Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:40
Tabular Output Report in Format: HTML
Building: MF+CZ4AWH+USA_MD_Baltimore-Washington.Intl.AP.724060+oilfurnace+unheatedbsmt+IECC_2012
Environment: ANNUAL ** Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060
Simulation Timestamp: 2019-02-14 08:40:37
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 947920.66 | 24.30 | 43.86 |
Net Site Energy | 947920.66 | 24.30 | 43.86 |
Total Source Energy | 1941332.42 | 49.77 | 89.84 |
Net Source Energy | 1941332.42 | 49.77 | 89.84 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 231015.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 67312.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 18532.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 278217.36 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 438687.67 | 509232.99 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 231015.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 67312.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 18532.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 278217.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 3.97 | 23.56 | 0.00 | 0.00 | 0.00 | 17.48 |
Other | 13.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 20.30 | 23.56 | 0.00 | 0.00 | 0.00 | 17.48 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.20 | 13.06 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.25 | 13.06 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 438687.673 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 438687.673 | 100.00 |
Total On-Site and Utility Electric Sources | 438687.673 | 100.00 |
Total Electricity End Uses | 438687.673 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1133.75 |
Time Setpoint Not Met During Occupied Cooling | 13.25 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1399.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:40 |
RunPeriod | ANNUAL |
Weather File | Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Latitude [deg] | 39.17 |
Longitude [deg] | -76.7 |
Elevation [ft] | 147.65 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
UNHEATEDBSMT | 7794.39 | No | Yes | 58419.71 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6659 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 141767.99 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 09-JUL-18:15 | 26-DEC-06:30 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 194.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 45.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 113.85 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 121.09 | 308.66 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 194.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 45.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 12.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 113.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 250420.94 | 0.00 | 0.00 | 0.00 |
Cooling | 213177.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 58691.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 301587.62 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1389323.86 | 552008.56 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 11.59 | 0.00 | 0.00 | 0.00 |
Cooling | 9.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.96 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 64.29 | 25.54 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 11.59 | 0.00 | 0.00 | 0.00 |
Cooling | 9.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 43.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2.72 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.96 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 64.29 | 25.54 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 12.92 | 0.00 | 12.92 | Wetbulb [F] | 767.75 | 290.00 |
BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 93.92 | 18.72 | 75.02 | Wetbulb [F] | 905.56 | 280.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 839.40 | 839.40 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 455.77 | 455.77 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 839.40 | 839.40 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.089 | 0.094 | 455.77 | 455.77 | 270.00 | 90.00 | W |
BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.049 | 0.051 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 367031.92 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 23189.54 | 17806.90 | 5382.64 | 0.77 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7607.68 | 5224.04 | 2383.64 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9457.81 | 6757.56 | 2700.25 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 12865.18 | 9324.70 | 3540.48 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7352.16 | 5038.85 | 2313.31 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9414.62 | 6723.97 | 2690.65 | 0.71 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13095.60 | 9592.98 | 3502.63 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7756.12 | 5394.46 | 2361.66 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9407.10 | 6767.26 | 2639.84 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 12780.26 | 9335.29 | 3444.98 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7560.81 | 5237.99 | 2322.82 | 0.69 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9382.98 | 6748.77 | 2634.21 | 0.72 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14192.11 | 10414.76 | 3777.35 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8944.83 | 6291.29 | 2653.54 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10668.20 | 7482.74 | 3185.46 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 14144.86 | 10376.00 | 3768.85 | 0.73 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8956.70 | 6299.79 | 2656.90 | 0.70 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10302.47 | 7287.40 | 3015.07 | 0.71 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.8 | 3.32 | 11.32 | 11.99 | 11.58 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.48 | 11.86 | 12.59 | 12.49 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.42 | 11.67 | 12.38 | 12.16 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.0 | 3.40 | 11.60 | 12.30 | 12.05 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.48 | 11.87 | 12.60 | 12.50 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.42 | 11.67 | 12.38 | 12.17 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.0 | 3.38 | 11.55 | 12.25 | 11.96 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.46 | 11.80 | 12.52 | 12.38 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.41 | 11.64 | 12.34 | 12.11 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.0 | 3.39 | 11.56 | 12.26 | 11.98 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.46 | 11.82 | 12.54 | 12.41 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.41 | 11.64 | 12.34 | 12.11 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.1 | 3.38 | 11.54 | 12.24 | 11.95 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.7 | 3.44 | 11.75 | 12.46 | 12.29 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.45 | 11.76 | 12.48 | 12.31 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.1 | 3.38 | 11.54 | 12.24 | 11.95 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.7 | 3.44 | 11.75 | 12.46 | 12.29 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.8 | 3.43 | 11.72 | 12.43 | 12.24 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 45786.56 | 48695.86 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 13552.23 | 13232.65 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 17597.97 | 17715.75 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 23635.59 | 24377.14 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 13139.69 | 12773.43 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 17515.69 | 17624.77 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 24563.23 | 25399.21 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 14136.73 | 13881.77 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 17770.76 | 17905.76 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 23893.99 | 24660.34 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 13739.45 | 13440.18 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 17726.29 | 17856.59 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 26483.39 | 27512.80 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 16250.36 | 16225.41 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 18716.42 | 18950.57 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 26382.30 | 27401.50 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 16268.99 | 16246.03 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 18509.20 | 18721.67 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 797.06 | 300.65 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 198.46 | 74.86 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 273.56 | 103.18 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 385.64 | 145.46 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 190.80 | 71.97 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 272.03 | 102.61 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 402.88 | 151.96 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 209.32 | 78.95 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 276.78 | 104.40 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 390.46 | 147.28 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 201.94 | 76.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 275.95 | 104.09 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 438.51 | 165.40 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 248.55 | 93.75 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 294.32 | 111.02 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 436.63 | 164.69 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 248.89 | 93.88 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 290.48 | 109.57 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 36.907886 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 18625.07 | 18625.07 | 15.51 | 797.060 | 797.060 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00856 | 90.36 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4637.52 | 4637.52 | 3.86 | 198.457 | 198.457 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00989 | 87.32 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6392.60 | 6392.60 | 5.32 | 273.560 | 273.560 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00937 | 86.01 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9011.49 | 9011.49 | 7.51 | 385.644 | 385.644 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00907 | 90.36 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4458.57 | 4458.57 | 3.71 | 190.798 | 190.798 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00998 | 86.62 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6356.90 | 6356.90 | 5.29 | 272.033 | 272.033 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00938 | 86.01 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9414.46 | 9414.46 | 7.84 | 402.883 | 402.883 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00892 | 89.90 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4891.35 | 4891.35 | 4.07 | 209.316 | 209.316 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00965 | 86.62 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6467.89 | 6467.89 | 5.39 | 276.780 | 276.780 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00921 | 86.01 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9124.12 | 9124.12 | 7.60 | 390.458 | 390.458 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00895 | 89.90 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4718.99 | 4718.99 | 3.93 | 201.941 | 201.941 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00971 | 86.62 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6448.60 | 6448.60 | 5.37 | 275.954 | 275.954 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 09:45:00 | 74.98 | 74.98 | 0.00921 | 86.01 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 6787.69 | 6787.69 | 5.65 | 290.476 | 290.476 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00939 | 89.43 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6876.87 | 6876.87 | 5.73 | 294.323 | 294.323 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00924 | 93.36 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10246.82 | 10246.82 | 8.54 | 438.510 | 438.510 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00897 | 89.90 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5816.07 | 5816.07 | 4.84 | 248.892 | 248.892 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00961 | 86.62 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5808.00 | 5808.00 | 4.84 | 248.546 | 248.546 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00960 | 86.62 | 0.01446 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10202.97 | 10202.97 | 8.50 | 436.634 | 436.634 | BALTIMORE BLT WASHNGTN INTL ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00898 | 89.90 | 0.01446 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.000 | 44.995 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 32.00 | 32.00 | 0.00000 | 12.92 | 0.00152 | 44.995 | 0.00 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7340.52 | 7340.52 | 6.11 | 134.288 | 134.288 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00588 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9509.43 | 9509.43 | 7.92 | 173.964 | 173.964 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00615 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9522.17 | 9522.17 | 7.93 | 174.196 | 174.196 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00615 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7391.08 | 7391.08 | 6.16 | 135.213 | 135.213 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00589 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9511.10 | 9511.10 | 7.92 | 173.994 | 173.994 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00615 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8309.83 | 8309.83 | 6.92 | 152.026 | 152.026 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00631 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6273.55 | 6273.55 | 5.23 | 114.775 | 114.775 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00605 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8424.63 | 8424.63 | 7.02 | 154.126 | 154.126 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00633 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8441.81 | 8441.81 | 7.03 | 154.441 | 154.441 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00633 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6287.63 | 6287.63 | 5.24 | 115.033 | 115.033 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00605 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8425.89 | 8425.89 | 7.02 | 154.149 | 154.149 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.99 | 0.00633 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 10625.84 | 10625.84 | 8.85 | 194.387 | 194.387 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00629 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 10621.48 | 10621.48 | 8.85 | 194.307 | 194.307 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00629 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10617.69 | 10617.69 | 8.84 | 194.238 | 194.238 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00629 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 8486.09 | 8486.09 | 7.07 | 155.245 | 155.245 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00607 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 8477.89 | 8477.89 | 7.06 | 155.095 | 155.095 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00607 | 12.92 | 0.00152 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10643.64 | 10643.64 | 8.87 | 194.712 | 194.712 | BALTIMORE BLT WASHNGTN INTL ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00629 | 12.92 | 0.00152 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 | 797.06 | 44.99 | 44.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 | 198.46 | 134.29 | 134.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 | 273.56 | 173.96 | 173.96 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 | 385.64 | 174.20 | 174.20 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 | 190.80 | 135.21 | 135.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 | 272.03 | 173.99 | 173.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 | 402.88 | 152.03 | 152.03 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 | 209.32 | 114.77 | 114.77 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 | 276.78 | 154.13 | 154.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 | 390.46 | 154.44 | 154.44 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 | 201.94 | 115.03 | 115.03 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 | 275.95 | 154.15 | 154.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.51 | 438.51 | 194.24 | 194.24 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.55 | 248.55 | 155.10 | 155.10 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 294.32 | 294.32 | 194.31 | 194.31 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 436.63 | 436.63 | 194.71 | 194.71 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 248.89 | 248.89 | 155.25 | 155.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.48 | 290.48 | 194.39 | 194.39 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1322.25 | 5341.00 | 26.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2545.25 | 5698.00 | 790.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2789.50 | 5567.75 | 685.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2960.75 | 6054.25 | 1045.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2284.75 | 6070.00 | 659.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2759.75 | 5869.25 | 757.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2882.50 | 5210.25 | 479.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2499.00 | 5110.25 | 336.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2858.00 | 5119.50 | 431.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 3000.00 | 5570.50 | 721.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2370.25 | 5470.75 | 325.75 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2798.75 | 5415.25 | 472.75 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3101.25 | 5468.50 | 711.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 2996.75 | 5265.50 | 559.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3079.75 | 5439.25 | 693.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2680.75 | 5583.50 | 511.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2663.00 | 5357.25 | 428.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3206.00 | 5645.00 | 883.50 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3659.25 | 6549.50 | 1399.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 2.25 | 0.00 | 2.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 170.00 | 0.00 | 170.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 145.50 | 8.50 | 145.50 | 8.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 368.25 | 2.50 | 368.25 | 2.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 47.50 | 0.00 | 47.50 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 41.50 | 7.75 | 41.50 | 7.75 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 28.00 | 1.25 | 28.00 | 1.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5.75 | 0.00 | 5.75 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 157.50 | 7.75 | 157.50 | 7.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 400.50 | 1.50 | 400.50 | 1.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 29.25 | 0.00 | 29.25 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 61.75 | 6.50 | 61.75 | 6.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 49.25 | 2.50 | 49.25 | 2.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.00 | 0.50 | 91.00 | 0.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 86.25 | 1.75 | 86.25 | 1.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 25.25 | 0.00 | 25.25 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 20.00 | 0.00 | 20.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 277.25 | 2.00 | 277.25 | 2.00 |
UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1133.75 | 13.25 | 1133.75 | 13.25 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.118 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.102 | 0.000 | 0.274 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.116 | 0.000 | 0.274 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.115 | 0.000 | 0.274 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.102 | 0.000 | 0.274 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.116 | 0.000 | 0.274 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.051 | 0.000 | 0.274 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.037 | 0.000 | 0.274 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.051 | 0.000 | 0.274 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.051 | 0.000 | 0.274 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.037 | 0.000 | 0.274 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.051 | 0.000 | 0.274 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.274 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.274 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.274 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.102 | 0.000 | 0.274 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.102 | 0.000 | 0.274 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.116 | 0.000 | 0.274 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1867 |
Defaulted Fields | 446 |
Fields with Defaults | 4744 |
Autosized Fields | 328 |
Autosizable Fields | 438 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Fans:Electricity | 5427.61 | 100.36 | 20-APR-01:30 | 2181.58 | 09-JUL-17:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
ElectricityPurchased:Plant | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
Cogeneration:ElectricityPurchased | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
ElectricityNet:Plant | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
Cogeneration:ElectricityNet | 128480.98 | 7328.94 | 10-MAY-03:15 | 35464.92 | 09-JUL-18:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 25141.72 | 503.53 | 20-APR-01:30 | 15802.92 | 09-JUL-16:15 |
General:Fans:Electricity | 5427.61 | 100.36 | 20-APR-01:30 | 2181.58 | 09-JUL-17:15 |
Cooling:Electricity | 19714.11 | 0.00 | 05-JAN-01:45 | 13630.98 | 09-JUL-16:15 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 5092.33 | 0.00 | 01-FEB-14:15 | 308440.87 | 26-DEC-06:30 |
Gas:Plant | 5092.33 | 0.00 | 01-FEB-14:15 | 308440.87 | 26-DEC-06:30 |
WaterSystems:Gas | 2782.17 | 0.00 | 01-JAN-00:15 | 115498.03 | 11-FEB-08:30 |
Water Heater:WaterSystems:Gas | 2782.17 | 0.00 | 01-JAN-00:15 | 115498.03 | 11-FEB-08:30 |
Heating:Gas | 2310.16 | 0.00 | 01-FEB-14:00 | 196093.93 | 26-DEC-05:45 |
Boiler:Heating:Gas | 2310.16 | 0.00 | 01-FEB-14:00 | 196093.93 | 26-DEC-05:45 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
Water:Plant | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
WaterSystems:Water | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
MainsWater:Plant | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 14-FEB-02:45 | 0.18 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 328976.00 | 1146.94 | 09-AUG-02:15 | 192746.20 | 19-JAN-07:15 |
PlantLoopHeatingDemand:Plant | 144363.36 | 1146.94 | 09-AUG-02:15 | 39475.59 | 05-FEB-08:30 |
WaterSystems:PlantLoopHeatingDemand | 144363.36 | 1146.94 | 09-AUG-02:15 | 39475.59 | 05-FEB-08:30 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1234480.32 | 15954.30 | 05-JUN-02:15 | 507030.50 | 19-JAN-07:15 |
EnergyTransfer:Building | 417346.87 | 7003.62 | 04-MAY-00:30 | 161091.79 | 26-DEC-05:45 |
EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 190714.16 | 0.00 | 01-FEB-14:15 | 161091.79 | 26-DEC-05:45 |
Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 226632.72 | 0.00 | 05-JAN-01:45 | 135551.30 | 17-AUG-17:15 |
Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 71006.73 | 0.00 | 05-JAN-01:45 | 18825.28 | 17-AUG-16:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3.05 | 0.00 | 01-JAN-00:15 | 711.12 | 26-DEC-05:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 71003.68 | 0.00 | 05-JAN-01:45 | 18825.28 | 17-AUG-16:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14255.89 | 0.00 | 01-JAN-12:15 | 12264.85 | 21-DEC-10:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7436.00 | 0.00 | 01-JAN-12:15 | 12264.85 | 21-DEC-10:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6819.89 | 0.00 | 01-JAN-00:15 | 4913.77 | 17-AUG-17:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 20974.77 | 0.00 | 01-JAN-12:45 | 10453.81 | 19-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11439.87 | 0.00 | 01-JAN-12:45 | 10453.81 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9534.90 | 0.00 | 01-JAN-00:15 | 6922.81 | 08-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22247.30 | 0.00 | 01-FEB-13:30 | 10121.98 | 19-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13795.86 | 0.00 | 01-FEB-13:30 | 10121.98 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8451.44 | 0.00 | 01-JAN-00:15 | 9399.05 | 08-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 16562.89 | 0.00 | 26-JAN-20:45 | 7854.19 | 25-DEC-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 10879.29 | 0.00 | 26-JAN-20:45 | 7854.19 | 25-DEC-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5683.60 | 0.00 | 01-JAN-00:15 | 4582.63 | 09-JUL-19:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22040.73 | 0.00 | 01-FEB-13:30 | 10152.89 | 19-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13736.97 | 0.00 | 01-FEB-13:30 | 10152.89 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8303.76 | 0.00 | 01-JAN-00:15 | 6952.14 | 11-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 19711.80 | 0.00 | 01-JAN-12:45 | 9822.82 | 17-AUG-17:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8527.32 | 0.00 | 01-JAN-12:45 | 8807.21 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11184.48 | 0.00 | 01-JAN-00:15 | 9822.82 | 17-AUG-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 14435.21 | 0.00 | 01-JAN-12:00 | 7247.69 | 26-DEC-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6272.35 | 0.00 | 01-JAN-12:00 | 7247.69 | 26-DEC-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8162.85 | 0.00 | 01-JAN-00:15 | 5155.80 | 17-AUG-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 20021.61 | 0.00 | 01-JAN-12:15 | 8902.12 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 9104.11 | 0.00 | 01-JAN-12:15 | 8902.12 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10917.50 | 0.00 | 01-JAN-00:15 | 7007.20 | 08-JUL-09:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20966.50 | 0.00 | 01-FEB-13:00 | 9533.36 | 08-JUL-18:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11301.17 | 0.00 | 01-FEB-13:00 | 8893.51 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9665.34 | 0.00 | 01-JAN-00:15 | 9533.36 | 08-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15335.84 | 0.00 | 26-JAN-18:15 | 6618.59 | 19-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8421.12 | 0.00 | 26-JAN-18:15 | 6618.59 | 19-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6914.72 | 0.00 | 01-JAN-00:15 | 4897.13 | 09-JUL-19:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 20879.23 | 0.00 | 01-FEB-13:00 | 8925.21 | 19-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11277.84 | 0.00 | 01-FEB-13:00 | 8925.21 | 19-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9601.38 | 0.00 | 01-JAN-00:15 | 7032.27 | 11-JUL-09:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 25608.79 | 0.00 | 01-FEB-14:00 | 11244.60 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 15106.58 | 0.00 | 01-FEB-14:00 | 11244.60 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 10502.20 | 0.00 | 01-JAN-00:15 | 7503.97 | 08-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 24217.57 | 0.00 | 14-JAN-12:00 | 11219.01 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 12973.59 | 0.00 | 14-JAN-12:00 | 11219.01 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11243.98 | 0.00 | 01-JAN-00:15 | 7461.97 | 08-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 24546.88 | 0.00 | 01-JAN-14:45 | 11188.23 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 13097.44 | 0.00 | 01-JAN-14:45 | 11188.23 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11449.44 | 0.00 | 01-JAN-00:15 | 10642.96 | 17-AUG-17:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 20075.56 | 0.00 | 01-FEB-14:15 | 8921.48 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 12139.09 | 0.00 | 01-FEB-14:15 | 8921.48 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7936.47 | 0.00 | 01-JAN-00:15 | 5924.42 | 09-JUL-20:00 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18514.24 | 0.00 | 01-JAN-14:30 | 8951.80 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9890.88 | 0.00 | 01-JAN-14:30 | 8951.80 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8623.36 | 0.00 | 01-JAN-00:15 | 6046.77 | 17-AUG-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25945.32 | 0.00 | 01-FEB-14:00 | 11241.86 | 26-DEC-07:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 15311.61 | 0.00 | 01-FEB-14:00 | 11241.86 | 26-DEC-07:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 10633.70 | 0.00 | 01-JAN-00:15 | 10515.54 | 08-JUL-17:45 |
EnergyTransfer:Plant | 329175.86 | 1146.94 | 09-AUG-02:15 | 192331.78 | 19-JAN-07:15 |
WaterSystems:EnergyTransfer | 144363.36 | 1146.94 | 09-AUG-02:15 | 39475.59 | 05-FEB-08:30 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 144363.36 | 1146.94 | 09-AUG-02:15 | 39475.59 | 05-FEB-08:30 |
EnergyTransfer:HVAC | 487957.58 | 7202.53 | 19-APR-00:45 | 191112.49 | 09-JUL-18:15 |
HeatingCoils:EnergyTransfer | 184612.64 | 0.00 | 01-FEB-14:00 | 157144.34 | 26-DEC-05:45 |
PlantLoopHeatingDemand:HVAC | 184612.64 | 0.00 | 01-FEB-14:00 | 157144.34 | 26-DEC-05:45 |
HeatingCoils:PlantLoopHeatingDemand | 184612.64 | 0.00 | 01-FEB-14:00 | 157144.34 | 26-DEC-05:45 |
CoolingCoils:EnergyTransfer | 303344.94 | 0.00 | 05-JAN-01:45 | 191112.49 | 09-JUL-18:15 |
Boilers:EnergyTransfer | 184812.50 | 0.00 | 01-FEB-14:00 | 156875.15 | 26-DEC-05:45 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 3.048 | -5913.02 | 0.000 | 0.000 | 2876.561 | 2456.001 | 10405.511 | 8629.106 | 0.000 | 624.279 | 65616.010 | 0.000 | -5856.67 | 0.000 | -13750.23 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 7435.963 | -567.94 | 0.000 | 0.000 | 3041.217 | 2456.001 | 10405.511 | 4080.738 | 0.000 | 603.772 | 0.000 | 0.000 | -2215.97 | 0.000 | -12060.02 | -6927.36 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 11439.808 | -794.04 | 0.000 | 0.000 | 3036.000 | 2456.001 | 10405.511 | 8819.629 | 0.000 | 623.856 | 0.000 | 0.000 | -5365.32 | 0.000 | -12666.70 | -9213.92 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 13795.789 | -703.81 | 0.000 | 0.000 | 3047.485 | 2456.001 | 10405.511 | 6123.572 | 0.000 | 624.513 | 0.000 | 0.000 | -5817.41 | 0.000 | -12495.88 | -9688.25 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 10879.239 | -473.32 | 0.000 | 0.000 | 3040.187 | 2456.001 | 10405.511 | 1256.451 | 0.000 | 603.994 | 0.000 | 0.000 | -2469.19 | 0.000 | -12068.96 | -8419.64 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 13736.902 | -691.52 | 0.000 | 0.000 | 3044.956 | 2456.001 | 10405.511 | 6094.823 | 0.000 | 623.846 | 0.000 | 0.000 | -5604.73 | 0.000 | -12573.68 | -9879.89 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 8527.269 | -931.41 | 0.000 | 0.000 | 3017.924 | 2456.001 | 10405.511 | 8694.344 | 0.000 | 524.936 | 0.000 | 0.000 | -5684.47 | 0.000 | -10404.74 | -6352.41 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6272.314 | -679.78 | 0.000 | 0.000 | 3009.848 | 2456.001 | 10405.511 | 4054.184 | 0.000 | 504.498 | 0.000 | 0.000 | -2275.33 | 0.000 | -9927.65 | -6336.55 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 9104.063 | -909.18 | 0.000 | 0.000 | 3023.934 | 2456.001 | 10405.511 | 8768.974 | 0.000 | 524.621 | 0.000 | 0.000 | -5481.67 | 0.000 | -10390.17 | -7493.79 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11301.111 | -804.90 | 0.000 | 0.000 | 3036.459 | 2456.001 | 10405.511 | 6086.228 | 0.000 | 525.098 | 0.000 | 0.000 | -5940.59 | 0.000 | -10246.20 | -7958.37 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8421.079 | -575.84 | 0.000 | 0.000 | 3027.387 | 2456.001 | 10405.511 | 1243.814 | 0.000 | 504.635 | 0.000 | 0.000 | -2521.51 | 0.000 | -9813.70 | -6808.49 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 11277.792 | -799.58 | 0.000 | 0.000 | 3034.434 | 2456.001 | 10405.511 | 6052.964 | 0.000 | 524.633 | 0.000 | 0.000 | -5720.01 | 0.000 | -10307.57 | -8122.37 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 15106.515 | -874.60 | 0.000 | 0.000 | 3038.721 | 2456.001 | 10405.511 | 6057.188 | 0.000 | 618.294 | 0.000 | 0.000 | -5713.39 | 0.000 | -12634.23 | -8832.40 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 12973.526 | -936.37 | 0.000 | 0.000 | 3031.423 | 2456.001 | 10405.511 | 8793.829 | 0.000 | 618.547 | 0.000 | 0.000 | -5458.65 | 0.000 | -12704.56 | -8871.65 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13097.372 | -953.47 | 0.000 | 0.000 | 3030.158 | 2456.001 | 10405.511 | 8735.446 | 0.000 | 618.549 | 0.000 | 0.000 | -5624.16 | 0.000 | -12686.57 | -8582.98 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 12139.037 | -660.93 | 0.000 | 0.000 | 3033.097 | 2456.001 | 10405.511 | 1243.088 | 0.000 | 598.507 | 0.000 | 0.000 | -2514.98 | 0.000 | -12139.32 | -7284.47 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 9890.832 | -718.13 | 0.000 | 0.000 | 3022.434 | 2456.001 | 10405.511 | 4063.395 | 0.000 | 598.198 | 0.000 | 0.000 | -2259.89 | 0.000 | -12224.21 | -7328.94 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 15311.544 | -885.54 | 0.000 | 0.000 | 3039.567 | 2456.001 | 10405.511 | 6075.960 | 0.000 | 618.847 | 0.000 | 0.000 | -5932.35 | 0.000 | -12587.44 | -8754.02 |
UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4406.433 | 41665.117 | 0.000 | 0.000 | 0.000 | -46071.55 | -0.63 |
Total Facility | 0.000 | 0.000 | 190713.201 | -18873.37 | 0.000 | 0.000 | 54431.794 | 44208.020 | 187299.191 | 104873.733 | 0.000 | 14890.057 | 107281.128 | 0.000 | -82456.31 | 0.000 | -257753.42 | -136856.13 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17-AUG-16:30 | 0.00 | 0.00 | 0.00 | -1.6 | 0.00 | 0.00 | 140.45 | 384.73 | 1343.91 | 7007.93 | 0.00 | 1209.30 | 8763.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 17-AUG-17:05 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 263.34 | 535.87 | 1656.36 | 551.46 | 0.00 | 1132.33 | 775.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 08-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 192.33 | 151.14 | 1168.32 | 6683.90 | 0.00 | 647.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1904.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 08-JUL-17:19 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 260.26 | 535.87 | 1676.47 | 7343.24 | 0.00 | 983.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1389.5 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 09-JUL-19:49 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.64 | 799.44 | 1674.43 | 140.76 | 0.00 | 769.36 | 779.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11-JUL-08:47 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.54 | 151.14 | 1145.90 | 6469.01 | 0.00 | 467.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1474.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17-AUG-17:05 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.34 | 535.87 | 1656.36 | 5891.50 | 0.00 | 985.40 | 491.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17-AUG-18:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.04 | 721.37 | 1713.78 | 300.01 | 0.00 | 765.85 | 1228.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 08-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 192.99 | 151.14 | 1168.32 | 6677.29 | 0.00 | 550.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1721.3 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 08-JUL-17:34 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 260.76 | 535.87 | 1676.47 | 6836.82 | 0.00 | 796.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -566.5 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 09-JUL-19:49 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.77 | 799.44 | 1674.43 | 142.68 | 0.00 | 654.57 | 1208.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11-JUL-08:47 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.54 | 151.14 | 1145.90 | 6456.30 | 0.00 | 405.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1320.0 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 08-JUL-08:49 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.55 | 151.14 | 1168.32 | 6571.59 | 0.00 | 667.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1238.5 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 08-JUL-08:49 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.55 | 151.14 | 1168.32 | 6677.27 | 0.00 | 667.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1395.6 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 17-AUG-17:05 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.34 | 535.87 | 1656.36 | 5873.69 | 0.00 | 1167.50 | 1147.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 09-JUL-20:04 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.34 | 799.44 | 1638.87 | 123.11 | 0.00 | 728.41 | 2218.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 17-AUG-18:08 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.04 | 721.37 | 1713.78 | 294.57 | 0.00 | 901.72 | 1989.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 08-JUL-17:34 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 260.13 | 535.87 | 1676.47 | 6807.97 | 0.00 | 951.41 | 295.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-AUG-17:15 | 0.00 | 0.00 | 0.00 | -11.3 | 0.00 | 0.00 | 4740.02 | 9645.69 | 29814.52 | 46945.02 | 0.00 | 19711.75 | 39643.66 | 0.00 | 0.00 | 0.00 | -14698.4 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 25-DEC-07:08 | 0.00 | 0.00 | 766.74 | 0.00 | 0.00 | 0.00 | 464.78 | 343.51 | 1204.86 | 0.00 | 0.00 | 0.00 | 6305.58 | 0.00 | -2935.2 | 0.00 | -6150.3 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 18-JAN-06:35 | 0.00 | 0.00 | 13003.92 | 0.00 | 0.00 | 0.00 | 703.16 | 384.73 | 1074.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -953.2 | 0.00 | -4132.1 | -10081.2 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 03-DEC-16:57 | 0.00 | 0.00 | 11202.12 | 0.00 | 0.00 | 0.00 | 160.50 | 384.73 | 1363.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1680.4 | 0.00 | -2838.9 | -8591.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24-FEB-14:36 | 0.00 | 0.00 | 17699.96 | 0.00 | 0.00 | 0.00 | 144.24 | 103.05 | 1085.09 | 2543.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2565.2 | -19010.2 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 03-DEC-15:30 | 0.00 | 0.00 | 11388.97 | 0.00 | 0.00 | 0.00 | 127.31 | 178.62 | 1161.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -462.6 | 0.00 | -2632.7 | -9760.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 19-JAN-04:48 | 0.00 | 0.00 | 10153.06 | 0.00 | 0.00 | 0.00 | 526.31 | 164.88 | 831.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2940.2 | 0.00 | -5773.8 | -2961.4 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17-APR-09:54 | 0.00 | 0.00 | 17501.17 | 0.00 | 0.00 | 0.00 | 137.74 | 103.05 | 1084.61 | 1001.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1641.9 | -18185.8 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26-DEC-04:49 | 0.00 | 0.00 | 7247.73 | 0.00 | 0.00 | 0.00 | 526.30 | 164.88 | 831.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1154.5 | 0.00 | -4222.4 | -3393.1 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 17-NOV-23:53 | 0.00 | 0.00 | 11946.85 | 0.00 | 0.00 | 0.00 | 554.60 | 137.40 | 1146.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1605.8 | 0.00 | -2122.3 | -10057.2 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 15-JAN-14:53 | 0.00 | 0.00 | 17875.46 | 0.00 | 0.00 | 0.00 | 143.10 | 103.05 | 1106.23 | 425.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2043.2 | -17610.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 16-FEB-17:38 | 0.00 | 0.00 | 11852.67 | 0.00 | 0.00 | 0.00 | 308.48 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -612.5 | 0.00 | -1880.9 | -11860.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 19-JAN-04:48 | 0.00 | 0.00 | 8925.34 | 0.00 | 0.00 | 0.00 | 526.30 | 164.88 | 831.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2971.5 | 0.00 | -4614.3 | -2861.9 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 26-DEC-07:00 | 0.00 | 0.00 | 11244.63 | 0.00 | 0.00 | 0.00 | 526.32 | 384.73 | 1074.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2928.6 | 0.00 | -5752.6 | -4549.1 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 24-NOV-19:53 | 0.00 | 0.00 | 11228.17 | 0.00 | 0.00 | 0.00 | 488.06 | 799.44 | 1651.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1696.9 | 0.00 | -2578.8 | -9891.2 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 17-APR-10:40 | 0.00 | 0.00 | 18113.19 | 0.00 | 0.00 | 0.00 | 142.85 | 103.05 | 1079.31 | 1607.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1685.5 | -19360.3 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 30-DEC-14:57 | 0.00 | 0.00 | 9167.03 | 0.00 | 0.00 | 0.00 | 127.31 | 103.05 | 1106.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -330.3 | 0.00 | -2135.6 | -8037.7 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 06-MAR-17:42 | 0.00 | 0.00 | 11255.36 | 0.00 | 0.00 | 0.00 | 303.22 | 535.87 | 1656.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -563.8 | 0.00 | -2624.3 | -10562.7 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 29-JAN-13:24 | 0.00 | 0.00 | 18954.80 | 0.00 | 0.00 | 0.00 | 140.82 | 103.05 | 1100.57 | 183.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1584.0 | -18898.9 |
UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 19-JAN-04:35 | 0.00 | 0.00 | 161714.64 | 0.00 | 0.00 | 0.00 | 9638.77 | 2967.90 | 14959.71 | 0.00 | 0.00 | 1166.73 | 0.00 | 0.00 | -42352.2 | 0.00 | -93948.5 | -54147.0 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 797.060 | 2.00 | 2.00 | 1.00 | 44.9950 | 797.060 | 0.056 | 1.000 | 44.9950 | 0.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 198.457 | 2.00 | 2.00 | 1.00 | 44.9950 | 198.457 | 0.227 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 273.560 | 2.00 | 2.00 | 1.00 | 44.9950 | 273.560 | 0.164 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 385.644 | 2.00 | 2.00 | 1.00 | 44.9950 | 385.644 | 0.117 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 190.798 | 2.00 | 2.00 | 1.00 | 44.9950 | 190.798 | 0.236 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 272.033 | 2.00 | 2.00 | 1.00 | 44.9950 | 272.033 | 0.165 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 402.883 | 2.00 | 2.00 | 1.00 | 44.9950 | 402.883 | 0.112 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 209.316 | 2.00 | 2.00 | 1.00 | 44.9950 | 209.316 | 0.215 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 276.780 | 2.00 | 2.00 | 1.00 | 44.9950 | 276.780 | 0.163 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 390.458 | 2.00 | 2.00 | 1.00 | 44.9950 | 390.458 | 0.115 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 201.941 | 2.00 | 2.00 | 1.00 | 44.9950 | 201.941 | 0.223 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 275.954 | 2.00 | 2.00 | 1.00 | 44.9950 | 275.954 | 0.163 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.510 | 2.00 | 2.00 | 1.00 | 44.9950 | 438.510 | 0.103 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.546 | 2.00 | 2.00 | 1.00 | 44.9950 | 248.546 | 0.181 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 294.323 | 2.00 | 2.00 | 1.00 | 44.9950 | 294.323 | 0.153 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 436.634 | 2.00 | 2.00 | 1.00 | 44.9950 | 436.634 | 0.103 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 248.892 | 2.00 | 2.00 | 1.00 | 44.9950 | 248.892 | 0.181 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.476 | 2.00 | 2.00 | 1.00 | 44.9950 | 290.476 | 0.155 | 1.000 | 44.9950 | 0.15 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 2.00 | 2.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 134.288 | 2.00 | 2.00 | 1.00 | 44.9950 | 134.288 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 173.964 | 2.00 | 2.00 | 1.00 | 44.9950 | 173.964 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 174.196 | 2.00 | 2.00 | 1.00 | 44.9950 | 174.196 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 135.213 | 2.00 | 2.00 | 1.00 | 44.9950 | 135.213 | 1.000 | 1.000 | 44.9950 | 0.33 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 173.994 | 2.00 | 2.00 | 1.00 | 44.9950 | 173.994 | 1.000 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 152.026 | 2.00 | 2.00 | 1.00 | 44.9950 | 152.026 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 114.775 | 2.00 | 2.00 | 1.00 | 44.9950 | 114.775 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 154.126 | 2.00 | 2.00 | 1.00 | 44.9950 | 154.126 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 154.441 | 2.00 | 2.00 | 1.00 | 44.9950 | 154.441 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 115.033 | 2.00 | 2.00 | 1.00 | 44.9950 | 115.033 | 1.000 | 1.000 | 44.9950 | 0.39 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 154.149 | 2.00 | 2.00 | 1.00 | 44.9950 | 154.149 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 194.238 | 2.00 | 2.00 | 1.00 | 44.9950 | 194.238 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.095 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.095 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 194.307 | 2.00 | 2.00 | 1.00 | 44.9950 | 194.307 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 194.712 | 2.00 | 2.00 | 1.00 | 44.9950 | 194.712 | 1.000 | 1.000 | 44.9950 | 0.23 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.245 | 2.00 | 2.00 | 1.00 | 44.9950 | 155.245 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 194.387 | 2.00 | 2.00 | 1.00 | 44.9950 | 194.387 | 1.000 | 1.000 | 44.9950 | 0.23 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 797.060 | 797.0595 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 198.457 | 198.4568 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 273.560 | 273.5602 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 385.644 | 385.6437 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 190.798 | 190.7982 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 272.033 | 272.0327 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 402.883 | 402.8830 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 209.316 | 209.3164 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 276.780 | 276.7799 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 390.458 | 390.4585 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 201.941 | 201.9407 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 275.954 | 275.9542 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.476 | 290.4761 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 294.323 | 294.3229 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.510 | 438.5102 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 248.892 | 248.8917 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.546 | 248.5459 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 436.634 | 436.6336 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 | 797.060 | 797.06 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 | 198.457 | 198.46 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 | 273.560 | 273.56 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 | 385.644 | 385.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 | 190.798 | 190.80 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 | 272.033 | 272.03 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 | 402.883 | 402.88 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 | 209.316 | 209.32 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 | 276.780 | 276.78 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 | 390.458 | 390.46 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 | 201.941 | 201.94 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 | 275.954 | 275.95 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.51 | 438.510 | 438.51 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.55 | 248.546 | 248.55 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 294.32 | 294.323 | 294.32 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 436.63 | 436.634 | 436.63 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 248.89 | 248.892 | 248.89 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.48 | 290.476 | 290.48 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.995 | 44.995 | 44.995 | 44.9950 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 134.288 | 134.288 | 134.288 | 44.9950 | 0.335 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 173.964 | 173.964 | 173.964 | 44.9950 | 0.259 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 174.196 | 174.196 | 174.196 | 44.9950 | 0.258 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 135.213 | 135.213 | 135.213 | 44.9950 | 0.333 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 173.994 | 173.994 | 173.994 | 44.9950 | 0.259 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 152.026 | 152.026 | 152.026 | 44.9950 | 0.296 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 114.775 | 114.775 | 114.775 | 44.9950 | 0.392 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 154.126 | 154.126 | 154.126 | 44.9950 | 0.292 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 154.441 | 154.441 | 154.441 | 44.9950 | 0.291 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 115.033 | 115.033 | 115.033 | 44.9950 | 0.391 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 154.149 | 154.149 | 154.149 | 44.9950 | 0.292 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 194.387 | 194.387 | 194.387 | 44.9950 | 0.231 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 194.307 | 194.307 | 194.307 | 44.9950 | 0.232 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 194.238 | 194.238 | 194.238 | 44.9950 | 0.232 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.245 | 155.245 | 155.245 | 44.9950 | 0.290 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.095 | 155.095 | 155.095 | 44.9950 | 0.290 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 194.712 | 194.712 | 194.712 | 44.9950 | 0.231 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 44.99 | 44.995 | 44.99 | 44.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 134.29 | 134.288 | 134.29 | 134.29 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 173.96 | 173.964 | 173.96 | 173.96 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 174.20 | 174.196 | 174.20 | 174.20 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 135.21 | 135.213 | 135.21 | 135.21 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 173.99 | 173.994 | 173.99 | 173.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 152.03 | 152.026 | 152.03 | 152.03 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 114.77 | 114.775 | 114.77 | 114.77 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 154.13 | 154.126 | 154.13 | 154.13 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 154.44 | 154.441 | 154.44 | 154.44 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 115.03 | 115.033 | 115.03 | 115.03 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 154.15 | 154.149 | 154.15 | 154.15 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 194.24 | 194.238 | 194.24 | 194.24 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 155.10 | 155.095 | 155.10 | 155.10 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 194.31 | 194.307 | 194.31 | 194.31 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 194.71 | 194.712 | 194.71 | 194.71 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 155.25 | 155.245 | 155.25 | 155.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 194.39 | 194.387 | 194.39 | 194.39 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Baltimore Blt Washngtn IntL MD USA TMY3 WMO#=724060 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 1133.75 |
Number of hours cooling loads not met | 13.25 |
Number of hours not met | 1147.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 3805.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 614.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 2310.16 | 194671.75 | 0.00 | 0.00 |
Space Cooling | 19714.11 | 13467.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 5427.61 | 2181.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 2782.17 | 113769.12 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 15395.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 128480.98 | 5092.33 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 438687.67 |
Natural Gas | 0.00 | 509232.99 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 947920.66 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.00 |
Space Cooling | 0.51 |
Fans-Interior | 0.14 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 3.29 |
Natural Gas [kWh/ft2] | |
Space Heating | 1.73 |
Service Water Heating | 2.09 |
Miscellaneous | 0.00 |
Subtotal | 3.82 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.66 |
Space Heating | 24.37 |
Space Cooling | 7.10 |
Fans-Interior | 1.96 |
Service Water Heating | 29.35 |
Receptacle Equipment | 31.64 |
Miscellaneous | 0.92 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 290.48 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 294.32 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 438.51 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 248.89 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 248.55 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 436.63 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 438.51 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 248.55 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 294.32 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 436.63 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 248.89 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 290.48 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 | 1.93 | 0.767885 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 | 0.633973 | 0.686680 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 | 0.788151 | 0.714495 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 | 1.07 | 0.724801 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 | 0.612680 | 0.685356 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 | 0.784552 | 0.714205 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 | 1.09 | 0.732534 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 | 0.646343 | 0.695510 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 | 0.783925 | 0.719378 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 | 1.07 | 0.730446 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 | 0.630067 | 0.692781 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 | 0.781915 | 0.719257 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 438.51 | 1.18 | 0.733842 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 248.55 | 0.745402 | 0.703344 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 294.32 | 0.889016 | 0.701406 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 436.63 | 1.18 | 0.733553 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 248.89 | 0.746391 | 0.703361 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 290.48 | 0.858539 | 0.707345 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 | 797.06 | 797.06 | 1.93 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 | 198.46 | 198.46 | 0.633973 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 | 273.56 | 273.56 | 0.788151 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 | 385.64 | 385.64 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 | 190.80 | 190.80 | 0.612680 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 | 272.03 | 272.03 | 0.784552 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 | 402.88 | 402.88 | 1.09 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 | 209.32 | 209.32 | 0.646343 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 | 276.78 | 276.78 | 0.783925 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 | 390.46 | 390.46 | 1.07 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 | 201.94 | 201.94 | 0.630067 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 | 275.95 | 275.95 | 0.781915 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 438.51 | 438.51 | 438.51 | 1.18 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 248.55 | 248.55 | 248.55 | 0.745402 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 294.32 | 294.32 | 294.32 | 0.889016 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 436.63 | 436.63 | 436.63 | 1.18 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 248.89 | 248.89 | 248.89 | 0.746391 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 290.48 | 290.48 | 290.48 | 0.858539 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 45786.56 | 4.62 | 647.90 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 13552.23 | 1.37 | 180.86 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 17597.97 | 1.78 | 239.84 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 23635.59 | 2.39 | 327.59 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13139.69 | 1.33 | 174.83 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 17515.69 | 1.77 | 238.64 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 24563.23 | 2.48 | 341.05 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 14136.73 | 1.43 | 189.39 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 17770.76 | 1.79 | 242.33 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 23893.99 | 2.41 | 331.30 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 13739.45 | 1.39 | 183.58 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 17726.29 | 1.79 | 241.68 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 26483.39 | 2.67 | 368.91 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 16250.36 | 1.64 | 220.22 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 18716.42 | 1.89 | 256.09 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 26382.30 | 2.66 | 367.45 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 16268.99 | 1.64 | 220.50 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 18509.20 | 1.87 | 253.07 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 797.06 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 198.46 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 273.56 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 385.64 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 190.80 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 272.03 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 402.88 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 209.32 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 276.78 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 390.46 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 201.94 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 275.95 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 438.51 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 248.55 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 294.32 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 436.63 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 248.89 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 290.48 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 4.93 | 92.51 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 4.93 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 367031.92 | 36.91 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:40:37
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 679.880 | 35.798 | 3.511 | 0.014 | 35.812 |
February | 633.150 | 41.460 | 0.000 | 0.000 | 41.460 |
March | 744.000 | 68.849 | 0.000 | 0.000 | 68.849 |
April | 720.000 | 87.394 | 0.000 | 0.000 | 87.394 |
May | 744.000 | 113.501 | 0.000 | 0.000 | 113.501 |
June | 720.000 | 130.524 | 0.000 | 0.000 | 130.524 |
July | 744.000 | 147.274 | 0.000 | 0.000 | 147.274 |
August | 744.000 | 141.942 | 0.000 | 0.000 | 141.942 |
September | 720.000 | 122.407 | 0.000 | 0.000 | 122.407 |
October | 744.000 | 89.965 | 0.000 | 0.000 | 89.965 |
November | 720.000 | 70.055 | 0.000 | 0.000 | 70.055 |
December | 684.382 | 44.864 | 5.249 | 0.027 | 44.891 |
Annual Sum or Average | 8597.412 | 1094.031 | 8.760 | 0.041 | 1094.072 |
Minimum of Months | 633.150 | 35.798 | 0.000 | 0.000 | 35.812 |
Maximum of Months | 744.000 | 147.274 | 5.249 | 0.027 | 147.274 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 645.466 | 8.941 | 13.478 |
February | 10.958 | 0.119 | 551.817 | 6.486 | 9.514 |
March | 86.275 | 1.230 | 481.271 | 3.742 | 4.972 |
April | 190.421 | 2.385 | 237.851 | 0.852 | 3.237 |
May | 411.689 | 10.338 | 92.333 | 0.278 | 10.615 |
June | 645.136 | 19.369 | 3.250 | 0.003 | 19.372 |
July | 741.250 | 26.719 | 0.000 | 0.000 | 26.719 |
August | 715.578 | 24.450 | 0.000 | 0.000 | 24.450 |
September | 557.222 | 16.073 | 5.446 | 0.005 | 16.078 |
October | 244.492 | 4.843 | 237.202 | 1.169 | 6.012 |
November | 76.354 | 1.009 | 416.096 | 2.598 | 3.607 |
December | 28.792 | 0.334 | 572.356 | 7.365 | 11.768 |
Annual Sum or Average | 3708.168 | 106.867 | 3243.088 | 31.439 | 149.821 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 3.237 |
Maximum of Months | 741.250 | 26.719 | 645.466 | 8.941 | 26.719 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 704.067 | 25.453 | 27.297 |
February | 13.763 | 0.143 | 585.256 | 18.076 | 20.013 |
March | 90.455 | 1.752 | 446.131 | 9.805 | 15.711 |
April | 234.821 | 4.465 | 193.125 | 2.394 | 12.984 |
May | 437.014 | 16.265 | 78.125 | 0.903 | 20.242 |
June | 633.480 | 29.714 | 1.625 | 0.013 | 30.095 |
July | 731.000 | 38.344 | 0.000 | 0.000 | 38.344 |
August | 697.764 | 34.639 | 0.000 | 0.000 | 34.639 |
September | 555.408 | 22.226 | 3.875 | 0.037 | 23.768 |
October | 234.573 | 6.181 | 217.286 | 3.646 | 16.269 |
November | 57.390 | 1.096 | 404.075 | 7.900 | 15.328 |
December | 22.521 | 0.294 | 625.550 | 21.605 | 25.549 |
Annual Sum or Average | 3708.189 | 155.119 | 3259.114 | 89.832 | 280.240 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.984 |
Maximum of Months | 731.000 | 38.344 | 704.067 | 25.453 | 38.344 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 723.117 | 30.746 | 33.701 |
February | 6.500 | 0.040 | 607.459 | 22.390 | 27.324 |
March | 54.450 | 1.360 | 499.523 | 12.344 | 28.002 |
April | 146.200 | 3.523 | 274.753 | 3.158 | 14.873 |
May | 389.002 | 16.537 | 115.585 | 1.120 | 20.082 |
June | 616.101 | 29.484 | 7.400 | 0.036 | 29.784 |
July | 731.758 | 39.822 | 0.000 | 0.000 | 39.822 |
August | 691.231 | 34.143 | 0.000 | 0.000 | 34.143 |
September | 500.999 | 19.437 | 25.112 | 0.122 | 20.688 |
October | 133.589 | 3.147 | 318.791 | 5.262 | 20.916 |
November | 5.625 | 0.023 | 495.069 | 10.690 | 25.773 |
December | 4.750 | 0.019 | 667.856 | 25.770 | 30.903 |
Annual Sum or Average | 3280.206 | 147.537 | 3734.664 | 111.639 | 326.010 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 14.873 |
Maximum of Months | 731.758 | 39.822 | 723.117 | 30.746 | 39.822 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 741.896 | 13.458 | 13.499 |
February | 0.500 | 0.001 | 640.641 | 9.820 | 10.040 |
March | 41.833 | 0.653 | 595.499 | 5.540 | 8.377 |
April | 98.500 | 0.905 | 286.265 | 1.290 | 3.791 |
May | 393.513 | 9.275 | 100.903 | 0.377 | 9.686 |
June | 645.904 | 18.678 | 3.250 | 0.004 | 18.682 |
July | 741.250 | 25.856 | 0.000 | 0.000 | 25.856 |
August | 713.552 | 22.447 | 0.000 | 0.000 | 22.447 |
September | 519.507 | 12.392 | 12.231 | 0.016 | 12.414 |
October | 109.775 | 1.457 | 371.205 | 2.173 | 5.742 |
November | 1.250 | 0.002 | 585.649 | 4.581 | 6.742 |
December | 4.750 | 0.020 | 696.646 | 11.245 | 11.653 |
Annual Sum or Average | 3270.335 | 91.684 | 4034.185 | 48.503 | 148.928 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 3.791 |
Maximum of Months | 741.250 | 25.856 | 741.896 | 13.458 | 25.856 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 742.464 | 30.396 | 30.554 |
February | 0.000 | 0.000 | 638.579 | 21.835 | 21.958 |
March | 41.092 | 0.859 | 590.660 | 12.405 | 14.783 |
April | 169.645 | 2.428 | 238.697 | 2.877 | 10.154 |
May | 431.248 | 15.204 | 84.350 | 0.983 | 18.838 |
June | 635.540 | 29.066 | 1.625 | 0.012 | 29.457 |
July | 731.250 | 37.568 | 0.000 | 0.000 | 37.568 |
August | 697.202 | 32.718 | 0.000 | 0.000 | 32.718 |
September | 545.053 | 18.502 | 6.125 | 0.056 | 20.070 |
October | 122.192 | 2.235 | 354.279 | 5.226 | 11.461 |
November | 0.000 | 0.000 | 604.196 | 11.264 | 14.043 |
December | 2.750 | 0.007 | 702.146 | 25.888 | 27.042 |
Annual Sum or Average | 3375.972 | 138.587 | 3963.121 | 110.943 | 268.645 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 10.154 |
Maximum of Months | 731.250 | 37.568 | 742.464 | 30.396 | 37.568 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.500 | 0.037 | 688.242 | 21.199 | 21.236 |
February | 21.500 | 0.365 | 563.375 | 14.950 | 15.496 |
March | 126.892 | 3.539 | 421.892 | 7.901 | 13.105 |
April | 245.369 | 7.253 | 163.854 | 1.512 | 12.697 |
May | 455.959 | 20.559 | 67.796 | 0.498 | 22.471 |
June | 660.208 | 34.128 | 1.550 | 0.004 | 34.220 |
July | 743.250 | 44.930 | 0.000 | 0.000 | 44.930 |
August | 722.436 | 40.598 | 0.000 | 0.000 | 40.598 |
September | 573.122 | 26.846 | 4.250 | 0.014 | 26.970 |
October | 261.549 | 8.948 | 220.100 | 2.648 | 12.842 |
November | 100.917 | 2.167 | 393.792 | 5.975 | 8.261 |
December | 34.142 | 0.577 | 612.962 | 17.727 | 18.304 |
Annual Sum or Average | 3947.843 | 189.949 | 3137.812 | 72.428 | 271.128 |
Minimum of Months | 2.500 | 0.037 | 0.000 | 0.000 | 8.261 |
Maximum of Months | 743.250 | 44.930 | 688.242 | 21.199 | 44.930 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.250 | 0.007 | 675.004 | 8.497 | 8.979 |
February | 17.208 | 0.180 | 552.354 | 5.956 | 6.991 |
March | 106.967 | 1.681 | 405.133 | 2.974 | 5.552 |
April | 238.929 | 3.483 | 126.938 | 0.534 | 4.886 |
May | 486.729 | 12.821 | 57.746 | 0.168 | 13.171 |
June | 686.005 | 22.944 | 0.000 | 0.000 | 22.944 |
July | 744.000 | 30.475 | 0.000 | 0.000 | 30.475 |
August | 740.917 | 28.341 | 0.000 | 0.000 | 28.341 |
September | 611.491 | 19.323 | 0.000 | 0.000 | 19.323 |
October | 291.244 | 6.198 | 177.583 | 0.808 | 7.337 |
November | 105.267 | 1.409 | 347.271 | 2.033 | 3.911 |
December | 37.771 | 0.472 | 593.633 | 7.083 | 8.067 |
Annual Sum or Average | 4068.778 | 127.335 | 2935.663 | 28.053 | 159.978 |
Minimum of Months | 2.250 | 0.007 | 0.000 | 0.000 | 3.911 |
Maximum of Months | 744.000 | 30.475 | 675.004 | 8.497 | 30.475 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 680.117 | 20.519 | 23.271 |
February | 17.438 | 0.205 | 557.408 | 14.188 | 16.774 |
March | 117.393 | 2.273 | 385.884 | 7.336 | 14.307 |
April | 271.201 | 5.836 | 114.500 | 1.273 | 14.396 |
May | 481.995 | 18.847 | 51.292 | 0.487 | 22.095 |
June | 672.548 | 33.241 | 0.000 | 0.000 | 33.369 |
July | 742.000 | 42.008 | 0.000 | 0.000 | 42.008 |
August | 725.567 | 38.415 | 0.000 | 0.000 | 38.415 |
September | 593.001 | 25.365 | 0.000 | 0.000 | 25.918 |
October | 272.439 | 7.469 | 166.208 | 2.356 | 16.305 |
November | 74.735 | 1.374 | 342.146 | 5.783 | 14.692 |
December | 28.625 | 0.390 | 599.767 | 17.375 | 21.850 |
Annual Sum or Average | 3996.941 | 175.424 | 2897.321 | 69.317 | 283.400 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 14.307 |
Maximum of Months | 742.000 | 42.008 | 680.117 | 20.519 | 42.008 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 710.471 | 26.130 | 30.958 |
February | 8.500 | 0.078 | 586.113 | 18.512 | 26.102 |
March | 67.421 | 1.619 | 453.889 | 9.695 | 28.059 |
April | 184.163 | 4.453 | 201.734 | 1.953 | 13.520 |
May | 437.355 | 19.051 | 82.706 | 0.656 | 21.645 |
June | 659.826 | 33.238 | 1.425 | 0.004 | 33.432 |
July | 743.250 | 43.896 | 0.000 | 0.000 | 43.896 |
August | 719.723 | 38.312 | 0.000 | 0.000 | 38.312 |
September | 545.195 | 22.597 | 7.634 | 0.026 | 23.144 |
October | 157.317 | 3.932 | 261.058 | 3.782 | 20.702 |
November | 11.771 | 0.060 | 444.176 | 8.385 | 26.528 |
December | 6.750 | 0.051 | 646.481 | 21.791 | 28.745 |
Annual Sum or Average | 3541.270 | 167.287 | 3395.687 | 90.934 | 335.043 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 13.520 |
Maximum of Months | 743.250 | 43.896 | 710.471 | 26.130 | 43.896 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.440 | 10.751 | 10.808 |
February | 6.000 | 0.024 | 634.137 | 7.717 | 8.086 |
March | 51.875 | 0.898 | 552.049 | 4.163 | 7.472 |
April | 152.613 | 1.636 | 174.820 | 0.719 | 3.479 |
May | 475.948 | 11.727 | 68.048 | 0.190 | 11.933 |
June | 685.367 | 22.200 | 0.000 | 0.000 | 22.200 |
July | 744.000 | 29.511 | 0.000 | 0.000 | 29.511 |
August | 740.533 | 26.264 | 0.000 | 0.000 | 26.264 |
September | 582.681 | 15.522 | 0.000 | 0.000 | 15.522 |
October | 150.217 | 2.218 | 309.708 | 1.464 | 4.765 |
November | 9.500 | 0.039 | 546.289 | 3.501 | 5.213 |
December | 13.500 | 0.067 | 680.540 | 8.947 | 9.283 |
Annual Sum or Average | 3612.233 | 110.104 | 3702.030 | 37.451 | 154.534 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 3.479 |
Maximum of Months | 744.000 | 29.511 | 736.440 | 10.751 | 29.511 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.188 | 25.292 | 25.812 |
February | 0.000 | 0.000 | 632.342 | 17.751 | 18.174 |
March | 54.227 | 1.111 | 541.525 | 9.451 | 13.316 |
April | 222.359 | 3.576 | 144.063 | 1.598 | 11.580 |
May | 478.533 | 17.845 | 54.771 | 0.528 | 20.928 |
June | 673.281 | 32.666 | 0.000 | 0.000 | 32.785 |
July | 742.000 | 41.317 | 0.000 | 0.000 | 41.317 |
August | 725.567 | 36.598 | 0.000 | 0.000 | 36.598 |
September | 584.623 | 21.735 | 0.000 | 0.000 | 22.438 |
October | 159.504 | 3.025 | 281.938 | 3.603 | 11.429 |
November | 4.625 | 0.018 | 555.777 | 8.753 | 12.716 |
December | 5.750 | 0.033 | 683.708 | 21.448 | 23.239 |
Annual Sum or Average | 3650.467 | 157.923 | 3631.310 | 88.424 | 270.331 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 11.429 |
Maximum of Months | 742.000 | 41.317 | 737.188 | 25.292 | 41.317 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 732.750 | 32.877 | 32.877 |
February | 9.000 | 0.171 | 607.875 | 23.717 | 24.307 |
March | 87.842 | 2.569 | 495.942 | 13.111 | 19.584 |
April | 200.396 | 6.153 | 210.013 | 2.951 | 18.852 |
May | 427.159 | 21.293 | 89.212 | 1.063 | 25.475 |
June | 649.579 | 36.837 | 3.875 | 0.020 | 37.231 |
July | 741.375 | 49.278 | 0.000 | 0.000 | 49.278 |
August | 716.144 | 43.975 | 0.000 | 0.000 | 43.975 |
September | 548.595 | 27.575 | 8.250 | 0.052 | 28.688 |
October | 223.060 | 7.659 | 278.117 | 4.893 | 16.966 |
November | 60.517 | 1.158 | 478.546 | 10.542 | 12.913 |
December | 20.875 | 0.291 | 667.229 | 27.557 | 27.920 |
Annual Sum or Average | 3684.540 | 196.957 | 3571.809 | 116.784 | 338.065 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.913 |
Maximum of Months | 741.375 | 49.278 | 732.750 | 32.877 | 49.278 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 729.729 | 13.483 | 13.969 |
February | 9.500 | 0.096 | 603.104 | 9.727 | 11.264 |
March | 74.275 | 1.307 | 499.342 | 5.237 | 7.792 |
April | 194.138 | 3.009 | 221.088 | 1.161 | 5.127 |
May | 445.789 | 14.032 | 86.969 | 0.391 | 14.451 |
June | 678.173 | 26.073 | 1.825 | 0.001 | 26.075 |
July | 744.000 | 35.258 | 0.000 | 0.000 | 35.258 |
August | 729.924 | 32.163 | 0.000 | 0.000 | 32.163 |
September | 583.861 | 20.584 | 5.375 | 0.005 | 20.589 |
October | 244.554 | 5.359 | 255.708 | 1.693 | 7.101 |
November | 61.208 | 0.732 | 449.817 | 3.862 | 4.996 |
December | 24.500 | 0.247 | 647.075 | 11.217 | 12.028 |
Annual Sum or Average | 3789.923 | 138.861 | 3500.031 | 46.776 | 190.814 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.996 |
Maximum of Months | 744.000 | 35.258 | 729.729 | 13.483 | 35.258 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 733.872 | 26.597 | 26.930 |
February | 9.875 | 0.078 | 616.638 | 18.884 | 19.665 |
March | 78.292 | 1.593 | 485.254 | 10.159 | 14.886 |
April | 232.817 | 4.557 | 183.613 | 2.173 | 12.599 |
May | 462.609 | 18.544 | 72.958 | 0.801 | 21.965 |
June | 666.072 | 33.923 | 0.250 | 0.001 | 34.160 |
July | 741.500 | 43.680 | 0.000 | 0.000 | 43.680 |
August | 719.700 | 39.400 | 0.000 | 0.000 | 39.400 |
September | 576.923 | 24.713 | 2.500 | 0.018 | 25.581 |
October | 232.790 | 6.058 | 234.708 | 3.649 | 14.979 |
November | 47.842 | 0.739 | 447.125 | 8.363 | 14.564 |
December | 18.042 | 0.200 | 653.304 | 22.495 | 25.556 |
Annual Sum or Average | 3786.460 | 173.485 | 3430.222 | 93.141 | 293.966 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.599 |
Maximum of Months | 741.500 | 43.680 | 733.872 | 26.597 | 43.680 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.684 | 35.941 | 37.106 |
February | 6.625 | 0.037 | 623.713 | 26.003 | 29.130 |
March | 60.671 | 1.604 | 515.475 | 14.328 | 28.157 |
April | 173.779 | 4.780 | 245.843 | 3.243 | 17.654 |
May | 422.032 | 20.799 | 102.201 | 1.104 | 24.456 |
June | 651.016 | 36.675 | 4.315 | 0.020 | 37.027 |
July | 741.500 | 49.064 | 0.000 | 0.000 | 49.064 |
August | 715.465 | 42.941 | 0.000 | 0.000 | 42.941 |
September | 530.713 | 24.890 | 12.569 | 0.072 | 26.058 |
October | 152.077 | 4.183 | 309.332 | 5.796 | 23.367 |
November | 6.188 | 0.027 | 515.467 | 12.645 | 26.424 |
December | 5.000 | 0.028 | 688.233 | 30.260 | 33.189 |
Annual Sum or Average | 3465.065 | 185.027 | 3753.832 | 129.413 | 374.572 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 17.654 |
Maximum of Months | 741.500 | 49.064 | 736.684 | 35.941 | 49.064 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.754 | 15.984 | 16.007 |
February | 2.000 | 0.003 | 640.892 | 11.635 | 11.811 |
March | 48.283 | 0.950 | 589.579 | 6.573 | 9.660 |
April | 148.725 | 2.031 | 250.694 | 1.362 | 4.637 |
May | 440.935 | 13.676 | 89.250 | 0.407 | 14.101 |
June | 679.295 | 25.985 | 1.188 | 0.000 | 25.986 |
July | 744.000 | 35.119 | 0.000 | 0.000 | 35.119 |
August | 729.549 | 31.260 | 0.000 | 0.000 | 31.260 |
September | 562.223 | 18.114 | 9.517 | 0.011 | 18.132 |
October | 141.025 | 2.472 | 356.106 | 2.537 | 6.629 |
November | 3.250 | 0.013 | 587.813 | 5.665 | 8.020 |
December | 5.750 | 0.031 | 699.329 | 13.420 | 13.755 |
Annual Sum or Average | 3505.036 | 129.656 | 3968.120 | 57.593 | 195.117 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 4.637 |
Maximum of Months | 744.000 | 35.119 | 743.754 | 15.984 | 35.119 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 29.918 | 29.918 |
February | 0.000 | 0.000 | 640.921 | 21.348 | 21.609 |
March | 46.425 | 1.083 | 589.150 | 11.879 | 14.149 |
April | 200.945 | 3.466 | 208.667 | 2.397 | 11.267 |
May | 459.536 | 18.463 | 73.625 | 0.806 | 21.853 |
June | 667.324 | 34.305 | 0.125 | 0.000 | 34.565 |
July | 741.500 | 44.144 | 0.000 | 0.000 | 44.144 |
August | 719.367 | 39.127 | 0.000 | 0.000 | 39.127 |
September | 568.446 | 22.721 | 3.125 | 0.025 | 23.598 |
October | 150.876 | 3.060 | 337.756 | 4.820 | 12.220 |
November | 2.250 | 0.007 | 609.321 | 11.039 | 13.827 |
December | 3.750 | 0.014 | 702.929 | 25.479 | 26.673 |
Annual Sum or Average | 3560.419 | 166.389 | 3909.618 | 107.710 | 292.948 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 11.267 |
Maximum of Months | 741.500 | 44.144 | 744.000 | 29.918 | 44.144 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.30 |
February | 0.00 | 0.00 | 0.38 |
March | 0.00 | 0.00 | 0.57 |
April | 0.00 | 0.00 | 0.75 |
May | 0.00 | 0.00 | 0.94 |
June | 0.00 | 0.00 | 1.11 |
July | 0.00 | 0.00 | 1.21 |
August | 0.00 | 0.00 | 1.16 |
September | 0.00 | 0.00 | 1.06 |
October | 0.00 | 0.00 | 0.75 |
November | 0.00 | 0.00 | 0.60 |
December | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.00 | 0.00 | 0.77 |
Minimum of Months | 0.00 | 0.00 | 0.30 |
Maximum of Months | 0.00 | 0.00 | 1.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.16 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.23 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.29 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.15 |
June | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.36 |
September | 0.00 | 0.00 | 0.25 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.33 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.17 |
June | 0.00 | 0.00 | 0.31 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.17 |
June | 0.00 | 0.00 | 0.32 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.19 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.26 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.14 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.22 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.19 |
June | 0.00 | 0.00 | 0.36 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.40 |
September | 0.00 | 0.00 | 0.27 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.00 | 0.44 |
August | 0.00 | 0.00 | 0.38 |
September | 0.00 | 0.00 | 0.24 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.44 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.14 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.18 |
June | 0.00 | 0.00 | 0.35 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.39 |
September | 0.00 | 0.00 | 0.24 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.14 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |
Minimum of Months | 0.00 | 0.00 | 1173.50 | 873.70 |
Maximum of Months | 0.00 | 0.00 | 1648.00 | 1211.47 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:40:37
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1627.17 | 1211.47 |
February | 0.00 | 0.00 | 1648.00 | 1108.24 |
March | 0.00 | 0.00 | 1602.05 | 1192.77 |
April | 0.00 | 0.00 | 1513.09 | 1090.20 |
May | 0.00 | 0.00 | 1387.72 | 1033.20 |
June | 0.00 | 0.00 | 1273.58 | 917.63 |
July | 0.00 | 0.00 | 1197.59 | 891.64 |
August | 0.00 | 0.00 | 1173.50 | 873.70 |
September | 0.00 | 0.00 | 1219.71 | 878.81 |
October | 0.00 | 0.00 | 1313.95 | 978.27 |
November | 0.00 | 0.00 | 1432.90 | 1032.42 |
December | 0.00 | 0.00 | 1553.82 | 1156.86 |
Annual Sum or Average | 0.00 | 0.00 | 1410.55 | 12365.22 |