Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:43
Tabular Output Report in Format: HTML
Building: MF+CZ5AWH+USA_IL_Chicago-OHare.Intl.AP.725300+oilfurnace+heatedbsmt+IECC_2009
Environment: ANNUAL ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Simulation Timestamp: 2019-02-14 08:43:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1257159.25 | 32.23 | 42.75 |
Net Site Energy | 1257159.25 | 32.23 | 42.75 |
Total Source Energy | 2296008.38 | 58.86 | 78.08 |
Net Source Energy | 2296008.38 | 58.86 | 78.08 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 29404.35 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 484906.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 57841.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28536.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 324222.13 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 448030.60 | 809128.65 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | Boiler | 0.00 | 484906.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 57841.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28536.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 324222.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.94 | 27.52 | 0.00 | 0.00 | 0.00 | 14.27 |
Other | 10.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 15.24 | 27.52 | 0.00 | 0.00 | 0.00 | 14.27 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.21 | 20.74 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 11.49 | 20.74 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 448030.603 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 448030.603 | 100.00 |
Total On-Site and Utility Electric Sources | 448030.603 | 100.00 |
Total Electricity End Uses | 448030.603 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 1331.75 |
Time Setpoint Not Met During Occupied Cooling | 24.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2122.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |COILLOADS
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:43 |
RunPeriod | ANNUAL |
Weather File | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Latitude [deg] | 41.98 |
Longitude [deg] | -87.9 |
Elevation [ft] | 659.48 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Above Ground Wall Area [ft2] | 15481.63 | 6175.53 | 1565.28 | 6175.53 | 1565.28 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Above Ground Window-Wall Ratio [%] | 13.74 | 8.61 | 33.97 | 8.61 | 33.97 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
HEATEDBSMT | 7794.39 | Yes | Yes | 58419.71 | 1.00 | 185.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 325507.37 | 16363.00 | 0.00 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 29404.35 | 242159.09 | 15481.63 | 0.00 | 2126.74 | 2126.74 | 0.5522 | 816.79 | 2.1381 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 16-JUL-18:15 | 27-JAN-06:30 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 363.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 50.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 52.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 10.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 115.49 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 131.27 | 479.30 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | Boiler | 0.00 | 363.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 50.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 14.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 2.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 6.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 10.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 115.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 525638.66 | 0.00 | 0.00 | 0.00 |
Cooling | 183184.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 90373.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 351456.79 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1418912.92 | 877095.46 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
Cooling | 6.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 48.26 | 29.83 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
Cooling | 6.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 5.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 32.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 11.95 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 48.26 | 29.83 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -4.0 | 0.00 | -4.0 | Wetbulb [F] | 964.61 | 270.00 |
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 91.94 | 18.90 | 74.66 | Wetbulb [F] | 1023.67 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.087 | 0.094 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
CENTRAL BOILER | Boiler:HotWater | 418355.71 | 0.80 |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 24754.59 | 19039.79 | 5714.80 | 0.77 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9542.52 | 6546.34 | 2996.17 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10523.27 | 7564.06 | 2959.21 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14329.08 | 10414.96 | 3914.12 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9486.81 | 6522.41 | 2964.40 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10525.63 | 7564.65 | 2960.97 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13814.79 | 10172.29 | 3642.50 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7848.78 | 5471.43 | 2377.35 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9702.35 | 7018.91 | 2683.44 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13410.88 | 9851.30 | 3559.59 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7643.21 | 5305.49 | 2337.72 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9683.37 | 7004.69 | 2678.68 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15719.85 | 11564.82 | 4155.03 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10323.63 | 7257.70 | 3065.93 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12590.30 | 8831.49 | 3758.81 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15647.18 | 11505.14 | 4142.04 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10266.17 | 7232.93 | 3033.23 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12689.16 | 8873.84 | 3815.32 | 0.70 | 3.97 | |||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed | 3882.64 | 2624.99 | 1257.65 | 0.68 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.0 | 3.25 | 11.07 | 11.74 | 11.36 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.8 | 3.40 | 11.61 | 12.33 | 12.25 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.34 | 11.40 | 12.09 | 11.89 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.32 | 11.34 | 12.03 | 11.80 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.8 | 3.40 | 11.60 | 12.32 | 12.24 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.34 | 11.40 | 12.09 | 11.89 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.31 | 11.28 | 11.96 | 11.70 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.38 | 11.54 | 12.25 | 12.13 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.33 | 11.37 | 12.06 | 11.84 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.31 | 11.29 | 11.98 | 11.72 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.39 | 11.56 | 12.27 | 12.16 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.33 | 11.37 | 12.06 | 11.84 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.31 | 11.29 | 11.97 | 11.71 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.37 | 11.50 | 12.20 | 12.06 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.37 | 11.51 | 12.22 | 12.08 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.31 | 11.29 | 11.97 | 11.71 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.37 | 11.49 | 12.19 | 12.04 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.38 | 11.52 | 12.23 | 12.10 | |
DX COOLING COIL_UNITHEATEDBSMT | 0.3 | 3.42 | 11.68 | 12.40 | 12.37 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNITHEATEDBSMT | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 48776.70 | 51648.40 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 16745.30 | 16300.41 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 19956.52 | 19864.17 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 26489.23 | 27083.62 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 16745.73 | 16300.89 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 19954.23 | 19861.64 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 26372.50 | 26952.91 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 14882.60 | 14221.41 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 18921.93 | 18715.81 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 25579.87 | 26078.49 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 14465.35 | 13753.68 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 18889.33 | 18679.65 | - |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 29459.47 | 30355.61 | - |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 18767.12 | 18545.65 | - |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 21988.38 | 22111.55 | - |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 29306.45 | 30187.01 | - |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 18767.13 | 18545.67 | - |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 21986.96 | 22109.98 | - |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | Coil:Heating:Water | 8747.24 | 7239.29 | - |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 854.03 | 427.69 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 248.29 | 124.34 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 308.99 | 154.74 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 432.51 | 216.60 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 248.29 | 124.34 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 308.95 | 154.72 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 430.36 | 215.52 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 213.09 | 106.72 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 289.47 | 144.97 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 415.37 | 208.02 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 205.20 | 102.77 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 288.86 | 144.66 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 488.67 | 244.72 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 286.51 | 143.49 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 347.41 | 173.98 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 485.77 | 243.27 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 286.52 | 143.49 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 347.38 | 173.97 | 0.50 | 1.00 | General |
SUPPLY FAN_UNITHEATEDBSMT | Fan:OnOff | 0.38 | 0.06 | 97.09 | 48.62 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 42.068888 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 5.35 | 36002.06 | 0.80 | 1.08 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 19588.41 | 19588.41 | 16.32 | 854.027 | 854.027 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00875 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5041.92 | 5041.92 | 4.20 | 219.811 | 219.811 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.01024 | 86.70 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6932.65 | 6932.65 | 5.77 | 302.236 | 302.236 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 74.98 | 74.98 | 0.00975 | 82.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9920.36 | 9920.36 | 8.26 | 432.508 | 432.508 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00935 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4827.19 | 4827.19 | 4.02 | 210.446 | 210.446 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01036 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6912.78 | 6912.78 | 5.76 | 301.369 | 301.369 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 74.98 | 74.98 | 0.00975 | 82.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9871.55 | 9871.55 | 8.22 | 430.363 | 430.363 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00906 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4888.06 | 4888.06 | 4.07 | 213.095 | 213.095 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00990 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6640.05 | 6640.05 | 5.53 | 289.472 | 289.472 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 74.98 | 74.98 | 0.00945 | 83.15 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9527.74 | 9527.74 | 7.94 | 415.375 | 415.375 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00911 | 87.88 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4707.06 | 4707.06 | 3.92 | 205.204 | 205.204 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00997 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6625.92 | 6625.92 | 5.52 | 288.856 | 288.856 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 74.98 | 74.98 | 0.00945 | 83.15 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7154.11 | 7154.11 | 5.96 | 311.941 | 311.941 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00967 | 91.37 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7375.94 | 7375.94 | 6.14 | 321.614 | 321.614 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00963 | 91.37 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11208.45 | 11208.45 | 9.34 | 488.667 | 488.667 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00923 | 87.88 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6225.77 | 6225.77 | 5.19 | 271.421 | 271.421 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00996 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6222.78 | 6222.78 | 5.18 | 271.292 | 271.292 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00994 | 85.28 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11142.08 | 11142.08 | 9.28 | 485.774 | 485.774 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00924 | 87.88 | 0.01496 | 44.995 | 0.00 |
HEATEDBSMT | 451.06 | 451.06 | 0.06 | 19.662 | 44.995 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01046 | 84.57 | 0.01496 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 6646.69 | 6646.69 | 5.54 | 123.859 | 123.859 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00436 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13325.59 | 13325.59 | 11.10 | 248.286 | 248.286 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00567 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16584.35 | 16584.35 | 13.81 | 308.993 | 308.993 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00588 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 16607.10 | 16607.10 | 13.83 | 309.417 | 309.417 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00588 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13326.02 | 13326.02 | 11.10 | 248.294 | 248.294 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00567 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16582.03 | 16582.03 | 13.81 | 308.950 | 308.950 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00588 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13135.71 | 13135.71 | 10.94 | 244.779 | 244.779 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00619 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9833.61 | 9833.61 | 8.19 | 183.253 | 183.253 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00598 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13108.26 | 13108.26 | 10.92 | 244.268 | 244.268 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00619 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13138.86 | 13138.86 | 10.94 | 244.838 | 244.838 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00619 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9833.69 | 9833.69 | 8.19 | 183.255 | 183.255 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00598 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13106.20 | 13106.20 | 10.92 | 244.230 | 244.230 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00619 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 18644.80 | 18644.80 | 15.53 | 347.384 | 347.384 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 18646.24 | 18646.24 | 15.53 | 347.411 | 347.411 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 18678.94 | 18678.94 | 15.56 | 348.020 | 348.020 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 15377.29 | 15377.29 | 12.81 | 286.515 | 286.515 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00589 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 15377.28 | 15377.28 | 12.81 | 286.515 | 286.515 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00589 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 18680.50 | 18680.50 | 15.56 | 348.049 | 348.049 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
HEATEDBSMT | 5208.15 | 5208.15 | 0.67 | 97.086 | 97.086 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 17:15:00 | 72.00 | 72.00 | 0.00800 | -4.0 | 0.00065 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 | 854.03 | 123.86 | 123.86 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 219.81 | 219.81 | 248.29 | 248.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 302.24 | 302.24 | 308.99 | 308.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 | 432.51 | 309.42 | 309.42 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 210.45 | 210.45 | 248.29 | 248.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 301.37 | 301.37 | 308.95 | 308.95 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 | 430.36 | 244.78 | 244.78 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 | 213.09 | 183.25 | 183.25 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 | 289.47 | 244.27 | 244.27 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 | 415.37 | 244.84 | 244.84 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 | 205.20 | 183.25 | 183.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 | 288.86 | 244.23 | 244.23 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.67 | 488.67 | 348.02 | 348.02 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.29 | 271.29 | 286.51 | 286.51 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.61 | 321.61 | 347.41 | 347.41 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.77 | 485.77 | 348.05 | 348.05 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.42 | 271.42 | 286.52 | 286.52 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.94 | 311.94 | 347.38 | 347.38 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.99 | 97.09 | 97.09 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1753.75 | 5605.00 | 365.25 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 3136.50 | 6139.75 | 1508.50 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2846.75 | 6072.50 | 988.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2910.00 | 6433.75 | 1232.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2218.25 | 6423.00 | 717.50 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2841.50 | 6254.50 | 1121.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2795.00 | 5816.75 | 749.25 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2207.75 | 5689.75 | 342.50 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2756.25 | 5722.75 | 699.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2909.25 | 6084.00 | 1000.25 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2156.00 | 5949.75 | 385.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2819.50 | 5897.75 | 876.50 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3349.00 | 6162.25 | 1481.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3154.25 | 6046.75 | 1197.25 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3220.75 | 6268.75 | 1365.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2741.50 | 6375.75 | 1092.75 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2595.50 | 6216.50 | 884.50 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3391.00 | 6419.50 | 1620.50 |
HEATEDBSMT | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 4095.50 | 6857.00 | 2122.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 3.00 | 0.00 | 3.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 784.50 | 0.00 | 784.50 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 78.75 | 23.25 | 78.75 | 23.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 166.00 | 0.00 | 166.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 34.75 | 0.00 | 34.75 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 40.50 | 6.00 | 40.50 | 6.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15.00 | 0.00 | 15.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15.50 | 0.00 | 15.50 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 84.50 | 9.75 | 84.50 | 9.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 185.50 | 0.00 | 185.50 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 25.75 | 0.00 | 25.75 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 46.00 | 2.25 | 46.00 | 2.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 31.25 | 0.00 | 31.25 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 40.50 | 1.75 | 40.50 | 1.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 83.00 | 0.00 | 83.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21.50 | 0.00 | 21.50 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 17.75 | 0.25 | 17.75 | 0.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 121.00 | 0.00 | 121.00 | 0.00 |
HEATEDBSMT | 151.75 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 1473.75 | 24.50 | 1331.75 | 24.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.317 | 0.000 | 0.278 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.273 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.100 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.099 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 54 |
Floor | 29 | 3 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 19 |
Conditioned Zones | 19 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1890 |
Defaulted Fields | 455 |
Fields with Defaults | 4813 |
Autosized Fields | 342 |
Autosizable Fields | 454 |
Autocalculated Fields | 99 |
Autocalculatable Fields | 287 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Fans:Electricity | 8357.52 | 132.81 | 06-MAY-22:45 | 3229.85 | 19-JUL-16:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:HEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
ElectricityPurchased:Plant | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
Cogeneration:ElectricityPurchased | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
ElectricityNet:Plant | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
Cogeneration:ElectricityNet | 131217.30 | 7487.46 | 26-JUN-03:30 | 38446.45 | 16-JUL-18:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 25297.96 | 532.25 | 06-MAY-23:00 | 18899.11 | 19-JUL-15:00 |
General:Fans:Electricity | 8357.52 | 132.81 | 06-MAY-22:45 | 3229.85 | 19-JUL-16:30 |
Cooling:Electricity | 16940.44 | 0.00 | 01-JAN-00:30 | 15692.73 | 19-JUL-15:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 8091.29 | 0.00 | 10-MAR-15:15 | 478960.47 | 27-JAN-06:30 |
Gas:Plant | 8091.29 | 0.00 | 10-MAR-15:15 | 478960.47 | 27-JAN-06:30 |
WaterSystems:Gas | 3242.22 | 0.00 | 01-JAN-00:15 | 117293.82 | 05-FEB-08:30 |
Water Heater:WaterSystems:Gas | 3242.22 | 0.00 | 01-JAN-00:15 | 117293.82 | 05-FEB-08:30 |
Heating:Gas | 4849.07 | 0.00 | 10-MAR-15:15 | 377751.50 | 27-JAN-07:15 |
Boiler:Heating:Gas | 4849.07 | 0.00 | 10-MAR-15:15 | 377751.50 | 27-JAN-07:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 06-JAN-03:00 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 569053.31 | 1498.91 | 15-AUG-02:15 | 314719.83 | 27-JAN-07:30 |
PlantLoopHeatingDemand:Plant | 180718.07 | 1498.91 | 15-AUG-02:15 | 48158.23 | 12-FEB-08:45 |
WaterSystems:PlantLoopHeatingDemand | 180718.07 | 1498.91 | 15-AUG-02:15 | 48158.23 | 12-FEB-08:45 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1800885.37 | 16427.37 | 26-JUN-03:15 | 896054.17 | 27-JAN-07:15 |
EnergyTransfer:Building | 588354.17 | 6619.89 | 24-APR-18:00 | 279378.48 | 27-JAN-07:15 |
EnergyTransfer:Zone:HEATEDBSMT | 14731.63 | 0.00 | 01-MAY-16:15 | 6541.70 | 26-MAR-22:30 |
Heating:EnergyTransfer | 402938.27 | 0.00 | 01-MAY-16:15 | 279378.48 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:HEATEDBSMT | 14670.26 | 0.00 | 01-MAY-16:15 | 6541.70 | 26-MAR-22:30 |
Cooling:EnergyTransfer | 185415.90 | 0.00 | 01-JAN-00:30 | 142855.79 | 18-JUL-17:15 |
Cooling:EnergyTransfer:Zone:HEATEDBSMT | 61.38 | 0.00 | 01-JAN-00:15 | 472.60 | 16-JUL-18:45 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 58487.51 | 0.00 | 01-JAN-00:30 | 18828.83 | 05-JUL-17:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1048.06 | 0.00 | 01-JAN-00:15 | 9077.20 | 27-JAN-01:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 57439.44 | 0.00 | 01-JAN-00:30 | 18828.83 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21672.46 | 0.00 | 17-JAN-11:00 | 15261.66 | 08-JAN-22:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 15589.26 | 0.00 | 17-JAN-11:00 | 15261.66 | 08-JAN-22:45 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6083.19 | 0.00 | 01-JAN-00:15 | 5755.19 | 19-JUL-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 33019.82 | 0.00 | 17-JAN-11:00 | 16062.89 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 24628.16 | 0.00 | 17-JAN-11:00 | 16062.89 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8391.66 | 0.00 | 01-JAN-00:15 | 7220.60 | 06-JUL-08:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 34349.99 | 0.00 | 08-MAR-16:00 | 18651.95 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 26900.89 | 0.00 | 08-MAR-16:00 | 18651.95 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 7449.10 | 0.00 | 01-JAN-00:15 | 9831.38 | 05-JUL-17:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 26619.60 | 0.00 | 19-MAR-16:15 | 14711.64 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21501.60 | 0.00 | 19-MAR-16:15 | 14711.64 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5118.00 | 0.00 | 01-JAN-00:15 | 5588.67 | 19-JUL-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 34161.93 | 0.00 | 10-MAR-12:45 | 16071.01 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 26777.66 | 0.00 | 10-MAR-12:45 | 16071.01 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7384.27 | 0.00 | 01-JAN-00:15 | 7235.89 | 06-JUL-08:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 26336.36 | 0.00 | 10-JAN-14:00 | 13807.78 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 17306.37 | 0.00 | 10-JAN-14:00 | 13807.78 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9029.99 | 0.00 | 01-JAN-00:15 | 9695.14 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 19723.62 | 0.00 | 10-JAN-12:45 | 10185.15 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 13184.28 | 0.00 | 10-JAN-12:45 | 10185.15 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6539.34 | 0.00 | 01-JAN-00:15 | 5124.35 | 17-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 26916.82 | 0.00 | 17-JAN-10:45 | 13925.33 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 18083.48 | 0.00 | 17-JAN-10:45 | 13925.33 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8833.34 | 0.00 | 01-JAN-00:15 | 6902.35 | 05-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 28166.76 | 0.00 | 08-MAR-15:45 | 13986.31 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20337.82 | 0.00 | 08-MAR-15:45 | 13986.31 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7828.94 | 0.00 | 01-JAN-00:15 | 9470.74 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20476.80 | 0.00 | 23-FEB-18:15 | 10455.15 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14934.71 | 0.00 | 23-FEB-18:15 | 10455.15 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5542.09 | 0.00 | 01-JAN-00:15 | 4944.99 | 17-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28050.77 | 0.00 | 10-MAR-11:15 | 13625.15 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 20253.42 | 0.00 | 10-MAR-11:15 | 13625.15 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7797.35 | 0.00 | 01-JAN-00:15 | 6894.73 | 05-JUL-09:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 39142.40 | 0.00 | 10-MAR-15:00 | 18150.80 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 30782.87 | 0.00 | 10-MAR-15:00 | 18150.80 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 8359.53 | 0.00 | 01-JAN-00:15 | 8172.37 | 17-JUL-16:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 37606.35 | 0.00 | 11-FEB-13:45 | 18141.36 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 28667.01 | 0.00 | 11-FEB-13:45 | 18141.36 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 8939.34 | 0.00 | 01-JAN-00:15 | 8221.26 | 17-JUL-14:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 37860.87 | 0.00 | 11-FEB-14:00 | 19680.27 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 28734.02 | 0.00 | 11-FEB-14:00 | 19680.27 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 9126.85 | 0.00 | 01-JAN-00:15 | 10945.55 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 31561.47 | 0.00 | 19-MAR-16:15 | 16732.26 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 25334.48 | 0.00 | 19-MAR-16:15 | 16732.26 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 6226.99 | 0.00 | 01-JAN-00:15 | 6554.90 | 17-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 29943.61 | 0.00 | 17-JAN-13:30 | 16703.33 | 27-JAN-07:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 23182.09 | 0.00 | 17-JAN-13:30 | 16703.33 | 27-JAN-07:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6761.53 | 0.00 | 01-JAN-00:15 | 6631.76 | 17-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 39525.38 | 0.00 | 08-MAR-16:15 | 20672.57 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 31021.82 | 0.00 | 08-MAR-16:15 | 20672.57 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 8503.56 | 0.00 | 01-JAN-00:15 | 10883.98 | 05-JUL-17:30 |
EnergyTransfer:Plant | 568643.28 | 1498.91 | 15-AUG-02:15 | 348009.51 | 27-JAN-07:15 |
WaterSystems:EnergyTransfer | 180718.07 | 1498.91 | 15-AUG-02:15 | 48158.23 | 12-FEB-08:45 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 180718.07 | 1498.91 | 15-AUG-02:15 | 48158.23 | 12-FEB-08:45 |
EnergyTransfer:HVAC | 643887.92 | 6897.52 | 25-JUN-01:00 | 268911.49 | 27-JAN-07:30 |
HeatingCoils:EnergyTransfer | 388335.24 | 0.00 | 10-MAR-15:15 | 268911.49 | 27-JAN-07:30 |
PlantLoopHeatingDemand:HVAC | 388335.24 | 0.00 | 10-MAR-15:15 | 268911.49 | 27-JAN-07:30 |
HeatingCoils:PlantLoopHeatingDemand | 388335.24 | 0.00 | 10-MAR-15:15 | 268911.49 | 27-JAN-07:30 |
CoolingCoils:EnergyTransfer | 255552.68 | 0.00 | 01-JAN-00:30 | 215764.56 | 18-JUL-17:30 |
Boilers:EnergyTransfer | 387925.21 | 0.00 | 10-MAR-15:15 | 302201.20 | 27-JAN-07:15 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 1048.054 | -4783.42 | 0.000 | 0.000 | 2902.757 | 2771.241 | 10464.601 | 7537.247 | 0.000 | 631.193 | 65613.703 | 0.000 | -7425.72 | 0.000 | -26103.65 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 15589.224 | -506.59 | 0.000 | 0.000 | 3121.158 | 2771.241 | 10464.601 | 3601.793 | 0.000 | 591.843 | 0.404 | 0.000 | -2774.80 | 0.000 | -21901.85 | -5380.05 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 24628.052 | -698.84 | 0.000 | 0.000 | 3063.865 | 2771.241 | 10464.601 | 7721.479 | 0.000 | 629.273 | 0.000 | 0.000 | -6916.66 | 0.000 | -24380.23 | -9589.98 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 26900.787 | -620.33 | 0.000 | 0.000 | 3069.584 | 2771.241 | 10464.601 | 5354.668 | 0.000 | 631.599 | 0.000 | 0.000 | -7495.48 | 0.000 | -24264.05 | -9983.96 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 21501.523 | -426.21 | 0.000 | 0.000 | 3064.629 | 2771.241 | 10464.601 | 1086.230 | 0.000 | 591.984 | 0.000 | 0.000 | -3181.44 | 0.000 | -22677.91 | -8502.86 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 26777.559 | -614.94 | 0.000 | 0.000 | 3068.538 | 2771.241 | 10464.601 | 5358.993 | 0.000 | 630.679 | 0.000 | 0.000 | -7312.63 | 0.000 | -24307.68 | -10067.03 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 17306.284 | -751.99 | 0.000 | 0.000 | 3049.893 | 2771.241 | 10464.601 | 7618.960 | 0.000 | 442.849 | 0.000 | 0.000 | -7202.59 | 0.000 | -16809.79 | -8611.58 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 13184.220 | -544.58 | 0.000 | 0.000 | 3043.763 | 2771.241 | 10464.601 | 3573.392 | 0.000 | 403.386 | 0.000 | 0.000 | -2879.02 | 0.000 | -15189.26 | -8833.02 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 18083.399 | -735.62 | 0.000 | 0.000 | 3053.407 | 2771.241 | 10464.601 | 7694.955 | 0.000 | 442.004 | 0.000 | 0.000 | -7015.26 | 0.000 | -16799.66 | -9861.37 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 20337.740 | -651.97 | 0.000 | 0.000 | 3060.082 | 2771.241 | 10464.601 | 5344.571 | 0.000 | 443.136 | 0.000 | 0.000 | -7601.21 | 0.000 | -16702.35 | -10288.96 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 14934.647 | -461.53 | 0.000 | 0.000 | 3053.546 | 2771.241 | 10464.601 | 1083.891 | 0.000 | 403.543 | 0.000 | 0.000 | -3223.05 | 0.000 | -15113.25 | -8833.08 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 20253.344 | -649.34 | 0.000 | 0.000 | 3059.397 | 2771.241 | 10464.601 | 5342.310 | 0.000 | 442.554 | 0.000 | 0.000 | -7406.86 | 0.000 | -16740.40 | -10388.84 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 30782.767 | -696.16 | 0.000 | 0.000 | 3068.442 | 2771.241 | 10464.601 | 5355.091 | 0.000 | 625.186 | 0.000 | 0.000 | -7357.44 | 0.000 | -24358.49 | -12991.89 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 28666.898 | -744.44 | 0.000 | 0.000 | 3065.165 | 2771.241 | 10464.601 | 7728.236 | 0.000 | 625.051 | 0.000 | 0.000 | -6953.49 | 0.000 | -24407.80 | -13020.59 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 28733.908 | -760.05 | 0.000 | 0.000 | 3065.591 | 2771.241 | 10464.601 | 7664.389 | 0.000 | 625.897 | 0.000 | 0.000 | -7100.78 | 0.000 | -24384.93 | -12713.21 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 25334.396 | -518.57 | 0.000 | 0.000 | 3064.722 | 2771.241 | 10464.601 | 1086.476 | 0.000 | 586.862 | 0.000 | 0.000 | -3195.96 | 0.000 | -22727.93 | -11157.44 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 23181.999 | -563.08 | 0.000 | 0.000 | 3059.950 | 2771.241 | 10464.601 | 3584.749 | 0.000 | 586.410 | 0.000 | 0.000 | -2851.21 | 0.000 | -22785.57 | -11250.69 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 31021.714 | -708.15 | 0.000 | 0.000 | 3069.048 | 2771.241 | 10464.601 | 5343.938 | 0.000 | 626.357 | 0.000 | 0.000 | -7546.16 | 0.000 | -24329.14 | -12918.16 |
HEATEDBSMT | 0.000 | 0.000 | 14670.257 | -5.11 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -14608.88 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3891.219 | 39892.843 | 0.000 | 0.000 | 0.000 | -43784.06 | 0.000 |
Total Facility | 0.000 | 0.000 | 402936.773 | -15440.93 | 0.000 | 0.000 | 55003.536 | 49882.340 | 188362.826 | 92081.368 | 0.000 | 13851.026 | 105506.950 | 0.000 | -105439.76 | 0.000 | -427768.00 | -189001.62 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 05-JUL-17:20 | 0.00 | 0.00 | 0.00 | -1.6 | 0.00 | 0.00 | 260.81 | 604.65 | 1664.02 | 6483.51 | 0.00 | 1539.33 | 8281.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 19-JUL-15:05 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 114.48 | 201.55 | 1147.45 | 1101.88 | 0.00 | 2326.03 | 878.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 06-JUL-08:25 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.08 | 170.54 | 1155.86 | 6870.39 | 0.00 | 673.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1839.1 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 05-JUL-17:45 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 261.60 | 604.65 | 1664.02 | 5985.42 | 0.00 | 1472.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -147.7 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19-JUL-14:55 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 1006.74 | 0.00 | 2476.96 | 786.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 06-JUL-08:15 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 193.42 | 170.54 | 1155.86 | 6960.74 | 0.00 | 578.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1817.2 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 05-JUL-17:20 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.37 | 604.65 | 1664.02 | 6475.30 | 0.00 | 1027.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -339.9 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17-JUL-18:45 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.60 | 813.96 | 1724.99 | 259.13 | 0.00 | 818.51 | 1082.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 05-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 193.28 | 170.54 | 1155.86 | 6123.13 | 0.00 | 572.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1303.4 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 05-JUL-17:20 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.37 | 604.65 | 1664.02 | 6634.86 | 0.00 | 1027.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.8 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 17-JUL-19:00 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.80 | 813.96 | 1724.99 | 302.13 | 0.00 | 804.22 | 875.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 05-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 193.04 | 170.54 | 1155.86 | 5953.19 | 0.00 | 570.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1139.4 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 17-JUL-16:15 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.46 | 434.11 | 1350.56 | 2010.62 | 0.00 | 2023.93 | 2215.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 17-JUL-14:38 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 2854.12 | 0.00 | 1973.33 | 2077.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 05-JUL-17:35 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 262.62 | 604.65 | 1664.02 | 5762.55 | 0.00 | 1466.45 | 1196.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 17-JUL-18:04 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.08 | 813.96 | 1724.99 | 428.02 | 0.00 | 1290.39 | 1871.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 17-JUL-18:08 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.08 | 813.96 | 1724.99 | 329.13 | 0.00 | 1290.37 | 2048.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 05-JUL-17:40 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 262.53 | 604.65 | 1664.02 | 5946.12 | 0.00 | 1469.83 | 967.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HEATEDBSMT | 16-JUL-18:33 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-17:04 | 0.00 | 0.00 | 0.00 | -11.9 | 0.00 | 0.00 | 4728.08 | 10883.76 | 29952.39 | 43611.08 | 0.00 | 27383.92 | 44030.06 | 0.00 | 0.00 | 0.00 | -17632.3 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27-JAN-01:45 | 0.00 | 0.00 | 9077.08 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 891.39 | 0.00 | 0.00 | 0.00 | 6258.76 | 0.00 | -3616.0 | 0.00 | -13199.6 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 31-JAN-04:51 | 0.00 | 0.00 | 16107.60 | 0.00 | 0.00 | 0.00 | 704.21 | 186.05 | 831.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -732.6 | 0.00 | -4055.8 | -13041.4 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 16062.94 | 0.00 | 0.00 | 0.00 | 509.32 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3491.5 | 0.00 | -12344.7 | -2334.3 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 17-JAN-15:21 | 0.00 | 0.00 | 19594.27 | 0.00 | 0.00 | 0.00 | 141.15 | 201.55 | 1147.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -107.5 | 0.00 | -2087.5 | -18889.5 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 27-JAN-08:15 | 0.00 | 0.00 | 14716.90 | 0.00 | 0.00 | 0.00 | 217.48 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1345.1 | 0.00 | -11932.5 | -2983.2 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 16071.06 | 0.00 | 0.00 | 0.00 | 510.13 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3519.4 | 0.00 | -12332.7 | -2327.5 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23-APR-09:35 | 0.00 | 0.00 | 17057.35 | 0.00 | 0.00 | 0.00 | 134.80 | 116.28 | 1126.15 | 1504.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1861.4 | -18077.8 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 03-APR-17:36 | 0.00 | 0.00 | 12619.75 | 0.00 | 0.00 | 0.00 | 305.75 | 604.65 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -549.0 | 0.00 | -2535.7 | -12109.5 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 13925.39 | 0.00 | 0.00 | 0.00 | 468.15 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3634.6 | 0.00 | -8094.5 | -4262.8 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 05-DEC-14:51 | 0.00 | 0.00 | 18580.17 | 0.00 | 0.00 | 0.00 | 141.56 | 116.28 | 1091.85 | 2763.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2517.0 | -20176.3 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 05-DEC-15:00 | 0.00 | 0.00 | 12127.22 | 0.00 | 0.00 | 0.00 | 127.31 | 116.28 | 1091.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -521.9 | 0.00 | -2466.3 | -10474.4 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 13625.21 | 0.00 | 0.00 | 0.00 | 474.23 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3655.6 | 0.00 | -8043.9 | -3998.3 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 18150.84 | 0.00 | 0.00 | 0.00 | 505.42 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3553.1 | 0.00 | -12415.5 | -4285.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 18141.40 | 0.00 | 0.00 | 0.00 | 504.58 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3518.9 | 0.00 | -12428.0 | -4297.5 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 19680.31 | 0.00 | 0.00 | 0.00 | 471.81 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3680.1 | 0.00 | -12891.1 | -5179.3 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 27-JAN-08:15 | 0.00 | 0.00 | 16737.36 | 0.00 | 0.00 | 0.00 | 216.90 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1357.3 | 0.00 | -11962.1 | -4961.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 27-JAN-07:30 | 0.00 | 0.00 | 16703.37 | 0.00 | 0.00 | 0.00 | 466.17 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -985.3 | 0.00 | -12022.0 | -5760.5 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 20673.71 | 0.00 | 0.00 | 0.00 | 215.07 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3355.3 | 0.00 | -13073.4 | -5786.5 |
HEATEDBSMT | 28-MAR-01:00 | 0.00 | 0.00 | 6585.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6585.8 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JAN-07:15 | 0.00 | 0.00 | 279379.49 | 0.00 | 0.00 | 0.00 | 8559.26 | 6976.77 | 21793.53 | 0.00 | 0.00 | 78.47 | 0.00 | 0.00 | -52590.7 | 0.00 | -195746.9 | -68450.0 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 854.027 | 2.00 | 2.00 | 1.00 | 44.9950 | 854.027 | 0.053 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 219.811 | 2.00 | 2.00 | 1.00 | 44.9950 | 219.811 | 0.205 | 1.000 | 44.9950 | 0.20 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 302.236 | 2.00 | 2.00 | 1.00 | 44.9950 | 302.236 | 0.149 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 432.508 | 2.00 | 2.00 | 1.00 | 44.9950 | 432.508 | 0.104 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 210.446 | 2.00 | 2.00 | 1.00 | 44.9950 | 210.446 | 0.214 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 301.369 | 2.00 | 2.00 | 1.00 | 44.9950 | 301.369 | 0.149 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 430.363 | 2.00 | 2.00 | 1.00 | 44.9950 | 430.363 | 0.105 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 213.095 | 2.00 | 2.00 | 1.00 | 44.9950 | 213.095 | 0.211 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 289.472 | 2.00 | 2.00 | 1.00 | 44.9950 | 289.472 | 0.155 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 415.375 | 2.00 | 2.00 | 1.00 | 44.9950 | 415.375 | 0.108 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 205.204 | 2.00 | 2.00 | 1.00 | 44.9950 | 205.204 | 0.219 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 288.856 | 2.00 | 2.00 | 1.00 | 44.9950 | 288.856 | 0.156 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.667 | 2.00 | 2.00 | 1.00 | 44.9950 | 488.667 | 0.092 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.292 | 2.00 | 2.00 | 1.00 | 44.9950 | 271.292 | 0.166 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.614 | 2.00 | 2.00 | 1.00 | 44.9950 | 321.614 | 0.140 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.774 | 2.00 | 2.00 | 1.00 | 44.9950 | 485.774 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.421 | 2.00 | 2.00 | 1.00 | 44.9950 | 271.421 | 0.166 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.941 | 2.00 | 2.00 | 1.00 | 44.9950 | 311.941 | 0.144 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 0.00 | 0.00 | 1.00 | 44.9950 | 44.995 | 1.000 | 1.000 | 44.9950 | 1.00 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 123.859 | 2.00 | 2.00 | 1.00 | 44.9950 | 123.859 | 1.000 | 1.000 | 44.9950 | 0.36 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 248.286 | 2.00 | 2.00 | 1.00 | 44.9950 | 248.286 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.993 | 2.00 | 2.00 | 1.00 | 44.9950 | 308.993 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 309.417 | 2.00 | 2.00 | 1.00 | 44.9950 | 309.417 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 248.294 | 2.00 | 2.00 | 1.00 | 44.9950 | 248.294 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 308.950 | 2.00 | 2.00 | 1.00 | 44.9950 | 308.950 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 244.779 | 2.00 | 2.00 | 1.00 | 44.9950 | 244.779 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 183.253 | 2.00 | 2.00 | 1.00 | 44.9950 | 183.253 | 1.000 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 244.268 | 2.00 | 2.00 | 1.00 | 44.9950 | 244.268 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 244.838 | 2.00 | 2.00 | 1.00 | 44.9950 | 244.838 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 183.255 | 2.00 | 2.00 | 1.00 | 44.9950 | 183.255 | 1.000 | 1.000 | 44.9950 | 0.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 244.230 | 2.00 | 2.00 | 1.00 | 44.9950 | 244.230 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.020 | 2.00 | 2.00 | 1.00 | 44.9950 | 348.020 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.515 | 2.00 | 2.00 | 1.00 | 44.9950 | 286.515 | 1.000 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.411 | 2.00 | 2.00 | 1.00 | 44.9950 | 347.411 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.049 | 2.00 | 2.00 | 1.00 | 44.9950 | 348.049 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.515 | 2.00 | 2.00 | 1.00 | 44.9950 | 286.515 | 1.000 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.384 | 2.00 | 2.00 | 1.00 | 44.9950 | 347.384 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 97.086 | 0.00 | 0.00 | 1.00 | 44.9950 | 97.086 | 1.000 | 1.000 | 44.9950 | 0.46 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 0.000000 | 0.00 | 0.000000 | 7794.39 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 0.00 | 0.000000 | 7794.39 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 854.027 | 854.0271 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 219.811 | 219.8114 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 302.236 | 302.2360 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 432.508 | 432.5076 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 210.446 | 210.4464 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 301.369 | 301.3693 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 430.363 | 430.3632 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 213.095 | 213.0947 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 289.472 | 289.4723 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 415.375 | 415.3746 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 205.204 | 205.2043 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 288.856 | 288.8559 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.941 | 311.9414 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.614 | 321.6138 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.667 | 488.6672 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.421 | 271.4207 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.292 | 271.2920 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.774 | 485.7739 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 44.995 | 44.9950 | 1168.9135 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 | 854.027 | 854.03 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 219.81 | 219.811 | 219.81 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 302.24 | 302.236 | 302.24 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 | 432.508 | 432.51 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 210.45 | 210.446 | 210.45 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 301.37 | 301.369 | 301.37 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 | 430.363 | 430.36 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 | 213.095 | 213.09 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 | 289.472 | 289.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 | 415.375 | 415.37 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 | 205.204 | 205.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 | 288.856 | 288.86 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.67 | 488.667 | 488.67 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.29 | 271.292 | 271.29 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.61 | 321.614 | 321.61 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.77 | 485.774 | 485.77 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.42 | 271.421 | 271.42 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.94 | 311.941 | 311.94 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 44.99 | 44.995 | 44.99 | 1168.9135 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 123.859 | 123.859 | 123.859 | 44.9950 | 0.363 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 248.286 | 248.286 | 248.286 | 44.9950 | 0.181 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.993 | 308.993 | 308.993 | 44.9950 | 0.146 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 309.417 | 309.417 | 309.417 | 44.9950 | 0.145 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 248.294 | 248.294 | 248.294 | 44.9950 | 0.181 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 308.950 | 308.950 | 308.950 | 44.9950 | 0.146 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 244.779 | 244.779 | 244.779 | 44.9950 | 0.184 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 183.253 | 183.253 | 183.253 | 44.9950 | 0.246 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 244.268 | 244.268 | 244.268 | 44.9950 | 0.184 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 244.838 | 244.838 | 244.838 | 44.9950 | 0.184 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 183.255 | 183.255 | 183.255 | 44.9950 | 0.246 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 244.230 | 244.230 | 244.230 | 44.9950 | 0.184 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.384 | 347.384 | 347.384 | 44.9950 | 0.130 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.411 | 347.411 | 347.411 | 44.9950 | 0.130 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.020 | 348.020 | 348.020 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.515 | 286.515 | 286.515 | 44.9950 | 0.157 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.515 | 286.515 | 286.515 | 44.9950 | 0.157 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.049 | 348.049 | 348.049 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
HEATEDBSMT | CENTRAL SYSTEM_UNITHEATEDBSMT | 97.086 | 97.086 | 97.086 | 44.9950 | 0.463 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 123.86 | 123.859 | 123.86 | 123.86 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 | 248.286 | 248.29 | 248.29 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 | 308.993 | 308.99 | 308.99 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 309.42 | 309.417 | 309.42 | 309.42 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 | 248.294 | 248.29 | 248.29 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 | 308.950 | 308.95 | 308.95 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 244.78 | 244.779 | 244.78 | 244.78 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 183.25 | 183.253 | 183.25 | 183.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 244.27 | 244.268 | 244.27 | 244.27 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 244.84 | 244.838 | 244.84 | 244.84 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 183.25 | 183.255 | 183.25 | 183.25 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 244.23 | 244.230 | 244.23 | 244.23 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.02 | 348.020 | 348.02 | 348.02 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.51 | 286.515 | 286.51 | 286.51 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.41 | 347.411 | 347.41 | 347.41 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.05 | 348.049 | 348.05 | 348.05 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.52 | 286.515 | 286.52 | 286.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.38 | 347.384 | 347.38 | 347.38 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 97.09 | 97.086 | 97.09 | 97.09 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
HEATEDBSMT | 7794.39 | 7794.39 | 0.00 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 29404.35 | 9600.82 |
Data | |
Number of hours heating loads not met | 1331.75 |
Number of hours cooling loads not met | 24.50 |
Number of hours not met | 1356.25 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4294.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 723.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 4849.07 | 363555.90 | 0.00 | 0.00 |
Space Cooling | 16940.44 | 14780.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 8357.52 | 3151.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 3242.22 | 115404.57 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 15497.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 131217.30 | 8091.29 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 448030.60 |
Natural Gas | 0.00 | 809128.65 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 1257159.25 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 0.00 |
Space Cooling | 0.43 |
Fans-Interior | 0.21 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 3.36 |
Natural Gas [kWh/ft2] | |
Space Heating | 3.64 |
Service Water Heating | 2.43 |
Miscellaneous | 0.00 |
Subtotal | 6.08 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 3.97 |
Space Heating | 38.57 |
Space Cooling | 4.60 |
Fans-Interior | 2.27 |
Service Water Heating | 25.79 |
Receptacle Equipment | 23.98 |
Miscellaneous | 0.82 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNITHEATEDBSMT | 97.09 |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 347.38 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 347.41 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 488.67 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 286.52 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 286.51 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 485.77 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.67 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.51 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.41 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.77 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.52 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.38 |
CENTRAL SYSTEM_UNITHEATEDBSMT | 97.09 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 | 2.06 | 0.769142 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 | 0.795210 | 0.686018 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 | 0.876939 | 0.718794 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 | 1.19 | 0.726841 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 | 0.790567 | 0.687524 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 | 0.877136 | 0.718689 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 | 1.15 | 0.736333 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 | 0.654065 | 0.697105 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 | 0.808529 | 0.723424 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 | 1.12 | 0.734575 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 | 0.636934 | 0.694144 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 | 0.806948 | 0.723373 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 488.67 | 1.31 | 0.735683 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 286.51 | 0.860302 | 0.703018 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 347.41 | 1.05 | 0.701452 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 485.77 | 1.30 | 0.735285 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 286.52 | 0.855514 | 0.704541 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 347.38 | 1.06 | 0.699324 |
DX COOLING COIL_UNITHEATEDBSMT | 97.09 | 0.323554 | 0.676083 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 | 854.03 | 854.03 | 2.06 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 | 248.29 | 248.29 | 0.795210 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 | 308.99 | 308.99 | 0.876939 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 | 432.51 | 432.51 | 1.19 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 | 248.29 | 248.29 | 0.790567 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 | 308.95 | 308.95 | 0.877136 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 | 430.36 | 430.36 | 1.15 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 | 213.09 | 213.09 | 0.654065 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 | 289.47 | 289.47 | 0.808529 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 | 415.37 | 415.37 | 1.12 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 | 205.20 | 205.20 | 0.636934 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 | 288.86 | 288.86 | 0.806948 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 488.67 | 488.67 | 488.67 | 1.31 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 286.51 | 286.51 | 286.51 | 0.860302 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 347.41 | 347.41 | 347.41 | 1.05 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 485.77 | 485.77 | 485.77 | 1.30 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 286.52 | 286.52 | 286.52 | 0.855514 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 347.38 | 347.38 | 347.38 | 1.06 | 1.00 |
ACANDF_UNITHEATEDBSMT | 97.09 | 97.09 | 97.09 | 0.323554 | 1.00 |
Design Size Design Coil Load [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 48776.70 | 4.92 | 689.08 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16745.30 | 1.69 | 223.01 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 19956.52 | 2.01 | 269.87 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 26489.23 | 2.67 | 364.94 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 16745.73 | 1.69 | 223.02 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 19954.23 | 2.01 | 269.84 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 26372.50 | 2.66 | 363.18 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 14882.60 | 1.50 | 195.67 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 18921.93 | 1.91 | 254.73 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 25579.87 | 2.58 | 351.66 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 14465.35 | 1.46 | 189.52 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 18889.33 | 1.91 | 254.26 |
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 29459.47 | 2.97 | 408.04 |
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18767.12 | 1.89 | 252.52 |
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 21988.38 | 2.22 | 299.44 |
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 29306.45 | 2.96 | 405.81 |
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 18767.13 | 1.89 | 252.52 |
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 21986.96 | 2.22 | 299.42 |
MAIN WATER HEATING COIL_UNITHEATEDBSMT | 8747.24 | 0.882882 | 104.19 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 854.03 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 248.29 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 308.99 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 432.51 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 248.29 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 308.95 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 430.36 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 213.09 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 289.47 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 415.37 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 205.20 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 288.86 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 488.67 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 286.51 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 347.41 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 485.77 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 286.52 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 347.38 |
SUPPLY FAN_UNITHEATEDBSMT | 97.09 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
BOILER LOOP | 5.62 | 105.45 |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
BOILER CIRC PUMP | 5.62 |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
CENTRAL BOILER | 418355.71 | 42.07 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:43:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 365.278 | 17.124 | 178.337 | 22.739 | 39.863 |
February | 420.188 | 22.400 | 93.369 | 9.970 | 32.370 |
March | 684.138 | 54.126 | 6.250 | 0.206 | 54.332 |
April | 719.625 | 93.823 | 0.000 | 0.000 | 93.823 |
May | 744.000 | 135.511 | 0.000 | 0.000 | 135.511 |
June | 720.000 | 171.191 | 0.000 | 0.000 | 171.191 |
July | 744.000 | 206.821 | 0.000 | 0.000 | 206.821 |
August | 744.000 | 186.615 | 0.000 | 0.000 | 186.615 |
September | 720.000 | 153.333 | 0.000 | 0.000 | 153.333 |
October | 744.000 | 102.682 | 0.000 | 0.000 | 102.682 |
November | 593.379 | 59.020 | 39.669 | 2.792 | 61.812 |
December | 406.530 | 17.108 | 122.535 | 9.546 | 26.654 |
Annual Sum or Average | 7605.139 | 1219.755 | 440.160 | 45.253 | 1265.009 |
Minimum of Months | 365.278 | 17.108 | 0.000 | 0.000 | 26.654 |
Maximum of Months | 744.000 | 206.821 | 178.337 | 22.739 | 206.821 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 537.740 | 23.833 | 48.749 |
February | 0.000 | 0.000 | 504.432 | 17.817 | 37.518 |
March | 16.458 | 0.098 | 603.526 | 11.793 | 18.557 |
April | 149.521 | 6.268 | 472.796 | 6.942 | 13.257 |
May | 278.710 | 8.643 | 216.729 | 1.155 | 9.797 |
June | 558.191 | 24.034 | 19.696 | 0.072 | 24.106 |
July | 709.567 | 40.211 | 0.000 | 0.000 | 40.211 |
August | 662.351 | 29.653 | 0.250 | 0.000 | 29.653 |
September | 462.777 | 16.974 | 60.000 | 0.179 | 17.152 |
October | 111.450 | 2.724 | 376.683 | 3.472 | 6.196 |
November | 35.688 | 0.723 | 495.027 | 10.809 | 22.344 |
December | 0.000 | 0.000 | 527.208 | 19.779 | 46.504 |
Annual Sum or Average | 2984.712 | 129.327 | 3814.087 | 95.852 | 314.045 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.196 |
Maximum of Months | 709.567 | 40.211 | 603.526 | 23.833 | 48.749 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 738.125 | 57.397 | 57.580 |
February | 0.000 | 0.000 | 662.875 | 44.432 | 44.898 |
March | 17.042 | 0.149 | 649.879 | 29.347 | 31.401 |
April | 158.783 | 9.368 | 453.342 | 15.838 | 27.426 |
May | 313.332 | 14.740 | 177.838 | 3.096 | 22.879 |
June | 556.662 | 36.775 | 15.417 | 0.256 | 39.011 |
July | 698.542 | 56.537 | 0.000 | 0.000 | 56.643 |
August | 641.672 | 41.630 | 0.125 | 0.003 | 42.451 |
September | 453.788 | 23.717 | 54.500 | 0.748 | 29.313 |
October | 105.827 | 3.581 | 360.558 | 9.270 | 20.574 |
November | 30.750 | 0.765 | 580.729 | 29.002 | 34.739 |
December | 0.000 | 0.000 | 742.071 | 53.205 | 53.463 |
Annual Sum or Average | 2976.396 | 187.262 | 4435.459 | 242.595 | 460.378 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 20.574 |
Maximum of Months | 698.542 | 56.537 | 742.071 | 57.397 | 57.580 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 739.310 | 67.746 | 68.736 |
February | 0.000 | 0.000 | 666.150 | 52.917 | 54.015 |
March | 7.583 | 0.067 | 665.696 | 35.876 | 43.953 |
April | 137.304 | 8.252 | 455.691 | 18.607 | 33.041 |
May | 267.670 | 14.538 | 216.197 | 3.998 | 25.825 |
June | 530.566 | 36.371 | 29.203 | 0.348 | 37.861 |
July | 695.585 | 57.966 | 1.000 | 0.002 | 57.981 |
August | 618.973 | 39.821 | 6.000 | 0.034 | 40.289 |
September | 378.872 | 18.376 | 97.281 | 1.217 | 22.841 |
October | 49.042 | 1.098 | 443.404 | 12.948 | 35.098 |
November | 15.917 | 0.181 | 626.904 | 35.258 | 40.376 |
December | 0.000 | 0.000 | 743.929 | 63.014 | 63.029 |
Annual Sum or Average | 2701.512 | 176.669 | 4690.764 | 291.966 | 523.045 |
Minimum of Months | 0.000 | 0.000 | 1.000 | 0.002 | 22.841 |
Maximum of Months | 695.585 | 57.966 | 743.929 | 67.746 | 68.736 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.881 | 33.523 | 33.537 |
February | 0.000 | 0.000 | 671.950 | 25.720 | 25.727 |
March | 0.000 | 0.000 | 704.904 | 16.967 | 18.283 |
April | 125.200 | 5.080 | 482.817 | 8.691 | 17.029 |
May | 252.446 | 7.252 | 230.035 | 1.665 | 10.084 |
June | 555.226 | 23.088 | 21.333 | 0.108 | 23.357 |
July | 709.375 | 38.753 | 0.000 | 0.000 | 38.753 |
August | 657.196 | 26.597 | 1.250 | 0.001 | 26.598 |
September | 398.198 | 11.496 | 81.431 | 0.339 | 11.862 |
October | 31.875 | 0.439 | 528.084 | 6.100 | 9.328 |
November | 16.250 | 0.204 | 626.858 | 16.288 | 16.895 |
December | 0.000 | 0.000 | 744.000 | 29.794 | 29.794 |
Annual Sum or Average | 2745.765 | 112.909 | 4836.544 | 139.195 | 261.246 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 9.328 |
Maximum of Months | 709.375 | 38.753 | 744.000 | 33.523 | 38.753 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 61.266 | 61.266 |
February | 0.000 | 0.000 | 672.000 | 48.041 | 48.041 |
March | 0.000 | 0.000 | 709.433 | 32.500 | 33.364 |
April | 140.020 | 7.795 | 484.919 | 16.887 | 25.814 |
May | 290.085 | 13.072 | 198.500 | 3.336 | 20.414 |
June | 556.274 | 35.704 | 17.250 | 0.265 | 37.852 |
July | 698.750 | 54.911 | 0.000 | 0.000 | 55.000 |
August | 639.139 | 38.415 | 1.000 | 0.009 | 39.186 |
September | 428.036 | 17.938 | 68.875 | 0.904 | 23.289 |
October | 47.313 | 0.824 | 519.863 | 12.136 | 16.485 |
November | 18.750 | 0.199 | 627.750 | 31.954 | 34.886 |
December | 0.000 | 0.000 | 744.000 | 56.917 | 56.917 |
Annual Sum or Average | 2818.366 | 168.858 | 4787.590 | 264.217 | 452.514 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 16.485 |
Maximum of Months | 698.750 | 54.911 | 744.000 | 61.266 | 61.266 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 731.792 | 46.143 | 46.143 |
February | 2.750 | 0.041 | 648.083 | 34.706 | 34.747 |
March | 43.417 | 1.176 | 622.546 | 21.904 | 23.079 |
April | 192.342 | 11.392 | 409.818 | 11.751 | 25.078 |
May | 336.581 | 18.497 | 148.295 | 1.811 | 24.564 |
June | 582.973 | 39.618 | 12.813 | 0.093 | 40.040 |
July | 712.412 | 60.431 | 0.000 | 0.000 | 60.431 |
August | 659.848 | 45.377 | 1.250 | 0.003 | 45.419 |
September | 469.352 | 26.710 | 54.875 | 0.424 | 27.955 |
October | 150.896 | 5.263 | 340.875 | 6.452 | 12.532 |
November | 45.063 | 1.290 | 559.500 | 22.060 | 23.350 |
December | 0.000 | 0.000 | 740.350 | 42.865 | 42.865 |
Annual Sum or Average | 3195.632 | 209.794 | 4270.198 | 188.211 | 406.203 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.532 |
Maximum of Months | 712.412 | 60.431 | 740.350 | 46.143 | 60.431 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 726.396 | 20.286 | 20.620 |
February | 0.000 | 0.000 | 641.187 | 15.073 | 15.959 |
March | 31.250 | 0.291 | 610.242 | 8.870 | 10.272 |
April | 170.167 | 6.914 | 408.995 | 4.666 | 13.565 |
May | 323.863 | 10.011 | 132.690 | 0.589 | 10.876 |
June | 598.389 | 25.549 | 8.375 | 0.013 | 25.564 |
July | 731.842 | 40.431 | 0.000 | 0.000 | 40.431 |
August | 700.903 | 31.384 | 0.000 | 0.000 | 31.384 |
September | 513.894 | 18.924 | 24.812 | 0.061 | 18.998 |
October | 152.417 | 3.455 | 292.025 | 2.137 | 5.772 |
November | 52.042 | 1.093 | 526.812 | 9.054 | 10.397 |
December | 0.000 | 0.000 | 739.050 | 18.412 | 18.462 |
Annual Sum or Average | 3274.766 | 138.051 | 4110.585 | 79.161 | 222.299 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.772 |
Maximum of Months | 731.842 | 40.431 | 739.050 | 20.286 | 40.431 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 730.396 | 45.675 | 46.571 |
February | 0.000 | 0.000 | 649.396 | 34.668 | 36.222 |
March | 28.167 | 0.319 | 607.450 | 21.939 | 24.901 |
April | 183.481 | 10.059 | 402.371 | 11.900 | 25.210 |
May | 369.747 | 16.254 | 103.487 | 1.595 | 25.189 |
June | 598.112 | 37.996 | 6.750 | 0.076 | 39.289 |
July | 715.142 | 56.226 | 0.000 | 0.000 | 56.226 |
August | 673.966 | 42.922 | 0.000 | 0.000 | 43.112 |
September | 496.922 | 25.436 | 22.354 | 0.272 | 30.581 |
October | 130.683 | 4.144 | 277.538 | 6.190 | 20.239 |
November | 38.479 | 1.047 | 530.208 | 22.174 | 29.658 |
December | 0.000 | 0.000 | 739.513 | 42.522 | 42.718 |
Annual Sum or Average | 3234.699 | 194.403 | 4069.462 | 187.009 | 419.914 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 20.239 |
Maximum of Months | 715.142 | 56.226 | 739.513 | 45.675 | 56.226 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.417 | 53.240 | 54.596 |
February | 0.000 | 0.000 | 660.875 | 41.123 | 43.119 |
March | 14.250 | 0.132 | 630.162 | 26.202 | 38.375 |
April | 161.083 | 8.978 | 415.164 | 13.489 | 30.587 |
May | 312.620 | 16.054 | 163.143 | 2.292 | 25.237 |
June | 574.555 | 38.009 | 14.500 | 0.126 | 38.710 |
July | 711.512 | 58.233 | 0.000 | 0.000 | 58.233 |
August | 654.542 | 41.653 | 1.250 | 0.005 | 41.771 |
September | 424.715 | 20.154 | 64.900 | 0.625 | 23.377 |
October | 62.833 | 1.360 | 376.496 | 8.849 | 33.692 |
November | 20.000 | 0.325 | 594.187 | 26.933 | 32.658 |
December | 0.000 | 0.000 | 741.232 | 50.065 | 50.613 |
Annual Sum or Average | 2936.111 | 184.898 | 4399.326 | 222.948 | 470.968 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 23.377 |
Maximum of Months | 711.512 | 58.233 | 741.232 | 53.240 | 58.233 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.937 | 22.395 | 22.402 |
February | 0.000 | 0.000 | 667.417 | 17.076 | 17.110 |
March | 2.917 | 0.010 | 684.871 | 10.415 | 11.562 |
April | 136.500 | 5.462 | 445.418 | 5.206 | 13.239 |
May | 298.601 | 8.471 | 154.669 | 0.673 | 9.728 |
June | 599.931 | 24.338 | 10.125 | 0.015 | 24.353 |
July | 732.067 | 38.430 | 0.000 | 0.000 | 38.430 |
August | 697.961 | 28.080 | 0.000 | 0.000 | 28.080 |
September | 460.351 | 13.218 | 40.583 | 0.096 | 13.315 |
October | 58.650 | 0.723 | 455.815 | 3.352 | 6.070 |
November | 23.542 | 0.363 | 582.708 | 10.429 | 11.252 |
December | 0.000 | 0.000 | 743.866 | 20.285 | 20.298 |
Annual Sum or Average | 3010.519 | 119.093 | 4529.410 | 89.942 | 215.839 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.070 |
Maximum of Months | 732.067 | 38.430 | 743.937 | 22.395 | 38.430 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 51.491 | 51.491 |
February | 0.000 | 0.000 | 667.750 | 39.764 | 40.363 |
March | 0.000 | 0.000 | 687.800 | 25.622 | 27.023 |
April | 162.646 | 8.360 | 443.443 | 13.039 | 23.809 |
May | 348.195 | 14.511 | 119.704 | 1.784 | 22.943 |
June | 598.446 | 37.027 | 7.375 | 0.086 | 38.255 |
July | 715.567 | 54.671 | 0.000 | 0.000 | 54.671 |
August | 672.722 | 39.912 | 0.000 | 0.000 | 40.098 |
September | 470.787 | 19.727 | 33.542 | 0.382 | 24.584 |
October | 56.354 | 1.051 | 444.700 | 8.785 | 16.503 |
November | 23.000 | 0.350 | 581.417 | 25.904 | 30.988 |
December | 0.000 | 0.000 | 744.000 | 48.114 | 48.114 |
Annual Sum or Average | 3047.716 | 175.608 | 4473.731 | 214.971 | 418.842 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 16.503 |
Maximum of Months | 715.567 | 54.671 | 744.000 | 51.491 | 54.671 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 82.950 | 82.950 |
February | 0.000 | 0.000 | 667.083 | 64.297 | 64.297 |
March | 19.458 | 0.384 | 669.050 | 43.823 | 44.870 |
April | 156.767 | 10.987 | 434.251 | 23.414 | 42.020 |
May | 282.319 | 18.176 | 190.026 | 4.833 | 37.142 |
June | 523.877 | 41.880 | 21.566 | 0.394 | 45.882 |
July | 689.687 | 66.773 | 0.050 | 0.000 | 66.984 |
August | 615.103 | 47.422 | 3.690 | 0.032 | 48.947 |
September | 400.947 | 25.465 | 74.443 | 1.462 | 35.180 |
October | 88.896 | 3.428 | 441.946 | 15.497 | 25.394 |
November | 28.417 | 0.704 | 610.312 | 42.822 | 46.863 |
December | 0.000 | 0.000 | 744.000 | 77.210 | 77.210 |
Annual Sum or Average | 2805.470 | 215.218 | 4600.418 | 356.734 | 617.739 |
Minimum of Months | 0.000 | 0.000 | 0.050 | 0.000 | 25.394 |
Maximum of Months | 689.687 | 66.773 | 744.000 | 82.950 | 82.950 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.500 | 36.780 | 36.780 |
February | 0.000 | 0.000 | 666.833 | 27.991 | 28.054 |
March | 5.562 | 0.032 | 667.071 | 18.357 | 19.620 |
April | 142.660 | 7.287 | 459.691 | 10.014 | 20.259 |
May | 271.674 | 10.462 | 234.793 | 2.075 | 13.628 |
June | 541.964 | 28.534 | 27.433 | 0.151 | 28.745 |
July | 703.087 | 47.492 | 0.000 | 0.000 | 47.492 |
August | 645.823 | 34.166 | 4.750 | 0.011 | 34.177 |
September | 437.437 | 18.342 | 89.469 | 0.495 | 18.871 |
October | 89.737 | 2.127 | 439.331 | 5.918 | 8.893 |
November | 27.708 | 0.585 | 614.354 | 17.819 | 18.460 |
December | 0.000 | 0.000 | 744.000 | 32.983 | 32.983 |
Annual Sum or Average | 2865.654 | 149.028 | 4691.225 | 152.594 | 307.960 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.893 |
Maximum of Months | 703.087 | 47.492 | 744.000 | 36.780 | 47.492 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.500 | 65.315 | 65.330 |
February | 0.000 | 0.000 | 667.575 | 50.819 | 50.923 |
March | 3.958 | 0.013 | 671.058 | 34.180 | 35.671 |
April | 155.300 | 9.503 | 464.262 | 18.631 | 30.290 |
May | 301.163 | 14.967 | 202.271 | 3.767 | 22.915 |
June | 560.243 | 38.116 | 21.375 | 0.328 | 40.279 |
July | 695.491 | 59.228 | 0.000 | 0.000 | 59.365 |
August | 640.634 | 42.552 | 3.500 | 0.032 | 43.363 |
September | 438.253 | 22.914 | 75.292 | 1.140 | 28.182 |
October | 86.342 | 2.613 | 428.104 | 11.807 | 20.635 |
November | 25.250 | 0.583 | 613.396 | 33.817 | 37.316 |
December | 0.000 | 0.000 | 744.000 | 60.815 | 60.815 |
Annual Sum or Average | 2906.634 | 190.489 | 4634.333 | 280.651 | 495.083 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 20.635 |
Maximum of Months | 695.491 | 59.228 | 744.000 | 65.315 | 65.330 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 77.878 | 77.878 |
February | 0.000 | 0.000 | 668.425 | 60.849 | 61.649 |
March | 6.187 | 0.035 | 679.808 | 41.615 | 47.326 |
April | 142.204 | 9.780 | 458.162 | 21.845 | 36.927 |
May | 271.814 | 17.294 | 226.024 | 4.814 | 31.011 |
June | 523.915 | 41.407 | 33.736 | 0.451 | 43.244 |
July | 690.158 | 65.919 | 1.250 | 0.004 | 65.989 |
August | 612.346 | 45.458 | 9.808 | 0.071 | 45.989 |
September | 370.971 | 21.203 | 111.062 | 1.646 | 27.870 |
October | 49.063 | 1.134 | 481.983 | 16.102 | 36.033 |
November | 14.375 | 0.196 | 639.875 | 41.140 | 45.258 |
December | 0.000 | 0.000 | 744.000 | 72.752 | 72.752 |
Annual Sum or Average | 2681.033 | 202.426 | 4798.134 | 339.167 | 591.925 |
Minimum of Months | 0.000 | 0.000 | 1.250 | 0.004 | 27.870 |
Maximum of Months | 690.158 | 65.919 | 744.000 | 77.878 | 77.878 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 39.950 | 39.950 |
February | 0.000 | 0.000 | 672.000 | 30.673 | 30.673 |
March | 0.000 | 0.000 | 706.183 | 20.257 | 21.568 |
April | 125.125 | 6.544 | 479.525 | 10.533 | 20.111 |
May | 262.974 | 9.931 | 244.501 | 2.174 | 13.243 |
June | 544.060 | 28.339 | 28.025 | 0.156 | 28.582 |
July | 702.858 | 47.014 | 0.000 | 0.000 | 47.014 |
August | 643.197 | 32.570 | 4.750 | 0.010 | 32.580 |
September | 396.679 | 14.570 | 105.760 | 0.584 | 15.185 |
October | 34.500 | 0.528 | 556.046 | 7.825 | 10.556 |
November | 15.250 | 0.228 | 640.062 | 19.829 | 20.468 |
December | 0.000 | 0.000 | 744.000 | 35.907 | 35.907 |
Annual Sum or Average | 2724.644 | 139.725 | 4924.853 | 167.899 | 315.837 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 10.556 |
Maximum of Months | 702.858 | 47.014 | 744.000 | 39.950 | 47.014 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 69.401 | 69.401 |
February | 0.000 | 0.000 | 672.000 | 54.399 | 54.399 |
March | 0.000 | 0.000 | 713.629 | 36.918 | 37.670 |
April | 141.250 | 8.510 | 483.667 | 19.288 | 29.384 |
May | 292.582 | 14.267 | 209.370 | 3.893 | 21.975 |
June | 560.691 | 37.576 | 22.500 | 0.332 | 39.666 |
July | 695.881 | 58.191 | 0.000 | 0.000 | 58.307 |
August | 639.929 | 40.667 | 3.500 | 0.032 | 41.481 |
September | 417.465 | 18.929 | 86.036 | 1.251 | 24.257 |
October | 43.896 | 0.806 | 551.637 | 14.567 | 18.053 |
November | 16.500 | 0.193 | 639.854 | 36.706 | 39.310 |
December | 0.000 | 0.000 | 744.000 | 64.832 | 64.832 |
Annual Sum or Average | 2808.193 | 179.139 | 4870.193 | 301.618 | 498.736 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 18.053 |
Maximum of Months | 695.881 | 58.191 | 744.000 | 69.401 | 69.401 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 20.158 | 20.158 |
February | 0.000 | 0.000 | 672.000 | 17.192 | 17.192 |
March | 0.000 | 0.000 | 718.813 | 14.042 | 15.263 |
April | 0.000 | 0.000 | 635.625 | 9.082 | 13.184 |
May | 0.000 | 0.000 | 131.103 | 0.225 | 1.663 |
June | 0.167 | 0.000 | 0.000 | 0.000 | 0.000 |
July | 264.679 | 0.905 | 0.000 | 0.000 | 0.905 |
August | 68.552 | 0.153 | 0.000 | 0.000 | 0.153 |
September | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
October | 0.000 | 0.000 | 291.250 | 0.370 | 0.370 |
November | 0.000 | 0.000 | 675.667 | 10.313 | 12.469 |
December | 0.000 | 0.000 | 744.000 | 18.577 | 18.577 |
Annual Sum or Average | 333.398 | 1.058 | 4612.457 | 89.960 | 99.935 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
Maximum of Months | 264.679 | 0.905 | 744.000 | 20.158 | 20.158 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.11 |
February | 0.00 | 0.00 | 0.15 |
March | 0.00 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.60 |
May | 0.00 | 0.00 | 0.84 |
June | 0.00 | 0.00 | 1.09 |
July | 0.00 | 0.00 | 1.29 |
August | 0.00 | 0.00 | 1.17 |
September | 0.00 | 0.00 | 0.99 |
October | 0.00 | 0.00 | 0.64 |
November | 0.00 | 0.00 | 0.38 |
December | 0.00 | 0.00 | 0.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.64 |
Minimum of Months | 0.00 | 0.00 | 0.11 |
Maximum of Months | 0.00 | 0.00 | 1.29 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.34 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.42 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.21 |
July | 0.00 | 0.00 | 0.33 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.33 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.19 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNITHEATEDBSMT
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.01 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.01 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:43:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1879.84 | 1399.59 |
February | 0.00 | 0.00 | 1910.09 | 1284.49 |
March | 0.00 | 0.00 | 1867.36 | 1390.30 |
April | 0.00 | 0.00 | 1774.38 | 1278.46 |
May | 0.00 | 0.00 | 1643.10 | 1223.33 |
June | 0.00 | 0.00 | 1511.32 | 1088.92 |
July | 0.00 | 0.00 | 1417.55 | 1055.41 |
August | 0.00 | 0.00 | 1380.58 | 1027.88 |
September | 0.00 | 0.00 | 1416.60 | 1020.67 |
October | 0.00 | 0.00 | 1512.63 | 1126.19 |
November | 0.00 | 0.00 | 1645.60 | 1185.68 |
December | 0.00 | 0.00 | 1784.95 | 1328.94 |
Annual Sum or Average | 0.00 | 0.00 | 1643.80 | 14409.87 |
Minimum of Months | 0.00 | 0.00 | 1380.58 | 1020.67 |
Maximum of Months | 0.00 | 0.00 | 1910.09 | 1399.59 |