sum or Average 3494.145 167.656 4079.617 135.445 303.101
Minimum of Months 0.000 0.000 0.000 0.000 9.136
Maximum of Months 723.771 42.777 738.833 35.986 42.777



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 55.779 55.779
February 4.750 0.033 656.100 41.803 41.837
March 49.242 1.447 626.521 25.621 27.067
April 122.812 3.528 415.594 8.582 12.109
May 358.619 18.213 180.461 3.039 21.252
June 591.536 33.689 21.375 0.200 33.889
July 723.594 46.449 0.000 0.000 46.449
August 679.158 39.476 0.000 0.000 39.476
September 478.790 22.030 72.181 0.626 22.656
October 119.135 3.457 466.152 11.908 15.365
November 3.625 0.035 633.104 21.763 21.799
December 4.000 0.010 711.625 47.069 47.079
           
Annual Sum or Average 3135.261 168.366 4527.113 216.390 384.756
Minimum of Months 0.000 0.000 0.000 0.000 12.109
Maximum of Months 723.594 46.449 744.000 55.779 55.779



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 28.244 28.244
February 0.000 0.000 648.000 21.335 21.335
March 36.712 0.692 661.079 13.164 13.855
April 75.417 0.764 404.458 4.006 4.770
May 361.148 10.512 156.117 1.226 11.737
June 622.708 22.192 9.833 0.043 22.235
July 736.325 31.409 0.000 0.000 31.409
August 698.440 26.990 0.000 0.000 26.990
September 491.756 14.509 32.194 0.126 14.636
October 98.037 1.593 463.232 5.622 7.215
November 0.000 0.000 652.750 10.752 10.752
December 3.750 0.012 714.375 23.673 23.685
           
Annual Sum or Average 3124.293 108.673 4486.039 108.191 216.863
Minimum of Months 0.000 0.000 0.000 0.000 4.770
Maximum of Months 736.325 31.409 744.000 28.244 31.409



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 38.972 38.972
February 0.000 0.000 658.250 28.817 28.817
March 36.958 0.917 656.417 17.374 18.292
April 131.626 2.109 395.333 5.354 7.463
May 396.568 16.528 153.146 1.905 18.433
June 615.027 32.984 14.375 0.100 33.083
July 723.958 43.627 0.000 0.000 43.627
August 686.628 37.692 0.500 0.000 37.693
September 518.058 20.773 53.042 0.332 21.105
October 109.776 2.434 462.904 7.870 10.304
November 0.000 0.000 666.563 15.225 15.225
December 0.000 0.000 721.000 33.201 33.201
           
Annual Sum or Average 3218.600 157.066 4525.529 149.151 306.216
Minimum of Months 0.000 0.000 0.000 0.000 7.463
Maximum of Months 723.958 43.627 744.000 38.972 43.627



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 1.000 0.004 718.750 44.414 44.418
February 14.292 0.285 594.650 32.440 32.724
March 102.500 3.230 514.158 18.948 22.178
April 208.038 6.841 306.250 5.628 12.469
May 407.818 21.036 133.000 2.048 23.084
June 623.673 35.879 9.750 0.086 35.965
July 736.417 48.299 0.000 0.000 48.299
August 699.597 43.194 0.000 0.000 43.194
September 532.162 27.723 31.054 0.232 27.955
October 224.450 8.712 316.850 7.577 16.289
November 74.933 1.831 477.729 14.873 16.705
December 24.750 0.483 653.125 37.379 37.862
           
Annual Sum or Average 3649.629 197.516 3755.316 163.626 361.142
Minimum of Months 1.000 0.004 0.000 0.000 12.469
Maximum of Months 736.417 48.299 718.750 44.414 48.299



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 705.792 20.814 20.814
February 12.746 0.151 595.250 15.179 15.330
March 91.146 1.538 494.292 8.554 10.092
April 195.408 3.059 264.375 2.233 5.292
May 423.918 12.910 101.944 0.766 13.676
June 656.793 24.110 4.500 0.012 24.122
July 744.000 32.927 0.000 0.000 32.927
August 720.975 30.236 0.000 0.000 30.236
September 567.633 19.779 8.875 0.027 19.806
October 250.129 5.957 263.750 2.946 8.903
November 78.192 1.183 436.350 6.272 7.455
December 30.625 0.417 636.313 17.382 17.798
           
Annual Sum or Average 3771.565 132.266 3511.440 74.186 206.451
Minimum of Months 0.000 0.000 0.000 0.000 5.292
Maximum of Months 744.000 32.927 705.792 20.814 32.927



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 726.521 31.182 31.182
February 14.042 0.160 606.050 22.333 22.493
March 92.779 1.978 506.483 12.695 14.673
April 232.907 5.030 278.461 3.539 8.568
May 438.289 18.292 120.875 1.368 19.660
June 642.623 33.429 7.000 0.040 33.469
July 734.250 43.265 0.000 0.000 43.265
August 702.034 39.106 0.000 0.000 39.106
September 557.625 24.913 24.500 0.143 25.056
October 233.764 6.981 310.750 5.142 12.122
November 58.721 1.216 490.658 10.484 11.701
December 24.750 0.353 669.417 26.594 26.947
           
Annual Sum or Average 3731.783 174.723 3740.715 113.520 288.244
Minimum of Months 0.000 0.000 0.000 0.000 8.568
Maximum of Months 734.250 43.265 726.521 31.182 43.265



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 49.862 49.862
February 7.250 0.061 642.858 36.584 36.644
March 60.250 1.638 597.521 21.642 23.280
April 156.396 4.286 348.321 6.304 10.589
May 393.381 19.436 146.243 2.151 21.587
June 623.483 34.852 10.750 0.090 34.942
July 735.714 47.121 0.000 0.000 47.121
August 696.218 40.588 0.000 0.000 40.588
September 503.491 23.130 41.098 0.321 23.451
October 139.540 3.877 419.458 9.793 13.670
November 8.562 0.053 608.875 18.890 18.942
December 6.125 0.042 706.708 42.051 42.093
           
Annual Sum or Average 3330.411 175.083 4265.834 187.687 362.770
Minimum of Months 0.000 0.000 0.000 0.000 10.589
Maximum of Months 735.714 47.121 744.000 49.862 49.862



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.500 24.770 24.770
February 3.000 0.009 644.521 18.241 18.250
March 46.392 0.853 620.917 10.677 11.530
April 114.058 1.301 312.833 2.619 3.920
May 410.000 11.804 105.763 0.771 12.575
June 659.117 23.487 3.685 0.009 23.496
July 744.000 32.140 0.000 0.000 32.140
August 719.844 28.144 0.000 0.000 28.144
September 535.779 15.804 14.250 0.043 15.847
October 125.483 2.053 405.375 4.293 6.346
November 3.250 0.011 612.225 8.964 8.975
December 7.000 0.044 704.417 20.699 20.742
           
Annual Sum or Average 3367.923 115.650 4165.485 91.086 206.736
Minimum of Months 0.000 0.000 0.000 0.000 3.920
Maximum of Months 744.000 32.140 741.500 24.770 32.140



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 34.514 34.514
February 0.000 0.000 643.018 24.883 24.883
March 42.667 1.048 614.841 14.327 15.375
April 174.670 2.898 310.692 3.707 6.606
May 433.754 17.759 121.750 1.324 19.083
June 643.717 33.880 6.750 0.037 33.918
July 734.875 43.871 0.000 0.000 43.871
August 702.243 38.382 0.000 0.000 38.382
September 544.507 21.803 26.500 0.149 21.953
October 134.135 2.805 413.146 6.276 9.082
November 1.000 0.001 643.392 13.065 13.066
December 5.000 0.021 714.250 29.442 29.463
           
Annual Sum or Average 3416.568 162.468 4238.338 127.726 290.194
Minimum of Months 0.000 0.000 0.000 0.000 6.606
Maximum of Months 734.875 43.871 744.000 34.514 43.871



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.917 59.109 59.109
February 7.375 0.136 637.830 44.060 44.196
March 65.000 2.457 582.083 26.812 29.269
April 164.479 5.940 389.050 9.287 15.227
May 371.356 22.107 181.000 3.545 25.652
June 590.871 39.176 21.875 0.237 39.413
July 724.468 53.856 0.000 0.000 53.856
August 679.636 47.289 0.000 0.000 47.289
September 498.993 28.571 73.958 0.748 29.319
October 175.679 7.450 406.778 11.938 19.388
November 39.833 0.951 565.558 21.753 22.704
December 16.542 0.235 696.821 49.964 50.200
           
Annual Sum or Average 3334.232 208.167 4296.871 227.453 435.620
Minimum of Months 0.000 0.000 0.000 0.000 15.227
Maximum of Months 724.468 53.856 741.917 59.109 59.109



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 32.966 32.966
February 7.500 0.062 636.563 24.680 24.742
March 53.283 1.213 590.588 14.760 15.973
April 148.475 2.580 360.950 4.711 7.291
May 378.420 14.415 162.200 1.668 16.084
June 619.002 27.849 11.250 0.072 27.922
July 736.951 39.041 0.000 0.000 39.041
August 695.338 34.896 0.000 0.000 34.896
September 516.013 21.154 39.201 0.193 21.348
October 185.787 5.024 365.455 5.902 10.926
November 40.750 0.528 543.117 11.371 11.900
December 16.250 0.183 693.155 27.679 27.863
           
Annual Sum or Average 3397.769 146.946 4146.478 124.005 270.951
Minimum of Months 0.000 0.000 0.000 0.000 7.291
Maximum of Months 736.951 39.041 744.000 32.966 39.041



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 42.297 42.297
February 6.083 0.035 644.917 31.155 31.190
March 53.829 1.486 586.429 18.489 19.975
April 176.115 4.030 359.854 5.897 9.927
May 401.083 19.313 154.958 2.259 21.572
June 618.023 36.743 14.125 0.111 36.854
July 726.304 48.818 0.000 0.000 48.818
August 688.128 43.284 0.500 0.001 43.284
September 528.287 25.853 56.375 0.407 26.260
October 182.688 5.860 389.521 8.070 13.930
November 36.437 0.597 580.633 15.487 16.084
December 13.958 0.157 698.708 36.058 36.215
           
Annual Sum or Average 3430.936 186.175 4230.021 160.230 346.404
Minimum of Months 0.000 0.000 0.000 0.000 9.927
Maximum of Months 726.304 48.818 744.000 42.297 48.818



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 64.452 64.452
February 4.125 0.016 657.750 48.066 48.081
March 50.171 1.660 623.558 29.395 31.055
April 146.388 4.783 409.292 9.746 14.530
May 366.497 21.704 183.342 3.583 25.287
June 592.681 39.103 21.411 0.231 39.334
July 724.829 53.772 0.000 0.000 53.772
August 678.733 46.362 0.000 0.000 46.362
September 482.689 25.955 80.734 0.818 26.773
October 125.024 4.220 469.787 14.101 18.320
November 5.417 0.027 642.354 25.831 25.858
December 3.750 0.008 714.458 54.712 54.720
           
Annual Sum or Average 3180.302 197.610 4546.686 250.934 448.544
Minimum of Months 0.000 0.000 0.000 0.000 14.530
Maximum of Months 724.829 53.772 744.000 64.452 64.452



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 36.855 36.855
February 0.000 0.000 653.375 27.600 27.600
March 38.500 0.923 650.500 16.877 17.800
April 111.104 1.749 389.030 5.081 6.830
May 372.503 14.134 166.929 1.685 15.819
June 621.944 27.875 11.250 0.069 27.944
July 737.304 39.058 0.000 0.000 39.058
August 693.788 34.119 0.000 0.000 34.119
September 494.718 18.750 45.182 0.228 18.977
October 116.374 2.295 466.187 7.552 9.847
November 0.000 0.000 661.292 14.462 14.462
December 3.250 0.010 717.000 31.136 31.146
           
Annual Sum or Average 3189.485 138.912 4504.744 141.544 280.456
Minimum of Months 0.000 0.000 0.000 0.000 6.830
Maximum of Months 737.304 39.058 744.000 36.855 39.058



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 45.402 45.402
February 0.000 0.000 659.750 33.464 33.464
March 37.083 1.080 642.482 20.142 21.221
April 150.520 3.013 379.812 6.087 9.100
May 399.022 18.882 157.517 2.231 21.113
June 619.363 36.437 14.000 0.107 36.544
July 726.429 48.388 0.000 0.000 48.388
August 687.420 42.181 0.500 0.001 42.182
September 519.183 23.323 60.175 0.418 23.741
October 120.389 2.950 475.550 9.424 12.374
November 0.000 0.000 677.500 18.234 18.234
December 0.000 0.000 722.500 38.857 38.857
           
Annual Sum or Average 3259.410 176.254 4533.786 174.366 350.620
Minimum of Months 0.000 0.000 0.000 0.000 9.100
Maximum of Months 726.429 48.388 744.000 45.402 48.388



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 14.245 14.245
February 0.000 0.000 672.000 11.830 11.830
March 0.000 0.000 744.000 10.279 10.279
April 0.000 0.000 720.000 6.428 6.428
May 0.000 0.000 82.300 0.172 0.172
June 52.304 0.132 0.000 0.000 0.132
July 348.167 1.478 0.000 0.000 1.478
August 302.751 1.248 0.000 0.000 1.248
September 36.146 0.079 0.000 0.000 0.079
October 0.000 0.000 124.392 0.199 0.199
November 0.000 0.000 717.250 7.445 7.445
December 0.000 0.000 744.000 12.304 12.304
           
Annual Sum or Average 739.367 2.937 4547.942 62.903 65.840
Minimum of Months 0.000 0.000 0.000 0.000 0.079
Maximum of Months 348.167 1.478 744.000 14.245 14.245



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4246.12 0.00
February 0.00 3335.80 0.00
March 0.00 1447.13 0.00
April 0.00 256.52 0.00
May 0.00 63.48 0.00
June 0.00 0.10 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.22 0.00
October 0.00 416.02 0.00
November 0.00 1005.42 0.00
December 0.00 3461.35 0.00
       
Annual Sum or Average 0.00 1177.88 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4246.12 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4752.63 0.00
February 0.00 3954.42 0.00
March 0.00 2101.78 0.00
April 0.00 689.34 0.00
May 0.00 227.66 0.00
June 0.00 8.95 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 18.40 0.00
October 0.00 785.88 0.00
November 0.00 1596.35 0.00
December 0.00 3970.45 0.00
       
Annual Sum or Average 0.00 1498.92 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4752.63 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6090.99 0.00
February 0.00 4963.60 0.00
March 0.00 2635.40 0.00
April 0.00 891.91 0.00
May 0.00 331.54 0.00
June 0.00 18.49 0.00
July 0.00 0.00 0.00
August 0.00 0.05 0.00
September 0.00 56.58 0.00
October 0.00 1120.28 0.00
November 0.00 2215.98 0.00
December 0.00 5183.23 0.00
       
Annual Sum or Average 0.00 1947.06 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6090.99 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6833.20 0.00
February 0.00 5669.82 0.00
March 0.00 3138.69 0.00
April 0.00 1086.39 0.00
May 0.00 372.30 0.00
June 0.00 25.38 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 79.24 0.00
October 0.00 1458.75 0.00
November 0.00 2755.02 0.00
December 0.00 5766.28 0.00
       
Annual Sum or Average 0.00 2251.46 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6833.20 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5563.30 0.00
February 0.00 4652.57 0.00
March 0.00 2592.85 0.00
April 0.00 815.27 0.00
May 0.00 241.48 0.00
June 0.00 8.82 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 25.72 0.00
October 0.00 1107.31 0.00
November 0.00 2188.43 0.00
December 0.00 4662.91 0.00
       
Annual Sum or Average 0.00 1809.92 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5563.30 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6881.61 0.00
February 0.00 5633.66 0.00
March 0.00 3067.92 0.00
April 0.00 976.91 0.00
May 0.00 336.38 0.00
June 0.00 18.23 0.00
July 0.00 0.00 0.00
August 0.00 0.07 0.00
September 0.00 60.54 0.00
October 0.00 1389.59 0.00
November 0.00 2778.06 0.00
December 0.00 5862.62 0.00
       
Annual Sum or Average 0.00 2236.82 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6881.61 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4676.43 0.00
February 0.00 3781.60 0.00
March 0.00 1995.05 0.00
April 0.00 612.34 0.00
May 0.00 215.66 0.00
June 0.00 9.39 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 25.22 0.00
October 0.00 797.83 0.00
November 0.00 1618.23 0.00
December 0.00 3935.75 0.00
       
Annual Sum or Average 0.00 1463.24 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4676.43 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3354.73 0.00
February 0.00 2708.74 0.00
March 0.00 1378.77 0.00
April 0.00 371.88 0.00
May 0.00 123.45 0.00
June 0.00 2.05 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 4.52 0.00
October 0.00 474.89 0.00
November 0.00 1044.60 0.00
December 0.00 2801.57 0.00
       
Annual Sum or Average 0.00 1015.54 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3354.73 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4710.92 0.00
February 0.00 3735.52 0.00
March 0.00 1917.84 0.00
April 0.00 552.44 0.00
May 0.00 206.64 0.00
June 0.00 6.28 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 22.31 0.00
October 0.00 776.82 0.00
November 0.00 1636.74 0.00
December 0.00 4017.75 0.00
       
Annual Sum or Average 0.00 1456.59 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4710.92 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5437.41 0.00
February 0.00 4416.85 0.00
March 0.00 2360.07 0.00
April 0.00 710.34 0.00
May 0.00 234.58 0.00
June 0.00 10.15 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 36.12 0.00
October 0.00 1067.89 0.00
November 0.00 2128.55 0.00
December 0.00 4585.60 0.00
       
Annual Sum or Average 0.00 1738.30 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5437.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4128.45 0.00
February 0.00 3365.94 0.00
March 0.00 1779.53 0.00
April 0.00 451.07 0.00
May 0.00 128.46 0.00
June 0.00 1.53 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 7.37 0.00
October 0.00 715.52 0.00
November 0.00 1543.89 0.00
December 0.00 3449.84 0.00
       
Annual Sum or Average 0.00 1289.36 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4128.45 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5478.71 0.00
February 0.00 4373.06 0.00
March 0.00 2274.25 0.00
April 0.00 608.13 0.00
May 0.00 210.22 0.00
June 0.00 6.13 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 24.49 0.00
October 0.00 996.27 0.00
November 0.00 2143.12 0.00
December 0.00 4673.59 0.00
       
Annual Sum or Average 0.00 1721.99 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5478.71 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7064.73 0.00
February 0.00 5830.25 0.00
March 0.00 3204.58 0.00
April 0.00 1147.00 0.00
May 0.00 423.70 0.00
June 0.00 29.33 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 92.38 0.00
October 0.00 1426.80 0.00
November 0.00 2686.57 0.00
December 0.00 5971.73 0.00
       
Annual Sum or Average 0.00 2308.89 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 7064.73 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5723.65 0.00
February 0.00 4744.17 0.00
March 0.00 2562.68 0.00
April 0.00 845.28 0.00
May 0.00 289.62 0.00
June 0.00 12.95 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 34.72 0.00
October 0.00 1024.70 0.00
November 0.00 2040.15 0.00
December 0.00 4805.76 0.00
       
Annual Sum or Average 0.00 1828.57 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 5723.65 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7112.88 0.00
February 0.00 5800.56 0.00
March 0.00 3109.14 0.00
April 0.00 1024.74 0.00
May 0.00 379.82 0.00
June 0.00 19.28 0.00
July 0.00 0.00 0.00
August 0.00 0.10 0.00
September 0.00 70.66 0.00
October 0.00 1357.06 0.00
November 0.00 2691.29 0.00
December 0.00 6063.76 0.00
       
Annual Sum or Average 0.00 2288.49 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 7112.88 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7741.26 0.00
February 0.00 6391.67 0.00
March 0.00 3530.60 0.00
April 0.00 1209.64 0.00
May 0.00 430.37 0.00
June 0.00 28.67 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 101.52 0.00
October 0.00 1693.62 0.00
November 0.00 3205.91 0.00
December 0.00 6571.40 0.00
       
Annual Sum or Average 0.00 2559.79 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 7741.26 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6426.75 0.00
February 0.00 5328.61 0.00
March 0.00 2943.00 0.00
April 0.00 915.60 0.00
May 0.00 293.83 0.00
June 0.00 12.36 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 41.04 0.00
October 0.00 1316.98 0.00
November 0.00 2605.92 0.00
December 0.00 5429.53 0.00
       
Annual Sum or Average 0.00 2096.33 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 6426.75 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 7798.10 0.00
February 0.00 6363.62 0.00
March 0.00 3459.51 0.00
April 0.00 1080.42 0.00
May 0.00 383.20 0.00
June 0.00 18.93 0.00
July 0.00 0.00 0.00
August 0.00 0.11 0.00
September 0.00 74.16 0.00
October 0.00 1618.63 0.00
November 0.00 3236.22 0.00
December 0.00 6673.94 0.00
       
Annual Sum or Average 0.00 2543.59 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 7798.10 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4219.16 0.00
February 0.00 3879.29 0.00
March 0.00 3044.43 0.00
April 0.00 1967.37 0.00
May 0.00 51.06 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 58.87 0.00
November 0.00 2278.61 0.00
December 0.00 3644.22 0.00
       
Annual Sum or Average 0.00 1582.33 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 4219.16 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.30
June 0.00 0.00 0.49
July 0.00 0.00 0.62
August 0.00 0.00 0.56
September 0.00 0.00 0.42
October 0.00 0.00 0.14
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.62



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.12
June 0.00 0.00 0.25
July 0.00 0.00 0.35
August 0.00 0.00 0.32
September 0.00 0.00 0.21
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.04
May 0.00 0.00 0.17
June 0.00 0.00 0.34
July 0.00 0.00 0.45
August 0.00 0.00 0.40
September 0.00 0.00 0.26
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.45



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.17
June 0.00 0.00 0.32
July 0.00 0.00 0.43
August 0.00 0.00 0.36
September 0.00 0.00 0.22
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.01
May 0.00 0.00 0.11
June 0.00 0.00 0.24
July 0.00 0.00 0.34
August 0.00 0.00 0.29
September 0.00 0.00 0.17
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.16
June 0.00 0.00 0.33
July 0.00 0.00 0.43
August 0.00 0.00 0.37
September 0.00 0.00 0.21
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.03
April 0.00 0.00 0.06
May 0.00 0.00 0.19
June 0.00 0.00 0.33
July 0.00 0.00 0.43
August 0.00 0.00 0.39
September 0.00 0.00 0.26
October 0.00 0.00 0.08
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.13
June 0.00 0.00 0.26
July 0.00 0.00 0.34
August 0.00 0.00 0.32
September 0.00 0.00 0.22
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.05
May 0.00 0.00 0.18
June 0.00 0.00 0.35
July 0.00 0.00 0.44
August 0.00 0.00 0.40
September 0.00 0.00 0.26
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.17
June 0.00 0.00 0.32
July 0.00 0.00 0.42
August 0.00 0.00 0.36
September 0.00 0.00 0.22
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.42



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.01
May 0.00 0.00 0.12
June 0.00 0.00 0.25
July 0.00 0.00 0.34
August 0.00 0.00 0.29
September 0.00 0.00 0.17
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.17
June 0.00 0.00 0.34
July 0.00 0.00 0.43
August 0.00 0.00 0.37
September 0.00 0.00 0.22
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.05
May 0.00 0.00 0.20
June 0.00 0.00 0.36
July 0.00 0.00 0.48
August 0.00 0.00 0.42
September 0.00 0.00 0.27
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.14
June 0.00 0.00 0.29
July 0.00 0.00 0.40
August 0.00 0.00 0.35
September 0.00 0.00 0.23
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.19
June 0.00 0.00 0.38
July 0.00 0.00 0.49
August 0.00 0.00 0.43
September 0.00 0.00 0.27
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.19
June 0.00 0.00 0.36
July 0.00 0.00 0.48
August 0.00 0.00 0.41
September 0.00 0.00 0.25
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.02
May 0.00 0.00 0.14
June 0.00 0.00 0.29
July 0.00 0.00 0.40
August 0.00 0.00 0.34
September 0.00 0.00 0.20
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.03
May 0.00 0.00 0.19
June 0.00 0.00 0.38
July 0.00 0.00 0.49
August 0.00 0.00 0.42
September 0.00 0.00 0.25
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.15
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.01
August 0.00 0.00 0.01
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.01



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47
Minimum of Months 0.00 0.00 852.43 634.66
Maximum of Months 0.00 0.00 1381.37 1014.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:37

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1362.11 1014.13
February 0.00 0.00 1381.37 928.94
March 0.00 0.00 1332.87 992.36
April 0.00 0.00 1228.71 885.30
May 0.00 0.00 1091.59 812.72
June 0.00 0.00 959.85 691.59
July 0.00 0.00 876.81 652.81
August 0.00 0.00 852.43 634.66
September 0.00 0.00 901.13 649.28
October 0.00 0.00 1009.26 751.42
November 0.00 0.00 1147.31 826.65
December 0.00 0.00 1275.49 949.64
         
Annual Sum or Average 0.00 0.00 1116.73 9789.47