Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42
Tabular Output Report in Format: HTML
Building: MF+CZ4CWH+USA_OR_Salem-McNary.Field.726940+hp+heatedbsmt+IECC_2012
Environment: ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940
Simulation Timestamp: 2019-02-14 08:42:04
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 670589.32 | 17.19 | 22.81 |
Net Site Energy | 670589.32 | 17.19 | 22.81 |
Total Source Energy | 2123756.38 | 54.45 | 72.23 |
Net Source Energy | 2123756.38 | 54.45 | 72.23 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 103228.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 29031.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 8724.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 299910.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17084.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 168400.40 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 670589.32 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 103228.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 29031.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 44208.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 7094.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1630.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 9491.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 4847.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 17084.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 168400.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377715.79 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 10.81 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
Other | 10.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 22.81 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 8.15 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
Other | 7.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 17.19 | 0.00 | 0.00 | 0.00 | 0.00 | 9.68 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 670589.320 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 670589.320 | 100.00 |
Total On-Site and Utility Electric Sources | 670589.320 | 100.00 |
Total Electricity End Uses | 670589.320 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 377715.79 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 377715.79 | 100.00 |
Total Water End Uses | 377715.79 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 61.75 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 88.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNITHEATEDBSMT | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:42 |
RunPeriod | ANNUAL |
Weather File | Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Latitude [deg] | 44.90 |
Longitude [deg] | -123.0 |
Elevation [ft] | 196.86 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6659 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6659 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.3689 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.4894 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 23-DEC-08:15 | - | - | - | - | 01-JAN-08:30 |
Heating | 98.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 35.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 128.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 272.16 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 98.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 2.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 1.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 16.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 7.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 128.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 326925.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 91943.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 140006.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 27632.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 949816.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 54107.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 533324.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2123756.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 11.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 72.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 11.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 4.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 18.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 72.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 21.92 | 0.00 | 21.92 | Wetbulb [F] | 413.41 | 0.00 |
SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 91.94 | 27.72 | 66.92 | Wetbulb [F] | 846.50 | 0.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.320 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.320 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.320 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.4836 | 1200.55 | 580.62 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 522.42 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3329 | 43219.92 | 14389.84 | 12947.46 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 26.35 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 115.43 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 8.64 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 26.54 |
Exterior Lighting Total | 629.94 | 2555.34 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14073.62 | 11239.97 | 2833.65 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6333.88 | 4839.08 | 1494.80 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8222.17 | 6402.19 | 1819.98 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10965.34 | 8757.53 | 2207.81 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 4724.09 | 3719.56 | 1004.52 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 6900.81 | 5511.37 | 1389.44 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11728.86 | 9367.32 | 2361.54 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6117.19 | 4664.00 | 1453.19 | 0.76 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 8124.57 | 6325.06 | 1799.52 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10710.89 | 8554.31 | 2156.58 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 4786.40 | 3770.09 | 1016.30 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 6663.86 | 5322.13 | 1341.73 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12321.69 | 9840.78 | 2480.91 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6318.42 | 4999.09 | 1319.33 | 0.79 | 4.07 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8283.09 | 6442.14 | 1840.95 | 0.78 | 4.07 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11960.28 | 9552.14 | 2408.14 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 5968.03 | 4749.85 | 1218.18 | 0.80 | 4.07 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 6992.62 | 5509.52 | 1483.11 | 0.79 | 4.07 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 2325.21 | 1710.20 | 615.00 | 0.74 | 4.07 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5 | 3.32 | 11.33 | 11.86 | 11.19 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.29 | 11.24 | 11.76 | 11.05 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.4 | 3.28 | 11.18 | 11.70 | 10.97 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5 | 3.32 | 11.34 | 11.88 | 11.21 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.6 | 3.29 | 11.24 | 11.76 | 11.05 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.4 | 3.28 | 11.18 | 11.70 | 10.97 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.5 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.0 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.5 | 3.27 | 11.16 | 11.67 | 10.93 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.7 | 3.30 | 11.24 | 11.77 | 11.06 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 0.9 | 3.26 | 11.11 | 11.62 | 10.86 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.5 | 3.26 | 11.13 | 11.64 | 10.89 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.6 | 3.28 | 11.18 | 11.70 | 10.96 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.2 | 3.38 | 11.52 | 12.07 | 11.47 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 14748.1 | 8213.8 | 7.86 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6609.6 | 3668.8 | 7.94 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 8595.3 | 4777.8 | 7.84 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 11490.9 | 6399.7 | 7.90 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 4943.7 | 2750.4 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 7231.6 | 4027.5 | 7.85 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 12291.0 | 6845.4 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6382.2 | 3542.0 | 7.94 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 8493.2 | 4721.0 | 7.82 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11224.2 | 6251.2 | 7.90 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 5009.1 | 2786.8 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6983.2 | 3889.3 | 7.87 | 4 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12912.2 | 7191.3 | 7.81 | 4 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6615.3 | 3681.6 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 8658.1 | 4812.3 | 7.85 | 4 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12533.5 | 6980.4 | 7.77 | 4 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6252.0 | 3481.0 | 7.88 | 4 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 7318.2 | 4071.6 | 7.86 | 4 |
MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | 2418.0 | 1338.4 | 6.83 | 4 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 14073.62 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 7521.58 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6333.88 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 7805.99 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 8222.17 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 9448.47 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 10965.34 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 9449.54 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 4724.09 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 7807.20 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:DX:SingleSpeed | 6900.81 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 9446.86 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 11728.86 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8872.80 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6117.19 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 7223.48 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 8124.57 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 8875.51 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 10710.89 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8875.96 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 4786.40 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 7223.99 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:DX:SingleSpeed | 6663.86 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 8873.42 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 12321.69 | 3.69 | |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 10631.17 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6318.42 | 3.69 | |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 8978.21 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 8283.09 | 3.69 | |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 10633.05 | 1.00 | |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 11960.28 | 3.69 | |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 10633.21 | 1.00 | |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 5968.03 | 3.69 | |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 8978.39 | 1.00 | |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:DX:SingleSpeed | 6992.62 | 3.69 | |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 10631.36 | 1.00 | |
MAIN DX HEATING COIL_UNITHEATEDBSMT | Coil:Heating:DX:SingleSpeed | 2325.21 | 3.69 | |
SUPP HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Electric | 6305.65 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 527.91 | 199.13 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 215.19 | 81.17 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 291.64 | 110.00 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 411.32 | 155.15 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 171.76 | 64.79 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 258.86 | 97.64 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 439.96 | 165.95 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 206.86 | 78.03 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 288.06 | 108.65 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 401.78 | 151.55 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 174.18 | 65.70 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 249.97 | 94.29 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 462.20 | 174.34 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 232.20 | 87.58 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 293.04 | 110.53 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 448.64 | 169.22 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 222.18 | 83.80 | 0.38 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 254.63 | 96.04 | 0.38 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.50 | 0.06 | 72.24 | 27.25 | 0.38 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12315.25 | 12315.25 | 10.26 | 527.915 | 527.915 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:30:00 | 74.98 | 74.98 | 0.00819 | 86.67 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5019.94 | 5019.94 | 4.18 | 215.194 | 215.194 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 74.98 | 74.98 | 0.00829 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6803.33 | 6803.33 | 5.67 | 291.639 | 291.639 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 74.98 | 74.98 | 0.00822 | 91.59 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9595.33 | 9595.33 | 7.99 | 411.320 | 411.320 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00826 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4006.88 | 4006.88 | 3.34 | 171.761 | 171.761 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00860 | 81.13 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6038.66 | 6038.66 | 5.03 | 258.856 | 258.856 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:30:00 | 74.98 | 74.98 | 0.00833 | 79.05 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10263.46 | 10263.46 | 8.55 | 439.960 | 439.960 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00824 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4825.52 | 4825.52 | 4.02 | 206.860 | 206.860 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:45:00 | 74.98 | 74.98 | 0.00829 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6719.87 | 6719.87 | 5.60 | 288.061 | 288.061 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:45:00 | 74.98 | 74.98 | 0.00822 | 91.59 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9372.67 | 9372.67 | 7.81 | 401.776 | 401.776 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00827 | 85.29 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4063.22 | 4063.22 | 3.38 | 174.177 | 174.177 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00860 | 81.13 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5831.32 | 5831.32 | 4.86 | 249.968 | 249.968 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:45:00 | 74.98 | 74.98 | 0.00831 | 80.23 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 5940.04 | 5940.04 | 4.95 | 254.629 | 254.629 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00836 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 6835.86 | 6835.86 | 5.69 | 293.036 | 293.036 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:15:00 | 74.98 | 74.98 | 0.00822 | 91.94 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 10782.20 | 10782.20 | 8.98 | 462.198 | 462.198 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:45:00 | 74.98 | 74.98 | 0.00823 | 85.98 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 5182.99 | 5182.99 | 4.32 | 222.178 | 222.178 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 19:00:00 | 74.98 | 74.98 | 0.00850 | 81.13 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 5416.77 | 5416.77 | 4.51 | 232.199 | 232.199 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | 74.98 | 74.98 | 0.00846 | 83.21 | 0.00850 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 10465.94 | 10465.94 | 8.72 | 448.641 | 448.641 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 74.98 | 74.98 | 0.00825 | 85.29 | 0.00850 | 44.995 | 0.00 |
HEATEDBSMT | 393.45 | 393.45 | 0.05 | 16.865 | 44.995 | SALEM MCNARY FIELD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:45:00 | 74.98 | 74.98 | 0.00828 | 82.17 | 0.00850 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5175.12 | 5175.12 | 4.31 | 94.850 | 94.850 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00582 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5463.76 | 5463.76 | 4.55 | 100.139 | 100.139 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00595 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7130.55 | 7130.55 | 5.94 | 130.686 | 130.686 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00620 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7131.63 | 7131.63 | 5.94 | 130.706 | 130.706 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00620 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5464.98 | 5464.98 | 4.55 | 100.161 | 100.161 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00595 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7128.92 | 7128.92 | 5.94 | 130.656 | 130.656 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00620 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 6546.28 | 6546.28 | 5.45 | 119.982 | 119.982 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4872.55 | 4872.55 | 4.06 | 89.306 | 89.306 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00612 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6549.03 | 6549.03 | 5.46 | 120.032 | 120.032 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6549.49 | 6549.49 | 5.46 | 120.040 | 120.040 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4873.06 | 4873.06 | 4.06 | 89.316 | 89.316 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00612 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6546.91 | 6546.91 | 5.45 | 119.993 | 119.993 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8330.92 | 8330.92 | 6.94 | 152.685 | 152.685 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 8332.64 | 8332.64 | 6.94 | 152.717 | 152.717 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 8330.74 | 8330.74 | 6.94 | 152.682 | 152.682 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6653.49 | 6653.49 | 5.54 | 121.944 | 121.944 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00618 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6653.31 | 6653.31 | 5.54 | 121.940 | 121.940 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00618 | 21.92 | 0.00237 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 8332.81 | 8332.81 | 6.94 | 152.720 | 152.720 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00638 | 21.92 | 0.00237 | 44.995 | 0.00 |
HEATEDBSMT | 3940.77 | 3940.77 | 0.51 | 72.239 | 72.239 | SALEM MCNARY FIELD ANN HTG 99.6% CONDNS DB | 12/21 17:15:00 | 72.00 | 72.00 | 0.00800 | 21.92 | 0.00237 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 | 527.91 | 94.85 | 94.85 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 | 215.19 | 100.14 | 100.14 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 | 291.64 | 130.69 | 130.69 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 | 411.32 | 130.71 | 130.71 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 | 171.76 | 100.16 | 100.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 | 258.86 | 130.66 | 130.66 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 | 439.96 | 119.98 | 119.98 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 | 206.86 | 89.31 | 89.31 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 | 288.06 | 120.03 | 120.03 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 | 401.78 | 120.04 | 120.04 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 | 174.18 | 89.32 | 89.32 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 | 249.97 | 119.99 | 119.99 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 462.20 | 462.20 | 152.68 | 152.68 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 232.20 | 232.20 | 121.94 | 121.94 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 293.04 | 293.04 | 152.72 | 152.72 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 448.64 | 448.64 | 152.72 | 152.72 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 222.18 | 222.18 | 121.94 | 121.94 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 254.63 | 254.63 | 152.69 | 152.69 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 72.24 | 72.24 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1275.25 | 5574.75 | 23.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 891.75 | 5915.50 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1405.25 | 5937.50 | 22.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1162.00 | 6466.75 | 36.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 613.00 | 6451.75 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1186.00 | 6281.50 | 26.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1471.50 | 5844.75 | 20.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 931.75 | 5722.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1456.25 | 5799.50 | 20.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1219.75 | 6324.75 | 34.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 697.75 | 6220.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1259.00 | 6131.75 | 23.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1385.00 | 6276.25 | 87.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1477.25 | 6047.00 | 50.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1448.75 | 6194.75 | 50.25 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 930.00 | 6426.75 | 14.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1099.00 | 6108.25 | 6.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1312.00 | 6476.50 | 75.00 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1997.00 | 6871.75 | 88.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 11.00 | 0.00 | 11.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 4.25 | 0.00 | 4.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 19.00 | 0.00 | 19.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 39.00 | 0.00 | 39.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 20.25 | 0.00 | 20.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 9.00 | 0.00 | 9.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 5.50 | 0.00 | 5.50 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 17.25 | 0.00 | 17.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 34.50 | 0.00 | 34.50 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 28.25 | 0.00 | 28.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 47.50 | 0.00 | 47.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 12.50 | 0.00 | 12.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 14.75 | 0.00 | 14.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 34.25 | 0.00 | 34.25 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 25.25 | 0.00 | 25.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 17.25 | 0.00 | 17.25 |
HEATEDBSMT | 74.75 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 74.75 | 61.75 | 0.00 | 61.75 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.115 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.100 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.114 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.113 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.100 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.113 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.036 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.036 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.050 | 0.000 | 0.275 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.113 | 0.000 | 0.275 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.114 | 0.000 | 0.275 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.113 | 0.000 | 0.275 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.100 | 0.000 | 0.275 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.100 | 0.000 | 0.275 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.113 | 0.000 | 0.275 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.006 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1865 |
Defaulted Fields | 531 |
Fields with Defaults | 4810 |
Autosized Fields | 338 |
Autosizable Fields | 467 |
Autocalculated Fields | 98 |
Autocalculatable Fields | 286 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
Electricity:Building | 100783.92 | 6307.14 | 02-JAN-03:15 | 19201.42 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 12947.46 | 289.95 | 01-JAN-00:15 | 4217.42 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5599.11 | 350.40 | 02-JAN-03:15 | 1066.75 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 719.30 | 16.11 | 01-JAN-00:15 | 234.30 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 87836.46 | 5989.55 | 02-JAN-04:15 | 15395.85 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 2779.94 | 25.45 | 02-JAN-03:15 | 887.02 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1419.57 | 13.63 | 02-JAN-02:15 | 384.46 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4879.80 | 332.75 | 02-JAN-04:15 | 855.33 | 01-JAN-18:15 |
Electricity:Plant | 49320.39 | 0.00 | 01-JAN-00:15 | 38008.66 | 25-FEB-08:30 |
WaterSystems:Electricity | 49320.39 | 0.00 | 01-JAN-00:15 | 38008.66 | 25-FEB-08:30 |
Water Heater:WaterSystems:Electricity | 49320.39 | 0.00 | 01-JAN-00:15 | 38008.66 | 25-FEB-08:30 |
Fans:Electricity | 5003.73 | 0.00 | 03-MAY-01:15 | 2115.45 | 21-DEC-04:00 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
ElectricityPurchased:Plant | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
Cogeneration:ElectricityPurchased | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
ElectricityNet:Plant | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
Cogeneration:ElectricityNet | 196399.35 | 6800.77 | 19-JUN-03:15 | 79708.55 | 23-DEC-08:15 |
ExteriorLights:Electricity | 2555.34 | 20.06 | 01-JAN-09:15 | 629.94 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2077.71 | 0.00 | 01-JAN-06:15 | 474.36 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 477.63 | 10.70 | 01-JAN-00:15 | 155.58 | 01-JAN-19:15 |
Electricity:HVAC | 43739.70 | 5.44 | 27-MAY-01:45 | 32567.23 | 21-DEC-04:00 |
General:Fans:Electricity | 5003.73 | 0.00 | 03-MAY-01:15 | 2115.45 | 21-DEC-04:00 |
Cooling:Electricity | 8502.73 | 0.00 | 01-JAN-00:15 | 11118.53 | 16-JUL-16:00 |
Heating:Electricity | 30233.24 | 0.00 | 01-MAY-11:00 | 30451.78 | 21-DEC-04:00 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
Water:Plant | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
WaterSystems:Water | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
MainsWater:Plant | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
WaterSystems:MainsWater | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
Domestic Hot Water:WaterSystems:MainsWater | 50500.66 | 0.01 | 07-AUG-02:45 | 0.18 | 01-JAN-08:30 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
PlantLoopHeatingDemand:Plant | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 733003.82 | 1612.02 | 02-OCT-03:00 | 298943.37 | 23-DEC-08:15 |
EnergyTransfer:Building | 285967.25 | 0.00 | 03-MAY-01:15 | 140829.38 | 21-DEC-04:00 |
EnergyTransfer:Zone:HEATEDBSMT | 11850.76 | 0.00 | 01-MAY-11:00 | 7757.83 | 11-DEC-22:00 |
Heating:EnergyTransfer | 176685.87 | 0.00 | 01-MAY-11:00 | 140829.38 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 11827.47 | 0.00 | 01-MAY-11:00 | 7757.83 | 11-DEC-22:00 |
Cooling:EnergyTransfer | 109281.38 | 0.00 | 01-JAN-00:15 | 130545.71 | 24-JUN-18:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 23.29 | 0.00 | 01-JAN-00:15 | 531.29 | 16-JUL-19:30 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 17394.87 | 0.00 | 01-JAN-11:30 | 12445.48 | 24-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 3059.44 | 0.00 | 01-JAN-11:30 | 6294.34 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 14335.44 | 0.00 | 01-JAN-00:15 | 12445.48 | 24-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 11241.50 | 0.00 | 01-JAN-12:15 | 6219.09 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6551.24 | 0.00 | 01-JAN-12:15 | 6219.09 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4690.26 | 0.00 | 01-JAN-00:15 | 5283.81 | 24-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16313.18 | 0.00 | 01-JAN-12:30 | 8183.14 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9592.32 | 0.00 | 01-JAN-12:30 | 8183.14 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6720.86 | 0.00 | 01-JAN-00:15 | 6994.57 | 09-SEP-13:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 16930.25 | 0.00 | 19-JAN-15:15 | 9819.62 | 24-JUN-19:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11121.91 | 0.00 | 19-JAN-15:15 | 8291.80 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5808.34 | 0.00 | 01-JAN-00:15 | 9819.62 | 24-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 11254.09 | 0.00 | 24-FEB-18:15 | 6401.42 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8146.96 | 0.00 | 24-FEB-18:15 | 6401.42 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 3107.12 | 0.00 | 01-JAN-00:15 | 4268.01 | 24-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16129.69 | 0.00 | 25-FEB-14:15 | 8320.00 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 11052.59 | 0.00 | 25-FEB-14:15 | 8320.00 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5077.10 | 0.00 | 01-JAN-00:15 | 6010.53 | 16-JUL-09:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15770.10 | 0.00 | 01-JAN-13:45 | 10421.12 | 24-JUN-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7913.15 | 0.00 | 01-JAN-13:45 | 7322.38 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7856.95 | 0.00 | 01-JAN-00:15 | 10421.12 | 24-JUN-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 10114.07 | 0.00 | 01-JAN-12:15 | 5374.54 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5161.05 | 0.00 | 01-JAN-12:15 | 5374.54 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4953.02 | 0.00 | 01-JAN-00:15 | 5133.03 | 24-JUN-18:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15031.64 | 0.00 | 01-JAN-12:30 | 7360.49 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8054.63 | 0.00 | 01-JAN-12:30 | 7360.49 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6977.00 | 0.00 | 01-JAN-00:15 | 6885.65 | 09-SEP-13:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 15488.05 | 0.00 | 19-JAN-15:30 | 9594.92 | 24-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9479.87 | 0.00 | 19-JAN-15:30 | 7468.34 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 6008.18 | 0.00 | 01-JAN-00:15 | 9594.92 | 24-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9945.81 | 0.00 | 14-JAN-19:15 | 5562.17 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6543.15 | 0.00 | 14-JAN-19:15 | 5562.17 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 3402.66 | 0.00 | 01-JAN-00:15 | 4269.03 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14781.58 | 0.00 | 25-FEB-14:00 | 7496.69 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9424.99 | 0.00 | 25-FEB-14:00 | 7496.69 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5356.60 | 0.00 | 01-JAN-00:15 | 5855.48 | 24-JUN-18:15 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 18819.84 | 0.00 | 25-FEB-15:15 | 9494.14 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 13142.36 | 0.00 | 25-FEB-15:15 | 9494.14 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5677.49 | 0.00 | 01-JAN-00:15 | 6304.03 | 24-JUN-19:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 18376.74 | 0.00 | 19-JAN-11:30 | 9384.32 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11725.18 | 0.00 | 19-JAN-11:30 | 9384.32 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 6651.56 | 0.00 | 01-JAN-00:15 | 7015.26 | 15-JUL-17:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 19337.45 | 0.00 | 18-JAN-15:15 | 10950.24 | 24-JUN-19:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11845.58 | 0.00 | 18-JAN-15:15 | 9352.68 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 7491.86 | 0.00 | 01-JAN-00:15 | 10950.24 | 24-JUN-19:00 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 14050.95 | 0.00 | 25-FEB-15:45 | 7564.99 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 10139.96 | 0.00 | 25-FEB-15:45 | 7564.99 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 3910.99 | 0.00 | 01-JAN-00:15 | 5413.00 | 24-JUN-19:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 13431.85 | 0.00 | 19-JAN-11:45 | 7414.01 | 21-DEC-04:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8645.71 | 0.00 | 19-JAN-11:45 | 7414.01 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4786.14 | 0.00 | 01-JAN-00:15 | 5633.23 | 24-JUN-19:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 19704.83 | 0.00 | 30-JAN-15:45 | 10722.57 | 24-JUN-19:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 13258.31 | 0.00 | 30-JAN-15:45 | 9470.21 | 21-DEC-04:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 6446.52 | 0.00 | 01-JAN-00:15 | 10722.57 | 24-JUN-19:30 |
EnergyTransfer:Plant | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
WaterSystems:EnergyTransfer | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 152635.37 | 1409.42 | 11-AUG-02:15 | 37783.34 | 11-FEB-09:00 |
EnergyTransfer:HVAC | 294401.20 | 0.00 | 03-MAY-01:15 | 148528.40 | 18-JUL-18:45 |
CoolingCoils:EnergyTransfer | 128244.22 | 0.00 | 01-JAN-00:15 | 148528.40 | 18-JUL-18:45 |
HeatingCoils:EnergyTransfer | 166156.99 | 0.00 | 01-MAY-11:00 | 133611.03 | 21-DEC-04:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 3059.413 | -1193.82 | 0.000 | 0.000 | 2988.479 | 2456.001 | 10405.511 | 8123.032 | 0.000 | 259.802 | 6449.030 | 0.000 | -5757.55 | 0.000 | -13648.35 | -0.05 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 6551.200 | -390.59 | 0.000 | 0.000 | 3051.644 | 2456.001 | 10405.511 | 3446.423 | 0.000 | 251.075 | 0.000 | 0.000 | -2291.91 | 0.000 | -12755.18 | -6424.55 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 9592.257 | -559.69 | 0.000 | 0.000 | 3067.121 | 2456.001 | 10405.511 | 7481.388 | 0.000 | 260.384 | 0.000 | 0.000 | -5484.85 | 0.000 | -13189.58 | -7867.43 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 11121.843 | -483.70 | 0.000 | 0.000 | 3075.774 | 2456.001 | 10405.511 | 5836.350 | 0.000 | 259.128 | 0.000 | 0.000 | -5740.21 | 0.000 | -13079.26 | -8526.87 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 8146.918 | -258.75 | 0.000 | 0.000 | 3068.844 | 2456.001 | 10405.511 | 993.099 | 0.000 | 248.590 | 0.000 | 0.000 | -2377.20 | 0.000 | -12616.09 | -7218.57 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 11052.515 | -422.81 | 0.000 | 0.000 | 3077.748 | 2456.001 | 10405.511 | 5093.512 | 0.000 | 259.197 | 0.000 | 0.000 | -5556.19 | 0.000 | -13094.29 | -8616.93 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 7913.101 | -654.30 | 0.000 | 0.000 | 3051.239 | 2456.001 | 10405.511 | 8172.366 | 0.000 | 216.111 | 0.000 | 0.000 | -5722.95 | 0.000 | -10993.62 | -7640.91 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 5161.023 | -412.47 | 0.000 | 0.000 | 3038.475 | 2456.001 | 10405.511 | 3442.962 | 0.000 | 207.268 | 0.000 | 0.000 | -2319.55 | 0.000 | -10553.77 | -6884.96 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 8054.576 | -581.02 | 0.000 | 0.000 | 3056.032 | 2456.001 | 10405.511 | 7471.670 | 0.000 | 216.533 | 0.000 | 0.000 | -5553.02 | 0.000 | -10992.57 | -8137.78 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 9479.809 | -500.34 | 0.000 | 0.000 | 3064.610 | 2456.001 | 10405.511 | 5831.328 | 0.000 | 215.856 | 0.000 | 0.000 | -5809.23 | 0.000 | -10901.18 | -8734.60 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 6543.113 | -283.36 | 0.000 | 0.000 | 3056.220 | 2456.001 | 10405.511 | 992.752 | 0.000 | 205.917 | 0.000 | 0.000 | -2402.11 | 0.000 | -10442.76 | -7412.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 9424.927 | -446.08 | 0.000 | 0.000 | 3067.761 | 2456.001 | 10405.511 | 5086.238 | 0.000 | 215.072 | 0.000 | 0.000 | -5618.29 | 0.000 | -10911.23 | -8769.42 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 13142.285 | -472.80 | 0.000 | 0.000 | 3074.688 | 2456.001 | 10405.511 | 5108.579 | 0.000 | 253.652 | 0.000 | 0.000 | -5593.43 | 0.000 | -13127.35 | -10042.48 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 11725.111 | -553.92 | 0.000 | 0.000 | 3067.494 | 2456.001 | 10405.511 | 7511.951 | 0.000 | 257.203 | 0.000 | 0.000 | -5514.09 | 0.000 | -13194.54 | -10063.13 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 11845.522 | -623.90 | 0.000 | 0.000 | 3066.060 | 2456.001 | 10405.511 | 8217.192 | 0.000 | 257.069 | 0.000 | 0.000 | -5665.04 | 0.000 | -13177.44 | -9913.11 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 10139.915 | -325.70 | 0.000 | 0.000 | 3067.048 | 2456.001 | 10405.511 | 1000.824 | 0.000 | 247.050 | 0.000 | 0.000 | -2384.89 | 0.000 | -12649.62 | -8370.87 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 8645.665 | -398.57 | 0.000 | 0.000 | 3056.033 | 2456.001 | 10405.511 | 3460.347 | 0.000 | 247.405 | 0.000 | 0.000 | -2297.15 | 0.000 | -12735.03 | -8452.69 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 13258.238 | -536.84 | 0.000 | 0.000 | 3073.452 | 2456.001 | 10405.511 | 5846.145 | 0.000 | 257.286 | 0.000 | 0.000 | -5773.67 | 0.000 | -13112.47 | -9964.06 |
HEATEDBSMT | 0.000 | 0.000 | 11827.474 | -1.94 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -11804.19 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4349.809 | 38270.439 | 0.000 | 0.000 | 0.000 | -42620.25 | -0.40 |
Total Facility | 0.000 | 0.000 | 176684.906 | -9100.62 | 0.000 | 0.000 | 55068.723 | 44208.020 | 187299.191 | 93116.160 | 0.000 | 8684.408 | 44719.470 | 0.000 | -81861.33 | 0.000 | -263794.59 | -154845.02 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 24-JUN-18:45 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 421.69 | 721.37 | 1735.60 | 5393.95 | 0.00 | 1079.87 | 3098.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 24-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.02 | 721.37 | 1735.60 | 418.38 | 0.00 | 1165.13 | 816.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 09-SEP-13:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 114.94 | 103.05 | 1100.57 | 4385.97 | 0.00 | 1200.83 | 89.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 24-JUN-19:04 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 414.12 | 799.44 | 1674.43 | 4322.54 | 0.00 | 855.06 | 1775.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 24-JUN-19:19 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 409.66 | 799.44 | 1674.43 | 752.57 | 0.00 | 702.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -61.2 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16-JUL-09:45 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 110.85 | 103.05 | 1113.11 | 5034.35 | 0.00 | 539.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -879.7 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 24-JUN-18:27 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 420.20 | 721.37 | 1735.60 | 6216.10 | 0.00 | 896.21 | 435.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 24-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 427.02 | 721.37 | 1735.60 | 422.68 | 0.00 | 905.66 | 921.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 09-SEP-13:45 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.17 | 103.05 | 1100.57 | 4188.85 | 0.00 | 967.30 | 410.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24-JUN-19:04 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 414.05 | 799.44 | 1674.43 | 4324.57 | 0.00 | 704.01 | 1697.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 24-JUN-19:48 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 412.90 | 799.44 | 1674.43 | 57.28 | 0.00 | 429.88 | 900.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 24-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.01 | 721.37 | 1735.60 | 1296.06 | 0.00 | 960.33 | 716.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 24-JUN-19:19 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 413.67 | 799.44 | 1674.43 | 980.20 | 0.00 | 744.03 | 1707.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 15-JUL-17:04 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 263.33 | 535.87 | 1676.47 | 1541.53 | 0.00 | 1464.60 | 1541.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 24-JUN-19:04 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 422.49 | 799.44 | 1674.43 | 3726.00 | 0.00 | 887.89 | 3506.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 413.61 | 799.44 | 1674.43 | 617.42 | 0.00 | 614.31 | 1302.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 422.91 | 799.44 | 1674.43 | 125.37 | 0.00 | 652.20 | 1968.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 24-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 424.82 | 799.44 | 1674.43 | 2441.29 | 0.00 | 682.25 | 4723.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-19:17 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 24-JUN-18:08 | 0.00 | 0.00 | 0.00 | -10.9 | 0.00 | 0.00 | 7578.09 | 12984.58 | 31240.86 | 50958.16 | 0.00 | 19504.41 | 22756.64 | 0.00 | 0.00 | 0.00 | -14453.4 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6294.46 | 0.00 | 0.00 | 0.00 | 526.28 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2325.0 | 0.00 | -4931.7 | -465.9 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6219.24 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -944.0 | 0.00 | -4733.6 | -1969.9 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8183.34 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2321.9 | 0.00 | -4931.6 | -2358.0 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8291.98 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2329.0 | 0.00 | -4931.6 | -2459.6 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 6401.58 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.5 | 0.00 | -4733.6 | -2146.7 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 8320.20 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2326.1 | 0.00 | -4931.6 | -2490.6 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7322.50 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2343.4 | 0.00 | -4002.2 | -2405.0 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 5374.63 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -951.5 | 0.00 | -3804.1 | -2047.2 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7360.63 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2340.8 | 0.00 | -4002.2 | -2445.7 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7468.46 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2345.8 | 0.00 | -4002.2 | -2548.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 5562.27 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -955.4 | 0.00 | -3804.1 | -2231.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7496.83 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2343.6 | 0.00 | -4002.2 | -2579.2 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9494.37 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2333.6 | 0.00 | -4938.1 | -3650.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9384.54 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2331.2 | 0.00 | -4938.1 | -3543.4 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9352.88 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2333.2 | 0.00 | -4938.1 | -3509.8 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7565.17 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.4 | 0.00 | -4739.7 | -3304.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 7414.18 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -946.1 | 0.00 | -4739.7 | -3156.5 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 21-DEC-04:00 | 0.00 | 0.00 | 9470.41 | 0.00 | 0.00 | 0.00 | 526.31 | 54.96 | 846.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2335.3 | 0.00 | -4938.1 | -3625.2 |
HEATEDBSMT | 27-JAN-15:53 | 0.00 | 0.00 | 8828.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -8828.7 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 21-DEC-04:00 | 0.00 | 0.00 | 140832.31 | 0.00 | 0.00 | 0.00 | 9473.49 | 989.30 | 15243.78 | 0.00 | 0.00 | 791.36 | 0.00 | 0.00 | -33704.5 | 0.00 | -82042.4 | -51583.3 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 527.915 | 2.00 | 2.00 | 1.00 | 44.9950 | 527.915 | 0.085 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 215.194 | 2.00 | 2.00 | 1.00 | 44.9950 | 215.194 | 0.209 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 291.639 | 2.00 | 2.00 | 1.00 | 44.9950 | 291.639 | 0.154 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 411.320 | 2.00 | 2.00 | 1.00 | 44.9950 | 411.320 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 171.761 | 2.00 | 2.00 | 1.00 | 44.9950 | 171.761 | 0.262 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 258.856 | 2.00 | 2.00 | 1.00 | 44.9950 | 258.856 | 0.174 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 439.960 | 2.00 | 2.00 | 1.00 | 44.9950 | 439.960 | 0.102 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 206.860 | 2.00 | 2.00 | 1.00 | 44.9950 | 206.860 | 0.218 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.061 | 2.00 | 2.00 | 1.00 | 44.9950 | 288.061 | 0.156 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 401.776 | 2.00 | 2.00 | 1.00 | 44.9950 | 401.776 | 0.112 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 174.177 | 2.00 | 2.00 | 1.00 | 44.9950 | 174.177 | 0.258 | 1.000 | 44.9950 | 0.26 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 249.968 | 2.00 | 2.00 | 1.00 | 44.9950 | 249.968 | 0.180 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 462.198 | 2.00 | 2.00 | 1.00 | 44.9950 | 462.198 | 0.097 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 232.199 | 2.00 | 2.00 | 1.00 | 44.9950 | 232.199 | 0.194 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 293.036 | 2.00 | 2.00 | 1.00 | 44.9950 | 293.036 | 0.154 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 448.641 | 2.00 | 2.00 | 1.00 | 44.9950 | 448.641 | 0.100 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 222.178 | 2.00 | 2.00 | 1.00 | 44.9950 | 222.178 | 0.203 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 254.629 | 2.00 | 2.00 | 1.00 | 44.9950 | 254.629 | 0.177 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 0.00 | 0.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 94.850 | 2.00 | 2.00 | 1.00 | 44.9950 | 94.850 | 1.000 | 1.000 | 44.9950 | 0.47 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 100.139 | 2.00 | 2.00 | 1.00 | 44.9950 | 100.139 | 1.000 | 1.000 | 44.9950 | 0.45 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 130.686 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.686 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 130.706 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.706 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 100.161 | 2.00 | 2.00 | 1.00 | 44.9950 | 100.161 | 1.000 | 1.000 | 44.9950 | 0.45 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 130.656 | 2.00 | 2.00 | 1.00 | 44.9950 | 130.656 | 1.000 | 1.000 | 44.9950 | 0.34 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 119.982 | 2.00 | 2.00 | 1.00 | 44.9950 | 119.982 | 1.000 | 1.000 | 44.9950 | 0.38 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 89.306 | 2.00 | 2.00 | 1.00 | 44.9950 | 89.306 | 1.000 | 1.000 | 44.9950 | 0.50 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 120.032 | 2.00 | 2.00 | 1.00 | 44.9950 | 120.032 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 120.040 | 2.00 | 2.00 | 1.00 | 44.9950 | 120.040 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 89.316 | 2.00 | 2.00 | 1.00 | 44.9950 | 89.316 | 1.000 | 1.000 | 44.9950 | 0.50 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 119.993 | 2.00 | 2.00 | 1.00 | 44.9950 | 119.993 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 152.682 | 2.00 | 2.00 | 1.00 | 44.9950 | 152.682 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 121.940 | 2.00 | 2.00 | 1.00 | 44.9950 | 121.940 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 152.717 | 2.00 | 2.00 | 1.00 | 44.9950 | 152.717 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 152.720 | 2.00 | 2.00 | 1.00 | 44.9950 | 152.720 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 121.944 | 2.00 | 2.00 | 1.00 | 44.9950 | 121.944 | 1.000 | 1.000 | 44.9950 | 0.37 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 152.685 | 2.00 | 2.00 | 1.00 | 44.9950 | 152.685 | 1.000 | 1.000 | 44.9950 | 0.29 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 72.239 | 0.00 | 0.00 | 1.00 | 44.9950 | 72.239 | 1.000 | 1.000 | 44.9950 | 0.62 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 527.915 | 527.9145 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 215.194 | 215.1937 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 291.639 | 291.6385 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 411.320 | 411.3201 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 171.761 | 171.7612 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 258.856 | 258.8558 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 439.960 | 439.9604 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 206.860 | 206.8599 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.061 | 288.0608 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 401.776 | 401.7755 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 174.177 | 174.1767 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 249.968 | 249.9677 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 254.629 | 254.6295 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 293.036 | 293.0360 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 462.198 | 462.1979 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 222.178 | 222.1777 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 232.199 | 232.1990 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 448.641 | 448.6410 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 44.9950 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 | 527.915 | 527.91 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 | 215.194 | 215.19 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 | 291.639 | 291.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 | 411.320 | 411.32 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 | 171.761 | 171.76 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 | 258.856 | 258.86 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 | 439.960 | 439.96 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 | 206.860 | 206.86 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 | 288.061 | 288.06 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 | 401.776 | 401.78 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 | 174.177 | 174.18 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 | 249.968 | 249.97 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 462.20 | 462.198 | 462.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 232.20 | 232.199 | 232.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 293.04 | 293.036 | 293.04 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 448.64 | 448.641 | 448.64 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 222.18 | 222.178 | 222.18 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 254.63 | 254.629 | 254.63 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.995 | 44.99 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 94.850 | 94.850 | 94.850 | 44.9950 | 0.474 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 100.139 | 100.139 | 100.139 | 44.9950 | 0.449 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 130.686 | 130.686 | 130.686 | 44.9950 | 0.344 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 130.706 | 130.706 | 130.706 | 44.9950 | 0.344 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 100.161 | 100.161 | 100.161 | 44.9950 | 0.449 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 130.656 | 130.656 | 130.656 | 44.9950 | 0.344 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 119.982 | 119.982 | 119.982 | 44.9950 | 0.375 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 89.306 | 89.306 | 89.306 | 44.9950 | 0.504 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 120.032 | 120.032 | 120.032 | 44.9950 | 0.375 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 120.040 | 120.040 | 120.040 | 44.9950 | 0.375 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 89.316 | 89.316 | 89.316 | 44.9950 | 0.504 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 119.993 | 119.993 | 119.993 | 44.9950 | 0.375 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 152.685 | 152.685 | 152.685 | 44.9950 | 0.295 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 152.717 | 152.717 | 152.717 | 44.9950 | 0.295 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 152.682 | 152.682 | 152.682 | 44.9950 | 0.295 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 121.944 | 121.944 | 121.944 | 44.9950 | 0.369 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 121.940 | 121.940 | 121.940 | 44.9950 | 0.369 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 152.720 | 152.720 | 152.720 | 44.9950 | 0.295 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 72.239 | 72.239 | 72.239 | 44.9950 | 0.623 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 94.85 | 94.850 | 94.85 | 94.85 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 100.14 | 100.139 | 100.14 | 100.14 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 130.69 | 130.686 | 130.69 | 130.69 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 130.71 | 130.706 | 130.71 | 130.71 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 100.16 | 100.161 | 100.16 | 100.16 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 130.66 | 130.656 | 130.66 | 130.66 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 119.98 | 119.982 | 119.98 | 119.98 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 89.31 | 89.306 | 89.31 | 89.31 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 120.03 | 120.032 | 120.03 | 120.03 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 120.04 | 120.040 | 120.04 | 120.04 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 89.32 | 89.316 | 89.32 | 89.32 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 119.99 | 119.993 | 119.99 | 119.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 152.68 | 152.682 | 152.68 | 152.68 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 121.94 | 121.940 | 121.94 | 121.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 152.72 | 152.717 | 152.72 | 152.72 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 152.72 | 152.720 | 152.72 | 152.72 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 121.94 | 121.944 | 121.94 | 121.94 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 152.69 | 152.685 | 152.69 | 152.69 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 72.24 | 72.239 | 72.24 | 72.24 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Salem Mcnary Field OR USA TMY3 WMO#=726940 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 61.75 |
Number of hours not met | 61.75 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 12947.46 | 797.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2555.34 | 29.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 30233.24 | 28703.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Cooling | 8502.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 5003.73 | 2100.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 49320.39 | 37768.38 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 87836.46 | 10309.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 196399.35 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 299910.33 | 670589.32 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 299910.33 | 670589.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.33 |
Space Heating | 0.78 |
Space Cooling | 0.22 |
Fans-Interior | 0.13 |
Service Water Heating | 1.26 |
Receptacle Equipment | 2.25 |
Miscellaneous | 0.07 |
Subtotal | 5.04 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 6.59 |
Space Heating | 15.39 |
Space Cooling | 4.33 |
Fans-Interior | 2.55 |
Service Water Heating | 25.11 |
Receptacle Equipment | 44.72 |
Miscellaneous | 1.30 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 72.24 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 254.63 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 293.04 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 462.20 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 222.18 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 232.20 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 448.64 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 462.20 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 232.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 293.04 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 448.64 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 222.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 254.63 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 72.24 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 | 1.17 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 | 0.527823 | 0.763999 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 | 0.685181 | 0.778649 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 | 0.913778 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 | 0.393674 | 0.787361 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 | 0.575068 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 | 0.977405 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 | 0.509766 | 0.762442 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 | 0.677048 | 0.778510 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 | 0.892574 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 | 0.398866 | 0.787668 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 | 0.555322 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 462.20 | 1.03 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 232.20 | 0.526535 | 0.791193 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 293.04 | 0.690257 | 0.777746 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 448.64 | 0.996690 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 222.18 | 0.497336 | 0.795882 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 254.63 | 0.582718 | 0.787904 |
DX COOLING COIL_UNITHEATEDBSMT | 72.24 | 0.193767 | 0.735506 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Supplemental Heating Coil Nominal Capacity [Btu/h] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 | 527.91 | 527.91 | 14073.62 | 1.17 | 7521.58 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 | 215.19 | 215.19 | 6333.88 | 0.527823 | 7805.99 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 | 291.64 | 291.64 | 8222.17 | 0.685181 | 9448.47 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 | 411.32 | 411.32 | 10965.34 | 0.913778 | 9449.54 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 | 171.76 | 171.76 | 4724.09 | 0.393674 | 7807.20 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 | 258.86 | 258.86 | 6900.81 | 0.575068 | 9446.86 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 | 439.96 | 439.96 | 11728.86 | 0.977405 | 8872.80 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 | 206.86 | 206.86 | 6117.19 | 0.509766 | 7223.48 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 | 288.06 | 288.06 | 8124.57 | 0.677048 | 8875.51 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 | 401.78 | 401.78 | 10710.89 | 0.892574 | 8875.96 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 | 174.18 | 174.18 | 4786.40 | 0.398866 | 7223.99 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 | 249.97 | 249.97 | 6663.86 | 0.555322 | 8873.42 | 1.00 |
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR | 462.20 | 462.20 | 462.20 | 12321.69 | 1.03 | 10631.17 | 1.00 |
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR | 232.20 | 232.20 | 232.20 | 6318.42 | 0.526535 | 8978.21 | 1.00 |
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR | 293.04 | 293.04 | 293.04 | 8283.09 | 0.690257 | 10633.05 | 1.00 |
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR | 448.64 | 448.64 | 448.64 | 11960.28 | 0.996690 | 10633.21 | 1.00 |
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR | 222.18 | 222.18 | 222.18 | 5968.03 | 0.497336 | 8978.39 | 1.00 |
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR | 254.63 | 254.63 | 254.63 | 6992.62 | 0.582718 | 10631.36 | 1.00 |
HEAT PUMP_UNITHEATEDBSMT | 72.24 | 72.24 | 72.24 | 2325.21 | 0.193767 | 6305.65 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 462.20 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 232.20 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 293.04 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 448.64 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 222.18 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 254.63 |
SUPPLY FAN_UNITHEATEDBSMT | 72.24 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Heating Capacity [Btu/h] | |
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 527.91 | 14073.62 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 215.19 | 6333.88 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 291.64 | 8222.17 |
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 411.32 | 10965.34 |
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 171.76 | 4724.09 |
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 258.86 | 6900.81 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 439.96 | 11728.86 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 206.86 | 6117.19 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 288.06 | 8124.57 |
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 401.78 | 10710.89 |
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 174.18 | 4786.40 |
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 249.97 | 6663.86 |
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 462.20 | 12321.69 |
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 232.20 | 6318.42 |
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 293.04 | 8283.09 |
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 448.64 | 11960.28 |
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 222.18 | 5968.03 |
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 254.63 | 6992.62 |
MAIN DX HEATING COIL_UNITHEATEDBSMT | 72.24 | 2325.21 |
Design Size Nominal Capacity [Btu/h] | |
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 7521.58 |
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 7805.99 |
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 9448.47 |
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 9449.54 |
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 7807.20 |
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 9446.86 |
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 8872.80 |
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 7223.48 |
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 8875.51 |
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 8875.96 |
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 7223.99 |
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 8873.42 |
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 10631.17 |
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 8978.21 |
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 10633.05 |
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 10633.21 |
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 8978.39 |
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 10631.36 |
SUPP HEATING COIL_UNITHEATEDBSMT | 6305.65 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:42:04
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 55.676 | 1.520 | 503.608 | 16.305 | 17.825 |
February | 77.340 | 3.581 | 426.859 | 16.480 | 20.061 |
March | 238.142 | 9.203 | 202.492 | 5.097 | 14.300 |
April | 346.304 | 14.246 | 133.185 | 2.088 | 16.334 |
May | 502.133 | 24.439 | 20.595 | 0.170 | 24.609 |
June | 680.795 | 39.127 | 0.000 | 0.000 | 39.127 |
July | 735.595 | 53.476 | 0.000 | 0.000 | 53.476 |
August | 739.771 | 50.495 | 0.000 | 0.000 | 50.495 |
September | 638.545 | 38.409 | 0.000 | 0.000 | 38.409 |
October | 380.858 | 15.359 | 113.469 | 1.595 | 16.953 |
November | 129.408 | 2.430 | 272.625 | 5.077 | 7.507 |
December | 45.008 | 1.038 | 528.208 | 22.751 | 23.789 |
Annual Sum or Average | 4569.577 | 253.322 | 2201.042 | 69.563 | 322.885 |
Minimum of Months | 45.008 | 1.038 | 0.000 | 0.000 | 7.507 |
Maximum of Months | 739.771 | 53.476 | 528.208 | 22.751 | 53.476 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 18.063 | 0.233 | 665.354 | 24.313 | 24.547 |
February | 38.175 | 0.927 | 584.125 | 22.926 | 23.853 |
March | 86.333 | 1.728 | 466.375 | 11.344 | 13.072 |
April | 114.946 | 2.442 | 343.167 | 7.183 | 9.625 |
May | 207.480 | 5.087 | 186.458 | 2.033 | 7.120 |
June | 406.020 | 11.458 | 12.375 | 0.044 | 11.502 |
July | 561.317 | 19.565 | 1.750 | 0.003 | 19.568 |
August | 539.647 | 18.776 | 0.000 | 0.000 | 18.776 |
September | 397.945 | 13.979 | 33.167 | 0.164 | 14.143 |
October | 180.409 | 4.083 | 293.771 | 5.455 | 9.538 |
November | 19.817 | 0.189 | 557.017 | 12.348 | 12.537 |
December | 8.958 | 0.122 | 675.675 | 26.952 | 27.074 |
Annual Sum or Average | 2579.109 | 78.590 | 3819.233 | 112.765 | 191.354 |
Minimum of Months | 8.958 | 0.122 | 0.000 | 0.000 | 7.120 |
Maximum of Months | 561.317 | 19.565 | 675.675 | 26.952 | 27.074 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 12.663 | 0.177 | 687.515 | 35.522 | 35.698 |
February | 36.235 | 1.098 | 596.167 | 32.701 | 33.799 |
March | 90.391 | 2.587 | 497.621 | 16.931 | 19.517 |
April | 136.841 | 3.905 | 361.117 | 10.853 | 14.758 |
May | 255.542 | 8.217 | 217.338 | 3.846 | 12.063 |
June | 424.111 | 17.991 | 46.042 | 0.378 | 18.369 |
July | 556.929 | 29.787 | 16.875 | 0.110 | 29.897 |
August | 533.240 | 26.859 | 6.375 | 0.030 | 26.889 |
September | 403.618 | 18.562 | 83.542 | 0.841 | 19.403 |
October | 166.579 | 4.975 | 376.708 | 9.829 | 14.803 |
November | 13.354 | 0.130 | 629.188 | 19.656 | 19.786 |
December | 7.125 | 0.093 | 698.146 | 39.098 | 39.191 |
Annual Sum or Average | 2636.629 | 114.381 | 4216.632 | 169.793 | 284.174 |
Minimum of Months | 7.125 | 0.093 | 6.375 | 0.030 | 12.063 |
Maximum of Months | 556.929 | 29.787 | 698.146 | 39.098 | 39.191 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.913 | 44.125 | 44.125 |
February | 11.479 | 0.179 | 620.429 | 39.324 | 39.503 |
March | 36.829 | 0.720 | 576.358 | 21.616 | 22.336 |
April | 99.614 | 3.610 | 431.017 | 13.131 | 16.741 |
May | 211.917 | 9.398 | 268.375 | 4.648 | 14.047 |
June | 378.781 | 19.323 | 50.876 | 0.413 | 19.736 |
July | 512.847 | 30.273 | 17.288 | 0.095 | 30.368 |
August | 472.973 | 24.859 | 8.000 | 0.039 | 24.898 |
September | 310.917 | 13.926 | 128.975 | 1.289 | 15.215 |
October | 79.812 | 1.910 | 481.492 | 12.819 | 14.729 |
November | 0.000 | 0.000 | 685.917 | 24.373 | 24.373 |
December | 0.000 | 0.000 | 730.875 | 49.095 | 49.095 |
Annual Sum or Average | 2115.169 | 104.199 | 4737.513 | 210.968 | 315.167 |
Minimum of Months | 0.000 | 0.000 | 8.000 | 0.039 | 14.047 |
Maximum of Months | 512.847 | 30.273 | 737.913 | 49.095 | 49.095 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 28.856 | 28.856 |
February | 0.000 | 0.000 | 636.188 | 25.808 | 25.808 |
March | 5.617 | 0.022 | 604.875 | 15.061 | 15.083 |
April | 60.229 | 1.166 | 450.517 | 9.448 | 10.614 |
May | 164.275 | 3.541 | 226.406 | 2.561 | 6.102 |
June | 388.297 | 10.402 | 13.417 | 0.053 | 10.455 |
July | 558.046 | 17.837 | 1.500 | 0.004 | 17.841 |
August | 524.025 | 14.849 | 0.000 | 0.000 | 14.849 |
September | 327.815 | 7.170 | 50.514 | 0.307 | 7.477 |
October | 53.517 | 0.632 | 461.321 | 8.169 | 8.801 |
November | 0.000 | 0.000 | 671.667 | 16.389 | 16.389 |
December | 0.000 | 0.000 | 730.250 | 29.390 | 29.390 |
Annual Sum or Average | 2081.821 | 55.619 | 4590.654 | 136.046 | 191.665 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.102 |
Maximum of Months | 558.046 | 17.837 | 744.000 | 29.390 | 29.390 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 40.977 | 40.977 |
February | 0.000 | 0.000 | 630.875 | 36.498 | 36.498 |
March | 26.864 | 0.234 | 589.890 | 20.315 | 20.549 |
April | 90.364 | 2.165 | 438.183 | 12.844 | 15.009 |
May | 230.002 | 6.592 | 231.346 | 4.240 | 10.832 |
June | 420.338 | 17.202 | 44.375 | 0.386 | 17.588 |
July | 558.224 | 28.555 | 16.500 | 0.110 | 28.665 |
August | 528.125 | 23.361 | 7.250 | 0.039 | 23.400 |
September | 375.753 | 11.831 | 93.250 | 1.035 | 12.866 |
October | 80.837 | 1.311 | 494.825 | 12.730 | 14.041 |
November | 0.000 | 0.000 | 700.750 | 23.878 | 23.878 |
December | 0.000 | 0.000 | 740.500 | 42.568 | 42.568 |
Annual Sum or Average | 2310.508 | 91.250 | 4731.744 | 195.621 | 286.871 |
Minimum of Months | 0.000 | 0.000 | 7.250 | 0.039 | 10.832 |
Maximum of Months | 558.224 | 28.555 | 744.000 | 42.568 | 42.568 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 16.583 | 0.375 | 671.146 | 33.933 | 34.308 |
February | 42.708 | 1.687 | 573.167 | 30.679 | 32.366 |
March | 108.729 | 3.721 | 469.708 | 15.238 | 18.959 |
April | 159.008 | 6.292 | 327.950 | 8.870 | 15.162 |
May | 269.901 | 12.313 | 193.107 | 2.617 | 14.929 |
June | 421.909 | 22.007 | 19.608 | 0.103 | 22.110 |
July | 551.505 | 33.659 | 2.625 | 0.008 | 33.667 |
August | 520.821 | 30.591 | 0.250 | 0.000 | 30.592 |
September | 390.429 | 22.050 | 60.098 | 0.435 | 22.485 |
October | 179.164 | 6.648 | 335.156 | 8.074 | 14.722 |
November | 22.558 | 0.377 | 582.000 | 17.269 | 17.646 |
December | 8.250 | 0.168 | 683.317 | 39.367 | 39.535 |
Annual Sum or Average | 2691.568 | 139.888 | 3918.133 | 156.593 | 296.481 |
Minimum of Months | 8.250 | 0.168 | 0.250 | 0.000 | 14.722 |
Maximum of Months | 551.505 | 33.659 | 683.317 | 39.367 | 39.535 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 19.792 | 0.226 | 649.687 | 20.235 | 20.461 |
February | 41.758 | 0.984 | 572.667 | 18.582 | 19.566 |
March | 94.567 | 1.906 | 431.292 | 8.887 | 10.793 |
April | 129.452 | 2.706 | 302.154 | 5.257 | 7.963 |
May | 238.331 | 5.551 | 139.435 | 1.162 | 6.714 |
June | 443.395 | 12.276 | 0.000 | 0.000 | 12.276 |
July | 605.137 | 20.407 | 0.000 | 0.000 | 20.407 |
August | 593.450 | 19.645 | 0.000 | 0.000 | 19.645 |
September | 437.043 | 14.453 | 14.271 | 0.058 | 14.510 |
October | 195.563 | 4.249 | 259.156 | 4.086 | 8.335 |
November | 19.542 | 0.192 | 523.121 | 9.742 | 9.934 |
December | 10.250 | 0.151 | 661.750 | 22.607 | 22.757 |
Annual Sum or Average | 2828.279 | 82.745 | 3553.533 | 90.616 | 173.360 |
Minimum of Months | 10.250 | 0.151 | 0.000 | 0.000 | 6.714 |
Maximum of Months | 605.137 | 20.407 | 661.750 | 22.607 | 22.757 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 12.917 | 0.158 | 678.976 | 31.525 | 31.683 |
February | 38.807 | 1.140 | 589.083 | 28.410 | 29.550 |
March | 97.507 | 2.778 | 478.521 | 14.216 | 16.994 |
April | 145.515 | 4.212 | 328.500 | 8.685 | 12.897 |
May | 277.404 | 8.805 | 179.917 | 2.566 | 11.370 |
June | 451.280 | 18.891 | 20.625 | 0.122 | 19.013 |
July | 585.306 | 30.687 | 5.250 | 0.023 | 30.710 |
August | 562.907 | 27.766 | 0.500 | 0.002 | 27.768 |
September | 422.416 | 19.074 | 53.271 | 0.427 | 19.501 |
October | 174.940 | 5.061 | 342.292 | 8.062 | 13.124 |
November | 15.004 | 0.125 | 607.442 | 16.767 | 16.892 |
December | 8.417 | 0.113 | 692.908 | 34.912 | 35.025 |
Annual Sum or Average | 2792.420 | 118.810 | 3977.285 | 145.717 | 264.527 |
Minimum of Months | 8.417 | 0.113 | 0.500 | 0.002 | 11.370 |
Maximum of Months | 585.306 | 30.687 | 692.908 | 34.912 | 35.025 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.971 | 39.337 | 39.337 |
February | 13.146 | 0.143 | 614.575 | 34.260 | 34.403 |
March | 44.396 | 0.743 | 555.658 | 18.383 | 19.126 |
April | 111.081 | 3.833 | 394.333 | 10.519 | 14.352 |
May | 233.775 | 9.921 | 225.813 | 3.157 | 13.079 |
June | 405.971 | 20.180 | 24.917 | 0.138 | 20.317 |
July | 545.031 | 31.170 | 5.083 | 0.015 | 31.185 |
August | 501.630 | 25.749 | 1.000 | 0.003 | 25.752 |
September | 331.005 | 14.354 | 95.006 | 0.741 | 15.095 |
October | 81.662 | 1.906 | 454.333 | 10.718 | 12.624 |
November | 0.000 | 0.000 | 672.667 | 21.134 | 21.134 |
December | 0.000 | 0.000 | 727.500 | 44.111 | 44.111 |
Annual Sum or Average | 2267.698 | 108.000 | 4508.856 | 182.515 | 290.515 |
Minimum of Months | 0.000 | 0.000 | 1.000 | 0.003 | 12.624 |
Maximum of Months | 545.031 | 31.170 | 737.971 | 44.111 | 44.111 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 738.750 | 25.425 | 25.425 |
February | 0.000 | 0.000 | 624.875 | 22.405 | 22.405 |
March | 9.983 | 0.052 | 563.025 | 12.195 | 12.246 |
April | 72.899 | 1.408 | 400.704 | 7.021 | 8.429 |
May | 197.257 | 4.112 | 159.982 | 1.429 | 5.541 |
June | 433.396 | 11.531 | 0.000 | 0.000 | 11.531 |
July | 605.484 | 19.184 | 0.000 | 0.000 | 19.184 |
August | 583.011 | 16.171 | 0.000 | 0.000 | 16.171 |
September | 368.764 | 7.908 | 25.316 | 0.117 | 8.025 |
October | 62.879 | 0.757 | 404.667 | 6.372 | 7.129 |
November | 0.000 | 0.000 | 638.125 | 13.423 | 13.423 |
December | 0.000 | 0.000 | 721.750 | 26.180 | 26.180 |
Annual Sum or Average | 2333.674 | 61.122 | 4277.194 | 114.566 | 175.689 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.541 |
Maximum of Months | 605.484 | 19.184 | 738.750 | 26.180 | 26.180 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 36.986 | 36.986 |
February | 0.000 | 0.000 | 626.875 | 32.320 | 32.320 |
March | 29.699 | 0.304 | 557.634 | 17.365 | 17.668 |
April | 103.315 | 2.459 | 401.750 | 10.353 | 12.813 |
May | 249.447 | 7.234 | 188.833 | 2.840 | 10.074 |
June | 447.996 | 18.217 | 19.167 | 0.121 | 18.338 |
July | 586.254 | 29.575 | 5.500 | 0.022 | 29.597 |
August | 559.401 | 24.463 | 0.750 | 0.003 | 24.466 |
September | 398.353 | 12.459 | 64.667 | 0.551 | 13.010 |
October | 82.641 | 1.423 | 470.917 | 10.759 | 12.182 |
November | 0.000 | 0.000 | 691.000 | 20.789 | 20.789 |
December | 0.000 | 0.000 | 735.750 | 38.531 | 38.531 |
Annual Sum or Average | 2457.106 | 96.134 | 4506.842 | 170.640 | 266.774 |
Minimum of Months | 0.000 | 0.000 | 0.750 | 0.003 | 10.074 |
Maximum of Months | 586.254 | 29.575 | 744.000 | 38.531 | 38.531 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 6.583 | 0.099 | 705.443 | 47.105 | 47.204 |
February | 32.167 | 1.104 | 596.667 | 42.614 | 43.717 |
March | 80.854 | 2.689 | 529.071 | 22.610 | 25.299 |
April | 127.634 | 5.281 | 408.062 | 13.934 | 19.215 |
May | 230.025 | 11.479 | 267.494 | 5.074 | 16.553 |
June | 384.623 | 21.723 | 60.054 | 0.469 | 22.192 |
July | 518.869 | 34.485 | 20.095 | 0.116 | 34.600 |
August | 484.269 | 30.517 | 6.875 | 0.026 | 30.543 |
September | 351.555 | 20.684 | 120.211 | 1.350 | 22.033 |
October | 144.458 | 5.084 | 424.792 | 13.052 | 18.136 |
November | 8.250 | 0.110 | 655.417 | 26.021 | 26.131 |
December | 5.500 | 0.065 | 713.333 | 52.899 | 52.963 |
Annual Sum or Average | 2374.787 | 133.318 | 4507.514 | 225.268 | 358.586 |
Minimum of Months | 5.500 | 0.065 | 6.875 | 0.026 | 16.553 |
Maximum of Months | 518.869 | 34.485 | 713.333 | 52.899 | 52.963 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.250 | 0.015 | 698.696 | 32.407 | 32.422 |
February | 32.167 | 0.604 | 599.542 | 29.736 | 30.340 |
March | 68.369 | 1.392 | 513.912 | 15.805 | 17.197 |
April | 100.113 | 2.501 | 403.121 | 9.986 | 12.486 |
May | 194.838 | 5.727 | 230.538 | 3.032 | 8.759 |
June | 398.695 | 13.215 | 23.815 | 0.082 | 13.297 |
July | 561.418 | 22.672 | 1.188 | 0.001 | 22.673 |
August | 533.893 | 21.050 | 0.000 | 0.000 | 21.050 |
September | 380.211 | 14.327 | 51.796 | 0.389 | 14.716 |
October | 140.835 | 3.201 | 361.479 | 8.141 | 11.342 |
November | 6.125 | 0.027 | 626.625 | 17.889 | 17.916 |
December | 7.250 | 0.050 | 707.213 | 34.802 | 34.851 |
Annual Sum or Average | 2426.164 | 84.781 | 4217.923 | 152.269 | 237.050 |
Minimum of Months | 2.250 | 0.015 | 0.000 | 0.000 | 8.759 |
Maximum of Months | 561.418 | 22.672 | 707.213 | 34.802 | 34.851 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 2.250 | 0.011 | 711.150 | 41.911 | 41.922 |
February | 29.542 | 0.679 | 607.250 | 37.926 | 38.605 |
March | 76.400 | 1.913 | 531.367 | 20.301 | 22.213 |
April | 119.080 | 3.496 | 407.796 | 12.832 | 16.328 |
May | 238.581 | 8.100 | 234.900 | 4.295 | 12.395 |
June | 425.069 | 18.597 | 44.000 | 0.345 | 18.942 |
July | 571.129 | 31.212 | 15.500 | 0.102 | 31.314 |
August | 543.894 | 27.554 | 4.250 | 0.019 | 27.573 |
September | 389.929 | 17.693 | 88.625 | 0.965 | 18.658 |
October | 132.184 | 3.816 | 410.446 | 12.110 | 15.926 |
November | 2.750 | 0.020 | 670.271 | 24.265 | 24.285 |
December | 3.875 | 0.022 | 716.708 | 44.933 | 44.955 |
Annual Sum or Average | 2534.683 | 113.113 | 4442.263 | 200.003 | 313.116 |
Minimum of Months | 2.250 | 0.011 | 4.250 | 0.019 | 12.395 |
Maximum of Months | 571.129 | 31.212 | 716.708 | 44.933 | 44.955 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 742.150 | 52.173 | 52.173 |
February | 8.188 | 0.074 | 626.542 | 45.831 | 45.905 |
March | 38.575 | 0.770 | 584.562 | 25.261 | 26.031 |
April | 101.629 | 4.038 | 443.862 | 15.200 | 19.238 |
May | 215.947 | 10.468 | 281.679 | 5.305 | 15.774 |
June | 381.690 | 21.174 | 59.481 | 0.456 | 21.630 |
July | 518.719 | 33.596 | 18.625 | 0.112 | 33.708 |
August | 472.835 | 27.918 | 6.875 | 0.030 | 27.948 |
September | 308.827 | 15.356 | 139.758 | 1.575 | 16.931 |
October | 69.104 | 1.883 | 503.875 | 15.550 | 17.433 |
November | 0.000 | 0.000 | 701.525 | 29.363 | 29.363 |
December | 0.000 | 0.000 | 736.500 | 57.092 | 57.092 |
Annual Sum or Average | 2115.513 | 115.278 | 4845.434 | 247.948 | 363.226 |
Minimum of Months | 0.000 | 0.000 | 6.875 | 0.030 | 15.774 |
Maximum of Months | 518.719 | 33.596 | 742.150 | 57.092 | 57.092 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 36.907 | 36.907 |
February | 0.000 | 0.000 | 640.625 | 32.680 | 32.680 |
March | 15.136 | 0.138 | 612.146 | 18.879 | 19.017 |
April | 70.711 | 1.729 | 466.617 | 11.566 | 13.296 |
May | 176.665 | 5.004 | 249.775 | 3.283 | 8.288 |
June | 394.030 | 12.939 | 22.136 | 0.069 | 13.008 |
July | 562.885 | 22.089 | 0.000 | 0.000 | 22.089 |
August | 526.095 | 18.723 | 0.000 | 0.000 | 18.723 |
September | 327.683 | 9.181 | 68.887 | 0.511 | 9.692 |
October | 55.637 | 0.827 | 505.842 | 10.926 | 11.753 |
November | 0.000 | 0.000 | 690.563 | 21.342 | 21.342 |
December | 0.000 | 0.000 | 733.250 | 37.671 | 37.671 |
Annual Sum or Average | 2128.842 | 70.630 | 4733.840 | 173.836 | 244.466 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.288 |
Maximum of Months | 562.885 | 22.089 | 744.000 | 37.671 | 37.671 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 45.241 | 45.241 |
February | 0.000 | 0.000 | 640.688 | 39.552 | 39.552 |
March | 25.525 | 0.339 | 614.750 | 22.887 | 23.226 |
April | 92.140 | 2.566 | 451.619 | 14.271 | 16.836 |
May | 225.822 | 7.359 | 245.801 | 4.541 | 11.900 |
June | 422.759 | 18.360 | 41.804 | 0.338 | 18.698 |
July | 572.416 | 30.469 | 14.750 | 0.099 | 30.568 |
August | 541.646 | 25.519 | 4.375 | 0.022 | 25.541 |
September | 363.935 | 12.678 | 94.125 | 1.094 | 13.772 |
October | 70.987 | 1.307 | 528.404 | 14.911 | 16.218 |
November | 0.000 | 0.000 | 709.083 | 27.631 | 27.631 |
December | 0.000 | 0.000 | 744.000 | 46.179 | 46.179 |
Annual Sum or Average | 2315.231 | 98.596 | 4833.399 | 216.765 | 315.361 |
Minimum of Months | 0.000 | 0.000 | 4.375 | 0.022 | 11.900 |
Maximum of Months | 572.416 | 30.469 | 744.000 | 46.179 | 46.179 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.875 | 20.232 | 20.232 |
February | 0.000 | 0.000 | 671.667 | 18.037 | 18.037 |
March | 0.000 | 0.000 | 744.000 | 18.522 | 18.522 |
April | 0.000 | 0.000 | 720.000 | 15.668 | 15.668 |
May | 0.000 | 0.000 | 125.750 | 0.387 | 0.387 |
June | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 92.583 | 0.331 | 0.000 | 0.000 | 0.331 |
August | 27.431 | 0.038 | 0.000 | 0.000 | 0.038 |
September | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 260.667 | 0.965 | 0.965 |
November | 0.000 | 0.000 | 720.000 | 18.094 | 18.094 |
December | 0.000 | 0.000 | 743.250 | 20.185 | 20.185 |
Annual Sum or Average | 120.014 | 0.369 | 4729.208 | 112.089 | 112.458 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 92.583 | 0.331 | 744.000 | 20.232 | 20.232 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 899.38 | 0.00 | 0.00 |
February | 990.38 | 0.00 | 0.00 |
March | 283.57 | 0.00 | 0.00 |
April | 129.78 | 0.00 | 0.00 |
May | 11.05 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 97.29 | 0.00 | 0.00 |
November | 317.28 | 0.00 | 0.00 |
December | 1171.73 | 0.00 | 0.00 |
Annual Sum or Average | 321.91 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1171.73 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 1705.77 | 0.00 | 0.00 |
February | 1747.42 | 0.00 | 0.00 |
March | 838.54 | 0.00 | 0.00 |
April | 578.06 | 0.00 | 0.00 |
May | 177.68 | 0.00 | 0.00 |
June | 4.10 | 0.00 | 0.00 |
July | 0.27 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 15.33 | 0.00 | 0.00 |
October | 429.45 | 0.00 | 0.00 |
November | 1006.96 | 0.00 | 0.00 |
December | 1816.46 | 0.00 | 0.00 |
Annual Sum or Average | 687.87 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1816.46 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2402.72 | 0.00 | 0.00 |
February | 2406.33 | 0.00 | 0.00 |
March | 1209.37 | 0.00 | 0.00 |
April | 826.83 | 0.00 | 0.00 |
May | 321.64 | 0.00 | 0.00 |
June | 34.60 | 0.00 | 0.00 |
July | 9.88 | 0.00 | 0.00 |
August | 2.72 | 0.00 | 0.00 |
September | 77.15 | 0.00 | 0.00 |
October | 754.09 | 0.00 | 0.00 |
November | 1554.82 | 0.00 | 0.00 |
December | 2555.03 | 0.00 | 0.00 |
Annual Sum or Average | 1005.75 | 0.00 | 0.00 |
Minimum of Months | 2.72 | 0.00 | 0.00 |
Maximum of Months | 2555.03 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2792.24 | 0.00 | 0.00 |
February | 2695.14 | 0.00 | 0.00 |
March | 1468.10 | 0.00 | 0.00 |
April | 965.83 | 0.00 | 0.00 |
May | 372.99 | 0.00 | 0.00 |
June | 36.11 | 0.00 | 0.00 |
July | 8.22 | 0.00 | 0.00 |
August | 3.30 | 0.00 | 0.00 |
September | 114.20 | 0.00 | 0.00 |
October | 950.92 | 0.00 | 0.00 |
November | 1826.83 | 0.00 | 0.00 |
December | 2974.41 | 0.00 | 0.00 |
Annual Sum or Average | 1176.52 | 0.00 | 0.00 |
Minimum of Months | 3.30 | 0.00 | 0.00 |
Maximum of Months | 2974.41 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 1989.87 | 0.00 | 0.00 |
February | 1933.59 | 0.00 | 0.00 |
March | 1101.31 | 0.00 | 0.00 |
April | 741.48 | 0.00 | 0.00 |
May | 213.93 | 0.00 | 0.00 |
June | 4.61 | 0.00 | 0.00 |
July | 0.30 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 27.58 | 0.00 | 0.00 |
October | 634.85 | 0.00 | 0.00 |
November | 1309.40 | 0.00 | 0.00 |
December | 1957.57 | 0.00 | 0.00 |
Annual Sum or Average | 820.45 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1989.87 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2707.63 | 0.00 | 0.00 |
February | 2618.10 | 0.00 | 0.00 |
March | 1411.92 | 0.00 | 0.00 |
April | 950.10 | 0.00 | 0.00 |
May | 338.65 | 0.00 | 0.00 |
June | 33.51 | 0.00 | 0.00 |
July | 9.38 | 0.00 | 0.00 |
August | 3.33 | 0.00 | 0.00 |
September | 90.46 | 0.00 | 0.00 |
October | 954.87 | 0.00 | 0.00 |
November | 1840.30 | 0.00 | 0.00 |
December | 2725.96 | 0.00 | 0.00 |
Annual Sum or Average | 1132.72 | 0.00 | 0.00 |
Minimum of Months | 3.33 | 0.00 | 0.00 |
Maximum of Months | 2725.96 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2088.78 | 0.00 | 0.00 |
February | 2037.20 | 0.00 | 0.00 |
March | 996.58 | 0.00 | 0.00 |
April | 637.30 | 0.00 | 0.00 |
May | 205.93 | 0.00 | 0.00 |
June | 8.82 | 0.00 | 0.00 |
July | 0.64 | 0.00 | 0.00 |
August | 0.01 | 0.00 | 0.00 |
September | 37.73 | 0.00 | 0.00 |
October | 574.58 | 0.00 | 0.00 |
November | 1250.92 | 0.00 | 0.00 |
December | 2297.75 | 0.00 | 0.00 |
Annual Sum or Average | 838.84 | 0.00 | 0.00 |
Minimum of Months | 0.01 | 0.00 | 0.00 |
Maximum of Months | 2297.75 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 1405.38 | 0.00 | 0.00 |
February | 1396.32 | 0.00 | 0.00 |
March | 652.14 | 0.00 | 0.00 |
April | 422.90 | 0.00 | 0.00 |
May | 101.60 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 5.47 | 0.00 | 0.00 |
October | 321.69 | 0.00 | 0.00 |
November | 787.45 | 0.00 | 0.00 |
December | 1494.02 | 0.00 | 0.00 |
Annual Sum or Average | 544.63 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1494.02 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2107.51 | 0.00 | 0.00 |
February | 2059.53 | 0.00 | 0.00 |
March | 1002.75 | 0.00 | 0.00 |
April | 653.51 | 0.00 | 0.00 |
May | 211.62 | 0.00 | 0.00 |
June | 10.94 | 0.00 | 0.00 |
July | 1.99 | 0.00 | 0.00 |
August | 0.13 | 0.00 | 0.00 |
September | 38.90 | 0.00 | 0.00 |
October | 612.24 | 0.00 | 0.00 |
November | 1310.37 | 0.00 | 0.00 |
December | 2240.56 | 0.00 | 0.00 |
Annual Sum or Average | 848.11 | 0.00 | 0.00 |
Minimum of Months | 0.13 | 0.00 | 0.00 |
Maximum of Months | 2240.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2468.27 | 0.00 | 0.00 |
February | 2323.20 | 0.00 | 0.00 |
March | 1239.51 | 0.00 | 0.00 |
April | 770.64 | 0.00 | 0.00 |
May | 252.07 | 0.00 | 0.00 |
June | 11.92 | 0.00 | 0.00 |
July | 1.24 | 0.00 | 0.00 |
August | 0.21 | 0.00 | 0.00 |
September | 65.84 | 0.00 | 0.00 |
October | 790.81 | 0.00 | 0.00 |
November | 1569.96 | 0.00 | 0.00 |
December | 2633.84 | 0.00 | 0.00 |
Annual Sum or Average | 1004.29 | 0.00 | 0.00 |
Minimum of Months | 0.21 | 0.00 | 0.00 |
Maximum of Months | 2633.84 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 1712.81 | 0.00 | 0.00 |
February | 1636.74 | 0.00 | 0.00 |
March | 872.70 | 0.00 | 0.00 |
April | 542.15 | 0.00 | 0.00 |
May | 117.94 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 10.58 | 0.00 | 0.00 |
October | 487.98 | 0.00 | 0.00 |
November | 1050.59 | 0.00 | 0.00 |
December | 1689.73 | 0.00 | 0.00 |
Annual Sum or Average | 671.90 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1712.81 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2417.03 | 0.00 | 0.00 |
February | 2287.48 | 0.00 | 0.00 |
March | 1189.37 | 0.00 | 0.00 |
April | 753.64 | 0.00 | 0.00 |
May | 223.60 | 0.00 | 0.00 |
June | 10.27 | 0.00 | 0.00 |
July | 1.81 | 0.00 | 0.00 |
August | 0.22 | 0.00 | 0.00 |
September | 47.76 | 0.00 | 0.00 |
October | 798.28 | 0.00 | 0.00 |
November | 1584.09 | 0.00 | 0.00 |
December | 2428.68 | 0.00 | 0.00 |
Annual Sum or Average | 971.92 | 0.00 | 0.00 |
Minimum of Months | 0.22 | 0.00 | 0.00 |
Maximum of Months | 2428.68 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2971.83 | 0.00 | 0.00 |
February | 2911.66 | 0.00 | 0.00 |
March | 1529.77 | 0.00 | 0.00 |
April | 1031.85 | 0.00 | 0.00 |
May | 413.23 | 0.00 | 0.00 |
June | 42.36 | 0.00 | 0.00 |
July | 10.27 | 0.00 | 0.00 |
August | 2.25 | 0.00 | 0.00 |
September | 121.30 | 0.00 | 0.00 |
October | 962.94 | 0.00 | 0.00 |
November | 1946.00 | 0.00 | 0.00 |
December | 3196.14 | 0.00 | 0.00 |
Annual Sum or Average | 1253.29 | 0.00 | 0.00 |
Minimum of Months | 2.25 | 0.00 | 0.00 |
Maximum of Months | 3196.14 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2161.27 | 0.00 | 0.00 |
February | 2154.63 | 0.00 | 0.00 |
March | 1120.11 | 0.00 | 0.00 |
April | 770.89 | 0.00 | 0.00 |
May | 255.20 | 0.00 | 0.00 |
June | 7.57 | 0.00 | 0.00 |
July | 0.06 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 35.57 | 0.00 | 0.00 |
October | 617.80 | 0.00 | 0.00 |
November | 1391.66 | 0.00 | 0.00 |
December | 2237.95 | 0.00 | 0.00 |
Annual Sum or Average | 889.49 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2237.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2903.42 | 0.00 | 0.00 |
February | 2855.52 | 0.00 | 0.00 |
March | 1484.61 | 0.00 | 0.00 |
April | 1003.50 | 0.00 | 0.00 |
May | 366.16 | 0.00 | 0.00 |
June | 32.17 | 0.00 | 0.00 |
July | 9.38 | 0.00 | 0.00 |
August | 1.69 | 0.00 | 0.00 |
September | 90.22 | 0.00 | 0.00 |
October | 955.16 | 0.00 | 0.00 |
November | 1966.91 | 0.00 | 0.00 |
December | 3016.02 | 0.00 | 0.00 |
Annual Sum or Average | 1215.26 | 0.00 | 0.00 |
Minimum of Months | 1.69 | 0.00 | 0.00 |
Maximum of Months | 3016.02 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 3337.98 | 0.00 | 0.00 |
February | 3174.55 | 0.00 | 0.00 |
March | 1740.01 | 0.00 | 0.00 |
April | 1138.52 | 0.00 | 0.00 |
May | 434.10 | 0.00 | 0.00 |
June | 41.21 | 0.00 | 0.00 |
July | 9.93 | 0.00 | 0.00 |
August | 2.55 | 0.00 | 0.00 |
September | 143.15 | 0.00 | 0.00 |
October | 1175.54 | 0.00 | 0.00 |
November | 2227.18 | 0.00 | 0.00 |
December | 3499.79 | 0.00 | 0.00 |
Annual Sum or Average | 1401.60 | 0.00 | 0.00 |
Minimum of Months | 2.55 | 0.00 | 0.00 |
Maximum of Months | 3499.79 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 2489.38 | 0.00 | 0.00 |
February | 2392.46 | 0.00 | 0.00 |
March | 1357.86 | 0.00 | 0.00 |
April | 899.16 | 0.00 | 0.00 |
May | 274.96 | 0.00 | 0.00 |
June | 6.29 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 46.84 | 0.00 | 0.00 |
October | 848.19 | 0.00 | 0.00 |
November | 1677.22 | 0.00 | 0.00 |
December | 2450.73 | 0.00 | 0.00 |
Annual Sum or Average | 1029.94 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2489.38 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 3147.94 | 0.00 | 0.00 |
February | 2979.89 | 0.00 | 0.00 |
March | 1672.03 | 0.00 | 0.00 |
April | 1110.84 | 0.00 | 0.00 |
May | 379.73 | 0.00 | 0.00 |
June | 30.67 | 0.00 | 0.00 |
July | 8.91 | 0.00 | 0.00 |
August | 1.88 | 0.00 | 0.00 |
September | 100.02 | 0.00 | 0.00 |
October | 1181.17 | 0.00 | 0.00 |
November | 2237.45 | 0.00 | 0.00 |
December | 3117.96 | 0.00 | 0.00 |
Annual Sum or Average | 1322.21 | 0.00 | 0.00 |
Minimum of Months | 1.88 | 0.00 | 0.00 |
Maximum of Months | 3147.94 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN DX HEATING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 1910.31 | 0.00 | 0.00 |
February | 1881.86 | 0.00 | 0.00 |
March | 1989.35 | 0.00 | 0.00 |
April | 1809.33 | 0.00 | 0.00 |
May | 40.17 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 89.91 | 0.00 | 0.00 |
November | 2031.15 | 0.00 | 0.00 |
December | 1889.16 | 0.00 | 0.00 |
Annual Sum or Average | 962.72 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2031.15 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 13.22 | 0.00 |
February | 0.00 | 28.72 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 143.71 | 0.00 |
Annual Sum or Average | 0.00 | 15.53 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 143.71 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 27.58 | 0.00 |
February | 0.00 | 43.09 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 196.69 | 0.00 |
Annual Sum or Average | 0.00 | 22.35 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 196.69 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6.32 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 112.46 | 0.00 |
Annual Sum or Average | 0.00 | 10.04 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 112.46 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 121.11 | 0.00 |
February | 0.00 | 154.94 | 0.00 |
March | 0.00 | 10.60 | 0.00 |
April | 0.00 | 0.40 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 2.05 | 0.00 |
December | 0.00 | 384.34 | 0.00 |
Annual Sum or Average | 0.00 | 55.92 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 384.34 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 104.35 | 0.00 |
February | 0.00 | 116.76 | 0.00 |
March | 0.00 | 6.36 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 1.67 | 0.00 |
December | 0.00 | 393.34 | 0.00 |
Annual Sum or Average | 0.00 | 51.90 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 393.34 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 33.59 | 0.00 |
Annual Sum or Average | 0.00 | 2.85 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 33.59 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2.01 | 0.00 |
February | 0.00 | 11.06 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 91.78 | 0.00 |
Annual Sum or Average | 0.00 | 8.81 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 91.78 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 9.08 | 0.00 |
February | 0.00 | 21.62 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 135.77 | 0.00 |
Annual Sum or Average | 0.00 | 13.96 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 135.77 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 1.79 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 69.39 | 0.00 |
Annual Sum or Average | 0.00 | 6.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 69.39 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 54.50 | 0.00 |
February | 0.00 | 53.32 | 0.00 |
March | 0.00 | 0.62 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 248.54 | 0.00 |
Annual Sum or Average | 0.00 | 29.88 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 248.54 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 67.94 | 0.00 |
February | 0.00 | 67.27 | 0.00 |
March | 0.00 | 1.74 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.02 | 0.00 |
December | 0.00 | 302.40 | 0.00 |
Annual Sum or Average | 0.00 | 36.76 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 302.40 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 6.90 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 114.36 | 0.00 |
Annual Sum or Average | 0.00 | 10.24 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 114.36 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 75.92 | 0.00 |
February | 0.00 | 94.08 | 0.00 |
March | 0.00 | 1.15 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 278.92 | 0.00 |
Annual Sum or Average | 0.00 | 37.45 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 278.92 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 90.64 | 0.00 |
February | 0.00 | 101.51 | 0.00 |
March | 0.00 | 2.06 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.24 | 0.00 |
December | 0.00 | 337.97 | 0.00 |
Annual Sum or Average | 0.00 | 44.38 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 337.97 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 11.88 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 157.05 | 0.00 |
Annual Sum or Average | 0.00 | 14.25 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 157.05 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 130.36 | 0.00 |
February | 0.00 | 146.88 | 0.00 |
March | 0.00 | 6.83 | 0.00 |
April | 0.00 | 0.13 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 1.66 | 0.00 |
December | 0.00 | 423.76 | 0.00 |
Annual Sum or Average | 0.00 | 59.06 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 423.76 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 226.51 | 0.00 |
February | 0.00 | 258.08 | 0.00 |
March | 0.00 | 22.46 | 0.00 |
April | 0.00 | 1.47 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 10.91 | 0.00 |
December | 0.00 | 595.87 | 0.00 |
Annual Sum or Average | 0.00 | 92.57 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 595.87 | 0.00 |
Report: COILLOADS
For: SUPP HEATING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 1174.57 | 0.00 |
February | 0.00 | 1121.19 | 0.00 |
March | 0.00 | 337.82 | 0.00 |
April | 0.00 | 125.45 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 230.10 | 0.00 |
December | 0.00 | 1167.41 | 0.00 |
Annual Sum or Average | 0.00 | 342.83 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 1174.57 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.01 |
February | 0.00 | 0.00 | 0.03 |
March | 0.00 | 0.00 | 0.06 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.17 |
June | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.37 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.11 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.15 |
Minimum of Months | 0.00 | 0.00 | 0.01 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.16 |
August | 0.00 | 0.00 | 0.15 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.08 |
July | 0.00 | 0.00 | 0.14 |
August | 0.00 | 0.00 | 0.11 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.14 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.13 |
July | 0.00 | 0.00 | 0.21 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.21 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.05 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.23 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.03 |
June | 0.00 | 0.00 | 0.09 |
July | 0.00 | 0.00 | 0.15 |
August | 0.00 | 0.00 | 0.12 |
September | 0.00 | 0.00 | 0.06 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.15 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.22 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.16 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.05 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.15 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.20 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.01 |
May | 0.00 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.10 |
July | 0.00 | 0.00 | 0.17 |
August | 0.00 | 0.00 | 0.14 |
September | 0.00 | 0.00 | 0.07 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.04 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.02 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.14 |
July | 0.00 | 0.00 | 0.24 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:42:04
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1191.13 | 886.83 |
February | 0.00 | 0.00 | 1206.14 | 811.10 |
March | 0.00 | 0.00 | 1180.90 | 879.22 |
April | 0.00 | 0.00 | 1132.42 | 815.92 |
May | 0.00 | 0.00 | 1058.99 | 788.45 |
June | 0.00 | 0.00 | 991.95 | 714.71 |
July | 0.00 | 0.00 | 945.04 | 703.61 |
August | 0.00 | 0.00 | 927.84 | 690.80 |
September | 0.00 | 0.00 | 951.58 | 685.62 |
October | 0.00 | 0.00 | 1006.59 | 749.44 |
November | 0.00 | 0.00 | 1076.96 | 775.96 |
December | 0.00 | 0.00 | 1146.94 | 853.93 |
Annual Sum or Average | 0.00 | 0.00 | 1067.23 | 9355.58 |
Minimum of Months | 0.00 | 0.00 | 927.84 | 685.62 |
Maximum of Months | 0.00 | 0.00 | 1206.14 | 886.83 |