Table of Contents

Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:40

Tabular Output Report in Format: HTML

Building: MF+CZ5BWH+USA_ID_Boise.Air.Terminal.726810+oilfurnace+crawlspace+IECC_2009

Environment: ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810

Simulation Timestamp: 2019-02-14 08:40:10


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1075837.38 27.58 49.78
Net Site Energy 1075837.38 27.58 49.78
Total Source Energy 2082476.30 53.39 96.37
Net Source Energy 2082476.30 53.39 96.37


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 0.300
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil #1 1.050
Fuel Oil #2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.17
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.21


End Uses

Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 321863.68 0.00 0.00 0.00 0.00
Cooling 50776.69 0.00 0.00 0.00 0.00 0.00
Interior Lighting 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 10266.93 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 27449.80 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 314094.40 0.00 0.00 0.00 419684.21
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 439879.30 635958.09 0.00 0.00 0.00 419684.21
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Additional Fuel [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Boiler 0.00 321863.68 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 50776.69 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 49882.34 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 8347.88 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 1919.05 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 27449.80 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 314094.40 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 419684.21
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.78 0.00 0.00 0.00 0.00 0.00
HVAC 3.62 29.43 0.00 0.00 0.00 19.42
Other 13.95 0.00 0.00 0.00 0.00 0.00
Total 20.36 29.43 0.00 0.00 0.00 19.42


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Additional Fuel Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.54 0.00 0.00 0.00 0.00 0.00
HVAC 2.01 16.30 0.00 0.00 0.00 10.76
Other 7.73 0.00 0.00 0.00 0.00 0.00
Total 11.28 16.30 0.00 0.00 0.00 10.76


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 439879.296 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 439879.296 100.00
     
Total On-Site and Utility Electric Sources 439879.296 100.00
Total Electricity End Uses 439879.296 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 419684.21 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 419684.21 100.00
Total Water End Uses 419684.21 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1250.75
Time Setpoint Not Met During Occupied Cooling 34.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 602.75


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
System Summary
Outdoor Air Summary
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

General

Value
Program Version and Build EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:40
RunPeriod ANNUAL
Weather File Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Latitude [deg] 43.62
Longitude [deg] -116.2
Elevation [ft] 2299.98
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19407.54 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.13 No Yes 30552.60 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
ATTIC 7802.69 No Yes 52795.67 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7514 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7514 600.28 2.9092
Total 39005.17     286495.20   16363.00 740.10 2126.74 2126.74 0.4163 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.7514 600.28 2.9092
Unconditioned Total 17395.21     102755.82   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-18:15 13-JAN-08:30 - - - 01-JAN-08:15
Heating 0.00 234.69 0.00 0.00 0.00 0.00
Cooling 48.29 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.47 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.91 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Fans 12.55 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 116.40 0.00 0.00 0.00 1.52
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00
             
Total End Uses 130.89 351.09 0.00 0.00 0.00 1.52


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Propane [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating Boiler 0.00 234.69 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 48.29 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.66 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 1.91 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.56 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.64 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.82 0.00 0.00 0.00 0.00 0.00
  electric_dryer 6.92 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00
  General 12.55 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Water Heater 0.00 116.40 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 1.52
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Additional Fuel [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 348900.23 0.00 0.00 0.00
Cooling 160809.77 0.00 0.00 0.00 0.00
Interior Lighting 157977.37 0.00 0.00 0.00 0.00
Exterior Lighting 32515.36 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 86933.52 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 340478.33 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 1393097.73 689378.57 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 16.15 0.00 0.00 0.00
Cooling 7.44 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.02 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.76 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 64.47 31.90 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Additional Fuel [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 16.15 0.00 0.00 0.00
Cooling 7.44 0.00 0.00 0.00 0.00
Interior Lighting 7.31 0.00 0.00 0.00 0.00
Exterior Lighting 1.50 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00
Fans 4.02 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.76 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00
           
Total Source Energy End Use Components 64.47 31.90 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 2.66 0.00 2.66 Wetbulb [F] 452.78 120.00
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 98.06 30.06 64.22 Wetbulb [F] 826.81 330.00


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.38 599.38 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Exterior Fenestration

Construction Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW 59.08 0.00 0.00 59.08 59.08 0.350 0.330 0.882     Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW 88.61 0.00 0.00 88.61 88.61 0.350 0.330 0.882     Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average           2126.74 0.350 0.330 0.882              
North Total or Average           531.68 0.350 0.330 0.882              
Non-North Total or Average           1595.05 0.350 0.330 0.882              


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES Interior Blind WINDOW_W_BLINDS OnIfScheduleAllows No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Interior Lighting

Zone Lighting Power Density [Btu/h-ft2] Zone Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.5691 1200.55 683.23 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 614.75
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total   0.3757 43219.92 16236.84               14609.33


Daylighting

Zone Daylighting Type Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None            


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 31.01 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 135.83
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 10.17 Schedule INTERIORLIGHTINGHE 58.88 168.00 58.88 31.22
Exterior Lighting Total 741.27           3006.93



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Central Plant

Type Nominal Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh] IPLV in SI Units [Btuh/Btuh] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 423701.75 0.80    


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   25511.84 20375.17 5136.68 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6833.76 5457.82 1375.94 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9118.90 7268.78 1850.12 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13456.96 10747.47 2709.49 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6268.31 5006.22 1262.09 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   8766.46 7001.38 1765.08 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13698.06 10940.02 2758.03 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6742.20 5384.69 1357.51 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8884.97 7074.70 1810.27 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13157.57 10508.36 2649.21 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6250.46 4991.96 1258.50 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8657.73 6914.54 1743.19 0.80 3.97    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15588.84 12450.11 3138.73 0.80 3.97    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8635.46 6896.75 1738.70 0.80 3.97    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10342.16 8259.82 2082.34 0.80 3.97    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15514.41 12390.66 3123.74 0.80 3.97    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8550.42 6828.84 1721.58 0.80 3.97    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10135.56 8094.82 2040.74 0.80 3.97    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   2.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.7 3.20 10.90 11.55 11.09
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.20 10.91 11.55 11.10
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.0 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.2 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.8 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.2 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.19 10.89 11.54 11.07
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.19 10.89 11.54 11.07
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 50765.09 54133.85 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 15873.78 15660.28 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 20072.25 20307.45 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 28249.28 29325.69 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 14817.31 14486.16 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 19485.27 19658.69 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 28696.86 29816.77 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 15701.40 15468.12 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 19596.52 19780.53 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 27687.11 28705.02 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 14782.74 14447.02 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 19280.38 19431.04 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 32232.62 33707.71 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 19240.08 19388.25 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 22429.40 22908.78 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 32093.54 33554.71 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 19081.21 19212.56 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 22043.37 22482.83 -
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electric Power [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction End Use
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 956.97 479.25 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 256.34 128.37 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 340.62 170.58 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 504.78 252.79 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 235.13 117.75 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.38 0.06 328.84 164.68 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 513.83 257.32 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 252.91 126.65 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 331.11 165.82 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 493.55 247.17 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 234.46 117.42 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.38 0.06 324.76 162.64 0.50 1.00 General
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 584.75 292.84 0.50 1.00 General
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 323.92 162.22 0.50 1.00 General
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.38 0.06 387.94 194.28 0.50 1.00 General
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 581.96 291.44 0.50 1.00 General
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 320.73 160.62 0.50 1.00 General
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.38 0.06 380.19 190.40 0.50 1.00 General


Pumps

Type Control Head [psi] Water Flow [gal/min] Electric Power [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh]
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 42.606473 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 1.08 0.55



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20677.74 20677.74 17.22 956.973 956.973 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00797 89.72 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5538.86 5538.86 4.61 256.341 256.341 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00790 89.72 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7360.27 7360.27 6.13 340.622 340.622 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.99 0.00777 98.06 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10907.08 10907.08 9.09 504.783 504.783 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:15:00 74.98 74.98 0.00794 89.72 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5080.55 5080.55 4.23 235.130 235.130 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00792 87.46 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7105.38 7105.38 5.92 328.838 328.838 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00778 88.89 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11102.38 11102.38 9.25 513.827 513.827 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5464.60 5464.60 4.55 252.906 252.906 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00805 87.46 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7154.52 7154.52 5.96 331.107 331.107 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 14:45:00 74.98 74.98 0.00786 98.06 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10664.31 10664.31 8.88 493.553 493.553 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00802 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5066.04 5066.04 4.22 234.460 234.460 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.98 74.98 0.00806 86.34 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7017.22 7017.22 5.84 324.759 324.759 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 74.98 74.98 0.00787 88.89 0.00627 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8215.08 8215.08 6.84 380.194 380.194 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 17:45:00 74.98 74.98 0.00790 91.60 0.00627 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8382.63 8382.63 6.98 387.944 387.944 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 16:45:00 74.98 74.98 0.00783 94.45 0.00627 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12634.98 12634.98 10.52 584.752 584.752 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00796 88.59 0.00627 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6930.23 6930.23 5.77 320.734 320.734 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00795 87.46 0.00627 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6999.14 6999.14 5.83 323.924 323.924 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:45:00 74.98 74.98 0.00795 87.46 0.00627 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12574.65 12574.65 10.47 581.960 581.960 BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 74.98 74.98 0.00796 88.59 0.00627 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3951.60 3951.60 3.29 78.190 78.190 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00401 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11143.16 11143.16 9.28 220.456 220.456 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00580 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13908.10 13908.10 11.58 275.150 275.150 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00601 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 13912.89 13912.89 11.59 275.245 275.245 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00601 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11143.68 11143.68 9.28 220.466 220.466 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00580 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13905.26 13905.26 11.58 275.094 275.094 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00601 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10917.44 10917.44 9.09 216.011 216.011 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00625 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8158.05 8158.05 6.80 161.419 161.419 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00602 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10921.31 10921.31 9.10 216.088 216.088 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00625 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10921.07 10921.07 9.10 216.083 216.083 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00625 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8157.81 8157.81 6.80 161.415 161.415 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00602 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10918.26 10918.26 9.09 216.027 216.027 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00625 2.66 0.00098 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 15233.86 15233.86 12.69 301.378 301.378 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00613 2.66 0.00098 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 15236.99 15236.99 12.69 301.440 301.440 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00613 2.66 0.00098 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 15232.03 15232.03 12.69 301.342 301.342 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00613 2.66 0.00098 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12470.02 12470.02 10.39 246.707 246.707 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00596 2.66 0.00098 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12471.15 12471.15 10.39 246.729 246.729 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.98 0.00596 2.66 0.00098 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 15232.99 15232.99 12.69 301.361 301.361 BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.97 0.00613 2.66 0.00098 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 956.97 956.97 78.19 78.19
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 256.34 256.34 220.46 220.46
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.62 340.62 275.15 275.15
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 504.78 504.78 275.24 275.24
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 235.13 235.13 220.47 220.47
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.84 328.84 275.09 275.09
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.83 513.83 216.01 216.01
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.91 252.91 161.42 161.42
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.11 331.11 216.09 216.09
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.55 493.55 216.08 216.08
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 234.46 234.46 161.41 161.41
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.76 324.76 216.03 216.03
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 584.75 584.75 301.34 301.34
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.92 323.92 246.73 246.73
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 387.94 387.94 301.44 301.44
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 581.96 581.96 301.36 301.36
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 320.73 320.73 246.71 246.71
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 380.19 380.19 301.38 301.38


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 893.25 6325.50 52.25
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 632.00 6606.75 380.75
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 974.75 6184.25 130.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 934.25 6845.75 267.75
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 167.00 7128.75 23.75
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 723.25 6551.50 131.75
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1075.50 6070.50 32.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 454.50 6113.25 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1090.25 5839.25 41.50
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 998.25 6517.75 180.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 288.25 6653.75 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 864.25 6223.00 48.75
LIVING_UNIT3_BACKROW_TOPFLOOR 1209.00 6290.50 275.75
LIVING_UNIT3_FRONTROW_TOPFLOOR 1301.25 6064.25 216.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 1311.50 6363.25 249.75
LIVING_UNIT2_BACKROW_TOPFLOOR 549.50 6691.00 46.75
LIVING_UNIT2_FRONTROW_TOPFLOOR 658.25 6408.00 32.25
LIVING_UNIT1_BACKROW_TOPFLOOR 1285.25 6587.75 334.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 2098.00 7346.25 602.75
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 8.75 0.00 8.75
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 352.00 18.50 352.00 18.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 61.50 6.50 61.50 6.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 343.75 17.50 343.75 17.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 50.75 24.50 50.75 24.50
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12.50 1.50 12.50 1.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.00 15.25 44.00 15.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.75 15.00 1.75 15.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 138.00 3.25 138.00 3.25
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 391.50 15.50 391.50 15.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 28.00 18.00 28.00 18.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 46.00 0.00 46.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12.00 19.50 12.00 19.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 31.50 19.50 31.50 19.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 178.00 16.50 178.00 16.50
LIVING_UNIT2_BACKROW_TOPFLOOR 24.25 19.00 24.25 19.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 10.50 18.25 10.50 18.25
LIVING_UNIT1_BACKROW_TOPFLOOR 240.00 15.75 240.00 15.75
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 1250.75 34.00 1250.75 34.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.274 0.000 0.277
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.235 0.000 0.276
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.268 0.000 0.276
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.266 0.000 0.276
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.235 0.000 0.276
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.267 0.000 0.276
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.117 0.000 0.276
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.086 0.000 0.276
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.118 0.000 0.276
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.117 0.000 0.276
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.085 0.000 0.276
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.117 0.000 0.276
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.268 0.000 0.276
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.267 0.000 0.276
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.235 0.000 0.276
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.236 0.000 0.276
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.267 0.000 0.276
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1867
Defaulted Fields 446
Fields with Defaults 4736
Autosized Fields 328
Autosizable Fields 438
Autocalculated Fields 99
Autocalculatable Fields 287



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
Electricity:Building 102912.40 6348.70 02-JAN-03:15 19791.35 01-JAN-18:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
General:InteriorLights:Electricity 14609.33 327.16 01-JAN-00:15 4758.75 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5717.36 352.71 02-JAN-03:15 1099.52 01-JAN-18:15
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.63 18.18 01-JAN-00:15 264.37 01-JAN-19:15
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:15 15497.32 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:15 985.58 01-JAN-19:15
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:15 1639.04 01-JAN-18:15
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:15 427.18 01-JAN-09:15
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:15 3196.73 01-JAN-11:15
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:15 3721.08 01-JAN-17:15
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:15 7929.96 01-JAN-20:15
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:15 526.17 01-JAN-20:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:15 860.96 01-JAN-18:15
Fans:Electricity 8039.38 143.38 27-AUG-00:45 3682.26 12-JUL-18:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityPurchased:Facility 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
ElectricityPurchased:Plant 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
Cogeneration:ElectricityPurchased 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
ElectricityNet:Facility 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
ElectricityNet:Plant 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
Cogeneration:ElectricityNet 128829.98 7499.17 15-JUN-03:30 38334.32 29-JUL-18:15
ExteriorLights:Electricity 3006.93 23.60 01-JAN-09:15 741.27 01-JAN-19:15
Exterior-Lights:ExteriorLights:Electricity 2444.89 0.00 01-JAN-06:15 558.19 01-JAN-00:15
Garage-Lights:ExteriorLights:Electricity 562.04 12.59 01-JAN-00:15 183.08 01-JAN-19:15
Electricity:HVAC 22910.64 547.16 18-JUN-02:30 18211.51 31-JUL-18:00
General:Fans:Electricity 8039.38 143.38 27-AUG-00:45 3682.26 12-JUL-18:15
Cooling:Electricity 14871.26 0.00 01-JAN-00:45 14529.25 31-JUL-18:00
Electricity:Plant 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Pumps:Electricity 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15


Annual and Peak Values - Gas

Gas Annual Value [therm] Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
Gas:Facility 6359.58 0.00 03-MAR-17:45 350841.88 13-JAN-08:30
Gas:Plant 6359.58 0.00 03-MAR-17:45 350841.88 13-JAN-08:30
WaterSystems:Gas 3140.94 0.00 01-JAN-00:15 116782.74 18-FEB-08:15
Water Heater:WaterSystems:Gas 3140.94 0.00 01-JAN-00:15 116782.74 18-FEB-08:15
Heating:Gas 3218.64 0.00 03-MAR-17:45 235490.47 13-JAN-08:15
Boiler:Heating:Gas 3218.64 0.00 03-MAR-17:45 235490.47 13-JAN-08:15


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
Water:Plant 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
WaterSystems:Water 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
MainsWater:Facility 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
MainsWater:Plant 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
WaterSystems:MainsWater 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Domestic Hot Water:WaterSystems:Water 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15
Domestic Hot Water:WaterSystems:MainsWater 56111.84 0.01 11-JAN-02:45 0.20 01-JAN-08:15


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:15 0.000 01-JAN-00:15


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
PlantLoopHeatingDemand:Facility 430584.36 1435.23 11-AUG-02:15 234377.39 13-JAN-08:15
PlantLoopHeatingDemand:Plant 173002.09 1435.21 14-AUG-02:15 46097.87 11-FEB-08:45
WaterSystems:PlantLoopHeatingDemand 173002.09 1435.21 14-AUG-02:15 46097.87 11-FEB-08:45
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Facility 1372206.36 15649.15 18-JUN-02:30 621072.63 13-JAN-08:15
EnergyTransfer:Building 467655.43 6701.35 27-AUG-00:45 198302.87 13-JAN-08:15
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer 269671.53 0.00 17-MAR-17:15 198302.87 13-JAN-08:15
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer 197983.90 0.00 01-JAN-00:45 162983.47 29-JUL-18:30
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63232.33 0.00 01-JAN-00:45 21365.31 29-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 64.32 0.00 01-JAN-00:15 3452.56 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63168.01 0.00 01-JAN-00:45 21365.31 29-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17276.29 0.00 23-JAN-14:15 14696.08 15-JAN-06:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11487.62 0.00 23-JAN-14:15 14696.08 15-JAN-06:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5788.67 0.00 01-JAN-00:15 5911.51 21-JUL-20:45
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 26113.53 0.00 04-FEB-13:00 12950.96 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 17298.89 0.00 04-FEB-13:00 12950.96 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8814.63 0.00 01-JAN-00:15 7672.18 22-JUL-09:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 27627.90 0.00 05-FEB-17:00 12956.05 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 20085.37 0.00 05-FEB-17:00 12956.05 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7542.54 0.00 01-JAN-00:15 11516.89 23-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 20313.83 0.00 03-MAR-17:45 10346.67 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 16053.85 0.00 03-MAR-17:45 10346.67 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4259.98 0.00 01-JAN-00:15 5430.27 21-JUN-20:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 26968.38 0.00 17-MAR-16:15 12960.39 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 19828.41 0.00 17-MAR-16:15 12960.39 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7139.97 0.00 01-JAN-00:15 7699.25 22-JUL-09:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21605.35 0.00 01-JAN-16:30 11685.05 14-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11206.59 0.00 01-JAN-16:30 10074.95 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10398.76 0.00 01-JAN-00:15 11685.05 14-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14942.15 0.00 06-JAN-13:45 7529.35 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8183.18 0.00 06-JAN-13:45 7529.35 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6758.96 0.00 01-JAN-00:15 5910.53 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21778.65 0.00 23-JAN-14:15 10103.58 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11861.26 0.00 23-JAN-14:15 10103.58 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9917.39 0.00 01-JAN-00:15 7581.71 22-JUL-09:45
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 22598.91 0.00 05-FEB-16:30 11241.58 14-JUL-18:45
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 14292.64 0.00 05-FEB-16:30 10119.72 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8306.27 0.00 01-JAN-00:15 11241.58 14-JUL-18:45
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 15451.05 0.00 02-MAR-20:45 7510.30 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10394.37 0.00 02-MAR-20:45 7510.30 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5056.68 0.00 01-JAN-00:15 5497.25 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22245.87 0.00 03-MAR-17:00 10124.39 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 14154.44 0.00 03-MAR-17:00 10124.39 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8091.43 0.00 01-JAN-00:15 7624.12 22-JUL-09:45
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:15 0.00 01-JAN-00:15
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 30519.02 0.00 03-MAR-18:15 14184.32 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 21464.73 0.00 03-MAR-18:15 14184.32 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 9054.29 0.00 01-JAN-00:15 8652.79 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 29225.12 0.00 05-FEB-13:15 14161.46 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19168.73 0.00 05-FEB-13:15 14161.46 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10056.38 0.00 01-JAN-00:15 8825.23 21-JUL-20:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 30025.56 0.00 23-JAN-15:45 14145.98 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 19421.10 0.00 23-JAN-15:45 14145.98 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10604.46 0.00 01-JAN-00:15 13250.79 14-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 23899.45 0.00 03-MAR-17:30 11578.87 13-JAN-08:45
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 17601.46 0.00 03-MAR-17:30 11578.87 13-JAN-08:45
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6297.99 0.00 01-JAN-00:15 7491.97 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 22378.49 0.00 05-FEB-13:15 11542.46 13-JAN-08:15
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15166.46 0.00 05-FEB-13:15 11542.46 13-JAN-08:15
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 7212.03 0.00 01-JAN-00:15 7566.20 21-JUL-21:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 31453.55 0.00 10-FEB-16:15 14183.68 13-JAN-08:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 21938.08 0.00 10-FEB-16:15 14183.68 13-JAN-08:30
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9515.48 0.00 01-JAN-00:15 13202.49 14-JUL-18:30
EnergyTransfer:Plant 430493.04 1435.23 11-AUG-02:15 231666.95 13-JAN-08:15
WaterSystems:EnergyTransfer 173002.09 1435.21 14-AUG-02:15 46097.87 11-FEB-08:45
Domestic Hot Water:WaterSystems:EnergyTransfer 173002.09 1435.21 14-AUG-02:15 46097.87 11-FEB-08:45
EnergyTransfer:HVAC 474057.89 6381.40 03-JUN-00:15 191102.81 13-JAN-08:15
HeatingCoils:EnergyTransfer 257582.27 0.00 03-MAR-17:45 191102.81 13-JAN-08:15
PlantLoopHeatingDemand:HVAC 257582.27 0.00 03-MAR-17:45 191102.81 13-JAN-08:15
HeatingCoils:PlantLoopHeatingDemand 257582.27 0.00 03-MAR-17:45 191102.81 13-JAN-08:15
CoolingCoils:EnergyTransfer 216475.62 0.00 01-JAN-00:45 178691.50 12-JUL-19:30
Boilers:EnergyTransfer 257490.95 0.00 03-MAR-17:45 188392.37 13-JAN-08:15



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 64.324 -5260.48 0.000 0.000 2879.036 2771.241 10464.601 9773.339 0.000 775.201 63753.948 0.000 -6980.48 0.000 -20333.29 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 11487.537 -482.07 0.000 0.000 3090.660 2771.241 10464.601 4378.205 0.000 730.081 0.835 0.000 -2630.92 0.000 -17106.10 -7396.65
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 17298.742 -734.06 0.000 0.000 3068.634 2771.241 10464.601 9961.864 0.000 775.491 0.000 0.000 -6335.43 0.000 -18613.65 -10576.90
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 20085.206 -628.12 0.000 0.000 3081.145 2771.241 10464.601 6805.214 0.000 774.941 0.000 0.000 -6810.35 0.000 -18364.22 -11265.25
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 16053.728 -354.76 0.000 0.000 3076.683 2771.241 10464.601 1066.690 0.000 730.520 0.000 0.000 -2849.11 0.000 -17301.24 -9753.14
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 19828.255 -594.60 0.000 0.000 3078.124 2771.241 10464.601 6769.388 0.000 775.852 0.000 0.000 -6531.63 0.000 -18499.05 -11516.84
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 11206.480 -865.98 0.000 0.000 3045.361 2771.241 10464.601 9866.671 0.000 565.377 0.000 0.000 -6771.91 0.000 -13340.90 -7408.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 8183.105 -562.87 0.000 0.000 3036.812 2771.241 10464.601 4350.901 0.000 521.521 0.000 0.000 -2717.16 0.000 -12220.66 -7631.41
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 11861.151 -825.89 0.000 0.000 3050.411 2771.241 10464.601 9909.641 0.000 566.013 0.000 0.000 -6475.65 0.000 -13353.92 -8876.13
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 14292.514 -691.73 0.000 0.000 3063.824 2771.241 10464.601 6771.267 0.000 565.729 0.000 0.000 -6955.66 0.000 -13162.90 -9504.35
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 10394.291 -421.11 0.000 0.000 3055.273 2771.241 10464.601 1056.813 0.000 521.686 0.000 0.000 -2911.97 0.000 -12094.88 -8200.38
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 14154.323 -673.83 0.000 0.000 3061.657 2771.241 10464.601 6728.398 0.000 566.254 0.000 0.000 -6670.48 0.000 -13260.36 -9724.22
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 21464.560 -754.02 0.000 0.000 3070.611 2771.241 10464.601 6745.183 0.000 769.010 0.000 0.000 -6640.58 0.000 -18585.54 -11004.82
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 19168.571 -837.47 0.000 0.000 3063.779 2771.241 10464.601 9955.379 0.000 769.133 0.000 0.000 -6427.64 0.000 -18666.39 -11042.33
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 19420.935 -883.11 0.000 0.000 3065.370 2771.241 10464.601 9930.554 0.000 769.350 0.000 0.000 -6670.41 0.000 -18585.42 -10561.78
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 17601.329 -524.48 0.000 0.000 3067.245 2771.241 10464.601 1058.785 0.000 726.002 0.000 0.000 -2891.29 0.000 -17409.09 -9090.85
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 15166.337 -600.60 0.000 0.000 3057.542 2771.241 10464.601 4367.488 0.000 725.455 0.000 0.000 -2688.93 0.000 -17504.05 -9147.67
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 21937.905 -792.43 0.000 0.000 3072.131 2771.241 10464.601 6762.744 0.000 770.187 0.000 0.000 -6912.76 0.000 -18501.20 -10849.38
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 9150.524 55946.157 0.000 0.000 0.000 -65096.68 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 4661.251 42579.992 0.000 0.000 0.000 -47241.24 -0.49
Total Facility 0.000 0.000 269669.293 -16487.61 0.000 0.000 54984.297 49882.340 188362.826 116258.525 0.000 26209.579 162280.933 0.000 -96872.36 0.000 -409240.79 -163550.77


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUL-18:23 0.00 0.00 0.00 -1.8 0.00 0.00 421.61 813.96 1748.06 8060.34 0.00 1889.64 8457.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 21-JUL-20:48 0.00 0.00 0.00 -0.5 0.00 0.00 425.02 902.05 1628.20 39.67 0.00 666.78 2279.80 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-09:17 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 116.28 1126.15 7284.30 0.00 713.57 0.00 0.00 0.00 0.00 0.00 -1683.0
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23-JUL-18:20 0.00 0.00 0.00 -1.0 0.00 0.00 426.89 813.96 1748.06 8318.51 0.00 1470.79 0.00 0.00 0.00 0.00 0.00 -1259.8
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 21-JUL-20:55 0.00 0.00 0.00 -0.5 0.00 0.00 422.38 902.05 1628.20 41.82 0.00 670.01 1828.53 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 22-JUL-09:17 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 116.28 1126.15 7147.42 0.00 713.60 0.00 0.00 0.00 0.00 0.00 -1519.0
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 14-JUL-18:33 0.00 0.00 0.00 -1.0 0.00 0.00 426.22 813.96 1724.99 7028.41 0.00 1041.37 673.63 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21-JUL-20:58 0.00 0.00 0.00 -0.5 0.00 0.00 422.54 902.05 1628.20 41.43 0.00 510.44 2427.75 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-09:32 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 116.28 1126.15 6843.18 0.00 574.13 0.00 0.00 0.00 0.00 0.00 -1192.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 14-JUL-18:33 0.00 0.00 0.00 -0.9 0.00 0.00 424.81 813.96 1724.99 7266.75 0.00 1035.11 0.00 0.00 0.00 0.00 0.00 -3.5
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 21-JUN-20:47 0.00 0.00 0.00 -0.5 0.00 0.00 427.01 902.05 1628.20 51.99 0.00 503.73 2019.45 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 22-JUL-09:45 0.00 0.00 0.00 -0.6 0.00 0.00 115.16 116.28 1126.15 6686.10 0.00 574.14 0.00 0.00 0.00 0.00 0.00 -993.4
LIVING_UNIT3_BACKROW_TOPFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.7 0.00 0.00 423.06 902.05 1628.20 169.51 0.00 875.96 4768.17 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 21-JUL-20:33 0.00 0.00 0.00 -0.7 0.00 0.00 425.11 902.05 1628.20 175.76 0.00 886.42 4923.81 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.1 0.00 0.00 423.38 813.96 1724.99 7792.84 0.00 1551.22 959.65 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 21-JUL-21:00 0.00 0.00 0.00 -0.6 0.00 0.00 419.12 902.05 1628.20 22.88 0.00 656.18 3876.64 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-21:00 0.00 0.00 0.00 -0.6 0.00 0.00 419.14 902.05 1628.20 25.06 0.00 656.61 3948.51 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 20-JUL-18:19 0.00 0.00 0.00 -1.1 0.00 0.00 423.34 813.96 1724.99 7971.95 0.00 1550.85 720.46 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUL-18:19 0.00 0.00 0.00 -13.6 0.00 0.00 7529.94 14651.21 31465.06 62579.10 0.00 44129.74 15333.45 0.00 0.00 0.00 -12295.5 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 3452.44 0.00 0.00 0.00 215.06 170.54 1155.86 0.00 0.00 0.00 5847.14 0.00 -2926.4 0.00 -7914.6 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11-JAN-08:03 0.00 0.00 15458.80 0.00 0.00 0.00 287.13 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -786.6 0.00 -4001.0 -12284.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15-MAR-06:28 0.00 0.00 15157.99 0.00 0.00 0.00 526.31 434.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2142.2 0.00 -4790.3 -10263.9
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 04-APR-11:23 0.00 0.00 20656.17 0.00 0.00 0.00 144.38 116.28 1092.38 579.17 0.00 0.00 0.00 0.00 0.00 0.00 -3089.0 -19499.4
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 08-MAR-18:49 0.00 0.00 12979.75 0.00 0.00 0.00 472.06 813.96 1724.99 0.00 0.00 0.00 0.00 0.00 -622.1 0.00 -2769.2 -12599.5
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 13-JAN-08:15 0.00 0.00 12959.98 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2919.5 0.00 -7914.8 -3667.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 09-APR-11:05 0.00 0.00 14086.64 0.00 0.00 0.00 131.74 116.28 1122.49 3086.21 0.00 0.00 0.00 0.00 0.00 0.00 -1388.4 -17155.0
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 7529.09 0.00 0.00 0.00 215.04 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1204.3 0.00 -4877.9 -2988.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 10103.24 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2965.7 0.00 -5410.8 -3268.2
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 13-MAY-10:09 0.00 0.00 19851.98 0.00 0.00 0.00 135.39 116.28 1121.12 507.26 0.00 0.00 0.00 0.00 0.00 0.00 -1212.0 -20520.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 26-FEB-17:54 0.00 0.00 12644.28 0.00 0.00 0.00 304.91 604.65 1685.13 0.00 0.00 0.00 0.00 0.00 -560.1 0.00 -2053.4 -12625.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 13-JAN-08:15 0.00 0.00 10124.05 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2963.3 0.00 -5411.0 -3291.2
LIVING_UNIT3_BACKROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 14183.88 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2950.2 0.00 -7924.7 -4850.4
LIVING_UNIT3_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 14161.02 0.00 0.00 0.00 215.05 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -2950.4 0.00 -7924.7 -4827.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 13-MAY-10:08 0.00 0.00 20670.87 0.00 0.00 0.00 140.49 116.28 1121.12 913.40 0.00 0.00 0.00 0.00 0.00 0.00 -1440.2 -21521.9
LIVING_UNIT2_BACKROW_TOPFLOOR 13-JAN-08:45 0.00 0.00 11578.38 0.00 0.00 0.00 215.03 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1103.9 0.00 -7391.7 -4624.2
LIVING_UNIT2_FRONTROW_TOPFLOOR 13-JAN-08:15 0.00 0.00 11542.08 0.00 0.00 0.00 215.03 170.54 1155.86 0.00 0.00 0.00 0.00 0.00 -1195.8 0.00 -7391.6 -4496.1
LIVING_UNIT1_BACKROW_TOPFLOOR 18-DEC-17:36 0.00 0.00 19805.42 0.00 0.00 0.00 315.07 604.65 1664.02 0.00 0.00 0.00 0.00 0.00 -1387.1 0.00 -2673.8 -18328.2
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 13-JAN-08:15 0.00 0.00 198296.47 0.00 0.00 0.00 3870.84 3069.78 20805.49 0.00 0.00 1096.43 0.00 0.00 -42524.6 0.00 -159861.1 -24753.3



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 956.973 2.00 2.00 1.00 44.9950 956.973 0.047 1.000 44.9950 0.05
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 256.341 2.00 2.00 1.00 44.9950 256.341 0.176 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.622 2.00 2.00 1.00 44.9950 340.622 0.132 1.000 44.9950 0.13
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 504.783 2.00 2.00 1.00 44.9950 504.783 0.089 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 235.130 2.00 2.00 1.00 44.9950 235.130 0.191 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.838 2.00 2.00 1.00 44.9950 328.838 0.137 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.827 2.00 2.00 1.00 44.9950 513.827 0.088 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.906 2.00 2.00 1.00 44.9950 252.906 0.178 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.107 2.00 2.00 1.00 44.9950 331.107 0.136 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.553 2.00 2.00 1.00 44.9950 493.553 0.091 1.000 44.9950 0.09
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 234.460 2.00 2.00 1.00 44.9950 234.460 0.192 1.000 44.9950 0.19
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.759 2.00 2.00 1.00 44.9950 324.759 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 584.752 2.00 2.00 1.00 44.9950 584.752 0.077 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.924 2.00 2.00 1.00 44.9950 323.924 0.139 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 387.944 2.00 2.00 1.00 44.9950 387.944 0.116 1.000 44.9950 0.12
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 581.960 2.00 2.00 1.00 44.9950 581.960 0.077 1.000 44.9950 0.08
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 320.734 2.00 2.00 1.00 44.9950 320.734 0.140 1.000 44.9950 0.14
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 380.194 2.00 2.00 1.00 44.9950 380.194 0.118 1.000 44.9950 0.12


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 78.190 2.00 2.00 1.00 44.9950 78.190 1.000 1.000 44.9950 0.58
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 220.456 2.00 2.00 1.00 44.9950 220.456 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 275.150 2.00 2.00 1.00 44.9950 275.150 1.000 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 275.245 2.00 2.00 1.00 44.9950 275.245 1.000 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 220.466 2.00 2.00 1.00 44.9950 220.466 1.000 1.000 44.9950 0.20
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 275.094 2.00 2.00 1.00 44.9950 275.094 1.000 1.000 44.9950 0.16
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 216.011 2.00 2.00 1.00 44.9950 216.011 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 161.419 2.00 2.00 1.00 44.9950 161.419 1.000 1.000 44.9950 0.28
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 216.088 2.00 2.00 1.00 44.9950 216.088 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 216.083 2.00 2.00 1.00 44.9950 216.083 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 161.415 2.00 2.00 1.00 44.9950 161.415 1.000 1.000 44.9950 0.28
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 216.027 2.00 2.00 1.00 44.9950 216.027 1.000 1.000 44.9950 0.21
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 301.342 2.00 2.00 1.00 44.9950 301.342 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 246.729 2.00 2.00 1.00 44.9950 246.729 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 301.440 2.00 2.00 1.00 44.9950 301.440 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 301.361 2.00 2.00 1.00 44.9950 301.361 1.000 1.000 44.9950 0.15
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 246.707 2.00 2.00 1.00 44.9950 246.707 1.000 1.000 44.9950 0.18
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 301.378 2.00 2.00 1.00 44.9950 301.378 1.000 1.000 44.9950 0.15


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 1.000 44.9950 1.000 44.9950


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.55 44.9950 44.9950 44.9950


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   956.973 956.9729 191.3946 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   256.341 256.3405 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   340.622 340.6221 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   504.783 504.7828 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   235.130 235.1303 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   328.838 328.8381 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   513.827 513.8267 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   252.906 252.9062 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   331.107 331.1070 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   493.553 493.5525 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   234.460 234.4604 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   324.759 324.7595 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   380.194 380.1942 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   387.944 387.9440 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   584.752 584.7518 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   320.734 320.7343 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   323.924 323.9239 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   581.960 581.9598 180.0453 44.9950 0.000 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 956.97 956.973 956.97 191.3946 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 256.34 256.341 256.34 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.62 340.622 340.62 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 504.78 504.783 504.78 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 235.13 235.130 235.13 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.84 328.838 328.84 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.83 513.827 513.83 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.91 252.906 252.91 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.11 331.107 331.11 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.55 493.553 493.55 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 234.46 234.460 234.46 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.76 324.759 324.76 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 584.75 584.752 584.75 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.92 323.924 323.92 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 387.94 387.944 387.94 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 581.96 581.960 581.96 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 320.73 320.734 320.73 180.0453 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 380.19 380.194 380.19 180.0453 44.9950 1.000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR   78.190 78.190 78.190 44.9950 0.575 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR   220.456 220.456 220.456 44.9950 0.204 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR   275.150 275.150 275.150 44.9950 0.164 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR   275.245 275.245 275.245 44.9950 0.163 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR   220.466 220.466 220.466 44.9950 0.204 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR   275.094 275.094 275.094 44.9950 0.164 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR   216.011 216.011 216.011 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR   161.419 161.419 161.419 44.9950 0.279 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR   216.088 216.088 216.088 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR   216.083 216.083 216.083 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR   161.415 161.415 161.415 44.9950 0.279 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR   216.027 216.027 216.027 44.9950 0.208 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR   301.378 301.378 301.378 44.9950 0.149 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR   301.440 301.440 301.440 44.9950 0.149 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR   301.342 301.342 301.342 44.9950 0.149 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR   246.707 246.707 246.707 44.9950 0.182 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR   246.729 246.729 246.729 44.9950 0.182 1.000 0.000 0.000 0.000 0.000 1.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR   301.361 301.361 301.361 44.9950 0.149 1.000 0.000 0.000 0.000 0.000 1.000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 78.19 78.190 78.19 78.19 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 220.46 220.456 220.46 220.46 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 275.15 275.150 275.15 275.15 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 275.24 275.245 275.24 275.24 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 220.47 220.466 220.47 220.47 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 275.09 275.094 275.09 275.09 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 216.01 216.011 216.01 216.01 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 161.42 161.419 161.42 161.42 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 216.09 216.088 216.09 216.09 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 216.08 216.083 216.08 216.08 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 161.41 161.415 161.41 161.41 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 216.03 216.027 216.03 216.03 44.9950 1.000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 301.34 301.342 301.34 301.34 44.9950 1.000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 246.73 246.729 246.73 246.73 44.9950 1.000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 301.44 301.440 301.44 301.44 44.9950 1.000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 301.36 301.361 301.36 301.36 44.9950 1.000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 246.71 246.707 246.71 246.71 44.9950 1.000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 301.38 301.378 301.38 301.38 44.9950 1.000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Sec1.1A-General Information

Data
Weather File ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Total gross floor area [ft2] 39005.17
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.13 0.00 1798.13 0.00
ATTIC 7802.69 0.00 7802.69 0.00
Totals 39005.17 21609.96 17395.21  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1250.75
Number of hours cooling loads not met 34.00
Number of hours not met 1284.75


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electric Energy Use [kWh] Electric Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Additional Energy Use [kBtu] Additional Demand [Btu/h]
Interior Lighting 14609.33 4294.03 0.00 0.00 0.00 0.00
Exterior Lighting 3006.93 723.39 0.00 0.00 0.00 0.00
Space Heating 0.00 0.00 3218.64 234522.68 0.00 0.00
Space Cooling 14871.26 14142.76 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00
Fans-Interior 8039.38 3676.83 0.00 0.00 0.00 0.00
Fans-Parking Garage 0.00 0.00 0.00 0.00 0.00 0.00
Service Water Heating 0.00 0.00 3140.94 116319.21 0.00 0.00
Receptacle Equipment 88303.07 15497.32 0.00 0.00 0.00 0.00
Interior Lighting-Process 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration Equipment 0.00 0.00 0.00 0.00 0.00 0.00
Cooking 0.00 0.00 0.00 0.00 0.00 0.00
Industrial Process 0.00 0.00 0.00 0.00 0.00 0.00
Elevators and Escalators 0.00 0.00 0.00 0.00 0.00 0.00
Total Line 128829.98   6359.58   0.00  


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 439879.30
Natural Gas 0.00 635958.09
Additional 0.00 0.00
Total 301503.54 1075837.38


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting 0.37
Space Heating 0.00
Space Cooling 0.38
Fans-Interior 0.21
Service Water Heating 0.00
Receptacle Equipment 2.26
Miscellaneous 0.08
Subtotal 3.30


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 2.42
Service Water Heating 2.36
Miscellaneous -0.0
Subtotal 4.78


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Miscellaneous 0.00
Subtotal 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting 4.64
Space Heating 29.92
Space Cooling 4.72
Fans-Interior 2.55
Service Water Heating 29.20
Receptacle Equipment 28.03
Miscellaneous 0.95



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

AirTerminal:SingleDuct:Uncontrolled

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 956.97
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 256.34
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 340.62
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 504.78
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 235.13
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 328.84
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 513.83
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 252.91
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 331.11
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 493.55
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 234.46
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 324.76
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 380.19
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 387.94
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 584.75
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 320.73
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 323.92
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 581.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 956.97
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 256.34
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 340.62
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 504.78
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 235.13
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 328.84
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 513.83
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 252.91
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 331.11
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 493.55
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 234.46
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.76
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 584.75
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 323.92
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 387.94
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 581.96
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 320.73
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 380.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 956.97 2.13 0.798655
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 256.34 0.569480 0.798655
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 340.62 0.759909 0.797111
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 504.78 1.12 0.798655
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 235.13 0.522360 0.798655
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 328.84 0.730538 0.798655
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 513.83 1.14 0.798655
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 252.91 0.561850 0.798655
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 331.11 0.740414 0.796254
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 493.55 1.10 0.798655
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 234.46 0.520871 0.798655
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 324.76 0.721478 0.798655
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 584.75 1.30 0.798655
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 323.92 0.719621 0.798655
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 387.94 0.861847 0.798655
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 581.96 1.29 0.798655
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 320.73 0.712535 0.798655
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 380.19 0.844630 0.798655
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 956.97 956.97 956.97 2.13 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 256.34 256.34 256.34 0.569480 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 340.62 340.62 340.62 0.759909 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 504.78 504.78 504.78 1.12 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 235.13 235.13 235.13 0.522360 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 328.84 328.84 328.84 0.730538 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 513.83 513.83 513.83 1.14 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 252.91 252.91 252.91 0.561850 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 331.11 331.11 331.11 0.740414 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 493.55 493.55 493.55 1.10 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 234.46 234.46 234.46 0.520871 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 324.76 324.76 324.76 0.721478 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 584.75 584.75 584.75 1.30 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 323.92 323.92 323.92 0.719621 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 387.94 387.94 387.94 0.861847 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 581.96 581.96 581.96 1.29 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 320.73 320.73 320.73 0.712535 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 380.19 380.19 380.19 0.844630 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Design Coil Load [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 50765.09 5.12 720.73
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 15873.78 1.60 213.32
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 20072.25 2.03 274.47
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 28249.28 2.85 393.28
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 14817.31 1.50 197.89
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 19485.27 1.97 265.93
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 28696.86 2.90 399.72
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 15701.40 1.58 210.78
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 19596.52 1.98 267.51
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 27687.11 2.79 385.07
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 14782.74 1.49 197.35
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 19280.38 1.95 262.91
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 32232.62 3.25 451.02
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 19240.08 1.94 262.37
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 22429.40 2.26 308.71
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 32093.54 3.24 449.01
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 19081.21 1.93 260.06
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 22043.37 2.22 303.10
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 956.97
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 256.34
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 340.62
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 504.78
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 235.13
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 328.84
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 513.83
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 252.91
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 331.11
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 493.55
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 234.46
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 324.76
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 584.75
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 323.92
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 387.94
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 581.96
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 320.73
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 380.19
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.69 106.80
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 19.59
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 19.59
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 19.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.69
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 423701.75 42.61
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2019-02-14 08:40:10

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 525.217 31.070 42.102 1.154 32.224
February 650.012 54.481 0.000 0.000 54.481
March 742.733 82.759 0.000 0.000 82.759
April 720.000 117.835 0.000 0.000 117.835
May 744.000 141.894 0.000 0.000 141.894
June 720.000 171.201 0.000 0.000 171.201
July 744.000 206.634 0.000 0.000 206.634
August 744.000 186.781 0.000 0.000 186.781
September 720.000 157.454 0.000 0.000 157.454
October 744.000 123.009 0.000 0.000 123.009
November 673.467 64.635 0.000 0.000 64.635
December 667.946 48.255 0.000 0.000 48.255
           
Annual Sum or Average 8395.377 1386.009 42.102 1.154 1387.162
Minimum of Months 525.217 31.070 0.000 0.000 32.224
Maximum of Months 744.000 206.634 42.102 1.154 206.634



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 564.403 16.913 39.595
February 7.325 0.091 595.400 11.263 14.177
March 38.146 0.716 597.754 8.923 9.802
April 155.079 5.275 335.763 3.535 8.811
May 217.731 8.111 244.038 1.507 9.618
June 430.336 22.341 73.292 0.492 22.833
July 642.137 40.118 5.021 0.011 40.129
August 506.205 29.658 43.375 0.183 29.842
September 368.866 19.345 109.475 0.557 19.902
October 184.177 7.150 326.833 2.918 10.067
November 26.542 0.791 584.405 10.197 16.961
December 2.312 0.031 631.030 13.343 23.137
           
Annual Sum or Average 2578.856 133.629 4110.787 69.843 244.875
Minimum of Months 0.000 0.000 5.021 0.011 8.811
Maximum of Months 642.137 40.118 631.030 16.913 40.129



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 741.000 49.644 50.132
February 4.177 0.029 614.525 29.042 31.142
March 44.872 1.240 565.708 21.431 26.143
April 195.625 8.854 274.948 8.050 23.259
May 301.173 14.616 187.729 3.814 25.861
June 480.916 36.252 45.417 0.957 40.907
July 650.598 59.428 2.125 0.032 60.188
August 541.706 43.722 27.125 0.514 48.630
September 390.278 27.102 86.000 1.631 34.995
October 195.075 9.568 296.375 7.868 25.634
November 25.226 0.849 626.617 28.730 32.324
December 1.179 0.008 706.808 38.275 40.227
           
Annual Sum or Average 2830.826 201.668 4174.377 189.989 439.442
Minimum of Months 0.000 0.000 2.125 0.032 23.259
Maximum of Months 650.598 59.428 741.000 49.644 60.188



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.917 59.013 59.034
February 0.000 0.000 632.469 36.678 45.305
March 13.208 0.471 600.552 27.604 46.739
April 127.917 6.256 332.043 10.766 37.635
May 214.779 14.138 250.928 4.948 30.794
June 415.482 36.347 80.471 1.444 44.566
July 612.404 57.558 10.192 0.078 58.036
August 472.667 40.681 69.996 0.944 45.406
September 288.715 18.601 157.853 2.566 29.340
October 79.482 3.809 397.494 11.922 40.340
November 1.417 0.015 658.971 36.244 46.947
December 0.000 0.000 721.826 47.385 52.859
           
Annual Sum or Average 2226.070 177.875 4656.712 239.593 537.002
Minimum of Months 0.000 0.000 10.192 0.078 29.340
Maximum of Months 612.404 57.558 743.917 59.013 59.034



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 25.835 25.835
February 0.000 0.000 667.269 15.621 16.125
March 2.700 0.033 675.930 11.929 16.102
April 87.946 2.169 396.170 4.805 10.137
May 172.912 5.562 263.460 1.923 9.353
June 424.059 20.661 75.867 0.589 22.017
July 643.838 37.040 4.808 0.012 37.056
August 474.139 23.516 55.489 0.264 23.824
September 274.359 9.257 150.621 0.916 10.675
October 51.958 1.295 483.236 5.007 9.055
November 0.000 0.000 703.002 15.145 15.990
December 0.000 0.000 743.368 19.690 19.751
           
Annual Sum or Average 2131.912 99.533 4963.220 101.735 215.920
Minimum of Months 0.000 0.000 4.808 0.012 9.055
Maximum of Months 643.838 37.040 744.000 25.835 37.056



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 55.458 55.458
February 0.000 0.000 671.460 35.376 35.449
March 8.494 0.209 697.317 26.306 27.332
April 142.531 4.981 346.744 9.751 19.242
May 274.559 11.844 210.163 4.269 22.044
June 477.946 34.782 55.021 1.046 39.039
July 651.640 56.710 2.125 0.031 57.468
August 531.537 37.793 34.083 0.615 42.315
September 336.252 16.806 108.292 2.019 24.359
October 77.955 2.748 454.564 11.154 18.621
November 0.000 0.000 704.673 34.730 34.884
December 0.000 0.000 743.888 44.901 44.919
           
Annual Sum or Average 2500.915 165.872 4772.328 225.655 421.131
Minimum of Months 0.000 0.000 2.125 0.031 18.621
Maximum of Months 651.640 56.710 744.000 55.458 57.468



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.667 0.003 721.413 38.865 38.868
February 19.583 0.644 553.187 21.139 21.782
March 80.600 3.701 519.292 15.806 20.853
April 225.028 13.336 242.876 5.491 25.816
May 301.709 20.354 149.363 2.014 28.897
June 484.148 41.775 36.437 0.522 45.318
July 665.462 64.112 2.326 0.006 64.244
August 543.360 50.368 25.790 0.241 52.058
September 407.775 32.785 71.799 0.801 36.619
October 224.043 13.557 285.658 5.548 21.587
November 37.500 1.422 582.779 21.110 22.532
December 6.208 0.114 675.575 28.829 28.944
           
Annual Sum or Average 2996.084 242.169 3866.495 140.372 407.517
Minimum of Months 0.667 0.003 2.326 0.006 20.853
Maximum of Months 665.462 64.112 721.413 38.865 64.244



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 717.246 15.254 15.528
February 13.567 0.230 538.817 7.682 9.278
March 60.720 1.302 493.829 5.626 7.879
April 208.307 7.173 225.649 1.881 9.374
May 288.234 10.694 135.463 0.696 11.680
June 507.486 25.766 34.417 0.184 25.961
July 700.228 43.783 0.000 0.000 43.783
August 581.763 33.050 16.222 0.041 33.101
September 441.159 22.806 52.582 0.206 23.014
October 245.837 9.318 236.383 1.554 10.894
November 40.500 1.123 549.175 7.609 9.150
December 5.250 0.065 658.075 10.569 10.994
           
Annual Sum or Average 3093.051 155.311 3657.858 51.303 210.637
Minimum of Months 0.000 0.000 0.000 0.000 7.879
Maximum of Months 700.228 43.783 717.246 15.254 43.783



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 719.404 35.721 37.478
February 8.024 0.126 548.375 19.926 25.898
March 61.909 1.912 473.037 13.906 23.360
April 252.567 11.231 173.417 4.263 24.175
May 356.529 18.055 102.233 1.713 26.815
June 531.800 40.036 17.375 0.312 42.326
July 688.730 62.880 0.000 0.000 63.049
August 587.449 47.177 7.625 0.111 49.387
September 446.134 30.645 38.125 0.589 36.620
October 240.832 11.789 206.125 4.244 26.370
November 30.414 1.084 549.887 19.828 29.027
December 2.312 0.032 662.246 26.920 32.513
           
Annual Sum or Average 3206.701 224.966 3497.850 127.532 417.019
Minimum of Months 0.000 0.000 0.000 0.000 23.360
Maximum of Months 688.730 62.880 719.404 35.721 63.049



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 733.453 44.561 47.086
February 0.000 0.000 590.780 26.097 43.133
March 21.771 0.607 541.884 18.811 42.324
April 168.379 7.800 251.381 6.096 33.467
May 267.709 16.647 171.200 2.500 28.686
June 474.377 39.621 35.983 0.541 44.987
July 665.368 61.111 2.554 0.006 61.323
August 519.932 43.773 32.031 0.324 46.147
September 345.668 21.305 94.658 1.171 27.580
October 107.376 4.467 329.101 7.444 34.156
November 1.300 0.012 619.283 26.162 43.314
December 0.000 0.000 704.490 35.248 44.799
           
Annual Sum or Average 2571.880 195.343 4106.797 168.961 497.003
Minimum of Months 0.000 0.000 2.554 0.006 27.580
Maximum of Months 665.368 61.111 733.453 44.561 61.323



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.668 16.986 17.025
February 0.000 0.000 660.539 10.195 11.383
March 5.625 0.081 637.159 7.326 11.748
April 127.441 3.377 292.244 2.423 8.150
May 254.721 8.036 157.423 0.781 9.327
June 506.929 24.331 39.354 0.193 24.555
July 704.452 40.992 0.000 0.000 40.992
August 552.222 26.970 19.583 0.050 27.030
September 354.716 12.137 78.054 0.324 12.519
October 70.742 1.832 371.970 2.694 6.254
November 0.000 0.000 673.600 9.888 10.414
December 0.000 0.000 743.081 12.972 13.074
           
Annual Sum or Average 2576.848 117.755 4416.675 63.831 192.470
Minimum of Months 0.000 0.000 0.000 0.000 6.254
Maximum of Months 704.452 40.992 743.668 16.986 40.992



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 41.765 41.765
February 0.000 0.000 671.158 25.921 26.028
March 11.518 0.305 659.146 17.753 20.381
April 179.898 6.707 230.273 5.309 18.575
May 342.404 15.331 117.991 1.948 23.881
June 532.534 38.882 18.063 0.350 41.023
July 689.441 60.622 0.000 0.000 60.774
August 579.053 41.622 8.750 0.139 43.904
September 395.725 20.107 48.479 0.783 26.076
October 99.694 3.511 336.794 6.407 18.980
November 0.000 0.000 673.839 25.453 28.004
December 0.000 0.000 743.950 33.491 33.499
           
Annual Sum or Average 2830.268 187.088 4252.443 159.321 382.892
Minimum of Months 0.000 0.000 0.000 0.000 18.575
Maximum of Months 689.441 60.622 744.000 41.765 60.774



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 740.563 68.127 68.127
February 7.292 0.147 621.467 40.442 40.610
March 50.208 2.188 594.971 31.316 36.793
April 181.933 11.696 263.117 11.064 47.556
May 253.025 20.365 196.701 5.272 42.124
June 437.435 44.945 52.277 1.295 56.909
July 631.198 70.945 4.554 0.056 72.016
August 502.288 53.660 39.603 0.803 60.909
September 355.040 31.929 99.737 2.319 47.067
October 162.175 10.910 348.954 12.525 34.230
November 20.292 0.770 654.504 40.380 41.149
December 0.000 0.000 727.446 53.471 53.471
           
Annual Sum or Average 2600.887 247.555 4343.893 267.069 600.962
Minimum of Months 0.000 0.000 4.554 0.056 34.230
Maximum of Months 631.198 70.945 740.563 68.127 72.016



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 740.500 26.724 27.236
February 0.000 0.000 616.896 15.504 17.988
March 26.208 0.652 596.791 11.921 14.927
April 164.817 6.622 327.648 4.683 13.091
May 244.502 11.583 231.116 2.136 14.698
June 452.486 29.572 71.272 0.651 30.301
July 661.088 50.959 4.964 0.014 50.978
August 523.007 36.929 42.342 0.261 37.244
September 374.574 22.529 116.744 0.863 23.448
October 164.695 7.142 349.489 4.286 11.634
November 22.083 0.539 644.008 15.135 17.298
December 0.000 0.000 721.863 20.233 20.427
           
Annual Sum or Average 2633.461 166.528 4463.634 102.413 279.268
Minimum of Months 0.000 0.000 4.964 0.014 11.634
Maximum of Months 661.088 50.959 740.500 26.724 50.978



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 743.938 51.463 51.475
February 0.000 0.000 636.408 30.830 32.502
March 34.581 1.015 598.554 22.621 26.655
April 194.202 9.845 291.625 8.139 23.589
May 313.998 17.716 183.500 3.721 27.997
June 499.261 43.006 45.958 0.874 46.743
July 670.347 69.594 1.500 0.015 70.315
August 553.329 50.322 24.750 0.435 54.305
September 396.807 29.754 91.896 1.673 36.820
October 171.871 9.196 320.573 8.459 25.342
November 21.167 0.597 653.329 30.542 33.155
December 0.000 0.000 723.721 40.440 41.856
           
Annual Sum or Average 2855.563 231.045 4315.752 199.212 470.755
Minimum of Months 0.000 0.000 1.500 0.015 23.589
Maximum of Months 670.347 69.594 743.938 51.463 70.315



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 65.484 65.484
February 0.000 0.000 646.921 41.013 46.879
March 16.646 0.685 613.893 30.726 45.130
April 150.312 8.901 322.127 11.810 37.474
May 241.772 19.022 226.579 5.172 37.057
June 438.655 44.708 71.465 1.505 52.365
July 633.456 70.183 9.045 0.067 70.815
August 490.906 50.432 56.256 0.819 56.147
September 316.673 24.214 143.004 2.636 36.686
October 95.435 4.997 392.653 13.284 44.236
November 1.104 0.008 675.058 40.922 47.013
December 0.000 0.000 733.038 53.159 56.266
           
Annual Sum or Average 2384.958 223.152 4634.038 266.598 595.553
Minimum of Months 0.000 0.000 9.045 0.067 36.686
Maximum of Months 633.456 70.183 744.000 65.484 70.815



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 29.348 29.348
February 0.000 0.000 669.125 18.459 18.874
March 7.250 0.139 663.669 13.937 18.353
April 120.025 4.420 361.103 5.306 12.853
May 233.341 10.492 239.429 2.217 13.909
June 455.334 29.499 70.051 0.644 30.341
July 665.133 50.271 4.625 0.011 50.282
August 509.838 33.890 46.584 0.279 34.199
September 313.023 15.180 140.836 1.070 16.459
October 67.773 2.412 467.065 6.021 10.404
November 0.000 0.000 696.667 17.967 18.577
December 0.000 0.000 743.600 23.300 23.348
           
Annual Sum or Average 2371.717 146.302 4846.754 118.560 276.947
Minimum of Months 0.000 0.000 4.625 0.011 10.404
Maximum of Months 665.133 50.271 744.000 29.348 50.282



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRIC ENERGY [kWh]
January 0.000 0.000 744.000 55.091 55.091
February 0.000 0.000 671.958 34.988 34.996
March 11.125 0.334 686.578 25.509 27.168
April 160.063 7.246 324.396 8.948 21.201
May 308.144 16.565 191.033 3.819 26.583
June 500.547 42.857 47.333 0.877 46.501
July 671.385 68.732 1.375 0.014 69.460
August 546.291 47.231 26.500 0.455 51.253
September 357.223 22.138 105.125 1.849 29.353
October 89.228 3.826 439.979 10.850 20.884
November 0.000 0.000 698.783 34.591 35.459
December 0.000 0.000 743.900 44.857 44.876
           
Annual Sum or Average 2644.006 208.929 4680.961 221.847 462.823
Minimum of Months 0.000 0.000 1.375 0.014 20.884
Maximum of Months 671.385 68.732 744.000 55.091 69.460



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.18
February 0.00 0.00 0.34
March 0.00 0.00 0.47
April 0.00 0.00 0.68
May 0.00 0.00 0.79
June 0.00 0.00 0.97
July 0.00 0.00 1.11
August 0.00 0.00 1.02
September 0.00 0.00 0.90
October 0.00 0.00 0.69
November 0.00 0.00 0.38
December 0.00 0.00 0.27
       
Annual Sum or Average 0.00 0.00 0.65
Minimum of Months 0.00 0.00 0.18
Maximum of Months 0.00 0.00 1.11



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.04
June 0.00 0.00 0.12
July 0.00 0.00 0.21
August 0.00 0.00 0.16
September 0.00 0.00 0.11
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.08
June 0.00 0.00 0.20
July 0.00 0.00 0.32
August 0.00 0.00 0.23
September 0.00 0.00 0.15
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.07
June 0.00 0.00 0.20
July 0.00 0.00 0.30
August 0.00 0.00 0.21
September 0.00 0.00 0.10
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.03
June 0.00 0.00 0.11
July 0.00 0.00 0.20
August 0.00 0.00 0.12
September 0.00 0.00 0.05
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.06
June 0.00 0.00 0.19
July 0.00 0.00 0.30
August 0.00 0.00 0.20
September 0.00 0.00 0.09
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.02
April 0.00 0.00 0.07
May 0.00 0.00 0.11
June 0.00 0.00 0.23
July 0.00 0.00 0.33
August 0.00 0.00 0.26
September 0.00 0.00 0.18
October 0.00 0.00 0.07
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.14
July 0.00 0.00 0.23
August 0.00 0.00 0.18
September 0.00 0.00 0.13
October 0.00 0.00 0.05
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.10
June 0.00 0.00 0.22
July 0.00 0.00 0.34
August 0.00 0.00 0.25
September 0.00 0.00 0.17
October 0.00 0.00 0.06
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.09
June 0.00 0.00 0.22
July 0.00 0.00 0.32
August 0.00 0.00 0.23
September 0.00 0.00 0.11
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.04
June 0.00 0.00 0.14
July 0.00 0.00 0.22
August 0.00 0.00 0.14
September 0.00 0.00 0.07
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.08
June 0.00 0.00 0.22
July 0.00 0.00 0.33
August 0.00 0.00 0.22
September 0.00 0.00 0.11
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.11
June 0.00 0.00 0.24
July 0.00 0.00 0.37
August 0.00 0.00 0.28
September 0.00 0.00 0.17
October 0.00 0.00 0.06
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.06
June 0.00 0.00 0.16
July 0.00 0.00 0.27
August 0.00 0.00 0.20
September 0.00 0.00 0.12
October 0.00 0.00 0.04
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.09
June 0.00 0.00 0.24
July 0.00 0.00 0.37
August 0.00 0.00 0.27
September 0.00 0.00 0.16
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.10
June 0.00 0.00 0.24
July 0.00 0.00 0.36
August 0.00 0.00 0.26
September 0.00 0.00 0.13
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.36



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.06
June 0.00 0.00 0.16
July 0.00 0.00 0.27
August 0.00 0.00 0.18
September 0.00 0.00 0.08
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

HEATING COIL TOTAL HEATING RATE [Invalid/Undefined] HEATING COIL AIR HEATING RATE [Invalid/Undefined] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.09
June 0.00 0.00 0.24
July 0.00 0.00 0.37
August 0.00 0.00 0.25
September 0.00 0.00 0.12
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92
Maximum of Months 0.00 0.00 1841.94 1353.75



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2019-02-14 08:40:10

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1818.26 1353.75
February 0.00 0.00 1841.94 1238.66
March 0.00 0.00 1801.80 1341.49
April 0.00 0.00 1712.77 1234.07
May 0.00 0.00 1582.49 1178.21
June 0.00 0.00 1461.85 1053.28
July 0.00 0.00 1373.56 1022.66
August 0.00 0.00 1342.12 999.24
September 0.00 0.00 1383.63 996.92
October 0.00 0.00 1477.40 1099.97
November 0.00 0.00 1601.60 1153.97
December 0.00 0.00 1729.34 1287.54
         
Annual Sum or Average 0.00 0.00 1592.45 13959.75
Minimum of Months 0.00 0.00 1342.12 996.92