Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39

Tabular Output Report in Format: HTML

Building: MF+CZ5BWH+USA_ID_Boise.Air.Terminal.726810+gasfurnace+crawlspace+IECC_2009

Environment: ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810

Simulation Timestamp: 2019-02-14 08:39:35


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1172950.03 30.07 54.28
Net Site Energy 1172950.03 30.07 54.28
Total Source Energy 2126517.17 54.52 98.40
Net Source Energy 2126517.17 54.52 98.40


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 284451.80 0.00 0.00 0.00 0.00
Cooling 58430.16 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 263405.37 163973.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28499.77 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 314040.48 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 410484.56 762465.47 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 284451.80 0.00 0.00 0.00 0.00
Cooling General 58430.16 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 143183.64 17261.25 0.00 0.00 0.00 0.00
  IECC_adj 59304.86 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 28499.77 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 314040.48 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 4.02 27.70 0.00 0.00 0.00 19.42
Other 12.19 7.59 0.00 0.00 0.00 0.00
Total 19.00 35.28 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 2.23 15.34 0.00 0.00 0.00 10.76
Other 6.75 4.20 0.00 0.00 0.00 0.00
Total 10.52 19.55 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 410484.560 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 410484.560 100.00
     
Total On-Site and Utility Electric Sources 410484.560 100.00
Total Electricity End Uses 410484.560 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 30.75
Time Not Comfortable Based on Simple ASHRAE 55-2004 250.50


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39
RunPeriod ANNUAL
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Latitude [deg] 43.62
Longitude [deg] -116.2
Elevation [ft] 2299.98
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 4.4634
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 4.4634
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.4163 1083.48 2.4729
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 4.4634
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 31-JUL-19:15 13-JAN-08:15 - - - 01-JAN-08:15
Heating 0.00 228.04 0.00 0.00 0.00 0.00
Cooling 52.52 0.00 0.00 0.00 0.00 0.00
Interior Lighting 16.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.53 0.00 0.00 0.00 0.00 0.00
Interior Equipment 42.84 20.12 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 13.60 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 151.33 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 127.74 399.50 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 228.04 0.00 0.00 0.00 0.00
Cooling General 52.52 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 16.25 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.63 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.14 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.51 9.86 0.00 0.00 0.00 0.00
  gas_range 0.00 8.49 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 23.39 1.77 0.00 0.00 0.00 0.00
  IECC_adj 9.69 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 13.60 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 151.33 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 308345.75 0.00 0.00 0.00
Cooling 185048.31 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 834204.80 177746.94 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 90258.76 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 340419.88 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1300004.60 826512.57 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 14.27 0.00 0.00 0.00
Cooling 8.56 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.18 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 60.16 38.25 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 14.27 0.00 0.00 0.00
Cooling 8.56 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 38.60 8.23 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.18 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.75 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 60.16 38.25 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 2.66 0.00 2.66 Wetbulb [F] 452.78 120.00
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 98.06 30.06 64.22 Wetbulb [F] 826.81 330.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.330 0.882              
North Total or Average           531.68 0.350 0.330 0.882              
Non-North Total or Average           1595.05 0.350 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
None          


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   26537.50 21194.31 5343.19 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7809.93 6237.44 1572.49 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9619.50 7682.66 1936.84 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14484.19 11567.87 2916.31 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7260.85 5798.92 1461.93 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9277.54 7409.56 1867.98 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14731.59 11765.46 2966.13 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7738.41 6180.32 1558.09 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9385.76 7495.99 1889.77 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14193.02 11335.33 2857.69 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7252.92 5792.58 1460.34 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9178.17 7330.20 1847.98 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16636.75 13287.03 3349.72 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9659.68 7714.76 1944.93 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11178.12 8927.46 2250.66 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16565.73 13230.31 3335.42 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9587.67 7657.24 1930.43 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11081.88 8850.60 2231.28 0.80 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.2 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.6 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.9 3.19 10.89 11.54 11.07
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   6562.70 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   13653.15 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   16374.67 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   16379.41 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   13653.71 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   16371.90 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   13435.75 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   10724.25 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   13439.62 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   13439.39 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   10724.03 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   13436.63 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   17683.21 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   14961.62 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   17688.11 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   17684.16 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   14960.50 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   17685.03 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 995.45 498.52 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 292.96 146.71 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 360.84 180.71 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 543.32 272.09 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 272.36 136.40 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 348.01 174.28 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 552.60 276.74 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 290.27 145.37 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 352.07 176.31 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 532.39 266.62 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 272.06 136.25 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 344.28 172.41 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 624.06 312.53 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 362.34 181.46 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 419.30 209.98 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 621.40 311.19 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 359.64 180.11 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 415.69 208.18 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 36002.06 0.80 0.83 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 21509.12 21509.12 17.92 995.446 995.446 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00796 89.72 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6330.07 6330.07 5.27 292.958 292.958 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00789 88.59 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7797.07 7797.07 6.49 360.836 360.836 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.99 0.00778 98.06 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11739.70 11739.70 9.78 543.315 543.315 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00792 89.72 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5885.03 5885.03 4.90 272.361 272.361 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00790 87.46 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7519.62 7519.62 6.26 348.009 348.009 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00779 88.89 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11940.10 11940.10 9.95 552.596 552.596 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00800 88.59 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6272.04 6272.04 5.22 290.275 290.275 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00802 86.34 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7607.46 7607.46 6.34 352.069 352.069 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00787 98.06 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11503.59 11503.59 9.58 532.393 532.393 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00800 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5878.55 5878.55 4.90 272.064 272.064 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00802 86.34 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7439.04 7439.04 6.20 344.282 344.282 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00787 88.89 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8982.07 8982.07 7.48 415.691 415.691 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00790 89.72 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9060.09 9060.09 7.55 419.302 419.302 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 74.98 74.98 0.00789 90.85 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 13484.37 13484.37 11.23 624.060 624.060 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00795 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 7770.94 7770.94 6.47 359.642 359.642 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00794 86.34 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7829.31 7829.31 6.52 362.344 362.344 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00793 87.46 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 13426.80 13426.80 11.18 621.396 621.396 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00794 88.59 0.00627 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3507.87 3507.87 2.92 69.411 69.411 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00383 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10703.51 10703.51 8.92 211.758 211.758 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00575 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13465.32 13465.32 11.22 266.390 266.390 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00597 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13470.14 13470.14 11.22 266.486 266.486 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00597 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10704.07 10704.07 8.92 211.769 211.769 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00575 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13462.51 13462.51 11.21 266.335 266.335 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00597 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10482.68 10482.68 8.73 207.409 207.409 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00621 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 7731.03 7731.03 6.44 152.970 152.970 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00596 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10486.61 10486.61 8.73 207.487 207.487 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00621 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10486.37 10486.37 8.73 207.482 207.482 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00621 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7730.80 7730.80 6.44 152.966 152.966 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00596 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10483.57 10483.57 8.73 207.427 207.427 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.98 0.00621 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 14795.05 14795.05 12.32 292.697 292.697 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00610 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 14798.18 14798.18 12.33 292.759 292.759 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00610 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 14793.20 14793.20 12.32 292.661 292.661 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00610 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12030.18 12030.18 10.02 238.005 238.005 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00592 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12031.32 12031.32 10.02 238.028 238.028 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.98 0.00592 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 14794.17 14794.17 12.32 292.680 292.680 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 11:15:00 72.00 71.97 0.00610 2.66 0.00098 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 995.45 995.45 69.41 69.41
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.96 292.96 211.76 211.76
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 360.84 360.84 266.39 266.39
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 543.32 543.32 266.49 266.49
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 272.36 272.36 211.77 211.77
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 348.01 348.01 266.33 266.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 552.60 552.60 207.41 207.41
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 290.27 290.27 152.97 152.97
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 352.07 352.07 207.49 207.49
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 532.39 532.39 207.48 207.48
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 272.06 272.06 152.97 152.97
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 344.28 344.28 207.43 207.43
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 624.06 624.06 292.66 292.66
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 362.34 362.34 238.03 238.03
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 419.30 419.30 292.76 292.76
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 621.40 621.40 292.68 292.68
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 359.64 359.64 238.01 238.01
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 415.69 415.69 292.70 292.70


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1001.75 5996.00 27.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 443.00 6160.50 6.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1093.25 5886.75 66.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 906.25 6547.75 100.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 269.00 6735.00 11.25
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 869.00 6288.75 89.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1244.75 5724.50 24.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 685.25 5635.50 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1290.75 5525.25 25.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1025.50 6208.00 38.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 439.50 6207.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1009.75 5934.25 32.50
LIVING_UNIT3_BACKROW_TOPFLOOR 1329.75 6049.00 216.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1433.25 5826.25 173.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 1387.50 6105.00 165.50
LIVING_UNIT2_BACKROW_TOPFLOOR 726.50 6369.00 36.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 846.00 6068.75 24.50
LIVING_UNIT1_BACKROW_TOPFLOOR 1345.25 6346.25 239.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 1965.00 6998.75 250.50
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 8.75 0.00 8.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 16.00 0.00 16.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 15.75 0.00 15.75
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 17.00 0.00 17.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 20.00 0.00 20.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 4.75 0.00 4.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 14.00 0.00 14.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 11.75 0.00 11.75
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 12.25 0.00 12.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 14.75 0.00 14.75
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 13.25 0.00 13.25
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 3.25 0.00 3.25
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 16.75 0.00 16.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 17.25 0.00 17.25
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 15.00 0.00 15.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 16.00 0.00 16.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 15.25 0.00 15.25
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 15.00 0.00 15.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 30.75 0.00 30.75
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.274 0.000 0.277
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.236 0.000 0.276
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.268 0.000 0.276
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.267 0.000 0.276
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.235 0.000 0.276
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.268 0.000 0.276
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.276
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.086 0.000 0.276
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.276
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.117 0.000 0.276
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.085 0.000 0.276
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.276
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.236 0.000 0.276
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.236 0.000 0.276
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1878
Defaulted Fields 500
Fields with Defaults 4912
Autosized Fields 288
Autosizable Fields 396
Autocalculated Fields 98
Autocalculatable Fields 286



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
Electricity:Building 91754.37 7056.43 02-JAN-03:15 17558.18 01-JAN-20:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5097.47 392.02 02-JAN-03:15 975.45 01-JAN-20:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 77145.04 6525.11 02-JAN-04:15 12799.44 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:15 291.20 01-JAN-11:15
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
gas_mels:InteriorEquipment:Electricity 41935.01 3663.85 01-JAN-09:15 7086.44 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 17368.96 1517.52 01-JAN-09:15 2935.11 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.84 362.51 02-JAN-04:15 711.08 01-JAN-20:15
Fans:Electricity 8346.89 137.67 03-JUN-00:15 3985.85 12-JUL-17:45
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
ElectricityPurchased:Plant 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
Cogeneration:ElectricityPurchased 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
ElectricityNet:Plant 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
Cogeneration:ElectricityNet 120220.97 8185.81 19-JUN-03:15 37411.51 31-JUL-19:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 25459.67 510.87 01-APR-00:15 19698.88 31-JUL-18:00
General:Fans:Electricity 8346.89 137.67 03-JUN-00:15 3985.85 12-JUL-17:45
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:Electricity 17112.78 0.00 01-JAN-01:00 15713.03 31-JUL-18:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 7624.65 2644.47 07-APR-03:30 399213.86 13-JAN-08:15
Gas:Building 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas 1639.73 2644.47 02-JAN-03:15 43735.22 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
gas_dryer:InteriorEquipment:Gas 792.69 403.80 02-JAN-03:15 20254.25 01-JAN-11:15
gas_range:InteriorEquipment:Gas 674.43 651.88 01-JAN-02:15 27685.38 01-JAN-17:15
gas_mels:InteriorEquipment:Gas 172.61 1507.04 01-JAN-09:15 2914.85 01-JAN-20:15
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.10 146.92 02-JAN-03:15 2429.73 01-JAN-17:15
Gas:Plant 3140.40 0.00 01-JAN-00:15 151830.46 12-FEB-08:45
WaterSystems:Gas 3140.40 0.00 01-JAN-00:15 151830.46 12-FEB-08:45
Water Heater:WaterSystems:Gas 3140.40 0.00 01-JAN-00:15 151830.46 12-FEB-08:45
Gas:HVAC 2844.52 0.00 03-MAR-16:45 227878.13 13-JAN-08:15
Heating:Gas 2844.52 0.00 03-MAR-16:45 227878.13 13-JAN-08:15


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 04-JAN-02:30 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
PlantLoopHeatingDemand:Plant 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
WaterSystems:PlantLoopHeatingDemand 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1118427.40 15140.82 18-JUN-02:45 416963.00 13-JAN-08:15
EnergyTransfer:Building 467401.04 6426.65 15-MAY-24:00 191386.01 13-JAN-08:15
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 238260.53 0.00 03-MAR-16:45 191386.01 13-JAN-08:15
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 229140.51 0.00 01-JAN-01:00 177474.91 20-JUL-18:15
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 67099.65 0.00 01-JAN-01:00 22358.98 20-JUL-18:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.45 0.00 01-JAN-00:15 2997.28 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 67055.20 0.00 01-JAN-01:00 22358.98 20-JUL-18:15
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 18249.81 0.00 06-JAN-14:45 9907.00 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10902.86 0.00 06-JAN-14:45 9907.00 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7346.95 0.00 01-JAN-00:15 6668.98 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25682.15 0.00 04-FEB-12:15 12553.11 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15275.05 0.00 04-FEB-12:15 12553.11 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10407.09 0.00 01-JAN-00:15 8096.93 04-AUG-18:15
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 27175.52 0.00 05-FEB-16:15 12618.73 13-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18217.66 0.00 05-FEB-16:15 12618.73 13-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8957.85 0.00 01-JAN-00:15 12361.11 23-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 19450.99 0.00 10-FEB-17:15 10004.39 13-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13908.45 0.00 10-FEB-17:15 10004.39 13-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5542.54 0.00 01-JAN-00:15 6277.24 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 26250.16 0.00 03-MAR-16:45 12639.20 13-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 17718.45 0.00 03-MAR-16:45 12639.20 13-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8531.71 0.00 01-JAN-00:15 8106.51 22-JUL-09:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21845.67 0.00 01-JAN-15:45 12547.72 14-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9585.02 0.00 01-JAN-15:45 9693.26 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12260.64 0.00 01-JAN-00:15 12547.72 14-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 15048.16 0.00 06-JAN-12:45 7093.42 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6386.13 0.00 06-JAN-12:45 7093.42 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8662.03 0.00 01-JAN-00:15 6712.46 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21986.55 0.00 06-JAN-13:45 9731.67 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10205.60 0.00 06-JAN-13:45 9731.67 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11780.94 0.00 01-JAN-00:15 7997.42 22-JUL-09:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22598.81 0.00 03-FEB-16:45 12120.22 14-JUL-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12639.60 0.00 03-FEB-16:45 9766.54 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9959.20 0.00 01-JAN-00:15 12120.22 14-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 15123.86 0.00 01-FEB-19:45 7156.17 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8494.63 0.00 01-FEB-19:45 7156.17 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6629.24 0.00 01-JAN-00:15 6294.05 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21986.06 0.00 10-FEB-17:15 9771.59 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12263.80 0.00 10-FEB-17:15 9771.59 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9722.26 0.00 01-JAN-00:15 8039.58 22-JUL-09:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 29949.83 0.00 10-FEB-18:15 13827.17 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 19360.92 0.00 10-FEB-18:15 13827.17 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 10588.91 0.00 01-JAN-00:15 9452.76 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 28914.08 0.00 04-FEB-14:15 13795.68 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 17192.77 0.00 04-FEB-14:15 13795.68 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 11721.31 0.00 01-JAN-00:15 9534.77 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 29847.80 0.00 23-JAN-15:15 14125.40 20-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 17578.53 0.00 23-JAN-15:15 13776.28 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 12269.27 0.00 01-JAN-00:15 14125.40 20-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 23216.44 0.00 10-FEB-17:15 11204.55 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 15439.81 0.00 10-FEB-17:15 11204.55 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 7776.64 0.00 01-JAN-00:15 8295.96 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 21985.83 0.00 23-JAN-15:30 11148.44 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 13124.50 0.00 23-JAN-15:30 11148.44 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 8861.33 0.00 01-JAN-00:15 8358.40 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 30989.69 0.00 05-FEB-16:30 14084.44 14-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 19922.30 0.00 05-FEB-16:30 13822.90 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 11067.40 0.00 01-JAN-00:15 14084.44 14-JUL-18:30
EnergyTransfer:Plant 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
WaterSystems:EnergyTransfer 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 173002.32 1435.19 14-AUG-02:30 46097.53 11-FEB-08:45
EnergyTransfer:HVAC 478024.04 6916.68 03-JUN-00:15 193754.85 12-JUL-19:45
HeatingCoils:EnergyTransfer 227561.44 0.00 03-MAR-16:45 182302.50 13-JAN-08:15
CoolingCoils:EnergyTransfer 250462.59 0.00 01-JAN-01:00 193754.85 12-JUL-19:45



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 44.451 -5584.19 0.000 0.000 2876.944 2771.241 14528.036 9774.851 0.000 775.250 63642.677 0.000 -7001.22 0.000 -20357.12 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 10902.746 -611.84 0.000 0.000 3047.256 2771.241 14528.036 4360.084 0.000 730.444 0.000 0.000 -2680.53 0.000 -17574.40 -8737.94
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 15274.900 -866.67 0.000 0.000 3057.419 2771.241 14528.036 9953.028 0.000 774.944 0.000 0.000 -6374.82 0.000 -18707.98 -10869.72
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 18217.502 -745.99 0.000 0.000 3067.329 2771.241 14528.036 6769.525 0.000 774.301 0.000 0.000 -6851.65 0.000 -18532.48 -11785.96
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 13908.326 -461.57 0.000 0.000 3062.059 2771.241 14528.036 1058.161 0.000 730.396 0.000 0.000 -2871.12 0.000 -17412.93 -10231.64
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 17718.299 -710.50 0.000 0.000 3067.364 2771.241 14528.036 6759.999 0.000 775.514 0.000 0.000 -6569.75 0.000 -18585.44 -11933.58
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 9584.914 -1021.04 0.000 0.000 3032.364 2771.241 14528.036 9852.507 0.000 565.444 0.000 0.000 -6811.46 0.000 -13423.82 -7838.59
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 6386.053 -721.35 0.000 0.000 3018.793 2771.241 14528.036 4340.706 0.000 521.692 0.000 0.000 -2743.27 0.000 -12322.04 -7839.18
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 10205.491 -981.09 0.000 0.000 3036.058 2771.241 14528.036 9899.009 0.000 565.609 0.000 0.000 -6522.29 0.000 -13438.38 -9263.87
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 12639.483 -829.38 0.000 0.000 3047.610 2771.241 14528.036 6735.593 0.000 565.429 0.000 0.000 -7006.69 0.000 -13296.37 -10025.14
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 8494.548 -552.07 0.000 0.000 3037.636 2771.241 14528.036 1047.824 0.000 521.680 0.000 0.000 -2937.73 0.000 -12187.30 -8646.70
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 12263.688 -809.65 0.000 0.000 3048.448 2771.241 14528.036 6716.938 0.000 566.071 0.000 0.000 -6716.01 0.000 -13334.79 -10121.38
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 19360.756 -881.82 0.000 0.000 3060.879 2771.241 14528.036 6737.367 0.000 769.273 0.000 0.000 -6674.69 0.000 -18664.31 -11299.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 17192.605 -976.12 0.000 0.000 3053.843 2771.241 14528.036 9948.547 0.000 769.176 0.000 0.000 -6461.90 0.000 -18749.76 -11330.52
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 17578.362 -1021.75 0.000 0.000 3054.419 2771.241 14528.036 9911.080 0.000 769.261 0.000 0.000 -6701.94 0.000 -18700.40 -10940.81
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 15439.677 -647.62 0.000 0.000 3054.564 2771.241 14528.036 1051.626 0.000 725.757 0.000 0.000 -2910.41 0.000 -17505.82 -9378.04
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 13124.378 -737.95 0.000 0.000 3045.416 2771.241 14528.036 4360.781 0.000 725.653 0.000 0.000 -2707.06 0.000 -17602.57 -9384.55
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 19922.127 -921.67 0.000 0.000 3060.941 2771.241 14528.036 6738.281 0.000 769.402 0.000 0.000 -6947.57 0.000 -18619.93 -11155.15
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9122.032 56140.874 0.000 0.000 0.000 -65262.91 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4625.599 42680.122 0.000 0.000 0.000 -47305.72 -0.52
Total Facility 0.000 0.000 238258.305 -19082.25 0.000 0.000 54729.343 49882.340 261504.651 116015.905 0.000 26142.925 162463.674 0.000 -97490.11 0.000 -411584.47 -170782.96


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20-JUL-18:08 0.00 0.00 0.00 -1.9 0.00 0.00 426.99 813.96 2666.18 8197.88 0.00 1642.49 8672.83 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.6 0.00 0.00 422.93 902.05 2167.29 84.37 0.00 836.43 2345.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 04-AUG-18:08 0.00 0.00 0.00 -0.7 0.00 0.00 426.42 813.96 2666.18 1193.45 0.00 1724.92 1292.34 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23-JUL-18:25 0.00 0.00 0.00 -1.0 0.00 0.00 427.02 813.96 2698.15 8328.67 0.00 1471.41 0.00 0.00 0.00 0.00 0.00 -1377.6
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.5 0.00 0.00 421.13 902.05 2167.29 86.65 0.00 828.40 1881.47 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 22-JUL-09:17 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1603.33 7152.46 0.00 713.60 0.00 0.00 0.00 0.00 0.00 -1594.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14-JUL-18:33 0.00 0.00 0.00 -1.0 0.00 0.00 426.46 813.96 2666.18 7039.26 0.00 1042.37 583.43 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.6 0.00 0.00 425.88 902.05 2167.29 43.17 0.00 510.70 2711.73 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21-JUL-20:17 0.00 0.00 0.00 -0.7 0.00 0.00 426.28 902.05 2167.29 327.61 0.00 837.34 3364.88 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 14-JUL-18:48 0.00 0.00 0.00 -1.0 0.00 0.00 426.60 813.96 2666.18 6324.04 0.00 1015.94 896.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21-JUL-20:50 0.00 0.00 0.00 -0.5 0.00 0.00 424.80 902.05 2167.29 43.98 0.00 510.12 2322.92 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22-JUL-09:32 0.00 0.00 0.00 -0.7 0.00 0.00 115.16 116.28 1603.33 6690.92 0.00 574.15 0.00 0.00 0.00 0.00 0.00 -1059.6
LIVING_UNIT3_BACKROW_TOPFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.8 0.00 0.00 424.83 902.05 2167.29 172.05 0.00 884.69 5026.04 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.8 0.00 0.00 424.93 902.05 2167.29 174.22 0.00 885.24 5106.15 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.2 0.00 0.00 423.69 813.96 2666.18 7803.67 0.00 1553.27 889.79 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUL-20:53 0.00 0.00 0.00 -0.7 0.00 0.00 422.79 902.05 2167.29 25.21 0.00 664.60 4212.56 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-20:53 0.00 0.00 0.00 -0.7 0.00 0.00 422.71 902.05 2167.29 27.37 0.00 664.39 4273.71 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.2 0.00 0.00 423.65 813.96 2666.18 7982.51 0.00 1552.88 653.97 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:19 0.00 0.00 0.00 -14.8 0.00 0.00 7521.06 14651.21 48566.62 62691.64 0.00 44062.98 12379.29 0.00 0.00 0.00 -12304.6 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 2997.18 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 5831.03 0.00 -2922.5 0.00 -7914.7 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 9906.63 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -1189.2 0.00 -7382.0 -3344.4
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 12552.66 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2921.0 0.00 -7914.7 -3725.9
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13-JAN-05:00 0.00 0.00 12618.41 0.00 0.00 0.00 526.31 186.05 1036.84 0.00 0.00 0.00 0.00 0.00 -2931.8 0.00 -8062.2 -3373.6
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 13-JAN-05:00 0.00 0.00 10004.15 0.00 0.00 0.00 526.31 186.05 1036.84 0.00 0.00 0.00 0.00 0.00 -1185.9 0.00 -7518.1 -3049.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13-JAN-05:00 0.00 0.00 12638.90 0.00 0.00 0.00 526.31 186.05 1036.84 0.00 0.00 0.00 0.00 0.00 -2922.8 0.00 -8062.2 -3403.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 9692.91 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2962.2 0.00 -5410.9 -3328.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 7093.14 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -1203.6 0.00 -4877.7 -3020.8
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 9731.31 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2961.0 0.00 -5410.9 -3368.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 9766.19 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2958.2 0.00 -5410.9 -3406.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13-JAN-08:30 0.00 0.00 7155.78 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -1140.6 0.00 -4877.8 -3146.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 9771.22 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2958.1 0.00 -5410.9 -3411.2
LIVING_UNIT3_BACKROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 13826.69 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2944.6 0.00 -7924.6 -4966.4
LIVING_UNIT3_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 13795.20 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2945.0 0.00 -7924.6 -4934.6
LIVING_UNIT1_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 13775.83 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2945.4 0.00 -7924.6 -4914.8
LIVING_UNIT2_BACKROW_TOPFLOOR 13-JAN-08:30 0.00 0.00 11204.02 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -1133.9 0.00 -7391.1 -4688.0
LIVING_UNIT2_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 11148.04 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -1194.1 0.00 -7391.1 -4571.8
LIVING_UNIT1_BACKROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 13822.44 0.00 0.00 0.00 215.05 170.54 1623.38 0.00 0.00 0.00 0.00 0.00 -2944.7 0.00 -7924.6 -4962.1
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 13-JAN-08:15 0.00 0.00 191379.17 0.00 0.00 0.00 3870.98 3069.78 29220.83 0.00 0.00 1092.00 0.00 0.00 -42456.5 0.00 -159889.2 -26287.1



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 995.446 2.00 2.00 1.00 44.9950 995.446 0.045 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.958 2.00 2.00 1.00 44.9950 292.958 0.154 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 360.836 2.00 2.00 1.00 44.9950 360.836 0.125 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 543.315 2.00 2.00 1.00 44.9950 543.315 0.083 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 272.361 2.00 2.00 1.00 44.9950 272.361 0.165 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 348.009 2.00 2.00 1.00 44.9950 348.009 0.129 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 552.596 2.00 2.00 1.00 44.9950 552.596 0.081 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 290.275 2.00 2.00 1.00 44.9950 290.275 0.155 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 352.069 2.00 2.00 1.00 44.9950 352.069 0.128 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 532.393 2.00 2.00 1.00 44.9950 532.393 0.085 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 272.064 2.00 2.00 1.00 44.9950 272.064 0.165 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 344.282 2.00 2.00 1.00 44.9950 344.282 0.131 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 624.060 2.00 2.00 1.00 44.9950 624.060 0.072 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 362.344 2.00 2.00 1.00 44.9950 362.344 0.124 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 419.302 2.00 2.00 1.00 44.9950 419.302 0.107 1.000 44.9950 0.11
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 621.396 2.00 2.00 1.00 44.9950 621.396 0.072 1.000 44.9950 0.07
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 359.642 2.00 2.00 1.00 44.9950 359.642 0.125 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 415.691 2.00 2.00 1.00 44.9950 415.691 0.108 1.000 44.9950 0.11


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 69.411 2.00 2.00 1.00 44.9950 69.411 1.000 1.000 44.9950 0.65
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 211.758 2.00 2.00 1.00 44.9950 211.758 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 266.390 2.00 2.00 1.00 44.9950 266.390 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 266.486 2.00 2.00 1.00 44.9950 266.486 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 211.769 2.00 2.00 1.00 44.9950 211.769 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 266.335 2.00 2.00 1.00 44.9950 266.335 1.000 1.000 44.9950 0.17
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 207.409 2.00 2.00 1.00 44.9950 207.409 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 152.970 2.00 2.00 1.00 44.9950 152.970 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 207.487 2.00 2.00 1.00 44.9950 207.487 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 207.482 2.00 2.00 1.00 44.9950 207.482 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 152.966 2.00 2.00 1.00 44.9950 152.966 1.000 1.000 44.9950 0.29
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 207.427 2.00 2.00 1.00 44.9950 207.427 1.000 1.000 44.9950 0.22
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 292.661 2.00 2.00 1.00 44.9950 292.661 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 238.028 2.00 2.00 1.00 44.9950 238.028 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 292.759 2.00 2.00 1.00 44.9950 292.759 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 292.680 2.00 2.00 1.00 44.9950 292.680 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 238.005 2.00 2.00 1.00 44.9950 238.005 1.000 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 292.697 2.00 2.00 1.00 44.9950 292.697 1.000 1.000 44.9950 0.15


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   995.446 995.4460 199.0892 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   292.958 292.9578 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   360.836 360.8362 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   543.315 543.3152 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   272.361 272.3612 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   348.009 348.0091 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   552.596 552.5955 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   290.275 290.2748 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   352.069 352.0686 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   532.393 532.3934 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   272.064 272.0636 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   344.282 344.2818 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   415.691 415.6914 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   419.302 419.3015 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   624.060 624.0599 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   359.642 359.6424 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   362.344 362.3436 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   621.396 621.3958 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 995.45 995.446 995.45 199.0892 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.96 292.958 292.96 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 360.84 360.836 360.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 543.32 543.315 543.32 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 272.36 272.361 272.36 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 348.01 348.009 348.01 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 552.60 552.596 552.60 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 290.27 290.275 290.27 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 352.07 352.069 352.07 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 532.39 532.393 532.39 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 272.06 272.064 272.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 344.28 344.282 344.28 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 624.06 624.060 624.06 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 362.34 362.344 362.34 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 419.30 419.302 419.30 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 621.40 621.396 621.40 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 359.64 359.642 359.64 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 415.69 415.691 415.69 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   69.411 69.411 69.411 44.9950 0.648 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   211.758 211.758 211.758 44.9950 0.212 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   266.390 266.390 266.390 44.9950 0.169 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   266.486 266.486 266.486 44.9950 0.169 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   211.769 211.769 211.769 44.9950 0.212 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   266.335 266.335 266.335 44.9950 0.169 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   207.409 207.409 207.409 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   152.970 152.970 152.970 44.9950 0.294 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   207.487 207.487 207.487 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   207.482 207.482 207.482 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   152.966 152.966 152.966 44.9950 0.294 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   207.427 207.427 207.427 44.9950 0.217 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   292.697 292.697 292.697 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   292.759 292.759 292.759 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   292.661 292.661 292.661 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   238.005 238.005 238.005 44.9950 0.189 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   238.028 238.028 238.028 44.9950 0.189 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   292.680 292.680 292.680 44.9950 0.154 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 69.41 69.411 69.41 69.41 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 211.76 211.758 211.76 211.76 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 266.39 266.390 266.39 266.39 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 266.49 266.486 266.49 266.49 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 211.77 211.769 211.77 211.77 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 266.33 266.335 266.33 266.33 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 207.41 207.409 207.41 207.41 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 152.97 152.970 152.97 152.97 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 207.49 207.487 207.49 207.49 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 207.48 207.482 207.48 207.48 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 152.97 152.966 152.97 152.97 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 207.43 207.427 207.43 207.43 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 292.66 292.661 292.66 292.66 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 238.03 238.028 238.03 238.03 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 292.76 292.759 292.76 292.76 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 292.68 292.680 292.68 292.68 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 238.01 238.005 238.01 238.01 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 292.70 292.697 292.70 292.70 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Sec1.1A-General Information

Data
Weather File ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 30.75
Number of hours not met 30.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4758.75 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 741.27 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 2844.52 227878.13 0.00 0.00
Space Cooling 17112.78 15382.34 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8346.89 3982.66 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3140.40 151225.45 0.00 0.00
Receptacle Equipment 77145.04 12546.50 1639.73 20110.29 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 120220.97   7624.65   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 263405.37 410484.56
Natural Gas 163973.19 762465.47
Additional 0.00 0.00
Total 427378.56 1172950.03


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 0.44
Fans-Interior 0.21
Service Water Heating 0.00
Receptacle Equipment 1.98
Miscellaneous 0.08
Subtotal 3.08


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 2.14
Service Water Heating 2.36
Miscellaneous 1.23
Subtotal 5.73


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.25
Space Heating 24.25
Space Cooling 4.98
Fans-Interior 2.43
Service Water Heating 26.77
Receptacle Equipment 36.44
Miscellaneous 0.88



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 995.45
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 292.96
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 360.84
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 543.32
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 272.36
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 348.01
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 552.60
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 290.27
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 352.07
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 532.39
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 272.06
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 344.28
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 415.69
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 419.30
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 624.06
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 359.64
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 362.34
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 621.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 995.45
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 292.96
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 360.84
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 543.32
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 272.36
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 348.01
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 552.60
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 290.27
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 352.07
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 532.39
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 272.06
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 344.28
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 624.06
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 362.34
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 419.30
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 621.40
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 359.64
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 415.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 995.45 2.21 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 292.96 0.650828 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 360.84 0.801625 0.798655
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 543.32 1.21 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 272.36 0.605071 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 348.01 0.773128 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 552.60 1.23 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 290.27 0.644867 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 352.07 0.782147 0.798655
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 532.39 1.18 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 272.06 0.604410 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 344.28 0.764848 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 624.06 1.39 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 362.34 0.804973 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 419.30 0.931510 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 621.40 1.38 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 359.64 0.798973 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 415.69 0.923490 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 995.45 995.45 995.45 6562.70 2.21 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 292.96 292.96 292.96 13653.15 0.650828 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 360.84 360.84 360.84 16374.67 0.801625 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 543.32 543.32 543.32 16379.41 1.21 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 272.36 272.36 272.36 13653.71 0.605071 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 348.01 348.01 348.01 16371.90 0.773128 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 552.60 552.60 552.60 13435.75 1.23 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 290.27 290.27 290.27 10724.25 0.644867 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 352.07 352.07 352.07 13439.62 0.782147 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 532.39 532.39 532.39 13439.39 1.18 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 272.06 272.06 272.06 10724.03 0.604410 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 344.28 344.28 344.28 13436.63 0.764848 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 624.06 624.06 624.06 17683.21 1.39 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 362.34 362.34 362.34 14961.62 0.804973 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 419.30 419.30 419.30 17688.11 0.931510 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 621.40 621.40 621.40 17684.16 1.38 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 359.64 359.64 359.64 14960.50 0.798973 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 415.69 415.69 415.69 17685.03 0.923490 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 995.45
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 292.96
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 360.84
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 543.32
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 272.36
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 348.01
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 552.60
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 290.27
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 352.07
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 532.39
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 272.06
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 344.28
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 624.06
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 362.34
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 419.30
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 621.40
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 359.64
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 415.69
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 6562.70
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 13653.15
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 16374.67
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 16379.41
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13653.71
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 16371.90
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 13435.75
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 10724.25
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 13439.62
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 13439.39
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 10724.03
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 13436.63
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 17683.21
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 14961.62
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 17688.11
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 17684.16
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 14960.50
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 17685.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:39:35

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 576.886 37.453 28.021 2.679 40.133
February 658.500 60.698 0.000 0.000 60.698
March 744.000 89.710 0.000 0.000 89.710
April 720.000 124.758 0.000 0.000 124.758
May 744.000 149.086 0.000 0.000 149.086
June 720.000 178.185 0.000 0.000 178.185
July 744.000 213.904 0.000 0.000 213.904
August 744.000 194.011 0.000 0.000 194.011
September 720.000 164.352 0.000 0.000 164.352
October 744.000 130.118 0.000 0.000 130.118
November 692.958 71.355 0.000 0.000 71.355
December 692.654 55.176 0.000 0.000 55.176
           
Annual Sum or Average 8500.998 1468.807 28.021 2.679 1471.486
Minimum of Months 576.886 37.453 0.000 0.000 40.133
Maximum of Months 744.000 213.904 28.021 2.679 213.904



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 728.313 31.341 31.341
February 15.042 0.298 580.185 17.248 17.546
March 61.975 1.591 526.146 12.948 14.539
April 203.003 8.099 273.042 4.917 13.016
May 283.299 11.990 176.821 1.856 13.846
June 476.751 27.994 54.500 0.627 28.621
July 670.743 47.194 2.500 0.006 47.200
August 545.248 35.923 29.278 0.204 36.128
September 413.711 24.474 73.489 0.631 25.104
October 237.813 10.261 266.357 3.999 14.260
November 38.312 1.266 569.712 16.455 17.720
December 4.958 0.081 681.283 22.704 22.785
           
Annual Sum or Average 2950.855 169.173 3961.626 112.935 282.108
Minimum of Months 0.000 0.000 2.500 0.006 13.016
Maximum of Months 670.743 47.194 728.313 31.341 47.200



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 43.413 43.413
February 10.658 0.152 609.358 24.935 25.087
March 64.562 2.053 553.390 17.947 19.999
April 239.561 11.925 271.288 6.578 18.503
May 347.208 18.991 192.425 2.957 21.948
June 507.935 42.031 54.292 0.765 42.796
July 667.441 66.268 5.500 0.030 66.298
August 566.573 50.023 42.750 0.471 50.494
September 427.463 32.213 103.042 1.308 33.521
October 233.313 12.517 305.000 6.371 18.888
November 30.639 1.242 623.179 24.477 25.719
December 2.500 0.039 710.942 33.087 33.126
           
Annual Sum or Average 3097.854 237.454 4215.165 162.338 399.792
Minimum of Months 0.000 0.000 5.500 0.030 18.503
Maximum of Months 667.441 66.268 744.000 43.413 66.298



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 71.027 71.027
February 0.000 0.000 655.917 43.662 43.662
March 26.417 0.975 641.521 33.017 33.992
April 169.158 9.054 368.808 13.313 22.366
May 264.622 18.108 256.221 5.558 23.666
June 452.966 42.071 84.403 1.815 43.886
July 640.388 64.573 7.083 0.067 64.640
August 500.567 46.813 65.348 1.004 47.817
September 333.705 23.375 154.083 2.822 26.197
October 113.720 5.660 439.188 14.286 19.946
November 3.875 0.072 688.917 42.956 43.028
December 0.000 0.000 744.000 56.665 56.665
           
Annual Sum or Average 2505.419 210.700 4849.488 286.191 496.891
Minimum of Months 0.000 0.000 7.083 0.067 19.946
Maximum of Months 640.388 64.573 744.000 71.027 71.027



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 34.288 34.288
February 0.000 0.000 670.300 21.309 21.309
March 7.083 0.135 681.438 15.926 16.061
April 131.029 4.023 348.533 5.974 9.997
May 248.076 9.095 206.560 2.062 11.157
June 473.416 26.295 59.975 0.650 26.945
July 672.732 44.128 2.571 0.005 44.133
August 521.684 29.552 35.125 0.235 29.787
September 336.414 13.602 103.750 0.861 14.464
October 81.237 2.393 404.425 5.965 8.358
November 0.000 0.000 675.150 20.232 20.232
December 0.000 0.000 744.000 26.760 26.760
           
Annual Sum or Average 2471.672 129.224 4675.827 134.267 263.491
Minimum of Months 0.000 0.000 2.571 0.005 8.358
Maximum of Months 672.732 44.128 744.000 34.288 44.133



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 46.448 46.448
February 0.000 0.000 672.000 28.901 28.901
March 13.142 0.367 678.203 20.577 20.944
April 178.886 7.303 314.940 7.238 14.541
May 332.026 15.993 205.668 3.013 19.006
June 508.103 40.421 54.000 0.746 41.167
July 668.468 63.352 5.250 0.028 63.379
August 558.577 43.881 44.875 0.482 44.363
September 384.056 21.361 111.000 1.395 22.755
October 112.539 4.162 420.425 7.977 12.139
November 0.000 0.000 690.713 28.051 28.051
December 0.000 0.000 744.000 37.020 37.020
           
Annual Sum or Average 2755.797 196.839 4685.074 181.876 378.716
Minimum of Months 0.000 0.000 5.250 0.028 12.139
Maximum of Months 668.468 63.352 744.000 46.448 63.379



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 3.333 0.038 705.542 52.893 52.931
February 40.500 1.197 516.487 27.749 28.946
March 105.296 5.311 465.162 20.252 25.563
April 274.489 17.441 231.943 7.045 24.487
May 357.955 25.439 133.948 2.332 27.772
June 525.069 48.202 38.762 0.692 48.894
July 689.933 71.571 0.000 0.000 71.571
August 575.467 57.142 22.994 0.269 57.411
September 444.893 38.544 58.250 0.917 39.461
October 267.904 17.306 243.833 6.514 23.820
November 51.208 2.124 531.633 27.420 29.544
December 13.750 0.276 648.629 38.246 38.521
           
Annual Sum or Average 3349.798 284.591 3597.185 184.329 468.921
Minimum of Months 3.333 0.038 0.000 0.000 23.820
Maximum of Months 689.933 71.571 705.542 52.893 71.571



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 697.229 25.189 25.189
February 32.125 0.607 486.008 12.832 13.439
March 93.775 2.644 426.958 9.054 11.698
April 270.891 10.962 182.500 2.676 13.639
May 367.049 15.693 83.396 0.729 16.422
June 560.692 32.309 24.792 0.187 32.496
July 724.850 51.423 0.000 0.000 51.423
August 623.825 40.155 6.625 0.025 40.180
September 500.831 28.871 27.075 0.179 29.049
October 309.610 13.495 160.449 2.031 15.527
November 53.167 1.827 486.292 12.351 14.178
December 18.125 0.250 609.513 17.426 17.676
           
Annual Sum or Average 3554.940 198.235 3190.837 82.679 280.915
Minimum of Months 0.000 0.000 0.000 0.000 11.698
Maximum of Months 724.850 51.423 697.229 25.189 51.423



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 721.188 36.876 36.876
February 16.479 0.343 554.334 19.914 20.257
March 94.175 3.199 464.453 13.526 16.725
April 299.533 15.295 193.290 4.136 19.431
May 404.052 23.295 112.972 1.534 24.829
June 567.199 46.564 21.821 0.289 46.852
July 703.320 70.182 0.500 0.001 70.183
August 611.705 54.135 15.500 0.151 54.287
September 483.659 36.521 52.125 0.572 37.093
October 292.655 15.592 222.208 4.043 19.635
November 42.352 1.634 559.479 19.774 21.408
December 6.167 0.092 677.667 27.245 27.337
           
Annual Sum or Average 3521.295 266.852 3595.538 128.060 394.912
Minimum of Months 0.000 0.000 0.500 0.001 16.725
Maximum of Months 703.320 70.182 721.188 36.876 70.183



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 62.299 62.299
February 0.000 0.000 637.167 36.494 36.494
March 41.937 1.378 576.771 26.115 27.494
April 214.471 11.438 283.634 8.974 20.412
May 322.854 21.519 162.845 2.981 24.500
June 517.526 46.084 44.232 0.806 46.890
July 689.142 68.628 0.875 0.001 68.629
August 555.620 50.530 30.517 0.373 50.902
September 393.972 26.868 82.179 1.374 28.242
October 146.499 6.857 353.625 10.105 16.962
November 6.000 0.095 661.313 36.299 36.395
December 0.000 0.000 744.000 48.868 48.868
           
Annual Sum or Average 2888.022 233.397 4321.156 234.690 468.087
Minimum of Months 0.000 0.000 0.875 0.001 16.962
Maximum of Months 689.142 68.628 744.000 62.299 68.629



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 29.022 29.022
February 0.000 0.000 661.437 16.864 16.864
March 15.042 0.247 580.189 11.442 11.688
April 198.954 6.219 234.857 3.296 9.515
May 334.840 12.659 95.809 0.798 13.458
June 555.803 30.784 26.375 0.179 30.963
July 725.581 48.631 0.000 0.000 48.631
August 605.090 33.946 7.250 0.029 33.975
September 445.096 17.660 39.833 0.273 17.933
October 139.241 3.632 275.637 3.422 7.054
November 0.000 0.000 622.375 16.167 16.167
December 0.000 0.000 742.250 21.873 21.873
           
Annual Sum or Average 3019.647 153.778 4030.013 103.367 257.144
Minimum of Months 0.000 0.000 0.000 0.000 7.054
Maximum of Months 725.581 48.631 744.000 29.022 48.631



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 41.295 41.295
February 0.000 0.000 669.937 24.586 24.586
March 19.173 0.553 604.400 15.806 16.359
April 243.927 9.956 223.171 4.556 14.512
May 388.080 20.324 118.333 1.594 21.918
June 563.284 45.083 21.000 0.292 45.375
July 704.518 67.604 0.500 0.001 67.605
August 605.645 48.313 16.375 0.158 48.471
September 454.714 25.645 57.000 0.636 26.280
October 161.700 5.601 299.605 5.278 10.879
November 0.000 0.000 658.060 24.065 24.065
December 0.000 0.000 744.000 32.390 32.390
           
Annual Sum or Average 3141.039 223.078 4156.381 150.658 373.736
Minimum of Months 0.000 0.000 0.500 0.001 10.879
Maximum of Months 704.518 67.604 744.000 41.295 67.605



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 736.779 75.809 75.809
February 11.454 0.321 596.546 43.657 43.978
March 66.750 3.340 574.167 33.407 36.747
April 214.260 15.291 321.962 13.400 28.691
May 297.375 24.923 232.713 5.943 30.865
June 472.388 51.039 77.417 1.907 52.946
July 653.080 78.259 6.417 0.072 78.331
August 527.740 60.176 53.286 0.986 61.162
September 385.867 37.307 129.875 2.773 40.080
October 199.102 13.906 352.437 13.141 27.047
November 26.708 1.150 632.002 43.303 44.453
December 1.000 0.006 717.338 58.403 58.409
           
Annual Sum or Average 2855.725 285.719 4430.937 292.800 578.519
Minimum of Months 0.000 0.000 6.417 0.072 27.047
Maximum of Months 653.080 78.259 736.779 75.809 78.331



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 740.813 41.564 41.564
February 7.917 0.085 611.087 23.477 23.562
March 50.837 1.422 559.271 17.438 18.861
April 207.652 9.740 281.200 6.415 16.155
May 300.052 15.943 191.256 2.540 18.483
June 495.123 35.649 54.587 0.771 36.421
July 683.565 58.417 2.597 0.005 58.422
August 559.089 43.607 31.500 0.278 43.885
September 415.745 27.975 85.911 0.942 28.917
October 219.817 10.261 294.500 5.681 15.941
November 33.271 1.009 613.679 22.665 23.674
December 0.250 0.001 710.917 30.970 30.971
           
Annual Sum or Average 2973.318 204.109 4177.317 152.745 356.854
Minimum of Months 0.000 0.000 2.597 0.005 15.941
Maximum of Months 683.565 58.417 740.813 41.564 58.422



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 52.324 52.324
February 2.083 0.011 626.304 30.374 30.386
March 50.429 1.745 573.912 21.651 23.395
April 237.042 13.109 273.329 7.528 20.637
May 353.338 22.405 183.542 3.272 25.678
June 522.712 49.120 49.042 0.769 49.889
July 683.098 76.851 3.417 0.021 76.872
August 578.041 56.977 34.250 0.441 57.418
September 429.549 35.122 99.333 1.479 36.601
October 217.775 12.118 321.042 7.755 19.873
November 27.425 0.978 647.771 29.996 30.974
December 0.000 0.000 724.375 40.410 40.410
           
Annual Sum or Average 3101.493 268.437 4280.317 196.020 464.456
Minimum of Months 0.000 0.000 3.417 0.021 19.873
Maximum of Months 683.098 76.851 744.000 52.324 76.872



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 82.537 82.537
February 0.000 0.000 660.867 50.593 50.593
March 34.170 1.300 629.263 37.583 38.884
April 190.038 12.161 348.792 14.583 26.744
May 286.801 23.523 240.339 6.142 29.665
June 472.292 50.805 76.617 1.893 52.698
July 655.545 77.526 6.542 0.066 77.592
August 520.523 56.964 57.125 1.022 57.986
September 352.041 29.432 147.625 3.161 32.593
October 125.365 7.142 432.633 16.420 23.562
November 3.771 0.068 686.875 50.214 50.281
December 0.000 0.000 744.000 66.272 66.272
           
Annual Sum or Average 2640.545 258.921 4774.677 330.486 589.407
Minimum of Months 0.000 0.000 6.542 0.066 23.562
Maximum of Months 655.545 77.526 744.000 82.537 82.537



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 45.995 45.995
February 0.000 0.000 669.400 28.348 28.348
March 11.125 0.336 660.285 20.543 20.879
April 171.210 7.085 325.604 7.296 14.382
May 289.391 14.782 197.631 2.632 17.414
June 496.265 35.607 55.208 0.767 36.374
July 685.814 57.750 1.528 0.001 57.751
August 548.245 40.532 33.417 0.286 40.819
September 370.549 20.207 101.893 1.138 21.345
October 106.004 3.955 393.792 7.884 11.838
November 0.000 0.000 675.125 27.296 27.296
December 0.000 0.000 744.000 36.231 36.231
           
Annual Sum or Average 2678.603 180.255 4601.882 178.417 358.672
Minimum of Months 0.000 0.000 1.528 0.001 11.838
Maximum of Months 685.814 57.750 744.000 45.995 57.751



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 56.329 56.329
February 0.000 0.000 671.750 34.870 34.870
March 14.600 0.571 663.046 24.430 25.001
April 203.577 10.138 314.499 8.160 18.297
May 346.919 21.223 188.750 3.338 24.560
June 521.602 49.030 48.780 0.758 49.788
July 684.188 76.103 3.125 0.019 76.122
August 575.403 53.931 34.375 0.448 54.379
September 404.072 27.282 104.583 1.561 28.843
October 124.547 5.557 411.042 9.610 15.167
November 0.000 0.000 688.400 34.224 34.224
December 0.000 0.000 744.000 45.204 45.204
           
Annual Sum or Average 2874.907 243.835 4616.349 218.949 462.784
Minimum of Months 0.000 0.000 3.125 0.019 15.167
Maximum of Months 684.188 76.103 744.000 56.329 76.122



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 47.41 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 4.03 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 47.41 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3920.13 0.00
February 0.00 2388.56 0.00
March 0.00 1619.54 0.00
April 0.00 635.47 0.00
May 0.00 232.16 0.00
June 0.00 81.01 0.00
July 0.00 0.77 0.00
August 0.00 25.57 0.00
September 0.00 81.51 0.00
October 0.00 500.18 0.00
November 0.00 2126.80 0.00
December 0.00 2839.86 0.00
       
Annual Sum or Average 0.00 1199.75 0.00
Minimum of Months 0.00 0.77 0.00
Maximum of Months 0.00 3920.13 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5287.45 0.00
February 0.00 3362.33 0.00
March 0.00 2185.80 0.00
April 0.00 827.84 0.00
May 0.00 360.18 0.00
June 0.00 96.31 0.00
July 0.00 3.64 0.00
August 0.00 57.32 0.00
September 0.00 164.58 0.00
October 0.00 776.00 0.00
November 0.00 3080.57 0.00
December 0.00 4029.81 0.00
       
Annual Sum or Average 0.00 1679.26 0.00
Minimum of Months 0.00 3.64 0.00
Maximum of Months 0.00 5287.45 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5746.95 0.00
February 0.00 3911.29 0.00
March 0.00 2671.44 0.00
April 0.00 1113.06 0.00
May 0.00 449.70 0.00
June 0.00 151.76 0.00
July 0.00 5.40 0.00
August 0.00 81.20 0.00
September 0.00 235.98 0.00
October 0.00 1155.89 0.00
November 0.00 3591.52 0.00
December 0.00 4584.84 0.00
       
Annual Sum or Average 0.00 1966.70 0.00
Minimum of Months 0.00 5.40 0.00
Maximum of Months 0.00 5746.95 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4613.28 0.00
February 0.00 3174.30 0.00
March 0.00 2142.76 0.00
April 0.00 830.55 0.00
May 0.00 277.47 0.00
June 0.00 90.36 0.00
July 0.00 0.68 0.00
August 0.00 31.63 0.00
September 0.00 119.75 0.00
October 0.00 802.52 0.00
November 0.00 2812.85 0.00
December 0.00 3600.50 0.00
       
Annual Sum or Average 0.00 1534.30 0.00
Minimum of Months 0.00 0.68 0.00
Maximum of Months 0.00 4613.28 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5864.70 0.00
February 0.00 4040.15 0.00
March 0.00 2598.12 0.00
April 0.00 944.37 0.00
May 0.00 380.46 0.00
June 0.00 97.31 0.00
July 0.00 3.49 0.00
August 0.00 60.86 0.00
September 0.00 181.96 0.00
October 0.00 1007.16 0.00
November 0.00 3659.87 0.00
December 0.00 4674.21 0.00
       
Annual Sum or Average 0.00 1950.38 0.00
Minimum of Months 0.00 3.49 0.00
Maximum of Months 0.00 5864.70 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3451.57 0.00
February 0.00 2004.79 0.00
March 0.00 1321.57 0.00
April 0.00 475.08 0.00
May 0.00 152.20 0.00
June 0.00 46.67 0.00
July 0.00 0.00 0.00
August 0.00 17.55 0.00
September 0.00 61.85 0.00
October 0.00 425.06 0.00
November 0.00 1848.98 0.00
December 0.00 2495.76 0.00
       
Annual Sum or Average 0.00 1021.61 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3451.57 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 2497.64 0.00
February 0.00 1408.75 0.00
March 0.00 897.73 0.00
April 0.00 274.21 0.00
May 0.00 72.30 0.00
June 0.00 19.15 0.00
July 0.00 0.00 0.00
August 0.00 2.51 0.00
September 0.00 18.29 0.00
October 0.00 201.41 0.00
November 0.00 1265.55 0.00
December 0.00 1727.91 0.00
       
Annual Sum or Average 0.00 696.29 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 2497.64 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3778.04 0.00
February 0.00 2258.81 0.00
March 0.00 1385.76 0.00
April 0.00 437.89 0.00
May 0.00 157.13 0.00
June 0.00 30.57 0.00
July 0.00 0.14 0.00
August 0.00 15.50 0.00
September 0.00 60.54 0.00
October 0.00 414.19 0.00
November 0.00 2093.44 0.00
December 0.00 2791.38 0.00
       
Annual Sum or Average 0.00 1114.32 0.00
Minimum of Months 0.00 0.14 0.00
Maximum of Months 0.00 3778.04 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4220.79 0.00
February 0.00 2737.41 0.00
March 0.00 1769.31 0.00
April 0.00 628.30 0.00
May 0.00 201.96 0.00
June 0.00 56.44 0.00
July 0.00 0.04 0.00
August 0.00 25.24 0.00
September 0.00 96.22 0.00
October 0.00 684.64 0.00
November 0.00 2541.28 0.00
December 0.00 3310.83 0.00
       
Annual Sum or Average 0.00 1350.44 0.00
Minimum of Months 0.00 0.04 0.00
Maximum of Months 0.00 4220.79 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 3070.34 0.00
February 0.00 1975.25 0.00
March 0.00 1210.43 0.00
April 0.00 360.37 0.00
May 0.00 84.45 0.00
June 0.00 19.60 0.00
July 0.00 0.00 0.00
August 0.00 3.03 0.00
September 0.00 29.85 0.00
October 0.00 362.05 0.00
November 0.00 1767.39 0.00
December 0.00 2314.00 0.00
       
Annual Sum or Average 0.00 928.76 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 3070.34 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4325.56 0.00
February 0.00 2851.29 0.00
March 0.00 1655.63 0.00
April 0.00 493.15 0.00
May 0.00 166.93 0.00
June 0.00 31.65 0.00
July 0.00 0.11 0.00
August 0.00 16.60 0.00
September 0.00 68.80 0.00
October 0.00 552.87 0.00
November 0.00 2604.80 0.00
December 0.00 3392.72 0.00
       
Annual Sum or Average 0.00 1340.30 0.00
Minimum of Months 0.00 0.11 0.00
Maximum of Months 0.00 4325.56 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5765.29 0.00
February 0.00 3675.88 0.00
March 0.00 2540.61 0.00
April 0.00 1053.00 0.00
May 0.00 451.94 0.00
June 0.00 149.89 0.00
July 0.00 5.44 0.00
August 0.00 74.98 0.00
September 0.00 217.88 0.00
October 0.00 999.38 0.00
November 0.00 3402.98 0.00
December 0.00 4441.57 0.00
       
Annual Sum or Average 0.00 1891.21 0.00
Minimum of Months 0.00 5.44 0.00
Maximum of Months 0.00 5765.29 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 4606.15 0.00
February 0.00 2880.54 0.00
March 0.00 1932.52 0.00
April 0.00 734.59 0.00
May 0.00 281.45 0.00
June 0.00 88.34 0.00
July 0.00 0.54 0.00
August 0.00 30.83 0.00
September 0.00 107.85 0.00
October 0.00 629.54 0.00
November 0.00 2595.46 0.00
December 0.00 3432.16 0.00
       
Annual Sum or Average 0.00 1437.67 0.00
Minimum of Months 0.00 0.54 0.00
Maximum of Months 0.00 4606.15 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5924.05 0.00
February 0.00 3807.39 0.00
March 0.00 2451.26 0.00
April 0.00 880.76 0.00
May 0.00 370.50 0.00
June 0.00 89.95 0.00
July 0.00 2.38 0.00
August 0.00 49.97 0.00
September 0.00 173.02 0.00
October 0.00 878.01 0.00
November 0.00 3509.33 0.00
December 0.00 4575.16 0.00
       
Annual Sum or Average 0.00 1884.90 0.00
Minimum of Months 0.00 2.38 0.00
Maximum of Months 0.00 5924.05 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6304.18 0.00
February 0.00 4278.32 0.00
March 0.00 2870.62 0.00
April 0.00 1150.98 0.00
May 0.00 469.16 0.00
June 0.00 149.42 0.00
July 0.00 5.05 0.00
August 0.00 78.07 0.00
September 0.00 249.52 0.00
October 0.00 1254.15 0.00
November 0.00 3963.20 0.00
December 0.00 5061.88 0.00
       
Annual Sum or Average 0.00 2143.90 0.00
Minimum of Months 0.00 5.05 0.00
Maximum of Months 0.00 6304.18 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 5135.10 0.00
February 0.00 3504.08 0.00
March 0.00 2293.58 0.00
April 0.00 841.72 0.00
May 0.00 293.81 0.00
June 0.00 88.44 0.00
July 0.00 0.15 0.00
August 0.00 31.97 0.00
September 0.00 131.31 0.00
October 0.00 880.16 0.00
November 0.00 3149.03 0.00
December 0.00 4045.06 0.00
       
Annual Sum or Average 0.00 1691.79 0.00
Minimum of Months 0.00 0.15 0.00
Maximum of Months 0.00 5135.10 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Btu/h] COOLING COIL TOTAL COOLING RATE [Invalid/Undefined]
January 0.00 6431.75 0.00
February 0.00 4408.10 0.00
March 0.00 2789.44 0.00
April 0.00 962.74 0.00
May 0.00 381.09 0.00
June 0.00 89.38 0.00
July 0.00 2.21 0.00
August 0.00 51.14 0.00
September 0.00 184.15 0.00
October 0.00 1097.29 0.00
November 0.00 4038.08 0.00
December 0.00 5161.55 0.00
       
Annual Sum or Average 0.00 2123.30 0.00
Minimum of Months 0.00 2.21 0.00
Maximum of Months 0.00 6431.75 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.21
February 0.00 0.00 0.38
March 0.00 0.00 0.51
April 0.00 0.00 0.72
May 0.00 0.00 0.83
June 0.00 0.00 1.01
July 0.00 0.00 1.15
August 0.00 0.00 1.06
September 0.00 0.00 0.94
October 0.00 0.00 0.73
November 0.00 0.00 0.42
December 0.00 0.00 0.31
       
Annual Sum or Average 0.00 0.00 0.69
Minimum of Months 0.00 0.00 0.21
Maximum of Months 0.00 0.00 1.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.25
August 0.00 0.00 0.19
September 0.00 0.00 0.14
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.36
August 0.00 0.00 0.27
September 0.00 0.00 0.18
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.33
August 0.00 0.00 0.24
September 0.00 0.00 0.13
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.23
August 0.00 0.00 0.16
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.08
June 0.00 0.00 0.22
July 0.00 0.00 0.34
August 0.00 0.00 0.23
September 0.00 0.00 0.12
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.14
June 0.00 0.00 0.26
July 0.00 0.00 0.37
August 0.00 0.00 0.30
September 0.00 0.00 0.21
October 0.00 0.00 0.09
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.08
June 0.00 0.00 0.18
July 0.00 0.00 0.28
August 0.00 0.00 0.22
September 0.00 0.00 0.16
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.09
May 0.00 0.00 0.13
June 0.00 0.00 0.26
July 0.00 0.00 0.38
August 0.00 0.00 0.29
September 0.00 0.00 0.21
October 0.00 0.00 0.08
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.11
June 0.00 0.00 0.25
July 0.00 0.00 0.36
August 0.00 0.00 0.26
September 0.00 0.00 0.15
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.17
July 0.00 0.00 0.26
August 0.00 0.00 0.18
September 0.00 0.00 0.10
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.11
June 0.00 0.00 0.25
July 0.00 0.00 0.37
August 0.00 0.00 0.26
September 0.00 0.00 0.14
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.13
June 0.00 0.00 0.28
July 0.00 0.00 0.41
August 0.00 0.00 0.31
September 0.00 0.00 0.20
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.20
July 0.00 0.00 0.31
August 0.00 0.00 0.23
September 0.00 0.00 0.16
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.12
June 0.00 0.00 0.27
July 0.00 0.00 0.41
August 0.00 0.00 0.30
September 0.00 0.00 0.19
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.07
May 0.00 0.00 0.12
June 0.00 0.00 0.28
July 0.00 0.00 0.40
August 0.00 0.00 0.30
September 0.00 0.00 0.16
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.08
June 0.00 0.00 0.20
July 0.00 0.00 0.31
August 0.00 0.00 0.21
September 0.00 0.00 0.11
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.06
May 0.00 0.00 0.11
June 0.00 0.00 0.27
July 0.00 0.00 0.41
August 0.00 0.00 0.29
September 0.00 0.00 0.15
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83
Maximum of Months 0.00 0.00 1840.37 1352.91



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:39:35

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1817.14 1352.91
February 0.00 0.00 1840.37 1237.60
March 0.00 0.00 1800.92 1340.83
April 0.00 0.00 1714.08 1235.01
May 0.00 0.00 1583.19 1178.73
June 0.00 0.00 1460.13 1052.04
July 0.00 0.00 1373.97 1022.96
August 0.00 0.00 1342.72 999.69
September 0.00 0.00 1383.50 996.83
October 0.00 0.00 1477.09 1099.73
November 0.00 0.00 1600.90 1153.47
December 0.00 0.00 1729.35 1287.55
         
Annual Sum or Average 0.00 0.00 1592.18 13957.35
Minimum of Months 0.00 0.00 1342.72 996.83