Program Version:EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39
Tabular Output Report in Format: HTML
Building: MF+CZ5BWH+USA_ID_Boise.Air.Terminal.726810+gasfurnace+slab+IECC_2009
Environment: ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810
Simulation Timestamp: 2019-02-14 08:39:44
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Values gathered over 8760.00 hoursTotal Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
Total Site Energy | 1165233.91 | 37.33 | 53.92 |
Net Site Energy | 1165233.91 | 37.33 | 53.92 |
Total Source Energy | 2121579.31 | 67.98 | 98.18 |
Net Source Energy | 2121579.31 | 67.98 | 98.18 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [ft2] | |
Total Building Area | 31210.78 |
Net Conditioned Building Area | 21609.96 |
Unconditioned Building Area | 9600.82 |
Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | 0.00 | 275109.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 59778.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 10266.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 263405.37 | 163973.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 28796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 314022.12 | 0.00 | 0.00 | 0.00 | 419684.21 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 412129.50 | 753104.41 | 0.00 | 0.00 | 0.00 | 419684.21 |
Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Additional Fuel [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
Heating | General | 0.00 | 275109.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 59778.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 49882.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 8347.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 1919.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 3888.48 | 79268.53 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 67443.41 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 143183.64 | 17261.25 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 59304.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 28796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 314022.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 419684.21 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 2.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 4.10 | 27.26 | 0.00 | 0.00 | 0.00 | 19.42 |
Other | 12.19 | 7.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 19.07 | 34.85 | 0.00 | 0.00 | 0.00 | 19.42 |
Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Additional Fuel Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
Lighting | 1.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 2.84 | 18.88 | 0.00 | 0.00 | 0.00 | 13.45 |
Other | 8.44 | 5.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 13.20 | 24.13 | 0.00 | 0.00 | 0.00 | 13.45 |
Electricity [kBtu] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 412129.501 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 412129.501 | 100.00 |
Total On-Site and Utility Electric Sources | 412129.501 | 100.00 |
Total Electricity End Uses | 412129.501 | 100.00 |
Heat [kBtu] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [gal] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 419684.21 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 419684.21 | 100.00 |
Total Water End Uses | 419684.21 | 100.00 |
Degrees [deltaF] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 30.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 247.25 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
GeneralValue | |
Program Version and Build | EnergyPlus, Version 8.6.0-Unknown, YMD=2019.02.14 08:39 |
RunPeriod | ANNUAL |
Weather File | Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Latitude [deg] | 43.62 |
Longitude [deg] | -116.2 |
Elevation [ft] | 2299.98 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
Total | |
Gross Roof Area [ft2] | 8451.30 |
Skylight Area [ft2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
BREEZEWAY | 1798.13 | No | Yes | 30552.60 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
ATTIC | 7802.69 | No | Yes | 52795.67 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.7514 | 600.28 | 4.4634 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.7514 | 600.28 | 4.4634 |
Total | 31210.78 | 267087.66 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.5202 | 866.97 | 3.0904 | |||
Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.7514 | 600.28 | 4.4634 | |||
Unconditioned Total | 9600.82 | 83348.27 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
End UsesElectricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Time of Peak | 31-JUL-19:15 | 13-JAN-08:00 | - | - | - | 01-JAN-08:15 |
Heating | 0.00 | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 52.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 16.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 42.84 | 20.12 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 151.34 | 0.00 | 0.00 | 0.00 | 1.52 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 128.11 | 382.64 | 0.00 | 0.00 | 0.00 | 1.52 |
Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Propane [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
Heating | General | 0.00 | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 52.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | General | 16.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Exterior-Lights | 1.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Garage-Lights | 0.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Equipment | dishwasher | 3.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
refrigerator | 5.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_dryer | 0.51 | 9.86 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_range | 0.00 | 8.49 | 0.00 | 0.00 | 0.00 | 0.00 | |
television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
gas_mels | 23.39 | 1.77 | 0.00 | 0.00 | 0.00 | 0.00 | |
IECC_adj | 9.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
General | 13.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 151.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.52 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Values gathered over 8760.00 hoursSource Electricity [kBtu] | Source Natural Gas [kBtu] | Source Additional Fuel [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
Heating | 0.00 | 298218.26 | 0.00 | 0.00 | 0.00 |
Cooling | 189317.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 157977.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 32515.36 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 834204.80 | 177746.94 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91198.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 340399.98 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1305214.13 | 816365.18 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 13.80 | 0.00 | 0.00 | 0.00 |
Cooling | 8.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38.60 | 8.23 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.75 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 60.40 | 37.78 | 0.00 | 0.00 | 0.00 |
Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Additional Fuel [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
Heating | 0.00 | 13.80 | 0.00 | 0.00 | 0.00 |
Cooling | 8.76 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 7.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 38.60 | 8.23 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 15.75 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 60.40 | 37.78 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
SizingPeriod:DesignDayMaximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 2.66 | 0.00 | 2.66 | Wetbulb [F] | 452.78 | 120.00 |
BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 98.06 | 30.06 | 64.22 | Wetbulb [F] | 826.81 | 330.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.38 | 599.38 | 0.00 | 180.00 | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
Construction | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | ||
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | ||
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | ||
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.330 | 0.882 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | ||
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.330 | 0.882 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | ||
Total or Average | 2126.74 | 0.350 | 0.330 | 0.882 | ||||||||||||
North Total or Average | 531.68 | 0.350 | 0.330 | 0.882 | ||||||||||||
Non-North Total or Average | 1595.05 | 0.350 | 0.330 | 0.882 |
Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Report: Shading Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES | Interior Blind | WINDOW_W_BLINDS | OnIfScheduleAllows | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Interior LightingZone | Lighting Power Density [Btu/h-ft2] | Zone Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.5691 | 1200.55 | 683.23 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 614.75 |
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
Interior Lighting Total | 0.3757 | 43219.92 | 16236.84 | 14609.33 |
Zone | Daylighting Type | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 31.01 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 135.83 |
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 10.17 | Schedule | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 31.22 |
Exterior Lighting Total | 741.27 | 3006.93 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Central PlantType | Nominal Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | IPLV in SI Units [Btuh/Btuh] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 26641.52 | 21277.39 | 5364.13 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7907.36 | 6315.25 | 1592.10 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9809.54 | 7834.44 | 1975.10 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14589.72 | 11652.16 | 2937.56 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7355.40 | 5874.43 | 1480.97 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9560.49 | 7635.53 | 1924.95 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14749.69 | 11779.92 | 2969.77 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7756.12 | 6194.47 | 1561.65 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9411.10 | 7516.23 | 1894.88 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 14211.81 | 11350.34 | 2861.47 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7271.55 | 5807.47 | 1464.09 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 9208.32 | 7354.27 | 1854.05 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16639.83 | 13289.49 | 3350.34 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9663.00 | 7717.40 | 1945.59 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11180.77 | 8929.58 | 2251.19 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16568.95 | 13232.88 | 3336.07 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9591.10 | 7659.98 | 1931.12 | 0.80 | 3.97 | |||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11084.59 | 8852.77 | 2231.82 | 0.80 | 3.97 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 2.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.2 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.1 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.7 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.19 | 10.89 | 11.54 | 11.07 | |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.19 | 10.89 | 11.54 | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 5962.74 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 13069.94 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Fuel | 15776.19 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 15780.96 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 13070.56 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Fuel | 15773.46 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 13371.09 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 10654.51 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Fuel | 13375.09 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 13374.87 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 10654.30 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Fuel | 13372.10 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 17675.33 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 14951.93 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Fuel | 17680.24 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 17676.30 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 14950.81 | 0.80 | |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Fuel | 17677.16 | 0.80 |
Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | End Use | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 999.35 | 500.47 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 296.61 | 148.54 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 367.96 | 184.28 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 547.27 | 274.07 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 275.91 | 138.17 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.38 | 0.06 | 358.62 | 179.60 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 553.27 | 277.08 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 290.94 | 145.70 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 353.02 | 176.79 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 533.10 | 266.97 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 272.76 | 136.60 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.38 | 0.06 | 345.41 | 172.98 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 624.18 | 312.58 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 362.47 | 181.52 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 419.40 | 210.03 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 621.52 | 311.25 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 359.77 | 180.17 | 0.50 | 1.00 | General |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.38 | 0.06 | 415.79 | 208.23 | 0.50 | 1.00 | General |
Type | Control | Head [psi] | Water Flow [gal/min] | Electric Power [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 |
Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.83 | 0.55 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Zone Sensible CoolingCalculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 21593.44 | 21593.44 | 17.99 | 999.348 | 999.348 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00796 | 89.72 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6409.04 | 6409.04 | 5.34 | 296.612 | 296.612 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00790 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7951.06 | 7951.06 | 6.62 | 367.965 | 367.965 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 74.98 | 74.99 | 0.00778 | 98.06 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 11825.24 | 11825.24 | 9.85 | 547.274 | 547.274 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00793 | 89.72 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5961.66 | 5961.66 | 4.97 | 275.908 | 275.908 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00790 | 87.46 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7748.96 | 7748.96 | 6.45 | 358.623 | 358.623 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 74.98 | 74.98 | 0.00780 | 88.89 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11954.77 | 11954.77 | 9.96 | 553.274 | 553.274 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00800 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6286.40 | 6286.40 | 5.24 | 290.939 | 290.939 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00802 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7628.00 | 7628.00 | 6.35 | 353.019 | 353.019 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 14:45:00 | 74.98 | 74.98 | 0.00787 | 98.06 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11518.82 | 11518.82 | 9.59 | 533.098 | 533.098 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00800 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5893.66 | 5893.66 | 4.91 | 272.763 | 272.763 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00802 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7463.48 | 7463.48 | 6.22 | 345.413 | 345.413 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 74.98 | 74.98 | 0.00787 | 88.89 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 8984.27 | 8984.27 | 7.48 | 415.793 | 415.793 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:15:00 | 74.98 | 74.98 | 0.00790 | 89.72 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 9062.25 | 9062.25 | 7.55 | 419.401 | 419.401 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 74.98 | 74.98 | 0.00789 | 90.85 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 13486.86 | 13486.86 | 11.23 | 624.175 | 624.175 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00795 | 88.59 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 7773.72 | 7773.72 | 6.48 | 359.771 | 359.771 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 74.98 | 74.98 | 0.00794 | 86.34 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 7832.00 | 7832.00 | 6.52 | 362.468 | 362.468 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:45:00 | 74.98 | 74.98 | 0.00793 | 87.46 | 0.00627 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 13429.41 | 13429.41 | 11.19 | 621.517 | 621.517 | BOISE AIR TERMINAL UO ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 74.98 | 74.98 | 0.00794 | 88.59 | 0.00627 | 44.995 | 0.00 |
Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2898.99 | 2898.99 | 2.41 | 57.365 | 57.365 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.99 | 0.00355 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10111.68 | 10111.68 | 8.42 | 200.049 | 200.049 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.98 | 0.00566 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12858.00 | 12858.00 | 10.71 | 254.375 | 254.375 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00590 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12862.84 | 12862.84 | 10.71 | 254.471 | 254.471 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00590 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 10112.31 | 10112.31 | 8.42 | 200.061 | 200.061 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.98 | 0.00566 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12855.23 | 12855.23 | 10.71 | 254.320 | 254.320 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00590 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10417.06 | 10417.06 | 8.68 | 206.111 | 206.111 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00620 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7660.26 | 7660.26 | 6.38 | 151.570 | 151.570 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00595 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10421.12 | 10421.12 | 8.68 | 206.191 | 206.191 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00620 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10420.90 | 10420.90 | 8.68 | 206.187 | 206.187 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00620 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7660.04 | 7660.04 | 6.38 | 151.566 | 151.566 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00595 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 10418.08 | 10418.08 | 8.68 | 206.131 | 206.131 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:00:00 | 72.00 | 71.98 | 0.00620 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 14787.06 | 14787.06 | 12.32 | 292.539 | 292.539 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00610 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 14790.19 | 14790.19 | 12.32 | 292.601 | 292.601 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00610 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 14785.20 | 14785.20 | 12.32 | 292.502 | 292.502 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00610 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 12020.35 | 12020.35 | 10.01 | 237.811 | 237.811 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.98 | 0.00592 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 12021.49 | 12021.49 | 10.01 | 237.833 | 237.833 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.98 | 0.00592 | 2.66 | 0.00098 | 44.995 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 14786.19 | 14786.19 | 12.32 | 292.522 | 292.522 | BOISE AIR TERMINAL UO ANN HTG 99.6% CONDNS DB | 12/21 11:15:00 | 72.00 | 71.97 | 0.00610 | 2.66 | 0.00098 | 44.995 | 0.00 |
Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 | 999.35 | 57.36 | 57.36 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 | 296.61 | 200.05 | 200.05 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 | 367.96 | 254.38 | 254.38 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 | 547.27 | 254.47 | 254.47 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 | 275.91 | 200.06 | 200.06 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 | 358.62 | 254.32 | 254.32 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 | 553.27 | 206.11 | 206.11 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 | 290.94 | 151.57 | 151.57 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 | 353.02 | 206.19 | 206.19 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 | 533.10 | 206.19 | 206.19 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 | 272.76 | 151.57 | 151.57 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 | 345.41 | 206.13 | 206.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 624.18 | 624.18 | 292.50 | 292.50 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 362.47 | 362.47 | 237.83 | 237.83 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 419.40 | 419.40 | 292.60 | 292.60 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 621.52 | 621.52 | 292.52 | 292.52 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 359.77 | 359.77 | 237.81 | 237.81 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 415.79 | 415.79 | 292.54 | 292.54 |
Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Report: System Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1057.75 | 5796.00 | 22.75 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 510.25 | 5922.25 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1149.00 | 5726.75 | 29.25 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 912.00 | 6392.25 | 44.50 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 308.25 | 6507.25 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 887.00 | 6137.50 | 42.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1254.50 | 5696.25 | 23.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 704.75 | 5582.75 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1307.00 | 5493.00 | 24.50 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1037.00 | 6173.00 | 37.50 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 451.50 | 6151.50 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1018.25 | 5906.50 | 30.75 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1329.75 | 6043.50 | 212.50 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1433.50 | 5822.00 | 171.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1388.00 | 6101.00 | 162.75 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 728.75 | 6359.00 | 36.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 847.00 | 6063.75 | 24.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1345.50 | 6341.75 | 237.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 |
Facility | 1991.75 | 6848.00 | 247.25 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 8.00 | 0.00 | 8.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 16.25 | 0.00 | 16.25 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 13.50 | 0.00 | 13.50 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 17.00 | 0.00 | 17.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 20.00 | 0.00 | 20.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 3.25 | 0.00 | 3.25 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 14.00 | 0.00 | 14.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 12.25 | 0.00 | 12.25 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 12.25 | 0.00 | 12.25 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 14.75 | 0.00 | 14.75 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 13.00 | 0.00 | 13.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 3.25 | 0.00 | 3.25 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 16.75 | 0.00 | 16.75 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 17.25 | 0.00 | 17.25 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 15.00 | 0.00 | 15.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 16.00 | 0.00 | 16.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 15.25 | 0.00 | 15.25 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 15.00 | 0.00 | 15.00 |
BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 30.00 | 0.00 | 30.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.274 | 0.000 | 0.277 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.236 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.268 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.267 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.236 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.268 | 0.000 | 0.276 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.118 | 0.000 | 0.276 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.086 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.118 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.117 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.085 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.118 | 0.000 | 0.276 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.268 | 0.000 | 0.276 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.268 | 0.000 | 0.276 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.268 | 0.000 | 0.276 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.236 | 0.000 | 0.276 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.236 | 0.000 | 0.276 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.268 | 0.000 | 0.276 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.004 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Surfaces by ClassTotal | Outdoors | |
Wall | 74 | 50 |
Floor | 28 | 3 |
Roof | 21 | 2 |
Internal Mass | 0 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 30 | 30 |
Door | 18 | 18 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 18 |
Conditioned Zones | 18 |
Unconditioned Zones | 2 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 1866 |
Defaulted Fields | 490 |
Fields with Defaults | 4870 |
Autosized Fields | 288 |
Autosizable Fields | 396 |
Autocalculated Fields | 89 |
Autocalculatable Fields | 268 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Annual and Peak Values - ElectricityElectricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
Electricity:Building | 91754.37 | 7056.43 | 02-JAN-03:15 | 17558.18 | 01-JAN-20:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
General:InteriorLights:Electricity | 14609.33 | 327.16 | 01-JAN-00:15 | 4758.75 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5097.47 | 392.02 | 02-JAN-03:15 | 975.45 | 01-JAN-20:15 |
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 811.63 | 18.18 | 01-JAN-00:15 | 264.37 | 01-JAN-19:15 |
InteriorEquipment:Electricity | 77145.04 | 6525.11 | 02-JAN-04:15 | 12799.44 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:15 | 985.58 | 01-JAN-19:15 |
refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:15 | 1639.04 | 01-JAN-18:15 |
clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:15 | 427.18 | 01-JAN-09:15 |
gas_dryer:InteriorEquipment:Electricity | 1138.84 | 5.81 | 02-JAN-03:15 | 291.20 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
gas_mels:InteriorEquipment:Electricity | 41935.01 | 3663.85 | 01-JAN-09:15 | 7086.44 | 01-JAN-20:15 |
IECC_adj:InteriorEquipment:Electricity | 17368.96 | 1517.52 | 01-JAN-09:15 | 2935.11 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4285.84 | 362.51 | 02-JAN-04:15 | 711.08 | 01-JAN-20:15 |
Fans:Electricity | 8433.84 | 136.61 | 15-MAY-24:00 | 4005.04 | 21-JUL-17:30 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityPurchased:Facility | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
ElectricityPurchased:Plant | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
Cogeneration:ElectricityPurchased | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
ElectricityNet:Facility | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
ElectricityNet:Plant | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
Cogeneration:ElectricityNet | 120702.73 | 8166.88 | 07-APR-04:00 | 37519.87 | 31-JUL-19:15 |
ExteriorLights:Electricity | 3006.93 | 23.60 | 01-JAN-09:15 | 741.27 | 01-JAN-19:15 |
Exterior-Lights:ExteriorLights:Electricity | 2444.89 | 0.00 | 01-JAN-06:15 | 558.19 | 01-JAN-00:15 |
Garage-Lights:ExteriorLights:Electricity | 562.04 | 12.59 | 01-JAN-00:15 | 183.08 | 01-JAN-19:15 |
Electricity:HVAC | 25941.43 | 512.14 | 03-JUN-01:00 | 19793.67 | 31-JUL-18:00 |
General:Fans:Electricity | 8433.84 | 136.61 | 15-MAY-24:00 | 4005.04 | 21-JUL-17:30 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:Electricity | 17507.59 | 0.00 | 01-JAN-01:00 | 15788.63 | 31-JUL-18:00 |
Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Gas Annual Value [therm] | Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 7531.04 | 2644.47 | 07-APR-03:15 | 382365.29 | 13-JAN-09:00 |
Gas:Building | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas | 1639.73 | 2644.47 | 02-JAN-03:15 | 43735.22 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
gas_dryer:InteriorEquipment:Gas | 792.69 | 403.80 | 02-JAN-03:15 | 20254.25 | 01-JAN-11:15 |
gas_range:InteriorEquipment:Gas | 674.43 | 651.88 | 01-JAN-02:15 | 27685.38 | 01-JAN-17:15 |
gas_mels:InteriorEquipment:Gas | 172.61 | 1507.04 | 01-JAN-09:15 | 2914.85 | 01-JAN-20:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
InteriorEquipment:Gas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 91.10 | 146.92 | 02-JAN-03:15 | 2429.73 | 01-JAN-17:15 |
Gas:Plant | 3140.22 | 0.00 | 01-JAN-00:15 | 151819.55 | 18-FEB-08:45 |
WaterSystems:Gas | 3140.22 | 0.00 | 01-JAN-00:15 | 151819.55 | 18-FEB-08:45 |
Water Heater:WaterSystems:Gas | 3140.22 | 0.00 | 01-JAN-00:15 | 151819.55 | 18-FEB-08:45 |
Gas:HVAC | 2751.09 | 0.00 | 03-MAR-16:45 | 223243.57 | 13-JAN-08:15 |
Heating:Gas | 2751.09 | 0.00 | 03-MAR-16:45 | 223243.57 | 13-JAN-08:15 |
Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
Water:Plant | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
WaterSystems:Water | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
MainsWater:Facility | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
MainsWater:Plant | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
WaterSystems:MainsWater | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Domestic Hot Water:WaterSystems:Water | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
Domestic Hot Water:WaterSystems:MainsWater | 56111.84 | 0.01 | 10-JAN-02:45 | 0.20 | 01-JAN-08:15 |
Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:15 | 0.000 | 01-JAN-00:15 |
Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
PlantLoopHeatingDemand:Plant | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
WaterSystems:PlantLoopHeatingDemand | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Facility | 1115632.44 | 15456.55 | 18-JUN-03:00 | 409444.13 | 13-JAN-08:15 |
EnergyTransfer:Building | 465677.65 | 5944.41 | 15-MAY-24:00 | 187575.49 | 13-JAN-08:15 |
EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer | 230647.38 | 0.00 | 03-MAR-16:45 | 187575.49 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer | 235030.28 | 0.00 | 01-JAN-01:00 | 177945.25 | 29-JUL-18:30 |
Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 69088.61 | 0.00 | 01-JAN-01:00 | 22216.42 | 12-JUL-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 29.67 | 0.00 | 01-JAN-00:15 | 2524.27 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 69058.94 | 0.00 | 01-JAN-01:00 | 22216.42 | 12-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 17770.50 | 0.00 | 06-JAN-14:15 | 9387.19 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 9767.83 | 0.00 | 06-JAN-14:15 | 9387.19 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8002.67 | 0.00 | 01-JAN-00:15 | 6778.50 | 04-AUG-18:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 25185.49 | 0.00 | 23-JAN-14:00 | 12018.96 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14079.14 | 0.00 | 23-JAN-14:00 | 12018.96 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 11106.35 | 0.00 | 01-JAN-00:15 | 8274.43 | 22-JUL-09:30 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 26385.73 | 0.00 | 05-FEB-16:00 | 12483.18 | 23-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 16883.37 | 0.00 | 05-FEB-16:00 | 12105.27 | 13-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 9502.36 | 0.00 | 01-JAN-00:15 | 12483.18 | 23-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 18697.46 | 0.00 | 10-FEB-17:00 | 9498.26 | 13-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12632.92 | 0.00 | 10-FEB-17:00 | 9498.26 | 13-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6064.54 | 0.00 | 01-JAN-00:15 | 6358.24 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 25561.08 | 0.00 | 10-FEB-17:15 | 12127.44 | 13-JAN-05:00 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 16429.88 | 0.00 | 10-FEB-17:15 | 12127.44 | 13-JAN-05:00 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 9131.19 | 0.00 | 01-JAN-00:15 | 8300.70 | 22-JUL-09:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 21795.42 | 0.00 | 01-JAN-15:45 | 12563.20 | 14-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 9425.53 | 0.00 | 01-JAN-15:45 | 9627.60 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12369.89 | 0.00 | 01-JAN-00:15 | 12563.20 | 14-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 15022.24 | 0.00 | 06-JAN-12:45 | 7027.97 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6216.55 | 0.00 | 06-JAN-12:45 | 7027.97 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8805.69 | 0.00 | 01-JAN-00:15 | 6727.78 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21942.41 | 0.00 | 06-JAN-13:45 | 9672.87 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 10031.81 | 0.00 | 06-JAN-13:45 | 9672.87 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11910.60 | 0.00 | 01-JAN-00:15 | 8015.06 | 22-JUL-09:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 22516.57 | 0.00 | 03-FEB-16:30 | 12136.29 | 14-JUL-18:45 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12441.78 | 0.00 | 03-FEB-16:30 | 9709.05 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10074.79 | 0.00 | 01-JAN-00:15 | 12136.29 | 14-JUL-18:45 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 15045.35 | 0.00 | 01-FEB-19:00 | 7093.55 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8290.96 | 0.00 | 01-FEB-19:00 | 7093.55 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6754.39 | 0.00 | 01-JAN-00:15 | 6310.17 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21907.53 | 0.00 | 10-FEB-17:00 | 9714.57 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12069.72 | 0.00 | 10-FEB-17:00 | 9714.57 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9837.81 | 0.00 | 01-JAN-00:15 | 8057.13 | 22-JUL-09:45 |
EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:15 | 0.00 | 01-JAN-00:15 |
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 29924.17 | 0.00 | 10-FEB-18:15 | 13819.85 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 19315.84 | 0.00 | 10-FEB-18:15 | 13819.85 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 10608.33 | 0.00 | 01-JAN-00:15 | 9455.02 | 21-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 28891.13 | 0.00 | 04-FEB-14:15 | 13787.66 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 17150.29 | 0.00 | 04-FEB-14:15 | 13787.66 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11740.84 | 0.00 | 01-JAN-00:15 | 9537.00 | 21-JUL-20:30 |
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 29828.45 | 0.00 | 23-JAN-15:15 | 14128.01 | 20-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 17541.04 | 0.00 | 23-JAN-15:15 | 13766.20 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 12287.41 | 0.00 | 01-JAN-00:15 | 14128.01 | 20-JUL-18:30 |
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 23187.76 | 0.00 | 10-FEB-17:15 | 11195.03 | 13-JAN-08:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 15387.57 | 0.00 | 10-FEB-17:15 | 11195.03 | 13-JAN-08:30 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7800.19 | 0.00 | 01-JAN-00:15 | 8298.93 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 21959.25 | 0.00 | 23-JAN-15:15 | 11137.96 | 13-JAN-08:15 |
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 13074.90 | 0.00 | 23-JAN-15:15 | 11137.96 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8884.34 | 0.00 | 01-JAN-00:15 | 8361.26 | 21-JUL-20:45 |
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 30968.52 | 0.00 | 05-FEB-16:15 | 14087.20 | 14-JUL-18:30 |
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 19878.59 | 0.00 | 05-FEB-16:15 | 13815.37 | 13-JAN-08:15 |
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 11089.93 | 0.00 | 01-JAN-00:15 | 14087.20 | 14-JUL-18:30 |
EnergyTransfer:Plant | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
WaterSystems:EnergyTransfer | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
Domestic Hot Water:WaterSystems:EnergyTransfer | 173002.31 | 1435.21 | 11-AUG-02:30 | 46098.04 | 11-FEB-09:00 |
EnergyTransfer:HVAC | 476952.47 | 6990.80 | 15-MAY-24:00 | 194850.47 | 12-JUL-19:45 |
HeatingCoils:EnergyTransfer | 220087.28 | 0.00 | 03-MAR-16:45 | 178594.86 | 13-JAN-08:15 |
CoolingCoils:EnergyTransfer | 256865.20 | 0.00 | 01-JAN-01:00 | 194850.47 | 12-JUL-19:45 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 29.668 | -5751.06 | 0.000 | 0.000 | 2875.887 | 2771.241 | 14528.036 | 9747.326 | 0.000 | 775.247 | 65750.053 | 0.000 | -7050.33 | 0.000 | -20368.29 | 0.000 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 9767.720 | -666.44 | 0.000 | 0.000 | 3039.710 | 2771.241 | 14528.036 | 4344.260 | 0.000 | 730.375 | 0.000 | 0.000 | -2705.60 | 0.000 | -17640.24 | -6832.86 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 14078.996 | -924.91 | 0.000 | 0.000 | 3052.055 | 2771.241 | 14528.036 | 9917.441 | 0.000 | 775.067 | 0.000 | 0.000 | -6429.20 | 0.000 | -18757.96 | -8829.37 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 16883.219 | -791.33 | 0.000 | 0.000 | 3062.192 | 2771.241 | 14528.036 | 6737.645 | 0.000 | 774.206 | 0.000 | 0.000 | -6913.03 | 0.000 | -18575.97 | -9765.21 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 12632.806 | -505.04 | 0.000 | 0.000 | 3055.069 | 2771.241 | 14528.036 | 1045.746 | 0.000 | 730.303 | 0.000 | 0.000 | -2900.87 | 0.000 | -17467.72 | -8330.07 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 16429.736 | -760.42 | 0.000 | 0.000 | 3062.190 | 2771.241 | 14528.036 | 6728.682 | 0.000 | 775.696 | 0.000 | 0.000 | -6630.79 | 0.000 | -18629.95 | -9903.68 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 9425.417 | -1030.13 | 0.000 | 0.000 | 3031.370 | 2771.241 | 14528.036 | 9846.894 | 0.000 | 565.442 | 0.000 | 0.000 | -6819.92 | 0.000 | -13430.53 | -7548.07 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 6216.475 | -733.32 | 0.000 | 0.000 | 3016.904 | 2771.241 | 14528.036 | 4337.630 | 0.000 | 521.686 | 0.000 | 0.000 | -2748.25 | 0.000 | -12332.98 | -7505.06 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 10031.699 | -991.88 | 0.000 | 0.000 | 3034.794 | 2771.241 | 14528.036 | 9892.827 | 0.000 | 565.619 | 0.000 | 0.000 | -6532.24 | 0.000 | -13446.42 | -8934.99 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 12441.663 | -839.00 | 0.000 | 0.000 | 3046.434 | 2771.241 | 14528.036 | 6729.379 | 0.000 | 565.417 | 0.000 | 0.000 | -7017.40 | 0.000 | -13303.55 | -9686.43 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 8290.885 | -562.49 | 0.000 | 0.000 | 3035.890 | 2771.241 | 14528.036 | 1045.255 | 0.000 | 521.671 | 0.000 | 0.000 | -2943.59 | 0.000 | -12196.79 | -8298.21 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 12069.609 | -819.27 | 0.000 | 0.000 | 3047.205 | 2771.241 | 14528.036 | 6711.224 | 0.000 | 566.080 | 0.000 | 0.000 | -6727.21 | 0.000 | -13342.29 | -9786.11 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 19315.679 | -883.43 | 0.000 | 0.000 | 3060.671 | 2771.241 | 14528.036 | 6736.228 | 0.000 | 769.272 | 0.000 | 0.000 | -6676.83 | 0.000 | -18666.18 | -11229.82 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17150.125 | -977.75 | 0.000 | 0.000 | 3053.666 | 2771.241 | 14528.036 | 9947.382 | 0.000 | 769.176 | 0.000 | 0.000 | -6463.73 | 0.000 | -18751.48 | -11263.61 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 17540.872 | -1023.27 | 0.000 | 0.000 | 3054.291 | 2771.241 | 14528.036 | 9910.009 | 0.000 | 769.259 | 0.000 | 0.000 | -6703.45 | 0.000 | -18701.70 | -10881.17 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 15387.439 | -649.58 | 0.000 | 0.000 | 3054.277 | 2771.241 | 14528.036 | 1051.079 | 0.000 | 725.752 | 0.000 | 0.000 | -2911.57 | 0.000 | -17508.14 | -9297.92 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 13074.780 | -739.87 | 0.000 | 0.000 | 3045.174 | 2771.241 | 14528.036 | 4360.178 | 0.000 | 725.653 | 0.000 | 0.000 | -2708.00 | 0.000 | -17604.74 | -9307.99 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 19878.416 | -923.54 | 0.000 | 0.000 | 3060.777 | 2771.241 | 14528.036 | 6737.064 | 0.000 | 769.392 | 0.000 | 0.000 | -6949.51 | 0.000 | -18621.43 | -11084.07 |
BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4624.604 | 42683.512 | 0.000 | 0.000 | 0.000 | -47308.12 | -0.52 |
Total Facility | 0.000 | 0.000 | 230645.204 | -19572.74 | 0.000 | 0.000 | 54688.554 | 49882.340 | 261504.651 | 115826.249 | 0.000 | 17019.917 | 108433.565 | 0.000 | -97831.51 | 0.000 | -346654.48 | -158485.15 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12-JUL-17:49 | 0.00 | 0.00 | 0.00 | -1.9 | 0.00 | 0.00 | 259.06 | 604.65 | 2756.77 | 8827.07 | 0.00 | 1926.18 | 7880.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 21-JUL-20:33 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 423.28 | 902.05 | 2167.29 | 84.02 | 0.00 | 838.00 | 2427.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-JUL-09:17 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.16 | 116.28 | 1603.33 | 7285.32 | 0.00 | 713.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1558.9 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 23-JUL-18:20 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.75 | 813.96 | 2698.15 | 8325.91 | 0.00 | 1469.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1250.5 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21-JUL-20:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 421.44 | 902.05 | 2167.29 | 86.25 | 0.00 | 829.79 | 1961.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22-JUL-09:17 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.16 | 116.28 | 1603.33 | 7148.56 | 0.00 | 713.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1395.9 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 14-JUL-18:33 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.42 | 813.96 | 2666.18 | 7038.84 | 0.00 | 1042.21 | 599.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 21-JUL-20:48 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 425.89 | 902.05 | 2167.29 | 43.04 | 0.00 | 510.74 | 2727.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 21-JUL-20:17 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.54 | 902.05 | 2167.29 | 327.93 | 0.00 | 838.29 | 3384.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 14-JUL-18:48 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 426.56 | 813.96 | 2666.18 | 6323.61 | 0.00 | 1015.79 | 913.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 21-JUL-20:50 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.82 | 902.05 | 2167.29 | 43.85 | 0.00 | 510.22 | 2339.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 22-JUL-09:32 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.16 | 116.28 | 1603.33 | 6690.56 | 0.00 | 574.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1041.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 21-JUL-20:33 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.85 | 902.05 | 2167.29 | 172.06 | 0.00 | 884.78 | 5028.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 21-JUL-20:33 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.94 | 902.05 | 2167.29 | 174.22 | 0.00 | 885.31 | 5108.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 20-JUL-18:19 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 423.69 | 813.96 | 2666.18 | 7803.61 | 0.00 | 1553.26 | 892.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 21-JUL-20:53 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 422.79 | 902.05 | 2167.29 | 25.18 | 0.00 | 664.61 | 4215.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 21-JUL-20:53 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 422.72 | 902.05 | 2167.29 | 27.35 | 0.00 | 664.40 | 4276.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 20-JUL-18:19 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 423.65 | 813.96 | 2666.18 | 7982.45 | 0.00 | 1552.87 | 656.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-JUL-18:19 | 0.00 | 0.00 | 0.00 | -14.9 | 0.00 | 0.00 | 7518.33 | 14651.21 | 48566.62 | 62674.47 | 0.00 | 29714.81 | 27527.06 | 0.00 | 0.00 | 0.00 | -12305.3 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13-JAN-08:30 | 0.00 | 0.00 | 2524.16 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 5867.04 | 0.00 | -2485.4 | 0.00 | -7914.7 | 0.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 9386.84 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1195.7 | 0.00 | -7382.0 | -2818.1 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 12018.54 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2935.3 | 0.00 | -7914.7 | -3177.5 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13-JAN-05:00 | 0.00 | 0.00 | 12104.97 | 0.00 | 0.00 | 0.00 | 526.31 | 186.05 | 1036.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2945.3 | 0.00 | -8062.2 | -2846.6 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 13-JAN-05:00 | 0.00 | 0.00 | 9498.03 | 0.00 | 0.00 | 0.00 | 526.31 | 186.05 | 1036.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1192.0 | 0.00 | -7518.1 | -2537.1 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13-JAN-05:00 | 0.00 | 0.00 | 12127.15 | 0.00 | 0.00 | 0.00 | 526.31 | 186.05 | 1036.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2936.3 | 0.00 | -8062.2 | -2877.8 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 9627.25 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2964.0 | 0.00 | -5410.9 | -3261.3 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 7027.69 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1204.4 | 0.00 | -4877.7 | -2954.5 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 9672.50 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2962.6 | 0.00 | -5410.9 | -3308.0 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 9708.70 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2959.7 | 0.00 | -5410.9 | -3347.1 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 13-JAN-08:30 | 0.00 | 0.00 | 7093.17 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1141.4 | 0.00 | -4877.8 | -3083.0 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 9714.21 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2959.7 | 0.00 | -5410.9 | -3352.7 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 13819.37 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2944.8 | 0.00 | -7924.6 | -4958.9 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 13787.18 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2945.2 | 0.00 | -7924.6 | -4926.4 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 13765.74 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2945.6 | 0.00 | -7924.6 | -4904.5 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 13-JAN-08:30 | 0.00 | 0.00 | 11194.51 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1134.0 | 0.00 | -7391.1 | -4678.4 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 11137.56 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1194.2 | 0.00 | -7391.1 | -4561.2 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 13-JAN-08:15 | 0.00 | 0.00 | 13814.91 | 0.00 | 0.00 | 0.00 | 215.05 | 170.54 | 1623.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2944.9 | 0.00 | -7924.6 | -4954.4 |
BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 13-JAN-08:15 | 0.00 | 0.00 | 187568.79 | 0.00 | 0.00 | 0.00 | 3870.98 | 3069.78 | 29220.83 | 0.00 | 0.00 | 1091.84 | 0.00 | 0.00 | -42536.0 | 0.00 | -124302.5 | -57983.7 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 999.348 | 2.00 | 2.00 | 1.00 | 44.9950 | 999.348 | 0.045 | 1.000 | 44.9950 | 0.05 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 296.612 | 2.00 | 2.00 | 1.00 | 44.9950 | 296.612 | 0.152 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 367.965 | 2.00 | 2.00 | 1.00 | 44.9950 | 367.965 | 0.122 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 547.274 | 2.00 | 2.00 | 1.00 | 44.9950 | 547.274 | 0.082 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 275.908 | 2.00 | 2.00 | 1.00 | 44.9950 | 275.908 | 0.163 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 358.623 | 2.00 | 2.00 | 1.00 | 44.9950 | 358.623 | 0.125 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 553.274 | 2.00 | 2.00 | 1.00 | 44.9950 | 553.274 | 0.081 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 290.939 | 2.00 | 2.00 | 1.00 | 44.9950 | 290.939 | 0.155 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.019 | 2.00 | 2.00 | 1.00 | 44.9950 | 353.019 | 0.127 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 533.098 | 2.00 | 2.00 | 1.00 | 44.9950 | 533.098 | 0.084 | 1.000 | 44.9950 | 0.08 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 272.763 | 2.00 | 2.00 | 1.00 | 44.9950 | 272.763 | 0.165 | 1.000 | 44.9950 | 0.16 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 345.413 | 2.00 | 2.00 | 1.00 | 44.9950 | 345.413 | 0.130 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 624.175 | 2.00 | 2.00 | 1.00 | 44.9950 | 624.175 | 0.072 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 362.468 | 2.00 | 2.00 | 1.00 | 44.9950 | 362.468 | 0.124 | 1.000 | 44.9950 | 0.12 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 419.401 | 2.00 | 2.00 | 1.00 | 44.9950 | 419.401 | 0.107 | 1.000 | 44.9950 | 0.11 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 621.517 | 2.00 | 2.00 | 1.00 | 44.9950 | 621.517 | 0.072 | 1.000 | 44.9950 | 0.07 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 359.771 | 2.00 | 2.00 | 1.00 | 44.9950 | 359.771 | 0.125 | 1.000 | 44.9950 | 0.13 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 415.793 | 2.00 | 2.00 | 1.00 | 44.9950 | 415.793 | 0.108 | 1.000 | 44.9950 | 0.11 |
Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 57.365 | 2.00 | 2.00 | 1.00 | 44.9950 | 57.365 | 1.000 | 1.000 | 44.9950 | 0.78 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.049 | 2.00 | 2.00 | 1.00 | 44.9950 | 200.049 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 254.375 | 2.00 | 2.00 | 1.00 | 44.9950 | 254.375 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 254.471 | 2.00 | 2.00 | 1.00 | 44.9950 | 254.471 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 200.061 | 2.00 | 2.00 | 1.00 | 44.9950 | 200.061 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 254.320 | 2.00 | 2.00 | 1.00 | 44.9950 | 254.320 | 1.000 | 1.000 | 44.9950 | 0.18 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 206.111 | 2.00 | 2.00 | 1.00 | 44.9950 | 206.111 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 151.570 | 2.00 | 2.00 | 1.00 | 44.9950 | 151.570 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 206.191 | 2.00 | 2.00 | 1.00 | 44.9950 | 206.191 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 206.187 | 2.00 | 2.00 | 1.00 | 44.9950 | 206.187 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 151.566 | 2.00 | 2.00 | 1.00 | 44.9950 | 151.566 | 1.000 | 1.000 | 44.9950 | 0.30 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 206.131 | 2.00 | 2.00 | 1.00 | 44.9950 | 206.131 | 1.000 | 1.000 | 44.9950 | 0.22 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 292.502 | 2.00 | 2.00 | 1.00 | 44.9950 | 292.502 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 237.833 | 2.00 | 2.00 | 1.00 | 44.9950 | 237.833 | 1.000 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 292.601 | 2.00 | 2.00 | 1.00 | 44.9950 | 292.601 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 292.522 | 2.00 | 2.00 | 1.00 | 44.9950 | 292.522 | 1.000 | 1.000 | 44.9950 | 0.15 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 237.811 | 2.00 | 2.00 | 1.00 | 44.9950 | 237.811 | 1.000 | 1.000 | 44.9950 | 0.19 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 292.539 | 2.00 | 2.00 | 1.00 | 44.9950 | 292.539 | 1.000 | 1.000 | 44.9950 | 0.15 |
AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 1.000 | 44.9950 | 1.000 | 44.9950 |
People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.55 | 44.9950 | 44.9950 | 44.9950 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 999.348 | 999.3480 | 199.8696 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 296.612 | 296.6123 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 367.965 | 367.9648 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 547.274 | 547.2739 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 275.908 | 275.9079 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 358.623 | 358.6227 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 553.274 | 553.2744 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 290.939 | 290.9394 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.019 | 353.0191 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 533.098 | 533.0981 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 272.763 | 272.7627 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 345.413 | 345.4125 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 415.793 | 415.7932 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 419.401 | 419.4011 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 624.175 | 624.1753 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 359.771 | 359.7710 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 362.468 | 362.4679 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 621.517 | 621.5166 | 180.0453 | 44.9950 | 0.000 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 | 999.348 | 999.35 | 199.8696 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 | 296.612 | 296.61 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 | 367.965 | 367.96 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 | 547.274 | 547.27 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 | 275.908 | 275.91 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 | 358.623 | 358.62 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 | 553.274 | 553.27 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 | 290.939 | 290.94 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 | 353.019 | 353.02 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 | 533.098 | 533.10 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 | 272.763 | 272.76 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 | 345.413 | 345.41 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 624.18 | 624.175 | 624.18 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 362.47 | 362.468 | 362.47 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 419.40 | 419.401 | 419.40 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 621.52 | 621.517 | 621.52 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 359.77 | 359.771 | 359.77 | 180.0453 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 415.79 | 415.793 | 415.79 | 180.0453 | 44.9950 | 1.000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 57.365 | 57.365 | 57.365 | 44.9950 | 0.784 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.049 | 200.049 | 200.049 | 44.9950 | 0.225 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 254.375 | 254.375 | 254.375 | 44.9950 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 254.471 | 254.471 | 254.471 | 44.9950 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 200.061 | 200.061 | 200.061 | 44.9950 | 0.225 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 254.320 | 254.320 | 254.320 | 44.9950 | 0.177 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 206.111 | 206.111 | 206.111 | 44.9950 | 0.218 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 151.570 | 151.570 | 151.570 | 44.9950 | 0.297 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 206.191 | 206.191 | 206.191 | 44.9950 | 0.218 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 206.187 | 206.187 | 206.187 | 44.9950 | 0.218 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 151.566 | 151.566 | 151.566 | 44.9950 | 0.297 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 206.131 | 206.131 | 206.131 | 44.9950 | 0.218 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 292.539 | 292.539 | 292.539 | 44.9950 | 0.154 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 292.601 | 292.601 | 292.601 | 44.9950 | 0.154 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 292.502 | 292.502 | 292.502 | 44.9950 | 0.154 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 237.811 | 237.811 | 237.811 | 44.9950 | 0.189 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 237.833 | 237.833 | 237.833 | 44.9950 | 0.189 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | |
LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 292.522 | 292.522 | 292.522 | 44.9950 | 0.154 | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 |
Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 57.36 | 57.365 | 57.36 | 57.36 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 200.05 | 200.049 | 200.05 | 200.05 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 254.38 | 254.375 | 254.38 | 254.38 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 254.47 | 254.471 | 254.47 | 254.47 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 200.06 | 200.061 | 200.06 | 200.06 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 254.32 | 254.320 | 254.32 | 254.32 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 206.11 | 206.111 | 206.11 | 206.11 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 151.57 | 151.570 | 151.57 | 151.57 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 206.19 | 206.191 | 206.19 | 206.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 206.19 | 206.187 | 206.19 | 206.19 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 151.57 | 151.566 | 151.57 | 151.57 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 206.13 | 206.131 | 206.13 | 206.13 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 292.50 | 292.502 | 292.50 | 292.50 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 237.83 | 237.833 | 237.83 | 237.83 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 292.60 | 292.601 | 292.60 | 292.60 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 292.52 | 292.522 | 292.52 | 292.52 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 237.81 | 237.811 | 237.81 | 237.81 | 44.9950 | 1.000 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 292.54 | 292.539 | 292.54 | 292.54 | 44.9950 | 1.000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Sec1.1A-General InformationData | |
Weather File | ANNUAL ** Boise Air Terminal Uo ID USA TMY3 WMO#=726810 |
Total gross floor area [ft2] | 31210.78 |
Principal Heating Source | Natural Gas |
Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
BREEZEWAY | 1798.13 | 0.00 | 1798.13 | 0.00 |
ATTIC | 7802.69 | 0.00 | 7802.69 | 0.00 |
Totals | 31210.78 | 21609.96 | 9600.82 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 30.00 |
Number of hours not met | 30.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [kWh] | Electric Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Additional Energy Use [kBtu] | Additional Demand [Btu/h] | |
Interior Lighting | 14609.33 | 4758.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 3006.93 | 741.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Heating | 0.00 | 0.00 | 2751.09 | 211020.03 | 0.00 | 0.00 |
Space Cooling | 17507.59 | 15468.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Interior | 8433.84 | 4005.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans-Parking Garage | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Service Water Heating | 0.00 | 0.00 | 3140.22 | 151234.97 | 0.00 | 0.00 |
Receptacle Equipment | 77145.04 | 12546.50 | 1639.73 | 20110.29 | 0.00 | 0.00 |
Interior Lighting-Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooking | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Industrial Process | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Elevators and Escalators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Line | 120702.73 | 7531.04 | 0.00 |
Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
Electricity | 263405.37 | 412129.50 |
Natural Gas | 163973.19 | 753104.41 |
Additional | 0.00 | 0.00 |
Total | 427378.56 | 1165233.91 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [kWh/ft2] | |
Interior Lighting | 0.47 |
Space Heating | 0.00 |
Space Cooling | 0.56 |
Fans-Interior | 0.27 |
Service Water Heating | 0.00 |
Receptacle Equipment | 2.47 |
Miscellaneous | 0.10 |
Subtotal | 3.87 |
Natural Gas [kWh/ft2] | |
Space Heating | 2.58 |
Service Water Heating | 2.95 |
Miscellaneous | 1.54 |
Subtotal | 7.07 |
Additional [kBtu/ft2] | |
Miscellaneous | 0.00 |
Subtotal | 0.00 |
Percent [%] | |
Interior Lighting | 4.28 |
Space Heating | 23.61 |
Space Cooling | 5.13 |
Fans-Interior | 2.47 |
Service Water Heating | 26.95 |
Receptacle Equipment | 36.68 |
Miscellaneous | 0.88 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [ft3/min] | |
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 |
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 |
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 |
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 |
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 |
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 |
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 |
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 |
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 |
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 |
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 |
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 |
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 415.79 |
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 419.40 |
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 624.18 |
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 359.77 |
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 362.47 |
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 621.52 |
Design Supply Air Flow Rate [ft3/min] | |
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 |
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 |
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 |
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 |
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 |
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 |
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 |
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 |
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 |
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 |
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 |
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 |
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 624.18 |
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 362.47 |
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 419.40 |
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 621.52 |
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 359.77 |
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 415.79 |
Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 | 2.22 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 | 0.658946 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 | 0.817461 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 | 1.22 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 | 0.612950 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 | 0.796707 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 | 1.23 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 | 0.646344 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 | 0.784258 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 | 1.18 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 | 0.605963 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 | 0.767360 | 0.798655 |
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 624.18 | 1.39 | 0.798655 |
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 362.47 | 0.805250 | 0.798655 |
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 419.40 | 0.931731 | 0.798655 |
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 621.52 | 1.38 | 0.798655 |
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 359.77 | 0.799258 | 0.798655 |
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 415.79 | 0.923716 | 0.798655 |
Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 | 999.35 | 999.35 | 5962.74 | 2.22 | 1.00 |
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 | 296.61 | 296.61 | 13069.94 | 0.658946 | 1.00 |
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 | 367.96 | 367.96 | 15776.19 | 0.817461 | 1.00 |
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 | 547.27 | 547.27 | 15780.96 | 1.22 | 1.00 |
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 | 275.91 | 275.91 | 13070.56 | 0.612950 | 1.00 |
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 | 358.62 | 358.62 | 15773.46 | 0.796707 | 1.00 |
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 | 553.27 | 553.27 | 13371.09 | 1.23 | 1.00 |
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 | 290.94 | 290.94 | 10654.51 | 0.646344 | 1.00 |
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 | 353.02 | 353.02 | 13375.09 | 0.784258 | 1.00 |
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 | 533.10 | 533.10 | 13374.87 | 1.18 | 1.00 |
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 | 272.76 | 272.76 | 10654.30 | 0.605963 | 1.00 |
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 | 345.41 | 345.41 | 13372.10 | 0.767360 | 1.00 |
ACANDF_UNIT1_FRONTROW_TOPFLOOR | 624.18 | 624.18 | 624.18 | 17675.33 | 1.39 | 1.00 |
ACANDF_UNIT2_FRONTROW_TOPFLOOR | 362.47 | 362.47 | 362.47 | 14951.93 | 0.805250 | 1.00 |
ACANDF_UNIT3_FRONTROW_TOPFLOOR | 419.40 | 419.40 | 419.40 | 17680.24 | 0.931731 | 1.00 |
ACANDF_UNIT1_BACKROW_TOPFLOOR | 621.52 | 621.52 | 621.52 | 17676.30 | 1.38 | 1.00 |
ACANDF_UNIT2_BACKROW_TOPFLOOR | 359.77 | 359.77 | 359.77 | 14950.81 | 0.799258 | 1.00 |
ACANDF_UNIT3_BACKROW_TOPFLOOR | 415.79 | 415.79 | 415.79 | 17677.16 | 0.923716 | 1.00 |
Design Size Maximum Flow Rate [ft3/min] | |
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 999.35 |
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 296.61 |
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 367.96 |
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 547.27 |
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 275.91 |
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 358.62 |
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 553.27 |
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 290.94 |
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 353.02 |
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 533.10 |
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 272.76 |
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 345.41 |
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 624.18 |
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 362.47 |
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 419.40 |
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 621.52 |
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 359.77 |
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 415.79 |
Design Size Nominal Capacity [Btu/h] | |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 5962.74 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 13069.94 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 15776.19 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 15780.96 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 13070.56 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 15773.46 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 13371.09 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 10654.51 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 13375.09 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 13374.87 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 10654.30 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 13372.10 |
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 17675.33 |
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 14951.93 |
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 17680.24 |
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 17676.30 |
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 14950.81 |
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 17677.16 |
Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 19.59 |
DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 19.59 |
Design Flow Rate [ft3/min] | |
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesPossible Shadow Receivers | |
BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
Possible Shadow Receivers | |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2019-02-14 08:39:44
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 609.420 | 41.586 | 24.688 | 1.934 | 43.520 |
February | 669.000 | 64.462 | 0.000 | 0.000 | 64.462 |
March | 744.000 | 93.282 | 0.000 | 0.000 | 93.282 |
April | 720.000 | 127.380 | 0.000 | 0.000 | 127.380 |
May | 744.000 | 151.463 | 0.000 | 0.000 | 151.463 |
June | 720.000 | 180.927 | 0.000 | 0.000 | 180.927 |
July | 744.000 | 216.515 | 0.000 | 0.000 | 216.515 |
August | 744.000 | 197.194 | 0.000 | 0.000 | 197.194 |
September | 720.000 | 167.896 | 0.000 | 0.000 | 167.896 |
October | 744.000 | 133.538 | 0.000 | 0.000 | 133.538 |
November | 709.417 | 75.584 | 0.000 | 0.000 | 75.584 |
December | 707.992 | 59.677 | 0.000 | 0.000 | 59.677 |
Annual Sum or Average | 8575.829 | 1509.504 | 24.688 | 1.934 | 1511.438 |
Minimum of Months | 609.420 | 41.586 | 0.000 | 0.000 | 43.520 |
Maximum of Months | 744.000 | 216.515 | 24.688 | 1.934 | 216.515 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 720.725 | 30.458 | 30.458 |
February | 18.375 | 0.436 | 552.267 | 16.482 | 16.918 |
March | 70.792 | 1.990 | 498.062 | 12.254 | 14.243 |
April | 219.650 | 8.985 | 251.938 | 4.482 | 13.467 |
May | 305.634 | 13.114 | 143.949 | 1.516 | 14.629 |
June | 502.115 | 30.147 | 42.208 | 0.472 | 30.619 |
July | 690.478 | 49.835 | 0.000 | 0.000 | 49.835 |
August | 573.898 | 38.698 | 18.000 | 0.116 | 38.814 |
September | 445.014 | 27.082 | 48.383 | 0.399 | 27.482 |
October | 264.545 | 11.726 | 234.478 | 3.415 | 15.141 |
November | 42.869 | 1.500 | 539.417 | 15.482 | 16.982 |
December | 9.333 | 0.149 | 659.558 | 21.718 | 21.867 |
Annual Sum or Average | 3142.704 | 183.661 | 3708.985 | 106.793 | 290.455 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 13.467 |
Maximum of Months | 690.478 | 49.835 | 720.725 | 30.458 | 49.835 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.958 | 43.089 | 43.089 |
February | 13.167 | 0.251 | 596.667 | 24.436 | 24.687 |
March | 73.516 | 2.492 | 528.603 | 17.427 | 19.919 |
April | 257.307 | 13.051 | 254.104 | 6.288 | 19.339 |
May | 362.225 | 20.384 | 172.583 | 2.678 | 23.063 |
June | 524.271 | 44.356 | 42.208 | 0.627 | 44.983 |
July | 678.808 | 68.942 | 2.500 | 0.020 | 68.962 |
August | 579.051 | 52.913 | 31.250 | 0.357 | 53.271 |
September | 446.360 | 34.897 | 82.625 | 1.024 | 35.920 |
October | 254.376 | 13.963 | 278.190 | 5.866 | 19.828 |
November | 34.069 | 1.445 | 604.446 | 23.742 | 25.187 |
December | 4.083 | 0.070 | 703.275 | 32.484 | 32.554 |
Annual Sum or Average | 3227.233 | 252.765 | 4033.410 | 158.038 | 410.803 |
Minimum of Months | 0.000 | 0.000 | 2.500 | 0.020 | 19.339 |
Maximum of Months | 678.808 | 68.942 | 736.958 | 43.089 | 68.962 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 70.013 | 70.013 |
February | 0.000 | 0.000 | 651.862 | 42.621 | 42.621 |
March | 30.313 | 1.150 | 627.996 | 31.911 | 33.061 |
April | 178.429 | 9.831 | 349.292 | 12.603 | 22.435 |
May | 278.453 | 19.203 | 232.074 | 4.954 | 24.157 |
June | 475.237 | 44.225 | 68.899 | 1.510 | 45.734 |
July | 656.882 | 67.220 | 4.750 | 0.041 | 67.261 |
August | 520.276 | 49.455 | 48.625 | 0.742 | 50.196 |
September | 359.538 | 25.651 | 125.417 | 2.180 | 27.831 |
October | 123.927 | 6.358 | 407.796 | 13.097 | 19.455 |
November | 4.687 | 0.103 | 679.583 | 41.525 | 41.628 |
December | 0.000 | 0.000 | 744.000 | 55.422 | 55.422 |
Annual Sum or Average | 2627.741 | 223.197 | 4684.293 | 276.619 | 499.816 |
Minimum of Months | 0.000 | 0.000 | 4.750 | 0.041 | 19.455 |
Maximum of Months | 656.882 | 67.220 | 744.000 | 70.013 | 70.013 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 33.778 | 33.778 |
February | 0.000 | 0.000 | 669.437 | 20.747 | 20.747 |
March | 8.292 | 0.170 | 657.150 | 15.227 | 15.397 |
April | 150.255 | 4.585 | 320.882 | 5.488 | 10.073 |
May | 269.152 | 10.072 | 173.891 | 1.708 | 11.779 |
June | 496.729 | 28.428 | 47.875 | 0.489 | 28.917 |
July | 691.766 | 46.782 | 0.000 | 0.000 | 46.782 |
August | 551.523 | 32.229 | 21.083 | 0.137 | 32.365 |
September | 382.752 | 15.858 | 69.950 | 0.557 | 16.416 |
October | 103.024 | 2.883 | 360.544 | 5.197 | 8.079 |
November | 0.000 | 0.000 | 661.938 | 19.405 | 19.405 |
December | 0.000 | 0.000 | 744.000 | 26.075 | 26.075 |
Annual Sum or Average | 2653.493 | 141.007 | 4470.750 | 128.807 | 269.814 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 8.079 |
Maximum of Months | 691.766 | 46.782 | 744.000 | 33.778 | 46.782 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 46.858 | 46.858 |
February | 0.000 | 0.000 | 671.700 | 28.910 | 28.910 |
March | 14.315 | 0.441 | 664.083 | 20.190 | 20.630 |
April | 198.786 | 8.120 | 293.124 | 6.963 | 15.083 |
May | 347.763 | 17.341 | 185.115 | 2.748 | 20.089 |
June | 522.586 | 42.786 | 41.905 | 0.618 | 43.404 |
July | 679.624 | 66.119 | 2.500 | 0.018 | 66.137 |
August | 573.212 | 46.816 | 32.875 | 0.368 | 47.185 |
September | 416.109 | 23.901 | 88.125 | 1.100 | 25.002 |
October | 134.455 | 4.878 | 378.782 | 7.320 | 12.198 |
November | 0.000 | 0.000 | 675.042 | 27.780 | 27.780 |
December | 0.000 | 0.000 | 744.000 | 37.075 | 37.075 |
Annual Sum or Average | 2886.850 | 210.403 | 4521.250 | 179.948 | 390.351 |
Minimum of Months | 0.000 | 0.000 | 2.500 | 0.018 | 12.198 |
Maximum of Months | 679.624 | 66.119 | 744.000 | 46.858 | 66.137 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 3.583 | 0.044 | 703.258 | 52.458 | 52.502 |
February | 42.104 | 1.254 | 511.390 | 27.504 | 28.758 |
March | 106.679 | 5.418 | 459.283 | 20.035 | 25.453 |
April | 276.762 | 17.647 | 229.844 | 6.935 | 24.582 |
May | 360.786 | 25.678 | 129.529 | 2.250 | 27.927 |
June | 528.586 | 48.552 | 37.046 | 0.658 | 49.210 |
July | 691.754 | 71.931 | 0.000 | 0.000 | 71.931 |
August | 578.706 | 57.555 | 21.264 | 0.247 | 57.802 |
September | 448.441 | 38.950 | 56.375 | 0.858 | 39.808 |
October | 271.524 | 17.546 | 240.076 | 6.354 | 23.900 |
November | 52.467 | 2.180 | 528.458 | 27.110 | 29.290 |
December | 14.250 | 0.295 | 646.054 | 37.883 | 38.179 |
Annual Sum or Average | 3375.642 | 287.051 | 3562.577 | 182.290 | 469.340 |
Minimum of Months | 3.583 | 0.044 | 0.000 | 0.000 | 23.900 |
Maximum of Months | 691.754 | 71.931 | 703.258 | 52.458 | 71.931 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 694.667 | 24.907 | 24.907 |
February | 34.800 | 0.665 | 479.037 | 12.627 | 13.292 |
March | 99.821 | 2.775 | 420.780 | 8.862 | 11.637 |
April | 276.276 | 11.221 | 177.475 | 2.586 | 13.807 |
May | 374.253 | 16.012 | 76.751 | 0.675 | 16.687 |
June | 568.674 | 32.763 | 23.875 | 0.164 | 32.928 |
July | 727.225 | 51.830 | 0.000 | 0.000 | 51.830 |
August | 628.795 | 40.681 | 6.000 | 0.019 | 40.700 |
September | 510.754 | 29.432 | 24.056 | 0.151 | 29.583 |
October | 314.353 | 13.846 | 153.482 | 1.925 | 15.772 |
November | 55.202 | 1.890 | 478.833 | 12.097 | 13.987 |
December | 19.583 | 0.285 | 604.750 | 17.151 | 17.436 |
Annual Sum or Average | 3609.736 | 201.400 | 3139.706 | 81.164 | 282.565 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 11.637 |
Maximum of Months | 727.225 | 51.830 | 694.667 | 24.907 | 51.830 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 720.046 | 36.691 | 36.691 |
February | 17.833 | 0.371 | 550.608 | 19.738 | 20.109 |
March | 99.864 | 3.331 | 460.729 | 13.368 | 16.699 |
April | 304.952 | 15.560 | 190.392 | 4.062 | 19.622 |
May | 406.166 | 23.588 | 109.958 | 1.477 | 25.065 |
June | 571.315 | 46.976 | 20.125 | 0.270 | 47.246 |
July | 705.398 | 70.545 | 0.500 | 0.001 | 70.546 |
August | 615.122 | 54.599 | 15.125 | 0.139 | 54.738 |
September | 488.296 | 37.013 | 49.275 | 0.528 | 37.541 |
October | 297.735 | 15.909 | 215.542 | 3.926 | 19.835 |
November | 43.058 | 1.680 | 554.483 | 19.557 | 21.237 |
December | 6.917 | 0.104 | 673.971 | 27.028 | 27.132 |
Annual Sum or Average | 3556.656 | 269.675 | 3560.754 | 126.787 | 396.462 |
Minimum of Months | 0.000 | 0.000 | 0.500 | 0.001 | 16.699 |
Maximum of Months | 705.398 | 70.545 | 720.046 | 36.691 | 70.546 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 61.994 | 61.994 |
February | 0.000 | 0.000 | 634.658 | 36.198 | 36.198 |
March | 43.604 | 1.437 | 572.417 | 25.824 | 27.261 |
April | 217.225 | 11.651 | 279.250 | 8.813 | 20.464 |
May | 327.633 | 21.804 | 157.683 | 2.869 | 24.673 |
June | 521.152 | 46.517 | 42.337 | 0.762 | 47.279 |
July | 691.448 | 69.043 | 0.000 | 0.000 | 69.043 |
August | 561.092 | 51.042 | 28.533 | 0.340 | 51.381 |
September | 399.813 | 27.390 | 77.247 | 1.281 | 28.670 |
October | 151.229 | 7.049 | 348.240 | 9.822 | 16.871 |
November | 6.250 | 0.105 | 658.146 | 35.927 | 36.032 |
December | 0.000 | 0.000 | 744.000 | 48.518 | 48.518 |
Annual Sum or Average | 2919.446 | 236.037 | 4286.512 | 232.348 | 468.385 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 16.871 |
Maximum of Months | 691.448 | 69.043 | 744.000 | 61.994 | 69.043 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 28.802 | 28.802 |
February | 0.000 | 0.000 | 658.850 | 16.644 | 16.644 |
March | 16.417 | 0.271 | 572.767 | 11.224 | 11.495 |
April | 204.245 | 6.435 | 228.125 | 3.186 | 9.621 |
May | 342.067 | 12.973 | 89.125 | 0.741 | 13.714 |
June | 562.456 | 31.241 | 24.063 | 0.155 | 31.396 |
July | 727.000 | 49.049 | 0.000 | 0.000 | 49.049 |
August | 613.714 | 34.509 | 6.500 | 0.022 | 34.531 |
September | 458.444 | 18.270 | 35.263 | 0.232 | 18.501 |
October | 148.066 | 3.853 | 262.479 | 3.248 | 7.101 |
November | 0.000 | 0.000 | 617.917 | 15.905 | 15.905 |
December | 0.000 | 0.000 | 741.875 | 21.612 | 21.612 |
Annual Sum or Average | 3072.409 | 156.600 | 3980.963 | 101.771 | 258.371 |
Minimum of Months | 0.000 | 0.000 | 0.000 | 0.000 | 7.101 |
Maximum of Months | 727.000 | 49.049 | 744.000 | 28.802 | 49.049 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 41.177 | 41.177 |
February | 0.000 | 0.000 | 669.625 | 24.424 | 24.424 |
March | 19.865 | 0.580 | 593.863 | 15.624 | 16.205 |
April | 249.026 | 10.197 | 219.219 | 4.467 | 14.664 |
May | 391.602 | 20.616 | 114.500 | 1.538 | 22.154 |
June | 567.630 | 45.493 | 19.750 | 0.273 | 45.767 |
July | 705.333 | 67.972 | 0.250 | 0.001 | 67.973 |
August | 608.129 | 48.797 | 15.500 | 0.146 | 48.943 |
September | 462.583 | 26.181 | 53.750 | 0.582 | 26.763 |
October | 166.208 | 5.817 | 290.792 | 5.119 | 10.936 |
November | 0.000 | 0.000 | 655.336 | 23.859 | 23.859 |
December | 0.000 | 0.000 | 744.000 | 32.217 | 32.217 |
Annual Sum or Average | 3170.375 | 225.654 | 4120.585 | 149.428 | 375.081 |
Minimum of Months | 0.000 | 0.000 | 0.250 | 0.001 | 10.936 |
Maximum of Months | 705.333 | 67.972 | 744.000 | 41.177 | 67.973 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 736.738 | 75.740 | 75.740 |
February | 11.667 | 0.324 | 596.108 | 43.603 | 43.927 |
March | 66.917 | 3.355 | 573.333 | 33.351 | 36.707 |
April | 215.081 | 15.328 | 321.527 | 13.374 | 28.702 |
May | 297.821 | 24.969 | 232.208 | 5.919 | 30.888 |
June | 472.994 | 51.103 | 77.333 | 1.898 | 53.001 |
July | 653.175 | 78.311 | 6.250 | 0.071 | 78.382 |
August | 528.141 | 60.246 | 52.875 | 0.979 | 61.226 |
September | 386.128 | 37.386 | 128.583 | 2.750 | 40.137 |
October | 199.914 | 13.945 | 351.925 | 13.098 | 27.042 |
November | 26.708 | 1.156 | 631.333 | 43.232 | 44.388 |
December | 1.000 | 0.006 | 717.254 | 58.333 | 58.339 |
Annual Sum or Average | 2859.546 | 286.129 | 4425.468 | 292.349 | 578.479 |
Minimum of Months | 0.000 | 0.000 | 6.250 | 0.071 | 27.042 |
Maximum of Months | 653.175 | 78.311 | 736.738 | 75.740 | 78.382 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 740.479 | 41.513 | 41.513 |
February | 7.958 | 0.089 | 610.383 | 23.419 | 23.508 |
March | 51.336 | 1.438 | 557.625 | 17.379 | 18.817 |
April | 208.565 | 9.786 | 279.992 | 6.386 | 16.172 |
May | 301.280 | 16.006 | 190.481 | 2.514 | 18.520 |
June | 495.757 | 35.727 | 53.972 | 0.762 | 36.489 |
July | 683.740 | 58.475 | 2.503 | 0.004 | 58.480 |
August | 559.973 | 43.696 | 31.500 | 0.273 | 43.969 |
September | 417.661 | 28.072 | 83.911 | 0.923 | 28.995 |
October | 220.559 | 10.316 | 293.385 | 5.641 | 15.956 |
November | 33.521 | 1.017 | 612.196 | 22.594 | 23.611 |
December | 0.625 | 0.001 | 710.429 | 30.903 | 30.905 |
Annual Sum or Average | 2980.976 | 204.622 | 4166.857 | 152.313 | 356.935 |
Minimum of Months | 0.000 | 0.000 | 2.503 | 0.004 | 15.956 |
Maximum of Months | 683.740 | 58.475 | 740.479 | 41.513 | 58.480 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 52.285 | 52.285 |
February | 2.083 | 0.012 | 625.879 | 30.328 | 30.340 |
March | 51.190 | 1.757 | 572.582 | 21.600 | 23.357 |
April | 237.769 | 13.150 | 272.750 | 7.503 | 20.653 |
May | 353.814 | 22.458 | 182.267 | 3.252 | 25.710 |
June | 522.840 | 49.182 | 48.899 | 0.761 | 49.943 |
July | 683.130 | 76.900 | 3.125 | 0.021 | 76.921 |
August | 578.477 | 57.052 | 34.250 | 0.437 | 57.490 |
September | 430.156 | 35.207 | 98.677 | 1.461 | 36.668 |
October | 218.415 | 12.163 | 319.892 | 7.716 | 19.879 |
November | 27.475 | 0.984 | 647.042 | 29.940 | 30.925 |
December | 0.000 | 0.000 | 724.021 | 40.360 | 40.360 |
Annual Sum or Average | 3105.348 | 268.867 | 4273.383 | 195.664 | 464.530 |
Minimum of Months | 0.000 | 0.000 | 3.125 | 0.021 | 19.879 |
Maximum of Months | 683.130 | 76.900 | 744.000 | 52.285 | 76.921 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 82.484 | 82.484 |
February | 0.000 | 0.000 | 660.554 | 50.537 | 50.537 |
March | 34.577 | 1.311 | 628.575 | 37.514 | 38.825 |
April | 190.496 | 12.207 | 348.417 | 14.542 | 26.749 |
May | 287.747 | 23.584 | 239.229 | 6.111 | 29.695 |
June | 473.236 | 50.885 | 76.525 | 1.881 | 52.765 |
July | 655.743 | 77.588 | 6.417 | 0.065 | 77.653 |
August | 520.785 | 57.059 | 56.576 | 1.012 | 58.071 |
September | 353.385 | 29.548 | 146.875 | 3.127 | 32.675 |
October | 126.073 | 7.183 | 430.792 | 16.336 | 23.519 |
November | 3.771 | 0.070 | 686.625 | 50.138 | 50.208 |
December | 0.000 | 0.000 | 744.000 | 66.211 | 66.211 |
Annual Sum or Average | 2645.812 | 259.433 | 4768.584 | 329.960 | 589.393 |
Minimum of Months | 0.000 | 0.000 | 6.417 | 0.065 | 23.519 |
Maximum of Months | 655.743 | 77.588 | 744.000 | 82.484 | 82.484 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 45.953 | 45.953 |
February | 0.000 | 0.000 | 669.400 | 28.304 | 28.304 |
March | 11.500 | 0.340 | 659.334 | 20.485 | 20.825 |
April | 171.706 | 7.135 | 324.500 | 7.260 | 14.395 |
May | 289.995 | 14.852 | 197.095 | 2.605 | 17.457 |
June | 497.477 | 35.690 | 54.681 | 0.756 | 36.446 |
July | 686.106 | 57.811 | 1.500 | 0.001 | 57.813 |
August | 549.135 | 40.635 | 32.813 | 0.280 | 40.915 |
September | 371.560 | 20.326 | 100.617 | 1.112 | 21.437 |
October | 107.425 | 3.996 | 391.708 | 7.818 | 11.814 |
November | 0.000 | 0.000 | 674.875 | 27.232 | 27.232 |
December | 0.000 | 0.000 | 744.000 | 36.180 | 36.180 |
Annual Sum or Average | 2684.906 | 180.784 | 4594.522 | 177.985 | 358.770 |
Minimum of Months | 0.000 | 0.000 | 1.500 | 0.001 | 11.814 |
Maximum of Months | 686.106 | 57.811 | 744.000 | 45.953 | 57.813 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportAIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRIC ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRIC ENERGY [kWh] | |
January | 0.000 | 0.000 | 744.000 | 56.295 | 56.295 |
February | 0.000 | 0.000 | 671.700 | 34.832 | 34.832 |
March | 14.600 | 0.576 | 662.733 | 24.382 | 24.958 |
April | 204.246 | 10.182 | 313.896 | 8.127 | 18.309 |
May | 347.498 | 21.278 | 188.292 | 3.317 | 24.595 |
June | 522.661 | 49.092 | 47.875 | 0.748 | 49.841 |
July | 684.255 | 76.153 | 3.042 | 0.019 | 76.172 |
August | 575.716 | 54.013 | 34.375 | 0.443 | 54.456 |
September | 404.930 | 27.379 | 103.883 | 1.537 | 28.917 |
October | 125.166 | 5.595 | 409.292 | 9.552 | 15.147 |
November | 0.000 | 0.000 | 688.233 | 34.169 | 34.169 |
December | 0.000 | 0.000 | 744.000 | 45.161 | 45.161 |
Annual Sum or Average | 2879.071 | 244.268 | 4611.321 | 218.584 | 462.852 |
Minimum of Months | 0.000 | 0.000 | 3.042 | 0.019 | 15.147 |
Maximum of Months | 684.255 | 76.153 | 744.000 | 56.295 | 76.172 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 30.97 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 2.63 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 30.97 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3602.04 | 0.00 |
February | 0.00 | 2158.09 | 0.00 |
March | 0.00 | 1449.16 | 0.00 |
April | 0.00 | 547.75 | 0.00 |
May | 0.00 | 179.25 | 0.00 |
June | 0.00 | 57.68 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 13.77 | 0.00 |
September | 0.00 | 48.79 | 0.00 |
October | 0.00 | 403.82 | 0.00 |
November | 0.00 | 1891.93 | 0.00 |
December | 0.00 | 2568.43 | 0.00 |
Annual Sum or Average | 0.00 | 1072.66 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 3602.04 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4958.27 | 0.00 |
February | 0.00 | 3113.08 | 0.00 |
March | 0.00 | 2005.33 | 0.00 |
April | 0.00 | 747.72 | 0.00 |
May | 0.00 | 308.17 | 0.00 |
June | 0.00 | 74.53 | 0.00 |
July | 0.00 | 2.30 | 0.00 |
August | 0.00 | 41.10 | 0.00 |
September | 0.00 | 121.72 | 0.00 |
October | 0.00 | 674.95 | 0.00 |
November | 0.00 | 2823.06 | 0.00 |
December | 0.00 | 3737.94 | 0.00 |
Annual Sum or Average | 0.00 | 1544.51 | 0.00 |
Minimum of Months | 0.00 | 2.30 | 0.00 |
Maximum of Months | 0.00 | 4958.27 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5418.44 | 0.00 |
February | 0.00 | 3651.89 | 0.00 |
March | 0.00 | 2469.64 | 0.00 |
April | 0.00 | 1007.91 | 0.00 |
May | 0.00 | 383.40 | 0.00 |
June | 0.00 | 120.73 | 0.00 |
July | 0.00 | 3.21 | 0.00 |
August | 0.00 | 57.39 | 0.00 |
September | 0.00 | 174.36 | 0.00 |
October | 0.00 | 1013.58 | 0.00 |
November | 0.00 | 3320.83 | 0.00 |
December | 0.00 | 4289.21 | 0.00 |
Annual Sum or Average | 0.00 | 1818.22 | 0.00 |
Minimum of Months | 0.00 | 3.21 | 0.00 |
Maximum of Months | 0.00 | 5418.44 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4294.64 | 0.00 |
February | 0.00 | 2920.51 | 0.00 |
March | 0.00 | 1935.98 | 0.00 |
April | 0.00 | 720.98 | 0.00 |
May | 0.00 | 217.11 | 0.00 |
June | 0.00 | 64.21 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 17.37 | 0.00 |
September | 0.00 | 73.24 | 0.00 |
October | 0.00 | 660.73 | 0.00 |
November | 0.00 | 2549.54 | 0.00 |
December | 0.00 | 3315.24 | 0.00 |
Annual Sum or Average | 0.00 | 1390.92 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4294.64 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5531.40 | 0.00 |
February | 0.00 | 3778.34 | 0.00 |
March | 0.00 | 2383.31 | 0.00 |
April | 0.00 | 849.40 | 0.00 |
May | 0.00 | 324.34 | 0.00 |
June | 0.00 | 75.34 | 0.00 |
July | 0.00 | 2.15 | 0.00 |
August | 0.00 | 43.50 | 0.00 |
September | 0.00 | 134.24 | 0.00 |
October | 0.00 | 864.12 | 0.00 |
November | 0.00 | 3388.64 | 0.00 |
December | 0.00 | 4376.62 | 0.00 |
Annual Sum or Average | 0.00 | 1804.14 | 0.00 |
Minimum of Months | 0.00 | 2.15 | 0.00 |
Maximum of Months | 0.00 | 5531.40 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3402.54 | 0.00 |
February | 0.00 | 1975.09 | 0.00 |
March | 0.00 | 1299.50 | 0.00 |
April | 0.00 | 464.78 | 0.00 |
May | 0.00 | 145.92 | 0.00 |
June | 0.00 | 44.09 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 16.01 | 0.00 |
September | 0.00 | 57.49 | 0.00 |
October | 0.00 | 412.11 | 0.00 |
November | 0.00 | 1817.01 | 0.00 |
December | 0.00 | 2457.20 | 0.00 |
Annual Sum or Average | 0.00 | 1004.21 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 3402.54 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 2448.07 | 0.00 |
February | 0.00 | 1374.03 | 0.00 |
March | 0.00 | 871.01 | 0.00 |
April | 0.00 | 262.64 | 0.00 |
May | 0.00 | 66.33 | 0.00 |
June | 0.00 | 16.69 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 1.90 | 0.00 |
September | 0.00 | 15.34 | 0.00 |
October | 0.00 | 189.24 | 0.00 |
November | 0.00 | 1228.61 | 0.00 |
December | 0.00 | 1685.69 | 0.00 |
Annual Sum or Average | 0.00 | 677.54 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 2448.07 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3731.04 | 0.00 |
February | 0.00 | 2222.12 | 0.00 |
March | 0.00 | 1359.37 | 0.00 |
April | 0.00 | 426.83 | 0.00 |
May | 0.00 | 150.18 | 0.00 |
June | 0.00 | 28.42 | 0.00 |
July | 0.00 | 0.09 | 0.00 |
August | 0.00 | 14.17 | 0.00 |
September | 0.00 | 55.49 | 0.00 |
October | 0.00 | 399.25 | 0.00 |
November | 0.00 | 2055.02 | 0.00 |
December | 0.00 | 2748.44 | 0.00 |
Annual Sum or Average | 0.00 | 1094.99 | 0.00 |
Minimum of Months | 0.00 | 0.09 | 0.00 |
Maximum of Months | 0.00 | 3731.04 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4174.43 | 0.00 |
February | 0.00 | 2698.59 | 0.00 |
March | 0.00 | 1738.89 | 0.00 |
April | 0.00 | 613.22 | 0.00 |
May | 0.00 | 193.19 | 0.00 |
June | 0.00 | 53.02 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 22.88 | 0.00 |
September | 0.00 | 89.10 | 0.00 |
October | 0.00 | 661.40 | 0.00 |
November | 0.00 | 2499.82 | 0.00 |
December | 0.00 | 3267.02 | 0.00 |
Annual Sum or Average | 0.00 | 1328.79 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 4174.43 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 3019.43 | 0.00 |
February | 0.00 | 1931.86 | 0.00 |
March | 0.00 | 1176.67 | 0.00 |
April | 0.00 | 345.10 | 0.00 |
May | 0.00 | 77.67 | 0.00 |
June | 0.00 | 16.84 | 0.00 |
July | 0.00 | 0.00 | 0.00 |
August | 0.00 | 2.34 | 0.00 |
September | 0.00 | 25.10 | 0.00 |
October | 0.00 | 340.55 | 0.00 |
November | 0.00 | 1722.94 | 0.00 |
December | 0.00 | 2265.67 | 0.00 |
Annual Sum or Average | 0.00 | 906.15 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 3019.43 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4278.40 | 0.00 |
February | 0.00 | 2809.65 | 0.00 |
March | 0.00 | 1623.41 | 0.00 |
April | 0.00 | 479.64 | 0.00 |
May | 0.00 | 159.83 | 0.00 |
June | 0.00 | 29.35 | 0.00 |
July | 0.00 | 0.06 | 0.00 |
August | 0.00 | 15.13 | 0.00 |
September | 0.00 | 62.52 | 0.00 |
October | 0.00 | 531.85 | 0.00 |
November | 0.00 | 2561.61 | 0.00 |
December | 0.00 | 3347.46 | 0.00 |
Annual Sum or Average | 0.00 | 1318.64 | 0.00 |
Minimum of Months | 0.00 | 0.06 | 0.00 |
Maximum of Months | 0.00 | 4278.40 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5756.44 | 0.00 |
February | 0.00 | 3669.00 | 0.00 |
March | 0.00 | 2534.79 | 0.00 |
April | 0.00 | 1050.35 | 0.00 |
May | 0.00 | 449.88 | 0.00 |
June | 0.00 | 149.05 | 0.00 |
July | 0.00 | 5.37 | 0.00 |
August | 0.00 | 74.43 | 0.00 |
September | 0.00 | 216.00 | 0.00 |
October | 0.00 | 995.47 | 0.00 |
November | 0.00 | 3395.27 | 0.00 |
December | 0.00 | 4433.43 | 0.00 |
Annual Sum or Average | 0.00 | 1887.11 | 0.00 |
Minimum of Months | 0.00 | 5.37 | 0.00 |
Maximum of Months | 0.00 | 5756.44 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 4595.96 | 0.00 |
February | 0.00 | 2870.60 | 0.00 |
March | 0.00 | 1924.06 | 0.00 |
April | 0.00 | 730.63 | 0.00 |
May | 0.00 | 278.36 | 0.00 |
June | 0.00 | 87.21 | 0.00 |
July | 0.00 | 0.50 | 0.00 |
August | 0.00 | 30.27 | 0.00 |
September | 0.00 | 105.60 | 0.00 |
October | 0.00 | 624.47 | 0.00 |
November | 0.00 | 2584.79 | 0.00 |
December | 0.00 | 3421.37 | 0.00 |
Annual Sum or Average | 0.00 | 1432.19 | 0.00 |
Minimum of Months | 0.00 | 0.50 | 0.00 |
Maximum of Months | 0.00 | 4595.96 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5915.59 | 0.00 |
February | 0.00 | 3799.02 | 0.00 |
March | 0.00 | 2443.82 | 0.00 |
April | 0.00 | 877.21 | 0.00 |
May | 0.00 | 367.94 | 0.00 |
June | 0.00 | 88.93 | 0.00 |
July | 0.00 | 2.33 | 0.00 |
August | 0.00 | 49.49 | 0.00 |
September | 0.00 | 170.84 | 0.00 |
October | 0.00 | 872.97 | 0.00 |
November | 0.00 | 3500.44 | 0.00 |
December | 0.00 | 4566.45 | 0.00 |
Annual Sum or Average | 0.00 | 1880.20 | 0.00 |
Minimum of Months | 0.00 | 2.33 | 0.00 |
Maximum of Months | 0.00 | 5915.59 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6296.17 | 0.00 |
February | 0.00 | 4270.89 | 0.00 |
March | 0.00 | 2863.52 | 0.00 |
April | 0.00 | 1147.02 | 0.00 |
May | 0.00 | 466.45 | 0.00 |
June | 0.00 | 148.34 | 0.00 |
July | 0.00 | 4.97 | 0.00 |
August | 0.00 | 77.28 | 0.00 |
September | 0.00 | 246.67 | 0.00 |
October | 0.00 | 1246.99 | 0.00 |
November | 0.00 | 3954.72 | 0.00 |
December | 0.00 | 5054.02 | 0.00 |
Annual Sum or Average | 0.00 | 2139.12 | 0.00 |
Minimum of Months | 0.00 | 4.97 | 0.00 |
Maximum of Months | 0.00 | 6296.17 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 5125.27 | 0.00 |
February | 0.00 | 3495.13 | 0.00 |
March | 0.00 | 2284.72 | 0.00 |
April | 0.00 | 836.72 | 0.00 |
May | 0.00 | 290.56 | 0.00 |
June | 0.00 | 87.17 | 0.00 |
July | 0.00 | 0.13 | 0.00 |
August | 0.00 | 31.27 | 0.00 |
September | 0.00 | 128.14 | 0.00 |
October | 0.00 | 871.92 | 0.00 |
November | 0.00 | 3138.47 | 0.00 |
December | 0.00 | 4035.24 | 0.00 |
Annual Sum or Average | 0.00 | 1686.00 | 0.00 |
Minimum of Months | 0.00 | 0.13 | 0.00 |
Maximum of Months | 0.00 | 5125.27 | 0.00 |
Report: COILLOADS
For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Btu/h] | COOLING COIL TOTAL COOLING RATE [Invalid/Undefined] | |
January | 0.00 | 6423.49 | 0.00 |
February | 0.00 | 4400.35 | 0.00 |
March | 0.00 | 2782.14 | 0.00 |
April | 0.00 | 958.23 | 0.00 |
May | 0.00 | 378.51 | 0.00 |
June | 0.00 | 88.23 | 0.00 |
July | 0.00 | 2.16 | 0.00 |
August | 0.00 | 50.59 | 0.00 |
September | 0.00 | 181.28 | 0.00 |
October | 0.00 | 1089.87 | 0.00 |
November | 0.00 | 4028.77 | 0.00 |
December | 0.00 | 5153.11 | 0.00 |
Annual Sum or Average | 0.00 | 2118.30 | 0.00 |
Minimum of Months | 0.00 | 2.16 | 0.00 |
Maximum of Months | 0.00 | 6423.49 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.24 |
February | 0.00 | 0.00 | 0.41 |
March | 0.00 | 0.00 | 0.53 |
April | 0.00 | 0.00 | 0.74 |
May | 0.00 | 0.00 | 0.85 |
June | 0.00 | 0.00 | 1.02 |
July | 0.00 | 0.00 | 1.17 |
August | 0.00 | 0.00 | 1.07 |
September | 0.00 | 0.00 | 0.96 |
October | 0.00 | 0.00 | 0.75 |
November | 0.00 | 0.00 | 0.44 |
December | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.00 | 0.24 |
Maximum of Months | 0.00 | 0.00 | 1.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.27 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.28 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.10 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.35 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.03 |
May | 0.00 | 0.00 | 0.05 |
June | 0.00 | 0.00 | 0.16 |
July | 0.00 | 0.00 | 0.25 |
August | 0.00 | 0.00 | 0.17 |
September | 0.00 | 0.00 | 0.09 |
October | 0.00 | 0.00 | 0.01 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.24 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.25 |
September | 0.00 | 0.00 | 0.13 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.01 |
March | 0.00 | 0.00 | 0.03 |
April | 0.00 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.14 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.18 |
July | 0.00 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.22 |
September | 0.00 | 0.00 | 0.17 |
October | 0.00 | 0.00 | 0.08 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.09 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.26 |
July | 0.00 | 0.00 | 0.38 |
August | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.00 | 0.21 |
October | 0.00 | 0.00 | 0.09 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.36 |
August | 0.00 | 0.00 | 0.27 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.07 |
June | 0.00 | 0.00 | 0.17 |
July | 0.00 | 0.00 | 0.26 |
August | 0.00 | 0.00 | 0.18 |
September | 0.00 | 0.00 | 0.10 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.07 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.25 |
July | 0.00 | 0.00 | 0.37 |
August | 0.00 | 0.00 | 0.26 |
September | 0.00 | 0.00 | 0.14 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.02 |
April | 0.00 | 0.00 | 0.08 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.32 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.07 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.13 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.05 |
May | 0.00 | 0.00 | 0.09 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.23 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.09 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.12 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.20 |
October | 0.00 | 0.00 | 0.06 |
November | 0.00 | 0.00 | 0.01 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.01 |
April | 0.00 | 0.00 | 0.07 |
May | 0.00 | 0.00 | 0.13 |
June | 0.00 | 0.00 | 0.28 |
July | 0.00 | 0.00 | 0.40 |
August | 0.00 | 0.00 | 0.30 |
September | 0.00 | 0.00 | 0.16 |
October | 0.00 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.12 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.40 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.04 |
May | 0.00 | 0.00 | 0.08 |
June | 0.00 | 0.00 | 0.20 |
July | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.21 |
September | 0.00 | 0.00 | 0.11 |
October | 0.00 | 0.00 | 0.02 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.08 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportHEATING COIL TOTAL HEATING RATE [Invalid/Undefined] | HEATING COIL AIR HEATING RATE [Invalid/Undefined] | COOLING COIL TOTAL COOLING RATE [ton] | |
January | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.06 |
May | 0.00 | 0.00 | 0.11 |
June | 0.00 | 0.00 | 0.27 |
July | 0.00 | 0.00 | 0.41 |
August | 0.00 | 0.00 | 0.29 |
September | 0.00 | 0.00 | 0.15 |
October | 0.00 | 0.00 | 0.03 |
November | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.11 |
Minimum of Months | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.41 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2019-02-14 08:39:44
Custom Monthly ReportWATER HEATER TOTAL DEMAND RATE [Invalid/Undefined] | WATER HEATER TOTAL DEMAND ENERGY [Invalid/Undefined] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
January | 0.00 | 0.00 | 1814.98 | 1351.30 |
February | 0.00 | 0.00 | 1840.26 | 1237.53 |
March | 0.00 | 0.00 | 1803.09 | 1342.45 |
April | 0.00 | 0.00 | 1711.97 | 1233.49 |
May | 0.00 | 0.00 | 1583.25 | 1178.77 |
June | 0.00 | 0.00 | 1462.33 | 1053.63 |
July | 0.00 | 0.00 | 1373.80 | 1022.83 |
August | 0.00 | 0.00 | 1342.04 | 999.18 |
September | 0.00 | 0.00 | 1382.30 | 995.96 |
October | 0.00 | 0.00 | 1477.08 | 1099.73 |
November | 0.00 | 0.00 | 1603.37 | 1155.25 |
December | 0.00 | 0.00 | 1727.83 | 1286.41 |
Annual Sum or Average | 0.00 | 0.00 | 1592.08 | 13956.54 |
Minimum of Months | 0.00 | 0.00 | 1342.04 | 995.96 |
Maximum of Months | 0.00 | 0.00 | 1840.26 | 1351.30 |