Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37
Tabular Output Report in Format: HTML
Building: MF+CZ5AWH+USA_IL_Chicago-OHare.Intl.AP.725300+elecres+crawlspace+IECC_2009
Environment: ANNUAL ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
Simulation Timestamp: 2019-02-14 08:37:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1036498.45 | 26.57 | 47.96 |
Net Site Energy | 1036498.45 | 26.57 | 47.96 |
Total Source Energy | 3282590.60 | 84.16 | 151.90 |
Net Source Energy | 3282590.60 | 84.16 | 151.90 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 39005.17 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 17395.21 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 408112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 46705.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 23394.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 196632.97 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1036498.45 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 408112.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 46705.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 23394.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 196632.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 31.23 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 47.96 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 17.30 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 26.57 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1036498.452 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1036498.452 | 100.00 |
Total On-Site and Utility Electric Sources | 1036498.452 | 100.00 |
Total Electricity End Uses | 1036498.452 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 9.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1961.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:37 |
RunPeriod | ANNUAL |
Weather File | Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Latitude [deg] | 41.98 |
Longitude [deg] | -87.9 |
Elevation [ft] | 659.48 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 17103.09 | 6415.36 | 2136.19 | 6415.36 | 2136.19 |
Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 12.43 | 8.29 | 24.89 | 8.29 | 24.89 |
Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
CRAWLSPACE | 7794.39 | No | Yes | 19407.54 | 1.00 | 185.02 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 2.9092 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 2.9092 |
Total | 39005.17 | 286495.20 | 16363.00 | 740.10 | 2126.74 | 2126.74 | 0.4163 | 1083.48 | 1.6118 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 2.9092 | |||
Unconditioned Total | 17395.21 | 102755.82 | 1066.39 | 740.10 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 27-JAN-07:30 | - | - | - | - | 01-JAN-08:15 |
Heating | 284.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 6.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 33.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 9.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 134.39 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 469.38 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 284.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 6.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 0.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 4.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_dryer | 3.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_range | 3.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
electric_mels | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 1.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 9.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 134.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 1292493.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 147915.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 74090.57 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 622736.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3282590.60 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 151.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 59.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 6.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 3.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 28.82 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 151.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | -4.0 | 0.00 | -4.0 | Wetbulb [F] | 964.61 | 270.00 |
CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 91.94 | 18.90 | 74.66 | Wetbulb [F] | 1023.67 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BGWALL_UPPER_LDF | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 180.00 | 90.00 | S |
BGWALL_LOWER_LDF | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 180.00 | 90.00 | S |
BGWALL_UPPER_SDR | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 90.00 | 90.00 | E |
BGWALL_LOWER_SDR | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 90.00 | 90.00 | E |
BGWALL_UPPER_LDB | CRAWL WALL | 0.30 | 0.776 | 2.276 | 59.96 | 59.96 | 0.00 | 90.00 | N |
BGWALL_LOWER_LDB | CRAWL WALL | 0.30 | 0.893 | 2.276 | 239.83 | 239.83 | 0.00 | 90.00 | N |
BGWALL_UPPER_SDL | CRAWL WALL | 0.30 | 0.776 | 2.276 | 32.56 | 32.56 | 270.00 | 90.00 | W |
BGWALL_LOWER_SDL | CRAWL WALL | 0.30 | 0.893 | 2.276 | 130.22 | 130.22 | 270.00 | 90.00 | W |
BGFLOOR | INTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 16569.21 | 12247.71 | 4321.50 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10118.37 | 6937.14 | 3181.23 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11138.28 | 7974.04 | 3164.24 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14143.64 | 10263.99 | 3879.65 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10120.78 | 6938.19 | 3182.60 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11140.49 | 7974.56 | 3165.93 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13790.43 | 10152.23 | 3638.20 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7824.26 | 5451.98 | 2372.29 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9671.19 | 6993.06 | 2678.13 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 13386.35 | 9831.12 | 3555.24 | 0.73 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7617.38 | 5285.04 | 2332.34 | 0.69 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9652.32 | 6978.95 | 2673.38 | 0.72 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15716.32 | 11561.93 | 4154.39 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10332.68 | 7263.68 | 3069.00 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12597.93 | 8836.50 | 3761.43 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 15643.47 | 11502.10 | 4141.37 | 0.74 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10275.23 | 7238.92 | 3036.31 | 0.70 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 12696.93 | 8878.90 | 3818.03 | 0.70 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | 3.30 | 11.26 | 11.94 | 11.67 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.8 | 3.40 | 11.62 | 12.33 | 12.26 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.35 | 11.41 | 12.11 | 11.92 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.33 | 11.35 | 12.04 | 11.81 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.8 | 3.40 | 11.62 | 12.33 | 12.26 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.9 | 3.35 | 11.42 | 12.11 | 11.92 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.1 | 3.31 | 11.28 | 11.97 | 11.70 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.38 | 11.54 | 12.25 | 12.13 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.8 | 3.33 | 11.37 | 12.06 | 11.84 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.31 | 11.29 | 11.98 | 11.72 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.39 | 11.56 | 12.27 | 12.17 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.33 | 11.37 | 12.06 | 11.84 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.31 | 11.29 | 11.97 | 11.71 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.37 | 11.50 | 12.20 | 12.06 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.37 | 11.51 | 12.22 | 12.08 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.31 | 11.29 | 11.97 | 11.71 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.37 | 11.49 | 12.19 | 12.05 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 1.0 | 3.38 | 11.52 | 12.23 | 12.10 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 18834.08 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 17514.75 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 20738.44 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 20760.81 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 17514.80 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 20736.13 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 16639.85 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 13391.69 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 16611.94 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 16642.03 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 13391.71 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 16609.91 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 22029.95 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 18778.34 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 21997.65 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 22031.39 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 18778.35 | 1.00 | |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 21996.22 | 1.00 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 520.99 | 260.91 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 262.83 | 131.63 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 323.78 | 162.15 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 425.26 | 212.97 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 262.84 | 131.63 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 323.73 | 162.12 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 429.39 | 215.04 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 212.19 | 106.26 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 288.20 | 144.33 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 414.39 | 207.53 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 204.25 | 102.29 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 287.59 | 144.03 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 488.53 | 244.65 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 286.73 | 143.59 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 347.59 | 174.07 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 485.63 | 243.20 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 286.73 | 143.59 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 347.56 | 174.06 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.06 | 0.96 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 11949.84 | 11949.84 | 9.95 | 520.991 | 520.991 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00916 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4894.57 | 4894.57 | 4.08 | 213.386 | 213.386 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.01030 | 85.99 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6670.62 | 6670.62 | 5.56 | 290.812 | 290.812 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 74.98 | 74.98 | 0.00982 | 82.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9754.10 | 9754.10 | 8.12 | 425.259 | 425.259 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00937 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4683.62 | 4683.62 | 3.90 | 204.187 | 204.187 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.01042 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6651.36 | 6651.36 | 5.54 | 289.973 | 289.973 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:15:00 | 74.98 | 74.98 | 0.00982 | 82.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9849.18 | 9849.18 | 8.20 | 429.388 | 429.388 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 74.98 | 74.98 | 0.00906 | 88.35 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4867.28 | 4867.28 | 4.05 | 212.189 | 212.189 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00991 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 6610.97 | 6610.97 | 5.51 | 288.205 | 288.205 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 74.98 | 74.98 | 0.00946 | 83.15 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9505.25 | 9505.25 | 7.92 | 414.394 | 414.394 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00911 | 87.88 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4685.27 | 4685.27 | 3.90 | 204.254 | 204.254 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00998 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6596.98 | 6596.98 | 5.49 | 287.594 | 287.594 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 74.98 | 74.98 | 0.00946 | 83.15 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 7151.08 | 7151.08 | 5.96 | 311.809 | 311.809 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00967 | 91.37 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 7372.98 | 7372.98 | 6.14 | 321.485 | 321.485 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 74.98 | 74.98 | 0.00963 | 91.37 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 11205.24 | 11205.24 | 9.33 | 488.527 | 488.527 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00923 | 87.88 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 6222.24 | 6222.24 | 5.18 | 271.267 | 271.267 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00996 | 84.57 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 6219.43 | 6219.43 | 5.18 | 271.146 | 271.146 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00994 | 85.28 | 0.01496 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 11138.71 | 11138.71 | 9.28 | 485.627 | 485.627 | CHICAGO OHARE INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 17:45:00 | 74.98 | 74.98 | 0.00924 | 87.88 | 0.01496 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 15445.28 | 15445.28 | 12.87 | 287.776 | 287.776 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00577 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14106.41 | 14106.41 | 11.75 | 262.835 | 262.835 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00576 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 17377.83 | 17377.83 | 14.47 | 323.778 | 323.778 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00595 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 17400.53 | 17400.53 | 14.49 | 324.201 | 324.201 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00595 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 14106.46 | 14106.46 | 11.75 | 262.836 | 262.836 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00576 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17375.48 | 17375.48 | 14.47 | 323.734 | 323.734 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00595 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13218.27 | 13218.27 | 11.01 | 246.318 | 246.318 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9922.00 | 9922.00 | 8.26 | 184.900 | 184.900 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00599 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13189.95 | 13189.95 | 10.99 | 245.790 | 245.790 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13220.48 | 13220.48 | 11.01 | 246.359 | 246.359 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 9922.02 | 9922.02 | 8.26 | 184.901 | 184.901 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00599 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13187.88 | 13187.88 | 10.98 | 245.752 | 245.752 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 18654.20 | 18654.20 | 15.54 | 347.559 | 347.559 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 18655.64 | 18655.64 | 15.54 | 347.586 | 347.586 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 18688.43 | 18688.43 | 15.57 | 348.197 | 348.197 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 15388.67 | 15388.67 | 12.82 | 286.727 | 286.727 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00589 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 15388.67 | 15388.67 | 12.82 | 286.727 | 286.727 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00589 | -4.0 | 0.00065 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 18689.89 | 18689.89 | 15.57 | 348.224 | 348.224 | CHICAGO OHARE INTL AP ANN HTG 99.6% CONDNS DB | 1/21 15:00:00 | 72.00 | 71.97 | 0.00605 | -4.0 | 0.00065 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 | 520.99 | 287.78 | 287.78 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 213.39 | 213.39 | 262.83 | 262.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 290.81 | 290.81 | 323.78 | 323.78 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 | 425.26 | 324.20 | 324.20 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.19 | 204.19 | 262.84 | 262.84 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 289.97 | 289.97 | 323.73 | 323.73 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 | 429.39 | 246.32 | 246.32 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 | 212.19 | 184.90 | 184.90 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 | 288.20 | 245.79 | 245.79 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 | 414.39 | 246.36 | 246.36 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 | 204.25 | 184.90 | 184.90 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 | 287.59 | 245.75 | 245.75 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.53 | 488.53 | 348.20 | 348.20 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.15 | 271.15 | 286.73 | 286.73 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.48 | 321.48 | 347.59 | 347.59 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.63 | 485.63 | 348.22 | 348.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.27 | 271.27 | 286.73 | 286.73 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.81 | 311.81 | 347.56 | 347.56 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2504.75 | 5548.75 | 654.50 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2244.50 | 6457.75 | 854.75 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2853.50 | 6293.25 | 1173.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 3012.50 | 6689.50 | 1551.75 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2323.25 | 6763.00 | 1073.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2993.25 | 6473.25 | 1459.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2822.50 | 5877.00 | 812.75 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2184.75 | 5766.00 | 359.75 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2748.25 | 5757.50 | 717.75 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2885.50 | 6124.25 | 1012.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2168.50 | 6015.75 | 435.25 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2831.50 | 5939.75 | 919.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 3350.25 | 6170.50 | 1488.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 3155.25 | 6052.75 | 1202.50 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 3222.75 | 6275.00 | 1371.50 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 2744.25 | 6386.25 | 1101.25 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 2570.50 | 6224.00 | 865.75 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 3388.00 | 6421.00 | 1623.25 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 3796.25 | 6987.50 | 1961.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.75 | 0.00 | 0.75 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 9.00 | 0.00 | 9.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 2.25 | 0.00 | 2.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 1.75 | 0.00 | 1.75 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 9.00 | 0.00 | 9.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.313 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.274 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.100 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.099 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.137 | 0.000 | 0.277 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.275 | 0.000 | 0.277 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.312 | 0.000 | 0.277 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Surfaces by ClassTotal | Outdoors | |
Wall | 82 | 58 |
Floor | 29 | 4 |
Roof | 27 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 3 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1824 |
Defaulted Fields | 446 |
Fields with Defaults | 4570 |
Autosized Fields | 288 |
Autosizable Fields | 396 |
Autocalculated Fields | 98 |
Autocalculatable Fields | 286 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
Electricity:Building | 102912.40 | 6348.70 | 02-JAN-03:15 | 19791.35 | 01-JAN-18:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5717.36 | 352.71 | 02-JAN-03:15 | 1099.52 | 01-JAN-18:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:15 | 15497.32 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:15 | 3196.73 | 01-JAN-11:15 |
electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:15 | 3721.08 | 01-JAN-17:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:15 | 7929.96 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:15 | 526.17 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:15 | 860.96 | 01-JAN-18:15 |
Electricity:Plant | 57589.03 | 0.00 | 01-JAN-00:15 | 39776.02 | 12-FEB-08:45 |
WaterSystems:Electricity | 57589.03 | 0.00 | 01-JAN-00:15 | 39776.02 | 12-FEB-08:45 |
Water Heater:WaterSystems:Electricity | 57589.03 | 0.00 | 01-JAN-00:15 | 39776.02 | 12-FEB-08:45 |
Fans:Electricity | 6851.70 | 0.00 | 12-APR-13:45 | 3053.98 | 19-JUL-16:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
ElectricityPurchased:Plant | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
Cogeneration:ElectricityPurchased | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
ElectricityNet:Plant | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
Cogeneration:ElectricityNet | 303565.26 | 6931.05 | 12-JUN-03:45 | 137469.97 | 27-JAN-07:30 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 140056.89 | 0.00 | 12-APR-13:45 | 87273.73 | 27-JAN-07:15 |
General:Fans:Electricity | 6851.70 | 0.00 | 12-APR-13:45 | 3053.98 | 19-JUL-16:30 |
Heating:Electricity | 119526.36 | 0.00 | 26-MAR-17:15 | 84601.66 | 27-JAN-07:15 |
Cooling:Electricity | 13678.83 | 0.00 | 01-JAN-00:15 | 15133.47 | 19-JUL-15:00 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
None |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 04-JAN-02:15 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
PlantLoopHeatingDemand:Plant | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1348282.60 | 1518.59 | 01-SEP-03:00 | 632247.27 | 27-JAN-07:15 |
EnergyTransfer:Building | 558406.57 | 0.00 | 12-APR-13:45 | 297777.96 | 27-JAN-07:15 |
EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 420907.54 | 0.00 | 26-MAR-17:15 | 297777.96 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 137499.03 | 0.00 | 01-JAN-00:15 | 134704.34 | 18-JUL-17:15 |
Cooling:EnergyTransfer:Zone:CRAWLSPACE | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 31963.66 | 0.00 | 10-JAN-13:30 | 17400.30 | 27-JAN-01:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 18040.11 | 0.00 | 10-JAN-13:30 | 17400.30 | 27-JAN-01:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13923.56 | 0.00 | 01-JAN-00:15 | 11703.14 | 05-JUL-17:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 26184.71 | 0.00 | 17-JAN-11:30 | 15655.05 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20824.36 | 0.00 | 17-JAN-11:30 | 15655.05 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5360.35 | 0.00 | 01-JAN-00:15 | 5803.68 | 19-JUL-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 33957.97 | 0.00 | 17-JAN-11:30 | 19251.92 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 26297.73 | 0.00 | 17-JAN-11:30 | 19251.92 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7660.23 | 0.00 | 01-JAN-00:15 | 7320.85 | 06-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 35789.57 | 0.00 | 08-MAR-15:30 | 19520.87 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 28987.35 | 0.00 | 08-MAR-15:30 | 19520.87 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6802.22 | 0.00 | 01-JAN-00:15 | 9681.99 | 05-JUL-17:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 27905.23 | 0.00 | 19-MAR-18:15 | 15950.43 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 23427.77 | 0.00 | 19-MAR-18:15 | 15950.43 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4477.47 | 0.00 | 01-JAN-00:15 | 5409.02 | 19-JUL-15:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 35479.41 | 0.00 | 26-MAR-14:30 | 19271.62 | 27-JAN-01:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28778.20 | 0.00 | 26-MAR-14:30 | 19271.62 | 27-JAN-01:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6701.20 | 0.00 | 01-JAN-00:15 | 7339.00 | 06-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 27332.36 | 0.00 | 10-JAN-14:30 | 13881.94 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 18463.58 | 0.00 | 10-JAN-14:30 | 13881.94 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8868.78 | 0.00 | 01-JAN-00:15 | 9676.05 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 19362.11 | 0.00 | 10-JAN-12:45 | 10246.45 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12969.52 | 0.00 | 10-JAN-12:45 | 10246.45 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6392.58 | 0.00 | 01-JAN-00:15 | 5103.19 | 17-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27031.13 | 0.00 | 17-JAN-10:45 | 13838.67 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 18327.85 | 0.00 | 17-JAN-10:45 | 13838.67 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8703.28 | 0.00 | 01-JAN-00:15 | 6875.16 | 05-JUL-09:00 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 28459.99 | 0.00 | 11-FEB-15:15 | 14073.88 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 20745.47 | 0.00 | 11-FEB-15:15 | 14073.88 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 7714.53 | 0.00 | 01-JAN-00:15 | 9451.99 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 20629.40 | 0.00 | 23-FEB-18:15 | 10494.83 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15216.74 | 0.00 | 23-FEB-18:15 | 10494.83 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5412.65 | 0.00 | 01-JAN-00:15 | 4924.22 | 17-JUL-19:00 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 28215.37 | 0.00 | 10-MAR-11:45 | 13858.42 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 20538.69 | 0.00 | 10-MAR-11:45 | 13858.42 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7676.68 | 0.00 | 01-JAN-00:15 | 6867.58 | 05-JUL-09:00 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 39195.44 | 0.00 | 19-MAR-15:45 | 20397.44 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 30854.40 | 0.00 | 19-MAR-15:45 | 20397.44 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 8341.04 | 0.00 | 01-JAN-00:15 | 8167.42 | 17-JUL-16:15 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 37652.09 | 0.00 | 11-FEB-13:45 | 20372.54 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 28730.91 | 0.00 | 11-FEB-13:45 | 20372.54 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 8921.18 | 0.00 | 01-JAN-00:15 | 8223.76 | 17-JUL-14:45 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 38114.55 | 0.00 | 11-FEB-14:00 | 20419.51 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 29006.91 | 0.00 | 11-FEB-14:00 | 20419.51 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 9107.65 | 0.00 | 01-JAN-00:15 | 10942.66 | 05-JUL-17:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 31598.89 | 0.00 | 19-MAR-16:15 | 17091.43 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 25394.14 | 0.00 | 19-MAR-16:15 | 17091.43 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 6204.75 | 0.00 | 01-JAN-00:15 | 6549.47 | 17-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 29922.79 | 0.00 | 17-JAN-13:30 | 16778.14 | 27-JAN-07:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 23183.91 | 0.00 | 17-JAN-13:30 | 16778.14 | 27-JAN-07:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 6738.88 | 0.00 | 01-JAN-00:15 | 6623.30 | 17-JUL-18:15 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 39611.91 | 0.00 | 08-MAR-15:30 | 20677.60 | 27-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 31119.90 | 0.00 | 08-MAR-15:30 | 20677.60 | 27-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 8492.01 | 0.00 | 01-JAN-00:15 | 10880.94 | 05-JUL-17:30 |
EnergyTransfer:Plant | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
WaterSystems:EnergyTransfer | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 180719.91 | 1498.86 | 15-AUG-02:45 | 48159.02 | 12-FEB-09:00 |
EnergyTransfer:HVAC | 609156.12 | 0.00 | 12-APR-13:45 | 288660.86 | 27-JAN-07:15 |
HeatingCoils:EnergyTransfer | 408112.87 | 0.00 | 26-MAR-17:15 | 288660.86 | 27-JAN-07:15 |
CoolingCoils:EnergyTransfer | 201043.25 | 0.00 | 01-JAN-00:15 | 206566.13 | 18-JUL-17:30 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 18040.015 | -1159.51 | 0.000 | 0.000 | 3031.517 | 2771.241 | 10464.601 | 7658.292 | 0.000 | 631.366 | 3027.266 | 0.000 | -7044.45 | 0.000 | -24656.38 | -0.05 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 20824.265 | -446.39 | 0.000 | 0.000 | 3063.065 | 2771.241 | 10464.601 | 3600.983 | 0.000 | 592.021 | 0.000 | 0.000 | -2811.38 | 0.000 | -22722.83 | -10421.66 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 26297.612 | -637.92 | 0.000 | 0.000 | 3068.214 | 2771.241 | 10464.601 | 7760.445 | 0.000 | 631.260 | 0.000 | 0.000 | -6848.95 | 0.000 | -24343.40 | -12140.83 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 28987.227 | -566.46 | 0.000 | 0.000 | 3073.157 | 2771.241 | 10464.601 | 5380.745 | 0.000 | 632.038 | 0.000 | 0.000 | -7416.91 | 0.000 | -24258.33 | -12831.68 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 23427.676 | -372.87 | 0.000 | 0.000 | 3070.445 | 2771.241 | 10464.601 | 1099.725 | 0.000 | 592.362 | 0.000 | 0.000 | -3143.62 | 0.000 | -22634.20 | -11170.78 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 28778.086 | -558.06 | 0.000 | 0.000 | 3072.855 | 2771.241 | 10464.601 | 5393.180 | 0.000 | 631.337 | 0.000 | 0.000 | -7233.14 | 0.000 | -24274.42 | -12902.55 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 18463.485 | -738.56 | 0.000 | 0.000 | 3051.522 | 2771.241 | 10464.601 | 7637.703 | 0.000 | 442.924 | 0.000 | 0.000 | -7159.43 | 0.000 | -16795.35 | -10008.04 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 12969.456 | -532.36 | 0.000 | 0.000 | 3045.600 | 2771.241 | 10464.601 | 3575.117 | 0.000 | 403.424 | 0.000 | 0.000 | -2878.45 | 0.000 | -15178.51 | -8779.93 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 18327.760 | -724.79 | 0.000 | 0.000 | 3053.557 | 2771.241 | 10464.601 | 7700.979 | 0.000 | 442.082 | 0.000 | 0.000 | -7005.93 | 0.000 | -16797.56 | -10253.47 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 20745.374 | -642.44 | 0.000 | 0.000 | 3059.220 | 2771.241 | 10464.601 | 5340.243 | 0.000 | 443.206 | 0.000 | 0.000 | -7592.25 | 0.000 | -16727.66 | -10789.54 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 15216.678 | -450.75 | 0.000 | 0.000 | 3054.874 | 2771.241 | 10464.601 | 1086.497 | 0.000 | 403.604 | 0.000 | 0.000 | -3216.82 | 0.000 | -15106.84 | -9261.19 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 20538.598 | -639.30 | 0.000 | 0.000 | 3059.906 | 2771.241 | 10464.601 | 5347.959 | 0.000 | 442.560 | 0.000 | 0.000 | -7394.82 | 0.000 | -16736.67 | -10816.70 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 30854.287 | -694.62 | 0.000 | 0.000 | 3068.005 | 2771.241 | 10464.601 | 5355.846 | 0.000 | 625.189 | 0.000 | 0.000 | -7356.74 | 0.000 | -24363.80 | -13077.61 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 28730.792 | -742.93 | 0.000 | 0.000 | 3064.616 | 2771.241 | 10464.601 | 7728.895 | 0.000 | 625.059 | 0.000 | 0.000 | -6953.26 | 0.000 | -24413.53 | -13097.27 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 29006.784 | -758.45 | 0.000 | 0.000 | 3064.782 | 2771.241 | 10464.601 | 7663.194 | 0.000 | 625.897 | 0.000 | 0.000 | -7094.55 | 0.000 | -24397.96 | -12996.48 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 25394.045 | -516.72 | 0.000 | 0.000 | 3064.782 | 2771.241 | 10464.601 | 1086.938 | 0.000 | 586.902 | 0.000 | 0.000 | -3195.27 | 0.000 | -22728.70 | -11239.81 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 23183.811 | -561.19 | 0.000 | 0.000 | 3060.122 | 2771.241 | 10464.601 | 3585.112 | 0.000 | 586.436 | 0.000 | 0.000 | -2850.99 | 0.000 | -22785.16 | -11276.34 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 31119.782 | -707.18 | 0.000 | 0.000 | 3068.150 | 2771.241 | 10464.601 | 5339.004 | 0.000 | 626.360 | 0.000 | 0.000 | -7546.35 | 0.000 | -24349.80 | -13001.10 |
CRAWLSPACE | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10183.563 | 81264.201 | 0.000 | 0.000 | 0.000 | -91447.76 | 0.000 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3893.277 | 39893.004 | 0.000 | 0.000 | 0.000 | -43786.28 | 0.000 |
Total Facility | 0.000 | 0.000 | 420905.732 | -11450.52 | 0.000 | 0.000 | 55094.390 | 49882.340 | 188362.826 | 92340.859 | 0.000 | 24040.866 | 124184.472 | 0.000 | -104743.31 | 0.000 | -518505.11 | -194065.05 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 05-JUL-17:45 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 261.69 | 604.65 | 1664.02 | 5800.89 | 0.00 | 1476.87 | 1902.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 19-JUL-14:55 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 1196.27 | 0.00 | 2476.95 | 811.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 06-JUL-08:56 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.56 | 170.54 | 1155.86 | 6175.23 | 0.00 | 907.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1282.3 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 05-JUL-17:45 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 261.46 | 604.65 | 1664.02 | 5987.77 | 0.00 | 1469.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -297.2 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 19-JUL-14:55 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 1008.73 | 0.00 | 2476.89 | 604.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 06-JUL-08:56 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 194.57 | 170.54 | 1155.86 | 6009.15 | 0.00 | 907.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1098.0 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 05-JUL-17:20 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.37 | 604.65 | 1664.02 | 6475.70 | 0.00 | 1027.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -359.4 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17-JUL-18:45 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.67 | 813.96 | 1724.99 | 259.45 | 0.00 | 818.83 | 1060.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 05-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 193.26 | 170.54 | 1155.86 | 6123.65 | 0.00 | 572.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1331.0 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 05-JUL-17:20 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 263.37 | 604.65 | 1664.02 | 6635.26 | 0.00 | 1027.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -742.9 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 17-JUL-19:00 | 0.00 | 0.00 | 0.00 | -0.4 | 0.00 | 0.00 | 426.77 | 813.96 | 1724.99 | 302.32 | 0.00 | 804.09 | 854.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 05-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 193.03 | 170.54 | 1155.86 | 5953.71 | 0.00 | 570.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1167.0 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 17-JUL-16:04 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 140.46 | 434.11 | 1350.56 | 2010.80 | 0.00 | 2024.02 | 2214.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 17-JUL-14:38 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.19 | 116.28 | 1091.85 | 2854.30 | 0.00 | 1973.65 | 2080.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 05-JUL-17:35 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 262.62 | 604.65 | 1664.02 | 5762.61 | 0.00 | 1466.43 | 1193.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 17-JUL-18:04 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 427.08 | 813.96 | 1724.99 | 428.08 | 0.00 | 1290.39 | 1866.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 17-JUL-18:04 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 427.08 | 813.96 | 1724.99 | 329.22 | 0.00 | 1290.40 | 2038.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 05-JUL-17:40 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 262.52 | 604.65 | 1664.02 | 5946.17 | 0.00 | 1469.81 | 964.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-JUL-17:04 | 0.00 | 0.00 | 0.00 | -11.2 | 0.00 | 0.00 | 4733.50 | 10883.76 | 29952.39 | 43655.94 | 0.00 | 42429.20 | 20789.62 | 0.00 | 0.00 | 0.00 | -17632.2 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27-JAN-01:15 | 0.00 | 0.00 | 17400.00 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 891.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3579.6 | 0.00 | -13377.7 | -1922.4 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 15655.11 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1460.2 | 0.00 | -11956.7 | -4301.3 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 19251.98 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3601.1 | 0.00 | -12990.5 | -4723.4 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 19520.58 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3301.2 | 0.00 | -13060.3 | -4700.5 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 15950.18 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1340.6 | 0.00 | -12014.4 | -4136.6 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 27-JAN-01:00 | 0.00 | 0.00 | 19271.28 | 0.00 | 0.00 | 0.00 | 526.31 | 62.02 | 962.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3552.0 | 0.00 | -13467.3 | -3803.2 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 13882.02 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3710.0 | 0.00 | -8129.4 | -4105.7 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 10246.53 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1482.1 | 0.00 | -7095.0 | -3732.6 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 13838.76 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3653.6 | 0.00 | -8129.4 | -4118.9 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 14073.66 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3367.0 | 0.00 | -8142.5 | -4105.6 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 10494.65 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1368.0 | 0.00 | -7096.0 | -3572.1 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 13858.50 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3691.3 | 0.00 | -8129.4 | -4101.0 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 20397.50 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3677.1 | 0.00 | -13003.9 | -5779.6 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 20372.60 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3637.7 | 0.00 | -13003.9 | -5794.2 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 20419.57 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3696.8 | 0.00 | -13003.9 | -5782.1 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 17091.16 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1361.7 | 0.00 | -12026.7 | -5244.2 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 27-JAN-07:15 | 0.00 | 0.00 | 16778.20 | 0.00 | 0.00 | 0.00 | 464.78 | 387.60 | 1210.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1474.2 | 0.00 | -11968.9 | -5398.3 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 27-JAN-08:08 | 0.00 | 0.00 | 20677.29 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1155.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3355.2 | 0.00 | -13073.7 | -5789.8 |
CRAWLSPACE | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 27-JAN-07:15 | 0.00 | 0.00 | 297779.16 | 0.00 | 0.00 | 0.00 | 8366.07 | 6976.77 | 21793.53 | 0.00 | 0.00 | 60.98 | 0.00 | 0.00 | -53062.2 | 0.00 | -259324.2 | -22590.1 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 520.991 | 2.00 | 2.00 | 1.00 | 44.9950 | 520.991 | 0.086 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 213.386 | 2.00 | 2.00 | 1.00 | 44.9950 | 213.386 | 0.211 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 290.812 | 2.00 | 2.00 | 1.00 | 44.9950 | 290.812 | 0.155 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.259 | 2.00 | 2.00 | 1.00 | 44.9950 | 425.259 | 0.106 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.187 | 2.00 | 2.00 | 1.00 | 44.9950 | 204.187 | 0.220 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 289.973 | 2.00 | 2.00 | 1.00 | 44.9950 | 289.973 | 0.155 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.388 | 2.00 | 2.00 | 1.00 | 44.9950 | 429.388 | 0.105 | 1.000 | 44.9950 | 0.10 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.189 | 2.00 | 2.00 | 1.00 | 44.9950 | 212.189 | 0.212 | 1.000 | 44.9950 | 0.21 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.205 | 2.00 | 2.00 | 1.00 | 44.9950 | 288.205 | 0.156 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 414.394 | 2.00 | 2.00 | 1.00 | 44.9950 | 414.394 | 0.109 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 204.254 | 2.00 | 2.00 | 1.00 | 44.9950 | 204.254 | 0.220 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 287.594 | 2.00 | 2.00 | 1.00 | 44.9950 | 287.594 | 0.156 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.527 | 2.00 | 2.00 | 1.00 | 44.9950 | 488.527 | 0.092 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.146 | 2.00 | 2.00 | 1.00 | 44.9950 | 271.146 | 0.166 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.485 | 2.00 | 2.00 | 1.00 | 44.9950 | 321.485 | 0.140 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.627 | 2.00 | 2.00 | 1.00 | 44.9950 | 485.627 | 0.093 | 1.000 | 44.9950 | 0.09 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.267 | 2.00 | 2.00 | 1.00 | 44.9950 | 271.267 | 0.166 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.809 | 2.00 | 2.00 | 1.00 | 44.9950 | 311.809 | 0.144 | 1.000 | 44.9950 | 0.14 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 287.776 | 2.00 | 2.00 | 1.00 | 44.9950 | 287.776 | 1.000 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 262.835 | 2.00 | 2.00 | 1.00 | 44.9950 | 262.835 | 1.000 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 323.778 | 2.00 | 2.00 | 1.00 | 44.9950 | 323.778 | 1.000 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 324.201 | 2.00 | 2.00 | 1.00 | 44.9950 | 324.201 | 1.000 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 262.836 | 2.00 | 2.00 | 1.00 | 44.9950 | 262.836 | 1.000 | 1.000 | 44.9950 | 0.17 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 323.734 | 2.00 | 2.00 | 1.00 | 44.9950 | 323.734 | 1.000 | 1.000 | 44.9950 | 0.14 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 246.318 | 2.00 | 2.00 | 1.00 | 44.9950 | 246.318 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 184.900 | 2.00 | 2.00 | 1.00 | 44.9950 | 184.900 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 245.790 | 2.00 | 2.00 | 1.00 | 44.9950 | 245.790 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 246.359 | 2.00 | 2.00 | 1.00 | 44.9950 | 246.359 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 184.901 | 2.00 | 2.00 | 1.00 | 44.9950 | 184.901 | 1.000 | 1.000 | 44.9950 | 0.24 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 245.752 | 2.00 | 2.00 | 1.00 | 44.9950 | 245.752 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.197 | 2.00 | 2.00 | 1.00 | 44.9950 | 348.197 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.727 | 2.00 | 2.00 | 1.00 | 44.9950 | 286.727 | 1.000 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.586 | 2.00 | 2.00 | 1.00 | 44.9950 | 347.586 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.224 | 2.00 | 2.00 | 1.00 | 44.9950 | 348.224 | 1.000 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.727 | 2.00 | 2.00 | 1.00 | 44.9950 | 286.727 | 1.000 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.559 | 2.00 | 2.00 | 1.00 | 44.9950 | 347.559 | 1.000 | 1.000 | 44.9950 | 0.13 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 520.991 | 520.9910 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 213.386 | 213.3861 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 290.812 | 290.8125 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.259 | 425.2589 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.187 | 204.1869 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 289.973 | 289.9727 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.388 | 429.3878 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.189 | 212.1886 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.205 | 288.2047 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 414.394 | 414.3944 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 204.254 | 204.2541 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 287.594 | 287.5944 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.809 | 311.8092 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.485 | 321.4849 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.527 | 488.5271 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.267 | 271.2669 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.146 | 271.1456 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.627 | 485.6267 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 | 520.991 | 520.99 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 213.39 | 213.386 | 213.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 290.81 | 290.812 | 290.81 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 | 425.259 | 425.26 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 204.19 | 204.187 | 204.19 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 289.97 | 289.973 | 289.97 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 | 429.388 | 429.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 | 212.189 | 212.19 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 | 288.205 | 288.20 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 | 414.394 | 414.39 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 | 204.254 | 204.25 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 | 287.594 | 287.59 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.53 | 488.527 | 488.53 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 271.15 | 271.146 | 271.15 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 321.48 | 321.485 | 321.48 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.63 | 485.627 | 485.63 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 271.27 | 271.267 | 271.27 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 311.81 | 311.809 | 311.81 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 287.776 | 287.776 | 287.776 | 44.9950 | 0.156 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 262.835 | 262.835 | 262.835 | 44.9950 | 0.171 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 323.778 | 323.778 | 323.778 | 44.9950 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 324.201 | 324.201 | 324.201 | 44.9950 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 262.836 | 262.836 | 262.836 | 44.9950 | 0.171 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 323.734 | 323.734 | 323.734 | 44.9950 | 0.139 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 246.318 | 246.318 | 246.318 | 44.9950 | 0.183 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 184.900 | 184.900 | 184.900 | 44.9950 | 0.243 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 245.790 | 245.790 | 245.790 | 44.9950 | 0.183 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 246.359 | 246.359 | 246.359 | 44.9950 | 0.183 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 184.901 | 184.901 | 184.901 | 44.9950 | 0.243 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 245.752 | 245.752 | 245.752 | 44.9950 | 0.183 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.559 | 347.559 | 347.559 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.586 | 347.586 | 347.586 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.197 | 348.197 | 348.197 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.727 | 286.727 | 286.727 | 44.9950 | 0.157 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.727 | 286.727 | 286.727 | 44.9950 | 0.157 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.224 | 348.224 | 348.224 | 44.9950 | 0.129 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 287.78 | 287.776 | 287.78 | 287.78 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 | 262.835 | 262.83 | 262.83 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 | 323.778 | 323.78 | 323.78 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 324.20 | 324.201 | 324.20 | 324.20 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 | 262.836 | 262.84 | 262.84 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 | 323.734 | 323.73 | 323.73 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 246.32 | 246.318 | 246.32 | 246.32 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 184.90 | 184.900 | 184.90 | 184.90 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 245.79 | 245.790 | 245.79 | 245.79 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 246.36 | 246.359 | 246.36 | 246.36 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 184.90 | 184.901 | 184.90 | 184.90 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 245.75 | 245.752 | 245.75 | 245.75 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 348.20 | 348.197 | 348.20 | 348.20 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.73 | 286.727 | 286.73 | 286.73 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.59 | 347.586 | 347.59 | 347.59 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 348.22 | 348.224 | 348.22 | 348.22 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.73 | 286.727 | 286.73 | 286.73 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.56 | 347.559 | 347.56 | 347.56 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300 |
Total gross floor area [ft2] | 39005.17 |
Principal Heating Source | Electricity |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
CRAWLSPACE | 7794.39 | 0.00 | 7794.39 | 0.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 39005.17 | 21609.96 | 17395.21 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 9.00 |
Number of hours not met | 9.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 2044.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 78.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 119526.36 | 83435.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Cooling | 13678.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 6851.70 | 2639.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 57589.03 | 39358.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Receptacle Equipment | 88303.07 | 9912.20 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 303565.26 | 0.00 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 301503.54 | 1036498.45 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 301503.54 | 1036498.45 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.37 |
Space Heating | 3.06 |
Space Cooling | 0.35 |
Fans-Interior | 0.18 |
Service Water Heating | 1.48 |
Receptacle Equipment | 2.26 |
Miscellaneous | 0.08 |
Subtotal | 7.78 |
Natural Gas [kWh/ft2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.81 |
Space Heating | 39.37 |
Space Cooling | 4.51 |
Fans-Interior | 2.26 |
Service Water Heating | 18.97 |
Receptacle Equipment | 29.09 |
Miscellaneous | 0.99 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 347.56 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 347.59 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 488.53 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 286.73 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 286.73 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 485.63 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 488.53 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 286.73 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 347.59 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 485.63 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 286.73 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 347.56 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 | 1.38 | 0.739185 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 | 0.843197 | 0.685598 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 | 0.928190 | 0.715913 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 | 1.18 | 0.725697 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 | 0.843399 | 0.685538 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 | 0.928374 | 0.715818 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 | 1.15 | 0.736179 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 | 0.652022 | 0.696804 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 | 0.805932 | 0.723081 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 | 1.12 | 0.734413 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 | 0.634782 | 0.693814 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 | 0.804360 | 0.723033 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 488.53 | 1.31 | 0.735664 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 286.73 | 0.861057 | 0.702981 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 347.59 | 1.05 | 0.701425 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 485.63 | 1.30 | 0.735265 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 286.73 | 0.856269 | 0.704502 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 347.56 | 1.06 | 0.699295 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 | 520.99 | 520.99 | 18834.08 | 1.38 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 | 262.83 | 262.83 | 17514.75 | 0.843197 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 | 323.78 | 323.78 | 20738.44 | 0.928190 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 | 425.26 | 425.26 | 20760.81 | 1.18 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 | 262.84 | 262.84 | 17514.80 | 0.843399 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 | 323.73 | 323.73 | 20736.13 | 0.928374 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 | 429.39 | 429.39 | 16639.85 | 1.15 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 | 212.19 | 212.19 | 13391.69 | 0.652022 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 | 288.20 | 288.20 | 16611.94 | 0.805932 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 | 414.39 | 414.39 | 16642.03 | 1.12 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 | 204.25 | 204.25 | 13391.71 | 0.634782 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 | 287.59 | 287.59 | 16609.91 | 0.804360 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 488.53 | 488.53 | 488.53 | 22029.95 | 1.31 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 286.73 | 286.73 | 286.73 | 18778.34 | 0.861057 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 347.59 | 347.59 | 347.59 | 21997.65 | 1.05 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 485.63 | 485.63 | 485.63 | 22031.39 | 1.30 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 286.73 | 286.73 | 286.73 | 18778.35 | 0.856269 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 347.56 | 347.56 | 347.56 | 21996.22 | 1.06 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 520.99 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 262.83 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 323.78 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 425.26 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 262.84 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 323.73 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 429.39 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 212.19 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 288.20 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 414.39 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 204.25 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 287.59 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 488.53 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 286.73 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 347.59 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 485.63 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 286.73 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 347.56 |
Design Size Nominal Capacity [Btu/h] | |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 18834.08 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 17514.75 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 20738.44 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 20760.81 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 17514.80 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 20736.13 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 16639.85 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 13391.69 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 16611.94 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 16642.03 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 13391.71 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 16609.91 |
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 22029.95 |
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18778.34 |
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 21997.65 |
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 22031.39 |
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 18778.35 |
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 21996.22 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:37:21
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 721.950 | 62.223 | 62.223 |
February | 4.000 | 0.115 | 628.375 | 46.102 | 46.217 |
March | 60.204 | 2.182 | 602.337 | 26.955 | 29.137 |
April | 230.389 | 17.495 | 385.654 | 12.766 | 30.261 |
May | 464.325 | 29.684 | 80.271 | 0.968 | 30.652 |
June | 666.006 | 59.168 | 4.250 | 0.018 | 59.186 |
July | 741.200 | 86.260 | 0.000 | 0.000 | 86.260 |
August | 730.510 | 68.188 | 0.000 | 0.000 | 68.188 |
September | 594.234 | 42.910 | 9.000 | 0.046 | 42.955 |
October | 257.254 | 10.332 | 259.583 | 5.541 | 15.873 |
November | 93.896 | 3.271 | 475.333 | 27.631 | 30.902 |
December | 0.000 | 0.000 | 736.800 | 56.215 | 56.215 |
Annual Sum or Average | 3842.019 | 319.605 | 3903.554 | 238.463 | 558.068 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 15.873 |
Maximum of Months | 741.200 | 86.260 | 736.800 | 62.223 | 86.260 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 740.250 | 35.524 | 35.524 |
February | 0.000 | 0.000 | 666.000 | 27.722 | 27.722 |
March | 5.812 | 0.017 | 670.792 | 19.080 | 19.097 |
April | 134.021 | 5.895 | 494.000 | 10.626 | 16.520 |
May | 244.481 | 7.466 | 253.690 | 2.313 | 9.779 |
June | 513.245 | 21.695 | 31.750 | 0.191 | 21.886 |
July | 695.443 | 37.377 | 0.000 | 0.000 | 37.377 |
August | 625.898 | 26.570 | 5.500 | 0.012 | 26.583 |
September | 423.809 | 14.616 | 86.446 | 0.500 | 15.117 |
October | 88.596 | 2.090 | 429.167 | 6.014 | 8.104 |
November | 30.000 | 0.552 | 607.708 | 17.906 | 18.458 |
December | 0.000 | 0.000 | 744.000 | 32.590 | 32.590 |
Annual Sum or Average | 2761.307 | 116.279 | 4729.304 | 152.478 | 268.757 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.104 |
Maximum of Months | 695.443 | 37.377 | 744.000 | 35.524 | 37.377 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 740.750 | 46.404 | 46.404 |
February | 0.000 | 0.000 | 666.917 | 35.984 | 35.984 |
March | 8.625 | 0.034 | 676.358 | 24.379 | 24.413 |
April | 152.988 | 8.861 | 483.979 | 13.466 | 22.327 |
May | 285.544 | 13.212 | 245.813 | 3.086 | 16.298 |
June | 530.811 | 34.114 | 43.396 | 0.368 | 34.482 |
July | 676.955 | 53.484 | 2.500 | 0.009 | 53.494 |
August | 616.114 | 38.218 | 12.250 | 0.063 | 38.281 |
September | 421.562 | 21.132 | 113.792 | 1.007 | 22.138 |
October | 92.747 | 2.932 | 461.667 | 8.518 | 11.450 |
November | 27.500 | 0.599 | 634.563 | 23.995 | 24.594 |
December | 0.000 | 0.000 | 744.000 | 42.851 | 42.851 |
Annual Sum or Average | 2812.847 | 172.586 | 4825.983 | 200.128 | 372.715 |
Minimum of Months | 0.000 | 0.000 | 2.500 | 0.009 | 11.450 |
Maximum of Months | 676.955 | 53.484 | 744.000 | 46.404 | 53.494 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 65.060 | 65.060 |
February | 0.000 | 0.000 | 672.000 | 50.985 | 50.985 |
March | 4.875 | 0.028 | 706.683 | 35.503 | 35.531 |
April | 129.167 | 7.858 | 492.792 | 18.826 | 26.684 |
May | 246.360 | 13.166 | 290.450 | 4.780 | 17.946 |
June | 495.429 | 33.581 | 53.875 | 0.532 | 34.112 |
July | 673.364 | 54.316 | 3.000 | 0.013 | 54.328 |
August | 583.002 | 36.176 | 15.500 | 0.094 | 36.271 |
September | 339.391 | 15.992 | 151.334 | 1.674 | 17.666 |
October | 43.667 | 0.798 | 577.025 | 14.512 | 15.310 |
November | 11.125 | 0.091 | 660.667 | 34.608 | 34.699 |
December | 0.000 | 0.000 | 744.000 | 60.512 | 60.512 |
Annual Sum or Average | 2526.380 | 162.006 | 5111.326 | 287.098 | 449.104 |
Minimum of Months | 0.000 | 0.000 | 3.000 | 0.013 | 15.310 |
Maximum of Months | 673.364 | 54.316 | 744.000 | 65.060 | 65.060 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 39.053 | 39.053 |
February | 0.000 | 0.000 | 672.000 | 30.906 | 30.906 |
March | 0.000 | 0.000 | 724.500 | 21.670 | 21.670 |
April | 119.562 | 4.793 | 528.750 | 11.515 | 16.308 |
May | 227.802 | 6.166 | 290.229 | 2.592 | 8.758 |
June | 512.459 | 20.622 | 36.750 | 0.222 | 20.844 |
July | 694.289 | 35.688 | 0.000 | 0.000 | 35.688 |
August | 617.652 | 23.297 | 6.000 | 0.015 | 23.312 |
September | 350.635 | 9.366 | 116.625 | 0.675 | 10.041 |
October | 24.292 | 0.274 | 590.750 | 8.472 | 8.746 |
November | 11.625 | 0.122 | 650.250 | 20.404 | 20.525 |
December | 0.000 | 0.000 | 744.000 | 36.018 | 36.018 |
Annual Sum or Average | 2558.316 | 100.328 | 5103.854 | 171.541 | 271.869 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.746 |
Maximum of Months | 694.289 | 35.688 | 744.000 | 39.053 | 39.053 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 50.056 | 50.056 |
February | 0.000 | 0.000 | 672.000 | 39.243 | 39.243 |
March | 0.000 | 0.000 | 728.500 | 26.972 | 26.972 |
April | 136.377 | 7.385 | 513.792 | 14.248 | 21.633 |
May | 264.532 | 11.672 | 254.750 | 3.248 | 14.919 |
June | 528.995 | 33.036 | 50.500 | 0.380 | 33.416 |
July | 677.179 | 51.719 | 2.375 | 0.008 | 51.728 |
August | 613.535 | 34.948 | 13.000 | 0.065 | 35.012 |
September | 394.727 | 15.387 | 128.725 | 1.136 | 16.523 |
October | 37.412 | 0.536 | 579.888 | 10.741 | 11.277 |
November | 12.000 | 0.095 | 664.542 | 26.499 | 26.593 |
December | 0.000 | 0.000 | 744.000 | 46.404 | 46.404 |
Annual Sum or Average | 2664.757 | 154.777 | 5096.071 | 219.000 | 373.777 |
Minimum of Months | 0.000 | 0.000 | 2.375 | 0.008 | 11.277 |
Maximum of Months | 677.179 | 51.719 | 744.000 | 50.056 | 51.728 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 735.563 | 54.480 | 54.480 |
February | 2.250 | 0.024 | 653.042 | 41.532 | 41.555 |
March | 38.775 | 0.994 | 631.125 | 27.308 | 28.302 |
April | 186.833 | 11.169 | 431.083 | 15.058 | 26.227 |
May | 327.934 | 18.034 | 188.479 | 2.715 | 20.749 |
June | 578.524 | 39.132 | 19.071 | 0.154 | 39.286 |
July | 710.712 | 59.948 | 0.000 | 0.000 | 59.948 |
August | 656.102 | 44.848 | 2.250 | 0.008 | 44.856 |
September | 463.670 | 26.179 | 69.400 | 0.637 | 26.816 |
October | 138.833 | 4.850 | 367.125 | 8.497 | 13.347 |
November | 42.417 | 1.214 | 581.521 | 26.965 | 28.179 |
December | 0.000 | 0.000 | 740.825 | 51.012 | 51.012 |
Annual Sum or Average | 3146.051 | 206.392 | 4419.484 | 228.365 | 434.758 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 13.347 |
Maximum of Months | 710.712 | 59.948 | 740.825 | 54.480 | 59.948 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 731.917 | 24.423 | 24.423 |
February | 0.000 | 0.000 | 651.125 | 18.687 | 18.687 |
March | 28.375 | 0.229 | 629.287 | 12.002 | 12.231 |
April | 168.292 | 6.808 | 436.164 | 6.689 | 13.497 |
May | 315.463 | 9.673 | 153.992 | 0.901 | 10.574 |
June | 593.666 | 25.050 | 10.333 | 0.026 | 25.076 |
July | 730.975 | 39.940 | 0.000 | 0.000 | 39.940 |
August | 696.876 | 30.830 | 0.000 | 0.000 | 30.830 |
September | 505.947 | 18.413 | 32.896 | 0.109 | 18.522 |
October | 143.213 | 3.227 | 315.063 | 3.111 | 6.338 |
November | 49.854 | 1.020 | 541.167 | 11.571 | 12.591 |
December | 0.000 | 0.000 | 739.750 | 22.611 | 22.611 |
Annual Sum or Average | 3232.662 | 135.190 | 4241.693 | 100.130 | 235.319 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 6.338 |
Maximum of Months | 730.975 | 39.940 | 739.750 | 24.423 | 39.940 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 737.875 | 37.190 | 37.190 |
February | 0.000 | 0.000 | 661.750 | 28.346 | 28.346 |
March | 27.000 | 0.276 | 631.350 | 18.153 | 18.429 |
April | 180.951 | 9.944 | 431.301 | 9.975 | 19.919 |
May | 362.328 | 15.908 | 168.063 | 1.665 | 17.573 |
June | 594.343 | 37.516 | 18.375 | 0.121 | 37.637 |
July | 712.625 | 55.696 | 0.000 | 0.000 | 55.696 |
August | 669.990 | 42.367 | 2.750 | 0.008 | 42.375 |
September | 491.318 | 24.964 | 64.875 | 0.447 | 25.412 |
October | 126.767 | 3.986 | 368.313 | 5.594 | 9.580 |
November | 38.083 | 1.000 | 594.500 | 18.395 | 19.395 |
December | 0.000 | 0.000 | 741.833 | 34.653 | 34.653 |
Annual Sum or Average | 3203.405 | 191.657 | 4420.984 | 154.546 | 346.203 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 9.580 |
Maximum of Months | 712.625 | 55.696 | 741.833 | 37.190 | 55.696 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 58.084 | 58.084 |
February | 0.000 | 0.000 | 670.050 | 44.974 | 44.974 |
March | 14.500 | 0.136 | 687.846 | 29.800 | 29.936 |
April | 162.758 | 8.976 | 456.021 | 15.517 | 24.492 |
May | 305.747 | 15.756 | 210.798 | 3.002 | 18.758 |
June | 568.971 | 37.488 | 23.054 | 0.182 | 37.670 |
July | 709.629 | 57.716 | 0.000 | 0.000 | 57.716 |
August | 649.777 | 41.044 | 4.250 | 0.014 | 41.058 |
September | 416.060 | 19.641 | 91.667 | 0.866 | 20.507 |
October | 61.312 | 1.293 | 517.350 | 11.134 | 12.427 |
November | 19.208 | 0.290 | 626.938 | 29.792 | 30.082 |
December | 0.000 | 0.000 | 744.000 | 54.599 | 54.599 |
Annual Sum or Average | 2907.963 | 182.340 | 4775.972 | 247.964 | 430.303 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 12.427 |
Maximum of Months | 709.629 | 57.716 | 744.000 | 58.084 | 58.084 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 26.920 | 26.920 |
February | 0.000 | 0.000 | 668.000 | 21.058 | 21.058 |
March | 1.625 | 0.004 | 701.063 | 13.845 | 13.849 |
April | 136.250 | 5.399 | 475.000 | 7.102 | 12.501 |
May | 291.991 | 8.177 | 175.615 | 0.981 | 9.158 |
June | 593.837 | 23.829 | 11.850 | 0.028 | 23.857 |
July | 730.913 | 37.931 | 0.000 | 0.000 | 37.931 |
August | 694.962 | 27.498 | 0.000 | 0.000 | 27.498 |
September | 445.398 | 12.704 | 49.503 | 0.159 | 12.863 |
October | 52.354 | 0.633 | 498.021 | 4.651 | 5.284 |
November | 21.125 | 0.326 | 595.833 | 13.349 | 13.675 |
December | 0.000 | 0.000 | 744.000 | 25.105 | 25.105 |
Annual Sum or Average | 2968.455 | 116.501 | 4662.885 | 113.197 | 229.699 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 5.284 |
Maximum of Months | 730.913 | 37.931 | 744.000 | 26.920 | 37.931 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 40.941 | 40.941 |
February | 0.000 | 0.000 | 672.000 | 31.722 | 31.722 |
March | 0.000 | 0.000 | 701.542 | 20.597 | 20.597 |
April | 157.766 | 8.264 | 467.101 | 10.583 | 18.847 |
May | 337.646 | 14.186 | 180.396 | 1.762 | 15.948 |
June | 594.908 | 36.543 | 18.583 | 0.122 | 36.665 |
July | 712.792 | 54.153 | 0.000 | 0.000 | 54.153 |
August | 668.837 | 39.344 | 2.750 | 0.008 | 39.352 |
September | 463.795 | 19.240 | 74.937 | 0.511 | 19.751 |
October | 52.521 | 0.969 | 515.437 | 7.407 | 8.375 |
November | 22.000 | 0.313 | 626.083 | 20.877 | 21.190 |
December | 0.000 | 0.000 | 744.000 | 38.324 | 38.324 |
Annual Sum or Average | 3010.265 | 173.011 | 4746.830 | 172.853 | 345.864 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.375 |
Maximum of Months | 712.792 | 54.153 | 744.000 | 40.941 | 54.153 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 71.308 | 71.308 |
February | 0.000 | 0.000 | 667.250 | 55.349 | 55.349 |
March | 19.188 | 0.356 | 674.021 | 37.959 | 38.315 |
April | 157.650 | 11.036 | 467.625 | 20.910 | 31.946 |
May | 280.669 | 18.109 | 262.083 | 5.029 | 23.138 |
June | 522.961 | 41.802 | 46.792 | 0.501 | 42.303 |
July | 689.491 | 66.702 | 2.500 | 0.008 | 66.710 |
August | 613.275 | 47.337 | 12.844 | 0.087 | 47.425 |
September | 400.461 | 25.382 | 127.283 | 1.638 | 27.021 |
October | 88.333 | 3.379 | 486.733 | 13.820 | 17.199 |
November | 28.167 | 0.696 | 638.188 | 37.124 | 37.820 |
December | 0.000 | 0.000 | 744.000 | 66.419 | 66.419 |
Annual Sum or Average | 2800.194 | 214.799 | 4873.319 | 310.154 | 524.953 |
Minimum of Months | 0.000 | 0.000 | 2.500 | 0.008 | 17.199 |
Maximum of Months | 689.491 | 66.702 | 744.000 | 71.308 | 71.308 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 743.500 | 40.196 | 40.196 |
February | 0.000 | 0.000 | 667.950 | 31.378 | 31.378 |
March | 5.104 | 0.029 | 678.471 | 21.410 | 21.439 |
April | 142.660 | 7.276 | 485.312 | 11.838 | 19.114 |
May | 270.332 | 10.403 | 249.595 | 2.477 | 12.880 |
June | 540.344 | 28.448 | 29.458 | 0.182 | 28.631 |
July | 702.246 | 47.424 | 0.000 | 0.000 | 47.424 |
August | 645.348 | 34.081 | 4.884 | 0.013 | 34.094 |
September | 435.828 | 18.259 | 92.544 | 0.593 | 18.851 |
October | 88.400 | 2.096 | 454.312 | 6.998 | 9.095 |
November | 27.250 | 0.575 | 615.917 | 20.401 | 20.976 |
December | 0.000 | 0.000 | 744.000 | 37.163 | 37.163 |
Annual Sum or Average | 2857.511 | 148.590 | 4765.944 | 172.650 | 321.240 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 9.095 |
Maximum of Months | 702.246 | 47.424 | 744.000 | 40.196 | 47.424 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 51.346 | 51.346 |
February | 0.000 | 0.000 | 668.600 | 39.866 | 39.866 |
March | 3.625 | 0.012 | 681.838 | 26.905 | 26.917 |
April | 155.300 | 9.493 | 479.025 | 14.725 | 24.218 |
May | 300.216 | 14.928 | 232.438 | 3.119 | 18.047 |
June | 559.699 | 38.048 | 35.600 | 0.317 | 38.365 |
July | 695.095 | 59.162 | 1.500 | 0.004 | 59.166 |
August | 639.925 | 42.477 | 9.750 | 0.050 | 42.527 |
September | 437.724 | 22.852 | 107.750 | 1.033 | 23.885 |
October | 85.683 | 2.595 | 474.708 | 9.516 | 12.111 |
November | 25.292 | 0.577 | 637.750 | 26.639 | 27.216 |
December | 0.000 | 0.000 | 744.000 | 47.697 | 47.697 |
Annual Sum or Average | 2902.559 | 190.144 | 4816.958 | 221.217 | 411.361 |
Minimum of Months | 0.000 | 0.000 | 1.500 | 0.004 | 12.111 |
Maximum of Months | 695.095 | 59.162 | 744.000 | 51.346 | 59.166 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 75.325 | 75.325 |
February | 0.000 | 0.000 | 672.000 | 58.906 | 58.906 |
March | 7.417 | 0.045 | 701.408 | 40.532 | 40.577 |
April | 144.433 | 9.842 | 481.667 | 21.442 | 31.284 |
May | 272.239 | 17.291 | 269.680 | 5.169 | 22.460 |
June | 522.580 | 41.318 | 46.014 | 0.501 | 41.819 |
July | 689.991 | 65.841 | 2.350 | 0.007 | 65.847 |
August | 611.502 | 45.356 | 12.844 | 0.088 | 45.444 |
September | 370.338 | 21.116 | 143.469 | 1.833 | 22.948 |
October | 49.208 | 1.151 | 567.946 | 16.596 | 17.747 |
November | 14.375 | 0.188 | 659.208 | 40.035 | 40.223 |
December | 0.000 | 0.000 | 744.000 | 70.390 | 70.390 |
Annual Sum or Average | 2682.084 | 202.148 | 5044.585 | 330.823 | 532.971 |
Minimum of Months | 0.000 | 0.000 | 2.350 | 0.007 | 17.747 |
Maximum of Months | 689.991 | 65.841 | 744.000 | 75.325 | 75.325 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 43.395 | 43.395 |
February | 0.000 | 0.000 | 672.000 | 34.179 | 34.179 |
March | 0.000 | 0.000 | 717.083 | 23.553 | 23.553 |
April | 124.875 | 6.535 | 503.612 | 12.374 | 18.909 |
May | 262.122 | 9.876 | 259.459 | 2.587 | 12.463 |
June | 542.362 | 28.250 | 30.000 | 0.187 | 28.437 |
July | 702.496 | 46.943 | 0.000 | 0.000 | 46.943 |
August | 642.782 | 32.475 | 4.750 | 0.012 | 32.487 |
September | 395.083 | 14.472 | 109.319 | 0.698 | 15.171 |
October | 34.083 | 0.513 | 579.433 | 9.180 | 9.694 |
November | 14.750 | 0.219 | 646.083 | 22.649 | 22.868 |
December | 0.000 | 0.000 | 744.000 | 40.293 | 40.293 |
Annual Sum or Average | 2718.553 | 139.283 | 5009.741 | 189.109 | 328.393 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 9.694 |
Maximum of Months | 702.496 | 46.943 | 744.000 | 43.395 | 46.943 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 54.582 | 54.582 |
February | 0.000 | 0.000 | 672.000 | 42.690 | 42.690 |
March | 0.000 | 0.000 | 719.958 | 29.036 | 29.036 |
April | 141.125 | 8.499 | 495.500 | 15.222 | 23.721 |
May | 291.788 | 14.228 | 237.341 | 3.205 | 17.433 |
June | 559.496 | 37.507 | 36.750 | 0.319 | 37.827 |
July | 695.714 | 58.128 | 1.500 | 0.003 | 58.131 |
August | 639.851 | 40.589 | 9.625 | 0.050 | 40.639 |
September | 416.691 | 18.856 | 117.571 | 1.123 | 19.979 |
October | 43.417 | 0.791 | 576.337 | 11.566 | 12.357 |
November | 16.250 | 0.185 | 660.000 | 28.898 | 29.083 |
December | 0.000 | 0.000 | 744.000 | 50.868 | 50.868 |
Annual Sum or Average | 2804.331 | 178.783 | 5014.583 | 237.564 | 416.347 |
Minimum of Months | 0.000 | 0.000 | 1.500 | 0.003 | 12.357 |
Maximum of Months | 695.714 | 58.128 | 744.000 | 54.582 | 58.131 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6037.12 | 0.00 |
February | 0.00 | 4952.24 | 0.00 |
March | 0.00 | 2615.28 | 0.00 |
April | 0.00 | 1279.87 | 0.00 |
May | 0.00 | 93.87 | 0.00 |
June | 0.00 | 1.77 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 4.57 | 0.00 |
October | 0.00 | 537.58 | 0.00 |
November | 0.00 | 2770.24 | 0.00 |
December | 0.00 | 5454.25 | 0.00 |
Annual Sum or Average | 0.00 | 1965.03 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6037.12 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6353.49 | 0.00 |
February | 0.00 | 5489.33 | 0.00 |
March | 0.00 | 3412.36 | 0.00 |
April | 0.00 | 1963.76 | 0.00 |
May | 0.00 | 413.67 | 0.00 |
June | 0.00 | 35.31 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 2.22 | 0.00 |
September | 0.00 | 92.49 | 0.00 |
October | 0.00 | 1075.57 | 0.00 |
November | 0.00 | 3309.23 | 0.00 |
December | 0.00 | 5828.65 | 0.00 |
Annual Sum or Average | 0.00 | 2316.14 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6353.49 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 7977.13 | 0.00 |
February | 0.00 | 6848.68 | 0.00 |
March | 0.00 | 4190.93 | 0.00 |
April | 0.00 | 2392.12 | 0.00 |
May | 0.00 | 530.44 | 0.00 |
June | 0.00 | 65.33 | 0.00 |
July | 0.00 | 1.57 | 0.00 |
August | 0.00 | 10.79 | 0.00 |
September | 0.00 | 178.83 | 0.00 |
October | 0.00 | 1464.24 | 0.00 |
November | 0.00 | 4262.37 | 0.00 |
December | 0.00 | 7366.48 | 0.00 |
Annual Sum or Average | 0.00 | 2921.95 | 0.00 |
Minimum of Months | 0.00 | 1.57 | 0.00 |
Maximum of Months | 0.00 | 7977.13 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 8524.57 | 0.00 |
February | 0.00 | 7396.03 | 0.00 |
March | 0.00 | 4651.78 | 0.00 |
April | 0.00 | 2548.96 | 0.00 |
May | 0.00 | 626.31 | 0.00 |
June | 0.00 | 71.99 | 0.00 |
July | 0.00 | 1.64 | 0.00 |
August | 0.00 | 12.35 | 0.00 |
September | 0.00 | 226.63 | 0.00 |
October | 0.00 | 1901.39 | 0.00 |
November | 0.00 | 4685.70 | 0.00 |
December | 0.00 | 7928.63 | 0.00 |
Annual Sum or Average | 0.00 | 3194.89 | 0.00 |
Minimum of Months | 0.00 | 1.64 | 0.00 |
Maximum of Months | 0.00 | 8524.57 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6984.58 | 0.00 |
February | 0.00 | 6119.79 | 0.00 |
March | 0.00 | 3875.70 | 0.00 |
April | 0.00 | 2128.03 | 0.00 |
May | 0.00 | 463.49 | 0.00 |
June | 0.00 | 41.01 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 2.76 | 0.00 |
September | 0.00 | 124.72 | 0.00 |
October | 0.00 | 1515.19 | 0.00 |
November | 0.00 | 3770.82 | 0.00 |
December | 0.00 | 6441.71 | 0.00 |
Annual Sum or Average | 0.00 | 2605.69 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6984.58 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 8605.19 | 0.00 |
February | 0.00 | 7469.19 | 0.00 |
March | 0.00 | 4636.85 | 0.00 |
April | 0.00 | 2531.10 | 0.00 |
May | 0.00 | 558.30 | 0.00 |
June | 0.00 | 67.52 | 0.00 |
July | 0.00 | 1.44 | 0.00 |
August | 0.00 | 11.09 | 0.00 |
September | 0.00 | 201.81 | 0.00 |
October | 0.00 | 1846.57 | 0.00 |
November | 0.00 | 4707.25 | 0.00 |
December | 0.00 | 7977.34 | 0.00 |
Annual Sum or Average | 0.00 | 3197.56 | 0.00 |
Minimum of Months | 0.00 | 1.44 | 0.00 |
Maximum of Months | 0.00 | 8605.19 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5666.38 | 0.00 |
February | 0.00 | 4782.42 | 0.00 |
March | 0.00 | 2840.26 | 0.00 |
April | 0.00 | 1618.37 | 0.00 |
May | 0.00 | 282.33 | 0.00 |
June | 0.00 | 16.57 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.83 | 0.00 |
September | 0.00 | 68.50 | 0.00 |
October | 0.00 | 883.70 | 0.00 |
November | 0.00 | 2898.02 | 0.00 |
December | 0.00 | 5305.63 | 0.00 |
Annual Sum or Average | 0.00 | 2017.27 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 5666.38 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4136.87 | 0.00 |
February | 0.00 | 3504.53 | 0.00 |
March | 0.00 | 2033.01 | 0.00 |
April | 0.00 | 1170.74 | 0.00 |
May | 0.00 | 152.68 | 0.00 |
June | 0.00 | 4.53 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 19.08 | 0.00 |
October | 0.00 | 526.99 | 0.00 |
November | 0.00 | 2025.25 | 0.00 |
December | 0.00 | 3829.92 | 0.00 |
Annual Sum or Average | 0.00 | 1440.49 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4136.87 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5753.21 | 0.00 |
February | 0.00 | 4854.90 | 0.00 |
March | 0.00 | 2808.19 | 0.00 |
April | 0.00 | 1594.60 | 0.00 |
May | 0.00 | 257.54 | 0.00 |
June | 0.00 | 19.30 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 1.21 | 0.00 |
September | 0.00 | 71.49 | 0.00 |
October | 0.00 | 865.32 | 0.00 |
November | 0.00 | 2940.58 | 0.00 |
December | 0.00 | 5360.71 | 0.00 |
Annual Sum or Average | 0.00 | 2030.54 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 5753.21 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6260.59 | 0.00 |
February | 0.00 | 5366.86 | 0.00 |
March | 0.00 | 3212.02 | 0.00 |
April | 0.00 | 1728.20 | 0.00 |
May | 0.00 | 323.53 | 0.00 |
June | 0.00 | 20.30 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 1.53 | 0.00 |
September | 0.00 | 96.45 | 0.00 |
October | 0.00 | 1200.10 | 0.00 |
November | 0.00 | 3318.12 | 0.00 |
December | 0.00 | 5885.00 | 0.00 |
Annual Sum or Average | 0.00 | 2269.94 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6260.59 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4737.10 | 0.00 |
February | 0.00 | 4102.44 | 0.00 |
March | 0.00 | 2436.24 | 0.00 |
April | 0.00 | 1291.33 | 0.00 |
May | 0.00 | 172.60 | 0.00 |
June | 0.00 | 5.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 28.99 | 0.00 |
October | 0.00 | 818.47 | 0.00 |
November | 0.00 | 2427.30 | 0.00 |
December | 0.00 | 4417.56 | 0.00 |
Annual Sum or Average | 0.00 | 1691.75 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4737.10 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6346.12 | 0.00 |
February | 0.00 | 5443.97 | 0.00 |
March | 0.00 | 3192.66 | 0.00 |
April | 0.00 | 1695.13 | 0.00 |
May | 0.00 | 273.11 | 0.00 |
June | 0.00 | 19.60 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 1.20 | 0.00 |
September | 0.00 | 81.78 | 0.00 |
October | 0.00 | 1148.09 | 0.00 |
November | 0.00 | 3344.02 | 0.00 |
December | 0.00 | 5940.48 | 0.00 |
Annual Sum or Average | 0.00 | 2275.61 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 6346.12 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 8630.42 | 0.00 |
February | 0.00 | 7416.64 | 0.00 |
March | 0.00 | 4594.17 | 0.00 |
April | 0.00 | 2615.12 | 0.00 |
May | 0.00 | 608.67 | 0.00 |
June | 0.00 | 62.65 | 0.00 |
July | 0.00 | 0.97 | 0.00 |
August | 0.00 | 10.57 | 0.00 |
September | 0.00 | 204.91 | 0.00 |
October | 0.00 | 1672.58 | 0.00 |
November | 0.00 | 4642.92 | 0.00 |
December | 0.00 | 8038.65 | 0.00 |
Annual Sum or Average | 0.00 | 3188.14 | 0.00 |
Minimum of Months | 0.00 | 0.97 | 0.00 |
Maximum of Months | 0.00 | 8630.42 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 7065.48 | 0.00 |
February | 0.00 | 6106.30 | 0.00 |
March | 0.00 | 3763.38 | 0.00 |
April | 0.00 | 2150.23 | 0.00 |
May | 0.00 | 435.44 | 0.00 |
June | 0.00 | 33.13 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 2.30 | 0.00 |
September | 0.00 | 107.62 | 0.00 |
October | 0.00 | 1230.09 | 0.00 |
November | 0.00 | 3705.45 | 0.00 |
December | 0.00 | 6532.26 | 0.00 |
Annual Sum or Average | 0.00 | 2577.44 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 7065.48 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 8721.43 | 0.00 |
February | 0.00 | 7496.99 | 0.00 |
March | 0.00 | 4569.98 | 0.00 |
April | 0.00 | 2584.44 | 0.00 |
May | 0.00 | 529.78 | 0.00 |
June | 0.00 | 55.63 | 0.00 |
July | 0.00 | 0.64 | 0.00 |
August | 0.00 | 8.50 | 0.00 |
September | 0.00 | 181.36 | 0.00 |
October | 0.00 | 1616.35 | 0.00 |
November | 0.00 | 4675.62 | 0.00 |
December | 0.00 | 8101.59 | 0.00 |
Annual Sum or Average | 0.00 | 3191.30 | 0.00 |
Minimum of Months | 0.00 | 0.64 | 0.00 |
Maximum of Months | 0.00 | 8721.43 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 9171.61 | 0.00 |
February | 0.00 | 7940.84 | 0.00 |
March | 0.00 | 4935.17 | 0.00 |
April | 0.00 | 2697.80 | 0.00 |
May | 0.00 | 629.39 | 0.00 |
June | 0.00 | 63.08 | 0.00 |
July | 0.00 | 0.82 | 0.00 |
August | 0.00 | 10.67 | 0.00 |
September | 0.00 | 230.59 | 0.00 |
October | 0.00 | 2020.68 | 0.00 |
November | 0.00 | 5037.16 | 0.00 |
December | 0.00 | 8570.69 | 0.00 |
Annual Sum or Average | 0.00 | 3421.13 | 0.00 |
Minimum of Months | 0.00 | 0.82 | 0.00 |
Maximum of Months | 0.00 | 9171.61 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 7627.75 | 0.00 |
February | 0.00 | 6651.56 | 0.00 |
March | 0.00 | 4140.06 | 0.00 |
April | 0.00 | 2247.47 | 0.00 |
May | 0.00 | 454.80 | 0.00 |
June | 0.00 | 33.93 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 2.18 | 0.00 |
September | 0.00 | 126.80 | 0.00 |
October | 0.00 | 1613.69 | 0.00 |
November | 0.00 | 4113.74 | 0.00 |
December | 0.00 | 7082.54 | 0.00 |
Annual Sum or Average | 0.00 | 2823.16 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 7627.75 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 9271.26 | 0.00 |
February | 0.00 | 8028.20 | 0.00 |
March | 0.00 | 4932.07 | 0.00 |
April | 0.00 | 2671.78 | 0.00 |
May | 0.00 | 544.46 | 0.00 |
June | 0.00 | 56.04 | 0.00 |
July | 0.00 | 0.55 | 0.00 |
August | 0.00 | 8.47 | 0.00 |
September | 0.00 | 197.06 | 0.00 |
October | 0.00 | 1964.64 | 0.00 |
November | 0.00 | 5072.19 | 0.00 |
December | 0.00 | 8640.29 | 0.00 |
Annual Sum or Average | 0.00 | 3427.17 | 0.00 |
Minimum of Months | 0.00 | 0.55 | 0.00 |
Maximum of Months | 0.00 | 9271.26 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.12 |
May | 0.00 | 0.00 | 0.19 |
June | 0.00 | 0.00 | 0.40 |
July | 0.00 | 0.00 | 0.59 |
August | 0.00 | 0.00 | 0.46 |
September | 0.00 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.02 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.18 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.59 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.12 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.30 |
August | 0.00 | 0.00 | 0.19 |
September | 0.00 | 0.00 | 0.08 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.30 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.39 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.32 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.06 |
June | 0.00 | 0.00 | 0.19 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.33 |
September | 0.00 | 0.00 | 0.18 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.45 |
August | 0.00 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.45 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.22 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.29 |
July | 0.00 | 0.00 | 0.46 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.46 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:37:21
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1476.46 | 1099.26 |
February | 0.00 | 0.00 | 1510.34 | 1015.67 |
March | 0.00 | 0.00 | 1473.04 | 1096.72 |
April | 0.00 | 0.00 | 1380.97 | 995.00 |
May | 0.00 | 0.00 | 1245.92 | 927.62 |
June | 0.00 | 0.00 | 1113.94 | 802.61 |
July | 0.00 | 0.00 | 1021.43 | 760.48 |
August | 0.00 | 0.00 | 981.79 | 730.97 |
September | 0.00 | 0.00 | 1020.27 | 735.12 |
October | 0.00 | 0.00 | 1117.17 | 831.76 |
November | 0.00 | 0.00 | 1248.18 | 899.32 |
December | 0.00 | 0.00 | 1382.78 | 1029.52 |
Annual Sum or Average | 0.00 | 0.00 | 1246.15 | 10924.05 |
Minimum of Months | 0.00 | 0.00 | 981.79 | 730.97 |
Maximum of Months | 0.00 | 0.00 | 1510.34 | 1099.26 |